Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280
Simulation Timestamp: 2023-10-16 09:04:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 29599.27 | 639.01 | 639.01 |
Net Site Energy | 29599.27 | 639.01 | 639.01 |
Total Source Energy | 88420.72 | 1908.89 | 1908.89 |
Net Source Energy | 88420.72 | 1908.89 | 1908.89 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1805.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3028.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2743.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 447.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2256.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 482.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 898.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3225.44 |
Humidification | 17.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
Heat Recovery | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 748.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 27045.18 | 2554.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5512.29 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1805.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3028.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2743.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 447.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2256.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 482.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 898.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3225.44 |
Humidification | General | 17.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
Heat Recovery | General | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 748.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1805.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3028.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2743.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 447.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2256.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 482.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 898.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3225.44 |
Humidification | Unassigned | 17.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.68 |
Heat Recovery | Unassigned | 41.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 748.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.31 | 55.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 370.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 583.87 | 55.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 144.31 | 55.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Other | 370.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 583.87 | 55.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.12 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 27045.185 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 27045.185 | 100.00 |
Total On-Site and Utility Electric Sources | 27045.185 | 100.00 |
Total Electricity End Uses | 27045.185 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | 0.00 |
Air to Air Heat Recovery for Cooling | 114.27 | 6.28 |
Air to Air Heat Recovery for Heating | 1706.35 | 93.72 |
High-Temperature Geothermal* | 0.00 | 0.00 |
Solar Water Thermal | 0.00 | 0.00 |
Solar Air Thermal | 0.00 | 0.00 |
Total On-Site Thermal Sources | 1820.62 | 100.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 5512.29 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 5512.29 | 100.00 |
Total Water End Uses | 5512.29 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 115.67 |
Time Setpoint Not Met During Occupied Cooling | 199.83 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5936.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Latitude [deg] | 42.93 |
Longitude [deg] | -78.7 |
Elevation [m] | 215.00 |
Time Zone | -5.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 07-AUG-15:30 | 02-JAN-05:10 | - | - | - | - | - | - | - | - | - | - | 04-AUG-15:00 |
Heating | 0.00 | 1680702.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 463029.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 83146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 202746.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 63278.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 87066.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1927706.14 | 1686398.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1680702.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 463029.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 202746.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 63278.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 87066.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 5695.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1957.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 9590.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8689.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1418.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 7147.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1528.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2846.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 56.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 130.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 811.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 85652.10 | 2768.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 207.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 154.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 61.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1849.12 | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 42.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 207.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 154.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 33.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 61.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 1.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 2.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1849.12 | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.35 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.491025 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.69 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.477539 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.82 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.70 | 0.333882 | 0.335000 | 1.91 | 0.890353 | 0.500000 | 0.001141 | 0.000214 | 1.91 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 53.40 | 0.356216 | 0.349000 | 18.64 | 0.949909 | 0.500000 | 0.001070 | 0.004489 | 18.64 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 5.29 | 0.359634 | 0.361000 | 1.91 | 0.959023 | 0.500000 | 0.001059 | 0.000877 | 3.06 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.906477 | 0.263460 | 0.264000 | 0.239310 | 0.702561 | 0.500000 | 0.001446 | 0.000155 | 0.542734 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.09 | 0.141058 | 0.200000 | 0.218216 | 0.376154 | 0.500000 | 0.002701 | 0.000106 | 0.369335 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.31 | 0.182435 | 0.200000 | 0.261820 | 0.486493 | 0.500000 | 0.002088 | 0.000170 | 0.594032 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.37 | 0.112621 | 0.200000 | 0.273316 | 0.300321 | 0.500000 | 0.003383 | 0.000084 | 0.294994 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 8.48 | 0.281598 | 0.276000 | 2.34 | 0.750927 | 0.500000 | 0.001353 | 0.002415 | 8.45 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 11.48 | 0.134071 | 0.200000 | 2.30 | 0.357522 | 0.500000 | 0.002842 | 0.001584 | 5.54 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 12.86 | 0.185671 | 0.200000 | 2.57 | 0.495122 | 0.500000 | 0.002052 | 0.002415 | 8.45 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 12.12 | 0.126976 | 0.200000 | 2.42 | 0.338602 | 0.500000 | 0.003001 | 0.001544 | 5.40 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.09 | 0.218401 | 0.247000 | 0.270093 | 0.582404 | 0.500000 | 0.001744 | 0.000312 | 1.09 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.16 | 0.132578 | 0.200000 | 0.232173 | 0.353541 | 0.500000 | 0.002874 | 0.000204 | 0.714592 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.40 | 0.170412 | 0.200000 | 0.280292 | 0.454433 | 0.500000 | 0.002236 | 0.000312 | 1.09 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.29 | 0.118880 | 0.200000 | 0.258924 | 0.317014 | 0.500000 | 0.003205 | 0.000202 | 0.708136 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 24492.97 | 0.000214 | 509.18 |
CORE_MID VAV BOX REHEAT COIL | 513142.38 | 0.004489 | 12632.39 |
CORE_TOP VAV BOX REHEAT COIL | 100197.92 | 0.000877 | 2644.57 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 17745.64 | 0.000155 | 468.08 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 12074.57 | 0.000106 | 318.48 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 19419.68 | 0.000170 | 512.20 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9648.97 | 0.000084 | 254.56 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 275992.80 | 0.002415 | 7276.65 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 181088.97 | 0.001584 | 4774.40 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 275994.35 | 0.002415 | 7276.69 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 176473.84 | 0.001544 | 4652.78 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 35705.74 | 0.000312 | 941.24 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 23332.92 | 0.000204 | 615.08 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 35706.01 | 0.000312 | 941.25 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 23122.21 | 0.000202 | 609.52 |
VAV_BOT WITH REHEAT HEATING COIL | 84865.73 | 0.000742 | 1327.54 |
VAV_MID WITH REHEAT HEATING COIL | 869378.30 | 0.007606 | 13371.48 |
VAV_TOP WITH REHEAT HEATING COIL | 85698.23 | 0.000750 | 1339.91 |
CAV_BAS HEATING COIL | 275622.10 | 0.002411 | 5977.74 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.18 | 2.90 | 10.37 | 2.90 | 9.24 | 9.24 | 0.300000 | 0.313947 | 9.24 |
VAV_MID WITH REHEAT | 49.17 | 28.27 | 98.34 | 42.16 | 85.49 | 85.49 | 0.300000 | 0.493213 | 85.49 |
VAV_TOP WITH REHEAT | 5.12 | 2.95 | 10.24 | 6.67 | 9.29 | 9.29 | 0.300000 | 0.717686 | 9.29 |
CAV_BAS | 5.35 | 5.35 | 5.35 | 5.35 | 5.35 | 5.35 | 1.00 | 1.00 | 5.35 |
AIRLOOP DATACENTER BASEMENT | 21.82 | 21.82 | 21.82 | 21.82 | 21.82 | 21.82 | 1.00 | 0.999989 | 21.82 |
AIRLOOP DATACENTER BOT | 0.491025 | 0.491025 | 0.491025 | 0.491025 | 0.491025 | 0.491025 | 1.00 | 1.00 | 0.491025 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 4.69 | 1.00 | 1.00 | 4.69 |
AIRLOOP DATACENTER TOP | 0.477539 | 0.477539 | 0.477539 | 0.477539 | 0.477539 | 0.477539 | 1.00 | 1.00 | 0.477539 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 9.24 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 85.49 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 9.29 | |
CAV_BAS_OA_CONTROLLER | 5.35 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.82 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.491025 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.69 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.477539 | 0.015632 |
Design Size Nominal Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT OA HEAT RECOVERY | 2.54 |
VAV_MID WITH REHEAT OA HEAT RECOVERY | 25.38 |
VAV_TOP WITH REHEAT OA HEAT RECOVERY | 2.54 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 25.80 | 6.67 | 10.90 | 0.010191 | 0.008500 | 211758.73 | 0.009009 | 9.24 |
VAV_MID WITH REHEAT COOLING COIL | 26.00 | 6.67 | 10.90 | 0.010409 | 0.008500 | 2034812.37 | 0.086566 | 85.49 |
VAV_TOP WITH REHEAT COOLING COIL | 25.72 | 6.67 | 10.90 | 0.010186 | 0.008500 | 211940.87 | 0.009016 | 9.29 |
CAV_BAS COOLING COIL | 25.01 | 6.67 | 11.39 | 0.010072 | 0.008500 | 112522.33 | 0.004787 | 5.35 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 9.24 |
VAV_MID WITH REHEAT FAN | 85.49 |
VAV_TOP WITH REHEAT FAN | 9.29 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.009009 | 0.000053 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000742 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.086566 | 0.000006 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.007606 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.009016 | 0.000053 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000750 | |
CAV_BAS_COOLC_CONTROLLER | 0.004787 | 0.000099 |
CAV_BAS_HEATC_CONTROLLER | 0.002411 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.35 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.82 | 432985.54 | 304627.06 | 0.010604 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.491025 | 9630.35 | 6809.52 | 0.000236 |
AIRLOOP DATACENTER MID COOLING COIL | 4.69 | 92151.15 | 65107.07 | 0.002257 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.477539 | 9374.16 | 6625.14 | 0.000230 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.82 | 21.82 | 21.82 | 21.82 | 432985.54 | 432985.54 | 22473.72 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.491025 | 0.491025 | 0.491025 | 0.491025 | 9630.35 | 9630.35 | 1038.19 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.69 | 4.69 | 4.69 | 4.69 | 92151.15 | 92151.15 | 10381.93 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.477539 | 0.477539 | 0.477539 | 0.477539 | 9374.16 | 9374.16 | 1038.19 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.82 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.491025 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.69 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.477539 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.82 | 432985.54 | 0.010604 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.491025 | 9630.35 | 0.000236 |
AIRLOOP DATACENTER MID HEATING COIL | 4.69 | 92151.15 | 0.002257 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.477539 | 9374.16 | 0.000230 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 22473.72 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 1038.19 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 10381.93 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 1038.19 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000187 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.109378 | 22538.70 | |
HEATSYS1 PUMP | 0.026593 | 8008.54 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.109378 | 13.13 |
HEATSYS1 | 0.026593 | 3.19 |
COOLSYS1_SUPPLY | 0.109378 | 13.13 |
SINGLE WATER PLANT LOOP | 0.013326 | 1.60 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.109378 | 0.109378 | 459113.27 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 3039703.33 | 3039703.33 | 0.026593 |
CENTRAL BOILER | 548916.25 | 538151.42 | 0.013326 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.109378 | 15604.30 |
PLANT CIRC PUMP | 0.013326 | 3398.79 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.109378 | 0.054955 | 1294945.97 | 1301121.22 | 0.064388 |
COOLSYS1 CHILLER2 | 0.109378 | 0.054955 | 1294945.97 | 1301121.22 | 0.064388 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013326 | 139666.47 | 59143.24 | 69833.23 | 7879.72 | 21402.38 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.128775 | 15.45 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.128775 | 38784.33 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 51.05 | 1543770.08 | 10.21 | 192971.26 |
TOWERWATERSYS COOLTOWER 2 | 51.05 | 1543770.08 | 10.21 | 192971.26 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.066878 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.70 | 6.00 | -2.20 | -3.40 | -4.20 | 2.70 | 7.50 | 13.70 | 18.60 | 22.00 | 20.70 | 16.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 | 42.93 | -78.73 | -5.00 | 215.00 | 98769 | 1.1739 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 8.97 | 26.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.149 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.571 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6483 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7026 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4692 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.15847945E-14 | 0.40415870E-16 | -0.13570955E-09 | -0.55776231E-17 |
51 | 8 | 0.19900788E-07 | 0.16227319E-12 | 0.35673126E-03 | -0.22627880E-09 |
52 | 7 | -0.11611995E-01 | 0.86155623E-08 | -0.22179000E-01 | 0.13203260E-03 |
53 | 6 | 0.38824249 | 0.30290701E-05 | 0.45749374 | -0.45461023E-02 |
54 | 5 | -5.0235921 | 0.11413317E-03 | -4.3290265 | 0.61113495E-01 |
55 | 4 | 32.264180 | 0.94131685E-03 | 21.001374 | -0.41231550 |
56 | 3 | -109.65428 | 0.20665218E-02 | -54.756066 | 1.4924847 |
57 | 2 | 195.57288 | 0.11699747E-02 | 77.079281 | -2.8759721 |
58 | 1 | -170.58880 | 0.12564906E-03 | -55.024271 | 2.7354972 |
59 | 0 | 57.057407 | 0.71994484E-06 | 15.597457 | |
60 | 9 | 0.92194319E-15 | 0.45185080E-16 | -0.13934922E-09 | -0.37336789E-17 |
61 | 8 | 0.20414049E-07 | 0.15291409E-12 | 0.36227410E-03 | -0.23211478E-09 |
62 | 7 | -0.11777906E-01 | 0.80689916E-08 | -0.22418053E-01 | 0.13391908E-03 |
63 | 6 | 0.39275134 | 0.28300412E-05 | 0.46134659 | -0.45992504E-02 |
64 | 5 | -5.0676021 | 0.10641223E-03 | -4.3586752 | 0.61659190E-01 |
65 | 4 | 32.458904 | 0.87600040E-03 | 21.117392 | -0.41490080 |
66 | 3 | -110.06874 | 0.19199492E-02 | -54.985491 | 1.4984722 |
67 | 2 | 195.98384 | 0.10853975E-02 | 77.289466 | -2.8824978 |
68 | 1 | -170.74067 | 0.11640795E-03 | -55.084954 | 2.7381589 |
69 | 0 | 57.057407 | 0.66605595E-06 | 15.587079 | |
70 | 9 | 0.99499981E-15 | 0.49201796E-16 | -0.11918706E-09 | -0.33210447E-17 |
71 | 8 | 0.17565796E-07 | 0.20231051E-12 | 0.33086922E-03 | -0.19972915E-09 |
72 | 7 | -0.10835659E-01 | 0.11065463E-07 | -0.21059630E-01 | 0.12320537E-03 |
73 | 6 | 0.36714142 | 0.39371282E-05 | 0.43940598 | -0.42973741E-02 |
74 | 5 | -4.8175888 | 0.14987275E-03 | -4.1895891 | 0.58559222E-01 |
75 | 4 | 31.352470 | 0.12474171E-02 | 20.455190 | -0.40021127 |
76 | 3 | -107.71307 | 0.27606440E-02 | -53.675749 | 1.4644420 |
77 | 2 | 193.64724 | 0.15741070E-02 | 76.090603 | -2.8453956 |
78 | 1 | -169.87685 | 0.17016149E-03 | -54.740743 | 2.7230195 |
79 | 0 | 57.057407 | 0.98204117E-06 | 15.647518 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9796E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9815E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5033E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5049E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3975E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3986E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8674E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8681E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0218E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1449E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5387E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6454E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4276E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5168E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8859E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9330E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1279 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0388E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1461 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0416E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.3743E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9266E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9234E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3771E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.0288E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1815E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5463E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6855E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4338E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5408E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8864E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9344E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9795E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9816E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.5032E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5050E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3974E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3988E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8673E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8680E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4125E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.7260E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2681E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.6227E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9081E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0284E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1954E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2279E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2038E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.6377E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.0170E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.4553E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.2979E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2407E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0350E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5085E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.3166E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.4067E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.1432E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.2091E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8707E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.8975E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1955E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2284E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9814E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9832E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6806E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6821E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4798E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4809E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8681E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0231E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1297E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7151E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8006E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5086E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5727E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8864E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9344E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.2225E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8725E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4935E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4210E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.5065E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.9479E-003 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9234E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3767E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0211E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1286E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7124E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7960E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5038E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5576E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8860E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9331E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9812E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9830E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6805E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6819E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4797E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4807E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8680E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8321E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.9260E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5313E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5991E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5009E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5254E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1956E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2284E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.2726E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.2537E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8511E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9739E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.5345E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9262E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0350E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5085E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9061E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1342E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6283E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8734E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5357E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.6427E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1954E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2278E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1213 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.9588E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1345 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1013 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.8522E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3615E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5331E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.1963E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9573E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.6203E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.7542E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.4132E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9883E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1035E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6386E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2195E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.8312E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.7089E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0389E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1371E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0479E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6509E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5332E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1959E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.9474E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.1173E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.4885E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7806E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.1689E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7078E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6386E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2195E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1211 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.9706E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1343 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1014 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.8528E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3721E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5383E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2005E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9537E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.6236E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.7519E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.4166E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9898E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1088E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6435E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2237E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.8261E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.7099E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0354E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1380E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0494E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6534E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5383E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2001E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.9437E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.1196E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.4859E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7830E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.1703E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7123E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6435E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2237E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72483.91915 | 72483.91915 | 5.35222 | 5.35222 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 77151.04656 | 77151.04656 | 5.69675 | 5.69675 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 5760.86308 | 5760.86308 | 0.25074 | 1.07782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 723344.47993 | 723344.47993 | 53.39583 | 53.39583 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 330221.01102 | 330221.01102 | 14.31827 | 14.31827 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 71646.60234 | 71646.60234 | 5.28884 | 5.28884 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 23.41800 | 1.33548E-002 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 70157.42787 | 70157.42787 | 3.06038 | 3.06038 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12162.47576 | 12162.47576 | 0.90648 | 0.90648 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 12424.66515 | 12424.66515 | 0.54273 | 0.54273 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14639.47673 | 14639.47673 | 1.09108 | 1.09108 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.18500 | 1.33579E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 8453.27885 | 8453.27885 | 0.36934 | 0.36934 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17564.71798 | 17564.71798 | 1.30910 | 1.30910 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 29.99000 | 1.33664E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 13594.66188 | 13594.66188 | 0.59403 | 0.59403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18336.07526 | 18336.07526 | 1.36658 | 1.36658 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 6758.33022 | 6758.33022 | 0.29499 | 0.29499 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 113783.91732 | 113783.91732 | 8.48092 | 8.48092 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 193183.15848 | 193183.15848 | 8.44937 | 8.44937 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 154014.11161 | 154014.11161 | 11.47939 | 11.47939 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 25.71200 | 1.33588E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 126754.04094 | 126754.04094 | 5.54413 | 5.54413 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 172575.22108 | 172575.22108 | 12.86288 | 12.86288 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 30.06750 | 1.33665E-002 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 193184.24480 | 193184.24480 | 8.44942 | 8.44942 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 162619.87016 | 162619.87016 | 12.12081 | 12.12081 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 123526.92400 | 123526.92400 | 5.40268 | 5.40268 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13025.19979 | 13025.19979 | 0.97086 | 0.97086 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 30.30000 | 1.33670E-002 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 24988.94186 | 24988.94186 | 1.09349 | 1.09349 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15574.45137 | 15574.45137 | 1.16087 | 1.16087 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 25.97550 | 1.33593E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 16329.78864 | 16329.78864 | 0.71459 | 0.71459 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18802.29308 | 18802.29308 | 1.40146 | 1.40146 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 30.22250 | 1.33668E-002 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 24989.12899 | 24989.12899 | 1.09350 | 1.09350 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 17369.00833 | 17369.00833 | 1.29462 | 1.29462 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 28.84300 | 1.33644E-002 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 16182.41437 | 16182.41437 | 0.70814 | 0.70814 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -16.30000 | 9.24091E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8353.27995 | 8353.27995 | 0.49102 | 0.49102 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 79814.50678 | 79814.50678 | 4.69171 | 4.69171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 26.50250 | 1.33602E-002 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8123.82884 | 8123.82884 | 0.47754 | 0.47754 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 26.67300 | 1.33605E-002 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -16.30000 | 9.24091E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371255.51590 | 371255.51590 | 21.82290 | 21.82290 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 21.83700 | 1.33520E-002 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | -16.30000 | 9.24091E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 135907.66 | 9.24064 | 9.24064 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 87114.41 | 2.87892 | 2.87892 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1245369.27 | 85.48807 | 85.48807 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 863621.42 | 42.16386 | 42.16386 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 141466.85 | 9.29390 | 9.29390 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 86792.88 | 6.67010 | 6.67010 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 |
7 | CAV_BAS | Cooling | Sensible | 70971.02 | 5.35222 | 5.35222 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 79706.12 | 1.20016 | 1.20016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 366378.94 | 21.82313 | 21.82313 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 22473.72 | 0.33839 | 0.33839 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8216.71 | 0.49102 | 0.49102 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 78500.76 | 4.69171 | 4.69171 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 10381.93 | 0.15632 | 0.15632 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 7992.21 | 0.47754 | 0.47754 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 1038.19 | 1.56323E-002 | 1.56323E-002 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.35222 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.69675 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.33388 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33500 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.90841 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.89035 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.14112E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.14275E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.90841 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 24492.97479 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.14275E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 509.17813 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 53.39583 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35622 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.34900 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.63514 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.94991 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.06958E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.48919E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.63514 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 513142.37718 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.48919E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 12632.38673 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.28884 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35963 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.36100 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.90927 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.95902 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.05941E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.76575E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.06038 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 100197.92464 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.76575E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2644.56550 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.90648 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.26346 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.26400 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23931 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.70256 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.44614E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.55247E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.54273 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17745.63771 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.55247E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 468.08217 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09108 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14106 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21822 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37615 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.70102E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.05634E-004 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.36934 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 12074.57041 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.05634E-004 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 318.47671 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.30910 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18243 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26182 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.48649 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.08842E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.69892E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.59403 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 19419.68259 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.69892E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 512.20005 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.36658 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11262 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27332 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30032 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.38304E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.44134E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.29499 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9648.96545 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.44134E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 254.55761 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 8.48092 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.28160 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.27600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.34073 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.75093 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.35299E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41451E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.44937 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 275992.79891 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41451E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7276.64557 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.47939 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13407 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.29588 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35752 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.84178E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.58425E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.54413 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 181088.97489 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.58425E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4774.39976 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.86288 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.18567 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.57258 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.49512 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.05202E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.41452E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.44942 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 275994.34873 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41452E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 7276.68653 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 12.12081 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12698 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.42416 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33860 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.00057E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.54387E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.40268 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 176473.84439 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.54387E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4652.78167 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.09349 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21840 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.24700 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.27009 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.58240 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.74449E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.12369E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09349 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35705.73848 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12369E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 941.24377 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.16087 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13258 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23217 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35354 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.87378E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.04127E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.71459 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23332.92433 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.04127E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 615.07569 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.40146 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.17041 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28029 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.45443 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.23575E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.12372E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.09350 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 35706.00577 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.12372E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 941.25082 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.29462 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11888 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25892 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.31701 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.20491E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.02283E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.70814 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 23122.20627 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.02283E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 609.52182 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49102 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.69171 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.47754 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.82290 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.18499 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.90107 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.36999 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.90107 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.24064 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.24064 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.31395 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 49.16991 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.26849 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 98.33982 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 42.16386 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 85.48807 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 85.48807 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.49321 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.11964 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.95075 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.23928 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 6.67010 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 9.29390 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 9.29390 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.71769 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.35222 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.35222 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.35222 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.35222 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.35222 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.35222 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.82290 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.82290 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.82290 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.82290 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.82313 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.82313 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49102 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49102 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49102 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49102 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49102 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49102 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.69171 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.69171 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.69171 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.69171 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.69171 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.69171 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.47754 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.47754 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.47754 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.47754 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.47754 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.47754 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.24064 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 85.48807 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 9.29390 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.35222 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.82313 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49102 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.69171 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.47754 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.24064 |
289 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_BOT WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.80379 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89982 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01906E-002 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 211758.73018 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.00871E-003 |
297 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.24064 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 84865.72572 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.42442E-004 |
300 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1327.53872 |
301 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.24064 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.00871E-003 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.28589E-005 |
304 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.42442E-004 |
305 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 85.48807 |
306 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_MID WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 25.38195 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.99777 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.90057 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.04092E-002 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 2034812.36954 |
313 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 8.65656E-002 |
314 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 85.48807 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 869378.30433 |
316 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.60570E-003 |
317 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 13371.47669 |
318 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 85.48807 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 8.65656E-002 |
320 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.50092E-006 |
321 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.60570E-003 |
322 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 9.29390 |
323 | HeatExchanger:AirToAir:SensibleAndLatent | VAV_TOP WITH REHEAT OA HEAT RECOVERY | Design Size Nominal Supply Air Flow Rate [m3/s] | 2.53819 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.72157 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.89980 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.01863E-002 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
329 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 211940.87080 |
330 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 9.01645E-003 |
331 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 9.29390 |
332 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 85698.22873 |
333 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.49725E-004 |
334 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1339.90761 |
335 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 9.29390 |
336 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 9.01645E-003 |
337 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 5.28135E-005 |
338 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.49725E-004 |
339 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.35222 |
340 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.01270 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.38882 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 1.00716E-002 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
346 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 112522.33093 |
347 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.78696E-003 |
348 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.35222 |
349 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 275622.09853 |
350 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.41126E-003 |
351 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5977.73539 |
352 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.35222 |
353 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.78696E-003 |
354 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 9.94766E-005 |
355 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.41126E-003 |
356 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.82313 |
357 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.82313 |
359 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 432985.53577 |
360 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 304627.05557 |
361 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06038E-002 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.82313 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.82313 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.82313 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.82313 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 432985.53577 |
367 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 432985.53577 |
368 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 22473.71574 |
369 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
370 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.82313 |
371 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.82313 |
372 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 432985.53577 |
373 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.06038E-002 |
374 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 22473.71574 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.86942E-004 |
376 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
377 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
378 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
379 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49102 |
380 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49102 |
382 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9630.35319 |
383 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6809.52250 |
384 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35847E-004 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49102 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49102 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49102 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49102 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9630.35319 |
390 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9630.35319 |
391 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
392 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
393 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49102 |
394 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49102 |
395 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9630.35319 |
396 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.35847E-004 |
397 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
398 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.69171 |
399 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69171 |
401 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 92151.15351 |
402 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 65107.06903 |
403 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25678E-003 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.69171 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.69171 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.69171 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.69171 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 92151.15351 |
409 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 92151.15351 |
410 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 10381.92564 |
411 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
412 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.69171 |
413 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.69171 |
414 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 92151.15351 |
415 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.25678E-003 |
416 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 10381.92564 |
417 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.47754 |
418 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47754 |
420 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9374.15705 |
421 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6625.13818 |
422 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29573E-004 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.47754 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.47754 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.47754 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.47754 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9374.15705 |
428 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9374.15705 |
429 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 1038.19256 |
430 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
431 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.47754 |
432 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.47754 |
433 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9374.15705 |
434 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.29573E-004 |
435 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 1038.19256 |
436 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 0.10938 |
437 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 22538.69884 |
438 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 0.10938 |
439 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 13.12533 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 0.10938 |
441 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 0.10938 |
442 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 459113.26812 |
443 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
444 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.65927E-002 |
445 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 3.19112 |
446 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.65927E-002 |
447 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 8008.53860 |
448 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
449 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 3039703.33184 |
450 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 3039703.33000 |
451 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.65927E-002 |
452 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 0.10938 |
453 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 13.12533 |
454 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 0.10938 |
455 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 15604.30149 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10938 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.49550E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1294945.97357 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1301121.21500 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.43877E-002 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 0.10938 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 5.49550E-002 |
463 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1294945.97357 |
464 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1301121.21500 |
465 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 6.43877E-002 |
466 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.33260E-002 |
467 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.59912 |
468 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.33260E-002 |
469 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3398.79205 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.33260E-002 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 59143.24029 |
473 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
474 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
475 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21402.38408 |
476 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 548916.25342 |
477 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 538151.42000 |
478 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.33260E-002 |
479 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
480 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
481 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
482 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
483 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
484 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.12878 |
485 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 15.45304 |
486 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.12878 |
487 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 38784.32775 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 51.04846 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1543770.07715 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.20969 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 192971.25964 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 51.04846 |
493 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1543770.07715 |
494 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.20969 |
495 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 192971.25964 |
496 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.68775E-002 |
497 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 6.68775E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 23221.32 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 486050.89 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 94948.85 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 16814.08 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 11440.60 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 18399.98 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 9142.74 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 261482.37 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 171567.66 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 261483.84 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 167195.58 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 33827.48 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 22105.48 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 33827.74 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 21905.85 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 58584.90 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 583606.13 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 59095.02 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 211761.88 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 239634.59 | 162086.95 | 77547.64 | 0.68 | 25396.91 | 257.59 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2250643.70 | 1514951.39 | 735692.31 | 0.67 | 238618.56 | 2420.20 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 240591.59 | 162830.78 | 77760.81 | 0.68 | 25507.10 | 258.71 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 131968.64 | 90595.51 | 41373.14 | 0.69 | 13655.95 | 138.51 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 7.0864607885E-004 | 1.3892549098E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 1.5903049657E-003 | 2.0775997910E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.1718599198E-002 | 2.2097042232E-002 | Pass | Pass | 0.4831888769 | 0.4888025439 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 2.7574284248E-002 | 3.2567855201E-002 | Pass | Pass | 12.2824990262 | 37.7290166363 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.8189042447E-002 | 1.3088955270E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 1.8149351294E-002 | 1.2802905399E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 1.9873664960E-002 | 1.4275740512E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 1.9589139755E-002 | 1.4363040434E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2766220486 | 0.2591087233 | Pass | Pass | 34.2463536123 | 154.6535760558 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2940727210 | 0.2810100330 | Pass | Pass | 11.4102449657 | 39.1376291005 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2610763453 | 0.2556645089 | Pass | Pass | 17.0519291810 | 55.9477372590 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1844220430 | 0.1893397767 | Pass | Pass | 14.0224759965 | 44.4202867406 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.4535631060 | 0.4243182804 | Pass | Pass | 18.2143253822 | 72.5340744218 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.4830840554 | 0.4563156136 | Pass | Pass | 29.5153304112 | 98.5384563812 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.4324307411 | 0.4155257294 | Pass | Pass | 35.8679577106 | 120.9150155082 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.3832137688 | 0.3682003977 | Pass | Pass | 17.7799764318 | 77.3530863387 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.6775653442E-003 | 5.2127471694E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 5.1037055153E-002 | 2.8608266037E-002 | Pass | Pass | 0.4971454123 | 0.4672945551 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1232662223 | 8.2385581033E-002 | Pass | Pass | 0.4899543679 | 0.4775880041 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3405957854E-007 | 5.9416817964E-007 | Pass | Pass | 3.1982073038E-003 | 2.3549803682E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.0849938889E-003 | 2.9385026427E-003 | Pass | Pass | 1.6027285075E-003 | 1.4329267955E-003 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 7.2163297389E-003 | 5.1261182969E-003 | Pass | Pass | 3.0847375123E-003 | 2.5332190234E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 8.8512223651E-006 | 9.0236723767E-006 | Pass | Pass | 3.4046445469E-005 | 1.1015279906E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6967.22 | 311.40 | 0.00 | 17293.41 | 18663.85 | 43235.86 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | -16.30 | 0.00 | -16.30 | Wetbulb [C] | 5.10 | 270.00 |
BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 30.30 | 9.30 | 21.80 | Wetbulb [C] | 5.70 | 240.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 44.00 | 33 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 67.00 | 33 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.86 | 0.0000 | Y | 13.83 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.79 | 0.0000 | Y | 8.89 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.66 | 0.0000 | Y | 13.75 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.77 | 0.0000 | Y | 8.89 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.89 | 0.0000 | Y | 138.47 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.80 | 0.0000 | Y | 88.98 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.69 | 0.0000 | Y | 137.60 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.78 | 0.0000 | Y | 88.93 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.89 | 0.0000 | Y | 13.85 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.80 | 0.0000 | Y | 8.90 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.69 | 0.0000 | Y | 13.76 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.78 | 0.0000 | Y | 8.89 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 856.81 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.04 | 42.04 | 78.71 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.67 | 71.18 | 369.28 | |
Exterior Lighting Total | 37611.08 | 447.99 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2565121.68 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 3039703.33 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1301121.22 | 6.28 | 1245337.89 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1301121.22 | 6.28 | 1245337.89 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 538151.42 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1543770.08 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1543770.08 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 211758.73 | 239634.59 | 162086.95 | 77547.64 | 0.68 | - | 25396.91 | 257.59 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 2034812.37 | 2250643.70 | 1514951.39 | 735692.31 | 0.67 | - | 238618.56 | 2420.20 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 211940.87 | 240591.59 | 162830.78 | 77760.81 | 0.68 | - | 25507.10 | 258.71 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 112522.33 | 131968.64 | 90595.51 | 41373.14 | 0.69 | - | 13655.95 | 138.51 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 432985.54 | 304627.06 | 128358.48 | 0.70 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9630.35 | 6809.52 | 2820.83 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 92151.15 | 65107.07 | 27044.08 | 0.71 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9374.16 | 6625.14 | 2749.02 | 0.71 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 24492.97 | 23221.32 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 513142.38 | 486050.89 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 100197.92 | 94948.85 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 17745.64 | 16814.08 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 12074.57 | 11440.60 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 19419.68 | 18399.98 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 9648.97 | 9142.74 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 275992.80 | 261482.37 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 181088.97 | 171567.66 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 275994.35 | 261483.84 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 176473.84 | 167195.58 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 35705.74 | 33827.48 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 23332.92 | 22105.48 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 35706.01 | 33827.74 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 23122.21 | 21905.85 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 84865.73 | 58584.90 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 869378.30 | 583606.13 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 85698.23 | 59095.02 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 275622.10 | 211761.88 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 432985.54 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9630.35 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 92151.15 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9374.16 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 22473.72 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 10381.93 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 1038.19 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.24 | 21103.11 | 2283.73 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 85.49 | 195231.49 | 2283.73 | 1.00 | 1.07 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 9.29 | 21224.73 | 2283.73 | 1.00 | 1.12 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.35 | 9075.52 | 1695.65 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 21.82 | 35991.74 | 1649.25 | 1.00 | 1.14 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.49 | 550.00 | 1120.11 | 1.00 | 1.61 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.69 | 5255.22 | 1120.11 | 1.00 | 1.16 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 534.90 | 1120.11 | 1.00 | 1.63 | General | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.109378 | 22538.70 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.026593 | 8008.54 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.109378 | 15604.30 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013326 | 3398.79 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.128775 | 38784.33 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72483.92 | 72483.92 | 26.08 | 5.352 | 5.352 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 23.42 | 0.01335 | 1.200 | 0.00 |
CORE_BOTTOM | 77151.05 | 77151.05 | 30.91 | 5.697 | 5.697 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 23.42 | 0.01335 | 1.078 | 0.00 |
CORE_MID | 723344.48 | 723344.48 | 289.79 | 53.396 | 53.396 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00893 | 23.42 | 0.01335 | 10.778 | 0.00 |
CORE_TOP | 71646.60 | 71646.60 | 28.70 | 5.289 | 5.289 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 23.42 | 0.01335 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12162.48 | 12162.48 | 38.81 | 0.906 | 0.906 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:30:00 | 24.00 | 24.00 | 0.00897 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14639.48 | 14639.48 | 72.48 | 1.091 | 1.091 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00876 | 25.18 | 0.01336 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17564.72 | 17564.72 | 56.04 | 1.309 | 1.309 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00883 | 29.99 | 0.01337 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18336.08 | 18336.08 | 90.78 | 1.367 | 1.367 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00871 | 28.84 | 0.01336 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 113783.92 | 113783.92 | 363.05 | 8.481 | 8.481 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00921 | 30.30 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 154014.11 | 154014.11 | 762.54 | 11.479 | 11.479 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00886 | 25.71 | 0.01336 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 172575.22 | 172575.22 | 550.62 | 12.863 | 12.863 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:30:00 | 24.00 | 24.00 | 0.00898 | 30.07 | 0.01337 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 162619.87 | 162619.87 | 805.15 | 12.121 | 12.121 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00884 | 28.84 | 0.01336 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13025.20 | 13025.20 | 41.56 | 0.971 | 0.971 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | 24.00 | 24.00 | 0.00920 | 30.30 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15574.45 | 15574.45 | 77.11 | 1.161 | 1.161 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:30:00 | 24.00 | 24.00 | 0.00890 | 25.98 | 0.01336 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18802.29 | 18802.29 | 59.99 | 1.401 | 1.401 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24.00 | 24.00 | 0.00899 | 30.22 | 0.01337 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 17369.01 | 17369.01 | 86.00 | 1.295 | 1.295 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | 24.00 | 24.00 | 0.00886 | 28.84 | 0.01336 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8353.28 | 8353.28 | 230.74 | 0.491 | 0.491 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 79814.51 | 79814.51 | 2204.65 | 4.692 | 4.692 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 27.00 | 27.00 | 0.00859 | 26.50 | 0.01336 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8123.83 | 8123.83 | 224.40 | 0.478 | 0.478 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 27.00 | 27.00 | 0.00859 | 26.67 | 0.01336 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371255.52 | 371255.52 | 473.73 | 21.823 | 21.823 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 21.84 | 0.01335 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 22.96 | 0.00092 | -16.30 | 0.00092 | 1.200 | 0.00 |
CORE_BOTTOM | 5760.86 | 5760.86 | 2.31 | 0.251 | 1.078 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00798 | -16.30 | 0.00092 | 1.078 | 0.00 |
CORE_MID | 330221.01 | 330221.01 | 132.29 | 14.318 | 14.318 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 10.778 | 0.00 |
CORE_TOP | 70157.43 | 70157.43 | 28.11 | 3.060 | 3.060 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -16.30 | 0.00092 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12424.67 | 12424.67 | 39.64 | 0.543 | 0.543 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 8453.28 | 8453.28 | 41.85 | 0.369 | 0.369 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00751 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 13594.66 | 13594.66 | 43.38 | 0.594 | 0.594 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00756 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 6758.33 | 6758.33 | 33.46 | 0.295 | 0.295 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00724 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 193183.16 | 193183.16 | 616.39 | 8.449 | 8.449 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 126754.04 | 126754.04 | 627.57 | 5.544 | 5.544 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00736 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 193184.24 | 193184.24 | 616.38 | 8.449 | 8.449 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -16.30 | 0.00092 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 123526.92 | 123526.92 | 611.59 | 5.403 | 5.403 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00734 | -16.30 | 0.00092 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 24988.94 | 24988.94 | 79.73 | 1.093 | 1.093 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 16329.79 | 16329.79 | 80.85 | 0.715 | 0.715 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -16.30 | 0.00092 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 24989.13 | 24989.13 | 79.73 | 1.094 | 1.094 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00739 | -16.30 | 0.00092 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16182.41 | 16182.41 | 80.12 | 0.708 | 0.708 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00738 | -16.30 | 0.00092 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:30:00 | 18.00 | 24.72 | 0.00248 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 22.51 | 0.00148 | -16.30 | 0.00092 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 20.39 | 0.00148 | -16.30 | 0.00092 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 14:00:00 | 18.00 | 27.00 | 0.00850 | -16.30 | 0.00092 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 9.24 | 9.24 | 2.88 | 2.88 | 9.2406 | 2.9011 | 9.2406 | 0.3139 | 0.3000 |
VAV_MID WITH REHEAT | 85.49 | 85.49 | 42.16 | 42.16 | 85.4881 | 42.1639 | 85.4881 | 0.4932 | 0.3000 |
VAV_TOP WITH REHEAT | 9.29 | 9.29 | 6.67 | 6.67 | 9.2939 | 6.6701 | 9.2939 | 0.7177 | 0.3000 |
CAV_BAS | 5.35 | 5.35 | 1.20 | 1.20 | 5.3522 | 5.3522 | 5.3522 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.82 | 21.82 | 0.34 | 0.34 | 21.8231 | 21.8229 | 21.8231 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.49 | 0.49 | 0.02 | 0.02 | 0.4910 | 0.4910 | 0.4910 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.69 | 4.69 | 0.16 | 0.16 | 4.6917 | 4.6917 | 4.6917 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4775 | 0.4775 | 0.4775 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 24492.975 | 24492.975 | 1.908410 | 0.00021428 | 509.178 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 24492.97 | 24492.97 | 1.908410 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00797931 | 50.2898 | 5760.86 | 0.00 | 24581.91 | 24581.91 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 513142.377 | 513142.377 | 18.635144 | 0.00448919 | 12632.387 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 513142.38 | 513142.38 | 18.635144 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 330221.01 | 0.00 | 514756.34 | 514756.34 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 100197.925 | 100197.925 | 3.060381 | 0.00087658 | 2644.565 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 100197.92 | 100197.92 | 3.060381 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00800000 | 50.4185 | 70157.43 | 0.00 | 100541.64 | 100541.64 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 17745.638 | 17745.638 | 0.542734 | 0.00015525 | 468.082 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 17745.64 | 17745.64 | 0.542734 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00747330 | 47.1446 | 12424.67 | 0.00 | 17804.46 | 17804.46 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 12074.570 | 12074.570 | 0.369335 | 0.00010563 | 318.477 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 12074.57 | 12074.57 | 0.369335 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00751367 | 47.3958 | 8453.28 | 0.00 | 12114.46 | 12114.46 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 19419.683 | 19419.683 | 0.594032 | 0.00016989 | 512.200 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 19419.68 | 19419.68 | 0.594032 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00755961 | 47.6817 | 13594.66 | 0.00 | 19483.77 | 19483.77 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 9648.965 | 9648.965 | 0.294994 | 0.00008441 | 254.558 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9648.97 | 9648.97 | 0.294994 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00723928 | 45.6873 | 6758.33 | 0.00 | 9681.26 | 9681.26 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 275992.799 | 275992.799 | 8.449368 | 0.00241451 | 7276.646 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 275992.80 | 275992.80 | 8.449368 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00736770 | 46.4896 | 193183.16 | 0.00 | 276883.78 | 276883.78 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 181088.975 | 181088.975 | 5.544127 | 0.00158425 | 4774.400 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 181088.97 | 181088.97 | 5.544127 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00735915 | 46.4365 | 126754.04 | 0.00 | 181673.05 | 181673.05 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 275994.349 | 275994.349 | 8.449416 | 0.00241452 | 7276.687 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 275994.35 | 275994.35 | 8.449416 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00736770 | 46.4896 | 193184.24 | 0.00 | 276885.34 | 276885.34 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 176473.844 | 176473.844 | 5.402681 | 0.00154387 | 4652.782 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 176473.84 | 176473.84 | 5.402681 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00734300 | 46.3359 | 123526.92 | 0.00 | 177043.46 | 177043.46 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 35705.738 | 35705.738 | 1.093494 | 0.00031237 | 941.244 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35705.74 | 35604.36 | 1.093494 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00739472 | 46.6597 | 24988.94 | 0.00 | 35819.92 | 35819.92 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 23332.924 | 23332.924 | 0.714592 | 0.00020413 | 615.076 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23332.92 | 23332.92 | 0.714592 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00738354 | 46.5903 | 16329.79 | 0.00 | 23407.49 | 23407.49 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 35706.006 | 35706.006 | 1.093502 | 0.00031237 | 941.251 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 35706.01 | 35706.01 | 1.093502 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00739472 | 46.6597 | 24989.13 | 0.00 | 35820.19 | 35820.19 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 23122.206 | 23122.206 | 0.708136 | 0.00020228 | 609.522 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 23122.21 | 23122.21 | 0.708136 | 12.80 | 11.37 | 0.00800000 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 0.0000 | 21.00 | 0.00737867 | 46.5600 | 16182.41 | 0.00 | 23196.11 | 23196.11 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 211758.730 | -999.000 | 9.240640 | 0.00900871 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 211758.73 | 164230.64 | 9.240640 | 25.80 | 18.13 | 0.01019063 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 27.4677 | 24.00 | 0.00891531 | 46.7599 | 118878.57 | 0.00 | 215485.83 | 158889.75 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 84865.726 | 84865.726 | 2.772192 | 0.00074244 | 1327.539 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 84865.73 | 84865.73 | 2.772192 | -13.15 | -13.15 | 0.00149588 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 91.5590 | 21.00 | 0.00752983 | 47.4951 | 36560.89 | 0.00 | 70816.61 | 70816.61 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 2034812.370 | -999.000 | 85.488074 | 0.08656562 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 2034812.37 | 1538533.02 | 85.488074 | 26.00 | 18.37 | 0.01040917 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 29.6906 | 24.00 | 0.00903446 | 47.3769 | 1073281.54 | 0.00 | 2069100.09 | 1492412.63 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 869378.304 | 869378.304 | 25.646422 | 0.00760570 | 13371.477 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 869378.30 | 869378.30 | 25.646422 | -15.94 | -15.94 | 0.00099011 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 98.9688 | 19.29 | 0.00700352 | 49.1347 | 471600.12 | 0.00 | 705771.28 | 705771.28 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 211940.871 | -999.000 | 9.293897 | 0.00901645 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 211940.87 | 164259.88 | 9.293897 | 25.72 | 18.10 | 0.01018631 | 10.90 | 10.90 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | 27.3103 | 24.00 | 0.00898901 | 47.1422 | 124523.77 | 0.00 | 215681.38 | 158891.54 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 85698.229 | 85698.229 | 2.788169 | 0.00074973 | 1339.908 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 85698.23 | 85698.23 | 2.788169 | -13.26 | -13.26 | 0.00149089 | 12.80 | 11.37 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 91.0343 | 17.37 | 0.00695340 | 55.0542 | 53845.68 | 0.00 | 71432.71 | 71432.71 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 112522.331 | -999.000 | 5.352224 | 0.00478696 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 112522.33 | 87614.58 | 5.352224 | 25.01 | 17.78 | 0.01007162 | 11.39 | 11.29 | 0.00850000 | 28.16 | 0.01336316 | 21.21 | 22.4235 | 24.00 | 0.00901146 | 47.2566 | 66100.37 | 0.00 | 114549.57 | 85164.02 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 275622.099 | 275622.099 | 5.352224 | 0.00241126 | 5977.735 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 275622.10 | 275622.10 | 5.352224 | -3.66 | -7.04 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 22.4235 | 23.06 | 0.00092409 | 5.1951 | 0.00 | 0.00 | 223524.84 | 223524.84 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 432985.536 | 304627.056 | 21.823134 | 0.01060379 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 402224.48 | 395504.12 | -999.0 | 28.48 | 17.76 | 0.00861723 | 12.80 | 11.87 | 0.00850000 | 30.30 | 0.01336696 | 21.83 | -999.0000 | 27.00 | 0.00854233 | 37.5164 | 370794.31 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9630.353 | 6809.523 | 0.491025 | 0.00023585 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 8927.91 | 8620.68 | -999.0 | 27.96 | 17.68 | 0.00873857 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858656 | 37.7056 | 8351.86 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92151.154 | 65107.069 | 4.691708 | 0.00225678 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | 85449.93 | 82378.75 | -999.0 | 27.96 | 17.69 | 0.00874955 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00859058 | 37.7232 | 79794.64 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9374.157 | 6625.138 | 0.477539 | 0.00022957 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8691.66 | 8384.47 | -999.0 | 27.96 | 17.69 | 0.00874525 | 12.80 | 11.87 | 0.00850000 | 26.67 | 0.01336053 | 20.77 | -999.0000 | 27.00 | 0.00858906 | 37.7166 | 8123.83 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 432985.536 | 432985.536 | 21.823134 | 0.01060379 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 432985.54 | 432985.54 | 21.823134 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.5506 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9630.353 | 9630.353 | 0.491025 | 0.00023585 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9630.35 | 9630.35 | 0.491025 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1836 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 92151.154 | 92151.154 | 4.691708 | 0.00225678 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 92151.15 | 92151.15 | 4.691708 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.3319 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9374.157 | 9374.157 | 0.477539 | 0.00022957 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9374.16 | 9374.16 | 0.477539 | -16.30 | -16.30 | 0.00092409 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2735 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 22473.72 | 22473.72 | 21.823134 | -0.25 | -0.25 | 0.00838253 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 1.5506 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.491025 | -0.52 | -2.51 | 0.00242704 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.1836 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 10381.93 | 10381.93 | 4.691708 | -0.54 | -4.12 | 0.00146563 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.3319 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 1038.19 | 1038.19 | 0.477539 | -0.53 | -4.11 | 0.00146555 | 40.00 | 20.89 | 0.00800000 | -16.30 | 0.00092409 | -16.30 | 3.2735 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 24492.975 | 24492.975 | 1.908410 | 0.00021428 | 509.178 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 0.7899 | 0.805769 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 24492.97 | 24492.97 | 1.0000 | 2.24033073 | 1.908410 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.21425337 | 60.00 | 32.22 | 27.78 | 0.000 | 24492.97 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.86 | 0.00797931 | 21.00 | 0.00797931 | 50.2898 | 5760.86 | 0.00 | 24581.91 | 24581.91 | 2.24033073 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 23.56 | 15.80 | 0.00800000 | 44032.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 513142.377 | 513142.377 | 18.635144 | 0.00448919 | 12632.387 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 16.5483 | 16.881331 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 513142.38 | 513142.38 | 1.0000 | 21.87626744 | 18.635144 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 4.48873542 | 60.00 | 32.22 | 27.78 | 0.000 | 513142.38 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 330221.01 | 0.00 | 514756.34 | 514756.34 | 21.87626744 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.88 | 19.93 | 0.00800000 | 56590.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 100197.925 | 100197.925 | 3.060381 | 0.00087658 | 2644.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 3.2313 | 3.296306 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 100197.92 | 100197.92 | 1.0000 | 3.59265817 | 3.060381 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.87648574 | 60.00 | 32.22 | 27.78 | 0.000 | 100197.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.91 | 0.00800000 | 21.00 | 0.00800000 | 50.4185 | 70157.43 | 0.00 | 100541.64 | 100541.64 | 3.59265817 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.24 | 21.25 | 0.00800000 | 61045.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17745.638 | 17745.638 | 0.542734 | 0.00015525 | 468.082 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 0.5723 | 0.583795 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 17745.64 | 17745.64 | 1.0000 | 0.63712935 | 0.542734 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.15523074 | 60.00 | 32.22 | 27.78 | 0.000 | 17745.64 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00747330 | 21.00 | 0.00747330 | 47.1446 | 12424.67 | 0.00 | 17804.46 | 17804.46 | 0.63712935 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61004.6 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 12074.570 | 12074.570 | 0.369335 | 0.00010563 | 318.477 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 0.3894 | 0.397229 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 12074.57 | 12074.57 | 1.0000 | 0.43357201 | 0.369335 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.10562283 | 60.00 | 32.22 | 27.78 | 0.000 | 12074.57 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00751367 | 21.00 | 0.00751367 | 47.3958 | 8453.28 | 0.00 | 12114.46 | 12114.46 | 0.43357201 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 61000.9 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 19419.683 | 19419.683 | 0.594032 | 0.00016989 | 512.200 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 0.6263 | 0.638868 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 19419.68 | 19419.68 | 1.0000 | 0.69734915 | 0.594032 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.16987452 | 60.00 | 32.22 | 27.78 | 0.000 | 19419.68 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00755961 | 21.00 | 0.00755961 | 47.6817 | 13594.66 | 0.00 | 19483.77 | 19483.77 | 0.69734915 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.6 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9648.965 | 9648.965 | 0.294994 | 0.00008441 | 254.558 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 0.3112 | 0.317431 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9648.97 | 9648.97 | 1.0000 | 0.34630058 | 0.294994 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.08440475 | 60.00 | 32.22 | 27.78 | 0.000 | 9648.97 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.90 | 0.00723928 | 21.00 | 0.00723928 | 45.6873 | 6758.33 | 0.00 | 9681.26 | 9681.26 | 0.34630058 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.1 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 275992.799 | 275992.799 | 8.449368 | 0.00241451 | 7276.646 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 8.9005 | 9.079597 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 275992.80 | 275992.80 | 1.0000 | 9.91892735 | 8.449368 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.41425910 | 60.00 | 32.22 | 27.78 | 0.000 | 275992.80 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00736770 | 21.00 | 0.00736770 | 46.4896 | 193183.16 | 0.00 | 276883.78 | 276883.78 | 9.91892735 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.5 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 181088.975 | 181088.975 | 5.544127 | 0.00158425 | 4774.400 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 5.8399 | 5.957456 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 181088.97 | 181088.97 | 1.0000 | 6.50839105 | 5.544127 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.58408374 | 60.00 | 32.22 | 27.78 | 0.000 | 181088.97 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00735915 | 21.00 | 0.00735915 | 46.4365 | 126754.04 | 0.00 | 181673.05 | 181673.05 | 6.50839105 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60973.5 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 275994.349 | 275994.349 | 8.449416 | 0.00241452 | 7276.687 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 8.9005 | 9.079648 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 275994.35 | 275994.35 | 1.0000 | 9.91898276 | 8.449416 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.41427266 | 60.00 | 32.22 | 27.78 | 0.000 | 275994.35 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00736770 | 21.00 | 0.00736770 | 46.4896 | 193184.24 | 0.00 | 276885.34 | 276885.34 | 9.91898276 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60974.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 176473.844 | 176473.844 | 5.402681 | 0.00154387 | 4652.782 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 5.6911 | 5.805627 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 176473.84 | 176473.84 | 1.0000 | 6.34234424 | 5.402681 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 1.54371268 | 60.00 | 32.22 | 27.78 | 0.000 | 176473.84 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.95 | 0.00734300 | 21.00 | 0.00734300 | 46.3359 | 123526.92 | 0.00 | 177043.46 | 177043.46 | 6.34234424 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60974.3 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35705.738 | 35705.738 | 1.093494 | 0.00031237 | 941.244 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 1.1515 | 1.174646 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35705.74 | 35604.36 | 1.0000 | 1.28368036 | 1.093494 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.31233751 | 60.00 | 32.22 | 27.78 | 0.000 | 35705.74 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00739472 | 21.00 | 0.00739472 | 46.6597 | 24988.94 | 0.00 | 35819.92 | 35819.92 | 1.28368036 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.9 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23332.924 | 23332.924 | 0.714592 | 0.00020413 | 615.076 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 0.7525 | 0.767605 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23332.92 | 23332.92 | 1.0000 | 0.83887712 | 0.714592 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.20410578 | 60.00 | 32.22 | 27.78 | 0.000 | 23332.92 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00738354 | 21.00 | 0.00738354 | 46.5903 | 16329.79 | 0.00 | 23407.49 | 23407.49 | 0.83887712 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.2 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 35706.006 | 35706.006 | 1.093502 | 0.00031237 | 941.251 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 1.1515 | 1.174654 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 35706.01 | 35706.01 | 1.0000 | 1.28368994 | 1.093502 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.31233985 | 60.00 | 32.22 | 27.78 | 0.000 | 35706.01 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00739472 | 21.00 | 0.00739472 | 46.6597 | 24989.13 | 0.00 | 35820.19 | 35820.19 | 1.28368994 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.9 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 23122.206 | 23122.206 | 0.708136 | 0.00020228 | 609.522 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 0.7457 | 0.760673 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 23122.21 | 23122.21 | 1.0000 | 0.83129878 | 0.708136 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 0.20226251 | 60.00 | 32.22 | 27.78 | 0.000 | 23122.21 | -16.30 | 0.00092409 | -16.30 | 0.00000000 | 0.0000 | 20.94 | 0.00737867 | 21.00 | 0.00737867 | 46.5600 | 16182.41 | 0.00 | 23196.11 | 23196.11 | 0.83129878 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.16 | 21.23 | 0.00800000 | 60963.3 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 211758.730 | -999.000 | 9.240640 | 0.00900871 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7839 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.240640 | 10.84782081 | 4197.9300 | 999.8980 | 109.36658499 | 12.27 | 6.67 | 5.60 | 2571034.30 | 8.2363 | 8.236325 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 211758.73 | 164230.64 | 1.0000 | 10.84782081 | 9.240640 | 25.80 | 18.13 | 0.01019063 | 51903.6 | 10.90 | 10.90 | 0.00850000 | 32382.8 | 9.00778692 | 6.67 | 12.27 | 5.60 | 21103.106 | 190655.62 | 30.30 | 0.01336696 | 21.83 | 2.53819000 | 27.4677 | 24.00 | 0.00891531 | 24.00 | 0.00891531 | 46.7599 | 118878.57 | 0.00 | 215485.83 | 158889.75 | 10.84782081 | 25.80 | 18.41 | 0.01019063 | 51903.6 | 11.50 | 11.17 | 0.00812218 | 32039.2 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 84865.726 | 84865.726 | 2.772192 | 0.00074244 | 1327.539 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 9.240640 | 10.84782081 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 2.7368 | 2.791908 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 13:50:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 84865.73 | 84865.73 | 1.0000 | 3.25434624 | 2.772192 | -13.15 | -13.15 | 0.00149588 | -9510.7 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.74236665 | 60.00 | 32.22 | 27.78 | 0.000 | 84865.73 | -16.30 | 0.00092409 | -16.30 | 2.53819000 | 91.5590 | 21.00 | 0.00769796 | 21.00 | 0.00752983 | 47.4951 | 36560.89 | 0.00 | 70816.61 | 70816.61 | 3.25434624 | 2.80 | -1.98 | 0.00149588 | 6562.4 | 24.40 | 9.70 | 0.00149588 | 28323.1 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 2034812.370 | -999.000 | 85.488074 | 0.08656562 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1024.1901 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 85.488074 | 100.35661437 | 4197.9300 | 999.8980 | 109.36658499 | 12.27 | 6.67 | 5.60 | 2571034.30 | 79.1437 | 79.143727 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 2034812.37 | 1538533.02 | 1.0000 | 100.35661437 | 85.488074 | 26.00 | 18.37 | 0.01040917 | 52659.4 | 10.90 | 10.90 | 0.00850000 | 32383.6 | 86.55679149 | 6.67 | 12.27 | 5.60 | 195231.493 | 1839580.88 | 30.30 | 0.01336696 | 21.83 | 25.38195000 | 29.6906 | 24.00 | 0.00903446 | 24.00 | 0.00903446 | 47.3769 | 1073281.54 | 0.00 | 2069100.09 | 1492412.63 | 100.35661437 | 26.00 | 18.64 | 0.01040917 | 52659.4 | 11.48 | 11.17 | 0.00813092 | 32041.9 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 869378.304 | 869378.304 | 25.646422 | 0.00760570 | 13371.477 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 85.488074 | 100.35661437 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 28.0365 | 28.600762 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 06:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 869378.30 | 869378.30 | 1.0000 | 30.10698431 | 25.646422 | -15.94 | -15.94 | 0.00099011 | -13566.9 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 7.60492480 | 60.00 | 32.22 | 27.78 | 0.000 | 869378.30 | -16.30 | 0.00092409 | -16.30 | 25.38195000 | 98.9688 | 18.93 | 0.00732577 | 19.29 | 0.00700352 | 49.1347 | 471600.12 | 0.00 | 705771.28 | 705771.28 | 30.10698431 | 2.80 | -2.80 | 0.00099011 | 5294.9 | 26.09 | 9.89 | 0.00099011 | 28737.0 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 211940.871 | -999.000 | 9.293897 | 0.00901645 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7758 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.293897 | 10.91034133 | 4197.9300 | 999.8980 | 109.36658499 | 12.27 | 6.67 | 5.60 | 2571034.30 | 8.2434 | 8.243409 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 211940.87 | 164259.88 | 1.0000 | 10.91034133 | 9.293897 | 25.72 | 18.10 | 0.01018631 | 51808.5 | 10.90 | 10.90 | 0.00850000 | 32382.8 | 9.01553482 | 6.67 | 12.27 | 5.60 | 21224.732 | 190716.14 | 30.30 | 0.01336696 | 21.83 | 2.53819000 | 27.3103 | 24.00 | 0.00898901 | 24.00 | 0.00898901 | 47.1422 | 124523.77 | 0.00 | 215681.38 | 158891.54 | 10.91034133 | 25.72 | 18.37 | 0.01018631 | 51808.5 | 11.50 | 11.17 | 0.00812267 | 32039.9 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 85698.229 | 85698.229 | 2.788169 | 0.00074973 | 1339.908 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 9.293897 | 10.91034133 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 2.7637 | 2.819296 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 05:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 85698.23 | 85698.23 | 1.0000 | 3.27310240 | 2.788169 | -13.26 | -13.26 | 0.00149089 | -9628.2 | 12.80 | 11.37 | 0.00800000 | 33059.8 | 0.74964901 | 60.00 | 32.22 | 27.78 | 0.000 | 85698.23 | -16.30 | 0.00092409 | -16.30 | 2.53819000 | 91.0343 | 17.65 | 0.00724595 | 17.37 | 0.00695340 | 55.0542 | 53845.68 | 0.00 | 71432.71 | 71432.71 | 3.27310240 | 2.80 | -1.99 | 0.00149089 | 6549.9 | 24.46 | 9.72 | 0.00149089 | 28374.1 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 112522.331 | -999.000 | 5.352224 | 0.00478696 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.5626 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:ConstantVolume | 5.352224 | 6.28311167 | 4197.9300 | 999.8980 | 109.36658499 | 12.27 | 6.67 | 5.60 | 2571034.30 | 4.3765 | 4.376539 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 112522.33 | 87614.58 | 1.0000 | 6.28311167 | 5.352224 | 25.01 | 17.78 | 0.01007162 | 50790.6 | 11.39 | 11.29 | 0.00850000 | 32881.9 | 4.78647176 | 6.67 | 12.27 | 5.60 | 9075.523 | 103446.81 | 28.16 | 0.01336316 | 21.21 | 1.20015641 | 22.4235 | 24.00 | 0.00901146 | 24.00 | 0.00901146 | 47.2566 | 66100.37 | 0.00 | 114549.57 | 85164.02 | 6.28311167 | 25.01 | 18.05 | 0.01007162 | 50790.6 | 11.77 | 11.38 | 0.00821778 | 32559.2 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 275622.099 | 275622.099 | 5.352224 | 0.00241126 | 5977.735 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | CAV_BAS FAN | Fan:ConstantVolume | 5.352224 | 6.28311167 | 4197.9300 | 999.8980 | 26.58993806 | 54.44 | 82.22 | 27.78 | 3100878.57 | 8.8885 | 9.067401 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 275622.10 | 275622.10 | 1.0000 | 6.28311167 | 5.352224 | -3.66 | -7.04 | 0.00092409 | -1367.9 | 40.00 | 20.89 | 0.00800000 | 60796.0 | 2.41101638 | 60.00 | 32.22 | 27.78 | 0.000 | 275622.10 | -16.30 | 0.00092409 | -16.30 | 1.20015641 | 22.4235 | 0.00 | 0.00092409 | 23.06 | 0.00092409 | 5.1951 | 0.00 | 0.00 | 223524.84 | 223524.84 | 6.28311167 | 12.80 | 3.26 | 0.00092409 | 15195.0 | 48.14 | 18.28 | 0.00092409 | 50770.5 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 432985.536 | 304627.056 | 21.823134 | 0.01060379 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.8590 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 402224.48 | 395504.12 | 0.9290 | -999.0 | -999.0 | 28.48 | 17.76 | 0.00861723 | 50622.6 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 402224.48 | 30.30 | 0.01336696 | 21.83 | 0.33839277 | -999.0000 | 27.00 | 0.00854233 | 27.00 | 0.00854233 | 37.5164 | 370794.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9630.353 | 6809.523 | 0.491025 | 0.00023585 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0846 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 8927.91 | 8620.68 | 0.9271 | -999.0 | -999.0 | 27.96 | 17.68 | 0.00873857 | 50402.3 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8927.91 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | -999.0000 | 27.00 | 0.00858656 | 27.00 | 0.00858656 | 37.7056 | 8351.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 92151.154 | 65107.069 | 4.691708 | 0.00225678 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.1050 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:10:00 | Sensible | 85449.93 | 82378.75 | 0.9273 | -999.0 | -999.0 | 27.96 | 17.69 | 0.00874955 | 50429.8 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 85449.93 | 26.67 | 0.01336053 | 20.77 | 0.15632344 | -999.0000 | 27.00 | 0.00859058 | 27.00 | 0.00859058 | 37.7232 | 79794.64 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9374.157 | 6625.138 | 0.477539 | 0.00022957 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1021.0970 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8691.66 | 8384.47 | 0.9272 | -999.0 | -999.0 | 27.96 | 17.69 | 0.00874525 | 50419.1 | 12.80 | 11.87 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8691.66 | 26.67 | 0.01336053 | 20.77 | 0.01563234 | -999.0000 | 27.00 | 0.00858906 | 27.00 | 0.00858906 | 37.7166 | 8123.83 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 432985.536 | 432985.536 | 21.823134 | 0.01060379 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 432985.54 | 432985.54 | 1.0000 | 25.61872922 | 21.823134 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 432985.54 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.5506 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9630.353 | 9630.353 | 0.491025 | 0.00023585 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9630.35 | 9630.35 | 1.0000 | 0.57642652 | 0.491025 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9630.35 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1836 | 0.00 | 0.00247647 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 92151.154 | 92151.154 | 4.691708 | 0.00225678 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 92151.15 | 92151.15 | 1.0000 | 5.50771510 | 4.691708 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 92151.15 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.3319 | 0.00 | 0.00148430 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9374.157 | 9374.157 | 0.477539 | 0.00022957 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1739 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9374.16 | 9374.16 | 1.0000 | 0.56059508 | 0.477539 | -16.30 | -16.30 | 0.00092409 | -14095.8 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9374.16 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2735 | 0.00 | 0.00148387 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 22473.716 | 22473.716 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.823134 | 25.61872922 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 22473.72 | 22473.72 | 1.0000 | 25.61872922 | 21.823134 | -0.25 | -0.25 | 0.00838253 | 20706.3 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22473.72 | -16.30 | 0.00092409 | -16.30 | 0.33839277 | 1.5506 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.3272 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.491025 | 0.57642652 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.57642652 | 0.491025 | -0.52 | -2.51 | 0.00242704 | 5546.1 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.1836 | 0.00 | 0.00247647 | 25.44 | 0.00247647 | 12.0381 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10381.926 | 10381.926 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.691708 | 5.50771510 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 10381.93 | 10381.93 | 1.0000 | 5.50771510 | 4.691708 | -0.54 | -4.12 | 0.00146563 | 3118.2 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10381.93 | -16.30 | 0.00092409 | -16.30 | 0.15632344 | 3.3319 | 0.00 | 0.00148430 | 23.72 | 0.00148430 | 8.0131 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 1038.193 | 1038.193 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1739 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.477539 | 0.56059508 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | BUFFALO.NIAGARA.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 1038.19 | 1038.19 | 1.0000 | 0.56059508 | 0.477539 | -0.53 | -4.11 | 0.00146555 | 3127.6 | 40.00 | 20.89 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 1038.19 | -16.30 | 0.00092409 | -16.30 | 0.01563234 | 3.2735 | 0.00 | 0.00148387 | 22.47 | 0.00148387 | 8.6361 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.24 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 85.49 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 9.29 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.35 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2362.50 | 1879.50 | 413.50 |
CORE_BOTTOM | 2335.67 | 1603.17 | 16.50 |
CORE_MID | 1876.00 | 3199.50 | 245.67 |
CORE_TOP | 2580.00 | 3729.50 | 1102.83 |
PERIMETER_BOT_ZN_3 | 2326.83 | 3383.67 | 677.00 |
PERIMETER_BOT_ZN_2 | 2562.67 | 3389.67 | 738.83 |
PERIMETER_BOT_ZN_1 | 2644.67 | 3109.17 | 719.00 |
PERIMETER_BOT_ZN_4 | 2772.00 | 2414.67 | 380.33 |
PERIMETER_MID_ZN_3 | 3270.00 | 4124.00 | 1996.50 |
PERIMETER_MID_ZN_2 | 2933.17 | 3349.83 | 1686.67 |
PERIMETER_MID_ZN_1 | 3110.17 | 3546.33 | 1469.33 |
PERIMETER_MID_ZN_4 | 3334.00 | 3864.67 | 1722.17 |
PERIMETER_TOP_ZN_3 | 3669.83 | 4365.00 | 2514.67 |
PERIMETER_TOP_ZN_2 | 3833.83 | 3996.00 | 2361.67 |
PERIMETER_TOP_ZN_1 | 3521.00 | 3915.17 | 2031.00 |
PERIMETER_TOP_ZN_4 | 3652.50 | 4097.17 | 2187.00 |
DATACENTER_BOT_ZN_6 | 5886.00 | 686.67 | 686.67 |
DATACENTER_MID_ZN_6 | 4997.67 | 221.67 | 76.67 |
DATACENTER_TOP_ZN_6 | 4545.50 | 674.33 | 229.17 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5463.17 | 5463.17 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5936.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 47.50 | 0.00 | 3.17 |
CORE_BOTTOM | 0.00 | 0.83 | 0.00 | 0.00 |
CORE_MID | 1.33 | 0.00 | 0.50 | 0.00 |
CORE_TOP | 16.17 | 0.00 | 3.33 | 0.00 |
PERIMETER_BOT_ZN_3 | 2.50 | 0.83 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 3.67 | 10.17 | 0.00 | 10.17 |
PERIMETER_BOT_ZN_1 | 4.83 | 18.83 | 0.00 | 17.67 |
PERIMETER_BOT_ZN_4 | 0.67 | 84.33 | 0.00 | 31.17 |
PERIMETER_MID_ZN_3 | 144.33 | 0.00 | 46.67 | 0.00 |
PERIMETER_MID_ZN_2 | 69.00 | 12.17 | 4.83 | 12.17 |
PERIMETER_MID_ZN_1 | 61.33 | 14.17 | 3.83 | 14.17 |
PERIMETER_MID_ZN_4 | 50.33 | 22.67 | 1.67 | 12.50 |
PERIMETER_TOP_ZN_3 | 314.33 | 1.67 | 107.67 | 1.17 |
PERIMETER_TOP_ZN_2 | 199.50 | 12.67 | 40.50 | 12.33 |
PERIMETER_TOP_ZN_1 | 185.50 | 16.33 | 40.33 | 15.00 |
PERIMETER_TOP_ZN_4 | 143.00 | 23.50 | 26.83 | 12.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 137.50 | 0.00 | 126.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 356.67 | 313.50 | 115.67 | 199.83 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 1.203 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.917 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.719 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.705 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.869 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.235 | 0.061 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 1.159 | 0.059 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 1.761 | 0.061 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.728 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.102 | 0.151 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 1.041 | 0.138 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.233 | 0.143 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.794 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.207 | 0.177 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 1.055 | 0.171 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.278 | 0.177 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.481 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.01 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.69 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.99 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.99 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.48 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.01 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.69 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.99 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.48 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1027.73 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 49746921.05 | 0.00 | 49746921.05 | 0.00 | 49746921.05 | 37848132.68 | 3990.59 | 1241.14 | 3528.27 | 319.44 |
CORE_BOTTOM | 39744266.41 | 0.00 | 39744266.41 | 0.00 | 39744266.41 | 33990283.35 | 4644.54 | 64.66 | 4050.79 | 541.68 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 6086.43 | 79.02 | 2594.54 | 408.87 |
CORE_TOP | 29121782.02 | 0.00 | 29121782.02 | 0.00 | 29121782.02 | 33990283.35 | 6344.08 | 23.10 | 2392.83 | 477.09 |
PERIMETER_BOT_ZN_3 | 4736421.24 | 0.00 | 4736421.24 | 584665.50 | 5321086.73 | 4267819.30 | 5394.00 | 41.92 | 3324.07 | 541.68 |
PERIMETER_BOT_ZN_2 | 4340714.54 | 0.00 | 4340714.54 | 389776.73 | 4730491.27 | 2750345.05 | 3508.58 | 11.34 | 5240.08 | 541.68 |
PERIMETER_BOT_ZN_1 | 6231338.46 | 0.00 | 6231338.46 | 584665.50 | 6816003.95 | 4267912.63 | 4119.09 | 100.96 | 4539.95 | 541.68 |
PERIMETER_BOT_ZN_4 | 6167475.91 | 0.00 | 6167475.91 | 389776.73 | 6557252.64 | 2750345.05 | 3454.59 | 5.11 | 5300.30 | 541.68 |
PERIMETER_MID_ZN_3 | 38103533.69 | 0.00 | 38103533.69 | 1371204.53 | 39474738.22 | 42678193.03 | 5763.52 | 88.20 | 2908.27 | 408.87 |
PERIMETER_MID_ZN_2 | 40166136.41 | 0.00 | 40166136.41 | 914135.73 | 41080272.14 | 27503450.52 | 3956.73 | 4.58 | 4798.69 | 1317.88 |
PERIMETER_MID_ZN_1 | 53908027.68 | 0.00 | 53908027.68 | 1371204.53 | 55279232.21 | 42679126.28 | 4065.25 | 28.01 | 4666.74 | 408.87 |
PERIMETER_MID_ZN_4 | 41596093.11 | 0.00 | 41596093.11 | 914135.73 | 42510228.84 | 27503450.52 | 3949.80 | 3.99 | 4806.21 | 408.87 |
PERIMETER_TOP_ZN_3 | 4129486.65 | 0.00 | 4129486.65 | 1702496.76 | 5831983.40 | 4267819.30 | 4082.18 | 11.22 | 4666.59 | 477.09 |
PERIMETER_TOP_ZN_2 | 4025164.03 | 0.00 | 4025164.03 | 1134997.06 | 5160161.10 | 2750345.05 | 4017.33 | 1.24 | 4741.43 | 477.09 |
PERIMETER_TOP_ZN_1 | 5441604.89 | 0.00 | 5441604.89 | 1702496.76 | 7144101.65 | 4267912.63 | 4060.25 | 3.14 | 4696.62 | 477.09 |
PERIMETER_TOP_ZN_4 | 4284310.41 | 0.00 | 4284310.41 | 1134997.06 | 5419307.47 | 2750345.05 | 4006.58 | 1.82 | 4751.60 | 477.09 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.49E+10 | 0.00 | 0.49E+10 | 53330677.35 | 0.50E+10 | 0.50E+10 | 6769.22 | 4393.66 | 5461.73 | 2035.54 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.2158 | 0.0000 | 2.2158 | 0.0000 | 2.2158 | 1.2002 | 1362.24 | 1238.09 | 3342.67 |
CORE_BOTTOM | 1.7063 | 0.0000 | 1.7063 | 0.0000 | 1.7063 | 1.0778 | 2274.14 | 62.04 | 3606.81 |
CORE_MID | 13.4042 | 0.0000 | 13.4042 | 0.0000 | 13.4042 | 10.7782 | 3404.24 | 78.98 | 2459.78 |
CORE_TOP | 1.3140 | 0.0000 | 1.3140 | 0.0000 | 1.3140 | 1.0778 | 3634.69 | 23.10 | 2285.22 |
PERIMETER_BOT_ZN_3 | 0.2032 | 0.0000 | 0.2032 | 0.0139 | 0.2171 | 0.1353 | 3018.85 | 39.18 | 2884.97 |
PERIMETER_BOT_ZN_2 | 0.1863 | 0.0000 | 0.1863 | 0.0092 | 0.1956 | 0.0872 | 1179.74 | 8.81 | 4754.45 |
PERIMETER_BOT_ZN_1 | 0.2713 | 0.0000 | 0.2713 | 0.0139 | 0.2852 | 0.1353 | 1758.70 | 99.02 | 4085.28 |
PERIMETER_BOT_ZN_4 | 0.2653 | 0.0000 | 0.2653 | 0.0092 | 0.2746 | 0.0872 | 1138.65 | 2.92 | 4801.43 |
PERIMETER_MID_ZN_3 | 1.7078 | 0.0000 | 1.7078 | 0.0325 | 1.7403 | 1.3533 | 3083.27 | 87.92 | 2771.81 |
PERIMETER_MID_ZN_2 | 1.6651 | 0.0000 | 1.6651 | 0.0230 | 1.6881 | 0.8721 | 1295.52 | 3.14 | 3735.35 |
PERIMETER_MID_ZN_1 | 2.4395 | 0.0000 | 2.4395 | 0.0325 | 2.4721 | 1.3533 | 1391.27 | 26.75 | 4524.98 |
PERIMETER_MID_ZN_4 | 1.8636 | 0.0000 | 1.8636 | 0.0217 | 1.8853 | 0.8721 | 1291.23 | 1.87 | 4649.90 |
PERIMETER_TOP_ZN_3 | 0.1862 | 0.0000 | 0.1862 | 0.0404 | 0.2266 | 0.1353 | 1376.93 | 11.03 | 4555.04 |
PERIMETER_TOP_ZN_2 | 0.1824 | 0.0000 | 0.1824 | 0.0269 | 0.2093 | 0.0872 | 1324.77 | 0.85 | 4617.38 |
PERIMETER_TOP_ZN_1 | 0.2473 | 0.0000 | 0.2473 | 0.0404 | 0.2877 | 0.1353 | 1355.18 | 2.45 | 4585.37 |
PERIMETER_TOP_ZN_4 | 0.1931 | 0.0000 | 0.1931 | 0.0269 | 0.2200 | 0.0872 | 1317.79 | 0.35 | 4624.86 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 219.1860 | 0.0000 | 219.1860 | 1.2780 | 220.4640 | 158.4706 | 3952.22 | 4373.15 | 4861.88 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 84374584.55 | 0.00 | 84374584.55 | 48026705.38 | 3484.15 | 3.64 | 5272.21 | 541.68 |
VAV_MID WITH REHEAT | 0.65E+09 | 0.00 | 0.65E+09 | 0.48E+09 | 3972.93 | 5.41 | 4781.66 | 408.87 |
VAV_TOP WITH REHEAT | 64773998.35 | 0.00 | 64773998.35 | 48026705.38 | 4023.25 | 0.84 | 4735.91 | 476.84 |
CAV_BAS | 68556263.83 | 0.00 | 68556263.83 | 37848132.68 | 3919.41 | 3.17 | 4837.41 | 319.44 |
AIRLOOP DATACENTER BASEMENT | 7287763.88 | 0.00 | 7287763.88 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3366645.00 | 0.00 | 3366645.00 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 336664.50 | 0.00 | 336664.50 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.6280 | 0.0000 | 3.6280 | 1.5229 | 1159.86 | 2.49 | 4780.65 |
VAV_MID WITH REHEAT | 29.2465 | 0.0000 | 29.2465 | 15.2292 | 1303.97 | 4.55 | 4634.48 |
VAV_TOP WITH REHEAT | 2.9258 | 0.0000 | 2.9258 | 1.5229 | 1327.68 | 0.35 | 4614.97 |
CAV_BAS | 3.0536 | 0.0000 | 3.0536 | 1.2002 | 1333.77 | 1.04 | 4608.19 |
AIRLOOP DATACENTER BASEMENT | 0.3406 | 0.0000 | 0.3406 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1574 | 0.0000 | 0.1574 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0157 | 0.0000 | 0.0157 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.04 | 3695.50 | 0.00 | 0.00 | 0.00 | 1707.79 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.19 | 3347.03 | 0.00 | 0.00 | 0.00 | 1863.88 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.15 | 3119.80 | 0.00 | 0.00 | 0.00 | 2221.83 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1229.67 | 3743.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.5732 | 0.0000 | 0.0000 | 0.0000 | 2.3367 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 44.9120 | 0.0000 | 0.0000 | 0.0000 | 22.4576 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.6963 | 0.0000 | 0.0000 | 0.0000 | 2.2416 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.6548 | 4.7061 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4664 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2155 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0215 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1386 |
Defaulted Fields | 1179 |
Fields with Defaults | 3922 |
Autosized Fields | 333 |
Autosizable Fields | 412 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
Electricity:Building | 17957.18 | 247233.96 | 01-JAN-09:10 | 1055078.17 | 01-DEC-16:40 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17957.18 | 247233.96 | 01-JAN-09:10 | 1055078.17 | 01-DEC-16:40 |
InteriorLights:Electricity | 2743.76 | 13024.70 | 01-JAN-09:10 | 261074.09 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2743.76 | 13024.70 | 01-JAN-09:10 | 261074.09 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 2743.76 | 13024.70 | 01-JAN-09:10 | 261074.09 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2743.76 | 13024.70 | 01-JAN-09:10 | 261074.09 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.18 | 818.50 | 01-JAN-09:10 | 4026.32 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.83 | 59.73 | 01-JAN-09:10 | 1750.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.83 | 59.73 | 01-JAN-09:10 | 1750.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.89 | 527.47 | 01-JAN-08:50 | 2594.71 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.89 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.89 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.09 | 818.51 | 01-JAN-08:50 | 4026.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.75 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.75 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.89 | 527.47 | 01-JAN-09:10 | 2594.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.89 | 38.49 | 01-JAN-09:10 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.89 | 38.49 | 01-JAN-09:10 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 541.89 | 8184.99 | 01-JAN-09:10 | 40263.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 138.47 | 597.26 | 01-JAN-09:10 | 17500.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 138.47 | 597.26 | 01-JAN-09:10 | 17500.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 348.96 | 5274.72 | 01-JAN-08:50 | 25947.12 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.98 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 88.98 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 541.03 | 8185.12 | 01-JAN-08:50 | 40263.91 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.60 | 597.27 | 01-JAN-08:50 | 17500.38 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.60 | 597.27 | 01-JAN-08:50 | 17500.38 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 348.91 | 5274.69 | 01-JAN-09:10 | 25947.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.93 | 384.90 | 01-JAN-09:10 | 11277.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.93 | 384.90 | 01-JAN-09:10 | 11277.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.19 | 818.50 | 01-JAN-09:10 | 4026.32 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.85 | 59.73 | 01-JAN-09:10 | 1750.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.85 | 59.73 | 01-JAN-09:10 | 1750.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.90 | 527.47 | 01-JAN-08:50 | 2594.71 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.90 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.90 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.10 | 818.51 | 01-JAN-08:50 | 4026.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.76 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.76 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.89 | 527.47 | 01-JAN-09:10 | 2594.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.89 | 38.49 | 01-JAN-09:10 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.89 | 38.49 | 01-JAN-09:10 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1995.73 | 5267.17 | 06-JAN-08:00 | 505858.75 | 14-AUG-10:10 |
HeatRejection:Electricity | 898.76 | 1823.38 | 04-JAN-08:00 | 87066.30 | 01-JUN-15:30 |
General:HeatRejection:Electricity | 898.76 | 1823.38 | 04-JAN-08:00 | 87066.30 | 01-JUN-15:30 |
Electricity:HVAC | 4789.68 | 73873.98 | 01-JAN-04:00 | 423621.94 | 09-AUG-15:30 |
ExteriorEquipment:Electricity | 1914.38 | 28294.68 | 01-JAN-00:10 | 117203.81 | 02-NOV-07:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3726.76 | 01-DEC-16:50 |
ElectricityPurchased:Facility | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
ElectricityPurchased:Plant | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
Cogeneration:ElectricityPurchased | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
General:Cogeneration:ElectricityPurchased | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
ElectricityNet:Plant | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
Cogeneration:ElectricityNet | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
General:Cogeneration:ElectricityNet | 27045.18 | 361322.81 | 29-JAN-10:20 | 1927706.14 | 07-AUG-15:30 |
Fans:Electricity | 2256.80 | 42331.85 | 01-JAN-02:00 | 244430.48 | 09-AUG-15:30 |
General:Fans:Electricity | 2256.80 | 42331.85 | 01-JAN-02:00 | 244430.48 | 09-AUG-15:30 |
ExteriorLights:Electricity | 447.99 | 0.00 | 01-JAN-08:00 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 447.99 | 0.00 | 01-JAN-08:00 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
HeatRecovery:Electricity | 41.22 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
General:HeatRecovery:Electricity | 41.22 | 0.00 | 01-JAN-00:10 | 5613.48 | 02-JAN-07:10 |
Cooling:Electricity | 3028.25 | 27107.44 | 30-JAN-07:20 | 505944.19 | 14-AUG-10:20 |
General:Cooling:Electricity | 3028.25 | 27107.44 | 30-JAN-07:20 | 505944.19 | 14-AUG-10:20 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 17.95 | 0.00 | 01-JAN-00:10 | 6182.48 | 23-JAN-21:00 |
General:Humidifier:Electricity | 17.95 | 0.00 | 01-JAN-00:10 | 6182.48 | 23-JAN-21:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 482.66 | 3398.79 | 13-FEB-03:50 | 66139.41 | 01-AUG-15:00 |
General:Pumps:Electricity | 482.66 | 3398.79 | 13-FEB-03:50 | 66139.41 | 01-AUG-15:00 |
WIRED_LTG_ELECTRICITY | 77.10 | 0.00 | 01-JAN-00:10 | 7336.18 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2554.08 | 5695.87 | 23-JAN-05:40 | 1686398.24 | 02-JAN-05:10 |
NaturalGas:Plant | 2554.08 | 5695.87 | 23-JAN-05:40 | 1686398.24 | 02-JAN-05:10 |
Heating:NaturalGas | 1805.49 | 0.00 | 01-JAN-00:40 | 1680702.37 | 02-JAN-05:10 |
Boiler:Heating:NaturalGas | 1805.49 | 0.00 | 01-JAN-00:40 | 1680702.37 | 02-JAN-05:10 |
WaterSystems:NaturalGas | 748.59 | 5695.87 | 06-JAN-04:10 | 84373.55 | 17-FEB-12:40 |
Water Heater:WaterSystems:NaturalGas | 748.59 | 5695.87 | 06-JAN-04:10 | 84373.55 | 17-FEB-12:40 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 16324.69 | 133024.35 | 30-JAN-07:10 | 3038194.92 | 15-AUG-14:40 |
PlantLoopCoolingDemand:HVAC | 16324.69 | 133024.35 | 30-JAN-07:10 | 3038194.92 | 15-AUG-14:40 |
CoolingCoils:PlantLoopCoolingDemand | 16324.69 | 133024.35 | 30-JAN-07:10 | 3038194.92 | 15-AUG-14:40 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 5512.29 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-16:00 |
Water:HVAC | 6.68 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
Humidifier:Water | 6.68 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
General:Humidifier:Water | 6.68 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
MainsWater:Facility | 5512.29 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-16:00 |
MainsWater:HVAC | 6.68 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
Humidifier:MainsWater | 6.68 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
General:Humidifier:MainsWater | 6.68 | 0.00 | 01-JAN-00:10 | 0.00 | 23-JAN-21:00 |
Water:Plant | 5505.61 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-16:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 5505.61 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-16:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 3225.44 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:40 |
General:HeatRejection:Water | 3225.44 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:40 |
HeatRejection:MainsWater | 3225.44 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:40 |
General:HeatRejection:MainsWater | 3225.44 | 0.00 | 01-JAN-00:10 | 0.00 | 04-AUG-14:40 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 49509.78 | 211746.70 | 30-JAN-03:40 | 11717416.89 | 15-AUG-14:40 |
EnergyTransfer:Building | 17726.35 | 88147.86 | 15-JAN-15:20 | 1559629.02 | 09-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 616.36 | 0.00 | 01-JAN-00:10 | 69140.48 | 05-SEP-05:10 |
Heating:EnergyTransfer | 1057.82 | 0.00 | 01-FEB-00:20 | 1245929.56 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.57 | 0.00 | 01-JAN-00:10 | 12583.31 | 17-JUN-16:10 |
General:Heating:EnergyTransfer | 1057.82 | 0.00 | 01-FEB-00:20 | 1245929.56 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.57 | 0.00 | 01-JAN-00:10 | 12583.31 | 17-JUN-16:10 |
Cooling:EnergyTransfer | 16668.54 | 84611.69 | 30-JAN-06:00 | 1559629.02 | 09-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 613.79 | 0.00 | 01-JAN-00:10 | 69140.48 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 16668.54 | 84611.69 | 30-JAN-06:00 | 1559629.02 | 09-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 613.79 | 0.00 | 01-JAN-00:10 | 69140.48 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 565.07 | 0.00 | 01-JAN-00:10 | 50685.87 | 07-AUG-09:30 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 565.07 | 0.00 | 01-JAN-00:10 | 50685.87 | 07-AUG-09:30 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 565.07 | 0.00 | 01-JAN-00:10 | 50685.87 | 07-AUG-09:30 |
EnergyTransfer:Zone:CORE_MID | 3982.72 | 0.00 | 01-JAN-00:40 | 474974.66 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 16.00 | 0.00 | 01-JAN-00:10 | 474974.66 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 16.00 | 0.00 | 01-JAN-00:10 | 474974.66 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3966.72 | 0.00 | 01-JAN-00:40 | 414576.15 | 18-SEP-10:00 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3966.72 | 0.00 | 01-JAN-00:40 | 414576.15 | 18-SEP-10:00 |
EnergyTransfer:Zone:CORE_TOP | 369.56 | 0.00 | 01-JAN-00:40 | 67271.40 | 09-JAN-05:20 |
Heating:EnergyTransfer:Zone:CORE_TOP | 20.65 | 0.00 | 01-JAN-00:40 | 67271.40 | 09-JAN-05:20 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 20.65 | 0.00 | 01-JAN-00:40 | 67271.40 | 09-JAN-05:20 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 348.91 | 0.00 | 01-JAN-00:20 | 48403.00 | 17-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 348.91 | 0.00 | 01-JAN-00:20 | 48403.00 | 17-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 61.26 | 0.00 | 01-JAN-00:10 | 9701.69 | 14-AUG-12:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.72 | 0.00 | 01-JAN-00:10 | 9029.84 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 1.72 | 0.00 | 01-JAN-00:10 | 9029.84 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.53 | 0.00 | 01-JAN-00:10 | 9701.69 | 14-AUG-12:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 59.53 | 0.00 | 01-JAN-00:10 | 9701.69 | 14-AUG-12:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 54.07 | 0.00 | 01-JAN-00:10 | 11756.35 | 17-JUL-07:40 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.48 | 0.00 | 01-JAN-00:10 | 6800.64 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 1.48 | 0.00 | 01-JAN-00:10 | 6800.64 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.59 | 0.00 | 01-JAN-00:10 | 11756.35 | 17-JUL-07:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.59 | 0.00 | 01-JAN-00:10 | 11756.35 | 17-JUL-07:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 83.12 | 0.00 | 01-JAN-00:10 | 17654.14 | 11-OCT-12:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.52 | 0.00 | 01-JAN-00:10 | 11270.52 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 2.52 | 0.00 | 01-JAN-00:10 | 11270.52 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 80.59 | 0.00 | 01-JAN-00:10 | 17654.14 | 11-OCT-12:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 80.59 | 0.00 | 01-JAN-00:10 | 17654.14 | 11-OCT-12:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 84.11 | 0.00 | 01-JAN-00:10 | 15728.75 | 10-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 3855.74 | 06-FEB-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.19 | 0.00 | 01-JAN-00:10 | 3855.74 | 06-FEB-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 83.92 | 0.00 | 01-JAN-00:10 | 15728.75 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 83.92 | 0.00 | 01-JAN-00:10 | 15728.75 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 597.16 | 0.00 | 01-JAN-00:40 | 122382.42 | 06-FEB-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 220.67 | 0.00 | 01-JAN-00:40 | 122382.42 | 06-FEB-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 220.67 | 0.00 | 01-JAN-00:40 | 122382.42 | 06-FEB-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 376.49 | 0.00 | 01-JAN-00:20 | 91963.26 | 21-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 376.49 | 0.00 | 01-JAN-00:20 | 91963.26 | 21-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 537.76 | 0.00 | 01-JAN-00:40 | 146173.95 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 131.43 | 0.00 | 01-JAN-00:40 | 146173.95 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 131.43 | 0.00 | 01-JAN-00:40 | 146173.95 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 406.33 | 0.00 | 01-JAN-00:20 | 123181.47 | 13-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 406.33 | 0.00 | 01-JAN-00:20 | 123181.47 | 13-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 773.14 | 0.00 | 01-JAN-00:40 | 176962.98 | 31-OCT-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 142.95 | 0.00 | 01-JAN-00:40 | 171666.80 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 142.95 | 0.00 | 01-JAN-00:40 | 171666.80 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 630.20 | 0.00 | 01-JAN-00:20 | 176962.98 | 31-OCT-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 630.20 | 0.00 | 01-JAN-00:20 | 176962.98 | 31-OCT-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 547.49 | 0.00 | 01-JAN-00:40 | 144690.88 | 13-FEB-05:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 103.12 | 0.00 | 01-JAN-00:40 | 144690.88 | 13-FEB-05:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 103.12 | 0.00 | 01-JAN-00:40 | 144690.88 | 13-FEB-05:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 444.37 | 0.00 | 01-JAN-00:20 | 130207.16 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 444.37 | 0.00 | 01-JAN-00:20 | 130207.16 | 10-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 82.42 | 0.00 | 01-JAN-00:40 | 16401.67 | 06-FEB-03:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.18 | 0.00 | 01-JAN-00:40 | 16401.67 | 06-FEB-03:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 47.18 | 0.00 | 01-JAN-00:40 | 16401.67 | 06-FEB-03:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.25 | 0.00 | 01-JAN-00:10 | 10269.97 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 35.25 | 0.00 | 01-JAN-00:10 | 10269.97 | 21-JUL-13:50 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 65.77 | 0.00 | 01-JAN-00:40 | 15697.79 | 07-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.78 | 0.00 | 01-JAN-00:40 | 15697.79 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 27.78 | 0.00 | 01-JAN-00:40 | 15697.79 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.99 | 0.00 | 01-JAN-00:20 | 12170.01 | 12-JUN-09:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 37.99 | 0.00 | 01-JAN-00:20 | 12170.01 | 12-JUN-09:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 91.25 | 0.00 | 01-JAN-00:40 | 19904.77 | 13-FEB-04:40 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.75 | 0.00 | 01-JAN-00:40 | 19904.77 | 13-FEB-04:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 33.75 | 0.00 | 01-JAN-00:40 | 19904.77 | 13-FEB-04:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.50 | 0.00 | 01-JAN-00:20 | 17996.53 | 21-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 57.50 | 0.00 | 01-JAN-00:20 | 17996.53 | 21-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 64.23 | 0.00 | 01-JAN-00:40 | 16928.19 | 07-FEB-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.60 | 0.00 | 01-JAN-00:40 | 16928.19 | 07-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 22.60 | 0.00 | 01-JAN-00:40 | 16928.19 | 07-FEB-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.63 | 0.00 | 01-JAN-00:20 | 13631.90 | 10-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 41.63 | 0.00 | 01-JAN-00:20 | 13631.90 | 10-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 49.78 | 0.00 | 01-JAN-00:10 | 8495.82 | 17-JUL-07:10 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 6.87 | 0.00 | 01-JAN-00:10 | 4677.85 | 08-FEB-13:20 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 6.87 | 0.00 | 01-JAN-00:10 | 4677.85 | 08-FEB-13:20 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 42.91 | 0.00 | 01-JAN-00:10 | 8495.82 | 17-JUL-07:10 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 42.91 | 0.00 | 01-JAN-00:10 | 8495.82 | 17-JUL-07:10 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 474.46 | 0.00 | 01-JAN-00:40 | 163271.78 | 02-JAN-06:20 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 204.35 | 0.00 | 01-JAN-00:40 | 163271.78 | 02-JAN-06:20 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 204.35 | 0.00 | 01-JAN-00:40 | 163271.78 | 02-JAN-06:20 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 270.11 | 0.00 | 01-JAN-00:10 | 69034.64 | 17-JUL-12:10 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 270.11 | 0.00 | 01-JAN-00:10 | 69034.64 | 17-JUL-12:10 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 107.35 | 0.00 | 01-JAN-00:40 | 28228.48 | 06-FEB-05:40 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 64.56 | 0.00 | 01-JAN-00:40 | 28228.48 | 06-FEB-05:40 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 64.56 | 0.00 | 01-JAN-00:40 | 28228.48 | 06-FEB-05:40 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.79 | 0.00 | 01-JAN-00:10 | 18659.18 | 21-JUL-13:50 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 42.79 | 0.00 | 01-JAN-00:10 | 18659.18 | 21-JUL-13:50 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.57 | 9.06 | 30-JAN-05:20 | 8060.16 | 04-AUG-18:30 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.57 | 9.06 | 30-JAN-05:20 | 8060.16 | 04-AUG-18:30 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 134.57 | 9.06 | 30-JAN-05:20 | 8060.16 | 04-AUG-18:30 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1134.32 | 0.66 | 20-JAN-08:00 | 76916.93 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.48 | 0.00 | 02-JAN-08:10 | 5497.25 | 23-JAN-24:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 6.48 | 0.00 | 02-JAN-08:10 | 5497.25 | 23-JAN-24:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1127.84 | 0.00 | 01-JAN-00:10 | 76916.93 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1127.84 | 0.00 | 01-JAN-00:10 | 76916.93 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.38 | 0.01 | 20-JAN-09:20 | 7746.17 | 02-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.93 | 0.00 | 02-JAN-08:40 | 586.88 | 23-JAN-24:00 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.93 | 0.00 | 02-JAN-08:40 | 586.88 | 23-JAN-24:00 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.44 | 0.00 | 01-JAN-00:10 | 7746.17 | 02-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 102.44 | 0.00 | 01-JAN-00:10 | 7746.17 | 02-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7146.99 | 84565.53 | 30-JAN-05:00 | 368322.65 | 11-AUG-10:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7146.99 | 84565.53 | 30-JAN-05:00 | 368322.65 | 11-AUG-10:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7146.99 | 84565.53 | 30-JAN-05:00 | 368322.65 | 11-AUG-10:00 |
PlantLoopHeatingDemand:Facility | 1761.22 | 0.00 | 01-JAN-00:40 | 1433970.68 | 26-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 444.85 | 0.00 | 01-JAN-00:10 | 55179.01 | 15-FEB-12:50 |
WaterSystems:PlantLoopHeatingDemand | 444.85 | 0.00 | 01-JAN-00:10 | 55179.01 | 15-FEB-12:50 |
General:WaterSystems:PlantLoopHeatingDemand | 444.85 | 0.00 | 01-JAN-00:10 | 55179.01 | 15-FEB-12:50 |
EnergyTransfer:HVAC | 17047.74 | 121246.85 | 30-JAN-03:40 | 2884978.56 | 15-AUG-14:40 |
HeatingCoils:EnergyTransfer | 1316.37 | 0.00 | 01-JAN-00:40 | 1416397.15 | 26-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 1316.37 | 0.00 | 01-JAN-00:40 | 1416397.15 | 26-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1316.37 | 0.00 | 01-JAN-00:40 | 1416397.15 | 26-DEC-07:10 |
CoolingCoils:EnergyTransfer | 13910.75 | 106001.99 | 30-JAN-07:10 | 2884978.56 | 15-AUG-14:40 |
HeatRecoveryForHeating:EnergyTransfer | 1706.35 | 0.00 | 01-JAN-00:10 | 667892.02 | 07-FEB-07:10 |
HeatRecoveryForCooling:EnergyTransfer | 114.27 | 0.00 | 01-JAN-00:10 | 329110.29 | 15-JUL-14:00 |
EnergyTransfer:Plant | 14735.68 | 0.00 | 01-JAN-00:40 | 7512367.13 | 05-JUL-16:00 |
LoopToLoop:EnergyTransfer | 4373.05 | -459.13 | 06-JAN-13:10 | 2381238.40 | 15-AUG-14:40 |
WaterSystems:EnergyTransfer | 444.85 | 0.00 | 01-JAN-00:10 | 55179.01 | 15-FEB-12:50 |
WaterUse:WaterSystems:EnergyTransfer | 444.85 | 0.00 | 01-JAN-00:10 | 55179.01 | 15-FEB-12:50 |
Boilers:EnergyTransfer | 1309.68 | 0.00 | 01-JAN-00:40 | 1402507.37 | 02-JAN-05:10 |
Chillers:EnergyTransfer | 3996.90 | 0.00 | 01-JAN-00:10 | 2378979.55 | 05-JUL-16:00 |
HeatRejection:EnergyTransfer | 4611.21 | 0.00 | 01-JAN-00:10 | 2728479.30 | 05-JUL-16:00 |
General:HeatRejection:EnergyTransfer | 4611.21 | 0.00 | 01-JAN-00:10 | 2728479.30 | 05-JUL-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.571 | -613.790 | 0.000 | 0.000 | 93.320 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -84.240 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -565.069 | 0.000 | 0.000 | 83.621 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 0.538 | 0.000 | 0.000 | 0.000 | 0.000 | -0.001 |
CORE_MID | 0.000 | 0.000 | 16.004 | -3966.710 | 0.000 | 0.000 | 864.151 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1722.536 |
CORE_TOP | 0.000 | 0.000 | 20.648 | -348.908 | 0.000 | 0.000 | 89.325 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -241.975 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 1.724 | -59.531 | 0.000 | 0.000 | 11.028 | 13.833 | 40.342 | 21.074 | 0.000 | 0.052 | 37.763 | 0.000 | -55.613 | 0.000 | -10.672 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 1.483 | -52.588 | 0.000 | 0.000 | 7.147 | 8.895 | 25.998 | 40.515 | 0.000 | 0.036 | 9.615 | 0.000 | -34.090 | 0.000 | -7.011 | 0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 2.524 | -80.591 | 0.000 | 0.000 | 10.949 | 13.747 | 40.343 | 75.506 | 0.000 | 0.049 | 0.005 | 0.000 | -50.453 | 0.000 | -10.611 | -1.464 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.187 | -83.924 | 0.000 | 0.000 | 6.955 | 8.889 | 25.998 | 39.761 | 0.000 | 0.031 | 48.977 | 0.000 | -39.165 | 0.000 | -7.709 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 220.668 | -376.490 | 0.000 | 0.000 | 114.982 | 138.469 | 403.423 | 219.433 | 0.000 | 1.206 | 0.015 | 0.000 | -499.118 | 0.000 | -220.905 | -1.668 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 131.432 | -406.330 | 0.000 | 0.000 | 54.234 | 88.979 | 259.981 | 407.823 | 0.000 | 0.755 | 0.000 | 0.000 | -314.650 | 0.000 | -149.382 | -72.841 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 142.950 | -630.190 | 0.000 | 0.000 | 112.193 | 137.601 | 403.429 | 756.174 | 0.000 | 1.061 | 0.011 | 0.000 | -478.853 | 0.000 | -231.243 | -213.120 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 103.120 | -444.370 | 0.000 | 0.000 | 73.853 | 88.926 | 259.979 | 408.105 | 0.000 | 0.730 | 0.018 | 0.000 | -336.450 | 0.000 | -153.603 | -0.291 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 47.176 | -35.247 | 0.000 | 0.000 | 11.682 | 13.847 | 40.342 | 22.428 | 0.000 | 0.140 | 0.001 | 0.000 | -47.254 | 0.000 | -26.163 | -26.950 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 27.784 | -37.988 | 0.000 | 0.000 | 7.439 | 8.898 | 25.998 | 41.095 | 0.000 | 0.087 | 0.001 | 0.000 | -29.941 | 0.000 | -17.777 | -25.595 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 33.751 | -57.496 | 0.000 | 0.000 | 11.410 | 13.760 | 40.343 | 76.202 | 0.000 | 0.124 | 0.001 | 0.000 | -45.296 | 0.000 | -27.253 | -45.545 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 22.600 | -41.628 | 0.000 | 0.000 | 7.486 | 8.893 | 25.998 | 41.025 | 0.000 | 0.086 | 0.000 | 0.000 | -32.087 | 0.000 | -18.248 | -14.124 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -134.573 | 0.000 | 0.000 | 0.950 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -24.897 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 6.484 | -1127.839 | 0.000 | 0.000 | 9.527 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -473.374 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.932 | -102.444 | 0.000 | 0.000 | 0.957 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -57.966 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7146.996 | 0.000 | 0.000 | 20.482 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -418.459 |
GROUNDFLOOR_PLENUM | 6.870 | -42.905 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.089 | 58.661 | 0.000 | 0.000 | 0.000 | -22.715 | 0.000 |
MIDFLOOR_PLENUM | 204.359 | -270.103 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 1.673 | 440.125 | 0.000 | 0.000 | 0.000 | -376.054 | -0.002 |
TOPFLOOR_PLENUM | 64.559 | -42.791 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.104 | 18.094 | 0.000 | 0.000 | 0.000 | -39.967 | -0.001 |
Total Facility | 275.788 | -355.800 | 782.040 | -16312.703 | 0.000 | 0.000 | 1591.692 | 2743.764 | 15213.411 | 2149.140 | 0.000 | 6.223 | 613.827 | 0.000 | -1962.970 | 0.000 | -1319.313 | -3425.050 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 05-SEP-03:02 | 0.00 | 0.00 | 0.00 | -106985.63 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 92665.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 30-MAY-03:02 | 0.00 | 0.00 | 0.00 | -90261.19 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 81429.70 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 18-SEP-03:02 | 0.00 | 0.00 | 0.00 | -816194.98 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 727880.37 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 07-AUG-03:02 | 0.00 | 0.00 | 0.00 | -79839.30 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 71007.84 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 21-JUL-04:12 | 0.00 | 0.00 | 0.00 | -12126.67 | 0.00 | 0.00 | 0.00 | 194.45 | 1011.70 | 21.23 | 0.00 | 66.42 | 10832.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 04-JUL-08:12 | 0.00 | 0.00 | 0.00 | -20007.96 | 0.00 | 0.00 | 22.40 | 38.49 | 488.98 | 16346.61 | 0.00 | 0.00 | 3308.44 | 0.00 | -0.00 | 0.00 | -196.97 | 0.00 |
PERIMETER_BOT_ZN_1 | 04-SEP-13:43 | 0.00 | 0.00 | 0.00 | -22617.07 | 0.00 | 0.00 | 38.20 | 59.73 | 758.78 | 16324.76 | 0.00 | 0.00 | 5803.02 | 0.00 | -0.00 | 0.00 | -367.43 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-17:51 | 0.00 | 0.00 | 0.00 | -25669.01 | 0.00 | 0.00 | 0.00 | 38.49 | 488.98 | 12165.97 | 0.00 | 0.00 | 13067.87 | 0.00 | -0.00 | 0.00 | -92.30 | 0.00 |
PERIMETER_MID_ZN_3 | 21-JUL-05:03 | 0.00 | 0.00 | 0.00 | -112248.05 | 0.00 | 0.00 | 1103.37 | 1846.14 | 10116.97 | 792.75 | 0.00 | 320.86 | 98067.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 04-JUL-08:12 | 0.00 | 0.00 | 0.00 | -210503.53 | 0.00 | 0.00 | 221.82 | 384.90 | 4889.82 | 162563.69 | 0.00 | 0.00 | 47139.93 | 0.00 | -0.00 | 0.00 | -4696.62 | 0.00 |
PERIMETER_MID_ZN_1 | 10-SEP-13:12 | 0.00 | 0.00 | 0.00 | -231971.52 | 0.00 | 0.00 | 363.02 | 597.27 | 7587.84 | 191315.36 | 0.00 | 0.00 | 40535.95 | 0.00 | -0.00 | 0.00 | -8427.92 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-17:51 | 0.00 | 0.00 | 0.00 | -226255.85 | 0.00 | 0.00 | 0.00 | 384.90 | 4889.79 | 121187.21 | 0.00 | 0.00 | 101972.31 | 0.00 | -0.00 | 0.00 | -2178.35 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-16:41 | 0.00 | 0.00 | 0.00 | -18378.78 | 0.00 | 0.00 | 41.56 | 59.73 | 758.77 | 3097.66 | 0.00 | 30.25 | 14390.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 16-JUL-09:22 | 0.00 | 0.00 | 0.00 | -21428.87 | 0.00 | 0.00 | 21.68 | 38.49 | 488.98 | 12869.08 | 0.00 | 0.00 | 8069.71 | 0.00 | -0.00 | 0.00 | -59.07 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:02 | 0.00 | 0.00 | 0.00 | -24798.85 | 0.00 | 0.00 | 36.98 | 59.73 | 758.78 | 16331.23 | 0.00 | 0.00 | 8605.18 | 0.00 | -0.00 | 0.00 | -993.06 | 0.00 |
PERIMETER_TOP_ZN_4 | 16-JUL-16:41 | 0.00 | 0.00 | 0.00 | -24489.02 | 0.00 | 0.00 | 19.28 | 38.49 | 488.98 | 12994.36 | 0.00 | 0.00 | 11076.51 | 0.00 | -0.00 | 0.00 | -128.60 | 0.00 |
DATACENTER_BOT_ZN_6 | 04-AUG-18:30 | 0.00 | 0.00 | 0.00 | -8059.98 | 0.00 | 0.00 | 10.62 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 119.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -76915.45 | 0.00 | 0.00 | 106.16 | 1350.33 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2485.25 |
DATACENTER_TOP_ZN_6 | 02-AUG-18:40 | 0.00 | 0.00 | 0.00 | -7746.02 | 0.00 | 0.00 | 10.62 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -194.05 |
DATACENTER_BASEMENT_ZN_6 | 04-AUG-21:02 | 0.00 | 0.00 | 0.00 | -369376.42 | 0.00 | 0.00 | 114.08 | 486.22 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10856.40 |
GROUNDFLOOR_PLENUM | 17-JUL-05:13 | 0.00 | -11462.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11498.53 | 0.00 | -0.00 | 0.00 | -35.86 | 0.00 |
MIDFLOOR_PLENUM | 05-JUL-05:15 | 0.00 | -75732.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77288.42 | 0.00 | -0.00 | 0.00 | -1555.58 | 0.00 |
TOPFLOOR_PLENUM | 21-JUL-13:50 | 0.00 | -18658.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.99 | 18436.33 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 11-AUG-05:03 | 0.00 | -12982.88 | 0.00 | -1888380.19 | 0.00 | 0.00 | 16141.97 | 29009.37 | 623236.89 | 0.00 | 0.00 | 0.00 | 1296115.63 | 0.00 | -57866.73 | 0.00 | -5274.06 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 17-JUN-16:02 | 0.00 | 0.00 | 13710.90 | 0.00 | 0.00 | 0.00 | 520.12 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -28550.80 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 02-JAN-04:01 | 0.00 | 0.00 | 539363.82 | 0.00 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -627678.43 |
CORE_TOP | 11-DEC-04:11 | 0.00 | 0.00 | 75905.69 | 0.00 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84737.15 |
PERIMETER_BOT_ZN_3 | 07-FEB-05:01 | 0.00 | 0.00 | 11728.73 | 0.00 | 0.00 | 0.00 | 0.00 | 194.45 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5482.24 | 0.00 | -2094.50 | -5358.14 |
PERIMETER_BOT_ZN_2 | 06-FEB-05:01 | 0.00 | 0.00 | 12475.97 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3593.52 | 0.00 | -1370.82 | -8288.93 |
PERIMETER_BOT_ZN_1 | 06-FEB-04:01 | 0.00 | 0.00 | 17958.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5337.24 | 0.00 | -1865.78 | -11863.93 |
PERIMETER_BOT_ZN_4 | 06-FEB-05:01 | 0.00 | 0.00 | 10966.88 | 0.00 | 0.00 | 0.00 | 0.00 | 125.31 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3832.80 | 0.00 | -1395.13 | -6516.24 |
PERIMETER_MID_ZN_3 | 06-FEB-00:12 | 0.00 | 0.00 | 132332.19 | 0.00 | 0.00 | 0.00 | 0.00 | 972.26 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -46744.35 | 0.00 | -47968.53 | -48708.54 |
PERIMETER_MID_ZN_2 | 05-FEB-23:32 | 0.00 | 0.00 | 173968.96 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -30328.36 | 0.00 | -32299.50 | -116857.48 |
PERIMETER_MID_ZN_1 | 06-FEB-00:12 | 0.00 | 0.00 | 196524.36 | 0.00 | 0.00 | 0.00 | 0.00 | 972.28 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -47366.02 | 0.00 | -48853.97 | -111393.78 |
PERIMETER_MID_ZN_4 | 05-FEB-23:32 | 0.00 | 0.00 | 181806.19 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -31832.02 | 0.00 | -32602.62 | -122887.91 |
PERIMETER_TOP_ZN_3 | 11-DEC-04:11 | 0.00 | 0.00 | 17413.72 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4897.61 | 0.00 | -1625.80 | -11999.23 |
PERIMETER_TOP_ZN_2 | 11-DEC-04:11 | 0.00 | 0.00 | 18258.91 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3356.63 | 0.00 | -1094.46 | -14522.45 |
PERIMETER_TOP_ZN_1 | 12-FEB-22:32 | 0.00 | 0.00 | 21945.86 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 758.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3759.83 | 0.00 | -4529.97 | -14512.07 |
PERIMETER_TOP_ZN_4 | 29-JAN-23:02 | 0.00 | 0.00 | 19876.91 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2611.32 | 0.00 | -2349.03 | -15468.19 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 23-JAN-24:00 | 0.00 | 0.00 | 5497.29 | 0.00 | 0.00 | 0.00 | 54.13 | 225.07 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -25262.54 |
DATACENTER_TOP_ZN_6 | 15-JAN-17:55 | 0.00 | 0.00 | 590.10 | 0.00 | 0.00 | 0.00 | 5.79 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2567.01 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 18-DEC-05:01 | 14689.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1894.31 | -12795.63 |
MIDFLOOR_PLENUM | 02-JAN-06:12 | 177732.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -5312.47 | -172420.12 |
TOPFLOOR_PLENUM | 06-FEB-05:20 | 28664.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -7805.61 | -20858.85 |
Total Facility | 02-JAN-04:01 | -154036.15 | 189520.47 | 1345716.75 | -189520.47 | 0.00 | 0.00 | 0.00 | 14504.71 | 268362.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -106844.70 | 0.00 | -78091.68 | -1289611.63 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.3700 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2406 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 98.3398 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 85.4881 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 10.2393 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 9.2939 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.3522 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.3522 | 0.2242 | 1.0000 | Not calculated | 1.2002 | 0.2242 | ||
AIRLOOP DATACENTER BASEMENT | 21.8229 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.8231 | 0.0155 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4910 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4910 | 0.0318 | 1.0000 | Not calculated | 0.0156 | 0.0318 | ||
AIRLOOP DATACENTER MID | 4.6917 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6917 | 0.0333 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4775 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4775 | 0.0327 | 1.0000 | Not calculated | 0.0156 | 0.0327 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.1850 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9011 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 49.1699 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.2685 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 5.1196 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9508 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.3522 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.3522 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2242 | ||
AIRLOOP DATACENTER BASEMENT | 21.8229 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.8229 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0155 | ||
AIRLOOP DATACENTER BOT | 0.4910 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4910 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0318 | ||
AIRLOOP DATACENTER MID | 4.6917 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.6917 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0333 | ||
AIRLOOP DATACENTER TOP | 0.4775 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4775 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0327 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3522 | 5.3522 | 5.3522 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.6967 | 5.6967 | 1.9084 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 53.3958 | 53.3958 | 18.6351 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2888 | 5.2888 | 1.9093 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.9065 | 0.9065 | 0.2393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0911 | 1.0911 | 0.2182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3091 | 1.3091 | 0.2618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3666 | 1.3666 | 0.2733 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 8.4809 | 8.4809 | 2.3407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.4794 | 11.4794 | 2.2959 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.8629 | 12.8629 | 2.5726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 12.1208 | 12.1208 | 2.4242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0935 | 1.0935 | 0.2701 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1609 | 1.1609 | 0.2322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4015 | 1.4015 | 0.2803 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2946 | 1.2946 | 0.2589 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4910 | 0.4910 | 0.4910 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6917 | 4.6917 | 4.6917 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4775 | 0.4775 | 0.4775 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.8229 | 21.8229 | 21.8229 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.3700 | 9.2406 | 10.3700 | 2.9011 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 98.3398 | 85.4881 | 98.3398 | 28.2685 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 10.2393 | 9.2939 | 10.2393 | 2.9508 | 0.0000 | 1.0000 |
CAV_BAS | 5.3522 | 5.3522 | 5.3522 | 5.3522 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.8229 | 21.8231 | 21.8229 | 21.8229 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4910 | 0.4910 | 0.4910 | 0.4910 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6917 | 4.6917 | 4.6917 | 4.6917 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4775 | 0.4775 | 0.4775 | 0.4775 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.3522 | 5.3522 | 5.3522 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.8484 | 2.8484 | 1.9084 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.6979 | 26.6979 | 18.6351 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.6444 | 2.6444 | 1.9093 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.4532 | 0.4532 | 0.2393 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5455 | 0.5455 | 0.2182 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6546 | 0.6546 | 0.2618 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6833 | 0.6833 | 0.2733 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.2405 | 4.2405 | 2.3407 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.7397 | 5.7397 | 2.2959 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4314 | 6.4314 | 2.5726 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.0604 | 6.0604 | 2.4242 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5467 | 0.5467 | 0.2701 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5804 | 0.5804 | 0.2322 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7007 | 0.7007 | 0.2803 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6473 | 0.6473 | 0.2589 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4910 | 0.4910 | 0.4910 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.6917 | 4.6917 | 4.6917 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4775 | 0.4775 | 0.4775 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.8229 | 21.8229 | 21.8229 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.1850 | 2.9011 | 2.9011 | 2.9011 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 49.1699 | 28.2685 | 28.2685 | 28.2685 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 5.1196 | 2.9508 | 2.9508 | 2.9508 | 0.0000 | 1.0000 |
CAV_BAS | 5.3522 | 5.3522 | 5.3522 | 5.3522 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.8229 | 21.8229 | 21.8229 | 21.8229 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4910 | 0.4910 | 0.4910 | 0.4910 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.6917 | 4.6917 | 4.6917 | 4.6917 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4775 | 0.4775 | 0.4775 | 0.4775 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Buffalo Niagara Intl AP NY USA TMY3 WMO#=725280 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 115.67 |
Number of hours cooling loads not met | 199.83 |
Number of hours not met | 315.50 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1805.49 | 1680702.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3028.25 | 505944.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2743.76 | 261074.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 447.99 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3726.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2256.80 | 244430.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 482.66 | 66139.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 898.76 | 87066.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 17.95 | 6182.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- General | 41.22 | 5613.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 748.59 | 84373.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 27045.18 |
Natural Gas | 0.00 | 2554.08 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 29599.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.23 |
Space Heating | 0.00 |
Space Cooling | 65.38 |
Fans (All) | 48.72 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 583.87 |
Subtotal | 583.87 |
Natural Gas [MJ/m2] | |
Space Heating | 38.98 |
Service Water Heating | 16.16 |
Miscellaneous (All) | 55.14 |
Subtotal | 55.14 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.27 |
Space Heating | 6.10 |
Space Cooling | 10.23 |
Fans (All) | 7.62 |
Service Water Heating | 2.53 |
Receptacle Equipment | 51.40 |
Miscellaneous | 12.85 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8449.50 | 310.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8732.67 | 27.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8755.67 | 4.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8730.33 | 29.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8715.00 | 45.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8427.83 | 332.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8751.33 | 8.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8711.67 | 48.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8704.33 | 55.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8582.33 | 177.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8741.17 | 18.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8698.33 | 61.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8685.67 | 74.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8589.50 | 170.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7677.17 | 1082.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7668.83 | 1091.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7644.00 | 1116.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7647.17 | 1112.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8685.67 | 74.33 | 0.00 | 0.00 | 0.00 |
Min | 7644.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1116.00 | 0.00 | 0.00 | 0.00 |
Average | 8505.81 | 254.19 | 0.00 | 0.00 | 0.00 |
Sum | 195633.67 | 5846.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 367665.17 | 950.83 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330808.00 | 5.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330795.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1687.67 | 580.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1680.33 | 587.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1665.00 | 603.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 81347.67 | 22047.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367665.17 | 22047.33 | 0.00 | 0.00 | 0.00 |
Average | 79256.99 | 1077.92 | 0.00 | 0.00 | 0.00 |
Sum | 1822910.83 | 24792.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 7730.67 | 1029.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8290.67 | 469.33 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8262.50 | 497.50 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8260.50 | 499.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8291.00 | 469.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8441.83 | 318.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8259.00 | 501.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 7972.17 | 787.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8277.83 | 482.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8245.33 | 514.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8216.33 | 543.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8141.50 | 618.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8294.17 | 465.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8249.50 | 510.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8232.50 | 527.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8162.33 | 597.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8272.33 | 487.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8254.83 | 505.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8244.17 | 515.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8327.33 | 432.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8157.83 | 602.17 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8237.50 | 522.50 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 7926.33 | 833.67 | 0.00 | 0.00 | 0.00 |
Min | 7730.67 | 318.17 | 0.00 | 0.00 | 0.00 |
Max | 8441.83 | 1029.33 | 0.00 | 0.00 | 0.00 |
Average | 8206.44 | 553.56 | 0.00 | 0.00 | 0.00 |
Sum | 188748.17 | 12731.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 358680.83 | 9935.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330012.50 | 800.50 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330046.00 | 767.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330006.00 | 807.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38922.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18353.67 | 0.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38923.33 | 1.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24908.83 | 0.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38922.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24908.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38923.00 | 2.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24908.67 | 0.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1951.00 | 317.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1941.50 | 326.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1936.50 | 331.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 93352.33 | 10042.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 358680.83 | 10042.67 | 0.00 | 0.00 | 0.00 |
Average | 79320.26 | 1014.65 | 0.00 | 0.00 | 0.00 |
Sum | 1824366.00 | 23337.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5A
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_BUFFALO
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -3.40 |
February | -4.23 |
March | 2.667 |
April | 7.472 |
May | 13.731 |
June | 18.627 |
July | 22.029 |
August | 20.690 |
September | 16.545 |
October | 9.725 |
November | 6.035 |
December | -2.18 |
Annual Sum or Average | 9.049 |
Minimum of Months | -4.23 |
Maximum of Months | 22.029 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423903E+11 | 102836.97 | 02-JAN-04:01 | -1.0 | -1.9 | 0.540631E+10 | 7499.21 | 11-JAN-10:09 | 7.98 | 6.90 |
February | 0.379674E+11 | 99635.20 | 21-FEB-04:01 | -11.2 | -12.4 | 0.488383E+10 | 7499.19 | 17-FEB-10:20 | -11.2 | -12.4 |
March | 0.486662E+11 | 100476.84 | 20-MAR-03:01 | -2.3 | -3.7 | 0.610245E+10 | 7499.36 | 14-MAR-09:39 | -2.3 | -3.7 |
April | 0.483521E+11 | 102920.41 | 10-APR-03:02 | 3.80 | 3.10 | 0.544521E+10 | 7499.16 | 12-APR-13:20 | 11.70 | 9.99 |
May | 0.509740E+11 | 101165.27 | 01-MAY-03:02 | 4.48 | 3.23 | 0.589798E+10 | 7499.20 | 24-MAY-09:20 | 15.00 | 14.57 |
June | 0.550686E+11 | 93830.78 | 13-JUN-05:03 | 8.90 | 8.27 | 0.588000E+10 | 7499.51 | 22-JUN-13:20 | 20.60 | 15.30 |
July | 0.562089E+11 | 97312.92 | 03-JUL-03:02 | 12.62 | 11.97 | 0.547184E+10 | 7499.03 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.632512E+11 | 94252.02 | 21-AUG-03:02 | 15.50 | 13.60 | 0.613705E+10 | 7548.84 | 14-AUG-09:00 | 15.50 | 13.60 |
September | 0.559621E+11 | 106989.00 | 05-SEP-03:02 | 7.12 | 6.58 | 0.545130E+10 | 7499.51 | 12-SEP-13:20 | 21.10 | 16.62 |
October | 0.557400E+11 | 104809.39 | 16-OCT-03:01 | 0.68 | 0.41 | 0.566766E+10 | 7499.13 | 27-OCT-13:20 | 10.17 | 7.43 |
November | 0.523365E+11 | 103984.87 | 06-NOV-04:03 | 8.90 | 6.74 | 0.561114E+10 | 7499.20 | 16-NOV-14:20 | 17.20 | 13.27 |
December | 0.468740E+11 | 104022.71 | 26-DEC-04:01 | -11.8 | -12.8 | 0.541292E+10 | 7498.96 | 04-DEC-10:20 | -11.8 | -12.8 |
Annual Sum or Average | 0.613791E+12 | 0.673677E+11 | ||||||||
Minimum of Months | 0.379674E+11 | 93830.78 | -11.8 | -12.8 | 0.488383E+10 | 7498.96 | -11.8 | -12.8 | ||
Maximum of Months | 0.632512E+11 | 106989.00 | 15.50 | 13.60 | 0.613705E+10 | 7548.84 | 21.10 | 16.62 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.286910E+11 | 75464.91 | 18-JAN-06:01 | 2.80 | 1.63 | 0.497776E+10 | 6734.83 | 11-JAN-10:09 | 2.80 | 1.63 |
February | 0.270011E+11 | 77046.47 | 23-FEB-06:01 | 2.30 | 1.81 | 0.452575E+10 | 6741.54 | 17-FEB-10:00 | 2.30 | 1.81 |
March | 0.435202E+11 | 82895.15 | 13-MAR-04:01 | 10.73 | 10.39 | 0.548751E+10 | 6745.50 | 02-MAR-10:09 | 10.73 | 10.39 |
April | 0.488228E+11 | 86322.73 | 10-APR-03:02 | 3.80 | 3.10 | 0.488251E+10 | 6734.82 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.485474E+11 | 90267.44 | 30-MAY-03:02 | 12.20 | 11.33 | 0.528695E+10 | 6734.88 | 10-MAY-09:09 | 12.20 | 11.33 |
June | 0.582835E+11 | 85286.63 | 13-JUN-03:02 | 10.50 | 10.11 | 0.526918E+10 | 6735.12 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.650974E+11 | 85755.54 | 06-JUL-03:02 | 13.12 | 10.73 | 0.489379E+10 | 6734.84 | 03-JUL-13:30 | 13.12 | 10.73 |
August | 0.711338E+11 | 85261.91 | 31-AUG-03:02 | 12.12 | 11.53 | 0.549517E+10 | 6735.23 | 02-AUG-13:09 | 12.12 | 11.53 |
September | 0.497660E+11 | 90070.57 | 18-SEP-03:02 | 11.52 | 10.07 | 0.488243E+10 | 6735.15 | 12-SEP-13:09 | 11.52 | 10.07 |
October | 0.458102E+11 | 86156.35 | 23-OCT-03:02 | 15.63 | 12.80 | 0.507846E+10 | 6734.81 | 03-OCT-09:00 | 15.63 | 12.80 |
November | 0.422565E+11 | 86896.23 | 13-NOV-04:01 | 5.50 | 4.05 | 0.502910E+10 | 6734.87 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.361404E+11 | 83010.85 | 18-DEC-05:02 | 1.70 | 0.81 | 0.487883E+10 | 6745.10 | 20-DEC-10:39 | 2.60 | 0.50 |
Annual Sum or Average | 0.565070E+12 | 0.606874E+11 | ||||||||
Minimum of Months | 0.270011E+11 | 75464.91 | 1.70 | 0.81 | 0.452575E+10 | 6734.81 | 2.30 | 0.50 | ||
Maximum of Months | 0.711338E+11 | 90267.44 | 15.63 | 12.80 | 0.549517E+10 | 6745.50 | 20.60 | 15.40 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.208214E+11 | 27516.57 | 20-JAN-07:40 | -1.5 | -3.7 | 0.421467E+10 | 6372.69 | 20-JAN-14:00 | 0.60 | -3.3 |
February | 0.198768E+11 | 28583.89 | 28-FEB-17:05 | -0.7 | -3.0 | 0.385078E+10 | 6420.79 | 17-FEB-14:00 | -0.7 | -3.0 |
March | 0.277498E+11 | 76589.03 | 16-MAR-05:02 | 14.03 | 11.42 | 0.518181E+10 | 6734.88 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.294421E+11 | 73363.29 | 27-APR-05:02 | 5.00 | 3.27 | 0.478435E+10 | 6748.61 | 05-APR-09:00 | 5.00 | 3.27 |
May | 0.387417E+11 | 76165.95 | 19-MAY-05:02 | 8.90 | 7.70 | 0.526565E+10 | 6734.87 | 10-MAY-09:09 | 8.90 | 7.70 |
June | 0.456654E+11 | 77791.43 | 22-JUN-04:03 | 12.20 | 11.84 | 0.526158E+10 | 6735.13 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.472519E+11 | 77872.39 | 18-JUL-03:02 | 17.80 | 17.05 | 0.489218E+10 | 6734.83 | 03-JUL-13:30 | 17.80 | 17.05 |
August | 0.492346E+11 | 79140.17 | 21-AUG-03:02 | 15.50 | 13.60 | 0.549451E+10 | 6735.19 | 02-AUG-13:09 | 15.50 | 13.60 |
September | 0.401710E+11 | 81649.34 | 18-SEP-03:02 | 11.52 | 10.07 | 0.486802E+10 | 6735.16 | 12-SEP-13:09 | 11.52 | 10.07 |
October | 0.308377E+11 | 76058.24 | 06-OCT-05:02 | 10.50 | 9.00 | 0.500790E+10 | 6741.03 | 18-OCT-09:50 | 7.62 | 5.06 |
November | 0.250647E+11 | 68528.93 | 01-NOV-05:02 | 5.68 | 3.03 | 0.484109E+10 | 6775.05 | 07-NOV-10:30 | 2.50 | 1.47 |
December | 0.218150E+11 | 21756.61 | 01-DEC-17:00 | 7.20 | 4.89 | 0.423086E+10 | 6740.02 | 01-DEC-14:30 | 7.20 | 4.89 |
Annual Sum or Average | 0.396672E+12 | 0.578934E+11 | ||||||||
Minimum of Months | 0.198768E+11 | 21756.61 | -1.5 | -3.7 | 0.385078E+10 | 6372.69 | -0.7 | -3.3 | ||
Maximum of Months | 0.492346E+11 | 81649.34 | 17.80 | 17.05 | 0.549451E+10 | 6775.05 | 20.60 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.133287E+11 | 16126.52 | 11-JAN-17:00 | 11.10 | 9.84 | 0.388296E+10 | 5784.80 | 19-JAN-14:00 | 1.10 | -0.2 |
February | 0.135476E+11 | 16502.57 | 28-FEB-17:00 | -0.6 | -3.0 | 0.358544E+10 | 5917.19 | 17-FEB-14:00 | -0.6 | -3.0 |
March | 0.226973E+11 | 74990.77 | 16-MAR-05:02 | 14.03 | 11.42 | 0.471526E+10 | 6734.86 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.243813E+11 | 35639.94 | 21-APR-16:00 | 13.30 | 8.77 | 0.448090E+10 | 6742.50 | 13-APR-13:00 | 13.30 | 8.77 |
May | 0.347464E+11 | 73134.15 | 17-MAY-05:03 | 16.05 | 11.54 | 0.518762E+10 | 6734.87 | 10-MAY-09:09 | 16.05 | 11.54 |
June | 0.462149E+11 | 79209.00 | 19-JUN-03:02 | 17.12 | 16.11 | 0.524909E+10 | 6735.12 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.499936E+11 | 78562.20 | 05-JUL-03:02 | 18.80 | 16.41 | 0.489250E+10 | 6734.77 | 12-JUL-09:00 | 20.60 | 14.64 |
August | 0.497646E+11 | 79853.48 | 07-AUG-03:02 | 20.00 | 18.50 | 0.548887E+10 | 6735.19 | 02-AUG-13:09 | 20.00 | 18.50 |
September | 0.362092E+11 | 79727.25 | 18-SEP-03:02 | 11.52 | 10.07 | 0.481969E+10 | 6735.12 | 12-SEP-13:09 | 11.52 | 10.07 |
October | 0.243322E+11 | 49966.66 | 12-OCT-05:03 | 13.40 | 11.29 | 0.464122E+10 | 6734.65 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.189835E+11 | 21183.41 | 01-NOV-16:00 | 9.40 | 6.91 | 0.425186E+10 | 6711.31 | 01-NOV-13:00 | 9.40 | 6.91 |
December | 0.147100E+11 | 17037.01 | 01-DEC-17:00 | 7.20 | 4.89 | 0.378779E+10 | 6073.47 | 01-DEC-14:00 | 7.20 | 4.89 |
Annual Sum or Average | 0.348909E+12 | 0.549832E+11 | ||||||||
Minimum of Months | 0.133287E+11 | 16126.52 | -0.6 | -3.0 | 0.358544E+10 | 5784.80 | -0.6 | -3.0 | ||
Maximum of Months | 0.499936E+11 | 79853.48 | 20.00 | 18.50 | 0.548887E+10 | 6742.50 | 20.60 | 18.50 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120413E+10 | 2287.80 | 17-JAN-06:02 | 7.20 | 2.95 | 0.487144E+09 | 750.98 | 17-JAN-14:00 | 6.70 | 5.64 |
February | 0.128514E+10 | 2279.74 | 23-FEB-06:01 | 2.30 | 1.81 | 0.450873E+09 | 756.84 | 23-FEB-14:00 | 0.60 | -1.1 |
March | 0.334686E+10 | 6900.83 | 15-MAR-14:00 | 26.10 | 16.06 | 0.620523E+09 | 845.65 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.422512E+10 | 5896.97 | 07-APR-13:30 | 20.00 | 10.05 | 0.595245E+09 | 845.63 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.547267E+10 | 8807.06 | 30-MAY-05:03 | 12.20 | 11.93 | 0.658298E+09 | 845.64 | 10-MAY-09:09 | 12.20 | 11.93 |
June | 0.857348E+10 | 11735.53 | 21-JUN-05:02 | 18.30 | 16.18 | 0.661410E+09 | 845.80 | 26-JUN-13:39 | 26.83 | 20.63 |
July | 0.103549E+11 | 12129.80 | 21-JUL-04:12 | 26.33 | 23.62 | 0.615243E+09 | 846.07 | 20-JUL-13:20 | 26.33 | 23.62 |
August | 0.103601E+11 | 11274.63 | 21-AUG-05:02 | 14.40 | 13.12 | 0.690057E+09 | 846.09 | 14-AUG-13:20 | 14.40 | 13.12 |
September | 0.578575E+10 | 9055.30 | 14-SEP-05:03 | 20.60 | 19.14 | 0.608713E+09 | 845.68 | 12-SEP-13:09 | 20.60 | 19.14 |
October | 0.392844E+10 | 5262.64 | 12-OCT-14:00 | 18.30 | 14.87 | 0.616226E+09 | 845.63 | 10-OCT-09:20 | 18.30 | 14.87 |
November | 0.300681E+10 | 4186.73 | 27-NOV-12:00 | 15.00 | 10.52 | 0.587079E+09 | 845.64 | 16-NOV-14:09 | 15.00 | 10.52 |
December | 0.198821E+10 | 2619.11 | 14-DEC-06:03 | 5.68 | 5.18 | 0.500608E+09 | 819.65 | 01-DEC-14:09 | 5.68 | 5.18 |
Annual Sum or Average | 0.595316E+11 | 0.709142E+10 | ||||||||
Minimum of Months | 0.120413E+10 | 2279.74 | 2.30 | 1.81 | 0.450873E+09 | 750.98 | 0.60 | -1.1 | ||
Maximum of Months | 0.103601E+11 | 12129.80 | 26.33 | 23.62 | 0.690057E+09 | 846.09 | 26.83 | 23.62 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105739E+10 | 2018.03 | 17-JAN-06:02 | 7.20 | 2.95 | 0.311786E+09 | 472.81 | 12-JAN-10:30 | 7.20 | 2.95 |
February | 0.109853E+10 | 3419.20 | 28-FEB-09:35 | -5.2 | -6.5 | 0.292131E+09 | 544.95 | 28-FEB-10:39 | -2.8 | -4.6 |
March | 0.297972E+10 | 6492.91 | 21-MAR-09:10 | 1.88 | -0.4 | 0.405247E+09 | 545.85 | 28-MAR-09:30 | 2.75 | -0.3 |
April | 0.419160E+10 | 10397.21 | 23-APR-09:13 | 12.20 | 4.98 | 0.380235E+09 | 544.96 | 21-APR-13:00 | 12.20 | 4.98 |
May | 0.557394E+10 | 10849.48 | 31-MAY-08:30 | 17.50 | 13.13 | 0.422881E+09 | 544.97 | 10-MAY-09:09 | 17.50 | 13.13 |
June | 0.760320E+10 | 18971.05 | 11-JUN-09:12 | 23.67 | 16.37 | 0.425934E+09 | 545.65 | 12-JUN-09:50 | 27.62 | 19.41 |
July | 0.879905E+10 | 20018.34 | 04-JUL-08:12 | 21.10 | 17.58 | 0.396382E+09 | 545.59 | 03-JUL-09:39 | 21.10 | 17.58 |
August | 0.848753E+10 | 18210.95 | 06-AUG-08:32 | 23.17 | 16.90 | 0.443727E+09 | 545.83 | 04-AUG-09:20 | 23.17 | 16.90 |
September | 0.550387E+10 | 18308.40 | 04-SEP-09:43 | 17.62 | 13.21 | 0.390779E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.349575E+10 | 8394.49 | 11-OCT-08:50 | 14.53 | 11.11 | 0.394560E+09 | 544.96 | 03-OCT-09:00 | 14.53 | 11.11 |
November | 0.246573E+10 | 4584.22 | 06-NOV-08:50 | 7.38 | 3.86 | 0.359635E+09 | 544.95 | 15-NOV-10:20 | 5.17 | 3.02 |
December | 0.133197E+10 | 2197.73 | 05-DEC-06:03 | -2.9 | -4.3 | 0.306020E+09 | 532.25 | 04-DEC-10:09 | -2.9 | -4.3 |
Annual Sum or Average | 0.525883E+11 | 0.452932E+10 | ||||||||
Minimum of Months | 0.105739E+10 | 2018.03 | -5.2 | -6.5 | 0.292131E+09 | 472.81 | -2.9 | -4.6 | ||
Maximum of Months | 0.879905E+10 | 20018.34 | 23.67 | 17.58 | 0.443727E+09 | 545.85 | 27.62 | 19.41 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186862E+10 | 8783.56 | 12-JAN-13:30 | -6.7 | -9.2 | 0.517134E+09 | 845.64 | 12-JAN-14:20 | -5.9 | -8.5 |
February | 0.211929E+10 | 11486.83 | 28-FEB-13:30 | 0.00 | -2.9 | 0.482512E+09 | 846.89 | 17-FEB-10:00 | 0.00 | -2.9 |
March | 0.540246E+10 | 15453.38 | 15-MAR-13:30 | 25.55 | 15.84 | 0.645898E+09 | 848.14 | 01-MAR-14:39 | 25.55 | 15.84 |
April | 0.609784E+10 | 13207.42 | 24-APR-12:40 | 10.93 | 5.90 | 0.590424E+09 | 846.05 | 24-APR-13:20 | 11.67 | 6.21 |
May | 0.713727E+10 | 16538.94 | 14-MAY-14:02 | 25.18 | 18.10 | 0.654959E+09 | 845.67 | 10-MAY-13:09 | 25.18 | 18.10 |
June | 0.989280E+10 | 16632.39 | 25-JUN-13:53 | 26.10 | 17.70 | 0.660629E+09 | 845.71 | 22-JUN-13:09 | 26.10 | 17.70 |
July | 0.122341E+11 | 22585.92 | 30-JUL-12:13 | 25.60 | 19.74 | 0.615647E+09 | 846.58 | 17-JUL-13:39 | 25.60 | 19.74 |
August | 0.133903E+11 | 22139.13 | 27-AUG-13:02 | 23.40 | 18.88 | 0.690537E+09 | 846.46 | 03-AUG-13:00 | 23.40 | 18.88 |
September | 0.944462E+10 | 22618.50 | 04-SEP-13:43 | 18.07 | 13.01 | 0.609445E+09 | 846.85 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.663235E+10 | 17654.14 | 11-OCT-12:30 | 21.95 | 13.79 | 0.618816E+09 | 850.73 | 31-OCT-13:20 | 15.00 | 10.26 |
November | 0.413420E+10 | 13368.76 | 03-NOV-12:20 | 8.17 | 4.43 | 0.578151E+09 | 845.69 | 03-NOV-13:09 | 8.98 | 4.94 |
December | 0.223724E+10 | 10046.85 | 04-DEC-11:40 | -0.4 | -3.0 | 0.506400E+09 | 845.63 | 11-DEC-14:00 | -8.3 | -9.4 |
Annual Sum or Average | 0.805912E+11 | 0.717055E+10 | ||||||||
Minimum of Months | 0.186862E+10 | 8783.56 | -6.7 | -9.2 | 0.482512E+09 | 845.63 | -8.3 | -9.4 | ||
Maximum of Months | 0.133903E+11 | 22618.50 | 26.10 | 19.74 | 0.690537E+09 | 850.73 | 26.10 | 19.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.204181E+10 | 2870.05 | 17-JAN-06:02 | 7.20 | 2.95 | 0.324237E+09 | 513.68 | 12-JAN-16:10 | 7.20 | 2.95 |
February | 0.248043E+10 | 6853.82 | 28-FEB-16:30 | 0.00 | -2.6 | 0.312964E+09 | 544.94 | 22-FEB-14:00 | 0.00 | -2.6 |
March | 0.543580E+10 | 10497.57 | 13-MAR-04:01 | 10.73 | 10.39 | 0.430200E+09 | 546.09 | 01-MAR-14:39 | 10.73 | 10.39 |
April | 0.759479E+10 | 18901.22 | 30-APR-15:32 | 15.00 | 12.10 | 0.394821E+09 | 544.97 | 21-APR-13:00 | 15.00 | 12.10 |
May | 0.718621E+10 | 23153.92 | 07-MAY-17:52 | 13.90 | 5.26 | 0.426043E+09 | 544.96 | 10-MAY-09:09 | 18.68 | 14.82 |
June | 0.111567E+11 | 25673.00 | 11-JUN-17:51 | 25.00 | 17.50 | 0.427513E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.133254E+11 | 24577.36 | 02-JUL-16:52 | 25.00 | 17.00 | 0.397879E+09 | 545.00 | 03-JUL-13:30 | 25.00 | 16.74 |
August | 0.145602E+11 | 24500.26 | 06-AUG-16:31 | 27.80 | 18.98 | 0.446236E+09 | 545.01 | 02-AUG-13:09 | 27.80 | 18.98 |
September | 0.707631E+10 | 18856.88 | 04-SEP-16:22 | 18.30 | 13.01 | 0.393956E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.538050E+10 | 11295.94 | 11-OCT-16:00 | 21.70 | 14.52 | 0.404974E+09 | 544.96 | 03-OCT-09:00 | 21.70 | 14.52 |
November | 0.429152E+10 | 10349.59 | 16-NOV-06:02 | 11.78 | 7.27 | 0.398559E+09 | 544.97 | 16-NOV-14:09 | 17.20 | 13.27 |
December | 0.339442E+10 | 6599.37 | 14-DEC-06:02 | 5.68 | 5.18 | 0.364923E+09 | 545.24 | 15-DEC-14:39 | 2.80 | 1.36 |
Annual Sum or Average | 0.839241E+11 | 0.472231E+10 | ||||||||
Minimum of Months | 0.204181E+10 | 2870.05 | 0.00 | -2.6 | 0.312964E+09 | 513.68 | 0.00 | -2.6 | ||
Maximum of Months | 0.145602E+11 | 25673.00 | 27.80 | 18.98 | 0.446236E+09 | 546.09 | 27.80 | 18.98 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44680821.69 | 1428.25 | 14-JAN-17:03 | 3.22 | 2.72 | 0.463654E+09 | 625.95 | 24-JAN-14:30 | -7.0 | -9.5 |
February | 49360534.32 | 1427.57 | 18-FEB-17:03 | 0.82 | -0.6 | 0.420377E+09 | 625.92 | 06-FEB-10:00 | 0.82 | -0.6 |
March | 0.135111E+10 | 5004.17 | 15-MAR-14:40 | 25.77 | 16.18 | 0.544219E+09 | 845.64 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.222665E+10 | 3136.18 | 21-APR-15:10 | 14.72 | 8.39 | 0.518662E+09 | 845.62 | 21-APR-13:00 | 14.72 | 8.39 |
May | 0.399537E+10 | 6003.64 | 23-MAY-14:40 | 23.90 | 13.32 | 0.638468E+09 | 845.63 | 17-MAY-09:00 | 23.90 | 13.32 |
June | 0.666869E+10 | 10532.35 | 19-JUN-05:03 | 16.70 | 15.97 | 0.658228E+09 | 845.67 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.787691E+10 | 11224.64 | 21-JUL-05:03 | 25.60 | 23.14 | 0.614830E+09 | 845.70 | 20-JUL-13:39 | 25.60 | 23.14 |
August | 0.727071E+10 | 10608.67 | 11-AUG-05:03 | 17.80 | 15.36 | 0.687979E+09 | 845.69 | 02-AUG-13:09 | 17.80 | 15.36 |
September | 0.439546E+10 | 8000.26 | 15-SEP-05:02 | 18.30 | 16.87 | 0.595631E+09 | 845.68 | 12-SEP-13:09 | 18.30 | 16.87 |
October | 0.242483E+10 | 3515.67 | 12-OCT-15:30 | 18.30 | 15.05 | 0.547965E+09 | 845.62 | 12-OCT-13:00 | 18.30 | 15.05 |
November | 0.120234E+10 | 2321.77 | 07-NOV-11:20 | 2.77 | 2.05 | 0.483157E+09 | 766.44 | 16-NOV-14:00 | 17.20 | 13.27 |
December | 0.143172E+09 | 1706.73 | 01-DEC-13:30 | 11.10 | 9.57 | 0.447984E+09 | 663.38 | 01-DEC-14:09 | 8.12 | 6.69 |
Annual Sum or Average | 0.376493E+11 | 0.662116E+10 | ||||||||
Minimum of Months | 44680821.69 | 1427.57 | 0.82 | -0.6 | 0.420377E+09 | 625.92 | -7.0 | -9.5 | ||
Maximum of Months | 0.787691E+10 | 11224.64 | 25.77 | 23.14 | 0.687979E+09 | 845.70 | 25.60 | 23.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 44108580.45 | 1538.59 | 17-JAN-06:05 | 7.20 | 2.95 | 0.219172E+09 | 385.78 | 31-JAN-08:00 | -11.7 | -12.6 |
February | 0.187034E+09 | 2446.19 | 28-FEB-10:05 | -3.6 | -5.3 | 0.199699E+09 | 464.80 | 28-FEB-09:00 | -3.6 | -5.3 |
March | 0.167008E+10 | 4554.35 | 14-MAR-10:30 | 20.80 | 17.14 | 0.263000E+09 | 521.22 | 16-MAR-14:20 | 19.07 | 15.39 |
April | 0.293147E+10 | 8890.25 | 24-APR-09:00 | 6.10 | 2.71 | 0.257832E+09 | 521.21 | 21-APR-14:09 | 6.10 | 2.71 |
May | 0.488196E+10 | 10963.86 | 31-MAY-08:50 | 17.70 | 13.18 | 0.303130E+09 | 521.22 | 26-MAY-10:09 | 17.70 | 13.18 |
June | 0.701129E+10 | 19940.54 | 11-JUN-09:52 | 24.40 | 16.86 | 0.311595E+09 | 521.30 | 23-JUN-08:00 | 15.60 | 11.53 |
July | 0.796805E+10 | 21061.36 | 04-JUL-08:12 | 21.10 | 17.58 | 0.292415E+09 | 521.43 | 17-JUL-08:09 | 24.08 | 20.74 |
August | 0.736001E+10 | 13003.10 | 20-AUG-09:32 | 20.20 | 14.23 | 0.325216E+09 | 521.80 | 02-AUG-08:50 | 20.20 | 14.23 |
September | 0.490202E+10 | 16733.94 | 04-SEP-09:32 | 17.43 | 13.19 | 0.281601E+09 | 521.24 | 12-SEP-12:20 | 20.77 | 15.37 |
October | 0.250351E+10 | 6638.40 | 11-OCT-09:00 | 15.00 | 11.35 | 0.264757E+09 | 524.17 | 17-OCT-10:50 | 5.92 | 2.31 |
November | 0.107026E+10 | 2279.12 | 03-NOV-10:20 | 5.97 | 3.19 | 0.228274E+09 | 504.10 | 03-NOV-10:30 | 6.15 | 3.28 |
December | 0.103476E+09 | 1660.02 | 04-DEC-10:00 | -1.7 | -3.7 | 0.211610E+09 | 394.76 | 01-DEC-13:39 | -1.7 | -3.7 |
Annual Sum or Average | 0.406333E+11 | 0.315830E+10 | ||||||||
Minimum of Months | 44108580.45 | 1538.59 | -3.6 | -5.3 | 0.199699E+09 | 385.78 | -11.7 | -12.6 | ||
Maximum of Months | 0.796805E+10 | 21061.36 | 24.40 | 17.58 | 0.325216E+09 | 524.17 | 24.08 | 20.74 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.854260E+09 | 9699.93 | 12-JAN-14:05 | -6.0 | -8.6 | 0.489846E+09 | 859.97 | 12-JAN-14:09 | -6.0 | -8.6 |
February | 0.110263E+10 | 12585.99 | 28-FEB-13:05 | 0.00 | -2.8 | 0.451552E+09 | 845.64 | 08-FEB-14:00 | 0.00 | -2.8 |
March | 0.385863E+10 | 14619.87 | 15-MAR-13:30 | 25.55 | 15.84 | 0.606963E+09 | 846.26 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.431414E+10 | 12413.76 | 24-APR-13:10 | 11.38 | 6.04 | 0.556144E+09 | 845.67 | 21-APR-13:50 | 11.38 | 6.04 |
May | 0.612355E+10 | 16629.70 | 14-MAY-13:53 | 25.00 | 18.14 | 0.642713E+09 | 845.66 | 05-MAY-13:09 | 25.00 | 18.14 |
June | 0.833638E+10 | 15153.01 | 25-JUN-13:53 | 26.10 | 17.70 | 0.657194E+09 | 845.70 | 22-JUN-13:09 | 26.10 | 17.70 |
July | 0.999834E+10 | 21963.32 | 30-JUL-12:02 | 25.60 | 19.84 | 0.615120E+09 | 846.27 | 31-JUL-13:00 | 25.00 | 19.43 |
August | 0.107078E+11 | 22151.20 | 13-AUG-13:13 | 30.00 | 22.88 | 0.689208E+09 | 846.24 | 03-AUG-13:00 | 30.00 | 22.88 |
September | 0.874503E+10 | 23195.65 | 10-SEP-13:12 | 17.20 | 10.59 | 0.603746E+09 | 852.67 | 21-SEP-13:30 | 25.30 | 16.56 |
October | 0.554472E+10 | 17696.30 | 31-OCT-13:30 | 15.00 | 10.33 | 0.597198E+09 | 872.23 | 31-OCT-13:39 | 15.00 | 10.41 |
November | 0.271205E+10 | 13249.33 | 03-NOV-12:40 | 8.53 | 4.68 | 0.528788E+09 | 846.86 | 06-NOV-10:09 | 7.98 | 4.09 |
December | 0.721941E+09 | 6470.11 | 16-DEC-13:30 | 5.60 | 3.03 | 0.462041E+09 | 845.64 | 11-DEC-14:50 | 5.60 | 3.03 |
Annual Sum or Average | 0.630195E+11 | 0.690051E+10 | ||||||||
Minimum of Months | 0.721941E+09 | 6470.11 | -6.0 | -8.6 | 0.451552E+09 | 845.64 | -6.0 | -8.6 | ||
Maximum of Months | 0.107078E+11 | 23195.65 | 30.00 | 22.88 | 0.689208E+09 | 872.23 | 30.00 | 22.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175465E+09 | 1814.33 | 12-JAN-16:10 | -6.2 | -8.3 | 0.299972E+09 | 425.90 | 06-JAN-14:00 | -6.2 | -8.3 |
February | 0.317858E+09 | 4011.33 | 28-FEB-17:05 | -0.7 | -3.0 | 0.274368E+09 | 517.52 | 28-FEB-16:49 | -0.7 | -3.0 |
March | 0.199686E+10 | 5605.51 | 15-MAR-14:20 | 25.93 | 16.12 | 0.361131E+09 | 544.97 | 16-MAR-13:00 | 18.90 | 15.16 |
April | 0.314158E+10 | 9390.22 | 24-APR-16:00 | 13.30 | 7.63 | 0.342311E+09 | 544.96 | 21-APR-13:00 | 13.30 | 7.63 |
May | 0.509917E+10 | 21055.26 | 07-MAY-16:42 | 15.00 | 5.89 | 0.407962E+09 | 544.96 | 17-MAY-09:00 | 18.90 | 14.77 |
June | 0.773686E+10 | 22633.76 | 11-JUN-17:51 | 25.00 | 17.50 | 0.423124E+09 | 544.99 | 22-JUN-13:09 | 20.60 | 15.40 |
July | 0.836057E+10 | 22045.50 | 30-JUL-17:21 | 24.40 | 20.03 | 0.396563E+09 | 544.98 | 03-JUL-13:30 | 24.40 | 20.03 |
August | 0.803384E+10 | 20326.15 | 06-AUG-16:42 | 27.80 | 19.02 | 0.443532E+09 | 545.00 | 02-AUG-13:09 | 27.80 | 19.02 |
September | 0.499670E+10 | 20757.54 | 04-SEP-17:32 | 17.23 | 12.32 | 0.382017E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.283636E+10 | 8899.50 | 11-OCT-16:00 | 21.70 | 14.52 | 0.354675E+09 | 544.95 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.146399E+10 | 3018.22 | 15-NOV-15:40 | 11.70 | 6.73 | 0.315954E+09 | 544.87 | 15-NOV-14:00 | 11.70 | 6.73 |
December | 0.278033E+09 | 1968.96 | 04-DEC-15:50 | -0.5 | -3.2 | 0.289882E+09 | 447.82 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.444373E+11 | 0.429149E+10 | ||||||||
Minimum of Months | 0.175465E+09 | 1814.33 | -6.2 | -8.3 | 0.274368E+09 | 425.90 | -6.2 | -8.3 | ||
Maximum of Months | 0.836057E+10 | 22633.76 | 27.80 | 20.03 | 0.443532E+09 | 545.00 | 27.80 | 20.03 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 15168953.59 | 1611.32 | 14-JAN-17:03 | 3.22 | 2.72 | 0.462382E+09 | 625.93 | 23-JAN-10:09 | -7.0 | -8.8 |
February | 15064452.09 | 1612.47 | 18-FEB-17:03 | 0.82 | -0.6 | 0.418469E+09 | 625.93 | 06-FEB-14:50 | 0.82 | -0.6 |
March | 0.952686E+09 | 5453.01 | 15-MAR-14:50 | 25.68 | 16.21 | 0.527987E+09 | 845.64 | 15-MAR-13:20 | 25.68 | 16.21 |
April | 0.167716E+10 | 3158.16 | 20-APR-16:00 | 15.00 | 11.00 | 0.483916E+09 | 830.70 | 20-APR-13:00 | 15.00 | 11.00 |
May | 0.373181E+10 | 6083.53 | 23-MAY-14:40 | 23.90 | 13.32 | 0.607429E+09 | 845.63 | 10-MAY-13:39 | 23.90 | 13.32 |
June | 0.679029E+10 | 11900.15 | 27-JUN-05:03 | 21.20 | 19.66 | 0.650951E+09 | 845.67 | 22-JUN-13:09 | 21.20 | 19.66 |
July | 0.832056E+10 | 18382.02 | 16-JUL-16:41 | 27.77 | 20.68 | 0.613704E+09 | 845.63 | 12-JUL-09:00 | 27.77 | 20.68 |
August | 0.742362E+10 | 11383.31 | 13-AUG-16:12 | 28.67 | 23.12 | 0.683122E+09 | 845.69 | 02-AUG-13:09 | 28.67 | 23.12 |
September | 0.412923E+10 | 6674.20 | 15-SEP-14:00 | 25.60 | 21.03 | 0.573337E+09 | 845.67 | 12-SEP-13:09 | 25.60 | 21.03 |
October | 0.172810E+10 | 3143.94 | 12-OCT-15:30 | 18.30 | 15.05 | 0.506507E+09 | 843.34 | 12-OCT-13:00 | 18.30 | 15.05 |
November | 0.427085E+09 | 2168.98 | 16-NOV-17:00 | 18.30 | 13.48 | 0.463777E+09 | 703.04 | 16-NOV-14:00 | 18.30 | 13.48 |
December | 36710212.57 | 1618.55 | 02-DEC-17:02 | 2.62 | 1.32 | 0.445603E+09 | 625.91 | 26-DEC-14:00 | -9.4 | -10.8 |
Annual Sum or Average | 0.352475E+11 | 0.643718E+10 | ||||||||
Minimum of Months | 15064452.09 | 1611.32 | 0.82 | -0.6 | 0.418469E+09 | 625.91 | -9.4 | -10.8 | ||
Maximum of Months | 0.832056E+10 | 18382.02 | 28.67 | 23.12 | 0.683122E+09 | 845.69 | 28.67 | 23.12 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16119543.49 | 1375.84 | 14-JAN-17:03 | 3.22 | 2.72 | 0.298649E+09 | 403.37 | 03-JAN-10:09 | 3.22 | 2.72 |
February | 89319767.81 | 1734.29 | 28-FEB-10:15 | -3.3 | -5.1 | 0.271407E+09 | 443.03 | 28-FEB-10:20 | -3.3 | -5.1 |
March | 0.121057E+10 | 4450.41 | 15-MAR-14:00 | 26.10 | 16.06 | 0.348715E+09 | 544.98 | 15-MAR-13:20 | 26.10 | 16.06 |
April | 0.225739E+10 | 7029.84 | 24-APR-09:30 | 6.65 | 3.34 | 0.339596E+09 | 544.96 | 21-APR-13:00 | 6.65 | 3.34 |
May | 0.445189E+10 | 10297.30 | 31-MAY-09:10 | 17.88 | 13.30 | 0.406709E+09 | 544.97 | 10-MAY-13:39 | 17.88 | 13.30 |
June | 0.709556E+10 | 12173.54 | 11-JUN-09:23 | 23.85 | 16.50 | 0.423503E+09 | 545.61 | 12-JUN-09:00 | 27.80 | 19.41 |
July | 0.837053E+10 | 21432.02 | 16-JUL-09:22 | 27.50 | 22.25 | 0.396554E+09 | 545.58 | 14-JUL-09:50 | 27.50 | 22.25 |
August | 0.754152E+10 | 13402.31 | 06-AUG-13:23 | 26.95 | 18.29 | 0.442066E+09 | 545.57 | 10-AUG-09:00 | 27.80 | 20.31 |
September | 0.457225E+10 | 9691.96 | 04-SEP-09:43 | 17.62 | 13.21 | 0.378586E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.186754E+10 | 5243.78 | 11-OCT-09:40 | 16.13 | 11.96 | 0.342134E+09 | 544.95 | 11-OCT-13:09 | 22.20 | 14.14 |
November | 0.487090E+09 | 1894.32 | 03-NOV-10:00 | 5.60 | 2.99 | 0.301767E+09 | 468.78 | 03-NOV-09:00 | 5.60 | 2.99 |
December | 28935135.48 | 1567.44 | 21-DEC-06:04 | 1.02 | 0.58 | 0.288020E+09 | 403.37 | 28-DEC-10:09 | -11.5 | -12.1 |
Annual Sum or Average | 0.379887E+11 | 0.423771E+10 | ||||||||
Minimum of Months | 16119543.49 | 1375.84 | -3.3 | -5.1 | 0.271407E+09 | 403.37 | -11.5 | -12.1 | ||
Maximum of Months | 0.837053E+10 | 21432.02 | 27.50 | 22.25 | 0.442066E+09 | 545.61 | 27.80 | 22.25 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.503642E+09 | 4618.12 | 12-JAN-14:00 | -6.1 | -8.8 | 0.478783E+09 | 845.65 | 12-JAN-14:20 | -5.9 | -8.5 |
February | 0.741231E+09 | 9974.38 | 28-FEB-14:10 | 0.00 | -3.0 | 0.441014E+09 | 845.64 | 08-FEB-14:50 | 0.00 | -3.0 |
March | 0.297634E+10 | 15088.00 | 15-MAR-13:30 | 25.55 | 15.84 | 0.581475E+09 | 846.46 | 15-MAR-13:00 | 26.10 | 16.06 |
April | 0.343323E+10 | 11499.32 | 24-APR-13:30 | 11.95 | 6.38 | 0.526889E+09 | 847.01 | 13-APR-13:00 | 11.95 | 6.38 |
May | 0.555939E+10 | 11087.06 | 26-MAY-13:30 | 20.85 | 13.56 | 0.621072E+09 | 845.68 | 10-MAY-13:39 | 20.85 | 13.56 |
June | 0.841902E+10 | 16842.36 | 25-JUN-13:43 | 26.10 | 17.61 | 0.650939E+09 | 845.71 | 22-JUN-13:09 | 26.10 | 17.61 |
July | 0.104792E+11 | 23975.54 | 16-JUL-11:22 | 28.05 | 21.22 | 0.613646E+09 | 846.54 | 21-JUL-13:50 | 31.52 | 21.79 |
August | 0.108806E+11 | 23993.24 | 13-AUG-14:51 | 30.00 | 23.24 | 0.685639E+09 | 846.41 | 03-AUG-13:00 | 30.00 | 23.24 |
September | 0.817653E+10 | 24798.63 | 10-SEP-14:02 | 17.20 | 10.67 | 0.591553E+09 | 846.74 | 22-SEP-13:00 | 23.90 | 15.30 |
October | 0.435199E+10 | 17764.00 | 11-OCT-12:30 | 21.95 | 13.79 | 0.564414E+09 | 846.14 | 11-OCT-13:39 | 22.20 | 14.14 |
November | 0.160825E+10 | 10645.67 | 03-NOV-13:10 | 8.98 | 4.94 | 0.500740E+09 | 845.64 | 01-NOV-13:39 | 8.98 | 4.94 |
December | 0.367437E+09 | 4397.13 | 16-DEC-13:30 | 5.60 | 3.03 | 0.453937E+09 | 845.63 | 04-DEC-14:00 | 5.60 | 3.03 |
Annual Sum or Average | 0.574969E+11 | 0.671010E+10 | ||||||||
Minimum of Months | 0.367437E+09 | 4397.13 | -6.1 | -8.8 | 0.441014E+09 | 845.63 | -5.9 | -8.5 | ||
Maximum of Months | 0.108806E+11 | 24798.63 | 30.00 | 23.24 | 0.685639E+09 | 847.01 | 31.52 | 23.24 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 64037929.37 | 1774.34 | 18-JAN-06:04 | 2.80 | 1.63 | 0.298864E+09 | 403.37 | 25-JAN-10:09 | -7.7 | -8.3 |
February | 0.183491E+09 | 2548.81 | 28-FEB-16:40 | -0.2 | -2.7 | 0.273058E+09 | 515.40 | 28-FEB-16:49 | -0.4 | -2.9 |
March | 0.156303E+10 | 5925.31 | 15-MAR-14:20 | 25.93 | 16.12 | 0.349685E+09 | 544.97 | 15-MAR-13:20 | 25.93 | 16.12 |
April | 0.258193E+10 | 8969.03 | 20-APR-15:40 | 14.80 | 10.94 | 0.324465E+09 | 544.96 | 21-APR-13:00 | 14.40 | 8.43 |
May | 0.480311E+10 | 18587.48 | 07-MAY-16:12 | 15.00 | 5.96 | 0.391513E+09 | 544.97 | 10-MAY-13:39 | 25.73 | 17.72 |
June | 0.779199E+10 | 24011.14 | 25-JUN-17:01 | 27.12 | 18.23 | 0.418689E+09 | 544.99 | 22-JUN-13:09 | 27.12 | 18.23 |
July | 0.867423E+10 | 24499.30 | 16-JUL-16:41 | 27.77 | 20.68 | 0.395446E+09 | 544.96 | 12-JUL-09:00 | 27.77 | 20.68 |
August | 0.814360E+10 | 23315.80 | 27-AUG-16:32 | 22.57 | 18.97 | 0.440569E+09 | 545.00 | 02-AUG-13:09 | 22.57 | 18.97 |
September | 0.472731E+10 | 12564.06 | 10-SEP-16:02 | 17.52 | 11.16 | 0.370135E+09 | 544.99 | 12-SEP-13:09 | 21.10 | 16.55 |
October | 0.220589E+10 | 8738.35 | 11-OCT-16:00 | 21.70 | 14.52 | 0.335315E+09 | 544.95 | 12-OCT-13:00 | 18.30 | 14.87 |
November | 0.781201E+09 | 2482.78 | 15-NOV-15:50 | 11.70 | 6.77 | 0.304663E+09 | 514.60 | 15-NOV-14:00 | 11.70 | 6.77 |
December | 0.109049E+09 | 1856.82 | 04-DEC-15:50 | -0.5 | -3.2 | 0.288391E+09 | 412.90 | 04-DEC-15:00 | -0.6 | -3.3 |
Annual Sum or Average | 0.416289E+11 | 0.419079E+10 | ||||||||
Minimum of Months | 64037929.37 | 1774.34 | -0.5 | -3.2 | 0.273058E+09 | 403.37 | -7.7 | -8.3 | ||
Maximum of Months | 0.867423E+10 | 24499.30 | 27.77 | 20.68 | 0.440569E+09 | 545.00 | 27.77 | 20.68 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 82954180.17 | 3936.27 | 21-JAN-06:01 | -2.9 | -4.2 | 0.00 | 0.00 | 01-JAN-00:10 | -2.9 | -4.2 |
February | 56827123.90 | 3628.82 | 25-FEB-06:01 | -8.4 | -9.2 | 0.00 | 0.00 | 01-FEB-00:10 | -8.4 | -9.2 |
March | 0.127372E+10 | 4431.38 | 15-MAR-14:10 | 26.02 | 16.09 | 0.00 | 0.00 | 01-MAR-00:10 | 26.02 | 16.09 |
April | 0.277001E+10 | 6088.50 | 10-APR-05:15 | 4.07 | 3.41 | 0.00 | 0.00 | 01-APR-00:10 | 4.07 | 3.41 |
May | 0.422808E+10 | 7771.96 | 30-MAY-05:15 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.703935E+10 | 8125.25 | 05-JUN-05:13 | 14.40 | 13.62 | 0.00 | 0.00 | 01-JUN-00:10 | 14.40 | 13.62 |
July | 0.859995E+10 | 11463.22 | 17-JUL-05:13 | 22.80 | 21.19 | 0.00 | 0.00 | 01-JUL-00:10 | 22.80 | 21.19 |
August | 0.888749E+10 | 11167.05 | 14-AUG-05:15 | 22.80 | 21.58 | 0.00 | 0.00 | 01-AUG-00:10 | 22.80 | 21.58 |
September | 0.537709E+10 | 7204.41 | 05-SEP-05:15 | 6.50 | 5.78 | 0.00 | 0.00 | 01-SEP-00:10 | 6.50 | 5.78 |
October | 0.289447E+10 | 6028.84 | 23-OCT-05:15 | 11.70 | 10.06 | 0.00 | 0.00 | 01-OCT-00:10 | 11.70 | 10.06 |
November | 0.153317E+10 | 4124.87 | 06-NOV-06:15 | 8.90 | 6.78 | 0.00 | 0.00 | 01-NOV-00:10 | 8.90 | 6.78 |
December | 0.162535E+09 | 2398.99 | 16-DEC-06:08 | -0.7 | -1.3 | 0.00 | 0.00 | 01-DEC-00:10 | -0.7 | -1.3 |
Annual Sum or Average | 0.429057E+11 | 0.00 | ||||||||
Minimum of Months | 56827123.90 | 2398.99 | -8.4 | -9.2 | 0.00 | 0.00 | -8.4 | -9.2 | ||
Maximum of Months | 0.888749E+10 | 11463.22 | 26.02 | 21.58 | 0.00 | 0.00 | 26.02 | 21.58 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.103470E+09 | 5038.62 | 24-JAN-04:01 | -11.7 | -13.2 | 0.00 | 0.00 | 01-JAN-00:10 | -11.7 | -13.2 |
February | 0.115362E+09 | 5294.88 | 12-FEB-22:32 | -8.3 | -8.9 | 0.00 | 0.00 | 01-FEB-00:10 | -8.3 | -8.9 |
March | 0.433873E+09 | 6211.80 | 06-MAR-04:01 | -11.1 | -11.9 | 0.00 | 0.00 | 01-MAR-00:10 | -11.1 | -11.9 |
April | 0.805030E+09 | 4834.27 | 17-APR-04:01 | -3.4 | -5.0 | 0.00 | 0.00 | 01-APR-00:10 | -3.4 | -5.0 |
May | 0.241970E+10 | 4183.37 | 30-MAY-05:10 | 12.20 | 11.93 | 0.00 | 0.00 | 01-MAY-00:10 | 12.20 | 11.93 |
June | 0.501326E+10 | 5829.46 | 27-JUN-16:00 | 26.10 | 22.53 | 0.00 | 0.00 | 01-JUN-00:10 | 26.10 | 22.53 |
July | 0.647265E+10 | 7573.73 | 05-JUL-05:15 | 19.23 | 16.66 | 0.00 | 0.00 | 01-JUL-00:10 | 19.23 | 16.66 |
August | 0.633114E+10 | 6708.26 | 07-AUG-05:03 | 20.10 | 18.54 | 0.00 | 0.00 | 01-AUG-00:10 | 20.10 | 18.54 |
September | 0.374459E+10 | 5530.64 | 18-SEP-05:10 | 9.50 | 8.65 | 0.00 | 0.00 | 01-SEP-00:10 | 9.50 | 8.65 |
October | 0.114729E+10 | 4563.08 | 17-OCT-05:01 | -2.8 | -3.4 | 0.00 | 0.00 | 01-OCT-00:10 | -2.8 | -3.4 |
November | 0.318892E+09 | 5537.24 | 24-NOV-05:01 | -3.0 | -3.7 | 0.00 | 0.00 | 01-NOV-00:10 | -3.0 | -3.7 |
December | 0.105232E+09 | 5548.76 | 07-DEC-04:01 | -7.8 | -8.1 | 0.00 | 0.00 | 01-DEC-00:10 | -7.8 | -8.1 |
Annual Sum or Average | 0.270105E+11 | 0.00 | ||||||||
Minimum of Months | 0.103470E+09 | 4183.37 | -11.7 | -13.2 | 0.00 | 0.00 | -11.7 | -13.2 | ||
Maximum of Months | 0.647265E+10 | 7573.73 | 26.10 | 22.53 | 0.00 | 0.00 | 26.10 | 22.53 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 | -1.6 | 0.00 | 0.00 | 01-JAN-00:10 | -1.0 | -1.6 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 | -4.7 | 0.00 | 0.00 | 01-FEB-00:10 | -3.3 | -4.7 |
March | 0.465355E+09 | 10078.57 | 15-MAR-14:00 | 26.10 | 16.06 | 0.00 | 0.00 | 01-MAR-00:10 | 26.10 | 16.06 |
April | 0.137148E+10 | 7701.06 | 21-APR-14:20 | 14.60 | 8.38 | 0.00 | 0.00 | 01-APR-00:10 | 14.60 | 8.38 |
May | 0.441787E+10 | 12769.47 | 31-MAY-14:20 | 21.70 | 14.12 | 0.00 | 0.00 | 01-MAY-00:10 | 21.70 | 14.12 |
June | 0.926860E+10 | 17858.60 | 12-JUN-13:50 | 30.40 | 20.15 | 0.00 | 0.00 | 01-JUN-00:10 | 30.40 | 20.15 |
July | 0.116289E+11 | 18659.18 | 21-JUL-13:50 | 31.52 | 21.79 | 0.00 | 0.00 | 01-JUL-00:10 | 31.52 | 21.79 |
August | 0.100774E+11 | 17244.96 | 09-AUG-15:20 | 29.40 | 18.24 | 0.00 | 0.00 | 01-AUG-00:10 | 29.40 | 18.24 |
September | 0.477839E+10 | 12876.33 | 21-SEP-15:40 | 26.10 | 17.00 | 0.00 | 0.00 | 01-SEP-00:10 | 26.10 | 17.00 |
October | 0.752734E+09 | 6463.26 | 11-OCT-15:30 | 21.95 | 14.56 | 0.00 | 0.00 | 01-OCT-00:10 | 21.95 | 14.56 |
November | 31173871.21 | 1284.47 | 04-NOV-16:20 | 17.93 | 13.33 | 0.00 | 0.00 | 01-NOV-00:10 | 17.93 | 13.33 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 | 3.07 |
Annual Sum or Average | 0.427919E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | -3.3 | -4.7 | 0.00 | 0.00 | -3.3 | -4.7 | ||
Maximum of Months | 0.116289E+11 | 18659.18 | 31.52 | 21.79 | 0.00 | 0.00 | 31.52 | 21.79 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197586E+10 | 1785.74 | 12-JAN-16:40 | -6.5 | -8.3 | 95230018.16 | 126.82 | 12-JAN-10:50 | -6.5 | -8.3 |
February | 0.666280E+10 | 3983.69 | 28-FEB-17:00 | -0.6 | -3.0 | 86396474.53 | 126.82 | 16-FEB-14:09 | -0.6 | -3.0 |
March | 0.138079E+11 | 6983.36 | 31-MAR-24:00 | 4.20 | 3.93 | 0.103237E+09 | 126.83 | 14-MAR-09:20 | 4.20 | 3.93 |
April | 0.187138E+11 | 7971.44 | 02-APR-17:45 | 6.20 | 4.89 | 91605139.11 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.431271E+10 | 3472.83 | 31-MAY-24:00 | 17.10 | 14.03 | 99235939.41 | 126.85 | 17-MAY-13:39 | 17.10 | 14.03 |
June | 0.935877E+10 | 5348.95 | 30-JUN-24:00 | 16.90 | 13.02 | 98967087.86 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.147568E+11 | 7240.91 | 31-JUL-23:57 | 19.10 | 16.93 | 91888913.48 | 126.84 | 19-JUL-09:09 | 19.10 | 16.93 |
August | 0.197722E+11 | 8060.16 | 04-AUG-18:30 | 26.95 | 16.52 | 0.103238E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.428601E+10 | 3197.54 | 30-SEP-24:00 | 14.40 | 12.09 | 91611272.33 | 126.85 | 25-SEP-13:00 | 14.40 | 12.09 |
October | 0.909935E+10 | 5145.21 | 31-OCT-24:00 | 6.60 | 4.77 | 95232235.59 | 126.84 | 26-OCT-09:00 | 6.60 | 4.77 |
November | 0.134994E+11 | 5765.29 | 24-NOV-16:10 | 4.13 | 1.57 | 94300297.11 | 126.82 | 10-NOV-14:00 | 4.13 | 1.57 |
December | 0.183276E+11 | 7621.99 | 04-DEC-16:10 | -0.9 | -3.5 | 91880869.57 | 126.82 | 01-DEC-14:09 | -0.9 | -3.5 |
Annual Sum or Average | 0.134573E+12 | 0.114282E+10 | ||||||||
Minimum of Months | 0.197586E+10 | 1785.74 | -6.5 | -8.3 | 86396474.53 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.197722E+11 | 8060.16 | 26.95 | 16.93 | 0.103238E+09 | 126.86 | 19.10 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.268270E+09 | 1239.92 | 12-JAN-16:40 | -6.5 | -8.3 | 92665963.91 | 126.82 | 12-JAN-14:20 | -6.5 | -8.3 |
February | 0.378897E+10 | 3328.54 | 28-FEB-17:00 | -0.6 | -3.0 | 86396480.60 | 126.82 | 16-FEB-14:09 | -0.6 | -3.0 |
March | 0.111774E+11 | 6070.57 | 31-MAR-23:50 | 4.30 | 3.99 | 0.103237E+09 | 126.83 | 14-MAR-09:09 | 4.30 | 3.99 |
April | 0.165773E+11 | 7480.56 | 24-APR-18:00 | 11.70 | 8.10 | 91605160.39 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.353075E+10 | 3258.05 | 31-MAY-24:00 | 17.10 | 14.03 | 99235649.25 | 126.84 | 24-MAY-09:00 | 17.10 | 14.03 |
June | 0.868817E+10 | 5135.20 | 30-JUN-24:00 | 16.90 | 13.02 | 98966598.14 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.140155E+11 | 7001.52 | 31-JUL-23:57 | 19.10 | 16.93 | 91889308.95 | 126.85 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.187737E+11 | 7691.69 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.357686E+10 | 2619.24 | 30-SEP-24:00 | 14.40 | 12.09 | 91609501.95 | 126.84 | 08-SEP-13:00 | 14.40 | 12.09 |
October | 0.728491E+10 | 4383.83 | 31-OCT-24:00 | 6.60 | 4.77 | 95232080.41 | 126.84 | 26-OCT-09:00 | 6.60 | 4.77 |
November | 0.108051E+11 | 5269.59 | 15-NOV-16:30 | 10.55 | 6.20 | 94300316.83 | 126.82 | 10-NOV-14:00 | 10.55 | 6.20 |
December | 0.142971E+11 | 6712.94 | 04-DEC-16:20 | -1.1 | -3.7 | 91880879.74 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.112784E+12 | 0.114026E+10 | ||||||||
Minimum of Months | 0.268270E+09 | 1239.92 | -6.5 | -8.3 | 86396480.60 | 126.82 | -6.5 | -8.3 | ||
Maximum of Months | 0.187737E+11 | 7691.69 | 22.07 | 16.93 | 0.103239E+09 | 126.86 | 19.10 | 17.48 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116904E+09 | 975.05 | 12-JAN-16:30 | -6.4 | -8.3 | 88186152.32 | 127.90 | 17-JAN-14:00 | 6.70 | 5.64 |
February | 0.255127E+10 | 3338.56 | 28-FEB-17:00 | -0.6 | -3.0 | 86393720.36 | 126.82 | 16-FEB-14:09 | -0.6 | -3.0 |
March | 0.960583E+10 | 5593.19 | 31-MAR-23:20 | 4.60 | 4.18 | 0.103237E+09 | 126.83 | 14-MAR-09:20 | 4.60 | 4.18 |
April | 0.154128E+11 | 7468.01 | 24-APR-18:00 | 11.70 | 8.10 | 91605168.01 | 126.82 | 28-APR-13:00 | 10.00 | 9.06 |
May | 0.299683E+10 | 3161.16 | 31-MAY-24:00 | 17.10 | 14.03 | 99235599.35 | 126.84 | 24-MAY-09:00 | 17.10 | 14.03 |
June | 0.858245E+10 | 5066.35 | 30-JUN-24:00 | 16.90 | 13.02 | 98966926.31 | 126.86 | 27-JUN-13:00 | 16.90 | 13.02 |
July | 0.140457E+11 | 6996.17 | 31-JUL-23:57 | 19.10 | 16.93 | 91889565.89 | 126.85 | 05-JUL-13:09 | 19.10 | 16.93 |
August | 0.187172E+11 | 7746.17 | 02-AUG-18:40 | 22.07 | 14.68 | 0.103239E+09 | 126.83 | 30-AUG-09:00 | 17.80 | 17.48 |
September | 0.312383E+10 | 2166.18 | 04-SEP-17:34 | 17.23 | 12.32 | 91609193.38 | 126.85 | 08-SEP-13:00 | 22.80 | 18.10 |
October | 0.578509E+10 | 3935.87 | 31-OCT-23:20 | 6.87 | 4.91 | 95232034.62 | 126.83 | 12-OCT-13:00 | 6.87 | 4.91 |
November | 0.899224E+10 | 5102.87 | 15-NOV-16:30 | 10.55 | 6.20 | 94300316.34 | 126.82 | 10-NOV-14:00 | 10.55 | 6.20 |
December | 0.125135E+11 | 6336.05 | 04-DEC-16:20 | -1.1 | -3.7 | 91880883.83 | 126.82 | 01-DEC-14:09 | -1.1 | -3.7 |
Annual Sum or Average | 0.102444E+12 | 0.113578E+10 | ||||||||
Minimum of Months | 0.116904E+09 | 975.05 | -6.4 | -8.3 | 86393720.36 | 126.82 | -1.1 | -3.7 | ||
Maximum of Months | 0.187172E+11 | 7746.17 | 22.07 | 16.93 | 0.103239E+09 | 127.90 | 22.80 | 18.10 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.233457E+12 | 90181.48 | 19-JAN-17:00 | 0.60 | -0.1 | 0.206152E+10 | 2746.77 | 20-JAN-10:00 | -1.7 | -2.7 |
February | 0.430797E+12 | 181684.19 | 23-FEB-17:00 | -0.6 | -1.8 | 0.187145E+10 | 2749.16 | 21-FEB-14:00 | -0.6 | -1.8 |
March | 0.726002E+12 | 357824.67 | 31-MAR-24:00 | 4.20 | 3.93 | 0.223597E+10 | 2749.03 | 07-MAR-10:09 | 4.20 | 3.93 |
April | 0.940944E+12 | 366581.01 | 24-APR-16:00 | 13.30 | 7.63 | 0.198331E+10 | 2748.03 | 17-APR-13:00 | 13.30 | 7.63 |
May | 0.239133E+12 | 175514.38 | 31-MAY-24:00 | 17.10 | 14.03 | 0.214825E+10 | 2746.23 | 04-MAY-13:09 | 17.10 | 14.03 |
June | 0.469370E+12 | 267569.97 | 30-JUN-24:00 | 16.90 | 13.02 | 0.214239E+10 | 2746.41 | 14-JUN-13:09 | 16.90 | 13.02 |
July | 0.731309E+12 | 359769.91 | 31-JUL-23:57 | 19.10 | 16.93 | 0.198911E+10 | 2745.81 | 05-JUL-13:00 | 19.10 | 16.93 |
August | 0.976287E+12 | 369383.69 | 04-AUG-21:02 | 21.52 | 16.10 | 0.231543E+10 | 3246.45 | 10-AUG-13:00 | 30.60 | 20.24 |
September | 0.235002E+12 | 175249.67 | 30-SEP-24:00 | 14.40 | 12.09 | 0.198325E+10 | 2746.56 | 14-SEP-13:00 | 14.40 | 12.09 |
October | 0.485838E+12 | 267942.39 | 31-OCT-24:00 | 6.60 | 4.77 | 0.206165E+10 | 2747.47 | 17-OCT-13:09 | 6.60 | 4.77 |
November | 0.706550E+12 | 275758.38 | 06-NOV-17:00 | 6.10 | 3.25 | 0.204171E+10 | 2747.09 | 22-NOV-10:09 | 1.10 | -1.2 |
December | 0.972304E+12 | 366355.85 | 15-DEC-17:00 | 2.80 | 1.83 | 0.199044E+10 | 2749.77 | 26-DEC-14:09 | -9.4 | -11.1 |
Annual Sum or Average | 0.714699E+13 | 0.248245E+11 | ||||||||
Minimum of Months | 0.233457E+12 | 90181.48 | -0.6 | -1.8 | 0.187145E+10 | 2745.81 | -9.4 | -11.1 | ||
Maximum of Months | 0.976287E+12 | 369383.69 | 21.52 | 16.93 | 0.231543E+10 | 3246.45 | 30.60 | 20.24 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 38632410.68 | 10578.78 | 10-JAN-06:05 | -13.0 |
February | 30321254.58 | 10538.37 | 14-FEB-06:04 | -9.4 |
March | 0.102021E+09 | 10852.68 | 14-MAR-04:05 | 11.20 |
April | 96330254.48 | 11009.00 | 03-APR-03:05 | -1.8 |
May | 0.231141E+09 | 11097.22 | 08-MAY-03:15 | 2.97 |
June | 0.214112E+09 | 13710.36 | 17-JUN-16:02 | 28.40 |
July | 0.295873E+09 | 12602.48 | 15-JUL-16:02 | 27.65 |
August | 0.342578E+09 | 12269.89 | 05-AUG-16:02 | 27.30 |
September | 0.504798E+09 | 11105.57 | 16-SEP-16:02 | 26.60 |
October | 0.333740E+09 | 10882.31 | 11-OCT-03:05 | 9.90 |
November | 0.313999E+09 | 11052.64 | 24-NOV-05:25 | -3.3 |
December | 67954001.84 | 10476.35 | 04-DEC-04:54 | -2.2 |
Annual Sum or Average | 0.257150E+10 | |||
Minimum of Months | 30321254.58 | 10476.35 | -13.0 | |
Maximum of Months | 0.504798E+09 | 13710.36 | 28.40 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.913513E+09 | 53936.48 | 02-JAN-04:01 | -1.0 |
February | 0.400487E+09 | 48132.87 | 06-FEB-05:01 | -14.8 |
March | 14658454.38 | 45027.69 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.271702E+09 | 48699.84 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.160036E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.913513E+09 | 53936.48 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.635891E+10 | 75834.27 | 02-JAN-04:01 | -1.0 |
February | 0.543210E+10 | 75235.95 | 06-FEB-04:01 | -15.0 |
March | 0.207642E+10 | 73241.44 | 06-MAR-04:01 | -11.1 |
April | 0.394801E+09 | 68799.45 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.367895E+09 | 67024.86 | 30-OCT-04:01 | -0.5 |
November | 0.107241E+10 | 68777.63 | 24-NOV-05:01 | -3.0 |
December | 0.494585E+10 | 75904.83 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.206484E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.635891E+10 | 75904.83 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.777764E+09 | 11682.61 | 30-JAN-05:01 | -9.5 |
February | 0.665599E+09 | 11729.17 | 07-FEB-05:01 | -15.7 |
March | 70395750.28 | 10743.00 | 06-MAR-05:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.210531E+09 | 11041.67 | 11-DEC-05:01 | -17.5 |
Annual Sum or Average | 0.172429E+10 | |||
Minimum of Months | 0.00 | 0.00 | -17.5 | |
Maximum of Months | 0.777764E+09 | 11729.17 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.573094E+09 | 12452.07 | 30-JAN-05:01 | -9.5 |
February | 0.546439E+09 | 12475.66 | 06-FEB-05:01 | -14.8 |
March | 44811547.13 | 11171.10 | 06-MAR-05:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 401108.53 | 2631.18 | 25-NOV-06:01 | -1.7 |
December | 0.318473E+09 | 12042.38 | 12-DEC-05:01 | -9.9 |
Annual Sum or Average | 0.148322E+10 | |||
Minimum of Months | 0.00 | 0.00 | -14.8 | |
Maximum of Months | 0.573094E+09 | 12475.66 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.997297E+09 | 17355.41 | 30-JAN-04:01 | -9.9 |
February | 0.963876E+09 | 17957.73 | 06-FEB-04:01 | -15.0 |
March | 0.100290E+09 | 15903.20 | 06-MAR-05:01 | -11.1 |
April | 3135521.85 | 7096.23 | 17-APR-05:03 | -4.0 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 1732130.11 | 14160.17 | 30-OCT-05:01 | -0.1 |
November | 9600960.14 | 12572.20 | 24-NOV-06:03 | -3.8 |
December | 0.448021E+09 | 16968.47 | 26-DEC-05:01 | -12.2 |
Annual Sum or Average | 0.252395E+10 | |||
Minimum of Months | 0.00 | 0.00 | -15.0 | |
Maximum of Months | 0.997297E+09 | 17957.73 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.118306E+09 | 10841.36 | 30-JAN-05:01 | -9.5 |
February | 66786898.96 | 10966.57 | 06-FEB-05:01 | -14.8 |
March | 87632.24 | 1314.48 | 06-MAR-06:01 | -11.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 2110642.89 | 9322.84 | 11-DEC-06:01 | -18.5 |
Annual Sum or Average | 0.187292E+09 | |||
Minimum of Months | 0.00 | 0.00 | -18.5 | |
Maximum of Months | 0.118306E+09 | 10966.57 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.702071E+10 | 12877.40 | 29-JAN-23:02 | -9.0 |
February | 0.614805E+10 | 13233.61 | 06-FEB-00:12 | -12.8 |
March | 0.208362E+10 | 12129.26 | 06-MAR-04:01 | -11.1 |
April | 0.242057E+09 | 11321.49 | 17-APR-03:01 | -2.9 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.131098E+09 | 10658.40 | 30-OCT-04:01 | -0.5 |
November | 0.734682E+09 | 11173.14 | 24-NOV-04:01 | -3.2 |
December | 0.570636E+10 | 12881.47 | 25-DEC-20:32 | -9.2 |
Annual Sum or Average | 0.220666E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.702071E+10 | 13233.61 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.420660E+10 | 17038.13 | 29-JAN-23:02 | -9.0 |
February | 0.368052E+10 | 17397.30 | 05-FEB-23:32 | -12.8 |
March | 0.878337E+09 | 16138.55 | 06-MAR-04:01 | -11.1 |
April | 0.112531E+09 | 14772.44 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 75358742.90 | 14209.58 | 30-OCT-04:01 | -0.5 |
November | 0.458914E+09 | 14674.67 | 25-NOV-05:01 | -1.7 |
December | 0.373093E+10 | 17035.81 | 25-DEC-20:32 | -9.2 |
Annual Sum or Average | 0.131432E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.420660E+10 | 17397.30 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460565E+10 | 19197.02 | 29-JAN-23:02 | -9.0 |
February | 0.423494E+10 | 19653.00 | 06-FEB-00:12 | -12.8 |
March | 0.829556E+09 | 18103.24 | 06-MAR-04:01 | -11.1 |
April | 0.162951E+09 | 16337.42 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 56278585.02 | 15608.57 | 30-OCT-04:01 | -0.5 |
November | 0.480124E+09 | 16565.90 | 24-NOV-05:01 | -3.0 |
December | 0.392541E+10 | 19069.94 | 26-DEC-03:51 | -11.7 |
Annual Sum or Average | 0.142949E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.460565E+10 | 19653.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.359422E+10 | 17818.52 | 29-JAN-23:02 | -9.0 |
February | 0.296823E+10 | 18180.89 | 05-FEB-23:32 | -12.8 |
March | 0.645658E+09 | 16970.49 | 06-MAR-04:01 | -11.1 |
April | 65067291.95 | 14730.12 | 17-APR-04:01 | -3.4 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 43385669.09 | 13804.27 | 30-OCT-05:01 | -0.1 |
November | 0.298204E+09 | 15427.25 | 24-NOV-05:01 | -3.0 |
December | 0.269714E+10 | 17650.91 | 26-DEC-03:51 | -11.7 |
Annual Sum or Average | 0.103119E+11 | |||
Minimum of Months | 0.00 | 0.00 | -12.8 | |
Maximum of Months | 0.359422E+10 | 18180.89 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.126778E+11 | 17281.69 | 29-JAN-23:02 | -9.0 |
February | 0.114810E+11 | 17323.04 | 12-FEB-17:52 | -7.2 |
March | 0.550409E+10 | 16809.54 | 06-MAR-02:62 | -10.6 |
April | 0.143223E+10 | 15876.80 | 16-APR-07:43 | -3.0 |
May | 44382837.47 | 12794.69 | 01-MAY-05:02 | 1.70 |
June | 323923.20 | 2159.49 | 14-JUN-05:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 39869878.19 | 12511.66 | 29-SEP-05:03 | 10.50 |
October | 0.110889E+10 | 15742.89 | 30-OCT-03:01 | -0.1 |
November | 0.326763E+10 | 15646.97 | 20-NOV-04:01 | 5.50 |
December | 0.116193E+11 | 17414.02 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.471756E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.126778E+11 | 17414.02 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.767249E+10 | 18012.67 | 29-JAN-23:02 | -9.0 |
February | 0.690476E+10 | 18071.11 | 12-FEB-17:52 | -7.2 |
March | 0.257161E+10 | 17368.29 | 06-MAR-01:22 | -10.6 |
April | 0.656859E+09 | 16153.61 | 17-APR-03:01 | -2.9 |
May | 16998231.23 | 13294.59 | 01-MAY-05:02 | 1.70 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 24225042.50 | 9063.64 | 29-SEP-05:03 | 10.50 |
October | 0.568052E+09 | 16508.17 | 30-OCT-03:01 | -0.1 |
November | 0.191855E+10 | 16354.68 | 20-NOV-04:01 | 5.50 |
December | 0.745039E+10 | 18259.43 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.277839E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.767249E+10 | 18259.43 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.916427E+10 | 21828.58 | 29-JAN-23:02 | -9.0 |
February | 0.868773E+10 | 21947.03 | 12-FEB-22:32 | -8.3 |
March | 0.296443E+10 | 20783.46 | 06-MAR-03:22 | -10.8 |
April | 0.103380E+10 | 19692.74 | 17-APR-03:01 | -2.9 |
May | 34507014.74 | 14458.71 | 01-MAY-05:02 | 1.70 |
June | 1048200.43 | 5420.56 | 14-JUN-05:03 | 6.78 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 26478674.33 | 13462.03 | 29-SEP-05:03 | 10.50 |
October | 0.629455E+09 | 19894.94 | 30-OCT-03:01 | -0.1 |
November | 0.226149E+10 | 19845.74 | 20-NOV-04:01 | 5.50 |
December | 0.894753E+10 | 21884.43 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.337507E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.916427E+10 | 21947.03 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692500E+10 | 19877.35 | 29-JAN-23:02 | -9.0 |
February | 0.578990E+10 | 19758.93 | 12-FEB-17:52 | -7.2 |
March | 0.200207E+10 | 18839.06 | 06-MAR-04:01 | -11.1 |
April | 0.455431E+09 | 17831.56 | 17-APR-03:01 | -2.9 |
May | 3843799.00 | 7565.23 | 12-MAY-05:03 | 8.90 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 12735645.62 | 8571.04 | 29-SEP-05:03 | 10.50 |
October | 0.388989E+09 | 17760.90 | 30-OCT-03:01 | -0.1 |
November | 0.131381E+10 | 17898.89 | 24-NOV-04:01 | -3.2 |
December | 0.570833E+10 | 19796.26 | 11-DEC-04:11 | -17.2 |
Annual Sum or Average | 0.226001E+11 | |||
Minimum of Months | 0.00 | 0.00 | -17.2 | |
Maximum of Months | 0.692500E+10 | 19877.35 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.199453E+10 | 11377.61 | 18-JAN-06:01 | 2.80 |
February | 0.217055E+10 | 13826.47 | 15-FEB-06:01 | 5.60 |
March | 0.597026E+09 | 13031.86 | 13-MAR-04:01 | 10.73 |
April | 0.158635E+09 | 12161.91 | 18-APR-04:01 | 3.98 |
May | 95764418.74 | 9201.61 | 01-MAY-03:02 | 4.48 |
June | 0.100481E+09 | 9296.04 | 05-JUN-03:02 | 15.82 |
July | 0.119285E+09 | 7993.53 | 06-JUL-03:02 | 13.12 |
August | 0.108848E+09 | 9697.44 | 31-AUG-03:02 | 12.12 |
September | 81163330.16 | 9211.55 | 01-SEP-03:02 | 15.43 |
October | 95896790.41 | 11174.39 | 30-OCT-04:01 | -0.5 |
November | 94218034.85 | 12843.00 | 24-NOV-05:01 | -3.0 |
December | 0.125349E+10 | 14687.29 | 18-DEC-05:01 | 1.70 |
Annual Sum or Average | 0.686989E+10 | |||
Minimum of Months | 81163330.16 | 7993.53 | -3.0 | |
Maximum of Months | 0.217055E+10 | 14687.29 | 15.82 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.586406E+10 | 17773.28 | 02-JAN-06:12 | -1.1 |
February | 0.504927E+10 | 11215.24 | 13-FEB-06:12 | -9.4 |
March | 0.241386E+10 | 7854.47 | 15-MAR-05:03 | 15.00 |
April | 0.740859E+09 | 8161.47 | 07-APR-05:03 | 10.60 |
May | 77704073.01 | 7726.40 | 30-MAY-03:02 | 12.20 |
June | 60109895.39 | 6689.04 | 13-JUN-04:03 | 9.82 |
July | 60394192.93 | 7045.85 | 20-JUL-03:02 | 25.50 |
August | 52667463.43 | 7023.62 | 14-AUG-03:02 | 23.80 |
September | 62318638.60 | 7152.57 | 29-SEP-05:03 | 10.50 |
October | 0.483616E+09 | 8062.52 | 26-OCT-05:02 | 15.50 |
November | 0.121272E+10 | 7546.05 | 01-NOV-05:02 | 5.68 |
December | 0.435776E+10 | 11210.52 | 11-DEC-06:12 | -18.2 |
Annual Sum or Average | 0.204353E+11 | |||
Minimum of Months | 52667463.43 | 6689.04 | -18.2 | |
Maximum of Months | 0.586406E+10 | 17773.28 | 25.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158766E+11 | 27138.20 | 30-JAN-05:08 | -9.5 |
February | 0.140893E+11 | 28664.52 | 06-FEB-05:20 | -14.6 |
March | 0.724392E+10 | 26865.47 | 06-MAR-05:33 | -11.1 |
April | 0.277275E+10 | 21510.04 | 17-APR-04:12 | -3.5 |
May | 0.672501E+09 | 17390.78 | 23-MAY-05:02 | 7.38 |
June | 0.193442E+09 | 16323.44 | 06-JUN-05:03 | 6.78 |
July | 0.101284E+09 | 13563.32 | 13-JUL-05:02 | 11.88 |
August | 0.141783E+09 | 14179.67 | 03-AUG-05:02 | 11.10 |
September | 0.521879E+09 | 15794.43 | 12-SEP-05:03 | 9.40 |
October | 0.246278E+10 | 20248.84 | 30-OCT-05:13 | -0.2 |
November | 0.570674E+10 | 22055.63 | 24-NOV-05:12 | -3.2 |
December | 0.147755E+11 | 28530.19 | 11-DEC-05:12 | -17.8 |
Annual Sum or Average | 0.645585E+11 | |||
Minimum of Months | 0.101284E+09 | 13563.32 | -17.8 | |
Maximum of Months | 0.158766E+11 | 28664.52 | 11.88 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.648440E+09 | 549.73 | 23-JAN-24:00 | -11.1 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.648440E+09 | |||
Minimum of Months | 0.00 | 0.00 | -11.1 | |
Maximum of Months | 0.648440E+09 | 549.73 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.773422E+09 | 590.10 | 15-JAN-17:55 | 1.10 |
February | 0.158908E+09 | 548.68 | 05-FEB-18:53 | -10.6 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 142857.23 | 24.84 | 30-SEP-07:00 | 7.80 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.932473E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.6 | |
Maximum of Months | 0.773422E+09 | 590.10 | 18.85 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | -1.0 |
February | 0.00 | 0.00 | 01-FEB-00:03 | -3.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -4.9 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.10 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 6.67 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 17.05 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 16.82 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 18.85 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14.65 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14.42 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.53 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.95 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -4.9 | |
Maximum of Months | 0.00 | 0.00 | 18.85 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123595E+10 | 1750.00 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.107634E+10 | 1591.22 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122869E+10 | 1389.41 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107387E+10 | 1250.95 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113907E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112359E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105698E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118594E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108914E+10 | 1352.79 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117114E+10 | 1710.62 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.122946E+10 | 1750.00 | 06-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.122272E+10 | 1750.00 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.138329E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105698E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.123595E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788487E+09 | 1127.77 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.691843E+09 | 1032.51 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.790676E+09 | 828.03 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.692787E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.736705E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.726825E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.683538E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.766719E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701400E+09 | 801.65 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.750062E+09 | 1044.87 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.786291E+09 | 1127.77 | 06-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.779208E+09 | 1127.77 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.889454E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.683538E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.790676E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.120927E+10 | 1750.04 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106622E+10 | 1567.10 | 01-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122272E+10 | 1362.94 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107544E+10 | 1243.55 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114342E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.112841E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106132E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118913E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108807E+10 | 1332.67 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115833E+10 | 1580.32 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.120810E+10 | 1750.04 | 06-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.119705E+10 | 1750.04 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137475E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106132E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122272E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.787528E+09 | 1127.77 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.690009E+09 | 1022.53 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.790388E+09 | 928.16 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.692750E+09 | 846.04 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.734965E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.725083E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.682408E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.764966E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702394E+09 | 905.11 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.753584E+09 | 1102.96 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.785198E+09 | 1127.77 | 06-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.779876E+09 | 1127.77 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.888915E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682408E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.790388E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123859E+10 | 1750.00 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.107749E+10 | 1595.99 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122955E+10 | 1400.28 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107430E+10 | 1265.74 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113956E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112422E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105728E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118633E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108984E+10 | 1364.57 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117263E+10 | 1712.08 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.123164E+10 | 1750.00 | 06-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.122542E+10 | 1750.00 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.138469E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105728E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.123859E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788878E+09 | 1127.77 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.692084E+09 | 1033.28 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.791039E+09 | 832.81 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.692932E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.736852E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.726979E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.683671E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.766861E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701661E+09 | 806.87 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.750343E+09 | 1046.16 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.786778E+09 | 1127.77 | 06-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.779827E+09 | 1127.77 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.889790E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.683671E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.791039E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121123E+10 | 1750.04 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106754E+10 | 1573.04 | 01-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122356E+10 | 1374.97 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107598E+10 | 1258.60 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114401E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.112888E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106175E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118966E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108868E+10 | 1345.25 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115974E+10 | 1653.72 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.121033E+10 | 1750.04 | 06-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.119873E+10 | 1750.04 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137601E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106175E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122356E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788127E+09 | 1127.77 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.690285E+09 | 1023.37 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.790694E+09 | 929.71 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.692979E+09 | 848.18 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.735148E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.725172E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.682501E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.765113E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702622E+09 | 906.82 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.754010E+09 | 1103.52 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.785606E+09 | 1127.77 | 06-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.780378E+09 | 1127.77 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.889263E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682501E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.790694E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.123857E+10 | 1750.00 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.107747E+10 | 1595.86 | 01-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.122961E+10 | 1400.02 | 17-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107430E+10 | 1265.32 | 12-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113956E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112422E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105728E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118633E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108986E+10 | 1364.25 | 26-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117262E+10 | 1712.12 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.123162E+10 | 1750.00 | 06-NOV-16:00 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.122539E+10 | 1750.00 | 01-DEC-16:40 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.138469E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105728E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.123857E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788869E+09 | 1127.77 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.692079E+09 | 1033.20 | 01-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.791042E+09 | 832.72 | 17-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.692932E+09 | 692.79 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.736851E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.726969E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.683685E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.766861E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.701662E+09 | 806.75 | 26-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.750344E+09 | 1046.33 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.786770E+09 | 1127.77 | 06-NOV-16:00 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.779817E+09 | 1127.77 | 01-DEC-16:40 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.889788E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.683685E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.791042E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121117E+10 | 1750.04 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106754E+10 | 1572.91 | 01-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122354E+10 | 1374.71 | 17-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107596E+10 | 1258.18 | 12-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114401E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.112888E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106175E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118967E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108867E+10 | 1344.93 | 26-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115973E+10 | 1653.88 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.121026E+10 | 1750.04 | 06-NOV-16:00 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.119872E+10 | 1750.04 | 01-DEC-16:40 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137599E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106175E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122354E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.788124E+09 | 1127.77 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.690282E+09 | 1023.27 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.790693E+09 | 929.54 | 17-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.692980E+09 | 847.92 | 12-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.735160E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.725173E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.682507E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.765114E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.702621E+09 | 906.62 | 26-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.754047E+09 | 1103.55 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.785600E+09 | 1127.77 | 06-NOV-16:00 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.780368E+09 | 1127.77 | 01-DEC-16:40 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.889267E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.682507E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.790693E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.123595E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168731E+10 |
February | 0.136985E+10 | 0.107634E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178530E+10 |
March | 0.163685E+10 | 0.122869E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360189.55 | 0.113880E+10 |
April | 0.145243E+10 | 0.107387E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.940594E+09 |
May | 0.157338E+10 | 0.113907E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 276648.93 | 0.538228E+09 |
June | 0.156900E+10 | 0.112359E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9126078.45 | 0.299699E+09 |
July | 0.145680E+10 | 0.105698E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23265380.27 | 0.164312E+09 |
August | 0.163685E+10 | 0.118594E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17600072.68 | 0.192503E+09 |
September | 0.145243E+10 | 0.108914E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1281107.69 | 0.315330E+09 |
October | 0.150991E+10 | 0.117114E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.737608E+09 |
November | 0.149516E+10 | 0.122946E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101888E+10 |
December | 0.145680E+10 | 0.122272E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185372E+10 |
Annual Sum or Average | 0.181194E+11 | 0.138329E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 51909477.56 | 0.106723E+11 |
Minimum of Months | 0.136985E+10 | 0.105698E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164312E+09 |
Maximum of Months | 0.163685E+10 | 0.123595E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23265380.27 | 0.185372E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.788487E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112015E+10 |
February | 0.882782E+09 | 0.691843E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117975E+10 |
March | 0.105485E+10 | 0.790676E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 240140.81 | 0.752980E+09 |
April | 0.936002E+09 | 0.692787E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.614490E+09 |
May | 0.101394E+10 | 0.736705E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 241507.30 | 0.362388E+09 |
June | 0.101113E+10 | 0.726825E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6195923.46 | 0.196484E+09 |
July | 0.938820E+09 | 0.683538E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16471400.16 | 0.101893E+09 |
August | 0.105485E+10 | 0.766719E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12426908.00 | 0.118258E+09 |
September | 0.936002E+09 | 0.701400E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 894341.81 | 0.209355E+09 |
October | 0.973041E+09 | 0.750062E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.486975E+09 |
November | 0.963541E+09 | 0.786291E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659631E+09 |
December | 0.938820E+09 | 0.779208E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120852E+10 |
Annual Sum or Average | 0.116768E+11 | 0.889454E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 36470221.54 | 0.701087E+10 |
Minimum of Months | 0.882782E+09 | 0.683538E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101893E+09 |
Maximum of Months | 0.105485E+10 | 0.790676E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16471400.16 | 0.120852E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.120927E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167589E+10 |
February | 0.136988E+10 | 0.106622E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176102E+10 |
March | 0.163688E+10 | 0.122272E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 359261.57 | 0.114925E+10 |
April | 0.145246E+10 | 0.107544E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.930787E+09 |
May | 0.157341E+10 | 0.114342E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 164038.17 | 0.542686E+09 |
June | 0.156904E+10 | 0.112841E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8747446.68 | 0.300806E+09 |
July | 0.145684E+10 | 0.106132E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22334907.52 | 0.168548E+09 |
August | 0.163688E+10 | 0.118913E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16026316.06 | 0.200094E+09 |
September | 0.145246E+10 | 0.108807E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1148277.47 | 0.326950E+09 |
October | 0.150994E+10 | 0.115833E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742138E+09 |
November | 0.149520E+10 | 0.120810E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993883E+09 |
December | 0.145684E+10 | 0.119705E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181913E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137475E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 48780247.47 | 0.106112E+11 |
Minimum of Months | 0.136988E+10 | 0.106132E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168548E+09 |
Maximum of Months | 0.163688E+10 | 0.122272E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22334907.52 | 0.181913E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.787528E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116299E+10 |
February | 0.882782E+09 | 0.690009E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125295E+10 |
March | 0.105485E+10 | 0.790388E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 240122.11 | 0.832424E+09 |
April | 0.936002E+09 | 0.692750E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697474E+09 |
May | 0.101394E+10 | 0.734965E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 109360.85 | 0.392605E+09 |
June | 0.101113E+10 | 0.725083E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5466886.37 | 0.227937E+09 |
July | 0.938820E+09 | 0.682408E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14053773.43 | 0.135589E+09 |
August | 0.105485E+10 | 0.764966E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10345576.12 | 0.157812E+09 |
September | 0.936002E+09 | 0.702394E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 733058.05 | 0.231174E+09 |
October | 0.973041E+09 | 0.753584E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534673E+09 |
November | 0.963541E+09 | 0.785198E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.740055E+09 |
December | 0.938820E+09 | 0.779876E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134290E+10 |
Annual Sum or Average | 0.116768E+11 | 0.888915E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 30948776.94 | 0.770858E+10 |
Minimum of Months | 0.882782E+09 | 0.682408E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135589E+09 |
Maximum of Months | 0.105485E+10 | 0.790388E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14053773.43 | 0.134290E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.123859E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353264E+10 |
February | 0.136985E+10 | 0.107749E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.374403E+10 |
March | 0.163685E+10 | 0.122955E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 773657.98 | 0.234266E+10 |
April | 0.145243E+10 | 0.107430E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190351E+10 |
May | 0.157338E+10 | 0.113956E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1167487.84 | 0.115377E+10 |
June | 0.156900E+10 | 0.112422E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23070533.01 | 0.671159E+09 |
July | 0.145680E+10 | 0.105728E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50494219.28 | 0.392494E+09 |
August | 0.163685E+10 | 0.118633E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42179156.58 | 0.456673E+09 |
September | 0.145243E+10 | 0.108984E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2898742.58 | 0.677536E+09 |
October | 0.150991E+10 | 0.117263E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147642E+10 |
November | 0.149516E+10 | 0.123164E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198864E+10 |
December | 0.145680E+10 | 0.122542E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.375094E+10 |
Annual Sum or Average | 0.181194E+11 | 0.138469E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120584E+09 | 0.220905E+11 |
Minimum of Months | 0.136985E+10 | 0.105728E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392494E+09 |
Maximum of Months | 0.163685E+10 | 0.123859E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 50494219.28 | 0.375094E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.788878E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.236641E+10 |
February | 0.649041E+09 | 0.692084E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.251076E+10 |
March | 0.773965E+09 | 0.791039E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 504193.28 | 0.158487E+10 |
April | 0.688021E+09 | 0.692932E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130249E+10 |
May | 0.744847E+09 | 0.736852E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 695516.27 | 0.804157E+09 |
June | 0.742030E+09 | 0.726979E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13633270.87 | 0.461560E+09 |
July | 0.690839E+09 | 0.683671E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32374120.19 | 0.271199E+09 |
August | 0.773965E+09 | 0.766861E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26283303.36 | 0.314754E+09 |
September | 0.688021E+09 | 0.701661E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1972161.21 | 0.465572E+09 |
October | 0.715730E+09 | 0.750343E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101424E+10 |
November | 0.708685E+09 | 0.786778E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133504E+10 |
December | 0.690839E+09 | 0.779827E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250714E+10 |
Annual Sum or Average | 0.858171E+10 | 0.889790E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 75462565.18 | 0.149382E+11 |
Minimum of Months | 0.649041E+09 | 0.683671E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.271199E+09 |
Maximum of Months | 0.773965E+09 | 0.791039E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32374120.19 | 0.251076E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.121123E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.363931E+10 |
February | 0.136988E+10 | 0.106754E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.382811E+10 |
March | 0.163688E+10 | 0.122356E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 749343.14 | 0.250658E+10 |
April | 0.145246E+10 | 0.107598E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200773E+10 |
May | 0.157341E+10 | 0.114401E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 351790.54 | 0.121300E+10 |
June | 0.156904E+10 | 0.112888E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 19599310.86 | 0.687618E+09 |
July | 0.145684E+10 | 0.106175E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47488956.86 | 0.413678E+09 |
August | 0.163688E+10 | 0.118966E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 35433022.41 | 0.492320E+09 |
September | 0.145246E+10 | 0.108868E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2486111.79 | 0.742635E+09 |
October | 0.150994E+10 | 0.115974E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162787E+10 |
November | 0.149520E+10 | 0.121033E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210519E+10 |
December | 0.145684E+10 | 0.119873E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386029E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137601E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106109E+09 | 0.231243E+11 |
Minimum of Months | 0.136988E+10 | 0.106175E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.413678E+09 |
Maximum of Months | 0.163688E+10 | 0.122356E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47488956.86 | 0.386029E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.788127E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239583E+10 |
February | 0.882782E+09 | 0.690285E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254831E+10 |
March | 0.105485E+10 | 0.790694E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 545652.64 | 0.164588E+10 |
April | 0.936002E+09 | 0.692979E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.135327E+10 |
May | 0.101394E+10 | 0.735148E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 234537.01 | 0.837730E+09 |
June | 0.101113E+10 | 0.725172E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13122527.83 | 0.493220E+09 |
July | 0.938820E+09 | 0.682501E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32247195.00 | 0.301648E+09 |
August | 0.105485E+10 | 0.765113E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25271845.90 | 0.347924E+09 |
September | 0.936002E+09 | 0.702622E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1621432.22 | 0.484804E+09 |
October | 0.973041E+09 | 0.754010E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103076E+10 |
November | 0.963541E+09 | 0.785606E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136531E+10 |
December | 0.938820E+09 | 0.780378E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255562E+10 |
Annual Sum or Average | 0.116768E+11 | 0.889263E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 73043190.60 | 0.153603E+11 |
Minimum of Months | 0.882782E+09 | 0.682501E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301648E+09 |
Maximum of Months | 0.105485E+10 | 0.790694E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32247195.00 | 0.255562E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.123857E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.429268E+10 |
February | 0.136985E+10 | 0.107747E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456438E+10 |
March | 0.163685E+10 | 0.122961E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 964087.38 | 0.275406E+10 |
April | 0.145243E+10 | 0.107430E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218638E+10 |
May | 0.157338E+10 | 0.113956E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1308210.40 | 0.134424E+10 |
June | 0.156900E+10 | 0.112422E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 26713939.29 | 0.817001E+09 |
July | 0.145680E+10 | 0.105728E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58599081.93 | 0.491702E+09 |
August | 0.163685E+10 | 0.118633E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 48940786.54 | 0.560740E+09 |
September | 0.145243E+10 | 0.108986E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3314168.74 | 0.784473E+09 |
October | 0.150991E+10 | 0.117262E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161514E+10 |
November | 0.149516E+10 | 0.123162E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223332E+10 |
December | 0.145680E+10 | 0.122539E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451930E+10 |
Annual Sum or Average | 0.181194E+11 | 0.138469E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139840E+09 | 0.261634E+11 |
Minimum of Months | 0.136985E+10 | 0.105728E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.491702E+09 |
Maximum of Months | 0.163685E+10 | 0.123857E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58599081.93 | 0.456438E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.788869E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287631E+10 |
February | 0.882782E+09 | 0.692079E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306351E+10 |
March | 0.105485E+10 | 0.791042E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546986.01 | 0.185312E+10 |
April | 0.936002E+09 | 0.692932E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151038E+10 |
May | 0.101394E+10 | 0.736851E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 624291.58 | 0.957439E+09 |
June | 0.101113E+10 | 0.726969E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15420840.76 | 0.572625E+09 |
July | 0.938820E+09 | 0.683685E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37807208.49 | 0.345669E+09 |
August | 0.105485E+10 | 0.766861E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 30095873.03 | 0.392994E+09 |
September | 0.936002E+09 | 0.701662E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2187356.13 | 0.553115E+09 |
October | 0.973041E+09 | 0.750344E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112455E+10 |
November | 0.963541E+09 | 0.786770E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150474E+10 |
December | 0.938820E+09 | 0.779817E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302248E+10 |
Annual Sum or Average | 0.116768E+11 | 0.889788E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 86682556.00 | 0.177769E+11 |
Minimum of Months | 0.882782E+09 | 0.683685E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.345669E+09 |
Maximum of Months | 0.105485E+10 | 0.791042E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37807208.49 | 0.306351E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.121117E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436760E+10 |
February | 0.136988E+10 | 0.106754E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.462673E+10 |
March | 0.163688E+10 | 0.122354E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 819280.57 | 0.290313E+10 |
April | 0.145246E+10 | 0.107596E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231723E+10 |
May | 0.157341E+10 | 0.114401E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 398624.95 | 0.143159E+10 |
June | 0.156904E+10 | 0.112888E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 22746840.64 | 0.841048E+09 |
July | 0.145684E+10 | 0.106175E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55758226.36 | 0.519142E+09 |
August | 0.163688E+10 | 0.118967E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 41848507.89 | 0.609218E+09 |
September | 0.145246E+10 | 0.108867E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2881152.07 | 0.881633E+09 |
October | 0.150994E+10 | 0.115973E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181164E+10 |
November | 0.149520E+10 | 0.121026E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235666E+10 |
December | 0.145684E+10 | 0.119872E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.458713E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137599E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124453E+09 | 0.272528E+11 |
Minimum of Months | 0.136988E+10 | 0.106175E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519142E+09 |
Maximum of Months | 0.163688E+10 | 0.122354E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55758226.36 | 0.462673E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.788124E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.289689E+10 |
February | 0.882782E+09 | 0.690282E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309237E+10 |
March | 0.105485E+10 | 0.790693E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 650687.78 | 0.192625E+10 |
April | 0.936002E+09 | 0.692980E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157452E+10 |
May | 0.101394E+10 | 0.735160E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 265763.37 | 0.995895E+09 |
June | 0.101113E+10 | 0.725173E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15260845.68 | 0.605308E+09 |
July | 0.938820E+09 | 0.682507E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37806359.48 | 0.377072E+09 |
August | 0.105485E+10 | 0.765114E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29884087.44 | 0.429959E+09 |
September | 0.936002E+09 | 0.702621E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1914326.70 | 0.574861E+09 |
October | 0.973041E+09 | 0.754047E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116166E+10 |
November | 0.963541E+09 | 0.785600E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155612E+10 |
December | 0.938820E+09 | 0.780368E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305742E+10 |
Annual Sum or Average | 0.116768E+11 | 0.889267E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85782070.44 | 0.182483E+11 |
Minimum of Months | 0.882782E+09 | 0.682507E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.377072E+09 |
Maximum of Months | 0.105485E+10 | 0.790693E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37806359.48 | 0.309237E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362101E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381032E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407992.28 | 0.243152E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198005E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563647.75 | 0.111944E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15195879.88 | 0.627757E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38888376.49 | 0.352467E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32282266.60 | 0.422590E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1705182.49 | 0.668328E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155804E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.215565E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.396789E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89043345.48 | 0.227151E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352467E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38888376.49 | 0.396789E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591445E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.624951E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1357475.38 | 0.404307E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331243E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1952207.64 | 0.193210E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 32370053.51 | 0.109709E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68666423.88 | 0.625808E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59749819.88 | 0.753511E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3158726.03 | 0.116211E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260551E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.351050E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.639932E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167255E+09 | 0.376054E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625808E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68666423.88 | 0.639932E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.627597E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667085E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95287.33 | 0.423879E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.350882E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81366.15 | 0.219838E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16525144.73 | 0.130946E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47709792.12 | 0.791803E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38190207.61 | 0.900719E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1615264.82 | 0.128886E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.262265E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348918E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.667111E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104217E+09 | 0.399666E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.791803E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47709792.12 | 0.667111E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3036.42 | 12-JAN-05:53 |
February | 2010.79 | 01-FEB-10:09 | 1591.22 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3125.98 | 13-FEB-05:52 |
March | 2010.79 | 01-MAR-10:09 | 1389.41 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 15-MAR-14:00 | 1906.25 | 02-MAR-01:00 |
April | 2010.79 | 03-APR-09:09 | 1250.95 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1852.81 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 57.78 | 14-MAY-15:00 | 1045.29 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 148.06 | 17-JUN-17:03 | 915.36 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.88 | 21-JUL-02:40 | 670.26 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 278.79 | 13-AUG-12:52 | 423.77 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1352.79 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 59.98 | 16-SEP-17:03 | 787.61 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1710.62 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1031.74 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1821.59 | 17-NOV-02:00 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2967.35 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 423.77 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 278.79 | 3125.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2024.29 | 12-JAN-05:59 |
February | 1295.83 | 01-FEB-10:09 | 1032.51 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2080.05 | 13-FEB-05:52 |
March | 1295.83 | 01-MAR-10:09 | 828.03 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 15-MAR-14:00 | 1268.54 | 02-MAR-01:00 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1199.01 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 | 14-MAY-14:50 | 735.20 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 112.65 | 17-JUN-17:03 | 608.12 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 193.59 | 21-JUL-03:00 | 428.48 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 217.16 | 13-AUG-13:10 | 266.91 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 801.65 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.00 | 16-SEP-17:03 | 511.76 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1044.87 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 698.37 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1176.54 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1936.09 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 266.91 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 217.16 | 2080.05 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 3036.43 | 12-JAN-05:57 |
February | 2010.83 | 01-FEB-10:09 | 1567.10 | 01-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 3109.52 | 13-FEB-05:52 |
March | 2010.83 | 01-MAR-10:09 | 1362.94 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 24.08 | 15-MAR-14:00 | 1977.88 | 02-MAR-01:00 |
April | 2010.83 | 03-APR-09:09 | 1243.55 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1753.82 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.67 | 10-MAY-14:00 | 1084.48 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 151.97 | 17-JUN-17:03 | 917.15 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 232.27 | 21-JUL-03:00 | 664.52 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 267.97 | 13-AUG-13:05 | 420.33 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1332.67 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.60 | 16-SEP-13:00 | 761.14 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1580.32 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1010.38 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1780.30 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2930.12 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.33 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 267.97 | 3109.52 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 2039.18 | 12-JAN-01:53 |
February | 1295.83 | 01-FEB-10:09 | 1022.53 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 2095.25 | 13-FEB-05:52 |
March | 1295.83 | 01-MAR-10:09 | 928.16 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.22 | 15-MAR-14:00 | 1424.99 | 02-MAR-01:00 |
April | 1295.83 | 03-APR-09:09 | 846.04 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1360.08 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.45 | 10-MAY-14:00 | 764.17 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 72.48 | 12-JUN-13:00 | 673.41 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 132.47 | 21-JUL-02:30 | 523.18 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.12 | 13-AUG-13:08 | 338.45 | 27-AUG-19:00 |
September | 1295.83 | 01-SEP-09:09 | 905.11 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.40 | 16-SEP-13:00 | 555.60 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1102.96 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 746.27 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1332.97 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2097.39 | 09-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.45 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 186.12 | 2097.39 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6732.09 | 12-JAN-05:40 |
February | 2010.79 | 01-FEB-10:09 | 1595.99 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6566.52 | 13-FEB-06:00 |
March | 2010.79 | 01-MAR-10:09 | 1400.28 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 54.11 | 15-MAR-14:00 | 4090.08 | 02-MAR-05:10 |
April | 2010.79 | 03-APR-09:09 | 1265.74 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3510.15 | 16-APR-02:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 233.51 | 14-MAY-15:00 | 2066.70 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 362.88 | 17-JUN-17:03 | 1959.42 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 495.68 | 21-JUL-03:00 | 1423.10 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 725.70 | 13-AUG-13:00 | 924.26 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1364.57 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 153.82 | 16-SEP-17:03 | 1595.27 | 29-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1712.08 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1990.39 | 08-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3517.82 | 17-NOV-05:57 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6331.97 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 924.26 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 725.70 | 6732.09 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1127.77 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4766.69 | 12-JAN-06:00 |
February | 1239.33 | 01-FEB-08:09 | 1033.28 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4952.57 | 13-FEB-06:00 |
March | 1239.33 | 01-MAR-08:09 | 832.81 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.06 | 15-MAR-14:00 | 2727.05 | 02-MAR-05:10 |
April | 1239.33 | 03-APR-07:10 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2346.04 | 16-APR-06:53 |
May | 1239.33 | 01-MAY-07:10 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 152.64 | 14-MAY-15:00 | 1560.88 | 29-MAY-14:00 |
June | 1239.33 | 01-JUN-07:10 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.84 | 17-JUN-17:03 | 1330.38 | 13-JUN-03:00 |
July | 1239.33 | 03-JUL-07:10 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.92 | 21-JUL-03:00 | 949.81 | 06-JUL-02:00 |
August | 1239.33 | 01-AUG-07:10 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 476.55 | 13-AUG-13:20 | 598.28 | 30-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 806.87 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.41 | 16-SEP-17:03 | 1042.76 | 29-SEP-04:00 |
October | 1239.33 | 02-OCT-07:10 | 1046.16 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1384.67 | 08-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 1127.77 | 06-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2345.18 | 17-NOV-06:00 |
December | 1239.33 | 01-DEC-08:09 | 1127.77 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4197.97 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 598.28 | |||||
Maximum of Months | 1239.33 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 476.55 | 4952.57 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 7149.22 | 12-JAN-06:00 |
February | 2010.83 | 01-FEB-10:09 | 1573.04 | 01-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7068.99 | 13-FEB-06:00 |
March | 2010.83 | 01-MAR-10:09 | 1374.97 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 53.76 | 15-MAR-14:00 | 4090.60 | 02-MAR-05:07 |
April | 2010.83 | 03-APR-09:09 | 1258.60 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3515.44 | 16-APR-02:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 41.51 | 10-MAY-14:00 | 2286.66 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 367.10 | 17-JUN-17:03 | 1987.27 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 494.13 | 21-JUL-03:00 | 1434.14 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 578.38 | 13-AUG-13:00 | 926.42 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1345.25 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.11 | 16-SEP-13:00 | 1608.68 | 29-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1653.72 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2121.93 | 08-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3586.00 | 17-NOV-02:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6401.15 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 926.42 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 578.38 | 7149.22 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 4766.66 | 12-JAN-05:57 |
February | 1295.83 | 01-FEB-10:09 | 1023.37 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 4952.54 | 13-FEB-05:58 |
March | 1295.83 | 01-MAR-10:09 | 929.71 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 36.07 | 15-MAR-14:00 | 2762.74 | 25-MAR-17:10 |
April | 1295.83 | 03-APR-09:09 | 848.18 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2385.03 | 16-APR-02:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.67 | 10-MAY-14:00 | 1632.92 | 06-MAY-17:05 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 166.55 | 12-JUN-13:00 | 1358.64 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 356.69 | 21-JUL-03:00 | 1003.41 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 482.36 | 13-AUG-13:20 | 692.99 | 27-AUG-16:40 |
September | 1295.83 | 01-SEP-09:09 | 906.82 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 73.40 | 16-SEP-13:00 | 1060.06 | 29-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1103.52 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1374.67 | 08-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2351.72 | 17-NOV-02:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4284.94 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 692.99 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 482.36 | 4952.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8275.04 | 12-JAN-05:50 |
February | 2010.79 | 01-FEB-10:09 | 1595.86 | 01-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 7880.60 | 13-FEB-06:00 |
March | 2010.79 | 01-MAR-10:09 | 1400.02 | 17-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.50 | 15-MAR-14:00 | 4817.56 | 02-MAR-05:20 |
April | 2010.79 | 03-APR-09:09 | 1265.32 | 12-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4144.61 | 04-APR-21:03 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 282.65 | 14-MAY-15:00 | 2404.34 | 29-MAY-14:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 423.12 | 17-JUN-17:03 | 2371.15 | 13-JUN-03:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 597.83 | 21-JUL-03:00 | 1687.08 | 06-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 888.77 | 13-AUG-13:00 | 1105.20 | 30-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1364.25 | 26-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 168.17 | 16-SEP-17:03 | 1742.88 | 29-SEP-04:10 |
October | 2010.79 | 02-OCT-09:09 | 1712.12 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2298.00 | 30-OCT-04:51 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:00 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4399.12 | 17-NOV-05:57 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:40 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7565.89 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1105.20 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 888.77 | 8275.04 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5906.61 | 12-JAN-05:46 |
February | 1295.83 | 01-FEB-10:09 | 1033.20 | 01-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 5852.24 | 13-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 832.72 | 17-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 15-MAR-14:00 | 3353.74 | 02-MAR-05:17 |
April | 1295.83 | 03-APR-09:09 | 692.79 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2762.24 | 04-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.84 | 14-MAY-15:00 | 1829.89 | 29-MAY-14:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 298.87 | 17-JUN-17:03 | 1614.38 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.40 | 21-JUL-03:00 | 1128.30 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 559.62 | 13-AUG-13:00 | 721.62 | 30-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 806.75 | 26-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 105.25 | 16-SEP-17:03 | 1160.99 | 29-SEP-04:10 |
October | 1295.83 | 02-OCT-09:09 | 1046.33 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1533.24 | 30-OCT-04:51 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:00 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2932.90 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5028.26 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.62 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 559.62 | 5906.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 8649.02 | 12-JAN-05:50 |
February | 2010.83 | 01-FEB-10:09 | 1572.91 | 01-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8319.42 | 13-FEB-06:00 |
March | 2010.83 | 01-MAR-10:09 | 1374.71 | 17-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 63.42 | 15-MAR-14:00 | 5030.48 | 02-MAR-05:18 |
April | 2010.83 | 03-APR-09:09 | 1258.18 | 12-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4145.68 | 04-APR-21:03 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 48.71 | 10-MAY-14:00 | 2669.47 | 29-MAY-14:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 421.87 | 17-JUN-17:03 | 2406.68 | 13-JUN-03:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 585.05 | 21-JUL-03:00 | 1701.12 | 06-JUL-02:00 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 764.43 | 13-AUG-12:54 | 1112.78 | 30-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1344.93 | 26-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 131.89 | 16-SEP-13:00 | 1743.45 | 29-SEP-04:10 |
October | 2010.83 | 02-OCT-09:09 | 1653.88 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2305.11 | 30-OCT-04:51 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:00 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4399.06 | 17-NOV-06:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:40 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7645.53 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1112.78 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 764.43 | 8649.02 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 5906.70 | 12-JAN-05:44 |
February | 1295.83 | 01-FEB-10:09 | 1023.27 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6086.51 | 13-FEB-06:00 |
March | 1295.83 | 01-MAR-10:09 | 929.54 | 17-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 15-MAR-14:00 | 3353.64 | 02-MAR-05:15 |
April | 1295.83 | 03-APR-09:09 | 847.92 | 12-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2768.20 | 04-APR-21:03 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 32.48 | 10-MAY-14:00 | 2034.51 | 06-MAY-17:10 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 202.53 | 12-JUN-13:00 | 1645.20 | 13-JUN-03:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 428.14 | 21-JUL-03:00 | 1195.31 | 06-JUL-02:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 587.93 | 13-AUG-13:00 | 885.93 | 27-AUG-16:30 |
September | 1295.83 | 01-SEP-09:09 | 906.62 | 26-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 87.92 | 16-SEP-13:00 | 1162.07 | 29-SEP-04:10 |
October | 1295.83 | 02-OCT-09:09 | 1103.55 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1542.19 | 30-OCT-04:51 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:00 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2932.75 | 17-NOV-06:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:40 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5140.62 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 885.93 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 587.93 | 6086.51 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 6408.84 | 12-JAN-01:53 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 6452.47 | 13-FEB-05:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.67 | 15-MAR-14:00 | 4207.89 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3991.12 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.87 | 14-MAY-15:00 | 1944.10 | 29-MAY-14:10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.72 | 17-JUN-17:03 | 1895.91 | 13-JUN-03:05 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 432.40 | 21-JUL-02:42 | 1373.27 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.59 | 13-AUG-12:52 | 868.16 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.18 | 16-SEP-17:03 | 1697.41 | 29-SEP-04:07 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2172.79 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3888.27 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 6409.92 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.16 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.59 | 6452.47 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10625.65 | 12-JAN-06:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 10501.48 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.03 | 15-MAR-14:00 | 6760.15 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6577.58 | 16-APR-02:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.34 | 14-MAY-15:00 | 3159.94 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.26 | 17-JUN-17:03 | 3269.17 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.37 | 21-JUL-03:00 | 2388.74 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.28 | 13-AUG-13:00 | 1539.38 | 30-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.32 | 16-SEP-17:03 | 2910.93 | 29-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3638.37 | 08-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6406.47 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 10707.86 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1539.38 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1225.28 | 10707.86 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 11529.76 | 12-JAN-05:50 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 11354.55 | 13-FEB-06:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 15-MAR-14:00 | 6775.68 | 02-MAR-01:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6362.36 | 16-APR-04:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.20 | 10-MAY-15:00 | 4205.96 | 29-MAY-14:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.20 | 17-JUN-17:03 | 3701.55 | 13-JUN-03:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 730.26 | 21-JUL-03:00 | 2611.69 | 06-JUL-02:00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 913.54 | 13-AUG-13:00 | 1709.61 | 30-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.45 | 16-SEP-13:00 | 2836.09 | 29-SEP-04:20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3301.28 | 07-OCT-02:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6417.96 | 17-NOV-02:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 12007.74 | 09-DEC-18:03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1709.61 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 913.54 | 12007.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102836.97 | 02-JAN-04:01 | 0.00 | 8622.27 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 99635.20 | 21-FEB-04:01 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 100476.84 | 20-MAR-03:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 102920.41 | 10-APR-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 101165.27 | 01-MAY-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 93830.78 | 13-JUN-05:03 | 7180.90 | 6897.82 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 97312.92 | 03-JUL-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 94252.02 | 21-AUG-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 106989.00 | 05-SEP-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 104809.39 | 16-OCT-03:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 103984.87 | 06-NOV-04:03 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 104022.71 | 26-DEC-04:01 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 93830.78 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 106989.00 | 7180.90 | 8622.27 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 75464.91 | 18-JAN-06:01 | 11285.67 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 77046.47 | 23-FEB-06:01 | 11285.67 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82895.15 | 13-MAR-04:01 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86322.73 | 10-APR-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 90267.44 | 30-MAY-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85286.63 | 13-JUN-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 85755.54 | 06-JUL-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85261.91 | 31-AUG-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 90070.57 | 18-SEP-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 86156.35 | 23-OCT-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86896.23 | 13-NOV-04:01 | 0.00 | 5420.38 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83010.85 | 18-DEC-05:02 | 0.00 | 15486.81 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 75464.91 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 90267.44 | 11285.67 | 15486.81 | 80571.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 27516.57 | 20-JAN-07:40 | 6448.95 | 9291.71 | 16114.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 28583.89 | 28-FEB-17:05 | 9673.43 | 15486.05 | 20142.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 76589.03 | 16-MAR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 73363.29 | 27-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76165.95 | 19-MAY-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77791.43 | 22-JUN-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 77872.39 | 18-JUL-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79140.17 | 21-AUG-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 81649.34 | 18-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 76058.24 | 06-OCT-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68528.93 | 01-NOV-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 21756.61 | 01-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 21756.61 | 0.00 | 3871.70 | 16114.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 81649.34 | 15316.26 | 15486.05 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16126.52 | 11-JAN-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16502.57 | 28-FEB-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 74990.77 | 16-MAR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 35639.94 | 21-APR-16:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 73134.15 | 17-MAY-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 79209.00 | 19-JUN-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78562.20 | 05-JUL-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79853.48 | 07-AUG-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79727.25 | 18-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 49966.66 | 12-OCT-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21183.41 | 01-NOV-16:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17037.01 | 01-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 16126.52 | 0.00 | 3097.36 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79853.48 | 15316.26 | 13937.56 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2287.80 | 17-JAN-06:02 | 1214.60 | 1166.71 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.34 |
February | 2279.74 | 23-FEB-06:01 | 1417.03 | 1361.17 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.36 |
March | 6900.83 | 15-MAR-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 24.33 | 0.00 |
April | 5896.97 | 07-APR-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.69 |
May | 8807.06 | 30-MAY-05:03 | 809.73 | 702.20 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.97 |
June | 11735.53 | 21-JUN-05:02 | 1012.16 | 597.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.55 |
July | 12129.80 | 21-JUL-04:12 | 0.00 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 | 0.00 |
August | 11274.63 | 21-AUG-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.91 |
September | 9055.30 | 14-SEP-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.74 |
October | 5262.64 | 12-OCT-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.67 |
November | 4186.73 | 27-NOV-12:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 172.12 |
December | 2619.11 | 14-DEC-06:03 | 1214.60 | 1166.71 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2279.74 | 0.00 | 597.26 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12129.80 | 2010.79 | 1361.17 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 66.42 | 273.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2018.03 | 17-JAN-06:02 | 782.73 | 751.88 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.78 |
February | 3419.20 | 28-FEB-09:35 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.62 |
March | 6492.91 | 21-MAR-09:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 107.60 |
April | 10397.21 | 23-APR-09:13 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.55 |
May | 10849.48 | 31-MAY-08:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.81 |
June | 18971.05 | 11-JUN-09:12 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.03 |
July | 20018.34 | 04-JUL-08:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.97 |
August | 18210.95 | 06-AUG-08:32 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.26 |
September | 18308.40 | 04-SEP-09:43 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.52 |
October | 8394.49 | 11-OCT-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 |
November | 4584.22 | 06-NOV-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.10 |
December | 2197.73 | 05-DEC-06:03 | 913.19 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2018.03 | 195.68 | 115.47 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.27 | |
Maximum of Months | 20018.34 | 2478.65 | 1385.57 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 250.55 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8783.56 | 12-JAN-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 725.57 |
February | 11486.83 | 28-FEB-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 293.49 |
March | 15453.38 | 15-MAR-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 0.00 |
April | 13207.42 | 24-APR-12:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.70 |
May | 16538.94 | 14-MAY-14:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.40 |
June | 16632.39 | 25-JUN-13:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 31.15 |
July | 22585.92 | 30-JUL-12:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.25 |
August | 22139.13 | 27-AUG-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.79 |
September | 22618.50 | 04-SEP-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 367.43 |
October | 17654.14 | 11-OCT-12:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.25 |
November | 13368.76 | 03-NOV-12:20 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.77 |
December | 10046.85 | 04-DEC-11:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 388.21 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8783.56 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22618.50 | 2010.83 | 1075.05 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 19.34 | 725.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2870.05 | 17-JAN-06:02 | 782.73 | 751.88 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.56 |
February | 6853.82 | 28-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.95 |
March | 10497.57 | 13-MAR-04:01 | 0.00 | 877.19 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.48 |
April | 18901.22 | 30-APR-15:32 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.11 |
May | 23153.92 | 07-MAY-17:52 | 0.00 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 294.70 |
June | 25673.00 | 11-JUN-17:51 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.30 |
July | 24577.36 | 02-JUL-16:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.99 |
August | 24500.26 | 06-AUG-16:31 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 |
September | 18856.88 | 04-SEP-16:22 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.99 |
October | 11295.94 | 11-OCT-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.63 |
November | 10349.59 | 16-NOV-06:02 | 652.28 | 626.56 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 103.01 |
December | 6599.37 | 14-DEC-06:02 | 782.73 | 751.88 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2870.05 | 0.00 | 192.45 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.39 | |
Maximum of Months | 25673.00 | 1239.33 | 877.19 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.48 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1428.25 | 14-JAN-17:03 | 404.87 | 388.90 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.42 |
February | 1427.57 | 18-FEB-17:03 | 404.87 | 314.60 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 574.94 |
March | 5004.17 | 15-MAR-14:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 35.66 | 0.00 |
April | 3136.18 | 21-APR-15:10 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.04 |
May | 6003.64 | 23-MAY-14:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.98 |
June | 10532.35 | 19-JUN-05:03 | 809.73 | 716.86 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.36 |
July | 11224.64 | 21-JUL-05:03 | 607.30 | 553.84 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 32.09 | 0.00 |
August | 10608.67 | 11-AUG-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.57 |
September | 8000.26 | 15-SEP-05:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.86 |
October | 3515.67 | 12-OCT-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.57 |
November | 2321.77 | 07-NOV-11:20 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.42 |
December | 1706.73 | 01-DEC-13:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 573.38 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1427.57 | 404.87 | 314.60 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11224.64 | 1923.11 | 1075.02 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 35.66 | 574.94 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1538.59 | 17-JAN-06:05 | 782.73 | 751.88 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.65 |
February | 2446.19 | 28-FEB-10:05 | 0.00 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.37 |
March | 4554.35 | 14-MAR-10:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.96 |
April | 8890.25 | 24-APR-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 186.43 |
May | 10963.86 | 31-MAY-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.27 |
June | 19940.54 | 11-JUN-09:52 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.97 |
July | 21061.36 | 04-JUL-08:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 469.66 |
August | 13003.10 | 20-AUG-09:32 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 409.82 |
September | 16733.94 | 04-SEP-09:32 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 387.13 |
October | 6638.40 | 11-OCT-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.56 |
November | 2279.12 | 03-NOV-10:20 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.24 |
December | 1660.02 | 04-DEC-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1538.59 | 0.00 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.96 | |
Maximum of Months | 21061.36 | 1239.33 | 1385.57 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9699.93 | 12-JAN-14:05 | 4021.67 | 2150.10 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1549.57 |
February | 12585.99 | 28-FEB-13:05 | 3846.30 | 2150.10 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 667.30 |
March | 14619.87 | 15-MAR-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 42.17 | 0.00 |
April | 12413.76 | 24-APR-13:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 215.92 |
May | 16629.70 | 14-MAY-13:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.29 |
June | 15153.01 | 25-JUN-13:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.16 |
July | 21963.32 | 30-JUL-12:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.60 |
August | 22151.20 | 13-AUG-13:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 448.36 | 0.00 |
September | 23195.65 | 10-SEP-13:12 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.79 |
October | 17696.30 | 31-OCT-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.35 |
November | 13249.33 | 03-NOV-12:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.05 |
December | 6470.11 | 16-DEC-13:30 | 202.44 | 179.18 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6470.11 | 202.44 | 179.18 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23195.65 | 4021.67 | 2150.10 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 448.36 | 1549.57 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1814.33 | 12-JAN-16:10 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 917.79 |
February | 4011.33 | 28-FEB-17:05 | 782.73 | 769.76 | 1629.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 389.79 |
March | 5605.51 | 15-MAR-14:20 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 29.61 | 0.00 |
April | 9390.22 | 24-APR-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.96 |
May | 21055.26 | 07-MAY-16:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 726.27 |
June | 22633.76 | 11-JUN-17:51 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 217.84 |
July | 22045.50 | 30-JUL-17:21 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 304.77 |
August | 20326.15 | 06-AUG-16:42 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 | 0.00 |
September | 20757.54 | 04-SEP-17:32 | 0.00 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.35 |
October | 8899.50 | 11-OCT-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 |
November | 3018.22 | 15-NOV-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.06 |
December | 1968.96 | 04-DEC-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 377.66 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1814.33 | 0.00 | 192.45 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22633.76 | 1239.33 | 769.76 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 56.01 | 917.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1611.32 | 14-JAN-17:03 | 404.87 | 388.90 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.57 |
February | 1612.47 | 18-FEB-17:03 | 404.87 | 314.65 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.87 |
March | 5453.01 | 15-MAR-14:50 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 36.56 | 0.00 |
April | 3158.16 | 20-APR-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.35 |
May | 6083.53 | 23-MAY-14:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 |
June | 11900.15 | 27-JUN-05:03 | 809.73 | 551.04 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.36 |
July | 18382.02 | 16-JUL-16:41 | 809.73 | 477.81 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 30.25 | 0.00 |
August | 11383.31 | 13-AUG-16:12 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 311.59 | 0.00 |
September | 6674.20 | 15-SEP-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 21.70 | 0.00 |
October | 3143.94 | 12-OCT-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 273.94 |
November | 2168.98 | 16-NOV-17:00 | 1923.11 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.63 |
December | 1618.55 | 02-DEC-17:02 | 506.08 | 486.13 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1188.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1611.32 | 404.87 | 314.65 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18382.02 | 2010.79 | 1750.00 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 311.59 | 1188.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1375.84 | 14-JAN-17:03 | 260.91 | 250.63 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.50 |
February | 1734.29 | 28-FEB-10:15 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.04 |
March | 4450.41 | 15-MAR-14:00 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 0.00 |
April | 7029.84 | 24-APR-09:30 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.62 |
May | 10297.30 | 31-MAY-09:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.27 |
June | 12173.54 | 11-JUN-09:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.66 |
July | 21432.02 | 16-JUL-09:22 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 59.07 |
August | 13402.31 | 06-AUG-13:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.69 |
September | 9691.96 | 04-SEP-09:43 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.71 |
October | 5243.78 | 11-OCT-09:40 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.33 |
November | 1894.32 | 03-NOV-10:00 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 380.97 |
December | 1567.44 | 21-DEC-06:04 | 913.19 | 877.19 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209.68 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1375.84 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21432.02 | 2591.66 | 1385.57 | 4563.83 | 0.00 | 0.00 | 0.00 | 0.00 | 42.33 | 470.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4618.12 | 12-JAN-14:00 | 3846.30 | 2150.10 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1948.77 |
February | 9974.38 | 28-FEB-14:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 883.92 |
March | 15088.00 | 15-MAR-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 48.39 | 0.00 |
April | 11499.32 | 24-APR-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 247.15 |
May | 11087.06 | 26-MAY-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 66.86 |
June | 16842.36 | 25-JUN-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.90 |
July | 23975.54 | 16-JUL-11:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 80.18 | 0.00 |
August | 23993.24 | 13-AUG-14:51 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 525.54 | 0.00 |
September | 24798.63 | 10-SEP-14:02 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.06 |
October | 17764.00 | 11-OCT-12:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.63 |
November | 10645.67 | 03-NOV-13:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.61 |
December | 4397.13 | 16-DEC-13:30 | 202.44 | 179.18 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 362.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4397.13 | 202.44 | 179.18 | 885.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24798.63 | 3846.30 | 2150.10 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 525.54 | 1948.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1774.34 | 18-JAN-06:04 | 913.19 | 877.19 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 510.50 |
February | 2548.81 | 28-FEB-16:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.40 |
March | 5925.31 | 15-MAR-14:20 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 | 0.00 |
April | 8969.03 | 20-APR-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.87 |
May | 18587.48 | 07-MAY-16:12 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.19 |
June | 24011.14 | 25-JUN-17:01 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.58 |
July | 24499.30 | 16-JUL-16:41 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.60 |
August | 23315.80 | 27-AUG-16:32 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.76 |
September | 12564.06 | 10-SEP-16:02 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.78 |
October | 8738.35 | 11-OCT-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.96 |
November | 2482.78 | 15-NOV-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.81 |
December | 1856.82 | 04-DEC-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.03 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1774.34 | 0.00 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24499.30 | 1239.33 | 877.19 | 4563.80 | 0.00 | 0.00 | 0.00 | 0.00 | 34.56 | 813.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3936.27 | 21-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 680.80 |
February | 3628.82 | 25-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.42 |
March | 4431.38 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.13 | 0.00 |
April | 6088.50 | 10-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 248.23 |
May | 7771.96 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.81 |
June | 8125.25 | 05-JUN-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 160.67 |
July | 11463.22 | 17-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.86 |
August | 11167.05 | 14-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.62 |
September | 7204.41 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 117.10 |
October | 6028.84 | 23-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.78 |
November | 4124.87 | 06-NOV-06:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333.66 |
December | 2398.99 | 16-DEC-06:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2398.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 11463.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.13 | 789.42 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5038.62 | 24-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7530.12 |
February | 5294.88 | 12-FEB-22:32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6680.78 |
March | 6211.80 | 06-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3127.55 |
April | 4834.27 | 17-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4183.37 | 30-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.52 |
June | 5829.46 | 27-JUN-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.13 | 0.00 |
July | 7573.73 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.56 |
August | 6708.26 | 07-AUG-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.63 |
September | 5530.64 | 18-SEP-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.24 |
October | 4563.08 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 424.57 |
November | 5537.24 | 24-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1663.98 |
December | 5548.76 | 07-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4837.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4183.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7573.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.13 | 7530.12 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2145.61 |
February | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3095.96 |
March | 10078.57 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.22 | 0.00 |
April | 7701.06 | 21-APR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.80 |
May | 12769.47 | 31-MAY-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.57 |
June | 17858.60 | 12-JUN-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.46 | 0.00 |
July | 18659.18 | 21-JUL-13:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.99 | 0.00 |
August | 17244.96 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.26 | 0.00 |
September | 12876.33 | 21-SEP-15:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.71 | 0.00 |
October | 6463.26 | 11-OCT-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.14 |
November | 1284.47 | 04-NOV-16:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.34 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2630.41 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18659.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.46 | 3095.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1785.74 | 12-JAN-16:40 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3983.69 | 28-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6983.36 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7971.44 | 02-APR-17:45 | 0.00 | 90.03 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3472.83 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5348.95 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7240.91 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8060.16 | 04-AUG-18:30 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3197.54 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5145.21 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5765.29 | 24-NOV-16:10 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7621.99 | 04-DEC-16:10 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1785.74 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8060.16 | 222.14 | 405.10 | 31177.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1239.92 | 12-JAN-16:40 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3328.54 | 28-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6070.57 | 31-MAR-23:50 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7480.56 | 24-APR-18:00 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3258.05 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5135.20 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7001.52 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7691.69 | 02-AUG-18:40 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2619.24 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4383.83 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5269.59 | 15-NOV-16:30 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6712.94 | 04-DEC-16:20 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1239.92 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7691.69 | 222.14 | 405.10 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 975.05 | 12-JAN-16:30 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3338.56 | 28-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5593.19 | 31-MAR-23:20 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7468.01 | 24-APR-18:00 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3161.16 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5066.35 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6996.17 | 31-JUL-23:57 | 0.00 | 67.52 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7746.17 | 02-AUG-18:40 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2166.18 | 04-SEP-17:34 | 0.00 | 112.53 | 9743.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3935.87 | 31-OCT-23:20 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5102.87 | 15-NOV-16:30 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6336.05 | 04-DEC-16:20 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 975.05 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7746.17 | 222.14 | 405.10 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 90181.48 | 19-JAN-17:00 | 4808.68 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 181684.19 | 23-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357824.67 | 31-MAR-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 366581.01 | 24-APR-16:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175514.38 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267569.97 | 30-JUN-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359769.91 | 31-JUL-23:57 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369383.69 | 04-AUG-21:02 | 1518.53 | 2917.33 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175249.67 | 30-SEP-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267942.39 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275758.38 | 06-NOV-17:00 | 4808.68 | 4375.82 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366355.85 | 15-DEC-17:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 90181.48 | 0.00 | 243.11 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 369383.69 | 4808.68 | 4375.82 | 2277795.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.154179E+13 | 978340.73 | 04-JAN-16:49 | 0.603622E+12 | 1686398.24 | 02-JAN-05:10 |
February | 0.174241E+13 | 1095308.84 | 02-FEB-08:09 | 0.524763E+12 | 1617465.87 | 21-FEB-07:10 |
March | 0.238483E+13 | 1458701.98 | 15-MAR-15:20 | 0.240492E+12 | 1117858.16 | 06-MAR-06:10 |
April | 0.266181E+13 | 1488423.68 | 07-APR-15:09 | 0.106398E+12 | 732074.28 | 17-APR-06:10 |
May | 0.167407E+13 | 1161092.52 | 26-MAY-15:00 | 0.655561E+11 | 170919.91 | 04-MAY-06:10 |
June | 0.225272E+13 | 1589125.92 | 27-JUN-07:40 | 0.606694E+11 | 79438.86 | 01-JUN-11:30 |
July | 0.284431E+13 | 1806180.43 | 05-JUL-15:00 | 0.569138E+11 | 77165.50 | 03-JUL-11:00 |
August | 0.323928E+13 | 1927706.14 | 07-AUG-15:30 | 0.599135E+11 | 75904.44 | 01-AUG-11:20 |
September | 0.172443E+13 | 1357060.21 | 21-SEP-15:00 | 0.569808E+11 | 129500.45 | 30-SEP-06:10 |
October | 0.199481E+13 | 1274964.52 | 11-OCT-15:50 | 0.889595E+11 | 582456.95 | 30-OCT-06:10 |
November | 0.228571E+13 | 1375664.39 | 16-NOV-16:00 | 0.180196E+12 | 743044.92 | 24-NOV-07:10 |
December | 0.269903E+13 | 1413053.77 | 12-DEC-16:49 | 0.509617E+12 | 1680757.07 | 26-DEC-07:10 |
Annual Sum or Average | 0.270452E+14 | 0.255408E+13 | ||||
Minimum of Months | 0.154179E+13 | 978340.73 | 0.569138E+11 | 75904.44 | ||
Maximum of Months | 0.323928E+13 | 1927706.14 | 0.603622E+12 | 1686398.24 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [J] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.231799E+12 | 0.498058E+11 | 0.811612E+12 | 0.162550E+12 | 0.167897E+12 | 0.171060E+11 | 0.00 | 0.818804E+11 | 0.791492E+10 | 0.425902E+10 | 0.696183E+10 | 0.00 | 0.00 |
February | 0.208758E+12 | 0.407215E+11 | 0.102011E+13 | 0.146826E+12 | 0.152048E+12 | 0.157947E+11 | 0.00 | 0.135887E+12 | 0.120888E+11 | 0.381573E+10 | 0.635951E+10 | 0.00 | 0.00 |
March | 0.246184E+12 | 0.391995E+11 | 0.146267E+13 | 0.162740E+12 | 0.170876E+12 | 0.217047E+11 | 0.00 | 0.230690E+12 | 0.422265E+11 | 0.287048E+10 | 0.567214E+10 | 0.00 | 0.00 |
April | 0.219080E+12 | 0.319891E+11 | 0.170311E+13 | 0.157288E+12 | 0.168196E+12 | 0.196718E+11 | 0.00 | 0.281612E+12 | 0.771850E+11 | 0.113694E+10 | 0.254066E+10 | 0.00 | 0.00 |
May | 0.235691E+12 | 0.281218E+11 | 0.820521E+12 | 0.162644E+12 | 0.192010E+12 | 0.370698E+11 | 0.00 | 0.130387E+12 | 0.667440E+11 | 0.631104E+09 | 0.245870E+09 | 0.00 | 0.00 |
June | 0.234165E+12 | 0.250642E+11 | 0.110677E+13 | 0.157466E+12 | 0.222745E+12 | 0.717260E+11 | 0.00 | 0.302613E+12 | 0.130984E+12 | 76942977.39 | 0.110810E+10 | 0.00 | 0.00 |
July | 0.219391E+12 | 0.265524E+11 | 0.143888E+13 | 0.162465E+12 | 0.242939E+12 | 0.955535E+11 | 0.00 | 0.488588E+12 | 0.167074E+12 | 0.00 | 0.286624E+10 | 0.00 | 0.00 |
August | 0.244662E+12 | 0.307144E+11 | 0.177780E+13 | 0.162739E+12 | 0.243905E+12 | 0.913753E+11 | 0.00 | 0.529969E+12 | 0.155953E+12 | 464853.66 | 0.216736E+10 | 0.00 | 0.00 |
September | 0.219639E+12 | 0.353741E+11 | 0.784732E+12 | 0.157287E+12 | 0.197463E+12 | 0.541536E+11 | 0.00 | 0.177135E+12 | 0.982898E+11 | 0.00 | 0.355333E+09 | 0.00 | 0.00 |
October | 0.229520E+12 | 0.426522E+11 | 0.112899E+13 | 0.162550E+12 | 0.172850E+12 | 0.237694E+11 | 0.00 | 0.173886E+12 | 0.583483E+11 | 0.499133E+09 | 0.174411E+10 | 0.00 | 0.00 |
November | 0.229499E+12 | 0.465671E+11 | 0.140306E+13 | 0.157362E+12 | 0.159566E+12 | 0.170503E+11 | 0.00 | 0.217952E+12 | 0.489634E+11 | 0.133187E+10 | 0.435362E+10 | 0.00 | 0.00 |
December | 0.225376E+12 | 0.512275E+11 | 0.175516E+13 | 0.162467E+12 | 0.166303E+12 | 0.176823E+11 | 0.00 | 0.277654E+12 | 0.329838E+11 | 0.333130E+10 | 0.684507E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.274376E+13 | 0.447990E+12 | 0.152134E+14 | 0.191438E+13 | 0.225680E+13 | 0.482657E+12 | 0.00 | 0.302825E+13 | 0.898756E+12 | 0.179530E+11 | 0.412198E+11 | 0.00 | 0.00 |
Minimum of Months | 0.208758E+12 | 0.250642E+11 | 0.784732E+12 | 0.146826E+12 | 0.152048E+12 | 0.157947E+11 | 0.00 | 0.818804E+11 | 0.791492E+10 | 0.00 | 0.245870E+09 | 0.00 | 0.00 |
Maximum of Months | 0.246184E+12 | 0.512275E+11 | 0.177780E+13 | 0.162740E+12 | 0.243905E+12 | 0.955535E+11 | 0.00 | 0.529969E+12 | 0.167074E+12 | 0.425902E+10 | 0.696183E+10 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.535901E+12 | 0.00 | 0.677218E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.462631E+12 | 0.00 | 0.621321E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.169215E+12 | 0.00 | 0.712772E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.427347E+11 | 0.00 | 0.636629E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.996297E+09 | 0.00 | 0.645598E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 22492663.39 | 0.00 | 0.606469E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 6069.51 | 0.00 | 0.569137E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.599135E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.910585E+09 | 0.00 | 0.560702E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.290233E+11 | 0.00 | 0.599362E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.118853E+12 | 0.00 | 0.613431E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.445202E+12 | 0.00 | 0.644157E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.180549E+13 | 0.00 | 0.748593E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.560702E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.535901E+12 | 0.00 | 0.712772E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 261074.09 | 02-JAN-16:49 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117201.33 | 11-JAN-08:20 | 100668.52 | 02-JAN-06:19 | 38818.87 | 02-JAN-07:19 | 0.00 | 01-JAN-00:10 |
February | 254425.27 | 01-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117200.75 | 01-FEB-08:20 | 94997.45 | 06-FEB-06:10 | 38701.49 | 07-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 246430.45 | 17-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117196.39 | 17-MAR-07:19 | 144659.52 | 15-MAR-14:09 | 58756.54 | 15-MAR-12:50 | 0.00 | 01-MAR-00:10 |
April | 240757.75 | 12-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117193.16 | 12-APR-07:19 | 139023.10 | 21-APR-15:20 | 38581.25 | 08-APR-13:39 | 0.00 | 01-APR-00:10 |
May | 234435.00 | 01-MAY-07:10 | 37611.08 | 01-MAY-05:10 | 439129.89 | 01-MAY-07:10 | 117189.56 | 01-MAY-07:19 | 169099.82 | 31-MAY-15:00 | 58372.98 | 10-MAY-12:39 | 0.00 | 01-MAY-00:10 |
June | 234435.00 | 01-JUN-07:10 | 37611.08 | 01-JUN-19:49 | 557421.28 | 01-JUN-07:10 | 117189.56 | 01-JUN-07:19 | 215796.08 | 12-JUN-15:20 | 62213.49 | 27-JUN-07:40 | 0.00 | 01-JUN-00:10 |
July | 234435.00 | 03-JUL-07:10 | 37611.08 | 01-JUL-19:00 | 675712.68 | 03-JUL-07:10 | 117189.56 | 03-JUL-07:19 | 227723.84 | 19-JUL-14:00 | 65090.31 | 05-JUL-15:00 | 0.00 | 01-JUL-00:10 |
August | 234435.00 | 01-AUG-07:10 | 37611.08 | 01-AUG-19:40 | 794004.08 | 01-AUG-07:10 | 117189.56 | 01-AUG-07:19 | 244430.48 | 09-AUG-15:30 | 66139.41 | 01-AUG-14:00 | 0.00 | 01-AUG-00:10 |
September | 245057.14 | 26-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117195.60 | 26-SEP-07:19 | 204225.15 | 21-SEP-15:00 | 66094.22 | 20-SEP-14:09 | 0.00 | 01-SEP-00:10 |
October | 258108.25 | 31-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117203.04 | 31-OCT-07:19 | 146045.22 | 11-OCT-15:00 | 62033.30 | 11-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 261074.09 | 06-NOV-16:00 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117203.81 | 02-NOV-07:19 | 104338.88 | 03-NOV-14:30 | 38472.44 | 16-NOV-13:09 | 0.00 | 01-NOV-00:10 |
December | 261074.09 | 01-DEC-16:40 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117201.85 | 18-DEC-08:20 | 95912.17 | 26-DEC-06:10 | 38796.17 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 234435.00 | 37611.08 | 439129.89 | 117189.56 | 94997.45 | 38472.44 | 0.00 | |||||||
Maximum of Months | 261074.09 | 37611.08 | 794004.08 | 117203.81 | 244430.48 | 66139.41 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY {Maximum} [W] | HEATRECOVERY:ELECTRICITY {TIMESTAMP} | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 39568.72 | 17-JAN-07:40 | 7505.05 | 11-JAN-15:00 | 6182.48 | 23-JAN-20:00 | 5613.48 | 02-JAN-07:10 | 0.00 | 0.00 |
February | 64586.83 | 15-FEB-10:00 | 29181.36 | 22-FEB-17:00 | 5982.56 | 06-FEB-20:00 | 5613.48 | 01-FEB-07:10 | 0.00 | 0.00 |
March | 217447.97 | 15-MAR-15:20 | 68157.28 | 14-MAR-11:39 | 5865.48 | 06-MAR-19:00 | 5613.48 | 01-MAR-07:10 | 0.00 | 0.00 |
April | 201538.61 | 08-APR-13:39 | 50403.31 | 08-APR-13:50 | 4997.37 | 17-APR-19:00 | 5613.48 | 01-APR-06:10 | 0.00 | 0.00 |
May | 143487.10 | 10-MAY-12:39 | 68157.28 | 10-MAY-12:09 | 4634.35 | 08-MAY-18:00 | 5613.48 | 01-MAY-06:10 | 0.00 | 0.00 |
June | 387950.09 | 27-JUN-07:40 | 87066.30 | 01-JUN-15:30 | 2558.71 | 03-JUN-16:00 | 5613.48 | 01-JUN-16:49 | 0.00 | 0.00 |
July | 468125.99 | 05-JUL-15:00 | 87066.30 | 03-JUL-13:09 | 0.00 | 01-JUL-00:10 | 5613.48 | 03-JUL-14:09 | 0.00 | 0.00 |
August | 505944.19 | 14-AUG-10:20 | 87066.30 | 01-AUG-12:00 | 348.56 | 13-AUG-13:30 | 5613.48 | 03-AUG-11:00 | 0.00 | 0.00 |
September | 303140.16 | 15-SEP-10:00 | 87066.30 | 08-SEP-13:20 | 0.00 | 01-SEP-00:10 | 5613.48 | 15-SEP-11:50 | 0.00 | 0.00 |
October | 168316.66 | 11-OCT-14:00 | 52316.27 | 11-OCT-14:09 | 3871.64 | 17-OCT-17:10 | 5613.48 | 03-OCT-06:10 | 0.00 | 0.00 |
November | 153343.85 | 16-NOV-12:00 | 49955.51 | 16-NOV-12:00 | 4193.71 | 29-NOV-20:00 | 5613.48 | 01-NOV-06:10 | 0.00 | 0.00 |
December | 116110.15 | 01-DEC-10:50 | 49248.27 | 01-DEC-08:00 | 5935.94 | 27-DEC-21:00 | 5613.48 | 01-DEC-18:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||
Minimum of Months | 39568.72 | 7505.05 | 0.00 | 5613.48 | 0.00 | 0.00 | ||||
Maximum of Months | 505944.19 | 87066.30 | 6182.48 | 5613.48 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 978340.73 | 04-JAN-16:49 | 261074.09 | 439129.89 | 37611.08 | 83156.88 | 74723.53 | 38283.74 | 0.00 | 33266.04 | 2448.92 |
February | 1095308.84 | 02-FEB-08:09 | 239289.90 | 557421.28 | 0.00 | 117103.21 | 74011.89 | 38278.67 | 0.00 | 57788.73 | 5101.83 |
March | 1458701.98 | 15-MAR-15:20 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 130250.70 | 58403.06 | 0.00 | 217447.97 | 53692.91 |
April | 1488423.68 | 07-APR-15:09 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 108737.85 | 38354.76 | 0.00 | 180242.58 | 49503.24 |
May | 1161092.52 | 26-MAY-15:00 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 161243.98 | 57995.37 | 0.00 | 134283.66 | 50858.44 |
June | 1589125.92 | 27-JUN-07:40 | 234435.00 | 557421.28 | 0.00 | 117189.56 | 142850.20 | 62213.49 | 0.00 | 387950.09 | 87066.30 |
July | 1806180.43 | 05-JUL-15:00 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 192603.98 | 65090.31 | 0.00 | 468125.99 | 87066.30 |
August | 1927706.14 | 07-AUG-15:30 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 202746.45 | 63278.33 | 0.00 | 463029.81 | 87066.30 |
September | 1357060.21 | 21-SEP-15:00 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 204225.15 | 59492.86 | 0.00 | 243951.37 | 87066.30 |
October | 1274964.52 | 11-OCT-15:50 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 142381.96 | 40214.34 | 0.00 | 165832.99 | 51532.77 |
November | 1375664.39 | 16-NOV-16:00 | 261074.09 | 675712.68 | 37611.08 | 83161.34 | 86146.80 | 38400.01 | 0.00 | 143723.50 | 49834.88 |
December | 1413053.77 | 12-DEC-16:49 | 261074.09 | 794004.08 | 37611.08 | 83161.34 | 75078.31 | 38279.16 | 0.00 | 106571.08 | 10782.04 |
Annual Sum or Average | |||||||||||
Minimum of Months | 978340.73 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 74011.89 | 38278.67 | 0.00 | 33266.04 | 2448.92 | |
Maximum of Months | 1927706.14 | 261074.09 | 794004.08 | 37611.08 | 117189.56 | 204225.15 | 65090.31 | 0.00 | 468125.99 | 87066.30 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1680702.37 | 02-JAN-05:10 | 0.00 | 84217.06 | 30-JAN-12:50 | 0.00 |
February | 0.00 | 0.00 | 1587508.51 | 21-FEB-07:10 | 0.00 | 84373.55 | 17-FEB-12:39 | 0.00 |
March | 0.00 | 0.00 | 1112162.29 | 06-MAR-06:10 | 0.00 | 84194.26 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 702475.97 | 17-APR-06:10 | 0.00 | 83258.51 | 03-APR-11:50 | 0.00 |
May | 0.00 | 0.00 | 141468.29 | 04-MAY-06:10 | 0.00 | 81609.04 | 02-MAY-11:39 | 0.00 |
June | 0.00 | 0.00 | 7749.81 | 14-JUN-05:10 | 0.00 | 79438.86 | 01-JUN-11:30 | 0.00 |
July | 0.00 | 0.00 | 5.74 | 15-JUL-07:49 | 0.00 | 77165.50 | 03-JUL-11:00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 75904.44 | 01-AUG-11:20 | 0.00 |
September | 0.00 | 0.00 | 102338.51 | 30-SEP-06:10 | 0.00 | 77082.51 | 28-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 556859.45 | 30-OCT-04:10 | 0.00 | 79376.54 | 31-OCT-11:39 | 0.00 |
November | 0.00 | 0.00 | 713671.05 | 24-NOV-07:10 | 0.00 | 81561.64 | 30-NOV-12:30 | 0.00 |
December | 0.00 | 0.00 | 1651014.07 | 26-DEC-07:10 | 0.00 | 83208.65 | 29-DEC-12:20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 75904.44 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1680702.37 | 0.00 | 84373.55 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.93 | 0.00 | 25.93 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.87 | 0.00 | 25.87 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.29 | 0.33 | 26.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.91 | 0.00 | 25.91 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 26.15 | 0.17 | 26.11 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.46 | 0.00 | 26.46 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.79 | 0.33 | 26.81 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 8.00 | 26.48 | 0.67 | 26.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 26.56 | 1.67 | 26.71 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 25.78 | 0.00 | 25.78 |
Annual Sum or Average | 0.00 | 0.00 | 47.50 | 26.41 | 3.17 | 26.46 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 9.33 | 26.79 | 1.67 | 26.81 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.89 | 0.00 | 25.89 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.66 | 0.00 | 25.66 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 25.74 | 0.00 | 25.74 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.89 | 0.00 | 25.89 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.58 | 0.50 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
February | 0.17 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
Annual Sum or Average | 1.33 | 19.51 | 0.50 | 19.70 | 0.00 | 19.70 | 0.00 | 19.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.00 | 19.58 | 0.50 | 19.79 | 0.00 | 19.79 | 0.00 | 19.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.50 | 18.78 | 1.17 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
February | 4.17 | 18.62 | 1.00 | 18.91 | 0.00 | 18.91 | 0.00 | 18.91 |
March | 1.67 | 19.25 | 0.33 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
April | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
November | 0.33 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 | 0.00 | 19.15 |
December | 4.00 | 18.75 | 0.83 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
Annual Sum or Average | 16.17 | 18.80 | 3.33 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 5.50 | 19.37 | 1.17 | 19.39 | 0.00 | 19.39 | 0.00 | 19.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 1.33 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 | 0.00 | 18.89 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.62 | 0.00 | 25.62 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.60 | 0.00 | 25.60 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2.50 | 18.97 | 0.00 | 18.97 | 0.83 | 20.63 | 0.00 | 20.63 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 19.05 | 0.00 | 19.05 | 0.50 | 25.62 | 0.00 | 25.62 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 1.50 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.43 | 0.50 | 27.43 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.53 | 0.83 | 27.53 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.61 | 2.50 | 27.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.91 | 3.17 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.58 | 1.00 | 27.58 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.65 | 2.17 | 27.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Annual Sum or Average | 3.67 | 19.01 | 0.00 | 19.01 | 10.17 | 25.39 | 10.17 | 26.37 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 19.34 | 0.00 | 19.34 | 3.17 | 27.91 | 3.17 | 27.91 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.83 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
February | 2.33 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 | 0.00 | 18.56 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.48 | 0.67 | 27.48 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.37 | 0.50 | 27.37 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.44 | 1.50 | 27.44 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 27.38 | 5.67 | 27.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 27.46 | 4.67 | 27.55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.73 | 4.17 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.32 | 0.50 | 27.32 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 | 0.00 | 19.20 |
Annual Sum or Average | 4.83 | 18.79 | 0.00 | 18.79 | 18.83 | 25.71 | 17.67 | 26.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 19.20 | 0.00 | 19.20 | 6.17 | 27.73 | 5.67 | 27.73 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
February | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 26.50 | 0.17 | 26.81 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.94 | 3.33 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.83 | 2.50 | 27.83 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 12.83 | 27.52 | 4.67 | 27.70 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 29.00 | 27.31 | 9.17 | 27.50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 29.50 | 27.18 | 8.00 | 27.37 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.91 | 3.00 | 27.91 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.32 | 0.33 | 27.32 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.67 | 19.18 | 0.00 | 19.18 | 84.33 | 27.31 | 31.17 | 27.51 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 19.26 | 0.00 | 19.26 | 29.50 | 27.94 | 9.17 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 48.00 | 17.68 | 15.83 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
February | 46.50 | 17.44 | 15.17 | 17.86 | 0.00 | 17.86 | 0.00 | 17.86 |
March | 10.50 | 18.81 | 2.67 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
April | 0.50 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.17 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
November | 1.33 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
December | 37.33 | 17.53 | 13.00 | 17.75 | 0.00 | 17.75 | 0.00 | 17.75 |
Annual Sum or Average | 144.33 | 17.67 | 46.67 | 17.97 | 0.00 | 17.97 | 0.00 | 17.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 48.00 | 19.30 | 15.83 | 19.30 | 0.00 | 19.30 | 0.00 | 19.30 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 22.67 | 16.33 | 1.67 | 16.27 | 0.00 | 16.27 | 0.00 | 16.27 |
February | 21.17 | 16.10 | 1.33 | 16.03 | 0.00 | 16.03 | 0.00 | 16.03 |
March | 4.33 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 | 0.00 | 18.35 |
April | 0.33 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 27.33 | 0.33 | 27.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.64 | 2.67 | 27.64 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.79 | 6.33 | 27.79 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.66 | 1.67 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.62 | 1.17 | 27.62 |
October | 0.17 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 | 0.00 | 19.23 |
November | 1.50 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 | 0.00 | 19.27 |
December | 18.83 | 16.46 | 1.83 | 16.42 | 0.00 | 16.42 | 0.00 | 16.42 |
Annual Sum or Average | 69.00 | 16.51 | 4.83 | 16.44 | 12.17 | 18.03 | 12.17 | 19.23 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.03 | 0.00 | 16.03 |
Maximum of Months | 22.67 | 19.27 | 1.83 | 19.27 | 6.33 | 27.79 | 6.33 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.83 | 16.96 | 1.00 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
February | 20.83 | 16.84 | 1.17 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
March | 3.50 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
April | 0.33 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 | 0.00 | 19.37 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.35 | 0.50 | 27.35 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.41 | 1.00 | 27.41 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 27.56 | 4.50 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 27.67 | 4.00 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.75 | 4.17 | 27.75 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.83 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 | 0.00 | 19.29 |
December | 16.00 | 17.33 | 1.67 | 17.45 | 0.00 | 17.45 | 0.00 | 17.45 |
Annual Sum or Average | 61.33 | 17.16 | 3.83 | 17.26 | 14.17 | 19.11 | 14.17 | 20.40 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 20.83 | 19.37 | 1.67 | 19.37 | 4.50 | 27.75 | 4.50 | 27.75 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 17.67 | 16.80 | 1.00 | 16.75 | 0.00 | 16.75 | 0.00 | 16.75 |
February | 16.33 | 16.52 | 0.17 | 16.51 | 0.00 | 16.51 | 0.00 | 16.51 |
March | 3.17 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 | 0.00 | 18.65 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 27.71 | 1.50 | 27.68 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.67 | 28.16 | 2.67 | 28.15 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.08 | 4.00 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.87 | 2.67 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.76 | 1.67 | 27.74 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
December | 12.50 | 16.93 | 0.50 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
Annual Sum or Average | 50.33 | 16.89 | 1.67 | 16.85 | 22.67 | 20.23 | 12.50 | 21.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 17.67 | 19.32 | 1.00 | 19.32 | 7.67 | 28.16 | 4.00 | 28.15 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.83 | 16.54 | 31.67 | 16.79 | 0.00 | 16.79 | 0.00 | 16.79 |
February | 89.83 | 16.35 | 33.50 | 16.67 | 0.00 | 16.67 | 0.00 | 16.67 |
March | 35.67 | 16.94 | 10.67 | 17.12 | 0.00 | 17.12 | 0.00 | 17.12 |
April | 6.83 | 16.94 | 1.67 | 16.85 | 0.00 | 16.85 | 0.00 | 16.85 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.45 | 1.17 | 27.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.83 | 18.65 | 0.33 | 18.82 | 0.00 | 18.82 | 0.00 | 18.82 |
November | 10.00 | 17.98 | 1.17 | 18.14 | 0.00 | 18.14 | 0.00 | 18.14 |
December | 79.33 | 16.43 | 28.67 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
Annual Sum or Average | 314.33 | 16.58 | 107.67 | 16.81 | 1.67 | 16.85 | 1.17 | 16.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 89.83 | 18.65 | 33.50 | 18.82 | 1.67 | 27.45 | 1.17 | 27.46 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 56.50 | 15.35 | 13.33 | 15.26 | 0.00 | 15.26 | 0.00 | 15.26 |
February | 56.50 | 15.43 | 13.17 | 15.43 | 0.00 | 15.43 | 0.00 | 15.43 |
March | 19.00 | 16.22 | 1.17 | 16.23 | 0.00 | 16.23 | 0.00 | 16.23 |
April | 4.67 | 17.04 | 0.33 | 16.90 | 0.00 | 16.90 | 0.00 | 16.90 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.59 | 3.00 | 27.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 27.83 | 7.00 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.72 | 2.33 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 | 0.00 | 18.29 |
November | 8.33 | 17.49 | 0.17 | 17.44 | 0.00 | 17.44 | 0.00 | 17.44 |
December | 52.50 | 15.41 | 12.33 | 15.34 | 0.00 | 15.34 | 0.00 | 15.34 |
Annual Sum or Average | 199.50 | 15.63 | 40.50 | 15.55 | 12.67 | 16.16 | 12.33 | 16.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 56.50 | 18.29 | 13.33 | 18.29 | 7.33 | 27.83 | 7.00 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 53.17 | 16.01 | 12.67 | 16.02 | 0.00 | 16.02 | 0.00 | 16.02 |
February | 56.33 | 16.05 | 15.67 | 16.26 | 0.00 | 16.26 | 0.00 | 16.26 |
March | 15.83 | 16.94 | 1.33 | 17.03 | 0.00 | 17.03 | 0.00 | 17.03 |
April | 4.33 | 17.24 | 0.83 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.38 | 0.50 | 27.38 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.47 | 1.83 | 27.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.58 | 5.83 | 27.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.73 | 4.17 | 27.75 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.77 | 2.67 | 27.77 |
October | 1.67 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
November | 6.67 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 | 0.00 | 18.05 |
December | 47.50 | 16.09 | 9.83 | 16.19 | 0.00 | 16.19 | 0.00 | 16.19 |
Annual Sum or Average | 185.50 | 16.25 | 40.33 | 16.31 | 16.33 | 17.08 | 15.00 | 17.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.02 | 0.00 | 16.02 |
Maximum of Months | 56.33 | 18.52 | 15.67 | 18.52 | 6.67 | 27.77 | 5.83 | 27.77 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 46.50 | 15.42 | 11.83 | 15.29 | 0.00 | 15.29 | 0.00 | 15.29 |
February | 39.17 | 15.47 | 7.67 | 15.39 | 0.00 | 15.39 | 0.00 | 15.39 |
March | 12.50 | 16.65 | 1.33 | 16.55 | 0.00 | 16.55 | 0.00 | 16.55 |
April | 2.17 | 18.34 | 0.17 | 18.10 | 0.00 | 18.10 | 0.00 | 18.10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.74 | 1.00 | 27.75 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 28.22 | 3.00 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 28.14 | 4.67 | 28.15 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.95 | 3.00 | 28.02 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.73 | 1.17 | 27.71 |
October | 1.50 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 | 0.00 | 18.57 |
November | 5.83 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 | 0.00 | 18.28 |
December | 35.33 | 15.58 | 5.83 | 15.47 | 0.00 | 15.47 | 0.00 | 15.47 |
Annual Sum or Average | 143.00 | 15.78 | 26.83 | 15.63 | 23.50 | 17.14 | 12.83 | 17.83 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.29 | 0.00 | 15.29 |
Maximum of Months | 46.50 | 18.57 | 11.83 | 18.57 | 8.83 | 28.22 | 4.67 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 137.50 | 28.35 | 126.00 | 28.36 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 137.50 | 28.35 | 126.00 | 28.36 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 137.50 | 28.35 | 126.00 | 28.36 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 397.50 | 23.58 | 28.17 | 23.73 | 12.00 | 23.80 |
February | 405.33 | 23.53 | 12.00 | 23.60 | 0.00 | 23.60 |
March | 251.33 | 23.88 | 79.83 | 24.15 | 0.00 | 24.15 |
April | 62.83 | 24.00 | 90.67 | 25.24 | 0.00 | 25.24 |
May | 45.50 | 24.00 | 166.17 | 24.97 | 0.00 | 24.97 |
June | 101.33 | 24.58 | 333.50 | 24.61 | 99.33 | 24.61 |
July | 181.17 | 24.99 | 480.50 | 24.70 | 181.17 | 24.77 |
August | 73.50 | 24.87 | 458.67 | 24.57 | 73.50 | 24.60 |
September | 47.50 | 25.02 | 346.67 | 24.77 | 47.50 | 24.80 |
October | 7.17 | 24.00 | 192.83 | 25.33 | 0.00 | 25.33 |
November | 59.67 | 24.00 | 113.50 | 25.36 | 0.00 | 25.36 |
December | 246.67 | 23.77 | 60.00 | 24.22 | 0.00 | 24.22 |
Annual Sum or Average | 1879.50 | 23.95 | 2362.50 | 24.49 | 413.50 | 24.53 |
Minimum of Months | 7.17 | 23.53 | 12.00 | 23.60 | 0.00 | 23.60 |
Maximum of Months | 405.33 | 25.02 | 480.50 | 25.36 | 181.17 | 25.36 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 451.50 | 23.59 | 12.67 | 23.62 | 12.67 | 23.64 |
February | 409.33 | 23.64 | 0.00 | 23.64 | 0.00 | 23.64 |
March | 241.33 | 23.92 | 85.83 | 24.12 | 0.00 | 24.12 |
April | 43.00 | 23.96 | 90.17 | 24.99 | 0.00 | 24.99 |
May | 46.50 | 23.94 | 167.83 | 24.62 | 0.00 | 24.62 |
June | 0.50 | 23.94 | 351.00 | 24.32 | 0.00 | 24.32 |
July | 0.00 | 0.00 | 485.50 | 24.25 | 0.00 | 24.25 |
August | 0.00 | 0.00 | 484.83 | 24.22 | 0.00 | 24.22 |
September | 9.67 | 24.83 | 342.33 | 24.45 | 3.83 | 24.47 |
October | 33.50 | 23.90 | 193.17 | 24.77 | 0.00 | 24.77 |
November | 78.67 | 23.94 | 88.50 | 24.84 | 0.00 | 24.84 |
December | 289.17 | 23.88 | 33.83 | 24.04 | 0.00 | 24.04 |
Annual Sum or Average | 1603.17 | 23.76 | 2335.67 | 24.20 | 16.50 | 24.21 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 23.62 | 0.00 | 23.64 |
Maximum of Months | 451.50 | 24.83 | 485.50 | 24.99 | 12.67 | 24.99 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.59 | 96.33 | 21.36 | 96.33 | 21.19 |
February | 454.00 | 21.76 | 83.67 | 21.61 | 83.67 | 21.50 |
March | 441.83 | 22.94 | 29.00 | 22.98 | 4.50 | 22.96 |
April | 342.67 | 23.47 | 6.17 | 23.50 | 0.00 | 23.50 |
May | 162.00 | 23.72 | 117.67 | 24.09 | 0.00 | 24.09 |
June | 31.17 | 23.75 | 289.00 | 24.19 | 0.00 | 24.19 |
July | 0.00 | 0.00 | 467.83 | 24.24 | 0.00 | 24.24 |
August | 0.00 | 0.00 | 439.67 | 24.25 | 0.00 | 24.25 |
September | 41.33 | 23.67 | 252.50 | 24.29 | 3.50 | 24.30 |
October | 287.33 | 23.57 | 36.50 | 23.66 | 0.00 | 23.66 |
November | 444.50 | 23.27 | 0.00 | 23.27 | 0.00 | 23.27 |
December | 492.67 | 22.01 | 57.67 | 21.87 | 57.67 | 21.75 |
Annual Sum or Average | 3199.50 | 22.64 | 1876.00 | 23.07 | 245.67 | 22.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21.36 | 0.00 | 21.19 |
Maximum of Months | 502.00 | 23.75 | 467.83 | 24.29 | 96.33 | 24.30 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.61 | 316.00 | 20.40 | 316.00 | 20.31 |
February | 454.00 | 20.78 | 246.00 | 20.52 | 246.00 | 20.40 |
March | 467.17 | 21.66 | 150.00 | 21.44 | 131.33 | 21.24 |
April | 440.67 | 22.60 | 22.50 | 22.47 | 21.50 | 22.35 |
May | 251.17 | 23.39 | 73.83 | 23.61 | 0.00 | 23.61 |
June | 61.00 | 23.63 | 286.33 | 24.10 | 0.00 | 24.10 |
July | 0.33 | 23.62 | 464.17 | 24.28 | 0.00 | 24.28 |
August | 7.83 | 23.51 | 424.67 | 24.24 | 0.00 | 24.24 |
September | 141.83 | 23.26 | 201.50 | 23.84 | 3.33 | 23.85 |
October | 419.00 | 22.35 | 46.00 | 22.23 | 35.67 | 22.10 |
November | 487.50 | 21.73 | 85.17 | 21.50 | 85.17 | 21.33 |
December | 497.00 | 20.74 | 263.83 | 20.49 | 263.83 | 20.37 |
Annual Sum or Average | 3729.50 | 21.70 | 2580.00 | 22.02 | 1102.83 | 21.73 |
Minimum of Months | 0.33 | 20.61 | 22.50 | 20.40 | 0.00 | 20.31 |
Maximum of Months | 502.00 | 23.63 | 464.17 | 24.28 | 316.00 | 24.28 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.98 | 279.00 | 20.85 | 279.00 | 20.79 |
February | 454.00 | 21.13 | 209.67 | 20.97 | 209.67 | 20.89 |
March | 440.83 | 22.25 | 89.17 | 22.19 | 60.00 | 22.05 |
April | 360.33 | 23.28 | 17.50 | 23.36 | 0.00 | 23.36 |
May | 201.83 | 23.59 | 91.83 | 23.89 | 0.00 | 23.89 |
June | 25.83 | 24.26 | 327.17 | 24.33 | 5.00 | 24.35 |
July | 4.00 | 26.58 | 478.83 | 24.38 | 4.00 | 24.40 |
August | 3.67 | 25.93 | 458.67 | 24.27 | 2.67 | 24.29 |
September | 87.17 | 23.55 | 224.67 | 24.10 | 6.67 | 24.14 |
October | 353.00 | 23.17 | 32.17 | 23.28 | 0.00 | 23.28 |
November | 454.17 | 22.82 | 8.17 | 22.85 | 0.00 | 22.85 |
December | 496.83 | 21.55 | 110.00 | 21.39 | 110.00 | 21.28 |
Annual Sum or Average | 3383.67 | 22.23 | 2326.83 | 22.66 | 677.00 | 22.47 |
Minimum of Months | 3.67 | 20.98 | 8.17 | 20.85 | 0.00 | 20.79 |
Maximum of Months | 502.00 | 26.58 | 478.83 | 24.38 | 279.00 | 24.40 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.95 | 259.17 | 20.83 | 259.17 | 20.76 |
February | 454.00 | 21.10 | 211.00 | 20.94 | 211.00 | 20.86 |
March | 452.33 | 22.25 | 69.50 | 22.24 | 39.00 | 22.15 |
April | 326.50 | 22.88 | 38.83 | 23.06 | 0.83 | 23.06 |
May | 165.83 | 23.36 | 170.67 | 23.98 | 5.00 | 24.02 |
June | 43.00 | 24.56 | 368.33 | 24.39 | 14.67 | 24.46 |
July | 25.00 | 26.78 | 484.00 | 24.47 | 25.00 | 24.58 |
August | 24.00 | 23.96 | 433.00 | 24.20 | 5.00 | 24.23 |
September | 111.33 | 23.47 | 292.50 | 24.14 | 12.83 | 24.20 |
October | 334.50 | 22.84 | 61.33 | 23.10 | 0.00 | 23.10 |
November | 454.17 | 22.28 | 8.00 | 22.33 | 0.00 | 22.33 |
December | 497.00 | 21.14 | 166.33 | 21.01 | 166.33 | 20.94 |
Annual Sum or Average | 3389.67 | 22.03 | 2562.67 | 22.61 | 738.83 | 22.44 |
Minimum of Months | 24.00 | 20.95 | 8.00 | 20.83 | 0.00 | 20.76 |
Maximum of Months | 502.00 | 26.78 | 484.00 | 24.47 | 259.17 | 24.58 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 487.67 | 21.18 | 239.50 | 20.96 | 235.83 | 20.83 |
February | 435.67 | 21.32 | 186.50 | 21.05 | 186.50 | 20.91 |
March | 379.33 | 22.41 | 79.67 | 22.46 | 37.17 | 22.34 |
April | 295.83 | 22.94 | 52.67 | 23.14 | 6.50 | 23.10 |
May | 187.50 | 23.42 | 146.00 | 23.92 | 3.33 | 23.95 |
June | 52.50 | 24.29 | 352.83 | 24.35 | 13.17 | 24.41 |
July | 32.00 | 26.76 | 477.67 | 24.57 | 32.00 | 24.70 |
August | 24.33 | 26.35 | 467.50 | 24.43 | 20.67 | 24.53 |
September | 80.50 | 24.07 | 334.33 | 24.39 | 19.67 | 24.49 |
October | 259.83 | 22.90 | 111.33 | 23.38 | 0.83 | 23.38 |
November | 394.17 | 22.42 | 36.83 | 22.57 | 6.50 | 22.55 |
December | 479.83 | 21.45 | 159.83 | 21.25 | 156.83 | 21.12 |
Annual Sum or Average | 3109.17 | 22.22 | 2644.67 | 22.80 | 719.00 | 22.63 |
Minimum of Months | 24.33 | 21.18 | 36.83 | 20.96 | 0.83 | 20.83 |
Maximum of Months | 487.67 | 26.76 | 477.67 | 24.57 | 235.83 | 24.70 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.67 | 21.36 | 131.00 | 21.22 | 131.00 | 21.14 |
February | 441.67 | 21.90 | 48.00 | 21.80 | 48.00 | 21.72 |
March | 266.33 | 23.12 | 92.83 | 23.48 | 0.83 | 23.49 |
April | 60.67 | 24.25 | 201.50 | 24.78 | 11.00 | 24.87 |
May | 90.17 | 23.91 | 236.67 | 24.51 | 12.83 | 24.60 |
June | 33.83 | 26.71 | 452.00 | 24.67 | 31.83 | 24.81 |
July | 70.50 | 26.83 | 497.00 | 24.88 | 70.50 | 25.10 |
August | 50.83 | 26.89 | 514.00 | 24.72 | 50.83 | 24.89 |
September | 49.50 | 24.80 | 374.67 | 24.54 | 21.50 | 24.65 |
October | 165.00 | 23.42 | 164.00 | 24.00 | 0.00 | 24.00 |
November | 249.33 | 23.39 | 52.67 | 23.70 | 0.00 | 23.70 |
December | 437.17 | 22.85 | 7.67 | 22.86 | 2.00 | 22.85 |
Annual Sum or Average | 2414.67 | 22.86 | 2772.00 | 23.66 | 380.33 | 23.68 |
Minimum of Months | 33.83 | 21.36 | 7.67 | 21.22 | 0.00 | 21.14 |
Maximum of Months | 499.67 | 26.89 | 514.00 | 24.88 | 131.00 | 25.10 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.94 | 476.33 | 19.91 | 476.33 | 19.90 |
February | 454.00 | 19.99 | 434.33 | 19.97 | 434.33 | 19.96 |
March | 488.83 | 20.88 | 283.00 | 20.71 | 269.50 | 20.59 |
April | 481.67 | 21.84 | 62.00 | 21.63 | 62.00 | 21.46 |
May | 347.00 | 23.09 | 45.50 | 23.22 | 0.00 | 23.22 |
June | 87.83 | 23.79 | 265.83 | 24.12 | 11.17 | 24.16 |
July | 29.83 | 25.43 | 461.67 | 24.40 | 27.83 | 24.47 |
August | 38.67 | 23.61 | 392.83 | 24.18 | 4.33 | 24.20 |
September | 234.83 | 23.13 | 147.17 | 23.55 | 12.67 | 23.62 |
October | 473.33 | 21.83 | 72.83 | 21.66 | 69.83 | 21.51 |
November | 489.00 | 20.89 | 189.67 | 20.69 | 189.67 | 20.58 |
December | 497.00 | 20.00 | 438.83 | 19.94 | 438.83 | 19.91 |
Annual Sum or Average | 4124.00 | 21.22 | 3270.00 | 21.44 | 1996.50 | 21.17 |
Minimum of Months | 29.83 | 19.94 | 45.50 | 19.91 | 0.00 | 19.90 |
Maximum of Months | 502.00 | 25.43 | 476.33 | 24.40 | 476.33 | 24.47 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 19.84 | 409.33 | 19.82 | 409.33 | 19.81 |
February | 385.00 | 19.93 | 358.00 | 19.88 | 358.00 | 19.87 |
March | 411.50 | 20.99 | 197.50 | 20.81 | 184.00 | 20.66 |
April | 340.83 | 21.78 | 59.33 | 21.73 | 41.50 | 21.55 |
May | 226.83 | 22.89 | 99.00 | 23.44 | 3.17 | 23.47 |
June | 74.67 | 24.01 | 278.50 | 24.35 | 17.50 | 24.46 |
July | 52.33 | 26.38 | 402.83 | 24.74 | 51.00 | 24.92 |
August | 52.33 | 24.24 | 342.17 | 24.38 | 17.50 | 24.47 |
September | 162.33 | 23.04 | 187.33 | 23.80 | 16.17 | 23.90 |
October | 378.00 | 21.84 | 51.33 | 21.77 | 40.67 | 21.65 |
November | 417.00 | 20.89 | 163.33 | 20.69 | 163.33 | 20.58 |
December | 422.00 | 19.88 | 384.50 | 19.83 | 384.50 | 19.81 |
Annual Sum or Average | 3349.83 | 21.18 | 2933.17 | 21.57 | 1686.67 | 21.30 |
Minimum of Months | 52.33 | 19.84 | 51.33 | 19.82 | 3.17 | 19.81 |
Maximum of Months | 427.00 | 26.38 | 409.33 | 24.74 | 409.33 | 24.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.83 | 20.40 | 378.00 | 20.20 | 378.00 | 20.13 |
February | 445.33 | 20.47 | 319.83 | 20.23 | 319.83 | 20.13 |
March | 425.67 | 21.62 | 152.50 | 21.44 | 127.00 | 21.24 |
April | 364.33 | 22.07 | 68.17 | 22.08 | 40.00 | 21.91 |
May | 248.17 | 23.03 | 105.00 | 23.47 | 3.00 | 23.49 |
June | 89.00 | 23.70 | 309.00 | 24.17 | 13.17 | 24.23 |
July | 57.17 | 25.82 | 464.50 | 24.59 | 48.83 | 24.73 |
August | 44.83 | 24.84 | 435.33 | 24.40 | 19.83 | 24.50 |
September | 131.17 | 23.66 | 292.17 | 24.19 | 24.83 | 24.33 |
October | 322.00 | 22.23 | 103.33 | 22.57 | 21.67 | 22.46 |
November | 435.33 | 21.47 | 124.00 | 21.28 | 114.83 | 21.11 |
December | 489.50 | 20.38 | 358.33 | 20.21 | 358.33 | 20.15 |
Annual Sum or Average | 3546.33 | 21.55 | 3110.17 | 21.99 | 1469.33 | 21.72 |
Minimum of Months | 44.83 | 20.38 | 68.17 | 20.20 | 3.00 | 20.13 |
Maximum of Months | 493.83 | 25.82 | 464.50 | 24.59 | 378.00 | 24.73 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.10 | 452.17 | 20.05 | 452.17 | 20.04 |
February | 454.00 | 20.24 | 382.17 | 20.15 | 382.17 | 20.11 |
March | 473.50 | 21.28 | 189.50 | 21.11 | 172.67 | 20.95 |
April | 397.00 | 21.96 | 66.00 | 22.02 | 31.33 | 21.88 |
May | 261.00 | 22.99 | 141.83 | 23.54 | 6.00 | 23.59 |
June | 81.33 | 24.12 | 354.83 | 24.34 | 23.17 | 24.45 |
July | 51.17 | 26.10 | 473.33 | 24.64 | 45.83 | 24.78 |
August | 40.50 | 24.69 | 448.67 | 24.41 | 16.67 | 24.49 |
September | 180.67 | 23.18 | 227.67 | 23.85 | 19.17 | 23.97 |
October | 440.17 | 21.94 | 60.67 | 21.94 | 35.83 | 21.84 |
November | 486.33 | 21.11 | 142.17 | 20.93 | 142.17 | 20.81 |
December | 497.00 | 20.19 | 395.00 | 20.09 | 395.00 | 20.06 |
Annual Sum or Average | 3864.67 | 21.35 | 3334.00 | 21.80 | 1722.17 | 21.55 |
Minimum of Months | 40.50 | 20.10 | 60.67 | 20.05 | 6.00 | 20.04 |
Maximum of Months | 502.00 | 26.10 | 473.33 | 24.64 | 452.17 | 24.78 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.74 | 495.17 | 19.73 | 495.17 | 19.73 |
February | 454.00 | 19.79 | 451.00 | 19.79 | 451.00 | 19.79 |
March | 494.67 | 20.46 | 357.33 | 20.30 | 349.00 | 20.21 |
April | 483.17 | 21.13 | 165.00 | 20.85 | 165.00 | 20.68 |
May | 393.50 | 22.49 | 44.00 | 22.55 | 12.83 | 22.49 |
June | 134.33 | 23.35 | 258.83 | 23.92 | 13.50 | 23.97 |
July | 47.17 | 24.86 | 448.33 | 24.38 | 31.83 | 24.46 |
August | 77.67 | 23.26 | 358.67 | 24.05 | 6.83 | 24.07 |
September | 297.00 | 22.56 | 115.33 | 23.00 | 15.33 | 23.07 |
October | 495.50 | 20.99 | 160.17 | 20.67 | 158.17 | 20.46 |
November | 489.00 | 20.25 | 338.67 | 20.10 | 338.67 | 20.04 |
December | 497.00 | 19.75 | 477.33 | 19.73 | 477.33 | 19.72 |
Annual Sum or Average | 4365.00 | 20.85 | 3669.83 | 21.05 | 2514.67 | 20.79 |
Minimum of Months | 47.17 | 19.74 | 44.00 | 19.73 | 6.83 | 19.72 |
Maximum of Months | 502.00 | 24.86 | 495.17 | 24.38 | 495.17 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.81 | 495.33 | 19.80 | 495.33 | 19.80 |
February | 454.00 | 19.88 | 439.00 | 19.86 | 439.00 | 19.85 |
March | 484.67 | 20.56 | 305.67 | 20.39 | 286.50 | 20.25 |
April | 405.33 | 21.33 | 107.83 | 21.02 | 104.17 | 20.80 |
May | 271.00 | 22.54 | 116.17 | 23.07 | 4.50 | 23.06 |
June | 93.33 | 23.87 | 342.17 | 24.25 | 23.33 | 24.37 |
July | 64.67 | 26.11 | 473.50 | 24.65 | 58.83 | 24.83 |
August | 69.67 | 23.89 | 407.00 | 24.26 | 19.67 | 24.35 |
September | 196.00 | 22.52 | 225.33 | 23.45 | 14.17 | 23.51 |
October | 469.33 | 21.25 | 125.50 | 20.95 | 119.83 | 20.73 |
November | 489.00 | 20.36 | 316.83 | 20.19 | 316.83 | 20.11 |
December | 497.00 | 19.80 | 479.50 | 19.78 | 479.50 | 19.77 |
Annual Sum or Average | 3996.00 | 20.89 | 3833.83 | 21.28 | 2361.67 | 21.02 |
Minimum of Months | 64.67 | 19.80 | 107.83 | 19.78 | 4.50 | 19.77 |
Maximum of Months | 502.00 | 26.11 | 495.33 | 24.65 | 495.33 | 24.83 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.08 | 436.33 | 19.94 | 436.33 | 19.89 |
February | 449.17 | 20.11 | 364.33 | 19.91 | 364.33 | 19.83 |
March | 455.50 | 21.04 | 245.33 | 20.80 | 221.83 | 20.59 |
April | 397.67 | 21.45 | 131.67 | 21.28 | 110.33 | 21.05 |
May | 301.00 | 22.55 | 101.17 | 22.93 | 11.83 | 22.91 |
June | 123.00 | 23.40 | 295.83 | 24.03 | 19.33 | 24.13 |
July | 77.67 | 25.32 | 451.50 | 24.56 | 55.33 | 24.72 |
August | 77.17 | 24.06 | 411.33 | 24.30 | 21.67 | 24.40 |
September | 177.17 | 22.99 | 260.83 | 23.82 | 24.33 | 23.94 |
October | 391.17 | 21.53 | 145.83 | 21.50 | 89.67 | 21.24 |
November | 467.83 | 20.81 | 236.67 | 20.51 | 235.83 | 20.36 |
December | 495.83 | 20.00 | 440.17 | 19.90 | 440.17 | 19.86 |
Annual Sum or Average | 3915.17 | 21.16 | 3521.00 | 21.51 | 2031.00 | 21.23 |
Minimum of Months | 77.17 | 20.00 | 101.17 | 19.90 | 11.83 | 19.83 |
Maximum of Months | 502.00 | 25.32 | 451.50 | 24.56 | 440.17 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 19.87 | 484.00 | 19.85 | 484.00 | 19.84 |
February | 454.00 | 19.99 | 412.00 | 19.92 | 412.00 | 19.90 |
March | 484.67 | 20.83 | 267.17 | 20.62 | 252.83 | 20.48 |
April | 418.33 | 21.40 | 128.17 | 21.32 | 98.67 | 21.11 |
May | 302.50 | 22.48 | 114.17 | 23.02 | 7.50 | 23.06 |
June | 112.00 | 23.66 | 338.50 | 24.19 | 26.33 | 24.31 |
July | 65.00 | 25.64 | 460.17 | 24.62 | 50.17 | 24.78 |
August | 70.17 | 23.94 | 422.17 | 24.31 | 18.17 | 24.40 |
September | 239.50 | 22.72 | 190.33 | 23.45 | 19.33 | 23.57 |
October | 463.00 | 21.26 | 125.17 | 21.06 | 107.33 | 20.86 |
November | 489.00 | 20.55 | 256.67 | 20.33 | 256.67 | 20.22 |
December | 497.00 | 19.88 | 454.00 | 19.83 | 454.00 | 19.81 |
Annual Sum or Average | 4097.17 | 21.02 | 3652.50 | 21.40 | 2187.00 | 21.14 |
Minimum of Months | 65.00 | 19.87 | 114.17 | 19.83 | 7.50 | 19.81 |
Maximum of Months | 502.00 | 25.64 | 484.00 | 24.62 | 484.00 | 24.78 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 450.33 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 448.67 | 27.00 | 0.00 | 27.00 |
March | 3.67 | 27.00 | 514.00 | 27.00 | 3.67 | 27.00 |
April | 28.00 | 27.00 | 485.00 | 27.00 | 28.00 | 27.00 |
May | 2.83 | 27.00 | 508.00 | 27.00 | 2.83 | 27.00 |
June | 58.67 | 27.00 | 496.00 | 27.00 | 58.67 | 27.00 |
July | 231.50 | 27.00 | 497.00 | 27.00 | 231.50 | 27.00 |
August | 349.00 | 27.00 | 514.00 | 27.00 | 349.00 | 27.00 |
September | 7.33 | 27.00 | 485.00 | 27.00 | 7.33 | 27.00 |
October | 4.33 | 27.00 | 502.00 | 27.00 | 4.33 | 27.00 |
November | 1.33 | 27.00 | 489.00 | 27.00 | 1.33 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 686.67 | 27.00 | 5886.00 | 27.00 | 686.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 448.67 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 349.00 | 27.00 | 514.00 | 27.00 | 349.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 128.50 | 25.47 | 118.67 | 26.21 | 0.00 | 26.21 |
February | 16.50 | 27.00 | 180.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 433.50 | 27.00 | 0.00 | 27.00 |
April | 0.33 | 27.00 | 485.00 | 27.00 | 0.33 | 27.00 |
May | 0.67 | 27.00 | 508.00 | 27.00 | 0.67 | 27.00 |
June | 2.33 | 27.00 | 496.00 | 27.00 | 2.33 | 27.00 |
July | 20.50 | 27.00 | 497.00 | 27.00 | 20.50 | 27.00 |
August | 50.17 | 27.00 | 514.00 | 27.00 | 50.17 | 27.00 |
September | 1.83 | 27.00 | 485.00 | 27.00 | 1.83 | 27.00 |
October | 0.83 | 27.00 | 502.00 | 27.00 | 0.83 | 27.00 |
November | 0.00 | 0.00 | 480.17 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 298.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 221.67 | 26.11 | 4997.67 | 26.96 | 76.67 | 26.96 |
Minimum of Months | 0.00 | 0.00 | 118.67 | 26.21 | 0.00 | 26.21 |
Maximum of Months | 128.50 | 27.00 | 514.00 | 27.00 | 50.17 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 302.00 | 24.90 | 93.67 | 24.94 | 40.50 | 24.71 |
February | 81.33 | 26.99 | 112.67 | 27.00 | 0.00 | 27.00 |
March | 25.17 | 27.00 | 340.00 | 27.00 | 0.00 | 27.00 |
April | 0.00 | 0.00 | 459.33 | 27.00 | 0.00 | 27.00 |
May | 1.33 | 27.00 | 508.00 | 27.00 | 1.33 | 27.00 |
June | 19.33 | 27.00 | 496.00 | 27.00 | 19.33 | 27.00 |
July | 79.17 | 27.00 | 497.00 | 27.00 | 79.17 | 27.00 |
August | 85.83 | 27.00 | 514.00 | 27.00 | 85.83 | 27.00 |
September | 2.17 | 27.00 | 485.00 | 27.00 | 2.17 | 27.00 |
October | 0.83 | 27.00 | 455.83 | 27.00 | 0.83 | 27.00 |
November | 4.50 | 27.00 | 384.67 | 27.00 | 0.00 | 27.00 |
December | 72.67 | 27.00 | 199.33 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 674.33 | 26.06 | 4545.50 | 26.84 | 229.17 | 26.82 |
Minimum of Months | 0.00 | 0.00 | 93.67 | 24.94 | 0.00 | 24.71 |
Maximum of Months | 302.00 | 27.00 | 514.00 | 27.00 | 85.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 32.00 | 27.00 | 502.00 | 27.00 | 32.00 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
May | 498.17 | 27.00 | 508.00 | 27.00 | 498.17 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.37 | 514.00 | 27.37 | 514.00 | 27.37 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
Annual Sum or Average | 5463.17 | 27.04 | 5943.00 | 27.04 | 5463.17 | 27.04 |
Minimum of Months | 32.00 | 27.00 | 454.00 | 27.00 | 32.00 | 27.00 |
Maximum of Months | 514.00 | 27.37 | 514.00 | 27.37 | 514.00 | 27.37 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00000 | 16.95163 | 0.63581 | 13.61699 |
February | 454.00000 | 27.00000 | 16.10904 | 0.67631 | 14.71804 |
March | 514.00000 | 27.00007 | 21.74210 | 0.83111 | 19.78335 |
April | 485.00000 | 27.00000 | 26.63423 | 0.93697 | 23.60846 |
May | 508.00000 | 27.00022 | 30.42690 | 0.21452 | 6.07175 |
June | 496.00000 | 27.00084 | 34.99973 | 0.33301 | 7.38668 |
July | 497.00000 | 27.00079 | 37.32080 | 0.40536 | 8.47915 |
August | 514.00000 | 27.00019 | 36.61340 | 0.43898 | 9.08039 |
September | 485.00000 | 27.00056 | 36.08181 | 0.27195 | 6.62035 |
October | 502.00000 | 27.00016 | 30.26869 | 0.89631 | 22.03777 |
November | 489.00000 | 27.00000 | 26.07930 | 0.87172 | 21.12688 |
December | 497.00000 | 27.00000 | 19.05881 | 0.79289 | 18.36794 |
Annual Sum or Average | 5943.00000 | 27.00024 | 27.76717 | 0.60765 | 14.21839 |
Minimum of Months | 454.00000 | 27.00000 | 16.10904 | 0.21452 | 6.07175 |
Maximum of Months | 514.00000 | 27.00084 | 37.32080 | 0.93697 | 23.60846 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.52009 | 17.17617 | 0.40543 | 9.32218 |
February | 454.00000 | 27.00000 | 16.09337 | 0.51436 | 10.68368 |
March | 514.00000 | 27.00006 | 21.73248 | 0.67138 | 14.82061 |
April | 485.00000 | 27.00001 | 26.60852 | 0.78089 | 18.00635 |
May | 508.00000 | 27.00020 | 30.43648 | 0.13135 | 5.53178 |
June | 496.00000 | 27.00080 | 35.00578 | 0.24722 | 6.39389 |
July | 497.00000 | 27.00081 | 37.32663 | 0.30786 | 7.04187 |
August | 514.00000 | 27.00021 | 36.59438 | 0.31640 | 7.16951 |
September | 485.00000 | 27.00044 | 36.18709 | 0.19248 | 5.91062 |
October | 502.00000 | 27.00015 | 30.24930 | 0.77921 | 17.94029 |
November | 489.00000 | 27.00000 | 26.04104 | 0.69967 | 15.43123 |
December | 497.00000 | 27.00000 | 19.03263 | 0.57093 | 12.01056 |
Annual Sum or Average | 5943.00000 | 26.95969 | 27.78379 | 0.46715 | 10.84221 |
Minimum of Months | 454.00000 | 26.52009 | 16.09337 | 0.13135 | 5.53178 |
Maximum of Months | 514.00000 | 27.00081 | 37.32663 | 0.78089 | 18.00635 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 25.64453 | 17.57367 | 0.18771 | 8.08488 |
February | 454.00000 | 26.99908 | 16.09333 | 0.46078 | 9.69036 |
March | 514.00000 | 27.00007 | 21.74293 | 0.60852 | 13.29165 |
April | 485.00000 | 27.00001 | 26.61975 | 0.72418 | 16.32424 |
May | 508.00000 | 27.00020 | 30.47272 | 0.09584 | 5.52073 |
June | 496.00000 | 27.00083 | 35.02117 | 0.24658 | 6.49492 |
July | 497.00000 | 27.00083 | 37.34165 | 0.31976 | 7.26307 |
August | 514.00000 | 27.00023 | 36.61645 | 0.31703 | 7.25420 |
September | 485.00000 | 27.00041 | 36.26364 | 0.16061 | 5.82091 |
October | 502.00000 | 27.00015 | 30.28188 | 0.71104 | 15.93186 |
November | 489.00000 | 27.00000 | 26.05901 | 0.61825 | 13.23731 |
December | 497.00000 | 27.00000 | 19.04308 | 0.50421 | 10.57223 |
Annual Sum or Average | 5943.00000 | 26.88566 | 27.83808 | 0.41192 | 9.94784 |
Minimum of Months | 454.00000 | 25.64453 | 16.09333 | 0.09584 | 5.52073 |
Maximum of Months | 514.00000 | 27.00083 | 37.34165 | 0.72418 | 16.32424 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00030 | 30.36815 | 0.98771 | 25.61844 |
February | 454.00000 | 27.00456 | 30.11367 | 1.15418 | 33.05044 |
March | 514.00000 | 27.00578 | 31.13329 | 1.34377 | 42.55162 |
April | 485.00000 | 27.00310 | 30.81595 | 1.49062 | 50.39229 |
May | 508.00000 | 27.00072 | 32.61416 | 0.47706 | 9.80271 |
June | 496.00000 | 27.00121 | 35.26347 | 0.74622 | 16.75268 |
July | 497.00000 | 27.00077 | 37.15211 | 0.97444 | 25.07320 |
August | 514.00000 | 27.37354 | 36.30712 | 1.27380 | 39.17641 |
September | 485.00000 | 27.00127 | 35.72664 | 0.56540 | 11.74114 |
October | 502.00000 | 27.00141 | 32.25849 | 1.25532 | 38.00833 |
November | 489.00000 | 27.00355 | 30.97294 | 1.37720 | 44.30417 |
December | 497.00000 | 27.00910 | 30.28739 | 1.47570 | 49.58336 |
Annual Sum or Average | 5943.00000 | 27.03494 | 32.77294 | 1.09309 | 32.16332 |
Minimum of Months | 454.00000 | 27.00030 | 30.11367 | 0.47706 | 9.80271 |
Maximum of Months | 514.00000 | 27.37354 | 37.15211 | 1.49062 | 50.39229 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.81695 | 18.31923 | 0.15028 | 6.47153 |
February | 454.00000 | 23.73127 | 17.02758 | 0.11855 | 5.90684 |
March | 514.00000 | 24.23266 | 23.41408 | 0.29507 | 7.24436 |
April | 485.00000 | 24.43748 | 26.70182 | 0.37189 | 8.30213 |
May | 508.00000 | 24.44166 | 32.35958 | -0.4502 | 10.10503 |
June | 496.00000 | 24.42542 | 46.37952 | -0.3384 | 8.31254 |
July | 497.00000 | 24.57621 | 57.32893 | -0.2069 | 7.21042 |
August | 514.00000 | 24.46151 | 51.18573 | -0.2754 | 7.61301 |
September | 485.00000 | 24.52577 | 45.52737 | -0.3052 | 8.12630 |
October | 502.00000 | 24.54017 | 32.23148 | 0.44673 | 9.75138 |
November | 489.00000 | 24.53183 | 25.58275 | 0.39222 | 8.77762 |
December | 497.00000 | 24.29694 | 19.42480 | 0.28053 | 7.14388 |
Annual Sum or Average | 5943.00000 | 24.33832 | 33.07789 | 0.03833 | 7.92745 |
Minimum of Months | 454.00000 | 23.73127 | 17.02758 | -0.4502 | 5.90684 |
Maximum of Months | 514.00000 | 24.57621 | 57.32893 | 0.44673 | 10.10503 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.65431 | 24.50258 | 0.12752 | 5.97487 |
February | 454.00000 | 23.72742 | 21.90498 | 0.12920 | 5.69698 |
March | 514.00000 | 24.17255 | 25.59898 | 0.30029 | 7.24307 |
April | 485.00000 | 24.31400 | 28.05369 | 0.37243 | 8.16925 |
May | 508.00000 | 24.29079 | 33.81354 | -0.4654 | 10.13116 |
June | 496.00000 | 24.24042 | 45.33643 | -0.3711 | 8.28301 |
July | 497.00000 | 24.24026 | 53.76946 | -0.2977 | 7.09672 |
August | 514.00000 | 24.20513 | 50.53771 | -0.3228 | 7.39880 |
September | 485.00000 | 24.31357 | 45.63886 | -0.3608 | 8.33299 |
October | 502.00000 | 24.36639 | 34.23104 | 0.41840 | 8.99773 |
November | 489.00000 | 24.38339 | 28.08768 | 0.37010 | 8.23923 |
December | 497.00000 | 24.16204 | 22.90569 | 0.26027 | 6.69223 |
Annual Sum or Average | 5943.00000 | 24.17492 | 34.63080 | 0.01155 | 7.70138 |
Minimum of Months | 454.00000 | 23.65431 | 21.90498 | -0.4654 | 5.69698 |
Maximum of Months | 514.00000 | 24.38339 | 53.76946 | 0.41840 | 10.13116 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.59182 | 24.65672 | -0.4019 | 9.92089 |
February | 454.00000 | 21.76325 | 23.96702 | -0.3618 | 8.64489 |
March | 514.00000 | 23.09264 | 28.93335 | 0.01507 | 6.28425 |
April | 485.00000 | 23.67946 | 30.81716 | 0.18717 | 6.19800 |
May | 508.00000 | 24.10235 | 34.60541 | -0.5588 | 12.08272 |
June | 496.00000 | 24.13381 | 46.01651 | -0.4382 | 9.39035 |
July | 497.00000 | 24.22390 | 54.38117 | -0.3431 | 7.79889 |
August | 514.00000 | 24.20648 | 51.29457 | -0.3693 | 8.15027 |
September | 485.00000 | 24.14746 | 46.46636 | -0.4453 | 9.75700 |
October | 502.00000 | 23.80727 | 36.62387 | 0.25915 | 6.76112 |
November | 489.00000 | 23.34067 | 31.97237 | 0.09239 | 5.77394 |
December | 497.00000 | 22.03106 | 27.11918 | -0.2739 | 7.77870 |
Annual Sum or Average | 5943.00000 | 23.35442 | 36.49797 | -0.2197 | 8.21434 |
Minimum of Months | 454.00000 | 21.59182 | 23.96702 | -0.5588 | 5.77394 |
Maximum of Months | 514.00000 | 24.22390 | 54.38117 | 0.25915 | 12.08272 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.61078 | 25.61595 | -0.6692 | 16.97953 |
February | 454.00000 | 20.78179 | 25.12473 | -0.6248 | 15.73449 |
March | 514.00000 | 21.87504 | 30.50905 | -0.2921 | 10.00445 |
April | 485.00000 | 22.72747 | 32.79119 | -0.0512 | 6.94549 |
May | 508.00000 | 23.80102 | 35.53704 | -0.6698 | 15.54630 |
June | 496.00000 | 24.08713 | 46.16236 | -0.4465 | 9.73299 |
July | 497.00000 | 24.25829 | 54.05519 | -0.3194 | 7.55815 |
August | 514.00000 | 24.18760 | 51.16769 | -0.3716 | 8.22227 |
September | 485.00000 | 23.87532 | 47.50974 | -0.5459 | 12.51842 |
October | 502.00000 | 22.61935 | 39.79000 | -0.0363 | 7.03687 |
November | 489.00000 | 21.73578 | 34.90827 | -0.3078 | 8.67629 |
December | 497.00000 | 20.73587 | 28.59569 | -0.6132 | 15.29327 |
Annual Sum or Average | 5943.00000 | 22.62225 | 37.73602 | -0.4113 | 11.16156 |
Minimum of Months | 454.00000 | 20.61078 | 25.12473 | -0.6698 | 6.94549 |
Maximum of Months | 514.00000 | 24.25829 | 54.05519 | -0.0363 | 16.97953 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.98340 | 22.72399 | -0.5492 | 12.17173 |
February | 454.00000 | 21.12979 | 22.55453 | -0.5090 | 11.23512 |
March | 514.00000 | 22.50810 | 26.69154 | -0.1207 | 7.59299 |
April | 485.00000 | 23.51072 | 28.62582 | 0.14495 | 6.17597 |
May | 508.00000 | 23.96278 | 34.09001 | -0.6004 | 13.47857 |
June | 496.00000 | 24.23448 | 44.75749 | -0.3671 | 8.48638 |
July | 497.00000 | 24.34821 | 52.98129 | -0.2401 | 6.84679 |
August | 514.00000 | 24.22992 | 49.87342 | -0.3141 | 7.57078 |
September | 485.00000 | 24.04667 | 45.74652 | -0.4804 | 10.74936 |
October | 502.00000 | 23.45126 | 34.99406 | 0.16577 | 6.38698 |
November | 489.00000 | 22.92045 | 29.11601 | -0.0136 | 5.92097 |
December | 497.00000 | 21.55544 | 24.14008 | -0.3805 | 9.07110 |
Annual Sum or Average | 5943.00000 | 23.08656 | 34.78440 | -0.2712 | 8.79742 |
Minimum of Months | 454.00000 | 20.98340 | 22.55453 | -0.6004 | 5.92097 |
Maximum of Months | 514.00000 | 24.34821 | 52.98129 | 0.16577 | 13.47857 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94952 | 22.27973 | -0.5532 | 12.13329 |
February | 454.00000 | 21.10489 | 22.11290 | -0.5109 | 11.41799 |
March | 514.00000 | 22.45718 | 26.44578 | -0.1126 | 7.30434 |
April | 485.00000 | 23.30274 | 28.49966 | 0.13493 | 6.64000 |
May | 508.00000 | 23.96240 | 33.65621 | -0.5327 | 12.86750 |
June | 496.00000 | 24.23681 | 44.48448 | -0.3043 | 8.27461 |
July | 497.00000 | 24.33842 | 52.77614 | -0.1849 | 6.93074 |
August | 514.00000 | 24.13445 | 49.99548 | -0.2953 | 7.75289 |
September | 485.00000 | 24.03428 | 45.46047 | -0.4234 | 10.54675 |
October | 502.00000 | 23.29348 | 34.86474 | 0.15353 | 6.79890 |
November | 489.00000 | 22.43071 | 29.31268 | -0.1131 | 6.46737 |
December | 497.00000 | 21.14254 | 24.20864 | -0.4788 | 10.51344 |
Annual Sum or Average | 5943.00000 | 22.96234 | 34.60277 | -0.2674 | 8.95775 |
Minimum of Months | 454.00000 | 20.94952 | 22.11290 | -0.5532 | 6.46737 |
Maximum of Months | 514.00000 | 24.33842 | 52.77614 | 0.15353 | 12.86750 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.27484 | 22.32003 | -0.4786 | 12.04374 |
February | 454.00000 | 21.42925 | 21.99622 | -0.4347 | 11.31352 |
March | 514.00000 | 22.86250 | 25.93076 | -0.0147 | 7.51433 |
April | 485.00000 | 23.43892 | 28.33077 | 0.15529 | 7.04302 |
May | 508.00000 | 23.94941 | 33.85585 | -0.5695 | 13.54722 |
June | 496.00000 | 24.22852 | 44.63494 | -0.3433 | 8.64801 |
July | 497.00000 | 24.40030 | 52.64349 | -0.1881 | 6.94055 |
August | 514.00000 | 24.29104 | 49.47294 | -0.2374 | 7.23591 |
September | 485.00000 | 24.21373 | 44.95081 | -0.3473 | 9.44892 |
October | 502.00000 | 23.54639 | 34.23492 | 0.22503 | 7.77486 |
November | 489.00000 | 22.79356 | 28.92052 | -0.0297 | 6.84610 |
December | 497.00000 | 21.55236 | 24.10947 | -0.3862 | 9.92588 |
Annual Sum or Average | 5943.00000 | 23.17782 | 34.37691 | -0.2199 | 9.01350 |
Minimum of Months | 454.00000 | 21.27484 | 21.99622 | -0.5695 | 6.84610 |
Maximum of Months | 514.00000 | 24.40030 | 52.64349 | 0.22503 | 13.54722 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.37402 | 21.48466 | -0.4227 | 9.60145 |
February | 454.00000 | 21.96237 | 20.78384 | -0.2701 | 7.64668 |
March | 514.00000 | 23.68175 | 24.22777 | 0.21498 | 7.51503 |
April | 485.00000 | 24.37713 | 26.26936 | 0.44668 | 10.06758 |
May | 508.00000 | 24.27151 | 32.88505 | -0.3879 | 9.96336 |
June | 496.00000 | 24.47313 | 43.68387 | -0.1329 | 7.03723 |
July | 497.00000 | 24.60644 | 51.71077 | 0.01303 | 6.87541 |
August | 514.00000 | 24.50084 | 48.60499 | -0.0284 | 6.64938 |
September | 485.00000 | 24.32352 | 44.50918 | -0.2843 | 8.35531 |
October | 502.00000 | 24.03640 | 32.98259 | 0.36011 | 8.51326 |
November | 489.00000 | 23.88762 | 26.61021 | 0.25591 | 7.15642 |
December | 497.00000 | 23.00677 | 21.55165 | -0.0045 | 6.10539 |
Annual Sum or Average | 5943.00000 | 23.71967 | 33.03696 | -0.0190 | 7.95618 |
Minimum of Months | 454.00000 | 21.37402 | 20.78384 | -0.4227 | 6.10539 |
Maximum of Months | 514.00000 | 24.60644 | 51.71077 | 0.44668 | 10.06758 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.94155 | 23.32475 | -0.8999 | 24.42808 |
February | 454.00000 | 19.99089 | 23.18742 | -0.8752 | 23.46738 |
March | 514.00000 | 21.03144 | 29.56549 | -0.5135 | 14.07490 |
April | 485.00000 | 21.85046 | 31.97003 | -0.2593 | 8.33537 |
May | 508.00000 | 23.39761 | 35.76940 | -0.8049 | 20.25670 |
June | 496.00000 | 24.05330 | 45.84231 | -0.4525 | 10.17994 |
July | 497.00000 | 24.31151 | 54.26179 | -0.2809 | 7.30091 |
August | 514.00000 | 24.13544 | 50.94008 | -0.3847 | 8.71941 |
September | 485.00000 | 23.58622 | 47.48899 | -0.6522 | 15.82087 |
October | 502.00000 | 21.94843 | 38.30703 | -0.1967 | 7.72725 |
November | 489.00000 | 20.89396 | 33.06195 | -0.5132 | 11.75375 |
December | 497.00000 | 20.00162 | 26.68677 | -0.8425 | 22.45114 |
Annual Sum or Average | 5943.00000 | 22.11247 | 36.79810 | -0.5543 | 14.48801 |
Minimum of Months | 454.00000 | 19.94155 | 23.18742 | -0.8999 | 7.30091 |
Maximum of Months | 514.00000 | 24.31151 | 54.26179 | -0.1967 | 24.42808 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 19.83984 | 22.48049 | -0.9113 | 24.91515 |
February | 385.00000 | 19.92915 | 22.36426 | -0.8713 | 23.44472 |
March | 433.00000 | 21.13534 | 28.47314 | -0.4612 | 12.49997 |
April | 410.00000 | 22.20141 | 30.39064 | -0.1442 | 8.29948 |
May | 430.00000 | 23.55812 | 34.47910 | -0.6873 | 17.99792 |
June | 418.00000 | 24.17837 | 45.01136 | -0.3423 | 9.49723 |
July | 422.00000 | 24.49554 | 53.34182 | -0.1529 | 7.34921 |
August | 433.00000 | 24.21375 | 50.19874 | -0.2968 | 8.47012 |
September | 410.00000 | 23.71418 | 46.53238 | -0.5510 | 14.43517 |
October | 427.00000 | 22.09927 | 36.87090 | -0.1431 | 7.57545 |
November | 417.00000 | 20.89232 | 31.81267 | -0.5096 | 11.71387 |
December | 422.00000 | 19.88291 | 25.81746 | -0.8667 | 23.27904 |
Annual Sum or Average | 5034.00000 | 22.19282 | 35.73073 | -0.4927 | 14.06828 |
Minimum of Months | 385.00000 | 19.83984 | 22.36426 | -0.9113 | 7.34921 |
Maximum of Months | 433.00000 | 24.49554 | 53.34182 | -0.1431 | 24.91515 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.46640 | 22.64184 | -0.7215 | 19.42115 |
February | 454.00000 | 20.53827 | 22.43881 | -0.6881 | 18.74149 |
March | 514.00000 | 22.03189 | 27.97734 | -0.2224 | 9.80593 |
April | 485.00000 | 22.61690 | 30.18035 | -0.0472 | 7.97748 |
May | 508.00000 | 23.62704 | 34.80878 | -0.6832 | 17.28911 |
June | 496.00000 | 24.08250 | 45.51163 | -0.4082 | 10.05749 |
July | 497.00000 | 24.38903 | 53.73359 | -0.2136 | 7.35263 |
August | 514.00000 | 24.25630 | 50.20694 | -0.2769 | 7.93752 |
September | 485.00000 | 24.03436 | 45.70550 | -0.4114 | 11.26302 |
October | 502.00000 | 22.94649 | 35.68499 | 0.08194 | 8.01236 |
November | 489.00000 | 21.75876 | 31.31967 | -0.2818 | 9.34569 |
December | 497.00000 | 20.43845 | 26.04870 | -0.7004 | 18.08263 |
Annual Sum or Average | 5943.00000 | 22.61524 | 35.61878 | -0.3793 | 12.06710 |
Minimum of Months | 454.00000 | 20.43845 | 22.43881 | -0.7215 | 7.35263 |
Maximum of Months | 514.00000 | 24.38903 | 53.73359 | 0.08194 | 19.42115 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.10391 | 22.61826 | -0.8334 | 21.85168 |
February | 454.00000 | 20.23717 | 22.42779 | -0.7796 | 20.04218 |
March | 514.00000 | 21.49583 | 28.35556 | -0.3605 | 10.94492 |
April | 485.00000 | 22.38205 | 30.32705 | -0.0911 | 7.92532 |
May | 508.00000 | 23.60607 | 34.70672 | -0.6549 | 17.07982 |
June | 496.00000 | 24.16608 | 45.08995 | -0.3124 | 9.10159 |
July | 497.00000 | 24.44351 | 53.40554 | -0.1451 | 7.12440 |
August | 514.00000 | 24.26987 | 50.11289 | -0.2428 | 7.80259 |
September | 485.00000 | 23.74702 | 46.56060 | -0.5257 | 13.66185 |
October | 502.00000 | 22.18932 | 37.04507 | -0.1086 | 7.34472 |
November | 489.00000 | 21.12806 | 32.04125 | -0.4352 | 10.22319 |
December | 497.00000 | 20.19305 | 25.96964 | -0.7677 | 19.45921 |
Annual Sum or Average | 5943.00000 | 22.34718 | 35.81857 | -0.4358 | 12.66429 |
Minimum of Months | 454.00000 | 20.10391 | 22.42779 | -0.8334 | 7.12440 |
Maximum of Months | 514.00000 | 24.44351 | 53.40554 | -0.0911 | 21.85168 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.73860 | 23.91601 | -1.0023 | 28.80310 |
February | 454.00000 | 19.79092 | 23.73222 | -0.9774 | 27.83273 |
March | 514.00000 | 20.59111 | 30.28134 | -0.6644 | 18.61618 |
April | 485.00000 | 21.14416 | 33.30326 | -0.4503 | 11.73647 |
May | 508.00000 | 22.83137 | 36.92042 | -0.9936 | 28.36988 |
June | 496.00000 | 23.88276 | 46.27722 | -0.5008 | 12.07082 |
July | 497.00000 | 24.26567 | 54.32624 | -0.2834 | 7.62897 |
August | 514.00000 | 24.01368 | 51.19864 | -0.4192 | 9.81061 |
September | 485.00000 | 23.10019 | 48.86929 | -0.8156 | 22.32270 |
October | 502.00000 | 21.03229 | 40.35823 | -0.4386 | 12.33455 |
November | 489.00000 | 20.25081 | 34.62490 | -0.7190 | 18.28175 |
December | 497.00000 | 19.75137 | 27.27679 | -0.9650 | 27.51258 |
Annual Sum or Average | 5943.00000 | 21.71643 | 37.68667 | -0.6837 | 18.71469 |
Minimum of Months | 454.00000 | 19.73860 | 23.73222 | -1.0023 | 7.62897 |
Maximum of Months | 514.00000 | 24.26567 | 54.32624 | -0.2834 | 28.80310 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.80900 | 23.63773 | -0.9687 | 27.44479 |
February | 454.00000 | 19.88186 | 23.45836 | -0.9308 | 26.07698 |
March | 514.00000 | 20.75233 | 29.73965 | -0.5833 | 16.68731 |
April | 485.00000 | 21.79168 | 31.85461 | -0.2598 | 10.43665 |
May | 508.00000 | 23.31188 | 35.36619 | -0.7662 | 21.03305 |
June | 496.00000 | 24.09547 | 45.25088 | -0.3458 | 9.83367 |
July | 497.00000 | 24.41602 | 53.32650 | -0.1443 | 7.24116 |
August | 514.00000 | 24.12785 | 50.41859 | -0.2982 | 8.66805 |
September | 485.00000 | 23.46508 | 47.35367 | -0.6285 | 17.21426 |
October | 502.00000 | 21.42651 | 39.08796 | -0.3219 | 10.71591 |
November | 489.00000 | 20.36333 | 34.08642 | -0.6799 | 17.12651 |
December | 497.00000 | 19.80308 | 27.05875 | -0.9455 | 26.67485 |
Annual Sum or Average | 5943.00000 | 21.95404 | 36.81406 | -0.5703 | 16.52909 |
Minimum of Months | 454.00000 | 19.80308 | 23.45836 | -0.9687 | 7.24116 |
Maximum of Months | 514.00000 | 24.41602 | 53.32650 | -0.1443 | 27.44479 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.07703 | 23.51458 | -0.8602 | 24.24212 |
February | 454.00000 | 20.14982 | 23.29858 | -0.8261 | 23.86737 |
March | 514.00000 | 21.37681 | 29.05885 | -0.4119 | 13.97245 |
April | 485.00000 | 21.95358 | 31.65630 | -0.2270 | 10.36159 |
May | 508.00000 | 23.20695 | 35.81434 | -0.8303 | 23.35072 |
June | 496.00000 | 23.93880 | 45.91935 | -0.4483 | 11.76519 |
July | 497.00000 | 24.34061 | 53.82425 | -0.2160 | 7.77768 |
August | 514.00000 | 24.16426 | 50.38555 | -0.3014 | 8.76066 |
September | 485.00000 | 23.72737 | 46.67917 | -0.5223 | 15.00977 |
October | 502.00000 | 22.10267 | 37.68925 | -0.1415 | 10.17005 |
November | 489.00000 | 20.94890 | 33.24471 | -0.5169 | 14.37340 |
December | 497.00000 | 20.00623 | 26.94299 | -0.8576 | 23.83106 |
Annual Sum or Average | 5943.00000 | 22.18286 | 36.59712 | -0.5113 | 15.57067 |
Minimum of Months | 454.00000 | 20.00623 | 23.29858 | -0.8602 | 7.77768 |
Maximum of Months | 514.00000 | 24.34061 | 53.82425 | -0.1415 | 24.24212 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 19.86603 | 23.47981 | -0.9401 | 26.30669 |
February | 454.00000 | 19.98812 | 23.23258 | -0.8819 | 24.30353 |
March | 514.00000 | 21.00432 | 29.24157 | -0.5105 | 14.71221 |
April | 485.00000 | 21.79174 | 31.63736 | -0.2506 | 10.02394 |
May | 508.00000 | 23.17395 | 35.66355 | -0.8017 | 23.05223 |
June | 496.00000 | 24.03201 | 45.46418 | -0.3493 | 10.59516 |
July | 497.00000 | 24.39520 | 53.51094 | -0.1480 | 7.52631 |
August | 514.00000 | 24.17123 | 50.31306 | -0.2692 | 8.60762 |
September | 485.00000 | 23.38439 | 47.62162 | -0.6506 | 18.17860 |
October | 502.00000 | 21.47450 | 38.79839 | -0.2999 | 10.23670 |
November | 489.00000 | 20.54708 | 33.63028 | -0.6147 | 15.16377 |
December | 497.00000 | 19.88355 | 26.85295 | -0.8905 | 24.56618 |
Annual Sum or Average | 5943.00000 | 21.99302 | 36.71484 | -0.5482 | 16.04812 |
Minimum of Months | 454.00000 | 19.86603 | 23.23258 | -0.9401 | 7.52631 |
Maximum of Months | 514.00000 | 24.39520 | 53.51094 | -0.1480 | 26.30669 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.701608E+09 | 3322.12 | 17-JAN-08:50 | 63.31 | 0.319525E+10 | 0.00 | 0.389686E+10 | 0.39 | 4.56 | 08-JAN-00:50 | 0.00 | 0.00 |
February | 0.666541E+09 | 3197.98 | 28-FEB-16:20 | 59.94 | 0.303529E+10 | 0.00 | 0.370183E+10 | 0.41 | 4.56 | 28-FEB-14:10 | 0.00 | 0.00 |
March | 0.749749E+10 | 96462.26 | 15-MAR-15:20 | 98.61 | 0.455782E+11 | 0.00 | 0.530757E+11 | 0.66 | 7.27 | 15-MAR-12:50 | 0.00 | 0.00 |
April | 0.450980E+10 | 65179.66 | 08-APR-13:40 | 86.41 | 0.219759E+11 | 0.00 | 0.264857E+11 | 0.56 | 6.46 | 08-APR-13:40 | 0.00 | 0.00 |
May | 0.314260E+11 | 95710.28 | 10-MAY-12:40 | 220.47 | 0.177208E+12 | 0.00 | 0.208634E+12 | 1.53 | 7.33 | 16-MAY-14:50 | 0.00 | 0.00 |
June | 0.964698E+11 | 151823.91 | 27-JUN-07:40 | 455.18 | 0.615338E+12 | 0.00 | 0.711808E+12 | 3.70 | 7.74 | 29-JUN-05:02 | 0.00 | 0.00 |
July | 0.143354E+12 | 188729.42 | 20-JUL-05:05 | 587.49 | 0.945778E+12 | 0.00 | 0.108913E+13 | 4.80 | 7.74 | 05-JUL-05:04 | 0.00 | 0.00 |
August | 0.126700E+12 | 179416.74 | 15-AUG-05:03 | 576.83 | 0.835449E+12 | 0.00 | 0.962149E+12 | 4.63 | 7.76 | 28-AUG-05:02 | 0.00 | 0.00 |
September | 0.650565E+11 | 136963.05 | 14-SEP-05:03 | 335.51 | 0.410071E+12 | 0.00 | 0.475128E+12 | 2.66 | 7.81 | 15-SEP-05:04 | 0.00 | 0.00 |
October | 0.116341E+11 | 90668.66 | 11-OCT-15:00 | 115.97 | 0.610212E+11 | 0.00 | 0.726553E+11 | 0.75 | 7.29 | 11-OCT-15:00 | 0.00 | 0.00 |
November | 0.251210E+10 | 55024.15 | 16-NOV-13:00 | 65.45 | 0.113570E+11 | 0.00 | 0.138691E+11 | 0.41 | 5.89 | 16-NOV-13:00 | 0.00 | 0.00 |
December | 0.762690E+09 | 12973.73 | 01-DEC-06:03 | 68.02 | 0.347289E+10 | 0.00 | 0.423558E+10 | 0.42 | 4.56 | 15-DEC-21:50 | 0.00 | 0.00 |
Annual Sum or Average | 0.491291E+12 | 2733.19 | 0.313348E+13 | 0.00 | 0.362477E+13 | 1.75 | 0.00 | 0.00 | ||||
Minimum of Months | 0.666541E+09 | 3197.98 | 59.94 | 0.303529E+10 | 0.00 | 0.370183E+10 | 0.39 | 4.56 | 0.00 | 0.00 | ||
Maximum of Months | 0.143354E+12 | 188729.42 | 587.49 | 0.945778E+12 | 0.00 | 0.108913E+13 | 4.80 | 7.81 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 |
June | 0.222838E+11 | 151823.91 | 27-JUN-07:40 | 61.67 | 0.156662E+12 | 0.00 | 0.178945E+12 | 0.60 | 7.74 | 29-JUN-05:02 | 0.00 | 0.00 |
July | 0.511351E+11 | 188729.42 | 20-JUL-05:05 | 132.18 | 0.356546E+12 | 0.00 | 0.407681E+12 | 1.24 | 7.74 | 05-JUL-05:04 | 0.00 | 0.00 |
August | 0.387220E+11 | 179416.74 | 15-AUG-05:03 | 101.66 | 0.272797E+12 | 0.00 | 0.311519E+12 | 0.96 | 7.76 | 28-AUG-05:02 | 0.00 | 0.00 |
September | 0.108815E+11 | 136963.05 | 14-SEP-05:03 | 30.62 | 0.774156E+11 | 0.00 | 0.882971E+11 | 0.30 | 7.81 | 15-SEP-05:04 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.123022E+12 | 326.13 | 0.863420E+12 | 0.00 | 0.986442E+12 | 0.26 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.511351E+11 | 188729.42 | 132.18 | 0.356546E+12 | 0.00 | 0.407681E+12 | 1.24 | 7.81 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.791492E+10 | 744.00 | 7505.05 | 11-JAN-16:00 | 205026.99 | 17-JAN-13:20 | 21.45 | 18.33 | 14.19 |
February | 0.120888E+11 | 672.00 | 29181.36 | 22-FEB-18:00 | 334381.89 | 15-FEB-11:10 | 24.22 | 18.33 | 14.19 |
March | 0.417012E+11 | 744.00 | 49248.27 | 12-MAR-12:25 | 587128.61 | 31-MAR-24:00 | 27.73 | 18.70 | 14.18 |
April | 0.771647E+11 | 720.00 | 49248.27 | 06-APR-13:50 | 636883.86 | 07-APR-14:10 | 30.64 | 18.69 | 14.19 |
May | 0.659915E+11 | 744.00 | 49248.27 | 02-MAY-11:00 | 328653.16 | 31-MAY-24:00 | 22.78 | 19.03 | 14.19 |
June | 0.114797E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 474397.91 | 30-JUN-23:50 | 29.35 | 22.48 | 14.19 |
July | 0.131182E+12 | 744.00 | 49248.27 | 01-JUL-00:10 | 634343.87 | 31-JUL-23:33 | 36.50 | 26.50 | 14.19 |
August | 0.131396E+12 | 744.00 | 49248.27 | 01-AUG-00:05 | 684570.51 | 18-AUG-16:00 | 39.15 | 26.39 | 14.19 |
September | 0.893302E+11 | 720.00 | 49248.27 | 01-SEP-10:00 | 313336.52 | 30-SEP-24:00 | 24.06 | 20.17 | 14.19 |
October | 0.582022E+11 | 744.00 | 49248.27 | 01-OCT-09:30 | 452531.29 | 31-OCT-24:00 | 25.12 | 18.66 | 14.16 |
November | 0.489444E+11 | 720.00 | 49248.27 | 04-NOV-10:30 | 485669.00 | 22-NOV-13:30 | 27.63 | 18.54 | 14.16 |
December | 0.329838E+11 | 744.00 | 49248.27 | 01-DEC-09:00 | 599709.19 | 01-DEC-13:10 | 29.91 | 18.34 | 14.18 |
Annual Sum or Average | 0.811697E+12 | 8760.00 | 28.25 | 20.37 | 14.18 | ||||
Minimum of Months | 0.791492E+10 | 672.00 | 7505.05 | 205026.99 | 21.45 | 18.33 | 14.16 | ||
Maximum of Months | 0.131396E+12 | 744.00 | 49248.27 | 684570.51 | 39.15 | 26.50 | 14.19 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 228260.53 | 27-JAN-06:40 | 21.01 | 20.99 | 1.04 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 228218.00 | 09-FEB-15:20 | 20.97 | 20.96 | 0.85 |
March | 0.525335E+09 | 27.62 | 18909.01 | 14-MAR-11:40 | 964403.52 | 15-MAR-13:10 | 21.12 | 21.04 | 3.69 |
April | 20298362.51 | 18.00 | 1155.04 | 08-APR-13:50 | 495364.59 | 07-APR-14:00 | 21.08 | 21.03 | 3.83 |
May | 0.752437E+09 | 152.64 | 18909.01 | 10-MAY-12:10 | 1046186.92 | 31-MAY-15:30 | 21.49 | 21.17 | 17.41 |
June | 0.119286E+11 | 407.35 | 18909.01 | 01-JUN-13:10 | 1196960.75 | 27-JUN-07:40 | 22.73 | 21.63 | 39.28 |
July | 0.257901E+11 | 549.51 | 18909.01 | 01-JUL-14:00 | 1378020.82 | 05-JUL-16:00 | 24.03 | 22.42 | 49.65 |
August | 0.185642E+11 | 495.47 | 18909.01 | 01-AUG-12:00 | 1394733.74 | 14-AUG-10:20 | 23.24 | 21.78 | 47.66 |
September | 0.689242E+10 | 287.37 | 18909.01 | 08-SEP-11:40 | 1158532.48 | 22-SEP-13:20 | 22.22 | 21.48 | 28.80 |
October | 0.146075E+09 | 63.60 | 3068.00 | 11-OCT-14:10 | 994081.68 | 11-OCT-14:10 | 21.22 | 21.11 | 8.01 |
November | 18980807.66 | 14.59 | 707.23 | 16-NOV-13:00 | 372823.57 | 16-NOV-13:00 | 21.02 | 20.99 | 2.32 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 228230.97 | 29-DEC-21:10 | 20.99 | 20.98 | 0.88 |
Annual Sum or Average | 0.646384E+11 | 2016.15 | 21.77 | 21.30 | 17.07 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 228218.00 | 20.97 | 20.96 | 0.85 | ||
Maximum of Months | 0.257901E+11 | 549.51 | 18909.01 | 1394733.74 | 24.03 | 22.42 | 49.65 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 21.01 | 21.01 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 20.97 | 20.97 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 21.12 | 21.12 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.08 | 21.08 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 01-MAY-00:03 | 21.49 | 21.49 | 0.00 |
June | 0.425772E+10 | 62.85 | 18909.01 | 01-JUN-15:30 | 1196960.75 | 27-JUN-07:40 | 22.73 | 22.46 | 5.57 |
July | 0.101026E+11 | 148.41 | 18909.01 | 03-JUL-13:10 | 1378020.82 | 05-JUL-16:00 | 24.03 | 23.40 | 12.58 |
August | 0.599302E+10 | 88.04 | 18909.01 | 01-AUG-13:00 | 1394733.74 | 14-AUG-10:20 | 23.24 | 22.85 | 7.58 |
September | 0.206713E+10 | 30.37 | 18909.01 | 08-SEP-13:20 | 1158532.48 | 22-SEP-13:20 | 22.22 | 22.09 | 2.70 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.22 | 21.22 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.02 | 21.02 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 20.99 | 20.99 | 0.00 |
Annual Sum or Average | 0.224205E+11 | 329.67 | 21.77 | 21.65 | 2.39 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.97 | 20.97 | 0.00 | ||
Maximum of Months | 0.101026E+11 | 148.41 | 18909.01 | 1394733.74 | 24.03 | 23.40 | 12.58 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.395431E+12 | 0.00 | 590.14 | 1942445.39 | 02-JAN-04:01 | 0.00 | 34.02 | 71.28 | 0.83 | 0.00 | 0.05 | 0.64 | 02-JAN-04:01 |
February | 0.341784E+12 | 0.00 | 539.80 | 1755590.72 | 27-FEB-05:01 | 0.00 | 34.14 | 72.18 | 0.80 | 0.00 | 0.05 | 0.58 | 27-FEB-05:01 |
March | 0.118730E+12 | 0.00 | 431.00 | 1573581.37 | 06-MAR-06:01 | 0.00 | 29.23 | 58.16 | 0.24 | 0.00 | 0.01 | 0.52 | 06-MAR-06:01 |
April | 0.290668E+11 | 0.00 | 246.31 | 1290503.64 | 05-APR-04:01 | 0.00 | 24.77 | 43.39 | 0.05 | 0.00 | 0.00 | 0.42 | 05-APR-04:01 |
May | 0.646785E+09 | 0.00 | 39.97 | 97251.04 | 12-MAY-05:03 | 0.00 | 23.08 | 26.12 | 0.00 | 0.00 | 0.00 | 0.03 | 12-MAY-05:03 |
June | 14601997.69 | 0.00 | 2.67 | 15197.32 | 14-JUN-05:03 | 0.00 | 22.76 | 22.97 | 0.00 | 0.00 | 0.00 | 0.00 | 14-JUN-05:03 |
July | 4931.48 | 0.00 | 0.33 | 4.67 | 15-JUL-07:50 | 0.00 | 22.73 | 22.76 | 0.00 | 0.00 | 0.00 | 0.00 | 15-JUL-07:50 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 22.73 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.591142E+09 | 0.00 | 26.26 | 114746.33 | 30-SEP-05:03 | 0.00 | 22.47 | 24.55 | 0.00 | 0.00 | 0.00 | 0.04 | 30-SEP-05:03 |
October | 0.195701E+11 | 0.00 | 221.65 | 1345942.18 | 30-OCT-04:01 | 0.00 | 23.66 | 39.99 | 0.03 | 0.00 | 0.00 | 0.44 | 30-OCT-04:01 |
November | 0.805775E+11 | 0.00 | 397.15 | 1288631.29 | 20-NOV-05:01 | 0.00 | 26.28 | 55.74 | 0.15 | 0.00 | 0.01 | 0.42 | 20-NOV-05:01 |
December | 0.323268E+12 | 0.00 | 579.42 | 1656053.17 | 13-DEC-06:01 | 0.00 | 32.99 | 70.40 | 0.67 | 0.00 | 0.04 | 0.54 | 13-DEC-06:01 |
Annual Sum or Average | 0.130968E+13 | 0.00 | 3074.71 | 0.00 | 26.54 | 44.04 | 0.23 | 0.00 | 0.01 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.47 | 22.73 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.395431E+12 | 0.00 | 590.14 | 1942445.39 | 0.00 | 34.14 | 72.18 | 0.83 | 0.00 | 0.05 | 0.64 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 21.45 | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 24.22 | 24.22 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.73 | 27.73 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 30.64 | 30.64 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 22.78 | 22.78 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 29.35 | 29.35 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 36.50 | 36.50 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 39.15 | 39.15 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 24.06 | 24.06 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 25.12 | 25.12 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.63 | 27.63 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 29.91 | 29.91 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 28.25 | 28.25 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.45 | 21.45 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.15 | 39.15 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 21219853.21 | 0.00 | 41.86 | 21219853.21 | 0.00 | 0.00 | 0.00 | 0.00 | 2568.54 | 06-JAN-13:10 | 2568.54 | 06-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 18144811.43 | 0.00 | 37.47 | 18144811.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2027.07 | 03-FEB-13:10 | 2027.07 | 03-FEB-13:10 | 0.00 | 0.00 | 0.00 |
March | 0.554183E+10 | 0.00 | 59.20 | 0.538861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 98338.81 | 14-MAR-13:10 | 94050.20 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 |
April | 0.220645E+10 | 0.00 | 56.46 | 0.220645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47445.20 | 07-APR-14:00 | 47445.20 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.170947E+11 | 0.00 | 212.38 | 0.168630E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 90308.28 | 10-MAY-14:30 | 82330.02 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.776827E+11 | 0.00 | 435.75 | 0.614678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 217873.63 | 27-JUN-05:03 | 111444.23 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.139985E+12 | 0.00 | 562.20 | 0.100912E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 274570.57 | 20-JUL-05:03 | 114942.37 | 21-JUL-04:12 | 0.00 | 0.00 | 0.00 |
August | 0.122247E+12 | 0.00 | 556.83 | 0.950999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 267032.39 | 14-AUG-04:23 | 120514.16 | 14-AUG-14:40 | 0.00 | 0.00 | 0.00 |
September | 0.466708E+11 | 0.00 | 323.28 | 0.370478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 188044.40 | 14-SEP-05:03 | 98088.56 | 21-SEP-15:30 | 0.00 | 0.00 | 0.00 |
October | 0.610909E+10 | 0.00 | 95.90 | 0.610310E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71882.62 | 11-OCT-15:00 | 71882.62 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.101221E+10 | 0.00 | 35.00 | 0.101221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54115.21 | 27-NOV-06:02 | 54115.21 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 14708763.43 | 0.00 | 34.92 | 14708763.43 | 0.00 | 0.00 | 0.00 | 0.00 | 5188.53 | 15-DEC-08:10 | 5188.53 | 15-DEC-08:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418603E+12 | 0.00 | 2451.24 | 0.326155E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 14708763.43 | 0.00 | 34.92 | 14708763.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2027.07 | 2027.07 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.139985E+12 | 0.00 | 562.20 | 0.100912E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 274570.57 | 120514.16 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 9486165.94 | 0.00 | 38.51 | 9486165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 1685.69 | 10-JAN-14:50 | 1685.69 | 10-JAN-14:50 | 0.00 | 0.00 | 0.00 |
February | 10410426.43 | 0.00 | 40.22 | 10410426.43 | 0.00 | 0.00 | 0.00 | 0.00 | 2128.94 | 28-FEB-11:30 | 2128.94 | 28-FEB-11:30 | 0.00 | 0.00 | 0.00 |
March | 0.354208E+11 | 0.00 | 63.72 | 0.343786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 676442.02 | 15-MAR-14:10 | 676442.02 | 15-MAR-14:10 | 0.00 | 0.00 | 0.00 |
April | 0.135248E+11 | 0.00 | 52.51 | 0.135248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 301395.44 | 07-APR-14:00 | 301395.44 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.141384E+12 | 0.00 | 203.25 | 0.139494E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 799707.53 | 24-MAY-05:03 | 730283.35 | 23-MAY-14:30 | 0.00 | 0.00 | 0.00 |
June | 0.626989E+12 | 0.00 | 393.83 | 0.502479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2047684.13 | 27-JUN-05:03 | 954374.61 | 12-JUN-15:20 | 0.00 | 0.00 | 0.00 |
July | 0.107437E+13 | 0.00 | 455.32 | 0.790909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2793507.06 | 20-JUL-03:02 | 1201111.66 | 20-JUL-03:02 | 0.00 | 0.00 | 0.00 |
August | 0.890325E+12 | 0.00 | 436.98 | 0.713097E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2437883.53 | 14-AUG-05:02 | 1043877.52 | 09-AUG-15:30 | 0.00 | 0.00 | 0.00 |
September | 0.389991E+12 | 0.00 | 309.42 | 0.312889E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1844754.48 | 16-SEP-05:03 | 912255.97 | 21-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.437743E+11 | 0.00 | 96.42 | 0.437536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 554430.73 | 11-OCT-15:00 | 554430.73 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.582241E+10 | 0.00 | 38.25 | 0.582241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 155006.71 | 16-NOV-13:10 | 155006.71 | 16-NOV-13:10 | 0.00 | 0.00 | 0.00 |
December | 2388570.91 | 0.00 | 48.12 | 2388570.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.24 | 22-DEC-13:40 | 1301.24 | 22-DEC-13:40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.322162E+13 | 0.00 | 2176.57 | 0.255637E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2388570.91 | 0.00 | 38.25 | 2388570.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1301.24 | 1301.24 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.107437E+13 | 0.00 | 455.32 | 0.790909E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 2793507.06 | 1201111.66 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 11146237.06 | 0.00 | 36.72 | 11146237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 364.74 | 06-JAN-13:10 | 364.74 | 06-JAN-13:10 | 0.00 | 0.00 | 0.00 |
February | 11402298.96 | 0.00 | 26.30 | 11402298.96 | 0.00 | 0.00 | 0.00 | 0.00 | 509.10 | 14-FEB-05:31 | 509.10 | 14-FEB-05:31 | 0.00 | 0.00 | 0.00 |
March | 0.376529E+10 | 0.00 | 77.82 | 0.374893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85127.58 | 15-MAR-14:00 | 85127.58 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.124957E+10 | 0.00 | 66.95 | 0.124957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27653.86 | 07-APR-14:00 | 27653.86 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.140105E+11 | 0.00 | 196.26 | 0.138776E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 91921.60 | 10-MAY-14:50 | 83984.86 | 10-MAY-14:40 | 0.00 | 0.00 | 0.00 |
June | 0.688758E+11 | 0.00 | 386.68 | 0.548712E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 282258.96 | 27-JUN-15:00 | 123017.67 | 12-JUN-14:00 | 0.00 | 0.00 | 0.00 |
July | 0.119937E+12 | 0.00 | 454.37 | 0.882900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 298289.02 | 20-JUL-03:02 | 131052.35 | 16-JUL-16:01 | 0.00 | 0.00 | 0.00 |
August | 0.967205E+11 | 0.00 | 432.42 | 0.771897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 260286.99 | 14-AUG-05:02 | 127251.25 | 09-AUG-15:20 | 0.00 | 0.00 | 0.00 |
September | 0.383610E+11 | 0.00 | 302.41 | 0.306610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 167252.54 | 15-SEP-12:40 | 106338.05 | 21-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.358841E+10 | 0.00 | 98.03 | 0.358841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51927.87 | 11-OCT-15:00 | 51927.87 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.584440E+09 | 0.00 | 48.42 | 0.584440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 14807.36 | 27-NOV-06:02 | 14807.36 | 27-NOV-06:02 | 0.00 | 0.00 | 0.00 |
December | 7099229.82 | 0.00 | 24.83 | 7099229.82 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.49 | 26-DEC-06:20 | 1378.49 | 26-DEC-06:20 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.347122E+12 | 0.00 | 2151.20 | 0.274091E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 7099229.82 | 0.00 | 24.83 | 7099229.82 | 0.00 | 0.00 | 0.00 | 0.00 | 364.74 | 364.74 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.119937E+12 | 0.00 | 454.37 | 0.882900E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 298289.02 | 131052.35 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 170747.40 | 0.00 | 1.02 | 170747.40 | 0.00 | 0.00 | 0.00 | 0.00 | 77.35 | 03-JAN-12:00 | 77.35 | 03-JAN-12:00 | 0.00 | 0.00 | 0.00 |
February | 2859.21 | 0.00 | 0.19 | 2859.21 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 27-FEB-16:40 | 4.66 | 27-FEB-16:40 | 0.00 | 0.00 | 0.00 |
March | 0.303668E+10 | 0.00 | 28.03 | 0.302932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51731.76 | 15-MAR-14:00 | 51731.76 | 15-MAR-14:00 | 0.00 | 0.00 | 0.00 |
April | 0.513332E+09 | 0.00 | 14.61 | 0.513332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22421.94 | 07-APR-14:00 | 22421.94 | 07-APR-14:00 | 0.00 | 0.00 | 0.00 |
May | 0.727253E+10 | 0.00 | 114.92 | 0.723695E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72379.33 | 24-MAY-04:03 | 49748.06 | 10-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.369770E+11 | 0.00 | 293.62 | 0.310895E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 122851.08 | 27-JUN-05:05 | 68101.58 | 12-JUN-03:02 | 0.00 | 0.00 | 0.00 |
July | 0.719508E+11 | 0.00 | 366.98 | 0.539763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163265.15 | 20-JUL-03:02 | 78713.74 | 21-JUL-05:03 | 0.00 | 0.00 | 0.00 |
August | 0.628733E+11 | 0.00 | 376.48 | 0.511881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 156240.97 | 14-AUG-03:02 | 73304.61 | 14-AUG-07:50 | 0.00 | 0.00 | 0.00 |
September | 0.266115E+11 | 0.00 | 238.14 | 0.223476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115199.47 | 16-SEP-05:03 | 61923.06 | 25-SEP-13:10 | 0.00 | 0.00 | 0.00 |
October | 0.256818E+10 | 0.00 | 56.99 | 0.255585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56042.12 | 26-OCT-05:02 | 43189.27 | 11-OCT-13:10 | 0.00 | 0.00 | 0.00 |
November | 0.508483E+09 | 0.00 | 12.30 | 0.508483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 47859.99 | 27-NOV-06:15 | 47859.99 | 27-NOV-06:15 | 0.00 | 0.00 | 0.00 |
December | 1539165.23 | 0.00 | 0.15 | 1539165.23 | 0.00 | 0.00 | 0.00 | 0.00 | 8400.41 | 01-DEC-06:03 | 8400.41 | 01-DEC-06:03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.212313E+12 | 0.00 | 1503.44 | 0.172447E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2859.21 | 0.00 | 0.15 | 2859.21 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 4.66 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.719508E+11 | 0.00 | 376.48 | 0.539763E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 163265.15 | 78713.74 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.314274E+12 | 0.793819E+11 | 744.00 | 0.314265E+12 | 8341168.39 | 0.00 | 0.34 | 17-JAN-13:10 | 0.29 | 30-JAN-07:03 | 123602.70 | 18-JAN-22:10 | 123602.70 | 18-JAN-22:10 | 796.57 | 02-JAN-07:10 | 36793.97 | 17-JAN-13:10 | 0.00 |
February | 0.503459E+12 | 0.120729E+12 | 672.00 | 0.503459E+12 | 0.00 | 0.00 | 0.56 | 22-FEB-11:40 | 0.51 | 06-FEB-07:03 | 215190.99 | 17-FEB-22:03 | 215190.99 | 17-FEB-22:03 | 0.00 | 07-FEB-17:50 | 57216.06 | 15-FEB-09:20 | 0.00 |
March | 0.810131E+12 | 0.187734E+12 | 744.00 | 0.809620E+12 | 0.511582E+09 | 0.00 | 0.93 | 31-MAR-24:00 | 0.72 | 06-MAR-07:05 | 393816.41 | 31-MAR-24:00 | 393816.41 | 31-MAR-24:00 | 7517.66 | 16-MAR-16:10 | 100400.44 | 15-MAR-14:00 | 0.00 |
April | 0.102493E+13 | 0.229142E+12 | 720.00 | 0.102491E+13 | 24376070.39 | 0.00 | 1.00 | 07-APR-14:00 | 0.36 | 30-APR-23:55 | 399798.27 | 21-APR-21:03 | 399798.27 | 21-APR-21:03 | 1980.49 | 12-APR-16:10 | 113403.76 | 08-APR-13:00 | 0.00 |
May | 0.330033E+12 | 0.843605E+11 | 744.00 | 0.329078E+12 | 0.955802E+09 | 0.00 | 0.54 | 31-MAY-24:00 | 0.31 | 13-MAY-06:10 | 212252.46 | 31-MAY-24:00 | 211506.14 | 31-MAY-24:00 | 6202.37 | 10-MAY-17:50 | 52678.08 | 31-MAY-23:30 | 0.00 |
June | 0.563621E+12 | 0.151590E+12 | 720.00 | 0.558843E+12 | 0.477829E+10 | 0.00 | 0.76 | 30-JUN-23:13 | 0.53 | 10-JUN-06:30 | 303561.71 | 30-JUN-24:00 | 303561.71 | 30-JUN-24:00 | 11594.02 | 27-JUN-14:00 | 83414.68 | 27-JUN-13:00 | 0.00 |
July | 0.833539E+12 | 0.240585E+12 | 744.00 | 0.826089E+12 | 0.745051E+10 | 0.00 | 0.96 | 31-JUL-23:15 | 0.73 | 07-JUL-06:30 | 396432.65 | 31-JUL-23:53 | 395763.55 | 31-JUL-23:57 | 11346.92 | 20-JUL-21:00 | 119082.08 | 21-JUL-14:00 | 0.00 |
August | 0.107461E+13 | 0.297610E+12 | 744.00 | 0.106981E+13 | 0.480171E+10 | 0.00 | 1.00 | 01-AUG-15:30 | 0.36 | 31-AUG-24:00 | 415613.61 | 26-AUG-16:03 | 406582.56 | 04-AUG-21:02 | 13042.41 | 26-AUG-16:00 | 139812.23 | 10-AUG-14:00 | 0.00 |
September | 0.327636E+12 | 0.858204E+11 | 720.00 | 0.323754E+12 | 0.388180E+10 | 0.00 | 0.54 | 30-SEP-24:00 | 0.31 | 06-SEP-06:10 | 211241.40 | 30-SEP-24:00 | 211241.40 | 30-SEP-24:00 | 8747.07 | 15-SEP-15:10 | 50310.73 | 30-SEP-24:00 | 0.00 |
October | 0.574726E+12 | 0.137867E+12 | 744.00 | 0.573900E+12 | 0.826598E+09 | 0.00 | 0.74 | 31-OCT-24:00 | 0.53 | 03-OCT-06:10 | 303934.12 | 31-OCT-24:00 | 303934.12 | 31-OCT-24:00 | 4960.94 | 12-OCT-16:10 | 68894.10 | 31-OCT-24:00 | 0.00 |
November | 0.789502E+12 | 0.181889E+12 | 720.00 | 0.789479E+12 | 22472993.54 | 0.00 | 0.78 | 26-NOV-14:00 | 0.73 | 01-NOV-06:10 | 309035.73 | 16-NOV-17:00 | 308916.21 | 06-NOV-22:03 | 4987.13 | 16-NOV-18:40 | 82418.16 | 05-NOV-14:00 | 0.00 |
December | 0.105404E+13 | 0.233517E+12 | 744.00 | 0.105402E+13 | 11731143.14 | 0.00 | 0.95 | 05-DEC-22:01 | 0.90 | 11-DEC-07:05 | 400241.59 | 21-DEC-22:02 | 400241.59 | 21-DEC-22:02 | 2893.75 | 01-DEC-13:20 | 92131.43 | 01-DEC-11:00 | 0.00 |
Annual Sum or Average | 0.820050E+13 | 0.203022E+13 | 8760.00 | 0.817723E+13 | 0.232732E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.314274E+12 | 0.793819E+11 | 672.00 | 0.314265E+12 | 0.00 | 0.00 | 0.34 | 0.29 | 123602.70 | 123602.70 | 0.00 | 36793.97 | 0.00 | ||||||
Maximum of Months | 0.107461E+13 | 0.297610E+12 | 744.00 | 0.106981E+13 | 0.745051E+10 | 0.00 | 1.00 | 0.90 | 415613.61 | 406582.56 | 13042.41 | 139812.23 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.271972E+10 | 0.763598E+09 | 744.00 | 0.271970E+10 | 24895.17 | 0.00 | 0.27 | 15-JAN-16:30 | 0.01 | 30-JAN-07:03 | 2049.86 | 15-JAN-16:30 | 2049.86 | 15-JAN-16:30 | 9.39 | 02-JAN-07:10 | 531.04 | 15-JAN-16:30 | 0.00 |
February | 0.731981E+10 | 0.189278E+10 | 672.00 | 0.731981E+10 | -0.0 | 0.00 | 0.51 | 28-FEB-17:00 | 0.27 | 07-FEB-07:03 | 4022.24 | 28-FEB-17:00 | 4022.24 | 28-FEB-17:00 | 0.00 | 01-FEB-15:10 | 1003.09 | 28-FEB-17:00 | 0.00 |
March | 0.147066E+11 | 0.353010E+10 | 744.00 | 0.146848E+11 | 21786946.69 | 0.00 | 0.82 | 31-MAR-24:00 | 0.57 | 06-MAR-07:05 | 7533.36 | 31-MAR-24:00 | 7533.36 | 31-MAR-24:00 | 255.76 | 16-MAR-16:10 | 1956.38 | 15-MAR-14:10 | 0.00 |
April | 0.197093E+11 | 0.443131E+10 | 720.00 | 0.197065E+11 | 2854652.71 | 0.00 | 0.94 | 23-APR-15:05 | 0.30 | 30-APR-23:55 | 8521.44 | 02-APR-17:45 | 8521.44 | 02-APR-17:45 | 99.13 | 12-APR-16:10 | 2193.07 | 07-APR-14:00 | 0.00 |
May | 0.552367E+10 | 0.141366E+10 | 744.00 | 0.548630E+10 | 37374528.35 | 0.00 | 0.47 | 31-MAY-24:00 | 0.18 | 12-MAY-06:50 | 4030.03 | 31-MAY-24:00 | 4022.83 | 31-MAY-24:00 | 230.87 | 17-MAY-15:20 | 980.82 | 31-MAY-24:00 | 0.00 |
June | 0.107963E+11 | 0.285943E+10 | 720.00 | 0.106079E+11 | 0.188460E+09 | 0.00 | 0.68 | 30-JUN-24:00 | 0.42 | 10-JUN-06:40 | 5898.95 | 30-JUN-24:00 | 5898.95 | 30-JUN-24:00 | 480.72 | 27-JUN-15:00 | 1665.68 | 27-JUN-13:00 | 0.00 |
July | 0.164687E+11 | 0.466285E+10 | 744.00 | 0.161551E+11 | 0.313591E+09 | 0.00 | 0.87 | 31-JUL-23:15 | 0.63 | 07-JUL-06:40 | 7809.26 | 31-JUL-23:53 | 7790.97 | 31-JUL-23:57 | 478.14 | 20-JUL-15:00 | 2388.10 | 21-JUL-14:00 | 0.00 |
August | 0.213483E+11 | 0.583770E+10 | 744.00 | 0.211253E+11 | 0.222909E+09 | 0.00 | 1.00 | 18-AUG-15:40 | 0.30 | 31-AUG-24:00 | 8642.50 | 14-AUG-15:20 | 8608.86 | 04-AUG-18:30 | 472.37 | 14-AUG-10:00 | 2953.43 | 10-AUG-14:10 | 0.00 |
September | 0.564350E+10 | 0.146128E+10 | 720.00 | 0.550196E+10 | 0.141540E+09 | 0.00 | 0.44 | 30-SEP-24:00 | 0.18 | 30-SEP-07:00 | 3747.54 | 30-SEP-24:00 | 3747.54 | 30-SEP-24:00 | 338.13 | 15-SEP-15:10 | 883.07 | 30-SEP-24:00 | 0.00 |
October | 0.102198E+11 | 0.244468E+10 | 744.00 | 0.101864E+11 | 33393433.36 | 0.00 | 0.64 | 31-OCT-24:00 | 0.38 | 30-OCT-06:10 | 5695.21 | 31-OCT-24:00 | 5695.21 | 31-OCT-24:00 | 192.19 | 12-OCT-15:30 | 1291.76 | 11-OCT-16:50 | 0.00 |
November | 0.144455E+11 | 0.337062E+10 | 720.00 | 0.144439E+11 | 1609672.63 | 0.00 | 0.74 | 26-NOV-14:03 | 0.59 | 21-NOV-07:10 | 6025.66 | 05-NOV-12:50 | 6025.66 | 05-NOV-12:50 | 116.41 | 16-NOV-18:40 | 1658.09 | 26-NOV-14:00 | 0.00 |
December | 0.191166E+11 | 0.443543E+10 | 744.00 | 0.191161E+11 | 495761.88 | 0.00 | 0.89 | 24-DEC-16:10 | 0.75 | 11-DEC-07:05 | 7726.00 | 17-DEC-16:10 | 7726.00 | 17-DEC-16:10 | 97.92 | 01-DEC-13:30 | 1761.24 | 24-DEC-16:10 | 0.00 |
Annual Sum or Average | 0.148018E+12 | 0.371034E+11 | 8760.00 | 0.147054E+12 | 0.964040E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.271972E+10 | 0.763598E+09 | 672.00 | 0.271970E+10 | -0.0 | 0.00 | 0.27 | 0.01 | 2049.86 | 2049.86 | 0.00 | 531.04 | 0.00 | ||||||
Maximum of Months | 0.213483E+11 | 0.583770E+10 | 744.00 | 0.211253E+11 | 0.313591E+09 | 0.00 | 1.00 | 0.75 | 8642.50 | 8608.86 | 480.72 | 2953.43 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.305314E+10 | 0.100992E+10 | 300.25 | 0.305310E+10 | 30624.51 | 0.00 | 0.17 | 12-JAN-16:40 | 0.00 | 01-JAN-00:03 | 11460.59 | 12-JAN-16:40 | 11460.59 | 12-JAN-16:40 | 15.72 | 11-JAN-18:10 | 3196.43 | 12-JAN-16:40 | 0.00 |
February | 0.438684E+11 | 0.117738E+11 | 672.00 | 0.438684E+11 | -0.0 | 0.00 | 0.45 | 28-FEB-17:00 | 0.10 | 06-FEB-07:03 | 33426.71 | 28-FEB-17:00 | 33426.71 | 28-FEB-17:00 | 0.00 | 24-FEB-10:50 | 8454.08 | 28-FEB-17:00 | 0.00 |
March | 0.120105E+12 | 0.293365E+11 | 744.00 | 0.119888E+12 | 0.216576E+09 | 0.00 | 0.76 | 31-MAR-23:50 | 0.40 | 06-MAR-07:05 | 65960.88 | 31-MAR-23:50 | 65960.88 | 31-MAR-23:50 | 2518.68 | 16-MAR-16:10 | 18457.35 | 15-MAR-14:10 | 0.00 |
April | 0.175096E+12 | 0.397721E+11 | 720.00 | 0.175066E+12 | 30267390.11 | 0.00 | 0.92 | 22-APR-17:55 | 0.22 | 30-APR-24:00 | 77335.28 | 02-APR-17:55 | 77335.28 | 02-APR-17:55 | 990.97 | 12-APR-16:10 | 20658.15 | 07-APR-14:00 | 0.00 |
May | 0.467544E+11 | 0.120963E+11 | 744.00 | 0.463878E+11 | 0.366532E+09 | 0.00 | 0.46 | 31-MAY-24:00 | 0.13 | 01-MAY-06:05 | 37901.61 | 31-MAY-24:00 | 37835.75 | 31-MAY-24:00 | 2261.16 | 17-MAY-15:30 | 9242.54 | 31-MAY-23:50 | 0.00 |
June | 0.100608E+12 | 0.267448E+11 | 720.00 | 0.987383E+11 | 0.186936E+10 | 0.00 | 0.69 | 30-JUN-23:50 | 0.38 | 14-JUN-06:05 | 56607.18 | 30-JUN-24:00 | 56607.18 | 30-JUN-24:00 | 4780.09 | 27-JUN-15:00 | 15921.48 | 27-JUN-13:00 | 0.00 |
July | 0.156606E+12 | 0.443865E+11 | 744.00 | 0.153482E+12 | 0.312421E+10 | 0.00 | 0.88 | 31-JUL-23:15 | 0.61 | 06-JUL-06:50 | 75450.44 | 31-JUL-23:53 | 75270.96 | 31-JUL-23:57 | 4770.95 | 20-JUL-15:00 | 22858.97 | 21-JUL-14:00 | 0.00 |
August | 0.202842E+12 | 0.555351E+11 | 744.00 | 0.200612E+12 | 0.222944E+10 | 0.00 | 0.99 | 18-AUG-15:50 | 0.23 | 31-AUG-24:00 | 82041.64 | 10-AUG-18:10 | 81926.87 | 04-AUG-18:30 | 4713.17 | 14-AUG-10:00 | 28109.00 | 10-AUG-14:10 | 0.00 |
September | 0.486702E+11 | 0.127391E+11 | 720.00 | 0.472933E+11 | 0.137694E+10 | 0.00 | 0.39 | 30-SEP-24:00 | 0.11 | 30-SEP-07:00 | 31447.62 | 30-SEP-24:00 | 31447.62 | 30-SEP-24:00 | 3337.12 | 15-SEP-15:10 | 8151.17 | 21-SEP-17:00 | 0.00 |
October | 0.833946E+11 | 0.202461E+11 | 744.00 | 0.830644E+11 | 0.330210E+09 | 0.00 | 0.58 | 31-OCT-24:00 | 0.26 | 30-OCT-06:10 | 49093.50 | 31-OCT-24:00 | 49093.50 | 31-OCT-24:00 | 1906.42 | 12-OCT-15:30 | 12082.27 | 11-OCT-16:50 | 0.00 |
November | 0.116879E+12 | 0.277863E+11 | 720.00 | 0.116861E+12 | 18130408.72 | 0.00 | 0.66 | 03-NOV-16:00 | 0.46 | 24-NOV-07:10 | 54958.04 | 15-NOV-16:20 | 54958.04 | 15-NOV-16:20 | 1103.89 | 16-NOV-16:20 | 13837.32 | 16-NOV-13:00 | 0.00 |
December | 0.150208E+12 | 0.357343E+11 | 744.00 | 0.150202E+12 | 5798223.71 | 0.00 | 0.82 | 04-DEC-16:20 | 0.56 | 11-DEC-07:05 | 67299.03 | 01-DEC-13:20 | 67167.57 | 04-DEC-16:20 | 1015.73 | 01-DEC-13:30 | 15575.69 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.124808E+13 | 0.317161E+12 | 8316.25 | 0.123852E+13 | 0.956749E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.305314E+10 | 0.100992E+10 | 300.25 | 0.305310E+10 | -0.0 | 0.00 | 0.17 | 0.00 | 11460.59 | 11460.59 | 0.00 | 3196.43 | 0.00 | ||||||
Maximum of Months | 0.202842E+12 | 0.555351E+11 | 744.00 | 0.200612E+12 | 0.312421E+10 | 0.00 | 0.99 | 0.61 | 82041.64 | 81926.87 | 4780.09 | 28109.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 69521586.30 | 23290807.36 | 73.74 | 69521586.30 | -0.0 | 0.00 | 0.13 | 12-JAN-16:30 | 0.00 | 01-JAN-00:03 | 892.51 | 12-JAN-16:30 | 892.51 | 12-JAN-16:30 | 0.00 | 19-JAN-12:10 | 255.39 | 12-JAN-16:30 | 0.00 |
February | 0.301291E+10 | 0.825205E+09 | 628.89 | 0.301291E+10 | -0.0 | 0.00 | 0.44 | 28-FEB-17:00 | 0.00 | 01-FEB-00:03 | 3362.08 | 28-FEB-17:00 | 3362.08 | 28-FEB-17:00 | 0.00 | 12-FEB-14:32 | 851.18 | 28-FEB-17:00 | 0.00 |
March | 0.104640E+11 | 0.259201E+10 | 744.00 | 0.104425E+11 | 21492058.61 | 0.00 | 0.73 | 15-MAR-15:00 | 0.24 | 06-MAR-04:16 | 6128.09 | 31-MAR-23:20 | 6128.09 | 31-MAR-23:20 | 252.16 | 16-MAR-16:10 | 1874.45 | 15-MAR-14:10 | 0.00 |
April | 0.163693E+11 | 0.375754E+10 | 720.00 | 0.163664E+11 | 2939697.48 | 0.00 | 0.90 | 22-APR-17:55 | 0.15 | 30-APR-23:55 | 7738.66 | 09-APR-17:55 | 7738.66 | 09-APR-17:55 | 98.07 | 12-APR-16:10 | 2071.34 | 07-APR-14:00 | 0.00 |
May | 0.416600E+10 | 0.109039E+10 | 744.00 | 0.412998E+10 | 36017420.08 | 0.00 | 0.45 | 31-MAY-23:50 | 0.03 | 01-MAY-06:05 | 3702.52 | 31-MAY-24:00 | 3696.06 | 31-MAY-24:00 | 225.80 | 17-MAY-15:30 | 907.83 | 31-MAY-23:30 | 0.00 |
June | 0.997917E+10 | 0.266451E+10 | 720.00 | 0.979241E+10 | 0.186763E+09 | 0.00 | 0.67 | 30-JUN-23:25 | 0.32 | 14-JUN-06:05 | 5601.24 | 30-JUN-24:00 | 5601.24 | 30-JUN-24:00 | 479.57 | 27-JUN-15:00 | 1621.96 | 27-JUN-13:00 | 0.00 |
July | 0.157157E+11 | 0.446541E+10 | 744.00 | 0.154036E+11 | 0.312163E+09 | 0.00 | 0.86 | 31-JUL-23:15 | 0.58 | 06-JUL-06:50 | 7549.20 | 31-JUL-23:53 | 7531.12 | 31-JUL-23:57 | 477.04 | 20-JUL-15:00 | 2322.32 | 21-JUL-14:00 | 0.00 |
August | 0.202524E+11 | 0.556407E+10 | 744.00 | 0.200299E+11 | 0.222526E+09 | 0.00 | 0.99 | 18-AUG-15:40 | 0.20 | 31-AUG-24:00 | 8294.59 | 10-AUG-18:10 | 8279.06 | 04-AUG-18:30 | 471.06 | 14-AUG-10:00 | 2845.56 | 10-AUG-14:10 | 0.00 |
September | 0.443652E+10 | 0.117615E+10 | 720.00 | 0.430048E+10 | 0.136043E+09 | 0.00 | 0.34 | 21-SEP-17:20 | 0.03 | 30-SEP-06:10 | 2701.07 | 04-SEP-17:34 | 2701.07 | 04-SEP-17:34 | 335.56 | 15-SEP-15:00 | 835.05 | 21-SEP-17:00 | 0.00 |
October | 0.686415E+10 | 0.169405E+10 | 744.00 | 0.683177E+10 | 32379152.47 | 0.00 | 0.53 | 11-OCT-16:50 | 0.10 | 30-OCT-03:15 | 4470.77 | 31-OCT-23:20 | 4470.77 | 31-OCT-23:20 | 191.09 | 12-OCT-15:30 | 1215.76 | 11-OCT-16:50 | 0.00 |
November | 0.989935E+10 | 0.239473E+10 | 720.00 | 0.989768E+10 | 1675502.53 | 0.00 | 0.63 | 03-NOV-16:00 | 0.30 | 24-NOV-04:03 | 5337.80 | 15-NOV-16:20 | 5337.80 | 15-NOV-16:20 | 106.48 | 16-NOV-16:30 | 1345.40 | 16-NOV-17:00 | 0.00 |
December | 0.132623E+11 | 0.320418E+10 | 744.00 | 0.132617E+11 | 540648.99 | 0.00 | 0.77 | 04-DEC-16:20 | 0.42 | 26-DEC-04:01 | 6349.31 | 04-DEC-16:20 | 6349.31 | 04-DEC-16:20 | 95.14 | 01-DEC-13:30 | 1486.29 | 04-DEC-16:20 | 0.00 |
Annual Sum or Average | 0.114491E+12 | 0.294515E+11 | 8046.63 | 0.113539E+12 | 0.952539E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 69521586.30 | 23290807.36 | 73.74 | 69521586.30 | -0.0 | 0.00 | 0.13 | 0.00 | 892.51 | 892.51 | 0.00 | 255.39 | 0.00 | ||||||
Maximum of Months | 0.202524E+11 | 0.556407E+10 | 744.00 | 0.200299E+11 | 0.312163E+09 | 0.00 | 0.99 | 0.58 | 8294.59 | 8279.06 | 479.57 | 2845.56 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.72 | 0.00 | 96.72 | 0.01 | 663.91 | 0.00 | 0.00 | 0.00 |
February | 147.36 | 0.00 | 147.36 | 3.77 | 620.95 | 0.00 | 0.00 | 0.00 |
March | 178.71 | 0.00 | 178.71 | 45.56 | 463.08 | 0.00 | 0.00 | 0.00 |
April | 227.71 | 0.91 | 226.81 | 103.73 | 334.19 | 0.00 | 0.00 | 0.00 |
May | 264.59 | 11.22 | 253.37 | 197.37 | 201.64 | 0.00 | 0.00 | 0.00 |
June | 318.25 | 27.09 | 291.16 | 338.62 | 126.88 | 0.00 | 0.00 | 0.00 |
July | 295.22 | 19.06 | 276.16 | 366.69 | 86.60 | 0.00 | 0.00 | 0.00 |
August | 255.45 | 3.89 | 251.56 | 297.64 | 116.92 | 0.00 | 0.00 | 0.00 |
September | 194.40 | 0.04 | 194.36 | 170.40 | 198.16 | 0.00 | 0.00 | 0.00 |
October | 145.32 | 0.00 | 145.32 | 57.64 | 333.14 | 0.00 | 0.00 | 0.00 |
November | 97.65 | 0.00 | 97.65 | 12.33 | 447.76 | 0.00 | 0.00 | 0.00 |
December | 90.53 | 0.00 | 90.53 | 0.42 | 655.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.85 | 5.21 | 187.64 | 133.65 | 352.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.53 | 0.00 | 90.53 | 0.01 | 86.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.25 | 27.09 | 291.16 | 366.69 | 663.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.72 | 0.00 | 96.72 | 0.01 | 663.91 | 0.00 | 0.00 | 0.00 |
February | 147.36 | 0.00 | 147.36 | 3.77 | 620.95 | 0.00 | 0.00 | 0.00 |
March | 178.71 | 0.00 | 178.71 | 45.56 | 463.08 | 0.00 | 0.00 | 0.00 |
April | 227.71 | 0.91 | 226.80 | 103.73 | 334.19 | 0.00 | 0.00 | 0.00 |
May | 264.59 | 11.22 | 253.37 | 197.36 | 201.64 | 0.00 | 0.00 | 0.00 |
June | 318.25 | 27.09 | 291.16 | 338.62 | 126.88 | 0.00 | 0.00 | 0.00 |
July | 295.21 | 19.06 | 276.16 | 366.68 | 86.60 | 0.00 | 0.00 | 0.00 |
August | 255.44 | 3.89 | 251.56 | 297.64 | 116.92 | 0.00 | 0.00 | 0.00 |
September | 194.40 | 0.04 | 194.36 | 170.40 | 198.16 | 0.00 | 0.00 | 0.00 |
October | 145.32 | 0.00 | 145.32 | 57.64 | 333.14 | 0.00 | 0.00 | 0.00 |
November | 97.65 | 0.00 | 97.65 | 12.33 | 447.76 | 0.00 | 0.00 | 0.00 |
December | 90.52 | 0.00 | 90.52 | 0.42 | 655.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.84 | 5.21 | 187.64 | 133.65 | 352.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.52 | 0.00 | 90.52 | 0.01 | 86.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.25 | 27.09 | 291.16 | 366.68 | 663.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.72 | 0.00 | 96.72 | 0.01 | 663.91 | 0.00 | 0.00 | 0.00 |
February | 147.36 | 0.00 | 147.36 | 3.77 | 620.95 | 0.00 | 0.00 | 0.00 |
March | 178.71 | 0.00 | 178.71 | 45.56 | 463.08 | 0.00 | 0.00 | 0.00 |
April | 227.71 | 0.91 | 226.80 | 103.73 | 334.19 | 0.00 | 0.00 | 0.00 |
May | 264.59 | 11.22 | 253.37 | 197.36 | 201.64 | 0.00 | 0.00 | 0.00 |
June | 318.25 | 27.09 | 291.16 | 338.62 | 126.88 | 0.00 | 0.00 | 0.00 |
July | 295.22 | 19.06 | 276.16 | 366.68 | 86.60 | 0.00 | 0.00 | 0.00 |
August | 255.44 | 3.89 | 251.56 | 297.64 | 116.92 | 0.00 | 0.00 | 0.00 |
September | 194.40 | 0.04 | 194.36 | 170.40 | 198.16 | 0.00 | 0.00 | 0.00 |
October | 145.32 | 0.00 | 145.32 | 57.64 | 333.14 | 0.00 | 0.00 | 0.00 |
November | 97.65 | 0.00 | 97.65 | 12.33 | 447.76 | 0.00 | 0.00 | 0.00 |
December | 90.53 | 0.00 | 90.53 | 0.42 | 655.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.85 | 5.21 | 187.64 | 133.65 | 352.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.53 | 0.00 | 90.53 | 0.01 | 86.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.25 | 27.09 | 291.16 | 366.68 | 663.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.72 | 0.00 | 96.72 | 0.01 | 663.91 | 0.00 | 0.00 | 0.00 |
February | 147.36 | 0.00 | 147.36 | 3.77 | 620.95 | 0.00 | 0.00 | 0.00 |
March | 178.71 | 0.00 | 178.71 | 45.56 | 463.08 | 0.00 | 0.00 | 0.00 |
April | 227.71 | 0.91 | 226.80 | 103.73 | 334.19 | 0.00 | 0.00 | 0.00 |
May | 264.59 | 11.22 | 253.37 | 197.36 | 201.64 | 0.00 | 0.00 | 0.00 |
June | 318.25 | 27.09 | 291.16 | 338.62 | 126.88 | 0.00 | 0.00 | 0.00 |
July | 295.21 | 19.06 | 276.16 | 366.68 | 86.60 | 0.00 | 0.00 | 0.00 |
August | 255.44 | 3.89 | 251.56 | 297.64 | 116.92 | 0.00 | 0.00 | 0.00 |
September | 194.40 | 0.04 | 194.36 | 170.40 | 198.16 | 0.00 | 0.00 | 0.00 |
October | 145.32 | 0.00 | 145.32 | 57.64 | 333.14 | 0.00 | 0.00 | 0.00 |
November | 97.65 | 0.00 | 97.65 | 12.33 | 447.76 | 0.00 | 0.00 | 0.00 |
December | 90.52 | 0.00 | 90.52 | 0.42 | 655.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.84 | 5.21 | 187.64 | 133.65 | 352.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.52 | 0.00 | 90.52 | 0.01 | 86.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.25 | 27.09 | 291.16 | 366.68 | 663.91 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.71 | 0.00 | 96.71 | 0.01 | 663.88 | 0.00 | 0.00 | 0.00 |
February | 147.36 | 0.00 | 147.36 | 3.77 | 620.93 | 0.00 | 0.00 | 0.00 |
March | 178.70 | 0.00 | 178.70 | 45.56 | 463.06 | 0.00 | 0.00 | 0.00 |
April | 227.70 | 0.91 | 226.79 | 103.72 | 334.18 | 0.00 | 0.00 | 0.00 |
May | 264.58 | 11.22 | 253.36 | 197.35 | 201.64 | 0.00 | 0.00 | 0.00 |
June | 318.23 | 27.09 | 291.14 | 338.60 | 126.88 | 0.00 | 0.00 | 0.00 |
July | 295.20 | 19.06 | 276.15 | 366.67 | 86.60 | 0.00 | 0.00 | 0.00 |
August | 255.43 | 3.89 | 251.55 | 297.63 | 116.92 | 0.00 | 0.00 | 0.00 |
September | 194.39 | 0.04 | 194.35 | 170.39 | 198.15 | 0.00 | 0.00 | 0.00 |
October | 145.31 | 0.00 | 145.31 | 57.64 | 333.13 | 0.00 | 0.00 | 0.00 |
November | 97.65 | 0.00 | 97.65 | 12.33 | 447.74 | 0.00 | 0.00 | 0.00 |
December | 90.52 | 0.00 | 90.52 | 0.42 | 655.27 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 192.84 | 5.21 | 187.63 | 133.65 | 352.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 90.52 | 0.00 | 90.52 | 0.01 | 86.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 318.23 | 27.09 | 291.14 | 366.67 | 663.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 196.66 | 63.42 | 133.25 | 69.64 | 666.80 | 0.00 | 0.00 | 0.00 |
February | 288.57 | 86.59 | 201.97 | 124.87 | 624.95 | 0.00 | 0.00 | 0.00 |
March | 414.08 | 173.42 | 240.67 | 308.60 | 462.50 | 0.00 | 0.00 | 0.00 |
April | 548.07 | 242.16 | 305.90 | 499.37 | 337.75 | 0.00 | 0.00 | 0.00 |
May | 614.03 | 271.62 | 342.41 | 660.35 | 223.91 | 0.00 | 0.00 | 0.00 |
June | 685.77 | 303.08 | 382.69 | 833.63 | 140.43 | 0.00 | 0.00 | 0.00 |
July | 658.52 | 289.94 | 368.58 | 864.48 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 594.71 | 249.63 | 345.08 | 762.95 | 121.90 | 0.00 | 0.00 | 0.00 |
September | 494.90 | 219.52 | 275.38 | 567.86 | 207.07 | 0.00 | 0.00 | 0.00 |
October | 335.83 | 138.91 | 196.92 | 287.18 | 339.55 | 0.00 | 0.00 | 0.00 |
November | 190.49 | 61.11 | 129.38 | 105.91 | 456.49 | 0.00 | 0.00 | 0.00 |
December | 153.35 | 31.69 | 121.67 | 34.14 | 666.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 431.89 | 178.02 | 253.87 | 428.24 | 360.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.35 | 31.69 | 121.67 | 34.14 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.77 | 303.08 | 382.69 | 864.48 | 666.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 196.66 | 63.42 | 133.25 | 69.64 | 666.80 | 0.00 | 0.00 | 0.00 |
February | 288.57 | 86.59 | 201.97 | 124.87 | 624.95 | 0.00 | 0.00 | 0.00 |
March | 414.08 | 173.42 | 240.67 | 308.60 | 462.50 | 0.00 | 0.00 | 0.00 |
April | 548.07 | 242.16 | 305.90 | 499.37 | 337.75 | 0.00 | 0.00 | 0.00 |
May | 614.03 | 271.62 | 342.41 | 660.35 | 223.91 | 0.00 | 0.00 | 0.00 |
June | 685.77 | 303.08 | 382.69 | 833.63 | 140.43 | 0.00 | 0.00 | 0.00 |
July | 658.52 | 289.94 | 368.58 | 864.48 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 594.71 | 249.63 | 345.08 | 762.95 | 121.90 | 0.00 | 0.00 | 0.00 |
September | 494.90 | 219.52 | 275.38 | 567.86 | 207.07 | 0.00 | 0.00 | 0.00 |
October | 335.83 | 138.91 | 196.92 | 287.18 | 339.55 | 0.00 | 0.00 | 0.00 |
November | 190.49 | 61.11 | 129.38 | 105.91 | 456.49 | 0.00 | 0.00 | 0.00 |
December | 153.35 | 31.69 | 121.67 | 34.14 | 666.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 431.89 | 178.02 | 253.87 | 428.24 | 360.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.35 | 31.69 | 121.67 | 34.14 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.77 | 303.08 | 382.69 | 864.48 | 666.80 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 196.66 | 63.41 | 133.25 | 69.64 | 666.79 | 0.00 | 0.00 | 0.00 |
February | 288.56 | 86.59 | 201.97 | 124.87 | 624.93 | 0.00 | 0.00 | 0.00 |
March | 414.08 | 173.41 | 240.66 | 308.60 | 462.49 | 0.00 | 0.00 | 0.00 |
April | 548.06 | 242.16 | 305.89 | 499.36 | 337.74 | 0.00 | 0.00 | 0.00 |
May | 614.02 | 271.61 | 342.41 | 660.34 | 223.90 | 0.00 | 0.00 | 0.00 |
June | 685.75 | 303.07 | 382.68 | 833.61 | 140.42 | 0.00 | 0.00 | 0.00 |
July | 658.50 | 289.93 | 368.57 | 864.46 | 92.41 | 0.00 | 0.00 | 0.00 |
August | 594.70 | 249.62 | 345.08 | 762.93 | 121.89 | 0.00 | 0.00 | 0.00 |
September | 494.90 | 219.52 | 275.38 | 567.85 | 207.07 | 0.00 | 0.00 | 0.00 |
October | 335.83 | 138.91 | 196.92 | 287.17 | 339.54 | 0.00 | 0.00 | 0.00 |
November | 190.49 | 61.11 | 129.38 | 105.91 | 456.48 | 0.00 | 0.00 | 0.00 |
December | 153.35 | 31.69 | 121.67 | 34.14 | 666.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 431.88 | 178.02 | 253.86 | 428.23 | 360.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 153.35 | 31.69 | 121.67 | 34.14 | 92.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 685.75 | 303.07 | 382.68 | 864.46 | 666.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.89 | 242.77 | 173.12 | 327.57 | 548.84 | 0.00 | 0.00 | 0.00 |
February | 474.84 | 228.96 | 245.88 | 367.27 | 536.09 | 0.00 | 0.00 | 0.00 |
March | 579.57 | 325.66 | 253.92 | 557.05 | 409.98 | 0.00 | 0.00 | 0.00 |
April | 479.98 | 191.80 | 288.18 | 480.45 | 328.93 | 0.00 | 0.00 | 0.00 |
May | 420.02 | 121.99 | 298.03 | 463.03 | 218.42 | 0.00 | 0.00 | 0.00 |
June | 408.13 | 86.48 | 321.65 | 505.90 | 139.77 | 0.00 | 0.00 | 0.00 |
July | 416.63 | 101.09 | 315.55 | 573.65 | 94.88 | 0.00 | 0.00 | 0.00 |
August | 467.74 | 151.65 | 316.09 | 632.67 | 124.17 | 0.00 | 0.00 | 0.00 |
September | 543.84 | 264.89 | 278.95 | 677.41 | 199.40 | 0.00 | 0.00 | 0.00 |
October | 520.37 | 297.25 | 223.13 | 554.62 | 305.69 | 0.00 | 0.00 | 0.00 |
November | 372.68 | 210.39 | 162.29 | 342.86 | 395.32 | 0.00 | 0.00 | 0.00 |
December | 347.76 | 179.98 | 167.78 | 256.02 | 552.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.81 | 200.14 | 253.68 | 478.86 | 319.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 347.76 | 86.48 | 162.29 | 256.02 | 94.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 579.57 | 325.66 | 321.65 | 677.41 | 552.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.88 | 242.76 | 173.12 | 327.57 | 548.84 | 0.00 | 0.00 | 0.00 |
February | 474.84 | 228.96 | 245.87 | 367.26 | 536.09 | 0.00 | 0.00 | 0.00 |
March | 579.57 | 325.65 | 253.91 | 557.04 | 409.98 | 0.00 | 0.00 | 0.00 |
April | 479.98 | 191.80 | 288.18 | 480.45 | 328.93 | 0.00 | 0.00 | 0.00 |
May | 420.02 | 121.99 | 298.03 | 463.03 | 218.42 | 0.00 | 0.00 | 0.00 |
June | 408.13 | 86.48 | 321.64 | 505.90 | 139.77 | 0.00 | 0.00 | 0.00 |
July | 416.63 | 101.09 | 315.54 | 573.64 | 94.88 | 0.00 | 0.00 | 0.00 |
August | 467.74 | 151.65 | 316.09 | 632.67 | 124.17 | 0.00 | 0.00 | 0.00 |
September | 543.84 | 264.89 | 278.95 | 677.41 | 199.40 | 0.00 | 0.00 | 0.00 |
October | 520.37 | 297.24 | 223.13 | 554.62 | 305.69 | 0.00 | 0.00 | 0.00 |
November | 372.68 | 210.39 | 162.29 | 342.86 | 395.32 | 0.00 | 0.00 | 0.00 |
December | 347.76 | 179.98 | 167.78 | 256.02 | 552.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.81 | 200.13 | 253.68 | 478.86 | 319.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 347.76 | 86.48 | 162.29 | 256.02 | 94.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 579.57 | 325.65 | 321.64 | 677.41 | 552.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.89 | 242.77 | 173.12 | 327.57 | 548.84 | 0.00 | 0.00 | 0.00 |
February | 474.84 | 228.96 | 245.88 | 367.27 | 536.09 | 0.00 | 0.00 | 0.00 |
March | 579.57 | 325.66 | 253.92 | 557.05 | 409.98 | 0.00 | 0.00 | 0.00 |
April | 479.98 | 191.80 | 288.18 | 480.45 | 328.93 | 0.00 | 0.00 | 0.00 |
May | 420.02 | 121.99 | 298.03 | 463.03 | 218.42 | 0.00 | 0.00 | 0.00 |
June | 408.13 | 86.48 | 321.65 | 505.90 | 139.77 | 0.00 | 0.00 | 0.00 |
July | 416.63 | 101.09 | 315.55 | 573.65 | 94.88 | 0.00 | 0.00 | 0.00 |
August | 467.74 | 151.65 | 316.09 | 632.67 | 124.17 | 0.00 | 0.00 | 0.00 |
September | 543.84 | 264.89 | 278.95 | 677.41 | 199.40 | 0.00 | 0.00 | 0.00 |
October | 520.37 | 297.25 | 223.13 | 554.62 | 305.69 | 0.00 | 0.00 | 0.00 |
November | 372.68 | 210.39 | 162.29 | 342.86 | 395.32 | 0.00 | 0.00 | 0.00 |
December | 347.76 | 179.98 | 167.78 | 256.02 | 552.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.81 | 200.14 | 253.68 | 478.86 | 319.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 347.76 | 86.48 | 162.29 | 256.02 | 94.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 579.57 | 325.66 | 321.65 | 677.41 | 552.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.88 | 242.76 | 173.12 | 327.57 | 548.84 | 0.00 | 0.00 | 0.00 |
February | 474.84 | 228.96 | 245.87 | 367.26 | 536.09 | 0.00 | 0.00 | 0.00 |
March | 579.57 | 325.65 | 253.91 | 557.04 | 409.98 | 0.00 | 0.00 | 0.00 |
April | 479.98 | 191.80 | 288.18 | 480.45 | 328.93 | 0.00 | 0.00 | 0.00 |
May | 420.02 | 121.99 | 298.03 | 463.03 | 218.42 | 0.00 | 0.00 | 0.00 |
June | 408.13 | 86.48 | 321.64 | 505.90 | 139.77 | 0.00 | 0.00 | 0.00 |
July | 416.63 | 101.09 | 315.54 | 573.64 | 94.88 | 0.00 | 0.00 | 0.00 |
August | 467.74 | 151.65 | 316.09 | 632.67 | 124.17 | 0.00 | 0.00 | 0.00 |
September | 543.84 | 264.89 | 278.95 | 677.41 | 199.40 | 0.00 | 0.00 | 0.00 |
October | 520.37 | 297.24 | 223.13 | 554.62 | 305.69 | 0.00 | 0.00 | 0.00 |
November | 372.68 | 210.39 | 162.29 | 342.86 | 395.32 | 0.00 | 0.00 | 0.00 |
December | 347.76 | 179.98 | 167.78 | 256.02 | 552.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.81 | 200.13 | 253.68 | 478.86 | 319.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 347.76 | 86.48 | 162.29 | 256.02 | 94.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 579.57 | 325.65 | 321.64 | 677.41 | 552.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 415.87 | 242.75 | 173.11 | 327.56 | 548.82 | 0.00 | 0.00 | 0.00 |
February | 474.82 | 228.95 | 245.87 | 367.25 | 536.07 | 0.00 | 0.00 | 0.00 |
March | 579.55 | 325.64 | 253.90 | 557.02 | 409.97 | 0.00 | 0.00 | 0.00 |
April | 479.96 | 191.79 | 288.17 | 480.43 | 328.91 | 0.00 | 0.00 | 0.00 |
May | 420.01 | 121.99 | 298.02 | 463.01 | 218.41 | 0.00 | 0.00 | 0.00 |
June | 408.11 | 86.48 | 321.63 | 505.88 | 139.77 | 0.00 | 0.00 | 0.00 |
July | 416.62 | 101.08 | 315.53 | 573.62 | 94.88 | 0.00 | 0.00 | 0.00 |
August | 467.72 | 151.65 | 316.07 | 632.65 | 124.17 | 0.00 | 0.00 | 0.00 |
September | 543.82 | 264.88 | 278.94 | 677.38 | 199.39 | 0.00 | 0.00 | 0.00 |
October | 520.35 | 297.23 | 223.12 | 554.60 | 305.67 | 0.00 | 0.00 | 0.00 |
November | 372.66 | 210.38 | 162.28 | 342.85 | 395.31 | 0.00 | 0.00 | 0.00 |
December | 347.75 | 179.98 | 167.77 | 256.01 | 552.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 453.79 | 200.13 | 253.67 | 478.84 | 319.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 347.75 | 86.48 | 162.28 | 256.01 | 94.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 579.55 | 325.64 | 321.63 | 677.38 | 552.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.73 | 39.61 | 129.12 | 40.87 | 722.54 | 0.00 | 0.00 | 0.00 |
February | 273.47 | 70.28 | 203.19 | 100.92 | 691.63 | 0.00 | 0.00 | 0.00 |
March | 428.62 | 183.52 | 245.09 | 314.47 | 527.20 | 0.00 | 0.00 | 0.00 |
April | 524.78 | 215.18 | 309.60 | 458.50 | 407.07 | 0.00 | 0.00 | 0.00 |
May | 619.07 | 279.78 | 339.29 | 662.99 | 256.35 | 0.00 | 0.00 | 0.00 |
June | 746.92 | 351.32 | 395.60 | 907.41 | 173.54 | 0.00 | 0.00 | 0.00 |
July | 667.78 | 292.78 | 375.00 | 863.53 | 125.29 | 0.00 | 0.00 | 0.00 |
August | 603.96 | 256.81 | 347.15 | 764.11 | 162.39 | 0.00 | 0.00 | 0.00 |
September | 474.30 | 204.83 | 269.47 | 538.01 | 237.81 | 0.00 | 0.00 | 0.00 |
October | 307.46 | 108.31 | 199.16 | 246.43 | 389.98 | 0.00 | 0.00 | 0.00 |
November | 182.20 | 52.50 | 129.70 | 90.06 | 528.72 | 0.00 | 0.00 | 0.00 |
December | 157.95 | 34.42 | 123.54 | 35.16 | 762.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 430.31 | 174.62 | 255.70 | 420.27 | 413.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.95 | 34.42 | 123.54 | 35.16 | 125.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 746.92 | 351.32 | 395.60 | 907.41 | 762.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.73 | 39.61 | 129.12 | 40.87 | 722.54 | 0.00 | 0.00 | 0.00 |
February | 273.47 | 70.28 | 203.19 | 100.92 | 691.63 | 0.00 | 0.00 | 0.00 |
March | 428.62 | 183.52 | 245.09 | 314.47 | 527.20 | 0.00 | 0.00 | 0.00 |
April | 524.78 | 215.18 | 309.60 | 458.50 | 407.07 | 0.00 | 0.00 | 0.00 |
May | 619.07 | 279.78 | 339.29 | 662.99 | 256.35 | 0.00 | 0.00 | 0.00 |
June | 746.92 | 351.32 | 395.60 | 907.41 | 173.54 | 0.00 | 0.00 | 0.00 |
July | 667.78 | 292.78 | 375.00 | 863.53 | 125.29 | 0.00 | 0.00 | 0.00 |
August | 603.96 | 256.81 | 347.15 | 764.11 | 162.39 | 0.00 | 0.00 | 0.00 |
September | 474.30 | 204.83 | 269.47 | 538.01 | 237.81 | 0.00 | 0.00 | 0.00 |
October | 307.46 | 108.31 | 199.16 | 246.43 | 389.98 | 0.00 | 0.00 | 0.00 |
November | 182.20 | 52.50 | 129.70 | 90.06 | 528.72 | 0.00 | 0.00 | 0.00 |
December | 157.95 | 34.42 | 123.54 | 35.16 | 762.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 430.31 | 174.62 | 255.70 | 420.27 | 413.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.95 | 34.42 | 123.54 | 35.16 | 125.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 746.92 | 351.32 | 395.60 | 907.41 | 762.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 168.73 | 39.61 | 129.12 | 40.87 | 722.53 | 0.00 | 0.00 | 0.00 |
February | 273.47 | 70.28 | 203.18 | 100.92 | 691.62 | 0.00 | 0.00 | 0.00 |
March | 428.61 | 183.52 | 245.09 | 314.47 | 527.19 | 0.00 | 0.00 | 0.00 |
April | 524.77 | 215.18 | 309.60 | 458.49 | 407.06 | 0.00 | 0.00 | 0.00 |
May | 619.05 | 279.77 | 339.28 | 662.98 | 256.35 | 0.00 | 0.00 | 0.00 |
June | 746.91 | 351.31 | 395.59 | 907.39 | 173.54 | 0.00 | 0.00 | 0.00 |
July | 667.76 | 292.77 | 374.99 | 863.52 | 125.28 | 0.00 | 0.00 | 0.00 |
August | 603.95 | 256.81 | 347.15 | 764.09 | 162.39 | 0.00 | 0.00 | 0.00 |
September | 474.29 | 204.83 | 269.47 | 538.00 | 237.80 | 0.00 | 0.00 | 0.00 |
October | 307.46 | 108.30 | 199.15 | 246.43 | 389.97 | 0.00 | 0.00 | 0.00 |
November | 182.20 | 52.50 | 129.70 | 90.06 | 528.71 | 0.00 | 0.00 | 0.00 |
December | 157.95 | 34.42 | 123.54 | 35.16 | 762.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 430.31 | 174.61 | 255.69 | 420.27 | 413.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 157.95 | 34.42 | 123.54 | 35.16 | 125.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 746.91 | 351.31 | 395.59 | 907.39 | 762.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.60 | 0.00 | 483.60 | 4.87 | 3016.93 | 0.00 | 0.00 | 0.00 |
February | 736.82 | 0.00 | 736.82 | 39.45 | 2820.10 | 0.00 | 0.00 | 0.00 |
March | 893.56 | 0.00 | 893.56 | 273.95 | 2055.70 | 0.00 | 0.00 | 0.00 |
April | 1138.57 | 4.54 | 1134.03 | 598.31 | 1461.34 | 0.00 | 0.00 | 0.00 |
May | 1322.97 | 56.10 | 1266.86 | 1019.66 | 942.08 | 0.00 | 0.00 | 0.00 |
June | 1591.25 | 135.46 | 1455.79 | 1705.06 | 609.75 | 0.00 | 0.00 | 0.00 |
July | 1476.09 | 95.29 | 1380.81 | 1841.45 | 425.72 | 0.00 | 0.00 | 0.00 |
August | 1277.23 | 19.43 | 1257.80 | 1501.65 | 567.85 | 0.00 | 0.00 | 0.00 |
September | 972.00 | 0.20 | 971.80 | 872.25 | 923.78 | 0.00 | 0.00 | 0.00 |
October | 726.61 | 0.00 | 726.61 | 342.20 | 1461.25 | 0.00 | 0.00 | 0.00 |
November | 488.27 | 0.00 | 488.27 | 97.18 | 1901.92 | 0.00 | 0.00 | 0.00 |
December | 452.63 | 0.00 | 452.63 | 6.05 | 2879.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 964.24 | 26.03 | 938.21 | 695.82 | 1582.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 452.63 | 0.00 | 452.63 | 4.87 | 425.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1591.25 | 135.46 | 1455.79 | 1841.45 | 3016.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 589.98 | 190.24 | 399.74 | 222.44 | 1829.66 | 0.00 | 0.00 | 0.00 |
February | 865.69 | 259.77 | 605.92 | 399.86 | 1730.77 | 0.00 | 0.00 | 0.00 |
March | 1242.24 | 520.24 | 722.00 | 955.27 | 1265.36 | 0.00 | 0.00 | 0.00 |
April | 1644.18 | 726.49 | 917.69 | 1523.05 | 930.74 | 0.00 | 0.00 | 0.00 |
May | 1842.07 | 814.85 | 1027.22 | 1979.14 | 641.21 | 0.00 | 0.00 | 0.00 |
June | 2057.28 | 909.22 | 1148.06 | 2486.02 | 416.41 | 0.00 | 0.00 | 0.00 |
July | 1975.53 | 869.80 | 1105.73 | 2573.60 | 289.60 | 0.00 | 0.00 | 0.00 |
August | 1784.12 | 748.88 | 1035.24 | 2271.26 | 379.41 | 0.00 | 0.00 | 0.00 |
September | 1484.70 | 658.56 | 826.14 | 1701.37 | 593.98 | 0.00 | 0.00 | 0.00 |
October | 1007.49 | 416.73 | 590.77 | 887.50 | 923.70 | 0.00 | 0.00 | 0.00 |
November | 571.47 | 183.32 | 388.15 | 346.06 | 1210.61 | 0.00 | 0.00 | 0.00 |
December | 460.06 | 95.06 | 365.00 | 114.84 | 1805.41 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1295.66 | 534.06 | 761.60 | 1293.20 | 997.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.06 | 95.06 | 365.00 | 114.84 | 289.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2057.28 | 909.22 | 1148.06 | 2573.60 | 1829.66 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2079.47 | 1213.85 | 865.62 | 1654.75 | 2598.92 | 0.00 | 0.00 | 0.00 |
February | 2374.24 | 1144.84 | 1229.40 | 1855.03 | 2549.50 | 0.00 | 0.00 | 0.00 |
March | 2897.92 | 1628.32 | 1269.59 | 2793.55 | 1939.67 | 0.00 | 0.00 | 0.00 |
April | 2399.93 | 959.02 | 1440.91 | 2416.89 | 1544.40 | 0.00 | 0.00 | 0.00 |
May | 2100.15 | 609.97 | 1490.18 | 2306.17 | 1056.54 | 0.00 | 0.00 | 0.00 |
June | 2040.67 | 432.43 | 1608.24 | 2520.33 | 679.44 | 0.00 | 0.00 | 0.00 |
July | 2083.19 | 505.45 | 1577.74 | 2857.58 | 472.04 | 0.00 | 0.00 | 0.00 |
August | 2338.73 | 758.27 | 1580.45 | 3151.77 | 616.36 | 0.00 | 0.00 | 0.00 |
September | 2719.24 | 1324.47 | 1394.77 | 3368.60 | 974.96 | 0.00 | 0.00 | 0.00 |
October | 2601.91 | 1486.26 | 1115.65 | 2770.08 | 1455.93 | 0.00 | 0.00 | 0.00 |
November | 1863.44 | 1051.97 | 811.46 | 1733.27 | 1837.78 | 0.00 | 0.00 | 0.00 |
December | 1738.85 | 899.94 | 838.92 | 1307.64 | 2562.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.11 | 1000.70 | 1268.41 | 2397.81 | 1518.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1738.85 | 432.43 | 811.46 | 1307.64 | 472.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2897.92 | 1628.32 | 1608.24 | 3368.60 | 2598.92 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.20 | 118.84 | 387.36 | 134.15 | 1937.73 | 0.00 | 0.00 | 0.00 |
February | 820.40 | 210.85 | 609.55 | 337.32 | 1826.85 | 0.00 | 0.00 | 0.00 |
March | 1285.84 | 550.57 | 735.27 | 1003.83 | 1337.98 | 0.00 | 0.00 | 0.00 |
April | 1574.33 | 645.54 | 928.79 | 1450.33 | 1011.52 | 0.00 | 0.00 | 0.00 |
May | 1857.18 | 839.33 | 1017.85 | 2007.73 | 705.66 | 0.00 | 0.00 | 0.00 |
June | 2240.74 | 1053.95 | 1186.79 | 2734.58 | 476.56 | 0.00 | 0.00 | 0.00 |
July | 2003.31 | 878.32 | 1124.99 | 2612.50 | 340.31 | 0.00 | 0.00 | 0.00 |
August | 1811.87 | 770.43 | 1041.45 | 2322.38 | 429.79 | 0.00 | 0.00 | 0.00 |
September | 1422.88 | 614.48 | 808.40 | 1631.23 | 647.89 | 0.00 | 0.00 | 0.00 |
October | 922.38 | 324.92 | 597.47 | 792.04 | 984.90 | 0.00 | 0.00 | 0.00 |
November | 546.61 | 157.51 | 389.09 | 313.54 | 1270.05 | 0.00 | 0.00 | 0.00 |
December | 473.86 | 103.25 | 370.61 | 127.67 | 1879.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1290.93 | 523.84 | 767.08 | 1294.09 | 1066.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 473.86 | 103.25 | 370.61 | 127.67 | 340.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2240.74 | 1053.95 | 1186.79 | 2734.58 | 1937.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 483.60 | 0.00 | 483.60 | 8.46 | 2921.11 | 0.00 | 0.00 | 0.00 |
February | 736.82 | 0.00 | 736.82 | 47.48 | 2727.64 | 0.00 | 0.00 | 0.00 |
March | 893.56 | 0.00 | 893.56 | 295.85 | 1934.65 | 0.00 | 0.00 | 0.00 |
April | 1138.57 | 4.54 | 1134.03 | 642.40 | 1348.77 | 0.00 | 0.00 | 0.00 |
May | 1322.97 | 56.10 | 1266.86 | 1052.76 | 884.68 | 0.00 | 0.00 | 0.00 |
June | 1591.25 | 135.46 | 1455.79 | 1704.02 | 597.36 | 0.00 | 0.00 | 0.00 |
July | 1476.09 | 95.29 | 1380.81 | 1827.16 | 426.37 | 0.00 | 0.00 | 0.00 |
August | 1277.23 | 19.43 | 1257.80 | 1496.06 | 558.45 | 0.00 | 0.00 | 0.00 |
September | 972.00 | 0.20 | 971.80 | 892.09 | 865.09 | 0.00 | 0.00 | 0.00 |
October | 726.61 | 0.00 | 726.61 | 389.69 | 1305.85 | 0.00 | 0.00 | 0.00 |
November | 488.27 | 0.00 | 488.27 | 121.58 | 1725.21 | 0.00 | 0.00 | 0.00 |
December | 452.63 | 0.00 | 452.63 | 8.95 | 2757.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 964.24 | 26.03 | 938.21 | 711.18 | 1498.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 452.63 | 0.00 | 452.63 | 8.46 | 426.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1591.25 | 135.46 | 1455.79 | 1827.16 | 2921.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 589.98 | 190.24 | 399.74 | 229.26 | 1770.39 | 0.00 | 0.00 | 0.00 |
February | 865.69 | 259.77 | 605.92 | 410.95 | 1675.21 | 0.00 | 0.00 | 0.00 |
March | 1242.24 | 520.24 | 722.00 | 978.15 | 1190.12 | 0.00 | 0.00 | 0.00 |
April | 1644.18 | 726.49 | 917.69 | 1550.74 | 869.26 | 0.00 | 0.00 | 0.00 |
May | 1842.07 | 814.85 | 1027.22 | 1988.78 | 612.72 | 0.00 | 0.00 | 0.00 |
June | 2057.28 | 909.22 | 1148.06 | 2477.90 | 412.61 | 0.00 | 0.00 | 0.00 |
July | 1975.53 | 869.80 | 1105.73 | 2560.15 | 293.01 | 0.00 | 0.00 | 0.00 |
August | 1784.12 | 748.88 | 1035.24 | 2262.84 | 377.33 | 0.00 | 0.00 | 0.00 |
September | 1484.70 | 658.56 | 826.14 | 1708.34 | 567.39 | 0.00 | 0.00 | 0.00 |
October | 1007.49 | 416.73 | 590.77 | 922.87 | 835.15 | 0.00 | 0.00 | 0.00 |
November | 571.47 | 183.32 | 388.15 | 369.08 | 1102.35 | 0.00 | 0.00 | 0.00 |
December | 460.06 | 95.06 | 365.00 | 120.80 | 1730.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1295.66 | 534.06 | 761.60 | 1303.11 | 949.42 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 460.06 | 95.06 | 365.00 | 120.80 | 293.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2057.28 | 909.22 | 1148.06 | 2560.15 | 1770.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 2079.47 | 1213.85 | 865.62 | 1677.18 | 2496.75 | 0.00 | 0.00 | 0.00 |
February | 2374.24 | 1144.84 | 1229.40 | 1877.76 | 2452.97 | 0.00 | 0.00 | 0.00 |
March | 2897.92 | 1628.32 | 1269.59 | 2832.47 | 1812.27 | 0.00 | 0.00 | 0.00 |
April | 2399.93 | 959.02 | 1440.91 | 2455.28 | 1435.10 | 0.00 | 0.00 | 0.00 |
May | 2100.15 | 609.97 | 1490.18 | 2321.37 | 1000.84 | 0.00 | 0.00 | 0.00 |
June | 2040.67 | 432.43 | 1608.24 | 2511.11 | 665.92 | 0.00 | 0.00 | 0.00 |
July | 2083.19 | 505.45 | 1577.74 | 2838.93 | 473.42 | 0.00 | 0.00 | 0.00 |
August | 2338.73 | 758.27 | 1580.45 | 3139.27 | 609.53 | 0.00 | 0.00 | 0.00 |
September | 2719.24 | 1324.47 | 1394.77 | 3374.89 | 929.52 | 0.00 | 0.00 | 0.00 |
October | 2601.91 | 1486.26 | 1115.65 | 2820.27 | 1317.05 | 0.00 | 0.00 | 0.00 |
November | 1863.44 | 1051.97 | 811.46 | 1778.20 | 1666.03 | 0.00 | 0.00 | 0.00 |
December | 1738.85 | 899.94 | 838.92 | 1331.95 | 2441.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2269.11 | 1000.70 | 1268.41 | 2416.35 | 1436.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1738.85 | 432.43 | 811.46 | 1331.95 | 473.42 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2897.92 | 1628.32 | 1608.24 | 3374.89 | 2496.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 506.20 | 118.84 | 387.36 | 139.25 | 1872.54 | 0.00 | 0.00 | 0.00 |
February | 820.40 | 210.85 | 609.55 | 343.55 | 1770.03 | 0.00 | 0.00 | 0.00 |
March | 1285.84 | 550.57 | 735.27 | 1019.90 | 1262.78 | 0.00 | 0.00 | 0.00 |
April | 1574.33 | 645.54 | 928.79 | 1471.71 | 946.48 | 0.00 | 0.00 | 0.00 |
May | 1857.18 | 839.33 | 1017.85 | 2017.48 | 672.36 | 0.00 | 0.00 | 0.00 |
June | 2240.74 | 1053.95 | 1186.79 | 2725.82 | 468.70 | 0.00 | 0.00 | 0.00 |
July | 2003.31 | 878.32 | 1124.99 | 2599.13 | 340.55 | 0.00 | 0.00 | 0.00 |
August | 1811.87 | 770.43 | 1041.45 | 2314.24 | 425.16 | 0.00 | 0.00 | 0.00 |
September | 1422.88 | 614.48 | 808.40 | 1637.82 | 618.07 | 0.00 | 0.00 | 0.00 |
October | 922.38 | 324.92 | 597.47 | 817.28 | 901.80 | 0.00 | 0.00 | 0.00 |
November | 546.61 | 157.51 | 389.09 | 330.48 | 1171.37 | 0.00 | 0.00 | 0.00 |
December | 473.86 | 103.25 | 370.61 | 132.62 | 1804.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1290.93 | 523.84 | 767.08 | 1300.91 | 1017.47 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 473.86 | 103.25 | 370.61 | 132.62 | 340.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2240.74 | 1053.95 | 1186.79 | 2725.82 | 1872.54 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259053E+09 | 0.00 | 0.259053E+09 | 39586.17 | 0.177820E+10 |
February | 0.356503E+09 | 0.00 | 0.356503E+09 | 9119823.80 | 0.150220E+10 |
March | 0.478660E+09 | 0.00 | 0.478660E+09 | 0.122040E+09 | 0.124031E+10 |
April | 0.590236E+09 | 2355260.72 | 0.587881E+09 | 0.268866E+09 | 0.866217E+09 |
May | 0.708686E+09 | 30052126.63 | 0.678634E+09 | 0.528625E+09 | 0.540086E+09 |
June | 0.824903E+09 | 70219523.97 | 0.754684E+09 | 0.877712E+09 | 0.328880E+09 |
July | 0.790715E+09 | 51042062.01 | 0.739672E+09 | 0.982134E+09 | 0.231961E+09 |
August | 0.684188E+09 | 10408363.43 | 0.673779E+09 | 0.797208E+09 | 0.313168E+09 |
September | 0.503885E+09 | 104684.89 | 0.503781E+09 | 0.441681E+09 | 0.513632E+09 |
October | 0.389231E+09 | 0.00 | 0.389231E+09 | 0.154395E+09 | 0.892287E+09 |
November | 0.253117E+09 | 0.00 | 0.253117E+09 | 31961907.43 | 0.116058E+10 |
December | 0.242466E+09 | 0.00 | 0.242466E+09 | 1111980.69 | 0.175513E+10 |
Annual Sum or Average | 0.608164E+10 | 0.164182E+09 | 0.591746E+10 | 0.421489E+10 | 0.111227E+11 |
Minimum of Months | 0.242466E+09 | 0.00 | 0.242466E+09 | 39586.17 | 0.231961E+09 |
Maximum of Months | 0.824903E+09 | 70219523.97 | 0.754684E+09 | 0.982134E+09 | 0.177820E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259049E+09 | 0.00 | 0.259049E+09 | 39560.98 | 0.177821E+10 |
February | 0.356497E+09 | 0.00 | 0.356497E+09 | 9118476.19 | 0.150220E+10 |
March | 0.478653E+09 | 0.00 | 0.478653E+09 | 0.122035E+09 | 0.124032E+10 |
April | 0.590228E+09 | 2355208.95 | 0.587872E+09 | 0.268858E+09 | 0.866218E+09 |
May | 0.708677E+09 | 30051465.97 | 0.678625E+09 | 0.528613E+09 | 0.540086E+09 |
June | 0.824892E+09 | 70217980.28 | 0.754674E+09 | 0.877697E+09 | 0.328879E+09 |
July | 0.790703E+09 | 51040939.91 | 0.739662E+09 | 0.982120E+09 | 0.231959E+09 |
August | 0.684178E+09 | 10408134.61 | 0.673770E+09 | 0.797196E+09 | 0.313166E+09 |
September | 0.503878E+09 | 104682.59 | 0.503774E+09 | 0.441673E+09 | 0.513631E+09 |
October | 0.389225E+09 | 0.00 | 0.389225E+09 | 0.154390E+09 | 0.892288E+09 |
November | 0.253112E+09 | 0.00 | 0.253112E+09 | 31960359.32 | 0.116059E+10 |
December | 0.242462E+09 | 0.00 | 0.242462E+09 | 1111845.28 | 0.175513E+10 |
Annual Sum or Average | 0.608155E+10 | 0.164178E+09 | 0.591738E+10 | 0.421481E+10 | 0.111227E+11 |
Minimum of Months | 0.242462E+09 | 0.00 | 0.242462E+09 | 39560.98 | 0.231959E+09 |
Maximum of Months | 0.824892E+09 | 70217980.28 | 0.754674E+09 | 0.982120E+09 | 0.177821E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259050E+09 | 0.00 | 0.259050E+09 | 39569.38 | 0.177821E+10 |
February | 0.356499E+09 | 0.00 | 0.356499E+09 | 9118925.39 | 0.150220E+10 |
March | 0.478655E+09 | 0.00 | 0.478655E+09 | 0.122037E+09 | 0.124031E+10 |
April | 0.590230E+09 | 2355226.20 | 0.587875E+09 | 0.268860E+09 | 0.866218E+09 |
May | 0.708680E+09 | 30051686.19 | 0.678628E+09 | 0.528617E+09 | 0.540086E+09 |
June | 0.824896E+09 | 70218494.84 | 0.754677E+09 | 0.877702E+09 | 0.328879E+09 |
July | 0.790707E+09 | 51041313.94 | 0.739666E+09 | 0.982124E+09 | 0.231960E+09 |
August | 0.684181E+09 | 10408210.89 | 0.673773E+09 | 0.797200E+09 | 0.313167E+09 |
September | 0.503881E+09 | 104683.35 | 0.503776E+09 | 0.441676E+09 | 0.513632E+09 |
October | 0.389227E+09 | 0.00 | 0.389227E+09 | 0.154392E+09 | 0.892288E+09 |
November | 0.253114E+09 | 0.00 | 0.253114E+09 | 31960875.35 | 0.116059E+10 |
December | 0.242463E+09 | 0.00 | 0.242463E+09 | 1111890.42 | 0.175513E+10 |
Annual Sum or Average | 0.608158E+10 | 0.164180E+09 | 0.591740E+10 | 0.421484E+10 | 0.111227E+11 |
Minimum of Months | 0.242463E+09 | 0.00 | 0.242463E+09 | 39569.38 | 0.231960E+09 |
Maximum of Months | 0.824896E+09 | 70218494.84 | 0.754677E+09 | 0.982124E+09 | 0.177821E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259049E+09 | 0.00 | 0.259049E+09 | 39560.98 | 0.177821E+10 |
February | 0.356497E+09 | 0.00 | 0.356497E+09 | 9118476.19 | 0.150220E+10 |
March | 0.478653E+09 | 0.00 | 0.478653E+09 | 0.122035E+09 | 0.124032E+10 |
April | 0.590228E+09 | 2355208.95 | 0.587872E+09 | 0.268858E+09 | 0.866218E+09 |
May | 0.708677E+09 | 30051465.97 | 0.678625E+09 | 0.528613E+09 | 0.540086E+09 |
June | 0.824892E+09 | 70217980.28 | 0.754674E+09 | 0.877697E+09 | 0.328879E+09 |
July | 0.790703E+09 | 51040939.91 | 0.739662E+09 | 0.982120E+09 | 0.231959E+09 |
August | 0.684178E+09 | 10408134.61 | 0.673770E+09 | 0.797196E+09 | 0.313166E+09 |
September | 0.503878E+09 | 104682.59 | 0.503774E+09 | 0.441673E+09 | 0.513631E+09 |
October | 0.389225E+09 | 0.00 | 0.389225E+09 | 0.154390E+09 | 0.892288E+09 |
November | 0.253112E+09 | 0.00 | 0.253112E+09 | 31960359.32 | 0.116059E+10 |
December | 0.242462E+09 | 0.00 | 0.242462E+09 | 1111845.28 | 0.175513E+10 |
Annual Sum or Average | 0.608155E+10 | 0.164178E+09 | 0.591738E+10 | 0.421481E+10 | 0.111227E+11 |
Minimum of Months | 0.242462E+09 | 0.00 | 0.242462E+09 | 39560.98 | 0.231959E+09 |
Maximum of Months | 0.824892E+09 | 70217980.28 | 0.754674E+09 | 0.982120E+09 | 0.177821E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.259039E+09 | 0.00 | 0.259039E+09 | 39563.58 | 0.177814E+10 |
February | 0.356484E+09 | 0.00 | 0.356484E+09 | 9118333.27 | 0.150214E+10 |
March | 0.478634E+09 | 0.00 | 0.478634E+09 | 0.122031E+09 | 0.124027E+10 |
April | 0.590205E+09 | 2355122.65 | 0.587850E+09 | 0.268848E+09 | 0.866183E+09 |
May | 0.708650E+09 | 30050364.87 | 0.678599E+09 | 0.528594E+09 | 0.540064E+09 |
June | 0.824860E+09 | 70215407.46 | 0.754645E+09 | 0.877664E+09 | 0.328866E+09 |
July | 0.790673E+09 | 51039069.74 | 0.739634E+09 | 0.982082E+09 | 0.231950E+09 |
August | 0.684152E+09 | 10407753.25 | 0.673744E+09 | 0.797166E+09 | 0.313154E+09 |
September | 0.503859E+09 | 104678.75 | 0.503754E+09 | 0.441657E+09 | 0.513611E+09 |
October | 0.389211E+09 | 0.00 | 0.389211E+09 | 0.154385E+09 | 0.892252E+09 |
November | 0.253103E+09 | 0.00 | 0.253103E+09 | 31959329.18 | 0.116054E+10 |
December | 0.242453E+09 | 0.00 | 0.242453E+09 | 1111823.03 | 0.175506E+10 |
Annual Sum or Average | 0.608132E+10 | 0.164172E+09 | 0.591715E+10 | 0.421466E+10 | 0.111222E+11 |
Minimum of Months | 0.242453E+09 | 0.00 | 0.242453E+09 | 39563.58 | 0.231950E+09 |
Maximum of Months | 0.824860E+09 | 70215407.46 | 0.754645E+09 | 0.982082E+09 | 0.177814E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.526744E+09 | 0.169852E+09 | 0.356892E+09 | 0.186514E+09 | 0.178597E+10 |
February | 0.698097E+09 | 0.209482E+09 | 0.488615E+09 | 0.302094E+09 | 0.151187E+10 |
March | 0.110908E+10 | 0.464476E+09 | 0.644604E+09 | 0.826560E+09 | 0.123875E+10 |
April | 0.142059E+10 | 0.627691E+09 | 0.792894E+09 | 0.129437E+10 | 0.875436E+09 |
May | 0.164462E+10 | 0.727502E+09 | 0.917114E+09 | 0.176869E+10 | 0.599710E+09 |
June | 0.177751E+10 | 0.785572E+09 | 0.991938E+09 | 0.216076E+10 | 0.363984E+09 |
July | 0.176377E+10 | 0.776564E+09 | 0.987207E+09 | 0.231542E+10 | 0.247502E+09 |
August | 0.159288E+10 | 0.668604E+09 | 0.924276E+09 | 0.204348E+10 | 0.326489E+09 |
September | 0.128279E+10 | 0.568997E+09 | 0.713795E+09 | 0.147189E+10 | 0.536725E+09 |
October | 0.899497E+09 | 0.372056E+09 | 0.527441E+09 | 0.769176E+09 | 0.909438E+09 |
November | 0.493752E+09 | 0.158390E+09 | 0.335362E+09 | 0.274517E+09 | 0.118323E+10 |
December | 0.410746E+09 | 84868890.97 | 0.325877E+09 | 91451403.44 | 0.178426E+10 |
Annual Sum or Average | 0.136201E+11 | 0.561405E+10 | 0.800602E+10 | 0.135049E+11 | 0.113634E+11 |
Minimum of Months | 0.410746E+09 | 84868890.97 | 0.325877E+09 | 91451403.44 | 0.247502E+09 |
Maximum of Months | 0.177751E+10 | 0.785572E+09 | 0.991938E+09 | 0.231542E+10 | 0.178597E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.526744E+09 | 0.169852E+09 | 0.356892E+09 | 0.186514E+09 | 0.178597E+10 |
February | 0.698097E+09 | 0.209482E+09 | 0.488615E+09 | 0.302094E+09 | 0.151187E+10 |
March | 0.110908E+10 | 0.464476E+09 | 0.644604E+09 | 0.826560E+09 | 0.123875E+10 |
April | 0.142059E+10 | 0.627691E+09 | 0.792894E+09 | 0.129437E+10 | 0.875436E+09 |
May | 0.164462E+10 | 0.727502E+09 | 0.917114E+09 | 0.176869E+10 | 0.599710E+09 |
June | 0.177751E+10 | 0.785572E+09 | 0.991938E+09 | 0.216076E+10 | 0.363984E+09 |
July | 0.176377E+10 | 0.776564E+09 | 0.987207E+09 | 0.231542E+10 | 0.247502E+09 |
August | 0.159288E+10 | 0.668604E+09 | 0.924276E+09 | 0.204348E+10 | 0.326489E+09 |
September | 0.128279E+10 | 0.568997E+09 | 0.713795E+09 | 0.147189E+10 | 0.536725E+09 |
October | 0.899497E+09 | 0.372056E+09 | 0.527441E+09 | 0.769176E+09 | 0.909438E+09 |
November | 0.493752E+09 | 0.158390E+09 | 0.335362E+09 | 0.274517E+09 | 0.118323E+10 |
December | 0.410746E+09 | 84868890.97 | 0.325877E+09 | 91451403.44 | 0.178426E+10 |
Annual Sum or Average | 0.136201E+11 | 0.561405E+10 | 0.800602E+10 | 0.135049E+11 | 0.113634E+11 |
Minimum of Months | 0.410746E+09 | 84868890.97 | 0.325877E+09 | 91451403.44 | 0.247502E+09 |
Maximum of Months | 0.177751E+10 | 0.785572E+09 | 0.991938E+09 | 0.231542E+10 | 0.178597E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.526734E+09 | 0.169848E+09 | 0.356885E+09 | 0.186511E+09 | 0.178594E+10 |
February | 0.698084E+09 | 0.209478E+09 | 0.488606E+09 | 0.302088E+09 | 0.151184E+10 |
March | 0.110906E+10 | 0.464468E+09 | 0.644593E+09 | 0.826545E+09 | 0.123873E+10 |
April | 0.142056E+10 | 0.627679E+09 | 0.792880E+09 | 0.129435E+10 | 0.875420E+09 |
May | 0.164459E+10 | 0.727489E+09 | 0.917098E+09 | 0.176866E+10 | 0.599699E+09 |
June | 0.177748E+10 | 0.785558E+09 | 0.991919E+09 | 0.216072E+10 | 0.363977E+09 |
July | 0.176374E+10 | 0.776550E+09 | 0.987189E+09 | 0.231538E+10 | 0.247498E+09 |
August | 0.159285E+10 | 0.668592E+09 | 0.924259E+09 | 0.204344E+10 | 0.326483E+09 |
September | 0.128277E+10 | 0.568987E+09 | 0.713782E+09 | 0.147186E+10 | 0.536715E+09 |
October | 0.899481E+09 | 0.372049E+09 | 0.527431E+09 | 0.769162E+09 | 0.909421E+09 |
November | 0.493743E+09 | 0.158387E+09 | 0.335356E+09 | 0.274512E+09 | 0.118321E+10 |
December | 0.410738E+09 | 84867340.23 | 0.325871E+09 | 91449732.43 | 0.178422E+10 |
Annual Sum or Average | 0.136198E+11 | 0.561395E+10 | 0.800587E+10 | 0.135047E+11 | 0.113632E+11 |
Minimum of Months | 0.410738E+09 | 84867340.23 | 0.325871E+09 | 91449732.43 | 0.247498E+09 |
Maximum of Months | 0.177748E+10 | 0.785558E+09 | 0.991919E+09 | 0.231538E+10 | 0.178594E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111391E+10 | 0.650222E+09 | 0.463690E+09 | 0.877370E+09 | 0.147002E+10 |
February | 0.114873E+10 | 0.553906E+09 | 0.594824E+09 | 0.888488E+09 | 0.129692E+10 |
March | 0.155233E+10 | 0.872240E+09 | 0.680088E+09 | 0.149200E+10 | 0.109809E+10 |
April | 0.124410E+10 | 0.497145E+09 | 0.746959E+09 | 0.124533E+10 | 0.852582E+09 |
May | 0.112499E+10 | 0.326743E+09 | 0.798251E+09 | 0.124019E+10 | 0.585004E+09 |
June | 0.105787E+10 | 0.224166E+09 | 0.833705E+09 | 0.131129E+10 | 0.362287E+09 |
July | 0.111591E+10 | 0.270754E+09 | 0.845157E+09 | 0.153645E+10 | 0.254135E+09 |
August | 0.125279E+10 | 0.406184E+09 | 0.846608E+09 | 0.169455E+10 | 0.332586E+09 |
September | 0.140963E+10 | 0.686593E+09 | 0.723040E+09 | 0.175586E+10 | 0.516838E+09 |
October | 0.139377E+10 | 0.796145E+09 | 0.597623E+09 | 0.148550E+10 | 0.818748E+09 |
November | 0.965988E+09 | 0.545331E+09 | 0.420657E+09 | 0.888701E+09 | 0.102467E+10 |
December | 0.931451E+09 | 0.482067E+09 | 0.449384E+09 | 0.685735E+09 | 0.147870E+10 |
Annual Sum or Average | 0.143115E+11 | 0.631150E+10 | 0.799999E+10 | 0.151015E+11 | 0.100906E+11 |
Minimum of Months | 0.931451E+09 | 0.224166E+09 | 0.420657E+09 | 0.685735E+09 | 0.254135E+09 |
Maximum of Months | 0.155233E+10 | 0.872240E+09 | 0.846608E+09 | 0.175586E+10 | 0.147870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111390E+10 | 0.650217E+09 | 0.463687E+09 | 0.877361E+09 | 0.147002E+10 |
February | 0.114872E+10 | 0.553902E+09 | 0.594821E+09 | 0.888479E+09 | 0.129692E+10 |
March | 0.155232E+10 | 0.872234E+09 | 0.680084E+09 | 0.149198E+10 | 0.109809E+10 |
April | 0.124410E+10 | 0.497142E+09 | 0.746955E+09 | 0.124532E+10 | 0.852582E+09 |
May | 0.112499E+10 | 0.326741E+09 | 0.798247E+09 | 0.124018E+10 | 0.585004E+09 |
June | 0.105787E+10 | 0.224164E+09 | 0.833701E+09 | 0.131128E+10 | 0.362287E+09 |
July | 0.111590E+10 | 0.270752E+09 | 0.845153E+09 | 0.153644E+10 | 0.254134E+09 |
August | 0.125278E+10 | 0.406181E+09 | 0.846603E+09 | 0.169454E+10 | 0.332586E+09 |
September | 0.140962E+10 | 0.686588E+09 | 0.723036E+09 | 0.175584E+10 | 0.516838E+09 |
October | 0.139376E+10 | 0.796139E+09 | 0.597620E+09 | 0.148549E+10 | 0.818748E+09 |
November | 0.965981E+09 | 0.545327E+09 | 0.420654E+09 | 0.888693E+09 | 0.102467E+10 |
December | 0.931445E+09 | 0.482064E+09 | 0.449381E+09 | 0.685727E+09 | 0.147870E+10 |
Annual Sum or Average | 0.143114E+11 | 0.631145E+10 | 0.799994E+10 | 0.151013E+11 | 0.100906E+11 |
Minimum of Months | 0.931445E+09 | 0.224164E+09 | 0.420654E+09 | 0.685727E+09 | 0.254134E+09 |
Maximum of Months | 0.155232E+10 | 0.872234E+09 | 0.846603E+09 | 0.175584E+10 | 0.147870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111391E+10 | 0.650222E+09 | 0.463690E+09 | 0.877370E+09 | 0.147002E+10 |
February | 0.114873E+10 | 0.553906E+09 | 0.594824E+09 | 0.888488E+09 | 0.129692E+10 |
March | 0.155233E+10 | 0.872240E+09 | 0.680088E+09 | 0.149200E+10 | 0.109809E+10 |
April | 0.124410E+10 | 0.497145E+09 | 0.746959E+09 | 0.124533E+10 | 0.852582E+09 |
May | 0.112499E+10 | 0.326743E+09 | 0.798251E+09 | 0.124019E+10 | 0.585004E+09 |
June | 0.105787E+10 | 0.224166E+09 | 0.833705E+09 | 0.131129E+10 | 0.362287E+09 |
July | 0.111591E+10 | 0.270754E+09 | 0.845157E+09 | 0.153645E+10 | 0.254135E+09 |
August | 0.125279E+10 | 0.406184E+09 | 0.846608E+09 | 0.169455E+10 | 0.332586E+09 |
September | 0.140963E+10 | 0.686593E+09 | 0.723040E+09 | 0.175586E+10 | 0.516838E+09 |
October | 0.139377E+10 | 0.796145E+09 | 0.597623E+09 | 0.148550E+10 | 0.818748E+09 |
November | 0.965988E+09 | 0.545331E+09 | 0.420657E+09 | 0.888701E+09 | 0.102467E+10 |
December | 0.931451E+09 | 0.482067E+09 | 0.449384E+09 | 0.685735E+09 | 0.147870E+10 |
Annual Sum or Average | 0.143115E+11 | 0.631150E+10 | 0.799999E+10 | 0.151015E+11 | 0.100906E+11 |
Minimum of Months | 0.931451E+09 | 0.224166E+09 | 0.420657E+09 | 0.685735E+09 | 0.254135E+09 |
Maximum of Months | 0.155233E+10 | 0.872240E+09 | 0.846608E+09 | 0.175586E+10 | 0.147870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111390E+10 | 0.650217E+09 | 0.463687E+09 | 0.877361E+09 | 0.147002E+10 |
February | 0.114872E+10 | 0.553902E+09 | 0.594821E+09 | 0.888479E+09 | 0.129692E+10 |
March | 0.155232E+10 | 0.872234E+09 | 0.680084E+09 | 0.149198E+10 | 0.109809E+10 |
April | 0.124410E+10 | 0.497142E+09 | 0.746955E+09 | 0.124532E+10 | 0.852582E+09 |
May | 0.112499E+10 | 0.326741E+09 | 0.798247E+09 | 0.124018E+10 | 0.585004E+09 |
June | 0.105787E+10 | 0.224164E+09 | 0.833701E+09 | 0.131128E+10 | 0.362287E+09 |
July | 0.111590E+10 | 0.270752E+09 | 0.845153E+09 | 0.153644E+10 | 0.254134E+09 |
August | 0.125278E+10 | 0.406181E+09 | 0.846603E+09 | 0.169454E+10 | 0.332586E+09 |
September | 0.140962E+10 | 0.686588E+09 | 0.723036E+09 | 0.175584E+10 | 0.516838E+09 |
October | 0.139376E+10 | 0.796139E+09 | 0.597620E+09 | 0.148549E+10 | 0.818748E+09 |
November | 0.965981E+09 | 0.545327E+09 | 0.420654E+09 | 0.888693E+09 | 0.102467E+10 |
December | 0.931445E+09 | 0.482064E+09 | 0.449381E+09 | 0.685727E+09 | 0.147870E+10 |
Annual Sum or Average | 0.143114E+11 | 0.631145E+10 | 0.799994E+10 | 0.151013E+11 | 0.100906E+11 |
Minimum of Months | 0.931445E+09 | 0.224164E+09 | 0.420654E+09 | 0.685727E+09 | 0.254134E+09 |
Maximum of Months | 0.155232E+10 | 0.872234E+09 | 0.846603E+09 | 0.175584E+10 | 0.147870E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.111386E+10 | 0.650193E+09 | 0.463670E+09 | 0.877330E+09 | 0.146996E+10 |
February | 0.114868E+10 | 0.553882E+09 | 0.594798E+09 | 0.888448E+09 | 0.129687E+10 |
March | 0.155226E+10 | 0.872202E+09 | 0.680058E+09 | 0.149193E+10 | 0.109805E+10 |
April | 0.124405E+10 | 0.497123E+09 | 0.746927E+09 | 0.124527E+10 | 0.852548E+09 |
May | 0.112495E+10 | 0.326729E+09 | 0.798217E+09 | 0.124014E+10 | 0.584981E+09 |
June | 0.105783E+10 | 0.224156E+09 | 0.833670E+09 | 0.131123E+10 | 0.362272E+09 |
July | 0.111586E+10 | 0.270742E+09 | 0.845121E+09 | 0.153639E+10 | 0.254124E+09 |
August | 0.125274E+10 | 0.406166E+09 | 0.846571E+09 | 0.169448E+10 | 0.332572E+09 |
September | 0.140957E+10 | 0.686563E+09 | 0.723009E+09 | 0.175578E+10 | 0.516817E+09 |
October | 0.139371E+10 | 0.796110E+09 | 0.597597E+09 | 0.148544E+10 | 0.818715E+09 |
November | 0.965946E+09 | 0.545307E+09 | 0.420638E+09 | 0.888661E+09 | 0.102463E+10 |
December | 0.931411E+09 | 0.482046E+09 | 0.449365E+09 | 0.685704E+09 | 0.147864E+10 |
Annual Sum or Average | 0.143109E+11 | 0.631122E+10 | 0.799964E+10 | 0.151008E+11 | 0.100902E+11 |
Minimum of Months | 0.931411E+09 | 0.224156E+09 | 0.420638E+09 | 0.685704E+09 | 0.254124E+09 |
Maximum of Months | 0.155226E+10 | 0.872202E+09 | 0.846571E+09 | 0.175578E+10 | 0.147864E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.451937E+09 | 0.106097E+09 | 0.345840E+09 | 0.109463E+09 | 0.193525E+10 |
February | 0.661581E+09 | 0.170031E+09 | 0.491550E+09 | 0.244157E+09 | 0.167320E+10 |
March | 0.114801E+10 | 0.491550E+09 | 0.656458E+09 | 0.842284E+09 | 0.141206E+10 |
April | 0.136024E+10 | 0.557753E+09 | 0.802486E+09 | 0.118843E+10 | 0.105512E+10 |
May | 0.165811E+10 | 0.749357E+09 | 0.908749E+09 | 0.177576E+10 | 0.686611E+09 |
June | 0.193602E+10 | 0.910625E+09 | 0.102540E+10 | 0.235201E+10 | 0.449826E+09 |
July | 0.178857E+10 | 0.784172E+09 | 0.100440E+10 | 0.231289E+10 | 0.335565E+09 |
August | 0.161766E+10 | 0.687844E+09 | 0.929814E+09 | 0.204658E+10 | 0.434946E+09 |
September | 0.122938E+10 | 0.530917E+09 | 0.698467E+09 | 0.139451E+10 | 0.616395E+09 |
October | 0.823510E+09 | 0.290087E+09 | 0.533423E+09 | 0.660050E+09 | 0.104452E+10 |
November | 0.472273E+09 | 0.136092E+09 | 0.336181E+09 | 0.233430E+09 | 0.137044E+10 |
December | 0.423066E+09 | 92181302.71 | 0.330884E+09 | 94180151.22 | 0.204126E+10 |
Annual Sum or Average | 0.135704E+11 | 0.550671E+10 | 0.806365E+10 | 0.132537E+11 | 0.130552E+11 |
Minimum of Months | 0.423066E+09 | 92181302.71 | 0.330884E+09 | 94180151.22 | 0.335565E+09 |
Maximum of Months | 0.193602E+10 | 0.910625E+09 | 0.102540E+10 | 0.235201E+10 | 0.204126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.451937E+09 | 0.106097E+09 | 0.345840E+09 | 0.109463E+09 | 0.193525E+10 |
February | 0.661581E+09 | 0.170031E+09 | 0.491550E+09 | 0.244157E+09 | 0.167320E+10 |
March | 0.114801E+10 | 0.491550E+09 | 0.656458E+09 | 0.842284E+09 | 0.141206E+10 |
April | 0.136024E+10 | 0.557753E+09 | 0.802486E+09 | 0.118843E+10 | 0.105512E+10 |
May | 0.165811E+10 | 0.749357E+09 | 0.908749E+09 | 0.177576E+10 | 0.686611E+09 |
June | 0.193602E+10 | 0.910625E+09 | 0.102540E+10 | 0.235201E+10 | 0.449826E+09 |
July | 0.178857E+10 | 0.784172E+09 | 0.100440E+10 | 0.231289E+10 | 0.335565E+09 |
August | 0.161766E+10 | 0.687844E+09 | 0.929814E+09 | 0.204658E+10 | 0.434946E+09 |
September | 0.122938E+10 | 0.530917E+09 | 0.698467E+09 | 0.139451E+10 | 0.616395E+09 |
October | 0.823510E+09 | 0.290087E+09 | 0.533423E+09 | 0.660050E+09 | 0.104452E+10 |
November | 0.472273E+09 | 0.136092E+09 | 0.336181E+09 | 0.233430E+09 | 0.137044E+10 |
December | 0.423066E+09 | 92181302.71 | 0.330884E+09 | 94180151.22 | 0.204126E+10 |
Annual Sum or Average | 0.135704E+11 | 0.550671E+10 | 0.806365E+10 | 0.132537E+11 | 0.130552E+11 |
Minimum of Months | 0.423066E+09 | 92181302.71 | 0.330884E+09 | 94180151.22 | 0.335565E+09 |
Maximum of Months | 0.193602E+10 | 0.910625E+09 | 0.102540E+10 | 0.235201E+10 | 0.204126E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.451928E+09 | 0.106095E+09 | 0.345833E+09 | 0.109461E+09 | 0.193522E+10 |
February | 0.661569E+09 | 0.170028E+09 | 0.491541E+09 | 0.244152E+09 | 0.167317E+10 |
March | 0.114799E+10 | 0.491541E+09 | 0.656446E+09 | 0.842268E+09 | 0.141204E+10 |
April | 0.136021E+10 | 0.557743E+09 | 0.802472E+09 | 0.118841E+10 | 0.105510E+10 |
May | 0.165808E+10 | 0.749343E+09 | 0.908733E+09 | 0.177573E+10 | 0.686599E+09 |
June | 0.193599E+10 | 0.910608E+09 | 0.102538E+10 | 0.235196E+10 | 0.449818E+09 |
July | 0.178854E+10 | 0.784157E+09 | 0.100438E+10 | 0.231285E+10 | 0.335559E+09 |
August | 0.161763E+10 | 0.687831E+09 | 0.929797E+09 | 0.204654E+10 | 0.434938E+09 |
September | 0.122936E+10 | 0.530908E+09 | 0.698454E+09 | 0.139448E+10 | 0.616384E+09 |
October | 0.823495E+09 | 0.290082E+09 | 0.533413E+09 | 0.660038E+09 | 0.104450E+10 |
November | 0.472264E+09 | 0.136090E+09 | 0.336175E+09 | 0.233425E+09 | 0.137042E+10 |
December | 0.423058E+09 | 92179618.36 | 0.330878E+09 | 94178430.34 | 0.204122E+10 |
Annual Sum or Average | 0.135701E+11 | 0.550661E+10 | 0.806350E+10 | 0.132535E+11 | 0.130550E+11 |
Minimum of Months | 0.423058E+09 | 92179618.36 | 0.330878E+09 | 94178430.34 | 0.335559E+09 |
Maximum of Months | 0.193599E+10 | 0.910608E+09 | 0.102538E+10 | 0.235196E+10 | 0.204122E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129527E+10 | 0.00 | 0.129527E+10 | 13031336.63 | 0.808054E+10 |
February | 0.178252E+10 | 0.00 | 0.178252E+10 | 95445642.20 | 0.682238E+10 |
March | 0.239330E+10 | 0.00 | 0.239330E+10 | 0.733740E+09 | 0.550599E+10 |
April | 0.295118E+10 | 11776378.66 | 0.293940E+10 | 0.155082E+10 | 0.378778E+10 |
May | 0.354343E+10 | 0.150262E+09 | 0.339317E+10 | 0.273106E+10 | 0.252327E+10 |
June | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.441951E+10 | 0.158048E+10 |
July | 0.395357E+10 | 0.255212E+09 | 0.369836E+10 | 0.493213E+10 | 0.114026E+10 |
August | 0.342094E+10 | 52042148.80 | 0.336890E+10 | 0.402202E+10 | 0.152094E+10 |
September | 0.251943E+10 | 523427.78 | 0.251890E+10 | 0.226088E+10 | 0.239445E+10 |
October | 0.194616E+10 | 0.00 | 0.194616E+10 | 0.916540E+09 | 0.391382E+10 |
November | 0.126558E+10 | 0.00 | 0.126558E+10 | 0.251895E+09 | 0.492978E+10 |
December | 0.121233E+10 | 0.00 | 0.121233E+10 | 16209371.35 | 0.771209E+10 |
Annual Sum or Average | 0.304082E+11 | 0.820915E+09 | 0.295873E+11 | 0.219433E+11 | 0.499118E+11 |
Minimum of Months | 0.121233E+10 | 0.00 | 0.121233E+10 | 13031336.63 | 0.114026E+10 |
Maximum of Months | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.493213E+10 | 0.808054E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158021E+10 | 0.509550E+09 | 0.107067E+10 | 0.595783E+09 | 0.490055E+10 |
February | 0.209427E+10 | 0.628439E+09 | 0.146583E+10 | 0.967336E+09 | 0.418707E+10 |
March | 0.332721E+10 | 0.139341E+10 | 0.193379E+10 | 0.255859E+10 | 0.338913E+10 |
April | 0.426171E+10 | 0.188305E+10 | 0.237866E+10 | 0.394775E+10 | 0.241249E+10 |
May | 0.493380E+10 | 0.218248E+10 | 0.275132E+10 | 0.530094E+10 | 0.171742E+10 |
June | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.644376E+10 | 0.107932E+10 |
July | 0.529126E+10 | 0.232967E+10 | 0.296159E+10 | 0.689313E+10 | 0.775677E+09 |
August | 0.477859E+10 | 0.200579E+10 | 0.277280E+10 | 0.608334E+10 | 0.101620E+10 |
September | 0.384834E+10 | 0.170698E+10 | 0.214136E+10 | 0.440996E+10 | 0.153960E+10 |
October | 0.269846E+10 | 0.111616E+10 | 0.158231E+10 | 0.237708E+10 | 0.247405E+10 |
November | 0.148124E+10 | 0.475165E+09 | 0.100608E+10 | 0.896991E+09 | 0.313791E+10 |
December | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.307600E+09 | 0.483561E+10 |
Annual Sum or Average | 0.408598E+11 | 0.168420E+11 | 0.240178E+11 | 0.407823E+11 | 0.314650E+11 |
Minimum of Months | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.307600E+09 | 0.775677E+09 |
Maximum of Months | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.689313E+10 | 0.490055E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.556966E+10 | 0.325118E+10 | 0.231849E+10 | 0.443208E+10 | 0.696094E+10 |
February | 0.574376E+10 | 0.276959E+10 | 0.297417E+10 | 0.448768E+10 | 0.616775E+10 |
March | 0.776178E+10 | 0.436129E+10 | 0.340048E+10 | 0.748225E+10 | 0.519521E+10 |
April | 0.622062E+10 | 0.248578E+10 | 0.373484E+10 | 0.626457E+10 | 0.400307E+10 |
May | 0.562505E+10 | 0.163375E+10 | 0.399130E+10 | 0.617684E+10 | 0.282983E+10 |
June | 0.528942E+10 | 0.112085E+10 | 0.416856E+10 | 0.653269E+10 | 0.176110E+10 |
July | 0.557963E+10 | 0.135380E+10 | 0.422583E+10 | 0.765373E+10 | 0.126432E+10 |
August | 0.626405E+10 | 0.203096E+10 | 0.423309E+10 | 0.844169E+10 | 0.165086E+10 |
September | 0.704828E+10 | 0.343304E+10 | 0.361525E+10 | 0.873142E+10 | 0.252709E+10 |
October | 0.696897E+10 | 0.398081E+10 | 0.298816E+10 | 0.741938E+10 | 0.389955E+10 |
November | 0.483003E+10 | 0.272671E+10 | 0.210332E+10 | 0.449263E+10 | 0.476352E+10 |
December | 0.465734E+10 | 0.241039E+10 | 0.224696E+10 | 0.350238E+10 | 0.686212E+10 |
Annual Sum or Average | 0.715586E+11 | 0.315582E+11 | 0.400004E+11 | 0.756174E+11 | 0.478853E+11 |
Minimum of Months | 0.465734E+10 | 0.112085E+10 | 0.210332E+10 | 0.350238E+10 | 0.126432E+10 |
Maximum of Months | 0.776178E+10 | 0.436129E+10 | 0.423309E+10 | 0.873142E+10 | 0.696094E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135580E+10 | 0.318288E+09 | 0.103751E+10 | 0.359306E+09 | 0.519002E+10 |
February | 0.198472E+10 | 0.510089E+09 | 0.147464E+10 | 0.816034E+09 | 0.441953E+10 |
March | 0.344399E+10 | 0.147464E+10 | 0.196935E+10 | 0.268865E+10 | 0.358364E+10 |
April | 0.408068E+10 | 0.167324E+10 | 0.240743E+10 | 0.375926E+10 | 0.262187E+10 |
May | 0.497427E+10 | 0.224805E+10 | 0.272622E+10 | 0.537751E+10 | 0.189004E+10 |
June | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.708802E+10 | 0.123525E+10 |
July | 0.536566E+10 | 0.235249E+10 | 0.301317E+10 | 0.699733E+10 | 0.911494E+09 |
August | 0.485292E+10 | 0.206351E+10 | 0.278941E+10 | 0.622026E+10 | 0.115115E+10 |
September | 0.368811E+10 | 0.159274E+10 | 0.209538E+10 | 0.422814E+10 | 0.167932E+10 |
October | 0.247051E+10 | 0.870254E+09 | 0.160025E+10 | 0.212139E+10 | 0.263796E+10 |
November | 0.141680E+10 | 0.408272E+09 | 0.100853E+10 | 0.812690E+09 | 0.329197E+10 |
December | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.341965E+09 | 0.503279E+10 |
Annual Sum or Average | 0.407107E+11 | 0.165200E+11 | 0.241907E+11 | 0.408105E+11 | 0.336450E+11 |
Minimum of Months | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.341965E+09 | 0.911494E+09 |
Maximum of Months | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.708802E+10 | 0.519002E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.129527E+10 | 0.00 | 0.129527E+10 | 22650193.24 | 0.782391E+10 |
February | 0.178252E+10 | 0.00 | 0.178252E+10 | 0.114856E+09 | 0.659871E+10 |
March | 0.239330E+10 | 0.00 | 0.239330E+10 | 0.792393E+09 | 0.518176E+10 |
April | 0.295118E+10 | 11776378.66 | 0.293940E+10 | 0.166511E+10 | 0.349601E+10 |
May | 0.354343E+10 | 0.150262E+09 | 0.339317E+10 | 0.281971E+10 | 0.236954E+10 |
June | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.441683E+10 | 0.154835E+10 |
July | 0.395357E+10 | 0.255212E+09 | 0.369836E+10 | 0.489386E+10 | 0.114198E+10 |
August | 0.342094E+10 | 52042148.80 | 0.336890E+10 | 0.400705E+10 | 0.149574E+10 |
September | 0.251943E+10 | 523427.78 | 0.251890E+10 | 0.231230E+10 | 0.224232E+10 |
October | 0.194616E+10 | 0.00 | 0.194616E+10 | 0.104375E+10 | 0.349759E+10 |
November | 0.126558E+10 | 0.00 | 0.126558E+10 | 0.315146E+09 | 0.447174E+10 |
December | 0.121233E+10 | 0.00 | 0.121233E+10 | 23968673.12 | 0.738655E+10 |
Annual Sum or Average | 0.304082E+11 | 0.820915E+09 | 0.295873E+11 | 0.224276E+11 | 0.472542E+11 |
Minimum of Months | 0.121233E+10 | 0.00 | 0.121233E+10 | 22650193.24 | 0.114198E+10 |
Maximum of Months | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.489386E+10 | 0.782391E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.158021E+10 | 0.509550E+09 | 0.107067E+10 | 0.614041E+09 | 0.474182E+10 |
February | 0.209427E+10 | 0.628439E+09 | 0.146583E+10 | 0.994168E+09 | 0.405267E+10 |
March | 0.332721E+10 | 0.139341E+10 | 0.193379E+10 | 0.261989E+10 | 0.318762E+10 |
April | 0.426171E+10 | 0.188305E+10 | 0.237866E+10 | 0.401951E+10 | 0.225311E+10 |
May | 0.493380E+10 | 0.218248E+10 | 0.275132E+10 | 0.532676E+10 | 0.164112E+10 |
June | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.642273E+10 | 0.106949E+10 |
July | 0.529126E+10 | 0.232967E+10 | 0.296159E+10 | 0.685710E+10 | 0.784798E+09 |
August | 0.477859E+10 | 0.200579E+10 | 0.277280E+10 | 0.606078E+10 | 0.101063E+10 |
September | 0.384834E+10 | 0.170698E+10 | 0.214136E+10 | 0.442803E+10 | 0.147066E+10 |
October | 0.269846E+10 | 0.111616E+10 | 0.158231E+10 | 0.247182E+10 | 0.223688E+10 |
November | 0.148124E+10 | 0.475165E+09 | 0.100608E+10 | 0.956659E+09 | 0.285730E+10 |
December | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.323552E+09 | 0.463484E+10 |
Annual Sum or Average | 0.408598E+11 | 0.168420E+11 | 0.240178E+11 | 0.410950E+11 | 0.299409E+11 |
Minimum of Months | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.323552E+09 | 0.784798E+09 |
Maximum of Months | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.685710E+10 | 0.474182E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.556966E+10 | 0.325118E+10 | 0.231849E+10 | 0.449216E+10 | 0.668730E+10 |
February | 0.574376E+10 | 0.276959E+10 | 0.297417E+10 | 0.454269E+10 | 0.593423E+10 |
March | 0.776178E+10 | 0.436129E+10 | 0.340048E+10 | 0.758650E+10 | 0.485398E+10 |
April | 0.622062E+10 | 0.248578E+10 | 0.373484E+10 | 0.636408E+10 | 0.371979E+10 |
May | 0.562505E+10 | 0.163375E+10 | 0.399130E+10 | 0.621755E+10 | 0.268064E+10 |
June | 0.528942E+10 | 0.112085E+10 | 0.416856E+10 | 0.650879E+10 | 0.172607E+10 |
July | 0.557963E+10 | 0.135380E+10 | 0.422583E+10 | 0.760380E+10 | 0.126801E+10 |
August | 0.626405E+10 | 0.203096E+10 | 0.423309E+10 | 0.840821E+10 | 0.163255E+10 |
September | 0.704828E+10 | 0.343304E+10 | 0.361525E+10 | 0.874773E+10 | 0.240931E+10 |
October | 0.696897E+10 | 0.398081E+10 | 0.298816E+10 | 0.755380E+10 | 0.352759E+10 |
November | 0.483003E+10 | 0.272671E+10 | 0.210332E+10 | 0.460909E+10 | 0.431835E+10 |
December | 0.465734E+10 | 0.241039E+10 | 0.224696E+10 | 0.356750E+10 | 0.653824E+10 |
Annual Sum or Average | 0.715586E+11 | 0.315582E+11 | 0.400004E+11 | 0.762019E+11 | 0.452960E+11 |
Minimum of Months | 0.465734E+10 | 0.112085E+10 | 0.210332E+10 | 0.356750E+10 | 0.126801E+10 |
Maximum of Months | 0.776178E+10 | 0.436129E+10 | 0.423309E+10 | 0.874773E+10 | 0.668730E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.135580E+10 | 0.318288E+09 | 0.103751E+10 | 0.372959E+09 | 0.501541E+10 |
February | 0.198472E+10 | 0.510089E+09 | 0.147464E+10 | 0.831109E+09 | 0.428205E+10 |
March | 0.344399E+10 | 0.147464E+10 | 0.196935E+10 | 0.273169E+10 | 0.338223E+10 |
April | 0.408068E+10 | 0.167324E+10 | 0.240743E+10 | 0.381466E+10 | 0.245327E+10 |
May | 0.497427E+10 | 0.224805E+10 | 0.272622E+10 | 0.540363E+10 | 0.180085E+10 |
June | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.706531E+10 | 0.121487E+10 |
July | 0.536566E+10 | 0.235249E+10 | 0.301317E+10 | 0.696152E+10 | 0.912121E+09 |
August | 0.485292E+10 | 0.206351E+10 | 0.278941E+10 | 0.619845E+10 | 0.113874E+10 |
September | 0.368811E+10 | 0.159274E+10 | 0.209538E+10 | 0.424523E+10 | 0.160204E+10 |
October | 0.247051E+10 | 0.870254E+09 | 0.160025E+10 | 0.218901E+10 | 0.241539E+10 |
November | 0.141680E+10 | 0.408272E+09 | 0.100853E+10 | 0.856595E+09 | 0.303619E+10 |
December | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.355203E+09 | 0.483368E+10 |
Annual Sum or Average | 0.407107E+11 | 0.165200E+11 | 0.241907E+11 | 0.410254E+11 | 0.320869E+11 |
Minimum of Months | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.355203E+09 | 0.912121E+09 |
Maximum of Months | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.706531E+10 | 0.501541E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.07 | 3319.50 | 483.59 | 0.00 | 483.59 | 0.00 | 0.00 |
February | 18.85 | 3104.73 | 736.81 | 0.00 | 736.81 | 0.00 | 0.00 |
March | 227.81 | 2315.38 | 893.54 | 0.00 | 893.54 | 0.00 | 0.00 |
April | 518.63 | 1670.93 | 1138.55 | 4.54 | 1134.01 | 0.00 | 0.00 |
May | 986.81 | 1008.22 | 1322.94 | 56.10 | 1266.84 | 0.00 | 0.00 |
June | 1693.08 | 634.41 | 1591.22 | 135.45 | 1455.77 | 0.00 | 0.00 |
July | 1833.40 | 433.02 | 1476.07 | 95.28 | 1380.79 | 0.00 | 0.00 |
August | 1488.19 | 584.61 | 1277.21 | 19.43 | 1257.78 | 0.00 | 0.00 |
September | 851.99 | 990.79 | 971.98 | 0.20 | 971.78 | 0.00 | 0.00 |
October | 288.21 | 1665.70 | 726.60 | 0.00 | 726.60 | 0.00 | 0.00 |
November | 61.65 | 2238.77 | 488.26 | 0.00 | 488.26 | 0.00 | 0.00 |
December | 2.08 | 3276.43 | 452.62 | 0.00 | 452.62 | 0.00 | 0.00 |
Annual Sum or Average | 668.25 | 1763.47 | 964.22 | 26.03 | 938.19 | 0.00 | 0.00 |
Minimum of Months | 0.07 | 433.02 | 452.62 | 0.00 | 452.62 | 0.00 | 0.00 |
Maximum of Months | 1833.40 | 3319.50 | 1591.22 | 135.45 | 1455.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 208.91 | 2000.40 | 589.99 | 190.24 | 399.74 | 0.00 | 0.00 |
February | 374.62 | 1874.83 | 865.69 | 259.77 | 605.92 | 0.00 | 0.00 |
March | 925.80 | 1387.48 | 1242.24 | 520.24 | 722.00 | 0.00 | 0.00 |
April | 1498.10 | 1013.23 | 1644.19 | 726.49 | 917.70 | 0.00 | 0.00 |
May | 1981.05 | 671.71 | 1842.08 | 814.85 | 1027.23 | 0.00 | 0.00 |
June | 2500.86 | 421.28 | 2057.29 | 909.22 | 1148.07 | 0.00 | 0.00 |
July | 2593.43 | 277.22 | 1975.54 | 869.80 | 1105.74 | 0.00 | 0.00 |
August | 2288.83 | 365.69 | 1784.13 | 748.88 | 1035.25 | 0.00 | 0.00 |
September | 1703.56 | 621.21 | 1484.70 | 658.56 | 826.15 | 0.00 | 0.00 |
October | 861.53 | 1018.63 | 1007.50 | 416.73 | 590.77 | 0.00 | 0.00 |
November | 317.73 | 1369.47 | 571.47 | 183.32 | 388.15 | 0.00 | 0.00 |
December | 102.43 | 1998.48 | 460.06 | 95.06 | 365.00 | 0.00 | 0.00 |
Annual Sum or Average | 1284.71 | 1080.98 | 1295.66 | 534.06 | 761.60 | 0.00 | 0.00 |
Minimum of Months | 102.43 | 277.22 | 460.06 | 95.06 | 365.00 | 0.00 | 0.00 |
Maximum of Months | 2593.43 | 2000.40 | 2057.29 | 909.22 | 1148.07 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1637.84 | 2744.19 | 2079.41 | 1213.81 | 865.60 | 0.00 | 0.00 |
February | 1836.30 | 2680.45 | 2374.17 | 1144.80 | 1229.37 | 0.00 | 0.00 |
March | 2785.21 | 2049.89 | 2897.83 | 1628.27 | 1269.56 | 0.00 | 0.00 |
April | 2402.22 | 1644.63 | 2399.87 | 958.99 | 1440.88 | 0.00 | 0.00 |
May | 2315.15 | 1092.07 | 2100.10 | 609.95 | 1490.15 | 0.00 | 0.00 |
June | 2529.47 | 698.85 | 2040.62 | 432.41 | 1608.21 | 0.00 | 0.00 |
July | 2868.20 | 474.41 | 2083.14 | 505.43 | 1577.71 | 0.00 | 0.00 |
August | 3163.33 | 620.86 | 2338.67 | 758.25 | 1580.42 | 0.00 | 0.00 |
September | 3387.03 | 996.98 | 2719.17 | 1324.43 | 1394.74 | 0.00 | 0.00 |
October | 2773.08 | 1528.41 | 2601.84 | 1486.22 | 1115.62 | 0.00 | 0.00 |
November | 1714.29 | 1976.59 | 1863.38 | 1051.94 | 811.44 | 0.00 | 0.00 |
December | 1280.10 | 2760.39 | 1738.80 | 899.91 | 838.89 | 0.00 | 0.00 |
Annual Sum or Average | 2394.29 | 1599.84 | 2269.05 | 1000.67 | 1268.38 | 0.00 | 0.00 |
Minimum of Months | 1280.10 | 474.41 | 1738.80 | 432.41 | 811.44 | 0.00 | 0.00 |
Maximum of Months | 3387.03 | 2760.39 | 2897.83 | 1628.27 | 1608.21 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 122.61 | 2167.61 | 506.20 | 118.84 | 387.36 | 0.00 | 0.00 |
February | 302.77 | 2074.89 | 820.41 | 210.85 | 609.56 | 0.00 | 0.00 |
March | 943.41 | 1581.60 | 1285.84 | 550.57 | 735.28 | 0.00 | 0.00 |
April | 1375.49 | 1221.20 | 1574.34 | 645.54 | 928.80 | 0.00 | 0.00 |
May | 1988.97 | 769.05 | 1857.19 | 839.33 | 1017.86 | 0.00 | 0.00 |
June | 2722.21 | 520.63 | 2240.75 | 1053.96 | 1186.79 | 0.00 | 0.00 |
July | 2590.59 | 375.85 | 2003.32 | 878.32 | 1124.99 | 0.00 | 0.00 |
August | 2292.30 | 487.17 | 1811.88 | 770.43 | 1041.45 | 0.00 | 0.00 |
September | 1614.01 | 713.42 | 1422.89 | 614.48 | 808.41 | 0.00 | 0.00 |
October | 739.30 | 1169.93 | 922.38 | 324.92 | 597.47 | 0.00 | 0.00 |
November | 270.17 | 1586.15 | 546.61 | 157.51 | 389.10 | 0.00 | 0.00 |
December | 105.49 | 2286.34 | 473.86 | 103.25 | 370.61 | 0.00 | 0.00 |
Annual Sum or Average | 1260.81 | 1241.93 | 1290.93 | 523.85 | 767.09 | 0.00 | 0.00 |
Minimum of Months | 105.49 | 375.85 | 473.86 | 103.25 | 370.61 | 0.00 | 0.00 |
Maximum of Months | 2722.21 | 2286.34 | 2240.75 | 1053.96 | 1186.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 4.87 | 3016.93 | 483.60 | 0.00 | 483.60 | 0.00 | 0.00 |
February | 39.45 | 2820.10 | 736.82 | 0.00 | 736.82 | 0.00 | 0.00 |
March | 273.95 | 2055.70 | 893.56 | 0.00 | 893.56 | 0.00 | 0.00 |
April | 598.31 | 1461.34 | 1138.57 | 4.54 | 1134.03 | 0.00 | 0.00 |
May | 1019.66 | 942.08 | 1322.97 | 56.10 | 1266.86 | 0.00 | 0.00 |
June | 1705.06 | 609.75 | 1591.25 | 135.46 | 1455.79 | 0.00 | 0.00 |
July | 1841.45 | 425.72 | 1476.09 | 95.29 | 1380.81 | 0.00 | 0.00 |
August | 1501.65 | 567.85 | 1277.23 | 19.43 | 1257.80 | 0.00 | 0.00 |
September | 872.25 | 923.78 | 972.00 | 0.20 | 971.80 | 0.00 | 0.00 |
October | 342.20 | 1461.25 | 726.61 | 0.00 | 726.61 | 0.00 | 0.00 |
November | 97.18 | 1901.92 | 488.27 | 0.00 | 488.27 | 0.00 | 0.00 |
December | 6.05 | 2879.36 | 452.63 | 0.00 | 452.63 | 0.00 | 0.00 |
Annual Sum or Average | 695.82 | 1582.69 | 964.24 | 26.03 | 938.21 | 0.00 | 0.00 |
Minimum of Months | 4.87 | 425.72 | 452.63 | 0.00 | 452.63 | 0.00 | 0.00 |
Maximum of Months | 1841.45 | 3016.93 | 1591.25 | 135.46 | 1455.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 222.44 | 1829.66 | 589.98 | 190.24 | 399.74 | 0.00 | 0.00 |
February | 399.86 | 1730.77 | 865.69 | 259.77 | 605.92 | 0.00 | 0.00 |
March | 955.27 | 1265.36 | 1242.24 | 520.24 | 722.00 | 0.00 | 0.00 |
April | 1523.05 | 930.74 | 1644.18 | 726.49 | 917.69 | 0.00 | 0.00 |
May | 1979.14 | 641.21 | 1842.07 | 814.85 | 1027.22 | 0.00 | 0.00 |
June | 2486.02 | 416.41 | 2057.28 | 909.22 | 1148.06 | 0.00 | 0.00 |
July | 2573.60 | 289.60 | 1975.53 | 869.80 | 1105.73 | 0.00 | 0.00 |
August | 2271.26 | 379.41 | 1784.12 | 748.88 | 1035.24 | 0.00 | 0.00 |
September | 1701.37 | 593.98 | 1484.70 | 658.56 | 826.14 | 0.00 | 0.00 |
October | 887.50 | 923.70 | 1007.49 | 416.73 | 590.77 | 0.00 | 0.00 |
November | 346.06 | 1210.61 | 571.47 | 183.32 | 388.15 | 0.00 | 0.00 |
December | 114.84 | 1805.41 | 460.06 | 95.06 | 365.00 | 0.00 | 0.00 |
Annual Sum or Average | 1293.20 | 997.75 | 1295.66 | 534.06 | 761.60 | 0.00 | 0.00 |
Minimum of Months | 114.84 | 289.60 | 460.06 | 95.06 | 365.00 | 0.00 | 0.00 |
Maximum of Months | 2573.60 | 1829.66 | 2057.28 | 909.22 | 1148.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1654.75 | 2598.92 | 2079.47 | 1213.85 | 865.62 | 0.00 | 0.00 |
February | 1855.03 | 2549.50 | 2374.24 | 1144.84 | 1229.40 | 0.00 | 0.00 |
March | 2793.55 | 1939.67 | 2897.92 | 1628.32 | 1269.59 | 0.00 | 0.00 |
April | 2416.89 | 1544.40 | 2399.93 | 959.02 | 1440.91 | 0.00 | 0.00 |
May | 2306.17 | 1056.54 | 2100.15 | 609.97 | 1490.18 | 0.00 | 0.00 |
June | 2520.33 | 679.44 | 2040.67 | 432.43 | 1608.24 | 0.00 | 0.00 |
July | 2857.58 | 472.04 | 2083.19 | 505.45 | 1577.74 | 0.00 | 0.00 |
August | 3151.77 | 616.36 | 2338.73 | 758.27 | 1580.45 | 0.00 | 0.00 |
September | 3368.60 | 974.96 | 2719.24 | 1324.47 | 1394.77 | 0.00 | 0.00 |
October | 2770.08 | 1455.93 | 2601.91 | 1486.26 | 1115.65 | 0.00 | 0.00 |
November | 1733.27 | 1837.78 | 1863.44 | 1051.97 | 811.46 | 0.00 | 0.00 |
December | 1307.64 | 2562.02 | 1738.85 | 899.94 | 838.92 | 0.00 | 0.00 |
Annual Sum or Average | 2397.81 | 1518.43 | 2269.11 | 1000.70 | 1268.41 | 0.00 | 0.00 |
Minimum of Months | 1307.64 | 472.04 | 1738.85 | 432.43 | 811.46 | 0.00 | 0.00 |
Maximum of Months | 3368.60 | 2598.92 | 2897.92 | 1628.32 | 1608.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 134.15 | 1937.73 | 506.20 | 118.84 | 387.36 | 0.00 | 0.00 |
February | 337.32 | 1826.85 | 820.40 | 210.85 | 609.55 | 0.00 | 0.00 |
March | 1003.83 | 1337.98 | 1285.84 | 550.57 | 735.27 | 0.00 | 0.00 |
April | 1450.33 | 1011.52 | 1574.33 | 645.54 | 928.79 | 0.00 | 0.00 |
May | 2007.73 | 705.66 | 1857.18 | 839.33 | 1017.85 | 0.00 | 0.00 |
June | 2734.58 | 476.56 | 2240.74 | 1053.95 | 1186.79 | 0.00 | 0.00 |
July | 2612.50 | 340.31 | 2003.31 | 878.32 | 1124.99 | 0.00 | 0.00 |
August | 2322.38 | 429.79 | 1811.87 | 770.43 | 1041.45 | 0.00 | 0.00 |
September | 1631.23 | 647.89 | 1422.88 | 614.48 | 808.40 | 0.00 | 0.00 |
October | 792.04 | 984.90 | 922.38 | 324.92 | 597.47 | 0.00 | 0.00 |
November | 313.54 | 1270.05 | 546.61 | 157.51 | 389.09 | 0.00 | 0.00 |
December | 127.67 | 1879.03 | 473.86 | 103.25 | 370.61 | 0.00 | 0.00 |
Annual Sum or Average | 1294.09 | 1066.88 | 1290.93 | 523.84 | 767.08 | 0.00 | 0.00 |
Minimum of Months | 127.67 | 340.31 | 473.86 | 103.25 | 370.61 | 0.00 | 0.00 |
Maximum of Months | 2734.58 | 1937.73 | 2240.74 | 1053.95 | 1186.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 8.46 | 2921.11 | 483.60 | 0.00 | 483.60 | 0.00 | 0.00 |
February | 47.48 | 2727.64 | 736.82 | 0.00 | 736.82 | 0.00 | 0.00 |
March | 295.85 | 1934.65 | 893.56 | 0.00 | 893.56 | 0.00 | 0.00 |
April | 642.40 | 1348.77 | 1138.57 | 4.54 | 1134.03 | 0.00 | 0.00 |
May | 1052.76 | 884.68 | 1322.97 | 56.10 | 1266.86 | 0.00 | 0.00 |
June | 1704.02 | 597.36 | 1591.25 | 135.46 | 1455.79 | 0.00 | 0.00 |
July | 1827.16 | 426.37 | 1476.09 | 95.29 | 1380.81 | 0.00 | 0.00 |
August | 1496.06 | 558.45 | 1277.23 | 19.43 | 1257.80 | 0.00 | 0.00 |
September | 892.09 | 865.09 | 972.00 | 0.20 | 971.80 | 0.00 | 0.00 |
October | 389.69 | 1305.85 | 726.61 | 0.00 | 726.61 | 0.00 | 0.00 |
November | 121.58 | 1725.21 | 488.27 | 0.00 | 488.27 | 0.00 | 0.00 |
December | 8.95 | 2757.82 | 452.63 | 0.00 | 452.63 | 0.00 | 0.00 |
Annual Sum or Average | 711.18 | 1498.42 | 964.24 | 26.03 | 938.21 | 0.00 | 0.00 |
Minimum of Months | 8.46 | 426.37 | 452.63 | 0.00 | 452.63 | 0.00 | 0.00 |
Maximum of Months | 1827.16 | 2921.11 | 1591.25 | 135.46 | 1455.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 229.26 | 1770.39 | 589.98 | 190.24 | 399.74 | 0.00 | 0.00 |
February | 410.95 | 1675.21 | 865.69 | 259.77 | 605.92 | 0.00 | 0.00 |
March | 978.15 | 1190.12 | 1242.24 | 520.24 | 722.00 | 0.00 | 0.00 |
April | 1550.74 | 869.26 | 1644.18 | 726.49 | 917.69 | 0.00 | 0.00 |
May | 1988.78 | 612.72 | 1842.07 | 814.85 | 1027.22 | 0.00 | 0.00 |
June | 2477.90 | 412.61 | 2057.28 | 909.22 | 1148.06 | 0.00 | 0.00 |
July | 2560.15 | 293.01 | 1975.53 | 869.80 | 1105.73 | 0.00 | 0.00 |
August | 2262.84 | 377.33 | 1784.12 | 748.88 | 1035.24 | 0.00 | 0.00 |
September | 1708.34 | 567.39 | 1484.70 | 658.56 | 826.14 | 0.00 | 0.00 |
October | 922.87 | 835.15 | 1007.49 | 416.73 | 590.77 | 0.00 | 0.00 |
November | 369.08 | 1102.35 | 571.47 | 183.32 | 388.15 | 0.00 | 0.00 |
December | 120.80 | 1730.45 | 460.06 | 95.06 | 365.00 | 0.00 | 0.00 |
Annual Sum or Average | 1303.11 | 949.42 | 1295.66 | 534.06 | 761.60 | 0.00 | 0.00 |
Minimum of Months | 120.80 | 293.01 | 460.06 | 95.06 | 365.00 | 0.00 | 0.00 |
Maximum of Months | 2560.15 | 1770.39 | 2057.28 | 909.22 | 1148.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1677.18 | 2496.75 | 2079.47 | 1213.85 | 865.62 | 0.00 | 0.00 |
February | 1877.76 | 2452.97 | 2374.24 | 1144.84 | 1229.40 | 0.00 | 0.00 |
March | 2832.47 | 1812.27 | 2897.92 | 1628.32 | 1269.59 | 0.00 | 0.00 |
April | 2455.28 | 1435.10 | 2399.93 | 959.02 | 1440.91 | 0.00 | 0.00 |
May | 2321.37 | 1000.84 | 2100.15 | 609.97 | 1490.18 | 0.00 | 0.00 |
June | 2511.11 | 665.92 | 2040.67 | 432.43 | 1608.24 | 0.00 | 0.00 |
July | 2838.93 | 473.42 | 2083.19 | 505.45 | 1577.74 | 0.00 | 0.00 |
August | 3139.27 | 609.53 | 2338.73 | 758.27 | 1580.45 | 0.00 | 0.00 |
September | 3374.89 | 929.52 | 2719.24 | 1324.47 | 1394.77 | 0.00 | 0.00 |
October | 2820.27 | 1317.05 | 2601.91 | 1486.26 | 1115.65 | 0.00 | 0.00 |
November | 1778.20 | 1666.03 | 1863.44 | 1051.97 | 811.46 | 0.00 | 0.00 |
December | 1331.95 | 2441.10 | 1738.85 | 899.94 | 838.92 | 0.00 | 0.00 |
Annual Sum or Average | 2416.35 | 1436.33 | 2269.11 | 1000.70 | 1268.41 | 0.00 | 0.00 |
Minimum of Months | 1331.95 | 473.42 | 1738.85 | 432.43 | 811.46 | 0.00 | 0.00 |
Maximum of Months | 3374.89 | 2496.75 | 2897.92 | 1628.32 | 1608.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 139.25 | 1872.54 | 506.20 | 118.84 | 387.36 | 0.00 | 0.00 |
February | 343.55 | 1770.03 | 820.40 | 210.85 | 609.55 | 0.00 | 0.00 |
March | 1019.90 | 1262.78 | 1285.84 | 550.57 | 735.27 | 0.00 | 0.00 |
April | 1471.71 | 946.48 | 1574.33 | 645.54 | 928.79 | 0.00 | 0.00 |
May | 2017.48 | 672.36 | 1857.18 | 839.33 | 1017.85 | 0.00 | 0.00 |
June | 2725.82 | 468.70 | 2240.74 | 1053.95 | 1186.79 | 0.00 | 0.00 |
July | 2599.13 | 340.55 | 2003.31 | 878.32 | 1124.99 | 0.00 | 0.00 |
August | 2314.24 | 425.16 | 1811.87 | 770.43 | 1041.45 | 0.00 | 0.00 |
September | 1637.82 | 618.07 | 1422.88 | 614.48 | 808.40 | 0.00 | 0.00 |
October | 817.28 | 901.80 | 922.38 | 324.92 | 597.47 | 0.00 | 0.00 |
November | 330.48 | 1171.37 | 546.61 | 157.51 | 389.09 | 0.00 | 0.00 |
December | 132.62 | 1804.69 | 473.86 | 103.25 | 370.61 | 0.00 | 0.00 |
Annual Sum or Average | 1300.91 | 1017.47 | 1290.93 | 523.84 | 767.08 | 0.00 | 0.00 |
Minimum of Months | 132.62 | 340.55 | 473.86 | 103.25 | 370.61 | 0.00 | 0.00 |
Maximum of Months | 2725.82 | 1872.54 | 2240.74 | 1053.95 | 1186.79 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 197841.10 | 0.889096E+10 | 0.129524E+10 | 0.00 | 0.129524E+10 | 0.00 | 0.00 |
February | 45594034.84 | 0.751096E+10 | 0.178248E+10 | 0.00 | 0.178248E+10 | 0.00 | 0.00 |
March | 0.610179E+09 | 0.620152E+10 | 0.239325E+10 | 0.00 | 0.239325E+10 | 0.00 | 0.00 |
April | 0.134429E+10 | 0.433106E+10 | 0.295113E+10 | 11776027.47 | 0.293935E+10 | 0.00 | 0.00 |
May | 0.264306E+10 | 0.270041E+10 | 0.354337E+10 | 0.150257E+09 | 0.339311E+10 | 0.00 | 0.00 |
June | 0.438847E+10 | 0.164438E+10 | 0.412444E+10 | 0.351089E+09 | 0.377335E+10 | 0.00 | 0.00 |
July | 0.491058E+10 | 0.115979E+10 | 0.395350E+10 | 0.255204E+09 | 0.369830E+10 | 0.00 | 0.00 |
August | 0.398597E+10 | 0.156582E+10 | 0.342088E+10 | 52040596.80 | 0.336884E+10 | 0.00 | 0.00 |
September | 0.220836E+10 | 0.256814E+10 | 0.251938E+10 | 523412.17 | 0.251886E+10 | 0.00 | 0.00 |
October | 0.771951E+09 | 0.446140E+10 | 0.194612E+10 | 0.00 | 0.194612E+10 | 0.00 | 0.00 |
November | 0.159803E+09 | 0.580288E+10 | 0.126556E+10 | 0.00 | 0.126556E+10 | 0.00 | 0.00 |
December | 5559384.70 | 0.877560E+10 | 0.121231E+10 | 0.00 | 0.121231E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.210740E+11 | 0.556129E+11 | 0.304077E+11 | 0.820891E+09 | 0.295868E+11 | 0.00 | 0.00 |
Minimum of Months | 197841.10 | 0.115979E+10 | 0.121231E+10 | 0.00 | 0.121231E+10 | 0.00 | 0.00 |
Maximum of Months | 0.491058E+10 | 0.889096E+10 | 0.412444E+10 | 0.351089E+09 | 0.377335E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.559538E+09 | 0.535787E+10 | 0.158022E+10 | 0.509552E+09 | 0.107067E+10 | 0.00 | 0.00 |
February | 0.906276E+09 | 0.453558E+10 | 0.209428E+10 | 0.628441E+09 | 0.146584E+10 | 0.00 | 0.00 |
March | 0.247966E+10 | 0.371624E+10 | 0.332722E+10 | 0.139342E+10 | 0.193380E+10 | 0.00 | 0.00 |
April | 0.388308E+10 | 0.262629E+10 | 0.426173E+10 | 0.188306E+10 | 0.237867E+10 | 0.00 | 0.00 |
May | 0.530603E+10 | 0.179912E+10 | 0.493382E+10 | 0.218249E+10 | 0.275133E+10 | 0.00 | 0.00 |
June | 0.648224E+10 | 0.109195E+10 | 0.533250E+10 | 0.235670E+10 | 0.297579E+10 | 0.00 | 0.00 |
July | 0.694623E+10 | 0.742503E+09 | 0.529128E+10 | 0.232968E+10 | 0.296160E+10 | 0.00 | 0.00 |
August | 0.613040E+10 | 0.979462E+09 | 0.477861E+10 | 0.200580E+10 | 0.277281E+10 | 0.00 | 0.00 |
September | 0.441563E+10 | 0.161016E+10 | 0.384835E+10 | 0.170698E+10 | 0.214137E+10 | 0.00 | 0.00 |
October | 0.230751E+10 | 0.272830E+10 | 0.269847E+10 | 0.111616E+10 | 0.158231E+10 | 0.00 | 0.00 |
November | 0.823547E+09 | 0.354967E+10 | 0.148125E+10 | 0.475167E+09 | 0.100608E+10 | 0.00 | 0.00 |
December | 0.274353E+09 | 0.535273E+10 | 0.123223E+10 | 0.254605E+09 | 0.977624E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.405145E+11 | 0.340899E+11 | 0.408600E+11 | 0.168421E+11 | 0.240179E+11 | 0.00 | 0.00 |
Minimum of Months | 0.274353E+09 | 0.742503E+09 | 0.123223E+10 | 0.254605E+09 | 0.977624E+09 | 0.00 | 0.00 |
Maximum of Months | 0.694623E+10 | 0.535787E+10 | 0.533250E+10 | 0.235670E+10 | 0.297579E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.438679E+10 | 0.735004E+10 | 0.556949E+10 | 0.325107E+10 | 0.231842E+10 | 0.00 | 0.00 |
February | 0.444238E+10 | 0.648454E+10 | 0.574359E+10 | 0.276950E+10 | 0.297409E+10 | 0.00 | 0.00 |
March | 0.745990E+10 | 0.549043E+10 | 0.776155E+10 | 0.436115E+10 | 0.340040E+10 | 0.00 | 0.00 |
April | 0.622656E+10 | 0.426288E+10 | 0.622045E+10 | 0.248570E+10 | 0.373476E+10 | 0.00 | 0.00 |
May | 0.620089E+10 | 0.292500E+10 | 0.562491E+10 | 0.163370E+10 | 0.399121E+10 | 0.00 | 0.00 |
June | 0.655638E+10 | 0.181142E+10 | 0.528930E+10 | 0.112082E+10 | 0.416848E+10 | 0.00 | 0.00 |
July | 0.768218E+10 | 0.127066E+10 | 0.557950E+10 | 0.135376E+10 | 0.422574E+10 | 0.00 | 0.00 |
August | 0.847266E+10 | 0.166292E+10 | 0.626389E+10 | 0.203090E+10 | 0.423299E+10 | 0.00 | 0.00 |
September | 0.877918E+10 | 0.258417E+10 | 0.704808E+10 | 0.343292E+10 | 0.361516E+10 | 0.00 | 0.00 |
October | 0.742743E+10 | 0.409371E+10 | 0.696876E+10 | 0.398068E+10 | 0.298808E+10 | 0.00 | 0.00 |
November | 0.444345E+10 | 0.512333E+10 | 0.482988E+10 | 0.272662E+10 | 0.210326E+10 | 0.00 | 0.00 |
December | 0.342863E+10 | 0.739343E+10 | 0.465720E+10 | 0.241031E+10 | 0.224690E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.755064E+11 | 0.504525E+11 | 0.715566E+11 | 0.315571E+11 | 0.399995E+11 | 0.00 | 0.00 |
Minimum of Months | 0.342863E+10 | 0.127066E+10 | 0.465720E+10 | 0.112082E+10 | 0.210326E+10 | 0.00 | 0.00 |
Maximum of Months | 0.877918E+10 | 0.739343E+10 | 0.776155E+10 | 0.436115E+10 | 0.423299E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.328388E+09 | 0.580573E+10 | 0.135580E+10 | 0.318289E+09 | 0.103751E+10 | 0.00 | 0.00 |
February | 0.732465E+09 | 0.501957E+10 | 0.198473E+10 | 0.510091E+09 | 0.147464E+10 | 0.00 | 0.00 |
March | 0.252684E+10 | 0.423617E+10 | 0.344400E+10 | 0.147464E+10 | 0.196936E+10 | 0.00 | 0.00 |
April | 0.356527E+10 | 0.316535E+10 | 0.408069E+10 | 0.167325E+10 | 0.240744E+10 | 0.00 | 0.00 |
May | 0.532725E+10 | 0.205982E+10 | 0.497429E+10 | 0.224806E+10 | 0.272623E+10 | 0.00 | 0.00 |
June | 0.705598E+10 | 0.134947E+10 | 0.580803E+10 | 0.273186E+10 | 0.307617E+10 | 0.00 | 0.00 |
July | 0.693863E+10 | 0.100669E+10 | 0.536568E+10 | 0.235250E+10 | 0.301318E+10 | 0.00 | 0.00 |
August | 0.613970E+10 | 0.130483E+10 | 0.485294E+10 | 0.206352E+10 | 0.278943E+10 | 0.00 | 0.00 |
September | 0.418350E+10 | 0.184917E+10 | 0.368813E+10 | 0.159274E+10 | 0.209539E+10 | 0.00 | 0.00 |
October | 0.198014E+10 | 0.313354E+10 | 0.247052E+10 | 0.870257E+09 | 0.160026E+10 | 0.00 | 0.00 |
November | 0.700285E+09 | 0.411130E+10 | 0.141681E+10 | 0.408274E+09 | 0.100854E+10 | 0.00 | 0.00 |
December | 0.282539E+09 | 0.612374E+10 | 0.126919E+10 | 0.276542E+09 | 0.992647E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.397610E+11 | 0.391654E+11 | 0.407108E+11 | 0.165200E+11 | 0.241908E+11 | 0.00 | 0.00 |
Minimum of Months | 0.282539E+09 | 0.100669E+10 | 0.126919E+10 | 0.276542E+09 | 0.992647E+09 | 0.00 | 0.00 |
Maximum of Months | 0.705598E+10 | 0.612374E+10 | 0.580803E+10 | 0.273186E+10 | 0.307617E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 13031336.63 | 0.808054E+10 | 0.129527E+10 | 0.00 | 0.129527E+10 | 0.00 | 0.00 |
February | 95445642.20 | 0.682238E+10 | 0.178252E+10 | 0.00 | 0.178252E+10 | 0.00 | 0.00 |
March | 0.733740E+09 | 0.550599E+10 | 0.239330E+10 | 0.00 | 0.239330E+10 | 0.00 | 0.00 |
April | 0.155082E+10 | 0.378778E+10 | 0.295118E+10 | 11776378.66 | 0.293940E+10 | 0.00 | 0.00 |
May | 0.273106E+10 | 0.252327E+10 | 0.354343E+10 | 0.150262E+09 | 0.339317E+10 | 0.00 | 0.00 |
June | 0.441951E+10 | 0.158048E+10 | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.00 | 0.00 |
July | 0.493213E+10 | 0.114026E+10 | 0.395357E+10 | 0.255212E+09 | 0.369836E+10 | 0.00 | 0.00 |
August | 0.402202E+10 | 0.152094E+10 | 0.342094E+10 | 52042148.80 | 0.336890E+10 | 0.00 | 0.00 |
September | 0.226088E+10 | 0.239445E+10 | 0.251943E+10 | 523427.78 | 0.251890E+10 | 0.00 | 0.00 |
October | 0.916540E+09 | 0.391382E+10 | 0.194616E+10 | 0.00 | 0.194616E+10 | 0.00 | 0.00 |
November | 0.251895E+09 | 0.492978E+10 | 0.126558E+10 | 0.00 | 0.126558E+10 | 0.00 | 0.00 |
December | 16209371.35 | 0.771209E+10 | 0.121233E+10 | 0.00 | 0.121233E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.219433E+11 | 0.499118E+11 | 0.304082E+11 | 0.820915E+09 | 0.295873E+11 | 0.00 | 0.00 |
Minimum of Months | 13031336.63 | 0.114026E+10 | 0.121233E+10 | 0.00 | 0.121233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.493213E+10 | 0.808054E+10 | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.595783E+09 | 0.490055E+10 | 0.158021E+10 | 0.509550E+09 | 0.107067E+10 | 0.00 | 0.00 |
February | 0.967336E+09 | 0.418707E+10 | 0.209427E+10 | 0.628439E+09 | 0.146583E+10 | 0.00 | 0.00 |
March | 0.255859E+10 | 0.338913E+10 | 0.332721E+10 | 0.139341E+10 | 0.193379E+10 | 0.00 | 0.00 |
April | 0.394775E+10 | 0.241249E+10 | 0.426171E+10 | 0.188305E+10 | 0.237866E+10 | 0.00 | 0.00 |
May | 0.530094E+10 | 0.171742E+10 | 0.493380E+10 | 0.218248E+10 | 0.275132E+10 | 0.00 | 0.00 |
June | 0.644376E+10 | 0.107932E+10 | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.00 | 0.00 |
July | 0.689313E+10 | 0.775677E+09 | 0.529126E+10 | 0.232967E+10 | 0.296159E+10 | 0.00 | 0.00 |
August | 0.608334E+10 | 0.101620E+10 | 0.477859E+10 | 0.200579E+10 | 0.277280E+10 | 0.00 | 0.00 |
September | 0.440996E+10 | 0.153960E+10 | 0.384834E+10 | 0.170698E+10 | 0.214136E+10 | 0.00 | 0.00 |
October | 0.237708E+10 | 0.247405E+10 | 0.269846E+10 | 0.111616E+10 | 0.158231E+10 | 0.00 | 0.00 |
November | 0.896991E+09 | 0.313791E+10 | 0.148124E+10 | 0.475165E+09 | 0.100608E+10 | 0.00 | 0.00 |
December | 0.307600E+09 | 0.483561E+10 | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.407823E+11 | 0.314650E+11 | 0.408598E+11 | 0.168420E+11 | 0.240178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.307600E+09 | 0.775677E+09 | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.00 | 0.00 |
Maximum of Months | 0.689313E+10 | 0.490055E+10 | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.443208E+10 | 0.696094E+10 | 0.556966E+10 | 0.325118E+10 | 0.231849E+10 | 0.00 | 0.00 |
February | 0.448768E+10 | 0.616775E+10 | 0.574376E+10 | 0.276959E+10 | 0.297417E+10 | 0.00 | 0.00 |
March | 0.748225E+10 | 0.519521E+10 | 0.776178E+10 | 0.436129E+10 | 0.340048E+10 | 0.00 | 0.00 |
April | 0.626457E+10 | 0.400307E+10 | 0.622062E+10 | 0.248578E+10 | 0.373484E+10 | 0.00 | 0.00 |
May | 0.617684E+10 | 0.282983E+10 | 0.562505E+10 | 0.163375E+10 | 0.399130E+10 | 0.00 | 0.00 |
June | 0.653269E+10 | 0.176110E+10 | 0.528942E+10 | 0.112085E+10 | 0.416856E+10 | 0.00 | 0.00 |
July | 0.765373E+10 | 0.126432E+10 | 0.557963E+10 | 0.135380E+10 | 0.422583E+10 | 0.00 | 0.00 |
August | 0.844169E+10 | 0.165086E+10 | 0.626405E+10 | 0.203096E+10 | 0.423309E+10 | 0.00 | 0.00 |
September | 0.873142E+10 | 0.252709E+10 | 0.704828E+10 | 0.343304E+10 | 0.361525E+10 | 0.00 | 0.00 |
October | 0.741938E+10 | 0.389955E+10 | 0.696897E+10 | 0.398081E+10 | 0.298816E+10 | 0.00 | 0.00 |
November | 0.449263E+10 | 0.476352E+10 | 0.483003E+10 | 0.272671E+10 | 0.210332E+10 | 0.00 | 0.00 |
December | 0.350238E+10 | 0.686212E+10 | 0.465734E+10 | 0.241039E+10 | 0.224696E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.756174E+11 | 0.478853E+11 | 0.715586E+11 | 0.315582E+11 | 0.400004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.350238E+10 | 0.126432E+10 | 0.465734E+10 | 0.112085E+10 | 0.210332E+10 | 0.00 | 0.00 |
Maximum of Months | 0.873142E+10 | 0.696094E+10 | 0.776178E+10 | 0.436129E+10 | 0.423309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.359306E+09 | 0.519002E+10 | 0.135580E+10 | 0.318288E+09 | 0.103751E+10 | 0.00 | 0.00 |
February | 0.816034E+09 | 0.441953E+10 | 0.198472E+10 | 0.510089E+09 | 0.147464E+10 | 0.00 | 0.00 |
March | 0.268865E+10 | 0.358364E+10 | 0.344399E+10 | 0.147464E+10 | 0.196935E+10 | 0.00 | 0.00 |
April | 0.375926E+10 | 0.262187E+10 | 0.408068E+10 | 0.167324E+10 | 0.240743E+10 | 0.00 | 0.00 |
May | 0.537751E+10 | 0.189004E+10 | 0.497427E+10 | 0.224805E+10 | 0.272622E+10 | 0.00 | 0.00 |
June | 0.708802E+10 | 0.123525E+10 | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.00 | 0.00 |
July | 0.699733E+10 | 0.911494E+09 | 0.536566E+10 | 0.235249E+10 | 0.301317E+10 | 0.00 | 0.00 |
August | 0.622026E+10 | 0.115115E+10 | 0.485292E+10 | 0.206351E+10 | 0.278941E+10 | 0.00 | 0.00 |
September | 0.422814E+10 | 0.167932E+10 | 0.368811E+10 | 0.159274E+10 | 0.209538E+10 | 0.00 | 0.00 |
October | 0.212139E+10 | 0.263796E+10 | 0.247051E+10 | 0.870254E+09 | 0.160025E+10 | 0.00 | 0.00 |
November | 0.812690E+09 | 0.329197E+10 | 0.141680E+10 | 0.408272E+09 | 0.100853E+10 | 0.00 | 0.00 |
December | 0.341965E+09 | 0.503279E+10 | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.408105E+11 | 0.336450E+11 | 0.407107E+11 | 0.165200E+11 | 0.241907E+11 | 0.00 | 0.00 |
Minimum of Months | 0.341965E+09 | 0.911494E+09 | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.00 | 0.00 |
Maximum of Months | 0.708802E+10 | 0.519002E+10 | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 22650193.24 | 0.782391E+10 | 0.129527E+10 | 0.00 | 0.129527E+10 | 0.00 | 0.00 |
February | 0.114856E+09 | 0.659871E+10 | 0.178252E+10 | 0.00 | 0.178252E+10 | 0.00 | 0.00 |
March | 0.792393E+09 | 0.518176E+10 | 0.239330E+10 | 0.00 | 0.239330E+10 | 0.00 | 0.00 |
April | 0.166511E+10 | 0.349601E+10 | 0.295118E+10 | 11776378.66 | 0.293940E+10 | 0.00 | 0.00 |
May | 0.281971E+10 | 0.236954E+10 | 0.354343E+10 | 0.150262E+09 | 0.339317E+10 | 0.00 | 0.00 |
June | 0.441683E+10 | 0.154835E+10 | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.00 | 0.00 |
July | 0.489386E+10 | 0.114198E+10 | 0.395357E+10 | 0.255212E+09 | 0.369836E+10 | 0.00 | 0.00 |
August | 0.400705E+10 | 0.149574E+10 | 0.342094E+10 | 52042148.80 | 0.336890E+10 | 0.00 | 0.00 |
September | 0.231230E+10 | 0.224232E+10 | 0.251943E+10 | 523427.78 | 0.251890E+10 | 0.00 | 0.00 |
October | 0.104375E+10 | 0.349759E+10 | 0.194616E+10 | 0.00 | 0.194616E+10 | 0.00 | 0.00 |
November | 0.315146E+09 | 0.447174E+10 | 0.126558E+10 | 0.00 | 0.126558E+10 | 0.00 | 0.00 |
December | 23968673.12 | 0.738655E+10 | 0.121233E+10 | 0.00 | 0.121233E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.224276E+11 | 0.472542E+11 | 0.304082E+11 | 0.820915E+09 | 0.295873E+11 | 0.00 | 0.00 |
Minimum of Months | 22650193.24 | 0.114198E+10 | 0.121233E+10 | 0.00 | 0.121233E+10 | 0.00 | 0.00 |
Maximum of Months | 0.489386E+10 | 0.782391E+10 | 0.412452E+10 | 0.351100E+09 | 0.377342E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.614041E+09 | 0.474182E+10 | 0.158021E+10 | 0.509550E+09 | 0.107067E+10 | 0.00 | 0.00 |
February | 0.994168E+09 | 0.405267E+10 | 0.209427E+10 | 0.628439E+09 | 0.146583E+10 | 0.00 | 0.00 |
March | 0.261989E+10 | 0.318762E+10 | 0.332721E+10 | 0.139341E+10 | 0.193379E+10 | 0.00 | 0.00 |
April | 0.401951E+10 | 0.225311E+10 | 0.426171E+10 | 0.188305E+10 | 0.237866E+10 | 0.00 | 0.00 |
May | 0.532676E+10 | 0.164112E+10 | 0.493380E+10 | 0.218248E+10 | 0.275132E+10 | 0.00 | 0.00 |
June | 0.642273E+10 | 0.106949E+10 | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.00 | 0.00 |
July | 0.685710E+10 | 0.784798E+09 | 0.529126E+10 | 0.232967E+10 | 0.296159E+10 | 0.00 | 0.00 |
August | 0.606078E+10 | 0.101063E+10 | 0.477859E+10 | 0.200579E+10 | 0.277280E+10 | 0.00 | 0.00 |
September | 0.442803E+10 | 0.147066E+10 | 0.384834E+10 | 0.170698E+10 | 0.214136E+10 | 0.00 | 0.00 |
October | 0.247182E+10 | 0.223688E+10 | 0.269846E+10 | 0.111616E+10 | 0.158231E+10 | 0.00 | 0.00 |
November | 0.956659E+09 | 0.285730E+10 | 0.148124E+10 | 0.475165E+09 | 0.100608E+10 | 0.00 | 0.00 |
December | 0.323552E+09 | 0.463484E+10 | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.410950E+11 | 0.299409E+11 | 0.408598E+11 | 0.168420E+11 | 0.240178E+11 | 0.00 | 0.00 |
Minimum of Months | 0.323552E+09 | 0.784798E+09 | 0.123222E+10 | 0.254604E+09 | 0.977620E+09 | 0.00 | 0.00 |
Maximum of Months | 0.685710E+10 | 0.474182E+10 | 0.533247E+10 | 0.235669E+10 | 0.297578E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.449216E+10 | 0.668730E+10 | 0.556966E+10 | 0.325118E+10 | 0.231849E+10 | 0.00 | 0.00 |
February | 0.454269E+10 | 0.593423E+10 | 0.574376E+10 | 0.276959E+10 | 0.297417E+10 | 0.00 | 0.00 |
March | 0.758650E+10 | 0.485398E+10 | 0.776178E+10 | 0.436129E+10 | 0.340048E+10 | 0.00 | 0.00 |
April | 0.636408E+10 | 0.371979E+10 | 0.622062E+10 | 0.248578E+10 | 0.373484E+10 | 0.00 | 0.00 |
May | 0.621755E+10 | 0.268064E+10 | 0.562505E+10 | 0.163375E+10 | 0.399130E+10 | 0.00 | 0.00 |
June | 0.650879E+10 | 0.172607E+10 | 0.528942E+10 | 0.112085E+10 | 0.416856E+10 | 0.00 | 0.00 |
July | 0.760380E+10 | 0.126801E+10 | 0.557963E+10 | 0.135380E+10 | 0.422583E+10 | 0.00 | 0.00 |
August | 0.840821E+10 | 0.163255E+10 | 0.626405E+10 | 0.203096E+10 | 0.423309E+10 | 0.00 | 0.00 |
September | 0.874773E+10 | 0.240931E+10 | 0.704828E+10 | 0.343304E+10 | 0.361525E+10 | 0.00 | 0.00 |
October | 0.755380E+10 | 0.352759E+10 | 0.696897E+10 | 0.398081E+10 | 0.298816E+10 | 0.00 | 0.00 |
November | 0.460909E+10 | 0.431835E+10 | 0.483003E+10 | 0.272671E+10 | 0.210332E+10 | 0.00 | 0.00 |
December | 0.356750E+10 | 0.653824E+10 | 0.465734E+10 | 0.241039E+10 | 0.224696E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.762019E+11 | 0.452960E+11 | 0.715586E+11 | 0.315582E+11 | 0.400004E+11 | 0.00 | 0.00 |
Minimum of Months | 0.356750E+10 | 0.126801E+10 | 0.465734E+10 | 0.112085E+10 | 0.210332E+10 | 0.00 | 0.00 |
Maximum of Months | 0.874773E+10 | 0.668730E+10 | 0.776178E+10 | 0.436129E+10 | 0.423309E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.372959E+09 | 0.501541E+10 | 0.135580E+10 | 0.318288E+09 | 0.103751E+10 | 0.00 | 0.00 |
February | 0.831109E+09 | 0.428205E+10 | 0.198472E+10 | 0.510089E+09 | 0.147464E+10 | 0.00 | 0.00 |
March | 0.273169E+10 | 0.338223E+10 | 0.344399E+10 | 0.147464E+10 | 0.196935E+10 | 0.00 | 0.00 |
April | 0.381466E+10 | 0.245327E+10 | 0.408068E+10 | 0.167324E+10 | 0.240743E+10 | 0.00 | 0.00 |
May | 0.540363E+10 | 0.180085E+10 | 0.497427E+10 | 0.224805E+10 | 0.272622E+10 | 0.00 | 0.00 |
June | 0.706531E+10 | 0.121487E+10 | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.00 | 0.00 |
July | 0.696152E+10 | 0.912121E+09 | 0.536566E+10 | 0.235249E+10 | 0.301317E+10 | 0.00 | 0.00 |
August | 0.619845E+10 | 0.113874E+10 | 0.485292E+10 | 0.206351E+10 | 0.278941E+10 | 0.00 | 0.00 |
September | 0.424523E+10 | 0.160204E+10 | 0.368811E+10 | 0.159274E+10 | 0.209538E+10 | 0.00 | 0.00 |
October | 0.218901E+10 | 0.241539E+10 | 0.247051E+10 | 0.870254E+09 | 0.160025E+10 | 0.00 | 0.00 |
November | 0.856595E+09 | 0.303619E+10 | 0.141680E+10 | 0.408272E+09 | 0.100853E+10 | 0.00 | 0.00 |
December | 0.355203E+09 | 0.483368E+10 | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.410254E+11 | 0.320869E+11 | 0.407107E+11 | 0.165200E+11 | 0.241907E+11 | 0.00 | 0.00 |
Minimum of Months | 0.355203E+09 | 0.912121E+09 | 0.126918E+10 | 0.276541E+09 | 0.992643E+09 | 0.00 | 0.00 |
Maximum of Months | 0.706531E+10 | 0.501541E+10 | 0.580801E+10 | 0.273185E+10 | 0.307616E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -3.4 | -4.9 | -8.7 | 5.96 | -14.4 | 41.15 | 62.17 | 0.00 |
February | -4.2 | -5.4 | -8.1 | 6.66 | -15.1 | 65.72 | 71.39 | 0.00 |
March | 2.67 | 0.66 | -2.8 | 5.20 | -8.9 | 69.76 | 141.76 | 0.00 |
April | 7.47 | 4.95 | 1.92 | 5.29 | -2.7 | 89.32 | 159.79 | 0.00 |
May | 13.73 | 9.66 | 5.81 | 4.79 | 3.34 | 93.75 | 203.34 | 0.03 |
June | 18.63 | 14.47 | 11.49 | 5.10 | 8.69 | 105.42 | 236.95 | 0.00 |
July | 22.03 | 18.19 | 16.11 | 4.43 | 13.39 | 102.98 | 214.28 | 0.00 |
August | 20.69 | 16.39 | 13.72 | 4.23 | 11.88 | 99.24 | 178.64 | 0.00 |
September | 16.55 | 13.42 | 11.22 | 4.10 | 7.08 | 75.66 | 154.97 | 0.03 |
October | 9.73 | 7.36 | 4.97 | 4.79 | 0.13 | 58.70 | 104.01 | 0.00 |
November | 6.03 | 3.70 | 0.77 | 5.87 | -3.2 | 41.19 | 58.47 | 0.00 |
December | -2.2 | -3.2 | -5.3 | 6.59 | -12.0 | 40.52 | 44.30 | 0.00 |
Annual Sum or Average | 9.05 | 6.33 | 3.49 | 5.24 | -0.9 | 73.64 | 136.19 | 0.01 |
Minimum of Months | -4.2 | -5.4 | -8.7 | 4.10 | -15.1 | 40.52 | 44.30 | 0.00 |
Maximum of Months | 22.03 | 18.19 | 16.11 | 6.66 | 13.39 | 105.42 | 236.95 | 0.03 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 11.70 | 11-JAN-15:00 | 10.14 | 8.90 | 13.40 | 7.15 | 65.50 | 1.00 |
February | 12.80 | 22-FEB-17:00 | 6.18 | -2.2 | 14.90 | 3.48 | 0.00 | 0.00 |
March | 26.10 | 15-MAR-13:00 | 16.06 | 9.40 | 6.70 | 14.65 | 249.50 | 400.00 |
April | 21.10 | 08-APR-12:00 | 13.43 | 7.80 | 8.20 | 11.46 | 330.00 | 283.50 |
May | 26.10 | 10-MAY-13:00 | 17.84 | 13.30 | 5.20 | 13.35 | 258.50 | 457.00 |
June | 30.60 | 12-JUN-13:00 | 20.23 | 15.00 | 8.20 | 17.93 | 252.00 | 572.00 |
July | 31.70 | 21-JUL-13:00 | 21.73 | 17.20 | 5.20 | 22.47 | 330.00 | 231.00 |
August | 30.60 | 10-AUG-13:00 | 20.24 | 15.00 | 5.70 | 19.70 | 220.50 | 635.00 |
September | 27.20 | 16-SEP-13:09 | 19.53 | 15.68 | 8.80 | 17.30 | 207.00 | 564.67 |
October | 22.20 | 11-OCT-12:00 | 14.14 | 8.30 | 6.20 | 6.95 | 121.00 | 665.00 |
November | 19.40 | 05-NOV-13:00 | 13.85 | 10.00 | 12.40 | 14.84 | 133.00 | 3.50 |
December | 15.00 | 01-DEC-10:00 | 12.41 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.70 | 6.18 | -2.2 | 5.20 | 3.48 | 0.00 | 0.00 | |
Maximum of Months | 31.70 | 21.73 | 17.20 | 14.90 | 22.47 | 330.00 | 665.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -13.9 | 31-JAN-01:00 | -14.5 | -17.2 | 1.50 | -25.9 | 0.00 | 0.00 |
February | -16.7 | 07-FEB-06:00 | -17.3 | -20.6 | 6.20 | -35.1 | 0.00 | 0.00 |
March | -13.3 | 07-MAR-05:19 | -13.9 | -16.7 | 2.43 | -32.2 | 0.00 | 0.00 |
April | -4.4 | 17-APR-05:00 | -5.4 | -7.8 | 2.10 | -20.5 | 35.00 | 151.50 |
May | 1.70 | 01-MAY-04:00 | 0.96 | 0.00 | 0.00 | -14.2 | 0.00 | 0.00 |
June | 6.70 | 04-JUN-04:00 | 5.40 | 3.90 | 2.10 | -7.3 | 20.00 | 104.00 |
July | 11.70 | 03-JUL-03:00 | 11.07 | 10.60 | 2.10 | -1.2 | 0.00 | 0.00 |
August | 11.10 | 01-AUG-04:00 | 10.75 | 10.60 | 2.10 | -0.8 | 0.00 | 0.00 |
September | 6.10 | 05-SEP-05:00 | 5.59 | 5.00 | 2.10 | -6.2 | 24.50 | 41.00 |
October | -2.8 | 17-OCT-04:10 | -3.2 | -4.0 | 2.18 | -19.4 | 0.00 | 0.00 |
November | -3.9 | 24-NOV-05:00 | -4.5 | -5.6 | 2.10 | -18.1 | 0.00 | 0.00 |
December | -18.9 | 11-DEC-05:00 | -19.4 | -23.3 | 2.10 | -35.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -18.9 | -19.4 | -23.3 | 0.00 | -35.1 | 0.00 | 0.00 | |
Maximum of Months | 11.70 | 11.07 | 10.60 | 6.20 | -0.8 | 35.00 | 151.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.21 | 11-JAN-17:00 | 11.10 | 9.40 | 10.30 | 6.55 | 0.00 | 0.00 |
February | 6.89 | 01-FEB-03:00 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 |
March | 17.83 | 14-MAR-12:00 | 25.00 | 13.90 | 6.20 | 14.10 | 197.00 | 562.50 |
April | 13.78 | 08-APR-13:00 | 20.60 | 8.90 | 10.30 | 9.72 | 268.50 | 325.50 |
May | 18.19 | 10-MAY-14:00 | 26.10 | 13.90 | 5.20 | 16.85 | 273.00 | 238.00 |
June | 23.75 | 27-JUN-12:00 | 30.60 | 21.10 | 9.30 | 21.09 | 304.00 | 606.00 |
July | 24.79 | 21-JUL-01:00 | 28.90 | 23.30 | 8.80 | 27.46 | 0.00 | 0.00 |
August | 23.42 | 13-AUG-15:00 | 29.40 | 21.10 | 9.80 | 19.87 | 212.00 | 276.00 |
September | 21.17 | 15-SEP-11:00 | 26.10 | 18.90 | 3.60 | 16.30 | 204.00 | 464.50 |
October | 15.23 | 12-OCT-14:00 | 18.30 | 13.30 | 10.30 | 9.13 | 148.00 | 367.50 |
November | 13.96 | 05-NOV-14:00 | 18.30 | 11.10 | 11.30 | 14.10 | 72.00 | 6.00 |
December | 12.41 | 01-DEC-10:00 | 15.00 | 10.60 | 12.90 | 10.69 | 56.50 | 11.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.89 | 7.20 | 6.70 | 3.60 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 24.79 | 30.60 | 23.30 | 12.90 | 27.46 | 304.00 | 606.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.40 | 11-JAN-13:00 | 10.00 | 9.66 | 12.90 | 5.54 | 95.50 | 2.00 |
February | 6.70 | 01-FEB-04:10 | 7.20 | 6.89 | 3.52 | 2.22 | 0.00 | 0.00 |
March | 15.00 | 14-MAR-10:20 | 20.33 | 16.97 | 4.80 | 10.50 | 159.17 | 592.83 |
April | 11.10 | 08-APR-21:00 | 13.90 | 12.23 | 12.90 | 9.72 | 0.00 | 0.00 |
May | 15.60 | 17-MAY-12:00 | 16.70 | 15.97 | 6.70 | 13.54 | 184.00 | 0.00 |
June | 21.70 | 27-JUN-14:00 | 25.60 | 22.78 | 8.20 | 16.85 | 255.50 | 530.00 |
July | 23.30 | 20-JUL-20:00 | 25.60 | 24.03 | 4.60 | 24.16 | 0.00 | 0.00 |
August | 21.70 | 14-AUG-03:20 | 23.70 | 22.19 | 5.00 | 21.90 | 0.00 | 0.00 |
September | 20.00 | 15-SEP-18:00 | 21.70 | 20.51 | 0.00 | 19.52 | 0.00 | 0.00 |
October | 14.40 | 01-OCT-07:19 | 14.60 | 14.50 | 3.77 | 10.56 | 67.50 | 30.17 |
November | 11.70 | 05-NOV-15:00 | 12.80 | 12.14 | 7.20 | 8.74 | 28.00 | 4.50 |
December | 11.10 | 01-DEC-12:00 | 13.90 | 12.22 | 10.30 | 6.35 | 158.00 | 84.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.70 | 7.20 | 6.89 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 23.30 | 25.60 | 24.03 | 12.90 | 24.16 | 255.50 | 592.83 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 7.32 | 12.49 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 6.57 | 19.26 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 7.29 | 28.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 9.34 | 37.44 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.19 | 46.60 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 15.07 | 54.01 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.20 | 50.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.01 | 43.20 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.27 | 32.93 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.18 | 21.28 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.32 | 12.54 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 9.45 | 10.96 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.30 | 30.86 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 6.57 | 10.96 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.01 | 54.01 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.421856E+11 | -0.411390E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.104663E+10 | 58.98 | 0.00 | 0.00 |
February | 0.388721E+11 | -0.379235E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -948585388.6 | 58.99 | 0.00 | 0.00 |
March | 0.450346E+11 | -0.440004E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103423E+10 | 58.98 | 0.00 | 0.00 |
April | 0.393162E+11 | -0.383231E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993182672.1 | 58.98 | 0.00 | 0.00 |
May | 0.396319E+11 | -0.386054E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102653E+10 | 58.98 | 0.00 | 0.00 |
June | 0.368894E+11 | -0.358965E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992993634.0 | 58.98 | 0.00 | 0.00 |
July | 0.334889E+11 | -0.324685E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102037E+10 | 58.98 | 0.00 | 0.00 |
August | 0.359026E+11 | -0.348784E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102423E+10 | 58.98 | 0.00 | 0.00 |
September | 0.332045E+11 | -0.322155E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988953146.1 | 58.97 | 0.00 | 0.00 |
October | 0.359187E+11 | -0.348967E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102199E+10 | 58.97 | 0.00 | 0.00 |
November | 0.374463E+11 | -0.364563E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -989955080.4 | 58.98 | 0.00 | 0.00 |
December | 0.395219E+11 | -0.384913E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103066E+10 | 58.97 | 0.00 | 0.00 |
Annual Sum or Average | 0.457413E+12 | -0.445294E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.121183E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.332045E+11 | -0.440004E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.104663E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.450346E+11 | -0.322155E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -948585388.6 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 3678.08 | 30.75 | 216.50 | 240.33 | 3040.31 | 33.46 | 241.67 | 212.00 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 4714.49 | 32.19 | 243.00 | 249.83 | 1433.44 | 25.22 | 213.50 | 224.33 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:30 | 6903.92 | 28.91 | 245.33 | 318.83 | 1137.66 | 21.15 | 162.17 | 277.67 |
April | 371.17 | 0.64 | 0.61 | 01-APR-06:40 | 1642.50 | 17.35 | 0.00 | 334.83 | 896.48 | 20.28 | 157.00 | 291.67 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:19 | 1481.02 | 17.29 | 0.00 | 368.33 | 855.60 | 20.31 | 130.00 | 312.67 |
June | 430.67 | 0.64 | 0.61 | 01-JUN-05:49 | 1342.41 | 17.06 | 0.00 | 377.83 | 759.74 | 20.05 | 150.33 | 330.00 |
July | 439.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1409.86 | 17.13 | 0.00 | 384.50 | 784.93 | 20.11 | 167.17 | 331.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:00 | 1672.56 | 17.69 | 0.00 | 363.17 | 906.81 | 20.65 | 203.00 | 318.50 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2400.43 | 19.30 | 17.00 | 313.33 | 1178.26 | 21.35 | 181.33 | 274.83 |
October | 314.33 | 0.63 | 0.61 | 01-OCT-06:00 | 5513.40 | 31.26 | 268.17 | 291.83 | 1228.12 | 21.93 | 171.50 | 267.50 |
November | 258.33 | 0.63 | 0.61 | 01-NOV-07:40 | 3491.01 | 30.78 | 225.33 | 232.50 | 1364.49 | 27.57 | 208.83 | 205.83 |
December | 230.67 | 0.62 | 0.61 | 01-DEC-08:09 | 3079.82 | 29.46 | 193.33 | 228.50 | 2471.80 | 32.39 | 217.17 | 193.50 |
Annual Sum or Average | 3928.50 | 0.63 | 2936.47 | 23.03 | 1408.67 | 3703.83 | 1233.14 | 22.94 | 2203.67 | 3239.83 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 1342.41 | 17.06 | 0.00 | 228.50 | 759.74 | 20.05 | 130.00 | 193.50 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 6903.92 | 32.19 | 268.17 | 384.50 | 3040.31 | 33.46 | 241.67 | 331.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 1147.08 | 16.90 | 46.00 | 222.00 | 600.48 | 17.78 | 40.50 | 160.33 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 1684.42 | 18.44 | 65.00 | 237.33 | 837.58 | 17.91 | 39.50 | 198.50 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:30 | 2345.98 | 17.40 | 66.67 | 305.33 | 951.52 | 15.01 | 1.83 | 258.17 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:19 | 2395.04 | 15.23 | 41.83 | 337.17 | 1403.24 | 14.39 | 0.00 | 292.83 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:30 | 3365.48 | 13.15 | 0.00 | 375.00 | 1387.87 | 14.62 | 0.00 | 323.67 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3041.58 | 13.17 | 0.00 | 388.50 | 1315.37 | 14.51 | 0.00 | 353.00 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-04:00 | 2881.61 | 13.20 | 0.00 | 392.00 | 1234.15 | 14.49 | 0.00 | 349.50 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 2679.80 | 13.65 | 3.50 | 365.50 | 1115.85 | 14.86 | 0.00 | 323.33 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2615.07 | 16.70 | 45.67 | 309.33 | 1471.92 | 15.51 | 1.83 | 266.17 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-06:00 | 1697.99 | 17.95 | 72.67 | 275.50 | 884.21 | 17.63 | 48.33 | 227.00 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 1205.09 | 17.62 | 68.17 | 215.50 | 678.70 | 18.20 | 55.17 | 146.67 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-07:00 | 1052.57 | 17.85 | 55.00 | 211.00 | 518.67 | 17.42 | 34.83 | 143.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2302.34 | 15.59 | 464.50 | 3634.17 | 1078.70 | 15.76 | 222.00 | 3042.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1052.57 | 13.15 | 0.00 | 211.00 | 518.67 | 14.39 | 0.00 | 143.67 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3365.48 | 18.44 | 72.67 | 392.00 | 1471.92 | 18.20 | 55.17 | 353.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.61 | 01-JAN-09:09 | 520.63 | 0.00 | 0.00 | 198.83 | 290.24 | 0.00 | 0.00 | 63.00 |
February | 262.50 | 0.64 | 0.61 | 01-FEB-09:39 | 686.23 | 0.00 | 0.00 | 229.50 | 379.59 | 0.00 | 0.00 | 154.67 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:00 | 721.14 | 0.00 | 0.00 | 298.50 | 422.10 | 0.00 | 0.00 | 225.67 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 837.36 | 0.00 | 0.00 | 341.50 | 489.62 | 0.00 | 0.00 | 285.50 |
May | 332.17 | 0.62 | 0.61 | 01-MAY-05:40 | 986.41 | 0.00 | 0.00 | 389.67 | 600.90 | 0.00 | 0.00 | 340.67 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:49 | 1121.42 | 0.00 | 0.00 | 405.17 | 628.00 | 0.00 | 0.00 | 371.67 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:10 | 1066.82 | 0.00 | 0.00 | 411.33 | 621.19 | 0.00 | 0.00 | 376.17 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 940.65 | 0.00 | 0.00 | 376.83 | 559.14 | 0.00 | 0.00 | 332.83 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 777.82 | 0.00 | 0.00 | 306.17 | 485.22 | 0.00 | 0.00 | 238.67 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:10 | 633.73 | 0.00 | 0.00 | 262.83 | 364.07 | 0.00 | 0.00 | 169.50 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-07:00 | 505.77 | 0.00 | 0.00 | 196.17 | 280.21 | 0.00 | 0.00 | 64.00 |
December | 230.67 | 0.64 | 0.61 | 01-DEC-11:30 | 526.22 | 0.00 | 0.00 | 183.33 | 286.00 | 0.00 | 0.00 | 61.83 |
Annual Sum or Average | 3928.50 | 0.63 | 815.96 | 0.00 | 0.00 | 3599.83 | 473.86 | 0.00 | 0.00 | 2684.17 | ||
Minimum of Months | 230.67 | 0.62 | 0.61 | 505.77 | 0.00 | 0.00 | 183.33 | 280.21 | 0.00 | 0.00 | 61.83 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 1121.42 | 0.00 | 0.00 | 411.33 | 628.00 | 0.00 | 0.00 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.61 | 01-JAN-09:09 | 1126.58 | 18.02 | 66.33 | 218.50 | 626.18 | 18.76 | 58.00 | 157.00 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:39 | 1561.76 | 18.16 | 65.00 | 238.50 | 797.52 | 17.79 | 40.17 | 196.17 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-08:09 | 2158.53 | 17.30 | 66.17 | 308.00 | 1272.79 | 17.09 | 40.17 | 264.17 |
April | 371.17 | 0.63 | 0.61 | 01-APR-07:10 | 2699.02 | 15.26 | 42.50 | 332.67 | 1110.88 | 14.39 | 0.00 | 291.50 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:30 | 2764.48 | 13.10 | 0.00 | 376.33 | 1559.51 | 14.70 | 1.50 | 325.33 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:00 | 3052.68 | 13.17 | 0.00 | 387.00 | 1260.38 | 16.26 | 34.00 | 348.17 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-06:10 | 2704.06 | 13.23 | 0.00 | 391.83 | 1160.56 | 14.54 | 0.00 | 350.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-06:19 | 2460.03 | 13.71 | 4.17 | 368.83 | 1359.98 | 14.87 | 0.00 | 320.83 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2617.69 | 18.00 | 64.83 | 307.83 | 1144.58 | 15.52 | 3.67 | 269.00 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:30 | 1590.67 | 17.63 | 69.67 | 273.00 | 823.96 | 17.47 | 47.83 | 225.50 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-07:00 | 1166.87 | 17.55 | 71.00 | 214.50 | 628.20 | 17.88 | 53.50 | 151.33 |
December | 230.67 | 0.64 | 0.61 | 01-DEC-10:00 | 1095.14 | 17.86 | 53.67 | 205.83 | 563.36 | 17.32 | 33.00 | 144.17 |
Annual Sum or Average | 3928.50 | 0.63 | 2204.78 | 15.71 | 503.33 | 3622.83 | 1073.70 | 16.16 | 311.83 | 3043.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1095.14 | 13.10 | 0.00 | 205.83 | 563.36 | 14.39 | 0.00 | 144.17 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 3052.68 | 18.16 | 71.00 | 391.83 | 1559.51 | 18.76 | 58.00 | 350.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 3534.83 | 27.54 | 190.83 | 236.83 | 3066.86 | 32.76 | 231.00 | 213.17 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 4603.69 | 29.39 | 218.67 | 247.33 | 1512.12 | 23.53 | 105.00 | 230.00 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:40 | 6858.32 | 27.19 | 216.67 | 317.00 | 1188.83 | 16.69 | 5.67 | 280.33 |
April | 371.17 | 0.64 | 0.61 | 01-APR-06:40 | 1611.32 | 11.33 | 0.00 | 333.17 | 926.72 | 16.08 | 0.00 | 293.00 |
May | 332.17 | 0.64 | 0.61 | 01-MAY-06:19 | 1459.02 | 11.61 | 0.00 | 366.33 | 884.93 | 16.48 | 0.00 | 315.00 |
June | 430.67 | 0.64 | 0.61 | 01-JUN-05:00 | 1318.42 | 11.48 | 0.00 | 375.33 | 783.79 | 16.25 | 0.00 | 333.00 |
July | 439.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1383.51 | 11.42 | 0.00 | 382.00 | 809.62 | 16.19 | 0.00 | 334.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:00 | 1638.22 | 11.86 | 0.00 | 361.83 | 935.23 | 16.62 | 0.00 | 320.67 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2360.22 | 13.70 | 17.00 | 312.17 | 1218.58 | 17.25 | 0.00 | 277.00 |
October | 314.33 | 0.63 | 0.61 | 01-OCT-06:00 | 5448.93 | 30.14 | 256.67 | 290.33 | 1346.24 | 17.49 | 24.67 | 268.17 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:49 | 3391.34 | 28.04 | 205.17 | 229.17 | 1648.40 | 26.76 | 158.33 | 207.17 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-08:09 | 2872.43 | 24.41 | 153.00 | 226.17 | 2480.72 | 30.90 | 200.67 | 193.00 |
Annual Sum or Average | 3928.50 | 0.63 | 2875.05 | 18.61 | 1258.00 | 3677.67 | 1289.83 | 19.61 | 725.33 | 3264.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1318.42 | 11.33 | 0.00 | 226.17 | 783.79 | 16.08 | 0.00 | 193.00 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 6858.32 | 30.14 | 256.67 | 382.00 | 3066.86 | 32.76 | 231.00 | 334.33 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 1138.61 | 14.29 | 46.33 | 221.17 | 615.72 | 15.53 | 40.83 | 164.33 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 1674.64 | 16.21 | 64.83 | 237.00 | 857.53 | 15.70 | 39.67 | 200.67 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:30 | 2178.69 | 14.96 | 66.67 | 304.50 | 977.59 | 12.36 | 1.83 | 261.50 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:19 | 2396.18 | 12.33 | 41.67 | 336.50 | 1433.82 | 11.83 | 0.00 | 296.17 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:40 | 3356.34 | 9.64 | 0.00 | 374.33 | 1425.53 | 12.15 | 0.00 | 326.83 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3028.05 | 9.75 | 0.00 | 387.33 | 1350.59 | 12.14 | 0.00 | 355.00 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:10 | 2848.50 | 9.76 | 0.00 | 391.67 | 1267.98 | 12.09 | 0.00 | 352.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 2516.62 | 10.25 | 3.50 | 364.50 | 1147.51 | 12.34 | 0.00 | 326.67 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2601.28 | 13.88 | 44.67 | 308.00 | 1503.48 | 12.86 | 1.83 | 268.83 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-06:00 | 1545.53 | 13.81 | 51.67 | 274.50 | 906.25 | 15.52 | 48.67 | 230.00 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 1194.92 | 15.22 | 66.50 | 214.83 | 692.97 | 16.28 | 55.83 | 150.67 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-07:00 | 998.10 | 13.81 | 39.17 | 209.00 | 531.65 | 15.18 | 35.50 | 148.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2246.89 | 12.44 | 425.00 | 3623.33 | 1106.04 | 13.38 | 224.17 | 3081.67 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 998.10 | 9.64 | 0.00 | 209.00 | 531.65 | 11.83 | 0.00 | 148.67 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3356.34 | 16.21 | 66.67 | 391.67 | 1503.48 | 16.28 | 55.83 | 355.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.65 | 0.61 | 01-JAN-09:09 | 508.13 | 0.00 | 0.00 | 195.00 | 297.63 | 0.00 | 0.00 | 71.17 |
February | 262.50 | 0.64 | 0.61 | 01-FEB-09:39 | 671.28 | 0.00 | 0.00 | 227.33 | 389.85 | 0.00 | 0.00 | 159.50 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-08:09 | 706.90 | 0.00 | 0.00 | 296.33 | 434.13 | 0.00 | 0.00 | 232.00 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 822.03 | 0.00 | 0.00 | 340.67 | 503.97 | 0.00 | 0.00 | 290.33 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:40 | 970.19 | 0.00 | 0.00 | 388.00 | 621.80 | 0.00 | 0.00 | 343.83 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:49 | 1078.17 | 0.00 | 0.00 | 402.33 | 673.28 | 0.00 | 0.00 | 377.67 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:10 | 1049.53 | 0.00 | 0.00 | 410.00 | 639.18 | 0.00 | 0.00 | 376.83 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 923.73 | 0.00 | 0.00 | 375.17 | 575.08 | 0.00 | 0.00 | 335.33 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 763.90 | 0.00 | 0.00 | 303.83 | 498.94 | 0.00 | 0.00 | 243.67 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:19 | 620.19 | 0.00 | 0.00 | 259.83 | 374.00 | 0.00 | 0.00 | 174.33 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-07:00 | 493.74 | 0.00 | 0.00 | 192.17 | 287.48 | 0.00 | 0.00 | 71.83 |
December | 230.67 | 0.65 | 0.61 | 01-DEC-11:30 | 513.57 | 0.00 | 0.00 | 180.50 | 293.33 | 0.00 | 0.00 | 70.50 |
Annual Sum or Average | 3928.50 | 0.63 | 798.03 | 0.00 | 0.00 | 3571.17 | 490.52 | 0.00 | 0.00 | 2747.00 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 493.74 | 0.00 | 0.00 | 180.50 | 287.48 | 0.00 | 0.00 | 70.50 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 1078.17 | 0.00 | 0.00 | 410.00 | 673.28 | 0.00 | 0.00 | 377.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.61 | 01-JAN-09:09 | 1118.18 | 15.88 | 66.67 | 217.50 | 639.38 | 16.85 | 59.00 | 160.17 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:39 | 1551.09 | 15.91 | 65.00 | 237.50 | 816.48 | 15.58 | 40.33 | 198.00 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-08:09 | 2156.77 | 14.84 | 66.00 | 307.67 | 1299.87 | 14.92 | 40.67 | 266.67 |
April | 371.17 | 0.64 | 0.61 | 01-APR-07:10 | 2698.34 | 12.39 | 42.50 | 332.50 | 1084.79 | 11.86 | 0.00 | 292.83 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2757.13 | 9.58 | 0.00 | 376.00 | 1593.79 | 12.10 | 0.00 | 328.50 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:00 | 3037.05 | 9.68 | 0.00 | 386.67 | 1257.31 | 12.09 | 0.00 | 349.17 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-06:10 | 2690.92 | 9.77 | 0.00 | 391.33 | 1194.05 | 12.11 | 0.00 | 352.67 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-06:19 | 2450.62 | 10.33 | 4.17 | 367.33 | 1391.20 | 12.36 | 0.00 | 323.67 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2620.67 | 15.57 | 64.83 | 307.17 | 1177.36 | 12.90 | 3.67 | 271.83 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:30 | 1583.06 | 15.31 | 69.67 | 272.00 | 844.39 | 15.35 | 48.33 | 228.83 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-08:09 | 1159.12 | 15.43 | 70.83 | 213.33 | 641.73 | 15.97 | 54.67 | 155.50 |
December | 230.67 | 0.64 | 0.61 | 01-DEC-11:09 | 1085.84 | 15.69 | 53.67 | 205.00 | 576.39 | 15.12 | 33.50 | 147.17 |
Annual Sum or Average | 3928.50 | 0.63 | 2197.09 | 12.88 | 503.33 | 3614.00 | 1090.93 | 13.64 | 280.17 | 3075.00 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1085.84 | 9.58 | 0.00 | 205.00 | 576.39 | 11.86 | 0.00 | 147.17 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 3037.05 | 15.91 | 70.83 | 391.33 | 1593.79 | 16.85 | 59.00 | 352.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 3533.88 | 27.52 | 190.83 | 236.83 | 3068.07 | 32.76 | 231.00 | 213.17 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 4603.39 | 29.38 | 218.67 | 247.33 | 1513.86 | 23.52 | 105.00 | 230.00 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:40 | 6858.98 | 27.17 | 216.50 | 317.00 | 1190.21 | 16.68 | 5.67 | 280.67 |
April | 371.17 | 0.64 | 0.61 | 01-APR-06:40 | 1612.22 | 11.29 | 0.00 | 333.17 | 927.87 | 16.06 | 0.00 | 293.00 |
May | 332.17 | 0.64 | 0.61 | 01-MAY-06:19 | 1459.62 | 11.57 | 0.00 | 366.33 | 885.83 | 16.46 | 0.00 | 315.00 |
June | 430.67 | 0.64 | 0.61 | 01-JUN-05:00 | 1318.99 | 11.44 | 0.00 | 375.33 | 784.63 | 16.24 | 0.00 | 333.17 |
July | 439.00 | 0.64 | 0.61 | 01-JUL-05:00 | 1384.18 | 11.38 | 0.00 | 382.00 | 810.53 | 16.17 | 0.00 | 334.67 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:00 | 1639.13 | 11.82 | 0.00 | 361.83 | 936.39 | 16.60 | 0.00 | 320.83 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2361.03 | 13.66 | 17.00 | 312.17 | 1220.00 | 17.23 | 0.00 | 277.00 |
October | 314.33 | 0.63 | 0.61 | 01-OCT-06:00 | 5448.97 | 30.13 | 256.67 | 290.33 | 1432.84 | 17.76 | 28.67 | 268.33 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:49 | 3390.78 | 28.03 | 205.17 | 229.00 | 1893.19 | 28.58 | 184.33 | 207.83 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-08:09 | 2871.44 | 24.39 | 152.83 | 226.17 | 2481.92 | 30.89 | 200.67 | 193.17 |
Annual Sum or Average | 3928.50 | 0.63 | 2875.36 | 18.58 | 1257.67 | 3677.50 | 1313.84 | 19.73 | 755.33 | 3266.83 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1318.99 | 11.29 | 0.00 | 226.17 | 784.63 | 16.06 | 0.00 | 193.17 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 6858.98 | 30.13 | 256.67 | 382.00 | 3068.07 | 32.76 | 231.00 | 334.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.63 | 0.61 | 01-JAN-08:50 | 1138.50 | 14.28 | 46.33 | 221.17 | 616.35 | 15.53 | 40.83 | 164.50 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:09 | 1674.64 | 16.20 | 64.83 | 237.00 | 858.41 | 15.69 | 39.67 | 200.67 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-07:30 | 2178.52 | 14.95 | 66.67 | 304.50 | 978.40 | 12.35 | 1.83 | 261.50 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:19 | 2396.18 | 12.32 | 41.67 | 336.33 | 1434.72 | 11.83 | 0.00 | 296.33 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:40 | 3356.20 | 9.63 | 0.00 | 374.17 | 1426.44 | 12.14 | 0.00 | 326.83 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:40 | 3027.99 | 9.74 | 0.00 | 387.33 | 1351.53 | 12.13 | 0.00 | 355.17 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:10 | 2848.51 | 9.75 | 0.00 | 391.50 | 1268.90 | 12.08 | 0.00 | 352.33 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 2516.60 | 10.23 | 3.50 | 364.50 | 1148.49 | 12.33 | 0.00 | 326.67 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2600.80 | 13.86 | 44.67 | 308.00 | 1504.39 | 12.86 | 1.83 | 268.83 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-06:00 | 1545.39 | 13.80 | 51.67 | 274.33 | 906.99 | 15.52 | 48.67 | 230.17 |
November | 258.33 | 0.64 | 0.61 | 01-NOV-07:40 | 1194.87 | 15.21 | 66.50 | 214.67 | 693.57 | 16.27 | 55.83 | 150.83 |
December | 230.67 | 0.63 | 0.61 | 01-DEC-07:00 | 998.09 | 13.80 | 39.17 | 209.00 | 532.28 | 15.17 | 35.50 | 148.67 |
Annual Sum or Average | 3928.50 | 0.63 | 2246.80 | 12.43 | 425.00 | 3622.50 | 1106.89 | 13.37 | 224.17 | 3082.50 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 998.09 | 9.63 | 0.00 | 209.00 | 532.28 | 11.83 | 0.00 | 148.67 | |
Maximum of Months | 439.00 | 0.64 | 0.61 | 3356.20 | 16.20 | 66.67 | 391.50 | 1504.39 | 16.27 | 55.83 | 355.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.65 | 0.61 | 01-JAN-09:09 | 508.22 | 0.00 | 0.00 | 194.83 | 297.98 | 0.00 | 0.00 | 71.50 |
February | 262.50 | 0.64 | 0.61 | 01-FEB-09:39 | 671.44 | 0.00 | 0.00 | 227.33 | 390.33 | 0.00 | 0.00 | 159.83 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-08:09 | 706.96 | 0.00 | 0.00 | 296.33 | 434.57 | 0.00 | 0.00 | 232.50 |
April | 371.17 | 0.63 | 0.61 | 01-APR-06:40 | 822.14 | 0.00 | 0.00 | 340.67 | 504.48 | 0.00 | 0.00 | 290.33 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-05:40 | 970.05 | 0.00 | 0.00 | 388.00 | 622.28 | 0.00 | 0.00 | 343.83 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:49 | 1078.17 | 0.00 | 0.00 | 402.33 | 673.88 | 0.00 | 0.00 | 377.83 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-05:10 | 1049.56 | 0.00 | 0.00 | 410.00 | 639.77 | 0.00 | 0.00 | 377.17 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-05:49 | 923.77 | 0.00 | 0.00 | 375.17 | 575.63 | 0.00 | 0.00 | 335.50 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 763.72 | 0.00 | 0.00 | 303.83 | 499.33 | 0.00 | 0.00 | 244.00 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:19 | 620.26 | 0.00 | 0.00 | 259.83 | 374.40 | 0.00 | 0.00 | 174.67 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-07:00 | 493.85 | 0.00 | 0.00 | 192.17 | 287.83 | 0.00 | 0.00 | 72.17 |
December | 230.67 | 0.65 | 0.61 | 01-DEC-11:30 | 513.71 | 0.00 | 0.00 | 180.83 | 293.70 | 0.00 | 0.00 | 70.67 |
Annual Sum or Average | 3928.50 | 0.63 | 798.07 | 0.00 | 0.00 | 3571.33 | 490.99 | 0.00 | 0.00 | 2750.00 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 493.85 | 0.00 | 0.00 | 180.83 | 287.83 | 0.00 | 0.00 | 70.67 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 1078.17 | 0.00 | 0.00 | 410.00 | 673.88 | 0.00 | 0.00 | 377.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 255.17 | 0.64 | 0.61 | 01-JAN-09:09 | 1118.14 | 15.87 | 66.67 | 217.50 | 639.99 | 16.85 | 59.00 | 160.17 |
February | 262.50 | 0.63 | 0.61 | 01-FEB-09:39 | 1551.07 | 15.90 | 65.00 | 237.67 | 817.36 | 15.57 | 40.33 | 198.17 |
March | 339.33 | 0.63 | 0.61 | 01-MAR-08:09 | 2156.59 | 14.83 | 66.00 | 307.67 | 1300.69 | 14.91 | 40.67 | 266.83 |
April | 371.17 | 0.64 | 0.61 | 01-APR-07:10 | 2698.34 | 12.37 | 42.50 | 332.50 | 1085.70 | 11.85 | 0.00 | 292.83 |
May | 332.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2756.95 | 9.56 | 0.00 | 376.00 | 1594.67 | 12.09 | 0.00 | 328.67 |
June | 430.67 | 0.63 | 0.61 | 01-JUN-05:00 | 3036.89 | 9.66 | 0.00 | 386.67 | 1258.29 | 12.08 | 0.00 | 349.17 |
July | 439.00 | 0.63 | 0.61 | 01-JUL-06:10 | 2690.92 | 9.75 | 0.00 | 391.33 | 1195.02 | 12.10 | 0.00 | 352.67 |
August | 406.00 | 0.63 | 0.61 | 01-AUG-06:19 | 2450.65 | 10.32 | 4.17 | 367.17 | 1392.19 | 12.35 | 0.00 | 323.67 |
September | 289.17 | 0.63 | 0.61 | 01-SEP-07:40 | 2607.45 | 15.38 | 62.83 | 307.17 | 1178.22 | 12.89 | 3.67 | 272.00 |
October | 314.33 | 0.64 | 0.61 | 01-OCT-07:30 | 1472.62 | 13.65 | 50.00 | 272.00 | 845.15 | 15.35 | 48.33 | 228.83 |
November | 258.33 | 0.65 | 0.61 | 01-NOV-08:09 | 1159.10 | 15.42 | 70.83 | 213.33 | 642.33 | 15.96 | 54.67 | 155.67 |
December | 230.67 | 0.64 | 0.61 | 01-DEC-11:09 | 1085.82 | 15.69 | 53.67 | 205.00 | 577.03 | 15.12 | 33.50 | 147.33 |
Annual Sum or Average | 3928.50 | 0.63 | 2187.23 | 12.73 | 481.67 | 3614.00 | 1091.78 | 13.63 | 280.17 | 3076.00 | ||
Minimum of Months | 230.67 | 0.63 | 0.61 | 1085.82 | 9.56 | 0.00 | 205.00 | 577.03 | 11.85 | 0.00 | 147.33 | |
Maximum of Months | 439.00 | 0.65 | 0.61 | 3036.89 | 15.90 | 70.83 | 391.33 | 1594.67 | 16.85 | 59.00 | 352.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.160957E+09 | 26567.28 | 23-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.205472E+09 | 43073.42 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.315696E+09 | 27800.09 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110662E+09 | 23792.38 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 8088224.44 | 4835.49 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 64.88 | 0.11 | 14-JUN-20:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 597766.78 | 937.98 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 77148354.10 | 20887.10 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.208564E+09 | 21902.77 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.425515E+09 | 39127.21 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.151270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.425515E+09 | 43073.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.185423E+10 | 13842.38 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.151284E+10 | 14202.06 | 16-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.225131E+09 | 14250.11 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 159466.86 | 88.49 | 25-NOV-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.653136E+09 | 14274.60 | 22-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.424550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.185423E+10 | 14274.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.157589E+10 | 14367.33 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139735E+10 | 14592.36 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202961E+09 | 14625.06 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 1917450.71 | 1470.83 | 17-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 2996314.49 | 369.21 | 17-OCT-06:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 42908676.22 | 4705.61 | 25-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.105327E+10 | 14589.28 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.427729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.157589E+10 | 14625.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.200036E+10 | 19966.15 | 20-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175869E+10 | 20274.52 | 24-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.254412E+09 | 20317.83 | 04-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16654830.04 | 10058.74 | 17-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 14998111.22 | 19959.46 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 67580882.39 | 17716.19 | 24-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.112267E+10 | 20405.31 | 22-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.523537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.200036E+10 | 20405.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.763848E+09 | 13608.15 | 30-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.341054E+09 | 13609.37 | 13-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 592632.25 | 3043.01 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 15538256.65 | 13590.15 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.763848E+09 | 13609.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.188372E+11 | 311343.91 | 03-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196114E+11 | 506465.22 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.996805E+10 | 319857.13 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.573569E+10 | 280143.98 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.101538E+09 | 70518.01 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 176999.76 | 541.75 | 14-JUN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5668.73 | 5.37 | 15-JUL-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59174237.70 | 33039.61 | 05-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243667E+10 | 234601.61 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.725641E+10 | 258815.69 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.104681E+11 | 478281.65 | 26-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.744744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.196114E+11 | 506465.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.270119E+11 | 591442.68 | 30-JAN-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158708E+11 | 591517.01 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.106743E+10 | 591529.15 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.110635E+11 | 591277.28 | 11-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.550136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270119E+11 | 591529.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.936762E+11 | 123881.43 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.829219E+11 | 123750.03 | 01-FEB-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.338291E+11 | 123631.40 | 10-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.560336E+10 | 133309.33 | 14-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 34732877.88 | 7153.08 | 30-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.354830E+10 | 133998.71 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.169760E+11 | 132646.65 | 02-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.784074E+11 | 123893.55 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314997E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.936762E+11 | 133998.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.641035E+11 | 167453.37 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.557456E+11 | 167309.58 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183946E+11 | 166205.51 | 02-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.346573E+10 | 177247.98 | 13-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 24074403.65 | 13121.13 | 01-MAY-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.103609E+09 | 18543.26 | 30-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.304065E+10 | 166953.55 | 25-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150295E+11 | 166694.69 | 25-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.578849E+11 | 167005.47 | 26-DEC-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.641035E+11 | 177247.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.658574E+11 | 187920.90 | 17-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.591232E+11 | 187332.61 | 27-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147617E+11 | 186813.35 | 20-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384797E+10 | 200931.16 | 13-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2890832.50 | 1419.98 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166783E+10 | 185584.03 | 16-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.110796E+11 | 187027.39 | 24-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.586576E+11 | 187450.27 | 15-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214998E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.658574E+11 | 200931.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.576424E+11 | 176506.41 | 03-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.483262E+11 | 176098.00 | 21-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151786E+11 | 175415.04 | 20-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.269999E+10 | 175035.56 | 05-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 9577877.16 | 3992.16 | 12-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 49655073.03 | 7891.23 | 29-SEP-05:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.211891E+10 | 174769.38 | 17-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111615E+11 | 175608.87 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.468322E+11 | 176097.00 | 28-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.184019E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.576424E+11 | 176506.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.279372E+10 | 33984.61 | 23-JAN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.278013E+10 | 51850.39 | 21-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.714456E+09 | 37500.15 | 27-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189154E+09 | 32807.73 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 23280724.86 | 10287.36 | 04-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 997373.78 | 1606.23 | 10-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 7781436.21 | 6440.72 | 30-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144197E+09 | 28609.78 | 17-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211479E+09 | 30886.36 | 24-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.241348E+10 | 49047.26 | 27-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.927868E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.279372E+10 | 51850.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.142964E+11 | 76974.93 | 18-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119629E+11 | 76885.38 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.503580E+10 | 76795.00 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.895405E+09 | 76714.69 | 17-APR-04:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.902642E+09 | 77131.57 | 30-OCT-04:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.320576E+10 | 76956.01 | 20-NOV-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.119881E+11 | 77065.77 | 13-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.482870E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.142964E+11 | 77131.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.156049E+11 | 15989.07 | 02-JAN-04:43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.141229E+11 | 16003.10 | 02-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.763870E+10 | 16005.87 | 13-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.248390E+10 | 15977.98 | 03-APR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165959E+09 | 15907.91 | 12-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 639258.44 | 3893.66 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.120828E+09 | 15916.91 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.214605E+10 | 15994.37 | 16-OCT-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.537065E+10 | 15990.75 | 20-NOV-06:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144315E+11 | 16017.88 | 14-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.620860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156049E+11 | 16017.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.100341E+11 | 16931.52 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.900668E+10 | 16920.61 | 23-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.402532E+10 | 16907.64 | 13-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.127367E+10 | 16919.75 | 03-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 84905618.83 | 16865.60 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 160890.51 | 1072.60 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 79390013.85 | 11583.73 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.122345E+10 | 16949.94 | 10-OCT-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.359387E+10 | 16913.96 | 18-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.975246E+10 | 16969.73 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.390740E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.100341E+11 | 16969.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.117793E+11 | 20447.16 | 03-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109430E+11 | 20499.53 | 01-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.432804E+10 | 20431.50 | 09-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.176904E+10 | 20451.54 | 18-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150817E+09 | 18450.37 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 9334059.35 | 7219.51 | 14-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69117160.11 | 17211.53 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.123098E+10 | 20484.05 | 30-OCT-04:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.380451E+10 | 20470.44 | 14-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.115907E+11 | 20499.99 | 15-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.456749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.117793E+11 | 20499.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.942634E+10 | 18871.52 | 18-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.798151E+10 | 18843.03 | 17-FEB-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.344259E+10 | 18848.59 | 21-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.112264E+10 | 18755.18 | 05-APR-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 76556059.97 | 9675.68 | 12-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3856836.58 | 871.32 | 14-JUN-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 69689340.85 | 10954.34 | 29-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.110154E+10 | 18804.73 | 30-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295234E+10 | 18822.74 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.810826E+10 | 18871.87 | 19-DEC-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.342853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.942634E+10 | 18871.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 21219853.21 | 21219853.21 | 2568.54 | 06-JAN-13:10 | 2568.54 | 0.00 |
February | 0.00 | 0.00 | 18144811.43 | 18144811.43 | 2027.07 | 03-FEB-13:10 | 2027.07 | 0.00 |
March | 0.00 | 0.00 | 0.554183E+10 | 0.538861E+10 | 98338.81 | 14-MAR-13:10 | 84603.17 | 0.04 |
April | 0.00 | 0.00 | 0.220645E+10 | 0.220645E+10 | 47445.20 | 07-APR-14:00 | 47445.20 | 0.01 |
May | 0.00 | 0.00 | 0.170947E+11 | 0.168630E+11 | 90308.28 | 10-MAY-14:30 | 81065.58 | 0.11 |
June | 0.00 | 0.00 | 0.776827E+11 | 0.614678E+11 | 217873.63 | 27-JUN-05:03 | 92164.00 | 0.46 |
July | 0.00 | 0.00 | 0.139985E+12 | 0.100912E+12 | 274570.57 | 20-JUL-05:03 | 110005.06 | 0.74 |
August | 0.00 | 0.00 | 0.122247E+12 | 0.950999E+11 | 267032.39 | 14-AUG-04:23 | 100577.72 | 0.72 |
September | 0.00 | 0.00 | 0.466708E+11 | 0.370478E+11 | 188044.40 | 14-SEP-05:03 | 80335.32 | 0.32 |
October | 0.00 | 0.00 | 0.610909E+10 | 0.610310E+10 | 71882.62 | 11-OCT-15:00 | 71882.62 | 0.08 |
November | 0.00 | 0.00 | 0.101221E+10 | 0.101221E+10 | 54115.21 | 27-NOV-06:02 | 54115.21 | 0.02 |
December | 0.00 | 0.00 | 14708763.43 | 14708763.43 | 5188.53 | 15-DEC-08:10 | 5188.53 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.418603E+12 | 0.326155E+12 | 0.21 | |||
Minimum of Months | 0.00 | 0.00 | 14708763.43 | 14708763.43 | 2027.07 | 2027.07 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.139985E+12 | 0.100912E+12 | 274570.57 | 110005.06 | 0.74 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 9486165.94 | 9486165.94 | 1685.69 | 10-JAN-14:50 | 1685.69 | 0.00 |
February | 0.00 | 0.00 | 10410426.43 | 10410426.43 | 2128.94 | 28-FEB-11:30 | 2128.94 | 0.00 |
March | 0.00 | 0.00 | 0.354208E+11 | 0.343786E+11 | 676442.02 | 15-MAR-14:10 | 676442.02 | 0.04 |
April | 0.00 | 0.00 | 0.135248E+11 | 0.135248E+11 | 301395.44 | 07-APR-14:00 | 301395.44 | 0.01 |
May | 0.00 | 0.00 | 0.141384E+12 | 0.139494E+12 | 799707.53 | 24-MAY-05:03 | 535608.64 | 0.10 |
June | 0.00 | 0.00 | 0.626989E+12 | 0.502479E+12 | 2047684.13 | 27-JUN-05:03 | 865596.93 | 0.41 |
July | 0.00 | 0.00 | 0.107437E+13 | 0.790909E+12 | 2793507.06 | 20-JUL-03:02 | 1201111.66 | 0.60 |
August | 0.00 | 0.00 | 0.890325E+12 | 0.713097E+12 | 2437883.53 | 14-AUG-05:02 | 925932.75 | 0.56 |
September | 0.00 | 0.00 | 0.389991E+12 | 0.312889E+12 | 1844754.48 | 16-SEP-05:03 | 830920.97 | 0.31 |
October | 0.00 | 0.00 | 0.437743E+11 | 0.437536E+11 | 554430.73 | 11-OCT-15:00 | 554430.73 | 0.07 |
November | 0.00 | 0.00 | 0.582241E+10 | 0.582241E+10 | 155006.71 | 16-NOV-13:10 | 155006.71 | 0.02 |
December | 0.00 | 0.00 | 2388570.91 | 2388570.91 | 1301.24 | 22-DEC-13:40 | 1301.24 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.322162E+13 | 0.255637E+13 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 2388570.91 | 2388570.91 | 1301.24 | 1301.24 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107437E+13 | 0.790909E+12 | 2793507.06 | 1201111.66 | 0.60 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 11146237.06 | 11146237.06 | 364.74 | 06-JAN-13:10 | 364.74 | 0.00 |
February | 0.00 | 0.00 | 11402298.96 | 11402298.96 | 509.10 | 14-FEB-05:31 | 509.10 | 0.00 |
March | 0.00 | 0.00 | 0.376529E+10 | 0.374893E+10 | 85127.58 | 15-MAR-14:00 | 85127.58 | 0.05 |
April | 0.00 | 0.00 | 0.124957E+10 | 0.124957E+10 | 27653.86 | 07-APR-14:00 | 27653.86 | 0.01 |
May | 0.00 | 0.00 | 0.140105E+11 | 0.138776E+11 | 91921.60 | 10-MAY-14:50 | 83770.22 | 0.10 |
June | 0.00 | 0.00 | 0.688758E+11 | 0.548712E+11 | 282258.96 | 27-JUN-15:00 | 118085.35 | 0.41 |
July | 0.00 | 0.00 | 0.119937E+12 | 0.882900E+11 | 298289.02 | 20-JUL-03:02 | 128446.08 | 0.60 |
August | 0.00 | 0.00 | 0.967205E+11 | 0.771897E+11 | 260286.99 | 14-AUG-05:02 | 98827.85 | 0.56 |
September | 0.00 | 0.00 | 0.383610E+11 | 0.306610E+11 | 167252.54 | 15-SEP-12:40 | 91052.33 | 0.30 |
October | 0.00 | 0.00 | 0.358841E+10 | 0.358841E+10 | 51927.87 | 11-OCT-15:00 | 51927.87 | 0.07 |
November | 0.00 | 0.00 | 0.584440E+09 | 0.584440E+09 | 14807.36 | 27-NOV-06:02 | 14807.36 | 0.02 |
December | 0.00 | 0.00 | 7099229.82 | 7099229.82 | 1378.49 | 26-DEC-06:20 | 1378.49 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.347122E+12 | 0.274091E+12 | 0.18 | |||
Minimum of Months | 0.00 | 0.00 | 7099229.82 | 7099229.82 | 364.74 | 364.74 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.119937E+12 | 0.882900E+11 | 298289.02 | 128446.08 | 0.60 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 170747.40 | 170747.40 | 77.35 | 03-JAN-12:00 | 77.35 | 0.00 |
February | 0.00 | 0.00 | 2859.21 | 2859.21 | 4.66 | 27-FEB-16:40 | 4.66 | 0.00 |
March | 0.00 | 0.00 | 0.303668E+10 | 0.302932E+10 | 51731.76 | 15-MAR-14:00 | 51731.76 | 0.04 |
April | 0.00 | 0.00 | 0.513332E+09 | 0.513332E+09 | 22421.94 | 07-APR-14:00 | 22421.94 | 0.00 |
May | 0.00 | 0.00 | 0.727253E+10 | 0.723695E+10 | 72379.33 | 24-MAY-04:03 | 42091.92 | 0.07 |
June | 0.00 | 0.00 | 0.369770E+11 | 0.310895E+11 | 122851.08 | 27-JUN-05:05 | 52009.47 | 0.32 |
July | 0.00 | 0.00 | 0.719508E+11 | 0.539763E+11 | 163265.15 | 20-JUL-03:02 | 70599.89 | 0.48 |
August | 0.00 | 0.00 | 0.628733E+11 | 0.511881E+11 | 156240.97 | 14-AUG-03:02 | 60055.25 | 0.48 |
September | 0.00 | 0.00 | 0.266115E+11 | 0.223476E+11 | 115199.47 | 16-SEP-05:03 | 52427.80 | 0.25 |
October | 0.00 | 0.00 | 0.256818E+10 | 0.255585E+10 | 56042.12 | 26-OCT-05:02 | 29536.98 | 0.04 |
November | 0.00 | 0.00 | 0.508483E+09 | 0.508483E+09 | 47859.99 | 27-NOV-06:15 | 47859.99 | 0.01 |
December | 0.00 | 0.00 | 1539165.23 | 1539165.23 | 8400.41 | 01-DEC-06:03 | 8400.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212313E+12 | 0.172447E+12 | 0.14 | |||
Minimum of Months | 0.00 | 0.00 | 2859.21 | 2859.21 | 4.66 | 4.66 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.719508E+11 | 0.539763E+11 | 163265.15 | 70599.89 | 0.48 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.314274E+12 | 0.314265E+12 | 123602.70 | 18-JAN-22:10 | 123602.70 | 0.00 |
February | 0.00 | 0.00 | 0.503459E+12 | 0.503459E+12 | 215190.99 | 17-FEB-22:03 | 215190.99 | 0.00 |
March | 0.00 | 0.00 | 0.810131E+12 | 0.809620E+12 | 393816.41 | 31-MAR-24:00 | 393816.41 | 0.00 |
April | 0.00 | 0.00 | 0.102493E+13 | 0.102491E+13 | 399798.27 | 21-APR-21:03 | 399798.27 | 0.00 |
May | 0.00 | 0.00 | 0.330033E+12 | 0.329078E+12 | 212252.46 | 31-MAY-24:00 | 211506.14 | 0.00 |
June | 0.00 | 0.00 | 0.563621E+12 | 0.558843E+12 | 303561.71 | 30-JUN-24:00 | 303561.71 | 0.00 |
July | 0.00 | 0.00 | 0.833539E+12 | 0.826089E+12 | 396432.65 | 31-JUL-23:53 | 395759.74 | 0.00 |
August | 0.00 | 0.00 | 0.107461E+13 | 0.106981E+13 | 415613.61 | 26-AUG-16:03 | 404400.33 | 0.00 |
September | 0.00 | 0.00 | 0.327636E+12 | 0.323754E+12 | 211241.40 | 30-SEP-24:00 | 211241.40 | 0.00 |
October | 0.00 | 0.00 | 0.574726E+12 | 0.573900E+12 | 303934.12 | 31-OCT-24:00 | 303934.12 | 0.00 |
November | 0.00 | 0.00 | 0.789502E+12 | 0.789479E+12 | 309035.73 | 16-NOV-17:00 | 307974.01 | 0.00 |
December | 0.00 | 0.00 | 0.105404E+13 | 0.105402E+13 | 400241.59 | 21-DEC-22:02 | 400241.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.820050E+13 | 0.817723E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.314274E+12 | 0.314265E+12 | 123602.70 | 123602.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.107461E+13 | 0.106981E+13 | 415613.61 | 404400.33 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.271972E+10 | 0.271970E+10 | 2049.86 | 15-JAN-16:30 | 2049.86 | 0.00 |
February | 0.00 | 0.00 | 0.731981E+10 | 0.731981E+10 | 4022.24 | 28-FEB-17:00 | 4022.24 | 0.00 |
March | 0.00 | 0.00 | 0.147066E+11 | 0.146848E+11 | 7533.36 | 31-MAR-24:00 | 7533.36 | 0.00 |
April | 0.00 | 0.00 | 0.197093E+11 | 0.197065E+11 | 8521.44 | 02-APR-17:45 | 8521.44 | 0.00 |
May | 0.00 | 0.00 | 0.552367E+10 | 0.548630E+10 | 4030.03 | 31-MAY-24:00 | 4022.83 | 0.00 |
June | 0.00 | 0.00 | 0.107963E+11 | 0.106079E+11 | 5898.95 | 30-JUN-24:00 | 5898.95 | 0.00 |
July | 0.00 | 0.00 | 0.164687E+11 | 0.161551E+11 | 7809.26 | 31-JUL-23:53 | 7790.84 | 0.00 |
August | 0.00 | 0.00 | 0.213483E+11 | 0.211253E+11 | 8642.50 | 14-AUG-15:20 | 8264.76 | 0.00 |
September | 0.00 | 0.00 | 0.564350E+10 | 0.550196E+10 | 3747.54 | 30-SEP-24:00 | 3747.54 | 0.00 |
October | 0.00 | 0.00 | 0.102198E+11 | 0.101864E+11 | 5695.21 | 31-OCT-24:00 | 5695.21 | 0.00 |
November | 0.00 | 0.00 | 0.144455E+11 | 0.144439E+11 | 6025.66 | 05-NOV-12:50 | 6025.66 | 0.00 |
December | 0.00 | 0.00 | 0.191166E+11 | 0.191161E+11 | 7726.00 | 17-DEC-16:10 | 7726.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.148018E+12 | 0.147054E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.271972E+10 | 0.271970E+10 | 2049.86 | 2049.86 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.213483E+11 | 0.211253E+11 | 8642.50 | 8521.44 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.305314E+10 | 0.305310E+10 | 11460.59 | 12-JAN-16:40 | 11460.59 | 0.00 |
February | 0.00 | 0.00 | 0.438684E+11 | 0.438684E+11 | 33426.71 | 28-FEB-17:00 | 33426.71 | 0.00 |
March | 0.00 | 0.00 | 0.120105E+12 | 0.119888E+12 | 65960.88 | 31-MAR-23:50 | 65960.88 | 0.00 |
April | 0.00 | 0.00 | 0.175096E+12 | 0.175066E+12 | 77335.28 | 02-APR-17:55 | 77335.28 | 0.00 |
May | 0.00 | 0.00 | 0.467544E+11 | 0.463878E+11 | 37901.61 | 31-MAY-24:00 | 37835.75 | 0.00 |
June | 0.00 | 0.00 | 0.100608E+12 | 0.987383E+11 | 56607.18 | 30-JUN-24:00 | 56607.18 | 0.00 |
July | 0.00 | 0.00 | 0.156606E+12 | 0.153482E+12 | 75450.44 | 31-JUL-23:53 | 75269.58 | 0.00 |
August | 0.00 | 0.00 | 0.202842E+12 | 0.200612E+12 | 82041.64 | 10-AUG-18:10 | 80097.14 | 0.00 |
September | 0.00 | 0.00 | 0.486702E+11 | 0.472933E+11 | 31447.62 | 30-SEP-24:00 | 31447.62 | 0.00 |
October | 0.00 | 0.00 | 0.833946E+11 | 0.830644E+11 | 49093.50 | 31-OCT-24:00 | 49093.50 | 0.00 |
November | 0.00 | 0.00 | 0.116879E+12 | 0.116861E+12 | 54958.04 | 15-NOV-16:20 | 54958.04 | 0.00 |
December | 0.00 | 0.00 | 0.150208E+12 | 0.150202E+12 | 67299.03 | 01-DEC-13:20 | 66297.01 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124808E+13 | 0.123852E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.305314E+10 | 0.305310E+10 | 11460.59 | 11460.59 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202842E+12 | 0.200612E+12 | 82041.64 | 80097.14 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 69521586.30 | 69521586.30 | 892.51 | 12-JAN-16:30 | 892.51 | 0.00 |
February | 0.00 | 0.00 | 0.301291E+10 | 0.301291E+10 | 3362.08 | 28-FEB-17:00 | 3362.08 | 0.00 |
March | 0.00 | 0.00 | 0.104640E+11 | 0.104425E+11 | 6128.09 | 31-MAR-23:20 | 6128.09 | 0.00 |
April | 0.00 | 0.00 | 0.163693E+11 | 0.163664E+11 | 7738.66 | 09-APR-17:55 | 7738.66 | 0.00 |
May | 0.00 | 0.00 | 0.416600E+10 | 0.412998E+10 | 3702.52 | 31-MAY-24:00 | 3696.06 | 0.00 |
June | 0.00 | 0.00 | 0.997917E+10 | 0.979241E+10 | 5601.24 | 30-JUN-24:00 | 5601.24 | 0.00 |
July | 0.00 | 0.00 | 0.157157E+11 | 0.154036E+11 | 7549.20 | 31-JUL-23:53 | 7530.98 | 0.00 |
August | 0.00 | 0.00 | 0.202524E+11 | 0.200299E+11 | 8294.59 | 10-AUG-18:10 | 8100.25 | 0.00 |
September | 0.00 | 0.00 | 0.443652E+10 | 0.430048E+10 | 2701.07 | 04-SEP-17:34 | 2701.07 | 0.00 |
October | 0.00 | 0.00 | 0.686415E+10 | 0.683177E+10 | 4470.77 | 31-OCT-23:20 | 4470.77 | 0.00 |
November | 0.00 | 0.00 | 0.989935E+10 | 0.989768E+10 | 5337.80 | 15-NOV-16:20 | 5337.80 | 0.00 |
December | 0.00 | 0.00 | 0.132623E+11 | 0.132617E+11 | 6349.31 | 04-DEC-16:20 | 6349.31 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114491E+12 | 0.113539E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 69521586.30 | 69521586.30 | 892.51 | 892.51 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.202524E+11 | 0.200299E+11 | 8294.59 | 8100.25 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 147636.91 | 1942445.39 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 141279.78 | 1755590.72 | 27-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 44328.61 | 1573581.37 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 11214.03 | 1290503.64 | 05-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 241.48 | 97251.04 | 12-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 5.63 | 15197.32 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 4.67 | 15-JUL-07:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 228.06 | 114746.33 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7306.64 | 1345942.18 | 30-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 31086.99 | 1288631.29 | 20-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 120694.50 | 1656053.17 | 13-DEC-06:01 |
Annual Sum or Average | 0.00 | 41529.67 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 147636.91 | 1942445.39 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2371.03 | 28411.33 | 28-JAN-08:00 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2497.18 | 28979.63 | 28-FEB-16:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 33877.90 | 1399100.65 | 15-MAR-12:50 | 9.69 | 57736.36 | 16-MAR-04:35 |
April | 16869.26 | 838477.33 | 08-APR-13:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 131699.31 | 1388762.16 | 23-MAY-13:30 | 37.44 | 101968.00 | 14-MAY-16:53 |
June | 473159.82 | 2141852.83 | 27-JUN-05:05 | 0.52 | 6766.04 | 24-JUN-21:13 |
July | 704336.65 | 2868116.87 | 22-JUL-05:04 | 7.65 | 48466.39 | 06-JUL-00:42 |
August | 621987.28 | 3312988.05 | 14-AUG-05:03 | 0.30 | 4538.44 | 29-AUG-02:23 |
September | 315233.53 | 2104448.30 | 14-SEP-05:03 | 12.27 | 136030.13 | 18-SEP-03:02 |
October | 45342.21 | 1322740.19 | 11-OCT-15:00 | 64.51 | 184216.28 | 23-OCT-01:03 |
November | 8720.68 | 644583.49 | 16-NOV-13:00 | 17.99 | 140613.45 | 06-NOV-04:03 |
December | 2580.70 | 117463.87 | 01-DEC-06:03 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 198075.25 | 12.69 | ||||
Minimum of Months | 2371.03 | 28411.33 | 0.00 | 0.00 | ||
Maximum of Months | 704336.65 | 3312988.05 | 64.51 | 184216.28 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.62 | 332.48 | 20-JAN-08:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 7.86 | 2070.09 | 28-FEB-16:20 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 21664.07 | 1055193.94 | 15-MAR-13:30 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8372.52 | 579085.72 | 08-APR-13:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84495.52 | 1849992.22 | 24-MAY-05:03 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 371461.08 | 3687930.95 | 27-JUN-05:03 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 592178.60 | 4093660.68 | 20-JUL-05:03 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 511854.04 | 4208789.62 | 14-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 239020.74 | 3431077.62 | 16-SEP-05:03 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28219.70 | 1274323.64 | 11-OCT-14:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4100.50 | 498503.65 | 27-NOV-06:02 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18.74 | 107887.01 | 01-DEC-05:01 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 156384.29 | 0.00 | ||||
Minimum of Months | 1.62 | 332.48 | 0.00 | 0.00 | ||
Maximum of Months | 592178.60 | 4208789.62 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 153341.00 | 205026.99 | 17-JAN-13:20 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 291114.12 | 334381.89 | 15-FEB-11:10 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 465490.98 | 1129697.73 | 15-MAR-14:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 611826.64 | 1041872.13 | 08-APR-13:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 219700.04 | 698234.88 | 10-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 548400.44 | 1185712.76 | 27-JUN-13:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 909496.62 | 1473590.38 | 21-JUL-14:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1044840.50 | 1604655.54 | 10-AUG-14:10 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 283560.78 | 746854.09 | 16-SEP-14:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 334300.81 | 701173.91 | 11-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 459720.98 | 738291.37 | 05-NOV-14:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 574862.21 | 689784.31 | 01-DEC-11:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 493204.00 | 0.00 | ||||
Minimum of Months | 153341.00 | 205026.99 | 0.00 | 0.00 | ||
Maximum of Months | 1044840.50 | 1604655.54 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 16761.22 | 56743.07 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 17077.45 | 56966.69 | 17-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17827.51 | 56800.54 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 16191.61 | 55038.78 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 15822.32 | 52531.25 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15255.43 | 49349.35 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 13534.70 | 46507.22 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 14431.10 | 45034.58 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 13844.53 | 46449.09 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14446.19 | 49265.61 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15478.35 | 52350.72 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15778.20 | 54972.00 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15528.51 | ||||
Minimum of Months | 0.00 | 0.00 | 13534.70 | 45034.58 | ||
Maximum of Months | 0.00 | 0.00 | 17827.51 | 56966.69 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174.97 | 28764.70 | 27-JAN-06:40 | 2480.12 | 142972.10 | 13-JAN-20:20 |
February | 146.41 | 27866.52 | 09-FEB-15:20 | 2746.04 | 139783.90 | 17-FEB-21:50 |
March | 21696.07 | 1252950.26 | 14-MAR-12:40 | 3141.26 | 131235.90 | 21-MAR-10:50 |
April | 8150.83 | 495364.59 | 07-APR-14:00 | 2119.72 | 118222.82 | 15-APR-10:40 |
May | 82979.09 | 1148711.81 | 10-MAY-13:10 | 533.92 | 75335.73 | 04-MAY-11:40 |
June | 545230.94 | 5433516.23 | 27-JUN-07:40 | 360.79 | 97752.13 | 13-JUN-09:40 |
July | 1092252.34 | 5875875.42 | 19-JUL-09:20 | 129.23 | 60320.70 | 06-JUL-05:50 |
August | 781556.71 | 6224275.48 | 14-AUG-10:10 | 383.99 | 45690.29 | 12-AUG-21:15 |
September | 312914.41 | 4127354.50 | 15-SEP-11:00 | 303.77 | 60271.52 | 06-SEP-06:40 |
October | 26985.85 | 994081.68 | 11-OCT-14:10 | 980.00 | 113208.02 | 17-OCT-09:50 |
November | 4367.88 | 372823.57 | 16-NOV-13:00 | 2224.71 | 128463.28 | 24-NOV-09:40 |
December | 132.95 | 28140.45 | 29-DEC-21:10 | 3069.20 | 154779.34 | 10-DEC-04:02 |
Annual Sum or Average | 241926.41 | 1532.62 | ||||
Minimum of Months | 132.95 | 27866.52 | 129.23 | 45690.29 | ||
Maximum of Months | 1092252.34 | 6224275.48 | 3141.26 | 154779.34 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.126900E+11 | 0.75 | 9075.52 | 02-JAN-04:01 | 1.42 |
February | 0.115985E+11 | 0.76 | 9075.52 | 01-FEB-06:01 | 1.43 |
March | 0.142147E+11 | 0.83 | 9075.52 | 01-MAR-06:01 | 1.43 |
April | 0.132194E+11 | 0.80 | 9075.52 | 01-APR-04:02 | 1.43 |
May | 0.141850E+11 | 0.83 | 9075.52 | 01-MAY-03:02 | 1.42 |
June | 0.142477E+11 | 0.86 | 9075.52 | 01-JUN-03:20 | 1.42 |
July | 0.137943E+11 | 0.80 | 9075.52 | 01-JUL-03:02 | 1.41 |
August | 0.153567E+11 | 0.89 | 9075.52 | 01-AUG-03:02 | 1.42 |
September | 0.143130E+11 | 0.86 | 9075.52 | 01-SEP-03:02 | 1.41 |
October | 0.141233E+11 | 0.83 | 9075.52 | 02-OCT-03:02 | 1.42 |
November | 0.135368E+11 | 0.82 | 9075.52 | 01-NOV-03:10 | 1.42 |
December | 0.130312E+11 | 0.77 | 9075.52 | 01-DEC-05:01 | 1.42 |
Annual Sum or Average | 0.164311E+12 | 0.82 | |||
Minimum of Months | 0.115985E+11 | 0.75 | 9075.52 | 1.41 | |
Maximum of Months | 0.153567E+11 | 0.89 | 9075.52 | 1.43 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.304266E+10 | 0.30 | 12528.00 | 14-JAN-06:01 | 1.38 |
February | 0.288669E+10 | 0.31 | 12528.00 | 02-FEB-06:01 | 1.38 |
March | 0.537797E+10 | 0.39 | 13656.96 | 03-MAR-13:10 | 1.46 |
April | 0.690595E+10 | 0.46 | 13014.71 | 24-APR-15:20 | 1.42 |
May | 0.719838E+10 | 0.46 | 12726.35 | 17-MAY-05:03 | 1.39 |
June | 0.107035E+11 | 0.61 | 21094.66 | 21-JUN-05:02 | 1.91 |
July | 0.129188E+11 | 0.69 | 21094.66 | 17-JUL-04:53 | 1.90 |
August | 0.139996E+11 | 0.73 | 21094.66 | 14-AUG-04:23 | 1.90 |
September | 0.797174E+10 | 0.49 | 14459.47 | 05-SEP-15:10 | 1.51 |
October | 0.601891E+10 | 0.40 | 12314.31 | 11-OCT-15:40 | 1.36 |
November | 0.490418E+10 | 0.37 | 10816.97 | 16-NOV-06:02 | 1.26 |
December | 0.381674E+10 | 0.32 | 13165.00 | 04-DEC-13:10 | 1.43 |
Annual Sum or Average | 0.857452E+11 | 0.46 | |||
Minimum of Months | 0.288669E+10 | 0.30 | 10816.97 | 1.26 | |
Maximum of Months | 0.139996E+11 | 0.73 | 21094.66 | 1.91 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.344305E+11 | 0.37 | 48194.97 | 02-JAN-04:01 | 0.83 |
February | 0.311400E+11 | 0.37 | 48194.97 | 06-FEB-05:01 | 0.83 |
March | 0.340340E+11 | 0.34 | 91324.01 | 16-MAR-05:02 | 1.19 |
April | 0.351025E+11 | 0.33 | 128058.76 | 13-APR-05:02 | 1.47 |
May | 0.526897E+11 | 0.40 | 97391.21 | 24-MAY-05:03 | 1.23 |
June | 0.800689E+11 | 0.52 | 195153.40 | 19-JUN-05:03 | 1.90 |
July | 0.930318E+11 | 0.54 | 195153.40 | 05-JUL-05:02 | 1.91 |
August | 0.920430E+11 | 0.55 | 195153.40 | 11-AUG-05:03 | 1.91 |
September | 0.602525E+11 | 0.43 | 142126.37 | 16-SEP-05:03 | 1.56 |
October | 0.361529E+11 | 0.32 | 114050.31 | 25-OCT-05:02 | 1.37 |
November | 0.283588E+11 | 0.31 | 94734.49 | 02-NOV-05:03 | 1.22 |
December | 0.318254E+11 | 0.35 | 48194.97 | 11-DEC-05:01 | 0.83 |
Annual Sum or Average | 0.609130E+12 | 0.40 | |||
Minimum of Months | 0.283588E+11 | 0.31 | 48194.97 | 0.83 | |
Maximum of Months | 0.930318E+11 | 0.55 | 195153.40 | 1.91 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.435263E+10 | 0.44 | 4773.45 | 02-JAN-04:01 | 0.79 |
February | 0.401312E+10 | 0.44 | 4773.45 | 01-FEB-05:01 | 0.78 |
March | 0.386786E+10 | 0.38 | 8590.49 | 15-MAR-14:00 | 1.09 |
April | 0.324405E+10 | 0.33 | 6635.00 | 21-APR-15:30 | 0.94 |
May | 0.455513E+10 | 0.36 | 10610.87 | 31-MAY-16:00 | 1.24 |
June | 0.800037E+10 | 0.49 | 18576.29 | 27-JUN-05:03 | 1.75 |
July | 0.981272E+10 | 0.53 | 21216.24 | 05-JUL-05:02 | 1.90 |
August | 0.912401E+10 | 0.52 | 21216.24 | 14-AUG-05:02 | 1.90 |
September | 0.520161E+10 | 0.38 | 13656.00 | 21-SEP-15:50 | 1.44 |
October | 0.317280E+10 | 0.31 | 7645.28 | 12-OCT-05:03 | 1.02 |
November | 0.304191E+10 | 0.33 | 4773.45 | 13-NOV-05:01 | 0.78 |
December | 0.424786E+10 | 0.43 | 4773.45 | 02-DEC-06:01 | 0.78 |
Annual Sum or Average | 0.626341E+11 | 0.41 | |||
Minimum of Months | 0.304191E+10 | 0.31 | 4773.45 | 0.78 | |
Maximum of Months | 0.981272E+10 | 0.53 | 21216.24 | 1.90 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.964003E+11 | 1.38 | 35991.74 | 01-JAN-00:03 | 1.38 |
February | 0.870712E+11 | 1.38 | 35991.74 | 01-FEB-00:03 | 1.38 |
March | 0.964003E+11 | 1.38 | 35991.74 | 01-MAR-00:10 | 1.38 |
April | 0.932906E+11 | 1.38 | 35991.74 | 01-APR-00:10 | 1.38 |
May | 0.964003E+11 | 1.38 | 35991.74 | 01-MAY-00:07 | 1.38 |
June | 0.932906E+11 | 1.38 | 35991.74 | 01-JUN-00:10 | 1.38 |
July | 0.964003E+11 | 1.38 | 35991.74 | 01-JUL-00:10 | 1.38 |
August | 0.964003E+11 | 1.38 | 35991.74 | 01-AUG-00:05 | 1.38 |
September | 0.932906E+11 | 1.38 | 35991.74 | 01-SEP-00:10 | 1.38 |
October | 0.964003E+11 | 1.38 | 35991.74 | 01-OCT-00:30 | 1.38 |
November | 0.932906E+11 | 1.38 | 35991.74 | 01-NOV-00:10 | 1.38 |
December | 0.964003E+11 | 1.38 | 35991.74 | 01-DEC-00:10 | 1.38 |
Annual Sum or Average | 0.113504E+13 | 1.38 | |||
Minimum of Months | 0.870712E+11 | 1.38 | 35991.74 | 1.38 | |
Maximum of Months | 0.964003E+11 | 1.38 | 35991.74 | 1.38 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.147312E+10 | 0.94 | 550.00 | 01-JAN-00:03 | 0.94 |
February | 0.133056E+10 | 0.94 | 550.00 | 01-FEB-00:03 | 0.95 |
March | 0.147312E+10 | 0.94 | 550.00 | 01-MAR-00:10 | 0.94 |
April | 0.142560E+10 | 0.94 | 550.00 | 01-APR-00:10 | 0.94 |
May | 0.147312E+10 | 0.94 | 550.00 | 01-MAY-00:03 | 0.94 |
June | 0.142560E+10 | 0.94 | 550.00 | 01-JUN-00:10 | 0.94 |
July | 0.147312E+10 | 0.94 | 550.00 | 01-JUL-00:10 | 0.94 |
August | 0.147312E+10 | 0.94 | 550.00 | 01-AUG-00:05 | 0.94 |
September | 0.142560E+10 | 0.94 | 550.00 | 01-SEP-00:10 | 0.94 |
October | 0.147312E+10 | 0.94 | 550.00 | 01-OCT-00:10 | 0.94 |
November | 0.142560E+10 | 0.94 | 550.00 | 01-NOV-00:10 | 0.94 |
December | 0.147312E+10 | 0.94 | 550.00 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.173448E+11 | 0.94 | |||
Minimum of Months | 0.133056E+10 | 0.94 | 550.00 | 0.94 | |
Maximum of Months | 0.147312E+10 | 0.94 | 550.00 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140756E+11 | 0.94 | 5255.22 | 01-JAN-00:03 | 0.94 |
February | 0.127134E+11 | 0.94 | 5255.22 | 01-FEB-00:03 | 0.95 |
March | 0.140756E+11 | 0.94 | 5255.22 | 01-MAR-00:10 | 0.94 |
April | 0.136215E+11 | 0.94 | 5255.22 | 01-APR-00:30 | 0.94 |
May | 0.140756E+11 | 0.94 | 5255.22 | 01-MAY-00:03 | 0.94 |
June | 0.136215E+11 | 0.94 | 5255.22 | 01-JUN-00:10 | 0.94 |
July | 0.140756E+11 | 0.94 | 5255.22 | 01-JUL-00:10 | 0.94 |
August | 0.140756E+11 | 0.94 | 5255.22 | 01-AUG-00:05 | 0.94 |
September | 0.136215E+11 | 0.94 | 5255.22 | 01-SEP-00:10 | 0.94 |
October | 0.140756E+11 | 0.94 | 5255.22 | 01-OCT-00:10 | 0.94 |
November | 0.136215E+11 | 0.94 | 5255.22 | 01-NOV-00:10 | 0.94 |
December | 0.140756E+11 | 0.94 | 5255.22 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.165729E+12 | 0.94 | |||
Minimum of Months | 0.127134E+11 | 0.94 | 5255.22 | 0.94 | |
Maximum of Months | 0.140756E+11 | 0.94 | 5255.22 | 0.95 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143266E+10 | 0.94 | 534.90 | 01-JAN-00:03 | 0.94 |
February | 0.129402E+10 | 0.94 | 534.90 | 01-FEB-00:03 | 0.95 |
March | 0.143266E+10 | 0.94 | 534.90 | 01-MAR-00:10 | 0.94 |
April | 0.138645E+10 | 0.94 | 534.90 | 01-APR-00:10 | 0.94 |
May | 0.143266E+10 | 0.94 | 534.90 | 01-MAY-00:03 | 0.94 |
June | 0.138645E+10 | 0.94 | 534.90 | 01-JUN-00:10 | 0.94 |
July | 0.143266E+10 | 0.94 | 534.90 | 01-JUL-00:10 | 0.94 |
August | 0.143266E+10 | 0.94 | 534.90 | 01-AUG-00:05 | 0.94 |
September | 0.138645E+10 | 0.94 | 534.90 | 01-SEP-00:10 | 0.94 |
October | 0.143266E+10 | 0.94 | 534.90 | 01-OCT-00:10 | 0.94 |
November | 0.138645E+10 | 0.94 | 534.90 | 01-NOV-00:10 | 0.94 |
December | 0.143266E+10 | 0.94 | 534.90 | 01-DEC-00:10 | 0.94 |
Annual Sum or Average | 0.168685E+11 | 0.94 | |||
Minimum of Months | 0.129402E+10 | 0.94 | 534.90 | 0.94 | |
Maximum of Months | 0.143266E+10 | 0.94 | 534.90 | 0.95 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 46816608.02 | 42134947.22 | 1019.17 | 02-JAN-06:01 | 917.25 | 917.25 | 50.23 | 11.18 |
February | 40627969.04 | 36565172.14 | 977.38 | 22-FEB-06:03 | 879.64 | 879.64 | 48.52 | 10.98 |
March | 9554877.90 | 8599390.11 | 934.56 | 06-MAR-06:01 | 841.10 | 841.10 | 47.26 | 10.77 |
April | 1661031.86 | 1494928.68 | 277.52 | 05-APR-05:01 | 249.77 | 249.77 | 36.41 | 6.18 |
May | 18199.41 | 16379.47 | 3.40 | 12-MAY-05:03 | 3.06 | 3.06 | 23.64 | 0.42 |
June | 383.96 | 345.57 | 0.41 | 14-JUN-05:03 | 0.37 | 0.37 | 22.83 | 0.06 |
July | 0.13 | 0.12 | 0.00 | 15-JUL-07:50 | 0.00 | 0.00 | 22.73 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:05 | 0.00 | 0.00 | 22.73 | 0.00 |
September | 16738.24 | 15064.42 | 4.10 | 30-SEP-05:03 | 3.69 | 3.69 | 22.99 | 0.48 |
October | 977389.94 | 879650.94 | 303.15 | 30-OCT-05:01 | 272.83 | 272.83 | 39.66 | 6.45 |
November | 4536631.34 | 4082968.20 | 320.25 | 14-NOV-06:01 | 288.22 | 288.22 | 36.31 | 6.62 |
December | 33431270.97 | 30088143.88 | 1001.12 | 13-DEC-06:01 | 901.01 | 901.01 | 45.23 | 11.11 |
Annual Sum or Average | 0.137641E+09 | 0.123877E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.73 | 0.00 | |
Maximum of Months | 46816608.02 | 42134947.22 | 1019.17 | 917.25 | 917.25 | 50.23 | 11.18 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 6112.05 | 5500.85 | 0.35 | 06-JAN-13:10 | 0.31 | 0.31 | 6.77 | 0.08 |
February | 9525.15 | 8572.64 | 0.92 | 28-FEB-16:20 | 0.83 | 0.83 | 7.38 | 0.21 |
March | 40481777.03 | 36433599.32 | 1315.69 | 15-MAR-13:30 | 1184.12 | 1184.12 | 7.31 | 32.75 |
April | 5739088.59 | 5165179.73 | 298.30 | 08-APR-13:40 | 268.47 | 268.47 | 8.31 | 15.79 |
May | 0.124335E+09 | 0.111902E+09 | 4613.98 | 24-MAY-05:03 | 4152.58 | 4152.58 | 8.49 | 57.13 |
June | 0.863382E+09 | 0.777044E+09 | 22671.68 | 27-JUN-05:03 | 20404.51 | 20404.51 | 7.96 | 109.37 |
July | 0.168472E+10 | 0.151625E+10 | 22671.68 | 05-JUL-05:02 | 20404.51 | 20404.51 | 8.08 | 109.37 |
August | 0.160035E+10 | 0.144031E+10 | 22671.68 | 14-AUG-05:02 | 20404.51 | 20404.51 | 7.96 | 109.37 |
September | 0.576138E+09 | 0.518524E+09 | 21592.93 | 16-SEP-05:03 | 19433.63 | 19433.63 | 7.93 | 107.28 |
October | 56160050.53 | 50544045.48 | 4482.39 | 11-OCT-14:30 | 4034.15 | 4034.15 | 8.64 | 56.43 |
November | 3657595.55 | 3291835.99 | 371.39 | 27-NOV-06:02 | 334.25 | 334.25 | 8.21 | 17.69 |
December | 13767.28 | 12390.55 | 39.02 | 01-DEC-06:03 | 35.12 | 35.12 | 8.44 | 4.79 |
Annual Sum or Average | 0.495499E+10 | 0.445949E+10 | ||||||
Minimum of Months | 6112.05 | 5500.85 | 0.35 | 0.31 | 0.31 | 6.77 | 0.08 | |
Maximum of Months | 0.168472E+10 | 0.151625E+10 | 22671.68 | 20404.51 | 20404.51 | 8.64 | 109.37 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.355670E+10 | 0.320103E+10 | 15604.30 | 02-JAN-07:20 | 14043.87 | 14043.87 | 8.43 | 109.37 |
February | 0.336734E+10 | 0.303061E+10 | 15604.30 | 01-FEB-11:10 | 14043.87 | 14043.87 | 8.43 | 109.37 |
March | 0.555339E+10 | 0.499805E+10 | 15604.30 | 01-MAR-07:00 | 14043.87 | 14043.87 | 8.43 | 109.37 |
April | 0.485423E+10 | 0.436881E+10 | 15604.30 | 01-APR-07:25 | 14043.87 | 14043.87 | 8.43 | 109.37 |
May | 0.124138E+11 | 0.111725E+11 | 15604.30 | 02-MAY-09:15 | 14043.87 | 14043.87 | 8.45 | 109.37 |
June | 0.255730E+11 | 0.230157E+11 | 15604.30 | 01-JUN-03:02 | 14043.87 | 14043.87 | 8.48 | 109.37 |
July | 0.330230E+11 | 0.297207E+11 | 15604.30 | 01-JUL-03:02 | 14043.87 | 14043.87 | 8.44 | 109.37 |
August | 0.324091E+11 | 0.291682E+11 | 15604.30 | 01-AUG-00:05 | 14043.87 | 14043.87 | 8.01 | 109.37 |
September | 0.188570E+11 | 0.169713E+11 | 15604.30 | 01-SEP-03:02 | 14043.87 | 14043.87 | 8.55 | 109.37 |
October | 0.653361E+10 | 0.588025E+10 | 15604.30 | 02-OCT-03:02 | 14043.87 | 14043.87 | 8.57 | 109.37 |
November | 0.368535E+10 | 0.331681E+10 | 15604.30 | 01-NOV-09:30 | 14043.87 | 14043.87 | 8.46 | 109.37 |
December | 0.382078E+10 | 0.343871E+10 | 15604.30 | 01-DEC-05:01 | 14043.87 | 14043.87 | 8.52 | 109.37 |
Annual Sum or Average | 0.153647E+12 | 0.138283E+12 | ||||||
Minimum of Months | 0.336734E+10 | 0.303061E+10 | 15604.30 | 14043.87 | 14043.87 | 8.01 | 109.37 | |
Maximum of Months | 0.330230E+11 | 0.297207E+11 | 15604.30 | 14043.87 | 14043.87 | 8.57 | 109.37 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.910332E+10 | 0.819299E+10 | 3398.79 | 01-JAN-00:03 | 3058.91 | 3058.91 | 21.52 | 14.19 |
February | 0.822236E+10 | 0.740012E+10 | 3398.79 | 01-FEB-00:03 | 3058.91 | 3058.91 | 23.37 | 14.19 |
March | 0.910332E+10 | 0.819299E+10 | 3398.79 | 01-MAR-00:10 | 3058.91 | 3058.91 | 26.90 | 14.19 |
April | 0.880967E+10 | 0.792870E+10 | 3398.79 | 01-APR-00:10 | 3058.91 | 3058.91 | 30.14 | 14.19 |
May | 0.910332E+10 | 0.819299E+10 | 3398.79 | 01-MAY-00:03 | 3058.91 | 3058.91 | 22.37 | 14.19 |
June | 0.880967E+10 | 0.792870E+10 | 3398.79 | 01-JUN-00:10 | 3058.91 | 3058.91 | 26.57 | 14.19 |
July | 0.910332E+10 | 0.819299E+10 | 3398.79 | 01-JUL-00:10 | 3058.91 | 3058.91 | 30.53 | 14.19 |
August | 0.910332E+10 | 0.819299E+10 | 3398.79 | 01-AUG-00:05 | 3058.91 | 3058.91 | 37.01 | 14.19 |
September | 0.880967E+10 | 0.792870E+10 | 3398.79 | 01-SEP-00:10 | 3058.91 | 3058.91 | 22.45 | 14.19 |
October | 0.910332E+10 | 0.819299E+10 | 3398.79 | 01-OCT-00:10 | 3058.91 | 3058.91 | 24.67 | 14.19 |
November | 0.880967E+10 | 0.792870E+10 | 3398.79 | 01-NOV-00:10 | 3058.91 | 3058.91 | 27.46 | 14.19 |
December | 0.910332E+10 | 0.819299E+10 | 3398.79 | 01-DEC-00:10 | 3058.91 | 3058.91 | 29.79 | 14.19 |
Annual Sum or Average | 0.107184E+12 | 0.964659E+11 | ||||||
Minimum of Months | 0.822236E+10 | 0.740012E+10 | 3398.79 | 3058.91 | 3058.91 | 21.52 | 14.19 | |
Maximum of Months | 0.910332E+10 | 0.819299E+10 | 3398.79 | 3058.91 | 3058.91 | 37.01 | 14.19 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:03 | 1.79 | 1.79 | 55.51 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 55.86 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:01 | 1.79 | 1.79 | 55.84 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 56.17 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:02 | 1.79 | 1.79 | 56.04 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:02 | 1.79 | 1.79 | 56.48 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.65 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.87 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.68 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.36 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:02 | 1.79 | 1.79 | 55.60 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:03 | 1.79 | 1.79 | 55.84 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.51 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.87 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.438715E+10 | 0.394844E+10 | 19250.60 | 27-JAN-06:40 | 17325.54 | 17325.54 | 21.21 | 64.13 |
February | 0.415355E+10 | 0.373820E+10 | 19250.55 | 09-FEB-15:20 | 17325.50 | 17325.50 | 21.20 | 64.13 |
March | 0.698593E+10 | 0.628734E+10 | 38563.23 | 14-MAR-12:40 | 34706.91 | 34706.91 | 23.44 | 128.25 |
April | 0.598888E+10 | 0.538999E+10 | 19274.71 | 07-APR-14:00 | 17347.24 | 17347.24 | 22.95 | 64.13 |
May | 0.154163E+11 | 0.138747E+11 | 38552.36 | 10-MAY-12:40 | 34697.13 | 34697.13 | 23.04 | 128.25 |
June | 0.364684E+11 | 0.328216E+11 | 38730.03 | 27-JUN-07:10 | 34857.03 | 34857.03 | 29.19 | 128.25 |
July | 0.517305E+11 | 0.465574E+11 | 38730.03 | 05-JUL-09:40 | 34857.03 | 34857.03 | 28.90 | 128.25 |
August | 0.482506E+11 | 0.434255E+11 | 38730.03 | 07-AUG-11:40 | 34857.03 | 34857.03 | 28.94 | 128.25 |
September | 0.258992E+11 | 0.233093E+11 | 38729.77 | 15-SEP-11:00 | 34856.79 | 34856.79 | 28.80 | 128.25 |
October | 0.806331E+10 | 0.725698E+10 | 38541.87 | 11-OCT-15:00 | 34687.69 | 34687.69 | 22.66 | 128.25 |
November | 0.453547E+10 | 0.408193E+10 | 19268.37 | 16-NOV-13:00 | 17341.54 | 17341.54 | 22.49 | 64.13 |
December | 0.471283E+10 | 0.424154E+10 | 19250.57 | 29-DEC-21:10 | 17325.51 | 17325.51 | 21.20 | 64.13 |
Annual Sum or Average | 0.216592E+12 | 0.194933E+12 | ||||||
Minimum of Months | 0.415355E+10 | 0.373820E+10 | 19250.55 | 17325.50 | 17325.50 | 21.20 | 64.13 | |
Maximum of Months | 0.517305E+11 | 0.465574E+11 | 38730.03 | 34857.03 | 34857.03 | 29.19 | 128.25 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 34.43 | 34.43 | 147636.91 | 1942445.39 | 02-JAN-04:01 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 38.78 | 38.78 | 141279.78 | 1755590.72 | 27-FEB-05:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 28.67 | 28.67 | 44328.61 | 1573581.37 | 06-MAR-06:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 22.49 | 22.49 | 11214.03 | 1290503.64 | 05-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 21.97 | 21.97 | 241.48 | 97251.04 | 12-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.80 | 22.80 | 5.63 | 15197.32 | 14-JUN-05:03 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.73 | 22.73 | 0.00 | 4.67 | 15-JUL-07:50 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 22.73 | 22.73 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.73 | 22.73 | 228.06 | 114746.33 | 30-SEP-05:03 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.34 | 22.34 | 7306.64 | 1345942.18 | 30-OCT-04:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23.96 | 23.96 | 31086.99 | 1288631.29 | 20-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 25.31 | 25.31 | 120694.50 | 1656053.17 | 13-DEC-06:01 |
Annual Sum or Average | 0.00 | 41529.67 | ||||||
Minimum of Months | 0.00 | 0.00 | 21.97 | 21.97 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 38.78 | 38.78 | 147636.91 | 1942445.39 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 2371.03 | 28411.33 | 28-JAN-08:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 2497.18 | 28979.63 | 28-FEB-16:20 | 8.43 | 8.40 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 33877.90 | 1399100.65 | 15-MAR-12:50 | 10.01 | 8.37 | 9.69 | 57736.36 | 16-MAR-04:35 |
April | 16869.26 | 838477.33 | 08-APR-13:40 | 9.42 | 8.50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 131699.31 | 1388762.16 | 23-MAY-13:30 | 10.23 | 8.60 | 37.44 | 101968.00 | 14-MAY-16:53 |
June | 473159.82 | 2141852.83 | 27-JUN-05:05 | 12.20 | 7.53 | 0.52 | 6766.04 | 24-JUN-21:13 |
July | 704336.65 | 2868116.87 | 22-JUL-05:04 | 13.81 | 8.12 | 7.65 | 48466.39 | 06-JUL-00:42 |
August | 621987.28 | 3312988.05 | 14-AUG-05:03 | 14.52 | 8.84 | 0.30 | 4538.44 | 29-AUG-02:23 |
September | 315233.53 | 2104448.30 | 14-SEP-05:03 | 12.21 | 7.62 | 12.27 | 136030.13 | 18-SEP-03:02 |
October | 45342.21 | 1322740.19 | 11-OCT-15:00 | 10.26 | 8.79 | 64.51 | 184216.28 | 23-OCT-01:03 |
November | 8720.68 | 644583.49 | 16-NOV-13:00 | 9.28 | 8.57 | 17.99 | 140613.45 | 06-NOV-04:03 |
December | 2580.70 | 117463.87 | 01-DEC-06:03 | 8.63 | 8.50 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 198075.25 | 12.69 | ||||||
Minimum of Months | 2371.03 | 28411.33 | 8.43 | 7.53 | 0.00 | 0.00 | ||
Maximum of Months | 704336.65 | 3312988.05 | 14.52 | 8.84 | 64.51 | 184216.28 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 1.62 | 332.48 | 20-JAN-08:20 | 7.72 | 8.40 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 7.86 | 2070.09 | 28-FEB-16:20 | 9.06 | 8.40 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 21664.07 | 1055193.94 | 15-MAR-13:30 | 14.40 | 7.96 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 8372.52 | 579085.72 | 08-APR-13:40 | 15.47 | 8.30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 84495.52 | 1849992.22 | 24-MAY-05:03 | 14.44 | 8.69 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 371461.08 | 3687930.95 | 27-JUN-05:03 | 14.76 | 7.55 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 592178.60 | 4093660.68 | 20-JUL-05:03 | 15.65 | 7.24 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 511854.04 | 4208789.62 | 14-AUG-05:02 | 15.90 | 7.42 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 239020.74 | 3431077.62 | 16-SEP-05:03 | 14.34 | 7.59 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28219.70 | 1274323.64 | 11-OCT-14:10 | 12.34 | 8.54 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 4100.50 | 498503.65 | 27-NOV-06:02 | 13.43 | 8.18 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 18.74 | 107887.01 | 01-DEC-05:01 | 12.29 | 8.42 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 156384.29 | 0.00 | ||||||
Minimum of Months | 1.62 | 332.48 | 7.72 | 7.24 | 0.00 | 0.00 | ||
Maximum of Months | 592178.60 | 4208789.62 | 15.90 | 8.69 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 153341.00 | 205026.99 | 17-JAN-13:20 | 22.48 | 18.33 | 0.00 | 0.00 | 01-JAN-00:03 |
February | 291114.12 | 334381.89 | 15-FEB-11:10 | 25.09 | 18.33 | 0.00 | 0.00 | 01-FEB-00:03 |
March | 465490.98 | 1129697.73 | 15-MAR-14:00 | 40.83 | 30.64 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 611826.64 | 1041872.13 | 08-APR-13:10 | 39.11 | 26.58 | 0.00 | 0.00 | 01-APR-00:10 |
May | 219700.04 | 698234.88 | 10-MAY-15:00 | 32.35 | 28.01 | 0.00 | 0.00 | 01-MAY-00:03 |
June | 548400.44 | 1185712.76 | 27-JUN-13:00 | 41.92 | 34.09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 909496.62 | 1473590.38 | 21-JUL-14:00 | 47.49 | 36.60 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 1044840.50 | 1604655.54 | 10-AUG-14:10 | 50.00 | 36.57 | 0.00 | 0.00 | 01-AUG-00:05 |
September | 283560.78 | 746854.09 | 16-SEP-14:00 | 33.31 | 29.07 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 334300.81 | 701173.91 | 11-OCT-15:00 | 32.40 | 25.31 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 459720.98 | 738291.37 | 05-NOV-14:00 | 33.14 | 23.60 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 574862.21 | 689784.31 | 01-DEC-11:00 | 32.18 | 20.24 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 493204.00 | 0.00 | ||||||
Minimum of Months | 153341.00 | 205026.99 | 22.48 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 1044840.50 | 1604655.54 | 50.00 | 36.60 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:03 | 57.02 | 57.02 | 16761.22 | 56743.07 | 31-JAN-12:40 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 56.37 | 56.37 | 17077.45 | 56966.69 | 17-FEB-12:40 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.38 | 56.38 | 17827.51 | 56800.54 | 01-MAR-12:10 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.57 | 56.57 | 16191.61 | 55038.78 | 03-APR-11:20 |
May | 0.00 | 0.00 | 01-MAY-00:03 | 56.88 | 56.88 | 15822.32 | 52531.25 | 01-MAY-11:40 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 56.71 | 56.71 | 15255.43 | 49349.35 | 01-JUN-11:50 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.13 | 57.13 | 13534.70 | 46507.22 | 03-JUL-11:30 |
August | 0.00 | 0.00 | 01-AUG-00:05 | 57.38 | 57.38 | 14431.10 | 45034.58 | 01-AUG-11:40 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 57.28 | 57.28 | 13844.53 | 46449.09 | 29-SEP-11:40 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.66 | 56.66 | 14446.19 | 49265.61 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.19 | 56.19 | 15478.35 | 52350.72 | 30-NOV-12:50 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.38 | 56.38 | 15778.20 | 54972.00 | 29-DEC-12:40 |
Annual Sum or Average | 0.00 | 15528.51 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.19 | 56.19 | 13534.70 | 45034.58 | ||
Maximum of Months | 0.00 | 0.00 | 57.38 | 57.38 | 17827.51 | 56966.69 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 174.97 | 28764.70 | 27-JAN-06:40 | 21.21 | 20.36 | 2480.12 | 142972.10 | 13-JAN-20:20 |
February | 146.41 | 27866.52 | 09-FEB-15:20 | 21.20 | 20.35 | 2746.04 | 139783.90 | 17-FEB-21:50 |
March | 21696.07 | 1252950.26 | 14-MAR-12:40 | 23.44 | 22.29 | 3141.26 | 131235.90 | 21-MAR-10:50 |
April | 8150.83 | 495364.59 | 07-APR-14:00 | 22.95 | 21.10 | 2119.72 | 118222.82 | 15-APR-10:40 |
May | 82979.09 | 1148711.81 | 10-MAY-13:10 | 25.39 | 22.17 | 533.92 | 75335.73 | 04-MAY-11:40 |
June | 545230.94 | 5433516.23 | 27-JUN-07:40 | 31.24 | 26.77 | 360.79 | 97752.13 | 13-JUN-09:40 |
July | 1092252.34 | 5875875.42 | 19-JUL-09:20 | 32.06 | 27.14 | 129.23 | 60320.70 | 06-JUL-05:50 |
August | 781556.71 | 6224275.48 | 14-AUG-10:10 | 32.71 | 27.51 | 383.99 | 45690.29 | 12-AUG-21:15 |
September | 312914.41 | 4127354.50 | 15-SEP-11:00 | 28.80 | 24.90 | 303.77 | 60271.52 | 06-SEP-06:40 |
October | 26985.85 | 994081.68 | 11-OCT-14:10 | 24.81 | 21.10 | 980.00 | 113208.02 | 17-OCT-09:50 |
November | 4367.88 | 372823.57 | 16-NOV-13:00 | 22.49 | 21.10 | 2224.71 | 128463.28 | 24-NOV-09:40 |
December | 132.95 | 28140.45 | 29-DEC-21:10 | 21.20 | 20.35 | 3069.20 | 154779.34 | 10-DEC-04:02 |
Annual Sum or Average | 241926.41 | 1532.62 | ||||||
Minimum of Months | 132.95 | 27866.52 | 21.20 | 20.35 | 129.23 | 45690.29 | ||
Maximum of Months | 1092252.34 | 6224275.48 | 32.71 | 27.51 | 3141.26 | 154779.34 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.635529E+10 | 0.00 | 21219853.21 | 0.304266E+10 | 0.00 | 0.00 |
February | 0.521540E+10 | 0.00 | 18144811.43 | 0.288669E+10 | 0.00 | 0.00 |
March | 0.998792E+09 | 0.00 | 0.554183E+10 | 0.537797E+10 | 0.00 | 0.00 |
April | 0.129234E+09 | 0.00 | 0.220645E+10 | 0.690595E+10 | 0.00 | 0.00 |
May | 8088224.44 | 0.00 | 0.170947E+11 | 0.719838E+10 | 0.00 | 0.00 |
June | 64.88 | 0.00 | 0.776827E+11 | 0.107035E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.139985E+12 | 0.129188E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.122247E+12 | 0.139996E+11 | 0.00 | 0.00 |
September | 597766.78 | 0.00 | 0.466708E+11 | 0.797174E+10 | 0.00 | 0.00 |
October | 95142779.81 | 0.00 | 0.610909E+10 | 0.601891E+10 | 0.00 | 0.00 |
November | 0.319213E+09 | 0.00 | 0.101221E+10 | 0.490418E+10 | 0.00 | 0.00 |
December | 0.327013E+10 | 0.00 | 14708763.43 | 0.381674E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.163919E+11 | 0.00 | 0.418603E+12 | 0.857452E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 14708763.43 | 0.288669E+10 | 0.00 | 0.00 |
Maximum of Months | 0.635529E+10 | 0.00 | 0.139985E+12 | 0.139996E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.327128E+12 | 0.00 | 9486165.94 | 0.344305E+11 | 0.00 | 0.00 |
February | 0.281599E+12 | 0.00 | 10410426.43 | 0.311400E+11 | 0.00 | 0.00 |
March | 0.931995E+11 | 0.00 | 0.354208E+11 | 0.340340E+11 | 0.00 | 0.00 |
April | 0.213527E+11 | 0.00 | 0.135248E+11 | 0.351025E+11 | 0.00 | 0.00 |
May | 0.135191E+09 | 0.00 | 0.141384E+12 | 0.526897E+11 | 0.00 | 0.00 |
June | 176999.76 | 0.00 | 0.626989E+12 | 0.800689E+11 | 0.00 | 0.00 |
July | 5668.73 | 0.00 | 0.107437E+13 | 0.930318E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.890325E+12 | 0.920430E+11 | 0.00 | 0.00 |
September | 0.250062E+09 | 0.00 | 0.389991E+12 | 0.602525E+11 | 0.00 | 0.00 |
October | 0.128123E+11 | 0.00 | 0.437743E+11 | 0.361529E+11 | 0.00 | 0.00 |
November | 0.615030E+11 | 0.00 | 0.582241E+10 | 0.283588E+11 | 0.00 | 0.00 |
December | 0.263314E+12 | 0.00 | 2388570.91 | 0.318254E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.106129E+13 | 0.00 | 0.322162E+13 | 0.609130E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2388570.91 | 0.283588E+11 | 0.00 | 0.00 |
Maximum of Months | 0.327128E+12 | 0.00 | 0.107437E+13 | 0.930318E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.639348E+11 | 0.00 | 11146237.06 | 0.435263E+10 | 0.00 | 0.00 |
February | 0.567971E+11 | 0.00 | 11402298.96 | 0.401312E+10 | 0.00 | 0.00 |
March | 0.251849E+11 | 0.00 | 0.376529E+10 | 0.386786E+10 | 0.00 | 0.00 |
April | 0.773381E+10 | 0.00 | 0.124957E+10 | 0.324405E+10 | 0.00 | 0.00 |
May | 0.501518E+09 | 0.00 | 0.140105E+11 | 0.455513E+10 | 0.00 | 0.00 |
June | 14988418.66 | 0.00 | 0.688758E+11 | 0.800037E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.119937E+12 | 0.981272E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.967205E+11 | 0.912401E+10 | 0.00 | 0.00 |
September | 0.346806E+09 | 0.00 | 0.383610E+11 | 0.520161E+10 | 0.00 | 0.00 |
October | 0.674886E+10 | 0.00 | 0.358841E+10 | 0.317280E+10 | 0.00 | 0.00 |
November | 0.191386E+11 | 0.00 | 0.584440E+09 | 0.304191E+10 | 0.00 | 0.00 |
December | 0.582845E+11 | 0.00 | 7099229.82 | 0.424786E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.238686E+12 | 0.00 | 0.347122E+12 | 0.626341E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 7099229.82 | 0.304191E+10 | 0.00 | 0.00 |
Maximum of Months | 0.639348E+11 | 0.00 | 0.119937E+12 | 0.981272E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 170747.40 | 0.126900E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 2859.21 | 0.115985E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.303668E+10 | 0.142147E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.513332E+09 | 0.132194E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.727253E+10 | 0.141850E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.369770E+11 | 0.142477E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.719508E+11 | 0.137943E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.628733E+11 | 0.153567E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.266115E+11 | 0.143130E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.256818E+10 | 0.141233E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.508483E+09 | 0.135368E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 1539165.23 | 0.130312E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212313E+12 | 0.164311E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 2859.21 | 0.115985E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.719508E+11 | 0.153567E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.393656E+12 | 0.180041E+12 | 0.00 | 1.58 |
February | 0.00 | 0.00 | 0.624187E+12 | 0.211616E+12 | 0.00 | 1.42 |
March | 0.00 | 0.00 | 0.997865E+12 | 0.287005E+12 | 0.00 | 1.07 |
April | 0.00 | 0.00 | 0.125407E+13 | 0.323569E+12 | 0.00 | 0.42 |
May | 0.00 | 0.00 | 0.414394E+12 | 0.181392E+12 | 0.00 | 0.23 |
June | 0.00 | 0.00 | 0.715212E+12 | 0.244958E+12 | 0.00 | 0.03 |
July | 0.00 | 0.00 | 0.107412E+13 | 0.336985E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.137222E+13 | 0.394011E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.413456E+12 | 0.179111E+12 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.712593E+12 | 0.234766E+12 | 0.00 | 0.19 |
November | 0.00 | 0.00 | 0.971390E+12 | 0.276511E+12 | 0.00 | 0.50 |
December | 0.00 | 0.00 | 0.128755E+13 | 0.333249E+12 | 0.00 | 1.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.102307E+14 | 0.318321E+13 | 0.00 | 6.68 |
Minimum of Months | 0.00 | 0.00 | 0.393656E+12 | 0.179111E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.137222E+13 | 0.394011E+12 | 0.00 | 1.58 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.348332E+10 | 0.223672E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.921259E+10 | 0.322335E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.182367E+11 | 0.500322E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.241406E+11 | 0.585691E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.693733E+10 | 0.288678E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.136558E+11 | 0.428503E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211315E+11 | 0.613598E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.271860E+11 | 0.731082E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.710478E+10 | 0.288689E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.126645E+11 | 0.391780E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.178161E+11 | 0.479622E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.235520E+11 | 0.590855E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185121E+12 | 0.544483E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.348332E+10 | 0.223672E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.271860E+11 | 0.731082E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.406305E+10 | 0.150855E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.556422E+11 | 0.244872E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.149442E+12 | 0.434121E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.214868E+12 | 0.533936E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.588507E+11 | 0.261719E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.127352E+12 | 0.403663E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.200992E+12 | 0.584621E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.258377E+12 | 0.696107E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.614094E+11 | 0.263607E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.103641E+12 | 0.343217E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.144666E+12 | 0.414078E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.185942E+12 | 0.498099E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156525E+13 | 0.482889E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.406305E+10 | 0.150855E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.258377E+12 | 0.696107E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 92812393.66 | 0.145595E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.383812E+10 | 0.211922E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.130560E+11 | 0.402467E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.201268E+11 | 0.514398E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.525639E+10 | 0.252305E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.126437E+11 | 0.405096E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.201811E+11 | 0.589807E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.258165E+11 | 0.699673E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.561267E+10 | 0.256260E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.855819E+10 | 0.312671E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.122941E+11 | 0.378118E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.164664E+11 | 0.463684E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143943E+12 | 0.463200E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 92812393.66 | 0.145595E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.258165E+11 | 0.699673E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.304266E+10 | 21219853.21 | 0.635529E+10 | 0.349040E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288669E+10 | 18144811.43 | 0.521540E+10 | 0.318983E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537797E+10 | 0.554183E+10 | 0.998792E+09 | 0.129944E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690595E+10 | 0.220645E+10 | 0.129234E+09 | 0.143620E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719838E+10 | 0.170947E+11 | 8088224.44 | 31068023.47 | 629161.71 | 0.00 | 0.00 | 0.00 |
June | 0.107035E+11 | 0.776827E+11 | 64.88 | 0.136807E+09 | 0.185617E+10 | 0.00 | 0.00 | 0.00 |
July | 0.129188E+11 | 0.139985E+12 | 0.00 | 0.127016E+09 | 0.545897E+10 | 0.00 | 0.00 | 0.00 |
August | 0.139996E+11 | 0.122247E+12 | 0.00 | 0.610317E+09 | 0.213850E+10 | 0.00 | 0.00 | 0.00 |
September | 0.797174E+10 | 0.466708E+11 | 597766.78 | 42715790.50 | 0.279676E+09 | 0.00 | 0.00 | 0.00 |
October | 0.601891E+10 | 0.610909E+10 | 95142779.81 | 0.825413E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490418E+10 | 0.101221E+10 | 0.319213E+09 | 0.326540E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381674E+10 | 14708763.43 | 0.327013E+10 | 0.249795E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.857452E+11 | 0.418603E+12 | 0.163919E+11 | 0.111251E+12 | 0.973394E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.288669E+10 | 14708763.43 | 0.00 | 31068023.47 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139996E+11 | 0.139985E+12 | 0.635529E+10 | 0.349040E+11 | 0.545897E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.344305E+11 | 9486165.94 | 0.327128E+12 | 0.383720E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311400E+11 | 10410426.43 | 0.281599E+12 | 0.349889E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340340E+11 | 0.354208E+11 | 0.931995E+11 | 0.196879E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351025E+11 | 0.135248E+11 | 0.213527E+11 | 0.420856E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.526897E+11 | 0.141384E+12 | 0.135191E+09 | 0.118326E+10 | 5076062.83 | 0.00 | 0.00 | 0.00 |
June | 0.800689E+11 | 0.626989E+12 | 176999.76 | 0.158088E+10 | 0.186250E+11 | 0.00 | 0.00 | 0.00 |
July | 0.930318E+11 | 0.107437E+13 | 5668.73 | 0.160444E+10 | 0.541068E+11 | 0.00 | 0.00 | 0.00 |
August | 0.920430E+11 | 0.890325E+12 | 0.00 | 0.674621E+10 | 0.211216E+11 | 0.00 | 0.00 | 0.00 |
September | 0.602525E+11 | 0.389991E+12 | 0.250062E+09 | 0.502253E+09 | 0.291403E+10 | 0.00 | 0.00 | 0.00 |
October | 0.361529E+11 | 0.437743E+11 | 0.128123E+11 | 0.207715E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283588E+11 | 0.582241E+10 | 0.615030E+11 | 0.907110E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318254E+11 | 2388570.91 | 0.263314E+12 | 0.337765E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609130E+12 | 0.322162E+13 | 0.106129E+13 | 0.143344E+13 | 0.967725E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283588E+11 | 2388570.91 | 0.00 | 0.502253E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.930318E+11 | 0.107437E+13 | 0.327128E+12 | 0.383720E+12 | 0.541068E+11 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.435263E+10 | 11146237.06 | 0.639348E+11 | 0.417669E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401312E+10 | 11402298.96 | 0.567971E+11 | 0.377962E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386786E+10 | 0.376529E+10 | 0.251849E+11 | 0.220009E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324405E+10 | 0.124957E+10 | 0.773381E+10 | 0.623722E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.455513E+10 | 0.140105E+11 | 0.501518E+09 | 0.274301E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.800037E+10 | 0.688758E+11 | 14988418.66 | 0.145720E+09 | 0.151261E+10 | 0.00 | 0.00 | 0.00 |
July | 0.981272E+10 | 0.119937E+12 | 0.00 | 0.112018E+09 | 0.448592E+10 | 0.00 | 0.00 | 0.00 |
August | 0.912401E+10 | 0.967205E+11 | 0.00 | 0.619612E+09 | 0.158937E+10 | 0.00 | 0.00 | 0.00 |
September | 0.520161E+10 | 0.383610E+11 | 0.346806E+09 | 0.103530E+09 | 0.177738E+09 | 0.00 | 0.00 | 0.00 |
October | 0.317280E+10 | 0.358841E+10 | 0.674886E+10 | 0.369122E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304191E+10 | 0.584440E+09 | 0.191386E+11 | 0.127608E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.424786E+10 | 7099229.82 | 0.582845E+11 | 0.361503E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626341E+11 | 0.347122E+12 | 0.238686E+12 | 0.161659E+12 | 0.776564E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304191E+10 | 7099229.82 | 0.00 | 0.103530E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.981272E+10 | 0.119937E+12 | 0.639348E+11 | 0.417669E+11 | 0.448592E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.126900E+11 | 170747.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115985E+11 | 2859.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142147E+11 | 0.303668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132194E+11 | 0.513332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141850E+11 | 0.727253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142477E+11 | 0.369770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137943E+11 | 0.719508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153567E+11 | 0.628733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143130E+11 | 0.266115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141233E+11 | 0.256818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135368E+11 | 0.508483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130312E+11 | 1539165.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164311E+12 | 0.212313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115985E+11 | 2859.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153567E+11 | 0.719508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.964003E+11 | 0.314274E+12 | 0.00 | 0.00 | 0.00 | 0.423994E+10 | 0.00 | 0.00 |
February | 0.870712E+11 | 0.503459E+12 | 0.00 | 0.00 | 0.00 | 0.379863E+10 | 0.00 | 0.00 |
March | 0.964003E+11 | 0.810131E+12 | 0.00 | 0.00 | 0.00 | 0.285762E+10 | 0.00 | 0.00 |
April | 0.932906E+11 | 0.102493E+13 | 0.00 | 0.00 | 0.00 | 0.113185E+10 | 0.00 | 0.00 |
May | 0.964003E+11 | 0.330033E+12 | 0.00 | 0.00 | 0.00 | 0.628275E+09 | 0.00 | 0.00 |
June | 0.932906E+11 | 0.563621E+12 | 0.00 | 0.00 | 0.00 | 76598177.94 | 0.00 | 0.00 |
July | 0.964003E+11 | 0.833539E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.964003E+11 | 0.107461E+13 | 0.00 | 0.00 | 0.00 | 462770.55 | 0.00 | 0.00 |
September | 0.932906E+11 | 0.327636E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.964003E+11 | 0.574726E+12 | 0.00 | 0.00 | 0.00 | 0.496896E+09 | 0.00 | 0.00 |
November | 0.932906E+11 | 0.789502E+12 | 0.00 | 0.00 | 0.00 | 0.132590E+10 | 0.00 | 0.00 |
December | 0.964003E+11 | 0.105404E+13 | 0.00 | 0.00 | 0.00 | 0.331638E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.113504E+13 | 0.820050E+13 | 0.00 | 0.00 | 0.00 | 0.178726E+11 | 0.00 | 0.00 |
Minimum of Months | 0.870712E+11 | 0.314274E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.964003E+11 | 0.107461E+13 | 0.00 | 0.00 | 0.00 | 0.423994E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.147312E+10 | 0.271972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133056E+10 | 0.731981E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147312E+10 | 0.147066E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142560E+10 | 0.197093E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147312E+10 | 0.552367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142560E+10 | 0.107963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147312E+10 | 0.164687E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147312E+10 | 0.213483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142560E+10 | 0.564350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147312E+10 | 0.102198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142560E+10 | 0.144455E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147312E+10 | 0.191166E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173448E+11 | 0.148018E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133056E+10 | 0.271972E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147312E+10 | 0.213483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140756E+11 | 0.305314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127134E+11 | 0.438684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140756E+11 | 0.120105E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136215E+11 | 0.175096E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140756E+11 | 0.467544E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136215E+11 | 0.100608E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140756E+11 | 0.156606E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140756E+11 | 0.202842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136215E+11 | 0.486702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140756E+11 | 0.833946E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136215E+11 | 0.116879E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140756E+11 | 0.150208E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165729E+12 | 0.124808E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127134E+11 | 0.305314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140756E+11 | 0.202842E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143266E+10 | 69521586.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129402E+10 | 0.301291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143266E+10 | 0.104640E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138645E+10 | 0.163693E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143266E+10 | 0.416600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138645E+10 | 0.997917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143266E+10 | 0.157157E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143266E+10 | 0.202524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138645E+10 | 0.443652E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143266E+10 | 0.686415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138645E+10 | 0.989935E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143266E+10 | 0.132623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168685E+11 | 0.114491E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129402E+10 | 69521586.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143266E+10 | 0.202524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.304266E+10 | 0.635529E+10 | 21219853.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.288669E+10 | 0.521540E+10 | 18144811.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.537797E+10 | 0.998792E+09 | 0.554183E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.690595E+10 | 0.129234E+09 | 0.220645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.719838E+10 | 8088224.44 | 0.170947E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.107035E+11 | 64.88 | 0.776827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129188E+11 | 0.00 | 0.139985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.139996E+11 | 0.00 | 0.122247E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.797174E+10 | 597766.78 | 0.466708E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.601891E+10 | 95142779.81 | 0.610909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.490418E+10 | 0.319213E+09 | 0.101221E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381674E+10 | 0.327013E+10 | 14708763.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.857452E+11 | 0.163919E+11 | 0.418603E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.288669E+10 | 0.00 | 14708763.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.139996E+11 | 0.635529E+10 | 0.139985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.344305E+11 | 0.327128E+12 | 9486165.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.311400E+11 | 0.281599E+12 | 10410426.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.340340E+11 | 0.931995E+11 | 0.354208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.351025E+11 | 0.213527E+11 | 0.135248E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.526897E+11 | 0.135191E+09 | 0.141384E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.800689E+11 | 176999.76 | 0.626989E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.930318E+11 | 5668.73 | 0.107437E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.920430E+11 | 0.00 | 0.890325E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.602525E+11 | 0.250062E+09 | 0.389991E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.361529E+11 | 0.128123E+11 | 0.437743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.283588E+11 | 0.615030E+11 | 0.582241E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.318254E+11 | 0.263314E+12 | 2388570.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.609130E+12 | 0.106129E+13 | 0.322162E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283588E+11 | 0.00 | 2388570.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.930318E+11 | 0.327128E+12 | 0.107437E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.435263E+10 | 0.639348E+11 | 11146237.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.401312E+10 | 0.567971E+11 | 11402298.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.386786E+10 | 0.251849E+11 | 0.376529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.324405E+10 | 0.773381E+10 | 0.124957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.455513E+10 | 0.501518E+09 | 0.140105E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.800037E+10 | 14988418.66 | 0.688758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.981272E+10 | 0.00 | 0.119937E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.912401E+10 | 0.00 | 0.967205E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.520161E+10 | 0.346806E+09 | 0.383610E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.317280E+10 | 0.674886E+10 | 0.358841E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304191E+10 | 0.191386E+11 | 0.584440E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.424786E+10 | 0.582845E+11 | 7099229.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.626341E+11 | 0.238686E+12 | 0.347122E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.304191E+10 | 0.00 | 7099229.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.981272E+10 | 0.639348E+11 | 0.119937E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.126900E+11 | 0.00 | 170747.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.115985E+11 | 0.00 | 2859.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142147E+11 | 0.00 | 0.303668E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.132194E+11 | 0.00 | 0.513332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141850E+11 | 0.00 | 0.727253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142477E+11 | 0.00 | 0.369770E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.137943E+11 | 0.00 | 0.719508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153567E+11 | 0.00 | 0.628733E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143130E+11 | 0.00 | 0.266115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141233E+11 | 0.00 | 0.256818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135368E+11 | 0.00 | 0.508483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.130312E+11 | 0.00 | 1539165.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164311E+12 | 0.00 | 0.212313E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.115985E+11 | 0.00 | 2859.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153567E+11 | 0.00 | 0.719508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.964003E+11 | 0.00 | 0.393656E+12 | 0.00 | 0.793819E+11 | 0.00 | 0.00 | 0.00 | 0.425902E+10 | 0.00 | 0.00 | 0.00 |
February | 0.870712E+11 | 0.00 | 0.624187E+12 | 0.00 | 0.120729E+12 | 0.00 | 0.00 | 0.00 | 0.381573E+10 | 0.00 | 0.00 | 0.00 |
March | 0.964003E+11 | 0.00 | 0.997865E+12 | 0.00 | 0.187734E+12 | 0.00 | 0.00 | 0.00 | 0.287048E+10 | 0.00 | 0.00 | 0.00 |
April | 0.932906E+11 | 0.00 | 0.125407E+13 | 0.00 | 0.229142E+12 | 0.00 | 0.00 | 0.00 | 0.113694E+10 | 0.00 | 0.00 | 0.00 |
May | 0.964003E+11 | 0.00 | 0.414394E+12 | 0.00 | 0.843605E+11 | 0.00 | 0.00 | 0.00 | 0.631104E+09 | 0.00 | 0.00 | 0.00 |
June | 0.932906E+11 | 0.00 | 0.715212E+12 | 0.00 | 0.151590E+12 | 0.00 | 0.00 | 0.00 | 76942977.39 | 0.00 | 0.00 | 0.00 |
July | 0.964003E+11 | 0.00 | 0.107412E+13 | 0.00 | 0.240585E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.964003E+11 | 0.00 | 0.137222E+13 | 0.00 | 0.297610E+12 | 0.00 | 0.00 | 0.00 | 464853.66 | 0.00 | 0.00 | 0.00 |
September | 0.932906E+11 | 0.00 | 0.413456E+12 | 0.00 | 0.858204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.964003E+11 | 0.00 | 0.712593E+12 | 0.00 | 0.137867E+12 | 0.00 | 0.00 | 0.00 | 0.499133E+09 | 0.00 | 0.00 | 0.00 |
November | 0.932906E+11 | 0.00 | 0.971390E+12 | 0.00 | 0.181889E+12 | 0.00 | 0.00 | 0.00 | 0.133187E+10 | 0.00 | 0.00 | 0.00 |
December | 0.964003E+11 | 0.00 | 0.128755E+13 | 0.00 | 0.233517E+12 | 0.00 | 0.00 | 0.00 | 0.333130E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.113504E+13 | 0.00 | 0.102307E+14 | 0.00 | 0.203022E+13 | 0.00 | 0.00 | 0.00 | 0.179530E+11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.870712E+11 | 0.00 | 0.393656E+12 | 0.00 | 0.793819E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.964003E+11 | 0.00 | 0.137222E+13 | 0.00 | 0.297610E+12 | 0.00 | 0.00 | 0.00 | 0.425902E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.147312E+10 | 0.00 | 0.348332E+10 | 0.00 | 0.763598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.133056E+10 | 0.00 | 0.921259E+10 | 0.00 | 0.189278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147312E+10 | 0.00 | 0.182367E+11 | 0.00 | 0.353010E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.142560E+10 | 0.00 | 0.241406E+11 | 0.00 | 0.443131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147312E+10 | 0.00 | 0.693733E+10 | 0.00 | 0.141366E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142560E+10 | 0.00 | 0.136558E+11 | 0.00 | 0.285943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147312E+10 | 0.00 | 0.211315E+11 | 0.00 | 0.466285E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147312E+10 | 0.00 | 0.271860E+11 | 0.00 | 0.583770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.142560E+10 | 0.00 | 0.710478E+10 | 0.00 | 0.146128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.147312E+10 | 0.00 | 0.126645E+11 | 0.00 | 0.244468E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.142560E+10 | 0.00 | 0.178161E+11 | 0.00 | 0.337062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147312E+10 | 0.00 | 0.235520E+11 | 0.00 | 0.443543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173448E+11 | 0.00 | 0.185121E+12 | 0.00 | 0.371034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.133056E+10 | 0.00 | 0.348332E+10 | 0.00 | 0.763598E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147312E+10 | 0.00 | 0.271860E+11 | 0.00 | 0.583770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140756E+11 | 0.00 | 0.406305E+10 | 0.00 | 0.100992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127134E+11 | 0.00 | 0.556422E+11 | 0.00 | 0.117738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140756E+11 | 0.00 | 0.149442E+12 | 0.00 | 0.293365E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136215E+11 | 0.00 | 0.214868E+12 | 0.00 | 0.397721E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140756E+11 | 0.00 | 0.588507E+11 | 0.00 | 0.120963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.136215E+11 | 0.00 | 0.127352E+12 | 0.00 | 0.267448E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.140756E+11 | 0.00 | 0.200992E+12 | 0.00 | 0.443865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.140756E+11 | 0.00 | 0.258377E+12 | 0.00 | 0.555351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136215E+11 | 0.00 | 0.614094E+11 | 0.00 | 0.127391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140756E+11 | 0.00 | 0.103641E+12 | 0.00 | 0.202461E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136215E+11 | 0.00 | 0.144666E+12 | 0.00 | 0.277863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140756E+11 | 0.00 | 0.185942E+12 | 0.00 | 0.357343E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165729E+12 | 0.00 | 0.156525E+13 | 0.00 | 0.317161E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127134E+11 | 0.00 | 0.406305E+10 | 0.00 | 0.100992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.140756E+11 | 0.00 | 0.258377E+12 | 0.00 | 0.555351E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143266E+10 | 0.00 | 92812393.66 | 0.00 | 23290807.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129402E+10 | 0.00 | 0.383812E+10 | 0.00 | 0.825205E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143266E+10 | 0.00 | 0.130560E+11 | 0.00 | 0.259201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138645E+10 | 0.00 | 0.201268E+11 | 0.00 | 0.375754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143266E+10 | 0.00 | 0.525639E+10 | 0.00 | 0.109039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138645E+10 | 0.00 | 0.126437E+11 | 0.00 | 0.266451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143266E+10 | 0.00 | 0.201811E+11 | 0.00 | 0.446541E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143266E+10 | 0.00 | 0.258165E+11 | 0.00 | 0.556407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138645E+10 | 0.00 | 0.561267E+10 | 0.00 | 0.117615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143266E+10 | 0.00 | 0.855819E+10 | 0.00 | 0.169405E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138645E+10 | 0.00 | 0.122941E+11 | 0.00 | 0.239473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143266E+10 | 0.00 | 0.164664E+11 | 0.00 | 0.320418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168685E+11 | 0.00 | 0.143943E+12 | 0.00 | 0.294515E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129402E+10 | 0.00 | 92812393.66 | 0.00 | 23290807.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143266E+10 | 0.00 | 0.258165E+11 | 0.00 | 0.556407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.227037E+11 | 0.00 | 0.00 | 42340667.50 | 0.00 | 0.00 | 0.382913E+11 | 0.00 | 0.36 |
February | 0.234023E+11 | 0.00 | 0.00 | 35000137.93 | 0.00 | 0.00 | 0.310795E+11 | 0.00 | 0.35 |
March | 0.340720E+10 | 0.00 | 0.00 | 96532561.91 | 0.00 | 0.00 | 0.624069E+11 | 0.00 | 0.59 |
April | 0.383151E+09 | 0.00 | 0.00 | 0.100072E+09 | 0.00 | 0.00 | 0.660419E+11 | 0.00 | 0.76 |
May | 0.223063E+09 | 3822129.38 | 0.00 | 0.101133E+09 | 0.00 | 0.00 | 0.633590E+11 | 0.00 | 1.16 |
June | 0.135937E+09 | 0.280849E+10 | 0.00 | 90251702.93 | 39384131.49 | 0.00 | 0.407289E+11 | 0.00 | 1.31 |
July | 0.102280E+09 | 0.122965E+11 | 0.00 | 59903241.12 | 63527551.34 | 0.00 | 0.150234E+11 | 0.00 | 1.05 |
August | 95176375.84 | 0.729385E+10 | 0.00 | 93133967.76 | 33022978.04 | 0.00 | 0.286954E+11 | 0.00 | 1.27 |
September | 0.273073E+09 | 0.168662E+10 | 0.00 | 0.105704E+09 | 4320129.95 | 0.00 | 0.500605E+11 | 0.00 | 1.36 |
October | 0.411183E+09 | 0.00 | 0.00 | 0.118038E+09 | 0.00 | 0.00 | 0.723553E+11 | 0.00 | 0.95 |
November | 0.334073E+09 | 0.00 | 0.00 | 0.114093E+09 | 0.00 | 0.00 | 0.704334E+11 | 0.00 | 0.70 |
December | 0.341101E+10 | 0.00 | 0.00 | 90034299.06 | 0.00 | 0.00 | 0.619144E+11 | 0.00 | 0.41 |
Annual Sum or Average | 0.548822E+11 | 0.240892E+11 | 0.00 | 0.104624E+10 | 0.140255E+09 | 0.00 | 0.600390E+12 | 0.00 | 0.86 |
Minimum of Months | 95176375.84 | 0.00 | 0.00 | 35000137.93 | 0.00 | 0.00 | 0.150234E+11 | 0.00 | 0.35 |
Maximum of Months | 0.234023E+11 | 0.122965E+11 | 0.00 | 0.118038E+09 | 63527551.34 | 0.00 | 0.723553E+11 | 0.00 | 1.36 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131022E+11 | 0.00 | 0.00 | 27495157.64 | 0.00 | 0.00 | 0.194844E+11 | 0.00 | 0.31 |
February | 0.108923E+11 | 0.00 | 0.00 | 28123818.13 | 0.00 | 0.00 | 0.194484E+11 | 0.00 | 0.31 |
March | 0.252977E+10 | 0.00 | 0.00 | 79277840.19 | 0.00 | 0.00 | 0.468655E+11 | 0.00 | 0.48 |
April | 0.452264E+10 | 0.00 | 0.00 | 88452165.73 | 0.00 | 0.00 | 0.545296E+11 | 0.00 | 0.66 |
May | 0.341160E+10 | 1375736.74 | 0.00 | 84455805.05 | 23611757.71 | 0.00 | 0.481409E+11 | 0.00 | 0.84 |
June | 0.375404E+10 | 0.271076E+10 | 0.00 | 70268082.63 | 0.620907E+09 | 0.00 | 0.288113E+11 | 0.00 | 1.01 |
July | 0.480463E+10 | 0.104613E+11 | 0.00 | 38663339.44 | 0.268092E+10 | 0.00 | 0.972379E+10 | 0.00 | 0.93 |
August | 0.761122E+10 | 0.678507E+10 | 0.00 | 69347329.40 | 0.145277E+10 | 0.00 | 0.199297E+11 | 0.00 | 1.11 |
September | 0.387808E+10 | 0.237285E+10 | 0.00 | 72963656.58 | 71602687.57 | 0.00 | 0.338860E+11 | 0.00 | 0.93 |
October | 0.228787E+10 | 0.00 | 0.00 | 86111455.65 | 0.00 | 0.00 | 0.514316E+11 | 0.00 | 0.66 |
November | 0.128517E+10 | 0.00 | 0.00 | 81363095.84 | 1495647.05 | 0.00 | 0.498826E+11 | 0.00 | 0.50 |
December | 0.345835E+10 | 0.00 | 0.00 | 57890052.27 | 0.00 | 0.00 | 0.381643E+11 | 0.00 | 0.35 |
Annual Sum or Average | 0.615379E+11 | 0.223314E+11 | 0.00 | 0.784412E+09 | 0.485130E+10 | 0.00 | 0.420298E+12 | 0.00 | 0.68 |
Minimum of Months | 0.128517E+10 | 0.00 | 0.00 | 27495157.64 | 0.00 | 0.00 | 0.972379E+10 | 0.00 | 0.31 |
Maximum of Months | 0.131022E+11 | 0.104613E+11 | 0.00 | 88452165.73 | 0.268092E+10 | 0.00 | 0.545296E+11 | 0.00 | 1.11 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239394E+12 | 0.00 | 0.00 | 123951.93 | 0.00 | 0.716730E+10 | 0.828918E+09 | 0.00 | 0.30 |
February | 0.225039E+12 | 0.00 | 0.00 | 439124.66 | 0.00 | 0.462059E+10 | 0.170179E+10 | 0.00 | 0.30 |
March | 0.178632E+12 | 0.00 | 0.00 | 0.176197E+09 | 0.00 | 0.200700E+09 | 0.129463E+12 | 0.00 | 0.35 |
April | 0.113723E+12 | 0.00 | 0.00 | 0.309186E+09 | 0.00 | 0.00 | 0.236355E+12 | 0.00 | 0.42 |
May | 0.357943E+11 | 26095989.73 | 0.00 | 0.578317E+09 | 0.325680E+09 | 0.00 | 0.369641E+12 | 0.00 | 0.68 |
June | 0.180764E+11 | 0.208858E+11 | 0.00 | 0.563265E+09 | 0.210248E+10 | 0.00 | 0.234031E+12 | 0.00 | 0.79 |
July | 0.168303E+11 | 0.817265E+11 | 0.00 | 0.330533E+09 | 0.919753E+10 | 0.00 | 0.783705E+11 | 0.00 | 0.66 |
August | 0.169707E+11 | 0.455511E+11 | 0.00 | 0.584412E+09 | 0.441887E+10 | 0.00 | 0.163881E+12 | 0.00 | 0.76 |
September | 0.392632E+11 | 0.189620E+11 | 0.00 | 0.540190E+09 | 0.118776E+09 | 0.00 | 0.258292E+12 | 0.00 | 0.76 |
October | 0.907606E+11 | 0.00 | 0.00 | 0.372565E+09 | 2005654.30 | 0.00 | 0.263168E+12 | 0.00 | 0.46 |
November | 0.141315E+12 | 0.00 | 0.00 | 0.186817E+09 | 53760617.17 | 0.00 | 0.152489E+12 | 0.00 | 0.33 |
December | 0.231063E+12 | 0.00 | 0.00 | 8901304.50 | 0.00 | 0.266623E+10 | 0.142084E+11 | 0.00 | 0.29 |
Annual Sum or Average | 0.134686E+13 | 0.167152E+12 | 0.00 | 0.365095E+10 | 0.162191E+11 | 0.146548E+11 | 0.190243E+13 | 0.00 | 0.51 |
Minimum of Months | 0.168303E+11 | 0.00 | 0.00 | 123951.93 | 0.00 | 0.00 | 0.828918E+09 | 0.00 | 0.29 |
Maximum of Months | 0.239394E+12 | 0.817265E+11 | 0.00 | 0.584412E+09 | 0.919753E+10 | 0.716730E+10 | 0.369641E+12 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.147153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334865E+10 | 0.00 | 0.00 | 0.27 |
February | 0.142920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.300388E+10 | 0.00 | 0.00 | 0.28 |
March | 0.198491E+11 | 0.00 | 0.00 | 7135486.52 | 0.00 | 0.961210E+09 | 0.463867E+10 | 0.00 | 0.35 |
April | 0.165789E+11 | 0.00 | 0.00 | 12029840.21 | 0.00 | 0.188200E+09 | 0.118682E+11 | 0.00 | 0.37 |
May | 0.864815E+10 | 3076568.51 | 0.00 | 40451510.65 | 18496018.62 | 0.00 | 0.278495E+11 | 0.00 | 0.63 |
June | 0.259455E+10 | 0.239651E+10 | 0.00 | 51973337.55 | 0.352696E+09 | 0.00 | 0.222062E+11 | 0.00 | 0.83 |
July | 0.157815E+10 | 0.916380E+10 | 0.00 | 32086583.18 | 0.103685E+10 | 0.00 | 0.789252E+10 | 0.00 | 0.72 |
August | 0.154105E+10 | 0.520267E+10 | 0.00 | 55683439.75 | 0.551695E+09 | 0.00 | 0.153019E+11 | 0.00 | 0.78 |
September | 0.696796E+10 | 0.183428E+10 | 0.00 | 38269780.38 | 23614014.75 | 0.00 | 0.185998E+11 | 0.00 | 0.71 |
October | 0.161467E+11 | 0.00 | 0.00 | 12919412.09 | 89474.58 | 0.282572E+09 | 0.112302E+11 | 0.00 | 0.40 |
November | 0.204843E+11 | 0.00 | 726003.85 | 864630.11 | 25527257.23 | 0.552717E+09 | 0.121848E+10 | 878.10 | 0.31 |
December | 0.157449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282758E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.139141E+12 | 0.186003E+11 | 726003.85 | 0.251414E+09 | 0.200896E+10 | 0.111648E+11 | 0.120806E+12 | 878.10 | 0.50 |
Minimum of Months | 0.154105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.27 |
Maximum of Months | 0.204843E+11 | 0.916380E+10 | 726003.85 | 55683439.75 | 0.103685E+10 | 0.334865E+10 | 0.278495E+11 | 878.10 | 0.83 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121920E+10 | 0.00 | 0.00 | 0.28 |
February | 0.246181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.886195E+09 | 0.00 | 0.00 | 0.28 |
March | 0.323462E+10 | 0.00 | 0.00 | 1839166.19 | 0.00 | 0.146256E+09 | 0.113446E+10 | 0.00 | 0.37 |
April | 0.232206E+10 | 0.00 | 0.00 | 3771428.22 | 0.00 | 0.00 | 0.305843E+10 | 0.00 | 0.50 |
May | 0.128339E+10 | 0.00 | 0.00 | 7034588.87 | 3037589.89 | 0.00 | 0.442183E+10 | 0.00 | 0.78 |
June | 0.568624E+09 | 0.487384E+09 | 0.00 | 8852415.75 | 77860130.36 | 0.00 | 0.363214E+10 | 0.00 | 1.16 |
July | 0.656922E+09 | 0.181332E+10 | 0.00 | 5470593.04 | 0.329401E+09 | 0.00 | 0.131533E+10 | 0.00 | 1.11 |
August | 0.101773E+10 | 0.110529E+10 | 0.00 | 9186504.32 | 0.181493E+09 | 0.00 | 0.244021E+10 | 0.00 | 1.24 |
September | 0.115906E+10 | 0.337455E+09 | 0.00 | 5902301.03 | 9724025.66 | 0.00 | 0.289462E+10 | 0.00 | 0.88 |
October | 0.225398E+10 | 0.00 | 0.00 | 3345283.64 | 0.00 | 0.00 | 0.258786E+10 | 0.00 | 0.49 |
November | 0.306424E+10 | 0.00 | 0.00 | 1017052.98 | 187550.37 | 0.00 | 0.107116E+10 | 0.00 | 0.33 |
December | 0.335081E+10 | 0.00 | 0.00 | 11982.41 | 0.00 | 0.400531E+09 | 46977854.74 | 0.00 | 0.26 |
Annual Sum or Average | 0.238262E+11 | 0.374346E+10 | 0.00 | 46431316.47 | 0.601703E+09 | 0.265218E+10 | 0.226030E+11 | 0.00 | 0.64 |
Minimum of Months | 0.568624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.26 |
Maximum of Months | 0.335081E+10 | 0.181332E+10 | 0.00 | 9186504.32 | 0.329401E+09 | 0.121920E+10 | 0.442183E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109463E+10 | 0.00 | 0.00 | 0.39 |
February | 0.209473E+10 | 0.00 | 0.00 | 72586.77 | 0.00 | 0.926678E+09 | 37295018.18 | 0.00 | 0.39 |
March | 0.284438E+10 | 0.00 | 0.00 | 1931698.32 | 0.00 | 0.114121E+09 | 0.117582E+10 | 0.00 | 0.52 |
April | 0.222764E+10 | 0.00 | 0.00 | 4436205.99 | 0.00 | 0.00 | 0.324210E+10 | 0.00 | 0.77 |
May | 0.121236E+10 | 0.00 | 0.00 | 7674418.54 | 2769842.77 | 0.00 | 0.476314E+10 | 0.00 | 1.24 |
June | 0.635545E+09 | 0.401270E+09 | 0.00 | 7958208.84 | 49425320.45 | 0.00 | 0.365319E+10 | 0.00 | 1.62 |
July | 0.599228E+09 | 0.133744E+10 | 0.00 | 5963175.70 | 0.305617E+09 | 0.00 | 0.151118E+10 | 0.00 | 1.55 |
August | 0.109463E+10 | 0.702189E+09 | 0.00 | 7491322.46 | 0.177890E+09 | 0.00 | 0.211131E+10 | 0.00 | 1.62 |
September | 0.115332E+10 | 0.256359E+09 | 0.00 | 6198185.65 | 9035357.69 | 0.00 | 0.303132E+10 | 0.00 | 1.30 |
October | 0.208152E+10 | 0.00 | 0.00 | 3227894.06 | 0.00 | 0.00 | 0.233739E+10 | 0.00 | 0.69 |
November | 0.314753E+10 | 0.00 | 0.00 | 629774.19 | 171018.82 | 2054333.09 | 0.597123E+09 | 0.00 | 0.45 |
December | 0.268476E+10 | 0.00 | 0.00 | 6463.84 | 0.00 | 0.769927E+09 | 12062384.10 | 0.00 | 0.37 |
Annual Sum or Average | 0.220302E+11 | 0.269725E+10 | 0.00 | 45589934.36 | 0.544908E+09 | 0.290741E+10 | 0.224719E+11 | 0.00 | 0.91 |
Minimum of Months | 0.599228E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.314753E+10 | 0.133744E+10 | 0.00 | 7958208.84 | 0.305617E+09 | 0.109463E+10 | 0.476314E+10 | 0.00 | 1.62 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.245715E+10 | 0.00 | 0.00 | 869739.45 | 0.00 | 0.119659E+10 | 0.620659E+09 | 0.00 | 0.32 |
February | 0.222404E+10 | 0.00 | 0.00 | 1392761.88 | 0.00 | 0.975943E+09 | 0.923325E+09 | 0.00 | 0.34 |
March | 0.259057E+10 | 0.00 | 0.00 | 6234553.59 | 0.00 | 0.198376E+09 | 0.382365E+10 | 0.00 | 0.53 |
April | 0.239682E+10 | 0.00 | 0.00 | 7055617.67 | 0.00 | 14126569.77 | 0.534810E+10 | 0.00 | 0.75 |
May | 0.154768E+10 | 2682881.63 | 0.00 | 9426934.25 | 1196083.84 | 0.00 | 0.573291E+10 | 0.00 | 1.04 |
June | 0.785015E+09 | 0.530645E+09 | 0.00 | 9800892.61 | 81946112.49 | 0.00 | 0.397301E+10 | 0.00 | 1.33 |
July | 0.703776E+09 | 0.202477E+10 | 0.00 | 6607670.59 | 0.344757E+09 | 0.00 | 0.140960E+10 | 0.00 | 1.25 |
August | 0.111750E+10 | 0.126972E+10 | 0.00 | 12361143.46 | 0.195725E+09 | 0.00 | 0.292962E+10 | 0.00 | 1.52 |
September | 0.107882E+10 | 0.456036E+09 | 0.00 | 12621396.66 | 10153586.12 | 0.00 | 0.519107E+10 | 0.00 | 1.41 |
October | 0.192280E+10 | 0.00 | 0.00 | 8837819.39 | 0.00 | 4419837.88 | 0.579342E+10 | 0.00 | 0.85 |
November | 0.314015E+10 | 0.00 | 0.00 | 3486070.10 | 205192.29 | 23978006.19 | 0.259182E+10 | 0.00 | 0.46 |
December | 0.312018E+10 | 0.00 | 0.00 | 829026.83 | 0.00 | 0.713317E+09 | 0.612405E+09 | 0.00 | 0.30 |
Annual Sum or Average | 0.230845E+11 | 0.428386E+10 | 0.00 | 79523626.47 | 0.633983E+09 | 0.312675E+10 | 0.389496E+11 | 0.00 | 0.84 |
Minimum of Months | 0.703776E+09 | 0.00 | 0.00 | 829026.83 | 0.00 | 0.00 | 0.612405E+09 | 0.00 | 0.30 |
Maximum of Months | 0.314015E+10 | 0.202477E+10 | 0.00 | 12621396.66 | 0.344757E+09 | 0.119659E+10 | 0.579342E+10 | 0.00 | 1.52 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.374956E+10 | 0.00 | 0.00 | 23943.35 | 0.00 | 0.395716E+09 | 41200875.75 | 0.00 | 0.49 |
February | 0.337306E+10 | 0.00 | 0.00 | 424079.28 | 0.00 | 0.139636E+09 | 0.384026E+09 | 0.00 | 0.50 |
March | 0.161791E+10 | 0.00 | 0.00 | 6804131.89 | 0.00 | 170265.46 | 0.468462E+10 | 0.00 | 0.78 |
April | 0.557354E+09 | 0.00 | 0.00 | 13090093.34 | 0.00 | 0.00 | 0.850521E+10 | 0.00 | 1.34 |
May | 0.772567E+09 | 978322.16 | 0.00 | 11134687.48 | 2670006.48 | 0.00 | 0.651028E+10 | 0.00 | 1.58 |
June | 0.406589E+09 | 0.581355E+09 | 0.00 | 14712945.98 | 71089646.02 | 0.00 | 0.504806E+10 | 0.00 | 2.31 |
July | 0.455743E+09 | 0.233016E+10 | 0.00 | 9991275.07 | 0.206582E+09 | 0.00 | 0.193798E+10 | 0.00 | 2.14 |
August | 0.595973E+09 | 0.152384E+10 | 0.00 | 17153864.34 | 36614713.20 | 0.00 | 0.406447E+10 | 0.00 | 2.57 |
September | 0.702484E+09 | 0.343403E+09 | 0.00 | 9528087.26 | 7772735.67 | 0.00 | 0.418888E+10 | 0.00 | 1.63 |
October | 0.110786E+10 | 0.00 | 0.00 | 7068136.46 | 0.00 | 0.00 | 0.517302E+10 | 0.00 | 1.02 |
November | 0.139813E+10 | 84533.05 | 0.00 | 4767721.21 | 153826.58 | 0.00 | 0.399093E+10 | 0.00 | 0.67 |
December | 0.288465E+10 | 0.00 | 0.00 | 1530433.98 | 0.00 | 1594847.23 | 0.156660E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.176219E+11 | 0.477982E+10 | 0.00 | 96229399.65 | 0.324883E+09 | 0.537117E+09 | 0.460953E+11 | 0.00 | 1.30 |
Minimum of Months | 0.406589E+09 | 0.00 | 0.00 | 23943.35 | 0.00 | 0.00 | 41200875.75 | 0.00 | 0.48 |
Maximum of Months | 0.374956E+10 | 0.233016E+10 | 0.00 | 17153864.34 | 0.206582E+09 | 0.395716E+09 | 0.850521E+10 | 0.00 | 2.57 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.185756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.317730E+11 | 0.00 | 0.00 | 0.31 |
February | 0.252075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293044E+11 | 0.00 | 0.00 | 0.32 |
March | 0.192090E+11 | 0.00 | 0.00 | 4644058.94 | 0.00 | 0.163266E+11 | 0.202231E+10 | 0.00 | 0.34 |
April | 0.310835E+11 | 0.00 | 0.00 | 2989888.36 | 0.00 | 0.354240E+10 | 0.265957E+10 | 0.00 | 0.36 |
May | 0.198170E+11 | 194806.64 | 0.00 | 35810249.74 | 41907160.45 | 0.00 | 0.226588E+11 | 0.00 | 0.59 |
June | 0.617329E+10 | 0.392692E+10 | 0.00 | 63031114.64 | 0.264357E+09 | 0.00 | 0.245378E+11 | 0.00 | 0.89 |
July | 0.249767E+10 | 0.146627E+11 | 0.00 | 43322789.91 | 0.110327E+10 | 0.00 | 0.100436E+11 | 0.00 | 0.82 |
August | 0.522787E+10 | 0.769759E+10 | 0.00 | 66646111.38 | 0.561607E+09 | 0.00 | 0.165978E+11 | 0.00 | 0.85 |
September | 0.160488E+11 | 0.264879E+10 | 0.00 | 32970454.77 | 21216862.51 | 0.00 | 0.149515E+11 | 0.00 | 0.69 |
October | 0.304667E+11 | 0.00 | 0.00 | 5387451.87 | 251927.23 | 0.208080E+10 | 0.444092E+10 | 0.00 | 0.38 |
November | 0.240473E+11 | 0.00 | 384637.66 | 0.00 | 6360872.47 | 0.107070E+11 | 0.00 | 7280.52 | 0.31 |
December | 0.400992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292657E+11 | 0.00 | 0.00 | 0.31 |
Annual Sum or Average | 0.162959E+12 | 0.289362E+11 | 384637.66 | 0.254802E+09 | 0.199897E+10 | 0.123000E+12 | 0.979124E+11 | 7280.52 | 0.52 |
Minimum of Months | 0.185756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.31 |
Maximum of Months | 0.310835E+11 | 0.146627E+11 | 384637.66 | 66646111.38 | 0.110327E+10 | 0.317730E+11 | 0.245378E+11 | 7280.52 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.274429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285784E+11 | 0.00 | 0.00 | 0.45 |
February | 0.575278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.237056E+11 | 0.00 | 0.00 | 0.46 |
March | 0.233657E+11 | 0.00 | 0.00 | 6310987.46 | 0.00 | 0.100006E+11 | 0.299354E+10 | 0.00 | 0.51 |
April | 0.226420E+11 | 0.00 | 0.00 | 24526766.56 | 0.00 | 0.204546E+10 | 0.179160E+11 | 0.00 | 0.63 |
May | 0.158829E+11 | 191073.64 | 0.00 | 59444400.04 | 41104110.76 | 0.00 | 0.365877E+11 | 0.00 | 1.11 |
June | 0.543354E+10 | 0.358612E+10 | 0.00 | 73310710.89 | 0.134478E+09 | 0.00 | 0.334679E+11 | 0.00 | 1.48 |
July | 0.215702E+10 | 0.125108E+11 | 0.00 | 63201035.51 | 0.118227E+10 | 0.00 | 0.154121E+11 | 0.00 | 1.36 |
August | 0.491104E+10 | 0.594493E+10 | 0.00 | 75740534.73 | 0.578984E+09 | 0.00 | 0.204417E+11 | 0.00 | 1.37 |
September | 0.141311E+11 | 0.220401E+10 | 0.00 | 50017169.11 | 86086788.03 | 0.00 | 0.231361E+11 | 0.00 | 1.19 |
October | 0.273049E+11 | 0.00 | 0.00 | 11046965.73 | 247099.66 | 0.164814E+10 | 0.815037E+10 | 0.00 | 0.60 |
November | 0.243325E+11 | 0.00 | 368658.43 | 77981.91 | 6253142.54 | 0.948091E+10 | 0.221236E+09 | 1588.72 | 0.47 |
December | 0.390116E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273719E+11 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.152559E+12 | 0.242461E+11 | 368658.43 | 0.363677E+09 | 0.202942E+10 | 0.102831E+12 | 0.158327E+12 | 1588.72 | 0.84 |
Minimum of Months | 0.215702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.273049E+11 | 0.125108E+11 | 368658.43 | 75740534.73 | 0.118227E+10 | 0.285784E+11 | 0.365877E+11 | 1588.72 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103725E+11 | 0.00 | 0.00 | 4275565.75 | 0.00 | 0.237057E+11 | 0.281909E+10 | 0.00 | 0.34 |
February | 0.112505E+11 | 0.00 | 0.00 | 7576249.25 | 0.00 | 0.197939E+11 | 0.550017E+10 | 0.00 | 0.36 |
March | 0.225809E+11 | 0.00 | 0.00 | 40974440.98 | 0.00 | 0.704182E+10 | 0.219156E+11 | 0.00 | 0.48 |
April | 0.234754E+11 | 0.00 | 0.00 | 43640144.47 | 0.00 | 0.264792E+10 | 0.318941E+11 | 0.00 | 0.59 |
May | 0.180718E+11 | 32424251.59 | 0.00 | 74391422.02 | 22451782.76 | 0.00 | 0.437954E+11 | 0.00 | 0.90 |
June | 0.788517E+10 | 0.441274E+10 | 0.00 | 80523358.40 | 0.290006E+09 | 0.00 | 0.308481E+11 | 0.00 | 1.11 |
July | 0.336725E+10 | 0.170742E+11 | 0.00 | 56852475.09 | 0.112818E+10 | 0.00 | 0.113523E+11 | 0.00 | 0.98 |
August | 0.527763E+10 | 0.957667E+10 | 0.00 | 0.107887E+09 | 0.565462E+09 | 0.00 | 0.235454E+11 | 0.00 | 1.18 |
September | 0.119417E+11 | 0.401779E+10 | 0.00 | 0.118850E+09 | 18541892.83 | 0.00 | 0.439673E+11 | 0.00 | 1.30 |
October | 0.207789E+11 | 276879.92 | 0.00 | 67497684.65 | 0.00 | 0.107500E+10 | 0.418963E+11 | 0.00 | 0.74 |
November | 0.238642E+11 | 0.00 | 0.00 | 21105258.14 | 7421635.71 | 0.748123E+10 | 0.146483E+11 | 0.00 | 0.41 |
December | 0.106381E+11 | 0.00 | 0.00 | 3081833.99 | 0.00 | 0.240312E+11 | 0.176602E+10 | 0.00 | 0.34 |
Annual Sum or Average | 0.169504E+12 | 0.351141E+11 | 0.00 | 0.626656E+09 | 0.203207E+10 | 0.857768E+11 | 0.273948E+12 | 0.00 | 0.73 |
Minimum of Months | 0.336725E+10 | 0.00 | 0.00 | 3081833.99 | 0.00 | 0.00 | 0.176602E+10 | 0.00 | 0.34 |
Maximum of Months | 0.238642E+11 | 0.170742E+11 | 0.00 | 0.118850E+09 | 0.112818E+10 | 0.240312E+11 | 0.439673E+11 | 0.00 | 1.30 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.595509E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267702E+11 | 0.00 | 0.00 | 0.48 |
February | 0.908281E+10 | 0.00 | 0.00 | 151686.24 | 0.00 | 0.214262E+11 | 0.197006E+09 | 0.00 | 0.48 |
March | 0.259449E+11 | 0.00 | 0.00 | 8195645.58 | 0.00 | 0.817446E+10 | 0.460402E+10 | 0.00 | 0.54 |
April | 0.270792E+11 | 0.00 | 0.00 | 21683975.66 | 0.00 | 0.173643E+10 | 0.163087E+11 | 0.00 | 0.69 |
May | 0.178658E+11 | 339453.15 | 0.00 | 61124925.90 | 43400840.00 | 0.00 | 0.348380E+11 | 0.00 | 1.17 |
June | 0.620045E+10 | 0.401177E+10 | 0.00 | 86523882.52 | 0.237416E+09 | 0.00 | 0.297135E+11 | 0.00 | 1.59 |
July | 0.262181E+10 | 0.140143E+11 | 0.00 | 55121631.32 | 0.721709E+09 | 0.00 | 0.985304E+10 | 0.00 | 1.30 |
August | 0.460957E+10 | 0.722248E+10 | 0.00 | 81041189.82 | 0.432981E+09 | 0.00 | 0.174261E+11 | 0.00 | 1.38 |
September | 0.147432E+11 | 0.229416E+10 | 0.00 | 51833513.95 | 92019103.16 | 0.00 | 0.202104E+11 | 0.00 | 1.19 |
October | 0.295663E+11 | 0.00 | 0.00 | 12500614.43 | 260906.57 | 0.121005E+10 | 0.930672E+10 | 0.00 | 0.66 |
November | 0.278703E+11 | 0.00 | 0.00 | 865316.29 | 6993477.57 | 0.709193E+10 | 0.993339E+09 | 0.00 | 0.50 |
December | 0.847487E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241930E+11 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.180014E+12 | 0.275431E+11 | 0.00 | 0.379042E+09 | 0.153478E+10 | 0.906022E+11 | 0.143451E+12 | 0.00 | 0.87 |
Minimum of Months | 0.262181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.295663E+11 | 0.140143E+11 | 0.00 | 86523882.52 | 0.721709E+09 | 0.267702E+11 | 0.348380E+11 | 0.00 | 1.59 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 42139940.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288850E+10 | 0.00 | 0.00 | 0.35 |
February | 45777578.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276202E+10 | 0.00 | 0.00 | 0.36 |
March | 0.135106E+10 | 0.00 | 0.00 | 368395.49 | 0.00 | 0.214790E+10 | 0.150911E+09 | 0.00 | 0.39 |
April | 0.275381E+10 | 0.00 | 0.00 | 125255.93 | 0.00 | 0.943584E+09 | 0.151970E+09 | 0.00 | 0.40 |
May | 0.264778E+10 | 0.00 | 0.00 | 2445495.77 | 2804522.48 | 72538989.53 | 0.163289E+10 | 0.00 | 0.60 |
June | 0.871631E+09 | 0.442080E+09 | 0.00 | 5859089.06 | 51975337.83 | 283516.58 | 0.227480E+10 | 0.00 | 0.95 |
July | 0.357011E+09 | 0.161653E+10 | 0.00 | 4018195.00 | 0.146998E+09 | 0.00 | 0.956955E+09 | 0.00 | 0.90 |
August | 0.718967E+09 | 0.863644E+09 | 0.00 | 6352658.05 | 84318318.52 | 0.00 | 0.148026E+10 | 0.00 | 0.90 |
September | 0.201328E+10 | 0.239290E+09 | 0.00 | 2336996.17 | 23299770.33 | 46247639.93 | 0.102823E+10 | 0.00 | 0.70 |
October | 0.265887E+10 | 0.00 | 0.00 | 127557.06 | 12657.44 | 0.903842E+09 | 0.152617E+09 | 0.00 | 0.42 |
November | 0.108254E+10 | 0.00 | 3381756.09 | 0.00 | 400809.23 | 0.212624E+10 | 0.00 | 64597.12 | 0.36 |
December | 0.165848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280082E+10 | 0.00 | 0.00 | 0.35 |
Annual Sum or Average | 0.147087E+11 | 0.316154E+10 | 3381756.09 | 21633642.54 | 0.309809E+09 | 0.146920E+11 | 0.782863E+10 | 64597.12 | 0.56 |
Minimum of Months | 42139940.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.35 |
Maximum of Months | 0.275381E+10 | 0.161653E+10 | 3381756.09 | 6352658.05 | 0.146998E+09 | 0.288850E+10 | 0.227480E+10 | 64597.12 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38069891.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226055E+10 | 0.00 | 0.00 | 0.43 |
February | 0.274136E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193771E+10 | 0.00 | 0.00 | 0.44 |
March | 0.161598E+10 | 0.00 | 0.00 | 480386.48 | 0.00 | 0.126233E+10 | 0.179810E+09 | 0.00 | 0.52 |
April | 0.185036E+10 | 0.00 | 0.00 | 1647006.26 | 0.00 | 0.516698E+09 | 0.128691E+10 | 0.00 | 0.59 |
May | 0.150929E+10 | 31836.80 | 0.00 | 5182015.20 | 2378943.54 | 31740244.50 | 0.333787E+10 | 0.00 | 1.05 |
June | 0.518489E+09 | 0.413082E+09 | 0.00 | 7441819.97 | 21638979.92 | 0.00 | 0.334230E+10 | 0.00 | 1.55 |
July | 0.207378E+09 | 0.142643E+10 | 0.00 | 6297637.73 | 0.132422E+09 | 0.00 | 0.158792E+10 | 0.00 | 1.49 |
August | 0.467693E+09 | 0.675023E+09 | 0.00 | 7912623.42 | 73651813.43 | 0.00 | 0.201768E+10 | 0.00 | 1.44 |
September | 0.128581E+10 | 0.213087E+09 | 0.00 | 4351977.18 | 15277914.91 | 30095034.40 | 0.209131E+10 | 0.00 | 1.15 |
October | 0.229514E+10 | 0.00 | 0.00 | 508732.63 | 10880.39 | 0.516175E+09 | 0.407401E+09 | 0.00 | 0.57 |
November | 0.109060E+10 | 0.00 | 2981430.63 | 0.00 | 306230.34 | 0.163912E+10 | 0.00 | 32504.04 | 0.47 |
December | 0.139670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221922E+10 | 0.00 | 0.00 | 0.43 |
Annual Sum or Average | 0.112926E+11 | 0.272765E+10 | 2981430.63 | 33822198.88 | 0.245687E+09 | 0.104136E+11 | 0.142512E+11 | 32504.04 | 0.84 |
Minimum of Months | 38069891.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 |
Maximum of Months | 0.229514E+10 | 0.142643E+10 | 2981430.63 | 7912623.42 | 0.132422E+09 | 0.226055E+10 | 0.334230E+10 | 32504.04 | 1.55 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.520565E+09 | 0.00 | 0.00 | 156701.54 | 0.00 | 0.228547E+10 | 87641448.49 | 0.00 | 0.34 |
February | 0.663844E+09 | 0.00 | 0.00 | 442787.38 | 0.00 | 0.195693E+10 | 0.275687E+09 | 0.00 | 0.36 |
March | 0.178343E+10 | 0.00 | 0.00 | 2872687.31 | 0.00 | 0.104873E+10 | 0.149807E+10 | 0.00 | 0.48 |
April | 0.206488E+10 | 0.00 | 0.00 | 3255767.14 | 0.00 | 0.635897E+09 | 0.259181E+10 | 0.00 | 0.56 |
May | 0.201213E+10 | 1712479.14 | 0.00 | 6351291.67 | 1374580.30 | 77104501.61 | 0.393422E+10 | 0.00 | 0.86 |
June | 0.876063E+09 | 0.514431E+09 | 0.00 | 8005549.24 | 41551889.42 | 1867674.53 | 0.313231E+10 | 0.00 | 1.17 |
July | 0.406038E+09 | 0.193654E+10 | 0.00 | 5868156.58 | 0.147514E+09 | 0.00 | 0.119739E+10 | 0.00 | 1.10 |
August | 0.644894E+09 | 0.108935E+10 | 0.00 | 11194600.77 | 79042622.59 | 0.00 | 0.232818E+10 | 0.00 | 1.25 |
September | 0.123659E+10 | 0.377009E+09 | 0.00 | 10404817.01 | 13307678.78 | 38763449.95 | 0.411172E+10 | 0.00 | 1.27 |
October | 0.208344E+10 | 17588.37 | 0.00 | 4678362.02 | 1071.68 | 0.449223E+09 | 0.293859E+10 | 0.00 | 0.68 |
November | 0.150512E+10 | 0.00 | 2047087.52 | 1067433.32 | 1889730.67 | 0.137542E+10 | 0.770577E+09 | 19240.23 | 0.40 |
December | 0.446172E+09 | 0.00 | 0.00 | 110394.93 | 0.00 | 0.242123E+10 | 70513570.73 | 0.00 | 0.35 |
Annual Sum or Average | 0.142432E+11 | 0.391906E+10 | 2047087.52 | 54408548.89 | 0.284681E+09 | 0.102906E+11 | 0.229367E+11 | 19240.23 | 0.74 |
Minimum of Months | 0.406038E+09 | 0.00 | 0.00 | 110394.93 | 0.00 | 0.00 | 70513570.73 | 0.00 | 0.34 |
Maximum of Months | 0.208344E+10 | 0.193654E+10 | 2047087.52 | 11194600.77 | 0.147514E+09 | 0.242123E+10 | 0.411172E+10 | 19240.23 | 1.27 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230881E+10 | 0.00 | 0.00 | 0.47 |
February | 0.442615E+09 | 0.00 | 0.00 | 10439.07 | 0.00 | 0.194336E+10 | 12444246.38 | 0.00 | 0.47 |
March | 0.193585E+10 | 0.00 | 0.00 | 626604.14 | 0.00 | 0.111192E+10 | 0.354670E+09 | 0.00 | 0.57 |
April | 0.236117E+10 | 0.00 | 0.00 | 1702354.55 | 0.00 | 0.439406E+09 | 0.144329E+10 | 0.00 | 0.69 |
May | 0.204796E+10 | 35505.07 | 0.00 | 5288179.65 | 2653048.41 | 15999337.68 | 0.320818E+10 | 0.00 | 1.15 |
June | 0.731026E+09 | 0.455267E+09 | 0.00 | 9337684.70 | 43202021.32 | 0.00 | 0.299046E+10 | 0.00 | 1.68 |
July | 0.318978E+09 | 0.155677E+10 | 0.00 | 5602761.03 | 0.100008E+09 | 0.00 | 0.100227E+10 | 0.00 | 1.42 |
August | 0.547254E+09 | 0.826131E+09 | 0.00 | 8508521.67 | 58258626.59 | 0.00 | 0.166982E+10 | 0.00 | 1.46 |
September | 0.156077E+10 | 0.210885E+09 | 0.00 | 4367692.47 | 20056993.37 | 33536810.73 | 0.180946E+10 | 0.00 | 1.19 |
October | 0.268597E+10 | 0.00 | 0.00 | 863596.13 | 12134.04 | 0.387170E+09 | 0.617790E+09 | 0.00 | 0.66 |
November | 0.166542E+10 | 0.00 | 1737936.98 | 15331.31 | 1813852.64 | 0.132622E+10 | 36338936.20 | 8650.16 | 0.52 |
December | 0.338528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222211E+10 | 0.00 | 0.00 | 0.47 |
Annual Sum or Average | 0.148353E+11 | 0.304908E+10 | 1737936.98 | 36323164.71 | 0.226005E+09 | 0.978853E+10 | 0.131447E+11 | 8650.16 | 0.90 |
Minimum of Months | 0.199790E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.47 |
Maximum of Months | 0.268597E+10 | 0.155677E+10 | 1737936.98 | 9337684.70 | 0.100008E+09 | 0.230881E+10 | 0.320818E+10 | 8650.16 | 1.68 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2111227.86 | 0.00 | 0.00 | 0.829225E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 6458912.74 | 0.00 | 0.00 | 0.752885E+09 | 0.00 | 0.28 |
March | 0.00 | 296283.92 | 0.00 | 13541253.43 | 0.00 | 0.00 | 0.663072E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16831016.78 | 0.00 | 0.00 | 0.504661E+09 | 0.00 | 0.29 |
May | 0.00 | 176531.75 | 0.00 | 3883920.63 | 0.00 | 0.00 | 0.362531E+09 | 0.00 | 0.29 |
June | 0.00 | 56748366.58 | 0.00 | 5515630.35 | 0.00 | 0.00 | 0.161444E+09 | 0.00 | 0.30 |
July | 0.00 | 0.160797E+09 | 0.00 | 3070439.56 | 0.00 | 0.00 | 28936799.47 | 0.00 | 0.28 |
August | 0.00 | 82342255.41 | 0.00 | 10058621.54 | 0.00 | 0.00 | 76220361.54 | 0.00 | 0.31 |
September | 0.00 | 22382085.65 | 0.00 | 3030848.99 | 0.00 | 0.00 | 0.198697E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 8025696.19 | 0.00 | 0.00 | 0.445527E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11800251.00 | 0.00 | 0.00 | 0.565334E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 15843634.20 | 0.00 | 0.00 | 0.762326E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.322743E+09 | 0.00 | 0.100171E+09 | 0.00 | 0.00 | 0.535086E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2111227.86 | 0.00 | 0.00 | 28936799.47 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 0.160797E+09 | 0.00 | 16831016.78 | 0.00 | 0.00 | 0.829225E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.406022E+10 | 0.00 | 0.00 | 3760966.40 | 0.00 | 0.00 | 0.413592E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 44061399.08 | 0.00 | 0.00 | 0.754922E+10 | 0.00 | 0.28 |
March | 0.00 | 2794000.12 | 0.00 | 0.114328E+09 | 0.00 | 0.00 | 0.665224E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.151982E+09 | 0.00 | 0.00 | 0.506110E+10 | 0.00 | 0.29 |
May | 0.00 | 1581230.99 | 0.00 | 32887897.50 | 0.00 | 0.00 | 0.363550E+10 | 0.00 | 0.29 |
June | 0.00 | 0.562915E+09 | 0.00 | 51528237.85 | 0.00 | 0.00 | 0.161673E+10 | 0.00 | 0.30 |
July | 0.00 | 0.160451E+10 | 0.00 | 29163250.90 | 0.00 | 0.00 | 0.290293E+09 | 0.00 | 0.28 |
August | 0.00 | 0.822777E+09 | 0.00 | 95701051.81 | 0.00 | 0.00 | 0.764502E+09 | 0.00 | 0.31 |
September | 0.00 | 0.215309E+09 | 0.00 | 25917133.86 | 0.00 | 0.00 | 0.200154E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 67390412.59 | 0.00 | 0.00 | 0.446749E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 98713639.11 | 0.00 | 0.00 | 0.566947E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.130782E+09 | 0.00 | 0.00 | 0.764920E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.406022E+10 | 0.320988E+10 | 0.00 | 0.846216E+09 | 0.00 | 0.00 | 0.494932E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3760966.40 | 0.00 | 0.00 | 0.290293E+09 | 0.00 | 0.28 |
Maximum of Months | 0.406022E+10 | 0.160451E+10 | 0.00 | 0.151982E+09 | 0.00 | 0.00 | 0.764920E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.652151E+09 | 0.00 | 0.00 | 104499.77 | 0.00 | 0.00 | 0.148323E+09 | 0.00 | 0.28 |
February | 1010052.52 | 0.00 | 0.00 | 3732149.84 | 0.00 | 0.00 | 0.754478E+09 | 0.00 | 0.28 |
March | 0.00 | 270026.80 | 0.00 | 10501098.67 | 0.00 | 0.00 | 0.666246E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 14470845.60 | 0.00 | 0.00 | 0.506929E+09 | 0.00 | 0.29 |
May | 0.00 | 163400.91 | 0.00 | 2945985.88 | 0.00 | 0.00 | 0.364436E+09 | 0.00 | 0.29 |
June | 0.00 | 56311276.42 | 0.00 | 5097668.14 | 0.00 | 0.00 | 0.161919E+09 | 0.00 | 0.30 |
July | 0.00 | 0.160324E+09 | 0.00 | 2908448.55 | 0.00 | 0.00 | 29110425.56 | 0.00 | 0.28 |
August | 0.00 | 82130505.10 | 0.00 | 9544487.04 | 0.00 | 0.00 | 76679515.22 | 0.00 | 0.31 |
September | 1542154.91 | 21448799.92 | 0.00 | 2325509.62 | 0.00 | 0.00 | 0.199940E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5861414.79 | 0.00 | 0.00 | 0.448097E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 8802774.67 | 0.00 | 0.00 | 0.568187E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12187439.69 | 0.00 | 0.00 | 0.765883E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.654703E+09 | 0.320648E+09 | 0.00 | 78482322.25 | 0.00 | 0.00 | 0.469023E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 104499.77 | 0.00 | 0.00 | 29110425.56 | 0.00 | 0.28 |
Maximum of Months | 0.652151E+09 | 0.160324E+09 | 0.00 | 14470845.60 | 0.00 | 0.00 | 0.765883E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.206844E+09 | 0.00 | 0.00 | 0.217285E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.396499E+09 | 0.00 | 0.00 | 0.196783E+11 | 0.00 | 0.32 |
March | 0.00 | 7371435.03 | 0.00 | 0.701486E+09 | 0.00 | 0.00 | 0.167720E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.844537E+09 | 0.00 | 0.00 | 0.115519E+11 | 0.00 | 0.33 |
May | 0.00 | 6794683.63 | 0.00 | 0.211972E+09 | 0.00 | 0.00 | 0.829142E+10 | 0.00 | 0.33 |
June | 0.00 | 0.133713E+10 | 0.00 | 0.270635E+09 | 0.00 | 0.00 | 0.345129E+10 | 0.00 | 0.34 |
July | 0.00 | 0.359131E+10 | 0.00 | 0.145370E+09 | 0.00 | 0.00 | 0.558900E+09 | 0.00 | 0.32 |
August | 0.00 | 0.153567E+10 | 0.00 | 0.513869E+09 | 0.00 | 0.00 | 0.152493E+10 | 0.00 | 0.34 |
September | 0.00 | 0.611640E+09 | 0.00 | 0.163112E+09 | 0.00 | 0.00 | 0.415540E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.423267E+09 | 0.00 | 0.00 | 0.991036E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.612673E+09 | 0.00 | 0.00 | 0.131183E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.832071E+09 | 0.00 | 0.00 | 0.191324E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.708991E+10 | 0.00 | 0.532234E+10 | 0.00 | 0.00 | 0.129874E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.145370E+09 | 0.00 | 0.00 | 0.558900E+09 | 0.00 | 0.32 |
Maximum of Months | 0.00 | 0.359131E+10 | 0.00 | 0.844537E+09 | 0.00 | 0.00 | 0.217285E+11 | 0.00 | 0.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.270004E+12 | 0.521451E+11 | 0.00 | 0.150674E+13 | 0.568835E+12 |
February | 0.408499E+12 | 0.548244E+11 | 0.00 | 0.139392E+13 | 0.844509E+12 |
March | 0.607582E+12 | 0.345729E+11 | 0.00 | 0.172599E+13 | 0.135054E+13 |
April | 0.729469E+12 | 0.279542E+11 | 0.00 | 0.188287E+13 | 0.166212E+13 |
May | 0.896577E+12 | 0.162050E+11 | 0.00 | 0.190534E+13 | 0.793737E+12 |
June | 0.961533E+12 | 0.704305E+10 | 0.00 | 0.109797E+13 | 0.196890E+13 |
July | 0.892186E+12 | -326534983.5 | 0.00 | 0.217825E+12 | 0.309922E+13 |
August | 0.764406E+12 | 0.319646E+10 | 0.00 | 0.806166E+12 | 0.320357E+13 |
September | 0.583141E+12 | 0.931548E+10 | 0.00 | 0.154661E+13 | 0.120135E+13 |
October | 0.394240E+12 | 0.214632E+11 | 0.00 | 0.193406E+13 | 0.100009E+13 |
November | 0.215930E+12 | 0.295959E+11 | 0.00 | 0.170027E+13 | 0.126906E+13 |
December | 0.243654E+12 | 0.554084E+11 | 0.00 | 0.157563E+13 | 0.170188E+13 |
Annual Sum or Average | 0.696722E+13 | 0.311398E+12 | 0.00 | 0.172934E+14 | 0.186638E+14 |
Minimum of Months | 0.215930E+12 | -326534983.5 | 0.00 | 0.217825E+12 | 0.568835E+12 |