Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190

Simulation Timestamp: 2023-10-16 09:04:13


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 30138.49 650.65 650.65
Net Site Energy 30138.49 650.65 650.65
Total Source Energy 93041.94 2008.66 2008.66
Net Source Energy 93041.94 2008.66 2008.66


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 497.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3987.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2746.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 447.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2410.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 773.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1437.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7185.64
Humidification 8.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery 44.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 657.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 28983.11 1155.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9469.14
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 497.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3987.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2746.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 447.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 59.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2410.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 773.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1437.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7185.64
Humidification General 8.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery General 44.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 657.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 497.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3987.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2746.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 447.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2410.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 773.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1437.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7185.64
Humidification Unassigned 8.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3.33
Heat Recovery Unassigned 44.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 657.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 186.03 24.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.20
Other 370.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 625.71 24.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.20


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 186.03 24.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.20
Other 370.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 625.71 24.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.20


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 28983.111 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 28983.111 100.00
     
Total On-Site and Utility Electric Sources 28983.111 100.00
Total Electricity End Uses 28983.111 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 807.25 68.44
Air to Air Heat Recovery for Heating 372.22 31.56
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 1179.47 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 9469.14 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 9469.14 100.00
Total Water End Uses 9469.14 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 37.83
Time Setpoint Not Met During Occupied Cooling 539.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5929.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
RunPeriod RUNPERIOD 1
Weather File Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Latitude [deg] 33.63
Longitude [deg] -84.4
Elevation [m] 308.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 7.6202 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 7.6202 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 7.6202 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 7.6202 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 7.6202 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 7.6202 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 7.6202 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 7.6202 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 12.5114 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 12.5114 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 12.5114 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 7.6202 18.58 484.4232  
Total 46320.38             7.6661 9.29 17.8789  
Conditioned Total 46320.38             7.6661 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.3561 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 03-AUG-15:50 13-FEB-07:10 - - - - - - - - - - 14-APR-12:39
Heating 0.00 1211803.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 427008.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 83146.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 219917.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 65597.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 90905.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 29163.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1920628.32 1240967.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1211803.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 427008.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3711.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 219917.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 65597.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 90905.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 29163.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 539.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 12626.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8696.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1417.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6062.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7633.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 2450.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 4551.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 28.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 141.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 712.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 91789.51 1252.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 11.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 272.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 164.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 52.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 98.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1981.62 27.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 11.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 272.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 164.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 52.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 98.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 15.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1981.62 27.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.40
DATACENTER_BOT_ZN_6 DIRECT AIR 0.481319
DATACENTER_MID_ZN_6 DIRECT AIR 4.58
DATACENTER_TOP_ZN_6 DIRECT AIR 0.463804
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 22.03
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.79 0.328756 0.329000 1.90 0.876683 0.500000 0.001159 0.000162 1.90 12.80 0.008000
CORE_MID VAV BOX COMPONENT 54.51 0.348923 0.342000 18.64 0.930461 0.500000 0.001092 0.004035 18.64 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.39 0.352869 0.354000 1.91 0.940984 0.500000 0.001080 0.000766 2.70 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.948229 0.251860 0.252000 0.238954 0.671626 0.500000 0.001513 0.000122 0.429468 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.925142 0.166358 0.200000 0.185028 0.443622 0.500000 0.002290 0.000084 0.295666 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.09 0.218660 0.219000 0.239197 0.583093 0.500000 0.001742 0.000137 0.484494 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.20 0.128216 0.200000 0.240072 0.341908 0.500000 0.002972 0.000065 0.240072 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.90 0.268320 0.263000 2.34 0.715519 0.500000 0.001420 0.002058 7.28 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 9.52 0.161725 0.200000 1.90 0.431267 0.500000 0.002356 0.001350 4.78 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 10.32 0.231513 0.227000 2.34 0.617367 0.500000 0.001646 0.002035 7.20 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 10.09 0.152595 0.200000 2.02 0.406920 0.500000 0.002497 0.001304 4.61 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.02 0.233120 0.234000 0.239722 0.621653 0.500000 0.001634 0.000266 0.940328 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.977836 0.157394 0.200000 0.195567 0.419716 0.500000 0.002421 0.000174 0.614373 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.16 0.206084 0.207000 0.239887 0.549558 0.500000 0.001849 0.000263 0.930660 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.10 0.139996 0.200000 0.219870 0.373323 0.500000 0.002722 0.000171 0.604058 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 18478.09 0.000162 372.50
CORE_MID VAV BOX REHEAT COIL 461273.88 0.004035 11002.51
CORE_TOP VAV BOX REHEAT COIL 87569.98 0.000766 2311.76
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 13894.74 0.000122 366.60
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 9564.50 0.000084 252.33
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 15671.90 0.000137 413.45
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 7436.53 0.000065 192.48
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 235288.57 0.002058 6204.29
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 154368.28 0.001350 4070.45
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 232645.67 0.002035 6134.66
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 149044.56 0.001304 3930.16
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 30372.89 0.000266 800.75
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 19843.93 0.000174 523.16
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 30061.01 0.000263 792.53
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 19511.04 0.000171 514.39
VAV_BOT WITH REHEAT HEATING COIL 56773.45 0.000497 926.29
VAV_MID WITH REHEAT HEATING COIL 563769.03 0.004932 9137.48
VAV_TOP WITH REHEAT HEATING COIL 54413.71 0.000476 891.59
CAV_BAS HEATING COIL 261003.99 0.002283 5785.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 4.98 2.81 9.95 2.81 9.19 9.19 0.300000 0.305549 9.19
VAV_MID WITH REHEAT 46.67 27.25 93.33 36.13 85.42 85.42 0.300000 0.423010 85.42
VAV_TOP WITH REHEAT 4.83 2.80 9.65 5.79 9.21 9.21 0.300000 0.629118 9.21
CAV_BAS 5.40 5.40 5.40 5.40 5.40 5.40 1.00 1.00 5.40
AIRLOOP DATACENTER BASEMENT 22.03 22.03 22.03 22.03 22.03 22.03 1.00 0.999989 22.03
AIRLOOP DATACENTER BOT 0.481319 0.481319 0.481319 0.481319 0.481319 0.481319 1.00 1.00 0.481319
AIRLOOP DATACENTER MID 4.58 4.58 4.58 4.58 4.58 4.58 1.00 1.00 4.58
AIRLOOP DATACENTER TOP 0.463804 0.463804 0.463804 0.463804 0.463804 0.463804 1.00 1.00 0.463804
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.19  
VAV_MID WITH REHEAT_OA_CONTROLLER 85.42  
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.21  
CAV_BAS_OA_CONTROLLER 5.40 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 22.03 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.481319 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.58 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.463804 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 27.02 6.67 10.88 0.010532 0.008500 230972.63 0.009826 9.19
VAV_MID WITH REHEAT COOLING COIL 27.37 6.67 10.88 0.010797 0.008500 2250186.46 0.095728 85.42
VAV_TOP WITH REHEAT COOLING COIL 26.88 6.67 10.88 0.010504 0.008500 229252.62 0.009753 9.21
CAV_BAS COOLING COIL 25.99 6.67 11.37 0.010333 0.008500 122895.78 0.005228 5.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.19
VAV_MID WITH REHEAT FAN 85.42
VAV_TOP WITH REHEAT FAN 9.21
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.009826 0.000048
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000497  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.095728 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.004932  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.009753 0.000049
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000476  
CAV_BAS_COOLC_CONTROLLER 0.005228 0.000091
CAV_BAS_HEATC_CONTROLLER 0.002283  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 22.03 436298.38 302337.30 0.010685
AIRLOOP DATACENTER BOT COOLING COIL 0.481319 9489.77 6583.54 0.000232
AIRLOOP DATACENTER MID COOLING COIL 4.58 90405.53 62654.68 0.002214
AIRLOOP DATACENTER TOP COOLING COIL 0.463804 9156.24 6347.68 0.000224
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 22.03 22.03 22.03 22.03 436298.38 436298.38 18278.08 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.481319 0.481319 0.481319 0.481319 9489.77 9489.77 844.37 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.58 4.58 4.58 4.58 90405.53 90405.53 8443.71 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.463804 0.463804 0.463804 0.463804 9156.24 9156.24 844.37 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 22.03
AIRLOOP DATACENTER BOT SUPPLY FAN 0.481319
AIRLOOP DATACENTER MID SUPPLY FAN 4.58
AIRLOOP DATACENTER TOP SUPPLY FAN 0.463804
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 22.03 436298.38 0.010685
AIRLOOP DATACENTER BOT HEATING COIL 0.481319 9489.77 0.000232
AIRLOOP DATACENTER MID HEATING COIL 4.58 90405.53 0.002214
AIRLOOP DATACENTER TOP HEATING COIL 0.463804 9156.24 0.000224
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 18278.08
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 844.37
AIRLOOP DATACENTER MID_SUPPHEATCOIL 8443.71
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 844.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000153 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.120535 24837.89  
HEATSYS1 PUMP 0.021180 6378.44 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.120535 14.46
HEATSYS1 0.021180 2.54
COOLSYS1_SUPPLY 0.120535 14.46
SINGLE WATER PLANT LOOP 0.013356 1.60
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.120535 0.120535 505947.77 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2420985.77 2420985.77 0.021180
CENTRAL BOILER 550135.59 539255.35 0.013356
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.120535 17196.11
PLANT CIRC PUMP 0.013356 3406.34
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.120535 0.060535 1426431.71 1433207.92 0.070924
COOLSYS1 CHILLER2 0.120535 0.060535 1426431.71 1433207.92 0.070924
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013356 139666.47 59026.20 69833.23 7879.72 21390.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.141848 17.02
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.141848 42721.62
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 56.86 1700458.72 11.37 212557.34
TOWERWATERSYS COOLTOWER 2 56.86 1700458.72 11.37 212557.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.073667
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 11.90 7.70 4.00 7.90 13.80 17.20 20.80 24.80 26.10 26.50 22.50


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190 33.63 -84.43 -5.00 308.00 97679 1.1610


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 16.60 22.50 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 7.620 4.842 0.000 0.000 0.000 0.000 12.462 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 7.620 484.423 0.000 0.000 0.000 0.000 492.043 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 21179.739 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 21179.739
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5971.780 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5971.780
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.498 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.416 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.867 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5004
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.5391
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3683
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.14091426E-14 0.48101397E-16 -0.12271849E-09 -0.49605034E-17
51 8 0.18065296E-07 0.19413100E-12 0.33649602E-03 -0.20540863E-09
52 7 -0.11004888E-01 0.10546945E-07 -0.21303752E-01 0.12512956E-03
53 6 0.37174157 0.37425545E-05 0.44335749 -0.43515980E-02
54 5 -4.8625044 0.14213861E-03 -4.2200868 0.59116134E-01
55 4 31.551289 0.11806248E-02 20.574731 -0.40285082
56 3 -108.13650 0.26081321E-02 -53.912227 1.4705586
57 2 194.06739 0.14847903E-02 76.306869 -2.8520668
58 1 -170.03224 0.16027253E-03 -54.802483 2.7257428
59 0 57.057407 0.92345258E-06 15.636386  
60 9 0.11726792E-14 0.46876770E-16 -0.12664795E-09 -0.40425794E-17
61 8 0.18621286E-07 0.18477046E-12 0.34269676E-03 -0.21173044E-09
62 7 -0.11191167E-01 0.99660246E-08 -0.21572393E-01 0.12724763E-03
63 6 0.37680492 0.35261678E-05 0.44770143 -0.44112820E-02
64 5 -4.9119389 0.13358806E-03 -4.2535898 0.59729078E-01
65 4 31.770087 0.11071467E-02 20.706000 -0.40575564
66 3 -108.60241 0.24410452E-02 -54.171883 1.4772891
67 2 194.52961 0.13872791E-02 76.544434 -2.8594062
68 1 -170.20315 0.14950961E-03 -54.870487 2.7287383
69 0 57.057407 0.85997654E-06 15.624277  
70 9 0.98458787E-15 0.55454857E-16 -0.10492535E-09 -0.15601002E-17
71 8 0.15540463E-07 0.23311053E-12 0.30746206E-03 -0.17670042E-09
72 7 -0.10129638E-01 0.13130386E-07 -0.20040359E-01 0.11517765E-03
73 6 0.34794661 0.47273228E-05 0.42286390 -0.40711180E-02
74 5 -4.6301347 0.18177508E-03 -4.0616887 0.56235001E-01
75 4 30.522476 0.15264987E-02 19.953355 -0.38919251
76 3 -105.94476 0.34047073E-02 -52.682811 1.4388992
77 2 191.89184 0.19546755E-02 75.183526 -2.8175246
78 1 -169.22736 0.21263380E-03 -54.483619 2.7116363
79 0 57.057407 0.12355163E-05 15.695393  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.4644_SHGC_EAST_0.25 35 1 VerySmooth 2.640 2.640 1.000 0.251    
2 WINDOW_U_0.4644_SHGC_SOUTH_0.25 36 1 VerySmooth 2.640 2.640 1.000 0.251    
3 WINDOW_U_0.4644_SHGC_WEST_0.25 37 1 VerySmooth 2.640 2.640 1.000 0.251    
4 WINDOW_U_0.4644_SHGC_NORTH_0.25 38 1 VerySmooth 2.640 2.640 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   2.48111E-002 0.16139 0.61554 0.61554 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.11929 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8576E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8588E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0627E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0636E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1965E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1972E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8841E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9574E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0842E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1455E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2138E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2647E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.9514E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.5821E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.9420E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.9097E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.1838E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3924E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8923E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9988E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0932E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.1909E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2216E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2944E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8576E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8591E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.0626E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0639E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1965E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1974E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9893E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.1535E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9090E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0865E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6660E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7416E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6649E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7784E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5899E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.6705E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6669E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5111E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.9489E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0027E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.8579E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8975E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6437E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6612E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2519E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2531E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0708E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0718E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.5534E-004
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.5613E-004
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2802E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3489E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0943E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1498E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.7508E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0180E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9763E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1285E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5382E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.6054E-003
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5549E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 6.1673E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2777E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3470E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0909E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1437E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.6906E-004
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.9954E-004
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2518E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2530E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0707E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0716E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.5522E-004
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.5579E-004
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3645E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4222E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1390E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1805E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1397E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1547E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5180E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3326E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1920E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.1281E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6222E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.1005E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3925E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4998E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1750E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2820E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1598E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2218E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.0715E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.7955E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 8.9227E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.2135E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.5812E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.3388E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.1810E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.4404E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.0992E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.3184E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.1418E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.1001E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.3737E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.6608E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8955E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.3196E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.9079E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.0403E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.9382E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8591E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.5823E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.6090E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0182E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5792E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.0678E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.8033E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 8.9195E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.2230E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.5838E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.3458E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.1798E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.4428E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.0990E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.3211E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.1435E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1038E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.3708E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.6614E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8936E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.3202E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.9089E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.0418E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.9362E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8605E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.5810E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.6103E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0194E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5817E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 72376.91016 72376.91016 5.40416 5.40416 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:30:00 -6.30000 2.29779E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 77484.33880 77484.33880 5.78558 5.78558 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 730249.40786 730249.40786 54.51188 54.51188 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 280293.32590 280293.32590 12.26174 12.26174 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 72210.48984 72210.48984 5.39022 5.39022 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 27.37000 1.44605E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 61327.70771 61327.70771 2.70325 2.70325 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12582.42667 12582.42667 0.94823 0.94823 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40000 1.44733E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 9731.54397 9731.54397 0.42947 0.42947 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12276.13224 12276.13224 0.92514 0.92514 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 30.52083 1.44662E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 6698.01016 6698.01016 0.29567 0.29567 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 14493.18402 14493.18402 1.09222 1.09222 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 34.32083 1.44731E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 10973.99237 10973.99237 0.48449 0.48449 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 15928.24050 15928.24050 1.20036 1.20036 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 32.91167 1.44705E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 5110.99486 5110.99486 0.22530 0.22530 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 118098.87079 118098.87079 8.90060 8.90060 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 34.40000 1.44733E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 164701.69641 164701.69641 7.28144 7.28144 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 126271.21839 126271.21839 9.51647 9.51647 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 30.79000 1.44667E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 108056.77091 108056.77091 4.77739 4.77739 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 136878.10554 136878.10554 10.31589 10.31589 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 34.40000 1.44733E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 162853.90780 162853.90780 7.19951 7.19951 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 133826.49675 133826.49675 10.08585 10.08585 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 104334.41755 104334.41755 4.61240 4.61240 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13592.84453 13592.84453 1.02445 1.02445 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 34.11500 1.44727E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 21257.23883 21257.23883 0.94033 0.94033 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 12974.34000 12974.34000 0.97784 0.97784 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 31.26500 1.44675E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 13888.28767 13888.28767 0.61437 0.61437 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 15376.41776 15376.41776 1.15887 1.15887 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 34.40000 1.44733E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 21039.16912 21039.16912 0.93066 0.93066 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 14586.72872 14586.72872 1.09935 1.09935 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 32.75333 1.44703E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 13655.49406 13655.49406 0.60406 0.60406 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -6.30000 2.29779E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8098.75523 8098.75523 0.48132 0.48132 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 24.96333 1.44561E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 -6.30000 2.29779E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 77010.23484 77010.23484 4.57682 4.57682 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 24.96333 1.44561E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -6.30000 2.29779E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7803.10174 7803.10174 0.46380 0.46380 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 30.69500 1.44665E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -6.30000 2.29779E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 370593.60221 370593.60221 22.02697 22.02697 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 25.75500 1.44575E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 11:20:00 -6.30000 2.29779E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 144922.81 9.18579 9.18579 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 55990.24 2.51276 2.51276 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1330812.82 85.41766 85.41766 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 564677.14 36.13248 36.13248 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00
5 VAV_TOP WITH REHEAT Cooling Sensible 150370.60 9.20761 9.20761 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 56437.02 5.79267 5.79267 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00
7 CAV_BAS Cooling Sensible 76318.34 5.40416 5.40416 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 64825.70 1.20016 1.20016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 367298.38 22.02723 22.02723 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 18278.08 0.33839 0.33839 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 7978.79 0.48132 0.48132 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 844.37 1.56323E-002 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 75984.22 4.57682 4.57682 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 8443.71 0.15632 0.15632 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7749.86 0.46380 0.46380 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 844.37 1.56323E-002 1.56323E-002 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.40416
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.78558
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32876
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32900
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.90345
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.87668
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.15891E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.61654E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.90345
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 18478.09236
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.61654E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 372.50384
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 54.51188
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.34892
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34200
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 18.64306
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.93046
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.09193E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.03543E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 18.64306
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 461273.87960
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.03543E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 11002.51035
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.39022
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35287
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35400
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.90814
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.94098
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07972E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.66100E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.70325
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 87569.97557
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.66100E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2311.76452
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.94823
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25186
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25200
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23895
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.67163
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.51275E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.21557E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.42947
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13894.74067
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.21557E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 366.59553
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.92514
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16636
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18503
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44362
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.29024E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.36744E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.29567
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 9564.50200
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.36744E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 252.33184
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.09222
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21866
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21900
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23920
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.58309
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.74243E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.37105E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.48449
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 15671.90154
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.37105E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 413.44606
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.20036
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12822
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24007
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34191
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.97156E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.50580E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24007
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7436.53277
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.50580E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 192.47961
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.90060
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26832
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26300
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.34086
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.71552
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.41995E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.05841E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.28144
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 235288.57361
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.05841E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6204.29450
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.51647
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16173
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.90329
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43127
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.35585E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.35048E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.77739
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 154368.28094
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.35048E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4070.44775
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.31589
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23151
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22700
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.34171
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61737
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.64570E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.03529E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 7.19951
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 232645.67414
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.03529E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 6134.65769
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.08585
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15260
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.01717
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40692
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.49680E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.30391E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.61240
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 149044.55852
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.30391E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3930.15904
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.02445
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23312
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23400
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23972
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.62165
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.63435E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.65715E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.94033
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30372.89293
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.65715E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 800.74996
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.97784
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15739
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19557
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.41972
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.42068E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.73603E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.61437
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19843.92747
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.73603E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 523.15857
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.15887
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20608
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20700
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23989
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54956
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.84876E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.62987E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.93066
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 30061.01215
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.62987E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 792.53230
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.09935
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14000
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.21987
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37332
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.72150E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.70691E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.60406
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19511.03770
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.70691E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 514.38551
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48132
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.57682
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46380
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 22.02697
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.97577
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.80671
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.95153
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.80671
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.18579
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.18579
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30555
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 46.66534
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 27.24609
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 93.33069
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 36.13248
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 85.41766
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 85.41766
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.42301
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.82537
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.80319
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.65074
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 5.79267
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.20761
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.20761
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.62912
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.40416
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.40416
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.40416
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.40416
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.40416
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.40416
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 22.02697
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 22.02697
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 22.02697
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 22.02697
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 22.02723
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 22.02723
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48132
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48132
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48132
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.48132
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.48132
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.48132
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.57682
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.57682
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.57682
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.57682
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.57682
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.57682
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46380
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46380
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46380
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.46380
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.46380
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.46380
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.18579
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 85.41766
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.20761
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.40416
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 22.02723
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.48132
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.57682
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.46380
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.18579
289 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.02084
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.87981
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.05320E-002
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 230972.62604
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.82611E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.18579
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 56773.44800
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.96679E-004
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 926.28982
301 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.18579
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.82611E-003
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.84618E-005
304 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.96679E-004
305 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 85.41766
306 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.37049
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.88073
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.07966E-002
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2250186.46230
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.57281E-002
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 85.41766
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 563769.03233
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.93210E-003
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 9137.47730
318 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 85.41766
319 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.57281E-002
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.97440E-006
321 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.93210E-003
322 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.20761
323 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.88281
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.87972
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.05042E-002
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 229252.61627
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.75294E-003
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.20761
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 54413.71261
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 4.76035E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 891.59246
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.20761
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.75294E-003
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.88253E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 4.76035E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.40416
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.98630
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.37376
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.03333E-002
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 122895.78035
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.22827E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.40416
349 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 261003.99450
350 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.28338E-003
351 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5785.84414
352 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.40416
353 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.22827E-003
354 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.10799E-005
355 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.28338E-003
356 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 22.02723
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 22.02723
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 436298.37890
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 302337.29795
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.06849E-002
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 22.02723
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 22.02723
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 22.02723
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 22.02723
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 436298.37890
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 436298.37890
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 18278.07505
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
370 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 22.02723
371 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 22.02723
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 436298.37890
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.06849E-002
374 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 18278.07505
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.52644E-004
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
377 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
379 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48132
380 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.48132
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9489.77430
383 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6583.53871
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.32404E-004
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48132
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48132
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48132
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48132
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9489.77430
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9489.77430
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 844.37135
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
393 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48132
394 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.48132
395 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9489.77430
396 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.32404E-004
397 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 844.37135
398 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.57682
399 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.57682
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 90405.53194
402 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 62654.67724
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.21403E-003
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.57682
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.57682
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.57682
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.57682
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 90405.53194
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 90405.53194
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 8443.71345
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
412 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.57682
413 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.57682
414 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 90405.53194
415 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.21403E-003
416 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 8443.71345
417 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46380
418 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46380
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9156.24098
421 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6347.67668
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.24236E-004
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46380
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46380
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46380
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46380
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9156.24098
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9156.24098
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 844.37135
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
431 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46380
432 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46380
433 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9156.24098
434 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.24236E-004
435 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 844.37135
436 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12054
437 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 24837.88881
438 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12054
439 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 14.46425
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12054
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12054
442 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 505947.76517
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
444 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.11798E-002
445 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.54158
446 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.11798E-002
447 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 6378.43759
448 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
449 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2420985.76940
450 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2420985.77000
451 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.11798E-002
452 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12054
453 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 14.46425
454 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.12054
455 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 17196.10827
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12054
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.05350E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1426431.70794
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1433207.92000
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.09241E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12054
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.05350E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1426431.70794
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1433207.92000
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.09241E-002
466 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.33556E-002
467 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.60267
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.33556E-002
469 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3406.34195
470 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.33556E-002
471 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
472 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 59026.19910
473 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
474 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
475 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21390.83763
476 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 550135.58707
477 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 539255.35000
478 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.33556E-002
479 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
480 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
482 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
483 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
484 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.14185
485 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 17.02180
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.14185
487 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 42721.61968
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 56.85852
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1700458.71722
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.37170
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 212557.33965
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 56.85852
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1700458.71722
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.37170
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 212557.33965
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.36675E-002
497 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.36675E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 17521.32
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 437012.89
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 82987.54
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 13166.22
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 9062.92
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 14849.95
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 7042.71
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 222928.56
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 146258.65
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 220424.85
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 141215.20
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 28776.36
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 18800.80
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 28480.91
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 18485.43
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 42917.65
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 420372.18
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 41501.39
19 Coil:Heating:Water CAV_BAS HEATING COIL 205812.60


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 247720.95 164280.55 83440.40 0.66 26483.04 268.61
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2343856.42 1546003.40 797853.02 0.66 251074.62 2546.54
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 247451.53 164284.48 83167.05 0.66 26458.54 268.36
4 Coil:Cooling:Water CAV_BAS COOLING COIL 138284.01 93131.45 45152.57 0.67 14419.58 146.25


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_NORTH_0.25 N/A 2.640 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_EAST_0.25 N/A 2.640 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_SOUTH_0.25 N/A 2.640 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.4644_SHGC_WEST_0.25 N/A 2.640 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.498 1.223   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.416 1.168   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.867 1.459   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.3010197898 0.2580865324 Pass Pass 0.7757193818 1.4989231053 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 1.8634935652E-003 1.8045042157E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 2.4453903356E-003 2.4136006737E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 3.1218081064E-002 3.4200681891E-002 Pass Pass 0.1330447212 0.3386822489 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.1909914146E-002 2.3560039052E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.2100649685E-002 2.4144667774E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 2.1855205730E-002 2.2997240936E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 2.2345106818E-002 2.3696076424E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.7247927253E-002 2.8378565024E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 2.8007953297E-002 2.9123113463E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 2.8473383671E-002 2.9888362158E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 2.8924030337E-002 2.9712641325E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 9.4117022431E-002 0.1437402480 Pass Pass 3.9282839045 21.1988230948 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 9.2852491754E-002 0.1403275951 Pass Pass 3.4020290639 18.3217463079 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 8.2365846066E-002 0.1183145522 Pass Pass 3.5291879771 19.0550650492 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 4.0781418162E-002 4.7594724190E-002 Pass Pass 5.4693309770 31.5450913001 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.7105058033E-003 4.2214984294E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.0889806222E-003 6.4938741549E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.1379871536E-002 4.4632921828E-002 Pass Pass 0.1327260842 0.3331257167 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 6.9017611488E-006 8.8203366949E-006 Pass Pass 1.9326527656E-003 1.3669267193E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 5.3222457640E-003 4.7963045273E-003 Pass Pass 5.5292200157E-003 6.8066014292E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 1.4655800049E-002 1.0661847632E-002 Pass Pass 3.4357259063E-003 3.8014618832E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 8.2756271278E-006 1.0712973222E-005 Pass Pass 3.4520228069E-005 1.1010900647E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5635.25 112.64 0.00 11294.30 24701.90 41744.07



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB -6.30 0.00 -6.30 Wetbulb [C] 5.30 320.00
ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 34.40 9.50 23.50 Wetbulb [C] 4.00 300.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 90.00 25      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.223 1.498 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.223 1.498 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.168 1.416 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.168 1.416 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.459 1.867 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.459 1.867 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.4644_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.4644_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.4644_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.640 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.4644_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.640 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.640 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.640 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.4644_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.4644_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.4644_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.640 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.4644_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.640 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.640 0.251 0.251                      
North Total or Average             1043.06 2.640 0.251 0.251                      
Non-North Total or Average             2433.80 2.640 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 7.6202 2779.43 21179.74 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 177.74
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 7.6202 24961.20 190208.95 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 1596.24
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 31.09 0.0000 Y 13.94
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.85 0.0000 Y 8.91
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.66 0.0000 Y 13.74
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.99 0.0000 Y 8.95
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 7.6202 3134.13 23882.63 LightsWired LTG_SCH_OFFICE 45.89 168.00 31.13 0.0000 Y 139.57
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.86 0.0000 Y 89.17
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 7.6202 3134.20 23883.15 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.69 0.0000 Y 137.58
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 31.00 0.0000 Y 89.57
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 31.13 0.0000 Y 13.96
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.86 0.0000 Y 8.92
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.69 0.0000 Y 13.76
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 31.00 0.0000 Y 8.96
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 7.6202 783.68 5971.78 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 50.12
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 12.5114 362.03 4529.48 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 46.40
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
Interior Lighting Total       7.6661 46320.38 355094.67               857.38


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   41.77 41.77 78.20
EXTERIOR_LIGHTS_B 27638.03 AstronomicalClock -   83.77 71.17 369.23
Exterior Lighting Total 37611.08           447.43



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2826791.71          
HEATSYS1 BOILER Boiler:HotWater 2420985.77 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1433207.92 6.28 1371766.01 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1433207.92 6.28 1371766.01 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 539255.35 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1700458.72          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1700458.72          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 230972.63 247720.95 164280.55 83440.40 0.66 - 26483.04 268.61
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2250186.46 2343856.42 1546003.40 797853.02 0.66 - 251074.62 2546.54
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 229252.62 247451.53 164284.48 83167.05 0.66 - 26458.54 268.36
CAV_BAS COOLING COIL Coil:Cooling:Water 122895.78 138284.01 93131.45 45152.57 0.67 - 14419.58 146.25
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   436298.38 302337.30 133961.08 0.69 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9489.77 6583.54 2906.24 0.69 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   90405.53 62654.68 27750.85 0.69 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9156.24 6347.68 2808.56 0.69 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 18478.09 17521.32 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 461273.88 437012.89 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 87569.98 82987.54 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 13894.74 13166.22 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 9564.50 9062.92 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 15671.90 14849.95 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 7436.53 7042.71 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 235288.57 222928.56 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 154368.28 146258.65 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 232645.67 220424.85 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 149044.56 141215.20 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 30372.89 28776.36 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 19843.93 18800.80 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 30061.01 28480.91 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 19511.04 18485.43 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 56773.45 42917.65 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 563769.03 420372.18 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 54413.71 41501.39 -
CAV_BAS HEATING COIL Coil:Heating:Water 261003.99 205812.60 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   436298.38 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9489.77 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   90405.53 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9156.24 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   18278.08 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   844.37 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   8443.71 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   844.37 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.19 20977.85 2283.73 1.00 1.12 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 85.42 195070.68 2283.73 1.00 1.07 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.21 21027.67 2283.73 1.00 1.12 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.40 9163.58 1695.65 1.00 1.16 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 22.03 36328.34 1649.25 1.00 1.14 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 539.13 1120.11 1.00 1.62 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.58 5126.53 1120.11 1.00 1.16 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 519.51 1120.11 1.00 1.64 General ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.120535 24837.89 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.021180 6378.44 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.120535 17196.11 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013356 3406.34 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.141848 42721.62 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 72376.91 72376.91 26.04 5.404 5.404 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00898 27.37 0.01446 1.200 0.00
CORE_BOTTOM 77484.34 77484.34 31.04 5.786 5.786 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00890 27.37 0.01446 1.078 0.00
CORE_MID 730249.41 730249.41 292.55 54.512 54.512 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00893 27.37 0.01446 10.778 0.00
CORE_TOP 72210.49 72210.49 28.93 5.390 5.390 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00893 27.37 0.01446 1.078 0.00
PERIMETER_BOT_ZN_3 12582.43 12582.43 40.15 0.948 0.948 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00893 34.40 0.01447 0.135 0.00
PERIMETER_BOT_ZN_2 12276.13 12276.13 60.78 0.925 0.925 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 24.00 24.00 0.00879 30.52 0.01447 0.087 0.00
PERIMETER_BOT_ZN_1 14493.18 14493.18 46.24 1.092 1.092 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:50:00 24.00 24.00 0.00888 34.32 0.01447 0.135 0.00
PERIMETER_BOT_ZN_4 15928.24 15928.24 78.86 1.200 1.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 24.00 24.00 0.00873 32.91 0.01447 0.087 0.00
PERIMETER_MID_ZN_3 118098.87 118098.87 376.82 8.901 8.901 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 24.00 24.00 0.00914 34.40 0.01447 1.353 0.00
PERIMETER_MID_ZN_2 126271.22 126271.22 625.18 9.516 9.516 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:00:00 24.00 24.00 0.00890 30.79 0.01447 0.872 0.00
PERIMETER_MID_ZN_1 136878.11 136878.11 436.72 10.316 10.316 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00905 34.40 0.01447 1.353 0.00
PERIMETER_MID_ZN_4 133826.50 133826.50 662.59 10.086 10.086 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00888 32.75 0.01447 0.872 0.00
PERIMETER_TOP_ZN_3 13592.84 13592.84 43.37 1.024 1.024 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 24.00 24.00 0.00912 34.12 0.01447 0.135 0.00
PERIMETER_TOP_ZN_2 12974.34 12974.34 64.24 0.978 0.978 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 24.00 24.00 0.00894 31.26 0.01447 0.087 0.00
PERIMETER_TOP_ZN_1 15376.42 15376.42 49.06 1.159 1.159 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00905 34.40 0.01447 0.135 0.00
PERIMETER_TOP_ZN_4 14586.73 14586.73 72.22 1.099 1.099 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 24.00 24.00 0.00889 32.75 0.01447 0.087 0.00
DATACENTER_BOT_ZN_6 8098.76 8098.76 223.71 0.481 0.481 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00850 24.96 0.01446 0.016 0.00
DATACENTER_MID_ZN_6 77010.23 77010.23 2127.19 4.577 4.577 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 27.00 27.00 0.00850 24.96 0.01446 0.156 0.00
DATACENTER_TOP_ZN_6 7803.10 7803.10 215.54 0.464 0.464 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 27.00 27.00 0.00859 30.70 0.01447 0.016 0.00
DATACENTER_BASEMENT_ZN_6 370593.60 370593.60 472.89 22.027 22.027 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 25.75 0.01446 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:30:00 21.00 23.45 0.00230 -6.30 0.00230 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 17.60 21.02 0.00230 -6.30 0.00230 1.078 0.00
CORE_MID 280293.33 280293.33 112.29 12.262 12.262 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 10.778 0.00
CORE_TOP 61327.71 61327.71 24.57 2.703 2.703 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -6.30 0.00230 1.078 0.00
PERIMETER_BOT_ZN_3 9731.54 9731.54 31.05 0.429 0.429 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00736 -6.30 0.00230 0.135 0.00
PERIMETER_BOT_ZN_2 6698.01 6698.01 33.16 0.296 0.296 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00742 -6.30 0.00230 0.087 0.00
PERIMETER_BOT_ZN_1 10973.99 10973.99 35.01 0.484 0.484 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00749 -6.30 0.00230 0.135 0.00
PERIMETER_BOT_ZN_4 5110.99 5110.99 25.31 0.225 0.225 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00701 -6.30 0.00230 0.087 0.00
PERIMETER_MID_ZN_3 164701.70 164701.70 525.51 7.281 7.281 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00741 -6.30 0.00230 1.353 0.00
PERIMETER_MID_ZN_2 108056.77 108056.77 535.00 4.777 4.777 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00740 -6.30 0.00230 0.872 0.00
PERIMETER_MID_ZN_1 162853.91 162853.91 519.60 7.200 7.200 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00741 -6.30 0.00230 1.353 0.00
PERIMETER_MID_ZN_4 104334.42 104334.42 516.57 4.612 4.612 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00738 -6.30 0.00230 0.872 0.00
PERIMETER_TOP_ZN_3 21257.24 21257.24 67.83 0.940 0.940 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 0.135 0.00
PERIMETER_TOP_ZN_2 13888.29 13888.29 68.76 0.614 0.614 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00743 -6.30 0.00230 0.087 0.00
PERIMETER_TOP_ZN_1 21039.17 21039.17 67.13 0.931 0.931 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00744 -6.30 0.00230 0.135 0.00
PERIMETER_TOP_ZN_4 13655.49 13655.49 67.61 0.604 0.604 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00742 -6.30 0.00230 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:20:00 18.00 25.42 0.00797 -6.30 0.00230 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.89 0.00296 -6.30 0.00230 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 21.00 0.00276 -6.30 0.00230 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 11:20:00 18.00 27.00 0.00850 -6.30 0.00230 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.19 9.19 2.51 2.51 9.1858 2.8067 9.1858 0.3055 0.3000
VAV_MID WITH REHEAT 85.42 85.42 36.13 36.13 85.4177 36.1325 85.4177 0.4230 0.3000
VAV_TOP WITH REHEAT 9.21 9.21 5.79 5.79 9.2076 5.7927 9.2076 0.6291 0.3000
CAV_BAS 5.40 5.40 1.20 1.20 5.4042 5.4042 5.4042 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 22.03 22.03 0.34 0.34 22.0272 22.0270 22.0272 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.48 0.48 0.02 0.02 0.4813 0.4813 0.4813 1.0000 1.0000
AIRLOOP DATACENTER MID 4.58 4.58 0.16 0.16 4.5768 4.5768 4.5768 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.46 0.46 0.02 0.02 0.4638 0.4638 0.4638 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 18478.092 18478.092 1.903454 0.00016165 372.504 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 18478.09 18478.09 1.903454 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 0.00 0.00 18546.23 18546.23
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 461273.880 461273.880 18.643063 0.00403543 11002.510 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 461273.88 461273.88 18.643063 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 280293.33 0.00 462774.27 462774.27
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 87569.976 87569.976 2.703253 0.00076610 2311.765 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 87569.98 87569.98 2.703253 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00800000 49.8624 61327.71 0.00 87873.91 87873.91
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 13894.741 13894.741 0.429468 0.00012156 366.596 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13894.74 13894.74 0.429468 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00736137 45.9345 9731.54 0.00 13941.44 13941.44
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 9564.502 9564.502 0.295666 0.00008367 252.332 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 9564.50 9564.50 0.295666 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00741999 46.2957 6698.01 0.00 9596.53 9596.53
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 15671.902 15671.902 0.484494 0.00013710 413.446 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 15671.90 15671.90 0.484494 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00749196 46.7388 10973.99 0.00 15724.30 15724.30
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 7436.533 7436.533 0.240072 0.00006506 192.480 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7436.53 7436.53 0.240072 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00700546 43.7400 5110.99 0.00 7459.33 7459.33
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 235288.574 235288.574 7.281439 0.00205841 6204.295 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 235288.57 235288.57 7.281439 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00741190 46.2477 164701.70 0.00 236054.14 236054.14
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 154368.281 154368.281 4.777390 0.00135048 4070.448 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 154368.28 154368.28 4.777390 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00740474 46.2037 108056.77 0.00 154870.05 154870.05
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 232645.674 232645.674 7.199512 0.00203529 6134.658 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 232645.67 232645.67 7.199512 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00740515 46.2061 162853.91 0.00 233403.03 233403.03
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 149044.559 149044.559 4.612402 0.00130391 3930.159 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 149044.56 149044.56 4.612402 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00738309 46.0703 104334.42 0.00 149529.67 149529.67
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 30372.893 30372.893 0.940328 0.00026572 800.750 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30372.89 30372.89 0.940328 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00744127 46.4300 21257.24 0.00 30470.64 30470.64
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 19843.927 19843.927 0.614373 0.00017360 523.159 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19843.93 19843.93 0.614373 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00743113 46.3676 13888.29 0.00 19907.75 19907.75
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 30061.012 30061.012 0.930660 0.00026299 792.532 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 30061.01 30061.01 0.930660 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00743593 46.3970 21039.17 0.00 30157.79 30157.79
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 19511.038 19511.038 0.604058 0.00017069 514.386 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19511.04 19511.04 0.604058 12.80 11.27 0.00800000 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 0.0000 21.00 0.00742233 46.3134 13655.49 0.00 19573.81 19573.81
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 230972.626 -999.000 9.185795 0.00982611 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 230972.63 175248.55 9.185795 27.02 18.67 0.01053197 10.88 10.88 0.00850000 34.40 0.01447326 23.54 27.6317 24.00 0.00891774 46.2565 115915.59 0.00 236440.52 170886.50
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 56773.448 56773.448 2.755738 0.00049668 926.290 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 56773.45 56773.45 2.755738 -4.86 -4.99 0.00252608 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 92.1056 21.02 0.00593773 37.0845 32514.54 0.00 51914.27 51914.27
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2250186.462 -999.000 85.417658 0.09572813 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2250186.46 1664614.59 85.417658 27.37 18.98 0.01079662 10.88 10.88 0.00850000 34.40 0.01447326 23.54 29.7151 24.00 0.00903284 46.8458 1038871.18 0.00 2302053.75 1627764.24
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 563769.032 563769.032 25.625297 0.00493210 9137.477 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 563769.03 563769.03 25.625297 -6.06 -6.06 0.00234662 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 99.0504 19.62 0.00715767 48.6357 428469.23 0.00 508441.72 508441.72
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 229252.616 -999.000 9.207607 0.00975294 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 229252.62 174161.20 9.207607 26.88 18.60 0.01050418 10.88 10.88 0.00850000 34.40 0.01447326 23.54 27.5662 24.00 0.00898110 46.5815 121447.83 0.00 234711.83 169754.55
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 54413.713 54413.713 2.762282 0.00047603 891.592 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 54413.71 54413.71 2.762282 -4.09 -4.20 0.00271154 12.80 11.27 0.00800000 -6.30 0.00229779 -6.30 91.8874 18.28 0.00735331 54.3330 53426.68 0.00 50205.06 50205.06
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 122895.780 -999.000 5.404155 0.00522827 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 122895.78 94063.04 5.404155 25.99 18.18 0.01033334 11.37 11.18 0.00850000 32.21 0.01446927 22.96 22.2080 24.00 0.00901352 46.7460 65832.44 0.00 125972.37 92086.46
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 261003.995 261003.995 5.404155 0.00228338 5785.844 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 261003.99 261003.99 5.404155 -1.40 -3.29 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 22.2080 23.55 0.00229779 12.3755 0.00 0.00 217406.40 217406.40
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 436298.379 302337.298 22.027227 0.01068492 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 404426.92 396847.39 -999.0 28.56 17.68 0.00863364 12.80 11.77 0.00850000 34.40 0.01447326 23.54 -999.0000 27.00 0.00854241 37.1030 370098.95 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9489.774 6583.539 0.481319 0.00023240 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 8789.02 8439.42 -999.0 28.10 17.65 0.00878240 12.80 11.77 0.00850000 30.70 0.01446650 22.54 -999.0000 27.00 0.00859006 37.3049 8035.63 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90405.532 62654.677 4.576818 0.00221403 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 83755.55 80264.91 -999.0 28.10 17.66 0.00879647 12.80 11.77 0.00850000 30.52 0.01446618 22.49 -999.0000 27.00 0.00859468 37.3249 76525.14 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9156.241 6347.677 0.463804 0.00022424 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8481.95 8135.03 -999.0 28.10 17.65 0.00879077 12.80 11.77 0.00850000 30.70 0.01446650 22.54 -999.0000 27.00 0.00859280 37.3168 7803.10 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 436298.379 436298.379 22.027227 0.01068492 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 436298.38 436298.38 22.027227 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 1.5362 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9489.774 9489.774 0.481319 0.00023240 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9489.77 9489.77 0.481319 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.2478 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90405.532 90405.532 4.576818 0.00221403 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 90405.53 90405.53 4.576818 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.4155 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9156.241 9156.241 0.463804 0.00022424 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9156.24 9156.24 0.463804 -6.30 -6.30 0.00229779 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3705 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 18278.075 18278.075 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 18278.08 18278.08 22.027227 -0.10 -0.10 0.00840472 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 1.5362 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 844.371 844.371 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 844.37 844.37 0.481319 -0.20 -0.20 0.00778157 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.2478 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 8443.713 8443.713 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 8443.71 8443.71 4.576818 -0.22 -1.60 0.00293341 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.4155 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 844.371 844.371 -999.0 -999.0 -999.000 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 844.37 844.37 0.463804 -0.21 -1.89 0.00274875 40.00 20.76 0.00800000 -6.30 0.00229779 -6.30 3.3705 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 18478.092 18478.092 1.903454 0.00016165 372.504 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 0.7482 0.763247 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:00:00 Sensible 18478.09 18478.09 1.0000 2.20986591 1.903454 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.16163792 60.00 32.22 27.78 0.000 18478.09 -6.30 0.00229779 -6.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 49.8624 0.00 0.00 18546.23 18546.23 2.20986591 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 461273.880 461273.880 18.643063 0.00403543 11002.510 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 18.6773 19.053143 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 461273.88 461273.88 1.0000 21.64415824 18.643063 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 4.03501347 60.00 32.22 27.78 0.000 461273.88 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 49.8624 280293.33 0.00 462774.27 462774.27 21.64415824 12.80 11.60 0.00800000 33059.8 33.77 19.27 0.00800000 54440.9
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 87569.976 87569.976 2.703253 0.00076610 2311.765 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 3.5458 3.617121 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 87569.98 87569.98 1.0000 3.13841342 2.703253 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.76602220 60.00 32.22 27.78 0.000 87569.98 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 49.8624 61327.71 0.00 87873.91 87873.91 3.13841342 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61059.3
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 13894.741 13894.741 0.429468 0.00012156 366.596 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 0.5626 0.573929 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13894.74 13894.74 1.0000 0.49860241 0.429468 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.12154485 60.00 32.22 27.78 0.000 13894.74 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00736137 21.00 0.00736137 45.9345 9731.54 0.00 13941.44 13941.44 0.49860241 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61020.9
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 9564.502 9564.502 0.295666 0.00008367 252.332 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 0.3873 0.395066 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 9564.50 9564.50 1.0000 0.34326168 0.295666 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.08366590 60.00 32.22 27.78 0.000 9564.50 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00741999 21.00 0.00741999 46.2957 6698.01 0.00 9596.53 9596.53 0.34326168 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61016.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 15671.902 15671.902 0.484494 0.00013710 413.446 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 0.6346 0.647336 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 15671.90 15671.90 1.0000 0.56248638 0.484494 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.13709065 60.00 32.22 27.78 0.000 15671.90 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00749196 21.00 0.00749196 46.7388 10973.99 0.00 15724.30 15724.30 0.56248638 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.8
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 7436.533 7436.533 0.240072 0.00006506 192.480 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 0.3011 0.307170 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 7436.53 7436.53 1.0000 0.27871839 0.240072 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.06505140 60.00 32.22 27.78 0.000 7436.53 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.91 0.00700546 21.00 0.00700546 43.7400 5110.99 0.00 7459.33 7459.33 0.27871839 12.80 11.60 0.00800000 33059.8 39.05 20.90 0.00800000 59822.8
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 235288.574 235288.574 7.281439 0.00205841 6204.295 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 9.5270 9.718709 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 235288.57 235288.57 1.0000 8.45357959 7.281439 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 2.05819711 60.00 32.22 27.78 0.000 235288.57 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00741190 21.00 0.00741190 46.2477 164701.70 0.00 236054.14 236054.14 8.45357959 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60983.4
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 154368.281 154368.281 4.777390 0.00135048 4070.448 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 6.2505 6.376257 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 154368.28 154368.28 1.0000 5.54643824 4.777390 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 1.35034330 60.00 32.22 27.78 0.000 154368.28 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00740474 21.00 0.00740474 46.2037 108056.77 0.00 154870.05 154870.05 5.54643824 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60982.3
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 232645.674 232645.674 7.199512 0.00203529 6134.658 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 9.4200 9.609543 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 232645.67 232645.67 1.0000 8.35846461 7.199512 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 2.03507823 60.00 32.22 27.78 0.000 232645.67 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00740515 21.00 0.00740515 46.2061 162853.91 0.00 233403.03 233403.03 8.35846461 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60984.0
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 149044.559 149044.559 4.612402 0.00130391 3930.159 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 6.0349 6.156358 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 149044.56 149044.56 1.0000 5.35489070 4.612402 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 1.30377380 60.00 32.22 27.78 0.000 149044.56 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00738309 21.00 0.00738309 46.0703 104334.42 0.00 149529.67 149529.67 5.35489070 12.80 11.60 0.00800000 33059.8 40.18 21.24 0.00800000 60983.8
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 30372.893 30372.893 0.940328 0.00026572 800.750 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 1.2298 1.254567 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30372.89 30372.89 1.0000 1.09169879 0.940328 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.26568821 60.00 32.22 27.78 0.000 30372.89 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00744127 21.00 0.00744127 46.4300 21257.24 0.00 30470.64 30470.64 1.09169879 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.0
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 19843.927 19843.927 0.614373 0.00017360 523.159 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 0.8035 0.819663 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19843.93 19843.93 1.0000 0.71327230 0.614373 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.17358562 60.00 32.22 27.78 0.000 19843.93 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00743113 21.00 0.00743113 46.3676 13888.29 0.00 19907.75 19907.75 0.71327230 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 30061.012 30061.012 0.930660 0.00026299 792.532 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 1.2172 1.241685 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 30061.01 30061.01 1.0000 1.08047461 0.930660 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.26296002 60.00 32.22 27.78 0.000 30061.01 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00743593 21.00 0.00743593 46.3970 21039.17 0.00 30157.79 30157.79 1.08047461 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 19511.038 19511.038 0.604058 0.00017069 514.386 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 0.7900 0.805913 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19511.04 19511.04 1.0000 0.70129752 0.604058 12.80 11.27 0.00800000 33059.8 40.00 20.76 0.00800000 60796.0 0.17067366 60.00 32.22 27.78 0.000 19511.04 -6.30 0.00229779 -6.30 0.00000000 0.0000 20.95 0.00742233 21.00 0.00742233 46.3134 13655.49 0.00 19573.81 19573.81 0.70129752 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60970.7
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 230972.626 -999.000 9.185795 0.00982611 -999.000 -999.0000 1.00000 1.00000 1024.4184 1004.8586 1.1610 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.185795 10.66449193   4197.9300 999.8980 120.52315431 12.27 6.67 5.60 2833307.48 8.1520 8.152049 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 230972.63 175248.55 1.0000 10.66449193 9.185795 27.02 18.67 0.01053197 54020.5 10.88 10.88 0.00850000 32362.4 9.82510709 6.67 12.27 5.60 20977.854 209994.77 34.40 0.01447326 23.54 2.53819000 27.6317 24.00 0.00891774 24.00 0.00891774 46.2565 115915.59 0.00 236440.52 170886.50 10.66449193 27.02 19.07 0.01053197 54020.5 11.38 11.09 0.00809473 31849.7
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 56773.448 56773.448 2.755738 0.00049668 926.290 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.185795 10.66449193   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 2.2988 2.345055 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 56773.45 56773.45 1.0000 3.19934758 2.755738 -4.86 -4.99 0.00252608 1411.7 12.80 11.27 0.00800000 33059.8 0.49662822 60.00 32.22 27.78 0.000 56773.45 -6.30 0.00229779 -6.30 2.53819000 92.1056 11.95 0.00518956 21.02 0.00593773 37.0845 32514.54 0.00 51914.27 51914.27 3.19934758 2.80 -0.37 0.00252608 9144.3 18.87 8.34 0.00252608 25370.8
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2250186.462 -999.000 85.417658 0.09572813 -999.000 -999.0000 1.00000 1.00000 1024.9104 1004.8586 1.1610 VAV_MID WITH REHEAT FAN Fan:VariableVolume 85.417658 99.16789697   4197.9300 999.8980 120.52315431 12.27 6.67 5.60 2833307.48 79.4191 79.419070 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2250186.46 1664614.59 1.0000 99.16789697 85.417658 27.37 18.98 0.01079662 55054.0 10.88 10.88 0.00850000 32363.3 95.71836861 6.67 12.27 5.60 195070.681 2055115.78 34.40 0.01447326 23.54 25.38195000 29.7151 24.00 0.00903284 24.00 0.00903284 46.8458 1038871.18 0.00 2302053.75 1627764.24 99.16789697 27.37 19.39 0.01079662 55054.0 11.36 11.09 0.00810061 31840.3
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 563769.032 563769.032 25.625297 0.00493210 9137.477 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_MID WITH REHEAT FAN Fan:VariableVolume 85.417658 99.16789697   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 22.8273 23.286755 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 06:30:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 563769.03 563769.03 1.0000 29.75036909 25.625297 -6.06 -6.06 0.00234662 -245.4 12.80 11.27 0.00800000 33059.8 4.93159431 60.00 32.22 27.78 0.000 563769.03 -6.30 0.00229779 -6.30 25.38195000 99.0504 19.15 0.00743893 19.62 0.00715767 48.6357 428469.23 0.00 508441.72 508441.72 29.75036909 2.80 -0.65 0.00234662 8694.5 19.73 8.54 0.00234662 25784.8
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 229252.616 -999.000 9.207607 0.00975294 -999.000 -999.0000 1.00000 1.00000 1024.3667 1004.8586 1.1610 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.207607 10.68981545   4197.9300 999.8980 120.52315431 12.27 6.67 5.60 2833307.48 8.0913 8.091343 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:50:00 Sensible 229252.62 174161.20 1.0000 10.68981545 9.207607 26.88 18.60 0.01050418 53808.2 10.88 10.88 0.00850000 32362.3 9.75194136 6.67 12.27 5.60 21027.668 208224.95 34.40 0.01447326 23.54 2.53819000 27.5662 24.00 0.00898110 24.00 0.00898110 46.5815 121447.83 0.00 234711.83 169754.55 10.68981545 26.88 19.00 0.01050418 53808.2 11.38 11.09 0.00809485 31851.6
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 54413.713 54413.713 2.762282 0.00047603 891.592 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.207607 10.68981545   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 2.2032 2.247585 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 22:20:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 54413.71 54413.71 1.0000 3.20694463 2.762282 -4.09 -4.20 0.00271154 2655.6 12.80 11.27 0.00800000 33059.8 0.47598633 60.00 32.22 27.78 0.000 54413.71 -6.30 0.00229779 -6.30 2.53819000 91.8874 21.00 0.00739787 18.28 0.00735331 54.3330 53426.68 0.00 50205.06 50205.06 3.20694463 2.80 0.10 0.00271154 9609.1 18.30 8.29 0.00271154 25264.2
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 122895.780 -999.000 5.404155 0.00522827 -999.000 -999.0000 1.00000 1.00000 1024.0492 1004.8586 1.1610 CAV_BAS FAN Fan:ConstantVolume 5.404155 6.27409720   4197.9300 999.8980 120.52315431 12.27 6.67 5.60 2833307.48 4.3375 4.337538 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 122895.78 94063.04 1.0000 6.27409720 5.404155 25.99 18.18 0.01033334 52454.3 11.37 11.18 0.00850000 32866.5 5.22773726 6.67 12.27 5.60 9163.579 113732.20 32.21 0.01446927 22.96 1.20015641 22.2080 24.00 0.00901352 24.00 0.00901352 46.7460 65832.44 0.00 125972.37 92086.46 6.27409720 25.99 18.58 0.01033334 52454.3 11.65 11.31 0.00819233 32376.2
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 261003.995 261003.995 5.404155 0.00228338 5785.844 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 CAV_BAS FAN Fan:ConstantVolume 5.404155 6.27409720   4197.9300 999.8980 21.17767908 54.44 82.22 27.78 2469709.07 10.5682 10.780898 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 261003.99 261003.99 1.0000 6.27409720 5.404155 -1.40 -3.29 0.00229779 4334.8 40.00 20.76 0.00800000 60796.0 2.28314388 60.00 32.22 27.78 0.000 261003.99 -6.30 0.00229779 -6.30 1.20015641 22.2080 0.00 0.00229779 23.55 0.00229779 12.3755 0.00 0.00 217406.40 217406.40 6.27409720 12.80 5.08 0.00229779 18663.3 47.14 19.06 0.00229779 53314.7
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 436298.379 302337.298 22.027227 0.01068492 -999.000 -999.0000 -999.00000 -999.00000 1020.8895 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 404426.92 396847.39 0.9270 -999.0 -999.0 28.56 17.68 0.00863364 50745.0 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 404426.92 34.40 0.01447326 23.54 0.33839277 -999.0000 27.00 0.00854241 27.00 0.00854241 37.1030 370098.95 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9489.774 6583.539 0.481319 0.00023240 -999.000 -999.0000 -999.00000 -999.00000 1021.1660 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 8789.02 8439.42 0.9262 -999.0 -999.0 28.10 17.65 0.00878240 50659.8 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8789.02 30.70 0.01446650 22.54 0.01563234 -999.0000 27.00 0.00859006 27.00 0.00859006 37.3049 8035.63 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 90405.532 62654.677 4.576818 0.00221403 -999.000 -999.0000 -999.00000 -999.00000 1021.1922 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:20:00 Sensible 83755.55 80264.91 0.9264 -999.0 -999.0 28.10 17.66 0.00879647 50695.6 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 83755.55 30.52 0.01446618 22.49 0.15632344 -999.0000 27.00 0.00859468 27.00 0.00859468 37.3249 76525.14 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9156.241 6347.677 0.463804 0.00022424 -999.000 -999.0000 -999.00000 -999.00000 1021.1816 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8481.95 8135.03 0.9264 -999.0 -999.0 28.10 17.65 0.00879077 50684.8 12.80 11.77 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8481.95 30.70 0.01446650 22.54 0.01563234 -999.0000 27.00 0.00859280 27.00 0.00859280 37.3168 7803.10 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 436298.379 436298.379 22.027227 0.01068492 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 436298.38 436298.38 1.0000 25.57309356 22.027227 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 436298.38 -6.30 0.00229779 -6.30 0.33839277 1.5362 0.00 0.00850000 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9489.774 9489.774 0.481319 0.00023240 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9489.77 9489.77 1.0000 0.55880063 0.481319 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9489.77 -6.30 0.00229779 -6.30 0.01563234 3.2478 0.00 0.00796565 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 90405.532 90405.532 4.576818 0.00221403 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 90405.53 90405.53 1.0000 5.31357801 4.576818 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 90405.53 -6.30 0.00229779 -6.30 0.15632344 3.4155 0.00 0.00295589 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9156.241 9156.241 0.463804 0.00022424 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1610 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9156.24 9156.24 1.0000 0.53846607 0.463804 -6.30 -6.30 0.00229779 -610.8 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9156.24 -6.30 0.00229779 -6.30 0.01563234 3.3705 0.00 0.00276448 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 18278.075 18278.075 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 22.027227 25.57309356   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 18278.08 18278.08 1.0000 25.57309356 22.027227 -0.10 -0.10 0.00840472 20920.9 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 18278.08 -6.30 0.00229779 -6.30 0.33839277 1.5362 0.00 0.00850000 27.00 0.00850000 36.9155 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 844.371 844.371 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.481319 0.55880063   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 844.37 844.37 1.0000 0.55880063 0.481319 -0.20 -0.20 0.00778157 19252.7 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 844.37 -6.30 0.00229779 -6.30 0.01563234 3.2478 0.00 0.00796565 25.97 0.00796565 36.7905 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 8443.713 8443.713 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.576818 5.31357801   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 8443.71 8443.71 1.0000 5.31357801 4.576818 -0.22 -1.60 0.00293341 7118.9 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 8443.71 -6.30 0.00229779 -6.30 0.15632344 3.4155 0.00 0.00295589 24.04 0.00295589 15.4409 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 844.371 844.371 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1610 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.463804 0.53846607   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown ATLANTA-HARTSFIELD.JACKSON.INTL.AP_GA_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 844.37 844.37 1.0000 0.53846607 0.463804 -0.21 -1.89 0.00274875 6660.0 40.00 20.76 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 844.37 -6.30 0.00229779 -6.30 0.01563234 3.3705 0.00 0.00276448 22.90 0.00276448 15.4755 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 9.19 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 85.42 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 9.21 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 5.40 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 3605.17 1897.17 1241.17
CORE_BOTTOM 3607.17 757.83 36.83
CORE_MID 3060.83 2017.67 95.67
CORE_TOP 3187.00 2664.83 483.17
PERIMETER_BOT_ZN_3 3151.50 2411.17 290.50
PERIMETER_BOT_ZN_2 3153.50 2400.00 321.83
PERIMETER_BOT_ZN_1 3368.50 1927.50 288.50
PERIMETER_BOT_ZN_4 3868.17 1436.67 405.50
PERIMETER_MID_ZN_3 3419.50 3267.50 1103.00
PERIMETER_MID_ZN_2 2921.00 2650.17 909.00
PERIMETER_MID_ZN_1 3331.00 2481.17 634.33
PERIMETER_MID_ZN_4 3474.33 2889.67 842.33
PERIMETER_TOP_ZN_3 3768.33 3476.83 1616.00
PERIMETER_TOP_ZN_2 3768.33 3215.50 1419.67
PERIMETER_TOP_ZN_1 3557.67 2891.17 1048.17
PERIMETER_TOP_ZN_4 3687.83 3167.50 1257.83
DATACENTER_BOT_ZN_6 5938.17 1001.17 1001.17
DATACENTER_MID_ZN_6 5704.17 160.33 135.00
DATACENTER_TOP_ZN_6 5377.00 484.33 297.00
DATACENTER_BASEMENT_ZN_6 5943.00 5612.33 5612.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5940.50 5929.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 69.17 0.00 4.83
CORE_BOTTOM 0.00 3.17 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 5.17 0.00 0.67 0.00
PERIMETER_BOT_ZN_3 0.00 3.83 0.00 1.17
PERIMETER_BOT_ZN_2 0.00 21.33 0.00 20.83
PERIMETER_BOT_ZN_1 0.33 31.83 0.00 27.67
PERIMETER_BOT_ZN_4 0.00 160.00 0.00 49.33
PERIMETER_MID_ZN_3 23.50 1.33 5.50 1.00
PERIMETER_MID_ZN_2 12.83 27.50 0.67 26.67
PERIMETER_MID_ZN_1 10.17 19.33 1.00 18.50
PERIMETER_MID_ZN_4 10.17 39.67 0.67 18.00
PERIMETER_TOP_ZN_3 107.83 10.17 37.00 6.50
PERIMETER_TOP_ZN_2 58.83 39.00 8.33 32.00
PERIMETER_TOP_ZN_1 44.83 29.33 8.83 23.67
PERIMETER_TOP_ZN_4 37.50 46.17 6.67 20.50
DATACENTER_BOT_ZN_6 0.00 54.67 0.00 53.67
DATACENTER_MID_ZN_6 0.00 60.67 0.00 60.67
DATACENTER_TOP_ZN_6 0.00 53.50 0.00 51.33
DATACENTER_BASEMENT_ZN_6 0.00 486.00 0.00 426.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 114.50 774.17 37.83 539.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 149.60 6779.02 1.189 0.000 0.000 0.000
CORE_BOTTOM 55.32 134.35 6849.35 0.846 0.000 0.000 0.000
CORE_MID 55.32 134.35 6849.35 0.678 0.000 0.000 0.000
CORE_TOP 55.32 134.35 6849.35 0.638 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.95 16.87 860.00 0.760 0.043 0.000 0.000
PERIMETER_BOT_ZN_2 4.48 10.87 554.22 0.974 0.045 0.000 0.000
PERIMETER_BOT_ZN_1 6.95 16.87 860.02 1.040 0.043 0.000 0.000
PERIMETER_BOT_ZN_4 4.48 10.87 554.22 1.533 0.045 0.000 0.000
PERIMETER_MID_ZN_3 6.95 16.87 860.00 0.667 0.101 0.000 0.000
PERIMETER_MID_ZN_2 3.91 10.87 554.22 0.869 0.111 0.000 0.000
PERIMETER_MID_ZN_1 6.95 16.87 860.02 0.937 0.102 0.000 0.000
PERIMETER_MID_ZN_4 4.48 10.87 554.22 1.009 0.105 0.000 0.000
PERIMETER_TOP_ZN_3 6.95 16.87 860.00 0.668 0.126 0.000 0.000
PERIMETER_TOP_ZN_2 4.48 10.87 554.22 0.950 0.130 0.000 0.000
PERIMETER_TOP_ZN_1 6.95 16.87 860.02 0.887 0.126 0.000 0.000
PERIMETER_TOP_ZN_4 4.48 10.87 554.22 1.017 0.130 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.37 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 61.60 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.32 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.32 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.32 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.95 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.95 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.95 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.91 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.95 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.95 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.48 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.95 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.48 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.80 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.37 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 61.60 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.32 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.32 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.32 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.95 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.95 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.95 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.91 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.95 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.95 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.95 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.48 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.80 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.80 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.37 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1020.85 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 49470860.48 0.00 49470860.48 0.00 49470860.48 37848132.68 3987.16 1694.59 3078.25 318.29
CORE_BOTTOM 35783513.84 0.00 35783513.84 0.00 35783513.84 33990283.35 5434.16 168.67 3157.18 324.51
CORE_MID 0.28E+09 0.00 0.28E+09 0.00 0.28E+09 0.34E+09 5779.81 549.55 2430.64 154.40
CORE_TOP 25940782.08 0.00 25940782.08 0.00 25940782.08 33990283.35 6122.39 467.54 2170.07 221.20
PERIMETER_BOT_ZN_3 4039025.61 0.00 4039025.61 439326.30 4478351.91 4267819.30 4548.57 198.09 4013.34 324.51
PERIMETER_BOT_ZN_2 3327409.11 0.00 3327409.11 292884.00 3620293.11 2750345.05 4037.06 50.51 4672.42 324.51
PERIMETER_BOT_ZN_1 5446980.17 0.00 5446980.17 439326.30 5886306.47 4267912.63 4359.50 194.70 4205.80 324.51
PERIMETER_BOT_ZN_4 5203398.89 0.00 5203398.89 292884.00 5496282.89 2750345.05 3794.15 1.42 4964.43 324.51
PERIMETER_MID_ZN_3 34271019.47 0.00 34271019.47 1030333.47 35301352.94 42678193.03 4612.75 548.53 3598.72 154.40
PERIMETER_MID_ZN_2 31341772.62 0.00 31341772.62 686888.51 32028661.13 27503450.52 4158.65 10.40 4590.94 1063.40
PERIMETER_MID_ZN_1 47730149.50 0.00 47730149.50 1030333.47 48760482.96 42679126.28 4411.60 546.19 3802.21 154.40
PERIMETER_MID_ZN_4 33280423.48 0.00 33280423.48 686888.51 33967311.99 27503450.52 4123.33 7.29 4629.37 154.40
PERIMETER_TOP_ZN_3 3414196.07 0.00 3414196.07 1279256.65 4693452.72 4267819.30 4767.88 474.95 3517.17 221.20
PERIMETER_TOP_ZN_2 3119254.61 0.00 3119254.61 852837.19 3972091.80 2750345.05 4224.43 5.07 4530.50 221.20
PERIMETER_TOP_ZN_1 4506716.45 0.00 4506716.45 1279256.65 5785973.10 4267912.63 4623.51 526.67 3609.82 221.20
PERIMETER_TOP_ZN_4 3343919.21 0.00 3343919.21 852837.19 4196756.39 2750345.05 4198.49 4.67 4556.84 221.20
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.44E+10 0.00 0.44E+10 40073047.80 0.45E+10 0.50E+10 6718.05 4374.64 5139.90 1559.23


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.1914 0.0000 2.1914 0.0000 2.1914 1.2002 1376.70 1692.23 2874.07
CORE_BOTTOM 1.5777 0.0000 1.5777 0.0000 1.5777 1.0778 2898.51 165.80 2878.69
CORE_MID 12.6385 0.0000 12.6385 0.0000 12.6385 10.7782 3039.66 548.66 2354.68
CORE_TOP 1.1895 0.0000 1.1895 0.0000 1.1895 1.0778 3348.95 467.46 2126.59
PERIMETER_BOT_ZN_3 0.1778 0.0000 0.1778 0.0102 0.1880 0.1353 2007.86 194.86 3740.28
PERIMETER_BOT_ZN_2 0.1470 0.0000 0.1470 0.0068 0.1538 0.0872 1522.76 47.29 4372.95
PERIMETER_BOT_ZN_1 0.2435 0.0000 0.2435 0.0102 0.2537 0.1353 1819.06 191.64 3932.30
PERIMETER_BOT_ZN_4 0.2311 0.0000 0.2311 0.0068 0.2379 0.0872 1294.97 1.13 4646.90
PERIMETER_MID_ZN_3 1.5639 0.0000 1.5639 0.0239 1.5878 1.3533 1874.59 547.17 3521.24
PERIMETER_MID_ZN_2 1.3118 0.0000 1.3118 0.0169 1.3287 0.8721 1410.50 6.57 3616.93
PERIMETER_MID_ZN_1 2.1932 0.0000 2.1932 0.0239 2.2171 1.3533 1672.81 545.02 3725.18
PERIMETER_MID_ZN_4 1.5223 0.0000 1.5223 0.0159 1.5382 0.8721 1389.07 6.87 4547.05
PERIMETER_TOP_ZN_3 0.1567 0.0000 0.1567 0.0297 0.1863 0.1353 1997.55 474.48 3470.97
PERIMETER_TOP_ZN_2 0.1435 0.0000 0.1435 0.0198 0.1632 0.0872 1457.55 4.96 4480.50
PERIMETER_TOP_ZN_1 0.2078 0.0000 0.2078 0.0297 0.2374 0.1353 1851.41 526.51 3565.08
PERIMETER_TOP_ZN_4 0.1536 0.0000 0.1536 0.0198 0.1734 0.0872 1434.53 4.27 4504.21
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 200.1291 0.0000 200.1291 0.9383 201.0674 158.4706 3901.05 4362.54 4697.39


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 72512252.12 0.00 72512252.12 48026705.38 3799.24 2.25 4958.51 324.51
VAV_MID WITH REHEAT 0.57E+09 0.00 0.57E+09 0.48E+09 4116.96 3.28 4639.76 154.40
VAV_TOP WITH REHEAT 54344766.14 0.00 54344766.14 48026705.38 4199.04 2.31 4558.65 221.04
CAV_BAS 66680116.93 0.00 66680116.93 37848132.68 3937.25 3.55 4819.21 318.29
AIRLOOP DATACENTER BASEMENT 7127877.82 0.00 7127877.82 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 329278.43 0.00 329278.43 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3292784.26 0.00 3292784.26 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 329278.43 0.00 329278.43 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.2039 0.0000 3.2039 1.5229 1297.62 0.71 4644.67
VAV_MID WITH REHEAT 26.0820 0.0000 26.0820 15.2292 1381.88 2.89 4558.22
VAV_TOP WITH REHEAT 2.4945 0.0000 2.4945 1.5229 1433.55 1.56 4507.89
CAV_BAS 2.9537 0.0000 2.9537 1.2002 1362.86 1.15 4579.00
AIRLOOP DATACENTER BASEMENT 0.3332 0.0000 0.3332 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0154 0.0000 0.0154 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1539 0.0000 0.1539 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0154 0.0000 0.0154 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.85 3028.25 0.00 0.00 0.00 1967.91 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.15 2631.49 0.00 0.00 0.00 2141.78 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.42 2496.50 0.00 0.00 0.00 2366.47 0.00 0.00 0.00
CAV_BAS 0.00 1690.08 3223.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 5.4347 0.0000 0.0000 0.0000 2.2066 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 43.5265 0.0000 0.0000 0.0000 22.0331 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 4.2547 0.0000 0.0000 0.0000 2.1726 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6177 5.1014 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4562 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0211 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2108 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0211 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1386
Defaulted Fields 1179
Fields with Defaults 3922
Autosized Fields 333
Autosizable Fields 412
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
Electricity:Building 17959.48 247233.96 01-JAN-09:20 1050571.48 06-DEC-08:10
Electricity:Zone:BASEMENT 602.14 14319.77 01-JAN-00:10 28977.00 02-JAN-08:10
Electricity:SpaceType:GENERAL 17959.48 247233.96 01-JAN-09:20 1050571.48 06-DEC-08:10
InteriorLights:Electricity 2746.07 13024.70 01-JAN-09:20 260952.65 30-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2746.07 13024.70 01-JAN-09:20 260952.65 30-OCT-07:10
LightsWired:InteriorLights:Electricity 2746.07 13024.70 01-JAN-09:20 260952.65 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2746.07 13024.70 01-JAN-09:20 260952.65 30-OCT-07:10
Electricity:Zone:CORE_BOTTOM 480.91 6817.20 01-JAN-00:10 32066.15 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:CORE_MID 4809.09 68171.81 01-JAN-00:10 320660.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
Electricity:Zone:CORE_TOP 480.91 6817.18 01-JAN-00:10 32066.08 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 54.28 818.50 01-JAN-09:10 4023.18 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.94 59.73 01-JAN-09:10 1746.86 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.94 59.73 01-JAN-09:10 1746.86 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 34.91 527.47 01-JAN-08:50 2592.69 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.91 38.49 01-JAN-08:50 1125.75 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.91 38.49 01-JAN-08:50 1125.75 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_1 54.09 818.51 01-JAN-08:50 4023.25 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.74 59.73 01-JAN-08:50 1746.90 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.74 59.73 01-JAN-08:50 1746.90 30-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 34.95 527.47 01-JAN-09:20 2592.68 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.95 38.49 01-JAN-09:20 1125.75 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.95 38.49 01-JAN-09:20 1125.75 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 543.00 8184.99 01-JAN-09:10 40232.74 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 139.57 597.26 01-JAN-09:10 17469.56 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 139.57 597.26 01-JAN-09:10 17469.56 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 349.15 5274.72 01-JAN-08:50 25927.06 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 89.17 384.90 01-JAN-08:50 11257.60 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 89.17 384.90 01-JAN-08:50 11257.60 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_1 541.01 8185.12 01-JAN-08:50 40233.47 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 137.58 597.27 01-JAN-08:50 17469.94 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 137.58 597.27 01-JAN-08:50 17469.94 30-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 349.55 5274.69 01-JAN-09:20 25926.96 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 89.57 384.90 01-JAN-09:20 11257.60 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 89.57 384.90 01-JAN-09:20 11257.60 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 54.30 818.50 01-JAN-09:10 4023.27 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.96 59.73 01-JAN-09:10 1746.95 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.96 59.73 01-JAN-09:10 1746.95 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 34.92 527.47 01-JAN-08:50 2592.70 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.92 38.49 01-JAN-08:50 1125.76 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.92 38.49 01-JAN-08:50 1125.76 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_1 54.10 818.51 01-JAN-08:50 4023.34 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.76 59.73 01-JAN-08:50 1746.99 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.76 59.73 01-JAN-08:50 1746.99 30-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 34.96 527.47 01-JAN-09:20 2592.69 30-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.96 38.49 01-JAN-09:20 1125.76 30-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.96 38.49 01-JAN-09:20 1125.76 30-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7544.97 95151.24 01-JAN-00:10 384008.34 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1585.20 19711.13 01-JAN-00:10 81995.25 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 3484.58 5877.28 07-JAN-17:10 423602.84 25-AUG-13:50
HeatRejection:Electricity 1437.08 2316.44 14-JAN-08:00 90905.92 30-MAR-12:50
General:HeatRejection:Electricity 1437.08 2316.44 14-JAN-08:00 90905.92 30-MAR-12:50
Electricity:HVAC 5237.02 74345.19 08-JAN-23:50 433848.72 12-APR-15:30
ExteriorEquipment:Electricity 1914.38 28294.68 01-JAN-00:10 117204.66 30-OCT-07:20
Transformer:ExteriorEquipment:Electricity 59.77 1112.61 01-JAN-00:10 3726.69 30-OCT-07:20
ElectricityPurchased:Facility 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
ElectricityPurchased:Plant 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
Cogeneration:ElectricityPurchased 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
General:Cogeneration:ElectricityPurchased 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
ElectricityNet:Plant 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
Cogeneration:ElectricityNet 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
General:Cogeneration:ElectricityNet 28983.11 362024.03 08-JAN-10:30 1920628.32 03-AUG-15:50
Fans:Electricity 2410.30 42513.51 06-JAN-22:10 278556.53 02-JUN-15:30
General:Fans:Electricity 2410.30 42513.51 06-JAN-22:10 278556.53 02-JUN-15:30
ExteriorLights:Electricity 447.43 0.00 01-JAN-07:50 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 447.43 0.00 01-JAN-07:50 37611.08 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 44.68 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
General:HeatRecovery:Electricity 44.68 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
Cooling:Electricity 3987.01 28046.97 09-JAN-07:20 440803.98 25-AUG-13:50
General:Cooling:Electricity 3987.01 28046.97 09-JAN-07:20 440803.98 25-AUG-13:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 8.95 0.00 01-JAN-00:10 5868.07 05-JAN-18:10
General:Humidifier:Electricity 8.95 0.00 01-JAN-00:10 5868.07 05-JAN-18:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 773.81 3406.34 01-JAN-00:10 69385.65 12-APR-15:30
General:Pumps:Electricity 773.81 3406.34 01-JAN-00:10 69385.65 12-APR-15:30
WIRED_LTG_ELECTRICITY 77.16 0.00 01-JAN-00:10 7332.77 30-OCT-07:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1155.38 5695.87 13-AUG-16:20 1240967.67 13-FEB-07:10
NaturalGas:Plant 1155.38 5695.87 13-AUG-16:20 1240967.67 13-FEB-07:10
Heating:NaturalGas 497.66 0.00 01-JAN-00:10 1211803.93 13-FEB-07:10
Boiler:Heating:NaturalGas 497.66 0.00 01-JAN-00:10 1211803.93 13-FEB-07:10
WaterSystems:NaturalGas 657.72 5695.87 07-JAN-04:10 79719.79 01-FEB-12:20
Water Heater:WaterSystems:NaturalGas 657.72 5695.87 07-JAN-04:10 79719.79 01-FEB-12:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 21396.01 138012.33 09-JAN-07:10 2558543.80 25-AUG-13:50
PlantLoopCoolingDemand:HVAC 21396.01 138012.33 09-JAN-07:10 2558543.80 25-AUG-13:50
CoolingCoils:PlantLoopCoolingDemand 21396.01 138012.33 09-JAN-07:10 2558543.80 25-AUG-13:50


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 9469.14 0.00 01-JAN-00:10 0.00 14-APR-12:40
Water:HVAC 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Humidifier:Water 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
General:Humidifier:Water 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
MainsWater:Facility 9469.14 0.00 01-JAN-00:10 0.00 14-APR-12:40
MainsWater:HVAC 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Humidifier:MainsWater 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
General:Humidifier:MainsWater 3.33 0.00 01-JAN-00:10 0.00 05-JAN-18:10
Water:Plant 9465.81 0.00 01-JAN-00:10 0.00 14-APR-12:40
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 9465.81 0.00 01-JAN-00:10 0.00 14-APR-12:40
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 7185.64 0.00 01-JAN-00:10 0.00 14-APR-14:10
General:HeatRejection:Water 7185.64 0.00 01-JAN-00:10 0.00 14-APR-14:10
HeatRejection:MainsWater 7185.64 0.00 01-JAN-00:10 0.00 14-APR-14:10
General:HeatRejection:MainsWater 7185.64 0.00 01-JAN-00:10 0.00 14-APR-14:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 66668.47 212916.23 09-JAN-04:30 10023887.15 25-AUG-13:50
EnergyTransfer:Building 18855.93 87836.55 14-JAN-19:30 1539627.69 02-AUG-15:40
EnergyTransfer:Zone:BASEMENT 640.92 0.00 01-JAN-00:40 73240.94 13-NOV-06:10
Heating:EnergyTransfer 284.03 0.00 19-JAN-20:10 822817.41 09-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.02 0.00 01-JAN-00:20 23527.37 08-JUL-16:10
General:Heating:EnergyTransfer 284.03 0.00 19-JAN-20:10 822817.41 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.02 0.00 01-JAN-00:20 23527.37 08-JUL-16:10
Cooling:EnergyTransfer 18571.89 85209.75 09-JAN-04:30 1539627.69 02-AUG-15:40
Cooling:EnergyTransfer:Zone:BASEMENT 636.91 0.00 01-JAN-00:40 73240.94 13-NOV-06:10
General:Cooling:EnergyTransfer 18571.89 85209.75 09-JAN-04:30 1539627.69 02-AUG-15:40
General:Cooling:EnergyTransfer:Zone:BASEMENT 636.91 0.00 01-JAN-00:40 73240.94 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 639.85 0.00 01-JAN-00:10 52773.26 07-AUG-09:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 639.85 0.00 01-JAN-00:10 52773.26 07-AUG-09:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 639.85 0.00 01-JAN-00:10 52773.26 07-AUG-09:20
EnergyTransfer:Zone:CORE_MID 4638.54 0.00 01-JAN-00:10 445884.53 02-JUN-14:10
Heating:EnergyTransfer:Zone:CORE_MID 0.91 0.00 01-JAN-00:10 181317.16 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.91 0.00 01-JAN-00:10 181317.16 09-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_MID 4637.63 0.00 01-JAN-00:10 445884.53 02-JUN-14:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 4637.63 0.00 01-JAN-00:10 445884.53 02-JUN-14:10
EnergyTransfer:Zone:CORE_TOP 443.26 0.00 01-JAN-00:10 65515.84 09-JAN-05:20
Heating:EnergyTransfer:Zone:CORE_TOP 6.26 0.00 01-JAN-00:10 65515.84 09-JAN-05:20
General:Heating:EnergyTransfer:Zone:CORE_TOP 6.26 0.00 01-JAN-00:10 65515.84 09-JAN-05:20
Cooling:EnergyTransfer:Zone:CORE_TOP 437.00 0.00 01-JAN-00:10 49225.07 16-MAY-14:30
General:Cooling:EnergyTransfer:Zone:CORE_TOP 437.00 0.00 01-JAN-00:10 49225.07 16-MAY-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 78.17 0.00 01-JAN-00:10 9976.75 07-AUG-13:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.27 0.00 01-JAN-00:10 4829.90 13-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.27 0.00 01-JAN-00:10 4829.90 13-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 77.90 0.00 01-JAN-00:10 9976.75 07-AUG-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 77.90 0.00 01-JAN-00:10 9976.75 07-AUG-13:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 62.63 0.00 01-JAN-00:10 10495.36 07-JUL-09:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.19 0.00 01-JAN-00:10 3321.82 14-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.19 0.00 01-JAN-00:10 3321.82 14-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 62.44 0.00 01-JAN-00:10 10495.36 07-JUL-09:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 62.44 0.00 01-JAN-00:10 10495.36 07-JUL-09:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 99.35 0.00 01-JAN-00:10 14929.46 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.34 0.00 01-JAN-00:10 8050.43 09-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.34 0.00 01-JAN-00:10 8050.43 09-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 99.01 0.00 01-JAN-00:10 14929.46 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 99.01 0.00 01-JAN-00:10 14929.46 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.25 0.00 01-JAN-00:10 14456.16 18-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.01 0.00 01-JAN-00:10 1876.29 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.01 0.00 01-JAN-00:10 1876.29 09-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.24 0.00 01-JAN-00:10 14456.16 18-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 99.24 0.00 01-JAN-00:10 14456.16 18-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 614.38 0.00 01-JAN-00:10 115977.15 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 57.37 0.00 01-JAN-00:10 115977.15 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 57.37 0.00 01-JAN-00:10 115977.15 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 557.01 0.00 01-JAN-00:10 91960.35 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 557.01 0.00 01-JAN-00:10 91960.35 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 547.74 0.00 01-JAN-00:10 108994.35 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 28.95 0.00 01-JAN-00:10 108994.35 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 28.95 0.00 01-JAN-00:10 108994.35 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 518.80 0.00 01-JAN-00:10 108397.23 07-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 518.80 0.00 01-JAN-00:10 108397.23 07-JUL-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 818.97 0.00 01-JAN-00:10 142268.20 10-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 24.85 0.00 01-JAN-00:10 128800.09 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 24.85 0.00 01-JAN-00:10 128800.09 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 794.12 0.00 01-JAN-00:10 142268.20 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 794.12 0.00 01-JAN-00:10 142268.20 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 579.34 0.00 01-JAN-00:10 111260.87 02-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 21.05 0.00 01-JAN-00:10 98734.52 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 21.05 0.00 01-JAN-00:10 98734.52 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 558.28 0.00 01-JAN-00:10 111260.87 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 558.28 0.00 01-JAN-00:10 111260.87 02-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 71.83 0.00 01-JAN-00:10 14346.62 13-FEB-04:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 17.29 0.00 01-JAN-00:10 14346.62 13-FEB-04:40
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 17.29 0.00 01-JAN-00:10 14346.62 13-FEB-04:40
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 54.55 0.00 01-JAN-00:10 10350.07 14-JUL-15:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 54.55 0.00 01-JAN-00:10 10350.07 14-JUL-15:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 60.45 0.00 01-JAN-00:10 12598.32 13-FEB-05:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 8.70 0.00 01-JAN-00:10 12598.32 13-FEB-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 8.70 0.00 01-JAN-00:10 12598.32 13-FEB-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 51.75 0.00 01-JAN-00:10 11319.66 07-JUL-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 51.75 0.00 01-JAN-00:10 11319.66 07-JUL-09:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 84.86 0.00 01-JAN-00:10 15605.23 13-FEB-04:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 8.95 0.00 01-JAN-00:10 15605.23 13-FEB-04:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 8.95 0.00 01-JAN-00:10 15605.23 13-FEB-04:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 75.91 0.00 01-JAN-00:10 15559.42 10-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 75.91 0.00 01-JAN-00:10 15559.42 10-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 62.36 0.00 01-JAN-00:10 13142.12 13-FEB-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.90 0.00 01-JAN-00:10 13142.12 13-FEB-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 6.90 0.00 01-JAN-00:10 13142.12 13-FEB-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 55.46 0.00 01-JAN-00:10 11961.52 02-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 55.46 0.00 01-JAN-00:10 11961.52 02-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 68.53 0.00 01-JAN-00:10 10273.30 14-AUG-05:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 2.14 0.00 01-JAN-00:10 3914.77 24-NOV-04:10
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 2.14 0.00 01-JAN-00:10 3914.77 24-NOV-04:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 66.39 0.00 01-JAN-00:10 10273.30 14-AUG-05:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 66.39 0.00 01-JAN-00:10 10273.30 14-AUG-05:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 513.48 0.00 01-JAN-00:10 72819.72 05-JUL-16:00
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 64.12 0.00 01-JAN-00:10 67578.94 09-JAN-06:10
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 64.12 0.00 01-JAN-00:10 67578.94 09-JAN-06:10
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 449.37 0.00 01-JAN-00:10 72819.72 05-JUL-16:00
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 449.37 0.00 01-JAN-00:10 72819.72 05-JUL-16:00
EnergyTransfer:Zone:TOPFLOOR_PLENUM 98.34 0.00 01-JAN-00:10 23929.69 13-FEB-05:30
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 28.07 0.00 01-JAN-00:10 23929.69 13-FEB-05:30
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 28.07 0.00 01-JAN-00:10 23929.69 13-FEB-05:30
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 70.26 0.00 01-JAN-00:10 20542.99 07-JUL-15:10
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 70.26 0.00 01-JAN-00:10 20542.99 07-JUL-15:10
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.92 285.20 08-JAN-08:00 7880.62 09-APR-18:20
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.92 285.20 08-JAN-08:00 7880.62 09-APR-18:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 138.92 285.20 08-JAN-08:00 7880.62 09-APR-18:20
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1234.97 7.73 23-JAN-07:40 73792.10 13-AUG-19:10
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 2.93 0.00 02-JAN-10:00 5272.90 08-JAN-19:00
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 2.93 0.00 02-JAN-10:00 5272.90 08-JAN-19:00
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1232.04 0.00 01-JAN-00:10 73792.10 13-AUG-19:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1232.04 0.00 01-JAN-00:10 73792.10 13-AUG-19:10
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 117.11 0.26 14-JAN-07:20 7536.78 20-AUG-16:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.72 0.00 02-JAN-14:00 570.85 15-JAN-19:00
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.72 0.00 02-JAN-14:00 570.85 15-JAN-19:00
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 116.39 0.00 01-JAN-00:10 7536.78 20-AUG-16:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 116.39 0.00 01-JAN-00:10 7536.78 20-AUG-16:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7142.68 84853.40 09-JAN-05:00 369453.19 07-AUG-21:20
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7142.68 84853.40 09-JAN-05:00 369453.19 07-AUG-21:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7142.68 84853.40 09-JAN-05:00 369453.19 07-AUG-21:20
PlantLoopHeatingDemand:Facility 724.99 0.00 01-JAN-00:10 1055191.49 13-FEB-07:10
PlantLoopHeatingDemand:Plant 371.93 0.00 01-JAN-00:10 47930.29 31-JAN-12:20
WaterSystems:PlantLoopHeatingDemand 371.93 0.00 01-JAN-00:10 47930.29 31-JAN-12:20
General:WaterSystems:PlantLoopHeatingDemand 371.93 0.00 01-JAN-00:10 47930.29 31-JAN-12:20
EnergyTransfer:HVAC 20215.22 122077.22 09-JAN-04:30 2462878.06 10-AUG-16:00
HeatingCoils:EnergyTransfer 353.06 0.00 01-JAN-00:10 1039317.49 13-FEB-07:10
PlantLoopHeatingDemand:HVAC 353.06 0.00 01-JAN-00:10 1039317.49 13-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 353.06 0.00 01-JAN-00:10 1039317.49 13-FEB-07:10
CoolingCoils:EnergyTransfer 18682.69 110006.32 09-JAN-07:20 2383013.98 25-AUG-13:50
HeatRecoveryForHeating:EnergyTransfer 372.22 0.00 01-JAN-00:10 454886.43 03-FEB-07:20
HeatRecoveryForCooling:EnergyTransfer 807.25 0.00 01-JAN-00:10 407317.07 08-JUL-14:00
EnergyTransfer:Plant 27597.32 0.00 01-JAN-00:10 6157234.88 25-AUG-13:50
LoopToLoop:EnergyTransfer 9162.07 -5573.72 19-JAN-06:10 1967769.74 25-AUG-13:50
WaterSystems:EnergyTransfer 371.93 0.00 01-JAN-00:10 47930.29 31-JAN-12:20
WaterUse:WaterSystems:EnergyTransfer 371.93 0.00 01-JAN-00:10 47930.29 31-JAN-12:20
Boilers:EnergyTransfer 349.77 0.00 01-JAN-00:10 1012744.51 13-FEB-07:10
Chillers:EnergyTransfer 8219.93 0.00 01-JAN-00:10 1935910.91 25-AUG-13:50
HeatRejection:EnergyTransfer 9493.62 0.00 01-JAN-00:10 2201185.06 25-AUG-13:50
General:HeatRejection:EnergyTransfer 9493.62 0.00 01-JAN-00:10 2201185.06 25-AUG-13:50
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.017 -636.909 0.000 0.000 92.747 177.742 424.397 0.000 0.000 0.000 0.001 0.000 0.000 0.000 0.000 -61.994
CORE_BOTTOM 0.000 0.000 0.000 -639.850 0.000 0.000 83.461 159.625 321.286 0.000 0.000 0.000 75.478 0.000 0.000 0.000 0.000 -0.005
CORE_MID 0.000 0.000 0.914 -4637.609 0.000 0.000 844.296 1596.246 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1016.691
CORE_TOP 0.000 0.000 6.264 -436.993 0.000 0.000 86.554 159.625 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -136.735
PERIMETER_BOT_ZN_3 0.000 0.000 0.269 -77.901 0.000 0.000 10.743 13.940 40.342 22.931 0.000 0.227 37.548 0.000 -43.108 0.000 -4.990 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.190 -62.438 0.000 0.000 6.910 8.913 25.998 38.150 0.000 0.151 11.150 0.000 -25.725 0.000 -3.299 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.340 -99.013 0.000 0.000 10.644 13.744 40.343 67.215 0.000 0.216 10.254 0.000 -38.664 0.000 -5.079 -0.002
PERIMETER_BOT_ZN_4 0.000 0.000 0.010 -99.239 0.000 0.000 6.817 8.954 25.998 37.554 0.000 0.134 54.696 0.000 -31.188 0.000 -3.735 0.000
PERIMETER_MID_ZN_3 0.000 0.000 57.369 -557.000 0.000 0.000 111.302 139.574 403.423 237.275 0.000 5.356 89.875 0.000 -385.130 0.000 -102.044 -0.008
PERIMETER_MID_ZN_2 0.000 0.000 28.945 -518.792 0.000 0.000 52.258 89.170 259.981 382.778 0.000 3.316 11.391 0.000 -238.811 0.000 -70.237 -0.003
PERIMETER_MID_ZN_1 0.000 0.000 24.847 -794.106 0.000 0.000 107.985 137.582 403.429 672.464 0.000 4.952 0.006 0.000 -369.915 0.000 -111.708 -75.529
PERIMETER_MID_ZN_4 0.000 0.000 21.053 -558.277 0.000 0.000 71.046 89.570 259.979 386.067 0.000 3.201 65.375 0.000 -264.908 0.000 -73.107 0.000
PERIMETER_TOP_ZN_3 0.000 0.000 17.287 -54.547 0.000 0.000 11.294 13.957 40.342 23.901 0.000 0.630 0.001 0.000 -36.059 0.000 -11.802 -5.004
PERIMETER_TOP_ZN_2 0.000 0.000 8.701 -51.746 0.000 0.000 7.188 8.917 25.998 38.496 0.000 0.392 0.000 0.000 -22.501 0.000 -8.143 -7.302
PERIMETER_TOP_ZN_1 0.000 0.000 8.946 -75.912 0.000 0.000 10.961 13.759 40.343 67.643 0.000 0.579 0.000 0.000 -34.828 0.000 -12.900 -18.590
PERIMETER_TOP_ZN_4 0.000 0.000 6.903 -55.458 0.000 0.000 7.216 8.957 25.998 38.688 0.000 0.384 0.872 0.000 -25.047 0.000 -8.514 -0.000
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -138.921 0.000 0.000 0.948 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -20.548
DATACENTER_MID_ZN_6 0.000 0.000 2.932 -1232.037 0.000 0.000 9.487 46.396 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -365.584
DATACENTER_TOP_ZN_6 0.000 0.000 0.721 -116.387 0.000 0.000 0.952 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -43.806
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7142.692 0.000 0.000 20.222 50.116 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -422.503
GROUNDFLOOR_PLENUM 2.135 -66.392 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.405 74.683 0.000 0.000 0.000 -10.832 0.000
MIDFLOOR_PLENUM 64.117 -449.364 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 7.482 558.281 0.000 0.000 0.000 -180.517 -0.005
TOPFLOOR_PLENUM 28.075 -70.260 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.641 60.051 0.000 0.000 0.000 -18.507 -0.002
Total Facility 94.328 -586.015 189.710 -17985.825 0.000 0.000 1553.030 2746.065 15213.411 2013.162 0.000 28.068 1049.663 0.000 -1515.885 0.000 -625.414 -2174.313


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 18-DEC-04:01 0.00 0.00 0.00 -105385.38 0.00 0.00 0.00 862.23 13457.54 0.00 0.00 0.00 91065.61 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 10-OCT-03:03 0.00 0.00 0.00 -91707.95 0.00 0.00 0.00 774.34 8057.15 0.00 0.00 0.00 82876.46 0.00 -0.00 0.00 0.00 0.00
CORE_MID 18-SEP-03:02 0.00 0.00 0.00 -795594.12 0.00 0.00 0.00 7743.41 80571.20 0.00 0.00 0.00 707279.51 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 19-JUN-03:02 0.00 0.00 0.00 -80431.03 0.00 0.00 0.00 774.34 8057.12 0.00 0.00 0.00 71599.57 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 25-JUN-16:41 0.00 0.00 0.00 -15466.34 0.00 0.00 43.73 59.73 758.77 3888.96 0.00 231.63 10483.52 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 04-JUN-09:02 0.00 0.00 0.00 -16107.46 0.00 0.00 24.39 38.49 488.98 10511.46 0.00 0.00 5070.35 0.00 -0.00 0.00 -26.20 0.00
PERIMETER_BOT_ZN_1 09-OCT-14:22 0.00 0.00 0.00 -19345.04 0.00 0.00 37.66 59.73 758.78 11853.67 0.00 0.00 6644.05 0.00 -0.00 0.00 -8.84 0.00
PERIMETER_BOT_ZN_4 23-JUL-16:51 0.00 0.00 0.00 -22274.71 0.00 0.00 20.40 38.49 488.98 9790.93 0.00 36.02 11899.88 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 17-JUL-05:02 0.00 0.00 0.00 -116207.48 0.00 0.00 1104.92 1944.52 10116.97 0.00 0.00 0.00 114323.18 0.00 -11254.22 0.00 -27.91 0.00
PERIMETER_MID_ZN_2 04-JUN-09:52 0.00 0.00 0.00 -168386.49 0.00 0.00 235.18 384.90 4889.82 89307.63 0.00 0.00 73825.07 0.00 -0.00 0.00 -256.11 0.00
PERIMETER_MID_ZN_1 09-OCT-14:32 0.00 0.00 0.00 -184196.95 0.00 0.00 378.20 597.27 7587.84 113022.82 0.00 0.00 62842.86 0.00 -0.00 0.00 -232.04 0.00
PERIMETER_MID_ZN_4 13-AUG-18:11 0.00 0.00 0.00 -181640.03 0.00 0.00 0.00 384.90 4889.79 57815.78 0.00 897.71 117651.85 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 13-AUG-18:11 0.00 0.00 0.00 -16734.73 0.00 0.00 0.00 59.73 758.77 1736.86 0.00 242.34 13937.02 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 27-AUG-08:32 0.00 0.00 0.00 -16608.30 0.00 0.00 24.74 38.49 488.98 10691.30 0.00 0.00 5393.25 0.00 -0.00 0.00 -28.47 0.00
PERIMETER_TOP_ZN_1 09-OCT-14:02 0.00 0.00 0.00 -20155.24 0.00 0.00 38.31 59.73 758.78 12119.58 0.00 0.00 7207.60 0.00 -0.00 0.00 -28.76 0.00
PERIMETER_TOP_ZN_4 13-AUG-18:11 0.00 0.00 0.00 -19930.32 0.00 0.00 0.00 38.49 488.98 5705.57 0.00 93.14 13604.13 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 09-APR-18:13 0.00 0.00 0.00 -7880.62 0.00 0.00 0.00 22.51 7794.42 0.00 0.00 0.00 63.69 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 13-AUG-19:10 0.00 0.00 0.00 -73804.12 0.00 0.00 0.00 225.07 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -4365.17
DATACENTER_TOP_ZN_6 20-AUG-16:40 0.00 0.00 0.00 -7536.81 0.00 0.00 5.31 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -285.42
DATACENTER_BASEMENT_ZN_6 07-AUG-21:12 0.00 0.00 0.00 -369782.04 0.00 0.00 112.95 486.22 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10449.65
GROUNDFLOOR_PLENUM 17-JUL-05:13 0.00 -13652.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13659.21 0.00 -0.00 0.00 -6.78 0.00
MIDFLOOR_PLENUM 15-JUN-05:02 0.00 -82202.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83189.08 0.00 -0.00 0.00 -986.93 0.00
TOPFLOOR_PLENUM 07-JUL-15:10 0.00 -20542.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.65 20427.75 0.00 -0.00 0.00 0.00 0.00
Total Facility 26-AUG-05:02 0.00 -18338.69 0.00 -1888023.07 0.00 0.00 16051.57 29009.37 623236.89 0.00 0.00 0.00 1285528.66 0.00 -45241.56 0.00 -2223.18 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 08-JUL-16:01 0.00 0.00 25072.45 0.00 0.00 0.00 520.12 862.23 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -39912.34
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 09-JAN-05:11 0.00 0.00 399796.36 0.00 0.00 0.00 0.00 15486.81 80571.20 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -495854.37
CORE_TOP 09-JAN-04:01 0.00 0.00 74584.87 0.00 0.00 0.00 0.00 774.34 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -83416.33
PERIMETER_BOT_ZN_3 13-FEB-05:01 0.00 0.00 11472.84 0.00 0.00 0.00 0.00 194.45 1011.70 0.00 0.00 0.00 0.00 0.00 -5070.24 0.00 -1371.49 -6237.26
PERIMETER_BOT_ZN_2 13-FEB-05:01 0.00 0.00 9489.72 0.00 0.00 0.00 0.00 125.31 651.98 0.00 0.00 0.00 0.00 0.00 -3371.91 0.00 -915.03 -5980.06
PERIMETER_BOT_ZN_1 09-JAN-05:01 0.00 0.00 13858.54 0.00 0.00 0.00 0.00 194.46 1011.71 0.00 0.00 0.00 0.00 0.00 -3935.43 0.00 -875.72 -10253.56
PERIMETER_BOT_ZN_4 10-JAN-06:01 0.00 0.00 7176.02 0.00 0.00 0.00 94.15 125.31 651.97 0.00 0.00 0.00 0.00 0.00 -3206.95 0.00 -101.52 -4738.98
PERIMETER_MID_ZN_3 12-FEB-07:01 0.00 0.00 129901.99 0.00 0.00 0.00 893.96 972.26 7587.73 0.00 0.00 0.00 0.00 0.00 -56808.47 0.00 -36341.20 -46206.27
PERIMETER_MID_ZN_2 12-FEB-07:01 0.00 0.00 137107.77 0.00 0.00 0.00 576.23 626.56 4889.82 0.00 0.00 0.00 0.00 0.00 -36437.22 0.00 -24507.25 -82255.91
PERIMETER_MID_ZN_1 12-FEB-07:01 0.00 0.00 148556.00 0.00 0.00 0.00 885.62 972.28 7587.84 0.00 0.00 0.00 0.00 0.00 -55296.76 0.00 -36738.87 -65966.12
PERIMETER_MID_ZN_4 09-JAN-04:01 0.00 0.00 139699.76 0.00 0.00 0.00 0.00 626.56 6519.72 0.00 0.00 0.00 0.00 0.00 -24025.27 0.00 -11418.73 -111402.04
PERIMETER_TOP_ZN_3 12-FEB-05:12 0.00 0.00 16049.29 0.00 0.00 0.00 0.00 97.23 758.77 0.00 0.00 0.00 0.00 0.00 -5304.41 0.00 -4224.27 -7376.61
PERIMETER_TOP_ZN_2 12-FEB-05:12 0.00 0.00 15122.47 0.00 0.00 0.00 0.00 62.66 488.98 0.00 0.00 0.00 0.00 0.00 -3407.39 0.00 -2854.79 -9411.92
PERIMETER_TOP_ZN_1 12-FEB-05:12 0.00 0.00 17962.34 0.00 0.00 0.00 0.00 97.23 758.78 0.00 0.00 0.00 0.00 0.00 -5154.90 0.00 -4276.00 -9387.45
PERIMETER_TOP_ZN_4 12-FEB-05:12 0.00 0.00 16639.57 0.00 0.00 0.00 0.00 62.66 488.98 0.00 0.00 0.00 0.00 0.00 -3621.89 0.00 -2922.06 -10647.25
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 08-JAN-19:00 0.00 0.00 5272.90 0.00 0.00 0.00 0.00 225.07 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -24984.03
DATACENTER_TOP_ZN_6 15-JAN-18:35 0.00 0.00 573.77 0.00 0.00 0.00 0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2544.88
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 26-DEC-04:01 14257.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1796.27 -12461.05
MIDFLOOR_PLENUM 20-NOV-06:03 84145.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7295.85 -76849.79
TOPFLOOR_PLENUM 13-FEB-05:18 25213.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -4911.15 -20302.20
Total Facility 09-JAN-05:11 -87604.01 102653.05 1077871.22 -102653.05 0.00 0.00 0.00 29009.37 268362.69 0.00 0.00 0.00 0.00 0.00 -148542.44 0.00 -110491.04 -1028605.80



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 9.9515 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.1858 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 93.3307 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 85.4177 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 9.6507 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.2076 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.4042 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.4042 0.2221 1.0000 Not calculated 1.2002 0.2221    
AIRLOOP DATACENTER BASEMENT 22.0270 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 22.0272 0.0154 1.0000 Not calculated 0.3384 0.0154    
AIRLOOP DATACENTER BOT 0.4813 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4813 0.0325 1.0000 Not calculated 0.0156 0.0325    
AIRLOOP DATACENTER MID 4.5768 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5768 0.0342 1.0000 Not calculated 0.1563 0.0342    
AIRLOOP DATACENTER TOP 0.4638 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4638 0.0337 1.0000 Not calculated 0.0156 0.0337    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 4.9758 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.8067 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 46.6653 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 27.2461 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 4.8254 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.8032 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.4042 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.4042 1.0000 1.0000 Not calculated 1.2002 0.2221    
AIRLOOP DATACENTER BASEMENT 22.0270 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 22.0270 1.0000 1.0000 Not calculated 0.3384 0.0154    
AIRLOOP DATACENTER BOT 0.4813 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4813 1.0000 1.0000 Not calculated 0.0156 0.0325    
AIRLOOP DATACENTER MID 4.5768 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5768 1.0000 1.0000 Not calculated 0.1563 0.0342    
AIRLOOP DATACENTER TOP 0.4638 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4638 1.0000 1.0000 Not calculated 0.0156 0.0337    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4042 5.4042 5.4042 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7856 5.7856 1.9035 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 54.5119 54.5119 18.6431 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3902 5.3902 1.9081 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9482 0.9482 0.2390 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9251 0.9251 0.1850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0922 1.0922 0.2392 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2004 1.2004 0.2401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.9006 8.9006 2.3409 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.5165 9.5165 1.9033 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.3159 10.3159 2.3417 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.0859 10.0859 2.0172 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0245 1.0245 0.2397 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9778 0.9778 0.1956 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1589 1.1589 0.2399 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0994 1.0994 0.2199 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4813 0.4813 0.4813 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5768 4.5768 4.5768 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4638 0.4638 0.4638 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 22.0270 22.0270 22.0270 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 9.9515 9.1858 9.9515 2.8067 0.0000 1.0000
VAV_MID WITH REHEAT 93.3307 85.4177 93.3307 27.2461 0.0000 1.0000
VAV_TOP WITH REHEAT 9.6507 9.2076 9.6507 2.8032 0.0000 1.0000
CAV_BAS 5.4042 5.4042 5.4042 5.4042 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 22.0270 22.0272 22.0270 22.0270 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4813 0.4813 0.4813 0.4813 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5768 4.5768 4.5768 4.5768 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4638 0.4638 0.4638 0.4638 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4042 5.4042 5.4042 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8928 2.8928 1.9035 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 27.2559 27.2559 18.6431 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6951 2.6951 1.9081 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4741 0.4741 0.2390 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4626 0.4626 0.1850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5461 0.5461 0.2392 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6002 0.6002 0.2401 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.4503 4.4503 2.3409 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.7582 4.7582 1.9033 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1579 5.1579 2.3417 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0429 5.0429 2.0172 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5122 0.5122 0.2397 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4889 0.4889 0.1956 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5794 0.5794 0.2399 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5497 0.5497 0.2199 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4813 0.4813 0.4813 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5768 4.5768 4.5768 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4638 0.4638 0.4638 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 22.0270 22.0270 22.0270 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 4.9758 2.8067 2.8067 2.8067 0.0000 1.0000
VAV_MID WITH REHEAT 46.6653 27.2461 27.2461 27.2461 0.0000 1.0000
VAV_TOP WITH REHEAT 4.8254 2.8032 2.8032 2.8032 0.0000 1.0000
CAV_BAS 5.4042 5.4042 5.4042 5.4042 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 22.0270 22.0270 22.0270 22.0270 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4813 0.4813 0.4813 0.4813 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5768 4.5768 4.5768 4.5768 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4638 0.4638 0.4638 0.4638 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Atlanta-Hartsfield Jackson Intl AP GA USA TMY3 WMO#=722190
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 37.83
Number of hours cooling loads not met 539.83
Number of hours not met 577.50


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 497.66 1211803.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3987.01 440803.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2746.07 260952.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 447.43 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 59.77 3726.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2410.30 278556.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 773.81 69385.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1437.08 90905.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 8.95 5868.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 44.68 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 657.72 79719.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 28983.11
Natural Gas 0.00 1155.38
Additional 0.00 0.00
Total 15213.41 30138.49


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 59.28
Space Heating 0.00
Space Cooling 86.07
Fans (All) 52.04
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 625.71
Subtotal 625.71


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 10.74
Service Water Heating 14.20
Miscellaneous (All) 24.94
Subtotal 24.94


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 9.11
Space Heating 1.65
Space Cooling 13.23
Fans (All) 8.00
Service Water Heating 2.18
Receptacle Equipment 50.48
Miscellaneous 15.35


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2393. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8118.17 641.83 0.00 0.00 0.00
CORE_BOTTOM 8697.50 62.50 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8754.00 6.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8736.33 23.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8681.50 78.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8679.33 80.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7984.00 776.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8731.67 28.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8580.00 180.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8626.00 134.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8262.83 497.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8681.50 78.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8520.33 239.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8559.17 200.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8264.33 495.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6781.67 1978.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6760.17 1999.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6743.17 2016.83 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 6629.33 2130.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8574.50 185.50 0.00 0.00 0.00
Min 6629.33 0.00 0.00 0.00 0.00
Max 8760.00 2130.67 0.00 0.00 0.00
Average 8245.46 514.54 0.00 0.00 0.00
Sum 189645.50 11834.50 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 366643.17 1972.83 0.00 0.00 0.00
CORE_BOTTOM 330704.00 109.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330809.00 4.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1243.83 1024.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1232.33 1035.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1225.50 1042.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 61466.00 41929.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 366643.17 41929.00 0.00 0.00 0.00
Average 78286.34 2048.57 0.00 0.00 0.00
Sum 1800585.83 47117.17 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 6272.33 2487.67 0.00 0.00 0.00
CORE_BOTTOM 7615.33 1144.67 0.00 0.00 0.00
CORE_MID 7516.00 1244.00 0.00 0.00 0.00
CORE_TOP 7578.67 1181.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 7452.00 1308.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 7714.17 1045.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7375.33 1384.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7011.67 1748.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 7407.00 1353.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 7357.67 1402.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 7303.17 1456.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7245.83 1514.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 7439.00 1321.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 7386.67 1373.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 7339.33 1420.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7286.33 1473.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7393.17 1366.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7364.50 1395.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7336.67 1423.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7469.17 1290.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 7166.50 1593.50 0.00 0.00 0.00
MIDFLOOR_PLENUM 7223.83 1536.17 0.00 0.00 0.00
TOPFLOOR_PLENUM 6405.83 2354.17 0.00 0.00 0.00
Min 6272.33 1045.83 0.00 0.00 0.00
Max 7714.17 2487.67 0.00 0.00 0.00
Average 7289.57 1470.43 0.00 0.00 0.00
Sum 167660.17 33819.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 341944.83 26671.17 0.00 0.00 0.00
CORE_BOTTOM 328657.33 2155.67 0.00 0.00 0.00
CORE_MID 328585.00 2228.00 0.00 0.00 0.00
CORE_TOP 328681.33 2131.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38917.33 7.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18350.67 3.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38918.83 6.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24907.17 1.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38915.17 9.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24904.67 4.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38916.83 8.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24906.50 2.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1475.17 792.83 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1458.17 809.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1446.00 822.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 75822.83 27572.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 341944.83 27572.17 0.00 0.00 0.00
Average 77585.91 2749.01 0.00 0.00 0.00
Sum 1784475.83 63227.17 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:13

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3A

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_GA_ATLANTA

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 3.965
February 7.937
March 13.764
April 17.213
May 20.837
June 24.797
July 26.063
August 26.547
September 22.525
October 16.026
November 11.940
December 7.696
   
Annual Sum or Average 16.653
Minimum of Months 3.965
Maximum of Months 26.547



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.428414E+11 102961.10 02-JAN-04:01 3.30 2.57 0.564020E+10 7499.15 31-JAN-10:39 13.30 11.14
February 0.400404E+11 104385.79 21-FEB-04:03 6.70 4.44 0.512828E+10 7499.16 28-FEB-14:20 25.00 13.71
March 0.510053E+11 101571.86 13-MAR-03:02 7.70 3.23 0.612948E+10 7499.45 08-MAR-10:20 7.70 3.23
April 0.462189E+11 96045.81 06-APR-04:02 0.92 -0.5 0.544499E+10 7499.26 03-APR-09:20 0.92 -0.5
May 0.506604E+11 99277.75 15-MAY-03:02 12.80 11.19 0.589848E+10 7499.38 11-MAY-09:00 12.80 11.19
June 0.548251E+11 95028.93 08-JUN-04:03 11.70 8.74 0.588040E+10 7499.07 09-JUN-13:20 29.60 18.61
July 0.564342E+11 84179.44 03-JUL-03:02 17.80 16.72 0.547241E+10 7498.78 27-JUL-09:20 21.10 20.75
August 0.646541E+11 78594.81 27-AUG-16:51 31.10 21.22 0.613818E+10 7499.01 25-AUG-09:50 31.10 21.22
September 0.586129E+11 93178.94 29-SEP-04:03 11.78 11.10 0.545312E+10 7499.15 20-SEP-13:20 11.78 11.10
October 0.601060E+11 101428.04 30-OCT-03:13 8.90 8.90 0.567091E+10 7498.96 31-OCT-09:50 10.13 8.85
November 0.582472E+11 103725.94 06-NOV-04:02 10.92 10.30 0.561490E+10 7499.35 16-NOV-10:20 10.77 10.06
December 0.532616E+11 105405.35 18-DEC-04:01 -4.1 -6.3 0.546883E+10 7499.18 12-DEC-10:20 -4.1 -6.3
                     
Annual Sum or Average 0.636907E+12         0.679402E+11        
Minimum of Months 0.400404E+11 78594.81   -4.1 -6.3 0.512828E+10 7498.78   -4.1 -6.3
Maximum of Months 0.646541E+11 105405.35   31.10 21.22 0.613818E+10 7499.45   31.10 21.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.335762E+11 86128.40 02-JAN-04:01 3.30 2.57 0.503771E+10 6752.42 17-JAN-14:50 4.40 4.12
February 0.360898E+11 85071.83 21-FEB-04:03 6.70 4.44 0.458938E+10 6742.33 09-FEB-10:30 6.70 4.44
March 0.534466E+11 86172.70 13-MAR-03:02 7.70 3.23 0.549951E+10 6735.20 08-MAR-10:09 7.70 3.23
April 0.574755E+11 84808.72 04-APR-03:02 15.10 14.40 0.488131E+10 6807.72 18-APR-13:00 27.20 15.86
May 0.534770E+11 86849.23 08-MAY-03:02 16.78 16.47 0.528703E+10 6795.22 18-MAY-13:39 28.50 18.22
June 0.617286E+11 83375.16 06-JUN-03:02 19.32 15.31 0.526836E+10 6734.83 09-JUN-09:00 24.40 15.46
July 0.673693E+11 83743.10 29-JUL-03:02 17.70 17.43 0.489318E+10 6734.60 17-JUL-09:00 17.70 17.43
August 0.759122E+11 81980.62 14-AUG-05:05 23.30 20.62 0.549302E+10 6734.58 28-AUG-13:20 28.30 22.11
September 0.538950E+11 89365.34 18-SEP-03:02 15.00 14.25 0.488401E+10 6734.82 22-SEP-13:39 26.50 17.31
October 0.522887E+11 91731.20 10-OCT-03:03 16.10 15.06 0.508000E+10 6734.70 30-OCT-09:00 11.10 11.10
November 0.495428E+11 90065.63 06-NOV-04:02 10.92 10.30 0.503114E+10 6735.02 16-NOV-10:09 10.68 10.03
December 0.450498E+11 88011.33 26-DEC-04:01 3.90 2.94 0.490234E+10 6746.97 01-DEC-10:09 3.90 2.94
                     
Annual Sum or Average 0.639852E+12         0.608470E+11        
Minimum of Months 0.335762E+11 81980.62   3.30 2.57 0.458938E+10 6734.58   3.90 2.94
Maximum of Months 0.759122E+11 91731.20   23.30 20.62 0.549951E+10 6807.72   28.50 22.11



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.231119E+11 25816.36 31-JAN-17:00 19.40 13.37 0.462030E+10 6734.64 31-JAN-10:00 19.40 13.37
February 0.248811E+11 75590.28 28-FEB-06:02 10.78 5.86 0.436862E+10 6734.77 22-FEB-14:09 10.78 5.86
March 0.376443E+11 77551.76 31-MAR-04:03 17.12 14.83 0.546577E+10 6735.12 08-MAR-10:09 17.12 14.83
April 0.390141E+11 77995.79 20-APR-04:03 14.32 13.08 0.486946E+10 6734.86 12-APR-13:39 14.32 13.08
May 0.458597E+11 79382.06 31-MAY-03:02 20.92 19.80 0.528138E+10 6827.25 16-MAY-13:00 20.92 19.80
June 0.495005E+11 79524.98 20-JUN-03:02 20.40 19.67 0.526663E+10 6736.60 02-JUN-13:50 20.40 19.67
July 0.496790E+11 78404.63 11-JUL-03:02 20.50 19.77 0.489261E+10 6734.59 05-JUL-09:20 20.50 19.77
August 0.534289E+11 76432.33 22-AUG-03:02 23.80 22.15 0.549417E+10 6734.73 25-AUG-13:09 30.18 18.86
September 0.445613E+11 79574.33 18-SEP-03:02 15.00 14.25 0.487711E+10 6734.81 22-SEP-13:50 26.60 17.45
October 0.380621E+11 78258.10 11-OCT-04:03 17.07 15.56 0.505252E+10 6734.67 31-OCT-09:20 8.73 8.05
November 0.317745E+11 77098.65 03-NOV-05:02 13.90 12.93 0.497849E+10 6738.18 20-NOV-14:09 5.50 2.47
December 0.262454E+11 74395.19 13-DEC-06:02 16.70 15.65 0.471184E+10 6734.85 11-DEC-10:00 16.70 15.65
                     
Annual Sum or Average 0.463763E+12         0.598789E+11        
Minimum of Months 0.231119E+11 25816.36   10.78 5.86 0.436862E+10 6734.59   5.50 2.47
Maximum of Months 0.534289E+11 79574.33   23.80 22.15 0.549417E+10 6827.25   30.18 19.80



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.171183E+11 25138.78 20-JAN-17:00 16.70 11.48 0.411502E+10 6734.21 20-JAN-14:00 16.70 11.48
February 0.195493E+11 34665.89 28-FEB-17:00 23.90 12.94 0.400764E+10 6734.73 22-FEB-14:00 23.90 12.94
March 0.314148E+11 73752.34 29-MAR-05:03 17.70 15.66 0.528519E+10 6734.71 13-MAR-13:00 17.70 15.66
April 0.357104E+11 76069.56 21-APR-05:02 15.50 14.28 0.480405E+10 6734.86 12-APR-13:39 15.50 14.28
May 0.462819E+11 79367.45 22-MAY-03:02 17.70 16.67 0.527093E+10 6890.87 19-MAY-13:30 17.70 16.67
June 0.531960E+11 80446.68 19-JUN-03:02 20.60 19.79 0.526698E+10 6734.78 09-JUN-09:00 20.60 19.79
July 0.546778E+11 78790.82 11-JUL-03:02 20.50 19.77 0.489416E+10 6734.51 27-JUL-09:09 21.10 20.75
August 0.584299E+11 77449.51 11-AUG-03:02 22.88 22.07 0.549686E+10 6734.64 25-AUG-13:09 30.18 18.86
September 0.438339E+11 79313.24 05-SEP-03:02 22.02 20.50 0.486495E+10 6734.78 22-SEP-13:00 26.70 17.59
October 0.324204E+11 77038.49 19-OCT-04:03 21.60 21.60 0.491032E+10 6734.70 16-OCT-09:09 21.60 21.60
November 0.241586E+11 69767.84 04-NOV-05:03 16.60 15.28 0.465053E+10 6734.67 02-NOV-09:00 16.60 15.28
December 0.202048E+11 50927.27 13-DEC-06:02 16.70 15.65 0.418788E+10 6734.51 13-DEC-10:09 18.48 16.98
                     
Annual Sum or Average 0.436996E+12         0.577545E+11        
Minimum of Months 0.171183E+11 25138.78   15.50 11.48 0.400764E+10 6734.21   15.50 11.48
Maximum of Months 0.584299E+11 80446.68   23.90 22.07 0.549686E+10 6890.87   30.18 21.60



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.209913E+10 3453.45 31-JAN-14:50 21.02 13.03 0.531939E+09 845.60 19-JAN-14:09 21.02 13.03
February 0.274060E+10 5685.65 28-FEB-15:00 25.00 13.71 0.515485E+09 845.64 22-FEB-14:09 25.00 13.71
March 0.498392E+10 7062.26 30-MAR-14:00 27.80 17.87 0.674943E+09 845.65 08-MAR-10:30 27.80 17.87
April 0.656176E+10 11162.32 03-APR-05:02 17.75 16.94 0.607153E+09 856.94 18-APR-13:00 27.20 15.86
May 0.750984E+10 11368.36 30-MAY-05:02 18.68 17.36 0.662889E+09 855.31 18-MAY-13:39 18.68 17.36
June 0.104125E+11 15469.13 25-JUN-16:41 32.88 22.29 0.662148E+09 845.64 02-JUN-13:00 32.88 22.29
July 0.114593E+11 14551.64 16-JUL-13:43 33.62 23.40 0.615692E+09 845.79 17-JUL-13:39 29.40 21.87
August 0.125972E+11 13469.10 06-AUG-16:21 32.50 23.58 0.690706E+09 846.10 10-AUG-13:39 30.77 23.76
September 0.728293E+10 11336.78 01-SEP-05:02 20.60 18.65 0.612324E+09 845.65 22-SEP-13:39 26.50 17.31
October 0.515354E+10 11230.63 02-OCT-05:03 18.22 18.22 0.626135E+09 845.61 16-OCT-13:00 25.00 19.11
November 0.395247E+10 5382.37 02-NOV-14:00 23.30 17.05 0.608980E+09 845.63 16-NOV-10:50 11.02 10.17
December 0.314841E+10 5182.40 13-DEC-12:00 20.00 17.41 0.568263E+09 845.63 11-DEC-10:00 20.00 17.41
                     
Annual Sum or Average 0.779016E+11         0.737666E+10        
Minimum of Months 0.209913E+10 3453.45   17.75 13.03 0.515485E+09 845.60   11.02 10.17
Maximum of Months 0.125972E+11 15469.13   33.62 23.58 0.690706E+09 856.94   32.88 23.76



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.168760E+10 2586.66 31-JAN-10:30 12.75 10.76 0.351276E+09 544.95 31-JAN-10:00 14.40 11.88
February 0.231251E+10 6198.65 27-FEB-09:40 12.23 5.46 0.336225E+09 545.48 09-FEB-10:30 12.23 5.46
March 0.407462E+10 7061.44 14-MAR-09:30 16.95 13.93 0.434497E+09 545.00 08-MAR-10:09 16.95 13.93
April 0.547242E+10 10859.30 16-APR-09:43 22.02 14.52 0.391693E+09 551.80 18-APR-13:00 27.20 15.86
May 0.653177E+10 11143.49 29-MAY-09:53 25.00 20.02 0.427548E+09 549.05 18-MAY-13:39 25.00 20.02
June 0.832504E+10 16108.83 04-JUN-09:02 24.78 18.48 0.426873E+09 545.25 05-JUN-09:00 28.90 20.65
July 0.893448E+10 15687.28 04-JUL-09:32 26.47 23.26 0.396771E+09 546.02 17-JUL-09:50 27.52 21.93
August 0.928831E+10 16101.28 27-AUG-09:42 26.83 21.78 0.445060E+09 545.63 14-AUG-09:50 26.83 21.78
September 0.615446E+10 15693.83 04-SEP-09:32 26.13 22.05 0.394375E+09 545.73 11-SEP-09:00 25.00 22.21
October 0.433241E+10 9466.10 09-OCT-09:43 22.02 17.20 0.403173E+09 544.95 05-OCT-09:00 22.02 17.20
November 0.300567E+10 5840.79 06-NOV-09:30 13.30 11.71 0.393121E+09 544.96 06-NOV-10:09 14.87 12.62
December 0.231859E+10 3293.43 12-DEC-11:10 18.68 15.65 0.366224E+09 544.97 11-DEC-10:00 18.68 15.65
                     
Annual Sum or Average 0.624379E+11         0.476684E+10        
Minimum of Months 0.168760E+10 2586.66   12.23 5.46 0.336225E+09 544.95   12.23 5.46
Maximum of Months 0.928831E+10 16108.83   26.83 23.26 0.445060E+09 551.80   28.90 22.21



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.344029E+10 8679.87 27-JAN-14:20 3.17 -2.2 0.573275E+09 847.52 26-JAN-14:00 3.17 -2.2
February 0.446382E+10 18475.68 26-FEB-14:13 24.60 12.61 0.535831E+09 848.16 21-FEB-14:39 24.60 12.61
March 0.742602E+10 13535.02 30-MAR-13:30 27.25 18.02 0.678162E+09 847.03 30-MAR-13:00 27.80 17.87
April 0.825081E+10 18090.85 16-APR-13:43 28.80 16.16 0.607816E+09 878.90 11-APR-13:20 28.80 16.16
May 0.827022E+10 13254.94 30-MAY-03:02 20.00 17.77 0.662613E+09 864.14 18-MAY-13:39 20.00 17.77
June 0.105893E+11 17922.27 25-JUN-16:41 32.88 22.29 0.662072E+09 845.67 02-JUN-13:00 32.88 22.29
July 0.118446E+11 17280.68 23-JUL-16:51 30.00 23.22 0.615877E+09 846.11 31-JUL-13:00 30.60 24.81
August 0.142758E+11 18320.62 27-AUG-13:02 31.70 22.66 0.691202E+09 846.60 28-AUG-13:20 28.30 22.11
September 0.969906E+10 18634.72 24-SEP-13:43 28.40 19.81 0.613088E+09 846.50 08-SEP-13:39 28.40 19.81
October 0.863198E+10 19346.07 09-OCT-14:22 27.50 19.51 0.628847E+09 871.95 10-OCT-13:50 29.22 21.00
November 0.672317E+10 18877.28 11-NOV-13:53 21.10 11.67 0.619726E+09 851.61 06-NOV-14:09 21.10 11.67
December 0.539937E+10 16228.73 10-DEC-13:33 16.33 7.80 0.587574E+09 846.25 12-DEC-14:20 22.80 16.78
                     
Annual Sum or Average 0.990144E+11         0.747608E+10        
Minimum of Months 0.344029E+10 8679.87   3.17 -2.2 0.535831E+09 845.67   3.17 -2.2
Maximum of Months 0.142758E+11 19346.07   32.88 23.22 0.691202E+09 878.90   32.88 24.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.270781E+10 4678.72 20-JAN-16:30 16.95 12.13 0.362087E+09 544.94 30-JAN-14:00 16.70 10.51
February 0.374079E+10 13195.60 26-FEB-15:32 24.60 12.48 0.352499E+09 544.96 22-FEB-14:09 24.60 12.48
March 0.763906E+10 18083.82 19-MAR-15:53 16.70 6.23 0.444755E+09 544.99 08-MAR-10:09 16.70 6.23
April 0.102040E+11 20225.21 09-APR-16:42 21.70 10.75 0.396413E+09 555.01 18-APR-13:00 27.20 15.86
May 0.836896E+10 20719.33 21-MAY-17:32 25.97 19.50 0.428539E+09 549.96 18-MAY-13:39 25.97 19.50
June 0.114904E+11 21889.36 25-JUN-16:01 33.22 22.10 0.427718E+09 544.97 02-JUN-13:00 33.22 22.10
July 0.133741E+11 22284.82 23-JUL-16:51 30.00 23.22 0.397916E+09 544.95 17-JUL-09:00 30.00 23.22
August 0.160750E+11 21455.09 13-AUG-16:22 30.55 22.29 0.446402E+09 544.95 10-AUG-13:39 30.55 22.29
September 0.805917E+10 17542.70 03-SEP-15:23 29.70 23.13 0.395884E+09 544.98 22-SEP-13:39 26.50 17.31
October 0.676156E+10 19826.44 09-OCT-14:22 27.50 19.51 0.410170E+09 544.95 16-OCT-13:00 25.00 19.11
November 0.580985E+10 17288.15 05-NOV-15:43 24.32 18.04 0.404851E+09 544.98 16-NOV-10:09 10.68 10.03
December 0.500864E+10 16122.85 13-DEC-06:02 16.70 15.65 0.392650E+09 544.97 11-DEC-10:00 16.70 15.65
                     
Annual Sum or Average 0.992392E+11         0.485989E+10        
Minimum of Months 0.270781E+10 4678.72   16.70 6.23 0.352499E+09 544.94   10.68 6.23
Maximum of Months 0.160750E+11 22284.82   33.22 23.22 0.446402E+09 555.01   33.22 23.22



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.581279E+09 2132.60 31-JAN-17:00 19.40 13.37 0.476834E+09 785.37 31-JAN-14:00 19.40 13.37
February 0.129550E+10 3977.20 28-FEB-15:00 25.00 13.71 0.458297E+09 845.61 28-FEB-14:09 25.00 13.71
March 0.320369E+10 6102.55 30-MAR-16:00 27.80 17.47 0.623648E+09 845.61 27-MAR-13:00 27.80 17.47
April 0.409482E+10 7440.48 12-APR-15:15 28.13 16.55 0.587031E+09 845.64 12-APR-13:39 28.13 16.55
May 0.624750E+10 10574.97 30-MAY-05:02 18.68 17.36 0.659010E+09 858.49 16-MAY-13:00 18.68 17.36
June 0.868667E+10 10845.21 01-JUN-05:02 19.32 17.90 0.661743E+09 850.95 02-JUN-13:50 27.33 17.19
July 0.907706E+10 11622.74 17-JUL-05:02 21.70 19.38 0.615529E+09 845.61 05-JUL-09:20 21.70 19.38
August 0.949987E+10 11596.57 10-AUG-03:02 24.82 22.64 0.690925E+09 845.63 25-AUG-13:09 30.18 18.86
September 0.591520E+10 10670.95 01-SEP-05:02 20.60 18.65 0.608947E+09 845.64 22-SEP-13:50 26.60 17.45
October 0.356815E+10 9589.13 19-OCT-05:03 20.92 20.92 0.587840E+09 845.61 05-OCT-13:09 20.92 20.92
November 0.225961E+10 3540.01 03-NOV-14:00 21.70 17.40 0.539656E+09 845.61 03-NOV-13:30 21.70 17.40
December 0.127134E+10 2772.18 13-DEC-13:20 19.83 17.21 0.479704E+09 845.60 13-DEC-14:09 18.30 16.86
                     
Annual Sum or Average 0.557007E+11         0.698916E+10        
Minimum of Months 0.581279E+09 2132.60   18.68 13.37 0.458297E+09 785.37   18.30 13.37
Maximum of Months 0.949987E+10 11622.74   28.13 22.64 0.690925E+09 858.49   30.18 20.92



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.688171E+09 1715.35 31-JAN-17:00 19.40 13.37 0.226970E+09 483.76 31-JAN-16:00 19.40 13.37
February 0.129456E+10 4471.64 27-FEB-10:00 12.80 5.65 0.223820E+09 521.21 28-FEB-11:09 20.87 12.02
March 0.302851E+10 5551.73 14-MAR-10:10 18.27 14.61 0.304713E+09 521.22 08-MAR-09:00 18.27 14.61
April 0.430651E+10 9798.36 16-APR-11:23 26.65 15.57 0.284855E+09 533.28 12-APR-15:20 26.65 15.57
May 0.604432E+10 16079.79 07-MAY-09:43 24.72 19.90 0.313284E+09 532.00 15-MAY-14:09 28.30 17.25
June 0.777717E+10 16842.28 04-JUN-09:52 26.70 19.39 0.313912E+09 533.75 02-JUN-14:09 26.70 19.39
July 0.812638E+10 16119.88 23-JUL-08:23 25.30 22.43 0.292887E+09 521.71 07-JUL-10:00 25.30 22.43
August 0.827716E+10 16246.05 27-AUG-08:32 24.27 21.30 0.327622E+09 521.82 01-AUG-10:50 24.27 21.30
September 0.559747E+10 15860.22 04-SEP-09:23 25.85 21.92 0.288734E+09 524.47 14-SEP-15:20 25.93 14.94
October 0.343022E+10 6644.26 11-OCT-10:10 23.27 19.04 0.283972E+09 521.21 05-OCT-12:09 23.27 19.04
November 0.204760E+10 3888.99 06-NOV-09:50 14.03 12.24 0.263305E+09 521.21 02-NOV-10:20 14.03 12.24
December 0.126172E+10 2206.56 13-DEC-06:02 16.70 15.65 0.231790E+09 516.31 13-DEC-13:39 19.07 17.05
                     
Annual Sum or Average 0.518798E+11         0.335587E+10        
Minimum of Months 0.688171E+09 1715.35   12.80 5.65 0.223820E+09 483.76   14.03 12.02
Maximum of Months 0.827716E+10 16842.28   26.70 22.43 0.327622E+09 533.75   28.30 22.43



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243258E+10 8375.01 27-JAN-14:50 3.72 -1.9 0.542281E+09 845.63 24-JAN-14:09 3.72 -1.9
February 0.330964E+10 16980.77 26-FEB-13:03 23.98 12.59 0.507754E+09 847.20 21-FEB-14:39 23.98 12.59
March 0.575725E+10 13062.67 30-MAR-14:30 27.80 17.47 0.659914E+09 846.77 30-MAR-13:00 27.80 17.47
April 0.596751E+10 14221.80 16-APR-13:23 28.60 16.10 0.599068E+09 870.38 17-APR-13:00 28.90 16.63
May 0.719390E+10 12404.48 30-MAY-05:02 18.68 17.36 0.659975E+09 870.72 16-MAY-13:00 18.68 17.36
June 0.892025E+10 12099.34 26-JUN-05:02 23.30 21.67 0.661559E+09 852.25 02-JUN-13:50 23.30 21.67
July 0.951494E+10 15425.73 09-JUL-14:13 33.17 23.50 0.615791E+09 845.69 14-JUL-13:00 34.40 24.06
August 0.113116E+11 16980.64 13-AUG-15:31 30.20 22.22 0.691605E+09 869.31 25-AUG-13:00 31.10 18.60
September 0.866575E+10 17197.79 24-SEP-12:03 28.40 19.81 0.611511E+09 863.83 22-SEP-13:39 28.40 19.81
October 0.731507E+10 18419.53 09-OCT-14:32 27.60 19.53 0.616599E+09 879.93 10-OCT-13:50 29.22 21.00
November 0.522747E+10 17806.27 11-NOV-13:53 21.10 11.67 0.600570E+09 852.65 06-NOV-14:20 21.10 11.67
December 0.379596E+10 14720.34 10-DEC-14:23 17.50 8.24 0.554630E+09 849.51 19-DEC-10:50 6.73 1.51
                     
Annual Sum or Average 0.794119E+11         0.732125E+10        
Minimum of Months 0.243258E+10 8375.01   3.72 -1.9 0.507754E+09 845.63   3.72 -1.9
Maximum of Months 0.113116E+11 18419.53   33.17 23.50 0.691605E+09 879.93   34.40 24.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.884611E+09 2182.46 20-JAN-16:30 16.95 12.13 0.315899E+09 521.16 20-JAN-16:40 16.87 11.91
February 0.154236E+10 6525.21 27-FEB-17:00 22.20 11.44 0.304385E+09 544.96 22-FEB-14:09 22.20 11.44
March 0.364572E+10 8942.01 30-MAR-16:00 27.80 17.47 0.411898E+09 544.95 13-MAR-13:00 27.80 17.47
April 0.474615E+10 16655.80 09-APR-17:11 21.50 10.93 0.383784E+09 544.97 12-APR-13:39 28.53 16.91
May 0.621404E+10 16536.61 21-MAY-18:23 24.75 19.04 0.425686E+09 556.56 16-MAY-13:00 24.75 19.04
June 0.792415E+10 18089.17 04-JUN-16:32 31.50 19.59 0.426907E+09 545.17 02-JUN-13:50 31.50 19.59
July 0.836671E+10 18121.22 02-JUL-17:32 30.60 22.04 0.397187E+09 544.94 05-JUL-09:20 28.87 23.62
August 0.900043E+10 18170.86 13-AUG-18:11 30.73 21.88 0.445966E+09 544.95 25-AUG-13:09 30.18 18.86
September 0.579110E+10 17201.80 04-SEP-16:42 28.22 22.25 0.393019E+09 544.97 22-SEP-13:50 26.60 17.45
October 0.374446E+10 14644.98 09-OCT-16:33 27.07 19.44 0.384861E+09 544.94 16-OCT-13:00 25.00 19.11
November 0.241309E+10 6113.67 06-NOV-16:00 20.60 10.48 0.359992E+09 544.94 03-NOV-13:30 20.60 10.48
December 0.155550E+10 3389.93 11-DEC-15:40 21.10 15.44 0.322673E+09 544.94 13-DEC-14:09 18.30 16.86
                     
Annual Sum or Average 0.558283E+11         0.457226E+10        
Minimum of Months 0.884611E+09 2182.46   16.95 10.48 0.304385E+09 521.16   16.87 10.48
Maximum of Months 0.900043E+10 18170.86   31.50 22.25 0.445966E+09 556.56   31.50 23.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.333101E+09 2143.19 20-JAN-17:00 16.70 11.48 0.470306E+09 767.99 20-JAN-14:00 16.70 11.48
February 0.880647E+09 3451.77 28-FEB-15:30 24.15 13.12 0.444999E+09 845.61 28-FEB-14:09 24.15 13.12
March 0.266054E+10 6772.29 30-MAR-15:50 27.80 17.41 0.590365E+09 845.60 28-MAR-13:09 27.80 17.41
April 0.381009E+10 6984.35 19-APR-14:30 26.15 17.54 0.568784E+09 845.64 12-APR-13:39 26.15 17.54
May 0.633230E+10 11986.70 30-MAY-05:02 18.68 17.36 0.653248E+09 845.65 19-MAY-13:39 18.68 17.36
June 0.926735E+10 14485.39 25-JUN-16:52 32.80 22.34 0.661076E+09 845.63 02-JUN-13:09 32.80 22.34
July 0.987233E+10 16590.94 09-JUL-14:13 33.17 23.50 0.615442E+09 845.60 03-JUL-13:20 33.17 23.50
August 0.102661E+11 16738.18 13-AUG-18:11 30.73 21.88 0.691077E+09 845.62 25-AUG-13:09 30.18 18.86
September 0.588151E+10 12100.42 06-SEP-05:03 21.20 20.02 0.603454E+09 845.64 22-SEP-13:00 26.70 17.59
October 0.297278E+10 8020.35 19-OCT-05:03 20.92 20.92 0.560384E+09 845.60 05-OCT-13:50 20.92 20.92
November 0.159378E+10 3121.82 03-NOV-15:00 21.70 17.40 0.504182E+09 845.61 03-NOV-13:50 21.70 17.40
December 0.677267E+09 2375.37 13-DEC-15:10 18.12 16.87 0.462040E+09 837.12 13-DEC-14:00 18.12 16.87
                     
Annual Sum or Average 0.545478E+11         0.682536E+10        
Minimum of Months 0.333101E+09 2143.19   16.70 11.48 0.444999E+09 767.99   16.70 11.48
Maximum of Months 0.102661E+11 16738.18   33.17 23.50 0.691077E+09 845.65   33.17 23.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.376502E+09 1686.57 31-JAN-17:00 19.40 13.37 0.303809E+09 484.24 31-JAN-14:00 19.40 13.37
February 0.968664E+09 3319.31 28-FEB-15:00 25.00 13.71 0.297963E+09 544.95 28-FEB-10:00 25.00 13.71
March 0.261145E+10 5321.96 30-MAR-11:00 22.20 17.83 0.403301E+09 544.99 08-MAR-10:09 22.20 17.83
April 0.411600E+10 9640.22 16-APR-11:13 26.47 15.53 0.383404E+09 544.97 17-APR-13:20 28.17 16.82
May 0.625411E+10 16443.57 07-MAY-09:13 23.87 19.51 0.424652E+09 545.12 30-MAY-09:00 27.80 21.16
June 0.839278E+10 16378.97 11-JUN-09:53 25.00 14.66 0.426965E+09 545.20 05-JUN-09:00 25.00 14.66
July 0.890897E+10 16581.29 02-JUL-10:23 26.65 22.35 0.396949E+09 545.34 21-JUL-09:50 29.82 23.54
August 0.904661E+10 16614.86 27-AUG-08:32 24.27 21.30 0.445758E+09 545.27 07-AUG-09:00 24.27 21.30
September 0.574062E+10 15582.24 04-SEP-09:23 25.85 21.92 0.390342E+09 545.35 08-SEP-09:00 27.20 22.45
October 0.300401E+10 6362.27 11-OCT-10:20 23.73 19.29 0.377158E+09 544.95 04-OCT-13:00 23.73 19.29
November 0.156489E+10 2548.23 02-NOV-15:10 22.70 16.39 0.337108E+09 544.95 06-NOV-10:09 14.87 12.62
December 0.762201E+09 1886.41 13-DEC-15:10 18.12 16.87 0.301860E+09 529.10 13-DEC-14:00 18.12 16.87
                     
Annual Sum or Average 0.517468E+11         0.448927E+10        
Minimum of Months 0.376502E+09 1686.57   18.12 13.37 0.297963E+09 484.24   14.87 12.62
Maximum of Months 0.904661E+10 16614.86   26.65 22.35 0.445758E+09 545.35   29.82 23.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.167760E+10 6855.86 11-JAN-14:50 6.70 2.05 0.522807E+09 845.63 05-JAN-14:00 6.70 2.05
February 0.251399E+10 13060.01 21-FEB-14:30 22.25 10.82 0.490561E+09 845.68 21-FEB-14:50 22.62 11.12
March 0.487874E+10 13549.21 30-MAR-13:50 27.62 17.92 0.634238E+09 845.74 30-MAR-13:00 27.80 17.87
April 0.560432E+10 14032.63 17-APR-14:20 28.90 16.56 0.585198E+09 863.27 17-APR-13:09 28.90 16.56
May 0.731307E+10 14536.57 30-MAY-05:02 18.68 17.36 0.654891E+09 856.43 19-MAY-13:30 18.68 17.36
June 0.953171E+10 15318.54 25-JUN-16:12 33.13 22.15 0.660565E+09 845.66 02-JUN-13:09 33.13 22.15
July 0.103498E+11 19094.98 09-JUL-14:13 33.17 23.50 0.615636E+09 845.63 14-JUL-13:00 34.40 24.06
August 0.122061E+11 19227.61 13-AUG-18:11 30.73 21.88 0.691713E+09 869.70 25-AUG-13:50 30.92 18.65
September 0.871726E+10 20016.81 24-SEP-14:23 28.60 20.22 0.607799E+09 846.46 08-SEP-13:39 28.60 20.22
October 0.646556E+10 20155.04 09-OCT-14:02 27.30 19.46 0.598774E+09 855.81 10-OCT-13:50 29.22 21.00
November 0.402869E+10 13458.95 06-NOV-14:10 20.60 11.29 0.569252E+09 845.85 07-NOV-14:50 18.80 8.66
December 0.262690E+10 9459.62 12-DEC-13:50 22.52 17.00 0.527650E+09 845.62 11-DEC-14:09 22.52 17.00
                     
Annual Sum or Average 0.759137E+11         0.715909E+10        
Minimum of Months 0.167760E+10 6855.86   6.70 2.05 0.490561E+09 845.62   6.70 2.05
Maximum of Months 0.122061E+11 20155.04   33.17 23.50 0.691713E+09 869.70   34.40 24.06



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.641656E+09 2161.59 20-JAN-16:40 16.87 11.91 0.308159E+09 516.40 20-JAN-16:49 16.78 11.69
February 0.122994E+10 6220.83 27-FEB-17:00 22.20 11.44 0.294300E+09 544.95 28-FEB-14:09 25.00 13.72
March 0.324864E+10 9425.26 30-MAR-16:00 27.80 17.47 0.391316E+09 544.94 27-MAR-13:00 27.80 17.47
April 0.457570E+10 18237.77 09-APR-17:03 21.60 10.86 0.372710E+09 544.97 12-APR-13:39 28.53 16.91
May 0.637432E+10 19119.27 21-MAY-17:32 25.97 19.50 0.421590E+09 544.97 19-MAY-13:50 25.97 19.50
June 0.840775E+10 19630.62 11-JUN-17:12 32.20 20.99 0.426175E+09 544.96 02-JUN-13:09 32.20 20.99
July 0.904617E+10 18835.56 09-JUL-16:52 33.30 22.74 0.396953E+09 544.94 05-JUL-13:09 33.30 22.74
August 0.966412E+10 19938.20 13-AUG-18:11 30.73 21.88 0.445959E+09 544.95 25-AUG-13:09 30.18 18.86
September 0.586664E+10 18700.16 04-SEP-16:42 28.22 22.25 0.389379E+09 544.97 22-SEP-13:00 26.70 17.59
October 0.339044E+10 10723.33 09-OCT-15:23 27.80 19.57 0.368560E+09 544.93 19-OCT-13:09 22.48 19.30
November 0.195504E+10 5675.87 06-NOV-16:00 20.60 10.48 0.337768E+09 544.94 03-NOV-13:50 20.60 10.48
December 0.105802E+10 2633.41 12-DEC-14:40 22.80 16.47 0.308344E+09 544.91 12-DEC-14:00 22.80 16.17
                     
Annual Sum or Average 0.554584E+11         0.446121E+10        
Minimum of Months 0.641656E+09 2161.59   16.87 10.48 0.294300E+09 516.40   16.78 10.48
Maximum of Months 0.966412E+10 19938.20   33.30 22.74 0.445959E+09 544.97   33.30 22.74



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.533010E+09 3112.19 21-JAN-06:10 5.50 3.54 0.00 0.00 01-JAN-00:10 5.50 3.54
February 0.145807E+10 4898.95 28-FEB-06:15 10.97 5.96 0.00 0.00 01-FEB-00:10 10.97 5.96
March 0.426004E+10 5940.94 14-MAR-05:15 13.30 11.16 0.00 0.00 01-MAR-00:10 13.30 11.16
April 0.568567E+10 8383.90 17-APR-14:35 28.90 16.48 0.00 0.00 01-APR-00:10 28.90 16.48
May 0.667093E+10 11597.54 30-MAY-05:15 19.07 17.52 0.00 0.00 01-MAY-00:10 19.07 17.52
June 0.889973E+10 10497.08 19-JUN-05:15 20.93 20.12 0.00 0.00 01-JUN-00:10 20.93 20.12
July 0.990839E+10 13653.78 17-JUL-05:13 21.70 19.38 0.00 0.00 01-JUL-00:10 21.70 19.38
August 0.113800E+11 13244.13 14-AUG-05:13 23.30 20.62 0.00 0.00 01-AUG-00:10 23.30 20.62
September 0.718246E+10 10105.33 05-SEP-05:15 21.70 20.50 0.00 0.00 01-SEP-00:10 21.70 20.50
October 0.507503E+10 10606.47 10-OCT-05:15 15.73 14.81 0.00 0.00 01-OCT-00:10 15.73 14.81
November 0.348457E+10 7478.08 06-NOV-06:15 9.23 8.65 0.00 0.00 01-NOV-00:10 9.23 8.65
December 0.185440E+10 4524.35 13-DEC-06:15 16.70 15.65 0.00 0.00 01-DEC-00:10 16.70 15.65
                     
Annual Sum or Average 0.663923E+11         0.00        
Minimum of Months 0.533010E+09 3112.19   5.50 3.54 0.00 0.00   5.50 3.54
Maximum of Months 0.113800E+11 13653.78   28.90 20.62 0.00 0.00   28.90 20.62



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.147299E+09 5743.62 26-JAN-05:01 -4.5 -6.7 0.00 0.00 01-JAN-00:10 -4.5 -6.7
February 0.516619E+09 7030.70 12-FEB-05:41 -12.1 -13.3 0.00 0.00 01-FEB-00:10 -12.1 -13.3
March 0.198315E+10 4455.49 31-MAR-05:15 16.87 15.37 0.00 0.00 01-MAR-00:10 16.87 15.37
April 0.341350E+10 5968.03 17-APR-15:10 28.90 16.41 0.00 0.00 01-APR-00:10 28.90 16.41
May 0.518028E+10 6860.36 19-MAY-05:03 16.60 15.60 0.00 0.00 01-MAY-00:10 16.60 15.60
June 0.722603E+10 8220.29 15-JUN-05:02 22.20 18.53 0.00 0.00 01-JUN-00:10 22.20 18.53
July 0.775130E+10 8166.90 12-JUL-05:15 20.60 20.26 0.00 0.00 01-JUL-00:10 20.60 20.26
August 0.846065E+10 7883.85 08-AUG-05:15 20.60 20.10 0.00 0.00 01-AUG-00:10 20.60 20.10
September 0.569482E+10 7504.56 09-SEP-05:02 21.78 19.79 0.00 0.00 01-SEP-00:10 21.78 19.79
October 0.291059E+10 4725.56 11-OCT-16:00 26.10 17.12 0.00 0.00 01-OCT-00:10 26.10 17.12
November 0.118061E+10 4511.53 21-NOV-05:01 -2.3 -3.6 0.00 0.00 01-NOV-00:10 -2.3 -3.6
December 0.471877E+09 4997.23 18-DEC-05:01 -5.0 -6.8 0.00 0.00 01-DEC-00:10 -5.0 -6.8
                     
Annual Sum or Average 0.449367E+11         0.00        
Minimum of Months 0.147299E+09 4455.49   -12.1 -13.3 0.00 0.00   -12.1 -13.3
Maximum of Months 0.846065E+10 8220.29   28.90 20.26 0.00 0.00   28.90 20.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 49760840.97 1550.67 31-JAN-17:40 19.07 13.27 0.00 0.00 01-JAN-00:10 19.07 13.27
February 0.552414E+09 6448.90 28-FEB-16:00 23.30 12.53 0.00 0.00 01-FEB-00:10 23.30 12.53
March 0.250184E+10 12844.00 30-MAR-15:40 27.80 17.34 0.00 0.00 01-MAR-00:10 27.80 17.34
April 0.527123E+10 18088.49 17-APR-14:35 28.90 16.48 0.00 0.00 01-APR-00:10 28.90 16.48
May 0.896658E+10 18653.08 16-MAY-15:27 29.40 17.75 0.00 0.00 01-MAY-00:10 29.40 17.75
June 0.129030E+11 18511.97 12-JUN-15:00 33.30 22.72 0.00 0.00 01-JUN-00:10 33.30 22.72
July 0.137067E+11 20542.99 07-JUL-15:10 35.10 23.86 0.00 0.00 01-JUL-00:10 35.10 23.86
August 0.143974E+11 19496.01 01-AUG-14:20 34.27 23.72 0.00 0.00 01-AUG-00:10 34.27 23.72
September 0.765011E+10 16052.81 06-SEP-14:50 29.68 22.88 0.00 0.00 01-SEP-00:10 29.68 22.88
October 0.328831E+10 11661.40 10-OCT-14:50 28.98 20.71 0.00 0.00 01-OCT-00:10 28.98 20.71
November 0.844701E+09 5057.20 06-NOV-15:00 20.60 10.48 0.00 0.00 01-NOV-00:10 20.60 10.48
December 0.128830E+09 2936.17 12-DEC-14:50 22.80 16.32 0.00 0.00 01-DEC-00:10 22.80 16.32
                     
Annual Sum or Average 0.702609E+11         0.00        
Minimum of Months 49760840.97 1550.67   19.07 10.48 0.00 0.00   19.07 10.48
Maximum of Months 0.143974E+11 20542.99   35.10 23.86 0.00 0.00   35.10 23.86



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.282221E+10 1793.76 23-JAN-17:00 10.00 3.54 95230833.78 126.84 20-JAN-10:00 10.00 3.54
February 0.771799E+10 3911.45 20-FEB-18:00 17.20 9.39 86397275.58 126.84 17-FEB-14:00 17.20 9.39
March 0.143694E+11 7149.88 31-MAR-24:00 12.10 7.93 0.103239E+09 126.84 31-MAR-13:09 12.10 7.93
April 0.188915E+11 7880.62 09-APR-18:13 19.80 10.92 91606041.54 126.83 03-APR-09:39 19.80 10.92
May 0.448111E+10 3474.02 31-MAY-24:00 21.00 18.72 99241678.74 126.85 30-MAY-13:00 21.00 18.72
June 0.933553E+10 5336.89 30-JUN-24:00 22.30 21.46 98974909.25 126.86 23-JUN-09:50 22.30 21.46
July 0.147265E+11 7253.01 31-JUL-24:00 25.20 21.98 91891946.92 126.85 26-JUL-09:09 25.20 21.98
August 0.198291E+11 7820.65 27-AUG-19:03 28.62 21.12 0.104963E+09 136.09 02-AUG-13:00 28.62 21.12
September 0.441098E+10 3257.10 30-SEP-24:00 16.80 15.75 91611447.28 126.85 21-SEP-13:20 16.80 15.75
October 0.941282E+10 5157.69 31-OCT-24:00 9.70 6.26 95238364.37 126.86 18-OCT-13:09 9.70 6.26
November 0.138464E+11 5832.98 06-NOV-17:00 18.90 9.61 94302073.54 126.84 27-NOV-10:00 19.40 16.85
December 0.190768E+11 7619.47 19-DEC-17:00 13.90 5.19 91881320.78 126.83 06-DEC-14:00 13.90 5.19
                     
Annual Sum or Average 0.138920E+12         0.114458E+10        
Minimum of Months 0.282221E+10 1793.76   9.70 3.54 86397275.58 126.83   9.70 3.54
Maximum of Months 0.198291E+11 7880.62   28.62 21.98 0.104963E+09 136.09   28.62 21.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.794502E+09 1452.96 20-JAN-17:00 16.70 11.48 94864287.80 126.83 20-JAN-14:50 16.70 11.48
February 0.572266E+10 3566.53 24-FEB-17:50 15.18 6.70 86397231.41 126.84 17-FEB-14:00 15.18 6.70
March 0.129470E+11 6718.38 31-MAR-24:00 12.10 7.93 0.103239E+09 126.84 31-MAR-13:09 12.10 7.93
April 0.177343E+11 7320.07 09-APR-18:13 19.80 10.92 91606066.12 126.83 03-APR-09:39 19.80 10.92
May 0.403026E+10 3289.77 31-MAY-24:00 21.00 18.72 99238037.48 126.84 04-MAY-13:39 21.00 18.72
June 0.882830E+10 5127.65 30-JUN-24:00 22.30 21.46 98973851.48 126.86 23-JUN-09:00 22.30 21.46
July 0.140136E+11 6998.47 31-JUL-24:00 25.20 21.98 91892111.02 126.85 26-JUL-09:09 25.20 21.98
August 0.188146E+11 7380.41 13-AUG-19:10 29.90 21.88 0.105090E+09 136.34 02-AUG-13:00 29.90 21.88
September 0.392194E+10 2769.61 30-SEP-24:00 16.80 15.75 91609266.24 126.84 25-SEP-13:20 16.80 15.75
October 0.821583E+10 4473.53 31-OCT-24:00 9.70 6.26 95237632.72 126.86 18-OCT-13:50 9.70 6.26
November 0.120361E+11 5464.86 06-NOV-17:00 18.90 9.61 94301895.36 126.83 03-NOV-13:50 18.90 9.61
December 0.161444E+11 7060.73 08-DEC-17:00 11.10 4.72 91881352.05 126.83 06-DEC-14:00 11.10 4.72
                     
Annual Sum or Average 0.123204E+12         0.114433E+10        
Minimum of Months 0.794502E+09 1452.96   9.70 4.72 86397231.41 126.83   9.70 4.72
Maximum of Months 0.188146E+11 7380.41   29.90 21.98 0.105090E+09 136.34   29.90 21.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.329028E+09 1475.45 20-JAN-17:00 16.70 11.48 91808371.94 127.31 02-JAN-14:09 16.70 11.48
February 0.448286E+10 3568.30 28-FEB-17:00 23.90 12.94 86395808.19 126.84 17-FEB-14:00 23.90 12.94
March 0.121056E+11 6467.20 31-MAR-23:20 12.23 7.91 0.103239E+09 126.84 31-MAR-13:09 12.23 7.91
April 0.173395E+11 7377.90 14-APR-18:20 23.90 15.14 91606194.80 126.83 03-APR-09:50 23.90 15.14
May 0.394730E+10 3246.75 31-MAY-24:00 21.00 18.72 99239193.34 126.85 30-MAY-13:00 21.00 18.72
June 0.888756E+10 5104.97 30-JUN-24:00 22.30 21.46 98974616.68 126.86 26-JUN-13:00 22.30 21.46
July 0.141057E+11 7029.26 31-JUL-24:00 25.20 21.98 91892437.20 126.85 26-JUL-09:09 25.20 21.98
August 0.189144E+11 7536.78 20-AUG-16:40 27.97 24.54 0.104856E+09 136.50 02-AUG-13:00 27.97 24.54
September 0.379618E+10 2306.43 30-SEP-24:00 16.80 15.75 91609254.98 126.84 25-SEP-13:20 16.80 15.75
October 0.745807E+10 3987.94 31-OCT-23:20 9.63 5.89 95237644.47 126.86 18-OCT-13:00 9.63 5.89
November 0.107314E+11 5448.70 06-NOV-17:00 18.90 9.61 94301924.65 126.83 27-NOV-14:00 22.20 17.55
December 0.142894E+11 6947.95 07-DEC-17:00 14.40 6.55 91881417.14 126.83 06-DEC-14:00 14.40 6.55
                     
Annual Sum or Average 0.116387E+12         0.114104E+10        
Minimum of Months 0.329028E+09 1475.45   9.63 5.89 86395808.19 126.83   9.63 5.89
Maximum of Months 0.189144E+11 7536.78   27.97 24.54 0.104856E+09 136.50   27.97 24.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234843E+12 90760.85 20-JAN-17:00 16.70 11.48 0.206172E+10 2747.22 11-JAN-14:00 16.70 11.48
February 0.432435E+12 182347.88 21-FEB-17:00 21.70 10.37 0.187079E+10 2748.95 09-FEB-14:50 21.70 10.37
March 0.725582E+12 357490.70 31-MAR-24:00 12.10 7.93 0.223510E+10 2747.33 20-MAR-13:09 12.10 7.93
April 0.937266E+12 365481.21 16-APR-18:53 22.20 15.51 0.200683E+10 3016.69 17-APR-13:00 28.90 16.63
May 0.238119E+12 174814.64 31-MAY-24:00 21.00 18.72 0.214858E+10 2746.55 25-MAY-13:00 21.00 18.72
June 0.468128E+12 266836.78 30-JUN-24:00 22.30 21.46 0.214258E+10 2746.33 26-JUN-09:00 22.30 21.46
July 0.730071E+12 359177.29 31-JUL-24:00 25.20 21.98 0.198919E+10 2745.89 26-JUL-09:09 25.20 21.98
August 0.971241E+12 369793.45 07-AUG-21:12 22.60 21.54 0.255302E+10 3597.15 18-AUG-13:50 33.48 22.91
September 0.235594E+12 175508.53 30-SEP-24:00 16.80 15.75 0.198356E+10 2747.01 28-SEP-13:00 16.80 15.75
October 0.486923E+12 267813.37 31-OCT-24:00 9.70 6.26 0.206165E+10 2746.39 18-OCT-13:30 9.70 6.26
November 0.708020E+12 276316.85 06-NOV-17:00 18.90 9.61 0.204178E+10 2747.82 22-NOV-14:09 11.28 3.90
December 0.974459E+12 367153.97 12-DEC-17:00 21.70 16.13 0.198973E+10 2748.66 18-DEC-14:09 8.17 1.58
                     
Annual Sum or Average 0.714268E+13         0.250845E+11        
Minimum of Months 0.234843E+12 90760.85   9.70 6.26 0.187079E+10 2745.89   8.17 1.58
Maximum of Months 0.974459E+12 369793.45   25.20 21.98 0.255302E+10 3597.15   33.48 22.91



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.342587E+09 10615.21 20-JAN-05:17 12.80
February 80229410.95 11026.57 23-FEB-05:05 6.02
March 0.181662E+09 11158.97 13-MAR-03:05 7.70
April 0.228304E+09 13660.41 15-APR-16:01 28.03
May 0.300299E+09 15476.38 06-MAY-16:02 29.63
June 0.308686E+09 20591.01 24-JUN-16:02 33.22
July 0.423153E+09 25072.26 08-JUL-16:01 36.32
August 0.421815E+09 19255.79 19-AUG-16:02 32.33
September 0.478793E+09 13996.50 23-SEP-16:02 28.72
October 0.473605E+09 12938.79 09-OCT-09:43 22.02
November 0.429270E+09 11216.43 24-NOV-04:07 8.90
December 0.348661E+09 10828.49 12-DEC-04:05 13.22
         
Annual Sum or Average 0.401706E+10      
Minimum of Months 80229410.95 10615.21   6.02
Maximum of Months 0.478793E+09 25072.26   36.32



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 70414190.69 39979.72 09-JAN-05:11 -2.2
February 20969984.86 38716.02 13-FEB-06:02 -5.6
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 91384175.55      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 70414190.69 39979.72   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.327363E+10 74584.89 09-JAN-04:01 -1.8
February 0.147828E+10 73739.25 13-FEB-04:01 -5.0
March 4850121.34 32334.14 20-MAR-05:03 5.00
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 2741346.24 18275.64 30-OCT-05:03 8.90
November 69426562.54 61611.82 22-NOV-06:01 -3.3
December 0.143546E+10 71252.10 04-DEC-04:01 -2.3
         
Annual Sum or Average 0.626439E+10      
Minimum of Months 0.00 0.00   -5.0
Maximum of Months 0.327363E+10 74584.89   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.196932E+09 11357.09 09-JAN-05:01 -2.2
February 71273104.45 11472.73 13-FEB-05:01 -5.1
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 138978.59 1853.05 22-NOV-06:01 -3.3
December 408112.21 5001.48 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.268752E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.196932E+09 11472.73   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.141230E+09 9322.60 09-JAN-05:01 -2.2
February 44249262.21 9489.57 13-FEB-05:01 -5.1
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 718328.19 5038.44 22-NOV-06:01 -3.3
December 3704204.45 7616.20 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.189902E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.141230E+09 9489.57   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.240468E+09 13858.68 09-JAN-05:01 -2.2
February 85184179.79 13450.17 13-FEB-05:01 -5.1
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 1138495.07 9779.33 21-NOV-06:01 -2.8
December 12786362.72 11655.30 18-DEC-06:01 -5.0
         
Annual Sum or Average 0.339577E+09      
Minimum of Months 0.00 0.00   -5.1
Maximum of Months 0.240468E+09 13858.68   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8595420.28 7175.96 10-JAN-06:01 -4.4
February 939672.28 7121.79 13-FEB-06:02 -5.6
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 9535092.55      
Minimum of Months 0.00 0.00   -5.6
Maximum of Months 8595420.28 7175.96   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292277E+10 12774.50 09-JAN-03:53 -1.7
February 0.154941E+10 12990.09 12-FEB-07:01 -12.7
March 38414667.55 10317.35 22-MAR-05:02 6.02
April 6800205.98 8172.78 06-APR-05:03 0.18
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 10315462.59 10087.71 26-OCT-05:03 2.20
November 0.185848E+09 11258.06 22-NOV-05:01 -2.9
December 0.102329E+10 12096.38 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.573685E+10      
Minimum of Months 0.00 0.00   -12.7
Maximum of Months 0.292277E+10 12990.09   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.156799E+10 13202.43 09-JAN-04:01 -1.8
February 0.750841E+09 13710.59 12-FEB-07:01 -12.7
March 18741377.12 10876.09 22-MAR-05:02 6.02
April 1814477.60 3984.49 06-APR-05:03 0.18
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 6584942.30 7907.42 26-OCT-05:03 2.20
November 72453083.99 11697.25 22-NOV-05:01 -2.9
December 0.476085E+09 12530.26 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.289451E+10      
Minimum of Months 0.00 0.00   -12.7
Maximum of Months 0.156799E+10 13710.59   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.138200E+10 14476.97 09-JAN-04:01 -1.8
February 0.652876E+09 14855.44 12-FEB-07:01 -12.7
March 10307706.75 11756.11 22-MAR-05:02 6.02
April 293233.99 1954.89 06-APR-05:03 0.18
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 340228.18 2207.96 31-OCT-05:03 8.30
November 60350075.62 12480.16 21-NOV-05:01 -2.3
December 0.378475E+09 13509.56 26-DEC-04:01 3.90
         
Annual Sum or Average 0.248464E+10      
Minimum of Months 0.00 0.00   -12.7
Maximum of Months 0.138200E+10 14855.44   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.115185E+10 13969.97 09-JAN-04:01 -1.8
February 0.545636E+09 13928.65 13-FEB-04:01 -5.0
March 3114635.24 9388.35 22-MAR-05:02 6.02
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 235831.66 1261.85 26-OCT-05:03 2.20
November 62720199.37 12257.08 22-NOV-05:01 -2.9
December 0.341734E+09 12670.98 26-DEC-05:01 3.80
         
Annual Sum or Average 0.210529E+10      
Minimum of Months 0.00 0.00   -5.0
Maximum of Months 0.115185E+10 13969.97   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.719224E+10 15336.12 09-JAN-03:53 -1.7
February 0.411244E+10 16050.11 12-FEB-05:12 -11.9
March 0.491041E+09 13058.28 20-MAR-04:01 6.42
April 0.123324E+09 12510.67 06-APR-04:02 0.92
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.201984E+09 12947.12 26-OCT-04:01 2.70
November 0.122100E+10 14431.17 22-NOV-04:01 -2.8
December 0.394472E+10 15157.76 03-DEC-09:02 -0.9
         
Annual Sum or Average 0.172867E+11      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.719224E+10 16050.11   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.378590E+10 14385.55 08-JAN-01:53 -5.6
February 0.211095E+10 15123.43 12-FEB-05:12 -11.9
March 0.214589E+09 12290.56 22-MAR-04:01 6.60
April 46825257.50 11641.84 06-APR-04:02 0.92
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.113384E+09 12112.77 26-OCT-04:01 2.70
November 0.522419E+09 13452.73 22-NOV-04:01 -2.8
December 0.190728E+10 14074.04 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.870135E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.378590E+10 15123.43   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.394690E+10 17159.75 09-JAN-03:53 -1.7
February 0.225304E+10 17963.52 12-FEB-05:12 -11.9
March 0.237459E+09 14484.18 22-MAR-04:01 6.60
April 75112694.17 13725.10 06-APR-04:02 0.92
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.124754E+09 14010.46 31-OCT-04:02 8.80
November 0.485270E+09 15560.93 21-NOV-04:02 -1.8
December 0.182345E+10 16604.51 26-DEC-04:01 3.90
         
Annual Sum or Average 0.894598E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.394690E+10 17963.52   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.320932E+10 15854.85 09-JAN-03:53 -1.7
February 0.164996E+10 16640.27 12-FEB-05:12 -11.9
March 0.121561E+09 13350.79 22-MAR-04:01 6.60
April 28852813.05 9275.57 06-APR-05:03 0.18
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 60273494.28 12880.90 26-OCT-04:01 2.70
November 0.429640E+09 14742.84 22-NOV-04:01 -2.8
December 0.140345E+10 15498.49 18-DEC-04:01 -4.1
         
Annual Sum or Average 0.690306E+10      
Minimum of Months 0.00 0.00   -11.9
Maximum of Months 0.320932E+10 16640.27   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.785828E+09 11990.23 17-JAN-06:02 4.72
February 0.473000E+09 11552.16 08-FEB-06:03 7.38
March 0.108380E+09 10905.41 22-MAR-04:01 6.60
April 0.130087E+09 9818.95 04-APR-03:02 15.10
May 64354067.72 6957.62 15-MAY-03:02 12.80
June 67446245.31 6802.68 09-JUN-03:02 15.40
July 71140323.10 7823.16 29-JUL-03:02 17.70
August 47343460.67 6440.08 06-AUG-16:21 32.50
September 67089508.35 7243.26 18-SEP-03:02 15.00
October 0.100374E+09 10401.60 02-OCT-03:02 19.82
November 0.121193E+09 11215.69 27-NOV-04:03 14.50
December 99040225.08 14250.15 26-DEC-04:01 3.90
         
Annual Sum or Average 0.213528E+10      
Minimum of Months 47343460.67 6440.08   3.90
Maximum of Months 0.785828E+09 14250.15   32.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288818E+10 7081.54 09-JAN-06:08 -2.4
February 0.147376E+10 7311.91 22-FEB-06:03 12.02
March 0.126986E+09 7644.70 24-MAR-05:03 11.52
April 50080025.99 7388.19 03-APR-04:03 20.22
May 49671086.61 6956.28 01-MAY-04:03 16.10
June 38869386.54 6199.66 14-JUN-03:02 22.62
July 42525836.55 6853.89 31-JUL-03:02 21.60
August 39201508.06 6602.57 10-AUG-03:02 24.82
September 43209897.95 6025.18 25-SEP-03:02 20.10
October 0.105452E+09 7635.71 31-OCT-05:03 8.30
November 0.260129E+09 8420.24 20-NOV-06:03 6.02
December 0.129353E+10 7630.00 12-DEC-06:03 12.70
         
Annual Sum or Average 0.641159E+10      
Minimum of Months 38869386.54 6025.18   -2.4
Maximum of Months 0.288818E+10 8420.24   24.82



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.934732E+10 23155.06 09-JAN-05:19 -2.2
February 0.572001E+10 25213.38 13-FEB-05:18 -5.2
March 0.168295E+10 13509.00 14-MAR-05:03 13.30
April 0.851067E+09 16765.60 25-APR-05:03 9.40
May 0.261889E+09 17742.73 10-MAY-05:03 8.98
June 0.125482E+09 15029.57 08-JUN-05:03 11.70
July 57786634.93 9778.77 03-JUL-03:02 17.80
August 45566777.40 9726.61 28-AUG-03:02 21.60
September 0.218731E+09 16133.36 29-SEP-05:02 12.30
October 0.129409E+10 16546.33 04-OCT-05:02 7.70
November 0.264850E+10 15297.54 22-NOV-06:12 -3.3
December 0.582100E+10 22998.43 18-DEC-05:33 -5.0
         
Annual Sum or Average 0.280744E+11      
Minimum of Months 45566777.40 9726.61   -5.2
Maximum of Months 0.934732E+10 25213.38   21.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.293237E+09 527.29 08-JAN-19:00 -0.6
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.293237E+09      
Minimum of Months 0.00 0.00   -0.6
Maximum of Months 0.293237E+09 527.29   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.674367E+09 573.77 15-JAN-18:35 4.47
February 46941651.11 528.86 12-FEB-07:30 -12.5
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.721308E+09      
Minimum of Months 0.00 0.00   -12.5
Maximum of Months 0.674367E+09 573.77   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 5.70
February 0.00 0.00 01-FEB-00:10 9.92
March 0.00 0.00 01-MAR-00:10 15.32
April 0.00 0.00 01-APR-00:10 12.05
May 0.00 0.00 01-MAY-00:03 16.68
June 0.00 0.00 01-JUN-00:10 20.93
July 0.00 0.00 01-JUL-00:10 22.28
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:03 21.40
October 0.00 0.00 01-OCT-00:10 16.85
November 0.00 0.00 01-NOV-00:10 9.70
December 0.00 0.00 01-DEC-00:10 1.80
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   1.80
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.148304E+11 15519.45 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.134523E+11 15519.45 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.159851E+11 15519.45 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.142779E+11 15519.45 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.154078E+11 15519.45 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.153333E+11 15519.45 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.143524E+11 15519.45 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.159851E+11 15519.45 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.142779E+11 15519.45 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.148304E+11 15519.45 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.146566E+11 15519.45 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.143524E+11 15519.45 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.177742E+12     0.424397E+12    
Minimum of Months 0.134523E+11 15519.45   0.325565E+11 13457.54  
Maximum of Months 0.159851E+11 15519.45   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321286E+12    
Minimum of Months 0.120811E+11 13937.56   0.244881E+11 18128.59  
Maximum of Months 0.143557E+11 13937.56   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123446E+10 1639.45 03-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.111861E+10 1714.13 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.124035E+10 1648.92 21-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108264E+10 1536.68 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.114597E+10 1202.06 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.113194E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.106782E+10 1305.94 27-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.120146E+10 1484.87 24-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110242E+10 1584.27 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.120829E+10 1746.86 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.120161E+10 1731.20 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.120398E+10 1642.47 06-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.139395E+11     0.403423E+11    
Minimum of Months 0.106782E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.124035E+10 1746.86   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.779841E+09 1041.60 03-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.705655E+09 1104.65 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.793890E+09 1055.36 21-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.698200E+09 962.92 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.741631E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.733308E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.690852E+09 780.24 27-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.775722E+09 927.22 24-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.707905E+09 1002.40 29-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.760573E+09 1125.75 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.766176E+09 1109.23 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.759261E+09 1043.73 06-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.891301E+10     0.259981E+11    
Minimum of Months 0.690852E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.793890E+09 1125.75   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118649E+10 1623.64 03-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.107915E+10 1714.17 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.123111E+10 1647.29 21-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.108533E+10 1540.88 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.115289E+10 1291.26 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.113981E+10 1204.79 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.107552E+10 1357.13 27-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.120509E+10 1496.77 24-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.109948E+10 1574.82 29-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.116969E+10 1746.90 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.116677E+10 1724.83 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.115266E+10 1625.19 06-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.137440E+11     0.403429E+11    
Minimum of Months 0.107552E+10 1204.79   0.307490E+10 2276.35  
Maximum of Months 0.123111E+10 1746.90   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.781240E+09 1059.66 03-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.712442E+09 1104.65 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.801341E+09 1067.00 21-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.701470E+09 1009.83 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.743067E+09 936.23 24-MAY-07:30 0.222974E+10 1466.94 01-MAY-07:10
June 0.733575E+09 827.21 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.693207E+09 906.24 27-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.778070E+09 981.31 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.714309E+09 1029.28 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.773933E+09 1125.75 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.762073E+09 1116.98 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.758916E+09 1060.79 06-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.895364E+10     0.259979E+11    
Minimum of Months 0.693207E+09 827.21   0.198154E+10 1466.94  
Maximum of Months 0.801341E+09 1125.75   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123719E+10 1642.65 03-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.112117E+10 1715.18 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.124164E+10 1651.92 21-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108344E+10 1542.97 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.114644E+10 1217.22 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.113226E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.106839E+10 1318.92 27-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.120234E+10 1492.69 24-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110357E+10 1589.15 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.120980E+10 1746.96 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.120409E+10 1731.72 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.120701E+10 1645.57 06-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.139574E+11     0.403423E+11    
Minimum of Months 0.106839E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.124164E+10 1746.96   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.780790E+09 1042.67 03-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.706047E+09 1104.82 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.794237E+09 1056.20 21-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.698478E+09 965.55 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.741791E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.733434E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.691002E+09 785.39 27-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.775909E+09 930.20 24-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.708240E+09 1003.96 29-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.760838E+09 1125.76 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.766584E+09 1109.54 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.759675E+09 1044.76 06-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.891702E+10     0.259981E+11    
Minimum of Months 0.691002E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.794237E+09 1125.76   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118953E+10 1627.61 03-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.108051E+10 1715.22 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.123199E+10 1650.36 21-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.108601E+10 1546.99 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.115372E+10 1303.38 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.114044E+10 1219.75 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.107636E+10 1368.21 27-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.120584E+10 1504.10 24-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.110025E+10 1580.12 29-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.117212E+10 1746.99 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.116765E+10 1725.64 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.115379E+10 1629.12 06-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.137582E+11     0.403429E+11    
Minimum of Months 0.107636E+10 1219.75   0.307490E+10 2276.35  
Maximum of Months 0.123199E+10 1746.99   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.781542E+09 1060.19 03-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.712560E+09 1104.82 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.801708E+09 1067.45 21-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.701780E+09 1010.70 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.743353E+09 937.32 24-MAY-07:30 0.222974E+10 1466.94 01-MAY-07:10
June 0.733748E+09 829.34 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.693375E+09 907.89 27-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.778321E+09 982.39 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.714743E+09 1030.02 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.774115E+09 1125.76 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.762418E+09 1117.07 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.759381E+09 1061.31 06-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.895704E+10     0.259979E+11    
Minimum of Months 0.693375E+09 829.34   0.198154E+10 1466.94  
Maximum of Months 0.801708E+09 1125.76   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123721E+10 1642.55 03-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.112116E+10 1715.14 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.124165E+10 1651.82 21-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108345E+10 1542.80 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.114644E+10 1217.03 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.113225E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.106839E+10 1318.61 27-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.120234E+10 1492.47 24-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110357E+10 1589.00 29-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.120979E+10 1746.95 30-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.120410E+10 1731.71 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.120710E+10 1645.47 06-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.139575E+11     0.403423E+11    
Minimum of Months 0.106839E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.124165E+10 1746.95   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.780801E+09 1042.62 03-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.706036E+09 1104.79 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.794243E+09 1056.15 21-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.698485E+09 965.47 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.741791E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.733435E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.691001E+09 785.28 27-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.775909E+09 930.10 24-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.708264E+09 1003.89 29-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.760844E+09 1125.76 30-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.766592E+09 1109.54 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.759682E+09 1044.71 06-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.891708E+10     0.259981E+11    
Minimum of Months 0.691001E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.794243E+09 1125.76   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.118947E+10 1627.51 03-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.108177E+10 1715.18 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.123198E+10 1650.27 21-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.108601E+10 1546.82 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.115372E+10 1303.18 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.114044E+10 1219.33 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.107635E+10 1367.89 27-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.120584E+10 1503.88 24-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.110025E+10 1579.98 29-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.117211E+10 1746.99 30-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.116771E+10 1725.63 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.115379E+10 1629.03 06-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.137594E+11     0.403429E+11    
Minimum of Months 0.107635E+10 1219.33   0.307490E+10 2276.35  
Maximum of Months 0.123198E+10 1746.99   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.781561E+09 1060.13 03-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.712558E+09 1104.79 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.801714E+09 1067.39 21-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.701843E+09 1010.59 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.743354E+09 937.24 24-MAY-07:30 0.222974E+10 1466.94 01-MAY-07:10
June 0.733763E+09 829.09 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.693377E+09 907.69 27-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.778321E+09 982.25 24-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.714750E+09 1029.92 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.774120E+09 1125.76 30-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.762465E+09 1117.06 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.759394E+09 1061.25 06-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.895722E+10     0.259979E+11    
Minimum of Months 0.693377E+09 829.09   0.198154E+10 1466.94  
Maximum of Months 0.801714E+09 1125.76   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.418155E+10 4375.82 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.379298E+10 4375.82 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.450711E+10 4375.82 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.402577E+10 4375.82 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.434433E+10 4375.82 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.432333E+10 4375.82 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.404678E+10 4375.82 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.450711E+10 4375.82 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.402577E+10 4375.82 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.418155E+10 4375.82 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.413254E+10 4375.82 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.404678E+10 4375.82 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.501156E+11     0.749486E+13    
Minimum of Months 0.379298E+10 4375.82   0.246344E+12 94908.13  
Maximum of Months 0.450711E+10 4375.82   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.154078E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.153333E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.146566E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.177742E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.123446E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.967479E+09
February 0.136985E+10 0.111861E+10 0.307485E+10 0.00 0.00 0.00 0.00 364899.56 0.825951E+09
March 0.163685E+10 0.124035E+10 0.352283E+10 0.00 0.00 0.00 0.00 1595194.53 0.541113E+09
April 0.145243E+10 0.108264E+10 0.328108E+10 0.00 0.00 0.00 0.00 4577201.98 0.320553E+09
May 0.157338E+10 0.114597E+10 0.346000E+10 0.00 0.00 0.00 0.00 13771825.61 0.204414E+09
June 0.156900E+10 0.113194E+10 0.339353E+10 0.00 0.00 0.00 0.00 58649425.65 91364753.35
July 0.145680E+10 0.106782E+10 0.334664E+10 0.00 0.00 0.00 0.00 64453144.05 56548767.61
August 0.163685E+10 0.120146E+10 0.352283E+10 0.00 0.00 0.00 0.00 62101896.08 28200949.71
September 0.145243E+10 0.110242E+10 0.327926E+10 0.00 0.00 0.00 0.00 17359384.15 0.106989E+09
October 0.150991E+10 0.120829E+10 0.339809E+10 0.00 0.00 0.00 0.00 3840459.03 0.367854E+09
November 0.149516E+10 0.120161E+10 0.332024E+10 0.00 0.00 0.00 0.00 8475.94 0.540867E+09
December 0.145680E+10 0.120398E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.938371E+09
                   
Annual Sum or Average 0.181194E+11 0.139395E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.226722E+09 0.498971E+10
Minimum of Months 0.136985E+10 0.106782E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 28200949.71
Maximum of Months 0.163685E+10 0.124035E+10 0.352283E+10 0.00 0.00 0.00 0.00 64453144.05 0.967479E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.779841E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.649211E+09
February 0.882782E+09 0.705655E+09 0.198155E+10 0.00 0.00 0.00 0.00 88061.46 0.551875E+09
March 0.105485E+10 0.793890E+09 0.227025E+10 0.00 0.00 0.00 0.00 1109351.03 0.357973E+09
April 0.936002E+09 0.698200E+09 0.211446E+10 0.00 0.00 0.00 0.00 2900517.02 0.207838E+09
May 0.101394E+10 0.741631E+09 0.222976E+10 0.00 0.00 0.00 0.00 8477438.98 0.139416E+09
June 0.101113E+10 0.733308E+09 0.218692E+10 0.00 0.00 0.00 0.00 38733596.23 59309792.94
July 0.938820E+09 0.690852E+09 0.215670E+10 0.00 0.00 0.00 0.00 43059159.73 35126990.59
August 0.105485E+10 0.775722E+09 0.227025E+10 0.00 0.00 0.00 0.00 42798026.46 14888839.87
September 0.936002E+09 0.707905E+09 0.211328E+10 0.00 0.00 0.00 0.00 11164343.64 70210363.07
October 0.973041E+09 0.760573E+09 0.218986E+10 0.00 0.00 0.00 0.00 2251940.31 0.243558E+09
November 0.963541E+09 0.766176E+09 0.213969E+10 0.00 0.00 0.00 0.00 48955.47 0.356768E+09
December 0.938820E+09 0.759261E+09 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.613007E+09
                   
Annual Sum or Average 0.116768E+11 0.891301E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.150631E+09 0.329918E+10
Minimum of Months 0.882782E+09 0.690852E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 14888839.87
Maximum of Months 0.105485E+10 0.793890E+09 0.227025E+10 0.00 0.00 0.00 0.00 43059159.73 0.649211E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.118649E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.981899E+09
February 0.136988E+10 0.107915E+10 0.307490E+10 0.00 0.00 0.00 0.00 95571.22 0.843823E+09
March 0.163688E+10 0.123111E+10 0.352288E+10 0.00 0.00 0.00 0.00 1560879.30 0.560885E+09
April 0.145246E+10 0.108533E+10 0.328113E+10 0.00 0.00 0.00 0.00 3842559.24 0.323728E+09
May 0.157341E+10 0.115289E+10 0.346006E+10 0.00 0.00 0.00 0.00 12895555.33 0.205936E+09
June 0.156904E+10 0.113981E+10 0.339359E+10 0.00 0.00 0.00 0.00 58034887.02 91244781.99
July 0.145684E+10 0.107552E+10 0.334669E+10 0.00 0.00 0.00 0.00 63160107.32 56787240.25
August 0.163688E+10 0.120509E+10 0.352288E+10 0.00 0.00 0.00 0.00 59657276.54 30690329.10
September 0.145246E+10 0.109948E+10 0.327931E+10 0.00 0.00 0.00 0.00 14813924.43 0.110071E+09
October 0.150994E+10 0.116969E+10 0.339814E+10 0.00 0.00 0.00 0.00 2438022.36 0.380686E+09
November 0.149520E+10 0.116677E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.557854E+09
December 0.145684E+10 0.115266E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.935016E+09
                   
Annual Sum or Average 0.181198E+11 0.137440E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.216499E+09 0.507862E+10
Minimum of Months 0.136988E+10 0.107552E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 30690329.10
Maximum of Months 0.163688E+10 0.123111E+10 0.352288E+10 0.00 0.00 0.00 0.00 63160107.32 0.981899E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.781240E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.682088E+09
February 0.882782E+09 0.712442E+09 0.198154E+10 0.00 0.00 0.00 0.00 63716.14 0.602408E+09
March 0.105485E+10 0.801341E+09 0.227023E+10 0.00 0.00 0.00 0.00 1037692.66 0.416628E+09
April 0.936002E+09 0.701470E+09 0.211444E+10 0.00 0.00 0.00 0.00 2487849.41 0.252361E+09
May 0.101394E+10 0.743067E+09 0.222974E+10 0.00 0.00 0.00 0.00 7956529.85 0.154426E+09
June 0.101113E+10 0.733575E+09 0.218691E+10 0.00 0.00 0.00 0.00 36185863.19 74249669.57
July 0.938820E+09 0.693207E+09 0.215669E+10 0.00 0.00 0.00 0.00 38158451.96 49178217.76
August 0.105485E+10 0.778070E+09 0.227023E+10 0.00 0.00 0.00 0.00 36321786.25 33138889.29
September 0.936002E+09 0.714309E+09 0.211327E+10 0.00 0.00 0.00 0.00 10212068.61 82686167.97
October 0.973041E+09 0.773933E+09 0.218984E+10 0.00 0.00 0.00 0.00 1682081.60 0.277259E+09
November 0.963541E+09 0.762073E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.406360E+09
December 0.938820E+09 0.758916E+09 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.704202E+09
                   
Annual Sum or Average 0.116768E+11 0.895364E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.134106E+09 0.373499E+10
Minimum of Months 0.882782E+09 0.693207E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 33138889.29
Maximum of Months 0.105485E+10 0.801341E+09 0.227023E+10 0.00 0.00 0.00 0.00 38158451.96 0.704202E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.123719E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.195453E+10
February 0.136985E+10 0.112117E+10 0.307485E+10 0.00 0.00 0.00 0.00 3557444.21 0.167156E+10
March 0.163685E+10 0.124164E+10 0.352283E+10 0.00 0.00 0.00 0.00 4370586.24 0.110642E+10
April 0.145243E+10 0.108344E+10 0.328108E+10 0.00 0.00 0.00 0.00 12089223.92 0.697048E+09
May 0.157338E+10 0.114644E+10 0.346000E+10 0.00 0.00 0.00 0.00 32847509.41 0.454566E+09
June 0.156900E+10 0.113226E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.135424E+09 0.225868E+09
July 0.145680E+10 0.106839E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.147887E+09 0.146397E+09
August 0.163685E+10 0.120234E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.144713E+09 90146545.27
September 0.145243E+10 0.110357E+10 0.327926E+10 0.00 0.00 0.00 0.00 41367293.96 0.233979E+09
October 0.150991E+10 0.120980E+10 0.339809E+10 0.00 0.00 0.00 0.00 12697180.79 0.751483E+09
November 0.149516E+10 0.120409E+10 0.332024E+10 0.00 0.00 0.00 0.00 609939.49 0.107226E+10
December 0.145680E+10 0.120701E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.180013E+10
                   
Annual Sum or Average 0.181194E+11 0.139574E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.535564E+09 0.102044E+11
Minimum of Months 0.136985E+10 0.106839E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 90146545.27
Maximum of Months 0.163685E+10 0.124164E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.147887E+09 0.195453E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.780790E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.132838E+10
February 0.649041E+09 0.706047E+09 0.198155E+10 0.00 0.00 0.00 0.00 680004.92 0.114604E+10
March 0.773965E+09 0.794237E+09 0.227025E+10 0.00 0.00 0.00 0.00 2780568.01 0.774636E+09
April 0.688021E+09 0.698478E+09 0.211446E+10 0.00 0.00 0.00 0.00 6161425.81 0.485414E+09
May 0.744847E+09 0.741791E+09 0.222976E+10 0.00 0.00 0.00 0.00 18849652.07 0.322259E+09
June 0.742030E+09 0.733434E+09 0.218692E+10 0.00 0.00 0.00 0.00 86735005.70 0.158103E+09
July 0.690839E+09 0.691002E+09 0.215670E+10 0.00 0.00 0.00 0.00 93515771.16 0.102955E+09
August 0.773965E+09 0.775909E+09 0.227025E+10 0.00 0.00 0.00 0.00 92060703.30 64424653.31
September 0.688021E+09 0.708240E+09 0.211328E+10 0.00 0.00 0.00 0.00 24996800.29 0.160079E+09
October 0.715730E+09 0.760838E+09 0.218986E+10 0.00 0.00 0.00 0.00 5634070.37 0.521528E+09
November 0.708685E+09 0.766584E+09 0.213969E+10 0.00 0.00 0.00 0.00 235779.13 0.740905E+09
December 0.690839E+09 0.759675E+09 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.121900E+10
                   
Annual Sum or Average 0.858171E+10 0.891702E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.331650E+09 0.702373E+10
Minimum of Months 0.649041E+09 0.691002E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 64424653.31
Maximum of Months 0.773965E+09 0.794237E+09 0.227025E+10 0.00 0.00 0.00 0.00 93515771.16 0.132838E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.118953E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.213162E+10
February 0.136988E+10 0.108051E+10 0.307490E+10 0.00 0.00 0.00 0.00 191640.43 0.182739E+10
March 0.163688E+10 0.123199E+10 0.352288E+10 0.00 0.00 0.00 0.00 3424542.40 0.124399E+10
April 0.145246E+10 0.108601E+10 0.328113E+10 0.00 0.00 0.00 0.00 8558768.93 0.737569E+09
May 0.157341E+10 0.115372E+10 0.346006E+10 0.00 0.00 0.00 0.00 29592469.43 0.466742E+09
June 0.156904E+10 0.114044E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.134038E+09 0.226012E+09
July 0.145684E+10 0.107636E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.144454E+09 0.147853E+09
August 0.163688E+10 0.120584E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.136298E+09 98436681.40
September 0.145246E+10 0.110025E+10 0.327931E+10 0.00 0.00 0.00 0.00 33398596.66 0.251633E+09
October 0.150994E+10 0.117212E+10 0.339814E+10 0.00 0.00 0.00 0.00 5202137.32 0.846863E+09
November 0.149520E+10 0.116765E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.122800E+10
December 0.145684E+10 0.115379E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.196465E+10
                   
Annual Sum or Average 0.181198E+11 0.137582E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.495158E+09 0.111708E+11
Minimum of Months 0.136988E+10 0.107636E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 98436681.40
Maximum of Months 0.163688E+10 0.123199E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.144454E+09 0.213162E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.781542E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.136376E+10
February 0.882782E+09 0.712560E+09 0.198154E+10 0.00 0.00 0.00 0.00 1016344.72 0.117306E+10
March 0.105485E+10 0.801708E+09 0.227023E+10 0.00 0.00 0.00 0.00 2310236.68 0.821469E+09
April 0.936002E+09 0.701780E+09 0.211444E+10 0.00 0.00 0.00 0.00 6118256.52 0.513282E+09
May 0.101394E+10 0.743353E+09 0.222974E+10 0.00 0.00 0.00 0.00 18743657.91 0.333431E+09
June 0.101113E+10 0.733748E+09 0.218691E+10 0.00 0.00 0.00 0.00 84890501.80 0.168425E+09
July 0.938820E+09 0.693375E+09 0.215669E+10 0.00 0.00 0.00 0.00 91397377.60 0.110256E+09
August 0.105485E+10 0.778321E+09 0.227023E+10 0.00 0.00 0.00 0.00 86843574.80 77542070.92
September 0.936002E+09 0.714743E+09 0.211327E+10 0.00 0.00 0.00 0.00 24141524.35 0.171836E+09
October 0.973041E+09 0.774115E+09 0.218984E+10 0.00 0.00 0.00 0.00 4683344.69 0.546492E+09
November 0.963541E+09 0.762418E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.770251E+09
December 0.938820E+09 0.759381E+09 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.126092E+10
                   
Annual Sum or Average 0.116768E+11 0.895704E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.320145E+09 0.731072E+10
Minimum of Months 0.882782E+09 0.693375E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 77542070.92
Maximum of Months 0.105485E+10 0.801708E+09 0.227023E+10 0.00 0.00 0.00 0.00 91397377.60 0.136376E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.123721E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.228563E+10
February 0.136985E+10 0.112116E+10 0.307485E+10 0.00 0.00 0.00 0.00 6636153.22 0.196120E+10
March 0.163685E+10 0.124165E+10 0.352283E+10 0.00 0.00 0.00 0.00 5803703.97 0.125932E+10
April 0.145243E+10 0.108345E+10 0.328108E+10 0.00 0.00 0.00 0.00 14507109.91 0.814541E+09
May 0.157338E+10 0.114644E+10 0.346000E+10 0.00 0.00 0.00 0.00 36904734.51 0.555039E+09
June 0.156900E+10 0.113225E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.158745E+09 0.286128E+09
July 0.145680E+10 0.106839E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.170891E+09 0.186729E+09
August 0.163685E+10 0.120234E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.167567E+09 0.118818E+09
September 0.145243E+10 0.110357E+10 0.327926E+10 0.00 0.00 0.00 0.00 47800298.27 0.279761E+09
October 0.150991E+10 0.120979E+10 0.339809E+10 0.00 0.00 0.00 0.00 17427084.20 0.848763E+09
November 0.149516E+10 0.120410E+10 0.332024E+10 0.00 0.00 0.00 0.00 3959424.65 0.118494E+10
December 0.145680E+10 0.120710E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.202135E+10
                   
Annual Sum or Average 0.181194E+11 0.139575E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.630242E+09 0.118022E+11
Minimum of Months 0.136985E+10 0.106839E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.118818E+09
Maximum of Months 0.163685E+10 0.124165E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.170891E+09 0.228563E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.780801E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.154247E+10
February 0.882782E+09 0.706036E+09 0.198155E+10 0.00 0.00 0.00 0.00 1523454.78 0.134095E+10
March 0.105485E+10 0.794243E+09 0.227025E+10 0.00 0.00 0.00 0.00 3575065.56 0.892772E+09
April 0.936002E+09 0.698485E+09 0.211446E+10 0.00 0.00 0.00 0.00 6998635.25 0.575407E+09
May 0.101394E+10 0.741791E+09 0.222976E+10 0.00 0.00 0.00 0.00 21476163.22 0.396749E+09
June 0.101113E+10 0.733435E+09 0.218692E+10 0.00 0.00 0.00 0.00 0.102631E+09 0.201263E+09
July 0.938820E+09 0.691001E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.110055E+09 0.131283E+09
August 0.105485E+10 0.775909E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.108275E+09 84624214.27
September 0.936002E+09 0.708264E+09 0.211328E+10 0.00 0.00 0.00 0.00 28779989.68 0.193186E+09
October 0.973041E+09 0.760844E+09 0.218986E+10 0.00 0.00 0.00 0.00 7141656.39 0.598614E+09
November 0.963541E+09 0.766592E+09 0.213969E+10 0.00 0.00 0.00 0.00 1973222.59 0.824269E+09
December 0.938820E+09 0.759682E+09 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.136141E+10
                   
Annual Sum or Average 0.116768E+11 0.891708E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.392429E+09 0.814300E+10
Minimum of Months 0.882782E+09 0.691001E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 84624214.27
Maximum of Months 0.105485E+10 0.794243E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.110055E+09 0.154247E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.118947E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.244217E+10
February 0.136988E+10 0.108177E+10 0.307490E+10 0.00 0.00 0.00 0.00 201226.48 0.212042E+10
March 0.163688E+10 0.123198E+10 0.352288E+10 0.00 0.00 0.00 0.00 4000380.54 0.144272E+10
April 0.145246E+10 0.108601E+10 0.328113E+10 0.00 0.00 0.00 0.00 9926810.32 0.871156E+09
May 0.157341E+10 0.115372E+10 0.346006E+10 0.00 0.00 0.00 0.00 33548116.61 0.572413E+09
June 0.156904E+10 0.114044E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.157519E+09 0.286499E+09
July 0.145684E+10 0.107635E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.168235E+09 0.188518E+09
August 0.163688E+10 0.120584E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.160407E+09 0.129766E+09
September 0.145246E+10 0.110025E+10 0.327931E+10 0.00 0.00 0.00 0.00 39159352.12 0.304466E+09
October 0.150994E+10 0.117211E+10 0.339814E+10 0.00 0.00 0.00 0.00 6048592.21 0.982079E+09
November 0.149520E+10 0.116771E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.138195E+10
December 0.145684E+10 0.115379E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.217826E+10
                   
Annual Sum or Average 0.181198E+11 0.137594E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.579045E+09 0.129004E+11
Minimum of Months 0.136988E+10 0.107635E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.129766E+09
Maximum of Months 0.163688E+10 0.123198E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.168235E+09 0.244217E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.781561E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.158019E+10
February 0.882782E+09 0.712558E+09 0.198154E+10 0.00 0.00 0.00 0.00 1756781.03 0.137676E+10
March 0.105485E+10 0.801714E+09 0.227023E+10 0.00 0.00 0.00 0.00 2773068.64 0.955459E+09
April 0.936002E+09 0.701843E+09 0.211444E+10 0.00 0.00 0.00 0.00 7323978.33 0.609355E+09
May 0.101394E+10 0.743354E+09 0.222974E+10 0.00 0.00 0.00 0.00 22126424.26 0.408583E+09
June 0.101113E+10 0.733763E+09 0.218691E+10 0.00 0.00 0.00 0.00 0.102141E+09 0.211991E+09
July 0.938820E+09 0.693377E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.109380E+09 0.138141E+09
August 0.105485E+10 0.778321E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.104028E+09 99703216.42
September 0.936002E+09 0.714750E+09 0.211327E+10 0.00 0.00 0.00 0.00 28724979.24 0.207203E+09
October 0.973041E+09 0.774120E+09 0.218984E+10 0.00 0.00 0.00 0.00 6027257.11 0.631930E+09
November 0.963541E+09 0.762465E+09 0.213967E+10 0.00 0.00 0.00 0.00 19060.98 0.870109E+09
December 0.938820E+09 0.759394E+09 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.142428E+10
                   
Annual Sum or Average 0.116768E+11 0.895722E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.384300E+09 0.851370E+10
Minimum of Months 0.882782E+09 0.693377E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 99703216.42
Maximum of Months 0.105485E+10 0.801714E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.109380E+09 0.158019E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.418155E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.379298E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.450711E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.402577E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.434433E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.432333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.404678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.450711E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.402577E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.418155E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.413254E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.404678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.501156E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.379298E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.450711E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.211718E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80230.49 0.180422E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2088984.76 0.116907E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6367474.82 0.691021E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22623277.82 0.429348E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.106828E+09 0.197814E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122029E+09 0.127290E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.112481E+09 74956619.33
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28163968.31 0.228228E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4739208.55 0.792017E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.117175E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.202927E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.405401E+09 0.108322E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74956619.33
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122029E+09 0.211718E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.344742E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1249089.10 0.296804E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4268350.44 0.198175E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12930159.45 0.119639E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42866000.40 0.755720E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.193826E+09 0.356928E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.222266E+09 0.230043E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.206482E+09 0.140745E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52816129.31 0.398036E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11169340.77 0.134343E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 372007.49 0.194917E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328405E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.748245E+09 0.180517E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.140745E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.222266E+09 0.344742E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.344927E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1385344.09 0.302246E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2821456.81 0.208066E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6106901.23 0.130587E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26655847.99 0.867210E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.172143E+09 0.416393E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.194714E+09 0.277139E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.187183E+09 0.174621E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40784787.81 0.432427E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7428982.27 0.138971E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1979347.96 0.192570E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.316598E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.641203E+09 0.185074E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.174621E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.194714E+09 0.344927E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 15519.45 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 15519.45 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 15519.45 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 15519.45 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 15519.45 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 15519.45 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 15519.45 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 15519.45 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 15519.45 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 15519.45 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 15519.45 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 15519.45 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1639.45 03-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1727.79 07-JAN-18:03
February 2010.79 01-FEB-10:09 1714.13 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 34.32 26-FEB-15:00 2122.03 12-FEB-00:55
March 2010.79 01-MAR-10:09 1648.92 21-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 46.43 30-MAR-16:00 1397.86 22-MAR-03:00
April 2010.79 03-APR-09:09 1536.68 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 76.50 16-APR-11:53 714.63 05-APR-05:00
May 2010.79 01-MAY-09:09 1202.06 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 96.65 07-MAY-12:10 548.67 10-MAY-04:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 312.16 11-JUN-14:53 404.11 07-JUN-03:00
July 2010.79 03-JUL-09:09 1305.94 27-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 294.68 08-JUL-18:53 297.99 28-JUL-22:00
August 2010.79 01-AUG-09:09 1484.87 24-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 303.68 06-AUG-14:00 171.40 25-AUG-04:50
September 2010.79 01-SEP-09:09 1584.27 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 115.36 17-SEP-15:00 383.37 30-SEP-19:00
October 2010.79 02-OCT-09:09 1746.86 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 89.27 09-OCT-15:53 830.08 28-OCT-03:55
November 2010.79 01-NOV-09:09 1731.20 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 7.43 19-NOV-15:10 1184.69 21-NOV-04:00
December 2010.79 01-DEC-10:09 1642.47 06-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2073.09 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   171.40  
Maximum of Months 2010.79   1746.86   2276.32   0.00 0.00 0.00 0.00 312.16   2122.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1041.60 03-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1139.71 07-JAN-18:03
February 1295.83 01-FEB-10:09 1104.65 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 12.36 28-FEB-15:00 1398.19 12-FEB-00:55
March 1295.83 01-MAR-10:09 1055.36 21-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 30.96 30-MAR-16:00 902.17 22-MAR-03:00
April 1295.83 03-APR-09:09 962.92 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 35.43 16-APR-14:00 456.92 05-APR-05:00
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 57.90 29-MAY-18:00 364.56 10-MAY-04:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 199.03 25-JUN-16:06 267.83 07-JUN-03:00
July 1295.83 03-JUL-09:09 780.24 27-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 199.11 08-JUL-18:53 186.78 28-JUL-22:00
August 1295.83 01-AUG-09:09 927.22 24-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 199.87 06-AUG-13:53 103.15 25-AUG-04:50
September 1295.83 01-SEP-09:09 1002.40 29-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 82.22 17-SEP-15:00 247.71 29-SEP-05:00
October 1295.83 02-OCT-09:09 1125.75 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 51.03 09-OCT-15:53 540.44 28-OCT-03:55
November 1295.83 01-NOV-09:09 1109.23 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 21.03 19-NOV-15:20 779.51 07-NOV-02:00
December 1295.83 01-DEC-10:09 1043.73 06-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1345.39 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   103.15  
Maximum of Months 1295.83   1125.75   1466.95   0.00 0.00 0.00 0.00 199.87   1398.19  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1623.64 03-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1714.67 07-JAN-18:03
February 2010.83 01-FEB-10:09 1714.17 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 18.54 28-FEB-15:00 2090.14 11-FEB-19:00
March 2010.83 01-MAR-10:09 1647.29 21-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 46.28 30-MAR-16:00 1355.25 22-MAR-03:00
April 2010.83 03-APR-09:09 1540.88 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 42.04 16-APR-13:48 705.54 05-APR-05:00
May 2010.83 01-MAY-09:09 1291.26 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 79.58 29-MAY-18:00 546.83 10-MAY-04:00
June 2010.83 01-JUN-09:09 1204.79 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 298.84 11-JUN-15:00 406.23 07-JUN-03:00
July 2010.83 03-JUL-09:09 1357.13 27-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 285.90 08-JUL-18:53 296.49 28-JUL-22:00
August 2010.83 01-AUG-09:09 1496.77 24-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 294.84 06-AUG-13:53 174.71 25-AUG-04:50
September 2010.83 01-SEP-09:09 1574.82 29-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 76.16 17-SEP-15:00 373.21 29-SEP-05:00
October 2010.83 02-OCT-09:09 1746.90 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 42.58 09-OCT-15:45 836.76 28-OCT-03:55
November 2010.83 01-NOV-09:09 1724.83 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1222.22 07-NOV-02:00
December 2010.83 01-DEC-10:09 1625.19 06-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2007.92 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1204.79   2276.35   0.00 0.00 0.00 0.00 0.00   174.71  
Maximum of Months 2010.83   1746.90   2276.35   0.00 0.00 0.00 0.00 298.84   2090.14  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1059.66 03-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 1186.79 07-JAN-18:10
February 1295.83 01-FEB-10:09 1104.65 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 12.36 28-FEB-15:00 1508.37 11-FEB-18:13
March 1295.83 01-MAR-10:09 1067.00 21-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 30.96 30-MAR-16:00 1035.07 22-MAR-03:00
April 1295.83 03-APR-09:09 1009.83 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 31.44 16-APR-13:48 541.04 05-APR-05:00
May 1295.83 01-MAY-09:09 936.23 24-MAY-07:30 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 59.35 07-MAY-12:30 393.41 10-MAY-04:00
June 1295.83 01-JUN-09:09 827.21 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 188.31 25-JUN-16:04 312.79 07-JUN-03:00
July 1295.83 03-JUL-09:09 906.24 27-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 169.46 08-JUL-19:10 236.26 28-JUL-22:00
August 1295.83 01-AUG-09:09 981.31 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 196.59 06-AUG-13:53 155.15 29-AUG-03:10
September 1295.83 01-SEP-09:09 1029.28 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 58.30 24-SEP-13:10 286.55 30-SEP-19:00
October 1295.83 02-OCT-09:09 1125.75 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 28.27 09-OCT-14:26 619.77 28-OCT-03:55
November 1295.83 01-NOV-09:09 1116.98 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 886.04 07-NOV-02:00
December 1295.83 01-DEC-10:09 1060.79 06-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1527.89 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   827.21   1466.94   0.00 0.00 0.00 0.00 0.00   155.15  
Maximum of Months 1295.83   1125.75   1466.94   0.00 0.00 0.00 0.00 196.59   1527.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1642.65 03-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3756.01 07-JAN-18:03
February 2010.79 01-FEB-10:09 1715.18 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 208.74 26-FEB-13:30 4405.36 11-FEB-18:03
March 2010.79 01-MAR-10:09 1651.92 21-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 124.73 11-MAR-16:00 2724.53 22-MAR-03:00
April 2010.79 03-APR-09:09 1542.97 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 201.39 16-APR-12:10 1525.68 05-APR-04:53
May 2010.79 01-MAY-09:09 1217.22 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 256.39 07-MAY-11:57 1218.38 10-MAY-04:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 732.99 11-JUN-14:53 900.45 07-JUN-03:00
July 2010.79 03-JUL-09:09 1318.92 27-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 686.55 08-JUL-18:53 629.80 28-JUL-22:00
August 2010.79 01-AUG-09:09 1492.69 24-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 732.74 06-AUG-14:00 417.44 25-AUG-05:00
September 2010.79 01-SEP-09:09 1589.15 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 290.62 17-SEP-15:00 822.32 29-SEP-05:00
October 2010.79 02-OCT-09:09 1746.96 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 308.96 08-OCT-14:00 1645.26 28-OCT-03:55
November 2010.79 01-NOV-09:09 1731.72 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 142.45 19-NOV-14:53 2557.92 30-NOV-22:03
December 2010.79 01-DEC-10:09 1645.57 06-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3918.88 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   417.44  
Maximum of Months 2010.79   1746.96   2276.32   0.00 0.00 0.00 0.00 732.99   4405.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1042.67 03-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2492.16 07-JAN-18:03
February 1239.33 01-FEB-08:09 1104.82 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 68.35 26-FEB-15:20 2933.18 11-FEB-18:03
March 1239.33 01-MAR-08:09 1056.20 21-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 73.33 11-MAR-16:00 1795.65 22-MAR-03:00
April 1239.33 03-APR-07:10 965.55 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 72.63 08-APR-17:02 1014.66 05-APR-04:57
May 1239.33 01-MAY-07:10 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 130.24 29-MAY-18:00 823.28 10-MAY-04:00
June 1239.33 01-JUN-07:10 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 451.06 25-JUN-15:51 619.62 07-JUN-03:00
July 1239.33 03-JUL-07:10 785.39 27-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 441.36 08-JUL-18:53 419.25 01-JUL-20:00
August 1239.33 01-AUG-07:10 930.20 24-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 478.50 06-AUG-14:00 276.48 25-AUG-05:00
September 1239.33 01-SEP-07:10 1003.96 29-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 191.67 17-SEP-15:00 543.22 29-SEP-05:00
October 1239.33 02-OCT-07:10 1125.76 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 136.79 09-OCT-16:00 1103.98 28-OCT-03:55
November 1239.33 01-NOV-07:10 1109.54 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 68.54 19-NOV-14:53 1702.61 30-NOV-22:03
December 1239.33 01-DEC-08:09 1044.76 06-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2610.77 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   276.48  
Maximum of Months 1239.33   1125.76   1466.95   0.00 0.00 0.00 0.00 478.50   2933.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1627.61 03-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3808.54 07-JAN-18:03
February 2010.83 01-FEB-10:09 1715.22 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 38.76 28-FEB-15:00 4633.12 11-FEB-18:03
March 2010.83 01-MAR-10:09 1650.36 21-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 105.25 30-MAR-16:00 2767.07 22-MAR-03:00
April 2010.83 03-APR-09:09 1546.99 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 94.08 16-APR-14:10 1535.00 05-APR-04:57
May 2010.83 01-MAY-09:09 1303.38 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 199.25 07-MAY-12:00 1240.83 10-MAY-04:00
June 2010.83 01-JUN-09:09 1219.75 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 692.63 11-JUN-14:53 908.15 07-JUN-03:00
July 2010.83 03-JUL-09:09 1368.21 27-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 666.35 08-JUL-18:53 633.56 28-JUL-22:00
August 2010.83 01-AUG-09:09 1504.10 24-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 698.99 06-AUG-13:57 430.18 25-AUG-05:00
September 2010.83 01-SEP-09:09 1580.12 29-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 158.82 06-SEP-12:00 828.14 29-SEP-05:00
October 2010.83 02-OCT-09:09 1746.99 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 83.77 10-OCT-16:00 1763.86 28-OCT-03:55
November 2010.83 01-NOV-09:09 1725.64 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2603.06 07-NOV-02:00
December 2010.83 01-DEC-10:09 1629.12 06-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4070.71 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1219.75   2276.35   0.00 0.00 0.00 0.00 0.00   430.18  
Maximum of Months 2010.83   1746.99   2276.35   0.00 0.00 0.00 0.00 698.99   4633.12  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1060.19 03-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 2552.03 07-JAN-18:03
February 1295.83 01-FEB-10:09 1104.82 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 116.49 26-FEB-13:10 3188.22 11-FEB-18:03
March 1295.83 01-MAR-10:09 1067.45 21-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 70.51 30-MAR-16:00 1867.01 22-MAR-03:00
April 1295.83 03-APR-09:09 1010.70 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 113.81 16-APR-12:10 1037.71 05-APR-04:57
May 1295.83 01-MAY-09:09 937.32 24-MAY-07:30 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 166.62 07-MAY-11:57 853.79 10-MAY-04:00
June 1295.83 01-JUN-09:09 829.34 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 419.81 25-JUN-16:00 640.43 07-JUN-03:00
July 1295.83 03-JUL-09:09 907.89 27-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 393.00 08-JUL-19:10 438.76 28-JUL-22:00
August 1295.83 01-AUG-09:09 982.39 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 469.96 06-AUG-14:00 304.07 25-AUG-05:00
September 1295.83 01-SEP-09:09 1030.02 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 164.71 24-SEP-12:50 550.34 29-SEP-05:00
October 1295.83 02-OCT-09:09 1125.76 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 111.85 08-OCT-14:00 1150.14 28-OCT-03:55
November 1295.83 01-NOV-09:09 1117.07 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1709.05 30-NOV-22:03
December 1295.83 01-DEC-10:09 1061.31 06-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2682.70 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   829.34   1466.94   0.00 0.00 0.00 0.00 0.00   304.07  
Maximum of Months 1295.83   1125.76   1466.94   0.00 0.00 0.00 0.00 469.96   3188.22  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1642.55 03-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4461.86 07-JAN-18:03
February 2010.79 01-FEB-10:09 1715.14 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 365.55 26-FEB-13:30 5527.50 12-FEB-00:55
March 2010.79 01-MAR-10:09 1651.82 21-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 169.12 11-MAR-16:00 3374.03 22-MAR-04:55
April 2010.79 03-APR-09:09 1542.80 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 254.05 16-APR-12:00 1820.78 05-APR-04:53
May 2010.79 01-MAY-09:09 1217.03 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 268.89 07-MAY-12:20 1398.77 10-MAY-04:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 843.00 11-JUN-14:53 1105.59 07-JUN-03:00
July 2010.79 03-JUL-09:09 1318.61 27-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 741.01 08-JUL-18:53 763.15 01-JUL-20:00
August 2010.79 01-AUG-09:09 1492.47 24-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 862.54 06-AUG-14:00 515.56 25-AUG-05:00
September 2010.79 01-SEP-09:09 1589.00 29-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 310.32 17-SEP-15:00 928.40 29-SEP-05:00
October 2010.79 02-OCT-09:09 1746.95 30-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 427.14 08-OCT-13:53 1837.83 28-OCT-03:55
November 2010.79 01-NOV-09:09 1731.71 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 432.99 19-NOV-14:53 3160.89 30-NOV-22:03
December 2010.79 01-DEC-10:09 1645.47 06-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4459.86 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   515.56  
Maximum of Months 2010.79   1746.95   2276.32   0.00 0.00 0.00 0.00 862.54   5527.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1042.62 03-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3092.16 07-JAN-05:09
February 1295.83 01-FEB-10:09 1104.79 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 131.46 26-FEB-16:00 3685.03 12-FEB-01:00
March 1295.83 01-MAR-10:09 1056.15 21-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 98.13 11-MAR-16:00 2249.23 22-MAR-05:00
April 1295.83 03-APR-09:09 965.47 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 90.14 16-APR-14:00 1215.89 05-APR-04:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 143.37 29-MAY-17:40 949.40 10-MAY-04:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 530.52 25-JUN-15:51 764.19 07-JUN-03:00
July 1295.83 03-JUL-09:09 785.28 27-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 475.86 08-JUL-18:50 552.43 01-JUL-20:00
August 1295.83 01-AUG-09:09 930.10 24-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 588.78 06-AUG-14:00 343.56 25-AUG-05:00
September 1295.83 01-SEP-09:09 1003.89 29-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 205.07 17-SEP-15:00 616.03 29-SEP-05:00
October 1295.83 02-OCT-09:09 1125.76 30-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 171.65 08-OCT-14:10 1238.64 28-OCT-03:55
November 1295.83 01-NOV-09:09 1109.54 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 255.17 19-NOV-14:53 2105.20 30-NOV-22:03
December 1295.83 01-DEC-10:09 1044.71 06-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2973.50 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   343.56  
Maximum of Months 1295.83   1125.76   1466.95   0.00 0.00 0.00 0.00 588.78   3685.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1627.51 03-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 4541.40 07-JAN-05:10
February 2010.83 01-FEB-10:09 1715.18 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 42.24 28-FEB-15:00 5527.34 12-FEB-00:55
March 2010.83 01-MAR-10:09 1650.27 21-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 127.00 30-MAR-16:00 3373.76 22-MAR-05:00
April 2010.83 03-APR-09:09 1546.82 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 113.65 16-APR-14:00 1832.72 05-APR-04:53
May 2010.83 01-MAY-09:09 1303.18 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 208.07 29-MAY-17:40 1430.49 10-MAY-04:00
June 2010.83 01-JUN-09:09 1219.33 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 797.57 11-JUN-15:00 1116.68 07-JUN-03:00
July 2010.83 03-JUL-09:09 1367.89 27-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 715.21 08-JUL-18:53 768.18 01-JUL-20:00
August 2010.83 01-AUG-09:09 1503.88 24-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 856.57 06-AUG-13:57 533.45 25-AUG-05:00
September 2010.83 01-SEP-09:09 1579.98 29-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 193.87 06-SEP-12:00 936.88 29-SEP-05:00
October 2010.83 02-OCT-09:09 1746.99 30-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 102.07 10-OCT-16:00 2003.67 28-OCT-03:55
November 2010.83 01-NOV-09:09 1725.63 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3163.89 30-NOV-22:03
December 2010.83 01-DEC-10:09 1629.03 06-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4460.39 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1219.33   2276.35   0.00 0.00 0.00 0.00 0.00   533.45  
Maximum of Months 2010.83   1746.99   2276.35   0.00 0.00 0.00 0.00 856.57   5527.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1060.13 03-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3092.01 07-JAN-05:09
February 1295.83 01-FEB-10:09 1104.79 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 181.73 26-FEB-13:30 3819.41 11-FEB-18:03
March 1295.83 01-MAR-10:09 1067.39 21-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 84.97 30-MAR-16:00 2249.41 22-MAR-05:00
April 1295.83 03-APR-09:09 1010.59 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 149.53 16-APR-12:00 1245.15 05-APR-04:53
May 1295.83 01-MAY-09:09 937.24 24-MAY-07:30 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 184.58 07-MAY-12:00 992.42 10-MAY-04:00
June 1295.83 01-JUN-09:09 829.09 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 512.47 25-JUN-16:00 788.46 07-JUN-03:00
July 1295.83 03-JUL-09:09 907.69 27-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 476.78 08-JUL-19:10 532.13 01-JUL-20:00
August 1295.83 01-AUG-09:09 982.25 24-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 581.75 06-AUG-14:00 377.75 25-AUG-05:00
September 1295.83 01-SEP-09:09 1029.92 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 191.03 24-SEP-13:10 630.66 29-SEP-05:00
October 1295.83 02-OCT-09:09 1125.76 30-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 171.43 08-OCT-13:43 1308.03 28-OCT-03:55
November 1295.83 01-NOV-09:09 1117.06 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 24.17 19-NOV-14:53 2113.81 30-NOV-22:03
December 1295.83 01-DEC-10:09 1061.25 06-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2973.28 17-DEC-04:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   829.09   1466.94   0.00 0.00 0.00 0.00 0.00   377.75  
Maximum of Months 1295.83   1125.76   1466.94   0.00 0.00 0.00 0.00 581.75   3819.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4375.82 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4375.82 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4375.82 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4375.82 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4375.82 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4375.82 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4375.82 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4375.82 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4375.82 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4375.82 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4375.82 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4375.82 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4375.82   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4375.82   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 3797.53 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.51 28-FEB-15:00 4728.82 12-FEB-00:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.40 30-MAR-16:00 3029.51 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 116.94 16-APR-14:00 1520.98 05-APR-05:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 189.86 07-MAY-11:53 1200.03 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 630.49 11-JUN-15:00 822.28 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 617.07 08-JUL-18:53 593.05 28-JUL-24:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 651.47 06-AUG-14:00 378.87 25-AUG-04:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 215.53 17-SEP-14:55 829.62 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 119.96 09-OCT-16:00 1775.75 28-OCT-03:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2591.09 21-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4571.31 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   378.87  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 651.47   4728.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 6467.68 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 123.87 26-FEB-14:53 7985.03 12-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 138.73 11-MAR-16:00 5102.04 22-MAR-03:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 237.92 16-APR-11:53 2639.49 05-APR-04:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 365.70 07-MAY-12:10 2141.47 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1180.55 11-JUN-14:53 1460.32 07-JUN-03:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1134.89 08-JUL-18:53 1038.10 28-JUL-22:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1200.59 06-AUG-13:53 688.81 25-AUG-05:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 431.44 17-SEP-15:00 1474.58 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 298.94 09-OCT-15:43 3006.15 28-OCT-03:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 141.26 19-NOV-14:53 4428.69 21-NOV-04:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7570.55 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   688.81  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1200.59   7985.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 7097.68 07-JAN-18:03
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.92 26-FEB-14:48 8420.72 11-FEB-18:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 115.17 30-MAR-16:00 4966.15 22-MAR-05:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 137.76 16-APR-14:00 2849.45 05-APR-04:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 204.20 29-MAY-18:00 2141.46 10-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 946.35 11-JUN-15:00 1668.01 07-JUN-03:05
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1009.44 08-JUL-18:53 1187.04 01-JUL-20:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 958.23 06-AUG-14:00 756.03 25-AUG-04:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 229.45 17-SEP-15:00 1399.22 29-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 222.21 08-OCT-13:53 3048.97 28-OCT-03:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 412.50 19-NOV-14:53 4644.26 30-NOV-22:03
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 7105.81 17-DEC-04:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   756.03  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1009.44   8420.72  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 102961.10 02-JAN-04:01 0.00 6035.59 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
February 104385.79 21-FEB-04:03 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
March 101571.86 13-MAR-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
April 96045.81 06-APR-04:02 0.00 8622.27 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 99277.75 15-MAY-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
June 95028.93 08-JUN-04:03 0.00 6897.82 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
July 84179.44 03-JUL-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
August 78594.81 27-AUG-16:51 6283.29 6035.59 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
September 93178.94 29-SEP-04:03 0.00 6897.82 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
October 101428.04 30-OCT-03:13 0.00 2586.68 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
November 103725.94 06-NOV-04:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
December 105405.35 18-DEC-04:01 0.00 7760.04 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 78594.81   0.00 2586.68 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 105405.35   6283.29 8622.27 121117.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 86128.40 02-JAN-04:01 0.00 5420.38 56400.06 0.00 0.00 0.00 0.00 0.00 0.00
February 85071.83 21-FEB-04:03 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
March 86172.70 13-MAR-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
April 84808.72 04-APR-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
May 86849.23 08-MAY-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
June 83375.16 06-JUN-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
July 83743.10 29-JUL-03:02 0.00 3871.70 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
August 81980.62 14-AUG-05:05 9673.43 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
September 89365.34 18-SEP-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
October 91731.20 10-OCT-03:03 0.00 4646.04 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
November 90065.63 06-NOV-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 88011.33 26-DEC-04:01 0.00 6969.07 72514.36 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 81980.62   0.00 3097.36 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 91731.20   9673.43 9292.09 72514.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 25816.36 31-JAN-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 75590.28 28-FEB-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 77551.76 31-MAR-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 77995.79 20-APR-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
May 79382.06 31-MAY-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 79524.98 20-JUN-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 78404.63 11-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 76432.33 22-AUG-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 79574.33 18-SEP-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 78258.10 11-OCT-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
November 77098.65 03-NOV-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 74395.19 13-DEC-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 25816.36   0.00 3871.70 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 79574.33   15316.26 13937.56 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 25138.78 20-JAN-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 34665.89 28-FEB-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 73752.34 29-MAR-05:03 6448.95 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 76069.56 21-APR-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 79367.45 22-MAY-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 80446.68 19-JUN-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 78790.82 11-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 77449.51 11-AUG-03:02 0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
September 79313.24 05-SEP-03:02 0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
October 77038.49 19-OCT-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
November 69767.84 04-NOV-05:03 6448.95 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
December 50927.27 13-DEC-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 25138.78   0.00 3097.36 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 80446.68   15316.26 13937.56 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3453.45 31-JAN-14:50 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 28.42
February 5685.65 28-FEB-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 18.54 0.00
March 7062.26 30-MAR-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 36.77 0.00
April 11162.32 03-APR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 72.86
May 11368.36 30-MAY-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 17.28
June 15469.13 25-JUN-16:41 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 231.63 0.00
July 14551.64 16-JUL-13:43 404.87 238.90 3035.09 0.00 0.00 0.00 0.00 120.49 0.00
August 13469.10 06-AUG-16:21 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 220.86 0.00
September 11336.78 01-SEP-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 22.75
October 11230.63 02-OCT-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 35.98
November 5382.37 02-NOV-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 7.53
December 5182.40 13-DEC-12:00 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 28.75
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3453.45   404.87 238.90 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15469.13   2010.79 1075.02 5311.41 0.00 0.00 0.00 0.00 231.63 72.86



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2586.66 31-JAN-10:30 2591.66 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 55.74
February 6198.65 27-FEB-09:40 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 63.24
March 7061.44 14-MAR-09:30 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 36.09
April 10859.30 16-APR-09:43 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 61.48
May 11143.49 29-MAY-09:53 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 21.54
June 16108.83 04-JUN-09:02 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 26.20
July 15687.28 04-JUL-09:32 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 7.01
August 16101.28 27-AUG-09:42 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 3.84
September 15693.83 04-SEP-09:32 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 11.30
October 9466.10 09-OCT-09:43 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 77.49
November 5840.79 06-NOV-09:30 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 62.39
December 3293.43 12-DEC-11:10 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 33.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2586.66   195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 3.84
Maximum of Months 16108.83   2591.66 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 77.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8679.87 27-JAN-14:20 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 133.78
February 18475.68 26-FEB-14:13 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 86.68
March 13535.02 30-MAR-13:30 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 31.45 0.00
April 18090.85 16-APR-13:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 30.81 0.00
May 13254.94 30-MAY-03:02 0.00 486.14 5058.56 0.00 0.00 0.00 0.00 0.00 63.03
June 17922.27 25-JUN-16:41 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 228.46 0.00
July 17280.68 23-JUL-16:51 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 138.08 0.00
August 18320.62 27-AUG-13:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 145.56 0.00
September 18634.72 24-SEP-13:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 33.13 0.00
October 19346.07 09-OCT-14:22 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 8.84
November 18877.28 11-NOV-13:53 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 231.53
December 16228.73 10-DEC-13:33 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 156.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8679.87   0.00 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19346.07   2010.83 1075.05 5311.49 0.00 0.00 0.00 0.00 228.46 231.53



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4678.72 20-JAN-16:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 44.51
February 13195.60 26-FEB-15:32 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 51.30
March 18083.82 19-MAR-15:53 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 100.89
April 20225.21 09-APR-16:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 38.32
May 20719.33 21-MAY-17:32 0.00 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 42.43
June 21889.36 25-JUN-16:01 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 128.08 0.00
July 22284.82 23-JUL-16:51 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 36.02 0.00
August 21455.09 13-AUG-16:22 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 49.12 0.00
September 17542.70 03-SEP-15:23 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 22.83 0.00
October 19826.44 09-OCT-14:22 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 11.73 0.00
November 17288.15 05-NOV-15:43 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 23.54
December 16122.85 13-DEC-06:02 652.28 626.56 3259.86 0.00 0.00 0.00 0.00 0.00 36.92
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4678.72   0.00 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22284.82   1239.33 692.79 3422.85 0.00 0.00 0.00 0.00 128.08 100.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2132.60 31-JAN-17:00 1923.11 1292.54 2276.32 0.00 0.00 0.00 0.00 0.00 59.62
February 3977.20 28-FEB-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 38.76 0.00
March 6102.55 30-MAR-16:00 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 105.77 0.00
April 7440.48 12-APR-15:15 3846.22 2150.05 4552.64 0.00 0.00 0.00 0.00 47.30 0.00
May 10574.97 30-MAY-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 38.37
June 10845.21 01-JUN-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 81.68
July 11622.74 17-JUL-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 2.79
August 11596.57 10-AUG-03:02 0.00 486.13 5058.48 0.00 0.00 0.00 0.00 0.00 0.00
September 10670.95 01-SEP-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 53.93
October 9589.13 19-OCT-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 66.12
November 3540.01 03-NOV-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 30.58
December 2772.18 13-DEC-13:20 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 79.07
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2132.60   0.00 486.13 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11622.74   3846.22 2150.05 5058.48 0.00 0.00 0.00 0.00 105.77 81.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1715.35 31-JAN-17:00 1239.33 867.69 1466.95 0.00 0.00 0.00 0.00 0.00 38.96
February 4471.64 27-FEB-10:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 130.58
March 5551.73 14-MAR-10:10 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 72.51
April 9798.36 16-APR-11:23 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 9.63
May 16079.79 07-MAY-09:43 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 130.94
June 16842.28 04-JUN-09:52 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 25.61
July 16119.88 23-JUL-08:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 117.96
August 16246.05 27-AUG-08:32 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 22.67
September 15860.22 04-SEP-09:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 30.00
October 6644.26 11-OCT-10:10 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 13.46
November 3888.99 06-NOV-09:50 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 152.34
December 2206.56 13-DEC-06:02 652.28 626.56 3259.88 0.00 0.00 0.00 0.00 0.00 71.76
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1715.35   195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 9.63
Maximum of Months 16842.28   1239.33 867.69 3259.88 0.00 0.00 0.00 0.00 0.00 152.34



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8375.01 27-JAN-14:50 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 217.78
February 16980.77 26-FEB-13:03 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 308.89
March 13062.67 30-MAR-14:30 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 90.46 0.00
April 14221.80 16-APR-13:23 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 55.98 0.00
May 12404.48 30-MAY-05:02 1012.19 972.28 5058.56 0.00 0.00 0.00 0.00 0.00 39.26
June 12099.34 26-JUN-05:02 1012.19 972.28 5058.56 0.00 0.00 0.00 0.00 0.00 19.80
July 15425.73 09-JUL-14:13 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 388.75 0.00
August 16980.64 13-AUG-15:31 809.75 477.82 6070.27 0.00 0.00 0.00 0.00 230.71 0.00
September 17197.79 24-SEP-12:03 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 83.88 0.00
October 18419.53 09-OCT-14:32 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 23.20
November 17806.27 11-NOV-13:53 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 550.58
December 14720.34 10-DEC-14:23 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 366.96
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8375.01   303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18419.53   2010.83 1075.05 6070.27 0.00 0.00 0.00 0.00 388.75 550.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2182.46 20-JAN-16:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 106.00
February 6525.21 27-FEB-17:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 10.89
March 8942.01 30-MAR-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 70.51 0.00
April 16655.80 09-APR-17:11 0.00 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 102.56
May 16536.61 21-MAY-18:23 0.00 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 141.42
June 18089.17 04-JUN-16:32 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 109.99 0.00
July 18121.22 02-JUL-17:32 0.00 230.94 2933.87 0.00 0.00 0.00 0.00 88.08 0.00
August 18170.86 13-AUG-18:11 0.00 269.43 3422.85 0.00 0.00 0.00 0.00 89.77 0.00
September 17201.80 04-SEP-16:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 23.06 0.00
October 14644.98 09-OCT-16:33 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 5.99 0.00
November 6113.67 06-NOV-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 77.92
December 3389.93 11-DEC-15:40 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 33.81
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2182.46   0.00 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18170.86   1239.33 692.79 3422.85 0.00 0.00 0.00 0.00 109.99 141.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2143.19 20-JAN-17:00 1923.11 1322.11 2276.32 0.00 0.00 0.00 0.00 0.00 156.68
February 3451.77 28-FEB-15:30 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 3.00
March 6772.29 30-MAR-15:50 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 125.97 0.00
April 6984.35 19-APR-14:30 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 57.48 0.00
May 11986.70 30-MAY-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 47.90
June 14485.39 25-JUN-16:52 506.08 298.63 3793.86 0.00 0.00 0.00 0.00 646.67 0.00
July 16590.94 09-JUL-14:13 404.87 238.90 3035.09 0.00 0.00 0.00 0.00 475.04 0.00
August 16738.18 13-AUG-18:11 0.00 418.08 5311.41 0.00 0.00 0.00 0.00 242.34 0.00
September 12100.42 06-SEP-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 40.56
October 8020.35 19-OCT-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 84.41
November 3121.82 03-NOV-15:00 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 46.04
December 2375.37 13-DEC-15:10 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 93.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2143.19   0.00 238.90 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16738.18   1923.11 1322.11 5311.41 0.00 0.00 0.00 0.00 646.67 156.68



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1686.57 31-JAN-17:00 1239.33 867.51 1466.95 0.00 0.00 0.00 0.00 0.00 45.67
February 3319.31 28-FEB-15:00 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 28.16 0.00
March 5321.96 30-MAR-11:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 38.68
April 9640.22 16-APR-11:13 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 23.35
May 16443.57 07-MAY-09:13 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 197.78
June 16378.97 11-JUN-09:53 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 108.13
July 16581.29 02-JUL-10:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 19.92
August 16614.86 27-AUG-08:32 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 28.47
September 15582.24 04-SEP-09:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 40.93
October 6362.27 11-OCT-10:20 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 9.15
November 2548.23 02-NOV-15:10 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 24.08
December 1886.41 13-DEC-15:10 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 59.79
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1686.57   195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16614.86   1295.83 867.51 1955.93 0.00 0.00 0.00 0.00 28.16 197.78



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6855.86 11-JAN-14:50 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 197.56
February 13060.01 21-FEB-14:30 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 51.39
March 13549.21 30-MAR-13:50 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 95.79 0.00
April 14032.63 17-APR-14:20 3846.30 2150.10 4552.71 0.00 0.00 0.00 0.00 46.73 0.00
May 14536.57 30-MAY-05:02 1012.19 972.28 5058.56 0.00 0.00 0.00 0.00 0.00 48.59
June 15318.54 25-JUN-16:12 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 722.05 0.00
July 19094.98 09-JUL-14:13 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 456.37 0.00
August 19227.61 13-AUG-18:11 0.00 462.01 5311.49 0.00 0.00 0.00 0.00 227.68 0.00
September 20016.81 24-SEP-14:23 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 73.85 0.00
October 20155.04 09-OCT-14:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 28.76
November 13458.95 06-NOV-14:10 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 174.18
December 9459.62 12-DEC-13:50 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 47.04
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 6855.86   0.00 238.91 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20155.04   3846.30 2150.10 5311.49 0.00 0.00 0.00 0.00 722.05 197.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2161.59 20-JAN-16:40 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 126.78
February 6220.83 27-FEB-17:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 14.29
March 9425.26 30-MAR-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 84.97 0.00
April 18237.77 09-APR-17:03 0.00 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 121.32
May 19119.27 21-MAY-17:32 0.00 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 152.58
June 19630.62 11-JUN-17:12 0.00 230.94 2933.87 0.00 0.00 0.00 0.00 192.95 0.00
July 18835.56 09-JUL-16:52 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 302.21 0.00
August 19938.20 13-AUG-18:11 0.00 269.43 3422.85 0.00 0.00 0.00 0.00 93.14 0.00
September 18700.16 04-SEP-16:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 25.83 0.00
October 10723.33 09-OCT-15:23 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 48.85 0.00
November 5675.87 06-NOV-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 99.76
December 2633.41 12-DEC-14:40 1295.83 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 24.88
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2161.59   0.00 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19938.20   1295.83 692.79 3422.85 0.00 0.00 0.00 0.00 302.21 152.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3112.19 21-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 478.37
February 4898.95 28-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 210.53
March 5940.94 14-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 148.46
April 8383.90 17-APR-14:35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.38 0.00
May 11597.54 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40.77
June 10497.08 19-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.45
July 13653.78 17-JUL-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.78
August 13244.13 14-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.75
September 10105.33 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.22
October 10606.47 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 99.07
November 7478.08 06-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 232.21
December 4524.35 13-DEC-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 115.95
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3112.19   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13653.78   0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.38 478.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5743.62 26-JAN-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4290.86
February 7030.70 12-FEB-05:41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7241.08
March 4455.49 31-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 313.71
April 5968.03 17-APR-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.52 0.00
May 6860.36 19-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 8220.29 15-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 98.69
July 8166.90 12-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.57
August 7883.85 08-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.08
September 7504.56 09-SEP-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 4725.56 11-OCT-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 41.06 0.00
November 4511.53 21-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3733.84
December 4997.23 18-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2120.55
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4455.49   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8220.29   0.00 0.00 0.00 0.00 0.00 0.00 0.00 74.52 7241.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1550.67 31-JAN-17:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 143.49
February 6448.90 28-FEB-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 103.31
March 12844.00 30-MAR-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 109.21 0.00
April 18088.49 17-APR-14:35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.12 0.00
May 18653.08 16-MAY-15:27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.41 0.00
June 18511.97 12-JUN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 243.48 0.00
July 20542.99 07-JUL-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 114.65 0.00
August 19496.01 01-AUG-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 191.67 0.00
September 16052.81 06-SEP-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 108.37 0.00
October 11661.40 10-OCT-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72.83 0.00
November 5057.20 06-NOV-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 279.01
December 2936.17 12-DEC-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 78.91
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 1550.67   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20542.99   0.00 0.00 0.00 0.00 0.00 0.00 0.00 243.48 279.01



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1793.76 23-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3911.45 20-FEB-18:00 23.38 45.01 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
March 7149.88 31-MAR-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7880.62 09-APR-18:13 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3474.02 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5336.89 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7253.01 31-JUL-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7820.65 27-AUG-19:03 0.00 90.03 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3257.10 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5157.69 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5832.98 06-NOV-17:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7619.47 19-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1793.76   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7880.62   222.14 405.10 31177.69 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1452.96 20-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3566.53 24-FEB-17:50 70.15 225.06 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6718.38 31-MAR-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7320.07 09-APR-18:13 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3289.77 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5127.65 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6998.47 31-JUL-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7380.41 13-AUG-19:10 0.00 112.53 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
September 2769.61 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4473.53 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5464.86 06-NOV-17:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7060.73 08-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1452.96   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7380.41   222.14 405.10 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1475.45 20-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3568.30 28-FEB-17:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6467.20 31-MAR-23:20 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7377.90 14-APR-18:20 23.38 135.03 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3246.75 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5104.97 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7029.26 31-JUL-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7536.78 20-AUG-16:40 11.69 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 2306.43 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 3987.94 31-OCT-23:20 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5448.70 06-NOV-17:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6947.95 07-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1475.45   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7536.78   222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 90760.85 20-JAN-17:00 4808.68 4375.82 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 182347.88 21-FEB-17:00 4808.68 4375.82 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 357490.70 31-MAR-24:00 0.00 243.11 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 365481.21 16-APR-18:53 0.00 729.33 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
May 174814.64 31-MAY-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 266836.78 30-JUN-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359177.29 31-JUL-24:00 0.00 243.11 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
August 369793.45 07-AUG-21:12 1265.44 2431.11 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00
September 175508.53 30-SEP-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 267813.37 31-OCT-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276316.85 06-NOV-17:00 4808.68 4375.82 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 367153.97 12-DEC-17:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 90760.85   0.00 243.11 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369793.45   4808.68 4375.82 1898162.61 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.155296E+13 1033950.48 31-JAN-16:00 0.287112E+12 1202928.04 09-JAN-06:10
February 0.180817E+13 1305561.21 28-FEB-16:40 0.177352E+12 1240967.67 13-FEB-07:10
March 0.253010E+13 1671877.78 30-MAR-15:20 0.732191E+11 334098.89 22-MAR-05:10
April 0.290120E+13 1917494.28 12-APR-15:30 0.596690E+11 341382.91 06-APR-06:10
May 0.194655E+13 1451851.23 15-MAY-15:30 0.576408E+11 180787.29 15-MAY-14:30
June 0.248408E+13 1635138.32 02-JUN-15:30 0.522634E+11 106010.70 03-JUN-12:09
July 0.299364E+13 1783308.50 07-JUL-15:20 0.483370E+11 66993.32 03-JUL-11:30
August 0.351768E+13 1920628.32 03-AUG-15:50 0.513014E+11 83496.74 25-AUG-13:50
September 0.193337E+13 1404663.71 06-SEP-15:50 0.493820E+11 119287.27 15-SEP-11:39
October 0.216907E+13 1507703.24 02-OCT-15:00 0.579386E+11 326075.64 26-OCT-06:10
November 0.238946E+13 1410497.03 08-NOV-16:19 0.836225E+11 627627.01 22-NOV-07:10
December 0.275684E+13 1534458.37 12-DEC-16:00 0.157542E+12 820477.23 18-DEC-07:10
             
Annual Sum or Average 0.289831E+14     0.115538E+13    
Minimum of Months 0.155296E+13 1033950.48   0.483370E+11 66993.32  
Maximum of Months 0.351768E+13 1920628.32   0.287112E+12 1240967.67  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.231344E+12 0.463080E+11 0.811612E+12 0.162550E+12 0.163223E+12 0.208054E+11 0.00 0.903700E+11 0.189758E+11 0.261573E+10 0.515261E+10 0.00 0.00
February 0.209873E+12 0.389162E+11 0.102011E+13 0.146827E+12 0.152261E+12 0.261118E+11 0.00 0.159025E+12 0.501775E+11 0.183398E+10 0.303801E+10 0.00 0.00
March 0.246600E+12 0.388610E+11 0.146267E+13 0.162740E+12 0.185628E+12 0.449094E+11 0.00 0.282967E+12 0.103757E+12 0.936842E+09 0.102989E+10 0.00 0.00
April 0.219482E+12 0.333882E+11 0.170311E+13 0.157288E+12 0.194422E+12 0.657922E+11 0.00 0.401814E+12 0.124443E+12 0.300734E+09 0.116683E+10 0.00 0.00
May 0.236047E+12 0.308273E+11 0.820521E+12 0.162644E+12 0.219542E+12 0.796727E+11 0.00 0.252205E+12 0.141933E+12 52293235.50 0.310799E+10 0.00 0.00
June 0.234581E+12 0.282204E+11 0.110677E+13 0.157466E+12 0.242531E+12 0.101223E+12 0.00 0.436828E+12 0.170194E+12 14739346.33 0.624499E+10 0.00 0.00
July 0.219917E+12 0.297667E+11 0.143888E+13 0.162465E+12 0.249155E+12 0.116246E+12 0.00 0.578280E+12 0.191978E+12 0.00 0.695173E+10 0.00 0.00
August 0.245315E+12 0.328357E+11 0.177780E+13 0.162740E+12 0.263659E+12 0.124494E+12 0.00 0.701959E+12 0.201155E+12 1033470.14 0.772302E+10 0.00 0.00
September 0.220166E+12 0.357803E+11 0.784732E+12 0.157287E+12 0.214046E+12 0.836361E+11 0.00 0.279713E+12 0.153708E+12 0.00 0.429936E+10 0.00 0.00
October 0.230481E+12 0.413433E+11 0.112899E+13 0.162551E+12 0.189731E+12 0.535793E+11 0.00 0.250915E+12 0.109541E+12 41127621.78 0.189866E+10 0.00 0.00
November 0.228137E+12 0.438366E+11 0.140306E+13 0.157361E+12 0.169731E+12 0.365509E+11 0.00 0.258124E+12 0.900513E+11 0.121548E+10 0.138765E+10 0.00 0.00
December 0.224122E+12 0.473461E+11 0.175516E+13 0.162466E+12 0.166369E+12 0.207894E+11 0.00 0.294807E+12 0.811627E+11 0.193377E+10 0.268268E+10 0.00 0.00
                           
Annual Sum or Average 0.274607E+13 0.447430E+12 0.152134E+14 0.191438E+13 0.241030E+13 0.773810E+12 0.00 0.398701E+13 0.143708E+13 0.894573E+10 0.446834E+11 0.00 0.00
Minimum of Months 0.209873E+12 0.282204E+11 0.784732E+12 0.146827E+12 0.152261E+12 0.207894E+11 0.00 0.903700E+11 0.189758E+11 0.00 0.102989E+10 0.00 0.00
Maximum of Months 0.246600E+12 0.473461E+11 0.177780E+13 0.162740E+12 0.263659E+12 0.124494E+12 0.00 0.701959E+12 0.201155E+12 0.261573E+10 0.772302E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.225769E+12 0.00 0.613422E+11 0.00 0.00
February 0.00 0.00 0.121613E+12 0.00 0.557395E+11 0.00 0.00
March 0.00 0.00 0.103161E+11 0.00 0.629030E+11 0.00 0.00
April 0.00 0.00 0.429589E+10 0.00 0.553731E+11 0.00 0.00
May 0.00 0.00 0.244389E+10 0.00 0.551969E+11 0.00 0.00
June 0.00 0.00 0.998278E+09 0.00 0.512652E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.483370E+11 0.00 0.00
August 0.00 0.00 70433455.49 0.00 0.512310E+11 0.00 0.00
September 0.00 0.00 0.371583E+09 0.00 0.490104E+11 0.00 0.00
October 0.00 0.00 0.453900E+10 0.00 0.533996E+11 0.00 0.00
November 0.00 0.00 0.282424E+11 0.00 0.553801E+11 0.00 0.00
December 0.00 0.00 0.990031E+11 0.00 0.585394E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.497663E+12 0.00 0.657717E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.483370E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.225769E+12 0.00 0.629030E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 256475.52 03-JAN-08:09 37611.08 01-JAN-06:10 439129.89 02-JAN-08:09 117202.11 03-JAN-08:20 90849.27 09-JAN-06:10 44773.73 07-JAN-06:10 0.00 01-JAN-00:10
February 259685.17 01-FEB-08:09 37611.08 01-FEB-06:10 557421.28 01-FEB-08:09 117203.94 01-FEB-08:20 138988.66 28-FEB-15:39 63570.08 28-FEB-14:00 0.00 01-FEB-00:10
March 257110.75 21-MAR-07:10 37611.08 01-MAR-06:10 675712.68 01-MAR-08:09 117202.47 21-MAR-07:19 179545.81 30-MAR-15:20 67377.78 30-MAR-14:00 0.00 01-MAR-00:10
April 252785.46 03-APR-07:10 37611.08 01-APR-05:10 794004.08 03-APR-07:10 117200.01 03-APR-07:19 264728.61 12-APR-15:30 69385.65 12-APR-15:30 0.00 01-APR-00:10
May 241542.09 24-MAY-07:10 37611.08 01-MAY-05:10 439129.89 01-MAY-07:10 117193.60 24-MAY-07:19 250618.32 15-MAY-14:39 67596.57 15-MAY-14:30 0.00 01-MAY-00:10
June 237792.30 23-JUN-07:10 37611.08 01-JUN-05:10 557421.28 01-JUN-07:10 117191.47 23-JUN-07:19 278556.53 02-JUN-15:30 66564.56 02-JUN-15:09 0.00 01-JUN-00:10
July 244540.26 27-JUL-07:10 37611.08 01-JUL-05:10 675712.68 03-JUL-07:10 117195.31 27-JUL-07:19 226238.41 13-JUL-15:39 65746.54 07-JUL-15:00 0.00 01-JUL-00:10
August 250899.87 24-AUG-07:10 37611.08 01-AUG-05:10 794004.08 01-AUG-07:10 117198.93 24-AUG-07:19 242631.06 25-AUG-13:50 67422.77 25-AUG-13:50 0.00 01-AUG-00:10
September 254433.34 29-SEP-07:10 37611.08 01-SEP-05:10 439129.89 01-SEP-07:10 117200.94 29-SEP-07:19 253921.13 14-SEP-14:50 67112.20 13-SEP-14:00 0.00 01-SEP-00:10
October 260952.65 30-OCT-07:10 37611.08 01-OCT-05:10 557421.28 02-OCT-07:10 117204.66 30-OCT-07:19 169462.54 02-OCT-15:00 67390.47 10-OCT-14:30 0.00 01-OCT-00:10
November 260213.11 01-NOV-07:10 37611.08 01-NOV-05:10 675712.68 01-NOV-07:10 117204.24 01-NOV-07:19 138097.21 06-NOV-16:30 43440.89 22-NOV-06:10 0.00 01-NOV-00:10
December 256567.40 06-DEC-08:09 37611.08 01-DEC-06:10 794004.08 01-DEC-08:09 117202.16 06-DEC-08:20 108327.46 12-DEC-14:30 43639.84 18-DEC-07:19 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 237792.30   37611.08   439129.89   117191.47   90849.27   43440.89   0.00  
Maximum of Months 260952.65   37611.08   794004.08   117204.66   278556.53   69385.65   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 110407.97 31-JAN-15:50 50359.83 19-JAN-21:00 5868.07 05-JAN-18:10 5613.48 02-JAN-07:10 0.00 0.00
February 189188.54 28-FEB-14:00 51204.25 28-FEB-13:50 5740.43 03-FEB-18:00 5613.48 01-FEB-07:10 0.00 0.00
March 357101.04 30-MAR-14:00 90905.92 30-MAR-12:50 5578.94 18-MAR-16:10 5613.48 03-MAR-07:10 0.00 0.00
April 416362.16 12-APR-15:30 90905.92 11-APR-13:09 4007.27 05-APR-18:00 5613.48 04-APR-08:00 0.00 0.00
May 303252.73 19-MAY-14:50 90905.92 03-MAY-14:30 2996.15 10-MAY-18:00 5613.48 02-MAY-15:50 0.00 0.00
June 340995.28 06-JUN-12:39 90905.92 01-JUN-09:09 2977.37 10-JUN-16:00 5613.48 01-JUN-06:49 0.00 0.00
July 409618.20 07-JUL-15:00 90905.92 01-JUL-06:00 0.00 01-JUL-00:10 5613.48 01-JUL-06:10 0.00 0.00
August 440803.98 25-AUG-13:50 90905.92 01-AUG-06:49 673.22 06-AUG-13:50 5613.48 01-AUG-06:10 0.00 0.00
September 304639.84 06-SEP-12:20 90905.92 01-SEP-10:50 0.00 01-SEP-00:10 5613.48 01-SEP-08:00 0.00 0.00
October 331459.27 10-OCT-14:09 90905.92 02-OCT-10:20 2667.82 31-OCT-20:00 5613.48 02-OCT-08:39 0.00 0.00
November 210101.95 02-NOV-13:00 53420.01 27-NOV-16:00 4329.22 22-NOV-18:10 5613.48 08-NOV-07:10 0.00 0.00
December 233821.63 12-DEC-14:30 52275.42 13-DEC-11:09 5337.70 02-DEC-17:00 5613.48 01-DEC-07:10 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 110407.97   50359.83   0.00   5613.48   0.00 0.00
Maximum of Months 440803.98   90905.92   5868.07   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1033950.48 31-JAN-16:00 239128.69 439129.89 0.00 83147.88 83794.05 42028.46 0.00 97139.99 49581.53
February 1305561.21 28-FEB-16:40 234435.00 557421.28 0.00 83146.17 134480.94 63547.47 0.00 181935.98 50594.36
March 1671877.78 30-MAR-15:20 234435.00 675712.68 0.00 83146.17 179545.81 66283.74 0.00 341848.45 90905.92
April 1917494.28 12-APR-15:30 234435.00 794004.08 0.00 83146.17 264728.61 69385.65 0.00 416362.16 55432.61
May 1451851.23 15-MAY-15:30 234435.00 439129.89 0.00 83146.17 247941.12 66363.36 0.00 288058.61 90905.92
June 1635138.32 02-JUN-15:30 234435.00 557421.28 0.00 83146.17 278556.53 66465.58 0.00 322336.66 90905.92
July 1783308.50 07-JUL-15:20 234435.00 675712.68 0.00 83146.17 225810.60 65404.76 0.00 402279.88 90905.92
August 1920628.32 03-AUG-15:50 234435.00 794004.08 0.00 83146.17 219917.52 65597.82 0.00 427008.32 90905.92
September 1404663.71 06-SEP-15:50 234435.00 439129.89 0.00 83146.17 197368.05 65315.89 0.00 288749.31 90905.92
October 1507703.24 02-OCT-15:00 234435.00 557421.28 0.00 83146.17 169462.54 64740.98 0.00 301977.86 90905.92
November 1410497.03 08-NOV-16:19 238788.76 675712.68 0.00 83148.27 125930.22 42118.92 0.00 194137.22 49581.53
December 1534458.37 12-DEC-16:00 248793.45 794004.08 0.00 83152.74 98916.93 42156.49 0.00 216185.97 51248.71
                       
Annual Sum or Average                      
Minimum of Months 1033950.48   234435.00 439129.89 0.00 83146.17 83794.05 42028.46 0.00 97139.99 49581.53
Maximum of Months 1920628.32   248793.45 794004.08 0.00 83152.74 278556.53 69385.65 0.00 427008.32 90905.92



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 1197232.17 09-JAN-06:10 0.00 79707.81 30-JAN-12:50 0.00
February 0.00 0.00 1211803.93 13-FEB-07:10 0.00 79719.79 01-FEB-12:20 0.00
March 0.00 0.00 328403.02 22-MAR-05:10 0.00 79101.18 01-MAR-12:30 0.00
April 0.00 0.00 312552.58 06-APR-06:10 0.00 77011.73 03-APR-11:30 0.00
May 0.00 0.00 138922.89 15-MAY-14:30 0.00 74117.42 01-MAY-11:20 0.00
June 0.00 0.00 91487.91 03-JUN-12:09 0.00 69871.07 05-JUN-11:30 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 66993.32 03-JUL-11:30 0.00
August 0.00 0.00 49499.96 25-AUG-13:50 0.00 66815.06 31-AUG-11:00 0.00
September 0.00 0.00 59516.10 15-SEP-11:30 0.00 68710.44 20-SEP-11:39 0.00
October 0.00 0.00 312563.45 26-OCT-06:10 0.00 73622.53 31-OCT-11:20 0.00
November 0.00 0.00 598883.08 22-NOV-07:10 0.00 76219.86 24-NOV-12:39 0.00
December 0.00 0.00 806843.72 18-DEC-07:10 0.00 78776.41 28-DEC-12:50 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 66815.06   0.00
Maximum of Months 0.00 0.00 1211803.93   0.00 79719.79   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.50 27.18 2.67 27.27
February 0.00 0.00 0.00 0.00 1.17 25.79 0.00 25.79
March 0.00 0.00 0.00 0.00 2.67 25.76 0.00 25.76
April 0.00 0.00 0.00 0.00 2.83 25.75 0.00 25.75
May 0.00 0.00 0.00 0.00 4.00 25.92 0.00 25.92
June 0.00 0.00 0.00 0.00 1.83 25.90 0.00 25.90
July 0.00 0.00 0.00 0.00 5.50 26.23 0.17 26.18
August 0.00 0.00 0.00 0.00 6.00 25.98 0.33 25.99
September 0.00 0.00 0.00 0.00 9.00 26.64 0.00 26.64
October 0.00 0.00 0.00 0.00 10.17 26.71 0.00 26.71
November 0.00 0.00 0.00 0.00 11.33 26.85 0.00 26.85
December 0.00 0.00 0.00 0.00 8.17 26.68 1.67 26.81
                 
Annual Sum or Average 0.00   0.00   69.17 26.50 4.83 26.55
Minimum of Months 0.00 0.00 0.00 0.00 1.17 25.75 0.00 25.75
Maximum of Months 0.00 0.00 0.00 0.00 11.33 27.18 2.67 27.27



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.50 25.58 0.00 25.58
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
May 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 1.17 25.60 0.00 25.60
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.33 25.59 0.00 25.59
November 0.00 0.00 0.00 0.00 0.83 25.72 0.00 25.72
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.17 25.63 0.00 25.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 25.72 0.00 25.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.50 18.67 0.33 18.86 0.00 18.86 0.00 18.86
February 1.17 18.98 0.17 19.16 0.00 19.16 0.00 19.16
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 1.50 19.09 0.17 19.21 0.00 19.21 0.00 19.21
                 
Annual Sum or Average 5.17 18.86 0.67 19.03 0.00 19.03 0.00 19.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.50 19.09 0.33 19.21 0.00 19.21 0.00 19.21



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.17 25.59 0.00 25.59
July 0.00 0.00 0.00 0.00 2.00 26.64 0.83 26.85
August 0.00 0.00 0.00 0.00 1.67 25.99 0.33 26.20
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.83 26.31 1.17 26.55
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 2.00 26.64 0.83 26.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.52 0.67 27.52
May 0.00 0.00 0.00 0.00 2.17 27.56 2.17 27.56
June 0.00 0.00 0.00 0.00 3.50 27.71 3.50 27.71
July 0.00 0.00 0.00 0.00 6.50 27.59 6.33 27.59
August 0.00 0.00 0.00 0.00 6.00 27.44 5.67 27.50
September 0.00 0.00 0.00 0.00 1.83 27.57 1.83 27.57
October 0.00 0.00 0.00 0.00 0.67 27.36 0.67 27.36
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   21.33 27.55 20.83 27.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 6.50 27.71 6.33 27.71



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.17 0.00 19.17 0.17 23.22 0.17 24.57
February 0.17 19.36 0.00 19.36 2.33 26.95 2.33 27.22
March 0.00 0.00 0.00 0.00 1.00 27.29 1.00 27.29
April 0.00 0.00 0.00 0.00 1.00 27.45 1.00 27.45
May 0.00 0.00 0.00 0.00 0.33 27.32 0.33 27.32
June 0.00 0.00 0.00 0.00 1.33 27.08 1.00 27.18
July 0.00 0.00 0.00 0.00 4.33 27.06 3.17 27.20
August 0.00 0.00 0.00 0.00 8.17 27.08 5.50 27.27
September 0.00 0.00 0.00 0.00 2.83 27.48 2.83 27.48
October 0.00 0.00 0.00 0.00 5.67 27.65 5.67 27.65
November 0.00 0.00 0.00 0.00 3.67 27.62 3.67 27.62
December 0.00 0.00 0.00 0.00 1.00 27.44 1.00 27.44
                 
Annual Sum or Average 0.33 19.27 0.00 19.27 31.83 27.26 27.67 27.38
Minimum of Months 0.00 0.00 0.00 0.00 0.17 23.22 0.17 24.57
Maximum of Months 0.17 19.36 0.00 19.36 8.17 27.65 5.67 27.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 1.33 27.62 1.17 27.65
March 0.00 0.00 0.00 0.00 6.17 27.41 2.83 27.54
April 0.00 0.00 0.00 0.00 16.00 27.02 5.33 27.17
May 0.00 0.00 0.00 0.00 5.33 27.32 2.00 27.47
June 0.00 0.00 0.00 0.00 22.33 27.01 5.50 27.20
July 0.00 0.00 0.00 0.00 36.00 27.37 9.83 27.52
August 0.00 0.00 0.00 0.00 53.83 27.50 12.17 27.59
September 0.00 0.00 0.00 0.00 9.50 26.94 4.00 27.16
October 0.00 0.00 0.00 0.00 6.00 27.18 3.33 27.41
November 0.00 0.00 0.00 0.00 2.67 27.67 2.67 27.67
December 0.00 0.00 0.00 0.00 0.83 26.84 0.50 27.11
                 
Annual Sum or Average 0.00   0.00   160.00 27.30 49.33 27.44
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 53.83 27.67 12.17 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 11.33 18.88 2.33 19.10 0.00 19.10 0.00 19.10
February 9.00 17.61 2.83 17.81 0.00 17.81 0.00 17.81
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.33 27.31 1.00 27.31
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.17 0.00 19.17 0.00 19.17 0.00 19.17
December 2.83 18.96 0.33 19.07 0.00 19.07 0.00 19.07
                 
Annual Sum or Average 23.50 18.41 5.50 18.57 1.33 18.95 1.00 19.22
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11.33 19.17 2.83 19.17 1.33 27.31 1.00 27.31



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 6.17 18.40 0.17 18.45 0.00 18.45 0.00 18.45
February 4.33 17.05 0.50 16.80 0.00 16.80 0.00 16.80
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.62 0.67 27.62
May 0.00 0.00 0.00 0.00 2.50 27.54 2.50 27.54
June 0.00 0.00 0.00 0.00 5.83 27.67 5.67 27.67
July 0.00 0.00 0.00 0.00 10.33 27.67 9.83 27.67
August 0.00 0.00 0.00 0.00 6.83 27.65 6.67 27.65
September 0.00 0.00 0.00 0.00 1.33 27.59 1.33 27.59
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.33 19.22 0.00 19.22 0.00 19.22 0.00 19.22
December 2.00 18.95 0.00 18.95 0.00 18.95 0.00 18.95
                 
Annual Sum or Average 12.83 18.05 0.67 17.95 27.50 24.45 26.67 25.72
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 6.17 19.22 0.50 19.22 10.33 27.67 9.83 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.67 18.83 0.50 18.95 0.00 18.95 0.00 18.95
February 3.00 17.74 0.50 17.32 1.00 19.62 1.00 21.09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.83 27.36 0.83 27.36
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.17 27.38 2.00 27.38
August 0.00 0.00 0.00 0.00 5.00 27.39 4.67 27.43
September 0.00 0.00 0.00 0.00 2.33 27.50 2.33 27.50
October 0.00 0.00 0.00 0.00 4.83 27.67 4.50 27.69
November 0.17 19.43 0.00 19.43 2.67 27.12 2.67 27.36
December 1.33 19.12 0.00 19.12 0.50 21.38 0.50 22.67
                 
Annual Sum or Average 10.17 18.56 1.00 18.47 19.33 24.20 18.50 25.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.67 19.43 0.50 19.43 5.00 27.67 4.67 27.69



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.17 18.66 0.00 18.66 0.00 18.66 0.00 18.66
February 3.17 17.60 0.67 17.13 0.00 17.13 0.00 17.13
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.50 27.58 1.67 27.56
May 0.00 0.00 0.00 0.00 3.17 27.72 1.67 27.73
June 0.00 0.00 0.00 0.00 6.50 27.68 3.17 27.76
July 0.00 0.00 0.00 0.00 12.83 27.60 5.17 27.71
August 0.00 0.00 0.00 0.00 10.67 27.25 3.67 27.44
September 0.00 0.00 0.00 0.00 3.00 27.61 2.00 27.63
October 0.00 0.00 0.00 0.00 1.00 27.57 0.67 27.57
November 0.33 19.27 0.00 19.27 0.00 19.27 0.00 19.27
December 1.50 19.06 0.00 19.06 0.00 19.06 0.00 19.06
                 
Annual Sum or Average 10.17 18.41 0.67 18.19 39.67 25.52 18.00 26.14
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.17 19.27 0.67 19.27 12.83 27.72 5.17 27.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 48.50 17.00 17.50 17.18 0.00 17.18 0.00 17.18
February 29.67 16.59 10.50 16.79 0.00 16.79 0.00 16.79
March 1.00 19.23 0.00 19.23 0.00 19.23 0.00 19.23
April 0.17 19.32 0.00 19.32 0.00 19.32 0.00 19.32
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 1.83 27.43 1.33 27.42
July 0.00 0.00 0.00 0.00 5.67 27.43 3.00 27.45
August 0.00 0.00 0.00 0.00 2.67 27.32 2.17 27.32
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.17 19.21 0.00 19.21 0.00 19.21 0.00 19.21
November 3.50 18.74 0.50 18.93 0.00 18.93 0.00 18.93
December 24.83 17.25 8.50 17.41 0.00 17.41 0.00 17.41
                 
Annual Sum or Average 107.83 17.03 37.00 17.19 10.17 17.86 6.50 18.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 48.50 19.32 17.50 19.32 5.67 27.43 3.00 27.45



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 26.67 16.21 4.83 16.13 0.00 16.13 0.00 16.13
February 15.50 16.03 2.00 16.05 0.00 16.05 0.00 16.05
March 0.67 19.20 0.00 19.20 0.00 19.20 0.00 19.20
April 0.17 19.38 0.00 19.38 0.50 25.46 0.50 26.33
May 0.00 0.00 0.00 0.00 3.50 27.53 3.33 27.53
June 0.00 0.00 0.00 0.00 9.00 27.69 7.17 27.73
July 0.00 0.00 0.00 0.00 14.67 27.77 11.33 27.80
August 0.00 0.00 0.00 0.00 10.00 27.72 8.33 27.74
September 0.00 0.00 0.00 0.00 1.33 27.58 1.33 27.58
October 0.17 19.25 0.00 19.25 0.00 19.25 0.00 19.25
November 2.00 18.36 0.00 18.36 0.00 18.36 0.00 18.36
December 13.67 16.78 1.50 16.70 0.00 16.70 0.00 16.70
                 
Annual Sum or Average 58.83 16.42 8.33 16.35 39.00 20.52 32.00 22.20
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.05 0.00 16.05
Maximum of Months 26.67 19.38 4.83 19.38 14.67 27.77 11.33 27.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 21.67 16.98 4.50 17.03 0.00 17.03 0.00 17.03
February 13.17 16.79 3.17 16.96 0.50 17.27 0.50 17.56
March 0.33 19.21 0.00 19.21 0.00 19.21 0.00 19.21
April 0.00 0.00 0.00 0.00 0.83 27.43 0.83 27.43
May 0.00 0.00 0.00 0.00 1.17 27.39 1.00 27.39
June 0.00 0.00 0.00 0.00 3.00 27.36 2.33 27.41
July 0.00 0.00 0.00 0.00 8.33 27.46 5.83 27.48
August 0.00 0.00 0.00 0.00 7.50 27.58 5.33 27.63
September 0.00 0.00 0.00 0.00 2.83 27.57 2.83 27.57
October 0.00 0.00 0.00 0.00 4.17 27.60 4.00 27.60
November 1.33 18.41 0.00 18.41 1.00 22.27 1.00 23.82
December 8.33 18.43 1.17 18.56 0.00 18.56 0.00 18.56
                 
Annual Sum or Average 44.83 17.25 8.83 17.33 29.33 20.92 23.67 22.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 17.03 0.00 17.03
Maximum of Months 21.67 19.21 4.50 19.21 8.33 27.60 5.83 27.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 19.33 16.32 3.83 16.12 0.00 16.12 0.00 16.12
February 10.17 16.06 2.17 15.79 0.00 15.79 0.00 15.79
March 0.17 19.19 0.00 19.19 0.00 19.19 0.00 19.19
April 0.00 0.00 0.00 0.00 2.50 27.61 1.50 27.63
May 0.00 0.00 0.00 0.00 3.67 27.82 1.83 27.83
June 0.00 0.00 0.00 0.00 8.50 27.80 3.83 27.87
July 0.00 0.00 0.00 0.00 15.17 27.76 6.00 27.87
August 0.00 0.00 0.00 0.00 12.00 27.49 4.33 27.66
September 0.00 0.00 0.00 0.00 3.67 27.65 2.50 27.66
October 0.00 0.00 0.00 0.00 0.67 27.54 0.50 27.55
November 1.33 18.09 0.00 18.09 0.00 18.09 0.00 18.09
December 6.50 18.07 0.67 17.90 0.00 17.90 0.00 17.90
                 
Annual Sum or Average 37.50 16.63 6.67 16.38 46.17 22.16 20.50 23.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.79 0.00 15.79
Maximum of Months 19.33 19.19 3.83 19.19 15.17 27.82 6.00 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 54.67 27.80 53.67 27.80
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   54.67 27.80 53.67 27.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 54.67 27.80 53.67 27.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 60.67 27.80 60.67 27.80
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   60.67 27.80 60.67 27.80
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 60.67 27.80 60.67 27.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 53.50 27.82 51.33 27.83
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   53.50 27.82 51.33 27.83
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 53.50 27.82 51.33 27.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 57.50 28.02 53.50 28.02
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 428.50 29.00 372.83 29.04
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   486.00 28.88 426.33 28.91
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 428.50 29.00 372.83 29.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 243.00 23.93 64.83 24.23 0.00 24.23
February 170.33 24.16 87.83 24.55 13.00 24.66
March 84.83 24.01 165.33 24.60 1.83 24.59
April 65.83 24.45 249.50 24.73 35.33 24.74
May 152.83 24.58 428.17 24.54 144.17 24.55
June 276.83 24.45 450.50 24.47 276.83 24.46
July 296.67 24.98 497.00 24.73 296.67 24.80
August 241.33 25.00 514.00 24.64 241.33 24.73
September 164.17 25.17 473.67 24.72 164.17 24.81
October 42.67 25.37 306.83 25.01 42.00 25.05
November 52.00 24.82 210.67 25.21 23.17 25.26
December 106.67 24.00 156.83 24.88 2.67 24.87
             
Annual Sum or Average 1897.17 24.57 3605.17 24.67 1241.17 24.71
Minimum of Months 42.67 23.93 64.83 24.23 0.00 24.23
Maximum of Months 296.67 25.37 514.00 25.21 296.67 25.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 327.00 23.89 48.83 23.99 12.67 24.05
February 190.17 24.02 74.33 24.25 9.83 24.32
March 48.17 23.98 182.00 24.51 0.00 24.51
April 9.67 24.00 283.33 24.43 0.00 24.43
May 6.17 23.98 444.33 24.32 0.00 24.32
June 0.00 0.00 455.17 24.24 0.00 24.24
July 0.00 0.00 497.00 24.23 0.00 24.23
August 0.00 0.00 514.00 24.17 0.00 24.17
September 2.33 26.47 475.33 24.35 2.33 24.36
October 14.33 25.66 299.67 24.68 11.00 24.73
November 48.50 24.04 196.83 24.73 1.00 24.74
December 111.50 23.99 136.33 24.61 0.00 24.61
             
Annual Sum or Average 757.83 23.99 3607.17 24.34 36.83 24.35
Minimum of Months 0.00 0.00 48.83 23.99 0.00 24.05
Maximum of Months 327.00 26.47 514.00 24.73 12.67 24.74



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 485.83 22.57 37.83 22.49 37.33 22.42
February 396.50 23.06 42.33 23.04 30.00 22.99
March 219.00 23.72 119.67 23.95 0.00 23.95
April 82.17 23.77 211.67 24.25 1.17 24.26
May 16.00 23.81 421.33 24.23 0.00 24.23
June 5.83 23.71 441.33 24.22 0.00 24.22
July 0.00 0.00 495.50 24.23 0.00 24.23
August 0.00 0.00 514.00 24.19 0.00 24.19
September 9.00 25.43 454.33 24.29 7.17 24.32
October 101.50 23.70 210.33 24.17 14.50 24.20
November 273.50 23.72 80.17 23.85 5.50 23.86
December 428.33 23.20 32.33 23.26 0.00 23.26
             
Annual Sum or Average 2017.67 23.21 3060.83 23.81 95.67 23.79
Minimum of Months 0.00 0.00 32.33 22.49 0.00 22.42
Maximum of Months 485.83 25.43 514.00 24.29 37.33 24.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 496.50 21.11 199.17 20.78 199.17 20.59
February 429.17 21.94 101.17 21.68 95.83 21.48
March 343.33 23.04 99.50 23.22 9.33 23.17
April 163.50 23.35 180.33 23.84 3.83 23.85
May 32.17 23.60 413.83 24.18 0.00 24.18
June 7.67 23.62 442.33 24.25 0.00 24.25
July 0.67 23.15 486.17 24.30 0.00 24.30
August 0.00 0.00 514.00 24.24 0.00 24.24
September 27.83 23.72 421.00 24.24 6.67 24.26
October 265.00 23.04 137.17 23.37 15.33 23.37
November 426.00 22.66 57.50 22.67 31.17 22.61
December 473.00 21.62 134.83 21.39 121.83 21.19
             
Annual Sum or Average 2664.83 22.23 3187.00 23.01 483.17 22.82
Minimum of Months 0.00 0.00 57.50 20.78 0.00 20.59
Maximum of Months 496.50 23.72 514.00 24.30 199.17 24.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 476.00 21.64 146.00 21.45 139.17 21.31
February 405.00 22.32 78.83 22.11 68.33 21.92
March 304.67 23.34 97.00 23.55 0.00 23.55
April 117.33 23.49 216.33 24.00 0.00 24.00
May 34.67 24.11 416.67 24.30 6.67 24.32
June 7.17 24.92 456.33 24.35 3.17 24.36
July 19.17 26.29 497.00 24.48 19.17 24.54
August 9.50 26.71 514.00 24.34 9.50 24.38
September 32.83 25.24 433.17 24.42 24.33 24.49
October 215.50 23.43 178.33 23.82 9.50 23.86
November 356.00 23.23 73.67 23.40 0.00 23.40
December 433.33 22.65 44.17 22.71 10.67 22.67
             
Annual Sum or Average 2411.17 22.79 3151.50 23.51 290.50 23.44
Minimum of Months 7.17 21.64 44.17 21.45 0.00 21.31
Maximum of Months 476.00 26.71 514.00 24.48 139.17 24.54



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 481.83 21.88 99.33 21.67 98.33 21.52
February 375.33 22.26 52.67 22.20 40.17 22.06
March 266.50 23.17 111.17 23.51 0.00 23.51
April 111.00 23.30 246.17 23.97 1.50 23.98
May 47.83 25.42 430.33 24.53 28.83 24.65
June 23.67 26.31 467.83 24.47 20.17 24.56
July 49.17 26.57 493.33 24.62 49.17 24.78
August 27.33 26.77 514.00 24.41 27.33 24.52
September 57.67 24.93 432.67 24.46 33.33 24.57
October 185.67 23.24 208.17 23.86 11.17 23.90
November 323.83 23.08 64.50 23.29 1.17 23.28
December 450.17 22.53 33.33 22.56 10.67 22.52
             
Annual Sum or Average 2400.00 22.87 3153.50 23.63 321.83 23.63
Minimum of Months 23.67 21.88 33.33 21.67 0.00 21.52
Maximum of Months 481.83 26.77 514.00 24.62 98.33 24.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 416.17 22.06 94.33 21.92 79.83 21.73
February 324.17 22.46 58.83 22.57 26.50 22.45
March 201.17 23.28 156.67 23.83 0.33 23.83
April 97.17 23.46 264.00 24.12 1.50 24.14
May 41.67 24.36 419.50 24.35 12.17 24.40
June 18.17 25.40 448.00 24.39 11.00 24.44
July 35.83 26.46 497.00 24.57 35.83 24.69
August 25.50 26.81 514.00 24.46 25.50 24.57
September 53.67 25.84 443.67 24.61 44.33 24.75
October 145.67 23.73 267.83 24.24 28.33 24.37
November 231.17 23.39 139.83 23.87 11.33 23.92
December 337.17 22.71 64.83 22.90 11.83 22.84
             
Annual Sum or Average 1927.50 23.06 3368.50 23.84 288.50 23.85
Minimum of Months 18.17 22.06 58.83 21.92 0.33 21.73
Maximum of Months 416.17 26.81 514.00 24.61 79.83 24.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 435.83 22.22 52.17 22.20 34.50 22.10
February 265.67 22.83 86.33 23.18 12.83 23.12
March 60.50 24.19 258.83 24.60 8.17 24.67
April 41.83 26.46 397.00 24.85 35.67 25.01
May 28.33 26.10 470.00 24.59 22.67 24.68
June 42.50 26.93 483.50 24.71 42.50 24.87
July 80.33 26.82 497.00 24.93 80.33 25.16
August 89.67 26.78 514.00 24.87 89.67 25.11
September 50.33 26.61 477.33 24.71 48.50 24.88
October 58.83 24.71 321.83 24.70 22.50 24.81
November 110.83 23.84 200.00 24.51 8.00 24.57
December 172.00 23.62 110.17 24.09 0.17 24.10
             
Annual Sum or Average 1436.67 23.85 3868.17 24.37 405.50 24.49
Minimum of Months 28.33 22.22 52.17 22.20 0.17 22.10
Maximum of Months 435.83 26.93 514.00 24.93 89.67 25.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.42 362.50 20.25 362.50 20.18
February 450.67 21.13 173.33 20.83 173.33 20.66
March 433.67 22.36 96.50 22.44 34.50 22.33
April 251.00 22.93 143.17 23.38 11.50 23.39
May 73.67 23.59 372.67 24.13 12.67 24.15
June 37.00 25.25 435.50 24.40 27.50 24.48
July 64.67 25.65 492.00 24.57 62.50 24.68
August 55.17 25.72 514.00 24.47 55.17 24.58
September 83.67 24.16 388.33 24.27 38.17 24.36
October 368.17 22.55 120.17 22.90 21.33 22.94
November 461.33 21.92 79.17 21.80 67.17 21.66
December 486.50 20.82 242.17 20.62 236.67 20.50
             
Annual Sum or Average 3267.50 21.89 3419.50 22.58 1103.00 22.38
Minimum of Months 37.00 20.42 79.17 20.25 11.50 20.18
Maximum of Months 502.00 25.72 514.00 24.57 362.50 24.68



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.51 280.50 20.33 280.50 20.24
February 366.67 21.31 136.83 21.01 135.33 20.82
March 314.83 22.59 65.67 22.80 8.50 22.75
April 146.50 23.04 172.83 23.80 10.33 23.85
May 68.33 24.68 336.50 24.53 31.83 24.67
June 45.67 26.24 387.50 24.69 41.17 24.86
July 80.17 26.29 413.33 24.91 76.33 25.11
August 68.00 26.37 433.00 24.75 68.00 24.95
September 81.17 24.56 341.50 24.49 44.00 24.63
October 250.67 22.57 139.50 23.18 19.50 23.21
November 386.83 22.19 44.33 22.16 27.50 22.06
December 414.33 20.95 169.50 20.70 166.00 20.55
             
Annual Sum or Average 2650.17 22.17 2921.00 22.90 909.00 22.78
Minimum of Months 45.67 20.51 44.33 20.33 8.50 20.24
Maximum of Months 427.00 26.37 433.00 24.91 280.50 25.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 447.67 21.37 184.00 21.06 178.33 20.85
February 371.83 21.81 101.17 21.72 81.33 21.52
March 270.67 22.79 129.50 23.31 5.83 23.28
April 163.67 23.12 212.00 23.84 8.50 23.88
May 61.33 23.83 389.00 24.23 15.67 24.27
June 42.50 25.19 435.33 24.42 29.17 24.51
July 70.17 25.87 492.17 24.63 68.67 24.77
August 63.83 26.16 514.00 24.59 63.83 24.75
September 83.83 24.98 428.00 24.52 50.67 24.68
October 204.83 23.13 237.50 23.85 35.67 23.98
November 304.33 22.81 100.17 23.19 20.17 23.17
December 396.50 21.78 108.17 21.67 76.50 21.44
             
Annual Sum or Average 2481.17 22.59 3331.00 23.39 634.33 23.32
Minimum of Months 42.50 21.37 100.17 21.06 5.83 20.85
Maximum of Months 447.67 26.16 514.00 24.63 178.33 24.77



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.33 20.82 274.50 20.58 274.50 20.47
February 426.83 21.43 127.00 21.18 121.67 20.99
March 332.83 22.61 121.17 23.01 8.83 22.97
April 153.17 23.23 250.17 23.97 12.67 24.04
May 51.33 24.40 417.83 24.37 20.83 24.44
June 42.00 25.90 458.00 24.56 33.67 24.68
July 71.00 26.22 492.50 24.73 70.17 24.90
August 61.50 26.57 514.00 24.68 61.50 24.87
September 83.33 24.66 423.00 24.46 45.00 24.59
October 282.17 22.77 172.00 23.35 20.67 23.42
November 406.00 22.23 66.17 22.31 28.67 22.21
December 479.17 21.27 158.00 21.08 144.17 20.91
             
Annual Sum or Average 2889.67 22.21 3474.33 23.04 842.33 22.92
Minimum of Months 42.00 20.82 66.17 20.58 8.83 20.47
Maximum of Months 500.33 26.57 514.00 24.73 274.50 24.90



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.03 420.17 19.91 420.17 19.86
February 452.33 20.74 260.00 20.49 260.00 20.37
March 443.83 21.71 139.50 21.73 83.33 21.54
April 282.17 22.45 142.17 22.85 32.50 22.78
May 108.50 23.27 356.67 24.01 18.17 24.04
June 54.00 25.03 433.33 24.43 35.17 24.54
July 84.00 25.67 486.50 24.63 79.17 24.78
August 71.67 25.80 514.00 24.53 71.67 24.67
September 113.17 23.73 354.67 24.16 43.00 24.26
October 394.17 21.93 121.50 22.28 41.50 22.27
November 476.83 21.19 187.67 20.95 180.50 20.78
December 494.17 20.29 352.17 20.10 350.83 20.02
             
Annual Sum or Average 3476.83 21.50 3768.33 22.16 1616.00 21.93
Minimum of Months 54.00 20.03 121.50 19.91 18.17 19.86
Maximum of Months 502.00 25.80 514.00 24.63 420.17 24.78



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.15 398.00 20.01 398.00 19.96
February 445.17 21.04 211.67 20.71 211.67 20.54
March 401.00 22.20 108.67 22.30 41.83 22.17
April 186.17 22.65 206.83 23.45 18.50 23.44
May 96.17 24.25 399.33 24.38 39.17 24.52
June 56.00 26.07 463.67 24.61 47.83 24.78
July 90.83 26.09 481.17 24.80 83.17 25.00
August 73.00 26.37 513.33 24.67 73.00 24.86
September 104.50 24.13 391.50 24.33 50.50 24.49
October 305.67 22.06 153.00 22.64 30.00 22.62
November 464.50 21.51 131.50 21.32 118.00 21.15
December 490.50 20.40 309.67 20.16 308.00 20.05
             
Annual Sum or Average 3215.50 21.75 3768.33 22.48 1419.67 22.29
Minimum of Months 56.00 20.15 108.67 20.01 18.50 19.96
Maximum of Months 502.00 26.37 513.33 24.80 398.00 25.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 482.67 20.88 267.50 20.49 267.50 20.30
February 393.17 21.32 176.00 21.09 160.50 20.87
March 322.00 22.26 143.17 22.61 37.17 22.45
April 211.67 22.70 207.83 23.43 21.83 23.41
May 99.50 23.49 370.50 24.13 22.67 24.18
June 61.00 24.97 432.67 24.44 37.33 24.55
July 86.33 25.77 487.17 24.67 81.50 24.83
August 70.50 26.14 514.00 24.62 70.50 24.78
September 105.83 24.47 415.17 24.43 54.83 24.59
October 251.83 22.49 216.00 23.31 41.17 23.38
November 363.83 22.08 119.17 22.18 67.83 22.01
December 442.83 21.12 208.50 20.80 185.33 20.54
             
Annual Sum or Average 2891.17 22.14 3557.67 22.88 1048.17 22.72
Minimum of Months 61.00 20.88 119.17 20.49 21.83 20.30
Maximum of Months 482.67 26.14 514.00 24.67 267.50 24.83



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.67 20.33 350.50 20.12 350.50 20.04
February 434.83 21.02 189.17 20.76 185.50 20.59
March 365.17 22.00 134.33 22.30 42.00 22.15
April 208.00 22.76 228.00 23.55 22.33 23.59
May 90.83 23.76 393.00 24.24 25.17 24.33
June 57.83 25.58 451.50 24.56 41.67 24.71
July 89.00 26.05 487.17 24.76 84.00 24.95
August 70.50 26.53 514.00 24.71 70.50 24.91
September 107.17 24.09 396.83 24.34 47.67 24.49
October 319.50 22.15 153.67 22.79 24.00 22.84
November 439.67 21.59 122.17 21.45 103.83 21.28
December 484.33 20.66 267.50 20.41 260.67 20.26
             
Annual Sum or Average 3167.50 21.81 3687.83 22.59 1257.83 22.42
Minimum of Months 57.83 20.33 122.17 20.12 22.33 20.04
Maximum of Months 500.67 26.53 514.00 24.76 350.50 24.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 497.17 27.00 0.00 27.00
February 1.00 27.00 454.00 27.00 1.00 27.00
March 19.17 27.00 514.00 27.00 19.17 27.00
April 153.50 27.00 485.00 27.00 153.50 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 65.33 27.00 496.00 27.00 65.33 27.00
July 242.50 27.00 497.00 27.00 242.50 27.00
August 468.17 27.16 514.00 27.15 468.17 27.15
September 12.67 27.00 485.00 27.00 12.67 27.00
October 12.67 27.00 502.00 27.00 12.67 27.00
November 10.50 27.00 489.00 27.00 10.50 27.00
December 15.67 27.00 497.00 27.00 15.67 27.00
             
Annual Sum or Average 1001.17 27.07 5938.17 27.02 1001.17 27.03
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 468.17 27.16 514.00 27.15 468.17 27.15



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 25.33 25.88 340.17 26.92 0.00 26.92
February 0.00 0.00 390.17 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 2.00 27.00 485.00 27.00 2.00 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 1.50 27.00 497.00 27.00 1.50 27.00
August 131.00 27.54 514.00 27.23 131.00 27.28
September 0.50 27.00 485.00 27.00 0.50 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 483.83 27.00 0.00 27.00
             
Annual Sum or Average 160.33 27.27 5704.17 27.02 135.00 27.03
Minimum of Months 0.00 0.00 340.17 26.92 0.00 26.92
Maximum of Months 131.00 27.54 514.00 27.23 131.00 27.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 170.83 24.81 227.33 25.84 20.17 25.69
February 26.50 26.97 336.50 27.00 0.00 27.00
March 1.00 27.00 492.50 27.00 1.00 27.00
April 8.67 27.00 485.00 27.00 8.67 27.00
May 1.00 27.00 508.00 27.00 1.00 27.00
June 19.17 27.00 496.00 27.00 19.17 27.00
July 82.50 27.00 497.00 27.00 82.50 27.00
August 159.67 27.42 514.00 27.20 159.67 27.24
September 4.83 27.00 485.00 27.00 4.83 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 451.67 27.00 0.00 27.00
December 10.17 27.00 382.00 27.00 0.00 27.00
             
Annual Sum or Average 484.33 26.36 5377.00 26.94 297.00 26.94
Minimum of Months 0.00 0.00 227.33 25.84 0.00 25.69
Maximum of Months 170.83 27.42 514.00 27.20 159.67 27.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 185.67 27.00 502.00 27.00 185.67 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.14 485.00 27.14 485.00 27.14
May 493.67 27.00 508.00 27.00 493.67 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.55 514.00 28.55 514.00 28.55
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5612.33 27.16 5943.00 27.15 5612.33 27.15
Minimum of Months 185.67 27.00 454.00 27.00 185.67 27.00
Maximum of Months 514.00 28.55 514.00 28.55 514.00 28.55



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00007 21.63885 0.72239 16.19826
February 454.00000 27.00011 24.17428 0.81002 19.02806
March 514.00000 27.00019 29.00356 0.92853 23.31079
April 485.00000 27.00009 32.59812 1.00473 26.37047
May 508.00000 27.00080 36.70173 0.28013 6.69068
June 496.00000 27.00155 37.47896 0.35026 7.60502
July 497.00000 27.00106 37.94678 0.40546 8.46789
August 514.00000 27.14200 37.86477 0.49637 10.33929
September 485.00000 27.00071 38.52920 0.30559 6.99954
October 502.00000 27.00069 33.69910 0.94608 23.95168
November 489.00000 27.00017 27.46667 0.91114 22.63337
December 497.00000 27.00004 24.81953 0.89585 22.06136
           
Annual Sum or Average 5943.00000 27.01274 31.88322 0.66996 16.10067
Minimum of Months 454.00000 27.00004 21.63885 0.28013 6.69068
Maximum of Months 514.00000 27.14200 38.52920 1.00473 26.37047



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.91469 21.92538 0.58159 12.52804
February 454.00000 27.00010 24.16687 0.67889 14.97818
March 514.00000 27.00017 28.96864 0.82246 19.43714
April 485.00000 27.00009 32.56017 0.90354 22.32975
May 508.00000 27.00053 36.80743 0.22528 6.13329
June 496.00000 27.00148 37.51411 0.27830 6.67455
July 497.00000 27.00106 37.96475 0.31045 7.05350
August 514.00000 27.14637 37.87098 0.37353 8.11390
September 485.00000 27.00044 38.72421 0.24411 6.31833
October 502.00000 27.00063 33.72221 0.85759 20.61097
November 489.00000 27.00016 27.43327 0.77986 17.98014
December 497.00000 27.00005 24.79099 0.70857 15.75535
           
Annual Sum or Average 5943.00000 27.00585 31.92747 0.56240 13.13243
Minimum of Months 454.00000 26.91469 21.92538 0.22528 6.13329
Maximum of Months 514.00000 27.14637 38.72421 0.90354 22.32975



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.20318 22.75617 0.37951 10.41294
February 454.00000 26.99852 24.19526 0.61911 13.48518
March 514.00000 27.00018 28.98956 0.77926 18.11170
April 485.00000 27.00010 32.57920 0.88193 21.61112
May 508.00000 27.00063 36.81805 0.22450 6.20940
June 496.00000 27.00154 37.51252 0.29286 6.90553
July 497.00000 27.00109 37.97582 0.32867 7.35399
August 514.00000 27.13117 37.89306 0.38762 8.39601
September 485.00000 27.00047 38.77691 0.23795 6.33343
October 502.00000 27.00064 33.78461 0.81845 19.32151
November 489.00000 27.00016 27.46213 0.71209 15.96542
December 497.00000 27.00005 24.80824 0.62804 13.60842
           
Annual Sum or Average 5943.00000 26.94433 32.02018 0.52303 12.28874
Minimum of Months 454.00000 26.20318 22.75617 0.22450 6.20940
Maximum of Months 514.00000 27.13117 38.77691 0.88193 21.61112



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00093 30.99112 1.01293 26.69346
February 454.00000 27.00254 31.23472 1.18434 34.50168
March 514.00000 27.00236 32.55898 1.35288 43.02533
April 485.00000 27.13874 33.83425 1.51815 51.88668
May 508.00000 27.00204 36.12530 0.48846 10.03434
June 496.00000 27.00193 37.12274 0.74565 16.73340
July 497.00000 27.00108 37.66050 0.96494 24.68453
August 514.00000 28.54674 36.65136 1.59909 56.06470
September 485.00000 27.00276 37.29273 0.58892 12.31038
October 502.00000 27.00092 34.04221 1.28001 39.25685
November 489.00000 27.00347 32.01762 1.39875 45.44995
December 497.00000 27.00530 31.27506 1.50221 51.02170
           
Annual Sum or Average 5943.00000 27.14703 34.25545 1.13682 34.34072
Minimum of Months 454.00000 27.00092 30.99112 0.48846 10.03434
Maximum of Months 514.00000 28.54674 37.66050 1.59909 56.06470



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.32887 22.73103 0.30047 7.43127
February 454.00000 24.37732 26.23441 0.34158 8.16425
March 514.00000 24.36222 32.58820 0.39526 8.69877
April 485.00000 24.43355 39.95424 0.46056 9.98689
May 508.00000 24.44851 53.09544 -0.3011 7.92601
June 496.00000 24.43183 56.99874 -0.2619 7.32231
July 497.00000 24.58593 62.37153 -0.1669 6.98582
August 514.00000 24.47678 60.92604 -0.1958 7.00267
September 485.00000 24.55213 56.97716 -0.2061 7.45209
October 502.00000 24.58754 41.99120 0.53638 11.89791
November 489.00000 24.58699 30.12062 0.44977 10.07083
December 497.00000 24.53375 26.43153 0.40022 9.12407
           
Annual Sum or Average 5943.00000 24.47555 42.66986 0.14373 8.50207
Minimum of Months 454.00000 24.32887 22.73103 -0.3011 6.98582
Maximum of Months 514.00000 24.58754 62.37153 0.53638 11.89791



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.01398 27.53216 0.25472 7.22562
February 454.00000 24.16317 28.12008 0.31195 7.56613
March 514.00000 24.28296 33.06582 0.40463 8.80206
April 485.00000 24.27883 40.06768 0.46461 9.84855
May 508.00000 24.28707 51.07010 -0.3288 7.76947
June 496.00000 24.21959 52.21428 -0.3219 7.44629
July 497.00000 24.23498 55.62319 -0.2821 6.86693
August 514.00000 24.16748 55.14748 -0.2893 6.87447
September 485.00000 24.33410 53.87476 -0.2844 7.27658
October 502.00000 24.38189 42.50818 0.49748 10.66798
November 489.00000 24.40447 31.22822 0.41771 9.14502
December 497.00000 24.39720 28.20964 0.38129 8.63461
           
Annual Sum or Average 5943.00000 24.26390 41.66379 0.09974 8.17726
Minimum of Months 454.00000 24.01398 27.53216 -0.3288 6.86693
Maximum of Months 514.00000 24.40447 55.62319 0.49748 10.66798



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.61756 30.57297 -0.1050 6.41380
February 454.00000 23.18889 30.79516 0.05458 6.44357
March 514.00000 23.99743 34.69789 0.31037 7.44502
April 485.00000 24.17051 41.06432 0.40860 8.88709
May 508.00000 24.20492 51.59304 -0.3766 8.36999
June 496.00000 24.19969 52.82522 -0.3558 8.01910
July 497.00000 24.22976 56.53402 -0.3209 7.45969
August 514.00000 24.19373 56.35061 -0.3277 7.50505
September 485.00000 24.24136 54.57060 -0.3402 7.87566
October 502.00000 24.08812 43.97676 0.40179 8.70706
November 489.00000 23.91048 33.21672 0.26689 6.95510
December 497.00000 23.31337 31.81164 0.08972 5.92336
           
Annual Sum or Average 5943.00000 23.86746 43.26908 -0.0259 7.50668
Minimum of Months 454.00000 22.61756 30.57297 -0.3766 5.92336
Maximum of Months 514.00000 24.24136 56.53402 0.40860 8.88709



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.14271 30.92329 -0.4866 13.43264
February 454.00000 22.05342 33.25201 -0.2296 9.47432
March 514.00000 23.39589 36.47093 0.15644 7.01806
April 485.00000 23.88724 41.92129 0.33648 8.13502
May 508.00000 24.16894 51.62999 -0.3840 8.63214
June 496.00000 24.23425 52.48390 -0.3299 7.74538
July 497.00000 24.27716 56.13148 -0.2880 7.14540
August 514.00000 24.23730 56.02315 -0.2964 7.13626
September 485.00000 24.17541 54.99087 -0.3615 8.34735
October 502.00000 23.52678 46.01330 0.25893 7.35154
November 489.00000 22.83275 35.99284 -0.0057 6.80676
December 497.00000 21.73491 33.77765 -0.3078 9.80231
           
Annual Sum or Average 5943.00000 23.31506 44.22149 -0.1616 8.41033
Minimum of Months 454.00000 21.14271 30.92329 -0.4866 6.80676
Maximum of Months 514.00000 24.27716 56.13148 0.33648 13.43264



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.76172 27.19934 -0.3180 9.17857
February 454.00000 22.50545 28.75001 -0.1151 7.85954
March 514.00000 23.65029 33.69121 0.21688 6.95357
April 485.00000 24.01579 40.15728 0.37572 8.64833
May 508.00000 24.24600 50.60171 -0.3469 8.30129
June 496.00000 24.31289 51.42054 -0.2607 7.05824
July 497.00000 24.40872 54.89583 -0.1893 6.55582
August 514.00000 24.29667 54.49259 -0.2160 6.54828
September 485.00000 24.29459 54.06183 -0.3074 7.88210
October 502.00000 23.84411 43.61639 0.33623 8.14506
November 489.00000 23.47679 32.57590 0.15468 6.69562
December 497.00000 22.82248 29.00791 -0.0358 6.45893
           
Annual Sum or Average 5943.00000 23.64413 41.80797 -0.0591 7.51848
Minimum of Months 454.00000 21.76172 27.19934 -0.3469 6.45893
Maximum of Months 514.00000 24.40872 54.89583 0.37572 9.17857



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.96250 26.80930 -0.2653 8.40247
February 454.00000 22.61135 28.45818 -0.0762 7.59781
March 514.00000 23.64932 33.47332 0.23854 7.28581
April 485.00000 23.96602 40.04726 0.39502 9.07913
May 508.00000 24.33352 50.07046 -0.2665 7.97157
June 496.00000 24.34873 51.11102 -0.2028 6.86397
July 497.00000 24.42180 54.62518 -0.1431 6.74791
August 514.00000 24.28609 54.38681 -0.1891 6.66558
September 485.00000 24.30483 53.72890 -0.2583 7.76691
October 502.00000 23.85945 43.24386 0.36412 8.91149
November 489.00000 23.44294 32.45186 0.15963 6.78707
December 497.00000 22.66968 29.11995 -0.0622 6.45272
           
Annual Sum or Average 5943.00000 23.66226 41.56241 -0.0258 7.54098
Minimum of Months 454.00000 21.96250 26.80930 -0.2665 6.45272
Maximum of Months 514.00000 24.42180 54.62518 0.39502 9.07913



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.45162 26.21921 -0.1457 8.42978
February 454.00000 23.00115 27.91561 0.02235 7.92872
March 514.00000 23.89912 32.86979 0.30859 8.27490
April 485.00000 24.09317 39.73385 0.41849 9.55638
May 508.00000 24.26455 50.44343 -0.3257 8.23578
June 496.00000 24.31424 51.39215 -0.2578 7.18855
July 497.00000 24.42886 54.79274 -0.1760 6.65308
August 514.00000 24.34415 54.17621 -0.1694 6.46811
September 485.00000 24.38728 53.50025 -0.2264 7.51184
October 502.00000 24.08778 42.47818 0.44160 10.42818
November 489.00000 23.88244 31.25943 0.28731 8.41314
December 497.00000 23.20745 28.04095 0.08135 7.07789
           
Annual Sum or Average 5943.00000 23.86932 41.17280 0.02078 8.01110
Minimum of Months 454.00000 22.45162 26.21921 -0.3257 6.46811
Maximum of Months 514.00000 24.42886 54.79274 0.44160 10.42818



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.48395 25.54721 -0.1203 7.28447
February 454.00000 23.45047 26.54915 0.14926 7.64099
March 514.00000 24.35345 31.61404 0.46891 10.50597
April 485.00000 24.55570 38.32768 0.62103 14.14182
May 508.00000 24.45311 49.55373 -0.1761 6.97615
June 496.00000 24.49642 50.47067 -0.0739 6.51984
July 497.00000 24.62315 53.67091 0.02688 6.81293
August 514.00000 24.53355 53.14413 0.04913 6.72201
September 485.00000 24.49855 52.88229 -0.1397 7.02204
October 502.00000 24.40576 41.45847 0.53672 12.00313
November 489.00000 24.32294 30.14000 0.41818 9.78619
December 497.00000 24.13906 26.07475 0.32607 8.08626
           
Annual Sum or Average 5943.00000 24.19746 40.05914 0.17336 8.62176
Minimum of Months 454.00000 22.48395 25.54721 -0.1761 6.51984
Maximum of Months 514.00000 24.62315 53.67091 0.62103 14.14182



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.41633 29.86134 -0.6969 18.00353
February 454.00000 21.15069 31.12873 -0.4760 13.08902
March 514.00000 22.61378 36.02227 -0.0402 7.17580
April 485.00000 23.49438 41.99543 0.23206 7.65545
May 508.00000 24.07626 51.63494 -0.4217 9.65581
June 496.00000 24.28998 52.58950 -0.2886 7.52927
July 497.00000 24.41201 56.92350 -0.2108 6.86855
August 514.00000 24.33110 56.89502 -0.2365 6.87087
September 485.00000 24.12870 55.67293 -0.3808 9.11925
October 502.00000 22.93164 46.74680 0.11185 6.94167
November 489.00000 22.02842 35.98152 -0.1996 7.87339
December 497.00000 20.88801 32.50263 -0.5234 13.34472
           
Annual Sum or Average 5943.00000 22.91007 44.09777 -0.2598 9.48281
Minimum of Months 454.00000 20.41633 29.86134 -0.6969 6.86855
Maximum of Months 514.00000 24.41201 56.92350 0.23206 18.00353



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.51291 28.63204 -0.6593 16.45437
February 385.00000 21.45413 29.96166 -0.3874 11.77100
March 433.00000 23.00554 34.25113 0.06694 6.98331
April 410.00000 23.81317 40.61083 0.33608 8.84542
May 430.00000 24.30237 50.37633 -0.3009 8.96035
June 418.00000 24.47087 51.77770 -0.1826 7.22442
July 422.00000 24.60874 55.98511 -0.0983 7.31858
August 433.00000 24.50070 56.15718 -0.1375 6.98946
September 410.00000 24.26161 54.93750 -0.2938 8.84926
October 427.00000 23.24587 45.13426 0.20422 7.97051
November 417.00000 22.32002 34.45186 -0.1195 7.15679
December 422.00000 20.99869 31.38151 -0.4829 12.19367
           
Annual Sum or Average 5034.00000 23.13435 42.88739 -0.1703 9.20890
Minimum of Months 385.00000 20.51291 28.63204 -0.6593 6.98331
Maximum of Months 433.00000 24.60874 56.15718 0.33608 16.45437



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.69545 28.06352 -0.3438 11.77701
February 454.00000 22.28540 29.37210 -0.1628 9.61451
March 514.00000 23.49858 33.97924 0.20278 7.90247
April 485.00000 23.85400 40.83107 0.34447 8.89755
May 508.00000 24.14622 51.25928 -0.3790 9.13207
June 496.00000 24.29294 52.54645 -0.2835 7.61418
July 497.00000 24.44066 56.76043 -0.1932 6.92117
August 514.00000 24.39830 56.37751 -0.1795 6.74636
September 485.00000 24.31105 54.62260 -0.2623 8.12545
October 502.00000 23.76237 43.92267 0.35823 9.77785
November 489.00000 23.37587 32.89892 0.16018 8.06488
December 497.00000 22.26690 30.15974 -0.1515 9.10025
           
Annual Sum or Average 5943.00000 23.53634 42.67206 -0.0742 8.63087
Minimum of Months 454.00000 21.69545 28.06352 -0.3790 6.74636
Maximum of Months 514.00000 24.44066 56.76043 0.35823 11.77701



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.82669 28.88287 -0.5686 14.35387
February 454.00000 21.59924 30.03775 -0.3392 10.91716
March 514.00000 23.17671 34.43143 0.12729 7.52574
April 485.00000 23.90906 40.61920 0.37802 9.49749
May 508.00000 24.23627 50.77730 -0.3020 8.29168
June 496.00000 24.39084 51.95295 -0.1890 7.06245
July 497.00000 24.50901 56.11808 -0.1120 6.87501
August 514.00000 24.45771 55.85348 -0.1168 6.71846
September 485.00000 24.26692 54.74997 -0.2721 8.30597
October 502.00000 23.37258 45.02777 0.24674 8.18148
November 489.00000 22.55807 34.37989 -0.0513 7.29138
December 497.00000 21.36080 31.33625 -0.3847 10.61588
           
Annual Sum or Average 5943.00000 23.23432 42.94815 -0.1309 8.78326
Minimum of Months 454.00000 20.82669 28.88287 -0.5686 6.71846
Maximum of Months 514.00000 24.50901 56.11808 0.37802 14.35387



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.03005 30.82024 -0.8430 23.63872
February 454.00000 20.75342 32.14126 -0.6133 16.46853
March 514.00000 22.02322 37.21819 -0.1948 9.15168
April 485.00000 23.12470 42.87000 0.14051 7.81729
May 508.00000 23.96806 51.96545 -0.4525 10.93820
June 496.00000 24.28904 52.52666 -0.2744 7.75605
July 497.00000 24.42761 56.89973 -0.1874 7.05999
August 514.00000 24.35544 56.88944 -0.2110 6.87233
September 485.00000 24.00465 56.38958 -0.4193 10.47753
October 502.00000 22.36734 48.56521 -0.0324 7.69893
November 489.00000 21.25941 37.76770 -0.4107 11.47109
December 497.00000 20.30684 34.02043 -0.7118 19.38930
           
Annual Sum or Average 5943.00000 22.59026 44.93745 -0.3492 11.52209
Minimum of Months 454.00000 20.03005 30.82024 -0.8430 6.87233
Maximum of Months 514.00000 24.42761 56.89973 0.14051 23.63872



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.14767 30.38839 -0.7876 21.43994
February 454.00000 21.10203 31.37510 -0.5032 14.43143
March 514.00000 22.59480 35.87597 -0.0362 7.82842
April 485.00000 23.57900 41.50133 0.28774 8.74329
May 508.00000 24.18444 50.85399 -0.3130 9.35911
June 496.00000 24.39863 51.75836 -0.1667 7.16687
July 497.00000 24.51144 55.97230 -0.0885 7.35944
August 514.00000 24.43250 56.03286 -0.1193 6.84170
September 485.00000 24.10858 55.43256 -0.3220 9.74069
October 502.00000 22.85867 46.76892 0.10824 8.14447
November 489.00000 21.62852 36.70713 -0.3019 9.50562
December 497.00000 20.44163 33.51607 -0.6528 17.58581
           
Annual Sum or Average 5943.00000 22.84628 43.94461 -0.2396 10.64507
Minimum of Months 454.00000 20.14767 30.38839 -0.7876 6.84170
Maximum of Months 514.00000 24.51144 56.03286 0.28774 21.43994



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.00608 29.42866 -0.5460 16.50662
February 454.00000 21.74969 30.55421 -0.3231 12.39577
March 514.00000 23.00306 35.09939 0.07033 8.42311
April 485.00000 23.54641 41.63899 0.26694 8.77760
May 508.00000 24.04810 51.57017 -0.4057 10.28631
June 496.00000 24.28578 52.49845 -0.2706 7.89502
July 497.00000 24.44699 56.75850 -0.1721 7.12598
August 514.00000 24.41174 56.38671 -0.1557 6.77690
September 485.00000 24.21393 55.21676 -0.2902 9.15000
October 502.00000 23.34172 45.46312 0.24595 9.63277
November 489.00000 22.65717 34.67032 -0.0355 8.81740
December 497.00000 21.45028 32.04948 -0.3808 13.52400
           
Annual Sum or Average 5943.00000 23.19105 43.54609 -0.1657 9.92318
Minimum of Months 454.00000 21.00608 29.42866 -0.5460 6.77690
Maximum of Months 514.00000 24.44699 56.75850 0.26694 16.50662



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.33598 29.92434 -0.7282 19.74032
February 454.00000 21.16443 31.04154 -0.4732 13.70015
March 514.00000 22.63415 35.53938 -0.0107 8.39566
April 485.00000 23.57649 41.39593 0.29734 9.23900
May 508.00000 24.11602 51.11985 -0.3336 9.41379
June 496.00000 24.36712 51.94420 -0.1810 7.37480
July 497.00000 24.49682 56.15059 -0.0968 7.12820
August 514.00000 24.46112 55.87538 -0.0970 6.80157
September 485.00000 24.13587 55.41790 -0.3098 9.52551
October 502.00000 22.86649 46.63299 0.12010 8.24331
November 489.00000 21.84257 35.99846 -0.2411 9.24131
December 497.00000 20.73503 32.80813 -0.5686 15.36443
           
Annual Sum or Average 5943.00000 22.90796 43.75155 -0.2170 10.31764
Minimum of Months 454.00000 20.33598 29.92434 -0.7282 6.80157
Maximum of Months 514.00000 24.49682 56.15059 0.29734 19.74032



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.418864E+10 69513.53 31-JAN-15:50 78.62 0.194649E+11 0.00 0.236535E+11 0.48 6.38 31-JAN-15:50 0.00 0.00
February 0.139280E+11 104037.89 28-FEB-13:50 124.87 0.762388E+11 0.00 0.901668E+11 0.91 7.25 28-FEB-13:50 0.00 0.00
March 0.399806E+11 113546.25 30-MAR-15:00 254.30 0.235082E+12 0.00 0.275063E+12 1.80 7.39 31-MAR-05:04 0.00 0.00
April 0.714970E+11 127059.60 12-APR-15:15 395.37 0.442789E+12 0.00 0.514286E+12 3.03 7.53 03-APR-05:04 0.00 0.00
May 0.120704E+12 151008.67 31-MAY-03:02 474.60 0.779587E+12 0.00 0.900291E+12 3.88 7.76 31-MAY-05:03 0.00 0.00
June 0.161464E+12 191892.66 19-JUN-05:04 566.66 0.105733E+13 0.00 0.121880E+13 4.86 7.76 17-JUN-05:02 0.00 0.00
July 0.180775E+12 198133.38 27-JUL-05:04 657.32 0.116457E+13 0.00 0.134534E+13 5.30 7.76 28-JUL-05:02 0.00 0.00
August 0.194063E+12 194871.13 21-AUG-05:03 693.90 0.124981E+13 0.00 0.144387E+13 5.57 7.70 08-AUG-05:03 0.00 0.00
September 0.130883E+12 193035.50 27-SEP-05:04 484.59 0.852644E+12 0.00 0.983526E+12 4.13 7.69 28-SEP-05:03 0.00 0.00
October 0.638919E+11 151681.02 19-OCT-05:03 305.37 0.395627E+12 0.00 0.459519E+12 2.31 7.70 17-OCT-05:04 0.00 0.00
November 0.286722E+11 95292.31 02-NOV-14:00 199.11 0.159278E+12 0.00 0.187950E+12 1.41 7.14 02-NOV-14:00 0.00 0.00
December 0.813282E+10 87848.54 12-DEC-14:30 81.77 0.450930E+11 0.00 0.532258E+11 0.54 6.97 12-DEC-14:30 0.00 0.00
                         
Annual Sum or Average 0.101818E+13     4316.48 0.647751E+13 0.00 0.749569E+13 2.86     0.00 0.00
Minimum of Months 0.418864E+10 69513.53   78.62 0.194649E+11 0.00 0.236535E+11 0.48 6.38   0.00 0.00
Maximum of Months 0.194063E+12 198133.38   693.90 0.124981E+13 0.00 0.144387E+13 5.57 7.76   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.827595E+09 113546.25 30-MAR-15:00 2.17 0.591616E+10 0.00 0.674375E+10 0.02 7.27 30-MAR-14:50 0.00 0.00
April 0.506074E+10 127059.60 12-APR-15:15 13.14 0.362935E+11 0.00 0.413543E+11 0.13 7.53 03-APR-05:04 0.00 0.00
May 0.147921E+11 151008.67 31-MAY-03:02 38.10 0.103871E+12 0.00 0.118664E+12 0.36 7.76 31-MAY-05:03 0.00 0.00
June 0.552394E+11 191892.66 19-JUN-05:04 139.05 0.376378E+12 0.00 0.431617E+12 1.32 7.76 17-JUN-05:02 0.00 0.00
July 0.642248E+11 198133.38 27-JUL-05:04 159.91 0.435978E+12 0.00 0.500202E+12 1.46 7.76 28-JUL-05:02 0.00 0.00
August 0.798157E+11 194871.13 21-AUG-05:03 196.01 0.538858E+12 0.00 0.618674E+12 1.78 7.70 08-AUG-05:03 0.00 0.00
September 0.285360E+11 193035.50 27-SEP-05:04 72.12 0.196075E+12 0.00 0.224611E+12 0.69 7.69 28-SEP-05:03 0.00 0.00
October 0.701417E+10 151681.02 19-OCT-05:03 17.70 0.490518E+11 0.00 0.560660E+11 0.17 7.70 17-OCT-05:04 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.255510E+12     638.19 0.174242E+13 0.00 0.199793E+13 0.50     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.798157E+11 198133.38   196.01 0.538858E+12 0.00 0.618674E+12 1.78 7.76   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.189348E+11 744.00 49248.27 19-JAN-12:10 195318.21 31-JAN-15:40 21.67 18.38 14.23
February 0.501062E+11 672.00 49248.27 01-FEB-19:00 359211.14 28-FEB-15:10 25.16 18.90 14.23
March 0.102259E+12 744.00 49248.27 01-MAR-00:10 596251.68 31-MAR-24:00 29.85 20.47 14.23
April 0.120084E+12 720.00 49248.27 01-APR-09:40 671614.75 17-APR-16:15 35.96 23.56 14.23
May 0.122294E+12 744.00 49248.27 01-MAY-00:03 339192.94 31-MAY-23:40 27.04 23.02 14.23
June 0.126510E+12 720.00 49248.27 01-JUN-00:10 488453.46 30-JUN-24:00 35.27 28.07 14.23
July 0.131907E+12 744.00 49248.27 01-JUL-00:10 652201.94 31-JUL-23:45 40.97 30.68 14.23
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 705850.55 11-AUG-16:40 45.72 32.51 14.23
September 0.123427E+12 720.00 49248.27 01-SEP-00:03 319913.24 30-SEP-24:00 28.66 24.51 14.23
October 0.100975E+12 744.00 49248.27 01-OCT-00:10 454999.85 31-OCT-24:00 27.73 21.02 14.23
November 0.895555E+11 720.00 49248.27 01-NOV-10:35 510051.58 02-NOV-14:10 29.14 19.81 14.23
December 0.809912E+11 744.00 49248.27 04-DEC-15:40 654238.13 12-DEC-15:10 30.70 18.84 14.23
                   
Annual Sum or Average 0.119895E+13 8760.00         31.53 23.34 14.23
Minimum of Months 0.189348E+11 672.00 49248.27   195318.21   21.67 18.38 14.23
Maximum of Months 0.131907E+12 744.00 49248.27   705850.55   45.72 32.51 14.23



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 40970176.57 21.89 1111.56 19-JAN-22:00 504313.19 31-JAN-15:50 21.02 20.98 3.46
February 71234236.97 57.81 1955.98 28-FEB-13:50 1058739.34 28-FEB-14:40 21.17 21.03 9.03
March 0.137261E+10 159.28 20828.82 29-MAR-13:10 1121542.95 30-MAR-15:30 21.47 21.09 20.42
April 0.392353E+10 285.73 20828.82 04-APR-08:40 1345966.03 14-APR-13:40 21.90 21.14 34.78
May 0.168042E+11 446.75 20828.82 01-MAY-13:20 1154964.31 12-MAY-15:10 22.96 21.72 44.45
June 0.315198E+11 548.61 20828.82 01-JUN-05:02 1259354.44 08-JUN-16:00 24.52 22.84 54.84
July 0.443321E+11 655.96 20828.82 01-JUL-01:03 1196890.68 27-JUL-05:04 25.42 23.64 61.27
August 0.499727E+11 693.81 20828.82 01-AUG-00:20 1133731.74 26-AUG-05:04 26.15 24.24 64.26
September 0.243544E+11 466.40 20828.82 01-SEP-05:02 1285224.11 14-SEP-14:55 24.04 22.65 47.06
October 0.710076E+10 249.51 20828.82 02-OCT-04:07 1078339.33 11-OCT-15:50 22.14 21.52 26.98
November 0.495788E+09 133.00 4171.74 27-NOV-17:00 793620.75 02-NOV-14:00 21.38 21.12 16.52
December 0.171465E+09 36.63 3027.15 13-DEC-11:10 718967.06 12-DEC-14:30 21.04 20.96 4.74
                   
Annual Sum or Average 0.180159E+12 3755.39         22.78 21.92 32.44
Minimum of Months 40970176.57 21.89 1111.56   504313.19   21.02 20.96 3.46
Maximum of Months 0.499727E+11 693.81 20828.82   1345966.03   26.15 24.24 64.26



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:05 0.00 01-JAN-00:05 21.02 21.02 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 21.17 21.17 0.00
March 0.124973E+09 1.67 20828.82 30-MAR-12:50 1108980.49 30-MAR-15:20 21.47 21.46 0.16
April 0.435220E+09 6.94 20828.82 11-APR-13:10 1345966.03 14-APR-13:40 21.90 21.86 0.68
May 0.283501E+10 37.81 20828.82 03-MAY-14:30 1131942.57 31-MAY-03:02 22.96 22.80 3.59
June 0.121644E+11 162.23 20828.82 01-JUN-05:04 1237104.42 19-JUN-05:04 24.52 23.86 15.60
July 0.157389E+11 209.90 20828.82 01-JUL-05:04 1196890.68 27-JUL-05:04 25.42 24.60 18.79
August 0.192762E+11 257.07 20828.82 01-AUG-03:02 1133731.74 26-AUG-05:04 26.15 25.13 22.78
September 0.592690E+10 79.19 20828.82 01-SEP-05:04 1285224.11 14-SEP-14:55 24.04 23.72 7.66
October 0.146468E+10 19.53 20828.82 02-OCT-10:20 984088.90 11-OCT-14:10 22.14 22.05 1.80
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.38 21.38 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 21.04 21.04 0.00
                   
Annual Sum or Average 0.579663E+11 774.34         22.78 22.52 5.97
Minimum of Months 0.00 0.00 0.00   0.00   21.02 21.02 0.00
Maximum of Months 0.192762E+11 257.07 20828.82   1345966.03   26.15 25.13 22.78



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.161868E+12 0.00 477.06 1447838.50 09-JAN-05:11 0.00 31.02 62.24 0.34 0.00 0.02 0.60 09-JAN-05:11
February 0.854901E+11 0.00 324.62 1344776.36 13-FEB-06:02 0.00 26.97 51.62 0.19 0.00 0.01 0.56 13-FEB-06:02
March 0.676048E+10 0.00 120.94 1006500.73 22-MAR-05:02 0.00 25.60 34.42 0.01 0.00 0.00 0.42 22-MAR-05:02
April 0.280987E+10 0.00 50.87 341710.33 06-APR-05:03 0.00 38.07 41.15 0.01 0.00 0.00 0.14 06-APR-05:03
May 0.160428E+10 0.00 28.35 89008.22 15-MAY-14:30 0.00 40.57 41.81 0.00 0.00 0.00 0.04 15-MAY-14:30
June 0.644549E+09 0.00 11.42 58616.52 03-JUN-12:10 0.00 51.42 51.97 0.00 0.00 0.00 0.02 03-JUN-12:10
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 52.61 52.61 0.00 0.00 0.00 0.00 01-JUL-00:10
August 45749307.96 0.00 1.67 31714.74 25-AUG-13:50 0.00 51.28 51.34 0.00 0.00 0.00 0.01 25-AUG-13:50
September 0.246003E+09 0.00 7.67 38132.10 15-SEP-11:30 0.00 48.21 48.55 0.00 0.00 0.00 0.02 15-SEP-11:30
October 0.295386E+10 0.00 94.34 554987.01 26-OCT-05:03 0.00 35.49 41.90 0.01 0.00 0.00 0.23 26-OCT-05:03
November 0.189673E+11 0.00 192.52 1055402.22 25-NOV-06:01 0.00 24.68 39.08 0.03 0.00 0.00 0.44 25-NOV-06:01
December 0.683784E+11 0.00 377.85 1113833.05 19-DEC-05:01 0.00 25.68 52.45 0.13 0.00 0.01 0.46 19-DEC-05:01
                           
Annual Sum or Average 0.349769E+12 0.00 1687.29     0.00 37.69 47.42 0.06 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 24.68 34.42 0.00 0.00 0.00 0.00  
Maximum of Months 0.161868E+12 0.00 477.06 1447838.50   0.00 52.61 62.24 0.34 0.00 0.02 0.60  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 21.67 21.67 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 25.16 25.16 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 29.85 29.85 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 35.96 35.96 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:03 0.00 27.04 27.04 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 35.27 35.27 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 40.97 40.97 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 45.72 45.72 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 28.66 28.66 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 27.73 27.73 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 29.14 29.14 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.70 30.70 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 31.53 31.53 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.67 21.67 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 45.72 45.72 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.170240E+10 0.00 68.07 0.161784E+10 0.00 0.00 0.00 0.00 37848.76 31-JAN-15:00 37848.76 31-JAN-15:00 0.00 0.00 0.00
February 0.785620E+10 0.00 106.28 0.785243E+10 0.00 0.00 0.00 0.00 86875.98 28-FEB-15:00 86875.98 28-FEB-15:00 0.00 0.00 0.00
March 0.254286E+11 0.00 246.92 0.245313E+11 0.00 0.00 0.00 0.00 121292.02 30-MAR-14:40 121292.02 30-MAR-14:40 0.00 0.00 0.00
April 0.561150E+11 0.00 386.18 0.535745E+11 0.00 0.00 0.00 0.00 160975.89 17-APR-14:35 160975.89 17-APR-14:35 0.00 0.00 0.00
May 0.885510E+11 0.00 457.42 0.760433E+11 0.00 0.00 0.00 0.00 205064.54 31-MAY-05:03 157486.62 16-MAY-15:17 0.00 0.00 0.00
June 0.136427E+12 0.00 542.74 0.118117E+12 0.00 0.00 0.00 0.00 211940.52 26-JUN-05:02 149693.02 26-JUN-05:02 0.00 0.00 0.00
July 0.162383E+12 0.00 616.42 0.135670E+12 0.00 0.00 0.00 0.00 214059.46 06-JUL-05:03 152430.04 17-JUL-05:04 0.00 0.00 0.00
August 0.187957E+12 0.00 657.56 0.157075E+12 0.00 0.00 0.00 0.00 217102.14 07-AUG-05:03 154346.11 07-AUG-05:03 0.00 0.00 0.00
September 0.102888E+12 0.00 459.37 0.866076E+11 0.00 0.00 0.00 0.00 209420.64 07-SEP-05:03 148520.74 11-SEP-05:02 0.00 0.00 0.00
October 0.476811E+11 0.00 281.81 0.399763E+11 0.00 0.00 0.00 0.00 218631.13 19-OCT-05:03 141308.51 18-OCT-05:02 0.00 0.00 0.00
November 0.174501E+11 0.00 174.62 0.161107E+11 0.00 0.00 0.00 0.00 108255.77 27-NOV-06:03 108255.77 27-NOV-06:03 0.00 0.00 0.00
December 0.533743E+10 0.00 59.67 0.447382E+10 0.00 0.00 0.00 0.00 97166.29 13-DEC-06:02 71449.26 12-DEC-14:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.839776E+12 0.00 4057.05 0.721650E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.170240E+10 0.00 59.67 0.161784E+10 0.00 0.00 0.00 0.00 37848.76   37848.76   0.00 0.00 0.00
Maximum of Months 0.187957E+12 0.00 657.56 0.157075E+12 0.00 0.00 0.00 0.00 218631.13   160975.89   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.118183E+11 0.00 55.75 0.112566E+11 0.00 0.00 0.00 0.00 251386.18 31-JAN-15:00 251386.18 31-JAN-15:00 0.00 0.00 0.00
February 0.559120E+11 0.00 99.68 0.559120E+11 0.00 0.00 0.00 0.00 676909.21 28-FEB-15:00 676909.21 28-FEB-15:00 0.00 0.00 0.00
March 0.183385E+12 0.00 221.17 0.178019E+12 0.00 0.00 0.00 0.00 1123846.26 30-MAR-15:20 1123846.26 30-MAR-15:20 0.00 0.00 0.00
April 0.396528E+12 0.00 306.51 0.381513E+12 0.00 0.00 0.00 0.00 1430460.49 12-APR-15:15 1430460.49 12-APR-15:15 0.00 0.00 0.00
May 0.767148E+12 0.00 433.88 0.658203E+12 0.00 0.00 0.00 0.00 1941333.62 31-MAY-05:03 1484725.19 19-MAY-14:50 0.00 0.00 0.00
June 0.114664E+13 0.00 471.15 0.960804E+12 0.00 0.00 0.00 0.00 2085228.30 19-JUN-03:02 1364076.21 14-JUN-03:02 0.00 0.00 0.00
July 0.128866E+13 0.00 500.53 0.102233E+13 0.00 0.00 0.00 0.00 2112400.83 26-JUL-05:03 1382701.65 07-JUL-05:02 0.00 0.00 0.00
August 0.143588E+13 0.00 520.19 0.112368E+13 0.00 0.00 0.00 0.00 2397773.12 23-AUG-03:02 1555078.57 25-AUG-13:50 0.00 0.00 0.00
September 0.876085E+12 0.00 425.44 0.718488E+12 0.00 0.00 0.00 0.00 2053957.56 27-SEP-05:02 1368433.33 11-SEP-05:02 0.00 0.00 0.00
October 0.361363E+12 0.00 261.48 0.295163E+12 0.00 0.00 0.00 0.00 2207670.12 19-OCT-05:03 1217434.10 19-OCT-05:03 0.00 0.00 0.00
November 0.111274E+12 0.00 162.75 0.105038E+12 0.00 0.00 0.00 0.00 680928.19 04-NOV-05:03 502665.93 02-NOV-14:10 0.00 0.00 0.00
December 0.296407E+11 0.00 56.30 0.252955E+11 0.00 0.00 0.00 0.00 734280.96 13-DEC-06:02 442396.45 12-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.666433E+13 0.00 3514.83 0.553570E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.118183E+11 0.00 55.75 0.112566E+11 0.00 0.00 0.00 0.00 251386.18   251386.18   0.00 0.00 0.00
Maximum of Months 0.143588E+13 0.00 520.19 0.112368E+13 0.00 0.00 0.00 0.00 2397773.12   1555078.57   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.112782E+10 0.00 53.11 0.107011E+10 0.00 0.00 0.00 0.00 20631.63 31-JAN-15:00 20631.63 31-JAN-15:00 0.00 0.00 0.00
February 0.482683E+10 0.00 98.28 0.482683E+10 0.00 0.00 0.00 0.00 63845.21 28-FEB-15:00 63845.21 28-FEB-15:00 0.00 0.00 0.00
March 0.175328E+11 0.00 214.67 0.171658E+11 0.00 0.00 0.00 0.00 117536.83 30-MAR-15:20 117536.83 30-MAR-15:20 0.00 0.00 0.00
April 0.408191E+11 0.00 300.07 0.392828E+11 0.00 0.00 0.00 0.00 153893.36 17-APR-15:10 153893.36 17-APR-15:10 0.00 0.00 0.00
May 0.835939E+11 0.00 430.82 0.724681E+11 0.00 0.00 0.00 0.00 194563.47 31-MAY-05:03 167080.88 19-MAY-14:20 0.00 0.00 0.00
June 0.128479E+12 0.00 473.80 0.109122E+12 0.00 0.00 0.00 0.00 217389.20 26-JUN-05:02 145406.00 26-JUN-05:02 0.00 0.00 0.00
July 0.144977E+12 0.00 509.39 0.117307E+12 0.00 0.00 0.00 0.00 223878.38 26-JUL-05:03 149775.07 15-JUL-03:02 0.00 0.00 0.00
August 0.159690E+12 0.00 529.95 0.127477E+12 0.00 0.00 0.00 0.00 258890.94 23-AUG-03:02 172864.98 25-AUG-14:00 0.00 0.00 0.00
September 0.909157E+11 0.00 421.75 0.753402E+11 0.00 0.00 0.00 0.00 216953.18 27-SEP-05:02 141607.32 27-SEP-05:02 0.00 0.00 0.00
October 0.352155E+11 0.00 251.94 0.286186E+11 0.00 0.00 0.00 0.00 213019.94 19-OCT-05:03 113068.95 19-OCT-05:03 0.00 0.00 0.00
November 0.930220E+10 0.00 163.37 0.877156E+10 0.00 0.00 0.00 0.00 61331.41 04-NOV-05:03 48604.21 02-NOV-14:30 0.00 0.00 0.00
December 0.253367E+10 0.00 63.00 0.215805E+10 0.00 0.00 0.00 0.00 36533.81 12-DEC-14:40 36533.81 12-DEC-14:40 0.00 0.00 0.00
                               
Annual Sum or Average 0.719013E+12 0.00 3510.16 0.603608E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.112782E+10 0.00 53.11 0.107011E+10 0.00 0.00 0.00 0.00 20631.63   20631.63   0.00 0.00 0.00
Maximum of Months 0.159690E+12 0.00 529.95 0.127477E+12 0.00 0.00 0.00 0.00 258890.94   172864.98   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.524622E+09 0.00 18.06 0.513165E+09 0.00 0.00 0.00 0.00 51523.20 19-JAN-06:03 27689.93 31-JAN-15:00 0.00 0.00 0.00
February 0.390557E+10 0.00 46.83 0.389432E+10 0.00 0.00 0.00 0.00 55614.74 28-FEB-14:20 55614.74 28-FEB-14:20 0.00 0.00 0.00
March 0.121630E+11 0.00 139.19 0.121157E+11 0.00 0.00 0.00 0.00 79473.88 30-MAR-05:02 71476.26 30-MAR-14:20 0.00 0.00 0.00
April 0.257121E+11 0.00 222.68 0.253121E+11 0.00 0.00 0.00 0.00 87943.01 03-APR-03:02 87943.01 03-APR-03:02 0.00 0.00 0.00
May 0.468085E+11 0.00 343.24 0.427488E+11 0.00 0.00 0.00 0.00 124495.62 31-MAY-03:02 82828.88 19-MAY-12:40 0.00 0.00 0.00
June 0.815630E+11 0.00 398.14 0.683942E+11 0.00 0.00 0.00 0.00 147014.70 26-JUN-03:02 101690.62 12-JUN-03:02 0.00 0.00 0.00
July 0.942548E+11 0.00 409.69 0.741536E+11 0.00 0.00 0.00 0.00 145098.98 21-JUL-03:02 86918.93 06-JUL-03:02 0.00 0.00 0.00
August 0.113944E+12 0.00 465.52 0.877611E+11 0.00 0.00 0.00 0.00 162734.31 20-AUG-16:20 90842.46 27-AUG-16:51 0.00 0.00 0.00
September 0.697246E+11 0.00 377.64 0.587103E+11 0.00 0.00 0.00 0.00 148147.25 04-SEP-16:42 88698.74 05-SEP-03:02 0.00 0.00 0.00
October 0.307473E+11 0.00 218.97 0.256249E+11 0.00 0.00 0.00 0.00 135022.09 19-OCT-04:03 80921.75 19-OCT-03:02 0.00 0.00 0.00
November 0.980654E+10 0.00 116.65 0.907783E+10 0.00 0.00 0.00 0.00 77352.31 27-NOV-06:03 68899.59 20-NOV-00:13 0.00 0.00 0.00
December 0.280578E+10 0.00 36.87 0.260407E+10 0.00 0.00 0.00 0.00 74239.27 13-DEC-06:02 46338.00 12-DEC-14:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.491960E+12 0.00 2793.46 0.410910E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.524622E+09 0.00 18.06 0.513165E+09 0.00 0.00 0.00 0.00 51523.20   27689.93   0.00 0.00 0.00
Maximum of Months 0.113944E+12 0.00 465.52 0.877611E+11 0.00 0.00 0.00 0.00 162734.31   101690.62   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.321566E+12 0.810783E+11 744.00 0.321064E+12 0.502039E+09 0.00 0.34 31-JAN-15:00 0.30 09-JAN-07:05 129146.46 19-JAN-17:00 124535.76 31-JAN-15:00 6011.05 19-JAN-17:10 35895.85 31-JAN-15:00 0.00
February 0.512648E+12 0.124720E+12 672.00 0.512104E+12 0.543845E+09 0.00 0.59 28-FEB-14:10 0.51 01-FEB-07:10 219177.13 17-FEB-17:00 217684.53 28-FEB-15:00 5771.95 17-FEB-17:10 70584.39 28-FEB-14:20 0.00
March 0.817896E+12 0.200271E+12 744.00 0.816358E+12 0.153757E+10 0.00 0.92 31-MAR-24:00 0.72 06-MAR-07:20 393819.03 31-MAR-24:00 393819.03 31-MAR-24:00 8543.18 31-MAR-11:50 106231.92 30-MAR-16:00 0.00
April 0.102932E+13 0.266550E+12 720.00 0.102735E+13 0.196922E+10 0.00 1.00 02-APR-12:00 0.36 30-APR-24:00 405786.59 04-APR-13:00 403957.27 16-APR-18:53 7156.30 04-APR-10:00 136376.87 17-APR-16:00 0.00
May 0.339373E+12 0.976773E+11 744.00 0.333189E+12 0.618433E+10 0.00 0.55 31-MAY-23:20 0.31 12-MAY-07:00 212502.97 31-MAY-23:10 211146.09 31-MAY-24:00 8655.20 23-MAY-14:00 60128.36 31-MAY-23:20 0.00
June 0.571381E+12 0.180752E+12 720.00 0.562367E+12 0.901375E+10 0.00 0.77 30-JUN-24:00 0.53 10-JUN-06:30 303665.34 30-JUN-23:03 303165.13 30-JUN-24:00 13108.24 26-JUN-17:00 91950.47 06-JUN-15:00 0.00
July 0.838942E+12 0.272471E+12 744.00 0.827929E+12 0.110129E+11 0.00 0.99 31-JUL-23:45 0.75 29-JUL-04:00 396291.11 31-JUL-24:00 395505.67 31-JUL-24:00 13984.81 25-JUL-16:50 134516.85 08-JUL-15:50 0.00
August 0.107911E+13 0.348012E+12 744.00 0.106797E+13 0.111363E+11 0.00 1.00 01-AUG-07:10 0.37 31-AUG-24:00 421696.92 08-AUG-17:00 406920.12 07-AUG-21:35 19150.34 11-AUG-17:00 152958.01 01-AUG-16:10 0.00
September 0.336431E+12 0.100696E+12 720.00 0.328167E+12 0.826384E+10 0.00 0.53 30-SEP-24:00 0.32 29-SEP-06:10 212067.84 30-SEP-23:20 211836.91 30-SEP-24:00 10480.23 28-SEP-13:20 53228.44 07-SEP-16:00 0.00
October 0.582806E+12 0.150522E+12 744.00 0.579133E+12 0.367334E+10 0.00 0.74 31-OCT-24:00 0.53 31-OCT-07:00 304141.75 31-OCT-24:00 304141.75 31-OCT-24:00 11877.89 18-OCT-16:10 82247.80 10-OCT-16:00 0.00
November 0.796779E+12 0.190982E+12 720.00 0.795334E+12 0.144484E+10 0.00 0.81 19-NOV-15:00 0.73 13-NOV-07:20 316825.87 27-NOV-17:00 310330.36 02-NOV-14:00 6760.71 27-NOV-17:10 97821.95 19-NOV-15:00 0.00
December 0.106384E+13 0.238790E+12 744.00 0.106310E+13 0.740463E+09 0.00 1.00 12-DEC-14:40 0.91 01-DEC-07:10 407560.41 13-DEC-14:00 401711.59 12-DEC-15:00 7796.23 13-DEC-14:00 119642.88 12-DEC-14:40 0.00
                                       
Annual Sum or Average 0.829009E+13 0.225252E+13 8760.00 0.823407E+13 0.560225E+11 0.00                         0.00
Minimum of Months 0.321566E+12 0.810783E+11 672.00 0.321064E+12 0.502039E+09 0.00 0.34   0.30   129146.46   124535.76   5771.95   35895.85   0.00
Maximum of Months 0.107911E+13 0.348012E+12 744.00 0.106797E+13 0.111363E+11 0.00 1.00   0.91   421696.92   406920.12   19150.34   152958.01   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.376797E+10 0.100916E+10 744.00 0.374885E+10 19115523.46 0.00 0.29 29-JAN-17:20 0.06 09-JAN-07:05 2207.48 20-JAN-17:00 2113.90 22-JAN-17:40 222.89 19-JAN-17:00 602.93 31-JAN-15:00 0.00
February 0.866105E+10 0.216424E+10 672.00 0.863896E+10 22081833.26 0.00 0.59 26-FEB-17:45 0.32 13-FEB-07:10 4483.68 20-FEB-18:00 4450.67 20-FEB-18:00 229.73 17-FEB-17:00 1399.10 26-FEB-17:15 0.00
March 0.155761E+11 0.381536E+10 744.00 0.155102E+11 65840120.91 0.00 0.85 31-MAR-24:00 0.60 22-MAR-06:50 7689.01 31-MAR-24:00 7689.01 31-MAR-24:00 304.58 31-MAR-11:40 2094.02 30-MAR-16:00 0.00
April 0.201942E+11 0.517180E+10 720.00 0.201045E+11 89781878.55 0.00 0.99 08-APR-18:05 0.30 30-APR-24:00 8419.75 09-APR-18:13 8419.75 09-APR-18:13 332.59 04-APR-10:00 2794.61 17-APR-16:00 0.00
May 0.605388E+10 0.171565E+10 744.00 0.582201E+10 0.231870E+09 0.00 0.49 31-MAY-24:00 0.21 11-MAY-06:10 4067.47 31-MAY-24:00 4013.40 31-MAY-24:00 337.25 31-MAY-11:00 1123.67 31-MAY-23:30 0.00
June 0.111066E+11 0.344005E+10 720.00 0.107364E+11 0.370263E+09 0.00 0.70 30-JUN-23:20 0.44 10-JUN-06:50 5920.61 30-JUN-23:03 5876.03 30-JUN-24:00 481.50 26-JUN-16:50 1835.43 06-JUN-15:10 0.00
July 0.166720E+11 0.529220E+10 744.00 0.161962E+11 0.475778E+09 0.00 0.92 31-JUL-24:00 0.67 29-JUL-06:10 7812.85 31-JUL-24:00 7792.16 31-JUL-24:00 547.69 26-JUL-09:00 2701.75 07-JUL-16:00 0.00
August 0.218516E+11 0.698500E+10 744.00 0.213025E+11 0.549130E+09 0.00 1.00 01-AUG-10:00 0.31 31-AUG-24:00 8808.90 04-AUG-15:00 8371.62 27-AUG-19:03 654.51 11-AUG-17:00 3191.11 01-AUG-16:10 0.00
September 0.604858E+10 0.177828E+10 720.00 0.573502E+10 0.313567E+09 0.00 0.45 30-SEP-24:00 0.21 29-SEP-06:40 3809.67 30-SEP-24:00 3796.23 30-SEP-24:00 416.44 05-SEP-11:00 1071.23 07-SEP-16:00 0.00
October 0.107725E+11 0.274494E+10 744.00 0.106216E+11 0.150840E+09 0.00 0.67 31-OCT-24:00 0.40 26-OCT-07:00 5696.82 31-OCT-24:00 5696.82 31-OCT-24:00 504.66 18-OCT-16:00 1631.06 10-OCT-16:00 0.00
November 0.149824E+11 0.361159E+10 720.00 0.149252E+11 57173564.44 0.00 0.79 19-NOV-16:53 0.60 30-NOV-22:00 6362.35 11-NOV-16:55 6362.35 11-NOV-16:55 281.81 27-NOV-17:10 1972.04 19-NOV-15:00 0.00
December 0.201492E+11 0.459008E+10 744.00 0.201171E+11 32092813.51 0.00 0.99 10-DEC-16:43 0.76 01-DEC-07:10 8152.87 11-DEC-16:50 8089.68 10-DEC-17:10 330.70 13-DEC-16:00 2329.15 12-DEC-14:50 0.00
                                       
Annual Sum or Average 0.155836E+12 0.423184E+11 8760.00 0.153459E+12 0.237753E+10 0.00                         0.00
Minimum of Months 0.376797E+10 0.100916E+10 672.00 0.374885E+10 19115523.46 0.00 0.29   0.06   2207.48   2113.90   222.89   602.93   0.00
Maximum of Months 0.218516E+11 0.698500E+10 744.00 0.213025E+11 0.549130E+09 0.00 1.00   0.76   8808.90   8419.75   654.51   3191.11   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.137511E+11 0.393486E+10 609.60 0.135815E+11 0.169610E+09 0.00 0.24 20-JAN-17:00 0.00 01-JAN-00:05 18792.38 20-JAN-17:00 17761.29 20-JAN-17:00 2089.56 19-JAN-17:00 4878.04 31-JAN-15:00 0.00
February 0.660097E+11 0.168335E+11 672.00 0.657964E+11 0.213286E+09 0.00 0.54 26-FEB-18:00 0.15 13-FEB-07:10 40043.23 28-FEB-17:00 40043.23 28-FEB-17:00 2239.63 17-FEB-17:00 12496.73 28-FEB-15:00 0.00
March 0.140827E+12 0.347668E+11 744.00 0.140169E+12 0.658545E+09 0.00 0.84 31-MAR-24:00 0.54 22-MAR-06:30 72310.37 31-MAR-24:00 72310.37 31-MAR-24:00 3016.70 31-MAR-11:30 19973.29 30-MAR-16:00 0.00
April 0.189686E+12 0.487284E+11 720.00 0.188786E+12 0.900002E+09 0.00 0.98 17-APR-16:00 0.27 30-APR-24:00 78793.92 04-APR-15:30 78327.22 09-APR-18:13 3330.95 04-APR-10:00 26588.07 17-APR-16:00 0.00
May 0.552783E+11 0.157500E+11 744.00 0.530009E+11 0.227733E+10 0.00 0.49 31-MAY-24:00 0.18 11-MAY-06:10 38589.14 31-MAY-24:00 38026.93 31-MAY-24:00 3346.87 31-MAY-11:00 10669.28 31-MAY-23:20 0.00
June 0.105287E+12 0.326378E+11 720.00 0.101605E+12 0.368227E+10 0.00 0.70 30-JUN-24:00 0.42 10-JUN-06:50 56574.14 30-JUN-24:00 56403.15 30-JUN-24:00 4783.29 23-JUN-10:10 17538.81 06-JUN-15:10 0.00
July 0.158868E+12 0.504311E+11 744.00 0.154124E+12 0.474463E+10 0.00 0.93 31-JUL-24:00 0.65 29-JUL-06:10 75313.64 31-JUL-24:00 75111.40 31-JUL-24:00 5471.65 26-JUL-09:00 25805.26 07-JUL-16:00 0.00
August 0.207658E+12 0.663949E+11 744.00 0.202169E+12 0.548905E+10 0.00 1.00 01-AUG-09:40 0.28 31-AUG-24:00 83959.71 04-AUG-15:00 79063.29 13-AUG-19:23 6518.23 11-AUG-17:00 30404.74 01-AUG-16:10 0.00
September 0.548468E+11 0.162193E+11 720.00 0.517719E+11 0.307488E+10 0.00 0.42 30-SEP-24:00 0.18 29-SEP-07:00 33022.28 30-SEP-24:00 32822.95 30-SEP-24:00 4110.53 06-SEP-14:30 10174.48 07-SEP-16:00 0.00
October 0.950277E+11 0.244589E+11 744.00 0.935374E+11 0.149028E+10 0.00 0.62 31-OCT-24:00 0.33 31-OCT-07:00 49861.81 31-OCT-24:00 49861.81 31-OCT-24:00 5019.85 18-OCT-16:00 15416.05 10-OCT-16:00 0.00
November 0.131029E+12 0.319382E+11 720.00 0.130463E+12 0.566546E+09 0.00 0.76 08-NOV-17:00 0.52 25-NOV-07:10 58716.20 03-NOV-15:20 58274.69 06-NOV-17:00 2791.73 27-NOV-17:00 17559.15 19-NOV-16:53 0.00
December 0.171461E+12 0.396941E+11 744.00 0.171139E+12 0.322307E+09 0.00 0.92 10-DEC-17:05 0.65 26-DEC-07:30 76366.00 13-DEC-16:00 74156.97 11-DEC-17:00 3295.24 13-DEC-16:00 21885.18 12-DEC-15:00 0.00
                                       
Annual Sum or Average 0.138973E+13 0.381788E+12 8625.60 0.136614E+13 0.235887E+11 0.00                         0.00
Minimum of Months 0.137511E+11 0.393486E+10 609.60 0.135815E+11 0.169610E+09 0.00 0.24   0.00   18792.38   17761.29   2089.56   4878.04   0.00
Maximum of Months 0.207658E+12 0.663949E+11 744.00 0.202169E+12 0.548905E+10 0.00 1.00   0.65   83959.71   79063.29   6518.23   30404.74   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.554213E+09 0.159076E+09 285.97 0.538606E+09 15607819.73 0.00 0.25 20-JAN-17:00 0.00 01-JAN-00:05 1911.72 20-JAN-17:00 1805.50 20-JAN-17:00 213.85 19-JAN-17:00 467.73 20-JAN-17:00 0.00
February 0.533047E+10 0.137913E+10 660.99 0.530960E+10 20867488.64 0.00 0.54 27-FEB-17:00 0.00 05-FEB-04:55 4030.34 28-FEB-17:00 4030.34 28-FEB-17:00 222.63 17-FEB-17:00 1250.74 28-FEB-15:00 0.00
March 0.132592E+11 0.330643E+10 744.00 0.131939E+11 65351337.59 0.00 0.81 31-MAR-23:20 0.44 23-MAR-06:10 6986.71 31-MAR-23:20 6986.71 31-MAR-23:20 301.82 31-MAR-11:40 2022.66 30-MAR-16:00 0.00
April 0.185912E+11 0.480562E+10 720.00 0.185016E+11 89668307.23 0.00 0.98 17-APR-16:00 0.25 30-APR-24:00 7910.61 04-APR-15:40 7884.14 09-APR-18:13 333.32 04-APR-10:00 2689.88 17-APR-16:00 0.00
May 0.546299E+10 0.156608E+10 744.00 0.523556E+10 0.227430E+09 0.00 0.48 31-MAY-23:40 0.12 11-MAY-07:00 3826.18 31-MAY-23:20 3766.55 31-MAY-24:00 339.32 31-MAY-11:00 1060.69 31-MAY-23:20 0.00
June 0.106060E+11 0.329478E+10 720.00 0.102375E+11 0.368438E+09 0.00 0.69 30-JUN-24:00 0.39 08-JUN-06:50 5641.74 30-JUN-24:00 5624.49 30-JUN-24:00 479.91 23-JUN-10:10 1788.88 06-JUN-15:10 0.00
July 0.159972E+11 0.508622E+10 744.00 0.155229E+11 0.474323E+09 0.00 0.92 31-JUL-24:00 0.63 29-JUL-07:00 7569.12 31-JUL-24:00 7548.78 31-JUL-24:00 547.35 26-JUL-10:40 2628.83 07-JUL-16:00 0.00
August 0.208846E+11 0.668766E+10 744.00 0.203357E+11 0.548929E+09 0.00 1.00 01-AUG-10:00 0.27 31-AUG-24:00 8488.38 04-AUG-15:00 8056.29 20-AUG-16:40 645.49 11-AUG-17:00 3079.60 01-AUG-16:10 0.00
September 0.537534E+10 0.160025E+10 720.00 0.506925E+10 0.306090E+09 0.00 0.39 07-SEP-16:00 0.11 29-SEP-07:00 2903.49 07-SEP-16:00 2826.10 30-SEP-24:00 414.41 06-SEP-14:30 1049.24 07-SEP-16:00 0.00
October 0.876240E+10 0.228403E+10 744.00 0.861437E+10 0.148029E+09 0.00 0.58 10-OCT-16:00 0.23 30-OCT-06:10 4524.29 18-OCT-16:00 4507.45 31-OCT-23:20 502.58 18-OCT-16:00 1564.60 10-OCT-16:00 0.00
November 0.118154E+11 0.291953E+10 720.00 0.117594E+11 55966660.94 0.00 0.74 08-NOV-17:00 0.39 22-NOV-07:10 5887.86 02-NOV-16:00 5818.18 06-NOV-17:00 278.30 27-NOV-17:00 1710.15 02-NOV-14:00 0.00
December 0.153093E+11 0.360004E+10 744.00 0.152773E+11 31973923.13 0.00 0.90 12-DEC-15:20 0.48 18-DEC-04:17 7613.50 13-DEC-16:00 7362.06 12-DEC-17:00 329.14 13-DEC-16:00 2179.66 12-DEC-15:00 0.00
                                       
Annual Sum or Average 0.131948E+12 0.366888E+11 8290.96 0.129596E+12 0.235267E+10 0.00                         0.00
Minimum of Months 0.554213E+09 0.159076E+09 285.97 0.538606E+09 15607819.73 0.00 0.25   0.00   1911.72   1805.50   213.85   467.73   0.00
Maximum of Months 0.208846E+11 0.668766E+10 744.00 0.203357E+11 0.548929E+09 0.00 1.00   0.63   8488.38   8056.29   645.49   3079.60   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 592.45 0.00 0.00 0.00
February 82.27 0.00 82.27 26.95 489.45 0.00 0.00 0.00
March 115.50 0.00 115.50 67.18 310.28 0.00 0.00 0.00
April 139.70 0.62 139.08 145.04 234.73 0.00 0.00 0.00
May 167.08 5.33 161.75 232.01 145.85 0.00 0.00 0.00
June 183.88 12.14 171.74 336.94 88.13 0.00 0.00 0.00
July 173.49 8.43 165.06 337.43 62.54 0.00 0.00 0.00
August 154.29 1.68 152.61 307.33 52.07 0.00 0.00 0.00
September 116.63 0.02 116.62 173.01 126.67 0.00 0.00 0.00
October 88.68 0.00 88.68 70.23 282.65 0.00 0.00 0.00
November 79.36 0.00 79.36 28.97 394.52 0.00 0.00 0.00
December 68.61 0.00 68.61 5.32 514.24 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.16 145.43 273.39 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.32 52.07 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 337.43 592.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 592.45 0.00 0.00 0.00
February 82.26 0.00 82.26 26.95 489.44 0.00 0.00 0.00
March 115.49 0.00 115.49 67.18 310.28 0.00 0.00 0.00
April 139.70 0.62 139.08 145.04 234.73 0.00 0.00 0.00
May 167.08 5.33 161.75 232.01 145.85 0.00 0.00 0.00
June 183.88 12.14 171.74 336.93 88.13 0.00 0.00 0.00
July 173.49 8.43 165.06 337.43 62.54 0.00 0.00 0.00
August 154.29 1.68 152.61 307.33 52.07 0.00 0.00 0.00
September 116.63 0.02 116.61 173.01 126.67 0.00 0.00 0.00
October 88.68 0.00 88.68 70.23 282.65 0.00 0.00 0.00
November 79.36 0.00 79.36 28.97 394.52 0.00 0.00 0.00
December 68.61 0.00 68.61 5.32 514.24 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.15 145.43 273.39 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.32 52.07 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 337.43 592.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 592.45 0.00 0.00 0.00
February 82.26 0.00 82.26 26.95 489.44 0.00 0.00 0.00
March 115.50 0.00 115.50 67.18 310.28 0.00 0.00 0.00
April 139.70 0.62 139.08 145.04 234.73 0.00 0.00 0.00
May 167.08 5.33 161.75 232.01 145.85 0.00 0.00 0.00
June 183.88 12.14 171.74 336.94 88.13 0.00 0.00 0.00
July 173.49 8.43 165.06 337.43 62.54 0.00 0.00 0.00
August 154.29 1.68 152.61 307.33 52.07 0.00 0.00 0.00
September 116.63 0.02 116.61 173.01 126.67 0.00 0.00 0.00
October 88.68 0.00 88.68 70.23 282.65 0.00 0.00 0.00
November 79.36 0.00 79.36 28.97 394.52 0.00 0.00 0.00
December 68.61 0.00 68.61 5.32 514.24 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.15 145.43 273.39 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.32 52.07 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 337.43 592.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 592.45 0.00 0.00 0.00
February 82.26 0.00 82.26 26.95 489.44 0.00 0.00 0.00
March 115.49 0.00 115.49 67.18 310.28 0.00 0.00 0.00
April 139.70 0.62 139.08 145.04 234.73 0.00 0.00 0.00
May 167.08 5.33 161.75 232.01 145.85 0.00 0.00 0.00
June 183.88 12.14 171.74 336.93 88.13 0.00 0.00 0.00
July 173.49 8.43 165.06 337.43 62.54 0.00 0.00 0.00
August 154.29 1.68 152.61 307.33 52.07 0.00 0.00 0.00
September 116.63 0.02 116.61 173.01 126.67 0.00 0.00 0.00
October 88.68 0.00 88.68 70.23 282.65 0.00 0.00 0.00
November 79.36 0.00 79.36 28.97 394.52 0.00 0.00 0.00
December 68.61 0.00 68.61 5.32 514.24 0.00 0.00 0.00
                 
Annual Sum or Average 120.52 2.36 118.15 145.43 273.39 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.32 52.07 0.00 0.00 0.00
Maximum of Months 183.88 12.14 171.74 337.43 592.45 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 74.22 0.00 74.22 6.60 592.42 0.00 0.00 0.00
February 82.26 0.00 82.26 26.95 489.43 0.00 0.00 0.00
March 115.49 0.00 115.49 67.18 310.27 0.00 0.00 0.00
April 139.70 0.62 139.08 145.03 234.72 0.00 0.00 0.00
May 167.07 5.33 161.74 232.00 145.84 0.00 0.00 0.00
June 183.87 12.14 171.73 336.92 88.13 0.00 0.00 0.00
July 173.48 8.43 165.05 337.42 62.54 0.00 0.00 0.00
August 154.29 1.68 152.61 307.32 52.06 0.00 0.00 0.00
September 116.63 0.02 116.61 173.01 126.67 0.00 0.00 0.00
October 88.67 0.00 88.67 70.22 282.64 0.00 0.00 0.00
November 79.36 0.00 79.36 28.97 394.50 0.00 0.00 0.00
December 68.61 0.00 68.61 5.32 514.22 0.00 0.00 0.00
                 
Annual Sum or Average 120.51 2.36 118.15 145.42 273.38 0.00 0.00 0.00
Minimum of Months 68.61 0.00 68.61 5.32 52.06 0.00 0.00 0.00
Maximum of Months 183.87 12.14 171.73 337.42 592.42 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 181.11 81.69 99.42 113.48 586.74 0.00 0.00 0.00
February 228.32 122.67 105.65 207.85 481.91 0.00 0.00 0.00
March 287.25 130.77 156.49 314.32 306.47 0.00 0.00 0.00
April 347.36 158.39 188.97 476.23 235.66 0.00 0.00 0.00
May 381.43 161.30 220.13 586.74 158.49 0.00 0.00 0.00
June 394.91 165.52 229.39 698.65 95.41 0.00 0.00 0.00
July 385.05 161.88 223.17 705.94 65.78 0.00 0.00 0.00
August 352.20 139.73 212.47 658.17 51.72 0.00 0.00 0.00
September 289.46 128.25 161.21 463.60 133.73 0.00 0.00 0.00
October 246.93 128.48 118.45 309.41 283.27 0.00 0.00 0.00
November 197.42 89.39 108.03 178.81 382.57 0.00 0.00 0.00
December 171.01 77.95 93.06 113.43 493.80 0.00 0.00 0.00
                 
Annual Sum or Average 288.83 128.81 160.01 403.25 271.91 0.00 0.00 0.00
Minimum of Months 171.01 77.95 93.06 113.43 51.72 0.00 0.00 0.00
Maximum of Months 394.91 165.52 229.39 705.94 586.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 181.11 81.69 99.42 113.48 586.74 0.00 0.00 0.00
February 228.32 122.67 105.65 207.85 481.91 0.00 0.00 0.00
March 287.25 130.77 156.49 314.32 306.47 0.00 0.00 0.00
April 347.36 158.39 188.97 476.23 235.66 0.00 0.00 0.00
May 381.43 161.30 220.13 586.74 158.49 0.00 0.00 0.00
June 394.91 165.52 229.39 698.65 95.41 0.00 0.00 0.00
July 385.05 161.88 223.17 705.94 65.78 0.00 0.00 0.00
August 352.20 139.73 212.47 658.17 51.72 0.00 0.00 0.00
September 289.46 128.25 161.21 463.60 133.73 0.00 0.00 0.00
October 246.93 128.48 118.45 309.41 283.27 0.00 0.00 0.00
November 197.42 89.39 108.03 178.81 382.57 0.00 0.00 0.00
December 171.01 77.95 93.06 113.43 493.80 0.00 0.00 0.00
                 
Annual Sum or Average 288.83 128.81 160.01 403.25 271.91 0.00 0.00 0.00
Minimum of Months 171.01 77.95 93.06 113.43 51.72 0.00 0.00 0.00
Maximum of Months 394.91 165.52 229.39 705.94 586.74 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 181.10 81.69 99.42 113.48 586.73 0.00 0.00 0.00
February 228.32 122.67 105.64 207.85 481.90 0.00 0.00 0.00
March 287.25 130.76 156.48 314.32 306.46 0.00 0.00 0.00
April 347.36 158.39 188.97 476.22 235.65 0.00 0.00 0.00
May 381.42 161.30 220.12 586.73 158.48 0.00 0.00 0.00
June 394.90 165.51 229.39 698.64 95.40 0.00 0.00 0.00
July 385.04 161.88 223.17 705.93 65.78 0.00 0.00 0.00
August 352.19 139.73 212.46 658.16 51.72 0.00 0.00 0.00
September 289.45 128.25 161.20 463.59 133.73 0.00 0.00 0.00
October 246.93 128.48 118.44 309.40 283.26 0.00 0.00 0.00
November 197.42 89.39 108.03 178.80 382.56 0.00 0.00 0.00
December 171.00 77.95 93.05 113.43 493.79 0.00 0.00 0.00
                 
Annual Sum or Average 288.82 128.81 160.01 403.24 271.91 0.00 0.00 0.00
Minimum of Months 171.00 77.95 93.05 113.43 51.72 0.00 0.00 0.00
Maximum of Months 394.90 165.51 229.39 705.93 586.73 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.47 477.62 0.00 0.00 0.00
February 370.47 248.33 122.13 448.52 415.71 0.00 0.00 0.00
March 333.18 173.63 159.55 440.01 290.80 0.00 0.00 0.00
April 249.53 81.23 168.30 368.48 237.53 0.00 0.00 0.00
May 201.61 23.43 178.18 318.09 154.58 0.00 0.00 0.00
June 186.41 10.37 176.04 353.50 94.99 0.00 0.00 0.00
July 188.46 14.05 174.40 375.94 66.01 0.00 0.00 0.00
August 225.00 42.03 182.97 457.08 55.81 0.00 0.00 0.00
September 247.45 92.04 155.41 425.36 129.17 0.00 0.00 0.00
October 358.73 232.38 126.34 527.27 264.24 0.00 0.00 0.00
November 385.92 256.09 129.83 502.73 345.96 0.00 0.00 0.00
December 391.26 275.26 116.01 460.29 420.96 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.28 245.21 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.09 55.81 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.27 477.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.47 477.62 0.00 0.00 0.00
February 370.47 248.33 122.13 448.52 415.71 0.00 0.00 0.00
March 333.18 173.63 159.55 440.00 290.80 0.00 0.00 0.00
April 249.53 81.23 168.30 368.48 237.53 0.00 0.00 0.00
May 201.61 23.43 178.18 318.08 154.58 0.00 0.00 0.00
June 186.41 10.37 176.04 353.50 94.99 0.00 0.00 0.00
July 188.46 14.05 174.40 375.93 66.01 0.00 0.00 0.00
August 225.00 42.03 182.97 457.07 55.81 0.00 0.00 0.00
September 247.45 92.04 155.41 425.36 129.17 0.00 0.00 0.00
October 358.72 232.38 126.34 527.27 264.24 0.00 0.00 0.00
November 385.92 256.09 129.83 502.73 345.96 0.00 0.00 0.00
December 391.26 275.25 116.01 460.29 420.96 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.28 245.21 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.08 55.81 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.27 477.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.47 477.62 0.00 0.00 0.00
February 370.47 248.33 122.13 448.52 415.71 0.00 0.00 0.00
March 333.18 173.63 159.55 440.01 290.80 0.00 0.00 0.00
April 249.53 81.23 168.30 368.48 237.53 0.00 0.00 0.00
May 201.61 23.43 178.18 318.09 154.58 0.00 0.00 0.00
June 186.41 10.37 176.04 353.50 94.99 0.00 0.00 0.00
July 188.46 14.05 174.40 375.94 66.01 0.00 0.00 0.00
August 225.00 42.03 182.97 457.08 55.81 0.00 0.00 0.00
September 247.45 92.04 155.41 425.36 129.17 0.00 0.00 0.00
October 358.73 232.38 126.34 527.27 264.24 0.00 0.00 0.00
November 385.92 256.09 129.83 502.73 345.96 0.00 0.00 0.00
December 391.26 275.26 116.01 460.29 420.96 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.28 245.21 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.09 55.81 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.27 477.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.93 276.74 120.19 438.47 477.62 0.00 0.00 0.00
February 370.47 248.33 122.13 448.52 415.71 0.00 0.00 0.00
March 333.18 173.63 159.55 440.00 290.80 0.00 0.00 0.00
April 249.53 81.23 168.30 368.48 237.53 0.00 0.00 0.00
May 201.61 23.43 178.18 318.08 154.58 0.00 0.00 0.00
June 186.41 10.37 176.04 353.50 94.99 0.00 0.00 0.00
July 188.46 14.05 174.40 375.93 66.01 0.00 0.00 0.00
August 225.00 42.03 182.97 457.07 55.81 0.00 0.00 0.00
September 247.45 92.04 155.41 425.36 129.17 0.00 0.00 0.00
October 358.72 232.38 126.34 527.27 264.24 0.00 0.00 0.00
November 385.92 256.09 129.83 502.73 345.96 0.00 0.00 0.00
December 391.26 275.25 116.01 460.29 420.96 0.00 0.00 0.00
                 
Annual Sum or Average 294.25 143.31 150.94 426.28 245.21 0.00 0.00 0.00
Minimum of Months 186.41 10.37 116.01 318.08 55.81 0.00 0.00 0.00
Maximum of Months 396.93 276.74 182.97 527.27 477.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 396.91 276.73 120.19 438.45 477.60 0.00 0.00 0.00
February 370.45 248.32 122.13 448.50 415.70 0.00 0.00 0.00
March 333.16 173.62 159.54 439.99 290.79 0.00 0.00 0.00
April 249.52 81.22 168.29 368.47 237.52 0.00 0.00 0.00
May 201.60 23.43 178.17 318.07 154.58 0.00 0.00 0.00
June 186.40 10.37 176.03 353.49 94.99 0.00 0.00 0.00
July 188.45 14.05 174.40 375.92 66.00 0.00 0.00 0.00
August 224.99 42.03 182.96 457.06 55.81 0.00 0.00 0.00
September 247.44 92.03 155.40 425.34 129.17 0.00 0.00 0.00
October 358.71 232.37 126.34 527.25 264.23 0.00 0.00 0.00
November 385.91 256.08 129.83 502.71 345.95 0.00 0.00 0.00
December 391.25 275.24 116.00 460.27 420.94 0.00 0.00 0.00
                 
Annual Sum or Average 294.24 143.30 150.94 426.26 245.20 0.00 0.00 0.00
Minimum of Months 186.40 10.37 116.00 318.07 55.81 0.00 0.00 0.00
Maximum of Months 396.91 276.73 182.96 527.25 477.60 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.02 86.29 99.73 130.56 639.58 0.00 0.00 0.00
February 213.55 99.85 113.70 199.54 558.52 0.00 0.00 0.00
March 314.76 152.10 162.66 367.45 379.71 0.00 0.00 0.00
April 354.10 162.04 192.07 481.77 303.88 0.00 0.00 0.00
May 355.89 134.83 221.05 550.38 189.74 0.00 0.00 0.00
June 374.26 143.98 230.28 657.19 126.15 0.00 0.00 0.00
July 353.01 130.89 222.13 638.28 95.66 0.00 0.00 0.00
August 345.90 129.35 216.55 628.93 89.90 0.00 0.00 0.00
September 281.82 117.39 164.43 447.57 159.90 0.00 0.00 0.00
October 251.06 130.33 120.73 327.64 344.81 0.00 0.00 0.00
November 200.37 89.94 110.43 201.61 472.07 0.00 0.00 0.00
December 165.30 72.30 93.00 119.81 609.87 0.00 0.00 0.00
                 
Annual Sum or Average 283.36 120.86 162.50 396.95 329.66 0.00 0.00 0.00
Minimum of Months 165.30 72.30 93.00 119.81 89.90 0.00 0.00 0.00
Maximum of Months 374.26 162.04 230.28 657.19 639.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.02 86.29 99.73 130.56 639.58 0.00 0.00 0.00
February 213.55 99.85 113.70 199.54 558.52 0.00 0.00 0.00
March 314.76 152.10 162.66 367.45 379.71 0.00 0.00 0.00
April 354.10 162.04 192.07 481.77 303.88 0.00 0.00 0.00
May 355.89 134.83 221.05 550.38 189.74 0.00 0.00 0.00
June 374.26 143.98 230.28 657.19 126.15 0.00 0.00 0.00
July 353.01 130.89 222.13 638.28 95.66 0.00 0.00 0.00
August 345.90 129.35 216.55 628.93 89.90 0.00 0.00 0.00
September 281.82 117.39 164.43 447.57 159.90 0.00 0.00 0.00
October 251.06 130.33 120.73 327.64 344.81 0.00 0.00 0.00
November 200.37 89.94 110.43 201.61 472.07 0.00 0.00 0.00
December 165.30 72.30 93.00 119.81 609.87 0.00 0.00 0.00
                 
Annual Sum or Average 283.36 120.86 162.50 396.95 329.66 0.00 0.00 0.00
Minimum of Months 165.30 72.30 93.00 119.81 89.90 0.00 0.00 0.00
Maximum of Months 374.26 162.04 230.28 657.19 639.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 186.02 86.29 99.73 130.56 639.57 0.00 0.00 0.00
February 213.55 99.85 113.70 199.54 558.51 0.00 0.00 0.00
March 314.76 152.10 162.66 367.44 379.70 0.00 0.00 0.00
April 354.10 162.03 192.06 481.76 303.87 0.00 0.00 0.00
May 355.88 134.83 221.05 550.37 189.74 0.00 0.00 0.00
June 374.25 143.97 230.28 657.18 126.15 0.00 0.00 0.00
July 353.01 130.88 222.12 638.27 95.66 0.00 0.00 0.00
August 345.90 129.35 216.54 628.92 89.90 0.00 0.00 0.00
September 281.81 117.39 164.42 447.56 159.89 0.00 0.00 0.00
October 251.06 130.33 120.73 327.64 344.80 0.00 0.00 0.00
November 200.36 89.93 110.43 201.60 472.06 0.00 0.00 0.00
December 165.30 72.30 93.00 119.81 609.86 0.00 0.00 0.00
                 
Annual Sum or Average 283.35 120.86 162.49 396.94 329.65 0.00 0.00 0.00
Minimum of Months 165.30 72.30 93.00 119.81 89.90 0.00 0.00 0.00
Maximum of Months 374.25 162.03 230.28 657.18 639.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 371.10 0.00 371.10 50.84 2618.23 0.00 0.00 0.00
February 411.33 0.00 411.33 169.74 2158.68 0.00 0.00 0.00
March 577.48 0.00 577.48 379.03 1384.85 0.00 0.00 0.00
April 698.52 3.10 695.42 758.20 1095.40 0.00 0.00 0.00
May 835.42 26.66 808.75 1169.23 704.27 0.00 0.00 0.00
June 919.41 60.70 858.71 1693.54 438.62 0.00 0.00 0.00
July 867.47 42.17 825.30 1699.96 312.48 0.00 0.00 0.00
August 771.47 8.40 763.07 1556.73 256.36 0.00 0.00 0.00
September 583.16 0.08 583.08 878.45 600.64 0.00 0.00 0.00
October 443.39 0.00 443.39 387.47 1262.71 0.00 0.00 0.00
November 396.82 0.00 396.82 195.32 1723.79 0.00 0.00 0.00
December 343.05 0.00 343.05 50.48 2156.44 0.00 0.00 0.00
                 
Annual Sum or Average 602.59 11.81 590.78 752.39 1221.24 0.00 0.00 0.00
Minimum of Months 343.05 0.00 343.05 50.48 256.36 0.00 0.00 0.00
Maximum of Months 919.41 60.70 858.71 1699.96 2618.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 543.32 245.06 298.25 368.47 1568.71 0.00 0.00 0.00
February 684.95 368.02 316.93 647.69 1307.92 0.00 0.00 0.00
March 861.75 392.29 469.46 950.84 863.28 0.00 0.00 0.00
April 1042.08 475.16 566.92 1420.19 698.88 0.00 0.00 0.00
May 1144.28 483.90 660.38 1744.94 471.85 0.00 0.00 0.00
June 1184.71 496.54 688.17 2079.51 299.55 0.00 0.00 0.00
July 1155.14 485.64 669.50 2100.62 215.24 0.00 0.00 0.00
August 1056.57 419.18 637.39 1959.09 176.82 0.00 0.00 0.00
September 868.36 384.75 483.61 1384.29 394.01 0.00 0.00 0.00
October 740.78 385.45 355.34 935.93 790.72 0.00 0.00 0.00
November 592.26 268.17 324.09 566.62 1043.75 0.00 0.00 0.00
December 513.01 233.85 279.16 371.61 1290.60 0.00 0.00 0.00
                 
Annual Sum or Average 866.47 386.44 480.03 1213.78 757.26 0.00 0.00 0.00
Minimum of Months 513.01 233.85 279.16 368.47 176.82 0.00 0.00 0.00
Maximum of Months 1184.71 496.54 688.17 2100.62 1568.71 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1984.69 1383.72 600.97 2202.36 2262.14 0.00 0.00 0.00
February 1852.38 1241.70 610.68 2247.22 1964.22 0.00 0.00 0.00
March 1665.92 868.18 797.74 2189.10 1395.67 0.00 0.00 0.00
April 1247.66 406.14 841.52 1839.21 1153.38 0.00 0.00 0.00
May 1008.06 117.16 890.89 1587.15 757.10 0.00 0.00 0.00
June 932.06 51.87 880.19 1773.69 472.44 0.00 0.00 0.00
July 942.29 70.26 872.03 1888.93 330.40 0.00 0.00 0.00
August 1125.03 210.16 914.87 2292.74 279.40 0.00 0.00 0.00
September 1237.25 460.19 777.06 2118.37 633.98 0.00 0.00 0.00
October 1793.66 1161.94 631.73 2622.12 1272.76 0.00 0.00 0.00
November 1929.66 1280.49 649.17 2511.97 1653.62 0.00 0.00 0.00
December 1956.35 1376.31 580.04 2317.44 1952.27 0.00 0.00 0.00
                 
Annual Sum or Average 1471.29 716.57 754.72 2132.37 1172.99 0.00 0.00 0.00
Minimum of Months 932.06 51.87 580.04 1587.15 279.40 0.00 0.00 0.00
Maximum of Months 1984.69 1383.72 914.87 2622.12 2262.14 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 558.06 258.87 299.19 425.08 1673.96 0.00 0.00 0.00
February 640.65 299.54 341.11 640.61 1421.20 0.00 0.00 0.00
March 944.28 456.30 487.98 1140.88 966.31 0.00 0.00 0.00
April 1062.30 486.10 576.20 1487.62 792.18 0.00 0.00 0.00
May 1067.64 404.49 663.16 1660.26 530.51 0.00 0.00 0.00
June 1122.77 431.92 690.84 1989.55 345.64 0.00 0.00 0.00
July 1059.03 392.65 666.38 1947.71 247.15 0.00 0.00 0.00
August 1037.70 388.06 649.64 1929.60 214.00 0.00 0.00 0.00
September 845.44 352.16 493.28 1356.33 434.78 0.00 0.00 0.00
October 753.19 390.99 362.20 1011.67 888.07 0.00 0.00 0.00
November 601.10 269.80 331.29 655.67 1174.18 0.00 0.00 0.00
December 495.90 216.91 278.99 408.17 1428.70 0.00 0.00 0.00
                 
Annual Sum or Average 850.07 362.58 487.49 1224.21 840.02 0.00 0.00 0.00
Minimum of Months 495.90 216.91 278.99 408.17 214.00 0.00 0.00 0.00
Maximum of Months 1122.77 486.10 690.84 1989.55 1673.96 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 371.10 0.00 371.10 63.30 2454.77 0.00 0.00 0.00
February 411.33 0.00 411.33 186.87 2022.99 0.00 0.00 0.00
March 577.48 0.00 577.48 408.63 1274.40 0.00 0.00 0.00
April 698.52 3.10 695.42 773.66 1041.32 0.00 0.00 0.00
May 835.42 26.66 808.75 1160.74 693.68 0.00 0.00 0.00
June 919.41 60.70 858.71 1671.41 446.06 0.00 0.00 0.00
July 867.47 42.17 825.30 1673.36 322.53 0.00 0.00 0.00
August 771.47 8.40 763.07 1531.82 267.30 0.00 0.00 0.00
September 583.16 0.08 583.08 873.76 584.39 0.00 0.00 0.00
October 443.39 0.00 443.39 411.52 1158.31 0.00 0.00 0.00
November 396.82 0.00 396.82 234.74 1556.12 0.00 0.00 0.00
December 343.05 0.00 343.05 66.49 1953.71 0.00 0.00 0.00
                 
Annual Sum or Average 602.59 11.81 590.78 757.89 1143.41 0.00 0.00 0.00
Minimum of Months 343.05 0.00 343.05 63.30 267.30 0.00 0.00 0.00
Maximum of Months 919.41 60.70 858.71 1673.36 2454.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 543.32 245.06 298.25 389.98 1465.98 0.00 0.00 0.00
February 684.95 368.02 316.93 668.37 1226.32 0.00 0.00 0.00
March 861.75 392.29 469.46 973.57 805.54 0.00 0.00 0.00
April 1042.08 475.16 566.92 1426.78 673.37 0.00 0.00 0.00
May 1144.28 483.90 660.38 1735.86 469.19 0.00 0.00 0.00
June 1184.71 496.54 688.17 2062.63 306.00 0.00 0.00 0.00
July 1155.14 485.64 669.50 2081.42 222.21 0.00 0.00 0.00
August 1056.57 419.18 637.39 1940.64 184.41 0.00 0.00 0.00
September 868.36 384.75 483.61 1378.62 387.11 0.00 0.00 0.00
October 740.78 385.45 355.34 952.45 737.62 0.00 0.00 0.00
November 592.26 268.17 324.09 605.28 949.17 0.00 0.00 0.00
December 513.01 233.85 279.16 398.34 1167.54 0.00 0.00 0.00
                 
Annual Sum or Average 866.47 386.44 480.03 1220.70 713.52 0.00 0.00 0.00
Minimum of Months 513.01 233.85 279.16 389.98 184.41 0.00 0.00 0.00
Maximum of Months 1184.71 496.54 688.17 2081.42 1465.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 1984.69 1383.72 600.97 2257.42 2098.24 0.00 0.00 0.00
February 1852.38 1241.70 610.68 2284.50 1834.73 0.00 0.00 0.00
March 1665.92 868.18 797.74 2214.95 1305.35 0.00 0.00 0.00
April 1247.66 406.14 841.52 1846.86 1105.52 0.00 0.00 0.00
May 1008.06 117.16 890.89 1575.28 747.29 0.00 0.00 0.00
June 932.06 51.87 880.19 1751.43 479.64 0.00 0.00 0.00
July 942.29 70.26 872.03 1862.64 340.66 0.00 0.00 0.00
August 1125.03 210.16 914.87 2266.83 291.41 0.00 0.00 0.00
September 1237.25 460.19 777.06 2108.75 623.11 0.00 0.00 0.00
October 1793.66 1161.94 631.73 2637.18 1191.87 0.00 0.00 0.00
November 1929.66 1280.49 649.17 2561.35 1515.81 0.00 0.00 0.00
December 1956.35 1376.31 580.04 2375.65 1767.50 0.00 0.00 0.00
                 
Annual Sum or Average 1471.29 716.57 754.72 2144.95 1104.40 0.00 0.00 0.00
Minimum of Months 932.06 51.87 580.04 1575.28 291.41 0.00 0.00 0.00
Maximum of Months 1984.69 1383.72 914.87 2637.18 2098.24 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 558.06 258.87 299.19 441.67 1567.54 0.00 0.00 0.00
February 640.65 299.54 341.11 652.61 1340.14 0.00 0.00 0.00
March 944.28 456.30 487.98 1153.99 904.13 0.00 0.00 0.00
April 1062.30 486.10 576.20 1491.34 761.20 0.00 0.00 0.00
May 1067.64 404.49 663.16 1651.83 524.02 0.00 0.00 0.00
June 1122.77 431.92 690.84 1973.16 348.98 0.00 0.00 0.00
July 1059.03 392.65 666.38 1931.23 252.03 0.00 0.00 0.00
August 1037.70 388.06 649.64 1913.26 220.16 0.00 0.00 0.00
September 845.44 352.16 493.28 1351.05 425.82 0.00 0.00 0.00
October 753.19 390.99 362.20 1021.39 830.03 0.00 0.00 0.00
November 601.10 269.80 331.29 678.83 1080.69 0.00 0.00 0.00
December 495.90 216.91 278.99 424.63 1310.90 0.00 0.00 0.00
                 
Annual Sum or Average 850.07 362.58 487.49 1226.80 794.24 0.00 0.00 0.00
Minimum of Months 495.90 216.91 278.99 424.63 220.16 0.00 0.00 0.00
Maximum of Months 1122.77 486.10 690.84 1973.16 1567.54 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198791E+09 0.00 0.198791E+09 17665393.41 0.158681E+10
February 0.199017E+09 0.00 0.199017E+09 65197276.80 0.118407E+10
March 0.309346E+09 0.00 0.309346E+09 0.179946E+09 0.831061E+09
April 0.362112E+09 1606061.20 0.360506E+09 0.375948E+09 0.608429E+09
May 0.447516E+09 14282166.31 0.433234E+09 0.621417E+09 0.390636E+09
June 0.476624E+09 31468210.52 0.445155E+09 0.873345E+09 0.228442E+09
July 0.464685E+09 22588531.99 0.442097E+09 0.903781E+09 0.167517E+09
August 0.413261E+09 4501801.68 0.408759E+09 0.823155E+09 0.139453E+09
September 0.302309E+09 42556.45 0.302267E+09 0.448453E+09 0.328336E+09
October 0.237518E+09 0.00 0.237518E+09 0.188094E+09 0.757059E+09
November 0.205713E+09 0.00 0.205713E+09 75088190.95 0.102258E+10
December 0.183767E+09 0.00 0.183767E+09 14239373.25 0.137733E+10
           
Annual Sum or Average 0.380066E+10 74489328.14 0.372617E+10 0.458633E+10 0.862173E+10
Minimum of Months 0.183767E+09 0.00 0.183767E+09 14239373.25 0.139453E+09
Maximum of Months 0.476624E+09 31468210.52 0.445155E+09 0.903781E+09 0.158681E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198788E+09 0.00 0.198788E+09 17664720.20 0.158681E+10
February 0.199014E+09 0.00 0.199014E+09 65195760.09 0.118407E+10
March 0.309342E+09 0.00 0.309342E+09 0.179942E+09 0.831060E+09
April 0.362107E+09 1606025.89 0.360501E+09 0.375942E+09 0.608427E+09
May 0.447510E+09 14281852.33 0.433228E+09 0.621408E+09 0.390635E+09
June 0.476617E+09 31467518.73 0.445149E+09 0.873334E+09 0.228441E+09
July 0.464678E+09 22588035.41 0.442090E+09 0.903772E+09 0.167515E+09
August 0.413255E+09 4501702.71 0.408754E+09 0.823147E+09 0.139451E+09
September 0.302305E+09 42555.51 0.302263E+09 0.448447E+09 0.328334E+09
October 0.237515E+09 0.00 0.237515E+09 0.188091E+09 0.757058E+09
November 0.205710E+09 0.00 0.205710E+09 75086027.29 0.102258E+10
December 0.183765E+09 0.00 0.183765E+09 14238704.87 0.137733E+10
           
Annual Sum or Average 0.380061E+10 74487690.58 0.372612E+10 0.458627E+10 0.862172E+10
Minimum of Months 0.183765E+09 0.00 0.183765E+09 14238704.87 0.139451E+09
Maximum of Months 0.476617E+09 31467518.73 0.445149E+09 0.903772E+09 0.158681E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198789E+09 0.00 0.198789E+09 17664944.60 0.158681E+10
February 0.199015E+09 0.00 0.199015E+09 65196265.66 0.118407E+10
March 0.309343E+09 0.00 0.309343E+09 0.179943E+09 0.831061E+09
April 0.362109E+09 1606037.66 0.360502E+09 0.375944E+09 0.608428E+09
May 0.447512E+09 14281956.99 0.433230E+09 0.621411E+09 0.390636E+09
June 0.476619E+09 31467749.32 0.445151E+09 0.873338E+09 0.228441E+09
July 0.464681E+09 22588200.93 0.442092E+09 0.903775E+09 0.167516E+09
August 0.413257E+09 4501735.70 0.408755E+09 0.823149E+09 0.139452E+09
September 0.302307E+09 42555.83 0.302264E+09 0.448449E+09 0.328334E+09
October 0.237516E+09 0.00 0.237516E+09 0.188092E+09 0.757058E+09
November 0.205711E+09 0.00 0.205711E+09 75086748.08 0.102258E+10
December 0.183766E+09 0.00 0.183766E+09 14238927.66 0.137733E+10
           
Annual Sum or Average 0.380062E+10 74488236.43 0.372613E+10 0.458629E+10 0.862172E+10
Minimum of Months 0.183766E+09 0.00 0.183766E+09 14238927.66 0.139452E+09
Maximum of Months 0.476619E+09 31467749.32 0.445151E+09 0.903775E+09 0.158681E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198788E+09 0.00 0.198788E+09 17664720.20 0.158681E+10
February 0.199014E+09 0.00 0.199014E+09 65195760.09 0.118407E+10
March 0.309342E+09 0.00 0.309342E+09 0.179942E+09 0.831060E+09
April 0.362107E+09 1606025.89 0.360501E+09 0.375942E+09 0.608427E+09
May 0.447510E+09 14281852.33 0.433228E+09 0.621408E+09 0.390635E+09
June 0.476617E+09 31467518.73 0.445149E+09 0.873334E+09 0.228441E+09
July 0.464678E+09 22588035.41 0.442090E+09 0.903772E+09 0.167515E+09
August 0.413255E+09 4501702.71 0.408754E+09 0.823147E+09 0.139451E+09
September 0.302305E+09 42555.51 0.302263E+09 0.448447E+09 0.328334E+09
October 0.237515E+09 0.00 0.237515E+09 0.188091E+09 0.757058E+09
November 0.205710E+09 0.00 0.205710E+09 75086027.29 0.102258E+10
December 0.183765E+09 0.00 0.183765E+09 14238704.87 0.137733E+10
           
Annual Sum or Average 0.380061E+10 74487690.58 0.372612E+10 0.458627E+10 0.862172E+10
Minimum of Months 0.183765E+09 0.00 0.183765E+09 14238704.87 0.139451E+09
Maximum of Months 0.476617E+09 31467518.73 0.445149E+09 0.903772E+09 0.158681E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.198780E+09 0.00 0.198780E+09 17664120.43 0.158675E+10
February 0.199007E+09 0.00 0.199007E+09 65193385.19 0.118402E+10
March 0.309330E+09 0.00 0.309330E+09 0.179935E+09 0.831027E+09
April 0.362093E+09 1605967.04 0.360487E+09 0.375928E+09 0.608403E+09
May 0.447493E+09 14281329.04 0.433212E+09 0.621385E+09 0.390620E+09
June 0.476599E+09 31466365.74 0.445132E+09 0.873301E+09 0.228432E+09
July 0.464661E+09 22587207.77 0.442074E+09 0.903737E+09 0.167509E+09
August 0.413240E+09 4501537.77 0.408738E+09 0.823115E+09 0.139446E+09
September 0.302294E+09 42553.96 0.302251E+09 0.448430E+09 0.328321E+09
October 0.237506E+09 0.00 0.237506E+09 0.188084E+09 0.757027E+09
November 0.205702E+09 0.00 0.205702E+09 75083361.33 0.102254E+10
December 0.183758E+09 0.00 0.183758E+09 14238242.38 0.137728E+10
           
Annual Sum or Average 0.380046E+10 74484961.31 0.372598E+10 0.458609E+10 0.862137E+10
Minimum of Months 0.183758E+09 0.00 0.183758E+09 14238242.38 0.139446E+09
Maximum of Months 0.476599E+09 31466365.74 0.445132E+09 0.903737E+09 0.158675E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.485078E+09 0.218795E+09 0.266283E+09 0.303941E+09 0.157153E+10
February 0.552351E+09 0.296774E+09 0.255577E+09 0.502829E+09 0.116584E+10
March 0.769377E+09 0.350243E+09 0.419134E+09 0.841884E+09 0.820850E+09
April 0.900364E+09 0.410543E+09 0.489821E+09 0.123438E+10 0.610822E+09
May 0.102162E+10 0.432029E+09 0.589593E+09 0.157152E+10 0.424487E+09
June 0.102360E+10 0.429017E+09 0.594585E+09 0.181091E+10 0.247291E+09
July 0.103132E+10 0.433583E+09 0.597740E+09 0.189079E+10 0.176190E+09
August 0.943319E+09 0.374248E+09 0.569071E+09 0.176284E+10 0.138522E+09
September 0.750271E+09 0.332425E+09 0.417845E+09 0.120165E+10 0.346626E+09
October 0.661379E+09 0.344132E+09 0.317248E+09 0.828725E+09 0.758708E+09
November 0.511721E+09 0.231705E+09 0.280016E+09 0.463467E+09 0.991623E+09
December 0.458024E+09 0.208785E+09 0.249239E+09 0.303808E+09 0.132259E+10
           
Annual Sum or Average 0.910843E+10 0.406228E+10 0.504615E+10 0.127167E+11 0.857508E+10
Minimum of Months 0.458024E+09 0.208785E+09 0.249239E+09 0.303808E+09 0.138522E+09
Maximum of Months 0.103132E+10 0.433583E+09 0.597740E+09 0.189079E+10 0.157153E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.485078E+09 0.218795E+09 0.266283E+09 0.303941E+09 0.157153E+10
February 0.552351E+09 0.296774E+09 0.255577E+09 0.502829E+09 0.116584E+10
March 0.769377E+09 0.350243E+09 0.419134E+09 0.841884E+09 0.820850E+09
April 0.900364E+09 0.410543E+09 0.489821E+09 0.123438E+10 0.610822E+09
May 0.102162E+10 0.432029E+09 0.589593E+09 0.157152E+10 0.424487E+09
June 0.102360E+10 0.429017E+09 0.594585E+09 0.181091E+10 0.247291E+09
July 0.103132E+10 0.433583E+09 0.597740E+09 0.189079E+10 0.176190E+09
August 0.943319E+09 0.374248E+09 0.569071E+09 0.176284E+10 0.138522E+09
September 0.750271E+09 0.332425E+09 0.417845E+09 0.120165E+10 0.346626E+09
October 0.661379E+09 0.344132E+09 0.317248E+09 0.828725E+09 0.758708E+09
November 0.511721E+09 0.231705E+09 0.280016E+09 0.463467E+09 0.991623E+09
December 0.458024E+09 0.208785E+09 0.249239E+09 0.303808E+09 0.132259E+10
           
Annual Sum or Average 0.910843E+10 0.406228E+10 0.504615E+10 0.127167E+11 0.857508E+10
Minimum of Months 0.458024E+09 0.208785E+09 0.249239E+09 0.303808E+09 0.138522E+09
Maximum of Months 0.103132E+10 0.433583E+09 0.597740E+09 0.189079E+10 0.157153E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.485069E+09 0.218791E+09 0.266279E+09 0.303935E+09 0.157150E+10
February 0.552341E+09 0.296769E+09 0.255572E+09 0.502820E+09 0.116582E+10
March 0.769363E+09 0.350237E+09 0.419127E+09 0.841869E+09 0.820835E+09
April 0.900347E+09 0.410535E+09 0.489812E+09 0.123436E+10 0.610811E+09
May 0.102160E+10 0.432021E+09 0.589582E+09 0.157149E+10 0.424479E+09
June 0.102358E+10 0.429009E+09 0.594575E+09 0.181088E+10 0.247287E+09
July 0.103130E+10 0.433575E+09 0.597729E+09 0.189076E+10 0.176187E+09
August 0.943302E+09 0.374241E+09 0.569060E+09 0.176280E+10 0.138519E+09
September 0.750257E+09 0.332419E+09 0.417838E+09 0.120163E+10 0.346620E+09
October 0.661367E+09 0.344126E+09 0.317242E+09 0.828709E+09 0.758694E+09
November 0.511712E+09 0.231701E+09 0.280011E+09 0.463458E+09 0.991605E+09
December 0.458016E+09 0.208781E+09 0.249234E+09 0.303803E+09 0.132257E+10
           
Annual Sum or Average 0.910827E+10 0.406221E+10 0.504606E+10 0.127165E+11 0.857492E+10
Minimum of Months 0.458016E+09 0.208781E+09 0.249234E+09 0.303803E+09 0.138519E+09
Maximum of Months 0.103130E+10 0.433575E+09 0.597729E+09 0.189076E+10 0.157150E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106314E+10 0.741215E+09 0.321924E+09 0.117440E+10 0.127925E+10
February 0.896239E+09 0.600772E+09 0.295467E+09 0.108506E+10 0.100569E+10
March 0.892383E+09 0.465055E+09 0.427328E+09 0.117851E+10 0.778873E+09
April 0.646778E+09 0.210538E+09 0.436239E+09 0.955107E+09 0.615689E+09
May 0.539991E+09 62760903.20 0.477230E+09 0.851961E+09 0.414031E+09
June 0.483173E+09 26886366.83 0.456287E+09 0.916285E+09 0.246226E+09
July 0.504761E+09 37637437.05 0.467123E+09 0.100691E+10 0.176794E+09
August 0.602647E+09 0.112576E+09 0.490071E+09 0.122423E+10 0.149483E+09
September 0.641382E+09 0.238559E+09 0.402823E+09 0.110253E+10 0.334814E+09
October 0.960813E+09 0.622414E+09 0.338400E+09 0.141225E+10 0.707736E+09
November 0.100032E+10 0.663792E+09 0.336525E+09 0.130308E+10 0.896738E+09
December 0.104796E+10 0.737246E+09 0.310714E+09 0.123285E+10 0.112750E+10
           
Annual Sum or Average 0.927958E+10 0.451945E+10 0.476013E+10 0.134432E+11 0.773283E+10
Minimum of Months 0.483173E+09 26886366.83 0.295467E+09 0.851961E+09 0.149483E+09
Maximum of Months 0.106314E+10 0.741215E+09 0.490071E+09 0.141225E+10 0.127925E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106313E+10 0.741209E+09 0.321922E+09 0.117439E+10 0.127925E+10
February 0.896233E+09 0.600768E+09 0.295465E+09 0.108505E+10 0.100569E+10
March 0.892377E+09 0.465052E+09 0.427325E+09 0.117850E+10 0.778873E+09
April 0.646774E+09 0.210537E+09 0.436237E+09 0.955101E+09 0.615689E+09
May 0.539988E+09 62760443.29 0.477227E+09 0.851957E+09 0.414030E+09
June 0.483171E+09 26886169.80 0.456284E+09 0.916281E+09 0.246226E+09
July 0.504758E+09 37637161.24 0.467121E+09 0.100690E+10 0.176793E+09
August 0.602644E+09 0.112575E+09 0.490069E+09 0.122422E+10 0.149482E+09
September 0.641378E+09 0.238558E+09 0.402821E+09 0.110252E+10 0.334814E+09
October 0.960807E+09 0.622409E+09 0.338398E+09 0.141224E+10 0.707736E+09
November 0.100031E+10 0.663787E+09 0.336523E+09 0.130307E+10 0.896738E+09
December 0.104795E+10 0.737241E+09 0.310712E+09 0.123284E+10 0.112750E+10
           
Annual Sum or Average 0.927952E+10 0.451942E+10 0.476010E+10 0.134431E+11 0.773282E+10
Minimum of Months 0.483171E+09 26886169.80 0.295465E+09 0.851957E+09 0.149482E+09
Maximum of Months 0.106313E+10 0.741209E+09 0.490069E+09 0.141224E+10 0.127925E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106314E+10 0.741215E+09 0.321924E+09 0.117440E+10 0.127925E+10
February 0.896239E+09 0.600772E+09 0.295467E+09 0.108506E+10 0.100569E+10
March 0.892383E+09 0.465055E+09 0.427328E+09 0.117851E+10 0.778873E+09
April 0.646778E+09 0.210538E+09 0.436239E+09 0.955107E+09 0.615689E+09
May 0.539991E+09 62760903.20 0.477230E+09 0.851961E+09 0.414031E+09
June 0.483173E+09 26886366.83 0.456287E+09 0.916285E+09 0.246226E+09
July 0.504761E+09 37637437.05 0.467123E+09 0.100691E+10 0.176794E+09
August 0.602647E+09 0.112576E+09 0.490071E+09 0.122423E+10 0.149483E+09
September 0.641382E+09 0.238559E+09 0.402823E+09 0.110253E+10 0.334814E+09
October 0.960813E+09 0.622414E+09 0.338400E+09 0.141225E+10 0.707736E+09
November 0.100032E+10 0.663792E+09 0.336525E+09 0.130308E+10 0.896738E+09
December 0.104796E+10 0.737246E+09 0.310714E+09 0.123285E+10 0.112750E+10
           
Annual Sum or Average 0.927958E+10 0.451945E+10 0.476013E+10 0.134432E+11 0.773283E+10
Minimum of Months 0.483173E+09 26886366.83 0.295467E+09 0.851961E+09 0.149483E+09
Maximum of Months 0.106314E+10 0.741215E+09 0.490071E+09 0.141225E+10 0.127925E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106313E+10 0.741209E+09 0.321922E+09 0.117439E+10 0.127925E+10
February 0.896233E+09 0.600768E+09 0.295465E+09 0.108505E+10 0.100569E+10
March 0.892377E+09 0.465052E+09 0.427325E+09 0.117850E+10 0.778873E+09
April 0.646774E+09 0.210537E+09 0.436237E+09 0.955101E+09 0.615689E+09
May 0.539988E+09 62760443.29 0.477227E+09 0.851957E+09 0.414030E+09
June 0.483171E+09 26886169.80 0.456284E+09 0.916281E+09 0.246226E+09
July 0.504758E+09 37637161.24 0.467121E+09 0.100690E+10 0.176793E+09
August 0.602644E+09 0.112575E+09 0.490069E+09 0.122422E+10 0.149482E+09
September 0.641378E+09 0.238558E+09 0.402821E+09 0.110252E+10 0.334814E+09
October 0.960807E+09 0.622409E+09 0.338398E+09 0.141224E+10 0.707736E+09
November 0.100031E+10 0.663787E+09 0.336523E+09 0.130307E+10 0.896738E+09
December 0.104795E+10 0.737241E+09 0.310712E+09 0.123284E+10 0.112750E+10
           
Annual Sum or Average 0.927952E+10 0.451942E+10 0.476010E+10 0.134431E+11 0.773282E+10
Minimum of Months 0.483171E+09 26886169.80 0.295465E+09 0.851957E+09 0.149482E+09
Maximum of Months 0.106313E+10 0.741209E+09 0.490069E+09 0.141224E+10 0.127925E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.106309E+10 0.741182E+09 0.321910E+09 0.117435E+10 0.127920E+10
February 0.896200E+09 0.600746E+09 0.295454E+09 0.108501E+10 0.100565E+10
March 0.892344E+09 0.465035E+09 0.427309E+09 0.117846E+10 0.778842E+09
April 0.646750E+09 0.210529E+09 0.436221E+09 0.955066E+09 0.615664E+09
May 0.539967E+09 62758143.71 0.477209E+09 0.851925E+09 0.414014E+09
June 0.483152E+09 26885184.68 0.456267E+09 0.916246E+09 0.246216E+09
July 0.504739E+09 37635782.20 0.467103E+09 0.100686E+10 0.176786E+09
August 0.602621E+09 0.112571E+09 0.490050E+09 0.122418E+10 0.149476E+09
September 0.641354E+09 0.238549E+09 0.402805E+09 0.110248E+10 0.334800E+09
October 0.960772E+09 0.622387E+09 0.338385E+09 0.141218E+10 0.707707E+09
November 0.100027E+10 0.663763E+09 0.336510E+09 0.130303E+10 0.896702E+09
December 0.104791E+10 0.737214E+09 0.310700E+09 0.123280E+10 0.112745E+10
           
Annual Sum or Average 0.927918E+10 0.451925E+10 0.475992E+10 0.134426E+11 0.773251E+10
Minimum of Months 0.483152E+09 26885184.68 0.295454E+09 0.851925E+09 0.149476E+09
Maximum of Months 0.106309E+10 0.741182E+09 0.490050E+09 0.141218E+10 0.127920E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.498243E+09 0.231120E+09 0.267123E+09 0.349688E+09 0.171305E+10
February 0.516627E+09 0.241554E+09 0.275072E+09 0.482731E+09 0.135117E+10
March 0.843065E+09 0.407388E+09 0.435677E+09 0.984165E+09 0.101701E+10
April 0.917838E+09 0.419999E+09 0.497839E+09 0.124874E+10 0.787654E+09
May 0.953203E+09 0.361131E+09 0.592072E+09 0.147414E+10 0.508203E+09
June 0.970082E+09 0.373186E+09 0.596896E+09 0.170344E+10 0.326989E+09
July 0.945509E+09 0.350563E+09 0.594946E+09 0.170958E+10 0.256222E+09
August 0.926464E+09 0.346461E+09 0.580003E+09 0.168454E+10 0.240781E+09
September 0.730466E+09 0.304271E+09 0.426195E+09 0.116010E+10 0.414454E+09
October 0.672451E+09 0.349076E+09 0.323375E+09 0.877564E+09 0.923541E+09
November 0.519353E+09 0.233112E+09 0.286240E+09 0.522564E+09 0.122360E+10
December 0.442744E+09 0.193657E+09 0.249087E+09 0.320904E+09 0.163348E+10
           
Annual Sum or Average 0.893604E+10 0.381152E+10 0.512453E+10 0.125181E+11 0.103962E+11
Minimum of Months 0.442744E+09 0.193657E+09 0.249087E+09 0.320904E+09 0.240781E+09
Maximum of Months 0.970082E+09 0.419999E+09 0.596896E+09 0.170958E+10 0.171305E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.498243E+09 0.231120E+09 0.267123E+09 0.349688E+09 0.171305E+10
February 0.516627E+09 0.241554E+09 0.275072E+09 0.482731E+09 0.135117E+10
March 0.843065E+09 0.407388E+09 0.435677E+09 0.984165E+09 0.101701E+10
April 0.917838E+09 0.419999E+09 0.497839E+09 0.124874E+10 0.787654E+09
May 0.953203E+09 0.361131E+09 0.592072E+09 0.147414E+10 0.508203E+09
June 0.970082E+09 0.373186E+09 0.596896E+09 0.170344E+10 0.326989E+09
July 0.945509E+09 0.350563E+09 0.594946E+09 0.170958E+10 0.256222E+09
August 0.926464E+09 0.346461E+09 0.580003E+09 0.168454E+10 0.240781E+09
September 0.730466E+09 0.304271E+09 0.426195E+09 0.116010E+10 0.414454E+09
October 0.672451E+09 0.349076E+09 0.323375E+09 0.877564E+09 0.923541E+09
November 0.519353E+09 0.233112E+09 0.286240E+09 0.522564E+09 0.122360E+10
December 0.442744E+09 0.193657E+09 0.249087E+09 0.320904E+09 0.163348E+10
           
Annual Sum or Average 0.893604E+10 0.381152E+10 0.512453E+10 0.125181E+11 0.103962E+11
Minimum of Months 0.442744E+09 0.193657E+09 0.249087E+09 0.320904E+09 0.240781E+09
Maximum of Months 0.970082E+09 0.419999E+09 0.596896E+09 0.170958E+10 0.171305E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.498234E+09 0.231116E+09 0.267118E+09 0.349682E+09 0.171302E+10
February 0.516617E+09 0.241550E+09 0.275067E+09 0.482722E+09 0.135114E+10
March 0.843049E+09 0.407380E+09 0.435669E+09 0.984147E+09 0.101700E+10
April 0.917821E+09 0.419991E+09 0.497830E+09 0.124871E+10 0.787640E+09
May 0.953186E+09 0.361124E+09 0.592061E+09 0.147411E+10 0.508194E+09
June 0.970064E+09 0.373179E+09 0.596885E+09 0.170341E+10 0.326983E+09
July 0.945492E+09 0.350556E+09 0.594936E+09 0.170955E+10 0.256218E+09
August 0.926447E+09 0.346455E+09 0.579993E+09 0.168451E+10 0.240776E+09
September 0.730453E+09 0.304266E+09 0.426187E+09 0.116008E+10 0.414447E+09
October 0.672438E+09 0.349069E+09 0.323369E+09 0.877548E+09 0.923524E+09
November 0.519343E+09 0.233108E+09 0.286235E+09 0.522554E+09 0.122358E+10
December 0.442736E+09 0.193653E+09 0.249083E+09 0.320898E+09 0.163345E+10
           
Annual Sum or Average 0.893588E+10 0.381145E+10 0.512443E+10 0.125179E+11 0.103960E+11
Minimum of Months 0.442736E+09 0.193653E+09 0.249083E+09 0.320898E+09 0.240776E+09
Maximum of Months 0.970064E+09 0.419991E+09 0.596885E+09 0.170955E+10 0.171302E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.993954E+09 0.00 0.993954E+09 0.136165E+09 0.701267E+10
February 0.995084E+09 0.00 0.995084E+09 0.410633E+09 0.522229E+10
March 0.154673E+10 0.00 0.154673E+10 0.101518E+10 0.370917E+10
April 0.181056E+10 8030357.15 0.180253E+10 0.196525E+10 0.283929E+10
May 0.223758E+10 71411286.64 0.216617E+10 0.313165E+10 0.188631E+10
June 0.238312E+10 0.157342E+09 0.222578E+10 0.438967E+10 0.113689E+10
July 0.232342E+10 0.112943E+09 0.221048E+10 0.455316E+10 0.836943E+09
August 0.206630E+10 22509151.83 0.204380E+10 0.416955E+10 0.686636E+09
September 0.151155E+10 212783.61 0.151133E+10 0.227694E+10 0.155685E+10
October 0.118759E+10 0.00 0.118759E+10 0.103781E+10 0.338203E+10
November 0.102856E+10 0.00 0.102856E+10 0.506258E+09 0.446807E+10
December 0.918837E+09 0.00 0.918837E+09 0.135211E+09 0.577582E+10
           
Annual Sum or Average 0.190033E+11 0.372449E+09 0.186308E+11 0.237275E+11 0.385130E+11
Minimum of Months 0.918837E+09 0.00 0.918837E+09 0.135211E+09 0.686636E+09
Maximum of Months 0.238312E+10 0.157342E+09 0.222578E+10 0.455316E+10 0.701267E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.145522E+10 0.656378E+09 0.798842E+09 0.986902E+09 0.420163E+10
February 0.165704E+10 0.890313E+09 0.766723E+09 0.156688E+10 0.316413E+10
March 0.230811E+10 0.105072E+10 0.125739E+10 0.254673E+10 0.231221E+10
April 0.270106E+10 0.123161E+10 0.146945E+10 0.368112E+10 0.181149E+10
May 0.306484E+10 0.129607E+10 0.176876E+10 0.467364E+10 0.126381E+10
June 0.307078E+10 0.128704E+10 0.178374E+10 0.539010E+10 0.776433E+09
July 0.309394E+10 0.130073E+10 0.179320E+10 0.562631E+10 0.576494E+09
August 0.282993E+10 0.112273E+10 0.170720E+10 0.524723E+10 0.473607E+09
September 0.225079E+10 0.997266E+09 0.125352E+10 0.358807E+10 0.102128E+10
October 0.198412E+10 0.103239E+10 0.951733E+09 0.250680E+10 0.211787E+10
November 0.153515E+10 0.695109E+09 0.840039E+09 0.146868E+10 0.270540E+10
December 0.137406E+10 0.626349E+09 0.747709E+09 0.995331E+09 0.345673E+10
           
Annual Sum or Average 0.273250E+11 0.121867E+11 0.151383E+11 0.382778E+11 0.238811E+11
Minimum of Months 0.137406E+10 0.626349E+09 0.747709E+09 0.986902E+09 0.473607E+09
Maximum of Months 0.309394E+10 0.130073E+10 0.179320E+10 0.562631E+10 0.420163E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.531579E+10 0.370615E+10 0.160964E+10 0.589880E+10 0.605891E+10
February 0.448128E+10 0.300392E+10 0.147735E+10 0.543648E+10 0.475183E+10
March 0.446199E+10 0.232533E+10 0.213666E+10 0.586330E+10 0.373816E+10
April 0.323393E+10 0.105271E+10 0.218122E+10 0.476722E+10 0.298957E+10
May 0.269998E+10 0.313811E+09 0.238617E+10 0.425103E+10 0.202782E+10
June 0.241589E+10 0.134435E+09 0.228145E+10 0.459740E+10 0.122457E+10
July 0.252383E+10 0.188191E+09 0.233564E+10 0.505931E+10 0.884934E+09
August 0.301327E+10 0.562890E+09 0.245038E+10 0.614087E+10 0.748333E+09
September 0.320696E+10 0.119282E+10 0.201414E+10 0.549083E+10 0.164329E+10
October 0.480415E+10 0.311213E+10 0.169202E+10 0.702309E+10 0.340897E+10
November 0.500168E+10 0.331903E+10 0.168265E+10 0.651101E+10 0.428618E+10
December 0.523990E+10 0.368631E+10 0.155359E+10 0.620703E+10 0.522896E+10
           
Annual Sum or Average 0.463986E+11 0.225977E+11 0.238009E+11 0.672464E+11 0.369915E+11
Minimum of Months 0.241589E+10 0.134435E+09 0.147735E+10 0.425103E+10 0.748333E+09
Maximum of Months 0.531579E+10 0.370615E+10 0.245038E+10 0.702309E+10 0.605891E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.149471E+10 0.693353E+09 0.801361E+09 0.113852E+10 0.448353E+10
February 0.154986E+10 0.724655E+09 0.825209E+09 0.154976E+10 0.343816E+10
March 0.252917E+10 0.122215E+10 0.130702E+10 0.305574E+10 0.258817E+10
April 0.275349E+10 0.125998E+10 0.149350E+10 0.385591E+10 0.205333E+10
May 0.285958E+10 0.108338E+10 0.177620E+10 0.444684E+10 0.142093E+10
June 0.291021E+10 0.111955E+10 0.179067E+10 0.515690E+10 0.895899E+09
July 0.283650E+10 0.105168E+10 0.178482E+10 0.521675E+10 0.661969E+09
August 0.277936E+10 0.103937E+10 0.173999E+10 0.516825E+10 0.573189E+09
September 0.219138E+10 0.912804E+09 0.127857E+10 0.351561E+10 0.112695E+10
October 0.201733E+10 0.104722E+10 0.970115E+09 0.270966E+10 0.237861E+10
November 0.155804E+10 0.699329E+09 0.858712E+09 0.169951E+10 0.304348E+10
December 0.132822E+10 0.580965E+09 0.747255E+09 0.109325E+10 0.382662E+10
           
Annual Sum or Average 0.268079E+11 0.114344E+11 0.153734E+11 0.386067E+11 0.264908E+11
Minimum of Months 0.132822E+10 0.580965E+09 0.747255E+09 0.109325E+10 0.573189E+09
Maximum of Months 0.291021E+10 0.125998E+10 0.179067E+10 0.521675E+10 0.448353E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.993954E+09 0.00 0.993954E+09 0.169548E+09 0.657485E+10
February 0.995084E+09 0.00 0.995084E+09 0.452077E+09 0.489401E+10
March 0.154673E+10 0.00 0.154673E+10 0.109448E+10 0.341335E+10
April 0.181056E+10 8030357.15 0.180253E+10 0.200533E+10 0.269910E+10
May 0.223758E+10 71411286.64 0.216617E+10 0.310893E+10 0.185795E+10
June 0.238312E+10 0.157342E+09 0.222578E+10 0.433230E+10 0.115618E+10
July 0.232342E+10 0.112943E+09 0.221048E+10 0.448193E+10 0.863853E+09
August 0.206630E+10 22509151.83 0.204380E+10 0.410281E+10 0.715939E+09
September 0.151155E+10 212783.61 0.151133E+10 0.226478E+10 0.151474E+10
October 0.118759E+10 0.00 0.118759E+10 0.110221E+10 0.310242E+10
November 0.102856E+10 0.00 0.102856E+10 0.608454E+09 0.403347E+10
December 0.918837E+09 0.00 0.918837E+09 0.178099E+09 0.523281E+10
           
Annual Sum or Average 0.190033E+11 0.372449E+09 0.186308E+11 0.239010E+11 0.360587E+11
Minimum of Months 0.918837E+09 0.00 0.918837E+09 0.169548E+09 0.715939E+09
Maximum of Months 0.238312E+10 0.157342E+09 0.222578E+10 0.448193E+10 0.657485E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.145522E+10 0.656378E+09 0.798842E+09 0.104453E+10 0.392649E+10
February 0.165704E+10 0.890313E+09 0.766723E+09 0.161692E+10 0.296671E+10
March 0.230811E+10 0.105072E+10 0.125739E+10 0.260762E+10 0.215756E+10
April 0.270106E+10 0.123161E+10 0.146945E+10 0.369821E+10 0.174536E+10
May 0.306484E+10 0.129607E+10 0.176876E+10 0.464933E+10 0.125667E+10
June 0.307078E+10 0.128704E+10 0.178374E+10 0.534634E+10 0.793146E+09
July 0.309394E+10 0.130073E+10 0.179320E+10 0.557488E+10 0.595180E+09
August 0.282993E+10 0.112273E+10 0.170720E+10 0.519782E+10 0.493931E+09
September 0.225079E+10 0.997266E+09 0.125352E+10 0.357339E+10 0.100339E+10
October 0.198412E+10 0.103239E+10 0.951733E+09 0.255105E+10 0.197565E+10
November 0.153515E+10 0.695109E+09 0.840039E+09 0.156888E+10 0.246026E+10
December 0.137406E+10 0.626349E+09 0.747709E+09 0.106691E+10 0.312714E+10
           
Annual Sum or Average 0.273250E+11 0.121867E+11 0.151383E+11 0.384959E+11 0.225015E+11
Minimum of Months 0.137406E+10 0.626349E+09 0.747709E+09 0.104453E+10 0.493931E+09
Maximum of Months 0.309394E+10 0.130073E+10 0.179320E+10 0.557488E+10 0.392649E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.531579E+10 0.370615E+10 0.160964E+10 0.604629E+10 0.561992E+10
February 0.448128E+10 0.300392E+10 0.147735E+10 0.552667E+10 0.443857E+10
March 0.446199E+10 0.232533E+10 0.213666E+10 0.593252E+10 0.349625E+10
April 0.323393E+10 0.105271E+10 0.218122E+10 0.478707E+10 0.286550E+10
May 0.269998E+10 0.313811E+09 0.238617E+10 0.421923E+10 0.200155E+10
June 0.241589E+10 0.134435E+09 0.228145E+10 0.453970E+10 0.124324E+10
July 0.252383E+10 0.188191E+09 0.233564E+10 0.498889E+10 0.912433E+09
August 0.301327E+10 0.562890E+09 0.245038E+10 0.607148E+10 0.780521E+09
September 0.320696E+10 0.119282E+10 0.201414E+10 0.546587E+10 0.161509E+10
October 0.480415E+10 0.311213E+10 0.169202E+10 0.706342E+10 0.319230E+10
November 0.500168E+10 0.331903E+10 0.168265E+10 0.663902E+10 0.392899E+10
December 0.523990E+10 0.368631E+10 0.155359E+10 0.636294E+10 0.473408E+10
           
Annual Sum or Average 0.463986E+11 0.225977E+11 0.238009E+11 0.676431E+11 0.348285E+11
Minimum of Months 0.241589E+10 0.134435E+09 0.147735E+10 0.421923E+10 0.780521E+09
Maximum of Months 0.531579E+10 0.370615E+10 0.245038E+10 0.706342E+10 0.561992E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.149471E+10 0.693353E+09 0.801361E+09 0.118296E+10 0.419849E+10
February 0.154986E+10 0.724655E+09 0.825209E+09 0.157878E+10 0.324206E+10
March 0.252917E+10 0.122215E+10 0.130702E+10 0.309086E+10 0.242161E+10
April 0.275349E+10 0.125998E+10 0.149350E+10 0.386556E+10 0.197304E+10
May 0.285958E+10 0.108338E+10 0.177620E+10 0.442426E+10 0.140354E+10
June 0.291021E+10 0.111955E+10 0.179067E+10 0.511444E+10 0.904551E+09
July 0.283650E+10 0.105168E+10 0.178482E+10 0.517260E+10 0.675045E+09
August 0.277936E+10 0.103937E+10 0.173999E+10 0.512449E+10 0.589668E+09
September 0.219138E+10 0.912804E+09 0.127857E+10 0.350192E+10 0.110372E+10
October 0.201733E+10 0.104722E+10 0.970115E+09 0.273569E+10 0.222316E+10
November 0.155804E+10 0.699329E+09 0.858712E+09 0.175953E+10 0.280114E+10
December 0.132822E+10 0.580965E+09 0.747255E+09 0.113733E+10 0.351110E+10
           
Annual Sum or Average 0.268079E+11 0.114344E+11 0.153734E+11 0.386884E+11 0.250471E+11
Minimum of Months 0.132822E+10 0.580965E+09 0.747255E+09 0.113733E+10 0.589668E+09
Maximum of Months 0.291021E+10 0.125998E+10 0.179067E+10 0.517260E+10 0.419849E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 32.98 2962.22 371.09 0.00 371.09 0.00 0.00
February 134.75 2447.21 411.32 0.00 411.32 0.00 0.00
March 335.91 1551.40 577.47 0.00 577.47 0.00 0.00
April 725.19 1173.65 698.51 3.10 695.41 0.00 0.00
May 1160.03 729.23 835.40 26.66 808.74 0.00 0.00
June 1684.67 440.66 919.40 60.70 858.70 0.00 0.00
July 1687.14 312.71 867.45 42.17 825.28 0.00 0.00
August 1536.63 260.32 771.46 8.40 763.05 0.00 0.00
September 865.06 633.36 583.15 0.08 583.07 0.00 0.00
October 351.12 1413.25 443.39 0.00 443.39 0.00 0.00
November 144.84 1972.56 396.82 0.00 396.82 0.00 0.00
December 26.58 2571.16 343.05 0.00 343.05 0.00 0.00
               
Annual Sum or Average 727.15 1366.95 602.58 11.81 590.77 0.00 0.00
Minimum of Months 26.58 260.32 343.05 0.00 343.05 0.00 0.00
Maximum of Months 1687.14 2962.22 919.40 60.70 858.70 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 340.43 1760.22 543.32 245.06 298.25 0.00 0.00
February 623.54 1445.72 684.95 368.02 316.93 0.00 0.00
March 942.97 919.41 861.75 392.29 469.46 0.00 0.00
April 1428.67 706.97 1042.08 475.16 566.92 0.00 0.00
May 1760.20 475.45 1144.28 483.90 660.38 0.00 0.00
June 2095.95 286.22 1184.72 496.54 688.17 0.00 0.00
July 2117.81 197.34 1155.15 485.64 669.51 0.00 0.00
August 1974.49 155.15 1056.58 419.18 637.40 0.00 0.00
September 1390.79 401.19 868.36 384.75 483.61 0.00 0.00
October 928.23 849.80 740.79 385.45 355.34 0.00 0.00
November 536.42 1147.70 592.27 268.18 324.09 0.00 0.00
December 340.28 1481.39 513.02 233.85 279.16 0.00 0.00
               
Annual Sum or Average 1209.73 815.74 866.47 386.44 480.03 0.00 0.00
Minimum of Months 340.28 155.15 513.02 233.85 279.16 0.00 0.00
Maximum of Months 2117.81 1760.22 1184.72 496.54 688.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2192.32 2388.07 1984.63 1383.67 600.96 0.00 0.00
February 2242.57 2078.55 1852.32 1241.66 610.66 0.00 0.00
March 2200.01 1453.98 1665.87 868.15 797.72 0.00 0.00
April 1842.39 1187.66 1247.63 406.13 841.50 0.00 0.00
May 1590.41 772.90 1008.04 117.16 890.88 0.00 0.00
June 1767.51 474.97 932.04 51.86 880.17 0.00 0.00
July 1879.66 330.03 942.27 70.26 872.01 0.00 0.00
August 2285.35 279.05 1125.00 210.15 914.85 0.00 0.00
September 2126.77 645.85 1237.22 460.18 777.04 0.00 0.00
October 2636.33 1321.18 1793.61 1161.90 631.71 0.00 0.00
November 2513.64 1729.80 1929.60 1280.45 649.15 0.00 0.00
December 2301.44 2104.78 1956.29 1376.26 580.03 0.00 0.00
               
Annual Sum or Average 2131.38 1226.02 1471.25 716.55 754.71 0.00 0.00
Minimum of Months 1590.41 279.05 932.04 51.86 580.03 0.00 0.00
Maximum of Months 2636.33 2388.07 1984.63 1383.67 914.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 391.67 1918.73 558.06 258.87 299.19 0.00 0.00
February 598.62 1675.55 640.65 299.54 341.11 0.00 0.00
March 1102.33 1139.12 944.29 456.30 487.99 0.00 0.00
April 1445.29 911.63 1062.31 486.11 576.20 0.00 0.00
May 1651.13 569.22 1067.65 404.49 663.16 0.00 0.00
June 1971.56 378.46 1122.77 431.93 690.85 0.00 0.00
July 1914.84 286.99 1059.03 392.65 666.38 0.00 0.00
August 1886.79 269.69 1037.70 388.06 649.64 0.00 0.00
September 1342.70 479.69 845.44 352.16 493.28 0.00 0.00
October 982.93 1034.43 753.19 390.99 362.20 0.00 0.00
November 604.82 1416.19 601.10 269.80 331.29 0.00 0.00
December 359.43 1829.61 495.90 216.91 278.99 0.00 0.00
               
Annual Sum or Average 1190.84 988.97 850.08 362.59 487.49 0.00 0.00
Minimum of Months 359.43 269.69 495.90 216.91 278.99 0.00 0.00
Maximum of Months 1971.56 1918.73 1122.77 486.11 690.85 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 50.84 2618.23 371.10 0.00 371.10 0.00 0.00
February 169.74 2158.68 411.33 0.00 411.33 0.00 0.00
March 379.03 1384.85 577.48 0.00 577.48 0.00 0.00
April 758.20 1095.40 698.52 3.10 695.42 0.00 0.00
May 1169.23 704.27 835.42 26.66 808.75 0.00 0.00
June 1693.54 438.62 919.41 60.70 858.71 0.00 0.00
July 1699.96 312.48 867.47 42.17 825.30 0.00 0.00
August 1556.73 256.36 771.47 8.40 763.07 0.00 0.00
September 878.45 600.64 583.16 0.08 583.08 0.00 0.00
October 387.47 1262.71 443.39 0.00 443.39 0.00 0.00
November 195.32 1723.79 396.82 0.00 396.82 0.00 0.00
December 50.48 2156.44 343.05 0.00 343.05 0.00 0.00
               
Annual Sum or Average 752.39 1221.24 602.59 11.81 590.78 0.00 0.00
Minimum of Months 50.48 256.36 343.05 0.00 343.05 0.00 0.00
Maximum of Months 1699.96 2618.23 919.41 60.70 858.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 368.47 1568.71 543.32 245.06 298.25 0.00 0.00
February 647.69 1307.92 684.95 368.02 316.93 0.00 0.00
March 950.84 863.28 861.75 392.29 469.46 0.00 0.00
April 1420.19 698.88 1042.08 475.16 566.92 0.00 0.00
May 1744.94 471.85 1144.28 483.90 660.38 0.00 0.00
June 2079.51 299.55 1184.71 496.54 688.17 0.00 0.00
July 2100.62 215.24 1155.14 485.64 669.50 0.00 0.00
August 1959.09 176.82 1056.57 419.18 637.39 0.00 0.00
September 1384.29 394.01 868.36 384.75 483.61 0.00 0.00
October 935.93 790.72 740.78 385.45 355.34 0.00 0.00
November 566.62 1043.75 592.26 268.17 324.09 0.00 0.00
December 371.61 1290.60 513.01 233.85 279.16 0.00 0.00
               
Annual Sum or Average 1213.78 757.26 866.47 386.44 480.03 0.00 0.00
Minimum of Months 368.47 176.82 513.01 233.85 279.16 0.00 0.00
Maximum of Months 2100.62 1568.71 1184.71 496.54 688.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2202.36 2262.14 1984.69 1383.72 600.97 0.00 0.00
February 2247.22 1964.22 1852.38 1241.70 610.68 0.00 0.00
March 2189.10 1395.67 1665.92 868.18 797.74 0.00 0.00
April 1839.21 1153.38 1247.66 406.14 841.52 0.00 0.00
May 1587.15 757.10 1008.06 117.16 890.89 0.00 0.00
June 1773.69 472.44 932.06 51.87 880.19 0.00 0.00
July 1888.93 330.40 942.29 70.26 872.03 0.00 0.00
August 2292.74 279.40 1125.03 210.16 914.87 0.00 0.00
September 2118.37 633.98 1237.25 460.19 777.06 0.00 0.00
October 2622.12 1272.76 1793.66 1161.94 631.73 0.00 0.00
November 2511.97 1653.62 1929.66 1280.49 649.17 0.00 0.00
December 2317.44 1952.27 1956.35 1376.31 580.04 0.00 0.00
               
Annual Sum or Average 2132.37 1172.99 1471.29 716.57 754.72 0.00 0.00
Minimum of Months 1587.15 279.40 932.06 51.87 580.04 0.00 0.00
Maximum of Months 2622.12 2262.14 1984.69 1383.72 914.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 425.08 1673.96 558.06 258.87 299.19 0.00 0.00
February 640.61 1421.20 640.65 299.54 341.11 0.00 0.00
March 1140.88 966.31 944.28 456.30 487.98 0.00 0.00
April 1487.62 792.18 1062.30 486.10 576.20 0.00 0.00
May 1660.26 530.51 1067.64 404.49 663.16 0.00 0.00
June 1989.55 345.64 1122.77 431.92 690.84 0.00 0.00
July 1947.71 247.15 1059.03 392.65 666.38 0.00 0.00
August 1929.60 214.00 1037.70 388.06 649.64 0.00 0.00
September 1356.33 434.78 845.44 352.16 493.28 0.00 0.00
October 1011.67 888.07 753.19 390.99 362.20 0.00 0.00
November 655.67 1174.18 601.10 269.80 331.29 0.00 0.00
December 408.17 1428.70 495.90 216.91 278.99 0.00 0.00
               
Annual Sum or Average 1224.21 840.02 850.07 362.58 487.49 0.00 0.00
Minimum of Months 408.17 214.00 495.90 216.91 278.99 0.00 0.00
Maximum of Months 1989.55 1673.96 1122.77 486.10 690.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 63.30 2454.77 371.10 0.00 371.10 0.00 0.00
February 186.87 2022.99 411.33 0.00 411.33 0.00 0.00
March 408.63 1274.40 577.48 0.00 577.48 0.00 0.00
April 773.66 1041.32 698.52 3.10 695.42 0.00 0.00
May 1160.74 693.68 835.42 26.66 808.75 0.00 0.00
June 1671.41 446.06 919.41 60.70 858.71 0.00 0.00
July 1673.36 322.53 867.47 42.17 825.30 0.00 0.00
August 1531.82 267.30 771.47 8.40 763.07 0.00 0.00
September 873.76 584.39 583.16 0.08 583.08 0.00 0.00
October 411.52 1158.31 443.39 0.00 443.39 0.00 0.00
November 234.74 1556.12 396.82 0.00 396.82 0.00 0.00
December 66.49 1953.71 343.05 0.00 343.05 0.00 0.00
               
Annual Sum or Average 757.89 1143.41 602.59 11.81 590.78 0.00 0.00
Minimum of Months 63.30 267.30 343.05 0.00 343.05 0.00 0.00
Maximum of Months 1673.36 2454.77 919.41 60.70 858.71 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 389.98 1465.98 543.32 245.06 298.25 0.00 0.00
February 668.37 1226.32 684.95 368.02 316.93 0.00 0.00
March 973.57 805.54 861.75 392.29 469.46 0.00 0.00
April 1426.78 673.37 1042.08 475.16 566.92 0.00 0.00
May 1735.86 469.19 1144.28 483.90 660.38 0.00 0.00
June 2062.63 306.00 1184.71 496.54 688.17 0.00 0.00
July 2081.42 222.21 1155.14 485.64 669.50 0.00 0.00
August 1940.64 184.41 1056.57 419.18 637.39 0.00 0.00
September 1378.62 387.11 868.36 384.75 483.61 0.00 0.00
October 952.45 737.62 740.78 385.45 355.34 0.00 0.00
November 605.28 949.17 592.26 268.17 324.09 0.00 0.00
December 398.34 1167.54 513.01 233.85 279.16 0.00 0.00
               
Annual Sum or Average 1220.70 713.52 866.47 386.44 480.03 0.00 0.00
Minimum of Months 389.98 184.41 513.01 233.85 279.16 0.00 0.00
Maximum of Months 2081.42 1465.98 1184.71 496.54 688.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2257.42 2098.24 1984.69 1383.72 600.97 0.00 0.00
February 2284.50 1834.73 1852.38 1241.70 610.68 0.00 0.00
March 2214.95 1305.35 1665.92 868.18 797.74 0.00 0.00
April 1846.86 1105.52 1247.66 406.14 841.52 0.00 0.00
May 1575.28 747.29 1008.06 117.16 890.89 0.00 0.00
June 1751.43 479.64 932.06 51.87 880.19 0.00 0.00
July 1862.64 340.66 942.29 70.26 872.03 0.00 0.00
August 2266.83 291.41 1125.03 210.16 914.87 0.00 0.00
September 2108.75 623.11 1237.25 460.19 777.06 0.00 0.00
October 2637.18 1191.87 1793.66 1161.94 631.73 0.00 0.00
November 2561.35 1515.81 1929.66 1280.49 649.17 0.00 0.00
December 2375.65 1767.50 1956.35 1376.31 580.04 0.00 0.00
               
Annual Sum or Average 2144.95 1104.40 1471.29 716.57 754.72 0.00 0.00
Minimum of Months 1575.28 291.41 932.06 51.87 580.04 0.00 0.00
Maximum of Months 2637.18 2098.24 1984.69 1383.72 914.87 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 441.67 1567.54 558.06 258.87 299.19 0.00 0.00
February 652.61 1340.14 640.65 299.54 341.11 0.00 0.00
March 1153.99 904.13 944.28 456.30 487.98 0.00 0.00
April 1491.34 761.20 1062.30 486.10 576.20 0.00 0.00
May 1651.83 524.02 1067.64 404.49 663.16 0.00 0.00
June 1973.16 348.98 1122.77 431.92 690.84 0.00 0.00
July 1931.23 252.03 1059.03 392.65 666.38 0.00 0.00
August 1913.26 220.16 1037.70 388.06 649.64 0.00 0.00
September 1351.05 425.82 845.44 352.16 493.28 0.00 0.00
October 1021.39 830.03 753.19 390.99 362.20 0.00 0.00
November 678.83 1080.69 601.10 269.80 331.29 0.00 0.00
December 424.63 1310.90 495.90 216.91 278.99 0.00 0.00
               
Annual Sum or Average 1226.80 794.24 850.07 362.58 487.49 0.00 0.00
Minimum of Months 424.63 220.16 495.90 216.91 278.99 0.00 0.00
Maximum of Months 1973.16 1567.54 1122.77 486.10 690.84 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 88323898.84 0.793401E+10 0.993936E+09 0.00 0.993936E+09 0.00 0.00
February 0.325978E+09 0.592028E+10 0.995068E+09 0.00 0.995068E+09 0.00 0.00
March 0.899707E+09 0.415527E+10 0.154670E+10 0.00 0.154670E+10 0.00 0.00
April 0.187970E+10 0.304211E+10 0.181053E+10 8030117.67 0.180250E+10 0.00 0.00
May 0.310703E+10 0.195316E+10 0.223754E+10 71409157.01 0.216613E+10 0.00 0.00
June 0.436665E+10 0.114220E+10 0.238307E+10 0.157337E+09 0.222574E+10 0.00 0.00
July 0.451884E+10 0.837572E+09 0.232338E+10 0.112940E+09 0.221044E+10 0.00 0.00
August 0.411571E+10 0.697254E+09 0.206627E+10 22508480.56 0.204376E+10 0.00 0.00
September 0.224223E+10 0.164166E+10 0.151152E+10 212777.26 0.151131E+10 0.00 0.00
October 0.940453E+09 0.378526E+10 0.118757E+10 0.00 0.118757E+10 0.00 0.00
November 0.375430E+09 0.511288E+10 0.102854E+10 0.00 0.102854E+10 0.00 0.00
December 71193953.03 0.688660E+10 0.918820E+09 0.00 0.918820E+09 0.00 0.00
               
Annual Sum or Average 0.229312E+11 0.431082E+11 0.190030E+11 0.372438E+09 0.186305E+11 0.00 0.00
Minimum of Months 71193953.03 0.697254E+09 0.918820E+09 0.00 0.918820E+09 0.00 0.00
Maximum of Months 0.451884E+10 0.793401E+10 0.238307E+10 0.157337E+09 0.222574E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.911816E+09 0.471457E+10 0.145523E+10 0.656381E+09 0.798846E+09 0.00 0.00
February 0.150848E+10 0.349749E+10 0.165704E+10 0.890317E+09 0.766726E+09 0.00 0.00
March 0.252564E+10 0.246253E+10 0.230812E+10 0.105072E+10 0.125740E+10 0.00 0.00
April 0.370311E+10 0.183245E+10 0.270108E+10 0.123162E+10 0.146946E+10 0.00 0.00
May 0.471453E+10 0.127345E+10 0.306485E+10 0.129608E+10 0.176877E+10 0.00 0.00
June 0.543270E+10 0.741870E+09 0.307079E+10 0.128704E+10 0.178375E+10 0.00 0.00
July 0.567234E+10 0.528568E+09 0.309395E+10 0.130074E+10 0.179321E+10 0.00 0.00
August 0.528847E+10 0.415562E+09 0.282994E+10 0.112274E+10 0.170720E+10 0.00 0.00
September 0.360493E+10 0.103987E+10 0.225080E+10 0.997270E+09 0.125353E+10 0.00 0.00
October 0.248616E+10 0.227611E+10 0.198413E+10 0.103239E+10 0.951737E+09 0.00 0.00
November 0.139039E+10 0.297485E+10 0.153515E+10 0.695112E+09 0.840042E+09 0.00 0.00
December 0.911419E+09 0.396775E+10 0.137406E+10 0.626351E+09 0.747712E+09 0.00 0.00
               
Annual Sum or Average 0.381500E+11 0.257251E+11 0.273251E+11 0.121868E+11 0.151384E+11 0.00 0.00
Minimum of Months 0.911419E+09 0.415562E+09 0.137406E+10 0.626351E+09 0.747712E+09 0.00 0.00
Maximum of Months 0.567234E+10 0.471457E+10 0.309395E+10 0.130074E+10 0.179321E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.587192E+10 0.639622E+10 0.531563E+10 0.370603E+10 0.160960E+10 0.00 0.00
February 0.542523E+10 0.502842E+10 0.448114E+10 0.300382E+10 0.147732E+10 0.00 0.00
March 0.589250E+10 0.389433E+10 0.446186E+10 0.232525E+10 0.213662E+10 0.00 0.00
April 0.477548E+10 0.307842E+10 0.323385E+10 0.105268E+10 0.218117E+10 0.00 0.00
May 0.425976E+10 0.207014E+10 0.269992E+10 0.313801E+09 0.238612E+10 0.00 0.00
June 0.458138E+10 0.123112E+10 0.241584E+10 0.134430E+09 0.228141E+10 0.00 0.00
July 0.503448E+10 0.883960E+09 0.252378E+10 0.188185E+09 0.233559E+10 0.00 0.00
August 0.612109E+10 0.747405E+09 0.301320E+10 0.562872E+09 0.245033E+10 0.00 0.00
September 0.551259E+10 0.167406E+10 0.320688E+10 0.119278E+10 0.201409E+10 0.00 0.00
October 0.706115E+10 0.353865E+10 0.480401E+10 0.311203E+10 0.169198E+10 0.00 0.00
November 0.651534E+10 0.448365E+10 0.500153E+10 0.331892E+10 0.168261E+10 0.00 0.00
December 0.616419E+10 0.563745E+10 0.523974E+10 0.368619E+10 0.155355E+10 0.00 0.00
               
Annual Sum or Average 0.672151E+11 0.386638E+11 0.463974E+11 0.225970E+11 0.238004E+11 0.00 0.00
Minimum of Months 0.425976E+10 0.747405E+09 0.241584E+10 0.134430E+09 0.147732E+10 0.00 0.00
Maximum of Months 0.706115E+10 0.639622E+10 0.531563E+10 0.370603E+10 0.245033E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.104906E+10 0.513913E+10 0.149472E+10 0.693356E+09 0.801364E+09 0.00 0.00
February 0.144818E+10 0.405348E+10 0.154987E+10 0.724658E+09 0.825212E+09 0.00 0.00
March 0.295248E+10 0.305103E+10 0.252918E+10 0.122216E+10 0.130702E+10 0.00 0.00
April 0.374619E+10 0.236295E+10 0.275350E+10 0.125999E+10 0.149351E+10 0.00 0.00
May 0.442238E+10 0.152460E+10 0.285959E+10 0.108339E+10 0.177621E+10 0.00 0.00
June 0.511029E+10 0.980961E+09 0.291023E+10 0.111955E+10 0.179068E+10 0.00 0.00
July 0.512871E+10 0.768662E+09 0.283651E+10 0.105168E+10 0.178483E+10 0.00 0.00
August 0.505358E+10 0.722337E+09 0.277938E+10 0.103938E+10 0.174000E+10 0.00 0.00
September 0.348027E+10 0.124336E+10 0.219139E+10 0.912808E+09 0.127858E+10 0.00 0.00
October 0.263268E+10 0.277061E+10 0.201734E+10 0.104722E+10 0.970119E+09 0.00 0.00
November 0.156768E+10 0.367077E+10 0.155805E+10 0.699332E+09 0.858716E+09 0.00 0.00
December 0.962706E+09 0.490042E+10 0.132823E+10 0.580967E+09 0.747258E+09 0.00 0.00
               
Annual Sum or Average 0.375542E+11 0.311883E+11 0.268080E+11 0.114345E+11 0.153735E+11 0.00 0.00
Minimum of Months 0.962706E+09 0.722337E+09 0.132823E+10 0.580967E+09 0.747258E+09 0.00 0.00
Maximum of Months 0.512871E+10 0.513913E+10 0.291023E+10 0.125999E+10 0.179068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.136165E+09 0.701267E+10 0.993954E+09 0.00 0.993954E+09 0.00 0.00
February 0.410633E+09 0.522229E+10 0.995084E+09 0.00 0.995084E+09 0.00 0.00
March 0.101518E+10 0.370917E+10 0.154673E+10 0.00 0.154673E+10 0.00 0.00
April 0.196525E+10 0.283929E+10 0.181056E+10 8030357.15 0.180253E+10 0.00 0.00
May 0.313165E+10 0.188631E+10 0.223758E+10 71411286.64 0.216617E+10 0.00 0.00
June 0.438967E+10 0.113689E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00
July 0.455316E+10 0.836943E+09 0.232342E+10 0.112943E+09 0.221048E+10 0.00 0.00
August 0.416955E+10 0.686636E+09 0.206630E+10 22509151.83 0.204380E+10 0.00 0.00
September 0.227694E+10 0.155685E+10 0.151155E+10 212783.61 0.151133E+10 0.00 0.00
October 0.103781E+10 0.338203E+10 0.118759E+10 0.00 0.118759E+10 0.00 0.00
November 0.506258E+09 0.446807E+10 0.102856E+10 0.00 0.102856E+10 0.00 0.00
December 0.135211E+09 0.577582E+10 0.918837E+09 0.00 0.918837E+09 0.00 0.00
               
Annual Sum or Average 0.237275E+11 0.385130E+11 0.190033E+11 0.372449E+09 0.186308E+11 0.00 0.00
Minimum of Months 0.135211E+09 0.686636E+09 0.918837E+09 0.00 0.918837E+09 0.00 0.00
Maximum of Months 0.455316E+10 0.701267E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.986902E+09 0.420163E+10 0.145522E+10 0.656378E+09 0.798842E+09 0.00 0.00
February 0.156688E+10 0.316413E+10 0.165704E+10 0.890313E+09 0.766723E+09 0.00 0.00
March 0.254673E+10 0.231221E+10 0.230811E+10 0.105072E+10 0.125739E+10 0.00 0.00
April 0.368112E+10 0.181149E+10 0.270106E+10 0.123161E+10 0.146945E+10 0.00 0.00
May 0.467364E+10 0.126381E+10 0.306484E+10 0.129607E+10 0.176876E+10 0.00 0.00
June 0.539010E+10 0.776433E+09 0.307078E+10 0.128704E+10 0.178374E+10 0.00 0.00
July 0.562631E+10 0.576494E+09 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00
August 0.524723E+10 0.473607E+09 0.282993E+10 0.112273E+10 0.170720E+10 0.00 0.00
September 0.358807E+10 0.102128E+10 0.225079E+10 0.997266E+09 0.125352E+10 0.00 0.00
October 0.250680E+10 0.211787E+10 0.198412E+10 0.103239E+10 0.951733E+09 0.00 0.00
November 0.146868E+10 0.270540E+10 0.153515E+10 0.695109E+09 0.840039E+09 0.00 0.00
December 0.995331E+09 0.345673E+10 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
               
Annual Sum or Average 0.382778E+11 0.238811E+11 0.273250E+11 0.121867E+11 0.151383E+11 0.00 0.00
Minimum of Months 0.986902E+09 0.473607E+09 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
Maximum of Months 0.562631E+10 0.420163E+10 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.589880E+10 0.605891E+10 0.531579E+10 0.370615E+10 0.160964E+10 0.00 0.00
February 0.543648E+10 0.475183E+10 0.448128E+10 0.300392E+10 0.147735E+10 0.00 0.00
March 0.586330E+10 0.373816E+10 0.446199E+10 0.232533E+10 0.213666E+10 0.00 0.00
April 0.476722E+10 0.298957E+10 0.323393E+10 0.105271E+10 0.218122E+10 0.00 0.00
May 0.425103E+10 0.202782E+10 0.269998E+10 0.313811E+09 0.238617E+10 0.00 0.00
June 0.459740E+10 0.122457E+10 0.241589E+10 0.134435E+09 0.228145E+10 0.00 0.00
July 0.505931E+10 0.884934E+09 0.252383E+10 0.188191E+09 0.233564E+10 0.00 0.00
August 0.614087E+10 0.748333E+09 0.301327E+10 0.562890E+09 0.245038E+10 0.00 0.00
September 0.549083E+10 0.164329E+10 0.320696E+10 0.119282E+10 0.201414E+10 0.00 0.00
October 0.702309E+10 0.340897E+10 0.480415E+10 0.311213E+10 0.169202E+10 0.00 0.00
November 0.651101E+10 0.428618E+10 0.500168E+10 0.331903E+10 0.168265E+10 0.00 0.00
December 0.620703E+10 0.522896E+10 0.523990E+10 0.368631E+10 0.155359E+10 0.00 0.00
               
Annual Sum or Average 0.672464E+11 0.369915E+11 0.463986E+11 0.225977E+11 0.238009E+11 0.00 0.00
Minimum of Months 0.425103E+10 0.748333E+09 0.241589E+10 0.134435E+09 0.147735E+10 0.00 0.00
Maximum of Months 0.702309E+10 0.605891E+10 0.531579E+10 0.370615E+10 0.245038E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.113852E+10 0.448353E+10 0.149471E+10 0.693353E+09 0.801361E+09 0.00 0.00
February 0.154976E+10 0.343816E+10 0.154986E+10 0.724655E+09 0.825209E+09 0.00 0.00
March 0.305574E+10 0.258817E+10 0.252917E+10 0.122215E+10 0.130702E+10 0.00 0.00
April 0.385591E+10 0.205333E+10 0.275349E+10 0.125998E+10 0.149350E+10 0.00 0.00
May 0.444684E+10 0.142093E+10 0.285958E+10 0.108338E+10 0.177620E+10 0.00 0.00
June 0.515690E+10 0.895899E+09 0.291021E+10 0.111955E+10 0.179067E+10 0.00 0.00
July 0.521675E+10 0.661969E+09 0.283650E+10 0.105168E+10 0.178482E+10 0.00 0.00
August 0.516825E+10 0.573189E+09 0.277936E+10 0.103937E+10 0.173999E+10 0.00 0.00
September 0.351561E+10 0.112695E+10 0.219138E+10 0.912804E+09 0.127857E+10 0.00 0.00
October 0.270966E+10 0.237861E+10 0.201733E+10 0.104722E+10 0.970115E+09 0.00 0.00
November 0.169951E+10 0.304348E+10 0.155804E+10 0.699329E+09 0.858712E+09 0.00 0.00
December 0.109325E+10 0.382662E+10 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
               
Annual Sum or Average 0.386067E+11 0.264908E+11 0.268079E+11 0.114344E+11 0.153734E+11 0.00 0.00
Minimum of Months 0.109325E+10 0.573189E+09 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
Maximum of Months 0.521675E+10 0.448353E+10 0.291021E+10 0.125998E+10 0.179067E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.169548E+09 0.657485E+10 0.993954E+09 0.00 0.993954E+09 0.00 0.00
February 0.452077E+09 0.489401E+10 0.995084E+09 0.00 0.995084E+09 0.00 0.00
March 0.109448E+10 0.341335E+10 0.154673E+10 0.00 0.154673E+10 0.00 0.00
April 0.200533E+10 0.269910E+10 0.181056E+10 8030357.15 0.180253E+10 0.00 0.00
May 0.310893E+10 0.185795E+10 0.223758E+10 71411286.64 0.216617E+10 0.00 0.00
June 0.433230E+10 0.115618E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00
July 0.448193E+10 0.863853E+09 0.232342E+10 0.112943E+09 0.221048E+10 0.00 0.00
August 0.410281E+10 0.715939E+09 0.206630E+10 22509151.83 0.204380E+10 0.00 0.00
September 0.226478E+10 0.151474E+10 0.151155E+10 212783.61 0.151133E+10 0.00 0.00
October 0.110221E+10 0.310242E+10 0.118759E+10 0.00 0.118759E+10 0.00 0.00
November 0.608454E+09 0.403347E+10 0.102856E+10 0.00 0.102856E+10 0.00 0.00
December 0.178099E+09 0.523281E+10 0.918837E+09 0.00 0.918837E+09 0.00 0.00
               
Annual Sum or Average 0.239010E+11 0.360587E+11 0.190033E+11 0.372449E+09 0.186308E+11 0.00 0.00
Minimum of Months 0.169548E+09 0.715939E+09 0.918837E+09 0.00 0.918837E+09 0.00 0.00
Maximum of Months 0.448193E+10 0.657485E+10 0.238312E+10 0.157342E+09 0.222578E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.104453E+10 0.392649E+10 0.145522E+10 0.656378E+09 0.798842E+09 0.00 0.00
February 0.161692E+10 0.296671E+10 0.165704E+10 0.890313E+09 0.766723E+09 0.00 0.00
March 0.260762E+10 0.215756E+10 0.230811E+10 0.105072E+10 0.125739E+10 0.00 0.00
April 0.369821E+10 0.174536E+10 0.270106E+10 0.123161E+10 0.146945E+10 0.00 0.00
May 0.464933E+10 0.125667E+10 0.306484E+10 0.129607E+10 0.176876E+10 0.00 0.00
June 0.534634E+10 0.793146E+09 0.307078E+10 0.128704E+10 0.178374E+10 0.00 0.00
July 0.557488E+10 0.595180E+09 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00
August 0.519782E+10 0.493931E+09 0.282993E+10 0.112273E+10 0.170720E+10 0.00 0.00
September 0.357339E+10 0.100339E+10 0.225079E+10 0.997266E+09 0.125352E+10 0.00 0.00
October 0.255105E+10 0.197565E+10 0.198412E+10 0.103239E+10 0.951733E+09 0.00 0.00
November 0.156888E+10 0.246026E+10 0.153515E+10 0.695109E+09 0.840039E+09 0.00 0.00
December 0.106691E+10 0.312714E+10 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
               
Annual Sum or Average 0.384959E+11 0.225015E+11 0.273250E+11 0.121867E+11 0.151383E+11 0.00 0.00
Minimum of Months 0.104453E+10 0.493931E+09 0.137406E+10 0.626349E+09 0.747709E+09 0.00 0.00
Maximum of Months 0.557488E+10 0.392649E+10 0.309394E+10 0.130073E+10 0.179320E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.604629E+10 0.561992E+10 0.531579E+10 0.370615E+10 0.160964E+10 0.00 0.00
February 0.552667E+10 0.443857E+10 0.448128E+10 0.300392E+10 0.147735E+10 0.00 0.00
March 0.593252E+10 0.349625E+10 0.446199E+10 0.232533E+10 0.213666E+10 0.00 0.00
April 0.478707E+10 0.286550E+10 0.323393E+10 0.105271E+10 0.218122E+10 0.00 0.00
May 0.421923E+10 0.200155E+10 0.269998E+10 0.313811E+09 0.238617E+10 0.00 0.00
June 0.453970E+10 0.124324E+10 0.241589E+10 0.134435E+09 0.228145E+10 0.00 0.00
July 0.498889E+10 0.912433E+09 0.252383E+10 0.188191E+09 0.233564E+10 0.00 0.00
August 0.607148E+10 0.780521E+09 0.301327E+10 0.562890E+09 0.245038E+10 0.00 0.00
September 0.546587E+10 0.161509E+10 0.320696E+10 0.119282E+10 0.201414E+10 0.00 0.00
October 0.706342E+10 0.319230E+10 0.480415E+10 0.311213E+10 0.169202E+10 0.00 0.00
November 0.663902E+10 0.392899E+10 0.500168E+10 0.331903E+10 0.168265E+10 0.00 0.00
December 0.636294E+10 0.473408E+10 0.523990E+10 0.368631E+10 0.155359E+10 0.00 0.00
               
Annual Sum or Average 0.676431E+11 0.348285E+11 0.463986E+11 0.225977E+11 0.238009E+11 0.00 0.00
Minimum of Months 0.421923E+10 0.780521E+09 0.241589E+10 0.134435E+09 0.147735E+10 0.00 0.00
Maximum of Months 0.706342E+10 0.561992E+10 0.531579E+10 0.370615E+10 0.245038E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.118296E+10 0.419849E+10 0.149471E+10 0.693353E+09 0.801361E+09 0.00 0.00
February 0.157878E+10 0.324206E+10 0.154986E+10 0.724655E+09 0.825209E+09 0.00 0.00
March 0.309086E+10 0.242161E+10 0.252917E+10 0.122215E+10 0.130702E+10 0.00 0.00
April 0.386556E+10 0.197304E+10 0.275349E+10 0.125998E+10 0.149350E+10 0.00 0.00
May 0.442426E+10 0.140354E+10 0.285958E+10 0.108338E+10 0.177620E+10 0.00 0.00
June 0.511444E+10 0.904551E+09 0.291021E+10 0.111955E+10 0.179067E+10 0.00 0.00
July 0.517260E+10 0.675045E+09 0.283650E+10 0.105168E+10 0.178482E+10 0.00 0.00
August 0.512449E+10 0.589668E+09 0.277936E+10 0.103937E+10 0.173999E+10 0.00 0.00
September 0.350192E+10 0.110372E+10 0.219138E+10 0.912804E+09 0.127857E+10 0.00 0.00
October 0.273569E+10 0.222316E+10 0.201733E+10 0.104722E+10 0.970115E+09 0.00 0.00
November 0.175953E+10 0.280114E+10 0.155804E+10 0.699329E+09 0.858712E+09 0.00 0.00
December 0.113733E+10 0.351110E+10 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
               
Annual Sum or Average 0.386884E+11 0.250471E+11 0.268079E+11 0.114344E+11 0.153734E+11 0.00 0.00
Minimum of Months 0.113733E+10 0.589668E+09 0.132822E+10 0.580965E+09 0.747255E+09 0.00 0.00
Maximum of Months 0.517260E+10 0.419849E+10 0.291021E+10 0.125998E+10 0.179067E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 3.96 1.39 -3.0 4.56 -7.8 48.74 150.20 0.00
February 7.94 4.18 -1.3 5.19 -4.0 51.84 169.20 0.00
March 13.76 8.97 3.80 4.89 2.25 76.95 193.22 0.00
April 17.21 12.54 8.82 3.95 6.45 95.37 211.82 0.00
May 20.84 16.44 13.69 3.50 11.46 117.34 200.00 0.00
June 24.80 19.35 16.45 3.85 15.08 121.81 213.08 0.00
July 26.06 21.68 19.85 3.24 17.64 119.92 194.46 0.00
August 26.55 22.42 20.72 3.39 18.21 115.12 179.15 0.00
September 22.53 18.74 16.82 3.06 13.44 83.74 156.58 0.02
October 16.03 13.02 10.77 4.05 5.85 53.01 190.38 0.00
November 11.94 8.22 4.17 4.16 0.30 52.20 150.38 0.00
December 7.70 4.64 0.26 4.69 -4.1 44.81 142.03 0.00
                 
Annual Sum or Average 16.65 12.68 9.31 4.04 6.29 81.91 179.25 0.00
Minimum of Months 3.96 1.39 -3.0 3.06 -7.8 44.81 142.03 0.00
Maximum of Months 26.55 22.42 20.72 5.19 18.21 121.81 213.08 0.02



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.10 31-JAN-14:00 12.97 6.70 5.70 12.22 200.50 90.50
February 25.00 26-FEB-14:00 12.75 1.70 4.10 8.15 91.50 816.00
March 27.80 30-MAR-13:00 17.87 12.20 5.70 16.30 231.50 710.50
April 28.90 17-APR-14:20 16.56 8.13 2.03 13.35 125.83 887.67
May 30.60 19-MAY-13:00 18.49 11.70 4.60 15.76 140.00 875.50
June 34.40 06-JUN-14:00 22.39 17.20 8.20 22.13 251.00 561.00
July 36.70 08-JUL-14:00 23.91 18.90 2.10 24.66 274.00 567.00
August 35.00 01-AUG-14:00 23.84 19.40 2.60 26.15 306.00 508.00
September 31.70 07-SEP-15:09 23.05 19.60 4.02 22.55 218.67 591.33
October 30.00 10-OCT-15:00 20.56 16.10 3.60 17.57 97.00 561.00
November 24.40 05-NOV-15:00 17.95 14.40 2.10 14.10 117.50 361.50
December 22.80 12-DEC-14:20 16.78 13.33 5.20 13.35 144.17 433.83
                 
Annual Sum or Average                
Minimum of Months 21.10   12.75 1.70 2.03 8.15 91.50 90.50
Maximum of Months 36.70   23.91 19.60 8.20 26.15 306.00 887.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -6.7 14-JAN-06:10 -7.8 -10.6 4.95 -24.7 0.00 0.00
February -12.8 12-FEB-06:00 -13.8 -18.3 7.20 -30.1 0.00 0.00
March 1.10 19-MAR-06:00 -1.5 -6.1 0.00 -16.2 17.00 290.50
April 0.00 06-APR-04:00 -1.1 -2.8 3.10 -16.5 0.00 0.00
May 7.80 11-MAY-05:00 5.45 2.80 4.10 -7.8 21.50 204.50
June 11.10 10-JUN-04:00 8.73 6.70 0.00 -2.5 0.00 0.00
July 17.20 28-JUL-22:00 16.88 16.70 4.10 14.28 0.00 0.00
August 18.30 25-AUG-05:00 17.20 16.70 3.60 5.13 0.00 0.00
September 11.70 29-SEP-03:00 11.07 10.60 2.60 -2.3 0.00 0.00
October 2.20 26-OCT-04:00 1.95 1.70 3.10 -13.4 0.00 0.00
November -3.3 22-NOV-05:00 -4.0 -5.6 5.20 -20.2 0.00 0.00
December -5.6 18-DEC-07:00 -7.3 -11.7 2.60 -22.7 17.00 320.50
                 
Annual Sum or Average                
Minimum of Months -12.8   -13.8 -18.3 0.00 -30.1 0.00 0.00
Maximum of Months 18.30   17.20 16.70 7.20 14.28 21.50 320.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 16.51 19-JAN-21:00 18.30 15.60 8.80 15.21 0.00 0.00
February 15.81 18-FEB-15:00 17.20 15.00 5.20 13.91 73.00 1.00
March 18.16 30-MAR-12:30 25.85 13.85 5.45 15.39 323.00 600.00
April 20.01 04-APR-13:00 25.00 17.80 9.30 18.64 307.00 197.50
May 22.34 30-MAY-17:00 27.80 20.00 4.10 21.96 97.50 79.50
June 24.32 23-JUN-11:39 31.13 21.87 4.83 22.98 338.17 565.17
July 25.06 07-JUL-11:00 33.30 22.20 3.60 20.75 116.50 900.00
August 25.13 19-AUG-16:00 30.00 23.30 3.10 23.66 197.00 136.50
September 24.10 09-SEP-10:00 30.60 21.70 2.60 21.27 236.00 482.00
October 23.20 18-OCT-15:00 25.60 22.20 5.70 23.82 159.00 2.00
November 18.88 19-NOV-14:00 24.40 16.10 8.20 13.91 143.00 384.50
December 17.57 13-DEC-10:00 19.40 16.70 4.60 14.47 227.50 77.00
                 
Annual Sum or Average                
Minimum of Months 15.81   17.20 13.85 2.60 13.91 0.00 0.00
Maximum of Months 25.13   33.30 23.30 9.30 23.82 338.17 900.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.60 19-JAN-17:00 17.20 16.13 6.70 14.10 0.00 0.00
February 15.00 18-FEB-16:19 17.20 15.81 5.53 13.91 50.33 1.00
March 16.10 31-MAR-10:00 21.70 18.06 13.90 18.64 268.00 8.00
April 17.80 04-APR-09:20 20.77 18.74 7.53 16.79 242.00 111.50
May 20.60 30-MAY-19:00 25.00 21.79 2.60 12.41 0.00 0.00
June 22.80 18-JUN-16:00 28.30 24.23 0.00 24.66 140.50 115.50
July 23.30 26-JUL-09:00 26.10 24.10 3.60 24.66 338.00 251.50
August 23.90 08-AUG-19:00 26.10 24.51 1.50 24.83 0.00 0.00
September 23.30 16-SEP-16:00 25.60 23.89 2.10 22.13 108.00 57.50
October 22.20 18-OCT-14:00 25.00 23.04 4.60 23.32 234.50 2.00
November 17.20 04-NOV-13:00 17.80 17.48 3.60 15.02 276.50 2.50
December 16.70 13-DEC-16:19 17.03 16.82 2.93 14.10 54.00 4.50
                 
Annual Sum or Average                
Minimum of Months 15.00   17.03 15.81 0.00 12.41 0.00 0.00
Maximum of Months 23.90   28.30 24.51 13.90 24.83 338.00 251.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 13.74 22.89 0.00
February 18.00 13.00 16.00 13.65 27.55 0.00
March 18.00 13.00 16.00 15.17 38.46 0.00
April 18.00 13.00 16.00 17.98 47.59 0.00
May 18.00 13.00 16.00 21.32 52.44 0.00
June 18.00 13.00 16.00 24.28 55.84 0.00
July 18.00 13.00 16.00 26.07 52.33 0.00
August 18.00 13.00 16.00 26.20 48.31 0.00
September 18.00 13.00 16.00 24.63 36.35 0.00
October 18.00 13.00 16.00 21.78 31.91 0.00
November 18.00 13.00 16.00 18.45 24.33 0.00
December 18.00 13.00 16.00 15.51 20.76 0.00
             
Annual Sum or Average 18.00 13.00 16.00 19.94 38.29 0.00
Minimum of Months 18.00 13.00 16.00 13.65 20.76 0.00
Maximum of Months 18.00 13.00 16.00 26.20 55.84 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.370541E+11 -0.360223E+11 0.00 0.00 744.00 0.00 -0.103172E+10 58.97 0.00 0.00
February 0.337333E+11 -0.328032E+11 0.00 0.00 672.00 0.00 -930185277.3 58.98 0.00 0.00
March 0.383097E+11 -0.372805E+11 0.00 0.00 744.00 0.00 -0.102922E+10 58.97 0.00 0.00
April 0.326417E+11 -0.316481E+11 0.00 0.00 720.00 0.00 -993660105.4 58.97 0.00 0.00
May 0.321107E+11 -0.310845E+11 0.00 0.00 744.00 0.00 -0.102626E+10 58.98 0.00 0.00
June 0.293474E+11 -0.283548E+11 0.00 0.00 720.00 0.00 -992690313.6 58.97 0.00 0.00
July 0.265875E+11 -0.255676E+11 0.00 0.00 744.00 0.00 -0.101992E+10 58.97 0.00 0.00
August 0.289273E+11 -0.279036E+11 0.00 0.00 744.00 0.00 -0.102374E+10 58.98 0.00 0.00
September 0.275331E+11 -0.265452E+11 0.00 0.00 720.00 0.00 -987957379.6 58.97 0.00 0.00
October 0.306588E+11 -0.296390E+11 0.00 0.00 744.00 0.00 -0.101974E+10 58.97 0.00 0.00
November 0.326510E+11 -0.316638E+11 0.00 0.00 720.00 0.00 -987182909.6 58.97 0.00 0.00
December 0.348021E+11 -0.337799E+11 0.00 0.00 744.00 0.00 -0.102220E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.384357E+12 -0.372292E+12 0.00 0.00 8760.00 0.00 -0.120645E+11 58.97 0.00 0.00
Minimum of Months 0.265875E+11 -0.372805E+11 0.00 0.00 672.00 0.00 -0.103172E+10 58.97 0.00 0.00
Maximum of Months 0.383097E+11 -0.255676E+11 0.00 0.00 744.00 0.00 -930185277.3 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.63 0.61 01-JAN-08:50 5135.26 32.94 258.50 264.50 1312.65 25.39 169.67 238.83
February 263.00 0.64 0.61 01-FEB-10:09 6070.35 32.98 229.00 235.83 860.67 20.49 86.33 208.17
March 351.67 0.64 0.61 01-MAR-08:20 1281.08 16.72 6.67 303.17 727.60 19.52 81.67 261.67
April 369.33 0.64 0.61 01-APR-07:00 1065.79 16.18 0.00 307.83 595.38 19.06 43.33 256.83
May 407.00 0.64 0.61 01-MAY-07:10 969.25 16.28 0.00 340.33 533.72 19.18 14.33 284.17
June 411.67 0.64 0.61 01-JUN-06:40 900.25 15.97 0.00 342.33 502.31 18.89 5.67 280.67
July 411.00 0.64 0.61 01-JUL-06:00 949.53 16.18 0.00 343.83 522.58 19.06 19.17 282.67
August 390.50 0.64 0.61 01-AUG-06:00 1160.38 16.90 0.00 337.17 623.04 19.77 73.67 287.50
September 298.50 0.64 0.61 01-SEP-07:10 1232.52 17.09 6.50 294.50 674.77 19.66 68.83 239.33
October 293.50 0.63 0.61 01-OCT-07:40 2333.42 22.85 116.50 283.83 793.20 18.88 57.83 232.67
November 299.00 0.64 0.61 01-NOV-07:00 5037.34 32.73 268.00 263.67 888.30 22.15 116.17 233.83
December 285.17 0.63 0.61 01-DEC-07:00 4771.83 32.10 248.33 255.67 1256.60 26.37 168.67 233.00
                         
Annual Sum or Average 4071.00 0.64     2324.11 21.44 1133.50 3572.67 742.80 20.48 905.33 3039.33
Minimum of Months 263.00 0.63 0.61   900.25 15.97 0.00 235.83 502.31 18.88 5.67 208.17
Maximum of Months 411.67 0.64 0.61   6070.35 32.98 268.00 343.83 1312.65 26.37 169.67 287.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-08:50 1150.59 16.61 66.00 215.50 567.26 15.83 39.33 138.17
February 263.00 0.66 0.61 01-FEB-10:09 1547.56 16.26 58.33 198.17 769.54 15.38 36.50 144.50
March 351.67 0.64 0.61 01-MAR-08:09 1758.97 15.99 74.00 286.00 688.23 13.18 1.17 231.50
April 369.33 0.64 0.61 01-APR-07:49 1720.30 11.66 0.00 305.83 929.61 13.00 0.00 255.33
May 407.00 0.64 0.61 01-MAY-06:49 1945.92 12.24 0.00 348.00 789.72 13.41 0.00 292.17
June 411.67 0.64 0.61 01-JUN-06:19 2057.22 12.20 0.00 350.83 800.40 13.33 0.00 298.33
July 411.00 0.64 0.61 01-JUL-05:00 1946.81 12.35 0.00 354.50 809.76 13.50 0.00 303.33
August 390.50 0.64 0.61 01-AUG-06:40 1800.03 12.67 0.00 335.17 945.55 13.89 0.00 285.33
September 298.50 0.65 0.61 01-SEP-06:00 1702.25 12.18 3.83 286.33 854.92 13.53 2.83 223.50
October 293.50 0.65 0.61 01-OCT-07:30 2100.80 17.88 88.00 240.50 728.49 15.33 39.83 172.50
November 299.00 0.66 0.61 01-NOV-07:00 1350.97 16.88 75.67 224.67 746.19 17.70 64.67 160.83
December 285.17 0.65 0.61 01-DEC-07:00 1182.96 17.30 70.33 212.67 589.97 16.47 44.00 140.83
                         
Annual Sum or Average 4071.00 0.64     1720.29 14.23 436.17 3358.17 777.69 14.38 228.33 2646.33
Minimum of Months 263.00 0.64 0.61   1150.59 11.66 0.00 198.17 567.26 13.00 0.00 138.17
Maximum of Months 411.67 0.66 0.61   2100.80 17.88 88.00 354.50 945.55 17.70 64.67 303.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.67 0.61 01-JAN-09:09 394.64 0.00 0.00 154.67 238.41 0.00 0.00 22.67
February 263.00 0.68 0.61 01-FEB-10:20 418.16 0.00 0.00 144.50 260.32 0.00 0.00 56.83
March 351.67 0.65 0.61 01-MAR-08:39 534.33 0.00 0.00 272.50 325.77 0.00 0.00 147.33
April 369.33 0.64 0.61 01-APR-07:00 640.11 0.00 0.00 308.33 382.25 0.00 0.00 222.33
May 407.00 0.63 0.61 01-MAY-06:00 792.30 0.00 0.00 365.33 467.79 0.00 0.00 317.83
June 411.67 0.63 0.61 01-JUN-06:30 865.26 0.00 0.00 376.00 502.46 0.00 0.00 339.83
July 411.00 0.63 0.61 01-JUL-06:10 878.77 0.00 0.00 373.83 488.83 0.00 0.00 328.17
August 390.50 0.63 0.61 01-AUG-06:49 781.93 0.00 0.00 349.67 454.17 0.00 0.00 290.50
September 298.50 0.65 0.61 01-SEP-07:10 591.65 0.00 0.00 282.17 358.67 0.00 0.00 161.83
October 293.50 0.67 0.61 01-OCT-07:00 435.87 0.00 0.00 181.67 280.35 0.00 0.00 74.83
November 299.00 0.67 0.61 01-NOV-08:20 407.13 0.00 0.00 185.33 247.91 0.00 0.00 23.50
December 285.17 0.67 0.61 01-DEC-09:20 380.11 0.00 0.00 147.33 230.80 0.00 0.00 2.50
                         
Annual Sum or Average 4071.00 0.65     621.19 0.00 0.00 3141.33 368.04 0.00 0.00 1988.17
Minimum of Months 263.00 0.63 0.61   380.11 0.00 0.00 144.50 230.80 0.00 0.00 2.50
Maximum of Months 411.67 0.68 0.61   878.77 0.00 0.00 376.00 502.46 0.00 0.00 339.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-09:20 1355.63 16.91 68.50 217.17 781.20 17.81 60.00 147.50
February 263.00 0.66 0.61 01-FEB-10:20 1344.91 16.16 59.50 185.00 674.52 15.38 37.00 137.33
March 351.67 0.64 0.61 01-MAR-08:39 1775.01 14.62 47.33 288.67 948.45 13.25 0.00 230.83
April 369.33 0.64 0.61 01-APR-08:20 1860.99 11.76 0.00 307.83 1056.72 13.10 0.00 259.67
May 407.00 0.64 0.61 01-MAY-07:30 1954.43 12.31 0.00 345.83 778.65 13.55 1.33 294.33
June 411.67 0.64 0.61 01-JUN-06:00 2044.68 12.27 0.00 350.17 838.62 15.32 37.83 300.33
July 411.00 0.64 0.61 01-JUL-07:30 2030.64 12.34 0.00 349.17 818.61 15.02 27.83 297.00
August 390.50 0.64 0.61 01-AUG-07:30 1988.68 12.97 4.83 338.33 819.73 14.00 0.00 289.67
September 298.50 0.64 0.61 01-SEP-07:30 1741.64 15.11 49.67 285.50 917.00 13.58 0.00 218.00
October 293.50 0.65 0.61 01-OCT-08:20 1840.40 16.22 70.50 231.67 701.56 12.66 2.17 172.83
November 299.00 0.65 0.61 01-NOV-08:20 1313.70 17.02 79.50 226.00 652.50 16.30 51.67 162.00
December 285.17 0.65 0.61 01-DEC-09:20 1143.04 17.04 70.83 209.67 577.15 16.33 44.00 139.00
                         
Annual Sum or Average 4071.00 0.65     1740.71 14.26 450.67 3335.00 807.25 14.61 261.83 2648.50
Minimum of Months 263.00 0.64 0.61   1143.04 11.76 0.00 185.00 577.15 12.66 0.00 137.33
Maximum of Months 411.67 0.66 0.61   2044.68 17.04 79.50 350.17 1056.72 17.81 60.00 300.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.64 0.61 01-JAN-08:50 5045.08 30.47 233.00 259.83 1347.48 21.60 100.50 240.17
February 263.00 0.64 0.61 01-FEB-10:09 6053.42 32.50 227.50 234.00 895.79 15.72 25.83 208.67
March 351.67 0.64 0.61 01-MAR-08:20 1263.71 10.58 6.50 302.33 755.03 15.21 0.00 264.33
April 369.33 0.64 0.61 01-APR-07:00 1048.79 10.33 0.00 306.67 615.77 15.14 0.00 259.33
May 407.00 0.64 0.61 01-MAY-07:10 950.46 10.60 0.00 338.17 549.68 15.36 0.00 287.67
June 411.67 0.64 0.61 01-JUN-06:40 882.89 10.44 0.00 340.50 517.04 15.16 0.00 283.67
July 411.00 0.64 0.61 01-JUL-06:00 930.38 10.63 0.00 342.00 537.66 15.32 0.00 286.67
August 390.50 0.64 0.61 01-AUG-06:00 1135.99 11.29 0.00 335.17 641.03 15.98 0.00 290.33
September 298.50 0.64 0.61 01-SEP-07:10 1210.33 11.47 6.50 293.33 696.93 15.79 0.00 242.83
October 293.50 0.64 0.61 01-OCT-07:49 2321.95 18.72 115.00 281.33 832.05 14.36 2.00 236.00
November 299.00 0.64 0.61 01-NOV-07:00 5016.18 32.05 266.33 262.83 943.91 19.77 79.33 241.00
December 285.17 0.63 0.61 01-DEC-07:00 4747.47 31.25 241.33 254.67 1246.24 21.07 97.50 228.17
                         
Annual Sum or Average 4071.00 0.64     2299.92 17.13 1096.17 3550.83 765.89 16.51 305.17 3068.83
Minimum of Months 263.00 0.63 0.61   882.89 10.33 0.00 234.00 517.04 14.36 0.00 208.67
Maximum of Months 411.67 0.64 0.61   6053.42 32.50 266.33 342.00 1347.48 21.60 100.50 290.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-08:50 1009.75 12.28 45.00 213.33 582.50 13.79 40.00 144.33
February 263.00 0.66 0.61 01-FEB-10:09 1552.29 14.00 58.50 198.00 790.91 13.33 37.00 149.67
March 351.67 0.64 0.61 01-MAR-08:09 1763.32 13.61 74.33 284.83 709.62 10.68 1.17 236.83
April 369.33 0.64 0.61 01-APR-07:49 1718.65 8.18 0.00 305.50 953.59 10.53 0.00 259.67
May 407.00 0.64 0.61 01-MAY-06:49 1930.85 8.76 0.00 347.17 815.20 11.06 0.00 298.67
June 411.67 0.64 0.61 01-JUN-06:19 1949.25 8.80 0.00 349.50 825.67 11.08 0.00 301.83
July 411.00 0.64 0.61 01-JUL-05:00 1931.72 8.92 0.00 353.50 834.79 11.20 0.00 307.50
August 390.50 0.64 0.61 01-AUG-06:40 1784.64 9.29 0.00 334.33 968.44 11.51 0.00 288.83
September 298.50 0.65 0.61 01-SEP-06:00 1705.07 8.76 2.67 285.00 878.49 11.09 2.83 227.83
October 293.50 0.65 0.61 01-OCT-07:30 1933.03 13.74 67.33 241.00 751.26 13.31 40.00 177.67
November 299.00 0.66 0.61 01-NOV-07:00 1348.79 14.75 75.83 224.33 762.09 15.92 66.50 167.50
December 285.17 0.65 0.61 01-DEC-07:00 1169.58 14.79 67.33 211.50 605.57 14.40 44.33 145.50
                         
Annual Sum or Average 4071.00 0.65     1682.35 11.01 391.00 3348.00 799.63 12.13 231.83 2705.83
Minimum of Months 263.00 0.64 0.61   1009.75 8.18 0.00 198.00 582.50 10.53 0.00 144.33
Maximum of Months 411.67 0.66 0.61   1949.25 14.79 75.83 353.50 968.44 15.92 66.50 307.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.68 0.61 01-JAN-09:09 387.32 0.00 0.00 151.83 245.31 0.00 0.00 27.50
February 263.00 0.68 0.61 01-FEB-10:30 411.46 0.00 0.00 142.33 268.29 0.00 0.00 65.50
March 351.67 0.65 0.61 01-MAR-08:39 525.69 0.00 0.00 269.33 335.69 0.00 0.00 165.00
April 369.33 0.64 0.61 01-APR-07:00 630.18 0.00 0.00 307.00 394.14 0.00 0.00 229.67
May 407.00 0.63 0.61 01-MAY-06:00 778.83 0.00 0.00 364.17 481.55 0.00 0.00 323.33
June 411.67 0.63 0.61 01-JUN-06:30 850.86 0.00 0.00 375.33 524.92 0.00 0.00 349.83
July 411.00 0.63 0.61 01-JUL-06:10 863.87 0.00 0.00 372.67 502.95 0.00 0.00 331.50
August 390.50 0.63 0.61 01-AUG-06:49 764.99 0.00 0.00 346.17 467.03 0.00 0.00 296.17
September 298.50 0.65 0.61 01-SEP-07:10 581.54 0.00 0.00 280.17 369.13 0.00 0.00 170.17
October 293.50 0.67 0.61 01-OCT-08:09 429.84 0.00 0.00 181.33 289.21 0.00 0.00 81.67
November 299.00 0.67 0.61 01-NOV-08:20 399.32 0.00 0.00 181.50 254.89 0.00 0.00 33.17
December 285.17 0.68 0.61 01-DEC-09:20 372.42 0.00 0.00 144.00 237.17 0.00 0.00 8.33
                         
Annual Sum or Average 4071.00 0.65     610.36 0.00 0.00 3115.83 379.65 0.00 0.00 2081.83
Minimum of Months 263.00 0.63 0.61   372.42 0.00 0.00 142.33 237.17 0.00 0.00 8.33
Maximum of Months 411.67 0.68 0.61   863.87 0.00 0.00 375.33 524.92 0.00 0.00 349.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-09:20 1354.76 14.66 68.00 216.67 797.92 15.99 60.17 152.83
February 263.00 0.66 0.61 01-FEB-10:20 1186.53 11.63 41.17 185.00 694.20 13.39 37.00 140.00
March 351.67 0.64 0.61 01-MAR-08:39 1780.49 11.79 47.33 288.00 910.80 10.67 0.00 233.67
April 369.33 0.64 0.61 01-APR-08:20 1859.15 8.28 0.00 307.50 1080.68 10.65 0.00 264.17
May 407.00 0.64 0.61 01-MAY-07:30 1848.58 8.88 0.00 344.83 802.13 11.16 0.00 299.00
June 411.67 0.64 0.61 01-JUN-06:00 2031.51 8.90 0.00 349.67 842.29 11.17 0.00 301.17
July 411.00 0.64 0.61 01-JUL-07:30 2006.01 8.96 0.00 348.67 825.82 11.20 0.00 299.17
August 390.50 0.64 0.61 01-AUG-07:30 1896.20 9.65 4.83 337.33 842.74 11.63 0.00 294.50
September 298.50 0.65 0.61 01-SEP-07:30 1745.67 12.49 49.67 284.83 940.03 11.09 0.00 223.67
October 293.50 0.65 0.61 01-OCT-08:20 1844.44 13.93 70.50 232.17 723.30 10.12 2.17 179.33
November 299.00 0.66 0.61 01-NOV-08:20 1311.61 14.88 79.67 225.67 668.62 14.31 51.83 167.33
December 285.17 0.65 0.61 01-DEC-09:20 1141.42 14.88 70.83 209.50 592.21 14.27 44.50 142.67
                         
Annual Sum or Average 4071.00 0.65     1707.77 11.24 432.00 3329.83 819.78 11.98 195.67 2697.50
Minimum of Months 263.00 0.64 0.61   1141.42 8.28 0.00 185.00 592.21 10.12 0.00 140.00
Maximum of Months 411.67 0.66 0.61   2031.51 14.88 79.67 349.67 1080.68 15.99 60.17 301.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.64 0.61 01-JAN-08:50 5044.69 30.46 233.00 259.83 1348.41 21.59 100.50 240.17
February 263.00 0.64 0.61 01-FEB-10:09 6018.43 31.23 217.00 230.17 896.64 15.70 25.83 208.67
March 351.67 0.64 0.61 01-MAR-08:20 1264.30 10.53 6.33 302.33 755.88 15.19 0.00 264.33
April 369.33 0.64 0.61 01-APR-07:00 1049.35 10.29 0.00 306.67 616.47 15.12 0.00 259.67
May 407.00 0.64 0.61 01-MAY-07:10 950.94 10.56 0.00 338.17 550.31 15.34 0.00 287.83
June 411.67 0.64 0.61 01-JUN-06:40 883.29 10.40 0.00 340.50 517.61 15.14 0.00 284.00
July 411.00 0.64 0.61 01-JUL-06:00 930.84 10.59 0.00 342.00 538.26 15.30 0.00 287.00
August 390.50 0.64 0.61 01-AUG-06:00 1136.63 11.25 0.00 335.17 641.82 15.96 0.00 290.33
September 298.50 0.64 0.61 01-SEP-07:10 1210.97 11.43 6.50 293.33 697.76 15.78 0.00 242.83
October 293.50 0.64 0.61 01-OCT-07:49 2322.34 18.69 115.00 281.33 832.83 14.34 2.00 236.33
November 299.00 0.64 0.61 01-NOV-07:00 5016.03 32.04 266.33 262.83 944.86 19.76 79.33 241.00
December 285.17 0.63 0.61 01-DEC-07:00 4746.91 31.24 241.17 254.67 1247.16 21.06 97.50 228.17
                         
Annual Sum or Average 4071.00 0.64     2297.95 17.02 1085.33 3547.00 766.65 16.50 305.17 3070.33
Minimum of Months 263.00 0.63 0.61   883.29 10.29 0.00 230.17 517.61 14.34 0.00 208.67
Maximum of Months 411.67 0.64 0.61   6018.43 32.04 266.33 342.00 1348.41 21.59 100.50 290.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-08:50 1009.65 12.26 45.00 213.33 582.94 13.78 40.00 144.83
February 263.00 0.66 0.61 01-FEB-10:09 1552.17 13.99 58.50 197.83 791.31 13.32 37.00 150.00
March 351.67 0.64 0.61 01-MAR-08:09 1763.27 13.60 74.33 284.83 710.18 10.67 1.17 236.83
April 369.33 0.64 0.61 01-APR-07:49 1718.74 8.17 0.00 305.50 954.22 10.52 0.00 259.83
May 407.00 0.64 0.61 01-MAY-06:49 1930.98 8.75 0.00 347.33 815.93 11.05 0.00 298.67
June 411.67 0.64 0.61 01-JUN-06:19 1949.34 8.79 0.00 349.33 826.41 11.07 0.00 301.83
July 411.00 0.64 0.61 01-JUL-05:00 1931.79 8.90 0.00 353.50 835.55 11.19 0.00 307.50
August 390.50 0.64 0.61 01-AUG-06:40 1784.78 9.27 0.00 334.33 969.22 11.50 0.00 289.17
September 298.50 0.65 0.61 01-SEP-06:00 1704.94 8.75 2.67 285.00 879.10 11.08 2.83 228.00
October 293.50 0.65 0.61 01-OCT-07:30 1932.81 13.73 67.33 241.00 751.69 13.30 40.00 177.83
November 299.00 0.66 0.61 01-NOV-07:00 1348.65 14.74 75.83 224.33 762.53 15.92 66.50 167.67
December 285.17 0.65 0.61 01-DEC-07:00 1169.44 14.78 67.33 211.50 605.97 14.39 44.33 145.67
                         
Annual Sum or Average 4071.00 0.65     1682.34 11.00 391.00 3347.83 800.23 12.13 231.83 2707.83
Minimum of Months 263.00 0.64 0.61   1009.65 8.17 0.00 197.83 582.94 10.52 0.00 144.83
Maximum of Months 411.67 0.66 0.61   1949.34 14.78 75.83 353.50 969.22 15.92 66.50 307.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.68 0.61 01-JAN-09:09 387.32 0.00 0.00 151.50 245.53 0.00 0.00 27.67
February 263.00 0.68 0.61 01-FEB-10:30 411.42 0.00 0.00 142.33 268.51 0.00 0.00 65.67
March 351.67 0.65 0.61 01-MAR-08:39 525.68 0.00 0.00 269.50 335.98 0.00 0.00 165.50
April 369.33 0.64 0.61 01-APR-07:00 630.24 0.00 0.00 307.00 394.51 0.00 0.00 229.67
May 407.00 0.63 0.61 01-MAY-06:00 778.97 0.00 0.00 364.17 482.03 0.00 0.00 323.67
June 411.67 0.63 0.61 01-JUN-06:30 851.03 0.00 0.00 375.33 525.44 0.00 0.00 349.83
July 411.00 0.63 0.61 01-JUL-06:10 864.03 0.00 0.00 372.67 503.46 0.00 0.00 331.50
August 390.50 0.63 0.61 01-AUG-06:49 765.08 0.00 0.00 346.33 467.50 0.00 0.00 296.33
September 298.50 0.65 0.61 01-SEP-07:10 581.51 0.00 0.00 280.00 369.45 0.00 0.00 170.33
October 293.50 0.67 0.61 01-OCT-08:09 429.76 0.00 0.00 181.50 289.42 0.00 0.00 81.67
November 299.00 0.67 0.61 01-NOV-08:20 399.29 0.00 0.00 181.50 255.12 0.00 0.00 33.17
December 285.17 0.68 0.61 01-DEC-09:20 372.39 0.00 0.00 143.67 237.38 0.00 0.00 8.33
                         
Annual Sum or Average 4071.00 0.65     610.41 0.00 0.00 3115.50 380.01 0.00 0.00 2083.33
Minimum of Months 263.00 0.63 0.61   372.39 0.00 0.00 142.33 237.38 0.00 0.00 8.33
Maximum of Months 411.67 0.68 0.61   864.03 0.00 0.00 375.33 525.44 0.00 0.00 349.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 290.67 0.65 0.61 01-JAN-09:20 1354.66 14.65 68.00 216.67 798.35 15.98 60.17 153.00
February 263.00 0.66 0.61 01-FEB-10:20 1186.37 11.62 41.17 185.00 694.68 13.38 37.00 140.00
March 351.67 0.64 0.61 01-MAR-08:39 1780.28 11.78 47.33 288.00 911.38 10.67 0.00 234.00
April 369.33 0.64 0.61 01-APR-08:20 1859.22 8.26 0.00 307.67 1081.34 10.64 0.00 264.33
May 407.00 0.64 0.61 01-MAY-07:30 1848.72 8.86 0.00 344.83 802.88 11.16 0.00 299.00
June 411.67 0.64 0.61 01-JUN-06:00 2031.61 8.88 0.00 349.67 843.04 11.16 0.00 301.33
July 411.00 0.64 0.61 01-JUL-07:30 2006.15 8.95 0.00 348.67 826.58 11.19 0.00 299.33
August 390.50 0.64 0.61 01-AUG-07:30 1896.36 9.64 4.83 337.33 839.50 11.62 0.00 294.50
September 298.50 0.65 0.61 01-SEP-07:30 1745.68 12.48 49.67 284.83 898.59 11.08 0.00 221.17
October 293.50 0.65 0.61 01-OCT-08:20 1844.23 13.92 70.50 232.17 723.76 10.11 2.17 179.33
November 299.00 0.66 0.61 01-NOV-08:20 1311.47 14.87 79.67 225.67 669.08 14.31 51.83 167.33
December 285.17 0.65 0.61 01-DEC-09:20 1141.29 14.87 70.83 209.17 592.62 14.27 44.50 143.17
                         
Annual Sum or Average 4071.00 0.65     1707.76 11.23 432.00 3329.67 816.93 11.97 195.67 2696.50
Minimum of Months 263.00 0.64 0.61   1141.29 8.26 0.00 185.00 592.62 10.11 0.00 140.00
Maximum of Months 411.67 0.66 0.61   2031.61 14.87 79.67 349.67 1081.34 15.98 60.17 301.33



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.270236E+09 24934.34 06-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.210618E+09 32677.37 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 35274343.56 9291.98 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.175875E+09 15660.78 17-APR-14:20 0.00 0.00 0.00 0.00 0.00
May 0.169921E+09 12319.40 15-MAY-14:20 0.00 0.00 0.00 0.00 0.00
June 63518557.51 8099.72 02-JUN-13:50 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 6111848.72 3867.03 25-AUG-11:00 0.00 0.00 0.00 0.00 0.00
September 36965580.39 13474.61 14-SEP-16:30 0.00 0.00 0.00 0.00 0.00
October 10092401.14 10131.85 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 71502731.12 21001.90 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.175421E+09 23954.91 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.122554E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.270236E+09 32677.37   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.614812E+09 14556.14 06-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.217597E+09 14681.10 03-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 5962955.87 4064.17 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 19999899.63 7236.90 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.858371E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.614812E+09 14681.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.428328E+09 11868.27 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.144975E+09 11901.76 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 8306732.89 7127.51 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 41441297.96 11901.73 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.623050E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.428328E+09 11901.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.570171E+09 16567.13 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.195918E+09 16612.47 03-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 12229952.10 13673.44 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 59553204.43 16614.85 18-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.837873E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.570171E+09 16614.85   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.140624E+09 10629.18 10-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 14985035.81 10667.06 13-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.155609E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.140624E+09 10667.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.749084E+10 278028.81 06-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.446337E+10 351020.88 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.914326E+09 113271.23 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.138516E+10 139373.91 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.122654E+10 86528.19 18-MAY-15:00 0.00 0.00 0.00 0.00 0.00
June 0.500462E+09 52395.94 02-JUN-15:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 74084950.93 52707.88 25-AUG-13:50 0.00 0.00 0.00 0.00 0.00
September 0.187217E+09 44566.05 14-SEP-15:50 0.00 0.00 0.00 0.00 0.00
October 0.273221E+09 125667.42 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.264848E+10 235615.34 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.359969E+10 286530.09 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.227634E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.749084E+10 351020.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.340786E+10 529307.60 10-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.122133E+10 532215.99 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.462918E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.340786E+10 532215.99   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.459693E+11 129142.22 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.247005E+11 139073.42 24-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.158909E+10 138350.08 22-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.316740E+09 115631.95 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.443973E+09 139267.22 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.505974E+10 138979.35 18-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.202737E+11 138750.25 15-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.983531E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.459693E+11 139267.22   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.269611E+11 137990.34 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.141276E+11 137319.07 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.849082E+09 147596.04 22-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.122382E+09 57494.57 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.415303E+09 110469.29 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.229204E+10 136050.95 25-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.109463E+11 139683.89 08-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.557138E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.269611E+11 147596.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.218639E+11 149622.23 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.111408E+11 148542.63 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.484376E+09 160099.68 22-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.125784E+09 41283.10 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.238735E+09 36650.95 31-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.131418E+10 147445.62 25-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.728788E+10 148671.64 26-DEC-05:23 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.424556E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.218639E+11 160099.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.223379E+11 145433.69 02-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.112395E+11 144456.77 02-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.448707E+09 129901.50 22-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 65098491.72 10873.90 06-APR-05:05 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.227482E+09 30632.53 26-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.213929E+10 143985.91 21-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.868378E+10 145052.30 26-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.451418E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.223379E+11 145433.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.700370E+09 33372.54 06-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.603510E+09 43545.95 03-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 73219573.52 15946.06 18-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.119488E+09 18992.64 06-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.156814E+09 10163.79 16-MAY-16:00 0.00 0.00 0.00 0.00 0.00
June 40203974.90 5738.44 02-JUN-13:55 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 14459604.36 3356.54 22-SEP-15:00 0.00 0.00 0.00 0.00 0.00
October 40910345.87 17333.90 26-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.139172E+09 29947.99 22-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.319967E+09 35672.50 18-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.220811E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.700370E+09 43545.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.780480E+10 77873.04 02-JAN-05:15 0.00 0.00 0.00 0.00 0.00
February 0.360444E+10 77513.10 07-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 67166186.03 44238.04 20-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 40511089.60 30258.42 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.546503E+09 76912.47 21-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.369378E+10 77577.90 26-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.157572E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.780480E+10 77873.04   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.939109E+10 14836.72 02-JAN-05:55 0.00 0.00 0.00 0.00 0.00
February 0.551157E+10 14819.88 07-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.946137E+09 14789.62 23-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.238686E+09 14693.73 26-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 1914744.31 812.21 11-MAY-05:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.548984E+09 14769.66 24-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.206795E+10 14775.58 24-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.565058E+10 14839.80 11-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.243569E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.939109E+10 14839.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.538645E+10 14118.57 18-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.307885E+10 14154.60 11-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.468590E+09 14091.28 22-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 92455369.89 13991.65 06-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 430111.51 467.62 11-MAY-05:40 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 675934.61 157.49 29-SEP-07:00 0.00 0.00 0.00 0.00 0.00
October 0.338423E+09 14080.40 31-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.101673E+10 14101.53 25-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.306432E+10 14123.68 26-DEC-05:24 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.134469E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.538645E+10 14154.60   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.531806E+10 16768.30 02-JAN-04:34 0.00 0.00 0.00 0.00 0.00
February 0.316571E+10 16748.32 11-FEB-05:03 0.00 0.00 0.00 0.00 0.00
March 0.491723E+09 16716.88 22-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.148614E+09 16570.96 27-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 598016.36 265.48 11-MAY-05:50 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.289587E+09 16721.82 25-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.852102E+09 16725.16 24-NOV-05:02 0.00 0.00 0.00 0.00 0.00
December 0.268425E+10 16737.56 27-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.129506E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.531806E+10 16768.30   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.476924E+10 15880.44 18-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.262702E+10 15867.17 11-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.382459E+09 15760.74 22-MAR-04:01 0.00 0.00 0.00 0.00 0.00
April 86051638.38 11850.08 06-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.241323E+09 15639.60 26-OCT-04:01 0.00 0.00 0.00 0.00 0.00
November 0.942375E+09 15834.25 21-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.253748E+10 15839.47 26-DEC-04:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.115860E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.476924E+10 15880.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.170240E+10 0.161784E+10 37848.76 31-JAN-15:00 37848.76 0.03
February 0.00 0.00 0.785620E+10 0.785243E+10 86875.98 28-FEB-15:00 86875.98 0.03
March 0.00 0.00 0.254286E+11 0.245313E+11 121292.02 30-MAR-14:40 121292.02 0.17
April 0.00 0.00 0.561150E+11 0.535745E+11 160975.89 17-APR-14:35 160975.89 0.38
May 0.00 0.00 0.885510E+11 0.760433E+11 205064.54 31-MAY-05:03 84363.89 0.57
June 0.00 0.00 0.136427E+12 0.118117E+12 211940.52 26-JUN-05:02 149693.02 0.69
July 0.00 0.00 0.162383E+12 0.135670E+12 214059.46 06-JUL-05:03 149430.56 0.83
August 0.00 0.00 0.187957E+12 0.157075E+12 217102.14 07-AUG-05:03 154346.11 0.88
September 0.00 0.00 0.102888E+12 0.866076E+11 209420.64 07-SEP-05:03 146652.41 0.63
October 0.00 0.00 0.476811E+11 0.399763E+11 218631.13 19-OCT-05:03 139699.86 0.24
November 0.00 0.00 0.174501E+11 0.161107E+11 108255.77 27-NOV-06:03 108255.77 0.12
December 0.00 0.00 0.533743E+10 0.447382E+10 97166.29 13-DEC-06:02 46215.15 0.05
                 
Annual Sum or Average 0.00 0.00 0.839776E+12 0.721650E+12       0.39
Minimum of Months 0.00 0.00 0.170240E+10 0.161784E+10 37848.76   37848.76 0.03
Maximum of Months 0.00 0.00 0.187957E+12 0.157075E+12 218631.13   160975.89 0.88



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.118183E+11 0.112566E+11 251386.18 31-JAN-15:00 251386.18 0.03
February 0.00 0.00 0.559120E+11 0.559120E+11 676909.21 28-FEB-15:00 676909.21 0.03
March 0.00 0.00 0.183385E+12 0.178019E+12 1123846.26 30-MAR-15:20 1123846.26 0.15
April 0.00 0.00 0.396528E+12 0.381513E+12 1430460.49 12-APR-15:15 1430460.49 0.28
May 0.00 0.00 0.767148E+12 0.658203E+12 1941333.62 31-MAY-05:03 798568.62 0.54
June 0.00 0.00 0.114664E+13 0.960804E+12 2085228.30 19-JUN-03:02 1303493.03 0.60
July 0.00 0.00 0.128866E+13 0.102233E+13 2112400.83 26-JUL-05:03 1330121.00 0.67
August 0.00 0.00 0.143588E+13 0.112368E+13 2397773.12 23-AUG-03:02 1366400.42 0.70
September 0.00 0.00 0.876085E+12 0.718488E+12 2053957.56 27-SEP-05:02 1350909.20 0.59
October 0.00 0.00 0.361363E+12 0.295163E+12 2207670.12 19-OCT-05:03 1217434.10 0.21
November 0.00 0.00 0.111274E+12 0.105038E+12 680928.19 04-NOV-05:03 355693.01 0.11
December 0.00 0.00 0.296407E+11 0.252955E+11 734280.96 13-DEC-06:02 354027.83 0.05
                 
Annual Sum or Average 0.00 0.00 0.666433E+13 0.553570E+13       0.33
Minimum of Months 0.00 0.00 0.118183E+11 0.112566E+11 251386.18   251386.18 0.03
Maximum of Months 0.00 0.00 0.143588E+13 0.112368E+13 2397773.12   1430460.49 0.70



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.112782E+10 0.107011E+10 20631.63 31-JAN-15:00 20631.63 0.03
February 0.00 0.00 0.482683E+10 0.482683E+10 63845.21 28-FEB-15:00 63845.21 0.03
March 0.00 0.00 0.175328E+11 0.171658E+11 117536.83 30-MAR-15:20 117536.83 0.15
April 0.00 0.00 0.408191E+11 0.392828E+11 153893.36 17-APR-15:10 153893.36 0.28
May 0.00 0.00 0.835939E+11 0.724681E+11 194563.47 31-MAY-05:03 80029.29 0.53
June 0.00 0.00 0.128479E+12 0.109122E+12 217389.20 26-JUN-05:02 145406.00 0.60
July 0.00 0.00 0.144977E+12 0.117307E+12 223878.38 26-JUL-05:03 137117.88 0.68
August 0.00 0.00 0.159690E+12 0.127477E+12 258890.94 23-AUG-03:02 145359.09 0.71
September 0.00 0.00 0.909157E+11 0.753402E+11 216953.18 27-SEP-05:02 141607.32 0.58
October 0.00 0.00 0.352155E+11 0.286186E+11 213019.94 19-OCT-05:03 113068.95 0.21
November 0.00 0.00 0.930220E+10 0.877156E+10 61331.41 04-NOV-05:03 32789.09 0.11
December 0.00 0.00 0.253367E+10 0.215805E+10 36533.81 12-DEC-14:40 36533.81 0.05
                 
Annual Sum or Average 0.00 0.00 0.719013E+12 0.603608E+12       0.33
Minimum of Months 0.00 0.00 0.112782E+10 0.107011E+10 20631.63   20631.63 0.03
Maximum of Months 0.00 0.00 0.159690E+12 0.127477E+12 258890.94   153893.36 0.71



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.524622E+09 0.513165E+09 51523.20 19-JAN-06:03 21814.67 0.02
February 0.00 0.00 0.390557E+10 0.389432E+10 55614.74 28-FEB-14:20 55614.74 0.01
March 0.00 0.00 0.121630E+11 0.121157E+11 79473.88 30-MAR-05:02 40460.03 0.12
April 0.00 0.00 0.257121E+11 0.253121E+11 87943.01 03-APR-03:02 87943.01 0.22
May 0.00 0.00 0.468085E+11 0.427488E+11 124495.62 31-MAY-03:02 49523.06 0.43
June 0.00 0.00 0.815630E+11 0.683942E+11 147014.70 26-JUN-03:02 85875.04 0.51
July 0.00 0.00 0.942548E+11 0.741536E+11 145098.98 21-JUL-03:02 84252.09 0.55
August 0.00 0.00 0.113944E+12 0.877611E+11 162734.31 20-AUG-16:20 83756.31 0.63
September 0.00 0.00 0.697246E+11 0.587103E+11 148147.25 04-SEP-16:42 87246.77 0.52
October 0.00 0.00 0.307473E+11 0.256249E+11 135022.09 19-OCT-04:03 80149.31 0.19
November 0.00 0.00 0.980654E+10 0.907783E+10 77352.31 27-NOV-06:03 38395.61 0.08
December 0.00 0.00 0.280578E+10 0.260407E+10 74239.27 13-DEC-06:02 34903.84 0.04
                 
Annual Sum or Average 0.00 0.00 0.491960E+12 0.410910E+12       0.28
Minimum of Months 0.00 0.00 0.524622E+09 0.513165E+09 51523.20   21814.67 0.01
Maximum of Months 0.00 0.00 0.113944E+12 0.877611E+11 162734.31   87943.01 0.63



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.321566E+12 0.321064E+12 129146.46 19-JAN-17:00 123147.86 0.00
February 0.00 0.00 0.512648E+12 0.512104E+12 219177.13 17-FEB-17:00 213474.38 0.00
March 0.00 0.00 0.817896E+12 0.816358E+12 393819.03 31-MAR-24:00 393819.03 0.00
April 0.00 0.00 0.102932E+13 0.102735E+13 405786.59 04-APR-13:00 399304.50 0.00
May 0.00 0.00 0.339373E+12 0.333189E+12 212502.97 31-MAY-23:10 210564.28 0.00
June 0.00 0.00 0.571381E+12 0.562367E+12 303665.34 30-JUN-23:03 302488.72 0.00
July 0.00 0.00 0.838942E+12 0.827929E+12 396291.11 31-JUL-24:00 395505.67 0.00
August 0.00 0.00 0.107911E+13 0.106797E+13 421696.92 08-AUG-17:00 403198.37 0.00
September 0.00 0.00 0.336431E+12 0.328167E+12 212067.84 30-SEP-23:20 211565.07 0.00
October 0.00 0.00 0.582806E+12 0.579133E+12 304141.75 31-OCT-24:00 304141.75 0.00
November 0.00 0.00 0.796779E+12 0.795334E+12 316825.87 27-NOV-17:00 310190.65 0.00
December 0.00 0.00 0.106384E+13 0.106310E+13 407560.41 13-DEC-14:00 399764.18 0.00
                 
Annual Sum or Average 0.00 0.00 0.829009E+13 0.823407E+13       0.00
Minimum of Months 0.00 0.00 0.321566E+12 0.321064E+12 129146.46   123147.86 0.00
Maximum of Months 0.00 0.00 0.107911E+13 0.106797E+13 421696.92   403198.37 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.376797E+10 0.374885E+10 2207.48 20-JAN-17:00 2106.32 0.00
February 0.00 0.00 0.866105E+10 0.863896E+10 4483.68 20-FEB-18:00 4450.67 0.00
March 0.00 0.00 0.155761E+11 0.155102E+11 7689.01 31-MAR-24:00 7689.01 0.00
April 0.00 0.00 0.201942E+11 0.201045E+11 8419.75 09-APR-18:13 8419.75 0.00
May 0.00 0.00 0.605388E+10 0.582201E+10 4067.47 31-MAY-24:00 4013.40 0.00
June 0.00 0.00 0.111066E+11 0.107364E+11 5920.61 30-JUN-23:03 5865.11 0.00
July 0.00 0.00 0.166720E+11 0.161962E+11 7812.85 31-JUL-24:00 7792.16 0.00
August 0.00 0.00 0.218516E+11 0.213025E+11 8808.90 04-AUG-15:00 8184.72 0.00
September 0.00 0.00 0.604858E+10 0.573502E+10 3809.67 30-SEP-24:00 3796.23 0.00
October 0.00 0.00 0.107725E+11 0.106216E+11 5696.82 31-OCT-24:00 5696.82 0.00
November 0.00 0.00 0.149824E+11 0.149252E+11 6362.35 11-NOV-16:55 6362.35 0.00
December 0.00 0.00 0.201492E+11 0.201171E+11 8152.87 11-DEC-16:50 7964.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.155836E+12 0.153459E+12       0.00
Minimum of Months 0.00 0.00 0.376797E+10 0.374885E+10 2207.48   2106.32 0.00
Maximum of Months 0.00 0.00 0.218516E+11 0.213025E+11 8808.90   8419.75 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.137511E+11 0.135815E+11 18792.38 20-JAN-17:00 17761.29 0.00
February 0.00 0.00 0.660097E+11 0.657964E+11 40043.23 28-FEB-17:00 40043.23 0.00
March 0.00 0.00 0.140827E+12 0.140169E+12 72310.37 31-MAR-24:00 72310.37 0.00
April 0.00 0.00 0.189686E+12 0.188786E+12 78793.92 04-APR-15:30 75848.00 0.00
May 0.00 0.00 0.552783E+11 0.530009E+11 38589.14 31-MAY-24:00 38026.93 0.00
June 0.00 0.00 0.105287E+12 0.101605E+12 56574.14 30-JUN-24:00 56403.15 0.00
July 0.00 0.00 0.158868E+12 0.154124E+12 75313.64 31-JUL-24:00 75111.40 0.00
August 0.00 0.00 0.207658E+12 0.202169E+12 83959.71 04-AUG-15:00 77700.19 0.00
September 0.00 0.00 0.548468E+11 0.517719E+11 33022.28 30-SEP-24:00 32822.95 0.00
October 0.00 0.00 0.950277E+11 0.935374E+11 49861.81 31-OCT-24:00 49861.81 0.00
November 0.00 0.00 0.131029E+12 0.130463E+12 58716.20 03-NOV-15:20 56189.09 0.00
December 0.00 0.00 0.171461E+12 0.171139E+12 76366.00 13-DEC-16:00 73070.75 0.00
                 
Annual Sum or Average 0.00 0.00 0.138973E+13 0.136614E+13       0.00
Minimum of Months 0.00 0.00 0.137511E+11 0.135815E+11 18792.38   17761.29 0.00
Maximum of Months 0.00 0.00 0.207658E+12 0.202169E+12 83959.71   77700.19 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.554213E+09 0.538606E+09 1911.72 20-JAN-17:00 1805.50 0.00
February 0.00 0.00 0.533047E+10 0.530960E+10 4030.34 28-FEB-17:00 4030.34 0.00
March 0.00 0.00 0.132592E+11 0.131939E+11 6986.71 31-MAR-23:20 6986.71 0.00
April 0.00 0.00 0.185912E+11 0.185016E+11 7910.61 04-APR-15:40 7617.93 0.00
May 0.00 0.00 0.546299E+10 0.523556E+10 3826.18 31-MAY-23:20 3734.38 0.00
June 0.00 0.00 0.106060E+11 0.102375E+11 5641.74 30-JUN-24:00 5624.49 0.00
July 0.00 0.00 0.159972E+11 0.155229E+11 7569.12 31-JUL-24:00 7548.78 0.00
August 0.00 0.00 0.208846E+11 0.203357E+11 8488.38 04-AUG-15:00 7863.10 0.00
September 0.00 0.00 0.537534E+10 0.506925E+10 2903.49 07-SEP-16:00 2524.68 0.00
October 0.00 0.00 0.876240E+10 0.861437E+10 4524.29 18-OCT-16:00 4021.71 0.00
November 0.00 0.00 0.118154E+11 0.117594E+11 5887.86 02-NOV-16:00 5703.41 0.00
December 0.00 0.00 0.153093E+11 0.152773E+11 7613.50 13-DEC-16:00 7284.36 0.00
                 
Annual Sum or Average 0.00 0.00 0.131948E+12 0.129596E+12       0.00
Minimum of Months 0.00 0.00 0.554213E+09 0.538606E+09 1911.72   1805.50 0.00
Maximum of Months 0.00 0.00 0.208846E+11 0.203357E+11 8488.38   7863.10 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 60434.67 1447838.50 09-JAN-05:11
February 0.00 0.00 01-FEB-00:10 35338.19 1344776.36 13-FEB-06:02
March 0.00 0.00 01-MAR-00:10 2524.07 1006500.73 22-MAR-05:02
April 0.00 0.00 01-APR-00:10 1084.06 341710.33 06-APR-05:03
May 0.00 0.00 01-MAY-00:03 598.97 89008.22 15-MAY-14:30
June 0.00 0.00 01-JUN-00:10 248.67 58616.52 03-JUN-12:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 17.08 31714.74 25-AUG-13:50
September 0.00 0.00 01-SEP-00:03 94.91 38132.10 15-SEP-11:30
October 0.00 0.00 01-OCT-00:10 1102.84 554987.01 26-OCT-05:03
November 0.00 0.00 01-NOV-00:10 7317.63 1055402.22 25-NOV-06:01
December 0.00 0.00 01-DEC-00:10 25529.58 1113833.05 19-DEC-05:01
             
Annual Sum or Average 0.00     11091.10    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   60434.67 1447838.50  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 14466.85 882681.69 31-JAN-15:50 0.00 0.00 01-JAN-00:05
February 62750.26 1508846.61 28-FEB-13:50 142.72 306955.44 27-FEB-04:03
March 174801.26 1646732.98 30-MAR-15:00 350.03 399817.66 12-MAR-10:33
April 340346.10 1884326.35 12-APR-15:15 17.07 43644.13 21-APR-01:33
May 580012.35 2249250.44 31-MAY-03:02 281.97 513766.82 21-MAY-07:00
June 813731.86 3030079.59 19-JUN-05:04 12.78 54797.57 10-JUN-04:23
July 867450.84 3069080.28 27-JUL-05:04 0.00 0.00 01-JUL-00:10
August 931164.66 2953074.30 21-AUG-05:03 0.00 0.00 01-AUG-00:03
September 655782.00 2965878.55 27-SEP-05:04 16.92 68882.67 24-SEP-07:50
October 294311.90 2320177.88 19-OCT-05:03 107.40 243817.51 08-OCT-08:33
November 122353.26 1355300.44 02-NOV-14:00 15.45 79219.79 12-NOV-11:25
December 33522.91 1219927.41 12-DEC-14:30 0.00 6.60 11-DEC-10:50
             
Annual Sum or Average 409564.54     78.86    
Minimum of Months 14466.85 882681.69   0.00 0.00  
Maximum of Months 931164.66 3069080.28   350.03 513766.82  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 7120.81 594503.42 31-JAN-15:50 0.00 0.00 01-JAN-00:05
February 35780.17 1011888.73 28-FEB-15:00 0.00 0.00 01-FEB-00:10
March 109266.45 2141393.08 30-MAR-05:02 0.00 0.00 01-MAR-00:10
April 238579.43 2584505.02 03-APR-05:02 0.00 0.00 01-APR-00:10
May 435044.85 3893658.61 31-MAY-05:03 0.00 0.00 01-MAY-00:03
June 650685.22 4191087.77 19-JUN-05:02 0.00 0.00 01-JUN-00:10
July 702394.14 4171395.81 12-JUL-05:02 0.00 0.00 01-JUL-00:10
August 776922.98 4210553.97 21-AUG-05:02 0.00 0.00 01-AUG-00:03
September 511150.10 4114055.27 27-SEP-05:02 0.00 0.00 01-SEP-00:03
October 216373.99 4114279.78 18-OCT-05:02 0.00 0.00 01-OCT-00:10
November 71086.92 1669757.19 04-NOV-05:03 0.00 0.00 01-NOV-00:10
December 19075.28 1501761.83 13-DEC-06:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 316161.78     0.00    
Minimum of Months 7120.81 594503.42   0.00 0.00  
Maximum of Months 776922.98 4210553.97   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 165148.21 414570.76 31-JAN-15:00 0.00 0.00 01-JAN-00:05
February 338663.45 850011.15 28-FEB-15:00 0.00 0.00 01-FEB-00:10
March 574133.53 1239520.52 30-MAR-16:00 0.00 0.00 01-MAR-00:10
April 884583.09 1511506.08 17-APR-16:00 0.00 0.00 01-APR-00:10
May 433619.98 952749.36 30-MAY-15:00 0.00 0.00 01-MAY-00:03
June 849617.20 1396340.91 06-JUN-15:00 0.00 0.00 01-JUN-00:10
July 1140769.59 1758471.85 08-JUL-15:50 0.00 0.00 01-JUL-00:10
August 1385568.67 1862827.06 01-AUG-16:10 0.00 0.00 01-AUG-00:03
September 514650.11 1026578.05 07-SEP-16:00 0.00 0.00 01-SEP-00:03
October 467725.01 1149791.38 10-OCT-16:00 0.00 0.00 01-OCT-00:10
November 538333.52 1029654.53 05-NOV-16:00 0.00 0.00 01-NOV-00:10
December 617063.81 1172165.01 12-DEC-14:50 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 661378.05     0.00    
Minimum of Months 165148.21 414570.76   0.00 0.00  
Maximum of Months 1385568.67 1862827.06   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 14860.84 49715.31 27-JAN-12:10
February 0.00 0.00 01-FEB-00:10 14971.71 49710.31 03-FEB-12:10
March 0.00 0.00 01-MAR-00:10 15328.54 48925.30 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 13623.22 46292.28 03-APR-11:50
May 0.00 0.00 01-MAY-00:03 13024.31 43160.48 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 12356.56 39661.64 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 10969.00 36987.88 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 11840.02 36824.80 31-AUG-11:50
September 0.00 0.00 01-SEP-00:03 11664.09 39111.39 29-SEP-11:50
October 0.00 0.00 01-OCT-00:10 12487.35 42654.03 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 13634.79 46040.42 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 14030.37 48551.78 29-DEC-12:30
             
Annual Sum or Average 0.00     13222.80    
Minimum of Months 0.00 0.00   10969.00 36824.80  
Maximum of Months 0.00 0.00   15328.54 49715.31  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 7457.07 504313.19 31-JAN-15:50 2310.65 173961.99 09-JAN-21:00
February 36895.80 1058739.34 28-FEB-14:40 2300.95 174184.69 03-FEB-09:40
March 109340.66 2563449.70 30-MAR-15:20 1473.48 132435.62 03-MAR-06:40
April 251384.94 2715103.50 14-APR-13:40 1357.07 110231.86 05-APR-12:20
May 541015.81 4306928.27 31-MAY-13:10 133.80 85477.65 10-MAY-09:40
June 1381389.15 5131268.06 23-JUN-11:30 94.04 43844.64 10-JUN-07:40
July 1737573.24 5619194.52 07-JUL-12:00 0.03 422.23 03-JUL-02:50
August 2100976.41 5663660.44 10-AUG-16:00 0.00 0.00 01-AUG-00:03
September 901980.43 5054320.31 06-SEP-12:30 68.71 43914.50 18-SEP-07:00
October 290072.46 4400736.21 18-OCT-14:50 885.58 115272.57 31-OCT-08:70
November 72910.83 793620.75 02-NOV-14:00 1499.55 140381.52 21-NOV-10:00
December 18899.85 718967.06 12-DEC-14:30 2018.04 139477.74 01-DEC-18:30
             
Annual Sum or Average 625283.41     1004.05    
Minimum of Months 7457.07 504313.19   0.00 0.00  
Maximum of Months 2100976.41 5663660.44   2310.65 174184.69  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137451E+11 0.81 9163.58 01-JAN-00:05 1.44
February 0.122097E+11 0.79 9163.58 01-FEB-05:01 1.44
March 0.145307E+11 0.85 9163.58 01-MAR-05:03 1.44
April 0.132819E+11 0.80 9163.58 01-APR-04:03 1.44
May 0.141596E+11 0.82 9163.58 01-MAY-03:05 1.42
June 0.143969E+11 0.86 9163.58 01-JUN-04:03 1.43
July 0.141279E+11 0.82 9163.58 01-JUL-03:02 1.43
August 0.156946E+11 0.91 9163.58 01-AUG-03:02 1.43
September 0.149472E+11 0.90 9163.58 01-SEP-03:02 1.43
October 0.149692E+11 0.87 9163.58 01-OCT-23:20 1.42
November 0.144858E+11 0.88 9163.58 01-NOV-03:10 1.44
December 0.140258E+11 0.82 9163.58 01-DEC-04:02 1.44
           
Annual Sum or Average 0.170574E+12 0.85      
Minimum of Months 0.122097E+11 0.79 9163.58   1.42
Maximum of Months 0.156946E+11 0.91 9163.58   1.44



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.356414E+10 0.32 12154.81 05-JAN-06:01 1.38
February 0.433061E+10 0.37 12154.81 03-FEB-06:01 1.38
March 0.767553E+10 0.49 15467.75 31-MAR-05:02 1.59
April 0.938364E+10 0.58 20969.46 11-APR-14:20 1.93
May 0.909031E+10 0.53 20969.46 15-MAY-14:20 1.93
June 0.119894E+11 0.68 20969.46 02-JUN-14:00 1.93
July 0.134700E+11 0.73 20969.46 01-JUL-05:02 1.93
August 0.160127E+11 0.82 20969.46 01-AUG-05:03 1.93
September 0.921447E+10 0.55 20969.46 06-SEP-05:03 1.93
October 0.769767E+10 0.48 20969.46 10-OCT-05:02 1.93
November 0.660860E+10 0.45 12809.89 06-NOV-16:30 1.42
December 0.569872E+10 0.39 12763.56 13-DEC-06:02 1.41
           
Annual Sum or Average 0.104736E+12 0.53      
Minimum of Months 0.356414E+10 0.32 12154.81   1.38
Maximum of Months 0.160127E+11 0.82 20969.46   1.93



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.284738E+11 0.32 43109.69 02-JAN-06:02 0.78
February 0.297868E+11 0.34 94737.13 24-FEB-06:03 1.24
March 0.457422E+11 0.38 127428.99 22-MAR-05:02 1.48
April 0.565879E+11 0.42 194992.65 12-APR-15:15 1.93
May 0.749326E+11 0.49 194992.65 15-MAY-14:35 1.93
June 0.955653E+11 0.58 194992.65 01-JUN-05:02 1.93
July 0.968440E+11 0.58 194992.65 05-JUL-05:02 1.93
August 0.106313E+12 0.62 194992.65 01-AUG-05:03 1.93
September 0.726036E+11 0.49 194992.65 06-SEP-05:03 1.93
October 0.490119E+11 0.38 172978.59 19-OCT-05:03 1.78
November 0.355018E+11 0.33 97710.51 18-NOV-06:03 1.26
December 0.295779E+11 0.31 110633.36 15-DEC-06:03 1.36
           
Annual Sum or Average 0.720941E+12 0.44      
Minimum of Months 0.284738E+11 0.31 43109.69   0.78
Maximum of Months 0.106313E+12 0.62 194992.65   1.93



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.357151E+10 0.39 4262.79 13-JAN-06:02 0.75
February 0.308474E+10 0.36 6078.13 28-FEB-16:20 0.91
March 0.381160E+10 0.35 11734.63 30-MAR-16:00 1.33
April 0.497345E+10 0.38 21019.26 17-APR-14:35 1.93
May 0.749167E+10 0.47 21019.26 15-MAY-15:20 1.93
June 0.103844E+11 0.59 21019.26 02-JUN-15:50 1.93
July 0.108445E+11 0.59 21019.26 01-JUL-05:02 1.92
August 0.117710E+11 0.63 21019.26 01-AUG-05:03 1.93
September 0.708533E+10 0.46 21019.26 08-SEP-05:02 1.93
October 0.418426E+10 0.35 12002.06 19-OCT-05:03 1.35
November 0.293994E+10 0.31 7718.63 03-NOV-05:02 1.04
December 0.319839E+10 0.35 7718.63 13-DEC-06:02 1.03
           
Annual Sum or Average 0.733407E+11 0.44      
Minimum of Months 0.293994E+10 0.31 4262.79   0.75
Maximum of Months 0.117710E+11 0.63 21019.26   1.93



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.973018E+11 1.40 36328.34 01-JAN-00:05 1.39
February 0.878855E+11 1.40 36328.34 01-FEB-00:20 1.39
March 0.973018E+11 1.39 36328.34 01-MAR-00:10 1.40
April 0.941630E+11 1.39 36328.34 01-APR-00:10 1.39
May 0.973018E+11 1.39 36328.34 01-MAY-00:03 1.39
June 0.941630E+11 1.39 36328.34 01-JUN-00:10 1.39
July 0.973018E+11 1.39 36328.34 01-JUL-00:10 1.39
August 0.973018E+11 1.39 36328.34 01-AUG-00:03 1.39
September 0.941630E+11 1.39 36328.34 01-SEP-00:03 1.39
October 0.973018E+11 1.39 36328.34 01-OCT-00:10 1.39
November 0.941630E+11 1.39 36328.34 01-NOV-00:10 1.40
December 0.973018E+11 1.40 36328.34 01-DEC-00:10 1.39
           
Annual Sum or Average 0.114565E+13 1.39      
Minimum of Months 0.878855E+11 1.39 36328.34   1.39
Maximum of Months 0.973018E+11 1.40 36328.34   1.40



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144401E+10 0.95 539.13 01-JAN-00:05 0.95
February 0.130426E+10 0.95 539.13 01-FEB-00:10 0.95
March 0.144401E+10 0.95 539.13 01-MAR-00:10 0.95
April 0.139742E+10 0.95 539.13 01-APR-00:10 0.95
May 0.144401E+10 0.95 539.13 01-MAY-00:03 0.95
June 0.139742E+10 0.95 539.13 01-JUN-00:10 0.95
July 0.144401E+10 0.95 539.13 01-JUL-00:10 0.95
August 0.144401E+10 0.94 539.13 01-AUG-00:03 0.95
September 0.139742E+10 0.95 539.13 01-SEP-00:03 0.95
October 0.144401E+10 0.95 539.13 01-OCT-00:10 0.95
November 0.139742E+10 0.95 539.13 01-NOV-00:10 0.95
December 0.144401E+10 0.95 539.13 01-DEC-00:10 0.95
           
Annual Sum or Average 0.170020E+11 0.95      
Minimum of Months 0.130426E+10 0.94 539.13   0.95
Maximum of Months 0.144401E+10 0.95 539.13   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137309E+11 0.95 5126.53 01-JAN-00:05 0.95
February 0.124021E+11 0.95 5126.53 01-FEB-00:10 0.95
March 0.137309E+11 0.95 5126.53 01-MAR-00:10 0.95
April 0.132880E+11 0.95 5126.53 01-APR-00:10 0.95
May 0.137309E+11 0.95 5126.53 01-MAY-00:03 0.95
June 0.132880E+11 0.95 5126.53 01-JUN-00:10 0.95
July 0.137309E+11 0.95 5126.53 01-JUL-00:10 0.95
August 0.137309E+11 0.94 5126.53 01-AUG-00:03 0.95
September 0.132880E+11 0.94 5126.53 01-SEP-00:03 0.95
October 0.137309E+11 0.95 5126.53 01-OCT-00:10 0.95
November 0.132880E+11 0.95 5126.53 01-NOV-00:10 0.95
December 0.137309E+11 0.95 5126.53 01-DEC-00:10 0.95
           
Annual Sum or Average 0.161670E+12 0.95      
Minimum of Months 0.124021E+11 0.94 5126.53   0.95
Maximum of Months 0.137309E+11 0.95 5126.53   0.95



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.139146E+10 0.95 519.51 01-JAN-00:05 0.94
February 0.125680E+10 0.95 519.51 01-FEB-00:10 0.95
March 0.139146E+10 0.95 519.51 01-MAR-00:10 0.95
April 0.134657E+10 0.95 519.51 01-APR-00:10 0.95
May 0.139146E+10 0.95 519.51 01-MAY-00:03 0.95
June 0.134657E+10 0.95 519.51 01-JUN-00:10 0.95
July 0.139146E+10 0.95 519.51 01-JUL-00:10 0.95
August 0.139146E+10 0.94 519.51 01-AUG-00:03 0.95
September 0.134657E+10 0.94 519.51 01-SEP-00:03 0.95
October 0.139146E+10 0.95 519.51 01-OCT-00:10 0.95
November 0.134657E+10 0.95 519.51 01-NOV-00:10 0.95
December 0.139146E+10 0.95 519.51 01-DEC-00:10 0.95
           
Annual Sum or Average 0.163833E+11 0.95      
Minimum of Months 0.125680E+10 0.94 519.51   0.94
Maximum of Months 0.139146E+10 0.95 519.51   0.95



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.795334E+09 0.715800E+09 4718.11 02-JAN-06:02 4246.30 4246.30 46.47 9.77
February 0.405465E+09 0.364919E+09 4693.46 13-FEB-06:02 4224.12 4224.12 48.51 9.60
March 29174747.65 26257272.88 3604.58 22-MAR-05:02 3244.12 3244.12 35.64 5.42
April 16870006.85 15183006.17 1664.42 06-APR-05:03 1497.98 1497.98 38.83 1.94
May 12384457.20 11146011.48 555.89 15-MAY-16:30 500.30 500.30 58.00 0.58
June 4455043.06 4009538.75 440.78 03-JUN-12:10 396.70 396.70 48.92 0.46
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 52.61 0.00
August 355743.18 320168.86 231.64 25-AUG-13:50 208.48 208.48 47.54 0.24
September 1839185.75 1655267.17 291.77 15-SEP-11:40 262.60 262.60 52.23 0.30
October 13023565.29 11721208.76 2178.86 26-OCT-05:03 1960.98 1960.98 31.18 2.68
November 84364851.98 75928366.79 3642.60 25-NOV-06:01 3278.34 3278.34 35.21 5.52
December 0.316278E+09 0.284650E+09 3745.62 26-DEC-06:01 3371.06 3371.06 45.17 5.77
                 
Annual Sum or Average 0.167954E+10 0.151159E+10            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 31.18 0.00
Maximum of Months 0.795334E+09 0.715800E+09 4718.11   4246.30 4246.30 58.00 9.77



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 5783257.05 5204931.35 290.17 31-JAN-15:50 261.15 261.15 8.40 16.29
February 28523948.20 25671553.38 521.20 21-FEB-14:40 469.08 469.08 8.49 22.04
March 0.173163E+09 0.155847E+09 6031.06 30-MAR-05:02 5427.96 5427.96 8.41 67.68
April 0.601778E+09 0.541600E+09 9176.40 03-APR-05:02 8258.76 8258.76 8.58 80.61
May 0.933710E+09 0.840339E+09 24984.43 30-MAY-05:02 22485.99 22485.99 8.31 120.52
June 0.152702E+10 0.137432E+10 24984.43 17-JUN-05:02 22485.99 22485.99 8.20 120.52
July 0.166852E+10 0.150167E+10 24984.43 01-JUL-05:02 22485.99 22485.99 7.86 120.52
August 0.197530E+10 0.177777E+10 24984.43 01-AUG-05:03 22485.99 22485.99 7.60 120.52
September 0.123452E+10 0.111106E+10 24984.43 06-SEP-05:03 22485.99 22485.99 7.98 120.52
October 0.488348E+09 0.439513E+09 24984.43 19-OCT-05:03 22485.99 22485.99 7.92 120.52
November 72702760.17 65432484.15 3252.68 04-NOV-05:03 2927.41 2927.41 8.48 51.92
December 20991178.28 18892060.45 3099.71 13-DEC-06:02 2789.74 2789.74 8.39 50.83
                 
Annual Sum or Average 0.873035E+10 0.785732E+10            
Minimum of Months 5783257.05 5204931.35 290.17   261.15 261.15 7.60 16.29
Maximum of Months 0.197530E+10 0.177777E+10 24984.43   22485.99 22485.99 8.58 120.52



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.486697E+10 0.438027E+10 17196.11 02-JAN-20:10 15476.50 15476.50 8.42 120.52
February 0.778868E+10 0.700981E+10 17196.11 01-FEB-14:30 15476.50 15476.50 8.44 120.52
March 0.158276E+11 0.142449E+11 17196.11 02-MAR-06:03 15476.50 15476.50 8.73 120.52
April 0.245189E+11 0.220670E+11 17196.11 01-APR-05:03 15476.50 15476.50 8.79 120.52
May 0.294296E+11 0.264866E+11 17196.11 01-MAY-00:43 15476.50 15476.50 8.33 120.52
June 0.350969E+11 0.315872E+11 17196.11 01-JUN-03:02 15476.50 15476.50 9.94 120.52
July 0.406922E+11 0.366230E+11 17196.11 01-JUL-01:03 15476.50 15476.50 7.59 120.52
August 0.429564E+11 0.386608E+11 17196.11 01-AUG-00:20 15476.50 15476.50 7.14 120.52
September 0.300139E+11 0.270125E+11 17196.11 01-SEP-00:03 15476.50 15476.50 7.70 120.52
October 0.189482E+11 0.170534E+11 17196.11 01-OCT-12:43 15476.50 15476.50 8.18 120.52
November 0.123450E+11 0.111105E+11 17196.11 01-NOV-05:02 15476.50 15476.50 8.72 120.52
December 0.507250E+10 0.456525E+10 17196.11 01-DEC-04:10 15476.50 15476.50 8.43 120.52
                 
Annual Sum or Average 0.267557E+12 0.240801E+12            
Minimum of Months 0.486697E+10 0.438027E+10 17196.11   15476.50 15476.50 7.14 120.52
Maximum of Months 0.429564E+11 0.386608E+11 17196.11   15476.50 15476.50 9.94 120.52



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.912355E+10 0.821119E+10 3406.34 01-JAN-00:05 3065.71 3065.71 21.58 14.23
February 0.824062E+10 0.741656E+10 3406.34 01-FEB-00:10 3065.71 3065.71 24.33 14.23
March 0.912355E+10 0.821119E+10 3406.34 01-MAR-00:10 3065.71 3065.71 28.08 14.23
April 0.882924E+10 0.794631E+10 3406.34 01-APR-00:10 3065.71 3065.71 30.30 14.23
May 0.912355E+10 0.821119E+10 3406.34 01-MAY-00:03 3065.71 3065.71 22.66 14.23
June 0.882924E+10 0.794631E+10 3406.34 01-JUN-00:10 3065.71 3065.71 30.73 14.23
July 0.912355E+10 0.821119E+10 3406.34 01-JUL-00:10 3065.71 3065.71 36.37 14.23
August 0.912355E+10 0.821119E+10 3406.34 01-AUG-00:03 3065.71 3065.71 43.88 14.23
September 0.882924E+10 0.794631E+10 3406.34 01-SEP-00:03 3065.71 3065.71 27.65 14.23
October 0.912355E+10 0.821119E+10 3406.34 01-OCT-00:10 3065.71 3065.71 26.11 14.23
November 0.882924E+10 0.794631E+10 3406.34 01-NOV-00:10 3065.71 3065.71 27.49 14.23
December 0.912355E+10 0.821119E+10 3406.34 01-DEC-00:10 3065.71 3065.71 29.81 14.23
                 
Annual Sum or Average 0.107422E+12 0.966802E+11            
Minimum of Months 0.824062E+10 0.741656E+10 3406.34   3065.71 3065.71 21.58 14.23
Maximum of Months 0.912355E+10 0.821119E+10 3406.34   3065.71 3065.71 43.88 14.23



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:10 1.79 1.79 55.84 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:03 1.79 1.79 56.51 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:03 1.79 1.79 56.37 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 55.85 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:03 1.79 1.79 57.29 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:02 1.79 1.79 57.19 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:02 1.79 1.79 56.68 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 56.35 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:02 1.79 1.79 56.97 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 56.22 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:02 1.79 1.79 56.09 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:01 1.79 1.79 56.02 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.84 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 57.29 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.600180E+10 0.540162E+10 21229.29 31-JAN-15:50 19106.37 19106.37 22.81 70.64
February 0.963765E+10 0.867389E+10 42456.25 28-FEB-13:50 38210.62 38210.62 22.72 141.27
March 0.197439E+11 0.177695E+11 42541.49 30-MAR-15:20 38287.34 38287.34 25.44 141.27
April 0.318139E+11 0.286325E+11 42550.65 14-APR-13:40 38295.58 38295.58 25.70 141.27
May 0.401615E+11 0.361454E+11 42646.99 31-MAY-13:10 38382.30 38382.30 28.39 141.27
June 0.557542E+11 0.501788E+11 42661.81 12-JUN-10:50 38395.63 38395.63 28.87 141.27
July 0.647497E+11 0.582747E+11 42661.81 05-JUL-08:50 38395.63 38395.63 28.85 141.27
August 0.704261E+11 0.633835E+11 42661.81 01-AUG-09:10 38395.63 38395.63 28.86 141.27
September 0.435450E+11 0.391905E+11 42661.81 06-SEP-11:20 38395.63 38395.63 28.84 141.27
October 0.249942E+11 0.224948E+11 42652.69 18-OCT-14:50 38387.42 38387.42 28.55 141.27
November 0.152080E+11 0.136872E+11 21244.27 02-NOV-14:00 19119.84 19119.84 23.79 70.64
December 0.624414E+10 0.561973E+10 21240.40 12-DEC-14:30 19116.36 19116.36 23.54 70.64
                 
Annual Sum or Average 0.388280E+12 0.349452E+12            
Minimum of Months 0.600180E+10 0.540162E+10 21229.29   19106.37 19106.37 22.72 70.64
Maximum of Months 0.704261E+11 0.633835E+11 42661.81   38395.63 38395.63 28.87 141.27



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 29.35 29.35 60434.67 1447838.50 09-JAN-05:11
February 0.00 0.00 01-FEB-00:10 23.21 23.21 35338.19 1344776.36 13-FEB-06:02
March 0.00 0.00 01-MAR-00:10 24.63 24.63 2524.07 1006500.73 22-MAR-05:02
April 0.00 0.00 01-APR-00:10 38.23 38.23 1084.06 341710.33 06-APR-05:03
May 0.00 0.00 01-MAY-00:03 30.79 30.79 598.97 89008.22 15-MAY-14:30
June 0.00 0.00 01-JUN-00:10 43.74 43.74 248.67 58616.52 03-JUN-12:10
July 0.00 0.00 01-JUL-00:10 52.61 52.61 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:03 52.61 52.61 17.08 31714.74 25-AUG-13:50
September 0.00 0.00 01-SEP-00:03 46.26 46.26 94.91 38132.10 15-SEP-11:30
October 0.00 0.00 01-OCT-00:10 48.03 48.03 1102.84 554987.01 26-OCT-05:03
November 0.00 0.00 01-NOV-00:10 23.64 23.64 7317.63 1055402.22 25-NOV-06:01
December 0.00 0.00 01-DEC-00:10 27.56 27.56 25529.58 1113833.05 19-DEC-05:01
                 
Annual Sum or Average 0.00         11091.10    
Minimum of Months 0.00 0.00   23.21 23.21 0.00 0.00  
Maximum of Months 0.00 0.00   52.61 52.61 60434.67 1447838.50  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 14466.85 882681.69 31-JAN-15:50 9.43 8.55 0.00 0.00 01-JAN-00:05
February 62750.26 1508846.61 28-FEB-13:50 9.99 8.37 142.72 306955.44 27-FEB-04:03
March 174801.26 1646732.98 30-MAR-15:00 9.96 6.70 350.03 399817.66 12-MAR-10:33
April 340346.10 1884326.35 12-APR-15:15 10.43 6.70 17.07 43644.13 21-APR-01:33
May 580012.35 2249250.44 31-MAY-03:02 12.03 7.57 281.97 513766.82 21-MAY-07:00
June 813731.86 3030079.59 19-JUN-05:04 13.56 7.88 12.78 54797.57 10-JUN-04:23
July 867450.84 3069080.28 27-JUL-05:04 13.47 7.79 0.00 0.00 01-JUL-00:10
August 931164.66 2953074.30 21-AUG-05:03 13.29 7.61 0.00 0.00 01-AUG-00:03
September 655782.00 2965878.55 27-SEP-05:04 13.16 7.48 16.92 68882.67 24-SEP-07:50
October 294311.90 2320177.88 19-OCT-05:03 12.17 7.57 107.40 243817.51 08-OCT-08:33
November 122353.26 1355300.44 02-NOV-14:00 9.89 8.55 15.45 79219.79 12-NOV-11:25
December 33522.91 1219927.41 12-DEC-14:30 9.70 8.49 0.00 6.60 11-DEC-10:50
                 
Annual Sum or Average 409564.54         78.86    
Minimum of Months 14466.85 882681.69   9.43 6.70 0.00 0.00  
Maximum of Months 931164.66 3069080.28   13.56 8.55 350.03 513766.82  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 7120.81 594503.42 31-JAN-15:50 15.42 8.53 0.00 0.00 01-JAN-00:05
February 35780.17 1011888.73 28-FEB-15:00 17.82 7.94 0.00 0.00 01-FEB-00:10
March 109266.45 2141393.08 30-MAR-05:02 14.26 8.72 0.00 0.00 01-MAR-00:10
April 238579.43 2584505.02 03-APR-05:02 14.36 8.78 0.00 0.00 01-APR-00:10
May 435044.85 3893658.61 31-MAY-05:03 14.42 7.76 0.00 0.00 01-MAY-00:03
June 650685.22 4191087.77 19-JUN-05:02 15.01 7.99 0.00 0.00 01-JUN-00:10
July 702394.14 4171395.81 12-JUL-05:02 14.97 7.69 0.00 0.00 01-JUL-00:10
August 776922.98 4210553.97 21-AUG-05:02 15.05 7.53 0.00 0.00 01-AUG-00:03
September 511150.10 4114055.27 27-SEP-05:02 14.87 7.66 0.00 0.00 01-SEP-00:03
October 216373.99 4114279.78 18-OCT-05:02 14.96 7.75 0.00 0.00 01-OCT-00:10
November 71086.92 1669757.19 04-NOV-05:03 14.38 8.84 0.00 0.00 01-NOV-00:10
December 19075.28 1501761.83 13-DEC-06:02 13.76 8.65 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 316161.78         0.00    
Minimum of Months 7120.81 594503.42   13.76 7.53 0.00 0.00  
Maximum of Months 776922.98 4210553.97   17.82 8.84 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 165148.21 414570.76 31-JAN-15:00 26.68 22.80 0.00 0.00 01-JAN-00:05
February 338663.45 850011.15 28-FEB-15:00 35.31 28.17 0.00 0.00 01-FEB-00:10
March 574133.53 1239520.52 30-MAR-16:00 42.91 32.49 0.00 0.00 01-MAR-00:10
April 884583.09 1511506.08 17-APR-16:00 48.15 34.91 0.00 0.00 01-APR-00:10
May 433619.98 952749.36 30-MAY-15:00 37.32 32.67 0.00 0.00 01-MAY-00:03
June 849617.20 1396340.91 06-JUN-15:00 45.94 37.99 0.00 0.00 01-JUN-00:10
July 1140769.59 1758471.85 08-JUL-15:50 52.87 41.77 0.00 0.00 01-JUL-00:10
August 1385568.67 1862827.06 01-AUG-16:10 54.86 41.24 0.00 0.00 01-AUG-00:03
September 514650.11 1026578.05 07-SEP-16:00 38.77 33.88 0.00 0.00 01-SEP-00:03
October 467725.01 1149791.38 10-OCT-16:00 41.17 33.46 0.00 0.00 01-OCT-00:10
November 538333.52 1029654.53 05-NOV-16:00 38.83 28.86 0.00 0.00 01-NOV-00:10
December 617063.81 1172165.01 12-DEC-14:50 41.60 28.63 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 661378.05         0.00    
Minimum of Months 165148.21 414570.76   26.68 22.80 0.00 0.00  
Maximum of Months 1385568.67 1862827.06   54.86 41.77 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.25 57.25 14860.84 49715.31 27-JAN-12:10
February 0.00 0.00 01-FEB-00:10 57.09 57.09 14971.71 49710.31 03-FEB-12:10
March 0.00 0.00 01-MAR-00:10 57.05 57.05 15328.54 48925.30 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 56.53 56.53 13623.22 46292.28 03-APR-11:50
May 0.00 0.00 01-MAY-00:03 58.03 58.03 13024.31 43160.48 01-MAY-11:40
June 0.00 0.00 01-JUN-00:10 57.58 57.58 12356.56 39661.64 01-JUN-12:00
July 0.00 0.00 01-JUL-00:10 57.03 57.03 10969.00 36987.88 03-JUL-11:50
August 0.00 0.00 01-AUG-00:03 56.76 56.76 11840.02 36824.80 31-AUG-11:50
September 0.00 0.00 01-SEP-00:03 57.33 57.33 11664.09 39111.39 29-SEP-11:50
October 0.00 0.00 01-OCT-00:10 57.07 57.07 12487.35 42654.03 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 56.69 56.69 13634.79 46040.42 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 56.45 56.45 14030.37 48551.78 29-DEC-12:30
                 
Annual Sum or Average 0.00         13222.80    
Minimum of Months 0.00 0.00   56.45 56.45 10969.00 36824.80  
Maximum of Months 0.00 0.00   58.03 58.03 15328.54 49715.31  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 7457.07 504313.19 31-JAN-15:50 22.81 21.10 2310.65 173961.99 09-JAN-21:00
February 36895.80 1058739.34 28-FEB-14:40 24.69 21.10 2300.95 174184.69 03-FEB-09:40
March 109340.66 2563449.70 30-MAR-15:20 25.44 21.69 1473.48 132435.62 03-MAR-06:40
April 251384.94 2715103.50 14-APR-13:40 25.70 21.14 1357.07 110231.86 05-APR-12:20
May 541015.81 4306928.27 31-MAY-13:10 28.39 25.13 133.80 85477.65 10-MAY-09:40
June 1381389.15 5131268.06 23-JUN-11:30 29.79 26.78 94.04 43844.64 10-JUN-07:40
July 1737573.24 5619194.52 07-JUL-12:00 30.62 27.50 0.03 422.23 03-JUL-02:50
August 2100976.41 5663660.44 10-AUG-16:00 30.69 27.53 0.00 0.00 01-AUG-00:03
September 901980.43 5054320.31 06-SEP-12:30 29.66 26.46 68.71 43914.50 18-SEP-07:00
October 290072.46 4400736.21 18-OCT-14:50 28.55 25.60 885.58 115272.57 31-OCT-08:70
November 72910.83 793620.75 02-NOV-14:00 23.79 21.10 1499.55 140381.52 21-NOV-10:00
December 18899.85 718967.06 12-DEC-14:30 23.54 21.10 2018.04 139477.74 01-DEC-18:30
                 
Annual Sum or Average 625283.41         1004.05    
Minimum of Months 7457.07 504313.19   22.81 21.10 0.00 0.00  
Maximum of Months 2100976.41 5663660.44   30.69 27.53 2310.65 174184.69  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.202417E+10 0.00 0.170240E+10 0.356414E+10 0.00 0.00
February 0.784093E+09 0.00 0.785620E+10 0.433061E+10 0.00 0.00
March 35274343.56 0.00 0.254286E+11 0.767553E+10 0.00 0.00
April 0.175875E+09 0.00 0.561150E+11 0.938364E+10 0.00 0.00
May 0.169921E+09 0.00 0.885510E+11 0.909031E+10 0.00 0.00
June 63518557.51 0.00 0.136427E+12 0.119894E+11 0.00 0.00
July 0.00 0.00 0.162383E+12 0.134700E+11 0.00 0.00
August 6111848.72 0.00 0.187957E+12 0.160127E+11 0.00 0.00
September 36965580.39 0.00 0.102888E+12 0.921447E+10 0.00 0.00
October 10092401.14 0.00 0.476811E+11 0.769767E+10 0.00 0.00
November 98002371.97 0.00 0.174501E+11 0.660860E+10 0.00 0.00
December 0.296415E+09 0.00 0.533743E+10 0.569872E+10 0.00 0.00
             
Annual Sum or Average 0.370044E+10 0.00 0.839776E+12 0.104736E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.170240E+10 0.356414E+10 0.00 0.00
Maximum of Months 0.202417E+10 0.00 0.187957E+12 0.160127E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.128031E+12 0.00 0.118183E+11 0.284738E+11 0.00 0.00
February 0.668931E+11 0.00 0.559120E+11 0.297868E+11 0.00 0.00
March 0.428558E+10 0.00 0.183385E+12 0.457422E+11 0.00 0.00
April 0.201517E+10 0.00 0.396528E+12 0.565879E+11 0.00 0.00
May 0.122654E+10 0.00 0.767148E+12 0.749326E+11 0.00 0.00
June 0.500462E+09 0.00 0.114664E+13 0.955653E+11 0.00 0.00
July 0.00 0.00 0.128866E+13 0.968440E+11 0.00 0.00
August 74084950.93 0.00 0.143588E+13 0.106313E+12 0.00 0.00
September 0.187217E+09 0.00 0.876085E+12 0.726036E+11 0.00 0.00
October 0.159871E+10 0.00 0.361363E+12 0.490119E+11 0.00 0.00
November 0.134537E+11 0.00 0.111274E+12 0.355018E+11 0.00 0.00
December 0.507914E+11 0.00 0.296407E+11 0.295779E+11 0.00 0.00
             
Annual Sum or Average 0.269057E+12 0.00 0.666433E+13 0.720941E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.118183E+11 0.284738E+11 0.00 0.00
Maximum of Months 0.128031E+12 0.00 0.143588E+13 0.106313E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.333700E+11 0.00 0.112782E+10 0.357151E+10 0.00 0.00
February 0.185911E+11 0.00 0.482683E+10 0.308474E+10 0.00 0.00
March 0.242929E+10 0.00 0.175328E+11 0.381160E+10 0.00 0.00
April 0.685294E+09 0.00 0.408191E+11 0.497345E+10 0.00 0.00
May 0.159757E+09 0.00 0.835939E+11 0.749167E+10 0.00 0.00
June 40203974.90 0.00 0.128479E+12 0.103844E+11 0.00 0.00
July 0.00 0.00 0.144977E+12 0.108445E+11 0.00 0.00
August 0.00 0.00 0.159690E+12 0.117710E+11 0.00 0.00
September 15135538.97 0.00 0.909157E+11 0.708533E+10 0.00 0.00
October 0.149974E+10 0.00 0.352155E+11 0.418426E+10 0.00 0.00
November 0.556483E+10 0.00 0.930220E+10 0.293994E+10 0.00 0.00
December 0.179504E+11 0.00 0.253367E+10 0.319839E+10 0.00 0.00
             
Annual Sum or Average 0.803057E+11 0.00 0.719013E+12 0.733407E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.112782E+10 0.293994E+10 0.00 0.00
Maximum of Months 0.333700E+11 0.00 0.159690E+12 0.117710E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.524622E+09 0.137451E+11 0.00 0.00
February 0.00 0.00 0.390557E+10 0.122097E+11 0.00 0.00
March 0.00 0.00 0.121630E+11 0.145307E+11 0.00 0.00
April 0.00 0.00 0.257121E+11 0.132819E+11 0.00 0.00
May 0.00 0.00 0.468085E+11 0.141596E+11 0.00 0.00
June 0.00 0.00 0.815630E+11 0.143969E+11 0.00 0.00
July 0.00 0.00 0.942548E+11 0.141279E+11 0.00 0.00
August 0.00 0.00 0.113944E+12 0.156946E+11 0.00 0.00
September 0.00 0.00 0.697246E+11 0.149472E+11 0.00 0.00
October 0.00 0.00 0.307473E+11 0.149692E+11 0.00 0.00
November 0.00 0.00 0.980654E+10 0.144858E+11 0.00 0.00
December 0.00 0.00 0.280578E+10 0.140258E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.491960E+12 0.170574E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.524622E+09 0.122097E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.113944E+12 0.156946E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.402644E+12 0.180996E+12 0.00 0.97
February 0.00 0.00 0.637369E+12 0.214440E+12 0.00 0.68
March 0.00 0.00 0.101817E+13 0.298509E+12 0.00 0.35
April 0.00 0.00 0.129587E+13 0.361014E+12 0.00 0.11
May 0.00 0.00 0.437051E+12 0.195031E+12 0.00 0.02
June 0.00 0.00 0.752133E+12 0.274930E+12 0.00 0.01
July 0.00 0.00 0.111141E+13 0.369773E+12 0.00 0.00
August 0.00 0.00 0.142712E+13 0.445315E+12 0.00 0.00
September 0.00 0.00 0.437127E+12 0.194859E+12 0.00 0.00
October 0.00 0.00 0.733328E+12 0.247864E+12 0.00 0.02
November 0.00 0.00 0.987761E+12 0.286361E+12 0.00 0.45
December 0.00 0.00 0.130263E+13 0.338026E+12 0.00 0.72
             
Annual Sum or Average 0.00 0.00 0.105426E+14 0.340712E+13 0.00 3.33
Minimum of Months 0.00 0.00 0.402644E+12 0.180996E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.142712E+13 0.445315E+12 0.00 0.97



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.477713E+10 0.245316E+10 0.00 0.00
February 0.00 0.00 0.108253E+11 0.346850E+10 0.00 0.00
March 0.00 0.00 0.193914E+11 0.525937E+10 0.00 0.00
April 0.00 0.00 0.253660E+11 0.656923E+10 0.00 0.00
May 0.00 0.00 0.776953E+10 0.315966E+10 0.00 0.00
June 0.00 0.00 0.145467E+11 0.483748E+10 0.00 0.00
July 0.00 0.00 0.219642E+11 0.673621E+10 0.00 0.00
August 0.00 0.00 0.288366E+11 0.842901E+10 0.00 0.00
September 0.00 0.00 0.782687E+10 0.317571E+10 0.00 0.00
October 0.00 0.00 0.135174E+11 0.418894E+10 0.00 0.00
November 0.00 0.00 0.185939E+11 0.500901E+10 0.00 0.00
December 0.00 0.00 0.247393E+11 0.603408E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.198154E+12 0.593204E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.477713E+10 0.245316E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.288366E+11 0.842901E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.176859E+11 0.176658E+11 0.00 0.00
February 0.00 0.00 0.828432E+11 0.292356E+11 0.00 0.00
March 0.00 0.00 0.175594E+12 0.484977E+11 0.00 0.00
April 0.00 0.00 0.238414E+12 0.620164E+11 0.00 0.00
May 0.00 0.00 0.710283E+11 0.294809E+11 0.00 0.00
June 0.00 0.00 0.137925E+12 0.459258E+11 0.00 0.00
July 0.00 0.00 0.209299E+12 0.641620E+11 0.00 0.00
August 0.00 0.00 0.274053E+12 0.801258E+11 0.00 0.00
September 0.00 0.00 0.710662E+11 0.295073E+11 0.00 0.00
October 0.00 0.00 0.119487E+12 0.381898E+11 0.00 0.00
November 0.00 0.00 0.162967E+12 0.452261E+11 0.00 0.00
December 0.00 0.00 0.211155E+12 0.534250E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.177152E+13 0.543458E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.176859E+11 0.176658E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.274053E+12 0.801258E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.713289E+09 0.155053E+10 0.00 0.00
February 0.00 0.00 0.670960E+10 0.263593E+10 0.00 0.00
March 0.00 0.00 0.165657E+11 0.469789E+10 0.00 0.00
April 0.00 0.00 0.233968E+11 0.615219E+10 0.00 0.00
May 0.00 0.00 0.702907E+10 0.295753E+10 0.00 0.00
June 0.00 0.00 0.139008E+11 0.464135E+10 0.00 0.00
July 0.00 0.00 0.210834E+11 0.647767E+10 0.00 0.00
August 0.00 0.00 0.275723E+11 0.807912E+10 0.00 0.00
September 0.00 0.00 0.697559E+10 0.294682E+10 0.00 0.00
October 0.00 0.00 0.110464E+11 0.367549E+10 0.00 0.00
November 0.00 0.00 0.147349E+11 0.426611E+10 0.00 0.00
December 0.00 0.00 0.189093E+11 0.499150E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.168637E+12 0.530721E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.713289E+09 0.155053E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.275723E+11 0.807912E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.356414E+10 0.170240E+10 0.202417E+10 0.108784E+11 0.00 0.00 0.00 0.00
February 0.433061E+10 0.785620E+10 0.784093E+09 0.504810E+10 0.00 0.00 0.00 0.00
March 0.767553E+10 0.254286E+11 35274343.56 0.240749E+09 72603532.83 0.00 0.00 0.00
April 0.938364E+10 0.561150E+11 0.175875E+09 85007638.92 0.309499E+09 0.00 0.00 0.00
May 0.909031E+10 0.885510E+11 0.169921E+09 0.00 0.226852E+10 0.00 0.00 0.00
June 0.119894E+11 0.136427E+12 63518557.51 0.00 0.139632E+11 0.00 0.00 0.00
July 0.134700E+11 0.162383E+12 0.00 0.00 0.193092E+11 0.00 0.00 0.00
August 0.160127E+11 0.187957E+12 6111848.72 0.00 0.239443E+11 0.00 0.00 0.00
September 0.921447E+10 0.102888E+12 36965580.39 0.00 0.654405E+10 0.00 0.00 0.00
October 0.769767E+10 0.476811E+11 10092401.14 40220366.28 0.125001E+10 0.00 0.00 0.00
November 0.660860E+10 0.174501E+11 98002371.97 0.674707E+09 0.00 0.00 0.00 0.00
December 0.569872E+10 0.533743E+10 0.296415E+09 0.169100E+10 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104736E+12 0.839776E+12 0.370044E+10 0.186582E+11 0.676613E+11 0.00 0.00 0.00
Minimum of Months 0.356414E+10 0.170240E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.160127E+11 0.187957E+12 0.202417E+10 0.108784E+11 0.239443E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.284738E+11 0.118183E+11 0.128031E+12 0.158186E+12 0.00 0.00 0.00 0.00
February 0.297868E+11 0.559120E+11 0.668931E+11 0.800600E+11 0.00 0.00 0.00 0.00
March 0.457422E+11 0.183385E+12 0.428558E+10 0.803129E+10 0.884921E+09 0.00 0.00 0.00
April 0.565879E+11 0.396528E+12 0.201517E+10 0.202481E+10 0.309601E+10 0.00 0.00 0.00
May 0.749326E+11 0.767148E+12 0.122654E+10 0.00 0.229061E+11 0.00 0.00 0.00
June 0.955653E+11 0.114664E+13 0.500462E+09 0.00 0.139543E+12 0.00 0.00 0.00
July 0.968440E+11 0.128866E+13 0.00 0.00 0.193590E+12 0.00 0.00 0.00
August 0.106313E+12 0.143588E+13 74084950.93 0.00 0.237281E+12 0.00 0.00 0.00
September 0.726036E+11 0.876085E+12 0.187217E+09 0.00 0.668723E+11 0.00 0.00 0.00
October 0.490119E+11 0.361363E+12 0.159871E+10 0.170645E+10 0.127560E+11 0.00 0.00 0.00
November 0.355018E+11 0.111274E+12 0.134537E+11 0.168668E+11 0.00 0.00 0.00 0.00
December 0.295779E+11 0.296407E+11 0.507914E+11 0.457395E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.720941E+12 0.666433E+13 0.269057E+12 0.312615E+12 0.676928E+12 0.00 0.00 0.00
Minimum of Months 0.284738E+11 0.118183E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106313E+12 0.143588E+13 0.128031E+12 0.158186E+12 0.237281E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.357151E+10 0.112782E+10 0.333700E+11 0.184142E+11 0.00 0.00 0.00 0.00
February 0.308474E+10 0.482683E+10 0.185911E+11 0.974114E+10 0.00 0.00 0.00 0.00
March 0.381160E+10 0.175328E+11 0.242929E+10 0.173055E+10 54157340.04 0.00 0.00 0.00
April 0.497345E+10 0.408191E+11 0.685294E+09 0.422301E+09 0.155662E+09 0.00 0.00 0.00
May 0.749167E+10 0.835939E+11 0.159757E+09 5495175.88 0.170633E+10 0.00 0.00 0.00
June 0.103844E+11 0.128479E+12 40203974.90 0.00 0.128936E+11 0.00 0.00 0.00
July 0.108445E+11 0.144977E+12 0.00 0.00 0.182250E+11 0.00 0.00 0.00
August 0.117710E+11 0.159690E+12 0.00 0.00 0.225355E+11 0.00 0.00 0.00
September 0.708533E+10 0.909157E+11 15135538.97 0.00 0.616428E+10 0.00 0.00 0.00
October 0.418426E+10 0.352155E+11 0.149974E+10 0.605969E+09 0.928586E+09 0.00 0.00 0.00
November 0.293994E+10 0.930220E+10 0.556483E+10 0.333146E+10 0.00 0.00 0.00 0.00
December 0.319839E+10 0.253367E+10 0.179504E+11 0.669223E+10 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.733407E+11 0.719013E+12 0.803057E+11 0.409434E+11 0.626631E+11 0.00 0.00 0.00
Minimum of Months 0.293994E+10 0.112782E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117710E+11 0.159690E+12 0.333700E+11 0.184142E+11 0.225355E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.137451E+11 0.524622E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122097E+11 0.390557E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145307E+11 0.121630E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132819E+11 0.257121E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141596E+11 0.468085E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143969E+11 0.815630E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141279E+11 0.942548E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.156946E+11 0.113944E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.149472E+11 0.697246E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149692E+11 0.307473E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144858E+11 0.980654E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140258E+11 0.280578E+10 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170574E+12 0.491960E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122097E+11 0.524622E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.156946E+11 0.113944E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.973018E+11 0.321566E+12 0.00 0.00 0.00 0.260401E+10 0.00 0.00
February 0.878855E+11 0.512648E+12 0.00 0.00 0.00 0.182576E+10 0.00 0.00
March 0.973018E+11 0.817896E+12 0.00 0.00 0.00 0.932644E+09 0.00 0.00
April 0.941630E+11 0.102932E+13 0.00 0.00 0.00 0.299386E+09 0.00 0.00
May 0.973018E+11 0.339373E+12 0.00 0.00 0.00 52058897.30 0.00 0.00
June 0.941630E+11 0.571381E+12 0.00 0.00 0.00 14673295.88 0.00 0.00
July 0.973018E+11 0.838942E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.973018E+11 0.107911E+13 0.00 0.00 0.00 1028838.92 0.00 0.00
September 0.941630E+11 0.336431E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.973018E+11 0.582806E+12 0.00 0.00 0.00 40943319.31 0.00 0.00
November 0.941630E+11 0.796779E+12 0.00 0.00 0.00 0.121003E+10 0.00 0.00
December 0.973018E+11 0.106384E+13 0.00 0.00 0.00 0.192510E+10 0.00 0.00
                 
Annual Sum or Average 0.114565E+13 0.829009E+13 0.00 0.00 0.00 0.890564E+10 0.00 0.00
Minimum of Months 0.878855E+11 0.321566E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.973018E+11 0.107911E+13 0.00 0.00 0.00 0.260401E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.144401E+10 0.376797E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130426E+10 0.866105E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144401E+10 0.155761E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139742E+10 0.201942E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144401E+10 0.605388E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139742E+10 0.111066E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144401E+10 0.166720E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144401E+10 0.218516E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139742E+10 0.604858E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144401E+10 0.107725E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139742E+10 0.149824E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144401E+10 0.201492E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170020E+11 0.155836E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130426E+10 0.376797E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144401E+10 0.218516E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.137309E+11 0.137511E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124021E+11 0.660097E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137309E+11 0.140827E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132880E+11 0.189686E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137309E+11 0.552783E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132880E+11 0.105287E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137309E+11 0.158868E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137309E+11 0.207658E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132880E+11 0.548468E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137309E+11 0.950277E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132880E+11 0.131029E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137309E+11 0.171461E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.161670E+12 0.138973E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124021E+11 0.137511E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137309E+11 0.207658E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.139146E+10 0.554213E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125680E+10 0.533047E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139146E+10 0.132592E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134657E+10 0.185912E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139146E+10 0.546299E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134657E+10 0.106060E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139146E+10 0.159972E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139146E+10 0.208846E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134657E+10 0.537534E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139146E+10 0.876240E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134657E+10 0.118154E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139146E+10 0.153093E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163833E+11 0.131948E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125680E+10 0.554213E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139146E+10 0.208846E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.356414E+10 0.202417E+10 0.170240E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.433061E+10 0.784093E+09 0.785620E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.767553E+10 35274343.56 0.254286E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.938364E+10 0.175875E+09 0.561150E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.909031E+10 0.169921E+09 0.885510E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.119894E+11 63518557.51 0.136427E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.134700E+11 0.00 0.162383E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.160127E+11 6111848.72 0.187957E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.921447E+10 36965580.39 0.102888E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.769767E+10 10092401.14 0.476811E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.660860E+10 98002371.97 0.174501E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.569872E+10 0.296415E+09 0.533743E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.104736E+12 0.370044E+10 0.839776E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.356414E+10 0.00 0.170240E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.160127E+11 0.202417E+10 0.187957E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.284738E+11 0.128031E+12 0.118183E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.297868E+11 0.668931E+11 0.559120E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.457422E+11 0.428558E+10 0.183385E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.565879E+11 0.201517E+10 0.396528E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.749326E+11 0.122654E+10 0.767148E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.955653E+11 0.500462E+09 0.114664E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.968440E+11 0.00 0.128866E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.106313E+12 74084950.93 0.143588E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.726036E+11 0.187217E+09 0.876085E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.490119E+11 0.159871E+10 0.361363E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.355018E+11 0.134537E+11 0.111274E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.295779E+11 0.507914E+11 0.296407E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.720941E+12 0.269057E+12 0.666433E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.284738E+11 0.00 0.118183E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106313E+12 0.128031E+12 0.143588E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.357151E+10 0.333700E+11 0.112782E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.308474E+10 0.185911E+11 0.482683E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.381160E+10 0.242929E+10 0.175328E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.497345E+10 0.685294E+09 0.408191E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.749167E+10 0.159757E+09 0.835939E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.103844E+11 40203974.90 0.128479E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.108445E+11 0.00 0.144977E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.117710E+11 0.00 0.159690E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.708533E+10 15135538.97 0.909157E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.418426E+10 0.149974E+10 0.352155E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.293994E+10 0.556483E+10 0.930220E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.319839E+10 0.179504E+11 0.253367E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.733407E+11 0.803057E+11 0.719013E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.293994E+10 0.00 0.112782E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117710E+11 0.333700E+11 0.159690E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.137451E+11 0.00 0.524622E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122097E+11 0.00 0.390557E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145307E+11 0.00 0.121630E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132819E+11 0.00 0.257121E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141596E+11 0.00 0.468085E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143969E+11 0.00 0.815630E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141279E+11 0.00 0.942548E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.156946E+11 0.00 0.113944E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.149472E+11 0.00 0.697246E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.149692E+11 0.00 0.307473E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.144858E+11 0.00 0.980654E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.140258E+11 0.00 0.280578E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.170574E+12 0.00 0.491960E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122097E+11 0.00 0.524622E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.156946E+11 0.00 0.113944E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.973018E+11 0.00 0.402644E+12 0.00 0.810783E+11 0.00 0.00 0.00 0.261573E+10 0.00 0.00 0.00
February 0.878855E+11 0.00 0.637369E+12 0.00 0.124720E+12 0.00 0.00 0.00 0.183398E+10 0.00 0.00 0.00
March 0.973018E+11 0.00 0.101817E+13 0.00 0.200271E+12 0.00 0.00 0.00 0.936842E+09 0.00 0.00 0.00
April 0.941630E+11 0.00 0.129587E+13 0.00 0.266550E+12 0.00 0.00 0.00 0.300734E+09 0.00 0.00 0.00
May 0.973018E+11 0.00 0.437051E+12 0.00 0.976773E+11 0.00 0.00 0.00 52293235.50 0.00 0.00 0.00
June 0.941630E+11 0.00 0.752133E+12 0.00 0.180752E+12 0.00 0.00 0.00 14739346.33 0.00 0.00 0.00
July 0.973018E+11 0.00 0.111141E+13 0.00 0.272471E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.973018E+11 0.00 0.142712E+13 0.00 0.348012E+12 0.00 0.00 0.00 1033470.14 0.00 0.00 0.00
September 0.941630E+11 0.00 0.437127E+12 0.00 0.100696E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.973018E+11 0.00 0.733328E+12 0.00 0.150522E+12 0.00 0.00 0.00 41127621.78 0.00 0.00 0.00
November 0.941630E+11 0.00 0.987761E+12 0.00 0.190982E+12 0.00 0.00 0.00 0.121548E+10 0.00 0.00 0.00
December 0.973018E+11 0.00 0.130263E+13 0.00 0.238790E+12 0.00 0.00 0.00 0.193377E+10 0.00 0.00 0.00
                         
Annual Sum or Average 0.114565E+13 0.00 0.105426E+14 0.00 0.225252E+13 0.00 0.00 0.00 0.894573E+10 0.00 0.00 0.00
Minimum of Months 0.878855E+11 0.00 0.402644E+12 0.00 0.810783E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.973018E+11 0.00 0.142712E+13 0.00 0.348012E+12 0.00 0.00 0.00 0.261573E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.144401E+10 0.00 0.477713E+10 0.00 0.100916E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130426E+10 0.00 0.108253E+11 0.00 0.216424E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144401E+10 0.00 0.193914E+11 0.00 0.381536E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.139742E+10 0.00 0.253660E+11 0.00 0.517180E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144401E+10 0.00 0.776953E+10 0.00 0.171565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139742E+10 0.00 0.145467E+11 0.00 0.344005E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144401E+10 0.00 0.219642E+11 0.00 0.529220E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144401E+10 0.00 0.288366E+11 0.00 0.698500E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139742E+10 0.00 0.782687E+10 0.00 0.177828E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144401E+10 0.00 0.135174E+11 0.00 0.274494E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.139742E+10 0.00 0.185939E+11 0.00 0.361159E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144401E+10 0.00 0.247393E+11 0.00 0.459008E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.170020E+11 0.00 0.198154E+12 0.00 0.423184E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130426E+10 0.00 0.477713E+10 0.00 0.100916E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144401E+10 0.00 0.288366E+11 0.00 0.698500E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.137309E+11 0.00 0.176859E+11 0.00 0.393486E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124021E+11 0.00 0.828432E+11 0.00 0.168335E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137309E+11 0.00 0.175594E+12 0.00 0.347668E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132880E+11 0.00 0.238414E+12 0.00 0.487284E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137309E+11 0.00 0.710283E+11 0.00 0.157500E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.132880E+11 0.00 0.137925E+12 0.00 0.326378E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137309E+11 0.00 0.209299E+12 0.00 0.504311E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137309E+11 0.00 0.274053E+12 0.00 0.663949E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.132880E+11 0.00 0.710662E+11 0.00 0.162193E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137309E+11 0.00 0.119487E+12 0.00 0.244589E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132880E+11 0.00 0.162967E+12 0.00 0.319382E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137309E+11 0.00 0.211155E+12 0.00 0.396941E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.161670E+12 0.00 0.177152E+13 0.00 0.381788E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124021E+11 0.00 0.176859E+11 0.00 0.393486E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137309E+11 0.00 0.274053E+12 0.00 0.663949E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.139146E+10 0.00 0.713289E+09 0.00 0.159076E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125680E+10 0.00 0.670960E+10 0.00 0.137913E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139146E+10 0.00 0.165657E+11 0.00 0.330643E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134657E+10 0.00 0.233968E+11 0.00 0.480562E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139146E+10 0.00 0.702907E+10 0.00 0.156608E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134657E+10 0.00 0.139008E+11 0.00 0.329478E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139146E+10 0.00 0.210834E+11 0.00 0.508622E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139146E+10 0.00 0.275723E+11 0.00 0.668766E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134657E+10 0.00 0.697559E+10 0.00 0.160025E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139146E+10 0.00 0.110464E+11 0.00 0.228403E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134657E+10 0.00 0.147349E+11 0.00 0.291953E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139146E+10 0.00 0.189093E+11 0.00 0.360004E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.163833E+11 0.00 0.168637E+12 0.00 0.366888E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125680E+10 0.00 0.713289E+09 0.00 0.159076E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139146E+10 0.00 0.275723E+11 0.00 0.668766E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.159288E+10 0.00 0.00 87602406.50 0.00 0.00 0.597838E+11 0.00 0.59
February 0.425270E+09 280553.54 0.00 80405236.12 0.00 0.00 0.531295E+11 0.00 0.78
March 0.152312E+09 0.100250E+09 0.00 96077802.33 674109.57 0.00 0.593176E+11 0.00 1.14
April 75808715.06 0.297458E+09 0.00 77035003.49 10488370.31 0.00 0.390251E+11 0.00 1.13
May 45002956.71 0.216832E+10 0.00 67971563.76 22429148.25 0.00 0.257484E+11 0.00 1.12
June 39666629.10 0.142419E+11 0.00 30306579.99 74016703.89 0.00 0.731122E+10 0.00 0.64
July 37150147.58 0.212512E+11 0.00 15378411.81 0.235582E+09 0.00 0.268623E+10 0.00 0.44
August 4406445.32 0.284902E+11 0.00 4444981.54 0.194192E+09 0.00 0.777511E+09 0.00 0.39
September 0.161345E+09 0.873760E+10 0.00 56052984.03 75940475.36 0.00 0.174643E+11 0.00 0.90
October 0.199370E+09 0.248696E+10 0.00 0.101016E+09 0.00 0.00 0.520581E+11 0.00 1.09
November 0.274134E+09 3453780.44 0.00 0.120733E+09 0.00 0.00 0.678046E+11 0.00 1.15
December 0.535777E+09 0.00 0.00 0.118626E+09 0.00 0.00 0.690766E+11 0.00 0.85
                   
Annual Sum or Average 0.354313E+10 0.777777E+11 0.00 0.855651E+09 0.613322E+09 0.00 0.454183E+12 0.00 0.85
Minimum of Months 4406445.32 0.00 0.00 4444981.54 0.00 0.00 0.777511E+09 0.00 0.39
Maximum of Months 0.159288E+10 0.284902E+11 0.00 0.120733E+09 0.235582E+09 0.00 0.690766E+11 0.00 1.15



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.577952E+10 0.00 0.00 49298366.04 0.00 0.00 0.337014E+11 0.00 0.41
February 0.312923E+10 0.00 0.00 59510384.25 0.00 0.00 0.361389E+11 0.00 0.58
March 0.404156E+10 53465912.98 0.00 90219594.71 167668.94 0.00 0.477951E+11 0.00 0.90
April 0.664827E+10 0.253601E+09 0.00 75768570.71 6707272.59 0.00 0.319232E+11 0.00 0.97
May 0.175415E+10 0.136639E+10 0.00 52331442.87 27216548.73 0.00 0.147461E+11 0.00 0.72
June 0.120952E+10 0.615682E+10 0.00 16895457.59 74190556.89 0.00 0.461600E+10 0.00 0.44
July 0.248025E+09 0.889354E+10 0.00 3025956.40 0.200514E+09 0.00 0.347078E+09 0.00 0.28
August 0.115340E+09 0.119073E+11 0.00 1929635.20 0.106641E+09 0.00 0.226618E+09 0.00 0.29
September 0.931125E+09 0.450400E+10 0.00 36030532.74 0.138488E+09 0.00 0.102796E+11 0.00 0.58
October 0.182225E+10 0.161262E+10 0.00 71699026.93 0.00 0.00 0.367833E+11 0.00 0.72
November 0.265632E+10 21737316.72 0.00 88409639.13 0.00 0.00 0.482954E+11 0.00 0.80
December 0.195198E+10 0.00 0.00 87611798.90 0.00 0.00 0.499317E+11 0.00 0.63
                   
Annual Sum or Average 0.302873E+11 0.347694E+11 0.00 0.632730E+09 0.553925E+09 0.00 0.314784E+12 0.00 0.61
Minimum of Months 0.115340E+09 0.00 0.00 1929635.20 0.00 0.00 0.226618E+09 0.00 0.28
Maximum of Months 0.664827E+10 0.119073E+11 0.00 90219594.71 0.200514E+09 0.00 0.499317E+11 0.00 0.97



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.201541E+12 0.00 0.00 62679664.16 0.00 0.100794E+10 0.636580E+11 0.00 0.33
February 0.137477E+12 0.00 0.00 0.184560E+09 0.00 0.339594E+09 0.124709E+12 0.00 0.43
March 0.470436E+11 0.359530E+09 0.00 0.528402E+09 0.114785E+09 0.00 0.310456E+12 0.00 0.65
April 0.179738E+11 0.220083E+10 0.00 0.542323E+09 0.130381E+09 0.00 0.238050E+12 0.00 0.69
May 0.114305E+11 0.132258E+11 0.00 0.445944E+09 0.294505E+09 0.00 0.126721E+12 0.00 0.63
June 0.563832E+10 0.598832E+11 0.00 0.156734E+09 0.656783E+09 0.00 0.393372E+11 0.00 0.40
July 0.113419E+10 0.857571E+11 0.00 24613805.63 0.193672E+10 0.00 0.283845E+10 0.00 0.26
August 0.451878E+09 0.113962E+12 0.00 20540678.09 0.105810E+10 0.00 0.234311E+10 0.00 0.28
September 0.908894E+10 0.438769E+11 0.00 0.300899E+09 0.131269E+10 0.00 0.830866E+11 0.00 0.51
October 0.314184E+11 0.145727E+11 0.00 0.434584E+09 0.00 0.00 0.242573E+12 0.00 0.55
November 0.591038E+11 69217034.35 0.00 0.416174E+09 0.364272E+09 0.00 0.264802E+12 0.00 0.54
December 0.139039E+12 0.00 0.00 0.203342E+09 0.00 0.00 0.155015E+12 0.00 0.39
                   
Annual Sum or Average 0.661340E+12 0.333908E+12 0.00 0.332080E+10 0.586823E+10 0.134753E+10 0.165359E+13 0.00 0.47
Minimum of Months 0.451878E+09 0.00 0.00 20540678.09 0.00 0.00 0.234311E+10 0.00 0.26
Maximum of Months 0.201541E+12 0.113962E+12 0.00 0.542323E+09 0.193672E+10 0.100794E+10 0.310456E+12 0.00 0.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.180347E+11 0.00 0.00 879863.71 0.00 0.187539E+10 0.107554E+10 0.00 0.32
February 0.156544E+11 0.00 0.00 6448398.70 0.00 0.667417E+09 0.442828E+10 0.00 0.39
March 0.102430E+11 7889165.29 0.00 29926921.93 9447058.00 1268161.79 0.180772E+11 0.00 0.57
April 0.484095E+10 0.127517E+09 0.00 41682615.61 6321576.08 0.00 0.165416E+11 0.00 0.66
May 0.130204E+10 0.118795E+10 0.00 41689430.48 25842111.98 0.00 0.107999E+11 0.00 0.65
June 0.502277E+09 0.593819E+10 0.00 13535344.49 70415339.57 0.00 0.336103E+10 0.00 0.39
July 0.106645E+09 0.825343E+10 0.00 1895593.13 0.423228E+09 0.00 0.198538E+09 0.00 0.26
August 35503147.26 0.112415E+11 0.00 1895171.25 0.101524E+09 0.00 0.183471E+09 0.00 0.28
September 0.145024E+10 0.420361E+10 0.00 24333592.99 0.207410E+09 0.00 0.618423E+10 0.00 0.48
October 0.813267E+10 0.142486E+10 0.00 22103103.23 0.00 2442945.15 0.129749E+11 0.00 0.48
November 0.142501E+11 0.00 0.00 12935954.27 72294999.14 82086148.14 0.949458E+10 0.00 0.45
December 0.189599E+11 0.00 0.00 4037220.48 0.00 0.609259E+09 0.314929E+10 0.00 0.36
                   
Annual Sum or Average 0.935124E+11 0.323849E+11 0.00 0.201363E+09 0.916484E+09 0.323787E+10 0.864684E+11 0.00 0.44
Minimum of Months 35503147.26 0.00 0.00 879863.71 0.00 0.00 0.183471E+09 0.00 0.26
Maximum of Months 0.189599E+11 0.112415E+11 0.00 41689430.48 0.423228E+09 0.187539E+10 0.180772E+11 0.00 0.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.311376E+10 0.00 0.00 358629.97 0.00 0.427583E+09 0.272618E+09 0.00 0.32
February 0.268193E+10 0.00 0.00 1376066.29 0.00 0.139460E+09 0.778884E+09 0.00 0.44
March 0.199016E+10 7596968.48 0.00 4923558.59 21048.64 0.00 0.274573E+10 0.00 0.71
April 0.146776E+10 37610578.73 0.00 6259006.35 842010.11 0.00 0.244298E+10 0.00 0.89
May 0.386141E+09 0.230586E+09 0.00 5168634.00 3416680.75 0.00 0.144045E+10 0.00 0.76
June 0.198853E+09 0.114768E+10 0.00 2000169.57 9313651.41 0.00 0.509815E+09 0.00 0.57
July 32476113.65 0.167142E+10 0.00 319083.79 25171930.46 0.00 39192759.96 0.00 0.40
August 14908116.09 0.209635E+10 0.00 223497.90 13387339.81 0.00 27122291.73 0.00 0.40
September 0.295928E+09 0.691156E+09 0.00 3153295.93 17385344.39 0.00 0.877330E+09 0.00 0.58
October 0.145148E+10 0.222181E+09 0.00 3179815.66 0.00 0.00 0.188264E+10 0.00 0.55
November 0.213941E+10 107097.10 0.00 3390014.51 1555840.52 261365.03 0.204045E+10 0.00 0.56
December 0.306119E+10 0.00 0.00 1422856.28 0.00 810868.60 0.104278E+10 0.00 0.40
                   
Annual Sum or Average 0.168340E+11 0.610468E+10 0.00 31774628.83 71093846.09 0.568116E+09 0.141000E+11 0.00 0.55
Minimum of Months 14908116.09 0.00 0.00 223497.90 0.00 0.00 27122291.73 0.00 0.32
Maximum of Months 0.311376E+10 0.209635E+10 0.00 6259006.35 25171930.46 0.427583E+09 0.274573E+10 0.00 0.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.237486E+10 0.00 0.00 314102.43 0.00 0.298545E+09 0.268532E+09 0.00 0.38
February 0.197366E+10 0.00 0.00 1549283.94 0.00 76702181.49 0.968854E+09 0.00 0.56
March 0.153935E+10 5109132.42 0.00 4367871.60 16298.54 0.00 0.251546E+10 0.00 0.90
April 0.123747E+10 24944948.61 0.00 5802011.62 651991.52 0.00 0.227757E+10 0.00 1.19
May 0.330070E+09 0.188433E+09 0.00 4882542.13 2645629.60 0.00 0.141269E+10 0.00 1.04
June 0.162198E+09 0.880716E+09 0.00 2031953.94 7211815.69 0.00 0.541677E+09 0.00 0.74
July 31451009.25 0.129617E+10 0.00 137220.09 19491316.04 0.00 20457391.07 0.00 0.47
August 11746552.20 0.149026E+10 0.00 149517.51 10366184.33 0.00 19773895.62 0.00 0.46
September 0.313895E+09 0.555548E+09 0.00 2974072.31 13461948.91 0.00 0.768958E+09 0.00 0.79
October 0.106586E+10 0.149411E+09 0.00 3436499.84 0.00 0.00 0.198373E+10 0.00 0.75
November 0.167231E+10 36751.13 0.00 2536822.94 1239535.78 1815750.42 0.162139E+10 0.00 0.66
December 0.229652E+10 0.00 0.00 990517.18 0.00 37085524.70 0.836100E+09 0.00 0.47
                   
Annual Sum or Average 0.130094E+11 0.459062E+10 0.00 29172415.51 55084720.41 0.414149E+09 0.132352E+11 0.00 0.70
Minimum of Months 11746552.20 0.00 0.00 137220.09 0.00 0.00 19773895.62 0.00 0.38
Maximum of Months 0.237486E+10 0.149026E+10 0.00 5802011.62 19491316.04 0.298545E+09 0.251546E+10 0.00 1.19



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.217616E+10 0.00 0.00 3356084.86 0.00 0.401343E+09 0.249276E+10 0.00 0.41
February 0.195230E+10 0.00 0.00 5360297.49 0.00 0.124693E+09 0.299231E+10 0.00 0.67
March 0.148542E+10 15010944.31 0.00 9590046.18 21070.08 0.00 0.512127E+10 0.00 1.05
April 0.140524E+10 46879423.17 0.00 8587311.17 842867.96 0.00 0.316166E+10 0.00 1.12
May 0.413957E+09 0.262063E+09 0.00 5479363.78 3420161.70 0.00 0.146729E+10 0.00 0.82
June 0.244042E+09 0.116526E+10 0.00 1888876.05 9323140.27 0.00 0.428572E+09 0.00 0.57
July 32382944.54 0.172304E+10 0.00 295797.73 25197575.92 0.00 37605099.72 0.00 0.41
August 13621817.96 0.236183E+10 0.00 243917.97 13400978.99 0.00 29829386.94 0.00 0.46
September 0.311368E+09 0.885143E+09 0.00 4611719.08 17403056.78 0.00 0.110271E+10 0.00 0.78
October 0.107967E+10 0.294618E+09 0.00 8518333.50 0.00 0.00 0.439749E+10 0.00 0.96
November 0.140346E+10 47719.02 0.00 9897782.16 1602421.15 1721649.58 0.531408E+10 0.00 0.94
December 0.198571E+10 0.00 0.00 6751691.66 0.00 57790253.85 0.460160E+10 0.00 0.68
                   
Annual Sum or Average 0.125033E+11 0.675389E+10 0.00 64581221.64 71211272.85 0.585549E+09 0.311472E+11 0.00 0.74
Minimum of Months 13621817.96 0.00 0.00 243917.97 0.00 0.00 29829386.94 0.00 0.41
Maximum of Months 0.217616E+10 0.236183E+10 0.00 9897782.16 25197575.92 0.401343E+09 0.531408E+10 0.00 1.12



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.289308E+10 0.00 0.00 1117817.99 0.00 35721150.55 0.102840E+10 0.00 0.51
February 0.173344E+10 0.00 0.00 3927957.14 0.00 2153707.11 0.241713E+10 0.00 0.82
March 0.480273E+09 14325448.63 0.00 12227009.99 21147.17 0.00 0.622467E+10 0.00 1.62
April 0.518534E+09 54680042.14 0.00 14626040.74 517694.19 0.00 0.531281E+10 0.00 2.09
May 0.233183E+09 0.239575E+09 0.00 6778491.95 1319897.68 0.00 0.181028E+10 0.00 1.32
June 0.112644E+09 0.120666E+10 0.00 2930740.99 6527489.98 0.00 0.703045E+09 0.00 0.99
July 10940623.25 0.187905E+10 0.00 773153.35 17029647.70 0.00 79573833.20 0.00 0.70
August 1161267.88 0.263149E+10 0.00 552011.50 3222925.90 0.00 57649393.91 0.00 0.78
September 0.148031E+09 0.732962E+09 0.00 4311974.24 15061767.29 0.00 0.109969E+10 0.00 1.00
October 0.402375E+09 0.243169E+09 0.00 7456626.41 0.00 0.00 0.391509E+10 0.00 1.14
November 0.646310E+09 2287391.44 0.00 8915131.18 0.00 0.00 0.504139E+10 0.00 1.23
December 0.698294E+09 0.00 0.00 7489165.47 0.00 0.00 0.504931E+10 0.00 0.92
                   
Annual Sum or Average 0.787827E+10 0.700420E+10 0.00 71106120.94 43700569.92 37874857.66 0.327390E+11 0.00 1.09
Minimum of Months 1161267.88 0.00 0.00 552011.50 0.00 0.00 57649393.91 0.00 0.51
Maximum of Months 0.289308E+10 0.263149E+10 0.00 14626040.74 17029647.70 35721150.55 0.622467E+10 0.00 2.09



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.117653E+11 0.00 0.00 0.00 0.00 0.223604E+11 0.00 0.00 0.33
February 0.179433E+11 0.00 0.00 2127265.12 0.00 0.123552E+11 0.585540E+09 0.00 0.39
March 0.268641E+11 38852832.92 0.00 14590390.78 26158737.77 0.121737E+10 0.678151E+10 0.00 0.52
April 0.147978E+11 0.309778E+09 0.00 29348960.91 13006139.67 0.301097E+09 0.995147E+10 0.00 0.61
May 0.547843E+10 0.221765E+10 0.00 34952807.50 33608639.49 0.00 0.907853E+10 0.00 0.64
June 0.151237E+10 0.116127E+11 0.00 15645299.87 82466889.01 0.00 0.365556E+10 0.00 0.53
July 0.263280E+09 0.169418E+11 0.00 1784115.38 0.243178E+09 0.00 0.226440E+09 0.00 0.40
August 58267616.00 0.211618E+11 0.00 1814947.54 0.132856E+09 0.00 0.254160E+09 0.00 0.42
September 0.441816E+10 0.661669E+10 0.00 21490569.98 0.164824E+09 0.00 0.512194E+10 0.00 0.50
October 0.215077E+11 0.191141E+10 0.00 8157833.45 2760158.44 0.204111E+09 0.448790E+10 0.00 0.44
November 0.270851E+11 0.00 0.00 3315786.33 54429692.45 0.323489E+10 0.207978E+10 0.00 0.43
December 0.226344E+11 0.00 0.00 1218878.00 0.00 0.111803E+11 0.533959E+09 0.00 0.35
                   
Annual Sum or Average 0.154328E+12 0.608107E+11 0.00 0.134447E+09 0.753289E+09 0.508533E+11 0.427568E+11 0.00 0.46
Minimum of Months 58267616.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.33
Maximum of Months 0.270851E+11 0.211618E+11 0.00 34952807.50 0.243178E+09 0.223604E+11 0.995147E+10 0.00 0.64



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.136214E+11 0.00 0.00 0.00 0.00 0.136797E+11 0.00 0.00 0.41
February 0.135973E+11 0.00 0.00 6731361.91 0.00 0.801364E+10 0.418563E+10 0.00 0.51
March 0.165260E+11 48956815.20 0.00 25637827.09 610603.29 0.535079E+09 0.140965E+11 0.00 0.72
April 0.824611E+10 0.266788E+09 0.00 47071019.28 7778282.46 90118276.68 0.177754E+11 0.00 0.98
May 0.363651E+10 0.196086E+10 0.00 41524563.54 32602683.07 0.00 0.117568E+11 0.00 0.99
June 0.973570E+09 0.981553E+10 0.00 20030313.29 67051769.73 0.00 0.518880E+10 0.00 0.77
July 0.224709E+09 0.150342E+11 0.00 1410986.93 0.241713E+09 0.00 0.185723E+09 0.00 0.55
August 48497845.87 0.178383E+11 0.00 1901811.78 0.108022E+09 0.00 0.252521E+09 0.00 0.56
September 0.351525E+10 0.592195E+10 0.00 25246840.83 0.145132E+09 0.00 0.628862E+10 0.00 0.76
October 0.133880E+11 0.146136E+10 0.00 20384533.97 19774802.31 0.205735E+09 0.117029E+11 0.00 0.65
November 0.208507E+11 0.00 0.00 6224248.09 44255424.80 0.134812E+10 0.450165E+10 0.00 0.55
December 0.214536E+11 0.00 0.00 541941.89 0.00 0.589616E+10 0.412981E+09 0.00 0.44
                   
Annual Sum or Average 0.116082E+12 0.523480E+11 0.00 0.196705E+09 0.666941E+09 0.297686E+11 0.763475E+11 0.00 0.66
Minimum of Months 48497845.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.214536E+11 0.178383E+11 0.00 47071019.28 0.241713E+09 0.136797E+11 0.177754E+11 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.157668E+11 0.00 0.00 22389118.22 0.00 0.977074E+10 0.153678E+11 0.00 0.39
February 0.159696E+11 0.00 0.00 35690814.79 0.00 0.559267E+10 0.193617E+11 0.00 0.58
March 0.156157E+11 0.145984E+09 0.00 67009952.57 751252.66 0.432415E+09 0.344967E+11 0.00 0.84
April 0.110992E+11 0.470319E+09 0.00 60361699.85 9569970.41 4985066.73 0.202325E+11 0.00 0.85
May 0.504419E+10 0.261444E+10 0.00 41888082.48 32934170.87 0.00 0.106654E+11 0.00 0.73
June 0.180323E+10 0.118454E+11 0.00 15332448.18 82496805.10 0.00 0.328095E+10 0.00 0.54
July 0.259989E+09 0.177013E+11 0.00 1777556.95 0.243266E+09 0.00 0.226853E+09 0.00 0.42
August 54208736.45 0.248586E+11 0.00 2326517.41 0.132905E+09 0.00 0.284206E+09 0.00 0.50
September 0.362886E+10 0.911033E+10 0.00 40636283.16 0.164884E+09 0.00 0.870183E+10 0.00 0.74
October 0.116913E+11 0.285635E+10 0.00 69093328.04 0.00 16572058.48 0.341001E+11 0.00 0.85
November 0.148979E+11 0.00 0.00 70350384.19 54449437.63 0.795234E+09 0.368152E+11 0.00 0.77
December 0.183199E+11 0.00 0.00 42164668.56 0.00 0.392955E+10 0.272373E+11 0.00 0.54
                   
Annual Sum or Average 0.114151E+12 0.696027E+11 0.00 0.469021E+09 0.721257E+09 0.205422E+11 0.210771E+12 0.00 0.65
Minimum of Months 54208736.45 0.00 0.00 1777556.95 0.00 0.00 0.226853E+09 0.00 0.39
Maximum of Months 0.183199E+11 0.248586E+11 0.00 70350384.19 0.243266E+09 0.977074E+10 0.368152E+11 0.00 0.85



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.156809E+11 0.00 0.00 353300.14 0.00 0.124763E+11 0.595159E+09 0.00 0.44
February 0.177025E+11 0.00 0.00 6669952.58 0.00 0.627377E+10 0.310302E+10 0.00 0.55
March 0.184477E+11 0.117982E+09 0.00 29652050.72 1087508.62 0.160691E+09 0.152587E+11 0.00 0.85
April 0.917237E+10 0.403176E+09 0.00 48882343.01 5997886.58 0.00 0.160047E+11 0.00 1.04
May 0.374084E+10 0.210256E+10 0.00 39197545.52 15252337.73 0.00 0.100957E+11 0.00 1.00
June 0.112534E+10 0.101685E+11 0.00 16318265.01 53250875.79 0.00 0.347571E+10 0.00 0.77
July 0.184714E+09 0.150652E+11 0.00 2232863.23 0.164983E+09 0.00 0.265791E+09 0.00 0.57
August 46988858.91 0.199219E+11 0.00 1957328.05 67438470.10 0.00 0.236853E+09 0.00 0.62
September 0.333997E+10 0.622087E+10 0.00 24425248.81 0.128193E+09 0.00 0.520936E+10 0.00 0.77
October 0.148127E+11 0.169933E+10 0.00 20812866.32 0.00 10876919.11 0.106903E+11 0.00 0.70
November 0.217911E+11 0.00 0.00 12094862.56 46903297.62 0.934492E+09 0.675337E+10 0.00 0.62
December 0.227054E+11 0.00 0.00 3234022.89 0.00 0.484768E+10 0.200118E+10 0.00 0.48
                   
Annual Sum or Average 0.128750E+12 0.556996E+11 0.00 0.205831E+09 0.483106E+09 0.247038E+11 0.736898E+11 0.00 0.70
Minimum of Months 46988858.91 0.00 0.00 353300.14 0.00 0.00 0.236853E+09 0.00 0.44
Maximum of Months 0.227054E+11 0.199219E+11 0.00 48882343.01 0.164983E+09 0.124763E+11 0.160047E+11 0.00 1.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.616007E+09 0.00 0.00 0.00 0.00 0.223600E+10 0.00 0.00 0.35
February 0.122548E+10 0.00 0.00 103977.27 0.00 0.139658E+10 37547382.83 0.00 0.39
March 0.230476E+10 449392.07 0.00 1240475.48 1786755.58 0.424993E+09 0.485542E+09 0.00 0.51
April 0.148515E+10 16989653.07 0.00 2874985.76 893342.36 74811902.25 0.751834E+09 0.00 0.60
May 0.575310E+09 0.194789E+09 0.00 3687368.36 4398871.34 0.00 0.767507E+09 0.00 0.67
June 0.161822E+09 0.111544E+10 0.00 1440568.11 8846374.20 0.00 0.305692E+09 0.00 0.52
July 21556111.79 0.160902E+10 0.00 156378.39 38251481.03 0.00 15705832.57 0.00 0.39
August 4900378.64 0.203953E+10 0.00 162275.84 12754609.16 0.00 20589362.36 0.00 0.41
September 0.434777E+09 0.634310E+09 0.00 1884564.16 19512963.59 0.00 0.413721E+09 0.00 0.49
October 0.183343E+10 0.181298E+09 0.00 462071.45 2508385.75 0.262532E+09 0.251640E+09 0.00 0.42
November 0.211431E+10 0.00 5024298.54 141788.04 4046566.99 0.688767E+09 76500142.87 11652.84 0.42
December 0.121283E+10 0.00 0.00 45432.50 0.00 0.167319E+10 38265582.16 0.00 0.36
                   
Annual Sum or Average 0.119903E+11 0.579182E+10 5024298.54 12199885.35 92999349.99 0.675687E+10 0.316454E+10 11652.84 0.46
Minimum of Months 4900378.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 0.230476E+10 0.203953E+10 5024298.54 3687368.36 38251481.03 0.223600E+10 0.767507E+09 11652.84 0.67



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.790093E+09 0.00 0.00 0.00 0.00 0.143876E+10 0.00 0.00 0.42
February 0.102081E+10 0.00 0.00 383617.68 0.00 0.888662E+09 0.232503E+09 0.00 0.49
March 0.150233E+10 844662.81 0.00 1959194.32 968238.78 0.204207E+09 0.105810E+10 0.00 0.69
April 0.736251E+09 15447390.63 0.00 4676633.47 560102.37 37860212.37 0.155964E+10 0.00 0.97
May 0.332963E+09 0.177624E+09 0.00 4552123.29 3725682.22 0.00 0.110044E+10 0.00 1.05
June 92709348.02 0.959148E+09 0.00 1920886.32 7216941.27 0.00 0.482811E+09 0.00 0.77
July 16927847.47 0.144295E+10 0.00 127109.39 43538304.37 0.00 14052990.97 0.00 0.54
August 5052136.20 0.174433E+10 0.00 192196.82 10405309.92 0.00 20389674.10 0.00 0.56
September 0.302856E+09 0.581439E+09 0.00 2497681.60 21548489.79 0.00 0.600100E+09 0.00 0.76
October 0.118068E+10 0.144210E+09 0.00 1569329.17 3153834.79 0.150548E+09 0.850333E+09 0.00 0.62
November 0.178002E+10 0.00 4103808.62 302204.63 3301221.00 0.350640E+09 0.212005E+09 4559.91 0.54
December 0.129908E+10 0.00 0.00 24283.01 0.00 0.999123E+09 38540060.24 0.00 0.45
                   
Annual Sum or Average 0.905978E+10 0.506599E+10 4103808.62 18205259.70 94418124.52 0.406980E+10 0.616892E+10 4559.91 0.65
Minimum of Months 5052136.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.178002E+10 0.174433E+10 4103808.62 4676633.47 43538304.37 0.143876E+10 0.155964E+10 4559.91 1.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.115180E+10 0.00 0.00 1132267.13 0.00 0.107283E+10 0.812111E+09 0.00 0.36
February 0.117510E+10 0.00 0.00 2558767.15 0.00 0.757669E+09 0.139562E+10 0.00 0.53
March 0.152067E+10 5286757.32 0.00 5448278.89 32466.01 0.219600E+09 0.269735E+10 0.00 0.77
April 0.103679E+10 26479486.95 0.00 6188892.40 702405.98 60440181.41 0.178706E+10 0.00 0.84
May 0.515224E+09 0.227339E+09 0.00 4579558.73 4401897.47 0.00 0.961125E+09 0.00 0.77
June 0.176933E+09 0.113319E+10 0.00 1465709.80 8858354.20 0.00 0.296975E+09 0.00 0.54
July 20470747.02 0.167393E+10 0.00 156496.19 35922916.04 0.00 16851379.98 0.00 0.40
August 4814365.88 0.238204E+10 0.00 221697.14 12763383.50 0.00 22846609.66 0.00 0.48
September 0.359122E+09 0.865115E+09 0.00 4003497.10 16420226.08 0.00 0.802156E+09 0.00 0.73
October 0.102364E+10 0.270920E+09 0.00 5604539.09 1169930.12 0.128260E+09 0.284897E+10 0.00 0.78
November 0.148537E+10 0.00 0.00 4570936.65 9088766.56 0.290465E+09 0.246358E+10 0.00 0.67
December 0.140151E+10 0.00 0.00 2483807.58 0.00 0.644762E+09 0.158434E+10 0.00 0.46
                   
Annual Sum or Average 0.987144E+10 0.658429E+10 0.00 38414447.84 89360345.97 0.317403E+10 0.156890E+11 0.00 0.61
Minimum of Months 4814365.88 0.00 0.00 156496.19 0.00 0.00 16851379.98 0.00 0.36
Maximum of Months 0.152067E+10 0.238204E+10 0.00 6188892.40 35922916.04 0.107283E+10 0.284897E+10 0.00 0.84



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.109011E+10 0.00 0.00 15438.99 0.00 0.134329E+10 22622978.37 0.00 0.46
February 0.137216E+10 0.00 0.00 473591.65 0.00 0.818570E+09 0.231151E+09 0.00 0.57
March 0.188031E+10 3612198.30 0.00 2548750.32 216508.27 0.191742E+09 0.116646E+10 0.00 0.84
April 0.999922E+09 22496960.90 0.00 4904167.98 472195.65 39344791.92 0.138533E+10 0.00 1.06
May 0.430391E+09 0.179804E+09 0.00 4202586.84 3024082.30 0.00 0.927460E+09 0.00 1.05
June 0.136578E+09 0.952999E+09 0.00 1542822.82 6300367.20 0.00 0.306416E+09 0.00 0.75
July 16322776.84 0.140054E+10 0.00 201896.16 27981600.90 0.00 19014886.10 0.00 0.54
August 4125778.77 0.188471E+10 0.00 179120.13 5367710.86 0.00 19252790.29 0.00 0.59
September 0.360098E+09 0.592141E+09 0.00 2301498.83 18269946.03 0.00 0.446574E+09 0.00 0.76
October 0.152301E+10 0.160438E+09 0.00 1542541.06 3545764.81 85917676.05 0.785951E+09 0.00 0.69
November 0.189756E+10 0.00 0.00 759051.12 8330386.20 0.379092E+09 0.440332E+09 0.00 0.63
December 0.165742E+10 0.00 0.00 142306.82 0.00 0.830028E+09 0.113497E+09 0.00 0.50
                   
Annual Sum or Average 0.113680E+11 0.519674E+10 0.00 18813772.73 73508562.23 0.368798E+10 0.586406E+10 0.00 0.70
Minimum of Months 4125778.77 0.00 0.00 15438.99 0.00 0.00 19014886.10 0.00 0.46
Maximum of Months 0.189756E+10 0.188471E+10 0.00 4904167.98 27981600.90 0.134329E+10 0.138533E+10 0.00 1.06



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 2773069.85 0.00 0.00 0.592899E+09 0.00 0.28
February 0.00 0.00 0.00 6935878.87 0.00 0.00 0.445252E+09 0.00 0.28
March 0.00 4318538.27 0.00 11949387.89 0.00 0.00 0.341000E+09 0.00 0.31
April 0.00 11363491.73 0.00 14341895.43 0.00 0.00 0.186613E+09 0.00 0.29
May 0.00 65944504.95 0.00 1427466.64 0.00 0.00 59801483.37 0.00 0.29
June 0.00 0.278897E+09 0.00 1302208.42 0.00 0.00 27326435.75 0.00 0.30
July 0.00 0.392258E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.477870E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.155883E+09 0.00 1254125.89 0.00 0.00 34120125.45 0.00 0.29
October 0.00 50437460.14 0.00 5968196.31 0.00 0.00 0.241173E+09 0.00 0.28
November 0.00 3605114.91 0.00 10829116.75 0.00 0.00 0.355725E+09 0.00 0.28
December 0.00 451509.74 0.00 16013398.52 0.00 0.00 0.449039E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.144103E+10 0.00 72794744.56 0.00 0.00 0.273295E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.477870E+09 0.00 16013398.52 0.00 0.00 0.592899E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.917159E+09 0.00 0.00 11646295.02 0.00 0.00 0.503867E+10 0.00 0.28
February 0.00 0.00 0.00 55009785.27 0.00 0.00 0.446854E+10 0.00 0.28
March 0.00 42901071.74 0.00 0.108807E+09 0.00 0.00 0.341643E+10 0.00 0.31
April 0.00 0.113929E+09 0.00 0.135210E+09 0.00 0.00 0.187040E+10 0.00 0.29
May 0.00 0.642193E+09 0.00 13165022.68 0.00 0.00 0.602136E+09 0.00 0.29
June 0.00 0.277955E+10 0.00 12228124.94 0.00 0.00 0.273126E+09 0.00 0.30
July 0.00 0.391725E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.477092E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.153341E+10 0.00 11256080.51 0.00 0.00 0.350465E+09 0.00 0.29
October 0.00 0.498984E+09 0.00 52512879.22 0.00 0.00 0.241929E+10 0.00 0.28
November 0.00 35105209.70 0.00 96558067.76 0.00 0.00 0.356584E+10 0.00 0.28
December 0.00 4451149.16 0.00 0.140189E+09 0.00 0.00 0.450722E+10 0.00 0.28
                   
Annual Sum or Average 0.917159E+09 0.143387E+11 0.00 0.636582E+09 0.00 0.00 0.265121E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.917159E+09 0.477092E+10 0.00 0.140189E+09 0.00 0.00 0.503867E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.316717E+09 0.00 0.00 543416.78 0.00 0.00 0.269682E+09 0.00 0.28
February 0.00 0.00 0.00 4744279.61 0.00 0.00 0.447923E+09 0.00 0.28
March 0.00 4272419.81 0.00 10296968.93 0.00 0.00 0.342526E+09 0.00 0.31
April 0.00 11335681.80 0.00 13269687.06 0.00 0.00 0.187499E+09 0.00 0.29
May 0.00 64375062.63 0.00 1251205.29 0.00 0.00 60547039.38 0.00 0.29
June 0.00 0.278101E+09 0.00 1210977.21 0.00 0.00 27367910.98 0.00 0.30
July 0.00 0.391592E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.478035E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.153321E+09 0.00 1051789.10 0.00 0.00 35853120.96 0.00 0.29
October 0.00 49726862.53 0.00 4774975.20 0.00 0.00 0.243161E+09 0.00 0.28
November 0.00 3424900.46 0.00 8886932.71 0.00 0.00 0.357664E+09 0.00 0.28
December 0.00 430918.07 0.00 13000507.47 0.00 0.00 0.451961E+09 0.00 0.28
                   
Annual Sum or Average 0.316717E+09 0.143461E+10 0.00 59030739.36 0.00 0.00 0.242418E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.316717E+09 0.478035E+09 0.00 13269687.06 0.00 0.00 0.451961E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.206220E+09 0.00 0.00 0.151501E+11 0.00 0.32
February 0.00 0.00 0.00 0.380481E+09 0.00 0.00 0.111717E+11 0.00 0.32
March 0.00 84762630.15 0.00 0.598839E+09 0.00 0.00 0.799471E+10 0.00 0.34
April 0.00 0.232417E+09 0.00 0.719626E+09 0.00 0.00 0.409061E+10 0.00 0.32
May 0.00 0.174387E+10 0.00 70433855.87 0.00 0.00 0.128911E+10 0.00 0.33
June 0.00 0.628558E+10 0.00 64842436.08 0.00 0.00 0.583673E+09 0.00 0.34
July 0.00 0.865316E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
August 0.00 0.873491E+10 0.00 18534.98 0.00 0.00 0.00 0.00 0.35
September 0.00 0.380322E+10 0.00 62263288.29 0.00 0.00 0.641299E+09 0.00 0.33
October 0.00 0.116935E+10 0.00 0.309987E+09 0.00 0.00 0.516357E+10 0.00 0.32
November 0.00 69460756.86 0.00 0.550358E+09 0.00 0.00 0.855940E+10 0.00 0.32
December 0.00 9901575.23 0.00 0.812169E+09 0.00 0.00 0.110872E+11 0.00 0.31
                   
Annual Sum or Average 0.00 0.307866E+11 0.00 0.377524E+10 0.00 0.00 0.657313E+11 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.00 0.873491E+10 0.00 0.812169E+09 0.00 0.00 0.151501E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:04:13

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.351956E+12 0.292026E+11 0.00 0.153097E+13 0.546021E+12
February 0.353053E+12 0.257864E+11 0.00 0.152249E+13 0.935445E+12
March 0.515981E+12 0.169773E+11 0.00 0.179856E+13 0.166318E+13
April 0.578477E+12 0.931305E+10 0.00 0.142130E+13 0.235360E+13
May 0.637156E+12 0.451931E+10 0.00 0.860026E+12 0.177811E+13
June 0.619127E+12 -0.425395E+10 0.00 0.401059E+10 0.287629E+13
July 0.596830E+12 -0.879516E+10 0.00 -0.404218E+12 0.355107E+13
August 0.554851E+12 -0.115662E+11 0.00 -0.553358E+12 0.418886E+13
September 0.429302E+12 -359365984.6 0.00 0.337664E+12 0.199628E+13
October 0.408965E+12 0.932229E+10 0.00 0.139897E+13 0.155546E+13
November 0.301969E+12 0.154035E+11 0.00 0.169105E+13 0.150435E+13
December 0.287585E+12 0.270859E+11 0.00 0.168665E+13 0.175318E+13
           
Annual Sum or Average 0.563525E+13 0.112636E+12 0.00 0.112941E+14 0.247018E+14
Minimum of Months 0.287585E+12 -0.115662E+11 0.00 -0.553358E+12 0.546021E+12
Maximum of Months 0.637156E+12 0.292026E+11 0.00 0.179856E+13 0.418886E+13