Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860

Simulation Timestamp: 2023-10-16 09:04:39


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 29722.06 641.66 641.66
Net Site Energy 29722.06 641.66 641.66
Total Source Energy 90321.17 1949.92 1949.92
Net Source Energy 90321.17 1949.92 1949.92


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 1121.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3472.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2745.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 449.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2283.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 620.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1130.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4966.52
Humidification 14.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.29
Heat Recovery 48.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 706.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 27893.64 1828.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7251.98
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1121.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 3472.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2745.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 449.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 59.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2283.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 620.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1130.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4966.52
Humidification General 14.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.29
Heat Recovery General 48.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 706.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 1121.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 3472.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2745.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 449.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2283.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 620.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1130.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4966.52
Humidification Unassigned 14.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5.29
Heat Recovery Unassigned 48.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 706.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 162.39 39.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16
Other 370.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 602.19 39.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 162.39 39.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16
Other 370.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 602.19 39.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.16


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 27893.641 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 27893.641 100.00
     
Total On-Site and Utility Electric Sources 27893.641 100.00
Total Electricity End Uses 27893.641 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 470.49 33.91
Air to Air Heat Recovery for Heating 916.94 66.09
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 1387.43 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 7251.98 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 7251.98 100.00
Total Water End Uses 7251.98 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 56.00
Time Setpoint Not Met During Occupied Cooling 405.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 5939.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
RunPeriod RUNPERIOD 1
Weather File New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Latitude [deg] 40.65
Longitude [deg] -73.8
Elevation [m] 5.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 7.6202 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 7.6202 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 7.6202 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 7.6202 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 7.6202 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 7.6202 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 7.6202 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 7.6202 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 12.5114 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 12.5114 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 12.5114 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 7.6202 18.58 484.4232  
Total 46320.38             7.6661 9.29 17.8789  
Conditioned Total 46320.38             7.6661 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.3561 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 22-AUG-14:39 02-JAN-05:10 - - - - - - - - - - 30-AUG-15:50
Heating 0.00 1746492.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 445167.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 37754.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 283348.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 70698.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 90459.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3742.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 5695.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1959609.74 1752188.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 1746492.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 445167.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3711.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 33930.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 112.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 283348.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 70698.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 90459.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 3742.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 5695.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 1215.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 10998.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8695.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1422.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6062.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7232.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1965.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 3580.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 45.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 154.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 766.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 88339.16 1982.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 237.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 156.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 42.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 77.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1907.13 42.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 26.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 237.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 156.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 42.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 77.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 16.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1907.13 42.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.28
DATACENTER_BOT_ZN_6 DIRECT AIR 0.472311
DATACENTER_MID_ZN_6 DIRECT AIR 4.51
DATACENTER_TOP_ZN_6 DIRECT AIR 0.459345
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.61 0.338841 0.340000 1.91 0.903576 0.500000 0.001124 0.000176 1.91 12.80 0.008000
CORE_MID VAV BOX COMPONENT 52.76 0.360524 0.355000 18.73 0.961399 0.500000 0.001057 0.004447 18.73 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.37 0.354089 0.356000 1.91 0.944237 0.500000 0.001076 0.000811 2.76 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.934792 0.255480 0.256000 0.239307 0.681279 0.500000 0.001491 0.000141 0.479133 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.04 0.147752 0.200000 0.208329 0.394006 0.500000 0.002579 0.000096 0.327529 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.26 0.188908 0.200000 0.252849 0.503754 0.500000 0.002017 0.000155 0.528177 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.30 0.118174 0.200000 0.260472 0.315131 0.500000 0.003224 0.000076 0.260472 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.84 0.270076 0.266000 2.35 0.720203 0.500000 0.001411 0.002378 8.12 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 10.94 0.140644 0.200000 2.19 0.375050 0.500000 0.002709 0.001562 5.33 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 12.32 0.193852 0.200000 2.46 0.516938 0.500000 0.001965 0.002355 8.04 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 11.42 0.134737 0.200000 2.28 0.359298 0.500000 0.002828 0.001517 5.18 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.04 0.229537 0.236000 0.245545 0.612099 0.500000 0.001660 0.000305 1.04 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.12 0.137150 0.200000 0.224433 0.365734 0.500000 0.002778 0.000199 0.681083 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.36 0.175922 0.200000 0.271513 0.469125 0.500000 0.002166 0.000302 1.03 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.23 0.124926 0.200000 0.246394 0.333135 0.500000 0.003050 0.000197 0.672064 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 20089.51 0.000176 406.82
CORE_MID VAV BOX REHEAT COIL 508268.08 0.004447 12344.87
CORE_TOP VAV BOX REHEAT COIL 92710.99 0.000811 2447.39
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 16065.01 0.000141 423.79
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 10980.27 0.000096 289.64
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 17706.24 0.000155 467.04
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8694.95 0.000076 228.91
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 271829.17 0.002378 7166.71
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 178600.17 0.001562 4708.67
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 269201.03 0.002355 7097.46
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 173446.66 0.001517 4572.86
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 34830.21 0.000305 918.14
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 22799.52 0.000199 601.00
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 34513.29 0.000302 909.79
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 22497.72 0.000197 593.04
VAV_BOT WITH REHEAT HEATING COIL 69798.50 0.000611 1119.89
VAV_MID WITH REHEAT HEATING COIL 717380.55 0.006276 11389.18
VAV_TOP WITH REHEAT HEATING COIL 70617.11 0.000618 1132.48
CAV_BAS HEATING COIL 270970.20 0.002371 5947.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.08 2.87 10.16 2.87 9.25 9.25 0.300000 0.310289 9.25
VAV_MID WITH REHEAT 48.14 28.02 96.29 40.18 86.39 86.39 0.300000 0.465108 86.39
VAV_TOP WITH REHEAT 5.06 2.90 10.12 6.19 9.32 9.32 0.300000 0.663446 9.32
CAV_BAS 5.28 5.28 5.28 5.28 5.28 5.28 1.00 1.00 5.28
AIRLOOP DATACENTER BASEMENT 21.30 21.30 21.30 21.30 21.30 21.30 1.00 0.999988 21.30
AIRLOOP DATACENTER BOT 0.472311 0.472311 0.472311 0.472311 0.472311 0.472311 1.00 1.00 0.472311
AIRLOOP DATACENTER MID 4.51 4.51 4.51 4.51 4.51 4.51 1.00 1.00 4.51
AIRLOOP DATACENTER TOP 0.459345 0.459345 0.459345 0.459345 0.459345 0.459345 1.00 1.00 0.459345
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.25  
VAV_MID WITH REHEAT_OA_CONTROLLER 86.39  
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.32  
CAV_BAS_OA_CONTROLLER 5.28 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.30 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.472311 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.51 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.459345 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.33 6.67 10.95 0.010417 0.008500 229200.72 0.009751 9.25
VAV_MID WITH REHEAT COOLING COIL 26.58 6.67 10.95 0.010661 0.008500 2231858.92 0.094948 86.39
VAV_TOP WITH REHEAT COOLING COIL 26.20 6.67 10.95 0.010393 0.008500 228877.65 0.009737 9.32
CAV_BAS COOLING COIL 24.70 6.67 11.42 0.010148 0.008500 112810.89 0.004799 5.28
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.25
VAV_MID WITH REHEAT FAN 86.39
VAV_TOP WITH REHEAT FAN 9.32
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.009751 0.000049
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000611  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.094948 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.006276  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.009737 0.000049
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000618  
CAV_BAS_COOLC_CONTROLLER 0.004799 0.000099
CAV_BAS_HEATC_CONTROLLER 0.002371  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.28
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.30 430959.38 311115.05 0.010554
AIRLOOP DATACENTER BOT COOLING COIL 0.472311 9507.01 6877.70 0.000233
AIRLOOP DATACENTER MID COOLING COIL 4.51 90854.16 65670.26 0.002225
AIRLOOP DATACENTER TOP COOLING COIL 0.459345 9256.47 6692.41 0.000227
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.30 21.30 21.30 21.30 430959.38 430959.38 20749.82 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.472311 0.472311 0.472311 0.472311 9507.01 9507.01 958.56 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.51 4.51 4.51 4.51 90854.16 90854.16 9585.56 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.459345 0.459345 0.459345 0.459345 9256.47 9256.47 958.56 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.30
AIRLOOP DATACENTER BOT SUPPLY FAN 0.472311
AIRLOOP DATACENTER MID SUPPLY FAN 4.51
AIRLOOP DATACENTER TOP SUPPLY FAN 0.459345
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.30 430959.38 0.010554
AIRLOOP DATACENTER BOT HEATING COIL 0.472311 9507.01 0.000233
AIRLOOP DATACENTER MID HEATING COIL 4.51 90854.16 0.002225
AIRLOOP DATACENTER TOP HEATING COIL 0.459345 9256.47 0.000227
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 20749.82
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 958.56
AIRLOOP DATACENTER MID_SUPPHEATCOIL 9585.56
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 958.56
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000173 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.119235 24569.99  
HEATSYS1 PUMP 0.024592 7405.98 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.119235 14.31
HEATSYS1 0.024592 2.95
COOLSYS1_SUPPLY 0.119235 14.31
SINGLE WATER PLANT LOOP 0.013239 1.59
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.119235 0.119235 500490.75 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 2810999.16 2810999.16 0.024592
CENTRAL BOILER 545320.80 534724.26 0.013239
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.119235 17010.64
PLANT CIRC PUMP 0.013239 3376.53
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.119235 0.059885 1411115.27 1417827.83 0.070163
COOLSYS1 CHILLER2 0.119235 0.059885 1411115.27 1417827.83 0.070163
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013239 139666.47 59495.76 69833.23 7879.72 21436.87
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.140326 16.84
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.140326 42263.16
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 54.26 1682223.24 10.85 210277.90
TOWERWATERSYS COOLTOWER 2 54.26 1682223.24 10.85 210277.90
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.072877
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 14.00 7.30 3.30 1.20 -0.20 5.60 10.90 16.10 21.70 25.00 24.80 19.90


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860 40.65 -73.80 -5.00 5.00 101265 1.2036


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 12.47 25.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 7.620 4.842 0.000 0.000 0.000 0.000 12.462 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 7.620 484.423 0.000 0.000 0.000 0.000 492.043 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 21179.739 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 21179.739
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5971.780 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5971.780
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1864 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.339 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.260 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.694 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.4185 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 5.307
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.5795
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.6262
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.4230
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.312
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.312
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.312
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.312
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.312
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.312
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62854340E-06 0.84784826E-09 -0.38512804E-05 0.91756347E-17
47 2 0.78257096 0.11428808E-02 1.0614277 -0.73836085E-06
48 1 -21.991499 0.76199851E-01 -6.3161914 0.20349372
49 0 21.357363 0.71091016E-01 5.4032014  
50 9 0.13684007E-14 0.43769670E-16 -0.13032795E-09 -0.34517937E-17
51 8 0.19139952E-07 0.17580734E-12 0.34842432E-03 -0.21762784E-09
52 7 -0.11363040E-01 0.94207812E-08 -0.21820187E-01 0.12920189E-03
53 6 0.38147639 0.33245073E-05 0.45170425 -0.44663469E-02
54 5 -4.9575440 0.12566514E-03 -4.2844407 0.60294545E-01
55 4 31.971915 0.10393916E-02 20.826829 -0.40843520
56 3 -109.03212 0.22875987E-02 -54.410870 1.4834967
57 2 194.95586 0.12980373E-02 76.763178 -2.8661744
58 1 -170.36074 0.13969006E-03 -54.933270 2.7315001
59 0 57.057407 0.80219562E-06 15.613236  
60 9 0.17296484E-14 0.42300129E-16 -0.13408130E-09 -0.44058463E-17
61 8 0.19671007E-07 0.16641005E-12 0.35423406E-03 -0.22366611E-09
62 7 -0.11537194E-01 0.88593938E-08 -0.22071206E-01 0.13118209E-03
63 6 0.38620962 0.31182457E-05 0.45575528 -0.45221398E-02
64 5 -5.0037487 0.11760487E-03 -4.3156427 0.60867449E-01
65 4 32.176377 0.97077592E-03 20.948989 -0.41114975
66 3 -109.46738 0.21328008E-02 -54.652468 1.4897847
67 2 195.38754 0.12083052E-02 76.984396 -2.8730290
68 1 -170.52030 0.12984550E-03 -54.996922 2.7342967
69 0 57.057407 0.74448799E-06 15.602172  
70 9 0.10997584E-14 0.53843923E-16 -0.11326114E-09 -0.28570046E-17
71 8 0.16725364E-07 0.21557791E-12 0.32127585E-03 -0.19017314E-09
72 7 -0.10546704E-01 0.11930081E-07 -0.20642631E-01 0.11991984E-03
73 6 0.35928609 0.42648229E-05 0.43264702 -0.42047803E-02
74 5 -4.7408821 0.16300219E-03 -4.1373754 0.57608138E-01
75 4 31.012880 0.13615538E-02 20.250423 -0.39570291
76 3 -106.98970 0.30226891E-02 -53.270634 1.4539929
77 2 192.92930 0.17282771E-02 75.720319 -2.8339965
78 1 -169.61128 0.18730106E-03 -54.635416 2.7183650
79 0 57.057407 0.10839563E-05 15.666826  
80 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
81 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
82 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
83 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
84 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
85 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
86 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
87 0 0.43108349 0.21254961E-04 60.838472  
88 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
89 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
90 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
91 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
92 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
93 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
94 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
95 0 0.43108349 0.21254961E-04 60.838472  
96 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
97 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
98 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
99 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
100 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
101 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
102 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
103 0 0.43108349 0.21254961E-04 60.838472  
104 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
105 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
106 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
107 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
108 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
109 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
110 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
111 0 0.43108349 0.21254961E-04 60.838472  
112 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
113 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
114 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
115 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
116 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
117 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
118 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
119 0 0.43108349 0.21254961E-04 60.838472  
120 7 -0.98583555E-09 -0.79843648E-16 0.12056005E-14 0.46388562E-17
121 6 0.11736010E-04 0.80964505E-08 0.31724491E-02 -0.26613162E-04
122 5 -0.85155955E-03 0.48044989E-05 -0.22273424 0.19474091E-02
123 4 0.19629464E-01 0.21887653E-03 4.8130477 -0.45106395E-01
124 3 -0.17247723 0.17421542E-02 -37.928201 0.39762344
125 2 0.61254091 0.29000861E-02 116.30250 -1.4155123
126 1 -0.88416489 0.88473762E-03 -143.80049 2.0472841
127 0 0.43108349 0.21254961E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.3822_SHGC_EAST_0.36 35 1 VerySmooth 2.171 2.171 1.000 0.361    
2 WINDOW_U_0.3822_SHGC_SOUTH_0.36 36 1 VerySmooth 2.171 2.171 1.000 0.361    
3 WINDOW_U_0.3822_SHGC_WEST_0.36 37 1 VerySmooth 2.171 2.171 1.000 0.361    
4 WINDOW_U_0.3822_SHGC_NORTH_0.36 38 1 VerySmooth 2.171 2.171 1.000 0.361    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   3.43662E-002 0.27318 0.51756 0.51756 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11924 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   3.43662E-002 0.27318 0.51756 0.51756 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11924 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   3.43662E-002 0.27318 0.51756 0.51756 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11924 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   3.43662E-002 0.27318 0.51756 0.51756 0.36000 0.14234 0.19141 0.00000 0.84000 0.84000 0.11924 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5291E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5308E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.9532E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9547E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2216E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2228E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7698E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7704E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5696E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.6906E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.9875E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.0934E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2512E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.3391E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7873E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8319E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1208
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.2531E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1373
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0500E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 9.0010E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6925E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.7170E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.3047E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5718E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.7013E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.9898E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 5.1044E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2532E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.3467E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7877E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.8332E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.5289E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.5307E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.9531E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 4.9546E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.2215E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2227E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.7697E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.7704E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8941E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.1365E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.6887E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9537E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5298E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6368E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0284E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0591E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.4374E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.2710E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.1421E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.0485E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.6660E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.9684E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8227E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.4292E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8199E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.9036E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.5929E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.6535E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4957E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.5194E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.0285E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.0596E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8382E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8399E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5600E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5614E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3805E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3815E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7698E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7704E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8761E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9749E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5908E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6687E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4056E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4612E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7878E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8333E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9500E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7124E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2773E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2960E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2994E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1344E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.7170E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3043E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8751E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9726E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5897E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6661E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4040E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4566E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7873E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8320E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8381E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.8398E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.5600E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.5613E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.3805E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3814E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.7697E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.7704E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7111E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7955E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4569E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.5179E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4078E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.4310E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0286E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0596E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.2274E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1860E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8824E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.9434E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.4842E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.8944E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8227E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.4292E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.7808E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.0062E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.5472E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.7906E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.4412E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.5452E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.0283E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0590E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1103
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 7.9013E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1210
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 8.8006E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.3366E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.0391E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 4.2949E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.0811E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.1091E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.1347E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.7879E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.8721E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.2954E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.7483E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 4.3948E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.1031E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.5192E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.4890E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.7875E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.9612E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.8060E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.5254E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.2949E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.0807E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.8814E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.0233E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.5059E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.7338E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.1002E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.6550E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 4.3948E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.1031E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1102
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 7.9120E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1208
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 8.8135E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.3379E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.0492E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 4.2998E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.0851E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.1061E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.1374E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.7860E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.8749E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.2970E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.7529E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 4.3994E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1071E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.5146E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.4900E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.7844E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.9621E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.8074E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5277E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.2998E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.0847E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.8782E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.0258E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.5038E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.7363E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.1017E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.6595E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 4.3994E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.1071E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 73318.86467 73318.86467 5.28010 5.28010 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:20:00 -10.70000 1.50390E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 77948.18478 77948.18478 5.61338 5.61338 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 1101.61439 1101.61439 4.70658E-002 1.07782 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 732804.18102 732804.18102 52.75769 52.75769 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 319779.23227 319779.23227 13.51351 13.51351 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 74603.57039 74603.57039 5.37166 5.37166 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 26.62400 1.41098E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 64925.78402 64925.78402 2.76084 2.76084 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12859.32364 12859.32364 0.93479 0.93479 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 32.10000 1.41196E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 11251.76827 11251.76827 0.47913 0.47913 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 14329.30653 14329.30653 1.04164 1.04164 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 27.79567 1.41119E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 7689.61278 7689.61278 0.32753 0.32753 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 17391.45837 17391.45837 1.26425 1.26425 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 31.73000 1.41190E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 12398.78676 12398.78676 0.52818 0.52818 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 17915.91563 17915.91563 1.30236 1.30236 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 6079.89807 6079.89807 0.25870 0.25870 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 121634.60486 121634.60486 8.84271 8.84271 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 32.10000 1.41196E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 190303.58515 190303.58515 8.11716 8.11716 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 150524.29801 150524.29801 10.94289 10.94289 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 28.23967 1.41127E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 125034.84725 125034.84725 5.33343 5.33343 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 169466.74063 169466.74063 12.32001 12.32001 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 31.79167 1.41191E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 188465.86832 188465.86832 8.03858 8.03858 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 157123.95550 157123.95550 11.42266 11.42266 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 31.16267 1.41180E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 121431.04503 121431.04503 5.17937 5.17937 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 14002.82321 14002.82321 1.01802 1.01802 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 32.10000 1.41196E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 24380.82272 24380.82272 1.04044 1.04044 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 15435.41838 15435.41838 1.12216 1.12216 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 28.44933 1.41131E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 15959.51643 15959.51643 0.68108 0.68108 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 18673.39240 18673.39240 1.35757 1.35757 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 31.91500 1.41193E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 24159.19478 24159.19478 1.03097 1.03097 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 16945.87606 16945.87606 1.23197 1.23197 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 31.26133 1.41181E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 15748.43641 15748.43641 0.67206 0.67206 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -10.70000 1.50390E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8237.99884 8237.99884 0.47231 0.47231 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 29.58400 1.41151E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -10.70000 1.50390E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 78598.84137 78598.84137 4.50636 4.50636 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 29.58400 1.41151E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -10.70000 1.50390E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8011.81532 8011.81532 0.45935 0.45935 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 29.76900 1.41154E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -10.70000 1.50390E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 371512.58824 371512.58824 21.29966 21.29966 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 25.36600 1.41076E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 03:50:00 -10.70000 1.50390E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 144101.03 9.24784 9.24784 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 72120.43 2.67136 2.67136 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:50:00
3 VAV_MID WITH REHEAT Cooling Sensible 1328271.32 86.39302 86.39302 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 720953.29 40.18205 40.18205 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00
5 VAV_TOP WITH REHEAT Cooling Sensible 151138.33 9.32315 9.32315 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 72077.12 6.18540 6.18540 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00
7 CAV_BAS Cooling Sensible 75760.41 5.28010 5.28010 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 73592.09 1.20016 1.20016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 367420.18 21.29992 21.29992 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 20749.82 0.33839 0.33839 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8160.05 0.47231 0.47231 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 958.56 1.56323E-002 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 77872.30 4.50636 4.50636 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 9585.56 0.15632 0.15632 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7940.31 0.45935 0.45935 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 958.56 1.56323E-002 1.56323E-002 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.28010
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.61338
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33884
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34000
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.90855
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.90358
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12442E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.75752E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.90855
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20089.50992
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.75752E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 406.82197
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 52.75769
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36052
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35500
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 18.72898
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.96140
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.05679E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.44655E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 18.72898
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 508268.08469
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.44655E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12344.87102
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.37166
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35409
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.35600
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.91231
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.94424
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.07600E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.11076E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.76084
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 92710.98843
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.11076E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2447.38867
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.93479
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25548
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25600
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23931
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68128
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.49131E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.40544E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.47913
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 16065.00510
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.40544E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 423.78769
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.04164
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14775
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.20833
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.39401
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.57864E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 9.60602E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.32753
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 10980.27029
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 9.60602E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 289.63586
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.26425
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.18891
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25285
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.50375
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.01686E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.54902E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.52818
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 17706.23583
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.54902E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 467.04402
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.30236
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11817
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.26047
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31513
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.22406E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.60672E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.26047
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 8694.95004
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.60672E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 228.90717
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.84271
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27008
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26600
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.35216
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.72020
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.41071E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.37808E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.11716
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 271829.16870
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.37808E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7166.70630
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.94289
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14064
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.18858
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37505
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.70897E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.56247E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.33343
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 178600.16647
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.56247E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4708.66536
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.32001
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.19385
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.46400
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.51694
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.96542E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.35509E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.03858
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 269201.02998
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.35509E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7097.45928
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 11.42266
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13474
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.28453
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.35930
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.82774E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.51739E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.17937
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 173446.65596
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.51739E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4572.86341
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.04044
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.22954
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.23600
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24554
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61210
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.65986E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.04710E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.04044
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 34830.21446
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.04710E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 918.14073
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12216
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.13715
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.22443
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.36573
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.77797E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.99460E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.68108
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22799.51513
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.99460E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 600.99820
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.35757
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.17592
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27151
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.46913
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.16573E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.01937E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.03097
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 34513.28767
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.01937E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 909.79017
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23197
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12493
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24639
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33314
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.04981E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.96820E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.67206
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22497.71516
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.96820E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 593.04446
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.47231
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.50636
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.45935
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.29966
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.07821
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.86951
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.15642
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.86951
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.24784
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.24784
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.31029
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 48.14298
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 28.01825
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 96.28596
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 40.18205
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 86.39302
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 86.39302
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.46511
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.06190
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.90019
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 10.12380
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 6.18540
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.32315
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.32315
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.66345
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.28010
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.28010
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.28010
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.28010
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.28010
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.28010
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.29966
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.29966
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.29966
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.29966
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.29992
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.29992
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.47231
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.47231
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.47231
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.47231
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.47231
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.47231
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.50636
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.50636
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.50636
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.50636
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.50636
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.50636
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.45935
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.45935
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.45935
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.45935
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.45935
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.45935
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.24784
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 86.39302
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.32315
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.28010
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.29992
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.47231
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.50636
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.45935
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.24784
289 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.33437
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94742
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.04167E-002
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 229200.72335
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.75073E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.24784
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 69798.50194
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.10628E-004
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1119.88615
301 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.24784
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.75073E-003
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.88364E-005
304 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.10628E-004
305 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 86.39302
306 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.57797
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94824
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.06611E-002
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2231858.92395
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.49484E-002
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 86.39302
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 717380.54921
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.27596E-003
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 11389.17724
318 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 86.39302
319 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.49484E-002
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 5.01525E-006
321 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.27596E-003
322 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.32315
323 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.20376
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.94734
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.03926E-002
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 228877.65226
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 9.73698E-003
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.32315
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 70617.11296
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 6.17789E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 1132.48301
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.32315
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 9.73698E-003
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.89053E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 6.17789E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.28010
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.70431
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.42380
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.01478E-002
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 112810.89057
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 4.79924E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.28010
349 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 270970.19768
350 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.37057E-003
351 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5947.01436
352 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.28010
353 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 4.79924E-003
354 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 9.92221E-005
355 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.37057E-003
356 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.29992
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.29992
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 430959.38432
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 311115.04699
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.05542E-002
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.29992
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.29992
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.29992
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.29992
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 430959.38432
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 430959.38432
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 20749.82071
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
370 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.29992
371 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.29992
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 430959.38432
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.05542E-002
374 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 20749.82071
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.72692E-004
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
377 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
379 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.47231
380 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.47231
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9507.00802
383 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6877.69865
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.32826E-004
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.47231
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.47231
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.47231
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.47231
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9507.00802
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9507.00802
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 958.55576
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
393 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.47231
394 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.47231
395 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9507.00802
396 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.32826E-004
397 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 958.55576
398 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.50636
399 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.50636
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 90854.15736
402 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 65670.26171
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.22501E-003
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.50636
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.50636
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.50636
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.50636
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 90854.15736
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 90854.15736
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 9585.55755
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
412 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.50636
413 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.50636
414 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 90854.15736
415 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.22501E-003
416 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 9585.55755
417 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.45935
418 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.45935
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9256.46997
421 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6692.40897
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.26690E-004
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.45935
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.45935
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.45935
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.45935
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9256.46997
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9256.46997
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 958.55576
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
431 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.45935
432 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.45935
433 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9256.46997
434 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.26690E-004
435 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 958.55576
436 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.11924
437 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 24569.99400
438 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.11924
439 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 14.30825
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.11924
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.11924
442 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 500490.74824
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
444 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 2.45918E-002
445 PlantLoop HEATSYS1 Plant Loop Volume [m3] 2.95102
446 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 2.45918E-002
447 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 7405.98434
448 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
449 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 2810999.15962
450 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 2810999.16000
451 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 2.45918E-002
452 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.11924
453 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 14.30825
454 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.11924
455 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 17010.63565
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.11924
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 5.98850E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1411115.26935
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1417827.83500
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.01630E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.11924
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 5.98850E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1411115.26935
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1417827.83500
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.01630E-002
466 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.32387E-002
467 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.58864
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.32387E-002
469 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3376.52962
470 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.32387E-002
471 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
472 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 59495.75544
473 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
474 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
475 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21436.86697
476 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 545320.79648
477 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 534724.26000
478 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.32387E-002
479 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
480 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
482 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
483 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
484 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.14033
485 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 16.83913
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.14033
487 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 42263.16412
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 54.25705
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1682223.23500
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 10.85141
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 210277.90438
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 54.25705
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1682223.23500
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 10.85141
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 210277.90438
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.28775E-002
497 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.28775E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 19048.34
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 481462.57
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 87852.81
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 15221.19
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 10403.40
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 16775.96
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 8235.14
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 257524.30
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 169200.88
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 255034.76
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 164319.03
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 32996.29
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 21599.00
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 32696.08
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 21313.10
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 50927.45
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 511629.54
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 51479.24
19 Coil:Heating:Water CAV_BAS HEATING COIL 211120.40


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 244431.25 166932.50 77498.75 0.68 25391.95 257.54
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2321644.02 1577540.74 744103.28 0.68 241744.39 2451.91
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 245551.89 167886.16 77665.73 0.68 25510.38 258.74
4 Coil:Cooling:Water CAV_BAS COOLING COIL 129663.06 90516.25 39146.82 0.70 13187.83 133.76


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.419 0.394   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.419 0.394   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_NORTH_0.36 N/A 2.171 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_NORTH_0.36 N/A 2.171 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_NORTH_0.36 N/A 2.171 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_NORTH_0.36 N/A 2.171 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_NORTH_0.36 N/A 2.171 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_EAST_0.36 N/A 2.171 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_EAST_0.36 N/A 2.171 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_EAST_0.36 N/A 2.171 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_SOUTH_0.36 N/A 2.171 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_SOUTH_0.36 N/A 2.171 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_SOUTH_0.36 N/A 2.171 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_SOUTH_0.36 N/A 2.171 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_SOUTH_0.36 N/A 2.171 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_WEST_0.36 N/A 2.171 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_WEST_0.36 N/A 2.171 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_WEST_0.36 N/A 2.171 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_NORTH_0.36 N/A 2.171 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_EAST_0.36 N/A 2.171 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_SOUTH_0.36 N/A 2.171 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_WEST_0.36 N/A 2.171 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_NORTH_0.36 N/A 2.171 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_EAST_0.36 N/A 2.171 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_SOUTH_0.36 N/A 2.171 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.3822_SHGC_WEST_0.36 N/A 2.171 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.339 1.115   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.260 1.060   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.694 1.351   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.186 0.180   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.419 0.394   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.419 0.394   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 1.5244275008E-003 1.3779584362E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 3.2065267742E-003 3.0510702090E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 1.8952761453E-002 1.1827367006E-002 Pass Pass 0.4859363059 0.4932995494 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 7.1901655070E-002 8.6713160964E-002 Pass Pass 0.8741235618 1.4203244554 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 2.7926236535E-002 2.0209009678E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 5.1089938386E-002 5.8589347187E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 8.3801024038E-002 8.7844755793E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 4.0306845488E-002 3.5712845121E-002 Pass Pass 0.0000000000 0.0000000000 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.6448690840 0.5790721634 Pass Pass 0.7113388060 0.6131029056 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.5670729189 0.6043768880 Pass Pass 0.7401873142 0.6741318829 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.4363477464 0.5206109169 Pass Pass 7.1183368856 63.4717703490 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.5570105887 0.5745679134 Pass Pass 0.7432848997 0.6760115184 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.8541620596 0.7419026930 Pass Pass 0.6658858997 0.5858124633 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.7685567635 0.7843651848 Pass Pass 0.6869841275 0.6106380013 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.6193962294 0.6954695849 Pass Pass 0.9030426176 1.7192187851 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.7712561137 0.7884095620 Pass Pass 0.6952455600 0.6175171393 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 9.8365052701E-003 6.5841931496E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 9.4714098470E-002 6.0845066172E-002 Pass Pass 0.4888764262 0.4880077487 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1795239032 0.1364595483 Pass Pass 0.5041738029 0.4959766586 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 7.7966250106E-003 3.5117912283E-002 Pass Pass 0.6894088679 3.5006419731 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 9.6725776257E-003 7.9668935412E-003 Pass Pass 3.9038962358E-003 4.3700280452E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 1.4788464402E-002 1.1215955252E-002 Pass Pass 5.7453834229E-003 6.2157641296E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.2617979501E-005 2.1585885112E-005 Pass Pass 7.3784597941E-005 1.1160446637E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 7057.54 224.26 0.00 14673.12 21704.43 43659.34



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB -10.70 0.00 -10.70 Wetbulb [C] 7.50 320.00
NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 32.10 7.40 23.10 Wetbulb [C] 5.60 230.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 172.00 59      
Feb 49.00 37      
Mar 40.00 38      
Apr 70.00 48      
May 70.00 36      
Jun 25.00 15      
Jul 64.00 20      
Aug 2.00 4      
Sep 73.00 32      
Oct 7.00 8      
Nov 88.00 34      
Dec 62.00 39      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.399 0.419 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.399 0.419 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.060 1.260 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.060 1.260 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.115 1.339 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.115 1.339 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.060 1.260 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.060 1.260 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.060 1.260 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.351 1.694 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.351 1.694 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.182 0.186 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.399 0.419 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.399 0.419 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.3822_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.3822_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.3822_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.3822_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.3822_SHGC_NORTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.3822_SHGC_EAST_0.36   19.32 0.00 0.00 19.32 19.32 2.171 0.361 0.361             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.3822_SHGC_EAST_0.36   19.32 0.00 0.00 19.32 19.32 2.171 0.361 0.361             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.3822_SHGC_EAST_0.36   19.32 0.00 0.00 19.32 19.32 2.171 0.361 0.361             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.3822_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.3822_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.3822_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.3822_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.3822_SHGC_SOUTH_0.36   17.38 0.00 0.00 17.38 17.38 2.171 0.361 0.361             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.3822_SHGC_WEST_0.36   19.32 0.00 0.00 19.32 19.32 2.171 0.361 0.361             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.3822_SHGC_WEST_0.36   19.32 0.00 0.00 19.32 19.32 2.171 0.361 0.361             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.3822_SHGC_WEST_0.36   19.32 0.00 0.00 19.32 19.32 2.171 0.361 0.361             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3822_SHGC_NORTH_0.36   86.92 0.00 0.00 86.92 869.21 2.171 0.361 0.361             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3822_SHGC_EAST_0.36   57.95 0.00 0.00 57.95 579.48 2.171 0.361 0.361             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3822_SHGC_SOUTH_0.36   86.92 0.00 0.00 86.92 869.21 2.171 0.361 0.361             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3822_SHGC_WEST_0.36   57.95 0.00 0.00 57.95 579.48 2.171 0.361 0.361             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.3822_SHGC_NORTH_0.36   86.92 0.00 0.00 86.92 86.92 2.171 0.361 0.361             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.3822_SHGC_EAST_0.36   57.95 0.00 0.00 57.95 57.95 2.171 0.361 0.361             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.3822_SHGC_SOUTH_0.36   86.92 0.00 0.00 86.92 86.92 2.171 0.361 0.361             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.3822_SHGC_WEST_0.36   57.95 0.00 0.00 57.95 57.95 2.171 0.361 0.361             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.171 0.361 0.361                      
North Total or Average             1043.06 2.171 0.361 0.361                      
Non-North Total or Average             2433.80 2.171 0.361 0.361                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 7.6202 2779.43 21179.74 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 177.74
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 7.6202 24961.20 190208.95 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 1596.24
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.98 0.0000 Y 13.89
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.96 0.0000 Y 8.95
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.77 0.0000 Y 13.80
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.81 0.0000 Y 8.90
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 7.6202 3134.13 23882.63 LightsWired LTG_SCH_OFFICE 45.89 168.00 31.01 0.0000 Y 139.03
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.97 0.0000 Y 89.49
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 7.6202 3134.20 23883.15 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.79 0.0000 Y 138.04
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.82 0.0000 Y 89.05
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 31.01 0.0000 Y 13.90
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.97 0.0000 Y 8.95
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.79 0.0000 Y 13.80
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.82 0.0000 Y 8.91
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 7.6202 783.68 5971.78 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 50.12
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 12.5114 362.03 4529.48 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 46.40
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
Interior Lighting Total       7.6661 46320.38 355094.67               857.30


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   42.43 42.43 79.44
EXTERIOR_LIGHTS_B 27638.03 AstronomicalClock -   83.64 71.28 369.80
Exterior Lighting Total 37611.08           449.24



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 2796302.70          
HEATSYS1 BOILER Boiler:HotWater 2810999.16 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1417827.83 6.28 1357043.73 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1417827.83 6.28 1357043.73 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 534724.26 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1682223.24          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1682223.24          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 229200.72 244431.25 166932.50 77498.75 0.68 - 25391.95 257.54
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2231858.92 2321644.02 1577540.74 744103.28 0.68 - 241744.39 2451.91
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 228877.65 245551.89 167886.16 77665.73 0.68 - 25510.38 258.74
CAV_BAS COOLING COIL Coil:Cooling:Water 112810.89 129663.06 90516.25 39146.82 0.70 - 13187.83 133.76
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   430959.38 311115.05 119844.34 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9507.01 6877.70 2629.31 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   90854.16 65670.26 25183.90 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9256.47 6692.41 2564.06 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 20089.51 19048.34 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 508268.08 481462.57 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 92710.99 87852.81 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 16065.01 15221.19 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 10980.27 10403.40 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 17706.24 16775.96 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 8694.95 8235.14 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 271829.17 257524.30 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 178600.17 169200.88 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 269201.03 255034.76 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 173446.66 164319.03 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 34830.21 32996.29 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 22799.52 21599.00 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 34513.29 32696.08 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 22497.72 21313.10 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 69798.50 50927.45 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 717380.55 511629.54 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 70617.11 51479.24 -
CAV_BAS HEATING COIL Coil:Heating:Water 270970.20 211120.40 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   430959.38 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9507.01 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   90854.16 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9256.47 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   20749.82 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   958.56 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   9585.56 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   958.56 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.25 21119.54 2283.73 1.00 1.12 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 86.39 197298.14 2283.73 1.00 1.07 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.32 21291.54 2283.73 1.00 1.11 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.28 8953.22 1695.65 1.00 1.16 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.30 35314.70 1657.97 1.00 1.13 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.47 529.04 1120.11 1.00 1.63 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.51 5047.61 1120.11 1.00 1.16 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.46 514.52 1120.11 1.00 1.65 General NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.119235 24569.99 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.024592 7405.98 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.119235 17010.64 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013239 3376.53 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.140326 42263.16 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 73318.86 73318.86 26.38 5.280 5.280 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00898 26.62 0.01411 1.200 0.00
CORE_BOTTOM 77948.18 77948.18 31.23 5.613 5.613 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00890 26.62 0.01411 1.078 0.00
CORE_MID 732804.18 732804.18 293.58 52.758 52.758 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00893 26.62 0.01411 10.778 0.00
CORE_TOP 74603.57 74603.57 29.89 5.372 5.372 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00892 26.62 0.01411 1.078 0.00
PERIMETER_BOT_ZN_3 12859.32 12859.32 41.03 0.935 0.935 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00897 32.10 0.01412 0.135 0.00
PERIMETER_BOT_ZN_2 14329.31 14329.31 70.95 1.042 1.042 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:50:00 24.00 24.00 0.00878 27.80 0.01411 0.087 0.00
PERIMETER_BOT_ZN_1 17391.46 17391.46 55.49 1.264 1.264 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 24.00 24.00 0.00885 31.73 0.01412 0.135 0.00
PERIMETER_BOT_ZN_4 17915.92 17915.92 88.70 1.302 1.302 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00872 31.26 0.01412 0.087 0.00
PERIMETER_MID_ZN_3 121634.60 121634.60 388.10 8.843 8.843 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 24.00 24.00 0.00922 32.10 0.01412 1.353 0.00
PERIMETER_MID_ZN_2 150524.30 150524.30 745.26 10.943 10.943 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:10:00 24.00 24.00 0.00890 28.24 0.01411 0.872 0.00
PERIMETER_MID_ZN_1 169466.74 169466.74 540.70 12.320 12.320 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:10:00 24.00 24.00 0.00903 31.79 0.01412 1.353 0.00
PERIMETER_MID_ZN_4 157123.96 157123.96 777.94 11.423 11.423 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 24.00 24.00 0.00888 31.16 0.01412 0.872 0.00
PERIMETER_TOP_ZN_3 14002.82 14002.82 44.68 1.018 1.018 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 24.00 24.00 0.00921 32.10 0.01412 0.135 0.00
PERIMETER_TOP_ZN_2 15435.42 15435.42 76.42 1.122 1.122 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00894 28.45 0.01411 0.087 0.00
PERIMETER_TOP_ZN_1 18673.39 18673.39 59.58 1.358 1.358 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 13:30:00 24.00 24.00 0.00905 31.92 0.01412 0.135 0.00
PERIMETER_TOP_ZN_4 16945.88 16945.88 83.90 1.232 1.232 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 16:40:00 24.00 24.00 0.00890 31.26 0.01412 0.087 0.00
DATACENTER_BOT_ZN_6 8238.00 8238.00 227.55 0.472 0.472 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00859 29.58 0.01412 0.016 0.00
DATACENTER_MID_ZN_6 78598.84 78598.84 2171.07 4.506 4.506 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 27.00 27.00 0.00859 29.58 0.01412 0.156 0.00
DATACENTER_TOP_ZN_6 8011.82 8011.82 221.30 0.459 0.459 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 27.00 27.00 0.00859 29.77 0.01412 0.016 0.00
DATACENTER_BASEMENT_ZN_6 371512.59 371512.59 474.06 21.300 21.300 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00854 25.37 0.01411 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:20:00 21.00 23.50 0.00150 -10.70 0.00150 1.200 0.00
CORE_BOTTOM 1101.61 1101.61 0.44 0.047 1.078 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00174 -10.70 0.00150 1.078 0.00
CORE_MID 319779.23 319779.23 128.11 13.514 13.514 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 10.778 0.00
CORE_TOP 64925.78 64925.78 26.01 2.761 2.761 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -10.70 0.00150 1.078 0.00
PERIMETER_BOT_ZN_3 11251.77 11251.77 35.90 0.479 0.479 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00720 -10.70 0.00150 0.135 0.00
PERIMETER_BOT_ZN_2 7689.61 7689.61 38.07 0.328 0.328 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00726 -10.70 0.00150 0.087 0.00
PERIMETER_BOT_ZN_1 12398.79 12398.79 39.56 0.528 0.528 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00733 -10.70 0.00150 0.135 0.00
PERIMETER_BOT_ZN_4 6079.90 6079.90 30.10 0.259 0.259 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00690 -10.70 0.00150 0.087 0.00
PERIMETER_MID_ZN_3 190303.59 190303.59 607.20 8.117 8.117 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00717 -10.70 0.00150 1.353 0.00
PERIMETER_MID_ZN_2 125034.85 125034.85 619.06 5.333 5.333 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00716 -10.70 0.00150 0.872 0.00
PERIMETER_MID_ZN_1 188465.87 188465.87 601.32 8.039 8.039 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00716 -10.70 0.00150 1.353 0.00
PERIMETER_MID_ZN_4 121431.05 121431.05 601.22 5.179 5.179 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00714 -10.70 0.00150 0.872 0.00
PERIMETER_TOP_ZN_3 24380.82 24380.82 77.79 1.040 1.040 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00720 -10.70 0.00150 0.135 0.00
PERIMETER_TOP_ZN_2 15959.52 15959.52 79.02 0.681 0.681 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 20.99 0.00718 -10.70 0.00150 0.087 0.00
PERIMETER_TOP_ZN_1 24159.19 24159.19 77.08 1.031 1.031 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00719 -10.70 0.00150 0.135 0.00
PERIMETER_TOP_ZN_4 15748.44 15748.44 77.97 0.672 0.672 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 20.99 0.00717 -10.70 0.00150 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 25.14 0.00654 -10.70 0.00150 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.66 0.00200 -10.70 0.00150 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 20.77 0.00199 -10.70 0.00150 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 03:50:00 18.00 27.00 0.00850 -10.70 0.00150 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.25 9.25 2.67 2.67 9.2478 2.8695 9.2478 0.3103 0.3000
VAV_MID WITH REHEAT 86.39 86.39 40.18 40.18 86.3930 40.1821 86.3930 0.4651 0.3000
VAV_TOP WITH REHEAT 9.32 9.32 6.19 6.19 9.3232 6.1854 9.3232 0.6634 0.3000
CAV_BAS 5.28 5.28 1.20 1.20 5.2801 5.2801 5.2801 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.30 21.30 0.34 0.34 21.2999 21.2997 21.2999 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.47 0.47 0.02 0.02 0.4723 0.4723 0.4723 1.0000 1.0000
AIRLOOP DATACENTER MID 4.51 4.51 0.16 0.16 4.5064 4.5064 4.5064 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.46 0.46 0.02 0.02 0.4593 0.4593 0.4593 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 20089.510 20089.510 1.908549 0.00017575 406.822 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20089.51 20089.51 1.908549 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00173684 11.3356 1101.61 0.00 20163.40 20163.40
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 508268.085 508268.085 18.728978 0.00444655 12344.871 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 508268.08 508268.08 18.728978 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 319779.23 0.00 509908.34 509908.34
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 92710.988 92710.988 2.760845 0.00081108 2447.389 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 92710.99 92710.99 2.760845 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00800000 51.6928 64925.78 0.00 93032.10 93032.10
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 16065.005 16065.005 0.479133 0.00014054 423.788 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 16065.01 16065.01 0.479133 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00719854 46.5817 11251.77 0.00 16118.51 16118.51
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 10980.270 10980.270 0.327529 0.00009606 289.636 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 10980.27 10980.27 0.327529 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00725512 46.9432 7689.61 0.00 11016.71 11016.71
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 17706.236 17706.236 0.528177 0.00015490 467.044 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 17706.24 17706.24 0.528177 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00733066 47.4256 12398.79 0.00 17764.93 17764.93
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 8694.950 8694.950 0.260472 0.00007607 228.907 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 8694.95 8694.95 0.260472 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00690186 44.6844 6079.90 0.00 8720.88 8720.88
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 271829.169 271829.169 8.117165 0.00237808 7166.706 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 271829.17 271829.17 8.117165 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00716866 46.3943 190303.59 0.00 272705.53 272705.53
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 178600.166 178600.166 5.333432 0.00156247 4708.665 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 178600.17 178600.17 5.333432 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00715893 46.3323 125034.85 0.00 179175.37 179175.37
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 269201.030 269201.030 8.038578 0.00235509 7097.459 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 269201.03 269201.03 8.038578 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00716121 46.3466 188465.87 0.00 270069.23 270069.23
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 173446.656 173446.656 5.179371 0.00151739 4572.863 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 173446.66 173446.66 5.179371 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00713611 46.1863 121431.05 0.00 174005.74 174005.74
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 34830.214 34830.214 1.040444 0.00030471 918.141 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 34830.21 34733.25 1.040444 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00719576 46.5697 24380.82 0.00 34941.43 34941.43
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 22799.515 22799.515 0.681083 0.00019946 600.998 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22799.52 22799.52 0.681083 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 20.99 0.00718277 46.4870 15959.52 0.00 22872.26 22872.26
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 34513.288 34513.288 1.030967 0.00030194 909.790 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 34513.29 34513.29 1.030967 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 21.00 0.00718925 46.5281 24159.19 0.00 34623.52 34623.52
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 22497.715 22497.715 0.672064 0.00019682 593.044 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22497.72 22497.72 0.672064 12.80 11.59 0.00800000 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 0.0000 20.99 0.00717354 46.4280 15748.44 0.00 22569.51 22569.51
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 229200.723 -999.000 9.247836 0.00975073 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 229200.72 173008.65 9.247836 26.33 18.75 0.01041667 10.95 10.95 0.00850000 32.10 0.01411964 23.13 27.4463 24.00 0.00891647 47.9479 121103.82 0.00 229507.08 167073.30
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 69798.502 69798.502 2.774351 0.00061063 1119.886 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 69798.50 69798.50 2.774351 -8.00 -8.21 0.00179941 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 91.4877 21.00 0.00723482 46.8114 34602.79 0.00 61585.54 61585.54
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2231858.924 -999.000 86.393017 0.09494844 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 2231858.92 1640683.65 86.393017 26.58 19.02 0.01066108 10.95 10.95 0.00850000 32.10 0.01411964 23.13 29.3796 24.00 0.00904527 48.6318 1096515.53 0.00 2234964.44 1590148.74
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 717380.549 717380.549 25.917905 0.00627596 11389.177 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 717380.55 717380.55 25.917905 -10.09 -10.09 0.00162101 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 97.9321 19.36 0.00673517 48.2504 452087.97 0.00 618605.12 618605.12
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 228877.652 -999.000 9.323152 0.00973698 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 228877.65 172927.70 9.323152 26.20 18.69 0.01039257 10.95 10.95 0.00850000 32.10 0.01411964 23.13 27.2246 24.00 0.00899831 48.3831 128250.11 0.00 229181.57 166915.00
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 70617.113 70617.113 2.796946 0.00061779 1132.483 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 70617.11 70617.11 2.796946 -8.08 -8.08 0.00202180 12.80 11.59 0.00800000 -10.70 0.00150390 -10.70 90.7486 17.60 0.00668894 53.5319 50531.78 0.00 62256.55 62256.55
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 112810.891 -999.000 5.280095 0.00479924 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 112810.89 85881.69 5.280095 24.70 18.00 0.01014776 11.42 11.42 0.00850000 27.09 0.01411064 21.71 22.7298 24.00 0.00897685 48.2675 72388.71 0.00 112976.12 83034.10
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 270970.198 270970.198 5.280095 0.00237057 5947.014 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 270970.20 270970.20 5.280095 -2.43 -5.10 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 22.7298 23.62 0.00150390 8.3740 0.00 0.00 222940.97 222940.97
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 430959.384 311115.047 21.299925 0.01055417 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 403378.75 395698.35 -999.0 28.48 18.04 0.00863100 12.80 12.09 0.00850000 32.10 0.01411964 23.13 -999.0000 27.00 0.00854230 38.4643 371069.83 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9507.008 6877.699 0.472311 0.00023283 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 8890.19 8538.47 -999.0 28.04 18.00 0.00877081 12.80 12.09 0.00850000 29.77 0.01411544 22.48 -999.0000 27.00 0.00858780 38.6641 8235.01 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90854.157 65670.262 4.506359 0.00222501 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 84982.06 81465.46 -999.0 28.03 18.01 0.00878376 12.80 12.09 0.00850000 29.58 0.01411511 22.43 -999.0000 27.00 0.00859217 38.6837 78598.84 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9256.470 6692.409 0.459345 0.00022669 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 8657.54 8305.96 -999.0 28.04 18.01 0.00877833 12.80 12.09 0.00850000 29.77 0.01411544 22.48 -999.0000 27.00 0.00859030 38.6753 8011.82 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 430959.384 430959.384 21.299925 0.01055417 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 430959.38 430959.38 21.299925 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 1.5887 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9507.008 9507.008 0.472311 0.00023283 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9507.01 9507.01 0.472311 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.3098 25.77 0.00654062 31.7584 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90854.157 90854.157 4.506359 0.00222501 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 90854.16 90854.16 4.506359 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.4690 23.83 0.00199518 10.9586 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9256.470 9256.470 0.459345 0.00022669 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9256.47 9256.47 0.459345 -10.70 -10.70 0.00150390 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.4032 22.74 0.00199484 11.7052 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 20749.821 20749.821 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 20749.82 20749.82 21.299925 -0.17 -0.17 0.00838885 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 1.5887 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 958.556 958.556 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 958.56 958.56 0.472311 -0.35 -0.35 0.00637392 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.3098 25.77 0.00654062 31.7584 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 9585.558 9585.558 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9585.56 9585.56 4.506359 -0.37 -3.04 0.00197814 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.4690 23.83 0.00199518 10.9586 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 958.556 958.556 -999.0 -999.0 -999.000 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 958.56 958.56 0.459345 -0.36 -3.03 0.00197813 40.00 21.18 0.00800000 -10.70 0.00150390 -10.70 3.4032 22.74 0.00199484 11.7052 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 20089.510 20089.510 1.908549 0.00017575 406.822 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 0.7006 0.714675 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20089.51 20089.51 1.0000 2.29712040 1.908549 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.17573387 60.00 32.22 27.78 0.000 20089.51 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.93 0.00173684 21.00 0.00173684 11.3356 1101.61 0.00 20163.40 20163.40 2.29712040 12.80 11.60 0.00800000 33059.8 21.41 15.00 0.00800000 41837.5
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 508268.085 508268.085 18.728978 0.00444655 12344.871 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 17.7247 18.081403 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 508268.08 508268.08 1.0000 22.54210447 18.728978 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 4.44609734 60.00 32.22 27.78 0.000 508268.08 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 51.6928 319779.23 0.00 509908.34 509908.34 22.54210447 12.80 11.60 0.00800000 33059.8 34.98 19.65 0.00800000 55680.1
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 92710.988 92710.988 2.760845 0.00081108 2447.389 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 3.2331 3.298151 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 92710.99 92710.99 1.0000 3.32293912 2.760845 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.81099343 60.00 32.22 27.78 0.000 92710.99 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.91 0.00800000 21.00 0.00800000 51.6928 64925.78 0.00 93032.10 93032.10 3.32293912 12.80 11.60 0.00800000 33059.8 40.26 21.26 0.00800000 61056.8
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 16065.005 16065.005 0.479133 0.00014054 423.788 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 0.5602 0.571505 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 16065.01 16065.01 1.0000 0.57668156 0.479133 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.14052934 60.00 32.22 27.78 0.000 16065.01 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00719854 21.00 0.00719854 46.5817 11251.77 0.00 16118.51 16118.51 0.57668156 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61010.3
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 10980.270 10980.270 0.327529 0.00009606 289.636 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 0.3829 0.390618 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 10980.27 10980.27 1.0000 0.39421194 0.327529 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.09605040 60.00 32.22 27.78 0.000 10980.27 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00725512 21.00 0.00725512 46.9432 7689.61 0.00 11016.71 11016.71 0.39421194 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61006.0
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 17706.236 17706.236 0.528177 0.00015490 467.044 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 0.6175 0.629891 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 17706.24 17706.24 1.0000 0.63571123 0.528177 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.15488607 60.00 32.22 27.78 0.000 17706.24 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00733066 21.00 0.00733066 47.4256 12398.79 0.00 17764.93 17764.93 0.63571123 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61004.8
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 8694.950 8694.950 0.260472 0.00007607 228.907 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 0.3032 0.309319 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 8694.95 8694.95 1.0000 0.31350266 0.260472 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.07605946 60.00 32.22 27.78 0.000 8694.95 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.91 0.00690186 21.00 0.00690186 44.6844 6079.90 0.00 8720.88 8720.88 0.31350266 12.80 11.60 0.00800000 33059.8 40.08 21.21 0.00800000 60877.4
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 271829.169 271829.169 8.117165 0.00237808 7166.706 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 9.4794 9.670197 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 271829.17 271829.17 1.0000 9.76977888 8.117165 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 2.37783756 60.00 32.22 27.78 0.000 271829.17 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00716866 21.00 0.00716866 46.3943 190303.59 0.00 272705.53 272705.53 9.76977888 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60973.0
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 178600.166 178600.166 5.333432 0.00156247 4708.665 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 6.2283 6.353619 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 178600.17 178600.17 1.0000 6.41929211 5.333432 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 1.56231278 60.00 32.22 27.78 0.000 178600.17 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00715893 21.00 0.00715893 46.3323 125034.85 0.00 179175.37 179175.37 6.41929211 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60971.8
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 269201.030 269201.030 8.038578 0.00235509 7097.459 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 9.3878 9.576703 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 269201.03 269201.03 1.0000 9.67519240 8.038578 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 2.35484780 60.00 32.22 27.78 0.000 269201.03 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.95 0.00716121 21.00 0.00716121 46.3466 188465.87 0.00 270069.23 270069.23 9.67519240 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60973.4
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 173446.656 173446.656 5.179371 0.00151739 4572.863 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 6.0486 6.170285 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 173446.66 173446.66 1.0000 6.23386437 5.179371 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 1.51723222 60.00 32.22 27.78 0.000 173446.66 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00713611 21.00 0.00713611 46.1863 121431.05 0.00 174005.74 174005.74 6.23386437 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.8
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 34830.214 34830.214 1.040444 0.00030471 918.141 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 1.2146 1.239069 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 34830.21 34733.25 1.0000 1.25227323 1.040444 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.30467883 60.00 32.22 27.78 0.000 34830.21 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00719576 21.00 0.00719576 46.5697 24380.82 0.00 34941.43 34941.43 1.25227323 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.2
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 22799.515 22799.515 0.681083 0.00019946 600.998 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 0.7951 0.811082 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22799.52 22799.52 1.0000 0.81974863 0.681083 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.19943976 60.00 32.22 27.78 0.000 22799.52 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00718277 20.99 0.00718277 46.4870 15959.52 0.00 22872.26 22872.26 0.81974863 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60961.4
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 34513.288 34513.288 1.030967 0.00030194 909.790 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 1.2036 1.227794 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 34513.29 34513.29 1.0000 1.24086727 1.030967 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.30190650 60.00 32.22 27.78 0.000 34513.29 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00718925 21.00 0.00718925 46.5281 24159.19 0.00 34623.52 34623.52 1.24086727 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60962.5
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 22497.715 22497.715 0.672064 0.00019682 593.044 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 0.7846 0.800346 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22497.72 22497.72 1.0000 0.80889230 0.672064 12.80 11.59 0.00800000 33059.8 40.00 21.18 0.00800000 60796.0 0.19679975 60.00 32.22 27.78 0.000 22497.72 -10.70 0.00150390 -10.70 0.00000000 0.0000 20.94 0.00717354 20.99 0.00717354 46.4280 15748.44 0.00 22569.51 22569.51 0.80889230 12.80 11.60 0.00800000 33059.8 40.16 21.23 0.00800000 60961.6
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 229200.723 -999.000 9.247836 0.00975073 -999.000 -999.0000 1.00000 1.00000 1024.2041 1004.8586 1.2036 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.247836 11.13064917   4197.9300 999.8980 119.22322388 12.27 6.67 5.60 2802748.19 8.1777 8.177714 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 229200.72 173008.65 1.0000 11.13064917 9.247836 26.33 18.75 0.01041667 53023.2 10.95 10.95 0.00850000 32431.4 9.74973394 6.67 12.27 5.60 21119.541 208081.18 32.10 0.01411964 23.13 2.53819000 27.4463 24.00 0.00891647 24.00 0.00891647 47.9479 121103.82 0.00 229507.08 167073.30 11.13064917 26.33 18.76 0.01041667 53023.2 11.68 11.32 0.00819314 32403.9
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 69798.502 69798.502 2.774351 0.00061063 1119.886 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.247836 11.13064917   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 2.4341 2.483050 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:50:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 69798.50 69798.50 1.0000 3.33919475 2.774351 -8.00 -8.21 0.00179941 -3567.0 12.80 11.59 0.00800000 33059.8 0.61056545 60.00 32.22 27.78 0.000 69798.50 -10.70 0.00150390 -10.70 2.53819000 91.4877 21.00 0.00497549 21.00 0.00723482 46.8114 34602.79 0.00 61585.54 61585.54 3.33919475 2.80 -1.50 0.00179941 7323.1 21.09 8.54 0.00179941 25766.4
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2231858.924 -999.000 86.393017 0.09494844 -999.000 -999.0000 1.00000 1.00000 1024.6584 1004.8586 1.2036 VAV_MID WITH REHEAT FAN Fan:VariableVolume 86.393017 103.98220154   4197.9300 999.8980 119.22322388 12.27 6.67 5.60 2802748.19 79.6311 79.631090 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 2231858.92 1640683.65 1.0000 103.98220154 86.393017 26.58 19.02 0.01066108 53896.1 10.95 10.95 0.00850000 32432.2 94.93875229 6.67 12.27 5.60 197298.135 2034560.79 32.10 0.01411964 23.13 25.38195000 29.3796 24.00 0.00904527 24.00 0.00904527 48.6318 1096515.53 0.00 2234964.44 1590148.74 103.98220154 26.58 19.03 0.01066108 53896.1 11.65 11.32 0.00820282 32402.3
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 717380.549 717380.549 25.917905 0.00627596 11389.177 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV_MID WITH REHEAT FAN Fan:VariableVolume 86.393017 103.98220154   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 25.0170 25.520483 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 06:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 717380.55 717380.55 1.0000 31.19466046 25.917905 -10.09 -10.09 0.00162101 -6110.9 12.80 11.59 0.00800000 33059.8 6.27531778 60.00 32.22 27.78 0.000 717380.55 -10.70 0.00150390 -10.70 25.38195000 97.9321 19.01 0.00716748 19.36 0.00673517 48.2504 452087.97 0.00 618605.12 618605.12 31.19466046 2.80 -1.78 0.00162101 6876.0 22.48 8.97 0.00162101 26706.5
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 228877.652 -999.000 9.323152 0.00973698 -999.000 -999.0000 1.00000 1.00000 1024.1593 1004.8586 1.2036 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.323152 11.22129892   4197.9300 999.8980 119.22322388 12.27 6.67 5.60 2802748.19 8.1662 8.166187 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 Sensible 228877.65 172927.70 1.0000 11.22129892 9.323152 26.20 18.69 0.01039257 52828.0 10.95 10.95 0.00850000 32431.3 9.73599115 6.67 12.27 5.60 21291.541 207586.11 32.10 0.01411964 23.13 2.53819000 27.2246 24.00 0.00899831 24.00 0.00899831 48.3831 128250.11 0.00 229181.57 166915.00 11.22129892 26.20 18.70 0.01039257 52828.0 11.68 11.32 0.00819291 32404.2
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 70617.113 70617.113 2.796946 0.00061779 1132.483 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.323152 11.22129892   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 2.4626 2.512171 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 05:20:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 70617.11 70617.11 1.0000 3.36638968 2.796946 -8.08 -8.08 0.00202180 -3088.7 12.80 11.59 0.00800000 33059.8 0.61772629 60.00 32.22 27.78 0.000 70617.11 -10.70 0.00150390 -10.70 2.53819000 90.7486 17.67 0.00710204 17.60 0.00668894 53.5319 50531.78 0.00 62256.55 62256.55 3.36638968 2.80 -1.15 0.00202180 7880.5 21.14 8.81 0.00202180 26374.0
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 112810.891 -999.000 5.280095 0.00479924 -999.000 -999.0000 1.00000 1.00000 1023.7042 1004.8586 1.2036 CAV_BAS FAN Fan:ConstantVolume 5.280095 6.35509641   4197.9300 999.8980 119.22322388 12.27 6.67 5.60 2802748.19 4.0250 4.025010 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:20:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 112810.89 85881.69 1.0000 6.35509641 5.280095 24.70 18.00 0.01014776 50668.8 11.42 11.42 0.00850000 32917.6 4.79874650 6.67 12.27 5.60 8953.217 103857.67 27.09 0.01411064 21.71 1.20015641 22.7298 24.00 0.00897685 24.00 0.00897685 48.2675 72388.71 0.00 112976.12 83034.10 6.35509641 24.70 18.01 0.01014776 50668.8 11.94 11.52 0.00828044 32891.6
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 270970.198 270970.198 5.280095 0.00237057 5947.014 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 CAV_BAS FAN Fan:ConstantVolume 5.280095 6.35509641   4197.9300 999.8980 24.58933829 54.44 82.22 27.78 2867571.63 9.4495 9.639640 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 270970.20 270970.20 1.0000 6.35509641 5.280095 -2.43 -5.10 0.00150390 1310.5 40.00 21.18 0.00800000 60796.0 2.37032367 60.00 32.22 27.78 0.000 270970.20 -10.70 0.00150390 -10.70 1.20015641 22.7298 0.00 0.00150390 23.62 0.00150390 8.3740 0.00 0.00 222940.97 222940.97 6.35509641 12.80 4.04 0.00150390 16658.9 47.61 18.58 0.00150390 51739.6
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 430959.384 311115.047 21.299925 0.01055417 -999.000 -999.0000 -999.00000 -999.00000 1020.8846 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 403378.75 395698.35 0.9360 -999.0 -999.0 28.48 18.04 0.00863100 50660.0 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 403378.75 32.10 0.01411964 23.13 0.33839277 -999.0000 27.00 0.00854230 27.00 0.00854230 38.4643 371069.83 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9507.008 6877.699 0.472311 0.00023283 -999.000 -999.0000 -999.00000 -999.00000 1021.1445 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 8890.19 8538.47 0.9351 -999.0 -999.0 28.04 18.00 0.00877081 50564.8 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8890.19 29.77 0.01411544 22.48 0.01563234 -999.0000 27.00 0.00858780 27.00 0.00858780 38.6641 8235.01 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 90854.157 65670.262 4.506359 0.00222501 -999.000 -999.0000 -999.00000 -999.00000 1021.1686 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 84982.06 81465.46 0.9354 -999.0 -999.0 28.03 18.01 0.00878376 50595.7 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 84982.06 29.58 0.01411511 22.43 0.15632344 -999.0000 27.00 0.00859217 27.00 0.00859217 38.6837 78598.84 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9256.470 6692.409 0.459345 0.00022669 -999.000 -999.0000 -999.00000 -999.00000 1021.1585 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 8657.54 8305.96 0.9353 -999.0 -999.0 28.04 18.01 0.00877833 50586.6 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8657.54 29.77 0.01411544 22.48 0.01563234 -999.0000 27.00 0.00859030 27.00 0.00859030 38.6753 8011.82 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 430959.384 430959.384 21.299925 0.01055417 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 430959.38 430959.38 1.0000 25.63648259 21.299925 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 430959.38 -10.70 0.00150390 -10.70 0.33839277 1.5887 0.00 0.00850000 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9507.008 9507.008 0.472311 0.00023283 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9507.01 9507.01 1.0000 0.56847161 0.472311 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9507.01 -10.70 0.00150390 -10.70 0.01563234 3.3098 0.00 0.00654062 25.77 0.00654062 31.7584 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 90854.157 90854.157 4.506359 0.00222501 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 90854.16 90854.16 1.0000 5.42383146 4.506359 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 90854.16 -10.70 0.00150390 -10.70 0.15632344 3.4690 0.00 0.00199518 23.83 0.00199518 10.9586 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9256.470 9256.470 0.459345 0.00022669 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2036 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9256.47 9256.47 1.0000 0.55286559 0.459345 -10.70 -10.70 0.00150390 -7020.5 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9256.47 -10.70 0.00150390 -10.70 0.01563234 3.4032 0.00 0.00199484 22.74 0.00199484 11.7052 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 20749.821 20749.821 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.299925 25.63648259   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 20749.82 20749.82 1.0000 25.63648259 21.299925 -0.17 -0.17 0.00838885 20806.6 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 20749.82 -10.70 0.00150390 -10.70 0.33839277 1.5887 0.00 0.00850000 27.00 0.00850000 38.2706 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 958.556 958.556 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.472311 0.56847161   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 958.56 958.56 1.0000 0.56847161 0.472311 -0.35 -0.35 0.00637392 15580.7 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 958.56 -10.70 0.00150390 -10.70 0.01563234 3.3098 0.00 0.00654062 25.77 0.00654062 31.7584 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9585.558 9585.558 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.506359 5.42383146   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9585.56 9585.56 1.0000 5.42383146 4.506359 -0.37 -3.04 0.00197814 4572.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9585.56 -10.70 0.00150390 -10.70 0.15632344 3.4690 0.00 0.00199518 23.83 0.00199518 10.9586 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 958.556 958.556 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2036 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.459345 0.55286559   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown NEW.YORK-JOHN.F.KENNEDY.INTL.AP_NY_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 958.56 958.56 1.0000 0.55286559 0.459345 -0.36 -3.03 0.00197813 4579.9 40.00 21.18 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 958.56 -10.70 0.00150390 -10.70 0.01563234 3.4032 0.00 0.00199484 22.74 0.00199484 11.7052 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 9.25 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 86.39 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 9.32 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 5.28 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 2931.67 1690.00 591.33
CORE_BOTTOM 2753.67 1272.00 0.00
CORE_MID 2309.00 2828.00 134.83
CORE_TOP 2759.33 3323.67 741.00
PERIMETER_BOT_ZN_3 2565.67 3031.67 346.67
PERIMETER_BOT_ZN_2 2692.33 3000.17 398.83
PERIMETER_BOT_ZN_1 2887.00 2588.33 396.50
PERIMETER_BOT_ZN_4 3189.17 1998.67 348.00
PERIMETER_MID_ZN_3 3462.83 3728.83 1713.50
PERIMETER_MID_ZN_2 2945.67 3082.33 1356.33
PERIMETER_MID_ZN_1 3226.83 3051.83 1027.67
PERIMETER_MID_ZN_4 3381.33 3416.00 1314.67
PERIMETER_TOP_ZN_3 3944.67 3920.67 2309.17
PERIMETER_TOP_ZN_2 3936.17 3720.83 2051.17
PERIMETER_TOP_ZN_1 3607.67 3391.83 1575.83
PERIMETER_TOP_ZN_4 3780.00 3661.67 1868.17
DATACENTER_BOT_ZN_6 5910.83 928.83 928.83
DATACENTER_MID_ZN_6 5438.17 245.17 171.17
DATACENTER_TOP_ZN_6 4912.33 619.00 375.00
DATACENTER_BASEMENT_ZN_6 5943.00 5609.67 5609.67
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5939.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 62.83 0.00 0.83
CORE_BOTTOM 0.00 2.33 0.00 0.00
CORE_MID 2.33 0.00 1.17 0.00
CORE_TOP 8.17 0.00 1.17 0.00
PERIMETER_BOT_ZN_3 0.67 1.33 0.00 0.67
PERIMETER_BOT_ZN_2 0.83 20.17 0.00 19.83
PERIMETER_BOT_ZN_1 1.00 31.17 0.00 28.33
PERIMETER_BOT_ZN_4 0.33 103.50 0.00 39.00
PERIMETER_MID_ZN_3 60.83 0.00 15.50 0.00
PERIMETER_MID_ZN_2 35.17 22.67 3.00 22.50
PERIMETER_MID_ZN_1 28.17 25.67 2.67 24.67
PERIMETER_MID_ZN_4 27.17 27.00 3.33 16.50
PERIMETER_TOP_ZN_3 178.50 3.83 52.33 3.00
PERIMETER_TOP_ZN_2 118.83 30.17 24.17 29.17
PERIMETER_TOP_ZN_1 94.67 27.17 13.33 25.33
PERIMETER_TOP_ZN_4 83.83 29.83 15.17 18.67
DATACENTER_BOT_ZN_6 0.00 7.83 0.00 7.83
DATACENTER_MID_ZN_6 0.00 7.33 0.00 7.33
DATACENTER_TOP_ZN_6 0.00 3.33 0.00 3.33
DATACENTER_BASEMENT_ZN_6 0.00 334.33 0.00 298.17
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 198.83 568.00 56.00 405.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.22 149.60 6779.02 1.094 0.000 0.000 0.000
CORE_BOTTOM 55.88 134.35 6849.35 0.802 0.000 0.000 0.000
CORE_MID 55.88 134.35 6849.35 0.639 0.000 0.000 0.000
CORE_TOP 55.88 134.35 6849.35 0.622 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.02 16.87 860.00 0.755 0.055 0.000 0.000
PERIMETER_BOT_ZN_2 4.52 10.87 554.22 1.039 0.057 0.000 0.000
PERIMETER_BOT_ZN_1 7.02 16.87 860.02 1.098 0.055 0.000 0.000
PERIMETER_BOT_ZN_4 4.52 10.87 554.22 1.533 0.057 0.000 0.000
PERIMETER_MID_ZN_3 7.02 16.87 860.00 0.663 0.129 0.000 0.000
PERIMETER_MID_ZN_2 3.95 10.87 554.22 0.956 0.142 0.000 0.000
PERIMETER_MID_ZN_1 7.02 16.87 860.02 1.014 0.129 0.000 0.000
PERIMETER_MID_ZN_4 4.52 10.87 554.22 1.099 0.133 0.000 0.000
PERIMETER_TOP_ZN_3 7.02 16.87 860.00 0.677 0.159 0.000 0.000
PERIMETER_TOP_ZN_2 4.52 10.87 554.22 1.040 0.165 0.000 0.000
PERIMETER_TOP_ZN_1 7.02 16.87 860.02 1.006 0.160 0.000 0.000
PERIMETER_TOP_ZN_4 4.52 10.87 554.22 1.123 0.165 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.54 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.22 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 55.88 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.95 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.02 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.52 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.02 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.52 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.54 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.22 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 55.88 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.95 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.02 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.02 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.52 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.54 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1031.21 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 45488677.95 0.00 45488677.95 0.00 45488677.95 37848132.68 4010.95 1399.75 3349.30 320.54
CORE_BOTTOM 33978958.79 0.00 33978958.79 0.00 33978958.79 33990283.35 5386.10 101.11 3272.78 331.05
CORE_MID 0.26E+09 0.00 0.26E+09 0.00 0.26E+09 0.34E+09 6433.93 241.77 2084.30 225.97
CORE_TOP 25461877.89 0.00 25461877.89 0.00 25461877.89 33990283.35 6847.91 38.58 1873.50 354.18
PERIMETER_BOT_ZN_3 4013838.38 0.00 4013838.38 542909.24 4556747.62 4267819.30 5386.81 70.34 3302.86 331.05
PERIMETER_BOT_ZN_2 3560798.69 0.00 3560798.69 361939.24 3922737.94 2750345.05 3851.00 42.45 4866.55 331.05
PERIMETER_BOT_ZN_1 5752387.95 0.00 5752387.95 542909.24 6295297.19 4267912.63 4312.60 104.38 4343.02 331.05
PERIMETER_BOT_ZN_4 5220914.47 0.00 5220914.47 361939.24 5582853.72 2750345.05 3723.36 4.89 5031.76 331.05
PERIMETER_MID_ZN_3 34233480.55 0.00 34233480.55 1273269.14 35506749.70 42678193.03 5617.06 254.33 2888.61 225.97
PERIMETER_MID_ZN_2 34213161.99 0.00 34213161.99 848845.52 35062007.50 27503450.52 4102.74 11.62 4645.63 1134.97
PERIMETER_MID_ZN_1 51851833.58 0.00 51851833.58 1273269.14 53125102.72 42679126.28 4204.29 65.45 4490.26 225.97
PERIMETER_MID_ZN_4 36487237.25 0.00 36487237.25 848845.52 37336082.76 27503450.52 4082.71 5.61 4671.68 225.97
PERIMETER_TOP_ZN_3 3486406.56 0.00 3486406.56 1580892.99 5067299.55 4267819.30 4607.30 1193.61 2959.09 354.18
PERIMETER_TOP_ZN_2 3438899.52 0.00 3438899.52 1053927.94 4492827.46 2750345.05 4161.75 7.96 4590.29 354.18
PERIMETER_TOP_ZN_1 5140343.53 0.00 5140343.53 1580892.99 6721236.52 4267912.63 4188.27 7.32 4564.41 354.18
PERIMETER_TOP_ZN_4 3718327.44 0.00 3718327.44 1053927.94 4772255.38 2750345.05 4135.98 4.53 4619.49 354.18
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.44E+10 0.00 0.44E+10 49521632.03 0.44E+10 0.50E+10 7184.22 4394.07 5202.94 1679.99


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 2.0170 0.0000 2.0170 0.0000 2.0170 1.2002 1379.66 1397.23 3166.11
CORE_BOTTOM 1.4955 0.0000 1.4955 0.0000 1.4955 1.0778 2832.19 98.69 3012.11
CORE_MID 11.9147 0.0000 11.9147 0.0000 11.9147 10.7782 3693.62 241.73 2007.66
CORE_TOP 1.1604 0.0000 1.1604 0.0000 1.1604 1.0778 4081.93 38.58 1822.49
PERIMETER_BOT_ZN_3 0.1768 0.0000 0.1768 0.0129 0.1897 0.1353 2827.63 67.92 3047.45
PERIMETER_BOT_ZN_2 0.1570 0.0000 0.1570 0.0086 0.1656 0.0872 1335.26 40.35 4567.39
PERIMETER_BOT_ZN_1 0.2574 0.0000 0.2574 0.0129 0.2703 0.1353 1759.74 102.33 4080.92
PERIMETER_BOT_ZN_4 0.2313 0.0000 0.2313 0.0086 0.2399 0.0872 1222.95 3.76 4716.29
PERIMETER_MID_ZN_3 1.5544 0.0000 1.5544 0.0303 1.5848 1.3533 2879.96 253.97 2809.07
PERIMETER_MID_ZN_2 1.4450 0.0000 1.4450 0.0215 1.4665 0.8721 1368.04 6.13 3659.83
PERIMETER_MID_ZN_1 2.3759 0.0000 2.3759 0.0303 2.4062 1.3533 1468.73 65.00 4409.27
PERIMETER_MID_ZN_4 1.6612 0.0000 1.6612 0.0202 1.6814 0.8721 1358.30 3.79 4580.91
PERIMETER_TOP_ZN_3 0.1589 0.0000 0.1589 0.0377 0.1966 0.1353 1844.78 1193.13 2905.09
PERIMETER_TOP_ZN_2 0.1572 0.0000 0.1572 0.0251 0.1823 0.0872 1406.36 7.10 4529.54
PERIMETER_TOP_ZN_1 0.2359 0.0000 0.2359 0.0377 0.2736 0.1353 1426.41 6.64 4509.95
PERIMETER_TOP_ZN_4 0.1698 0.0000 0.1698 0.0251 0.1949 0.0872 1387.47 3.35 4552.18
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 197.1415 0.0000 197.1415 1.1927 198.3342 158.4706 4367.22 4376.09 4781.45


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 76098470.79 0.00 76098470.79 48026705.38 3743.90 5.27 5010.83 331.05
VAV_MID WITH REHEAT 0.61E+09 0.00 0.61E+09 0.48E+09 4071.73 9.07 4679.21 225.97
VAV_TOP WITH REHEAT 59746121.60 0.00 59746121.60 48026705.38 4140.14 4.88 4614.98 354.18
CAV_BAS 65896758.45 0.00 65896758.45 37848132.68 3934.47 3.21 4822.31 320.54
AIRLOOP DATACENTER BASEMENT 7660799.48 0.00 7660799.48 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 353897.20 0.00 353897.20 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3538971.99 0.00 3538971.99 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 353897.20 0.00 353897.20 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.3581 0.0000 3.3581 1.5229 1238.40 4.02 4700.57
VAV_MID WITH REHEAT 27.6153 0.0000 27.6153 15.2292 1349.41 5.35 4588.24
VAV_TOP WITH REHEAT 2.7265 0.0000 2.7265 1.5229 1388.02 2.81 4552.17
CAV_BAS 2.9219 0.0000 2.9219 1.2002 1351.79 0.66 4590.55
AIRLOOP DATACENTER BASEMENT 0.3581 0.0000 0.3581 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1654 0.0000 0.1654 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.87 3079.62 0.00 0.00 0.00 1999.03 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.69 2658.52 0.00 0.00 0.00 2269.33 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 1.17 2428.34 0.00 0.00 0.00 2665.81 0.00 0.00 0.00
CAV_BAS 0.00 1387.89 3543.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 5.5122 0.0000 0.0000 0.0000 2.4001 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 45.3740 0.0000 0.0000 0.0000 23.6591 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 15.7569 4.7911 0.0000 0.0000 0.0000 2.3456 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.7397 4.6390 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4903 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0227 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2265 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0227 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1386
Defaulted Fields 1179
Fields with Defaults 3922
Autosized Fields 333
Autosizable Fields 412
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
Electricity:Building 17959.14 247233.96 01-JAN-08:30 1055078.17 01-DEC-16:30
Electricity:Zone:BASEMENT 602.14 14319.77 01-JAN-00:10 28977.00 02-JAN-08:10
Electricity:SpaceType:GENERAL 17959.14 247233.96 01-JAN-08:30 1055078.17 01-DEC-16:30
InteriorLights:Electricity 2745.73 13024.70 01-JAN-08:30 261074.09 02-JAN-16:40
InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2745.73 13024.70 01-JAN-08:30 261074.09 02-JAN-16:40
LightsWired:InteriorLights:Electricity 2745.73 13024.70 01-JAN-08:30 261074.09 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2745.73 13024.70 01-JAN-08:30 261074.09 02-JAN-16:40
Electricity:Zone:CORE_BOTTOM 480.91 6817.20 01-JAN-00:10 32066.15 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:CORE_MID 4809.09 68171.81 01-JAN-00:10 320660.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
Electricity:Zone:CORE_TOP 480.91 6817.18 01-JAN-00:10 32066.08 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 54.23 818.50 01-JAN-08:30 4026.32 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.89 59.73 01-JAN-08:30 1750.00 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.89 59.73 01-JAN-08:30 1750.00 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_2 34.94 527.47 01-JAN-07:50 2594.71 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.95 38.49 01-JAN-07:50 1127.77 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.95 38.49 01-JAN-07:50 1127.77 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_1 54.14 818.51 01-JAN-07:50 4026.39 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.80 59.73 01-JAN-07:50 1750.04 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.80 59.73 01-JAN-07:50 1750.04 02-JAN-16:40
Electricity:Zone:PERIMETER_BOT_ZN_4 34.90 527.47 01-JAN-08:30 2594.70 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.90 38.49 01-JAN-08:30 1127.77 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.90 38.49 01-JAN-08:30 1127.77 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_3 542.46 8184.99 01-JAN-08:30 40263.18 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 139.03 597.26 01-JAN-08:30 17500.00 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 139.03 597.26 01-JAN-08:30 17500.00 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_2 349.47 5274.72 01-JAN-07:50 25947.12 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 89.49 384.90 01-JAN-07:50 11277.66 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 89.49 384.90 01-JAN-07:50 11277.66 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_1 541.47 8185.12 01-JAN-08:00 40263.91 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 138.04 597.27 01-JAN-08:00 17500.38 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 138.04 597.27 01-JAN-08:00 17500.38 02-JAN-16:40
Electricity:Zone:PERIMETER_MID_ZN_4 349.03 5274.69 01-JAN-08:30 25947.03 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 89.05 384.90 01-JAN-08:30 11277.66 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 89.05 384.90 01-JAN-08:30 11277.66 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_3 54.25 818.50 01-JAN-08:30 4026.32 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.90 59.73 01-JAN-08:30 1750.00 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.90 59.73 01-JAN-08:30 1750.00 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_2 34.95 527.47 01-JAN-07:50 2594.71 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.95 38.49 01-JAN-07:50 1127.77 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.95 38.49 01-JAN-07:50 1127.77 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_1 54.15 818.51 01-JAN-08:00 4026.39 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.80 59.73 01-JAN-08:00 1750.04 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.80 59.73 01-JAN-08:00 1750.04 02-JAN-16:40
Electricity:Zone:PERIMETER_TOP_ZN_4 34.90 527.47 01-JAN-08:30 2594.70 02-JAN-16:40
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.91 38.49 01-JAN-08:30 1127.77 02-JAN-16:40
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.91 38.49 01-JAN-08:30 1127.77 02-JAN-16:40
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7544.97 95151.24 01-JAN-00:10 384008.34 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1585.20 19711.13 01-JAN-00:10 81995.25 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 2708.40 5450.30 02-JAN-05:20 434328.31 22-AUG-14:40
HeatRejection:Electricity 1130.44 1866.13 02-JAN-07:20 90459.19 09-JUL-08:10
General:HeatRejection:Electricity 1130.44 1866.13 02-JAN-07:20 90459.19 09-JUL-08:10
Electricity:HVAC 4922.23 72083.80 01-JAN-24:00 462798.97 22-AUG-14:40
ExteriorEquipment:Electricity 1914.38 28294.68 01-JAN-00:10 117200.89 03-JAN-08:20
Transformer:ExteriorEquipment:Electricity 59.77 1112.61 01-JAN-00:10 3726.76 01-DEC-16:40
ElectricityPurchased:Facility 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
ElectricityPurchased:Plant 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
Cogeneration:ElectricityPurchased 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
General:Cogeneration:ElectricityPurchased 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
ElectricityNet:Plant 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
Cogeneration:ElectricityNet 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
General:Cogeneration:ElectricityNet 27893.64 359665.34 01-JAN-14:00 1959609.74 22-AUG-14:40
Fans:Electricity 2283.57 41405.87 02-JAN-22:30 283348.35 22-AUG-14:40
General:Fans:Electricity 2283.57 41405.87 02-JAN-22:30 283348.35 22-AUG-14:40
ExteriorLights:Electricity 449.24 0.00 01-JAN-07:30 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 449.24 0.00 01-JAN-07:30 37611.08 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 48.90 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
General:HeatRecovery:Electricity 48.90 0.00 01-JAN-00:10 5613.48 02-JAN-07:10
Cooling:Electricity 3472.96 26163.57 02-JAN-07:20 448279.91 04-AUG-14:00
General:Cooling:Electricity 3472.96 26163.57 02-JAN-07:20 448279.91 04-AUG-14:00
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 14.23 0.00 01-JAN-00:10 6185.89 02-JAN-20:00
General:Humidifier:Electricity 14.23 0.00 01-JAN-00:10 6185.89 02-JAN-20:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 620.77 3376.53 01-JAN-00:40 75732.46 30-AUG-13:50
General:Pumps:Electricity 620.77 3376.53 01-JAN-00:40 75732.46 30-AUG-13:50
WIRED_LTG_ELECTRICITY 77.15 0.00 01-JAN-00:10 7336.18 02-JAN-16:50
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 1828.42 5695.87 13-AUG-15:00 1752188.17 02-JAN-05:10
NaturalGas:Plant 1828.42 5695.87 13-AUG-15:00 1752188.17 02-JAN-05:10
Heating:NaturalGas 1121.52 0.00 01-JAN-00:40 1746492.30 02-JAN-05:10
Boiler:Heating:NaturalGas 1121.52 0.00 01-JAN-00:40 1746492.30 02-JAN-05:10
WaterSystems:NaturalGas 706.90 5695.87 02-JAN-06:10 82525.26 08-FEB-12:40
Water Heater:WaterSystems:NaturalGas 706.90 5695.87 02-JAN-06:10 82525.26 08-FEB-12:40


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 18841.29 130485.59 02-JAN-07:20 2662047.41 22-AUG-14:40
PlantLoopCoolingDemand:HVAC 18841.29 130485.59 02-JAN-07:20 2662047.41 22-AUG-14:40
CoolingCoils:PlantLoopCoolingDemand 18841.29 130485.59 02-JAN-07:20 2662047.41 22-AUG-14:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 7251.98 0.00 01-JAN-00:10 0.00 30-AUG-15:50
Water:HVAC 5.29 0.00 01-JAN-00:10 0.00 02-JAN-20:00
Humidifier:Water 5.29 0.00 01-JAN-00:10 0.00 02-JAN-20:00
General:Humidifier:Water 5.29 0.00 01-JAN-00:10 0.00 02-JAN-20:00
MainsWater:Facility 7251.98 0.00 01-JAN-00:10 0.00 30-AUG-15:50
MainsWater:HVAC 5.29 0.00 01-JAN-00:10 0.00 02-JAN-20:00
Humidifier:MainsWater 5.29 0.00 01-JAN-00:10 0.00 02-JAN-20:00
General:Humidifier:MainsWater 5.29 0.00 01-JAN-00:10 0.00 02-JAN-20:00
Water:Plant 7246.69 0.00 01-JAN-00:10 0.00 30-AUG-15:50
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 7246.69 0.00 01-JAN-00:10 0.00 30-AUG-15:50
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 4966.52 0.00 01-JAN-00:10 0.00 30-AUG-15:50
General:HeatRejection:Water 4966.52 0.00 01-JAN-00:10 0.00 30-AUG-15:50
HeatRejection:MainsWater 4966.52 0.00 01-JAN-00:10 0.00 30-AUG-15:50
General:HeatRejection:MainsWater 4966.52 0.00 01-JAN-00:10 0.00 30-AUG-15:50


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 58429.05 209852.27 02-JAN-06:00 10607950.59 22-AUG-14:40
EnergyTransfer:Building 18411.43 88478.70 28-JAN-18:20 1602770.89 18-AUG-15:00
EnergyTransfer:Zone:BASEMENT 640.80 0.00 01-JAN-00:10 70094.23 13-NOV-06:10
Heating:EnergyTransfer 610.15 0.00 19-JAN-22:10 1374424.63 02-JAN-05:10
Heating:EnergyTransfer:Zone:BASEMENT 3.19 0.00 01-JAN-00:10 11793.43 12-AUG-16:10
General:Heating:EnergyTransfer 610.15 0.00 19-JAN-22:10 1374424.63 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:BASEMENT 3.19 0.00 01-JAN-00:10 11793.43 12-AUG-16:10
Cooling:EnergyTransfer 17801.28 84269.82 02-JAN-04:40 1602770.89 18-AUG-15:00
Cooling:EnergyTransfer:Zone:BASEMENT 637.61 0.00 01-JAN-00:10 70094.23 13-NOV-06:10
General:Cooling:EnergyTransfer 17801.28 84269.82 02-JAN-04:40 1602770.89 18-AUG-15:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 637.61 0.00 01-JAN-00:10 70094.23 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 605.63 0.00 01-JAN-00:10 52350.18 14-AUG-09:40
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 605.63 0.00 01-JAN-00:10 52350.18 14-AUG-09:40
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 605.63 0.00 01-JAN-00:10 52350.18 14-AUG-09:40
EnergyTransfer:Zone:CORE_MID 4285.41 0.00 01-JAN-00:40 482418.23 02-JAN-05:30
Heating:EnergyTransfer:Zone:CORE_MID 11.63 0.00 01-JAN-00:20 482418.23 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:CORE_MID 11.63 0.00 01-JAN-00:20 482418.23 02-JAN-05:30
Cooling:EnergyTransfer:Zone:CORE_MID 4273.77 0.00 01-JAN-00:40 451679.06 11-JUL-14:30
General:Cooling:EnergyTransfer:Zone:CORE_MID 4273.77 0.00 01-JAN-00:40 451679.06 11-JUL-14:30
EnergyTransfer:Zone:CORE_TOP 407.63 0.00 01-JAN-00:40 70289.10 02-JAN-05:30
Heating:EnergyTransfer:Zone:CORE_TOP 11.79 0.00 01-JAN-00:40 70289.10 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:CORE_TOP 11.79 0.00 01-JAN-00:40 70289.10 02-JAN-05:30
Cooling:EnergyTransfer:Zone:CORE_TOP 395.85 0.00 01-JAN-00:10 51717.57 11-JUL-14:20
General:Cooling:EnergyTransfer:Zone:CORE_TOP 395.85 0.00 01-JAN-00:10 51717.57 11-JUL-14:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 71.22 0.00 01-JAN-00:10 10372.95 19-JUN-14:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.60 0.00 01-JAN-00:10 8464.87 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.60 0.00 01-JAN-00:10 8464.87 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 70.62 0.00 01-JAN-00:10 10372.95 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 70.62 0.00 01-JAN-00:10 10372.95 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 60.51 0.00 01-JAN-00:10 12166.53 26-JUN-08:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.41 0.00 01-JAN-00:10 5871.11 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.41 0.00 01-JAN-00:10 5871.11 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 60.11 0.00 01-JAN-00:10 12166.53 26-JUN-08:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 60.11 0.00 01-JAN-00:10 12166.53 26-JUN-08:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 100.47 0.00 01-JAN-00:10 17682.17 04-OCT-12:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.78 0.00 01-JAN-00:10 10027.91 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.78 0.00 01-JAN-00:10 10027.91 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 99.69 0.00 01-JAN-00:10 17682.17 04-OCT-12:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 99.69 0.00 01-JAN-00:10 17682.17 04-OCT-12:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 94.99 0.00 01-JAN-00:10 16614.94 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.06 0.00 01-JAN-00:10 4179.15 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.06 0.00 01-JAN-00:10 4179.15 02-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 94.93 0.00 01-JAN-00:10 16614.94 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 94.93 0.00 01-JAN-00:10 16614.94 15-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 597.46 0.00 01-JAN-00:40 128892.13 06-FEB-04:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 124.67 0.00 01-JAN-00:40 128892.13 06-FEB-04:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 124.67 0.00 01-JAN-00:40 128892.13 06-FEB-04:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 472.79 0.00 01-JAN-00:10 96672.52 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 472.79 0.00 01-JAN-00:10 96672.52 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 545.43 0.00 01-JAN-00:40 135515.66 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 66.15 0.00 01-JAN-00:40 135515.66 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 66.15 0.00 01-JAN-00:40 135515.66 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 479.28 0.00 01-JAN-00:10 128283.74 14-JUL-08:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 479.28 0.00 01-JAN-00:10 128283.74 14-JUL-08:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 875.73 0.00 01-JAN-00:40 177803.15 28-SEP-13:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 65.28 0.00 01-JAN-00:40 162913.66 02-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 65.28 0.00 01-JAN-00:40 162913.66 02-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 810.45 0.00 01-JAN-00:10 177803.15 28-SEP-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 810.45 0.00 01-JAN-00:10 177803.15 28-SEP-13:20
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 583.86 0.00 01-JAN-00:40 139443.55 15-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 51.44 0.00 01-JAN-00:40 130261.42 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 51.44 0.00 01-JAN-00:40 130261.42 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 532.42 0.00 01-JAN-00:10 139443.55 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 532.42 0.00 01-JAN-00:10 139443.55 15-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 76.04 0.00 01-JAN-00:40 15979.19 06-FEB-01:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 30.77 0.00 01-JAN-00:40 15979.19 06-FEB-01:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 30.77 0.00 01-JAN-00:40 15979.19 06-FEB-01:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.26 0.00 01-JAN-00:10 11094.55 19-JUN-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 45.26 0.00 01-JAN-00:10 11094.55 19-JUN-14:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 62.96 0.00 01-JAN-00:40 15338.64 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 16.50 0.00 01-JAN-00:40 15338.64 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 16.50 0.00 01-JAN-00:40 15338.64 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 46.46 0.00 01-JAN-00:10 13136.93 14-JUL-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 46.46 0.00 01-JAN-00:10 13136.93 14-JUL-09:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 95.16 0.00 01-JAN-00:40 19314.22 06-FEB-04:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 18.60 0.00 01-JAN-00:40 19314.22 06-FEB-04:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 18.60 0.00 01-JAN-00:40 19314.22 06-FEB-04:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 76.56 0.00 01-JAN-00:10 19085.45 28-SEP-13:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 76.56 0.00 01-JAN-00:10 19085.45 28-SEP-13:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 64.78 0.00 01-JAN-00:40 16357.61 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 13.31 0.00 01-JAN-00:40 16357.61 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 13.31 0.00 01-JAN-00:40 16357.61 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 51.47 0.00 01-JAN-00:10 14648.77 15-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 51.47 0.00 01-JAN-00:10 14648.77 15-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 57.82 0.00 01-JAN-00:10 9808.16 14-AUG-14:50
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.10 0.00 01-JAN-00:10 5134.98 02-JAN-11:50
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 4.10 0.00 01-JAN-00:10 5134.98 02-JAN-11:50
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 53.72 0.00 01-JAN-00:10 9808.16 14-AUG-14:50
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 53.72 0.00 01-JAN-00:10 9808.16 14-AUG-14:50
EnergyTransfer:Zone:MIDFLOOR_PLENUM 497.14 0.00 01-JAN-00:40 186451.43 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 141.68 0.00 01-JAN-00:40 186451.43 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 141.68 0.00 01-JAN-00:40 186451.43 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 355.46 0.00 01-JAN-00:10 78302.56 10-JUL-15:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 355.46 0.00 01-JAN-00:10 78302.56 10-JUL-15:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 102.88 0.00 01-JAN-00:40 28502.46 06-FEB-05:20
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 43.82 0.00 01-JAN-00:40 28502.46 06-FEB-05:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 43.82 0.00 01-JAN-00:40 28502.46 06-FEB-05:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 59.07 0.00 01-JAN-00:10 21693.77 19-JUN-13:50
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 59.07 0.00 01-JAN-00:10 21693.77 19-JUN-13:50
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 137.02 6.42 01-JAN-19:40 8071.72 23-APR-17:50
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.01 0.00 01-JAN-10:20 182.82 01-JAN-20:20
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.01 0.00 01-JAN-10:20 182.82 01-JAN-20:20
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 137.02 0.00 01-JAN-00:10 8071.72 23-APR-17:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 137.02 0.00 01-JAN-00:10 8071.72 23-APR-17:50
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1178.87 5.42 24-JAN-02:00 76053.88 31-AUG-17:30
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 4.57 0.00 02-JAN-07:10 5495.86 16-JAN-18:00
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 4.57 0.00 02-JAN-07:10 5495.86 16-JAN-18:00
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1174.30 0.00 01-JAN-00:10 76053.88 31-AUG-17:30
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1174.30 0.00 01-JAN-00:10 76053.88 31-AUG-17:30
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 109.10 0.41 30-JAN-20:10 7749.74 13-AUG-17:40
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.80 0.00 02-JAN-07:10 578.08 29-JAN-17:50
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.80 0.00 02-JAN-07:10 578.08 29-JAN-17:50
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 108.30 0.00 01-JAN-00:10 7749.74 13-AUG-17:40
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 108.30 0.00 01-JAN-00:10 7749.74 13-AUG-17:40
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7160.52 84259.08 02-JAN-05:00 369448.28 18-AUG-23:10
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7160.52 84259.08 02-JAN-05:00 369448.28 18-AUG-23:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7160.52 84259.08 02-JAN-05:00 369448.28 18-AUG-23:10
PlantLoopHeatingDemand:Facility 1207.67 0.00 01-JAN-00:40 1406554.83 02-JAN-06:20
PlantLoopHeatingDemand:Plant 411.41 0.00 01-JAN-00:10 52106.89 08-FEB-12:20
WaterSystems:PlantLoopHeatingDemand 411.41 0.00 01-JAN-00:10 52106.89 08-FEB-12:20
General:WaterSystems:PlantLoopHeatingDemand 411.41 0.00 01-JAN-00:10 52106.89 08-FEB-12:20
EnergyTransfer:HVAC 18509.22 119979.39 02-JAN-05:20 2686687.98 04-AUG-14:00
HeatingCoils:EnergyTransfer 796.26 0.00 01-JAN-00:40 1400301.67 02-JAN-06:20
PlantLoopHeatingDemand:HVAC 796.26 0.00 01-JAN-00:40 1400301.67 02-JAN-06:20
HeatingCoils:PlantLoopHeatingDemand 796.26 0.00 01-JAN-00:40 1400301.67 02-JAN-06:20
CoolingCoils:EnergyTransfer 16325.53 104322.02 02-JAN-07:20 2490050.71 22-AUG-14:40
HeatRecoveryForHeating:EnergyTransfer 916.94 0.00 01-JAN-00:10 587487.32 06-FEB-07:10
HeatRecoveryForCooling:EnergyTransfer 470.49 0.00 01-JAN-00:10 513257.78 08-JUL-12:00
EnergyTransfer:Plant 21508.40 0.00 01-JAN-00:40 6437908.63 22-AUG-14:40
LoopToLoop:EnergyTransfer 6851.56 -604.51 17-JAN-12:30 2026215.67 22-AUG-14:40
WaterSystems:EnergyTransfer 411.41 0.00 01-JAN-00:10 52106.89 08-FEB-12:20
WaterUse:WaterSystems:EnergyTransfer 411.41 0.00 01-JAN-00:10 52106.89 08-FEB-12:20
Boilers:EnergyTransfer 792.24 0.00 01-JAN-00:40 1455697.43 02-JAN-05:10
Chillers:EnergyTransfer 6248.00 0.00 01-JAN-00:10 2028449.81 22-AUG-14:40
HeatRejection:EnergyTransfer 7205.20 0.00 01-JAN-00:10 2301620.47 22-AUG-14:40
General:HeatRejection:EnergyTransfer 7205.20 0.00 01-JAN-00:10 2301620.47 22-AUG-14:40
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 3.188 -637.611 0.000 0.000 92.852 177.742 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -60.568
CORE_BOTTOM 0.000 0.000 0.000 -605.624 0.000 0.000 83.541 159.625 321.286 0.000 0.000 0.000 41.173 0.000 0.000 0.000 0.000 -0.001
CORE_MID 0.000 0.000 11.634 -4273.759 0.000 0.000 855.231 1596.246 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -1402.197
CORE_TOP 0.000 0.000 11.787 -395.843 0.000 0.000 88.255 159.625 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -185.107
PERIMETER_BOT_ZN_3 0.000 0.000 0.599 -70.623 0.000 0.000 10.886 13.890 40.342 23.885 0.000 0.118 35.675 0.000 -46.279 0.000 -8.494 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.405 -60.107 0.000 0.000 7.023 8.946 25.998 43.864 0.000 0.083 7.764 0.000 -28.380 0.000 -5.596 0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.775 -99.693 0.000 0.000 10.755 13.797 40.343 89.678 0.000 0.112 0.001 0.000 -42.069 0.000 -8.547 -5.150
PERIMETER_BOT_ZN_4 0.000 0.000 0.062 -94.926 0.000 0.000 6.869 8.902 25.998 43.691 0.000 0.070 48.415 0.000 -32.853 0.000 -6.228 0.000
PERIMETER_MID_ZN_3 0.000 0.000 124.675 -472.782 0.000 0.000 113.734 139.033 403.423 247.260 0.000 2.625 25.577 0.000 -409.745 0.000 -173.799 -0.006
PERIMETER_MID_ZN_2 0.000 0.000 66.151 -479.270 0.000 0.000 53.463 89.489 259.981 440.922 0.000 1.672 0.010 0.000 -259.878 0.000 -118.217 -54.314
PERIMETER_MID_ZN_1 0.000 0.000 65.279 -810.445 0.000 0.000 109.696 138.037 403.429 896.444 0.000 2.434 0.000 0.000 -397.718 0.000 -185.975 -221.181
PERIMETER_MID_ZN_4 0.000 0.000 51.443 -532.415 0.000 0.000 72.698 89.051 259.979 447.601 0.000 1.649 9.481 0.000 -277.245 0.000 -122.243 -0.003
PERIMETER_TOP_ZN_3 0.000 0.000 30.773 -45.263 0.000 0.000 11.514 13.903 40.342 25.043 0.000 0.302 0.000 0.000 -38.461 0.000 -20.327 -17.826
PERIMETER_TOP_ZN_2 0.000 0.000 16.505 -46.457 0.000 0.000 7.339 8.949 25.998 44.348 0.000 0.196 0.000 0.000 -24.500 0.000 -13.870 -18.508
PERIMETER_TOP_ZN_1 0.000 0.000 18.604 -76.556 0.000 0.000 11.158 13.804 40.343 90.095 0.000 0.289 0.001 0.000 -37.316 0.000 -21.646 -38.773
PERIMETER_TOP_ZN_4 0.000 0.000 13.309 -51.471 0.000 0.000 7.365 8.905 25.998 44.913 0.000 0.196 0.000 0.000 -26.237 0.000 -14.365 -8.613
DATACENTER_BOT_ZN_6 0.000 0.000 0.007 -137.017 0.000 0.000 0.950 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -22.460
DATACENTER_MID_ZN_6 0.000 0.000 4.568 -1174.300 0.000 0.000 9.512 46.396 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -424.981
DATACENTER_TOP_ZN_6 0.000 0.000 0.801 -108.300 0.000 0.000 0.954 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -51.975
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7160.526 0.000 0.000 20.327 50.116 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -404.774
GROUNDFLOOR_PLENUM 4.096 -53.721 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.197 67.673 0.000 0.000 0.000 -18.245 0.000
MIDFLOOR_PLENUM 141.683 -355.460 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 3.530 511.843 0.000 0.000 0.000 -301.596 -0.000
TOPFLOOR_PLENUM 43.816 -59.066 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.283 46.599 0.000 0.000 0.000 -31.632 -0.000
Total Facility 189.595 -468.247 420.564 -17332.988 0.000 0.000 1574.122 2745.734 15213.411 2437.742 0.000 13.756 794.213 0.000 -1620.681 0.000 -1050.779 -2916.438


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 26-DEC-04:01 0.00 0.00 0.00 -108545.55 0.00 0.00 0.00 862.23 13457.54 0.00 0.00 0.00 94225.78 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 13-NOV-04:02 0.00 0.00 0.00 -91665.16 0.00 0.00 0.00 774.34 8057.15 0.00 0.00 0.00 82833.67 0.00 -0.00 0.00 0.00 0.00
CORE_MID 07-AUG-03:02 0.00 0.00 0.00 -862675.97 0.00 0.00 0.00 7743.41 80571.20 0.00 0.00 0.00 774361.36 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 07-AUG-03:02 0.00 0.00 0.00 -88961.98 0.00 0.00 0.00 774.34 8057.12 0.00 0.00 0.00 80130.52 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 13-AUG-16:21 0.00 0.00 0.00 -15991.11 0.00 0.00 43.05 59.73 758.77 2790.82 0.00 74.63 12264.12 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 29-MAY-08:22 0.00 0.00 0.00 -18181.64 0.00 0.00 22.06 38.49 488.98 14277.01 0.00 0.00 3387.42 0.00 -0.00 0.00 -32.33 0.00
PERIMETER_BOT_ZN_1 13-AUG-13:02 0.00 0.00 0.00 -23321.16 0.00 0.00 35.98 59.73 758.78 13666.20 0.00 83.01 8717.46 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 13-AUG-16:21 0.00 0.00 0.00 -25790.51 0.00 0.00 18.49 38.49 488.98 9830.92 0.00 7.97 15405.66 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 10-JUL-03:02 0.00 0.00 0.00 -138092.49 0.00 0.00 0.00 972.26 10116.97 0.00 0.00 159.44 128853.12 0.00 -2009.30 0.00 0.00 0.00
PERIMETER_MID_ZN_2 02-JUL-09:01 0.00 0.00 0.00 -212826.16 0.00 0.00 211.27 384.90 4889.82 131031.12 0.00 0.00 77552.26 0.00 -0.00 0.00 -1243.20 0.00
PERIMETER_MID_ZN_1 04-SEP-11:52 0.00 0.00 0.00 -237443.99 0.00 0.00 340.93 597.27 7587.84 180224.90 0.00 0.00 50264.47 0.00 -0.00 0.00 -1571.42 0.00
PERIMETER_MID_ZN_4 10-SEP-16:02 0.00 0.00 0.00 -211602.79 0.00 0.00 220.63 384.90 4889.79 146505.81 0.00 0.00 62893.81 0.00 -0.00 0.00 -3292.14 0.00
PERIMETER_TOP_ZN_3 09-JUL-15:21 0.00 0.00 0.00 -18156.76 0.00 0.00 41.20 59.73 758.77 4629.91 0.00 0.00 12705.87 0.00 -0.00 0.00 -38.72 0.00
PERIMETER_TOP_ZN_2 29-MAY-08:52 0.00 0.00 0.00 -21299.15 0.00 0.00 21.60 38.49 488.98 13073.42 0.00 0.00 7812.46 0.00 -0.00 0.00 -135.81 0.00
PERIMETER_TOP_ZN_1 04-SEP-11:52 0.00 0.00 0.00 -26182.83 0.00 0.00 33.51 59.73 758.78 17944.70 0.00 0.00 7589.57 0.00 -0.00 0.00 -203.46 0.00
PERIMETER_TOP_ZN_4 09-JUL-15:21 0.00 0.00 0.00 -22939.54 0.00 0.00 21.42 38.49 488.98 9441.54 0.00 0.00 13043.40 0.00 -0.00 0.00 -94.28 0.00
DATACENTER_BOT_ZN_6 23-APR-17:45 0.00 0.00 0.00 -8071.72 0.00 0.00 0.00 22.51 7794.42 0.00 0.00 0.00 254.79 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 31-AUG-17:30 0.00 0.00 0.00 -76052.66 0.00 0.00 105.14 1350.33 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3347.04
DATACENTER_TOP_ZN_6 13-AUG-17:40 0.00 0.00 0.00 -7750.83 0.00 0.00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -66.10
DATACENTER_BASEMENT_ZN_6 18-AUG-23:15 0.00 0.00 0.00 -369559.35 0.00 0.00 0.00 243.11 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -10316.28
GROUNDFLOOR_PLENUM 14-AUG-05:15 0.00 -13505.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13531.69 0.00 -0.00 0.00 -26.52 0.00
MIDFLOOR_PLENUM 07-AUG-05:15 0.00 -95836.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 97183.09 0.00 -0.00 0.00 -1347.07 0.00
TOPFLOOR_PLENUM 19-JUN-13:50 0.00 -21692.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 274.89 21418.01 0.00 -0.00 0.00 0.00 0.00
Total Facility 23-AUG-05:02 0.00 -17071.95 0.00 -1962550.06 0.00 0.00 16028.24 29009.37 623236.89 0.00 0.00 0.00 1371234.60 0.00 -56225.88 0.00 -3661.19 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 12-AUG-16:02 0.00 0.00 13017.65 0.00 0.00 0.00 520.12 862.23 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -27857.55
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID 02-JAN-04:01 0.00 0.00 554995.36 0.00 0.00 0.00 0.00 7743.41 80571.20 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -643309.96
CORE_TOP 02-JAN-04:01 0.00 0.00 79287.83 0.00 0.00 0.00 0.00 774.34 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -88119.29
PERIMETER_BOT_ZN_3 06-FEB-05:01 0.00 0.00 12302.13 0.00 0.00 0.00 0.00 194.45 1011.70 0.00 0.00 0.00 0.00 0.00 -5418.45 0.00 -2040.38 -6049.45
PERIMETER_BOT_ZN_2 06-FEB-05:01 0.00 0.00 11582.08 0.00 0.00 0.00 0.00 125.31 651.98 0.00 0.00 0.00 0.00 0.00 -3511.53 0.00 -1368.56 -7479.28
PERIMETER_BOT_ZN_1 02-JAN-04:01 0.00 0.00 17511.71 0.00 0.00 0.00 0.00 97.23 1011.71 0.00 0.00 0.00 0.00 0.00 -4725.55 0.00 -621.97 -13273.13
PERIMETER_BOT_ZN_4 02-JAN-05:01 0.00 0.00 10002.31 0.00 0.00 0.00 0.00 125.31 651.97 0.00 0.00 0.00 0.00 0.00 -3441.23 0.00 -473.08 -6865.28
PERIMETER_MID_ZN_3 01-JAN-15:22 0.00 0.00 137567.29 0.00 0.00 0.00 896.59 700.70 7587.73 0.00 0.00 0.00 0.00 0.00 -21644.56 0.00 -27955.20 -97152.55
PERIMETER_MID_ZN_2 02-JAN-00:02 0.00 0.00 166334.29 0.00 0.00 0.00 0.00 626.56 6519.76 0.00 0.00 0.00 0.00 0.00 -27679.96 0.00 -28512.61 -117288.04
PERIMETER_MID_ZN_1 02-JAN-00:02 0.00 0.00 188171.50 0.00 0.00 0.00 0.00 972.28 10117.12 0.00 0.00 0.00 0.00 0.00 -41959.12 0.00 -42558.63 -114743.15
PERIMETER_MID_ZN_4 02-JAN-00:02 0.00 0.00 172071.61 0.00 0.00 0.00 0.00 626.56 6519.72 0.00 0.00 0.00 0.00 0.00 -28809.19 0.00 -28684.12 -121724.59
PERIMETER_TOP_ZN_3 06-FEB-01:01 0.00 0.00 16610.41 0.00 0.00 0.00 0.00 97.23 1011.70 0.00 0.00 0.00 0.00 0.00 -4621.32 0.00 -6142.66 -6955.35
PERIMETER_TOP_ZN_2 06-FEB-01:01 0.00 0.00 17555.94 0.00 0.00 0.00 0.00 62.66 651.98 0.00 0.00 0.00 0.00 0.00 -2998.11 0.00 -4172.41 -11100.05
PERIMETER_TOP_ZN_1 06-FEB-01:01 0.00 0.00 21268.20 0.00 0.00 0.00 0.00 97.23 1011.71 0.00 0.00 0.00 0.00 0.00 -4560.40 0.00 -6266.25 -11550.50
PERIMETER_TOP_ZN_4 06-FEB-01:01 0.00 0.00 19040.03 0.00 0.00 0.00 0.00 62.66 651.97 0.00 0.00 0.00 0.00 0.00 -3156.65 0.00 -4226.37 -12371.63
DATACENTER_BOT_ZN_6 01-JAN-09:58 0.00 0.00 436.15 0.00 0.00 0.00 5.26 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2412.52
DATACENTER_MID_ZN_6 16-JAN-18:00 0.00 0.00 5495.90 0.00 0.00 0.00 55.93 225.07 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25262.96
DATACENTER_TOP_ZN_6 29-JAN-17:50 0.00 0.00 578.08 0.00 0.00 0.00 5.66 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2554.85
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 11-DEC-05:01 14494.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1339.67 -13154.85
MIDFLOOR_PLENUM 02-JAN-06:12 192323.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -6441.41 -185882.02
TOPFLOOR_PLENUM 06-FEB-05:10 29364.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -7816.39 -21548.07
Total Facility 02-JAN-05:21 47251.24 100189.22 1350970.60 -100189.22 0.00 0.00 0.00 29009.37 268362.69 0.00 0.00 0.00 0.00 0.00 -183997.50 0.00 -94662.55 -1416933.85



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 10.1564 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.2478 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 96.2860 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 86.3930 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 10.1238 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.3232 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.2801 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.2801 0.2273 1.0000 Not calculated 1.2002 0.2273    
AIRLOOP DATACENTER BASEMENT 21.2997 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.2999 0.0159 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4723 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4723 0.0331 1.0000 Not calculated 0.0156 0.0331    
AIRLOOP DATACENTER MID 4.5064 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5064 0.0347 1.0000 Not calculated 0.1563 0.0347    
AIRLOOP DATACENTER TOP 0.4593 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4593 0.0340 1.0000 Not calculated 0.0156 0.0340    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.0782 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.8695 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 48.1430 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 28.0183 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.0619 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.9002 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.2801 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.2801 1.0000 1.0000 Not calculated 1.2002 0.2273    
AIRLOOP DATACENTER BASEMENT 21.2997 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.2997 1.0000 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4723 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4723 1.0000 1.0000 Not calculated 0.0156 0.0331    
AIRLOOP DATACENTER MID 4.5064 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.5064 1.0000 1.0000 Not calculated 0.1563 0.0347    
AIRLOOP DATACENTER TOP 0.4593 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4593 1.0000 1.0000 Not calculated 0.0156 0.0340    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.2801 5.2801 5.2801 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.6134 5.6134 1.9085 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 52.7577 52.7577 18.7290 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.3717 5.3717 1.9123 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9348 0.9348 0.2393 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0416 1.0416 0.2083 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2642 1.2642 0.2528 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3024 1.3024 0.2605 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.8427 8.8427 2.3522 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.9429 10.9429 2.1886 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.3200 12.3200 2.4640 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 11.4227 11.4227 2.2845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0404 1.0404 0.2455 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1222 1.1222 0.2244 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3576 1.3576 0.2715 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2320 1.2320 0.2464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4723 0.4723 0.4723 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5064 4.5064 4.5064 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4593 0.4593 0.4593 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.2997 21.2997 21.2997 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 10.1564 9.2478 10.1564 2.8695 0.0000 1.0000
VAV_MID WITH REHEAT 96.2860 86.3930 96.2860 28.0183 0.0000 1.0000
VAV_TOP WITH REHEAT 10.1238 9.3232 10.1238 2.9002 0.0000 1.0000
CAV_BAS 5.2801 5.2801 5.2801 5.2801 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.2997 21.2999 21.2997 21.2997 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4723 0.4723 0.4723 0.4723 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5064 4.5064 4.5064 4.5064 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4593 0.4593 0.4593 0.4593 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.2801 5.2801 5.2801 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8067 2.8067 1.9085 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 26.3788 26.3788 18.7290 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6858 2.6858 1.9123 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4674 0.4674 0.2393 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5208 0.5208 0.2083 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6321 0.6321 0.2528 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6512 0.6512 0.2605 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.4214 4.4214 2.3522 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.4714 5.4714 2.1886 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.1600 6.1600 2.4640 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7113 5.7113 2.2845 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5202 0.5202 0.2455 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5611 0.5611 0.2244 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6788 0.6788 0.2715 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6160 0.6160 0.2464 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4723 0.4723 0.4723 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.5064 4.5064 4.5064 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4593 0.4593 0.4593 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.2997 21.2997 21.2997 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.0782 2.8695 2.8695 2.8695 0.0000 1.0000
VAV_MID WITH REHEAT 48.1430 28.0183 28.0183 28.0183 0.0000 1.0000
VAV_TOP WITH REHEAT 5.0619 2.9002 2.9002 2.9002 0.0000 1.0000
CAV_BAS 5.2801 5.2801 5.2801 5.2801 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.2997 21.2997 21.2997 21.2997 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4723 0.4723 0.4723 0.4723 0.0156 1.0000
AIRLOOP DATACENTER MID 4.5064 4.5064 4.5064 4.5064 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4593 0.4593 0.4593 0.4593 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** New York-John F Kennedy Intl AP NY USA TMY3 WMO#=744860
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 56.00
Number of hours cooling loads not met 405.67
Number of hours not met 461.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 1121.52 1746492.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 3472.96 448279.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2745.73 261074.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 449.24 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 59.77 3726.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2283.57 283348.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 620.77 75732.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1130.44 90459.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 14.23 6185.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 48.90 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 706.90 82525.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 27893.64
Natural Gas 0.00 1828.42
Additional 0.00 0.00
Total 15213.41 29722.06


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 59.28
Space Heating 0.00
Space Cooling 74.98
Fans (All) 49.30
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 602.19
Subtotal 602.19


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 24.21
Service Water Heating 15.26
Miscellaneous (All) 39.47
Subtotal 39.47


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 9.24
Space Heating 3.77
Space Cooling 11.68
Fans (All) 7.68
Service Water Heating 2.38
Receptacle Equipment 51.19
Miscellaneous 14.06


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2393. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8300.17 459.83 0.00 0.00 0.00
CORE_BOTTOM 8703.17 56.83 0.00 0.00 0.00
CORE_MID 8749.83 10.17 0.00 0.00 0.00
CORE_TOP 8739.50 20.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8750.83 9.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8714.00 46.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8693.67 66.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8269.67 490.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8718.83 41.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8621.17 138.83 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8594.00 166.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8391.50 368.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8686.67 73.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8592.00 168.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8562.17 197.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8408.50 351.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 6163.33 2596.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 6169.17 2590.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 6143.50 2616.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5929.17 2830.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8647.33 112.67 0.00 0.00 0.00
Min 5929.17 0.00 0.00 0.00 0.00
Max 8760.00 2830.83 0.00 0.00 0.00
Average 8176.88 583.12 0.00 0.00 0.00
Sum 188068.17 13411.83 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 367171.67 1444.33 0.00 0.00 0.00
CORE_BOTTOM 330730.00 83.00 0.00 0.00 0.00
CORE_MID 330811.00 2.00 0.00 0.00 0.00
CORE_TOP 330782.00 31.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1304.00 964.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1298.50 969.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1295.83 972.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 61114.50 42280.50 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 367171.67 42280.50 0.00 0.00 0.00
Average 78302.46 2032.46 0.00 0.00 0.00
Sum 1800956.50 46746.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 7066.33 1693.67 0.00 0.00 0.00
CORE_BOTTOM 8073.67 686.33 0.00 0.00 0.00
CORE_MID 7916.17 843.83 0.00 0.00 0.00
CORE_TOP 7967.33 792.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 7908.33 851.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8165.83 594.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 7820.00 940.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7583.00 1177.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 7868.33 891.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 7848.67 911.33 0.00 0.00 0.00
PERIMETER_MID_ZN_1 7745.00 1015.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7736.67 1023.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 7879.33 880.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 7862.50 897.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 7788.83 971.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7783.50 976.50 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 7327.67 1432.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 7303.50 1456.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 7280.50 1479.50 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 7289.17 1470.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 7700.83 1059.17 0.00 0.00 0.00
MIDFLOOR_PLENUM 7762.50 997.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 7278.67 1481.33 0.00 0.00 0.00
Min 7066.33 594.17 0.00 0.00 0.00
Max 8165.83 1693.67 0.00 0.00 0.00
Average 7693.75 1066.25 0.00 0.00 0.00
Sum 176956.33 24523.67 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 352929.00 15687.00 0.00 0.00 0.00
CORE_BOTTOM 329643.00 1170.00 0.00 0.00 0.00
CORE_MID 329588.00 1225.00 0.00 0.00 0.00
CORE_TOP 329564.00 1249.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38915.67 9.33 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18352.50 1.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38918.83 6.17 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24908.50 0.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38912.00 13.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24905.33 3.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38916.33 8.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24907.83 1.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 1464.33 803.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 1449.33 818.67 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 1438.33 829.67 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 72951.33 30443.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 352929.00 30443.67 0.00 0.00 0.00
Average 78062.28 2272.64 0.00 0.00 0.00
Sum 1795432.33 52270.67 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:39

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4A

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_NY_NEWYORK

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 1.168
February -0.18
March 5.585
April 10.941
May 16.049
June 21.711
July 25.046
August 24.788
September 19.956
October 14.024
November 7.310
December 3.332
   
Annual Sum or Average 12.554
Minimum of Months -0.18
Maximum of Months 25.046



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.409779E+11 101225.76 30-JAN-04:01 -4.0 -5.6 0.558968E+10 7499.27 03-JAN-10:09 -4.0 -5.6
February 0.397012E+11 105817.05 21-FEB-04:01 1.78 1.01 0.508141E+10 7499.14 10-FEB-14:20 1.78 1.01
March 0.514482E+11 103836.54 13-MAR-03:01 0.50 -3.0 0.612732E+10 7499.11 27-MAR-09:20 11.30 11.30
April 0.499466E+11 103422.61 03-APR-03:01 3.22 0.25 0.544579E+10 7499.15 07-APR-13:00 26.10 15.95
May 0.528820E+11 103833.81 01-MAY-03:02 7.45 5.14 0.589880E+10 7499.51 25-MAY-09:20 16.87 13.21
June 0.563452E+11 93773.98 05-JUN-03:03 15.82 12.11 0.588058E+10 7499.24 23-JUN-09:00 30.00 18.39
July 0.572756E+11 87613.43 11-JUL-03:02 20.50 15.26 0.547276E+10 7499.16 12-JUL-09:30 27.50 18.52
August 0.649929E+11 89401.06 29-AUG-03:02 17.12 14.13 0.613793E+10 7499.16 09-AUG-09:20 17.12 14.13
September 0.579250E+11 102079.14 25-SEP-03:02 13.98 11.61 0.545215E+10 7499.25 19-SEP-09:20 13.98 11.61
October 0.604891E+11 105803.27 16-OCT-03:02 8.80 7.97 0.567087E+10 7499.49 16-OCT-09:20 17.07 14.18
November 0.547603E+11 105334.30 06-NOV-04:03 5.00 2.82 0.561200E+10 7499.12 09-NOV-14:00 13.90 12.65
December 0.508665E+11 108548.94 26-DEC-04:01 5.60 4.99 0.546593E+10 7499.08 15-DEC-10:09 5.60 4.99
                     
Annual Sum or Average 0.637610E+12         0.678352E+11        
Minimum of Months 0.397012E+11 87613.43   -4.0 -5.6 0.508141E+10 7499.08   -4.0 -5.6
Maximum of Months 0.649929E+11 108548.94   20.50 15.26 0.613793E+10 7499.51   30.00 18.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.310825E+11 79541.05 30-JAN-06:02 -5.0 -6.1 0.499414E+10 6734.75 17-JAN-10:20 -5.0 -6.1
February 0.314778E+11 83923.28 21-FEB-05:02 2.20 1.30 0.457221E+10 6745.22 10-FEB-14:39 2.20 1.30
March 0.461847E+11 84360.62 30-MAR-04:02 2.20 0.99 0.549470E+10 6747.95 13-MAR-09:30 2.20 0.99
April 0.512925E+11 85862.75 11-APR-03:02 6.60 1.81 0.488095E+10 6734.85 26-APR-09:00 16.10 12.59
May 0.513144E+11 87495.28 01-MAY-03:02 7.45 5.14 0.528460E+10 6842.05 30-MAY-13:00 29.40 16.93
June 0.600587E+11 89540.86 12-JUN-03:02 18.90 17.52 0.526929E+10 6784.86 22-JUN-13:20 28.87 17.36
July 0.675754E+11 84373.02 01-JUL-03:02 20.00 19.65 0.489208E+10 6757.03 11-JUL-13:39 28.53 17.90
August 0.756830E+11 84093.86 07-AUG-05:04 19.40 16.74 0.549321E+10 6736.28 25-AUG-13:00 26.70 15.26
September 0.525194E+11 91267.60 18-SEP-03:02 16.70 15.98 0.488280E+10 6735.66 01-SEP-13:00 16.70 15.98
October 0.524039E+11 90327.57 23-OCT-03:02 14.13 11.49 0.507871E+10 6735.13 16-OCT-09:09 14.13 11.49
November 0.437779E+11 91713.54 13-NOV-04:02 5.60 4.34 0.503060E+10 6746.44 22-NOV-14:50 1.28 -2.5
December 0.422548E+11 85475.15 26-DEC-04:01 5.60 4.99 0.489414E+10 6745.39 12-DEC-10:20 5.60 4.99
                     
Annual Sum or Average 0.605625E+12         0.607674E+11        
Minimum of Months 0.310825E+11 79541.05   -5.0 -6.1 0.457221E+10 6734.75   -5.0 -6.1
Maximum of Months 0.756830E+11 91713.54   20.00 19.65 0.549470E+10 6842.05   29.40 17.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.217881E+11 21262.51 31-JAN-09:40 -7.1 -9.7 0.435980E+10 6703.15 27-JAN-14:00 -7.1 -9.7
February 0.218105E+11 25464.82 04-FEB-17:08 0.10 -1.4 0.409389E+10 6734.48 03-FEB-14:00 0.10 -1.4
March 0.288536E+11 70076.28 30-MAR-05:02 2.20 0.86 0.530787E+10 6784.93 16-MAR-13:39 2.20 0.86
April 0.317254E+11 77420.71 08-APR-05:02 14.32 11.97 0.480874E+10 6734.76 26-APR-09:00 16.10 12.59
May 0.415773E+11 77442.54 20-MAY-05:02 13.30 11.39 0.526391E+10 6735.00 25-MAY-09:09 16.78 13.45
June 0.474372E+11 81975.11 12-JUN-03:02 18.90 17.52 0.526540E+10 6757.97 20-JUN-13:39 27.03 17.79
July 0.491834E+11 79698.32 12-JUL-03:02 21.70 19.09 0.489154E+10 6734.84 11-JUL-13:00 21.70 19.09
August 0.523991E+11 86286.94 07-AUG-03:02 18.80 17.42 0.549615E+10 6740.84 25-AUG-13:00 26.70 15.26
September 0.431044E+11 80536.55 18-SEP-03:02 16.70 15.98 0.487139E+10 6734.94 19-SEP-09:09 18.58 14.06
October 0.381759E+11 77929.20 05-OCT-04:03 15.60 14.25 0.504799E+10 6735.05 16-OCT-09:09 16.88 14.11
November 0.269673E+11 73403.98 03-NOV-05:02 9.22 6.42 0.483187E+10 6742.63 15-NOV-10:00 7.20 4.04
December 0.243551E+11 24633.11 21-DEC-17:00 1.70 -2.8 0.454682E+10 6734.52 22-DEC-14:00 1.70 -2.0
                     
Annual Sum or Average 0.427377E+12         0.587854E+11        
Minimum of Months 0.217881E+11 21262.51   -7.1 -9.7 0.409389E+10 6703.15   -7.1 -9.7
Maximum of Months 0.523991E+11 86286.94   21.70 19.09 0.549615E+10 6784.93   27.03 19.09



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.164177E+11 18386.66 20-JAN-17:00 5.60 3.19 0.401910E+10 6244.49 19-JAN-14:00 5.60 3.19
February 0.156704E+11 18461.24 24-FEB-17:00 6.70 1.42 0.368101E+10 6285.95 17-FEB-14:00 6.70 1.42
March 0.239484E+11 29245.72 03-MAR-17:00 14.00 7.84 0.481858E+10 6734.53 29-MAR-13:00 7.80 5.51
April 0.276354E+11 75034.63 08-APR-05:02 14.32 11.97 0.458616E+10 6734.72 07-APR-13:09 14.32 11.97
May 0.394743E+11 81840.28 30-MAY-03:02 18.22 15.08 0.520600E+10 6823.86 30-MAY-13:00 29.40 16.93
June 0.497909E+11 84215.32 12-JUN-03:02 18.90 17.52 0.526299E+10 6890.82 22-JUN-13:30 29.15 17.46
July 0.539085E+11 84498.08 24-JUL-03:02 22.02 21.19 0.489657E+10 6842.75 11-JUL-13:50 22.02 21.19
August 0.564296E+11 88980.59 07-AUG-03:02 18.80 17.42 0.549670E+10 6734.78 23-AUG-13:09 25.60 17.07
September 0.417954E+11 81556.61 05-SEP-03:02 20.50 17.81 0.485010E+10 6734.90 19-SEP-09:09 18.58 14.06
October 0.324523E+11 78239.46 06-OCT-05:02 19.40 18.22 0.491152E+10 6734.99 16-OCT-09:09 16.88 14.11
November 0.206854E+11 29554.38 03-NOV-16:00 15.00 10.26 0.435474E+10 6734.73 09-NOV-14:00 13.90 12.65
December 0.176372E+11 18152.88 20-DEC-17:00 6.70 3.52 0.397032E+10 6272.40 20-DEC-14:00 6.70 3.52
                     
Annual Sum or Average 0.395846E+12         0.560538E+11        
Minimum of Months 0.156704E+11 18152.88   5.60 1.42 0.368101E+10 6244.49   5.60 1.42
Maximum of Months 0.564296E+11 88980.59   22.02 21.19 0.549670E+10 6890.82   29.40 21.19



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.189118E+10 2594.39 24-JAN-06:03 11.10 11.10 0.514476E+09 789.99 20-JAN-14:00 11.10 11.10
February 0.188585E+10 2661.02 21-FEB-05:02 2.20 1.30 0.472964E+09 805.17 24-FEB-14:30 8.85 2.78
March 0.353645E+10 5368.29 27-MAR-13:30 20.85 16.76 0.642061E+09 845.62 06-MAR-14:20 20.85 16.76
April 0.498773E+10 6755.29 07-APR-13:40 26.30 16.10 0.598691E+09 845.64 26-APR-09:00 16.10 12.59
May 0.652347E+10 12709.70 30-MAY-05:03 18.17 14.31 0.660711E+09 871.97 30-MAY-13:00 29.40 16.93
June 0.961510E+10 12222.83 12-JUN-05:03 18.40 17.59 0.661996E+09 863.69 22-JUN-13:20 28.87 17.36
July 0.115587E+11 15480.16 04-JUL-16:01 25.92 18.02 0.615673E+09 860.22 11-JUL-13:39 28.53 17.90
August 0.122821E+11 15993.37 13-AUG-16:21 29.70 20.61 0.690411E+09 846.03 25-AUG-13:00 26.70 15.26
September 0.691302E+10 11727.90 02-SEP-05:03 22.12 16.30 0.611309E+09 845.87 01-SEP-13:00 22.12 16.30
October 0.535183E+10 10056.65 23-OCT-05:03 13.22 10.95 0.629102E+09 845.66 16-OCT-09:09 13.22 10.95
November 0.324965E+10 4446.36 03-NOV-13:50 17.70 10.66 0.593256E+09 845.64 09-NOV-14:00 13.90 12.65
December 0.282807E+10 2849.64 05-DEC-05:01 6.10 4.77 0.542546E+09 845.60 26-DEC-14:09 8.80 4.42
                     
Annual Sum or Average 0.706232E+11         0.723320E+10        
Minimum of Months 0.188585E+10 2594.39   2.20 1.30 0.472964E+09 789.99   8.80 2.78
Maximum of Months 0.122821E+11 15993.37   29.70 20.61 0.690411E+09 871.97   29.40 17.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.162241E+10 3010.30 19-JAN-09:25 6.10 3.63 0.335425E+09 544.94 26-JAN-10:09 2.38 -1.0
February 0.169872E+10 3977.52 22-FEB-09:30 0.30 -3.3 0.312039E+09 544.95 22-FEB-10:39 1.67 -2.5
March 0.330786E+10 7167.92 29-MAR-08:40 5.20 2.69 0.414074E+09 546.34 13-MAR-09:30 5.20 2.69
April 0.456074E+10 10541.44 23-APR-08:33 11.33 7.60 0.381131E+09 544.97 26-APR-09:50 16.38 12.56
May 0.613620E+10 18182.90 29-MAY-08:22 25.00 16.74 0.424694E+09 557.77 30-MAY-13:00 29.40 16.93
June 0.766083E+10 17846.79 04-JUN-08:13 22.57 12.59 0.426299E+09 553.39 22-JUN-09:30 25.85 16.85
July 0.901686E+10 18147.23 02-JUL-08:32 25.20 21.54 0.396626E+09 547.67 12-JUL-09:39 27.60 18.47
August 0.101411E+11 17440.45 13-AUG-09:02 27.98 19.16 0.444670E+09 546.19 22-AUG-09:00 28.30 18.37
September 0.612347E+10 18180.11 04-SEP-07:23 21.70 18.19 0.393690E+09 545.63 06-SEP-09:20 25.97 19.25
October 0.491683E+10 8599.91 03-OCT-08:40 18.33 16.58 0.405231E+09 544.99 16-OCT-09:09 16.88 14.11
November 0.271420E+10 5145.63 02-NOV-08:50 10.82 5.71 0.378174E+09 544.96 09-NOV-14:00 13.90 12.65
December 0.220793E+10 3674.70 20-DEC-09:25 7.20 4.58 0.341702E+09 544.94 18-DEC-10:09 7.20 4.58
                     
Annual Sum or Average 0.601071E+11         0.465376E+10        
Minimum of Months 0.162241E+10 3010.30   0.30 -3.3 0.312039E+09 544.94   1.67 -2.5
Maximum of Months 0.101411E+11 18182.90   27.98 21.54 0.444670E+09 557.77   29.40 19.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.315944E+10 10789.31 19-JAN-13:30 9.40 3.94 0.553934E+09 845.64 31-JAN-10:20 -6.3 -9.2
February 0.353431E+10 11529.95 22-FEB-13:20 4.27 -1.2 0.519179E+09 847.55 10-FEB-14:39 4.27 -1.2
March 0.627041E+10 14175.04 03-MAR-13:15 14.60 8.23 0.651885E+09 846.37 03-MAR-14:20 15.00 8.55
April 0.695393E+10 16859.92 09-APR-13:43 19.40 15.43 0.594470E+09 852.92 07-APR-13:50 19.40 15.43
May 0.774040E+10 21619.03 29-MAY-13:43 26.28 17.36 0.658717E+09 897.71 30-MAY-13:00 29.40 16.93
June 0.106235E+11 15566.95 26-JUN-05:02 20.78 17.10 0.662075E+09 869.37 22-JUN-13:20 20.78 17.10
July 0.131112E+11 22034.40 04-JUL-14:02 27.70 18.45 0.616086E+09 870.83 11-JUL-13:39 28.53 17.90
August 0.162768E+11 23327.09 13-AUG-13:02 31.20 19.67 0.691299E+09 857.06 30-AUG-13:50 28.62 15.51
September 0.110590E+11 22460.27 10-SEP-11:02 22.30 13.72 0.612943E+09 874.37 01-SEP-13:00 22.30 13.72
October 0.109664E+11 22342.11 15-OCT-13:32 20.93 13.28 0.634191E+09 859.02 04-OCT-13:20 20.93 13.28
November 0.556914E+10 16291.15 02-NOV-12:40 15.40 8.14 0.605812E+09 846.84 22-NOV-14:50 1.28 -2.5
December 0.442962E+10 17957.59 17-DEC-12:33 12.20 4.80 0.564009E+09 845.64 19-DEC-10:20 6.67 3.33
                     
Annual Sum or Average 0.996940E+11         0.736460E+10        
Minimum of Months 0.315944E+10 10789.31   4.27 -1.2 0.519179E+09 845.64   -6.3 -9.2
Maximum of Months 0.162768E+11 23327.09   31.20 19.67 0.691299E+09 897.71   29.40 17.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.266098E+10 5367.07 20-JAN-15:40 7.40 3.86 0.348339E+09 544.94 20-JAN-14:00 7.40 3.86
February 0.304200E+10 7665.10 24-FEB-15:30 8.05 2.04 0.332723E+09 546.08 10-FEB-14:39 8.05 2.04
March 0.601064E+10 11632.18 27-MAR-16:00 22.20 16.34 0.438296E+09 544.96 27-MAR-09:09 22.20 16.34
April 0.835523E+10 22755.94 09-APR-16:22 16.65 13.97 0.395102E+09 544.97 26-APR-09:50 16.38 12.56
May 0.782065E+10 18788.75 29-MAY-14:23 25.85 17.23 0.427370E+09 562.74 30-MAY-13:00 29.40 16.93
June 0.114669E+11 22960.94 18-JUN-16:02 25.50 22.07 0.427751E+09 550.93 22-JUN-13:20 28.87 17.36
July 0.139399E+11 25612.86 04-JUL-16:01 25.92 18.02 0.397995E+09 547.31 11-JUL-13:00 28.90 17.83
August 0.168864E+11 25797.33 13-AUG-16:21 29.70 20.61 0.446417E+09 546.51 22-AUG-15:09 29.90 17.46
September 0.813367E+10 22066.26 10-SEP-15:42 23.48 13.06 0.395316E+09 545.56 01-SEP-13:00 23.48 13.06
October 0.760819E+10 14656.52 23-OCT-05:03 13.22 10.95 0.410167E+09 544.99 16-OCT-09:09 13.22 10.95
November 0.468072E+10 10871.66 09-NOV-06:03 9.50 9.14 0.400383E+09 545.98 22-NOV-14:50 1.28 -2.5
December 0.432093E+10 7507.82 18-DEC-15:30 5.85 2.55 0.388010E+09 544.95 29-DEC-14:00 3.90 3.16
                     
Annual Sum or Average 0.949262E+11         0.480787E+10        
Minimum of Months 0.266098E+10 5367.07   5.85 2.04 0.332723E+09 544.94   1.28 -2.5
Maximum of Months 0.168864E+11 25797.33   29.70 22.07 0.446417E+09 562.74   29.90 17.83



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.324336E+09 1830.36 20-JAN-17:00 5.60 3.19 0.465378E+09 653.21 20-JAN-14:00 5.60 3.19
February 0.346390E+09 2714.43 04-FEB-17:08 0.10 -1.4 0.424173E+09 675.20 24-FEB-14:00 8.30 2.27
March 0.162726E+10 2369.75 27-MAR-16:00 22.20 16.34 0.542520E+09 828.92 28-MAR-13:00 13.30 8.41
April 0.272649E+10 4963.59 07-APR-15:20 25.60 16.01 0.542142E+09 845.63 06-APR-13:09 25.60 16.01
May 0.503564E+10 10386.10 30-MAY-05:03 18.17 14.31 0.647796E+09 849.14 30-MAY-13:00 29.40 16.93
June 0.778453E+10 11376.34 20-JUN-05:02 20.78 18.13 0.661064E+09 854.78 20-JUN-13:39 27.03 17.79
July 0.911152E+10 13815.51 10-JUL-03:02 26.10 21.76 0.615819E+09 850.86 11-JUL-13:30 28.35 17.93
August 0.908523E+10 12318.14 18-AUG-03:02 25.50 18.51 0.690561E+09 846.81 25-AUG-13:00 26.70 15.26
September 0.556707E+10 10780.97 22-SEP-05:03 21.70 20.52 0.605310E+09 845.64 19-SEP-09:09 21.70 20.52
October 0.363199E+10 5448.73 05-OCT-14:00 23.30 18.86 0.597515E+09 845.61 16-OCT-13:50 19.32 16.19
November 0.153308E+10 2789.43 02-NOV-13:20 15.77 8.37 0.502427E+09 826.96 03-NOV-13:00 17.80 10.67
December 0.505162E+09 1765.47 20-DEC-13:40 9.80 5.81 0.451298E+09 676.46 20-DEC-14:20 9.43 5.62
                     
Annual Sum or Average 0.472787E+11         0.674600E+10        
Minimum of Months 0.324336E+09 1765.47   0.10 -1.4 0.424173E+09 653.21   5.60 2.27
Maximum of Months 0.911152E+10 13815.51   26.10 21.76 0.690561E+09 854.78   29.40 20.52



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.404024E+09 2138.81 26-JAN-09:25 1.40 -1.6 0.221802E+09 461.50 27-JAN-09:00 4.40 1.46
February 0.582284E+09 2472.69 04-FEB-17:08 0.10 -1.4 0.203673E+09 483.11 17-FEB-09:50 4.13 0.27
March 0.198095E+10 5920.93 29-MAR-09:00 5.60 2.98 0.271671E+09 522.52 07-MAR-09:20 5.60 2.98
April 0.321635E+10 9091.63 28-APR-08:50 15.82 8.80 0.265384E+09 521.23 06-APR-12:09 15.82 8.80
May 0.557290E+10 20770.25 29-MAY-08:42 25.73 16.73 0.305599E+09 537.76 30-MAY-10:50 28.72 17.34
June 0.703955E+10 18718.30 04-JUN-08:23 22.75 12.67 0.312732E+09 526.43 26-JUN-07:19 23.50 18.22
July 0.815524E+10 21292.56 02-JUL-09:01 25.68 21.69 0.292910E+09 535.76 11-JUL-14:30 28.60 17.71
August 0.908529E+10 18935.18 27-AUG-09:53 26.10 21.81 0.327308E+09 529.92 22-AUG-15:39 26.10 21.81
September 0.561062E+10 20532.56 04-SEP-09:12 24.47 18.42 0.286664E+09 521.42 06-SEP-08:00 25.60 19.05
October 0.398374E+10 8046.64 05-OCT-09:00 18.90 16.77 0.288925E+09 521.22 16-OCT-08:00 16.70 14.03
November 0.159094E+10 3189.85 03-NOV-09:00 12.80 8.09 0.242307E+09 521.19 03-NOV-10:09 13.58 8.52
December 0.705637E+09 2048.78 21-DEC-09:15 0.20 -2.8 0.216404E+09 483.98 20-DEC-09:00 0.20 -2.8
                     
Annual Sum or Average 0.479275E+11         0.323538E+10        
Minimum of Months 0.404024E+09 2048.78   0.10 -2.8 0.203673E+09 461.50   0.20 -2.8
Maximum of Months 0.908529E+10 21292.56   26.10 21.81 0.327308E+09 537.76   28.72 21.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.194156E+10 9636.76 19-JAN-13:40 9.40 3.86 0.521895E+09 845.65 05-JAN-14:09 9.40 3.86
February 0.246599E+10 11131.70 22-FEB-13:40 4.63 -1.0 0.487109E+09 858.87 09-FEB-14:39 4.63 -1.0
March 0.471666E+10 13487.33 01-MAR-13:30 13.90 6.36 0.615067E+09 852.28 07-MAR-10:09 7.80 3.53
April 0.499425E+10 13860.82 07-APR-12:40 26.33 16.06 0.569410E+09 867.51 07-APR-13:50 26.20 16.03
May 0.666975E+10 21438.89 29-MAY-12:43 27.48 17.22 0.649787E+09 878.92 30-MAY-13:00 29.40 16.93
June 0.898030E+10 14925.82 08-JUN-05:02 19.08 17.42 0.661115E+09 855.92 20-JUN-13:39 27.03 17.79
July 0.107542E+11 21969.56 30-JUL-13:32 27.20 24.02 0.616344E+09 864.59 11-JUL-13:30 27.20 24.02
August 0.134403E+11 21882.55 20-AUG-12:32 27.43 15.69 0.692040E+09 886.24 30-AUG-13:00 28.90 15.47
September 0.103783E+11 23745.40 04-SEP-11:52 26.10 17.79 0.611021E+09 898.95 01-SEP-13:00 26.10 17.79
October 0.992465E+10 21877.50 15-OCT-14:32 20.77 13.06 0.628294E+09 884.28 04-OCT-13:30 20.77 13.06
November 0.416910E+10 16594.06 02-NOV-13:10 15.68 8.29 0.574106E+09 864.15 21-NOV-10:00 2.20 0.17
December 0.261032E+10 13902.34 15-DEC-12:00 2.20 -1.3 0.523958E+09 845.66 15-DEC-14:09 3.98 0.25
                     
Annual Sum or Average 0.810454E+11         0.715014E+10        
Minimum of Months 0.194156E+10 9636.76   2.20 -1.3 0.487109E+09 845.65   2.20 -1.0
Maximum of Months 0.134403E+11 23745.40   27.48 24.02 0.692040E+09 898.95   29.40 24.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.643836E+09 2393.09 20-JAN-16:10 6.93 3.71 0.307105E+09 506.41 20-JAN-16:10 6.93 3.71
February 0.792390E+09 3448.09 22-FEB-16:30 3.85 -0.7 0.283411E+09 530.24 17-FEB-14:00 3.85 -0.7
March 0.252490E+10 7749.30 29-MAR-16:00 7.20 4.88 0.367607E+09 544.94 01-MAR-14:00 7.20 4.88
April 0.370132E+10 12552.96 09-APR-16:33 16.47 13.91 0.356030E+09 544.96 10-APR-13:09 20.10 10.10
May 0.565331E+10 15095.03 28-MAY-16:03 23.43 15.49 0.415407E+09 544.99 15-MAY-13:50 23.43 15.49
June 0.795402E+10 20273.71 04-JUN-16:22 21.65 14.55 0.426357E+09 556.59 01-JUN-15:50 21.65 14.55
July 0.884985E+10 20989.66 02-JUL-16:21 24.70 20.69 0.397425E+09 549.15 11-JUL-15:20 28.30 17.46
August 0.996072E+10 20254.30 13-AUG-15:52 30.00 20.46 0.445907E+09 557.06 22-AUG-15:39 29.60 17.26
September 0.597092E+10 21157.38 10-SEP-16:02 23.22 12.85 0.389733E+09 544.97 11-SEP-13:09 20.60 12.01
October 0.452646E+10 10492.44 04-OCT-15:30 23.35 19.12 0.388649E+09 544.95 13-OCT-13:39 21.70 17.54
November 0.175100E+10 5405.39 03-NOV-15:30 16.10 10.65 0.329730E+09 544.95 08-NOV-14:00 13.30 11.09
December 0.913012E+09 2256.62 08-DEC-15:40 6.30 2.04 0.299674E+09 508.14 21-DEC-14:00 3.30 -1.8
                     
Annual Sum or Average 0.532417E+11         0.440703E+10        
Minimum of Months 0.643836E+09 2256.62   3.85 -0.7 0.283411E+09 506.41   3.30 -1.8
Maximum of Months 0.996072E+10 21157.38   30.00 20.69 0.445907E+09 557.06   29.60 17.54



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.105836E+09 1558.17 20-JAN-16:00 7.20 3.80 0.463159E+09 625.90 05-JAN-10:39 7.20 3.80
February 0.112441E+09 1633.69 24-FEB-15:30 8.05 2.04 0.420241E+09 625.94 06-FEB-10:50 8.05 2.04
March 0.924617E+09 2365.76 28-MAR-14:10 13.22 8.42 0.522317E+09 802.72 28-MAR-13:00 13.22 8.42
April 0.224459E+10 5617.14 07-APR-15:20 25.60 16.01 0.515174E+09 845.63 07-APR-13:09 25.60 16.01
May 0.482444E+10 11064.09 31-MAY-05:03 16.38 14.99 0.629155E+09 857.12 30-MAY-13:00 16.38 14.99
June 0.808143E+10 13587.36 26-JUN-05:02 20.78 17.10 0.659800E+09 859.78 22-JUN-13:30 20.78 17.10
July 0.983077E+10 18157.48 09-JUL-15:21 27.20 24.16 0.616011E+09 855.10 11-JUL-13:00 28.90 17.83
August 0.968552E+10 14778.17 13-AUG-15:52 30.00 20.46 0.690044E+09 845.64 09-AUG-13:30 30.00 20.46
September 0.543371E+10 10682.72 07-SEP-05:02 22.20 21.37 0.597117E+09 845.64 11-SEP-13:09 20.60 12.01
October 0.306645E+10 5694.95 04-OCT-14:00 24.40 18.95 0.568189E+09 845.61 16-OCT-13:00 19.40 16.27
November 0.881335E+09 2298.44 03-NOV-15:00 17.20 10.98 0.476317E+09 780.54 03-NOV-13:00 17.20 10.98
December 72464214.08 1505.85 09-DEC-17:03 4.32 1.58 0.447495E+09 625.90 11-DEC-14:09 1.10 -0.6
                     
Annual Sum or Average 0.452636E+11         0.660502E+10        
Minimum of Months 72464214.08 1505.85   4.32 1.58 0.420241E+09 625.90   1.10 -0.6
Maximum of Months 0.983077E+10 18157.48   30.00 24.16 0.690044E+09 859.78   30.00 20.46



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.217583E+09 1701.50 19-JAN-10:20 7.80 4.36 0.299700E+09 442.74 19-JAN-10:30 7.80 4.48
February 0.288266E+09 1738.90 22-FEB-10:15 1.13 -2.8 0.273062E+09 446.64 22-FEB-10:20 1.13 -2.8
March 0.141325E+10 4064.03 29-MAR-09:50 6.52 3.33 0.357189E+09 544.94 29-MAR-09:09 6.52 3.33
April 0.280458E+10 8512.42 07-APR-09:30 20.55 13.59 0.352722E+09 544.97 26-APR-09:00 16.10 12.59
May 0.542945E+10 21293.57 29-MAY-08:52 26.10 16.72 0.410108E+09 552.33 30-MAY-13:00 29.40 16.93
June 0.739838E+10 19106.42 04-JUN-09:13 23.67 12.90 0.425304E+09 549.80 22-JUN-13:30 29.15 17.46
July 0.883395E+10 19823.50 02-JUL-09:12 25.77 21.71 0.397222E+09 552.24 11-JUL-13:00 28.90 17.83
August 0.971007E+10 19155.68 13-AUG-09:52 28.90 19.41 0.445348E+09 560.89 22-AUG-09:00 28.30 18.37
September 0.558540E+10 20929.34 04-SEP-09:12 24.47 18.42 0.387437E+09 545.53 06-SEP-09:20 25.97 19.25
October 0.348883E+10 7532.67 05-OCT-09:20 19.27 16.99 0.385319E+09 544.98 16-OCT-09:09 16.88 14.11
November 0.103823E+10 2271.47 02-NOV-13:30 15.85 8.46 0.314964E+09 530.73 03-NOV-09:00 13.30 8.39
December 0.249841E+09 1752.42 20-DEC-09:35 7.57 4.72 0.289250E+09 449.72 20-DEC-10:09 8.40 5.03
                     
Annual Sum or Average 0.464578E+11         0.433762E+10        
Minimum of Months 0.217583E+09 1701.50   1.13 -2.8 0.273062E+09 442.74   1.13 -2.8
Maximum of Months 0.971007E+10 21293.57   28.90 21.71 0.445348E+09 560.89   29.40 19.25



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.134379E+10 8855.22 19-JAN-13:50 9.40 3.78 0.507356E+09 845.64 30-JAN-14:30 2.80 -1.1
February 0.173311E+10 9603.48 02-FEB-14:20 5.40 -1.3 0.468306E+09 845.64 10-FEB-14:20 2.97 -0.3
March 0.361066E+10 13234.09 03-MAR-13:40 14.80 8.43 0.587749E+09 845.65 01-MAR-14:50 14.80 8.43
April 0.437662E+10 14470.88 07-APR-12:40 26.33 16.06 0.545645E+09 846.34 07-APR-13:20 26.50 16.25
May 0.650924E+10 23794.92 29-MAY-12:13 28.33 17.95 0.631875E+09 891.73 30-MAY-13:00 29.40 16.93
June 0.935854E+10 15172.52 08-JUN-05:02 19.08 17.42 0.659344E+09 872.31 22-JUN-13:30 29.15 17.46
July 0.115990E+11 24299.51 30-JUL-13:32 27.20 24.02 0.616294E+09 862.78 11-JUL-13:00 27.20 24.02
August 0.142238E+11 23858.28 13-AUG-12:32 30.93 19.36 0.691357E+09 852.16 30-AUG-13:30 28.05 15.56
September 0.102845E+11 26184.92 04-SEP-11:52 26.10 17.79 0.605119E+09 870.51 01-SEP-13:50 26.10 17.79
October 0.883370E+10 23637.63 15-OCT-13:23 20.85 13.17 0.613206E+09 858.74 04-OCT-13:30 20.85 13.17
November 0.307069E+10 15345.22 02-NOV-13:20 15.77 8.37 0.539867E+09 845.76 02-NOV-13:00 16.10 8.71
December 0.161315E+10 8256.45 21-DEC-13:30 3.05 -1.7 0.496024E+09 845.64 14-DEC-14:09 3.05 -1.7
                     
Annual Sum or Average 0.765569E+11         0.696214E+10        
Minimum of Months 0.134379E+10 8256.45   3.05 -1.7 0.468306E+09 845.64   2.80 -1.7
Maximum of Months 0.142238E+11 26184.92   30.93 24.02 0.691357E+09 891.73   29.40 24.02



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.394358E+09 2304.73 20-JAN-16:00 7.20 3.80 0.303192E+09 486.19 20-JAN-16:10 6.93 3.71
February 0.494362E+09 2628.30 22-FEB-16:30 3.85 -0.7 0.278821E+09 521.16 22-FEB-16:40 3.67 -0.7
March 0.190219E+10 7250.86 29-MAR-16:00 7.20 4.88 0.353966E+09 544.94 02-MAR-14:00 7.20 4.88
April 0.329027E+10 19177.15 09-APR-16:51 16.10 13.79 0.340573E+09 544.96 10-APR-13:09 20.10 10.10
May 0.558572E+10 17229.03 29-MAY-14:13 25.93 17.30 0.403460E+09 553.83 30-MAY-13:00 29.40 16.93
June 0.821870E+10 21819.86 18-JUN-16:02 25.50 22.07 0.425021E+09 550.06 22-JUN-13:30 29.15 17.46
July 0.942488E+10 22945.55 09-JUL-15:21 27.20 24.16 0.397253E+09 553.65 11-JUL-13:00 28.90 17.83
August 0.104694E+11 21865.13 13-AUG-15:52 30.00 20.46 0.445553E+09 556.71 22-AUG-15:30 29.70 17.33
September 0.594651E+10 22558.35 10-SEP-16:52 22.80 12.70 0.384033E+09 544.97 11-SEP-13:09 20.60 12.01
October 0.407809E+10 10766.02 04-OCT-15:30 23.35 19.12 0.372944E+09 544.95 02-OCT-13:20 23.35 19.12
November 0.123084E+10 4847.76 03-NOV-15:30 16.10 10.65 0.314158E+09 544.88 03-NOV-13:00 16.10 10.65
December 0.435626E+09 2223.96 08-DEC-15:40 6.30 2.04 0.292702E+09 473.97 08-DEC-15:50 6.20 1.96
                     
Annual Sum or Average 0.514709E+11         0.431168E+10        
Minimum of Months 0.394358E+09 2223.96   3.85 -0.7 0.278821E+09 473.97   3.67 -0.7
Maximum of Months 0.104694E+11 22945.55   30.00 24.16 0.445553E+09 556.71   29.70 19.12



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288237E+09 3206.76 14-JAN-06:01 -7.8 -8.5 0.00 0.00 01-JAN-00:10 -7.8 -8.5
February 0.341578E+09 4721.37 06-FEB-05:01 -13.2 -14.5 0.00 0.00 01-FEB-00:10 -13.2 -14.5
March 0.151849E+10 3458.53 31-MAR-05:10 5.10 5.10 0.00 0.00 01-MAR-00:10 5.10 5.10
April 0.353341E+10 8349.65 10-APR-05:13 15.20 13.76 0.00 0.00 01-APR-00:10 15.20 13.76
May 0.508543E+10 12082.22 30-MAY-05:15 18.53 14.51 0.00 0.00 01-MAY-00:10 18.53 14.51
June 0.800837E+10 9709.11 12-JUN-05:15 18.50 17.63 0.00 0.00 01-JUN-00:10 18.50 17.63
July 0.950605E+10 12396.08 10-JUL-05:15 26.10 20.74 0.00 0.00 01-JUL-00:10 26.10 20.74
August 0.108666E+11 13506.91 14-AUG-05:15 22.57 20.98 0.00 0.00 01-AUG-00:10 22.57 20.98
September 0.660357E+10 12389.63 05-SEP-05:15 20.60 18.00 0.00 0.00 01-SEP-00:10 20.60 18.00
October 0.518235E+10 8235.25 23-OCT-05:13 13.13 11.01 0.00 0.00 01-OCT-00:10 13.13 11.01
November 0.197702E+10 5306.24 13-NOV-06:15 5.77 4.71 0.00 0.00 01-NOV-00:10 5.77 4.71
December 0.810363E+09 3401.73 18-DEC-06:08 0.60 -1.3 0.00 0.00 01-DEC-00:10 0.60 -1.3
                     
Annual Sum or Average 0.537215E+11         0.00        
Minimum of Months 0.288237E+09 3206.76   -13.2 -14.5 0.00 0.00   -13.2 -14.5
Maximum of Months 0.108666E+11 13506.91   26.10 20.98 0.00 0.00   26.10 20.98



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 95633488.82 5546.45 14-JAN-04:01 -6.8 -7.5 0.00 0.00 01-JAN-00:10 -6.8 -7.5
February 0.105149E+09 6177.63 05-FEB-22:51 -12.2 -14.0 0.00 0.00 01-FEB-00:10 -12.2 -14.0
March 0.408577E+09 5201.61 13-MAR-04:01 -0.1 -3.5 0.00 0.00 01-MAR-00:10 -0.1 -3.5
April 0.139014E+10 3752.97 10-APR-05:10 15.10 13.73 0.00 0.00 01-APR-00:10 15.10 13.73
May 0.322065E+10 7006.16 30-MAY-13:35 29.60 17.29 0.00 0.00 01-MAY-00:10 29.60 17.29
June 0.614503E+10 7475.25 20-JUN-13:30 26.95 17.82 0.00 0.00 01-JUN-00:10 26.95 17.82
July 0.747646E+10 7977.59 11-JUL-14:50 28.40 17.63 0.00 0.00 01-JUL-00:10 28.40 17.63
August 0.831204E+10 9585.18 07-AUG-05:15 19.40 16.84 0.00 0.00 01-AUG-00:10 19.40 16.84
September 0.498900E+10 9334.56 01-SEP-14:15 30.93 17.38 0.00 0.00 01-SEP-00:10 30.93 17.38
October 0.275922E+10 5063.56 05-OCT-05:13 15.60 14.70 0.00 0.00 01-OCT-00:10 15.60 14.70
November 0.536853E+09 5074.35 22-NOV-05:01 -2.2 -3.3 0.00 0.00 01-NOV-00:10 -2.2 -3.3
December 0.107523E+09 6049.39 02-DEC-05:01 1.10 -2.4 0.00 0.00 01-DEC-00:10 1.10 -2.4
                     
Annual Sum or Average 0.355463E+11         0.00        
Minimum of Months 95633488.82 3752.97   -12.2 -14.0 0.00 0.00   -12.2 -14.0
Maximum of Months 0.831204E+10 9585.18   30.93 17.82 0.00 0.00   30.93 17.82



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 -9.6 -11.5 0.00 0.00 01-JAN-00:10 -9.6 -11.5
February 1000283.73 298.64 17-FEB-13:00 6.70 1.56 0.00 0.00 01-FEB-00:10 6.70 1.56
March 0.582434E+09 5014.87 03-MAR-14:40 15.00 8.47 0.00 0.00 01-MAR-00:10 15.00 8.47
April 0.244079E+10 13190.03 07-APR-13:30 26.40 16.17 0.00 0.00 01-APR-00:10 26.40 16.17
May 0.613902E+10 20739.38 30-MAY-13:05 29.90 17.82 0.00 0.00 01-MAY-00:10 29.90 17.82
June 0.110272E+11 21693.77 19-JUN-13:50 34.50 23.73 0.00 0.00 01-JUN-00:10 34.50 23.73
July 0.136769E+11 20420.27 10-JUL-14:10 32.88 20.91 0.00 0.00 01-JUL-00:10 32.88 20.91
August 0.145591E+11 20693.14 22-AUG-14:20 30.73 18.19 0.00 0.00 01-AUG-00:10 30.73 18.19
September 0.706132E+10 17971.21 01-SEP-14:00 31.10 17.34 0.00 0.00 01-SEP-00:10 31.10 17.34
October 0.336570E+10 11076.43 04-OCT-14:50 23.98 19.09 0.00 0.00 01-OCT-00:10 23.98 19.09
November 0.213177E+09 3493.69 04-NOV-13:10 17.62 12.77 0.00 0.00 01-NOV-00:10 17.62 12.77
December 0.00 0.00 01-DEC-00:10 5.97 2.86 0.00 0.00 01-DEC-00:10 5.97 2.86
                     
Annual Sum or Average 0.590666E+11         0.00        
Minimum of Months 0.00 0.00   -9.6 -11.5 0.00 0.00   -9.6 -11.5
Maximum of Months 0.145591E+11 21693.77   34.50 23.73 0.00 0.00   34.50 23.73



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.235293E+10 1934.41 20-JAN-16:30 6.40 3.51 95227794.89 126.83 24-JAN-14:00 11.00 11.00
February 0.724080E+10 3979.31 22-FEB-16:50 3.48 -0.7 86396473.91 126.82 22-FEB-10:09 3.48 -0.7
March 0.140437E+11 6935.85 31-MAR-24:00 5.40 5.40 0.103237E+09 126.83 27-MAR-13:39 5.40 5.40
April 0.187468E+11 8071.72 23-APR-17:45 12.38 8.83 91605457.19 126.83 17-APR-09:00 12.38 8.83
May 0.437831E+10 3522.82 31-MAY-24:00 18.50 16.73 99238219.21 126.85 31-MAY-13:20 18.50 16.73
June 0.936771E+10 5342.74 30-JUN-24:00 20.00 19.21 98973713.06 126.86 15-JUN-13:00 20.00 19.21
July 0.147530E+11 7222.48 31-JUL-23:57 23.90 22.01 91892016.63 126.85 28-JUL-09:09 23.90 22.01
August 0.198873E+11 7984.20 13-AUG-18:12 27.80 20.19 0.103804E+09 133.39 16-AUG-13:00 32.20 25.36
September 0.439284E+10 3414.15 30-SEP-24:00 12.60 11.96 91611012.42 126.85 05-SEP-13:09 12.60 11.96
October 0.946356E+10 5136.44 31-OCT-24:00 10.60 9.48 95237801.29 126.85 24-OCT-09:00 10.60 9.48
November 0.135509E+11 5843.07 03-NOV-16:00 15.00 10.26 94301198.15 126.84 10-NOV-10:00 15.60 14.59
December 0.188388E+11 7701.48 18-DEC-16:00 5.60 2.49 91880795.25 126.82 21-DEC-10:09 0.78 -2.5
                     
Annual Sum or Average 0.137017E+12         0.114340E+10        
Minimum of Months 0.235293E+10 1934.41   3.48 -0.7 86396473.91 126.82   0.78 -2.5
Maximum of Months 0.198873E+11 8071.72   27.80 22.01 0.103804E+09 133.39   32.20 25.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.486441E+09 1540.40 20-JAN-16:40 6.13 3.40 93661360.81 126.83 24-JAN-10:50 10.60 10.60
February 0.465403E+10 3543.81 22-FEB-17:00 3.30 -0.7 86396479.90 126.82 22-FEB-10:09 3.30 -0.7
March 0.116481E+11 6009.06 31-MAR-23:50 5.53 5.53 0.103237E+09 126.83 06-MAR-14:00 5.53 5.53
April 0.168177E+11 7497.51 09-APR-17:30 15.55 13.44 91605513.83 126.83 17-APR-09:00 13.30 12.36
May 0.365381E+10 3350.89 31-MAY-24:00 18.50 16.73 99235508.31 126.84 31-MAY-09:00 18.50 16.73
June 0.878403E+10 5034.59 30-JUN-24:00 20.00 19.21 98972899.66 126.86 15-JUN-13:00 20.00 19.21
July 0.140600E+11 6968.16 31-JUL-23:57 23.90 22.01 91892714.40 126.85 18-JUL-09:00 23.90 22.01
August 0.189266E+11 7605.39 31-AUG-17:30 25.30 22.17 0.103745E+09 133.65 16-AUG-13:00 25.30 22.17
September 0.380004E+10 3073.88 30-SEP-23:40 12.87 12.13 91609132.16 126.84 01-SEP-09:09 12.87 12.13
October 0.821584E+10 4404.44 31-OCT-24:00 10.60 9.48 95237291.86 126.85 06-OCT-09:50 10.60 9.48
November 0.109912E+11 5470.13 03-NOV-16:00 15.00 10.26 94301110.94 126.84 10-NOV-10:50 15.68 14.79
December 0.153923E+11 7030.62 21-DEC-16:10 2.62 -2.3 91880825.70 126.82 21-DEC-10:09 2.62 -2.3
                     
Annual Sum or Average 0.117430E+12         0.114178E+10        
Minimum of Months 0.486441E+09 1540.40   2.62 -2.3 86396479.90 126.82   2.62 -2.3
Maximum of Months 0.189266E+11 7605.39   25.30 22.17 0.103745E+09 133.65   25.30 22.17



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.226279E+09 1423.12 19-JAN-16:30 8.05 2.65 91034777.73 128.07 18-JAN-10:09 8.05 2.65
February 0.314167E+10 3401.59 02-FEB-17:00 2.80 -3.1 86395831.85 126.82 22-FEB-10:09 0.87 -3.0
March 0.102025E+11 5539.09 29-MAR-17:00 6.10 4.33 0.103237E+09 126.83 06-MAR-14:00 6.10 4.33
April 0.158588E+11 7567.06 09-APR-17:30 15.55 13.44 91605557.99 126.83 17-APR-09:00 13.30 12.36
May 0.327413E+10 3321.63 31-MAY-24:00 18.50 16.73 99236564.25 126.85 31-MAY-13:00 18.50 16.73
June 0.877704E+10 4951.34 30-JUN-24:00 20.00 19.21 98973373.17 126.86 15-JUN-13:00 20.00 19.21
July 0.141607E+11 6971.72 31-JUL-23:57 23.90 22.01 91893008.27 126.85 20-JUL-09:00 23.90 22.01
August 0.189878E+11 7750.83 13-AUG-17:40 29.07 20.11 0.103553E+09 132.11 16-AUG-13:00 32.20 25.36
September 0.356592E+10 2808.19 30-SEP-23:20 13.13 12.30 91609330.71 126.85 06-SEP-13:00 13.13 12.30
October 0.734514E+10 3908.63 04-OCT-16:00 22.80 19.11 95237369.40 126.85 24-OCT-13:00 22.20 19.22
November 0.934213E+10 5434.26 03-NOV-16:00 15.00 10.26 94301129.09 126.84 10-NOV-10:50 15.68 14.79
December 0.134180E+11 6807.94 08-DEC-16:10 5.92 1.77 91880834.29 126.82 21-DEC-10:09 0.78 -2.5
                     
Annual Sum or Average 0.108300E+12         0.113896E+10        
Minimum of Months 0.226279E+09 1423.12   2.80 -3.1 86395831.85 126.82   0.78 -3.0
Maximum of Months 0.189878E+11 7750.83   29.07 22.01 0.103553E+09 132.11   32.20 25.36



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.234911E+12 91147.31 20-JAN-17:00 5.60 3.19 0.206164E+10 2746.94 26-JAN-10:00 3.30 -0.4
February 0.433152E+12 182527.00 22-FEB-17:00 3.30 -0.7 0.187129E+10 2749.18 13-FEB-10:20 3.30 -0.7
March 0.727771E+12 358031.60 31-MAR-24:00 5.40 5.40 0.223552E+10 2749.46 22-MAR-13:09 5.40 5.40
April 0.941832E+12 367103.26 10-APR-16:00 20.00 11.13 0.198542E+10 2940.86 07-APR-13:39 20.00 11.13
May 0.239862E+12 175884.78 31-MAY-24:00 18.50 16.73 0.214836E+10 2746.52 18-MAY-13:00 18.50 16.73
June 0.469954E+12 267492.19 30-JUN-24:00 20.00 19.21 0.214255E+10 2746.50 15-JUN-13:00 20.00 19.21
July 0.731902E+12 359805.13 31-JUL-23:57 23.90 22.01 0.198919E+10 2745.89 18-JUL-09:00 23.90 22.01
August 0.974914E+12 369565.33 18-AUG-23:15 23.13 17.02 0.246909E+10 3494.74 16-AUG-13:00 23.13 17.02
September 0.235894E+12 176249.20 30-SEP-24:00 12.60 11.96 0.198339E+10 2746.92 14-SEP-09:00 12.60 11.96
October 0.487831E+12 267951.31 31-OCT-24:00 10.60 9.48 0.206180E+10 2747.19 26-OCT-13:09 10.60 9.48
November 0.707543E+12 276238.39 06-NOV-17:00 11.70 7.36 0.204175E+10 2748.22 22-NOV-14:09 2.02 -1.8
December 0.974956E+12 367311.32 18-DEC-17:00 3.30 0.83 0.199010E+10 2748.59 22-DEC-14:09 1.20 -2.7
                     
Annual Sum or Average 0.716052E+13         0.249801E+11        
Minimum of Months 0.234911E+12 91147.31   3.30 -0.7 0.187129E+10 2745.89   1.20 -2.7
Maximum of Months 0.974956E+12 369565.33   23.90 22.01 0.246909E+10 3494.74   23.90 22.01



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 68145517.97 10425.49 24-JAN-05:50 10.92
February 58645315.32 10340.94 21-FEB-04:04 1.78
March 0.102354E+09 10805.86 29-MAR-04:05 2.20
April 0.137189E+09 10933.91 24-APR-03:05 7.88
May 0.201060E+09 12175.24 29-MAY-18:53 25.00
June 0.180938E+09 10519.03 10-JUN-04:07 16.28
July 0.355380E+09 12639.76 25-JUL-03:53 23.30
August 0.418096E+09 13016.42 12-AUG-16:02 27.80
September 0.490355E+09 12347.72 14-SEP-03:53 22.20
October 0.594492E+09 12695.24 25-OCT-03:53 17.20
November 0.436900E+09 10757.46 13-NOV-04:17 5.60
December 0.144433E+09 10643.15 26-DEC-05:15 5.77
         
Annual Sum or Average 0.318799E+10      
Minimum of Months 58645315.32 10340.94   1.78
Maximum of Months 0.594492E+09 13016.42   27.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 -9.6
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.104757E+10 55499.59 02-JAN-04:01 -11.8
February 0.115526E+09 45589.40 06-FEB-05:01 -13.2
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 310385.58 3621.17 27-NOV-06:01 6.78
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.116341E+10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.104757E+10 55499.59   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.473768E+10 79287.91 02-JAN-04:01 -11.8
February 0.329236E+10 77752.96 06-FEB-04:01 -13.3
March 0.688874E+09 71250.63 20-MAR-04:01 -0.8
April 0.126538E+09 67999.26 03-APR-04:01 2.80
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 1398972.70 9326.48 30-OCT-05:03 11.93
November 0.123151E+10 73443.05 24-NOV-04:01 -3.4
December 0.170864E+10 73984.87 26-DEC-04:01 5.60
         
Annual Sum or Average 0.117870E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.473768E+10 79287.91   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.351818E+09 12258.32 02-JAN-05:01 -12.1
February 0.246020E+09 12301.73 06-FEB-05:01 -13.2
March 107059.90 1427.47 17-MAR-05:01 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 877713.76 8353.23 22-NOV-06:01 -2.2
December 278709.42 3355.85 02-DEC-06:01 1.10
         
Annual Sum or Average 0.599101E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.351818E+09 12301.73   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.242699E+09 11519.33 02-JAN-05:01 -12.1
February 0.150112E+09 11581.43 06-FEB-05:01 -13.2
March 2345834.58 8819.13 17-MAR-05:01 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 3539907.77 8860.58 22-NOV-06:01 -2.2
December 6384185.72 8775.44 02-DEC-06:01 1.10
         
Annual Sum or Average 0.405081E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.242699E+09 11581.43   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.470033E+09 17511.63 02-JAN-04:01 -11.8
February 0.263453E+09 16547.15 06-FEB-05:01 -13.2
March 9725512.15 13483.84 17-MAR-05:01 -1.1
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 11704005.16 13495.77 24-NOV-06:01 -4.4
December 20123972.10 13453.56 07-DEC-06:01 0.10
         
Annual Sum or Average 0.775039E+09      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 0.470033E+09 17511.63   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 42099436.12 10000.62 02-JAN-05:01 -12.1
February 19568103.98 9668.38 06-FEB-05:01 -13.2
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 61667540.10      
Minimum of Months 0.00 0.00   -13.2
Maximum of Months 42099436.12 10000.62   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.478531E+10 13756.86 01-JAN-15:22 -2.8
February 0.382517E+10 13644.49 06-FEB-00:51 -13.3
March 0.799958E+09 12243.12 13-MAR-03:01 0.50
April 0.113947E+09 11328.61 03-APR-04:01 2.80
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 5836668.74 10360.56 28-OCT-05:02 3.90
November 0.856838E+09 12731.22 24-NOV-04:01 -3.4
December 0.208036E+10 13411.75 31-DEC-21:52 -7.2
         
Annual Sum or Average 0.124674E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.478531E+10 13756.86   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.271862E+10 16633.21 02-JAN-00:02 -10.7
February 0.184471E+10 16591.55 06-FEB-00:51 -13.3
March 0.381563E+09 14742.09 13-MAR-03:01 0.50
April 65260368.22 13534.38 03-APR-04:01 2.80
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 1710659.77 6286.70 28-OCT-05:02 3.90
November 0.445509E+09 15320.60 24-NOV-04:01 -3.4
December 0.115768E+10 15976.39 31-DEC-21:52 -7.2
         
Annual Sum or Average 0.661506E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.271862E+10 16633.21   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.286384E+10 18816.96 02-JAN-00:02 -10.7
February 0.172736E+10 18684.87 06-FEB-04:11 -13.3
March 0.390551E+09 16208.02 17-MAR-04:01 -1.6
April 80154219.66 15059.62 03-APR-04:01 2.80
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.373080E+09 16256.49 24-NOV-05:01 -4.0
December 0.109284E+10 16806.43 11-DEC-04:01 1.70
         
Annual Sum or Average 0.652782E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.286384E+10 18816.96   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.222264E+10 17206.93 02-JAN-00:02 -10.7
February 0.155062E+10 17174.80 06-FEB-04:11 -13.3
March 0.232642E+09 14787.69 13-MAR-04:01 -0.1
April 30184033.05 13261.02 03-APR-05:01 2.70
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 320197.04 2366.57 28-OCT-05:02 3.90
November 0.333383E+09 15415.00 24-NOV-04:01 -3.4
December 0.774440E+09 14980.62 11-DEC-05:01 1.70
         
Annual Sum or Average 0.514424E+10      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.222264E+10 17206.93   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.916142E+10 16514.81 16-JAN-06:12 -4.8
February 0.812607E+10 16610.30 06-FEB-01:01 -13.3
March 0.294541E+10 15610.26 13-MAR-03:01 0.50
April 0.860403E+09 15237.81 03-APR-03:01 3.22
May 24139727.55 12214.02 01-MAY-05:03 6.28
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.239728E+09 13394.57 28-OCT-04:02 4.32
November 0.313709E+10 16110.95 23-NOV-23:42 -3.2
December 0.627818E+10 16466.04 31-DEC-19:52 -6.1
         
Annual Sum or Average 0.307724E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.916142E+10 16610.30   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.527349E+10 17448.91 16-JAN-06:12 -4.8
February 0.420653E+10 17555.71 06-FEB-01:01 -13.3
March 0.140951E+10 16583.19 13-MAR-03:01 0.50
April 0.469598E+09 15961.03 03-APR-03:01 3.22
May 11733216.35 8874.12 01-MAY-05:03 6.28
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.102206E+09 13940.89 28-OCT-04:02 4.32
November 0.160870E+10 16908.47 23-NOV-23:42 -3.2
December 0.342284E+10 17373.66 31-DEC-19:52 -6.1
         
Annual Sum or Average 0.165046E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.527349E+10 17555.71   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.608040E+10 21267.55 16-JAN-06:12 -4.8
February 0.459700E+10 21267.97 06-FEB-01:01 -13.3
March 0.170756E+10 20089.11 13-MAR-03:01 0.50
April 0.653672E+09 19075.15 03-APR-03:01 3.22
May 25306579.09 14134.29 01-MAY-05:03 6.28
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 65703450.02 15792.58 27-OCT-05:02 6.02
November 0.171101E+10 19779.71 27-NOV-04:01 6.60
December 0.376278E+10 20945.50 31-DEC-19:52 -6.1
         
Annual Sum or Average 0.186034E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.608040E+10 21267.97   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.457371E+10 18955.04 02-JAN-00:02 -10.7
February 0.359368E+10 19039.72 06-FEB-01:01 -13.3
March 0.978588E+09 17867.61 13-MAR-03:01 0.50
April 0.277738E+09 16090.29 22-APR-04:11 5.60
May 4121214.69 8498.39 01-MAY-05:03 6.28
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 59897230.95 12352.93 28-OCT-04:02 4.32
November 0.128134E+10 17515.95 20-NOV-04:01 0.60
December 0.253940E+10 18567.23 31-DEC-21:52 -7.2
         
Annual Sum or Average 0.133085E+11      
Minimum of Months 0.00 0.00   -13.3
Maximum of Months 0.457371E+10 19039.72   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.166245E+10 12857.62 18-JAN-06:01 7.38
February 0.114428E+10 12052.39 17-FEB-06:01 0.60
March 0.192492E+09 13290.12 13-MAR-04:01 -0.1
April 0.187981E+09 12790.53 03-APR-04:01 2.80
May 87998368.20 10190.89 01-MAY-03:02 7.45
June 84423112.62 9910.42 12-JUN-03:02 18.90
July 90934005.86 7423.60 01-JUL-03:02 20.00
August 64959753.08 8439.51 13-AUG-15:01 30.50
September 77782048.99 9219.72 25-SEP-03:02 13.98
October 0.112477E+09 10327.69 10-OCT-03:02 10.60
November 0.145325E+09 14110.15 24-NOV-05:01 -4.0
December 0.244912E+09 14492.81 11-DEC-05:01 1.70
         
Annual Sum or Average 0.409601E+10      
Minimum of Months 64959753.08 7423.60   -4.0
Maximum of Months 0.166245E+10 14492.81   30.50



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.507270E+10 19232.34 02-JAN-06:12 -11.7
February 0.322701E+10 8754.08 06-FEB-06:03 -12.9
March 0.166080E+10 8427.33 28-MAR-05:03 9.50
April 0.496914E+09 8108.39 25-APR-05:02 9.60
May 62775176.66 7996.55 03-MAY-05:03 11.78
June 47973470.34 7311.53 12-JUN-03:02 18.90
July 59671007.13 7189.69 21-JUL-03:02 24.90
August 50549354.20 7227.52 02-AUG-03:02 25.00
September 65114738.82 6845.31 18-SEP-03:02 16.70
October 77703117.05 7243.63 10-OCT-05:03 9.72
November 0.118444E+10 7531.10 10-NOV-06:03 14.60
December 0.216223E+10 6560.61 03-DEC-12:53 8.30
         
Annual Sum or Average 0.141679E+11      
Minimum of Months 47973470.34 6560.61   -12.9
Maximum of Months 0.507270E+10 19232.34   25.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.119135E+11 27892.04 02-JAN-05:09 -12.1
February 0.100049E+11 29364.48 06-FEB-05:10 -13.2
March 0.453508E+10 21505.04 13-MAR-05:12 -0.6
April 0.187746E+10 14941.52 10-APR-05:02 15.10
May 0.327030E+09 16344.12 16-MAY-05:02 9.18
June 77686886.85 13967.31 03-JUN-05:03 13.48
July 53425410.21 10448.69 05-JUL-03:02 20.10
August 70407620.64 10778.42 08-AUG-04:03 15.50
September 0.196516E+09 14667.59 29-SEP-05:03 11.78
October 0.959540E+09 15726.72 16-OCT-05:03 8.90
November 0.503850E+10 23048.09 24-NOV-05:12 -4.1
December 0.876136E+10 20736.19 11-DEC-05:12 1.70
         
Annual Sum or Average 0.438154E+11      
Minimum of Months 53425410.21 10448.69   -13.2
Maximum of Months 0.119135E+11 29364.48   20.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 7167129.88 436.15 01-JAN-09:58 -2.2
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 7167129.88      
Minimum of Months 0.00 0.00   -2.2
Maximum of Months 7167129.88 436.15   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.456777E+09 549.59 16-JAN-18:00 3.90
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.456777E+09      
Minimum of Months 0.00 0.00   -1.1
Maximum of Months 0.456777E+09 549.59   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.732349E+09 578.08 29-JAN-17:50 0.18
February 67959135.76 525.80 05-FEB-23:17 -12.6
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 849251.02 355.74 01-MAY-03:55 6.70
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.801157E+09      
Minimum of Months 0.00 0.00   -12.6
Maximum of Months 0.732349E+09 578.08   23.90



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:01 -9.6
February 0.00 0.00 01-FEB-00:10 -1.1
March 0.00 0.00 01-MAR-00:10 5.52
April 0.00 0.00 01-APR-00:10 5.27
May 0.00 0.00 01-MAY-00:10 10.33
June 0.00 0.00 01-JUN-00:10 18.37
July 0.00 0.00 01-JUL-00:10 20.00
August 0.00 0.00 01-AUG-00:03 23.90
September 0.00 0.00 01-SEP-00:03 23.43
October 0.00 0.00 01-OCT-00:10 12.47
November 0.00 0.00 01-NOV-00:10 10.40
December 0.00 0.00 01-DEC-00:10 5.97
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -9.6
Maximum of Months 0.00 0.00   23.90



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.148304E+11 15519.45 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.134523E+11 15519.45 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.159851E+11 15519.45 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.142779E+11 15519.45 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.154078E+11 15519.45 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.153333E+11 15519.45 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.143524E+11 15519.45 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.159851E+11 15519.45 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.142779E+11 15519.45 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.148304E+11 15519.45 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.146566E+11 15519.45 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.143524E+11 15519.45 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.177742E+12     0.424397E+12    
Minimum of Months 0.134523E+11 15519.45   0.325565E+11 13457.54  
Maximum of Months 0.159851E+11 15519.45   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321286E+12    
Minimum of Months 0.120811E+11 13937.56   0.244881E+11 18128.59  
Maximum of Months 0.143557E+11 13937.56   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.125601E+10 1750.00 02-JAN-16:40 0.339718E+10 2276.32 02-JAN-08:09
February 0.108653E+10 1633.24 01-FEB-16:00 0.307485E+10 2276.32 01-FEB-08:09
March 0.123764E+10 1405.53 02-MAR-16:00 0.352283E+10 2276.32 01-MAR-08:09
April 0.107705E+10 1075.02 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.114469E+10 1075.02 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.112873E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.106210E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.119334E+10 1075.02 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.109024E+10 1294.12 27-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.116309E+10 1487.71 31-OCT-15:00 0.339809E+10 2276.32 02-OCT-07:10
November 0.121639E+10 1750.00 06-NOV-16:49 0.332024E+10 2276.32 01-NOV-07:10
December 0.123376E+10 1750.00 01-DEC-16:30 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.138896E+11     0.403423E+11    
Minimum of Months 0.106210E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.125601E+10 1750.00   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.804202E+09 1127.77 02-JAN-16:40 0.218927E+10 1466.95 02-JAN-08:09
February 0.698040E+09 1061.30 01-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.797944E+09 974.86 02-MAR-16:00 0.227025E+10 1466.95 01-MAR-08:09
April 0.695582E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.740418E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.730635E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.687186E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.771443E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.703077E+09 692.79 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.749140E+09 965.84 31-OCT-15:00 0.218986E+10 1466.95 02-OCT-07:10
November 0.782643E+09 1127.77 06-NOV-16:49 0.213969E+10 1466.95 01-NOV-07:10
December 0.785576E+09 1127.77 01-DEC-16:30 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.894589E+10     0.259981E+11    
Minimum of Months 0.687186E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.804202E+09 1127.77   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.122940E+10 1750.04 02-JAN-16:40 0.339723E+10 2276.35 02-JAN-08:09
February 0.107000E+10 1624.97 15-FEB-16:00 0.307490E+10 2276.35 01-FEB-08:09
March 0.123291E+10 1327.90 02-MAR-16:00 0.352288E+10 2276.35 01-MAR-08:09
April 0.107845E+10 1075.05 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.114844E+10 1075.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.113347E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.106607E+10 1075.05 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.119615E+10 1075.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.108863E+10 1261.96 27-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.115388E+10 1451.01 31-OCT-15:00 0.339814E+10 2276.35 02-OCT-07:10
November 0.120121E+10 1750.04 06-NOV-16:49 0.332029E+10 2276.35 01-NOV-07:10
December 0.119793E+10 1750.04 01-DEC-16:30 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.137965E+11     0.403429E+11    
Minimum of Months 0.106607E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.123291E+10 1750.04   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.796967E+09 1127.77 02-JAN-16:40 0.218926E+10 1466.94 02-JAN-08:09
February 0.692505E+09 1042.73 15-FEB-16:00 0.198154E+10 1466.94 01-FEB-08:09
March 0.793991E+09 895.58 16-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.694811E+09 794.98 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.737878E+09 692.79 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.727940E+09 692.79 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.685157E+09 692.79 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.769291E+09 774.11 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.702154E+09 868.81 27-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.744930E+09 941.51 06-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.775868E+09 1127.77 06-NOV-16:49 0.213967E+10 1466.94 01-NOV-07:10
December 0.780572E+09 1127.77 01-DEC-16:30 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.890206E+10     0.259979E+11    
Minimum of Months 0.685157E+09 692.79   0.198154E+10 1466.94  
Maximum of Months 0.796967E+09 1127.77   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.125892E+10 1750.00 02-JAN-16:40 0.339718E+10 2276.32 02-JAN-08:09
February 0.108831E+10 1636.80 01-FEB-16:00 0.307485E+10 2276.32 01-FEB-08:09
March 0.123829E+10 1415.81 02-MAR-16:00 0.352283E+10 2276.32 01-MAR-08:09
April 0.107756E+10 1075.02 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.114505E+10 1075.02 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.112912E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.106248E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.119361E+10 1075.02 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.109095E+10 1307.46 27-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.116409E+10 1495.56 31-OCT-15:00 0.339809E+10 2276.32 02-OCT-07:10
November 0.121799E+10 1750.00 06-NOV-16:49 0.332024E+10 2276.32 01-NOV-07:10
December 0.123696E+10 1750.00 01-DEC-16:30 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.139033E+11     0.403423E+11    
Minimum of Months 0.106248E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.125892E+10 1750.00   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.804704E+09 1127.77 02-JAN-16:40 0.218927E+10 1466.95 02-JAN-08:09
February 0.698386E+09 1061.85 01-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.798111E+09 976.04 02-MAR-16:00 0.227025E+10 1466.95 01-MAR-08:09
April 0.695759E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.740533E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.730761E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.687318E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.771545E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.703288E+09 692.79 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.749457E+09 967.14 31-OCT-15:00 0.218986E+10 1466.95 02-OCT-07:10
November 0.782917E+09 1127.77 06-NOV-16:49 0.213969E+10 1466.95 01-NOV-07:10
December 0.786159E+09 1127.77 01-DEC-16:30 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.894894E+10     0.259981E+11    
Minimum of Months 0.687318E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.804704E+09 1127.77   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123090E+10 1750.04 02-JAN-16:40 0.339723E+10 2276.35 02-JAN-08:09
February 0.107084E+10 1628.89 15-FEB-16:00 0.307490E+10 2276.35 01-FEB-08:09
March 0.123214E+10 1319.38 16-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.107902E+10 1075.05 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.114883E+10 1075.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.113399E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.106661E+10 1075.05 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.119653E+10 1075.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.108927E+10 1276.50 27-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.115453E+10 1460.67 31-OCT-15:00 0.339814E+10 2276.35 02-OCT-07:10
November 0.120189E+10 1750.04 06-NOV-16:49 0.332029E+10 2276.35 01-NOV-07:10
December 0.119915E+10 1750.04 01-DEC-16:30 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.138037E+11     0.403429E+11    
Minimum of Months 0.106661E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.123214E+10 1750.04   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.797475E+09 1127.77 02-JAN-16:40 0.218926E+10 1466.94 02-JAN-08:09
February 0.692851E+09 1043.66 15-FEB-16:00 0.198154E+10 1466.94 01-FEB-08:09
March 0.794228E+09 897.38 16-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.694978E+09 797.10 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.737957E+09 692.79 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.728019E+09 692.79 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.685277E+09 692.79 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.769437E+09 776.76 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.702412E+09 870.78 27-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.745162E+09 942.95 06-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.776175E+09 1127.77 06-NOV-16:49 0.213967E+10 1466.94 01-NOV-07:10
December 0.781167E+09 1127.77 01-DEC-16:30 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.890514E+10     0.259979E+11    
Minimum of Months 0.685277E+09 692.79   0.198154E+10 1466.94  
Maximum of Months 0.797475E+09 1127.77   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.125888E+10 1750.00 02-JAN-16:40 0.339718E+10 2276.32 02-JAN-08:09
February 0.108831E+10 1636.72 01-FEB-16:00 0.307485E+10 2276.32 01-FEB-08:09
March 0.123827E+10 1415.71 02-MAR-16:00 0.352283E+10 2276.32 01-MAR-08:09
April 0.107755E+10 1075.02 03-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.114505E+10 1075.02 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.112911E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.106247E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.119361E+10 1075.02 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.109095E+10 1307.08 27-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.116409E+10 1495.32 31-OCT-15:00 0.339809E+10 2276.32 02-OCT-07:10
November 0.121798E+10 1750.00 06-NOV-16:49 0.332024E+10 2276.32 01-NOV-07:10
December 0.123696E+10 1750.00 01-DEC-16:30 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.139032E+11     0.403423E+11    
Minimum of Months 0.106247E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.125888E+10 1750.00   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.804698E+09 1127.77 02-JAN-16:40 0.218927E+10 1466.95 02-JAN-08:09
February 0.698388E+09 1061.80 01-FEB-16:00 0.198155E+10 1466.95 01-FEB-08:09
March 0.798113E+09 975.96 02-MAR-16:00 0.227025E+10 1466.95 01-MAR-08:09
April 0.695757E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.740533E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.730759E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.687315E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.771552E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.703288E+09 692.79 01-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.749464E+09 966.99 31-OCT-15:00 0.218986E+10 1466.95 02-OCT-07:10
November 0.782914E+09 1127.77 06-NOV-16:49 0.213969E+10 1466.95 01-NOV-07:10
December 0.786163E+09 1127.77 01-DEC-16:30 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.894894E+10     0.259981E+11    
Minimum of Months 0.687315E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.804698E+09 1127.77   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.123090E+10 1750.04 02-JAN-16:40 0.339723E+10 2276.35 02-JAN-08:09
February 0.107084E+10 1628.78 15-FEB-16:00 0.307490E+10 2276.35 01-FEB-08:09
March 0.123213E+10 1319.06 16-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.107902E+10 1075.05 03-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.114883E+10 1075.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.113398E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.106658E+10 1075.05 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.119653E+10 1075.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.108926E+10 1276.12 27-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.115453E+10 1460.45 31-OCT-15:00 0.339814E+10 2276.35 02-OCT-07:10
November 0.120189E+10 1750.04 06-NOV-16:49 0.332029E+10 2276.35 01-NOV-07:10
December 0.119915E+10 1750.04 01-DEC-16:30 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.138036E+11     0.403429E+11    
Minimum of Months 0.106658E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.123213E+10 1750.04   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.797433E+09 1127.77 02-JAN-16:40 0.218926E+10 1466.94 02-JAN-08:09
February 0.692815E+09 1043.60 15-FEB-16:00 0.198154E+10 1466.94 01-FEB-08:09
March 0.794229E+09 897.18 16-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.694977E+09 796.91 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.737958E+09 692.79 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.728018E+09 692.79 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.685279E+09 692.79 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.769441E+09 776.43 16-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.702411E+09 870.55 27-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.745162E+09 942.77 06-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.776176E+09 1127.77 06-NOV-16:49 0.213967E+10 1466.94 01-NOV-07:10
December 0.781173E+09 1127.77 01-DEC-16:30 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.890507E+10     0.259979E+11    
Minimum of Months 0.685279E+09 692.79   0.198154E+10 1466.94  
Maximum of Months 0.797433E+09 1127.77   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.418155E+10 4375.82 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.379298E+10 4375.82 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.450711E+10 4375.82 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.402577E+10 4375.82 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.434433E+10 4375.82 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.432333E+10 4375.82 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.404678E+10 4375.82 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.450711E+10 4375.82 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.402577E+10 4375.82 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.418155E+10 4375.82 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.413254E+10 4375.82 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.404678E+10 4375.82 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.501156E+11     0.749486E+13    
Minimum of Months 0.379298E+10 4375.82   0.246344E+12 94908.13  
Maximum of Months 0.450711E+10 4375.82   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.154078E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.153333E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.146566E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.177742E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.125601E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.146822E+10
February 0.136985E+10 0.108653E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.128944E+10
March 0.163685E+10 0.123764E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.108059E+10
April 0.145243E+10 0.107705E+10 0.328108E+10 0.00 0.00 0.00 0.00 503445.29 0.724671E+09
May 0.157338E+10 0.114469E+10 0.346000E+10 0.00 0.00 0.00 0.00 2451720.96 0.409631E+09
June 0.156900E+10 0.112873E+10 0.339353E+10 0.00 0.00 0.00 0.00 17095056.48 0.203270E+09
July 0.145680E+10 0.106210E+10 0.334664E+10 0.00 0.00 0.00 0.00 41619808.60 57892889.78
August 0.163685E+10 0.119334E+10 0.352283E+10 0.00 0.00 0.00 0.00 50670018.09 77094173.95
September 0.145243E+10 0.109024E+10 0.327926E+10 0.00 0.00 0.00 0.00 5864698.84 0.223834E+09
October 0.150991E+10 0.116309E+10 0.339809E+10 0.00 0.00 0.00 0.00 95394.76 0.567994E+09
November 0.149516E+10 0.121639E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.109061E+10
December 0.145680E+10 0.123376E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.130090E+10
                   
Annual Sum or Average 0.181194E+11 0.138896E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.118300E+09 0.849414E+10
Minimum of Months 0.136985E+10 0.106210E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 57892889.78
Maximum of Months 0.163685E+10 0.125601E+10 0.352283E+10 0.00 0.00 0.00 0.00 50670018.09 0.146822E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.804202E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.974278E+09
February 0.882782E+09 0.698040E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.862549E+09
March 0.105485E+10 0.797944E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.711227E+09
April 0.936002E+09 0.695582E+09 0.211446E+10 0.00 0.00 0.00 0.00 335608.87 0.474484E+09
May 0.101394E+10 0.740418E+09 0.222976E+10 0.00 0.00 0.00 0.00 1286464.60 0.273781E+09
June 0.101113E+10 0.730635E+09 0.218692E+10 0.00 0.00 0.00 0.00 11651618.74 0.130005E+09
July 0.938820E+09 0.687186E+09 0.215670E+10 0.00 0.00 0.00 0.00 29623575.80 31552260.46
August 0.105485E+10 0.771443E+09 0.227025E+10 0.00 0.00 0.00 0.00 35977903.91 44530025.91
September 0.936002E+09 0.703077E+09 0.211328E+10 0.00 0.00 0.00 0.00 3857294.14 0.150909E+09
October 0.973041E+09 0.749140E+09 0.218986E+10 0.00 0.00 0.00 0.00 63586.01 0.378198E+09
November 0.963541E+09 0.782643E+09 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.715894E+09
December 0.938820E+09 0.785576E+09 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.848280E+09
                   
Annual Sum or Average 0.116768E+11 0.894589E+10 0.259981E+11 0.00 0.00 0.00 0.00 82796052.07 0.559569E+10
Minimum of Months 0.882782E+09 0.687186E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 31552260.46
Maximum of Months 0.105485E+10 0.804202E+09 0.227025E+10 0.00 0.00 0.00 0.00 35977903.91 0.974278E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.122940E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.145778E+10
February 0.136988E+10 0.107000E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.131391E+10
March 0.163688E+10 0.123291E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.108067E+10
April 0.145246E+10 0.107845E+10 0.328113E+10 0.00 0.00 0.00 0.00 498117.80 0.719422E+09
May 0.157341E+10 0.114844E+10 0.346006E+10 0.00 0.00 0.00 0.00 1883772.63 0.408907E+09
June 0.156904E+10 0.113347E+10 0.339359E+10 0.00 0.00 0.00 0.00 16077201.79 0.204197E+09
July 0.145684E+10 0.106607E+10 0.334669E+10 0.00 0.00 0.00 0.00 39615887.46 60683516.46
August 0.163688E+10 0.119615E+10 0.352288E+10 0.00 0.00 0.00 0.00 48371253.45 83376724.38
September 0.145246E+10 0.108863E+10 0.327931E+10 0.00 0.00 0.00 0.00 5704137.08 0.238315E+09
October 0.150994E+10 0.115388E+10 0.339814E+10 0.00 0.00 0.00 0.00 85504.12 0.599041E+09
November 0.149520E+10 0.120121E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.108635E+10
December 0.145684E+10 0.119793E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.129389E+10
                   
Annual Sum or Average 0.181198E+11 0.137965E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.112236E+09 0.854654E+10
Minimum of Months 0.136988E+10 0.106607E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 60683516.46
Maximum of Months 0.163688E+10 0.123291E+10 0.352288E+10 0.00 0.00 0.00 0.00 48371253.45 0.145778E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.796967E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.102429E+10
February 0.882782E+09 0.692505E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.917519E+09
March 0.105485E+10 0.793991E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.793742E+09
April 0.936002E+09 0.694811E+09 0.211444E+10 0.00 0.00 0.00 0.00 328137.21 0.548358E+09
May 0.101394E+10 0.737878E+09 0.222974E+10 0.00 0.00 0.00 0.00 1560069.05 0.298540E+09
June 0.101113E+10 0.727940E+09 0.218691E+10 0.00 0.00 0.00 0.00 10415386.31 0.160846E+09
July 0.938820E+09 0.685157E+09 0.215669E+10 0.00 0.00 0.00 0.00 24321562.08 57840852.58
August 0.105485E+10 0.769291E+09 0.227023E+10 0.00 0.00 0.00 0.00 29301814.36 73035914.82
September 0.936002E+09 0.702154E+09 0.211327E+10 0.00 0.00 0.00 0.00 3831605.72 0.170012E+09
October 0.973041E+09 0.744930E+09 0.218984E+10 0.00 0.00 0.00 0.00 63608.04 0.422803E+09
November 0.963541E+09 0.775868E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.797943E+09
December 0.938820E+09 0.780572E+09 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.962742E+09
                   
Annual Sum or Average 0.116768E+11 0.890206E+10 0.259979E+11 0.00 0.00 0.00 0.00 69822182.75 0.622768E+10
Minimum of Months 0.882782E+09 0.685157E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 57840852.58
Maximum of Months 0.105485E+10 0.796967E+09 0.227023E+10 0.00 0.00 0.00 0.00 29301814.36 0.102429E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.125892E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.301128E+10
February 0.136985E+10 0.108831E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.268036E+10
March 0.163685E+10 0.123829E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.217705E+10
April 0.145243E+10 0.107756E+10 0.328108E+10 0.00 0.00 0.00 0.00 1110854.42 0.146185E+10
May 0.157338E+10 0.114505E+10 0.346000E+10 0.00 0.00 0.00 0.00 6627531.52 0.884710E+09
June 0.156900E+10 0.112912E+10 0.339353E+10 0.00 0.00 0.00 0.00 39363339.57 0.463599E+09
July 0.145680E+10 0.106248E+10 0.334664E+10 0.00 0.00 0.00 0.00 91613093.03 0.163732E+09
August 0.163685E+10 0.119361E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.110156E+09 0.210613E+09
September 0.145243E+10 0.109095E+10 0.327926E+10 0.00 0.00 0.00 0.00 13442186.47 0.479251E+09
October 0.150991E+10 0.116409E+10 0.339809E+10 0.00 0.00 0.00 0.00 173082.75 0.115964E+10
November 0.149516E+10 0.121799E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.212695E+10
December 0.145680E+10 0.123696E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.256091E+10
                   
Annual Sum or Average 0.181194E+11 0.139033E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.262486E+09 0.173799E+11
Minimum of Months 0.136985E+10 0.106248E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.163732E+09
Maximum of Months 0.163685E+10 0.125892E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.110156E+09 0.301128E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.804704E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.201451E+10
February 0.649041E+09 0.698386E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.181152E+10
March 0.773965E+09 0.798111E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.148164E+10
April 0.688021E+09 0.695759E+09 0.211446E+10 0.00 0.00 0.00 0.00 735169.11 0.101761E+10
May 0.744847E+09 0.740533E+09 0.222976E+10 0.00 0.00 0.00 0.00 2876536.26 0.605913E+09
June 0.742030E+09 0.730761E+09 0.218692E+10 0.00 0.00 0.00 0.00 25180801.47 0.315355E+09
July 0.690839E+09 0.687318E+09 0.215670E+10 0.00 0.00 0.00 0.00 59072412.56 0.112840E+09
August 0.773965E+09 0.771545E+09 0.227025E+10 0.00 0.00 0.00 0.00 70708765.73 0.148748E+09
September 0.688021E+09 0.703288E+09 0.211328E+10 0.00 0.00 0.00 0.00 8549665.79 0.338959E+09
October 0.715730E+09 0.749457E+09 0.218986E+10 0.00 0.00 0.00 0.00 115285.96 0.807795E+09
November 0.708685E+09 0.782917E+09 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.144450E+10
December 0.690839E+09 0.786159E+09 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.172233E+10
                   
Annual Sum or Average 0.858171E+10 0.894894E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.167239E+09 0.118217E+11
Minimum of Months 0.649041E+09 0.687318E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.112840E+09
Maximum of Months 0.773965E+09 0.804704E+09 0.227025E+10 0.00 0.00 0.00 0.00 70708765.73 0.201451E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.123090E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.312588E+10
February 0.136988E+10 0.107084E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.285859E+10
March 0.163688E+10 0.123214E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.233354E+10
April 0.145246E+10 0.107902E+10 0.328113E+10 0.00 0.00 0.00 0.00 1082193.39 0.155723E+10
May 0.157341E+10 0.114883E+10 0.346006E+10 0.00 0.00 0.00 0.00 4357435.75 0.913770E+09
June 0.156904E+10 0.113399E+10 0.339359E+10 0.00 0.00 0.00 0.00 36158703.50 0.473901E+09
July 0.145684E+10 0.106661E+10 0.334669E+10 0.00 0.00 0.00 0.00 86103169.03 0.174865E+09
August 0.163688E+10 0.119653E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.102882E+09 0.234415E+09
September 0.145246E+10 0.108927E+10 0.327931E+10 0.00 0.00 0.00 0.00 12666392.19 0.543624E+09
October 0.150994E+10 0.115453E+10 0.339814E+10 0.00 0.00 0.00 0.00 103521.65 0.133903E+10
November 0.149520E+10 0.120189E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.230243E+10
December 0.145684E+10 0.119915E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.274019E+10
                   
Annual Sum or Average 0.181198E+11 0.138037E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.243354E+09 0.185975E+11
Minimum of Months 0.136988E+10 0.106661E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.174865E+09
Maximum of Months 0.163688E+10 0.123214E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.102882E+09 0.312588E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.797475E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.205721E+10
February 0.882782E+09 0.692851E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.184467E+10
March 0.105485E+10 0.794228E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.154566E+10
April 0.936002E+09 0.694978E+09 0.211444E+10 0.00 0.00 0.00 0.00 739105.15 0.105257E+10
May 0.101394E+10 0.737957E+09 0.222974E+10 0.00 0.00 0.00 0.00 4012964.28 0.633626E+09
June 0.101113E+10 0.728019E+09 0.218691E+10 0.00 0.00 0.00 0.00 24457109.18 0.346785E+09
July 0.938820E+09 0.685277E+09 0.215669E+10 0.00 0.00 0.00 0.00 57867822.38 0.138926E+09
August 0.105485E+10 0.769437E+09 0.227023E+10 0.00 0.00 0.00 0.00 69014510.27 0.170821E+09
September 0.936002E+09 0.702412E+09 0.211327E+10 0.00 0.00 0.00 0.00 8707292.40 0.353203E+09
October 0.973041E+09 0.745162E+09 0.218984E+10 0.00 0.00 0.00 0.00 115423.07 0.842948E+09
November 0.963541E+09 0.776175E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.146697E+10
December 0.938820E+09 0.781167E+09 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.177089E+10
                   
Annual Sum or Average 0.116768E+11 0.890514E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.164914E+09 0.122243E+11
Minimum of Months 0.882782E+09 0.685277E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.138926E+09
Maximum of Months 0.105485E+10 0.797475E+09 0.227023E+10 0.00 0.00 0.00 0.00 69014510.27 0.205721E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.125888E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.362620E+10
February 0.136985E+10 0.108831E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.320654E+10
March 0.163685E+10 0.123827E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.251018E+10
April 0.145243E+10 0.107755E+10 0.328108E+10 0.00 0.00 0.00 0.00 1310253.39 0.165614E+10
May 0.157338E+10 0.114505E+10 0.346000E+10 0.00 0.00 0.00 0.00 6759830.70 0.103955E+10
June 0.156900E+10 0.112911E+10 0.339353E+10 0.00 0.00 0.00 0.00 44325626.91 0.577383E+09
July 0.145680E+10 0.106247E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.103976E+09 0.217905E+09
August 0.163685E+10 0.119361E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.130213E+09 0.265881E+09
September 0.145243E+10 0.109095E+10 0.327926E+10 0.00 0.00 0.00 0.00 15558888.51 0.567127E+09
October 0.150991E+10 0.116409E+10 0.339809E+10 0.00 0.00 0.00 0.00 160899.82 0.129943E+10
November 0.149516E+10 0.121798E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.238749E+10
December 0.145680E+10 0.123696E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.297353E+10
                   
Annual Sum or Average 0.181194E+11 0.139032E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.302305E+09 0.203273E+11
Minimum of Months 0.136985E+10 0.106247E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.217905E+09
Maximum of Months 0.163685E+10 0.125888E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.130213E+09 0.362620E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.804698E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.242738E+10
February 0.882782E+09 0.698388E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.216229E+10
March 0.105485E+10 0.798113E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.170846E+10
April 0.936002E+09 0.695757E+09 0.211446E+10 0.00 0.00 0.00 0.00 850331.76 0.116614E+10
May 0.101394E+10 0.740533E+09 0.222976E+10 0.00 0.00 0.00 0.00 3328268.80 0.720625E+09
June 0.101113E+10 0.730759E+09 0.218692E+10 0.00 0.00 0.00 0.00 29087548.77 0.395119E+09
July 0.938820E+09 0.687315E+09 0.215670E+10 0.00 0.00 0.00 0.00 68232329.55 0.149802E+09
August 0.105485E+10 0.771552E+09 0.227025E+10 0.00 0.00 0.00 0.00 84223138.41 0.188893E+09
September 0.936002E+09 0.703288E+09 0.211328E+10 0.00 0.00 0.00 0.00 10102336.33 0.407369E+09
October 0.973041E+09 0.749464E+09 0.218986E+10 0.00 0.00 0.00 0.00 107230.26 0.922501E+09
November 0.963541E+09 0.782914E+09 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.162285E+10
December 0.938820E+09 0.786163E+09 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.199862E+10
                   
Annual Sum or Average 0.116768E+11 0.894894E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.195931E+09 0.138700E+11
Minimum of Months 0.882782E+09 0.687315E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.149802E+09
Maximum of Months 0.105485E+10 0.804698E+09 0.227025E+10 0.00 0.00 0.00 0.00 84223138.41 0.242738E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.123090E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.372027E+10
February 0.136988E+10 0.107084E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.336447E+10
March 0.163688E+10 0.123213E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.268432E+10
April 0.145246E+10 0.107902E+10 0.328113E+10 0.00 0.00 0.00 0.00 1274171.22 0.177530E+10
May 0.157341E+10 0.114883E+10 0.346006E+10 0.00 0.00 0.00 0.00 5018230.52 0.107566E+10
June 0.156904E+10 0.113398E+10 0.339359E+10 0.00 0.00 0.00 0.00 42830009.06 0.588042E+09
July 0.145684E+10 0.106658E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.101217E+09 0.228264E+09
August 0.163688E+10 0.119653E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.123363E+09 0.295769E+09
September 0.145246E+10 0.108926E+10 0.327931E+10 0.00 0.00 0.00 0.00 15047560.57 0.651163E+09
October 0.150994E+10 0.115453E+10 0.339814E+10 0.00 0.00 0.00 0.00 137156.23 0.155253E+10
November 0.149520E+10 0.120189E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.257022E+10
December 0.145684E+10 0.119915E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.314008E+10
                   
Annual Sum or Average 0.181198E+11 0.138036E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.288887E+09 0.216461E+11
Minimum of Months 0.136988E+10 0.106658E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.228264E+09
Maximum of Months 0.163688E+10 0.123213E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.123363E+09 0.372027E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.797433E+09 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.246061E+10
February 0.882782E+09 0.692815E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.220320E+10
March 0.105485E+10 0.794229E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.179596E+10
April 0.936002E+09 0.694977E+09 0.211444E+10 0.00 0.00 0.00 0.00 872531.77 0.121695E+10
May 0.101394E+10 0.737958E+09 0.222974E+10 0.00 0.00 0.00 0.00 4567106.96 0.752115E+09
June 0.101113E+10 0.728018E+09 0.218691E+10 0.00 0.00 0.00 0.00 28948484.75 0.429964E+09
July 0.938820E+09 0.685279E+09 0.215669E+10 0.00 0.00 0.00 0.00 68441439.90 0.177750E+09
August 0.105485E+10 0.769441E+09 0.227023E+10 0.00 0.00 0.00 0.00 82996474.87 0.214103E+09
September 0.936002E+09 0.702411E+09 0.211327E+10 0.00 0.00 0.00 0.00 10258575.96 0.422921E+09
October 0.973041E+09 0.745162E+09 0.218984E+10 0.00 0.00 0.00 0.00 107310.36 0.972152E+09
November 0.963541E+09 0.776176E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.166415E+10
December 0.938820E+09 0.781173E+09 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.205522E+10
                   
Annual Sum or Average 0.116768E+11 0.890507E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.196192E+09 0.143651E+11
Minimum of Months 0.882782E+09 0.685279E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.177750E+09
Maximum of Months 0.105485E+10 0.797433E+09 0.227023E+10 0.00 0.00 0.00 0.00 82996474.87 0.246061E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.418155E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.379298E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.450711E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.402577E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.434433E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.432333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.404678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.450711E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.402577E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.418155E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.413254E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.404678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.501156E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.379298E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.450711E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.316667E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.279099E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.230406E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 677907.87 0.153789E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4508646.44 0.860409E+09
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 28637630.65 0.430084E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 72206944.74 0.131975E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83036159.30 0.181626E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7998683.05 0.477058E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17130.84 0.122311E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.233191E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.280962E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.197083E+09 0.182454E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131975E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83036159.30 0.316667E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.507263E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.460890E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.382398E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1378863.11 0.256118E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9860519.94 0.148804E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 52532241.47 0.756081E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.128922E+09 0.242696E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.146116E+09 0.337426E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14167532.58 0.826737E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 40056.66 0.208584E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.381567E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.454037E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.353017E+09 0.301596E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.242696E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.146116E+09 0.507263E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.534927E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.481262E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.399213E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 338521.18 0.269474E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3314314.36 0.168278E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 39482277.37 0.917546E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96715867.03 0.335862E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131172E+09 0.408953E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11597306.12 0.929970E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.217994E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.379009E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.453793E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.282621E+09 0.316318E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.335862E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.131172E+09 0.534927E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 15519.45 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 15519.45 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 15519.45 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 15519.45 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 15519.45 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 15519.45 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 15519.45 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 15519.45 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 15519.45 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 15519.45 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 15519.45 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 15519.45 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1750.00 02-JAN-16:40 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 2475.63 31-JAN-01:00
February 2010.79 01-FEB-10:09 1633.24 01-FEB-16:00 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2472.69 06-FEB-00:51
March 2010.79 01-MAR-10:09 1405.53 02-MAR-16:00 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1941.15 12-MAR-10:00
April 2010.79 03-APR-09:09 1075.02 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 29.53 07-APR-13:00 1530.36 11-APR-03:53
May 2010.79 01-MAY-09:09 1075.02 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 118.65 29-MAY-12:00 924.42 03-MAY-04:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 198.52 19-JUN-21:02 522.61 02-JUN-22:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 205.52 09-JUL-14:00 220.59 11-JUL-04:50
August 2010.79 01-AUG-09:09 1075.02 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 277.06 04-AUG-21:01 329.52 20-AUG-06:00
September 2010.79 01-SEP-09:09 1294.12 27-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 77.01 14-SEP-14:00 472.43 17-SEP-10:00
October 2010.79 02-OCT-09:09 1487.71 31-OCT-15:00 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 13.53 25-OCT-11:00 1326.91 08-OCT-08:00
November 2010.79 01-NOV-09:09 1750.00 06-NOV-16:49 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2056.21 23-NOV-02:00
December 2010.79 01-DEC-10:09 1750.00 01-DEC-16:30 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2664.11 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   220.59  
Maximum of Months 2010.79   1750.00   2276.32   0.00 0.00 0.00 0.00 277.06   2664.11  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-16:40 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 1649.27 31-JAN-01:00
February 1295.83 01-FEB-10:09 1061.30 01-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1720.55 05-FEB-08:50
March 1295.83 01-MAR-10:09 974.86 02-MAR-16:00 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1415.28 12-MAR-10:00
April 1295.83 03-APR-09:09 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 19.69 07-APR-13:00 991.51 11-APR-03:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 67.00 29-MAY-11:50 612.86 03-MAY-04:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 132.25 19-JUN-21:02 345.23 02-JUN-22:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 135.68 09-JUL-13:52 146.47 02-JUL-18:30
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 195.62 12-AUG-18:53 214.92 20-AUG-06:10
September 1295.83 01-SEP-09:09 692.79 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 51.34 14-SEP-14:00 308.64 17-SEP-10:00
October 1295.83 02-OCT-09:09 965.84 31-OCT-15:00 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 9.02 25-OCT-11:00 964.52 08-OCT-08:00
November 1295.83 01-NOV-09:09 1127.77 06-NOV-16:49 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1355.40 23-NOV-02:00
December 1295.83 01-DEC-10:09 1127.77 01-DEC-16:30 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1749.98 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   146.47  
Maximum of Months 1295.83   1127.77   1466.95   0.00 0.00 0.00 0.00 195.62   1749.98  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1750.04 02-JAN-16:40 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 2502.84 31-JAN-01:00
February 2010.83 01-FEB-10:09 1624.97 15-FEB-16:00 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 2432.79 05-FEB-09:00
March 2010.83 01-MAR-10:09 1327.90 02-MAR-16:00 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2075.89 12-MAR-10:00
April 2010.83 03-APR-09:09 1075.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 29.44 07-APR-13:00 1526.98 11-APR-03:53
May 2010.83 01-MAY-09:09 1075.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 88.55 29-MAY-11:53 918.46 03-MAY-04:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 197.82 19-JUN-21:02 527.32 02-JUN-22:00
July 2010.83 03-JUL-09:09 1075.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 198.59 09-JUL-13:52 229.77 02-JUL-18:30
August 2010.83 01-AUG-09:09 1075.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 276.03 04-AUG-21:01 334.96 20-AUG-06:00
September 2010.83 01-SEP-09:09 1261.96 27-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 76.92 14-SEP-14:00 482.29 30-SEP-24:00
October 2010.83 02-OCT-09:09 1451.01 31-OCT-15:00 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 13.48 25-OCT-11:00 1369.64 08-OCT-08:00
November 2010.83 01-NOV-09:09 1750.04 06-NOV-16:49 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2045.22 23-NOV-02:00
December 2010.83 01-DEC-10:09 1750.04 01-DEC-16:30 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2613.92 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   229.77  
Maximum of Months 2010.83   1750.04   2276.35   0.00 0.00 0.00 0.00 276.03   2613.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-16:40 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 1720.11 31-JAN-01:00
February 1295.83 01-FEB-10:09 1042.73 15-FEB-16:00 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 1731.44 05-FEB-08:00
March 1295.83 01-MAR-10:09 895.58 16-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 1455.61 12-MAR-10:00
April 1295.83 03-APR-09:09 794.98 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 19.69 07-APR-13:00 1142.87 11-APR-03:50
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 84.26 29-MAY-11:50 683.73 03-MAY-04:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 126.32 19-JUN-21:02 409.09 02-JUN-22:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 132.39 09-JUL-13:52 226.33 02-JUL-17:50
August 1295.83 01-AUG-09:09 774.11 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 178.94 04-AUG-21:01 269.92 20-AUG-06:00
September 1295.83 01-SEP-09:09 868.81 27-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 51.34 14-SEP-14:00 350.08 17-SEP-10:00
October 1295.83 02-OCT-09:09 941.51 06-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 9.02 25-OCT-11:00 961.94 08-OCT-08:00
November 1295.83 01-NOV-09:09 1127.77 06-NOV-16:49 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1483.44 23-NOV-02:00
December 1295.83 01-DEC-10:09 1127.77 01-DEC-16:30 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1943.78 31-DEC-21:52
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.94   0.00 0.00 0.00 0.00 0.00   226.33  
Maximum of Months 1295.83   1127.77   1466.94   0.00 0.00 0.00 0.00 178.94   1943.78  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1750.00 02-JAN-16:40 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5093.89 14-JAN-05:51
February 2010.79 01-FEB-10:09 1636.80 01-FEB-16:00 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5380.31 06-FEB-01:00
March 2010.79 01-MAR-10:09 1415.81 02-MAR-16:00 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4083.16 21-MAR-21:02
April 2010.79 03-APR-09:09 1075.02 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 66.46 07-APR-13:00 3164.57 11-APR-03:53
May 2010.79 01-MAY-09:09 1075.02 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 311.32 29-MAY-11:53 1867.71 03-MAY-04:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 456.70 19-JUN-21:02 1133.30 02-JUN-22:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 500.25 09-JUL-14:00 506.03 11-JUL-04:50
August 2010.79 01-AUG-09:09 1075.02 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 642.84 04-AUG-21:01 763.37 20-AUG-06:00
September 2010.79 01-SEP-09:09 1307.46 27-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 177.63 14-SEP-14:00 979.42 23-SEP-04:00
October 2010.79 02-OCT-09:09 1495.56 31-OCT-15:00 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 28.29 25-OCT-11:00 2590.09 17-OCT-24:00
November 2010.79 01-NOV-09:09 1750.00 06-NOV-16:49 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4033.96 23-NOV-02:00
December 2010.79 01-DEC-10:09 1750.00 01-DEC-16:30 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5347.27 31-DEC-21:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   506.03  
Maximum of Months 2010.79   1750.00   2276.32   0.00 0.00 0.00 0.00 642.84   5380.31  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1127.77 02-JAN-16:40 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 3421.36 14-JAN-05:51
February 1239.33 01-FEB-08:09 1061.85 01-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3586.92 06-FEB-01:00
March 1239.33 01-MAR-08:09 976.04 02-MAR-16:00 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2727.21 21-MAR-21:02
April 1239.33 03-APR-07:10 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 44.30 07-APR-13:00 2122.13 11-APR-03:53
May 1239.33 01-MAY-07:10 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 175.38 29-MAY-12:08 1261.53 03-MAY-04:00
June 1239.33 01-JUN-07:10 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 302.53 19-JUN-21:02 765.79 02-JUN-22:00
July 1239.33 03-JUL-07:10 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 338.10 09-JUL-13:55 362.87 02-JUL-19:00
August 1239.33 01-AUG-07:10 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 444.29 12-AUG-19:00 539.54 20-AUG-06:00
September 1239.33 01-SEP-07:10 692.79 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 118.41 14-SEP-14:00 696.87 10-SEP-08:00
October 1239.33 02-OCT-07:10 967.14 31-OCT-15:00 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 18.85 25-OCT-11:00 1929.66 08-OCT-08:00
November 1239.33 01-NOV-07:10 1127.77 06-NOV-16:49 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2709.69 23-NOV-02:00
December 1239.33 01-DEC-08:09 1127.77 01-DEC-16:30 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3594.50 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   362.87  
Maximum of Months 1239.33   1127.77   1466.95   0.00 0.00 0.00 0.00 444.29   3594.50  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1750.04 02-JAN-16:40 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5278.93 31-JAN-01:00
February 2010.83 01-FEB-10:09 1628.89 15-FEB-16:00 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5380.38 06-FEB-00:55
March 2010.83 01-MAR-10:09 1319.38 16-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4146.55 12-MAR-10:00
April 2010.83 03-APR-09:09 1075.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 66.36 07-APR-13:00 3272.79 11-APR-03:53
May 2010.83 01-MAY-09:09 1075.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 205.97 29-MAY-12:05 1927.81 03-MAY-04:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 455.11 19-JUN-21:02 1153.03 02-JUN-22:00
July 2010.83 03-JUL-09:09 1075.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 478.70 09-JUL-13:55 527.74 02-JUL-19:00
August 2010.83 01-AUG-09:09 1075.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 640.25 04-AUG-21:01 801.12 20-AUG-05:53
September 2010.83 01-SEP-09:09 1276.50 27-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 177.47 14-SEP-14:00 1087.47 30-SEP-24:00
October 2010.83 02-OCT-09:09 1460.67 31-OCT-15:00 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 27.68 25-OCT-11:00 2857.57 08-OCT-08:00
November 2010.83 01-NOV-09:09 1750.04 06-NOV-16:49 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4231.06 23-NOV-02:00
December 2010.83 01-DEC-10:09 1750.04 01-DEC-16:30 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5367.77 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   527.74  
Maximum of Months 2010.83   1750.04   2276.35   0.00 0.00 0.00 0.00 640.25   5380.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-16:40 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 3427.22 14-JAN-05:51
February 1295.83 01-FEB-10:09 1043.66 15-FEB-16:00 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 3586.92 06-FEB-00:59
March 1295.83 01-MAR-10:09 897.38 16-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 2744.34 21-MAR-21:02
April 1295.83 03-APR-09:09 797.10 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 44.31 07-APR-13:00 2222.26 11-APR-03:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 217.88 29-MAY-11:47 1337.62 03-MAY-04:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 296.56 19-JUN-21:02 860.17 03-JUN-19:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 330.15 09-JUL-13:55 491.84 02-JUL-17:40
August 1295.83 01-AUG-09:09 776.76 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 424.09 04-AUG-21:01 572.44 20-AUG-05:53
September 1295.83 01-SEP-09:09 870.78 27-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 118.42 14-SEP-14:00 714.07 30-SEP-24:00
October 1295.83 02-OCT-09:09 942.95 06-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 18.86 25-OCT-11:00 1814.46 17-OCT-24:00
November 1295.83 01-NOV-09:09 1127.77 06-NOV-16:49 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2753.14 23-NOV-02:00
December 1295.83 01-DEC-10:09 1127.77 01-DEC-16:30 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3584.17 31-DEC-21:53
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.94   0.00 0.00 0.00 0.00 0.00   491.84  
Maximum of Months 1295.83   1127.77   1466.94   0.00 0.00 0.00 0.00 424.09   3586.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1750.00 02-JAN-16:40 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 6198.03 14-JAN-06:00
February 2010.79 01-FEB-10:09 1636.72 01-FEB-16:00 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 6648.38 06-FEB-00:50
March 2010.79 01-MAR-10:09 1415.71 02-MAR-16:00 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 5064.70 21-MAR-21:02
April 2010.79 03-APR-09:09 1075.02 03-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 79.04 07-APR-13:00 3595.51 11-APR-03:53
May 2010.79 01-MAY-09:09 1075.02 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 340.37 29-MAY-12:00 2100.12 03-MAY-04:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 548.49 19-JUN-21:02 1360.65 02-JUN-22:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 531.11 09-JUL-13:27 662.70 11-JUL-05:00
August 2010.79 01-AUG-09:09 1075.02 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 783.86 04-AUG-21:01 897.08 20-AUG-05:53
September 2010.79 01-SEP-09:09 1307.08 27-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 216.83 14-SEP-14:00 1127.29 23-SEP-04:00
October 2010.79 02-OCT-09:09 1495.32 31-OCT-15:00 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 30.85 25-OCT-11:00 2911.78 26-OCT-23:00
November 2010.79 01-NOV-09:09 1750.00 06-NOV-16:49 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4953.47 22-NOV-22:02
December 2010.79 01-DEC-10:09 1750.00 01-DEC-16:30 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6670.69 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   662.70  
Maximum of Months 2010.79   1750.00   2276.32   0.00 0.00 0.00 0.00 783.86   6670.69  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-16:40 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 4330.91 14-JAN-05:54
February 1295.83 01-FEB-10:09 1061.80 01-FEB-16:00 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4432.41 06-FEB-00:46
March 1295.83 01-MAR-10:09 975.96 02-MAR-16:00 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3381.17 21-MAR-21:02
April 1295.83 03-APR-09:09 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 52.69 07-APR-13:00 2418.96 11-APR-03:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 203.63 29-MAY-12:18 1428.61 03-MAY-04:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 362.86 19-JUN-21:02 926.82 02-JUN-22:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 365.47 09-JUL-14:04 501.94 02-JUL-18:30
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 536.56 12-AUG-19:00 635.80 20-AUG-06:00
September 1295.83 01-SEP-09:09 692.79 01-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 144.56 14-SEP-14:00 819.60 10-SEP-08:10
October 1295.83 02-OCT-09:09 966.99 31-OCT-15:00 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 20.56 25-OCT-11:00 2000.56 08-OCT-08:10
November 1295.83 01-NOV-09:09 1127.77 06-NOV-16:49 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3304.73 22-NOV-22:02
December 1295.83 01-DEC-10:09 1127.77 01-DEC-16:30 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4447.36 31-DEC-21:58
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   501.94  
Maximum of Months 1295.83   1127.77   1466.95   0.00 0.00 0.00 0.00 536.56   4447.36  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1750.04 02-JAN-16:40 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 6495.95 14-JAN-06:00
February 2010.83 01-FEB-10:09 1628.78 15-FEB-16:00 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 6648.63 06-FEB-00:50
March 2010.83 01-MAR-10:09 1319.06 16-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 5093.12 21-MAR-21:02
April 2010.83 03-APR-09:09 1075.05 03-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 78.86 07-APR-13:00 3740.11 11-APR-03:53
May 2010.83 01-MAY-09:09 1075.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 244.86 29-MAY-11:38 2183.21 03-MAY-04:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 546.20 19-JUN-21:02 1388.82 02-JUN-22:00
July 2010.83 03-JUL-09:09 1075.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 527.22 09-JUL-13:46 711.12 02-JUL-18:30
August 2010.83 01-AUG-09:09 1075.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 780.29 04-AUG-21:01 947.72 20-AUG-05:53
September 2010.83 01-SEP-09:09 1276.12 27-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 216.59 14-SEP-14:00 1289.25 10-SEP-19:55
October 2010.83 02-OCT-09:09 1460.45 31-OCT-15:00 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 30.83 25-OCT-11:00 3199.43 17-OCT-22:00
November 2010.83 01-NOV-09:09 1750.04 06-NOV-16:49 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4974.67 22-NOV-22:02
December 2010.83 01-DEC-10:09 1750.04 01-DEC-16:30 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 6670.94 31-DEC-22:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   711.12  
Maximum of Months 2010.83   1750.04   2276.35   0.00 0.00 0.00 0.00 780.29   6670.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-16:40 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 4330.88 14-JAN-05:59
February 1295.83 01-FEB-10:09 1043.60 15-FEB-16:00 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 4432.41 06-FEB-00:44
March 1295.83 01-MAR-10:09 897.18 16-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 3400.60 21-MAR-21:02
April 1295.83 03-APR-09:09 796.91 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 52.70 07-APR-13:00 2551.15 11-APR-03:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 253.16 29-MAY-12:00 1533.58 03-MAY-04:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 355.34 19-JUN-21:02 1064.02 03-JUN-19:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 356.82 09-JUL-13:25 660.30 02-JUL-17:50
August 1295.83 01-AUG-09:09 776.43 16-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 516.76 04-AUG-21:01 680.23 20-AUG-05:53
September 1295.83 01-SEP-09:09 870.55 27-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 144.55 14-SEP-14:00 888.01 10-SEP-19:55
October 1295.83 02-OCT-09:09 942.77 06-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 20.57 25-OCT-11:00 2080.15 17-OCT-22:00
November 1295.83 01-NOV-09:09 1127.77 06-NOV-16:49 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3309.93 22-NOV-22:02
December 1295.83 01-DEC-10:09 1127.77 01-DEC-16:30 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4447.25 31-DEC-21:57
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.94   0.00 0.00 0.00 0.00 0.00   660.30  
Maximum of Months 1295.83   1127.77   1466.94   0.00 0.00 0.00 0.00 516.76   4447.25  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4375.82 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4375.82 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4375.82 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4375.82 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4375.82 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4375.82 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4375.82 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4375.82 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4375.82 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4375.82 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4375.82 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4375.82 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4375.82   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4375.82   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 5464.70 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 5462.07 06-FEB-00:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 4059.60 12-MAR-10:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 47.03 07-APR-13:00 3345.64 11-APR-03:57
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 249.23 29-MAY-12:00 1983.60 03-MAY-04:05
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 328.93 19-JUN-21:02 1075.78 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 453.97 09-JUL-14:00 461.07 11-JUL-04:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 538.77 12-AUG-18:53 701.01 20-AUG-06:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 136.37 14-SEP-14:00 964.48 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.19 25-OCT-11:00 2865.98 08-OCT-07:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4543.44 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 5842.85 31-DEC-21:52
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   461.07  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 538.77   5842.85  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 9096.34 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 8938.86 05-FEB-08:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 6714.78 21-MAR-21:02
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 91.68 07-APR-13:00 5744.21 11-APR-03:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 510.11 29-MAY-11:53 3348.48 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 588.81 19-JUN-21:02 1894.04 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 818.67 09-JUL-14:00 837.27 11-JUL-04:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 960.04 12-AUG-19:00 1277.94 20-AUG-05:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 243.26 14-SEP-14:00 1689.80 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 21.49 25-OCT-11:00 4865.17 08-OCT-07:55
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 7555.68 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 9213.68 31-DEC-21:52
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   837.27  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 960.04   9213.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 9371.91 31-JAN-01:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 9032.88 06-FEB-00:51
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 7529.82 21-MAR-21:02
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.12 08-APR-10:00 5848.89 11-APR-03:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 212.87 29-MAY-12:00 3440.94 03-MAY-04:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 668.45 19-JUN-21:02 1998.44 02-JUN-22:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 588.63 07-JUL-21:53 1059.30 02-JUL-18:33
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1071.67 12-AUG-19:00 1318.50 20-AUG-05:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 240.04 14-SEP-14:00 1761.36 23-SEP-04:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 4754.44 17-OCT-24:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 7597.66 23-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 9158.34 31-DEC-22:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1059.30  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1071.67   9371.91  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 101225.76 30-JAN-04:01 0.00 7760.04 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
February 105817.05 21-FEB-04:01 0.00 6035.59 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
March 103836.54 13-MAR-03:01 0.00 7760.04 121117.90 0.00 0.00 0.00 0.00 0.00 0.00
April 103422.61 03-APR-03:01 0.00 6897.82 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
May 103833.81 01-MAY-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
June 93773.98 05-JUN-03:03 0.00 2586.68 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
July 87613.43 11-JUL-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 89401.06 29-AUG-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
September 102079.14 25-SEP-03:02 0.00 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
October 105803.27 16-OCT-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 105334.30 06-NOV-04:03 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
December 108548.94 26-DEC-04:01 0.00 6035.59 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 87613.43   0.00 2586.68 40372.63 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 108548.94   0.00 7760.04 121117.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 79541.05 30-JAN-06:02 14510.15 13938.13 72514.36 0.00 0.00 0.00 0.00 0.00 0.00
February 83923.28 21-FEB-05:02 0.00 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
March 84360.62 30-MAR-04:02 0.00 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
April 85862.75 11-APR-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
May 87495.28 01-MAY-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
June 89540.86 12-JUN-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
July 84373.02 01-JUL-03:02 0.00 3871.70 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
August 84093.86 07-AUG-05:04 8061.19 7743.41 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
September 91267.60 18-SEP-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
October 90327.57 23-OCT-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 91713.54 13-NOV-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 85475.15 26-DEC-04:01 0.00 5420.38 56400.06 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 79541.05   0.00 3097.36 30214.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 91713.54   14510.15 13938.13 72514.36 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 21262.51 31-JAN-09:40 30632.53 27875.12 36257.04 0.00 0.00 0.00 0.00 0.00 0.00
February 25464.82 04-FEB-17:08 4030.60 3871.70 30214.20 0.00 0.00 0.00 0.00 0.00 0.00
March 70076.28 30-MAR-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 77420.71 08-APR-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 77442.54 20-MAY-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 81975.11 12-JUN-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 79698.32 12-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 86286.94 07-AUG-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 80536.55 18-SEP-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 77929.20 05-OCT-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
November 73403.98 03-NOV-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 24633.11 21-DEC-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 21262.51   0.00 3871.70 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 86286.94   30632.53 27875.12 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 18386.66 20-JAN-17:00 30632.53 27875.12 36257.04 0.00 0.00 0.00 0.00 0.00 0.00
February 18461.24 24-FEB-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 29245.72 03-MAR-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
April 75034.63 08-APR-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 81840.28 30-MAY-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 84215.32 12-JUN-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 84498.08 24-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 88980.59 07-AUG-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 81556.61 05-SEP-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 78239.46 06-OCT-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 29554.38 03-NOV-16:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
December 18152.88 20-DEC-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 18152.88   0.00 3871.70 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 88980.59   30632.53 27875.12 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2594.39 24-JAN-06:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 268.33
February 2661.02 21-FEB-05:02 0.00 1166.71 6070.18 0.00 0.00 0.00 0.00 0.00 474.52
March 5368.29 27-MAR-13:30 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 29.38
April 6755.29 07-APR-13:40 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 27.89 0.00
May 12709.70 30-MAY-05:03 809.73 477.81 4046.79 0.00 0.00 0.00 0.00 0.00 24.31
June 12222.83 12-JUN-05:03 809.73 659.11 4046.79 0.00 0.00 0.00 0.00 0.00 70.39
July 15480.16 04-JUL-16:01 809.73 477.81 6070.18 0.00 0.00 0.00 0.00 0.00 31.16
August 15993.37 13-AUG-16:21 809.73 477.81 6070.18 0.00 0.00 0.00 0.00 74.63 0.00
September 11727.90 02-SEP-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 18.08
October 10056.65 23-OCT-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 60.43
November 4446.36 03-NOV-13:50 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 27.99
December 2849.64 05-DEC-05:01 0.00 1361.17 7081.88 0.00 0.00 0.00 0.00 0.00 350.39
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2594.39   0.00 477.81 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15993.37   2010.79 1361.17 7081.88 0.00 0.00 0.00 0.00 74.63 474.52



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3010.30 19-JAN-09:25 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 127.67
February 3977.52 22-FEB-09:30 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 205.41
March 7167.92 29-MAR-08:40 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 108.34
April 10541.44 23-APR-08:33 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 338.41
May 18182.90 29-MAY-08:22 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 32.33
June 17846.79 04-JUN-08:13 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 77.54
July 18147.23 02-JUL-08:32 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 27.31
August 17440.45 13-AUG-09:02 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 27.08 0.00
September 18180.11 04-SEP-07:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 19.18
October 8599.91 03-OCT-08:40 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 32.19
November 5145.63 02-NOV-08:50 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 134.99
December 3674.70 20-DEC-09:25 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 44.41
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 3010.30   195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18182.90   2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 27.08 338.41



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 10789.31 19-JAN-13:30 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 238.78
February 11529.95 22-FEB-13:20 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 188.52
March 14175.04 03-MAR-13:15 3846.30 2150.10 4552.71 0.00 0.00 0.00 0.00 0.00 167.29
April 16859.92 09-APR-13:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 297.68
May 21619.03 29-MAY-13:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 35.52
June 15566.95 26-JUN-05:02 1012.19 761.07 5058.56 0.00 0.00 0.00 0.00 0.00 32.80
July 22034.40 04-JUL-14:02 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 18.39 0.00
August 23327.09 13-AUG-13:02 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 83.01 0.00
September 22460.27 10-SEP-11:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 242.27
October 22342.11 15-OCT-13:32 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 413.22
November 16291.15 02-NOV-12:40 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 103.41
December 17957.59 17-DEC-12:33 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 424.25
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 10789.31   303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23327.09   3846.30 2150.10 5058.56 0.00 0.00 0.00 0.00 83.01 424.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5367.07 20-JAN-15:40 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 75.46
February 7665.10 24-FEB-15:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 185.05
March 11632.18 27-MAR-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 14.47
April 22755.94 09-APR-16:22 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 168.37
May 18788.75 29-MAY-14:23 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 40.40
June 22960.94 18-JUN-16:02 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 51.92
July 25612.86 04-JUL-16:01 521.82 307.92 3911.83 0.00 0.00 0.00 0.00 0.00 84.87
August 25797.33 13-AUG-16:21 521.82 307.92 3911.83 0.00 0.00 0.00 0.00 7.97 0.00
September 22066.26 10-SEP-15:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 98.74
October 14656.52 23-OCT-05:03 521.82 501.25 2607.89 0.00 0.00 0.00 0.00 0.00 40.74
November 10871.66 09-NOV-06:03 521.82 501.25 2607.89 0.00 0.00 0.00 0.00 0.00 0.00
December 7507.82 18-DEC-15:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 100.14
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5367.07   260.91 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 25797.33   1239.33 692.79 3911.83 0.00 0.00 0.00 0.00 7.97 185.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1830.36 20-JAN-17:00 3846.22 3500.00 4552.64 0.00 0.00 0.00 0.00 0.00 325.04
February 2714.43 04-FEB-17:08 506.08 448.10 3793.86 0.00 0.00 0.00 0.00 0.00 783.58
March 2369.75 27-MAR-16:00 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 47.66
April 4963.59 07-APR-15:20 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 41.45 0.00
May 10386.10 30-MAY-05:03 809.73 477.81 4046.79 0.00 0.00 0.00 0.00 0.00 53.90
June 11376.34 20-JUN-05:02 1012.16 597.26 5058.48 0.00 0.00 0.00 0.00 0.00 60.54
July 13815.51 10-JUL-03:02 0.00 486.13 5058.48 0.00 0.00 0.00 0.00 15.94 0.00
August 12318.14 18-AUG-03:02 0.00 486.13 5058.48 0.00 0.00 0.00 0.00 0.00 32.73
September 10780.97 22-SEP-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 24.50
October 5448.73 05-OCT-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 17.60
November 2789.43 02-NOV-13:20 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 193.16
December 1765.47 20-DEC-13:40 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 245.95
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1765.47   0.00 448.10 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13815.51   3846.22 3500.00 5058.48 0.00 0.00 0.00 0.00 41.45 783.58



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2138.81 26-JAN-09:25 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 115.54
February 2472.69 04-FEB-17:08 326.14 293.60 2444.91 0.00 0.00 0.00 0.00 0.00 517.11
March 5920.93 29-MAR-09:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 227.72
April 9091.63 28-APR-08:50 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 116.24
May 20770.25 29-MAY-08:42 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 0.00 114.47
June 18718.30 04-JUN-08:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 170.56
July 21292.56 02-JUL-09:01 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 0.00 124.32
August 18935.18 27-AUG-09:53 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 52.27
September 20532.56 04-SEP-09:12 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 0.00 105.24
October 8046.64 05-OCT-09:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 68.14
November 3189.85 03-NOV-09:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 135.01
December 2048.78 21-DEC-09:15 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 367.83
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2048.78   260.91 153.96 1466.95 0.00 0.00 0.00 0.00 0.00 52.27
Maximum of Months 21292.56   2478.65 1385.57 3422.87 0.00 0.00 0.00 0.00 0.00 517.11



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9636.76 19-JAN-13:40 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 552.36
February 11131.70 22-FEB-13:40 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 418.35
March 13487.33 01-MAR-13:30 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 205.12
April 13860.82 07-APR-12:40 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 57.08 0.00
May 21438.89 29-MAY-12:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 33.31 0.00
June 14925.82 08-JUN-05:02 1012.19 805.11 5058.56 0.00 0.00 0.00 0.00 0.00 9.61
July 21969.56 30-JUL-13:32 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 34.21
August 21882.55 20-AUG-12:32 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 3.98
September 23745.40 04-SEP-11:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 157.14
October 21877.50 15-OCT-14:32 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 1037.37
November 16594.06 02-NOV-13:10 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 228.19
December 13902.34 15-DEC-12:00 3846.30 2150.10 4552.71 0.00 0.00 0.00 0.00 0.00 562.52
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9636.76   404.87 238.91 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23745.40   3846.30 2150.10 5058.56 0.00 0.00 0.00 0.00 57.08 1037.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2393.09 20-JAN-16:10 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 167.35
February 3448.09 22-FEB-16:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 278.85
March 7749.30 29-MAR-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 314.09
April 12552.96 09-APR-16:33 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 349.12
May 15095.03 28-MAY-16:03 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 173.78
June 20273.71 04-JUN-16:22 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 374.42
July 20989.66 02-JUL-16:21 521.82 307.92 3911.83 0.00 0.00 0.00 0.00 0.00 260.42
August 20254.30 13-AUG-15:52 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 112.48 0.00
September 21157.38 10-SEP-16:02 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 329.21
October 10492.44 04-OCT-15:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 10.39
November 5405.39 03-NOV-15:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 71.24
December 2256.62 08-DEC-15:40 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 304.43
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2256.62   260.91 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21157.38   1239.33 692.79 3911.83 0.00 0.00 0.00 0.00 112.48 374.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1558.17 20-JAN-16:00 1923.11 1301.04 2276.32 0.00 0.00 0.00 0.00 0.00 239.86
February 1633.69 24-FEB-15:30 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 667.29
March 2365.76 28-MAR-14:10 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 421.74
April 5617.14 07-APR-15:20 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 47.70 0.00
May 11064.09 31-MAY-05:03 809.73 477.81 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
June 13587.36 26-JUN-05:02 1012.16 597.26 5058.48 0.00 0.00 0.00 0.00 0.00 94.65
July 18157.48 09-JUL-15:21 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 0.00 38.72
August 14778.17 13-AUG-15:52 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 253.59 0.00
September 10682.72 07-SEP-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 32.71
October 5694.95 04-OCT-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 3.91 0.00
November 2298.44 03-NOV-15:00 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 103.55
December 1505.85 09-DEC-17:03 404.87 388.90 3035.09 0.00 0.00 0.00 0.00 0.00 246.75
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1505.85   404.87 358.36 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18157.48   2010.79 1301.04 5311.41 0.00 0.00 0.00 0.00 253.59 667.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1701.50 19-JAN-10:20 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 393.61
February 1738.90 22-FEB-10:15 2591.66 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 490.14
March 4064.03 29-MAR-09:50 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 271.36
April 8512.42 07-APR-09:30 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 66.12
May 21293.57 29-MAY-08:52 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 0.00 135.81
June 19106.42 04-JUN-09:13 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 139.20
July 19823.50 02-JUL-09:12 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 83.33
August 19155.68 13-AUG-09:52 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 98.59 0.00
September 20929.34 04-SEP-09:12 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 0.00 130.79
October 7532.67 05-OCT-09:20 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 80.31
November 2271.47 02-NOV-13:30 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 170.23
December 1752.42 20-DEC-09:35 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 112.62
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1701.50   260.91 153.96 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21293.57   2591.66 1385.57 2933.89 0.00 0.00 0.00 0.00 98.59 490.14



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8855.22 19-JAN-13:50 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 676.10
February 9603.48 02-FEB-14:20 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 605.25
March 13234.09 03-MAR-13:40 3846.30 2150.10 4552.71 0.00 0.00 0.00 0.00 0.00 451.92
April 14470.88 07-APR-12:40 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 67.34 0.00
May 23794.92 29-MAY-12:13 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 117.64 0.00
June 15172.52 08-JUN-05:02 1012.19 804.98 5058.56 0.00 0.00 0.00 0.00 0.00 11.86
July 24299.51 30-JUL-13:32 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 89.45
August 23858.28 13-AUG-12:32 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 302.65 0.00
September 26184.92 04-SEP-11:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 203.46
October 23637.63 15-OCT-13:23 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 1225.29
November 15345.22 02-NOV-13:20 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 287.87
December 8256.45 21-DEC-13:30 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 614.63
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 8256.45   404.87 238.91 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 26184.92   3846.30 2150.10 5058.56 0.00 0.00 0.00 0.00 302.65 1225.29



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2304.73 20-JAN-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 185.74
February 2628.30 22-FEB-16:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 348.08
March 7250.86 29-MAR-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 392.49
April 19177.15 09-APR-16:51 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 324.10
May 17229.03 29-MAY-14:13 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 126.09
June 21819.86 18-JUN-16:02 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 176.69
July 22945.55 09-JUL-15:21 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 94.28
August 21865.13 13-AUG-15:52 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 125.16 0.00
September 22558.35 10-SEP-16:52 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 503.06
October 10766.02 04-OCT-15:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 14.76
November 4847.76 03-NOV-15:30 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 89.65
December 2223.96 08-DEC-15:40 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 365.29
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2223.96   260.91 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22945.55   1239.33 692.79 3422.85 0.00 0.00 0.00 0.00 125.16 503.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3206.76 14-JAN-06:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1153.00
February 4721.37 06-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4453.46
March 3458.53 31-MAR-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 416.11
April 8349.65 10-APR-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 144.80
May 12082.22 30-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 51.64
June 9709.11 12-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 158.32
July 12396.08 10-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.79 0.00
August 13506.91 14-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 26.52
September 12389.63 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.67
October 8235.25 23-OCT-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 129.89
November 5306.24 13-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 233.69
December 3401.73 18-DEC-06:08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 288.19
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3206.76   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13506.91   0.00 0.00 0.00 0.00 0.00 0.00 0.00 13.79 4453.46



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5546.45 14-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7481.48
February 6177.63 05-FEB-22:51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8635.09
March 5201.61 13-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4685.36
April 3752.97 10-APR-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 253.67
May 7006.16 30-MAY-13:35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 144.55 0.00
June 7475.25 20-JUN-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.46 0.00
July 7977.59 11-JUL-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 43.04 0.00
August 9585.18 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.71
September 9334.56 01-SEP-14:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 187.24 0.00
October 5063.56 05-OCT-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 199.40
November 5074.35 22-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6050.23
December 6049.39 02-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5316.16
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 3752.97   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 9585.18   0.00 0.00 0.00 0.00 0.00 0.00 0.00 187.24 8635.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6716.81
February 298.64 17-FEB-13:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 488.39
March 5014.87 03-MAR-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 701.87
April 13190.03 07-APR-13:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 32.46 0.00
May 20739.38 30-MAY-13:05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 152.20 0.00
June 21693.77 19-JUN-13:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 274.89 0.00
July 20420.27 10-JUL-14:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 364.17 0.00
August 20693.14 22-AUG-14:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 264.59 0.00
September 17971.21 01-SEP-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 176.60 0.00
October 11076.43 04-OCT-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 66.25
November 3493.69 04-NOV-13:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 235.90
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3601.74
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21693.77   0.00 0.00 0.00 0.00 0.00 0.00 0.00 364.17 6716.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1934.41 20-JAN-16:30 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3979.31 22-FEB-16:50 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6935.85 31-MAR-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8071.72 23-APR-17:45 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
May 3522.82 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5342.74 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7222.48 31-JUL-23:57 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7984.20 13-AUG-18:12 0.00 135.04 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3414.15 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5136.44 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5843.07 03-NOV-16:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7701.48 18-DEC-16:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1934.41   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8071.72   222.14 405.10 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1540.40 20-JAN-16:40 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3543.81 22-FEB-17:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6009.06 31-MAR-23:50 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7497.51 09-APR-17:30 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3350.89 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5034.59 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6968.16 31-JUL-23:57 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7605.39 31-AUG-17:30 23.38 135.03 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
September 3073.88 30-SEP-23:40 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4404.44 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5470.13 03-NOV-16:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7030.62 21-DEC-16:10 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1540.40   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7605.39   222.14 405.10 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1423.12 19-JAN-16:30 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3401.59 02-FEB-17:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5539.09 29-MAR-17:00 70.15 225.06 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 7567.06 09-APR-17:30 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
May 3321.63 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 4951.34 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6971.72 31-JUL-23:57 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7750.83 13-AUG-17:40 0.00 157.55 54560.95 0.00 0.00 0.00 0.00 0.00 0.00
September 2808.19 30-SEP-23:20 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 3908.63 04-OCT-16:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 5434.26 03-NOV-16:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 6807.94 08-DEC-16:10 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1423.12   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7750.83   222.14 405.10 54560.95 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 91147.31 20-JAN-17:00 9617.36 8751.64 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
February 182527.00 22-FEB-17:00 4808.68 4375.82 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358031.60 31-MAR-24:00 0.00 243.11 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 367103.26 10-APR-16:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175884.78 31-MAY-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267492.19 30-JUN-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359805.13 31-JUL-23:57 0.00 729.33 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 369565.33 18-AUG-23:15 0.00 486.22 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
September 176249.20 30-SEP-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 267951.31 31-OCT-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276238.39 06-NOV-17:00 4808.68 4375.82 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 367311.32 18-DEC-17:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 91147.31   0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 369565.33   9617.36 8751.64 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.153971E+13 982651.48 20-JAN-16:00 0.454158E+12 1752188.17 02-JAN-05:10
February 0.174464E+13 1099809.15 02-FEB-08:09 0.343145E+12 1378301.61 13-FEB-07:10
March 0.237473E+13 1374730.96 27-MAR-15:00 0.165134E+12 739074.78 13-MAR-04:10
April 0.271001E+13 1802086.15 07-APR-14:39 0.881354E+11 455252.31 03-APR-05:10
May 0.175521E+13 1457384.89 30-MAY-13:50 0.610582E+11 169729.33 30-MAY-14:09
June 0.238328E+13 1611494.27 22-JUN-13:09 0.582724E+11 226676.01 01-JUN-14:00
July 0.297602E+13 1788163.72 11-JUL-15:20 0.534638E+11 124969.40 11-JUL-14:09
August 0.342864E+13 1959609.74 22-AUG-14:39 0.588140E+11 184133.60 22-AUG-15:50
September 0.185088E+13 1421538.99 01-SEP-13:00 0.527741E+11 94287.47 01-SEP-17:19
October 0.212640E+13 1490517.29 05-OCT-15:39 0.605196E+11 277345.56 28-OCT-06:10
November 0.229346E+13 1335517.90 03-NOV-15:09 0.156143E+12 830105.94 24-NOV-07:10
December 0.271065E+13 1402668.30 26-DEC-08:09 0.276802E+12 707068.51 02-DEC-05:10
             
Annual Sum or Average 0.278936E+14     0.182842E+13    
Minimum of Months 0.153971E+13 982651.48   0.527741E+11 94287.47  
Maximum of Months 0.342864E+13 1959609.74   0.454158E+12 1752188.17  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.232581E+12 0.488806E+11 0.811612E+12 0.162551E+12 0.163006E+12 0.182597E+11 0.00 0.835575E+11 0.100962E+11 0.294498E+10 0.622067E+10 0.00 0.00
February 0.209034E+12 0.402025E+11 0.102011E+13 0.146826E+12 0.147299E+12 0.187738E+11 0.00 0.138687E+12 0.141941E+11 0.344635E+10 0.607262E+10 0.00 0.00
March 0.246521E+12 0.390867E+11 0.146267E+13 0.162740E+12 0.167045E+12 0.184926E+11 0.00 0.223567E+12 0.480225E+11 0.198702E+10 0.460342E+10 0.00 0.00
April 0.219214E+12 0.323953E+11 0.170311E+13 0.157288E+12 0.170576E+12 0.276576E+11 0.00 0.300717E+12 0.966186E+11 0.799627E+09 0.164026E+10 0.00 0.00
May 0.235893E+12 0.293732E+11 0.820521E+12 0.162644E+12 0.195787E+12 0.557829E+11 0.00 0.166026E+12 0.886415E+11 0.168346E+09 0.376103E+09 0.00 0.00
June 0.234365E+12 0.263910E+11 0.110677E+13 0.157466E+12 0.225179E+12 0.915863E+11 0.00 0.377883E+12 0.158955E+12 0.00 0.467995E+10 0.00 0.00
July 0.219588E+12 0.279276E+11 0.143888E+13 0.162465E+12 0.243456E+12 0.114593E+12 0.00 0.569254E+12 0.192901E+12 0.00 0.695397E+10 0.00 0.00
August 0.244941E+12 0.313334E+11 0.177780E+13 0.162739E+12 0.259428E+12 0.118790E+12 0.00 0.647992E+12 0.179983E+12 0.00 0.563331E+10 0.00 0.00
September 0.219676E+12 0.354418E+11 0.784732E+12 0.157287E+12 0.202403E+12 0.760422E+11 0.00 0.240298E+12 0.132220E+12 25735324.77 0.275678E+10 0.00 0.00
October 0.229239E+12 0.422686E+11 0.112899E+13 0.162550E+12 0.188540E+12 0.461724E+11 0.00 0.228518E+12 0.984992E+11 0.670971E+09 0.952420E+09 0.00 0.00
November 0.229077E+12 0.458675E+11 0.140306E+13 0.157362E+12 0.159988E+12 0.178669E+11 0.00 0.216648E+12 0.591990E+11 0.124326E+10 0.314486E+10 0.00 0.00
December 0.225605E+12 0.500766E+11 0.175516E+13 0.162467E+12 0.160865E+12 0.167531E+11 0.00 0.279811E+12 0.511062E+11 0.294180E+10 0.586777E+10 0.00 0.00
                           
Annual Sum or Average 0.274573E+13 0.449245E+12 0.152134E+14 0.191438E+13 0.228357E+13 0.620771E+12 0.00 0.347296E+13 0.113044E+13 0.142281E+11 0.489021E+11 0.00 0.00
Minimum of Months 0.209034E+12 0.263910E+11 0.784732E+12 0.146826E+12 0.147299E+12 0.167531E+11 0.00 0.835575E+11 0.100962E+11 0.00 0.376103E+09 0.00 0.00
Maximum of Months 0.246521E+12 0.500766E+11 0.177780E+13 0.162740E+12 0.259428E+12 0.118790E+12 0.00 0.647992E+12 0.192901E+12 0.344635E+10 0.695397E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.389126E+12 0.00 0.650320E+11 0.00 0.00
February 0.00 0.00 0.283696E+12 0.00 0.594494E+11 0.00 0.00
March 0.00 0.00 0.974369E+11 0.00 0.676968E+11 0.00 0.00
April 0.00 0.00 0.281275E+11 0.00 0.600079E+11 0.00 0.00
May 0.00 0.00 0.768000E+09 0.00 0.602902E+11 0.00 0.00
June 0.00 0.00 0.204979E+10 0.00 0.562226E+11 0.00 0.00
July 0.00 0.00 0.724880E+09 0.00 0.527389E+11 0.00 0.00
August 0.00 0.00 0.316626E+10 0.00 0.556477E+11 0.00 0.00
September 0.00 0.00 0.184119E+09 0.00 0.525900E+11 0.00 0.00
October 0.00 0.00 0.374196E+10 0.00 0.567777E+11 0.00 0.00
November 0.00 0.00 0.975378E+11 0.00 0.586053E+11 0.00 0.00
December 0.00 0.00 0.214962E+12 0.00 0.618399E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.112152E+13 0.00 0.706898E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.184119E+09 0.00 0.525900E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.389126E+12 0.00 0.676968E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 261074.09 02-JAN-16:40 37611.08 01-JAN-06:10 439129.89 02-JAN-08:09 117200.89 03-JAN-08:20 102185.66 02-JAN-06:19 41624.57 05-JAN-06:10 0.00 01-JAN-00:10
February 256360.64 15-FEB-16:00 37611.08 01-FEB-06:10 557421.28 01-FEB-08:09 117194.52 28-FEB-08:20 91994.68 06-FEB-05:10 41556.91 14-FEB-06:10 0.00 01-FEB-00:10
March 244593.34 02-MAR-16:00 37611.08 01-MAR-06:10 675712.68 01-MAR-08:09 117195.21 16-MAR-07:19 116926.71 29-MAR-15:20 41814.07 27-MAR-15:00 0.00 01-MAR-00:10
April 235684.48 14-APR-07:10 37611.08 01-APR-05:10 794004.08 03-APR-07:10 117190.27 14-APR-07:19 208522.90 07-APR-14:39 67180.20 07-APR-14:39 0.00 01-APR-00:10
May 234435.00 01-MAY-07:10 37611.08 01-MAY-18:49 439129.89 01-MAY-07:10 117189.56 01-MAY-07:19 269639.00 30-MAY-13:50 69893.45 30-MAY-13:00 0.00 01-MAY-00:10
June 234435.00 01-JUN-07:10 37611.08 01-JUN-19:19 557421.28 01-JUN-07:10 117189.56 01-JUN-07:19 272897.93 22-JUN-13:09 70333.84 01-JUN-15:30 0.00 01-JUN-00:10
July 234435.00 03-JUL-07:10 37611.08 01-JUL-19:30 675712.68 03-JUL-07:10 117189.56 03-JUL-07:19 280421.96 11-JUL-14:30 66910.26 11-JUL-14:30 0.00 01-JUL-00:10
August 235439.69 16-AUG-07:10 37611.08 01-AUG-19:10 794004.08 01-AUG-07:10 117190.13 16-AUG-07:19 283348.35 22-AUG-14:39 75732.46 30-AUG-13:50 0.00 01-AUG-00:10
September 241746.79 27-SEP-07:10 37611.08 01-SEP-05:10 439129.89 01-SEP-07:10 117193.72 27-SEP-07:19 216968.01 01-SEP-13:00 74972.30 01-SEP-13:00 0.00 01-SEP-00:10
October 250180.37 31-OCT-15:00 37611.08 01-OCT-05:10 557421.28 02-OCT-07:10 117197.72 06-OCT-07:19 174441.21 05-OCT-15:39 69201.80 05-OCT-13:09 0.00 01-OCT-00:10
November 261074.09 06-NOV-16:49 37611.08 01-NOV-05:10 675712.68 01-NOV-07:10 117198.73 30-NOV-08:20 118611.55 03-NOV-13:00 41508.27 02-NOV-13:30 0.00 01-NOV-00:10
December 261074.09 01-DEC-16:30 37611.08 01-DEC-06:10 794004.08 01-DEC-08:09 117199.02 11-DEC-08:20 92135.13 21-DEC-13:20 41436.03 30-DEC-06:10 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 234435.00   37611.08   439129.89   117189.56   91994.68   41436.03   0.00  
Maximum of Months 261074.09   37611.08   794004.08   117200.89   283348.35   75732.46   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 38445.03 20-JAN-16:10 8666.24 24-JAN-11:00 6185.89 02-JAN-19:00 5613.48 02-JAN-07:10 0.00 0.00
February 62385.49 17-FEB-14:30 16773.12 20-FEB-11:00 6165.13 02-FEB-18:00 5613.48 01-FEB-07:10 0.00 0.00
March 188318.48 27-MAR-15:00 51516.49 27-MAR-15:00 6031.85 22-MAR-17:10 5613.48 01-MAR-07:10 0.00 0.00
April 369729.79 07-APR-14:39 90459.19 07-APR-13:30 5704.84 11-APR-18:00 5613.48 01-APR-06:10 0.00 0.00
May 317785.98 30-MAY-13:20 90459.19 30-MAY-07:00 3341.87 01-MAY-17:00 5613.48 30-MAY-08:50 0.00 0.00
June 359416.60 23-JUN-09:00 90459.19 01-JUN-09:00 0.00 01-JUN-00:10 5613.48 01-JUN-09:00 0.00 0.00
July 399312.59 20-JUL-14:30 90459.19 09-JUL-08:09 0.00 01-JUL-00:10 5613.48 01-JUL-06:10 0.00 0.00
August 448279.91 04-AUG-13:00 90459.19 01-AUG-06:19 0.00 01-AUG-00:10 5613.48 01-AUG-06:10 0.00 0.00
September 325948.46 01-SEP-13:00 90459.19 01-SEP-06:30 1987.51 23-SEP-13:00 5613.48 01-SEP-06:10 0.00 0.00
October 316607.46 04-OCT-13:39 90459.19 03-OCT-12:09 4834.73 28-OCT-16:30 5613.48 03-OCT-12:20 0.00 0.00
November 151691.56 03-NOV-13:00 50029.62 10-NOV-07:00 4841.10 22-NOV-19:00 5613.48 01-NOV-06:10 0.00 0.00
December 109011.76 18-DEC-14:39 44729.82 17-DEC-14:00 6019.31 14-DEC-21:00 5613.48 01-DEC-07:10 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 38445.03   8666.24   0.00   5613.48   0.00 0.00
Maximum of Months 448279.91   90459.19   6185.89   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 982651.48 20-JAN-16:00 261074.09 439129.89 37611.08 83160.37 74212.12 41368.23 0.00 38126.85 4881.56
February 1099809.15 02-FEB-08:09 237848.94 557421.28 0.00 117102.48 72908.15 41370.86 0.00 59747.85 6521.57
March 1374730.96 27-MAR-15:00 234435.00 675712.68 0.00 83146.17 99788.07 41814.07 0.00 188318.48 51516.49
April 1802086.15 07-APR-14:39 234435.00 794004.08 0.00 37754.99 208522.90 67180.20 0.00 369729.79 90459.19
May 1457384.89 30-MAY-13:50 234435.00 439129.89 0.00 37754.99 269639.00 69759.88 0.00 316206.95 90459.19
June 1611494.27 22-JUN-13:09 234435.00 557421.28 0.00 37754.99 272897.93 68240.50 0.00 350285.38 90459.19
July 1788163.72 11-JUL-15:20 234435.00 675712.68 0.00 83146.17 263468.43 66735.23 0.00 373271.44 90459.19
August 1959609.74 22-AUG-14:39 234435.00 794004.08 0.00 37754.99 283348.35 70698.45 0.00 445167.36 90459.19
September 1421538.99 01-SEP-13:00 234435.00 439129.89 0.00 37754.99 216968.01 74972.30 0.00 325948.46 90459.19
October 1490517.29 05-OCT-15:39 234435.00 557421.28 0.00 83146.17 174441.21 64506.70 0.00 280494.25 90459.19
November 1335517.90 03-NOV-15:09 234435.00 675712.68 0.00 83146.17 116374.49 41426.78 0.00 135045.65 49377.12
December 1402668.30 26-DEC-08:09 241078.59 794004.08 0.00 117103.06 74907.66 41375.90 0.00 106016.51 25375.78
                       
Annual Sum or Average                      
Minimum of Months 982651.48   234435.00 439129.89 0.00 37754.99 72908.15 41368.23 0.00 38126.85 4881.56
Maximum of Months 1959609.74   261074.09 794004.08 37611.08 117103.06 283348.35 74972.30 0.00 445167.36 90459.19



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 1746492.30 02-JAN-05:10 0.00 82473.33 31-JAN-12:39 0.00
February 0.00 0.00 1348630.26 13-FEB-07:10 0.00 82525.26 08-FEB-12:39 0.00
March 0.00 0.00 729245.82 13-MAR-04:10 0.00 82276.28 01-MAR-12:50 0.00
April 0.00 0.00 439008.57 03-APR-04:10 0.00 80784.35 03-APR-11:20 0.00
May 0.00 0.00 128851.66 30-MAY-14:09 0.00 78493.21 03-MAY-11:20 0.00
June 0.00 0.00 189079.21 01-JUN-15:20 0.00 75615.45 02-JUN-11:39 0.00
July 0.00 0.00 92647.23 11-JUL-14:50 0.00 72658.36 06-JUL-11:20 0.00
August 0.00 0.00 148862.32 22-AUG-15:50 0.00 71726.77 31-AUG-11:20 0.00
September 0.00 0.00 65293.94 01-SEP-17:19 0.00 73646.05 27-SEP-11:39 0.00
October 0.00 0.00 261925.29 28-OCT-06:10 0.00 76694.73 31-OCT-11:20 0.00
November 0.00 0.00 801003.29 24-NOV-07:10 0.00 79491.69 29-NOV-12:50 0.00
December 0.00 0.00 701372.64 02-DEC-05:10 0.00 81484.90 29-DEC-12:39 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 65293.94   0.00 71726.77   0.00
Maximum of Months 0.00 0.00 1746492.30   0.00 82525.26   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.33 25.61 0.00 25.61
February 0.00 0.00 0.00 0.00 0.50 25.72 0.00 25.72
March 0.00 0.00 0.00 0.00 1.33 25.69 0.00 25.69
April 0.00 0.00 0.00 0.00 2.83 25.91 0.00 25.91
May 0.00 0.00 0.00 0.00 3.67 26.05 0.00 26.05
June 0.00 0.00 0.00 0.00 2.67 26.10 0.00 26.10
July 0.00 0.00 0.00 0.00 5.50 26.16 0.00 26.16
August 0.00 0.00 0.00 0.00 7.67 26.43 0.17 26.39
September 0.00 0.00 0.00 0.00 9.83 26.79 0.00 26.79
October 0.00 0.00 0.00 0.00 14.17 26.95 0.50 26.96
November 0.00 0.00 0.00 0.00 10.83 26.84 0.17 26.85
December 0.00 0.00 0.00 0.00 3.50 26.14 0.00 26.14
                 
Annual Sum or Average 0.00   0.00   62.83 26.55 0.83 26.55
Minimum of Months 0.00 0.00 0.00 0.00 0.33 25.61 0.00 25.61
Maximum of Months 0.00 0.00 0.00 0.00 14.17 26.95 0.50 26.96



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 25.62 0.00 25.62
April 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
May 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.33 25.57 0.00 25.57
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.33 25.58 0.00 25.58
November 0.00 0.00 0.00 0.00 0.50 25.62 0.00 25.62
December 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
                 
Annual Sum or Average 0.00   0.00   2.33 25.59 0.00 25.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.50 25.62 0.00 25.62



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 19.37 1.17 19.57 0.00 19.57 0.00 19.57
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2.33 19.37 1.17 19.57 0.00 19.57 0.00 19.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.37 1.17 19.57 0.00 19.57 0.00 19.57



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.17 18.81 0.83 19.00 0.00 19.00 0.00 19.00
February 2.17 18.73 0.33 18.94 0.00 18.94 0.00 18.94
March 0.33 19.16 0.00 19.16 0.00 19.16 0.00 19.16
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 19.00 0.00 19.00 0.00 19.00 0.00 19.00
December 0.67 19.29 0.00 19.29 0.00 19.29 0.00 19.29
                 
Annual Sum or Average 8.17 18.86 1.17 19.01 0.00 19.01 0.00 19.01
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 4.17 19.29 0.83 19.29 0.00 19.29 0.00 19.29



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.85 0.00 18.85 0.00 18.85 0.00 18.85
February 0.33 18.89 0.00 18.89 0.00 18.89 0.00 18.89
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 25.85 0.00 25.85
August 0.00 0.00 0.00 0.00 1.00 26.75 0.67 26.98
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.67 18.87 0.00 18.87 1.33 23.97 0.67 24.81
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.33 18.89 0.00 18.89 1.00 26.75 0.67 26.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.33 18.87 0.00 18.87 0.00 18.87 0.00 18.87
February 0.50 19.05 0.00 19.05 0.00 19.05 0.00 19.05
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.17 27.39 1.17 27.39
May 0.00 0.00 0.00 0.00 4.83 27.77 4.83 27.77
June 0.00 0.00 0.00 0.00 1.67 27.84 1.67 27.84
July 0.00 0.00 0.00 0.00 5.17 27.66 4.83 27.73
August 0.00 0.00 0.00 0.00 3.67 27.62 3.67 27.62
September 0.00 0.00 0.00 0.00 3.50 27.91 3.50 27.91
October 0.00 0.00 0.00 0.00 0.17 27.28 0.17 27.28
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.83 18.98 0.00 18.98 20.17 27.37 19.83 27.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 19.05 0.00 19.05 5.17 27.91 4.83 27.91



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.50 18.82 0.00 18.82 0.00 18.82 0.00 18.82
February 0.50 18.88 0.00 18.88 0.17 20.98 0.17 22.24
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.17 27.42 0.17 27.42
May 0.00 0.00 0.00 0.00 2.33 27.13 2.33 27.13
June 0.00 0.00 0.00 0.00 1.67 27.37 1.67 27.37
July 0.00 0.00 0.00 0.00 7.17 27.42 6.50 27.49
August 0.00 0.00 0.00 0.00 6.67 27.34 5.00 27.54
September 0.00 0.00 0.00 0.00 6.33 27.81 5.83 27.88
October 0.00 0.00 0.00 0.00 5.17 27.64 5.17 27.64
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 1.50 27.43 1.50 27.43
                 
Annual Sum or Average 1.00 18.85 0.00 18.85 31.17 27.22 28.33 27.42
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.50 18.88 0.00 18.88 7.17 27.81 6.50 27.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.17 19.20 0.00 19.20 0.00 19.20 0.00 19.20
February 0.17 19.43 0.00 19.43 0.00 19.43 0.00 19.43
March 0.00 0.00 0.00 0.00 0.67 27.61 0.50 27.63
April 0.00 0.00 0.00 0.00 8.00 27.44 4.17 27.63
May 0.00 0.00 0.00 0.00 4.83 27.78 4.17 27.79
June 0.00 0.00 0.00 0.00 16.33 27.06 5.00 27.29
July 0.00 0.00 0.00 0.00 32.17 27.28 10.67 27.46
August 0.00 0.00 0.00 0.00 32.83 27.22 8.83 27.36
September 0.00 0.00 0.00 0.00 6.50 27.53 3.50 27.73
October 0.00 0.00 0.00 0.00 2.00 27.73 2.00 27.73
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.17 27.32 0.17 27.32
                 
Annual Sum or Average 0.33 19.32 0.00 19.32 103.50 27.26 39.00 27.45
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.43 0.00 19.43 32.83 27.78 10.67 27.79



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 27.83 17.10 8.50 17.18 0.00 17.18 0.00 17.18
February 22.50 17.50 6.17 17.81 0.00 17.81 0.00 17.81
March 1.83 19.20 0.17 19.30 0.00 19.30 0.00 19.30
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 2.67 19.03 0.33 19.18 0.00 19.18 0.00 19.18
December 6.00 18.02 0.33 18.15 0.00 18.15 0.00 18.15
                 
Annual Sum or Average 60.83 17.49 15.50 17.63 0.00 17.63 0.00 17.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 27.83 19.20 8.50 19.30 0.00 19.30 0.00 19.30



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 17.00 16.18 3.00 16.00 0.00 16.00 0.00 16.00
February 10.17 16.84 0.00 16.84 0.00 16.84 0.00 16.84
March 1.33 19.06 0.00 19.06 0.00 19.06 0.00 19.06
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 4.33 27.84 4.33 27.84
June 0.00 0.00 0.00 0.00 2.50 27.76 2.50 27.76
July 0.00 0.00 0.00 0.00 7.50 27.80 7.33 27.83
August 0.00 0.00 0.00 0.00 4.17 27.79 4.17 27.79
September 0.00 0.00 0.00 0.00 4.17 27.87 4.17 27.87
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.67 18.71 0.00 18.71 0.00 18.71 0.00 18.71
December 5.00 18.00 0.00 18.00 0.00 18.00 0.00 18.00
                 
Annual Sum or Average 35.17 16.86 3.00 16.71 22.67 20.85 22.50 22.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17.00 19.06 3.00 19.06 7.50 27.87 7.33 27.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 15.83 16.72 2.67 16.76 0.00 16.76 0.00 16.76
February 7.33 17.53 0.00 17.53 0.00 17.53 0.00 17.53
March 0.67 18.93 0.00 18.93 0.00 18.93 0.00 18.93
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 1.67 27.51 1.67 27.51
June 0.00 0.00 0.00 0.00 1.00 27.34 1.00 27.34
July 0.00 0.00 0.00 0.00 6.00 27.46 5.50 27.52
August 0.00 0.00 0.00 0.00 5.17 27.76 4.83 27.77
September 0.00 0.00 0.00 0.00 7.17 27.46 7.00 27.46
October 0.00 0.00 0.00 0.00 4.50 27.64 4.50 27.64
November 1.33 19.08 0.00 19.08 0.00 19.08 0.00 19.08
December 3.00 18.81 0.00 18.81 0.17 19.25 0.17 19.66
                 
Annual Sum or Average 28.17 17.32 2.67 17.29 25.67 21.95 24.67 23.66
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15.83 19.08 2.67 19.08 7.17 27.76 7.00 27.77



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 14.67 16.24 3.33 16.00 0.00 16.00 0.00 16.00
February 7.33 16.98 0.00 16.98 0.00 16.98 0.00 16.98
March 0.67 18.98 0.00 18.98 0.00 18.98 0.00 18.98
April 0.00 0.00 0.00 0.00 0.67 27.83 0.33 27.88
May 0.00 0.00 0.00 0.00 3.50 27.57 3.00 27.58
June 0.00 0.00 0.00 0.00 4.83 27.93 2.83 27.99
July 0.00 0.00 0.00 0.00 9.00 27.70 5.33 27.80
August 0.00 0.00 0.00 0.00 5.67 27.14 2.50 27.39
September 0.00 0.00 0.00 0.00 3.17 28.11 2.33 28.14
October 0.00 0.00 0.00 0.00 0.17 27.41 0.17 27.41
November 1.17 18.93 0.00 18.93 0.00 18.93 0.00 18.93
December 3.33 18.23 0.00 18.23 0.00 18.23 0.00 18.23
                 
Annual Sum or Average 27.17 16.87 3.33 16.66 27.00 21.82 16.50 23.19
Minimum of Months 0.00 0.00 0.00 0.00 0.00 16.00 0.00 16.00
Maximum of Months 14.67 18.98 3.33 18.98 9.00 28.11 5.33 28.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 64.33 16.35 19.50 16.49 0.00 16.49 0.00 16.49
February 55.17 16.56 20.33 16.77 0.00 16.77 0.00 16.77
March 12.00 18.19 1.83 18.38 0.00 18.38 0.00 18.38
April 2.17 18.80 0.17 18.92 0.00 18.92 0.00 18.92
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 2.50 27.19 1.83 27.29
August 0.00 0.00 0.00 0.00 1.33 27.43 1.17 27.44
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.33 19.36 0.00 19.36 0.00 19.36 0.00 19.36
November 16.83 17.20 4.00 17.29 0.00 17.29 0.00 17.29
December 27.67 17.05 6.50 17.05 0.00 17.05 0.00 17.05
                 
Annual Sum or Average 178.50 16.77 52.33 16.88 3.83 17.05 3.00 17.18
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 64.33 19.36 20.33 19.36 2.50 27.43 1.83 27.44



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 44.50 15.44 11.50 15.35 0.00 15.35 0.00 15.35
February 33.17 15.77 8.33 15.67 0.00 15.67 0.00 15.67
March 8.50 17.81 0.17 17.86 0.00 17.86 0.00 17.86
April 1.67 18.56 0.00 18.56 0.00 18.56 0.00 18.56
May 0.00 0.00 0.00 0.00 5.33 27.76 5.33 27.76
June 0.00 0.00 0.00 0.00 3.00 27.77 3.00 27.77
July 0.00 0.00 0.00 0.00 12.00 27.76 11.33 27.79
August 0.00 0.00 0.00 0.00 5.67 27.80 5.33 27.81
September 0.00 0.00 0.00 0.00 4.17 27.84 4.17 27.84
October 0.17 19.38 0.00 19.38 0.00 19.38 0.00 19.38
November 10.33 16.68 0.83 16.54 0.00 16.54 0.00 16.54
December 20.50 16.37 3.33 16.13 0.00 16.13 0.00 16.13
                 
Annual Sum or Average 118.83 16.02 24.17 15.86 30.17 17.94 29.17 19.36
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.35 0.00 15.35
Maximum of Months 44.50 19.38 11.50 19.38 12.00 27.84 11.33 27.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 35.83 15.94 8.17 15.88 0.00 15.88 0.00 15.88
February 26.83 16.41 3.50 16.47 0.00 16.47 0.00 16.47
March 6.00 18.37 0.17 18.42 0.00 18.42 0.00 18.42
April 1.67 18.67 0.00 18.67 0.00 18.67 0.00 18.67
May 0.00 0.00 0.00 0.00 2.50 27.40 2.50 27.40
June 0.00 0.00 0.00 0.00 2.17 27.47 2.17 27.47
July 0.00 0.00 0.00 0.00 8.83 27.56 8.00 27.60
August 0.00 0.00 0.00 0.00 5.67 27.91 5.17 27.92
September 0.00 0.00 0.00 0.00 5.83 28.11 5.33 28.14
October 0.00 0.00 0.00 0.00 2.17 27.67 2.17 27.67
November 7.67 17.38 0.33 17.28 0.00 17.28 0.00 17.28
December 16.67 16.86 1.17 16.77 0.00 16.77 0.00 16.77
                 
Annual Sum or Average 94.67 16.55 13.33 16.49 27.17 18.75 25.33 20.17
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.88 0.00 15.88
Maximum of Months 35.83 18.67 8.17 18.67 8.83 28.11 8.00 28.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 34.17 15.52 8.50 15.36 0.00 15.36 0.00 15.36
February 22.67 15.84 4.33 15.63 0.00 15.63 0.00 15.63
March 5.17 18.57 0.00 18.57 0.00 18.57 0.00 18.57
April 1.17 18.90 0.00 18.90 0.67 22.12 0.50 23.33
May 0.00 0.00 0.00 0.00 3.83 27.64 3.33 27.66
June 0.00 0.00 0.00 0.00 5.17 28.04 3.17 28.08
July 0.00 0.00 0.00 0.00 10.17 27.95 5.83 28.04
August 0.00 0.00 0.00 0.00 6.33 27.37 3.17 27.58
September 0.00 0.00 0.00 0.00 3.67 28.09 2.67 28.11
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 6.67 17.44 0.33 17.33 0.00 17.33 0.00 17.33
December 14.00 17.03 2.00 16.73 0.00 16.73 0.00 16.73
                 
Annual Sum or Average 83.83 16.25 15.17 16.00 29.83 18.74 18.67 19.92
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 34.17 18.90 8.50 18.90 10.17 28.09 5.83 28.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 7.83 27.68 7.83 27.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.83 27.68 7.83 27.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.83 27.68 7.83 27.68



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 7.33 27.68 7.33 27.68
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   7.33 27.68 7.33 27.68
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.33 27.68 7.33 27.68



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 3.33 27.63 3.33 27.63
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   3.33 27.63 3.33 27.63
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.33 27.63 3.33 27.63



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 2.33 27.75 2.33 27.75
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 332.00 28.62 295.83 28.65
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   334.33 28.61 298.17 28.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 332.00 28.62 295.83 28.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 311.50 23.84 42.83 24.02 0.00 24.02
February 298.50 23.86 27.33 24.06 0.00 24.06
March 144.00 23.99 88.67 24.57 0.00 24.57
April 50.17 24.01 139.00 25.06 0.00 25.06
May 32.00 24.00 274.50 24.73 24.83 24.68
June 151.17 24.79 438.00 24.57 151.17 24.61
July 230.17 25.23 497.00 24.79 230.17 24.90
August 102.33 25.21 476.50 24.64 102.33 24.72
September 59.00 25.21 388.83 24.74 59.00 24.80
October 56.00 24.32 336.17 24.77 23.83 24.77
November 52.83 24.00 137.00 25.28 0.00 25.28
December 202.33 24.00 85.83 24.69 0.00 24.69
             
Annual Sum or Average 1690.00 24.31 2931.67 24.64 591.33 24.68
Minimum of Months 32.00 23.84 27.33 24.02 0.00 24.02
Maximum of Months 311.50 25.23 497.00 25.28 230.17 25.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 397.67 23.61 9.33 23.62 0.00 23.62
February 335.00 23.83 10.00 23.88 0.00 23.88
March 148.00 23.92 76.17 24.34 0.00 24.34
April 44.67 23.93 148.83 24.65 0.00 24.65
May 15.33 23.90 249.17 24.43 0.00 24.43
June 0.00 0.00 432.17 24.27 0.00 24.27
July 0.00 0.00 497.00 24.21 0.00 24.21
August 0.00 0.00 480.17 24.18 0.00 24.18
September 5.17 23.87 389.17 24.38 0.00 24.38
October 46.00 23.98 311.83 24.44 0.00 24.44
November 86.00 23.92 109.67 24.76 0.00 24.76
December 194.17 23.94 40.17 24.24 0.00 24.24
             
Annual Sum or Average 1272.00 23.80 2753.67 24.23 0.00 24.23
Minimum of Months 0.00 0.00 9.33 23.62 0.00 23.62
Maximum of Months 397.67 23.98 497.00 24.76 0.00 24.76



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.91 91.00 21.62 91.00 21.41
February 454.00 22.41 39.33 22.28 39.33 22.18
March 463.67 23.30 4.83 23.31 0.00 23.31
April 277.33 23.45 34.17 23.58 0.00 23.58
May 100.50 23.68 185.83 24.07 0.00 24.07
June 13.00 23.68 417.83 24.21 0.00 24.21
July 0.00 0.00 490.17 24.22 0.00 24.22
August 0.00 0.00 456.00 24.25 0.00 24.25
September 27.00 23.59 327.83 24.23 0.00 24.23
October 134.83 23.75 221.17 24.05 0.00 24.05
November 358.67 23.10 36.33 23.23 0.00 23.23
December 497.00 22.79 4.50 22.77 4.50 22.76
             
Annual Sum or Average 2828.00 22.85 2309.00 23.38 134.83 23.30
Minimum of Months 0.00 0.00 4.50 21.62 0.00 21.41
Maximum of Months 502.00 23.75 490.17 24.25 91.00 24.25



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.88 215.50 20.55 215.50 20.37
February 454.00 21.12 205.67 20.85 205.67 20.71
March 501.83 22.14 53.67 21.98 53.67 21.86
April 365.33 22.61 47.83 22.65 17.00 22.56
May 177.17 23.36 145.50 23.74 0.00 23.74
June 10.83 23.61 416.83 24.22 0.00 24.22
July 0.00 0.00 497.00 24.29 0.00 24.29
August 0.17 27.09 458.33 24.28 0.17 24.28
September 69.50 23.33 313.50 24.06 0.00 24.06
October 274.83 22.96 160.00 23.34 5.17 23.31
November 471.00 21.97 80.33 21.71 78.67 21.51
December 497.00 21.18 165.17 20.87 165.17 20.69
             
Annual Sum or Average 3323.67 21.86 2759.33 22.43 741.00 22.17
Minimum of Months 0.00 0.00 47.83 20.55 0.00 20.37
Maximum of Months 502.00 27.09 497.00 24.29 215.50 24.29



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.34 172.50 21.11 172.50 20.98
February 454.00 21.58 126.00 21.38 126.00 21.25
March 480.83 22.77 9.83 22.79 2.33 22.78
April 299.83 23.27 58.50 23.44 0.00 23.44
May 94.83 23.64 189.33 24.09 0.00 24.09
June 4.33 25.23 450.17 24.31 3.17 24.32
July 8.83 26.68 497.00 24.43 8.83 24.47
August 5.50 26.72 481.17 24.31 5.50 24.33
September 58.17 23.82 341.17 24.25 4.00 24.27
October 203.83 23.40 208.33 23.77 0.00 23.77
November 422.50 22.83 15.00 22.82 7.67 22.79
December 497.00 22.24 16.67 22.19 16.67 22.15
             
Annual Sum or Average 3031.67 22.44 2565.67 23.08 346.67 22.95
Minimum of Months 4.33 21.34 9.83 21.11 0.00 20.98
Maximum of Months 502.00 26.72 497.00 24.43 172.50 24.47



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 500.83 21.34 154.83 21.12 154.83 20.99
February 449.17 21.71 100.50 21.53 100.50 21.40
March 435.83 22.49 16.67 22.51 8.50 22.48
April 285.67 22.84 95.00 23.26 1.67 23.28
May 116.00 23.79 252.67 24.27 15.50 24.38
June 14.17 26.25 459.67 24.35 12.17 24.41
July 30.50 26.78 497.00 24.51 30.50 24.63
August 16.83 26.62 485.50 24.32 16.00 24.39
September 69.83 24.27 365.83 24.40 20.00 24.50
October 182.17 23.24 215.67 23.79 2.50 23.81
November 407.50 22.53 22.17 22.56 9.83 22.52
December 491.67 21.92 26.83 21.86 26.83 21.80
             
Annual Sum or Average 3000.17 22.35 2692.33 23.10 398.83 23.03
Minimum of Months 14.17 21.34 16.67 21.12 1.67 20.99
Maximum of Months 500.83 26.78 497.00 24.51 154.83 24.63



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 456.17 21.51 139.50 21.24 135.83 21.05
February 388.00 22.01 92.67 21.86 83.00 21.68
March 377.67 22.65 54.50 22.72 17.17 22.65
April 263.00 22.96 103.33 23.39 3.17 23.40
May 117.17 23.57 218.67 24.12 6.00 24.17
June 18.17 25.70 454.83 24.38 13.00 24.44
July 34.83 26.79 497.00 24.59 34.83 24.72
August 21.17 26.93 497.00 24.45 21.17 24.55
September 59.00 25.03 405.00 24.54 26.50 24.66
October 112.67 23.80 308.33 24.30 12.00 24.37
November 327.00 22.69 71.83 22.89 12.17 22.82
December 413.50 22.20 44.33 22.21 31.67 22.11
             
Annual Sum or Average 2588.33 22.58 2887.00 23.35 396.50 23.28
Minimum of Months 18.17 21.51 44.33 21.24 3.17 21.05
Maximum of Months 456.17 26.93 497.00 24.59 135.83 24.72



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 487.50 21.86 76.50 21.69 75.83 21.56
February 413.50 22.46 32.67 22.44 24.33 22.36
March 204.00 23.46 100.17 23.85 1.67 23.86
April 54.50 24.55 258.17 24.74 15.33 24.85
May 36.00 25.16 353.83 24.57 18.00 24.67
June 37.00 26.95 480.83 24.68 37.00 24.83
July 76.83 26.82 497.00 24.91 76.83 25.14
August 69.67 26.77 514.00 24.78 69.67 24.99
September 29.50 26.22 417.83 24.61 23.00 24.72
October 58.33 24.02 324.50 24.45 6.00 24.49
November 199.83 23.30 109.83 23.87 0.33 23.88
December 332.00 23.44 23.83 23.60 0.00 23.60
             
Annual Sum or Average 1998.67 23.27 3189.17 24.00 348.00 24.07
Minimum of Months 29.50 21.86 23.83 21.69 0.00 21.56
Maximum of Months 487.50 26.95 514.00 24.91 76.83 25.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.09 396.33 19.98 396.33 19.93
February 454.00 20.27 385.00 20.21 385.00 20.18
March 513.33 21.11 186.67 20.91 186.67 20.79
April 420.67 22.02 50.50 21.94 37.67 21.81
May 246.83 23.18 116.17 23.51 0.00 23.51
June 42.00 24.83 418.33 24.30 27.67 24.36
July 58.17 25.87 497.00 24.57 58.17 24.70
August 30.33 25.87 461.00 24.43 29.17 24.51
September 125.83 23.27 273.67 23.90 9.67 23.92
October 349.67 22.43 115.17 22.67 20.17 22.58
November 489.00 21.15 158.00 20.87 158.00 20.70
December 497.00 20.37 405.00 20.30 405.00 20.27
             
Annual Sum or Average 3728.83 21.37 3462.83 21.85 1713.50 21.59
Minimum of Months 30.33 20.09 50.50 19.98 0.00 19.93
Maximum of Months 513.33 25.87 497.00 24.57 405.00 24.70



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 20.00 331.67 19.86 331.67 19.80
February 385.00 20.39 288.33 20.25 288.33 20.20
March 422.50 21.32 112.33 21.07 112.33 20.90
April 302.83 22.02 76.83 22.36 18.50 22.27
May 188.33 23.13 150.67 23.84 13.50 23.96
June 37.67 25.48 362.33 24.49 27.50 24.60
July 76.00 26.43 421.67 24.87 76.00 25.07
August 40.67 26.46 408.33 24.65 39.67 24.81
September 115.17 23.68 264.17 24.24 25.50 24.36
October 251.83 22.51 112.00 22.97 6.00 22.94
November 413.33 21.23 120.83 20.93 120.83 20.74
December 422.00 20.42 296.50 20.28 296.50 20.22
             
Annual Sum or Average 3082.33 21.49 2945.67 22.08 1356.33 21.85
Minimum of Months 37.67 20.00 76.83 19.86 6.00 19.80
Maximum of Months 427.00 26.46 421.67 24.87 331.67 25.07



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 475.83 20.72 254.00 20.35 254.00 20.17
February 406.83 21.22 205.83 20.95 198.00 20.76
March 410.67 21.74 112.17 21.65 84.67 21.46
April 328.50 22.23 97.17 22.55 22.33 22.45
May 197.83 23.17 166.83 23.74 4.83 23.78
June 43.00 25.01 432.17 24.36 26.17 24.44
July 73.67 26.23 497.00 24.70 73.67 24.88
August 43.33 26.54 489.33 24.60 43.33 24.74
September 84.00 24.40 375.17 24.41 31.17 24.55
October 162.33 23.28 276.50 24.01 13.00 24.08
November 383.17 21.83 111.67 21.71 77.50 21.48
December 442.67 21.24 209.00 21.00 199.00 20.81
             
Annual Sum or Average 3051.83 21.97 3226.83 22.65 1027.67 22.45
Minimum of Months 43.00 20.72 97.17 20.35 4.83 20.17
Maximum of Months 475.83 26.54 497.00 24.70 254.00 24.88



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.35 325.67 20.16 325.67 20.07
February 453.33 20.69 290.17 20.49 290.17 20.40
March 461.00 21.50 108.83 21.38 98.83 21.25
April 346.50 22.14 81.33 22.44 16.50 22.39
May 187.00 23.18 207.50 23.82 9.67 23.90
June 43.50 25.52 450.83 24.48 32.50 24.59
July 67.00 26.53 497.00 24.77 67.00 24.96
August 37.33 26.68 496.67 24.61 37.33 24.74
September 101.67 23.56 324.33 24.15 19.50 24.24
October 246.33 22.55 185.67 23.20 4.50 23.18
November 473.33 21.32 123.17 21.07 122.83 20.90
December 497.00 20.72 290.17 20.56 290.17 20.48
             
Annual Sum or Average 3416.00 21.59 3381.33 22.27 1314.67 22.05
Minimum of Months 37.33 20.35 81.33 20.16 4.50 20.07
Maximum of Months 502.00 26.68 497.00 24.77 325.67 24.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.85 449.33 19.78 449.33 19.76
February 454.00 19.95 436.17 19.93 436.17 19.92
March 514.00 20.62 304.50 20.42 304.50 20.33
April 428.00 21.38 138.33 21.15 125.00 20.96
May 292.33 22.69 104.00 23.09 1.83 23.08
June 59.17 24.49 406.33 24.28 31.17 24.36
July 74.33 25.97 497.00 24.64 74.33 24.79
August 44.67 25.52 457.00 24.44 36.33 24.55
September 170.17 22.87 244.33 23.64 12.33 23.65
October 396.00 21.76 152.17 21.76 82.67 21.52
November 489.00 20.45 280.67 20.21 280.67 20.09
December 497.00 19.93 474.83 19.90 474.83 19.90
             
Annual Sum or Average 3920.67 21.00 3944.67 21.45 2309.17 21.18
Minimum of Months 44.67 19.85 104.00 19.78 1.83 19.76
Maximum of Months 514.00 25.97 497.00 24.64 474.83 24.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.90 428.83 19.81 428.83 19.77
February 454.00 20.11 401.17 20.05 401.17 20.03
March 509.33 20.95 203.50 20.63 203.50 20.45
April 369.33 21.63 149.83 21.71 86.50 21.49
May 236.67 22.73 193.50 23.55 16.67 23.67
June 54.00 25.09 429.17 24.41 33.50 24.53
July 85.33 26.40 495.00 24.79 85.33 25.00
August 47.33 26.32 485.17 24.57 44.17 24.72
September 154.00 23.33 305.83 24.02 29.83 24.14
October 322.83 22.03 159.00 22.41 36.50 22.26
November 489.00 20.67 233.33 20.36 233.33 20.20
December 497.00 20.03 451.83 19.98 451.83 19.96
             
Annual Sum or Average 3720.83 21.17 3936.17 21.74 2051.17 21.48
Minimum of Months 47.33 19.90 149.83 19.81 16.67 19.77
Maximum of Months 509.33 26.40 495.00 24.79 451.83 25.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 490.67 20.38 320.83 20.04 320.83 19.89
February 436.00 20.78 283.00 20.44 283.00 20.29
March 437.00 21.15 195.67 20.89 177.00 20.67
April 357.00 21.62 159.17 21.72 92.67 21.49
May 251.67 22.67 156.00 23.33 9.50 23.38
June 64.00 24.46 416.83 24.32 30.33 24.41
July 81.17 26.17 495.50 24.72 81.17 24.89
August 50.17 26.18 485.33 24.58 44.33 24.74
September 114.67 23.70 343.67 24.22 32.33 24.35
October 211.17 22.50 258.00 23.34 31.83 23.27
November 425.83 21.10 188.17 20.81 169.33 20.57
December 472.50 20.64 305.50 20.33 303.50 20.18
             
Annual Sum or Average 3391.83 21.50 3607.67 22.09 1575.83 21.83
Minimum of Months 50.17 20.38 156.00 20.04 9.50 19.89
Maximum of Months 490.67 26.18 495.50 24.72 320.83 24.89



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.05 390.50 19.90 390.50 19.84
February 454.00 20.32 357.83 20.17 357.83 20.12
March 475.17 21.03 198.50 20.80 191.50 20.65
April 374.50 21.61 131.33 21.75 71.83 21.56
May 248.67 22.77 182.50 23.48 13.00 23.58
June 61.67 25.00 434.33 24.44 38.00 24.57
July 76.33 26.47 495.33 24.78 76.33 24.98
August 45.00 26.38 493.83 24.60 41.33 24.75
September 142.00 23.12 290.67 23.92 21.83 24.02
October 303.50 21.96 180.00 22.42 40.83 22.25
November 481.83 20.72 221.00 20.44 221.00 20.29
December 497.00 20.24 404.17 20.13 404.17 20.09
             
Annual Sum or Average 3661.67 21.24 3780.00 21.84 1868.17 21.59
Minimum of Months 45.00 20.05 131.33 19.90 13.00 19.84
Maximum of Months 502.00 26.47 495.33 24.78 404.17 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 469.83 27.00 0.00 27.00
February 0.00 0.00 454.00 27.00 0.00 27.00
March 5.67 27.00 514.00 27.00 5.67 27.00
April 73.17 27.00 485.00 27.00 73.17 27.00
May 3.67 27.00 508.00 27.00 3.67 27.00
June 80.33 27.00 496.00 27.00 80.33 27.00
July 261.17 27.00 497.00 27.00 261.17 27.00
August 440.33 27.05 514.00 27.05 440.33 27.05
September 24.17 27.00 485.00 27.00 24.17 27.00
October 34.50 27.00 502.00 27.00 34.50 27.00
November 5.83 27.00 489.00 27.00 5.83 27.00
December 0.00 0.00 497.00 27.00 0.00 27.00
             
Annual Sum or Average 928.83 27.02 5910.83 27.01 928.83 27.01
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 440.33 27.05 514.00 27.05 440.33 27.05



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 86.17 25.05 295.00 26.41 12.17 26.29
February 0.00 0.00 269.00 27.00 0.00 27.00
March 0.00 0.00 495.67 27.00 0.00 27.00
April 2.17 27.00 485.00 27.00 2.17 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 2.17 27.00 496.00 27.00 2.17 27.00
July 33.83 27.00 497.00 27.00 33.83 27.00
August 110.33 27.17 514.00 27.06 110.33 27.08
September 6.50 27.00 485.00 27.00 6.50 27.00
October 4.00 27.00 502.00 27.00 4.00 27.00
November 0.00 0.00 447.33 27.00 0.00 27.00
December 0.00 0.00 444.17 27.00 0.00 27.00
             
Annual Sum or Average 245.17 26.39 5438.17 26.97 171.17 26.96
Minimum of Months 0.00 0.00 269.00 26.41 0.00 26.29
Maximum of Months 110.33 27.17 514.00 27.06 110.33 27.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 191.00 24.64 210.67 25.40 41.17 25.12
February 55.00 27.00 156.00 27.00 0.00 27.00
March 0.67 27.00 431.33 27.00 0.00 27.00
April 6.33 27.00 469.83 27.00 6.33 27.00
May 3.67 27.00 508.00 27.00 3.67 27.00
June 33.50 27.00 496.00 27.00 33.50 27.00
July 100.17 27.00 497.00 27.00 100.17 27.00
August 169.00 27.07 514.00 27.03 169.00 27.04
September 14.33 27.00 485.00 27.00 14.33 27.00
October 6.83 27.00 474.33 27.00 6.83 27.00
November 10.17 27.00 395.83 27.00 0.00 27.00
December 28.33 27.00 274.33 27.00 0.00 27.00
             
Annual Sum or Average 619.00 26.29 4912.33 26.89 375.00 26.87
Minimum of Months 0.67 24.64 156.00 25.40 0.00 25.12
Maximum of Months 191.00 27.07 514.00 27.03 169.00 27.04



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 168.67 27.00 502.00 27.00 168.67 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.01 485.00 27.01 485.00 27.01
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.02 514.00 28.02 514.00 28.02
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.01 497.00 27.01 497.00 27.01
             
Annual Sum or Average 5609.67 27.10 5943.00 27.09 5609.67 27.10
Minimum of Months 168.67 27.00 454.00 27.00 168.67 27.00
Maximum of Months 514.00 28.02 514.00 28.02 514.00 28.02



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.99970 20.72905 0.69140 15.24593
February 454.00000 27.00000 17.41129 0.72365 16.13479
March 514.00000 27.00004 24.54627 0.86951 21.07395
April 485.00000 27.00003 29.77106 0.96624 24.81504
May 508.00000 27.00045 34.25256 0.25376 6.42203
June 496.00000 27.00144 38.07483 0.36121 7.77419
July 497.00000 27.00110 39.19636 0.42296 8.77965
August 514.00000 27.04241 38.46187 0.48461 10.01698
September 485.00000 27.00060 37.70496 0.29925 6.97149
October 502.00000 27.00069 31.71066 0.93786 23.72332
November 489.00000 27.00007 27.01815 0.88656 21.73647
December 497.00000 26.99999 20.17986 0.83938 19.93474
           
Annual Sum or Average 5943.00000 27.00401 30.00989 0.64365 15.19494
Minimum of Months 454.00000 26.99970 17.41129 0.25376 6.42203
Maximum of Months 514.00000 27.04241 39.19636 0.96624 24.81504



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.62558 20.84880 0.48204 11.30248
February 454.00000 27.00000 17.40914 0.56692 11.90078
March 514.00000 27.00003 24.53094 0.71754 16.02677
April 485.00000 27.00003 29.73603 0.82321 19.48423
May 508.00000 27.00025 34.32985 0.17634 5.79068
June 496.00000 27.00138 38.11991 0.28392 6.75348
July 497.00000 27.00114 39.22083 0.33083 7.33562
August 514.00000 27.03713 38.45932 0.36756 7.93357
September 485.00000 27.00042 37.83195 0.22974 6.25930
October 502.00000 27.00066 31.71887 0.84860 20.42897
November 489.00000 27.00006 26.99860 0.72191 16.22368
December 497.00000 26.99999 20.16658 0.63180 13.49202
           
Annual Sum or Average 5943.00000 26.97192 30.03619 0.51416 11.89794
Minimum of Months 454.00000 26.62558 17.40914 0.17634 5.79068
Maximum of Months 514.00000 27.03713 39.22083 0.84860 20.42897



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.01956 21.27676 0.31632 10.04319
February 454.00000 27.00005 17.40702 0.50103 10.49260
March 514.00000 27.00004 24.54509 0.65505 14.32366
April 485.00000 27.00004 29.75293 0.77730 18.09355
May 508.00000 27.00031 34.41500 0.15534 5.79623
June 496.00000 27.00142 38.12581 0.29293 6.92907
July 497.00000 27.00117 39.22828 0.35141 7.67842
August 514.00000 27.02219 38.48396 0.37853 8.14695
September 485.00000 27.00043 37.86720 0.21641 6.25702
October 502.00000 27.00066 31.76558 0.80742 19.16506
November 489.00000 27.00006 27.02031 0.64783 14.16472
December 497.00000 27.00000 20.17199 0.55098 11.55704
           
Annual Sum or Average 5943.00000 26.91945 30.09437 0.47018 11.04728
Minimum of Months 454.00000 26.01956 17.40702 0.15534 5.79623
Maximum of Months 514.00000 27.02219 39.22828 0.80742 19.16506



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00071 30.96693 1.01472 26.76942
February 454.00000 27.00458 30.19475 1.18156 34.35935
March 514.00000 27.00454 30.86757 1.35648 43.21357
April 485.00000 27.00886 32.72327 1.51487 51.71122
May 508.00000 27.00115 34.76151 0.50927 10.46890
June 496.00000 27.00177 37.70167 0.77461 17.66597
July 497.00000 27.00113 38.88508 0.99566 25.95307
August 514.00000 28.02354 37.74792 1.48183 49.99003
September 485.00000 27.00189 37.23299 0.59229 12.42102
October 502.00000 27.00182 34.54840 1.29274 39.91231
November 489.00000 27.00335 31.62904 1.39096 45.03753
December 497.00000 27.00781 30.27393 1.49697 50.73674
           
Annual Sum or Average 5943.00000 27.09163 33.98818 1.13370 34.04053
Minimum of Months 454.00000 27.00071 30.19475 0.50927 10.46890
Maximum of Months 514.00000 28.02354 38.88508 1.51487 51.71122



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.15434 22.09410 0.25150 6.78144
February 454.00000 24.26260 17.78349 0.25371 6.81823
March 514.00000 24.34119 25.17798 0.33937 7.76848
April 485.00000 24.44549 31.32855 0.41069 9.05072
May 508.00000 24.45293 40.66802 -0.3821 8.87597
June 496.00000 24.43611 55.99032 -0.2620 7.40624
July 497.00000 24.58780 61.55023 -0.1693 7.01400
August 514.00000 24.47468 55.81498 -0.2321 7.35000
September 485.00000 24.53789 49.72913 -0.2652 7.80546
October 502.00000 24.58367 40.83262 0.52710 11.67501
November 489.00000 24.54212 27.34979 0.41277 9.20391
December 497.00000 24.49257 19.82143 0.33804 7.85534
           
Annual Sum or Average 5943.00000 24.44329 37.49833 0.09984 8.14067
Minimum of Months 454.00000 24.15434 17.78349 -0.3821 6.78144
Maximum of Months 514.00000 24.58780 61.55023 0.52710 11.67501



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.75537 26.98230 0.17753 6.07305
February 454.00000 24.02860 21.01433 0.21317 6.22474
March 514.00000 24.23885 26.96551 0.33321 7.60530
April 485.00000 24.29181 32.67376 0.40399 8.76051
May 508.00000 24.24752 41.61149 -0.4150 9.08152
June 496.00000 24.23814 51.82908 -0.3208 7.50043
July 497.00000 24.20976 55.47642 -0.2911 6.93776
August 514.00000 24.17198 51.70184 -0.3145 7.23556
September 485.00000 24.31800 48.06509 -0.3343 7.91188
October 502.00000 24.36178 40.29542 0.47822 10.30224
November 489.00000 24.40849 29.69087 0.39194 8.79298
December 497.00000 24.28707 22.24576 0.30481 7.18143
           
Annual Sum or Average 5943.00000 24.21357 37.50629 0.05012 7.80942
Minimum of Months 454.00000 23.75537 21.01433 -0.4150 6.07305
Maximum of Months 514.00000 24.40849 55.47642 0.47822 10.30224



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.90912 28.27207 -0.2965 9.25482
February 454.00000 22.41110 23.46341 -0.1967 6.90251
March 514.00000 23.37603 30.18395 0.09763 5.78645
April 485.00000 23.75909 35.07565 0.24322 6.75659
May 508.00000 24.04938 42.47038 -0.5094 10.86887
June 496.00000 24.18483 52.50778 -0.3686 8.20651
July 497.00000 24.21573 56.27238 -0.3264 7.52926
August 514.00000 24.22620 52.49264 -0.3440 7.87784
September 485.00000 24.17511 48.67846 -0.4088 8.97085
October 502.00000 24.03774 41.67668 0.37525 8.48383
November 489.00000 23.40990 33.27548 0.12617 6.47819
December 497.00000 22.79314 26.49974 -0.0805 5.82702
           
Annual Sum or Average 5943.00000 23.55363 39.35915 -0.1411 7.75492
Minimum of Months 454.00000 21.90912 23.46341 -0.5094 5.78645
Maximum of Months 514.00000 24.22620 56.27238 0.37525 10.86887



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.87706 29.96459 -0.5633 14.84307
February 454.00000 21.12079 24.76126 -0.5305 12.98252
March 514.00000 22.18254 32.47707 -0.1989 7.43599
April 485.00000 22.98216 37.08097 0.05161 6.97747
May 508.00000 23.84519 43.30954 -0.5802 12.97129
June 496.00000 24.19296 52.40553 -0.3540 8.04143
July 497.00000 24.29052 55.77075 -0.2836 7.08177
August 514.00000 24.24806 52.20435 -0.3211 7.61377
September 485.00000 24.04301 49.30115 -0.4531 10.03051
October 502.00000 23.43749 43.60441 0.22426 7.76991
November 489.00000 22.03950 36.04160 -0.2185 8.45435
December 497.00000 21.17759 28.99790 -0.4871 11.91556
           
Annual Sum or Average 5943.00000 22.88328 40.60972 -0.3085 9.65574
Minimum of Months 454.00000 20.87706 24.76126 -0.5802 6.97747
Maximum of Months 514.00000 24.29052 55.77075 0.22426 14.84307



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.33805 26.77439 -0.4250 10.28420
February 454.00000 21.58013 21.41213 -0.3939 9.38964
March 514.00000 22.85439 28.29039 -0.0271 6.07320
April 485.00000 23.60130 33.25466 0.20735 6.74254
May 508.00000 24.07145 41.26217 -0.4913 10.72687
June 496.00000 24.27798 51.33333 -0.2845 7.19086
July 497.00000 24.39083 54.84450 -0.1910 6.50149
August 514.00000 24.26021 50.95397 -0.2596 6.92516
September 485.00000 24.18650 48.06415 -0.3917 8.93200
October 502.00000 23.81077 40.52551 0.31562 8.04834
November 489.00000 23.00819 30.81996 0.02435 6.38313
December 497.00000 22.24150 23.78261 -0.2099 6.68643
           
Annual Sum or Average 5943.00000 23.31373 37.73314 -0.1764 7.81437
Minimum of Months 454.00000 21.33805 21.41213 -0.4913 6.07320
Maximum of Months 514.00000 24.39083 54.84450 0.31562 10.72687



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.34423 26.42230 -0.4149 10.08026
February 454.00000 21.74486 20.86629 -0.3435 8.80684
March 514.00000 22.73482 27.96661 -0.0298 6.41630
April 485.00000 23.41709 33.20701 0.19867 7.55574
May 508.00000 24.09182 40.98981 -0.4228 10.64735
June 496.00000 24.25936 51.22290 -0.2501 7.18024
July 497.00000 24.37070 54.67307 -0.1579 6.75089
August 514.00000 24.21891 50.81430 -0.2149 6.80207
September 485.00000 24.23079 47.65369 -0.3234 8.89971
October 502.00000 23.80303 40.21541 0.34898 8.80348
November 489.00000 22.80136 30.74085 -0.0070 6.60103
December 497.00000 21.94765 23.68073 -0.2679 7.47885
           
Annual Sum or Average 5943.00000 23.25777 37.49617 -0.1564 7.99654
Minimum of Months 454.00000 21.34423 20.86629 -0.4228 6.41630
Maximum of Months 514.00000 24.37070 54.67307 0.34898 10.64735



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.75449 26.10812 -0.3159 10.19595
February 454.00000 22.36630 20.32285 -0.1919 8.58435
March 514.00000 23.02630 27.44105 0.04807 6.79782
April 485.00000 23.54706 33.00319 0.22265 7.77031
May 508.00000 24.05643 41.22641 -0.4717 11.06801
June 496.00000 24.30252 51.16818 -0.2580 7.18114
July 497.00000 24.43290 54.52523 -0.1484 6.62299
August 514.00000 24.33289 50.43818 -0.1629 6.50037
September 485.00000 24.35038 47.26257 -0.2518 8.02608
October 502.00000 24.19433 39.12641 0.48330 11.34283
November 489.00000 23.19551 30.03541 0.09913 7.23809
December 497.00000 22.57485 23.03522 -0.1136 7.63921
           
Annual Sum or Average 5943.00000 23.51904 37.10086 -0.0884 8.24809
Minimum of Months 454.00000 21.75449 20.32285 -0.4717 6.50037
Maximum of Months 514.00000 24.43290 54.52523 0.48330 11.34283



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.92662 25.20861 -0.2546 7.95594
February 454.00000 22.64582 19.44996 -0.1039 6.83633
March 514.00000 23.94962 25.52709 0.29945 7.68291
April 485.00000 24.40193 30.89617 0.49690 11.21192
May 508.00000 24.32573 40.20595 -0.2994 8.19663
June 496.00000 24.49255 50.16542 -0.0707 6.57757
July 497.00000 24.61589 53.48573 0.04266 6.88803
August 514.00000 24.51140 49.65831 0.03892 6.52107
September 485.00000 24.41465 46.91856 -0.2055 7.38215
October 502.00000 24.34679 38.75215 0.52665 11.81982
November 489.00000 23.94243 28.28490 0.29163 7.83605
December 497.00000 23.76821 20.91079 0.18778 6.37501
           
Annual Sum or Average 5943.00000 23.95356 35.91403 0.07986 7.94212
Minimum of Months 454.00000 21.92662 19.44996 -0.2994 6.37501
Maximum of Months 514.00000 24.61589 53.48573 0.52665 11.81982



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.08812 28.33172 -0.8033 21.22662
February 454.00000 20.27437 22.85651 -0.7787 19.73761
March 514.00000 21.11824 31.46645 -0.4603 10.87375
April 485.00000 22.28480 36.30857 -0.1205 7.52409
May 508.00000 23.64544 42.71134 -0.6534 15.34127
June 496.00000 24.19888 52.83049 -0.3306 7.85843
July 497.00000 24.42006 57.18987 -0.1997 6.79309
August 514.00000 24.29475 52.66338 -0.2822 7.41658
September 485.00000 23.88803 49.40014 -0.5097 11.62224
October 502.00000 22.87715 42.95286 0.08436 7.44981
November 489.00000 21.14930 34.70208 -0.4364 11.32391
December 497.00000 20.36884 27.23735 -0.7069 16.90967
           
Annual Sum or Average 5943.00000 22.40045 40.01415 -0.4310 11.95565
Minimum of Months 454.00000 20.08812 22.85651 -0.8033 6.79309
Maximum of Months 514.00000 24.42006 57.18987 0.08436 21.22662



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 20.00487 27.30061 -0.8066 21.60935
February 385.00000 20.38942 21.64626 -0.7238 18.15943
March 433.00000 21.38817 30.09018 -0.3735 9.97369
April 410.00000 22.64444 34.71043 -0.0070 8.08845
May 430.00000 23.76265 41.80065 -0.5494 14.76326
June 418.00000 24.29239 52.20793 -0.2546 7.79066
July 422.00000 24.58473 56.34461 -0.0979 7.25220
August 433.00000 24.44164 51.93182 -0.1624 7.01490
September 410.00000 24.05504 48.53384 -0.4000 11.02052
October 427.00000 23.13451 41.30781 0.17410 7.85014
November 417.00000 21.24991 33.55884 -0.3955 10.79944
December 422.00000 20.41888 26.18407 -0.6793 16.18546
           
Annual Sum or Average 5034.00000 22.54399 38.91411 -0.3542 11.67264
Minimum of Months 385.00000 20.00487 21.64626 -0.8066 7.01490
Maximum of Months 433.00000 24.58473 56.34461 0.17410 21.60935



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.89634 27.18009 -0.5540 16.30932
February 454.00000 21.55212 21.31054 -0.4072 12.74398
March 514.00000 22.20625 29.32219 -0.1536 8.52945
April 485.00000 22.87878 34.66464 0.05255 8.04455
May 508.00000 23.78597 42.13418 -0.5726 13.96789
June 496.00000 24.24047 52.55255 -0.2934 7.74997
July 497.00000 24.47610 56.67223 -0.1497 6.89371
August 514.00000 24.40313 51.85412 -0.1638 6.80498
September 485.00000 24.23197 47.90305 -0.2964 8.98841
October 502.00000 23.94047 39.80592 0.41965 10.83509
November 489.00000 22.31111 32.29554 -0.1145 8.80001
December 497.00000 21.59812 25.50888 -0.3666 11.68130
           
Annual Sum or Average 5943.00000 23.05473 38.56279 -0.2158 10.10092
Minimum of Months 454.00000 20.89634 21.31054 -0.5726 6.80498
Maximum of Months 514.00000 24.47610 56.67223 0.41965 16.30932



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.35456 27.46118 -0.7067 18.22263
February 454.00000 20.69439 21.93095 -0.6382 15.98798
March 514.00000 21.76519 29.76391 -0.2664 8.74652
April 485.00000 22.72593 34.76148 0.02971 7.91131
May 508.00000 23.79930 41.93165 -0.5255 13.23366
June 496.00000 24.32084 51.94771 -0.2043 7.28079
July 497.00000 24.53250 56.08122 -0.0814 6.94622
August 514.00000 24.43432 51.69111 -0.1212 6.67695
September 485.00000 24.02617 48.47920 -0.3872 10.22120
October 502.00000 23.30787 41.30438 0.23472 8.45873
November 489.00000 21.40625 33.61361 -0.3501 9.88193
December 497.00000 20.71938 26.21848 -0.5929 13.71313
           
Annual Sum or Average 5943.00000 22.68991 38.89011 -0.2985 10.56847
Minimum of Months 454.00000 20.35456 21.93095 -0.7067 6.67695
Maximum of Months 514.00000 24.53250 56.08122 0.23472 18.22263



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.84562 28.93174 -0.9097 25.53843
February 454.00000 19.94813 23.59798 -0.9133 25.15149
March 514.00000 20.62204 32.55118 -0.6196 15.30908
April 485.00000 21.68990 37.63319 -0.2794 10.16300
May 508.00000 23.29678 43.70464 -0.7693 20.26838
June 496.00000 24.15727 53.06966 -0.3331 8.25592
July 497.00000 24.44391 57.15662 -0.1724 6.86539
August 514.00000 24.28096 52.66718 -0.2717 7.52623
September 485.00000 23.66781 50.25862 -0.5813 14.27998
October 502.00000 22.20633 44.59808 -0.0830 9.28416
November 489.00000 20.45498 36.38701 -0.6427 16.64087
December 497.00000 19.92889 28.44604 -0.8729 23.67387
           
Annual Sum or Average 5943.00000 22.06254 40.87456 -0.5348 15.17728
Minimum of Months 454.00000 19.84562 23.59798 -0.9133 6.86539
Maximum of Months 514.00000 24.44391 57.15662 -0.0830 25.53843



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.89939 28.50018 -0.8735 24.31135
February 454.00000 20.11488 23.05743 -0.8349 22.15138
March 514.00000 20.98027 31.60446 -0.4989 13.26249
April 485.00000 22.24142 35.95377 -0.1150 9.39225
May 508.00000 23.52073 42.73735 -0.6190 17.65968
June 496.00000 24.22072 52.45766 -0.2478 7.81682
July 497.00000 24.50783 56.20650 -0.0827 7.15422
August 514.00000 24.36662 51.79468 -0.1463 6.85948
September 485.00000 23.88218 49.14728 -0.4416 12.34222
October 502.00000 22.72896 42.85848 0.07669 8.76333
November 489.00000 20.67145 35.53216 -0.5659 15.04880
December 497.00000 20.03130 27.90362 -0.8246 21.84657
           
Annual Sum or Average 5943.00000 22.28103 39.93586 -0.4283 13.82545
Minimum of Months 454.00000 19.89939 23.05743 -0.8735 6.85948
Maximum of Months 514.00000 24.50783 56.20650 0.07669 24.31135



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.45944 28.00972 -0.6973 20.54122
February 454.00000 20.90710 22.33026 -0.6007 17.49281
March 514.00000 21.57578 30.65385 -0.3352 11.92976
April 485.00000 22.29557 36.02292 -0.1021 9.74300
May 508.00000 23.43327 43.15087 -0.6881 18.74265
June 496.00000 24.17692 52.83667 -0.3017 8.28114
July 497.00000 24.47338 56.70721 -0.1298 7.01129
August 514.00000 24.38411 51.88193 -0.1529 6.94081
September 485.00000 24.05304 48.64230 -0.3534 10.83102
October 502.00000 23.48715 40.98864 0.29861 10.57238
November 489.00000 21.47675 34.17662 -0.3437 12.41425
December 497.00000 20.82240 27.07902 -0.5955 17.25942
           
Annual Sum or Average 5943.00000 22.64268 39.49906 -0.3319 12.61997
Minimum of Months 454.00000 20.45944 22.33026 -0.6973 6.94081
Maximum of Months 514.00000 24.47338 56.70721 0.29861 20.54122



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.04897 28.16270 -0.8216 22.50306
February 454.00000 20.31749 22.74631 -0.7714 20.47723
March 514.00000 21.25321 30.86449 -0.4176 11.81905
April 485.00000 22.19930 35.96542 -0.1085 9.43450
May 508.00000 23.46849 42.84480 -0.6319 17.48441
June 496.00000 24.25973 52.22271 -0.2117 7.75518
July 497.00000 24.52008 56.14021 -0.0650 7.13194
August 514.00000 24.41397 51.71253 -0.1117 6.80965
September 485.00000 23.81603 49.27202 -0.4529 12.47494
October 502.00000 22.76809 42.64456 0.09922 9.06355
November 489.00000 20.76413 35.17054 -0.5343 13.99867
December 497.00000 20.23541 27.43487 -0.7559 19.30424
           
Annual Sum or Average 5943.00000 22.35582 39.72062 -0.3958 13.13429
Minimum of Months 454.00000 20.04897 22.74631 -0.8216 6.80965
Maximum of Months 514.00000 24.52008 56.14021 0.09922 22.50306



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.810076E+09 4632.17 24-JAN-06:03 67.03 0.368948E+10 0.00 0.449955E+10 0.41 4.56 06-JAN-06:50 0.00 0.00
February 0.937033E+09 3768.46 17-FEB-09:30 77.32 0.426735E+10 0.00 0.520438E+10 0.52 4.56 09-FEB-21:20 0.00 0.00
March 0.241973E+10 80051.69 27-MAR-16:00 68.94 0.126289E+11 0.00 0.150486E+11 0.43 6.78 27-MAR-16:00 0.00 0.00
April 0.180848E+11 110015.78 07-APR-14:20 135.96 0.103834E+12 0.00 0.121919E+12 0.96 7.29 07-APR-15:30 0.00 0.00
May 0.596177E+11 131958.21 30-MAY-13:15 330.43 0.356517E+12 0.00 0.416134E+12 2.41 7.42 30-MAY-11:10 0.00 0.00
June 0.142394E+12 179170.27 17-JUN-05:04 528.25 0.944768E+12 0.00 0.108716E+13 4.57 7.77 13-JUN-05:04 0.00 0.00
July 0.180463E+12 199082.35 20-JUL-05:02 647.04 0.117370E+13 0.00 0.135416E+13 5.26 7.69 05-JUL-05:03 0.00 0.00
August 0.174883E+12 180098.04 01-AUG-05:03 679.10 0.113856E+13 0.00 0.131344E+13 5.43 7.73 07-AUG-05:04 0.00 0.00
September 0.108219E+12 192398.58 07-SEP-05:04 443.41 0.696628E+12 0.00 0.804847E+12 3.68 7.70 13-SEP-05:03 0.00 0.00
October 0.512151E+11 116939.11 05-OCT-13:10 254.47 0.318574E+12 0.00 0.369789E+12 1.93 7.54 06-OCT-05:04 0.00 0.00
November 0.297206E+10 57498.63 10-NOV-06:03 66.51 0.134455E+11 0.00 0.164175E+11 0.42 5.90 10-NOV-06:03 0.00 0.00
December 0.690872E+09 4167.26 15-DEC-11:20 56.22 0.314682E+10 0.00 0.383770E+10 0.34 4.56 21-DEC-08:00 0.00 0.00
                         
Annual Sum or Average 0.742707E+12     3354.68 0.476975E+13 0.00 0.551246E+13 2.21     0.00 0.00
Minimum of Months 0.690872E+09 3768.46   56.22 0.314682E+10 0.00 0.383770E+10 0.34 4.56   0.00 0.00
Maximum of Months 0.180463E+12 199082.35   679.10 0.117370E+13 0.00 0.135416E+13 5.43 7.77   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 0.00
April 0.365394E+09 107313.10 07-APR-14:40 1.00 0.261571E+10 0.00 0.298110E+10 0.01 7.28 07-APR-14:40 0.00 0.00
May 0.534167E+10 131958.21 30-MAY-13:15 13.75 0.380827E+11 0.00 0.434243E+11 0.13 7.42 30-MAY-11:10 0.00 0.00
June 0.390614E+11 179170.27 17-JUN-05:04 100.02 0.272999E+12 0.00 0.312061E+12 0.97 7.77 13-JUN-05:04 0.00 0.00
July 0.703233E+11 199082.35 20-JUL-05:02 174.07 0.478245E+12 0.00 0.548568E+12 1.59 7.69 05-JUL-05:03 0.00 0.00
August 0.690577E+11 180098.04 01-AUG-05:03 169.16 0.472707E+12 0.00 0.541764E+12 1.56 7.73 07-AUG-05:04 0.00 0.00
September 0.232071E+11 192398.58 07-SEP-05:04 59.48 0.161886E+12 0.00 0.185093E+12 0.58 7.70 13-SEP-05:03 0.00 0.00
October 0.713301E+10 116939.11 05-OCT-13:10 18.57 0.517096E+11 0.00 0.588426E+11 0.18 7.54 06-OCT-05:04 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.214490E+12     536.04 0.147824E+13 0.00 0.169273E+13 0.42     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.703233E+11 199082.35   174.07 0.478245E+12 0.00 0.548568E+12 1.59 7.77   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.100962E+11 744.00 8666.24 24-JAN-12:00 176742.47 20-JAN-16:20 21.53 18.33 14.10
February 0.141941E+11 672.00 16774.46 20-FEB-12:00 320279.96 20-FEB-16:30 24.39 18.33 14.10
March 0.479879E+11 744.00 49248.27 02-MAR-15:40 584211.57 31-MAR-24:00 27.51 18.41 14.10
April 0.962244E+11 720.00 49248.27 05-APR-10:40 664819.87 07-APR-17:20 31.56 19.48 14.10
May 0.851541E+11 744.00 49248.27 01-MAY-10:50 334515.31 31-MAY-23:40 23.51 19.69 14.10
June 0.127032E+12 720.00 49248.27 01-JUN-00:10 477885.10 30-JUN-24:00 31.83 24.77 14.10
July 0.131907E+12 744.00 49248.27 01-JUL-00:10 641338.07 31-JUL-24:00 39.78 29.51 14.10
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 703039.27 04-AUG-21:01 43.66 30.54 14.10
September 0.114586E+12 720.00 49248.27 01-SEP-00:03 319238.85 30-SEP-24:00 26.20 22.18 14.10
October 0.925861E+11 744.00 49248.27 02-OCT-08:15 450597.70 31-OCT-24:00 26.31 19.64 14.10
November 0.591886E+11 720.00 49248.27 01-NOV-14:00 480280.80 03-NOV-15:10 27.54 18.41 14.10
December 0.511062E+11 744.00 44729.82 17-DEC-15:00 598082.20 17-DEC-16:07 30.11 18.33 14.10
                   
Annual Sum or Average 0.961968E+12 8760.00         29.54 21.50 14.10
Minimum of Months 0.100962E+11 672.00 8666.24   176742.47   21.53 18.33 14.10
Maximum of Months 0.131907E+12 744.00 49248.27   703039.27   43.66 30.54 14.10



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 271881.48 04-JAN-09:00 20.94 20.93 1.00
February 0.00 0.00 0.00 01-FEB-00:10 271919.63 14-FEB-21:30 20.97 20.96 1.02
March 34647684.99 7.75 2268.21 27-MAR-16:00 634193.55 27-MAR-16:00 21.05 21.03 1.58
April 0.319977E+09 78.29 20605.46 07-APR-13:00 1233782.64 07-APR-14:40 21.20 21.03 10.09
May 0.259728E+10 251.13 20605.46 18-MAY-10:00 1259938.94 30-MAY-08:00 21.74 21.17 28.45
June 0.241197E+11 496.54 20605.46 01-JUN-09:40 1151950.12 22-JUN-09:40 23.83 22.30 50.40
July 0.442502E+11 644.88 20605.46 01-JUL-03:02 1254591.60 24-JUL-05:04 25.61 23.79 59.27
August 0.334766E+11 641.27 20605.46 01-AUG-00:03 1522181.08 30-AUG-14:20 24.76 22.94 60.96
September 0.128083E+11 400.34 20605.46 01-SEP-03:02 1165948.69 18-SEP-14:10 23.10 21.97 42.00
October 0.458784E+10 213.05 20605.46 02-OCT-13:00 1081645.18 05-OCT-11:00 21.76 21.24 22.61
November 10405156.34 15.03 781.35 10-NOV-08:00 336963.55 03-NOV-14:00 21.01 20.98 2.80
December 0.00 0.00 0.00 01-DEC-00:10 271868.23 13-DEC-07:50 20.94 20.93 0.79
                   
Annual Sum or Average 0.122205E+12 2748.29         22.25 21.61 23.57
Minimum of Months 0.00 0.00 0.00   271868.23   20.94 20.93 0.79
Maximum of Months 0.442502E+11 644.88 20605.46   1522181.08   25.61 23.79 60.96



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:01 0.00 01-JAN-00:01 20.94 20.94 0.00
February 0.00 0.00 0.00 01-FEB-00:10 0.00 01-FEB-00:10 20.97 20.97 0.00
March 0.00 0.00 0.00 01-MAR-00:10 0.00 01-MAR-00:10 21.05 21.05 0.00
April 74179650.24 1.00 20605.46 07-APR-13:30 1233782.64 07-APR-14:40 21.20 21.20 0.10
May 0.890156E+09 12.00 20605.46 30-MAY-08:00 1259938.94 30-MAY-08:00 21.74 21.69 1.13
June 0.780308E+10 105.19 20605.46 01-JUN-10:00 1151950.12 22-JUN-09:40 23.83 23.39 10.12
July 0.167443E+11 225.73 20605.46 01-JUL-05:04 1254591.60 24-JUL-05:04 25.61 24.71 19.72
August 0.146002E+11 199.79 20605.46 01-AUG-05:03 1440385.34 30-AUG-15:50 24.76 23.93 17.17
September 0.482621E+10 65.06 20605.46 01-SEP-05:03 1101244.52 01-SEP-14:00 23.10 22.83 6.30
October 0.132534E+10 17.87 20605.46 03-OCT-12:10 1081645.18 05-OCT-11:00 21.76 21.69 1.68
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.01 21.01 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.94 20.94 0.00
                   
Annual Sum or Average 0.462635E+11 626.63         22.25 22.04 4.73
Minimum of Months 0.00 0.00 0.00   0.00   20.94 20.94 0.00
Maximum of Months 0.167443E+11 225.73 20605.46   1440385.34   25.61 24.71 19.72



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.284193E+12 0.00 553.25 1833185.28 09-JAN-05:01 0.00 31.62 67.75 0.60 0.00 0.04 0.65 09-JAN-05:01
February 0.202509E+12 0.00 479.23 1699049.81 13-FEB-05:11 0.00 31.92 66.37 0.47 0.00 0.03 0.60 13-FEB-05:11
March 0.664779E+11 0.00 376.19 1253412.36 07-MAR-06:02 0.00 25.52 52.18 0.13 0.00 0.01 0.45 07-MAR-06:02
April 0.185320E+11 0.00 164.08 1181952.09 03-APR-05:01 0.00 24.90 37.40 0.03 0.00 0.00 0.42 03-APR-05:01
May 0.492059E+09 0.00 19.24 115315.28 30-MAY-14:10 0.00 24.20 25.63 0.00 0.00 0.00 0.04 30-MAY-14:10
June 0.132684E+10 0.00 13.89 140880.44 01-JUN-14:50 0.00 50.78 51.47 0.00 0.00 0.00 0.05 01-JUN-14:50
July 0.483977E+09 0.00 8.44 61771.96 11-JUL-16:20 0.00 46.03 46.37 0.00 0.00 0.00 0.02 11-JUL-16:20
August 0.205652E+10 0.00 23.08 104413.73 22-AUG-15:50 0.00 45.45 46.35 0.01 0.00 0.00 0.04 22-AUG-15:50
September 0.118703E+09 0.00 3.75 41833.98 01-SEP-17:20 0.00 43.36 43.54 0.00 0.00 0.00 0.01 01-SEP-17:20
October 0.242339E+10 0.00 68.34 548427.29 28-OCT-05:02 0.00 31.33 36.12 0.00 0.00 0.00 0.20 28-OCT-05:02
November 0.666224E+11 0.00 335.07 1285962.51 27-NOV-06:01 0.00 26.21 50.62 0.13 0.00 0.01 0.46 27-NOV-06:01
December 0.147002E+12 0.00 482.68 1271144.51 26-DEC-05:01 0.00 27.13 61.34 0.27 0.00 0.02 0.45 26-DEC-05:01
                           
Annual Sum or Average 0.792237E+12 0.00 2527.25     0.00 34.03 48.65 0.14 0.00 0.01    
Minimum of Months 0.118703E+09 0.00 3.75 41833.98   0.00 24.20 25.63 0.00 0.00 0.00 0.01  
Maximum of Months 0.284193E+12 0.00 553.25 1833185.28   0.00 50.78 67.75 0.60 0.00 0.04 0.65  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:01 0.00 21.53 21.53 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 24.39 24.39 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 27.51 27.51 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 31.56 31.56 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 23.51 23.51 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 31.83 31.83 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 39.78 39.78 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 43.66 43.66 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:03 0.00 26.20 26.20 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 26.31 26.31 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 27.54 27.54 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 30.11 30.11 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 29.54 29.54 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.53 21.53 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 43.66 43.66 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 18841006.08 0.00 36.58 18841006.08 0.00 0.00 0.00 0.00 4419.47 19-JAN-08:30 4419.47 19-JAN-08:30 0.00 0.00 0.00
February 16076007.78 0.00 35.24 16076007.78 0.00 0.00 0.00 0.00 2775.79 02-FEB-08:10 2775.79 02-FEB-08:10 0.00 0.00 0.00
March 0.114333E+10 0.00 36.31 0.110759E+10 0.00 0.00 0.00 0.00 64484.72 27-MAR-16:00 64484.72 27-MAR-16:00 0.00 0.00 0.00
April 0.119550E+11 0.00 114.26 0.119493E+11 0.00 0.00 0.00 0.00 116677.73 07-APR-15:00 116677.73 07-APR-15:00 0.00 0.00 0.00
May 0.354743E+11 0.00 314.96 0.316231E+11 0.00 0.00 0.00 0.00 173874.24 30-MAY-13:30 173874.24 30-MAY-13:30 0.00 0.00 0.00
June 0.120795E+12 0.00 515.69 0.986641E+11 0.00 0.00 0.00 0.00 209170.36 19-JUN-05:03 174706.23 22-JUN-15:03 0.00 0.00 0.00
July 0.166254E+12 0.00 612.75 0.138266E+12 0.00 0.00 0.00 0.00 218371.39 10-JUL-05:02 162495.21 12-JUL-11:00 0.00 0.00 0.00
August 0.170332E+12 0.00 650.69 0.150198E+12 0.00 0.00 0.00 0.00 217988.29 03-AUG-05:03 199747.65 22-AUG-15:05 0.00 0.00 0.00
September 0.797612E+11 0.00 425.54 0.683656E+11 0.00 0.00 0.00 0.00 211319.70 07-SEP-05:02 173281.93 01-SEP-13:50 0.00 0.00 0.00
October 0.378106E+11 0.00 244.80 0.284025E+11 0.00 0.00 0.00 0.00 153356.62 06-OCT-05:02 97163.23 04-OCT-15:00 0.00 0.00 0.00
November 0.110735E+10 0.00 37.64 0.101617E+10 0.00 0.00 0.00 0.00 59452.13 10-NOV-06:03 28266.42 03-NOV-14:00 0.00 0.00 0.00
December 11156552.39 0.00 21.58 11156552.39 0.00 0.00 0.00 0.00 4328.34 13-DEC-08:10 4328.34 13-DEC-08:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.624678E+12 0.00 3046.05 0.529638E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 11156552.39 0.00 21.58 11156552.39 0.00 0.00 0.00 0.00 2775.79   2775.79   0.00 0.00 0.00
Maximum of Months 0.170332E+12 0.00 650.69 0.150198E+12 0.00 0.00 0.00 0.00 218371.39   199747.65   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 50727843.69 0.00 35.14 50727843.69 0.00 0.00 0.00 0.00 7138.87 17-JAN-12:40 7138.87 17-JAN-12:40 0.00 0.00 0.00
February 4552358.87 0.00 49.64 4552358.87 0.00 0.00 0.00 0.00 243.98 28-FEB-14:20 243.98 28-FEB-14:20 0.00 0.00 0.00
March 0.652141E+10 0.00 35.25 0.649186E+10 0.00 0.00 0.00 0.00 393420.99 27-MAR-16:00 393420.99 27-MAR-16:00 0.00 0.00 0.00
April 0.786206E+11 0.00 98.85 0.786083E+11 0.00 0.00 0.00 0.00 974438.23 07-APR-14:20 974438.23 07-APR-14:20 0.00 0.00 0.00
May 0.298317E+12 0.00 306.40 0.266452E+12 0.00 0.00 0.00 0.00 1515081.45 30-MAY-10:40 1515081.45 30-MAY-10:40 0.00 0.00 0.00
June 0.100096E+13 0.00 453.37 0.792011E+12 0.00 0.00 0.00 0.00 2113855.96 19-JUN-05:03 1654306.99 01-JUN-15:10 0.00 0.00 0.00
July 0.132677E+13 0.00 484.64 0.103970E+13 0.00 0.00 0.00 0.00 2397433.49 21-JUL-03:02 1515823.80 11-JUL-14:25 0.00 0.00 0.00
August 0.129637E+13 0.00 490.75 0.110260E+13 0.00 0.00 0.00 0.00 2361522.35 04-AUG-03:02 1589152.03 22-AUG-14:25 0.00 0.00 0.00
September 0.690689E+12 0.00 401.58 0.580703E+12 0.00 0.00 0.00 0.00 2090670.53 07-SEP-05:02 1800057.64 01-SEP-14:15 0.00 0.00 0.00
October 0.294965E+12 0.00 234.72 0.220688E+12 0.00 0.00 0.00 0.00 1403688.23 06-OCT-05:02 839596.80 04-OCT-15:00 0.00 0.00 0.00
November 0.783271E+10 0.00 40.57 0.734693E+10 0.00 0.00 0.00 0.00 485257.63 10-NOV-06:03 194980.86 03-NOV-14:00 0.00 0.00 0.00
December 15505479.75 0.00 18.22 15505479.75 0.00 0.00 0.00 0.00 7041.37 13-DEC-10:00 7041.37 13-DEC-10:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.500112E+13 0.00 2649.14 0.409467E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 4552358.87 0.00 18.22 4552358.87 0.00 0.00 0.00 0.00 243.98   243.98   0.00 0.00 0.00
Maximum of Months 0.132677E+13 0.00 490.75 0.110260E+13 0.00 0.00 0.00 0.00 2397433.49   1800057.64   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 17100433.12 0.00 39.94 17100433.12 0.00 0.00 0.00 0.00 881.79 15-JAN-10:40 881.79 15-JAN-10:40 0.00 0.00 0.00
February 11946115.34 0.00 33.52 11946115.34 0.00 0.00 0.00 0.00 1062.38 09-FEB-04:42 1062.38 09-FEB-04:42 0.00 0.00 0.00
March 0.596599E+09 0.00 50.86 0.595262E+09 0.00 0.00 0.00 0.00 32239.90 27-MAR-16:00 32239.90 27-MAR-16:00 0.00 0.00 0.00
April 0.801909E+10 0.00 110.29 0.801801E+10 0.00 0.00 0.00 0.00 101937.01 07-APR-14:00 101937.01 07-APR-14:00 0.00 0.00 0.00
May 0.313793E+11 0.00 296.89 0.283432E+11 0.00 0.00 0.00 0.00 185343.32 30-MAY-13:40 185343.32 30-MAY-13:40 0.00 0.00 0.00
June 0.108731E+12 0.00 450.46 0.872937E+11 0.00 0.00 0.00 0.00 221180.58 19-JUN-05:03 178430.01 22-JUN-15:10 0.00 0.00 0.00
July 0.148916E+12 0.00 487.31 0.118319E+12 0.00 0.00 0.00 0.00 259562.49 22-JUL-03:02 164858.81 11-JUL-14:15 0.00 0.00 0.00
August 0.144224E+12 0.00 493.92 0.124012E+12 0.00 0.00 0.00 0.00 251658.13 04-AUG-03:02 209279.41 22-AUG-14:50 0.00 0.00 0.00
September 0.709912E+11 0.00 393.44 0.597165E+11 0.00 0.00 0.00 0.00 220235.66 07-SEP-05:02 177671.17 01-SEP-14:10 0.00 0.00 0.00
October 0.277737E+11 0.00 223.35 0.208934E+11 0.00 0.00 0.00 0.00 135916.00 06-OCT-05:02 96524.44 04-OCT-15:00 0.00 0.00 0.00
November 0.601500E+09 0.00 53.24 0.563271E+09 0.00 0.00 0.00 0.00 16145.86 03-NOV-14:00 16145.86 03-NOV-14:00 0.00 0.00 0.00
December 16443966.69 0.00 38.58 16443966.69 0.00 0.00 0.00 0.00 2566.65 25-DEC-08:55 2566.65 25-DEC-08:55 0.00 0.00 0.00
                               
Annual Sum or Average 0.541278E+12 0.00 2671.80 0.447800E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 11946115.34 0.00 33.52 11946115.34 0.00 0.00 0.00 0.00 881.79   881.79   0.00 0.00 0.00
Maximum of Months 0.148916E+12 0.00 493.92 0.124012E+12 0.00 0.00 0.00 0.00 259562.49   209279.41   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 6817986.26 0.00 0.25 3030633.84 0.00 0.00 0.00 0.00 33639.40 24-JAN-06:03 14724.61 24-JAN-06:03 0.00 0.00 0.00
February 55406.60 0.00 0.35 55406.60 0.00 0.00 0.00 0.00 66.02 11-FEB-09:40 66.02 11-FEB-09:40 0.00 0.00 0.00
March 0.583547E+09 0.00 7.44 0.583345E+09 0.00 0.00 0.00 0.00 40317.22 27-MAR-16:00 40317.22 27-MAR-16:00 0.00 0.00 0.00
April 0.529742E+10 0.00 68.11 0.527661E+10 0.00 0.00 0.00 0.00 64036.39 07-APR-13:50 64036.39 07-APR-13:50 0.00 0.00 0.00
May 0.156082E+11 0.00 184.75 0.148307E+11 0.00 0.00 0.00 0.00 95981.71 30-MAY-13:50 95981.71 30-MAY-13:50 0.00 0.00 0.00
June 0.662030E+11 0.00 389.38 0.545677E+11 0.00 0.00 0.00 0.00 148327.48 19-JUN-03:02 88087.74 12-JUN-03:02 0.00 0.00 0.00
July 0.958121E+11 0.00 410.10 0.741709E+11 0.00 0.00 0.00 0.00 146004.82 10-JUL-03:02 88070.85 12-JUL-03:02 0.00 0.00 0.00
August 0.964099E+11 0.00 444.70 0.796964E+11 0.00 0.00 0.00 0.00 137621.43 03-AUG-03:02 105247.17 13-AUG-15:48 0.00 0.00 0.00
September 0.500455E+11 0.00 338.97 0.432785E+11 0.00 0.00 0.00 0.00 130636.23 07-SEP-03:02 98538.06 01-SEP-14:00 0.00 0.00 0.00
October 0.191459E+11 0.00 181.15 0.158261E+11 0.00 0.00 0.00 0.00 101894.32 06-OCT-05:04 60581.29 04-OCT-13:00 0.00 0.00 0.00
November 0.140696E+09 0.00 6.42 0.129357E+09 0.00 0.00 0.00 0.00 57945.93 10-NOV-06:03 22991.59 10-NOV-06:03 0.00 0.00 0.00
December 11741.56 0.00 0.67 11741.56 0.00 0.00 0.00 0.00 16.20 30-DEC-14:50 16.20 30-DEC-14:50 0.00 0.00 0.00
                               
Annual Sum or Average 0.349253E+12 0.00 2032.30 0.288363E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 11741.56 0.00 0.25 11741.56 0.00 0.00 0.00 0.00 16.20   16.20   0.00 0.00 0.00
Maximum of Months 0.964099E+11 0.00 444.70 0.796964E+11 0.00 0.00 0.00 0.00 148327.48   105247.17   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.316612E+12 0.794855E+11 744.00 0.316485E+12 0.127274E+09 0.00 0.33 20-JAN-22:03 0.28 02-JAN-07:10 123808.53 20-JAN-22:03 123808.53 20-JAN-22:03 2524.82 24-JAN-15:20 31033.47 20-JAN-22:03 0.00
February 0.506080E+12 0.120902E+12 672.00 0.506080E+12 -0.0 0.00 0.55 21-FEB-22:03 0.51 06-FEB-07:05 215251.88 21-FEB-22:03 215251.88 21-FEB-22:03 0.00 12-FEB-17:15 51241.46 21-FEB-22:03 0.00
March 0.810809E+12 0.185577E+12 744.00 0.810603E+12 0.206335E+09 0.00 0.92 31-MAR-24:00 0.72 31-MAR-17:10 393346.31 31-MAR-24:00 393346.31 31-MAR-24:00 5536.34 27-MAR-14:55 88699.95 27-MAR-16:00 0.00
April 0.102580E+13 0.233198E+12 720.00 0.102539E+13 0.413586E+09 0.00 1.00 07-APR-11:40 0.36 30-APR-24:00 403559.36 27-APR-15:50 400844.88 07-APR-17:20 5595.91 27-APR-16:00 128313.93 07-APR-13:00 0.00
May 0.331621E+12 0.858120E+11 744.00 0.329084E+12 0.253745E+10 0.00 0.54 31-MAY-23:20 0.31 20-MAY-07:00 212637.67 31-MAY-24:00 211203.06 31-MAY-24:00 7360.07 19-MAY-15:00 55389.79 31-MAY-23:20 0.00
June 0.567339E+12 0.161615E+12 720.00 0.559347E+12 0.799257E+10 0.00 0.76 30-JUN-24:00 0.53 02-JUN-06:20 303183.36 30-JUN-24:00 302807.28 30-JUN-24:00 13261.44 15-JUN-14:00 96316.75 19-JUN-12:00 0.00
July 0.837339E+12 0.260251E+12 744.00 0.826238E+12 0.111017E+11 0.00 0.98 31-JUL-24:00 0.76 01-JUL-00:10 395119.84 31-JUL-23:57 395119.84 31-JUL-23:57 13742.72 20-JUL-15:00 124646.44 07-JUL-12:00 0.00
August 0.107599E+13 0.328715E+12 744.00 0.106841E+13 0.758046E+10 0.00 1.00 01-AUG-06:50 0.38 31-AUG-24:00 412547.07 18-AUG-19:00 405353.74 18-AUG-23:15 13691.41 03-AUG-16:10 147754.14 24-AUG-16:00 0.00
September 0.329990E+12 0.915860E+11 720.00 0.324406E+12 0.558389E+10 0.00 0.53 30-SEP-24:00 0.31 30-SEP-06:10 211563.91 30-SEP-24:00 211563.91 30-SEP-24:00 10757.63 07-SEP-15:00 50688.34 01-SEP-13:45 0.00
October 0.580454E+12 0.142098E+12 744.00 0.576521E+12 0.393300E+10 0.00 0.73 31-OCT-24:00 0.53 21-OCT-06:40 303266.01 31-OCT-24:00 303266.01 31-OCT-24:00 8394.54 06-OCT-09:30 69789.14 25-OCT-11:00 0.00
November 0.789920E+12 0.180137E+12 720.00 0.789535E+12 0.384728E+09 0.00 0.77 03-NOV-14:00 0.72 01-NOV-06:10 312108.26 10-NOV-10:30 308644.49 06-NOV-22:03 6514.91 10-NOV-08:55 78764.74 03-NOV-14:00 0.00
December 0.105746E+13 0.233462E+12 744.00 0.105746E+13 -0.0 0.00 0.95 29-DEC-22:02 0.92 04-DEC-17:10 400230.39 14-DEC-22:02 400230.39 14-DEC-22:02 0.00 09-DEC-02:70 88238.34 29-DEC-22:02 0.00
                                       
Annual Sum or Average 0.822941E+13 0.210284E+13 8760.00 0.818955E+13 0.398610E+11 0.00                         0.00
Minimum of Months 0.316612E+12 0.794855E+11 672.00 0.316485E+12 -0.0 0.00 0.33   0.28   123808.53   123808.53   0.00   31033.47   0.00
Maximum of Months 0.107599E+13 0.328715E+12 744.00 0.106841E+13 0.111017E+11 0.00 1.00   0.92   412547.07   405353.74   13742.72   147754.14   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.316061E+10 0.856909E+09 742.56 0.315541E+10 5200752.43 0.00 0.28 29-JAN-16:35 0.00 01-JAN-09:45 2147.11 29-JAN-16:35 2147.11 29-JAN-16:35 100.05 24-JAN-15:20 544.21 29-JAN-16:35 0.00
February 0.793589E+10 0.201398E+10 672.00 0.793589E+10 0.00 0.00 0.53 20-FEB-16:25 0.28 06-FEB-07:05 4209.56 20-FEB-16:25 4209.56 20-FEB-16:25 0.00 05-FEB-20:18 1030.10 20-FEB-16:25 0.00
March 0.149250E+11 0.347374E+10 744.00 0.149138E+11 11191680.16 0.00 0.82 31-MAR-24:00 0.58 01-MAR-07:05 7464.89 31-MAR-24:00 7464.89 31-MAR-24:00 216.96 27-MAR-14:50 1744.10 27-MAR-17:00 0.00
April 0.197704E+11 0.448305E+10 720.00 0.197483E+11 22070246.97 0.00 0.95 16-APR-17:13 0.31 30-APR-24:00 8611.00 09-APR-17:23 8600.75 23-APR-17:45 218.46 27-APR-16:00 2550.59 07-APR-17:00 0.00
May 0.564674E+10 0.145213E+10 744.00 0.554719E+10 99551586.46 0.00 0.48 31-MAY-23:30 0.19 04-MAY-07:00 4105.21 31-MAY-24:00 4052.12 31-MAY-24:00 286.23 18-MAY-15:30 1045.21 31-MAY-23:20 0.00
June 0.109641E+11 0.305994E+10 720.00 0.106400E+11 0.324140E+09 0.00 0.68 30-JUN-24:00 0.44 02-JUN-06:30 5890.06 30-JUN-24:00 5871.80 30-JUN-24:00 532.49 15-JUN-14:00 1923.45 19-JUN-12:10 0.00
July 0.166377E+11 0.505883E+10 744.00 0.161583E+11 0.479417E+09 0.00 0.89 31-JUL-24:00 0.68 01-JUL-06:10 7751.52 31-JUL-23:57 7751.52 31-JUL-23:57 606.92 20-JUL-15:00 2485.80 07-JUL-12:10 0.00
August 0.216639E+11 0.655661E+10 744.00 0.212921E+11 0.371739E+09 0.00 1.00 01-AUG-12:10 0.32 31-AUG-24:00 8840.82 31-AUG-17:50 8524.74 13-AUG-18:12 612.70 03-AUG-15:00 3125.19 24-AUG-16:00 0.00
September 0.583540E+10 0.159879E+10 720.00 0.562444E+10 0.210960E+09 0.00 0.46 30-SEP-24:00 0.20 30-SEP-07:00 3943.19 30-SEP-24:00 3943.19 30-SEP-24:00 445.26 07-SEP-15:00 990.30 14-SEP-14:00 0.00
October 0.107610E+11 0.263014E+10 744.00 0.106068E+11 0.154151E+09 0.00 0.63 31-OCT-24:00 0.41 28-OCT-06:55 5667.09 31-OCT-24:00 5665.49 31-OCT-24:00 340.98 05-OCT-16:00 1363.66 04-OCT-16:00 0.00
November 0.144972E+11 0.333604E+10 720.00 0.144789E+11 18273082.94 0.00 0.72 23-NOV-15:55 0.59 21-NOV-07:10 6142.42 03-NOV-16:00 6142.42 03-NOV-16:00 258.12 10-NOV-08:55 1501.74 03-NOV-14:00 0.00
December 0.196917E+11 0.450548E+10 744.00 0.196917E+11 -0.0 0.00 0.94 03-DEC-15:43 0.79 30-DEC-08:00 8036.54 25-DEC-16:10 8036.54 25-DEC-16:10 0.00 01-DEC-20:30 1842.65 03-DEC-15:43 0.00
                                       
Annual Sum or Average 0.151490E+12 0.390256E+11 8758.56 0.149793E+12 0.169669E+10 0.00                         0.00
Minimum of Months 0.316061E+10 0.856909E+09 672.00 0.315541E+10 -0.0 0.00 0.28   0.00   2147.11   2147.11   0.00   544.21   0.00
Maximum of Months 0.216639E+11 0.655661E+10 744.00 0.212921E+11 0.479417E+09 0.00 1.00   0.79   8840.82   8600.75   612.70   3125.19   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.781669E+10 0.231994E+10 481.50 0.777888E+10 37808153.02 0.00 0.23 20-JAN-16:30 0.00 01-JAN-00:01 16519.59 20-JAN-16:30 16519.59 20-JAN-16:30 824.58 24-JAN-15:20 4307.64 20-JAN-16:30 0.00
February 0.529047E+11 0.138335E+11 672.00 0.529047E+11 -0.0 0.00 0.48 02-FEB-16:50 0.10 06-FEB-07:05 35982.61 22-FEB-17:00 35982.61 22-FEB-17:00 0.00 01-FEB-13:20 8965.85 02-FEB-16:50 0.00
March 0.124645E+12 0.294524E+11 744.00 0.124533E+12 0.112781E+09 0.00 0.75 31-MAR-23:50 0.47 01-MAR-07:05 65138.24 31-MAR-23:50 65138.24 31-MAR-23:50 2150.82 27-MAR-14:50 16234.17 27-MAR-17:00 0.00
April 0.177787E+12 0.406914E+11 720.00 0.177563E+12 0.223595E+09 0.00 0.94 07-APR-16:00 0.21 30-APR-24:00 80207.72 09-APR-17:23 80022.84 09-APR-17:27 2167.88 27-APR-16:00 24240.52 07-APR-17:00 0.00
May 0.485466E+11 0.126196E+11 744.00 0.475759E+11 0.970669E+09 0.00 0.48 31-MAY-23:40 0.14 01-MAY-06:05 39103.47 31-MAY-24:00 38559.15 31-MAY-24:00 2820.27 18-MAY-15:30 9955.56 31-MAY-23:20 0.00
June 0.103151E+12 0.288533E+11 720.00 0.999335E+11 0.321771E+10 0.00 0.67 30-JUN-24:00 0.42 03-JUN-07:00 55578.33 30-JUN-24:00 55393.76 30-JUN-24:00 5283.43 15-JUN-14:00 18385.15 19-JUN-12:10 0.00
July 0.158782E+12 0.482828E+11 744.00 0.154003E+12 0.477982E+10 0.00 0.90 31-JUL-24:00 0.67 01-JUL-06:10 74729.25 31-JUL-23:57 74729.25 31-JUL-23:57 6049.36 20-JUL-15:00 23802.77 07-JUL-12:10 0.00
August 0.206384E+12 0.624876E+11 744.00 0.202665E+12 0.371818E+10 0.00 1.00 01-AUG-12:10 0.29 31-AUG-24:00 84451.84 31-AUG-17:40 80940.40 15-AUG-18:00 6126.07 03-AUG-15:00 29865.46 24-AUG-16:00 0.00
September 0.517526E+11 0.143027E+11 720.00 0.496863E+11 0.206630E+10 0.00 0.44 30-SEP-23:40 0.16 30-SEP-07:00 35786.41 30-SEP-23:40 35786.41 30-SEP-23:40 4412.54 07-SEP-15:00 9397.26 14-SEP-14:00 0.00
October 0.944614E+11 0.232982E+11 744.00 0.929407E+11 0.152072E+10 0.00 0.58 31-OCT-24:00 0.34 28-OCT-06:55 49116.36 31-OCT-24:00 49092.17 31-OCT-24:00 3386.98 24-OCT-16:00 12930.56 04-OCT-16:00 0.00
November 0.118746E+12 0.277698E+11 720.00 0.118564E+12 0.181816E+09 0.00 0.69 02-NOV-15:40 0.44 24-NOV-07:10 57451.97 03-NOV-16:00 57451.97 03-NOV-16:00 2552.63 10-NOV-10:30 14031.70 03-NOV-14:00 0.00
December 0.161803E+12 0.377734E+11 744.00 0.161803E+12 -0.0 0.00 0.87 21-DEC-16:10 0.60 31-DEC-23:53 71210.37 08-DEC-16:10 71210.37 08-DEC-16:10 0.00 07-DEC-02:25 16270.51 21-DEC-16:10 0.00
                                       
Annual Sum or Average 0.130678E+13 0.341685E+12 8497.50 0.128995E+13 0.168294E+11 0.00                         0.00
Minimum of Months 0.781669E+10 0.231994E+10 481.50 0.777888E+10 -0.0 0.00 0.23   0.00   16519.59   16519.59   0.00   4307.64   0.00
Maximum of Months 0.206384E+12 0.624876E+11 744.00 0.202665E+12 0.477982E+10 0.00 1.00   0.67   84451.84   80940.40   6126.07   29865.46   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.280669E+09 85111568.41 199.47 0.277886E+09 2783332.87 0.00 0.21 19-JAN-16:30 0.00 01-JAN-00:01 1578.37 19-JAN-16:20 1578.37 19-JAN-16:20 73.24 24-JAN-15:20 407.88 19-JAN-16:20 0.00
February 0.373381E+10 0.999694E+09 653.77 0.373381E+10 0.00 0.00 0.46 02-FEB-16:50 0.00 05-FEB-03:02 3477.88 17-FEB-17:00 3477.88 17-FEB-17:00 0.00 28-FEB-18:10 871.69 02-FEB-16:50 0.00
March 0.110449E+11 0.264475E+10 744.00 0.110339E+11 11012180.08 0.00 0.71 27-MAR-17:00 0.34 13-MAR-03:17 5944.52 31-MAR-23:20 5944.52 31-MAR-23:20 215.56 27-MAR-14:50 1616.62 27-MAR-17:00 0.00
April 0.168449E+11 0.389446E+10 720.00 0.168228E+11 22152140.63 0.00 0.94 07-APR-16:00 0.12 30-APR-24:00 8100.14 09-APR-17:23 8081.60 09-APR-17:27 217.01 27-APR-16:00 2457.28 07-APR-17:00 0.00
May 0.449874E+10 0.118277E+10 743.75 0.440322E+10 95517455.85 0.00 0.47 31-MAY-23:30 0.00 01-MAY-03:55 3891.39 31-MAY-24:00 3836.43 31-MAY-24:00 282.64 18-MAY-15:30 993.44 31-MAY-23:20 0.00
June 0.103334E+11 0.289886E+10 720.00 0.100117E+11 0.321703E+09 0.00 0.65 30-JUN-24:00 0.38 03-JUN-06:50 5484.75 30-JUN-24:00 5465.88 30-JUN-24:00 530.62 15-JUN-14:00 1880.90 19-JUN-12:10 0.00
July 0.160051E+11 0.487496E+10 744.00 0.155271E+11 0.477926E+09 0.00 0.89 31-JUL-24:00 0.65 01-JUL-06:10 7486.24 31-JUL-23:57 7486.24 31-JUL-23:57 606.12 20-JUL-15:00 2415.06 07-JUL-12:10 0.00
August 0.207263E+11 0.629227E+10 744.00 0.203545E+11 0.371829E+09 0.00 1.00 01-AUG-12:30 0.28 31-AUG-24:00 8582.06 31-AUG-17:10 8266.25 13-AUG-17:42 614.27 03-AUG-15:00 3042.28 24-AUG-16:00 0.00
September 0.496566E+10 0.138439E+10 720.00 0.475987E+10 0.205787E+09 0.00 0.41 30-SEP-23:20 0.11 24-SEP-06:50 3322.70 30-SEP-23:20 3322.70 30-SEP-23:20 444.83 07-SEP-15:00 968.97 14-SEP-14:00 0.00
October 0.860050E+10 0.214371E+10 744.00 0.844951E+10 0.150984E+09 0.00 0.56 04-OCT-16:00 0.24 29-OCT-07:30 4660.74 04-OCT-16:00 4392.60 31-OCT-23:30 338.64 24-OCT-16:00 1313.93 04-OCT-16:00 0.00
November 0.102506E+11 0.243326E+10 720.00 0.102327E+11 17906902.45 0.00 0.68 02-NOV-15:30 0.28 24-NOV-04:03 5719.09 03-NOV-16:00 5719.09 03-NOV-16:00 254.97 10-NOV-10:30 1390.43 03-NOV-14:10 0.00
December 0.142322E+11 0.337935E+10 744.00 0.142322E+11 -0.0 0.00 0.83 21-DEC-16:00 0.45 31-DEC-23:55 6920.97 08-DEC-16:10 6920.97 08-DEC-16:10 0.00 26-DEC-04:55 1582.46 21-DEC-16:00 0.00
                                       
Annual Sum or Average 0.121517E+12 0.322136E+11 8196.99 0.119839E+12 0.167760E+10 0.00                         0.00
Minimum of Months 0.280669E+09 85111568.41 199.47 0.277886E+09 -0.0 0.00 0.21   0.00   1578.37   1578.37   0.00   407.88   0.00
Maximum of Months 0.207263E+11 0.629227E+10 744.00 0.203545E+11 0.477926E+09 0.00 1.00   0.65   8582.06   8266.25   614.27   3042.28   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.62 0.00 87.62 1.90 559.19 0.00 0.00 0.00
February 119.91 0.00 119.91 6.48 578.59 0.00 0.00 0.00
March 166.28 0.00 166.28 46.29 399.23 0.00 0.00 0.00
April 199.73 0.57 199.16 111.82 284.60 0.00 0.00 0.00
May 264.98 8.83 256.15 241.87 163.72 0.00 0.00 0.00
June 281.00 15.10 265.91 347.98 86.93 0.00 0.00 0.00
July 271.56 9.82 261.74 389.46 46.26 0.00 0.00 0.00
August 240.59 2.86 237.73 339.33 63.83 0.00 0.00 0.00
September 181.37 0.03 181.33 191.55 136.55 0.00 0.00 0.00
October 156.96 0.00 156.96 107.03 257.39 0.00 0.00 0.00
November 110.09 0.00 110.09 21.32 417.25 0.00 0.00 0.00
December 76.43 0.00 76.43 0.88 548.03 0.00 0.00 0.00
                 
Annual Sum or Average 180.06 3.12 176.94 151.48 293.50 0.00 0.00 0.00
Minimum of Months 76.43 0.00 76.43 0.88 46.26 0.00 0.00 0.00
Maximum of Months 281.00 15.10 265.91 389.46 578.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.62 0.00 87.62 1.90 559.19 0.00 0.00 0.00
February 119.91 0.00 119.91 6.48 578.59 0.00 0.00 0.00
March 166.28 0.00 166.28 46.29 399.23 0.00 0.00 0.00
April 199.73 0.57 199.16 111.81 284.60 0.00 0.00 0.00
May 264.97 8.83 256.14 241.86 163.72 0.00 0.00 0.00
June 281.00 15.10 265.90 347.97 86.93 0.00 0.00 0.00
July 271.56 9.82 261.74 389.46 46.26 0.00 0.00 0.00
August 240.59 2.86 237.73 339.32 63.83 0.00 0.00 0.00
September 181.36 0.03 181.33 191.55 136.55 0.00 0.00 0.00
October 156.96 0.00 156.96 107.03 257.39 0.00 0.00 0.00
November 110.09 0.00 110.09 21.32 417.25 0.00 0.00 0.00
December 76.43 0.00 76.43 0.88 548.03 0.00 0.00 0.00
                 
Annual Sum or Average 180.05 3.12 176.94 151.48 293.50 0.00 0.00 0.00
Minimum of Months 76.43 0.00 76.43 0.88 46.26 0.00 0.00 0.00
Maximum of Months 281.00 15.10 265.90 389.46 578.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.62 0.00 87.62 1.90 559.19 0.00 0.00 0.00
February 119.91 0.00 119.91 6.48 578.59 0.00 0.00 0.00
March 166.28 0.00 166.28 46.29 399.23 0.00 0.00 0.00
April 199.73 0.57 199.16 111.82 284.60 0.00 0.00 0.00
May 264.97 8.83 256.15 241.86 163.72 0.00 0.00 0.00
June 281.00 15.10 265.90 347.97 86.93 0.00 0.00 0.00
July 271.56 9.82 261.74 389.46 46.26 0.00 0.00 0.00
August 240.59 2.86 237.73 339.33 63.83 0.00 0.00 0.00
September 181.37 0.03 181.33 191.55 136.55 0.00 0.00 0.00
October 156.96 0.00 156.96 107.03 257.39 0.00 0.00 0.00
November 110.09 0.00 110.09 21.32 417.25 0.00 0.00 0.00
December 76.43 0.00 76.43 0.88 548.03 0.00 0.00 0.00
                 
Annual Sum or Average 180.05 3.12 176.94 151.48 293.50 0.00 0.00 0.00
Minimum of Months 76.43 0.00 76.43 0.88 46.26 0.00 0.00 0.00
Maximum of Months 281.00 15.10 265.90 389.46 578.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.62 0.00 87.62 1.90 559.19 0.00 0.00 0.00
February 119.91 0.00 119.91 6.48 578.59 0.00 0.00 0.00
March 166.28 0.00 166.28 46.29 399.23 0.00 0.00 0.00
April 199.73 0.57 199.16 111.81 284.60 0.00 0.00 0.00
May 264.97 8.83 256.14 241.86 163.72 0.00 0.00 0.00
June 281.00 15.10 265.90 347.97 86.93 0.00 0.00 0.00
July 271.56 9.82 261.74 389.46 46.26 0.00 0.00 0.00
August 240.59 2.86 237.73 339.32 63.83 0.00 0.00 0.00
September 181.36 0.03 181.33 191.55 136.55 0.00 0.00 0.00
October 156.96 0.00 156.96 107.03 257.39 0.00 0.00 0.00
November 110.09 0.00 110.09 21.32 417.25 0.00 0.00 0.00
December 76.43 0.00 76.43 0.88 548.03 0.00 0.00 0.00
                 
Annual Sum or Average 180.05 3.12 176.94 151.48 293.50 0.00 0.00 0.00
Minimum of Months 76.43 0.00 76.43 0.88 46.26 0.00 0.00 0.00
Maximum of Months 281.00 15.10 265.90 389.46 578.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 87.62 0.00 87.62 1.90 559.17 0.00 0.00 0.00
February 119.90 0.00 119.90 6.48 578.57 0.00 0.00 0.00
March 166.27 0.00 166.27 46.29 399.21 0.00 0.00 0.00
April 199.72 0.57 199.15 111.81 284.59 0.00 0.00 0.00
May 264.96 8.83 256.13 241.85 163.72 0.00 0.00 0.00
June 280.99 15.10 265.89 347.96 86.93 0.00 0.00 0.00
July 271.55 9.82 261.73 389.44 46.26 0.00 0.00 0.00
August 240.58 2.86 237.72 339.31 63.83 0.00 0.00 0.00
September 181.36 0.03 181.32 191.54 136.55 0.00 0.00 0.00
October 156.95 0.00 156.95 107.03 257.38 0.00 0.00 0.00
November 110.09 0.00 110.09 21.31 417.23 0.00 0.00 0.00
December 76.43 0.00 76.43 0.88 548.01 0.00 0.00 0.00
                 
Annual Sum or Average 180.05 3.12 176.93 151.47 293.49 0.00 0.00 0.00
Minimum of Months 76.43 0.00 76.43 0.88 46.26 0.00 0.00 0.00
Maximum of Months 280.99 15.10 265.89 389.44 578.57 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 203.37 81.54 121.84 116.22 571.95 0.00 0.00 0.00
February 315.39 147.13 168.26 209.03 571.71 0.00 0.00 0.00
March 402.34 171.12 231.22 340.01 414.24 0.00 0.00 0.00
April 482.83 211.50 271.34 480.67 292.54 0.00 0.00 0.00
May 585.58 234.03 351.54 677.26 182.63 0.00 0.00 0.00
June 542.70 196.46 346.25 714.80 95.28 0.00 0.00 0.00
July 545.08 196.71 348.37 782.17 47.33 0.00 0.00 0.00
August 613.77 276.75 337.02 874.97 65.10 0.00 0.00 0.00
September 457.76 205.38 252.38 572.79 144.27 0.00 0.00 0.00
October 414.99 188.09 226.90 455.71 270.39 0.00 0.00 0.00
November 256.64 98.55 158.09 193.39 420.24 0.00 0.00 0.00
December 199.94 93.88 106.06 125.43 542.35 0.00 0.00 0.00
                 
Annual Sum or Average 419.03 175.29 243.74 463.64 299.98 0.00 0.00 0.00
Minimum of Months 199.94 81.54 106.06 116.22 47.33 0.00 0.00 0.00
Maximum of Months 613.77 276.75 351.54 874.97 571.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 203.37 81.54 121.84 116.22 571.95 0.00 0.00 0.00
February 315.39 147.13 168.26 209.03 571.71 0.00 0.00 0.00
March 402.34 171.12 231.22 340.01 414.24 0.00 0.00 0.00
April 482.83 211.50 271.34 480.67 292.54 0.00 0.00 0.00
May 585.58 234.03 351.54 677.26 182.63 0.00 0.00 0.00
June 542.70 196.46 346.25 714.80 95.28 0.00 0.00 0.00
July 545.08 196.71 348.37 782.17 47.33 0.00 0.00 0.00
August 613.77 276.75 337.02 874.97 65.10 0.00 0.00 0.00
September 457.76 205.38 252.38 572.79 144.27 0.00 0.00 0.00
October 414.99 188.09 226.90 455.71 270.39 0.00 0.00 0.00
November 256.64 98.55 158.09 193.39 420.24 0.00 0.00 0.00
December 199.94 93.88 106.06 125.43 542.35 0.00 0.00 0.00
                 
Annual Sum or Average 419.03 175.29 243.74 463.64 299.98 0.00 0.00 0.00
Minimum of Months 199.94 81.54 106.06 116.22 47.33 0.00 0.00 0.00
Maximum of Months 613.77 276.75 351.54 874.97 571.95 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 203.37 81.54 121.84 116.22 571.94 0.00 0.00 0.00
February 315.38 147.13 168.26 209.03 571.70 0.00 0.00 0.00
March 402.33 171.11 231.22 340.01 414.23 0.00 0.00 0.00
April 482.82 211.49 271.33 480.67 292.54 0.00 0.00 0.00
May 585.57 234.03 351.54 677.25 182.63 0.00 0.00 0.00
June 542.69 196.45 346.24 714.78 95.28 0.00 0.00 0.00
July 545.07 196.70 348.37 782.15 47.33 0.00 0.00 0.00
August 613.76 276.75 337.02 874.96 65.09 0.00 0.00 0.00
September 457.75 205.37 252.37 572.78 144.27 0.00 0.00 0.00
October 414.98 188.08 226.90 455.71 270.38 0.00 0.00 0.00
November 256.63 98.55 158.08 193.39 420.23 0.00 0.00 0.00
December 199.93 93.88 106.06 125.43 542.34 0.00 0.00 0.00
                 
Annual Sum or Average 419.02 175.29 243.73 463.63 299.97 0.00 0.00 0.00
Minimum of Months 199.93 81.54 106.06 116.22 47.33 0.00 0.00 0.00
Maximum of Months 613.76 276.75 351.54 874.96 571.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 453.29 296.81 156.47 439.66 480.75 0.00 0.00 0.00
February 597.87 395.74 202.13 590.48 487.36 0.00 0.00 0.00
March 539.39 299.37 240.02 566.10 370.27 0.00 0.00 0.00
April 418.55 165.51 253.04 452.57 280.25 0.00 0.00 0.00
May 366.80 76.51 290.29 425.24 173.56 0.00 0.00 0.00
June 344.23 52.62 291.61 465.56 93.10 0.00 0.00 0.00
July 360.82 62.67 298.15 543.67 48.30 0.00 0.00 0.00
August 481.84 178.72 303.12 730.75 68.95 0.00 0.00 0.00
September 522.80 270.41 252.39 700.63 138.94 0.00 0.00 0.00
October 716.19 449.10 267.09 891.45 250.85 0.00 0.00 0.00
November 496.62 298.24 198.38 521.21 367.53 0.00 0.00 0.00
December 491.29 348.79 142.51 495.30 457.08 0.00 0.00 0.00
                 
Annual Sum or Average 481.93 240.43 241.50 568.74 266.80 0.00 0.00 0.00
Minimum of Months 344.23 52.62 142.51 425.24 48.30 0.00 0.00 0.00
Maximum of Months 716.19 449.10 303.12 891.45 487.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 453.28 296.81 156.47 439.66 480.75 0.00 0.00 0.00
February 597.86 395.74 202.13 590.48 487.36 0.00 0.00 0.00
March 539.39 299.37 240.02 566.09 370.27 0.00 0.00 0.00
April 418.55 165.50 253.04 452.57 280.25 0.00 0.00 0.00
May 366.80 76.51 290.29 425.23 173.56 0.00 0.00 0.00
June 344.23 52.62 291.61 465.55 93.10 0.00 0.00 0.00
July 360.82 62.67 298.15 543.66 48.29 0.00 0.00 0.00
August 481.83 178.72 303.11 730.75 68.95 0.00 0.00 0.00
September 522.80 270.41 252.39 700.63 138.94 0.00 0.00 0.00
October 716.19 449.10 267.09 891.45 250.85 0.00 0.00 0.00
November 496.61 298.24 198.37 521.20 367.53 0.00 0.00 0.00
December 491.29 348.78 142.51 495.29 457.08 0.00 0.00 0.00
                 
Annual Sum or Average 481.93 240.42 241.50 568.73 266.80 0.00 0.00 0.00
Minimum of Months 344.23 52.62 142.51 425.23 48.29 0.00 0.00 0.00
Maximum of Months 716.19 449.10 303.11 891.45 487.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 453.29 296.81 156.47 439.66 480.75 0.00 0.00 0.00
February 597.87 395.74 202.13 590.48 487.36 0.00 0.00 0.00
March 539.39 299.37 240.02 566.10 370.27 0.00 0.00 0.00
April 418.55 165.51 253.04 452.57 280.25 0.00 0.00 0.00
May 366.80 76.51 290.29 425.24 173.56 0.00 0.00 0.00
June 344.23 52.62 291.61 465.56 93.10 0.00 0.00 0.00
July 360.82 62.67 298.15 543.67 48.30 0.00 0.00 0.00
August 481.84 178.72 303.12 730.75 68.95 0.00 0.00 0.00
September 522.80 270.41 252.39 700.63 138.94 0.00 0.00 0.00
October 716.19 449.10 267.09 891.45 250.85 0.00 0.00 0.00
November 496.62 298.24 198.38 521.21 367.53 0.00 0.00 0.00
December 491.29 348.79 142.51 495.30 457.08 0.00 0.00 0.00
                 
Annual Sum or Average 481.93 240.43 241.50 568.74 266.80 0.00 0.00 0.00
Minimum of Months 344.23 52.62 142.51 425.24 48.30 0.00 0.00 0.00
Maximum of Months 716.19 449.10 303.12 891.45 487.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 453.28 296.81 156.47 439.66 480.75 0.00 0.00 0.00
February 597.86 395.74 202.13 590.48 487.36 0.00 0.00 0.00
March 539.39 299.37 240.02 566.09 370.27 0.00 0.00 0.00
April 418.55 165.50 253.04 452.57 280.25 0.00 0.00 0.00
May 366.80 76.51 290.29 425.23 173.56 0.00 0.00 0.00
June 344.23 52.62 291.61 465.55 93.10 0.00 0.00 0.00
July 360.82 62.67 298.15 543.66 48.29 0.00 0.00 0.00
August 481.83 178.72 303.11 730.75 68.95 0.00 0.00 0.00
September 522.80 270.41 252.39 700.63 138.94 0.00 0.00 0.00
October 716.19 449.10 267.09 891.45 250.85 0.00 0.00 0.00
November 496.61 298.24 198.37 521.20 367.53 0.00 0.00 0.00
December 491.29 348.78 142.51 495.29 457.08 0.00 0.00 0.00
                 
Annual Sum or Average 481.93 240.42 241.50 568.73 266.80 0.00 0.00 0.00
Minimum of Months 344.23 52.62 142.51 425.23 48.29 0.00 0.00 0.00
Maximum of Months 716.19 449.10 303.11 891.45 487.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 453.27 296.80 156.47 439.64 480.73 0.00 0.00 0.00
February 597.84 395.72 202.12 590.46 487.34 0.00 0.00 0.00
March 539.37 299.36 240.01 566.07 370.26 0.00 0.00 0.00
April 418.53 165.50 253.03 452.55 280.24 0.00 0.00 0.00
May 366.78 76.50 290.28 425.22 173.56 0.00 0.00 0.00
June 344.21 52.62 291.60 465.53 93.09 0.00 0.00 0.00
July 360.81 62.67 298.13 543.64 48.29 0.00 0.00 0.00
August 481.81 178.71 303.10 730.72 68.95 0.00 0.00 0.00
September 522.78 270.40 252.38 700.60 138.94 0.00 0.00 0.00
October 716.16 449.08 267.08 891.41 250.84 0.00 0.00 0.00
November 496.59 298.23 198.37 521.18 367.51 0.00 0.00 0.00
December 491.27 348.77 142.50 495.28 457.06 0.00 0.00 0.00
                 
Annual Sum or Average 481.91 240.41 241.49 568.71 266.79 0.00 0.00 0.00
Minimum of Months 344.21 52.62 142.50 425.22 48.29 0.00 0.00 0.00
Maximum of Months 716.16 449.08 303.10 891.41 487.34 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 200.78 82.24 118.54 114.07 616.37 0.00 0.00 0.00
February 296.07 130.04 166.04 188.24 641.94 0.00 0.00 0.00
March 437.19 201.84 235.35 370.03 466.25 0.00 0.00 0.00
April 477.82 204.45 273.38 462.32 355.75 0.00 0.00 0.00
May 556.62 211.38 345.24 636.17 206.67 0.00 0.00 0.00
June 609.20 245.71 363.49 794.96 120.11 0.00 0.00 0.00
July 570.55 214.85 355.70 799.53 71.90 0.00 0.00 0.00
August 631.18 292.20 338.99 883.60 98.95 0.00 0.00 0.00
September 448.09 195.81 252.28 559.13 168.47 0.00 0.00 0.00
October 444.25 216.03 228.22 487.46 310.34 0.00 0.00 0.00
November 208.62 60.29 148.33 121.42 491.52 0.00 0.00 0.00
December 185.56 80.29 105.27 101.30 639.17 0.00 0.00 0.00
                 
Annual Sum or Average 423.05 178.34 244.71 461.82 347.26 0.00 0.00 0.00
Minimum of Months 185.56 60.29 105.27 101.30 71.90 0.00 0.00 0.00
Maximum of Months 631.18 292.20 363.49 883.60 641.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 200.78 82.24 118.54 114.07 616.37 0.00 0.00 0.00
February 296.07 130.04 166.04 188.24 641.94 0.00 0.00 0.00
March 437.19 201.84 235.35 370.03 466.25 0.00 0.00 0.00
April 477.82 204.45 273.38 462.32 355.75 0.00 0.00 0.00
May 556.62 211.38 345.24 636.17 206.67 0.00 0.00 0.00
June 609.20 245.71 363.49 794.96 120.11 0.00 0.00 0.00
July 570.55 214.85 355.70 799.53 71.90 0.00 0.00 0.00
August 631.18 292.20 338.99 883.60 98.95 0.00 0.00 0.00
September 448.09 195.81 252.28 559.13 168.47 0.00 0.00 0.00
October 444.25 216.03 228.22 487.46 310.34 0.00 0.00 0.00
November 208.62 60.29 148.33 121.42 491.52 0.00 0.00 0.00
December 185.56 80.29 105.27 101.30 639.17 0.00 0.00 0.00
                 
Annual Sum or Average 423.05 178.34 244.71 461.82 347.26 0.00 0.00 0.00
Minimum of Months 185.56 60.29 105.27 101.30 71.90 0.00 0.00 0.00
Maximum of Months 631.18 292.20 363.49 883.60 641.94 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 200.77 82.24 118.53 114.07 616.35 0.00 0.00 0.00
February 296.07 130.03 166.03 188.24 641.93 0.00 0.00 0.00
March 437.18 201.83 235.35 370.03 466.24 0.00 0.00 0.00
April 477.82 204.45 273.37 462.31 355.74 0.00 0.00 0.00
May 556.61 211.38 345.23 636.15 206.66 0.00 0.00 0.00
June 609.19 245.70 363.49 794.95 120.11 0.00 0.00 0.00
July 570.54 214.85 355.69 799.51 71.90 0.00 0.00 0.00
August 631.17 292.19 338.98 883.59 98.95 0.00 0.00 0.00
September 448.08 195.81 252.27 559.12 168.47 0.00 0.00 0.00
October 444.24 216.02 228.22 487.45 310.33 0.00 0.00 0.00
November 208.61 60.29 148.32 121.42 491.51 0.00 0.00 0.00
December 185.56 80.29 105.27 101.30 639.15 0.00 0.00 0.00
                 
Annual Sum or Average 423.04 178.33 244.71 461.81 347.25 0.00 0.00 0.00
Minimum of Months 185.56 60.29 105.27 101.30 71.90 0.00 0.00 0.00
Maximum of Months 631.17 292.19 363.49 883.59 641.93 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 438.12 0.00 438.12 25.36 2481.94 0.00 0.00 0.00
February 599.54 0.00 599.54 52.82 2590.17 0.00 0.00 0.00
March 831.42 0.00 831.42 291.00 1734.30 0.00 0.00 0.00
April 998.65 2.84 995.80 622.43 1241.02 0.00 0.00 0.00
May 1324.88 44.15 1280.74 1233.61 767.78 0.00 0.00 0.00
June 1405.02 75.50 1329.53 1746.18 418.59 0.00 0.00 0.00
July 1357.82 49.10 1308.72 1952.20 232.43 0.00 0.00 0.00
August 1202.96 14.32 1188.65 1710.28 315.94 0.00 0.00 0.00
September 906.83 0.17 906.66 974.24 635.85 0.00 0.00 0.00
October 784.80 0.00 784.80 577.50 1154.12 0.00 0.00 0.00
November 550.46 0.00 550.46 147.95 1770.64 0.00 0.00 0.00
December 382.15 0.00 382.15 15.76 2337.15 0.00 0.00 0.00
                 
Annual Sum or Average 900.28 15.59 884.69 784.06 1299.29 0.00 0.00 0.00
Minimum of Months 382.15 0.00 382.15 15.76 232.43 0.00 0.00 0.00
Maximum of Months 1405.02 75.50 1329.53 1952.20 2590.17 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 610.12 244.61 365.51 371.60 1539.55 0.00 0.00 0.00
February 946.16 441.38 504.77 655.39 1559.03 0.00 0.00 0.00
March 1207.00 513.35 693.66 1044.07 1121.93 0.00 0.00 0.00
April 1448.49 634.48 814.00 1455.57 809.60 0.00 0.00 0.00
May 1756.71 702.09 1054.62 2026.83 523.96 0.00 0.00 0.00
June 1628.10 589.36 1038.74 2129.81 287.12 0.00 0.00 0.00
July 1635.23 590.11 1045.11 2327.91 159.22 0.00 0.00 0.00
August 1841.30 830.24 1011.06 2604.96 216.28 0.00 0.00 0.00
September 1373.25 616.13 757.13 1712.60 415.98 0.00 0.00 0.00
October 1244.96 564.26 680.70 1376.60 755.88 0.00 0.00 0.00
November 769.91 295.65 474.26 611.25 1111.20 0.00 0.00 0.00
December 599.80 281.63 318.17 399.59 1438.50 0.00 0.00 0.00
                 
Annual Sum or Average 1257.08 525.87 731.21 1398.15 824.07 0.00 0.00 0.00
Minimum of Months 599.80 244.61 318.17 371.60 159.22 0.00 0.00 0.00
Maximum of Months 1841.30 830.24 1054.62 2604.96 1559.03 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2266.47 1484.10 782.37 2213.12 2249.33 0.00 0.00 0.00
February 2989.40 1978.74 1010.66 2961.75 2309.82 0.00 0.00 0.00
March 2697.00 1496.88 1200.12 2831.91 1735.10 0.00 0.00 0.00
April 2092.78 827.55 1265.23 2270.85 1308.95 0.00 0.00 0.00
May 1834.01 382.55 1451.47 2119.98 837.65 0.00 0.00 0.00
June 1721.16 263.10 1458.07 2320.01 453.92 0.00 0.00 0.00
July 1804.13 313.38 1490.75 2711.43 244.28 0.00 0.00 0.00
August 2409.21 893.62 1515.59 3643.16 348.63 0.00 0.00 0.00
September 2614.04 1352.09 1261.95 3484.70 678.01 0.00 0.00 0.00
October 3581.02 2245.55 1335.46 4430.93 1217.18 0.00 0.00 0.00
November 2483.13 1491.24 991.89 2619.50 1708.37 0.00 0.00 0.00
December 2456.52 1743.96 712.55 2493.64 2115.23 0.00 0.00 0.00
                 
Annual Sum or Average 2409.69 1202.15 1207.54 2842.60 1261.15 0.00 0.00 0.00
Minimum of Months 1721.16 263.10 712.55 2119.98 244.28 0.00 0.00 0.00
Maximum of Months 3581.02 2245.55 1515.59 4430.93 2309.82 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 602.32 246.71 355.61 366.29 1612.39 0.00 0.00 0.00
February 888.21 390.10 498.10 600.56 1669.19 0.00 0.00 0.00
March 1311.55 605.50 706.04 1166.35 1158.34 0.00 0.00 0.00
April 1433.46 613.34 820.12 1448.48 870.48 0.00 0.00 0.00
May 1669.83 634.14 1035.70 1927.68 565.37 0.00 0.00 0.00
June 1827.58 737.12 1090.47 2398.13 322.82 0.00 0.00 0.00
July 1711.63 644.55 1067.08 2421.79 186.16 0.00 0.00 0.00
August 1893.53 876.58 1016.95 2682.66 251.85 0.00 0.00 0.00
September 1344.25 587.44 756.82 1692.81 453.61 0.00 0.00 0.00
October 1332.73 648.07 684.65 1497.31 809.59 0.00 0.00 0.00
November 625.84 180.87 444.97 414.83 1177.95 0.00 0.00 0.00
December 556.68 240.88 315.80 344.81 1526.04 0.00 0.00 0.00
                 
Annual Sum or Average 1269.12 535.00 734.12 1419.33 879.14 0.00 0.00 0.00
Minimum of Months 556.68 180.87 315.80 344.81 186.16 0.00 0.00 0.00
Maximum of Months 1893.53 876.58 1090.47 2682.66 1669.19 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 438.12 0.00 438.12 30.19 2377.85 0.00 0.00 0.00
February 599.54 0.00 599.54 63.78 2455.36 0.00 0.00 0.00
March 831.42 0.00 831.42 316.04 1603.60 0.00 0.00 0.00
April 998.65 2.84 995.80 657.54 1141.86 0.00 0.00 0.00
May 1324.88 44.15 1280.74 1250.03 730.29 0.00 0.00 0.00
June 1405.02 75.50 1329.53 1732.71 416.41 0.00 0.00 0.00
July 1357.82 49.10 1308.72 1929.15 240.63 0.00 0.00 0.00
August 1202.96 14.32 1188.65 1694.99 318.39 0.00 0.00 0.00
September 906.83 0.17 906.66 978.76 607.22 0.00 0.00 0.00
October 784.80 0.00 784.80 613.29 1056.52 0.00 0.00 0.00
November 550.46 0.00 550.46 179.06 1607.22 0.00 0.00 0.00
December 382.15 0.00 382.15 25.02 2163.84 0.00 0.00 0.00
                 
Annual Sum or Average 900.28 15.59 884.69 794.10 1219.61 0.00 0.00 0.00
Minimum of Months 382.15 0.00 382.15 25.02 240.63 0.00 0.00 0.00
Maximum of Months 1405.02 75.50 1329.53 1929.15 2455.36 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 610.12 244.61 365.51 379.69 1474.15 0.00 0.00 0.00
February 946.16 441.38 504.77 673.00 1476.25 0.00 0.00 0.00
March 1207.00 513.35 693.66 1066.43 1040.36 0.00 0.00 0.00
April 1448.49 634.48 814.00 1477.32 754.14 0.00 0.00 0.00
May 1756.71 702.09 1054.62 2030.82 503.33 0.00 0.00 0.00
June 1628.10 589.36 1038.74 2118.64 287.32 0.00 0.00 0.00
July 1635.23 590.11 1045.11 2311.75 165.30 0.00 0.00 0.00
August 1841.30 830.24 1011.06 2591.52 219.04 0.00 0.00 0.00
September 1373.25 616.13 757.13 1712.03 402.06 0.00 0.00 0.00
October 1244.96 564.26 680.70 1396.57 702.31 0.00 0.00 0.00
November 769.91 295.65 474.26 640.39 1013.94 0.00 0.00 0.00
December 599.80 281.63 318.17 416.41 1331.04 0.00 0.00 0.00
                 
Annual Sum or Average 1257.08 525.87 731.21 1406.26 776.88 0.00 0.00 0.00
Minimum of Months 599.80 244.61 318.17 379.69 165.30 0.00 0.00 0.00
Maximum of Months 1841.30 830.24 1054.62 2591.52 1476.25 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2266.47 1484.10 782.37 2232.79 2137.37 0.00 0.00 0.00
February 2989.40 1978.74 1010.66 2998.26 2170.53 0.00 0.00 0.00
March 2697.00 1496.88 1200.12 2861.70 1602.87 0.00 0.00 0.00
April 2092.78 827.55 1265.23 2300.34 1211.82 0.00 0.00 0.00
May 1834.01 382.55 1451.47 2129.47 797.47 0.00 0.00 0.00
June 1721.16 263.10 1458.07 2304.93 451.08 0.00 0.00 0.00
July 1804.13 313.38 1490.75 2688.25 251.93 0.00 0.00 0.00
August 2409.21 893.62 1515.59 3623.24 351.88 0.00 0.00 0.00
September 2614.04 1352.09 1261.95 3481.60 655.16 0.00 0.00 0.00
October 3581.02 2245.55 1335.46 4449.32 1139.02 0.00 0.00 0.00
November 2483.13 1491.24 991.89 2667.27 1553.03 0.00 0.00 0.00
December 2456.52 1743.96 712.55 2537.34 1945.10 0.00 0.00 0.00
                 
Annual Sum or Average 2409.69 1202.15 1207.54 2856.88 1183.29 0.00 0.00 0.00
Minimum of Months 1721.16 263.10 712.55 2129.47 251.93 0.00 0.00 0.00
Maximum of Months 3581.02 2245.55 1515.59 4449.32 2170.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 602.32 246.71 355.61 372.11 1541.93 0.00 0.00 0.00
February 888.21 390.10 498.10 609.51 1588.99 0.00 0.00 0.00
March 1311.55 605.50 706.04 1181.83 1082.19 0.00 0.00 0.00
April 1433.46 613.34 820.12 1464.88 813.64 0.00 0.00 0.00
May 1669.83 634.14 1035.70 1932.65 542.03 0.00 0.00 0.00
June 1827.58 737.12 1090.47 2386.53 321.03 0.00 0.00 0.00
July 1711.63 644.55 1067.08 2406.28 189.96 0.00 0.00 0.00
August 1893.53 876.58 1016.95 2670.00 253.44 0.00 0.00 0.00
September 1344.25 587.44 756.82 1692.78 437.85 0.00 0.00 0.00
October 1332.73 648.07 684.65 1513.04 756.70 0.00 0.00 0.00
November 625.84 180.87 444.97 435.14 1084.92 0.00 0.00 0.00
December 556.68 240.88 315.80 355.60 1422.65 0.00 0.00 0.00
                 
Annual Sum or Average 1269.12 535.00 734.12 1424.17 831.97 0.00 0.00 0.00
Minimum of Months 556.68 180.87 315.80 355.60 189.96 0.00 0.00 0.00
Maximum of Months 1893.53 876.58 1090.47 2670.00 1588.99 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.234690E+09 0.00 0.234690E+09 5092119.17 0.149774E+10
February 0.290084E+09 0.00 0.290084E+09 15675961.70 0.139973E+10
March 0.445374E+09 0.00 0.445374E+09 0.123986E+09 0.106930E+10
April 0.517698E+09 1472482.96 0.516225E+09 0.289831E+09 0.737683E+09
May 0.709714E+09 23647927.09 0.686066E+09 0.647813E+09 0.438521E+09
June 0.728364E+09 39137814.08 0.689226E+09 0.901954E+09 0.225320E+09
July 0.727357E+09 26303484.01 0.701053E+09 0.104314E+10 0.123897E+09
August 0.644404E+09 7669258.95 0.636735E+09 0.908855E+09 0.170973E+09
September 0.470103E+09 88030.64 0.470015E+09 0.496507E+09 0.353948E+09
October 0.420402E+09 0.00 0.420402E+09 0.286681E+09 0.689391E+09
November 0.285359E+09 0.00 0.285359E+09 55252258.30 0.108151E+10
December 0.204712E+09 0.00 0.204712E+09 2369643.28 0.146784E+10
           
Annual Sum or Average 0.567826E+10 98318997.72 0.557994E+10 0.477715E+10 0.925585E+10
Minimum of Months 0.204712E+09 0.00 0.204712E+09 2369643.28 0.123897E+09
Maximum of Months 0.728364E+09 39137814.08 0.701053E+09 0.104314E+10 0.149774E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.234687E+09 0.00 0.234687E+09 5091374.01 0.149774E+10
February 0.290079E+09 0.00 0.290079E+09 15674869.74 0.139973E+10
March 0.445367E+09 0.00 0.445367E+09 0.123981E+09 0.106930E+10
April 0.517691E+09 1472450.59 0.516218E+09 0.289824E+09 0.737684E+09
May 0.709704E+09 23647407.21 0.686056E+09 0.647800E+09 0.438520E+09
June 0.728354E+09 39136953.68 0.689217E+09 0.901940E+09 0.225319E+09
July 0.727346E+09 26302905.75 0.701043E+09 0.104312E+10 0.123896E+09
August 0.644396E+09 7669090.35 0.636726E+09 0.908845E+09 0.170972E+09
September 0.470097E+09 88028.70 0.470009E+09 0.496499E+09 0.353946E+09
October 0.420396E+09 0.00 0.420396E+09 0.286675E+09 0.689390E+09
November 0.285355E+09 0.00 0.285355E+09 55249775.91 0.108151E+10
December 0.204709E+09 0.00 0.204709E+09 2369319.48 0.146784E+10
           
Annual Sum or Average 0.567818E+10 98316836.30 0.557986E+10 0.477707E+10 0.925585E+10
Minimum of Months 0.204709E+09 0.00 0.204709E+09 2369319.48 0.123896E+09
Maximum of Months 0.728354E+09 39136953.68 0.701043E+09 0.104312E+10 0.149774E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.234688E+09 0.00 0.234688E+09 5091622.40 0.149774E+10
February 0.290081E+09 0.00 0.290081E+09 15675233.73 0.139973E+10
March 0.445369E+09 0.00 0.445369E+09 0.123983E+09 0.106930E+10
April 0.517693E+09 1472461.38 0.516221E+09 0.289827E+09 0.737684E+09
May 0.709707E+09 23647580.50 0.686060E+09 0.647804E+09 0.438520E+09
June 0.728357E+09 39137240.48 0.689220E+09 0.901945E+09 0.225320E+09
July 0.727350E+09 26303098.50 0.701047E+09 0.104313E+10 0.123897E+09
August 0.644398E+09 7669146.55 0.636729E+09 0.908848E+09 0.170972E+09
September 0.470099E+09 88029.35 0.470011E+09 0.496502E+09 0.353947E+09
October 0.420398E+09 0.00 0.420398E+09 0.286677E+09 0.689390E+09
November 0.285356E+09 0.00 0.285356E+09 55250603.38 0.108151E+10
December 0.204710E+09 0.00 0.204710E+09 2369427.41 0.146784E+10
           
Annual Sum or Average 0.567821E+10 98317556.77 0.557989E+10 0.477710E+10 0.925585E+10
Minimum of Months 0.204710E+09 0.00 0.204710E+09 2369427.41 0.123897E+09
Maximum of Months 0.728357E+09 39137240.48 0.701047E+09 0.104313E+10 0.149774E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.234687E+09 0.00 0.234687E+09 5091374.01 0.149774E+10
February 0.290079E+09 0.00 0.290079E+09 15674869.74 0.139973E+10
March 0.445367E+09 0.00 0.445367E+09 0.123981E+09 0.106930E+10
April 0.517691E+09 1472450.59 0.516218E+09 0.289824E+09 0.737684E+09
May 0.709704E+09 23647407.21 0.686056E+09 0.647800E+09 0.438520E+09
June 0.728354E+09 39136953.68 0.689217E+09 0.901940E+09 0.225319E+09
July 0.727346E+09 26302905.75 0.701043E+09 0.104312E+10 0.123896E+09
August 0.644396E+09 7669090.35 0.636726E+09 0.908845E+09 0.170972E+09
September 0.470097E+09 88028.70 0.470009E+09 0.496499E+09 0.353946E+09
October 0.420396E+09 0.00 0.420396E+09 0.286675E+09 0.689390E+09
November 0.285355E+09 0.00 0.285355E+09 55249775.91 0.108151E+10
December 0.204709E+09 0.00 0.204709E+09 2369319.48 0.146784E+10
           
Annual Sum or Average 0.567818E+10 98316836.30 0.557986E+10 0.477707E+10 0.925585E+10
Minimum of Months 0.204709E+09 0.00 0.204709E+09 2369319.48 0.123896E+09
Maximum of Months 0.728354E+09 39136953.68 0.701043E+09 0.104312E+10 0.149774E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.234678E+09 0.00 0.234678E+09 5091292.99 0.149768E+10
February 0.290068E+09 0.00 0.290068E+09 15674419.96 0.139967E+10
March 0.445350E+09 0.00 0.445350E+09 0.123977E+09 0.106925E+10
April 0.517671E+09 1472396.64 0.516199E+09 0.289814E+09 0.737654E+09
May 0.709677E+09 23646540.76 0.686030E+09 0.647776E+09 0.438503E+09
June 0.728326E+09 39135519.68 0.689191E+09 0.901906E+09 0.225310E+09
July 0.727319E+09 26301942.00 0.701017E+09 0.104308E+10 0.123892E+09
August 0.644371E+09 7668809.36 0.636702E+09 0.908810E+09 0.170965E+09
September 0.470079E+09 88025.48 0.469991E+09 0.496480E+09 0.353932E+09
October 0.420380E+09 0.00 0.420380E+09 0.286664E+09 0.689362E+09
November 0.285344E+09 0.00 0.285344E+09 55247962.82 0.108147E+10
December 0.204702E+09 0.00 0.204702E+09 2369277.95 0.146778E+10
           
Annual Sum or Average 0.567796E+10 98313233.92 0.557965E+10 0.477689E+10 0.925547E+10
Minimum of Months 0.204702E+09 0.00 0.204702E+09 2369277.95 0.123892E+09
Maximum of Months 0.728326E+09 39135519.68 0.701017E+09 0.104308E+10 0.149768E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544717E+09 0.218387E+09 0.326329E+09 0.311289E+09 0.153192E+10
February 0.762989E+09 0.355935E+09 0.407054E+09 0.505692E+09 0.138309E+10
March 0.107762E+10 0.458320E+09 0.619302E+09 0.910693E+09 0.110950E+10
April 0.125150E+10 0.548198E+09 0.703307E+09 0.124591E+10 0.758268E+09
May 0.156841E+10 0.626830E+09 0.941577E+09 0.181398E+10 0.489163E+09
June 0.140669E+10 0.509212E+09 0.897479E+09 0.185275E+10 0.246966E+09
July 0.145994E+10 0.526858E+09 0.933087E+09 0.209496E+10 0.126768E+09
August 0.164393E+10 0.741250E+09 0.902684E+09 0.234353E+10 0.174352E+09
September 0.118650E+10 0.532338E+09 0.654166E+09 0.148468E+10 0.373949E+09
October 0.111151E+10 0.503774E+09 0.607735E+09 0.122058E+10 0.724211E+09
November 0.665209E+09 0.255447E+09 0.409762E+09 0.501270E+09 0.108926E+10
December 0.535510E+09 0.251443E+09 0.284067E+09 0.335945E+09 0.145263E+10
           
Annual Sum or Average 0.132145E+11 0.552799E+10 0.768655E+10 0.146213E+11 0.946007E+10
Minimum of Months 0.535510E+09 0.218387E+09 0.284067E+09 0.311289E+09 0.126768E+09
Maximum of Months 0.164393E+10 0.741250E+09 0.941577E+09 0.234353E+10 0.153192E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544717E+09 0.218387E+09 0.326329E+09 0.311289E+09 0.153192E+10
February 0.762989E+09 0.355935E+09 0.407054E+09 0.505692E+09 0.138309E+10
March 0.107762E+10 0.458320E+09 0.619302E+09 0.910693E+09 0.110950E+10
April 0.125150E+10 0.548198E+09 0.703307E+09 0.124591E+10 0.758268E+09
May 0.156841E+10 0.626830E+09 0.941577E+09 0.181398E+10 0.489163E+09
June 0.140669E+10 0.509212E+09 0.897479E+09 0.185275E+10 0.246966E+09
July 0.145994E+10 0.526858E+09 0.933087E+09 0.209496E+10 0.126768E+09
August 0.164393E+10 0.741250E+09 0.902684E+09 0.234353E+10 0.174352E+09
September 0.118650E+10 0.532338E+09 0.654166E+09 0.148468E+10 0.373949E+09
October 0.111151E+10 0.503774E+09 0.607735E+09 0.122058E+10 0.724211E+09
November 0.665209E+09 0.255447E+09 0.409762E+09 0.501270E+09 0.108926E+10
December 0.535510E+09 0.251443E+09 0.284067E+09 0.335945E+09 0.145263E+10
           
Annual Sum or Average 0.132145E+11 0.552799E+10 0.768655E+10 0.146213E+11 0.946007E+10
Minimum of Months 0.535510E+09 0.218387E+09 0.284067E+09 0.311289E+09 0.126768E+09
Maximum of Months 0.164393E+10 0.741250E+09 0.941577E+09 0.234353E+10 0.153192E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.544707E+09 0.218383E+09 0.326323E+09 0.311283E+09 0.153189E+10
February 0.762975E+09 0.355928E+09 0.407047E+09 0.505682E+09 0.138307E+10
March 0.107760E+10 0.458312E+09 0.619291E+09 0.910676E+09 0.110948E+10
April 0.125148E+10 0.548188E+09 0.703294E+09 0.124588E+10 0.758254E+09
May 0.156838E+10 0.626818E+09 0.941560E+09 0.181394E+10 0.489155E+09
June 0.140667E+10 0.509203E+09 0.897462E+09 0.185272E+10 0.246961E+09
July 0.145992E+10 0.526848E+09 0.933070E+09 0.209492E+10 0.126765E+09
August 0.164390E+10 0.741236E+09 0.902667E+09 0.234349E+10 0.174349E+09
September 0.118648E+10 0.532328E+09 0.654154E+09 0.148465E+10 0.373942E+09
October 0.111149E+10 0.503764E+09 0.607724E+09 0.122056E+10 0.724198E+09
November 0.665196E+09 0.255442E+09 0.409754E+09 0.501260E+09 0.108924E+10
December 0.535500E+09 0.251438E+09 0.284062E+09 0.335939E+09 0.145260E+10
           
Annual Sum or Average 0.132143E+11 0.552789E+10 0.768641E+10 0.146210E+11 0.945990E+10
Minimum of Months 0.535500E+09 0.218383E+09 0.284062E+09 0.311283E+09 0.126765E+09
Maximum of Months 0.164390E+10 0.741236E+09 0.941560E+09 0.234349E+10 0.153189E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121408E+10 0.794987E+09 0.419094E+09 0.117760E+10 0.128765E+10
February 0.144636E+10 0.957373E+09 0.488991E+09 0.142849E+10 0.117903E+10
March 0.144471E+10 0.801834E+09 0.642872E+09 0.151624E+10 0.991738E+09
April 0.108488E+10 0.428992E+09 0.655888E+09 0.117306E+10 0.726409E+09
May 0.982430E+09 0.204918E+09 0.777512E+09 0.113895E+10 0.464876E+09
June 0.892241E+09 0.136387E+09 0.755854E+09 0.120672E+10 0.241303E+09
July 0.966422E+09 0.167866E+09 0.798556E+09 0.145616E+10 0.129354E+09
August 0.129055E+10 0.478682E+09 0.811865E+09 0.195725E+10 0.184672E+09
September 0.135510E+10 0.700908E+09 0.654188E+09 0.181604E+10 0.360144E+09
October 0.191824E+10 0.120287E+10 0.715370E+09 0.238767E+10 0.671884E+09
November 0.128723E+10 0.773041E+09 0.514188E+09 0.135096E+10 0.952635E+09
December 0.131588E+10 0.934186E+09 0.381695E+09 0.132661E+10 0.122425E+10
           
Annual Sum or Average 0.151981E+11 0.758205E+10 0.761607E+10 0.179357E+11 0.841394E+10
Minimum of Months 0.892241E+09 0.136387E+09 0.381695E+09 0.113895E+10 0.129354E+09
Maximum of Months 0.191824E+10 0.120287E+10 0.811865E+09 0.238767E+10 0.128765E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121407E+10 0.794981E+09 0.419092E+09 0.117758E+10 0.128765E+10
February 0.144635E+10 0.957366E+09 0.488988E+09 0.142848E+10 0.117903E+10
March 0.144470E+10 0.801828E+09 0.642868E+09 0.151622E+10 0.991738E+09
April 0.108487E+10 0.428989E+09 0.655885E+09 0.117305E+10 0.726409E+09
May 0.982425E+09 0.204916E+09 0.777508E+09 0.113894E+10 0.464875E+09
June 0.892236E+09 0.136386E+09 0.755850E+09 0.120671E+10 0.241303E+09
July 0.966416E+09 0.167865E+09 0.798552E+09 0.145615E+10 0.129353E+09
August 0.129054E+10 0.478679E+09 0.811861E+09 0.195724E+10 0.184672E+09
September 0.135509E+10 0.700903E+09 0.654185E+09 0.181602E+10 0.360143E+09
October 0.191823E+10 0.120286E+10 0.715366E+09 0.238765E+10 0.671883E+09
November 0.128722E+10 0.773035E+09 0.514185E+09 0.135095E+10 0.952635E+09
December 0.131587E+10 0.934180E+09 0.381693E+09 0.132660E+10 0.122425E+10
           
Annual Sum or Average 0.151980E+11 0.758199E+10 0.761603E+10 0.179356E+11 0.841393E+10
Minimum of Months 0.892236E+09 0.136386E+09 0.381693E+09 0.113894E+10 0.129353E+09
Maximum of Months 0.191823E+10 0.120286E+10 0.811861E+09 0.238765E+10 0.128765E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121408E+10 0.794987E+09 0.419094E+09 0.117760E+10 0.128765E+10
February 0.144636E+10 0.957373E+09 0.488991E+09 0.142849E+10 0.117903E+10
March 0.144471E+10 0.801834E+09 0.642872E+09 0.151624E+10 0.991738E+09
April 0.108488E+10 0.428992E+09 0.655888E+09 0.117306E+10 0.726409E+09
May 0.982430E+09 0.204918E+09 0.777512E+09 0.113895E+10 0.464876E+09
June 0.892241E+09 0.136387E+09 0.755854E+09 0.120672E+10 0.241303E+09
July 0.966422E+09 0.167866E+09 0.798556E+09 0.145616E+10 0.129354E+09
August 0.129055E+10 0.478682E+09 0.811865E+09 0.195725E+10 0.184672E+09
September 0.135510E+10 0.700908E+09 0.654188E+09 0.181604E+10 0.360144E+09
October 0.191824E+10 0.120287E+10 0.715370E+09 0.238767E+10 0.671884E+09
November 0.128723E+10 0.773041E+09 0.514188E+09 0.135096E+10 0.952635E+09
December 0.131588E+10 0.934186E+09 0.381695E+09 0.132661E+10 0.122425E+10
           
Annual Sum or Average 0.151981E+11 0.758205E+10 0.761607E+10 0.179357E+11 0.841394E+10
Minimum of Months 0.892241E+09 0.136387E+09 0.381695E+09 0.113895E+10 0.129354E+09
Maximum of Months 0.191824E+10 0.120287E+10 0.811865E+09 0.238767E+10 0.128765E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121407E+10 0.794981E+09 0.419092E+09 0.117758E+10 0.128765E+10
February 0.144635E+10 0.957366E+09 0.488988E+09 0.142848E+10 0.117903E+10
March 0.144470E+10 0.801828E+09 0.642868E+09 0.151622E+10 0.991738E+09
April 0.108487E+10 0.428989E+09 0.655885E+09 0.117305E+10 0.726409E+09
May 0.982425E+09 0.204916E+09 0.777508E+09 0.113894E+10 0.464875E+09
June 0.892236E+09 0.136386E+09 0.755850E+09 0.120671E+10 0.241303E+09
July 0.966416E+09 0.167865E+09 0.798552E+09 0.145615E+10 0.129353E+09
August 0.129054E+10 0.478679E+09 0.811861E+09 0.195724E+10 0.184672E+09
September 0.135509E+10 0.700903E+09 0.654185E+09 0.181602E+10 0.360143E+09
October 0.191823E+10 0.120286E+10 0.715366E+09 0.238765E+10 0.671883E+09
November 0.128722E+10 0.773035E+09 0.514185E+09 0.135095E+10 0.952635E+09
December 0.131587E+10 0.934180E+09 0.381693E+09 0.132660E+10 0.122425E+10
           
Annual Sum or Average 0.151980E+11 0.758199E+10 0.761603E+10 0.179356E+11 0.841393E+10
Minimum of Months 0.892236E+09 0.136386E+09 0.381693E+09 0.113894E+10 0.129353E+09
Maximum of Months 0.191823E+10 0.120286E+10 0.811861E+09 0.238765E+10 0.128765E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.121403E+10 0.794952E+09 0.419076E+09 0.117754E+10 0.128760E+10
February 0.144630E+10 0.957331E+09 0.488970E+09 0.142843E+10 0.117898E+10
March 0.144464E+10 0.801799E+09 0.642844E+09 0.151617E+10 0.991698E+09
April 0.108483E+10 0.428973E+09 0.655860E+09 0.117301E+10 0.726379E+09
May 0.982388E+09 0.204909E+09 0.777479E+09 0.113890E+10 0.464857E+09
June 0.892203E+09 0.136381E+09 0.755822E+09 0.120667E+10 0.241293E+09
July 0.966380E+09 0.167858E+09 0.798522E+09 0.145609E+10 0.129348E+09
August 0.129049E+10 0.478661E+09 0.811830E+09 0.195717E+10 0.184665E+09
September 0.135504E+10 0.700878E+09 0.654160E+09 0.181596E+10 0.360129E+09
October 0.191816E+10 0.120282E+10 0.715339E+09 0.238757E+10 0.671856E+09
November 0.128717E+10 0.773007E+09 0.514166E+09 0.135090E+10 0.952597E+09
December 0.131582E+10 0.934145E+09 0.381678E+09 0.132655E+10 0.122420E+10
           
Annual Sum or Average 0.151975E+11 0.758171E+10 0.761575E+10 0.179350E+11 0.841360E+10
Minimum of Months 0.892203E+09 0.136381E+09 0.381678E+09 0.113890E+10 0.129348E+09
Maximum of Months 0.191816E+10 0.120282E+10 0.811830E+09 0.238757E+10 0.128760E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.537757E+09 0.220267E+09 0.317490E+09 0.305529E+09 0.165087E+10
February 0.716257E+09 0.314583E+09 0.401674E+09 0.455392E+09 0.155298E+10
March 0.117096E+10 0.540600E+09 0.630360E+09 0.991099E+09 0.124879E+10
April 0.123852E+10 0.529931E+09 0.708590E+09 0.119832E+10 0.922102E+09
May 0.149084E+10 0.566164E+09 0.924679E+09 0.170390E+10 0.553541E+09
June 0.157905E+10 0.636875E+09 0.942173E+09 0.206054E+10 0.311324E+09
July 0.152816E+10 0.575458E+09 0.952701E+09 0.214146E+10 0.192581E+09
August 0.169056E+10 0.782618E+09 0.907941E+09 0.236664E+10 0.265030E+09
September 0.116145E+10 0.507550E+09 0.653898E+09 0.144926E+10 0.436678E+09
October 0.118987E+10 0.578606E+09 0.611266E+09 0.130560E+10 0.831210E+09
November 0.540735E+09 0.156276E+09 0.384459E+09 0.314726E+09 0.127402E+10
December 0.497005E+09 0.215056E+09 0.281950E+09 0.271319E+09 0.171194E+10
           
Annual Sum or Average 0.133412E+11 0.562398E+10 0.771718E+10 0.145638E+11 0.109511E+11
Minimum of Months 0.497005E+09 0.156276E+09 0.281950E+09 0.271319E+09 0.192581E+09
Maximum of Months 0.169056E+10 0.782618E+09 0.952701E+09 0.236664E+10 0.171194E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.537757E+09 0.220267E+09 0.317490E+09 0.305529E+09 0.165087E+10
February 0.716257E+09 0.314583E+09 0.401674E+09 0.455392E+09 0.155298E+10
March 0.117096E+10 0.540600E+09 0.630360E+09 0.991099E+09 0.124879E+10
April 0.123852E+10 0.529931E+09 0.708590E+09 0.119832E+10 0.922102E+09
May 0.149084E+10 0.566164E+09 0.924679E+09 0.170390E+10 0.553541E+09
June 0.157905E+10 0.636875E+09 0.942173E+09 0.206054E+10 0.311324E+09
July 0.152816E+10 0.575458E+09 0.952701E+09 0.214146E+10 0.192581E+09
August 0.169056E+10 0.782618E+09 0.907941E+09 0.236664E+10 0.265030E+09
September 0.116145E+10 0.507550E+09 0.653898E+09 0.144926E+10 0.436678E+09
October 0.118987E+10 0.578606E+09 0.611266E+09 0.130560E+10 0.831210E+09
November 0.540735E+09 0.156276E+09 0.384459E+09 0.314726E+09 0.127402E+10
December 0.497005E+09 0.215056E+09 0.281950E+09 0.271319E+09 0.171194E+10
           
Annual Sum or Average 0.133412E+11 0.562398E+10 0.771718E+10 0.145638E+11 0.109511E+11
Minimum of Months 0.497005E+09 0.156276E+09 0.281950E+09 0.271319E+09 0.192581E+09
Maximum of Months 0.169056E+10 0.782618E+09 0.952701E+09 0.236664E+10 0.171194E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.537747E+09 0.220263E+09 0.317484E+09 0.305523E+09 0.165084E+10
February 0.716244E+09 0.314577E+09 0.401667E+09 0.455384E+09 0.155295E+10
March 0.117094E+10 0.540590E+09 0.630348E+09 0.991081E+09 0.124877E+10
April 0.123850E+10 0.529922E+09 0.708577E+09 0.119830E+10 0.922086E+09
May 0.149082E+10 0.566154E+09 0.924662E+09 0.170387E+10 0.553531E+09
June 0.157902E+10 0.636864E+09 0.942155E+09 0.206051E+10 0.311318E+09
July 0.152813E+10 0.575447E+09 0.952684E+09 0.214142E+10 0.192578E+09
August 0.169053E+10 0.782604E+09 0.907925E+09 0.236660E+10 0.265025E+09
September 0.116143E+10 0.507541E+09 0.653886E+09 0.144923E+10 0.436670E+09
October 0.118985E+10 0.578595E+09 0.611255E+09 0.130558E+10 0.831195E+09
November 0.540725E+09 0.156273E+09 0.384452E+09 0.314721E+09 0.127399E+10
December 0.496996E+09 0.215052E+09 0.281944E+09 0.271314E+09 0.171191E+10
           
Annual Sum or Average 0.133409E+11 0.562388E+10 0.771704E+10 0.145635E+11 0.109509E+11
Minimum of Months 0.496996E+09 0.156273E+09 0.281944E+09 0.271314E+09 0.192578E+09
Maximum of Months 0.169053E+10 0.782604E+09 0.952684E+09 0.236660E+10 0.171191E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.117345E+10 0.00 0.117345E+10 67923433.42 0.664763E+10
February 0.145042E+10 0.00 0.145042E+10 0.127786E+09 0.626614E+10
March 0.222687E+10 0.00 0.222687E+10 0.779424E+09 0.464515E+10
April 0.258849E+10 7362461.72 0.258113E+10 0.161335E+10 0.321672E+10
May 0.354857E+10 0.118240E+09 0.343033E+10 0.330411E+10 0.205643E+10
June 0.364182E+10 0.195690E+09 0.344613E+10 0.452610E+10 0.108499E+10
July 0.363678E+10 0.131518E+09 0.350527E+10 0.522878E+10 0.622554E+09
August 0.322202E+10 38346539.14 0.318367E+10 0.458080E+10 0.846226E+09
September 0.235051E+10 440156.01 0.235007E+10 0.252522E+10 0.164813E+10
October 0.210201E+10 0.00 0.210201E+10 0.154679E+10 0.309120E+10
November 0.142680E+10 0.00 0.142680E+10 0.383484E+09 0.458951E+10
December 0.102356E+10 0.00 0.102356E+10 42209004.86 0.625982E+10
           
Annual Sum or Average 0.283913E+11 0.491598E+09 0.278997E+11 0.247260E+11 0.409745E+11
Minimum of Months 0.102356E+10 0.00 0.102356E+10 42209004.86 0.622554E+09
Maximum of Months 0.364182E+10 0.195690E+09 0.350527E+10 0.522878E+10 0.664763E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.163413E+10 0.655155E+09 0.978978E+09 0.995293E+09 0.412353E+10
February 0.228894E+10 0.106779E+10 0.122115E+10 0.158552E+10 0.377161E+10
March 0.323283E+10 0.137495E+10 0.185789E+10 0.279643E+10 0.300498E+10
April 0.375448E+10 0.164458E+10 0.210990E+10 0.377284E+10 0.209849E+10
May 0.470517E+10 0.188047E+10 0.282470E+10 0.542867E+10 0.140337E+10
June 0.422003E+10 0.152762E+10 0.269241E+10 0.552048E+10 0.744209E+09
July 0.437979E+10 0.158056E+10 0.279923E+10 0.623507E+10 0.426451E+09
August 0.493175E+10 0.222373E+10 0.270802E+10 0.697712E+10 0.579282E+09
September 0.355948E+10 0.159700E+10 0.196248E+10 0.443907E+10 0.107822E+10
October 0.333449E+10 0.151131E+10 0.182319E+10 0.368710E+10 0.202454E+10
November 0.199561E+10 0.766333E+09 0.122927E+10 0.158436E+10 0.288022E+10
December 0.160651E+10 0.754320E+09 0.852193E+09 0.107026E+10 0.385287E+10
           
Annual Sum or Average 0.396432E+11 0.165838E+11 0.230594E+11 0.440922E+11 0.259878E+11
Minimum of Months 0.160651E+10 0.655155E+09 0.852193E+09 0.995293E+09 0.426451E+09
Maximum of Months 0.493175E+10 0.222373E+10 0.282470E+10 0.697712E+10 0.412353E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.607052E+10 0.397502E+10 0.209550E+10 0.592763E+10 0.602459E+10
February 0.723196E+10 0.478697E+10 0.244499E+10 0.716508E+10 0.558791E+10
March 0.722365E+10 0.400925E+10 0.321440E+10 0.758500E+10 0.464729E+10
April 0.542448E+10 0.214500E+10 0.327948E+10 0.588605E+10 0.339279E+10
May 0.491221E+10 0.102461E+10 0.388760E+10 0.567815E+10 0.224355E+10
June 0.446126E+10 0.681949E+09 0.377931E+10 0.601347E+10 0.117655E+10
July 0.483217E+10 0.839346E+09 0.399282E+10 0.726228E+10 0.654267E+09
August 0.645283E+10 0.239346E+10 0.405937E+10 0.975784E+10 0.933769E+09
September 0.677560E+10 0.350462E+10 0.327098E+10 0.903235E+10 0.175741E+10
October 0.959139E+10 0.601449E+10 0.357690E+10 0.118678E+11 0.326009E+10
November 0.643627E+10 0.386529E+10 0.257098E+10 0.678975E+10 0.442809E+10
December 0.657953E+10 0.467103E+10 0.190850E+10 0.667897E+10 0.566544E+10
           
Annual Sum or Average 0.759919E+11 0.379110E+11 0.380808E+11 0.896444E+11 0.397718E+11
Minimum of Months 0.446126E+10 0.681949E+09 0.190850E+10 0.567815E+10 0.654267E+09
Maximum of Months 0.959139E+10 0.601449E+10 0.405937E+10 0.118678E+11 0.602459E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.161325E+10 0.660794E+09 0.952460E+09 0.981058E+09 0.431862E+10
February 0.214875E+10 0.943739E+09 0.120501E+10 0.145286E+10 0.403810E+10
March 0.351285E+10 0.162178E+10 0.189106E+10 0.312394E+10 0.310251E+10
April 0.371553E+10 0.158978E+10 0.212575E+10 0.375447E+10 0.225629E+10
May 0.447248E+10 0.169848E+10 0.277401E+10 0.516310E+10 0.151428E+10
June 0.473710E+10 0.191061E+10 0.282649E+10 0.621595E+10 0.836751E+09
July 0.458443E+10 0.172636E+10 0.285807E+10 0.648653E+10 0.498604E+09
August 0.507163E+10 0.234783E+10 0.272380E+10 0.718523E+10 0.674563E+09
September 0.348431E+10 0.152263E+10 0.196167E+10 0.438777E+10 0.117576E+10
October 0.356958E+10 0.173580E+10 0.183378E+10 0.401039E+10 0.216842E+10
November 0.162219E+10 0.468824E+09 0.115336E+10 0.107523E+10 0.305325E+10
December 0.149100E+10 0.645160E+09 0.845840E+09 0.923540E+09 0.408734E+10
           
Annual Sum or Average 0.400231E+11 0.168718E+11 0.231513E+11 0.447601E+11 0.277245E+11
Minimum of Months 0.149100E+10 0.468824E+09 0.845840E+09 0.923540E+09 0.498604E+09
Maximum of Months 0.507163E+10 0.234783E+10 0.285807E+10 0.718523E+10 0.431862E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.117345E+10 0.00 0.117345E+10 80854585.16 0.636884E+10
February 0.145042E+10 0.00 0.145042E+10 0.154306E+09 0.594000E+10
March 0.222687E+10 0.00 0.222687E+10 0.846491E+09 0.429507E+10
April 0.258849E+10 7362461.72 0.258113E+10 0.170435E+10 0.295970E+10
May 0.354857E+10 0.118240E+09 0.343033E+10 0.334807E+10 0.195602E+10
June 0.364182E+10 0.195690E+09 0.344613E+10 0.449119E+10 0.107934E+10
July 0.363678E+10 0.131518E+09 0.350527E+10 0.516703E+10 0.644501E+09
August 0.322202E+10 38346539.14 0.318367E+10 0.453986E+10 0.852765E+09
September 0.235051E+10 440156.01 0.235007E+10 0.253696E+10 0.157391E+10
October 0.210201E+10 0.00 0.210201E+10 0.164263E+10 0.282977E+10
November 0.142680E+10 0.00 0.142680E+10 0.464116E+09 0.416592E+10
December 0.102356E+10 0.00 0.102356E+10 67020251.34 0.579564E+10
           
Annual Sum or Average 0.283913E+11 0.491598E+09 0.278997E+11 0.250429E+11 0.384615E+11
Minimum of Months 0.102356E+10 0.00 0.102356E+10 67020251.34 0.644501E+09
Maximum of Months 0.364182E+10 0.195690E+09 0.350527E+10 0.516703E+10 0.636884E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.163413E+10 0.655155E+09 0.978978E+09 0.101695E+10 0.394835E+10
February 0.228894E+10 0.106779E+10 0.122115E+10 0.162812E+10 0.357134E+10
March 0.323283E+10 0.137495E+10 0.185789E+10 0.285632E+10 0.278651E+10
April 0.375448E+10 0.164458E+10 0.210990E+10 0.382922E+10 0.195473E+10
May 0.470517E+10 0.188047E+10 0.282470E+10 0.543934E+10 0.134812E+10
June 0.422003E+10 0.152762E+10 0.269241E+10 0.549152E+10 0.744735E+09
July 0.437979E+10 0.158056E+10 0.279923E+10 0.619180E+10 0.442735E+09
August 0.493175E+10 0.222373E+10 0.270802E+10 0.694113E+10 0.586690E+09
September 0.355948E+10 0.159700E+10 0.196248E+10 0.443757E+10 0.104214E+10
October 0.333449E+10 0.151131E+10 0.182319E+10 0.374056E+10 0.188108E+10
November 0.199561E+10 0.766333E+09 0.122927E+10 0.165989E+10 0.262813E+10
December 0.160651E+10 0.754320E+09 0.852193E+09 0.111531E+10 0.356505E+10
           
Annual Sum or Average 0.396432E+11 0.165838E+11 0.230594E+11 0.443477E+11 0.244996E+11
Minimum of Months 0.160651E+10 0.655155E+09 0.852193E+09 0.101695E+10 0.442735E+09
Maximum of Months 0.493175E+10 0.222373E+10 0.282470E+10 0.694113E+10 0.394835E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.607052E+10 0.397502E+10 0.209550E+10 0.598031E+10 0.572473E+10
February 0.723196E+10 0.478697E+10 0.244499E+10 0.725339E+10 0.525095E+10
March 0.722365E+10 0.400925E+10 0.321440E+10 0.766478E+10 0.429313E+10
April 0.542448E+10 0.214500E+10 0.327948E+10 0.596249E+10 0.314103E+10
May 0.491221E+10 0.102461E+10 0.388760E+10 0.570358E+10 0.213595E+10
June 0.446126E+10 0.681949E+09 0.377931E+10 0.597437E+10 0.116920E+10
July 0.483217E+10 0.839346E+09 0.399282E+10 0.720020E+10 0.674780E+09
August 0.645283E+10 0.239346E+10 0.405937E+10 0.970449E+10 0.942462E+09
September 0.677560E+10 0.350462E+10 0.327098E+10 0.902430E+10 0.169817E+10
October 0.959139E+10 0.601449E+10 0.357690E+10 0.119171E+11 0.305075E+10
November 0.643627E+10 0.386529E+10 0.257098E+10 0.691356E+10 0.402546E+10
December 0.657953E+10 0.467103E+10 0.190850E+10 0.679602E+10 0.520976E+10
           
Annual Sum or Average 0.759919E+11 0.379110E+11 0.380808E+11 0.900945E+11 0.373164E+11
Minimum of Months 0.446126E+10 0.681949E+09 0.190850E+10 0.570358E+10 0.674780E+09
Maximum of Months 0.959139E+10 0.601449E+10 0.405937E+10 0.119171E+11 0.572473E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.161325E+10 0.660794E+09 0.952460E+09 0.996651E+09 0.412991E+10
February 0.214875E+10 0.943739E+09 0.120501E+10 0.147453E+10 0.384409E+10
March 0.351285E+10 0.162178E+10 0.189106E+10 0.316542E+10 0.289853E+10
April 0.371553E+10 0.158978E+10 0.212575E+10 0.379698E+10 0.210896E+10
May 0.447248E+10 0.169848E+10 0.277401E+10 0.517642E+10 0.145177E+10
June 0.473710E+10 0.191061E+10 0.282649E+10 0.618588E+10 0.832104E+09
July 0.458443E+10 0.172636E+10 0.285807E+10 0.644498E+10 0.508780E+09
August 0.507163E+10 0.234783E+10 0.272380E+10 0.715133E+10 0.678803E+09
September 0.348431E+10 0.152263E+10 0.196167E+10 0.438768E+10 0.113491E+10
October 0.356958E+10 0.173580E+10 0.183378E+10 0.405252E+10 0.202676E+10
November 0.162219E+10 0.468824E+09 0.115336E+10 0.112787E+10 0.281211E+10
December 0.149100E+10 0.645160E+09 0.845840E+09 0.952442E+09 0.381043E+10
           
Annual Sum or Average 0.400231E+11 0.168718E+11 0.231513E+11 0.449127E+11 0.262372E+11
Minimum of Months 0.149100E+10 0.468824E+09 0.845840E+09 0.952442E+09 0.508780E+09
Maximum of Months 0.507163E+10 0.234783E+10 0.285807E+10 0.715133E+10 0.412991E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.50 2795.94 438.11 0.00 438.11 0.00 0.00
February 32.40 2892.93 599.53 0.00 599.53 0.00 0.00
March 231.45 1996.13 831.40 0.00 831.40 0.00 0.00
April 559.07 1422.99 998.63 2.84 995.79 0.00 0.00
May 1209.30 818.62 1324.86 44.14 1280.72 0.00 0.00
June 1739.85 434.64 1405.00 75.50 1329.50 0.00 0.00
July 1947.28 231.29 1357.79 49.10 1308.69 0.00 0.00
August 1696.61 319.17 1202.94 14.32 1188.63 0.00 0.00
September 957.75 682.76 906.82 0.17 906.65 0.00 0.00
October 535.16 1286.93 784.79 0.00 784.79 0.00 0.00
November 106.58 2086.24 550.45 0.00 550.45 0.00 0.00
December 4.42 2740.11 382.15 0.00 382.15 0.00 0.00
               
Annual Sum or Average 757.40 1467.49 900.27 15.59 884.68 0.00 0.00
Minimum of Months 4.42 231.29 382.15 0.00 382.15 0.00 0.00
Maximum of Months 1947.28 2892.93 1405.00 75.50 1329.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 348.66 1715.85 610.12 244.61 365.51 0.00 0.00
February 627.09 1715.13 946.16 441.38 504.78 0.00 0.00
March 1020.03 1242.71 1207.01 513.35 693.66 0.00 0.00
April 1442.01 877.62 1448.49 634.48 814.01 0.00 0.00
May 2031.77 547.89 1756.72 702.09 1054.63 0.00 0.00
June 2144.38 285.84 1628.10 589.36 1038.74 0.00 0.00
July 2346.49 141.99 1635.23 590.11 1045.12 0.00 0.00
August 2624.90 195.29 1841.31 830.25 1011.06 0.00 0.00
September 1718.37 432.81 1373.26 616.13 757.13 0.00 0.00
October 1367.13 811.16 1244.96 564.26 680.70 0.00 0.00
November 580.17 1260.71 769.91 295.65 474.26 0.00 0.00
December 376.28 1627.04 599.81 281.63 318.17 0.00 0.00
               
Annual Sum or Average 1390.90 899.93 1257.08 525.87 731.21 0.00 0.00
Minimum of Months 348.66 141.99 599.81 244.61 318.17 0.00 0.00
Maximum of Months 2624.90 1715.85 1841.31 830.25 1054.63 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2198.29 2403.74 2266.40 1484.05 782.35 0.00 0.00
February 2952.37 2436.80 2989.31 1978.68 1010.63 0.00 0.00
March 2830.45 1851.35 2696.93 1496.83 1200.09 0.00 0.00
April 2262.82 1401.24 2092.72 827.52 1265.20 0.00 0.00
May 2126.15 867.82 1833.97 382.53 1451.43 0.00 0.00
June 2327.75 465.47 1721.13 263.09 1458.04 0.00 0.00
July 2718.30 241.47 1804.08 313.37 1490.72 0.00 0.00
August 3653.73 344.74 2409.15 893.59 1515.56 0.00 0.00
September 3503.12 694.72 2613.97 1352.04 1261.92 0.00 0.00
October 4457.22 1254.25 3580.91 2245.48 1335.43 0.00 0.00
November 2606.00 1837.63 2483.05 1491.19 991.86 0.00 0.00
December 2476.46 2285.39 2456.44 1743.91 712.54 0.00 0.00
               
Annual Sum or Average 2843.66 1334.01 2409.62 1202.11 1207.51 0.00 0.00
Minimum of Months 2126.15 241.47 1721.13 263.09 712.54 0.00 0.00
Maximum of Months 4457.22 2436.80 3580.91 2245.48 1515.56 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 342.21 1849.09 602.32 246.71 355.61 0.00 0.00
February 564.72 1925.81 888.21 390.11 498.10 0.00 0.00
March 1110.10 1398.73 1311.55 605.51 706.04 0.00 0.00
April 1386.94 1067.24 1433.46 613.34 820.12 0.00 0.00
May 1908.48 620.00 1669.84 634.14 1035.70 0.00 0.00
June 2384.87 360.33 1827.59 737.12 1090.47 0.00 0.00
July 2398.57 215.70 1711.64 644.55 1067.09 0.00 0.00
August 2650.80 296.85 1893.54 876.58 1016.95 0.00 0.00
September 1677.37 505.41 1344.26 587.44 756.82 0.00 0.00
October 1462.36 931.01 1332.73 648.08 684.66 0.00 0.00
November 364.26 1474.55 625.85 180.87 444.97 0.00 0.00
December 303.89 1917.49 556.68 240.88 315.80 0.00 0.00
               
Annual Sum or Average 1385.44 1041.76 1269.13 535.00 734.13 0.00 0.00
Minimum of Months 303.89 215.70 556.68 180.87 315.80 0.00 0.00
Maximum of Months 2650.80 1925.81 1893.54 876.58 1090.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 25.36 2481.94 438.12 0.00 438.12 0.00 0.00
February 52.82 2590.17 599.54 0.00 599.54 0.00 0.00
March 291.00 1734.30 831.42 0.00 831.42 0.00 0.00
April 622.43 1241.02 998.65 2.84 995.80 0.00 0.00
May 1233.61 767.78 1324.88 44.15 1280.74 0.00 0.00
June 1746.18 418.59 1405.02 75.50 1329.53 0.00 0.00
July 1952.20 232.43 1357.82 49.10 1308.72 0.00 0.00
August 1710.28 315.94 1202.96 14.32 1188.65 0.00 0.00
September 974.24 635.85 906.83 0.17 906.66 0.00 0.00
October 577.50 1154.12 784.80 0.00 784.80 0.00 0.00
November 147.95 1770.64 550.46 0.00 550.46 0.00 0.00
December 15.76 2337.15 382.15 0.00 382.15 0.00 0.00
               
Annual Sum or Average 784.06 1299.29 900.28 15.59 884.69 0.00 0.00
Minimum of Months 15.76 232.43 382.15 0.00 382.15 0.00 0.00
Maximum of Months 1952.20 2590.17 1405.02 75.50 1329.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 371.60 1539.55 610.12 244.61 365.51 0.00 0.00
February 655.39 1559.03 946.16 441.38 504.77 0.00 0.00
March 1044.07 1121.93 1207.00 513.35 693.66 0.00 0.00
April 1455.57 809.60 1448.49 634.48 814.00 0.00 0.00
May 2026.83 523.96 1756.71 702.09 1054.62 0.00 0.00
June 2129.81 287.12 1628.10 589.36 1038.74 0.00 0.00
July 2327.91 159.22 1635.23 590.11 1045.11 0.00 0.00
August 2604.96 216.28 1841.30 830.24 1011.06 0.00 0.00
September 1712.60 415.98 1373.25 616.13 757.13 0.00 0.00
October 1376.60 755.88 1244.96 564.26 680.70 0.00 0.00
November 611.25 1111.20 769.91 295.65 474.26 0.00 0.00
December 399.59 1438.50 599.80 281.63 318.17 0.00 0.00
               
Annual Sum or Average 1398.15 824.07 1257.08 525.87 731.21 0.00 0.00
Minimum of Months 371.60 159.22 599.80 244.61 318.17 0.00 0.00
Maximum of Months 2604.96 1559.03 1841.30 830.24 1054.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2213.12 2249.33 2266.47 1484.10 782.37 0.00 0.00
February 2961.75 2309.82 2989.40 1978.74 1010.66 0.00 0.00
March 2831.91 1735.10 2697.00 1496.88 1200.12 0.00 0.00
April 2270.85 1308.95 2092.78 827.55 1265.23 0.00 0.00
May 2119.98 837.65 1834.01 382.55 1451.47 0.00 0.00
June 2320.01 453.92 1721.16 263.10 1458.07 0.00 0.00
July 2711.43 244.28 1804.13 313.38 1490.75 0.00 0.00
August 3643.16 348.63 2409.21 893.62 1515.59 0.00 0.00
September 3484.70 678.01 2614.04 1352.09 1261.95 0.00 0.00
October 4430.93 1217.18 3581.02 2245.55 1335.46 0.00 0.00
November 2619.50 1708.37 2483.13 1491.24 991.89 0.00 0.00
December 2493.64 2115.23 2456.52 1743.96 712.55 0.00 0.00
               
Annual Sum or Average 2842.60 1261.15 2409.69 1202.15 1207.54 0.00 0.00
Minimum of Months 2119.98 244.28 1721.16 263.10 712.55 0.00 0.00
Maximum of Months 4430.93 2309.82 3581.02 2245.55 1515.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 366.29 1612.39 602.32 246.71 355.61 0.00 0.00
February 600.56 1669.19 888.21 390.10 498.10 0.00 0.00
March 1166.35 1158.34 1311.55 605.50 706.04 0.00 0.00
April 1448.48 870.48 1433.46 613.34 820.12 0.00 0.00
May 1927.68 565.37 1669.83 634.14 1035.70 0.00 0.00
June 2398.13 322.82 1827.58 737.12 1090.47 0.00 0.00
July 2421.79 186.16 1711.63 644.55 1067.08 0.00 0.00
August 2682.66 251.85 1893.53 876.58 1016.95 0.00 0.00
September 1692.81 453.61 1344.25 587.44 756.82 0.00 0.00
October 1497.31 809.59 1332.73 648.07 684.65 0.00 0.00
November 414.83 1177.95 625.84 180.87 444.97 0.00 0.00
December 344.81 1526.04 556.68 240.88 315.80 0.00 0.00
               
Annual Sum or Average 1419.33 879.14 1269.12 535.00 734.12 0.00 0.00
Minimum of Months 344.81 186.16 556.68 180.87 315.80 0.00 0.00
Maximum of Months 2682.66 1669.19 1893.53 876.58 1090.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 30.19 2377.85 438.12 0.00 438.12 0.00 0.00
February 63.78 2455.36 599.54 0.00 599.54 0.00 0.00
March 316.04 1603.60 831.42 0.00 831.42 0.00 0.00
April 657.54 1141.86 998.65 2.84 995.80 0.00 0.00
May 1250.03 730.29 1324.88 44.15 1280.74 0.00 0.00
June 1732.71 416.41 1405.02 75.50 1329.53 0.00 0.00
July 1929.15 240.63 1357.82 49.10 1308.72 0.00 0.00
August 1694.99 318.39 1202.96 14.32 1188.65 0.00 0.00
September 978.76 607.22 906.83 0.17 906.66 0.00 0.00
October 613.29 1056.52 784.80 0.00 784.80 0.00 0.00
November 179.06 1607.22 550.46 0.00 550.46 0.00 0.00
December 25.02 2163.84 382.15 0.00 382.15 0.00 0.00
               
Annual Sum or Average 794.10 1219.61 900.28 15.59 884.69 0.00 0.00
Minimum of Months 25.02 240.63 382.15 0.00 382.15 0.00 0.00
Maximum of Months 1929.15 2455.36 1405.02 75.50 1329.53 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 379.69 1474.15 610.12 244.61 365.51 0.00 0.00
February 673.00 1476.25 946.16 441.38 504.77 0.00 0.00
March 1066.43 1040.36 1207.00 513.35 693.66 0.00 0.00
April 1477.32 754.14 1448.49 634.48 814.00 0.00 0.00
May 2030.82 503.33 1756.71 702.09 1054.62 0.00 0.00
June 2118.64 287.32 1628.10 589.36 1038.74 0.00 0.00
July 2311.75 165.30 1635.23 590.11 1045.11 0.00 0.00
August 2591.52 219.04 1841.30 830.24 1011.06 0.00 0.00
September 1712.03 402.06 1373.25 616.13 757.13 0.00 0.00
October 1396.57 702.31 1244.96 564.26 680.70 0.00 0.00
November 640.39 1013.94 769.91 295.65 474.26 0.00 0.00
December 416.41 1331.04 599.80 281.63 318.17 0.00 0.00
               
Annual Sum or Average 1406.26 776.88 1257.08 525.87 731.21 0.00 0.00
Minimum of Months 379.69 165.30 599.80 244.61 318.17 0.00 0.00
Maximum of Months 2591.52 1476.25 1841.30 830.24 1054.62 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 2232.79 2137.37 2266.47 1484.10 782.37 0.00 0.00
February 2998.26 2170.53 2989.40 1978.74 1010.66 0.00 0.00
March 2861.70 1602.87 2697.00 1496.88 1200.12 0.00 0.00
April 2300.34 1211.82 2092.78 827.55 1265.23 0.00 0.00
May 2129.47 797.47 1834.01 382.55 1451.47 0.00 0.00
June 2304.93 451.08 1721.16 263.10 1458.07 0.00 0.00
July 2688.25 251.93 1804.13 313.38 1490.75 0.00 0.00
August 3623.24 351.88 2409.21 893.62 1515.59 0.00 0.00
September 3481.60 655.16 2614.04 1352.09 1261.95 0.00 0.00
October 4449.32 1139.02 3581.02 2245.55 1335.46 0.00 0.00
November 2667.27 1553.03 2483.13 1491.24 991.89 0.00 0.00
December 2537.34 1945.10 2456.52 1743.96 712.55 0.00 0.00
               
Annual Sum or Average 2856.88 1183.29 2409.69 1202.15 1207.54 0.00 0.00
Minimum of Months 2129.47 251.93 1721.16 263.10 712.55 0.00 0.00
Maximum of Months 4449.32 2170.53 3581.02 2245.55 1515.59 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 372.11 1541.93 602.32 246.71 355.61 0.00 0.00
February 609.51 1588.99 888.21 390.10 498.10 0.00 0.00
March 1181.83 1082.19 1311.55 605.50 706.04 0.00 0.00
April 1464.88 813.64 1433.46 613.34 820.12 0.00 0.00
May 1932.65 542.03 1669.83 634.14 1035.70 0.00 0.00
June 2386.53 321.03 1827.58 737.12 1090.47 0.00 0.00
July 2406.28 189.96 1711.63 644.55 1067.08 0.00 0.00
August 2670.00 253.44 1893.53 876.58 1016.95 0.00 0.00
September 1692.78 437.85 1344.25 587.44 756.82 0.00 0.00
October 1513.04 756.70 1332.73 648.07 684.65 0.00 0.00
November 435.14 1084.92 625.84 180.87 444.97 0.00 0.00
December 355.60 1422.65 556.68 240.88 315.80 0.00 0.00
               
Annual Sum or Average 1424.17 831.97 1269.12 535.00 734.12 0.00 0.00
Minimum of Months 355.60 189.96 556.68 180.87 315.80 0.00 0.00
Maximum of Months 2670.00 1588.99 1893.53 876.58 1090.47 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 25457782.57 0.748865E+10 0.117343E+10 0.00 0.117343E+10 0.00 0.00
February 78375354.88 0.699859E+10 0.145039E+10 0.00 0.145039E+10 0.00 0.00
March 0.619907E+09 0.534645E+10 0.222683E+10 0.00 0.222683E+10 0.00 0.00
April 0.144912E+10 0.368839E+10 0.258844E+10 7362242.16 0.258108E+10 0.00 0.00
May 0.323899E+10 0.219258E+10 0.354851E+10 0.118237E+09 0.343027E+10 0.00 0.00
June 0.450969E+10 0.112659E+10 0.364175E+10 0.195684E+09 0.344607E+10 0.00 0.00
July 0.521560E+10 0.619479E+09 0.363672E+10 0.131514E+09 0.350520E+10 0.00 0.00
August 0.454420E+10 0.854854E+09 0.322196E+10 38345395.57 0.318362E+10 0.00 0.00
September 0.248249E+10 0.176972E+10 0.235047E+10 440142.88 0.235003E+10 0.00 0.00
October 0.143337E+10 0.344692E+10 0.210197E+10 0.00 0.210197E+10 0.00 0.00
November 0.276250E+09 0.540752E+10 0.142677E+10 0.00 0.142677E+10 0.00 0.00
December 11846987.61 0.733912E+10 0.102354E+10 0.00 0.102354E+10 0.00 0.00
               
Annual Sum or Average 0.238853E+11 0.462789E+11 0.283908E+11 0.491583E+09 0.278992E+11 0.00 0.00
Minimum of Months 11846987.61 0.619479E+09 0.102354E+10 0.00 0.102354E+10 0.00 0.00
Maximum of Months 0.521560E+10 0.748865E+10 0.364175E+10 0.195684E+09 0.350520E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.933860E+09 0.459574E+10 0.163414E+10 0.655158E+09 0.978982E+09 0.00 0.00
February 0.151707E+10 0.414925E+10 0.228895E+10 0.106780E+10 0.122116E+10 0.00 0.00
March 0.273206E+10 0.332848E+10 0.323285E+10 0.137495E+10 0.185790E+10 0.00 0.00
April 0.373770E+10 0.227479E+10 0.375449E+10 0.164458E+10 0.210991E+10 0.00 0.00
May 0.544190E+10 0.146748E+10 0.470519E+10 0.188048E+10 0.282471E+10 0.00 0.00
June 0.555823E+10 0.740892E+09 0.422005E+10 0.152763E+10 0.269242E+10 0.00 0.00
July 0.628485E+10 0.380300E+09 0.437981E+10 0.158056E+10 0.279924E+10 0.00 0.00
August 0.703054E+10 0.523053E+09 0.493177E+10 0.222373E+10 0.270803E+10 0.00 0.00
September 0.445402E+10 0.112184E+10 0.355949E+10 0.159700E+10 0.196249E+10 0.00 0.00
October 0.366173E+10 0.217262E+10 0.333451E+10 0.151131E+10 0.182319E+10 0.00 0.00
November 0.150380E+10 0.326775E+10 0.199561E+10 0.766336E+09 0.122928E+10 0.00 0.00
December 0.100783E+10 0.435785E+10 0.160652E+10 0.754323E+09 0.852197E+09 0.00 0.00
               
Annual Sum or Average 0.438636E+11 0.283800E+11 0.396434E+11 0.165839E+11 0.230595E+11 0.00 0.00
Minimum of Months 0.933860E+09 0.380300E+09 0.160652E+10 0.655158E+09 0.852197E+09 0.00 0.00
Maximum of Months 0.703054E+10 0.459574E+10 0.493177E+10 0.222373E+10 0.282471E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.588790E+10 0.643818E+10 0.607034E+10 0.397489E+10 0.209545E+10 0.00 0.00
February 0.714238E+10 0.589510E+10 0.723174E+10 0.478681E+10 0.244493E+10 0.00 0.00
March 0.758109E+10 0.495865E+10 0.722345E+10 0.400912E+10 0.321432E+10 0.00 0.00
April 0.586523E+10 0.363201E+10 0.542434E+10 0.214493E+10 0.327941E+10 0.00 0.00
May 0.569469E+10 0.232436E+10 0.491210E+10 0.102458E+10 0.388752E+10 0.00 0.00
June 0.603353E+10 0.120651E+10 0.446116E+10 0.681927E+09 0.377923E+10 0.00 0.00
July 0.728070E+10 0.646762E+09 0.483206E+10 0.839319E+09 0.399274E+10 0.00 0.00
August 0.978615E+10 0.923353E+09 0.645266E+10 0.239338E+10 0.405928E+10 0.00 0.00
September 0.908008E+10 0.180070E+10 0.677541E+10 0.350450E+10 0.327091E+10 0.00 0.00
October 0.119382E+11 0.335939E+10 0.959111E+10 0.601430E+10 0.357681E+10 0.00 0.00
November 0.675474E+10 0.476314E+10 0.643607E+10 0.386516E+10 0.257091E+10 0.00 0.00
December 0.663296E+10 0.612118E+10 0.657933E+10 0.467088E+10 0.190845E+10 0.00 0.00
               
Annual Sum or Average 0.896776E+11 0.420693E+11 0.759898E+11 0.379098E+11 0.380800E+11 0.00 0.00
Minimum of Months 0.569469E+10 0.646762E+09 0.446116E+10 0.681927E+09 0.190845E+10 0.00 0.00
Maximum of Months 0.119382E+11 0.643818E+10 0.959111E+10 0.601430E+10 0.405928E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.916580E+09 0.495259E+10 0.161326E+10 0.660796E+09 0.952464E+09 0.00 0.00
February 0.136617E+10 0.465892E+10 0.214876E+10 0.943743E+09 0.120502E+10 0.00 0.00
March 0.297328E+10 0.374636E+10 0.351286E+10 0.162179E+10 0.189107E+10 0.00 0.00
April 0.359494E+10 0.276629E+10 0.371554E+10 0.158978E+10 0.212576E+10 0.00 0.00
May 0.511168E+10 0.166061E+10 0.447250E+10 0.169848E+10 0.277402E+10 0.00 0.00
June 0.618159E+10 0.933965E+09 0.473712E+10 0.191061E+10 0.282650E+10 0.00 0.00
July 0.642434E+10 0.577741E+09 0.458445E+10 0.172636E+10 0.285809E+10 0.00 0.00
August 0.709989E+10 0.795085E+09 0.507165E+10 0.234784E+10 0.272381E+10 0.00 0.00
September 0.434774E+10 0.131002E+10 0.348432E+10 0.152264E+10 0.196168E+10 0.00 0.00
October 0.391679E+10 0.249361E+10 0.356959E+10 0.173581E+10 0.183379E+10 0.00 0.00
November 0.944174E+09 0.382202E+10 0.162219E+10 0.468826E+09 0.115337E+10 0.00 0.00
December 0.813952E+09 0.513579E+10 0.149101E+10 0.645163E+09 0.845843E+09 0.00 0.00
               
Annual Sum or Average 0.436911E+11 0.328530E+11 0.400232E+11 0.168718E+11 0.231514E+11 0.00 0.00
Minimum of Months 0.813952E+09 0.577741E+09 0.149101E+10 0.468826E+09 0.845843E+09 0.00 0.00
Maximum of Months 0.709989E+10 0.513579E+10 0.507165E+10 0.234784E+10 0.285809E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 67923433.42 0.664763E+10 0.117345E+10 0.00 0.117345E+10 0.00 0.00
February 0.127786E+09 0.626614E+10 0.145042E+10 0.00 0.145042E+10 0.00 0.00
March 0.779424E+09 0.464515E+10 0.222687E+10 0.00 0.222687E+10 0.00 0.00
April 0.161335E+10 0.321672E+10 0.258849E+10 7362461.72 0.258113E+10 0.00 0.00
May 0.330411E+10 0.205643E+10 0.354857E+10 0.118240E+09 0.343033E+10 0.00 0.00
June 0.452610E+10 0.108499E+10 0.364182E+10 0.195690E+09 0.344613E+10 0.00 0.00
July 0.522878E+10 0.622554E+09 0.363678E+10 0.131518E+09 0.350527E+10 0.00 0.00
August 0.458080E+10 0.846226E+09 0.322202E+10 38346539.14 0.318367E+10 0.00 0.00
September 0.252522E+10 0.164813E+10 0.235051E+10 440156.01 0.235007E+10 0.00 0.00
October 0.154679E+10 0.309120E+10 0.210201E+10 0.00 0.210201E+10 0.00 0.00
November 0.383484E+09 0.458951E+10 0.142680E+10 0.00 0.142680E+10 0.00 0.00
December 42209004.86 0.625982E+10 0.102356E+10 0.00 0.102356E+10 0.00 0.00
               
Annual Sum or Average 0.247260E+11 0.409745E+11 0.283913E+11 0.491598E+09 0.278997E+11 0.00 0.00
Minimum of Months 42209004.86 0.622554E+09 0.102356E+10 0.00 0.102356E+10 0.00 0.00
Maximum of Months 0.522878E+10 0.664763E+10 0.364182E+10 0.195690E+09 0.350527E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.995293E+09 0.412353E+10 0.163413E+10 0.655155E+09 0.978978E+09 0.00 0.00
February 0.158552E+10 0.377161E+10 0.228894E+10 0.106779E+10 0.122115E+10 0.00 0.00
March 0.279643E+10 0.300498E+10 0.323283E+10 0.137495E+10 0.185789E+10 0.00 0.00
April 0.377284E+10 0.209849E+10 0.375448E+10 0.164458E+10 0.210990E+10 0.00 0.00
May 0.542867E+10 0.140337E+10 0.470517E+10 0.188047E+10 0.282470E+10 0.00 0.00
June 0.552048E+10 0.744209E+09 0.422003E+10 0.152762E+10 0.269241E+10 0.00 0.00
July 0.623507E+10 0.426451E+09 0.437979E+10 0.158056E+10 0.279923E+10 0.00 0.00
August 0.697712E+10 0.579282E+09 0.493175E+10 0.222373E+10 0.270802E+10 0.00 0.00
September 0.443907E+10 0.107822E+10 0.355948E+10 0.159700E+10 0.196248E+10 0.00 0.00
October 0.368710E+10 0.202454E+10 0.333449E+10 0.151131E+10 0.182319E+10 0.00 0.00
November 0.158436E+10 0.288022E+10 0.199561E+10 0.766333E+09 0.122927E+10 0.00 0.00
December 0.107026E+10 0.385287E+10 0.160651E+10 0.754320E+09 0.852193E+09 0.00 0.00
               
Annual Sum or Average 0.440922E+11 0.259878E+11 0.396432E+11 0.165838E+11 0.230594E+11 0.00 0.00
Minimum of Months 0.995293E+09 0.426451E+09 0.160651E+10 0.655155E+09 0.852193E+09 0.00 0.00
Maximum of Months 0.697712E+10 0.412353E+10 0.493175E+10 0.222373E+10 0.282470E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.592763E+10 0.602459E+10 0.607052E+10 0.397502E+10 0.209550E+10 0.00 0.00
February 0.716508E+10 0.558791E+10 0.723196E+10 0.478697E+10 0.244499E+10 0.00 0.00
March 0.758500E+10 0.464729E+10 0.722365E+10 0.400925E+10 0.321440E+10 0.00 0.00
April 0.588605E+10 0.339279E+10 0.542448E+10 0.214500E+10 0.327948E+10 0.00 0.00
May 0.567815E+10 0.224355E+10 0.491221E+10 0.102461E+10 0.388760E+10 0.00 0.00
June 0.601347E+10 0.117655E+10 0.446126E+10 0.681949E+09 0.377931E+10 0.00 0.00
July 0.726228E+10 0.654267E+09 0.483217E+10 0.839346E+09 0.399282E+10 0.00 0.00
August 0.975784E+10 0.933769E+09 0.645283E+10 0.239346E+10 0.405937E+10 0.00 0.00
September 0.903235E+10 0.175741E+10 0.677560E+10 0.350462E+10 0.327098E+10 0.00 0.00
October 0.118678E+11 0.326009E+10 0.959139E+10 0.601449E+10 0.357690E+10 0.00 0.00
November 0.678975E+10 0.442809E+10 0.643627E+10 0.386529E+10 0.257098E+10 0.00 0.00
December 0.667897E+10 0.566544E+10 0.657953E+10 0.467103E+10 0.190850E+10 0.00 0.00
               
Annual Sum or Average 0.896444E+11 0.397718E+11 0.759919E+11 0.379110E+11 0.380808E+11 0.00 0.00
Minimum of Months 0.567815E+10 0.654267E+09 0.446126E+10 0.681949E+09 0.190850E+10 0.00 0.00
Maximum of Months 0.118678E+11 0.602459E+10 0.959139E+10 0.601449E+10 0.405937E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.981058E+09 0.431862E+10 0.161325E+10 0.660794E+09 0.952460E+09 0.00 0.00
February 0.145286E+10 0.403810E+10 0.214875E+10 0.943739E+09 0.120501E+10 0.00 0.00
March 0.312394E+10 0.310251E+10 0.351285E+10 0.162178E+10 0.189106E+10 0.00 0.00
April 0.375447E+10 0.225629E+10 0.371553E+10 0.158978E+10 0.212575E+10 0.00 0.00
May 0.516310E+10 0.151428E+10 0.447248E+10 0.169848E+10 0.277401E+10 0.00 0.00
June 0.621595E+10 0.836751E+09 0.473710E+10 0.191061E+10 0.282649E+10 0.00 0.00
July 0.648653E+10 0.498604E+09 0.458443E+10 0.172636E+10 0.285807E+10 0.00 0.00
August 0.718523E+10 0.674563E+09 0.507163E+10 0.234783E+10 0.272380E+10 0.00 0.00
September 0.438777E+10 0.117576E+10 0.348431E+10 0.152263E+10 0.196167E+10 0.00 0.00
October 0.401039E+10 0.216842E+10 0.356958E+10 0.173580E+10 0.183378E+10 0.00 0.00
November 0.107523E+10 0.305325E+10 0.162219E+10 0.468824E+09 0.115336E+10 0.00 0.00
December 0.923540E+09 0.408734E+10 0.149100E+10 0.645160E+09 0.845840E+09 0.00 0.00
               
Annual Sum or Average 0.447601E+11 0.277245E+11 0.400231E+11 0.168718E+11 0.231513E+11 0.00 0.00
Minimum of Months 0.923540E+09 0.498604E+09 0.149100E+10 0.468824E+09 0.845840E+09 0.00 0.00
Maximum of Months 0.718523E+10 0.431862E+10 0.507163E+10 0.234783E+10 0.285807E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 80854585.16 0.636884E+10 0.117345E+10 0.00 0.117345E+10 0.00 0.00
February 0.154306E+09 0.594000E+10 0.145042E+10 0.00 0.145042E+10 0.00 0.00
March 0.846491E+09 0.429507E+10 0.222687E+10 0.00 0.222687E+10 0.00 0.00
April 0.170435E+10 0.295970E+10 0.258849E+10 7362461.72 0.258113E+10 0.00 0.00
May 0.334807E+10 0.195602E+10 0.354857E+10 0.118240E+09 0.343033E+10 0.00 0.00
June 0.449119E+10 0.107934E+10 0.364182E+10 0.195690E+09 0.344613E+10 0.00 0.00
July 0.516703E+10 0.644501E+09 0.363678E+10 0.131518E+09 0.350527E+10 0.00 0.00
August 0.453986E+10 0.852765E+09 0.322202E+10 38346539.14 0.318367E+10 0.00 0.00
September 0.253696E+10 0.157391E+10 0.235051E+10 440156.01 0.235007E+10 0.00 0.00
October 0.164263E+10 0.282977E+10 0.210201E+10 0.00 0.210201E+10 0.00 0.00
November 0.464116E+09 0.416592E+10 0.142680E+10 0.00 0.142680E+10 0.00 0.00
December 67020251.34 0.579564E+10 0.102356E+10 0.00 0.102356E+10 0.00 0.00
               
Annual Sum or Average 0.250429E+11 0.384615E+11 0.283913E+11 0.491598E+09 0.278997E+11 0.00 0.00
Minimum of Months 67020251.34 0.644501E+09 0.102356E+10 0.00 0.102356E+10 0.00 0.00
Maximum of Months 0.516703E+10 0.636884E+10 0.364182E+10 0.195690E+09 0.350527E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.101695E+10 0.394835E+10 0.163413E+10 0.655155E+09 0.978978E+09 0.00 0.00
February 0.162812E+10 0.357134E+10 0.228894E+10 0.106779E+10 0.122115E+10 0.00 0.00
March 0.285632E+10 0.278651E+10 0.323283E+10 0.137495E+10 0.185789E+10 0.00 0.00
April 0.382922E+10 0.195473E+10 0.375448E+10 0.164458E+10 0.210990E+10 0.00 0.00
May 0.543934E+10 0.134812E+10 0.470517E+10 0.188047E+10 0.282470E+10 0.00 0.00
June 0.549152E+10 0.744735E+09 0.422003E+10 0.152762E+10 0.269241E+10 0.00 0.00
July 0.619180E+10 0.442735E+09 0.437979E+10 0.158056E+10 0.279923E+10 0.00 0.00
August 0.694113E+10 0.586690E+09 0.493175E+10 0.222373E+10 0.270802E+10 0.00 0.00
September 0.443757E+10 0.104214E+10 0.355948E+10 0.159700E+10 0.196248E+10 0.00 0.00
October 0.374056E+10 0.188108E+10 0.333449E+10 0.151131E+10 0.182319E+10 0.00 0.00
November 0.165989E+10 0.262813E+10 0.199561E+10 0.766333E+09 0.122927E+10 0.00 0.00
December 0.111531E+10 0.356505E+10 0.160651E+10 0.754320E+09 0.852193E+09 0.00 0.00
               
Annual Sum or Average 0.443477E+11 0.244996E+11 0.396432E+11 0.165838E+11 0.230594E+11 0.00 0.00
Minimum of Months 0.101695E+10 0.442735E+09 0.160651E+10 0.655155E+09 0.852193E+09 0.00 0.00
Maximum of Months 0.694113E+10 0.394835E+10 0.493175E+10 0.222373E+10 0.282470E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.598031E+10 0.572473E+10 0.607052E+10 0.397502E+10 0.209550E+10 0.00 0.00
February 0.725339E+10 0.525095E+10 0.723196E+10 0.478697E+10 0.244499E+10 0.00 0.00
March 0.766478E+10 0.429313E+10 0.722365E+10 0.400925E+10 0.321440E+10 0.00 0.00
April 0.596249E+10 0.314103E+10 0.542448E+10 0.214500E+10 0.327948E+10 0.00 0.00
May 0.570358E+10 0.213595E+10 0.491221E+10 0.102461E+10 0.388760E+10 0.00 0.00
June 0.597437E+10 0.116920E+10 0.446126E+10 0.681949E+09 0.377931E+10 0.00 0.00
July 0.720020E+10 0.674780E+09 0.483217E+10 0.839346E+09 0.399282E+10 0.00 0.00
August 0.970449E+10 0.942462E+09 0.645283E+10 0.239346E+10 0.405937E+10 0.00 0.00
September 0.902430E+10 0.169817E+10 0.677560E+10 0.350462E+10 0.327098E+10 0.00 0.00
October 0.119171E+11 0.305075E+10 0.959139E+10 0.601449E+10 0.357690E+10 0.00 0.00
November 0.691356E+10 0.402546E+10 0.643627E+10 0.386529E+10 0.257098E+10 0.00 0.00
December 0.679602E+10 0.520976E+10 0.657953E+10 0.467103E+10 0.190850E+10 0.00 0.00
               
Annual Sum or Average 0.900945E+11 0.373164E+11 0.759919E+11 0.379110E+11 0.380808E+11 0.00 0.00
Minimum of Months 0.570358E+10 0.674780E+09 0.446126E+10 0.681949E+09 0.190850E+10 0.00 0.00
Maximum of Months 0.119171E+11 0.572473E+10 0.959139E+10 0.601449E+10 0.405937E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.996651E+09 0.412991E+10 0.161325E+10 0.660794E+09 0.952460E+09 0.00 0.00
February 0.147453E+10 0.384409E+10 0.214875E+10 0.943739E+09 0.120501E+10 0.00 0.00
March 0.316542E+10 0.289853E+10 0.351285E+10 0.162178E+10 0.189106E+10 0.00 0.00
April 0.379698E+10 0.210896E+10 0.371553E+10 0.158978E+10 0.212575E+10 0.00 0.00
May 0.517642E+10 0.145177E+10 0.447248E+10 0.169848E+10 0.277401E+10 0.00 0.00
June 0.618588E+10 0.832104E+09 0.473710E+10 0.191061E+10 0.282649E+10 0.00 0.00
July 0.644498E+10 0.508780E+09 0.458443E+10 0.172636E+10 0.285807E+10 0.00 0.00
August 0.715133E+10 0.678803E+09 0.507163E+10 0.234783E+10 0.272380E+10 0.00 0.00
September 0.438768E+10 0.113491E+10 0.348431E+10 0.152263E+10 0.196167E+10 0.00 0.00
October 0.405252E+10 0.202676E+10 0.356958E+10 0.173580E+10 0.183378E+10 0.00 0.00
November 0.112787E+10 0.281211E+10 0.162219E+10 0.468824E+09 0.115336E+10 0.00 0.00
December 0.952442E+09 0.381043E+10 0.149100E+10 0.645160E+09 0.845840E+09 0.00 0.00
               
Annual Sum or Average 0.449127E+11 0.262372E+11 0.400231E+11 0.168718E+11 0.231513E+11 0.00 0.00
Minimum of Months 0.952442E+09 0.508780E+09 0.149100E+10 0.468824E+09 0.845840E+09 0.00 0.00
Maximum of Months 0.715133E+10 0.412991E+10 0.507163E+10 0.234783E+10 0.285807E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 1.17 -0.7 -4.4 5.65 -10.4 36.91 88.07 0.05
February -0.2 -2.6 -7.5 5.07 -13.4 46.98 136.68 0.04
March 5.59 3.43 0.29 5.58 -4.1 68.24 153.73 0.03
April 10.94 8.00 4.75 4.99 0.53 82.64 161.98 0.05
May 16.05 12.31 9.14 4.42 7.77 109.28 173.60 0.03
June 21.71 18.08 15.84 4.92 13.23 112.36 186.51 0.01
July 25.05 21.76 20.26 4.06 17.39 114.46 172.96 0.02
August 24.79 19.84 17.14 4.19 14.42 95.56 226.16 0.00
September 19.96 15.96 13.24 3.91 10.59 73.65 166.08 0.03
October 14.02 11.03 7.95 4.86 2.64 61.34 179.75 0.00
November 7.31 4.98 2.14 5.60 -4.0 48.23 90.71 0.03
December 3.33 0.91 -2.8 5.64 -8.5 30.23 98.59 0.04
                 
Annual Sum or Average 12.55 9.49 6.43 4.91 2.28 73.48 153.05 0.03
Minimum of Months -0.2 -2.6 -7.5 3.91 -13.4 30.23 88.07 0.00
Maximum of Months 25.05 21.76 20.26 5.65 17.39 114.46 226.16 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 12.20 24-JAN-12:20 11.81 11.50 1.00 8.15 93.67 0.00
February 10.00 20-FEB-11:00 4.36 -3.3 2.60 -3.9 151.50 540.00
March 22.20 27-MAR-15:00 16.34 12.80 6.70 11.65 136.50 590.00
April 26.70 07-APR-12:00 16.40 9.40 6.20 11.65 179.00 713.50
May 30.00 30-MAY-12:00 18.00 10.60 5.20 17.39 233.50 730.00
June 36.70 19-JUN-11:00 24.28 19.40 5.20 24.83 185.00 771.50
July 33.90 07-JUL-11:00 23.31 18.90 3.60 23.82 331.00 570.00
August 33.90 24-AUG-14:00 20.23 12.80 8.80 21.61 240.00 432.00
September 31.10 01-SEP-13:00 17.34 8.30 4.60 18.46 182.00 662.00
October 25.00 04-OCT-12:00 18.54 15.00 5.20 11.27 171.50 695.00
November 17.80 04-NOV-12:20 12.57 8.50 3.60 6.15 182.50 595.67
December 12.20 17-DEC-12:20 4.65 -6.1 4.27 -4.7 53.17 801.67
                 
Annual Sum or Average                
Minimum of Months 10.00   4.36 -6.1 1.00 -4.7 53.17 0.00
Maximum of Months 36.70   24.28 19.40 8.80 24.83 331.00 801.67



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -12.2 02-JAN-04:00 -13.6 -19.4 2.60 -30.7 0.00 0.00
February -13.9 06-FEB-02:00 -15.3 -22.8 7.20 -34.1 0.00 0.00
March -5.0 23-MAR-03:00 -7.6 -14.4 1.50 -23.9 0.00 0.00
April 2.20 01-APR-03:00 0.57 -1.7 3.10 -6.6 0.00 0.00
May 6.10 01-MAY-04:00 4.33 2.20 3.60 -9.7 25.50 0.00
June 13.30 03-JUN-02:00 9.35 5.60 4.60 -2.1 0.00 0.00
July 18.30 02-JUL-02:00 17.54 17.20 0.00 5.33 0.00 0.00
August 15.00 08-AUG-04:00 12.47 10.60 3.10 3.06 0.00 0.00
September 10.00 24-SEP-05:00 8.56 7.20 2.60 -3.4 18.50 158.50
October 2.20 09-OCT-03:00 1.71 1.10 0.00 -13.7 0.00 0.00
November -4.4 24-NOV-05:00 -6.2 -10.0 1.50 -19.7 0.00 0.00
December -8.3 31-DEC-23:00 -10.6 -18.9 9.30 -26.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -13.9   -15.3 -22.8 0.00 -34.1 0.00 0.00
Maximum of Months 18.30   17.54 17.20 9.30 5.33 25.50 158.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.93 24-JAN-11:00 12.20 11.70 1.50 8.15 103.00 0.00
February 6.67 28-FEB-09:00 7.20 6.10 4.10 2.01 101.50 0.00
March 16.99 27-MAR-12:00 20.60 15.00 3.60 10.50 295.50 565.50
April 17.70 09-APR-10:00 21.70 15.60 4.10 14.84 244.50 281.50
May 20.43 31-MAY-12:00 26.10 17.80 4.10 17.03 214.00 772.00
June 24.96 15-JUN-11:00 31.10 22.80 5.20 22.47 380.00 460.00
July 26.10 08-JUL-11:00 32.20 23.90 5.20 22.47 354.00 501.50
August 25.84 03-AUG-13:00 30.00 24.40 6.20 20.57 298.00 500.00
September 23.57 07-SEP-13:00 27.20 22.20 6.20 15.02 148.00 730.50
October 19.76 25-OCT-10:00 25.00 17.20 7.70 14.84 189.00 308.50
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.26 25-DEC-08:00 10.60 10.00 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.67   7.20 6.10 1.50 2.01 43.00 0.00
Maximum of Months 26.10   32.20 24.40 8.20 22.47 380.00 772.00



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 11.70 18-JAN-15:00 12.20 11.93 14.90 8.15 22.00 2.00
February 6.10 28-FEB-10:20 7.03 6.58 3.43 1.87 109.83 0.00
March 15.00 27-MAR-12:20 18.00 16.18 3.93 10.11 271.83 611.17
April 15.60 09-APR-10:00 21.70 17.70 4.10 14.84 244.50 281.50
May 18.00 18-MAY-09:00 18.00 18.00 4.60 15.39 265.50 12.00
June 22.80 15-JUN-11:00 31.10 24.96 5.20 22.47 380.00 460.00
July 24.40 09-JUL-07:00 27.20 25.17 2.10 15.39 195.00 504.00
August 25.00 03-AUG-19:00 26.10 25.32 5.70 19.35 0.00 0.00
September 22.20 07-SEP-13:00 27.20 23.57 6.20 15.02 148.00 730.50
October 18.30 05-OCT-18:00 19.40 18.62 7.70 6.55 0.00 0.00
November 16.10 10-NOV-07:00 16.10 16.10 8.20 12.98 71.50 0.00
December 10.00 25-DEC-08:00 10.60 10.26 3.60 6.15 43.00 0.00
                 
Annual Sum or Average                
Minimum of Months 6.10   7.03 6.58 2.10 1.87 0.00 0.00
Maximum of Months 25.00   31.10 25.32 14.90 22.47 380.00 730.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 10.03 13.58 0.00
February 18.00 13.00 16.00 9.54 21.42 0.00
March 18.00 13.00 16.00 10.65 30.29 0.00
April 18.00 13.00 16.00 13.15 37.02 0.00
May 18.00 13.00 16.00 16.36 45.86 0.00
June 18.00 13.00 16.00 19.42 49.74 0.00
July 18.00 13.00 16.00 21.50 48.12 0.00
August 18.00 13.00 16.00 22.05 49.54 0.00
September 18.00 13.00 16.00 20.89 34.71 0.00
October 18.00 13.00 16.00 18.36 29.93 0.00
November 18.00 13.00 16.00 15.14 17.00 0.00
December 18.00 13.00 16.00 12.10 12.41 0.00
             
Annual Sum or Average 18.00 13.00 16.00 15.80 32.53 0.00
Minimum of Months 18.00 13.00 16.00 9.54 12.41 0.00
Maximum of Months 18.00 13.00 16.00 22.05 49.74 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.400213E+11 -0.389835E+11 0.00 0.00 744.00 0.00 -0.103779E+10 58.98 0.00 0.00
February 0.367126E+11 -0.357798E+11 0.00 0.00 672.00 0.00 -932800943.3 58.97 0.00 0.00
March 0.421638E+11 -0.411338E+11 0.00 0.00 744.00 0.00 -0.102991E+10 58.97 0.00 0.00
April 0.363754E+11 -0.353826E+11 0.00 0.00 720.00 0.00 -992821672.5 58.98 0.00 0.00
May 0.362000E+11 -0.351743E+11 0.00 0.00 744.00 0.00 -0.102565E+10 58.97 0.00 0.00
June 0.333262E+11 -0.323337E+11 0.00 0.00 720.00 0.00 -992485768.9 58.98 0.00 0.00
July 0.301402E+11 -0.291203E+11 0.00 0.00 744.00 0.00 -0.101988E+10 58.98 0.00 0.00
August 0.324649E+11 -0.314413E+11 0.00 0.00 744.00 0.00 -0.102367E+10 58.98 0.00 0.00
September 0.304119E+11 -0.294234E+11 0.00 0.00 720.00 0.00 -988467184.3 58.97 0.00 0.00
October 0.333860E+11 -0.323660E+11 0.00 0.00 744.00 0.00 -0.101998E+10 58.97 0.00 0.00
November 0.352379E+11 -0.342486E+11 0.00 0.00 720.00 0.00 -989280199.0 58.98 0.00 0.00
December 0.374546E+11 -0.364306E+11 0.00 0.00 744.00 0.00 -0.102401E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.423895E+12 -0.411818E+12 0.00 0.00 8760.00 0.00 -0.120768E+11 58.97 0.00 0.00
Minimum of Months 0.301402E+11 -0.411338E+11 0.00 0.00 672.00 0.00 -0.103779E+10 58.97 0.00 0.00
Maximum of Months 0.421638E+11 -0.291203E+11 0.00 0.00 744.00 0.00 -932800943.3 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.64 0.61 01-JAN-07:49 5412.94 32.85 169.00 226.00 2818.79 33.17 182.17 185.33
February 216.00 0.63 0.61 01-FEB-07:40 8003.29 36.15 203.17 249.83 1659.65 27.10 179.33 224.50
March 275.00 0.64 0.61 01-MAR-06:00 2858.04 22.65 90.17 309.50 1204.34 21.16 149.00 255.00
April 261.17 0.63 0.61 01-APR-06:19 1624.56 17.47 0.00 328.17 936.92 20.45 109.33 278.33
May 372.00 0.64 0.61 01-MAY-05:40 1432.11 17.34 0.00 380.17 788.81 20.25 157.33 318.50
June 351.83 0.63 0.61 01-JUN-05:19 1363.28 17.26 0.00 368.33 763.77 20.26 135.00 318.17
July 365.17 0.63 0.61 01-JUL-05:30 1507.66 17.58 0.00 375.33 824.66 20.57 176.67 323.00
August 389.17 0.64 0.61 01-AUG-05:00 1658.02 17.58 0.00 360.50 940.20 20.53 185.50 320.33
September 285.33 0.63 0.61 01-SEP-06:10 3140.82 19.98 29.50 312.33 1109.81 20.85 146.83 272.50
October 305.50 0.63 0.61 01-OCT-14:39 8762.56 35.02 278.50 299.17 1558.74 22.93 241.17 276.33
November 240.83 0.63 0.61 01-NOV-06:00 5455.65 33.83 217.00 248.83 1805.64 28.52 213.83 222.50
December 211.17 0.64 0.61 01-DEC-07:40 5060.23 33.64 178.83 230.17 4634.15 37.63 197.67 198.17
                         
Annual Sum or Average 3472.67 0.63     3508.15 23.78 1166.17 3688.33 1420.29 23.49 2073.83 3192.67
Minimum of Months 199.50 0.63 0.61   1363.28 17.26 0.00 226.00 763.77 20.25 109.33 185.33
Maximum of Months 389.17 0.64 0.61   8762.56 36.15 278.50 380.17 4634.15 37.63 241.17 323.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.61 01-JAN-07:49 1616.17 19.15 60.33 202.00 856.60 18.50 40.00 136.00
February 216.00 0.64 0.61 01-FEB-07:40 2184.95 19.32 61.33 229.67 1339.44 20.64 58.50 177.50
March 275.00 0.65 0.61 01-MAR-06:49 2303.55 17.27 56.67 300.67 1320.74 17.15 38.50 227.33
April 261.17 0.63 0.61 01-APR-05:00 3207.42 15.80 38.83 326.33 1184.93 14.54 0.00 273.00
May 372.00 0.64 0.61 01-MAY-05:40 2523.34 13.38 0.00 382.83 1387.95 14.60 0.00 323.50
June 351.83 0.63 0.61 01-JUN-04:00 2318.97 13.36 0.00 372.83 1263.45 14.63 0.00 333.50
July 365.17 0.63 0.61 01-JUL-04:00 2324.94 13.78 1.83 382.00 1268.28 14.94 0.00 334.17
August 389.17 0.64 0.61 01-AUG-05:40 3200.07 16.02 57.67 359.67 1287.99 14.81 0.00 327.00
September 285.33 0.64 0.61 01-SEP-05:49 2645.30 17.54 61.33 308.00 1158.05 15.20 5.50 260.33
October 305.50 0.64 0.61 01-OCT-14:39 2384.23 18.88 74.17 279.83 1283.71 18.73 50.17 240.00
November 240.83 0.64 0.61 01-NOV-06:49 1511.88 17.82 52.00 230.67 830.60 18.82 46.17 174.50
December 211.17 0.66 0.61 01-DEC-07:40 1493.45 18.86 64.17 196.83 898.54 20.24 59.00 123.17
                         
Annual Sum or Average 3472.67 0.64     2383.50 16.37 528.33 3571.33 1200.94 16.51 297.83 2930.00
Minimum of Months 199.50 0.63 0.61   1493.45 13.36 0.00 196.83 830.60 14.54 0.00 123.17
Maximum of Months 389.17 0.66 0.61   3207.42 19.32 74.17 382.83 1387.95 20.64 59.00 334.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.66 0.61 01-JAN-08:30 497.40 0.00 0.00 175.67 303.69 0.00 0.00 71.67
February 216.00 0.65 0.61 01-FEB-08:30 535.18 0.00 0.00 208.33 348.56 0.00 0.00 117.50
March 275.00 0.65 0.61 01-MAR-07:10 715.40 0.00 0.00 296.33 445.15 0.00 0.00 198.00
April 261.17 0.63 0.61 01-APR-06:19 805.23 0.00 0.00 332.67 502.72 0.00 0.00 256.17
May 372.00 0.63 0.61 01-MAY-05:40 1048.62 0.00 0.00 393.83 597.21 0.00 0.00 332.00
June 351.83 0.62 0.61 01-JUN-04:00 1177.00 0.00 0.00 390.83 646.75 0.00 0.00 351.50
July 365.17 0.62 0.61 01-JUL-04:00 1164.95 0.00 0.00 395.83 645.43 0.00 0.00 348.00
August 389.17 0.63 0.61 01-AUG-05:49 952.05 0.00 0.00 371.50 571.82 0.00 0.00 329.67
September 285.33 0.64 0.61 01-SEP-06:10 736.72 0.00 0.00 304.50 465.23 0.00 0.00 228.00
October 305.50 0.64 0.61 01-OCT-14:39 663.30 0.00 0.00 275.67 430.43 0.00 0.00 206.67
November 240.83 0.65 0.61 01-NOV-07:19 557.23 0.00 0.00 213.67 332.28 0.00 0.00 107.67
December 211.17 0.68 0.61 01-DEC-08:20 398.81 0.00 0.00 155.83 252.27 0.00 0.00 34.67
                         
Annual Sum or Average 3472.67 0.64     821.63 0.00 0.00 3514.67 488.11 0.00 0.00 2581.50
Minimum of Months 199.50 0.62 0.61   398.81 0.00 0.00 155.83 252.27 0.00 0.00 34.67
Maximum of Months 389.17 0.68 0.61   1177.00 0.00 0.00 395.83 646.75 0.00 0.00 351.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.61 01-JAN-08:30 1547.48 19.01 57.17 205.00 902.44 20.31 52.17 138.00
February 216.00 0.64 0.61 01-FEB-08:39 1790.46 18.80 56.17 228.83 910.04 18.30 36.17 173.50
March 275.00 0.64 0.61 01-MAR-07:19 2483.05 18.35 69.67 304.50 1459.11 18.06 47.50 237.33
April 261.17 0.64 0.61 01-APR-07:19 3016.20 15.58 36.00 324.83 1154.12 14.50 0.00 275.50
May 372.00 0.63 0.61 01-MAY-05:00 2783.95 13.44 0.00 382.83 1205.73 14.77 1.83 325.67
June 351.83 0.63 0.61 01-JUN-05:40 2620.36 13.55 0.00 378.00 1431.61 16.94 43.00 323.17
July 365.17 0.63 0.61 01-JUL-05:40 2464.92 13.89 3.50 382.00 1329.62 14.98 0.00 330.00
August 389.17 0.64 0.61 01-AUG-05:00 3261.84 15.87 54.33 360.17 1385.52 14.81 0.00 327.83
September 285.33 0.64 0.61 01-SEP-06:30 2514.00 16.34 45.67 307.67 1354.43 15.32 5.50 261.00
October 305.50 0.63 0.61 01-OCT-14:39 2672.05 19.63 83.50 292.83 1139.83 19.22 53.17 256.00
November 240.83 0.64 0.61 01-NOV-07:19 1353.31 18.87 68.00 233.33 700.68 18.31 43.50 170.17
December 211.17 0.66 0.61 01-DEC-08:30 1273.61 19.09 67.33 198.50 677.65 18.21 43.67 125.67
                         
Annual Sum or Average 3472.67 0.64     2425.11 16.48 541.33 3598.50 1181.44 16.69 326.50 2943.83
Minimum of Months 199.50 0.63 0.61   1273.61 13.44 0.00 198.50 677.65 14.50 0.00 125.67
Maximum of Months 389.17 0.66 0.61   3261.84 19.63 83.50 382.83 1459.11 20.31 53.17 330.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.64 0.61 01-JAN-07:00 5366.84 31.74 169.00 224.50 2858.54 31.31 143.83 186.33
February 216.00 0.63 0.61 01-FEB-07:40 7968.37 35.58 202.50 248.50 1709.88 23.29 80.00 225.50
March 275.00 0.64 0.61 01-MAR-06:00 2869.51 18.16 89.67 311.67 1248.86 16.89 4.33 258.33
April 261.17 0.64 0.61 01-APR-06:19 1603.13 11.66 0.00 326.17 970.84 16.52 0.00 279.83
May 372.00 0.64 0.61 01-MAY-05:40 1404.22 11.71 0.00 378.83 812.95 16.40 0.00 325.00
June 351.83 0.63 0.61 01-JUN-05:30 1337.01 11.68 0.00 366.33 786.80 16.45 0.00 321.17
July 365.17 0.63 0.61 01-JUL-05:30 1476.18 11.86 0.00 373.50 848.84 16.63 0.00 324.67
August 389.17 0.64 0.61 01-AUG-05:00 1631.40 12.04 0.00 358.50 971.69 16.78 0.00 322.33
September 285.33 0.64 0.61 01-SEP-06:10 3115.37 14.58 29.50 311.00 1151.37 16.66 0.00 274.00
October 305.50 0.63 0.61 01-OCT-14:39 8720.04 34.31 278.17 298.67 1683.09 18.70 19.33 277.33
November 240.83 0.63 0.61 01-NOV-06:00 5384.43 32.62 213.50 247.50 2227.31 27.48 136.83 224.00
December 211.17 0.64 0.61 01-DEC-07:40 4834.34 29.38 155.00 227.83 4670.08 36.83 195.67 199.17
                         
Annual Sum or Average 3472.67 0.63     3466.17 19.65 1137.33 3673.00 1488.55 20.04 580.00 3217.67
Minimum of Months 199.50 0.63 0.61   1337.01 11.66 0.00 224.50 786.80 16.40 0.00 186.33
Maximum of Months 389.17 0.64 0.61   8720.04 35.58 278.17 378.83 4670.08 36.83 195.67 325.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.61 01-JAN-07:49 1609.90 17.20 60.33 201.33 875.16 16.44 40.00 138.67
February 216.00 0.64 0.61 01-FEB-07:40 2180.36 17.15 61.33 228.83 1363.99 18.84 58.50 181.33
March 275.00 0.65 0.61 01-MAR-06:49 2306.52 14.97 56.83 300.00 1349.76 15.10 38.50 231.17
April 261.17 0.63 0.61 01-APR-06:10 3210.86 12.98 38.83 324.83 1219.34 11.97 0.00 276.83
May 372.00 0.64 0.61 01-MAY-05:40 2497.31 10.00 0.00 382.00 1420.07 12.23 0.00 328.17
June 351.83 0.63 0.61 01-JUN-04:00 2212.92 10.01 0.00 372.33 1295.48 12.31 0.00 336.00
July 365.17 0.63 0.61 01-JUL-04:00 2306.18 10.39 1.83 381.33 1300.94 12.56 0.00 337.83
August 389.17 0.64 0.61 01-AUG-05:40 3193.06 13.31 57.67 359.33 1321.63 12.35 0.00 330.67
September 285.33 0.64 0.61 01-SEP-05:49 2650.70 15.09 61.33 306.00 1190.93 12.65 5.50 263.50
October 305.50 0.64 0.61 01-OCT-14:39 2376.94 16.65 74.17 279.17 1312.93 16.58 50.17 243.67
November 240.83 0.64 0.61 01-NOV-06:49 1504.57 15.35 52.00 229.50 850.71 16.64 46.17 177.50
December 211.17 0.66 0.61 01-DEC-07:40 1491.21 16.87 64.17 196.33 915.43 18.44 59.33 127.67
                         
Annual Sum or Average 3472.67 0.64     2366.22 13.68 528.50 3561.00 1230.01 14.25 298.17 2973.00
Minimum of Months 199.50 0.63 0.61   1491.21 10.00 0.00 196.33 850.71 11.97 0.00 127.67
Maximum of Months 389.17 0.66 0.61   3210.86 17.20 74.17 382.00 1420.07 18.84 59.33 337.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.66 0.61 01-JAN-08:30 485.63 0.00 0.00 169.83 311.14 0.00 0.00 77.50
February 216.00 0.65 0.61 01-FEB-08:30 524.38 0.00 0.00 205.50 357.73 0.00 0.00 123.00
March 275.00 0.65 0.61 01-MAR-07:10 702.31 0.00 0.00 294.83 457.82 0.00 0.00 202.00
April 261.17 0.63 0.61 01-APR-06:19 792.63 0.00 0.00 331.00 517.75 0.00 0.00 262.83
May 372.00 0.63 0.61 01-MAY-05:40 1029.81 0.00 0.00 392.50 614.94 0.00 0.00 335.83
June 351.83 0.63 0.61 01-JUN-04:00 1158.39 0.00 0.00 388.83 673.49 0.00 0.00 357.83
July 365.17 0.62 0.61 01-JUL-04:00 1145.11 0.00 0.00 393.50 664.00 0.00 0.00 350.17
August 389.17 0.63 0.61 01-AUG-05:49 936.52 0.00 0.00 370.33 588.45 0.00 0.00 332.17
September 285.33 0.64 0.61 01-SEP-06:10 724.28 0.00 0.00 302.17 478.73 0.00 0.00 233.67
October 305.50 0.64 0.61 01-OCT-14:39 649.56 0.00 0.00 273.50 441.55 0.00 0.00 211.50
November 240.83 0.65 0.61 01-NOV-07:19 544.44 0.00 0.00 210.17 340.65 0.00 0.00 113.67
December 211.17 0.68 0.61 01-DEC-08:30 389.14 0.00 0.00 150.17 258.23 0.00 0.00 41.83
                         
Annual Sum or Average 3472.67 0.64     806.86 0.00 0.00 3482.33 502.70 0.00 0.00 2642.00
Minimum of Months 199.50 0.62 0.61   389.14 0.00 0.00 150.17 258.23 0.00 0.00 41.83
Maximum of Months 389.17 0.68 0.61   1158.39 0.00 0.00 393.50 673.49 0.00 0.00 357.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.61 01-JAN-08:30 1529.81 16.85 56.17 203.50 920.45 18.42 52.33 141.00
February 216.00 0.64 0.61 01-FEB-08:39 1568.81 14.13 37.00 228.00 934.77 16.11 36.17 178.00
March 275.00 0.64 0.61 01-MAR-07:19 2480.50 16.04 68.67 303.83 1489.52 16.01 47.67 239.33
April 261.17 0.64 0.61 01-APR-07:19 2805.74 12.74 36.00 324.17 1187.68 11.96 0.00 278.83
May 372.00 0.63 0.61 01-MAY-05:00 2766.14 10.05 0.00 382.50 1237.24 12.40 1.83 330.67
June 351.83 0.63 0.61 01-JUN-05:40 2597.59 10.08 0.00 377.33 1467.95 14.96 43.00 326.33
July 365.17 0.63 0.61 01-JUL-05:40 2444.31 10.48 3.50 381.00 1363.34 12.58 0.00 333.83
August 389.17 0.64 0.61 01-AUG-05:00 3255.84 13.11 54.33 359.83 1419.94 12.34 0.00 329.50
September 285.33 0.64 0.61 01-SEP-06:30 2517.22 13.64 45.67 305.67 1385.53 12.79 5.50 264.67
October 305.50 0.63 0.61 01-OCT-14:39 2668.25 17.42 83.50 292.17 1169.29 17.05 53.17 258.00
November 240.83 0.64 0.61 01-NOV-07:19 1332.24 16.40 64.83 232.83 717.63 16.11 43.50 173.33
December 211.17 0.66 0.61 01-DEC-08:30 1101.46 14.43 45.67 196.67 693.98 16.17 43.67 129.67
                         
Annual Sum or Average 3472.67 0.64     2375.23 13.41 495.33 3587.50 1210.72 14.43 326.83 2983.17
Minimum of Months 199.50 0.63 0.61   1101.46 10.05 0.00 196.67 693.98 11.96 0.00 129.67
Maximum of Months 389.17 0.66 0.61   3255.84 17.42 83.50 382.50 1489.52 18.42 53.17 333.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.64 0.61 01-JAN-07:00 5365.46 31.72 169.00 224.50 2859.86 31.30 143.83 186.33
February 216.00 0.63 0.61 01-FEB-07:40 7967.46 35.56 202.50 248.50 1711.28 23.27 80.00 225.83
March 275.00 0.64 0.61 01-MAR-06:00 2870.01 18.13 89.67 311.67 1250.21 16.87 4.33 258.50
April 261.17 0.64 0.61 01-APR-06:19 1603.79 11.62 0.00 326.17 971.85 16.51 0.00 279.83
May 372.00 0.64 0.61 01-MAY-05:40 1404.91 11.67 0.00 379.00 813.90 16.38 0.00 325.17
June 351.83 0.63 0.61 01-JUN-05:30 1337.60 11.64 0.00 366.33 787.66 16.43 0.00 321.50
July 365.17 0.63 0.61 01-JUL-05:30 1476.94 11.82 0.00 373.67 849.83 16.61 0.00 325.17
August 389.17 0.64 0.61 01-AUG-05:00 1632.11 12.00 0.00 358.50 972.73 16.76 0.00 322.33
September 285.33 0.64 0.61 01-SEP-06:10 3116.04 14.54 29.50 311.00 1152.60 16.64 0.00 274.00
October 305.50 0.63 0.61 01-OCT-14:39 8719.66 34.30 278.17 298.67 1684.75 18.68 19.33 277.33
November 240.83 0.63 0.61 01-NOV-06:00 5383.21 32.61 213.50 247.50 2228.86 27.47 136.83 224.00
December 211.17 0.64 0.61 01-DEC-07:40 4804.08 28.97 152.00 227.67 4671.09 36.83 195.67 199.17
                         
Annual Sum or Average 3472.67 0.63     3464.52 19.60 1134.33 3673.17 1489.72 20.02 580.00 3219.17
Minimum of Months 199.50 0.63 0.61   1337.60 11.62 0.00 224.50 787.66 16.38 0.00 186.33
Maximum of Months 389.17 0.64 0.61   8719.66 35.56 278.17 379.00 4671.09 36.83 195.67 325.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.61 01-JAN-07:49 1609.46 17.19 60.33 201.33 875.71 16.43 40.00 138.67
February 216.00 0.64 0.61 01-FEB-07:40 2179.79 17.14 61.33 228.67 1364.53 18.83 58.50 181.67
March 275.00 0.65 0.61 01-MAR-06:49 2305.87 14.96 56.83 300.00 1350.52 15.09 38.50 231.17
April 261.17 0.63 0.61 01-APR-06:10 3210.59 12.96 38.83 324.83 1220.17 11.96 0.00 277.33
May 372.00 0.64 0.61 01-MAY-05:40 2497.32 9.99 0.00 382.00 1421.08 12.22 0.00 328.33
June 351.83 0.63 0.61 01-JUN-04:00 2212.91 9.99 0.00 372.33 1296.41 12.30 0.00 336.00
July 365.17 0.63 0.61 01-JUL-04:00 2306.33 10.38 1.83 381.33 1302.00 12.55 0.00 337.83
August 389.17 0.64 0.61 01-AUG-05:40 3192.93 13.30 57.67 359.33 1322.58 12.34 0.00 330.67
September 285.33 0.64 0.61 01-SEP-05:49 2650.32 15.07 61.33 305.83 1191.71 12.64 5.50 263.50
October 305.50 0.64 0.61 01-OCT-14:39 2376.23 16.64 74.17 279.17 1313.65 16.57 50.17 243.67
November 240.83 0.64 0.61 01-NOV-06:49 1504.20 15.34 52.00 229.33 848.68 16.46 44.83 177.17
December 211.17 0.66 0.61 01-DEC-07:40 1490.77 16.86 64.17 196.33 835.44 16.14 42.67 125.33
                         
Annual Sum or Average 3472.67 0.64     2365.94 13.67 528.50 3560.50 1225.74 14.09 280.17 2971.33
Minimum of Months 199.50 0.63 0.61   1490.77 9.99 0.00 196.33 835.44 11.96 0.00 125.33
Maximum of Months 389.17 0.66 0.61   3210.59 17.19 74.17 382.00 1421.08 18.83 58.50 337.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.66 0.61 01-JAN-08:30 485.52 0.00 0.00 170.00 311.41 0.00 0.00 77.83
February 216.00 0.65 0.61 01-FEB-08:30 524.13 0.00 0.00 205.67 357.96 0.00 0.00 123.17
March 275.00 0.65 0.61 01-MAR-07:10 702.18 0.00 0.00 294.83 458.19 0.00 0.00 202.17
April 261.17 0.63 0.61 01-APR-06:19 792.47 0.00 0.00 331.00 518.15 0.00 0.00 263.00
May 372.00 0.63 0.61 01-MAY-05:40 1029.87 0.00 0.00 392.50 615.56 0.00 0.00 336.00
June 351.83 0.63 0.61 01-JUN-04:00 1158.42 0.00 0.00 388.83 674.12 0.00 0.00 358.00
July 365.17 0.62 0.61 01-JUL-04:00 1145.18 0.00 0.00 393.50 664.65 0.00 0.00 350.17
August 389.17 0.63 0.61 01-AUG-05:49 936.38 0.00 0.00 370.33 588.93 0.00 0.00 332.17
September 285.33 0.64 0.61 01-SEP-06:10 724.11 0.00 0.00 302.33 479.09 0.00 0.00 234.17
October 305.50 0.64 0.61 01-OCT-14:39 649.25 0.00 0.00 273.50 441.84 0.00 0.00 211.67
November 240.83 0.65 0.61 01-NOV-07:19 544.38 0.00 0.00 210.17 340.97 0.00 0.00 113.83
December 211.17 0.68 0.61 01-DEC-08:30 388.98 0.00 0.00 150.00 258.42 0.00 0.00 42.00
                         
Annual Sum or Average 3472.67 0.64     806.76 0.00 0.00 3482.67 503.13 0.00 0.00 2644.17
Minimum of Months 199.50 0.62 0.61   388.98 0.00 0.00 150.00 258.42 0.00 0.00 42.00
Maximum of Months 389.17 0.68 0.61   1158.42 0.00 0.00 393.50 674.12 0.00 0.00 358.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 199.50 0.65 0.61 01-JAN-08:30 1529.39 16.84 56.17 203.83 844.57 16.21 36.83 138.50
February 216.00 0.64 0.61 01-FEB-08:39 1568.29 14.11 37.00 228.00 935.34 16.11 36.17 178.00
March 275.00 0.64 0.61 01-MAR-07:19 2479.85 16.03 68.67 303.83 1490.29 16.00 47.67 239.83
April 261.17 0.64 0.61 01-APR-07:19 2805.39 12.73 36.00 324.17 1188.52 11.95 0.00 278.83
May 372.00 0.63 0.61 01-MAY-05:00 2766.20 10.03 0.00 382.50 1238.23 12.39 1.83 330.67
June 351.83 0.63 0.61 01-JUN-05:40 2597.56 10.07 0.00 377.33 1469.07 14.95 43.00 326.50
July 365.17 0.63 0.61 01-JUL-05:49 2444.44 10.47 3.50 381.00 1364.44 12.57 0.00 334.17
August 389.17 0.64 0.61 01-AUG-05:00 3255.72 13.10 54.33 359.83 1420.88 12.33 0.00 329.50
September 285.33 0.64 0.61 01-SEP-06:30 2516.81 13.62 45.67 305.50 1386.34 12.78 5.50 264.83
October 305.50 0.63 0.61 01-OCT-14:39 2667.49 17.41 83.50 292.00 1170.03 17.04 53.17 258.00
November 240.83 0.64 0.61 01-NOV-07:19 1332.00 16.39 64.83 232.83 718.26 16.11 43.50 173.33
December 211.17 0.66 0.61 01-DEC-08:30 1101.06 14.42 45.67 196.50 694.38 16.16 43.67 129.67
                         
Annual Sum or Average 3472.67 0.64     2374.95 13.40 495.33 3587.33 1207.16 14.29 311.33 2981.83
Minimum of Months 199.50 0.63 0.61   1101.06 10.03 0.00 196.50 694.38 11.95 0.00 129.67
Maximum of Months 389.17 0.66 0.61   3255.72 17.41 83.50 382.50 1490.29 17.04 53.17 334.17



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.225549E+09 26903.76 30-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.334247E+09 36097.44 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.304603E+09 25564.96 23-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 52170126.04 11101.34 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 9988412.96 10037.71 30-MAY-13:40 0.00 0.00 0.00 0.00 0.00
June 0.107357E+09 13471.24 22-JUN-12:00 0.00 0.00 0.00 0.00 0.00
July 35833800.26 8161.29 11-JUL-15:10 0.00 0.00 0.00 0.00 0.00
August 0.129561E+09 14630.30 24-AUG-18:50 0.00 0.00 0.00 0.00 0.00
September 10587846.38 8306.57 01-SEP-17:20 0.00 0.00 0.00 0.00 0.00
October 12548123.97 7695.81 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.168077E+09 25239.18 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.411799E+09 25796.01 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180232E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 9988412.96 7695.81   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.411799E+09 36097.44   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.925650E+09 15073.28 30-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.672608E+09 15124.91 03-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 8579536.41 3646.88 17-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 18164270.88 11695.54 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 10385148.87 5576.37 02-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163539E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.925650E+09 15124.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.773533E+09 13680.23 30-JAN-06:01 0.00 0.00 0.00 0.00 0.00
February 0.519049E+09 13773.81 03-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 59239250.06 13563.94 17-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 106441.27 50.64 22-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 44277494.56 13595.53 22-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.173687E+09 13522.49 07-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.156989E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.773533E+09 13773.81   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.991201E+09 19260.83 26-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.625895E+09 19342.41 15-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 77434954.76 19112.77 13-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 124979.93 202.61 22-APR-05:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 61450014.08 19279.15 24-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.183669E+09 19035.95 07-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.193978E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.991201E+09 19342.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.309749E+09 12582.53 02-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 99596850.74 12566.08 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.409346E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.309749E+09 12582.53   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.185308E+11 305673.20 30-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.145417E+11 415877.62 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.865365E+10 282465.67 23-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 0.170644E+10 133402.02 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.114491E+09 85246.79 30-MAY-14:10 0.00 0.00 0.00 0.00 0.00
June 0.112838E+10 150605.20 01-JUN-14:50 0.00 0.00 0.00 0.00 0.00
July 0.377969E+09 85429.96 11-JUL-16:05 0.00 0.00 0.00 0.00 0.00
August 0.182212E+10 114511.09 22-AUG-15:30 0.00 0.00 0.00 0.00 0.00
September 0.149381E+09 54164.17 01-SEP-17:20 0.00 0.00 0.00 0.00 0.00
October 0.234257E+09 95708.03 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.501667E+10 296145.53 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.125837E+11 285292.59 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.648595E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.114491E+09 54164.17   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.185308E+11 415877.62   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.247827E+11 580508.74 02-JAN-06:06 0.00 0.00 0.00 0.00 0.00
February 0.539277E+10 579868.59 13-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.228662E+09 157538.90 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.159856E+09 75955.71 26-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.305640E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.247827E+11 580508.74   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.683041E+11 132404.03 18-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.561124E+11 132080.45 16-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.173092E+11 143276.91 30-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.379876E+10 143302.39 14-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.518620E+09 143675.75 28-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.168034E+11 142448.13 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.379096E+11 132453.51 01-DEC-05:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.200756E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.683041E+11 143675.75   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.447950E+11 163439.39 09-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.324003E+11 162963.76 16-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.102191E+11 173931.69 31-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.324731E+10 162538.10 21-APR-04:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.287964E+09 88232.73 28-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.109804E+11 173152.07 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.253482E+11 163437.30 26-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.127278E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.447950E+11 173931.69   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.418119E+11 184196.06 23-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.268752E+11 183795.24 28-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 0.802622E+10 198287.61 31-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.267796E+10 183225.89 22-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 22630413.26 5576.41 28-OCT-06:30 0.00 0.00 0.00 0.00 0.00
November 0.760860E+10 191565.76 13-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.198230E+11 183731.78 11-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.106846E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.418119E+11 198287.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.385415E+11 170677.07 09-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.287390E+11 169737.36 13-FEB-05:12 0.00 0.00 0.00 0.00 0.00
March 0.735276E+10 169450.04 13-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.183863E+10 168601.52 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.204357E+09 45000.19 28-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.975337E+10 169997.51 27-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.206937E+11 170007.56 11-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.107123E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.385415E+11 170677.07   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.164776E+10 35947.83 30-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.121225E+10 46230.27 13-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.282101E+09 33518.65 23-MAR-06:10 0.00 0.00 0.00 0.00 0.00
April 98128921.20 17682.30 01-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 31905434.60 12873.43 30-MAY-13:35 0.00 0.00 0.00 0.00 0.00
June 64024185.51 14282.95 01-JUN-14:40 0.00 0.00 0.00 0.00 0.00
July 46715621.23 7142.57 11-JUL-16:05 0.00 0.00 0.00 0.00 0.00
August 93737170.25 18641.35 25-AUG-14:47 0.00 0.00 0.00 0.00 0.00
September 6797665.66 4443.80 01-SEP-14:15 0.00 0.00 0.00 0.00 0.00
October 38320061.20 14120.23 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.239970E+09 34207.08 24-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.431640E+09 34042.07 22-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.419335E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 6797665.66 4443.80   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.164776E+10 46230.27   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.103424E+11 80499.06 23-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.803644E+10 80156.79 21-FEB-05:13 0.00 0.00 0.00 0.00 0.00
March 0.219844E+10 80061.85 20-MAR-05:05 0.00 0.00 0.00 0.00 0.00
April 0.548041E+09 80136.87 03-APR-04:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 33760246.49 21820.24 30-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.332992E+10 80442.95 27-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.591622E+10 80346.40 26-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.304052E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.103424E+11 80499.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.116892E+11 15618.76 24-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.104360E+11 15589.43 28-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.473516E+10 15651.49 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.156505E+10 15574.17 03-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 72442418.64 15505.50 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 760708.46 188.03 30-SEP-07:00 0.00 0.00 0.00 0.00 0.00
October 0.521547E+09 15524.73 10-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.468870E+10 15642.37 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.871402E+10 15630.43 26-DEC-04:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.424228E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.116892E+11 15651.49   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.733241E+10 16810.61 24-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.600102E+10 16772.38 04-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.258689E+10 16837.61 06-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.101195E+10 16743.81 14-APR-04:02 0.00 0.00 0.00 0.00 0.00
May 48984570.32 11340.79 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 352502.87 244.86 30-SEP-05:50 0.00 0.00 0.00 0.00 0.00
October 0.262017E+09 16594.06 28-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.280475E+10 16785.02 27-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.536117E+10 16781.97 01-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.254095E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.733241E+10 16837.61   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.806802E+10 20351.07 23-JAN-05:43 0.00 0.00 0.00 0.00 0.00
February 0.617287E+10 20343.90 28-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.286969E+10 20400.20 06-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.127622E+10 20281.00 22-APR-04:14 0.00 0.00 0.00 0.00 0.00
May 77491871.42 18064.34 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.189481E+09 20108.14 27-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.268697E+10 20401.71 27-NOV-05:23 0.00 0.00 0.00 0.00 0.00
December 0.540560E+10 20369.77 26-DEC-04:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.267463E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.806802E+10 20401.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.666014E+10 18381.07 12-JAN-05:03 0.00 0.00 0.00 0.00 0.00
February 0.540033E+10 18402.47 28-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.215756E+10 18335.87 13-MAR-04:23 0.00 0.00 0.00 0.00 0.00
April 0.796808E+09 18367.34 22-APR-04:12 0.00 0.00 0.00 0.00 0.00
May 41713049.22 10864.55 01-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.229354E+09 15003.37 28-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.251271E+10 18369.88 22-NOV-05:12 0.00 0.00 0.00 0.00 0.00
December 0.450516E+10 18414.91 01-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.223038E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.666014E+10 18414.91   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:01 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:03 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 18841006.08 18841006.08 4419.47 19-JAN-08:30 4419.47 0.00
February 0.00 0.00 16076007.78 16076007.78 2775.79 02-FEB-08:10 2775.79 0.00
March 0.00 0.00 0.114333E+10 0.110759E+10 64484.72 27-MAR-16:00 64484.72 0.02
April 0.00 0.00 0.119550E+11 0.119493E+11 116677.73 07-APR-15:00 116677.73 0.09
May 0.00 0.00 0.354743E+11 0.316231E+11 173874.24 30-MAY-13:30 173874.24 0.23
June 0.00 0.00 0.120795E+12 0.986641E+11 209170.36 19-JUN-05:03 145809.67 0.66
July 0.00 0.00 0.166254E+12 0.138266E+12 218371.39 10-JUL-05:02 156084.20 0.82
August 0.00 0.00 0.170332E+12 0.150198E+12 217988.29 03-AUG-05:03 153701.02 0.84
September 0.00 0.00 0.797612E+11 0.683656E+11 211319.70 07-SEP-05:02 148966.65 0.51
October 0.00 0.00 0.378106E+11 0.284025E+11 153356.62 06-OCT-05:02 65678.85 0.28
November 0.00 0.00 0.110735E+10 0.101617E+10 59452.13 10-NOV-06:03 23174.92 0.02
December 0.00 0.00 11156552.39 11156552.39 4328.34 13-DEC-08:10 4328.34 0.00
                 
Annual Sum or Average 0.00 0.00 0.624678E+12 0.529638E+12       0.29
Minimum of Months 0.00 0.00 11156552.39 11156552.39 2775.79   2775.79 0.00
Maximum of Months 0.00 0.00 0.170332E+12 0.150198E+12 218371.39   173874.24 0.84



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 50727843.69 50727843.69 7138.87 17-JAN-12:40 7138.87 0.00
February 0.00 0.00 4552358.87 4552358.87 243.98 28-FEB-14:20 243.98 0.00
March 0.00 0.00 0.652141E+10 0.649186E+10 393420.99 27-MAR-16:00 393420.99 0.02
April 0.00 0.00 0.786206E+11 0.786083E+11 974438.23 07-APR-14:20 974438.23 0.07
May 0.00 0.00 0.298317E+12 0.266452E+12 1515081.45 30-MAY-10:40 1515081.45 0.22
June 0.00 0.00 0.100096E+13 0.792011E+12 2113855.96 19-JUN-05:03 1364635.72 0.58
July 0.00 0.00 0.132677E+13 0.103970E+13 2397433.49 21-JUL-03:02 1407957.95 0.65
August 0.00 0.00 0.129637E+13 0.110260E+13 2361522.35 04-AUG-03:02 1402163.86 0.63
September 0.00 0.00 0.690689E+12 0.580703E+12 2090670.53 07-SEP-05:02 1377656.10 0.48
October 0.00 0.00 0.294965E+12 0.220688E+12 1403688.23 06-OCT-05:02 600920.96 0.27
November 0.00 0.00 0.783271E+10 0.734693E+10 485257.63 10-NOV-06:03 188247.70 0.02
December 0.00 0.00 15505479.75 15505479.75 7041.37 13-DEC-10:00 7041.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.500112E+13 0.409467E+13       0.25
Minimum of Months 0.00 0.00 4552358.87 4552358.87 243.98   243.98 0.00
Maximum of Months 0.00 0.00 0.132677E+13 0.110260E+13 2397433.49   1515081.45 0.65



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 17100433.12 17100433.12 881.79 15-JAN-10:40 881.79 0.00
February 0.00 0.00 11946115.34 11946115.34 1062.38 09-FEB-04:42 1062.38 0.00
March 0.00 0.00 0.596599E+09 0.595262E+09 32239.90 27-MAR-16:00 32239.90 0.02
April 0.00 0.00 0.801909E+10 0.801801E+10 101937.01 07-APR-14:00 101937.01 0.07
May 0.00 0.00 0.313793E+11 0.283432E+11 185343.32 30-MAY-13:40 185343.32 0.21
June 0.00 0.00 0.108731E+12 0.872937E+11 221180.58 19-JUN-05:03 142529.43 0.57
July 0.00 0.00 0.148916E+12 0.118319E+12 259562.49 22-JUL-03:02 129541.70 0.65
August 0.00 0.00 0.144224E+12 0.124012E+12 251658.13 04-AUG-03:02 145969.37 0.63
September 0.00 0.00 0.709912E+11 0.597165E+11 220235.66 07-SEP-05:02 140336.99 0.47
October 0.00 0.00 0.277737E+11 0.208934E+11 135916.00 06-OCT-05:02 58206.30 0.26
November 0.00 0.00 0.601500E+09 0.563271E+09 16145.86 03-NOV-14:00 16145.86 0.01
December 0.00 0.00 16443966.69 16443966.69 2566.65 25-DEC-08:55 2566.65 0.00
                 
Annual Sum or Average 0.00 0.00 0.541278E+12 0.447800E+12       0.24
Minimum of Months 0.00 0.00 11946115.34 11946115.34 881.79   881.79 0.00
Maximum of Months 0.00 0.00 0.148916E+12 0.124012E+12 259562.49   185343.32 0.65



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 6817986.26 3030633.84 33639.40 24-JAN-06:03 14724.61 0.00
February 0.00 0.00 55406.60 55406.60 66.02 11-FEB-09:40 66.02 0.00
March 0.00 0.00 0.583547E+09 0.583345E+09 40317.22 27-MAR-16:00 40317.22 0.01
April 0.00 0.00 0.529742E+10 0.527661E+10 64036.39 07-APR-13:50 64036.39 0.05
May 0.00 0.00 0.156082E+11 0.148307E+11 95981.71 30-MAY-13:50 95981.71 0.12
June 0.00 0.00 0.662030E+11 0.545677E+11 148327.48 19-JUN-03:02 81791.99 0.51
July 0.00 0.00 0.958121E+11 0.741709E+11 146004.82 10-JUL-03:02 84286.38 0.55
August 0.00 0.00 0.964099E+11 0.796964E+11 137621.43 03-AUG-03:02 84416.04 0.57
September 0.00 0.00 0.500455E+11 0.432785E+11 130636.23 07-SEP-03:02 81980.79 0.42
October 0.00 0.00 0.191459E+11 0.158261E+11 101894.32 06-OCT-05:04 43743.01 0.22
November 0.00 0.00 0.140696E+09 0.129357E+09 57945.93 10-NOV-06:03 22991.59 0.00
December 0.00 0.00 11741.56 11741.56 16.20 30-DEC-14:50 16.20 0.00
                 
Annual Sum or Average 0.00 0.00 0.349253E+12 0.288363E+12       0.21
Minimum of Months 0.00 0.00 11741.56 11741.56 16.20   16.20 0.00
Maximum of Months 0.00 0.00 0.964099E+11 0.796964E+11 148327.48   95981.71 0.57



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.316612E+12 0.316485E+12 123808.53 20-JAN-22:03 123808.53 0.00
February 0.00 0.00 0.506080E+12 0.506080E+12 215251.88 21-FEB-22:03 215251.88 0.00
March 0.00 0.00 0.810809E+12 0.810603E+12 393346.31 31-MAR-24:00 393346.31 0.00
April 0.00 0.00 0.102580E+13 0.102539E+13 403559.36 27-APR-15:50 398075.68 0.00
May 0.00 0.00 0.331621E+12 0.329084E+12 212637.67 31-MAY-24:00 211203.06 0.00
June 0.00 0.00 0.567339E+12 0.559347E+12 303183.36 30-JUN-24:00 302807.28 0.00
July 0.00 0.00 0.837339E+12 0.826238E+12 395119.84 31-JUL-23:57 395119.84 0.00
August 0.00 0.00 0.107599E+13 0.106841E+13 412547.07 18-AUG-19:00 402892.07 0.00
September 0.00 0.00 0.329990E+12 0.324406E+12 211563.91 30-SEP-24:00 211563.91 0.00
October 0.00 0.00 0.580454E+12 0.576521E+12 303266.01 31-OCT-24:00 303266.01 0.00
November 0.00 0.00 0.789920E+12 0.789535E+12 312108.26 10-NOV-10:30 305926.48 0.00
December 0.00 0.00 0.105746E+13 0.105746E+13 400230.39 14-DEC-22:02 400230.39 0.00
                 
Annual Sum or Average 0.00 0.00 0.822941E+13 0.818955E+13       0.00
Minimum of Months 0.00 0.00 0.316612E+12 0.316485E+12 123808.53   123808.53 0.00
Maximum of Months 0.00 0.00 0.107599E+13 0.106841E+13 412547.07   402892.07 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.316061E+10 0.315541E+10 2147.11 29-JAN-16:35 2147.11 0.00
February 0.00 0.00 0.793589E+10 0.793589E+10 4209.56 20-FEB-16:25 4209.56 0.00
March 0.00 0.00 0.149250E+11 0.149138E+11 7464.89 31-MAR-24:00 7464.89 0.00
April 0.00 0.00 0.197704E+11 0.197483E+11 8611.00 09-APR-17:23 8592.19 0.00
May 0.00 0.00 0.564674E+10 0.554719E+10 4105.21 31-MAY-24:00 4052.12 0.00
June 0.00 0.00 0.109641E+11 0.106400E+11 5890.06 30-JUN-24:00 5871.80 0.00
July 0.00 0.00 0.166377E+11 0.161583E+11 7751.52 31-JUL-23:57 7751.52 0.00
August 0.00 0.00 0.216639E+11 0.212921E+11 8840.82 31-AUG-17:50 8483.60 0.00
September 0.00 0.00 0.583540E+10 0.562444E+10 3943.19 30-SEP-24:00 3943.19 0.00
October 0.00 0.00 0.107610E+11 0.106068E+11 5667.09 31-OCT-24:00 5665.49 0.00
November 0.00 0.00 0.144972E+11 0.144789E+11 6142.42 03-NOV-16:00 6142.42 0.00
December 0.00 0.00 0.196917E+11 0.196917E+11 8036.54 25-DEC-16:10 8036.54 0.00
                 
Annual Sum or Average 0.00 0.00 0.151490E+12 0.149793E+12       0.00
Minimum of Months 0.00 0.00 0.316061E+10 0.315541E+10 2147.11   2147.11 0.00
Maximum of Months 0.00 0.00 0.216639E+11 0.212921E+11 8840.82   8592.19 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.781669E+10 0.777888E+10 16519.59 20-JAN-16:30 16519.59 0.00
February 0.00 0.00 0.529047E+11 0.529047E+11 35982.61 22-FEB-17:00 35982.61 0.00
March 0.00 0.00 0.124645E+12 0.124533E+12 65138.24 31-MAR-23:50 65138.24 0.00
April 0.00 0.00 0.177787E+12 0.177563E+12 80207.72 09-APR-17:23 80022.79 0.00
May 0.00 0.00 0.485466E+11 0.475759E+11 39103.47 31-MAY-24:00 38559.15 0.00
June 0.00 0.00 0.103151E+12 0.999335E+11 55578.33 30-JUN-24:00 55393.76 0.00
July 0.00 0.00 0.158782E+12 0.154003E+12 74729.25 31-JUL-23:57 74729.25 0.00
August 0.00 0.00 0.206384E+12 0.202665E+12 84451.84 31-AUG-17:40 80901.20 0.00
September 0.00 0.00 0.517526E+11 0.496863E+11 35786.41 30-SEP-23:40 35786.41 0.00
October 0.00 0.00 0.944614E+11 0.929407E+11 49116.36 31-OCT-24:00 49092.17 0.00
November 0.00 0.00 0.118746E+12 0.118564E+12 57451.97 03-NOV-16:00 57451.97 0.00
December 0.00 0.00 0.161803E+12 0.161803E+12 71210.37 08-DEC-16:10 71210.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.130678E+13 0.128995E+13       0.00
Minimum of Months 0.00 0.00 0.781669E+10 0.777888E+10 16519.59   16519.59 0.00
Maximum of Months 0.00 0.00 0.206384E+12 0.202665E+12 84451.84   80901.20 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.280669E+09 0.277886E+09 1578.37 19-JAN-16:20 1578.37 0.00
February 0.00 0.00 0.373381E+10 0.373381E+10 3477.88 17-FEB-17:00 3477.88 0.00
March 0.00 0.00 0.110449E+11 0.110339E+11 5944.52 31-MAR-23:20 5944.52 0.00
April 0.00 0.00 0.168449E+11 0.168228E+11 8100.14 09-APR-17:23 8081.59 0.00
May 0.00 0.00 0.449874E+10 0.440322E+10 3891.39 31-MAY-24:00 3836.43 0.00
June 0.00 0.00 0.103334E+11 0.100117E+11 5484.75 30-JUN-24:00 5465.88 0.00
July 0.00 0.00 0.160051E+11 0.155271E+11 7486.24 31-JUL-23:57 7486.24 0.00
August 0.00 0.00 0.207263E+11 0.203545E+11 8582.06 31-AUG-17:10 8198.27 0.00
September 0.00 0.00 0.496566E+10 0.475987E+10 3322.70 30-SEP-23:20 3322.70 0.00
October 0.00 0.00 0.860050E+10 0.844951E+10 4660.74 04-OCT-16:00 4344.30 0.00
November 0.00 0.00 0.102506E+11 0.102327E+11 5719.09 03-NOV-16:00 5719.09 0.00
December 0.00 0.00 0.142322E+11 0.142322E+11 6920.97 08-DEC-16:10 6920.97 0.00
                 
Annual Sum or Average 0.00 0.00 0.121517E+12 0.119839E+12       0.00
Minimum of Months 0.00 0.00 0.280669E+09 0.277886E+09 1578.37   1578.37 0.00
Maximum of Months 0.00 0.00 0.207263E+11 0.203545E+11 8582.06   8198.27 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 106105.41 1833185.28 09-JAN-05:01
February 0.00 0.00 01-FEB-00:10 83709.07 1699049.81 13-FEB-05:11
March 0.00 0.00 01-MAR-00:10 24820.01 1253412.36 07-MAR-06:02
April 0.00 0.00 01-APR-00:10 7149.68 1181952.09 03-APR-05:01
May 0.00 0.00 01-MAY-00:10 183.71 115315.28 30-MAY-14:10
June 0.00 0.00 01-JUN-00:10 511.90 140880.44 01-JUN-14:50
July 0.00 0.00 01-JUL-00:10 180.70 61771.96 11-JUL-16:20
August 0.00 0.00 01-AUG-00:03 767.82 104413.73 22-AUG-15:50
September 0.00 0.00 01-SEP-00:03 45.80 41833.98 01-SEP-17:20
October 0.00 0.00 01-OCT-00:10 904.79 548427.29 28-OCT-05:02
November 0.00 0.00 01-NOV-00:10 25703.08 1285962.51 27-NOV-06:01
December 0.00 0.00 01-DEC-00:10 54884.21 1271144.51 26-DEC-05:01
             
Annual Sum or Average 0.00     25121.68    
Minimum of Months 0.00 0.00   45.80 41833.98  
Maximum of Months 0.00 0.00   106105.41 1833185.28  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2742.69 41987.23 24-JAN-06:03 0.00 0.00 01-JAN-00:01
February 3510.05 31142.94 09-FEB-13:10 0.00 0.00 01-FEB-00:10
March 9375.07 1080294.11 27-MAR-16:00 0.00 0.00 01-MAR-00:10
April 79772.35 1602500.79 07-APR-14:20 1.04 10159.02 08-APR-03:02
May 265164.88 1953237.31 30-MAY-13:15 115.41 281628.67 21-MAY-06:43
June 726840.26 2702360.10 17-JUN-05:04 2.82 35427.86 05-JUN-01:12
July 874315.65 3042866.78 24-JUL-05:04 0.00 0.00 01-JUL-00:10
August 848142.72 2626657.47 01-AUG-05:03 0.00 0.00 01-AUG-00:03
September 535781.52 2802368.72 07-SEP-05:04 9.32 84476.35 11-SEP-03:02
October 237026.46 1717397.35 05-OCT-13:10 6.30 39048.13 22-OCT-21:03
November 10328.29 674997.41 10-NOV-06:03 0.00 0.00 01-NOV-00:10
December 2331.89 37794.13 15-DEC-11:20 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 301622.01     11.42    
Minimum of Months 2331.89 31142.94   0.00 0.00  
Maximum of Months 874315.65 3042866.78   115.41 281628.67  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 9.49 44848.52 24-JAN-06:03 0.00 0.00 01-JAN-00:01
February 5.76 987.50 09-FEB-13:10 0.00 0.00 01-FEB-00:10
March 4139.52 676809.51 27-MAR-16:00 0.00 0.00 01-MAR-00:10
April 50370.96 1589602.15 07-APR-14:40 0.00 0.00 01-APR-00:10
May 175362.53 2036214.53 30-MAY-13:15 0.00 0.00 01-MAY-00:10
June 591399.63 4082642.50 27-JUN-05:02 0.00 0.00 01-JUN-00:10
July 716843.76 4169953.02 24-JUL-05:02 0.00 0.00 01-JUL-00:10
August 708275.83 4031801.49 14-AUG-05:02 0.00 0.00 01-AUG-00:03
September 415973.95 4083687.27 07-SEP-05:02 0.00 0.00 01-SEP-00:03
October 186041.97 3097743.33 06-OCT-05:02 0.00 0.00 01-OCT-00:10
November 4879.19 1124000.47 10-NOV-06:03 0.00 0.00 01-NOV-00:10
December 23.37 7006.41 13-DEC-10:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 239425.93     0.00    
Minimum of Months 5.76 987.50   0.00 0.00  
Maximum of Months 716843.76 4169953.02   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 156828.69 176742.47 20-JAN-16:20 0.00 0.00 01-JAN-00:01
February 297605.34 320279.96 20-FEB-16:30 0.00 0.00 01-FEB-00:10
March 452282.06 897583.64 27-MAR-16:00 0.00 0.00 01-MAR-00:10
April 654469.41 1359812.72 07-APR-13:00 0.00 0.00 01-APR-00:10
May 254457.31 892221.28 30-MAY-13:00 0.00 0.00 01-MAY-00:10
June 668650.99 1510727.95 19-JUN-12:00 0.00 0.00 01-JUN-00:10
July 1069504.03 1585903.71 07-JUL-12:00 0.00 0.00 01-JUL-00:10
August 1268037.69 1777267.91 24-AUG-16:00 0.00 0.00 01-AUG-00:03
September 388023.44 965621.24 01-SEP-14:00 0.00 0.00 01-SEP-00:03
October 392926.86 854053.20 04-OCT-13:00 0.00 0.00 01-OCT-00:10
November 453743.55 655842.85 03-NOV-14:00 0.00 0.00 01-NOV-00:10
December 581746.58 598082.20 17-DEC-16:07 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 555421.51     0.00    
Minimum of Months 156828.69 176742.47   0.00 0.00  
Maximum of Months 1268037.69 1777267.91   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 15962.24 53799.88 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 16193.60 53874.81 09-FEB-13:00
March 0.00 0.00 01-MAR-00:10 16763.29 53456.28 01-MAR-12:20
April 0.00 0.00 01-APR-00:10 15062.79 51248.39 03-APR-11:40
May 0.00 0.00 01-MAY-00:10 14544.33 48331.83 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 13888.90 44836.21 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 12288.09 41926.21 03-JUL-11:40
August 0.00 0.00 01-AUG-00:03 13151.15 40982.77 31-AUG-11:40
September 0.00 0.00 01-SEP-00:03 12771.92 42847.30 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 13502.36 46142.96 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 14628.84 49520.12 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 15014.84 52220.11 29-DEC-13:00
             
Annual Sum or Average 0.00     14471.26    
Minimum of Months 0.00 0.00   12288.09 40982.77  
Maximum of Months 0.00 0.00   16763.29 53874.81  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 148.09 32501.51 04-JAN-09:00 3603.66 171740.92 10-JAN-10:30
February 142.52 33248.82 14-FEB-21:30 4309.72 170631.98 07-FEB-13:30
March 4157.01 634193.55 27-MAR-16:00 2991.59 160447.51 16-MAR-13:10
April 50750.39 2578234.17 07-APR-14:40 1731.46 134835.52 04-APR-09:00
May 195160.50 3412561.13 31-MAY-13:30 918.31 94636.67 13-MAY-10:30
June 975023.78 5500317.06 15-JUN-12:10 232.48 59848.38 09-JUN-06:10
July 1781012.58 6060086.24 20-JUL-13:10 1.18 5276.84 11-JUL-03:00
August 1524004.51 6392153.19 02-AUG-13:40 220.66 40037.63 29-AUG-03:45
September 626118.62 4895482.25 07-SEP-14:00 283.91 79906.24 23-SEP-11:30
October 202471.36 3079811.55 25-OCT-10:20 526.73 100618.19 26-OCT-11:50
November 5125.21 336963.55 03-NOV-14:00 2412.94 152943.66 29-NOV-07:20
December 98.16 32241.91 13-DEC-07:50 3068.50 171177.79 22-DEC-10:10
             
Annual Sum or Average 451049.72     1676.02    
Minimum of Months 98.16 32241.91   1.18 5276.84  
Maximum of Months 1781012.58 6392153.19   4309.72 171740.92  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.127455E+11 0.74 8953.22 02-JAN-06:01 1.39
February 0.117914E+11 0.76 8953.22 01-FEB-05:01 1.40
March 0.142060E+11 0.82 8953.22 01-MAR-05:01 1.39
April 0.132029E+11 0.79 8953.22 01-APR-04:01 1.39
May 0.140503E+11 0.81 8953.22 01-MAY-03:02 1.39
June 0.141291E+11 0.84 8953.22 01-JUN-03:02 1.38
July 0.138260E+11 0.79 8953.22 01-JUL-03:02 1.38
August 0.153191E+11 0.88 8953.22 01-AUG-03:02 1.38
September 0.143894E+11 0.85 8953.22 01-SEP-03:02 1.38
October 0.145526E+11 0.84 8953.22 01-OCT-21:20 1.38
November 0.138265E+11 0.83 8953.22 01-NOV-03:10 1.38
December 0.131822E+11 0.77 8953.22 01-DEC-04:50 1.39
           
Annual Sum or Average 0.165221E+12 0.81      
Minimum of Months 0.117914E+11 0.74 8953.22   1.38
Maximum of Months 0.153191E+11 0.88 8953.22   1.40



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.321762E+10 0.30 13680.45 31-JAN-06:01 1.43
February 0.332505E+10 0.32 11963.21 04-FEB-06:01 1.31
March 0.567218E+10 0.40 11038.72 17-MAR-05:01 1.25
April 0.742200E+10 0.47 19208.50 07-APR-14:40 1.75
May 0.767479E+10 0.47 21111.09 30-MAY-10:23 1.86
June 0.109585E+11 0.61 21111.09 01-JUN-14:20 1.86
July 0.129926E+11 0.69 21111.09 10-JUL-05:02 1.86
August 0.152963E+11 0.77 21111.09 07-AUG-05:02 1.86
September 0.844461E+10 0.50 21111.09 05-SEP-05:02 1.86
October 0.797692E+10 0.46 18323.26 23-OCT-05:03 1.70
November 0.525252E+10 0.37 11527.02 22-NOV-06:01 1.28
December 0.469038E+10 0.35 11038.72 02-DEC-06:01 1.25
           
Annual Sum or Average 0.929234E+11 0.48      
Minimum of Months 0.321762E+10 0.30 11038.72   1.25
Maximum of Months 0.152963E+11 0.77 21111.09   1.86



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.321838E+11 0.34 45478.13 03-JAN-05:12 0.78
February 0.285889E+11 0.33 45478.13 06-FEB-05:01 0.78
March 0.328917E+11 0.32 119145.24 31-MAR-05:02 1.36
April 0.389968E+11 0.34 128039.12 07-APR-14:40 1.42
May 0.576550E+11 0.41 197219.22 30-MAY-10:23 1.86
June 0.839093E+11 0.51 197219.22 01-JUN-14:37 1.86
July 0.951085E+11 0.54 197219.22 03-JUL-05:03 1.85
August 0.106209E+12 0.58 197219.22 02-AUG-03:02 1.86
September 0.658854E+11 0.44 197219.22 01-SEP-14:15 1.86
October 0.507770E+11 0.37 101891.93 05-OCT-15:40 1.22
November 0.304954E+11 0.30 119731.43 13-NOV-06:01 1.36
December 0.286613E+11 0.31 38136.91 21-DEC-13:20 0.71
           
Annual Sum or Average 0.651362E+12 0.40      
Minimum of Months 0.285889E+11 0.30 38136.91   0.71
Maximum of Months 0.106209E+12 0.58 197219.22   1.86



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.395796E+10 0.40 4644.26 02-JAN-04:01 0.76
February 0.342466E+10 0.38 4644.26 01-FEB-05:01 0.76
March 0.337347E+10 0.34 4644.26 06-MAR-05:01 0.75
April 0.362985E+10 0.32 11129.45 07-APR-15:20 1.24
May 0.550525E+10 0.39 21283.02 30-MAY-10:27 1.86
June 0.885780E+10 0.50 21283.02 01-JUN-14:40 1.86
July 0.106272E+11 0.55 21283.02 10-JUL-05:02 1.86
August 0.117025E+11 0.59 21283.02 04-AUG-05:03 1.86
September 0.635927E+10 0.41 21283.02 07-SEP-05:02 1.86
October 0.433162E+10 0.33 11395.47 04-OCT-15:50 1.25
November 0.308995E+10 0.32 4644.26 06-NOV-06:01 0.75
December 0.342981E+10 0.35 4644.26 01-DEC-06:01 0.75
           
Annual Sum or Average 0.682893E+11 0.41      
Minimum of Months 0.308995E+10 0.32 4644.26   0.75
Maximum of Months 0.117025E+11 0.59 21283.02   1.86



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.945869E+11 1.35 35314.70 01-JAN-00:01 1.35
February 0.854333E+11 1.35 35314.70 01-FEB-00:10 1.35
March 0.945869E+11 1.35 35314.70 01-MAR-00:10 1.35
April 0.915357E+11 1.35 35314.70 01-APR-00:10 1.35
May 0.945869E+11 1.35 35314.70 01-MAY-00:10 1.35
June 0.915357E+11 1.35 35314.70 01-JUN-00:10 1.35
July 0.945869E+11 1.35 35314.70 01-JUL-00:10 1.35
August 0.945869E+11 1.35 35314.70 01-AUG-00:03 1.35
September 0.915357E+11 1.35 35314.70 01-SEP-00:03 1.35
October 0.945869E+11 1.35 35314.70 01-OCT-00:10 1.35
November 0.915357E+11 1.35 35314.70 01-NOV-00:10 1.35
December 0.945869E+11 1.35 35314.70 01-DEC-00:10 1.35
           
Annual Sum or Average 0.111368E+13 1.35      
Minimum of Months 0.854333E+11 1.35 35314.70   1.35
Maximum of Months 0.945869E+11 1.35 35314.70   1.35



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.141698E+10 0.92 529.04 01-JAN-00:01 0.92
February 0.127985E+10 0.92 529.04 01-FEB-00:10 0.92
March 0.141698E+10 0.92 529.04 01-MAR-00:10 0.92
April 0.137127E+10 0.92 529.04 01-APR-00:10 0.91
May 0.141698E+10 0.91 529.04 01-MAY-00:10 0.91
June 0.137127E+10 0.91 529.04 01-JUN-00:10 0.91
July 0.141698E+10 0.91 529.04 01-JUL-00:10 0.91
August 0.141698E+10 0.91 529.04 01-AUG-00:03 0.91
September 0.137127E+10 0.91 529.04 01-SEP-00:03 0.91
October 0.141698E+10 0.91 529.04 01-OCT-00:10 0.91
November 0.137127E+10 0.92 529.04 01-NOV-00:10 0.91
December 0.141698E+10 0.92 529.04 01-DEC-00:10 0.92
           
Annual Sum or Average 0.166838E+11 0.92      
Minimum of Months 0.127985E+10 0.91 529.04   0.91
Maximum of Months 0.141698E+10 0.92 529.04   0.92



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135195E+11 0.92 5047.61 01-JAN-00:01 0.92
February 0.122112E+11 0.92 5047.61 01-FEB-00:10 0.92
March 0.135195E+11 0.92 5047.61 01-MAR-00:10 0.92
April 0.130834E+11 0.92 5047.61 01-APR-00:10 0.91
May 0.135195E+11 0.91 5047.61 01-MAY-00:10 0.91
June 0.130834E+11 0.91 5047.61 01-JUN-00:10 0.91
July 0.135195E+11 0.91 5047.61 01-JUL-00:10 0.91
August 0.135195E+11 0.91 5047.61 01-AUG-00:03 0.91
September 0.130834E+11 0.91 5047.61 01-SEP-00:03 0.91
October 0.135195E+11 0.91 5047.61 01-OCT-00:10 0.91
November 0.130834E+11 0.92 5047.61 01-NOV-00:10 0.91
December 0.135195E+11 0.92 5047.61 01-DEC-00:10 0.92
           
Annual Sum or Average 0.159181E+12 0.92      
Minimum of Months 0.122112E+11 0.91 5047.61   0.91
Maximum of Months 0.135195E+11 0.92 5047.61   0.92



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.137808E+10 0.92 514.52 01-JAN-00:01 0.92
February 0.124472E+10 0.92 514.52 01-FEB-00:10 0.92
March 0.137808E+10 0.92 514.52 01-MAR-00:10 0.92
April 0.133363E+10 0.92 514.52 01-APR-00:10 0.91
May 0.137808E+10 0.91 514.52 01-MAY-00:10 0.91
June 0.133363E+10 0.91 514.52 01-JUN-00:10 0.91
July 0.137808E+10 0.91 514.52 01-JUL-00:10 0.91
August 0.137808E+10 0.91 514.52 01-AUG-00:03 0.91
September 0.133363E+10 0.91 514.52 01-SEP-00:03 0.91
October 0.137808E+10 0.91 514.52 01-OCT-00:10 0.91
November 0.133363E+10 0.92 514.52 01-NOV-00:10 0.91
December 0.137808E+10 0.92 514.52 01-DEC-00:10 0.92
           
Annual Sum or Average 0.162258E+11 0.92      
Minimum of Months 0.124472E+10 0.91 514.52   0.91
Maximum of Months 0.137808E+10 0.92 514.52   0.92



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 38652184.59 34786966.13 1146.90 03-JAN-06:02 1032.21 1032.21 46.50 11.28
February 21120784.37 19008705.93 1062.08 06-FEB-05:02 955.88 955.88 49.22 10.89
March 4437067.61 3993360.85 334.39 17-MAR-05:01 300.95 300.95 41.78 6.48
April 878685.76 790817.18 323.31 03-APR-05:01 290.98 290.98 36.35 6.39
May 16750.76 15075.68 6.27 30-MAY-14:10 5.64 5.64 36.96 0.65
June 75429.98 67886.98 9.34 01-JUN-14:50 8.41 8.41 40.29 0.86
July 27140.61 24426.55 4.36 11-JUL-16:20 3.92 3.92 49.39 0.49
August 139151.36 125236.22 12.67 24-AUG-16:50 11.40 11.40 61.44 1.05
September 6528.52 5875.67 2.24 01-SEP-17:20 2.02 2.02 44.85 0.29
October 84713.07 76241.76 52.57 28-OCT-05:02 47.32 47.32 28.45 2.52
November 4605691.77 4145122.59 436.76 27-NOV-06:01 393.08 393.08 38.07 7.35
December 9693366.77 8724030.10 362.62 30-DEC-06:01 326.36 326.36 42.13 6.73
                 
Annual Sum or Average 79737495.16 71763745.65            
Minimum of Months 6528.52 5875.67 2.24   2.02 2.02 28.45 0.29
Maximum of Months 38652184.59 34786966.13 1146.90   1032.21 1032.21 61.44 11.28



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 20803.34 18723.00 37.52 24-JAN-06:03 33.77 33.77 7.34 4.80
February 4875.76 4388.18 0.36 09-FEB-13:10 0.32 0.32 7.50 0.08
March 4264293.43 3837864.09 412.47 27-MAR-16:00 371.22 371.22 8.45 19.47
April 0.100220E+09 90198118.10 4697.97 07-APR-14:40 4228.18 4228.18 7.20 60.50
May 0.353037E+09 0.317734E+09 7417.48 30-MAY-14:00 6675.73 6675.73 6.72 73.35
June 0.152161E+10 0.136945E+10 24714.96 08-JUN-05:02 22243.46 22243.46 8.18 119.22
July 0.188615E+10 0.169754E+10 24714.96 01-JUL-05:02 22243.46 22243.46 8.08 119.22
August 0.233773E+10 0.210396E+10 24714.96 02-AUG-05:03 22243.46 22243.46 7.46 119.22
September 0.120296E+10 0.108266E+10 24714.96 07-SEP-05:02 22243.46 22243.46 7.78 119.22
October 0.601594E+09 0.541434E+09 14407.95 06-OCT-05:02 12967.16 12967.16 8.14 96.23
November 3439517.92 3095566.13 1390.55 10-NOV-06:03 1251.50 1251.50 8.50 35.19
December 9540.57 8586.51 1.10 13-DEC-10:00 0.99 0.99 8.45 0.25
                 
Annual Sum or Average 0.801104E+10 0.720994E+10            
Minimum of Months 4875.76 4388.18 0.36   0.32 0.32 6.72 0.08
Maximum of Months 0.233773E+10 0.210396E+10 24714.96   22243.46 22243.46 8.50 119.22



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.410455E+10 0.369409E+10 17010.64 02-JAN-07:03 15309.57 15309.57 8.43 119.22
February 0.473508E+10 0.426157E+10 17010.64 01-FEB-11:50 15309.57 15309.57 8.43 119.22
March 0.422197E+10 0.379977E+10 17010.64 01-MAR-07:05 15309.57 15309.57 8.43 119.22
April 0.833072E+10 0.749764E+10 17010.64 01-APR-08:30 15309.57 15309.57 8.43 119.22
May 0.202690E+11 0.182421E+11 17010.64 01-MAY-09:30 15309.57 15309.57 8.44 119.22
June 0.323541E+11 0.291187E+11 17010.64 01-JUN-03:02 15309.57 15309.57 9.02 119.22
July 0.396239E+11 0.356615E+11 17010.64 01-JUL-03:02 15309.57 15309.57 9.59 119.22
August 0.415868E+11 0.374281E+11 17010.64 01-AUG-00:03 15309.57 15309.57 7.35 119.22
September 0.271714E+11 0.244543E+11 17010.64 01-SEP-00:20 15309.57 15309.57 7.40 119.22
October 0.155925E+11 0.140332E+11 17010.64 02-OCT-03:02 15309.57 15309.57 8.57 119.22
November 0.407281E+10 0.366553E+10 17010.64 02-NOV-11:00 15309.57 15309.57 8.45 119.22
December 0.344283E+10 0.309855E+10 17010.64 01-DEC-06:50 15309.57 15309.57 8.43 119.22
                 
Annual Sum or Average 0.205506E+12 0.184955E+12            
Minimum of Months 0.344283E+10 0.309855E+10 17010.64   15309.57 15309.57 7.35 119.22
Maximum of Months 0.415868E+11 0.374281E+11 17010.64   15309.57 15309.57 9.59 119.22



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.904370E+10 0.813933E+10 3376.53 01-JAN-00:01 3038.88 3038.88 21.46 14.10
February 0.816850E+10 0.735165E+10 3376.53 01-FEB-00:10 3038.88 3038.88 24.15 14.10
March 0.904370E+10 0.813933E+10 3376.53 01-MAR-00:10 3038.88 3038.88 26.94 14.10
April 0.875196E+10 0.787677E+10 3376.53 01-APR-00:10 3038.88 3038.88 30.16 14.10
May 0.904370E+10 0.813933E+10 3376.53 01-MAY-00:10 3038.88 3038.88 22.37 14.10
June 0.875196E+10 0.787677E+10 3376.53 01-JUN-00:10 3038.88 3038.88 28.03 14.10
July 0.904370E+10 0.813933E+10 3376.53 01-JUL-00:10 3038.88 3038.88 33.80 14.10
August 0.904370E+10 0.813933E+10 3376.53 01-AUG-00:03 3038.88 3038.88 42.35 14.10
September 0.875196E+10 0.787677E+10 3376.53 01-SEP-00:03 3038.88 3038.88 29.90 14.10
October 0.904370E+10 0.813933E+10 3376.53 01-OCT-00:10 3038.88 3038.88 24.83 14.10
November 0.875196E+10 0.787677E+10 3376.53 01-NOV-00:10 3038.88 3038.88 27.48 14.10
December 0.904370E+10 0.813933E+10 3376.53 01-DEC-00:10 3038.88 3038.88 29.87 14.10
                 
Annual Sum or Average 0.106482E+12 0.958340E+11            
Minimum of Months 0.816850E+10 0.735165E+10 3376.53   3038.88 3038.88 21.46 14.10
Maximum of Months 0.904370E+10 0.813933E+10 3376.53   3038.88 3038.88 42.35 14.10



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:02 1.79 1.79 56.01 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:01 1.79 1.79 56.35 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:03 1.79 1.79 56.23 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:02 1.79 1.79 56.22 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:03 1.79 1.79 55.99 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 56.92 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:02 1.79 1.79 56.05 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 56.51 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 56.10 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 56.55 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 56.16 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:01 1.79 1.79 55.87 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.87 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 56.92 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.506081E+10 0.455473E+10 20977.38 04-JAN-09:00 18879.64 18879.64 21.21 69.88
February 0.583828E+10 0.525445E+10 20977.42 14-FEB-21:30 18879.68 18879.68 21.21 69.88
March 0.520624E+10 0.468562E+10 21008.48 27-MAR-16:00 18907.63 18907.63 23.27 69.88
April 0.104622E+11 0.941602E+10 42087.52 07-APR-14:40 37878.77 37878.77 25.51 139.76
May 0.261051E+11 0.234946E+11 42137.95 31-MAY-13:30 37924.16 37924.16 26.94 139.76
June 0.489470E+11 0.440523E+11 42204.00 15-JUN-10:10 37983.60 37983.60 28.98 139.76
July 0.640275E+11 0.576247E+11 42204.00 05-JUL-16:00 37983.60 37983.60 28.89 139.76
August 0.658101E+11 0.592291E+11 42204.00 01-AUG-10:00 37983.60 37983.60 28.94 139.76
September 0.389043E+11 0.350139E+11 42204.00 07-SEP-12:40 37983.60 37983.60 28.83 139.76
October 0.209225E+11 0.188303E+11 42117.83 25-OCT-10:20 37906.04 37906.04 26.37 139.76
November 0.502252E+10 0.452026E+10 20993.11 03-NOV-14:00 18893.79 18893.79 22.25 69.88
December 0.424492E+10 0.382043E+10 20977.36 13-DEC-07:50 18879.63 18879.63 21.21 69.88
                 
Annual Sum or Average 0.300552E+12 0.270496E+12            
Minimum of Months 0.424492E+10 0.382043E+10 20977.36   18879.63 18879.63 21.21 69.88
Maximum of Months 0.658101E+11 0.592291E+11 42204.00   37983.60 37983.60 28.98 139.76



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 45.07 45.07 106105.41 1833185.28 09-JAN-05:01
February 0.00 0.00 01-FEB-00:10 30.01 30.01 83709.07 1699049.81 13-FEB-05:11
March 0.00 0.00 01-MAR-00:10 25.53 25.53 24820.01 1253412.36 07-MAR-06:02
April 0.00 0.00 01-APR-00:10 20.83 20.83 7149.68 1181952.09 03-APR-05:01
May 0.00 0.00 01-MAY-00:10 21.89 21.89 183.71 115315.28 30-MAY-14:10
June 0.00 0.00 01-JUN-00:10 37.69 37.69 511.90 140880.44 01-JUN-14:50
July 0.00 0.00 01-JUL-00:10 43.14 43.14 180.70 61771.96 11-JUL-16:20
August 0.00 0.00 01-AUG-00:03 47.28 47.28 767.82 104413.73 22-AUG-15:50
September 0.00 0.00 01-SEP-00:03 50.55 50.55 45.80 41833.98 01-SEP-17:20
October 0.00 0.00 01-OCT-00:10 42.70 42.70 904.79 548427.29 28-OCT-05:02
November 0.00 0.00 01-NOV-00:10 22.88 22.88 25703.08 1285962.51 27-NOV-06:01
December 0.00 0.00 01-DEC-00:10 23.73 23.73 54884.21 1271144.51 26-DEC-05:01
                 
Annual Sum or Average 0.00         25121.68    
Minimum of Months 0.00 0.00   20.83 20.83 45.80 41833.98  
Maximum of Months 0.00 0.00   50.55 50.55 106105.41 1833185.28  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 2742.69 41987.23 24-JAN-06:03 8.45 8.41 0.00 0.00 01-JAN-00:01
February 3510.05 31142.94 09-FEB-13:10 8.43 8.40 0.00 0.00 01-FEB-00:10
March 9375.07 1080294.11 27-MAR-16:00 9.54 8.45 0.00 0.00 01-MAR-00:10
April 79772.35 1602500.79 07-APR-14:20 10.02 8.11 1.04 10159.02 08-APR-03:02
May 265164.88 1953237.31 30-MAY-13:15 10.61 6.70 115.41 281628.67 21-MAY-06:43
June 726840.26 2702360.10 17-JUN-05:04 13.12 7.71 2.82 35427.86 05-JUN-01:12
July 874315.65 3042866.78 24-JUL-05:04 13.69 8.01 0.00 0.00 01-JUL-00:10
August 848142.72 2626657.47 01-AUG-05:03 12.38 7.12 0.00 0.00 01-AUG-00:03
September 535781.52 2802368.72 07-SEP-05:04 12.99 7.38 9.32 84476.35 11-SEP-03:02
October 237026.46 1717397.35 05-OCT-13:10 10.71 7.27 6.30 39048.13 22-OCT-21:03
November 10328.29 674997.41 10-NOV-06:03 9.72 9.04 0.00 0.00 01-NOV-00:10
December 2331.89 37794.13 15-DEC-11:20 8.45 8.41 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 301622.01         11.42    
Minimum of Months 2331.89 31142.94   8.43 6.70 0.00 0.00  
Maximum of Months 874315.65 3042866.78   13.69 9.04 115.41 281628.67  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 9.49 44848.52 24-JAN-06:03 8.93 8.41 0.00 0.00 01-JAN-00:01
February 5.76 987.50 09-FEB-13:10 9.54 8.40 0.00 0.00 01-FEB-00:10
March 4139.52 676809.51 27-MAR-16:00 15.01 8.42 0.00 0.00 01-MAR-00:10
April 50370.96 1589602.15 07-APR-14:40 12.97 8.12 0.00 0.00 01-APR-00:10
May 175362.53 2036214.53 30-MAY-13:15 13.75 6.97 0.00 0.00 01-MAY-00:10
June 591399.63 4082642.50 27-JUN-05:02 14.88 7.98 0.00 0.00 01-JUN-00:10
July 716843.76 4169953.02 24-JUL-05:02 15.06 8.09 0.00 0.00 01-JUL-00:10
August 708275.83 4031801.49 14-AUG-05:02 14.78 7.45 0.00 0.00 01-AUG-00:03
September 415973.95 4083687.27 07-SEP-05:02 14.88 7.41 0.00 0.00 01-SEP-00:03
October 186041.97 3097743.33 06-OCT-05:02 14.39 7.84 0.00 0.00 01-OCT-00:10
November 4879.19 1124000.47 10-NOV-06:03 14.33 8.81 0.00 0.00 01-NOV-00:10
December 23.37 7006.41 13-DEC-10:00 13.41 8.40 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 239425.93         0.00    
Minimum of Months 5.76 987.50   8.93 6.97 0.00 0.00  
Maximum of Months 716843.76 4169953.02   15.06 8.81 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 156828.69 176742.47 20-JAN-16:20 21.94 18.33 0.00 0.00 01-JAN-00:01
February 297605.34 320279.96 20-FEB-16:30 24.85 18.33 0.00 0.00 01-FEB-00:10
March 452282.06 897583.64 27-MAR-16:00 36.40 26.49 0.00 0.00 01-MAR-00:10
April 654469.41 1359812.72 07-APR-13:00 45.47 32.43 0.00 0.00 01-APR-00:10
May 254457.31 892221.28 30-MAY-13:00 36.29 31.90 0.00 0.00 01-MAY-00:10
June 668650.99 1510727.95 19-JUN-12:00 48.39 40.28 0.00 0.00 01-JUN-00:10
July 1069504.03 1585903.71 07-JUL-12:00 49.85 38.79 0.00 0.00 01-JUL-00:10
August 1268037.69 1777267.91 24-AUG-16:00 53.53 39.94 0.00 0.00 01-AUG-00:03
September 388023.44 965621.24 01-SEP-14:00 37.74 33.11 0.00 0.00 01-SEP-00:03
October 392926.86 854053.20 04-OCT-13:00 35.54 28.18 0.00 0.00 01-OCT-00:10
November 453743.55 655842.85 03-NOV-14:00 31.59 21.94 0.00 0.00 01-NOV-00:10
December 581746.58 598082.20 17-DEC-16:07 30.44 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 555421.51         0.00    
Minimum of Months 156828.69 176742.47   21.94 18.33 0.00 0.00  
Maximum of Months 1268037.69 1777267.91   53.53 40.28 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:01 57.09 57.09 15962.24 53799.88 31-JAN-13:00
February 0.00 0.00 01-FEB-00:10 56.78 56.78 16193.60 53874.81 09-FEB-13:00
March 0.00 0.00 01-MAR-00:10 56.57 56.57 16763.29 53456.28 01-MAR-12:20
April 0.00 0.00 01-APR-00:10 56.80 56.80 15062.79 51248.39 03-APR-11:40
May 0.00 0.00 01-MAY-00:10 56.84 56.84 14544.33 48331.83 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 57.41 57.41 13888.90 44836.21 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 56.51 56.51 12288.09 41926.21 03-JUL-11:40
August 0.00 0.00 01-AUG-00:03 57.02 57.02 13151.15 40982.77 31-AUG-11:40
September 0.00 0.00 01-SEP-00:03 56.66 56.66 12771.92 42847.30 29-SEP-11:20
October 0.00 0.00 01-OCT-00:10 56.84 56.84 13502.36 46142.96 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 56.75 56.75 14628.84 49520.12 30-NOV-13:00
December 0.00 0.00 01-DEC-00:10 56.34 56.34 15014.84 52220.11 29-DEC-13:00
                 
Annual Sum or Average 0.00         14471.26    
Minimum of Months 0.00 0.00   56.34 56.34 12288.09 40982.77  
Maximum of Months 0.00 0.00   57.41 57.41 16763.29 53874.81  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 148.09 32501.51 04-JAN-09:00 21.21 20.28 3603.66 171740.92 10-JAN-10:30
February 142.52 33248.82 14-FEB-21:30 21.21 20.28 4309.72 170631.98 07-FEB-13:30
March 4157.01 634193.55 27-MAR-16:00 23.27 21.10 2991.59 160447.51 16-MAR-13:10
April 50750.39 2578234.17 07-APR-14:40 25.51 21.29 1731.46 134835.52 04-APR-09:00
May 195160.50 3412561.13 31-MAY-13:30 26.94 23.76 918.31 94636.67 13-MAY-10:30
June 975023.78 5500317.06 15-JUN-12:10 30.52 27.36 232.48 59848.38 09-JUN-06:10
July 1781012.58 6060086.24 20-JUL-13:10 31.47 28.10 1.18 5276.84 11-JUL-03:00
August 1524004.51 6392153.19 02-AUG-13:40 32.04 28.51 220.66 40037.63 29-AUG-03:45
September 626118.62 4895482.25 07-SEP-14:00 29.48 26.32 283.91 79906.24 23-SEP-11:30
October 202471.36 3079811.55 25-OCT-10:20 26.37 23.15 526.73 100618.19 26-OCT-11:50
November 5125.21 336963.55 03-NOV-14:00 22.25 21.10 2412.94 152943.66 29-NOV-07:20
December 98.16 32241.91 13-DEC-07:50 21.21 20.28 3068.50 171177.79 22-DEC-10:10
                 
Annual Sum or Average 451049.72         1676.02    
Minimum of Months 98.16 32241.91   21.21 20.28 1.18 5276.84  
Maximum of Months 1781012.58 6392153.19   32.04 28.51 4309.72 171740.92  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.322568E+10 0.00 18841006.08 0.321762E+10 0.00 0.00
February 0.225140E+10 0.00 16076007.78 0.332505E+10 0.00 0.00
March 0.449857E+09 0.00 0.114333E+10 0.567218E+10 0.00 0.00
April 52401547.24 0.00 0.119550E+11 0.742200E+10 0.00 0.00
May 9988412.96 0.00 0.354743E+11 0.767479E+10 0.00 0.00
June 0.107357E+09 0.00 0.120795E+12 0.109585E+11 0.00 0.00
July 35833800.26 0.00 0.166254E+12 0.129926E+11 0.00 0.00
August 0.129561E+09 0.00 0.170332E+12 0.152963E+11 0.00 0.00
September 10587846.38 0.00 0.797612E+11 0.844461E+10 0.00 0.00
October 12548123.97 0.00 0.378106E+11 0.797692E+10 0.00 0.00
November 0.291969E+09 0.00 0.110735E+10 0.525252E+10 0.00 0.00
December 0.779541E+09 0.00 11156552.39 0.469038E+10 0.00 0.00
             
Annual Sum or Average 0.735672E+10 0.00 0.624678E+12 0.929234E+11 0.00 0.00
Minimum of Months 9988412.96 0.00 11156552.39 0.321762E+10 0.00 0.00
Maximum of Months 0.322568E+10 0.00 0.170332E+12 0.152963E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.236766E+12 0.00 50727843.69 0.321838E+11 0.00 0.00
February 0.164061E+12 0.00 4552358.87 0.285889E+11 0.00 0.00
March 0.515609E+11 0.00 0.652141E+10 0.328917E+11 0.00 0.00
April 0.132691E+11 0.00 0.786206E+11 0.389968E+11 0.00 0.00
May 0.114491E+09 0.00 0.298317E+12 0.576550E+11 0.00 0.00
June 0.112838E+10 0.00 0.100096E+13 0.839093E+11 0.00 0.00
July 0.377969E+09 0.00 0.132677E+13 0.951085E+11 0.00 0.00
August 0.182212E+10 0.00 0.129637E+13 0.106209E+12 0.00 0.00
September 0.149381E+09 0.00 0.690689E+12 0.658854E+11 0.00 0.00
October 0.126783E+10 0.00 0.294965E+12 0.507770E+11 0.00 0.00
November 0.503911E+11 0.00 0.783271E+10 0.304954E+11 0.00 0.00
December 0.116518E+12 0.00 15505479.75 0.286613E+11 0.00 0.00
             
Annual Sum or Average 0.637427E+12 0.00 0.500112E+13 0.651362E+12 0.00 0.00
Minimum of Months 0.114491E+09 0.00 4552358.87 0.285889E+11 0.00 0.00
Maximum of Months 0.236766E+12 0.00 0.132677E+13 0.106209E+12 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.457399E+11 0.00 17100433.12 0.395796E+10 0.00 0.00
February 0.372589E+11 0.00 11946115.34 0.342466E+10 0.00 0.00
March 0.148298E+11 0.00 0.596599E+09 0.337347E+10 0.00 0.00
April 0.529619E+10 0.00 0.801909E+10 0.362985E+10 0.00 0.00
May 0.272537E+09 0.00 0.313793E+11 0.550525E+10 0.00 0.00
June 64024185.51 0.00 0.108731E+12 0.885780E+10 0.00 0.00
July 46715621.23 0.00 0.148916E+12 0.106272E+11 0.00 0.00
August 93737170.25 0.00 0.144224E+12 0.117025E+11 0.00 0.00
September 7910876.99 0.00 0.709912E+11 0.635927E+10 0.00 0.00
October 0.127448E+10 0.00 0.277737E+11 0.433162E+10 0.00 0.00
November 0.162630E+11 0.00 0.601500E+09 0.308995E+10 0.00 0.00
December 0.303338E+11 0.00 16443966.69 0.342981E+10 0.00 0.00
             
Annual Sum or Average 0.151481E+12 0.00 0.541278E+12 0.682893E+11 0.00 0.00
Minimum of Months 7910876.99 0.00 11946115.34 0.308995E+10 0.00 0.00
Maximum of Months 0.457399E+11 0.00 0.148916E+12 0.117025E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 6817986.26 0.127455E+11 0.00 0.00
February 0.00 0.00 55406.60 0.117914E+11 0.00 0.00
March 0.00 0.00 0.583547E+09 0.142060E+11 0.00 0.00
April 0.00 0.00 0.529742E+10 0.132029E+11 0.00 0.00
May 0.00 0.00 0.156082E+11 0.140503E+11 0.00 0.00
June 0.00 0.00 0.662030E+11 0.141291E+11 0.00 0.00
July 0.00 0.00 0.958121E+11 0.138260E+11 0.00 0.00
August 0.00 0.00 0.964099E+11 0.153191E+11 0.00 0.00
September 0.00 0.00 0.500455E+11 0.143894E+11 0.00 0.00
October 0.00 0.00 0.191459E+11 0.145526E+11 0.00 0.00
November 0.00 0.00 0.140696E+09 0.138265E+11 0.00 0.00
December 0.00 0.00 11741.56 0.131822E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.349253E+12 0.165221E+12 0.00 0.00
Minimum of Months 0.00 0.00 11741.56 0.117914E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.964099E+11 0.153191E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.396097E+12 0.177017E+12 0.00 1.10
February 0.00 0.00 0.626983E+12 0.209782E+12 0.00 1.28
March 0.00 0.00 0.996386E+12 0.282151E+12 0.00 0.74
April 0.00 0.00 0.125900E+13 0.325533E+12 0.00 0.30
May 0.00 0.00 0.417433E+12 0.180567E+12 0.00 0.06
June 0.00 0.00 0.728954E+12 0.253151E+12 0.00 0.00
July 0.00 0.00 0.109759E+13 0.354838E+12 0.00 0.00
August 0.00 0.00 0.140470E+13 0.423302E+12 0.00 0.00
September 0.00 0.00 0.421576E+12 0.183147E+12 0.00 0.01
October 0.00 0.00 0.722551E+12 0.237355E+12 0.00 0.25
November 0.00 0.00 0.970057E+12 0.272916E+12 0.00 0.46
December 0.00 0.00 0.129092E+13 0.330991E+12 0.00 1.09
             
Annual Sum or Average 0.00 0.00 0.103322E+14 0.323075E+13 0.00 5.29
Minimum of Months 0.00 0.00 0.396097E+12 0.177017E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.140470E+13 0.423302E+12 0.00 1.28



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.401752E+10 0.227389E+10 0.00 0.00
February 0.00 0.00 0.994988E+10 0.329384E+10 0.00 0.00
March 0.00 0.00 0.183988E+11 0.489072E+10 0.00 0.00
April 0.00 0.00 0.242534E+11 0.585432E+10 0.00 0.00
May 0.00 0.00 0.709887E+10 0.286911E+10 0.00 0.00
June 0.00 0.00 0.140240E+11 0.443121E+10 0.00 0.00
July 0.00 0.00 0.216966E+11 0.647581E+10 0.00 0.00
August 0.00 0.00 0.282205E+11 0.797359E+10 0.00 0.00
September 0.00 0.00 0.743419E+10 0.297006E+10 0.00 0.00
October 0.00 0.00 0.133911E+11 0.404712E+10 0.00 0.00
November 0.00 0.00 0.178332E+11 0.470732E+10 0.00 0.00
December 0.00 0.00 0.241972E+11 0.592246E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.190515E+12 0.557094E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.401752E+10 0.227389E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.282205E+11 0.797359E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.101366E+11 0.158395E+11 0.00 0.00
February 0.00 0.00 0.667382E+11 0.260447E+11 0.00 0.00
March 0.00 0.00 0.154098E+12 0.429719E+11 0.00 0.00
April 0.00 0.00 0.218478E+12 0.537748E+11 0.00 0.00
May 0.00 0.00 0.611662E+11 0.261391E+11 0.00 0.00
June 0.00 0.00 0.132004E+12 0.419367E+11 0.00 0.00
July 0.00 0.00 0.207065E+12 0.618024E+11 0.00 0.00
August 0.00 0.00 0.268871E+12 0.760071E+11 0.00 0.00
September 0.00 0.00 0.660553E+11 0.273861E+11 0.00 0.00
October 0.00 0.00 0.117760E+12 0.368178E+11 0.00 0.00
November 0.00 0.00 0.146515E+12 0.408532E+11 0.00 0.00
December 0.00 0.00 0.199576E+12 0.512929E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.164846E+13 0.500866E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.101366E+11 0.158395E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.268871E+12 0.760071E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.365781E+09 0.146319E+10 0.00 0.00
February 0.00 0.00 0.473350E+10 0.224441E+10 0.00 0.00
March 0.00 0.00 0.136897E+11 0.402283E+10 0.00 0.00
April 0.00 0.00 0.207394E+11 0.522808E+10 0.00 0.00
May 0.00 0.00 0.568150E+10 0.256085E+10 0.00 0.00
June 0.00 0.00 0.132322E+11 0.423248E+10 0.00 0.00
July 0.00 0.00 0.208800E+11 0.625304E+10 0.00 0.00
August 0.00 0.00 0.270186E+11 0.767035E+10 0.00 0.00
September 0.00 0.00 0.635005E+10 0.271801E+10 0.00 0.00
October 0.00 0.00 0.107442E+11 0.352179E+10 0.00 0.00
November 0.00 0.00 0.126838E+11 0.376689E+10 0.00 0.00
December 0.00 0.00 0.176116E+11 0.475743E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.153730E+12 0.484394E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.365781E+09 0.146319E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.270186E+11 0.767035E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.321762E+10 18841006.08 0.322568E+10 0.182695E+11 0.00 0.00 0.00 0.00
February 0.332505E+10 16076007.78 0.225140E+10 0.166638E+11 0.00 0.00 0.00 0.00
March 0.567218E+10 0.114333E+10 0.449857E+09 0.481813E+10 0.00 0.00 0.00 0.00
April 0.742200E+10 0.119550E+11 52401547.24 0.488048E+09 12219509.69 0.00 0.00 0.00
May 0.767479E+10 0.354743E+11 9988412.96 0.00 0.260178E+09 0.00 0.00 0.00
June 0.109585E+11 0.120795E+12 0.107357E+09 0.00 0.407412E+10 0.00 0.00 0.00
July 0.129926E+11 0.166254E+12 35833800.26 0.00 0.165496E+11 0.00 0.00 0.00
August 0.152963E+11 0.170332E+12 0.129561E+09 0.00 0.163643E+11 0.00 0.00 0.00
September 0.844461E+10 0.797612E+11 10587846.38 0.00 0.225720E+10 0.00 0.00 0.00
October 0.797692E+10 0.378106E+11 12548123.97 57880580.23 32262931.19 0.00 0.00 0.00
November 0.525252E+10 0.110735E+10 0.291969E+09 0.282121E+10 0.00 0.00 0.00 0.00
December 0.469038E+10 11156552.39 0.779541E+09 0.670440E+10 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.929234E+11 0.624678E+12 0.735672E+10 0.498229E+11 0.395499E+11 0.00 0.00 0.00
Minimum of Months 0.321762E+10 11156552.39 9988412.96 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152963E+11 0.170332E+12 0.322568E+10 0.182695E+11 0.165496E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.321838E+11 50727843.69 0.236766E+12 0.218466E+12 0.00 0.00 0.00 0.00
February 0.285889E+11 4598398.06 0.164061E+12 0.219398E+12 0.00 0.00 0.00 0.00
March 0.328917E+11 0.652141E+10 0.515609E+11 0.100407E+12 0.00 0.00 0.00 0.00
April 0.389968E+11 0.786206E+11 0.132691E+11 0.147317E+11 0.151201E+09 0.00 0.00 0.00
May 0.576550E+11 0.298317E+12 0.114491E+09 30467670.68 0.260390E+10 0.00 0.00 0.00
June 0.839093E+11 0.100096E+13 0.112838E+10 0.00 0.407854E+11 0.00 0.00 0.00
July 0.951085E+11 0.132677E+13 0.377969E+09 0.00 0.164911E+12 0.00 0.00 0.00
August 0.106209E+12 0.129637E+13 0.182212E+10 0.00 0.163477E+12 0.00 0.00 0.00
September 0.658854E+11 0.690689E+12 0.149381E+09 0.00 0.232607E+11 0.00 0.00 0.00
October 0.507770E+11 0.294965E+12 0.126783E+10 0.165772E+10 0.400481E+09 0.00 0.00 0.00
November 0.304954E+11 0.783271E+10 0.503911E+11 0.634059E+11 0.00 0.00 0.00 0.00
December 0.286613E+11 15505479.75 0.116518E+12 0.154430E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.651362E+12 0.500112E+13 0.637427E+12 0.772526E+12 0.395590E+12 0.00 0.00 0.00
Minimum of Months 0.285889E+11 4598398.06 0.114491E+09 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106209E+12 0.132677E+13 0.236766E+12 0.219398E+12 0.164911E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.395796E+10 17100433.12 0.457399E+11 0.252456E+11 0.00 0.00 0.00 0.00
February 0.342466E+10 11946115.34 0.372589E+11 0.250676E+11 0.00 0.00 0.00 0.00
March 0.337347E+10 0.596599E+09 0.148298E+11 0.128970E+11 0.00 0.00 0.00 0.00
April 0.362985E+10 0.801909E+10 0.529619E+10 0.276442E+10 3539211.18 0.00 0.00 0.00
May 0.550525E+10 0.313793E+11 0.272537E+09 22983738.08 0.179293E+09 0.00 0.00 0.00
June 0.885780E+10 0.108731E+12 64024185.51 0.00 0.339595E+10 0.00 0.00 0.00
July 0.106272E+11 0.148916E+12 46715621.23 0.00 0.148584E+11 0.00 0.00 0.00
August 0.117025E+11 0.144224E+12 93737170.25 0.00 0.150674E+11 0.00 0.00 0.00
September 0.635927E+10 0.709912E+11 7910876.99 0.00 0.184598E+10 0.00 0.00 0.00
October 0.433162E+10 0.277737E+11 0.127448E+10 0.473075E+09 0.00 0.00 0.00 0.00
November 0.308995E+10 0.601500E+09 0.162630E+11 0.843917E+10 0.00 0.00 0.00 0.00
December 0.342981E+10 16443966.69 0.303338E+11 0.196799E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.682893E+11 0.541278E+12 0.151481E+12 0.945897E+11 0.353506E+11 0.00 0.00 0.00
Minimum of Months 0.308995E+10 11946115.34 7910876.99 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117025E+11 0.148916E+12 0.457399E+11 0.252456E+11 0.150674E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.127455E+11 6817986.26 0.00 0.00 0.00 0.00 0.00 0.00
February 0.117914E+11 55406.60 0.00 0.00 0.00 0.00 0.00 0.00
March 0.142060E+11 0.583547E+09 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132029E+11 0.529742E+10 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140503E+11 0.156082E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141291E+11 0.662030E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138260E+11 0.958121E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153191E+11 0.964099E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143894E+11 0.500455E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145526E+11 0.191459E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138265E+11 0.140696E+09 0.00 0.00 0.00 0.00 0.00 0.00
December 0.131822E+11 11741.56 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.165221E+12 0.349253E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.117914E+11 11741.56 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153191E+11 0.964099E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.945869E+11 0.316612E+12 0.00 0.00 0.00 0.293178E+10 0.00 0.00
February 0.854333E+11 0.506080E+12 0.00 0.00 0.00 0.343091E+10 0.00 0.00
March 0.945869E+11 0.810809E+12 0.00 0.00 0.00 0.197811E+10 0.00 0.00
April 0.915357E+11 0.102580E+13 0.00 0.00 0.00 0.796044E+09 0.00 0.00
May 0.945869E+11 0.331621E+12 0.00 0.00 0.00 0.167591E+09 0.00 0.00
June 0.915357E+11 0.567339E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.945869E+11 0.837339E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.945869E+11 0.107599E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.915357E+11 0.329990E+12 0.00 0.00 0.00 25619998.77 0.00 0.00
October 0.945869E+11 0.580454E+12 0.00 0.00 0.00 0.667964E+09 0.00 0.00
November 0.915357E+11 0.789920E+12 0.00 0.00 0.00 0.123769E+10 0.00 0.00
December 0.945869E+11 0.105746E+13 0.00 0.00 0.00 0.292862E+10 0.00 0.00
                 
Annual Sum or Average 0.111368E+13 0.822941E+13 0.00 0.00 0.00 0.141643E+11 0.00 0.00
Minimum of Months 0.854333E+11 0.316612E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.945869E+11 0.107599E+13 0.00 0.00 0.00 0.343091E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.141698E+10 0.316061E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127985E+10 0.793589E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.141698E+10 0.149250E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137127E+10 0.197704E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141698E+10 0.564674E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137127E+10 0.109641E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141698E+10 0.166377E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141698E+10 0.216639E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137127E+10 0.583540E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.141698E+10 0.107610E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137127E+10 0.144972E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.141698E+10 0.196917E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.166838E+11 0.151490E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127985E+10 0.316061E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141698E+10 0.216639E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135195E+11 0.781669E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122112E+11 0.529047E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.135195E+11 0.124645E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.130834E+11 0.177787E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135195E+11 0.485466E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130834E+11 0.103151E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.135195E+11 0.158782E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135195E+11 0.206384E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.130834E+11 0.517526E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135195E+11 0.944614E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.130834E+11 0.118746E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135195E+11 0.161803E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.159181E+12 0.130678E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122112E+11 0.781669E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135195E+11 0.206384E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.137808E+10 0.280669E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124472E+10 0.373381E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137808E+10 0.110449E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133363E+10 0.168449E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137808E+10 0.449874E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133363E+10 0.103334E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137808E+10 0.160051E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137808E+10 0.207263E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133363E+10 0.496566E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137808E+10 0.860050E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133363E+10 0.102506E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137808E+10 0.142322E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.162258E+11 0.121517E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124472E+10 0.280669E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137808E+10 0.207263E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.321762E+10 0.322568E+10 18841006.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.332505E+10 0.225140E+10 16076007.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.567218E+10 0.449857E+09 0.114333E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.742200E+10 52401547.24 0.119550E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.767479E+10 9988412.96 0.354743E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.109585E+11 0.107357E+09 0.120795E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129926E+11 35833800.26 0.166254E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.152963E+11 0.129561E+09 0.170332E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.844461E+10 10587846.38 0.797612E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.797692E+10 12548123.97 0.378106E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.525252E+10 0.291969E+09 0.110735E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.469038E+10 0.779541E+09 11156552.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.929234E+11 0.735672E+10 0.624678E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.321762E+10 9988412.96 11156552.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152963E+11 0.322568E+10 0.170332E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.321838E+11 0.236766E+12 50727843.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.285889E+11 0.164061E+12 4552358.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.328917E+11 0.515609E+11 0.652141E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.389968E+11 0.132691E+11 0.786206E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.576550E+11 0.114491E+09 0.298317E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.839093E+11 0.112838E+10 0.100096E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.951085E+11 0.377969E+09 0.132677E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.106209E+12 0.182212E+10 0.129637E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.658854E+11 0.149381E+09 0.690689E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.507770E+11 0.126783E+10 0.294965E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.304954E+11 0.503911E+11 0.783271E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.286613E+11 0.116518E+12 15505479.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.651362E+12 0.637427E+12 0.500112E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.285889E+11 0.114491E+09 4552358.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.106209E+12 0.236766E+12 0.132677E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.395796E+10 0.457399E+11 17100433.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342466E+10 0.372589E+11 11946115.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.337347E+10 0.148298E+11 0.596599E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.362985E+10 0.529619E+10 0.801909E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.550525E+10 0.272537E+09 0.313793E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.885780E+10 64024185.51 0.108731E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.106272E+11 46715621.23 0.148916E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.117025E+11 93737170.25 0.144224E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.635927E+10 7910876.99 0.709912E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.433162E+10 0.127448E+10 0.277737E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.308995E+10 0.162630E+11 0.601500E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.342981E+10 0.303338E+11 16443966.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.682893E+11 0.151481E+12 0.541278E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.308995E+10 7910876.99 11946115.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.117025E+11 0.457399E+11 0.148916E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.127455E+11 0.00 6817986.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.117914E+11 0.00 55406.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.142060E+11 0.00 0.583547E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.132029E+11 0.00 0.529742E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.140503E+11 0.00 0.156082E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.141291E+11 0.00 0.662030E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.138260E+11 0.00 0.958121E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153191E+11 0.00 0.964099E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143894E+11 0.00 0.500455E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.145526E+11 0.00 0.191459E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.138265E+11 0.00 0.140696E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.131822E+11 0.00 11741.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.165221E+12 0.00 0.349253E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.117914E+11 0.00 11741.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153191E+11 0.00 0.964099E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.945869E+11 0.00 0.396097E+12 0.00 0.794855E+11 0.00 0.00 0.00 0.294498E+10 0.00 0.00 0.00
February 0.854333E+11 0.00 0.626983E+12 0.00 0.120902E+12 0.00 0.00 0.00 0.344635E+10 0.00 0.00 0.00
March 0.945869E+11 0.00 0.996386E+12 0.00 0.185577E+12 0.00 0.00 0.00 0.198702E+10 0.00 0.00 0.00
April 0.915357E+11 0.00 0.125900E+13 0.00 0.233198E+12 0.00 0.00 0.00 0.799627E+09 0.00 0.00 0.00
May 0.945869E+11 0.00 0.417433E+12 0.00 0.858120E+11 0.00 0.00 0.00 0.168346E+09 0.00 0.00 0.00
June 0.915357E+11 0.00 0.728954E+12 0.00 0.161615E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.945869E+11 0.00 0.109759E+13 0.00 0.260251E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.945869E+11 0.00 0.140470E+13 0.00 0.328715E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.915357E+11 0.00 0.421576E+12 0.00 0.915860E+11 0.00 0.00 0.00 25735324.77 0.00 0.00 0.00
October 0.945869E+11 0.00 0.722551E+12 0.00 0.142098E+12 0.00 0.00 0.00 0.670971E+09 0.00 0.00 0.00
November 0.915357E+11 0.00 0.970057E+12 0.00 0.180137E+12 0.00 0.00 0.00 0.124326E+10 0.00 0.00 0.00
December 0.945869E+11 0.00 0.129092E+13 0.00 0.233462E+12 0.00 0.00 0.00 0.294180E+10 0.00 0.00 0.00
                         
Annual Sum or Average 0.111368E+13 0.00 0.103322E+14 0.00 0.210284E+13 0.00 0.00 0.00 0.142281E+11 0.00 0.00 0.00
Minimum of Months 0.854333E+11 0.00 0.396097E+12 0.00 0.794855E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.945869E+11 0.00 0.140470E+13 0.00 0.328715E+12 0.00 0.00 0.00 0.344635E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.141698E+10 0.00 0.401752E+10 0.00 0.856909E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.127985E+10 0.00 0.994988E+10 0.00 0.201398E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.141698E+10 0.00 0.183988E+11 0.00 0.347374E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.137127E+10 0.00 0.242534E+11 0.00 0.448305E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.141698E+10 0.00 0.709887E+10 0.00 0.145213E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.137127E+10 0.00 0.140240E+11 0.00 0.305994E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.141698E+10 0.00 0.216966E+11 0.00 0.505883E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.141698E+10 0.00 0.282205E+11 0.00 0.655661E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.137127E+10 0.00 0.743419E+10 0.00 0.159879E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.141698E+10 0.00 0.133911E+11 0.00 0.263014E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.137127E+10 0.00 0.178332E+11 0.00 0.333604E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.141698E+10 0.00 0.241972E+11 0.00 0.450548E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.166838E+11 0.00 0.190515E+12 0.00 0.390256E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.127985E+10 0.00 0.401752E+10 0.00 0.856909E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.141698E+10 0.00 0.282205E+11 0.00 0.655661E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135195E+11 0.00 0.101366E+11 0.00 0.231994E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122112E+11 0.00 0.667382E+11 0.00 0.138335E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.135195E+11 0.00 0.154098E+12 0.00 0.294524E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.130834E+11 0.00 0.218478E+12 0.00 0.406914E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135195E+11 0.00 0.611662E+11 0.00 0.126196E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.130834E+11 0.00 0.132004E+12 0.00 0.288533E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.135195E+11 0.00 0.207065E+12 0.00 0.482828E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135195E+11 0.00 0.268871E+12 0.00 0.624876E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.130834E+11 0.00 0.660553E+11 0.00 0.143027E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135195E+11 0.00 0.117760E+12 0.00 0.232982E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.130834E+11 0.00 0.146515E+12 0.00 0.277698E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135195E+11 0.00 0.199576E+12 0.00 0.377734E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.159181E+12 0.00 0.164846E+13 0.00 0.341685E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122112E+11 0.00 0.101366E+11 0.00 0.231994E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135195E+11 0.00 0.268871E+12 0.00 0.624876E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.137808E+10 0.00 0.365781E+09 0.00 85111568.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.124472E+10 0.00 0.473350E+10 0.00 0.999694E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.137808E+10 0.00 0.136897E+11 0.00 0.264475E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.133363E+10 0.00 0.207394E+11 0.00 0.389446E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.137808E+10 0.00 0.568150E+10 0.00 0.118277E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.133363E+10 0.00 0.132322E+11 0.00 0.289886E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137808E+10 0.00 0.208800E+11 0.00 0.487496E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.137808E+10 0.00 0.270186E+11 0.00 0.629227E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.133363E+10 0.00 0.635005E+10 0.00 0.138439E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.137808E+10 0.00 0.107442E+11 0.00 0.214371E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.133363E+10 0.00 0.126838E+11 0.00 0.243326E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.137808E+10 0.00 0.176116E+11 0.00 0.337935E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.162258E+11 0.00 0.153730E+12 0.00 0.322136E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.124472E+10 0.00 0.365781E+09 0.00 85111568.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137808E+10 0.00 0.270186E+11 0.00 0.629227E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.758624E+10 0.00 0.00 71145072.67 0.00 0.00 0.519523E+11 0.00 0.43
February 0.381697E+10 0.00 0.00 74159341.04 0.00 0.00 0.526262E+11 0.00 0.42
March 0.401887E+09 0.00 0.00 0.112727E+09 0.00 0.00 0.706967E+11 0.00 0.67
April 0.400116E+09 16220266.99 0.00 99815874.72 0.00 0.00 0.627847E+11 0.00 0.90
May 0.174981E+09 0.218822E+09 0.00 98459272.32 0.00 0.00 0.569852E+11 0.00 1.26
June 0.115865E+09 0.647842E+10 0.00 53953888.96 37371031.08 0.00 0.162808E+11 0.00 0.94
July 45486452.05 0.206652E+11 0.00 10566091.35 0.127667E+09 0.00 0.115222E+10 0.00 0.38
August 91170682.94 0.173534E+11 0.00 41069769.39 0.149685E+09 0.00 0.703104E+10 0.00 0.71
September 0.227076E+09 0.435937E+10 0.00 82519386.04 4290041.45 0.00 0.315844E+11 0.00 1.12
October 0.444300E+09 0.180841E+09 0.00 0.120467E+09 0.00 0.00 0.607418E+11 0.00 1.21
November 0.438305E+09 0.00 0.00 0.121642E+09 0.00 0.00 0.734308E+11 0.00 0.80
December 0.587309E+09 0.00 0.00 0.117449E+09 0.00 0.00 0.687487E+11 0.00 0.53
                   
Annual Sum or Average 0.143297E+11 0.492723E+11 0.00 0.100397E+10 0.319013E+09 0.00 0.554015E+12 0.00 0.78
Minimum of Months 45486452.05 0.00 0.00 10566091.35 0.00 0.00 0.115222E+10 0.00 0.38
Maximum of Months 0.758624E+10 0.206652E+11 0.00 0.121642E+09 0.149685E+09 0.00 0.734308E+11 0.00 1.26



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103036E+11 0.00 0.00 36632078.56 0.00 0.00 0.258013E+11 0.00 0.33
February 0.604292E+10 0.00 0.00 45586363.08 0.00 0.00 0.305939E+11 0.00 0.35
March 0.221471E+10 0.00 0.00 89620348.68 0.00 0.00 0.533570E+11 0.00 0.53
April 0.567086E+10 17080016.32 0.00 84608467.49 0.00 0.00 0.507311E+11 0.00 0.78
May 0.345530E+10 0.148699E+09 0.00 81135613.60 0.00 0.00 0.404807E+11 0.00 0.90
June 0.223142E+10 0.496402E+10 0.00 35580307.70 0.102514E+09 0.00 0.888484E+10 0.00 0.63
July 0.265286E+09 0.978551E+10 0.00 2315131.29 0.173492E+09 0.00 0.291615E+09 0.00 0.28
August 0.292786E+10 0.659614E+10 0.00 29270500.48 0.142369E+09 0.00 0.430649E+10 0.00 0.60
September 0.266477E+10 0.317641E+10 0.00 54815900.95 32902389.30 0.00 0.201067E+11 0.00 0.72
October 0.444478E+10 0.437703E+09 0.00 84837207.81 0.00 0.00 0.395410E+11 0.00 0.82
November 0.174765E+10 0.00 0.00 85006397.49 0.00 0.00 0.518032E+11 0.00 0.58
December 0.233019E+10 0.00 0.00 82731888.53 0.00 0.00 0.483123E+11 0.00 0.41
                   
Annual Sum or Average 0.442994E+11 0.251256E+11 0.00 0.712140E+09 0.451278E+09 0.00 0.374210E+12 0.00 0.58
Minimum of Months 0.265286E+09 0.00 0.00 2315131.29 0.00 0.00 0.291615E+09 0.00 0.28
Maximum of Months 0.103036E+11 0.978551E+10 0.00 89620348.68 0.173492E+09 0.00 0.533570E+11 0.00 0.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.231777E+12 0.00 0.00 13279297.30 0.00 0.714048E+10 0.223371E+11 0.00 0.30
February 0.211990E+12 0.00 0.00 33193138.60 0.00 0.170713E+10 0.395838E+11 0.00 0.30
March 0.160482E+12 0.00 0.00 0.220120E+09 0.00 0.00 0.178863E+12 0.00 0.36
April 0.921484E+11 57284945.76 0.00 0.371894E+09 0.00 0.00 0.252285E+12 0.00 0.49
May 0.371101E+11 0.125135E+10 0.00 0.562791E+09 0.00 0.00 0.310350E+12 0.00 0.73
June 0.101081E+11 0.467360E+11 0.00 0.304883E+09 0.977898E+09 0.00 0.744865E+11 0.00 0.54
July 0.948505E+09 0.945846E+11 0.00 20398023.23 0.170427E+10 0.00 0.288309E+10 0.00 0.27
August 0.800075E+10 0.617760E+11 0.00 0.275328E+09 0.133726E+10 0.00 0.389188E+11 0.00 0.48
September 0.227969E+11 0.308408E+11 0.00 0.405587E+09 0.338498E+09 0.00 0.156174E+12 0.00 0.60
October 0.483620E+11 0.411899E+10 0.00 0.499693E+09 0.00 0.00 0.261323E+12 0.00 0.61
November 0.137191E+12 0.00 0.00 0.235577E+09 0.00 11999871.28 0.183937E+12 0.00 0.39
December 0.206005E+12 0.00 0.00 73755451.98 0.00 0.00 0.797121E+11 0.00 0.30
                   
Annual Sum or Average 0.116692E+13 0.239365E+12 0.00 0.301650E+10 0.435792E+10 0.885961E+10 0.160085E+13 0.00 0.45
Minimum of Months 0.948505E+09 0.00 0.00 13279297.30 0.00 0.00 0.288309E+10 0.00 0.27
Maximum of Months 0.231777E+12 0.945846E+11 0.00 0.562791E+09 0.170427E+10 0.714048E+10 0.310350E+12 0.00 0.73



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.186345E+11 0.00 0.00 1736.23 0.00 0.201053E+10 83937269.18 0.00 0.28
February 0.174017E+11 0.00 0.00 24866.88 0.00 0.169207E+10 0.231420E+09 0.00 0.28
March 0.222701E+11 0.00 0.00 4631660.03 0.00 0.461010E+09 0.571839E+10 0.00 0.35
April 0.139669E+11 490248.16 0.00 21544173.89 0.00 88226067.16 0.158473E+11 0.00 0.46
May 0.837418E+10 0.130636E+09 0.00 43558412.88 0.00 0.00 0.244804E+11 0.00 0.71
June 0.108464E+10 0.459258E+10 0.00 30059342.14 94646060.85 0.00 0.773716E+10 0.00 0.55
July 0.164764E+09 0.965358E+10 0.00 2719066.32 0.171347E+09 0.00 0.285974E+09 0.00 0.28
August 0.684872E+09 0.622548E+10 0.00 27812181.43 0.141914E+09 0.00 0.396544E+10 0.00 0.51
September 0.419673E+10 0.308897E+10 0.00 31617127.74 29566262.05 0.00 0.122174E+11 0.00 0.58
October 0.100611E+11 0.276995E+09 0.00 28927975.24 0.00 1485475.58 0.152256E+11 0.00 0.54
November 0.195420E+11 0.00 0.00 4414433.04 0.00 0.638217E+09 0.474943E+10 0.00 0.34
December 0.203175E+11 0.00 0.00 0.00 0.00 0.132528E+10 0.00 0.00 0.29
                   
Annual Sum or Average 0.136699E+12 0.239687E+11 0.00 0.195311E+09 0.437474E+09 0.621682E+10 0.905424E+11 0.00 0.43
Minimum of Months 0.164764E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.222701E+11 0.965358E+10 0.00 43558412.88 0.171347E+09 0.201053E+10 0.244804E+11 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.320349E+10 0.00 0.00 0.00 0.00 0.622361E+09 0.00 0.00 0.28
February 0.317100E+10 0.00 0.00 0.00 0.00 0.421034E+09 0.00 0.00 0.27
March 0.336336E+10 0.00 0.00 1637480.21 0.00 276327.98 0.148073E+10 0.00 0.37
April 0.227843E+10 2546784.38 0.00 4834359.58 0.00 0.00 0.328465E+10 0.00 0.65
May 0.100410E+10 27241074.84 0.00 7940360.08 0.00 0.00 0.422222E+10 0.00 0.91
June 0.313490E+09 0.880600E+09 0.00 4849736.63 12853908.43 0.00 0.122017E+10 0.00 0.78
July 33945859.45 0.180030E+10 0.00 437166.39 21753652.64 0.00 46821825.04 0.00 0.41
August 0.383509E+09 0.121613E+10 0.00 4141202.30 17851163.50 0.00 0.570367E+09 0.00 0.75
September 0.624392E+09 0.467309E+09 0.00 5106724.48 4125524.57 0.00 0.197076E+10 0.00 0.73
October 0.157814E+10 60175034.82 0.00 5402555.10 0.00 0.00 0.274407E+10 0.00 0.68
November 0.275494E+10 0.00 0.00 1849594.53 0.00 969797.09 0.170214E+10 0.00 0.39
December 0.393385E+10 0.00 0.00 145214.41 0.00 514011.32 0.282301E+09 0.00 0.28
                   
Annual Sum or Average 0.226426E+11 0.445430E+10 0.00 36344393.72 56584249.14 0.104516E+10 0.175242E+11 0.00 0.54
Minimum of Months 33945859.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.27
Maximum of Months 0.393385E+10 0.180030E+10 0.00 7940360.08 21753652.64 0.622361E+09 0.422222E+10 0.00 0.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.270508E+10 0.00 0.00 145929.28 0.00 0.511320E+09 0.120205E+09 0.00 0.38
February 0.263310E+10 0.00 0.00 250933.74 0.00 0.347305E+09 0.170983E+09 0.00 0.37
March 0.263232E+10 0.00 0.00 2646406.89 0.00 18297581.51 0.199875E+10 0.00 0.54
April 0.216230E+10 1864866.20 0.00 4859770.05 0.00 0.00 0.309185E+10 0.00 0.94
May 0.944485E+09 24299351.41 0.00 8377053.60 0.00 0.00 0.409402E+10 0.00 1.32
June 0.273697E+09 0.632611E+09 0.00 4305244.67 11189978.34 0.00 0.120426E+10 0.00 1.01
July 31543859.56 0.130769E+10 0.00 410828.76 18937656.45 0.00 50941829.22 0.00 0.50
August 0.337409E+09 0.934403E+09 0.00 3610866.68 15540342.00 0.00 0.579798E+09 0.00 0.99
September 0.566668E+09 0.355255E+09 0.00 5411395.58 5338139.28 0.00 0.194484E+10 0.00 1.02
October 0.143426E+10 47347768.40 0.00 5243613.14 0.00 0.00 0.269369E+10 0.00 0.98
November 0.256789E+10 0.00 0.00 1595791.98 0.00 14539752.90 0.130515E+10 0.00 0.52
December 0.336481E+10 0.00 0.00 314757.82 0.00 31490717.55 0.300565E+09 0.00 0.38
                   
Annual Sum or Average 0.196536E+11 0.330347E+10 0.00 37172592.21 51006116.07 0.922952E+09 0.175551E+11 0.00 0.75
Minimum of Months 31543859.56 0.00 0.00 145929.28 0.00 0.00 50941829.22 0.00 0.37
Maximum of Months 0.336481E+10 0.130769E+10 0.00 8377053.60 18937656.45 0.511320E+09 0.409402E+10 0.00 1.32



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.252283E+10 0.00 0.00 2805158.62 0.00 0.579872E+09 0.200734E+10 0.00 0.37
February 0.224413E+10 0.00 0.00 3677785.45 0.00 0.371543E+09 0.261578E+10 0.00 0.39
March 0.266445E+10 0.00 0.00 7567964.83 0.00 45870660.21 0.556601E+10 0.00 0.66
April 0.236231E+10 4453253.93 0.00 8034491.30 0.00 0.00 0.514505E+10 0.00 0.93
May 0.128429E+10 34235705.69 0.00 9421504.82 0.00 0.00 0.475005E+10 0.00 1.07
June 0.354244E+09 0.976115E+09 0.00 5192588.35 13581299.55 0.00 0.128274E+10 0.00 0.86
July 34422850.63 0.201217E+10 0.00 643263.98 22984672.29 0.00 48031573.48 0.00 0.47
August 0.395787E+09 0.157805E+10 0.00 6131265.33 18861344.80 0.00 0.730791E+09 0.00 0.99
September 0.545652E+09 0.642024E+09 0.00 11921588.28 4358984.30 0.00 0.350191E+10 0.00 1.17
October 0.100579E+10 0.145167E+09 0.00 15472352.28 0.00 0.00 0.727026E+10 0.00 1.35
November 0.215856E+10 0.00 0.00 6924496.38 0.00 30567760.61 0.509650E+10 0.00 0.67
December 0.290369E+10 0.00 0.00 4709423.68 0.00 73643786.57 0.327358E+10 0.00 0.41
                   
Annual Sum or Average 0.184761E+11 0.539222E+10 0.00 82501883.30 59786300.94 0.110150E+10 0.412880E+11 0.00 0.78
Minimum of Months 34422850.63 0.00 0.00 643263.98 0.00 0.00 48031573.48 0.00 0.37
Maximum of Months 0.290369E+10 0.201217E+10 0.00 15472352.28 22984672.29 0.579872E+09 0.727026E+10 0.00 1.35



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.361168E+10 0.00 0.00 513138.27 0.00 0.137243E+09 0.504676E+09 0.00 0.48
February 0.282315E+10 0.00 0.00 1455668.94 0.00 43870189.57 0.137152E+10 0.00 0.50
March 0.110339E+10 0.00 0.00 8495631.35 0.00 0.00 0.626244E+10 0.00 0.90
April 0.635075E+09 4920091.59 0.00 14195191.65 0.00 0.00 0.815792E+10 0.00 1.63
May 0.550419E+09 32546692.97 0.00 11370805.13 0.00 0.00 0.564546E+10 0.00 1.66
June 0.213134E+09 0.104045E+10 0.00 6975104.38 10477031.55 0.00 0.160511E+10 0.00 1.44
July 20291273.91 0.213545E+10 0.00 1321722.82 12411319.95 0.00 69923188.95 0.00 0.76
August 0.197600E+09 0.167331E+10 0.00 8008093.92 8991116.72 0.00 0.104477E+10 0.00 1.59
September 0.375034E+09 0.533503E+09 0.00 7946327.92 3699083.72 0.00 0.263861E+10 0.00 1.33
October 0.719135E+09 90603966.99 0.00 10701744.58 0.00 0.00 0.515325E+10 0.00 1.47
November 0.122095E+10 0.00 0.00 6006162.29 0.00 0.00 0.465869E+10 0.00 0.82
December 0.165102E+10 0.00 0.00 4502839.29 0.00 0.00 0.375033E+10 0.00 0.55
                   
Annual Sum or Average 0.131209E+11 0.551078E+10 0.00 81492430.54 35578551.94 0.181113E+09 0.408627E+11 0.00 1.10
Minimum of Months 20291273.91 0.00 0.00 513138.27 0.00 0.00 69923188.95 0.00 0.48
Maximum of Months 0.361168E+10 0.213545E+10 0.00 14195191.65 12411319.95 0.137243E+09 0.815792E+10 0.00 1.66



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.835971E+10 0.00 0.00 0.00 0.00 0.258545E+11 0.00 0.00 0.31
February 0.857080E+10 0.00 0.00 0.00 0.00 0.244547E+11 0.00 0.00 0.31
March 0.294545E+11 0.00 0.00 264731.85 0.00 0.101922E+11 0.482392E+09 0.00 0.34
April 0.283408E+11 8117065.72 0.00 12241985.73 0.00 0.204431E+10 0.689295E+10 0.00 0.43
May 0.157576E+11 0.242735E+09 0.00 47233388.50 0.00 0.00 0.238674E+11 0.00 0.70
June 0.184455E+10 0.848878E+10 0.00 38128691.95 0.122814E+09 0.00 0.968414E+10 0.00 0.68
July 0.124002E+09 0.182571E+11 0.00 3271665.20 0.214038E+09 0.00 0.454255E+09 0.00 0.42
August 0.121342E+10 0.121469E+11 0.00 35384985.31 0.167946E+09 0.00 0.480396E+10 0.00 0.63
September 0.926747E+10 0.447073E+10 0.00 32199971.06 54740012.07 0.00 0.109494E+11 0.00 0.59
October 0.232249E+11 0.535251E+09 0.00 17582399.16 115070.53 0.189539E+09 0.809688E+10 0.00 0.51
November 0.265997E+11 0.00 0.00 203218.89 0.00 0.944129E+10 0.297988E+09 0.00 0.34
December 0.143259E+11 0.00 0.00 0.00 0.00 0.216391E+11 0.00 0.00 0.29
                   
Annual Sum or Average 0.167083E+12 0.441496E+11 0.00 0.186511E+09 0.559652E+09 0.938157E+11 0.655294E+11 0.00 0.46
Minimum of Months 0.124002E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.294545E+11 0.182571E+11 0.00 47233388.50 0.214038E+09 0.258545E+11 0.238674E+11 0.00 0.70



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.103402E+11 0.00 0.00 0.00 0.00 0.206275E+11 0.00 0.00 0.43
February 0.129373E+11 0.00 0.00 0.00 0.00 0.170201E+11 0.00 0.00 0.43
March 0.261784E+11 0.00 0.00 6456924.96 0.00 0.583564E+10 0.626471E+10 0.00 0.50
April 0.201923E+11 7663826.55 0.00 30268479.17 0.00 0.171939E+10 0.187930E+11 0.00 0.75
May 0.140836E+11 0.236441E+09 0.00 64473760.96 0.00 0.00 0.308616E+11 0.00 1.20
June 0.150641E+10 0.677692E+10 0.00 42225236.05 0.145105E+09 0.00 0.117129E+11 0.00 1.01
July 0.112374E+09 0.152469E+11 0.00 4270799.46 0.199152E+09 0.00 0.603848E+09 0.00 0.58
August 0.100118E+10 0.111670E+11 0.00 42197212.30 0.156266E+09 0.00 0.639830E+10 0.00 1.00
September 0.742589E+10 0.365294E+10 0.00 44801918.33 0.194848E+09 0.00 0.148559E+11 0.00 0.94
October 0.160932E+11 0.490034E+09 0.00 32830188.53 0.00 0.142340E+09 0.168355E+11 0.00 0.84
November 0.245685E+11 0.00 0.00 2410263.58 0.00 0.645706E+10 0.280699E+10 0.00 0.49
December 0.166639E+11 0.00 0.00 0.00 0.00 0.166566E+11 0.00 0.00 0.42
                   
Annual Sum or Average 0.151103E+12 0.375779E+11 0.00 0.269935E+09 0.695371E+09 0.684586E+11 0.109133E+12 0.00 0.72
Minimum of Months 0.112374E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.261784E+11 0.152469E+11 0.00 64473760.96 0.199152E+09 0.206275E+11 0.308616E+11 0.00 1.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.151749E+11 0.00 0.00 17419002.38 0.00 0.140247E+11 0.113733E+11 0.00 0.36
February 0.153969E+11 0.00 0.00 24755094.42 0.00 0.113316E+11 0.164279E+11 0.00 0.39
March 0.228659E+11 0.00 0.00 53701076.31 0.00 0.478289E+10 0.376436E+11 0.00 0.57
April 0.206828E+11 20073907.90 0.00 55339153.63 0.00 0.176636E+10 0.332212E+11 0.00 0.71
May 0.148797E+11 0.315734E+09 0.00 72261624.21 0.00 0.00 0.358113E+11 0.00 0.92
June 0.240766E+10 0.968326E+10 0.00 43373076.78 0.128653E+09 0.00 0.107329E+11 0.00 0.78
July 0.129671E+09 0.210280E+11 0.00 5007557.42 0.224215E+09 0.00 0.456195E+09 0.00 0.49
August 0.112909E+10 0.168920E+11 0.00 61169747.95 0.175931E+09 0.00 0.685047E+10 0.00 0.92
September 0.632569E+10 0.673662E+10 0.00 0.110239E+09 60114899.65 0.00 0.297603E+11 0.00 1.10
October 0.955017E+10 0.166994E+10 0.00 0.134980E+09 0.00 0.00 0.616638E+11 0.00 1.22
November 0.192905E+11 0.00 0.00 47842873.66 0.00 0.408019E+10 0.338613E+11 0.00 0.57
December 0.182789E+11 0.00 0.00 24254825.66 0.00 0.113845E+11 0.162584E+11 0.00 0.37
                   
Annual Sum or Average 0.146112E+12 0.563456E+11 0.00 0.650343E+09 0.588914E+09 0.473702E+11 0.294061E+12 0.00 0.70
Minimum of Months 0.129671E+09 0.00 0.00 5007557.42 0.00 0.00 0.456195E+09 0.00 0.36
Maximum of Months 0.228659E+11 0.210280E+11 0.00 0.134980E+09 0.224215E+09 0.140247E+11 0.616638E+11 0.00 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.143455E+11 0.00 0.00 152109.07 0.00 0.174492E+11 0.362497E+09 0.00 0.45
February 0.151149E+11 0.00 0.00 1644582.96 0.00 0.148207E+11 0.136720E+10 0.00 0.45
March 0.277659E+11 0.00 0.00 14372104.63 0.00 0.438709E+10 0.104826E+11 0.00 0.57
April 0.224414E+11 11502833.28 0.00 35168332.89 0.00 0.102208E+10 0.203920E+11 0.00 0.83
May 0.131792E+11 0.286583E+09 0.00 62452894.16 0.00 0.00 0.306183E+11 0.00 1.22
June 0.172946E+10 0.864290E+10 0.00 40461185.17 90286967.49 0.00 0.979858E+10 0.00 1.07
July 0.108561E+09 0.173729E+11 0.00 5312621.61 0.127621E+09 0.00 0.355505E+09 0.00 0.62
August 0.101973E+10 0.133415E+11 0.00 42376720.10 0.127425E+09 0.00 0.484614E+10 0.00 1.07
September 0.770817E+10 0.464911E+10 0.00 47057076.04 55718047.67 0.00 0.138463E+11 0.00 0.99
October 0.177154E+11 0.802344E+09 0.00 36587900.37 0.00 7567963.80 0.179408E+11 0.00 0.93
November 0.262458E+11 0.00 0.00 3937183.01 0.00 0.598951E+10 0.359879E+10 0.00 0.53
December 0.211340E+11 0.00 0.00 116191.98 0.00 0.132522E+11 0.315118E+09 0.00 0.44
                   
Annual Sum or Average 0.168508E+12 0.451068E+11 0.00 0.289639E+09 0.401052E+09 0.569284E+11 0.113924E+12 0.00 0.77
Minimum of Months 0.108561E+09 0.00 0.00 116191.98 0.00 0.00 0.315118E+09 0.00 0.44
Maximum of Months 0.277659E+11 0.173729E+11 0.00 62452894.16 0.127621E+09 0.174492E+11 0.306183E+11 0.00 1.22



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.368314E+09 0.00 0.00 0.00 0.00 0.251905E+10 0.00 0.00 0.32
February 0.379347E+09 0.00 0.00 0.00 0.00 0.234758E+10 0.00 0.00 0.32
March 0.188627E+10 0.00 0.00 0.00 0.00 0.179002E+10 0.00 0.00 0.36
April 0.233121E+10 63959.81 0.00 1106645.35 0.00 0.629852E+09 0.623213E+09 0.00 0.44
May 0.190535E+10 24310380.02 0.00 3953329.85 0.00 32861423.37 0.201398E+10 0.00 0.71
June 0.254935E+09 0.811233E+09 0.00 3936002.88 12279479.95 0.00 0.976158E+09 0.00 0.69
July 17694705.23 0.181484E+10 0.00 543982.54 22001385.53 0.00 49779173.81 0.00 0.42
August 0.148076E+09 0.119388E+10 0.00 3608870.47 18806025.27 0.00 0.482964E+09 0.00 0.66
September 0.975349E+09 0.429073E+09 0.00 2686288.58 18116427.45 0.00 0.955941E+09 0.00 0.59
October 0.212766E+10 34357768.28 0.00 1192126.12 399735.90 0.218092E+09 0.540683E+09 0.00 0.49
November 0.170503E+10 0.00 0.00 0.00 0.00 0.152346E+10 0.00 0.00 0.35
December 0.283968E+09 0.00 0.00 0.00 0.00 0.264231E+10 0.00 0.00 0.31
                   
Annual Sum or Average 0.123832E+11 0.430775E+10 0.00 17027245.80 71603054.09 0.117032E+11 0.564272E+10 0.00 0.47
Minimum of Months 17694705.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.233121E+10 0.181484E+10 0.00 3953329.85 22001385.53 0.264231E+10 0.201398E+10 0.00 0.71



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.539463E+09 0.00 0.00 0.00 0.00 0.195423E+10 0.00 0.00 0.42
February 0.699195E+09 0.00 0.00 0.00 0.00 0.162055E+10 0.00 0.00 0.42
March 0.198263E+10 0.00 0.00 257583.14 0.00 0.103611E+10 0.317959E+09 0.00 0.50
April 0.166716E+10 69665.57 0.00 2641590.23 0.00 0.478489E+09 0.162218E+10 0.00 0.74
May 0.146557E+10 23391754.73 0.00 6736334.30 0.00 19569220.17 0.296105E+10 0.00 1.21
June 0.147551E+09 0.656241E+09 0.00 4573540.39 22264917.47 0.00 0.124476E+10 0.00 1.03
July 14680534.53 0.153242E+10 0.00 723193.78 20109697.12 0.00 68369855.31 0.00 0.60
August 98096348.88 0.111571E+10 0.00 4560112.59 16655383.64 0.00 0.674015E+09 0.00 1.07
September 0.683616E+09 0.364857E+09 0.00 4487785.65 28159986.92 0.00 0.143353E+10 0.00 0.94
October 0.149303E+10 33652413.12 0.00 2636416.56 64631.88 0.105875E+09 0.127942E+10 0.00 0.80
November 0.183839E+10 0.00 0.00 33536.75 0.00 0.997010E+09 70468445.68 0.00 0.49
December 0.790900E+09 0.00 0.00 0.00 0.00 0.178977E+10 0.00 0.00 0.42
                   
Annual Sum or Average 0.114203E+11 0.372634E+10 0.00 26650093.39 87254617.03 0.800160E+10 0.967175E+10 0.00 0.72
Minimum of Months 14680534.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.198263E+10 0.153242E+10 0.00 6736334.30 28159986.92 0.195423E+10 0.296105E+10 0.00 1.21



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.987160E+09 0.00 0.00 1006066.52 0.00 0.167482E+10 0.665871E+09 0.00 0.35
February 0.104519E+10 0.00 0.00 1542723.13 0.00 0.126098E+10 0.101680E+10 0.00 0.37
March 0.180295E+10 0.00 0.00 3938828.83 0.00 0.960408E+09 0.298897E+10 0.00 0.54
April 0.181356E+10 179818.59 0.00 4849529.83 0.00 0.555404E+09 0.304855E+10 0.00 0.71
May 0.186788E+10 31143432.63 0.00 6951267.86 0.00 34671613.19 0.334236E+10 0.00 0.94
June 0.307191E+09 0.911558E+09 0.00 4642782.87 16486812.06 0.00 0.115635E+10 0.00 0.80
July 15994634.13 0.206808E+10 0.00 997646.12 26562423.20 0.00 59293751.96 0.00 0.49
August 0.138822E+09 0.163525E+10 0.00 6523622.75 20149274.82 0.00 0.757274E+09 0.00 0.98
September 0.699250E+09 0.653987E+09 0.00 11776129.43 13902039.44 0.00 0.299596E+10 0.00 1.11
October 0.102050E+10 0.107937E+09 0.00 11471181.05 0.00 87301309.75 0.539462E+10 0.00 1.16
November 0.171031E+10 0.00 0.00 2921965.22 0.00 0.815912E+09 0.211406E+10 0.00 0.52
December 0.120250E+10 0.00 0.00 1156979.09 0.00 0.148086E+10 0.743318E+09 0.00 0.35
                   
Annual Sum or Average 0.126113E+11 0.540813E+10 0.00 57778722.70 77100549.53 0.687036E+10 0.242834E+11 0.00 0.70
Minimum of Months 15994634.13 0.00 0.00 997646.12 0.00 0.00 59293751.96 0.00 0.35
Maximum of Months 0.186788E+10 0.206808E+10 0.00 11776129.43 26562423.20 0.167482E+10 0.539462E+10 0.00 1.16



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.893477E+09 0.00 0.00 0.00 0.00 0.181275E+10 0.00 0.00 0.46
February 0.909593E+09 0.00 0.00 76936.37 0.00 0.151446E+10 95774529.34 0.00 0.46
March 0.214973E+10 0.00 0.00 1083172.48 0.00 0.827312E+09 0.908309E+09 0.00 0.58
April 0.203719E+10 65086.59 0.00 3190715.02 0.00 0.350767E+09 0.192455E+10 0.00 0.84
May 0.166690E+10 27616957.70 0.00 5964595.20 0.00 14497437.90 0.288822E+10 0.00 1.25
June 0.223725E+09 0.805620E+09 0.00 4535011.56 9980053.10 0.00 0.104166E+10 0.00 1.09
July 12684342.94 0.169623E+10 0.00 1295023.74 15405086.75 0.00 49973185.52 0.00 0.62
August 0.116456E+09 0.127918E+10 0.00 4309537.76 13882226.99 0.00 0.509148E+09 0.00 1.11
September 0.843566E+09 0.448792E+09 0.00 4717514.49 14838234.25 0.00 0.132777E+10 0.00 1.01
October 0.173708E+10 53357363.22 0.00 2989867.98 0.00 0.102641E+09 0.151039E+10 0.00 0.91
November 0.204292E+10 0.00 0.00 205279.23 0.00 0.964218E+09 0.196076E+09 0.00 0.54
December 0.104087E+10 0.00 0.00 0.00 0.00 0.176408E+10 0.00 0.00 0.46
                   
Annual Sum or Average 0.136742E+11 0.431087E+10 0.00 28367653.83 54105601.08 0.735072E+10 0.104519E+11 0.00 0.78
Minimum of Months 12684342.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.46
Maximum of Months 0.214973E+10 0.169623E+10 0.00 5964595.20 15405086.75 0.181275E+10 0.288822E+10 0.00 1.25



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 928767.74 0.00 0.00 2548389.29 0.00 0.00 0.697246E+09 0.00 0.28
February 0.00 0.00 0.00 6765420.85 0.00 0.00 0.660260E+09 0.00 0.29
March 0.00 0.00 0.00 13907060.00 0.00 0.00 0.624831E+09 0.00 0.30
April 0.00 0.00 0.00 16413998.41 0.00 0.00 0.424898E+09 0.00 0.29
May 0.00 4443004.17 0.00 3689020.81 0.00 0.00 0.257041E+09 0.00 0.29
June 0.00 0.147525E+09 0.00 2580700.21 0.00 0.00 44292751.82 0.00 0.31
July 0.00 0.359779E+09 0.00 331570.78 0.00 0.00 958267.14 0.00 0.28
August 0.00 0.282954E+09 0.00 4310272.59 0.00 0.00 21205370.26 0.00 0.31
September 0.00 75536524.52 0.00 2252683.69 0.00 0.00 0.116260E+09 0.00 0.29
October 0.00 11913462.35 0.00 6629981.76 0.00 0.00 0.239041E+09 0.00 0.28
November 0.00 0.00 0.00 11975914.29 0.00 0.00 0.512738E+09 0.00 0.28
December 0.00 0.00 0.00 16661145.05 0.00 0.00 0.639744E+09 0.00 0.28
                   
Annual Sum or Average 928767.74 0.882151E+09 0.00 88066157.74 0.00 0.00 0.423852E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 331570.78 0.00 0.00 958267.14 0.00 0.28
Maximum of Months 928767.74 0.359779E+09 0.00 16661145.05 0.00 0.00 0.697246E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.197226E+10 0.00 0.00 7818002.69 0.00 0.00 0.496743E+10 0.00 0.28
February 0.00 0.00 0.00 49080490.09 0.00 0.00 0.662234E+10 0.00 0.29
March 0.00 0.00 0.00 0.119306E+09 0.00 0.00 0.626681E+10 0.00 0.30
April 0.00 0.00 0.00 0.149805E+09 0.00 0.00 0.425915E+10 0.00 0.29
May 0.00 43058339.57 0.00 31921218.59 0.00 0.00 0.259013E+10 0.00 0.29
June 0.00 0.146576E+10 0.00 24386674.46 0.00 0.00 0.443876E+09 0.00 0.31
July 0.00 0.359146E+10 0.00 3176855.36 0.00 0.00 9649135.25 0.00 0.28
August 0.00 0.283111E+10 0.00 41127527.53 0.00 0.00 0.212641E+09 0.00 0.31
September 0.00 0.740382E+09 0.00 19682708.70 0.00 0.00 0.117228E+10 0.00 0.29
October 0.00 0.115847E+09 0.00 59280850.24 0.00 0.00 0.239947E+10 0.00 0.28
November 0.00 0.00 0.00 0.101386E+09 0.00 0.00 0.514453E+10 0.00 0.28
December 0.00 0.00 0.00 0.141788E+09 0.00 0.00 0.642181E+10 0.00 0.28
                   
Annual Sum or Average 0.197226E+10 0.878762E+10 0.00 0.748760E+09 0.00 0.00 0.405101E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 3176855.36 0.00 0.00 9649135.25 0.00 0.28
Maximum of Months 0.197226E+10 0.359146E+10 0.00 0.149805E+09 0.00 0.00 0.662234E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.410085E+09 0.00 0.00 363919.27 0.00 0.00 0.273845E+09 0.00 0.28
February 279064.10 0.00 0.00 4077054.60 0.00 0.00 0.662689E+09 0.00 0.29
March 0.00 0.00 0.00 10981158.33 0.00 0.00 0.627833E+09 0.00 0.30
April 0.00 0.00 0.00 14425740.99 0.00 0.00 0.426687E+09 0.00 0.29
May 1738873.44 4347020.22 0.00 2972764.01 0.00 0.00 0.258804E+09 0.00 0.29
June 0.00 0.146582E+09 0.00 2449750.39 0.00 0.00 44432597.84 0.00 0.31
July 0.00 0.359076E+09 0.00 319384.13 0.00 0.00 966851.06 0.00 0.28
August 0.00 0.283993E+09 0.00 4127838.46 0.00 0.00 21300581.97 0.00 0.31
September 0.00 74094298.53 0.00 1854532.29 0.00 0.00 0.117803E+09 0.00 0.29
October 0.00 11478911.16 0.00 5482554.00 0.00 0.00 0.240929E+09 0.00 0.28
November 0.00 0.00 0.00 9176464.23 0.00 0.00 0.515693E+09 0.00 0.28
December 0.00 0.00 0.00 13087659.81 0.00 0.00 0.643291E+09 0.00 0.28
                   
Annual Sum or Average 0.412103E+09 0.879571E+09 0.00 69318820.51 0.00 0.00 0.383427E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 319384.13 0.00 0.00 966851.06 0.00 0.28
Maximum of Months 0.410085E+09 0.359076E+09 0.00 14425740.99 0.00 0.00 0.662689E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.211049E+09 0.00 0.00 0.177198E+11 0.00 0.32
February 0.00 0.00 0.00 0.390352E+09 0.00 0.00 0.174080E+11 0.00 0.32
March 0.00 0.00 0.00 0.713227E+09 0.00 0.00 0.150425E+11 0.00 0.34
April 0.00 0.00 0.00 0.822981E+09 0.00 0.00 0.960518E+10 0.00 0.32
May 0.00 0.136557E+09 0.00 0.192800E+09 0.00 0.00 0.552586E+10 0.00 0.33
June 0.00 0.340254E+10 0.00 0.124444E+09 0.00 0.00 0.917716E+09 0.00 0.34
July 0.00 0.796100E+10 0.00 14179609.08 0.00 0.00 15855041.49 0.00 0.31
August 0.00 0.507180E+10 0.00 0.236593E+09 0.00 0.00 0.504309E+09 0.00 0.35
September 0.00 0.188931E+10 0.00 0.119408E+09 0.00 0.00 0.245092E+10 0.00 0.32
October 0.00 0.303644E+09 0.00 0.330732E+09 0.00 0.00 0.563743E+10 0.00 0.32
November 0.00 0.00 0.00 0.620083E+09 0.00 0.00 0.119145E+11 0.00 0.32
December 0.00 0.00 0.00 0.855994E+09 0.00 0.00 0.161238E+11 0.00 0.32
                   
Annual Sum or Average 0.00 0.187648E+11 0.00 0.463184E+10 0.00 0.00 0.102866E+12 0.00 0.33
Minimum of Months 0.00 0.00 0.00 14179609.08 0.00 0.00 15855041.49 0.00 0.31
Maximum of Months 0.00 0.796100E+10 0.00 0.855994E+09 0.00 0.00 0.177198E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:04:39

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.252855E+12 0.441479E+11 0.00 0.145282E+13 0.544519E+12
February 0.399891E+12 0.398302E+11 0.00 0.148917E+13 0.824512E+12
March 0.661306E+12 0.324567E+11 0.00 0.183654E+13 0.129742E+13
April 0.703586E+12 0.213707E+11 0.00 0.183283E+13 0.179287E+13
May 0.890318E+12 0.123025E+11 0.00 0.176715E+13 0.107780E+13
June 0.868351E+12 0.223477E+09 0.00 0.398317E+12 0.255325E+13
July 0.847990E+12 -0.111996E+11 0.00 -0.399890E+12 0.358993E+13
August 0.813583E+12 -0.557004E+10 0.00 -0.383380E+11 0.390681E+13
September 0.577559E+12 0.468213E+10 0.00 0.971992E+12 0.170834E+13
October 0.552731E+12 0.167491E+11 0.00 0.187651E+13 0.144890E+13
November 0.280212E+12 0.314101E+11 0.00 0.182057E+13 0.127523E+13
December 0.209156E+12 0.378559E+11 0.00 0.166544E+13 0.168483E+13
           
Annual Sum or Average 0.705754E+13 0.224259E+12 0.00 0.146731E+14 0.217044E+14
Minimum of Months 0.209156E+12 -0.111996E+11 0.00 -0.399890E+12 0.544519E+12
Maximum of Months 0.890318E+12 0.441479E+11 0.00 0.187651E+13 0.390681E+13