Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820

Simulation Timestamp: 2023-10-16 09:04:27


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 33375.49 720.54 720.54
Net Site Energy 33375.49 720.54 720.54
Total Source Energy 104496.57 2255.95 2255.95
Net Source Energy 104496.57 2255.95 2255.95


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 18.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6499.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2741.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 447.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2647.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1289.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1962.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18423.02
Humidification 82.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.74
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 559.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 32797.66 577.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20733.93
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 18.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 6499.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2741.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 447.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 59.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2647.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1289.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1962.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18423.02
Humidification General 82.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.74
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 559.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 18.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 6499.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2741.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 447.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2647.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1289.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1962.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18423.02
Humidification Unassigned 82.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.74
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 559.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 269.44 12.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Other 369.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 708.06 12.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 269.44 12.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Other 369.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 708.06 12.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 32797.665 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 32797.665 100.00
     
Total On-Site and Utility Electric Sources 32797.665 100.00
Total Electricity End Uses 32797.665 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 20733.93 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 20733.93 100.00
Total Water End Uses 20733.93 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 1100.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
RunPeriod RUNPERIOD 1
Weather File New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Latitude [deg] 28.58
Longitude [deg] 77.20
Elevation [m] 216.00
Time Zone 5.50
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 7.6202 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 7.6202 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 7.6202 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 7.6202 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 7.6202 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 7.6202 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 7.6202 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 7.6202 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 12.5114 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 12.5114 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 12.5114 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 7.6202 18.58 484.4232  
Total 46320.38             7.6661 9.29 17.8789  
Conditioned Total 46320.38             7.6661 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.3561 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 07-AUG-15:09 02-JAN-06:19 - - - - - - - - - - 19-APR-15:09
Heating 0.00 217619.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 559423.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 83146.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 212155.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 67734.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 91812.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 26548.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 2042710.94 244167.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 217619.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 559423.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3711.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 212155.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 67734.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 91812.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 26548.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 19.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 20582.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8683.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1416.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6062.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8384.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 4083.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 6213.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 261.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 606.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 103870.20 626.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 444.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 181.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 88.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 134.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 5.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2242.43 13.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 0.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 444.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 181.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 88.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 134.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 5.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2242.43 13.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.57
DATACENTER_BOT_ZN_6 DIRECT AIR 0.482956
DATACENTER_MID_ZN_6 DIRECT AIR 4.60
DATACENTER_TOP_ZN_6 DIRECT AIR 0.463312
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.95 0.319862 0.326000 1.94 0.852965 0.500000 0.001191 0.000166 1.94 12.80 0.008000
CORE_MID VAV BOX COMPONENT 56.33 0.337662 0.339000 19.10 0.900432 0.500000 0.001128 0.003077 19.10 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.86 0.324791 0.338000 1.98 0.866109 0.500000 0.001173 0.000547 1.98 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 1.17 0.203374 0.208000 0.244253 0.542330 0.500000 0.001873 0.000036 0.244253 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.920155 0.167260 0.200000 0.184031 0.446026 0.500000 0.002278 0.000028 0.184031 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.20 0.199785 0.204000 0.243864 0.532760 0.500000 0.001907 0.000052 0.243864 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.21 0.127613 0.200000 0.241205 0.340302 0.500000 0.002986 0.000022 0.241205 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 11.40 0.209451 0.210000 2.39 0.558536 0.500000 0.001819 0.001070 3.74 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 9.53 0.161524 0.200000 1.91 0.430731 0.500000 0.002359 0.000713 2.49 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 11.50 0.207593 0.209000 2.40 0.553580 0.500000 0.001835 0.001070 3.74 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 10.21 0.150804 0.200000 2.04 0.402144 0.500000 0.002526 0.000617 2.15 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.34 0.177999 0.200000 0.268339 0.474664 0.500000 0.002140 0.000155 0.540259 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.02 0.150733 0.200000 0.204209 0.401954 0.500000 0.002528 0.000102 0.355715 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.34 0.177655 0.200000 0.268864 0.473748 0.500000 0.002145 0.000155 0.540265 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.15 0.133392 0.200000 0.230757 0.355711 0.500000 0.002856 0.000094 0.329853 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 19026.36 0.000166 383.56
CORE_MID VAV BOX REHEAT COIL 351752.39 0.003077 7765.61
CORE_TOP VAV BOX REHEAT COIL 62504.34 0.000547 1623.56
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 4066.49 0.000036 88.03
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 3242.83 0.000028 70.96
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 5927.70 0.000052 140.17
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2512.97 0.000022 50.97
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 122321.44 0.001070 3228.47
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 81481.53 0.000713 2150.45
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 122322.11 0.001070 3228.48
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 70505.88 0.000617 1861.23
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 17668.25 0.000155 466.11
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11632.41 0.000102 306.87
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 17668.43 0.000155 466.11
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10788.67 0.000094 284.63
VAV_BOT WITH REHEAT HEATING COIL 22570.87 0.000197 394.69
VAV_MID WITH REHEAT HEATING COIL 171567.88 0.001501 3027.85
VAV_TOP WITH REHEAT HEATING COIL 13282.34 0.000116 237.36
CAV_BAS HEATING COIL 253780.16 0.002220 5777.81
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.22 2.85 10.44 2.85 9.81 9.81 0.300000 0.290745 9.81
VAV_MID WITH REHEAT 49.49 27.84 98.97 27.84 92.79 92.79 0.300000 0.300057 92.79
VAV_TOP WITH REHEAT 5.36 2.95 10.72 3.64 10.59 10.59 0.300000 0.343589 10.59
CAV_BAS 5.57 5.57 5.57 5.57 5.57 5.57 1.00 1.00 5.57
AIRLOOP DATACENTER BASEMENT 21.90 21.90 21.90 21.90 21.90 21.90 1.00 0.999988 21.90
AIRLOOP DATACENTER BOT 0.482956 0.482956 0.482956 0.482956 0.482956 0.482956 1.00 1.00 0.482956
AIRLOOP DATACENTER MID 4.60 4.60 4.60 4.60 4.60 4.60 1.00 1.00 4.60
AIRLOOP DATACENTER TOP 0.463312 0.463312 0.463312 0.463312 0.463312 0.463312 1.00 1.00 0.463312
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.81  
VAV_MID WITH REHEAT_OA_CONTROLLER 92.79  
VAV_TOP WITH REHEAT_OA_CONTROLLER 10.59  
CAV_BAS_OA_CONTROLLER 5.57 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.90 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.482956 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.60 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.463312 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 28.81 6.67 10.99 0.007833 0.007000 233283.98 0.009924 9.81
VAV_MID WITH REHEAT COOLING COIL 29.27 6.67 10.99 0.007914 0.007000 2280072.41 0.097000 92.79
VAV_TOP WITH REHEAT COOLING COIL 28.32 6.67 11.00 0.007772 0.007000 243601.62 0.010363 10.59
CAV_BAS COOLING COIL 27.70 6.67 11.38 0.007883 0.007000 123307.64 0.005246 5.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.81
VAV_MID WITH REHEAT FAN 92.79
VAV_TOP WITH REHEAT FAN 10.59
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.009924 0.000048
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000197  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.097000 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.001501  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.010363 0.000046
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000116  
CAV_BAS_COOLC_CONTROLLER 0.005246 0.000091
CAV_BAS_HEATC_CONTROLLER 0.002220  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.57
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.90 451109.56 280919.89 0.011048
AIRLOOP DATACENTER BOT COOLING COIL 0.482956 9672.22 6096.44 0.000237
AIRLOOP DATACENTER MID COOLING COIL 4.60 92221.08 58100.27 0.002258
AIRLOOP DATACENTER TOP COOLING COIL 0.463312 9540.07 5930.05 0.000234
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.90 21.90 21.90 21.90 451109.56 451109.56 13450.69 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.482956 0.482956 0.482956 0.482956 9672.22 9672.22 621.37 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.60 4.60 4.60 4.60 92221.08 92221.08 6213.66 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.463312 0.463312 0.463312 0.463312 9540.07 9540.07 621.37 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.90
AIRLOOP DATACENTER BOT SUPPLY FAN 0.482956
AIRLOOP DATACENTER MID SUPPLY FAN 4.60
AIRLOOP DATACENTER TOP SUPPLY FAN 0.463312
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.90 451109.56 0.011048
AIRLOOP DATACENTER BOT HEATING COIL 0.482956 9672.22 0.000237
AIRLOOP DATACENTER MID HEATING COIL 4.60 92221.08 0.002258
AIRLOOP DATACENTER TOP HEATING COIL 0.463312 9540.07 0.000234
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 13450.69
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 621.37
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6213.66
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 621.37
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000048 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.122533 25249.54  
HEATSYS1 PUMP 0.011938 3595.30 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.122533 14.70
HEATSYS1 0.011938 1.43
COOLSYS1_SUPPLY 0.122533 14.70
SINGLE WATER PLANT LOOP 0.013777 1.65
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.122533 0.122533 514333.15 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1364623.04 1364623.04 0.011938
CENTRAL BOILER 567479.46 556467.27 0.013777
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.122533 17481.11
PLANT CIRC PUMP 0.013777 3513.73
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.122533 0.061850 1457418.04 1464382.66 0.072467
COOLSYS1 CHILLER2 0.122533 0.061850 1457418.04 1464382.66 0.072467
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013777 139666.47 57485.43 69833.23 7879.72 21233.18
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.144934 17.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.144934 43650.89
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 57.46 1737449.05 11.49 217181.13
TOWERWATERSYS COOLTOWER 2 57.46 1737449.05 11.49 217181.13
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.075270
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 25.10 19.60 14.50 13.40 17.00 22.40 29.10 33.00 33.60 31.70 30.00 28.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820 28.58 77.20 5.50 216.00 98757 1.1738


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 24.84 20.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 7.620 4.842 0.000 0.000 0.000 0.000 12.462 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 7.620 484.423 0.000 0.000 0.000 0.000 492.043 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 21179.739 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 21179.739
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5971.780 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5971.780
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2832 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.743 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.656 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 2.135 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 3.472
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.4064
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4365
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3009
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.61927053E-06 0.12767249E-08 -0.37968499E-05 0.16832131E-17
47 2 0.77611055 0.17315568E-02 1.0534842 -0.72792597E-06
48 1 -21.915918 0.11588205 -6.3286394 0.20197014
49 0 21.365777 0.10835518 5.5011278  
50 9 0.76055735E-15 0.55973061E-16 -0.11090261E-09 -0.43371185E-17
51 8 0.16390423E-07 0.22068143E-12 0.31740643E-03 -0.18636477E-09
52 7 -0.10429999E-01 0.12271718E-07 -0.20474149E-01 0.11859286E-03
53 6 0.35611320 0.43955117E-05 0.42991281 -0.41673803E-02
54 5 -4.7098961 0.16827687E-03 -4.1162358 0.57223947E-01
55 4 30.875684 0.14076848E-02 20.167480 -0.39388153
56 3 -106.69740 0.31291265E-02 -53.106522 1.4497707
57 2 192.63914 0.17911574E-02 75.570394 -2.8293896
58 1 -169.50392 0.19431750E-03 -54.592911 2.7164834
59 0 57.057407 0.11257899E-05 15.674734  
60 9 0.11474244E-14 0.54197419E-16 -0.11508650E-09 -0.49945851E-17
61 8 0.16984416E-07 0.21156325E-12 0.32425024E-03 -0.19311866E-09
62 7 -0.10636353E-01 0.11664670E-07 -0.20772028E-01 0.12093918E-03
63 6 0.36172330 0.41637772E-05 0.43474562 -0.42335086E-02
64 5 -4.7646824 0.15893927E-03 -4.1535939 0.57903236E-01
65 4 31.118254 0.13261305E-02 20.314042 -0.39710182
66 3 -107.21418 0.29411649E-02 -53.396504 1.4572354
67 2 193.15212 0.16802168E-02 75.835339 -2.8375342
68 1 -169.69371 0.18194848E-03 -54.668081 2.7198097
69 0 57.057407 0.10520719E-05 15.660794  
70 9 0.66246833E-15 0.57738042E-16 -0.92036509E-10 -0.27018983E-17
71 8 0.13701644E-07 0.25726543E-12 0.28527343E-03 -0.15579243E-09
72 7 -0.94571194E-02 0.14940887E-07 -0.19068097E-01 0.10753086E-03
73 6 0.32965778 0.54453531E-05 0.40701455 -0.38555430E-02
74 5 -4.4514676 0.21157254E-03 -3.9387765 0.54019785E-01
75 4 29.731016 0.17930056E-02 19.470280 -0.37868589
76 3 -104.25747 0.40308508E-02 -51.726693 1.4145289
77 2 190.21562 0.23301583E-02 74.311741 -2.7909129
78 1 -168.60668 0.25508611E-03 -54.239505 2.7007581
79 0 57.057407 0.14924561E-05 15.743350  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.5047_SHGC_EAST_0.25 35 1 VerySmooth 2.869 2.869 1.000 0.251    
2 WINDOW_U_0.5047_SHGC_SOUTH_0.25 36 1 VerySmooth 2.869 2.869 1.000 0.251    
3 WINDOW_U_0.5047_SHGC_WEST_0.25 37 1 VerySmooth 2.869 2.869 1.000 0.251    
4 WINDOW_U_0.5047_SHGC_NORTH_0.25 38 1 VerySmooth 2.869 2.869 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6556E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6567E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8034E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8043E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1458E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1465E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6818E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7553E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8248E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8865E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1628E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2127E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.3694E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0906E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.1712E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2798E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.0286E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2382E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6871E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7813E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8306E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.9145E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1681E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2329E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6555E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6568E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.8033E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8044E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1458E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1467E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7734E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.9022E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6487E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7820E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.5073E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5748E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2792E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5967E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.1179E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.4553E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.3343E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3602E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7433E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7949E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6113E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6492E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.4871E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5031E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2193E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2205E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0482E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0492E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.2927E-004
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.2997E-004
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2462E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3126E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0702E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1232E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4683E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.8505E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8970E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0736E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4831E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.2182E-003
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4618E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 5.7927E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2442E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3101E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0678E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1184E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4273E-004
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.7257E-004
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2192E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2203E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0481E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0490E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.2918E-004
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.2973E-004
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3719E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4257E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1617E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2007E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1392E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1537E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5554E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.3237E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.2515E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.1301E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6176E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.0860E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3958E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4967E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1920E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2913E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1581E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2174E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.2526E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.2005E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.8513E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.4500E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.3253E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.1602E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.7645E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.2088E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.5896E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.0428E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.7878E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9148E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.2887E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.5929E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8364E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2718E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8071E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 9.9091E-003
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.9784E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8510E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.6470E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.6146E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0155E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5644E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.2523E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.2071E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.8524E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.4578E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.3293E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.1668E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.7636E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.2110E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.5896E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.0450E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.7898E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9182E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.2861E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5936E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8346E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2724E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8081E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 9.9234E-003
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.9768E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8524E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.6462E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.6160E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0169E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5670E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 75181.81742 75181.81742 5.56805 5.56805 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 6.30000 6.07234E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 80291.25723 80291.25723 5.94646 5.94646 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 6.30000 6.07234E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 760763.86913 760763.86913 56.32982 56.32982 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 34.82200 9.14597E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 164331.48709 164331.48709 7.04256 10.77825 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 78353.55371 78353.55371 5.85621 5.85621 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:50:00 42.00000 9.15790E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 43076.99797 43076.99797 1.87236 1.87236 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 15711.61378 15711.61378 1.17429 1.17429 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:20:00 41.80600 9.15758E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 1670.32548 1670.32548 7.25146E-002 0.13533 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12311.34991 12311.34991 0.92016 0.92016 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:10:00 38.55650 9.15215E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 1437.36817 1437.36817 6.21895E-002 8.72129E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15994.18128 15994.18128 1.19541 1.19541 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 42.00000 9.15790E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 3534.94656 3534.94656 0.15294 0.15294 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 16136.28664 16136.28664 1.20603 1.20603 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 41.15933 9.15650E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 149.21061 149.21061 6.54944E-003 8.72129E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 152555.09452 152555.09452 11.40222 11.40222 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 41.70900 9.15741E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 85655.61543 85655.61543 3.73659 3.73659 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 127483.44478 127483.44478 9.52830 9.52830 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:20:00 38.79900 9.15255E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 57054.55283 57054.55283 2.48932 2.48932 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 153924.07964 153924.07964 11.50455 11.50455 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:10:00 42.00000 9.15790E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 85656.08753 85656.08753 3.73661 3.73661 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 136545.97971 136545.97971 10.20564 10.20564 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 41.03000 9.15628E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 49381.77448 49381.77448 2.15288 2.15288 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 17951.06011 17951.06011 1.34170 1.34170 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 41.61200 9.15725E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 12366.35462 12366.35462 0.54026 0.54026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 13660.96349 13660.96349 1.02105 1.02105 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:40:00 39.28400 9.15337E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 8141.55349 8141.55349 0.35572 0.35572 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 17986.16464 17986.16464 1.34432 1.34432 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:40:00 42.00000 9.15790E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 12366.47583 12366.47583 0.54026 0.54026 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 15436.93151 15436.93151 1.15378 1.15378 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 41.15933 9.15650E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 7551.69961 7551.69961 0.32985 0.32985 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 6.30000 6.07234E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8193.50212 8193.50212 0.48296 0.48296 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 32.36467 9.14193E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 78050.85023 78050.85023 4.60061 4.60061 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 32.36467 9.14193E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7859.30186 7859.30186 0.46331 0.46331 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 40.90067 9.15606E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 6.30000 6.07234E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 371509.00917 371509.00917 21.90024 21.90024 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:00:00 33.17300 9.14325E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 6.30000 6.07234E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 179307.50 9.80894 9.80894 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 11810.70 1.54052 1.54052 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1684130.86 92.78733 92.78733 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 175518.16 22.89365 22.89365 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 193487.50 10.58956 10.58956 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 19399.83 3.63846 3.63846 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 12:00:00
7 CAV_BAS Cooling Sensible 89805.36 5.56805 5.56805 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
8 CAV_BAS Heating Sensible 47704.73 1.20016 1.20016 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 372287.85 21.90051 21.90051 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 13450.69 0.33839 0.33839 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8187.82 0.48296 0.48296 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 621.37 1.56323E-002 1.56323E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 78043.59 4.60061 4.60061 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6213.66 0.15632 0.15632 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8019.11 0.46331 0.46331 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 621.37 1.56323E-002 1.56323E-002 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.56805
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.94646
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.31986
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.32600
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.93854
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.85296
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.19114E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66451E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.93854
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19026.36169
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66451E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 383.55652
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 56.32982
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33766
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33900
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 19.09581
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.90043
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12835E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.07728E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 19.09581
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 351752.38731
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.07728E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7765.61402
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.85621
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.32479
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33800
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.97940
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.86611
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.17306E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.46815E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.97940
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 62504.33746
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.46815E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1623.56270
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.17429
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20337
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20800
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24425
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.54233
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.87340E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.55754E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24425
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4066.49209
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.55754E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 88.03434
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.92016
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16726
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18403
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44603
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.27789E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.83697E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.18403
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3242.82773
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.83697E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 70.95758
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.19541
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19979
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20400
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24386
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.53276
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.90705E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.18581E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24386
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5927.69989
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.18581E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 140.16754
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.20603
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12761
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24121
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34030
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.98558E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.19845E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.24121
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 2512.96726
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.19845E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 50.96716
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.40222
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20945
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21000
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.39447
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55854
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.81904E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07012E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.73659
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 122321.44301
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07012E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3228.46535
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.52830
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16152
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.90566
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43073
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.35878E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.12836E-004
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.48932
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 81481.53457
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.12836E-004
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2150.45456
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.50455
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20759
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20900
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.40445
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55358
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.83533E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.07013E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.73661
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 122322.11399
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.07013E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3228.48315
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.20564
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15080
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.04113
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40214
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.52646E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.16816E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.15288
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 70505.87724
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.16816E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1861.23416
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.34170
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17800
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26834
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47466
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.14046E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54570E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54026
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17668.25253
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54570E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 466.10897
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.02105
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15073
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20421
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40195
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.52765E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.01765E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35572
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11632.41214
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.01765E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 306.86877
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.34432
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17766
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26886
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.47375
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.14460E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54571E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.54026
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17668.42545
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54571E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 466.11354
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.15378
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13339
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23076
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35571
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.85625E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.43840E-005
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32985
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10788.66831
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.43840E-005
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 284.63449
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.48296
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.60061
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46331
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.90024
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.22117
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.85190
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.44235
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.85190
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.80894
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.80894
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.29074
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 49.48527
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 27.84151
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 98.97053
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 27.84151
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 92.78733
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 92.78733
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.30006
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.35853
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.95157
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.71706
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.63846
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 10.58956
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 10.58956
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.34359
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.56805
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.56805
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.56805
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.56805
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.56805
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.56805
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.90024
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.90024
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.90024
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.90024
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.90051
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.90051
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.48296
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.48296
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.48296
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.48296
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.48296
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.48296
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.60061
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.60061
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.60061
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.60061
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.60061
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.60061
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46331
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46331
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46331
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.46331
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.46331
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.46331
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.80894
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 92.78733
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 10.58956
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.56805
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.90051
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.48296
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.60061
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.46331
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.80894
289 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.81087
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99403
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.83253E-003
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 233283.97957
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.92444E-003
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.80894
297 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 22570.86522
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.97460E-004
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 394.68947
300 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.80894
301 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.92444E-003
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.79816E-005
303 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.97460E-004
304 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 92.78733
305 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 29.26856
306 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.99430
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.91354E-003
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2280072.41273
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.69996E-002
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 92.78733
313 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 171567.88298
314 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.50095E-003
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 3027.84644
316 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 92.78733
317 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.69996E-002
318 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.90920E-006
319 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.50095E-003
320 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 10.58956
321 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 28.32196
322 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
323 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.00343
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.77160E-003
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 243601.61716
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.03634E-002
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 10.58956
329 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 13282.33747
330 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.16200E-004
331 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 237.35583
332 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 10.58956
333 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.03634E-002
334 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.59494E-005
335 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.16200E-004
336 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.56805
337 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
338 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 27.70339
339 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
340 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.38302
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.88349E-003
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 123307.64462
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.24579E-003
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.56805
346 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 253780.15715
347 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.22018E-003
348 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5777.80691
349 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.56805
350 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.24579E-003
351 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.07757E-005
352 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.22018E-003
353 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.90051
354 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
355 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.90051
356 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 451109.56477
357 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 280919.89260
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.10476E-002
359 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.90051
360 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.90051
361 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.90051
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.90051
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 451109.56477
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 451109.56477
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 13450.69260
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
367 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.90051
368 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.90051
369 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 451109.56477
370 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.10476E-002
371 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 13450.69260
372 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 4.78176E-005
373 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
374 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
376 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.48296
377 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
378 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.48296
379 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9672.21752
380 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6096.44376
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.36872E-004
382 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.48296
383 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.48296
384 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.48296
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.48296
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9672.21752
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9672.21752
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 621.36627
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.48296
391 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.48296
392 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9672.21752
393 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.36872E-004
394 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 621.36627
395 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.60061
396 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
397 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.60061
398 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 92221.07590
399 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 58100.26718
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.25849E-003
401 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.60061
402 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.60061
403 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.60061
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.60061
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 92221.07590
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 92221.07590
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6213.66275
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
409 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.60061
410 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.60061
411 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 92221.07590
412 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.25849E-003
413 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6213.66275
414 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46331
415 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
416 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46331
417 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9540.06689
418 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 5930.05476
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.33636E-004
420 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46331
421 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46331
422 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46331
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46331
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9540.06689
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9540.06689
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 621.36627
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
428 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46331
429 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46331
430 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9540.06689
431 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.33636E-004
432 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 621.36627
433 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12253
434 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 25249.54261
435 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12253
436 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 14.70398
437 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12253
438 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12253
439 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 514333.15251
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
441 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.19383E-002
442 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.43260
443 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.19383E-002
444 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 3595.29702
445 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
446 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1364623.04349
447 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1364623.04000
448 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.19383E-002
449 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12253
450 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 14.70398
451 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.12253
452 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 17481.11008
453 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12253
454 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.18500E-002
455 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1457418.04140
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1464382.66000
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.24669E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12253
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.18500E-002
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1457418.04140
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1464382.66000
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.24669E-002
463 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.37766E-002
464 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.65320
465 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.37766E-002
466 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3513.73214
467 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.37766E-002
468 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
469 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 57485.42595
470 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
471 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
472 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21233.17685
473 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 567479.46138
474 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 556467.27000
475 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.37766E-002
476 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
477 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
478 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
479 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
480 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
481 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.14493
482 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 17.39205
483 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.14493
484 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 43650.88847
485 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 57.46141
486 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1737449.04667
487 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.49228
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 217181.13083
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 57.46141
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1737449.04667
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.49228
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 217181.13083
493 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.52700E-002
494 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.52700E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 18041.04
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 333375.69
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 59191.66
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 3854.39
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 3073.53
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 5616.00
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 2382.76
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 115913.30
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 77212.16
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 115913.94
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 66814.59
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 16741.22
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 11022.02
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 16741.38
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 10222.71
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 19567.51
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 151298.88
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 11984.64
19 Coil:Heating:Water CAV_BAS HEATING COIL 206608.38


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 286360.91 187954.71 98406.20 0.66 37797.31 383.36
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2734121.12 1788934.72 945186.40 0.65 358896.74 3640.13
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 306011.31 201548.59 104462.72 0.66 40588.76 411.67
4 Coil:Cooling:Water CAV_BAS COOLING COIL 156896.37 104134.33 52762.05 0.66 20260.24 205.49


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.283 0.269   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.4179534797 0.1445237306 Pass Pass 0.5008472136 0.5178642309 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 2.7446870709E-003 2.0120071568E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 2.7342699512E-003 2.0212730289E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 2.1180242897E-002 1.2650471983E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.1500402697E-002 1.5074042896E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 2.9237037027E-002 3.3273024400E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 5.0217232847E-002 3.8130257264E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 3.4792914852E-002 3.0897086410E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 2.3029508803E-002 1.5121523883E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 3.1558747997E-002 3.1684784284E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 5.6812544635E-002 4.0990599032E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 3.7265566514E-002 3.1595908015E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 3.5490799815E-002 2.1293420539E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 4.3241650306E-002 2.8593610416E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 6.8159748067E-002 4.4137563676E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 5.0607760608E-002 3.6493446292E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.8024927934E-003 3.0692091663E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 3.9408484231E-003 3.3329043996E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.3676620974E-002 4.8015434543E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 4.7575454740E-005 7.2306833616E-005 Pass Pass 2.3826871028E-003 1.4102690012E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 3.2030136358E-005 4.7417908433E-005 Pass Pass 8.2655504681E-003 4.2404389886E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 3.6167558266E-002 1.8060830871E-002 Pass Pass 1.1174275852E-002 8.7583286461E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 2.1093864744E-004 2.0347591614E-004 Pass Pass 6.3483675957E-005 1.0377116494E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4683.87 -42.2 0.00 -5171.6 40559.66 40029.74



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 6.30 0.00 6.30 Wetbulb [C] 0.50 270.00
NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 42.00 9.70 22.20 Wetbulb [C] 3.20 320.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.60 4      
Feb 21.40 43      
Mar 12.00 35      
Apr 29.10 12      
May 29.10 57      
Jun 197.10 59      
Jul 47.90 83      
Aug 0.00 0      
Sep 171.60 106      
Oct 4.80 31      
Nov 1.20 7      
Dec 33.00 13      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.273 0.283 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.5047_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.869 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.5047_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.869 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.5047_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.869 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.5047_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.869 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.5047_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.869 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.5047_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.869 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.5047_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.869 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.5047_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.869 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.869 0.251 0.251                      
North Total or Average             1043.06 2.869 0.251 0.251                      
Non-North Total or Average             2433.80 2.869 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 7.6202 2779.43 21179.74 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 177.74
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 7.6202 24961.20 190208.95 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 1596.24
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.73 0.0000 Y 13.78
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.70 0.0000 Y 8.87
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.55 0.0000 Y 13.70
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.68 0.0000 Y 8.86
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 7.6202 3134.13 23882.63 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.76 0.0000 Y 137.90
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.71 0.0000 Y 88.73
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 7.6202 3134.20 23883.15 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.57 0.0000 Y 137.06
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.69 0.0000 Y 88.66
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.76 0.0000 Y 13.79
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.71 0.0000 Y 8.87
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.57 0.0000 Y 13.71
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.69 0.0000 Y 8.87
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 7.6202 783.68 5971.78 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 50.12
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 12.5114 362.03 4529.48 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 46.40
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
Interior Lighting Total       7.6661 46320.38 355094.67               856.32


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   41.75 41.75 78.17
EXTERIOR_LIGHTS_B 27638.03 AstronomicalClock -   83.75 71.15 369.15
Exterior Lighting Total 37611.08           447.32



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2873641.89          
HEATSYS1 BOILER Boiler:HotWater 1364623.04 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1464382.66 6.28 1401597.32 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1464382.66 6.28 1401597.32 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 556467.27 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1737449.05          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1737449.05          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 233283.98 286360.91 187954.71 98406.20 0.66 - 37797.31 383.36
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2280072.41 2734121.12 1788934.72 945186.40 0.65 - 358896.74 3640.13
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 243601.62 306011.31 201548.59 104462.72 0.66 - 40588.76 411.67
CAV_BAS COOLING COIL Coil:Cooling:Water 123307.64 156896.37 104134.33 52762.05 0.66 - 20260.24 205.49
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   451109.56 280919.89 170189.67 0.62 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9672.22 6096.44 3575.77 0.63 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   92221.08 58100.27 34120.81 0.63 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9540.07 5930.05 3610.01 0.62 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 19026.36 18041.04 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 351752.39 333375.69 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 62504.34 59191.66 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 4066.49 3854.39 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 3242.83 3073.53 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 5927.70 5616.00 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 2512.97 2382.76 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 122321.44 115913.30 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 81481.53 77212.16 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 122322.11 115913.94 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 70505.88 66814.59 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 17668.25 16741.22 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 11632.41 11022.02 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 17668.43 16741.38 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 10788.67 10222.71 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 22570.87 19567.51 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 171567.88 151298.88 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 13282.34 11984.64 -
CAV_BAS HEATING COIL Coil:Heating:Water 253780.16 206608.38 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   451109.56 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9672.22 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   92221.08 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9540.07 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   13450.69 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   621.37 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6213.66 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   621.37 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 9.81 21196.60 2160.95 1.00 1.12 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 92.79 200508.47 2160.95 1.00 1.08 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 10.59 22761.89 2149.46 1.00 1.12 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.57 9441.50 1695.65 1.00 1.16 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 21.90 36119.35 1649.25 1.00 1.14 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.48 540.96 1120.11 1.00 1.62 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.60 5153.18 1120.11 1.00 1.16 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 518.96 1120.11 1.00 1.64 General NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.122533 25249.54 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.011938 3595.30 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.122533 17481.11 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013777 3513.73 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.144934 43650.89 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 75181.82 75181.82 27.05 5.568 5.568 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00746 34.82 0.00915 1.200 0.00
CORE_BOTTOM 80291.26 80291.26 32.17 5.946 5.946 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00739 34.82 0.00915 1.078 0.00
CORE_MID 760763.87 760763.87 304.78 56.330 56.330 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 24.00 24.00 0.00741 34.82 0.00915 10.778 0.00
CORE_TOP 78353.55 78353.55 31.39 5.856 5.856 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:50:00 24.00 24.00 0.00739 42.00 0.00916 1.078 0.00
PERIMETER_BOT_ZN_3 15711.61 15711.61 50.13 1.174 1.174 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:20:00 24.00 24.00 0.00727 41.81 0.00916 0.135 0.00
PERIMETER_BOT_ZN_2 12311.35 12311.35 60.95 0.920 0.920 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:10:00 24.00 24.00 0.00722 38.56 0.00915 0.087 0.00
PERIMETER_BOT_ZN_1 15994.18 15994.18 51.03 1.195 1.195 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 24.00 24.00 0.00727 42.00 0.00916 0.135 0.00
PERIMETER_BOT_ZN_4 16136.29 16136.29 79.89 1.206 1.206 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 24.00 24.00 0.00717 41.16 0.00916 0.087 0.00
PERIMETER_MID_ZN_3 152555.09 152555.09 486.75 11.402 11.402 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 24.00 24.00 0.00732 41.71 0.00916 1.353 0.00
PERIMETER_MID_ZN_2 127483.44 127483.44 631.18 9.528 9.528 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:20:00 24.00 24.00 0.00725 38.80 0.00915 0.872 0.00
PERIMETER_MID_ZN_1 153924.08 153924.08 491.11 11.505 11.505 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:10:00 24.00 24.00 0.00731 42.00 0.00916 1.353 0.00
PERIMETER_MID_ZN_4 136545.98 136545.98 676.05 10.206 10.206 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:30:00 24.00 24.00 0.00723 41.03 0.00916 0.872 0.00
PERIMETER_TOP_ZN_3 17951.06 17951.06 57.28 1.342 1.342 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:40:00 24.00 24.00 0.00728 41.61 0.00916 0.135 0.00
PERIMETER_TOP_ZN_2 13660.96 13660.96 67.64 1.021 1.021 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 10:40:00 24.00 24.00 0.00724 39.28 0.00915 0.087 0.00
PERIMETER_TOP_ZN_1 17986.16 17986.16 57.39 1.344 1.344 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:40:00 24.00 24.00 0.00728 42.00 0.00916 0.135 0.00
PERIMETER_TOP_ZN_4 15436.93 15436.93 76.43 1.154 1.154 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:20:00 24.00 24.00 0.00722 41.16 0.00916 0.087 0.00
DATACENTER_BOT_ZN_6 8193.50 8193.50 226.32 0.483 0.483 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 27.00 27.00 0.00700 32.36 0.00914 0.016 0.00
DATACENTER_MID_ZN_6 78050.85 78050.85 2155.94 4.601 4.601 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 27.00 27.00 0.00700 32.36 0.00914 0.156 0.00
DATACENTER_TOP_ZN_6 7859.30 7859.30 217.09 0.463 0.463 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 27.00 27.00 0.00709 40.90 0.00916 0.016 0.00
DATACENTER_BASEMENT_ZN_6 371509.01 371509.01 474.06 21.900 21.900 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:00:00 27.00 27.00 0.00704 33.17 0.00914 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.81 0.00607 6.30 0.00607 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 23.39 0.00607 6.30 0.00607 1.078 0.00
CORE_MID 164331.49 164331.49 65.83 7.043 10.778 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 6.30 0.00607 10.778 0.00
CORE_TOP 43077.00 43077.00 17.26 1.872 1.872 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 6.30 0.00607 1.078 0.00
PERIMETER_BOT_ZN_3 1670.33 1670.33 5.33 0.073 0.135 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00775 6.30 0.00607 0.135 0.00
PERIMETER_BOT_ZN_2 1437.37 1437.37 7.12 0.062 0.087 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00778 6.30 0.00607 0.087 0.00
PERIMETER_BOT_ZN_1 3534.95 3534.95 11.28 0.153 0.153 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00785 6.30 0.00607 0.135 0.00
PERIMETER_BOT_ZN_4 149.21 149.21 0.74 0.007 0.087 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00717 6.30 0.00607 0.087 0.00
PERIMETER_MID_ZN_3 85655.62 85655.62 273.30 3.737 3.737 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 6.30 0.00607 1.353 0.00
PERIMETER_MID_ZN_2 57054.55 57054.55 282.48 2.489 2.489 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 6.30 0.00607 0.872 0.00
PERIMETER_MID_ZN_1 85656.09 85656.09 273.30 3.737 3.737 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00790 6.30 0.00607 1.353 0.00
PERIMETER_MID_ZN_4 49381.77 49381.77 244.49 2.153 2.153 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00787 6.30 0.00607 0.872 0.00
PERIMETER_TOP_ZN_3 12366.35 12366.35 39.46 0.540 0.540 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 6.30 0.00607 0.135 0.00
PERIMETER_TOP_ZN_2 8141.55 8141.55 40.31 0.356 0.356 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 6.30 0.00607 0.087 0.00
PERIMETER_TOP_ZN_1 12366.48 12366.48 39.46 0.540 0.540 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 6.30 0.00607 0.135 0.00
PERIMETER_TOP_ZN_4 7551.70 7551.70 37.39 0.330 0.330 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00794 6.30 0.00607 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00700 6.30 0.00607 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 25.16 0.00698 6.30 0.00607 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 24.11 0.00620 6.30 0.00607 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00700 6.30 0.00607 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.81 9.81 1.54 1.54 9.8089 2.8519 9.8089 0.2907 0.3000
VAV_MID WITH REHEAT 92.79 92.79 22.89 22.89 92.7873 27.8415 92.7873 0.3001 0.3000
VAV_TOP WITH REHEAT 10.59 10.59 3.64 3.64 10.5896 3.6385 10.5896 0.3436 0.3000
CAV_BAS 5.57 5.57 1.20 1.20 5.5681 5.5681 5.5681 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.90 21.90 0.34 0.34 21.9005 21.9002 21.9005 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.48 0.48 0.02 0.02 0.4830 0.4830 0.4830 1.0000 1.0000
AIRLOOP DATACENTER MID 4.60 4.60 0.16 0.16 4.6006 4.6006 4.6006 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.46 0.46 0.02 0.02 0.4633 0.4633 0.4633 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 19026.362 19026.362 1.938545 0.00016645 383.557   1/21 00:10:00   1/21 00:10:00 19026.36 19026.36 1.938545 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 0.00 0.00 19096.52 19096.52
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 351752.387 351752.387 19.095809 0.00307728 7765.614 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 351752.39 351752.39 19.095809 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 164331.49 0.00 352965.50 352965.50
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 62504.337 62504.337 1.979399 0.00054682 1623.563 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 62504.34 62504.34 1.979399 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00800000 50.4125 43077.00 0.00 62695.71 62695.71
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 4066.492 4066.492 0.244253 0.00003558 88.034 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4066.49 4066.49 0.244253 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00775217 48.8704 1670.33 0.00 4080.67 4080.67
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 3242.828 3242.828 0.184031 0.00002837 70.958 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3242.83 3242.83 0.184031 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00777922 49.0390 1437.37 0.00 3254.06 3254.06
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 5927.700 5927.700 0.243864 0.00005186 140.168 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5927.70 5927.70 0.243864 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00784759 49.4646 3534.95 0.00 5947.06 5947.06
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 2512.967 2512.967 0.241205 0.00002198 50.967 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 2512.97 2512.97 0.241205 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00716599 45.2170 149.21 0.00 2522.20 2522.20
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 122321.443 122321.443 3.736591 0.00107012 3228.465 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 122321.44 122321.44 3.736591 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00790031 49.7931 85655.62 0.00 122740.94 122740.94
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 81481.535 81481.535 2.489322 0.00071284 2150.455 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 81481.53 81481.53 2.489322 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00790358 49.8134 57054.55 0.00 81760.17 81760.17
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 122322.114 122322.114 3.736611 0.00107013 3228.483 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 122322.11 122322.11 3.736611 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00790031 49.7931 85656.09 0.00 122741.61 122741.61
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 70505.877 70505.877 2.152877 0.00061682 1861.234 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 70505.88 70505.88 2.152877 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00786997 49.6044 49381.77 0.00 70750.20 70750.20
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 17668.253 17668.253 0.540259 0.00015457 466.109 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17668.25 17668.25 0.540259 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00794874 50.0942 12366.35 0.00 17727.30 17727.30
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 11632.412 11632.412 0.355715 0.00010177 306.869 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11632.41 11632.41 0.355715 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00794965 50.0999 8141.55 0.00 11671.23 11671.23
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 17668.425 17668.425 0.540265 0.00015457 466.114 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17668.43 17668.43 0.540265 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00794874 50.0942 12366.48 0.00 17727.48 17727.48
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 10788.668 10788.668 0.329853 0.00009438 284.634 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10788.67 10788.67 0.329853 12.80 11.37 0.00800000 40.00 20.89 0.00800000 6.30 0.00607234 6.30 0.0000 21.00 0.00793757 50.0248 7551.70 0.00 10824.85 10824.85
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 233283.980 -999.000 9.808941 0.00992444 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 233283.98 211663.82 9.808941 28.81 17.23 0.00783253 10.99 9.55 0.00700000 42.00 0.00915790 22.26 25.8763 24.00 0.00734896 38.6354 127037.73 0.00 237639.92 223761.68
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 22570.865 22570.865 2.942682 0.00019746 394.689 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22570.87 22570.87 2.942682 6.30 6.30 0.00613865 12.80 11.37 0.00800000 6.30 0.00607234 6.30 86.2543 22.54 0.00665833 38.2686 6791.85 0.00 23690.11 23690.11
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2280072.413 -999.000 92.787326 0.09699955 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 2280072.41 2054737.19 92.787326 29.27 17.45 0.00791354 10.99 9.55 0.00700000 42.00 0.00915790 22.26 27.3550 24.00 0.00739846 38.8928 1160020.42 0.00 2321039.26 2167672.23
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 171567.883 171567.883 27.836198 0.00150095 3027.846 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 171567.88 171567.88 27.836198 7.57 7.11 0.00623743 12.80 11.37 0.00800000 6.30 0.00607234 6.30 91.1833 21.00 0.00793397 50.0022 442079.52 0.00 183176.43 183176.43
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 243601.617 -999.000 10.589565 0.01036338 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 243601.62 222071.32 10.589565 28.32 17.01 0.00777160 11.00 9.55 0.00700000 42.00 0.00915790 22.26 23.9688 24.00 0.00733343 38.5549 141400.81 0.00 248248.49 235266.64
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 13282.337 13282.337 3.176869 0.00011620 237.356 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 12:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13282.34 13282.34 3.176869 9.26 8.16 0.00645544 12.80 11.37 0.00800000 6.30 0.00607234 6.30 79.8959 21.00 0.00797793 50.2754 57545.58 0.00 14509.80 14509.80
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 123307.645 -999.000 5.568055 0.00524579 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 123307.64 110638.64 5.568055 27.70 16.89 0.00788349 11.38 9.72 0.00700000 39.77 0.00915417 21.63 21.5543 24.00 0.00749333 39.3855 68353.97 0.00 125668.08 118261.45
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 253780.157 253780.157 5.568055 0.00222018 5777.807 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 253780.16 253780.16 5.568055 1.36 1.36 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 21.5543 25.81 0.00607234 28.7199 0.00 0.00 218646.00 218646.00
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 451109.565 280919.893 21.900509 0.01104764 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00 405188.86 401471.72 -999.0 28.66 16.55 0.00707492 12.80 10.34 0.00700000 42.00 0.00915790 22.26 -999.0000 27.00 0.00704219 30.9981 371036.55 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9672.218 6096.444 0.482956 0.00023687 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 8642.49 8567.20 -999.0 28.14 16.36 0.00706933 12.80 10.34 0.00700000 32.36 0.00914193 19.41 -999.0000 27.00 0.00700000 30.8097 8144.83 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92221.076 58100.267 4.600613 0.00225849 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 82416.93 81663.87 -999.0 28.15 16.37 0.00707278 12.80 10.34 0.00700000 32.36 0.00914193 19.41 -999.0000 27.00 0.00700000 30.8097 77687.88 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9540.067 5930.055 0.463312 0.00023364 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 8569.33 8399.76 -999.0 28.45 16.55 0.00716170 12.80 10.34 0.00700000 41.29 0.00915671 22.06 -999.0000 27.00 0.00709201 31.2132 7855.92 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 451109.565 451109.565 21.900509 0.01104764 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 451109.56 451109.56 21.900509 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 1.5451 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9672.218 9672.218 0.482956 0.00023687 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9672.22 9672.22 0.482956 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.2368 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 92221.076 92221.076 4.600613 0.00225849 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 92221.08 92221.08 4.600613 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3979 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9540.067 9540.067 0.463312 0.00023364 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9540.07 9540.07 0.463312 6.30 6.30 0.00607234 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3740 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 13450.693 13450.693 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 13450.69 13450.69 21.900509 0.10 0.10 0.00698567 40.00 20.89 0.00800000 6.30 0.00607234 6.30 1.5451 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 621.366 621.366 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 621.37 621.37 0.482956 0.20 0.20 0.00696997 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.2368 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6213.663 6213.663 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6213.66 6213.66 4.600613 0.21 0.21 0.00695118 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3979 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 621.366 621.366 -999.0 -999.0 -999.000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 621.37 621.37 0.463312 0.21 0.21 0.00619689 40.00 20.89 0.00800000 6.30 0.00607234 6.30 3.3740 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 19026.362 19026.362 1.938545 0.00016645 383.557 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 1.3668 1.394258   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 19026.36 19026.36 1.0000 2.27543554 1.938545 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.16643393 60.00 32.22 27.78 0.000 19026.36 6.30 0.00607234 6.30 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 50.4125 0.00 0.00 19096.52 19096.52 2.27543554 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 351752.387 351752.387 19.095809 0.00307728 7765.614 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 25.2680 25.776524 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 351752.39 351752.39 1.0000 22.41438330 19.095809 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 3.07696942 60.00 32.22 27.78 0.000 351752.39 6.30 0.00607234 6.30 0.00000000 0.0000 20.58 0.00800000 21.00 0.00800000 50.4125 164331.49 0.00 352965.50 352965.50 22.41438330 12.80 11.60 0.00800000 33059.8 28.24 17.44 0.00800000 48807.1
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 62504.337 62504.337 1.979399 0.00054682 1623.563 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 4.4900 4.580337 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 62504.34 62504.34 1.0000 2.32339001 1.979399 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.54675943 60.00 32.22 27.78 0.000 62504.34 6.30 0.00607234 6.30 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 50.4125 43077.00 0.00 62695.71 62695.71 2.32339001 12.80 11.60 0.00800000 33059.8 39.26 20.96 0.00800000 60044.4
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 4066.492 4066.492 0.244253 0.00003558 88.034 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 0.2921 0.297994 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4066.49 4066.49 1.0000 0.28670089 0.244253 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.03557182 60.00 32.22 27.78 0.000 4066.49 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00775217 21.00 0.00775217 48.8704 1670.33 0.00 4080.67 4080.67 0.28670089 12.80 11.60 0.00800000 33059.8 26.76 16.93 0.00800000 47293.0
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 3242.828 3242.828 0.184031 0.00002837 70.958 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 0.2329 0.237635 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3242.83 3242.83 1.0000 0.21601293 0.184031 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.02836678 60.00 32.22 27.78 0.000 3242.83 6.30 0.00607234 6.30 0.00000000 0.0000 20.87 0.00777922 21.00 0.00777922 49.0390 1437.37 0.00 3254.06 3254.06 0.21601293 12.80 11.60 0.00800000 33059.8 27.57 17.21 0.00800000 48124.0
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 5927.700 5927.700 0.243864 0.00005186 140.168 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 0.4258 0.434384 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5927.70 5927.70 1.0000 0.28624446 0.243864 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.05185281 60.00 32.22 27.78 0.000 5927.70 6.30 0.00607234 6.30 0.00000000 0.0000 20.87 0.00784759 21.00 0.00784759 49.4646 3534.95 0.00 5947.06 5947.06 0.28624446 12.80 11.60 0.00800000 33059.8 33.17 19.08 0.00800000 53836.0
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 2512.967 2512.967 0.241205 0.00002198 50.967 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 0.1805 0.184151 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 2512.97 2512.97 1.0000 0.28312332 0.241205 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.02198229 60.00 32.22 27.78 0.000 2512.97 6.30 0.00607234 6.30 0.00000000 0.0000 20.99 0.00716599 21.00 0.00716599 45.2170 149.21 0.00 2522.20 2522.20 0.28312332 12.80 11.60 0.00800000 33059.8 21.54 15.05 0.00800000 41968.3
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 122321.443 122321.443 3.736591 0.00107012 3228.465 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 8.7869 8.963753 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 122321.44 122321.44 1.0000 4.38595607 3.736591 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.07001218 60.00 32.22 27.78 0.000 122321.44 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00790031 21.00 0.00790031 49.7931 85655.62 0.00 122740.94 122740.94 4.38595607 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61044.8
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 81481.535 81481.535 2.489322 0.00071284 2150.455 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 5.8532 5.970992 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 81481.53 81481.53 1.0000 2.92193049 2.489322 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.71276329 60.00 32.22 27.78 0.000 81481.53 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00790358 21.00 0.00790358 49.8134 57054.55 0.00 81760.17 81760.17 2.92193049 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61041.4
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 122322.114 122322.114 3.736611 0.00107013 3228.483 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 8.7870 8.963802 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 122322.11 122322.11 1.0000 4.38597986 3.736611 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 1.07001805 60.00 32.22 27.78 0.000 122322.11 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00790031 21.00 0.00790031 49.7931 85656.09 0.00 122741.61 122741.61 4.38597986 12.80 11.60 0.00800000 33059.8 40.24 21.25 0.00800000 61044.8
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 70505.877 70505.877 2.152877 0.00061682 1861.234 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 5.0648 5.166693 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 70505.88 70505.88 1.0000 2.52701524 2.152877 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.61675325 60.00 32.22 27.78 0.000 70505.88 6.30 0.00607234 6.30 0.00000000 0.0000 20.91 0.00786997 21.00 0.00786997 49.6044 49381.77 0.00 70750.20 70750.20 2.52701524 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61057.4
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 17668.253 17668.253 0.540259 0.00015457 466.109 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 1.2692 1.294735 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17668.25 17668.25 1.0000 0.63414873 0.540259 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.15455381 60.00 32.22 27.78 0.000 17668.25 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00794874 21.00 0.00794874 50.0942 12366.35 0.00 17727.30 17727.30 0.63414873 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.3
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 11632.412 11632.412 0.355715 0.00010177 306.869 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 0.8356 0.852427 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11632.41 11632.41 1.0000 0.41753340 0.355715 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.10175503 60.00 32.22 27.78 0.000 11632.41 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00794965 21.00 0.00794965 50.0999 8141.55 0.00 11671.23 11671.23 0.41753340 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61012.6
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 17668.425 17668.425 0.540265 0.00015457 466.114 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 1.2692 1.294748 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17668.43 17668.43 1.0000 0.63415491 0.540265 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.15455533 60.00 32.22 27.78 0.000 17668.43 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00794874 21.00 0.00794874 50.0942 12366.48 0.00 17727.48 17727.48 0.63415491 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61014.3
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 10788.668 10788.668 0.329853 0.00009438 284.634 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 0.7750 0.790597 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10788.67 10788.67 1.0000 0.38717649 0.329853 12.80 11.37 0.00800000 33059.8 40.00 20.89 0.00800000 60796.0 0.09437435 60.00 32.22 27.78 0.000 10788.67 6.30 0.00607234 6.30 0.00000000 0.0000 20.95 0.00793757 21.00 0.00793757 50.0248 7551.70 0.00 10824.85 10824.85 0.38717649 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61018.3
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 233283.980 -999.000 9.808941 0.00992444 -999.000 -999.0000 1.00000 1.00000 1019.4003 1004.8586 1.1738 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.808941 11.51359212   4197.9300 999.8980 122.52065959 12.27 6.67 5.60 2880265.65 8.0994 8.099391 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 233283.98 211663.82 1.0000 11.51359212 9.808941 28.81 17.23 0.00783253 48958.5 10.99 9.55 0.00700000 28696.9 9.92342738 6.67 12.27 5.60 21196.599 212087.38 42.00 0.00915790 22.26 2.53819000 25.8763 24.00 0.00734896 24.00 0.00734896 38.6354 127037.73 0.00 237639.92 223761.68 11.51359212 28.81 17.50 0.00783253 48958.5 9.75 9.59 0.00735403 28318.6
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 22570.865 22570.865 2.942682 0.00019746 394.689 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.808941 11.51359212   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 1.6214 1.654000 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22570.87 22570.87 1.0000 3.45407764 2.942682 6.30 6.30 0.00613865 21751.8 12.80 11.37 0.00800000 33059.8 0.19743963 60.00 32.22 27.78 0.000 22570.87 6.30 0.00607234 6.30 2.53819000 86.2543 6.28 0.00655470 22.54 0.00665833 38.2686 6791.85 0.00 23690.11 23690.11 3.45407764 2.80 2.80 0.00613865 18197.9 9.55 8.14 0.00613865 25056.5
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2280072.413 -999.000 92.787326 0.09699955 -999.000 -999.0000 1.00000 1.00000 1019.5509 1004.8586 1.1738 VAV_MID WITH REHEAT FAN Fan:VariableVolume 92.787326 108.91241465   4197.9300 999.8980 122.52065959 12.27 6.67 5.60 2880265.65 79.1619 79.161879 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 2280072.41 2054737.19 1.0000 108.91241465 92.787326 29.27 17.45 0.00791354 49632.1 10.99 9.55 0.00700000 28697.2 96.98965633 6.67 12.27 5.60 200508.471 2079563.94 42.00 0.00915790 22.26 25.38195000 27.3550 24.00 0.00739846 24.00 0.00739846 38.8928 1160020.42 0.00 2321039.26 2167672.23 108.91241465 29.27 17.72 0.00791354 49632.1 9.75 9.59 0.00735453 28321.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 171567.883 171567.883 27.836198 0.00150095 3027.846 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_MID WITH REHEAT FAN Fan:VariableVolume 92.787326 108.91241465   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 12.3245 12.572548 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 171567.88 171567.88 1.0000 32.67372439 27.836198 7.57 7.11 0.00623743 23298.4 12.80 11.37 0.00800000 33059.8 1.50079757 60.00 32.22 27.78 0.000 171567.88 6.30 0.00607234 6.30 25.38195000 91.1833 20.75 0.00794474 21.00 0.00793397 50.0022 442079.52 0.00 183176.43 183176.43 32.67372439 2.80 2.80 0.00623743 18445.4 8.32 7.66 0.00623743 24051.7
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 243601.617 -999.000 10.589565 0.01036338 -999.000 -999.0000 1.00000 1.00000 1019.2870 1004.8586 1.1738 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.589565 12.42987736   4197.9300 999.8980 122.52065959 12.27 6.67 5.60 2880265.65 8.4576 8.457609 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 15:30:00 Sensible 243601.62 222071.32 1.0000 12.42987736 10.589565 28.32 17.01 0.00777160 48304.5 11.00 9.55 0.00700000 28706.4 10.36231876 6.67 12.27 5.60 22761.895 220839.72 42.00 0.00915790 22.26 2.53819000 23.9688 24.00 0.00733343 24.00 0.00733343 38.5549 141400.81 0.00 248248.49 235266.64 12.42987736 28.32 17.28 0.00777160 48304.5 9.75 9.59 0.00735700 28332.6
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 13282.337 13282.337 3.176869 0.00011620 237.356 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 10.589565 12.42987736   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 0.9541 0.973334 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 12:00:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13282.34 13282.34 1.0000 3.72896321 3.176869 9.26 8.16 0.00645544 25555.8 12.80 11.37 0.00800000 33059.8 0.11618783 60.00 32.22 27.78 0.000 13282.34 6.30 0.00607234 6.30 2.53819000 79.8959 21.00 0.00797793 21.00 0.00797793 50.2754 57545.58 0.00 14509.80 14509.80 3.72896321 2.80 2.80 0.00645544 18991.8 6.63 6.63 0.00645544 22882.9
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 123307.645 -999.000 5.568055 0.00524579 -999.000 -999.0000 1.00000 1.00000 1019.4950 1004.8586 1.1738 CAV_BAS FAN Fan:ConstantVolume 5.568055 6.53570200   4197.9300 999.8980 122.52065959 12.27 6.67 5.60 2880265.65 4.2811 4.281121 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 11:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 08:00:00 Sensible 123307.64 110638.64 1.0000 6.53570200 5.568055 27.70 16.89 0.00788349 47959.6 11.38 9.72 0.00700000 29092.8 5.24525713 6.67 12.27 5.60 9441.497 113866.15 39.77 0.00915417 21.63 1.20015641 21.5543 24.00 0.00749333 24.00 0.00749333 39.3855 68353.97 0.00 125668.08 118261.45 6.53570200 27.70 17.16 0.00788349 47959.6 9.95 9.77 0.00743368 28731.7
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 253780.157 253780.157 5.568055 0.00222018 5777.807 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 CAV_BAS FAN Fan:ConstantVolume 5.568055 6.53570200   4197.9300 999.8980 11.93709985 54.44 82.22 27.78 1392086.62 18.2302 18.597089 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 253780.16 253780.16 1.0000 6.53570200 5.568055 1.36 1.36 0.00607234 16566.4 40.00 20.89 0.00800000 60796.0 2.21995304 60.00 32.22 27.78 0.000 253780.16 6.30 0.00607234 6.30 1.20015641 21.5543 0.00 0.00607234 25.81 0.00607234 28.7199 0.00 0.00 218646.00 218646.00 6.53570200 12.80 9.56 0.00607234 28193.0 45.72 21.48 0.00607234 61647.1
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 451109.565 280919.893 21.900509 0.01104764 -999.000 -999.0000 -999.00000 -999.00000 1017.9919 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 14:00:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 07:10:00 Sensible 405188.86 401471.72 0.8982 -999.0 -999.0 28.66 16.55 0.00707492 46869.4 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 405188.86 42.00 0.00915790 22.26 0.33839277 -999.0000 27.00 0.00704219 27.00 0.00704219 30.9981 371036.55 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9672.218 6096.444 0.482956 0.00023687 -999.000 -999.0000 -999.00000 -999.00000 1017.9815 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 06:40:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 Sensible 8642.49 8567.20 0.8935 -999.0 -999.0 28.14 16.36 0.00706933 46331.0 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8642.49 32.36 0.00914193 19.41 0.01563234 -999.0000 27.00 0.00700000 27.00 0.00700000 30.8097 8144.83 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 92221.076 58100.267 4.600613 0.00225849 -999.000 -999.0000 -999.00000 -999.00000 1017.9879 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 06:40:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 05:20:00 Sensible 82416.93 81663.87 0.8937 -999.0 -999.0 28.15 16.37 0.00707278 46348.6 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 82416.93 32.36 0.00914193 19.41 0.15632344 -999.0000 27.00 0.00700000 27.00 0.00700000 30.8097 77687.88 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9540.067 5930.055 0.463312 0.00023364 -999.000 -999.0000 -999.00000 -999.00000 1018.1532 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:10:00 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN CLG .4% CONDNS DB=>MWB 6/21 16:40:00 Sensible 8569.33 8399.76 0.8982 -999.0 -999.0 28.45 16.55 0.00716170 46880.4 12.80 10.34 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8569.33 41.29 0.00915671 22.06 0.01563234 -999.0000 27.00 0.00709201 27.00 0.00709201 31.2132 7855.92 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 451109.565 451109.565 21.900509 0.01104764 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 451109.56 451109.56 1.0000 25.70649850 21.900509 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 451109.56 6.30 0.00607234 6.30 0.33839277 1.5451 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9672.218 9672.218 0.482956 0.00023687 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9672.22 9672.22 1.0000 0.56688676 0.482956 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9672.22 6.30 0.00607234 6.30 0.01563234 3.2368 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 92221.076 92221.076 4.600613 0.00225849 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 92221.08 92221.08 1.0000 5.40013208 4.600613 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 92221.08 6.30 0.00607234 6.30 0.15632344 3.3979 0.00 0.00698209 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9540.067 9540.067 0.463312 0.00023364 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1738 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9540.07 9540.07 1.0000 0.54382862 0.463312 6.30 6.30 0.00607234 21588.2 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9540.07 6.30 0.00607234 6.30 0.01563234 3.3740 0.00 0.00620124 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 13450.693 13450.693 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.900509 25.70649850   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 13450.69 13450.69 1.0000 25.70649850 21.900509 0.10 0.10 0.00698567 17569.8 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 13450.69 6.30 0.00607234 6.30 0.33839277 1.5451 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 621.366 621.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.482956 0.56688676   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 621.37 621.37 1.0000 0.56688676 0.482956 0.20 0.20 0.00696997 17639.0 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 621.37 6.30 0.00607234 6.30 0.01563234 3.2368 0.00 0.00700000 27.00 0.00700000 30.8097 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6213.663 6213.663 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.600613 5.40013208   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6213.66 6213.66 1.0000 5.40013208 4.600613 0.21 0.21 0.00695118 17602.4 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6213.66 6.30 0.00607234 6.30 0.15632344 3.3979 0.00 0.00698209 25.16 0.00698209 34.2539 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 621.366 621.366 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1738 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.463312 0.54382862   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.DELHI-SAFDARJUNG.AP_DELHI_IND ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 621.37 621.37 1.0000 0.54382862 0.463312 0.21 0.21 0.00619689 15714.1 40.00 20.89 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 621.37 6.30 0.00607234 6.30 0.01563234 3.3740 0.00 0.00620124 24.11 0.00620124 32.4414 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 5309.50 1653.33 1653.00
CORE_BOTTOM 5343.83 23.00 13.33
CORE_MID 4638.00 307.50 23.00
CORE_TOP 4222.00 1123.33 26.83
PERIMETER_BOT_ZN_3 4603.50 797.83 173.67
PERIMETER_BOT_ZN_2 4744.83 816.00 241.33
PERIMETER_BOT_ZN_1 5218.50 621.67 333.33
PERIMETER_BOT_ZN_4 5479.33 758.50 623.33
PERIMETER_MID_ZN_3 3991.83 1679.83 273.00
PERIMETER_MID_ZN_2 3606.00 1316.00 379.17
PERIMETER_MID_ZN_1 4996.17 892.17 427.17
PERIMETER_MID_ZN_4 4475.67 1399.00 404.33
PERIMETER_TOP_ZN_3 3964.00 2093.33 460.83
PERIMETER_TOP_ZN_2 4238.67 1813.67 480.00
PERIMETER_TOP_ZN_1 4743.67 1260.33 472.00
PERIMETER_TOP_ZN_4 4282.83 1802.00 491.00
DATACENTER_BOT_ZN_6 5943.00 1410.17 1410.17
DATACENTER_MID_ZN_6 5943.00 493.83 493.83
DATACENTER_TOP_ZN_6 5907.17 659.00 646.17
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 89.17 0.00 7.50
CORE_BOTTOM 0.00 7.83 0.00 0.00
CORE_MID 0.00 0.17 0.00 0.00
CORE_TOP 0.17 0.50 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 71.00 0.00 26.00
PERIMETER_BOT_ZN_2 0.00 77.67 0.00 47.50
PERIMETER_BOT_ZN_1 0.00 136.67 0.00 75.17
PERIMETER_BOT_ZN_4 0.00 358.00 0.00 106.17
PERIMETER_MID_ZN_3 0.00 49.83 0.00 18.67
PERIMETER_MID_ZN_2 0.00 85.33 0.00 52.17
PERIMETER_MID_ZN_1 0.00 110.50 0.00 64.67
PERIMETER_MID_ZN_4 0.00 130.33 0.00 43.33
PERIMETER_TOP_ZN_3 0.67 91.17 0.00 35.50
PERIMETER_TOP_ZN_2 0.33 127.50 0.00 63.67
PERIMETER_TOP_ZN_1 0.33 142.00 0.00 69.17
PERIMETER_TOP_ZN_4 0.33 154.67 0.00 52.50
DATACENTER_BOT_ZN_6 0.00 660.17 0.00 517.00
DATACENTER_MID_ZN_6 0.00 537.50 0.00 453.83
DATACENTER_TOP_ZN_6 0.00 368.83 0.00 321.33
DATACENTER_BASEMENT_ZN_6 0.00 1290.33 0.00 923.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 0.67 1747.67 0.00 1100.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.75 149.60 6779.02 0.533 0.000 0.000 0.000
CORE_BOTTOM 56.35 134.35 6849.35 0.487 0.000 0.000 0.000
CORE_MID 56.35 134.35 6849.35 0.468 0.000 0.000 0.000
CORE_TOP 56.35 134.35 6849.35 0.450 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.08 16.87 860.00 0.593 0.017 0.000 0.000
PERIMETER_BOT_ZN_2 4.56 10.87 554.22 0.690 0.017 0.000 0.000
PERIMETER_BOT_ZN_1 7.08 16.87 860.02 0.770 0.017 0.000 0.000
PERIMETER_BOT_ZN_4 4.56 10.87 554.22 1.069 0.017 0.000 0.000
PERIMETER_MID_ZN_3 7.08 16.87 860.00 0.611 0.039 0.000 0.000
PERIMETER_MID_ZN_2 3.99 10.87 554.22 0.757 0.042 0.000 0.000
PERIMETER_MID_ZN_1 7.08 16.87 860.02 0.853 0.039 0.000 0.000
PERIMETER_MID_ZN_4 4.56 10.87 554.22 0.861 0.041 0.000 0.000
PERIMETER_TOP_ZN_3 7.08 16.87 860.00 0.612 0.049 0.000 0.000
PERIMETER_TOP_ZN_2 4.56 10.87 554.22 0.784 0.051 0.000 0.000
PERIMETER_TOP_ZN_1 7.08 16.87 860.02 0.821 0.049 0.000 0.000
PERIMETER_TOP_ZN_4 4.56 10.87 554.22 0.844 0.051 0.000 0.000
DATACENTER_BOT_ZN_6 0.82 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.82 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.82 1.95 99.34 0.590 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.69 42.18 1911.37 0.665 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.75 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 56.35 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 56.35 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 56.35 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.08 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.08 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.08 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.99 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.08 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.08 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.56 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.08 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.56 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.82 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.82 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.82 1.95 99.34 0.545 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.69 42.18 1911.37 0.613 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.75 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 56.35 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 56.35 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 56.35 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.08 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.08 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.08 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.99 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.08 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.08 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.08 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.56 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.82 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.82 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.82 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.69 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1040.03 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 23821144.57 0.00 23821144.57 0.00 23821144.57 37848132.68 3246.56 5513.44 0.00 719.50
CORE_BOTTOM 24247717.05 0.00 24247717.05 0.00 24247717.05 33990283.35 7580.00 88.46 1091.54 1349.10
CORE_MID 0.21E+09 0.00 0.21E+09 0.00 0.21E+09 0.34E+09 7620.43 317.86 821.71 807.06
CORE_TOP 20714760.06 0.00 20714760.06 0.00 20714760.06 33990283.35 8409.18 52.14 298.69 811.90
PERIMETER_BOT_ZN_3 3583031.23 0.00 3583031.23 135485.55 3718516.78 4267819.30 5740.40 123.17 2896.43 1349.10
PERIMETER_BOT_ZN_2 2677702.40 0.00 2677702.40 90323.64 2768026.04 2750345.05 2962.12 151.68 5646.20 1349.10
PERIMETER_BOT_ZN_1 4474710.85 0.00 4474710.85 135485.55 4610196.40 4267912.63 4298.69 49.38 4411.93 1349.10
PERIMETER_BOT_ZN_4 4161878.82 0.00 4161878.82 90323.64 4252202.46 2750345.05 2143.78 0.34 6615.88 1349.10
PERIMETER_MID_ZN_3 34114116.90 0.00 34114116.90 317743.67 34431860.57 42678193.03 5768.10 217.84 2774.06 807.06
PERIMETER_MID_ZN_2 28205769.50 0.00 28205769.50 211828.97 28417598.47 27503450.52 3071.05 50.45 5638.49 1716.06
PERIMETER_MID_ZN_1 46280118.34 0.00 46280118.34 317743.67 46597862.01 42679126.28 4044.61 421.12 4294.26 807.06
PERIMETER_MID_ZN_4 31051984.02 0.00 31051984.02 211828.97 31263812.99 27503450.52 2971.06 60.46 5728.48 807.06
PERIMETER_TOP_ZN_3 3461917.59 0.00 3461917.59 394502.81 3856420.40 4267819.30 3750.08 132.57 4877.34 811.90
PERIMETER_TOP_ZN_2 2827254.86 0.00 2827254.86 263001.69 3090256.55 2750345.05 2951.60 19.85 5788.55 811.90
PERIMETER_TOP_ZN_1 4511837.64 0.00 4511837.64 394502.81 4906340.45 4267912.63 2918.25 16.92 5824.83 811.90
PERIMETER_TOP_ZN_4 3086712.71 0.00 3086712.71 263001.69 3349714.40 2750345.05 2884.05 5.43 5870.52 811.90
DATACENTER_BOT_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_MID_ZN_6 4929815.99 0.00 4929815.99 0.00 4929815.99 4929815.99 0.00 8760.00 0.00 2817.00
DATACENTER_TOP_ZN_6 492981.60 0.00 492981.60 0.00 492981.60 492981.60 0.00 8760.00 0.00 2817.00
DATACENTER_BASEMENT_ZN_6 10671554.30 0.00 10671554.30 0.00 10671554.30 10671554.30 0.00 8760.00 0.00 2817.00
Total Facility 0.37E+10 0.00 0.37E+10 12358080.11 0.37E+10 0.50E+10 8759.86 8760.00 6999.59 3726.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 0.9681 0.0000 0.9681 0.0000 0.9681 1.2002 1149.06 4793.94 0.00
CORE_BOTTOM 0.8957 0.0000 0.8957 0.0000 0.8957 1.0778 4787.61 86.74 1068.66
CORE_MID 8.6059 0.0000 8.6059 0.0000 8.6059 10.7782 4821.45 310.23 811.32
CORE_TOP 0.8280 0.0000 0.8280 0.0000 0.8280 1.0778 5595.55 51.48 295.97
PERIMETER_BOT_ZN_3 0.1365 0.0000 0.1365 0.0039 0.1404 0.1353 3044.60 94.95 2803.45
PERIMETER_BOT_ZN_2 0.1024 0.0000 0.1024 0.0026 0.1050 0.0872 1468.08 147.11 4327.81
PERIMETER_BOT_ZN_1 0.1778 0.0000 0.1778 0.0039 0.1817 0.1353 1616.82 35.40 4290.78
PERIMETER_BOT_ZN_4 0.1588 0.0000 0.1588 0.0026 0.1614 0.0872 674.45 0.07 5268.49
PERIMETER_MID_ZN_3 1.4072 0.0000 1.4072 0.0091 1.4163 1.3533 3017.87 212.06 2713.08
PERIMETER_MID_ZN_2 1.1247 0.0000 1.1247 0.0062 1.1310 0.8721 958.25 30.64 4045.10
PERIMETER_MID_ZN_1 1.9697 0.0000 1.9697 0.0091 1.9788 1.3533 1363.90 378.38 4200.72
PERIMETER_MID_ZN_4 1.2790 0.0000 1.2790 0.0060 1.2851 0.8721 956.69 60.11 4926.20
PERIMETER_TOP_ZN_3 0.1412 0.0000 0.1412 0.0113 0.1524 0.1353 1734.61 124.43 4083.96
PERIMETER_TOP_ZN_2 0.1166 0.0000 0.1166 0.0075 0.1241 0.0872 944.97 19.64 4978.39
PERIMETER_TOP_ZN_1 0.1896 0.0000 0.1896 0.0113 0.2008 0.1353 911.48 14.68 5016.84
PERIMETER_TOP_ZN_4 0.1254 0.0000 0.1254 0.0075 0.1329 0.0872 878.65 5.40 5058.95
DATACENTER_BOT_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_MID_ZN_6 0.1563 0.0000 0.1563 0.0000 0.1563 0.1563 0.00 5943.00 0.00
DATACENTER_TOP_ZN_6 0.0156 0.0000 0.0156 0.0000 0.0156 0.0156 0.00 5943.00 0.00
DATACENTER_BASEMENT_ZN_6 0.3384 0.0000 0.3384 0.0000 0.3384 0.3384 0.00 5943.00 0.00
Total Facility 149.6397 0.0000 149.6397 0.3545 149.9943 158.4706 5942.86 5943.00 5401.74


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 53932977.31 0.00 53932977.31 48026705.38 2139.79 0.00 6620.21 1349.10
VAV_MID WITH REHEAT 0.49E+09 0.00 0.49E+09 0.48E+09 2871.73 0.00 5888.27 807.06
VAV_TOP WITH REHEAT 47674343.62 0.00 47674343.62 48026705.38 2877.93 0.00 5882.07 811.90
CAV_BAS 32820113.29 0.00 32820113.29 37848132.68 3246.56 0.00 5513.44 719.50
AIRLOOP DATACENTER BASEMENT 14702971.99 0.00 14702971.99 10671554.30 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER BOT 679216.39 0.00 679216.39 492981.60 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER MID 6792163.95 0.00 6792163.95 4929815.99 0.00 0.00 8760.00 2817.00
AIRLOOP DATACENTER TOP 679216.39 0.00 679216.39 492981.60 0.00 0.00 8760.00 2817.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 2.0271 0.0000 2.0271 1.5229 671.89 0.00 5271.11
VAV_MID WITH REHEAT 19.8857 0.0000 19.8857 15.2292 861.79 0.00 5081.21
VAV_TOP WITH REHEAT 1.9298 0.0000 1.9298 1.5229 872.82 0.00 5070.18
CAV_BAS 1.3338 0.0000 1.3338 1.2002 1149.06 0.00 4793.94
AIRLOOP DATACENTER BASEMENT 0.4662 0.0000 0.4662 0.3384 0.00 0.00 5943.00
AIRLOOP DATACENTER BOT 0.0215 0.0000 0.0215 0.0156 0.00 0.00 5943.00
AIRLOOP DATACENTER MID 0.2154 0.0000 0.2154 0.1563 0.00 0.00 5943.00
AIRLOOP DATACENTER TOP 0.0215 0.0000 0.0215 0.0156 0.00 0.00 5943.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.00 0.00 0.00 0.00 0.00 6620.21 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.00 0.00 0.00 0.00 0.00 5888.27 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.00 0.00 0.00 0.00 0.00 5882.07 0.00 0.00 0.00
CAV_BAS 0.00 5513.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 8760.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 2.2855 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 23.2594 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 2.2621 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6539 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4662 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2154 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0215 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1380
Defaulted Fields 1179
Fields with Defaults 3862
Autosized Fields 330
Autosizable Fields 409
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
Electricity:Building 17955.23 247233.96 01-JAN-08:50 1047565.99 29-DEC-17:00
Electricity:Zone:BASEMENT 602.14 14319.77 01-JAN-00:10 28977.00 02-JAN-08:10
Electricity:SpaceType:GENERAL 17955.23 247233.96 01-JAN-08:50 1047565.99 29-DEC-17:00
InteriorLights:Electricity 2741.82 13024.70 01-JAN-08:50 254941.81 11-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2741.82 13024.70 01-JAN-08:50 254941.81 11-OCT-07:10
LightsWired:InteriorLights:Electricity 2741.82 13024.70 01-JAN-08:50 254941.81 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2741.82 13024.70 01-JAN-08:50 254941.81 11-OCT-07:10
Electricity:Zone:CORE_BOTTOM 480.91 6817.20 01-JAN-00:10 32066.15 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:CORE_MID 4809.09 68171.81 01-JAN-00:10 320660.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
Electricity:Zone:CORE_TOP 480.91 6817.18 01-JAN-00:10 32066.08 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 54.12 818.50 01-JAN-08:40 3871.91 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.78 59.73 01-JAN-08:40 1595.59 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.78 59.73 01-JAN-08:40 1595.59 11-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 34.87 527.47 01-JAN-07:50 2496.53 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.87 38.49 01-JAN-07:50 1029.58 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.87 38.49 01-JAN-07:50 1029.58 27-NOV-17:00
Electricity:Zone:PERIMETER_BOT_ZN_1 54.04 818.51 01-JAN-07:50 3865.66 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.70 59.73 01-JAN-07:50 1589.31 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.70 59.73 01-JAN-07:50 1589.31 11-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 34.86 527.47 01-JAN-08:50 2499.72 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.86 38.49 01-JAN-08:50 1032.79 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.86 38.49 01-JAN-08:50 1032.79 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 541.32 8184.99 01-JAN-08:40 38764.25 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 137.90 597.26 01-JAN-08:40 16001.07 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 137.90 597.26 01-JAN-08:40 16001.07 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 348.71 5274.72 01-JAN-07:50 24974.07 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 88.73 384.90 01-JAN-07:50 10304.61 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 88.73 384.90 01-JAN-07:50 10304.61 27-NOV-17:00
Electricity:Zone:PERIMETER_MID_ZN_1 540.49 8185.12 01-JAN-08:00 38704.41 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 137.06 597.27 01-JAN-08:00 15940.89 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 137.06 597.27 01-JAN-08:00 15940.89 11-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 348.64 5274.69 01-JAN-08:50 25004.27 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 88.66 384.90 01-JAN-08:50 10334.90 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 88.66 384.90 01-JAN-08:50 10334.90 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 54.13 818.50 01-JAN-08:40 3876.27 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.79 59.73 01-JAN-08:40 1599.95 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.79 59.73 01-JAN-08:40 1599.95 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 34.87 527.47 01-JAN-07:50 2497.35 27-NOV-17:00
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.87 38.49 01-JAN-07:50 1030.41 27-NOV-17:00
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.87 38.49 01-JAN-07:50 1030.41 27-NOV-17:00
Electricity:Zone:PERIMETER_TOP_ZN_1 54.05 818.51 01-JAN-08:00 3870.29 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.71 59.73 01-JAN-08:00 1593.94 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.71 59.73 01-JAN-08:00 1593.94 11-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 34.86 527.47 01-JAN-08:50 2500.33 11-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.87 38.49 01-JAN-08:50 1033.39 11-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.87 38.49 01-JAN-08:50 1033.39 11-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7544.97 95151.24 01-JAN-00:10 384008.34 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1585.20 19711.13 01-JAN-00:10 81995.25 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 6333.66 8268.15 05-JAN-05:40 548558.64 22-JUN-15:40
HeatRejection:Electricity 1962.04 4579.22 05-JAN-07:00 91812.10 06-MAR-14:30
General:HeatRejection:Electricity 1962.04 4579.22 05-JAN-07:00 91812.10 06-MAR-14:30
Electricity:HVAC 6206.84 81819.38 16-JAN-04:40 423977.76 07-JUL-14:50
ExteriorEquipment:Electricity 1914.38 28294.68 01-JAN-00:10 117201.23 11-OCT-07:20
Transformer:ExteriorEquipment:Electricity 59.77 1112.61 01-JAN-00:10 3723.27 11-OCT-07:20
ElectricityPurchased:Facility 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
ElectricityPurchased:Plant 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
Cogeneration:ElectricityPurchased 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
General:Cogeneration:ElectricityPurchased 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
ElectricityNet:Plant 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
Cogeneration:ElectricityNet 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
General:Cogeneration:ElectricityNet 32797.66 375599.35 01-JAN-10:30 2042710.94 07-AUG-15:10
Fans:Electricity 2647.39 42332.45 05-JAN-23:40 229329.06 07-JUN-14:00
General:Fans:Electricity 2647.39 42332.45 05-JAN-23:40 229329.06 07-JUN-14:00
ExteriorLights:Electricity 447.32 0.00 01-JAN-07:20 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 447.32 0.00 01-JAN-07:20 37611.08 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
Cooling:Electricity 6499.17 33609.71 01-JAN-06:00 571270.01 28-AUG-14:50
General:Cooling:Electricity 6499.17 33609.71 01-JAN-06:00 571270.01 28-AUG-14:50
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 82.64 0.00 12-JAN-13:10 28639.67 22-DEC-06:00
General:Humidifier:Electricity 82.64 0.00 12-JAN-13:10 28639.67 22-DEC-06:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 1289.49 3513.73 01-JAN-00:10 70858.56 29-AUG-05:10
General:Pumps:Electricity 1289.49 3513.73 01-JAN-00:10 70858.56 29-AUG-05:10
WIRED_LTG_ELECTRICITY 77.05 0.00 01-JAN-00:10 7163.86 11-OCT-07:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 577.83 5695.87 16-APR-15:40 244167.48 02-JAN-06:20
NaturalGas:Plant 577.83 5695.87 16-APR-15:40 244167.48 02-JAN-06:20
Heating:NaturalGas 18.27 0.00 01-JAN-00:10 217619.02 02-JAN-06:20
Boiler:Heating:NaturalGas 18.27 0.00 01-JAN-00:10 217619.02 02-JAN-06:20
WaterSystems:NaturalGas 559.56 5695.87 16-APR-15:40 72823.30 10-JAN-12:50
Water Heater:WaterSystems:NaturalGas 559.56 5695.87 16-APR-15:40 72823.30 10-JAN-12:50


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 35429.36 165767.50 01-JAN-06:00 3103772.09 28-AUG-14:40
PlantLoopCoolingDemand:HVAC 35429.36 165767.50 01-JAN-06:00 3103772.09 28-AUG-14:40
CoolingCoils:PlantLoopCoolingDemand 35429.36 165767.50 01-JAN-06:00 3103772.09 28-AUG-14:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 20733.93 0.00 11-MAR-00:10 0.00 19-APR-15:10
Water:HVAC 30.74 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Humidifier:Water 30.74 0.00 12-JAN-13:10 0.00 22-DEC-06:00
General:Humidifier:Water 30.74 0.00 12-JAN-13:10 0.00 22-DEC-06:00
MainsWater:Facility 20733.93 0.00 11-MAR-00:10 0.00 19-APR-15:10
MainsWater:HVAC 30.74 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Humidifier:MainsWater 30.74 0.00 12-JAN-13:10 0.00 22-DEC-06:00
General:Humidifier:MainsWater 30.74 0.00 12-JAN-13:10 0.00 22-DEC-06:00
Water:Plant 20703.19 0.00 01-JAN-00:10 0.00 19-APR-15:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 20703.19 0.00 01-JAN-00:10 0.00 19-APR-15:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 18423.02 0.00 01-JAN-00:10 0.00 19-APR-15:00
General:HeatRejection:Water 18423.02 0.00 01-JAN-00:10 0.00 19-APR-15:00
HeatRejection:MainsWater 18423.02 0.00 01-JAN-00:10 0.00 19-APR-15:00
General:HeatRejection:MainsWater 18423.02 0.00 01-JAN-00:10 0.00 19-APR-15:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 120612.32 229336.65 01-JAN-05:30 12057260.73 28-AUG-14:40
EnergyTransfer:Building 22802.23 96830.74 01-JAN-07:50 1632312.71 27-APR-15:30
EnergyTransfer:Zone:BASEMENT 748.53 0.00 01-JAN-00:40 73749.36 26-DEC-06:10
Heating:EnergyTransfer 18.72 0.00 02-JAN-17:20 98312.78 02-JAN-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.49 0.00 01-JAN-00:10 33282.46 10-JUN-16:10
General:Heating:EnergyTransfer 18.72 0.00 02-JAN-17:20 98312.78 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.49 0.00 01-JAN-00:10 33282.46 10-JUN-16:10
Cooling:EnergyTransfer 22783.51 96603.22 01-JAN-07:50 1632312.71 27-APR-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 744.05 0.00 01-JAN-00:40 73749.36 26-DEC-06:10
General:Cooling:EnergyTransfer 22783.51 96603.22 01-JAN-07:50 1632312.71 27-APR-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 744.05 0.00 01-JAN-00:40 73749.36 26-DEC-06:10
EnergyTransfer:Zone:CORE_BOTTOM 763.72 0.00 01-JAN-00:10 58546.97 07-AUG-07:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 763.72 0.00 01-JAN-00:10 58546.97 07-AUG-07:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 763.72 0.00 01-JAN-00:10 58546.97 07-AUG-07:20
EnergyTransfer:Zone:CORE_MID 5794.37 0.00 01-JAN-00:10 433177.84 05-SEP-09:20
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 5794.37 0.00 01-JAN-00:10 433177.84 05-SEP-09:20
General:Cooling:EnergyTransfer:Zone:CORE_MID 5794.37 0.00 01-JAN-00:10 433177.84 05-SEP-09:20
EnergyTransfer:Zone:CORE_TOP 596.44 0.00 01-JAN-00:10 55989.00 12-JUN-14:00
Heating:EnergyTransfer:Zone:CORE_TOP 0.24 0.00 01-JAN-00:10 38510.49 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.24 0.00 01-JAN-00:10 38510.49 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_TOP 596.19 0.00 01-JAN-00:10 55989.00 12-JUN-14:00
General:Cooling:EnergyTransfer:Zone:CORE_TOP 596.19 0.00 01-JAN-00:10 55989.00 12-JUN-14:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 120.58 0.00 01-JAN-00:10 12797.57 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 120.58 0.00 01-JAN-00:10 12797.57 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 120.58 0.00 01-JAN-00:10 12797.57 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 90.00 0.00 01-JAN-00:10 12364.21 12-JUN-09:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 90.00 0.00 01-JAN-00:10 12364.21 12-JUN-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 90.00 0.00 01-JAN-00:10 12364.21 12-JUN-09:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 154.07 0.00 01-JAN-00:10 16568.23 02-OCT-13:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 154.07 0.00 01-JAN-00:10 16568.23 02-OCT-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 154.07 0.00 01-JAN-00:10 16568.23 02-OCT-13:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 139.69 0.00 01-JAN-00:10 16373.84 27-APR-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 139.69 0.00 01-JAN-00:10 16373.84 27-APR-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 139.69 0.00 01-JAN-00:10 16373.84 27-APR-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 977.68 0.00 01-JAN-00:10 120463.05 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.02 0.00 01-JAN-00:10 7205.96 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 0.02 0.00 01-JAN-00:10 7205.96 02-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 977.67 0.00 01-JAN-00:10 120463.05 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 977.67 0.00 01-JAN-00:10 120463.05 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 818.81 0.00 01-JAN-00:10 122773.51 03-MAY-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.00 0.00 01-JAN-00:10 1147.80 03-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 0.00 0.00 01-JAN-00:10 1147.80 03-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 818.81 0.00 01-JAN-00:10 122773.51 03-MAY-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 818.81 0.00 01-JAN-00:10 122773.51 03-MAY-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1352.36 0.00 01-JAN-00:10 161065.58 02-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1352.36 0.00 01-JAN-00:10 161065.58 02-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1352.36 0.00 01-JAN-00:10 161065.58 02-OCT-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 893.29 0.00 01-JAN-00:10 135111.42 06-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 893.29 0.00 01-JAN-00:10 135111.42 06-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 893.29 0.00 01-JAN-00:10 135111.42 06-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 105.91 0.00 01-JAN-00:10 14153.28 12-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.83 0.00 01-JAN-00:10 11536.76 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 0.83 0.00 01-JAN-00:10 11536.76 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 105.09 0.00 01-JAN-00:10 14153.28 12-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 105.09 0.00 01-JAN-00:10 14153.28 12-JUN-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 88.22 0.00 01-JAN-00:10 13460.91 12-JUN-09:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.30 0.00 01-JAN-00:10 7203.88 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 0.30 0.00 01-JAN-00:10 7203.88 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 87.92 0.00 01-JAN-00:10 13460.91 12-JUN-09:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 87.92 0.00 01-JAN-00:10 13460.91 12-JUN-09:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 140.89 0.00 01-JAN-00:10 18275.35 02-OCT-13:40
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.19 0.00 01-JAN-00:10 8843.13 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.19 0.00 01-JAN-00:10 8843.13 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 140.70 0.00 01-JAN-00:10 18275.35 02-OCT-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 140.70 0.00 01-JAN-00:10 18275.35 02-OCT-13:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 94.91 0.00 01-JAN-00:10 14931.82 06-JUN-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.18 0.00 01-JAN-00:10 5550.30 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.18 0.00 01-JAN-00:10 5550.30 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 94.73 0.00 01-JAN-00:10 14931.82 06-JUN-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 94.73 0.00 01-JAN-00:10 14931.82 06-JUN-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 115.27 0.00 01-JAN-00:10 14968.19 07-AUG-05:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.84 0.00 01-JAN-00:10 3632.26 24-DEC-11:00
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 0.84 0.00 01-JAN-00:10 3632.26 24-DEC-11:00
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 114.43 0.00 01-JAN-00:10 14968.19 07-AUG-05:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 114.43 0.00 01-JAN-00:10 14968.19 07-AUG-05:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 872.87 0.00 01-JAN-00:10 96427.67 05-JUL-12:10
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 5.36 0.00 01-JAN-00:10 20984.97 24-DEC-11:30
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 5.36 0.00 01-JAN-00:10 20984.97 24-DEC-11:30
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 867.51 0.00 01-JAN-00:10 96427.67 05-JUL-12:10
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 867.51 0.00 01-JAN-00:10 96427.67 05-JUL-12:10
EnergyTransfer:Zone:TOPFLOOR_PLENUM 159.71 0.00 01-JAN-00:10 30910.08 12-JUN-13:50
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 6.21 0.00 01-JAN-00:10 14931.28 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 6.21 0.00 01-JAN-00:10 14931.28 02-JAN-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 153.49 0.00 01-JAN-00:10 30910.08 12-JUN-13:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 153.49 0.00 01-JAN-00:10 30910.08 12-JUN-13:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.87 1159.82 07-JAN-08:00 7744.34 17-APR-02:00
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.87 1159.82 07-JAN-08:00 7744.34 17-APR-02:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.87 1159.82 07-JAN-08:00 7744.34 17-APR-02:00
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1326.17 5632.01 01-JAN-07:50 72442.37 12-APR-16:00
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1326.17 5632.01 01-JAN-07:50 72442.37 12-APR-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1326.17 5632.01 01-JAN-07:50 72442.37 12-APR-16:00
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 129.71 0.04 04-JAN-03:40 7449.43 16-APR-21:20
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.07 0.00 02-JAN-11:40 324.86 01-JAN-14:10
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.07 0.00 02-JAN-11:40 324.86 01-JAN-14:10
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 129.64 0.00 01-JAN-00:10 7449.43 16-APR-21:20
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 129.64 0.00 01-JAN-00:10 7449.43 16-APR-21:20
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7176.17 88468.31 14-MAY-02:10 369494.56 15-AUG-24:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7176.17 88468.31 14-MAY-02:10 369494.56 15-AUG-24:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7176.17 88468.31 14-MAY-02:10 369494.56 15-AUG-24:00
PlantLoopHeatingDemand:Facility 305.42 0.00 01-JAN-00:10 181284.13 02-JAN-06:20
PlantLoopHeatingDemand:Plant 293.17 0.00 01-JAN-00:10 40154.54 17-JAN-12:10
WaterSystems:PlantLoopHeatingDemand 293.17 0.00 01-JAN-00:10 40154.54 17-JAN-12:10
General:WaterSystems:PlantLoopHeatingDemand 293.17 0.00 01-JAN-00:10 40154.54 17-JAN-12:10
EnergyTransfer:HVAC 32024.57 132157.79 01-JAN-06:00 2907161.80 28-AUG-14:40
HeatingCoils:EnergyTransfer 12.25 0.00 01-JAN-00:10 176369.99 02-JAN-06:20
PlantLoopHeatingDemand:HVAC 12.25 0.00 01-JAN-00:10 176369.99 02-JAN-06:20
HeatingCoils:PlantLoopHeatingDemand 12.25 0.00 01-JAN-00:10 176369.99 02-JAN-06:20
CoolingCoils:EnergyTransfer 32012.32 132157.79 01-JAN-06:00 2907161.80 28-AUG-14:40
EnergyTransfer:Plant 65785.52 0.00 01-JAN-00:10 7857828.05 22-JUN-15:40
LoopToLoop:EnergyTransfer 22277.76 0.00 01-JAN-00:10 2476003.81 22-JUN-15:30
WaterSystems:EnergyTransfer 293.17 0.00 01-JAN-00:10 40154.54 17-JAN-12:10
WaterUse:WaterSystems:EnergyTransfer 293.17 0.00 01-JAN-00:10 40154.54 17-JAN-12:10
Boilers:EnergyTransfer 11.98 0.00 01-JAN-00:10 165341.44 02-JAN-06:20
Chillers:EnergyTransfer 20060.24 0.00 01-JAN-00:10 2487285.50 22-JUN-15:40
HeatRejection:EnergyTransfer 23142.37 0.00 01-JAN-00:10 2875638.92 22-JUN-15:40
General:HeatRejection:EnergyTransfer 23142.37 0.00 01-JAN-00:10 2875638.92 22-JUN-15:40
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.486 -744.041 0.000 0.000 92.664 177.742 424.397 0.000 0.000 0.000 44.753 0.000 0.000 0.000 0.000 -0.001
CORE_BOTTOM 0.000 0.000 0.000 -763.720 0.000 0.000 83.423 159.625 321.286 0.000 0.000 0.000 199.387 0.000 0.000 0.000 0.000 -0.002
CORE_MID 0.000 0.000 0.000 -5794.361 0.000 0.000 835.553 1596.246 3212.845 0.000 0.000 0.000 149.717 0.000 0.000 0.000 0.000 -0.030
CORE_TOP 0.000 0.000 0.244 -596.192 0.000 0.000 84.309 159.625 321.285 0.000 0.000 0.000 30.731 0.000 0.000 0.000 0.000 -0.001
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -120.582 0.000 0.000 10.500 13.776 40.342 42.201 0.000 0.626 34.779 0.000 -21.277 0.000 -0.365 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -90.000 0.000 0.000 6.762 8.870 25.998 50.214 0.000 0.422 10.918 0.000 -12.942 0.000 -0.242 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -154.066 0.000 0.000 10.473 13.696 40.343 90.148 0.000 0.614 19.795 0.000 -20.611 0.000 -0.393 -0.002
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -139.687 0.000 0.000 6.740 8.863 25.998 48.850 0.000 0.391 65.419 0.000 -16.286 0.000 -0.289 0.000
PERIMETER_MID_ZN_3 0.000 0.000 0.015 -977.656 0.000 0.000 106.160 137.901 403.423 432.376 0.000 14.280 87.534 0.000 -196.338 0.000 -7.695 0.000
PERIMETER_MID_ZN_2 0.000 0.000 0.001 -818.803 0.000 0.000 49.929 88.733 259.981 501.648 0.000 9.329 40.798 0.000 -126.123 0.000 -5.492 -0.013
PERIMETER_MID_ZN_1 0.000 0.000 0.000 -1352.350 0.000 0.000 104.873 137.061 403.429 902.696 0.000 13.897 3.918 0.000 -204.315 0.000 -9.209 -0.001
PERIMETER_MID_ZN_4 0.000 0.000 0.000 -893.280 0.000 0.000 68.136 88.661 259.979 503.628 0.000 9.151 109.870 0.000 -140.414 0.000 -5.730 -0.003
PERIMETER_TOP_ZN_3 0.000 0.000 0.826 -105.087 0.000 0.000 10.783 13.790 40.342 43.061 0.000 1.733 13.405 0.000 -18.011 0.000 -0.842 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 0.300 -87.915 0.000 0.000 6.863 8.873 25.998 50.058 0.000 1.129 7.110 0.000 -11.799 0.000 -0.618 -0.001
PERIMETER_TOP_ZN_1 0.000 0.000 0.189 -140.695 0.000 0.000 10.560 13.706 40.343 89.920 0.000 1.682 4.662 0.000 -19.302 0.000 -1.064 -0.000
PERIMETER_TOP_ZN_4 0.000 0.000 0.177 -94.732 0.000 0.000 6.898 8.866 25.998 50.178 0.000 1.119 15.324 0.000 -13.174 0.000 -0.654 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -142.865 0.000 0.000 0.936 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -16.591
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1326.176 0.000 0.000 9.380 46.396 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -268.406
DATACENTER_TOP_ZN_6 0.000 0.000 0.067 -129.645 0.000 0.000 0.942 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -29.884
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7176.183 0.000 0.000 19.434 50.116 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -388.223
GROUNDFLOOR_PLENUM 0.843 -114.428 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.176 113.216 0.000 0.000 0.000 -0.808 -0.000
MIDFLOOR_PLENUM 5.361 -867.503 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 21.362 854.615 0.000 0.000 0.000 -13.834 -0.000
TOPFLOOR_PLENUM 6.212 -153.491 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 2.197 146.456 0.000 0.000 0.000 -1.375 -0.001
Total Facility 12.416 -1135.422 6.305 -21648.036 0.000 0.000 1525.316 2741.824 15213.411 2804.978 0.000 79.107 1952.407 0.000 -800.592 0.000 -48.611 -703.160


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 06-FEB-04:03 0.00 0.00 0.00 -100510.50 0.00 0.00 0.00 862.23 13457.54 0.00 0.00 0.00 86190.73 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 02-JAN-04:02 0.00 0.00 0.00 -94134.29 0.00 0.00 0.00 774.34 8057.15 0.00 0.00 0.00 85302.80 0.00 -0.00 0.00 0.00 0.00
CORE_MID 27-FEB-04:02 0.00 0.00 0.00 -845701.94 0.00 0.00 0.00 7743.41 80571.20 0.00 0.00 0.00 757387.34 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 12-JUN-05:02 0.00 0.00 0.00 -86985.00 0.00 0.00 808.43 1548.68 8057.12 0.00 0.00 0.00 76570.77 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 02-JUL-17:01 0.00 0.00 0.00 -20860.56 0.00 0.00 0.00 59.73 758.77 5112.85 0.00 163.31 14765.90 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 07-MAY-09:11 0.00 0.00 0.00 -16989.09 0.00 0.00 22.40 38.49 488.98 11040.75 0.00 97.54 5300.93 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 01-OCT-13:11 0.00 0.00 0.00 -22454.51 0.00 0.00 34.11 59.73 758.78 14693.55 0.00 67.11 6841.22 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 02-JUL-16:21 0.00 0.00 0.00 -24089.81 0.00 0.00 17.84 38.49 488.98 10400.03 0.00 96.50 13047.98 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 28-MAY-16:41 0.00 0.00 0.00 -194137.11 0.00 0.00 388.21 597.26 7587.73 51511.90 0.00 11688.26 122363.75 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 28-MAY-09:21 0.00 0.00 0.00 -179963.44 0.00 0.00 213.14 384.90 4889.82 111412.28 0.00 1957.19 61106.11 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 01-OCT-13:11 0.00 0.00 0.00 -220219.11 0.00 0.00 330.54 597.27 7587.84 146026.92 0.00 1489.61 64186.92 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 28-MAY-16:01 0.00 0.00 0.00 -189865.75 0.00 0.00 177.88 384.90 4889.79 124372.39 0.00 7654.55 52386.25 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 28-MAY-16:11 0.00 0.00 0.00 -23072.64 0.00 0.00 35.40 59.73 758.77 5028.54 0.00 1514.13 15676.07 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 07-MAY-09:51 0.00 0.00 0.00 -19383.99 0.00 0.00 20.26 38.49 488.98 9600.21 0.00 278.65 8957.40 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 22-OCT-13:52 0.00 0.00 0.00 -25032.96 0.00 0.00 34.33 59.73 758.78 12764.41 0.00 59.32 11356.39 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 28-MAY-16:11 0.00 0.00 0.00 -21507.90 0.00 0.00 15.54 38.49 488.98 12141.13 0.00 925.03 7898.72 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 17-APR-01:55 0.00 0.00 0.00 -7748.03 0.00 0.00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -68.90
DATACENTER_MID_ZN_6 12-APR-16:00 0.00 0.00 0.00 -72437.66 0.00 0.00 985.53 4051.03 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10543.13
DATACENTER_TOP_ZN_6 16-APR-21:32 0.00 0.00 0.00 -7463.58 0.00 0.00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -353.35
DATACENTER_BASEMENT_ZN_6 15-AUG-23:53 0.00 0.00 0.00 -369673.07 0.00 0.00 0.00 243.11 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10202.57
GROUNDFLOOR_PLENUM 05-JUL-05:15 0.00 -18069.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.49 18013.96 0.00 -0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 05-SEP-05:15 0.00 -115675.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 42.81 115632.95 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 12-JUN-13:50 0.00 -30910.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 367.34 30543.33 0.00 -0.00 0.00 0.00 0.00
Total Facility 17-APR-05:02 0.00 -77674.29 0.00 -2073908.18 0.00 0.00 15633.57 29009.37 623236.89 0.00 0.00 0.00 1516786.30 0.00 -33078.85 0.00 -4.82 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 10-JUN-16:01 0.00 0.00 35206.82 0.00 0.00 0.00 520.12 862.23 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -50046.71
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 02-JAN-05:01 0.00 0.00 61366.80 0.00 0.00 0.00 0.00 1548.68 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -70972.61
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 02-JAN-06:01 0.00 0.00 37218.17 0.00 0.00 0.00 1405.93 1944.52 10116.97 0.00 0.00 0.00 0.00 0.00 -31742.49 0.00 0.00 -18943.11
PERIMETER_MID_ZN_2 03-JAN-06:05 0.00 0.00 4590.90 0.00 0.00 0.00 889.30 1253.13 6519.76 0.00 0.00 0.00 9916.65 0.00 -23056.35 0.00 -113.39 0.00
PERIMETER_MID_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 02-JAN-04:02 0.00 0.00 16865.17 0.00 0.00 0.00 0.00 97.23 1011.70 0.00 0.00 0.00 0.00 0.00 -2262.07 0.00 0.00 -15712.03
PERIMETER_TOP_ZN_2 02-JAN-04:02 0.00 0.00 11587.32 0.00 0.00 0.00 0.00 62.66 651.98 0.00 0.00 0.00 0.00 0.00 -1547.40 0.00 0.00 -10754.56
PERIMETER_TOP_ZN_1 02-JAN-05:01 0.00 0.00 16202.83 0.00 0.00 0.00 0.00 194.46 1011.71 0.00 0.00 0.00 0.00 0.00 -2545.23 0.00 0.00 -14863.77
PERIMETER_TOP_ZN_4 02-JAN-05:01 0.00 0.00 11193.67 0.00 0.00 0.00 0.00 125.31 651.97 0.00 0.00 0.00 0.00 0.00 -1705.48 0.00 0.00 -10265.48
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 01-JAN-14:00 0.00 0.00 331.77 0.00 0.00 0.00 6.24 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2309.12
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 11-DEC-04:02 11259.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -11259.34
MIDFLOOR_PLENUM 11-SEP-03:02 91186.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -91186.58
TOPFLOOR_PLENUM 02-JAN-06:13 19540.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -19540.64
Total Facility 02-JAN-06:01 -1003619.82 1087924.83 145399.07 -1087924.83 0.00 0.00 17732.50 29009.37 268362.69 0.00 0.00 0.00 672716.04 0.00 -129599.85 0.00 0.00 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.4423 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.8089 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 98.9705 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 92.7873 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.7171 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 10.5896 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.5681 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.5681 0.2155 1.0000 Not calculated 1.2002 0.2155    
AIRLOOP DATACENTER BASEMENT 21.9002 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.9005 0.0155 1.0000 Not calculated 0.3384 0.0155    
AIRLOOP DATACENTER BOT 0.4830 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4830 0.0324 1.0000 Not calculated 0.0156 0.0324    
AIRLOOP DATACENTER MID 4.6006 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6006 0.0340 1.0000 Not calculated 0.1563 0.0340    
AIRLOOP DATACENTER TOP 0.4633 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4633 0.0337 1.0000 Not calculated 0.0156 0.0337    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.2212 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.8519 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 49.4853 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 27.8415 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.3585 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.9516 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.5681 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.5681 1.0000 1.0000 Not calculated 1.2002 0.2155    
AIRLOOP DATACENTER BASEMENT 21.9002 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.9002 1.0000 1.0000 Not calculated 0.3384 0.0155    
AIRLOOP DATACENTER BOT 0.4830 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4830 1.0000 1.0000 Not calculated 0.0156 0.0324    
AIRLOOP DATACENTER MID 4.6006 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.6006 1.0000 1.0000 Not calculated 0.1563 0.0340    
AIRLOOP DATACENTER TOP 0.4633 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4633 1.0000 1.0000 Not calculated 0.0156 0.0337    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.5681 5.5681 5.5681 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.9465 5.9465 1.9385 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 56.3298 56.3298 19.0958 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.8562 5.8562 1.9794 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1743 1.1743 0.2443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9202 0.9202 0.1840 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1954 1.1954 0.2439 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2060 1.2060 0.2412 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.4022 11.4022 2.3945 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.5283 9.5283 1.9057 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.5045 11.5045 2.4045 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.2056 10.2056 2.0411 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3417 1.3417 0.2683 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0210 1.0210 0.2042 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3443 1.3443 0.2689 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1538 1.1538 0.2308 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4830 0.4830 0.4830 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6006 4.6006 4.6006 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4633 0.4633 0.4633 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.9002 21.9002 21.9002 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.4423 9.8089 10.4423 2.8519 0.0000 1.0000
VAV_MID WITH REHEAT 98.9705 92.7873 98.9705 27.8415 0.0000 1.0000
VAV_TOP WITH REHEAT 10.7171 10.5896 10.7171 2.9516 0.0000 1.0000
CAV_BAS 5.5681 5.5681 5.5681 5.5681 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.9002 21.9005 21.9002 21.9002 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4830 0.4830 0.4830 0.4830 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6006 4.6006 4.6006 4.6006 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4633 0.4633 0.4633 0.4633 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.5681 5.5681 5.5681 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9732 2.9732 1.9385 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 28.1649 28.1649 19.0958 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.9281 2.9281 1.9794 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5871 0.5871 0.2443 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4601 0.4601 0.1840 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5977 0.5977 0.2439 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6030 0.6030 0.2412 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7011 5.7011 2.3945 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.7642 4.7642 1.9057 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7523 5.7523 2.4045 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1028 5.1028 2.0411 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6708 0.6708 0.2683 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5105 0.5105 0.2042 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6722 0.6722 0.2689 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5769 0.5769 0.2308 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4830 0.4830 0.4830 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.6006 4.6006 4.6006 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4633 0.4633 0.4633 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.9002 21.9002 21.9002 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.2212 2.8519 2.8519 2.8519 0.0000 1.0000
VAV_MID WITH REHEAT 49.4853 27.8415 27.8415 27.8415 0.0000 1.0000
VAV_TOP WITH REHEAT 5.3585 2.9516 2.9516 2.9516 0.0000 1.0000
CAV_BAS 5.5681 5.5681 5.5681 5.5681 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.9002 21.9002 21.9002 21.9002 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4830 0.4830 0.4830 0.4830 0.0156 1.0000
AIRLOOP DATACENTER MID 4.6006 4.6006 4.6006 4.6006 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4633 0.4633 0.4633 0.4633 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New Delhi-Safdarjung AP Delhi IND IWEC2 WMO#=421820
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 1100.00
Number of hours not met 1100.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 18.27 217619.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 6499.17 571270.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2741.82 254941.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 447.32 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 59.77 3723.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2647.39 229329.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1289.49 70858.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1962.04 91812.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 82.64 28639.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 559.56 72823.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 32797.66
Natural Gas 0.00 577.83
Additional 0.00 0.00
Total 15213.41 33375.49


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 59.19
Space Heating 0.00
Space Cooling 140.31
Fans (All) 57.15
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 708.06
Subtotal 708.06


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 0.39
Service Water Heating 12.08
Miscellaneous (All) 12.47
Subtotal 12.47


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.22
Space Heating 0.05
Space Cooling 19.47
Fans (All) 7.93
Service Water Heating 1.68
Receptacle Equipment 45.58
Miscellaneous 17.07


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2393. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7493.50 1266.50 0.00 0.00 0.00
CORE_BOTTOM 8676.00 84.00 0.00 0.00 0.00
CORE_MID 8756.83 3.17 0.00 0.00 0.00
CORE_TOP 8751.00 9.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8605.00 155.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8586.83 173.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8466.50 293.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7576.67 1183.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8472.50 287.50 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8319.67 440.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8134.67 625.33 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7893.33 866.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8379.33 380.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8251.67 508.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8095.83 664.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7948.00 812.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6102.67 2657.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6085.50 2674.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6708.67 2051.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7279.67 1480.33 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8731.83 28.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8272.33 487.67 0.00 0.00 0.00
Min 6085.50 0.00 0.00 0.00 0.00
Max 8760.00 2674.50 0.00 0.00 0.00
Average 8015.13 744.87 0.00 0.00 0.00
Sum 184348.00 17132.00 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 365235.00 3381.00 0.00 0.00 0.00
CORE_BOTTOM 330646.00 167.00 0.00 0.00 0.00
CORE_MID 330794.00 19.00 0.00 0.00 0.00
CORE_TOP 330788.00 25.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1347.67 920.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1332.00 936.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1488.00 780.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 81926.33 21468.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 365235.00 21468.67 0.00 0.00 0.00
Average 79130.70 1204.22 0.00 0.00 0.00
Sum 1820006.00 27697.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 5403.33 3356.67 0.00 0.00 0.00
CORE_BOTTOM 7456.17 1303.83 0.00 0.00 0.00
CORE_MID 7539.17 1220.83 0.00 0.00 0.00
CORE_TOP 7516.17 1243.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 6849.17 1910.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 7028.00 1732.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 6596.17 2163.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 6271.00 2489.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 6842.67 1917.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 6734.50 2025.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 6549.33 2210.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 6618.67 2141.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 6867.17 1892.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 6751.00 2009.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 6584.83 2175.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 6668.00 2092.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7056.83 1703.17 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7059.50 1700.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7476.67 1283.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7542.50 1217.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 6172.50 2587.50 0.00 0.00 0.00
MIDFLOOR_PLENUM 5738.00 3022.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 4744.17 4015.83 0.00 0.00 0.00
Min 4744.17 1217.50 0.00 0.00 0.00
Max 7542.50 4015.83 0.00 0.00 0.00
Average 6698.50 2061.50 0.00 0.00 0.00
Sum 154065.50 47414.50 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 333368.00 35248.00 0.00 0.00 0.00
CORE_BOTTOM 328306.83 2506.17 0.00 0.00 0.00
CORE_MID 328578.17 2234.83 0.00 0.00 0.00
CORE_TOP 328356.17 2456.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38921.67 3.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18352.33 1.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38921.83 3.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24907.83 1.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38920.83 4.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24906.83 2.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38920.83 4.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24907.67 1.33 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1640.00 628.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1627.83 640.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1771.00 497.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 87353.83 16041.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 333368.00 35248.00 0.00 0.00 0.00
Average 77714.33 2620.58 0.00 0.00 0.00
Sum 1787429.67 60273.33 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 1B

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY IND_DELHI_NEWDELHI

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.392
February 16.974
March 22.368
April 29.134
May 32.978
June 33.595
July 31.671
August 30.033
September 28.750
October 25.087
November 19.629
December 14.516
   
Annual Sum or Average 24.876
Minimum of Months 13.392
Maximum of Months 33.595



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.576987E+11 97223.56 02-JAN-04:02 6.67 6.44 0.566885E+10 7499.04 04-JAN-10:20 13.03 10.49
February 0.510626E+11 100508.93 06-FEB-04:03 10.55 9.45 0.514165E+10 7499.07 02-FEB-10:09 10.55 9.45
March 0.585353E+11 95460.67 06-MAR-04:02 15.67 14.63 0.613458E+10 7499.00 16-MAR-09:00 19.90 15.14
April 0.553139E+11 95547.30 28-APR-03:02 28.85 17.10 0.545167E+10 7499.02 04-APR-09:09 28.85 17.10
May 0.585835E+11 94628.54 29-MAY-17:30 40.55 21.29 0.590305E+10 7498.86 04-MAY-13:20 40.55 21.29
June 0.614247E+11 91765.23 05-JUN-03:02 30.82 20.05 0.588419E+10 7498.87 07-JUN-09:09 37.65 20.59
July 0.657858E+11 85621.88 04-JUL-19:50 40.00 24.33 0.547682E+10 7498.76 28-JUL-09:20 28.17 25.73
August 0.754103E+11 83004.63 22-AUG-03:02 25.88 25.10 0.614011E+10 7498.72 24-AUG-09:20 29.43 26.79
September 0.651251E+11 84697.23 26-SEP-03:02 25.65 21.91 0.545546E+10 7498.75 15-SEP-13:20 25.65 21.91
October 0.674804E+11 94666.66 29-OCT-13:32 29.23 17.90 0.567432E+10 7498.91 17-OCT-09:30 29.23 17.90
November 0.649829E+11 99215.18 12-NOV-13:52 28.20 15.95 0.561814E+10 7498.95 09-NOV-10:09 28.20 15.95
December 0.626420E+11 96467.72 26-DEC-04:03 10.20 8.99 0.547479E+10 7498.95 13-DEC-10:09 10.20 8.99
                     
Annual Sum or Average 0.744045E+12         0.680236E+11        
Minimum of Months 0.510626E+11 83004.63   6.67 6.44 0.514165E+10 7498.72   10.20 8.99
Maximum of Months 0.754103E+11 100508.93   40.55 25.10 0.614011E+10 7499.07   40.55 26.79



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.454920E+11 94247.69 02-JAN-04:02 6.67 6.44 0.508059E+10 6734.74 04-JAN-10:00 15.50 12.02
February 0.474129E+11 93630.41 21-FEB-04:02 12.42 11.05 0.460628E+10 6734.76 02-FEB-10:09 12.42 11.05
March 0.650079E+11 89662.57 21-MAR-03:02 14.88 11.76 0.549823E+10 6734.75 27-MAR-09:09 23.33 16.01
April 0.720154E+11 86826.26 17-APR-05:05 24.22 18.83 0.487623E+10 6734.74 04-APR-09:09 24.22 18.83
May 0.676663E+11 85761.14 01-MAY-05:02 32.45 19.07 0.528054E+10 6734.55 08-MAY-13:09 38.60 20.90
June 0.691610E+11 85216.57 12-JUN-05:02 34.12 19.12 0.526504E+10 6734.56 12-JUN-13:09 43.40 22.40
July 0.727014E+11 85751.65 10-JUL-05:05 30.80 25.35 0.489285E+10 6734.53 17-JUL-13:00 33.90 27.72
August 0.813583E+11 84674.83 07-AUG-05:01 29.53 24.79 0.549482E+10 6734.54 07-AUG-09:09 32.20 25.23
September 0.616902E+11 82935.09 11-SEP-03:02 26.07 25.28 0.488007E+10 6734.54 05-SEP-09:09 26.07 25.28
October 0.649114E+11 90591.37 31-OCT-03:02 16.50 14.83 0.507705E+10 6734.66 24-OCT-09:09 16.50 14.83
November 0.601806E+11 93854.23 24-NOV-04:02 11.00 9.68 0.503088E+10 6734.70 16-NOV-10:09 11.00 9.68
December 0.561220E+11 93980.08 04-DEC-04:02 8.72 8.07 0.490322E+10 6734.72 18-DEC-10:00 21.70 14.67
                     
Annual Sum or Average 0.763719E+12         0.608858E+11        
Minimum of Months 0.454920E+11 82935.09   6.67 6.44 0.460628E+10 6734.53   11.00 9.68
Maximum of Months 0.813583E+11 94247.69   34.12 25.35 0.549823E+10 6734.76   43.40 27.72



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.348087E+11 80680.75 17-JAN-06:02 10.70 10.27 0.504312E+10 6734.71 04-JAN-10:00 10.70 10.27
February 0.362009E+11 84600.87 27-FEB-04:02 11.72 10.91 0.458687E+10 6734.74 02-FEB-10:09 11.72 10.91
March 0.491260E+11 81591.21 23-MAR-04:03 16.62 14.35 0.549288E+10 6734.75 27-MAR-09:09 23.33 16.01
April 0.521247E+11 79594.66 13-APR-03:02 24.18 17.44 0.487335E+10 6734.74 04-APR-09:09 24.18 17.44
May 0.581295E+11 75644.68 25-MAY-03:02 26.60 23.78 0.527550E+10 6734.60 01-MAY-09:20 26.60 23.78
June 0.562357E+11 77374.93 21-JUN-03:02 28.25 23.92 0.526173E+10 6734.64 05-JUN-13:09 28.25 23.92
July 0.549864E+11 77726.46 28-JUL-03:02 27.00 25.79 0.488690E+10 6734.56 18-JUL-13:09 27.00 25.79
August 0.562502E+11 78401.83 17-AUG-03:02 27.35 25.43 0.549215E+10 6734.56 21-AUG-13:09 29.57 27.56
September 0.501359E+11 80308.33 06-SEP-03:02 25.57 24.55 0.487896E+10 6734.56 11-SEP-13:09 31.10 27.02
October 0.504335E+11 82936.58 24-OCT-03:02 18.57 14.45 0.507321E+10 6734.65 24-OCT-09:09 23.63 15.90
November 0.439093E+11 81772.99 17-NOV-05:03 13.97 13.14 0.501878E+10 6734.70 06-NOV-10:09 13.97 13.14
December 0.370963E+11 80223.21 27-DEC-06:02 10.88 9.54 0.486971E+10 6734.67 18-DEC-10:00 10.88 9.54
                     
Annual Sum or Average 0.579437E+12         0.607532E+11        
Minimum of Months 0.348087E+11 75644.68   10.70 9.54 0.458687E+10 6734.56   10.70 9.54
Maximum of Months 0.581295E+11 84600.87   28.25 25.79 0.549288E+10 6734.75   31.10 27.56



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.252649E+11 34277.53 26-JAN-16:20 19.67 13.02 0.467447E+10 6734.53 13-JAN-14:09 19.67 13.02
February 0.300087E+11 79357.48 23-FEB-06:03 15.05 13.57 0.447724E+10 6734.62 15-FEB-10:09 15.05 13.57
March 0.478751E+11 83715.24 15-MAR-04:03 18.62 15.11 0.547284E+10 6734.74 27-MAR-09:09 23.33 16.01
April 0.582517E+11 83283.83 17-APR-05:03 24.22 18.83 0.487457E+10 6734.73 04-APR-09:09 24.22 18.83
May 0.686688E+11 82830.27 25-MAY-03:02 26.60 23.78 0.528191E+10 6734.56 08-MAY-13:09 26.60 23.78
June 0.672001E+11 86993.69 12-JUN-05:02 34.12 19.12 0.526712E+10 6734.62 12-JUN-13:09 43.40 22.40
July 0.640474E+11 83995.34 28-JUL-03:02 27.00 25.79 0.489393E+10 6734.52 17-JUL-13:00 27.00 25.79
August 0.637269E+11 84138.26 17-AUG-03:02 27.35 25.43 0.549580E+10 6734.53 21-AUG-13:00 28.90 27.65
September 0.549793E+11 85558.99 11-SEP-03:02 26.07 25.28 0.488032E+10 6734.54 08-SEP-13:00 26.07 25.28
October 0.505445E+11 84715.45 11-OCT-03:02 24.45 20.86 0.506305E+10 6734.64 17-OCT-09:20 26.63 18.34
November 0.380705E+11 81204.55 09-NOV-06:02 17.53 15.94 0.496320E+10 6734.66 06-NOV-10:09 17.53 15.94
December 0.275569E+11 69665.87 29-DEC-06:02 16.53 12.55 0.465534E+10 6734.59 29-DEC-10:09 18.00 13.36
                     
Annual Sum or Average 0.596195E+12         0.599998E+11        
Minimum of Months 0.252649E+11 34277.53   15.05 12.55 0.447724E+10 6734.52   15.05 13.02
Maximum of Months 0.686688E+11 86993.69   34.12 25.79 0.549580E+10 6734.74   43.40 27.65



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.392791E+10 4968.19 26-JAN-14:10 22.35 13.84 0.619610E+09 845.62 17-JAN-10:00 22.35 13.84
February 0.491946E+10 6682.53 23-FEB-14:30 26.10 14.00 0.571659E+09 845.62 02-FEB-10:00 26.10 14.00
March 0.881413E+10 13821.38 14-MAR-05:02 20.70 16.42 0.689502E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.124979E+11 19444.80 16-APR-15:41 39.37 22.61 0.613636E+09 845.63 04-APR-09:09 39.37 22.61
May 0.140021E+11 19446.64 07-MAY-16:31 41.77 21.63 0.665359E+09 845.61 08-MAY-13:09 38.60 20.90
June 0.146556E+11 19512.69 11-JUN-17:02 42.88 23.08 0.662950E+09 845.61 07-JUN-13:09 42.88 23.08
July 0.144747E+11 20867.56 02-JUL-17:01 40.18 26.57 0.616784E+09 845.60 10-JUL-09:09 32.98 26.50
August 0.150573E+11 18961.79 06-AUG-15:42 36.30 26.24 0.691492E+09 845.61 07-AUG-09:09 32.20 25.23
September 0.107885E+11 19212.21 24-SEP-14:42 35.10 24.80 0.613973E+09 845.61 08-SEP-13:30 35.10 24.80
October 0.953957E+10 17364.69 01-OCT-15:51 35.50 20.15 0.637691E+09 845.62 10-OCT-13:00 31.70 20.64
November 0.680923E+10 8997.97 06-NOV-06:02 14.70 13.68 0.629307E+09 845.63 06-NOV-14:50 28.48 18.19
December 0.509637E+10 5933.59 26-DEC-14:10 22.68 14.39 0.607185E+09 845.62 18-DEC-10:00 22.68 14.39
                     
Annual Sum or Average 0.120583E+12         0.761915E+10        
Minimum of Months 0.392791E+10 4968.19   14.70 13.68 0.571659E+09 845.60   22.35 13.84
Maximum of Months 0.150573E+11 20867.56   42.88 26.57 0.691492E+09 845.63   42.88 26.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.328112E+10 4453.37 26-JAN-10:20 18.10 12.94 0.404086E+09 544.95 04-JAN-10:00 18.10 12.94
February 0.408230E+10 7146.13 21-FEB-09:40 18.10 12.98 0.369167E+09 544.95 02-FEB-10:09 18.10 12.98
March 0.709092E+10 13235.84 12-MAR-09:53 25.90 17.17 0.444348E+09 544.96 27-MAR-09:20 23.77 16.23
April 0.981976E+10 16685.30 16-APR-09:02 33.08 21.25 0.395522E+09 545.35 28-APR-09:50 33.47 18.33
May 0.113152E+11 16990.34 07-MAY-09:11 34.60 20.48 0.429003E+09 545.24 26-MAY-09:00 35.60 21.80
June 0.106140E+11 15610.86 11-JUN-09:42 36.22 25.04 0.427165E+09 545.32 12-JUN-09:39 39.50 22.03
July 0.975500E+10 16213.54 02-JUL-15:41 40.33 26.36 0.397258E+09 545.08 07-JUL-09:00 36.90 24.55
August 0.950138E+10 12964.53 07-AUG-05:01 29.53 24.79 0.445222E+09 545.02 07-AUG-09:00 33.20 25.77
September 0.797521E+10 15173.92 24-SEP-14:42 35.10 24.80 0.395627E+09 544.94 08-SEP-13:30 35.10 24.80
October 0.746545E+10 15922.26 01-OCT-09:52 29.70 19.34 0.411170E+09 545.26 02-OCT-09:20 30.57 20.21
November 0.531285E+10 6736.27 13-NOV-09:40 21.37 14.10 0.405448E+09 544.96 06-NOV-14:50 21.37 14.10
December 0.378736E+10 4963.54 01-DEC-09:40 17.67 11.19 0.390993E+09 544.95 18-DEC-10:00 21.70 14.67
                     
Annual Sum or Average 0.900005E+11         0.491501E+10        
Minimum of Months 0.328112E+10 4453.37   17.67 11.19 0.369167E+09 544.94   18.10 12.94
Maximum of Months 0.113152E+11 16990.34   40.33 26.36 0.445222E+09 545.35   39.50 25.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.753033E+10 14671.94 08-JAN-14:23 22.60 13.48 0.629081E+09 845.88 12-JAN-14:20 23.40 14.05
February 0.854754E+10 20491.31 19-FEB-14:13 25.47 14.26 0.575339E+09 846.09 07-FEB-14:50 25.47 14.26
March 0.129485E+11 21190.03 12-MAR-13:12 30.87 19.14 0.690972E+09 846.05 08-MAR-14:00 30.87 19.14
April 0.150210E+11 20457.00 16-APR-15:01 39.63 22.37 0.614291E+09 845.96 12-APR-13:00 39.63 22.37
May 0.146427E+11 19971.29 07-MAY-15:11 42.37 21.49 0.665528E+09 846.01 30-MAY-13:20 39.27 24.02
June 0.146094E+11 19798.19 11-JUN-16:22 43.25 23.12 0.662976E+09 845.93 12-JUN-13:20 43.50 22.39
July 0.145409E+11 21177.55 02-JUL-16:21 40.35 26.46 0.616812E+09 845.89 05-JUL-13:20 37.90 25.56
August 0.156042E+11 20003.67 06-AUG-14:22 36.10 26.31 0.691632E+09 846.24 09-AUG-13:20 34.53 26.23
September 0.129914E+11 21061.96 24-SEP-14:42 35.10 24.80 0.614469E+09 846.00 19-SEP-13:00 35.10 24.80
October 0.150391E+11 22454.27 01-OCT-13:11 35.43 19.93 0.639986E+09 874.22 02-OCT-13:30 36.30 21.12
November 0.131785E+11 21450.98 23-NOV-12:52 25.80 14.32 0.632641E+09 851.20 27-NOV-14:09 26.35 13.94
December 0.941301E+10 20837.28 03-DEC-12:43 23.78 14.19 0.612585E+09 846.18 04-DEC-14:00 23.20 14.27
                     
Annual Sum or Average 0.154067E+12         0.764631E+10        
Minimum of Months 0.753033E+10 14671.94   22.60 13.48 0.575339E+09 845.88   23.20 13.94
Maximum of Months 0.156042E+11 22454.27   43.25 26.46 0.691632E+09 874.22   43.50 26.23



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.473417E+10 8480.49 14-JAN-06:02 14.50 12.49 0.405205E+09 544.95 17-JAN-10:00 14.40 13.62
February 0.627337E+10 17406.44 19-FEB-16:12 25.17 13.60 0.372553E+09 544.95 02-FEB-10:09 25.17 13.60
March 0.115387E+11 21070.60 26-MAR-14:42 30.37 16.76 0.446184E+09 544.97 30-MAR-13:50 32.05 19.26
April 0.168288E+11 22159.83 30-APR-16:21 37.45 18.00 0.396833E+09 544.96 04-APR-09:09 37.45 18.00
May 0.139290E+11 21518.67 07-MAY-15:51 42.30 21.45 0.429333E+09 544.94 05-MAY-09:00 42.30 21.45
June 0.149745E+11 21554.30 04-JUN-15:51 42.30 22.20 0.427837E+09 544.95 07-JUN-13:09 43.15 21.81
July 0.149320E+11 24103.34 02-JUL-16:21 40.35 26.46 0.398216E+09 544.94 10-JUL-09:09 32.98 26.50
August 0.178526E+11 21609.99 06-AUG-15:42 36.30 26.24 0.446629E+09 544.95 07-AUG-09:09 32.20 25.23
September 0.106089E+11 21299.59 24-SEP-14:42 35.10 24.80 0.396230E+09 544.94 08-SEP-13:30 35.10 24.80
October 0.109045E+11 22307.67 01-OCT-15:11 35.83 20.00 0.412306E+09 544.95 10-OCT-13:00 31.70 20.64
November 0.922537E+10 20184.25 23-NOV-14:12 25.47 14.21 0.408170E+09 544.97 06-NOV-14:50 25.47 14.21
December 0.788505E+10 18231.40 24-DEC-15:32 23.13 13.76 0.397499E+09 544.95 18-DEC-10:00 23.13 13.76
                     
Annual Sum or Average 0.139687E+12         0.493699E+10        
Minimum of Months 0.473417E+10 8480.49   14.50 12.49 0.372553E+09 544.94   14.40 13.60
Maximum of Months 0.178526E+11 24103.34   42.30 26.46 0.446629E+09 544.97   43.15 26.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.282036E+10 3666.53 26-JAN-14:30 22.05 13.77 0.573456E+09 845.61 13-JAN-14:09 22.05 13.77
February 0.349790E+10 5606.67 24-FEB-15:00 26.40 17.38 0.552553E+09 845.61 09-FEB-14:09 26.40 17.38
March 0.653020E+10 13820.12 14-MAR-05:02 20.70 16.42 0.685644E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.982985E+10 14864.95 28-APR-05:02 27.22 17.16 0.613600E+09 845.63 04-APR-09:09 27.22 17.16
May 0.132016E+11 19413.51 28-MAY-16:41 41.80 19.54 0.665498E+09 845.61 01-MAY-09:20 41.80 19.54
June 0.132471E+11 18920.92 11-JUN-17:02 42.88 23.08 0.663130E+09 845.70 12-JUN-13:00 43.90 22.36
July 0.122250E+11 18880.01 02-JUL-16:32 40.33 26.50 0.617010E+09 845.60 06-JUL-09:20 35.40 25.87
August 0.117068E+11 17268.53 02-AUG-03:02 28.98 24.83 0.691692E+09 845.60 28-AUG-09:09 30.88 27.50
September 0.934946E+10 18740.12 24-SEP-14:42 35.10 24.80 0.614223E+09 845.60 08-SEP-13:30 35.10 24.80
October 0.753789E+10 14289.53 12-OCT-05:02 21.05 20.47 0.636564E+09 845.61 16-OCT-09:09 26.53 17.36
November 0.471232E+10 5931.09 09-NOV-14:30 29.30 17.79 0.619969E+09 845.62 06-NOV-14:00 29.30 17.79
December 0.310804E+10 3555.20 28-DEC-15:00 24.50 15.39 0.570008E+09 845.61 29-DEC-14:09 19.75 14.80
                     
Annual Sum or Average 0.977666E+11         0.750334E+10        
Minimum of Months 0.282036E+10 3555.20   20.70 13.77 0.552553E+09 845.60   19.75 13.77
Maximum of Months 0.132471E+11 19413.51   42.88 26.50 0.691692E+09 845.70   43.90 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.251318E+10 3524.92 26-JAN-10:00 17.30 12.76 0.283747E+09 521.20 13-JAN-11:20 17.30 12.76
February 0.335076E+10 6241.44 22-FEB-10:00 20.60 13.92 0.266365E+09 521.21 15-FEB-11:20 20.60 13.92
March 0.626307E+10 11230.52 12-MAR-09:23 24.75 16.87 0.325742E+09 521.22 16-MAR-10:20 20.53 15.55
April 0.922490E+10 16467.59 16-APR-09:52 35.00 21.64 0.291845E+09 521.78 14-APR-10:50 35.00 21.64
May 0.113648E+11 17994.83 28-MAY-09:21 35.35 19.88 0.316031E+09 521.74 19-MAY-10:00 35.35 19.88
June 0.103295E+11 16318.97 04-JUN-10:43 36.87 21.80 0.314328E+09 521.68 12-JUN-10:00 41.40 22.35
July 0.903128E+10 16232.01 04-JUL-10:02 35.40 25.09 0.293436E+09 521.60 06-JUL-10:00 37.80 25.49
August 0.853623E+10 13615.72 07-AUG-05:03 29.53 24.79 0.327718E+09 521.20 21-AUG-12:09 30.20 27.51
September 0.739941E+10 15903.65 24-SEP-14:42 35.10 24.80 0.291682E+09 521.20 29-SEP-14:20 33.83 22.63
October 0.672127E+10 16716.65 01-OCT-09:52 29.70 19.34 0.302912E+09 521.22 10-OCT-14:20 31.63 20.81
November 0.440326E+10 6198.50 09-NOV-10:00 24.50 17.90 0.296308E+09 521.21 06-NOV-15:20 24.50 17.90
December 0.274320E+10 4156.04 01-DEC-10:00 18.30 11.37 0.278697E+09 521.21 18-DEC-11:20 22.00 14.81
                     
Annual Sum or Average 0.818809E+11         0.358881E+10        
Minimum of Months 0.251318E+10 3524.92   17.30 11.37 0.266365E+09 521.20   17.30 12.76
Maximum of Months 0.113648E+11 17994.83   36.87 25.09 0.327718E+09 521.78   41.40 27.51



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.701979E+10 17581.65 08-JAN-14:23 22.60 13.48 0.623528E+09 845.85 12-JAN-14:00 23.60 14.20
February 0.759379E+10 20020.60 20-FEB-12:23 25.20 13.29 0.571308E+09 845.99 07-FEB-14:00 25.20 13.29
March 0.111652E+11 19973.64 26-MAR-13:32 30.07 16.56 0.690064E+09 848.37 30-MAR-13:50 32.05 19.26
April 0.125445E+11 20027.83 16-APR-12:32 38.80 21.93 0.614559E+09 845.85 21-APR-13:00 35.00 19.79
May 0.138023E+11 19632.98 28-MAY-16:01 42.20 19.49 0.665635E+09 845.82 04-MAY-13:00 42.20 19.49
June 0.131387E+11 18963.11 11-JUN-16:22 43.25 23.12 0.663119E+09 845.77 12-JUN-13:50 43.80 22.37
July 0.123127E+11 18985.98 02-JUL-16:32 40.33 26.50 0.617026E+09 845.62 06-JUL-09:20 35.40 25.87
August 0.123971E+11 19151.91 27-AUG-14:43 35.52 29.13 0.691875E+09 845.77 07-AUG-13:00 35.52 29.13
September 0.117728E+11 20511.29 24-SEP-14:42 35.10 24.80 0.614858E+09 854.89 28-SEP-13:39 35.37 22.75
October 0.137838E+11 22021.59 01-OCT-13:11 35.43 19.93 0.640763E+09 883.82 02-OCT-13:50 36.37 21.07
November 0.118912E+11 21614.61 12-NOV-13:12 27.87 16.14 0.631966E+09 861.96 01-NOV-13:39 27.87 16.14
December 0.781449E+10 20107.48 03-DEC-13:02 24.08 14.17 0.607762E+09 845.92 06-DEC-14:50 21.82 13.16
                     
Annual Sum or Average 0.135236E+12         0.763246E+10        
Minimum of Months 0.701979E+10 17581.65   22.60 13.29 0.571308E+09 845.62   21.82 13.16
Maximum of Months 0.138023E+11 22021.59   43.25 29.13 0.691875E+09 883.82   43.80 29.13



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292566E+10 5187.61 31-JAN-16:00 21.10 11.23 0.378028E+09 544.94 25-JAN-14:00 21.10 11.23
February 0.357677E+10 10246.83 20-FEB-15:43 25.72 14.13 0.359289E+09 544.95 09-FEB-14:09 25.72 14.13
March 0.675453E+10 16661.43 12-MAR-17:23 29.85 19.55 0.443575E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.100248E+11 18114.90 30-APR-16:02 37.68 18.13 0.396262E+09 544.95 04-APR-09:09 37.68 18.13
May 0.118434E+11 18986.17 28-MAY-16:01 42.20 19.49 0.429292E+09 544.95 03-MAY-09:20 42.20 19.49
June 0.114785E+11 18241.39 11-JUN-16:22 43.25 23.12 0.427687E+09 544.95 07-JUN-09:20 43.25 23.12
July 0.981968E+10 18095.36 02-JUL-16:32 40.33 26.50 0.397885E+09 544.94 06-JUL-09:20 35.40 25.87
August 0.955318E+10 17610.66 06-AUG-16:22 36.15 26.34 0.446078E+09 544.94 28-AUG-09:09 30.88 27.50
September 0.799230E+10 18098.27 24-SEP-14:42 35.10 24.80 0.396206E+09 544.94 08-SEP-13:30 35.10 24.80
October 0.718103E+10 18856.78 01-OCT-15:51 35.50 20.15 0.411274E+09 544.95 16-OCT-09:09 26.53 17.36
November 0.493452E+10 14342.84 12-NOV-15:12 27.97 15.72 0.402572E+09 544.96 06-NOV-14:00 27.97 15.72
December 0.324451E+10 5662.30 01-DEC-15:30 22.85 13.56 0.375109E+09 544.95 29-DEC-14:09 19.75 14.80
                     
Annual Sum or Average 0.893289E+11         0.486326E+10        
Minimum of Months 0.292566E+10 5187.61   21.10 11.23 0.359289E+09 544.94   19.75 11.23
Maximum of Months 0.118434E+11 18986.17   43.25 26.50 0.446078E+09 544.96   43.25 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.215562E+10 3129.44 26-JAN-15:00 21.60 13.66 0.519460E+09 845.60 26-JAN-14:30 21.60 13.66
February 0.311071E+10 5757.36 23-FEB-14:50 25.90 14.07 0.521636E+09 845.61 24-FEB-14:20 26.07 17.12
March 0.656816E+10 13558.29 14-MAR-05:02 20.70 16.42 0.676585E+09 845.63 30-MAR-13:50 32.05 19.26
April 0.109786E+11 22425.99 16-APR-15:41 39.37 22.61 0.613294E+09 845.63 04-APR-09:09 39.37 22.61
May 0.152080E+11 23072.30 28-MAY-16:11 42.10 19.51 0.665667E+09 845.61 08-MAY-13:09 42.10 19.51
June 0.153121E+11 22971.45 04-JUN-16:31 41.97 22.48 0.663299E+09 845.62 12-JUN-13:09 43.40 22.40
July 0.139347E+11 22741.27 02-JUL-16:32 40.33 26.50 0.617226E+09 845.60 10-JUL-09:09 32.98 26.50
August 0.130612E+11 21402.19 06-AUG-15:42 36.30 26.24 0.691825E+09 845.60 28-AUG-09:09 30.88 27.50
September 0.102135E+11 22620.07 17-SEP-14:52 34.20 26.01 0.614194E+09 845.60 08-SEP-13:39 34.20 26.01
October 0.775445E+10 15286.49 04-OCT-05:02 25.07 21.35 0.633299E+09 845.61 16-OCT-09:20 26.87 17.49
November 0.433489E+10 6421.82 09-NOV-14:40 29.27 17.76 0.599860E+09 845.62 06-NOV-14:50 29.27 17.76
December 0.245637E+10 2982.71 28-DEC-15:50 23.92 15.23 0.520424E+09 845.61 28-DEC-14:00 23.92 15.23
                     
Annual Sum or Average 0.105088E+12         0.733677E+10        
Minimum of Months 0.215562E+10 2982.71   20.70 13.66 0.519460E+09 845.60   21.60 13.66
Maximum of Months 0.153121E+11 23072.30   42.10 26.50 0.691825E+09 845.63   43.40 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.202946E+10 3024.32 26-JAN-14:30 22.05 13.77 0.357817E+09 544.94 13-JAN-14:39 22.05 13.77
February 0.299243E+10 5702.31 23-FEB-10:40 22.80 14.32 0.353544E+09 544.95 15-FEB-10:50 22.80 14.32
March 0.639082E+10 16454.10 12-MAR-16:22 30.95 19.85 0.441945E+09 544.96 27-MAR-09:20 23.77 16.23
April 0.102694E+11 18984.57 16-APR-09:02 33.08 21.25 0.396088E+09 545.23 28-APR-09:50 33.47 18.33
May 0.129502E+11 19384.98 07-MAY-09:51 36.20 20.86 0.429301E+09 545.23 12-MAY-09:20 33.00 23.15
June 0.119045E+11 17604.11 11-JUN-10:22 37.75 25.19 0.427605E+09 545.10 02-JUN-09:20 37.75 25.19
July 0.103108E+11 17464.38 04-JUL-10:02 35.40 25.09 0.397861E+09 545.05 07-JUL-09:00 36.90 24.55
August 0.961047E+10 16901.28 06-AUG-15:02 36.30 26.24 0.445926E+09 544.94 28-AUG-09:09 30.88 27.50
September 0.815214E+10 17470.79 17-SEP-14:52 34.20 26.01 0.395916E+09 544.94 08-SEP-13:39 34.20 26.01
October 0.698097E+10 11882.51 01-OCT-10:02 30.08 19.42 0.410064E+09 544.95 17-OCT-09:20 26.63 18.34
November 0.411598E+10 5906.63 09-NOV-10:20 25.33 18.04 0.398582E+09 544.95 06-NOV-14:50 25.33 18.04
December 0.220834E+10 3089.37 01-DEC-14:50 23.42 13.31 0.359198E+09 544.94 28-DEC-14:09 24.58 15.31
                     
Annual Sum or Average 0.879155E+11         0.481385E+10        
Minimum of Months 0.202946E+10 3024.32   22.05 13.31 0.353544E+09 544.94   22.05 13.77
Maximum of Months 0.129502E+11 19384.98   37.75 26.24 0.445926E+09 545.23   37.75 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.544418E+10 11874.19 12-JAN-14:20 23.40 14.05 0.595185E+09 845.64 25-JAN-14:00 23.00 13.41
February 0.678222E+10 22961.50 20-FEB-15:43 25.72 14.13 0.556517E+09 845.93 21-FEB-14:00 26.30 15.42
March 0.112417E+11 24195.88 12-MAR-13:42 31.12 19.32 0.686371E+09 846.00 09-MAR-14:00 31.12 19.32
April 0.139152E+11 23332.65 16-APR-15:01 39.63 22.37 0.614460E+09 846.06 21-APR-13:20 34.67 19.93
May 0.158691E+11 23269.98 07-MAY-15:11 42.37 21.49 0.665789E+09 845.99 01-MAY-13:20 42.37 21.49
June 0.151917E+11 22933.34 04-JUN-15:51 42.30 22.20 0.663295E+09 846.06 12-JUN-13:20 43.50 22.39
July 0.140226E+11 22730.01 02-JUL-16:32 40.33 26.50 0.617241E+09 845.62 10-JUL-13:09 39.20 26.78
August 0.138060E+11 22519.96 06-AUG-14:22 36.10 26.31 0.692009E+09 845.62 28-AUG-09:09 30.88 27.50
September 0.127692E+11 24219.07 17-SEP-14:52 34.20 26.01 0.614799E+09 845.82 26-SEP-13:00 35.70 22.91
October 0.140824E+11 25030.65 22-OCT-13:52 30.80 17.95 0.638952E+09 857.06 02-OCT-13:50 30.80 17.95
November 0.112476E+11 25001.93 05-NOV-13:42 29.32 17.20 0.626735E+09 846.06 21-NOV-14:00 26.70 14.93
December 0.632462E+10 21256.23 03-DEC-13:32 24.33 14.17 0.588887E+09 845.64 04-DEC-14:50 23.20 14.19
                     
Annual Sum or Average 0.140697E+12         0.756024E+10        
Minimum of Months 0.544418E+10 11874.19   23.40 14.05 0.556517E+09 845.62   23.00 13.41
Maximum of Months 0.158691E+11 25030.65   42.37 26.50 0.692009E+09 857.06   43.50 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.239876E+10 4674.48 12-JAN-15:50 23.35 14.44 0.351200E+09 544.94 25-JAN-14:00 23.00 13.41
February 0.330481E+10 8499.11 20-FEB-15:43 25.72 14.13 0.342644E+09 544.95 24-FEB-14:20 26.07 17.12
March 0.681778E+10 20539.15 12-MAR-16:22 30.95 19.85 0.438973E+09 544.96 30-MAR-13:50 32.05 19.26
April 0.109537E+11 20700.95 30-APR-16:02 37.68 18.13 0.396164E+09 544.96 04-APR-09:09 37.68 18.13
May 0.133107E+11 21507.39 28-MAY-16:11 42.10 19.51 0.429306E+09 544.95 05-MAY-09:00 42.10 19.51
June 0.129839E+11 21212.49 04-JUN-16:31 41.97 22.48 0.427698E+09 544.95 12-JUN-13:09 43.40 22.40
July 0.110148E+11 20820.03 02-JUL-16:32 40.33 26.50 0.397940E+09 544.94 10-JUL-09:09 32.98 26.50
August 0.104770E+11 20041.98 06-AUG-16:22 36.15 26.34 0.446081E+09 544.94 28-AUG-09:09 30.88 27.50
September 0.867027E+10 20695.12 17-SEP-14:52 34.20 26.01 0.396071E+09 544.94 08-SEP-13:39 34.20 26.01
October 0.736970E+10 20076.81 22-OCT-15:52 30.40 17.68 0.409609E+09 544.95 16-OCT-09:20 30.40 17.68
November 0.468770E+10 15036.99 05-NOV-15:42 28.08 17.72 0.392332E+09 544.96 06-NOV-14:50 28.48 18.19
December 0.274416E+10 5295.54 28-DEC-15:40 24.03 15.27 0.351081E+09 544.95 29-DEC-14:50 19.55 14.90
                     
Annual Sum or Average 0.947333E+11         0.477910E+10        
Minimum of Months 0.239876E+10 4674.48   23.35 14.13 0.342644E+09 544.94   19.55 13.41
Maximum of Months 0.133107E+11 21507.39   42.10 26.50 0.446081E+09 544.96   43.40 27.50



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.369702E+10 6991.68 17-JAN-06:13 10.70 10.27 0.00 0.00 01-JAN-00:10 10.70 10.27
February 0.496714E+10 10225.49 21-FEB-06:15 11.70 10.89 0.00 0.00 01-FEB-00:10 11.70 10.89
March 0.869111E+10 10811.52 06-MAR-06:13 15.77 13.93 0.00 0.00 01-MAR-00:10 15.77 13.93
April 0.119360E+11 16257.10 17-APR-05:15 24.33 18.88 0.00 0.00 01-APR-00:10 24.33 18.88
May 0.129241E+11 17755.84 30-MAY-05:15 30.30 21.64 0.00 0.00 01-MAY-00:10 30.30 21.64
June 0.129059E+11 17355.93 12-JUN-05:15 34.23 19.16 0.00 0.00 01-JUN-00:10 34.23 19.16
July 0.126902E+11 18071.93 05-JUL-05:15 32.63 24.69 0.00 0.00 01-JUL-00:10 32.63 24.69
August 0.138079E+11 17631.53 07-AUG-05:13 29.57 24.74 0.00 0.00 01-AUG-00:10 29.57 24.74
September 0.994747E+10 13175.73 05-SEP-05:15 26.20 25.15 0.00 0.00 01-SEP-00:10 26.20 25.15
October 0.975623E+10 11566.60 10-OCT-05:10 19.80 18.03 0.00 0.00 01-OCT-00:10 19.80 18.03
November 0.767231E+10 11739.03 06-NOV-06:13 14.80 13.74 0.00 0.00 01-NOV-00:10 14.80 13.74
December 0.543259E+10 9077.87 26-DEC-06:13 10.23 8.49 0.00 0.00 01-DEC-00:10 10.23 8.49
                     
Annual Sum or Average 0.114428E+12         0.00        
Minimum of Months 0.369702E+10 6991.68   10.23 8.49 0.00 0.00   10.23 8.49
Maximum of Months 0.138079E+11 18071.93   34.23 25.15 0.00 0.00   34.23 25.15



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191019E+10 3840.52 20-JAN-06:10 7.47 6.75 0.00 0.00 01-JAN-00:10 7.47 6.75
February 0.311325E+10 4968.25 21-FEB-06:15 11.70 10.89 0.00 0.00 01-FEB-00:10 11.70 10.89
March 0.644008E+10 7305.32 13-MAR-16:00 32.50 18.65 0.00 0.00 01-MAR-00:10 32.50 18.65
April 0.917772E+10 8362.01 17-APR-15:10 34.65 21.60 0.00 0.00 01-APR-00:10 34.65 21.60
May 0.112479E+11 11081.53 31-MAY-05:03 31.72 21.12 0.00 0.00 01-MAY-00:10 31.72 21.12
June 0.108545E+11 10939.00 10-JUN-05:03 29.67 22.80 0.00 0.00 01-JUN-00:10 29.67 22.80
July 0.100836E+11 10485.90 07-JUL-05:03 31.52 25.91 0.00 0.00 01-JUL-00:10 31.52 25.91
August 0.988290E+10 11036.50 08-AUG-05:02 30.10 25.30 0.00 0.00 01-AUG-00:10 30.10 25.30
September 0.846099E+10 11569.19 05-SEP-05:15 26.20 25.15 0.00 0.00 01-SEP-00:10 26.20 25.15
October 0.775420E+10 9077.00 16-OCT-05:13 20.50 15.01 0.00 0.00 01-OCT-00:10 20.50 15.01
November 0.513158E+10 6956.99 06-NOV-06:13 14.80 13.74 0.00 0.00 01-NOV-00:10 14.80 13.74
December 0.269388E+10 4197.97 20-DEC-06:10 6.40 4.05 0.00 0.00 01-DEC-00:10 6.40 4.05
                     
Annual Sum or Average 0.867508E+11         0.00        
Minimum of Months 0.191019E+10 3840.52   6.40 4.05 0.00 0.00   6.40 4.05
Maximum of Months 0.112479E+11 11569.19   34.65 25.91 0.00 0.00   34.65 25.91



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.165985E+10 6448.44 12-JAN-15:00 23.60 14.20 0.00 0.00 01-JAN-00:10 23.60 14.20
February 0.388441E+10 13210.73 22-FEB-14:50 27.08 16.22 0.00 0.00 01-FEB-00:10 27.08 16.22
March 0.103755E+11 20925.33 28-MAR-15:20 35.57 18.58 0.00 0.00 01-MAR-00:10 35.57 18.58
April 0.182599E+11 25800.19 26-APR-14:50 39.22 22.03 0.00 0.00 01-APR-00:10 39.22 22.03
May 0.238305E+11 29385.58 01-MAY-14:20 43.93 22.01 0.00 0.00 01-MAY-00:10 43.93 22.01
June 0.237444E+11 30910.08 12-JUN-13:50 43.80 22.37 0.00 0.00 01-JUN-00:10 43.80 22.37
July 0.194390E+11 27485.09 07-JUL-14:00 40.30 24.54 0.00 0.00 01-JUL-00:10 40.30 24.54
August 0.178762E+11 24488.57 07-AUG-14:00 37.20 26.26 0.00 0.00 01-AUG-00:10 37.20 26.26
September 0.140258E+11 21333.92 26-SEP-14:40 35.97 22.76 0.00 0.00 01-SEP-00:10 35.97 22.76
October 0.118977E+11 20275.13 02-OCT-14:00 36.40 21.05 0.00 0.00 01-OCT-00:10 36.40 21.05
November 0.639852E+10 14160.35 09-NOV-14:10 29.37 17.83 0.00 0.00 01-NOV-00:10 29.37 17.83
December 0.210124E+10 7952.38 01-DEC-14:30 23.45 13.21 0.00 0.00 01-DEC-00:10 23.45 13.21
                     
Annual Sum or Average 0.153493E+12         0.00        
Minimum of Months 0.165985E+10 6448.44   23.45 13.21 0.00 0.00   23.45 13.21
Maximum of Months 0.238305E+11 30910.08   43.93 26.26 0.00 0.00   43.93 26.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.404960E+10 1887.21 30-JAN-17:00 19.20 10.80 95236668.02 126.85 17-JAN-14:50 19.20 10.80
February 0.848571E+10 3915.09 20-FEB-17:15 24.07 14.47 86404015.41 126.84 09-FEB-14:00 24.07 14.47
March 0.146372E+11 7201.51 31-MAR-23:53 23.70 16.75 0.103242E+09 126.84 23-MAR-09:09 23.70 16.75
April 0.191087E+11 7748.08 17-APR-01:55 26.00 19.96 95633468.81 146.09 27-APR-13:00 39.60 19.54
May 0.476590E+10 3494.18 31-MAY-24:00 28.10 22.60 99240598.27 126.85 10-MAY-13:39 28.10 22.60
June 0.948324E+10 5404.43 30-JUN-24:00 33.10 24.67 98979850.43 126.88 27-JUN-09:00 33.10 24.67
July 0.148525E+11 7250.20 31-JUL-24:00 29.40 26.34 91893539.13 126.85 27-JUL-09:09 29.40 26.34
August 0.195281E+11 7547.82 16-AUG-00:50 23.73 23.24 0.113266E+09 152.21 07-AUG-13:00 23.73 23.24
September 0.454382E+10 3486.88 30-SEP-24:00 26.60 21.92 91606574.04 126.85 29-SEP-13:09 26.60 21.92
October 0.970926E+10 5386.65 31-OCT-24:00 17.80 15.13 95244984.43 126.86 06-OCT-09:20 17.80 15.13
November 0.141846E+11 5798.22 12-NOV-16:23 26.95 15.49 94304960.06 126.83 09-NOV-10:09 26.95 15.49
December 0.195166E+11 7603.79 28-DEC-17:00 22.80 14.91 91882180.85 126.83 11-DEC-10:09 22.80 14.91
                     
Annual Sum or Average 0.142865E+12         0.115693E+10        
Minimum of Months 0.404960E+10 1887.21   17.80 10.80 86404015.41 126.83   17.80 10.80
Maximum of Months 0.195281E+11 7748.08   33.10 26.34 0.113266E+09 152.21   39.60 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.292516E+10 1735.60 12-JAN-17:00 22.30 14.53 95235189.93 126.84 13-JAN-14:00 21.50 15.25
February 0.754953E+10 3622.26 21-FEB-17:00 25.40 15.70 86403534.57 126.84 09-FEB-14:00 25.40 15.70
March 0.138240E+11 6949.20 31-MAR-23:53 23.70 16.75 0.103241E+09 126.83 29-MAR-09:09 23.70 16.75
April 0.180921E+11 7244.24 12-APR-16:00 28.10 17.52 95365586.80 144.51 26-APR-13:00 38.80 22.02
May 0.443053E+10 3365.50 31-MAY-24:00 28.10 22.60 99238204.75 126.85 30-MAY-13:00 28.10 22.60
June 0.897229E+10 5201.09 30-JUN-24:00 33.10 24.67 98979214.62 126.87 27-JUN-09:50 33.10 24.67
July 0.140757E+11 6927.47 31-JUL-23:43 29.40 26.34 91894354.97 126.85 18-JUL-09:00 29.40 26.34
August 0.184226E+11 7130.42 16-AUG-09:40 25.23 24.59 0.111575E+09 147.90 07-AUG-13:00 25.23 24.59
September 0.419038E+10 3369.15 30-SEP-24:00 26.60 21.92 91605401.01 126.84 27-SEP-13:20 26.60 21.92
October 0.911447E+10 5084.85 31-OCT-24:00 17.80 15.13 95244111.18 126.86 06-OCT-09:00 17.80 15.13
November 0.131789E+11 5445.65 08-NOV-16:40 28.33 18.82 94304883.95 126.83 09-NOV-10:09 24.92 17.98
December 0.178417E+11 7195.50 01-DEC-17:00 21.20 14.26 91882297.01 126.83 11-DEC-10:00 10.00 9.32
                     
Annual Sum or Average 0.132617E+12         0.115497E+10        
Minimum of Months 0.292516E+10 1735.60   17.80 14.26 86403534.57 126.83   10.00 9.32
Maximum of Months 0.184226E+11 7244.24   33.10 26.34 0.111575E+09 147.90   38.80 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.148960E+10 1731.45 12-JAN-17:00 22.30 14.53 95015606.26 126.84 13-JAN-14:00 21.50 15.25
February 0.682727E+10 3656.86 22-FEB-17:00 25.70 15.75 86404196.42 126.84 15-FEB-14:00 25.70 15.75
March 0.136453E+11 6899.61 31-MAR-23:53 23.70 16.75 0.103242E+09 126.84 29-MAR-09:09 23.70 16.75
April 0.182540E+11 7463.63 16-APR-21:32 28.07 20.03 94223769.91 143.03 26-APR-13:00 38.80 22.02
May 0.466363E+10 3341.38 31-MAY-24:00 28.10 22.60 99239146.83 126.85 30-MAY-13:09 28.10 22.60
June 0.919537E+10 5250.79 30-JUN-24:00 33.10 24.67 98981027.70 126.88 28-JUN-13:09 33.10 24.67
July 0.142874E+11 7047.25 31-JUL-23:57 29.40 26.34 91896111.45 126.85 12-JUL-13:09 29.40 26.34
August 0.187458E+11 7296.00 20-AUG-17:33 26.43 25.55 0.109009E+09 146.65 07-AUG-13:00 26.43 25.55
September 0.426521E+10 3356.05 30-SEP-23:17 26.60 22.12 91605459.11 126.84 27-SEP-13:20 26.60 22.12
October 0.902218E+10 4941.58 31-OCT-24:00 17.80 15.13 95245389.23 126.86 06-OCT-09:00 17.80 15.13
November 0.126558E+11 5493.45 08-NOV-16:30 28.55 18.76 94305607.26 126.83 09-NOV-10:09 24.92 17.98
December 0.165930E+11 7190.26 28-DEC-17:00 22.80 14.91 91882912.38 126.83 11-DEC-10:50 22.80 14.91
                     
Annual Sum or Average 0.129645E+12         0.115105E+10        
Minimum of Months 0.148960E+10 1731.45   17.80 14.53 86404196.42 126.83   17.80 14.91
Maximum of Months 0.187458E+11 7463.63   33.10 26.34 0.109009E+09 146.65   38.80 26.34



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.241088E+12 92473.16 12-JAN-17:00 22.30 14.53 0.206242E+10 2748.28 26-JAN-10:09 17.70 12.86
February 0.437544E+12 183895.03 21-FEB-17:00 25.40 15.70 0.187106E+10 2749.09 09-FEB-14:09 25.40 15.70
March 0.729233E+12 358642.06 31-MAR-23:57 23.70 16.75 0.223526E+10 2749.78 21-MAR-09:09 23.70 16.75
April 0.934111E+12 368779.80 30-APR-04:53 22.70 16.37 0.240827E+10 4040.51 28-APR-13:00 22.70 16.37
May 0.241964E+12 176019.30 31-MAY-24:00 28.10 22.60 0.214885E+10 2747.25 24-MAY-09:00 28.10 22.60
June 0.471565E+12 268193.27 30-JUN-24:00 33.10 24.67 0.214278E+10 2746.96 27-JUN-09:00 33.10 24.67
July 0.734787E+12 356261.78 31-JUL-23:20 29.40 26.34 0.198927E+10 2746.02 18-JUL-09:00 29.40 26.34
August 0.966883E+12 369681.22 15-AUG-23:53 23.40 22.91 0.293726E+10 4087.37 07-AUG-13:00 23.40 22.91
September 0.239065E+12 177491.45 30-SEP-24:00 26.60 21.92 0.198368E+10 2747.27 01-SEP-09:30 26.60 21.92
October 0.490165E+12 269346.88 31-OCT-24:00 17.80 15.13 0.206191E+10 2746.43 13-OCT-09:09 17.80 15.13
November 0.710886E+12 277030.05 13-NOV-17:00 26.40 16.65 0.204192E+10 2749.74 28-NOV-10:30 18.60 13.96
December 0.978876E+12 368383.94 04-DEC-17:00 20.10 14.52 0.199056E+10 2818.56 28-DEC-14:00 24.50 15.39
                     
Annual Sum or Average 0.717617E+13         0.258733E+11        
Minimum of Months 0.239065E+12 92473.16   17.80 14.52 0.187106E+10 2746.02   17.70 12.86
Maximum of Months 0.978876E+12 369681.22   33.10 26.34 0.293726E+10 4087.37   33.10 26.34



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 3575357.53 2409.09 14-JAN-17:03 20.55
February 52403877.96 9294.00 20-FEB-14:05 26.38
March 0.133021E+09 15691.62 11-MAR-17:02 29.70
April 0.442592E+09 30037.96 15-APR-16:01 39.58
May 0.610702E+09 33373.02 27-MAY-16:01 42.00
June 0.600621E+09 35206.26 10-JUN-16:01 43.12
July 0.804879E+09 29444.50 02-JUL-16:28 40.35
August 0.517245E+09 24458.33 05-AUG-16:01 35.70
September 0.651407E+09 22520.28 30-SEP-16:02 34.78
October 0.484766E+09 22951.17 01-OCT-15:43 35.58
November 0.169209E+09 14552.55 05-NOV-13:50 29.32
December 15443225.38 9125.93 03-DEC-13:43 24.42
         
Annual Sum or Average 0.448586E+10      
Minimum of Months 3575357.53 2409.09   20.55
Maximum of Months 0.804879E+09 35206.26   43.12



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.243611E+09 61371.01 02-JAN-05:01 6.48
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.243611E+09      
Minimum of Months 0.00 0.00   6.48
Maximum of Months 0.243611E+09 61371.01   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 1509235.62 3722.00 02-JAN-06:01 6.45
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 2510.44 16.74 23-DEC-06:08 5.43
         
Annual Sum or Average 1511746.06      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 1509235.62 3722.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 100048.35 459.12 03-JAN-06:05 5.57
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 100048.35      
Minimum of Months 0.00 0.00   5.57
Maximum of Months 100048.35 459.12   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.576556E+09 16867.79 02-JAN-04:02 6.67
February 67492235.15 14467.92 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 40864.27 261.57 27-NOV-06:05 9.55
December 0.182358E+09 14460.12 20-DEC-06:02 6.40
         
Annual Sum or Average 0.826447E+09      
Minimum of Months 0.00 0.00   6.40
Maximum of Months 0.576556E+09 16867.79   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.229675E+09 11589.49 02-JAN-04:02 6.67
February 17113153.93 10039.96 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 53356422.83 9816.20 21-DEC-06:02 5.27
         
Annual Sum or Average 0.300144E+09      
Minimum of Months 0.00 0.00   5.27
Maximum of Months 0.229675E+09 11589.49   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.153375E+09 16202.45 02-JAN-05:01 6.48
February 14807071.10 14456.42 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 20930135.83 13235.45 23-DEC-06:03 5.43
         
Annual Sum or Average 0.189113E+09      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 0.153375E+09 16202.45   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.143728E+09 11193.19 02-JAN-05:01 6.48
February 8356197.91 9459.04 11-FEB-06:02 9.30
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 25091763.76 8836.50 23-DEC-06:03 5.43
         
Annual Sum or Average 0.177176E+09      
Minimum of Months 0.00 0.00   5.43
Maximum of Months 0.143728E+09 11193.19   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 67962756.48 9320.49 17-JAN-04:02 11.75
February 82086192.63 8834.08 13-FEB-04:03 11.62
March 77798583.06 7993.51 21-MAR-03:02 14.88
April 55949950.79 7131.99 16-APR-15:01 39.63
May 33960403.90 6023.99 07-MAY-15:11 42.37
June 39705313.17 7542.96 04-JUN-15:51 42.30
July 62084144.98 6044.11 30-JUL-14:22 34.60
August 63584765.11 6389.49 27-AUG-15:02 35.43
September 55321580.88 6504.26 09-SEP-03:02 24.35
October 79625654.36 7183.57 27-OCT-03:02 17.72
November 97521060.12 8737.46 24-NOV-04:02 11.00
December 0.127876E+09 11258.94 11-DEC-04:02 10.80
         
Annual Sum or Average 0.843476E+09      
Minimum of Months 33960403.90 6023.99   10.80
Maximum of Months 0.127876E+09 11258.94   42.37



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 60178767.45 7235.63 02-JAN-06:01 6.45
February 45483901.88 6513.99 27-FEB-04:02 11.72
March 44014133.11 6094.82 29-MAR-03:02 21.75
April 35403566.26 6513.59 13-APR-03:02 24.18
May 37478530.62 7758.71 24-MAY-03:02 26.12
June 27525410.40 7123.71 21-JUN-03:02 28.25
July 46363501.00 7471.39 27-JUL-03:02 27.18
August 38504486.15 7222.02 17-AUG-03:02 27.35
September 51003888.36 9118.75 11-SEP-03:02 26.07
October 51469004.63 5693.94 11-OCT-03:02 24.45
November 48514052.91 5537.47 28-NOV-05:03 15.20
December 50128433.23 6898.62 22-DEC-06:03 12.42
         
Annual Sum or Average 0.536068E+09      
Minimum of Months 27525410.40 5537.47   6.45
Maximum of Months 60178767.45 9118.75   28.25



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.217587E+10 19541.47 02-JAN-06:13 6.50
February 0.984266E+09 18117.52 27-FEB-06:03 10.82
March 0.383634E+09 17791.18 01-MAR-06:02 13.67
April 82798449.74 13668.28 10-APR-05:02 18.28
May 18747756.06 8868.96 25-MAY-03:02 26.60
June 10367076.70 8237.15 28-JUN-03:02 26.40
July 10745772.45 6617.71 27-JUL-03:02 27.18
August 17287372.68 7495.90 24-AUG-03:02 25.58
September 42961569.23 11064.57 11-SEP-03:02 26.07
October 0.217483E+09 16183.94 27-OCT-05:02 16.90
November 0.661675E+09 18226.89 06-NOV-06:02 14.70
December 0.160618E+10 14692.14 29-DEC-06:02 16.53
         
Annual Sum or Average 0.621202E+10      
Minimum of Months 10367076.70 6617.71   6.50
Maximum of Months 0.217587E+10 19541.47   27.18



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 66865428.96 331.75 01-JAN-14:00 16.20
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 66865428.96      
Minimum of Months 0.00 0.00   9.73
Maximum of Months 66865428.96 331.75   32.95



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:10 7.83
February 0.00 0.00 01-FEB-00:10 9.73
March 0.00 0.00 01-MAR-00:10 15.55
April 0.00 0.00 01-APR-00:03 23.70
May 0.00 0.00 01-MAY-00:05 30.53
June 0.00 0.00 01-JUN-00:10 28.05
July 0.00 0.00 01-JUL-00:05 32.95
August 0.00 0.00 01-AUG-00:03 29.32
September 0.00 0.00 01-SEP-00:03 28.43
October 0.00 0.00 01-OCT-00:03 26.58
November 0.00 0.00 01-NOV-00:10 17.72
December 0.00 0.00 01-DEC-00:10 12.50
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   7.83
Maximum of Months 0.00 0.00   32.95



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.148304E+11 15519.45 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.134523E+11 15519.45 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.159851E+11 15519.45 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.142779E+11 15519.45 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.154078E+11 15519.45 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.153333E+11 15519.45 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.143524E+11 15519.45 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.159851E+11 15519.45 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.142779E+11 15519.45 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.148304E+11 15519.45 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.146566E+11 15519.45 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.143524E+11 15519.45 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.177742E+12     0.424397E+12    
Minimum of Months 0.134523E+11 15519.45   0.325565E+11 13457.54  
Maximum of Months 0.159851E+11 15519.45   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321286E+12    
Minimum of Months 0.120811E+11 13937.56   0.244881E+11 18128.59  
Maximum of Months 0.143557E+11 13937.56   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.119284E+10 1518.11 18-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.106120E+10 1493.71 10-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.122685E+10 1506.04 14-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108392E+10 1075.02 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.115420E+10 1249.63 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.114798E+10 1240.40 23-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.108862E+10 1459.75 26-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.121752E+10 1495.67 16-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110108E+10 1531.62 08-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.116174E+10 1595.59 11-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.117402E+10 1570.33 27-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.116591E+10 1578.40 29-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.137759E+11     0.403423E+11    
Minimum of Months 0.106120E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.122685E+10 1595.59   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.764375E+09 973.30 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.682979E+09 967.62 09-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.789745E+09 909.26 14-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.699325E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.746469E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.742294E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.702323E+09 917.91 26-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.784517E+09 943.58 16-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.709467E+09 968.41 07-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.745665E+09 1016.67 11-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.755439E+09 1029.58 27-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.747625E+09 1023.86 29-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.887022E+10     0.259981E+11    
Minimum of Months 0.682979E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.789745E+09 1029.58   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.116785E+10 1473.40 18-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.104951E+10 1456.78 10-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.122283E+10 1492.56 14-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.108531E+10 1075.05 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.115978E+10 1287.72 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.115290E+10 1296.72 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.109261E+10 1476.24 26-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.121960E+10 1502.97 16-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.110006E+10 1529.49 08-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.115302E+10 1589.31 11-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.115440E+10 1476.84 27-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.113822E+10 1537.17 29-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.136961E+11     0.403429E+11    
Minimum of Months 0.104951E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.122283E+10 1589.31   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.761171E+09 985.07 18-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.679755E+09 972.30 10-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.791821E+09 995.66 14-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.699843E+09 858.71 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.747200E+09 866.74 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.742235E+09 868.08 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.704269E+09 961.95 26-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.787792E+09 979.52 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.711323E+09 997.33 08-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.750330E+09 1032.79 11-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.747485E+09 959.54 03-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.739528E+09 977.42 29-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.886275E+10     0.259979E+11    
Minimum of Months 0.679755E+09 858.71   0.198154E+10 1466.94  
Maximum of Months 0.791821E+09 1032.79   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.119505E+10 1524.72 18-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.106222E+10 1501.05 10-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.122769E+10 1513.20 14-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108421E+10 1075.02 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.115539E+10 1264.06 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.114884E+10 1255.10 23-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.108930E+10 1468.23 26-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.121857E+10 1503.11 16-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110214E+10 1538.01 08-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.116304E+10 1600.11 11-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.117563E+10 1575.52 27-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.116805E+10 1583.38 29-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.137901E+11     0.403423E+11    
Minimum of Months 0.106222E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.122769E+10 1600.11   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.764789E+09 974.56 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.683231E+09 968.84 09-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.790057E+09 911.74 14-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.699478E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.746630E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.742404E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.702580E+09 921.23 26-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.784739E+09 945.96 16-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.709644E+09 970.43 08-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.745801E+09 1017.83 11-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.755814E+09 1030.46 27-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.748082E+09 1024.69 29-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.887325E+10     0.259981E+11    
Minimum of Months 0.683231E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.790057E+09 1030.46   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.117096E+10 1483.05 18-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.104998E+10 1465.43 10-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.122342E+10 1500.25 14-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.108567E+10 1075.05 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.116037E+10 1300.75 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.115367E+10 1309.39 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.109362E+10 1484.11 26-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.122041E+10 1510.13 16-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.110069E+10 1535.96 08-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.115247E+10 1594.09 11-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.115511E+10 1485.33 27-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.113972E+10 1543.67 29-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.137061E+11     0.403429E+11    
Minimum of Months 0.104998E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.122342E+10 1594.09   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.761629E+09 986.19 18-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.680120E+09 973.47 10-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.792152E+09 996.62 14-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.700030E+09 861.42 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.747333E+09 868.65 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.742337E+09 869.98 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.704619E+09 963.17 26-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.788011E+09 980.60 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.711551E+09 998.29 08-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.750650E+09 1033.49 11-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.747778E+09 961.41 03-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.739903E+09 979.00 29-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.886611E+10     0.259979E+11    
Minimum of Months 0.680120E+09 861.42   0.198154E+10 1466.94  
Maximum of Months 0.792152E+09 1033.49   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.119506E+10 1524.51 18-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.106222E+10 1500.81 10-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.122769E+10 1513.02 14-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108422E+10 1075.02 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.115539E+10 1263.67 24-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.114881E+10 1254.71 23-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.108928E+10 1467.96 26-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.121849E+10 1502.87 16-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110213E+10 1537.80 08-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.116303E+10 1599.95 11-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.117563E+10 1575.44 27-NOV-16:00 0.332024E+10 2276.32 01-NOV-07:10
December 0.116806E+10 1583.24 29-DEC-16:00 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.137900E+11     0.403423E+11    
Minimum of Months 0.106222E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.122769E+10 1599.95   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.764799E+09 974.44 17-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.683233E+09 968.69 09-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.790061E+09 911.68 14-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.699481E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.746628E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.742399E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.702572E+09 921.10 26-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.784732E+09 945.84 16-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.709641E+09 970.32 08-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.745800E+09 1017.75 11-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.755818E+09 1030.41 27-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.748091E+09 1024.60 29-DEC-16:00 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.887325E+10     0.259981E+11    
Minimum of Months 0.683233E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.790061E+09 1030.41   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.117097E+10 1482.85 18-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.104998E+10 1465.20 10-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.122342E+10 1500.08 14-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.108567E+10 1075.05 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.116036E+10 1300.36 24-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.115365E+10 1309.00 23-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.109360E+10 1483.84 26-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.122039E+10 1509.89 16-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.110068E+10 1535.75 08-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.115247E+10 1593.94 11-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.115512E+10 1485.29 27-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.113975E+10 1543.55 29-DEC-16:00 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.137061E+11     0.403429E+11    
Minimum of Months 0.104998E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.122342E+10 1593.94   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.761640E+09 986.06 18-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.680124E+09 973.33 10-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.792177E+09 996.51 14-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.700034E+09 861.42 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.747331E+09 868.41 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.742331E+09 869.75 23-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.704606E+09 963.00 26-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.787999E+09 980.46 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.711546E+09 998.16 08-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.750648E+09 1033.39 11-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.747830E+09 961.38 03-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.739913E+09 978.95 29-DEC-16:00 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.886618E+10     0.259979E+11    
Minimum of Months 0.680124E+09 861.42   0.198154E+10 1466.94  
Maximum of Months 0.792177E+09 1033.39   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.418155E+10 4375.82 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.379298E+10 4375.82 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.450711E+10 4375.82 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.402577E+10 4375.82 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.434433E+10 4375.82 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.432333E+10 4375.82 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.404678E+10 4375.82 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.450711E+10 4375.82 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.402577E+10 4375.82 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.418155E+10 4375.82 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.413254E+10 4375.82 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.404678E+10 4375.82 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.501156E+11     0.749486E+13    
Minimum of Months 0.379298E+10 4375.82   0.246344E+12 94908.13  
Maximum of Months 0.450711E+10 4375.82   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.154078E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.153333E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.146566E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.177742E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.119284E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 92835788.06
February 0.136985E+10 0.106120E+10 0.307485E+10 0.00 0.00 0.00 0.00 1173983.16 97095714.94
March 0.163685E+10 0.122685E+10 0.352283E+10 0.00 0.00 0.00 0.00 17765040.71 57889427.47
April 0.145243E+10 0.108392E+10 0.328108E+10 0.00 0.00 0.00 0.00 70487126.86 3598592.31
May 0.157338E+10 0.115420E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.153891E+09 1225959.64
June 0.156900E+10 0.114798E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.104434E+09 651768.59
July 0.145680E+10 0.108862E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.131907E+09 242510.18
August 0.163685E+10 0.121752E+10 0.352283E+10 0.00 0.00 0.00 0.00 74750431.20 439329.29
September 0.145243E+10 0.110108E+10 0.327926E+10 0.00 0.00 0.00 0.00 43627017.24 1280876.24
October 0.150991E+10 0.116174E+10 0.339809E+10 0.00 0.00 0.00 0.00 22813638.11 4725393.63
November 0.149516E+10 0.117402E+10 0.332024E+10 0.00 0.00 0.00 0.00 4774899.18 20436125.63
December 0.145680E+10 0.116591E+10 0.334573E+10 0.00 0.00 0.00 0.00 39168.28 84273795.94
                   
Annual Sum or Average 0.181194E+11 0.137759E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.625663E+09 0.364695E+09
Minimum of Months 0.136985E+10 0.106120E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 242510.18
Maximum of Months 0.163685E+10 0.122685E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.153891E+09 97095714.94



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.764375E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 62357929.06
February 0.882782E+09 0.682979E+09 0.198155E+10 0.00 0.00 0.00 0.00 679772.72 65367332.69
March 0.105485E+10 0.789745E+09 0.227025E+10 0.00 0.00 0.00 0.00 11313142.89 37738667.49
April 0.936002E+09 0.699325E+09 0.211446E+10 0.00 0.00 0.00 0.00 46728044.69 2094645.24
May 0.101394E+10 0.746469E+09 0.222976E+10 0.00 0.00 0.00 0.00 0.102033E+09 781939.55
June 0.101113E+10 0.742294E+09 0.218692E+10 0.00 0.00 0.00 0.00 70645429.58 343269.84
July 0.938820E+09 0.702323E+09 0.215670E+10 0.00 0.00 0.00 0.00 90864726.77 99525.03
August 0.105485E+10 0.784517E+09 0.227025E+10 0.00 0.00 0.00 0.00 52645602.01 165381.96
September 0.936002E+09 0.709467E+09 0.211328E+10 0.00 0.00 0.00 0.00 29486653.19 668692.46
October 0.973041E+09 0.745665E+09 0.218986E+10 0.00 0.00 0.00 0.00 14644309.56 3164567.21
November 0.963541E+09 0.755439E+09 0.213969E+10 0.00 0.00 0.00 0.00 3066434.55 13789076.44
December 0.938820E+09 0.747625E+09 0.215612E+10 0.00 0.00 0.00 0.00 19983.27 55392655.17
                   
Annual Sum or Average 0.116768E+11 0.887022E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.422127E+09 0.241964E+09
Minimum of Months 0.882782E+09 0.682979E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 99525.03
Maximum of Months 0.105485E+10 0.789745E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.102033E+09 65367332.69



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.116785E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 97227386.92
February 0.136988E+10 0.104951E+10 0.307490E+10 0.00 0.00 0.00 0.00 871414.26 0.105252E+09
March 0.163688E+10 0.122283E+10 0.352288E+10 0.00 0.00 0.00 0.00 15487704.85 63427324.05
April 0.145246E+10 0.108531E+10 0.328113E+10 0.00 0.00 0.00 0.00 68014243.69 4105131.54
May 0.157341E+10 0.115978E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.152745E+09 1247682.33
June 0.156904E+10 0.115290E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.104280E+09 665340.99
July 0.145684E+10 0.109261E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.131691E+09 238637.37
August 0.163688E+10 0.121960E+10 0.352288E+10 0.00 0.00 0.00 0.00 74291341.26 465240.21
September 0.145246E+10 0.110006E+10 0.327931E+10 0.00 0.00 0.00 0.00 42328186.67 1257065.64
October 0.150994E+10 0.115302E+10 0.339814E+10 0.00 0.00 0.00 0.00 20576022.53 5331997.09
November 0.149520E+10 0.115440E+10 0.332029E+10 0.00 0.00 0.00 0.00 3755160.17 23123237.61
December 0.145684E+10 0.113822E+10 0.334578E+10 0.00 0.00 0.00 0.00 17138.20 91077700.38
                   
Annual Sum or Average 0.181198E+11 0.136961E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.614057E+09 0.393419E+09
Minimum of Months 0.136988E+10 0.104951E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 238637.37
Maximum of Months 0.163688E+10 0.122283E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.152745E+09 0.105252E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.761171E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 67811360.14
February 0.882782E+09 0.679755E+09 0.198154E+10 0.00 0.00 0.00 0.00 585498.94 75310118.86
March 0.105485E+10 0.791821E+09 0.227023E+10 0.00 0.00 0.00 0.00 10199523.63 49538751.56
April 0.936002E+09 0.699843E+09 0.211444E+10 0.00 0.00 0.00 0.00 43347318.29 4908433.61
May 0.101394E+10 0.747200E+09 0.222974E+10 0.00 0.00 0.00 0.00 99123460.64 1212720.45
June 0.101113E+10 0.742235E+09 0.218691E+10 0.00 0.00 0.00 0.00 66611335.74 771423.28
July 0.938820E+09 0.704269E+09 0.215669E+10 0.00 0.00 0.00 0.00 82227989.62 325538.85
August 0.105485E+10 0.787792E+09 0.227023E+10 0.00 0.00 0.00 0.00 44874927.94 767315.92
September 0.936002E+09 0.711323E+09 0.211327E+10 0.00 0.00 0.00 0.00 27650875.25 1593750.49
October 0.973041E+09 0.750330E+09 0.218984E+10 0.00 0.00 0.00 0.00 14034263.67 3987784.29
November 0.963541E+09 0.747485E+09 0.213967E+10 0.00 0.00 0.00 0.00 2579012.42 16260982.54
December 0.938820E+09 0.739528E+09 0.215610E+10 0.00 0.00 0.00 0.00 11544.94 66096259.93
                   
Annual Sum or Average 0.116768E+11 0.886275E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.391246E+09 0.288584E+09
Minimum of Months 0.882782E+09 0.679755E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 325538.85
Maximum of Months 0.105485E+10 0.791821E+09 0.227023E+10 0.00 0.00 0.00 0.00 99123460.64 75310118.86



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.119505E+10 0.339718E+10 0.00 0.00 0.00 0.00 64820.85 0.187772E+09
February 0.136985E+10 0.106222E+10 0.307485E+10 0.00 0.00 0.00 0.00 4814185.63 0.202243E+09
March 0.163685E+10 0.122769E+10 0.352283E+10 0.00 0.00 0.00 0.00 42569536.46 0.132834E+09
April 0.145243E+10 0.108421E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.164833E+09 12021827.71
May 0.157338E+10 0.115539E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.350731E+09 3152443.47
June 0.156900E+10 0.114884E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.237715E+09 2330402.12
July 0.145680E+10 0.108930E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.293630E+09 962929.58
August 0.163685E+10 0.121857E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.168299E+09 1870671.64
September 0.145243E+10 0.110214E+10 0.327926E+10 0.00 0.00 0.00 0.00 97662164.75 3507269.47
October 0.150991E+10 0.116304E+10 0.339809E+10 0.00 0.00 0.00 0.00 53480617.31 11415300.31
November 0.149516E+10 0.117563E+10 0.332024E+10 0.00 0.00 0.00 0.00 13037993.32 42697834.67
December 0.145680E+10 0.116805E+10 0.334573E+10 0.00 0.00 0.00 0.00 1202253.11 0.168719E+09
                   
Annual Sum or Average 0.181194E+11 0.137901E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.142804E+10 0.769527E+09
Minimum of Months 0.136985E+10 0.106222E+10 0.307485E+10 0.00 0.00 0.00 0.00 64820.85 962929.58
Maximum of Months 0.163685E+10 0.122769E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.350731E+09 0.202243E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.764789E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.132286E+09
February 0.649041E+09 0.683231E+09 0.198155E+10 0.00 0.00 0.00 0.00 1692514.49 0.144641E+09
March 0.773965E+09 0.790057E+09 0.227025E+10 0.00 0.00 0.00 0.00 24857394.98 95375393.19
April 0.688021E+09 0.699478E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.104755E+09 9487095.13
May 0.744847E+09 0.746630E+09 0.222976E+10 0.00 0.00 0.00 0.00 0.230735E+09 2272397.77
June 0.742030E+09 0.742404E+09 0.218692E+10 0.00 0.00 0.00 0.00 0.158132E+09 1608367.46
July 0.690839E+09 0.702580E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.195903E+09 648804.78
August 0.773965E+09 0.784739E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.111739E+09 1283508.47
September 0.688021E+09 0.709644E+09 0.211328E+10 0.00 0.00 0.00 0.00 64468074.79 2310273.56
October 0.715730E+09 0.745801E+09 0.218986E+10 0.00 0.00 0.00 0.00 33218077.06 8377805.06
November 0.708685E+09 0.755814E+09 0.213969E+10 0.00 0.00 0.00 0.00 7107490.61 31086896.67
December 0.690839E+09 0.748082E+09 0.215612E+10 0.00 0.00 0.00 0.00 277786.04 0.119800E+09
                   
Annual Sum or Average 0.858171E+10 0.887325E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.932885E+09 0.549177E+09
Minimum of Months 0.649041E+09 0.683231E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 648804.78
Maximum of Months 0.773965E+09 0.790057E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.230735E+09 0.144641E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.117096E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.222136E+09
February 0.136988E+10 0.104998E+10 0.307490E+10 0.00 0.00 0.00 0.00 1853761.76 0.242305E+09
March 0.163688E+10 0.122342E+10 0.352288E+10 0.00 0.00 0.00 0.00 34625541.47 0.153790E+09
April 0.145246E+10 0.108567E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.157081E+09 14095750.48
May 0.157341E+10 0.116037E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.348908E+09 3264974.59
June 0.156904E+10 0.115367E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.237967E+09 2283710.29
July 0.145684E+10 0.109362E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.293546E+09 966210.90
August 0.163688E+10 0.122041E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.166349E+09 1957324.97
September 0.145246E+10 0.110069E+10 0.327931E+10 0.00 0.00 0.00 0.00 94238383.17 3823270.13
October 0.150994E+10 0.115247E+10 0.339814E+10 0.00 0.00 0.00 0.00 46767086.28 13610759.89
November 0.149520E+10 0.115511E+10 0.332029E+10 0.00 0.00 0.00 0.00 8332042.23 54160856.27
December 0.145684E+10 0.113972E+10 0.334578E+10 0.00 0.00 0.00 0.00 29183.99 0.208520E+09
                   
Annual Sum or Average 0.181198E+11 0.137061E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.138970E+10 0.920913E+09
Minimum of Months 0.136988E+10 0.104998E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 966210.90
Maximum of Months 0.163688E+10 0.122342E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.348908E+09 0.242305E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.761629E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.135883E+09
February 0.882782E+09 0.680120E+09 0.198154E+10 0.00 0.00 0.00 0.00 1506527.16 0.149110E+09
March 0.105485E+10 0.792152E+09 0.227023E+10 0.00 0.00 0.00 0.00 24658184.96 0.103311E+09
April 0.936002E+09 0.700030E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.103708E+09 10961728.85
May 0.101394E+10 0.747333E+09 0.222974E+10 0.00 0.00 0.00 0.00 0.227791E+09 2878043.79
June 0.101113E+10 0.742337E+09 0.218691E+10 0.00 0.00 0.00 0.00 0.154865E+09 2059451.44
July 0.938820E+09 0.704619E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.191205E+09 841195.52
August 0.105485E+10 0.788011E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.108301E+09 1639994.88
September 0.936002E+09 0.711551E+09 0.211327E+10 0.00 0.00 0.00 0.00 62798007.48 3063546.41
October 0.973041E+09 0.750650E+09 0.218984E+10 0.00 0.00 0.00 0.00 33237166.21 8497395.76
November 0.963541E+09 0.747778E+09 0.213967E+10 0.00 0.00 0.00 0.00 6883757.07 31416263.78
December 0.938820E+09 0.739903E+09 0.215610E+10 0.00 0.00 0.00 0.00 109025.09 0.123379E+09
                   
Annual Sum or Average 0.116768E+11 0.886611E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.915064E+09 0.573041E+09
Minimum of Months 0.882782E+09 0.680120E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 841195.52
Maximum of Months 0.105485E+10 0.792152E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.227791E+09 0.149110E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.119506E+10 0.339718E+10 0.00 0.00 0.00 0.00 352890.87 0.192789E+09
February 0.136985E+10 0.106222E+10 0.307485E+10 0.00 0.00 0.00 0.00 7891049.19 0.221903E+09
March 0.163685E+10 0.122769E+10 0.352283E+10 0.00 0.00 0.00 0.00 51205953.38 0.158233E+09
April 0.145243E+10 0.108422E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.197552E+09 15029560.82
May 0.157338E+10 0.115539E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.425611E+09 4120380.71
June 0.156900E+10 0.114881E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.288062E+09 3197554.43
July 0.145680E+10 0.108928E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.355286E+09 1237690.49
August 0.163685E+10 0.121849E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.202648E+09 2676586.84
September 0.145243E+10 0.110213E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.118105E+09 4598113.20
October 0.150991E+10 0.116303E+10 0.339809E+10 0.00 0.00 0.00 0.00 65516618.78 13720548.06
November 0.149516E+10 0.117563E+10 0.332024E+10 0.00 0.00 0.00 0.00 17400867.44 47243361.42
December 0.145680E+10 0.116806E+10 0.334573E+10 0.00 0.00 0.00 0.00 3029373.38 0.177291E+09
                   
Annual Sum or Average 0.181194E+11 0.137900E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.173266E+10 0.842040E+09
Minimum of Months 0.136985E+10 0.106222E+10 0.307485E+10 0.00 0.00 0.00 0.00 352890.87 1237690.49
Maximum of Months 0.163685E+10 0.122769E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.425611E+09 0.221903E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.764799E+09 0.218927E+10 0.00 0.00 0.00 0.00 47033.31 0.139881E+09
February 0.882782E+09 0.683233E+09 0.198155E+10 0.00 0.00 0.00 0.00 2489018.56 0.163635E+09
March 0.105485E+10 0.790061E+09 0.227025E+10 0.00 0.00 0.00 0.00 29466452.15 0.115963E+09
April 0.936002E+09 0.699481E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.126171E+09 12213615.60
May 0.101394E+10 0.746628E+09 0.222976E+10 0.00 0.00 0.00 0.00 0.279740E+09 2962637.08
June 0.101113E+10 0.742399E+09 0.218692E+10 0.00 0.00 0.00 0.00 0.191368E+09 2204359.90
July 0.938820E+09 0.702572E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.236839E+09 834132.99
August 0.105485E+10 0.784732E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.134363E+09 1836922.35
September 0.936002E+09 0.709641E+09 0.211328E+10 0.00 0.00 0.00 0.00 77964091.80 3046843.24
October 0.973041E+09 0.745800E+09 0.218986E+10 0.00 0.00 0.00 0.00 40238524.50 10241344.06
November 0.963541E+09 0.755818E+09 0.213969E+10 0.00 0.00 0.00 0.00 8937024.37 35585548.90
December 0.938820E+09 0.748091E+09 0.215612E+10 0.00 0.00 0.00 0.00 928052.16 0.129814E+09
                   
Annual Sum or Average 0.116768E+11 0.887325E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.112855E+10 0.618219E+09
Minimum of Months 0.882782E+09 0.683233E+09 0.198155E+10 0.00 0.00 0.00 0.00 47033.31 834132.99
Maximum of Months 0.105485E+10 0.790061E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.279740E+09 0.163635E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.117097E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.246102E+09
February 0.136988E+10 0.104998E+10 0.307490E+10 0.00 0.00 0.00 0.00 2076426.25 0.280279E+09
March 0.163688E+10 0.122342E+10 0.352288E+10 0.00 0.00 0.00 0.00 41550320.50 0.187673E+09
April 0.145246E+10 0.108567E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.189893E+09 18035218.08
May 0.157341E+10 0.116036E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.423484E+09 4274836.71
June 0.156904E+10 0.115365E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.288202E+09 3151178.91
July 0.145684E+10 0.109360E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.355187E+09 1241659.69
August 0.163688E+10 0.122039E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.200356E+09 2796595.73
September 0.145246E+10 0.110068E+10 0.327931E+10 0.00 0.00 0.00 0.00 0.114175E+09 5087786.03
October 0.150994E+10 0.115247E+10 0.339814E+10 0.00 0.00 0.00 0.00 56957241.41 16803839.49
November 0.149520E+10 0.115512E+10 0.332029E+10 0.00 0.00 0.00 0.00 9928568.14 64086049.78
December 0.145684E+10 0.113975E+10 0.334578E+10 0.00 0.00 0.00 0.00 24857.92 0.234898E+09
                   
Annual Sum or Average 0.181198E+11 0.137061E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.168183E+10 0.106443E+10
Minimum of Months 0.136988E+10 0.104998E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 1241659.69
Maximum of Months 0.163688E+10 0.122342E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.423484E+09 0.280279E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.761640E+09 0.218926E+10 0.00 0.00 0.00 0.00 1950.73 0.148301E+09
February 0.882782E+09 0.680124E+09 0.198154E+10 0.00 0.00 0.00 0.00 2092498.26 0.169680E+09
March 0.105485E+10 0.792177E+09 0.227023E+10 0.00 0.00 0.00 0.00 30019679.38 0.125416E+09
April 0.936002E+09 0.700034E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.126162E+09 13843424.73
May 0.101394E+10 0.747331E+09 0.222974E+10 0.00 0.00 0.00 0.00 0.278594E+09 3559189.85
June 0.101113E+10 0.742331E+09 0.218691E+10 0.00 0.00 0.00 0.00 0.189321E+09 2630509.08
July 0.938820E+09 0.704606E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.233676E+09 1076535.44
August 0.105485E+10 0.787999E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.131958E+09 2262143.05
September 0.936002E+09 0.711546E+09 0.211327E+10 0.00 0.00 0.00 0.00 76842513.09 3900138.61
October 0.973041E+09 0.750648E+09 0.218984E+10 0.00 0.00 0.00 0.00 41060801.47 10366299.94
November 0.963541E+09 0.747830E+09 0.213967E+10 0.00 0.00 0.00 0.00 8800913.87 36000785.83
December 0.938820E+09 0.739913E+09 0.215610E+10 0.00 0.00 0.00 0.00 488928.74 0.136529E+09
                   
Annual Sum or Average 0.116768E+11 0.886618E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.111902E+10 0.653565E+09
Minimum of Months 0.882782E+09 0.680124E+09 0.198154E+10 0.00 0.00 0.00 0.00 1950.73 1076535.44
Maximum of Months 0.105485E+10 0.792177E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.278594E+09 0.169680E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.418155E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.379298E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.450711E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.402577E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.434433E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.432333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.404678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.450711E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.402577E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.418155E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.413254E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.404678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.501156E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.379298E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.450711E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.201667E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 979256.55 0.213759E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29532153.53 0.130767E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131917E+09 10073041.13
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.295989E+09 2768015.02
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.200185E+09 1465080.19
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.251755E+09 691646.62
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.138041E+09 1099160.83
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 80334148.40 1933099.43
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40694974.18 11178440.71
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6779283.58 46359161.63
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.186135E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.117621E+10 0.807896E+09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 691646.62
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.295989E+09 0.213759E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.342726E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2589018.24 0.365281E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54664202.73 0.230371E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.241981E+09 19473278.86
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.535562E+09 4837159.51
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.360953E+09 2747210.98
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.457157E+09 1298781.76
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.252634E+09 2127542.90
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.143723E+09 3396975.03
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 73444009.63 20155926.12
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13351511.20 79058423.84
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 147916.91 0.311961E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.213621E+10 0.138344E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1298781.76
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.535562E+09 0.365281E+09



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.328292E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 553077.92 0.370562E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44501090.97 0.243500E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.237085E+09 19344084.34
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.566315E+09 5523435.51
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.385388E+09 3468897.93
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.476027E+09 1352881.78
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.261675E+09 3588642.47
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.145602E+09 4392406.02
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 69805158.59 19783849.20
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9677902.89 77401775.42
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 428371.18 0.297752E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.219706E+10 0.137496E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1352881.78
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.566315E+09 0.370562E+09



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 15519.45 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 15519.45 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 15519.45 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 15519.45 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 15519.45 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 15519.45 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 15519.45 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 15519.45 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 15519.45 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 15519.45 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 15519.45 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 15519.45 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1518.11 18-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 237.11 15-JAN-17:00
February 2010.79 01-FEB-10:09 1493.71 10-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 38.43 19-FEB-15:00 317.06 09-FEB-22:10
March 2010.79 01-MAR-10:09 1506.04 14-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 183.94 26-MAR-14:10 681.74 24-MAR-24:00
April 2010.79 03-APR-09:09 1075.02 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 343.34 15-APR-17:02 102.10 22-APR-18:07
May 2010.79 01-MAY-09:09 1249.63 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 612.56 28-MAY-14:55 49.14 15-MAY-02:47
June 2010.79 01-JUN-09:09 1240.40 23-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 282.12 03-JUN-17:02 50.10 18-JUN-04:30
July 2010.79 03-JUL-09:09 1459.75 26-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 298.30 02-JUL-11:45 38.93 19-JUL-02:20
August 2010.79 01-AUG-09:09 1495.67 16-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 194.48 06-AUG-14:25 45.48 15-AUG-23:50
September 2010.79 01-SEP-09:09 1531.62 08-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 170.10 24-SEP-14:45 27.27 08-SEP-22:10
October 2010.79 02-OCT-09:09 1595.59 11-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 194.16 15-OCT-12:40 96.62 12-OCT-02:30
November 2010.79 01-NOV-09:09 1570.33 27-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 62.34 12-NOV-14:10 158.89 28-NOV-05:20
December 2010.79 01-DEC-10:09 1578.40 29-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 8.55 24-DEC-14:23 367.40 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   27.27  
Maximum of Months 2010.79   1595.59   2276.32   0.00 0.00 0.00 0.00 612.56   681.74  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 973.30 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 154.78 15-JAN-17:00
February 1295.83 01-FEB-10:09 967.62 09-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 19.37 19-FEB-15:00 202.69 09-FEB-22:10
March 1295.83 01-MAR-10:09 909.26 14-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 116.34 26-MAR-14:50 449.46 24-MAR-24:00
April 1295.83 03-APR-09:09 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 229.62 15-APR-17:02 62.79 22-APR-18:07
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 409.44 28-MAY-14:53 33.89 15-MAY-02:47
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 193.13 17-JUN-20:50 29.48 18-JUN-04:30
July 1295.83 03-JUL-09:09 917.91 26-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 199.64 02-JUL-11:45 21.21 19-JUL-02:20
August 1295.83 01-AUG-09:09 943.58 16-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 131.22 06-AUG-14:00 24.23 15-AUG-23:50
September 1295.83 01-SEP-09:09 968.41 07-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 114.21 24-SEP-14:45 16.11 08-SEP-22:20
October 1295.83 02-OCT-09:09 1016.67 11-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 122.27 15-OCT-13:10 60.85 12-OCT-02:30
November 1295.83 01-NOV-09:09 1029.58 27-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 39.56 12-NOV-14:10 102.53 28-NOV-05:20
December 1295.83 01-DEC-10:09 1023.86 29-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 4.19 24-DEC-14:23 231.12 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   16.11  
Maximum of Months 1295.83   1029.58   1466.95   0.00 0.00 0.00 0.00 409.44   449.46  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1473.40 18-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 243.74 22-JAN-14:43
February 2010.83 01-FEB-10:09 1456.78 10-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 12.62 21-FEB-15:00 313.14 09-FEB-22:10
March 2010.83 01-MAR-10:09 1492.56 14-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 148.99 26-MAR-15:24 739.52 24-MAR-24:00
April 2010.83 03-APR-09:09 1075.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 338.69 15-APR-17:08 107.75 22-APR-18:07
May 2010.83 01-MAY-09:09 1287.72 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 610.63 28-MAY-14:53 53.36 15-MAY-02:47
June 2010.83 01-JUN-09:09 1296.72 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 284.13 03-JUN-17:02 50.88 18-JUN-04:30
July 2010.83 03-JUL-09:09 1476.24 26-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 297.66 02-JUL-11:45 38.66 19-JUL-02:20
August 2010.83 01-AUG-09:09 1502.97 16-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 193.59 06-AUG-13:44 46.93 15-AUG-23:50
September 2010.83 01-SEP-09:09 1529.49 08-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 162.24 24-SEP-14:45 26.51 08-SEP-22:10
October 2010.83 02-OCT-09:09 1589.31 11-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 164.10 15-OCT-12:50 96.66 12-OCT-02:30
November 2010.83 01-NOV-09:09 1476.84 27-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 34.57 12-NOV-14:45 169.51 29-NOV-24:00
December 2010.83 01-DEC-10:09 1537.17 29-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 2.91 28-DEC-14:00 405.70 31-DEC-14:50
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   26.51  
Maximum of Months 2010.83   1589.31   2276.35   0.00 0.00 0.00 0.00 610.63   739.52  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 985.07 18-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 170.69 15-JAN-17:00
February 1295.83 01-FEB-10:09 972.30 10-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 8.43 21-FEB-15:00 233.37 09-FEB-22:20
March 1295.83 01-MAR-10:09 995.66 14-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 100.10 26-MAR-13:28 611.67 24-MAR-24:00
April 1295.83 03-APR-09:09 858.71 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 220.39 15-APR-17:10 115.32 22-APR-18:07
May 1295.83 01-MAY-09:09 866.74 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 402.95 28-MAY-14:14 48.50 15-MAY-02:47
June 1295.83 01-JUN-09:09 868.08 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 190.14 17-JUN-20:30 49.00 18-JUN-04:30
July 1295.83 03-JUL-09:09 961.95 26-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 201.66 02-JUL-11:45 39.33 19-JUL-02:20
August 1295.83 01-AUG-09:09 979.52 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 126.06 06-AUG-13:44 51.80 15-AUG-23:50
September 1295.83 01-SEP-09:09 997.33 08-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 110.47 24-SEP-14:05 26.38 08-SEP-22:20
October 1295.83 02-OCT-09:09 1032.79 11-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 120.22 15-OCT-12:40 79.49 12-OCT-02:30
November 1295.83 01-NOV-09:09 959.54 03-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 24.40 12-NOV-14:05 127.51 29-NOV-24:00
December 1295.83 01-DEC-10:09 977.42 29-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 1.95 28-DEC-14:00 292.60 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   858.71   1466.94   0.00 0.00 0.00 0.00 0.00   26.38  
Maximum of Months 1295.83   1032.79   1466.94   0.00 0.00 0.00 0.00 402.95   611.67  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1524.72 18-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 17.78 08-JAN-14:50 478.18 15-JAN-17:00
February 2010.79 01-FEB-10:09 1501.05 10-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 162.37 19-FEB-14:53 676.13 09-FEB-22:10
March 2010.79 01-MAR-10:09 1513.20 14-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 484.65 26-MAR-14:32 1334.55 24-MAR-24:00
April 2010.79 03-APR-09:09 1075.02 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 821.08 15-APR-17:02 217.07 22-APR-18:03
May 2010.79 01-MAY-09:09 1264.06 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 1401.00 28-MAY-14:43 126.85 15-MAY-03:00
June 2010.79 01-JUN-09:09 1255.10 23-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 660.26 03-JUN-17:02 120.31 18-JUN-04:55
July 2010.79 03-JUL-09:09 1468.23 26-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 688.81 02-JUL-11:56 105.36 19-JUL-02:53
August 2010.79 01-AUG-09:09 1503.11 16-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 456.61 06-AUG-14:00 123.16 15-AUG-24:00
September 2010.79 01-SEP-09:09 1538.01 08-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 391.39 24-SEP-14:45 54.10 08-SEP-22:10
October 2010.79 02-OCT-09:09 1600.11 11-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 454.56 15-OCT-12:00 211.02 12-OCT-02:55
November 2010.79 01-NOV-09:09 1575.52 27-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 177.06 12-NOV-14:00 340.37 28-NOV-04:55
December 2010.79 01-DEC-10:09 1583.38 29-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 111.12 24-DEC-14:10 731.97 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 17.78   54.10  
Maximum of Months 2010.79   1600.11   2276.32   0.00 0.00 0.00 0.00 1401.00   1334.55  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 974.56 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 318.19 15-JAN-17:00
February 1239.33 01-FEB-08:09 968.84 09-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 60.08 19-FEB-14:55 438.69 09-FEB-22:10
March 1239.33 01-MAR-08:09 911.74 14-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 268.87 26-MAR-15:00 948.50 24-MAR-24:00
April 1239.33 03-APR-07:10 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 530.81 15-APR-17:02 164.91 22-APR-18:03
May 1239.33 01-MAY-07:10 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 936.48 28-MAY-14:43 94.28 15-MAY-03:00
June 1239.33 01-JUN-07:10 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 439.16 03-JUN-17:02 80.78 18-JUN-04:55
July 1239.33 03-JUL-07:10 921.23 26-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 461.65 02-JUL-11:56 69.72 19-JUL-02:53
August 1239.33 01-AUG-07:10 945.96 16-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 303.69 06-AUG-14:25 84.76 15-AUG-24:00
September 1239.33 01-SEP-07:10 970.43 08-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 261.39 24-SEP-14:45 35.03 08-SEP-22:20
October 1239.33 02-OCT-07:10 1017.83 11-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 290.82 15-OCT-12:55 141.45 12-OCT-02:55
November 1239.33 01-NOV-07:10 1030.46 27-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 91.30 12-NOV-14:40 234.70 28-NOV-04:55
December 1239.33 01-DEC-08:09 1024.69 29-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 42.20 24-DEC-14:10 483.34 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   35.03  
Maximum of Months 1239.33   1030.46   1466.95   0.00 0.00 0.00 0.00 936.48   948.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1483.05 18-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 584.00 22-JAN-14:00
February 2010.83 01-FEB-10:09 1465.43 10-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 28.20 21-FEB-15:00 686.86 09-FEB-22:10
March 2010.83 01-MAR-10:09 1500.25 14-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 346.27 26-MAR-14:55 1517.57 24-MAR-24:00
April 2010.83 03-APR-09:09 1075.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 779.22 15-APR-17:10 243.00 22-APR-18:03
May 2010.83 01-MAY-09:09 1300.75 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 1404.11 28-MAY-14:43 135.64 15-MAY-03:00
June 2010.83 01-JUN-09:09 1309.39 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 666.93 03-JUN-17:02 119.23 18-JUN-04:55
July 2010.83 03-JUL-09:09 1484.11 26-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 687.64 02-JUL-11:56 105.06 19-JUL-02:53
August 2010.83 01-AUG-09:09 1510.13 16-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 449.19 06-AUG-14:25 126.44 15-AUG-24:00
September 2010.83 01-SEP-09:09 1535.96 08-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 377.33 24-SEP-14:45 54.73 08-SEP-22:10
October 2010.83 02-OCT-09:09 1594.09 11-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 379.45 15-OCT-13:00 217.61 12-OCT-02:55
November 2010.83 01-NOV-09:09 1485.33 27-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 70.74 13-NOV-14:00 387.58 28-NOV-04:55
December 2010.83 01-DEC-10:09 1543.67 29-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 5.58 28-DEC-14:00 943.65 31-DEC-14:25
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   54.73  
Maximum of Months 2010.83   1594.09   2276.35   0.00 0.00 0.00 0.00 1404.11   1517.57  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 986.19 18-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 332.45 15-JAN-17:00
February 1295.83 01-FEB-10:09 973.47 10-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 32.12 19-FEB-14:13 456.48 09-FEB-22:10
March 1295.83 01-MAR-10:09 996.62 14-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 267.60 26-MAR-13:00 1035.64 24-MAR-24:00
April 1295.83 03-APR-09:09 861.42 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 522.04 15-APR-17:07 171.38 22-APR-18:00
May 1295.83 01-MAY-09:09 868.65 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 933.25 28-MAY-14:43 117.88 15-MAY-03:00
June 1295.83 01-JUN-09:09 869.98 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 433.73 17-JUN-20:30 95.58 18-JUN-03:55
July 1295.83 03-JUL-09:09 963.17 26-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 464.21 02-JUL-11:56 75.34 19-JUL-02:53
August 1295.83 01-AUG-09:09 980.60 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 299.77 06-AUG-13:46 92.57 15-AUG-24:00
September 1295.83 01-SEP-09:09 998.29 08-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 255.31 24-SEP-14:05 39.79 08-SEP-22:20
October 1295.83 02-OCT-09:09 1033.49 11-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 297.02 15-OCT-12:00 147.75 12-OCT-02:55
November 1295.83 01-NOV-09:09 961.41 03-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 81.91 12-NOV-13:00 245.13 28-NOV-04:55
December 1295.83 01-DEC-10:09 979.00 29-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 24.78 24-DEC-13:53 505.53 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   861.42   1466.94   0.00 0.00 0.00 0.00 0.00   39.79  
Maximum of Months 1295.83   1033.49   1466.94   0.00 0.00 0.00 0.00 933.25   1035.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1524.51 18-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 57.95 08-JAN-14:50 503.36 15-JAN-17:00
February 2010.79 01-FEB-10:09 1500.81 10-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 219.93 19-FEB-15:10 761.15 09-FEB-22:10
March 2010.79 01-MAR-10:09 1513.02 14-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 578.40 26-MAR-14:32 1544.29 24-MAR-24:00
April 2010.79 03-APR-09:09 1075.02 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 970.02 15-APR-17:02 253.26 22-APR-18:03
May 2010.79 01-MAY-09:09 1263.67 24-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 1720.61 28-MAY-14:58 159.96 15-MAY-02:30
June 2010.79 01-JUN-09:09 1254.71 23-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 783.55 17-JUN-20:30 162.68 18-JUN-03:55
July 2010.79 03-JUL-09:09 1467.96 26-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 853.72 02-JUL-11:56 129.90 19-JUL-02:53
August 2010.79 01-AUG-09:09 1502.87 16-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 558.98 06-AUG-14:25 169.16 15-AUG-24:00
September 2010.79 01-SEP-09:09 1537.80 08-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 470.81 24-SEP-14:56 64.54 08-SEP-22:10
October 2010.79 02-OCT-09:09 1599.95 11-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 565.66 15-OCT-12:00 248.70 12-OCT-02:55
November 2010.79 01-NOV-09:09 1575.44 27-NOV-16:00 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 227.32 12-NOV-14:00 370.67 28-NOV-04:55
December 2010.79 01-DEC-10:09 1583.24 29-DEC-16:00 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 226.60 24-DEC-14:00 809.52 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 57.95   64.54  
Maximum of Months 2010.79   1599.95   2276.32   0.00 0.00 0.00 0.00 1720.61   1544.29  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 974.44 17-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 17.31 08-JAN-14:50 335.39 15-JAN-17:00
February 1295.83 01-FEB-10:09 968.69 09-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 91.66 19-FEB-15:10 497.32 09-FEB-22:10
March 1295.83 01-MAR-10:09 911.68 14-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 310.13 26-MAR-15:00 1113.00 24-MAR-24:00
April 1295.83 03-APR-09:09 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 646.75 15-APR-17:08 196.19 22-APR-18:03
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 1147.18 28-MAY-14:55 117.89 15-MAY-02:30
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 529.05 17-JUN-20:30 109.86 18-JUN-03:55
July 1295.83 03-JUL-09:09 921.10 26-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 572.13 02-JUL-11:56 85.96 19-JUL-02:53
August 1295.83 01-AUG-09:09 945.84 16-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 376.40 06-AUG-14:25 116.49 15-AUG-24:00
September 1295.83 01-SEP-09:09 970.32 08-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 317.87 24-SEP-14:56 41.62 08-SEP-22:20
October 1295.83 02-OCT-09:09 1017.75 11-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 338.07 15-OCT-12:40 166.83 12-OCT-02:55
November 1295.83 01-NOV-09:09 1030.41 27-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 120.20 12-NOV-14:40 260.45 28-NOV-04:55
December 1295.83 01-DEC-10:09 1024.60 29-DEC-16:00 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 106.65 24-DEC-14:00 536.98 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 17.31   41.62  
Maximum of Months 1295.83   1030.41   1466.95   0.00 0.00 0.00 0.00 1147.18   1113.00  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1482.85 18-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 661.28 22-JAN-14:50
February 2010.83 01-FEB-10:09 1465.20 10-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 33.26 21-FEB-15:00 779.59 09-FEB-22:10
March 2010.83 01-MAR-10:09 1500.08 14-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 421.21 26-MAR-14:55 1796.50 24-MAR-24:00
April 2010.83 03-APR-09:09 1075.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 967.21 15-APR-17:08 286.71 22-APR-18:03
May 2010.83 01-MAY-09:09 1300.36 24-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 1720.61 28-MAY-14:57 169.88 15-MAY-02:30
June 2010.83 01-JUN-09:09 1309.00 23-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 790.96 03-JUN-17:02 161.58 18-JUN-04:43
July 2010.83 03-JUL-09:09 1483.84 26-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 851.99 02-JUL-11:56 129.51 19-JUL-02:53
August 2010.83 01-AUG-09:09 1509.89 16-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 552.82 06-AUG-13:46 173.56 15-AUG-24:00
September 2010.83 01-SEP-09:09 1535.75 08-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 461.14 24-SEP-14:15 65.50 08-SEP-22:10
October 2010.83 02-OCT-09:09 1593.94 11-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 460.17 15-OCT-12:50 257.81 12-OCT-02:55
November 2010.83 01-NOV-09:09 1485.29 27-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 96.84 12-NOV-13:55 440.10 28-NOV-04:55
December 2010.83 01-DEC-10:09 1543.55 29-DEC-16:00 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 5.41 28-DEC-14:00 1073.97 31-DEC-14:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   65.50  
Maximum of Months 2010.83   1593.94   2276.35   0.00 0.00 0.00 0.00 1720.61   1796.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 986.06 18-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 2.27 08-JAN-14:10 364.15 15-JAN-17:00
February 1295.83 01-FEB-10:09 973.33 10-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 59.96 19-FEB-14:02 518.08 09-FEB-22:10
March 1295.83 01-MAR-10:09 996.51 14-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 331.98 26-MAR-13:00 1224.17 24-MAR-24:00
April 1295.83 03-APR-09:09 861.42 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 642.52 15-APR-17:07 201.02 22-APR-18:00
May 1295.83 01-MAY-09:09 868.41 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 1147.95 28-MAY-14:55 139.43 15-MAY-02:30
June 1295.83 01-JUN-09:09 869.75 23-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 537.67 17-JUN-20:30 125.42 18-JUN-03:55
July 1295.83 03-JUL-09:09 963.00 26-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 577.20 02-JUL-11:56 92.91 19-JUL-02:53
August 1295.83 01-AUG-09:09 980.46 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 373.23 06-AUG-13:46 125.33 15-AUG-24:00
September 1295.83 01-SEP-09:09 998.16 08-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 312.79 24-SEP-14:54 46.89 08-SEP-22:20
October 1295.83 02-OCT-09:09 1033.39 11-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 373.44 15-OCT-11:50 175.17 12-OCT-02:55
November 1295.83 01-NOV-09:09 961.38 03-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 112.53 12-NOV-13:00 276.18 28-NOV-04:55
December 1295.83 01-DEC-10:09 978.95 29-DEC-16:00 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 74.39 24-DEC-14:00 568.10 29-DEC-24:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   861.42   1466.94   0.00 0.00 0.00 0.00 2.27   46.89  
Maximum of Months 1295.83   1033.39   1466.94   0.00 0.00 0.00 0.00 1147.95   1224.17  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4375.82 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4375.82 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4375.82 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4375.82 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4375.82 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4375.82 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4375.82 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4375.82 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4375.82 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4375.82 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4375.82 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4375.82 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4375.82   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4375.82   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 490.85 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.68 19-FEB-14:53 699.93 09-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 350.27 26-MAR-15:00 1444.24 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 710.40 15-APR-17:02 204.39 22-APR-18:13
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1226.35 28-MAY-14:41 85.76 13-MAY-03:04
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 573.04 03-JUN-17:02 92.92 18-JUN-04:35
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 596.45 02-JUL-12:00 75.85 19-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 385.55 06-AUG-14:10 80.97 15-AUG-23:57
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 335.42 24-SEP-13:52 38.09 19-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 374.86 15-OCT-12:50 186.52 12-OCT-02:38
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89.54 12-NOV-13:52 354.31 28-NOV-04:55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 774.49 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   38.09  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1226.35   1444.24  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 828.72 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 117.79 19-FEB-15:00 1223.23 09-FEB-22:10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 689.47 26-MAR-14:42 2459.77 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1306.21 15-APR-17:02 354.95 22-APR-18:20
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2218.51 28-MAY-15:00 151.91 13-MAY-03:04
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1041.10 03-JUN-17:02 164.76 18-JUN-04:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1113.62 02-JUL-11:40 141.39 19-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 739.68 06-AUG-14:10 150.04 15-AUG-24:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 608.99 24-SEP-13:52 67.64 19-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 674.31 15-OCT-12:40 324.99 12-OCT-03:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.91 12-NOV-14:20 609.93 28-NOV-05:07
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.67 24-DEC-14:30 1320.04 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   67.64  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2218.51   2459.77  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 808.05 15-JAN-17:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 29.24 19-FEB-14:53 1249.57 09-FEB-22:03
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 496.26 26-MAR-14:40 2424.89 24-MAR-24:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1323.38 15-APR-17:02 308.27 22-APR-18:40
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2149.93 28-MAY-15:00 174.14 13-MAY-03:06
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1092.70 03-JUN-17:10 200.68 18-JUN-04:55
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1040.16 02-JUL-10:52 153.70 19-JUL-02:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 709.87 06-AUG-08:52 222.44 15-AUG-24:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 538.04 24-SEP-14:00 67.12 19-SEP-05:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 606.70 15-OCT-12:02 347.36 12-OCT-02:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.95 12-NOV-14:20 565.77 28-NOV-04:55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86.59 24-DEC-14:10 1263.55 29-DEC-24:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   67.12  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2149.93   2424.89  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 97223.56 02-JAN-04:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
February 100508.93 06-FEB-04:03 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
March 95460.67 06-MAR-04:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
April 95547.30 28-APR-03:02 0.00 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
May 94628.54 29-MAY-17:30 0.00 7760.04 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
June 91765.23 05-JUN-03:02 0.00 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
July 85621.88 04-JUL-19:50 0.00 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
August 83004.63 22-AUG-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
September 84697.23 26-SEP-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 94666.66 29-OCT-13:32 5385.68 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
November 99215.18 12-NOV-13:52 5385.68 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
December 96467.72 26-DEC-04:03 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 83004.63   0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 100508.93   5385.68 7760.04 121117.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 94247.69 02-JAN-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
February 93630.41 21-FEB-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
March 89662.57 21-MAR-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
April 86826.26 17-APR-05:05 9673.43 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
May 85761.14 01-MAY-05:02 9673.43 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
June 85216.57 12-JUN-05:02 9673.43 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
July 85751.65 10-JUL-05:05 9673.43 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
August 84674.83 07-AUG-05:01 11285.67 10840.77 56400.06 0.00 0.00 0.00 0.00 0.00 0.00
September 82935.09 11-SEP-03:02 0.00 4646.04 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
October 90591.37 31-OCT-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 93854.23 24-NOV-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 93980.08 04-DEC-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 82935.09   0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 94247.69   11285.67 10840.77 56400.06 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 80680.75 17-JAN-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
February 84600.87 27-FEB-04:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 81591.21 23-MAR-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 79594.66 13-APR-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 75644.68 25-MAY-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 77374.93 21-JUN-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 77726.46 28-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 78401.83 17-AUG-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 80308.33 06-SEP-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 82936.58 24-OCT-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 81772.99 17-NOV-05:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
December 80223.21 27-DEC-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 75644.68   0.00 3871.70 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 84600.87   8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 34277.53 26-JAN-16:20 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 79357.48 23-FEB-06:03 6448.95 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
March 83715.24 15-MAR-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
April 83283.83 17-APR-05:03 9673.43 9292.09 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
May 82830.27 25-MAY-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 86993.69 12-JUN-05:02 9673.43 9292.09 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
July 83995.34 28-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 84138.26 17-AUG-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 85558.99 11-SEP-03:02 0.00 4646.04 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
October 84715.45 11-OCT-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 81204.55 09-NOV-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 69665.87 29-DEC-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 34277.53   0.00 3871.70 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86993.69   15316.26 13937.56 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4968.19 26-JAN-14:10 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 9.00
February 6682.53 23-FEB-14:30 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 5.79 0.00
March 13821.38 14-MAR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 3.61
April 19444.80 16-APR-15:41 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 45.09 0.00
May 19446.64 07-MAY-16:31 809.73 477.81 6070.18 0.00 0.00 0.00 0.00 217.26 0.00
June 19512.69 11-JUN-17:02 0.00 358.36 4552.64 0.00 0.00 0.00 0.00 99.01 0.00
July 20867.56 02-JUL-17:01 0.00 537.53 6828.95 0.00 0.00 0.00 0.00 163.31 0.00
August 18961.79 06-AUG-15:42 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 166.87 0.00
September 19212.21 24-SEP-14:42 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 156.15 0.00
October 17364.69 01-OCT-15:51 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 58.48 0.00
November 8997.97 06-NOV-06:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 0.00
December 5933.59 26-DEC-14:10 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 1.11
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4968.19   0.00 358.36 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20867.56   2010.79 1075.02 6828.95 0.00 0.00 0.00 0.00 217.26 9.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4453.37 26-JAN-10:20 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 15.32
February 7146.13 21-FEB-09:40 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 10.43
March 13235.84 12-MAR-09:53 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 4.14
April 16685.30 16-APR-09:02 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 5.50 0.00
May 16990.34 07-MAY-09:11 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 97.54 0.00
June 15610.86 11-JUN-09:42 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 51.43 0.00
July 16213.54 02-JUL-15:41 587.05 346.41 4400.84 0.00 0.00 0.00 0.00 114.14 0.00
August 12964.53 07-AUG-05:01 913.19 877.19 4563.83 0.00 0.00 0.00 0.00 5.82 0.00
September 15173.92 24-SEP-14:42 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 102.72 0.00
October 15922.26 01-OCT-09:52 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 10.92 0.00
November 6736.27 13-NOV-09:40 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 6.67
December 4963.54 01-DEC-09:40 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 7.48
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4453.37   260.91 153.96 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16990.34   1295.83 877.19 4563.83 0.00 0.00 0.00 0.00 114.14 15.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 14671.94 08-JAN-14:23 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 39.61
February 20491.31 19-FEB-14:13 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 49.56
March 21190.03 12-MAR-13:12 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 15.85 0.00
April 20457.00 16-APR-15:01 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 60.51 0.00
May 19971.29 07-MAY-15:11 809.75 477.82 6070.27 0.00 0.00 0.00 0.00 243.82 0.00
June 19798.19 11-JUN-16:22 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 110.31 0.00
July 21177.55 02-JUL-16:21 910.97 537.55 6829.06 0.00 0.00 0.00 0.00 170.31 0.00
August 20003.67 06-AUG-14:22 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 181.51 0.00
September 21061.96 24-SEP-14:42 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 136.57 0.00
October 22454.27 01-OCT-13:11 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 67.11 0.00
November 21450.98 23-NOV-12:52 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 7.11
December 20837.28 03-DEC-12:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 6.80
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 14671.94   303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22454.27   910.97 537.55 6829.06 0.00 0.00 0.00 0.00 243.82 49.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8480.49 14-JAN-06:02 652.28 626.56 3259.86 0.00 0.00 0.00 0.00 0.00 29.66
February 17406.44 19-FEB-16:12 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 31.88
March 21070.60 26-MAR-14:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 72.59 0.00
April 22159.83 30-APR-16:21 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 153.78 0.00
May 21518.67 07-MAY-15:51 521.82 307.92 3911.83 0.00 0.00 0.00 0.00 147.69 0.00
June 21554.30 04-JUN-15:51 521.82 307.92 3911.83 0.00 0.00 0.00 0.00 147.81 0.00
July 24103.34 02-JUL-16:21 587.05 346.41 4400.81 0.00 0.00 0.00 0.00 96.50 0.00
August 21609.99 06-AUG-15:42 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 97.55 0.00
September 21299.59 24-SEP-14:42 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 90.61 0.00
October 22307.67 01-OCT-15:11 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 38.94 0.00
November 20184.25 23-NOV-14:12 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 5.34
December 18231.40 24-DEC-15:32 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 42.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8480.49   260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24103.34   652.28 626.56 4400.81 0.00 0.00 0.00 0.00 153.78 42.36



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3666.53 26-JAN-14:30 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 25.25
February 5606.67 24-FEB-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 24.00 0.00
March 13820.12 14-MAR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 8.94
April 14864.95 28-APR-05:02 1214.60 1166.71 6070.18 0.00 0.00 0.00 0.00 1.03 0.00
May 19413.51 28-MAY-16:41 1012.16 597.26 7587.73 0.00 0.00 0.00 0.00 1168.83 0.00
June 18920.92 11-JUN-17:02 0.00 358.36 4552.64 0.00 0.00 0.00 0.00 230.87 0.00
July 18880.01 02-JUL-16:32 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 426.10 0.00
August 17268.53 02-AUG-03:02 0.00 486.13 5058.48 0.00 0.00 0.00 0.00 94.43 0.00
September 18740.12 24-SEP-14:42 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 359.47 0.00
October 14289.53 12-OCT-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 16.59
November 5931.09 09-NOV-14:30 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 17.61 0.00
December 3555.20 28-DEC-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 3.83 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3555.20   0.00 358.36 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19413.51   2010.79 1166.71 7587.73 0.00 0.00 0.00 0.00 1168.83 25.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3524.92 26-JAN-10:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 34.02
February 6241.44 22-FEB-10:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 12.52
March 11230.52 12-MAR-09:23 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 23.48
April 16467.59 16-APR-09:52 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 40.03 0.00
May 17994.83 28-MAY-09:21 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 195.72 0.00
June 16318.97 04-JUN-10:43 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 204.54 0.00
July 16232.01 04-JUL-10:02 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 177.26 0.00
August 13615.72 07-AUG-05:03 913.19 877.19 4563.83 0.00 0.00 0.00 0.00 19.22 0.00
September 15903.65 24-SEP-14:42 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 233.26 0.00
October 16716.65 01-OCT-09:52 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 22.55 0.00
November 6198.50 09-NOV-10:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.53 0.00
December 4156.04 01-DEC-10:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 16.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3524.92   195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17994.83   1239.33 877.19 4563.83 0.00 0.00 0.00 0.00 233.26 34.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 17581.65 08-JAN-14:23 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 95.79
February 20020.60 20-FEB-12:23 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 43.28
March 19973.64 26-MAR-13:32 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 222.65 0.00
April 20027.83 16-APR-12:32 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 172.34 0.00
May 19632.98 28-MAY-16:01 1012.19 597.27 7587.84 0.00 0.00 0.00 0.00 1258.14 0.00
June 18963.11 11-JUN-16:22 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 257.95 0.00
July 18985.98 02-JUL-16:32 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 427.54 0.00
August 19151.91 27-AUG-14:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 186.66 0.00
September 20511.29 24-SEP-14:42 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 308.45 0.00
October 22021.59 01-OCT-13:11 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 148.96 0.00
November 21614.61 12-NOV-13:12 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 34.78
December 20107.48 03-DEC-13:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 18.09
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17581.65   303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22021.59   1012.19 597.27 7587.84 0.00 0.00 0.00 0.00 1258.14 95.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5187.61 31-JAN-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 19.89
February 10246.83 20-FEB-15:43 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 11.49
March 16661.43 12-MAR-17:23 0.00 153.96 1955.92 0.00 0.00 0.00 0.00 83.98 0.00
April 18114.90 30-APR-16:02 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 381.80 0.00
May 18986.17 28-MAY-16:01 652.28 384.90 4889.79 0.00 0.00 0.00 0.00 765.46 0.00
June 18241.39 11-JUN-16:22 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 159.83 0.00
July 18095.36 02-JUL-16:32 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 263.38 0.00
August 17610.66 06-AUG-16:22 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 220.00 0.00
September 18098.27 24-SEP-14:42 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 207.98 0.00
October 18856.78 01-OCT-15:51 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 72.02 0.00
November 14342.84 12-NOV-15:12 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 29.71 0.00
December 5662.30 01-DEC-15:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 3.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5187.61   0.00 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18986.17   1239.33 692.79 4889.79 0.00 0.00 0.00 0.00 765.46 19.89



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3129.44 26-JAN-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 37.24
February 5757.36 23-FEB-14:50 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 14.07 0.00
March 13558.29 14-MAR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 11.25
April 22425.99 16-APR-15:41 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 127.63 0.00
May 23072.30 28-MAY-16:11 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 1514.13 0.00
June 22971.45 04-JUN-16:31 809.73 477.81 6070.18 0.00 0.00 0.00 0.00 616.04 0.00
July 22741.27 02-JUL-16:32 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 513.12 0.00
August 21402.19 06-AUG-15:42 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 473.74 0.00
September 22620.07 17-SEP-14:52 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 372.64 0.00
October 15286.49 04-OCT-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 1.74 0.00
November 6421.82 09-NOV-14:40 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 20.84 0.00
December 2982.71 28-DEC-15:50 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 3.13
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2982.71   607.30 358.36 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23072.30   2010.79 1075.02 6070.18 0.00 0.00 0.00 0.00 1514.13 37.24



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3024.32 26-JAN-14:30 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 22.01
February 5702.31 23-FEB-10:40 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 6.55
March 16454.10 12-MAR-16:22 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 117.07 0.00
April 18984.57 16-APR-09:02 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 14.75 0.00
May 19384.98 07-MAY-09:51 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 278.65 0.00
June 17604.11 11-JUN-10:22 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 176.63 0.00
July 17464.38 04-JUL-10:02 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 215.05 0.00
August 16901.28 06-AUG-15:02 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 337.97 0.00
September 17470.79 17-SEP-14:52 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 240.70 0.00
October 11882.51 01-OCT-10:02 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 41.89 0.00
November 5906.63 09-NOV-10:20 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 1.87 0.00
December 3089.37 01-DEC-14:50 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 2.70
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3024.32   260.91 153.96 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19384.98   1295.83 692.79 3422.87 0.00 0.00 0.00 0.00 337.97 22.01



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11874.19 12-JAN-14:20 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 16.02
February 22961.50 20-FEB-15:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 31.90
March 24195.88 12-MAR-13:42 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 37.28 0.00
April 23332.65 16-APR-15:01 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 170.13 0.00
May 23269.98 07-MAY-15:11 809.75 477.82 6070.27 0.00 0.00 0.00 0.00 680.00 0.00
June 22933.34 04-JUN-15:51 809.75 477.82 6070.27 0.00 0.00 0.00 0.00 668.87 0.00
July 22730.01 02-JUL-16:32 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 514.47 0.00
August 22519.96 06-AUG-14:22 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 513.54 0.00
September 24219.07 17-SEP-14:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 320.16 0.00
October 25030.65 22-OCT-13:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 59.32 0.00
November 25001.93 05-NOV-13:42 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 9.48 0.00
December 21256.23 03-DEC-13:32 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 19.93
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 11874.19   404.87 238.91 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25030.65   2010.83 1075.05 6070.27 0.00 0.00 0.00 0.00 680.00 31.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 4674.48 12-JAN-15:50 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 9.42
February 8499.11 20-FEB-15:43 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 15.38
March 20539.15 12-MAR-16:22 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 84.97 0.00
April 20700.95 30-APR-16:02 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 459.23 0.00
May 21507.39 28-MAY-16:11 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 925.03 0.00
June 21212.49 04-JUN-16:31 521.82 307.92 3911.83 0.00 0.00 0.00 0.00 380.76 0.00
July 20820.03 02-JUL-16:32 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 318.12 0.00
August 20041.98 06-AUG-16:22 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 264.42 0.00
September 20695.12 17-SEP-14:52 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 215.84 0.00
October 20076.81 22-OCT-15:52 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 46.93 0.00
November 15036.99 05-NOV-15:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 4.59 0.00
December 5295.54 28-DEC-15:40 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 1.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4674.48   260.91 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21507.39   1239.33 692.79 3911.83 0.00 0.00 0.00 0.00 925.03 15.38



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6991.68 17-JAN-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 10225.49 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.15
March 10811.52 06-MAR-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 15.69
April 16257.10 17-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.17
May 17755.84 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.22 0.00
June 17355.93 12-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.00 0.00
July 18071.93 05-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 55.49 0.00
August 17631.53 07-AUG-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.24 0.00
September 13175.73 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.75 0.00
October 11566.60 10-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 11739.03 06-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 9077.87 26-DEC-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6991.68   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18071.93   0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.00 15.69



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3840.52 20-JAN-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.87
February 4968.25 21-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.35
March 7305.32 13-MAR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 59.30 0.00
April 8362.01 17-APR-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 322.79 0.00
May 11081.53 31-MAY-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 149.39 0.00
June 10939.00 10-JUN-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.67 0.00
July 10485.90 07-JUL-05:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.30 0.00
August 11036.50 08-AUG-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 67.21 0.00
September 11569.19 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.28 0.00
October 9077.00 16-OCT-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.41
November 6956.99 06-NOV-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 4197.97 20-DEC-06:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 105.03
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3840.52   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 11569.19   0.00 0.00 0.00 0.00 0.00 0.00 0.00 322.79 105.03



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6448.44 12-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.79
February 13210.73 22-FEB-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.04 0.00
March 20925.33 28-MAR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 25800.19 26-APR-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 113.41 0.00
May 29385.58 01-MAY-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 335.29 0.00
June 30910.08 12-JUN-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 367.34 0.00
July 27485.09 07-JUL-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 254.03 0.00
August 24488.57 07-AUG-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 242.59 0.00
September 21333.92 26-SEP-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 107.48 0.00
October 20275.13 02-OCT-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 128.38 0.00
November 14160.35 09-NOV-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 22.02 0.00
December 7952.38 01-DEC-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.74
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 6448.44   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 30910.08   0.00 0.00 0.00 0.00 0.00 0.00 0.00 367.34 47.79



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1887.21 30-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3915.09 20-FEB-17:15 46.77 90.03 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
March 7201.51 31-MAR-23:53 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
April 7748.08 17-APR-01:55 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
May 3494.18 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5404.43 30-JUN-24:00 0.00 45.01 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7250.20 31-JUL-24:00 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7547.82 16-AUG-00:50 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 3486.88 30-SEP-24:00 0.00 45.01 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
October 5386.65 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5798.22 12-NOV-16:23 35.07 67.52 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
December 7603.79 28-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1887.21   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7748.08   222.14 405.10 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1735.60 12-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3622.26 21-FEB-17:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6949.20 31-MAR-23:53 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
April 7244.24 12-APR-16:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3365.50 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5201.09 30-JUN-24:00 0.00 45.01 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 6927.47 31-JUL-23:43 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7130.42 16-AUG-09:40 232.27 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3369.15 30-SEP-24:00 0.00 45.01 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
October 5084.85 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5445.65 08-NOV-16:40 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7195.50 01-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1735.60   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7244.24   232.27 405.10 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1731.45 12-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3656.86 22-FEB-17:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6899.61 31-MAR-23:53 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
April 7463.63 16-APR-21:32 0.00 112.53 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3341.38 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5250.79 30-JUN-24:00 0.00 45.01 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7047.25 31-JUL-23:57 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7296.00 20-AUG-17:33 0.00 90.03 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3356.05 30-SEP-23:17 0.00 67.52 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
October 4941.58 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5493.45 08-NOV-16:30 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7190.26 28-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1731.45   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7463.63   222.14 405.10 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92473.16 12-JAN-17:00 4808.68 4375.82 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183895.03 21-FEB-17:00 4808.68 4375.82 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358642.06 31-MAR-23:57 0.00 729.33 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
April 368779.80 30-APR-04:53 0.00 729.33 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
May 176019.30 31-MAY-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 268193.27 30-JUN-24:00 0.00 486.22 569448.78 0.00 0.00 0.00 0.00 0.00 0.00
July 356261.78 31-JUL-23:20 0.00 486.22 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
August 369681.22 15-AUG-23:53 0.00 729.33 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
September 177491.45 30-SEP-24:00 0.00 486.22 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
October 269346.88 31-OCT-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 277030.05 13-NOV-17:00 4808.68 4375.82 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 368383.94 04-DEC-17:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92473.16   0.00 243.11 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369681.22   4808.68 4375.82 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.174873E+13 1115941.33 12-JAN-16:30 0.675158E+11 244167.48 02-JAN-06:19
February 0.203008E+13 1323472.18 24-FEB-16:40 0.496620E+11 86230.74 02-FEB-06:00
March 0.284100E+13 1703269.47 29-MAR-15:50 0.533201E+11 70054.48 02-MAR-12:50
April 0.333074E+13 1942589.44 18-APR-15:09 0.459380E+11 65297.38 07-APR-11:50
May 0.238200E+13 1509528.89 09-MAY-15:00 0.447716E+11 60254.53 01-MAY-11:30
June 0.284464E+13 1753558.74 22-JUN-15:09 0.410891E+11 53093.97 01-JUN-11:00
July 0.336823E+13 1916426.92 05-JUL-15:00 0.392773E+11 47766.69 03-JUL-11:39
August 0.381333E+13 2042710.94 07-AUG-15:09 0.423262E+11 52019.59 31-AUG-11:50
September 0.225795E+13 1532602.57 14-SEP-15:20 0.419045E+11 58164.39 27-SEP-11:30
October 0.250838E+13 1557910.99 03-OCT-15:09 0.467968E+11 64548.95 27-OCT-11:20
November 0.265396E+13 1576264.58 06-NOV-14:39 0.492601E+11 69710.62 27-NOV-12:00
December 0.301861E+13 1614177.22 28-DEC-16:19 0.559683E+11 148250.85 23-DEC-06:40
             
Annual Sum or Average 0.327977E+14     0.577830E+12    
Minimum of Months 0.174873E+13 1115941.33   0.392773E+11 47766.69  
Maximum of Months 0.381333E+13 2042710.94   0.675158E+11 244167.48  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.230186E+12 0.445929E+11 0.811612E+12 0.162549E+12 0.174550E+12 0.694902E+11 0.00 0.177321E+12 0.664469E+11 0.119804E+11 0.00 0.00 0.00
February 0.208137E+12 0.381264E+11 0.102011E+13 0.146826E+12 0.169544E+12 0.699399E+11 0.00 0.262453E+12 0.101830E+12 0.131189E+11 0.00 0.00 0.00
March 0.246166E+12 0.387256E+11 0.146267E+13 0.162740E+12 0.218542E+12 0.963901E+11 0.00 0.468352E+12 0.140572E+12 0.684805E+10 0.00 0.00 0.00
April 0.219479E+12 0.340652E+11 0.170311E+13 0.157288E+12 0.239060E+12 0.118137E+12 0.00 0.700569E+12 0.158074E+12 0.962645E+09 0.00 0.00 0.00
May 0.236340E+12 0.322038E+11 0.820521E+12 0.162644E+12 0.260963E+12 0.130779E+12 0.00 0.537055E+12 0.201476E+12 15072026.57 0.00 0.00 0.00
June 0.235149E+12 0.295519E+11 0.110677E+13 0.157466E+12 0.256441E+12 0.132255E+12 0.00 0.713786E+12 0.213221E+12 0.00 0.00 0.00 0.00
July 0.220648E+12 0.314140E+11 0.143888E+13 0.162466E+12 0.249420E+12 0.142614E+12 0.00 0.890456E+12 0.232336E+12 0.00 0.00 0.00 0.00
August 0.245906E+12 0.338286E+11 0.177780E+13 0.162740E+12 0.256965E+12 0.143520E+12 0.00 0.963564E+12 0.229008E+12 0.00 0.00 0.00 0.00
September 0.220133E+12 0.360059E+11 0.784732E+12 0.157287E+12 0.227862E+12 0.119141E+12 0.00 0.506897E+12 0.205892E+12 0.00 0.00 0.00 0.00
October 0.229225E+12 0.407566E+11 0.112899E+13 0.162550E+12 0.219540E+12 0.105862E+12 0.00 0.457904E+12 0.162218E+12 0.133582E+10 0.00 0.00 0.00
November 0.227341E+12 0.423923E+11 0.140306E+13 0.157361E+12 0.193489E+12 0.841051E+11 0.00 0.403866E+12 0.128602E+12 0.137471E+11 0.00 0.00 0.00
December 0.223114E+12 0.456536E+11 0.175516E+13 0.162465E+12 0.181015E+12 0.772607E+11 0.00 0.416941E+12 0.122362E+12 0.346349E+11 0.00 0.00 0.00
                           
Annual Sum or Average 0.274182E+13 0.447317E+12 0.152134E+14 0.191438E+13 0.264739E+13 0.128949E+13 0.00 0.649917E+13 0.196204E+13 0.826428E+11 0.00 0.00 0.00
Minimum of Months 0.208137E+12 0.295519E+11 0.784732E+12 0.146826E+12 0.169544E+12 0.694902E+11 0.00 0.177321E+12 0.664469E+11 0.00 0.00 0.00 0.00
Maximum of Months 0.246166E+12 0.456536E+11 0.177780E+13 0.162740E+12 0.260963E+12 0.143520E+12 0.00 0.963564E+12 0.232336E+12 0.346349E+11 0.00 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.133055E+11 0.00 0.542103E+11 0.00 0.00
February 0.00 0.00 0.120457E+10 0.00 0.484574E+11 0.00 0.00
March 0.00 0.00 0.00 0.00 0.533201E+11 0.00 0.00
April 0.00 0.00 0.00 0.00 0.459380E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.447716E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.410891E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.392773E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.423262E+11 0.00 0.00
September 0.00 0.00 7305.64 0.00 0.419045E+11 0.00 0.00
October 0.00 0.00 0.00 0.00 0.467968E+11 0.00 0.00
November 0.00 0.00 43671473.35 0.00 0.492164E+11 0.00 0.00
December 0.00 0.00 0.371727E+10 0.00 0.522511E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.182710E+11 0.00 0.559559E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.392773E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.133055E+11 0.00 0.542103E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 251205.37 18-JAN-08:09 37611.08 01-JAN-06:10 439129.89 02-JAN-08:09 117199.11 18-JAN-08:20 119443.29 12-JAN-15:09 65670.73 12-JAN-14:09 0.00 01-JAN-00:10
February 250359.64 10-FEB-08:09 37611.08 01-FEB-06:10 557421.28 01-FEB-08:09 117198.62 10-FEB-08:20 152599.68 21-FEB-16:10 66204.05 16-FEB-16:40 0.00 01-FEB-00:10
March 251050.18 14-MAR-07:10 37611.08 01-MAR-06:10 675712.68 01-MAR-08:09 117199.02 14-MAR-07:19 185321.15 13-MAR-15:00 66728.74 28-MAR-14:20 0.00 01-MAR-00:10
April 236455.86 03-APR-07:10 37611.08 01-APR-05:10 794004.08 03-APR-07:10 117190.71 03-APR-07:19 201830.84 17-APR-15:09 68512.20 19-APR-16:10 0.00 01-APR-00:10
May 241491.81 24-MAY-07:10 37611.08 01-MAY-05:10 439129.89 01-MAY-07:10 117193.58 24-MAY-07:19 225642.14 30-MAY-14:09 68157.02 03-MAY-15:50 0.00 01-MAY-00:10
June 241504.02 23-JUN-07:10 37611.08 01-JUN-05:10 557421.28 01-JUN-07:10 117193.58 23-JUN-07:19 229329.06 07-JUN-13:00 68426.35 22-JUN-15:00 0.00 01-JUN-00:10
July 250026.35 26-JUL-07:10 37611.08 01-JUL-05:10 675712.68 03-JUL-07:10 117198.43 26-JUL-07:19 227382.65 05-JUL-15:20 70744.01 18-JUL-05:10 0.00 01-JUL-00:10
August 251266.09 16-AUG-07:10 37611.08 01-AUG-05:10 794004.08 01-AUG-07:10 117199.14 16-AUG-07:19 212273.56 07-AUG-14:50 70858.56 29-AUG-05:10 0.00 01-AUG-00:10
September 252502.98 08-SEP-07:10 37611.08 01-SEP-05:10 439129.89 01-SEP-07:10 117199.84 08-SEP-07:19 201694.50 27-SEP-15:00 67555.12 28-SEP-14:30 0.00 01-SEP-00:10
October 254941.81 11-OCT-07:10 37611.08 01-OCT-05:10 557421.28 02-OCT-07:10 117201.23 11-OCT-07:19 183825.22 04-OCT-15:00 67594.60 03-OCT-14:39 0.00 01-OCT-00:10
November 252112.79 27-NOV-16:00 37611.08 01-NOV-05:10 675712.68 01-NOV-07:10 117194.98 03-NOV-07:19 159990.45 13-NOV-16:10 67054.99 13-NOV-13:00 0.00 01-NOV-00:10
December 253561.92 29-DEC-16:00 37611.08 01-DEC-06:10 794004.08 01-DEC-08:09 117193.45 29-DEC-08:20 131789.64 01-DEC-15:39 65898.16 01-DEC-16:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 236455.86   37611.08   439129.89   117190.71   119443.29   65670.73   0.00  
Maximum of Months 254941.81   37611.08   794004.08   117201.23   229329.06   70858.56   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY [] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 150965.65 12-JAN-14:09 50450.41 13-JAN-14:00 7518.01 21-JAN-17:40 0.00 0.00 0.00
February 200879.52 24-FEB-16:40 53127.49 24-FEB-15:30 11142.13 04-FEB-05:00 0.00 0.00 0.00
March 392847.42 28-MAR-13:30 91812.10 06-MAR-14:30 13984.28 01-MAR-05:00 0.00 0.00 0.00
April 483888.37 18-APR-15:39 91812.10 03-APR-09:09 7692.98 11-APR-04:00 0.00 0.00 0.00
May 417622.23 17-MAY-15:30 91812.10 01-MAY-07:10 2037.96 28-MAY-14:00 0.00 0.00 0.00
June 528597.55 22-JUN-15:39 91812.10 01-JUN-06:40 0.00 01-JUN-00:10 0.00 0.00 0.00
July 539407.01 10-JUL-13:00 91812.10 01-JUL-03:39 0.00 01-JUL-00:10 0.00 0.00 0.00
August 571270.01 28-AUG-14:50 91812.10 01-AUG-01:10 0.00 01-AUG-00:10 0.00 0.00 0.00
September 427468.59 14-SEP-15:30 91812.10 01-SEP-00:20 0.00 01-SEP-00:10 0.00 0.00 0.00
October 386627.81 04-OCT-12:09 91812.10 02-OCT-08:09 7240.60 31-OCT-04:00 0.00 0.00 0.00
November 359511.14 06-NOV-13:09 91812.10 06-NOV-11:20 15174.12 30-NOV-22:00 0.00 0.00 0.00
December 262312.87 01-DEC-14:30 50764.07 28-DEC-14:00 28639.67 22-DEC-05:00 0.00 0.00 0.00
                   
Annual Sum or Average             0.00 0.00 0.00
Minimum of Months 150965.65   50450.41   0.00   0.00 0.00 0.00
Maximum of Months 571270.01   91812.10   28639.67   0.00 0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1115941.33 12-JAN-16:30 237063.17 439129.89 0.00 83146.61 113284.16 43655.31 0.00 149433.25 50228.95
February 1323472.18 24-FEB-16:40 234435.00 557421.28 0.00 83146.17 130051.76 65018.72 0.00 200879.52 52519.72
March 1703269.47 29-MAR-15:50 234435.00 675712.68 0.00 83146.17 175452.16 66089.92 0.00 376621.42 91812.10
April 1942589.44 18-APR-15:09 234435.00 794004.08 0.00 83146.17 191844.31 66756.00 0.00 480591.77 91812.10
May 1509528.89 09-MAY-15:00 234435.00 439129.89 0.00 83146.17 202737.54 66978.63 0.00 391289.55 91812.10
June 1753558.74 22-JUN-15:09 234435.00 557421.28 0.00 83146.17 196490.91 68081.54 0.00 522171.72 91812.10
July 1916426.92 05-JUL-15:00 234435.00 675712.68 0.00 83146.17 224961.07 67718.55 0.00 538641.34 91812.10
August 2042710.94 07-AUG-15:09 234435.00 794004.08 0.00 83146.17 212155.95 67734.36 0.00 559423.27 91812.10
September 1532602.57 14-SEP-15:20 234435.00 439129.89 0.00 83146.17 189715.44 67426.71 0.00 426937.25 91812.10
October 1557910.99 03-OCT-15:09 234435.00 557421.28 0.00 83146.17 139324.01 67511.73 0.00 384260.68 91812.10
November 1576264.58 06-NOV-14:39 234435.00 675712.68 0.00 37754.99 122702.75 66089.97 0.00 347757.08 91812.10
December 1614177.22 28-DEC-16:19 236798.20 794004.08 0.00 83146.17 123015.79 65298.54 0.00 261238.60 50675.84
                       
Annual Sum or Average                      
Minimum of Months 1115941.33   234435.00 439129.89 0.00 37754.99 113284.16 43655.31 0.00 149433.25 50228.95
Maximum of Months 2042710.94   237063.17 794004.08 0.00 83146.61 224961.07 68081.54 0.00 559423.27 91812.10



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 217619.02 02-JAN-06:19 0.00 72823.30 10-JAN-12:50 0.00
February 0.00 0.00 60286.66 02-FEB-06:00 0.00 72220.76 10-FEB-12:39 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 70054.48 02-MAR-12:50 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 65297.38 07-APR-11:50 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 60254.53 01-MAY-11:30 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 53093.97 01-JUN-11:00 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 47766.69 03-JUL-11:39 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 52019.59 31-AUG-11:50 0.00
September 0.00 0.00 12.18 25-SEP-10:20 0.00 58164.39 27-SEP-11:30 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 64548.95 27-OCT-11:20 0.00
November 0.00 0.00 3692.60 27-NOV-06:00 0.00 69710.62 27-NOV-12:00 0.00
December 0.00 0.00 122984.77 23-DEC-06:49 0.00 72384.62 28-DEC-12:39 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 47766.69   0.00
Maximum of Months 0.00 0.00 217619.02   0.00 72823.30   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 8.33 26.60 2.33 26.75
February 0.00 0.00 0.00 0.00 3.83 26.26 0.33 26.34
March 0.00 0.00 0.00 0.00 2.00 25.87 0.00 25.87
April 0.00 0.00 0.00 0.00 3.33 26.28 0.17 26.20
May 0.00 0.00 0.00 0.00 4.00 26.29 0.17 26.33
June 0.00 0.00 0.00 0.00 5.83 26.62 0.00 26.62
July 0.00 0.00 0.00 0.00 10.00 26.23 1.00 26.29
August 0.00 0.00 0.00 0.00 11.00 26.00 0.67 26.08
September 0.00 0.00 0.00 0.00 10.33 26.28 1.50 26.41
October 0.00 0.00 0.00 0.00 8.50 26.03 0.17 26.00
November 0.00 0.00 0.00 0.00 12.50 26.43 1.00 26.50
December 0.00 0.00 0.00 0.00 9.50 26.46 0.17 26.47
                 
Annual Sum or Average 0.00   0.00   89.17 26.30 7.50 26.36
Minimum of Months 0.00 0.00 0.00 0.00 2.00 25.87 0.00 25.87
Maximum of Months 0.00 0.00 0.00 0.00 12.50 26.62 2.33 26.75



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.67 25.75 0.00 25.75
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 25.63 0.00 25.63
May 0.00 0.00 0.00 0.00 0.50 25.67 0.00 25.67
June 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
July 0.00 0.00 0.00 0.00 1.50 25.64 0.00 25.64
August 0.00 0.00 0.00 0.00 1.83 25.69 0.00 25.69
September 0.00 0.00 0.00 0.00 0.33 25.60 0.00 25.60
October 0.00 0.00 0.00 0.00 0.33 25.63 0.00 25.63
November 0.00 0.00 0.00 0.00 0.67 25.59 0.00 25.59
December 0.00 0.00 0.00 0.00 1.17 25.77 0.00 25.77
                 
Annual Sum or Average 0.00   0.00   7.83 25.68 0.00 25.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.83 25.77 0.00 25.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.56 0.00 25.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.11 0.00 19.11 0.00 19.11 0.00 19.11
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 25.64 0.00 25.64
June 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
July 0.00 0.00 0.00 0.00 0.17 25.57 0.00 25.57
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.11 0.00 19.11 0.50 23.97 0.00 23.97
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.11 0.00 19.11 0.17 25.64 0.00 25.64



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 6.33 26.83 2.83 27.04
May 0.00 0.00 0.00 0.00 11.83 26.94 4.83 27.12
June 0.00 0.00 0.00 0.00 12.83 26.69 3.00 26.86
July 0.00 0.00 0.00 0.00 22.00 27.12 9.33 27.24
August 0.00 0.00 0.00 0.00 16.50 26.82 5.83 27.00
September 0.00 0.00 0.00 0.00 1.50 25.99 0.17 26.11
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   71.00 26.89 26.00 27.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 22.00 27.12 9.33 27.24



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.17 27.33 0.17 27.33
March 0.00 0.00 0.00 0.00 1.67 27.46 1.67 27.46
April 0.00 0.00 0.00 0.00 8.33 27.57 6.50 27.67
May 0.00 0.00 0.00 0.00 16.83 27.42 9.83 27.61
June 0.00 0.00 0.00 0.00 12.33 26.95 4.67 27.17
July 0.00 0.00 0.00 0.00 20.00 27.29 10.50 27.43
August 0.00 0.00 0.00 0.00 9.00 26.99 5.67 27.20
September 0.00 0.00 0.00 0.00 4.50 27.15 3.67 27.29
October 0.00 0.00 0.00 0.00 4.83 27.52 4.83 27.52
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   77.67 27.27 47.50 27.43
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 20.00 27.57 10.50 27.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.17 27.35 1.17 27.35
February 0.00 0.00 0.00 0.00 4.67 27.67 4.67 27.67
March 0.00 0.00 0.00 0.00 6.33 27.59 5.67 27.62
April 0.00 0.00 0.00 0.00 14.17 27.21 7.67 27.39
May 0.00 0.00 0.00 0.00 16.17 27.04 7.33 27.21
June 0.00 0.00 0.00 0.00 13.67 26.72 3.17 26.88
July 0.00 0.00 0.00 0.00 22.67 27.12 9.50 27.25
August 0.00 0.00 0.00 0.00 19.33 26.91 6.50 27.10
September 0.00 0.00 0.00 0.00 8.33 26.96 3.67 27.21
October 0.00 0.00 0.00 0.00 15.50 27.67 11.33 27.82
November 0.00 0.00 0.00 0.00 10.33 27.87 10.17 27.87
December 0.00 0.00 0.00 0.00 4.33 27.58 4.33 27.58
                 
Annual Sum or Average 0.00   0.00   136.67 27.21 75.17 27.40
Minimum of Months 0.00 0.00 0.00 0.00 1.17 26.72 1.17 26.88
Maximum of Months 0.00 0.00 0.00 0.00 22.67 27.87 11.33 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 2.50 27.73 2.50 27.73
March 0.00 0.00 0.00 0.00 19.67 26.87 5.33 27.10
April 0.00 0.00 0.00 0.00 67.67 27.71 18.67 27.79
May 0.00 0.00 0.00 0.00 35.00 27.35 10.00 27.52
June 0.00 0.00 0.00 0.00 42.17 27.42 10.50 27.52
July 0.00 0.00 0.00 0.00 59.00 27.62 18.00 27.72
August 0.00 0.00 0.00 0.00 74.50 27.74 19.17 27.79
September 0.00 0.00 0.00 0.00 17.83 26.88 4.00 27.05
October 0.00 0.00 0.00 0.00 23.33 27.10 8.33 27.33
November 0.00 0.00 0.00 0.00 11.17 26.99 6.00 27.29
December 0.00 0.00 0.00 0.00 5.17 27.07 3.67 27.28
                 
Annual Sum or Average 0.00   0.00   358.00 27.47 106.17 27.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 74.50 27.74 19.17 27.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.00 26.89 1.33 27.07
May 0.00 0.00 0.00 0.00 12.67 26.90 5.17 27.11
June 0.00 0.00 0.00 0.00 11.00 26.56 2.67 26.76
July 0.00 0.00 0.00 0.00 16.50 26.87 6.50 27.04
August 0.00 0.00 0.00 0.00 6.67 26.42 2.67 26.68
September 0.00 0.00 0.00 0.00 1.00 26.20 0.33 26.47
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   49.83 26.74 18.67 26.94
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 16.50 26.90 6.50 27.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 1.83 27.51 1.83 27.51
April 0.00 0.00 0.00 0.00 10.00 27.59 7.83 27.70
May 0.00 0.00 0.00 0.00 19.67 27.39 10.67 27.63
June 0.00 0.00 0.00 0.00 12.50 26.96 5.00 27.21
July 0.00 0.00 0.00 0.00 19.83 27.20 10.33 27.39
August 0.00 0.00 0.00 0.00 10.00 26.91 6.00 27.16
September 0.00 0.00 0.00 0.00 5.33 27.28 4.33 27.41
October 0.00 0.00 0.00 0.00 6.17 27.56 6.17 27.56
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   85.33 27.26 52.17 27.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 19.83 27.59 10.67 27.70



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.00 27.48 1.00 27.48
February 0.00 0.00 0.00 0.00 4.00 27.73 4.00 27.73
March 0.00 0.00 0.00 0.00 5.33 27.67 4.83 27.69
April 0.00 0.00 0.00 0.00 9.00 27.24 5.50 27.42
May 0.00 0.00 0.00 0.00 15.83 26.94 7.17 27.16
June 0.00 0.00 0.00 0.00 10.83 26.57 2.83 26.77
July 0.00 0.00 0.00 0.00 17.00 26.90 7.33 27.09
August 0.00 0.00 0.00 0.00 10.17 26.64 4.67 26.92
September 0.00 0.00 0.00 0.00 9.00 26.80 3.50 27.09
October 0.00 0.00 0.00 0.00 15.33 27.77 11.00 27.93
November 0.00 0.00 0.00 0.00 9.83 27.91 9.67 27.92
December 0.00 0.00 0.00 0.00 3.17 27.60 3.17 27.60
                 
Annual Sum or Average 0.00   0.00   110.50 27.17 64.67 27.39
Minimum of Months 0.00 0.00 0.00 0.00 1.00 26.57 1.00 26.77
Maximum of Months 0.00 0.00 0.00 0.00 17.00 27.91 11.00 27.93



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.33 27.31 0.33 27.31
March 0.00 0.00 0.00 0.00 3.17 27.62 2.17 27.68
April 0.00 0.00 0.00 0.00 16.50 27.22 5.67 27.45
May 0.00 0.00 0.00 0.00 29.00 27.32 8.50 27.52
June 0.00 0.00 0.00 0.00 22.83 27.13 5.33 27.32
July 0.00 0.00 0.00 0.00 25.50 27.27 8.50 27.43
August 0.00 0.00 0.00 0.00 16.67 26.91 5.00 27.12
September 0.00 0.00 0.00 0.00 8.33 26.76 2.17 27.04
October 0.00 0.00 0.00 0.00 7.33 27.64 5.00 27.76
November 0.00 0.00 0.00 0.00 0.67 27.41 0.67 27.41
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   130.33 27.20 43.33 27.40
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 29.00 27.64 8.50 27.76



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.67 18.36 0.00 18.36 0.00 18.36 0.00 18.36
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 6.17 27.46 3.67 27.54
May 0.00 0.00 0.00 0.00 22.83 27.34 9.00 27.48
June 0.00 0.00 0.00 0.00 20.17 27.03 5.50 27.19
July 0.00 0.00 0.00 0.00 25.17 27.24 9.50 27.37
August 0.00 0.00 0.00 0.00 12.67 26.85 5.00 27.07
September 0.00 0.00 0.00 0.00 3.67 27.10 2.33 27.27
October 0.00 0.00 0.00 0.00 0.50 27.35 0.50 27.35
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.67 18.36 0.00 18.36 91.17 27.11 35.50 27.28
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.67 18.36 0.00 18.36 25.17 27.46 9.50 27.54



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.51 0.00 18.51 0.00 18.51 0.00 18.51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 2.17 27.49 2.17 27.49
April 0.00 0.00 0.00 0.00 14.83 27.69 10.17 27.79
May 0.00 0.00 0.00 0.00 29.50 27.61 12.33 27.82
June 0.00 0.00 0.00 0.00 23.17 27.23 8.33 27.42
July 0.00 0.00 0.00 0.00 27.33 27.45 11.67 27.62
August 0.00 0.00 0.00 0.00 15.33 27.06 7.00 27.30
September 0.00 0.00 0.00 0.00 7.17 27.41 4.33 27.56
October 0.00 0.00 0.00 0.00 8.00 27.58 7.67 27.59
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.51 0.00 18.51 127.50 27.41 63.67 27.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.51 0.00 18.51 29.50 27.69 12.33 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.86 0.00 18.86 0.00 18.86 0.00 18.86
February 0.00 0.00 0.00 0.00 2.67 27.71 2.67 27.71
March 0.00 0.00 0.00 0.00 5.00 27.82 4.33 27.84
April 0.00 0.00 0.00 0.00 13.50 27.43 7.17 27.61
May 0.00 0.00 0.00 0.00 24.50 27.36 9.17 27.52
June 0.00 0.00 0.00 0.00 20.17 27.02 5.67 27.19
July 0.00 0.00 0.00 0.00 25.67 27.24 9.83 27.39
August 0.00 0.00 0.00 0.00 15.67 26.96 6.00 27.18
September 0.00 0.00 0.00 0.00 10.33 27.11 4.33 27.36
October 0.00 0.00 0.00 0.00 15.33 27.96 10.83 28.09
November 0.00 0.00 0.00 0.00 8.50 27.89 8.50 27.89
December 0.00 0.00 0.00 0.00 0.67 27.51 0.67 27.51
                 
Annual Sum or Average 0.33 18.86 0.00 18.86 142.00 27.33 69.17 27.53
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.86 0.00 18.86
Maximum of Months 0.33 18.86 0.00 18.86 25.67 27.96 10.83 28.09



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.89 0.00 18.89 0.00 18.89 0.00 18.89
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 3.33 27.83 2.33 27.86
April 0.00 0.00 0.00 0.00 19.67 27.50 6.83 27.70
May 0.00 0.00 0.00 0.00 33.33 27.59 9.83 27.79
June 0.00 0.00 0.00 0.00 28.00 27.39 7.00 27.57
July 0.00 0.00 0.00 0.00 32.17 27.50 10.50 27.65
August 0.00 0.00 0.00 0.00 21.83 27.14 7.17 27.33
September 0.00 0.00 0.00 0.00 9.17 27.16 3.33 27.40
October 0.00 0.00 0.00 0.00 6.67 27.99 5.00 28.04
November 0.00 0.00 0.00 0.00 0.50 27.38 0.50 27.38
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.33 18.89 0.00 18.89 154.67 27.44 52.50 27.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.89 0.00 18.89 33.33 27.99 10.50 28.04



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 181.00 28.27 156.83 28.28
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 479.17 28.28 360.17 28.30
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   660.17 28.28 517.00 28.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 479.17 28.28 360.17 28.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 163.67 28.19 148.83 28.19
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 373.83 28.16 305.00 28.18
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   537.50 28.17 453.83 28.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 373.83 28.19 305.00 28.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 119.17 28.24 105.67 28.23
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 249.67 28.14 215.67 28.14
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   368.83 28.17 321.33 28.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 249.67 28.24 215.67 28.23



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 546.17 29.51 409.33 29.61
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 1.00 28.29 0.00 28.29
August 0.00 0.00 0.00 0.00 743.17 30.27 514.00 30.35
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1290.33 29.94 923.33 30.03
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 743.17 30.27 514.00 30.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.17 26.74 294.33 24.96 1.83 24.98
February 12.17 26.72 352.67 24.76 12.17 24.82
March 35.00 25.07 431.67 24.56 35.00 24.59
April 32.50 24.21 411.33 24.59 32.50 24.57
May 287.33 24.46 489.83 24.51 287.33 24.49
June 345.33 24.55 496.00 24.51 345.33 24.52
July 298.50 25.07 497.00 24.80 298.50 24.88
August 253.17 25.02 514.00 24.67 253.17 24.76
September 279.67 25.01 485.00 24.74 279.67 24.81
October 107.33 25.16 502.00 24.72 107.33 24.79
November 0.17 27.21 465.17 24.66 0.17 24.66
December 0.00 0.00 370.50 24.82 0.00 24.82
             
Annual Sum or Average 1653.33 24.84 5309.50 24.67 1653.00 24.70
Minimum of Months 0.00 0.00 294.33 24.51 0.00 24.49
Maximum of Months 345.33 27.21 514.00 24.96 345.33 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 20.33 25.53 266.00 24.81 12.17 24.89
February 2.00 25.35 359.67 24.43 1.17 24.44
March 0.00 0.00 457.83 24.29 0.00 24.29
April 0.00 0.00 443.00 24.21 0.00 24.21
May 0.00 0.00 492.83 24.18 0.00 24.18
June 0.00 0.00 496.00 24.17 0.00 24.17
July 0.00 0.00 497.00 24.23 0.00 24.23
August 0.00 0.00 514.00 24.19 0.00 24.19
September 0.00 0.00 485.00 24.27 0.00 24.27
October 0.00 0.00 502.00 24.33 0.00 24.33
November 0.00 0.00 466.50 24.41 0.00 24.41
December 0.67 23.97 364.00 24.54 0.00 24.54
             
Annual Sum or Average 23.00 25.47 5343.83 24.31 13.33 24.32
Minimum of Months 0.00 0.00 266.00 24.17 0.00 24.17
Maximum of Months 20.33 25.53 514.00 24.81 12.17 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 136.17 23.59 124.83 24.02 13.00 24.04
February 61.67 23.82 249.17 24.23 8.17 24.27
March 8.17 23.75 398.17 24.24 0.50 24.24
April 3.33 23.78 382.50 24.19 0.00 24.19
May 0.00 0.00 474.17 24.12 0.00 24.12
June 0.00 0.00 495.83 24.12 0.00 24.12
July 0.00 0.00 497.00 24.14 0.00 24.14
August 0.00 0.00 514.00 24.17 0.00 24.17
September 1.33 26.10 484.50 24.26 1.33 24.27
October 0.00 0.00 489.00 24.29 0.00 24.29
November 10.50 23.56 382.00 24.27 0.00 24.27
December 86.33 23.50 146.83 24.07 0.00 24.07
             
Annual Sum or Average 307.50 23.63 4638.00 24.18 23.00 24.19
Minimum of Months 0.00 0.00 124.83 24.02 0.00 24.04
Maximum of Months 136.17 26.10 514.00 24.29 13.00 24.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 410.17 22.51 39.50 22.50 15.83 22.41
February 207.00 23.06 145.00 23.51 8.00 23.54
March 45.33 23.53 359.33 24.12 2.00 24.13
April 0.00 0.00 416.00 24.24 0.00 24.24
May 0.00 0.00 501.33 24.21 0.00 24.21
June 0.00 0.00 495.83 24.21 0.00 24.21
July 0.00 0.00 497.00 24.25 0.00 24.25
August 0.00 0.00 514.00 24.22 0.00 24.22
September 1.00 26.22 481.67 24.29 1.00 24.30
October 0.17 23.26 472.67 24.24 0.00 24.24
November 111.50 23.18 256.67 23.85 0.00 23.85
December 348.17 22.74 43.00 22.88 0.00 22.88
             
Annual Sum or Average 1123.33 22.79 4222.00 23.91 26.83 23.90
Minimum of Months 0.00 0.00 39.50 22.50 0.00 22.41
Maximum of Months 410.17 26.22 514.00 24.29 15.83 24.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 290.00 23.15 67.33 23.38 0.00 23.38
February 120.83 23.34 198.33 23.88 0.00 23.88
March 15.50 23.57 407.67 24.25 0.00 24.25
April 11.50 26.88 454.17 24.46 11.50 24.52
May 25.50 26.81 508.00 24.58 25.50 24.68
June 27.83 26.57 496.00 24.52 27.83 24.62
July 49.83 26.78 497.00 24.74 49.83 24.91
August 30.83 26.76 514.00 24.52 30.83 24.64
September 26.17 26.37 485.00 24.53 26.17 24.62
October 2.00 26.91 498.33 24.38 2.00 24.39
November 22.67 23.56 366.33 24.24 0.00 24.24
December 175.17 23.37 111.33 23.69 0.00 23.69
             
Annual Sum or Average 797.83 24.02 4603.50 24.33 173.67 24.41
Minimum of Months 2.00 23.15 67.33 23.38 0.00 23.38
Maximum of Months 290.00 26.91 514.00 24.74 49.83 24.91



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 220.67 23.09 98.67 23.48 0.00 23.48
February 97.67 23.15 245.00 24.00 0.00 24.00
March 23.50 24.06 425.67 24.31 4.67 24.33
April 30.83 26.88 457.83 24.57 30.83 24.71
May 47.50 26.91 508.00 24.71 47.50 24.88
June 29.00 26.67 496.00 24.52 29.00 24.63
July 47.17 26.81 497.00 24.69 47.17 24.86
August 27.33 26.73 514.00 24.43 27.33 24.54
September 28.83 26.45 485.00 24.54 28.83 24.64
October 25.50 26.79 492.83 24.56 25.50 24.66
November 41.83 23.42 375.33 24.26 0.50 24.26
December 196.17 23.16 149.50 23.66 0.00 23.66
             
Annual Sum or Average 816.00 24.22 4744.83 24.37 241.33 24.47
Minimum of Months 23.50 23.09 98.67 23.48 0.00 23.48
Maximum of Months 220.67 26.91 514.00 24.71 47.50 24.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 138.50 23.16 221.67 23.90 0.67 23.90
February 72.00 23.74 319.33 24.34 10.17 24.41
March 26.83 26.33 455.83 24.51 22.00 24.62
April 28.33 26.97 468.67 24.61 28.33 24.74
May 32.33 26.85 508.00 24.62 32.33 24.75
June 28.83 26.58 496.00 24.53 28.83 24.63
July 49.00 26.80 497.00 24.74 49.00 24.91
August 32.00 26.83 514.00 24.54 32.00 24.67
September 35.50 26.57 485.00 24.63 35.50 24.75
October 48.50 27.02 502.00 24.79 48.50 24.97
November 44.33 26.58 443.83 24.75 38.67 24.92
December 85.50 23.68 307.17 24.34 7.33 24.39
             
Annual Sum or Average 621.67 25.17 5218.50 24.55 333.33 24.68
Minimum of Months 26.83 23.16 221.67 23.90 0.67 23.90
Maximum of Months 138.50 27.02 514.00 24.79 49.00 24.97



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 119.50 23.25 212.83 24.03 0.00 24.03
February 24.67 24.84 377.33 24.55 10.17 24.61
March 30.00 26.98 507.67 24.64 30.00 24.76
April 87.33 26.94 485.00 24.99 87.33 25.25
May 66.83 26.88 508.00 24.83 66.83 25.05
June 75.17 26.78 496.00 24.82 75.17 25.04
July 105.83 26.84 497.00 25.05 105.83 25.32
August 95.33 26.88 514.00 24.93 95.33 25.19
September 56.67 26.76 485.00 24.77 56.67 24.96
October 54.33 26.95 502.00 24.84 54.33 25.03
November 29.67 26.96 479.17 24.75 29.67 24.88
December 13.17 26.66 415.33 24.73 12.00 24.79
             
Annual Sum or Average 758.50 26.23 5479.33 24.78 623.33 24.97
Minimum of Months 13.17 23.25 212.83 24.03 0.00 24.03
Maximum of Months 119.50 26.98 514.00 25.05 105.83 25.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 467.50 22.41 8.17 22.44 0.33 22.44
February 275.83 22.84 82.83 23.13 0.00 23.13
March 70.67 23.35 316.33 24.05 0.00 24.05
April 4.83 26.64 428.67 24.46 4.67 24.48
May 28.83 26.77 508.00 24.61 28.83 24.72
June 39.83 26.38 496.00 24.57 39.83 24.70
July 90.17 26.37 497.00 24.85 90.17 25.05
August 57.67 26.36 514.00 24.62 57.67 24.78
September 51.50 26.27 485.00 24.64 51.50 24.78
October 8.17 23.32 473.17 24.32 0.00 24.32
November 157.83 23.14 179.17 23.65 0.00 23.65
December 427.00 22.57 3.50 22.58 0.00 22.58
             
Annual Sum or Average 1679.83 23.28 3991.83 24.07 273.00 24.18
Minimum of Months 4.83 22.41 3.50 22.44 0.00 22.44
Maximum of Months 467.50 26.77 514.00 24.85 90.17 25.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 349.00 22.64 6.50 22.67 0.00 22.67
February 165.17 22.88 126.17 23.53 0.00 23.53
March 43.33 23.90 318.00 24.38 8.17 24.43
April 36.00 26.91 377.83 24.86 36.00 25.02
May 51.50 26.95 430.00 24.88 51.50 25.08
June 45.83 26.63 418.00 24.75 45.83 24.91
July 90.83 26.51 422.00 25.01 90.83 25.24
August 57.50 26.49 433.00 24.75 57.50 24.93
September 60.83 26.37 410.00 24.81 60.83 24.99
October 32.00 26.43 408.00 24.71 28.33 24.84
November 86.00 23.12 241.50 24.06 0.17 24.06
December 298.00 22.73 15.00 22.82 0.00 22.82
             
Annual Sum or Average 1316.00 23.89 3606.00 24.38 379.17 24.54
Minimum of Months 32.00 22.64 6.50 22.67 0.00 22.67
Maximum of Months 349.00 26.95 433.00 25.01 90.83 25.24



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 202.50 23.05 193.83 23.69 1.00 23.70
February 99.00 23.34 277.00 24.19 10.17 24.27
March 41.83 25.11 422.83 24.48 19.83 24.58
April 23.83 26.92 450.83 24.65 23.83 24.76
May 35.67 26.80 508.00 24.65 35.67 24.78
June 38.67 26.39 496.00 24.57 38.67 24.69
July 89.17 26.38 497.00 24.84 89.17 25.05
August 57.33 26.47 514.00 24.64 57.33 24.81
September 57.83 26.46 485.00 24.73 57.83 24.90
October 48.17 27.07 500.83 24.82 48.17 25.00
November 58.17 25.82 415.83 24.73 38.83 24.90
December 140.00 23.24 235.00 24.08 6.67 24.14
             
Annual Sum or Average 892.17 24.78 4996.17 24.55 427.17 24.69
Minimum of Months 23.83 23.05 193.83 23.69 1.00 23.70
Maximum of Months 202.50 27.07 514.00 24.84 89.17 25.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 383.33 22.64 36.17 22.77 0.00 22.77
February 180.50 22.87 170.50 23.58 0.83 23.59
March 38.50 24.10 403.83 24.34 8.50 24.39
April 29.83 26.98 473.33 24.69 29.83 24.82
May 53.67 26.96 508.00 24.79 53.67 24.98
June 62.50 26.68 496.00 24.74 62.50 24.93
July 97.67 26.61 497.00 24.95 97.67 25.18
August 63.83 26.68 514.00 24.72 63.83 24.92
September 64.33 26.55 485.00 24.77 64.33 24.96
October 21.67 26.96 489.17 24.60 21.67 24.70
November 78.67 23.26 327.00 24.12 1.50 24.13
December 324.50 22.86 75.67 23.11 0.00 23.11
             
Annual Sum or Average 1399.00 23.94 4475.67 24.36 404.33 24.51
Minimum of Months 21.67 22.64 36.17 22.77 0.00 22.77
Maximum of Months 383.33 26.98 514.00 24.95 97.67 25.18



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 494.17 21.38 78.33 21.17 78.33 21.01
February 352.83 22.25 57.67 22.41 9.33 22.36
March 131.67 23.04 289.83 23.83 0.00 23.83
April 21.17 25.90 429.67 24.52 15.17 24.59
May 43.50 26.82 508.00 24.69 43.50 24.84
June 48.50 26.53 496.00 24.64 48.50 24.79
July 96.83 26.45 497.00 24.89 96.83 25.11
August 59.17 26.41 514.00 24.64 59.17 24.80
September 55.67 26.26 485.00 24.65 55.67 24.80
October 35.17 23.40 432.67 24.24 3.50 24.26
November 269.67 22.66 127.17 23.09 2.17 23.07
December 485.00 21.72 48.67 21.55 48.67 21.41
             
Annual Sum or Average 2093.33 22.69 3964.00 23.72 460.83 23.78
Minimum of Months 21.17 21.38 48.67 21.17 0.00 21.01
Maximum of Months 494.17 26.82 514.00 24.89 96.83 25.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 472.83 21.85 45.50 21.71 39.50 21.57
February 250.33 22.48 126.83 23.01 3.00 22.98
March 74.83 23.43 376.00 24.19 8.67 24.24
April 43.67 26.80 456.50 24.75 41.67 24.92
May 59.00 26.98 508.00 24.81 59.00 25.01
June 54.00 26.72 496.00 24.70 54.00 24.88
July 98.67 26.54 497.00 24.93 98.67 25.16
August 58.50 26.55 514.00 24.66 58.50 24.84
September 63.00 26.35 485.00 24.70 63.00 24.87
October 51.83 25.45 462.33 24.57 34.17 24.71
November 153.67 22.76 246.17 23.66 0.00 23.66
December 433.33 22.17 25.33 22.10 19.83 22.02
             
Annual Sum or Average 1813.67 23.25 4238.67 24.06 480.00 24.18
Minimum of Months 43.67 21.85 25.33 21.71 0.00 21.57
Maximum of Months 472.83 26.98 514.00 24.93 98.67 25.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 297.00 22.14 143.83 22.65 19.33 22.53
February 162.33 22.62 220.50 23.67 6.50 23.73
March 74.17 24.14 395.00 24.36 19.67 24.46
April 31.17 26.75 451.33 24.67 29.17 24.80
May 44.17 26.86 508.00 24.70 44.17 24.86
June 47.83 26.54 496.00 24.63 47.83 24.79
July 95.83 26.45 497.00 24.89 95.83 25.11
August 60.33 26.49 514.00 24.67 60.33 24.84
September 63.50 26.44 485.00 24.75 63.50 24.93
October 51.17 26.73 484.83 24.79 46.83 24.97
November 96.67 24.25 368.17 24.46 31.83 24.63
December 236.17 22.44 180.00 23.26 7.00 23.22
             
Annual Sum or Average 1260.33 23.92 4743.67 24.36 472.00 24.50
Minimum of Months 31.17 22.14 143.83 22.65 6.50 22.53
Maximum of Months 297.00 26.86 514.00 24.89 95.83 25.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 436.33 21.79 49.17 21.73 31.83 21.60
February 265.33 22.37 122.33 22.98 0.00 22.98
March 86.00 23.48 367.00 24.18 9.67 24.24
April 35.83 26.97 467.00 24.72 35.67 24.87
May 63.67 26.95 508.00 24.83 63.67 25.04
June 70.33 26.67 496.00 24.77 70.33 24.98
July 103.83 26.61 497.00 24.97 103.83 25.21
August 66.33 26.66 514.00 24.73 66.33 24.93
September 69.67 26.50 485.00 24.77 69.67 24.96
October 38.33 25.30 466.33 24.52 22.33 24.62
November 167.17 22.84 248.67 23.69 1.33 23.70
December 399.17 22.10 62.33 22.23 16.33 22.16
             
Annual Sum or Average 1802.00 23.31 4282.83 24.10 491.00 24.24
Minimum of Months 35.83 21.79 49.17 21.73 0.00 21.60
Maximum of Months 436.33 26.97 514.00 24.97 103.83 25.21



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 43.50 27.00 514.00 27.00 43.50 27.00
April 358.67 27.64 485.00 27.54 358.67 27.57
May 20.50 27.00 508.00 27.00 20.50 27.00
June 122.50 27.00 496.00 27.00 122.50 27.00
July 260.50 27.00 497.00 27.00 260.50 27.00
August 498.17 28.02 514.00 28.00 498.17 28.01
September 17.83 27.00 485.00 27.00 17.83 27.00
October 21.00 27.00 502.00 27.00 21.00 27.00
November 36.00 27.00 489.00 27.00 36.00 27.00
December 31.50 27.00 497.00 27.00 31.50 27.00
             
Annual Sum or Average 1410.17 27.52 5943.00 27.20 1410.17 27.25
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 498.17 28.02 514.00 28.00 498.17 28.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 170.33 28.09 485.00 27.59 170.33 27.69
May 0.00 0.00 508.00 27.00 0.00 27.00
June 1.33 27.00 496.00 27.00 1.33 27.00
July 5.33 27.00 497.00 27.00 5.33 27.00
August 316.50 28.17 514.00 27.93 316.50 28.00
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.33 27.00 502.00 27.00 0.33 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 493.83 28.13 5943.00 27.18 493.83 27.25
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 316.50 28.17 514.00 27.93 316.50 28.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.83 24.51 466.17 26.93 0.00 26.93
February 0.00 0.00 454.00 27.00 0.00 27.00
March 2.50 27.00 514.00 27.00 2.50 27.00
April 156.67 27.92 485.00 27.46 156.67 27.55
May 53.17 27.00 508.00 27.00 53.17 27.00
June 87.33 27.00 496.00 27.00 87.33 27.00
July 76.33 27.00 497.00 27.00 76.33 27.00
August 252.33 28.04 514.00 27.70 252.33 27.79
September 10.33 27.00 485.00 27.00 10.33 27.00
October 7.50 27.00 502.00 27.00 7.50 27.00
November 0.00 0.00 489.00 27.00 0.00 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 659.00 27.57 5907.17 27.12 646.17 27.17
Minimum of Months 0.00 0.00 454.00 26.93 0.00 26.93
Maximum of Months 252.33 28.04 514.00 27.70 252.33 27.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.01 502.00 27.01 502.00 27.01
February 454.00 27.01 454.00 27.01 454.00 27.01
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 29.34 485.00 29.34 485.00 29.34
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 30.47 514.00 30.47 514.00 30.47
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5943.00 27.49 5943.00 27.49 5943.00 27.49
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 30.47 514.00 30.47 514.00 30.47



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00071 29.14523 0.85891 20.60436
February 454.00000 27.00090 29.61821 0.91217 22.60259
March 514.00000 27.00055 31.21559 0.97568 25.13376
April 485.00000 27.47113 32.47454 1.12894 32.13452
May 508.00000 27.00072 37.44610 0.32767 7.27559
June 496.00000 27.00241 37.19085 0.37233 7.92388
July 497.00000 27.00154 36.36942 0.40781 8.50720
August 514.00000 27.98913 34.65545 0.70489 16.26947
September 485.00000 27.00012 40.25516 0.33925 7.42640
October 502.00000 27.00162 33.22764 0.97223 24.99002
November 489.00000 27.00059 30.46599 0.97067 24.93045
December 497.00000 27.00016 28.23959 0.96354 24.64247
           
Annual Sum or Average 5943.00000 27.12477 33.37831 0.74316 18.49417
Minimum of Months 454.00000 27.00012 28.23959 0.32767 7.27559
Maximum of Months 514.00000 27.98913 40.25516 1.12894 32.13452



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00052 29.43100 0.78678 18.10675
February 454.00000 27.00085 29.69843 0.83489 19.75984
March 514.00000 27.00053 31.23166 0.90293 22.25339
April 485.00000 27.41949 32.53262 1.03025 27.70143
May 508.00000 27.00049 37.66225 0.28148 6.68868
June 496.00000 27.00234 37.34897 0.30128 6.92508
July 497.00000 27.00157 36.50456 0.30876 7.01712
August 514.00000 27.78429 34.89705 0.50722 11.08048
September 485.00000 27.00003 40.75350 0.29071 6.78778
October 502.00000 27.00154 33.33068 0.91644 22.76591
November 489.00000 27.00057 30.48908 0.88201 21.46573
December 497.00000 27.00017 28.23392 0.83331 19.71360
           
Annual Sum or Average 5943.00000 27.10278 33.52937 0.65470 15.81096
Minimum of Months 454.00000 27.00003 28.23392 0.28148 6.68868
Maximum of Months 514.00000 27.78429 40.75350 1.03025 27.70143



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.90952 29.93574 0.69573 15.63781
February 454.00000 27.00092 29.19086 0.79022 18.30249
March 514.00000 27.00061 30.59049 0.89239 21.90271
April 485.00000 27.30877 32.04150 1.02255 27.40309
May 508.00000 27.00058 36.98708 0.31333 7.14368
June 496.00000 27.00254 36.65729 0.33437 7.42264
July 497.00000 27.00178 35.80986 0.33588 7.43201
August 514.00000 27.54028 34.33191 0.46534 10.31167
September 485.00000 27.00004 40.06620 0.30103 6.95129
October 502.00000 27.00168 32.70772 0.91099 22.59196
November 489.00000 27.00066 29.86278 0.84932 20.33492
December 497.00000 27.00024 27.68206 0.76249 17.41330
           
Annual Sum or Average 5943.00000 27.06504 33.00889 0.63796 15.19826
Minimum of Months 454.00000 26.90952 27.68206 0.30103 6.95129
Maximum of Months 514.00000 27.54028 40.06620 1.02255 27.40309



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00515 30.03360 1.08599 29.88112
February 454.00000 27.00599 30.19470 1.23106 36.78350
March 514.00000 27.00312 31.01669 1.37177 44.01639
April 485.00000 29.33892 31.10883 1.98122 74.23090
May 508.00000 27.00353 34.96380 0.54657 11.32201
June 496.00000 27.00323 35.08717 0.77472 17.66594
July 497.00000 27.00174 34.48866 0.99034 25.72824
August 514.00000 30.46736 31.89435 2.19856 83.28766
September 485.00000 27.00421 35.51047 0.62243 13.19020
October 502.00000 27.00277 31.99604 1.29172 39.84832
November 489.00000 27.00429 30.63887 1.41227 46.16871
December 497.00000 27.00672 30.05060 1.52564 52.29513
           
Annual Sum or Average 5943.00000 27.49413 32.25933 1.25415 39.61053
Minimum of Months 454.00000 27.00174 30.03360 0.54657 11.32201
Maximum of Months 514.00000 30.46736 35.51047 2.19856 83.28766



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.56104 39.70734 0.50775 11.02737
February 454.00000 24.53484 44.36356 0.53310 11.50062
March 514.00000 24.43228 48.18276 0.53824 11.53423
April 485.00000 24.53135 47.49188 0.55586 12.02171
May 508.00000 24.51168 58.39214 -0.2188 6.99585
June 496.00000 24.48341 62.02988 -0.1886 6.94378
July 497.00000 24.64271 62.63469 -0.1199 7.20800
August 514.00000 24.50093 61.51795 -0.1526 7.08997
September 485.00000 24.57967 62.85375 -0.1348 7.20303
October 502.00000 24.62638 55.71494 0.65778 14.81207
November 489.00000 24.62904 46.95179 0.59337 13.07229
December 497.00000 24.61367 39.80588 0.53125 11.56758
           
Annual Sum or Average 5943.00000 24.55345 52.54068 0.25567 10.06417
Minimum of Months 454.00000 24.43228 39.70734 -0.2188 6.94378
Maximum of Months 514.00000 24.64271 62.85375 0.65778 14.81207



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.40147 42.10830 0.48460 10.59898
February 454.00000 24.34062 45.31433 0.50908 10.72450
March 514.00000 24.25515 48.88469 0.53132 11.12009
April 485.00000 24.19359 48.66040 0.53335 11.09114
May 508.00000 24.17568 54.41140 -0.3120 7.19319
June 496.00000 24.16517 56.19610 -0.2938 6.93491
July 497.00000 24.22666 56.39696 -0.2654 6.66719
August 514.00000 24.19352 56.09823 -0.2566 6.55849
September 485.00000 24.26647 56.79420 -0.2704 6.86619
October 502.00000 24.33186 54.08615 0.58923 12.52038
November 489.00000 24.39059 47.87201 0.55757 11.83030
December 497.00000 24.40183 40.71229 0.49985 10.58248
           
Annual Sum or Average 5943.00000 24.27781 50.67407 0.18911 9.37622
Minimum of Months 454.00000 24.16517 40.71229 -0.3120 6.55849
Maximum of Months 514.00000 24.40183 56.79420 0.58923 12.52038



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.02710 43.11083 0.37218 8.21850
February 454.00000 24.11577 45.73816 0.42764 9.13580
March 514.00000 24.18708 48.98921 0.48760 10.18152
April 485.00000 24.15363 48.98100 0.48744 10.12498
May 508.00000 24.10381 54.81589 -0.3627 7.91011
June 496.00000 24.11934 56.86771 -0.3431 7.63393
July 497.00000 24.13863 57.58313 -0.3363 7.56042
August 514.00000 24.16708 57.63722 -0.3240 7.41248
September 485.00000 24.25468 57.15718 -0.3038 7.32054
October 502.00000 24.27808 54.45433 0.55210 11.60014
November 489.00000 24.20822 48.24068 0.48207 10.08765
December 497.00000 24.03104 41.71322 0.37256 8.13141
           
Annual Sum or Average 5943.00000 24.14873 51.32402 0.12292 8.77292
Minimum of Months 454.00000 24.02710 41.71322 -0.3627 7.32054
Maximum of Months 514.00000 24.27808 57.63722 0.55210 11.60014



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.77742 46.88115 0.05209 6.52087
February 454.00000 23.56888 47.76877 0.28673 7.58404
March 514.00000 24.08143 49.69578 0.46588 9.81152
April 485.00000 24.20482 49.11951 0.51898 10.82835
May 508.00000 24.20911 54.36190 -0.2899 7.01823
June 496.00000 24.20856 56.28439 -0.2737 6.86705
July 497.00000 24.24719 57.05150 -0.2688 6.79954
August 514.00000 24.21900 57.40377 -0.2797 6.90075
September 485.00000 24.28357 57.28199 -0.2750 7.03080
October 502.00000 24.20678 55.37613 0.54425 11.37517
November 489.00000 23.85915 50.04552 0.39343 8.65155
December 497.00000 23.10844 44.90609 0.13586 6.52033
           
Annual Sum or Average 5943.00000 23.91691 52.22146 0.08192 7.99271
Minimum of Months 454.00000 22.77742 44.90609 -0.2899 6.52033
Maximum of Months 514.00000 24.28357 57.40377 0.54425 11.37517



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.55093 42.88036 0.23768 6.79758
February 454.00000 23.92665 45.75302 0.37560 8.38070
March 514.00000 24.20636 48.21460 0.50564 10.60005
April 485.00000 24.37755 47.23442 0.59876 12.98254
May 508.00000 24.46712 52.60502 -0.1413 6.39463
June 496.00000 24.40631 54.63001 -0.1286 6.18948
July 497.00000 24.53331 55.08557 -0.0922 6.53482
August 514.00000 24.38506 55.03714 -0.1352 6.31543
September 485.00000 24.43021 55.91536 -0.1782 6.56361
October 502.00000 24.36893 53.19700 0.59445 12.73781
November 489.00000 24.18271 47.85865 0.47429 9.92002
December 497.00000 23.83517 41.67535 0.31702 7.46896
           
Annual Sum or Average 5943.00000 24.22439 50.04453 0.20037 8.39900
Minimum of Months 454.00000 23.55093 41.67535 -0.1782 6.18948
Maximum of Months 514.00000 24.53331 55.91536 0.59876 12.98254



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.67624 42.18539 0.28556 7.33282
February 454.00000 23.99037 45.35738 0.41550 9.21731
March 514.00000 24.23289 47.93772 0.54202 11.64247
April 485.00000 24.39047 47.01640 0.63795 14.22262
May 508.00000 24.49962 52.33623 -0.0699 6.47138
June 496.00000 24.38931 54.56145 -0.1049 6.17311
July 497.00000 24.48551 55.19830 -0.0986 6.61749
August 514.00000 24.30886 55.31797 -0.1668 6.43092
September 485.00000 24.42276 55.78896 -0.1532 6.44323
October 502.00000 24.42610 52.79207 0.63380 14.01826
November 489.00000 24.19666 47.59011 0.50027 10.69409
December 497.00000 23.75871 41.67510 0.31508 7.66457
           
Annual Sum or Average 5943.00000 24.23293 49.85224 0.22594 8.89996
Minimum of Months 454.00000 23.67624 41.67510 -0.1668 6.17311
Maximum of Months 514.00000 24.49962 55.78896 0.63795 14.22262



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.93579 41.29494 0.37853 8.89064
February 454.00000 24.22990 44.55587 0.50353 11.19994
March 514.00000 24.34952 47.48049 0.59521 13.02734
April 485.00000 24.45193 46.87551 0.64985 14.51946
May 508.00000 24.48287 52.52282 -0.1246 6.41412
June 496.00000 24.40709 54.62688 -0.1292 6.22575
July 497.00000 24.53415 55.07765 -0.0907 6.56067
August 514.00000 24.39690 54.95805 -0.1216 6.33864
September 485.00000 24.48572 55.58024 -0.1169 6.46789
October 502.00000 24.57569 52.15848 0.71599 16.65329
November 489.00000 24.51010 46.34825 0.64127 14.52075
December 497.00000 24.23486 40.19154 0.47305 10.58929
           
Annual Sum or Average 5943.00000 24.38338 49.34815 0.27867 10.09782
Minimum of Months 454.00000 23.93579 40.19154 -0.1292 6.22575
Maximum of Months 514.00000 24.57569 55.58024 0.71599 16.65329



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.04019 40.87680 0.39812 8.93999
February 454.00000 24.40602 43.90695 0.55918 12.19112
March 514.00000 24.49517 46.95651 0.68343 15.52322
April 485.00000 24.63601 46.17971 0.80978 19.77065
May 508.00000 24.56470 52.07667 0.00839 6.61723
June 496.00000 24.51933 53.98877 0.04193 6.54263
July 497.00000 24.66754 54.27609 0.08078 7.24744
August 514.00000 24.56207 54.06422 0.10491 7.05860
September 485.00000 24.53963 55.18608 -0.0458 6.41114
October 502.00000 24.61133 52.04635 0.73978 17.32306
November 489.00000 24.60484 46.08279 0.67173 15.25144
December 497.00000 24.55449 39.18633 0.57854 12.71004
           
Annual Sum or Average 5943.00000 24.51701 48.77788 0.38399 11.27504
Minimum of Months 454.00000 24.04019 39.18633 -0.0458 6.41114
Maximum of Months 514.00000 24.66754 55.18608 0.80978 19.77065



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.51378 45.18269 -0.0201 6.00647
February 454.00000 23.29610 47.11971 0.20538 6.85928
March 514.00000 24.04139 48.45849 0.43988 9.40873
April 485.00000 24.38201 47.20870 0.56644 12.14264
May 508.00000 24.48532 52.79450 -0.1516 6.54155
June 496.00000 24.42860 55.42917 -0.1407 6.34723
July 497.00000 24.56928 56.83642 -0.1047 6.74439
August 514.00000 24.42077 56.95916 -0.1662 6.59198
September 485.00000 24.46220 57.08208 -0.1839 6.86098
October 502.00000 24.29964 53.52107 0.55503 11.75865
November 489.00000 23.73196 48.95492 0.34164 7.87886
December 497.00000 22.76568 44.16325 0.04215 6.04426
           
Annual Sum or Average 5943.00000 23.95445 51.17880 0.11395 7.76601
Minimum of Months 454.00000 22.51378 44.16325 -0.1839 6.00647
Maximum of Months 514.00000 24.56928 57.08208 0.56644 12.14264



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.88600 43.32844 0.07921 6.02386
February 385.00000 23.63114 45.31012 0.30387 7.93321
March 433.00000 24.26368 46.95669 0.52106 11.41537
April 410.00000 24.60802 45.80578 0.66003 15.08356
May 430.00000 24.63535 52.07312 -0.0469 6.86410
June 418.00000 24.53872 54.94180 -0.0759 6.48730
July 422.00000 24.68821 56.40809 -0.0509 7.07319
August 433.00000 24.51752 56.55582 -0.1238 6.70445
September 410.00000 24.58086 56.68080 -0.1217 6.85315
October 427.00000 24.53311 52.48502 0.63532 14.28307
November 417.00000 24.01623 47.43757 0.43092 9.55837
December 422.00000 23.12464 42.48607 0.14014 6.37523
           
Annual Sum or Average 5034.00000 24.17120 50.07332 0.19473 8.71864
Minimum of Months 385.00000 22.88600 42.48607 -0.1238 6.02386
Maximum of Months 433.00000 24.68821 56.68080 0.66003 15.08356



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.75404 41.25971 0.32923 8.45034
February 454.00000 24.09124 44.38437 0.45577 10.55675
March 514.00000 24.31467 47.22131 0.56800 12.45449
April 485.00000 24.49105 46.71987 0.63014 14.00551
May 508.00000 24.49796 52.71432 -0.1365 6.53250
June 496.00000 24.42500 55.44246 -0.1440 6.36562
July 497.00000 24.56907 56.81794 -0.1030 6.75462
August 514.00000 24.43954 56.79718 -0.1472 6.59644
September 485.00000 24.52870 56.60612 -0.1147 6.75979
October 502.00000 24.60609 52.05846 0.71075 16.59531
November 489.00000 24.45484 45.99618 0.61240 13.89717
December 497.00000 24.03083 40.23667 0.40470 9.74738
           
Annual Sum or Average 5943.00000 24.35147 49.73607 0.25306 9.87752
Minimum of Months 454.00000 23.75404 40.23667 -0.1472 6.36562
Maximum of Months 514.00000 24.60609 56.81794 0.71075 16.59531



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.96793 43.33847 0.11136 6.32834
February 454.00000 23.65406 45.65170 0.32209 8.27236
March 514.00000 24.23564 47.54137 0.53910 11.68457
April 485.00000 24.53641 46.58593 0.67596 15.40776
May 508.00000 24.56050 52.37380 -0.0453 6.72655
June 496.00000 24.49229 54.99258 -0.0451 6.48738
July 497.00000 24.61881 56.30901 -0.0416 6.97627
August 514.00000 24.48123 56.40628 -0.0954 6.59810
September 485.00000 24.53784 56.46562 -0.1047 6.77787
October 502.00000 24.47228 52.70118 0.64311 14.35447
November 489.00000 24.06673 47.45414 0.46255 10.06637
December 497.00000 23.27338 42.21103 0.18895 6.74524
           
Annual Sum or Average 5943.00000 24.16143 50.21010 0.21608 8.86297
Minimum of Months 454.00000 22.96793 42.21103 -0.1047 6.32834
Maximum of Months 514.00000 24.61881 56.46562 0.67596 15.40776



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.42057 47.92334 -0.3020 8.86892
February 454.00000 22.62401 49.00561 0.04024 6.88321
March 514.00000 23.85289 49.27673 0.40039 9.13037
April 485.00000 24.38216 47.61673 0.58733 12.82406
May 508.00000 24.50504 52.74094 -0.1058 6.58010
June 496.00000 24.45174 55.26447 -0.0935 6.38113
July 497.00000 24.59057 56.75548 -0.0637 6.90170
August 514.00000 24.43307 56.97925 -0.1343 6.57420
September 485.00000 24.46228 57.34780 -0.1641 6.84501
October 502.00000 24.18366 54.58180 0.53834 11.53088
November 489.00000 23.24821 50.88118 0.22737 7.24608
December 497.00000 21.76944 46.66681 -0.2077 7.71288
           
Annual Sum or Average 5943.00000 23.66803 52.11423 0.05976 8.12583
Minimum of Months 454.00000 21.42057 46.66681 -0.3020 6.38113
Maximum of Months 514.00000 24.59057 57.34780 0.58733 12.82406



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.97123 46.25283 -0.1522 7.44662
February 454.00000 23.18655 47.12652 0.19889 7.50000
March 514.00000 24.11810 48.13744 0.50911 11.32785
April 485.00000 24.51461 46.98742 0.68359 15.73128
May 508.00000 24.55605 52.36984 -0.0074 6.84165
June 496.00000 24.47514 54.98271 -0.0343 6.46438
July 497.00000 24.60552 56.47619 -0.0260 7.10284
August 514.00000 24.44907 56.70153 -0.1001 6.59093
September 485.00000 24.49094 56.94990 -0.1108 6.73508
October 502.00000 24.38373 53.59605 0.62706 14.05982
November 489.00000 23.70160 49.05988 0.36435 8.85216
December 497.00000 22.38727 44.83489 -0.0452 6.82473
           
Annual Sum or Average 5943.00000 23.90842 51.15827 0.15795 8.79022
Minimum of Months 454.00000 21.97123 44.83489 -0.1522 6.46438
Maximum of Months 514.00000 24.60552 56.94990 0.68359 15.73128



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.96873 43.48811 0.11481 8.17877
February 454.00000 23.67934 45.67733 0.34596 9.70050
March 514.00000 24.20951 47.84662 0.54805 12.30400
April 485.00000 24.48932 47.16929 0.65255 14.75504
May 508.00000 24.51635 52.67579 -0.0907 6.60483
June 496.00000 24.44903 55.27642 -0.0965 6.39883
July 497.00000 24.59014 56.74451 -0.0621 6.91692
August 514.00000 24.45165 56.83239 -0.1149 6.61261
September 485.00000 24.52982 56.89106 -0.0928 6.83532
October 502.00000 24.55203 52.95640 0.70998 16.66961
November 489.00000 24.24762 47.19070 0.55823 13.04137
December 497.00000 23.42871 41.98496 0.23918 8.71649
           
Annual Sum or Average 5943.00000 24.17894 50.43718 0.22416 9.71706
Minimum of Months 454.00000 22.96873 41.98496 -0.1149 6.39883
Maximum of Months 514.00000 24.59014 56.89106 0.70998 16.66961



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.08048 45.65236 -0.1169 7.48439
February 454.00000 23.10424 47.22398 0.18768 7.73896
March 514.00000 24.08872 48.24952 0.51039 11.42908
April 485.00000 24.52639 47.05557 0.69544 16.10305
May 508.00000 24.56391 52.40388 -0.0050 6.95680
June 496.00000 24.49686 54.91719 -0.0038 6.66703
July 497.00000 24.62219 56.31954 -0.0070 7.18750
August 514.00000 24.47744 56.51300 -0.0703 6.64415
September 485.00000 24.52255 56.79154 -0.0887 6.82919
October 502.00000 24.37213 53.71143 0.63165 14.16144
November 489.00000 23.69307 49.03510 0.37511 9.16423
December 497.00000 22.47465 44.29750 -0.0115 6.98787
           
Annual Sum or Average 5943.00000 23.92432 51.04813 0.17398 8.94478
Minimum of Months 454.00000 22.08048 44.29750 -0.1169 6.64415
Maximum of Months 514.00000 24.62219 56.79154 0.69544 16.10305



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.779983E+11 102601.76 12-JAN-14:10 423.63 0.457442E+12 0.00 0.535441E+12 3.08 7.25 25-JAN-15:30 0.00 0.00
February 0.934064E+11 109042.94 24-FEB-16:40 424.89 0.575441E+12 0.00 0.668847E+12 3.64 7.42 25-FEB-06:03 0.00 0.00
March 0.146362E+12 142048.25 14-MAR-05:02 579.64 0.955352E+12 0.00 0.110171E+13 4.75 7.67 14-MAR-05:02 0.00 0.00
April 0.189547E+12 194431.18 17-APR-05:03 671.62 0.125994E+13 0.00 0.144949E+13 5.81 7.71 24-APR-05:03 0.00 0.00
May 0.242892E+12 207213.35 25-MAY-05:03 687.74 0.161286E+13 0.00 0.185575E+13 5.96 7.58 13-MAY-05:03 0.00 0.00
June 0.260873E+12 228724.68 27-JUN-05:04 666.68 0.169905E+13 0.00 0.195992E+13 5.85 7.50 02-JUN-05:02 0.00 0.00
July 0.285848E+12 229671.88 18-JUL-05:04 710.24 0.181050E+13 0.00 0.209635E+13 5.79 7.02 01-JUL-05:03 0.00 0.00
August 0.281490E+12 226767.02 14-AUG-05:03 706.66 0.178552E+13 0.00 0.206701E+13 5.71 7.25 16-AUG-03:02 0.00 0.00
September 0.221318E+12 218466.06 13-SEP-05:03 607.69 0.142774E+13 0.00 0.164906E+13 5.18 7.49 27-SEP-05:02 0.00 0.00
October 0.169379E+12 197763.29 04-OCT-05:02 594.51 0.113038E+13 0.00 0.129975E+13 5.02 7.80 19-OCT-05:02 0.00 0.00
November 0.123512E+12 119908.57 10-NOV-06:04 515.72 0.786963E+12 0.00 0.910475E+12 4.27 7.71 10-NOV-06:04 0.00 0.00
December 0.914255E+11 107996.48 01-DEC-14:30 475.59 0.549056E+12 0.00 0.640482E+12 3.52 7.38 07-DEC-15:50 0.00 0.00
                         
Annual Sum or Average 0.218405E+13     7064.62 0.140503E+14 0.00 0.162343E+14 4.89     0.00 0.00
Minimum of Months 0.779983E+11 102601.76   423.63 0.457442E+12 0.00 0.535441E+12 3.08 7.02   0.00 0.00
Maximum of Months 0.285848E+12 229671.88   710.24 0.181050E+13 0.00 0.209635E+13 5.96 7.80   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.129122E+11 142048.25 14-MAR-05:02 33.52 0.918345E+11 0.00 0.104747E+12 0.32 7.67 14-MAR-05:02 0.00 0.00
April 0.568678E+11 194431.18 17-APR-05:03 141.06 0.402128E+12 0.00 0.458996E+12 1.39 7.71 24-APR-05:03 0.00 0.00
May 0.113365E+12 207213.35 25-MAY-05:03 255.73 0.779370E+12 0.00 0.892735E+12 2.36 7.58 13-MAY-05:03 0.00 0.00
June 0.152057E+12 228724.68 27-JUN-05:04 316.05 0.101475E+13 0.00 0.116681E+13 2.93 7.50 02-JUN-05:02 0.00 0.00
July 0.187984E+12 229671.88 18-JUL-05:04 379.18 0.122876E+13 0.00 0.141675E+13 3.33 7.02 01-JUL-05:03 0.00 0.00
August 0.198938E+12 226767.02 14-AUG-05:03 396.15 0.129893E+13 0.00 0.149787E+13 3.48 7.25 16-AUG-03:02 0.00 0.00
September 0.125038E+12 218466.06 13-SEP-05:03 268.60 0.834807E+12 0.00 0.959845E+12 2.49 7.49 27-SEP-05:02 0.00 0.00
October 0.485135E+11 197763.29 04-OCT-05:02 121.03 0.342262E+12 0.00 0.390776E+12 1.15 7.80 19-OCT-05:02 0.00 0.00
November 0.239966E+10 119908.57 10-NOV-06:04 6.33 0.171441E+11 0.00 0.195437E+11 0.06 7.71 10-NOV-06:04 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.898076E+12     1917.64 0.600999E+13 0.00 0.690806E+13 1.47     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.198938E+12 229671.88   396.15 0.129893E+13 0.00 0.149787E+13 3.48 7.80   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.661162E+11 744.00 49248.27 02-JAN-13:30 213681.58 12-JAN-17:00 22.67 19.06 14.67
February 0.101046E+12 672.00 49248.27 01-FEB-10:20 377518.32 24-FEB-16:10 28.02 21.40 14.67
March 0.131866E+12 744.00 49248.27 01-MAR-00:10 649395.19 31-MAR-24:00 36.93 27.16 14.67
April 0.127652E+12 720.00 49248.27 01-APR-00:03 720260.12 16-APR-17:31 48.57 35.61 14.67
May 0.131907E+12 744.00 49248.27 01-MAY-00:05 379848.41 31-MAY-23:20 39.84 35.25 14.67
June 0.127652E+12 720.00 49248.27 01-JUN-00:10 557927.11 30-JUN-23:25 45.33 37.49 14.67
July 0.131907E+12 744.00 49248.27 01-JUL-00:05 688331.62 31-JUL-24:00 48.00 37.11 14.67
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 720865.23 25-AUG-14:30 50.10 36.73 14.67
September 0.127652E+12 720.00 49248.27 01-SEP-00:03 376069.05 30-SEP-23:17 35.69 31.03 14.67
October 0.131907E+12 744.00 49248.27 01-OCT-00:03 487035.78 31-OCT-23:40 35.78 28.60 14.67
November 0.125489E+12 720.00 49248.27 01-NOV-00:10 548808.77 08-NOV-16:10 34.17 24.51 14.67
December 0.121918E+12 744.00 49248.27 01-DEC-07:00 669230.44 28-DEC-16:30 33.56 21.41 14.67
                   
Annual Sum or Average 0.145702E+13 8760.00         38.28 29.65 14.67
Minimum of Months 0.661162E+11 672.00 49248.27   213681.58   22.67 19.06 14.67
Maximum of Months 0.131907E+12 744.00 49248.27   720865.23   50.10 37.49 14.67



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.330686E+09 298.79 1202.13 13-JAN-15:00 1084391.75 25-JAN-16:10 21.94 21.24 35.69
February 0.784495E+09 354.47 3879.22 24-FEB-15:30 1223385.09 22-FEB-15:30 22.39 21.36 42.86
March 0.719269E+10 511.22 21281.92 06-MAR-13:00 1347195.03 08-MAR-14:40 22.90 21.29 54.31
April 0.226450E+11 618.99 21281.92 01-APR-09:10 1366496.07 10-APR-15:30 23.68 21.60 66.06
May 0.471156E+11 686.93 21281.92 01-MAY-04:04 1367652.61 18-MAY-05:04 26.16 23.78 65.61
June 0.508582E+11 666.68 21281.92 01-JUN-00:23 1505420.71 27-JUN-05:04 28.38 25.78 60.95
July 0.544152E+11 710.24 21281.92 01-JUL-00:05 1498658.13 18-JUL-05:04 30.10 27.38 58.42
August 0.541408E+11 706.66 21281.92 01-AUG-00:13 1428457.20 09-AUG-05:03 29.94 27.26 60.79
September 0.464812E+11 607.69 21281.92 01-SEP-00:03 1453080.91 06-SEP-05:04 28.32 26.10 54.21
October 0.228882E+11 572.24 21281.92 01-OCT-00:53 1400116.52 20-OCT-05:04 23.51 21.75 57.48
November 0.301350E+10 443.43 21281.92 06-NOV-10:40 1337284.10 01-NOV-15:20 22.73 21.30 49.00
December 0.444101E+09 339.29 1515.80 28-DEC-15:00 1128014.71 01-DEC-16:00 22.07 21.22 41.10
                   
Annual Sum or Average 0.310310E+12 6516.64         25.19 23.35 53.92
Minimum of Months 0.330686E+09 298.79 1202.13   1084391.75   21.94 21.22 35.69
Maximum of Months 0.544152E+11 710.24 21281.92   1505420.71   30.10 27.38 66.06



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10 21.94 21.94 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 22.39 22.39 0.00
March 0.151322E+10 20.40 21281.92 06-MAR-14:30 1337175.98 14-MAR-05:04 22.90 22.80 1.98
April 0.777715E+10 105.05 21281.92 03-APR-05:03 1366496.07 10-APR-15:30 23.68 23.20 10.53
May 0.224537E+11 293.10 21281.92 01-MAY-05:03 1367652.61 18-MAY-05:04 26.16 24.90 27.27
June 0.347117E+11 453.07 21281.92 01-JUN-04:03 1505420.71 27-JUN-05:04 28.38 26.35 39.53
July 0.460146E+11 600.60 21281.92 01-JUL-00:10 1498658.13 18-JUL-05:04 30.10 27.54 47.78
August 0.429609E+11 560.74 21281.92 01-AUG-00:57 1428457.20 09-AUG-05:03 29.94 27.45 46.64
September 0.317588E+11 414.53 21281.92 01-SEP-00:07 1453080.91 06-SEP-05:04 28.32 26.51 34.84
October 0.742346E+10 97.13 21281.92 02-OCT-08:70 1400116.52 20-OCT-05:04 23.51 23.10 9.42
November 98731013.26 2.53 21281.92 06-NOV-11:20 1321576.11 01-NOV-14:40 22.73 22.71 0.25
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 22.07 22.07 0.00
                   
Annual Sum or Average 0.194712E+12 2547.14         25.19 24.26 18.30
Minimum of Months 0.00 0.00 0.00   0.00   21.94 21.94 0.00
Maximum of Months 0.460146E+11 600.60 21281.92   1505420.71   30.10 27.54 47.78



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.880845E+10 0.00 146.56 207559.90 02-JAN-06:13 0.00 30.50 40.21 0.02 0.00 0.00 0.15 02-JAN-06:13
February 0.763173E+09 0.00 39.57 113461.85 11-FEB-06:02 0.00 25.57 28.68 0.00 0.00 0.00 0.08 11-FEB-06:02
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 24.47 24.47 0.00 0.00 0.00 0.00 01-MAR-00:10
April 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 24.47 24.47 0.00 0.00 0.00 0.00 01-APR-00:03
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 24.47 24.47 0.00 0.00 0.00 0.00 01-MAY-00:05
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 24.47 24.47 0.00 0.00 0.00 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 01-JUL-00:05 0.00 24.47 24.47 0.00 0.00 0.00 0.00 01-JUL-00:05
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 24.47 24.47 0.00 0.00 0.00 0.00 01-AUG-00:03
September 5935.83 0.00 0.17 9.89 25-SEP-10:20 0.00 24.47 24.48 0.00 0.00 0.00 0.00 25-SEP-10:20
October 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 24.47 24.47 0.00 0.00 0.00 0.00 01-OCT-00:03
November 27612496.95 0.00 7.04 2741.34 27-NOV-06:05 0.00 24.34 24.88 0.00 0.00 0.00 0.00 27-NOV-06:05
December 0.237810E+10 0.00 95.28 99383.19 23-DEC-06:03 0.00 25.60 32.32 0.00 0.00 0.00 0.07 23-DEC-06:03
                           
Annual Sum or Average 0.119773E+11 0.00 288.61     0.00 25.15 26.83 0.00 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 24.34 24.47 0.00 0.00 0.00 0.00  
Maximum of Months 0.880845E+10 0.00 146.56 207559.90   0.00 30.50 40.21 0.02 0.00 0.00 0.15  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:10 0.00 22.67 22.67 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 28.02 28.02 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 36.93 36.93 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:03 0.00 48.57 48.57 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 39.84 39.84 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 45.33 45.33 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:05 0.00 48.00 48.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 50.10 50.10 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 35.69 35.69 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:03 0.00 35.78 35.78 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 34.17 34.17 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 33.56 33.56 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 38.28 38.28 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 22.67 22.67 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 50.10 50.10 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.453706E+11 0.00 394.26 0.452951E+11 0.00 0.00 0.00 0.00 86484.70 18-JAN-06:03 81305.58 14-JAN-06:02 0.00 0.00 0.00
February 0.643314E+11 0.00 410.32 0.642073E+11 0.00 0.00 0.00 0.00 103576.57 21-FEB-16:00 103576.57 21-FEB-16:00 0.00 0.00 0.00
March 0.120624E+12 0.00 558.15 0.118666E+12 0.00 0.00 0.00 0.00 200178.88 29-MAR-05:03 149364.99 28-MAR-05:02 0.00 0.00 0.00
April 0.177620E+12 0.00 628.83 0.170685E+12 0.00 0.00 0.00 0.00 249997.83 17-APR-05:03 177804.91 28-APR-05:03 0.00 0.00 0.00
May 0.217423E+12 0.00 625.36 0.184253E+12 0.00 0.00 0.00 0.00 277208.69 22-MAY-05:02 192132.13 01-MAY-05:03 0.00 0.00 0.00
June 0.256762E+12 0.00 619.61 0.189662E+12 0.00 0.00 0.00 0.00 287729.18 26-JUN-05:02 196605.67 12-JUN-05:03 0.00 0.00 0.00
July 0.297209E+12 0.00 645.49 0.183584E+12 0.00 0.00 0.00 0.00 299718.20 31-JUL-05:03 188075.24 05-JUL-05:02 0.00 0.00 0.00
August 0.318655E+12 0.00 659.77 0.194049E+12 0.00 0.00 0.00 0.00 315682.45 28-AUG-05:04 184718.35 07-AUG-05:03 0.00 0.00 0.00
September 0.221857E+12 0.00 554.60 0.141278E+12 0.00 0.00 0.00 0.00 283436.53 05-SEP-05:02 171401.17 18-SEP-05:02 0.00 0.00 0.00
October 0.148554E+12 0.00 557.07 0.131722E+12 0.00 0.00 0.00 0.00 253426.05 04-OCT-05:02 165376.78 04-OCT-05:02 0.00 0.00 0.00
November 0.990074E+11 0.00 485.97 0.977505E+11 0.00 0.00 0.00 0.00 170716.22 10-NOV-06:02 132002.40 06-NOV-06:02 0.00 0.00 0.00
December 0.660829E+11 0.00 455.09 0.660829E+11 0.00 0.00 0.00 0.00 101627.38 29-DEC-06:02 101627.38 29-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.203350E+13 0.00 6594.52 0.158723E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.453706E+11 0.00 394.26 0.452951E+11 0.00 0.00 0.00 0.00 86484.70   81305.58   0.00 0.00 0.00
Maximum of Months 0.318655E+12 0.00 659.77 0.194049E+12 0.00 0.00 0.00 0.00 315682.45   196605.67   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.316074E+12 0.00 364.15 0.315985E+12 0.00 0.00 0.00 0.00 826637.85 18-JAN-06:03 691505.87 14-JAN-06:02 0.00 0.00 0.00
February 0.466977E+12 0.00 376.96 0.465988E+12 0.00 0.00 0.00 0.00 1273675.58 25-FEB-06:03 863622.00 25-FEB-06:03 0.00 0.00 0.00
March 0.922597E+12 0.00 474.76 0.908900E+12 0.00 0.00 0.00 0.00 1917600.85 14-MAR-05:02 1458699.03 29-MAR-05:03 0.00 0.00 0.00
April 0.137792E+13 0.00 527.95 0.132672E+13 0.00 0.00 0.00 0.00 2302218.55 26-APR-05:02 1563709.22 28-APR-05:02 0.00 0.00 0.00
May 0.199934E+13 0.00 599.75 0.168166E+13 0.00 0.00 0.00 0.00 2723695.48 24-MAY-03:02 1645073.61 05-MAY-05:02 0.00 0.00 0.00
June 0.227613E+13 0.00 575.02 0.165161E+13 0.00 0.00 0.00 0.00 2847278.10 26-JUN-05:02 1737234.01 12-JUN-05:02 0.00 0.00 0.00
July 0.250696E+13 0.00 572.18 0.147927E+13 0.00 0.00 0.00 0.00 2980871.43 27-JUL-03:02 1638125.55 06-JUL-05:02 0.00 0.00 0.00
August 0.247813E+13 0.00 554.50 0.141234E+13 0.00 0.00 0.00 0.00 2892133.00 10-AUG-05:02 1628675.43 02-AUG-05:02 0.00 0.00 0.00
September 0.192020E+13 0.00 487.17 0.120040E+13 0.00 0.00 0.00 0.00 2862700.79 09-SEP-05:03 1597641.34 05-SEP-05:02 0.00 0.00 0.00
October 0.121278E+13 0.00 482.72 0.106898E+13 0.00 0.00 0.00 0.00 2437777.84 12-OCT-05:02 1566354.03 04-OCT-05:02 0.00 0.00 0.00
November 0.725332E+12 0.00 430.63 0.716076E+12 0.00 0.00 0.00 0.00 1662271.15 09-NOV-06:02 1130449.78 09-NOV-06:02 0.00 0.00 0.00
December 0.384513E+12 0.00 401.98 0.384513E+12 0.00 0.00 0.00 0.00 736826.41 29-DEC-06:02 736826.41 29-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.165870E+14 0.00 5847.78 0.126124E+14 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.316074E+12 0.00 364.15 0.315985E+12 0.00 0.00 0.00 0.00 736826.41   691505.87   0.00 0.00 0.00
Maximum of Months 0.250696E+13 0.00 599.75 0.168166E+13 0.00 0.00 0.00 0.00 2980871.43   1737234.01   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.232183E+11 0.00 330.84 0.232183E+11 0.00 0.00 0.00 0.00 59605.80 12-JAN-15:00 59605.80 12-JAN-15:00 0.00 0.00 0.00
February 0.412320E+11 0.00 352.04 0.411399E+11 0.00 0.00 0.00 0.00 111329.74 25-FEB-06:03 95680.46 22-FEB-15:00 0.00 0.00 0.00
March 0.949783E+11 0.00 459.81 0.936886E+11 0.00 0.00 0.00 0.00 198865.85 14-MAR-05:02 148160.20 14-MAR-05:02 0.00 0.00 0.00
April 0.156239E+12 0.00 533.79 0.150929E+12 0.00 0.00 0.00 0.00 248592.61 17-APR-05:02 173491.03 28-APR-05:02 0.00 0.00 0.00
May 0.229640E+12 0.00 612.59 0.196709E+12 0.00 0.00 0.00 0.00 294419.81 24-MAY-05:02 192890.04 30-MAY-04:12 0.00 0.00 0.00
June 0.258883E+12 0.00 585.68 0.194715E+12 0.00 0.00 0.00 0.00 307109.39 22-JUN-05:02 212859.37 12-JUN-05:03 0.00 0.00 0.00
July 0.276720E+12 0.00 587.70 0.170914E+12 0.00 0.00 0.00 0.00 342673.02 25-JUL-03:02 202166.31 05-JUL-04:02 0.00 0.00 0.00
August 0.269569E+12 0.00 568.08 0.160250E+12 0.00 0.00 0.00 0.00 322552.24 10-AUG-05:02 190612.73 07-AUG-05:03 0.00 0.00 0.00
September 0.207122E+12 0.00 502.94 0.132844E+12 0.00 0.00 0.00 0.00 313339.76 08-SEP-05:02 179529.59 05-SEP-05:02 0.00 0.00 0.00
October 0.125099E+12 0.00 476.93 0.111623E+12 0.00 0.00 0.00 0.00 249817.80 04-OCT-05:02 163803.78 04-OCT-05:02 0.00 0.00 0.00
November 0.673464E+11 0.00 406.88 0.669089E+11 0.00 0.00 0.00 0.00 152748.17 09-NOV-06:02 107643.09 09-NOV-14:50 0.00 0.00 0.00
December 0.288834E+11 0.00 365.13 0.288834E+11 0.00 0.00 0.00 0.00 67394.81 01-DEC-15:00 67394.81 01-DEC-15:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.177893E+13 0.00 5782.40 0.137182E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.232183E+11 0.00 330.84 0.232183E+11 0.00 0.00 0.00 0.00 59605.80   59605.80   0.00 0.00 0.00
Maximum of Months 0.276720E+12 0.00 612.59 0.196709E+12 0.00 0.00 0.00 0.00 342673.02   212859.37   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.508292E+11 0.00 400.75 0.507519E+11 0.00 0.00 0.00 0.00 98805.55 17-JAN-04:02 85660.86 17-JAN-04:02 0.00 0.00 0.00
February 0.523339E+11 0.00 372.33 0.522820E+11 0.00 0.00 0.00 0.00 116353.47 27-FEB-04:02 92250.81 06-FEB-04:03 0.00 0.00 0.00
March 0.727924E+11 0.00 442.59 0.725662E+11 0.00 0.00 0.00 0.00 135638.78 13-MAR-03:02 94169.09 13-MAR-03:02 0.00 0.00 0.00
April 0.849268E+11 0.00 417.45 0.829803E+11 0.00 0.00 0.00 0.00 158468.71 27-APR-03:02 112826.30 28-APR-03:02 0.00 0.00 0.00
May 0.109000E+12 0.00 448.09 0.968889E+11 0.00 0.00 0.00 0.00 184999.95 22-MAY-03:02 125322.27 29-MAY-16:09 0.00 0.00 0.00
June 0.128552E+12 0.00 450.82 0.100906E+12 0.00 0.00 0.00 0.00 213420.58 26-JUN-03:02 119657.49 04-JUN-18:30 0.00 0.00 0.00
July 0.150085E+12 0.00 463.53 0.100371E+12 0.00 0.00 0.00 0.00 224035.41 30-JUL-19:40 116198.71 04-JUL-19:50 0.00 0.00 0.00
August 0.168700E+12 0.00 500.84 0.109043E+12 0.00 0.00 0.00 0.00 240745.28 27-AUG-14:59 105262.05 06-AUG-16:17 0.00 0.00 0.00
September 0.132492E+12 0.00 461.39 0.931082E+11 0.00 0.00 0.00 0.00 217368.28 17-SEP-20:17 103850.85 24-SEP-12:42 0.00 0.00 0.00
October 0.951481E+11 0.00 471.64 0.883773E+11 0.00 0.00 0.00 0.00 166534.52 04-OCT-03:02 115586.04 01-OCT-15:41 0.00 0.00 0.00
November 0.728296E+11 0.00 434.41 0.725483E+11 0.00 0.00 0.00 0.00 121054.96 09-NOV-06:02 113349.96 05-NOV-13:48 0.00 0.00 0.00
December 0.582386E+11 0.00 410.56 0.582313E+11 0.00 0.00 0.00 0.00 92460.77 29-DEC-04:02 88388.53 29-DEC-04:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.117593E+13 0.00 5274.39 0.978054E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.508292E+11 0.00 372.33 0.507519E+11 0.00 0.00 0.00 0.00 92460.77   85660.86   0.00 0.00 0.00
Maximum of Months 0.168700E+12 0.00 500.84 0.109043E+12 0.00 0.00 0.00 0.00 240745.28   125322.27   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.337411E+12 0.874060E+11 744.00 0.323791E+12 0.136203E+11 0.00 0.35 12-JAN-16:00 0.32 22-JAN-06:00 131369.15 17-JAN-15:00 127093.53 12-JAN-15:00 6384.37 17-JAN-15:00 41117.70 12-JAN-15:00 0.00
February 0.532790E+12 0.141624E+12 672.00 0.515874E+12 0.169161E+11 0.00 0.60 22-FEB-15:00 0.53 01-FEB-00:10 225101.03 24-FEB-17:00 219749.13 22-FEB-15:00 10336.41 27-FEB-09:40 77474.54 22-FEB-15:00 0.00
March 0.835439E+12 0.253971E+12 744.00 0.821376E+12 0.140632E+11 0.00 0.98 31-MAR-24:00 0.74 01-MAR-02:00 395738.57 31-MAR-24:00 393445.91 31-MAR-23:53 13903.23 05-MAR-06:00 136174.48 28-MAR-15:30 0.00
April 0.103387E+13 0.368918E+12 720.00 0.102764E+13 0.623054E+10 0.00 1.00 01-APR-08:70 0.42 30-APR-23:17 409642.52 22-APR-17:00 403753.64 30-APR-04:53 8847.56 11-APR-05:00 173337.68 15-APR-15:00 0.00
May 0.362309E+12 0.148435E+12 744.00 0.345365E+12 0.169447E+11 0.00 0.60 31-MAY-23:15 0.35 28-MAY-05:00 226062.27 31-MAY-23:03 212657.17 31-MAY-24:00 15171.85 22-MAY-23:10 79009.18 31-MAY-23:15 0.00
June 0.598264E+12 0.245268E+12 720.00 0.572403E+12 0.258618E+11 0.00 0.85 30-JUN-24:00 0.58 18-JUN-04:55 318207.61 30-JUN-23:03 306905.83 30-JUN-24:00 18586.69 28-JUN-13:30 127495.20 30-JUN-23:20 0.00
July 0.873669E+12 0.339011E+12 744.00 0.837004E+12 0.366650E+11 0.00 1.00 31-JUL-23:03 0.80 19-JUL-03:00 401295.33 31-JUL-24:00 389769.04 31-JUL-24:00 19562.60 18-JUL-08:30 157203.28 07-JUL-15:00 0.00
August 0.109901E+13 0.390764E+12 744.00 0.106349E+13 0.355186E+11 0.00 1.00 01-AUG-00:03 0.45 31-AUG-23:17 421246.85 10-AUG-14:00 404479.86 15-AUG-23:57 20793.96 25-AUG-16:00 166009.77 07-AUG-15:00 0.00
September 0.366104E+12 0.132071E+12 720.00 0.334825E+12 0.312789E+11 0.00 0.59 30-SEP-23:03 0.36 27-SEP-05:00 227388.26 30-SEP-23:03 213521.24 30-SEP-24:00 18092.20 12-SEP-16:00 76147.96 30-SEP-23:13 0.00
October 0.601447E+12 0.197519E+12 744.00 0.585009E+12 0.164374E+11 0.00 0.76 31-OCT-23:30 0.55 31-OCT-05:00 310615.61 31-OCT-24:00 302108.06 31-OCT-24:00 11505.56 13-OCT-08:30 101578.67 02-OCT-15:00 0.00
November 0.817191E+12 0.229491E+12 720.00 0.797581E+12 0.196103E+11 0.00 0.84 08-NOV-15:00 0.75 26-NOV-06:00 321426.53 24-NOV-08:15 313962.50 08-NOV-15:00 14617.17 23-NOV-08:00 118404.11 08-NOV-15:00 0.00
December 0.109883E+13 0.269807E+12 744.00 0.106407E+13 0.347623E+11 0.00 1.00 03-DEC-13:43 0.93 01-DEC-00:10 421933.43 22-DEC-06:03 403434.75 28-DEC-17:00 25655.78 22-DEC-06:03 130068.41 28-DEC-14:10 0.00
                                       
Annual Sum or Average 0.855633E+13 0.280428E+13 8760.00 0.828842E+13 0.267909E+12 0.00                         0.00
Minimum of Months 0.337411E+12 0.874060E+11 672.00 0.323791E+12 0.623054E+10 0.00 0.35   0.32   131369.15   127093.53   6384.37   41117.70   0.00
Maximum of Months 0.109901E+13 0.390764E+12 744.00 0.106407E+13 0.366650E+11 0.00 1.00   0.93   421933.43   404479.86   25655.78   173337.68   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.496405E+10 0.129302E+10 744.00 0.481944E+10 0.144612E+09 0.00 0.31 12-JAN-17:00 0.17 07-JAN-08:00 2461.85 12-JAN-17:00 2332.68 12-JAN-17:00 242.12 17-JAN-16:20 735.21 12-JAN-16:00 0.00
February 0.956863E+10 0.252289E+10 672.00 0.934264E+10 0.225990E+09 0.00 0.56 20-FEB-17:03 0.41 02-FEB-07:00 4507.57 21-FEB-17:00 4401.49 20-FEB-17:15 262.69 15-FEB-17:10 1488.42 22-FEB-15:00 0.00
March 0.161863E+11 0.482578E+10 744.00 0.158562E+11 0.330177E+09 0.00 0.91 31-MAR-24:00 0.64 01-MAR-07:00 7782.42 31-MAR-24:00 7681.68 31-MAR-23:53 335.36 10-MAR-17:10 2714.53 28-MAR-16:00 0.00
April 0.209044E+11 0.743386E+10 720.00 0.205976E+11 0.306832E+09 0.00 1.00 01-APR-13:50 0.39 30-APR-23:05 8531.71 17-APR-01:55 8274.66 17-APR-01:55 382.96 26-APR-08:00 3558.27 15-APR-15:00 0.00
May 0.718480E+10 0.283565E+10 744.00 0.652195E+10 0.662852E+09 0.00 0.57 31-MAY-23:03 0.29 13-MAY-07:00 4655.66 31-MAY-23:03 4059.13 31-MAY-24:00 642.66 22-MAY-23:10 1588.38 01-MAY-15:40 0.00
June 0.123015E+11 0.483594E+10 720.00 0.112179E+11 0.108358E+10 0.00 0.81 30-JUN-23:25 0.54 18-JUN-03:55 6544.35 30-JUN-23:03 6064.99 30-JUN-24:00 811.24 28-JUN-13:30 2530.51 08-JUN-16:00 0.00
July 0.181648E+11 0.675365E+10 744.00 0.165539E+11 0.161083E+10 0.00 1.00 31-JUL-23:03 0.75 19-JUL-03:00 8536.99 31-JUL-23:03 7838.72 31-JUL-24:00 844.79 18-JUL-08:20 3270.86 02-JUL-16:50 0.00
August 0.227886E+11 0.803399E+10 744.00 0.210995E+11 0.168917E+10 0.00 1.00 01-AUG-00:03 0.38 31-AUG-23:05 8774.97 10-AUG-14:10 8063.92 29-AUG-03:35 862.19 21-AUG-14:00 3414.04 07-AUG-15:00 0.00
September 0.731155E+10 0.250726E+10 720.00 0.604316E+10 0.126840E+10 0.00 0.56 30-SEP-23:03 0.30 27-SEP-06:00 4619.85 30-SEP-23:03 4023.56 30-SEP-24:00 731.12 12-SEP-16:00 1470.29 30-SEP-23:13 0.00
October 0.116850E+11 0.373155E+10 744.00 0.110668E+11 0.618249E+09 0.00 0.69 31-OCT-23:20 0.47 31-OCT-06:00 5960.59 31-OCT-23:10 5756.59 31-OCT-24:00 493.68 06-OCT-09:50 2030.82 02-OCT-15:00 0.00
November 0.155412E+11 0.430270E+10 720.00 0.152313E+11 0.309876E+09 0.00 0.80 08-NOV-16:20 0.64 25-NOV-08:00 6553.50 08-NOV-16:40 6338.54 12-NOV-16:20 282.78 08-NOV-20:00 2318.84 08-NOV-15:00 0.00
December 0.205124E+11 0.502349E+10 744.00 0.203422E+11 0.170145E+09 0.00 0.96 25-DEC-14:13 0.81 23-DEC-08:00 8226.95 28-DEC-17:00 8066.52 28-DEC-17:00 252.92 29-DEC-17:10 2561.58 25-DEC-14:00 0.00
                                       
Annual Sum or Average 0.167113E+12 0.540998E+11 8760.00 0.158693E+12 0.842071E+10 0.00                         0.00
Minimum of Months 0.496405E+10 0.129302E+10 672.00 0.481944E+10 0.144612E+09 0.00 0.31   0.17   2461.85   2332.68   242.12   735.21   0.00
Maximum of Months 0.227886E+11 0.803399E+10 744.00 0.210995E+11 0.168917E+10 0.00 1.00   0.81   8774.97   8274.66   862.19   3558.27   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.376245E+11 0.999568E+10 744.00 0.362624E+11 0.136201E+10 0.00 0.31 12-JAN-17:00 0.10 01-JAN-06:55 22908.01 12-JAN-17:00 21638.91 12-JAN-17:00 2378.01 17-JAN-16:20 6800.40 12-JAN-16:50 0.00
February 0.856789E+11 0.227712E+11 672.00 0.834441E+11 0.223480E+10 0.00 0.56 22-FEB-17:00 0.35 11-FEB-08:00 42571.53 22-FEB-17:00 41083.14 21-FEB-17:00 2602.39 15-FEB-17:10 14104.48 22-FEB-15:00 0.00
March 0.153034E+12 0.457082E+11 744.00 0.149743E+12 0.329083E+10 0.00 0.92 31-MAR-24:00 0.62 01-MAR-07:00 75049.05 31-MAR-24:00 74037.22 31-MAR-23:53 3336.43 10-MAR-17:10 25898.19 28-MAR-16:00 0.00
April 0.198255E+12 0.706109E+11 720.00 0.195176E+12 0.307970E+10 0.00 1.00 01-APR-13:30 0.33 30-APR-24:00 80291.95 12-APR-16:00 78037.86 12-APR-16:10 3831.10 26-APR-08:00 33920.29 15-APR-15:00 0.00
May 0.677233E+11 0.267355E+11 744.00 0.611764E+11 0.654694E+10 0.00 0.57 31-MAY-23:15 0.28 13-MAY-07:00 44631.54 31-MAY-23:03 39048.59 31-MAY-24:00 6283.20 22-MAY-23:20 14805.77 31-MAY-23:15 0.00
June 0.117176E+12 0.460233E+11 720.00 0.106404E+12 0.107720E+11 0.00 0.82 30-JUN-23:15 0.53 24-JUN-13:40 63260.26 30-JUN-23:03 58359.92 30-JUN-24:00 8087.89 28-JUN-13:30 24241.94 30-JUN-23:15 0.00
July 0.173140E+12 0.642970E+11 744.00 0.157083E+12 0.160575E+11 0.00 1.00 31-JUL-23:03 0.76 19-JUL-03:00 81503.66 31-JUL-23:03 74853.49 31-JUL-23:50 8424.40 18-JUL-08:20 30709.35 02-JUL-16:51 0.00
August 0.216311E+12 0.764863E+11 744.00 0.199372E+12 0.169391E+11 0.00 1.00 01-AUG-00:03 0.34 31-AUG-23:05 83476.87 10-AUG-14:10 76173.71 16-AUG-09:40 8599.85 21-AUG-14:00 32540.05 07-AUG-15:00 0.00
September 0.687551E+11 0.235570E+11 720.00 0.562298E+11 0.125253E+11 0.00 0.57 30-SEP-23:03 0.29 08-SEP-21:20 44822.67 30-SEP-23:03 38802.02 30-SEP-24:00 7229.46 12-SEP-16:00 14192.19 30-SEP-23:13 0.00
October 0.110166E+12 0.352266E+11 744.00 0.104033E+12 0.613356E+10 0.00 0.68 31-OCT-23:20 0.45 31-OCT-06:00 56366.39 31-OCT-23:10 54291.33 31-OCT-24:00 4921.84 06-OCT-09:50 19313.76 02-OCT-15:00 0.00
November 0.144678E+12 0.402210E+11 720.00 0.141592E+12 0.308659E+10 0.00 0.80 08-NOV-16:20 0.60 25-NOV-08:00 62400.34 08-NOV-16:50 59910.59 08-NOV-16:30 2790.36 08-NOV-20:00 22054.10 08-NOV-15:00 0.00
December 0.187690E+12 0.462811E+11 744.00 0.185987E+12 0.170305E+10 0.00 0.95 28-DEC-16:40 0.76 23-DEC-08:00 77874.40 28-DEC-17:00 76278.70 28-DEC-17:00 2521.47 29-DEC-17:10 24193.82 28-DEC-15:00 0.00
                                       
Annual Sum or Average 0.156023E+13 0.507914E+12 8760.00 0.147650E+13 0.837314E+11 0.00                         0.00
Minimum of Months 0.376245E+11 0.999568E+10 672.00 0.362624E+11 0.136201E+10 0.00 0.31   0.10   22908.01   21638.91   2378.01   6800.40   0.00
Maximum of Months 0.216311E+12 0.764863E+11 744.00 0.199372E+12 0.169391E+11 0.00 1.00   0.76   83476.87   78037.86   8599.85   33920.29   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.226246E+10 0.628486E+09 660.92 0.213883E+10 0.123629E+09 0.00 0.30 12-JAN-17:00 0.00 01-JAN-00:10 2298.72 12-JAN-17:00 2163.49 12-JAN-17:00 250.75 17-JAN-15:20 686.03 12-JAN-16:50 0.00
February 0.786748E+10 0.212871E+10 672.00 0.763117E+10 0.236311E+09 0.00 0.55 22-FEB-17:00 0.26 11-FEB-06:00 4312.75 22-FEB-17:00 4152.27 22-FEB-17:00 267.83 15-FEB-17:10 1437.73 22-FEB-15:00 0.00
March 0.151537E+11 0.457270E+10 744.00 0.148056E+11 0.348082E+09 0.00 0.90 31-MAR-24:00 0.56 01-MAR-08:00 7466.29 31-MAR-24:00 7357.89 31-MAR-23:53 341.44 10-MAR-17:10 2660.05 28-MAR-16:00 0.00
April 0.200188E+11 0.719157E+10 720.00 0.196932E+11 0.325613E+09 0.00 1.00 01-APR-15:00 0.34 30-APR-24:00 8283.88 16-APR-20:54 8012.65 16-APR-21:32 390.24 26-APR-08:00 3508.65 15-APR-15:00 0.00
May 0.703734E+10 0.279211E+10 744.00 0.636088E+10 0.676457E+09 0.00 0.55 31-MAY-23:15 0.26 13-MAY-07:00 4452.01 31-MAY-23:03 3884.53 31-MAY-24:00 640.87 31-MAY-23:03 1616.12 28-MAY-16:31 0.00
June 0.119715E+11 0.472930E+10 720.00 0.108733E+11 0.109817E+10 0.00 0.81 30-JUN-23:15 0.51 24-JUN-13:50 6391.36 30-JUN-23:03 5889.48 30-JUN-24:00 818.99 28-JUN-13:30 2564.20 11-JUN-16:10 0.00
July 0.175570E+11 0.656192E+10 744.00 0.159304E+11 0.162657E+10 0.00 1.00 31-JUL-23:03 0.73 19-JUL-03:00 8395.53 31-JUL-23:03 7618.14 31-JUL-23:57 849.73 18-JUL-08:20 3282.92 02-JUL-16:51 0.00
August 0.220047E+11 0.785259E+10 744.00 0.202827E+11 0.172192E+10 0.00 1.00 01-AUG-08:30 0.34 31-AUG-23:13 8537.75 10-AUG-14:10 7817.29 20-AUG-17:25 871.50 21-AUG-14:00 3365.16 07-AUG-15:00 0.00
September 0.698050E+10 0.240576E+10 720.00 0.570770E+10 0.127279E+10 0.00 0.55 30-SEP-23:03 0.27 09-SEP-17:13 4501.53 30-SEP-23:03 3871.73 30-SEP-23:17 730.00 12-SEP-16:00 1437.24 30-SEP-23:13 0.00
October 0.109526E+11 0.353440E+10 744.00 0.103210E+11 0.631566E+09 0.00 0.65 31-OCT-23:20 0.41 28-OCT-07:00 5524.99 31-OCT-23:10 5289.64 31-OCT-24:00 501.43 06-OCT-09:50 1988.65 02-OCT-15:10 0.00
November 0.139720E+11 0.393913E+10 720.00 0.136458E+11 0.326139E+09 0.00 0.79 08-NOV-16:20 0.50 26-NOV-07:40 6296.21 08-NOV-16:40 6042.89 08-NOV-16:30 286.18 08-NOV-20:00 2241.86 08-NOV-15:00 0.00
December 0.175460E+11 0.440401E+10 744.00 0.173600E+11 0.185941E+09 0.00 0.93 28-DEC-16:40 0.62 31-DEC-08:70 7798.23 28-DEC-17:00 7631.12 28-DEC-17:00 258.84 29-DEC-17:10 2439.28 28-DEC-15:00 0.00
                                       
Annual Sum or Average 0.153324E+12 0.507407E+11 8676.92 0.144751E+12 0.857319E+10 0.00                         0.00
Minimum of Months 0.226246E+10 0.628486E+09 660.92 0.213883E+10 0.123629E+09 0.00 0.30   0.00   2298.72   2163.49   250.75   686.03   0.00
Maximum of Months 0.220047E+11 0.785259E+10 744.00 0.202827E+11 0.172192E+10 0.00 1.00   0.73   8537.75   8012.65   871.50   3508.65   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 47.39 367.50 0.00 0.00 0.00
February 108.09 0.00 108.09 100.03 279.60 0.00 0.00 0.00
March 130.25 0.00 130.25 197.35 159.38 0.00 0.00 0.00
April 141.33 0.48 140.85 339.19 52.61 0.00 0.00 0.00
May 156.58 4.39 152.19 474.79 8.04 0.00 0.00 0.00
June 162.09 6.00 156.08 514.42 6.03 0.00 0.00 0.00
July 159.85 2.53 157.32 456.97 1.33 0.00 0.00 0.00
August 146.75 0.46 146.29 382.02 5.29 0.00 0.00 0.00
September 130.76 0.01 130.75 302.25 20.81 0.00 0.00 0.00
October 113.28 0.00 113.28 218.66 120.85 0.00 0.00 0.00
November 95.95 0.00 95.95 116.48 246.22 0.00 0.00 0.00
December 88.92 0.00 88.92 52.45 358.72 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 267.64 134.94 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 47.39 1.33 0.00 0.00 0.00
Maximum of Months 162.09 6.00 157.32 514.42 367.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 47.38 367.50 0.00 0.00 0.00
February 108.09 0.00 108.09 100.03 279.60 0.00 0.00 0.00
March 130.24 0.00 130.24 197.35 159.38 0.00 0.00 0.00
April 141.33 0.48 140.85 339.19 52.61 0.00 0.00 0.00
May 156.58 4.39 152.18 474.79 8.04 0.00 0.00 0.00
June 162.08 6.00 156.08 514.42 6.03 0.00 0.00 0.00
July 159.85 2.53 157.32 456.97 1.33 0.00 0.00 0.00
August 146.75 0.46 146.29 382.02 5.29 0.00 0.00 0.00
September 130.76 0.01 130.75 302.25 20.81 0.00 0.00 0.00
October 113.28 0.00 113.28 218.66 120.85 0.00 0.00 0.00
November 95.95 0.00 95.95 116.48 246.21 0.00 0.00 0.00
December 88.92 0.00 88.92 52.45 358.72 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 267.64 134.94 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 47.38 1.33 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.32 514.42 367.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 47.38 367.50 0.00 0.00 0.00
February 108.09 0.00 108.09 100.03 279.60 0.00 0.00 0.00
March 130.24 0.00 130.24 197.35 159.38 0.00 0.00 0.00
April 141.33 0.48 140.85 339.19 52.61 0.00 0.00 0.00
May 156.58 4.39 152.19 474.79 8.04 0.00 0.00 0.00
June 162.08 6.00 156.08 514.42 6.03 0.00 0.00 0.00
July 159.85 2.53 157.32 456.97 1.33 0.00 0.00 0.00
August 146.75 0.46 146.29 382.02 5.29 0.00 0.00 0.00
September 130.76 0.01 130.75 302.25 20.81 0.00 0.00 0.00
October 113.28 0.00 113.28 218.66 120.85 0.00 0.00 0.00
November 95.95 0.00 95.95 116.48 246.21 0.00 0.00 0.00
December 88.92 0.00 88.92 52.45 358.72 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 267.64 134.94 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 47.38 1.33 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.32 514.42 367.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.15 0.00 91.15 47.38 367.50 0.00 0.00 0.00
February 108.09 0.00 108.09 100.03 279.60 0.00 0.00 0.00
March 130.24 0.00 130.24 197.35 159.38 0.00 0.00 0.00
April 141.33 0.48 140.85 339.19 52.61 0.00 0.00 0.00
May 156.58 4.39 152.18 474.79 8.04 0.00 0.00 0.00
June 162.08 6.00 156.08 514.42 6.03 0.00 0.00 0.00
July 159.85 2.53 157.32 456.97 1.33 0.00 0.00 0.00
August 146.75 0.46 146.29 382.02 5.29 0.00 0.00 0.00
September 130.76 0.01 130.75 302.25 20.81 0.00 0.00 0.00
October 113.28 0.00 113.28 218.66 120.85 0.00 0.00 0.00
November 95.95 0.00 95.95 116.48 246.21 0.00 0.00 0.00
December 88.92 0.00 88.92 52.45 358.72 0.00 0.00 0.00
                 
Annual Sum or Average 127.18 1.16 126.02 267.64 134.94 0.00 0.00 0.00
Minimum of Months 88.92 0.00 88.92 47.38 1.33 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.32 514.42 367.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 91.14 0.00 91.14 47.38 367.48 0.00 0.00 0.00
February 108.08 0.00 108.08 100.03 279.59 0.00 0.00 0.00
March 130.24 0.00 130.24 197.34 159.38 0.00 0.00 0.00
April 141.32 0.48 140.84 339.17 52.61 0.00 0.00 0.00
May 156.57 4.39 152.18 474.77 8.04 0.00 0.00 0.00
June 162.08 6.00 156.07 514.40 6.03 0.00 0.00 0.00
July 159.84 2.53 157.31 456.95 1.33 0.00 0.00 0.00
August 146.74 0.46 146.28 382.00 5.29 0.00 0.00 0.00
September 130.75 0.01 130.74 302.24 20.81 0.00 0.00 0.00
October 113.27 0.00 113.27 218.65 120.84 0.00 0.00 0.00
November 95.94 0.00 95.94 116.47 246.20 0.00 0.00 0.00
December 88.91 0.00 88.91 52.45 358.71 0.00 0.00 0.00
                 
Annual Sum or Average 127.17 1.16 126.01 267.63 134.93 0.00 0.00 0.00
Minimum of Months 88.91 0.00 88.91 47.38 1.33 0.00 0.00 0.00
Maximum of Months 162.08 6.00 157.31 514.40 367.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 216.96 87.08 129.87 217.25 369.31 0.00 0.00 0.00
February 263.57 108.82 154.76 339.19 284.17 0.00 0.00 0.00
March 321.53 132.72 188.81 522.97 163.71 0.00 0.00 0.00
April 382.54 178.36 204.18 778.42 53.77 0.00 0.00 0.00
May 376.52 166.93 209.59 883.61 8.45 0.00 0.00 0.00
June 306.44 101.68 204.76 799.63 5.84 0.00 0.00 0.00
July 257.56 54.39 203.17 658.63 0.91 0.00 0.00 0.00
August 232.07 40.39 191.68 558.60 3.63 0.00 0.00 0.00
September 247.94 69.14 178.79 519.09 21.38 0.00 0.00 0.00
October 271.22 109.55 161.66 500.61 127.88 0.00 0.00 0.00
November 240.47 103.22 137.25 354.58 251.21 0.00 0.00 0.00
December 209.68 83.08 126.60 228.68 358.67 0.00 0.00 0.00
                 
Annual Sum or Average 277.13 102.79 174.35 530.77 136.80 0.00 0.00 0.00
Minimum of Months 209.68 40.39 126.60 217.25 0.91 0.00 0.00 0.00
Maximum of Months 382.54 178.36 209.59 883.61 369.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 216.96 87.08 129.87 217.25 369.31 0.00 0.00 0.00
February 263.57 108.82 154.76 339.19 284.17 0.00 0.00 0.00
March 321.53 132.72 188.81 522.97 163.71 0.00 0.00 0.00
April 382.54 178.36 204.18 778.42 53.77 0.00 0.00 0.00
May 376.52 166.93 209.59 883.61 8.45 0.00 0.00 0.00
June 306.44 101.68 204.76 799.63 5.84 0.00 0.00 0.00
July 257.56 54.39 203.17 658.63 0.91 0.00 0.00 0.00
August 232.07 40.39 191.68 558.60 3.63 0.00 0.00 0.00
September 247.94 69.14 178.79 519.09 21.38 0.00 0.00 0.00
October 271.22 109.55 161.66 500.61 127.88 0.00 0.00 0.00
November 240.47 103.22 137.25 354.58 251.21 0.00 0.00 0.00
December 209.68 83.08 126.60 228.68 358.67 0.00 0.00 0.00
                 
Annual Sum or Average 277.13 102.79 174.35 530.77 136.80 0.00 0.00 0.00
Minimum of Months 209.68 40.39 126.60 217.25 0.91 0.00 0.00 0.00
Maximum of Months 382.54 178.36 209.59 883.61 369.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 216.95 87.08 129.87 217.24 369.30 0.00 0.00 0.00
February 263.57 108.81 154.75 339.18 284.16 0.00 0.00 0.00
March 321.53 132.71 188.81 522.96 163.70 0.00 0.00 0.00
April 382.53 178.36 204.18 778.40 53.77 0.00 0.00 0.00
May 376.52 166.93 209.59 883.60 8.45 0.00 0.00 0.00
June 306.43 101.67 204.76 799.61 5.84 0.00 0.00 0.00
July 257.55 54.39 203.16 658.62 0.91 0.00 0.00 0.00
August 232.06 40.38 191.68 558.59 3.63 0.00 0.00 0.00
September 247.93 69.14 178.79 519.08 21.38 0.00 0.00 0.00
October 271.21 109.55 161.66 500.60 127.88 0.00 0.00 0.00
November 240.47 103.22 137.25 354.57 251.20 0.00 0.00 0.00
December 209.68 83.08 126.60 228.68 358.66 0.00 0.00 0.00
                 
Annual Sum or Average 277.13 102.78 174.34 530.76 136.80 0.00 0.00 0.00
Minimum of Months 209.68 40.38 126.60 217.24 0.91 0.00 0.00 0.00
Maximum of Months 382.53 178.36 209.59 883.60 369.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.54 251.88 162.65 567.57 334.31 0.00 0.00 0.00
February 394.17 218.93 175.24 587.79 269.34 0.00 0.00 0.00
March 337.02 148.86 188.16 588.49 163.46 0.00 0.00 0.00
April 236.73 66.81 169.92 547.33 57.35 0.00 0.00 0.00
May 170.24 12.60 157.64 508.44 8.22 0.00 0.00 0.00
June 155.72 2.66 153.07 501.87 6.09 0.00 0.00 0.00
July 162.43 2.23 160.20 463.91 1.25 0.00 0.00 0.00
August 172.31 9.20 163.11 434.75 5.54 0.00 0.00 0.00
September 230.99 59.95 171.04 495.80 23.45 0.00 0.00 0.00
October 397.40 221.90 175.49 735.82 128.50 0.00 0.00 0.00
November 496.37 328.09 168.28 803.81 245.35 0.00 0.00 0.00
December 443.00 277.59 165.40 628.63 332.96 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 571.72 130.71 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 434.75 1.25 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 803.81 334.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.53 251.88 162.65 567.57 334.31 0.00 0.00 0.00
February 394.16 218.93 175.23 587.79 269.34 0.00 0.00 0.00
March 337.02 148.86 188.16 588.49 163.46 0.00 0.00 0.00
April 236.72 66.81 169.91 547.33 57.35 0.00 0.00 0.00
May 170.24 12.60 157.64 508.44 8.22 0.00 0.00 0.00
June 155.72 2.66 153.07 501.87 6.09 0.00 0.00 0.00
July 162.43 2.23 160.20 463.90 1.25 0.00 0.00 0.00
August 172.31 9.20 163.10 434.75 5.54 0.00 0.00 0.00
September 230.99 59.95 171.04 495.80 23.45 0.00 0.00 0.00
October 397.39 221.90 175.49 735.82 128.50 0.00 0.00 0.00
November 496.37 328.09 168.28 803.81 245.35 0.00 0.00 0.00
December 442.99 277.59 165.40 628.62 332.96 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 571.72 130.71 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 434.75 1.25 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 803.81 334.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.54 251.88 162.65 567.57 334.31 0.00 0.00 0.00
February 394.17 218.93 175.24 587.79 269.34 0.00 0.00 0.00
March 337.02 148.86 188.16 588.49 163.46 0.00 0.00 0.00
April 236.73 66.81 169.92 547.33 57.35 0.00 0.00 0.00
May 170.24 12.60 157.64 508.44 8.22 0.00 0.00 0.00
June 155.72 2.66 153.07 501.87 6.09 0.00 0.00 0.00
July 162.43 2.23 160.20 463.91 1.25 0.00 0.00 0.00
August 172.31 9.20 163.11 434.75 5.54 0.00 0.00 0.00
September 230.99 59.95 171.04 495.80 23.45 0.00 0.00 0.00
October 397.40 221.90 175.49 735.82 128.50 0.00 0.00 0.00
November 496.37 328.09 168.28 803.81 245.35 0.00 0.00 0.00
December 443.00 277.59 165.40 628.63 332.96 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 571.72 130.71 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 434.75 1.25 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 803.81 334.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.53 251.88 162.65 567.57 334.31 0.00 0.00 0.00
February 394.16 218.93 175.23 587.79 269.34 0.00 0.00 0.00
March 337.02 148.86 188.16 588.49 163.46 0.00 0.00 0.00
April 236.72 66.81 169.91 547.33 57.35 0.00 0.00 0.00
May 170.24 12.60 157.64 508.44 8.22 0.00 0.00 0.00
June 155.72 2.66 153.07 501.87 6.09 0.00 0.00 0.00
July 162.43 2.23 160.20 463.90 1.25 0.00 0.00 0.00
August 172.31 9.20 163.10 434.75 5.54 0.00 0.00 0.00
September 230.99 59.95 171.04 495.80 23.45 0.00 0.00 0.00
October 397.39 221.90 175.49 735.82 128.50 0.00 0.00 0.00
November 496.37 328.09 168.28 803.81 245.35 0.00 0.00 0.00
December 442.99 277.59 165.40 628.62 332.96 0.00 0.00 0.00
                 
Annual Sum or Average 300.37 132.90 167.47 571.72 130.71 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.07 434.75 1.25 0.00 0.00 0.00
Maximum of Months 496.37 328.09 188.16 803.81 334.31 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 414.52 251.87 162.65 567.55 334.30 0.00 0.00 0.00
February 394.15 218.92 175.23 587.77 269.33 0.00 0.00 0.00
March 337.01 148.85 188.15 588.47 163.46 0.00 0.00 0.00
April 236.72 66.81 169.91 547.31 57.34 0.00 0.00 0.00
May 170.23 12.60 157.63 508.42 8.22 0.00 0.00 0.00
June 155.72 2.66 153.06 501.85 6.09 0.00 0.00 0.00
July 162.43 2.23 160.19 463.89 1.25 0.00 0.00 0.00
August 172.30 9.20 163.10 434.74 5.54 0.00 0.00 0.00
September 230.98 59.95 171.03 495.78 23.45 0.00 0.00 0.00
October 397.38 221.89 175.49 735.79 128.50 0.00 0.00 0.00
November 496.35 328.07 168.27 803.78 245.34 0.00 0.00 0.00
December 442.98 277.58 165.40 628.60 332.95 0.00 0.00 0.00
                 
Annual Sum or Average 300.36 132.89 167.47 571.70 130.71 0.00 0.00 0.00
Minimum of Months 155.72 2.23 153.06 434.74 1.25 0.00 0.00 0.00
Maximum of Months 496.35 328.07 188.15 803.78 334.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 212.26 82.60 129.65 233.49 428.03 0.00 0.00 0.00
February 242.72 89.45 153.27 315.20 343.34 0.00 0.00 0.00
March 314.75 125.82 188.93 506.22 211.29 0.00 0.00 0.00
April 382.57 179.41 203.16 752.30 89.44 0.00 0.00 0.00
May 362.26 153.66 208.60 843.49 15.14 0.00 0.00 0.00
June 340.26 132.17 208.09 830.60 11.83 0.00 0.00 0.00
July 252.49 49.11 203.38 607.75 5.29 0.00 0.00 0.00
August 231.88 41.21 190.67 511.02 20.27 0.00 0.00 0.00
September 254.90 74.83 180.07 519.35 35.66 0.00 0.00 0.00
October 265.31 105.65 159.67 485.90 159.89 0.00 0.00 0.00
November 240.02 102.29 137.72 359.56 311.12 0.00 0.00 0.00
December 205.39 78.32 127.07 224.56 443.18 0.00 0.00 0.00
                 
Annual Sum or Average 275.35 101.08 174.27 516.34 172.14 0.00 0.00 0.00
Minimum of Months 205.39 41.21 127.07 224.56 5.29 0.00 0.00 0.00
Maximum of Months 382.57 179.41 208.60 843.49 443.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 212.26 82.60 129.65 233.49 428.03 0.00 0.00 0.00
February 242.72 89.45 153.27 315.20 343.34 0.00 0.00 0.00
March 314.75 125.82 188.93 506.22 211.29 0.00 0.00 0.00
April 382.57 179.41 203.16 752.30 89.44 0.00 0.00 0.00
May 362.26 153.66 208.60 843.49 15.14 0.00 0.00 0.00
June 340.26 132.17 208.09 830.60 11.83 0.00 0.00 0.00
July 252.49 49.11 203.38 607.75 5.29 0.00 0.00 0.00
August 231.88 41.21 190.67 511.02 20.27 0.00 0.00 0.00
September 254.90 74.83 180.07 519.35 35.66 0.00 0.00 0.00
October 265.31 105.65 159.67 485.90 159.89 0.00 0.00 0.00
November 240.02 102.29 137.72 359.56 311.12 0.00 0.00 0.00
December 205.39 78.32 127.07 224.56 443.18 0.00 0.00 0.00
                 
Annual Sum or Average 275.35 101.08 174.27 516.34 172.14 0.00 0.00 0.00
Minimum of Months 205.39 41.21 127.07 224.56 5.29 0.00 0.00 0.00
Maximum of Months 382.57 179.41 208.60 843.49 443.18 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 212.25 82.60 129.65 233.48 428.03 0.00 0.00 0.00
February 242.72 89.45 153.27 315.19 343.33 0.00 0.00 0.00
March 314.74 125.81 188.93 506.21 211.28 0.00 0.00 0.00
April 382.56 179.41 203.16 752.29 89.44 0.00 0.00 0.00
May 362.25 153.66 208.59 843.47 15.14 0.00 0.00 0.00
June 340.25 132.16 208.09 830.58 11.83 0.00 0.00 0.00
July 252.48 49.11 203.38 607.74 5.28 0.00 0.00 0.00
August 231.88 41.21 190.67 511.01 20.27 0.00 0.00 0.00
September 254.90 74.83 180.07 519.34 35.65 0.00 0.00 0.00
October 265.31 105.65 159.66 485.89 159.89 0.00 0.00 0.00
November 240.02 102.29 137.72 359.55 311.11 0.00 0.00 0.00
December 205.38 78.32 127.07 224.56 443.17 0.00 0.00 0.00
                 
Annual Sum or Average 275.35 101.08 174.27 516.33 172.13 0.00 0.00 0.00
Minimum of Months 205.38 41.21 127.07 224.56 5.28 0.00 0.00 0.00
Maximum of Months 382.56 179.41 208.59 843.47 443.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 455.75 0.00 455.75 282.51 1658.77 0.00 0.00 0.00
February 540.44 0.00 540.44 538.41 1282.23 0.00 0.00 0.00
March 651.23 0.00 651.23 1008.91 761.47 0.00 0.00 0.00
April 706.64 2.40 704.24 1737.17 256.13 0.00 0.00 0.00
May 782.90 21.97 760.93 2397.84 41.53 0.00 0.00 0.00
June 810.43 30.02 780.41 2597.81 32.69 0.00 0.00 0.00
July 799.27 12.66 786.61 2312.28 8.60 0.00 0.00 0.00
August 733.75 2.29 731.46 1953.70 27.83 0.00 0.00 0.00
September 653.79 0.05 653.75 1522.75 108.63 0.00 0.00 0.00
October 566.40 0.00 566.40 1114.90 588.65 0.00 0.00 0.00
November 479.74 0.00 479.74 618.77 1141.57 0.00 0.00 0.00
December 444.59 0.00 444.59 319.03 1596.03 0.00 0.00 0.00
                 
Annual Sum or Average 635.89 5.80 630.09 1371.05 622.58 0.00 0.00 0.00
Minimum of Months 444.59 0.00 444.59 282.51 8.60 0.00 0.00 0.00
Maximum of Months 810.43 30.02 786.61 2597.81 1658.77 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 650.86 261.25 389.61 676.13 1032.49 0.00 0.00 0.00
February 790.71 326.44 464.27 1025.52 815.37 0.00 0.00 0.00
March 964.58 398.15 566.44 1561.14 497.94 0.00 0.00 0.00
April 1147.61 535.07 612.53 2323.43 180.58 0.00 0.00 0.00
May 1129.56 500.78 628.77 2641.81 29.05 0.00 0.00 0.00
June 919.31 305.03 614.29 2388.54 22.33 0.00 0.00 0.00
July 772.66 163.16 609.49 1962.01 5.08 0.00 0.00 0.00
August 696.20 121.15 575.04 1661.76 19.06 0.00 0.00 0.00
September 743.81 207.43 536.38 1548.74 76.29 0.00 0.00 0.00
October 813.64 328.66 484.98 1496.77 394.38 0.00 0.00 0.00
November 721.41 309.66 411.75 1069.33 734.90 0.00 0.00 0.00
December 629.04 249.23 379.81 709.89 1013.05 0.00 0.00 0.00
                 
Annual Sum or Average 831.39 308.36 523.03 1590.71 399.93 0.00 0.00 0.00
Minimum of Months 629.04 121.15 379.81 676.13 5.08 0.00 0.00 0.00
Maximum of Months 1147.61 535.07 628.77 2641.81 1032.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2072.73 1259.44 813.28 2819.13 1650.06 0.00 0.00 0.00
February 1970.86 1094.67 876.19 2921.52 1324.64 0.00 0.00 0.00
March 1685.13 744.31 940.82 2932.20 814.22 0.00 0.00 0.00
April 1183.64 334.06 849.58 2751.91 288.58 0.00 0.00 0.00
May 851.20 63.01 788.18 2564.76 41.62 0.00 0.00 0.00
June 778.63 13.29 765.34 2537.45 32.27 0.00 0.00 0.00
July 812.18 11.17 801.01 2348.72 7.59 0.00 0.00 0.00
August 861.55 46.01 815.54 2208.98 29.14 0.00 0.00 0.00
September 1154.98 299.78 855.20 2475.08 126.38 0.00 0.00 0.00
October 1987.02 1109.54 877.48 3665.47 653.74 0.00 0.00 0.00
November 2481.90 1640.48 841.42 4001.99 1218.94 0.00 0.00 0.00
December 2215.03 1388.00 827.03 3137.88 1623.00 0.00 0.00 0.00
                 
Annual Sum or Average 1501.89 664.51 837.38 2862.43 647.88 0.00 0.00 0.00
Minimum of Months 778.63 11.17 765.34 2208.98 7.59 0.00 0.00 0.00
Maximum of Months 2481.90 1640.48 940.82 4001.99 1650.06 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 636.76 247.80 388.96 734.66 1142.62 0.00 0.00 0.00
February 728.15 268.34 459.81 981.58 904.24 0.00 0.00 0.00
March 944.23 377.44 566.79 1550.54 558.32 0.00 0.00 0.00
April 1147.70 538.23 609.47 2317.11 211.51 0.00 0.00 0.00
May 1086.77 460.98 625.78 2559.20 39.11 0.00 0.00 0.00
June 1020.76 396.49 624.27 2544.53 28.70 0.00 0.00 0.00
July 757.46 147.33 610.13 1900.60 8.36 0.00 0.00 0.00
August 695.65 123.64 572.01 1636.70 25.16 0.00 0.00 0.00
September 764.70 224.49 540.20 1577.66 92.11 0.00 0.00 0.00
October 795.93 316.94 478.99 1482.88 434.29 0.00 0.00 0.00
November 720.05 306.88 413.17 1119.48 815.85 0.00 0.00 0.00
December 616.15 234.95 381.20 737.20 1106.73 0.00 0.00 0.00
                 
Annual Sum or Average 826.04 303.23 522.82 1596.99 445.25 0.00 0.00 0.00
Minimum of Months 616.15 123.64 381.20 734.66 8.36 0.00 0.00 0.00
Maximum of Months 1147.70 538.23 625.78 2559.20 1142.62 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 455.75 0.00 455.75 345.73 1440.50 0.00 0.00 0.00
February 540.44 0.00 540.44 577.59 1167.14 0.00 0.00 0.00
March 651.23 0.00 651.23 1008.60 731.89 0.00 0.00 0.00
April 706.64 2.40 704.24 1707.49 258.86 0.00 0.00 0.00
May 782.90 21.97 760.93 2350.60 46.78 0.00 0.00 0.00
June 810.43 30.02 780.41 2545.76 36.73 0.00 0.00 0.00
July 799.27 12.66 786.61 2260.62 9.57 0.00 0.00 0.00
August 733.75 2.29 731.46 1913.09 31.39 0.00 0.00 0.00
September 653.79 0.05 653.75 1498.61 113.16 0.00 0.00 0.00
October 566.40 0.00 566.40 1108.21 573.17 0.00 0.00 0.00
November 479.74 0.00 479.74 644.29 1059.80 0.00 0.00 0.00
December 444.59 0.00 444.59 378.69 1415.83 0.00 0.00 0.00
                 
Annual Sum or Average 635.89 5.80 630.09 1365.45 571.12 0.00 0.00 0.00
Minimum of Months 444.59 0.00 444.59 345.73 9.57 0.00 0.00 0.00
Maximum of Months 810.43 30.02 786.61 2545.76 1440.50 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 650.86 261.25 389.61 733.79 911.31 0.00 0.00 0.00
February 790.71 326.44 464.27 1051.76 758.59 0.00 0.00 0.00
March 964.58 398.15 566.44 1557.73 486.74 0.00 0.00 0.00
April 1147.61 535.07 612.53 2300.98 184.81 0.00 0.00 0.00
May 1129.56 500.78 628.77 2607.29 33.06 0.00 0.00 0.00
June 919.31 305.03 614.29 2351.21 25.31 0.00 0.00 0.00
July 772.66 163.16 609.49 1925.64 5.61 0.00 0.00 0.00
August 696.20 121.15 575.04 1633.20 21.58 0.00 0.00 0.00
September 743.81 207.43 536.38 1531.19 79.87 0.00 0.00 0.00
October 813.64 328.66 484.98 1490.12 389.30 0.00 0.00 0.00
November 721.41 309.66 411.75 1084.67 696.32 0.00 0.00 0.00
December 629.04 249.23 379.81 758.30 917.98 0.00 0.00 0.00
                 
Annual Sum or Average 831.39 308.36 523.03 1587.34 374.14 0.00 0.00 0.00
Minimum of Months 629.04 121.15 379.81 733.79 5.61 0.00 0.00 0.00
Maximum of Months 1147.61 535.07 628.77 2607.29 917.98 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2072.73 1259.44 813.28 2881.95 1479.87 0.00 0.00 0.00
February 1970.86 1094.67 876.19 2945.42 1240.41 0.00 0.00 0.00
March 1685.13 744.31 940.82 2922.43 795.65 0.00 0.00 0.00
April 1183.64 334.06 849.58 2719.84 294.19 0.00 0.00 0.00
May 851.20 63.01 788.18 2517.18 46.89 0.00 0.00 0.00
June 778.63 13.29 765.34 2484.96 36.51 0.00 0.00 0.00
July 812.18 11.17 801.01 2296.68 8.39 0.00 0.00 0.00
August 861.55 46.01 815.54 2167.75 32.95 0.00 0.00 0.00
September 1154.98 299.78 855.20 2448.54 132.82 0.00 0.00 0.00
October 1987.02 1109.54 877.48 3650.78 648.72 0.00 0.00 0.00
November 2481.90 1640.48 841.42 4009.02 1168.05 0.00 0.00 0.00
December 2215.03 1388.00 827.03 3189.09 1494.91 0.00 0.00 0.00
                 
Annual Sum or Average 1501.89 664.51 837.38 2851.35 612.07 0.00 0.00 0.00
Minimum of Months 778.63 11.17 765.34 2167.75 8.39 0.00 0.00 0.00
Maximum of Months 2481.90 1640.48 940.82 4009.02 1494.91 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 636.76 247.80 388.96 767.86 1024.66 0.00 0.00 0.00
February 728.15 268.34 459.81 998.69 841.67 0.00 0.00 0.00
March 944.23 377.44 566.79 1545.39 543.44 0.00 0.00 0.00
April 1147.70 538.23 609.47 2297.10 213.61 0.00 0.00 0.00
May 1086.77 460.98 625.78 2530.62 42.12 0.00 0.00 0.00
June 1020.76 396.49 624.27 2513.05 30.80 0.00 0.00 0.00
July 757.46 147.33 610.13 1870.54 8.96 0.00 0.00 0.00
August 695.65 123.64 572.01 1613.97 27.30 0.00 0.00 0.00
September 764.70 224.49 540.20 1562.43 94.60 0.00 0.00 0.00
October 795.93 316.94 478.99 1476.19 426.58 0.00 0.00 0.00
November 720.05 306.88 413.17 1129.02 772.57 0.00 0.00 0.00
December 616.15 234.95 381.20 768.01 1009.62 0.00 0.00 0.00
                 
Annual Sum or Average 826.04 303.23 522.82 1591.13 417.75 0.00 0.00 0.00
Minimum of Months 616.15 123.64 381.20 767.86 8.96 0.00 0.00 0.00
Maximum of Months 1147.70 538.23 625.78 2530.62 1024.66 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244134E+09 0.00 0.244134E+09 0.126918E+09 0.984302E+09
February 0.261485E+09 0.00 0.261485E+09 0.242004E+09 0.676404E+09
March 0.348851E+09 0.00 0.348851E+09 0.528592E+09 0.426896E+09
April 0.366321E+09 1242306.39 0.365078E+09 0.879178E+09 0.136363E+09
May 0.419386E+09 11768647.88 0.407617E+09 0.127169E+10 21523355.43
June 0.420126E+09 15561451.75 0.404565E+09 0.133338E+10 15642383.50
July 0.428151E+09 6779998.49 0.421371E+09 0.122396E+10 3574180.66
August 0.393055E+09 1224970.50 0.391830E+09 0.102320E+10 14170130.01
September 0.338926E+09 23798.53 0.338902E+09 0.783434E+09 53934588.87
October 0.303407E+09 0.00 0.303407E+09 0.585655E+09 0.323675E+09
November 0.248699E+09 0.00 0.248699E+09 0.301912E+09 0.638189E+09
December 0.238157E+09 0.00 0.238157E+09 0.140482E+09 0.960799E+09
           
Annual Sum or Average 0.401070E+10 36601173.55 0.397410E+10 0.844040E+10 0.425547E+10
Minimum of Months 0.238157E+09 0.00 0.238157E+09 0.126918E+09 3574180.66
Maximum of Months 0.428151E+09 15561451.75 0.421371E+09 0.133338E+10 0.984302E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244130E+09 0.00 0.244130E+09 0.126915E+09 0.984299E+09
February 0.261481E+09 0.00 0.261481E+09 0.242000E+09 0.676402E+09
March 0.348846E+09 0.00 0.348846E+09 0.528587E+09 0.426893E+09
April 0.366316E+09 1242279.08 0.365074E+09 0.879174E+09 0.136360E+09
May 0.419380E+09 11768389.16 0.407612E+09 0.127168E+10 21522604.71
June 0.420121E+09 15561109.65 0.404560E+09 0.133338E+10 15642116.53
July 0.428145E+09 6779849.44 0.421365E+09 0.122395E+10 3574029.43
August 0.393049E+09 1224943.57 0.391824E+09 0.102319E+10 14169717.70
September 0.338921E+09 23798.01 0.338897E+09 0.783428E+09 53933215.64
October 0.303403E+09 0.00 0.303403E+09 0.585651E+09 0.323672E+09
November 0.248696E+09 0.00 0.248696E+09 0.301909E+09 0.638186E+09
December 0.238154E+09 0.00 0.238154E+09 0.140479E+09 0.960796E+09
           
Annual Sum or Average 0.401064E+10 36600368.92 0.397404E+10 0.844034E+10 0.425545E+10
Minimum of Months 0.238154E+09 0.00 0.238154E+09 0.126915E+09 3574029.43
Maximum of Months 0.428145E+09 15561109.65 0.421365E+09 0.133338E+10 0.984299E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244132E+09 0.00 0.244132E+09 0.126916E+09 0.984300E+09
February 0.261483E+09 0.00 0.261483E+09 0.242001E+09 0.676403E+09
March 0.348848E+09 0.00 0.348848E+09 0.528588E+09 0.426894E+09
April 0.366318E+09 1242288.19 0.365075E+09 0.879175E+09 0.136361E+09
May 0.419382E+09 11768475.40 0.407614E+09 0.127168E+10 21522854.95
June 0.420122E+09 15561223.69 0.404561E+09 0.133338E+10 15642205.52
July 0.428147E+09 6779899.12 0.421367E+09 0.122395E+10 3574079.84
August 0.393051E+09 1224952.55 0.391826E+09 0.102319E+10 14169855.14
September 0.338923E+09 23798.18 0.338899E+09 0.783430E+09 53933673.38
October 0.303405E+09 0.00 0.303405E+09 0.585652E+09 0.323673E+09
November 0.248697E+09 0.00 0.248697E+09 0.301910E+09 0.638187E+09
December 0.238155E+09 0.00 0.238155E+09 0.140480E+09 0.960797E+09
           
Annual Sum or Average 0.401066E+10 36600637.13 0.397406E+10 0.844036E+10 0.425546E+10
Minimum of Months 0.238155E+09 0.00 0.238155E+09 0.126916E+09 3574079.84
Maximum of Months 0.428147E+09 15561223.69 0.421367E+09 0.133338E+10 0.984300E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244130E+09 0.00 0.244130E+09 0.126915E+09 0.984299E+09
February 0.261481E+09 0.00 0.261481E+09 0.242000E+09 0.676402E+09
March 0.348846E+09 0.00 0.348846E+09 0.528587E+09 0.426893E+09
April 0.366316E+09 1242279.08 0.365074E+09 0.879174E+09 0.136360E+09
May 0.419380E+09 11768389.16 0.407612E+09 0.127168E+10 21522604.71
June 0.420121E+09 15561109.65 0.404560E+09 0.133338E+10 15642116.53
July 0.428145E+09 6779849.44 0.421365E+09 0.122395E+10 3574029.43
August 0.393049E+09 1224943.57 0.391824E+09 0.102319E+10 14169717.70
September 0.338921E+09 23798.01 0.338897E+09 0.783428E+09 53933215.64
October 0.303403E+09 0.00 0.303403E+09 0.585651E+09 0.323672E+09
November 0.248696E+09 0.00 0.248696E+09 0.301909E+09 0.638186E+09
December 0.238154E+09 0.00 0.238154E+09 0.140479E+09 0.960796E+09
           
Annual Sum or Average 0.401064E+10 36600368.92 0.397404E+10 0.844034E+10 0.425545E+10
Minimum of Months 0.238154E+09 0.00 0.238154E+09 0.126915E+09 3574029.43
Maximum of Months 0.428145E+09 15561109.65 0.421365E+09 0.133338E+10 0.984299E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.244121E+09 0.00 0.244121E+09 0.126910E+09 0.984260E+09
February 0.261472E+09 0.00 0.261472E+09 0.241991E+09 0.676375E+09
March 0.348833E+09 0.00 0.348833E+09 0.528566E+09 0.426876E+09
April 0.366302E+09 1242233.56 0.365060E+09 0.879139E+09 0.136355E+09
May 0.419364E+09 11767957.96 0.407596E+09 0.127163E+10 21521862.37
June 0.420105E+09 15560539.49 0.404544E+09 0.133332E+10 15641530.58
July 0.428128E+09 6779601.02 0.421349E+09 0.122390E+10 3573910.58
August 0.393034E+09 1224898.69 0.391809E+09 0.102315E+10 14169215.31
September 0.338908E+09 23797.13 0.338884E+09 0.783397E+09 53931270.75
October 0.303392E+09 0.00 0.303392E+09 0.585628E+09 0.323660E+09
November 0.248686E+09 0.00 0.248686E+09 0.301897E+09 0.638161E+09
December 0.238145E+09 0.00 0.238145E+09 0.140474E+09 0.960758E+09
           
Annual Sum or Average 0.401049E+10 36599027.86 0.397389E+10 0.844001E+10 0.425528E+10
Minimum of Months 0.238145E+09 0.00 0.238145E+09 0.126910E+09 3573910.58
Maximum of Months 0.428128E+09 15560539.49 0.421349E+09 0.133332E+10 0.984260E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.581093E+09 0.233243E+09 0.347850E+09 0.581877E+09 0.989151E+09
February 0.637636E+09 0.263246E+09 0.374390E+09 0.820570E+09 0.687455E+09
March 0.861189E+09 0.355469E+09 0.505720E+09 0.140071E+10 0.438469E+09
April 0.991541E+09 0.462307E+09 0.529234E+09 0.201766E+10 0.139374E+09
May 0.100848E+10 0.447105E+09 0.561375E+09 0.236666E+10 22640970.60
June 0.794294E+09 0.263546E+09 0.530748E+09 0.207264E+10 15132845.67
July 0.689836E+09 0.145675E+09 0.544161E+09 0.176408E+10 2436678.38
August 0.621571E+09 0.108168E+09 0.513403E+09 0.149615E+10 9732023.79
September 0.642656E+09 0.179221E+09 0.463435E+09 0.134548E+10 55427648.53
October 0.726423E+09 0.293427E+09 0.432996E+09 0.134084E+10 0.342519E+09
November 0.623303E+09 0.267550E+09 0.355753E+09 0.919061E+09 0.651130E+09
December 0.561610E+09 0.222513E+09 0.339097E+09 0.612496E+09 0.960659E+09
           
Annual Sum or Average 0.873963E+10 0.324147E+10 0.549816E+10 0.167382E+11 0.431413E+10
Minimum of Months 0.561610E+09 0.108168E+09 0.339097E+09 0.581877E+09 2436678.38
Maximum of Months 0.100848E+10 0.462307E+09 0.561375E+09 0.236666E+10 0.989151E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.581093E+09 0.233243E+09 0.347850E+09 0.581877E+09 0.989151E+09
February 0.637636E+09 0.263246E+09 0.374390E+09 0.820570E+09 0.687455E+09
March 0.861189E+09 0.355469E+09 0.505720E+09 0.140071E+10 0.438469E+09
April 0.991541E+09 0.462307E+09 0.529234E+09 0.201766E+10 0.139374E+09
May 0.100848E+10 0.447105E+09 0.561375E+09 0.236666E+10 22640970.60
June 0.794294E+09 0.263546E+09 0.530748E+09 0.207264E+10 15132845.67
July 0.689836E+09 0.145675E+09 0.544161E+09 0.176408E+10 2436678.38
August 0.621571E+09 0.108168E+09 0.513403E+09 0.149615E+10 9732023.79
September 0.642656E+09 0.179221E+09 0.463435E+09 0.134548E+10 55427648.53
October 0.726423E+09 0.293427E+09 0.432996E+09 0.134084E+10 0.342519E+09
November 0.623303E+09 0.267550E+09 0.355753E+09 0.919061E+09 0.651130E+09
December 0.561610E+09 0.222513E+09 0.339097E+09 0.612496E+09 0.960659E+09
           
Annual Sum or Average 0.873963E+10 0.324147E+10 0.549816E+10 0.167382E+11 0.431413E+10
Minimum of Months 0.561610E+09 0.108168E+09 0.339097E+09 0.581877E+09 2436678.38
Maximum of Months 0.100848E+10 0.462307E+09 0.561375E+09 0.236666E+10 0.989151E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.581082E+09 0.233238E+09 0.347844E+09 0.581866E+09 0.989133E+09
February 0.637624E+09 0.263241E+09 0.374383E+09 0.820555E+09 0.687442E+09
March 0.861174E+09 0.355463E+09 0.505711E+09 0.140069E+10 0.438461E+09
April 0.991523E+09 0.462299E+09 0.529224E+09 0.201762E+10 0.139372E+09
May 0.100846E+10 0.447097E+09 0.561365E+09 0.236662E+10 22640556.90
June 0.794279E+09 0.263541E+09 0.530738E+09 0.207260E+10 15132569.16
July 0.689824E+09 0.145672E+09 0.544151E+09 0.176405E+10 2436633.85
August 0.621560E+09 0.108166E+09 0.513394E+09 0.149612E+10 9731845.97
September 0.642644E+09 0.179218E+09 0.463427E+09 0.134546E+10 55426635.74
October 0.726410E+09 0.293422E+09 0.432988E+09 0.134082E+10 0.342513E+09
November 0.623291E+09 0.267545E+09 0.355746E+09 0.919044E+09 0.651118E+09
December 0.561600E+09 0.222509E+09 0.339091E+09 0.612485E+09 0.960642E+09
           
Annual Sum or Average 0.873947E+10 0.324141E+10 0.549806E+10 0.167379E+11 0.431405E+10
Minimum of Months 0.561600E+09 0.108166E+09 0.339091E+09 0.581866E+09 2436633.85
Maximum of Months 0.100846E+10 0.462299E+09 0.561365E+09 0.236662E+10 0.989133E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111030E+10 0.674644E+09 0.435654E+09 0.152019E+10 0.895426E+09
February 0.953565E+09 0.529635E+09 0.423930E+09 0.142199E+10 0.651581E+09
March 0.902678E+09 0.398704E+09 0.503975E+09 0.157621E+10 0.437818E+09
April 0.613594E+09 0.173173E+09 0.440420E+09 0.141869E+10 0.148644E+09
May 0.455965E+09 33753370.59 0.422212E+09 0.136180E+10 22011699.92
June 0.403636E+09 6887849.73 0.396748E+09 0.130084E+10 15788643.85
July 0.435064E+09 5983889.20 0.429080E+09 0.124253E+10 3348161.86
August 0.461510E+09 24647909.05 0.436862E+09 0.116444E+10 14848119.75
September 0.598732E+09 0.155401E+09 0.443331E+09 0.128512E+10 60778256.41
October 0.106439E+10 0.594348E+09 0.470041E+09 0.197082E+10 0.344178E+09
November 0.128659E+10 0.850407E+09 0.436184E+09 0.208348E+10 0.635948E+09
December 0.118652E+10 0.743507E+09 0.443017E+09 0.168372E+10 0.891811E+09
           
Annual Sum or Average 0.947255E+10 0.419109E+10 0.528145E+10 0.180298E+11 0.412218E+10
Minimum of Months 0.403636E+09 5983889.20 0.396748E+09 0.116444E+10 3348161.86
Maximum of Months 0.128659E+10 0.850407E+09 0.503975E+09 0.208348E+10 0.895426E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111029E+10 0.674639E+09 0.435651E+09 0.152018E+10 0.895425E+09
February 0.953558E+09 0.529631E+09 0.423927E+09 0.142198E+10 0.651581E+09
March 0.902673E+09 0.398701E+09 0.503972E+09 0.157620E+10 0.437817E+09
April 0.613590E+09 0.173172E+09 0.440418E+09 0.141868E+10 0.148644E+09
May 0.455963E+09 33753123.25 0.422210E+09 0.136179E+10 22011446.13
June 0.403635E+09 6887799.25 0.396747E+09 0.130084E+10 15788559.17
July 0.435061E+09 5983845.35 0.429078E+09 0.124252E+10 3348117.42
August 0.461507E+09 24647728.43 0.436859E+09 0.116444E+10 14847981.59
September 0.598729E+09 0.155400E+09 0.443328E+09 0.128511E+10 60777770.87
October 0.106438E+10 0.594344E+09 0.470039E+09 0.197081E+10 0.344177E+09
November 0.128658E+10 0.850401E+09 0.436181E+09 0.208347E+10 0.635946E+09
December 0.118652E+10 0.743502E+09 0.443014E+09 0.168371E+10 0.891810E+09
           
Annual Sum or Average 0.947249E+10 0.419106E+10 0.528143E+10 0.180297E+11 0.412217E+10
Minimum of Months 0.403635E+09 5983845.35 0.396747E+09 0.116444E+10 3348117.42
Maximum of Months 0.128658E+10 0.850401E+09 0.503972E+09 0.208347E+10 0.895425E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111030E+10 0.674644E+09 0.435654E+09 0.152019E+10 0.895426E+09
February 0.953565E+09 0.529635E+09 0.423930E+09 0.142199E+10 0.651581E+09
March 0.902678E+09 0.398704E+09 0.503975E+09 0.157621E+10 0.437818E+09
April 0.613594E+09 0.173173E+09 0.440420E+09 0.141869E+10 0.148644E+09
May 0.455965E+09 33753370.59 0.422212E+09 0.136180E+10 22011699.92
June 0.403636E+09 6887849.73 0.396748E+09 0.130084E+10 15788643.85
July 0.435064E+09 5983889.20 0.429080E+09 0.124253E+10 3348161.86
August 0.461510E+09 24647909.05 0.436862E+09 0.116444E+10 14848119.75
September 0.598732E+09 0.155401E+09 0.443331E+09 0.128512E+10 60778256.41
October 0.106439E+10 0.594348E+09 0.470041E+09 0.197082E+10 0.344178E+09
November 0.128659E+10 0.850407E+09 0.436184E+09 0.208348E+10 0.635948E+09
December 0.118652E+10 0.743507E+09 0.443017E+09 0.168372E+10 0.891811E+09
           
Annual Sum or Average 0.947255E+10 0.419109E+10 0.528145E+10 0.180298E+11 0.412218E+10
Minimum of Months 0.403636E+09 5983889.20 0.396748E+09 0.116444E+10 3348161.86
Maximum of Months 0.128659E+10 0.850407E+09 0.503975E+09 0.208348E+10 0.895426E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111029E+10 0.674639E+09 0.435651E+09 0.152018E+10 0.895425E+09
February 0.953558E+09 0.529631E+09 0.423927E+09 0.142198E+10 0.651581E+09
March 0.902673E+09 0.398701E+09 0.503972E+09 0.157620E+10 0.437817E+09
April 0.613590E+09 0.173172E+09 0.440418E+09 0.141868E+10 0.148644E+09
May 0.455963E+09 33753123.25 0.422210E+09 0.136179E+10 22011446.13
June 0.403635E+09 6887799.25 0.396747E+09 0.130084E+10 15788559.17
July 0.435061E+09 5983845.35 0.429078E+09 0.124252E+10 3348117.42
August 0.461507E+09 24647728.43 0.436859E+09 0.116444E+10 14847981.59
September 0.598729E+09 0.155400E+09 0.443328E+09 0.128511E+10 60777770.87
October 0.106438E+10 0.594344E+09 0.470039E+09 0.197081E+10 0.344177E+09
November 0.128658E+10 0.850401E+09 0.436181E+09 0.208347E+10 0.635946E+09
December 0.118652E+10 0.743502E+09 0.443014E+09 0.168371E+10 0.891810E+09
           
Annual Sum or Average 0.947249E+10 0.419106E+10 0.528143E+10 0.180297E+11 0.412217E+10
Minimum of Months 0.403635E+09 5983845.35 0.396747E+09 0.116444E+10 3348117.42
Maximum of Months 0.128658E+10 0.850401E+09 0.503972E+09 0.208347E+10 0.895425E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111025E+10 0.674614E+09 0.435635E+09 0.152012E+10 0.895389E+09
February 0.953523E+09 0.529612E+09 0.423911E+09 0.142192E+10 0.651555E+09
March 0.902639E+09 0.398686E+09 0.503953E+09 0.157615E+10 0.437800E+09
April 0.613567E+09 0.173166E+09 0.440401E+09 0.141863E+10 0.148638E+09
May 0.455946E+09 33751886.52 0.422194E+09 0.136174E+10 22010685.86
June 0.403619E+09 6887546.88 0.396732E+09 0.130079E+10 15787965.16
July 0.435045E+09 5983626.10 0.429061E+09 0.124247E+10 3348004.70
August 0.461490E+09 24646825.33 0.436843E+09 0.116439E+10 14847452.23
September 0.598706E+09 0.155394E+09 0.443312E+09 0.128506E+10 60775564.02
October 0.106434E+10 0.594322E+09 0.470021E+09 0.197073E+10 0.344164E+09
November 0.128653E+10 0.850370E+09 0.436165E+09 0.208339E+10 0.635921E+09
December 0.118647E+10 0.743475E+09 0.442998E+09 0.168365E+10 0.891775E+09
           
Annual Sum or Average 0.947214E+10 0.419091E+10 0.528123E+10 0.180291E+11 0.412201E+10
Minimum of Months 0.403619E+09 5983626.10 0.396732E+09 0.116439E+10 3348004.70
Maximum of Months 0.128653E+10 0.850370E+09 0.503953E+09 0.208339E+10 0.895389E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.568506E+09 0.221241E+09 0.347265E+09 0.625375E+09 0.114644E+10
February 0.587189E+09 0.216395E+09 0.370794E+09 0.762529E+09 0.830604E+09
March 0.843016E+09 0.336983E+09 0.506033E+09 0.135585E+10 0.565909E+09
April 0.991624E+09 0.465034E+09 0.526590E+09 0.194996E+10 0.231836E+09
May 0.970274E+09 0.411570E+09 0.558703E+09 0.225920E+10 40541581.02
June 0.881948E+09 0.342572E+09 0.539376E+09 0.215291E+10 30673409.98
July 0.676266E+09 0.131534E+09 0.544732E+09 0.162780E+10 14155394.26
August 0.621079E+09 0.110385E+09 0.510694E+09 0.136872E+10 54286970.82
September 0.660705E+09 0.193964E+09 0.466741E+09 0.134616E+10 92417919.92
October 0.710616E+09 0.282966E+09 0.427650E+09 0.130142E+10 0.428254E+09
November 0.622131E+09 0.265149E+09 0.356983E+09 0.931977E+09 0.806416E+09
December 0.550107E+09 0.209768E+09 0.340339E+09 0.601462E+09 0.118701E+10
           
Annual Sum or Average 0.868346E+10 0.318756E+10 0.549590E+10 0.162834E+11 0.542855E+10
Minimum of Months 0.550107E+09 0.110385E+09 0.340339E+09 0.601462E+09 14155394.26
Maximum of Months 0.991624E+09 0.465034E+09 0.558703E+09 0.225920E+10 0.118701E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.568506E+09 0.221241E+09 0.347265E+09 0.625375E+09 0.114644E+10
February 0.587189E+09 0.216395E+09 0.370794E+09 0.762529E+09 0.830604E+09
March 0.843016E+09 0.336983E+09 0.506033E+09 0.135585E+10 0.565909E+09
April 0.991624E+09 0.465034E+09 0.526590E+09 0.194996E+10 0.231836E+09
May 0.970274E+09 0.411570E+09 0.558703E+09 0.225920E+10 40541581.02
June 0.881948E+09 0.342572E+09 0.539376E+09 0.215291E+10 30673409.98
July 0.676266E+09 0.131534E+09 0.544732E+09 0.162780E+10 14155394.26
August 0.621079E+09 0.110385E+09 0.510694E+09 0.136872E+10 54286970.82
September 0.660705E+09 0.193964E+09 0.466741E+09 0.134616E+10 92417919.92
October 0.710616E+09 0.282966E+09 0.427650E+09 0.130142E+10 0.428254E+09
November 0.622131E+09 0.265149E+09 0.356983E+09 0.931977E+09 0.806416E+09
December 0.550107E+09 0.209768E+09 0.340339E+09 0.601462E+09 0.118701E+10
           
Annual Sum or Average 0.868346E+10 0.318756E+10 0.549590E+10 0.162834E+11 0.542855E+10
Minimum of Months 0.550107E+09 0.110385E+09 0.340339E+09 0.601462E+09 14155394.26
Maximum of Months 0.991624E+09 0.465034E+09 0.558703E+09 0.225920E+10 0.118701E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.568496E+09 0.221237E+09 0.347259E+09 0.625364E+09 0.114642E+10
February 0.587178E+09 0.216391E+09 0.370787E+09 0.762515E+09 0.830589E+09
March 0.843001E+09 0.336977E+09 0.506024E+09 0.135583E+10 0.565898E+09
April 0.991605E+09 0.465025E+09 0.526580E+09 0.194993E+10 0.231831E+09
May 0.970256E+09 0.411563E+09 0.558693E+09 0.225916E+10 40540840.23
June 0.881932E+09 0.342566E+09 0.539366E+09 0.215287E+10 30672849.51
July 0.676253E+09 0.131532E+09 0.544722E+09 0.162777E+10 14155135.61
August 0.621068E+09 0.110383E+09 0.510685E+09 0.136870E+10 54285978.88
September 0.660693E+09 0.193961E+09 0.466732E+09 0.134614E+10 92416231.25
October 0.710603E+09 0.282961E+09 0.427642E+09 0.130140E+10 0.428246E+09
November 0.622120E+09 0.265144E+09 0.356976E+09 0.931960E+09 0.806401E+09
December 0.550097E+09 0.209764E+09 0.340333E+09 0.601451E+09 0.118699E+10
           
Annual Sum or Average 0.868330E+10 0.318750E+10 0.549580E+10 0.162831E+11 0.542845E+10
Minimum of Months 0.550097E+09 0.110383E+09 0.340333E+09 0.601451E+09 14155135.61
Maximum of Months 0.991605E+09 0.465025E+09 0.558693E+09 0.225916E+10 0.118699E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122067E+10 0.00 0.122067E+10 0.756676E+09 0.444286E+10
February 0.130743E+10 0.00 0.130743E+10 0.130253E+10 0.310198E+10
March 0.174425E+10 0.00 0.174425E+10 0.270227E+10 0.203953E+10
April 0.183160E+10 6211571.55 0.182539E+10 0.450275E+10 0.663896E+09
May 0.209692E+10 58843614.39 0.203808E+10 0.642238E+10 0.111234E+09
June 0.210063E+10 77807754.61 0.202282E+10 0.673352E+10 84736153.23
July 0.214076E+10 33900208.49 0.210686E+10 0.619321E+10 23045251.77
August 0.196528E+10 6124891.54 0.195915E+10 0.523278E+10 74549790.00
September 0.169463E+10 118993.41 0.169451E+10 0.394696E+10 0.281557E+09
October 0.151703E+10 0.00 0.151703E+10 0.298614E+10 0.157665E+10
November 0.124349E+10 0.00 0.124349E+10 0.160385E+10 0.295894E+10
December 0.119078E+10 0.00 0.119078E+10 0.854502E+09 0.427481E+10
           
Annual Sum or Average 0.200535E+11 0.183007E+09 0.198705E+11 0.432376E+11 0.196338E+11
Minimum of Months 0.119078E+10 0.00 0.119078E+10 0.756676E+09 23045251.77
Maximum of Months 0.214076E+10 77807754.61 0.210686E+10 0.673352E+10 0.444286E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174326E+10 0.699721E+09 0.104354E+10 0.181095E+10 0.276542E+10
February 0.191289E+10 0.789730E+09 0.112316E+10 0.248095E+10 0.197255E+10
March 0.258354E+10 0.106640E+10 0.151715E+10 0.418135E+10 0.133369E+10
April 0.297459E+10 0.138691E+10 0.158769E+10 0.602233E+10 0.468072E+09
May 0.302541E+10 0.134130E+10 0.168411E+10 0.707583E+10 77815196.25
June 0.238286E+10 0.790630E+09 0.159223E+10 0.619111E+10 57878419.62
July 0.206949E+10 0.437021E+09 0.163247E+10 0.525505E+10 13610752.54
August 0.186469E+10 0.324501E+09 0.154019E+10 0.445086E+10 51037486.80
September 0.192795E+10 0.537657E+09 0.139029E+10 0.401435E+10 0.197736E+09
October 0.217925E+10 0.880272E+09 0.129897E+10 0.400895E+10 0.105631E+10
November 0.186989E+10 0.802641E+09 0.106725E+10 0.277171E+10 0.190486E+10
December 0.168481E+10 0.667533E+09 0.101728E+10 0.190136E+10 0.271335E+10
           
Annual Sum or Average 0.262186E+11 0.972431E+10 0.164943E+11 0.501648E+11 0.126123E+11
Minimum of Months 0.168481E+10 0.324501E+09 0.101728E+10 0.181095E+10 13610752.54
Maximum of Months 0.302541E+10 0.138691E+10 0.168411E+10 0.707583E+10 0.276542E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555159E+10 0.337329E+10 0.217830E+10 0.755077E+10 0.441953E+10
February 0.476791E+10 0.264823E+10 0.211968E+10 0.706774E+10 0.320457E+10
March 0.451346E+10 0.199356E+10 0.251990E+10 0.785360E+10 0.218080E+10
April 0.306800E+10 0.865885E+09 0.220212E+10 0.713294E+10 0.748010E+09
May 0.227984E+10 0.168770E+09 0.211107E+10 0.686946E+10 0.111473E+09
June 0.201820E+10 34439972.86 0.198376E+10 0.657707E+10 83646886.49
July 0.217534E+10 29920075.17 0.214542E+10 0.629082E+10 20327321.27
August 0.230758E+10 0.123242E+09 0.218434E+10 0.591654E+10 78061325.72
September 0.299371E+10 0.777023E+09 0.221668E+10 0.641542E+10 0.327571E+09
October 0.532204E+10 0.297180E+10 0.235023E+10 0.981759E+10 0.175096E+10
November 0.643307E+10 0.425213E+10 0.218095E+10 0.103731E+11 0.315949E+10
December 0.593273E+10 0.371762E+10 0.221512E+10 0.840450E+10 0.434705E+10
           
Annual Sum or Average 0.473635E+11 0.209559E+11 0.264076E+11 0.902696E+11 0.204315E+11
Minimum of Months 0.201820E+10 29920075.17 0.198376E+10 0.591654E+10 20327321.27
Maximum of Months 0.643307E+10 0.425213E+10 0.251990E+10 0.103731E+11 0.441953E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170550E+10 0.663716E+09 0.104178E+10 0.196771E+10 0.306039E+10
February 0.176155E+10 0.649178E+09 0.111237E+10 0.237465E+10 0.218753E+10
March 0.252902E+10 0.101094E+10 0.151808E+10 0.415297E+10 0.149540E+10
April 0.297484E+10 0.139509E+10 0.157975E+10 0.600594E+10 0.548230E+09
May 0.291079E+10 0.123470E+10 0.167609E+10 0.685456E+10 0.104761E+09
June 0.264582E+10 0.102771E+10 0.161811E+10 0.659542E+10 74392060.00
July 0.202878E+10 0.394598E+09 0.163418E+10 0.509057E+10 22386456.82
August 0.186322E+10 0.331151E+09 0.153207E+10 0.438375E+10 67393117.14
September 0.198210E+10 0.581887E+09 0.140021E+10 0.408930E+10 0.238757E+09
October 0.213182E+10 0.848889E+09 0.128294E+10 0.397174E+10 0.116320E+10
November 0.186638E+10 0.795438E+09 0.107094E+10 0.290168E+10 0.211469E+10
December 0.165030E+10 0.629299E+09 0.102101E+10 0.197452E+10 0.296428E+10
           
Annual Sum or Average 0.260501E+11 0.956259E+10 0.164875E+11 0.503628E+11 0.140414E+11
Minimum of Months 0.165030E+10 0.331151E+09 0.102101E+10 0.196771E+10 22386456.82
Maximum of Months 0.297484E+10 0.139509E+10 0.167609E+10 0.685456E+10 0.306039E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.122067E+10 0.00 0.122067E+10 0.926004E+09 0.385822E+10
February 0.130743E+10 0.00 0.130743E+10 0.139731E+10 0.282356E+10
March 0.174425E+10 0.00 0.174425E+10 0.270144E+10 0.196029E+10
April 0.183160E+10 6211571.55 0.182539E+10 0.442581E+10 0.670970E+09
May 0.209692E+10 58843614.39 0.203808E+10 0.629584E+10 0.125302E+09
June 0.210063E+10 77807754.61 0.202282E+10 0.659860E+10 95200721.54
July 0.214076E+10 33900208.49 0.210686E+10 0.605485E+10 25632722.24
August 0.196528E+10 6124891.54 0.195915E+10 0.512401E+10 84073321.09
September 0.169463E+10 118993.41 0.169451E+10 0.388441E+10 0.293305E+09
October 0.151703E+10 0.00 0.151703E+10 0.296822E+10 0.153517E+10
November 0.124349E+10 0.00 0.124349E+10 0.167001E+10 0.274700E+10
December 0.119078E+10 0.00 0.119078E+10 0.101430E+10 0.379217E+10
           
Annual Sum or Average 0.200535E+11 0.183007E+09 0.198705E+11 0.430608E+11 0.180109E+11
Minimum of Months 0.119078E+10 0.00 0.119078E+10 0.926004E+09 25632722.24
Maximum of Months 0.214076E+10 77807754.61 0.210686E+10 0.659860E+10 0.385822E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.174326E+10 0.699721E+09 0.104354E+10 0.196537E+10 0.244085E+10
February 0.191289E+10 0.789730E+09 0.112316E+10 0.254442E+10 0.183518E+10
March 0.258354E+10 0.106640E+10 0.151715E+10 0.417223E+10 0.130370E+10
April 0.297459E+10 0.138691E+10 0.158769E+10 0.596414E+10 0.479036E+09
May 0.302541E+10 0.134130E+10 0.168411E+10 0.698338E+10 88544188.33
June 0.238286E+10 0.790630E+09 0.159223E+10 0.609433E+10 65594359.36
July 0.206949E+10 0.437021E+09 0.163247E+10 0.515764E+10 15020457.82
August 0.186469E+10 0.324501E+09 0.154019E+10 0.437436E+10 57794006.36
September 0.192795E+10 0.537657E+09 0.139029E+10 0.396885E+10 0.207012E+09
October 0.217925E+10 0.880272E+09 0.129897E+10 0.399114E+10 0.104270E+10
November 0.186989E+10 0.802641E+09 0.106725E+10 0.281147E+10 0.180485E+10
December 0.168481E+10 0.667533E+09 0.101728E+10 0.203102E+10 0.245871E+10
           
Annual Sum or Average 0.262186E+11 0.972431E+10 0.164943E+11 0.500584E+11 0.117990E+11
Minimum of Months 0.168481E+10 0.324501E+09 0.101728E+10 0.196537E+10 15020457.82
Maximum of Months 0.302541E+10 0.138691E+10 0.168411E+10 0.698338E+10 0.245871E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.555159E+10 0.337329E+10 0.217830E+10 0.771902E+10 0.396369E+10
February 0.476791E+10 0.264823E+10 0.211968E+10 0.712555E+10 0.300079E+10
March 0.451346E+10 0.199356E+10 0.251990E+10 0.782744E+10 0.213106E+10
April 0.306800E+10 0.865885E+09 0.220212E+10 0.704982E+10 0.762537E+09
May 0.227984E+10 0.168770E+09 0.211107E+10 0.674202E+10 0.125578E+09
June 0.201820E+10 34439972.86 0.198376E+10 0.644101E+10 94630488.00
July 0.217534E+10 29920075.17 0.214542E+10 0.615142E+10 22469016.34
August 0.230758E+10 0.123242E+09 0.218434E+10 0.580611E+10 88243698.41
September 0.299371E+10 0.777023E+09 0.221668E+10 0.634662E+10 0.344265E+09
October 0.532204E+10 0.297180E+10 0.235023E+10 0.977826E+10 0.173753E+10
November 0.643307E+10 0.425213E+10 0.218095E+10 0.103914E+11 0.302760E+10
December 0.593273E+10 0.371762E+10 0.221512E+10 0.854166E+10 0.400397E+10
           
Annual Sum or Average 0.473635E+11 0.209559E+11 0.264076E+11 0.899203E+11 0.193024E+11
Minimum of Months 0.201820E+10 29920075.17 0.198376E+10 0.580611E+10 22469016.34
Maximum of Months 0.643307E+10 0.425213E+10 0.251990E+10 0.103914E+11 0.400397E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.170550E+10 0.663716E+09 0.104178E+10 0.205664E+10 0.274444E+10
February 0.176155E+10 0.649178E+09 0.111237E+10 0.241604E+10 0.203617E+10
March 0.252902E+10 0.101094E+10 0.151808E+10 0.413917E+10 0.145554E+10
April 0.297484E+10 0.139509E+10 0.157975E+10 0.595408E+10 0.553672E+09
May 0.291079E+10 0.123470E+10 0.167609E+10 0.677802E+10 0.112825E+09
June 0.264582E+10 0.102771E+10 0.161811E+10 0.651382E+10 79833431.80
July 0.202878E+10 0.394598E+09 0.163418E+10 0.501006E+10 24005839.07
August 0.186322E+10 0.331151E+09 0.153207E+10 0.432287E+10 73117717.19
September 0.198210E+10 0.581887E+09 0.140021E+10 0.404981E+10 0.245201E+09
October 0.213182E+10 0.848889E+09 0.128294E+10 0.395383E+10 0.114256E+10
November 0.186638E+10 0.795438E+09 0.107094E+10 0.292642E+10 0.200251E+10
December 0.165030E+10 0.629299E+09 0.102101E+10 0.205705E+10 0.270416E+10
           
Annual Sum or Average 0.260501E+11 0.956259E+10 0.164875E+11 0.501778E+11 0.131740E+11
Minimum of Months 0.165030E+10 0.331151E+09 0.102101E+10 0.205664E+10 24005839.07
Maximum of Months 0.297484E+10 0.139509E+10 0.167609E+10 0.677802E+10 0.274444E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 236.92 1837.46 455.74 0.00 455.74 0.00 0.00
February 500.16 1397.98 540.43 0.00 540.43 0.00 0.00
March 986.75 796.91 651.22 0.00 651.22 0.00 0.00
April 1695.93 263.04 706.63 2.40 704.23 0.00 0.00
May 2373.94 40.18 782.89 21.97 760.92 0.00 0.00
June 2572.08 30.17 810.41 30.02 780.40 0.00 0.00
July 2284.84 6.67 799.25 12.66 786.60 0.00 0.00
August 1910.07 26.45 733.74 2.29 731.45 0.00 0.00
September 1511.23 104.04 653.78 0.05 653.73 0.00 0.00
October 1093.28 604.22 566.39 0.00 566.39 0.00 0.00
November 582.38 1231.06 479.74 0.00 479.74 0.00 0.00
December 262.24 1793.59 444.58 0.00 444.58 0.00 0.00
               
Annual Sum or Average 1338.20 674.69 635.88 5.80 630.08 0.00 0.00
Minimum of Months 236.92 6.67 444.58 0.00 444.58 0.00 0.00
Maximum of Months 2572.08 1837.46 810.41 30.02 786.60 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 651.74 1107.91 650.86 261.25 389.61 0.00 0.00
February 1017.57 852.49 790.71 326.44 464.27 0.00 0.00
March 1568.89 491.11 964.59 398.15 566.44 0.00 0.00
April 2335.24 161.31 1147.61 535.07 612.54 0.00 0.00
May 2650.82 25.36 1129.56 500.79 628.78 0.00 0.00
June 2398.87 17.51 919.32 305.03 614.29 0.00 0.00
July 1975.89 2.73 772.66 163.17 609.50 0.00 0.00
August 1675.78 10.90 696.20 121.16 575.04 0.00 0.00
September 1557.26 64.15 743.81 207.43 536.38 0.00 0.00
October 1501.83 383.64 813.64 328.66 484.98 0.00 0.00
November 1063.72 753.62 721.41 309.66 411.75 0.00 0.00
December 686.04 1076.00 629.04 249.23 379.81 0.00 0.00
               
Annual Sum or Average 1592.29 410.40 831.39 308.36 523.03 0.00 0.00
Minimum of Months 651.74 2.73 629.04 121.16 379.81 0.00 0.00
Maximum of Months 2650.82 1107.91 1147.61 535.07 628.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2837.84 1671.55 2072.66 1259.40 813.26 0.00 0.00
February 2938.93 1346.68 1970.80 1094.64 876.17 0.00 0.00
March 2942.42 817.30 1685.09 744.29 940.80 0.00 0.00
April 2736.64 286.73 1183.62 334.05 849.57 0.00 0.00
May 2542.16 41.09 851.18 63.01 788.17 0.00 0.00
June 2509.31 30.46 778.61 13.29 765.32 0.00 0.00
July 2319.51 6.25 812.16 11.17 800.99 0.00 0.00
August 2173.75 27.72 861.53 46.01 815.52 0.00 0.00
September 2478.98 117.24 1154.95 299.77 855.18 0.00 0.00
October 3679.06 642.50 1986.97 1109.51 877.46 0.00 0.00
November 4019.01 1226.74 2481.82 1640.43 841.39 0.00 0.00
December 3143.11 1664.81 2214.96 1387.95 827.01 0.00 0.00
               
Annual Sum or Average 2858.58 653.56 1501.85 664.49 837.36 0.00 0.00
Minimum of Months 2173.75 6.25 778.61 11.17 765.32 0.00 0.00
Maximum of Months 4019.01 1671.55 2481.82 1640.43 940.80 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 700.46 1284.09 636.76 247.80 388.96 0.00 0.00
February 945.59 1030.01 728.16 268.35 459.81 0.00 0.00
March 1518.64 633.85 944.23 377.44 566.79 0.00 0.00
April 2256.89 268.33 1147.71 538.23 609.48 0.00 0.00
May 2530.45 45.41 1086.77 460.99 625.78 0.00 0.00
June 2491.78 35.50 1020.77 396.49 624.27 0.00 0.00
July 1823.24 15.85 757.46 147.33 610.13 0.00 0.00
August 1533.06 60.80 695.65 123.64 572.01 0.00 0.00
September 1558.05 106.96 764.70 224.49 540.21 0.00 0.00
October 1457.68 479.67 795.94 316.94 479.00 0.00 0.00
November 1078.67 933.35 720.06 306.88 413.17 0.00 0.00
December 673.68 1329.53 616.16 234.95 381.20 0.00 0.00
               
Annual Sum or Average 1549.02 516.41 826.05 303.23 522.82 0.00 0.00
Minimum of Months 673.68 15.85 616.16 123.64 381.20 0.00 0.00
Maximum of Months 2530.45 1329.53 1147.71 538.23 625.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 282.51 1658.77 455.75 0.00 455.75 0.00 0.00
February 538.41 1282.23 540.44 0.00 540.44 0.00 0.00
March 1008.91 761.47 651.23 0.00 651.23 0.00 0.00
April 1737.17 256.13 706.64 2.40 704.24 0.00 0.00
May 2397.84 41.53 782.90 21.97 760.93 0.00 0.00
June 2597.81 32.69 810.43 30.02 780.41 0.00 0.00
July 2312.28 8.60 799.27 12.66 786.61 0.00 0.00
August 1953.70 27.83 733.75 2.29 731.46 0.00 0.00
September 1522.75 108.63 653.79 0.05 653.75 0.00 0.00
October 1114.90 588.65 566.40 0.00 566.40 0.00 0.00
November 618.77 1141.57 479.74 0.00 479.74 0.00 0.00
December 319.03 1596.03 444.59 0.00 444.59 0.00 0.00
               
Annual Sum or Average 1371.05 622.58 635.89 5.80 630.09 0.00 0.00
Minimum of Months 282.51 8.60 444.59 0.00 444.59 0.00 0.00
Maximum of Months 2597.81 1658.77 810.43 30.02 786.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 676.13 1032.49 650.86 261.25 389.61 0.00 0.00
February 1025.52 815.37 790.71 326.44 464.27 0.00 0.00
March 1561.14 497.94 964.58 398.15 566.44 0.00 0.00
April 2323.43 180.58 1147.61 535.07 612.53 0.00 0.00
May 2641.81 29.05 1129.56 500.78 628.77 0.00 0.00
June 2388.54 22.33 919.31 305.03 614.29 0.00 0.00
July 1962.01 5.08 772.66 163.16 609.49 0.00 0.00
August 1661.76 19.06 696.20 121.15 575.04 0.00 0.00
September 1548.74 76.29 743.81 207.43 536.38 0.00 0.00
October 1496.77 394.38 813.64 328.66 484.98 0.00 0.00
November 1069.33 734.90 721.41 309.66 411.75 0.00 0.00
December 709.89 1013.05 629.04 249.23 379.81 0.00 0.00
               
Annual Sum or Average 1590.71 399.93 831.39 308.36 523.03 0.00 0.00
Minimum of Months 676.13 5.08 629.04 121.15 379.81 0.00 0.00
Maximum of Months 2641.81 1032.49 1147.61 535.07 628.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2819.13 1650.06 2072.73 1259.44 813.28 0.00 0.00
February 2921.52 1324.64 1970.86 1094.67 876.19 0.00 0.00
March 2932.20 814.22 1685.13 744.31 940.82 0.00 0.00
April 2751.91 288.58 1183.64 334.06 849.58 0.00 0.00
May 2564.76 41.62 851.20 63.01 788.18 0.00 0.00
June 2537.45 32.27 778.63 13.29 765.34 0.00 0.00
July 2348.72 7.59 812.18 11.17 801.01 0.00 0.00
August 2208.98 29.14 861.55 46.01 815.54 0.00 0.00
September 2475.08 126.38 1154.98 299.78 855.20 0.00 0.00
October 3665.47 653.74 1987.02 1109.54 877.48 0.00 0.00
November 4001.99 1218.94 2481.90 1640.48 841.42 0.00 0.00
December 3137.88 1623.00 2215.03 1388.00 827.03 0.00 0.00
               
Annual Sum or Average 2862.43 647.88 1501.89 664.51 837.38 0.00 0.00
Minimum of Months 2208.98 7.59 778.63 11.17 765.34 0.00 0.00
Maximum of Months 4001.99 1650.06 2481.90 1640.48 940.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 734.66 1142.62 636.76 247.80 388.96 0.00 0.00
February 981.58 904.24 728.15 268.34 459.81 0.00 0.00
March 1550.54 558.32 944.23 377.44 566.79 0.00 0.00
April 2317.11 211.51 1147.70 538.23 609.47 0.00 0.00
May 2559.20 39.11 1086.77 460.98 625.78 0.00 0.00
June 2544.53 28.70 1020.76 396.49 624.27 0.00 0.00
July 1900.60 8.36 757.46 147.33 610.13 0.00 0.00
August 1636.70 25.16 695.65 123.64 572.01 0.00 0.00
September 1577.66 92.11 764.70 224.49 540.20 0.00 0.00
October 1482.88 434.29 795.93 316.94 478.99 0.00 0.00
November 1119.48 815.85 720.05 306.88 413.17 0.00 0.00
December 737.20 1106.73 616.15 234.95 381.20 0.00 0.00
               
Annual Sum or Average 1596.99 445.25 826.04 303.23 522.82 0.00 0.00
Minimum of Months 734.66 8.36 616.15 123.64 381.20 0.00 0.00
Maximum of Months 2559.20 1142.62 1147.70 538.23 625.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 345.73 1440.50 455.75 0.00 455.75 0.00 0.00
February 577.59 1167.14 540.44 0.00 540.44 0.00 0.00
March 1008.60 731.89 651.23 0.00 651.23 0.00 0.00
April 1707.49 258.86 706.64 2.40 704.24 0.00 0.00
May 2350.60 46.78 782.90 21.97 760.93 0.00 0.00
June 2545.76 36.73 810.43 30.02 780.41 0.00 0.00
July 2260.62 9.57 799.27 12.66 786.61 0.00 0.00
August 1913.09 31.39 733.75 2.29 731.46 0.00 0.00
September 1498.61 113.16 653.79 0.05 653.75 0.00 0.00
October 1108.21 573.17 566.40 0.00 566.40 0.00 0.00
November 644.29 1059.80 479.74 0.00 479.74 0.00 0.00
December 378.69 1415.83 444.59 0.00 444.59 0.00 0.00
               
Annual Sum or Average 1365.45 571.12 635.89 5.80 630.09 0.00 0.00
Minimum of Months 345.73 9.57 444.59 0.00 444.59 0.00 0.00
Maximum of Months 2545.76 1440.50 810.43 30.02 786.61 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 733.79 911.31 650.86 261.25 389.61 0.00 0.00
February 1051.76 758.59 790.71 326.44 464.27 0.00 0.00
March 1557.73 486.74 964.58 398.15 566.44 0.00 0.00
April 2300.98 184.81 1147.61 535.07 612.53 0.00 0.00
May 2607.29 33.06 1129.56 500.78 628.77 0.00 0.00
June 2351.21 25.31 919.31 305.03 614.29 0.00 0.00
July 1925.64 5.61 772.66 163.16 609.49 0.00 0.00
August 1633.20 21.58 696.20 121.15 575.04 0.00 0.00
September 1531.19 79.87 743.81 207.43 536.38 0.00 0.00
October 1490.12 389.30 813.64 328.66 484.98 0.00 0.00
November 1084.67 696.32 721.41 309.66 411.75 0.00 0.00
December 758.30 917.98 629.04 249.23 379.81 0.00 0.00
               
Annual Sum or Average 1587.34 374.14 831.39 308.36 523.03 0.00 0.00
Minimum of Months 733.79 5.61 629.04 121.15 379.81 0.00 0.00
Maximum of Months 2607.29 917.98 1147.61 535.07 628.77 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2881.95 1479.87 2072.73 1259.44 813.28 0.00 0.00
February 2945.42 1240.41 1970.86 1094.67 876.19 0.00 0.00
March 2922.43 795.65 1685.13 744.31 940.82 0.00 0.00
April 2719.84 294.19 1183.64 334.06 849.58 0.00 0.00
May 2517.18 46.89 851.20 63.01 788.18 0.00 0.00
June 2484.96 36.51 778.63 13.29 765.34 0.00 0.00
July 2296.68 8.39 812.18 11.17 801.01 0.00 0.00
August 2167.75 32.95 861.55 46.01 815.54 0.00 0.00
September 2448.54 132.82 1154.98 299.78 855.20 0.00 0.00
October 3650.78 648.72 1987.02 1109.54 877.48 0.00 0.00
November 4009.02 1168.05 2481.90 1640.48 841.42 0.00 0.00
December 3189.09 1494.91 2215.03 1388.00 827.03 0.00 0.00
               
Annual Sum or Average 2851.35 612.07 1501.89 664.51 837.38 0.00 0.00
Minimum of Months 2167.75 8.39 778.63 11.17 765.34 0.00 0.00
Maximum of Months 4009.02 1494.91 2481.90 1640.48 940.82 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 767.86 1024.66 636.76 247.80 388.96 0.00 0.00
February 998.69 841.67 728.15 268.34 459.81 0.00 0.00
March 1545.39 543.44 944.23 377.44 566.79 0.00 0.00
April 2297.10 213.61 1147.70 538.23 609.47 0.00 0.00
May 2530.62 42.12 1086.77 460.98 625.78 0.00 0.00
June 2513.05 30.80 1020.76 396.49 624.27 0.00 0.00
July 1870.54 8.96 757.46 147.33 610.13 0.00 0.00
August 1613.97 27.30 695.65 123.64 572.01 0.00 0.00
September 1562.43 94.60 764.70 224.49 540.20 0.00 0.00
October 1476.19 426.58 795.93 316.94 478.99 0.00 0.00
November 1129.02 772.57 720.05 306.88 413.17 0.00 0.00
December 768.01 1009.62 616.15 234.95 381.20 0.00 0.00
               
Annual Sum or Average 1591.13 417.75 826.04 303.23 522.82 0.00 0.00
Minimum of Months 767.86 8.96 616.15 123.64 381.20 0.00 0.00
Maximum of Months 2530.62 1024.66 1147.70 538.23 625.78 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.634572E+09 0.492146E+10 0.122065E+10 0.00 0.122065E+10 0.00 0.00
February 0.121000E+10 0.338199E+10 0.130740E+10 0.00 0.130740E+10 0.00 0.00
March 0.264292E+10 0.213445E+10 0.174422E+10 0.00 0.174422E+10 0.00 0.00
April 0.439584E+10 0.681800E+09 0.183157E+10 6211386.31 0.182536E+10 0.00 0.00
May 0.635836E+10 0.107613E+09 0.209689E+10 58841859.56 0.203805E+10 0.00 0.00
June 0.666683E+10 78210352.67 0.210059E+10 77805434.24 0.202279E+10 0.00 0.00
July 0.611972E+10 17870229.94 0.214072E+10 33899197.52 0.210682E+10 0.00 0.00
August 0.511592E+10 70848635.86 0.196524E+10 6124708.88 0.195911E+10 0.00 0.00
September 0.391712E+10 0.269666E+09 0.169460E+10 118989.86 0.169448E+10 0.00 0.00
October 0.292824E+10 0.161835E+10 0.151701E+10 0.00 0.151701E+10 0.00 0.00
November 0.150954E+10 0.319091E+10 0.124347E+10 0.00 0.124347E+10 0.00 0.00
December 0.702394E+09 0.480395E+10 0.119076E+10 0.00 0.119076E+10 0.00 0.00
               
Annual Sum or Average 0.422014E+11 0.212771E+11 0.200531E+11 0.183002E+09 0.198701E+11 0.00 0.00
Minimum of Months 0.634572E+09 17870229.94 0.119076E+10 0.00 0.119076E+10 0.00 0.00
Maximum of Months 0.666683E+10 0.492146E+10 0.214072E+10 77805434.24 0.210682E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.174562E+10 0.296743E+10 0.174327E+10 0.699724E+09 0.104354E+10 0.00 0.00
February 0.246170E+10 0.206235E+10 0.191290E+10 0.789733E+09 0.112316E+10 0.00 0.00
March 0.420211E+10 0.131540E+10 0.258355E+10 0.106640E+10 0.151715E+10 0.00 0.00
April 0.605293E+10 0.418120E+09 0.297461E+10 0.138691E+10 0.158769E+10 0.00 0.00
May 0.709995E+10 67922498.09 0.302542E+10 0.134131E+10 0.168411E+10 0.00 0.00
June 0.621787E+10 45398260.51 0.238287E+10 0.790633E+09 0.159223E+10 0.00 0.00
July 0.529222E+10 7309990.61 0.206950E+10 0.437022E+09 0.163247E+10 0.00 0.00
August 0.448842E+10 29195893.56 0.186470E+10 0.324502E+09 0.154020E+10 0.00 0.00
September 0.403643E+10 0.166282E+09 0.192796E+10 0.537659E+09 0.139030E+10 0.00 0.00
October 0.402250E+10 0.102755E+10 0.217926E+10 0.880276E+09 0.129898E+10 0.00 0.00
November 0.275717E+10 0.195338E+10 0.186990E+10 0.802644E+09 0.106725E+10 0.00 0.00
December 0.183748E+10 0.288196E+10 0.168482E+10 0.667536E+09 0.101729E+10 0.00 0.00
               
Annual Sum or Average 0.502144E+11 0.129423E+11 0.262187E+11 0.972435E+10 0.164944E+11 0.00 0.00
Minimum of Months 0.174562E+10 7309990.61 0.168482E+10 0.324502E+09 0.101729E+10 0.00 0.00
Maximum of Months 0.709995E+10 0.296743E+10 0.302542E+10 0.138691E+10 0.168411E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.760087E+10 0.447709E+10 0.555142E+10 0.337318E+10 0.217825E+10 0.00 0.00
February 0.710985E+10 0.325788E+10 0.476777E+10 0.264814E+10 0.211962E+10 0.00 0.00
March 0.788098E+10 0.218907E+10 0.451334E+10 0.199349E+10 0.251985E+10 0.00 0.00
April 0.709338E+10 0.743213E+09 0.306794E+10 0.865857E+09 0.220208E+10 0.00 0.00
May 0.680892E+10 0.110057E+09 0.227980E+10 0.168765E+09 0.211104E+10 0.00 0.00
June 0.650414E+10 78942371.21 0.201816E+10 34438844.85 0.198372E+10 0.00 0.00
July 0.621257E+10 16740563.26 0.217530E+10 29919095.19 0.214538E+10 0.00 0.00
August 0.582216E+10 74239654.92 0.230752E+10 0.123238E+09 0.218429E+10 0.00 0.00
September 0.642552E+10 0.303888E+09 0.299363E+10 0.776997E+09 0.221663E+10 0.00 0.00
October 0.985399E+10 0.172087E+10 0.532189E+10 0.297171E+10 0.235018E+10 0.00 0.00
November 0.104173E+11 0.317971E+10 0.643288E+10 0.425199E+10 0.218090E+10 0.00 0.00
December 0.841850E+10 0.445902E+10 0.593256E+10 0.371749E+10 0.221506E+10 0.00 0.00
               
Annual Sum or Average 0.901482E+11 0.206107E+11 0.473622E+11 0.209552E+11 0.264070E+11 0.00 0.00
Minimum of Months 0.582216E+10 16740563.26 0.201816E+10 29919095.19 0.198372E+10 0.00 0.00
Maximum of Months 0.104173E+11 0.447709E+10 0.643288E+10 0.425199E+10 0.251985E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.187611E+10 0.343931E+10 0.170551E+10 0.663719E+09 0.104179E+10 0.00 0.00
February 0.228757E+10 0.249180E+10 0.176155E+10 0.649181E+09 0.111237E+10 0.00 0.00
March 0.406753E+10 0.169772E+10 0.252903E+10 0.101094E+10 0.151809E+10 0.00 0.00
April 0.584985E+10 0.695503E+09 0.297485E+10 0.139509E+10 0.157976E+10 0.00 0.00
May 0.677756E+10 0.121624E+09 0.291080E+10 0.123470E+10 0.167610E+10 0.00 0.00
June 0.645868E+10 92019669.47 0.264583E+10 0.102771E+10 0.161812E+10 0.00 0.00
July 0.488337E+10 42465924.12 0.202878E+10 0.394599E+09 0.163419E+10 0.00 0.00
August 0.410614E+10 0.162860E+09 0.186323E+10 0.331152E+09 0.153207E+10 0.00 0.00
September 0.403846E+10 0.277252E+09 0.198210E+10 0.581889E+09 0.140021E+10 0.00 0.00
October 0.390425E+10 0.128476E+10 0.213183E+10 0.848893E+09 0.128294E+10 0.00 0.00
November 0.279592E+10 0.241923E+10 0.186638E+10 0.795441E+09 0.107094E+10 0.00 0.00
December 0.180438E+10 0.356101E+10 0.165031E+10 0.629301E+09 0.102101E+10 0.00 0.00
               
Annual Sum or Average 0.488498E+11 0.162855E+11 0.260502E+11 0.956263E+10 0.164876E+11 0.00 0.00
Minimum of Months 0.180438E+10 42465924.12 0.165031E+10 0.331152E+09 0.102101E+10 0.00 0.00
Maximum of Months 0.677756E+10 0.356101E+10 0.297485E+10 0.139509E+10 0.167610E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.756676E+09 0.444286E+10 0.122067E+10 0.00 0.122067E+10 0.00 0.00
February 0.130253E+10 0.310198E+10 0.130743E+10 0.00 0.130743E+10 0.00 0.00
March 0.270227E+10 0.203953E+10 0.174425E+10 0.00 0.174425E+10 0.00 0.00
April 0.450275E+10 0.663896E+09 0.183160E+10 6211571.55 0.182539E+10 0.00 0.00
May 0.642238E+10 0.111234E+09 0.209692E+10 58843614.39 0.203808E+10 0.00 0.00
June 0.673352E+10 84736153.23 0.210063E+10 77807754.61 0.202282E+10 0.00 0.00
July 0.619321E+10 23045251.77 0.214076E+10 33900208.49 0.210686E+10 0.00 0.00
August 0.523278E+10 74549790.00 0.196528E+10 6124891.54 0.195915E+10 0.00 0.00
September 0.394696E+10 0.281557E+09 0.169463E+10 118993.41 0.169451E+10 0.00 0.00
October 0.298614E+10 0.157665E+10 0.151703E+10 0.00 0.151703E+10 0.00 0.00
November 0.160385E+10 0.295894E+10 0.124349E+10 0.00 0.124349E+10 0.00 0.00
December 0.854502E+09 0.427481E+10 0.119078E+10 0.00 0.119078E+10 0.00 0.00
               
Annual Sum or Average 0.432376E+11 0.196338E+11 0.200535E+11 0.183007E+09 0.198705E+11 0.00 0.00
Minimum of Months 0.756676E+09 23045251.77 0.119078E+10 0.00 0.119078E+10 0.00 0.00
Maximum of Months 0.673352E+10 0.444286E+10 0.214076E+10 77807754.61 0.210686E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.181095E+10 0.276542E+10 0.174326E+10 0.699721E+09 0.104354E+10 0.00 0.00
February 0.248095E+10 0.197255E+10 0.191289E+10 0.789730E+09 0.112316E+10 0.00 0.00
March 0.418135E+10 0.133369E+10 0.258354E+10 0.106640E+10 0.151715E+10 0.00 0.00
April 0.602233E+10 0.468072E+09 0.297459E+10 0.138691E+10 0.158769E+10 0.00 0.00
May 0.707583E+10 77815196.25 0.302541E+10 0.134130E+10 0.168411E+10 0.00 0.00
June 0.619111E+10 57878419.62 0.238286E+10 0.790630E+09 0.159223E+10 0.00 0.00
July 0.525505E+10 13610752.54 0.206949E+10 0.437021E+09 0.163247E+10 0.00 0.00
August 0.445086E+10 51037486.80 0.186469E+10 0.324501E+09 0.154019E+10 0.00 0.00
September 0.401435E+10 0.197736E+09 0.192795E+10 0.537657E+09 0.139029E+10 0.00 0.00
October 0.400895E+10 0.105631E+10 0.217925E+10 0.880272E+09 0.129897E+10 0.00 0.00
November 0.277171E+10 0.190486E+10 0.186989E+10 0.802641E+09 0.106725E+10 0.00 0.00
December 0.190136E+10 0.271335E+10 0.168481E+10 0.667533E+09 0.101728E+10 0.00 0.00
               
Annual Sum or Average 0.501648E+11 0.126123E+11 0.262186E+11 0.972431E+10 0.164943E+11 0.00 0.00
Minimum of Months 0.181095E+10 13610752.54 0.168481E+10 0.324501E+09 0.101728E+10 0.00 0.00
Maximum of Months 0.707583E+10 0.276542E+10 0.302541E+10 0.138691E+10 0.168411E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.755077E+10 0.441953E+10 0.555159E+10 0.337329E+10 0.217830E+10 0.00 0.00
February 0.706774E+10 0.320457E+10 0.476791E+10 0.264823E+10 0.211968E+10 0.00 0.00
March 0.785360E+10 0.218080E+10 0.451346E+10 0.199356E+10 0.251990E+10 0.00 0.00
April 0.713294E+10 0.748010E+09 0.306800E+10 0.865885E+09 0.220212E+10 0.00 0.00
May 0.686946E+10 0.111473E+09 0.227984E+10 0.168770E+09 0.211107E+10 0.00 0.00
June 0.657707E+10 83646886.49 0.201820E+10 34439972.86 0.198376E+10 0.00 0.00
July 0.629082E+10 20327321.27 0.217534E+10 29920075.17 0.214542E+10 0.00 0.00
August 0.591654E+10 78061325.72 0.230758E+10 0.123242E+09 0.218434E+10 0.00 0.00
September 0.641542E+10 0.327571E+09 0.299371E+10 0.777023E+09 0.221668E+10 0.00 0.00
October 0.981759E+10 0.175096E+10 0.532204E+10 0.297180E+10 0.235023E+10 0.00 0.00
November 0.103731E+11 0.315949E+10 0.643307E+10 0.425213E+10 0.218095E+10 0.00 0.00
December 0.840450E+10 0.434705E+10 0.593273E+10 0.371762E+10 0.221512E+10 0.00 0.00
               
Annual Sum or Average 0.902696E+11 0.204315E+11 0.473635E+11 0.209559E+11 0.264076E+11 0.00 0.00
Minimum of Months 0.591654E+10 20327321.27 0.201820E+10 29920075.17 0.198376E+10 0.00 0.00
Maximum of Months 0.103731E+11 0.441953E+10 0.643307E+10 0.425213E+10 0.251990E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.196771E+10 0.306039E+10 0.170550E+10 0.663716E+09 0.104178E+10 0.00 0.00
February 0.237465E+10 0.218753E+10 0.176155E+10 0.649178E+09 0.111237E+10 0.00 0.00
March 0.415297E+10 0.149540E+10 0.252902E+10 0.101094E+10 0.151808E+10 0.00 0.00
April 0.600594E+10 0.548230E+09 0.297484E+10 0.139509E+10 0.157975E+10 0.00 0.00
May 0.685456E+10 0.104761E+09 0.291079E+10 0.123470E+10 0.167609E+10 0.00 0.00
June 0.659542E+10 74392060.00 0.264582E+10 0.102771E+10 0.161811E+10 0.00 0.00
July 0.509057E+10 22386456.82 0.202878E+10 0.394598E+09 0.163418E+10 0.00 0.00
August 0.438375E+10 67393117.14 0.186322E+10 0.331151E+09 0.153207E+10 0.00 0.00
September 0.408930E+10 0.238757E+09 0.198210E+10 0.581887E+09 0.140021E+10 0.00 0.00
October 0.397174E+10 0.116320E+10 0.213182E+10 0.848889E+09 0.128294E+10 0.00 0.00
November 0.290168E+10 0.211469E+10 0.186638E+10 0.795438E+09 0.107094E+10 0.00 0.00
December 0.197452E+10 0.296428E+10 0.165030E+10 0.629299E+09 0.102101E+10 0.00 0.00
               
Annual Sum or Average 0.503628E+11 0.140414E+11 0.260501E+11 0.956259E+10 0.164875E+11 0.00 0.00
Minimum of Months 0.196771E+10 22386456.82 0.165030E+10 0.331151E+09 0.102101E+10 0.00 0.00
Maximum of Months 0.685456E+10 0.306039E+10 0.297484E+10 0.139509E+10 0.167609E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.926004E+09 0.385822E+10 0.122067E+10 0.00 0.122067E+10 0.00 0.00
February 0.139731E+10 0.282356E+10 0.130743E+10 0.00 0.130743E+10 0.00 0.00
March 0.270144E+10 0.196029E+10 0.174425E+10 0.00 0.174425E+10 0.00 0.00
April 0.442581E+10 0.670970E+09 0.183160E+10 6211571.55 0.182539E+10 0.00 0.00
May 0.629584E+10 0.125302E+09 0.209692E+10 58843614.39 0.203808E+10 0.00 0.00
June 0.659860E+10 95200721.54 0.210063E+10 77807754.61 0.202282E+10 0.00 0.00
July 0.605485E+10 25632722.24 0.214076E+10 33900208.49 0.210686E+10 0.00 0.00
August 0.512401E+10 84073321.09 0.196528E+10 6124891.54 0.195915E+10 0.00 0.00
September 0.388441E+10 0.293305E+09 0.169463E+10 118993.41 0.169451E+10 0.00 0.00
October 0.296822E+10 0.153517E+10 0.151703E+10 0.00 0.151703E+10 0.00 0.00
November 0.167001E+10 0.274700E+10 0.124349E+10 0.00 0.124349E+10 0.00 0.00
December 0.101430E+10 0.379217E+10 0.119078E+10 0.00 0.119078E+10 0.00 0.00
               
Annual Sum or Average 0.430608E+11 0.180109E+11 0.200535E+11 0.183007E+09 0.198705E+11 0.00 0.00
Minimum of Months 0.926004E+09 25632722.24 0.119078E+10 0.00 0.119078E+10 0.00 0.00
Maximum of Months 0.659860E+10 0.385822E+10 0.214076E+10 77807754.61 0.210686E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.196537E+10 0.244085E+10 0.174326E+10 0.699721E+09 0.104354E+10 0.00 0.00
February 0.254442E+10 0.183518E+10 0.191289E+10 0.789730E+09 0.112316E+10 0.00 0.00
March 0.417223E+10 0.130370E+10 0.258354E+10 0.106640E+10 0.151715E+10 0.00 0.00
April 0.596414E+10 0.479036E+09 0.297459E+10 0.138691E+10 0.158769E+10 0.00 0.00
May 0.698338E+10 88544188.33 0.302541E+10 0.134130E+10 0.168411E+10 0.00 0.00
June 0.609433E+10 65594359.36 0.238286E+10 0.790630E+09 0.159223E+10 0.00 0.00
July 0.515764E+10 15020457.82 0.206949E+10 0.437021E+09 0.163247E+10 0.00 0.00
August 0.437436E+10 57794006.36 0.186469E+10 0.324501E+09 0.154019E+10 0.00 0.00
September 0.396885E+10 0.207012E+09 0.192795E+10 0.537657E+09 0.139029E+10 0.00 0.00
October 0.399114E+10 0.104270E+10 0.217925E+10 0.880272E+09 0.129897E+10 0.00 0.00
November 0.281147E+10 0.180485E+10 0.186989E+10 0.802641E+09 0.106725E+10 0.00 0.00
December 0.203102E+10 0.245871E+10 0.168481E+10 0.667533E+09 0.101728E+10 0.00 0.00
               
Annual Sum or Average 0.500584E+11 0.117990E+11 0.262186E+11 0.972431E+10 0.164943E+11 0.00 0.00
Minimum of Months 0.196537E+10 15020457.82 0.168481E+10 0.324501E+09 0.101728E+10 0.00 0.00
Maximum of Months 0.698338E+10 0.245871E+10 0.302541E+10 0.138691E+10 0.168411E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.771902E+10 0.396369E+10 0.555159E+10 0.337329E+10 0.217830E+10 0.00 0.00
February 0.712555E+10 0.300079E+10 0.476791E+10 0.264823E+10 0.211968E+10 0.00 0.00
March 0.782744E+10 0.213106E+10 0.451346E+10 0.199356E+10 0.251990E+10 0.00 0.00
April 0.704982E+10 0.762537E+09 0.306800E+10 0.865885E+09 0.220212E+10 0.00 0.00
May 0.674202E+10 0.125578E+09 0.227984E+10 0.168770E+09 0.211107E+10 0.00 0.00
June 0.644101E+10 94630488.00 0.201820E+10 34439972.86 0.198376E+10 0.00 0.00
July 0.615142E+10 22469016.34 0.217534E+10 29920075.17 0.214542E+10 0.00 0.00
August 0.580611E+10 88243698.41 0.230758E+10 0.123242E+09 0.218434E+10 0.00 0.00
September 0.634662E+10 0.344265E+09 0.299371E+10 0.777023E+09 0.221668E+10 0.00 0.00
October 0.977826E+10 0.173753E+10 0.532204E+10 0.297180E+10 0.235023E+10 0.00 0.00
November 0.103914E+11 0.302760E+10 0.643307E+10 0.425213E+10 0.218095E+10 0.00 0.00
December 0.854166E+10 0.400397E+10 0.593273E+10 0.371762E+10 0.221512E+10 0.00 0.00
               
Annual Sum or Average 0.899203E+11 0.193024E+11 0.473635E+11 0.209559E+11 0.264076E+11 0.00 0.00
Minimum of Months 0.580611E+10 22469016.34 0.201820E+10 29920075.17 0.198376E+10 0.00 0.00
Maximum of Months 0.103914E+11 0.400397E+10 0.643307E+10 0.425213E+10 0.251990E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.205664E+10 0.274444E+10 0.170550E+10 0.663716E+09 0.104178E+10 0.00 0.00
February 0.241604E+10 0.203617E+10 0.176155E+10 0.649178E+09 0.111237E+10 0.00 0.00
March 0.413917E+10 0.145554E+10 0.252902E+10 0.101094E+10 0.151808E+10 0.00 0.00
April 0.595408E+10 0.553672E+09 0.297484E+10 0.139509E+10 0.157975E+10 0.00 0.00
May 0.677802E+10 0.112825E+09 0.291079E+10 0.123470E+10 0.167609E+10 0.00 0.00
June 0.651382E+10 79833431.80 0.264582E+10 0.102771E+10 0.161811E+10 0.00 0.00
July 0.501006E+10 24005839.07 0.202878E+10 0.394598E+09 0.163418E+10 0.00 0.00
August 0.432287E+10 73117717.19 0.186322E+10 0.331151E+09 0.153207E+10 0.00 0.00
September 0.404981E+10 0.245201E+09 0.198210E+10 0.581887E+09 0.140021E+10 0.00 0.00
October 0.395383E+10 0.114256E+10 0.213182E+10 0.848889E+09 0.128294E+10 0.00 0.00
November 0.292642E+10 0.200251E+10 0.186638E+10 0.795438E+09 0.107094E+10 0.00 0.00
December 0.205705E+10 0.270416E+10 0.165030E+10 0.629299E+09 0.102101E+10 0.00 0.00
               
Annual Sum or Average 0.501778E+11 0.131740E+11 0.260501E+11 0.956259E+10 0.164875E+11 0.00 0.00
Minimum of Months 0.205664E+10 24005839.07 0.165030E+10 0.331151E+09 0.102101E+10 0.00 0.00
Maximum of Months 0.677802E+10 0.274444E+10 0.297484E+10 0.139509E+10 0.167609E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.39 10.38 7.87 1.20 0.38 63.33 149.51 0.00
February 16.97 12.78 9.69 1.81 4.63 75.94 163.32 0.01
March 22.37 15.60 11.23 1.86 10.07 92.70 193.23 0.00
April 29.13 18.33 11.93 1.64 16.17 89.20 259.84 0.01
May 32.98 21.97 16.72 2.17 21.14 97.31 248.85 0.02
June 33.59 24.39 20.62 1.55 23.45 107.22 203.36 0.06
July 31.67 26.29 24.51 2.27 24.88 132.35 83.14 0.02
August 30.03 26.31 25.11 1.75 23.81 127.44 60.46 0.00
September 28.75 24.70 23.21 1.33 20.22 105.62 105.60 0.08
October 25.09 18.74 15.36 0.77 12.83 75.09 190.08 0.00
November 19.63 14.46 10.99 0.66 5.78 58.54 201.10 0.00
December 14.52 10.88 7.89 0.97 0.94 60.91 153.60 0.01
                 
Annual Sum or Average 24.88 18.77 15.46 1.50 13.74 90.59 167.44 0.02
Minimum of Months 13.39 10.38 7.87 0.66 0.38 58.54 60.46 0.00
Maximum of Months 33.59 26.31 25.11 2.27 24.88 132.35 259.84 0.08



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 23.60 12-JAN-14:00 14.20 7.40 3.80 8.15 163.00 476.00
February 27.10 22-FEB-14:00 16.20 9.10 1.50 15.39 225.00 451.00
March 35.60 28-MAR-14:00 18.50 7.70 0.00 19.52 182.00 699.00
April 40.30 15-APR-14:00 20.67 10.00 6.70 28.43 201.00 649.50
May 44.50 03-MAY-14:00 20.64 5.30 2.80 28.91 150.00 809.00
June 44.60 07-JUN-15:00 21.53 9.10 3.10 28.43 167.00 640.50
July 40.40 02-JUL-15:00 26.36 21.60 2.10 29.87 200.00 545.50
August 37.30 07-AUG-14:00 26.58 22.90 3.00 29.87 311.00 370.00
September 37.50 17-SEP-19:00 27.68 24.60 0.20 28.59 0.00 0.00
October 36.40 02-OCT-14:20 21.05 13.00 1.80 21.61 187.33 678.83
November 30.30 04-NOV-13:00 17.17 8.90 1.10 14.84 155.00 710.00
December 24.60 28-DEC-13:00 15.30 8.90 2.80 10.88 181.50 535.00
                 
Annual Sum or Average                
Minimum of Months 23.60   14.20 5.30 0.00 8.15 0.00 0.00
Maximum of Months 44.60   27.68 24.60 6.70 29.87 311.00 809.00



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 4.80 05-JAN-06:00 4.73 4.60 0.00 -10.2 0.00 0.00
February 6.90 02-FEB-05:00 6.67 6.50 0.00 -7.8 0.00 0.00
March 13.30 01-MAR-03:00 10.56 8.30 0.80 -1.4 0.00 0.00
April 17.40 11-APR-04:00 13.58 10.90 0.00 3.06 0.00 0.00
May 22.70 13-MAY-04:00 20.32 19.30 2.10 20.40 0.00 0.00
June 23.30 18-JUN-04:00 21.80 21.20 2.70 17.75 0.00 0.00
July 23.20 19-JUL-02:00 23.20 23.20 2.30 15.39 0.00 0.00
August 23.40 15-AUG-23:00 22.91 22.80 2.40 21.78 0.00 0.00
September 23.00 27-SEP-04:00 20.74 19.70 0.00 10.30 0.00 0.00
October 15.50 31-OCT-04:00 14.07 13.20 0.00 1.80 0.00 0.00
November 9.50 27-NOV-05:00 8.75 8.10 0.00 -5.0 0.00 0.00
December 5.00 21-DEC-04:00 4.08 3.00 0.00 -10.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 4.80   4.08 3.00 0.00 -10.5 0.00 0.00
Maximum of Months 23.40   23.20 23.20 2.70 21.78 0.00 0.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 15.62 17-JAN-14:00 18.20 14.10 1.00 11.07 198.00 56.50
February 18.14 25-FEB-16:00 21.20 16.60 5.90 10.88 107.50 156.50
March 21.38 10-MAR-18:49 29.25 17.73 2.10 21.44 0.00 0.00
April 23.42 18-APR-13:00 37.10 17.80 5.70 23.49 233.50 671.50
May 27.40 22-MAY-22:00 29.40 26.80 0.00 20.40 0.00 0.00
June 28.92 28-JUN-12:00 34.40 27.50 1.00 25.49 332.50 501.50
July 29.18 01-JUL-16:00 37.20 26.80 2.30 25.66 196.00 196.00
August 29.17 27-AUG-15:00 35.10 27.40 1.30 29.55 256.00 129.00
September 28.10 14-SEP-16:00 33.70 26.40 1.40 26.48 122.50 108.50
October 23.06 06-OCT-10:00 28.60 20.80 1.30 20.22 327.00 348.50
November 18.93 08-NOV-17:10 27.55 14.47 0.17 16.67 28.00 65.33
December 15.64 29-DEC-19:00 16.80 14.90 4.80 13.54 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 15.62   16.80 14.10 0.00 10.88 0.00 0.00
Maximum of Months 29.18   37.20 27.50 5.90 29.55 332.50 671.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 14.10 17-JAN-13:00 17.80 15.48 0.90 9.72 260.50 81.50
February 16.60 25-FEB-16:00 21.20 18.14 5.90 10.88 107.50 156.50
March 18.30 10-MAR-19:00 27.70 21.26 2.10 21.44 0.00 0.00
April 19.30 26-APR-23:10 28.53 22.04 0.00 15.61 0.00 0.00
May 26.80 22-MAY-22:00 29.40 27.40 0.00 20.40 0.00 0.00
June 27.50 28-JUN-12:00 34.40 28.92 1.00 25.49 332.50 501.50
July 27.30 18-JUL-06:19 29.10 27.70 1.17 26.48 20.00 0.00
August 28.80 12-AUG-07:00 29.10 28.83 2.90 26.81 113.00 6.50
September 26.50 12-SEP-14:00 30.50 27.38 0.90 25.99 260.00 20.00
October 21.10 06-OCT-08:00 25.50 22.41 0.30 17.21 239.00 159.00
November 16.30 08-NOV-21:19 20.10 17.59 0.00 10.95 0.00 0.00
December 14.90 29-DEC-20:10 16.72 15.59 4.73 13.13 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months 14.10   16.72 15.48 0.00 9.72 0.00 0.00
Maximum of Months 28.80   34.40 28.92 5.90 26.81 332.50 501.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.92 27.26 0.00
February 18.00 13.00 16.00 21.74 33.91 0.00
March 18.00 13.00 16.00 24.21 44.04 0.00
April 18.00 13.00 16.00 27.79 55.91 0.00
May 18.00 13.00 16.00 31.48 58.43 0.00
June 18.00 13.00 16.00 34.27 54.82 0.00
July 18.00 13.00 16.00 35.42 39.75 0.00
August 18.00 13.00 16.00 34.60 34.68 0.00
September 18.00 13.00 16.00 32.04 35.55 0.00
October 18.00 13.00 16.00 28.44 39.44 0.00
November 18.00 13.00 16.00 24.77 33.85 0.00
December 18.00 13.00 16.00 22.02 26.79 0.00
             
Annual Sum or Average 18.00 13.00 16.00 28.18 40.37 0.00
Minimum of Months 18.00 13.00 16.00 20.92 26.79 0.00
Maximum of Months 18.00 13.00 16.00 35.42 58.43 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.313250E+11 -0.303039E+11 0.00 0.00 744.00 0.00 -0.102106E+10 58.97 0.00 0.00
February 0.278785E+11 -0.269554E+11 0.00 0.00 672.00 0.00 -923077069.9 58.97 0.00 0.00
March 0.306002E+11 -0.295746E+11 0.00 0.00 744.00 0.00 -0.102561E+10 58.98 0.00 0.00
April 0.250571E+11 -0.240683E+11 0.00 0.00 720.00 0.00 -988770070.4 58.97 0.00 0.00
May 0.237303E+11 -0.227078E+11 0.00 0.00 744.00 0.00 -0.102248E+10 58.97 0.00 0.00
June 0.211633E+11 -0.201733E+11 0.00 0.00 720.00 0.00 -989972621.0 58.96 0.00 0.00
July 0.193085E+11 -0.182913E+11 0.00 0.00 744.00 0.00 -0.101724E+10 58.96 0.00 0.00
August 0.217636E+11 -0.207422E+11 0.00 0.00 744.00 0.00 -0.102138E+10 58.97 0.00 0.00
September 0.218160E+11 -0.208298E+11 0.00 0.00 720.00 0.00 -986124291.4 58.96 0.00 0.00
October 0.253571E+11 -0.243390E+11 0.00 0.00 744.00 0.00 -0.101803E+10 58.97 0.00 0.00
November 0.277046E+11 -0.267189E+11 0.00 0.00 720.00 0.00 -985611251.0 58.97 0.00 0.00
December 0.297410E+11 -0.287222E+11 0.00 0.00 744.00 0.00 -0.101880E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.305445E+12 -0.293427E+12 0.00 0.00 8760.00 0.00 -0.120182E+11 58.97 0.00 0.00
Minimum of Months 0.193085E+11 -0.303039E+11 0.00 0.00 672.00 0.00 -0.102561E+10 58.96 0.00 0.00
Maximum of Months 0.313250E+11 -0.182913E+11 0.00 0.00 744.00 0.00 -923077069.9 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.64 0.61 01-JAN-07:49 5229.40 34.80 297.00 284.33 1049.42 24.95 250.50 263.50
February 303.83 0.64 0.61 01-FEB-07:49 3042.78 28.08 195.67 268.33 918.85 20.43 147.00 236.00
March 364.50 0.64 0.61 01-MAR-07:40 1477.59 17.65 7.50 315.00 789.00 20.23 129.17 279.83
April 379.83 0.65 0.61 01-APR-07:10 982.72 16.01 0.00 322.67 578.92 18.84 10.17 280.50
May 406.00 0.65 0.61 01-MAY-06:49 833.18 15.69 0.00 340.50 488.09 18.64 0.67 292.67
June 386.67 0.65 0.61 01-JUN-06:00 829.12 15.40 0.00 326.00 473.29 18.30 0.00 274.67
July 379.83 0.64 0.61 01-JUL-06:40 948.58 15.96 0.00 324.17 486.34 18.75 3.33 260.67
August 372.50 0.65 0.61 01-AUG-06:49 1073.85 16.05 0.00 313.50 530.54 18.80 51.17 252.33
September 344.33 0.64 0.61 01-SEP-06:00 1299.80 16.77 0.00 294.33 664.41 19.62 123.67 248.67
October 347.33 0.65 0.61 01-OCT-06:00 2269.30 18.78 39.33 300.17 883.15 19.96 131.00 269.67
November 317.83 0.64 0.61 01-NOV-07:19 7147.17 34.42 292.17 279.00 1080.60 22.63 172.83 259.17
December 315.50 0.64 0.61 01-DEC-07:30 5499.61 34.82 293.00 280.17 1253.63 27.25 275.83 276.00
                         
Annual Sum or Average 4237.50 0.64     2399.52 21.42 1124.67 3648.17 745.67 20.52 1295.33 3193.67
Minimum of Months 303.83 0.64 0.61   829.12 15.40 0.00 268.33 473.29 18.30 0.00 236.00
Maximum of Months 406.00 0.65 0.61   7147.17 34.82 297.00 340.50 1253.63 27.25 275.83 292.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-07:49 1408.41 17.63 83.67 252.17 757.96 18.92 74.33 200.50
February 303.83 0.65 0.61 01-FEB-07:49 1747.84 17.40 75.00 246.17 948.69 18.63 69.50 199.00
March 364.50 0.64 0.61 01-MAR-07:40 1690.85 15.45 57.83 305.67 849.32 14.19 2.67 264.67
April 379.83 0.65 0.61 01-APR-06:49 2045.00 11.68 0.00 316.00 1092.67 13.06 0.00 279.50
May 406.00 0.64 0.61 01-MAY-06:10 2207.47 11.81 0.00 344.83 801.02 13.00 0.00 301.00
June 386.67 0.65 0.61 01-JUN-06:40 1740.72 11.88 0.00 329.00 689.86 12.82 0.00 278.83
July 379.83 0.64 0.61 01-JUL-06:10 1427.28 12.51 0.00 328.33 612.22 13.14 0.00 260.00
August 372.50 0.65 0.61 01-AUG-06:19 1286.70 12.44 0.00 311.50 583.45 13.09 0.00 246.83
September 344.33 0.65 0.61 01-SEP-06:49 1436.76 13.06 8.50 289.17 722.50 13.86 5.50 230.67
October 347.33 0.65 0.61 01-OCT-06:49 1588.53 17.03 85.83 283.83 776.70 16.43 55.00 240.67
November 317.83 0.65 0.61 01-NOV-07:10 1431.06 17.88 82.50 254.67 711.90 17.54 56.17 210.67
December 315.50 0.65 0.61 01-DEC-07:40 1471.06 18.19 87.83 247.67 805.64 19.64 79.67 206.17
                         
Annual Sum or Average 4237.50 0.65     1635.41 14.54 481.17 3509.00 777.75 15.15 342.83 2918.50
Minimum of Months 303.83 0.64 0.61   1286.70 11.68 0.00 246.17 583.45 12.82 0.00 199.00
Maximum of Months 406.00 0.66 0.61   2207.47 18.19 87.83 344.83 1092.67 19.64 79.67 301.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.67 0.61 01-JAN-08:39 450.37 0.00 0.00 225.50 281.20 0.00 0.00 101.67
February 303.83 0.66 0.61 01-FEB-08:20 520.95 0.00 0.00 237.00 323.35 0.00 0.00 146.67
March 364.50 0.64 0.61 01-MAR-07:00 616.84 0.00 0.00 302.83 381.62 0.00 0.00 236.67
April 379.83 0.65 0.61 01-APR-07:10 664.67 0.00 0.00 325.67 417.80 0.00 0.00 278.67
May 406.00 0.64 0.61 01-MAY-06:19 802.65 0.00 0.00 360.00 471.90 0.00 0.00 322.83
June 386.67 0.64 0.61 01-JUN-06:49 896.14 0.00 0.00 342.50 498.79 0.00 0.00 300.17
July 379.83 0.63 0.61 01-JUL-06:19 922.74 0.00 0.00 336.83 477.54 0.00 0.00 278.83
August 372.50 0.64 0.61 01-AUG-06:40 827.49 0.00 0.00 317.17 427.45 0.00 0.00 249.33
September 344.33 0.64 0.61 01-SEP-06:00 710.28 0.00 0.00 290.67 393.92 0.00 0.00 216.67
October 347.33 0.66 0.61 01-OCT-07:10 543.29 0.00 0.00 279.17 345.60 0.00 0.00 198.00
November 317.83 0.66 0.61 01-NOV-07:40 456.83 0.00 0.00 235.17 304.39 0.00 0.00 132.33
December 315.50 0.67 0.61 01-DEC-08:20 442.31 0.00 0.00 223.17 279.49 0.00 0.00 89.33
                         
Annual Sum or Average 4237.50 0.65     667.50 0.00 0.00 3475.67 389.74 0.00 0.00 2551.17
Minimum of Months 303.83 0.63 0.61   442.31 0.00 0.00 223.17 279.49 0.00 0.00 89.33
Maximum of Months 406.00 0.67 0.61   922.74 0.00 0.00 360.00 498.79 0.00 0.00 322.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-08:50 1413.08 17.63 82.50 250.33 745.72 18.67 71.50 201.67
February 303.83 0.65 0.61 01-FEB-08:39 1662.73 17.31 77.00 247.67 663.34 16.83 44.00 201.83
March 364.50 0.64 0.61 01-MAR-08:09 1645.38 15.39 57.33 306.00 822.80 14.13 1.83 264.50
April 379.83 0.65 0.61 01-APR-07:30 1881.74 11.68 0.00 319.50 978.65 13.07 0.00 282.83
May 406.00 0.64 0.61 01-MAY-07:10 1807.33 11.79 0.00 342.00 934.99 12.97 0.00 301.67
June 386.67 0.65 0.61 01-JUN-07:10 1804.63 11.96 0.00 329.83 716.76 12.90 0.00 284.17
July 379.83 0.64 0.61 01-JUL-06:00 1378.71 12.53 0.00 325.67 605.46 13.16 0.00 263.17
August 372.50 0.65 0.61 01-AUG-07:10 1272.69 12.41 0.00 311.33 626.22 13.05 0.00 248.17
September 344.33 0.64 0.61 01-SEP-07:30 1410.50 13.13 8.50 290.00 698.44 13.92 5.50 236.00
October 347.33 0.65 0.61 01-OCT-07:30 1689.01 16.96 84.83 281.00 848.39 16.34 54.00 242.00
November 317.83 0.65 0.61 01-NOV-07:00 1480.96 17.90 84.83 257.67 720.42 17.28 55.00 211.83
December 315.50 0.65 0.61 01-DEC-08:20 1293.14 18.30 87.33 252.17 650.84 17.73 56.33 204.50
                         
Annual Sum or Average 4237.50 0.65     1569.62 14.54 482.33 3513.17 755.35 14.83 288.17 2942.33
Minimum of Months 303.83 0.64 0.61   1272.69 11.68 0.00 247.67 605.46 12.90 0.00 201.67
Maximum of Months 406.00 0.66 0.61   1881.74 18.30 87.33 342.00 978.65 18.67 71.50 301.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.64 0.61 01-JAN-07:00 5130.05 30.67 258.67 276.50 1080.85 20.87 85.17 263.83
February 303.83 0.64 0.61 01-FEB-07:49 3016.51 25.57 194.00 267.83 950.11 15.67 0.00 237.17
March 364.50 0.64 0.61 01-MAR-07:40 1455.73 11.86 7.50 313.67 815.73 16.26 0.00 281.83
April 379.83 0.65 0.61 01-APR-07:10 970.59 10.73 0.00 320.17 598.55 15.38 0.00 283.17
May 406.00 0.65 0.61 01-MAY-06:49 820.23 10.24 0.00 338.33 503.19 14.95 0.00 296.17
June 386.67 0.65 0.61 01-JUN-06:00 814.68 9.84 0.00 325.33 487.37 14.45 0.00 277.50
July 379.83 0.64 0.61 01-JUL-06:40 926.96 9.83 0.00 322.50 499.91 14.41 0.00 264.33
August 372.50 0.65 0.61 01-AUG-06:49 1046.53 9.89 0.00 312.00 544.67 14.35 0.00 254.50
September 344.33 0.64 0.61 01-SEP-06:00 1270.45 10.66 0.00 294.00 683.06 15.30 0.00 250.67
October 347.33 0.65 0.61 01-OCT-06:00 2255.69 13.22 39.33 301.83 915.79 15.53 5.33 271.67
November 317.83 0.64 0.61 01-NOV-07:19 7119.93 33.41 288.33 277.83 1123.69 18.15 45.17 263.67
December 315.50 0.64 0.61 01-DEC-07:40 5415.75 32.21 273.33 276.17 1276.95 22.72 113.50 272.50
                         
Annual Sum or Average 4237.50 0.64     2368.49 16.61 1061.17 3626.17 768.69 16.35 249.17 3217.00
Minimum of Months 303.83 0.64 0.61   814.68 9.83 0.00 267.83 487.37 14.35 0.00 237.17
Maximum of Months 406.00 0.65 0.61   7119.93 33.41 288.33 338.33 1276.95 22.72 113.50 296.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-07:49 1401.92 15.60 84.33 251.83 733.15 15.14 55.17 201.00
February 303.83 0.65 0.61 01-FEB-07:49 1742.61 15.21 75.33 245.67 968.45 16.85 70.00 201.83
March 364.50 0.64 0.61 01-MAR-07:40 1697.60 12.81 57.83 304.83 872.79 11.71 2.83 267.33
April 379.83 0.65 0.61 01-APR-06:49 2033.91 8.42 0.00 314.83 1117.79 10.77 0.00 282.50
May 406.00 0.64 0.61 01-MAY-06:10 2100.19 8.45 0.00 344.33 827.26 10.77 0.00 305.17
June 386.67 0.65 0.61 01-JUN-06:40 1728.87 8.66 0.00 328.33 712.17 10.73 0.00 283.50
July 379.83 0.64 0.61 01-JUL-06:10 1389.78 9.10 0.00 327.17 635.10 10.93 0.00 264.00
August 372.50 0.65 0.61 01-AUG-06:19 1272.50 9.07 0.00 311.00 658.83 10.81 0.00 251.17
September 344.33 0.65 0.61 01-SEP-06:49 1432.36 9.82 8.50 288.17 740.98 11.49 5.50 237.00
October 347.33 0.65 0.61 01-OCT-06:49 1572.48 14.64 81.83 283.50 797.34 14.52 55.50 244.17
November 317.83 0.65 0.61 01-NOV-07:10 1329.36 13.75 59.00 253.67 731.65 15.56 56.50 214.67
December 315.50 0.66 0.61 01-DEC-07:40 1464.61 16.15 87.83 247.33 822.19 17.81 79.83 210.17
                         
Annual Sum or Average 4237.50 0.65     1608.38 11.57 454.67 3500.67 800.71 12.88 325.33 2962.50
Minimum of Months 303.83 0.64 0.61   1272.50 8.42 0.00 245.67 635.10 10.73 0.00 201.00
Maximum of Months 406.00 0.66 0.61   2100.19 16.15 87.83 344.33 1117.79 17.81 79.83 305.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.67 0.61 01-JAN-08:39 441.09 0.00 0.00 221.50 288.57 0.00 0.00 116.67
February 303.83 0.66 0.61 01-FEB-08:20 511.05 0.00 0.00 234.33 332.25 0.00 0.00 152.83
March 364.50 0.64 0.61 01-MAR-07:00 606.20 0.00 0.00 300.33 392.55 0.00 0.00 241.00
April 379.83 0.65 0.61 01-APR-07:10 655.23 0.00 0.00 324.83 430.59 0.00 0.00 282.33
May 406.00 0.64 0.61 01-MAY-06:30 787.27 0.00 0.00 356.17 486.43 0.00 0.00 325.00
June 386.67 0.64 0.61 01-JUN-06:49 879.81 0.00 0.00 340.50 515.22 0.00 0.00 304.33
July 379.83 0.64 0.61 01-JUL-06:19 903.51 0.00 0.00 334.17 490.83 0.00 0.00 281.33
August 372.50 0.64 0.61 01-AUG-06:40 809.72 0.00 0.00 315.33 439.36 0.00 0.00 253.50
September 344.33 0.65 0.61 01-SEP-06:00 695.82 0.00 0.00 289.00 404.84 0.00 0.00 220.83
October 347.33 0.66 0.61 01-OCT-07:19 533.66 0.00 0.00 276.50 355.31 0.00 0.00 205.67
November 317.83 0.66 0.61 01-NOV-07:49 448.06 0.00 0.00 233.00 312.52 0.00 0.00 144.17
December 315.50 0.67 0.61 01-DEC-08:20 432.98 0.00 0.00 219.33 286.65 0.00 0.00 103.33
                         
Annual Sum or Average 4237.50 0.65     654.76 0.00 0.00 3445.00 400.97 0.00 0.00 2631.00
Minimum of Months 303.83 0.64 0.61   432.98 0.00 0.00 219.33 286.65 0.00 0.00 103.33
Maximum of Months 406.00 0.67 0.61   903.51 0.00 0.00 356.17 515.22 0.00 0.00 325.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-08:50 1406.70 15.58 82.83 249.50 761.98 16.83 72.00 204.17
February 303.83 0.65 0.61 01-FEB-08:39 1656.77 15.12 77.00 246.67 681.65 14.81 44.33 205.50
March 364.50 0.64 0.61 01-MAR-08:09 1651.00 12.76 57.33 305.50 845.71 11.66 1.83 268.50
April 379.83 0.65 0.61 01-APR-07:30 1870.60 8.42 0.00 318.83 964.50 10.78 0.00 283.17
May 406.00 0.65 0.61 01-MAY-07:10 1792.11 8.45 0.00 341.17 960.72 10.75 0.00 304.50
June 386.67 0.65 0.61 01-JUN-07:10 1794.68 8.64 0.00 329.67 741.16 10.74 0.00 288.33
July 379.83 0.64 0.61 01-JUL-06:00 1347.38 9.13 0.00 324.50 623.83 10.95 0.00 268.17
August 372.50 0.65 0.61 01-AUG-07:10 1258.54 9.05 0.00 310.17 643.06 10.78 0.00 252.83
September 344.33 0.64 0.61 01-SEP-07:30 1405.39 9.87 8.50 290.00 717.02 11.55 5.50 240.33
October 347.33 0.65 0.61 01-OCT-07:30 1689.90 14.87 85.00 280.33 868.71 14.44 54.17 246.00
November 317.83 0.65 0.61 01-NOV-07:00 1476.23 15.84 85.00 256.83 739.90 15.26 55.00 216.67
December 315.50 0.65 0.61 01-DEC-08:20 1287.98 16.29 87.33 251.67 667.01 15.64 56.33 208.50
                         
Annual Sum or Average 4237.50 0.65     1560.70 11.74 483.00 3504.83 772.25 12.67 289.17 2986.67
Minimum of Months 303.83 0.64 0.61   1258.54 8.42 0.00 246.67 623.83 10.74 0.00 204.17
Maximum of Months 406.00 0.66 0.61   1870.60 16.29 87.33 341.17 964.50 16.83 72.00 304.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.64 0.61 01-JAN-07:00 5129.79 30.66 258.67 276.50 1082.07 20.86 85.17 263.83
February 303.83 0.64 0.61 01-FEB-07:49 3017.09 25.55 194.00 267.83 951.25 15.65 0.00 237.33
March 364.50 0.64 0.61 01-MAR-07:40 1456.41 11.82 7.50 313.67 816.67 16.24 0.00 281.83
April 379.83 0.65 0.61 01-APR-07:10 970.87 10.69 0.00 320.17 599.12 15.37 0.00 283.33
May 406.00 0.65 0.61 01-MAY-06:49 820.44 10.20 0.00 338.33 503.68 14.93 0.00 296.17
June 386.67 0.65 0.61 01-JUN-06:00 814.96 9.80 0.00 325.33 487.88 14.43 0.00 277.67
July 379.83 0.64 0.61 01-JUL-06:40 927.68 9.80 0.00 322.50 500.61 14.39 0.00 265.00
August 372.50 0.65 0.61 01-AUG-06:49 1047.44 9.85 0.00 312.00 545.51 14.34 0.00 254.67
September 344.33 0.64 0.61 01-SEP-06:00 1271.35 10.62 0.00 294.00 684.03 15.28 0.00 250.67
October 347.33 0.65 0.61 01-OCT-06:00 2256.24 13.18 39.33 301.83 916.80 15.52 5.33 271.67
November 317.83 0.64 0.61 01-NOV-07:19 7119.82 33.40 288.33 277.83 1124.81 18.13 45.17 263.67
December 315.50 0.64 0.61 01-DEC-07:40 5415.31 32.19 273.33 276.17 1278.23 22.71 113.50 272.50
                         
Annual Sum or Average 4237.50 0.64     2368.86 16.58 1061.17 3626.17 769.57 16.33 249.17 3218.33
Minimum of Months 303.83 0.64 0.61   814.96 9.80 0.00 267.83 487.88 14.34 0.00 237.33
Maximum of Months 406.00 0.65 0.61   7119.82 33.40 288.33 338.33 1278.23 22.71 113.50 296.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-07:49 1401.67 15.59 84.33 251.83 733.67 15.13 55.17 201.33
February 303.83 0.65 0.61 01-FEB-07:49 1742.37 15.20 75.33 245.50 969.07 16.85 70.00 201.83
March 364.50 0.64 0.61 01-MAR-07:40 1697.34 12.79 57.83 304.83 873.48 11.70 2.83 267.33
April 379.83 0.65 0.61 01-APR-06:49 2033.75 8.41 0.00 314.83 1118.43 10.76 0.00 282.67
May 406.00 0.64 0.61 01-MAY-06:10 2100.13 8.44 0.00 344.33 827.95 10.76 0.00 305.17
June 386.67 0.65 0.61 01-JUN-06:40 1729.09 8.64 0.00 328.33 712.90 10.72 0.00 283.67
July 379.83 0.64 0.61 01-JUL-06:10 1390.42 9.09 0.00 327.17 635.96 10.92 0.00 264.33
August 372.50 0.65 0.61 01-AUG-06:19 1273.19 9.06 0.00 311.00 659.70 10.81 0.00 251.17
September 344.33 0.65 0.61 01-SEP-06:49 1432.68 9.81 8.50 288.17 741.81 11.48 5.50 237.17
October 347.33 0.65 0.61 01-OCT-06:49 1572.17 14.63 81.83 283.50 797.95 14.51 55.50 244.17
November 317.83 0.65 0.61 01-NOV-07:10 1329.00 13.74 59.00 253.67 732.15 15.55 56.50 214.67
December 315.50 0.66 0.61 01-DEC-07:40 1464.34 16.14 87.83 247.33 822.71 17.80 79.83 210.17
                         
Annual Sum or Average 4237.50 0.65     1608.39 11.55 454.67 3500.50 801.39 12.87 325.33 2963.67
Minimum of Months 303.83 0.64 0.61   1273.19 8.41 0.00 245.50 635.96 10.72 0.00 201.33
Maximum of Months 406.00 0.66 0.61   2100.13 16.14 87.83 344.33 1118.43 17.80 79.83 305.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.67 0.61 01-JAN-08:39 440.97 0.00 0.00 221.50 288.80 0.00 0.00 117.17
February 303.83 0.66 0.61 01-FEB-08:20 510.95 0.00 0.00 234.33 332.51 0.00 0.00 153.33
March 364.50 0.64 0.61 01-MAR-07:00 606.11 0.00 0.00 300.33 392.86 0.00 0.00 241.00
April 379.83 0.65 0.61 01-APR-07:10 655.12 0.00 0.00 324.83 430.92 0.00 0.00 282.33
May 406.00 0.64 0.61 01-MAY-06:30 787.31 0.00 0.00 356.17 486.87 0.00 0.00 325.00
June 386.67 0.64 0.61 01-JUN-06:49 880.04 0.00 0.00 340.50 515.77 0.00 0.00 304.50
July 379.83 0.64 0.61 01-JUL-06:19 904.08 0.00 0.00 334.17 491.50 0.00 0.00 281.67
August 372.50 0.64 0.61 01-AUG-06:40 810.24 0.00 0.00 315.33 439.99 0.00 0.00 253.50
September 344.33 0.65 0.61 01-SEP-06:00 696.04 0.00 0.00 289.00 405.31 0.00 0.00 221.00
October 347.33 0.66 0.61 01-OCT-07:19 533.51 0.00 0.00 276.50 355.57 0.00 0.00 206.00
November 317.83 0.66 0.61 01-NOV-07:49 447.82 0.00 0.00 233.00 312.70 0.00 0.00 144.33
December 315.50 0.67 0.61 01-DEC-08:20 432.83 0.00 0.00 219.33 286.86 0.00 0.00 103.50
                         
Annual Sum or Average 4237.50 0.65     654.83 0.00 0.00 3445.00 401.36 0.00 0.00 2633.33
Minimum of Months 303.83 0.64 0.61   432.83 0.00 0.00 219.33 286.86 0.00 0.00 103.50
Maximum of Months 406.00 0.67 0.61   904.08 0.00 0.00 356.17 515.77 0.00 0.00 325.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 319.33 0.66 0.61 01-JAN-08:50 1406.46 15.57 82.83 249.33 762.50 16.83 72.00 204.17
February 303.83 0.65 0.61 01-FEB-08:39 1656.59 15.11 77.00 246.67 682.26 14.81 44.33 205.67
March 364.50 0.64 0.61 01-MAR-08:09 1650.77 12.75 57.33 305.33 846.40 11.65 1.83 268.50
April 379.83 0.65 0.61 01-APR-07:30 1870.45 8.41 0.00 318.83 965.12 10.77 0.00 283.17
May 406.00 0.65 0.61 01-MAY-07:10 1792.07 8.44 0.00 341.17 961.41 10.74 0.00 304.83
June 386.67 0.65 0.61 01-JUN-07:10 1794.84 8.62 0.00 329.67 741.91 10.73 0.00 288.33
July 379.83 0.64 0.61 01-JUL-06:00 1348.05 9.11 0.00 324.50 624.69 10.94 0.00 268.33
August 372.50 0.65 0.61 01-AUG-07:10 1259.24 9.04 0.00 310.17 643.93 10.77 0.00 253.00
September 344.33 0.64 0.61 01-SEP-07:30 1405.74 9.86 8.50 290.00 717.85 11.54 5.50 240.50
October 347.33 0.65 0.61 01-OCT-07:30 1689.70 14.86 85.00 280.33 869.31 14.44 54.17 246.00
November 317.83 0.65 0.61 01-NOV-07:00 1475.88 15.83 85.00 256.83 740.39 15.25 55.00 216.83
December 315.50 0.65 0.61 01-DEC-08:20 1287.74 16.28 87.33 251.33 667.52 15.64 56.33 208.50
                         
Annual Sum or Average 4237.50 0.65     1560.73 11.73 483.00 3504.17 772.92 12.66 289.17 2987.83
Minimum of Months 303.83 0.64 0.61   1259.24 8.41 0.00 246.67 624.69 10.73 0.00 204.17
Maximum of Months 406.00 0.66 0.61   1870.45 16.28 87.33 341.17 965.12 16.83 72.00 304.83



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.163125E+09 5300.56 05-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 807832.26 869.18 02-FEB-06:08 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 35436036.95 4113.58 23-DEC-05:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.199369E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.163125E+09 5300.56   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.342266E+10 67608.38 05-JAN-07:00 0.00 0.00 0.00 0.00 0.00
February 0.137570E+09 22992.67 02-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 7053.43 11.76 25-SEP-10:20 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.716610E+09 50791.97 23-DEC-06:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.427685E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.342266E+10 67608.38   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.589766E+09 59170.07 02-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 3257951.78 1112.19 11-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.104670E+09 15584.92 23-DEC-06:08 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.697694E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.589766E+09 59170.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.164769E+09 17992.14 03-JAN-06:05 0.00 0.00 0.00 0.00 0.00
February 14417895.39 8183.39 11-FEB-06:08 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 25818644.69 8808.39 23-DEC-06:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.205005E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164769E+09 17992.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 91243135.80 10268.80 03-JAN-06:10 0.00 0.00 0.00 0.00 0.00
February 4218789.12 1116.78 11-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 9240750.83 2229.30 23-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.104703E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 91243135.80 10268.80   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.143374E+10 13444.84 02-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 0.153654E+09 7484.63 02-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 1339827.82 1020.22 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.376860E+09 12397.55 23-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.196559E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143374E+10 13444.84   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.602584E+09 71048.76 02-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 600876.17 714.08 23-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.603185E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.602584E+09 71048.76   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.119920E+10 18539.34 02-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 0.225155E+09 18336.85 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 24347687.63 1992.46 27-NOV-06:05 0.00 0.00 0.00 0.00 0.00
December 0.594157E+09 18433.71 23-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.204286E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.119920E+10 18539.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.501868E+09 13091.14 02-JAN-04:02 0.00 0.00 0.00 0.00 0.00
February 90289200.33 12946.53 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 4152964.94 660.58 27-NOV-07:00 0.00 0.00 0.00 0.00 0.00
December 0.238042E+09 12990.88 21-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.834353E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.501868E+09 13091.14   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.397139E+09 18501.20 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 70122257.02 18354.92 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.103610E+09 16915.67 23-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.570872E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.397139E+09 18501.20   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.475303E+09 13197.94 02-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 86090789.85 13092.95 11-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 382650.66 110.12 25-NOV-07:50 0.00 0.00 0.00 0.00 0.00
December 0.191731E+09 11577.89 23-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.753507E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.475303E+09 13197.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:05 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:03 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.453706E+11 0.452951E+11 86484.70 18-JAN-06:03 72576.05 0.30
February 0.00 0.00 0.643314E+11 0.642073E+11 103576.57 21-FEB-16:00 103576.57 0.48
March 0.00 0.00 0.120624E+12 0.118666E+12 200178.88 29-MAR-05:03 143935.68 0.68
April 0.00 0.00 0.177620E+12 0.170685E+12 249997.83 17-APR-05:03 175997.34 0.81
May 0.00 0.00 0.217423E+12 0.184253E+12 277208.69 22-MAY-05:02 174612.19 0.83
June 0.00 0.00 0.256762E+12 0.189662E+12 287729.18 26-JUN-05:02 169747.02 0.86
July 0.00 0.00 0.297209E+12 0.183584E+12 299718.20 31-JUL-05:03 176172.27 0.87
August 0.00 0.00 0.318655E+12 0.194049E+12 315682.45 28-AUG-05:04 175311.42 0.89
September 0.00 0.00 0.221857E+12 0.141278E+12 283436.53 05-SEP-05:02 169863.16 0.77
October 0.00 0.00 0.148554E+12 0.131722E+12 253426.05 04-OCT-05:02 165376.78 0.75
November 0.00 0.00 0.990074E+11 0.977505E+11 170716.22 10-NOV-06:02 122619.00 0.63
December 0.00 0.00 0.660829E+11 0.660829E+11 101627.38 29-DEC-06:02 101627.38 0.40
                 
Annual Sum or Average 0.00 0.00 0.203350E+13 0.158723E+13       0.69
Minimum of Months 0.00 0.00 0.453706E+11 0.452951E+11 86484.70   72576.05 0.30
Maximum of Months 0.00 0.00 0.318655E+12 0.194049E+12 315682.45   176172.27 0.89



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.316074E+12 0.315985E+12 826637.85 18-JAN-06:03 652604.61 0.27
February 0.00 0.00 0.466977E+12 0.465988E+12 1273675.58 25-FEB-06:03 863622.00 0.43
March 0.00 0.00 0.922597E+12 0.908900E+12 1917600.85 14-MAR-05:02 1439676.49 0.57
April 0.00 0.00 0.137792E+13 0.132672E+13 2302218.55 26-APR-05:02 1523340.26 0.67
May 0.00 0.00 0.199934E+13 0.168166E+13 2723695.48 24-MAY-03:02 1536009.70 0.80
June 0.00 0.00 0.227613E+13 0.165161E+13 2847278.10 26-JUN-05:02 1578548.39 0.80
July 0.00 0.00 0.250696E+13 0.147927E+13 2980871.43 27-JUL-03:02 1552684.26 0.77
August 0.00 0.00 0.247813E+13 0.141234E+13 2892133.00 10-AUG-05:02 1597063.45 0.75
September 0.00 0.00 0.192020E+13 0.120040E+13 2862700.79 09-SEP-05:03 1491498.15 0.68
October 0.00 0.00 0.121278E+13 0.106898E+13 2437777.84 12-OCT-05:02 1448482.13 0.65
November 0.00 0.00 0.725332E+12 0.716076E+12 1662271.15 09-NOV-06:02 1130449.78 0.55
December 0.00 0.00 0.384513E+12 0.384513E+12 736826.41 29-DEC-06:02 736826.41 0.33
                 
Annual Sum or Average 0.00 0.00 0.165870E+14 0.126124E+14       0.61
Minimum of Months 0.00 0.00 0.316074E+12 0.315985E+12 736826.41   652604.61 0.27
Maximum of Months 0.00 0.00 0.250696E+13 0.168166E+13 2980871.43   1597063.45 0.80



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.232183E+11 0.232183E+11 59605.80 12-JAN-15:00 59605.80 0.26
February 0.00 0.00 0.412320E+11 0.411399E+11 111329.74 25-FEB-06:03 74963.49 0.41
March 0.00 0.00 0.949783E+11 0.936886E+11 198865.85 14-MAR-05:02 148160.20 0.56
April 0.00 0.00 0.156239E+12 0.150929E+12 248592.61 17-APR-05:02 172595.31 0.69
May 0.00 0.00 0.229640E+12 0.196709E+12 294419.81 24-MAY-05:02 173170.27 0.82
June 0.00 0.00 0.258883E+12 0.194715E+12 307109.39 22-JUN-05:02 187091.32 0.81
July 0.00 0.00 0.276720E+12 0.170914E+12 342673.02 25-JUL-03:02 181778.09 0.79
August 0.00 0.00 0.269569E+12 0.160250E+12 322552.24 10-AUG-05:02 180795.29 0.76
September 0.00 0.00 0.207122E+12 0.132844E+12 313339.76 08-SEP-05:02 169863.66 0.70
October 0.00 0.00 0.125099E+12 0.111623E+12 249817.80 04-OCT-05:02 163803.78 0.64
November 0.00 0.00 0.673464E+11 0.669089E+11 152748.17 09-NOV-06:02 99836.80 0.53
December 0.00 0.00 0.288834E+11 0.288834E+11 67394.81 01-DEC-15:00 67394.81 0.32
                 
Annual Sum or Average 0.00 0.00 0.177893E+13 0.137182E+13       0.61
Minimum of Months 0.00 0.00 0.232183E+11 0.232183E+11 59605.80   59605.80 0.26
Maximum of Months 0.00 0.00 0.276720E+12 0.196709E+12 342673.02   187091.32 0.82



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.508292E+11 0.507519E+11 98805.55 17-JAN-04:02 85660.86 0.31
February 0.00 0.00 0.523339E+11 0.522820E+11 116353.47 27-FEB-04:02 84736.77 0.45
March 0.00 0.00 0.727924E+11 0.725662E+11 135638.78 13-MAR-03:02 94169.09 0.54
April 0.00 0.00 0.849268E+11 0.829803E+11 158468.71 27-APR-03:02 96542.15 0.52
May 0.00 0.00 0.109000E+12 0.968889E+11 184999.95 22-MAY-03:02 91230.48 0.60
June 0.00 0.00 0.128552E+12 0.100906E+12 213420.58 26-JUN-03:02 86799.52 0.63
July 0.00 0.00 0.150085E+12 0.100371E+12 224035.41 30-JUL-19:40 91119.37 0.62
August 0.00 0.00 0.168700E+12 0.109043E+12 240745.28 27-AUG-14:59 97063.34 0.67
September 0.00 0.00 0.132492E+12 0.931082E+11 217368.28 17-SEP-20:17 102940.02 0.64
October 0.00 0.00 0.951481E+11 0.883773E+11 166534.52 04-OCT-03:02 94188.97 0.63
November 0.00 0.00 0.728296E+11 0.725483E+11 121054.96 09-NOV-06:02 80524.94 0.57
December 0.00 0.00 0.582386E+11 0.582313E+11 92460.77 29-DEC-04:02 88388.53 0.38
                 
Annual Sum or Average 0.00 0.00 0.117593E+13 0.978054E+12       0.55
Minimum of Months 0.00 0.00 0.508292E+11 0.507519E+11 92460.77   80524.94 0.31
Maximum of Months 0.00 0.00 0.168700E+12 0.109043E+12 240745.28   102940.02 0.67



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.337411E+12 0.323791E+12 131369.15 17-JAN-15:00 124984.78 0.00
February 0.00 0.00 0.532790E+12 0.515874E+12 225101.03 24-FEB-17:00 219076.15 0.00
March 0.00 0.00 0.835439E+12 0.821376E+12 395738.57 31-MAR-24:00 393445.81 0.00
April 0.00 0.00 0.103387E+13 0.102764E+13 409642.52 22-APR-17:00 401408.45 0.00
May 0.00 0.00 0.362309E+12 0.345365E+12 226062.27 31-MAY-23:03 212107.23 0.00
June 0.00 0.00 0.598264E+12 0.572403E+12 318207.61 30-JUN-23:03 306257.71 0.00
July 0.00 0.00 0.873669E+12 0.837004E+12 401295.33 31-JUL-24:00 389769.04 0.00
August 0.00 0.00 0.109901E+13 0.106349E+13 421246.85 10-AUG-14:00 401433.81 0.00
September 0.00 0.00 0.366104E+12 0.334825E+12 227388.26 30-SEP-23:03 212883.38 0.00
October 0.00 0.00 0.601447E+12 0.585009E+12 310615.61 31-OCT-24:00 302108.06 0.00
November 0.00 0.00 0.817191E+12 0.797581E+12 321426.53 24-NOV-08:15 307251.90 0.00
December 0.00 0.00 0.109883E+13 0.106407E+13 421933.43 22-DEC-06:03 396277.65 0.00
                 
Annual Sum or Average 0.00 0.00 0.855633E+13 0.828842E+13       0.00
Minimum of Months 0.00 0.00 0.337411E+12 0.323791E+12 131369.15   124984.78 0.00
Maximum of Months 0.00 0.00 0.109901E+13 0.106407E+13 421933.43   401433.81 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.496405E+10 0.481944E+10 2461.85 12-JAN-17:00 2332.68 0.00
February 0.00 0.00 0.956863E+10 0.934264E+10 4507.57 21-FEB-17:00 4358.35 0.00
March 0.00 0.00 0.161863E+11 0.158562E+11 7782.42 31-MAR-24:00 7681.64 0.00
April 0.00 0.00 0.209044E+11 0.205976E+11 8531.71 17-APR-01:55 8274.66 0.00
May 0.00 0.00 0.718480E+10 0.652195E+10 4655.66 31-MAY-23:03 4042.65 0.00
June 0.00 0.00 0.123015E+11 0.112179E+11 6544.35 30-JUN-23:03 6031.78 0.00
July 0.00 0.00 0.181648E+11 0.165539E+11 8536.99 31-JUL-23:03 7741.65 0.00
August 0.00 0.00 0.227886E+11 0.210995E+11 8774.97 10-AUG-14:10 7955.55 0.00
September 0.00 0.00 0.731155E+10 0.604316E+10 4619.85 30-SEP-23:03 3997.36 0.00
October 0.00 0.00 0.116850E+11 0.110668E+11 5960.59 31-OCT-23:10 5711.11 0.00
November 0.00 0.00 0.155412E+11 0.152313E+11 6553.50 08-NOV-16:40 6300.45 0.00
December 0.00 0.00 0.205124E+11 0.203422E+11 8226.95 28-DEC-17:00 8066.52 0.00
                 
Annual Sum or Average 0.00 0.00 0.167113E+12 0.158693E+12       0.00
Minimum of Months 0.00 0.00 0.496405E+10 0.481944E+10 2461.85   2332.68 0.00
Maximum of Months 0.00 0.00 0.227886E+11 0.210995E+11 8774.97   8274.66 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.376245E+11 0.362624E+11 22908.01 12-JAN-17:00 21638.91 0.00
February 0.00 0.00 0.856789E+11 0.834441E+11 42571.53 22-FEB-17:00 41046.36 0.00
March 0.00 0.00 0.153034E+12 0.149743E+12 75049.05 31-MAR-24:00 74036.85 0.00
April 0.00 0.00 0.198255E+12 0.195176E+12 80291.95 12-APR-16:00 78025.38 0.00
May 0.00 0.00 0.677233E+11 0.611764E+11 44631.54 31-MAY-23:03 38359.29 0.00
June 0.00 0.00 0.117176E+12 0.106404E+12 63260.26 30-JUN-23:03 58093.40 0.00
July 0.00 0.00 0.173140E+12 0.157083E+12 81503.66 31-JUL-23:03 73553.17 0.00
August 0.00 0.00 0.216311E+12 0.199372E+12 83476.87 10-AUG-14:10 75342.21 0.00
September 0.00 0.00 0.687551E+11 0.562298E+11 44822.67 30-SEP-23:03 38474.61 0.00
October 0.00 0.00 0.110166E+12 0.104033E+12 56366.39 31-OCT-23:10 53807.87 0.00
November 0.00 0.00 0.144678E+12 0.141592E+12 62400.34 08-NOV-16:50 59802.51 0.00
December 0.00 0.00 0.187690E+12 0.185987E+12 77874.40 28-DEC-17:00 76278.70 0.00
                 
Annual Sum or Average 0.00 0.00 0.156023E+13 0.147650E+13       0.00
Minimum of Months 0.00 0.00 0.376245E+11 0.362624E+11 22908.01   21638.91 0.00
Maximum of Months 0.00 0.00 0.216311E+12 0.199372E+12 83476.87   78025.38 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.226246E+10 0.213883E+10 2298.72 12-JAN-17:00 2163.49 0.00
February 0.00 0.00 0.786748E+10 0.763117E+10 4312.75 22-FEB-17:00 4152.27 0.00
March 0.00 0.00 0.151537E+11 0.148056E+11 7466.29 31-MAR-24:00 7357.83 0.00
April 0.00 0.00 0.200188E+11 0.196932E+11 8283.88 16-APR-20:54 8000.82 0.00
May 0.00 0.00 0.703734E+10 0.636088E+10 4452.01 31-MAY-23:03 3811.14 0.00
June 0.00 0.00 0.119715E+11 0.108733E+11 6391.36 30-JUN-23:03 5866.14 0.00
July 0.00 0.00 0.175570E+11 0.159304E+11 8395.53 31-JUL-23:03 7573.77 0.00
August 0.00 0.00 0.220047E+11 0.202827E+11 8537.75 10-AUG-14:10 7709.19 0.00
September 0.00 0.00 0.698050E+10 0.570770E+10 4501.53 30-SEP-23:03 3858.03 0.00
October 0.00 0.00 0.109526E+11 0.103210E+11 5524.99 31-OCT-23:10 5257.24 0.00
November 0.00 0.00 0.139720E+11 0.136458E+11 6296.21 08-NOV-16:40 6037.44 0.00
December 0.00 0.00 0.175460E+11 0.173600E+11 7798.23 28-DEC-17:00 7631.12 0.00
                 
Annual Sum or Average 0.00 0.00 0.153324E+12 0.144751E+12       0.00
Minimum of Months 0.00 0.00 0.226246E+10 0.213883E+10 2298.72   2163.49 0.00
Maximum of Months 0.00 0.00 0.220047E+11 0.202827E+11 8537.75   8000.82 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 3288.70 207559.90 02-JAN-06:13
February 0.00 0.00 01-FEB-00:10 315.46 113461.85 11-FEB-06:02
March 0.00 0.00 01-MAR-00:10 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:03 0.00 0.00 01-APR-00:03
May 0.00 0.00 01-MAY-00:05 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:03 0.00 9.89 25-SEP-10:20
October 0.00 0.00 01-OCT-00:03 0.00 0.00 01-OCT-00:03
November 0.00 0.00 01-NOV-00:10 10.65 2741.34 27-NOV-06:05
December 0.00 0.00 01-DEC-00:10 887.88 99383.19 23-DEC-06:03
             
Annual Sum or Average 0.00     379.80    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   3288.70 207559.90  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 338362.96 1484294.89 12-JAN-14:10 4.37 58557.25 09-JAN-04:03
February 471508.37 1590596.31 17-FEB-16:10 145.26 244744.87 20-FEB-01:40
March 707682.66 2178349.57 14-MAR-05:02 1.20 16737.73 04-MAR-22:33
April 966365.79 3078479.26 17-APR-05:03 0.00 0.00 01-APR-00:03
May 1199020.52 3202931.04 18-MAY-05:02 0.00 0.00 01-MAY-00:05
June 1306546.33 3517870.50 27-JUN-05:02 0.00 0.00 01-JUN-00:10
July 1348206.12 3502432.09 06-JUL-05:02 0.00 0.00 01-JUL-00:05
August 1330200.70 3703129.11 07-AUG-05:03 0.00 0.00 01-AUG-00:03
September 1097778.47 3578453.37 05-SEP-05:04 0.00 0.00 01-SEP-00:03
October 838961.74 3189625.69 04-OCT-05:02 10.69 69135.39 28-OCT-19:33
November 601816.48 1849670.02 10-NOV-06:04 10.56 74720.81 19-NOV-08:13
December 406212.99 1581393.77 01-DEC-14:30 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 886590.48     13.39    
Minimum of Months 338362.96 1484294.89   0.00 0.00  
Maximum of Months 1348206.12 3703129.11   145.26 244744.87  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 211418.16 1659882.23 18-JAN-06:03 0.00 0.00 01-JAN-00:10
February 322634.06 2536869.36 25-FEB-06:03 0.00 0.00 01-FEB-00:10
March 530950.49 3593536.10 14-MAR-05:02 0.00 0.00 01-MAR-00:10
April 761685.85 4120582.58 17-APR-05:02 0.00 0.00 01-APR-00:03
May 1006300.65 4842933.64 24-MAY-05:02 0.00 0.00 01-MAY-00:05
June 1172891.89 5117348.16 27-JUN-05:02 0.00 0.00 01-JUN-00:10
July 1245830.12 5127218.35 18-JUL-05:02 0.00 0.00 01-JUL-00:05
August 1243429.77 5066309.31 09-AUG-05:02 0.00 0.00 01-AUG-00:03
September 1004343.59 5005870.77 06-SEP-05:02 0.00 0.00 01-SEP-00:03
October 657864.09 4702443.16 04-OCT-05:02 0.00 0.00 01-OCT-00:03
November 452532.23 3225268.09 09-NOV-06:02 0.00 0.00 01-NOV-00:10
December 261652.31 1665391.87 13-DEC-06:03 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 741529.24     0.00    
Minimum of Months 211418.16 1659882.23   0.00 0.00  
Maximum of Months 1245830.12 5127218.35   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 221478.88 581796.75 12-JAN-15:00 0.00 0.00 01-JAN-00:10
February 497445.86 1014514.91 22-FEB-15:00 0.00 0.00 01-FEB-00:10
March 963295.28 1757316.38 28-MAR-15:20 0.00 0.00 01-MAR-00:10
April 1582935.43 2218641.77 15-APR-15:00 0.00 0.00 01-APR-00:03
May 1117280.36 1775093.23 01-MAY-15:00 0.00 0.00 01-MAY-00:05
June 1409231.00 2060731.80 08-JUN-16:00 0.00 0.00 01-JUN-00:10
July 1551733.28 2083446.05 07-JUL-15:00 0.00 0.00 01-JUL-00:05
August 1664286.44 2080587.03 07-AUG-15:00 0.00 0.00 01-AUG-00:03
September 897172.92 1393224.69 17-SEP-20:00 0.00 0.00 01-SEP-00:03
October 902837.86 1572825.95 02-OCT-15:00 0.00 0.00 01-OCT-00:03
November 818829.36 1420749.50 08-NOV-15:00 0.00 0.00 01-NOV-00:10
December 785993.58 1320185.87 28-DEC-14:20 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 1037226.36     0.00    
Minimum of Months 221478.88 581796.75   0.00 0.00  
Maximum of Months 1664286.44 2218641.77   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 12736.51 41939.93 18-JAN-12:50
February 0.00 0.00 01-FEB-00:10 12564.27 41692.37 01-FEB-12:40
March 0.00 0.00 01-MAR-00:10 12460.74 39951.39 01-MAR-12:40
April 0.00 0.00 01-APR-00:03 10710.40 36287.29 03-APR-11:40
May 0.00 0.00 01-MAY-00:05 9907.20 32621.48 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 9217.51 29011.23 01-JUN-11:50
July 0.00 0.00 01-JUL-00:05 8270.58 26824.63 03-JUL-11:30
August 0.00 0.00 01-AUG-00:03 9179.52 28583.78 31-AUG-11:40
September 0.00 0.00 01-SEP-00:03 9467.79 31745.88 29-SEP-11:50
October 0.00 0.00 01-OCT-00:03 10514.71 35938.15 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 11730.58 39428.93 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 12147.66 41507.46 29-DEC-13:00
             
Annual Sum or Average 0.00     10732.36    
Minimum of Months 0.00 0.00   8270.58 26824.63  
Maximum of Months 0.00 0.00   12736.51 41939.93  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 198837.52 1084391.75 25-JAN-16:10 2946.31 144923.88 04-JAN-07:00
February 309851.23 1223385.09 22-FEB-15:30 1249.39 132853.29 01-FEB-06:50
March 561243.25 3213183.62 10-MAR-17:00 329.85 67291.58 02-MAR-04:30
April 1047093.08 4907954.29 18-APR-14:00 173.94 40475.78 10-APR-01:15
May 2208387.84 6628981.06 17-MAY-15:30 0.00 0.00 01-MAY-00:05
June 3317457.73 7696082.91 27-JUN-05:04 0.00 0.00 01-JUN-00:10
July 4206224.90 7783576.19 18-JUL-05:04 0.00 0.00 01-JUL-00:05
August 4236997.61 7525760.18 28-AUG-14:40 0.00 0.00 01-AUG-00:03
September 2941726.81 7293616.55 14-SEP-15:30 0.00 0.00 01-SEP-00:03
October 928113.33 4676191.28 04-OCT-05:04 33.74 23605.04 09-OCT-04:30
November 443314.24 2660791.00 09-NOV-11:20 577.35 75347.51 27-NOV-05:45
December 242173.05 1128014.71 01-DEC-16:00 1922.03 149588.97 30-DEC-05:30
             
Annual Sum or Average 1729328.47     601.95    
Minimum of Months 198837.52 1084391.75   0.00 0.00  
Maximum of Months 4236997.61 7783576.19   2946.31 149588.97  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.153726E+11 0.86 9441.50 01-JAN-00:10 1.42
February 0.136259E+11 0.84 9441.50 01-FEB-04:05 1.42
March 0.154623E+11 0.86 9441.50 01-MAR-04:03 1.42
April 0.144630E+11 0.84 9441.50 01-APR-03:03 1.42
May 0.154308E+11 0.86 9441.50 01-MAY-00:05 1.42
June 0.155245E+11 0.89 9441.50 01-JUN-03:02 1.41
July 0.160111E+11 0.89 9441.50 01-JUL-03:02 1.41
August 0.172150E+11 0.96 9441.50 01-AUG-03:02 1.41
September 0.160500E+11 0.92 9441.50 01-SEP-03:02 1.41
October 0.165709E+11 0.92 9441.50 01-OCT-10:43 1.40
November 0.159158E+11 0.92 9441.50 01-NOV-03:02 1.41
December 0.157564E+11 0.88 9441.50 01-DEC-04:03 1.42
           
Annual Sum or Average 0.187398E+12 0.89      
Minimum of Months 0.136259E+11 0.84 9441.50   1.40
Maximum of Months 0.172150E+11 0.96 9441.50   1.42



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.537995E+10 0.36 9543.90 14-JAN-06:02 1.09
February 0.646967E+10 0.43 12382.88 21-FEB-16:00 1.29
March 0.103858E+11 0.57 21044.18 14-MAR-05:02 1.79
April 0.132675E+11 0.71 21188.12 03-APR-05:02 1.80
May 0.125789E+11 0.66 21188.12 01-MAY-04:22 1.80
June 0.133987E+11 0.71 21188.12 01-JUN-05:02 1.80
July 0.137139E+11 0.70 21188.12 03-JUL-04:22 1.80
August 0.168514E+11 0.79 21188.12 01-AUG-05:02 1.80
September 0.102823E+11 0.58 21188.12 01-SEP-05:02 1.80
October 0.988408E+10 0.56 21188.12 02-OCT-05:02 1.80
November 0.858474E+10 0.50 18155.98 06-NOV-06:02 1.63
December 0.769572E+10 0.45 12016.50 29-DEC-06:02 1.26
           
Annual Sum or Average 0.128493E+12 0.59      
Minimum of Months 0.537995E+10 0.36 9543.90   1.09
Maximum of Months 0.168514E+11 0.79 21188.12   1.80



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.375350E+11 0.31 78641.93 02-JAN-06:01 1.01
February 0.435581E+11 0.36 100676.55 21-FEB-06:03 1.17
March 0.725011E+11 0.45 200428.27 14-MAR-05:02 1.80
April 0.914074E+11 0.55 200428.27 01-APR-05:02 1.80
May 0.106880E+12 0.62 200428.27 05-MAY-05:02 1.80
June 0.105107E+12 0.62 200428.27 01-JUN-05:02 1.80
July 0.954552E+11 0.57 200428.27 06-JUL-05:02 1.80
August 0.987994E+11 0.57 200428.27 01-AUG-05:02 1.80
September 0.830838E+11 0.51 200428.27 01-SEP-05:02 1.80
October 0.724875E+11 0.46 200428.27 02-OCT-05:02 1.80
November 0.545110E+11 0.39 144790.05 09-NOV-06:02 1.47
December 0.411517E+11 0.33 78641.93 01-DEC-05:03 1.01
           
Annual Sum or Average 0.902478E+12 0.48      
Minimum of Months 0.375350E+11 0.31 78641.93   1.01
Maximum of Months 0.106880E+12 0.62 200428.27   1.80



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.287959E+10 0.28 4300.58 02-JAN-05:01 0.67
February 0.347957E+10 0.31 8001.85 22-FEB-15:00 0.94
March 0.680978E+10 0.41 20395.72 14-MAR-05:02 1.67
April 0.101960E+11 0.55 22752.79 17-APR-05:02 1.79
May 0.126904E+11 0.63 22752.79 01-MAY-05:02 1.79
June 0.126853E+11 0.64 22752.79 02-JUN-05:02 1.79
July 0.108561E+11 0.57 22752.79 03-JUL-05:02 1.79
August 0.107163E+11 0.56 22752.79 01-AUG-05:02 1.79
September 0.872038E+10 0.49 22752.79 01-SEP-05:02 1.79
October 0.721443E+10 0.43 21496.52 04-OCT-05:02 1.73
November 0.475144E+10 0.34 12175.41 09-NOV-06:02 1.21
December 0.302798E+10 0.28 7289.53 29-DEC-06:02 0.89
           
Annual Sum or Average 0.940273E+11 0.46      
Minimum of Months 0.287959E+10 0.28 4300.58   0.67
Maximum of Months 0.126904E+11 0.64 22752.79   1.79



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.967421E+11 1.38 36119.35 01-JAN-00:10 1.38
February 0.873799E+11 1.38 36119.35 01-FEB-00:10 1.38
March 0.967421E+11 1.38 36119.35 01-MAR-00:10 1.38
April 0.936213E+11 1.38 36119.35 01-APR-00:03 1.38
May 0.967421E+11 1.38 36119.35 01-MAY-00:05 1.38
June 0.936213E+11 1.38 36119.35 01-JUN-00:10 1.38
July 0.967421E+11 1.38 36119.35 01-JUL-00:05 1.38
August 0.967421E+11 1.38 36119.35 01-AUG-00:03 1.38
September 0.936213E+11 1.38 36119.35 01-SEP-00:03 1.38
October 0.967421E+11 1.38 36119.35 01-OCT-00:03 1.38
November 0.936213E+11 1.38 36119.35 01-NOV-00:10 1.38
December 0.967421E+11 1.38 36119.35 01-DEC-00:10 1.38
           
Annual Sum or Average 0.113906E+13 1.38      
Minimum of Months 0.873799E+11 1.38 36119.35   1.38
Maximum of Months 0.967421E+11 1.38 36119.35   1.38



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.144892E+10 0.94 540.96 01-JAN-00:10 0.94
February 0.130870E+10 0.94 540.96 01-FEB-00:10 0.94
March 0.144892E+10 0.94 540.96 01-MAR-00:10 0.94
April 0.140218E+10 0.94 540.96 01-APR-00:03 0.94
May 0.144892E+10 0.93 540.96 01-MAY-00:05 0.94
June 0.140218E+10 0.93 540.96 01-JUN-00:10 0.94
July 0.144892E+10 0.93 540.96 01-JUL-00:05 0.93
August 0.144892E+10 0.93 540.96 01-AUG-00:03 0.93
September 0.140218E+10 0.93 540.96 01-SEP-00:03 0.93
October 0.144892E+10 0.94 540.96 01-OCT-00:03 0.94
November 0.140218E+10 0.94 540.96 01-NOV-00:10 0.94
December 0.144892E+10 0.94 540.96 01-DEC-00:10 0.94
           
Annual Sum or Average 0.170598E+11 0.94      
Minimum of Months 0.130870E+10 0.93 540.96   0.93
Maximum of Months 0.144892E+10 0.94 540.96   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138023E+11 0.94 5153.18 01-JAN-00:10 0.94
February 0.124666E+11 0.94 5153.18 01-FEB-00:10 0.94
March 0.138023E+11 0.94 5153.18 01-MAR-00:10 0.94
April 0.133570E+11 0.94 5153.18 01-APR-00:03 0.94
May 0.138023E+11 0.93 5153.18 01-MAY-00:05 0.94
June 0.133570E+11 0.93 5153.18 01-JUN-00:10 0.93
July 0.138023E+11 0.93 5153.18 01-JUL-00:05 0.93
August 0.138023E+11 0.93 5153.18 01-AUG-00:03 0.93
September 0.133570E+11 0.93 5153.18 01-SEP-00:03 0.93
October 0.138023E+11 0.94 5153.18 01-OCT-00:03 0.94
November 0.133570E+11 0.94 5153.18 01-NOV-00:10 0.94
December 0.138023E+11 0.94 5153.18 01-DEC-00:10 0.94
           
Annual Sum or Average 0.162511E+12 0.94      
Minimum of Months 0.124666E+11 0.93 5153.18   0.93
Maximum of Months 0.138023E+11 0.94 5153.18   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.138998E+10 0.94 518.96 01-JAN-00:10 0.94
February 0.125547E+10 0.94 518.96 01-FEB-00:10 0.94
March 0.138998E+10 0.94 518.96 01-MAR-00:10 0.94
April 0.134514E+10 0.94 518.96 01-APR-00:03 0.94
May 0.138998E+10 0.93 518.96 01-MAY-00:05 0.94
June 0.134514E+10 0.93 518.96 01-JUN-00:10 0.94
July 0.138998E+10 0.93 518.96 01-JUL-00:05 0.94
August 0.138998E+10 0.93 518.96 01-AUG-00:03 0.94
September 0.134514E+10 0.93 518.96 01-SEP-00:03 0.93
October 0.138998E+10 0.94 518.96 01-OCT-00:03 0.94
November 0.134514E+10 0.94 518.96 01-NOV-00:10 0.94
December 0.138998E+10 0.94 518.96 01-DEC-00:10 0.94
           
Annual Sum or Average 0.163659E+11 0.94      
Minimum of Months 0.125547E+10 0.93 518.96   0.93
Maximum of Months 0.138998E+10 0.94 518.96   0.94



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 43478407.91 39130567.12 1226.44 02-JAN-06:01 1103.80 1103.80 48.19 1.50
February 3434638.42 3091174.58 466.06 11-FEB-06:02 419.46 419.46 25.81 0.51
March 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00 24.47 0.00
April 0.00 0.00 0.00 01-APR-00:03 0.00 0.00 24.47 0.00
May 0.00 0.00 0.00 01-MAY-00:05 0.00 0.00 24.47 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 24.47 0.00
July 0.00 0.00 0.00 01-JUL-00:05 0.00 0.00 24.47 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 24.47 0.00
September 25.37 22.83 0.04 25-SEP-10:20 0.04 0.04 24.47 0.00
October 0.00 0.00 0.00 01-OCT-00:03 0.00 0.00 24.47 0.00
November 116959.72 105263.75 11.58 27-NOV-06:05 10.42 10.42 23.98 0.01
December 11099087.74 9989178.97 520.32 23-DEC-06:03 468.29 468.29 38.20 0.57
                 
Annual Sum or Average 58129119.16 52316207.25            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 23.98 0.00
Maximum of Months 43478407.91 39130567.12 1226.44   1103.80 1103.80 48.19 1.50



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.267171E+09 0.240454E+09 2866.15 28-JAN-06:02 2579.53 2579.53 8.62 49.56
February 0.492713E+09 0.443441E+09 5748.39 25-FEB-06:03 5173.55 5173.55 8.33 66.96
March 0.997944E+09 0.898150E+09 14525.48 27-MAR-05:03 13072.93 13072.93 7.98 98.13
April 0.158003E+10 0.142203E+10 21618.04 11-APR-05:03 19456.23 19456.23 8.37 114.98
May 0.203343E+10 0.183009E+10 24944.71 24-MAY-05:02 22450.24 22450.24 7.45 121.65
June 0.236270E+10 0.212643E+10 25398.51 27-JUN-05:02 22858.66 22858.66 7.98 122.52
July 0.261432E+10 0.235289E+10 25398.51 06-JUL-05:02 22858.66 22858.66 7.98 122.52
August 0.275158E+10 0.247642E+10 25398.51 10-AUG-05:02 22858.66 22858.66 7.37 122.52
September 0.198680E+10 0.178812E+10 25398.51 05-SEP-05:02 22858.66 22858.66 7.41 122.52
October 0.131607E+10 0.118447E+10 24658.18 04-OCT-05:02 22192.36 22192.36 7.99 121.09
November 0.975519E+09 0.877967E+09 9995.47 09-NOV-06:02 8995.92 8995.92 8.36 84.31
December 0.394752E+09 0.355277E+09 4001.16 13-DEC-06:03 3601.04 3601.04 8.75 57.34
                 
Annual Sum or Average 0.177730E+11 0.159957E+11            
Minimum of Months 0.267171E+09 0.240454E+09 2866.15   2579.53 2579.53 7.37 49.56
Maximum of Months 0.275158E+10 0.247642E+10 25398.51   22858.66 22858.66 8.75 122.52



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.266635E+11 0.239971E+11 17481.11 01-JAN-00:15 15733.00 15733.00 8.46 122.52
February 0.267811E+11 0.241030E+11 17481.11 01-FEB-04:05 15733.00 15733.00 8.60 122.52
March 0.364840E+11 0.328356E+11 17481.11 01-MAR-04:03 15733.00 15733.00 8.97 122.52
April 0.422666E+11 0.380399E+11 17481.11 01-APR-00:10 15733.00 15733.00 7.33 122.52
May 0.432807E+11 0.389527E+11 17481.11 01-MAY-00:05 15733.00 15733.00 8.24 122.52
June 0.419553E+11 0.377598E+11 17481.11 01-JUN-00:23 15733.00 15733.00 7.02 122.52
July 0.446970E+11 0.402273E+11 17481.11 01-JUL-00:05 15733.00 15733.00 8.93 122.52
August 0.444716E+11 0.400245E+11 17481.11 01-AUG-00:13 15733.00 15733.00 7.41 122.52
September 0.382434E+11 0.344191E+11 17481.11 01-SEP-00:03 15733.00 15733.00 8.91 122.52
October 0.374306E+11 0.336875E+11 17481.11 01-OCT-00:53 15733.00 15733.00 7.01 122.52
November 0.324677E+11 0.292209E+11 17481.11 01-NOV-03:02 15733.00 15733.00 10.17 122.52
December 0.299296E+11 0.269366E+11 17481.11 01-DEC-04:03 15733.00 15733.00 9.01 122.52
                 
Annual Sum or Average 0.444671E+12 0.400204E+12            
Minimum of Months 0.266635E+11 0.239971E+11 17481.11   15733.00 15733.00 7.01 122.52
Maximum of Months 0.446970E+11 0.402273E+11 17481.11   15733.00 15733.00 10.17 122.52



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.941118E+10 0.847006E+10 3513.73 01-JAN-00:10 3162.36 3162.36 21.71 14.67
February 0.850042E+10 0.765038E+10 3513.73 01-FEB-00:10 3162.36 3162.36 24.25 14.67
March 0.941118E+10 0.847006E+10 3513.73 01-MAR-00:10 3162.36 3162.36 28.58 14.67
April 0.910759E+10 0.819683E+10 3513.73 01-APR-00:03 3162.36 3162.36 42.38 14.67
May 0.941118E+10 0.847006E+10 3513.73 01-MAY-00:05 3162.36 3162.36 37.79 14.67
June 0.910759E+10 0.819683E+10 3513.73 01-JUN-00:10 3162.36 3162.36 38.95 14.67
July 0.941118E+10 0.847006E+10 3513.73 01-JUL-00:05 3162.36 3162.36 49.00 14.67
August 0.941118E+10 0.847006E+10 3513.73 01-AUG-00:03 3162.36 3162.36 49.11 14.67
September 0.910759E+10 0.819683E+10 3513.73 01-SEP-00:03 3162.36 3162.36 36.30 14.67
October 0.941118E+10 0.847006E+10 3513.73 01-OCT-00:03 3162.36 3162.36 37.33 14.67
November 0.910759E+10 0.819683E+10 3513.73 01-NOV-00:10 3162.36 3162.36 31.79 14.67
December 0.941118E+10 0.847006E+10 3513.73 01-DEC-00:10 3162.36 3162.36 29.94 14.67
                 
Annual Sum or Average 0.110809E+12 0.997282E+11            
Minimum of Months 0.850042E+10 0.765038E+10 3513.73   3162.36 3162.36 21.71 14.67
Maximum of Months 0.941118E+10 0.847006E+10 3513.73   3162.36 3162.36 49.11 14.67



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:05 1.79 1.79 55.98 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:02 1.79 1.79 56.12 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:02 1.79 1.79 56.20 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:02 1.79 1.79 56.70 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:02 1.79 1.79 58.03 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:02 1.79 1.79 57.70 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:03 1.79 1.79 57.83 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:02 1.79 1.79 57.70 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:02 1.79 1.79 58.01 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:05 1.79 1.79 56.41 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 56.26 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:03 1.79 1.79 56.19 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.98 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 58.03 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.330930E+11 0.297837E+11 43378.03 12-JAN-14:10 39040.23 39040.23 22.67 144.34
February 0.341514E+11 0.307363E+11 43383.77 21-FEB-11:40 39045.39 39045.39 22.85 144.34
March 0.494851E+11 0.445365E+11 43502.73 10-MAR-17:00 39152.45 39152.45 26.43 144.34
April 0.651710E+11 0.586539E+11 43589.78 18-APR-12:30 39230.80 39230.80 28.84 144.34
May 0.760417E+11 0.684376E+11 43589.78 09-MAY-13:10 39230.80 39230.80 28.84 144.34
June 0.788177E+11 0.709359E+11 43589.78 05-JUN-15:00 39230.80 39230.80 28.87 144.34
July 0.858796E+11 0.772916E+11 43589.78 01-JUL-05:03 39230.80 39230.80 29.05 144.34
August 0.868735E+11 0.781861E+11 43589.78 01-AUG-03:02 39230.80 39230.80 28.88 144.34
September 0.697920E+11 0.628128E+11 43589.78 01-SEP-03:04 39230.80 39230.80 29.52 144.34
October 0.576923E+11 0.519231E+11 43589.78 04-OCT-05:04 39230.80 39230.80 28.85 144.34
November 0.415426E+11 0.373883E+11 43469.35 09-NOV-11:20 39122.41 39122.41 25.51 144.34
December 0.375021E+11 0.337519E+11 43381.74 01-DEC-14:20 39043.56 39043.56 22.78 144.34
                 
Annual Sum or Average 0.716042E+12 0.644438E+12            
Minimum of Months 0.330930E+11 0.297837E+11 43378.03   39040.23 39040.23 22.67 144.34
Maximum of Months 0.868735E+11 0.781861E+11 43589.78   39230.80 39230.80 29.52 144.34



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 79.76 79.76 3288.70 207559.90 02-JAN-06:13
February 0.00 0.00 01-FEB-00:10 29.26 29.26 315.46 113461.85 11-FEB-06:02
March 0.00 0.00 01-MAR-00:10 24.47 24.47 0.00 0.00 01-MAR-00:10
April 0.00 0.00 01-APR-00:03 24.47 24.47 0.00 0.00 01-APR-00:03
May 0.00 0.00 01-MAY-00:05 24.47 24.47 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 24.47 24.47 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:05 24.47 24.47 0.00 0.00 01-JUL-00:05
August 0.00 0.00 01-AUG-00:03 24.47 24.47 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:03 24.47 24.47 0.00 9.89 25-SEP-10:20
October 0.00 0.00 01-OCT-00:03 24.47 24.47 0.00 0.00 01-OCT-00:03
November 0.00 0.00 01-NOV-00:10 24.47 24.47 10.65 2741.34 27-NOV-06:05
December 0.00 0.00 01-DEC-00:10 23.69 23.69 887.88 99383.19 23-DEC-06:03
                 
Annual Sum or Average 0.00         379.80    
Minimum of Months 0.00 0.00   23.69 23.69 0.00 0.00  
Maximum of Months 0.00 0.00   79.76 79.76 3288.70 207559.90  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 338362.96 1484294.89 12-JAN-14:10 10.09 8.63 4.37 58557.25 09-JAN-04:03
February 471508.37 1590596.31 17-FEB-16:10 10.36 8.68 145.26 244744.87 20-FEB-01:40
March 707682.66 2178349.57 14-MAR-05:02 11.85 7.60 1.20 16737.73 04-MAR-22:33
April 966365.79 3078479.26 17-APR-05:03 13.07 7.37 0.00 0.00 01-APR-00:03
May 1199020.52 3202931.04 18-MAY-05:02 12.94 7.23 0.00 0.00 01-MAY-00:05
June 1306546.33 3517870.50 27-JUN-05:02 13.56 7.85 0.00 0.00 01-JUN-00:10
July 1348206.12 3502432.09 06-JUL-05:02 13.53 7.82 0.00 0.00 01-JUL-00:05
August 1330200.70 3703129.11 07-AUG-05:03 13.92 8.21 0.00 0.00 01-AUG-00:03
September 1097778.47 3578453.37 05-SEP-05:04 13.75 8.04 0.00 0.00 01-SEP-00:03
October 838961.74 3189625.69 04-OCT-05:02 13.16 7.45 10.69 69135.39 28-OCT-19:33
November 601816.48 1849670.02 10-NOV-06:04 11.76 8.16 10.56 74720.81 19-NOV-08:13
December 406212.99 1581393.77 01-DEC-14:30 10.27 8.61 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 886590.48         13.39    
Minimum of Months 338362.96 1484294.89   10.09 7.23 0.00 0.00  
Maximum of Months 1348206.12 3703129.11   13.92 8.68 145.26 244744.87  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 211418.16 1659882.23 18-JAN-06:03 15.05 9.01 0.00 0.00 01-JAN-00:10
February 322634.06 2536869.36 25-FEB-06:03 15.75 8.92 0.00 0.00 01-FEB-00:10
March 530950.49 3593536.10 14-MAR-05:02 15.57 7.94 0.00 0.00 01-MAR-00:10
April 761685.85 4120582.58 17-APR-05:02 16.28 7.56 0.00 0.00 01-APR-00:03
May 1006300.65 4842933.64 24-MAY-05:02 16.22 7.01 0.00 0.00 01-MAY-00:05
June 1172891.89 5117348.16 27-JUN-05:02 16.68 7.93 0.00 0.00 01-JUN-00:10
July 1245830.12 5127218.35 18-JUL-05:02 16.70 7.87 0.00 0.00 01-JUL-00:05
August 1243429.77 5066309.31 09-AUG-05:02 16.81 7.70 0.00 0.00 01-AUG-00:03
September 1004343.59 5005870.77 06-SEP-05:02 16.47 7.78 0.00 0.00 01-SEP-00:03
October 657864.09 4702443.16 04-OCT-05:02 15.98 7.81 0.00 0.00 01-OCT-00:03
November 452532.23 3225268.09 09-NOV-06:02 15.84 8.12 0.00 0.00 01-NOV-00:10
December 261652.31 1665391.87 13-DEC-06:03 13.64 8.96 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 741529.24         0.00    
Minimum of Months 211418.16 1659882.23   13.64 7.01 0.00 0.00  
Maximum of Months 1245830.12 5127218.35   16.81 9.01 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 221478.88 581796.75 12-JAN-15:00 29.65 25.58 0.00 0.00 01-JAN-00:10
February 497445.86 1014514.91 22-FEB-15:00 37.93 30.67 0.00 0.00 01-FEB-00:10
March 963295.28 1757316.38 28-MAR-15:20 51.83 41.00 0.00 0.00 01-MAR-00:10
April 1582935.43 2218641.77 15-APR-15:00 60.29 47.04 0.00 0.00 01-APR-00:03
May 1117280.36 1775093.23 01-MAY-15:00 52.16 46.86 0.00 0.00 01-MAY-00:05
June 1409231.00 2060731.80 08-JUN-16:00 57.41 48.91 0.00 0.00 01-JUN-00:10
July 1551733.28 2083446.05 07-JUL-15:00 57.83 46.26 0.00 0.00 01-JUL-00:05
August 1664286.44 2080587.03 07-AUG-15:00 57.77 44.19 0.00 0.00 01-AUG-00:03
September 897172.92 1393224.69 17-SEP-20:00 45.06 40.01 0.00 0.00 01-SEP-00:03
October 902837.86 1572825.95 02-OCT-15:00 48.41 40.40 0.00 0.00 01-OCT-00:03
November 818829.36 1420749.50 08-NOV-15:00 45.57 35.11 0.00 0.00 01-NOV-00:10
December 785993.58 1320185.87 28-DEC-14:20 43.69 30.91 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 1037226.36         0.00    
Minimum of Months 221478.88 581796.75   29.65 25.58 0.00 0.00  
Maximum of Months 1664286.44 2218641.77   60.29 48.91 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:10 57.15 57.15 12736.51 41939.93 18-JAN-12:50
February 0.00 0.00 01-FEB-00:10 56.57 56.57 12564.27 41692.37 01-FEB-12:40
March 0.00 0.00 01-MAR-00:10 56.63 56.63 12460.74 39951.39 01-MAR-12:40
April 0.00 0.00 01-APR-00:03 57.05 57.05 10710.40 36287.29 03-APR-11:40
May 0.00 0.00 01-MAY-00:05 58.45 58.45 9907.20 32621.48 01-MAY-12:00
June 0.00 0.00 01-JUN-00:10 57.95 57.95 9217.51 29011.23 01-JUN-11:50
July 0.00 0.00 01-JUL-00:05 58.08 58.08 8270.58 26824.63 03-JUL-11:30
August 0.00 0.00 01-AUG-00:03 58.38 58.38 9179.52 28583.78 31-AUG-11:40
September 0.00 0.00 01-SEP-00:03 58.26 58.26 9467.79 31745.88 29-SEP-11:50
October 0.00 0.00 01-OCT-00:03 56.81 56.81 10514.71 35938.15 31-OCT-11:20
November 0.00 0.00 01-NOV-00:10 56.69 56.69 11730.58 39428.93 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 56.67 56.67 12147.66 41507.46 29-DEC-13:00
                 
Annual Sum or Average 0.00         10732.36    
Minimum of Months 0.00 0.00   56.57 56.57 8270.58 26824.63  
Maximum of Months 0.00 0.00   58.45 58.45 12736.51 41939.93  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 198837.52 1084391.75 25-JAN-16:10 24.70 21.10 2946.31 144923.88 04-JAN-07:00
February 309851.23 1223385.09 22-FEB-15:30 25.16 21.10 1249.39 132853.29 01-FEB-06:50
March 561243.25 3213183.62 10-MAR-17:00 26.43 23.32 329.85 67291.58 02-MAR-04:30
April 1047093.08 4907954.29 18-APR-14:00 29.23 25.57 173.94 40475.78 10-APR-01:15
May 2208387.84 6628981.06 17-MAY-15:30 32.09 27.83 0.00 0.00 01-MAY-00:05
June 3317457.73 7696082.91 27-JUN-05:04 33.86 28.87 0.00 0.00 01-JUN-00:10
July 4206224.90 7783576.19 18-JUL-05:04 34.00 29.03 0.00 0.00 01-JUL-00:05
August 4236997.61 7525760.18 28-AUG-14:40 33.57 28.90 0.00 0.00 01-AUG-00:03
September 2941726.81 7293616.55 14-SEP-15:30 33.19 28.77 0.00 0.00 01-SEP-00:03
October 928113.33 4676191.28 04-OCT-05:04 28.85 24.37 33.74 23605.04 09-OCT-04:30
November 443314.24 2660791.00 09-NOV-11:20 25.51 21.51 577.35 75347.51 27-NOV-05:45
December 242173.05 1128014.71 01-DEC-16:00 24.84 21.10 1922.03 149588.97 30-DEC-05:30
                 
Annual Sum or Average 1729328.47         601.95    
Minimum of Months 198837.52 1084391.75   24.70 21.10 0.00 0.00  
Maximum of Months 4236997.61 7783576.19   34.00 29.03 2946.31 149588.97  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.163125E+09 0.00 0.453706E+11 0.537995E+10 0.00 0.00
February 807832.26 0.00 0.643314E+11 0.646967E+10 0.00 0.00
March 0.00 0.00 0.120624E+12 0.103858E+11 0.00 0.00
April 0.00 0.00 0.177620E+12 0.132675E+11 0.00 0.00
May 0.00 0.00 0.217423E+12 0.125789E+11 0.00 0.00
June 0.00 0.00 0.256762E+12 0.133987E+11 0.00 0.00
July 0.00 0.00 0.297209E+12 0.137139E+11 0.00 0.00
August 0.00 0.00 0.318655E+12 0.168514E+11 0.00 0.00
September 0.00 0.00 0.221857E+12 0.102823E+11 0.00 0.00
October 0.00 0.00 0.148554E+12 0.988408E+10 0.00 0.00
November 0.00 0.00 0.990074E+11 0.858474E+10 0.00 0.00
December 35436036.95 0.00 0.660829E+11 0.769572E+10 0.00 0.00
             
Annual Sum or Average 0.199369E+09 0.00 0.203350E+13 0.128493E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.453706E+11 0.537995E+10 0.00 0.00
Maximum of Months 0.163125E+09 0.00 0.318655E+12 0.168514E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.426844E+10 0.00 0.316074E+12 0.375350E+11 0.00 0.00
February 0.159464E+09 0.00 0.466977E+12 0.435581E+11 0.00 0.00
March 0.00 0.00 0.922597E+12 0.725011E+11 0.00 0.00
April 0.00 0.00 0.137792E+13 0.914074E+11 0.00 0.00
May 0.00 0.00 0.199934E+13 0.106880E+12 0.00 0.00
June 0.00 0.00 0.227613E+13 0.105107E+12 0.00 0.00
July 0.00 0.00 0.250696E+13 0.954552E+11 0.00 0.00
August 0.00 0.00 0.247813E+13 0.987994E+11 0.00 0.00
September 7053.43 0.00 0.192020E+13 0.830838E+11 0.00 0.00
October 0.00 0.00 0.121278E+13 0.724875E+11 0.00 0.00
November 0.00 0.00 0.725332E+12 0.545110E+11 0.00 0.00
December 0.856340E+09 0.00 0.384513E+12 0.411517E+11 0.00 0.00
             
Annual Sum or Average 0.528425E+10 0.00 0.165870E+14 0.902478E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.316074E+12 0.375350E+11 0.00 0.00
Maximum of Months 0.426844E+10 0.00 0.250696E+13 0.106880E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.460983E+10 0.00 0.232183E+11 0.287959E+10 0.00 0.00
February 0.625311E+09 0.00 0.412320E+11 0.347957E+10 0.00 0.00
March 0.00 0.00 0.949783E+11 0.680978E+10 0.00 0.00
April 0.00 0.00 0.156239E+12 0.101960E+11 0.00 0.00
May 0.00 0.00 0.229640E+12 0.126904E+11 0.00 0.00
June 0.00 0.00 0.258883E+12 0.126853E+11 0.00 0.00
July 0.00 0.00 0.276720E+12 0.108561E+11 0.00 0.00
August 0.00 0.00 0.269569E+12 0.107163E+11 0.00 0.00
September 0.00 0.00 0.207122E+12 0.872038E+10 0.00 0.00
October 0.00 0.00 0.125099E+12 0.721443E+10 0.00 0.00
November 30223131.05 0.00 0.673464E+11 0.475144E+10 0.00 0.00
December 0.150500E+10 0.00 0.288834E+11 0.302798E+10 0.00 0.00
             
Annual Sum or Average 0.677037E+10 0.00 0.177893E+13 0.940273E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.232183E+11 0.287959E+10 0.00 0.00
Maximum of Months 0.460983E+10 0.00 0.276720E+12 0.126904E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.508292E+11 0.153726E+11 0.00 0.00
February 0.00 0.00 0.523339E+11 0.136259E+11 0.00 0.00
March 0.00 0.00 0.727924E+11 0.154623E+11 0.00 0.00
April 0.00 0.00 0.849268E+11 0.144630E+11 0.00 0.00
May 0.00 0.00 0.109000E+12 0.154308E+11 0.00 0.00
June 0.00 0.00 0.128552E+12 0.155245E+11 0.00 0.00
July 0.00 0.00 0.150085E+12 0.160111E+11 0.00 0.00
August 0.00 0.00 0.168700E+12 0.172150E+11 0.00 0.00
September 0.00 0.00 0.132492E+12 0.160500E+11 0.00 0.00
October 0.00 0.00 0.951481E+11 0.165709E+11 0.00 0.00
November 0.00 0.00 0.728296E+11 0.159158E+11 0.00 0.00
December 0.00 0.00 0.582386E+11 0.157564E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.117593E+13 0.187398E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.508292E+11 0.136259E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.168700E+12 0.172150E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.424817E+12 0.196128E+12 0.00 4.46
February 0.00 0.00 0.674414E+12 0.242123E+12 0.00 4.88
March 0.00 0.00 0.108941E+13 0.357561E+12 0.00 2.55
April 0.00 0.00 0.140279E+13 0.463502E+12 0.00 0.36
May 0.00 0.00 0.510744E+12 0.245192E+12 0.00 0.01
June 0.00 0.00 0.843532E+12 0.338889E+12 0.00 0.00
July 0.00 0.00 0.121268E+13 0.435753E+12 0.00 0.00
August 0.00 0.00 0.148977E+13 0.487506E+12 0.00 0.00
September 0.00 0.00 0.498175E+12 0.225692E+12 0.00 0.00
October 0.00 0.00 0.798965E+12 0.295596E+12 0.00 0.50
November 0.00 0.00 0.104668E+13 0.336859E+12 0.00 5.11
December 0.00 0.00 0.136864E+13 0.401184E+12 0.00 12.88
             
Annual Sum or Average 0.00 0.00 0.113606E+14 0.402599E+13 0.00 30.74
Minimum of Months 0.00 0.00 0.424817E+12 0.196128E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.148977E+13 0.487506E+12 0.00 12.88



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.625706E+10 0.274193E+10 0.00 0.00
February 0.00 0.00 0.120915E+11 0.383159E+10 0.00 0.00
March 0.00 0.00 0.210121E+11 0.627470E+10 0.00 0.00
April 0.00 0.00 0.283383E+11 0.883603E+10 0.00 0.00
May 0.00 0.00 0.100204E+11 0.428456E+10 0.00 0.00
June 0.00 0.00 0.171374E+11 0.623811E+10 0.00 0.00
July 0.00 0.00 0.249184E+11 0.820256E+10 0.00 0.00
August 0.00 0.00 0.308226E+11 0.948291E+10 0.00 0.00
September 0.00 0.00 0.981881E+10 0.390943E+10 0.00 0.00
October 0.00 0.00 0.154166E+11 0.518047E+10 0.00 0.00
November 0.00 0.00 0.198439E+11 0.570488E+10 0.00 0.00
December 0.00 0.00 0.255358E+11 0.647240E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.221213E+12 0.711596E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.625706E+10 0.274193E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.308226E+11 0.948291E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.476201E+11 0.237980E+11 0.00 0.00
February 0.00 0.00 0.108450E+12 0.352378E+11 0.00 0.00
March 0.00 0.00 0.198742E+12 0.595105E+11 0.00 0.00
April 0.00 0.00 0.268866E+12 0.839679E+11 0.00 0.00
May 0.00 0.00 0.944588E+11 0.405377E+11 0.00 0.00
June 0.00 0.00 0.163199E+12 0.593804E+11 0.00 0.00
July 0.00 0.00 0.237437E+12 0.780993E+11 0.00 0.00
August 0.00 0.00 0.292797E+12 0.902886E+11 0.00 0.00
September 0.00 0.00 0.923121E+11 0.369140E+11 0.00 0.00
October 0.00 0.00 0.145393E+12 0.490289E+11 0.00 0.00
November 0.00 0.00 0.184899E+12 0.535781E+11 0.00 0.00
December 0.00 0.00 0.233971E+12 0.600834E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.206815E+13 0.670425E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.476201E+11 0.237980E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.292797E+12 0.902886E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.289094E+10 0.201847E+10 0.00 0.00
February 0.00 0.00 0.999620E+10 0.338418E+10 0.00 0.00
March 0.00 0.00 0.197264E+11 0.596268E+10 0.00 0.00
April 0.00 0.00 0.272103E+11 0.853671E+10 0.00 0.00
May 0.00 0.00 0.982945E+10 0.418209E+10 0.00 0.00
June 0.00 0.00 0.167008E+11 0.607444E+10 0.00 0.00
July 0.00 0.00 0.241189E+11 0.795190E+10 0.00 0.00
August 0.00 0.00 0.298572E+11 0.924257E+10 0.00 0.00
September 0.00 0.00 0.938625E+10 0.375090E+10 0.00 0.00
October 0.00 0.00 0.144870E+11 0.492438E+10 0.00 0.00
November 0.00 0.00 0.179111E+11 0.528427E+10 0.00 0.00
December 0.00 0.00 0.219500E+11 0.579399E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.204065E+12 0.671066E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.289094E+10 0.201847E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.298572E+11 0.924257E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.537995E+10 0.453706E+11 0.163125E+09 0.00 0.00 0.00 0.00 0.00
February 0.646967E+10 0.643314E+11 807832.26 0.00 0.00 0.00 0.00 0.00
March 0.103858E+11 0.120624E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132675E+11 0.177620E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125789E+11 0.217423E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133987E+11 0.256762E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137139E+11 0.297209E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.168514E+11 0.318655E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.102823E+11 0.221857E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.988408E+10 0.148554E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.858474E+10 0.990074E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.769572E+10 0.660829E+11 35436036.95 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.128493E+12 0.203350E+13 0.199369E+09 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.537995E+10 0.453706E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168514E+11 0.318655E+12 0.163125E+09 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.375350E+11 0.316074E+12 0.426844E+10 0.00 0.00 0.00 0.00 0.00
February 0.435581E+11 0.466977E+12 0.159464E+09 0.00 0.00 0.00 0.00 0.00
March 0.725011E+11 0.922597E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.914074E+11 0.137792E+13 0.00 0.00 0.00 0.00 0.00 0.00
May 0.106880E+12 0.199934E+13 0.00 0.00 0.00 0.00 0.00 0.00
June 0.105107E+12 0.227613E+13 0.00 0.00 0.00 0.00 0.00 0.00
July 0.954552E+11 0.250696E+13 0.00 0.00 0.00 0.00 0.00 0.00
August 0.987994E+11 0.247813E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.830838E+11 0.192020E+13 7053.43 0.00 0.00 0.00 0.00 0.00
October 0.724875E+11 0.121278E+13 0.00 0.00 0.00 0.00 0.00 0.00
November 0.545110E+11 0.725332E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.411517E+11 0.384513E+12 0.856340E+09 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.902478E+12 0.165870E+14 0.528425E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.375350E+11 0.316074E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106880E+12 0.250696E+13 0.426844E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.287959E+10 0.232183E+11 0.460983E+10 0.00 0.00 0.00 0.00 0.00
February 0.347957E+10 0.412320E+11 0.625311E+09 0.00 0.00 0.00 0.00 0.00
March 0.680978E+10 0.949783E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.101960E+11 0.156239E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.126904E+11 0.229640E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.126853E+11 0.258883E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.108561E+11 0.276720E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.107163E+11 0.269569E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.872038E+10 0.207122E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.721443E+10 0.125099E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.475144E+10 0.673464E+11 30223131.05 0.00 0.00 0.00 0.00 0.00
December 0.302798E+10 0.288834E+11 0.150500E+10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.940273E+11 0.177893E+13 0.677037E+10 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.287959E+10 0.232183E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.126904E+11 0.276720E+12 0.460983E+10 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.153726E+11 0.508292E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136259E+11 0.523339E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.154623E+11 0.727924E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144630E+11 0.849268E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.154308E+11 0.109000E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155245E+11 0.128552E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.160111E+11 0.150085E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.172150E+11 0.168700E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.160500E+11 0.132492E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.165709E+11 0.951481E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.159158E+11 0.728296E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.157564E+11 0.582386E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.187398E+12 0.117593E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136259E+11 0.508292E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.172150E+11 0.168700E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.967421E+11 0.337411E+12 0.00 0.00 0.00 0.119267E+11 0.00 0.00
February 0.873799E+11 0.532790E+12 0.00 0.00 0.00 0.130601E+11 0.00 0.00
March 0.967421E+11 0.835439E+12 0.00 0.00 0.00 0.681737E+10 0.00 0.00
April 0.936213E+11 0.103387E+13 0.00 0.00 0.00 0.958331E+09 0.00 0.00
May 0.967421E+11 0.362309E+12 0.00 0.00 0.00 15004485.30 0.00 0.00
June 0.936213E+11 0.598264E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.967421E+11 0.873669E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.967421E+11 0.109901E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.936213E+11 0.366104E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.967421E+11 0.601447E+12 0.00 0.00 0.00 0.132983E+10 0.00 0.00
November 0.936213E+11 0.817191E+12 0.00 0.00 0.00 0.136855E+11 0.00 0.00
December 0.967421E+11 0.109883E+13 0.00 0.00 0.00 0.344797E+11 0.00 0.00
                 
Annual Sum or Average 0.113906E+13 0.855633E+13 0.00 0.00 0.00 0.822725E+11 0.00 0.00
Minimum of Months 0.873799E+11 0.337411E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.967421E+11 0.109901E+13 0.00 0.00 0.00 0.344797E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.144892E+10 0.496405E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130870E+10 0.956863E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144892E+10 0.161863E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.140218E+10 0.209044E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144892E+10 0.718480E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.140218E+10 0.123015E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144892E+10 0.181648E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144892E+10 0.227886E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.140218E+10 0.731155E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144892E+10 0.116850E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.140218E+10 0.155412E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144892E+10 0.205124E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.170598E+11 0.167113E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130870E+10 0.496405E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144892E+10 0.227886E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.138023E+11 0.376245E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124666E+11 0.856789E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138023E+11 0.153034E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133570E+11 0.198255E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138023E+11 0.677233E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133570E+11 0.117176E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138023E+11 0.173140E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138023E+11 0.216311E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133570E+11 0.687551E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138023E+11 0.110166E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133570E+11 0.144678E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138023E+11 0.187690E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.162511E+12 0.156023E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124666E+11 0.376245E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138023E+11 0.216311E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.138998E+10 0.226246E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125547E+10 0.786748E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138998E+10 0.151537E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134514E+10 0.200188E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138998E+10 0.703734E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134514E+10 0.119715E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138998E+10 0.175570E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138998E+10 0.220047E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134514E+10 0.698050E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138998E+10 0.109526E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134514E+10 0.139720E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138998E+10 0.175460E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163659E+11 0.153324E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125547E+10 0.226246E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138998E+10 0.220047E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.537995E+10 0.163125E+09 0.453706E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.646967E+10 807832.26 0.643314E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.103858E+11 0.00 0.120624E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132675E+11 0.00 0.177620E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125789E+11 0.00 0.217423E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133987E+11 0.00 0.256762E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137139E+11 0.00 0.297209E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.168514E+11 0.00 0.318655E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.102823E+11 0.00 0.221857E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.988408E+10 0.00 0.148554E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.858474E+10 0.00 0.990074E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.769572E+10 35436036.95 0.660829E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.128493E+12 0.199369E+09 0.203350E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.537995E+10 0.00 0.453706E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.168514E+11 0.163125E+09 0.318655E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.375350E+11 0.426844E+10 0.316074E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.435581E+11 0.159464E+09 0.466977E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.725011E+11 0.00 0.922597E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.914074E+11 0.00 0.137792E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.106880E+12 0.00 0.199934E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.105107E+12 0.00 0.227613E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.954552E+11 0.00 0.250696E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.987994E+11 0.00 0.247813E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.830838E+11 7053.43 0.192020E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.724875E+11 0.00 0.121278E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.545110E+11 0.00 0.725332E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.411517E+11 0.856340E+09 0.384513E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.902478E+12 0.528425E+10 0.165870E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.375350E+11 0.00 0.316074E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106880E+12 0.426844E+10 0.250696E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.287959E+10 0.460983E+10 0.232183E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.347957E+10 0.625311E+09 0.412320E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.680978E+10 0.00 0.949783E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.101960E+11 0.00 0.156239E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.126904E+11 0.00 0.229640E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.126853E+11 0.00 0.258883E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.108561E+11 0.00 0.276720E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.107163E+11 0.00 0.269569E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.872038E+10 0.00 0.207122E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.721443E+10 0.00 0.125099E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.475144E+10 30223131.05 0.673464E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.302798E+10 0.150500E+10 0.288834E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.940273E+11 0.677037E+10 0.177893E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.287959E+10 0.00 0.232183E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.126904E+11 0.460983E+10 0.276720E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.153726E+11 0.00 0.508292E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.136259E+11 0.00 0.523339E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.154623E+11 0.00 0.727924E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.144630E+11 0.00 0.849268E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.154308E+11 0.00 0.109000E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.155245E+11 0.00 0.128552E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.160111E+11 0.00 0.150085E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.172150E+11 0.00 0.168700E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.160500E+11 0.00 0.132492E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.165709E+11 0.00 0.951481E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.159158E+11 0.00 0.728296E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.157564E+11 0.00 0.582386E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.187398E+12 0.00 0.117593E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.136259E+11 0.00 0.508292E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.172150E+11 0.00 0.168700E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.967421E+11 0.00 0.424817E+12 0.00 0.874060E+11 0.00 0.00 0.00 0.119804E+11 0.00 0.00 0.00
February 0.873799E+11 0.00 0.674414E+12 0.00 0.141624E+12 0.00 0.00 0.00 0.131189E+11 0.00 0.00 0.00
March 0.967421E+11 0.00 0.108941E+13 0.00 0.253971E+12 0.00 0.00 0.00 0.684805E+10 0.00 0.00 0.00
April 0.936213E+11 0.00 0.140279E+13 0.00 0.368918E+12 0.00 0.00 0.00 0.962645E+09 0.00 0.00 0.00
May 0.967421E+11 0.00 0.510744E+12 0.00 0.148435E+12 0.00 0.00 0.00 15072026.57 0.00 0.00 0.00
June 0.936213E+11 0.00 0.843532E+12 0.00 0.245268E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.967421E+11 0.00 0.121268E+13 0.00 0.339011E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.967421E+11 0.00 0.148977E+13 0.00 0.390764E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.936213E+11 0.00 0.498175E+12 0.00 0.132071E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.967421E+11 0.00 0.798965E+12 0.00 0.197519E+12 0.00 0.00 0.00 0.133582E+10 0.00 0.00 0.00
November 0.936213E+11 0.00 0.104668E+13 0.00 0.229491E+12 0.00 0.00 0.00 0.137471E+11 0.00 0.00 0.00
December 0.967421E+11 0.00 0.136864E+13 0.00 0.269807E+12 0.00 0.00 0.00 0.346349E+11 0.00 0.00 0.00
                         
Annual Sum or Average 0.113906E+13 0.00 0.113606E+14 0.00 0.280428E+13 0.00 0.00 0.00 0.826428E+11 0.00 0.00 0.00
Minimum of Months 0.873799E+11 0.00 0.424817E+12 0.00 0.874060E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.967421E+11 0.00 0.148977E+13 0.00 0.390764E+12 0.00 0.00 0.00 0.346349E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.144892E+10 0.00 0.625706E+10 0.00 0.129302E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.130870E+10 0.00 0.120915E+11 0.00 0.252289E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.144892E+10 0.00 0.210121E+11 0.00 0.482578E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.140218E+10 0.00 0.283383E+11 0.00 0.743386E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.144892E+10 0.00 0.100204E+11 0.00 0.283565E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.140218E+10 0.00 0.171374E+11 0.00 0.483594E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.144892E+10 0.00 0.249184E+11 0.00 0.675365E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.144892E+10 0.00 0.308226E+11 0.00 0.803399E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.140218E+10 0.00 0.981881E+10 0.00 0.250726E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.144892E+10 0.00 0.154166E+11 0.00 0.373155E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.140218E+10 0.00 0.198439E+11 0.00 0.430270E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.144892E+10 0.00 0.255358E+11 0.00 0.502349E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.170598E+11 0.00 0.221213E+12 0.00 0.540998E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.130870E+10 0.00 0.625706E+10 0.00 0.129302E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.144892E+10 0.00 0.308226E+11 0.00 0.803399E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.138023E+11 0.00 0.476201E+11 0.00 0.999568E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124666E+11 0.00 0.108450E+12 0.00 0.227712E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138023E+11 0.00 0.198742E+12 0.00 0.457082E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133570E+11 0.00 0.268866E+12 0.00 0.706109E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138023E+11 0.00 0.944588E+11 0.00 0.267355E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133570E+11 0.00 0.163199E+12 0.00 0.460233E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138023E+11 0.00 0.237437E+12 0.00 0.642970E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138023E+11 0.00 0.292797E+12 0.00 0.764863E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133570E+11 0.00 0.923121E+11 0.00 0.235570E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138023E+11 0.00 0.145393E+12 0.00 0.352266E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133570E+11 0.00 0.184899E+12 0.00 0.402210E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138023E+11 0.00 0.233971E+12 0.00 0.462811E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.162511E+12 0.00 0.206815E+13 0.00 0.507914E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124666E+11 0.00 0.476201E+11 0.00 0.999568E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138023E+11 0.00 0.292797E+12 0.00 0.764863E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.138998E+10 0.00 0.289094E+10 0.00 0.628486E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.125547E+10 0.00 0.999620E+10 0.00 0.212871E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138998E+10 0.00 0.197264E+11 0.00 0.457270E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.134514E+10 0.00 0.272103E+11 0.00 0.719157E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.138998E+10 0.00 0.982945E+10 0.00 0.279211E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.134514E+10 0.00 0.167008E+11 0.00 0.472930E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138998E+10 0.00 0.241189E+11 0.00 0.656192E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.138998E+10 0.00 0.298572E+11 0.00 0.785259E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.134514E+10 0.00 0.938625E+10 0.00 0.240576E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.138998E+10 0.00 0.144870E+11 0.00 0.353440E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.134514E+10 0.00 0.179111E+11 0.00 0.393913E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.138998E+10 0.00 0.219500E+11 0.00 0.440401E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.163659E+11 0.00 0.204065E+12 0.00 0.507407E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.125547E+10 0.00 0.289094E+10 0.00 0.628486E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.138998E+10 0.00 0.298572E+11 0.00 0.785259E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.254336E+10 0.00 0.00 0.113700E+09 0.00 0.00 0.257122E+11 0.00 0.40
February 0.992914E+09 0.00 0.00 0.101515E+09 0.00 0.00 0.165293E+11 0.00 0.39
March 0.342322E+09 0.152966E+10 0.00 92139731.23 27747493.12 0.00 0.846132E+10 0.00 0.40
April 22318292.49 0.106819E+11 0.00 21368182.66 0.281402E+09 0.00 0.548877E+09 0.00 0.39
May 5171939.13 0.297736E+11 0.00 3174802.06 0.474510E+09 0.00 48846417.74 0.00 0.41
June 0.00 0.462440E+11 0.00 477049.84 0.780366E+09 0.00 879911.21 0.00 0.42
July 0.00 0.634032E+11 0.00 0.00 0.155379E+10 0.00 0.00 0.00 0.42
August 0.00 0.709591E+11 0.00 0.00 0.114476E+10 0.00 0.00 0.00 0.45
September 0.00 0.465107E+11 0.00 0.00 0.982365E+09 0.00 0.00 0.00 0.44
October 0.174253E+09 0.881618E+10 0.00 57322702.82 0.127534E+09 0.00 0.292506E+10 0.00 0.43
November 0.103723E+10 0.242869E+09 0.00 0.129809E+09 23533402.98 0.00 0.131761E+11 0.00 0.43
December 0.205880E+10 0.00 0.00 0.124693E+09 0.00 0.00 0.239784E+11 0.00 0.41
                   
Annual Sum or Average 0.717637E+10 0.278161E+12 0.00 0.644200E+09 0.539601E+10 0.00 0.913809E+11 0.00 0.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.39
Maximum of Months 0.254336E+10 0.709591E+11 0.00 0.129809E+09 0.155379E+10 0.00 0.257122E+11 0.00 0.45



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.181627E+10 0.00 0.00 80627018.17 0.00 0.00 0.251113E+11 0.00 0.36
February 0.193492E+10 0.00 0.00 80556225.63 1269930.79 0.00 0.161996E+11 0.00 0.37
March 0.264154E+10 0.115678E+10 0.00 79603992.65 0.389747E+09 0.00 0.818757E+10 0.00 0.42
April 0.697253E+09 0.702076E+10 0.00 22976466.19 0.398967E+10 0.00 0.762090E+09 0.00 0.46
May 15245814.15 0.233713E+11 0.00 575614.89 0.109513E+11 0.00 9032324.21 0.00 0.43
June 0.00 0.354032E+11 0.00 0.00 0.197564E+11 0.00 0.00 0.00 0.44
July 0.00 0.453139E+11 0.00 0.00 0.332166E+11 0.00 0.00 0.00 0.46
August 0.00 0.518099E+11 0.00 0.00 0.298537E+11 0.00 0.00 0.00 0.47
September 0.00 0.353174E+11 0.00 0.00 0.174936E+11 0.00 0.00 0.00 0.41
October 0.920007E+09 0.756738E+10 0.00 29481093.71 0.199217E+10 0.00 0.227417E+10 0.00 0.41
November 0.282989E+10 0.179127E+09 0.00 91429624.69 90469793.95 0.00 0.118673E+11 0.00 0.39
December 0.326570E+10 0.00 0.00 94596271.42 0.00 0.00 0.232962E+11 0.00 0.40
                   
Annual Sum or Average 0.141208E+11 0.207140E+12 0.00 0.479846E+09 0.117735E+12 0.00 0.877073E+11 0.00 0.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.326570E+10 0.518099E+11 0.00 94596271.42 0.332166E+11 0.00 0.251113E+11 0.00 0.47



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.371798E+11 0.00 0.00 0.479933E+09 0.00 0.00 0.192150E+12 0.00 0.34
February 0.140003E+11 0.00 0.00 0.556050E+09 61395997.46 0.00 0.140244E+12 0.00 0.35
March 0.103017E+11 0.116670E+11 0.00 0.661797E+09 0.344429E+10 0.00 0.776552E+11 0.00 0.36
April 0.245065E+10 0.675510E+11 0.00 0.166465E+09 0.350433E+11 0.00 0.611550E+10 0.00 0.38
May 0.109484E+09 0.229432E+12 0.00 3023522.05 0.979931E+11 0.00 82578280.25 0.00 0.41
June 0.00 0.344950E+12 0.00 0.00 0.159725E+12 0.00 0.00 0.00 0.41
July 0.00 0.434220E+12 0.00 0.00 0.249861E+12 0.00 0.00 0.00 0.40
August 0.00 0.493094E+12 0.00 0.00 0.183353E+12 0.00 0.00 0.00 0.39
September 0.00 0.347307E+12 0.00 0.00 0.110338E+12 0.00 0.00 0.00 0.36
October 0.516759E+10 0.746917E+11 0.00 0.241343E+09 0.136734E+11 0.00 0.203205E+11 0.00 0.35
November 0.143580E+11 0.184454E+10 0.00 0.667282E+09 0.111708E+10 0.00 0.101324E+12 0.00 0.35
December 0.237548E+11 0.00 0.00 0.527245E+09 10469191.04 0.00 0.187326E+12 0.00 0.35
                   
Annual Sum or Average 0.107322E+12 0.200476E+13 0.00 0.330314E+10 0.854620E+12 0.00 0.725219E+12 0.00 0.37
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.371798E+11 0.493094E+12 0.00 0.667282E+09 0.249861E+12 0.00 0.192150E+12 0.00 0.41



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.126112E+11 0.00 0.00 13477625.28 0.00 0.263789E+09 0.541169E+10 0.00 0.30
February 0.535084E+10 0.00 0.00 31343975.79 909367.88 0.00 0.724985E+10 0.00 0.31
March 0.125555E+10 0.828932E+09 0.00 56512772.94 0.238064E+09 0.00 0.653755E+10 0.00 0.34
April 0.221615E+09 0.587080E+10 0.00 21410369.15 0.313042E+10 0.00 0.701964E+09 0.00 0.38
May 10302283.83 0.220988E+11 0.00 269459.82 0.936761E+10 0.00 6854031.95 0.00 0.42
June 0.00 0.338251E+11 0.00 0.00 0.157946E+11 0.00 0.00 0.00 0.41
July 0.00 0.429470E+11 0.00 0.00 0.253007E+11 0.00 0.00 0.00 0.41
August 0.00 0.486186E+11 0.00 0.00 0.191134E+11 0.00 0.00 0.00 0.40
September 0.00 0.336002E+11 0.00 0.00 0.124890E+11 0.00 0.00 0.00 0.37
October 0.493387E+09 0.652683E+10 0.00 21177554.95 0.123437E+10 0.00 0.156997E+10 0.00 0.34
November 0.318368E+10 46712861.34 0.00 46870062.41 80064191.60 0.00 0.624812E+10 0.00 0.31
December 0.990485E+10 0.00 0.00 20270042.92 159115.22 0.00 0.648424E+10 0.00 0.30
                   
Annual Sum or Average 0.330314E+11 0.194363E+12 0.00 0.211332E+09 0.867494E+11 0.263789E+09 0.342102E+11 0.00 0.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.126112E+11 0.486186E+11 0.00 56512772.94 0.253007E+11 0.263789E+09 0.724985E+10 0.00 0.42



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.164376E+10 0.00 0.00 3364269.78 0.00 0.00 0.902376E+09 0.00 0.28
February 0.837591E+09 0.00 0.00 5848885.01 160009.05 0.00 0.994037E+09 0.00 0.32
March 0.419932E+09 0.207051E+09 0.00 8999503.39 48950918.76 0.00 0.857221E+09 0.00 0.44
April 91089633.41 0.154502E+10 0.00 3556546.01 0.425417E+09 0.00 0.103374E+09 0.00 0.58
May 1300643.41 0.576168E+10 0.00 213579.16 0.104987E+10 0.00 2761838.72 0.00 0.66
June 0.00 0.889836E+10 0.00 0.00 0.194909E+10 0.00 0.00 0.00 0.69
July 0.00 0.113680E+11 0.00 0.00 0.312958E+10 0.00 0.00 0.00 0.66
August 0.00 0.112637E+11 0.00 0.00 0.295811E+10 0.00 0.00 0.00 0.64
September 0.00 0.687572E+10 0.00 0.00 0.198651E+10 0.00 0.00 0.00 0.54
October 0.147949E+09 0.128025E+10 0.00 3085415.48 0.243289E+09 0.00 0.211949E+09 0.00 0.46
November 0.600247E+09 26855402.62 0.00 8174632.00 11399035.53 0.00 0.916464E+09 0.00 0.35
December 0.135640E+10 0.00 0.00 5329741.87 0.00 0.00 0.111331E+10 0.00 0.30
                   
Annual Sum or Average 0.509827E+10 0.472266E+11 0.00 38572572.69 0.118024E+11 0.00 0.510149E+10 0.00 0.49
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.164376E+10 0.113680E+11 0.00 8999503.39 0.312958E+10 0.00 0.111331E+10 0.00 0.69



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.107847E+10 0.00 0.00 3481870.33 0.00 0.00 0.100881E+10 0.00 0.35
February 0.585072E+09 0.00 0.00 5245147.83 120557.79 0.00 0.935126E+09 0.00 0.40
March 0.346703E+09 0.151079E+09 0.00 7528159.78 35697052.54 0.00 0.691927E+09 0.00 0.54
April 64939513.66 0.118710E+10 0.00 3070100.25 0.322547E+09 0.00 91593379.86 0.00 0.71
May 1115852.89 0.458939E+10 0.00 130118.23 0.748615E+09 0.00 1754088.46 0.00 0.81
June 0.00 0.618792E+10 0.00 0.00 0.155117E+10 0.00 0.00 0.00 0.77
July 0.00 0.725530E+10 0.00 0.00 0.260783E+10 0.00 0.00 0.00 0.70
August 0.00 0.653961E+10 0.00 0.00 0.258738E+10 0.00 0.00 0.00 0.64
September 0.00 0.491657E+10 0.00 0.00 0.150737E+10 0.00 0.00 0.00 0.62
October 0.111871E+09 0.958625E+09 0.00 2720908.85 0.171228E+09 0.00 0.181307E+09 0.00 0.55
November 0.522907E+09 18825614.48 0.00 6358287.64 8588529.70 0.00 0.685932E+09 0.00 0.42
December 0.110619E+10 0.00 0.00 3891537.61 0.00 0.00 0.784608E+09 0.00 0.35
                   
Annual Sum or Average 0.381726E+10 0.318044E+11 0.00 32426130.53 0.954055E+10 0.00 0.438105E+10 0.00 0.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 0.110619E+10 0.725530E+10 0.00 7528159.78 0.260783E+10 0.00 0.100881E+10 0.00 0.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.102379E+10 0.00 0.00 10937428.52 0.00 0.00 0.287742E+10 0.00 0.47
February 0.643379E+09 184296.83 0.00 13881165.01 29734.74 0.00 0.201047E+10 0.00 0.50
March 0.364091E+09 0.354053E+09 0.00 14450346.55 24870329.33 0.00 0.129602E+10 0.00 0.60
April 84712245.22 0.201712E+10 0.00 4615877.26 0.347383E+09 0.00 0.126747E+09 0.00 0.68
May 1258189.28 0.613121E+10 0.00 228197.16 0.971528E+09 0.00 2849975.11 0.00 0.68
June 0.00 0.889258E+10 0.00 0.00 0.192764E+10 0.00 0.00 0.00 0.68
July 0.00 0.114586E+11 0.00 0.00 0.310125E+10 0.00 0.00 0.00 0.67
August 0.00 0.117889E+11 0.00 0.00 0.289436E+10 0.00 0.00 0.00 0.66
September 0.00 0.860055E+10 0.00 0.00 0.169729E+10 0.00 0.00 0.00 0.64
October 0.117647E+09 0.216078E+10 0.00 6695841.17 0.145805E+09 0.00 0.339776E+09 0.00 0.68
November 0.450294E+09 68999458.88 0.00 21464189.62 6155373.62 0.00 0.189199E+10 0.00 0.62
December 0.950508E+09 0.00 0.00 14711094.98 0.00 0.00 0.276228E+10 0.00 0.50
                   
Annual Sum or Average 0.363568E+10 0.514730E+11 0.00 86984140.27 0.111163E+11 0.00 0.113075E+11 0.00 0.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.102379E+10 0.117889E+11 0.00 21464189.62 0.310125E+10 0.00 0.287742E+10 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.950174E+09 0.00 0.00 5855404.15 0.00 0.00 0.181618E+10 0.00 0.48
February 0.357717E+09 209731.30 0.00 10116592.93 20066.38 0.00 0.178609E+10 0.00 0.60
March 0.204468E+09 0.323506E+09 0.00 15052978.60 15622349.60 0.00 0.143955E+10 0.00 0.88
April 14744598.91 0.264871E+10 0.00 7292567.42 46830892.60 0.00 0.232725E+09 0.00 1.22
May 955848.56 0.621215E+10 0.00 271798.92 0.647733E+09 0.00 3119990.07 0.00 1.03
June 0.00 0.101945E+11 0.00 0.00 0.101192E+10 0.00 0.00 0.00 1.11
July 0.00 0.139211E+11 0.00 0.00 0.130042E+10 0.00 0.00 0.00 1.08
August 0.00 0.168723E+11 0.00 0.00 0.306943E+09 0.00 0.00 0.00 1.20
September 0.00 0.738073E+10 0.00 0.00 0.141685E+10 0.00 0.00 0.00 0.84
October 81554924.28 0.157905E+10 0.00 4964363.50 0.131113E+09 0.00 0.330340E+09 0.00 0.81
November 0.281537E+09 48989549.84 0.00 14596395.74 4112351.29 0.00 0.168415E+10 0.00 0.72
December 0.363089E+09 0.00 0.00 13445331.56 0.00 0.00 0.310610E+10 0.00 0.68
                   
Annual Sum or Average 0.225424E+10 0.591813E+11 0.00 71595432.83 0.488157E+10 0.00 0.103982E+11 0.00 0.89
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
Maximum of Months 0.950174E+09 0.168723E+11 0.00 15052978.60 0.141685E+10 0.00 0.310610E+10 0.00 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.206306E+11 0.00 0.00 6677382.98 0.00 0.291003E+09 0.265946E+10 0.00 0.27
February 0.108097E+11 0.00 0.00 27872753.38 7698584.10 0.00 0.504214E+10 0.00 0.29
March 0.365583E+10 0.214086E+10 0.00 62268435.42 0.432283E+09 0.00 0.638309E+10 0.00 0.37
April 0.310605E+09 0.160216E+11 0.00 25308259.16 0.398950E+10 0.00 0.843259E+09 0.00 0.54
May 8565343.50 0.627631E+11 0.00 1626772.16 0.840655E+10 0.00 28381591.01 0.00 0.68
June 0.00 0.964665E+11 0.00 0.00 0.143988E+11 0.00 0.00 0.00 0.71
July 0.00 0.121168E+12 0.00 0.00 0.209328E+11 0.00 0.00 0.00 0.66
August 0.00 0.117743E+12 0.00 0.00 0.173615E+11 0.00 0.00 0.00 0.61
September 0.00 0.712336E+11 0.00 0.00 0.116347E+11 0.00 0.00 0.00 0.51
October 0.135966E+10 0.128493E+11 0.00 20840755.99 0.167136E+10 0.00 0.144817E+10 0.00 0.40
November 0.762331E+10 0.245614E+09 0.00 43306555.62 0.141293E+09 0.00 0.451178E+10 0.00 0.31
December 0.181422E+11 0.00 0.00 12548632.90 1312755.73 5330559.89 0.328280E+10 0.00 0.28
                   
Annual Sum or Average 0.625404E+11 0.500632E+12 0.00 0.200450E+09 0.789778E+11 0.296333E+09 0.241991E+11 0.00 0.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.206306E+11 0.121168E+12 0.00 62268435.42 0.209328E+11 0.291003E+09 0.638309E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.134053E+11 0.00 0.00 15401855.26 0.00 30639242.32 0.581039E+10 0.00 0.35
February 0.680206E+10 0.00 0.00 37695339.44 6126994.91 0.00 0.763558E+10 0.00 0.41
March 0.225499E+10 0.184235E+10 0.00 69777525.40 0.307973E+09 0.00 0.747320E+10 0.00 0.54
April 0.182693E+09 0.153731E+11 0.00 29063321.89 0.249721E+10 0.00 0.988056E+09 0.00 0.77
May 5768815.36 0.534363E+11 0.00 1151191.51 0.577564E+10 0.00 21657727.85 0.00 0.90
June 0.00 0.739138E+11 0.00 0.00 0.109328E+11 0.00 0.00 0.00 0.85
July 0.00 0.889856E+11 0.00 0.00 0.161958E+11 0.00 0.00 0.00 0.75
August 0.00 0.847564E+11 0.00 0.00 0.133455E+11 0.00 0.00 0.00 0.69
September 0.00 0.556301E+11 0.00 0.00 0.846175E+10 0.00 0.00 0.00 0.62
October 0.873071E+09 0.109237E+11 0.00 25116561.27 0.107962E+10 0.00 0.180748E+10 0.00 0.55
November 0.490935E+10 0.211934E+09 0.00 50004680.00 0.111479E+09 0.00 0.624211E+10 0.00 0.43
December 0.117494E+11 0.00 0.00 20991828.76 1044769.74 0.00 0.590263E+10 0.00 0.36
                   
Annual Sum or Average 0.401826E+11 0.385073E+12 0.00 0.249202E+09 0.587148E+11 30639242.32 0.358811E+11 0.00 0.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.35
Maximum of Months 0.134053E+11 0.889856E+11 0.00 69777525.40 0.161958E+11 30639242.32 0.763558E+10 0.00 0.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103993E+11 0.00 0.00 0.100790E+09 0.00 0.00 0.299594E+11 0.00 0.53
February 0.606225E+10 10743700.23 0.00 0.123625E+09 910544.31 0.00 0.200349E+11 0.00 0.54
March 0.236366E+10 0.409666E+10 0.00 0.127070E+09 0.133652E+09 0.00 0.126607E+11 0.00 0.60
April 0.268988E+09 0.221791E+11 0.00 35295791.81 0.297269E+10 0.00 0.109857E+10 0.00 0.67
May 8462833.35 0.663510E+11 0.00 1788380.96 0.783001E+10 0.00 29110166.35 0.00 0.71
June 0.00 0.953543E+11 0.00 0.00 0.147352E+11 0.00 0.00 0.00 0.70
July 0.00 0.122381E+12 0.00 0.00 0.206970E+11 0.00 0.00 0.00 0.66
August 0.00 0.126847E+12 0.00 0.00 0.156877E+11 0.00 0.00 0.00 0.64
September 0.00 0.922818E+11 0.00 0.00 0.866419E+10 0.00 0.00 0.00 0.63
October 0.511533E+09 0.241580E+11 0.00 55218960.03 0.633694E+09 0.00 0.362298E+10 0.00 0.70
November 0.283571E+10 0.911685E+09 0.00 0.197008E+09 51240223.88 0.00 0.197624E+11 0.00 0.68
December 0.855549E+10 1271717.44 0.00 0.121118E+09 219638.67 0.00 0.290130E+11 0.00 0.56
                   
Annual Sum or Average 0.310054E+11 0.554572E+12 0.00 0.761914E+09 0.714064E+11 0.00 0.116181E+12 0.00 0.64
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.53
Maximum of Months 0.103993E+11 0.126847E+12 0.00 0.197008E+09 0.206970E+11 0.00 0.299594E+11 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.157805E+11 0.00 0.00 19256465.45 0.00 0.00 0.567940E+10 0.00 0.40
February 0.766417E+10 4404850.53 0.00 38258717.23 2953658.63 0.00 0.687801E+10 0.00 0.44
March 0.220725E+10 0.261694E+10 0.00 71826149.77 0.190974E+09 0.00 0.747002E+10 0.00 0.59
April 0.196533E+09 0.190479E+11 0.00 26836867.46 0.185901E+10 0.00 0.852026E+09 0.00 0.85
May 5171245.83 0.601119E+11 0.00 1686767.37 0.456985E+10 0.00 25478285.51 0.00 0.96
June 0.00 0.878944E+11 0.00 0.00 0.845737E+10 0.00 0.00 0.00 0.96
July 0.00 0.102207E+12 0.00 0.00 0.132335E+11 0.00 0.00 0.00 0.83
August 0.00 0.101264E+12 0.00 0.00 0.106081E+11 0.00 0.00 0.00 0.78
September 0.00 0.636458E+11 0.00 0.00 0.747840E+10 0.00 0.00 0.00 0.68
October 0.682292E+09 0.128084E+11 0.00 22468423.76 0.976961E+09 0.00 0.177939E+10 0.00 0.59
November 0.466406E+10 0.366907E+09 0.00 55607197.49 94479411.46 0.00 0.636708E+10 0.00 0.47
December 0.131550E+11 0.00 0.00 25258709.31 1119038.87 0.00 0.646627E+10 0.00 0.41
                   
Annual Sum or Average 0.443550E+11 0.449968E+12 0.00 0.261199E+09 0.474727E+11 0.00 0.355177E+11 0.00 0.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.40
Maximum of Months 0.157805E+11 0.102207E+12 0.00 71826149.77 0.132335E+11 0.00 0.747002E+10 0.00 0.96



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.176513E+10 0.00 0.00 122318.77 0.00 0.608606E+09 44635658.41 0.00 0.31
February 0.112965E+10 0.00 0.00 1703876.16 123279.45 0.122688E+09 0.304670E+09 0.00 0.30
March 0.377663E+09 0.149077E+09 0.00 5853352.91 31626317.66 0.00 0.598698E+09 0.00 0.37
April 33327033.54 0.137398E+10 0.00 3450449.82 0.353292E+09 0.00 0.107762E+09 0.00 0.54
May 755346.48 0.587905E+10 0.00 149155.55 0.756689E+09 0.00 2638389.54 0.00 0.68
June 0.00 0.923120E+10 0.00 0.00 0.132900E+10 0.00 0.00 0.00 0.70
July 0.00 0.119894E+11 0.00 0.00 0.194849E+10 0.00 0.00 0.00 0.66
August 0.00 0.115674E+11 0.00 0.00 0.175792E+10 0.00 0.00 0.00 0.62
September 0.00 0.693361E+10 0.00 0.00 0.131927E+10 0.00 0.00 0.00 0.52
October 0.150932E+09 0.108994E+10 0.00 2166753.87 0.178015E+09 0.00 0.109736E+09 0.00 0.40
November 0.808961E+09 6670726.14 0.00 3586606.28 10380601.08 279085.20 0.338805E+09 0.00 0.31
December 0.164980E+10 0.00 0.00 208781.96 21570.63 0.354948E+09 89368981.46 0.00 0.30
                   
Annual Sum or Average 0.591622E+10 0.482203E+11 0.00 17241295.31 0.768483E+10 0.108652E+10 0.159631E+10 0.00 0.48
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.30
Maximum of Months 0.176513E+10 0.119894E+11 0.00 5853352.91 0.194849E+10 0.608606E+09 0.598698E+09 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.129925E+10 0.00 0.00 484964.63 0.00 0.310987E+09 0.230640E+09 0.00 0.37
February 0.655858E+09 0.00 0.00 2922073.85 93817.00 49030531.19 0.615568E+09 0.00 0.40
March 0.191612E+09 0.131532E+09 0.00 7148972.37 19323570.04 0.00 0.758342E+09 0.00 0.54
April 16249880.53 0.132894E+10 0.00 3938968.21 0.217600E+09 0.00 0.123924E+09 0.00 0.77
May 589140.71 0.496817E+10 0.00 114214.58 0.513284E+09 0.00 1908422.62 0.00 0.89
June 0.00 0.707521E+10 0.00 0.00 0.974690E+09 0.00 0.00 0.00 0.83
July 0.00 0.882689E+10 0.00 0.00 0.144463E+10 0.00 0.00 0.00 0.76
August 0.00 0.843740E+10 0.00 0.00 0.128853E+10 0.00 0.00 0.00 0.70
September 0.00 0.550552E+10 0.00 0.00 0.918189E+09 0.00 0.00 0.00 0.64
October 85843134.93 0.956240E+09 0.00 2822338.09 0.107121E+09 0.00 0.163247E+09 0.00 0.55
November 0.450620E+09 6886652.05 0.00 4740938.04 7617120.16 0.00 0.559868E+09 0.00 0.42
December 0.116902E+10 0.00 0.00 847292.56 16415.48 0.124719E+09 0.308142E+09 0.00 0.36
                   
Annual Sum or Average 0.386904E+10 0.372368E+11 0.00 23019762.33 0.549110E+10 0.484736E+09 0.276164E+10 0.00 0.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.129925E+10 0.882689E+10 0.00 7148972.37 0.144463E+10 0.310987E+09 0.758342E+09 0.00 0.89



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.110496E+10 0.00 0.00 6854850.44 0.00 0.272553E+09 0.213333E+10 0.00 0.48
February 0.685329E+09 149362.47 0.00 10303757.76 18179.04 28512688.66 0.176212E+10 0.00 0.52
March 0.223719E+09 0.270874E+09 0.00 12926694.59 12863483.38 0.00 0.128894E+10 0.00 0.58
April 27702561.82 0.185728E+10 0.00 5036651.44 0.267124E+09 0.00 0.146639E+09 0.00 0.66
May 733649.18 0.616575E+10 0.00 162018.64 0.719701E+09 0.00 2734601.24 0.00 0.71
June 0.00 0.913284E+10 0.00 0.00 0.135049E+10 0.00 0.00 0.00 0.69
July 0.00 0.120708E+11 0.00 0.00 0.194183E+10 0.00 0.00 0.00 0.67
August 0.00 0.124090E+11 0.00 0.00 0.160225E+10 0.00 0.00 0.00 0.65
September 0.00 0.886647E+10 0.00 0.00 0.101456E+10 0.00 0.00 0.00 0.63
October 61065092.67 0.199638E+10 0.00 8180029.53 63541196.72 0.00 0.343007E+09 0.00 0.69
November 0.316716E+09 33380484.69 0.00 19497478.96 5436384.21 0.00 0.191790E+10 0.00 0.66
December 0.984631E+09 19330.07 0.00 8555902.11 9873.64 72087590.79 0.221758E+10 0.00 0.50
                   
Annual Sum or Average 0.340486E+10 0.528029E+11 0.00 71517383.47 0.697782E+10 0.373153E+09 0.981226E+10 0.00 0.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
Maximum of Months 0.110496E+10 0.124090E+11 0.00 19497478.96 0.194183E+10 0.272553E+09 0.221758E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.143016E+10 0.00 0.00 1135196.25 0.00 0.317566E+09 0.382666E+09 0.00 0.43
February 0.881769E+09 26195.33 0.00 2906526.46 89612.73 32712940.69 0.528500E+09 0.00 0.45
March 0.245816E+09 0.177898E+09 0.00 7021478.95 15021485.56 0.00 0.710364E+09 0.00 0.57
April 20710544.62 0.153889E+10 0.00 3889084.81 0.185806E+09 0.00 0.108685E+09 0.00 0.83
May 555900.20 0.532205E+10 0.00 150012.58 0.505811E+09 0.00 2287211.57 0.00 0.93
June 0.00 0.807930E+10 0.00 0.00 0.874691E+09 0.00 0.00 0.00 0.93
July 0.00 0.967862E+10 0.00 0.00 0.146991E+10 0.00 0.00 0.00 0.82
August 0.00 0.954499E+10 0.00 0.00 0.128460E+10 0.00 0.00 0.00 0.78
September 0.00 0.606867E+10 0.00 0.00 0.928031E+09 0.00 0.00 0.00 0.69
October 95687524.28 0.106491E+10 0.00 2779265.01 0.108833E+09 0.00 0.134746E+09 0.00 0.59
November 0.535918E+09 12838305.88 0.00 5132698.76 7735093.57 0.00 0.538585E+09 0.00 0.47
December 0.138645E+10 0.00 0.00 1510442.89 18549.51 73740720.47 0.422417E+09 0.00 0.42
                   
Annual Sum or Average 0.459707E+10 0.414882E+11 0.00 24524705.72 0.538054E+10 0.424019E+09 0.282825E+10 0.00 0.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.143016E+10 0.967862E+10 0.00 7021478.95 0.146991E+10 0.317566E+09 0.710364E+09 0.00 0.93



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 8277676.64 0.00 0.00 0.623625E+09 0.00 0.58
February 0.00 5583522.31 0.00 17166665.48 0.00 0.00 0.308232E+09 0.00 0.59
March 0.00 0.106507E+09 0.00 18260078.41 0.00 0.00 0.107853E+09 0.00 0.59
April 0.00 0.319097E+09 0.00 8226666.84 0.00 0.00 9821507.77 0.00 0.59
May 0.00 0.839330E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.127934E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
July 0.00 0.174962E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.170409E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
September 0.00 0.124668E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.404176E+09 0.00 2014555.10 0.00 0.00 6002295.50 0.00 0.59
November 0.00 37314741.76 0.00 24870823.00 0.00 0.00 0.164301E+09 0.00 0.59
December 0.00 5444.04 0.00 44140209.25 0.00 0.00 0.503795E+09 0.00 0.58
                   
Annual Sum or Average 0.00 0.769175E+10 0.00 0.122957E+09 0.00 0.00 0.172363E+10 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.00 0.174962E+10 0.00 44140209.25 0.00 0.00 0.623625E+09 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 58477410.63 0.00 0.00 0.634441E+10 0.00 0.58
February 0.00 53515577.94 0.00 0.152550E+09 0.00 0.00 0.311977E+10 0.00 0.59
March 0.00 0.106168E+10 0.00 0.172435E+09 0.00 0.00 0.108912E+10 0.00 0.59
April 0.00 0.322798E+10 0.00 79171958.13 0.00 0.00 0.100340E+09 0.00 0.59
May 0.00 0.833106E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.127480E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.60
July 0.00 0.174559E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.172214E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.60
September 0.00 0.123252E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.401447E+10 0.00 19051042.41 0.00 0.00 63350957.73 0.00 0.59
November 0.00 0.370582E+09 0.00 0.230406E+09 0.00 0.00 0.166512E+10 0.00 0.59
December 0.00 47319.91 0.00 0.402426E+09 0.00 0.00 0.507382E+10 0.00 0.58
                   
Annual Sum or Average 0.00 0.768099E+11 0.00 0.111452E+10 0.00 0.00 0.174559E+11 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.00 0.174559E+11 0.00 0.402426E+09 0.00 0.00 0.634441E+10 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.146546E+09 0.00 0.00 2735518.43 0.00 0.00 0.498316E+09 0.00 0.58
February 0.00 6486852.39 0.00 13443359.08 0.00 0.00 0.302186E+09 0.00 0.59
March 0.00 0.115142E+09 0.00 16017010.79 0.00 0.00 0.100648E+09 0.00 0.59
April 0.00 0.343070E+09 0.00 6961564.01 0.00 0.00 8398197.94 0.00 0.59
May 0.00 0.852862E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.59
June 0.00 0.129459E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
July 0.00 0.176619E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.60
August 0.00 0.176461E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
September 0.00 0.125191E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.59
October 0.00 0.417986E+09 0.00 1636525.09 0.00 0.00 5286332.08 0.00 0.59
November 0.00 42183528.20 0.00 21151082.31 0.00 0.00 0.156119E+09 0.00 0.59
December 0.00 36936.53 0.00 37161559.10 0.00 0.00 0.494528E+09 0.00 0.58
                   
Annual Sum or Average 0.146546E+09 0.785506E+10 0.00 99106618.80 0.00 0.00 0.156548E+10 0.00 0.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.58
Maximum of Months 0.146546E+09 0.176619E+10 0.00 37161559.10 0.00 0.00 0.498316E+09 0.00 0.60



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.495043E+09 0.00 0.00 0.139978E+11 0.00 0.66
February 0.00 0.162045E+09 0.00 0.865791E+09 0.00 0.00 0.675921E+10 0.00 0.66
March 0.00 0.247280E+10 0.00 0.832162E+09 0.00 0.00 0.206915E+10 0.00 0.66
April 0.00 0.462598E+10 0.00 0.614061E+09 0.00 0.00 0.392536E+09 0.00 0.67
May 0.00 0.196920E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
June 0.00 0.289772E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
July 0.00 0.390392E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
August 0.00 0.329510E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.68
September 0.00 0.298996E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.67
October 0.00 0.949475E+10 0.00 84764945.42 0.00 0.00 92306919.23 0.00 0.66
November 0.00 0.893764E+09 0.00 0.117770E+10 0.00 0.00 0.331140E+10 0.00 0.66
December 0.00 0.00 0.00 0.217203E+10 0.00 0.00 0.110815E+11 0.00 0.66
                   
Annual Sum or Average 0.00 0.168208E+12 0.00 0.624156E+10 0.00 0.00 0.377039E+11 0.00 0.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.66
Maximum of Months 0.00 0.390392E+11 0.00 0.217203E+10 0.00 0.00 0.139978E+11 0.00 0.68



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.290993E+12 0.300579E+10 0.00 0.851044E+12 0.113000E+13
February 0.336876E+12 0.351694E+10 0.00 0.551517E+12 0.166947E+13
March 0.457104E+12 0.207383E+10 0.00 0.252033E+12 0.287539E+13
April 0.496583E+12 -0.156170E+10 0.00 -0.266823E+12 0.392212E+13
May 0.541000E+12 -0.725241E+10 0.00 -0.912719E+12 0.370818E+13
June 0.505040E+12 -0.823236E+10 0.00 -0.141686E+13 0.453443E+13
July 0.410830E+12 -0.175677E+11 0.00 -0.193869E+13 0.540333E+13
August 0.344035E+12 -0.123155E+11 0.00 -0.195118E+13 0.579819E+13
September 0.371864E+12 -0.709814E+10 0.00 -0.142099E+13 0.356651E+13
October 0.354735E+12 -617010426.0 0.00 -0.151604E+12 0.291445E+13
November 0.307931E+12 0.876516E+09 0.00 0.438560E+12 0.255380E+13
December 0.266882E+12 0.298765E+10 0.00 0.793843E+12 0.248370E+13
           
Annual Sum or Average 0.468387E+13 -0.421841E+11 0.00 -0.517187E+13 0.405596E+14
Minimum of Months 0.266882E+12 -0.175677E+11 0.00 -0.195118E+13 0.113000E+13
Maximum of Months 0.541000E+12 0.351694E+10 0.00 0.851044E+12 0.579819E+13