Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 09:04:36
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 27864.27 | 601.56 | 601.56 |
Net Site Energy | 27864.27 | 601.56 | 601.56 |
Total Source Energy | 84228.04 | 1818.38 | 1818.38 |
Net Source Energy | 84228.04 | 1818.38 | 1818.38 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2435.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2752.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 449.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2190.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 248.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 726.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.79 |
Humidification | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 745.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 25935.27 | 1929.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3095.85 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 2435.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2752.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 449.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2190.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 248.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 726.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.79 |
Humidification | General | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 745.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1183.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 2435.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2752.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 449.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2190.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 248.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 726.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.79 |
Humidification | Unassigned | 5.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.90 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 745.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 69.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 121.03 | 41.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 559.91 | 41.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 69.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 121.03 | 41.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 559.91 | 41.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.07 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 25935.268 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 25935.268 | 100.00 |
Total On-Site and Utility Electric Sources | 25935.268 | 100.00 |
Total Electricity End Uses | 25935.268 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 3095.85 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 3095.85 | 100.00 |
Total Water End Uses | 3095.85 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 23.17 |
Time Setpoint Not Met During Occupied Cooling | 89.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5942.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 14-AUG-15:09 | 10-JAN-07:00 | - | - | - | - | - | - | - | - | - | - | 21-JUL-16:00 |
Heating | 0.00 | 725897.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 314554.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 83146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 207117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 44964.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 54595.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 29801.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1732817.37 | 755699.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 725897.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 314554.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 207117.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 44964.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 54595.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 29801.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1282.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 7714.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8716.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1422.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 6936.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 787.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2300.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 16.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 808.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 82136.99 | 2091.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 166.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 188.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 49.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1773.24 | 45.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 27.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 166.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 188.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 149.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 17.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 49.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1773.24 | 45.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 5.28 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.497046 |
DATACENTER_MID_ZN_6 DIRECT AIR | 4.75 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.481993 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 21.51 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 5.57 | 0.341493 | 0.338000 | 1.88 | 0.910648 | 0.500000 | 0.001116 | 0.000164 | 1.88 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 52.05 | 0.365394 | 0.352000 | 18.32 | 0.974384 | 0.500000 | 0.001043 | 0.003295 | 18.32 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 4.94 | 0.385084 | 0.380000 | 1.88 | 1.00 | 0.500000 | 0.000989 | 0.000632 | 2.17 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 0.765437 | 0.312006 | 0.309000 | 0.236520 | 0.832015 | 0.500000 | 0.001221 | 0.000065 | 0.236520 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.07 | 0.144424 | 0.200000 | 0.213129 | 0.385132 | 0.500000 | 0.002638 | 0.000051 | 0.213129 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.52 | 0.156948 | 0.200000 | 0.304337 | 0.418529 | 0.500000 | 0.002428 | 0.000087 | 0.304337 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.32 | 0.116228 | 0.200000 | 0.264833 | 0.309941 | 0.500000 | 0.003278 | 0.000041 | 0.264833 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 6.80 | 0.351395 | 0.338000 | 2.30 | 0.937053 | 0.500000 | 0.001084 | 0.001442 | 4.97 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 10.96 | 0.140400 | 0.200000 | 2.19 | 0.374399 | 0.500000 | 0.002714 | 0.000965 | 3.32 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 15.41 | 0.154979 | 0.200000 | 3.08 | 0.413278 | 0.500000 | 0.002458 | 0.001451 | 5.00 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 11.64 | 0.132174 | 0.200000 | 2.33 | 0.352464 | 0.500000 | 0.002883 | 0.000877 | 3.02 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 0.757839 | 0.315134 | 0.311000 | 0.235688 | 0.840356 | 0.500000 | 0.001209 | 0.000196 | 0.676153 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.08 | 0.142942 | 0.200000 | 0.215339 | 0.381178 | 0.500000 | 0.002665 | 0.000130 | 0.448586 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.62 | 0.147069 | 0.200000 | 0.324781 | 0.392183 | 0.500000 | 0.002591 | 0.000197 | 0.679907 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.22 | 0.125738 | 0.200000 | 0.244803 | 0.335301 | 0.500000 | 0.003030 | 0.000124 | 0.425945 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 18754.01 | 0.000164 | 378.07 |
CORE_MID VAV BOX REHEAT COIL | 376656.85 | 0.003295 | 8490.06 |
CORE_TOP VAV BOX REHEAT COIL | 72211.89 | 0.000632 | 1907.33 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 7388.81 | 0.000065 | 189.85 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5878.28 | 0.000051 | 144.05 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9915.55 | 0.000087 | 259.40 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4700.03 | 0.000041 | 102.69 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 164834.14 | 0.001442 | 4348.69 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 110336.54 | 0.000965 | 2910.79 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 165847.67 | 0.001451 | 4375.40 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 100274.83 | 0.000877 | 2645.64 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 22430.03 | 0.000196 | 591.57 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14880.05 | 0.000130 | 392.43 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 22554.31 | 0.000197 | 594.84 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 14130.37 | 0.000124 | 372.68 |
VAV_BOT WITH REHEAT HEATING COIL | 52484.46 | 0.000459 | 861.44 |
VAV_MID WITH REHEAT HEATING COIL | 496240.58 | 0.004341 | 8121.44 |
VAV_TOP WITH REHEAT HEATING COIL | 51126.33 | 0.000447 | 840.58 |
CAV_BAS HEATING COIL | 259156.75 | 0.002267 | 5768.65 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 5.12 | 2.90 | 10.25 | 2.90 | 8.81 | 8.81 | 0.300000 | 0.329277 | 8.81 |
VAV_MID WITH REHEAT | 48.43 | 28.22 | 96.87 | 28.22 | 80.80 | 80.80 | 0.300000 | 0.349293 | 80.80 |
VAV_TOP WITH REHEAT | 4.81 | 2.90 | 9.62 | 4.40 | 8.74 | 8.74 | 0.300000 | 0.503252 | 8.74 |
CAV_BAS | 5.28 | 5.28 | 5.28 | 5.28 | 5.28 | 5.28 | 1.00 | 1.00 | 5.28 |
AIRLOOP DATACENTER BASEMENT | 21.51 | 21.51 | 21.51 | 21.51 | 21.51 | 21.51 | 1.00 | 0.999993 | 21.51 |
AIRLOOP DATACENTER BOT | 0.497046 | 0.497046 | 0.497046 | 0.497046 | 0.497046 | 0.497046 | 1.00 | 1.00 | 0.497046 |
AIRLOOP DATACENTER MID | 4.75 | 4.75 | 4.75 | 4.75 | 4.75 | 4.75 | 1.00 | 1.00 | 4.75 |
AIRLOOP DATACENTER TOP | 0.481993 | 0.481993 | 0.481993 | 0.481993 | 0.481993 | 0.481993 | 1.00 | 1.00 | 0.481993 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 8.81 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 80.80 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 8.74 | |
CAV_BAS_OA_CONTROLLER | 5.28 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 21.51 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.497046 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 4.75 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.481993 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 24.70 | 6.67 | 10.92 | 0.008729 | 0.008500 | 153777.80 | 0.006542 | 8.81 |
VAV_MID WITH REHEAT COOLING COIL | 24.78 | 6.67 | 10.92 | 0.008740 | 0.008500 | 1420511.66 | 0.060432 | 80.80 |
VAV_TOP WITH REHEAT COOLING COIL | 24.70 | 6.67 | 10.92 | 0.008726 | 0.008500 | 152441.52 | 0.006485 | 8.74 |
CAV_BAS COOLING COIL | 24.31 | 6.67 | 11.41 | 0.008866 | 0.008500 | 88716.90 | 0.003774 | 5.28 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 8.81 |
VAV_MID WITH REHEAT FAN | 80.80 |
VAV_TOP WITH REHEAT FAN | 8.74 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.006542 | 0.000073 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000459 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.060432 | 0.000008 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.004341 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.006485 | 0.000073 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000447 | |
CAV_BAS_COOLC_CONTROLLER | 0.003774 | 0.000126 |
CAV_BAS_HEATC_CONTROLLER | 0.002267 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 5.28 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 21.51 | 425158.45 | 306270.10 | 0.010412 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.497046 | 9575.81 | 6988.26 | 0.000235 |
AIRLOOP DATACENTER MID COOLING COIL | 4.75 | 91556.18 | 66808.19 | 0.002242 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.481993 | 9287.16 | 6777.02 | 0.000227 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 21.51 | 21.51 | 21.51 | 21.51 | 425158.45 | 425158.45 | 17946.39 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.497046 | 0.497046 | 0.497046 | 0.497046 | 9575.81 | 9575.81 | 829.05 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 4.75 | 4.75 | 4.75 | 4.75 | 91556.18 | 91556.18 | 8290.49 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.481993 | 0.481993 | 0.481993 | 0.481993 | 9287.16 | 9287.16 | 829.05 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 21.51 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.497046 |
AIRLOOP DATACENTER MID SUPPLY FAN | 4.75 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.481993 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 21.51 | 425158.45 | 0.010412 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.497046 | 9575.81 | 0.000235 |
AIRLOOP DATACENTER MID HEATING COIL | 4.75 | 91556.18 | 0.002242 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.481993 | 9287.16 | 0.000227 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 17946.39 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 829.05 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8290.49 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 829.05 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000144 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.077233 | 15914.93 | |
HEATSYS1 PUMP | 0.017233 | 5189.73 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.077233 | 9.27 |
HEATSYS1 | 0.017233 | 2.07 |
COOLSYS1_SUPPLY | 0.077233 | 9.27 |
SINGLE WATER PLANT LOOP | 0.013116 | 1.57 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.077233 | 0.077233 | 324187.12 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 1969801.48 | 1969801.48 | 0.017233 |
CENTRAL BOILER | 540277.50 | 529493.12 | 0.013116 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.077233 | 11018.44 |
PLANT CIRC PUMP | 0.013116 | 3345.30 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.077233 | 0.038873 | 914782.62 | 920350.55 | 0.046660 |
COOLSYS1 CHILLER2 | 0.077233 | 0.038873 | 914782.62 | 920350.55 | 0.046660 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.013116 | 139666.47 | 60010.01 | 69833.23 | 7879.72 | 21486.44 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.093320 | 11.20 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.093320 | 28105.84 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 35.81 | 1093360.89 | 7.16 | 136670.11 |
TOWERWATERSYS COOLTOWER 2 | 35.81 | 1093360.89 | 7.16 | 136670.11 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.047308 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.149 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.571 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6483 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7026 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4692 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.15847945E-14 | 0.40415870E-16 | -0.13570955E-09 | -0.55776231E-17 |
51 | 8 | 0.19900788E-07 | 0.16227319E-12 | 0.35673126E-03 | -0.22627880E-09 |
52 | 7 | -0.11611995E-01 | 0.86155623E-08 | -0.22179000E-01 | 0.13203260E-03 |
53 | 6 | 0.38824249 | 0.30290701E-05 | 0.45749374 | -0.45461023E-02 |
54 | 5 | -5.0235921 | 0.11413317E-03 | -4.3290265 | 0.61113495E-01 |
55 | 4 | 32.264180 | 0.94131685E-03 | 21.001374 | -0.41231550 |
56 | 3 | -109.65428 | 0.20665218E-02 | -54.756066 | 1.4924847 |
57 | 2 | 195.57288 | 0.11699747E-02 | 77.079281 | -2.8759721 |
58 | 1 | -170.58880 | 0.12564906E-03 | -55.024271 | 2.7354972 |
59 | 0 | 57.057407 | 0.71994484E-06 | 15.597457 | |
60 | 9 | 0.92194319E-15 | 0.45185080E-16 | -0.13934922E-09 | -0.37336789E-17 |
61 | 8 | 0.20414049E-07 | 0.15291409E-12 | 0.36227410E-03 | -0.23211478E-09 |
62 | 7 | -0.11777906E-01 | 0.80689916E-08 | -0.22418053E-01 | 0.13391908E-03 |
63 | 6 | 0.39275134 | 0.28300412E-05 | 0.46134659 | -0.45992504E-02 |
64 | 5 | -5.0676021 | 0.10641223E-03 | -4.3586752 | 0.61659190E-01 |
65 | 4 | 32.458904 | 0.87600040E-03 | 21.117392 | -0.41490080 |
66 | 3 | -110.06874 | 0.19199492E-02 | -54.985491 | 1.4984722 |
67 | 2 | 195.98384 | 0.10853975E-02 | 77.289466 | -2.8824978 |
68 | 1 | -170.74067 | 0.11640795E-03 | -55.084954 | 2.7381589 |
69 | 0 | 57.057407 | 0.66605595E-06 | 15.587079 | |
70 | 9 | 0.99499981E-15 | 0.49201796E-16 | -0.11918706E-09 | -0.33210447E-17 |
71 | 8 | 0.17565796E-07 | 0.20231051E-12 | 0.33086922E-03 | -0.19972915E-09 |
72 | 7 | -0.10835659E-01 | 0.11065463E-07 | -0.21059630E-01 | 0.12320537E-03 |
73 | 6 | 0.36714142 | 0.39371282E-05 | 0.43940598 | -0.42973741E-02 |
74 | 5 | -4.8175888 | 0.14987275E-03 | -4.1895891 | 0.58559222E-01 |
75 | 4 | 31.352470 | 0.12474171E-02 | 20.455190 | -0.40021127 |
76 | 3 | -107.71307 | 0.27606440E-02 | -53.675749 | 1.4644420 |
77 | 2 | 193.64724 | 0.15741070E-02 | 76.090603 | -2.8453956 |
78 | 1 | -169.87685 | 0.17016149E-03 | -54.740743 | 2.7230195 |
79 | 0 | 57.057407 | 0.98204117E-06 | 15.647518 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2517E-003 |
2 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2536E-003 |
3 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8877E-003 |
4 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8893E-003 |
5 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3590E-003 |
6 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3602E-003 |
7 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8674E-003 |
8 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8681E-003 |
9 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2956E-003 |
10 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4246E-003 |
11 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9250E-003 |
12 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0384E-003 |
13 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3905E-003 |
14 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4834E-003 |
15 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8859E-003 |
16 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9330E-003 |
17 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1269 |
18 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.8163E-002 |
19 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1457 |
20 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 9.1183E-002 |
21 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.0698E-002 |
22 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9296E-002 |
23 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9234E-002 |
24 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3771E-002 |
25 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.3026E-003 |
26 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4618E-003 |
27 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.9327E-003 |
28 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 6.0796E-003 |
29 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3963E-003 |
30 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5057E-003 |
31 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8864E-003 |
32 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9344E-003 |
33 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.2515E-003 |
34 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.2537E-003 |
35 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.8875E-003 |
36 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.8894E-003 |
37 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.3589E-003 |
38 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.3604E-003 |
39 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8673E-003 |
40 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8680E-003 |
41 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5487E-003 |
42 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.9272E-003 |
43 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4364E-003 |
44 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.8785E-003 |
45 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9426E-003 |
46 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0665E-003 |
47 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1954E-003 |
48 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2279E-003 |
49 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3367E-002 |
50 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.7463E-002 |
51 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.1821E-002 |
52 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.5841E-002 |
53 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 5.3505E-002 |
54 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.2835E-002 |
55 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0350E-002 |
56 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5085E-002 |
57 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.4198E-003 |
58 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.5161E-003 |
59 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2657E-003 |
60 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3364E-003 |
61 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9037E-003 |
62 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.9318E-003 |
63 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1955E-003 |
64 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2284E-003 |
65 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0588E-003 |
66 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0607E-003 |
67 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7420E-003 |
68 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7436E-003 |
69 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5200E-003 |
70 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5212E-003 |
71 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
72 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8681E-003 |
73 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1020E-003 |
74 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2131E-003 |
75 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7781E-003 |
76 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8680E-003 |
77 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5499E-003 |
78 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6167E-003 |
79 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8864E-003 |
80 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9344E-003 |
81 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.4249E-002 |
82 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9952E-002 |
83 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6534E-002 |
84 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5175E-002 |
85 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.6448E-002 |
86 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.0462E-002 |
87 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9234E-002 |
88 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3767E-002 |
89 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.1002E-003 |
90 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.2127E-003 |
91 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7755E-003 |
92 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8638E-003 |
93 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5453E-003 |
94 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6024E-003 |
95 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8860E-003 |
96 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9331E-003 |
97 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0586E-003 |
98 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.0605E-003 |
99 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7419E-003 |
100 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7434E-003 |
101 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5199E-003 |
102 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5209E-003 |
103 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
104 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8680E-003 |
105 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9448E-003 |
106 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0451E-003 |
107 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6537E-003 |
108 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7266E-003 |
109 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.5733E-003 |
110 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.5991E-003 |
111 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1956E-003 |
112 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2284E-003 |
113 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.4364E-002 |
114 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.3600E-002 |
115 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0317E-002 |
116 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0890E-002 |
117 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6726E-002 |
118 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.9969E-002 |
119 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0350E-002 |
120 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5085E-002 |
121 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0399E-003 |
122 | Clear Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.3031E-003 |
123 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7804E-003 |
124 | Clear Turbid Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.0716E-003 |
125 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6092E-003 |
126 | Intermediate Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7193E-003 |
127 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1954E-003 |
128 | Overcast Sky | 01/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2278E-003 |
129 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1215 |
130 | Clear Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.7371E-002 |
131 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1356 |
132 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 0.1122 |
133 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.6215E-002 |
134 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3399E-002 |
135 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5331E-002 |
136 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.1963E-002 |
137 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.1062E-002 |
138 | Clear Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.7633E-002 |
139 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.9392E-002 |
140 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.5851E-002 |
141 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 6.0434E-002 |
142 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.1534E-002 |
143 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6386E-002 |
144 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2195E-002 |
145 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.0472E-002 |
146 | Clear Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.8623E-002 |
147 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.2103E-002 |
148 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.2583E-002 |
149 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.1978E-002 |
150 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.7203E-002 |
151 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5332E-002 |
152 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1959E-002 |
153 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.1288E-002 |
154 | Clear Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.2544E-002 |
155 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6890E-002 |
156 | Clear Turbid Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9312E-002 |
157 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.3163E-002 |
158 | Intermediate Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.7940E-002 |
159 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6386E-002 |
160 | Overcast Sky | 01/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2195E-002 |
161 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1213 |
162 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.7457E-002 |
163 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1353 |
164 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 0.1123 |
165 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.6210E-002 |
166 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3499E-002 |
167 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5383E-002 |
168 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2005E-002 |
169 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.1018E-002 |
170 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.7666E-002 |
171 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.9357E-002 |
172 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.5885E-002 |
173 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 6.0446E-002 |
174 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.1587E-002 |
175 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6435E-002 |
176 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2237E-002 |
177 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.0416E-002 |
178 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.8634E-002 |
179 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.2064E-002 |
180 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2593E-002 |
181 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.1994E-002 |
182 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.7230E-002 |
183 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5383E-002 |
184 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2001E-002 |
185 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.1245E-002 |
186 | Clear Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.2569E-002 |
187 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6858E-002 |
188 | Clear Turbid Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9336E-002 |
189 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.3175E-002 |
190 | Intermediate Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.7987E-002 |
191 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6435E-002 |
192 | Overcast Sky | 01/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2237E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72612.37106 | 72612.37106 | 5.28289 | 5.28289 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | -4.30000 | 2.65759E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 76558.85939 | 76558.85939 | 5.56979 | 5.56979 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 0.00000 | 0.00000 | 0.00000 | 1.07782 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 715724.73271 | 715724.73271 | 52.05461 | 52.05461 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 194124.25142 | 194124.25142 | 8.22879 | 10.77825 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 67924.70510 | 67924.70510 | 4.93929 | 4.93929 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 19.66600 | 8.39663E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 50596.92094 | 50596.92094 | 2.16978 | 2.16978 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 10423.26778 | 10423.26778 | 0.76544 | 0.76544 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 5035.64904 | 5035.64904 | 0.21553 | 0.21553 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14511.44627 | 14511.44627 | 1.06564 | 1.06564 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 21.10683 | 8.39884E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 3757.45656 | 3757.45656 | 0.16100 | 0.16100 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 20721.55929 | 20721.55929 | 1.52168 | 1.52168 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 26.09667 | 8.40660E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 6886.33422 | 6886.33422 | 0.29550 | 0.29550 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 18031.94363 | 18031.94363 | 1.32417 | 1.32417 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 25.12600 | 8.40508E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 2067.55038 | 2067.55038 | 8.79662E-002 | 8.79662E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 92548.93650 | 92548.93650 | 6.79636 | 6.79636 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 115400.05071 | 115400.05071 | 4.96546 | 4.96546 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 149274.72788 | 149274.72788 | 10.96193 | 10.96193 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 77242.13655 | 77242.13655 | 3.32410 | 3.32410 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 209848.86886 | 209848.86886 | 15.41019 | 15.41019 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 26.17250 | 8.40672E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 116108.42878 | 116108.42878 | 4.99607 | 4.99607 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 158564.62385 | 158564.62385 | 11.64412 | 11.64412 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 70209.32992 | 70209.32992 | 3.02027 | 3.02027 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 10319.84025 | 10319.84025 | 0.75784 | 0.75784 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 26.40000 | 8.40708E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 15697.32053 | 15697.32053 | 0.67615 | 0.67615 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 14661.99557 | 14661.99557 | 1.07670 | 1.07670 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 21.91067 | 8.40008E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 10413.31118 | 10413.31118 | 0.44859 | 0.44859 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 22113.64901 | 22113.64901 | 1.62391 | 1.62391 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 26.24833 | 8.40684E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 15784.20195 | 15784.20195 | 0.67991 | 0.67991 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 16668.12069 | 16668.12069 | 1.22401 | 1.22401 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.97433 | 8.40484E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 9889.20202 | 9889.20202 | 0.42595 | 0.42595 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | -4.30000 | 2.65759E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8581.40701 | 8581.40701 | 0.49705 | 0.49705 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 82031.77996 | 82031.77996 | 4.75142 | 4.75142 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8321.49232 | 8321.49232 | 0.48199 | 0.48199 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 23.30600 | 8.40224E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | -4.30000 | 2.65759E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371336.03054 | 371336.03054 | 21.50797 | 21.50797 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 18.11900 | 8.39428E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | -4.30000 | 2.65759E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 123284.40 | 8.81145 | 8.81145 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 37623.00 | 1.83783 | 1.83783 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1115804.21 | 80.80209 | 80.80209 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 519567.82 | 27.08414 | 27.08414 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 124463.30 | 8.74387 | 8.74387 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 51952.67 | 4.40037 | 4.40037 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 |
7 | CAV_BAS | Cooling | Sensible | 65728.92 | 5.28289 | 5.28289 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 63649.34 | 1.20016 | 1.20016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 364959.54 | 21.50813 | 21.50813 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 17946.39 | 0.33839 | 0.33839 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8379.61 | 0.49705 | 0.49705 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 80072.29 | 4.75142 | 4.75142 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8290.49 | 0.15632 | 0.15632 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8123.71 | 0.48199 | 0.48199 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 829.05 | 1.56323E-002 | 1.56323E-002 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.28289 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 5.56979 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.34149 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33800 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.88259 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.91065 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.11569E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.64068E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.88259 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 18754.00606 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.64068E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 378.06604 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 52.05461 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.36539 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.35200 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 18.32322 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.97438 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.04271E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 3.29516E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 18.32322 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 376656.85343 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 3.29516E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 8490.05850 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 4.93929 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.38508 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.38000 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 1.87693 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 1.00000 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 9.89394E-004 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.31741E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.16978 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 72211.89064 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.31741E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 1907.33426 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.76544 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31201 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30900 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23652 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.83201 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.22113E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 6.46405E-005 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.23652 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 7388.80822 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.46405E-005 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 189.84517 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.06564 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14442 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21313 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38513 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.63806E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 5.14258E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.21313 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 5878.28459 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 5.14258E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 144.04655 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.52168 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15695 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30434 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41853 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.42755E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.67456E-005 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.30434 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 9915.55015 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.67456E-005 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 259.39550 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.32417 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11623 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26483 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30994 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.27805E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.11179E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.26483 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 4700.02891 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.11179E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 102.68868 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.79636 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.35139 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.33800 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.29717 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.93705 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.08425E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.44204E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.96546 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 164834.14436 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.44204E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4348.69043 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.96193 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14040 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.19239 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.37440 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.71368E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.65272E-004 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.32410 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 110336.53719 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.65272E-004 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2910.79087 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.41019 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15498 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.08204 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41328 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.45840E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.45091E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 4.99607 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 165847.66808 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.45091E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4375.39798 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 11.64412 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.13217 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.32882 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.35246 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.88256E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.77248E-004 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.02027 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 100274.82739 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.77248E-004 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2645.63525 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 0.75784 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.31513 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31100 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.23569 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.84036 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.20901E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.96228E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67615 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22430.02973 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.96228E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 591.56510 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.07670 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14294 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.21534 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38118 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.66542E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.30177E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.44859 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14880.04839 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.30177E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 392.43269 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.62391 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14707 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32478 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.39218 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.59063E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.97315E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.67991 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 22554.30835 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.97315E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 594.83982 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.22401 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.12574 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.24480 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.33530 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.03011E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.23619E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.42595 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 14130.36749 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.23619E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 372.67715 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.49705 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 4.75142 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.48199 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 21.50797 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.12336 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.90141 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 10.24672 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 2.90141 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.81145 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.81145 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.32928 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 48.43361 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 28.22364 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 96.86721 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 28.22364 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 80.80209 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 80.80209 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.34929 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.81088 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.89754 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 9.62175 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 4.40037 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 8.74387 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 8.74387 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.50325 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.28289 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.28289 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.28289 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 5.28289 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.28289 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 5.28289 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 21.50797 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 21.50797 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 21.50797 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 21.50797 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 21.50813 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 21.50813 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.49705 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.49705 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.49705 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.49705 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.49705 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.49705 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 4.75142 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 4.75142 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 4.75142 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 4.75142 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 4.75142 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 4.75142 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.48199 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.48199 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.48199 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.48199 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.48199 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.48199 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.81145 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 80.80209 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 8.74387 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 5.28289 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 21.50813 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.49705 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 4.75142 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.48199 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.81145 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.70327 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92266 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72916E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 153777.80116 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.54206E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.81145 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 52484.45820 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.59157E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 861.43995 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.81145 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.54206E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.27890E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.59157E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 80.80209 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.78234 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92270 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.73969E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1420511.66179 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.04318E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 80.80209 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 496240.58319 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.34133E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 8121.43670 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 80.80209 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.04318E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.87979E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.34133E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 8.74387 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.69619 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.92265 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.72608E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 152441.51906 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 6.48521E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 8.74387 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 51126.33495 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.47275E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 840.58200 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 8.74387 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.48521E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 7.34271E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.47275E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.28289 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 24.30507 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.40643 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.86559E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 8.50000E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 88716.89728 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 3.77422E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 5.28289 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 259156.75048 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.26722E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5768.64645 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 5.28289 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 3.77422E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.26169E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.26722E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 21.50813 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.50813 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 425158.45452 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 306270.09776 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04121E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 21.50813 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 21.50813 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 21.50813 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 21.50813 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 425158.45452 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 425158.45452 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 17946.39161 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 21.50813 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 21.50813 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 425158.45452 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.04121E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 17946.39161 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.44244E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.49705 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49705 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9575.80505 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6988.25859 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34511E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.49705 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.49705 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.49705 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.49705 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9575.80505 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9575.80505 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.49705 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.49705 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 9575.80505 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.34511E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 4.75142 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.75142 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 91556.18077 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 66808.19476 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24220E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 4.75142 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 4.75142 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 4.75142 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 4.75142 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 91556.18077 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 91556.18077 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8290.48945 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 4.75142 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 4.75142 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 91556.18077 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.24220E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8290.48945 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.48199 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48199 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 9287.15675 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 6777.01793 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27442E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.48199 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.48199 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.48199 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.48199 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 9287.15675 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 9287.15675 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 829.04894 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.48199 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.48199 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 9287.15675 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.27442E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 829.04894 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 7.72333E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 15914.93080 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 7.72333E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 9.26800 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 7.72333E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 7.72333E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 324187.12130 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 1.72327E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.06792 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 1.72327E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 5189.72724 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 1969801.47979 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 1969801.48000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 1.72327E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 7.72333E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 9.26800 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 7.72333E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 11018.44345 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.72333E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.88735E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 914782.62231 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 920350.55000 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.66598E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 7.72333E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 3.88735E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 914782.62231 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 920350.55000 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 4.66598E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.31163E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.57395 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.31163E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3345.30244 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.31163E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 60010.00528 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 21486.44249 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 540277.50199 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 529493.12000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.31163E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 9.33196E-002 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 11.19835 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 9.33196E-002 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 28105.83884 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 35.81117 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1093360.89446 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 7.16223 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 136670.11181 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 35.81117 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1093360.89446 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 7.16223 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 136670.11181 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.73075E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 4.73075E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 17782.58 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 356938.92 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 68436.43 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 6997.21 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 5567.86 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 9388.84 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 4454.60 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 156182.18 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 104544.21 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 157142.30 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 95012.60 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 21251.44 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 14098.10 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 21369.16 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 13387.92 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 40168.42 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 377534.13 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 39267.35 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 205344.60 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 200178.72 | 142875.02 | 57303.70 | 0.71 | 20995.34 | 212.95 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 1841757.07 | 1312951.53 | 528805.54 | 0.71 | 193004.94 | 1957.56 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 198546.03 | 141734.37 | 56811.66 | 0.71 | 20825.85 | 211.23 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 115868.40 | 83499.15 | 32369.25 | 0.72 | 11881.87 | 120.51 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 7.08 | 24.14 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 7.08 | 24.14 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.3235938612 | 0.2281284129 | Pass | Pass | 0.4632231724 | 0.3932947071 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 3.5916591599E-003 | 3.9745380245E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.0956901257E-003 | 3.6218832926E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 4.1640158462E-002 | 2.4993527357E-002 | Pass | Pass | 0.5396255501 | 0.5071598893 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 1.5366189884E-002 | 1.3265241532E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.3182742290E-002 | 6.5873026679E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 6.6323713207E-002 | 8.5327005674E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.3492943993E-002 | 4.3032051412E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 2.1301390119E-002 | 1.8984903610E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 4.7474558121E-002 | 6.2470587251E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 7.5304485562E-002 | 8.6497943778E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 3.9407863884E-002 | 4.3752417839E-002 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.2397737770 | 0.2204898112 | Pass | Pass | 19.2776007590 | 36.9145668420 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1613899818 | 0.1786457578 | Pass | Pass | 14.7691804602 | 31.2712852120 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.1269409354 | 0.1109579787 | Pass | Pass | 7.9302861114 | 21.5857932061 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.6465413270E-002 | 9.7326669914E-002 | Pass | Pass | 13.8792918458 | 30.0900486848 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 6.0553983488E-003 | 6.1196805971E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 8.3832806571E-003 | 8.9390651187E-003 | Pass | Pass | 0.0000000000 | 0.0000000000 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 9.7853604243E-002 | 6.3252112146E-002 | Pass | Pass | 0.5254286609 | 0.4698894955 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.4600674504E-006 | 4.3974767962E-006 | Pass | Pass | 3.5956238235E-003 | 4.3113466484E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 3.3973964451E-006 | 6.3905405611E-006 | Pass | Pass | 0.3892771428 | 3.7349771316 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 1.9672887474E-002 | 1.8870328263E-002 | Pass | Pass | 3.1106075904E-003 | 4.1211214273E-003 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7662118884E-006 | 5.6805004846E-006 | Pass | Pass | 4.6895748944E-005 | 1.0743150857E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 6105.67 | 132.31 | 0.00 | 23173.65 | 14690.60 | 44102.24 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.39 | 0.0000 | Y | 14.07 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.20 | 0.0000 | Y | 9.01 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.10 | 0.0000 | Y | 13.94 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.29 | 0.0000 | Y | 9.04 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.42 | 0.0000 | Y | 140.88 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.21 | 0.0000 | Y | 90.17 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.12 | 0.0000 | Y | 139.52 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.31 | 0.0000 | Y | 90.45 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.42 | 0.0000 | Y | 14.09 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.21 | 0.0000 | Y | 9.02 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.12 | 0.0000 | Y | 13.95 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 31.31 | 0.0000 | Y | 9.04 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 858.92 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.50 | 42.50 | 79.56 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.54 | 71.23 | 369.53 | |
Exterior Lighting Total | 37611.08 | 449.08 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 1811272.88 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 1969801.48 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 920350.55 | 5.33 | 909986.93 | 4.98 | 7.08 | 24.14 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 920350.55 | 5.33 | 909986.93 | 4.98 | 7.08 | 24.14 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 529493.12 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1093360.89 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1093360.89 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 153777.80 | 200178.72 | 142875.02 | 57303.70 | 0.71 | - | 20995.34 | 212.95 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1420511.66 | 1841757.07 | 1312951.53 | 528805.54 | 0.71 | - | 193004.94 | 1957.56 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 152441.52 | 198546.03 | 141734.37 | 56811.66 | 0.71 | - | 20825.85 | 211.23 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 88716.90 | 115868.40 | 83499.15 | 32369.25 | 0.72 | - | 11881.87 | 120.51 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 425158.45 | 306270.10 | 118888.36 | 0.72 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9575.81 | 6988.26 | 2587.55 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 91556.18 | 66808.19 | 24747.99 | 0.73 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 9287.16 | 6777.02 | 2510.14 | 0.73 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 18754.01 | 17782.58 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 376656.85 | 356938.92 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 72211.89 | 68436.43 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 7388.81 | 6997.21 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 5878.28 | 5567.86 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 9915.55 | 9388.84 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 4700.03 | 4454.60 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 164834.14 | 156182.18 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 110336.54 | 104544.21 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 165847.67 | 157142.30 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 100274.83 | 95012.60 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 22430.03 | 21251.44 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 14880.05 | 14098.10 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 22554.31 | 21369.16 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 14130.37 | 13387.92 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 52484.46 | 40168.42 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 496240.58 | 377534.13 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 51126.33 | 39267.35 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 259156.75 | 205344.60 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 425158.45 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9575.81 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 91556.18 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 9287.16 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 17946.39 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8290.49 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 829.05 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.81 | 20122.95 | 2283.73 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 80.80 | 184529.97 | 2283.73 | 1.00 | 1.07 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 8.74 | 19968.61 | 2283.73 | 1.00 | 1.12 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 5.28 | 8957.95 | 1695.65 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.61 | 1018.41 | 21.51 | 35659.90 | 1657.97 | 1.00 | 1.13 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.50 | 556.75 | 1120.11 | 1.00 | 1.61 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 4.75 | 5322.10 | 1120.11 | 1.00 | 1.16 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.48 | 539.88 | 1120.11 | 1.00 | 1.62 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.077233 | 15914.93 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.017233 | 5189.73 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.077233 | 11018.44 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.013116 | 3345.30 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.093320 | 28105.84 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72612.37 | 72612.37 | 26.12 | 5.283 | 5.283 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00898 | 19.67 | 0.00840 | 1.200 | 0.00 |
CORE_BOTTOM | 76558.86 | 76558.86 | 30.67 | 5.570 | 5.570 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00891 | 19.67 | 0.00840 | 1.078 | 0.00 |
CORE_MID | 715724.73 | 715724.73 | 286.73 | 52.055 | 52.055 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00894 | 19.67 | 0.00840 | 10.778 | 0.00 |
CORE_TOP | 67924.71 | 67924.71 | 27.21 | 4.939 | 4.939 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 24.00 | 24.00 | 0.00896 | 19.67 | 0.00840 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10423.27 | 10423.27 | 33.26 | 0.765 | 0.765 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:10:00 | 24.00 | 24.00 | 0.00886 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14511.45 | 14511.45 | 71.85 | 1.066 | 1.066 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:50:00 | 24.00 | 24.00 | 0.00867 | 21.11 | 0.00840 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 20721.56 | 20721.56 | 66.11 | 1.522 | 1.522 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 24.00 | 24.00 | 0.00868 | 26.10 | 0.00841 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 18031.94 | 18031.94 | 89.28 | 1.324 | 1.324 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:00:00 | 24.00 | 24.00 | 0.00864 | 25.13 | 0.00841 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 92548.94 | 92548.94 | 295.29 | 6.796 | 6.796 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 24.00 | 24.00 | 0.00889 | 26.40 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 149274.73 | 149274.73 | 739.07 | 10.962 | 10.962 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 24.00 | 24.00 | 0.00866 | 21.39 | 0.00840 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 209848.87 | 209848.87 | 669.55 | 15.410 | 15.410 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | 24.00 | 24.00 | 0.00868 | 26.17 | 0.00841 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 158564.62 | 158564.62 | 785.07 | 11.644 | 11.644 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00865 | 24.97 | 0.00840 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 10319.84 | 10319.84 | 32.93 | 0.758 | 0.758 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | 24.00 | 24.00 | 0.00885 | 26.40 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14662.00 | 14662.00 | 72.59 | 1.077 | 1.077 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:20:00 | 24.00 | 24.00 | 0.00866 | 21.91 | 0.00840 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22113.65 | 22113.65 | 70.56 | 1.624 | 1.624 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 24.00 | 24.00 | 0.00867 | 26.25 | 0.00841 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 16668.12 | 16668.12 | 82.53 | 1.224 | 1.224 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 17:10:00 | 24.00 | 24.00 | 0.00864 | 24.97 | 0.00840 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8581.41 | 8581.41 | 237.04 | 0.497 | 0.497 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00858 | 23.31 | 0.00840 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 82031.78 | 82031.78 | 2265.90 | 4.751 | 4.751 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 23.31 | 0.00840 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8321.49 | 8321.49 | 229.86 | 0.482 | 0.482 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 27.00 | 27.00 | 0.00859 | 23.31 | 0.00840 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371336.03 | 371336.03 | 473.84 | 21.508 | 21.508 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:00:00 | 27.00 | 27.00 | 0.00854 | 18.12 | 0.00839 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:20:00 | 21.00 | 24.38 | 0.00266 | -4.30 | 0.00266 | 1.200 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.000 | 1.078 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 19.60 | 22.13 | 0.00266 | -4.30 | 0.00266 | 1.078 | 0.00 |
CORE_MID | 194124.25 | 194124.25 | 77.77 | 8.229 | 10.778 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 10.778 | 0.00 |
CORE_TOP | 50596.92 | 50596.92 | 20.27 | 2.170 | 2.170 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -4.30 | 0.00266 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 5035.65 | 5035.65 | 16.07 | 0.216 | 0.216 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00737 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 3757.46 | 3757.46 | 18.60 | 0.161 | 0.161 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00747 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 6886.33 | 6886.33 | 21.97 | 0.296 | 0.296 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00760 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 2067.55 | 2067.55 | 10.24 | 0.088 | 0.088 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00688 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 115400.05 | 115400.05 | 368.20 | 4.965 | 4.965 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00772 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 77242.14 | 77242.14 | 382.43 | 3.324 | 3.324 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 116108.43 | 116108.43 | 370.46 | 4.996 | 4.996 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00773 | -4.30 | 0.00266 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 70209.33 | 70209.33 | 347.61 | 3.020 | 3.020 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00767 | -4.30 | 0.00266 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 15697.32 | 15697.32 | 50.09 | 0.676 | 0.676 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 10413.31 | 10413.31 | 51.56 | 0.449 | 0.449 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 15784.20 | 15784.20 | 50.36 | 0.680 | 0.680 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00781 | -4.30 | 0.00266 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 9889.20 | 9889.20 | 48.96 | 0.426 | 0.426 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -4.30 | 0.00266 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 18.00 | 26.75 | 0.00850 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 23.61 | 0.00647 | -4.30 | 0.00266 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 05:40:00 | 18.00 | 21.72 | 0.00298 | -4.30 | 0.00266 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 18.00 | 27.00 | 0.00850 | -4.30 | 0.00266 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 8.81 | 8.81 | 1.84 | 1.84 | 8.8115 | 2.9014 | 8.8115 | 0.3293 | 0.3000 |
VAV_MID WITH REHEAT | 80.80 | 80.80 | 27.08 | 27.08 | 80.8021 | 28.2236 | 80.8021 | 0.3493 | 0.3000 |
VAV_TOP WITH REHEAT | 8.74 | 8.74 | 4.40 | 4.40 | 8.7439 | 4.4004 | 8.7439 | 0.5033 | 0.3000 |
CAV_BAS | 5.28 | 5.28 | 1.20 | 1.20 | 5.2829 | 5.2829 | 5.2829 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.51 | 21.51 | 0.34 | 0.34 | 21.5081 | 21.5080 | 21.5081 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.50 | 0.50 | 0.02 | 0.02 | 0.4970 | 0.4970 | 0.4970 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 4.75 | 4.75 | 0.16 | 0.16 | 4.7514 | 4.7514 | 4.7514 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.48 | 0.48 | 0.02 | 0.02 | 0.4820 | 0.4820 | 0.4820 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 18754.006 | 18754.006 | 1.882589 | 0.00016407 | 378.066 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | 18754.01 | 18754.01 | 1.882589 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 18823.16 | 18823.16 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 376656.853 | 376656.853 | 18.323222 | 0.00329516 | 8490.058 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 376656.85 | 376656.85 | 18.323222 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 194124.25 | 0.00 | 377943.34 | 377943.34 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 72211.891 | 72211.891 | 2.169782 | 0.00063174 | 1907.334 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 72211.89 | 72211.89 | 2.169782 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00800000 | 51.1678 | 50596.92 | 0.00 | 72469.75 | 72469.75 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 7388.808 | 7388.808 | 0.236520 | 0.00006464 | 189.845 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 7388.81 | 7388.81 | 0.236520 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00737301 | 47.2078 | 5035.65 | 0.00 | 7411.53 | 7411.53 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 5878.285 | 5878.285 | 0.213129 | 0.00005143 | 144.047 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 5878.28 | 5878.28 | 0.213129 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00747122 | 47.8291 | 3757.46 | 0.00 | 5896.83 | 5896.83 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 9915.550 | 9915.550 | 0.304337 | 0.00008675 | 259.396 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 9915.55 | 9915.55 | 0.304337 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00760295 | 48.6617 | 6886.33 | 0.00 | 9945.24 | 9945.24 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 4700.029 | 4700.029 | 0.264833 | 0.00004112 | 102.689 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 4700.03 | 4700.03 | 0.264833 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00688415 | 44.1122 | 2067.55 | 0.00 | 4716.33 | 4716.33 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 164834.144 | 164834.144 | 4.965457 | 0.00144204 | 4348.690 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 164834.14 | 164834.14 | 4.965457 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00772281 | 49.4197 | 115400.05 | 0.00 | 165386.32 | 165386.32 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 110336.537 | 110336.537 | 3.324102 | 0.00096527 | 2910.791 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 110336.54 | 110336.54 | 3.324102 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00773695 | 49.5090 | 77242.14 | 0.00 | 110705.20 | 110705.20 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 165847.668 | 165847.668 | 4.996066 | 0.00145091 | 4375.398 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 165847.67 | 165847.67 | 4.996066 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00772667 | 49.4440 | 116108.43 | 0.00 | 166403.01 | 166403.01 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 100274.827 | 100274.827 | 3.020269 | 0.00087725 | 2645.635 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 100274.83 | 100274.83 | 3.020269 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00767491 | 49.1172 | 70209.33 | 0.00 | 100611.91 | 100611.91 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 22430.030 | 22430.030 | 0.676153 | 0.00019623 | 591.565 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22430.03 | 22430.03 | 0.676153 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00780974 | 49.9685 | 15697.32 | 0.00 | 22503.81 | 22503.81 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 14880.048 | 14880.048 | 0.448586 | 0.00013018 | 392.433 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14880.05 | 14880.05 | 0.448586 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00781056 | 49.9737 | 10413.31 | 0.00 | 14928.92 | 14928.92 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 22554.308 | 22554.308 | 0.679907 | 0.00019731 | 594.840 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 22554.31 | 22554.31 | 0.679907 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00781111 | 49.9772 | 15784.20 | 0.00 | 22628.47 | 22628.47 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 14130.367 | 14130.367 | 0.425945 | 0.00012362 | 372.677 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 14130.37 | 14130.37 | 0.425945 | 12.80 | 11.50 | 0.00800000 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 0.0000 | 21.00 | 0.00779560 | 49.8793 | 9889.20 | 0.00 | 14176.89 | 14176.89 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 153777.801 | -999.000 | 8.811450 | 0.00654206 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 153777.80 | 147423.23 | 8.811450 | 24.70 | 16.72 | 0.00872916 | 10.92 | 10.92 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 28.8056 | 24.00 | 0.00886288 | 47.1790 | 117809.81 | 0.00 | 155189.51 | 137904.50 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 52484.458 | 52484.458 | 2.643435 | 0.00045916 | 861.440 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 52484.46 | 52484.46 | 2.643435 | -3.78 | -3.85 | 0.00273611 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 96.0186 | 21.50 | 0.00536186 | 33.3953 | 17746.99 | 0.00 | 48595.18 | 48595.18 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1420511.662 | -999.000 | 80.802086 | 0.06043185 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 1420511.66 | 1359574.21 | 80.802086 | 24.78 | 16.76 | 0.00873969 | 10.92 | 10.92 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 31.4125 | 24.00 | 0.00890080 | 47.3779 | 1059219.74 | 0.00 | 1433507.74 | 1272503.50 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 496240.583 | 496240.583 | 24.240626 | 0.00434133 | 8121.437 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 496240.58 | 496240.58 | 24.240626 | -4.30 | -4.30 | 0.00265759 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 104.7083 | 21.00 | 0.00784987 | 50.2210 | 504871.90 | 0.00 | 456717.34 | 456717.34 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 152441.519 | -999.000 | 8.743866 | 0.00648521 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | 152441.52 | 146220.09 | 8.743866 | 24.70 | 16.72 | 0.00872608 | 10.92 | 10.92 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 29.0282 | 24.00 | 0.00885665 | 47.1462 | 119007.25 | 0.00 | 153841.58 | 136764.88 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 51126.335 | 51126.335 | 2.623160 | 0.00044728 | 840.582 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | 51126.33 | 51126.33 | 2.623160 | -3.48 | -3.52 | 0.00282577 | 12.80 | 11.50 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 96.7608 | 21.00 | 0.00784960 | 50.2193 | 58606.77 | 0.00 | 47506.65 | 47506.65 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 88716.897 | -999.000 | 5.282889 | 0.00377422 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | 88716.90 | 82845.21 | 5.282889 | 24.31 | 16.70 | 0.00886559 | 11.41 | 11.41 | 0.00850000 | 25.22 | 0.00840522 | 16.63 | 22.7178 | 24.00 | 0.00902028 | 48.0052 | 64983.31 | 0.00 | 89517.54 | 78448.73 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 259156.750 | 259156.750 | 5.282889 | 0.00226722 | 5768.646 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 259156.75 | 259156.75 | 5.282889 | -0.98 | -2.33 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.7178 | 24.43 | 0.00265759 | 13.9239 | 0.00 | 0.00 | 216968.52 | 216968.52 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 425158.455 | 306270.098 | 21.508131 | 0.01041210 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | 395708.01 | 393376.96 | -999.0 | 28.40 | 17.83 | 0.00854018 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | -999.0000 | 27.00 | 0.00854231 | 38.0738 | 370937.47 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9575.805 | 6988.259 | 0.497046 | 0.00023451 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8874.04 | 8769.04 | -999.0 | 27.84 | 17.67 | 0.00857852 | 12.80 | 12.00 | 0.00850000 | 23.31 | 0.00840224 | 15.95 | -999.0000 | 27.00 | 0.00858425 | 38.2557 | 8581.41 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91556.181 | 66808.195 | 4.751416 | 0.00224220 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 84848.82 | 83800.55 | -999.0 | 27.83 | 17.67 | 0.00858200 | 12.80 | 12.00 | 0.00850000 | 23.31 | 0.00840224 | 15.95 | -999.0000 | 27.00 | 0.00858812 | 38.2729 | 82031.78 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9287.157 | 6777.018 | 0.481993 | 0.00022744 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | 8606.72 | 8501.74 | -999.0 | 27.83 | 17.67 | 0.00858096 | 12.80 | 12.00 | 0.00850000 | 23.31 | 0.00840224 | 15.95 | -999.0000 | 27.00 | 0.00858695 | 38.2677 | 8321.49 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 425158.455 | 425158.455 | 21.508131 | 0.01041210 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 425158.45 | 425158.45 | 21.508131 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.5733 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 9575.805 | 9575.805 | 0.497046 | 0.00023451 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9575.81 | 9575.81 | 0.497046 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1450 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 91556.181 | 91556.181 | 4.751416 | 0.00224220 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 91556.18 | 91556.18 | 4.751416 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2900 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 9287.157 | 9287.157 | 0.481993 | 0.00022744 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 9287.16 | 9287.16 | 0.481993 | -4.30 | -4.30 | 0.00265759 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2433 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 17946.39 | 17946.39 | 21.508131 | -0.07 | -0.07 | 0.00840808 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 1.5733 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.497046 | -0.14 | -0.14 | 0.00831625 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.1450 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 8290.49 | 8290.49 | 4.751416 | -0.14 | -0.14 | 0.00634013 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2900 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | 829.05 | 829.05 | 0.481993 | -0.14 | -1.36 | 0.00297270 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 3.2433 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 18754.006 | 18754.006 | 1.882589 | 0.00016407 | 378.066 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 0.9333 | 0.952076 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 06:40:00 | Sensible | 18754.01 | 18754.01 | 1.0000 | 2.24286348 | 1.882589 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.16405149 | 60.00 | 32.22 | 27.78 | 0.000 | 18754.01 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 21.00 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 0.00 | 0.00 | 18823.16 | 18823.16 | 2.24286348 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 376656.853 | 376656.853 | 18.323222 | 0.00329516 | 8490.058 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 18.7443 | 19.121564 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 376656.85 | 376656.85 | 1.0000 | 21.82977371 | 18.323222 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 3.29482233 | 60.00 | 32.22 | 27.78 | 0.000 | 376656.85 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.56 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 194124.25 | 0.00 | 377943.34 | 377943.34 | 21.82977371 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 29.78 | 17.96 | 0.00800000 | 50373.0 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 72211.891 | 72211.891 | 2.169782 | 0.00063174 | 1907.334 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 3.5936 | 3.665948 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 72211.89 | 72211.89 | 1.0000 | 2.58501709 | 2.169782 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.63167668 | 60.00 | 32.22 | 27.78 | 0.000 | 72211.89 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00800000 | 21.00 | 0.00800000 | 51.1678 | 50596.92 | 0.00 | 72469.75 | 72469.75 | 2.58501709 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.29 | 21.27 | 0.00800000 | 61094.4 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 7388.808 | 7388.808 | 0.236520 | 0.00006464 | 189.845 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 0.3677 | 0.375104 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 7388.81 | 7388.81 | 1.0000 | 0.28178337 | 0.236520 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.06463392 | 60.00 | 32.22 | 27.78 | 0.000 | 7388.81 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.86 | 0.00737301 | 21.00 | 0.00737301 | 47.2078 | 5035.65 | 0.00 | 7411.53 | 7411.53 | 0.28178337 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.59 | 20.76 | 0.00800000 | 59362.1 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 5878.285 | 5878.285 | 0.213129 | 0.00005143 | 144.047 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 0.2925 | 0.298420 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 5878.28 | 5878.28 | 1.0000 | 0.25391578 | 0.213129 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.05142055 | 60.00 | 32.22 | 27.78 | 0.000 | 5878.28 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.92 | 0.00747122 | 21.00 | 0.00747122 | 47.8291 | 3757.46 | 0.00 | 5896.83 | 5896.83 | 0.25391578 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 35.57 | 19.84 | 0.00800000 | 56283.4 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 9915.550 | 9915.550 | 0.304337 | 0.00008675 | 259.396 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 0.4934 | 0.503378 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 9915.55 | 9915.55 | 1.0000 | 0.36257839 | 0.304337 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.08673671 | 60.00 | 32.22 | 27.78 | 0.000 | 9915.55 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.91 | 0.00760295 | 21.00 | 0.00760295 | 48.6617 | 6886.33 | 0.00 | 9945.24 | 9945.24 | 0.36257839 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 39.70 | 21.09 | 0.00800000 | 60489.0 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 4700.029 | 4700.029 | 0.264833 | 0.00004112 | 102.689 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 0.2339 | 0.238604 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 4700.03 | 4700.03 | 1.0000 | 0.31551520 | 0.264833 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.04111371 | 60.00 | 32.22 | 27.78 | 0.000 | 4700.03 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.87 | 0.00688415 | 21.00 | 0.00688415 | 44.1122 | 2067.55 | 0.00 | 4716.33 | 4716.33 | 0.31551520 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 27.46 | 17.18 | 0.00800000 | 48007.8 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 164834.144 | 164834.144 | 4.965457 | 0.00144204 | 4348.690 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 8.2030 | 8.368059 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 164834.14 | 164834.14 | 1.0000 | 5.91570601 | 4.965457 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.44189390 | 60.00 | 32.22 | 27.78 | 0.000 | 164834.14 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00772281 | 21.00 | 0.00772281 | 49.4197 | 115400.05 | 0.00 | 165386.32 | 165386.32 | 5.91570601 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61017.0 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 110336.537 | 110336.537 | 3.324102 | 0.00096527 | 2910.791 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 5.4909 | 5.601404 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 110336.54 | 110336.54 | 1.0000 | 3.96024179 | 3.324102 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.96517369 | 60.00 | 32.22 | 27.78 | 0.000 | 110336.54 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00773695 | 21.00 | 0.00773695 | 49.5090 | 77242.14 | 0.00 | 110705.20 | 110705.20 | 3.96024179 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.25 | 0.00800000 | 61014.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 165847.668 | 165847.668 | 4.996066 | 0.00145091 | 4375.398 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 8.2534 | 8.419512 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 165847.67 | 165847.67 | 1.0000 | 5.95217366 | 4.996066 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 1.45075974 | 60.00 | 32.22 | 27.78 | 0.000 | 165847.67 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00772667 | 21.00 | 0.00772667 | 49.4440 | 116108.43 | 0.00 | 166403.01 | 166403.01 | 5.95217366 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61016.5 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 100274.827 | 100274.827 | 3.020269 | 0.00087725 | 2645.635 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 4.9902 | 5.090606 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 100274.83 | 100274.83 | 1.0000 | 3.59826338 | 3.020269 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.87715845 | 60.00 | 32.22 | 27.78 | 0.000 | 100274.83 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00767491 | 21.00 | 0.00767491 | 49.1172 | 70209.33 | 0.00 | 100611.91 | 100611.91 | 3.59826338 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.22 | 21.25 | 0.00800000 | 61021.1 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22430.030 | 22430.030 | 0.676153 | 0.00019623 | 591.565 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 1.1162 | 1.138695 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22430.03 | 22430.03 | 1.0000 | 0.80554943 | 0.676153 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.19620767 | 60.00 | 32.22 | 27.78 | 0.000 | 22430.03 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00780974 | 21.00 | 0.00780974 | 49.9685 | 15697.32 | 0.00 | 22503.81 | 22503.81 | 0.80554943 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.8 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14880.048 | 14880.048 | 0.448586 | 0.00013018 | 392.433 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 0.7405 | 0.755409 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14880.05 | 14880.05 | 1.0000 | 0.53443224 | 0.448586 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.13016388 | 60.00 | 32.22 | 27.78 | 0.000 | 14880.05 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781056 | 21.00 | 0.00781056 | 49.9737 | 10413.31 | 0.00 | 14928.92 | 14928.92 | 0.53443224 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.19 | 21.24 | 0.00800000 | 60994.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 22554.308 | 22554.308 | 0.679907 | 0.00019731 | 594.840 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 1.1224 | 1.145004 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 22554.31 | 22554.31 | 1.0000 | 0.81002165 | 0.679907 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.19729480 | 60.00 | 32.22 | 27.78 | 0.000 | 22554.31 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00781111 | 21.00 | 0.00781111 | 49.9772 | 15784.20 | 0.00 | 22628.47 | 22628.47 | 0.81002165 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60995.5 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 14130.367 | 14130.367 | 0.425945 | 0.00012362 | 372.677 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 0.7032 | 0.717350 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 14130.37 | 14130.37 | 1.0000 | 0.50745945 | 0.425945 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 0.12360601 | 60.00 | 32.22 | 27.78 | 0.000 | 14130.37 | -4.30 | 0.00265759 | -4.30 | 0.00000000 | 0.0000 | 20.95 | 0.00779560 | 21.00 | 0.00779560 | 49.8793 | 9889.20 | 0.00 | 14176.89 | 14176.89 | 0.50745945 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60996.8 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 153777.801 | -999.000 | 8.811450 | 0.00654206 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0671 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.811450 | 10.49771505 | 4197.9300 | 999.8980 | 77.22547096 | 12.27 | 6.67 | 5.60 | 1815447.88 | 8.4705 | 8.470516 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 153777.80 | 147423.23 | 1.0000 | 10.49771505 | 8.811450 | 24.70 | 16.72 | 0.00872916 | 47054.8 | 10.92 | 10.92 | 0.00850000 | 32406.1 | 6.54139579 | 6.67 | 12.27 | 5.60 | 20122.954 | 133654.85 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 28.8056 | 24.00 | 0.00886288 | 24.00 | 0.00886288 | 47.1790 | 117809.81 | 0.00 | 155189.51 | 137904.50 | 10.49771505 | 24.70 | 16.83 | 0.00872916 | 47054.8 | 11.84 | 11.27 | 0.00807653 | 32271.6 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 52484.458 | 52484.458 | 2.643435 | 0.00045916 | 861.440 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 8.811450 | 10.49771505 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 2.6119 | 2.664454 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 52484.46 | 52484.46 | 1.0000 | 3.14931451 | 2.643435 | -3.78 | -3.85 | 0.00273611 | 3020.5 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.45911010 | 60.00 | 32.22 | 27.78 | 0.000 | 52484.46 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 96.0186 | 8.64 | 0.00462975 | 21.50 | 0.00536186 | 33.3953 | 17746.99 | 0.00 | 48595.18 | 48595.18 | 3.14931451 | 2.80 | 0.14 | 0.00273611 | 9670.6 | 18.08 | 8.21 | 0.00273611 | 25101.0 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1420511.662 | -999.000 | 80.802086 | 0.06043185 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0866 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.802086 | 96.26534337 | 4197.9300 | 999.8980 | 77.22547096 | 12.27 | 6.67 | 5.60 | 1815447.88 | 78.2458 | 78.245797 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:50:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 1420511.66 | 1359574.21 | 1.0000 | 96.26534337 | 80.802086 | 24.78 | 16.76 | 0.00873969 | 47162.4 | 10.92 | 10.92 | 0.00850000 | 32406.1 | 60.42568522 | 6.67 | 12.27 | 5.60 | 184529.970 | 1235981.69 | 26.40 | 0.00840708 | 17.04 | 25.38195000 | 31.4125 | 24.00 | 0.00890080 | 24.00 | 0.00890080 | 47.3779 | 1059219.74 | 0.00 | 1433507.74 | 1272503.50 | 96.26534337 | 24.78 | 16.87 | 0.00873969 | 47162.4 | 11.84 | 11.27 | 0.00807677 | 32271.1 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 496240.583 | 496240.583 | 24.240626 | 0.00434133 | 8121.437 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 80.802086 | 96.26534337 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 24.6954 | 25.192416 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:50:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 496240.58 | 496240.58 | 1.0000 | 28.87960301 | 24.240626 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 4.34088624 | 60.00 | 32.22 | 27.78 | 0.000 | 496240.58 | -4.30 | 0.00265759 | -4.30 | 25.38195000 | 104.7083 | 21.00 | 0.00787062 | 21.00 | 0.00784987 | 50.2210 | 504871.90 | 0.00 | 456717.34 | 456717.34 | 28.87960301 | 2.80 | 0.02 | 0.00265759 | 9473.9 | 18.46 | 8.30 | 0.00265759 | 25288.4 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 152441.519 | -999.000 | 8.743866 | 0.00648521 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.0614 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.743866 | 10.41719663 | 4197.9300 | 999.8980 | 77.22547096 | 12.27 | 6.67 | 5.60 | 1815447.88 | 8.3969 | 8.396910 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:10:00 | Sensible | 152441.52 | 146220.09 | 1.0000 | 10.41719663 | 8.743866 | 24.70 | 16.72 | 0.00872608 | 47039.7 | 10.92 | 10.92 | 0.00850000 | 32406.1 | 6.48455306 | 6.67 | 12.27 | 5.60 | 19968.609 | 132472.91 | 26.40 | 0.00840708 | 17.04 | 2.53819000 | 29.0282 | 24.00 | 0.00885665 | 24.00 | 0.00885665 | 47.1462 | 119007.25 | 0.00 | 153841.58 | 136764.88 | 10.41719663 | 24.70 | 16.83 | 0.00872608 | 47039.7 | 11.84 | 11.27 | 0.00807633 | 32271.7 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 51126.335 | 51126.335 | 2.623160 | 0.00044728 | 840.582 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 8.743866 | 10.41719663 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 2.5443 | 2.595507 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 20:20:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 08:00:00 | Sensible | 51126.33 | 51126.33 | 1.0000 | 3.12515899 | 2.623160 | -3.48 | -3.52 | 0.00282577 | 3551.5 | 12.80 | 11.50 | 0.00800000 | 33059.8 | 0.44722985 | 60.00 | 32.22 | 27.78 | 0.000 | 51126.33 | -4.30 | 0.00265759 | -4.30 | 2.53819000 | 96.7608 | 21.00 | 0.00784960 | 21.00 | 0.00784960 | 50.2193 | 58606.77 | 0.00 | 47506.65 | 47506.65 | 3.12515899 | 2.80 | 0.27 | 0.00282577 | 9895.3 | 17.85 | 8.21 | 0.00282577 | 25096.7 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 88716.897 | -999.000 | 5.282889 | 0.00377422 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3207 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:ConstantVolume | 5.282889 | 6.29388553 | 4197.9300 | 999.8980 | 77.22547096 | 12.27 | 6.67 | 5.60 | 1815447.88 | 4.8868 | 4.886777 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 12:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 08:00:00 | Sensible | 88716.90 | 82845.21 | 1.0000 | 6.29388553 | 5.282889 | 24.31 | 16.70 | 0.00886559 | 46995.6 | 11.41 | 11.41 | 0.00850000 | 32899.9 | 3.77383689 | 6.67 | 12.27 | 5.60 | 8957.953 | 79758.94 | 25.22 | 0.00840522 | 16.63 | 1.20015641 | 22.7178 | 24.00 | 0.00902028 | 24.00 | 0.00902028 | 48.0052 | 64983.31 | 0.00 | 89517.54 | 78448.73 | 6.29388553 | 24.31 | 16.81 | 0.00886559 | 46995.6 | 12.10 | 11.47 | 0.00816866 | 32772.7 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 259156.750 | 259156.750 | 5.282889 | 0.00226722 | 5768.646 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | CAV_BAS FAN | Fan:ConstantVolume | 5.282889 | 6.29388553 | 4197.9300 | 999.8980 | 17.23092474 | 54.44 | 82.22 | 27.78 | 2009444.52 | 12.8969 | 13.156491 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 259156.75 | 259156.75 | 1.0000 | 6.29388553 | 5.282889 | -0.98 | -2.33 | 0.00265759 | 5660.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | 2.26698503 | 60.00 | 32.22 | 27.78 | 0.000 | 259156.75 | -4.30 | 0.00265759 | -4.30 | 1.20015641 | 22.7178 | 0.00 | 0.00265759 | 24.43 | 0.00265759 | 13.9239 | 0.00 | 0.00 | 216968.52 | 216968.52 | 6.29388553 | 12.80 | 5.54 | 0.00265759 | 19571.7 | 46.94 | 19.28 | 0.00265759 | 54044.6 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 425158.455 | 306270.098 | 21.508131 | 0.01041210 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7158 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 15:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 07:10:00 | Sensible | 395708.01 | 393376.96 | 0.9307 | -999.0 | -999.0 | 28.40 | 17.83 | 0.00854018 | 50349.9 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 395708.01 | 26.40 | 0.00840708 | 17.04 | 0.33839277 | -999.0000 | 27.00 | 0.00854231 | 27.00 | 0.00854231 | 38.0738 | 370937.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9575.805 | 6988.259 | 0.497046 | 0.00023451 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7870 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8874.04 | 8769.04 | 0.9267 | -999.0 | -999.0 | 27.84 | 17.67 | 0.00857852 | 49871.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8874.04 | 23.31 | 0.00840224 | 15.95 | 0.01563234 | -999.0000 | 27.00 | 0.00858425 | 27.00 | 0.00858425 | 38.2557 | 8581.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 91556.181 | 66808.195 | 4.751416 | 0.00224220 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7935 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 84848.82 | 83800.55 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00858200 | 49874.3 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84848.82 | 23.31 | 0.00840224 | 15.95 | 0.15632344 | -999.0000 | 27.00 | 0.00858812 | 27.00 | 0.00858812 | 38.2729 | 82031.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 9287.157 | 6777.018 | 0.481993 | 0.00022744 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1020.7916 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 18:40:00 | Sensible | 8606.72 | 8501.74 | 0.9267 | -999.0 | -999.0 | 27.83 | 17.67 | 0.00858096 | 49873.5 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8606.72 | 23.31 | 0.00840224 | 15.95 | 0.01563234 | -999.0000 | 27.00 | 0.00858695 | 27.00 | 0.00858695 | 38.2677 | 8321.49 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 425158.455 | 425158.455 | 21.508131 | 0.01041210 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 425158.45 | 425158.45 | 1.0000 | 25.62418478 | 21.508131 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 425158.45 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.5733 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9575.805 | 9575.805 | 0.497046 | 0.00023451 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9575.81 | 9575.81 | 1.0000 | 0.59216729 | 0.497046 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9575.81 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1450 | 0.00 | 0.00850000 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 91556.181 | 91556.181 | 4.751416 | 0.00224220 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 91556.18 | 91556.18 | 1.0000 | 5.66070450 | 4.751416 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 91556.18 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.2900 | 0.00 | 0.00646541 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 9287.157 | 9287.157 | 0.481993 | 0.00022744 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 1.1914 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 9287.16 | 9287.16 | 1.0000 | 0.57423344 | 0.481993 | -4.30 | -4.30 | 0.00265759 | 2304.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 9287.16 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.2433 | 0.00 | 0.00298326 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 17946.392 | 17946.392 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 21.508131 | 25.62418478 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 17946.39 | 17946.39 | 1.0000 | 25.62418478 | 21.508131 | -0.07 | -0.07 | 0.00840808 | 20959.1 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17946.39 | -4.30 | 0.00265759 | -4.30 | 0.33839277 | 1.5733 | 0.00 | 0.00850000 | 27.00 | 0.00850000 | 37.8820 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.497046 | 0.59216729 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.59216729 | 0.497046 | -0.14 | -0.14 | 0.00831625 | 20660.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.1450 | 0.00 | 0.00850000 | 26.98 | 0.00850000 | 37.9283 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8290.489 | 8290.489 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 4.751416 | 5.66070450 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 8290.49 | 8290.49 | 1.0000 | 5.66070450 | 4.751416 | -0.14 | -0.14 | 0.00634013 | 15712.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8290.49 | -4.30 | 0.00265759 | -4.30 | 0.15632344 | 3.2900 | 0.00 | 0.00646541 | 24.76 | 0.00646541 | 33.0078 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 829.049 | 829.049 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.481993 | 0.57423344 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 00:10:00 | Sensible | 829.05 | 829.05 | 1.0000 | 0.57423344 | 0.481993 | -0.14 | -1.36 | 0.00297270 | 7293.6 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 829.05 | -4.30 | 0.00265759 | -4.30 | 0.01563234 | 3.2433 | 0.00 | 0.00298326 | 23.56 | 0.00298326 | 16.4560 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.81 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 80.80 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 8.74 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 5.28 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 2305.50 | 268.67 | 0.00 |
CORE_BOTTOM | 2296.67 | 532.83 | 12.50 |
CORE_MID | 1055.33 | 2793.67 | 12.33 |
CORE_TOP | 1181.33 | 4188.67 | 423.17 |
PERIMETER_BOT_ZN_3 | 1061.83 | 3493.50 | 16.83 |
PERIMETER_BOT_ZN_2 | 1469.00 | 3508.17 | 78.17 |
PERIMETER_BOT_ZN_1 | 1689.50 | 3171.33 | 91.33 |
PERIMETER_BOT_ZN_4 | 2557.17 | 1756.17 | 88.00 |
PERIMETER_MID_ZN_3 | 1275.83 | 4718.33 | 812.17 |
PERIMETER_MID_ZN_2 | 1571.17 | 3569.67 | 719.17 |
PERIMETER_MID_ZN_1 | 1752.67 | 3802.50 | 460.50 |
PERIMETER_MID_ZN_4 | 1681.50 | 4168.33 | 561.50 |
PERIMETER_TOP_ZN_3 | 2298.50 | 5034.33 | 1894.00 |
PERIMETER_TOP_ZN_2 | 2757.00 | 4317.33 | 1720.00 |
PERIMETER_TOP_ZN_1 | 2439.50 | 4244.67 | 1353.17 |
PERIMETER_TOP_ZN_4 | 2370.17 | 4535.50 | 1418.67 |
DATACENTER_BOT_ZN_6 | 5943.00 | 552.67 | 552.67 |
DATACENTER_MID_ZN_6 | 5917.33 | 30.67 | 30.67 |
DATACENTER_TOP_ZN_6 | 5471.83 | 176.33 | 75.33 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5761.67 | 5761.67 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5942.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 57.83 | 0.00 | 6.50 |
CORE_BOTTOM | 0.00 | 1.83 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 2.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 13.33 | 0.00 | 13.33 |
PERIMETER_BOT_ZN_1 | 0.00 | 16.83 | 0.00 | 16.83 |
PERIMETER_BOT_ZN_4 | 0.00 | 49.83 | 0.00 | 20.17 |
PERIMETER_MID_ZN_3 | 3.17 | 0.00 | 0.17 | 0.00 |
PERIMETER_MID_ZN_2 | 2.33 | 10.83 | 0.00 | 10.83 |
PERIMETER_MID_ZN_1 | 0.83 | 14.83 | 0.00 | 14.67 |
PERIMETER_MID_ZN_4 | 0.83 | 17.00 | 0.00 | 9.17 |
PERIMETER_TOP_ZN_3 | 73.17 | 0.00 | 22.67 | 0.00 |
PERIMETER_TOP_ZN_2 | 31.33 | 6.50 | 0.67 | 6.50 |
PERIMETER_TOP_ZN_1 | 22.17 | 10.00 | 0.00 | 9.67 |
PERIMETER_TOP_ZN_4 | 18.83 | 15.00 | 0.00 | 7.83 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 12.67 | 0.00 | 10.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 76.50 | 180.50 | 23.17 | 89.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.70 | 149.60 | 6779.02 | 1.262 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.41 | 134.35 | 6849.35 | 0.981 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.41 | 134.35 | 6849.35 | 0.740 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.41 | 134.35 | 6849.35 | 0.679 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.96 | 16.87 | 860.00 | 0.836 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 1.244 | 0.026 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.96 | 16.87 | 860.02 | 1.330 | 0.025 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 1.839 | 0.026 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.96 | 16.87 | 860.00 | 0.662 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 1.064 | 0.064 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.96 | 16.87 | 860.02 | 1.231 | 0.059 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 1.235 | 0.061 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.96 | 16.87 | 860.00 | 0.641 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 1.103 | 0.075 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.96 | 16.87 | 860.02 | 1.176 | 0.073 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 1.221 | 0.075 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.427 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.426 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.40 | 42.18 | 1911.37 | 0.480 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 61.70 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.41 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.91 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 6.96 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 6.96 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.48 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.80 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.40 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 61.70 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.41 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.91 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 6.96 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 6.96 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.48 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.80 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.80 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.40 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1022.56 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 51692663.28 | 0.00 | 51692663.28 | 0.00 | 51692663.28 | 37848132.68 | 3959.56 | 138.63 | 4661.81 | 363.10 |
CORE_BOTTOM | 41268052.78 | 0.00 | 41268052.78 | 0.00 | 41268052.78 | 33990283.35 | 4188.63 | 74.77 | 4496.60 | 409.78 |
CORE_MID | 0.30E+09 | 0.00 | 0.30E+09 | 0.00 | 0.30E+09 | 0.34E+09 | 5533.35 | 75.55 | 3151.10 | 123.18 |
CORE_TOP | 27616735.98 | 0.00 | 27616735.98 | 0.00 | 27616735.98 | 33990283.35 | 6218.75 | 57.26 | 2483.99 | 234.10 |
PERIMETER_BOT_ZN_3 | 4439752.79 | 0.00 | 4439752.79 | 255127.48 | 4694880.27 | 4267819.30 | 5218.13 | 121.53 | 3420.34 | 409.78 |
PERIMETER_BOT_ZN_2 | 4246145.81 | 0.00 | 4246145.81 | 170084.87 | 4416230.68 | 2750345.05 | 3536.37 | 14.15 | 5209.47 | 409.78 |
PERIMETER_BOT_ZN_1 | 6989017.36 | 0.00 | 6989017.36 | 255127.48 | 7244144.84 | 4267912.63 | 3634.84 | 39.43 | 5085.73 | 409.78 |
PERIMETER_BOT_ZN_4 | 6249340.20 | 0.00 | 6249340.20 | 170084.87 | 6419425.07 | 2750345.05 | 3495.15 | 0.64 | 5264.21 | 409.78 |
PERIMETER_MID_ZN_3 | 33960746.20 | 0.00 | 33960746.20 | 598343.38 | 34559089.58 | 42678193.03 | 5947.06 | 95.58 | 2717.35 | 123.18 |
PERIMETER_MID_ZN_2 | 38468102.35 | 0.00 | 38468102.35 | 398895.31 | 38866997.66 | 27503450.52 | 3951.21 | 9.97 | 4798.82 | 1032.18 |
PERIMETER_MID_ZN_1 | 62697437.15 | 0.00 | 62697437.15 | 598343.38 | 63295780.53 | 42679126.28 | 3988.09 | 7.39 | 4764.51 | 123.18 |
PERIMETER_MID_ZN_4 | 40807336.55 | 0.00 | 40807336.55 | 398895.31 | 41206231.86 | 27503450.52 | 3924.00 | 12.30 | 4823.70 | 123.18 |
PERIMETER_TOP_ZN_3 | 3292378.70 | 0.00 | 3292378.70 | 742904.54 | 4035283.24 | 4267819.30 | 6149.48 | 64.54 | 2545.99 | 234.10 |
PERIMETER_TOP_ZN_2 | 3631443.26 | 0.00 | 3631443.26 | 495269.35 | 4126712.61 | 2750345.05 | 4114.77 | 5.86 | 4639.37 | 234.10 |
PERIMETER_TOP_ZN_1 | 5992329.36 | 0.00 | 5992329.36 | 742904.54 | 6735233.90 | 4267912.63 | 4124.85 | 2.66 | 4632.49 | 234.10 |
PERIMETER_TOP_ZN_4 | 4032227.91 | 0.00 | 4032227.91 | 495269.35 | 4527497.26 | 2750345.05 | 4078.50 | 5.11 | 4676.39 | 234.10 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.50E+10 | 0.00 | 0.50E+10 | 23271546.24 | 0.50E+10 | 0.50E+10 | 6463.67 | 4440.04 | 5389.98 | 1577.71 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.3297 | 0.0000 | 2.3297 | 0.0000 | 2.3297 | 1.2002 | 1314.13 | 134.78 | 4494.09 |
CORE_BOTTOM | 1.8292 | 0.0000 | 1.8292 | 0.0000 | 1.8292 | 1.0778 | 1679.88 | 69.74 | 4193.38 |
CORE_MID | 13.7997 | 0.0000 | 13.7997 | 0.0000 | 13.7997 | 10.7782 | 2796.14 | 74.28 | 3072.58 |
CORE_TOP | 1.2682 | 0.0000 | 1.2682 | 0.0000 | 1.2682 | 1.0778 | 3437.99 | 57.26 | 2447.75 |
PERIMETER_BOT_ZN_3 | 0.1959 | 0.0000 | 0.1959 | 0.0059 | 0.2018 | 0.1353 | 2700.48 | 115.89 | 3126.63 |
PERIMETER_BOT_ZN_2 | 0.1880 | 0.0000 | 0.1880 | 0.0039 | 0.1919 | 0.0872 | 1119.49 | 9.94 | 4813.57 |
PERIMETER_BOT_ZN_1 | 0.3117 | 0.0000 | 0.3117 | 0.0059 | 0.3176 | 0.1353 | 1197.89 | 34.08 | 4711.02 |
PERIMETER_BOT_ZN_4 | 0.2775 | 0.0000 | 0.2775 | 0.0039 | 0.2815 | 0.0872 | 1087.92 | 0.64 | 4854.44 |
PERIMETER_MID_ZN_3 | 1.5549 | 0.0000 | 1.5549 | 0.0138 | 1.5688 | 1.3533 | 3208.81 | 94.28 | 2639.91 |
PERIMETER_MID_ZN_2 | 1.6107 | 0.0000 | 1.6107 | 0.0098 | 1.6205 | 0.8721 | 1227.93 | 9.49 | 3796.58 |
PERIMETER_MID_ZN_1 | 2.8871 | 0.0000 | 2.8871 | 0.0138 | 2.9009 | 1.3533 | 1261.32 | 7.08 | 4674.60 |
PERIMETER_MID_ZN_4 | 1.8692 | 0.0000 | 1.8692 | 0.0092 | 1.8784 | 0.8721 | 1204.73 | 9.62 | 4728.65 |
PERIMETER_TOP_ZN_3 | 0.1509 | 0.0000 | 0.1509 | 0.0172 | 0.1681 | 0.1353 | 3369.49 | 64.45 | 2509.06 |
PERIMETER_TOP_ZN_2 | 0.1670 | 0.0000 | 0.1670 | 0.0115 | 0.1785 | 0.0872 | 1349.10 | 3.99 | 4589.91 |
PERIMETER_TOP_ZN_1 | 0.2760 | 0.0000 | 0.2760 | 0.0172 | 0.2932 | 0.1353 | 1355.37 | 2.44 | 4585.19 |
PERIMETER_TOP_ZN_4 | 0.1849 | 0.0000 | 0.1849 | 0.0115 | 0.1964 | 0.0872 | 1319.34 | 2.84 | 4620.82 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 225.8075 | 0.0000 | 225.8075 | 0.5438 | 226.3513 | 158.4706 | 3646.67 | 4411.89 | 4899.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 89693097.63 | 0.00 | 89693097.63 | 48026705.38 | 3502.96 | 0.54 | 5256.49 | 409.78 |
VAV_MID WITH REHEAT | 0.68E+09 | 0.00 | 0.68E+09 | 0.48E+09 | 3934.02 | 8.44 | 4817.53 | 123.18 |
VAV_TOP WITH REHEAT | 63254266.30 | 0.00 | 63254266.30 | 48026705.38 | 4095.18 | 5.74 | 4659.08 | 234.10 |
CAV_BAS | 73370874.31 | 0.00 | 73370874.31 | 37848132.68 | 3861.17 | 4.77 | 4894.06 | 363.10 |
AIRLOOP DATACENTER BASEMENT | 7505992.82 | 0.00 | 7505992.82 | 10671554.30 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER BOT | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER MID | 3467457.73 | 0.00 | 3467457.73 | 4929815.99 | 4419.00 | 0.00 | 4341.00 | 0.00 |
AIRLOOP DATACENTER TOP | 346745.77 | 0.00 | 346745.77 | 492981.60 | 4419.00 | 0.00 | 4341.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 3.9775 | 0.0000 | 3.9775 | 1.5229 | 1093.85 | 0.35 | 4848.80 |
VAV_MID WITH REHEAT | 31.0529 | 0.0000 | 31.0529 | 15.2292 | 1212.70 | 7.05 | 4723.25 |
VAV_TOP WITH REHEAT | 2.9055 | 0.0000 | 2.9055 | 1.5229 | 1329.47 | 5.21 | 4608.33 |
CAV_BAS | 3.3067 | 0.0000 | 3.3067 | 1.2002 | 1295.55 | 0.18 | 4647.27 |
AIRLOOP DATACENTER BASEMENT | 0.3508 | 0.0000 | 0.3508 | 0.3384 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER BOT | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER MID | 0.1621 | 0.0000 | 0.1621 | 0.1563 | 1602.00 | 0.00 | 4341.00 |
AIRLOOP DATACENTER TOP | 0.0162 | 0.0000 | 0.0162 | 0.0156 | 1602.00 | 0.00 | 4341.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.00 | 4549.63 | 0.00 | 0.00 | 0.00 | 719.58 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.00 | 3846.63 | 0.00 | 0.00 | 0.00 | 1059.87 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3070.78 | 0.00 | 0.00 | 0.00 | 1934.31 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 129.19 | 4895.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 5.2972 | 0.0000 | 0.0000 | 0.0000 | 2.3828 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 42.9950 | 0.0000 | 0.0000 | 0.0000 | 23.1135 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 4.5264 | 0.0000 | 0.0000 | 0.0000 | 2.2910 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.7060 | 4.2877 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.4804 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.2219 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0222 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
Electricity:Building | 17965.63 | 247233.96 | 01-JAN-09:50 | 1055078.17 | 01-DEC-15:30 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17965.63 | 247233.96 | 01-JAN-09:50 | 1055078.17 | 01-DEC-15:30 |
InteriorLights:Electricity | 2752.22 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2752.22 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity | 2752.22 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2752.22 | 13024.70 | 01-JAN-09:50 | 261074.09 | 02-JAN-08:10 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.41 | 818.50 | 01-JAN-09:40 | 4026.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.07 | 59.73 | 01-JAN-09:40 | 1750.00 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 14.07 | 59.73 | 01-JAN-09:40 | 1750.00 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 35.01 | 527.47 | 01-JAN-08:50 | 2594.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.01 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 9.01 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.28 | 818.51 | 01-JAN-08:50 | 4026.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.94 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.94 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 35.04 | 527.47 | 01-JAN-09:40 | 2594.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.04 | 38.49 | 01-JAN-09:40 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 9.04 | 38.49 | 01-JAN-09:40 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 544.30 | 8184.99 | 01-JAN-09:50 | 40263.18 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.88 | 597.26 | 01-JAN-09:50 | 17500.00 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 140.88 | 597.26 | 01-JAN-09:50 | 17500.00 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 350.15 | 5274.72 | 01-JAN-08:50 | 25947.12 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.17 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 90.17 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 542.95 | 8185.12 | 01-JAN-08:50 | 40263.91 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 139.52 | 597.27 | 01-JAN-08:50 | 17500.38 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 139.52 | 597.27 | 01-JAN-08:50 | 17500.38 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 350.43 | 5274.69 | 01-JAN-09:40 | 25947.03 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 90.45 | 384.90 | 01-JAN-09:40 | 11277.66 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 90.45 | 384.90 | 01-JAN-09:40 | 11277.66 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.43 | 818.50 | 01-JAN-09:50 | 4026.32 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.09 | 59.73 | 01-JAN-09:50 | 1750.00 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 14.09 | 59.73 | 01-JAN-09:50 | 1750.00 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 35.02 | 527.47 | 01-JAN-08:50 | 2594.71 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.02 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 9.02 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.29 | 818.51 | 01-JAN-08:50 | 4026.39 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.95 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.95 | 59.73 | 01-JAN-08:50 | 1750.04 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 35.04 | 527.47 | 01-JAN-09:40 | 2594.70 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.04 | 38.49 | 01-JAN-09:40 | 1127.77 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 9.04 | 38.49 | 01-JAN-09:40 | 1127.77 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 1139.06 | 5852.28 | 10-JAN-08:00 | 310244.48 | 13-JUN-16:00 |
HeatRejection:Electricity | 726.26 | 2371.39 | 10-JAN-08:00 | 76172.40 | 22-MAY-14:30 |
General:HeatRejection:Electricity | 726.26 | 2371.39 | 10-JAN-08:00 | 76172.40 | 22-MAY-14:30 |
Electricity:HVAC | 4526.88 | 74352.91 | 01-JAN-08:50 | 362723.22 | 14-AUG-15:20 |
ExteriorEquipment:Electricity | 1914.39 | 28294.68 | 01-JAN-00:10 | 117204.73 | 02-JAN-08:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3726.76 | 01-DEC-15:40 |
ElectricityPurchased:Facility | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
ElectricityPurchased:Plant | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
Cogeneration:ElectricityPurchased | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
ElectricityNet:Plant | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
Cogeneration:ElectricityNet | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
General:Cogeneration:ElectricityNet | 25935.27 | 363276.21 | 01-JAN-12:10 | 1732817.37 | 14-AUG-15:10 |
Fans:Electricity | 2190.10 | 42078.63 | 01-JAN-00:10 | 216449.11 | 13-JUN-15:30 |
General:Fans:Electricity | 2190.10 | 42078.63 | 01-JAN-00:10 | 216449.11 | 13-JUN-15:30 |
ExteriorLights:Electricity | 449.08 | 0.00 | 01-JAN-08:20 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 449.08 | 0.00 | 01-JAN-08:20 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 2435.98 | 28222.04 | 10-JAN-08:00 | 314554.22 | 14-AUG-15:10 |
General:Cooling:Electricity | 2435.98 | 28222.04 | 10-JAN-08:00 | 314554.22 | 14-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 5.10 | 0.00 | 01-JAN-00:10 | 5914.43 | 10-JAN-21:00 |
General:Humidifier:Electricity | 5.10 | 0.00 | 01-JAN-00:10 | 5914.43 | 10-JAN-21:00 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 248.73 | 3345.30 | 09-JAN-05:40 | 48432.31 | 28-APR-15:00 |
General:Pumps:Electricity | 248.73 | 3345.30 | 09-JAN-05:40 | 48432.31 | 28-APR-15:00 |
WIRED_LTG_ELECTRICITY | 77.34 | 0.00 | 01-JAN-00:10 | 7336.18 | 02-JAN-08:20 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1929.01 | 5695.87 | 30-APR-16:20 | 755699.03 | 10-JAN-08:00 |
NaturalGas:Plant | 1929.01 | 5695.87 | 30-APR-16:20 | 755699.03 | 10-JAN-08:00 |
Heating:NaturalGas | 1183.57 | 0.00 | 01-JAN-00:10 | 725897.71 | 10-JAN-08:00 |
Boiler:Heating:NaturalGas | 1183.57 | 0.00 | 01-JAN-00:10 | 725897.71 | 10-JAN-08:00 |
WaterSystems:NaturalGas | 745.44 | 5695.87 | 04-MAR-05:10 | 82180.11 | 17-FEB-12:20 |
Water Heater:WaterSystems:NaturalGas | 745.44 | 5695.87 | 04-MAR-05:10 | 82180.11 | 17-FEB-12:20 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 13147.84 | 139000.83 | 10-JAN-08:00 | 1831849.49 | 14-AUG-15:50 |
PlantLoopCoolingDemand:HVAC | 13147.84 | 139000.83 | 10-JAN-08:00 | 1831849.49 | 14-AUG-15:50 |
CoolingCoils:PlantLoopCoolingDemand | 13147.84 | 139000.83 | 10-JAN-08:00 | 1831849.49 | 14-AUG-15:50 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 3095.85 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
Water:HVAC | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
Humidifier:Water | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
General:Humidifier:Water | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
MainsWater:Facility | 3095.85 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
MainsWater:HVAC | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
Humidifier:MainsWater | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
General:Humidifier:MainsWater | 1.90 | 0.00 | 01-JAN-00:10 | 0.00 | 10-JAN-21:00 |
Water:Plant | 3093.96 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 3093.96 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 813.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
General:HeatRejection:Water | 813.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
HeatRejection:MainsWater | 813.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
General:HeatRejection:MainsWater | 813.79 | 0.00 | 01-JAN-00:10 | 0.00 | 21-JUL-17:00 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 33526.21 | 217493.28 | 15-JAN-06:00 | 7141200.35 | 13-JUN-16:00 |
EnergyTransfer:Building | 16929.86 | 88179.84 | 15-JAN-07:00 | 1445466.07 | 14-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 628.54 | 0.00 | 01-JAN-00:10 | 69975.75 | 10-OCT-05:10 |
Heating:EnergyTransfer | 208.49 | 0.00 | 15-JAN-16:00 | 371227.03 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 2.70 | 0.00 | 01-JAN-00:10 | 13608.43 | 22-JUL-16:10 |
General:Heating:EnergyTransfer | 208.49 | 0.00 | 15-JAN-16:00 | 371227.03 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 2.70 | 0.00 | 01-JAN-00:10 | 13608.43 | 22-JUL-16:10 |
Cooling:EnergyTransfer | 16721.36 | 87600.52 | 15-JAN-08:40 | 1445466.07 | 14-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 625.85 | 0.00 | 01-JAN-00:10 | 69975.75 | 10-OCT-05:10 |
General:Cooling:EnergyTransfer | 16721.36 | 87600.52 | 15-JAN-08:40 | 1445466.07 | 14-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 625.85 | 0.00 | 01-JAN-00:10 | 69975.75 | 10-OCT-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 575.65 | 0.00 | 01-JAN-00:10 | 49677.33 | 24-APR-09:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 575.65 | 0.00 | 01-JAN-00:10 | 49677.33 | 24-APR-09:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 575.65 | 0.00 | 01-JAN-00:10 | 49677.33 | 24-APR-09:10 |
EnergyTransfer:Zone:CORE_MID | 3982.68 | 0.00 | 01-JAN-00:10 | 405506.07 | 17-JUN-05:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 3982.68 | 0.00 | 01-JAN-00:10 | 405506.07 | 17-JUN-05:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 3982.68 | 0.00 | 01-JAN-00:10 | 405506.07 | 17-JUN-05:10 |
EnergyTransfer:Zone:CORE_TOP | 335.99 | 0.00 | 01-JAN-00:10 | 62451.27 | 02-JAN-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 5.41 | 0.00 | 01-JAN-00:10 | 62451.27 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 5.41 | 0.00 | 01-JAN-00:10 | 62451.27 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 330.58 | 0.00 | 01-JAN-00:10 | 45329.92 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 330.58 | 0.00 | 01-JAN-00:10 | 45329.92 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.03 | 0.00 | 01-JAN-00:10 | 8046.79 | 10-JUL-15:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 627.94 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 01-JAN-00:10 | 627.94 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.03 | 0.00 | 01-JAN-00:10 | 8046.79 | 10-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 56.03 | 0.00 | 01-JAN-00:10 | 8046.79 | 10-JUL-15:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.15 | 0.00 | 01-JAN-00:10 | 11163.67 | 13-JUN-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 774.26 | 11-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.01 | 0.00 | 01-JAN-00:10 | 774.26 | 11-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.15 | 0.00 | 01-JAN-00:10 | 11163.67 | 13-JUN-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 52.15 | 0.00 | 01-JAN-00:10 | 11163.67 | 13-JUN-08:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 86.23 | 0.00 | 01-JAN-00:10 | 17719.45 | 11-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2621.77 | 10-JAN-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 0.02 | 0.00 | 01-JAN-00:10 | 2621.77 | 10-JAN-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 86.21 | 0.00 | 01-JAN-00:10 | 17719.45 | 11-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 86.21 | 0.00 | 01-JAN-00:10 | 17719.45 | 11-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.49 | 0.00 | 01-JAN-00:10 | 14887.11 | 14-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.49 | 0.00 | 01-JAN-00:10 | 14887.11 | 14-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 81.49 | 0.00 | 01-JAN-00:10 | 14887.11 | 14-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 371.69 | 0.00 | 01-JAN-00:10 | 78412.27 | 26-DEC-06:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.89 | 0.00 | 01-JAN-00:10 | 78412.27 | 26-DEC-06:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 25.89 | 0.00 | 01-JAN-00:10 | 78412.27 | 26-DEC-06:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 345.80 | 0.00 | 01-JAN-00:10 | 68547.95 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 345.80 | 0.00 | 01-JAN-00:10 | 68547.95 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 418.06 | 0.00 | 01-JAN-00:10 | 115426.18 | 13-JUN-08:50 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 16.46 | 0.00 | 01-JAN-00:10 | 53942.92 | 30-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 16.46 | 0.00 | 01-JAN-00:10 | 53942.92 | 30-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 401.59 | 0.00 | 01-JAN-00:10 | 115426.18 | 13-JUN-08:50 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 401.59 | 0.00 | 01-JAN-00:10 | 115426.18 | 13-JUN-08:50 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 725.07 | 0.00 | 01-JAN-00:10 | 187465.54 | 11-SEP-13:10 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.76 | 0.00 | 01-JAN-00:10 | 76922.18 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 13.76 | 0.00 | 01-JAN-00:10 | 76922.18 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 711.32 | 0.00 | 01-JAN-00:10 | 187465.54 | 11-SEP-13:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 711.32 | 0.00 | 01-JAN-00:10 | 187465.54 | 11-SEP-13:10 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 448.09 | 0.00 | 01-JAN-00:10 | 132546.19 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.58 | 0.00 | 01-JAN-00:10 | 49841.92 | 26-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 8.58 | 0.00 | 01-JAN-00:10 | 49841.92 | 26-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 439.52 | 0.00 | 01-JAN-00:10 | 132546.19 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 439.52 | 0.00 | 01-JAN-00:10 | 132546.19 | 13-JUN-17:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 42.38 | 0.00 | 01-JAN-00:10 | 10634.05 | 26-DEC-04:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.83 | 0.00 | 01-JAN-00:10 | 10634.05 | 26-DEC-04:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 15.83 | 0.00 | 01-JAN-00:10 | 10634.05 | 26-DEC-04:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.55 | 0.00 | 01-JAN-00:10 | 7704.33 | 13-JUN-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 26.55 | 0.00 | 01-JAN-00:10 | 7704.33 | 13-JUN-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 42.43 | 0.00 | 01-JAN-00:10 | 11511.78 | 13-JUN-09:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.13 | 0.00 | 01-JAN-00:10 | 10971.18 | 26-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 9.13 | 0.00 | 01-JAN-00:10 | 10971.18 | 26-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.30 | 0.00 | 01-JAN-00:10 | 11511.78 | 13-JUN-09:10 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 33.30 | 0.00 | 01-JAN-00:10 | 11511.78 | 13-JUN-09:10 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 69.78 | 0.00 | 01-JAN-00:10 | 18938.74 | 11-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.26 | 0.00 | 01-JAN-00:10 | 15637.75 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 10.26 | 0.00 | 01-JAN-00:10 | 15637.75 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 59.52 | 0.00 | 01-JAN-00:10 | 18938.74 | 11-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 59.52 | 0.00 | 01-JAN-00:10 | 18938.74 | 11-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 43.44 | 0.00 | 01-JAN-00:10 | 13927.10 | 13-JUN-17:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.91 | 0.00 | 01-JAN-00:10 | 9625.01 | 02-JAN-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 5.91 | 0.00 | 01-JAN-00:10 | 9625.01 | 02-JAN-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.53 | 0.00 | 01-JAN-00:10 | 13927.10 | 13-JUN-17:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 37.53 | 0.00 | 01-JAN-00:10 | 13927.10 | 13-JUN-17:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 44.34 | 0.00 | 01-JAN-00:10 | 7146.98 | 24-JUL-15:20 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.30 | 0.00 | 01-JAN-00:10 | 3942.15 | 05-NOV-13:10 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 1.30 | 0.00 | 01-JAN-00:10 | 3942.15 | 05-NOV-13:10 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 43.04 | 0.00 | 01-JAN-00:10 | 7146.98 | 24-JUL-15:20 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 43.04 | 0.00 | 01-JAN-00:10 | 7146.98 | 24-JUL-15:20 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 286.38 | 0.00 | 01-JAN-00:10 | 50710.43 | 24-JUL-15:50 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 58.08 | 0.00 | 01-JAN-00:10 | 42717.71 | 26-DEC-14:30 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 58.08 | 0.00 | 01-JAN-00:10 | 42717.71 | 26-DEC-14:30 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 228.30 | 0.00 | 01-JAN-00:10 | 50710.43 | 24-JUL-15:50 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 228.30 | 0.00 | 01-JAN-00:10 | 50710.43 | 24-JUL-15:50 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 64.67 | 0.00 | 01-JAN-00:10 | 17754.99 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.97 | 0.00 | 01-JAN-00:10 | 17754.99 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 33.97 | 0.00 | 01-JAN-00:10 | 17754.99 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.70 | 0.00 | 01-JAN-00:10 | 15858.88 | 13-JUN-14:20 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 30.70 | 0.00 | 01-JAN-00:10 | 15858.88 | 13-JUN-14:20 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.45 | 775.25 | 14-JAN-18:30 | 8117.18 | 30-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.45 | 775.25 | 14-JAN-18:30 | 8117.18 | 30-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 137.45 | 775.25 | 14-JAN-18:30 | 8117.18 | 30-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1174.68 | 6.00 | 01-JAN-16:40 | 77247.60 | 30-APR-18:00 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.51 | 0.00 | 01-JAN-15:40 | 4656.61 | 01-JAN-08:40 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 0.51 | 0.00 | 01-JAN-15:40 | 4656.61 | 01-JAN-08:40 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1174.17 | 0.00 | 01-JAN-00:10 | 77247.60 | 30-APR-18:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1174.17 | 0.00 | 01-JAN-00:10 | 77247.60 | 30-APR-18:00 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 104.49 | 0.30 | 11-JAN-21:00 | 7835.99 | 30-APR-18:10 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.67 | 0.00 | 02-JAN-14:30 | 570.92 | 10-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.67 | 0.00 | 02-JAN-14:30 | 570.92 | 10-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.82 | 0.00 | 01-JAN-00:10 | 7835.99 | 30-APR-18:10 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 103.82 | 0.00 | 01-JAN-00:10 | 7835.99 | 30-APR-18:10 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.10 | 86618.60 | 15-JAN-06:00 | 367772.27 | 15-AUG-16:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.10 | 86618.60 | 15-JAN-06:00 | 367772.27 | 15-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7158.10 | 86618.60 | 15-JAN-06:00 | 367772.27 | 15-AUG-16:00 |
PlantLoopHeatingDemand:Facility | 1306.21 | 0.00 | 01-JAN-00:10 | 623386.73 | 10-JAN-08:00 |
PlantLoopHeatingDemand:Plant | 442.36 | 0.00 | 01-JAN-00:10 | 51545.26 | 13-FEB-12:20 |
WaterSystems:PlantLoopHeatingDemand | 442.36 | 0.00 | 01-JAN-00:10 | 51545.26 | 13-FEB-12:20 |
General:WaterSystems:PlantLoopHeatingDemand | 442.36 | 0.00 | 01-JAN-00:10 | 51545.26 | 13-FEB-12:20 |
EnergyTransfer:HVAC | 11739.77 | 124435.97 | 28-JAN-17:10 | 1678467.22 | 14-AUG-15:50 |
HeatingCoils:EnergyTransfer | 863.84 | 0.00 | 01-JAN-00:10 | 606461.86 | 10-JAN-08:00 |
PlantLoopHeatingDemand:HVAC | 863.84 | 0.00 | 01-JAN-00:10 | 606461.86 | 10-JAN-08:00 |
HeatingCoils:PlantLoopHeatingDemand | 863.84 | 0.00 | 01-JAN-00:10 | 606461.86 | 10-JAN-08:00 |
CoolingCoils:EnergyTransfer | 10875.93 | 110778.79 | 10-JAN-08:00 | 1678467.22 | 14-AUG-15:50 |
EnergyTransfer:Plant | 4856.58 | 0.00 | 01-JAN-00:10 | 4285071.42 | 13-JUN-16:00 |
LoopToLoop:EnergyTransfer | 1175.70 | -3189.57 | 20-APR-15:30 | 1348018.96 | 13-JUN-16:00 |
WaterSystems:EnergyTransfer | 442.36 | 0.00 | 01-JAN-00:10 | 51545.26 | 13-FEB-12:20 |
WaterUse:WaterSystems:EnergyTransfer | 442.36 | 0.00 | 01-JAN-00:10 | 51545.26 | 13-FEB-12:20 |
Boilers:EnergyTransfer | 859.56 | 0.00 | 01-JAN-00:10 | 605234.85 | 10-JAN-08:00 |
Chillers:EnergyTransfer | 1107.45 | 0.00 | 01-JAN-00:10 | 1355945.39 | 13-JUN-16:00 |
HeatRejection:EnergyTransfer | 1271.51 | 0.00 | 01-JAN-00:10 | 1544379.85 | 13-JUN-16:00 |
General:HeatRejection:EnergyTransfer | 1271.51 | 0.00 | 01-JAN-00:10 | 1544379.85 | 13-JUN-16:00 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 2.698 | -625.848 | 0.000 | 0.000 | 92.743 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -71.732 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -575.651 | 0.000 | 0.000 | 83.431 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 11.310 | 0.000 | 0.000 | 0.000 | 0.000 | -0.004 |
CORE_MID | 0.000 | 0.000 | 0.000 | -3982.676 | 0.000 | 0.000 | 844.524 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1670.939 |
CORE_TOP | 0.000 | 0.000 | 5.406 | -330.578 | 0.000 | 0.000 | 88.504 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -244.241 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.001 | -56.030 | 0.000 | 0.000 | 10.768 | 14.071 | 40.342 | 17.002 | 0.000 | 0.002 | 31.544 | 0.000 | -53.401 | 0.000 | -4.300 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.005 | -52.148 | 0.000 | 0.000 | 7.030 | 9.014 | 25.998 | 39.651 | 0.000 | 0.001 | 6.586 | 0.000 | -33.305 | 0.000 | -2.833 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 0.023 | -86.208 | 0.000 | 0.000 | 10.851 | 13.941 | 40.343 | 80.025 | 0.000 | 0.002 | 0.000 | 0.000 | -50.500 | 0.000 | -4.286 | -4.191 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.000 | -81.494 | 0.000 | 0.000 | 6.824 | 9.041 | 25.998 | 37.793 | 0.000 | 0.001 | 43.511 | 0.000 | -38.532 | 0.000 | -3.140 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 25.890 | -345.806 | 0.000 | 0.000 | 113.937 | 140.881 | 403.423 | 179.844 | 0.000 | 0.037 | 48.495 | 0.000 | -476.677 | 0.000 | -90.025 | -0.017 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 16.464 | -401.598 | 0.000 | 0.000 | 53.853 | 90.170 | 259.981 | 399.588 | 0.000 | 0.025 | 0.016 | 0.000 | -307.974 | 0.000 | -61.603 | -48.906 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 13.755 | -711.316 | 0.000 | 0.000 | 111.332 | 139.521 | 403.429 | 801.923 | 0.000 | 0.037 | 0.002 | 0.000 | -483.325 | 0.000 | -95.395 | -179.962 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 8.579 | -439.513 | 0.000 | 0.000 | 73.294 | 90.449 | 259.979 | 389.275 | 0.000 | 0.021 | 11.186 | 0.000 | -329.761 | 0.000 | -63.510 | -0.006 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 15.831 | -26.552 | 0.000 | 0.000 | 11.723 | 14.088 | 40.342 | 18.903 | 0.000 | 0.004 | 0.001 | 0.000 | -43.625 | 0.000 | -10.303 | -20.412 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 9.134 | -33.298 | 0.000 | 0.000 | 7.434 | 9.017 | 25.998 | 40.543 | 0.000 | 0.003 | 0.000 | 0.000 | -28.488 | 0.000 | -7.137 | -23.205 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 10.257 | -59.524 | 0.000 | 0.000 | 11.446 | 13.952 | 40.343 | 81.209 | 0.000 | 0.004 | 0.000 | 0.000 | -44.616 | 0.000 | -11.005 | -42.066 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 5.914 | -37.527 | 0.000 | 0.000 | 7.511 | 9.045 | 25.998 | 39.395 | 0.000 | 0.002 | 0.000 | 0.000 | -30.735 | 0.000 | -7.394 | -12.209 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -137.451 | 0.000 | 0.000 | 0.950 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -22.019 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 0.510 | -1174.174 | 0.000 | 0.000 | 9.502 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -421.040 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.672 | -103.821 | 0.000 | 0.000 | 0.952 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -56.322 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7158.098 | 0.000 | 0.000 | 20.565 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -407.440 |
GROUNDFLOOR_PLENUM | 1.298 | -43.041 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 50.827 | 0.000 | 0.000 | 0.000 | -9.086 | 0.000 |
MIDFLOOR_PLENUM | 58.080 | -228.303 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.048 | 324.834 | 0.000 | 0.000 | 0.000 | -154.659 | -0.000 |
TOPFLOOR_PLENUM | 33.975 | -30.695 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.003 | 12.996 | 0.000 | 0.000 | 0.000 | -16.279 | -0.005 |
Total Facility | 93.353 | -302.039 | 115.141 | -16419.311 | 0.000 | 0.000 | 1567.173 | 2752.218 | 15213.411 | 2125.151 | 0.000 | 0.193 | 541.308 | 0.000 | -1920.941 | 0.000 | -540.954 | -3224.715 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 30-MAY-03:02 | 0.00 | 0.00 | 0.00 | -107758.16 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 93438.39 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 10-OCT-03:02 | 0.00 | 0.00 | 0.00 | -89596.02 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 80764.53 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 05-JUL-04:03 | 0.00 | 0.00 | 0.00 | -763545.97 | 0.00 | 0.00 | 0.00 | 15486.81 | 80571.20 | 0.00 | 0.00 | 0.00 | 667487.96 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 14-JUN-05:02 | 0.00 | 0.00 | 0.00 | -72427.97 | 0.00 | 0.00 | 839.26 | 1548.68 | 8057.12 | 0.00 | 0.00 | 0.00 | 61982.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 26-JUN-05:03 | 0.00 | 0.00 | 0.00 | -10489.38 | 0.00 | 0.00 | 108.34 | 119.45 | 1011.70 | 2519.86 | 0.00 | 0.00 | 6801.95 | 0.00 | -0.00 | 0.00 | -71.91 | 0.00 |
PERIMETER_BOT_ZN_2 | 20-AUG-08:52 | 0.00 | 0.00 | 0.00 | -18787.02 | 0.00 | 0.00 | 24.23 | 38.49 | 488.98 | 13859.01 | 0.00 | 0.00 | 4506.96 | 0.00 | -0.00 | 0.00 | -130.66 | 0.00 |
PERIMETER_BOT_ZN_1 | 30-APR-13:02 | 0.00 | 0.00 | 0.00 | -28122.63 | 0.00 | 0.00 | 34.58 | 59.73 | 758.78 | 20522.16 | 0.00 | 0.00 | 6859.42 | 0.00 | -0.00 | 0.00 | -112.05 | 0.00 |
PERIMETER_BOT_ZN_4 | 25-JUN-17:11 | 0.00 | 0.00 | 0.00 | -25359.76 | 0.00 | 0.00 | 0.00 | 38.49 | 488.98 | 13994.54 | 0.00 | 0.00 | 10886.48 | 0.00 | -0.00 | 0.00 | -48.72 | 0.00 |
PERIMETER_MID_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -68539.24 | 0.00 | 0.00 | 11143.95 | 10750.25 | 22763.18 | 37144.52 | 0.00 | 402.50 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -13665.16 |
PERIMETER_MID_ZN_2 | 30-APR-09:32 | 0.00 | 0.00 | 0.00 | -195025.68 | 0.00 | 0.00 | 234.31 | 384.90 | 4889.82 | 122646.75 | 0.00 | 0.00 | 70354.16 | 0.00 | -0.00 | 0.00 | -3484.26 | 0.00 |
PERIMETER_MID_ZN_1 | 30-APR-13:32 | 0.00 | 0.00 | 0.00 | -290291.42 | 0.00 | 0.00 | 335.27 | 597.27 | 7587.84 | 189822.17 | 0.00 | 0.00 | 94486.51 | 0.00 | -0.00 | 0.00 | -2537.65 | 0.00 |
PERIMETER_MID_ZN_4 | 11-JUN-16:42 | 0.00 | 0.00 | 0.00 | -213849.00 | 0.00 | 0.00 | 225.02 | 384.90 | 4889.79 | 147205.51 | 0.00 | 0.00 | 65885.86 | 0.00 | -0.00 | 0.00 | -4742.07 | 0.00 |
PERIMETER_TOP_ZN_3 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | -7703.36 | 0.00 | 0.00 | 1114.39 | 1075.02 | 2276.32 | 3673.81 | 0.00 | 47.70 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -483.89 |
PERIMETER_TOP_ZN_2 | 23-JUL-09:32 | 0.00 | 0.00 | 0.00 | -18601.12 | 0.00 | 0.00 | 21.84 | 38.49 | 488.98 | 11953.47 | 0.00 | 0.00 | 6320.20 | 0.00 | -0.00 | 0.00 | -221.87 | 0.00 |
PERIMETER_TOP_ZN_1 | 10-SEP-14:22 | 0.00 | 0.00 | 0.00 | -28899.01 | 0.00 | 0.00 | 36.82 | 59.73 | 758.78 | 15321.38 | 0.00 | 0.00 | 13285.70 | 0.00 | -0.00 | 0.00 | -563.41 | 0.00 |
PERIMETER_TOP_ZN_4 | 09-JUL-17:11 | 0.00 | 0.00 | 0.00 | -23269.94 | 0.00 | 0.00 | 0.00 | 38.49 | 488.98 | 15633.42 | 0.00 | 0.00 | 7459.82 | 0.00 | -0.00 | 0.00 | -350.77 | 0.00 |
DATACENTER_BOT_ZN_6 | 30-APR-17:54 | 0.00 | 0.00 | 0.00 | -8121.94 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 305.02 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 30-APR-17:54 | 0.00 | 0.00 | 0.00 | -77254.24 | 0.00 | 0.00 | 0.00 | 225.07 | 77944.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -915.05 |
DATACENTER_TOP_ZN_6 | 30-APR-18:03 | 0.00 | 0.00 | 0.00 | -7836.61 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 19.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 30-APR-19:43 | 0.00 | 0.00 | 0.00 | -368981.09 | 0.00 | 0.00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -10894.54 |
GROUNDFLOOR_PLENUM | 17-JUL-05:13 | 0.00 | -8725.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8801.29 | 0.00 | -0.00 | 0.00 | -76.23 | 0.00 |
MIDFLOOR_PLENUM | 25-JUL-05:13 | 0.00 | -56202.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57824.23 | 0.00 | -0.00 | 0.00 | -1622.06 | 0.00 |
TOPFLOOR_PLENUM | 13-JUN-14:20 | 0.00 | -15858.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15873.99 | 0.00 | -0.00 | 0.00 | -15.06 | 0.00 |
Total Facility | 15-AUG-05:03 | 0.00 | 19205.90 | 0.00 | -1636540.72 | 0.00 | 0.00 | 16154.94 | 29009.37 | 623236.89 | 0.00 | 0.00 | 0.00 | 1021803.96 | 0.00 | -72032.68 | 0.00 | -837.66 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 22-JUL-16:01 | 0.00 | 0.00 | 14851.07 | 0.00 | 0.00 | 0.00 | 520.13 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -29690.96 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 02-JAN-04:11 | 0.00 | 0.00 | 69389.25 | 0.00 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -78220.71 |
PERIMETER_BOT_ZN_3 | 11-JAN-06:01 | 0.00 | 0.00 | 4633.65 | 0.00 | 0.00 | 0.00 | 140.72 | 194.45 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3843.08 | 0.00 | -108.10 | -2029.35 |
PERIMETER_BOT_ZN_2 | 11-JAN-06:01 | 0.00 | 0.00 | 3808.09 | 0.00 | 0.00 | 0.00 | 91.63 | 125.31 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2593.74 | 0.00 | -71.56 | -2011.71 |
PERIMETER_BOT_ZN_1 | 10-JAN-06:01 | 0.00 | 0.00 | 8148.19 | 0.00 | 0.00 | 0.00 | 144.67 | 194.46 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4058.84 | 0.00 | -139.40 | -5300.79 |
PERIMETER_BOT_ZN_4 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 26-DEC-04:01 | 0.00 | 0.00 | 93355.03 | 0.00 | 0.00 | 0.00 | 0.00 | 972.26 | 10116.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -33352.58 | 0.00 | -16039.13 | -55052.55 |
PERIMETER_MID_ZN_2 | 26-DEC-04:01 | 0.00 | 0.00 | 119226.49 | 0.00 | 0.00 | 0.00 | 0.00 | 626.56 | 6519.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -22329.70 | 0.00 | -10985.22 | -93057.89 |
PERIMETER_MID_ZN_1 | 26-DEC-05:01 | 0.00 | 0.00 | 167902.87 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.57 | 10117.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -28449.82 | 0.00 | -12192.19 | -139322.54 |
PERIMETER_MID_ZN_4 | 26-DEC-05:01 | 0.00 | 0.00 | 109032.91 | 0.00 | 0.00 | 0.00 | 0.00 | 1253.13 | 6519.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -18945.55 | 0.00 | -8130.14 | -89730.06 |
PERIMETER_TOP_ZN_3 | 26-DEC-03:53 | 0.00 | 0.00 | 11398.83 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2749.32 | 0.00 | -1828.54 | -7929.88 |
PERIMETER_TOP_ZN_2 | 02-JAN-04:11 | 0.00 | 0.00 | 15260.50 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1449.80 | 0.00 | -45.28 | -14480.05 |
PERIMETER_TOP_ZN_1 | 02-JAN-04:11 | 0.00 | 0.00 | 22888.78 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2237.91 | 0.00 | -68.76 | -21691.05 |
PERIMETER_TOP_ZN_4 | 02-JAN-04:11 | 0.00 | 0.00 | 15645.70 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1506.32 | 0.00 | -45.94 | -14808.06 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-08:35 | 0.00 | 0.00 | 4656.63 | 0.00 | 0.00 | 0.00 | 53.08 | 225.07 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24420.83 |
DATACENTER_TOP_ZN_6 | 10-JAN-00:10 | 0.00 | 0.00 | 570.92 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2542.03 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-04:01 | 13607.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1959.44 | -11648.30 |
MIDFLOOR_PLENUM | 30-APR-14:51 | 82541.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -483.25 | -82058.61 |
TOPFLOOR_PLENUM | 09-JAN-05:13 | 19784.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19784.34 |
Total Facility | 18-DEC-05:01 | -781295.06 | 771682.70 | 600085.52 | -771682.70 | 0.00 | 0.00 | 0.00 | 29009.37 | 623236.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -121400.16 | 0.00 | -47881.10 | -301755.45 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 10.2467 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.8115 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 96.8672 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 80.8021 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 9.6218 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 8.7439 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.2829 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.2829 | 0.2272 | 1.0000 | Not calculated | 1.2002 | 0.2272 | ||
AIRLOOP DATACENTER BASEMENT | 21.5080 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5081 | 0.0157 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4970 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4970 | 0.0315 | 1.0000 | Not calculated | 0.0156 | 0.0315 | ||
AIRLOOP DATACENTER MID | 4.7514 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7514 | 0.0329 | 1.0000 | Not calculated | 0.1563 | 0.0329 | ||
AIRLOOP DATACENTER TOP | 0.4820 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4820 | 0.0324 | 1.0000 | Not calculated | 0.0156 | 0.0324 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 5.1234 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.9014 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 48.4336 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 28.2236 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 4.8109 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 2.8975 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 5.2829 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 5.2829 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.2272 | ||
AIRLOOP DATACENTER BASEMENT | 21.5080 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 21.5080 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0157 | ||
AIRLOOP DATACENTER BOT | 0.4970 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4970 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0315 | ||
AIRLOOP DATACENTER MID | 4.7514 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 4.7514 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0329 | ||
AIRLOOP DATACENTER TOP | 0.4820 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.4820 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0324 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2829 | 5.2829 | 5.2829 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.5698 | 5.5698 | 1.8826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 52.0546 | 52.0546 | 18.3232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 4.9393 | 4.9393 | 1.8769 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7654 | 0.7654 | 0.2365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0656 | 1.0656 | 0.2131 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5217 | 1.5217 | 0.3043 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3242 | 1.3242 | 0.2648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.7964 | 6.7964 | 2.2972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.9619 | 10.9619 | 2.1924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.4102 | 15.4102 | 3.0820 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 11.6441 | 11.6441 | 2.3288 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7578 | 0.7578 | 0.2357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.0767 | 1.0767 | 0.2153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6239 | 1.6239 | 0.3248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2240 | 1.2240 | 0.2448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4970 | 0.4970 | 0.4970 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7514 | 4.7514 | 4.7514 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4820 | 0.4820 | 0.4820 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5080 | 21.5080 | 21.5080 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 10.2467 | 8.8115 | 10.2467 | 2.9014 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 96.8672 | 80.8021 | 96.8672 | 28.2236 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 9.6218 | 8.7439 | 9.6218 | 2.8975 | 0.0000 | 1.0000 |
CAV_BAS | 5.2829 | 5.2829 | 5.2829 | 5.2829 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5080 | 21.5081 | 21.5080 | 21.5080 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4970 | 0.4970 | 0.4970 | 0.4970 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7514 | 4.7514 | 4.7514 | 4.7514 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4820 | 0.4820 | 0.4820 | 0.4820 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.2829 | 5.2829 | 5.2829 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.7849 | 2.7849 | 1.8826 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 26.0273 | 26.0273 | 18.3232 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 2.4696 | 2.4696 | 1.8769 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3827 | 0.3827 | 0.2365 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5328 | 0.5328 | 0.2131 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7608 | 0.7608 | 0.3043 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6621 | 0.6621 | 0.2648 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.3982 | 3.3982 | 2.2972 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.4810 | 5.4810 | 2.1924 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7051 | 7.7051 | 3.0820 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.8221 | 5.8221 | 2.3288 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.3789 | 0.3789 | 0.2357 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5383 | 0.5383 | 0.2153 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8120 | 0.8120 | 0.3248 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6120 | 0.6120 | 0.2448 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4970 | 0.4970 | 0.4970 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 4.7514 | 4.7514 | 4.7514 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.4820 | 0.4820 | 0.4820 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 21.5080 | 21.5080 | 21.5080 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 5.1234 | 2.9014 | 2.9014 | 2.9014 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 48.4336 | 28.2236 | 28.2236 | 28.2236 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 4.8109 | 2.8975 | 2.8975 | 2.8975 | 0.0000 | 1.0000 |
CAV_BAS | 5.2829 | 5.2829 | 5.2829 | 5.2829 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 21.5080 | 21.5080 | 21.5080 | 21.5080 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.4970 | 0.4970 | 0.4970 | 0.4970 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 4.7514 | 4.7514 | 4.7514 | 4.7514 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.4820 | 0.4820 | 0.4820 | 0.4820 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 23.17 |
Number of hours cooling loads not met | 89.00 |
Number of hours not met | 112.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1183.57 | 725897.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 2435.98 | 314554.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2752.22 | 261074.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 449.08 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3726.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2190.10 | 216449.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 248.73 | 48432.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 726.26 | 76172.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 5.10 | 5914.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 745.44 | 82180.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 25935.27 |
Natural Gas | 0.00 | 1929.01 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 27864.27 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.42 |
Space Heating | 0.00 |
Space Cooling | 52.59 |
Fans (All) | 47.28 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 559.91 |
Subtotal | 559.91 |
Natural Gas [MJ/m2] | |
Space Heating | 25.55 |
Service Water Heating | 16.09 |
Miscellaneous (All) | 41.64 |
Subtotal | 41.64 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 9.88 |
Space Heating | 4.25 |
Space Cooling | 8.74 |
Fans (All) | 7.86 |
Service Water Heating | 2.68 |
Receptacle Equipment | 54.60 |
Miscellaneous | 12.00 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8546.83 | 213.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8738.17 | 21.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8556.83 | 203.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8738.00 | 22.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8745.17 | 14.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8742.33 | 17.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8733.83 | 26.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 7838.33 | 921.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 7785.33 | 974.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 7764.00 | 996.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8119.33 | 640.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8753.67 | 6.33 | 0.00 | 0.00 | 0.00 |
Min | 7764.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 996.00 | 0.00 | 0.00 | 0.00 |
Average | 8579.30 | 180.70 | 0.00 | 0.00 | 0.00 |
Sum | 197323.83 | 4156.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368161.00 | 455.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330741.00 | 72.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 1643.33 | 624.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 1612.00 | 656.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 1592.00 | 676.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85751.33 | 17643.67 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368161.00 | 17643.67 | 0.00 | 0.00 | 0.00 |
Average | 79459.81 | 875.10 | 0.00 | 0.00 | 0.00 |
Sum | 1827575.67 | 20127.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8487.83 | 272.17 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8634.50 | 110.00 | 15.50 | 0.00 | 0.00 |
CORE_MID | 8690.33 | 69.67 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8741.50 | 18.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8722.50 | 37.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8589.67 | 170.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8740.17 | 19.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8728.83 | 31.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8721.33 | 38.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8741.83 | 18.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8734.00 | 26.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8727.17 | 32.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8587.50 | 172.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8568.83 | 191.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8564.17 | 195.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 8696.83 | 63.17 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8736.83 | 23.17 | 0.00 | 0.00 | 0.00 |
Min | 8487.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 272.17 | 15.50 | 0.00 | 0.00 |
Average | 8693.49 | 65.84 | 0.67 | 0.00 | 0.00 |
Sum | 199950.17 | 1514.33 | 15.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 367885.67 | 730.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330620.50 | 141.50 | 51.00 | 0.00 | 0.00 |
CORE_MID | 330716.00 | 97.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330804.00 | 9.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2129.83 | 138.17 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2116.17 | 151.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2113.33 | 154.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 101716.17 | 1678.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 367885.67 | 1678.83 | 51.00 | 0.00 | 0.00 |
Average | 80197.86 | 134.84 | 2.22 | 0.00 | 0.00 |
Sum | 1844550.67 | 3101.33 | 51.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:36
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.460782E+11 | 104733.76 | 02-JAN-04:11 | 1.13 | 0.68 | 0.565763E+10 | 7499.19 | 10-JAN-10:09 | -2.8 | -3.5 |
February | 0.424561E+11 | 105038.43 | 21-FEB-04:01 | 5.93 | 5.00 | 0.513364E+10 | 7499.16 | 17-FEB-10:09 | 5.93 | 5.00 |
March | 0.520764E+11 | 101816.09 | 13-MAR-03:02 | 2.37 | 1.75 | 0.612915E+10 | 7499.13 | 28-MAR-13:20 | 10.33 | 6.95 |
April | 0.527773E+11 | 104724.34 | 24-APR-03:02 | 7.00 | 5.63 | 0.544856E+10 | 7499.29 | 25-APR-13:20 | 13.33 | 9.08 |
May | 0.528863E+11 | 107759.15 | 30-MAY-03:02 | 8.00 | 7.45 | 0.589826E+10 | 7499.06 | 16-MAY-13:20 | 8.00 | 7.45 |
June | 0.550669E+11 | 102801.57 | 12-JUN-03:02 | 8.83 | 8.83 | 0.587960E+10 | 7499.33 | 08-JUN-13:20 | 8.83 | 8.83 |
July | 0.560981E+11 | 105638.78 | 31-JUL-03:02 | 9.00 | 6.51 | 0.547100E+10 | 7499.10 | 18-JUL-13:20 | 9.00 | 6.51 |
August | 0.616680E+11 | 102424.20 | 14-AUG-03:02 | 10.00 | 9.41 | 0.613536E+10 | 7499.40 | 08-AUG-13:09 | 10.00 | 9.41 |
September | 0.533724E+11 | 102004.42 | 25-SEP-03:02 | 11.00 | 9.41 | 0.544926E+10 | 7499.31 | 06-SEP-09:20 | 11.00 | 9.41 |
October | 0.533692E+11 | 101099.59 | 16-OCT-03:03 | 8.17 | 8.08 | 0.566653E+10 | 7499.31 | 17-OCT-09:20 | 11.67 | 11.31 |
November | 0.511349E+11 | 104418.00 | 27-NOV-04:01 | 4.83 | 4.00 | 0.561051E+10 | 7499.12 | 10-NOV-10:20 | 4.83 | 4.00 |
December | 0.488634E+11 | 103567.98 | 04-DEC-04:01 | 1.33 | 0.37 | 0.546459E+10 | 7499.11 | 20-DEC-10:20 | 8.33 | 7.62 |
Annual Sum or Average | 0.625847E+12 | 0.679441E+11 | ||||||||
Minimum of Months | 0.424561E+11 | 101099.59 | 1.13 | 0.37 | 0.513364E+10 | 7499.06 | -2.8 | -3.5 | ||
Maximum of Months | 0.616680E+11 | 107759.15 | 11.00 | 9.41 | 0.613536E+10 | 7499.40 | 13.33 | 11.31 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.363607E+11 | 83191.35 | 02-JAN-05:01 | 1.00 | 0.59 | 0.505638E+10 | 6734.78 | 20-JAN-10:09 | 4.33 | 3.91 |
February | 0.357017E+11 | 82921.96 | 21-FEB-05:01 | 5.48 | 4.76 | 0.459693E+10 | 6734.78 | 17-FEB-10:09 | 5.48 | 4.76 |
March | 0.465947E+11 | 82729.30 | 13-MAR-03:02 | 2.37 | 1.75 | 0.549947E+10 | 6734.77 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.537337E+11 | 88905.95 | 24-APR-03:02 | 7.00 | 5.63 | 0.488493E+10 | 6735.04 | 14-APR-13:00 | 7.00 | 5.63 |
May | 0.482071E+11 | 86273.25 | 30-MAY-03:02 | 8.00 | 7.45 | 0.528538E+10 | 6734.73 | 22-MAY-13:00 | 8.00 | 7.45 |
June | 0.540057E+11 | 85810.24 | 05-JUN-03:02 | 11.17 | 11.17 | 0.527061E+10 | 6734.96 | 08-JUN-13:09 | 13.50 | 10.04 |
July | 0.583327E+11 | 88634.51 | 05-JUL-03:02 | 8.00 | 6.98 | 0.489814E+10 | 6734.84 | 03-JUL-09:09 | 8.00 | 6.98 |
August | 0.657710E+11 | 84335.06 | 31-AUG-03:02 | 12.00 | 11.55 | 0.549855E+10 | 6734.92 | 08-AUG-09:00 | 12.00 | 11.55 |
September | 0.480652E+11 | 86210.24 | 05-SEP-03:02 | 8.67 | 7.28 | 0.487906E+10 | 6734.97 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.447618E+11 | 89593.67 | 10-OCT-03:02 | 10.83 | 10.83 | 0.507974E+10 | 6734.94 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.428725E+11 | 86398.12 | 13-NOV-04:03 | 5.50 | 5.09 | 0.502991E+10 | 6734.75 | 10-NOV-10:20 | 5.50 | 5.09 |
December | 0.412436E+11 | 85070.05 | 26-DEC-04:01 | 2.00 | 0.68 | 0.489853E+10 | 6734.81 | 04-DEC-14:00 | 2.00 | 0.68 |
Annual Sum or Average | 0.575650E+12 | 0.608776E+11 | ||||||||
Minimum of Months | 0.357017E+11 | 82729.30 | 1.00 | 0.59 | 0.459693E+10 | 6734.73 | 2.00 | 0.68 | ||
Maximum of Months | 0.657710E+11 | 89593.67 | 12.00 | 11.55 | 0.549947E+10 | 6735.04 | 13.50 | 11.88 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.250350E+11 | 67017.15 | 26-JAN-06:02 | 5.00 | 4.51 | 0.485023E+10 | 6734.77 | 20-JAN-10:39 | 5.00 | 4.51 |
February | 0.237831E+11 | 48720.58 | 10-FEB-06:03 | 5.00 | 4.51 | 0.447309E+10 | 6734.78 | 17-FEB-10:39 | 5.00 | 3.80 |
March | 0.298572E+11 | 68650.33 | 24-MAR-05:03 | 4.00 | 3.12 | 0.540210E+10 | 6734.72 | 29-MAR-09:09 | 7.17 | 6.35 |
April | 0.349545E+11 | 76109.15 | 22-APR-05:02 | 6.17 | 5.51 | 0.485315E+10 | 6734.95 | 14-APR-13:00 | 6.17 | 5.51 |
May | 0.376911E+11 | 75977.17 | 03-MAY-05:02 | 3.50 | 2.98 | 0.525697E+10 | 6734.70 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.413021E+11 | 76191.21 | 17-JUN-05:02 | 11.17 | 11.08 | 0.525654E+10 | 6734.91 | 08-JUN-13:09 | 11.17 | 11.08 |
July | 0.412588E+11 | 76376.64 | 05-JUL-04:03 | 7.83 | 6.89 | 0.488432E+10 | 6734.78 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.450418E+11 | 75397.87 | 17-AUG-04:03 | 13.08 | 12.78 | 0.548598E+10 | 6734.86 | 08-AUG-09:00 | 13.08 | 12.78 |
September | 0.383966E+11 | 76111.35 | 21-SEP-05:02 | 5.83 | 4.97 | 0.486007E+10 | 6734.89 | 06-SEP-09:09 | 5.83 | 4.97 |
October | 0.311399E+11 | 74545.89 | 05-OCT-05:02 | 4.00 | 4.00 | 0.501839E+10 | 6734.86 | 17-OCT-09:09 | 12.33 | 11.88 |
November | 0.261541E+11 | 68184.94 | 09-NOV-06:02 | 9.00 | 9.00 | 0.490263E+10 | 6734.73 | 10-NOV-10:20 | 11.00 | 9.41 |
December | 0.236542E+11 | 24776.25 | 22-DEC-17:00 | 5.00 | 4.08 | 0.461261E+10 | 6734.57 | 21-DEC-14:09 | 5.00 | 4.08 |
Annual Sum or Average | 0.398268E+12 | 0.598561E+11 | ||||||||
Minimum of Months | 0.236542E+11 | 24776.25 | 3.50 | 2.98 | 0.447309E+10 | 6734.57 | 5.00 | 3.80 | ||
Maximum of Months | 0.450418E+11 | 76376.64 | 13.08 | 12.78 | 0.548598E+10 | 6734.95 | 23.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.177941E+11 | 18816.23 | 19-JAN-17:00 | 6.00 | 6.00 | 0.417417E+10 | 6511.57 | 20-JAN-14:00 | 8.00 | 6.49 |
February | 0.174495E+11 | 18648.18 | 09-FEB-17:00 | 6.00 | 4.60 | 0.387366E+10 | 6418.25 | 24-FEB-14:00 | 6.00 | 4.60 |
March | 0.227125E+11 | 21643.40 | 31-MAR-16:00 | 9.00 | 4.96 | 0.480244E+10 | 6608.23 | 31-MAR-13:00 | 9.00 | 4.96 |
April | 0.288543E+11 | 61971.44 | 21-APR-05:03 | 8.00 | 6.97 | 0.468383E+10 | 6734.91 | 14-APR-13:00 | 8.00 | 6.97 |
May | 0.321938E+11 | 66277.79 | 24-MAY-05:02 | 8.42 | 8.35 | 0.512953E+10 | 6734.69 | 22-MAY-13:00 | 8.42 | 8.35 |
June | 0.385089E+11 | 72431.44 | 14-JUN-05:02 | 12.00 | 12.00 | 0.521597E+10 | 6734.87 | 09-JUN-13:00 | 12.00 | 12.00 |
July | 0.395390E+11 | 72282.71 | 18-JUL-05:02 | 16.00 | 14.13 | 0.485237E+10 | 6734.74 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.419903E+11 | 70386.47 | 17-AUG-05:02 | 13.17 | 13.07 | 0.545370E+10 | 6734.80 | 08-AUG-09:00 | 13.17 | 13.07 |
September | 0.325646E+11 | 67647.32 | 13-SEP-05:03 | 9.33 | 9.25 | 0.477949E+10 | 6734.83 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.231323E+11 | 30514.63 | 05-OCT-16:00 | 16.00 | 9.13 | 0.458906E+10 | 6734.56 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.191037E+11 | 21514.39 | 10-NOV-17:00 | 7.00 | 6.47 | 0.427357E+10 | 6733.35 | 10-NOV-14:00 | 7.00 | 6.47 |
December | 0.167368E+11 | 17755.45 | 21-DEC-17:00 | 6.00 | 5.49 | 0.397668E+10 | 6292.46 | 21-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.330580E+12 | 0.558045E+11 | ||||||||
Minimum of Months | 0.167368E+11 | 17755.45 | 6.00 | 4.60 | 0.387366E+10 | 6292.46 | 6.00 | 4.60 | ||
Maximum of Months | 0.419903E+11 | 72431.44 | 16.00 | 14.13 | 0.545370E+10 | 6734.91 | 19.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.266563E+10 | 2773.86 | 17-JAN-06:03 | 6.07 | 6.02 | 0.562034E+09 | 835.94 | 19-JAN-14:00 | 9.00 | 7.43 |
February | 0.265258E+10 | 2808.91 | 21-FEB-06:03 | 4.75 | 4.46 | 0.529305E+09 | 845.61 | 21-FEB-14:09 | 9.00 | 7.84 |
March | 0.361925E+10 | 4381.61 | 20-MAR-12:30 | 10.10 | 6.57 | 0.662519E+09 | 845.63 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.525056E+10 | 6384.07 | 28-APR-14:00 | 20.00 | 12.76 | 0.605797E+09 | 845.66 | 14-APR-13:00 | 20.00 | 12.76 |
May | 0.505761E+10 | 6440.29 | 22-MAY-15:00 | 24.00 | 16.08 | 0.655508E+09 | 845.63 | 22-MAY-13:00 | 24.00 | 16.08 |
June | 0.675275E+10 | 10489.78 | 26-JUN-05:03 | 14.33 | 11.96 | 0.659855E+09 | 845.66 | 08-JUN-13:09 | 14.33 | 11.96 |
July | 0.755802E+10 | 10284.88 | 10-JUL-05:02 | 14.50 | 12.63 | 0.613988E+09 | 846.12 | 10-JUL-13:20 | 23.00 | 16.23 |
August | 0.793620E+10 | 7451.54 | 14-AUG-15:50 | 25.83 | 15.90 | 0.688795E+09 | 845.64 | 08-AUG-09:00 | 25.83 | 15.90 |
September | 0.497310E+10 | 5937.61 | 13-SEP-15:10 | 23.00 | 16.22 | 0.605259E+09 | 845.64 | 06-SEP-09:09 | 23.00 | 16.22 |
October | 0.366001E+10 | 5034.58 | 10-OCT-13:10 | 13.00 | 11.87 | 0.617094E+09 | 845.62 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.307641E+10 | 3336.81 | 08-NOV-14:30 | 12.00 | 11.73 | 0.594710E+09 | 845.62 | 24-NOV-14:09 | 12.83 | 11.81 |
December | 0.282810E+10 | 2856.22 | 05-DEC-06:04 | 6.00 | 5.49 | 0.556346E+09 | 830.48 | 21-DEC-14:50 | 8.00 | 6.98 |
Annual Sum or Average | 0.560302E+11 | 0.735121E+10 | ||||||||
Minimum of Months | 0.265258E+10 | 2773.86 | 4.75 | 4.46 | 0.529305E+09 | 830.48 | 8.00 | 6.98 | ||
Maximum of Months | 0.793620E+10 | 10489.78 | 25.83 | 16.22 | 0.688795E+09 | 846.12 | 25.83 | 16.23 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224576E+10 | 3264.56 | 20-JAN-10:15 | 4.67 | 4.23 | 0.353566E+09 | 544.95 | 20-JAN-10:39 | 5.33 | 4.86 |
February | 0.228821E+10 | 4116.01 | 23-FEB-09:30 | 6.00 | 4.18 | 0.331018E+09 | 544.95 | 17-FEB-10:50 | 6.00 | 4.18 |
March | 0.288502E+10 | 3732.96 | 31-MAR-09:25 | 7.00 | 4.34 | 0.408632E+09 | 544.95 | 08-MAR-10:00 | 7.00 | 4.34 |
April | 0.541710E+10 | 18245.59 | 30-APR-07:42 | 17.17 | 12.70 | 0.389712E+09 | 544.98 | 14-APR-13:00 | 17.17 | 12.70 |
May | 0.541558E+10 | 18072.79 | 21-MAY-08:23 | 13.00 | 9.56 | 0.422718E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.626065E+10 | 17123.45 | 25-JUN-09:53 | 18.00 | 12.90 | 0.424463E+09 | 545.44 | 13-JUN-09:09 | 18.00 | 12.90 |
July | 0.683582E+10 | 17504.31 | 23-JUL-08:12 | 19.33 | 15.41 | 0.395313E+09 | 545.49 | 10-JUL-09:20 | 19.33 | 15.41 |
August | 0.731595E+10 | 18787.02 | 20-AUG-08:52 | 17.00 | 13.49 | 0.443021E+09 | 544.97 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.546431E+10 | 18129.89 | 04-SEP-09:02 | 14.08 | 10.77 | 0.391511E+09 | 544.99 | 06-SEP-09:09 | 13.33 | 11.45 |
October | 0.331360E+10 | 6683.61 | 03-OCT-09:00 | 12.00 | 9.31 | 0.387241E+09 | 544.96 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.250191E+10 | 3917.80 | 13-NOV-09:30 | 8.00 | 7.22 | 0.362801E+09 | 544.95 | 13-NOV-10:09 | 8.17 | 7.54 |
December | 0.220390E+10 | 2343.47 | 05-DEC-06:04 | 6.00 | 5.49 | 0.336604E+09 | 544.88 | 26-DEC-10:30 | 3.50 | 1.21 |
Annual Sum or Average | 0.521478E+11 | 0.464660E+10 | ||||||||
Minimum of Months | 0.220390E+10 | 2343.47 | 4.67 | 4.18 | 0.331018E+09 | 544.88 | 3.50 | 1.21 | ||
Maximum of Months | 0.731595E+10 | 18787.02 | 19.33 | 15.41 | 0.443021E+09 | 545.49 | 23.00 | 15.76 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.405452E+10 | 11763.23 | 20-JAN-12:00 | 8.00 | 6.08 | 0.565522E+09 | 845.64 | 20-JAN-10:39 | 8.00 | 6.08 |
February | 0.449124E+10 | 13189.60 | 17-FEB-13:30 | 6.00 | 3.38 | 0.527951E+09 | 845.64 | 17-FEB-10:50 | 6.00 | 3.38 |
March | 0.461353E+10 | 9232.94 | 28-MAR-12:10 | 11.67 | 7.18 | 0.638869E+09 | 845.66 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.914871E+10 | 28116.23 | 30-APR-13:02 | 22.17 | 13.02 | 0.602192E+09 | 846.75 | 28-APR-13:39 | 22.17 | 13.02 |
May | 0.746339E+10 | 13783.44 | 22-MAY-13:10 | 22.17 | 14.96 | 0.648168E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.862565E+10 | 15112.52 | 11-JUN-13:53 | 18.00 | 14.39 | 0.656467E+09 | 845.69 | 08-JUN-13:09 | 18.00 | 14.39 |
July | 0.101893E+11 | 24978.80 | 23-JUL-12:53 | 22.00 | 16.43 | 0.612467E+09 | 845.66 | 18-JUL-13:09 | 22.00 | 16.43 |
August | 0.124120E+11 | 26197.05 | 06-AUG-13:02 | 17.17 | 13.56 | 0.688518E+09 | 846.37 | 29-AUG-13:50 | 17.83 | 13.84 |
September | 0.103097E+11 | 26369.59 | 10-SEP-11:53 | 21.00 | 15.44 | 0.606917E+09 | 846.48 | 27-SEP-13:00 | 22.00 | 13.55 |
October | 0.670512E+10 | 23808.86 | 01-OCT-13:02 | 12.17 | 9.71 | 0.603942E+09 | 846.14 | 03-OCT-13:00 | 14.00 | 9.41 |
November | 0.447845E+10 | 22748.40 | 11-NOV-13:23 | 9.00 | 7.22 | 0.577058E+09 | 845.64 | 17-NOV-14:09 | 8.00 | 6.02 |
December | 0.371643E+10 | 11696.79 | 18-DEC-13:30 | 8.00 | 5.46 | 0.540847E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.862080E+11 | 0.726892E+10 | ||||||||
Minimum of Months | 0.371643E+10 | 9232.94 | 6.00 | 3.38 | 0.527951E+09 | 845.64 | 6.00 | 3.37 | ||
Maximum of Months | 0.124120E+11 | 28116.23 | 22.17 | 16.43 | 0.688518E+09 | 846.75 | 23.00 | 16.43 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326357E+10 | 6251.77 | 30-JAN-16:40 | 7.37 | 6.68 | 0.371157E+09 | 544.95 | 17-JAN-14:00 | 7.37 | 6.68 |
February | 0.379185E+10 | 8530.73 | 27-FEB-16:30 | 8.00 | 6.72 | 0.358149E+09 | 544.95 | 22-FEB-10:30 | 8.00 | 6.72 |
March | 0.527253E+10 | 9234.88 | 23-MAR-16:00 | 10.00 | 6.65 | 0.441549E+09 | 544.96 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.916161E+10 | 23897.35 | 30-APR-16:21 | 24.00 | 12.86 | 0.396065E+09 | 544.99 | 14-APR-13:00 | 24.00 | 12.86 |
May | 0.696323E+10 | 24200.01 | 21-MAY-17:02 | 20.00 | 12.86 | 0.424600E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.940585E+10 | 25387.60 | 25-JUN-17:11 | 21.33 | 16.05 | 0.427091E+09 | 544.98 | 08-JUN-13:09 | 21.33 | 16.05 |
July | 0.111998E+11 | 23829.53 | 09-JUL-16:52 | 21.00 | 15.03 | 0.397690E+09 | 544.96 | 03-JUL-09:09 | 21.00 | 15.03 |
August | 0.123960E+11 | 23614.37 | 20-AUG-16:12 | 23.33 | 14.80 | 0.446169E+09 | 544.97 | 08-AUG-09:00 | 23.33 | 14.80 |
September | 0.659310E+10 | 16473.45 | 24-SEP-16:53 | 21.00 | 15.02 | 0.392780E+09 | 544.97 | 06-SEP-09:09 | 21.00 | 15.02 |
October | 0.501675E+10 | 10793.15 | 13-OCT-05:02 | 10.83 | 9.89 | 0.406125E+09 | 544.96 | 12-OCT-09:09 | 10.83 | 9.89 |
November | 0.434127E+10 | 14339.52 | 09-NOV-06:02 | 9.00 | 9.00 | 0.401052E+09 | 544.96 | 07-NOV-14:09 | 9.00 | 9.00 |
December | 0.408922E+10 | 11677.70 | 05-DEC-06:02 | 6.00 | 5.49 | 0.390516E+09 | 544.96 | 04-DEC-14:00 | 6.00 | 5.49 |
Annual Sum or Average | 0.814947E+11 | 0.485294E+10 | ||||||||
Minimum of Months | 0.326357E+10 | 6251.77 | 6.00 | 5.49 | 0.358149E+09 | 544.95 | 6.00 | 5.49 | ||
Maximum of Months | 0.123960E+11 | 25387.60 | 24.00 | 16.05 | 0.446169E+09 | 544.99 | 24.00 | 16.05 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112223E+10 | 2107.02 | 26-JAN-06:02 | 5.00 | 4.51 | 0.488240E+09 | 741.05 | 19-JAN-14:00 | 5.00 | 4.51 |
February | 0.125753E+10 | 1897.28 | 08-FEB-16:30 | 8.00 | 7.73 | 0.448531E+09 | 721.76 | 22-FEB-14:00 | 9.00 | 6.99 |
March | 0.215988E+10 | 2202.93 | 24-MAR-05:03 | 4.00 | 3.12 | 0.567351E+09 | 799.25 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.308361E+10 | 4798.29 | 28-APR-15:30 | 20.05 | 13.01 | 0.569041E+09 | 845.64 | 14-APR-13:00 | 20.05 | 13.01 |
May | 0.357497E+10 | 5117.92 | 23-MAY-14:00 | 19.00 | 14.77 | 0.626678E+09 | 845.62 | 22-MAY-13:00 | 19.00 | 14.77 |
June | 0.479723E+10 | 6854.79 | 13-JUN-16:00 | 26.50 | 17.70 | 0.651142E+09 | 845.64 | 08-JUN-13:09 | 26.50 | 17.70 |
July | 0.512035E+10 | 6588.12 | 10-JUL-15:00 | 23.00 | 16.69 | 0.607093E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.507759E+10 | 5730.05 | 14-AUG-16:00 | 26.00 | 15.86 | 0.679435E+09 | 845.63 | 08-AUG-09:00 | 26.00 | 15.86 |
September | 0.363481E+10 | 5128.61 | 13-SEP-15:30 | 23.00 | 16.22 | 0.586110E+09 | 845.63 | 19-SEP-13:00 | 14.00 | 14.00 |
October | 0.239723E+10 | 2657.52 | 01-OCT-13:53 | 13.00 | 9.28 | 0.548122E+09 | 841.90 | 11-OCT-13:00 | 16.00 | 10.23 |
November | 0.156153E+10 | 2346.42 | 09-NOV-06:02 | 9.00 | 9.00 | 0.497978E+09 | 766.11 | 10-NOV-14:00 | 12.00 | 8.42 |
December | 0.793478E+09 | 1731.15 | 21-DEC-16:10 | 6.83 | 6.31 | 0.455981E+09 | 681.39 | 22-DEC-14:09 | 7.00 | 5.54 |
Annual Sum or Average | 0.345805E+11 | 0.672570E+10 | ||||||||
Minimum of Months | 0.793478E+09 | 1731.15 | 4.00 | 3.12 | 0.448531E+09 | 681.39 | 5.00 | 4.51 | ||
Maximum of Months | 0.512035E+10 | 6854.79 | 26.50 | 17.70 | 0.679435E+09 | 845.64 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105542E+10 | 2068.06 | 20-JAN-10:00 | 4.00 | 3.60 | 0.228895E+09 | 487.05 | 20-JAN-09:00 | 4.00 | 3.60 |
February | 0.121812E+10 | 2186.37 | 17-FEB-10:00 | 3.00 | 2.16 | 0.213876E+09 | 510.14 | 17-FEB-09:00 | 3.00 | 2.16 |
March | 0.191195E+10 | 2135.43 | 30-MAR-10:40 | 9.67 | 6.89 | 0.262607E+09 | 504.57 | 30-MAR-10:39 | 9.67 | 6.89 |
April | 0.437716E+10 | 19501.95 | 30-APR-09:32 | 19.33 | 12.50 | 0.280134E+09 | 521.32 | 28-APR-07:00 | 19.33 | 12.50 |
May | 0.465182E+10 | 10968.45 | 23-MAY-08:50 | 18.67 | 14.65 | 0.301884E+09 | 521.21 | 22-MAY-14:09 | 18.67 | 14.65 |
June | 0.553474E+10 | 15588.60 | 11-JUN-09:43 | 16.00 | 13.04 | 0.308070E+09 | 521.37 | 13-JUN-08:00 | 21.60 | 15.95 |
July | 0.588327E+10 | 19466.57 | 16-JUL-09:22 | 16.00 | 13.59 | 0.289546E+09 | 521.23 | 10-JUL-10:39 | 16.00 | 13.59 |
August | 0.626368E+10 | 18709.52 | 20-AUG-08:23 | 16.50 | 13.27 | 0.322470E+09 | 521.24 | 14-AUG-07:10 | 16.50 | 13.27 |
September | 0.480742E+10 | 14658.52 | 04-SEP-09:02 | 14.08 | 10.77 | 0.283530E+09 | 521.22 | 21-SEP-08:09 | 13.00 | 11.30 |
October | 0.243371E+10 | 5379.38 | 04-OCT-10:10 | 13.02 | 9.83 | 0.259403E+09 | 521.20 | 02-OCT-10:30 | 13.02 | 9.83 |
November | 0.135725E+10 | 2187.15 | 09-NOV-06:02 | 9.00 | 9.00 | 0.230809E+09 | 480.02 | 03-NOV-10:39 | 9.00 | 9.00 |
December | 0.664836E+09 | 1755.95 | 06-DEC-10:00 | 4.00 | 3.12 | 0.215188E+09 | 435.34 | 06-DEC-09:00 | 4.00 | 3.12 |
Annual Sum or Average | 0.401594E+11 | 0.319641E+10 | ||||||||
Minimum of Months | 0.664836E+09 | 1755.95 | 3.00 | 2.16 | 0.213876E+09 | 435.34 | 3.00 | 2.16 | ||
Maximum of Months | 0.626368E+10 | 19501.95 | 19.33 | 14.65 | 0.322470E+09 | 521.37 | 21.60 | 15.95 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305363E+10 | 11221.46 | 20-JAN-12:00 | 8.00 | 6.08 | 0.535520E+09 | 845.64 | 20-JAN-10:39 | 8.00 | 6.08 |
February | 0.356353E+10 | 13866.89 | 17-FEB-13:40 | 6.00 | 3.25 | 0.500594E+09 | 845.64 | 17-FEB-10:50 | 6.00 | 3.25 |
March | 0.343649E+10 | 7638.42 | 28-MAR-12:10 | 11.67 | 7.18 | 0.593873E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.757363E+10 | 29023.15 | 30-APR-13:32 | 22.67 | 12.88 | 0.587162E+09 | 846.36 | 28-APR-13:39 | 22.67 | 12.88 |
May | 0.657768E+10 | 13759.53 | 22-MAY-13:20 | 22.33 | 15.12 | 0.630325E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.728613E+10 | 13178.46 | 13-JUN-13:20 | 24.37 | 17.19 | 0.646009E+09 | 845.69 | 08-JUN-13:09 | 24.37 | 17.19 |
July | 0.830702E+10 | 24690.80 | 23-JUL-12:53 | 22.00 | 16.43 | 0.606049E+09 | 845.66 | 18-JUL-13:09 | 22.00 | 16.43 |
August | 0.102667E+11 | 26486.46 | 20-AUG-13:43 | 23.00 | 14.82 | 0.682086E+09 | 846.24 | 29-AUG-13:50 | 17.83 | 13.84 |
September | 0.997554E+10 | 27902.45 | 24-SEP-13:22 | 20.00 | 15.13 | 0.600571E+09 | 846.53 | 29-SEP-13:00 | 16.00 | 9.47 |
October | 0.595801E+10 | 26201.62 | 01-OCT-13:53 | 13.00 | 9.28 | 0.577114E+09 | 846.28 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.321775E+10 | 15527.34 | 11-NOV-12:53 | 9.00 | 7.43 | 0.534737E+09 | 845.64 | 17-NOV-14:09 | 8.00 | 6.02 |
December | 0.191569E+10 | 9469.72 | 18-DEC-13:30 | 8.00 | 5.46 | 0.492475E+09 | 845.64 | 26-DEC-14:00 | 6.00 | 3.37 |
Annual Sum or Average | 0.711318E+11 | 0.698652E+10 | ||||||||
Minimum of Months | 0.191569E+10 | 7638.42 | 6.00 | 3.25 | 0.492475E+09 | 845.64 | 6.00 | 3.25 | ||
Maximum of Months | 0.102667E+11 | 29023.15 | 24.37 | 17.19 | 0.682086E+09 | 846.53 | 24.37 | 17.19 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.138015E+10 | 3052.90 | 19-JAN-15:50 | 8.17 | 7.46 | 0.318422E+09 | 532.73 | 19-JAN-14:00 | 8.17 | 7.46 |
February | 0.171778E+10 | 5112.30 | 27-FEB-16:30 | 8.00 | 6.72 | 0.299019E+09 | 544.25 | 09-FEB-14:00 | 8.00 | 6.72 |
March | 0.237324E+10 | 5345.67 | 23-MAR-17:00 | 10.00 | 6.65 | 0.365737E+09 | 544.02 | 10-MAR-14:00 | 10.00 | 6.65 |
April | 0.437821E+10 | 20677.28 | 30-APR-16:11 | 24.00 | 12.95 | 0.368427E+09 | 544.97 | 14-APR-13:00 | 24.00 | 12.95 |
May | 0.487452E+10 | 17507.68 | 21-MAY-18:42 | 19.17 | 13.23 | 0.400849E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.613618E+10 | 21382.97 | 11-JUN-16:42 | 14.33 | 12.47 | 0.417481E+09 | 544.97 | 09-JUN-13:00 | 14.33 | 12.47 |
July | 0.664598E+10 | 20895.18 | 09-JUL-17:21 | 21.00 | 15.03 | 0.391411E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.640247E+10 | 20364.60 | 13-AUG-17:01 | 18.83 | 14.64 | 0.438885E+09 | 544.96 | 08-AUG-09:00 | 18.83 | 14.64 |
September | 0.462038E+10 | 15461.58 | 24-SEP-16:42 | 21.17 | 15.09 | 0.376874E+09 | 544.96 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.275573E+10 | 7573.83 | 03-OCT-16:00 | 14.00 | 8.96 | 0.351789E+09 | 544.93 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.173584E+10 | 3251.17 | 10-NOV-15:40 | 11.33 | 8.41 | 0.322531E+09 | 544.93 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.931095E+09 | 2062.80 | 21-DEC-14:50 | 8.00 | 6.98 | 0.295978E+09 | 490.56 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.439516E+11 | 0.434740E+10 | ||||||||
Minimum of Months | 0.931095E+09 | 2062.80 | 8.00 | 6.65 | 0.295978E+09 | 490.56 | 8.00 | 6.65 | ||
Maximum of Months | 0.664598E+10 | 21382.97 | 24.00 | 15.09 | 0.438885E+09 | 544.97 | 24.00 | 15.79 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.370511E+09 | 1773.48 | 19-JAN-15:40 | 8.33 | 7.46 | 0.467153E+09 | 675.90 | 19-JAN-14:00 | 8.33 | 7.46 |
February | 0.458273E+09 | 1663.67 | 09-FEB-16:00 | 8.00 | 5.66 | 0.424226E+09 | 652.63 | 22-FEB-14:00 | 9.00 | 6.99 |
March | 0.109182E+10 | 1991.48 | 30-MAR-15:30 | 12.00 | 6.19 | 0.521677E+09 | 727.84 | 30-MAR-13:00 | 12.00 | 6.19 |
April | 0.248653E+10 | 4968.01 | 28-APR-15:40 | 20.03 | 12.78 | 0.529973E+09 | 845.62 | 21-APR-13:09 | 20.03 | 12.78 |
May | 0.302053E+10 | 5653.86 | 22-MAY-15:50 | 23.17 | 15.42 | 0.588481E+09 | 845.62 | 22-MAY-13:00 | 23.17 | 15.42 |
June | 0.442374E+10 | 7704.33 | 13-JUN-16:00 | 26.50 | 17.70 | 0.633937E+09 | 845.64 | 09-JUN-13:00 | 26.50 | 17.70 |
July | 0.482428E+10 | 7299.23 | 10-JUL-15:00 | 23.00 | 16.69 | 0.596897E+09 | 845.63 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.466568E+10 | 6141.35 | 14-AUG-16:00 | 26.00 | 15.86 | 0.665023E+09 | 845.62 | 15-AUG-13:00 | 19.00 | 15.28 |
September | 0.304262E+10 | 5225.81 | 13-SEP-15:30 | 23.00 | 16.22 | 0.558184E+09 | 845.62 | 28-SEP-13:00 | 16.00 | 13.03 |
October | 0.144305E+10 | 2244.82 | 06-OCT-16:00 | 17.00 | 9.21 | 0.496811E+09 | 776.87 | 11-OCT-13:00 | 16.00 | 10.23 |
November | 0.576656E+09 | 1885.08 | 10-NOV-15:30 | 11.50 | 8.42 | 0.466597E+09 | 706.24 | 10-NOV-14:00 | 11.50 | 8.42 |
December | 0.148097E+09 | 1544.32 | 21-DEC-16:00 | 7.00 | 6.47 | 0.447652E+09 | 625.97 | 04-DEC-10:30 | 7.00 | 6.47 |
Annual Sum or Average | 0.265518E+11 | 0.639661E+10 | ||||||||
Minimum of Months | 0.148097E+09 | 1544.32 | 7.00 | 5.66 | 0.424226E+09 | 625.97 | 7.00 | 6.19 | ||
Maximum of Months | 0.482428E+10 | 7704.33 | 26.50 | 17.70 | 0.665023E+09 | 845.64 | 26.50 | 17.70 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.423227E+09 | 1759.30 | 20-JAN-10:30 | 5.00 | 4.55 | 0.301865E+09 | 464.86 | 20-JAN-10:50 | 5.67 | 5.18 |
February | 0.588349E+09 | 1849.83 | 24-FEB-10:35 | 5.67 | 4.28 | 0.277877E+09 | 481.16 | 24-FEB-10:39 | 5.67 | 4.28 |
March | 0.108701E+10 | 1837.48 | 30-MAR-10:40 | 9.67 | 6.89 | 0.338007E+09 | 473.36 | 30-MAR-13:00 | 13.00 | 7.37 |
April | 0.366759E+10 | 18398.57 | 30-APR-09:53 | 20.00 | 12.74 | 0.374285E+09 | 544.97 | 14-APR-13:00 | 20.00 | 12.74 |
May | 0.405614E+10 | 10696.74 | 23-MAY-09:10 | 19.17 | 14.75 | 0.401182E+09 | 544.96 | 22-MAY-13:00 | 19.17 | 14.75 |
June | 0.527426E+10 | 15270.73 | 25-JUN-10:43 | 20.50 | 14.20 | 0.415724E+09 | 545.57 | 13-JUN-09:00 | 20.50 | 14.20 |
July | 0.567233E+10 | 18603.91 | 23-JUL-09:32 | 20.67 | 15.88 | 0.391456E+09 | 545.41 | 10-JUL-09:50 | 20.67 | 15.88 |
August | 0.598631E+10 | 18389.30 | 20-AUG-08:52 | 17.00 | 13.49 | 0.437003E+09 | 544.97 | 23-AUG-09:09 | 16.17 | 12.09 |
September | 0.419449E+10 | 9062.79 | 12-SEP-09:30 | 17.50 | 14.46 | 0.381426E+09 | 544.98 | 06-SEP-09:09 | 17.50 | 14.46 |
October | 0.158061E+10 | 4011.74 | 04-OCT-10:00 | 13.00 | 9.81 | 0.334625E+09 | 544.94 | 05-OCT-09:30 | 12.50 | 8.91 |
November | 0.567003E+09 | 1716.78 | 10-NOV-15:10 | 11.83 | 8.42 | 0.300842E+09 | 455.98 | 10-NOV-14:00 | 11.83 | 8.42 |
December | 0.200293E+09 | 1472.12 | 06-DEC-10:10 | 4.50 | 3.47 | 0.288909E+09 | 414.46 | 06-DEC-10:20 | 5.00 | 3.82 |
Annual Sum or Average | 0.332976E+11 | 0.424320E+10 | ||||||||
Minimum of Months | 0.200293E+09 | 1472.12 | 4.50 | 3.47 | 0.277877E+09 | 414.46 | 5.00 | 3.82 | ||
Maximum of Months | 0.598631E+10 | 18603.91 | 20.67 | 15.88 | 0.437003E+09 | 545.57 | 20.67 | 15.88 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174870E+10 | 8315.56 | 20-JAN-12:00 | 8.00 | 6.08 | 0.502958E+09 | 845.64 | 17-JAN-14:30 | 8.00 | 6.08 |
February | 0.221881E+10 | 11554.74 | 17-FEB-14:10 | 6.00 | 3.06 | 0.470099E+09 | 845.64 | 24-FEB-14:30 | 6.00 | 4.60 |
March | 0.216776E+10 | 5443.45 | 10-MAR-14:40 | 8.67 | 4.91 | 0.547752E+09 | 845.65 | 28-MAR-13:09 | 10.17 | 6.99 |
April | 0.653623E+10 | 28062.69 | 30-APR-13:12 | 22.33 | 12.98 | 0.563431E+09 | 846.54 | 28-APR-13:39 | 22.33 | 12.98 |
May | 0.580403E+10 | 14295.38 | 22-MAY-13:30 | 22.50 | 15.28 | 0.601397E+09 | 845.66 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.692176E+10 | 14345.20 | 25-JUN-16:02 | 24.33 | 14.70 | 0.629300E+09 | 845.68 | 08-JUN-13:09 | 24.33 | 14.70 |
July | 0.805467E+10 | 27241.26 | 23-JUL-13:32 | 21.33 | 16.14 | 0.595974E+09 | 845.67 | 21-JUL-13:09 | 21.33 | 16.14 |
August | 0.986040E+10 | 27645.65 | 06-AUG-13:53 | 18.00 | 13.90 | 0.670788E+09 | 845.66 | 15-AUG-13:39 | 19.67 | 15.37 |
September | 0.902890E+10 | 28905.71 | 10-SEP-14:22 | 21.50 | 16.22 | 0.585790E+09 | 846.37 | 27-SEP-13:00 | 22.00 | 13.55 |
October | 0.441262E+10 | 18155.09 | 01-OCT-13:53 | 13.00 | 9.28 | 0.539870E+09 | 845.66 | 11-OCT-13:09 | 16.00 | 10.53 |
November | 0.180961E+10 | 8796.18 | 03-NOV-12:50 | 9.00 | 5.42 | 0.496824E+09 | 845.63 | 03-NOV-13:00 | 9.00 | 5.72 |
December | 0.961176E+09 | 6311.77 | 18-DEC-13:40 | 8.00 | 5.53 | 0.469656E+09 | 845.63 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.595247E+11 | 0.667384E+10 | ||||||||
Minimum of Months | 0.961176E+09 | 5443.45 | 6.00 | 3.06 | 0.469656E+09 | 845.63 | 6.00 | 4.60 | ||
Maximum of Months | 0.986040E+10 | 28905.71 | 24.33 | 16.22 | 0.670788E+09 | 846.54 | 24.33 | 16.14 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.669417E+09 | 2408.28 | 19-JAN-16:00 | 8.00 | 7.45 | 0.305880E+09 | 507.17 | 19-JAN-16:10 | 7.67 | 7.22 |
February | 0.972414E+09 | 3977.98 | 27-FEB-16:30 | 8.00 | 6.72 | 0.285276E+09 | 521.18 | 17-FEB-16:00 | 8.00 | 6.72 |
March | 0.155113E+10 | 4362.91 | 23-MAR-17:00 | 10.00 | 6.65 | 0.341821E+09 | 521.17 | 31-MAR-15:00 | 9.00 | 4.96 |
April | 0.390730E+10 | 20907.79 | 30-APR-17:12 | 24.00 | 12.77 | 0.347715E+09 | 544.97 | 14-APR-13:00 | 24.00 | 12.77 |
May | 0.442419E+10 | 22075.84 | 21-MAY-17:12 | 20.00 | 12.93 | 0.380935E+09 | 544.96 | 22-MAY-13:00 | 23.00 | 15.76 |
June | 0.590768E+10 | 23283.98 | 25-JUN-17:21 | 21.50 | 17.05 | 0.406286E+09 | 544.97 | 09-JUN-13:00 | 21.50 | 17.05 |
July | 0.648615E+10 | 23269.49 | 09-JUL-17:11 | 21.00 | 15.03 | 0.384719E+09 | 544.96 | 18-JUL-13:09 | 19.00 | 15.79 |
August | 0.614530E+10 | 21450.78 | 06-AUG-16:32 | 18.33 | 13.35 | 0.429897E+09 | 544.96 | 21-AUG-13:00 | 21.00 | 15.01 |
September | 0.420878E+10 | 12026.68 | 24-SEP-16:53 | 21.00 | 15.02 | 0.360813E+09 | 544.96 | 25-SEP-13:00 | 21.00 | 13.56 |
October | 0.197591E+10 | 6915.33 | 03-OCT-16:00 | 14.00 | 8.96 | 0.326747E+09 | 544.86 | 04-OCT-13:00 | 14.00 | 10.28 |
November | 0.913515E+09 | 2443.56 | 10-NOV-15:50 | 11.17 | 8.40 | 0.305431E+09 | 514.92 | 15-NOV-14:00 | 12.00 | 8.90 |
December | 0.365120E+09 | 1952.00 | 21-DEC-14:50 | 8.00 | 6.98 | 0.290191E+09 | 456.31 | 21-DEC-14:00 | 8.00 | 6.98 |
Annual Sum or Average | 0.375269E+11 | 0.416571E+10 | ||||||||
Minimum of Months | 0.365120E+09 | 1952.00 | 8.00 | 6.65 | 0.285276E+09 | 456.31 | 7.67 | 4.96 | ||
Maximum of Months | 0.648615E+10 | 23283.98 | 24.00 | 17.05 | 0.429897E+09 | 544.97 | 24.00 | 17.05 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.123426E+10 | 3766.79 | 02-JAN-06:10 | 1.17 | 0.75 | 0.00 | 0.00 | 01-JAN-00:10 | 1.17 | 0.75 |
February | 0.116837E+10 | 3616.29 | 11-FEB-06:10 | 2.00 | 2.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2.00 | 2.00 |
March | 0.212813E+10 | 4047.92 | 14-MAR-05:10 | 2.00 | 1.57 | 0.00 | 0.00 | 01-MAR-00:10 | 2.00 | 1.57 |
April | 0.465240E+10 | 7073.64 | 24-APR-05:15 | 7.00 | 5.00 | 0.00 | 0.00 | 01-APR-00:10 | 7.00 | 5.00 |
May | 0.387899E+10 | 7613.08 | 01-MAY-05:15 | 4.67 | 3.91 | 0.00 | 0.00 | 01-MAY-00:10 | 4.67 | 3.91 |
June | 0.554565E+10 | 7614.01 | 26-JUN-05:15 | 14.67 | 12.18 | 0.00 | 0.00 | 01-JUN-00:10 | 14.67 | 12.18 |
July | 0.648412E+10 | 8725.15 | 17-JUL-05:13 | 14.00 | 13.04 | 0.00 | 0.00 | 01-JUL-00:10 | 14.00 | 13.04 |
August | 0.724729E+10 | 8040.18 | 07-AUG-05:15 | 10.33 | 9.22 | 0.00 | 0.00 | 01-AUG-00:10 | 10.33 | 9.22 |
September | 0.477440E+10 | 6101.01 | 05-SEP-05:15 | 6.67 | 5.99 | 0.00 | 0.00 | 01-SEP-00:10 | 6.67 | 5.99 |
October | 0.293194E+10 | 7216.05 | 10-OCT-05:15 | 11.00 | 11.00 | 0.00 | 0.00 | 01-OCT-00:10 | 11.00 | 11.00 |
November | 0.188317E+10 | 4855.43 | 13-NOV-06:13 | 4.33 | 3.86 | 0.00 | 0.00 | 01-NOV-00:10 | 4.33 | 3.86 |
December | 0.111262E+10 | 3355.46 | 21-DEC-06:10 | 3.00 | 2.55 | 0.00 | 0.00 | 01-DEC-00:10 | 3.00 | 2.55 |
Annual Sum or Average | 0.430413E+11 | 0.00 | ||||||||
Minimum of Months | 0.111262E+10 | 3355.46 | 1.17 | 0.75 | 0.00 | 0.00 | 1.17 | 0.75 | ||
Maximum of Months | 0.724729E+10 | 8725.15 | 14.67 | 13.04 | 0.00 | 0.00 | 14.67 | 13.04 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.435783E+09 | 3663.39 | 09-JAN-05:01 | -2.1 | -2.8 | 0.00 | 0.00 | 01-JAN-00:10 | -2.1 | -2.8 |
February | 0.502418E+09 | 4636.37 | 18-FEB-06:01 | -1.2 | -1.5 | 0.00 | 0.00 | 01-FEB-00:10 | -1.2 | -1.5 |
March | 0.855803E+09 | 3613.81 | 04-MAR-06:03 | 3.00 | 0.90 | 0.00 | 0.00 | 01-MAR-00:10 | 3.00 | 0.90 |
April | 0.202464E+10 | 4270.58 | 22-APR-05:10 | 6.17 | 5.51 | 0.00 | 0.00 | 01-APR-00:10 | 6.17 | 5.51 |
May | 0.210689E+10 | 4324.13 | 03-MAY-05:10 | 3.50 | 2.98 | 0.00 | 0.00 | 01-MAY-00:10 | 3.50 | 2.98 |
June | 0.339061E+10 | 4648.03 | 13-JUN-15:30 | 26.25 | 17.77 | 0.00 | 0.00 | 01-JUN-00:10 | 26.25 | 17.77 |
July | 0.394567E+10 | 5620.27 | 25-JUL-05:13 | 13.00 | 13.00 | 0.00 | 0.00 | 01-JUL-00:10 | 13.00 | 13.00 |
August | 0.427582E+10 | 4520.83 | 18-AUG-16:00 | 21.00 | 16.54 | 0.00 | 0.00 | 01-AUG-00:10 | 21.00 | 16.54 |
September | 0.311482E+10 | 4462.16 | 14-SEP-05:15 | 11.33 | 10.21 | 0.00 | 0.00 | 01-SEP-00:10 | 11.33 | 10.21 |
October | 0.135518E+10 | 4028.00 | 05-OCT-05:10 | 4.00 | 4.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4.00 | 4.00 |
November | 0.601900E+09 | 4215.97 | 17-NOV-06:02 | 2.67 | 1.51 | 0.00 | 0.00 | 01-NOV-00:10 | 2.67 | 1.51 |
December | 0.220922E+09 | 5082.34 | 26-DEC-05:01 | 1.98 | 0.30 | 0.00 | 0.00 | 01-DEC-00:10 | 1.98 | 0.30 |
Annual Sum or Average | 0.228305E+11 | 0.00 | ||||||||
Minimum of Months | 0.220922E+09 | 3613.81 | -2.1 | -2.8 | 0.00 | 0.00 | -2.1 | -2.8 | ||
Maximum of Months | 0.427582E+10 | 5620.27 | 26.25 | 17.77 | 0.00 | 0.00 | 26.25 | 17.77 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 438856.51 | 169.85 | 21-JAN-13:25 | 7.50 | 6.06 | 0.00 | 0.00 | 01-JAN-00:10 | 7.50 | 6.06 |
February | 5241774.41 | 516.90 | 22-FEB-12:40 | 9.33 | 7.76 | 0.00 | 0.00 | 01-FEB-00:10 | 9.33 | 7.76 |
March | 0.112712E+09 | 2716.92 | 25-MAR-12:40 | 13.33 | 10.44 | 0.00 | 0.00 | 01-MAR-00:10 | 13.33 | 10.44 |
April | 0.310730E+10 | 12693.19 | 28-APR-14:50 | 20.08 | 13.54 | 0.00 | 0.00 | 01-APR-00:10 | 20.08 | 13.54 |
May | 0.360648E+10 | 13486.57 | 22-MAY-14:40 | 23.67 | 15.97 | 0.00 | 0.00 | 01-MAY-00:10 | 23.67 | 15.97 |
June | 0.587434E+10 | 15858.88 | 13-JUN-14:20 | 25.40 | 17.58 | 0.00 | 0.00 | 01-JUN-00:10 | 25.40 | 17.58 |
July | 0.698321E+10 | 15378.64 | 21-JUL-14:40 | 27.00 | 15.95 | 0.00 | 0.00 | 01-JUL-00:10 | 27.00 | 15.95 |
August | 0.664537E+10 | 13403.32 | 14-AUG-15:00 | 25.00 | 16.02 | 0.00 | 0.00 | 01-AUG-00:10 | 25.00 | 16.02 |
September | 0.377382E+10 | 11364.62 | 12-SEP-15:10 | 21.83 | 15.52 | 0.00 | 0.00 | 01-SEP-00:10 | 21.83 | 15.52 |
October | 0.586355E+09 | 4168.29 | 03-OCT-14:40 | 14.00 | 9.11 | 0.00 | 0.00 | 01-OCT-00:10 | 14.00 | 9.11 |
November | 325749.09 | 261.79 | 04-NOV-16:25 | 7.00 | 5.55 | 0.00 | 0.00 | 01-NOV-00:10 | 7.00 | 5.55 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 | 3.53 |
Annual Sum or Average | 0.306956E+11 | 0.00 | ||||||||
Minimum of Months | 0.00 | 0.00 | 4.00 | 3.53 | 0.00 | 0.00 | 4.00 | 3.53 | ||
Maximum of Months | 0.698321E+10 | 15858.88 | 27.00 | 17.58 | 0.00 | 0.00 | 27.00 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.319354E+10 | 1928.69 | 19-JAN-16:20 | 7.33 | 6.98 | 95230136.13 | 126.83 | 18-JAN-14:00 | 7.33 | 6.98 |
February | 0.780684E+10 | 4056.77 | 27-FEB-17:00 | 8.00 | 6.97 | 86396562.39 | 126.83 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.140578E+11 | 7028.40 | 31-MAR-24:00 | 4.30 | 1.71 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.30 | 1.71 |
April | 0.189017E+11 | 8121.94 | 30-APR-17:54 | 24.00 | 13.13 | 91605078.04 | 126.82 | 28-APR-13:09 | 24.00 | 13.13 |
May | 0.422653E+10 | 3368.83 | 31-MAY-24:00 | 9.40 | 7.45 | 99234931.03 | 126.84 | 23-MAY-13:00 | 9.40 | 7.45 |
June | 0.924615E+10 | 5204.77 | 30-JUN-24:00 | 11.00 | 9.86 | 98963293.33 | 126.84 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.146885E+11 | 7264.11 | 31-JUL-24:00 | 11.40 | 9.79 | 91885157.69 | 126.83 | 25-JUL-09:09 | 11.40 | 9.79 |
August | 0.196813E+11 | 8098.39 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:50 | 17.83 | 13.92 |
September | 0.414941E+10 | 3254.43 | 30-SEP-24:00 | 7.60 | 5.71 | 91609818.58 | 126.84 | 12-SEP-13:00 | 7.60 | 5.71 |
October | 0.908127E+10 | 5088.79 | 31-OCT-24:00 | 6.60 | 4.32 | 95232084.92 | 126.83 | 10-OCT-13:00 | 6.60 | 4.32 |
November | 0.135542E+11 | 5717.02 | 03-NOV-16:00 | 8.00 | 4.84 | 94301193.59 | 126.83 | 08-NOV-14:00 | 12.00 | 12.00 |
December | 0.188644E+11 | 7463.58 | 18-DEC-15:20 | 7.20 | 5.18 | 91880845.84 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.137452E+12 | 0.114281E+10 | ||||||||
Minimum of Months | 0.319354E+10 | 1928.69 | 4.30 | 1.71 | 86396562.39 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.196813E+11 | 8121.94 | 24.00 | 13.92 | 0.103238E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124970E+10 | 1689.93 | 19-JAN-16:30 | 7.00 | 6.74 | 95221121.03 | 126.82 | 18-JAN-14:00 | 7.00 | 6.74 |
February | 0.587114E+10 | 3641.91 | 27-FEB-17:00 | 8.00 | 6.97 | 86396571.01 | 126.82 | 08-FEB-14:00 | 8.00 | 6.97 |
March | 0.118245E+11 | 6256.79 | 31-MAR-23:50 | 4.37 | 1.72 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.37 | 1.72 |
April | 0.173312E+11 | 7725.42 | 30-APR-17:54 | 24.00 | 13.13 | 91605089.19 | 126.82 | 28-APR-09:30 | 24.00 | 13.13 |
May | 0.331183E+10 | 3060.88 | 31-MAY-24:00 | 9.40 | 7.45 | 99234855.49 | 126.84 | 23-MAY-13:00 | 9.40 | 7.45 |
June | 0.837931E+10 | 4706.65 | 30-JUN-24:00 | 11.00 | 9.86 | 98962849.40 | 126.84 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.136305E+11 | 6813.23 | 31-JUL-24:00 | 11.40 | 9.79 | 91885128.62 | 126.83 | 24-JUL-13:00 | 11.40 | 9.79 |
August | 0.184703E+11 | 7510.53 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:50 | 17.83 | 13.92 |
September | 0.333852E+10 | 2851.92 | 30-SEP-23:40 | 7.63 | 5.74 | 91609527.81 | 126.84 | 12-SEP-13:00 | 7.63 | 5.74 |
October | 0.736420E+10 | 4330.42 | 31-OCT-24:00 | 6.60 | 4.32 | 95231941.05 | 126.83 | 13-OCT-13:00 | 6.60 | 4.32 |
November | 0.111157E+11 | 5287.96 | 10-NOV-16:20 | 9.67 | 7.83 | 94301116.92 | 126.83 | 08-NOV-14:00 | 9.67 | 7.83 |
December | 0.155306E+11 | 6773.59 | 21-DEC-15:20 | 7.67 | 6.81 | 91880858.00 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.117417E+12 | 0.114280E+10 | ||||||||
Minimum of Months | 0.124970E+10 | 1689.93 | 4.37 | 1.72 | 86396571.01 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.184703E+11 | 7725.42 | 24.00 | 13.92 | 0.103238E+09 | 126.84 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.307179E+09 | 1505.49 | 19-JAN-16:30 | 7.00 | 6.74 | 93458122.08 | 127.55 | 05-JAN-10:20 | 7.00 | 6.74 |
February | 0.399539E+10 | 3434.55 | 09-FEB-17:00 | 6.00 | 4.60 | 86396569.10 | 126.82 | 08-FEB-14:00 | 6.00 | 4.60 |
March | 0.101103E+11 | 5713.08 | 31-MAR-23:20 | 4.57 | 1.75 | 0.103236E+09 | 126.82 | 20-MAR-09:09 | 4.57 | 1.75 |
April | 0.164212E+11 | 7836.61 | 30-APR-18:03 | 24.00 | 13.14 | 91605092.01 | 126.82 | 28-APR-13:09 | 24.00 | 13.14 |
May | 0.250510E+10 | 2889.65 | 31-MAY-23:20 | 10.00 | 9.01 | 99235288.39 | 126.84 | 23-MAY-13:00 | 10.00 | 9.01 |
June | 0.798488E+10 | 4440.45 | 30-JUN-23:20 | 11.00 | 10.27 | 98962897.21 | 126.84 | 27-JUN-09:09 | 11.00 | 10.27 |
July | 0.132955E+11 | 6659.00 | 31-JUL-23:30 | 11.35 | 9.97 | 91885260.28 | 126.83 | 24-JUL-13:39 | 11.35 | 9.97 |
August | 0.181470E+11 | 7548.60 | 13-AUG-18:10 | 17.83 | 13.92 | 0.103238E+09 | 126.83 | 08-AUG-13:50 | 17.83 | 13.92 |
September | 0.263985E+10 | 2282.01 | 30-SEP-23:20 | 7.67 | 5.77 | 91609449.18 | 126.84 | 12-SEP-13:00 | 7.67 | 5.77 |
October | 0.575094E+10 | 3722.82 | 31-OCT-23:20 | 6.67 | 4.17 | 95231863.37 | 126.83 | 13-OCT-13:00 | 6.67 | 4.17 |
November | 0.921573E+10 | 5171.27 | 10-NOV-16:20 | 9.67 | 7.83 | 94301132.56 | 126.83 | 08-NOV-14:00 | 9.67 | 7.83 |
December | 0.134482E+11 | 6474.81 | 21-DEC-15:20 | 7.67 | 6.81 | 91880861.70 | 126.82 | 26-DEC-10:09 | 3.17 | 1.00 |
Annual Sum or Average | 0.103821E+12 | 0.114104E+10 | ||||||||
Minimum of Months | 0.307179E+09 | 1505.49 | 4.57 | 1.75 | 86396569.10 | 126.82 | 3.17 | 1.00 | ||
Maximum of Months | 0.181470E+11 | 7836.61 | 24.00 | 13.92 | 0.103238E+09 | 127.55 | 24.00 | 13.92 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236751E+12 | 91170.55 | 19-JAN-17:00 | 6.00 | 6.00 | 0.206159E+10 | 2747.29 | 09-JAN-10:09 | 6.00 | 6.00 |
February | 0.434719E+12 | 182631.94 | 09-FEB-17:00 | 6.00 | 4.60 | 0.187035E+10 | 2745.79 | 17-FEB-14:09 | 6.00 | 3.06 |
March | 0.727991E+12 | 358474.01 | 31-MAR-24:00 | 4.30 | 1.71 | 0.223495E+10 | 2746.37 | 08-MAR-10:09 | 4.30 | 1.71 |
April | 0.943033E+12 | 368981.09 | 30-APR-19:43 | 18.17 | 12.74 | 0.198339E+10 | 2746.68 | 14-APR-13:09 | 18.17 | 12.74 |
May | 0.240065E+12 | 175690.83 | 31-MAY-24:00 | 9.40 | 7.45 | 0.214816E+10 | 2745.84 | 23-MAY-13:50 | 9.40 | 7.45 |
June | 0.469472E+12 | 267076.30 | 30-JUN-24:00 | 11.00 | 9.86 | 0.214228E+10 | 2745.91 | 27-JUN-09:09 | 11.00 | 9.86 |
July | 0.731291E+12 | 359774.43 | 31-JUL-24:00 | 11.40 | 9.79 | 0.198903E+10 | 2745.56 | 25-JUL-09:00 | 11.40 | 9.79 |
August | 0.976610E+12 | 367772.27 | 15-AUG-16:00 | 17.00 | 13.95 | 0.223728E+10 | 2844.43 | 14-AUG-13:00 | 17.00 | 13.95 |
September | 0.233811E+12 | 175385.27 | 30-SEP-24:00 | 7.60 | 5.71 | 0.198313E+10 | 2746.01 | 19-SEP-13:00 | 7.60 | 5.71 |
October | 0.484641E+12 | 267241.64 | 31-OCT-24:00 | 6.60 | 4.32 | 0.206150E+10 | 2745.64 | 13-OCT-13:00 | 6.60 | 4.32 |
November | 0.705879E+12 | 275298.31 | 13-NOV-17:00 | 8.00 | 7.45 | 0.204142E+10 | 2746.38 | 29-NOV-10:09 | 2.17 | 0.48 |
December | 0.973837E+12 | 366753.06 | 26-DEC-17:00 | 1.00 | 0.17 | 0.198924E+10 | 2747.72 | 04-DEC-10:00 | 1.00 | 0.17 |
Annual Sum or Average | 0.715810E+13 | 0.247423E+11 | ||||||||
Minimum of Months | 0.233811E+12 | 91170.55 | 1.00 | 0.17 | 0.187035E+10 | 2745.56 | 1.00 | 0.17 | ||
Maximum of Months | 0.976610E+12 | 368981.09 | 18.17 | 13.95 | 0.223728E+10 | 2844.43 | 18.17 | 13.95 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.366373E+09 | 10793.39 | 18-JAN-05:05 | 6.83 |
February | 88936347.89 | 10780.64 | 08-FEB-05:05 | 6.00 |
March | 0.150542E+09 | 10982.03 | 27-MAR-03:07 | 1.65 |
April | 0.165625E+09 | 10684.56 | 27-APR-04:07 | 4.00 |
May | 0.250627E+09 | 10917.68 | 22-MAY-03:05 | 9.17 |
June | 0.167759E+09 | 10812.41 | 03-JUN-04:05 | 8.00 |
July | 0.265234E+09 | 14851.13 | 22-JUL-16:01 | 29.00 |
August | 0.225364E+09 | 10629.51 | 29-AUG-03:05 | 13.83 |
September | 0.273143E+09 | 12108.46 | 04-SEP-12:33 | 16.67 |
October | 0.315661E+09 | 11051.45 | 16-OCT-03:07 | 8.17 |
November | 0.292350E+09 | 11028.15 | 06-NOV-04:07 | 8.00 |
December | 0.136249E+09 | 11117.41 | 11-DEC-05:25 | 3.00 |
Annual Sum or Average | 0.269786E+10 | |||
Minimum of Months | 88936347.89 | 10629.51 | 1.65 | |
Maximum of Months | 0.366373E+09 | 14851.13 | 29.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173699E+10 | 69389.27 | 02-JAN-04:11 | 1.13 |
February | 0.827069E+09 | 64091.52 | 21-FEB-05:01 | 5.48 |
March | 0.309783E+09 | 62501.52 | 06-MAR-05:01 | 3.83 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 84253395.77 | 57845.66 | 23-OCT-05:03 | 3.17 |
November | 0.747748E+09 | 64155.15 | 27-NOV-05:01 | 4.00 |
December | 0.170069E+10 | 67431.21 | 26-DEC-04:01 | 2.00 |
Annual Sum or Average | 0.540653E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.13 | |
Maximum of Months | 0.173699E+10 | 69389.27 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 821474.34 | 4633.63 | 11-JAN-06:01 | -2.9 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 821474.34 | |||
Minimum of Months | 0.00 | 0.00 | -2.9 | |
Maximum of Months | 821474.34 | 4633.63 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 4705623.64 | 3808.02 | 11-JAN-06:01 | -2.9 |
February | 36176.22 | 422.06 | 17-FEB-06:03 | -3.1 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 267703.68 | 2926.44 | 30-DEC-06:01 | -1.0 |
Annual Sum or Average | 5009503.54 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 4705623.64 | 3808.02 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 18848939.99 | 8148.18 | 10-JAN-06:01 | -4.0 |
February | 96292.85 | 665.39 | 16-FEB-06:06 | 3.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 352820.21 | 3671.88 | 27-NOV-06:01 | 4.00 |
December | 3990079.66 | 7695.03 | 26-DEC-06:02 | 1.92 |
Annual Sum or Average | 23288132.71 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 18848939.99 | 8148.18 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.723291E+09 | 9006.81 | 02-JAN-05:01 | 1.00 |
February | 0.344472E+09 | 8564.08 | 13-FEB-05:01 | -1.0 |
March | 92224208.56 | 8113.74 | 06-MAR-06:01 | 4.00 |
April | 27331.29 | 182.21 | 01-APR-05:03 | 2.17 |
May | 1235032.13 | 5772.47 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 18781346.11 | 7839.06 | 23-OCT-05:03 | 3.17 |
November | 0.305983E+09 | 8776.62 | 20-NOV-05:01 | 0.67 |
December | 0.110303E+10 | 9335.41 | 26-DEC-04:01 | 2.00 |
Annual Sum or Average | 0.258904E+10 | |||
Minimum of Months | 0.00 | 0.00 | -1.0 | |
Maximum of Months | 0.110303E+10 | 9335.41 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.432637E+09 | 11529.07 | 11-JAN-05:01 | -3.0 |
February | 0.198953E+09 | 10879.37 | 17-FEB-05:01 | -2.1 |
March | 61898811.20 | 10087.77 | 06-MAR-06:01 | 4.00 |
April | 64792.40 | 312.37 | 11-APR-05:05 | 5.83 |
May | 682141.53 | 4547.61 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 13424195.81 | 7162.89 | 21-OCT-05:03 | 7.00 |
November | 0.195550E+09 | 11019.29 | 20-NOV-05:01 | 0.67 |
December | 0.743194E+09 | 11922.34 | 26-DEC-04:01 | 2.00 |
Annual Sum or Average | 0.164640E+10 | |||
Minimum of Months | 0.00 | 0.00 | -3.0 | |
Maximum of Months | 0.743194E+09 | 11922.34 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.318819E+09 | 16101.85 | 10-JAN-05:01 | -4.0 |
February | 0.125802E+09 | 15131.66 | 17-FEB-06:01 | -3.1 |
March | 46785846.17 | 14767.45 | 06-MAR-06:01 | 4.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 1716146.67 | 7700.76 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 5179952.17 | 7531.92 | 28-OCT-05:03 | 7.00 |
November | 0.155779E+09 | 15734.68 | 27-NOV-05:01 | 4.00 |
December | 0.721436E+09 | 16789.57 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.137552E+10 | |||
Minimum of Months | 0.00 | 0.00 | -4.0 | |
Maximum of Months | 0.721436E+09 | 16789.57 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.241260E+09 | 10606.99 | 11-JAN-05:01 | -3.0 |
February | 84887924.51 | 9624.72 | 17-FEB-06:01 | -3.1 |
March | 16789614.96 | 8310.32 | 04-MAR-06:03 | 3.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 545420.31 | 3347.09 | 05-MAY-05:03 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 1269198.11 | 3149.92 | 28-OCT-05:03 | 7.00 |
November | 0.106330E+09 | 10268.34 | 29-NOV-05:01 | -0.2 |
December | 0.406818E+09 | 10902.77 | 26-DEC-05:01 | 1.98 |
Annual Sum or Average | 0.857901E+09 | |||
Minimum of Months | 0.00 | 0.00 | -3.1 | |
Maximum of Months | 0.406818E+09 | 10902.77 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371247E+10 | 11199.73 | 02-JAN-04:11 | 1.13 |
February | 0.260002E+10 | 11139.62 | 13-FEB-04:01 | -1.8 |
March | 0.153307E+10 | 10561.13 | 06-MAR-04:02 | 3.80 |
April | 0.239620E+09 | 9301.08 | 11-APR-04:03 | 6.00 |
May | 0.120876E+09 | 9669.31 | 05-MAY-04:02 | 5.17 |
June | 1994797.76 | 7466.06 | 08-JUN-05:02 | 6.17 |
July | 120176.24 | 801.17 | 31-JUL-05:03 | 7.50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 22526225.57 | 8917.13 | 18-SEP-05:03 | 12.00 |
October | 0.825538E+09 | 10166.31 | 30-OCT-04:01 | 7.00 |
November | 0.228714E+10 | 11143.73 | 20-NOV-04:11 | 1.67 |
December | 0.448802E+10 | 11398.92 | 26-DEC-03:53 | 2.00 |
Annual Sum or Average | 0.158314E+11 | |||
Minimum of Months | 0.00 | 0.00 | -1.8 | |
Maximum of Months | 0.448802E+10 | 11398.92 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.210613E+10 | 15260.48 | 02-JAN-04:11 | 1.13 |
February | 0.143702E+10 | 14892.17 | 27-FEB-04:01 | 6.00 |
March | 0.906162E+09 | 14123.51 | 06-MAR-04:02 | 3.80 |
April | 74348819.62 | 10638.52 | 08-APR-05:02 | 0.00 |
May | 45657225.67 | 12966.95 | 05-MAY-04:02 | 5.17 |
June | 380549.10 | 1635.47 | 07-JUN-05:03 | 6.33 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 1556349.46 | 3660.59 | 18-SEP-05:03 | 12.00 |
October | 0.456837E+09 | 13382.53 | 30-OCT-04:01 | 7.00 |
November | 0.133954E+10 | 14971.13 | 20-NOV-04:11 | 1.67 |
December | 0.276656E+10 | 15231.26 | 30-DEC-04:01 | -2.0 |
Annual Sum or Average | 0.913419E+10 | |||
Minimum of Months | 0.00 | 0.00 | -2.0 | |
Maximum of Months | 0.276656E+10 | 15260.48 | 12.00 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215106E+10 | 22888.75 | 02-JAN-04:11 | 1.13 |
February | 0.147605E+10 | 22383.65 | 27-FEB-04:01 | 6.00 |
March | 0.114716E+10 | 21212.60 | 06-MAR-04:02 | 3.80 |
April | 0.111728E+09 | 15630.40 | 24-APR-05:03 | 7.00 |
May | 0.130312E+09 | 19506.43 | 05-MAY-04:02 | 5.17 |
June | 4099599.72 | 14066.47 | 08-JUN-05:02 | 6.17 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 365882.47 | 2703.24 | 07-SEP-05:02 | 8.83 |
October | 0.488262E+09 | 19777.08 | 30-OCT-04:01 | 7.00 |
November | 0.143814E+10 | 22522.46 | 27-NOV-04:01 | 4.83 |
December | 0.331020E+10 | 22771.05 | 04-DEC-04:01 | 1.33 |
Annual Sum or Average | 0.102574E+11 | |||
Minimum of Months | 0.00 | 0.00 | 1.13 | |
Maximum of Months | 0.331020E+10 | 22888.75 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149515E+10 | 15645.68 | 02-JAN-04:11 | 1.13 |
February | 0.861694E+09 | 14601.47 | 27-FEB-04:01 | 6.00 |
March | 0.512265E+09 | 13778.93 | 13-MAR-04:01 | 2.18 |
April | 32771182.17 | 8833.41 | 01-APR-05:03 | 2.17 |
May | 43683972.37 | 12852.15 | 05-MAY-04:02 | 5.17 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 1239255.43 | 4987.53 | 07-SEP-05:02 | 8.83 |
October | 0.250206E+09 | 13130.00 | 30-OCT-04:01 | 7.00 |
November | 0.850610E+09 | 15051.40 | 27-NOV-04:01 | 4.83 |
December | 0.186665E+10 | 15438.22 | 04-DEC-04:01 | 1.33 |
Annual Sum or Average | 0.591426E+10 | |||
Minimum of Months | 0.00 | 0.00 | 1.13 | |
Maximum of Months | 0.186665E+10 | 15645.68 | 11.43 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.206015E+09 | 10237.20 | 17-JAN-05:01 | 6.00 |
February | 85478908.31 | 11435.08 | 27-FEB-05:01 | 6.00 |
March | 64652535.73 | 10922.75 | 06-MAR-05:01 | 3.83 |
April | 0.146675E+09 | 10826.45 | 24-APR-03:02 | 7.00 |
May | 0.101075E+09 | 9312.93 | 01-MAY-03:02 | 6.17 |
June | 0.101578E+09 | 9109.53 | 19-JUN-03:02 | 11.00 |
July | 0.139303E+09 | 10055.21 | 03-JUL-03:02 | 9.83 |
August | 0.129054E+09 | 9806.63 | 31-AUG-03:02 | 12.00 |
September | 92381638.05 | 8742.76 | 01-SEP-03:02 | 12.92 |
October | 71216990.38 | 9497.25 | 10-OCT-03:02 | 10.83 |
November | 86647968.21 | 11922.28 | 20-NOV-05:01 | 0.67 |
December | 73897099.24 | 13601.68 | 26-DEC-04:01 | 2.00 |
Annual Sum or Average | 0.129797E+10 | |||
Minimum of Months | 64652535.73 | 8742.76 | 0.67 | |
Maximum of Months | 0.206015E+09 | 13601.68 | 12.92 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.130704E+10 | 6664.42 | 26-JAN-06:02 | 5.00 |
February | 0.949967E+09 | 6829.48 | 10-FEB-06:03 | 5.00 |
March | 0.682753E+09 | 7448.12 | 09-MAR-06:02 | 7.15 |
April | 63986904.67 | 8254.43 | 30-APR-14:51 | 24.00 |
May | 74749579.60 | 6979.03 | 30-MAY-04:03 | 8.00 |
June | 56070544.50 | 6700.67 | 08-JUN-05:02 | 6.17 |
July | 65132881.75 | 7677.45 | 05-JUL-04:03 | 7.83 |
August | 61630334.45 | 7340.05 | 13-AUG-15:41 | 21.00 |
September | 74536048.97 | 7088.22 | 10-SEP-15:42 | 21.17 |
October | 0.254619E+09 | 6917.20 | 27-OCT-05:03 | 9.00 |
November | 0.743312E+09 | 7258.38 | 15-NOV-06:03 | 10.50 |
December | 0.147398E+10 | 4271.77 | 26-DEC-14:30 | 6.00 |
Annual Sum or Average | 0.580778E+10 | |||
Minimum of Months | 56070544.50 | 4271.77 | 5.00 | |
Maximum of Months | 0.147398E+10 | 8254.43 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.645674E+10 | 19784.37 | 09-JAN-05:13 | -2.1 |
February | 0.470725E+10 | 17350.47 | 13-FEB-06:13 | -1.0 |
March | 0.376553E+10 | 13262.23 | 06-MAR-06:13 | 4.00 |
April | 0.122633E+10 | 15504.91 | 28-APR-05:03 | 6.17 |
May | 0.954632E+09 | 15570.23 | 24-MAY-05:02 | 8.42 |
June | 0.348557E+09 | 16093.81 | 20-JUN-05:02 | 8.50 |
July | 0.258852E+09 | 16814.76 | 05-JUL-05:03 | 7.33 |
August | 0.397686E+09 | 15288.96 | 23-AUG-05:03 | 9.33 |
September | 0.761544E+09 | 15322.70 | 29-SEP-05:02 | 9.33 |
October | 0.260833E+10 | 10210.51 | 23-OCT-05:03 | 3.17 |
November | 0.471456E+10 | 17293.00 | 27-NOV-06:13 | 4.00 |
December | 0.777486E+10 | 19534.28 | 26-DEC-05:23 | 1.95 |
Annual Sum or Average | 0.339749E+11 | |||
Minimum of Months | 0.258852E+09 | 10210.51 | -2.1 | |
Maximum of Months | 0.777486E+10 | 19784.37 | 9.33 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50996309.58 | 465.66 | 01-JAN-08:35 | 4.33 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 50996309.58 | |||
Minimum of Months | 0.00 | 0.00 | 3.80 | |
Maximum of Months | 50996309.58 | 465.66 | 12.43 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.664686E+09 | 570.92 | 10-JAN-00:10 | -2.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 4863963.72 | 369.58 | 14-MAY-06:35 | 9.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 2019335.40 | 369.57 | 17-SEP-09:05 | 13.33 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.671569E+09 | |||
Minimum of Months | 0.00 | 0.00 | -2.0 | |
Maximum of Months | 0.664686E+09 | 570.92 | 13.33 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 1.92 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 7.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 3.80 |
April | 0.00 | 0.00 | 01-APR-00:10 | 4.23 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 10.47 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 9.27 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 11.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 11.43 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 12.43 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 7.57 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 6.57 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 4.00 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1.92 | |
Maximum of Months | 0.00 | 0.00 | 12.43 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.129816E+10 | 1750.00 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.109617E+10 | 1676.34 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123733E+10 | 1551.92 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107221E+10 | 1392.21 | 10-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113161E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.111671E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105067E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118683E+10 | 1225.05 | 22-AUG-07:30 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108952E+10 | 1308.70 | 08-SEP-07:30 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.119761E+10 | 1743.29 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.127574E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.131874E+10 | 1750.00 | 01-DEC-15:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.140713E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105067E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.131874E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.822697E+09 | 1127.77 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.700601E+09 | 1076.92 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.796064E+09 | 978.80 | 15-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.691162E+09 | 861.78 | 10-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.730636E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.721329E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.678665E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.765573E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.699864E+09 | 788.09 | 08-SEP-07:30 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.766085E+09 | 1123.22 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.810530E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.830674E+09 | 1127.77 | 01-DEC-15:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.901388E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.678665E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.830674E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.126396E+10 | 1750.04 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.107976E+10 | 1672.94 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.123151E+10 | 1542.89 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107379E+10 | 1386.38 | 10-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.113501E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.112001E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.105409E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118900E+10 | 1215.49 | 22-AUG-07:30 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108777E+10 | 1282.58 | 08-SEP-07:30 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.118480E+10 | 1743.06 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.124564E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.127552E+10 | 1750.04 | 01-DEC-15:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.139409E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.105409E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.127552E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.827120E+09 | 1127.77 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.702041E+09 | 1081.04 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.797686E+09 | 1010.34 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.691941E+09 | 915.17 | 10-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.730500E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.720590E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.678131E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.766245E+09 | 829.07 | 22-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.703600E+09 | 923.52 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.770533E+09 | 1123.48 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.813668E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.838654E+09 | 1127.77 | 01-DEC-15:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.904071E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.678131E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.838654E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130076E+10 | 1750.00 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.109791E+10 | 1678.55 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123847E+10 | 1557.89 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107258E+10 | 1402.88 | 10-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113208E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.111699E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105084E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118677E+10 | 1240.46 | 22-AUG-07:30 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109005E+10 | 1321.76 | 08-SEP-07:30 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.119953E+10 | 1743.49 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.127921E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.132293E+10 | 1750.00 | 01-DEC-15:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.140881E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105084E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.132293E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.823122E+09 | 1127.77 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.701011E+09 | 1077.40 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.796372E+09 | 980.72 | 15-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.691254E+09 | 865.39 | 10-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.730747E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.721412E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.678754E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.765670E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.700006E+09 | 792.06 | 08-SEP-07:30 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.766378E+09 | 1123.26 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.810942E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.831350E+09 | 1127.77 | 01-DEC-15:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.901702E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.678754E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.831350E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.126543E+10 | 1750.04 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.108092E+10 | 1675.32 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.123246E+10 | 1549.27 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107410E+10 | 1397.26 | 10-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.113535E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.112034E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.105437E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118943E+10 | 1231.20 | 22-AUG-07:30 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108829E+10 | 1296.64 | 08-SEP-07:30 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.118622E+10 | 1743.27 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.124760E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.127762E+10 | 1750.04 | 01-DEC-15:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.139521E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.105437E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.127762E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.827730E+09 | 1127.77 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.702395E+09 | 1081.40 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.798076E+09 | 1011.24 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.692140E+09 | 916.79 | 10-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.730640E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.720681E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.678215E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.766358E+09 | 831.20 | 22-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.703827E+09 | 924.94 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.771078E+09 | 1123.51 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.814295E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.839493E+09 | 1127.77 | 01-DEC-15:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.904493E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.678215E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.839493E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.130075E+10 | 1750.00 | 02-JAN-08:09 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.109789E+10 | 1678.48 | 01-FEB-08:09 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123846E+10 | 1557.72 | 15-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107258E+10 | 1402.54 | 10-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.113208E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.111699E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105084E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.118676E+10 | 1239.98 | 22-AUG-07:30 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.109006E+10 | 1321.35 | 08-SEP-07:30 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.119951E+10 | 1743.49 | 31-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.127916E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.132288E+10 | 1750.00 | 01-DEC-15:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.140880E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105084E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.132288E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.823123E+09 | 1127.77 | 02-JAN-08:09 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.701008E+09 | 1077.36 | 01-FEB-08:09 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.796371E+09 | 980.63 | 15-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.691255E+09 | 865.22 | 10-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.730734E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.721410E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.678756E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.765671E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.700027E+09 | 791.87 | 08-SEP-07:30 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.766371E+09 | 1123.25 | 31-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.810886E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.831299E+09 | 1127.77 | 01-DEC-15:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.901691E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.678756E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.831299E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.126544E+10 | 1750.04 | 02-JAN-08:09 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.108092E+10 | 1675.24 | 01-FEB-08:09 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.123245E+10 | 1549.09 | 15-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107410E+10 | 1396.92 | 10-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.113535E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.112034E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.105437E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.118943E+10 | 1230.71 | 22-AUG-07:30 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108830E+10 | 1296.23 | 08-SEP-07:30 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.118621E+10 | 1743.27 | 31-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.124758E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.127762E+10 | 1750.04 | 01-DEC-15:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.139521E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.105437E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.127762E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.827812E+09 | 1127.77 | 02-JAN-08:09 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.702393E+09 | 1081.36 | 01-FEB-08:09 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.798028E+09 | 1011.13 | 15-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.692156E+09 | 916.58 | 10-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.730649E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.720681E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.678213E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.766359E+09 | 830.96 | 22-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.703835E+09 | 924.85 | 08-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.771074E+09 | 1123.51 | 31-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.814278E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.839481E+09 | 1127.77 | 01-DEC-15:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.904496E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.678213E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.839481E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.129816E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223374E+09 |
February | 0.136985E+10 | 0.109617E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314979E+09 |
March | 0.163685E+10 | 0.123733E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187596E+09 |
April | 0.145243E+10 | 0.107221E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233471E+09 |
May | 0.157338E+10 | 0.113161E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.52 | 0.555002E+09 |
June | 0.156900E+10 | 0.111671E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249727.70 | 0.427532E+09 |
July | 0.145680E+10 | 0.105067E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1209318.92 | 0.412042E+09 |
August | 0.163685E+10 | 0.118683E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161946.43 | 0.296748E+09 |
September | 0.145243E+10 | 0.108952E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.312310E+09 |
October | 0.150991E+10 | 0.119761E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340077E+09 |
November | 0.149516E+10 | 0.127574E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420842E+09 |
December | 0.145680E+10 | 0.131874E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.575815E+09 |
Annual Sum or Average | 0.181194E+11 | 0.140713E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1620996.57 | 0.429979E+10 |
Minimum of Months | 0.136985E+10 | 0.105067E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187596E+09 |
Maximum of Months | 0.163685E+10 | 0.131874E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1209318.92 | 0.575815E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.822697E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148295E+09 |
February | 0.882782E+09 | 0.700601E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207090E+09 |
March | 0.105485E+10 | 0.796064E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122218E+09 |
April | 0.936002E+09 | 0.691162E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154470E+09 |
May | 0.101394E+10 | 0.730636E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 0.371961E+09 |
June | 0.101113E+10 | 0.721329E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166483.00 | 0.282935E+09 |
July | 0.938820E+09 | 0.678665E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 860355.74 | 0.271871E+09 |
August | 0.105485E+10 | 0.765573E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107963.23 | 0.194300E+09 |
September | 0.936002E+09 | 0.699864E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212536E+09 |
October | 0.973041E+09 | 0.766085E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223574E+09 |
November | 0.963541E+09 | 0.810530E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272887E+09 |
December | 0.938820E+09 | 0.830674E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370369E+09 |
Annual Sum or Average | 0.116768E+11 | 0.901388E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1134804.30 | 0.283251E+10 |
Minimum of Months | 0.882782E+09 | 0.678665E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122218E+09 |
Maximum of Months | 0.105485E+10 | 0.830674E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 860355.74 | 0.371961E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.126396E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222539E+09 |
February | 0.136988E+10 | 0.107976E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.313235E+09 |
March | 0.163688E+10 | 0.123151E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182522E+09 |
April | 0.145246E+10 | 0.107379E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235955E+09 |
May | 0.157341E+10 | 0.113501E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.44 | 0.555306E+09 |
June | 0.156904E+10 | 0.112001E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 249721.98 | 0.426205E+09 |
July | 0.145684E+10 | 0.105409E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1205877.52 | 0.413639E+09 |
August | 0.163688E+10 | 0.118900E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 161945.22 | 0.303774E+09 |
September | 0.145246E+10 | 0.108777E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324875E+09 |
October | 0.150994E+10 | 0.118480E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.341022E+09 |
November | 0.149520E+10 | 0.124564E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.412918E+09 |
December | 0.145684E+10 | 0.127552E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.553729E+09 |
Annual Sum or Average | 0.181198E+11 | 0.139409E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 1617548.16 | 0.428572E+10 |
Minimum of Months | 0.136988E+10 | 0.105409E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182522E+09 |
Maximum of Months | 0.163688E+10 | 0.127552E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1205877.52 | 0.555306E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.827120E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155722E+09 |
February | 0.882782E+09 | 0.702041E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225888E+09 |
March | 0.105485E+10 | 0.797686E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134363E+09 |
April | 0.936002E+09 | 0.691941E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173031E+09 |
May | 0.101394E+10 | 0.730500E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 0.396241E+09 |
June | 0.101113E+10 | 0.720590E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166456.16 | 0.312650E+09 |
July | 0.938820E+09 | 0.678131E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 663228.60 | 0.310432E+09 |
August | 0.105485E+10 | 0.766245E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 107920.54 | 0.227302E+09 |
September | 0.936002E+09 | 0.703600E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225926E+09 |
October | 0.973041E+09 | 0.770533E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246370E+09 |
November | 0.963541E+09 | 0.813668E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307282E+09 |
December | 0.938820E+09 | 0.838654E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.424822E+09 |
Annual Sum or Average | 0.116768E+11 | 0.904071E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 937607.66 | 0.314003E+10 |
Minimum of Months | 0.882782E+09 | 0.678131E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134363E+09 |
Maximum of Months | 0.105485E+10 | 0.838654E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 663228.60 | 0.424822E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.130076E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454595E+09 |
February | 0.136985E+10 | 0.109791E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.647718E+09 |
March | 0.163685E+10 | 0.123847E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387729E+09 |
April | 0.145243E+10 | 0.107258E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.496055E+09 |
May | 0.157338E+10 | 0.113208E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120282E+10 |
June | 0.156900E+10 | 0.111699E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546242.35 | 0.940670E+09 |
July | 0.145680E+10 | 0.105084E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2837407.50 | 0.892864E+09 |
August | 0.163685E+10 | 0.118677E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356978.37 | 0.644841E+09 |
September | 0.145243E+10 | 0.109005E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669276E+09 |
October | 0.150991E+10 | 0.119953E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697928E+09 |
November | 0.149516E+10 | 0.127921E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.838566E+09 |
December | 0.145680E+10 | 0.132293E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112946E+10 |
Annual Sum or Average | 0.181194E+11 | 0.140881E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3740628.22 | 0.900252E+10 |
Minimum of Months | 0.136985E+10 | 0.105084E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387729E+09 |
Maximum of Months | 0.163685E+10 | 0.132293E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2837407.50 | 0.120282E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.823122E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306891E+09 |
February | 0.649041E+09 | 0.701011E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.437515E+09 |
March | 0.773965E+09 | 0.796372E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260124E+09 |
April | 0.688021E+09 | 0.691254E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.346928E+09 |
May | 0.744847E+09 | 0.730747E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.828996E+09 |
June | 0.742030E+09 | 0.721412E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 364131.89 | 0.641572E+09 |
July | 0.690839E+09 | 0.678754E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945016.52 | 0.621581E+09 |
August | 0.773965E+09 | 0.765670E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 237978.97 | 0.450650E+09 |
September | 0.688021E+09 | 0.700006E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.474824E+09 |
October | 0.715730E+09 | 0.766378E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475324E+09 |
November | 0.708685E+09 | 0.810942E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561928E+09 |
December | 0.690839E+09 | 0.831350E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.754010E+09 |
Annual Sum or Average | 0.858171E+10 | 0.901702E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2547127.39 | 0.616034E+10 |
Minimum of Months | 0.649041E+09 | 0.678754E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260124E+09 |
Maximum of Months | 0.773965E+09 | 0.831350E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1945016.52 | 0.828996E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.126543E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.492506E+09 |
February | 0.136988E+10 | 0.108092E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.697657E+09 |
March | 0.163688E+10 | 0.123246E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402511E+09 |
April | 0.145246E+10 | 0.107410E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.534699E+09 |
May | 0.157341E+10 | 0.113535E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125325E+10 |
June | 0.156904E+10 | 0.112034E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 546217.41 | 0.961515E+09 |
July | 0.145684E+10 | 0.105437E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2786036.69 | 0.933867E+09 |
August | 0.163688E+10 | 0.118943E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 356976.66 | 0.696087E+09 |
September | 0.145246E+10 | 0.108829E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.742470E+09 |
October | 0.150994E+10 | 0.118622E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.760088E+09 |
November | 0.149520E+10 | 0.124760E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892209E+09 |
December | 0.145684E+10 | 0.127762E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117266E+10 |
Annual Sum or Average | 0.181198E+11 | 0.139521E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 3689230.76 | 0.953951E+10 |
Minimum of Months | 0.136988E+10 | 0.105437E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402511E+09 |
Maximum of Months | 0.163688E+10 | 0.127762E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2786036.69 | 0.125325E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.827730E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.314034E+09 |
February | 0.882782E+09 | 0.702395E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451117E+09 |
March | 0.105485E+10 | 0.798076E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264576E+09 |
April | 0.936002E+09 | 0.692140E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.352832E+09 |
May | 0.101394E+10 | 0.730640E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.855235E+09 |
June | 0.101113E+10 | 0.720681E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 364120.95 | 0.669936E+09 |
July | 0.938820E+09 | 0.678215E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1493653.12 | 0.651543E+09 |
August | 0.105485E+10 | 0.766358E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 238000.90 | 0.473582E+09 |
September | 0.936002E+09 | 0.703827E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.478738E+09 |
October | 0.973041E+09 | 0.771078E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488245E+09 |
November | 0.963541E+09 | 0.814295E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.576757E+09 |
December | 0.938820E+09 | 0.839493E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.774374E+09 |
Annual Sum or Average | 0.116768E+11 | 0.904493E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2095774.97 | 0.635097E+10 |
Minimum of Months | 0.882782E+09 | 0.678215E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264576E+09 |
Maximum of Months | 0.105485E+10 | 0.839493E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1493653.12 | 0.855235E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.130075E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508259E+09 |
February | 0.136985E+10 | 0.109789E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721180E+09 |
March | 0.163685E+10 | 0.123846E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438177E+09 |
April | 0.145243E+10 | 0.107258E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.566567E+09 |
May | 0.157338E+10 | 0.113208E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139321E+10 |
June | 0.156900E+10 | 0.111699E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630077.43 | 0.111793E+10 |
July | 0.145680E+10 | 0.105084E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3191200.74 | 0.106248E+10 |
August | 0.163685E+10 | 0.118676E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415513.83 | 0.767875E+09 |
September | 0.145243E+10 | 0.109006E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762221E+09 |
October | 0.150991E+10 | 0.119951E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766584E+09 |
November | 0.149516E+10 | 0.127916E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925683E+09 |
December | 0.145680E+10 | 0.132288E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127256E+10 |
Annual Sum or Average | 0.181194E+11 | 0.140880E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4236792.01 | 0.103027E+11 |
Minimum of Months | 0.136985E+10 | 0.105084E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.438177E+09 |
Maximum of Months | 0.163685E+10 | 0.132288E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3191200.74 | 0.139321E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.823123E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.342090E+09 |
February | 0.882782E+09 | 0.701008E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488864E+09 |
March | 0.105485E+10 | 0.796371E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296567E+09 |
April | 0.936002E+09 | 0.691255E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404880E+09 |
May | 0.101394E+10 | 0.730734E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.976331E+09 |
June | 0.101113E+10 | 0.721410E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 420044.43 | 0.771371E+09 |
July | 0.938820E+09 | 0.678756E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2160416.54 | 0.750817E+09 |
August | 0.105485E+10 | 0.765671E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277008.51 | 0.546356E+09 |
September | 0.936002E+09 | 0.700027E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555476E+09 |
October | 0.973041E+09 | 0.766371E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.529714E+09 |
November | 0.963541E+09 | 0.810886E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623845E+09 |
December | 0.938820E+09 | 0.831299E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850656E+09 |
Annual Sum or Average | 0.116768E+11 | 0.901691E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2857469.47 | 0.713697E+10 |
Minimum of Months | 0.882782E+09 | 0.678756E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296567E+09 |
Maximum of Months | 0.105485E+10 | 0.831299E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2160416.54 | 0.976331E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.126544E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543889E+09 |
February | 0.136988E+10 | 0.108092E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.780064E+09 |
March | 0.163688E+10 | 0.123245E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456872E+09 |
April | 0.145246E+10 | 0.107410E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.623507E+09 |
May | 0.157341E+10 | 0.113535E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146914E+10 |
June | 0.156904E+10 | 0.112034E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 630062.28 | 0.114904E+10 |
July | 0.145684E+10 | 0.105437E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3140565.22 | 0.111910E+10 |
August | 0.163688E+10 | 0.118943E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 415515.80 | 0.839289E+09 |
September | 0.145246E+10 | 0.108830E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.870451E+09 |
October | 0.150994E+10 | 0.118621E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.854933E+09 |
November | 0.149520E+10 | 0.124758E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.988380E+09 |
December | 0.145684E+10 | 0.127762E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131035E+10 |
Annual Sum or Average | 0.181198E+11 | 0.139521E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 4186143.30 | 0.110050E+11 |
Minimum of Months | 0.136988E+10 | 0.105437E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456872E+09 |
Maximum of Months | 0.163688E+10 | 0.127762E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3140565.22 | 0.146914E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.827812E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353273E+09 |
February | 0.882782E+09 | 0.702393E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.512906E+09 |
March | 0.105485E+10 | 0.798028E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304784E+09 |
April | 0.936002E+09 | 0.692156E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.411578E+09 |
May | 0.101394E+10 | 0.730649E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100969E+10 |
June | 0.101113E+10 | 0.720681E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 419998.83 | 0.805226E+09 |
July | 0.938820E+09 | 0.678213E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1760552.46 | 0.784097E+09 |
August | 0.105485E+10 | 0.766359E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 277025.47 | 0.570905E+09 |
September | 0.936002E+09 | 0.703835E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559051E+09 |
October | 0.973041E+09 | 0.771074E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.552455E+09 |
November | 0.963541E+09 | 0.814278E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.651015E+09 |
December | 0.938820E+09 | 0.839481E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.879295E+09 |
Annual Sum or Average | 0.116768E+11 | 0.904496E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 2457576.76 | 0.739428E+10 |
Minimum of Months | 0.882782E+09 | 0.678213E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304784E+09 |
Maximum of Months | 0.105485E+10 | 0.839481E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1760552.46 | 0.100969E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.476643E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.669880E+09 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390329E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488670E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116526E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297552.25 | 0.890415E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2049155.47 | 0.861219E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201620.27 | 0.632388E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668321E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721475E+09 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.897701E+09 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122392E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2548327.99 | 0.908622E+10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390329E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2049155.47 | 0.122392E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.789297E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.113222E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659583E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841400E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203103E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556128.37 | 0.155623E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3849595.10 | 0.148934E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 395369.31 | 0.109761E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116363E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122822E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149068E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198665E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4801092.78 | 0.154659E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.659583E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3849595.10 | 0.203103E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.777171E+09 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112245E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683852E+09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.923804E+09 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222454E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171905.21 | 0.176299E+10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2516434.20 | 0.169347E+10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 209195.18 | 0.123493E+10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124251E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122693E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144492E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194125E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2897534.59 | 0.162788E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.683852E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2516434.20 | 0.222454E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 741.69 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 1676.34 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 669.85 | 08-FEB-22:10 |
March | 2010.79 | 01-MAR-10:09 | 1551.92 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 693.93 | 27-MAR-22:00 |
April | 2010.79 | 03-APR-09:09 | 1392.21 | 10-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 760.00 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 22-MAY-15:00 | 1091.38 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 756.79 | 05-JUN-22:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 22-JUL-17:01 | 689.42 | 11-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1225.05 | 22-AUG-07:30 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 517.18 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1308.70 | 08-SEP-07:30 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 677.63 | 06-SEP-04:00 |
October | 2010.79 | 02-OCT-09:09 | 1743.29 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 853.33 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 907.15 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-15:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1324.33 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.18 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 58.72 | 1324.33 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 490.52 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1076.92 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 430.97 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 978.80 | 15-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 447.37 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 861.78 | 10-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 490.14 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 712.35 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 545.89 | 18-JUN-11:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 22-JUL-19:10 | 453.85 | 30-JUL-18:30 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.16 | 14-AUG-16:50 | 326.50 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 788.09 | 08-SEP-07:30 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 451.63 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1123.22 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 546.14 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 579.42 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-15:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 841.70 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.50 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 | 841.70 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 722.09 | 08-JAN-08:00 |
February | 2010.83 | 01-FEB-10:09 | 1672.94 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 678.20 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1542.89 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 662.64 | 27-MAR-22:00 |
April | 2010.83 | 03-APR-09:09 | 1386.38 | 10-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 729.38 | 23-APR-22:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 22-MAY-15:00 | 1064.86 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 18.13 | 13-JUN-15:30 | 770.36 | 18-JUN-12:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 61.97 | 22-JUL-18:52 | 717.84 | 30-JUL-18:30 |
August | 2010.83 | 01-AUG-09:09 | 1215.49 | 22-AUG-07:30 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.74 | 14-AUG-16:50 | 527.43 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1282.58 | 08-SEP-07:30 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 670.00 | 06-SEP-04:00 |
October | 2010.83 | 02-OCT-09:09 | 1743.06 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 836.37 | 20-OCT-22:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 847.06 | 25-NOV-05:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-15:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1282.82 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.43 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 61.97 | 1282.82 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 519.11 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1081.04 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 477.97 | 08-FEB-22:10 |
March | 1295.83 | 01-MAR-10:09 | 1010.34 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 501.62 | 27-MAR-22:00 |
April | 1295.83 | 03-APR-09:09 | 915.17 | 10-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 571.80 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22-MAY-15:00 | 766.92 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 12.09 | 13-JUN-15:30 | 601.87 | 18-JUN-16:30 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 22-JUL-19:06 | 604.19 | 30-JUL-18:30 |
August | 1295.83 | 01-AUG-09:09 | 829.07 | 22-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 9.14 | 14-AUG-16:50 | 394.09 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 923.52 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 478.33 | 06-SEP-04:00 |
October | 1295.83 | 02-OCT-09:09 | 1123.48 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 625.53 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 671.46 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-15:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 975.54 | 02-DEC-18:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 394.09 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 30.09 | 975.54 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1474.48 | 08-JAN-08:00 |
February | 2010.79 | 01-FEB-10:09 | 1678.55 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1447.34 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1557.89 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1442.70 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1402.88 | 10-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1505.08 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 2307.39 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1648.53 | 05-JUN-21:13 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 146.23 | 22-JUL-18:52 | 1454.89 | 11-JUL-02:00 |
August | 2010.79 | 01-AUG-09:09 | 1240.46 | 22-AUG-07:30 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 14-AUG-16:50 | 1103.17 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1321.76 | 08-SEP-07:30 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1414.38 | 06-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 1743.49 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1709.74 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1689.71 | 25-NOV-05:00 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-15:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2686.61 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1103.17 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 146.23 | 2686.61 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1127.77 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 990.10 | 08-JAN-08:00 |
February | 1239.33 | 01-FEB-08:09 | 1077.40 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 963.67 | 08-FEB-22:03 |
March | 1239.33 | 01-MAR-08:09 | 980.72 | 15-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 960.52 | 27-MAR-21:03 |
April | 1239.33 | 03-APR-07:10 | 865.39 | 10-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1010.25 | 23-APR-22:00 |
May | 1239.33 | 01-MAY-07:10 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1508.38 | 04-MAY-23:00 |
June | 1239.33 | 01-JUN-07:10 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 13-JUN-15:40 | 1260.58 | 18-JUN-10:55 |
July | 1239.33 | 03-JUL-07:10 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 110.74 | 22-JUL-19:10 | 990.72 | 30-JUL-18:40 |
August | 1239.33 | 01-AUG-07:10 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.65 | 14-AUG-16:50 | 721.67 | 22-AUG-21:10 |
September | 1239.33 | 01-SEP-07:10 | 792.06 | 08-SEP-07:30 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 967.55 | 06-SEP-03:55 |
October | 1239.33 | 02-OCT-07:10 | 1123.26 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1119.02 | 20-OCT-22:00 |
November | 1239.33 | 01-NOV-07:10 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1109.72 | 25-NOV-05:00 |
December | 1239.33 | 01-DEC-08:09 | 1127.77 | 01-DEC-15:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1770.46 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 721.67 | |||||
Maximum of Months | 1239.33 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 110.74 | 1770.46 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1561.86 | 08-JAN-08:00 |
February | 2010.83 | 01-FEB-10:09 | 1675.32 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1508.59 | 05-FEB-14:00 |
March | 2010.83 | 01-MAR-10:09 | 1549.27 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1443.16 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1397.26 | 10-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1613.23 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 2298.36 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.51 | 13-JUN-15:40 | 1820.87 | 18-JUN-15:53 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 149.60 | 22-JUL-19:10 | 1614.10 | 30-JUL-18:40 |
August | 2010.83 | 01-AUG-09:09 | 1231.20 | 22-AUG-07:30 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 30.98 | 14-AUG-16:50 | 1156.47 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1296.64 | 08-SEP-07:30 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1463.87 | 06-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 1743.27 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1843.20 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1716.05 | 26-NOV-04:00 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-15:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2728.96 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.47 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 149.60 | 2728.96 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1015.21 | 08-JAN-08:00 |
February | 1295.83 | 01-FEB-10:09 | 1081.40 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 970.77 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1011.24 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 964.47 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 916.79 | 10-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1029.35 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1559.56 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 27.01 | 13-JUN-15:40 | 1327.98 | 18-JUN-16:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 | 22-JUL-19:06 | 1336.28 | 30-JUL-18:40 |
August | 1295.83 | 01-AUG-09:09 | 831.20 | 22-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 20.66 | 14-AUG-16:50 | 814.71 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 924.94 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 970.04 | 06-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1123.51 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1183.09 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1150.44 | 25-NOV-05:00 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-15:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1817.26 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 814.71 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 66.53 | 1817.26 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-08:09 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1630.86 | 10-JAN-05:52 |
February | 2010.79 | 01-FEB-10:09 | 1678.48 | 01-FEB-08:09 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1786.52 | 08-FEB-22:03 |
March | 2010.79 | 01-MAR-10:09 | 1557.72 | 15-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1776.67 | 27-MAR-21:03 |
April | 2010.79 | 03-APR-09:09 | 1402.54 | 10-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1611.49 | 23-APR-22:00 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 2595.26 | 04-MAY-23:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 13-JUN-15:50 | 1963.05 | 05-JUN-21:10 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 160.13 | 22-JUL-17:01 | 1774.87 | 30-JUL-19:00 |
August | 2010.79 | 01-AUG-09:09 | 1239.98 | 22-AUG-07:30 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 14-AUG-16:50 | 1315.93 | 22-AUG-21:10 |
September | 2010.79 | 01-SEP-09:09 | 1321.35 | 08-SEP-07:30 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1559.83 | 06-SEP-03:55 |
October | 2010.79 | 02-OCT-09:09 | 1743.49 | 31-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1915.27 | 20-OCT-22:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2133.21 | 25-NOV-05:10 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-15:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3125.83 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1315.93 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 160.13 | 3125.83 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1106.31 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1077.36 | 01-FEB-08:09 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1190.45 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 980.63 | 15-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1183.94 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 865.22 | 10-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1086.05 | 23-APR-22:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1713.81 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:50 | 1542.02 | 18-JUN-10:05 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 117.44 | 22-JUL-19:10 | 1270.22 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 14-AUG-16:50 | 868.01 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 791.87 | 08-SEP-07:30 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1081.55 | 06-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1123.25 | 31-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1266.68 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1422.15 | 25-NOV-05:05 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-15:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2066.44 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 868.01 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 117.44 | 2066.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-08:09 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1664.03 | 10-JAN-05:52 |
February | 2010.83 | 01-FEB-10:09 | 1675.24 | 01-FEB-08:09 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1793.83 | 08-FEB-22:03 |
March | 2010.83 | 01-MAR-10:09 | 1549.09 | 15-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1777.63 | 27-MAR-21:03 |
April | 2010.83 | 03-APR-09:09 | 1396.92 | 10-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1798.42 | 16-APR-12:00 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 2596.94 | 04-MAY-23:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 47.84 | 13-JUN-15:50 | 2207.39 | 18-JUN-15:53 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 164.39 | 22-JUL-19:10 | 2054.23 | 30-JUL-19:00 |
August | 2010.83 | 01-AUG-09:09 | 1230.71 | 22-AUG-07:30 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 36.92 | 14-AUG-16:50 | 1392.03 | 22-AUG-21:10 |
September | 2010.83 | 01-SEP-09:09 | 1296.23 | 08-SEP-07:30 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1633.17 | 06-SEP-03:55 |
October | 2010.83 | 02-OCT-09:09 | 1743.27 | 31-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2026.73 | 01-OCT-24:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2133.24 | 25-NOV-05:10 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-15:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3175.79 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1392.03 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 164.39 | 3175.79 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-08:09 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1109.93 | 10-JAN-05:52 |
February | 1295.83 | 01-FEB-10:09 | 1081.36 | 01-FEB-08:09 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1198.74 | 08-FEB-22:03 |
March | 1295.83 | 01-MAR-10:09 | 1011.13 | 15-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1189.77 | 27-MAR-21:03 |
April | 1295.83 | 03-APR-09:09 | 916.58 | 10-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1129.29 | 15-APR-17:07 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 1774.22 | 04-MAY-23:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 31.89 | 13-JUN-15:50 | 1614.31 | 18-JUN-16:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 79.11 | 22-JUL-19:06 | 1687.79 | 30-JUL-19:00 |
August | 1295.83 | 01-AUG-09:09 | 830.96 | 22-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 24.62 | 14-AUG-16:50 | 983.51 | 22-AUG-21:10 |
September | 1295.83 | 01-SEP-09:09 | 924.85 | 08-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1088.31 | 06-SEP-03:55 |
October | 1295.83 | 02-OCT-09:09 | 1123.51 | 31-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1347.94 | 20-OCT-22:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1441.71 | 25-NOV-05:04 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-15:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2137.78 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 983.51 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 79.11 | 2137.78 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1615.90 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1447.02 | 08-FEB-22:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 1457.49 | 27-MAR-22:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1589.48 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 2347.32 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.73 | 13-JUN-16:00 | 1576.62 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.73 | 22-JUL-18:52 | 1455.93 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.43 | 14-AUG-17:00 | 1081.48 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1461.12 | 06-SEP-04:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 1802.01 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1943.87 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2889.75 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.48 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.73 | 2889.75 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2710.05 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2473.80 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2448.53 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2680.76 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 4094.02 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.95 | 13-JUN-16:00 | 2745.02 | 05-JUN-22:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.32 | 22-JUL-18:52 | 2420.68 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.66 | 14-AUG-17:00 | 1896.38 | 22-AUG-21:10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2525.27 | 06-SEP-03:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3045.63 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3137.70 | 25-NOV-05:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4758.45 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1896.38 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.32 | 4758.45 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2409.24 | 08-JAN-08:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2633.95 | 08-FEB-22:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2590.53 | 27-MAR-21:03 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2606.59 | 23-APR-22:00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 4179.97 | 04-MAY-23:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.99 | 13-JUN-17:00 | 3333.07 | 18-JUN-15:53 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.59 | 22-JUL-18:52 | 2964.86 | 30-JUL-18:55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.96 | 14-AUG-18:00 | 2076.53 | 22-AUG-21:03 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 2470.24 | 06-SEP-03:55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3029.24 | 20-OCT-22:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2962.89 | 25-NOV-05:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5073.36 | 02-DEC-18:05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2076.53 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.59 | 5073.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 104733.76 | 02-JAN-04:11 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 105038.43 | 21-FEB-04:01 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 101816.09 | 13-MAR-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 104724.34 | 24-APR-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 107759.15 | 30-MAY-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 102801.57 | 12-JUN-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 105638.78 | 31-JUL-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 102424.20 | 14-AUG-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 102004.42 | 25-SEP-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 101099.59 | 16-OCT-03:03 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 104418.00 | 27-NOV-04:01 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 103567.98 | 04-DEC-04:01 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 101099.59 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 107759.15 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 83191.35 | 02-JAN-05:01 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82921.96 | 21-FEB-05:01 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 82729.30 | 13-MAR-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 88905.95 | 24-APR-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86273.25 | 30-MAY-03:02 | 0.00 | 4646.04 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 85810.24 | 05-JUN-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 88634.51 | 05-JUL-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 84335.06 | 31-AUG-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 86210.24 | 05-SEP-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 89593.67 | 10-OCT-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86398.12 | 13-NOV-04:03 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 85070.05 | 26-DEC-04:01 | 0.00 | 5420.38 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82729.30 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 89593.67 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 67017.15 | 26-JAN-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 48720.58 | 10-FEB-06:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68650.33 | 24-MAR-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 76109.15 | 22-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75977.17 | 03-MAY-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76191.21 | 17-JUN-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 76376.64 | 05-JUL-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 75397.87 | 17-AUG-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 76111.35 | 21-SEP-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74545.89 | 05-OCT-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 68184.94 | 09-NOV-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 24776.25 | 22-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 24776.25 | 0.00 | 6194.72 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 76376.64 | 15316.26 | 13937.56 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 18816.23 | 19-JAN-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 18648.18 | 09-FEB-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 21643.40 | 31-MAR-16:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 61971.44 | 21-APR-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 66277.79 | 24-MAY-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 72431.44 | 14-JUN-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 72282.71 | 18-JUL-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 70386.47 | 17-AUG-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 67647.32 | 13-SEP-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 30514.63 | 05-OCT-16:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 21514.39 | 10-NOV-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17755.45 | 21-DEC-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 17755.45 | 6448.95 | 6194.72 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 72431.44 | 15316.26 | 13937.56 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2773.86 | 17-JAN-06:03 | 1214.60 | 1166.71 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 |
February | 2808.91 | 21-FEB-06:03 | 1417.03 | 1361.17 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.05 |
March | 4381.61 | 20-MAR-12:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80.53 |
April | 6384.07 | 28-APR-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.56 |
May | 6440.29 | 22-MAY-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 0.00 |
June | 10489.78 | 26-JUN-05:03 | 809.73 | 477.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.91 |
July | 10284.88 | 10-JUL-05:02 | 1012.16 | 597.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.16 |
August | 7451.54 | 14-AUG-15:50 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 0.00 |
September | 5937.61 | 13-SEP-15:10 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.22 |
October | 5034.58 | 10-OCT-13:10 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 |
November | 3336.81 | 08-NOV-14:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 |
December | 2856.22 | 05-DEC-06:04 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.67 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2773.86 | 809.73 | 477.81 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 10489.78 | 2010.79 | 1361.17 | 7081.88 | 0.00 | 0.00 | 0.00 | 0.00 | 11.35 | 80.53 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3264.56 | 20-JAN-10:15 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4116.01 | 23-FEB-09:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.08 |
March | 3732.96 | 31-MAR-09:25 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.47 |
April | 18245.59 | 30-APR-07:42 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 81.89 |
May | 18072.79 | 21-MAY-08:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.99 |
June | 17123.45 | 25-JUN-09:53 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17504.31 | 23-JUL-08:12 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.72 |
August | 18787.02 | 20-AUG-08:52 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.66 |
September | 18129.89 | 04-SEP-09:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.29 |
October | 6683.61 | 03-OCT-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.63 |
November | 3917.80 | 13-NOV-09:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.23 |
December | 2343.47 | 05-DEC-06:04 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2343.47 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18787.02 | 2591.66 | 1385.57 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.99 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11763.23 | 20-JAN-12:00 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13189.60 | 17-FEB-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.17 |
March | 9232.94 | 28-MAR-12:10 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.35 |
April | 28116.23 | 30-APR-13:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.05 |
May | 13783.44 | 22-MAY-13:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.11 |
June | 15112.52 | 11-JUN-13:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 196.28 |
July | 24978.80 | 23-JUL-12:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.36 |
August | 26197.05 | 06-AUG-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 192.78 |
September | 26369.59 | 10-SEP-11:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.03 |
October | 23808.86 | 01-OCT-13:02 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.11 |
November | 22748.40 | 11-NOV-13:23 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.77 |
December | 11696.79 | 18-DEC-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.02 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9232.94 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28116.23 | 2010.83 | 1075.05 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6251.77 | 30-JAN-16:40 | 3717.98 | 2397.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 8530.73 | 27-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9234.88 | 23-MAR-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.98 |
April | 23897.35 | 30-APR-16:21 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.77 |
May | 24200.01 | 21-MAY-17:02 | 0.00 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.79 |
June | 25387.60 | 25-JUN-17:11 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 48.72 |
July | 23829.53 | 09-JUL-16:52 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.58 |
August | 23614.37 | 20-AUG-16:12 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.95 |
September | 16473.45 | 24-SEP-16:53 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.80 |
October | 10793.15 | 13-OCT-05:02 | 652.28 | 626.56 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 14339.52 | 09-NOV-06:02 | 652.28 | 626.56 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 11677.70 | 05-DEC-06:02 | 652.28 | 626.56 | 3259.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.20 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6251.77 | 0.00 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25387.60 | 3717.98 | 2397.62 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.79 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2107.02 | 26-JAN-06:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1897.28 | 08-FEB-16:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.14 |
March | 2202.93 | 24-MAR-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 4798.29 | 28-APR-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.67 |
May | 5117.92 | 23-MAY-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.94 |
June | 6854.79 | 13-JUN-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 0.00 |
July | 6588.12 | 10-JUL-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.94 |
August | 5730.05 | 14-AUG-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 28.10 | 0.00 |
September | 5128.61 | 13-SEP-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.41 |
October | 2657.52 | 01-OCT-13:53 | 404.87 | 238.90 | 3035.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.04 |
November | 2346.42 | 09-NOV-06:02 | 1012.16 | 972.26 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1731.15 | 21-DEC-16:10 | 1923.11 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1731.15 | 404.87 | 238.90 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 6854.79 | 2010.79 | 1750.00 | 5058.48 | 0.00 | 0.00 | 0.00 | 0.00 | 40.25 | 429.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2068.06 | 20-JAN-10:00 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 2186.37 | 17-FEB-10:00 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2135.43 | 30-MAR-10:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.64 |
April | 19501.95 | 30-APR-09:32 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 348.43 |
May | 10968.45 | 23-MAY-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.85 |
June | 15588.60 | 11-JUN-09:43 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 376.24 |
July | 19466.57 | 16-JUL-09:22 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.20 |
August | 18709.52 | 20-AUG-08:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.82 |
September | 14658.52 | 04-SEP-09:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.88 |
October | 5379.38 | 04-OCT-10:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.57 |
November | 2187.15 | 09-NOV-06:02 | 652.28 | 626.56 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1755.95 | 06-DEC-10:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1755.95 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19501.95 | 2478.65 | 1385.57 | 3259.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 407.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 11221.46 | 20-JAN-12:00 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 13866.89 | 17-FEB-13:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.98 |
March | 7638.42 | 28-MAR-12:10 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 230.32 |
April | 29023.15 | 30-APR-13:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.76 |
May | 13759.53 | 22-MAY-13:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.76 |
June | 13178.46 | 13-JUN-13:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 0.00 |
July | 24690.80 | 23-JUL-12:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 297.82 |
August | 26486.46 | 20-AUG-13:43 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.90 |
September | 27902.45 | 24-SEP-13:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.91 |
October | 26201.62 | 01-OCT-13:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.22 |
November | 15527.34 | 11-NOV-12:53 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 816.51 |
December | 9469.72 | 18-DEC-13:30 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.97 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7638.42 | 303.66 | 179.18 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 29023.15 | 2010.83 | 1075.05 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3.25 | 816.51 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3052.90 | 19-JAN-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5112.30 | 27-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5345.67 | 23-MAR-17:00 | 391.37 | 384.88 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.29 |
April | 20677.28 | 30-APR-16:11 | 587.05 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.09 |
May | 17507.68 | 21-MAY-18:42 | 0.00 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.90 |
June | 21382.97 | 11-JUN-16:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.21 |
July | 20895.18 | 09-JUL-17:21 | 0.00 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.89 |
August | 20364.60 | 13-AUG-17:01 | 0.00 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.32 |
September | 15461.58 | 24-SEP-16:42 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.51 |
October | 7573.83 | 03-OCT-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.69 |
November | 3251.17 | 10-NOV-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.20 |
December | 2062.80 | 21-DEC-14:50 | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.13 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2062.80 | 0.00 | 153.96 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21382.97 | 1295.83 | 692.79 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1773.48 | 19-JAN-15:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1663.67 | 09-FEB-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.99 |
March | 1991.48 | 30-MAR-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.31 |
April | 4968.01 | 28-APR-15:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.66 |
May | 5653.86 | 22-MAY-15:50 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.33 |
June | 7704.33 | 13-JUN-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 0.00 |
July | 7299.23 | 10-JUL-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.82 |
August | 6141.35 | 14-AUG-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 32.87 | 0.00 |
September | 5225.81 | 13-SEP-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.02 |
October | 2244.82 | 06-OCT-16:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 109.08 |
November | 1885.08 | 10-NOV-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.53 |
December | 1544.32 | 21-DEC-16:00 | 1923.11 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1544.32 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7704.33 | 1923.11 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 47.70 | 268.31 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 1759.30 | 20-JAN-10:30 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1849.83 | 24-FEB-10:35 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.98 |
March | 1837.48 | 30-MAR-10:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.74 |
April | 18398.57 | 30-APR-09:53 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 356.04 |
May | 10696.74 | 23-MAY-09:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.48 |
June | 15270.73 | 25-JUN-10:43 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 114.11 |
July | 18603.91 | 23-JUL-09:32 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 221.87 |
August | 18389.30 | 20-AUG-08:52 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.15 |
September | 9062.79 | 12-SEP-09:30 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.54 |
October | 4011.74 | 04-OCT-10:00 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 1716.78 | 10-NOV-15:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.90 |
December | 1472.12 | 06-DEC-10:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1472.12 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18603.91 | 2591.66 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 372.15 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8315.56 | 20-JAN-12:00 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 11554.74 | 17-FEB-14:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.87 |
March | 5443.45 | 10-MAR-14:40 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.31 |
April | 28062.69 | 30-APR-13:12 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.81 |
May | 14295.38 | 22-MAY-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.86 |
June | 14345.20 | 25-JUN-16:02 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.50 |
July | 27241.26 | 23-JUL-13:32 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.47 |
August | 27645.65 | 06-AUG-13:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 594.39 |
September | 28905.71 | 10-SEP-14:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 563.41 |
October | 18155.09 | 01-OCT-13:53 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.27 |
November | 8796.18 | 03-NOV-12:50 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.56 |
December | 6311.77 | 18-DEC-13:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5443.45 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 28905.71 | 2010.83 | 1075.05 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 778.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2408.28 | 19-JAN-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3977.98 | 27-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 4362.91 | 23-MAR-17:00 | 391.37 | 384.88 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.99 |
April | 20907.79 | 30-APR-17:12 | 0.00 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.15 |
May | 22075.84 | 21-MAY-17:12 | 0.00 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.96 |
June | 23283.98 | 25-JUN-17:21 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.04 |
July | 23269.49 | 09-JUL-17:11 | 0.00 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 350.77 |
August | 21450.78 | 06-AUG-16:32 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.21 |
September | 12026.68 | 24-SEP-16:53 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.01 |
October | 6915.33 | 03-OCT-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.99 |
November | 2443.56 | 10-NOV-15:50 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 116.91 |
December | 1952.00 | 21-DEC-14:50 | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.33 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1952.00 | 0.00 | 153.96 | 814.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 23283.98 | 1295.83 | 692.79 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 358.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3766.79 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3616.29 | 11-FEB-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 124.18 |
March | 4047.92 | 14-MAR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7073.64 | 24-APR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.68 |
May | 7613.08 | 01-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.49 |
June | 7614.01 | 26-JUN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.68 |
July | 8725.15 | 17-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.23 |
August | 8040.18 | 07-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 54.23 |
September | 6101.01 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 187.66 |
October | 7216.05 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 4855.43 | 13-NOV-06:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.55 |
December | 3355.46 | 21-DEC-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 325.95 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3355.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8725.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.49 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3663.39 | 09-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4636.37 | 18-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.31 |
March | 3613.81 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.77 |
April | 4270.58 | 22-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 4324.13 | 03-MAY-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.19 |
June | 4648.03 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 | 0.00 |
July | 5620.27 | 25-JUL-05:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.21 |
August | 4520.83 | 18-AUG-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.05 |
September | 4462.16 | 14-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4028.00 | 05-OCT-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 289.19 |
November | 4215.97 | 17-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 505.60 |
December | 5082.34 | 26-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2082.04 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3613.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 5620.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.28 | 2082.04 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 169.85 | 21-JAN-13:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.39 |
February | 516.90 | 22-FEB-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.86 |
March | 2716.92 | 25-MAR-12:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.50 |
April | 12693.19 | 28-APR-14:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 94.91 |
May | 13486.57 | 22-MAY-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.60 |
June | 15858.88 | 13-JUN-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.06 |
July | 15378.64 | 21-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 0.00 |
August | 13403.32 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.39 |
September | 11364.62 | 12-SEP-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.85 |
October | 4168.29 | 03-OCT-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 301.36 |
November | 261.79 | 04-NOV-16:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.81 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 593.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15858.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.55 | 593.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1928.69 | 19-JAN-16:20 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4056.77 | 27-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7028.40 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8121.94 | 30-APR-17:54 | 0.00 | 112.53 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3368.83 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5204.77 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7264.11 | 31-JUL-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8098.39 | 13-AUG-18:10 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3254.43 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5088.79 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5717.02 | 03-NOV-16:00 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7463.58 | 18-DEC-15:20 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1928.69 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8121.94 | 222.14 | 405.10 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1689.93 | 19-JAN-16:30 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3641.91 | 27-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6256.79 | 31-MAR-23:50 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7725.42 | 30-APR-17:54 | 0.00 | 112.53 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3060.88 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4706.65 | 30-JUN-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6813.23 | 31-JUL-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7510.53 | 13-AUG-18:10 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2851.92 | 30-SEP-23:40 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4330.42 | 31-OCT-24:00 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5287.96 | 10-NOV-16:20 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6773.59 | 21-DEC-15:20 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1689.93 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7725.42 | 222.14 | 405.10 | 38972.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 1505.49 | 19-JAN-16:30 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3434.55 | 09-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5713.08 | 31-MAR-23:20 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7836.61 | 30-APR-18:03 | 0.00 | 135.04 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 2889.65 | 31-MAY-23:20 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 4440.45 | 30-JUN-23:20 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6659.00 | 31-JUL-23:30 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7548.60 | 13-AUG-18:10 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2282.01 | 30-SEP-23:20 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 3722.82 | 31-OCT-23:20 | 0.00 | 22.51 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5171.27 | 10-NOV-16:20 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6474.81 | 21-DEC-15:20 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 1505.49 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7836.61 | 222.14 | 405.10 | 46766.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91170.55 | 19-JAN-17:00 | 4808.68 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 182631.94 | 09-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 358474.01 | 31-MAR-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 368981.09 | 30-APR-19:43 | 0.00 | 729.33 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175690.83 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267076.30 | 30-JUN-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 359774.43 | 31-JUL-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 367772.27 | 15-AUG-16:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 175385.27 | 30-SEP-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 267241.64 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 275298.31 | 13-NOV-17:00 | 4808.68 | 4375.82 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366753.06 | 26-DEC-17:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91170.55 | 0.00 | 243.11 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 368981.09 | 4808.68 | 4375.82 | 1138897.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.153439E+13 | 974913.88 | 24-JAN-16:00 | 0.356453E+12 | 755699.03 | 10-JAN-07:00 |
February | 0.173769E+13 | 1081620.06 | 07-FEB-16:00 | 0.259587E+12 | 643268.07 | 17-FEB-07:10 |
March | 0.235969E+13 | 1231687.10 | 31-MAR-15:00 | 0.211400E+12 | 448098.66 | 27-MAR-06:10 |
April | 0.268370E+13 | 1641229.25 | 28-APR-14:00 | 0.817288E+11 | 303582.32 | 08-APR-06:19 |
May | 0.158478E+13 | 1230308.85 | 22-MAY-15:09 | 0.727331E+11 | 226060.57 | 06-MAY-06:10 |
June | 0.201983E+13 | 1482556.26 | 13-JUN-15:30 | 0.621515E+11 | 79812.18 | 01-JUN-11:50 |
July | 0.249632E+13 | 1594625.72 | 21-JUL-15:20 | 0.592985E+11 | 78827.59 | 05-JUL-11:30 |
August | 0.297599E+13 | 1732817.37 | 14-AUG-15:09 | 0.629772E+11 | 78364.06 | 03-AUG-11:00 |
September | 0.160395E+13 | 1252338.64 | 13-SEP-15:20 | 0.598485E+11 | 162243.40 | 21-SEP-06:10 |
October | 0.196012E+13 | 1195819.11 | 06-OCT-15:20 | 0.993348E+11 | 329049.17 | 23-OCT-06:40 |
November | 0.227282E+13 | 1279649.91 | 07-NOV-16:49 | 0.210354E+12 | 567982.87 | 29-NOV-07:30 |
December | 0.270598E+13 | 1420341.24 | 20-DEC-16:19 | 0.393140E+12 | 627048.07 | 26-DEC-07:00 |
Annual Sum or Average | 0.259353E+14 | 0.192901E+13 | ||||
Minimum of Months | 0.153439E+13 | 974913.88 | 0.592985E+11 | 78364.06 | ||
Maximum of Months | 0.297599E+13 | 1732817.37 | 0.393140E+12 | 755699.03 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.234082E+12 | 0.522430E+11 | 0.811612E+12 | 0.162551E+12 | 0.162283E+12 | 0.111221E+11 | 0.00 | 0.873062E+11 | 0.120892E+11 | 0.110438E+10 | 0.00 | 0.00 | 0.00 |
February | 0.209416E+12 | 0.420078E+11 | 0.102011E+13 | 0.146827E+12 | 0.148042E+12 | 0.115508E+11 | 0.00 | 0.141275E+12 | 0.177518E+11 | 0.716047E+09 | 0.00 | 0.00 | 0.00 |
March | 0.246550E+12 | 0.394026E+11 | 0.146267E+13 | 0.162740E+12 | 0.167965E+12 | 0.129732E+11 | 0.00 | 0.220991E+12 | 0.454780E+11 | 0.926632E+09 | 0.00 | 0.00 | 0.00 |
April | 0.219007E+12 | 0.309510E+11 | 0.170311E+13 | 0.157288E+12 | 0.186584E+12 | 0.162278E+11 | 0.00 | 0.285018E+12 | 0.848998E+11 | 0.615721E+09 | 0.00 | 0.00 | 0.00 |
May | 0.235370E+12 | 0.264821E+11 | 0.820521E+12 | 0.162644E+12 | 0.190965E+12 | 0.166511E+11 | 0.00 | 0.103021E+12 | 0.290352E+11 | 94320409.47 | 0.00 | 0.00 | 0.00 |
June | 0.233856E+12 | 0.229421E+11 | 0.110677E+13 | 0.157466E+12 | 0.203056E+12 | 0.269043E+11 | 0.00 | 0.185492E+12 | 0.833401E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.219115E+12 | 0.246715E+11 | 0.143888E+13 | 0.162465E+12 | 0.213496E+12 | 0.403682E+11 | 0.00 | 0.279235E+12 | 0.118089E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.244666E+12 | 0.292347E+11 | 0.177780E+13 | 0.162739E+12 | 0.225085E+12 | 0.465174E+11 | 0.00 | 0.361179E+12 | 0.128768E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.219632E+12 | 0.350130E+11 | 0.784732E+12 | 0.157287E+12 | 0.197303E+12 | 0.314028E+11 | 0.00 | 0.121543E+12 | 0.570060E+11 | 27316696.05 | 0.00 | 0.00 | 0.00 |
October | 0.230557E+12 | 0.435549E+11 | 0.112899E+13 | 0.162551E+12 | 0.174489E+12 | 0.126935E+11 | 0.00 | 0.160608E+12 | 0.465668E+11 | 0.110197E+09 | 0.00 | 0.00 | 0.00 |
November | 0.231150E+12 | 0.485981E+11 | 0.140306E+13 | 0.157363E+12 | 0.159308E+12 | 0.114994E+11 | 0.00 | 0.212262E+12 | 0.491608E+11 | 0.422562E+09 | 0.00 | 0.00 | 0.00 |
December | 0.228818E+12 | 0.539807E+11 | 0.175516E+13 | 0.162468E+12 | 0.161522E+12 | 0.108197E+11 | 0.00 | 0.278046E+12 | 0.540806E+11 | 0.108442E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.275222E+13 | 0.449082E+12 | 0.152134E+14 | 0.191439E+13 | 0.219010E+13 | 0.248730E+12 | 0.00 | 0.243598E+13 | 0.726265E+12 | 0.510159E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.209416E+12 | 0.229421E+11 | 0.784732E+12 | 0.146827E+12 | 0.148042E+12 | 0.108197E+11 | 0.00 | 0.873062E+11 | 0.120892E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.246550E+12 | 0.539807E+11 | 0.177780E+13 | 0.162740E+12 | 0.225085E+12 | 0.465174E+11 | 0.00 | 0.361179E+12 | 0.128768E+12 | 0.110438E+10 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.291735E+12 | 0.00 | 0.647172E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.200560E+12 | 0.00 | 0.590263E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.143351E+12 | 0.00 | 0.680489E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.199194E+11 | 0.00 | 0.618094E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.857143E+10 | 0.00 | 0.641617E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.221416E+09 | 0.00 | 0.619301E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 20279821.61 | 0.00 | 0.592782E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 1263621.09 | 0.00 | 0.629759E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.140558E+10 | 0.00 | 0.584429E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.380760E+11 | 0.00 | 0.612589E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.149228E+12 | 0.00 | 0.611258E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.330476E+12 | 0.00 | 0.626642E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.118357E+13 | 0.00 | 0.745439E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 1263621.09 | 0.00 | 0.584429E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.330476E+12 | 0.00 | 0.680489E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 261074.09 | 02-JAN-08:09 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117204.73 | 02-JAN-08:20 | 99355.40 | 20-JAN-11:00 | 28426.70 | 09-JAN-06:10 | 0.00 | 01-JAN-00:10 |
February | 258153.70 | 01-FEB-08:09 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117203.06 | 01-FEB-08:20 | 101636.85 | 09-FEB-14:00 | 28380.24 | 13-FEB-06:10 | 0.00 | 01-FEB-00:10 |
March | 253180.95 | 15-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117200.23 | 15-MAR-07:19 | 102771.78 | 23-MAR-15:00 | 28375.74 | 07-MAR-06:10 | 0.00 | 01-MAR-00:10 |
April | 246967.20 | 10-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117196.69 | 10-APR-07:19 | 208060.85 | 28-APR-14:00 | 48432.31 | 28-APR-14:00 | 0.00 | 01-APR-00:10 |
May | 234435.00 | 01-MAY-07:10 | 37611.08 | 01-MAY-19:19 | 439129.89 | 01-MAY-07:10 | 117189.56 | 01-MAY-07:19 | 182190.00 | 23-MAY-15:20 | 46255.99 | 22-MAY-15:50 | 0.00 | 01-MAY-00:10 |
June | 234435.00 | 01-JUN-07:10 | 37611.08 | 01-JUN-19:00 | 557421.28 | 01-JUN-07:10 | 117189.56 | 01-JUN-07:19 | 216449.11 | 13-JUN-15:30 | 48177.86 | 20-JUN-14:00 | 0.00 | 01-JUN-00:10 |
July | 234435.00 | 03-JUL-07:10 | 37611.08 | 01-JUL-20:19 | 675712.68 | 03-JUL-07:10 | 117189.56 | 03-JUL-07:19 | 213195.63 | 21-JUL-15:20 | 47467.54 | 06-JUL-14:09 | 0.00 | 01-JUL-00:10 |
August | 239839.72 | 22-AUG-07:30 | 37611.08 | 01-AUG-19:49 | 794004.08 | 01-AUG-07:10 | 117192.64 | 22-AUG-07:40 | 207410.17 | 14-AUG-15:20 | 48396.76 | 21-AUG-12:09 | 0.00 | 01-AUG-00:10 |
September | 243290.08 | 08-SEP-07:30 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117194.60 | 08-SEP-07:40 | 211011.68 | 12-SEP-15:20 | 45571.42 | 12-SEP-14:50 | 0.00 | 01-SEP-00:10 |
October | 260809.14 | 31-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117204.58 | 31-OCT-07:19 | 152728.95 | 03-OCT-14:50 | 28429.91 | 06-OCT-15:30 | 0.00 | 01-OCT-00:10 |
November | 261074.09 | 06-NOV-16:49 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117204.60 | 02-NOV-07:19 | 103603.54 | 10-NOV-13:30 | 28415.58 | 20-NOV-06:10 | 0.00 | 01-NOV-00:10 |
December | 261074.09 | 01-DEC-15:30 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117204.73 | 27-DEC-08:20 | 88312.36 | 21-DEC-14:09 | 28464.94 | 26-DEC-06:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 234435.00 | 37611.08 | 439129.89 | 117189.56 | 88312.36 | 28375.74 | 0.00 | |||||||
Maximum of Months | 261074.09 | 37611.08 | 794004.08 | 117204.73 | 216449.11 | 48432.31 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 36550.94 | 20-JAN-16:30 | 18351.13 | 29-JAN-05:00 | 5914.43 | 10-JAN-20:00 | 0.00 | 0.00 | 0.00 |
February | 62550.53 | 24-FEB-16:00 | 20969.28 | 07-FEB-14:00 | 3659.66 | 17-FEB-20:00 | 0.00 | 0.00 | 0.00 |
March | 105239.08 | 31-MAR-23:00 | 45871.58 | 25-MAR-12:00 | 3493.66 | 03-MAR-21:49 | 0.00 | 0.00 | 0.00 |
April | 267055.30 | 28-APR-14:00 | 51486.72 | 28-APR-14:00 | 3251.78 | 14-APR-11:00 | 0.00 | 0.00 | 0.00 |
May | 186851.97 | 22-MAY-15:50 | 76172.40 | 22-MAY-14:30 | 2578.69 | 06-MAY-16:10 | 0.00 | 0.00 | 0.00 |
June | 277043.21 | 13-JUN-15:00 | 76172.40 | 12-JUN-13:39 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 293013.86 | 21-JUL-15:39 | 76172.40 | 10-JUL-08:50 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 314554.22 | 14-AUG-15:09 | 76172.40 | 14-AUG-10:20 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 192838.09 | 13-SEP-13:30 | 76172.40 | 11-SEP-13:30 | 1372.84 | 30-SEP-11:09 | 0.00 | 0.00 | 0.00 |
October | 103932.09 | 07-OCT-14:00 | 49418.59 | 11-OCT-14:00 | 2542.22 | 07-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 95433.58 | 24-NOV-11:00 | 49248.27 | 24-NOV-11:20 | 3626.25 | 28-NOV-20:00 | 0.00 | 0.00 | 0.00 |
December | 106586.21 | 16-DEC-05:30 | 47340.87 | 23-DEC-10:00 | 4696.10 | 29-DEC-20:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 36550.94 | 18351.13 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 314554.22 | 76172.40 | 5914.43 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 974913.88 | 24-JAN-16:00 | 261074.09 | 439129.89 | 37611.08 | 83160.46 | 84397.37 | 28315.94 | 0.00 | 35902.40 | 5322.66 |
February | 1081620.06 | 07-FEB-16:00 | 255694.06 | 557421.28 | 0.00 | 83157.22 | 82485.69 | 28318.25 | 0.00 | 60506.03 | 14037.52 |
March | 1231687.10 | 31-MAR-15:00 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 98851.14 | 28318.51 | 0.00 | 86157.74 | 25065.85 |
April | 1641229.25 | 28-APR-14:00 | 234435.00 | 794004.08 | 0.00 | 37754.99 | 208060.85 | 48432.31 | 0.00 | 267055.30 | 51486.72 |
May | 1230308.85 | 22-MAY-15:09 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 176144.45 | 44607.06 | 0.00 | 176673.87 | 76172.40 |
June | 1482556.26 | 13-JUN-15:30 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 216449.11 | 45013.99 | 0.00 | 269918.31 | 76172.40 |
July | 1594625.72 | 21-JUL-15:20 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 213195.63 | 45402.12 | 0.00 | 290663.48 | 52070.64 |
August | 1732817.37 | 14-AUG-15:09 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 207117.90 | 44964.77 | 0.00 | 314554.22 | 54595.22 |
September | 1252338.64 | 13-SEP-15:20 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 200531.51 | 44262.40 | 0.00 | 174661.26 | 76172.40 |
October | 1195819.11 | 06-OCT-15:20 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 143295.20 | 28429.66 | 0.00 | 99722.98 | 49368.81 |
November | 1279649.91 | 07-NOV-16:49 | 261074.09 | 675712.68 | 37611.08 | 83160.77 | 84346.83 | 28317.74 | 0.00 | 83999.14 | 25427.58 |
December | 1420341.24 | 20-DEC-16:19 | 261074.09 | 794004.08 | 37611.08 | 83161.34 | 79672.40 | 28317.60 | 0.00 | 105174.62 | 31326.03 |
Annual Sum or Average | |||||||||||
Minimum of Months | 974913.88 | 234435.00 | 439129.89 | 0.00 | 37754.99 | 79672.40 | 28315.94 | 0.00 | 35902.40 | 5322.66 | |
Maximum of Months | 1732817.37 | 261074.09 | 794004.08 | 37611.08 | 83161.34 | 216449.11 | 48432.31 | 0.00 | 314554.22 | 76172.40 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 725897.71 | 10-JAN-07:00 | 0.00 | 82094.84 | 30-JAN-12:20 | 0.00 |
February | 0.00 | 0.00 | 613729.39 | 17-FEB-07:10 | 0.00 | 82180.11 | 17-FEB-12:20 | 0.00 |
March | 0.00 | 0.00 | 423583.73 | 08-MAR-07:10 | 0.00 | 82130.89 | 01-MAR-12:50 | 0.00 |
April | 0.00 | 0.00 | 295140.09 | 08-APR-06:10 | 0.00 | 81605.79 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 213322.03 | 06-MAY-06:10 | 0.00 | 80825.30 | 01-MAY-11:30 | 0.00 |
June | 0.00 | 0.00 | 49918.11 | 07-JUN-20:00 | 0.00 | 79812.18 | 01-JUN-11:50 | 0.00 |
July | 0.00 | 0.00 | 2605.29 | 01-JUL-05:10 | 0.00 | 78827.59 | 05-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 2106.04 | 24-AUG-06:10 | 0.00 | 78364.06 | 03-AUG-11:00 | 0.00 |
September | 0.00 | 0.00 | 133191.52 | 21-SEP-06:10 | 0.00 | 78864.10 | 29-SEP-11:50 | 0.00 |
October | 0.00 | 0.00 | 299563.18 | 23-OCT-06:40 | 0.00 | 79721.87 | 27-OCT-11:50 | 0.00 |
November | 0.00 | 0.00 | 546064.61 | 29-NOV-07:10 | 0.00 | 80794.24 | 30-NOV-12:20 | 0.00 |
December | 0.00 | 0.00 | 597268.08 | 26-DEC-07:00 | 0.00 | 81575.89 | 27-DEC-12:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 2106.04 | 0.00 | 78364.06 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 725897.71 | 0.00 | 82180.11 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.97 | 2.33 | 27.06 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.91 | 0.00 | 25.91 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 25.86 | 0.00 | 25.86 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 26.02 | 0.00 | 26.02 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 26.57 | 0.00 | 26.57 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 25.94 | 0.00 | 25.94 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 26.37 | 0.00 | 26.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 26.25 | 0.00 | 26.25 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 26.24 | 0.17 | 26.28 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.56 | 1.83 | 26.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.33 | 26.58 | 2.17 | 26.77 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.22 | 0.00 | 26.22 |
Annual Sum or Average | 0.00 | 0.00 | 57.83 | 26.42 | 6.50 | 26.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 25.86 | 0.00 | 25.86 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 26.97 | 2.33 | 27.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.67 | 0.00 | 25.67 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.59 | 0.00 | 25.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.86 | 0.00 | 25.86 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.88 | 0.00 | 25.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.60 | 0.00 | 25.60 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.65 | 0.00 | 25.65 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.69 | 0.00 | 25.69 |
Annual Sum or Average | 0.00 | 0.00 | 1.83 | 25.72 | 0.00 | 25.72 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.88 | 0.00 | 25.88 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 | 0.00 | 18.68 |
February | 0.50 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 | 0.00 | 19.06 |
December | 1.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
Annual Sum or Average | 2.83 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 | 0.00 | 18.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.96 | 1.00 | 27.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.65 | 1.33 | 27.65 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.62 | 2.50 | 27.62 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.75 | 3.83 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.69 | 2.50 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.61 | 2.00 | 27.61 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.29 | 0.17 | 27.29 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 13.33 | 27.69 | 13.33 | 27.69 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.96 | 3.83 | 27.96 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.06 | 1.83 | 28.06 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.57 | 3.17 | 27.57 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.72 | 5.17 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 27.73 | 4.67 | 27.73 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.62 | 1.00 | 27.62 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.46 | 0.83 | 27.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 16.83 | 27.71 | 16.83 | 27.71 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.06 | 5.17 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 27.81 | 2.17 | 27.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 27.95 | 2.17 | 27.98 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 28.07 | 2.67 | 28.04 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.67 | 27.56 | 5.00 | 27.74 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 27.08 | 5.00 | 27.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.71 | 2.83 | 27.72 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.39 | 0.17 | 27.39 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 49.83 | 27.49 | 20.17 | 27.68 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 18.50 | 28.07 | 5.00 | 28.04 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 | 0.00 | 19.31 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
December | 2.00 | 19.29 | 0.17 | 19.36 | 0.00 | 19.36 | 0.00 | 19.36 |
Annual Sum or Average | 3.17 | 19.30 | 0.17 | 19.34 | 0.00 | 19.34 | 0.00 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 19.40 | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.83 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 | 0.00 | 19.32 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.95 | 1.17 | 27.95 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.58 | 1.00 | 27.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.67 | 1.83 | 27.67 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 27.91 | 3.17 | 27.91 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.66 | 2.33 | 27.66 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.50 | 1.33 | 27.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 | 0.00 | 19.43 |
December | 1.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
Annual Sum or Average | 2.33 | 19.24 | 0.00 | 19.24 | 10.83 | 26.24 | 10.83 | 26.92 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.17 | 19.43 | 0.00 | 19.43 | 3.17 | 27.95 | 3.17 | 27.95 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.31 | 0.17 | 27.31 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.14 | 1.67 | 28.17 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 27.56 | 1.83 | 27.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 27.69 | 4.33 | 27.69 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.82 | 5.00 | 27.82 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.68 | 1.17 | 27.68 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 27.44 | 0.50 | 27.44 |
December | 0.67 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 | 0.00 | 19.24 |
Annual Sum or Average | 0.83 | 19.28 | 0.00 | 19.28 | 14.83 | 27.31 | 14.67 | 27.53 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.44 | 0.00 | 19.44 | 5.00 | 28.14 | 5.00 | 28.17 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 | 0.00 | 19.40 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.18 | 1.00 | 28.18 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.72 | 1.33 | 27.70 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.02 | 1.33 | 28.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.09 | 2.33 | 28.10 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.90 | 2.33 | 27.95 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.70 | 0.83 | 27.70 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 | 0.00 | 19.26 |
Annual Sum or Average | 0.83 | 19.29 | 0.00 | 19.29 | 17.00 | 27.56 | 9.17 | 27.70 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.40 | 0.00 | 19.40 | 5.33 | 28.18 | 2.33 | 28.18 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.33 | 18.97 | 7.33 | 19.25 | 0.00 | 19.25 | 0.00 | 19.25 |
February | 11.83 | 18.93 | 3.00 | 19.16 | 0.00 | 19.16 | 0.00 | 19.16 |
March | 3.33 | 19.27 | 0.67 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.17 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 | 0.00 | 19.03 |
November | 11.67 | 18.62 | 3.17 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
December | 26.67 | 18.44 | 8.50 | 18.77 | 0.00 | 18.77 | 0.00 | 18.77 |
Annual Sum or Average | 73.17 | 18.73 | 22.67 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 26.67 | 19.33 | 8.50 | 19.44 | 0.00 | 19.44 | 0.00 | 19.44 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.83 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 | 0.00 | 18.18 |
February | 5.33 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
March | 2.33 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.79 | 1.00 | 27.79 |
May | 0.17 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 | 0.00 | 19.28 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.60 | 1.00 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.83 | 3.33 | 27.83 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 27.51 | 1.17 | 27.51 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
November | 4.17 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
December | 12.50 | 17.12 | 0.67 | 17.01 | 0.00 | 17.01 | 0.00 | 17.01 |
Annual Sum or Average | 31.33 | 17.95 | 0.67 | 17.89 | 6.50 | 19.55 | 6.50 | 20.74 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 12.50 | 19.28 | 0.67 | 19.28 | 3.33 | 27.83 | 3.33 | 27.83 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 5.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 | 0.00 | 18.42 |
February | 3.83 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 | 0.00 | 18.73 |
March | 1.67 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 | 0.00 | 19.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 28.16 | 1.50 | 28.23 |
May | 0.17 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 | 0.00 | 19.33 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 27.65 | 1.67 | 27.65 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.67 | 3.50 | 27.67 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 27.84 | 2.83 | 27.84 |
October | 0.33 | 18.79 | 0.00 | 18.79 | 0.17 | 21.64 | 0.17 | 23.07 |
November | 3.33 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
December | 7.83 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 | 0.00 | 18.30 |
Annual Sum or Average | 22.17 | 18.50 | 0.00 | 18.50 | 10.00 | 21.39 | 9.67 | 22.87 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 7.83 | 19.33 | 0.00 | 19.33 | 3.50 | 28.16 | 3.50 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 4.50 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 | 0.00 | 18.37 |
February | 3.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
March | 1.17 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 28.22 | 0.83 | 28.23 |
May | 0.17 | 19.43 | 0.00 | 19.43 | 1.50 | 27.01 | 0.67 | 27.23 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 28.23 | 1.00 | 28.23 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.33 | 28.10 | 2.50 | 28.09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.92 | 2.00 | 27.94 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.51 | 0.83 | 27.51 |
October | 0.17 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 | 0.00 | 18.44 |
November | 3.17 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 | 0.00 | 18.59 |
December | 6.67 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 | 0.00 | 18.49 |
Annual Sum or Average | 18.83 | 18.59 | 0.00 | 18.59 | 15.00 | 22.78 | 7.83 | 23.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 18.37 | 0.00 | 18.37 |
Maximum of Months | 6.67 | 19.43 | 0.00 | 19.43 | 5.33 | 28.23 | 2.50 | 28.23 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.38 | 5.00 | 28.34 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 28.10 | 5.00 | 28.10 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 12.67 | 28.27 | 10.00 | 28.23 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.38 | 5.00 | 28.34 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 106.67 | 23.94 | 93.17 | 24.90 | 0.00 | 24.90 |
February | 61.17 | 23.98 | 83.83 | 25.14 | 0.00 | 25.14 |
March | 41.67 | 24.00 | 82.50 | 25.31 | 0.00 | 25.31 |
April | 8.83 | 24.00 | 100.83 | 26.06 | 0.00 | 26.06 |
May | 3.00 | 24.00 | 156.00 | 25.38 | 0.00 | 25.38 |
June | 0.00 | 0.00 | 285.33 | 24.73 | 0.00 | 24.73 |
July | 0.00 | 0.00 | 392.00 | 24.72 | 0.00 | 24.72 |
August | 0.00 | 0.00 | 407.00 | 24.56 | 0.00 | 24.56 |
September | 0.00 | 0.00 | 284.83 | 24.84 | 0.00 | 24.84 |
October | 1.33 | 24.00 | 175.83 | 25.45 | 0.00 | 25.45 |
November | 9.17 | 24.00 | 143.67 | 25.61 | 0.00 | 25.61 |
December | 36.83 | 23.98 | 100.50 | 25.56 | 0.00 | 25.56 |
Annual Sum or Average | 268.67 | 23.97 | 2305.50 | 25.02 | 0.00 | 25.02 |
Minimum of Months | 0.00 | 0.00 | 82.50 | 24.56 | 0.00 | 24.56 |
Maximum of Months | 106.67 | 24.00 | 407.00 | 26.06 | 0.00 | 26.06 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 207.67 | 23.90 | 49.33 | 24.21 | 12.50 | 24.31 |
February | 108.67 | 23.81 | 54.67 | 24.37 | 0.00 | 24.37 |
March | 46.17 | 23.90 | 75.67 | 25.06 | 0.00 | 25.06 |
April | 6.67 | 23.94 | 96.17 | 25.58 | 0.00 | 25.58 |
May | 17.17 | 23.76 | 147.33 | 24.77 | 0.00 | 24.77 |
June | 0.00 | 0.00 | 323.50 | 24.41 | 0.00 | 24.41 |
July | 0.00 | 0.00 | 412.67 | 24.38 | 0.00 | 24.38 |
August | 0.00 | 0.00 | 437.67 | 24.31 | 0.00 | 24.31 |
September | 1.00 | 23.75 | 286.33 | 24.43 | 0.00 | 24.43 |
October | 19.50 | 23.77 | 183.00 | 24.93 | 0.00 | 24.93 |
November | 41.83 | 23.89 | 145.00 | 24.94 | 0.00 | 24.94 |
December | 84.17 | 23.87 | 85.33 | 24.80 | 0.00 | 24.80 |
Annual Sum or Average | 532.83 | 23.87 | 2296.67 | 24.56 | 12.50 | 24.57 |
Minimum of Months | 0.00 | 0.00 | 49.33 | 24.21 | 0.00 | 24.31 |
Maximum of Months | 207.67 | 23.94 | 437.67 | 25.58 | 12.50 | 25.58 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 440.17 | 23.12 | 12.33 | 23.08 | 12.33 | 23.05 |
February | 393.00 | 23.34 | 0.00 | 23.34 | 0.00 | 23.34 |
March | 413.83 | 23.53 | 0.00 | 23.53 | 0.00 | 23.53 |
April | 188.50 | 23.67 | 21.17 | 23.84 | 0.00 | 23.84 |
May | 151.00 | 23.56 | 65.50 | 23.90 | 0.00 | 23.90 |
June | 37.83 | 23.56 | 212.50 | 24.26 | 0.00 | 24.26 |
July | 27.50 | 23.46 | 274.50 | 24.28 | 0.00 | 24.28 |
August | 9.50 | 23.50 | 276.50 | 24.25 | 0.00 | 24.25 |
September | 63.83 | 23.54 | 157.83 | 24.17 | 0.00 | 24.17 |
October | 225.17 | 23.46 | 32.83 | 23.62 | 0.00 | 23.62 |
November | 357.33 | 23.38 | 2.17 | 23.38 | 0.00 | 23.38 |
December | 486.00 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
Annual Sum or Average | 2793.67 | 23.33 | 1055.33 | 23.61 | 12.33 | 23.61 |
Minimum of Months | 9.50 | 22.96 | 0.00 | 22.96 | 0.00 | 22.96 |
Maximum of Months | 486.00 | 23.67 | 276.50 | 24.28 | 12.33 | 24.28 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 21.40 | 124.83 | 21.13 | 124.83 | 20.96 |
February | 454.00 | 21.63 | 81.33 | 21.38 | 81.33 | 21.20 |
March | 514.00 | 22.16 | 29.50 | 22.06 | 29.50 | 21.98 |
April | 361.83 | 23.13 | 0.83 | 23.13 | 0.00 | 23.13 |
May | 310.83 | 23.15 | 43.17 | 23.27 | 0.00 | 23.27 |
June | 139.50 | 23.33 | 168.83 | 23.79 | 0.00 | 23.79 |
July | 117.00 | 23.31 | 235.17 | 23.92 | 0.00 | 23.92 |
August | 103.67 | 23.37 | 222.50 | 23.91 | 0.00 | 23.91 |
September | 235.83 | 23.14 | 87.67 | 23.40 | 0.00 | 23.40 |
October | 466.00 | 22.44 | 1.17 | 22.43 | 1.17 | 22.43 |
November | 487.00 | 21.84 | 50.50 | 21.69 | 50.50 | 21.57 |
December | 497.00 | 21.23 | 135.83 | 20.94 | 135.83 | 20.75 |
Annual Sum or Average | 4188.67 | 22.21 | 1181.33 | 22.31 | 423.17 | 22.15 |
Minimum of Months | 103.67 | 21.23 | 0.83 | 20.94 | 0.00 | 20.75 |
Maximum of Months | 514.00 | 23.37 | 235.17 | 23.92 | 135.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.37 | 16.83 | 22.32 | 16.83 | 22.28 |
February | 450.17 | 22.64 | 0.00 | 22.64 | 0.00 | 22.64 |
March | 476.83 | 23.21 | 4.00 | 23.23 | 0.00 | 23.23 |
April | 257.17 | 23.58 | 10.67 | 23.64 | 0.00 | 23.64 |
May | 239.33 | 23.46 | 46.83 | 23.60 | 0.00 | 23.60 |
June | 49.83 | 23.64 | 220.50 | 24.14 | 0.00 | 24.14 |
July | 9.33 | 23.70 | 325.67 | 24.29 | 0.00 | 24.29 |
August | 24.50 | 23.65 | 325.50 | 24.17 | 0.00 | 24.17 |
September | 176.17 | 23.40 | 97.83 | 23.68 | 0.00 | 23.68 |
October | 373.00 | 23.21 | 14.00 | 23.26 | 0.00 | 23.26 |
November | 438.17 | 22.97 | 0.00 | 22.97 | 0.00 | 22.97 |
December | 497.00 | 22.59 | 0.00 | 22.59 | 0.00 | 22.59 |
Annual Sum or Average | 3493.50 | 22.96 | 1061.83 | 23.25 | 16.83 | 23.25 |
Minimum of Months | 9.33 | 22.37 | 0.00 | 22.32 | 0.00 | 22.28 |
Maximum of Months | 502.00 | 23.70 | 325.67 | 24.29 | 16.83 | 24.29 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 493.50 | 22.11 | 18.83 | 22.08 | 17.67 | 22.05 |
February | 436.00 | 22.29 | 0.67 | 22.29 | 0.00 | 22.29 |
March | 488.17 | 22.70 | 1.50 | 22.71 | 0.00 | 22.71 |
April | 206.50 | 23.28 | 78.50 | 23.64 | 3.83 | 23.68 |
May | 178.50 | 23.24 | 153.67 | 23.85 | 2.83 | 23.88 |
June | 94.00 | 23.67 | 275.00 | 24.16 | 8.83 | 24.22 |
July | 54.83 | 24.24 | 341.50 | 24.41 | 14.17 | 24.50 |
August | 72.50 | 23.82 | 335.17 | 24.20 | 11.33 | 24.27 |
September | 148.33 | 23.40 | 220.83 | 24.03 | 8.67 | 24.10 |
October | 359.83 | 22.79 | 31.00 | 22.92 | 0.00 | 22.92 |
November | 479.00 | 22.49 | 1.50 | 22.50 | 0.00 | 22.50 |
December | 497.00 | 21.92 | 10.83 | 21.90 | 10.83 | 21.88 |
Annual Sum or Average | 3508.17 | 22.60 | 1469.00 | 23.11 | 78.17 | 23.14 |
Minimum of Months | 54.83 | 21.92 | 0.67 | 21.90 | 0.00 | 21.88 |
Maximum of Months | 497.00 | 24.24 | 341.50 | 24.41 | 17.67 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 424.83 | 22.05 | 35.33 | 22.17 | 11.83 | 22.14 |
February | 358.17 | 22.28 | 36.67 | 22.49 | 1.83 | 22.48 |
March | 448.33 | 22.67 | 0.00 | 22.67 | 0.00 | 22.67 |
April | 194.33 | 23.38 | 112.33 | 23.80 | 6.00 | 23.86 |
May | 225.67 | 23.08 | 124.17 | 23.57 | 0.00 | 23.57 |
June | 97.50 | 23.34 | 255.83 | 24.01 | 1.50 | 24.02 |
July | 63.33 | 24.13 | 333.50 | 24.35 | 14.17 | 24.44 |
August | 64.33 | 24.53 | 373.00 | 24.38 | 21.00 | 24.50 |
September | 129.00 | 23.67 | 268.83 | 24.21 | 17.17 | 24.32 |
October | 307.17 | 22.81 | 91.67 | 23.17 | 1.67 | 23.18 |
November | 404.67 | 22.50 | 29.83 | 22.68 | 0.50 | 22.68 |
December | 454.00 | 21.97 | 28.33 | 22.00 | 15.67 | 21.96 |
Annual Sum or Average | 3171.33 | 22.64 | 1689.50 | 23.23 | 91.33 | 23.27 |
Minimum of Months | 63.33 | 21.97 | 0.00 | 22.00 | 0.00 | 21.96 |
Maximum of Months | 454.00 | 24.53 | 373.00 | 24.38 | 21.00 | 24.50 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 456.67 | 22.68 | 9.17 | 22.72 | 0.00 | 22.72 |
February | 310.67 | 23.21 | 36.50 | 23.38 | 0.00 | 23.38 |
March | 165.50 | 23.50 | 59.00 | 24.02 | 0.00 | 24.02 |
April | 14.17 | 25.63 | 257.83 | 25.02 | 8.00 | 25.08 |
May | 98.17 | 23.58 | 208.50 | 24.28 | 7.50 | 24.34 |
June | 16.33 | 26.45 | 432.00 | 24.54 | 14.00 | 24.62 |
July | 24.83 | 27.01 | 477.33 | 24.73 | 24.83 | 24.83 |
August | 22.33 | 27.04 | 505.67 | 24.61 | 22.33 | 24.71 |
September | 62.83 | 23.91 | 295.33 | 24.35 | 10.83 | 24.43 |
October | 141.00 | 23.31 | 152.33 | 24.10 | 0.50 | 24.11 |
November | 184.33 | 23.40 | 95.67 | 23.95 | 0.00 | 23.95 |
December | 259.33 | 23.46 | 27.83 | 23.67 | 0.00 | 23.67 |
Annual Sum or Average | 1756.17 | 23.36 | 2557.17 | 24.12 | 88.00 | 24.18 |
Minimum of Months | 14.17 | 22.68 | 9.17 | 22.72 | 0.00 | 22.72 |
Maximum of Months | 456.67 | 27.04 | 505.67 | 25.02 | 24.83 | 25.08 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.90 | 227.50 | 20.73 | 227.50 | 20.65 |
February | 454.00 | 21.00 | 143.33 | 20.82 | 143.33 | 20.71 |
March | 514.00 | 21.61 | 53.00 | 21.52 | 53.00 | 21.45 |
April | 444.33 | 22.74 | 2.50 | 22.73 | 2.50 | 22.71 |
May | 414.83 | 22.83 | 14.33 | 22.87 | 0.00 | 22.87 |
June | 199.17 | 23.23 | 105.83 | 23.54 | 0.00 | 23.54 |
July | 168.83 | 23.29 | 176.00 | 23.72 | 0.00 | 23.72 |
August | 190.67 | 23.24 | 125.67 | 23.54 | 0.00 | 23.54 |
September | 345.83 | 22.87 | 41.83 | 22.99 | 0.00 | 22.99 |
October | 498.67 | 21.99 | 11.67 | 21.95 | 11.67 | 21.91 |
November | 489.00 | 21.19 | 102.83 | 21.04 | 102.83 | 20.93 |
December | 497.00 | 20.59 | 271.33 | 20.44 | 271.33 | 20.37 |
Annual Sum or Average | 4718.33 | 21.87 | 1275.83 | 21.82 | 812.17 | 21.64 |
Minimum of Months | 168.83 | 20.59 | 2.50 | 20.44 | 0.00 | 20.37 |
Maximum of Months | 514.00 | 23.29 | 271.33 | 23.72 | 271.33 | 23.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 427.00 | 20.90 | 180.17 | 20.76 | 180.17 | 20.69 |
February | 385.00 | 21.10 | 111.17 | 20.96 | 111.17 | 20.88 |
March | 433.00 | 21.48 | 45.83 | 21.41 | 45.83 | 21.34 |
April | 260.50 | 22.81 | 43.17 | 23.07 | 4.50 | 23.11 |
May | 243.00 | 22.73 | 92.83 | 23.24 | 2.33 | 23.27 |
June | 158.00 | 23.22 | 172.83 | 23.87 | 8.00 | 23.94 |
July | 116.00 | 23.61 | 228.83 | 24.29 | 14.33 | 24.39 |
August | 127.67 | 23.43 | 218.00 | 24.03 | 10.33 | 24.11 |
September | 194.50 | 22.88 | 135.50 | 23.59 | 4.50 | 23.63 |
October | 386.00 | 21.85 | 10.83 | 21.87 | 6.00 | 21.85 |
November | 417.00 | 21.11 | 87.33 | 20.99 | 87.33 | 20.90 |
December | 422.00 | 20.54 | 244.67 | 20.40 | 244.67 | 20.34 |
Annual Sum or Average | 3569.67 | 21.73 | 1571.17 | 22.04 | 719.17 | 21.88 |
Minimum of Months | 116.00 | 20.54 | 10.83 | 20.40 | 2.33 | 20.34 |
Maximum of Months | 433.00 | 23.61 | 244.67 | 24.29 | 244.67 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 445.50 | 21.52 | 113.33 | 21.44 | 100.17 | 21.31 |
February | 379.50 | 21.67 | 73.83 | 21.76 | 43.33 | 21.65 |
March | 486.33 | 21.92 | 28.17 | 21.86 | 28.17 | 21.79 |
April | 257.00 | 22.85 | 95.33 | 23.32 | 5.83 | 23.38 |
May | 305.00 | 22.71 | 104.83 | 23.16 | 0.00 | 23.16 |
June | 192.00 | 23.02 | 205.67 | 23.66 | 0.50 | 23.66 |
July | 145.17 | 23.30 | 261.67 | 23.99 | 10.50 | 24.06 |
August | 128.67 | 23.65 | 299.00 | 24.11 | 18.17 | 24.23 |
September | 182.50 | 23.33 | 241.00 | 23.97 | 19.00 | 24.10 |
October | 363.33 | 22.27 | 81.17 | 22.62 | 6.50 | 22.65 |
November | 437.50 | 21.67 | 63.17 | 21.72 | 43.33 | 21.63 |
December | 480.00 | 21.09 | 185.50 | 20.88 | 185.00 | 20.76 |
Annual Sum or Average | 3802.50 | 22.11 | 1752.67 | 22.55 | 460.50 | 22.45 |
Minimum of Months | 128.67 | 21.09 | 28.17 | 20.88 | 0.00 | 20.76 |
Maximum of Months | 486.33 | 23.65 | 299.00 | 24.11 | 185.00 | 24.23 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 499.33 | 21.13 | 151.67 | 20.99 | 151.67 | 20.90 |
February | 436.17 | 21.34 | 68.50 | 21.22 | 67.67 | 21.13 |
March | 502.33 | 21.72 | 21.00 | 21.68 | 21.00 | 21.64 |
April | 331.83 | 22.88 | 60.00 | 23.12 | 3.50 | 23.15 |
May | 324.17 | 22.82 | 106.17 | 23.21 | 4.33 | 23.25 |
June | 150.00 | 23.24 | 235.33 | 23.89 | 6.83 | 23.95 |
July | 119.67 | 23.45 | 313.00 | 24.11 | 12.83 | 24.19 |
August | 110.17 | 23.49 | 289.00 | 24.05 | 11.83 | 24.14 |
September | 256.50 | 22.87 | 142.33 | 23.39 | 4.50 | 23.43 |
October | 457.50 | 22.05 | 19.17 | 22.12 | 2.00 | 22.11 |
November | 483.67 | 21.36 | 59.33 | 21.25 | 59.33 | 21.16 |
December | 497.00 | 20.77 | 216.00 | 20.63 | 216.00 | 20.56 |
Annual Sum or Average | 4168.33 | 21.89 | 1681.50 | 22.25 | 561.50 | 22.13 |
Minimum of Months | 110.17 | 20.77 | 19.17 | 20.63 | 2.00 | 20.56 |
Maximum of Months | 502.33 | 23.49 | 313.00 | 24.11 | 216.00 | 24.19 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.20 | 377.67 | 20.07 | 377.67 | 20.02 |
February | 454.00 | 20.24 | 304.50 | 20.08 | 304.50 | 20.02 |
March | 514.00 | 20.81 | 254.17 | 20.65 | 254.17 | 20.58 |
April | 462.83 | 21.99 | 65.83 | 21.80 | 65.83 | 21.65 |
May | 444.00 | 22.10 | 40.50 | 22.09 | 22.50 | 22.01 |
June | 273.33 | 22.78 | 91.00 | 23.10 | 0.00 | 23.10 |
July | 227.67 | 22.83 | 158.50 | 23.35 | 0.00 | 23.35 |
August | 270.50 | 22.89 | 110.17 | 23.21 | 0.00 | 23.21 |
September | 398.00 | 22.27 | 36.17 | 22.32 | 9.33 | 22.27 |
October | 502.00 | 21.00 | 139.83 | 20.78 | 139.83 | 20.63 |
November | 489.00 | 20.39 | 292.00 | 20.20 | 292.00 | 20.12 |
December | 497.00 | 20.00 | 428.17 | 19.92 | 428.17 | 19.90 |
Annual Sum or Average | 5034.33 | 21.24 | 2298.50 | 21.07 | 1894.00 | 20.84 |
Minimum of Months | 227.67 | 20.00 | 36.17 | 19.92 | 0.00 | 19.90 |
Maximum of Months | 514.00 | 22.89 | 428.17 | 23.35 | 428.17 | 23.35 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.30 | 356.50 | 20.17 | 356.50 | 20.11 |
February | 454.00 | 20.45 | 274.17 | 20.26 | 274.17 | 20.18 |
March | 514.00 | 20.89 | 232.17 | 20.74 | 232.17 | 20.66 |
April | 328.83 | 22.38 | 63.50 | 22.50 | 27.83 | 22.43 |
May | 321.17 | 22.33 | 100.33 | 22.75 | 5.83 | 22.71 |
June | 203.83 | 22.80 | 211.50 | 23.57 | 3.67 | 23.60 |
July | 146.83 | 23.22 | 286.83 | 24.01 | 14.83 | 24.11 |
August | 156.67 | 23.05 | 278.67 | 23.83 | 5.83 | 23.87 |
September | 229.67 | 22.36 | 156.67 | 23.13 | 2.50 | 23.11 |
October | 474.33 | 21.24 | 117.17 | 21.00 | 117.17 | 20.84 |
November | 489.00 | 20.48 | 265.50 | 20.30 | 265.50 | 20.21 |
December | 497.00 | 20.06 | 414.00 | 19.97 | 414.00 | 19.94 |
Annual Sum or Average | 4317.33 | 21.22 | 2757.00 | 21.40 | 1720.00 | 21.15 |
Minimum of Months | 146.83 | 20.06 | 63.50 | 19.97 | 2.50 | 19.94 |
Maximum of Months | 514.00 | 23.22 | 414.00 | 24.01 | 414.00 | 24.11 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 479.00 | 20.80 | 267.50 | 20.56 | 267.50 | 20.44 |
February | 415.83 | 20.97 | 194.00 | 20.72 | 189.50 | 20.58 |
March | 502.67 | 21.13 | 197.83 | 20.93 | 197.83 | 20.82 |
April | 316.00 | 22.31 | 107.33 | 22.57 | 36.33 | 22.49 |
May | 345.33 | 22.07 | 108.50 | 22.46 | 18.17 | 22.39 |
June | 241.33 | 22.55 | 181.00 | 23.26 | 0.67 | 23.26 |
July | 185.00 | 22.76 | 238.33 | 23.65 | 9.00 | 23.71 |
August | 175.33 | 23.12 | 263.33 | 23.82 | 15.33 | 23.92 |
September | 221.83 | 22.57 | 220.83 | 23.43 | 16.67 | 23.48 |
October | 405.67 | 21.43 | 115.83 | 21.57 | 64.33 | 21.42 |
November | 465.83 | 20.90 | 197.83 | 20.71 | 190.67 | 20.56 |
December | 490.83 | 20.41 | 347.17 | 20.22 | 347.17 | 20.14 |
Annual Sum or Average | 4244.67 | 21.47 | 2439.50 | 21.69 | 1353.17 | 21.46 |
Minimum of Months | 175.33 | 20.41 | 107.33 | 20.22 | 0.67 | 20.14 |
Maximum of Months | 502.67 | 23.12 | 347.17 | 23.82 | 347.17 | 23.92 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.50 | 315.50 | 20.34 | 315.50 | 20.27 |
February | 448.33 | 20.74 | 216.00 | 20.52 | 216.00 | 20.41 |
March | 508.83 | 21.06 | 168.50 | 20.92 | 168.50 | 20.83 |
April | 370.17 | 22.20 | 75.83 | 22.37 | 27.67 | 22.31 |
May | 355.50 | 22.13 | 98.00 | 22.58 | 8.33 | 22.57 |
June | 219.50 | 22.80 | 204.83 | 23.51 | 6.33 | 23.56 |
July | 168.17 | 22.94 | 276.67 | 23.80 | 12.50 | 23.89 |
August | 187.83 | 23.08 | 242.00 | 23.74 | 11.00 | 23.82 |
September | 317.00 | 22.34 | 117.17 | 22.84 | 7.00 | 22.84 |
October | 472.17 | 21.28 | 75.33 | 21.20 | 65.50 | 21.08 |
November | 489.00 | 20.72 | 209.33 | 20.53 | 209.33 | 20.42 |
December | 497.00 | 20.25 | 371.00 | 20.13 | 371.00 | 20.09 |
Annual Sum or Average | 4535.50 | 21.37 | 2370.17 | 21.54 | 1418.67 | 21.33 |
Minimum of Months | 168.17 | 20.25 | 75.33 | 20.13 | 6.33 | 20.09 |
Maximum of Months | 508.83 | 23.08 | 371.00 | 23.80 | 371.00 | 23.89 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 1.50 | 27.00 | 454.00 | 27.00 | 1.50 | 27.00 |
March | 2.67 | 27.00 | 514.00 | 27.00 | 2.67 | 27.00 |
April | 59.33 | 27.00 | 485.00 | 27.00 | 59.33 | 27.00 |
May | 3.67 | 27.00 | 508.00 | 27.00 | 3.67 | 27.00 |
June | 38.50 | 27.00 | 496.00 | 27.00 | 38.50 | 27.00 |
July | 133.33 | 27.00 | 497.00 | 27.00 | 133.33 | 27.00 |
August | 299.33 | 27.00 | 514.00 | 27.00 | 299.33 | 27.00 |
September | 7.17 | 27.00 | 485.00 | 27.00 | 7.17 | 27.00 |
October | 5.00 | 27.00 | 502.00 | 27.00 | 5.00 | 27.00 |
November | 2.17 | 27.00 | 489.00 | 27.00 | 2.17 | 27.00 |
December | 0.00 | 0.00 | 497.00 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 552.67 | 27.00 | 5943.00 | 27.00 | 552.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 299.33 | 27.00 | 514.00 | 27.00 | 299.33 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 487.83 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 514.00 | 27.00 | 0.00 | 27.00 |
April | 5.50 | 27.00 | 485.00 | 27.00 | 5.50 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 2.33 | 27.00 | 496.00 | 27.00 | 2.33 | 27.00 |
July | 5.83 | 27.00 | 497.00 | 27.00 | 5.83 | 27.00 |
August | 15.83 | 27.00 | 514.00 | 27.00 | 15.83 | 27.00 |
September | 1.17 | 27.00 | 485.00 | 27.00 | 1.17 | 27.00 |
October | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 489.00 | 27.00 | 0.00 | 27.00 |
December | 0.00 | 0.00 | 485.50 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 30.67 | 27.00 | 5917.33 | 27.00 | 30.67 | 27.00 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 15.83 | 27.00 | 514.00 | 27.00 | 15.83 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 89.67 | 25.14 | 308.83 | 26.57 | 0.00 | 26.57 |
February | 4.00 | 27.00 | 372.67 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 481.67 | 27.00 | 0.00 | 27.00 |
April | 8.33 | 27.00 | 485.00 | 27.00 | 8.33 | 27.00 |
May | 2.00 | 27.00 | 508.00 | 27.00 | 2.00 | 27.00 |
June | 11.00 | 27.00 | 496.00 | 27.00 | 11.00 | 27.00 |
July | 18.83 | 27.00 | 497.00 | 27.00 | 18.83 | 27.00 |
August | 33.00 | 27.00 | 514.00 | 27.00 | 33.00 | 27.00 |
September | 2.17 | 27.00 | 485.00 | 27.00 | 2.17 | 27.00 |
October | 0.00 | 0.00 | 496.50 | 27.00 | 0.00 | 27.00 |
November | 0.00 | 0.00 | 443.50 | 27.00 | 0.00 | 27.00 |
December | 7.33 | 27.00 | 383.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 176.33 | 26.06 | 5471.83 | 26.97 | 75.33 | 26.97 |
Minimum of Months | 0.00 | 0.00 | 308.83 | 26.57 | 0.00 | 26.57 |
Maximum of Months | 89.67 | 27.00 | 514.00 | 27.00 | 33.00 | 27.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 320.67 | 27.00 | 502.00 | 27.00 | 320.67 | 27.00 |
February | 454.00 | 27.00 | 454.00 | 27.00 | 454.00 | 27.00 |
March | 514.00 | 27.00 | 514.00 | 27.00 | 514.00 | 27.00 |
April | 485.00 | 27.02 | 485.00 | 27.02 | 485.00 | 27.02 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.00 | 496.00 | 27.00 | 496.00 | 27.00 |
July | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
August | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.00 | 502.00 | 27.00 | 502.00 | 27.00 |
November | 489.00 | 27.00 | 489.00 | 27.00 | 489.00 | 27.00 |
December | 497.00 | 27.00 | 497.00 | 27.00 | 497.00 | 27.00 |
Annual Sum or Average | 5761.67 | 27.00 | 5943.00 | 27.00 | 5761.67 | 27.00 |
Minimum of Months | 320.67 | 27.00 | 454.00 | 27.00 | 320.67 | 27.00 |
Maximum of Months | 514.00 | 27.02 | 514.00 | 27.02 | 514.00 | 27.02 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00001 | 27.62855 | 0.79109 | 18.30390 |
February | 454.00000 | 27.00001 | 27.90315 | 0.84778 | 20.24445 |
March | 514.00000 | 27.00000 | 27.82813 | 0.89331 | 21.90137 |
April | 485.00000 | 27.00000 | 28.44795 | 0.97038 | 24.94379 |
May | 508.00000 | 27.00014 | 32.82205 | 0.22689 | 6.17567 |
June | 496.00000 | 27.00045 | 35.96269 | 0.32615 | 7.27719 |
July | 497.00000 | 27.00034 | 36.26206 | 0.38442 | 8.13643 |
August | 514.00000 | 27.00014 | 36.47885 | 0.42431 | 8.80746 |
September | 485.00000 | 27.00043 | 36.23099 | 0.26007 | 6.49102 |
October | 502.00000 | 27.00014 | 32.68753 | 0.91372 | 22.67604 |
November | 489.00000 | 27.00006 | 30.55258 | 0.91158 | 22.61101 |
December | 497.00000 | 27.00000 | 26.74309 | 0.89207 | 21.86031 |
Annual Sum or Average | 5943.00000 | 27.00014 | 31.65651 | 0.65151 | 15.73364 |
Minimum of Months | 454.00000 | 27.00000 | 26.74309 | 0.22689 | 6.17567 |
Maximum of Months | 514.00000 | 27.00045 | 36.47885 | 0.97038 | 24.94379 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99892 | 27.64901 | 0.67968 | 14.84767 |
February | 454.00000 | 27.00001 | 27.88663 | 0.71676 | 15.93998 |
March | 514.00000 | 27.00000 | 27.81617 | 0.74836 | 16.88116 |
April | 485.00000 | 27.00000 | 28.43815 | 0.84487 | 20.18106 |
May | 508.00000 | 27.00013 | 32.82270 | 0.13346 | 5.54960 |
June | 496.00000 | 27.00042 | 35.97888 | 0.22461 | 6.16162 |
July | 497.00000 | 27.00034 | 36.26452 | 0.25804 | 6.49942 |
August | 514.00000 | 27.00016 | 36.47538 | 0.27972 | 6.72150 |
September | 485.00000 | 27.00040 | 36.30986 | 0.17337 | 5.76217 |
October | 502.00000 | 27.00014 | 32.68876 | 0.80070 | 18.60390 |
November | 489.00000 | 27.00006 | 30.53005 | 0.75169 | 17.00833 |
December | 497.00000 | 27.00000 | 26.72452 | 0.68828 | 15.06057 |
Annual Sum or Average | 5943.00000 | 27.00005 | 31.65959 | 0.52296 | 12.39297 |
Minimum of Months | 454.00000 | 26.99892 | 26.72452 | 0.13346 | 5.54960 |
Maximum of Months | 514.00000 | 27.00042 | 36.47538 | 0.84487 | 20.18106 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.59421 | 28.22306 | 0.51395 | 11.58024 |
February | 454.00000 | 27.00001 | 27.89635 | 0.62626 | 13.46600 |
March | 514.00000 | 27.00000 | 27.82102 | 0.66674 | 14.49052 |
April | 485.00000 | 27.00000 | 28.44130 | 0.79682 | 18.64065 |
May | 508.00000 | 27.00037 | 32.84042 | 0.07909 | 5.50776 |
June | 496.00000 | 27.00043 | 35.99564 | 0.19902 | 6.07283 |
July | 497.00000 | 27.00035 | 36.27662 | 0.23805 | 6.44026 |
August | 514.00000 | 27.00017 | 36.48662 | 0.25737 | 6.58011 |
September | 485.00000 | 27.00047 | 36.38390 | 0.12355 | 5.61010 |
October | 502.00000 | 27.00013 | 32.73610 | 0.72280 | 16.16657 |
November | 489.00000 | 27.00006 | 30.55486 | 0.66216 | 14.38874 |
December | 497.00000 | 27.00000 | 26.73061 | 0.60116 | 12.76660 |
Annual Sum or Average | 5943.00000 | 26.96589 | 31.72699 | 0.45538 | 10.94167 |
Minimum of Months | 454.00000 | 26.59421 | 26.73061 | 0.07909 | 5.50776 |
Maximum of Months | 514.00000 | 27.00047 | 36.48662 | 0.79682 | 18.64065 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00071 | 31.41276 | 1.04311 | 27.98695 |
February | 454.00000 | 27.00196 | 31.22195 | 1.20822 | 35.66015 |
March | 514.00000 | 27.00234 | 30.81872 | 1.35722 | 43.24941 |
April | 485.00000 | 27.01537 | 30.95634 | 1.51098 | 51.49719 |
May | 508.00000 | 27.00036 | 33.43809 | 0.50059 | 10.30491 |
June | 496.00000 | 27.00055 | 35.82122 | 0.75139 | 16.90753 |
July | 497.00000 | 27.00034 | 36.15758 | 0.96546 | 24.70616 |
August | 514.00000 | 27.01676 | 36.42048 | 1.16554 | 33.60087 |
September | 485.00000 | 27.00077 | 35.94586 | 0.54826 | 11.34211 |
October | 502.00000 | 27.00043 | 33.58827 | 1.25547 | 38.01321 |
November | 489.00000 | 27.00116 | 32.45575 | 1.38389 | 44.66166 |
December | 497.00000 | 27.00287 | 30.58571 | 1.49065 | 50.39385 |
Annual Sum or Average | 5943.00000 | 27.00366 | 33.25088 | 1.09747 | 32.32125 |
Minimum of Months | 454.00000 | 27.00034 | 30.58571 | 0.50059 | 10.30491 |
Maximum of Months | 514.00000 | 27.01676 | 36.42048 | 1.51098 | 51.49719 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.41897 | 28.07931 | 0.36723 | 8.26113 |
February | 454.00000 | 24.41439 | 28.87669 | 0.37443 | 8.24561 |
March | 514.00000 | 24.35742 | 28.11804 | 0.36518 | 8.10885 |
April | 485.00000 | 24.48644 | 28.15548 | 0.40355 | 8.87744 |
May | 508.00000 | 24.44630 | 34.39835 | -0.4277 | 9.64091 |
June | 496.00000 | 24.41982 | 42.19422 | -0.3693 | 8.62938 |
July | 497.00000 | 24.56694 | 43.73599 | -0.3092 | 8.01234 |
August | 514.00000 | 24.44498 | 44.61276 | -0.3313 | 8.20711 |
September | 485.00000 | 24.49655 | 41.40360 | -0.3506 | 8.66592 |
October | 502.00000 | 24.52350 | 34.99400 | 0.45759 | 9.89232 |
November | 489.00000 | 24.52211 | 31.77853 | 0.43172 | 9.40491 |
December | 497.00000 | 24.47359 | 27.18592 | 0.38156 | 8.49088 |
Annual Sum or Average | 5943.00000 | 24.46405 | 34.50836 | 0.07972 | 8.70441 |
Minimum of Months | 454.00000 | 24.35742 | 27.18592 | -0.4277 | 8.01234 |
Maximum of Months | 514.00000 | 24.56694 | 44.61276 | 0.45759 | 9.89232 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.15908 | 32.51177 | 0.33300 | 8.02860 |
February | 454.00000 | 24.22833 | 31.00967 | 0.34571 | 7.68600 |
March | 514.00000 | 24.29330 | 29.90179 | 0.36770 | 8.10507 |
April | 485.00000 | 24.35190 | 29.19796 | 0.40098 | 8.65446 |
May | 508.00000 | 24.26739 | 35.69266 | -0.4627 | 9.91998 |
June | 496.00000 | 24.26459 | 43.14161 | -0.3878 | 8.52750 |
July | 497.00000 | 24.31491 | 45.03889 | -0.3475 | 7.92607 |
August | 514.00000 | 24.26259 | 45.38980 | -0.3503 | 7.91009 |
September | 485.00000 | 24.25277 | 42.57444 | -0.4065 | 8.83565 |
October | 502.00000 | 24.38856 | 36.63461 | 0.43736 | 9.35556 |
November | 489.00000 | 24.38750 | 33.73597 | 0.41318 | 8.91136 |
December | 497.00000 | 24.34184 | 29.37026 | 0.36483 | 8.09987 |
Annual Sum or Average | 5943.00000 | 24.29287 | 36.22879 | 0.05607 | 8.50115 |
Minimum of Months | 454.00000 | 24.15908 | 29.19796 | -0.4627 | 7.68600 |
Maximum of Months | 514.00000 | 24.38856 | 45.38980 | 0.43736 | 9.91998 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.22614 | 34.92249 | 0.08226 | 5.74199 |
February | 454.00000 | 23.42753 | 33.70859 | 0.12951 | 5.76983 |
March | 514.00000 | 23.62907 | 32.75881 | 0.18170 | 5.99762 |
April | 485.00000 | 24.03400 | 31.04025 | 0.29343 | 6.99415 |
May | 508.00000 | 24.01383 | 36.96616 | -0.5766 | 12.39582 |
June | 496.00000 | 24.10931 | 44.16535 | -0.4756 | 10.03343 |
July | 497.00000 | 24.14178 | 46.19020 | -0.4495 | 9.55283 |
August | 514.00000 | 24.10322 | 46.53822 | -0.4511 | 9.49489 |
September | 485.00000 | 24.04884 | 43.71360 | -0.5035 | 10.62214 |
October | 502.00000 | 23.86576 | 38.82001 | 0.28947 | 7.03655 |
November | 489.00000 | 23.55740 | 36.92235 | 0.18435 | 6.18092 |
December | 497.00000 | 22.98424 | 33.17323 | 0.00754 | 5.60415 |
Annual Sum or Average | 5943.00000 | 23.76396 | 38.28373 | -0.1099 | 7.97081 |
Minimum of Months | 454.00000 | 22.98424 | 31.04025 | -0.5766 | 5.60415 |
Maximum of Months | 514.00000 | 24.14178 | 46.53822 | 0.29343 | 12.39582 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.40394 | 36.58020 | -0.3846 | 10.03053 |
February | 454.00000 | 21.63082 | 37.02379 | -0.3190 | 8.78372 |
March | 514.00000 | 22.15713 | 35.98702 | -0.1871 | 6.83291 |
April | 485.00000 | 23.36049 | 32.91140 | 0.12279 | 6.20410 |
May | 508.00000 | 23.50092 | 38.70031 | -0.7630 | 18.58180 |
June | 496.00000 | 23.89027 | 45.08054 | -0.5527 | 12.00883 |
July | 497.00000 | 23.93535 | 46.94670 | -0.5180 | 11.26218 |
August | 514.00000 | 23.92688 | 47.24235 | -0.5151 | 10.94903 |
September | 485.00000 | 23.60658 | 45.73744 | -0.6655 | 15.24643 |
October | 502.00000 | 22.54933 | 42.66052 | -0.0405 | 6.18650 |
November | 489.00000 | 21.84988 | 40.98220 | -0.2409 | 7.59542 |
December | 497.00000 | 21.22847 | 35.67851 | -0.4376 | 10.76098 |
Annual Sum or Average | 5943.00000 | 22.76126 | 40.49082 | -0.3764 | 10.38664 |
Minimum of Months | 454.00000 | 21.22847 | 32.91140 | -0.7630 | 6.18650 |
Maximum of Months | 514.00000 | 23.93535 | 47.24235 | 0.12279 | 18.58180 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.36922 | 32.74946 | -0.1351 | 6.27632 |
February | 454.00000 | 22.65252 | 32.92358 | -0.0614 | 5.76958 |
March | 514.00000 | 23.28464 | 31.33598 | 0.08627 | 5.72249 |
April | 485.00000 | 23.84868 | 29.54782 | 0.24238 | 6.55880 |
May | 508.00000 | 23.79749 | 35.88143 | -0.6559 | 14.71048 |
June | 496.00000 | 24.09138 | 42.75779 | -0.4667 | 9.92102 |
July | 497.00000 | 24.20649 | 44.50515 | -0.4018 | 8.69109 |
August | 514.00000 | 24.11931 | 45.09488 | -0.4324 | 9.16779 |
September | 485.00000 | 23.80857 | 42.86060 | -0.6014 | 13.19499 |
October | 502.00000 | 23.44743 | 38.13961 | 0.17533 | 6.15409 |
November | 489.00000 | 23.07738 | 35.53389 | 0.05977 | 5.76016 |
December | 497.00000 | 22.58740 | 31.19303 | -0.0900 | 5.69690 |
Annual Sum or Average | 5943.00000 | 23.44665 | 36.91248 | -0.1917 | 8.15328 |
Minimum of Months | 454.00000 | 22.36922 | 29.54782 | -0.6559 | 5.69690 |
Maximum of Months | 514.00000 | 24.20649 | 45.09488 | 0.24238 | 14.71048 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.15556 | 32.47112 | -0.1736 | 6.64878 |
February | 454.00000 | 22.36374 | 32.76806 | -0.1134 | 6.22967 |
March | 514.00000 | 22.77229 | 31.64279 | -0.0181 | 5.85261 |
April | 485.00000 | 23.79112 | 29.14303 | 0.28035 | 7.54008 |
May | 508.00000 | 23.89177 | 35.19767 | -0.5532 | 13.26684 |
June | 496.00000 | 24.05544 | 42.57584 | -0.4154 | 9.98116 |
July | 497.00000 | 24.22526 | 44.27256 | -0.3324 | 8.84773 |
August | 514.00000 | 24.08917 | 44.93635 | -0.3727 | 9.23448 |
September | 485.00000 | 23.95536 | 41.96707 | -0.4732 | 11.62229 |
October | 502.00000 | 23.18187 | 38.18473 | 0.13757 | 6.31597 |
November | 489.00000 | 22.52823 | 36.00275 | -0.0539 | 5.84336 |
December | 497.00000 | 21.92349 | 31.66950 | -0.2328 | 6.81198 |
Annual Sum or Average | 5943.00000 | 23.25040 | 36.77311 | -0.1949 | 8.19714 |
Minimum of Months | 454.00000 | 21.92349 | 29.14303 | -0.5532 | 5.84336 |
Maximum of Months | 514.00000 | 24.22526 | 44.93635 | 0.28035 | 13.26684 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.40802 | 32.07716 | -0.1091 | 7.25139 |
February | 454.00000 | 22.70844 | 32.03120 | -0.0225 | 6.94508 |
March | 514.00000 | 22.84392 | 31.51732 | -0.0037 | 6.05212 |
April | 485.00000 | 23.87505 | 28.93330 | 0.30641 | 8.05686 |
May | 508.00000 | 23.71878 | 35.61186 | -0.6310 | 15.46011 |
June | 496.00000 | 24.00539 | 42.73170 | -0.4562 | 10.53461 |
July | 497.00000 | 24.18437 | 44.31611 | -0.3574 | 9.03373 |
August | 514.00000 | 24.20081 | 44.50266 | -0.3197 | 8.59049 |
September | 485.00000 | 24.05947 | 41.56139 | -0.4040 | 10.81568 |
October | 502.00000 | 23.35659 | 37.65885 | 0.19655 | 7.23194 |
November | 489.00000 | 22.83180 | 35.41448 | 0.02124 | 6.52654 |
December | 497.00000 | 22.17927 | 31.27584 | -0.1749 | 7.24181 |
Annual Sum or Average | 5943.00000 | 23.36799 | 36.51127 | -0.1650 | 8.65935 |
Minimum of Months | 454.00000 | 22.17927 | 28.93330 | -0.6310 | 6.05212 |
Maximum of Months | 514.00000 | 24.20081 | 44.50266 | 0.30641 | 15.46011 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.82349 | 30.86877 | 0.00026 | 5.97019 |
February | 454.00000 | 23.54976 | 30.17475 | 0.19089 | 6.49468 |
March | 514.00000 | 24.08271 | 28.66167 | 0.32643 | 7.72931 |
April | 485.00000 | 24.52418 | 27.54709 | 0.51764 | 11.40320 |
May | 508.00000 | 24.14329 | 34.45268 | -0.4309 | 10.43805 |
June | 496.00000 | 24.40398 | 41.41883 | -0.2158 | 7.27511 |
July | 497.00000 | 24.58145 | 43.09833 | -0.1032 | 6.91626 |
August | 514.00000 | 24.49392 | 43.54117 | -0.1134 | 6.84358 |
September | 485.00000 | 24.17055 | 41.25934 | -0.3727 | 9.31168 |
October | 502.00000 | 24.07982 | 35.81740 | 0.37549 | 8.55899 |
November | 489.00000 | 24.01691 | 32.58449 | 0.32225 | 7.76568 |
December | 497.00000 | 23.91340 | 27.90140 | 0.25599 | 6.81070 |
Annual Sum or Average | 5943.00000 | 24.06827 | 34.81837 | 0.06102 | 7.96065 |
Minimum of Months | 454.00000 | 22.82349 | 27.54709 | -0.4309 | 5.97019 |
Maximum of Months | 514.00000 | 24.58145 | 43.54117 | 0.51764 | 11.40320 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.90236 | 35.29274 | -0.5188 | 11.78491 |
February | 454.00000 | 21.00036 | 35.98858 | -0.4755 | 10.60631 |
March | 514.00000 | 21.61348 | 34.89570 | -0.3185 | 7.85074 |
April | 485.00000 | 22.84742 | 32.24687 | -0.0099 | 6.06579 |
May | 508.00000 | 23.04621 | 37.93325 | -0.9208 | 24.48920 |
June | 496.00000 | 23.70746 | 44.17010 | -0.6239 | 14.01473 |
July | 497.00000 | 23.79864 | 45.88180 | -0.5733 | 12.64857 |
August | 514.00000 | 23.69598 | 46.74047 | -0.6126 | 13.55229 |
September | 485.00000 | 23.18768 | 44.67661 | -0.8282 | 20.84530 |
October | 502.00000 | 22.00219 | 41.95841 | -0.1704 | 6.58886 |
November | 489.00000 | 21.19418 | 39.54425 | -0.4028 | 9.37686 |
December | 497.00000 | 20.59434 | 34.64772 | -0.6069 | 13.67674 |
Annual Sum or Average | 5943.00000 | 22.30893 | 39.52996 | -0.5061 | 12.64559 |
Minimum of Months | 454.00000 | 20.59434 | 32.24687 | -0.9208 | 6.06579 |
Maximum of Months | 514.00000 | 23.79864 | 46.74047 | -0.0099 | 24.48920 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 20.89965 | 33.86796 | -0.5166 | 11.44388 |
February | 385.00000 | 21.10441 | 34.27587 | -0.4472 | 9.95251 |
March | 433.00000 | 21.48444 | 33.74369 | -0.3423 | 8.12402 |
April | 410.00000 | 23.31428 | 30.15972 | 0.14620 | 7.13979 |
May | 430.00000 | 23.40009 | 35.97443 | -0.7384 | 19.55350 |
June | 418.00000 | 23.81970 | 42.93565 | -0.5177 | 12.95696 |
July | 422.00000 | 24.11378 | 44.32346 | -0.4017 | 10.88317 |
August | 433.00000 | 23.93885 | 45.07280 | -0.4535 | 11.33411 |
September | 410.00000 | 23.62090 | 42.43371 | -0.6127 | 15.87060 |
October | 427.00000 | 22.07188 | 40.45178 | -0.1396 | 6.81929 |
November | 417.00000 | 21.10852 | 38.36870 | -0.4198 | 9.39785 |
December | 422.00000 | 20.54334 | 33.47381 | -0.6192 | 13.91027 |
Annual Sum or Average | 5034.00000 | 22.45768 | 37.95548 | -0.4227 | 11.46116 |
Minimum of Months | 385.00000 | 20.54334 | 30.15972 | -0.7384 | 6.81929 |
Maximum of Months | 433.00000 | 24.11378 | 45.07280 | 0.14620 | 19.55350 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.83275 | 32.91507 | -0.2642 | 8.90787 |
February | 454.00000 | 22.11145 | 33.21411 | -0.1743 | 8.32989 |
March | 514.00000 | 22.03525 | 33.45190 | -0.1999 | 7.24201 |
April | 485.00000 | 23.48483 | 30.02834 | 0.20547 | 7.79100 |
May | 508.00000 | 23.32076 | 36.61253 | -0.7662 | 20.55153 |
June | 496.00000 | 23.70655 | 43.66050 | -0.5690 | 13.74725 |
July | 497.00000 | 23.92364 | 45.12155 | -0.4643 | 11.66610 |
August | 514.00000 | 23.98280 | 45.25309 | -0.4118 | 10.63433 |
September | 485.00000 | 23.85886 | 41.97771 | -0.4708 | 13.15296 |
October | 502.00000 | 22.79012 | 39.32758 | 0.06422 | 7.37303 |
November | 489.00000 | 21.96902 | 37.44777 | -0.1930 | 7.98555 |
December | 497.00000 | 21.18709 | 33.03272 | -0.4437 | 11.01259 |
Annual Sum or Average | 5943.00000 | 22.85420 | 37.71357 | -0.3095 | 10.72457 |
Minimum of Months | 454.00000 | 21.18709 | 30.02834 | -0.7662 | 7.24201 |
Maximum of Months | 514.00000 | 23.98280 | 45.25309 | 0.20547 | 20.55153 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.14473 | 33.95009 | -0.4401 | 10.06289 |
February | 454.00000 | 21.45218 | 34.29064 | -0.3418 | 8.77067 |
March | 514.00000 | 21.77109 | 33.64646 | -0.2581 | 7.27997 |
April | 485.00000 | 23.28079 | 30.51723 | 0.14569 | 7.02917 |
May | 508.00000 | 23.31002 | 36.57699 | -0.7520 | 20.16268 |
June | 496.00000 | 23.86108 | 43.20513 | -0.4766 | 11.84104 |
July | 497.00000 | 24.00737 | 44.88061 | -0.4007 | 10.54893 |
August | 514.00000 | 23.95035 | 45.46029 | -0.4306 | 10.54169 |
September | 485.00000 | 23.45901 | 43.22492 | -0.6597 | 16.86327 |
October | 502.00000 | 22.22917 | 40.59977 | -0.0891 | 6.43655 |
November | 489.00000 | 21.38373 | 38.35650 | -0.3378 | 8.34100 |
December | 497.00000 | 20.76942 | 33.55683 | -0.5471 | 11.91831 |
Annual Sum or Average | 5943.00000 | 22.55930 | 38.22453 | -0.3834 | 10.83182 |
Minimum of Months | 454.00000 | 20.76942 | 30.51723 | -0.7520 | 6.43655 |
Maximum of Months | 514.00000 | 24.00737 | 45.46029 | 0.14569 | 20.16268 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.19614 | 36.70377 | -0.7494 | 19.18532 |
February | 454.00000 | 20.24475 | 37.54119 | -0.7145 | 18.05314 |
March | 514.00000 | 20.80579 | 36.51270 | -0.5564 | 12.56870 |
April | 485.00000 | 22.08563 | 33.77922 | -0.2025 | 7.84641 |
May | 508.00000 | 22.33371 | 39.58175 | -1.1676 | 35.92781 |
June | 496.00000 | 23.32756 | 45.25216 | -0.7530 | 18.90445 |
July | 497.00000 | 23.48687 | 46.74839 | -0.6782 | 16.60875 |
August | 514.00000 | 23.39406 | 47.65275 | -0.7179 | 17.39878 |
September | 485.00000 | 22.56712 | 46.38728 | -1.0458 | 30.38416 |
October | 502.00000 | 21.00496 | 44.57762 | -0.4388 | 10.42984 |
November | 489.00000 | 20.38658 | 41.38965 | -0.6496 | 15.88862 |
December | 497.00000 | 19.99893 | 35.90312 | -0.8123 | 21.53652 |
Annual Sum or Average | 5943.00000 | 21.66361 | 41.03293 | -0.7078 | 18.73864 |
Minimum of Months | 454.00000 | 19.99893 | 33.77922 | -1.1676 | 7.84641 |
Maximum of Months | 514.00000 | 23.48687 | 47.65275 | -0.2025 | 35.92781 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.29985 | 35.81332 | -0.7135 | 17.77223 |
February | 454.00000 | 20.44659 | 36.50708 | -0.6522 | 15.89589 |
March | 514.00000 | 20.88982 | 35.65848 | -0.5253 | 11.77412 |
April | 485.00000 | 22.93823 | 31.32651 | 0.04936 | 7.70274 |
May | 508.00000 | 23.00543 | 37.43433 | -0.8745 | 25.06678 |
June | 496.00000 | 23.60219 | 43.91021 | -0.5808 | 15.10408 |
July | 497.00000 | 23.91115 | 45.12872 | -0.4540 | 12.13630 |
August | 514.00000 | 23.80475 | 45.77899 | -0.4857 | 12.28113 |
September | 485.00000 | 23.31747 | 43.60401 | -0.7183 | 19.43699 |
October | 502.00000 | 21.39104 | 43.13551 | -0.3301 | 9.39098 |
November | 489.00000 | 20.47775 | 40.58363 | -0.6201 | 14.76847 |
December | 497.00000 | 20.05597 | 35.22715 | -0.7928 | 20.75862 |
Annual Sum or Average | 5943.00000 | 22.02210 | 39.53980 | -0.5585 | 15.17347 |
Minimum of Months | 454.00000 | 20.05597 | 31.32651 | -0.8745 | 7.70274 |
Maximum of Months | 514.00000 | 23.91115 | 45.77899 | 0.04936 | 25.06678 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.94925 | 34.56208 | -0.5273 | 14.03194 |
February | 454.00000 | 21.22859 | 34.94968 | -0.4344 | 12.55295 |
March | 514.00000 | 21.19476 | 35.12687 | -0.4419 | 10.82384 |
April | 485.00000 | 22.93529 | 31.22611 | 0.05926 | 8.25517 |
May | 508.00000 | 22.75230 | 37.98309 | -0.9703 | 29.35338 |
June | 496.00000 | 23.35534 | 44.61900 | -0.6875 | 18.24051 |
July | 497.00000 | 23.63431 | 45.89679 | -0.5599 | 15.18179 |
August | 514.00000 | 23.74505 | 45.92356 | -0.4946 | 13.30102 |
September | 485.00000 | 23.45443 | 43.07773 | -0.6229 | 18.54386 |
October | 502.00000 | 21.95545 | 41.62477 | -0.1674 | 8.95823 |
November | 489.00000 | 21.07142 | 39.39342 | -0.4547 | 12.13354 |
December | 497.00000 | 20.45132 | 34.48325 | -0.6759 | 17.53561 |
Annual Sum or Average | 5943.00000 | 22.23303 | 39.11306 | -0.4999 | 14.94035 |
Minimum of Months | 454.00000 | 20.45132 | 31.22611 | -0.9703 | 8.25517 |
Maximum of Months | 514.00000 | 23.74505 | 45.92356 | 0.05926 | 29.35338 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.49829 | 35.17038 | -0.6475 | 15.80618 |
February | 454.00000 | 20.78156 | 35.63326 | -0.5482 | 13.53778 |
March | 514.00000 | 21.09126 | 35.01386 | -0.4575 | 10.48747 |
April | 485.00000 | 22.65163 | 31.76789 | -0.0127 | 7.73204 |
May | 508.00000 | 22.75361 | 37.89868 | -0.9479 | 28.73263 |
June | 496.00000 | 23.52809 | 44.08783 | -0.5888 | 15.74649 |
July | 497.00000 | 23.73344 | 45.59894 | -0.4913 | 13.64631 |
August | 514.00000 | 23.69035 | 46.18636 | -0.5204 | 13.34010 |
September | 485.00000 | 22.95248 | 44.54527 | -0.8383 | 23.97894 |
October | 502.00000 | 21.44817 | 42.71424 | -0.3022 | 8.59880 |
November | 489.00000 | 20.71648 | 39.83471 | -0.5431 | 12.71446 |
December | 497.00000 | 20.24674 | 34.62138 | -0.7260 | 18.06692 |
Annual Sum or Average | 5943.00000 | 22.01665 | 39.45703 | -0.5528 | 15.21284 |
Minimum of Months | 454.00000 | 20.24674 | 31.76789 | -0.9479 | 7.73204 |
Maximum of Months | 514.00000 | 23.73344 | 46.18636 | -0.0127 | 28.73263 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.164207E+09 | 1944.25 | 09-JAN-05:13 | 23.71 | 0.844741E+09 | 0.00 | 0.100895E+10 | 0.16 | 5.26 | 09-JAN-19:40 | 0.00 | 0.00 |
February | 0.265280E+09 | 1944.21 | 15-FEB-05:13 | 38.25 | 0.136540E+10 | 0.00 | 0.163068E+10 | 0.29 | 5.25 | 23-FEB-06:50 | 0.00 | 0.00 |
March | 0.308217E+09 | 1944.01 | 29-MAR-05:06 | 44.46 | 0.158637E+10 | 0.00 | 0.189459E+10 | 0.31 | 5.26 | 08-MAR-06:40 | 0.00 | 0.00 |
April | 0.647332E+10 | 67477.22 | 28-APR-15:00 | 83.41 | 0.414550E+11 | 0.00 | 0.479283E+11 | 0.66 | 7.83 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.753264E+10 | 70026.40 | 22-MAY-15:50 | 82.06 | 0.498901E+11 | 0.00 | 0.574227E+11 | 0.65 | 7.77 | 23-MAY-14:00 | 0.00 | 0.00 |
June | 0.207657E+11 | 94217.23 | 13-JUN-16:00 | 188.36 | 0.140824E+12 | 0.00 | 0.161590E+12 | 1.59 | 7.82 | 27-JUN-05:03 | 0.00 | 0.00 |
July | 0.366213E+11 | 82850.97 | 21-JUL-15:40 | 330.37 | 0.245551E+12 | 0.00 | 0.282172E+12 | 2.69 | 7.80 | 24-JUL-12:50 | 0.00 | 0.00 |
August | 0.482367E+11 | 81770.31 | 14-AUG-15:10 | 399.27 | 0.324596E+12 | 0.00 | 0.372832E+12 | 3.33 | 7.81 | 04-AUG-14:10 | 0.00 | 0.00 |
September | 0.248249E+11 | 73655.15 | 13-SEP-13:30 | 241.77 | 0.164246E+12 | 0.00 | 0.189070E+12 | 2.00 | 7.79 | 12-SEP-14:00 | 0.00 | 0.00 |
October | 0.193294E+10 | 35990.06 | 07-OCT-15:00 | 41.35 | 0.102872E+11 | 0.00 | 0.122202E+11 | 0.29 | 6.61 | 07-OCT-15:00 | 0.00 | 0.00 |
November | 0.235465E+09 | 9133.58 | 24-NOV-12:00 | 31.26 | 0.121038E+10 | 0.00 | 0.144585E+10 | 0.22 | 5.25 | 17-NOV-06:40 | 0.00 | 0.00 |
December | 0.141226E+09 | 1945.40 | 26-DEC-04:10 | 20.34 | 0.726230E+09 | 0.00 | 0.867456E+09 | 0.14 | 5.26 | 26-DEC-06:40 | 0.00 | 0.00 |
Annual Sum or Average | 0.147502E+12 | 1524.63 | 0.982582E+12 | 0.00 | 0.113008E+13 | 1.03 | 0.00 | 0.00 | ||||
Minimum of Months | 0.141226E+09 | 1944.01 | 20.34 | 0.726230E+09 | 0.00 | 0.867456E+09 | 0.14 | 5.25 | 0.00 | 0.00 | ||
Maximum of Months | 0.482367E+11 | 94217.23 | 399.27 | 0.324596E+12 | 0.00 | 0.372832E+12 | 3.33 | 7.83 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 40486334.93 | 67477.22 | 28-APR-15:00 | 0.17 | 0.316919E+09 | 0.00 | 0.357406E+09 | 0.00 | 7.83 | 28-APR-15:00 | 0.00 | 0.00 |
May | 0.732936E+09 | 70026.40 | 22-MAY-15:50 | 3.17 | 0.557518E+10 | 0.00 | 0.630812E+10 | 0.03 | 7.71 | 22-MAY-15:50 | 0.00 | 0.00 |
June | 0.450396E+10 | 94217.23 | 13-JUN-16:00 | 18.19 | 0.337688E+11 | 0.00 | 0.382727E+11 | 0.19 | 7.74 | 20-JUN-15:00 | 0.00 | 0.00 |
July | 0.467152E+10 | 82850.97 | 21-JUL-15:40 | 19.07 | 0.351377E+11 | 0.00 | 0.398092E+11 | 0.19 | 7.76 | 06-JUL-13:30 | 0.00 | 0.00 |
August | 0.368928E+10 | 81770.31 | 14-AUG-15:10 | 15.33 | 0.278399E+11 | 0.00 | 0.315291E+11 | 0.16 | 7.74 | 21-AUG-15:30 | 0.00 | 0.00 |
September | 0.292477E+10 | 73655.15 | 13-SEP-13:30 | 12.67 | 0.222281E+11 | 0.00 | 0.251529E+11 | 0.13 | 7.79 | 12-SEP-14:00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.165629E+11 | 68.59 | 0.124867E+12 | 0.00 | 0.141430E+12 | 0.06 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.467152E+10 | 94217.23 | 19.07 | 0.351377E+11 | 0.00 | 0.398092E+11 | 0.19 | 7.83 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.120892E+11 | 744.00 | 18351.13 | 29-JAN-06:00 | 179522.00 | 19-JAN-16:10 | 21.74 | 18.33 | 13.97 |
February | 0.177518E+11 | 672.00 | 20969.28 | 07-FEB-15:00 | 325084.79 | 19-FEB-17:07 | 24.65 | 18.33 | 13.97 |
March | 0.454780E+11 | 744.00 | 45871.58 | 25-MAR-13:00 | 590949.06 | 31-MAR-24:00 | 27.54 | 18.33 | 13.97 |
April | 0.848537E+11 | 720.00 | 49248.27 | 15-APR-13:20 | 679283.39 | 30-APR-19:03 | 31.00 | 18.77 | 13.97 |
May | 0.288336E+11 | 744.00 | 49248.27 | 11-MAY-14:50 | 318855.29 | 31-MAY-24:00 | 22.18 | 18.45 | 13.97 |
June | 0.816038E+11 | 720.00 | 49248.27 | 01-JUN-11:50 | 454611.94 | 30-JUN-24:00 | 25.75 | 19.05 | 13.97 |
July | 0.116523E+12 | 744.00 | 49248.27 | 01-JUL-12:40 | 598198.81 | 31-JUL-24:00 | 29.81 | 20.17 | 13.97 |
August | 0.127367E+12 | 744.00 | 49248.27 | 01-AUG-06:10 | 669112.82 | 20-AUG-17:02 | 33.78 | 21.27 | 13.97 |
September | 0.562567E+11 | 720.00 | 49248.27 | 01-SEP-09:40 | 316369.88 | 30-SEP-24:00 | 22.62 | 18.81 | 13.97 |
October | 0.465631E+11 | 744.00 | 49248.27 | 05-OCT-13:50 | 451040.04 | 31-OCT-24:00 | 24.84 | 18.35 | 13.97 |
November | 0.491608E+11 | 720.00 | 49248.27 | 24-NOV-11:20 | 466387.25 | 24-NOV-12:10 | 27.53 | 18.33 | 13.97 |
December | 0.540806E+11 | 744.00 | 47340.87 | 23-DEC-11:00 | 593094.22 | 22-DEC-22:10 | 30.23 | 18.33 | 13.97 |
Annual Sum or Average | 0.720561E+12 | 8760.00 | 26.82 | 18.88 | 13.97 | ||||
Minimum of Months | 0.120892E+11 | 672.00 | 18351.13 | 179522.00 | 21.74 | 18.33 | 13.97 | ||
Maximum of Months | 0.127367E+12 | 744.00 | 49248.27 | 679283.39 | 33.78 | 21.27 | 13.97 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 173664.19 | 31-JAN-07:00 | 21.00 | 20.99 | 0.13 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 181111.36 | 17-FEB-06:50 | 21.01 | 21.01 | 0.42 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 180916.14 | 08-MAR-06:03 | 20.96 | 20.95 | 0.39 |
April | 45502686.61 | 38.24 | 1314.71 | 28-APR-14:30 | 890630.09 | 28-APR-15:00 | 21.08 | 20.97 | 3.75 |
May | 0.145971E+09 | 48.00 | 13462.07 | 22-MAY-14:30 | 848124.17 | 22-MAY-13:30 | 21.13 | 21.00 | 4.04 |
June | 0.115395E+10 | 129.40 | 13462.07 | 12-JUN-12:20 | 888754.68 | 20-JUN-15:00 | 21.47 | 21.10 | 10.79 |
July | 0.119345E+10 | 248.91 | 13462.07 | 10-JUL-08:30 | 842396.43 | 12-JUL-15:40 | 21.73 | 21.11 | 18.67 |
August | 0.117278E+10 | 335.51 | 13462.07 | 14-AUG-09:50 | 879362.95 | 28-AUG-15:30 | 21.91 | 21.10 | 23.47 |
September | 0.566899E+09 | 168.71 | 13462.07 | 11-SEP-13:20 | 846807.18 | 25-SEP-13:20 | 21.55 | 21.11 | 13.58 |
October | 3762734.71 | 15.27 | 170.31 | 11-OCT-15:00 | 282079.79 | 07-OCT-15:00 | 21.06 | 21.03 | 1.52 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 176580.16 | 28-NOV-05:50 | 21.01 | 21.01 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 180839.92 | 31-DEC-05:40 | 21.02 | 21.01 | 0.15 |
Annual Sum or Average | 0.428231E+10 | 984.04 | 21.24 | 21.03 | 6.47 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 173664.19 | 20.96 | 20.95 | 0.13 | ||
Maximum of Months | 0.119345E+10 | 335.51 | 13462.07 | 890630.09 | 21.91 | 21.11 | 23.47 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.00 | 21.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.01 | 21.01 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 20.96 | 20.96 | 0.00 |
April | 671534.74 | 0.17 | 1119.22 | 28-APR-15:00 | 890630.09 | 28-APR-15:00 | 21.08 | 21.08 | 0.01 |
May | 55615441.38 | 2.17 | 13462.07 | 22-MAY-14:30 | 848124.17 | 22-MAY-13:30 | 21.13 | 21.11 | 0.14 |
June | 0.582392E+09 | 13.19 | 13462.07 | 12-JUN-13:40 | 888754.68 | 20-JUN-15:00 | 21.47 | 21.40 | 0.85 |
July | 0.372671E+09 | 12.00 | 13462.07 | 10-JUL-08:50 | 842396.43 | 12-JUL-15:40 | 21.73 | 21.67 | 0.75 |
August | 0.228052E+09 | 9.67 | 13462.07 | 14-AUG-10:20 | 879362.95 | 28-AUG-15:30 | 21.91 | 21.85 | 0.60 |
September | 0.182417E+09 | 4.67 | 13462.07 | 11-SEP-13:30 | 834954.47 | 13-SEP-13:00 | 21.55 | 21.52 | 0.30 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 21.06 | 21.06 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.01 | 21.01 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.02 | 21.02 | 0.00 |
Annual Sum or Average | 0.142182E+10 | 41.86 | 21.24 | 21.23 | 0.22 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 20.96 | 20.96 | 0.00 | ||
Maximum of Months | 0.582392E+09 | 13.19 | 13462.07 | 890630.09 | 21.91 | 21.85 | 0.85 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.219453E+12 | 0.00 | 427.83 | 963684.60 | 04-JAN-06:02 | 0.00 | 28.14 | 57.95 | 0.40 | 0.00 | 0.04 | 0.49 | 04-JAN-06:02 |
February | 0.144055E+12 | 0.00 | 376.40 | 971409.87 | 13-FEB-06:01 | 0.00 | 27.29 | 57.11 | 0.28 | 0.00 | 0.03 | 0.49 | 13-FEB-06:01 |
March | 0.990647E+11 | 0.00 | 389.36 | 950624.00 | 07-MAR-06:02 | 0.00 | 25.43 | 53.91 | 0.17 | 0.00 | 0.02 | 0.48 | 07-MAR-06:02 |
April | 0.131125E+11 | 0.00 | 128.92 | 227819.94 | 08-APR-06:05 | 0.00 | 24.55 | 34.40 | 0.02 | 0.00 | 0.00 | 0.12 | 08-APR-06:05 |
May | 0.553425E+10 | 0.00 | 101.73 | 557222.80 | 05-MAY-05:03 | 0.00 | 23.21 | 30.86 | 0.01 | 0.00 | 0.00 | 0.28 | 05-MAY-05:03 |
June | 0.141862E+09 | 0.00 | 9.46 | 58067.88 | 08-JUN-05:02 | 0.00 | 22.32 | 23.08 | 0.00 | 0.00 | 0.00 | 0.03 | 08-JUN-05:02 |
July | 12993328.67 | 0.00 | 5.08 | 2379.94 | 31-JUL-05:03 | 0.00 | 22.13 | 22.52 | 0.00 | 0.00 | 0.00 | 0.00 | 31-JUL-05:03 |
August | 809604.96 | 0.00 | 0.17 | 1354.75 | 24-AUG-06:10 | 0.00 | 22.10 | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | 24-AUG-06:10 |
September | 0.900556E+09 | 0.00 | 37.88 | 85336.11 | 21-SEP-06:10 | 0.00 | 22.17 | 25.18 | 0.00 | 0.00 | 0.00 | 0.04 | 21-SEP-06:10 |
October | 0.252129E+11 | 0.00 | 254.08 | 593202.32 | 28-OCT-05:03 | 0.00 | 23.76 | 42.81 | 0.04 | 0.00 | 0.00 | 0.30 | 28-OCT-05:03 |
November | 0.105958E+12 | 0.00 | 374.93 | 1023927.91 | 20-NOV-05:01 | 0.00 | 24.71 | 53.20 | 0.19 | 0.00 | 0.02 | 0.52 | 20-NOV-05:01 |
December | 0.246113E+12 | 0.00 | 453.10 | 1004155.81 | 18-DEC-05:01 | 0.00 | 28.14 | 59.93 | 0.44 | 0.00 | 0.05 | 0.51 | 18-DEC-05:01 |
Annual Sum or Average | 0.859559E+12 | 0.00 | 2558.93 | 0.00 | 24.48 | 40.19 | 0.13 | 0.00 | 0.01 | ||||
Minimum of Months | 809604.96 | 0.00 | 0.17 | 1354.75 | 0.00 | 22.10 | 22.11 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.246113E+12 | 0.00 | 453.10 | 1023927.91 | 0.00 | 28.14 | 59.93 | 0.44 | 0.00 | 0.05 | 0.52 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 21.74 | 21.74 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 24.65 | 24.65 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 27.54 | 27.54 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.00 | 31.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 22.18 | 22.18 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 25.75 | 25.75 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 29.81 | 29.81 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 33.78 | 33.78 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 22.62 | 22.62 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 24.84 | 24.84 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 27.53 | 27.53 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 30.23 | 30.23 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 26.82 | 26.82 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.74 | 21.74 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.78 | 33.78 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 897.69 | 0.00 | 0.83 | 897.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 30-JAN-06:13 | 0.78 | 30-JAN-06:13 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 2861.97 | 0.00 | 1.99 | 2861.97 | 0.00 | 0.00 | 0.00 | 0.00 | 1.05 | 20-MAR-04:50 | 1.05 | 20-MAR-04:50 | 0.00 | 0.00 | 0.00 |
April | 0.415575E+10 | 0.00 | 55.03 | 0.415001E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74165.38 | 30-APR-15:02 | 74165.38 | 30-APR-15:02 | 0.00 | 0.00 | 0.00 |
May | 0.513317E+10 | 0.00 | 67.50 | 0.513317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 90113.46 | 22-MAY-15:00 | 90113.46 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.170406E+11 | 0.00 | 174.32 | 0.166153E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116127.94 | 13-JUN-16:00 | 107268.76 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.288682E+11 | 0.00 | 310.03 | 0.287131E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109903.95 | 21-JUL-15:20 | 109903.95 | 21-JUL-15:20 | 0.00 | 0.00 | 0.00 |
August | 0.383842E+11 | 0.00 | 381.02 | 0.379862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 114802.59 | 14-AUG-15:00 | 114802.59 | 14-AUG-15:00 | 0.00 | 0.00 | 0.00 |
September | 0.176532E+11 | 0.00 | 212.18 | 0.175849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 81151.75 | 13-SEP-14:20 | 81151.75 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 |
October | 0.929994E+09 | 0.00 | 24.17 | 0.929994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 22732.22 | 11-OCT-15:00 | 22732.22 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 13330363.93 | 0.00 | 1.00 | 13330363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 7941.22 | 24-NOV-12:00 | 7941.22 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 1589.79 | 0.00 | 1.26 | 1589.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.94 | 26-DEC-06:13 | 0.94 | 26-DEC-06:13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112178E+12 | 0.00 | 1229.33 | 0.111126E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.383842E+11 | 0.00 | 381.02 | 0.379862E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 116127.94 | 114802.59 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 57669.71 | 0.00 | 23.36 | 57669.71 | 0.00 | 0.00 | 0.00 | 0.00 | 3.35 | 02-JAN-05:27 | 3.35 | 02-JAN-05:27 | 0.00 | 0.00 | 0.00 |
February | 84401.45 | 0.00 | 38.08 | 84401.45 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 13-FEB-06:01 | 1.41 | 13-FEB-06:01 | 0.00 | 0.00 | 0.00 |
March | 104418.45 | 0.00 | 42.97 | 104418.45 | 0.00 | 0.00 | 0.00 | 0.00 | 4.24 | 27-MAR-05:02 | 4.24 | 27-MAR-05:02 | 0.00 | 0.00 | 0.00 |
April | 0.331621E+11 | 0.00 | 77.07 | 0.331410E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 715598.85 | 30-APR-14:51 | 715598.85 | 30-APR-14:51 | 0.00 | 0.00 | 0.00 |
May | 0.422362E+11 | 0.00 | 77.82 | 0.422362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 755056.80 | 22-MAY-15:00 | 755056.80 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.137546E+12 | 0.00 | 171.14 | 0.134450E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1043876.95 | 13-JUN-16:00 | 948876.83 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.223227E+12 | 0.00 | 294.26 | 0.222704E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 967036.22 | 21-JUL-15:40 | 967036.22 | 21-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.282184E+12 | 0.00 | 372.81 | 0.280695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 907428.57 | 14-AUG-15:50 | 907428.57 | 14-AUG-15:50 | 0.00 | 0.00 | 0.00 |
September | 0.150846E+12 | 0.00 | 226.12 | 0.149723E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 754057.27 | 13-SEP-14:40 | 754057.27 | 13-SEP-14:40 | 0.00 | 0.00 | 0.00 |
October | 0.714757E+10 | 0.00 | 39.86 | 0.714757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191453.87 | 07-OCT-15:00 | 191453.87 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 47130665.60 | 0.00 | 30.58 | 47130665.60 | 0.00 | 0.00 | 0.00 | 0.00 | 34976.39 | 24-NOV-12:00 | 34976.39 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 47554.73 | 0.00 | 19.26 | 47554.73 | 0.00 | 0.00 | 0.00 | 0.00 | 2.35 | 26-DEC-06:02 | 2.35 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.876395E+12 | 0.00 | 1413.33 | 0.870145E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 47554.73 | 0.00 | 19.26 | 47554.73 | 0.00 | 0.00 | 0.00 | 0.00 | 1.41 | 1.41 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.282184E+12 | 0.00 | 372.81 | 0.280695E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1043876.95 | 967036.22 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 27.89 | 0.00 | 0.02 | 27.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 11-JAN-04:09 | 0.33 | 11-JAN-04:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 182.78 | 0.00 | 0.17 | 182.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.30 | 18-MAR-12:40 | 0.30 | 18-MAR-12:40 | 0.00 | 0.00 | 0.00 |
April | 0.326169E+10 | 0.00 | 51.75 | 0.326169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71618.80 | 30-APR-15:12 | 71618.80 | 30-APR-15:12 | 0.00 | 0.00 | 0.00 |
May | 0.441918E+10 | 0.00 | 64.07 | 0.441918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85737.35 | 22-MAY-15:00 | 85737.35 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.146872E+11 | 0.00 | 159.36 | 0.143366E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126614.41 | 13-JUN-16:00 | 117165.94 | 13-JUN-15:30 | 0.00 | 0.00 | 0.00 |
July | 0.232846E+11 | 0.00 | 278.26 | 0.232266E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 115771.07 | 21-JUL-15:40 | 115771.07 | 21-JUL-15:40 | 0.00 | 0.00 | 0.00 |
August | 0.275827E+11 | 0.00 | 360.72 | 0.274739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 106144.72 | 14-AUG-16:00 | 106144.72 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.137438E+11 | 0.00 | 196.01 | 0.136853E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78646.76 | 13-SEP-15:20 | 78646.76 | 13-SEP-15:20 | 0.00 | 0.00 | 0.00 |
October | 0.531325E+09 | 0.00 | 23.50 | 0.531325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 18047.51 | 07-OCT-15:00 | 18047.51 | 07-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 4474093.86 | 0.00 | 0.67 | 4474093.86 | 0.00 | 0.00 | 0.00 | 0.00 | 3328.76 | 24-NOV-12:00 | 3328.76 | 24-NOV-12:00 | 0.00 | 0.00 | 0.00 |
December | 21497.12 | 0.00 | 0.77 | 21497.12 | 0.00 | 0.00 | 0.00 | 0.00 | 241.36 | 26-DEC-04:09 | 241.36 | 26-DEC-04:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.875150E+11 | 0.00 | 1135.31 | 0.869391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.275827E+11 | 0.00 | 360.72 | 0.274739E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 126614.41 | 117165.94 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 18311.87 | 0.00 | 0.33 | 18311.87 | 0.00 | 0.00 | 0.00 | 0.00 | 27.00 | 20-JAN-21:20 | 27.00 | 20-JAN-21:20 | 0.00 | 0.00 | 0.00 |
February | 4482.34 | 0.00 | 0.17 | 4482.34 | 0.00 | 0.00 | 0.00 | 0.00 | 7.47 | 15-FEB-21:20 | 7.47 | 15-FEB-21:20 | 0.00 | 0.00 | 0.00 |
March | 843054.49 | 0.00 | 0.04 | 383024.99 | 0.00 | 0.00 | 0.00 | 0.00 | 5620.36 | 18-MAR-05:03 | 2553.50 | 18-MAR-05:03 | 0.00 | 0.00 | 0.00 |
April | 0.654900E+09 | 0.00 | 18.08 | 0.654900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25723.73 | 28-APR-15:00 | 25723.73 | 28-APR-15:00 | 0.00 | 0.00 | 0.00 |
May | 0.207754E+10 | 0.00 | 32.13 | 0.207754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53700.89 | 22-MAY-15:00 | 53700.89 | 22-MAY-15:00 | 0.00 | 0.00 | 0.00 |
June | 0.752776E+10 | 0.00 | 85.83 | 0.749062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56417.37 | 12-JUN-15:00 | 56417.37 | 12-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.123686E+11 | 0.00 | 173.98 | 0.122859E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62464.96 | 10-JUL-11:00 | 62464.96 | 10-JUL-11:00 | 0.00 | 0.00 | 0.00 |
August | 0.161247E+11 | 0.00 | 256.15 | 0.160920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 61583.57 | 14-AUG-16:00 | 61583.57 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 |
September | 0.783205E+10 | 0.00 | 118.28 | 0.780943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46424.50 | 25-SEP-13:00 | 46424.50 | 25-SEP-13:00 | 0.00 | 0.00 | 0.00 |
October | 0.128931E+09 | 0.00 | 8.50 | 0.115451E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 20411.63 | 20-OCT-05:03 | 9525.30 | 13-OCT-05:02 | 0.00 | 0.00 | 0.00 |
November | 14806520.58 | 0.00 | 1.01 | 13679810.48 | 0.00 | 0.00 | 0.00 | 0.00 | 11822.17 | 15-NOV-05:02 | 11822.17 | 15-NOV-05:02 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.467301E+11 | 0.00 | 694.50 | 0.465400E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.161247E+11 | 0.00 | 256.15 | 0.160920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62464.96 | 62464.96 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.320555E+12 | 0.802483E+11 | 744.00 | 0.320536E+12 | 18722402.61 | 0.00 | 0.34 | 20-JAN-22:05 | 0.31 | 10-JAN-08:00 | 124195.99 | 19-JAN-22:05 | 124195.99 | 19-JAN-22:05 | 1062.91 | 18-JAN-17:00 | 31101.38 | 20-JAN-22:05 | 0.00 |
February | 0.510557E+12 | 0.121359E+12 | 672.00 | 0.510545E+12 | 11466478.69 | 0.00 | 0.56 | 13-FEB-22:03 | 0.53 | 01-FEB-18:10 | 215702.20 | 23-FEB-22:03 | 215702.20 | 23-FEB-22:03 | 1197.55 | 08-FEB-16:40 | 51289.29 | 13-FEB-22:03 | 0.00 |
March | 0.812015E+12 | 0.185137E+12 | 744.00 | 0.812013E+12 | 1772575.23 | 0.00 | 0.95 | 31-MAR-24:00 | 0.73 | 20-MAR-06:30 | 394133.95 | 31-MAR-24:00 | 394133.95 | 31-MAR-24:00 | 1827.46 | 20-MAR-06:10 | 86806.75 | 31-MAR-24:00 | 0.00 |
April | 0.102694E+13 | 0.229071E+12 | 720.00 | 0.102694E+13 | -0.0 | 0.00 | 1.00 | 29-APR-17:02 | 0.37 | 30-APR-24:00 | 408594.93 | 30-APR-19:43 | 408594.93 | 30-APR-19:43 | 0.00 | 28-APR-10:30 | 119619.10 | 30-APR-18:11 | 0.00 |
May | 0.327495E+12 | 0.815575E+11 | 744.00 | 0.326988E+12 | 0.507007E+09 | 0.00 | 0.54 | 31-MAY-24:00 | 0.31 | 05-MAY-06:05 | 211350.74 | 31-MAY-24:00 | 211350.74 | 31-MAY-24:00 | 3902.10 | 23-MAY-14:40 | 49250.88 | 31-MAY-24:00 | 0.00 |
June | 0.557432E+12 | 0.133062E+12 | 720.00 | 0.555129E+12 | 0.230295E+10 | 0.00 | 0.74 | 30-JUN-24:00 | 0.53 | 01-JUN-06:20 | 302736.20 | 30-JUN-24:00 | 302736.20 | 30-JUN-24:00 | 5642.00 | 26-JUN-17:50 | 72346.79 | 13-JUN-17:00 | 0.00 |
July | 0.824304E+12 | 0.195760E+12 | 744.00 | 0.821452E+12 | 0.285138E+10 | 0.00 | 0.93 | 31-JUL-24:00 | 0.73 | 01-JUL-06:30 | 395434.33 | 31-JUL-24:00 | 395434.33 | 31-JUL-24:00 | 5859.79 | 18-JUL-16:00 | 110606.63 | 22-JUL-18:00 | 0.00 |
August | 0.106938E+13 | 0.253489E+12 | 744.00 | 0.106667E+13 | 0.270846E+10 | 0.00 | 1.00 | 14-AUG-12:20 | 0.37 | 31-AUG-23:55 | 405437.90 | 17-AUG-15:30 | 403240.48 | 20-AUG-17:02 | 6006.55 | 11-AUG-14:00 | 127243.55 | 14-AUG-17:40 | 0.00 |
September | 0.322016E+12 | 0.802558E+11 | 720.00 | 0.320101E+12 | 0.191495E+10 | 0.00 | 0.55 | 30-SEP-24:00 | 0.31 | 20-SEP-06:10 | 211045.17 | 30-SEP-24:00 | 211045.17 | 30-SEP-24:00 | 4337.76 | 19-SEP-14:10 | 50226.56 | 30-SEP-24:00 | 0.00 |
October | 0.572047E+12 | 0.134673E+12 | 744.00 | 0.571483E+12 | 0.564352E+09 | 0.00 | 0.75 | 31-OCT-24:00 | 0.53 | 19-OCT-06:10 | 302901.56 | 31-OCT-24:00 | 302901.56 | 31-OCT-24:00 | 4149.80 | 17-OCT-15:20 | 69085.85 | 31-OCT-24:00 | 0.00 |
November | 0.788612E+12 | 0.178651E+12 | 720.00 | 0.788295E+12 | 0.317067E+09 | 0.00 | 0.77 | 17-NOV-22:03 | 0.73 | 25-NOV-07:30 | 307962.20 | 03-NOV-21:03 | 307962.20 | 03-NOV-21:03 | 3256.91 | 08-NOV-15:00 | 72138.94 | 24-NOV-12:00 | 0.00 |
December | 0.105783E+13 | 0.232984E+12 | 744.00 | 0.105783E+13 | -0.0 | 0.00 | 0.96 | 13-DEC-22:03 | 0.93 | 20-DEC-18:10 | 399659.45 | 26-DEC-22:03 | 399659.45 | 26-DEC-22:03 | 0.00 | 02-DEC-08:30 | 87923.60 | 13-DEC-22:03 | 0.00 |
Annual Sum or Average | 0.818918E+13 | 0.190625E+13 | 8760.00 | 0.817798E+13 | 0.111981E+11 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.320555E+12 | 0.802483E+11 | 672.00 | 0.320101E+12 | -0.0 | 0.00 | 0.34 | 0.31 | 124195.99 | 124195.99 | 0.00 | 31101.38 | 0.00 | ||||||
Maximum of Months | 0.106938E+13 | 0.253489E+12 | 744.00 | 0.106667E+13 | 0.285138E+10 | 0.00 | 1.00 | 0.93 | 408594.93 | 408594.93 | 6006.55 | 127243.55 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.414230E+10 | 0.106622E+10 | 744.00 | 0.414077E+10 | 1534560.00 | 0.00 | 0.27 | 16-JAN-16:20 | 0.11 | 10-JAN-08:00 | 2236.33 | 01-JAN-16:10 | 2230.62 | 01-JAN-16:05 | 52.70 | 18-JAN-16:20 | 538.32 | 16-JAN-16:20 | 0.00 |
February | 0.867132E+10 | 0.208402E+10 | 672.00 | 0.867004E+10 | 1283353.41 | 0.00 | 0.53 | 19-FEB-17:00 | 0.37 | 02-FEB-08:00 | 4353.84 | 19-FEB-17:00 | 4353.84 | 19-FEB-17:00 | 54.93 | 07-FEB-17:00 | 1047.80 | 19-FEB-17:00 | 0.00 |
March | 0.150169E+11 | 0.343711E+10 | 744.00 | 0.150166E+11 | 328562.73 | 0.00 | 0.86 | 31-MAR-24:00 | 0.59 | 18-MAR-17:00 | 7585.15 | 31-MAR-24:00 | 7585.15 | 31-MAR-24:00 | 67.19 | 20-MAR-06:10 | 1695.13 | 31-MAR-24:00 | 0.00 |
April | 0.199500E+11 | 0.444522E+10 | 720.00 | 0.199497E+11 | 319066.33 | 0.00 | 1.00 | 30-APR-17:12 | 0.31 | 30-APR-24:00 | 8693.44 | 30-APR-19:03 | 8693.44 | 30-APR-19:03 | 57.17 | 28-APR-11:00 | 2586.59 | 30-APR-18:10 | 0.00 |
May | 0.534160E+10 | 0.132563E+10 | 744.00 | 0.532084E+10 | 20768331.74 | 0.00 | 0.45 | 31-MAY-24:00 | 0.17 | 05-MAY-06:05 | 3925.58 | 31-MAY-24:00 | 3925.58 | 31-MAY-24:00 | 140.10 | 23-MAY-15:00 | 899.76 | 31-MAY-24:00 | 0.00 |
June | 0.104661E+11 | 0.245963E+10 | 720.00 | 0.103763E+11 | 89725753.48 | 0.00 | 0.64 | 30-JUN-24:00 | 0.41 | 01-JUN-06:20 | 5761.52 | 30-JUN-24:00 | 5761.52 | 30-JUN-24:00 | 211.30 | 27-JUN-08:20 | 1440.96 | 13-JUN-16:00 | 0.00 |
July | 0.160433E+11 | 0.374800E+10 | 744.00 | 0.159326E+11 | 0.110665E+09 | 0.00 | 0.84 | 31-JUL-24:00 | 0.61 | 01-JUL-06:30 | 7820.85 | 31-JUL-24:00 | 7820.85 | 31-JUL-24:00 | 225.57 | 18-JUL-16:00 | 2268.15 | 22-JUL-18:35 | 0.00 |
August | 0.210372E+11 | 0.491229E+10 | 744.00 | 0.209211E+11 | 0.116033E+09 | 0.00 | 0.96 | 14-AUG-18:00 | 0.30 | 31-AUG-23:55 | 8667.03 | 13-AUG-18:05 | 8655.15 | 13-AUG-18:10 | 250.68 | 08-AUG-13:30 | 2651.98 | 14-AUG-18:00 | 0.00 |
September | 0.537767E+10 | 0.132780E+10 | 720.00 | 0.530876E+10 | 68911034.48 | 0.00 | 0.46 | 30-SEP-24:00 | 0.19 | 20-SEP-06:45 | 3811.18 | 30-SEP-24:00 | 3811.18 | 30-SEP-24:00 | 158.29 | 19-SEP-16:00 | 905.97 | 30-SEP-24:00 | 0.00 |
October | 0.101987E+11 | 0.238706E+10 | 744.00 | 0.101719E+11 | 26795682.47 | 0.00 | 0.65 | 31-OCT-24:00 | 0.38 | 28-OCT-07:00 | 5645.54 | 31-OCT-24:00 | 5645.54 | 31-OCT-24:00 | 146.47 | 17-OCT-15:20 | 1286.55 | 31-OCT-24:00 | 0.00 |
November | 0.145499E+11 | 0.329296E+10 | 720.00 | 0.145339E+11 | 15949714.59 | 0.00 | 0.70 | 19-NOV-15:55 | 0.59 | 25-NOV-08:00 | 6095.85 | 19-NOV-16:00 | 6095.85 | 19-NOV-16:00 | 143.34 | 08-NOV-15:10 | 1383.74 | 19-NOV-15:55 | 0.00 |
December | 0.198217E+11 | 0.440749E+10 | 744.00 | 0.198216E+11 | 84153.60 | 0.00 | 0.91 | 31-DEC-15:15 | 0.78 | 02-DEC-18:00 | 7948.76 | 25-DEC-15:15 | 7948.76 | 25-DEC-15:15 | 36.24 | 20-DEC-17:10 | 1782.00 | 31-DEC-15:15 | 0.00 |
Annual Sum or Average | 0.150617E+12 | 0.348934E+11 | 8760.00 | 0.150164E+12 | 0.452398E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.414230E+10 | 0.106622E+10 | 672.00 | 0.414077E+10 | 84153.60 | 0.00 | 0.27 | 0.11 | 2236.33 | 2230.62 | 36.24 | 538.32 | 0.00 | ||||||
Maximum of Months | 0.210372E+11 | 0.491229E+10 | 744.00 | 0.209211E+11 | 0.116033E+09 | 0.00 | 1.00 | 0.78 | 8693.44 | 8693.44 | 250.68 | 2651.98 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.208188E+11 | 0.566584E+10 | 739.79 | 0.208040E+11 | 14770251.50 | 0.00 | 0.24 | 19-JAN-16:20 | 0.00 | 02-JAN-07:10 | 18461.08 | 19-JAN-16:20 | 18461.08 | 19-JAN-16:20 | 492.56 | 18-JAN-16:30 | 4538.89 | 19-JAN-16:20 | 0.00 |
February | 0.667636E+11 | 0.163563E+11 | 672.00 | 0.667503E+11 | 13302201.54 | 0.00 | 0.47 | 19-FEB-17:03 | 0.27 | 13-FEB-07:10 | 38143.00 | 27-FEB-17:00 | 38143.00 | 27-FEB-17:00 | 539.59 | 07-FEB-16:30 | 8933.56 | 19-FEB-17:03 | 0.00 |
March | 0.127179E+12 | 0.295102E+11 | 744.00 | 0.127175E+12 | 3326193.14 | 0.00 | 0.81 | 31-MAR-23:50 | 0.51 | 27-MAR-06:10 | 67889.95 | 31-MAR-23:50 | 67889.95 | 31-MAR-23:50 | 570.17 | 20-MAR-06:10 | 15315.43 | 31-MAR-23:50 | 0.00 |
April | 0.183160E+12 | 0.410491E+11 | 720.00 | 0.183156E+12 | 3547383.27 | 0.00 | 1.00 | 30-APR-17:52 | 0.28 | 30-APR-23:55 | 82549.11 | 30-APR-18:00 | 82549.11 | 30-APR-18:00 | 593.02 | 28-APR-11:00 | 24721.23 | 30-APR-18:11 | 0.00 |
May | 0.436084E+11 | 0.109607E+11 | 744.00 | 0.434045E+11 | 0.203940E+09 | 0.00 | 0.44 | 31-MAY-24:00 | 0.11 | 05-MAY-06:05 | 35930.93 | 31-MAY-24:00 | 35930.93 | 31-MAY-24:00 | 1380.46 | 23-MAY-15:00 | 8269.33 | 31-MAY-24:00 | 0.00 |
June | 0.953459E+11 | 0.225239E+11 | 720.00 | 0.944592E+11 | 0.886737E+09 | 0.00 | 0.61 | 30-JUN-24:00 | 0.37 | 08-JUN-06:10 | 52388.58 | 30-JUN-24:00 | 52388.58 | 30-JUN-24:00 | 2081.61 | 27-JUN-08:20 | 13702.78 | 13-JUN-16:00 | 0.00 |
July | 0.149186E+12 | 0.349906E+11 | 744.00 | 0.148089E+12 | 0.109693E+10 | 0.00 | 0.83 | 31-JUL-24:00 | 0.57 | 01-JUL-06:40 | 73454.41 | 31-JUL-24:00 | 73454.41 | 31-JUL-24:00 | 2236.54 | 18-JUL-16:00 | 21519.74 | 22-JUL-18:35 | 0.00 |
August | 0.197602E+12 | 0.462736E+11 | 744.00 | 0.196445E+12 | 0.115684E+10 | 0.00 | 0.96 | 14-AUG-18:00 | 0.25 | 31-AUG-23:55 | 80547.58 | 13-AUG-18:05 | 80427.53 | 13-AUG-18:10 | 2496.45 | 08-AUG-13:30 | 25252.88 | 14-AUG-18:00 | 0.00 |
September | 0.450086E+11 | 0.112408E+11 | 720.00 | 0.443428E+11 | 0.665838E+09 | 0.00 | 0.43 | 30-SEP-23:40 | 0.14 | 07-SEP-06:05 | 33841.29 | 30-SEP-23:40 | 33841.29 | 30-SEP-23:40 | 1573.72 | 19-SEP-16:00 | 8103.27 | 30-SEP-23:40 | 0.00 |
October | 0.841563E+11 | 0.199665E+11 | 744.00 | 0.838912E+11 | 0.265136E+09 | 0.00 | 0.59 | 31-OCT-24:00 | 0.31 | 28-OCT-07:00 | 48626.34 | 31-OCT-24:00 | 48626.34 | 31-OCT-24:00 | 1420.26 | 17-OCT-15:30 | 11221.00 | 31-OCT-24:00 | 0.00 |
November | 0.120480E+12 | 0.277026E+11 | 720.00 | 0.120320E+12 | 0.159453E+09 | 0.00 | 0.65 | 03-NOV-16:00 | 0.48 | 20-NOV-07:10 | 55278.90 | 10-NOV-16:00 | 55089.55 | 10-NOV-16:00 | 1425.82 | 08-NOV-15:10 | 12365.97 | 03-NOV-16:00 | 0.00 |
December | 0.164223E+12 | 0.372043E+11 | 744.00 | 0.164222E+12 | 1170824.40 | 0.00 | 0.81 | 29-DEC-15:50 | 0.65 | 26-DEC-07:10 | 69394.81 | 21-DEC-15:20 | 69394.81 | 21-DEC-15:20 | 380.62 | 20-DEC-17:10 | 15348.40 | 29-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.129753E+13 | 0.303444E+12 | 8755.79 | 0.129306E+13 | 0.447098E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.208188E+11 | 0.566584E+10 | 672.00 | 0.208040E+11 | 1170824.40 | 0.00 | 0.24 | 0.00 | 18461.08 | 18461.08 | 380.62 | 4538.89 | 0.00 | ||||||
Maximum of Months | 0.197602E+12 | 0.462736E+11 | 744.00 | 0.196445E+12 | 0.115684E+10 | 0.00 | 1.00 | 0.65 | 82549.11 | 82549.11 | 2496.45 | 25252.88 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.551204E+09 | 0.161697E+09 | 370.61 | 0.550314E+09 | 890023.19 | 0.00 | 0.21 | 19-JAN-16:20 | 0.00 | 01-JAN-00:05 | 1666.78 | 19-JAN-16:30 | 1666.78 | 19-JAN-16:30 | 43.16 | 18-JAN-16:40 | 413.60 | 19-JAN-16:20 | 0.00 |
February | 0.481915E+10 | 0.120998E+10 | 672.00 | 0.481791E+10 | 1238549.22 | 0.00 | 0.45 | 17-FEB-17:00 | 0.09 | 20-FEB-08:30 | 3581.77 | 09-FEB-16:50 | 3581.77 | 09-FEB-16:50 | 51.45 | 08-FEB-16:40 | 854.55 | 17-FEB-17:00 | 0.00 |
March | 0.110243E+11 | 0.259840E+10 | 744.00 | 0.110240E+11 | 317147.68 | 0.00 | 0.75 | 31-MAR-23:20 | 0.38 | 06-MAR-04:53 | 6252.96 | 31-MAR-23:20 | 6252.96 | 31-MAR-23:20 | 45.37 | 20-MAR-06:10 | 1428.17 | 31-MAR-23:20 | 0.00 |
April | 0.174259E+11 | 0.393900E+10 | 720.00 | 0.174255E+11 | 340187.67 | 0.00 | 1.00 | 30-APR-17:52 | 0.26 | 30-APR-23:55 | 8374.73 | 30-APR-18:10 | 8374.73 | 30-APR-18:10 | 58.20 | 28-APR-11:00 | 2507.68 | 30-APR-18:10 | 0.00 |
May | 0.356971E+10 | 0.911732E+09 | 743.33 | 0.354952E+10 | 20188587.50 | 0.00 | 0.41 | 31-MAY-23:20 | 0.00 | 05-MAY-01:45 | 3429.53 | 31-MAY-23:20 | 3429.53 | 31-MAY-23:20 | 139.59 | 23-MAY-15:00 | 793.79 | 31-MAY-23:20 | 0.00 |
June | 0.915979E+10 | 0.217662E+10 | 720.00 | 0.907140E+10 | 88389294.40 | 0.00 | 0.58 | 30-JUN-23:20 | 0.30 | 08-JUN-06:10 | 4980.33 | 30-JUN-23:20 | 4980.33 | 30-JUN-23:20 | 207.88 | 26-JUN-16:10 | 1400.85 | 13-JUN-16:00 | 0.00 |
July | 0.146040E+11 | 0.344334E+10 | 744.00 | 0.144945E+11 | 0.109459E+09 | 0.00 | 0.81 | 22-JUL-18:50 | 0.52 | 01-JUL-06:30 | 7198.88 | 31-JUL-23:30 | 7198.88 | 31-JUL-23:30 | 223.80 | 18-JUL-16:00 | 2208.82 | 22-JUL-18:35 | 0.00 |
August | 0.194572E+11 | 0.457833E+10 | 744.00 | 0.193418E+11 | 0.115469E+09 | 0.00 | 0.96 | 14-AUG-18:00 | 0.22 | 31-AUG-23:55 | 8100.41 | 13-AUG-18:05 | 8088.50 | 13-AUG-18:10 | 249.46 | 08-AUG-13:30 | 2551.47 | 14-AUG-18:00 | 0.00 |
September | 0.381872E+10 | 0.968435E+09 | 719.83 | 0.375352E+10 | 65202143.00 | 0.00 | 0.36 | 30-SEP-23:20 | 0.00 | 17-SEP-03:25 | 2821.90 | 30-SEP-23:20 | 2821.90 | 30-SEP-23:20 | 158.50 | 19-SEP-16:00 | 730.78 | 13-SEP-17:00 | 0.00 |
October | 0.682216E+10 | 0.164804E+10 | 744.00 | 0.679645E+10 | 25708782.40 | 0.00 | 0.52 | 31-OCT-23:20 | 0.18 | 23-OCT-06:10 | 4262.70 | 31-OCT-23:20 | 4262.70 | 31-OCT-23:20 | 139.08 | 17-OCT-15:30 | 999.00 | 31-OCT-23:20 | 0.00 |
November | 0.101676E+11 | 0.237929E+10 | 720.00 | 0.101520E+11 | 15642482.18 | 0.00 | 0.63 | 03-NOV-16:00 | 0.32 | 27-NOV-04:04 | 5415.11 | 10-NOV-16:10 | 5394.86 | 10-NOV-16:00 | 141.29 | 08-NOV-15:10 | 1203.84 | 03-NOV-16:00 | 0.00 |
December | 0.143606E+11 | 0.330872E+10 | 744.00 | 0.143605E+11 | 102535.55 | 0.00 | 0.76 | 29-DEC-15:50 | 0.48 | 26-DEC-04:03 | 6648.41 | 21-DEC-15:20 | 6648.41 | 21-DEC-15:20 | 36.02 | 20-DEC-17:10 | 1461.36 | 29-DEC-15:50 | 0.00 |
Annual Sum or Average | 0.115780E+12 | 0.273236E+11 | 8385.78 | 0.115337E+12 | 0.442948E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.551204E+09 | 0.161697E+09 | 370.61 | 0.550314E+09 | 102535.55 | 0.00 | 0.21 | 0.00 | 1666.78 | 1666.78 | 36.02 | 413.60 | 0.00 | ||||||
Maximum of Months | 0.194572E+11 | 0.457833E+10 | 744.00 | 0.193418E+11 | 0.115469E+09 | 0.00 | 1.00 | 0.52 | 8374.73 | 8374.73 | 249.46 | 2551.47 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.97 | 0.00 | 68.97 | 1.82 | 496.16 | 0.00 | 0.00 | 0.00 |
February | 107.69 | 0.00 | 107.69 | 7.18 | 465.15 | 0.00 | 0.00 | 0.00 |
March | 149.03 | 0.00 | 149.03 | 34.37 | 390.53 | 0.00 | 0.00 | 0.00 |
April | 242.64 | 1.09 | 241.56 | 139.07 | 306.64 | 0.00 | 0.00 | 0.00 |
May | 303.37 | 14.64 | 288.73 | 181.26 | 237.84 | 0.00 | 0.00 | 0.00 |
June | 335.35 | 21.03 | 314.32 | 268.85 | 186.38 | 0.00 | 0.00 | 0.00 |
July | 318.10 | 18.14 | 299.96 | 271.90 | 172.61 | 0.00 | 0.00 | 0.00 |
August | 250.04 | 3.92 | 246.13 | 207.95 | 194.52 | 0.00 | 0.00 | 0.00 |
September | 190.32 | 0.04 | 190.27 | 133.40 | 259.05 | 0.00 | 0.00 | 0.00 |
October | 121.95 | 0.00 | 121.95 | 39.11 | 360.77 | 0.00 | 0.00 | 0.00 |
November | 73.28 | 0.00 | 73.28 | 2.98 | 453.96 | 0.00 | 0.00 | 0.00 |
December | 49.90 | 0.00 | 49.90 | 0.00 | 547.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.56 | 4.94 | 179.63 | 107.83 | 338.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.90 | 0.00 | 49.90 | 0.00 | 172.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 335.35 | 21.03 | 314.32 | 271.90 | 547.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.97 | 0.00 | 68.97 | 1.82 | 496.16 | 0.00 | 0.00 | 0.00 |
February | 107.69 | 0.00 | 107.69 | 7.18 | 465.15 | 0.00 | 0.00 | 0.00 |
March | 149.03 | 0.00 | 149.03 | 34.37 | 390.53 | 0.00 | 0.00 | 0.00 |
April | 242.64 | 1.09 | 241.55 | 139.06 | 306.64 | 0.00 | 0.00 | 0.00 |
May | 303.36 | 14.64 | 288.73 | 181.25 | 237.84 | 0.00 | 0.00 | 0.00 |
June | 335.35 | 21.03 | 314.32 | 268.84 | 186.38 | 0.00 | 0.00 | 0.00 |
July | 318.10 | 18.14 | 299.96 | 271.90 | 172.61 | 0.00 | 0.00 | 0.00 |
August | 250.04 | 3.92 | 246.12 | 207.95 | 194.52 | 0.00 | 0.00 | 0.00 |
September | 190.31 | 0.04 | 190.27 | 133.40 | 259.05 | 0.00 | 0.00 | 0.00 |
October | 121.95 | 0.00 | 121.95 | 39.11 | 360.77 | 0.00 | 0.00 | 0.00 |
November | 73.27 | 0.00 | 73.27 | 2.98 | 453.96 | 0.00 | 0.00 | 0.00 |
December | 49.90 | 0.00 | 49.90 | 0.00 | 547.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.56 | 4.94 | 179.62 | 107.83 | 338.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.90 | 0.00 | 49.90 | 0.00 | 172.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 335.35 | 21.03 | 314.32 | 271.90 | 547.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.97 | 0.00 | 68.97 | 1.82 | 496.16 | 0.00 | 0.00 | 0.00 |
February | 107.69 | 0.00 | 107.69 | 7.18 | 465.15 | 0.00 | 0.00 | 0.00 |
March | 149.03 | 0.00 | 149.03 | 34.37 | 390.53 | 0.00 | 0.00 | 0.00 |
April | 242.64 | 1.09 | 241.56 | 139.06 | 306.64 | 0.00 | 0.00 | 0.00 |
May | 303.36 | 14.64 | 288.73 | 181.26 | 237.84 | 0.00 | 0.00 | 0.00 |
June | 335.35 | 21.03 | 314.32 | 268.84 | 186.38 | 0.00 | 0.00 | 0.00 |
July | 318.10 | 18.14 | 299.96 | 271.90 | 172.61 | 0.00 | 0.00 | 0.00 |
August | 250.04 | 3.92 | 246.12 | 207.95 | 194.52 | 0.00 | 0.00 | 0.00 |
September | 190.32 | 0.04 | 190.27 | 133.40 | 259.05 | 0.00 | 0.00 | 0.00 |
October | 121.95 | 0.00 | 121.95 | 39.11 | 360.77 | 0.00 | 0.00 | 0.00 |
November | 73.28 | 0.00 | 73.28 | 2.98 | 453.96 | 0.00 | 0.00 | 0.00 |
December | 49.90 | 0.00 | 49.90 | 0.00 | 547.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.56 | 4.94 | 179.62 | 107.83 | 338.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.90 | 0.00 | 49.90 | 0.00 | 172.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 335.35 | 21.03 | 314.32 | 271.90 | 547.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.97 | 0.00 | 68.97 | 1.82 | 496.16 | 0.00 | 0.00 | 0.00 |
February | 107.69 | 0.00 | 107.69 | 7.18 | 465.15 | 0.00 | 0.00 | 0.00 |
March | 149.03 | 0.00 | 149.03 | 34.37 | 390.53 | 0.00 | 0.00 | 0.00 |
April | 242.64 | 1.09 | 241.55 | 139.06 | 306.64 | 0.00 | 0.00 | 0.00 |
May | 303.36 | 14.64 | 288.73 | 181.25 | 237.84 | 0.00 | 0.00 | 0.00 |
June | 335.35 | 21.03 | 314.32 | 268.84 | 186.38 | 0.00 | 0.00 | 0.00 |
July | 318.10 | 18.14 | 299.96 | 271.90 | 172.61 | 0.00 | 0.00 | 0.00 |
August | 250.04 | 3.92 | 246.12 | 207.95 | 194.52 | 0.00 | 0.00 | 0.00 |
September | 190.31 | 0.04 | 190.27 | 133.40 | 259.05 | 0.00 | 0.00 | 0.00 |
October | 121.95 | 0.00 | 121.95 | 39.11 | 360.77 | 0.00 | 0.00 | 0.00 |
November | 73.27 | 0.00 | 73.27 | 2.98 | 453.96 | 0.00 | 0.00 | 0.00 |
December | 49.90 | 0.00 | 49.90 | 0.00 | 547.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.56 | 4.94 | 179.62 | 107.83 | 338.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.90 | 0.00 | 49.90 | 0.00 | 172.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 335.35 | 21.03 | 314.32 | 271.90 | 547.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 68.96 | 0.00 | 68.96 | 1.82 | 496.14 | 0.00 | 0.00 | 0.00 |
February | 107.69 | 0.00 | 107.69 | 7.18 | 465.13 | 0.00 | 0.00 | 0.00 |
March | 149.02 | 0.00 | 149.02 | 34.36 | 390.51 | 0.00 | 0.00 | 0.00 |
April | 242.63 | 1.09 | 241.54 | 139.06 | 306.62 | 0.00 | 0.00 | 0.00 |
May | 303.35 | 14.64 | 288.72 | 181.25 | 237.83 | 0.00 | 0.00 | 0.00 |
June | 335.33 | 21.03 | 314.31 | 268.83 | 186.37 | 0.00 | 0.00 | 0.00 |
July | 318.08 | 18.14 | 299.95 | 271.89 | 172.60 | 0.00 | 0.00 | 0.00 |
August | 250.03 | 3.92 | 246.11 | 207.94 | 194.51 | 0.00 | 0.00 | 0.00 |
September | 190.31 | 0.04 | 190.27 | 133.39 | 259.04 | 0.00 | 0.00 | 0.00 |
October | 121.95 | 0.00 | 121.95 | 39.11 | 360.76 | 0.00 | 0.00 | 0.00 |
November | 73.27 | 0.00 | 73.27 | 2.98 | 453.94 | 0.00 | 0.00 | 0.00 |
December | 49.90 | 0.00 | 49.90 | 0.00 | 547.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 184.55 | 4.94 | 179.62 | 107.83 | 338.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 49.90 | 0.00 | 49.90 | 0.00 | 172.60 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 335.33 | 21.03 | 314.31 | 271.89 | 547.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.63 | 62.92 | 93.71 | 82.31 | 507.64 | 0.00 | 0.00 | 0.00 |
February | 233.56 | 86.28 | 147.28 | 139.10 | 476.43 | 0.00 | 0.00 | 0.00 |
March | 244.08 | 48.10 | 195.98 | 131.32 | 396.97 | 0.00 | 0.00 | 0.00 |
April | 655.36 | 307.96 | 347.40 | 671.69 | 313.71 | 0.00 | 0.00 | 0.00 |
May | 689.09 | 300.50 | 388.59 | 688.70 | 268.06 | 0.00 | 0.00 | 0.00 |
June | 682.08 | 272.42 | 409.66 | 731.24 | 208.30 | 0.00 | 0.00 | 0.00 |
July | 696.27 | 295.91 | 400.35 | 780.99 | 191.80 | 0.00 | 0.00 | 0.00 |
August | 659.56 | 315.13 | 344.43 | 762.62 | 207.25 | 0.00 | 0.00 | 0.00 |
September | 593.96 | 315.84 | 278.12 | 660.82 | 270.04 | 0.00 | 0.00 | 0.00 |
October | 286.71 | 118.82 | 167.89 | 241.57 | 375.36 | 0.00 | 0.00 | 0.00 |
November | 149.47 | 50.94 | 98.53 | 77.46 | 461.79 | 0.00 | 0.00 | 0.00 |
December | 110.78 | 41.18 | 69.59 | 49.44 | 554.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 430.42 | 184.90 | 245.51 | 419.12 | 352.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.78 | 41.18 | 69.59 | 49.44 | 191.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 696.27 | 315.84 | 409.66 | 780.99 | 554.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.63 | 62.92 | 93.71 | 82.31 | 507.64 | 0.00 | 0.00 | 0.00 |
February | 233.56 | 86.28 | 147.28 | 139.10 | 476.43 | 0.00 | 0.00 | 0.00 |
March | 244.08 | 48.10 | 195.98 | 131.32 | 396.97 | 0.00 | 0.00 | 0.00 |
April | 655.36 | 307.96 | 347.40 | 671.69 | 313.71 | 0.00 | 0.00 | 0.00 |
May | 689.09 | 300.50 | 388.59 | 688.70 | 268.06 | 0.00 | 0.00 | 0.00 |
June | 682.08 | 272.42 | 409.66 | 731.24 | 208.30 | 0.00 | 0.00 | 0.00 |
July | 696.27 | 295.91 | 400.35 | 780.99 | 191.80 | 0.00 | 0.00 | 0.00 |
August | 659.56 | 315.13 | 344.43 | 762.62 | 207.25 | 0.00 | 0.00 | 0.00 |
September | 593.96 | 315.84 | 278.12 | 660.82 | 270.04 | 0.00 | 0.00 | 0.00 |
October | 286.71 | 118.82 | 167.89 | 241.57 | 375.36 | 0.00 | 0.00 | 0.00 |
November | 149.47 | 50.94 | 98.53 | 77.46 | 461.79 | 0.00 | 0.00 | 0.00 |
December | 110.78 | 41.18 | 69.59 | 49.44 | 554.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 430.42 | 184.90 | 245.51 | 419.12 | 352.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.78 | 41.18 | 69.59 | 49.44 | 191.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 696.27 | 315.84 | 409.66 | 780.99 | 554.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 156.63 | 62.92 | 93.71 | 82.31 | 507.63 | 0.00 | 0.00 | 0.00 |
February | 233.56 | 86.28 | 147.28 | 139.10 | 476.42 | 0.00 | 0.00 | 0.00 |
March | 244.07 | 48.10 | 195.97 | 131.32 | 396.96 | 0.00 | 0.00 | 0.00 |
April | 655.35 | 307.95 | 347.40 | 671.68 | 313.70 | 0.00 | 0.00 | 0.00 |
May | 689.08 | 300.50 | 388.59 | 688.69 | 268.06 | 0.00 | 0.00 | 0.00 |
June | 682.07 | 272.41 | 409.66 | 731.23 | 208.29 | 0.00 | 0.00 | 0.00 |
July | 696.25 | 295.91 | 400.35 | 780.97 | 191.80 | 0.00 | 0.00 | 0.00 |
August | 659.55 | 315.13 | 344.42 | 762.61 | 207.24 | 0.00 | 0.00 | 0.00 |
September | 593.95 | 315.83 | 278.11 | 660.81 | 270.04 | 0.00 | 0.00 | 0.00 |
October | 286.71 | 118.82 | 167.89 | 241.57 | 375.35 | 0.00 | 0.00 | 0.00 |
November | 149.47 | 50.94 | 98.53 | 77.46 | 461.78 | 0.00 | 0.00 | 0.00 |
December | 110.77 | 41.18 | 69.59 | 49.44 | 554.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 430.41 | 184.90 | 245.51 | 419.11 | 352.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 110.77 | 41.18 | 69.59 | 49.44 | 191.80 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 696.25 | 315.83 | 409.66 | 780.97 | 554.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 391.54 | 253.46 | 138.08 | 377.96 | 423.08 | 0.00 | 0.00 | 0.00 |
February | 478.19 | 291.80 | 186.39 | 475.39 | 415.63 | 0.00 | 0.00 | 0.00 |
March | 295.65 | 86.08 | 209.57 | 226.54 | 356.58 | 0.00 | 0.00 | 0.00 |
April | 613.94 | 277.49 | 336.45 | 688.94 | 308.56 | 0.00 | 0.00 | 0.00 |
May | 507.79 | 165.32 | 342.47 | 526.31 | 262.12 | 0.00 | 0.00 | 0.00 |
June | 467.78 | 113.23 | 354.55 | 505.26 | 203.52 | 0.00 | 0.00 | 0.00 |
July | 506.83 | 158.72 | 348.11 | 591.21 | 189.83 | 0.00 | 0.00 | 0.00 |
August | 593.90 | 267.15 | 326.74 | 735.99 | 207.05 | 0.00 | 0.00 | 0.00 |
September | 701.83 | 411.14 | 290.69 | 863.22 | 260.51 | 0.00 | 0.00 | 0.00 |
October | 482.18 | 281.81 | 200.37 | 524.10 | 337.88 | 0.00 | 0.00 | 0.00 |
November | 341.87 | 207.97 | 133.90 | 331.64 | 402.89 | 0.00 | 0.00 | 0.00 |
December | 270.96 | 173.61 | 97.36 | 252.18 | 481.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.32 | 223.11 | 247.21 | 507.52 | 320.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 270.96 | 86.08 | 97.36 | 226.54 | 189.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 701.83 | 411.14 | 354.55 | 863.22 | 481.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 391.54 | 253.46 | 138.08 | 377.96 | 423.08 | 0.00 | 0.00 | 0.00 |
February | 478.19 | 291.80 | 186.39 | 475.39 | 415.63 | 0.00 | 0.00 | 0.00 |
March | 295.65 | 86.08 | 209.57 | 226.54 | 356.58 | 0.00 | 0.00 | 0.00 |
April | 613.94 | 277.49 | 336.45 | 688.94 | 308.56 | 0.00 | 0.00 | 0.00 |
May | 507.79 | 165.32 | 342.47 | 526.31 | 262.12 | 0.00 | 0.00 | 0.00 |
June | 467.78 | 113.23 | 354.55 | 505.26 | 203.52 | 0.00 | 0.00 | 0.00 |
July | 506.83 | 158.72 | 348.11 | 591.21 | 189.83 | 0.00 | 0.00 | 0.00 |
August | 593.89 | 267.15 | 326.74 | 735.98 | 207.05 | 0.00 | 0.00 | 0.00 |
September | 701.82 | 411.14 | 290.69 | 863.21 | 260.51 | 0.00 | 0.00 | 0.00 |
October | 482.18 | 281.81 | 200.37 | 524.10 | 337.88 | 0.00 | 0.00 | 0.00 |
November | 341.87 | 207.97 | 133.90 | 331.64 | 402.89 | 0.00 | 0.00 | 0.00 |
December | 270.96 | 173.61 | 97.36 | 252.17 | 481.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.32 | 223.11 | 247.21 | 507.52 | 320.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 270.96 | 86.08 | 97.36 | 226.54 | 189.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 701.82 | 411.14 | 354.55 | 863.21 | 481.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 391.54 | 253.46 | 138.08 | 377.96 | 423.08 | 0.00 | 0.00 | 0.00 |
February | 478.19 | 291.80 | 186.39 | 475.39 | 415.63 | 0.00 | 0.00 | 0.00 |
March | 295.65 | 86.08 | 209.57 | 226.54 | 356.58 | 0.00 | 0.00 | 0.00 |
April | 613.94 | 277.49 | 336.45 | 688.94 | 308.56 | 0.00 | 0.00 | 0.00 |
May | 507.79 | 165.32 | 342.47 | 526.31 | 262.12 | 0.00 | 0.00 | 0.00 |
June | 467.78 | 113.23 | 354.55 | 505.26 | 203.52 | 0.00 | 0.00 | 0.00 |
July | 506.83 | 158.72 | 348.11 | 591.21 | 189.83 | 0.00 | 0.00 | 0.00 |
August | 593.90 | 267.15 | 326.74 | 735.99 | 207.05 | 0.00 | 0.00 | 0.00 |
September | 701.83 | 411.14 | 290.69 | 863.22 | 260.51 | 0.00 | 0.00 | 0.00 |
October | 482.18 | 281.81 | 200.37 | 524.10 | 337.88 | 0.00 | 0.00 | 0.00 |
November | 341.87 | 207.97 | 133.90 | 331.64 | 402.89 | 0.00 | 0.00 | 0.00 |
December | 270.96 | 173.61 | 97.36 | 252.18 | 481.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.32 | 223.11 | 247.21 | 507.52 | 320.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 270.96 | 86.08 | 97.36 | 226.54 | 189.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 701.83 | 411.14 | 354.55 | 863.22 | 481.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 391.54 | 253.46 | 138.08 | 377.96 | 423.08 | 0.00 | 0.00 | 0.00 |
February | 478.19 | 291.80 | 186.39 | 475.39 | 415.63 | 0.00 | 0.00 | 0.00 |
March | 295.65 | 86.08 | 209.57 | 226.54 | 356.58 | 0.00 | 0.00 | 0.00 |
April | 613.94 | 277.49 | 336.45 | 688.94 | 308.56 | 0.00 | 0.00 | 0.00 |
May | 507.79 | 165.32 | 342.47 | 526.31 | 262.12 | 0.00 | 0.00 | 0.00 |
June | 467.78 | 113.23 | 354.55 | 505.26 | 203.52 | 0.00 | 0.00 | 0.00 |
July | 506.83 | 158.72 | 348.11 | 591.21 | 189.83 | 0.00 | 0.00 | 0.00 |
August | 593.89 | 267.15 | 326.74 | 735.98 | 207.05 | 0.00 | 0.00 | 0.00 |
September | 701.82 | 411.14 | 290.69 | 863.21 | 260.51 | 0.00 | 0.00 | 0.00 |
October | 482.18 | 281.81 | 200.37 | 524.10 | 337.88 | 0.00 | 0.00 | 0.00 |
November | 341.87 | 207.97 | 133.90 | 331.64 | 402.89 | 0.00 | 0.00 | 0.00 |
December | 270.96 | 173.61 | 97.36 | 252.17 | 481.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.32 | 223.11 | 247.21 | 507.52 | 320.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 270.96 | 86.08 | 97.36 | 226.54 | 189.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 701.82 | 411.14 | 354.55 | 863.21 | 481.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 391.52 | 253.45 | 138.07 | 377.95 | 423.06 | 0.00 | 0.00 | 0.00 |
February | 478.17 | 291.79 | 186.39 | 475.37 | 415.61 | 0.00 | 0.00 | 0.00 |
March | 295.64 | 86.08 | 209.56 | 226.53 | 356.56 | 0.00 | 0.00 | 0.00 |
April | 613.92 | 277.48 | 336.43 | 688.91 | 308.55 | 0.00 | 0.00 | 0.00 |
May | 507.77 | 165.31 | 342.46 | 526.29 | 262.11 | 0.00 | 0.00 | 0.00 |
June | 467.76 | 113.22 | 354.54 | 505.24 | 203.51 | 0.00 | 0.00 | 0.00 |
July | 506.81 | 158.71 | 348.10 | 591.19 | 189.82 | 0.00 | 0.00 | 0.00 |
August | 593.87 | 267.14 | 326.73 | 735.95 | 207.05 | 0.00 | 0.00 | 0.00 |
September | 701.80 | 411.12 | 290.67 | 863.18 | 260.50 | 0.00 | 0.00 | 0.00 |
October | 482.16 | 281.80 | 200.36 | 524.08 | 337.87 | 0.00 | 0.00 | 0.00 |
November | 341.85 | 207.96 | 133.90 | 331.63 | 402.87 | 0.00 | 0.00 | 0.00 |
December | 270.95 | 173.60 | 97.35 | 252.16 | 481.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 470.30 | 223.10 | 247.20 | 507.50 | 320.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 270.95 | 86.08 | 97.35 | 226.53 | 189.82 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 701.80 | 411.12 | 354.54 | 863.18 | 481.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.31 | 50.33 | 101.99 | 79.72 | 546.29 | 0.00 | 0.00 | 0.00 |
February | 269.68 | 113.87 | 155.81 | 193.69 | 536.69 | 0.00 | 0.00 | 0.00 |
March | 243.85 | 46.65 | 197.20 | 119.93 | 458.47 | 0.00 | 0.00 | 0.00 |
April | 575.37 | 228.54 | 346.83 | 558.07 | 377.90 | 0.00 | 0.00 | 0.00 |
May | 675.04 | 274.49 | 400.54 | 666.67 | 301.50 | 0.00 | 0.00 | 0.00 |
June | 728.97 | 300.09 | 428.88 | 782.62 | 244.19 | 0.00 | 0.00 | 0.00 |
July | 742.42 | 327.34 | 415.09 | 830.33 | 232.93 | 0.00 | 0.00 | 0.00 |
August | 623.59 | 270.00 | 353.59 | 701.56 | 257.66 | 0.00 | 0.00 | 0.00 |
September | 500.28 | 224.34 | 275.94 | 542.67 | 308.00 | 0.00 | 0.00 | 0.00 |
October | 266.88 | 95.97 | 170.91 | 213.76 | 427.64 | 0.00 | 0.00 | 0.00 |
November | 144.43 | 42.16 | 102.27 | 74.02 | 539.71 | 0.00 | 0.00 | 0.00 |
December | 81.75 | 17.25 | 64.50 | 22.26 | 663.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 417.49 | 165.99 | 251.50 | 399.47 | 407.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 81.75 | 17.25 | 64.50 | 22.26 | 232.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.42 | 327.34 | 428.88 | 830.33 | 663.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.31 | 50.33 | 101.99 | 79.72 | 546.29 | 0.00 | 0.00 | 0.00 |
February | 269.68 | 113.87 | 155.81 | 193.69 | 536.69 | 0.00 | 0.00 | 0.00 |
March | 243.85 | 46.65 | 197.20 | 119.93 | 458.47 | 0.00 | 0.00 | 0.00 |
April | 575.37 | 228.54 | 346.83 | 558.07 | 377.90 | 0.00 | 0.00 | 0.00 |
May | 675.04 | 274.49 | 400.54 | 666.67 | 301.50 | 0.00 | 0.00 | 0.00 |
June | 728.97 | 300.09 | 428.88 | 782.62 | 244.19 | 0.00 | 0.00 | 0.00 |
July | 742.42 | 327.34 | 415.09 | 830.33 | 232.93 | 0.00 | 0.00 | 0.00 |
August | 623.59 | 270.00 | 353.59 | 701.56 | 257.66 | 0.00 | 0.00 | 0.00 |
September | 500.28 | 224.34 | 275.94 | 542.67 | 308.00 | 0.00 | 0.00 | 0.00 |
October | 266.88 | 95.97 | 170.91 | 213.76 | 427.64 | 0.00 | 0.00 | 0.00 |
November | 144.43 | 42.16 | 102.27 | 74.02 | 539.71 | 0.00 | 0.00 | 0.00 |
December | 81.75 | 17.25 | 64.50 | 22.26 | 663.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 417.49 | 165.99 | 251.50 | 399.47 | 407.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 81.75 | 17.25 | 64.50 | 22.26 | 232.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.42 | 327.34 | 428.88 | 830.33 | 663.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 152.31 | 50.32 | 101.99 | 79.72 | 546.28 | 0.00 | 0.00 | 0.00 |
February | 269.67 | 113.87 | 155.81 | 193.69 | 536.68 | 0.00 | 0.00 | 0.00 |
March | 243.84 | 46.65 | 197.20 | 119.93 | 458.46 | 0.00 | 0.00 | 0.00 |
April | 575.36 | 228.54 | 346.82 | 558.06 | 377.89 | 0.00 | 0.00 | 0.00 |
May | 675.03 | 274.49 | 400.54 | 666.66 | 301.49 | 0.00 | 0.00 | 0.00 |
June | 728.96 | 300.08 | 428.87 | 782.61 | 244.19 | 0.00 | 0.00 | 0.00 |
July | 742.41 | 327.33 | 415.08 | 830.32 | 232.92 | 0.00 | 0.00 | 0.00 |
August | 623.57 | 269.99 | 353.58 | 701.55 | 257.65 | 0.00 | 0.00 | 0.00 |
September | 500.27 | 224.33 | 275.94 | 542.66 | 307.99 | 0.00 | 0.00 | 0.00 |
October | 266.88 | 95.97 | 170.91 | 213.75 | 427.63 | 0.00 | 0.00 | 0.00 |
November | 144.42 | 42.16 | 102.26 | 74.01 | 539.70 | 0.00 | 0.00 | 0.00 |
December | 81.75 | 17.25 | 64.50 | 22.26 | 663.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 417.48 | 165.98 | 251.50 | 399.46 | 407.28 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 81.75 | 17.25 | 64.50 | 22.26 | 232.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 742.41 | 327.33 | 428.87 | 830.32 | 663.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.83 | 0.00 | 344.83 | 19.77 | 2197.13 | 0.00 | 0.00 | 0.00 |
February | 538.47 | 0.00 | 538.47 | 68.33 | 2053.69 | 0.00 | 0.00 | 0.00 |
March | 745.15 | 0.00 | 745.15 | 226.19 | 1718.03 | 0.00 | 0.00 | 0.00 |
April | 1213.22 | 5.43 | 1207.79 | 743.92 | 1400.96 | 0.00 | 0.00 | 0.00 |
May | 1516.83 | 73.18 | 1443.65 | 950.06 | 1112.20 | 0.00 | 0.00 | 0.00 |
June | 1676.76 | 105.14 | 1571.62 | 1366.96 | 883.24 | 0.00 | 0.00 | 0.00 |
July | 1590.50 | 90.68 | 1499.82 | 1394.10 | 812.59 | 0.00 | 0.00 | 0.00 |
August | 1250.21 | 19.59 | 1230.63 | 1071.58 | 910.01 | 0.00 | 0.00 | 0.00 |
September | 951.58 | 0.21 | 951.37 | 698.10 | 1211.16 | 0.00 | 0.00 | 0.00 |
October | 609.77 | 0.00 | 609.77 | 239.79 | 1599.45 | 0.00 | 0.00 | 0.00 |
November | 366.38 | 0.00 | 366.38 | 33.08 | 1942.28 | 0.00 | 0.00 | 0.00 |
December | 249.50 | 0.00 | 249.50 | 1.03 | 2330.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 922.81 | 24.69 | 898.13 | 570.28 | 1511.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.50 | 0.00 | 249.50 | 1.03 | 812.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1676.76 | 105.14 | 1571.62 | 1394.10 | 2330.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.88 | 188.75 | 281.13 | 266.67 | 1377.84 | 0.00 | 0.00 | 0.00 |
February | 700.67 | 258.83 | 441.84 | 443.15 | 1303.31 | 0.00 | 0.00 | 0.00 |
March | 732.22 | 144.29 | 587.93 | 429.43 | 1084.86 | 0.00 | 0.00 | 0.00 |
April | 1966.07 | 923.87 | 1042.20 | 2017.72 | 902.83 | 0.00 | 0.00 | 0.00 |
May | 2067.26 | 901.50 | 1165.77 | 2067.04 | 768.74 | 0.00 | 0.00 | 0.00 |
June | 2046.21 | 817.24 | 1228.98 | 2187.54 | 606.02 | 0.00 | 0.00 | 0.00 |
July | 2088.78 | 887.73 | 1201.05 | 2334.62 | 561.63 | 0.00 | 0.00 | 0.00 |
August | 1978.66 | 945.39 | 1033.28 | 2280.13 | 611.83 | 0.00 | 0.00 | 0.00 |
September | 1781.85 | 947.51 | 834.34 | 1981.03 | 780.25 | 0.00 | 0.00 | 0.00 |
October | 860.12 | 356.46 | 503.67 | 745.11 | 1030.65 | 0.00 | 0.00 | 0.00 |
November | 448.41 | 152.82 | 295.58 | 251.94 | 1231.28 | 0.00 | 0.00 | 0.00 |
December | 332.32 | 123.55 | 208.77 | 165.09 | 1478.87 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1291.24 | 554.71 | 736.53 | 1267.08 | 976.58 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.32 | 123.55 | 208.77 | 165.09 | 561.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2088.78 | 947.51 | 1228.98 | 2334.62 | 1478.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1957.73 | 1267.32 | 690.41 | 1902.38 | 2031.57 | 0.00 | 0.00 | 0.00 |
February | 2391.01 | 1459.02 | 931.98 | 2386.12 | 2001.16 | 0.00 | 0.00 | 0.00 |
March | 1478.28 | 430.41 | 1047.87 | 1157.85 | 1681.76 | 0.00 | 0.00 | 0.00 |
April | 3069.76 | 1387.50 | 1682.27 | 3442.86 | 1492.67 | 0.00 | 0.00 | 0.00 |
May | 2538.98 | 826.61 | 1712.37 | 2628.71 | 1274.11 | 0.00 | 0.00 | 0.00 |
June | 2338.94 | 566.16 | 1772.78 | 2526.44 | 986.19 | 0.00 | 0.00 | 0.00 |
July | 2534.20 | 793.61 | 1740.59 | 2957.70 | 919.18 | 0.00 | 0.00 | 0.00 |
August | 2969.53 | 1335.80 | 1633.72 | 3675.14 | 1009.23 | 0.00 | 0.00 | 0.00 |
September | 3509.20 | 2055.75 | 1453.45 | 4297.84 | 1283.42 | 0.00 | 0.00 | 0.00 |
October | 2410.97 | 1409.10 | 1001.87 | 2623.08 | 1621.38 | 0.00 | 0.00 | 0.00 |
November | 1709.38 | 1039.86 | 669.52 | 1672.89 | 1888.25 | 0.00 | 0.00 | 0.00 |
December | 1354.84 | 868.05 | 486.79 | 1285.45 | 2232.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2351.63 | 1115.59 | 1236.05 | 2542.88 | 1532.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1354.84 | 430.41 | 486.79 | 1157.85 | 919.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3509.20 | 2055.75 | 1772.78 | 4297.84 | 2232.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.94 | 150.97 | 305.96 | 263.51 | 1435.11 | 0.00 | 0.00 | 0.00 |
February | 809.03 | 341.60 | 467.43 | 621.97 | 1378.83 | 0.00 | 0.00 | 0.00 |
March | 731.54 | 139.94 | 591.59 | 419.93 | 1133.63 | 0.00 | 0.00 | 0.00 |
April | 1726.08 | 685.62 | 1040.47 | 1733.13 | 984.26 | 0.00 | 0.00 | 0.00 |
May | 2025.10 | 823.47 | 1201.62 | 2028.33 | 836.87 | 0.00 | 0.00 | 0.00 |
June | 2186.89 | 900.26 | 1286.63 | 2371.75 | 667.75 | 0.00 | 0.00 | 0.00 |
July | 2227.25 | 982.00 | 1245.25 | 2528.49 | 625.02 | 0.00 | 0.00 | 0.00 |
August | 1870.74 | 809.98 | 1060.76 | 2144.26 | 682.39 | 0.00 | 0.00 | 0.00 |
September | 1500.83 | 673.01 | 827.82 | 1652.88 | 850.82 | 0.00 | 0.00 | 0.00 |
October | 800.63 | 287.90 | 512.73 | 684.78 | 1090.87 | 0.00 | 0.00 | 0.00 |
November | 433.28 | 126.48 | 306.80 | 253.88 | 1305.46 | 0.00 | 0.00 | 0.00 |
December | 245.25 | 51.75 | 193.49 | 85.08 | 1577.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1252.45 | 497.95 | 754.50 | 1234.38 | 1045.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.25 | 51.75 | 193.49 | 85.08 | 625.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2227.25 | 982.00 | 1286.63 | 2528.49 | 1577.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 344.83 | 0.00 | 344.83 | 33.89 | 1986.50 | 0.00 | 0.00 | 0.00 |
February | 538.47 | 0.00 | 538.47 | 101.33 | 1852.39 | 0.00 | 0.00 | 0.00 |
March | 745.15 | 0.00 | 745.15 | 271.87 | 1554.40 | 0.00 | 0.00 | 0.00 |
April | 1213.22 | 5.43 | 1207.79 | 788.58 | 1297.07 | 0.00 | 0.00 | 0.00 |
May | 1516.83 | 73.18 | 1443.65 | 1003.00 | 1035.80 | 0.00 | 0.00 | 0.00 |
June | 1676.76 | 105.14 | 1571.62 | 1389.00 | 844.20 | 0.00 | 0.00 | 0.00 |
July | 1590.50 | 90.68 | 1499.82 | 1411.23 | 780.95 | 0.00 | 0.00 | 0.00 |
August | 1250.21 | 19.59 | 1230.63 | 1085.77 | 872.94 | 0.00 | 0.00 | 0.00 |
September | 951.58 | 0.21 | 951.37 | 732.28 | 1129.56 | 0.00 | 0.00 | 0.00 |
October | 609.77 | 0.00 | 609.77 | 286.46 | 1420.35 | 0.00 | 0.00 | 0.00 |
November | 366.38 | 0.00 | 366.38 | 52.70 | 1728.98 | 0.00 | 0.00 | 0.00 |
December | 249.50 | 0.00 | 249.50 | 6.67 | 2125.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 922.81 | 24.69 | 898.13 | 599.40 | 1383.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 249.50 | 0.00 | 249.50 | 6.67 | 780.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1676.76 | 105.14 | 1571.62 | 1411.23 | 2125.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 469.88 | 188.75 | 281.13 | 286.56 | 1250.70 | 0.00 | 0.00 | 0.00 |
February | 700.67 | 258.83 | 441.84 | 475.07 | 1182.27 | 0.00 | 0.00 | 0.00 |
March | 732.22 | 144.29 | 587.93 | 463.43 | 990.15 | 0.00 | 0.00 | 0.00 |
April | 1966.07 | 923.87 | 1042.20 | 2039.80 | 850.83 | 0.00 | 0.00 | 0.00 |
May | 2067.26 | 901.50 | 1165.77 | 2089.64 | 726.97 | 0.00 | 0.00 | 0.00 |
June | 2046.21 | 817.24 | 1228.98 | 2194.32 | 585.22 | 0.00 | 0.00 | 0.00 |
July | 2088.78 | 887.73 | 1201.05 | 2338.06 | 545.59 | 0.00 | 0.00 | 0.00 |
August | 1978.66 | 945.39 | 1033.28 | 2281.90 | 595.31 | 0.00 | 0.00 | 0.00 |
September | 1781.85 | 947.51 | 834.34 | 1996.13 | 741.96 | 0.00 | 0.00 | 0.00 |
October | 860.12 | 356.46 | 503.67 | 776.54 | 928.45 | 0.00 | 0.00 | 0.00 |
November | 448.41 | 152.82 | 295.58 | 272.66 | 1105.56 | 0.00 | 0.00 | 0.00 |
December | 332.32 | 123.55 | 208.77 | 178.48 | 1353.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1291.24 | 554.71 | 736.53 | 1285.59 | 903.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 332.32 | 123.55 | 208.77 | 178.48 | 545.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2088.78 | 947.51 | 1228.98 | 2338.06 | 1353.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1957.73 | 1267.32 | 690.41 | 1953.74 | 1838.92 | 0.00 | 0.00 | 0.00 |
February | 2391.01 | 1459.02 | 931.98 | 2443.24 | 1816.82 | 0.00 | 0.00 | 0.00 |
March | 1478.28 | 430.41 | 1047.87 | 1213.25 | 1527.95 | 0.00 | 0.00 | 0.00 |
April | 3069.76 | 1387.50 | 1682.27 | 3472.27 | 1403.64 | 0.00 | 0.00 | 0.00 |
May | 2538.98 | 826.61 | 1712.37 | 2660.75 | 1196.53 | 0.00 | 0.00 | 0.00 |
June | 2338.94 | 566.16 | 1772.78 | 2540.12 | 945.86 | 0.00 | 0.00 | 0.00 |
July | 2534.20 | 793.61 | 1740.59 | 2966.21 | 886.21 | 0.00 | 0.00 | 0.00 |
August | 2969.53 | 1335.80 | 1633.72 | 3678.35 | 976.64 | 0.00 | 0.00 | 0.00 |
September | 3509.20 | 2055.75 | 1453.45 | 4315.48 | 1218.99 | 0.00 | 0.00 | 0.00 |
October | 2410.97 | 1409.10 | 1001.87 | 2666.44 | 1463.18 | 0.00 | 0.00 | 0.00 |
November | 1709.38 | 1039.86 | 669.52 | 1715.84 | 1691.62 | 0.00 | 0.00 | 0.00 |
December | 1354.84 | 868.05 | 486.79 | 1319.10 | 2036.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2351.63 | 1115.59 | 1236.05 | 2575.11 | 1414.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1354.84 | 430.41 | 486.79 | 1213.25 | 886.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3509.20 | 2055.75 | 1772.78 | 4315.48 | 2036.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 456.94 | 150.97 | 305.96 | 279.37 | 1316.40 | 0.00 | 0.00 | 0.00 |
February | 809.03 | 341.60 | 467.43 | 644.42 | 1270.21 | 0.00 | 0.00 | 0.00 |
March | 731.54 | 139.94 | 591.59 | 446.95 | 1045.23 | 0.00 | 0.00 | 0.00 |
April | 1726.08 | 685.62 | 1040.47 | 1754.89 | 928.22 | 0.00 | 0.00 | 0.00 |
May | 2025.10 | 823.47 | 1201.62 | 2048.10 | 791.87 | 0.00 | 0.00 | 0.00 |
June | 2186.89 | 900.26 | 1286.63 | 2377.15 | 643.43 | 0.00 | 0.00 | 0.00 |
July | 2227.25 | 982.00 | 1245.25 | 2531.21 | 604.66 | 0.00 | 0.00 | 0.00 |
August | 1870.74 | 809.98 | 1060.76 | 2146.44 | 660.67 | 0.00 | 0.00 | 0.00 |
September | 1500.83 | 673.01 | 827.82 | 1668.10 | 806.60 | 0.00 | 0.00 | 0.00 |
October | 800.63 | 287.90 | 512.73 | 709.70 | 995.59 | 0.00 | 0.00 | 0.00 |
November | 433.28 | 126.48 | 306.80 | 268.09 | 1190.31 | 0.00 | 0.00 | 0.00 |
December | 245.25 | 51.75 | 193.49 | 91.97 | 1460.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1252.45 | 497.95 | 754.50 | 1249.20 | 974.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 245.25 | 51.75 | 193.49 | 91.97 | 604.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2227.25 | 982.00 | 1286.63 | 2531.21 | 1460.15 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184720E+09 | 0.00 | 0.184720E+09 | 4887222.06 | 0.132890E+10 |
February | 0.260534E+09 | 0.00 | 0.260534E+09 | 17360510.66 | 0.112529E+10 |
March | 0.399161E+09 | 0.00 | 0.399161E+09 | 92048694.27 | 0.104599E+10 |
April | 0.628932E+09 | 2814817.95 | 0.626117E+09 | 0.360458E+09 | 0.794803E+09 |
May | 0.812536E+09 | 39200699.82 | 0.773335E+09 | 0.485483E+09 | 0.637021E+09 |
June | 0.869233E+09 | 54506199.42 | 0.814727E+09 | 0.696847E+09 | 0.483096E+09 |
July | 0.851998E+09 | 48576644.09 | 0.803422E+09 | 0.728265E+09 | 0.462317E+09 |
August | 0.669715E+09 | 10492701.57 | 0.659222E+09 | 0.556978E+09 | 0.520999E+09 |
September | 0.493302E+09 | 109157.00 | 0.493193E+09 | 0.345771E+09 | 0.671470E+09 |
October | 0.326641E+09 | 0.00 | 0.326641E+09 | 0.104759E+09 | 0.966294E+09 |
November | 0.189931E+09 | 0.00 | 0.189931E+09 | 7731483.72 | 0.117667E+10 |
December | 0.133654E+09 | 0.00 | 0.133654E+09 | 0.00 | 0.146734E+10 |
Annual Sum or Average | 0.582036E+10 | 0.155700E+09 | 0.566466E+10 | 0.340059E+10 | 0.106802E+11 |
Minimum of Months | 0.133654E+09 | 0.00 | 0.133654E+09 | 0.00 | 0.462317E+09 |
Maximum of Months | 0.869233E+09 | 54506199.42 | 0.814727E+09 | 0.728265E+09 | 0.146734E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184717E+09 | 0.00 | 0.184717E+09 | 4886648.31 | 0.132890E+10 |
February | 0.260530E+09 | 0.00 | 0.260530E+09 | 17358796.75 | 0.112529E+10 |
March | 0.399154E+09 | 0.00 | 0.399154E+09 | 92043320.20 | 0.104599E+10 |
April | 0.628923E+09 | 2814756.07 | 0.626108E+09 | 0.360448E+09 | 0.794803E+09 |
May | 0.812524E+09 | 39199838.04 | 0.773324E+09 | 0.485469E+09 | 0.637021E+09 |
June | 0.869220E+09 | 54505001.17 | 0.814715E+09 | 0.696830E+09 | 0.483096E+09 |
July | 0.851986E+09 | 48575576.19 | 0.803411E+09 | 0.728250E+09 | 0.462316E+09 |
August | 0.669706E+09 | 10492470.91 | 0.659213E+09 | 0.556967E+09 | 0.520998E+09 |
September | 0.493295E+09 | 109154.60 | 0.493186E+09 | 0.345763E+09 | 0.671468E+09 |
October | 0.326636E+09 | 0.00 | 0.326636E+09 | 0.104755E+09 | 0.966293E+09 |
November | 0.189928E+09 | 0.00 | 0.189928E+09 | 7730629.68 | 0.117667E+10 |
December | 0.133652E+09 | 0.00 | 0.133652E+09 | 0.00 | 0.146734E+10 |
Annual Sum or Average | 0.582027E+10 | 0.155697E+09 | 0.566457E+10 | 0.340050E+10 | 0.106802E+11 |
Minimum of Months | 0.133652E+09 | 0.00 | 0.133652E+09 | 0.00 | 0.462316E+09 |
Maximum of Months | 0.869220E+09 | 54505001.17 | 0.814715E+09 | 0.728250E+09 | 0.146734E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184718E+09 | 0.00 | 0.184718E+09 | 4886839.56 | 0.132890E+10 |
February | 0.260531E+09 | 0.00 | 0.260531E+09 | 17359368.05 | 0.112529E+10 |
March | 0.399156E+09 | 0.00 | 0.399156E+09 | 92045111.56 | 0.104599E+10 |
April | 0.628926E+09 | 2814776.69 | 0.626111E+09 | 0.360451E+09 | 0.794803E+09 |
May | 0.812528E+09 | 39200125.30 | 0.773328E+09 | 0.485473E+09 | 0.637021E+09 |
June | 0.869224E+09 | 54505400.58 | 0.814719E+09 | 0.696836E+09 | 0.483096E+09 |
July | 0.851990E+09 | 48575932.16 | 0.803414E+09 | 0.728255E+09 | 0.462317E+09 |
August | 0.669709E+09 | 10492547.80 | 0.659216E+09 | 0.556970E+09 | 0.520998E+09 |
September | 0.493297E+09 | 109155.40 | 0.493188E+09 | 0.345766E+09 | 0.671469E+09 |
October | 0.326637E+09 | 0.00 | 0.326637E+09 | 0.104756E+09 | 0.966293E+09 |
November | 0.189929E+09 | 0.00 | 0.189929E+09 | 7730914.36 | 0.117667E+10 |
December | 0.133653E+09 | 0.00 | 0.133653E+09 | 0.00 | 0.146734E+10 |
Annual Sum or Average | 0.582030E+10 | 0.155698E+09 | 0.566460E+10 | 0.340053E+10 | 0.106802E+11 |
Minimum of Months | 0.133653E+09 | 0.00 | 0.133653E+09 | 0.00 | 0.462317E+09 |
Maximum of Months | 0.869224E+09 | 54505400.58 | 0.814719E+09 | 0.728255E+09 | 0.146734E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184717E+09 | 0.00 | 0.184717E+09 | 4886648.31 | 0.132890E+10 |
February | 0.260530E+09 | 0.00 | 0.260530E+09 | 17358796.75 | 0.112529E+10 |
March | 0.399154E+09 | 0.00 | 0.399154E+09 | 92043320.20 | 0.104599E+10 |
April | 0.628923E+09 | 2814756.07 | 0.626108E+09 | 0.360448E+09 | 0.794803E+09 |
May | 0.812524E+09 | 39199838.04 | 0.773324E+09 | 0.485469E+09 | 0.637021E+09 |
June | 0.869220E+09 | 54505001.17 | 0.814715E+09 | 0.696830E+09 | 0.483096E+09 |
July | 0.851986E+09 | 48575576.19 | 0.803411E+09 | 0.728250E+09 | 0.462316E+09 |
August | 0.669706E+09 | 10492470.91 | 0.659213E+09 | 0.556967E+09 | 0.520998E+09 |
September | 0.493295E+09 | 109154.60 | 0.493186E+09 | 0.345763E+09 | 0.671468E+09 |
October | 0.326636E+09 | 0.00 | 0.326636E+09 | 0.104755E+09 | 0.966293E+09 |
November | 0.189928E+09 | 0.00 | 0.189928E+09 | 7730629.68 | 0.117667E+10 |
December | 0.133652E+09 | 0.00 | 0.133652E+09 | 0.00 | 0.146734E+10 |
Annual Sum or Average | 0.582027E+10 | 0.155697E+09 | 0.566457E+10 | 0.340050E+10 | 0.106802E+11 |
Minimum of Months | 0.133652E+09 | 0.00 | 0.133652E+09 | 0.00 | 0.462316E+09 |
Maximum of Months | 0.869220E+09 | 54505001.17 | 0.814715E+09 | 0.728250E+09 | 0.146734E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.184710E+09 | 0.00 | 0.184710E+09 | 4886546.98 | 0.132885E+10 |
February | 0.260520E+09 | 0.00 | 0.260520E+09 | 17358382.76 | 0.112525E+10 |
March | 0.399139E+09 | 0.00 | 0.399139E+09 | 92040506.09 | 0.104595E+10 |
April | 0.628899E+09 | 2814652.93 | 0.626084E+09 | 0.360435E+09 | 0.794771E+09 |
May | 0.812493E+09 | 39198401.73 | 0.773295E+09 | 0.485452E+09 | 0.636996E+09 |
June | 0.869187E+09 | 54503004.08 | 0.814684E+09 | 0.696805E+09 | 0.483077E+09 |
July | 0.851954E+09 | 48573796.36 | 0.803380E+09 | 0.728223E+09 | 0.462298E+09 |
August | 0.669680E+09 | 10492086.46 | 0.659188E+09 | 0.556946E+09 | 0.520977E+09 |
September | 0.493276E+09 | 109150.60 | 0.493167E+09 | 0.345751E+09 | 0.671441E+09 |
October | 0.326623E+09 | 0.00 | 0.326623E+09 | 0.104751E+09 | 0.966254E+09 |
November | 0.189921E+09 | 0.00 | 0.189921E+09 | 7730460.44 | 0.117662E+10 |
December | 0.133647E+09 | 0.00 | 0.133647E+09 | 0.00 | 0.146728E+10 |
Annual Sum or Average | 0.582005E+10 | 0.155691E+09 | 0.566436E+10 | 0.340038E+10 | 0.106798E+11 |
Minimum of Months | 0.133647E+09 | 0.00 | 0.133647E+09 | 0.00 | 0.462298E+09 |
Maximum of Months | 0.869187E+09 | 54503004.08 | 0.814684E+09 | 0.728223E+09 | 0.146728E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419514E+09 | 0.168520E+09 | 0.250995E+09 | 0.220468E+09 | 0.135966E+10 |
February | 0.565030E+09 | 0.208726E+09 | 0.356304E+09 | 0.336515E+09 | 0.115258E+10 |
March | 0.653733E+09 | 0.128827E+09 | 0.524906E+09 | 0.351739E+09 | 0.106324E+10 |
April | 0.169870E+10 | 0.798232E+09 | 0.900472E+09 | 0.174102E+10 | 0.813136E+09 |
May | 0.184567E+10 | 0.804866E+09 | 0.104081E+10 | 0.184462E+10 | 0.717977E+09 |
June | 0.176795E+10 | 0.706100E+09 | 0.106185E+10 | 0.189538E+10 | 0.539906E+09 |
July | 0.186488E+10 | 0.792574E+09 | 0.107231E+10 | 0.209180E+10 | 0.513714E+09 |
August | 0.176657E+10 | 0.844049E+09 | 0.922518E+09 | 0.204260E+10 | 0.555085E+09 |
September | 0.153954E+10 | 0.818655E+09 | 0.720881E+09 | 0.171284E+10 | 0.699953E+09 |
October | 0.767926E+09 | 0.318248E+09 | 0.449678E+09 | 0.647029E+09 | 0.100536E+10 |
November | 0.387428E+09 | 0.132041E+09 | 0.255387E+09 | 0.200786E+09 | 0.119696E+10 |
December | 0.296703E+09 | 0.110310E+09 | 0.186393E+09 | 0.132419E+09 | 0.148423E+10 |
Annual Sum or Average | 0.135736E+11 | 0.583115E+10 | 0.774249E+10 | 0.132172E+11 | 0.111018E+11 |
Minimum of Months | 0.296703E+09 | 0.110310E+09 | 0.186393E+09 | 0.132419E+09 | 0.513714E+09 |
Maximum of Months | 0.186488E+10 | 0.844049E+09 | 0.107231E+10 | 0.209180E+10 | 0.148423E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419514E+09 | 0.168520E+09 | 0.250995E+09 | 0.220468E+09 | 0.135966E+10 |
February | 0.565030E+09 | 0.208726E+09 | 0.356304E+09 | 0.336515E+09 | 0.115258E+10 |
March | 0.653733E+09 | 0.128827E+09 | 0.524906E+09 | 0.351739E+09 | 0.106324E+10 |
April | 0.169870E+10 | 0.798232E+09 | 0.900472E+09 | 0.174102E+10 | 0.813136E+09 |
May | 0.184567E+10 | 0.804866E+09 | 0.104081E+10 | 0.184462E+10 | 0.717977E+09 |
June | 0.176795E+10 | 0.706100E+09 | 0.106185E+10 | 0.189538E+10 | 0.539906E+09 |
July | 0.186488E+10 | 0.792574E+09 | 0.107231E+10 | 0.209180E+10 | 0.513714E+09 |
August | 0.176657E+10 | 0.844049E+09 | 0.922518E+09 | 0.204260E+10 | 0.555085E+09 |
September | 0.153954E+10 | 0.818655E+09 | 0.720881E+09 | 0.171284E+10 | 0.699953E+09 |
October | 0.767926E+09 | 0.318248E+09 | 0.449678E+09 | 0.647029E+09 | 0.100536E+10 |
November | 0.387428E+09 | 0.132041E+09 | 0.255387E+09 | 0.200786E+09 | 0.119696E+10 |
December | 0.296703E+09 | 0.110310E+09 | 0.186393E+09 | 0.132419E+09 | 0.148423E+10 |
Annual Sum or Average | 0.135736E+11 | 0.583115E+10 | 0.774249E+10 | 0.132172E+11 | 0.111018E+11 |
Minimum of Months | 0.296703E+09 | 0.110310E+09 | 0.186393E+09 | 0.132419E+09 | 0.513714E+09 |
Maximum of Months | 0.186488E+10 | 0.844049E+09 | 0.107231E+10 | 0.209180E+10 | 0.148423E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.419507E+09 | 0.168517E+09 | 0.250990E+09 | 0.220464E+09 | 0.135964E+10 |
February | 0.565020E+09 | 0.208723E+09 | 0.356297E+09 | 0.336509E+09 | 0.115255E+10 |
March | 0.653721E+09 | 0.128825E+09 | 0.524897E+09 | 0.351733E+09 | 0.106322E+10 |
April | 0.169867E+10 | 0.798218E+09 | 0.900455E+09 | 0.174099E+10 | 0.813121E+09 |
May | 0.184564E+10 | 0.804851E+09 | 0.104079E+10 | 0.184459E+10 | 0.717964E+09 |
June | 0.176791E+10 | 0.706087E+09 | 0.106183E+10 | 0.189535E+10 | 0.539896E+09 |
July | 0.186485E+10 | 0.792559E+09 | 0.107229E+10 | 0.209176E+10 | 0.513704E+09 |
August | 0.176653E+10 | 0.844034E+09 | 0.922501E+09 | 0.204256E+10 | 0.555075E+09 |
September | 0.153951E+10 | 0.818640E+09 | 0.720868E+09 | 0.171281E+10 | 0.699941E+09 |
October | 0.767912E+09 | 0.318242E+09 | 0.449669E+09 | 0.647017E+09 | 0.100534E+10 |
November | 0.387421E+09 | 0.132039E+09 | 0.255382E+09 | 0.200782E+09 | 0.119694E+10 |
December | 0.296697E+09 | 0.110308E+09 | 0.186389E+09 | 0.132417E+09 | 0.148421E+10 |
Annual Sum or Average | 0.135734E+11 | 0.583104E+10 | 0.774235E+10 | 0.132170E+11 | 0.111016E+11 |
Minimum of Months | 0.296697E+09 | 0.110308E+09 | 0.186389E+09 | 0.132417E+09 | 0.513704E+09 |
Maximum of Months | 0.186485E+10 | 0.844034E+09 | 0.107229E+10 | 0.209176E+10 | 0.148421E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104870E+10 | 0.678863E+09 | 0.369833E+09 | 0.101234E+10 | 0.113316E+10 |
February | 0.115684E+10 | 0.705919E+09 | 0.450923E+09 | 0.115006E+10 | 0.100548E+10 |
March | 0.791870E+09 | 0.230556E+09 | 0.561314E+09 | 0.606760E+09 | 0.955052E+09 |
April | 0.159134E+10 | 0.719263E+09 | 0.872076E+09 | 0.178574E+10 | 0.799796E+09 |
May | 0.136006E+10 | 0.442788E+09 | 0.917272E+09 | 0.140968E+10 | 0.702058E+09 |
June | 0.121249E+10 | 0.293491E+09 | 0.919000E+09 | 0.130964E+10 | 0.527518E+09 |
July | 0.135750E+10 | 0.425114E+09 | 0.932387E+09 | 0.158351E+10 | 0.508441E+09 |
August | 0.159069E+10 | 0.715548E+09 | 0.875142E+09 | 0.197126E+10 | 0.554574E+09 |
September | 0.181914E+10 | 0.106568E+10 | 0.753461E+09 | 0.223747E+10 | 0.675250E+09 |
October | 0.129148E+10 | 0.754812E+09 | 0.536672E+09 | 0.140376E+10 | 0.904979E+09 |
November | 0.886123E+09 | 0.539050E+09 | 0.347073E+09 | 0.859623E+09 | 0.104428E+10 |
December | 0.725745E+09 | 0.464988E+09 | 0.260757E+09 | 0.675426E+09 | 0.128955E+10 |
Annual Sum or Average | 0.148320E+11 | 0.703607E+10 | 0.779591E+10 | 0.160053E+11 | 0.101001E+11 |
Minimum of Months | 0.725745E+09 | 0.230556E+09 | 0.260757E+09 | 0.606760E+09 | 0.508441E+09 |
Maximum of Months | 0.181914E+10 | 0.106568E+10 | 0.932387E+09 | 0.223747E+10 | 0.128955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104869E+10 | 0.678858E+09 | 0.369831E+09 | 0.101233E+10 | 0.113316E+10 |
February | 0.115683E+10 | 0.705914E+09 | 0.450920E+09 | 0.115005E+10 | 0.100548E+10 |
March | 0.791865E+09 | 0.230554E+09 | 0.561310E+09 | 0.606753E+09 | 0.955052E+09 |
April | 0.159133E+10 | 0.719258E+09 | 0.872071E+09 | 0.178572E+10 | 0.799795E+09 |
May | 0.136005E+10 | 0.442785E+09 | 0.917267E+09 | 0.140967E+10 | 0.702059E+09 |
June | 0.121248E+10 | 0.293489E+09 | 0.918995E+09 | 0.130963E+10 | 0.527517E+09 |
July | 0.135749E+10 | 0.425110E+09 | 0.932383E+09 | 0.158350E+10 | 0.508440E+09 |
August | 0.159068E+10 | 0.715543E+09 | 0.875138E+09 | 0.197125E+10 | 0.554573E+09 |
September | 0.181913E+10 | 0.106567E+10 | 0.753457E+09 | 0.223745E+10 | 0.675249E+09 |
October | 0.129147E+10 | 0.754806E+09 | 0.536668E+09 | 0.140375E+10 | 0.904979E+09 |
November | 0.886117E+09 | 0.539046E+09 | 0.347071E+09 | 0.859615E+09 | 0.104428E+10 |
December | 0.725740E+09 | 0.464984E+09 | 0.260756E+09 | 0.675420E+09 | 0.128955E+10 |
Annual Sum or Average | 0.148319E+11 | 0.703602E+10 | 0.779587E+10 | 0.160051E+11 | 0.101001E+11 |
Minimum of Months | 0.725740E+09 | 0.230554E+09 | 0.260756E+09 | 0.606753E+09 | 0.508440E+09 |
Maximum of Months | 0.181913E+10 | 0.106567E+10 | 0.932383E+09 | 0.223745E+10 | 0.128955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104870E+10 | 0.678863E+09 | 0.369833E+09 | 0.101234E+10 | 0.113316E+10 |
February | 0.115684E+10 | 0.705919E+09 | 0.450923E+09 | 0.115006E+10 | 0.100548E+10 |
March | 0.791870E+09 | 0.230556E+09 | 0.561314E+09 | 0.606760E+09 | 0.955052E+09 |
April | 0.159134E+10 | 0.719263E+09 | 0.872076E+09 | 0.178574E+10 | 0.799796E+09 |
May | 0.136006E+10 | 0.442788E+09 | 0.917272E+09 | 0.140968E+10 | 0.702058E+09 |
June | 0.121249E+10 | 0.293491E+09 | 0.919000E+09 | 0.130964E+10 | 0.527518E+09 |
July | 0.135750E+10 | 0.425114E+09 | 0.932387E+09 | 0.158351E+10 | 0.508441E+09 |
August | 0.159069E+10 | 0.715548E+09 | 0.875142E+09 | 0.197126E+10 | 0.554574E+09 |
September | 0.181914E+10 | 0.106568E+10 | 0.753461E+09 | 0.223747E+10 | 0.675250E+09 |
October | 0.129148E+10 | 0.754812E+09 | 0.536672E+09 | 0.140376E+10 | 0.904979E+09 |
November | 0.886123E+09 | 0.539050E+09 | 0.347073E+09 | 0.859623E+09 | 0.104428E+10 |
December | 0.725745E+09 | 0.464988E+09 | 0.260757E+09 | 0.675426E+09 | 0.128955E+10 |
Annual Sum or Average | 0.148320E+11 | 0.703607E+10 | 0.779591E+10 | 0.160053E+11 | 0.101001E+11 |
Minimum of Months | 0.725745E+09 | 0.230556E+09 | 0.260757E+09 | 0.606760E+09 | 0.508441E+09 |
Maximum of Months | 0.181914E+10 | 0.106568E+10 | 0.932387E+09 | 0.223747E+10 | 0.128955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104869E+10 | 0.678858E+09 | 0.369831E+09 | 0.101233E+10 | 0.113316E+10 |
February | 0.115683E+10 | 0.705914E+09 | 0.450920E+09 | 0.115005E+10 | 0.100548E+10 |
March | 0.791865E+09 | 0.230554E+09 | 0.561310E+09 | 0.606753E+09 | 0.955052E+09 |
April | 0.159133E+10 | 0.719258E+09 | 0.872071E+09 | 0.178572E+10 | 0.799795E+09 |
May | 0.136005E+10 | 0.442785E+09 | 0.917267E+09 | 0.140967E+10 | 0.702059E+09 |
June | 0.121248E+10 | 0.293489E+09 | 0.918995E+09 | 0.130963E+10 | 0.527517E+09 |
July | 0.135749E+10 | 0.425110E+09 | 0.932383E+09 | 0.158350E+10 | 0.508440E+09 |
August | 0.159068E+10 | 0.715543E+09 | 0.875138E+09 | 0.197125E+10 | 0.554573E+09 |
September | 0.181913E+10 | 0.106567E+10 | 0.753457E+09 | 0.223745E+10 | 0.675249E+09 |
October | 0.129147E+10 | 0.754806E+09 | 0.536668E+09 | 0.140375E+10 | 0.904979E+09 |
November | 0.886117E+09 | 0.539046E+09 | 0.347071E+09 | 0.859615E+09 | 0.104428E+10 |
December | 0.725740E+09 | 0.464984E+09 | 0.260756E+09 | 0.675420E+09 | 0.128955E+10 |
Annual Sum or Average | 0.148319E+11 | 0.703602E+10 | 0.779587E+10 | 0.160051E+11 | 0.101001E+11 |
Minimum of Months | 0.725740E+09 | 0.230554E+09 | 0.260756E+09 | 0.606753E+09 | 0.508440E+09 |
Maximum of Months | 0.181913E+10 | 0.106567E+10 | 0.932383E+09 | 0.223745E+10 | 0.128955E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.104865E+10 | 0.678833E+09 | 0.369817E+09 | 0.101229E+10 | 0.113312E+10 |
February | 0.115679E+10 | 0.705888E+09 | 0.450903E+09 | 0.115001E+10 | 0.100544E+10 |
March | 0.791835E+09 | 0.230546E+09 | 0.561290E+09 | 0.606732E+09 | 0.955013E+09 |
April | 0.159127E+10 | 0.719232E+09 | 0.872038E+09 | 0.178566E+10 | 0.799763E+09 |
May | 0.136000E+10 | 0.442769E+09 | 0.917233E+09 | 0.140962E+10 | 0.702030E+09 |
June | 0.121244E+10 | 0.293478E+09 | 0.918960E+09 | 0.130959E+10 | 0.527496E+09 |
July | 0.135744E+10 | 0.425095E+09 | 0.932347E+09 | 0.158344E+10 | 0.508420E+09 |
August | 0.159062E+10 | 0.715516E+09 | 0.875105E+09 | 0.197118E+10 | 0.554551E+09 |
September | 0.181906E+10 | 0.106563E+10 | 0.753428E+09 | 0.223737E+10 | 0.675222E+09 |
October | 0.129143E+10 | 0.754779E+09 | 0.536648E+09 | 0.140370E+10 | 0.904942E+09 |
November | 0.886085E+09 | 0.539027E+09 | 0.347058E+09 | 0.859584E+09 | 0.104424E+10 |
December | 0.725713E+09 | 0.464967E+09 | 0.260746E+09 | 0.675396E+09 | 0.128950E+10 |
Annual Sum or Average | 0.148313E+11 | 0.703576E+10 | 0.779557E+10 | 0.160046E+11 | 0.100997E+11 |
Minimum of Months | 0.725713E+09 | 0.230546E+09 | 0.260746E+09 | 0.606732E+09 | 0.508420E+09 |
Maximum of Months | 0.181906E+10 | 0.106563E+10 | 0.932347E+09 | 0.223737E+10 | 0.128950E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407957E+09 | 0.134791E+09 | 0.273167E+09 | 0.213533E+09 | 0.146319E+10 |
February | 0.652408E+09 | 0.275468E+09 | 0.376940E+09 | 0.468578E+09 | 0.129836E+10 |
March | 0.653122E+09 | 0.124942E+09 | 0.528180E+09 | 0.321233E+09 | 0.122796E+10 |
April | 0.149135E+10 | 0.592378E+09 | 0.898974E+09 | 0.144651E+10 | 0.979509E+09 |
May | 0.180802E+10 | 0.735205E+09 | 0.107282E+10 | 0.178561E+10 | 0.807538E+09 |
June | 0.188949E+10 | 0.777831E+09 | 0.111166E+10 | 0.202855E+10 | 0.632949E+09 |
July | 0.198851E+10 | 0.876738E+09 | 0.111177E+10 | 0.222397E+10 | 0.623877E+09 |
August | 0.167021E+10 | 0.723155E+09 | 0.947057E+09 | 0.187907E+10 | 0.690115E+09 |
September | 0.129673E+10 | 0.581483E+09 | 0.715247E+09 | 0.140661E+10 | 0.798333E+09 |
October | 0.714814E+09 | 0.257044E+09 | 0.457770E+09 | 0.572528E+09 | 0.114539E+10 |
November | 0.374354E+09 | 0.109279E+09 | 0.265075E+09 | 0.191850E+09 | 0.139892E+10 |
December | 0.218959E+09 | 46205054.62 | 0.172754E+09 | 59622559.29 | 0.177808E+10 |
Annual Sum or Average | 0.131659E+11 | 0.523452E+10 | 0.793141E+10 | 0.125977E+11 | 0.128442E+11 |
Minimum of Months | 0.218959E+09 | 46205054.62 | 0.172754E+09 | 59622559.29 | 0.623877E+09 |
Maximum of Months | 0.198851E+10 | 0.876738E+09 | 0.111177E+10 | 0.222397E+10 | 0.177808E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407957E+09 | 0.134791E+09 | 0.273167E+09 | 0.213533E+09 | 0.146319E+10 |
February | 0.652408E+09 | 0.275468E+09 | 0.376940E+09 | 0.468578E+09 | 0.129836E+10 |
March | 0.653122E+09 | 0.124942E+09 | 0.528180E+09 | 0.321233E+09 | 0.122796E+10 |
April | 0.149135E+10 | 0.592378E+09 | 0.898974E+09 | 0.144651E+10 | 0.979509E+09 |
May | 0.180802E+10 | 0.735205E+09 | 0.107282E+10 | 0.178561E+10 | 0.807538E+09 |
June | 0.188949E+10 | 0.777831E+09 | 0.111166E+10 | 0.202855E+10 | 0.632949E+09 |
July | 0.198851E+10 | 0.876738E+09 | 0.111177E+10 | 0.222397E+10 | 0.623877E+09 |
August | 0.167021E+10 | 0.723155E+09 | 0.947057E+09 | 0.187907E+10 | 0.690115E+09 |
September | 0.129673E+10 | 0.581483E+09 | 0.715247E+09 | 0.140661E+10 | 0.798333E+09 |
October | 0.714814E+09 | 0.257044E+09 | 0.457770E+09 | 0.572528E+09 | 0.114539E+10 |
November | 0.374354E+09 | 0.109279E+09 | 0.265075E+09 | 0.191850E+09 | 0.139892E+10 |
December | 0.218959E+09 | 46205054.62 | 0.172754E+09 | 59622559.29 | 0.177808E+10 |
Annual Sum or Average | 0.131659E+11 | 0.523452E+10 | 0.793141E+10 | 0.125977E+11 | 0.128442E+11 |
Minimum of Months | 0.218959E+09 | 46205054.62 | 0.172754E+09 | 59622559.29 | 0.623877E+09 |
Maximum of Months | 0.198851E+10 | 0.876738E+09 | 0.111177E+10 | 0.222397E+10 | 0.177808E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.407950E+09 | 0.134788E+09 | 0.273162E+09 | 0.213529E+09 | 0.146317E+10 |
February | 0.652396E+09 | 0.275462E+09 | 0.376933E+09 | 0.468570E+09 | 0.129833E+10 |
March | 0.653110E+09 | 0.124940E+09 | 0.528170E+09 | 0.321227E+09 | 0.122794E+10 |
April | 0.149132E+10 | 0.592367E+09 | 0.898957E+09 | 0.144649E+10 | 0.979492E+09 |
May | 0.180799E+10 | 0.735192E+09 | 0.107280E+10 | 0.178558E+10 | 0.807523E+09 |
June | 0.188945E+10 | 0.777816E+09 | 0.111164E+10 | 0.202851E+10 | 0.632937E+09 |
July | 0.198847E+10 | 0.876722E+09 | 0.111175E+10 | 0.222393E+10 | 0.623865E+09 |
August | 0.167018E+10 | 0.723142E+09 | 0.947040E+09 | 0.187904E+10 | 0.690103E+09 |
September | 0.129671E+10 | 0.581472E+09 | 0.715234E+09 | 0.140658E+10 | 0.798319E+09 |
October | 0.714801E+09 | 0.257039E+09 | 0.457762E+09 | 0.572518E+09 | 0.114537E+10 |
November | 0.374347E+09 | 0.109277E+09 | 0.265071E+09 | 0.191846E+09 | 0.139889E+10 |
December | 0.218955E+09 | 46204210.35 | 0.172750E+09 | 59621469.86 | 0.177805E+10 |
Annual Sum or Average | 0.131657E+11 | 0.523442E+10 | 0.793126E+10 | 0.125974E+11 | 0.128440E+11 |
Minimum of Months | 0.218955E+09 | 46204210.35 | 0.172750E+09 | 59621469.86 | 0.623865E+09 |
Maximum of Months | 0.198847E+10 | 0.876722E+09 | 0.111175E+10 | 0.222393E+10 | 0.177805E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.923601E+09 | 0.00 | 0.923601E+09 | 52959337.74 | 0.588478E+10 |
February | 0.130267E+10 | 0.00 | 0.130267E+10 | 0.165310E+09 | 0.496829E+10 |
March | 0.199581E+10 | 0.00 | 0.199581E+10 | 0.605817E+09 | 0.460158E+10 |
April | 0.314466E+10 | 14074179.42 | 0.313058E+10 | 0.192825E+10 | 0.363128E+10 |
May | 0.406268E+10 | 0.196005E+09 | 0.386668E+10 | 0.254464E+10 | 0.297893E+10 |
June | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.354316E+10 | 0.228935E+10 |
July | 0.425999E+10 | 0.242885E+09 | 0.401711E+10 | 0.373395E+10 | 0.217643E+10 |
August | 0.334857E+10 | 52463842.21 | 0.329611E+10 | 0.287013E+10 | 0.243737E+10 |
September | 0.246651E+10 | 545788.48 | 0.246596E+10 | 0.180946E+10 | 0.313932E+10 |
October | 0.163320E+10 | 0.00 | 0.163320E+10 | 0.642247E+09 | 0.428398E+10 |
November | 0.949658E+09 | 0.00 | 0.949658E+09 | 85743155.02 | 0.503439E+10 |
December | 0.668272E+09 | 0.00 | 0.668272E+09 | 2755805.72 | 0.624201E+10 |
Annual Sum or Average | 0.291018E+11 | 0.778506E+09 | 0.283233E+11 | 0.179844E+11 | 0.476677E+11 |
Minimum of Months | 0.668272E+09 | 0.00 | 0.668272E+09 | 2755805.72 | 0.217643E+10 |
Maximum of Months | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.373395E+10 | 0.624201E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125853E+10 | 0.505554E+09 | 0.752977E+09 | 0.714260E+09 | 0.369041E+10 |
February | 0.169507E+10 | 0.626173E+09 | 0.106890E+10 | 0.107208E+10 | 0.315298E+10 |
March | 0.196118E+10 | 0.386477E+09 | 0.157470E+10 | 0.115017E+10 | 0.290568E+10 |
April | 0.509606E+10 | 0.239467E+10 | 0.270139E+10 | 0.522994E+10 | 0.234014E+10 |
May | 0.553696E+10 | 0.241457E+10 | 0.312239E+10 | 0.553635E+10 | 0.205898E+10 |
June | 0.530378E+10 | 0.211828E+10 | 0.318550E+10 | 0.567010E+10 | 0.157081E+10 |
July | 0.559458E+10 | 0.237770E+10 | 0.321689E+10 | 0.625305E+10 | 0.150428E+10 |
August | 0.529965E+10 | 0.253212E+10 | 0.276753E+10 | 0.610709E+10 | 0.163871E+10 |
September | 0.461856E+10 | 0.245594E+10 | 0.216262E+10 | 0.513483E+10 | 0.202240E+10 |
October | 0.230375E+10 | 0.954735E+09 | 0.134902E+10 | 0.199571E+10 | 0.276050E+10 |
November | 0.116227E+10 | 0.396120E+09 | 0.766154E+09 | 0.653016E+09 | 0.319149E+10 |
December | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.442165E+09 | 0.396100E+10 |
Annual Sum or Average | 0.407205E+11 | 0.174933E+11 | 0.232272E+11 | 0.399588E+11 | 0.307974E+11 |
Minimum of Months | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.442165E+09 | 0.150428E+10 |
Maximum of Months | 0.559458E+10 | 0.253212E+10 | 0.321689E+10 | 0.625305E+10 | 0.396100E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.524358E+10 | 0.339438E+10 | 0.184920E+10 | 0.509534E+10 | 0.544136E+10 |
February | 0.578432E+10 | 0.352967E+10 | 0.225465E+10 | 0.577249E+10 | 0.484121E+10 |
March | 0.395942E+10 | 0.115280E+10 | 0.280661E+10 | 0.310119E+10 | 0.450441E+10 |
April | 0.795683E+10 | 0.359639E+10 | 0.436043E+10 | 0.892390E+10 | 0.386900E+10 |
May | 0.680040E+10 | 0.221399E+10 | 0.458641E+10 | 0.704074E+10 | 0.341258E+10 |
June | 0.606254E+10 | 0.146749E+10 | 0.459505E+10 | 0.654852E+10 | 0.255621E+10 |
July | 0.678760E+10 | 0.212561E+10 | 0.466199E+10 | 0.792189E+10 | 0.246193E+10 |
August | 0.795358E+10 | 0.357781E+10 | 0.437576E+10 | 0.984350E+10 | 0.270311E+10 |
September | 0.909586E+10 | 0.532851E+10 | 0.376735E+10 | 0.111400E+11 | 0.332662E+10 |
October | 0.645754E+10 | 0.377414E+10 | 0.268340E+10 | 0.702566E+10 | 0.434270E+10 |
November | 0.443070E+10 | 0.269531E+10 | 0.173539E+10 | 0.433612E+10 | 0.489434E+10 |
December | 0.362880E+10 | 0.232499E+10 | 0.130381E+10 | 0.344294E+10 | 0.597907E+10 |
Annual Sum or Average | 0.741611E+11 | 0.351811E+11 | 0.389801E+11 | 0.801923E+11 | 0.483325E+11 |
Minimum of Months | 0.362880E+10 | 0.115280E+10 | 0.130381E+10 | 0.310119E+10 | 0.246193E+10 |
Maximum of Months | 0.909586E+10 | 0.532851E+10 | 0.466199E+10 | 0.111400E+11 | 0.597907E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122386E+10 | 0.404368E+09 | 0.819492E+09 | 0.705772E+09 | 0.384381E+10 |
February | 0.195720E+10 | 0.826394E+09 | 0.113081E+10 | 0.150466E+10 | 0.333567E+10 |
March | 0.195935E+10 | 0.374823E+09 | 0.158452E+10 | 0.112475E+10 | 0.303633E+10 |
April | 0.447401E+10 | 0.177712E+10 | 0.269689E+10 | 0.449228E+10 | 0.255121E+10 |
May | 0.542402E+10 | 0.220559E+10 | 0.321842E+10 | 0.543269E+10 | 0.224148E+10 |
June | 0.566841E+10 | 0.233347E+10 | 0.333494E+10 | 0.614758E+10 | 0.173082E+10 |
July | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.677230E+10 | 0.167405E+10 |
August | 0.501059E+10 | 0.216944E+10 | 0.284114E+10 | 0.574319E+10 | 0.182772E+10 |
September | 0.389015E+10 | 0.174443E+10 | 0.214572E+10 | 0.428427E+10 | 0.220532E+10 |
October | 0.214442E+10 | 0.771124E+09 | 0.137330E+10 | 0.183411E+10 | 0.292178E+10 |
November | 0.112305E+10 | 0.327833E+09 | 0.795218E+09 | 0.658065E+09 | 0.338376E+10 |
December | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.227876E+09 | 0.422420E+10 |
Annual Sum or Average | 0.394974E+11 | 0.157034E+11 | 0.237940E+11 | 0.389275E+11 | 0.329761E+11 |
Minimum of Months | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.227876E+09 | 0.167405E+10 |
Maximum of Months | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.677230E+10 | 0.422420E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.923601E+09 | 0.00 | 0.923601E+09 | 90758862.44 | 0.532064E+10 |
February | 0.130267E+10 | 0.00 | 0.130267E+10 | 0.245126E+09 | 0.448131E+10 |
March | 0.199581E+10 | 0.00 | 0.199581E+10 | 0.728165E+09 | 0.416331E+10 |
April | 0.314466E+10 | 14074179.42 | 0.313058E+10 | 0.204399E+10 | 0.336201E+10 |
May | 0.406268E+10 | 0.196005E+09 | 0.386668E+10 | 0.268644E+10 | 0.277428E+10 |
June | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.360030E+10 | 0.218817E+10 |
July | 0.425999E+10 | 0.242885E+09 | 0.401711E+10 | 0.377984E+10 | 0.209169E+10 |
August | 0.334857E+10 | 52463842.21 | 0.329611E+10 | 0.290812E+10 | 0.233809E+10 |
September | 0.246651E+10 | 545788.48 | 0.246596E+10 | 0.189806E+10 | 0.292783E+10 |
October | 0.163320E+10 | 0.00 | 0.163320E+10 | 0.767256E+09 | 0.380428E+10 |
November | 0.949658E+09 | 0.00 | 0.949658E+09 | 0.136598E+09 | 0.448153E+10 |
December | 0.668272E+09 | 0.00 | 0.668272E+09 | 17873440.33 | 0.569177E+10 |
Annual Sum or Average | 0.291018E+11 | 0.778506E+09 | 0.283233E+11 | 0.189025E+11 | 0.436249E+11 |
Minimum of Months | 0.668272E+09 | 0.00 | 0.668272E+09 | 17873440.33 | 0.209169E+10 |
Maximum of Months | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.377984E+10 | 0.569177E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.125853E+10 | 0.505554E+09 | 0.752977E+09 | 0.767512E+09 | 0.334988E+10 |
February | 0.169507E+10 | 0.626173E+09 | 0.106890E+10 | 0.114928E+10 | 0.286015E+10 |
March | 0.196118E+10 | 0.386477E+09 | 0.157470E+10 | 0.124124E+10 | 0.265202E+10 |
April | 0.509606E+10 | 0.239467E+10 | 0.270139E+10 | 0.528715E+10 | 0.220536E+10 |
May | 0.553696E+10 | 0.241457E+10 | 0.312239E+10 | 0.559690E+10 | 0.194712E+10 |
June | 0.530378E+10 | 0.211828E+10 | 0.318550E+10 | 0.568769E+10 | 0.151689E+10 |
July | 0.559458E+10 | 0.237770E+10 | 0.321689E+10 | 0.626226E+10 | 0.146132E+10 |
August | 0.529965E+10 | 0.253212E+10 | 0.276753E+10 | 0.611183E+10 | 0.159448E+10 |
September | 0.461856E+10 | 0.245594E+10 | 0.216262E+10 | 0.517397E+10 | 0.192316E+10 |
October | 0.230375E+10 | 0.954735E+09 | 0.134902E+10 | 0.207989E+10 | 0.248676E+10 |
November | 0.116227E+10 | 0.396120E+09 | 0.766154E+09 | 0.706739E+09 | 0.286562E+10 |
December | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.478037E+09 | 0.362544E+10 |
Annual Sum or Average | 0.407205E+11 | 0.174933E+11 | 0.232272E+11 | 0.405425E+11 | 0.284882E+11 |
Minimum of Months | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.478037E+09 | 0.146132E+10 |
Maximum of Months | 0.559458E+10 | 0.253212E+10 | 0.321689E+10 | 0.626226E+10 | 0.362544E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.524358E+10 | 0.339438E+10 | 0.184920E+10 | 0.523289E+10 | 0.492535E+10 |
February | 0.578432E+10 | 0.352967E+10 | 0.225465E+10 | 0.591068E+10 | 0.439525E+10 |
March | 0.395942E+10 | 0.115280E+10 | 0.280661E+10 | 0.324956E+10 | 0.409245E+10 |
April | 0.795683E+10 | 0.359639E+10 | 0.436043E+10 | 0.900013E+10 | 0.363824E+10 |
May | 0.680040E+10 | 0.221399E+10 | 0.458641E+10 | 0.712655E+10 | 0.320479E+10 |
June | 0.606254E+10 | 0.146749E+10 | 0.459505E+10 | 0.658400E+10 | 0.245166E+10 |
July | 0.678760E+10 | 0.212561E+10 | 0.466199E+10 | 0.794468E+10 | 0.237361E+10 |
August | 0.795358E+10 | 0.357781E+10 | 0.437576E+10 | 0.985210E+10 | 0.261584E+10 |
September | 0.909586E+10 | 0.532851E+10 | 0.376735E+10 | 0.111857E+11 | 0.315961E+10 |
October | 0.645754E+10 | 0.377414E+10 | 0.268340E+10 | 0.714180E+10 | 0.391899E+10 |
November | 0.443070E+10 | 0.269531E+10 | 0.173539E+10 | 0.444745E+10 | 0.438467E+10 |
December | 0.362880E+10 | 0.232499E+10 | 0.130381E+10 | 0.353309E+10 | 0.545545E+10 |
Annual Sum or Average | 0.741611E+11 | 0.351811E+11 | 0.389801E+11 | 0.812086E+11 | 0.446159E+11 |
Minimum of Months | 0.362880E+10 | 0.115280E+10 | 0.130381E+10 | 0.324956E+10 | 0.237361E+10 |
Maximum of Months | 0.909586E+10 | 0.532851E+10 | 0.466199E+10 | 0.111857E+11 | 0.545545E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.122386E+10 | 0.404368E+09 | 0.819492E+09 | 0.748257E+09 | 0.352584E+10 |
February | 0.195720E+10 | 0.826394E+09 | 0.113081E+10 | 0.155898E+10 | 0.307288E+10 |
March | 0.195935E+10 | 0.374823E+09 | 0.158452E+10 | 0.119711E+10 | 0.279956E+10 |
April | 0.447401E+10 | 0.177712E+10 | 0.269689E+10 | 0.454869E+10 | 0.240595E+10 |
May | 0.542402E+10 | 0.220559E+10 | 0.321842E+10 | 0.548563E+10 | 0.212093E+10 |
June | 0.566841E+10 | 0.233347E+10 | 0.333494E+10 | 0.616156E+10 | 0.166776E+10 |
July | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.677959E+10 | 0.161951E+10 |
August | 0.501059E+10 | 0.216944E+10 | 0.284114E+10 | 0.574902E+10 | 0.176953E+10 |
September | 0.389015E+10 | 0.174443E+10 | 0.214572E+10 | 0.432373E+10 | 0.209070E+10 |
October | 0.214442E+10 | 0.771124E+09 | 0.137330E+10 | 0.190086E+10 | 0.266659E+10 |
November | 0.112305E+10 | 0.327833E+09 | 0.795218E+09 | 0.694895E+09 | 0.308528E+10 |
December | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.246322E+09 | 0.391087E+10 |
Annual Sum or Average | 0.394974E+11 | 0.157034E+11 | 0.237940E+11 | 0.393946E+11 | 0.307354E+11 |
Minimum of Months | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.246322E+09 | 0.161951E+10 |
Maximum of Months | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.677959E+10 | 0.391087E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 9.12 | 2480.76 | 344.83 | 0.00 | 344.83 | 0.00 | 0.00 |
February | 35.88 | 2325.73 | 538.46 | 0.00 | 538.46 | 0.00 | 0.00 |
March | 171.83 | 1952.62 | 745.13 | 0.00 | 745.13 | 0.00 | 0.00 |
April | 695.31 | 1533.17 | 1213.20 | 5.43 | 1207.77 | 0.00 | 0.00 |
May | 906.27 | 1189.17 | 1516.80 | 73.18 | 1443.63 | 0.00 | 0.00 |
June | 1344.19 | 931.89 | 1676.73 | 105.14 | 1571.59 | 0.00 | 0.00 |
July | 1359.48 | 863.04 | 1590.47 | 90.68 | 1499.79 | 0.00 | 0.00 |
August | 1039.74 | 972.58 | 1250.19 | 19.59 | 1230.61 | 0.00 | 0.00 |
September | 666.98 | 1295.26 | 951.57 | 0.21 | 951.36 | 0.00 | 0.00 |
October | 195.56 | 1803.85 | 609.76 | 0.00 | 609.76 | 0.00 | 0.00 |
November | 14.91 | 2269.79 | 366.37 | 0.00 | 366.37 | 0.00 | 0.00 |
December | 0.00 | 2739.19 | 249.50 | 0.00 | 249.50 | 0.00 | 0.00 |
Annual Sum or Average | 539.15 | 1693.32 | 922.79 | 24.69 | 898.11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 863.04 | 249.50 | 0.00 | 249.50 | 0.00 | 0.00 |
Maximum of Months | 1359.48 | 2739.19 | 1676.73 | 105.14 | 1571.59 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 246.94 | 1522.91 | 469.88 | 188.75 | 281.13 | 0.00 | 0.00 |
February | 417.30 | 1429.28 | 700.68 | 258.84 | 441.84 | 0.00 | 0.00 |
March | 393.97 | 1190.90 | 732.22 | 144.29 | 587.93 | 0.00 | 0.00 |
April | 2015.06 | 941.12 | 1966.08 | 923.87 | 1042.21 | 0.00 | 0.00 |
May | 2066.10 | 804.18 | 2067.27 | 901.50 | 1165.77 | 0.00 | 0.00 |
June | 2193.71 | 624.89 | 2046.22 | 817.24 | 1228.98 | 0.00 | 0.00 |
July | 2342.95 | 575.39 | 2088.79 | 887.73 | 1201.05 | 0.00 | 0.00 |
August | 2287.84 | 621.73 | 1978.67 | 945.39 | 1033.28 | 0.00 | 0.00 |
September | 1982.44 | 810.13 | 1781.86 | 947.51 | 834.35 | 0.00 | 0.00 |
October | 724.71 | 1126.06 | 860.13 | 356.46 | 503.67 | 0.00 | 0.00 |
November | 232.39 | 1385.37 | 448.41 | 152.82 | 295.59 | 0.00 | 0.00 |
December | 148.32 | 1662.44 | 332.33 | 123.55 | 208.77 | 0.00 | 0.00 |
Annual Sum or Average | 1257.34 | 1056.10 | 1291.24 | 554.71 | 736.53 | 0.00 | 0.00 |
Minimum of Months | 148.32 | 575.39 | 332.33 | 123.55 | 208.77 | 0.00 | 0.00 |
Maximum of Months | 2342.95 | 1662.44 | 2088.79 | 947.51 | 1228.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1889.79 | 2115.36 | 1957.67 | 1267.28 | 690.39 | 0.00 | 0.00 |
February | 2376.92 | 2078.11 | 2390.93 | 1458.98 | 931.96 | 0.00 | 0.00 |
March | 1132.68 | 1782.86 | 1478.23 | 430.39 | 1047.84 | 0.00 | 0.00 |
April | 3444.67 | 1542.80 | 3069.68 | 1387.45 | 1682.23 | 0.00 | 0.00 |
May | 2631.54 | 1310.58 | 2538.91 | 826.58 | 1712.33 | 0.00 | 0.00 |
June | 2526.29 | 1017.58 | 2338.88 | 566.14 | 1772.74 | 0.00 | 0.00 |
July | 2956.04 | 949.14 | 2534.14 | 793.59 | 1740.55 | 0.00 | 0.00 |
August | 3679.89 | 1035.26 | 2969.45 | 1335.76 | 1633.69 | 0.00 | 0.00 |
September | 4316.05 | 1302.55 | 3509.10 | 2055.68 | 1453.42 | 0.00 | 0.00 |
October | 2620.49 | 1689.39 | 2410.90 | 1409.06 | 1001.84 | 0.00 | 0.00 |
November | 1658.20 | 2014.42 | 1709.32 | 1039.82 | 669.50 | 0.00 | 0.00 |
December | 1260.86 | 2407.30 | 1354.80 | 868.02 | 486.77 | 0.00 | 0.00 |
Annual Sum or Average | 2537.59 | 1601.36 | 2351.57 | 1115.55 | 1236.02 | 0.00 | 0.00 |
Minimum of Months | 1132.68 | 949.14 | 1354.80 | 430.39 | 486.77 | 0.00 | 0.00 |
Maximum of Months | 4316.05 | 2407.30 | 3509.10 | 2055.68 | 1772.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 239.17 | 1638.87 | 456.94 | 150.97 | 305.96 | 0.00 | 0.00 |
February | 581.07 | 1610.05 | 809.03 | 341.60 | 467.43 | 0.00 | 0.00 |
March | 359.80 | 1375.40 | 731.54 | 139.94 | 591.60 | 0.00 | 0.00 |
April | 1674.19 | 1133.68 | 1726.09 | 685.62 | 1040.47 | 0.00 | 0.00 |
May | 2000.00 | 904.49 | 2025.10 | 823.48 | 1201.63 | 0.00 | 0.00 |
June | 2347.84 | 732.58 | 2186.89 | 900.26 | 1286.63 | 0.00 | 0.00 |
July | 2490.99 | 698.78 | 2227.26 | 982.00 | 1245.25 | 0.00 | 0.00 |
August | 2104.68 | 772.97 | 1870.75 | 809.98 | 1060.77 | 0.00 | 0.00 |
September | 1628.01 | 923.99 | 1500.84 | 673.01 | 827.83 | 0.00 | 0.00 |
October | 641.27 | 1282.91 | 800.64 | 287.91 | 512.73 | 0.00 | 0.00 |
November | 222.05 | 1619.11 | 433.28 | 126.48 | 306.80 | 0.00 | 0.00 |
December | 66.78 | 1991.57 | 245.25 | 51.75 | 193.50 | 0.00 | 0.00 |
Annual Sum or Average | 1198.40 | 1221.86 | 1252.46 | 497.95 | 754.51 | 0.00 | 0.00 |
Minimum of Months | 66.78 | 698.78 | 245.25 | 51.75 | 193.50 | 0.00 | 0.00 |
Maximum of Months | 2490.99 | 1991.57 | 2227.26 | 982.00 | 1286.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 19.77 | 2197.13 | 344.83 | 0.00 | 344.83 | 0.00 | 0.00 |
February | 68.33 | 2053.69 | 538.47 | 0.00 | 538.47 | 0.00 | 0.00 |
March | 226.19 | 1718.03 | 745.15 | 0.00 | 745.15 | 0.00 | 0.00 |
April | 743.92 | 1400.96 | 1213.22 | 5.43 | 1207.79 | 0.00 | 0.00 |
May | 950.06 | 1112.20 | 1516.83 | 73.18 | 1443.65 | 0.00 | 0.00 |
June | 1366.96 | 883.24 | 1676.76 | 105.14 | 1571.62 | 0.00 | 0.00 |
July | 1394.10 | 812.59 | 1590.50 | 90.68 | 1499.82 | 0.00 | 0.00 |
August | 1071.58 | 910.01 | 1250.21 | 19.59 | 1230.63 | 0.00 | 0.00 |
September | 698.10 | 1211.16 | 951.58 | 0.21 | 951.37 | 0.00 | 0.00 |
October | 239.79 | 1599.45 | 609.77 | 0.00 | 609.77 | 0.00 | 0.00 |
November | 33.08 | 1942.28 | 366.38 | 0.00 | 366.38 | 0.00 | 0.00 |
December | 1.03 | 2330.50 | 249.50 | 0.00 | 249.50 | 0.00 | 0.00 |
Annual Sum or Average | 570.28 | 1511.53 | 922.81 | 24.69 | 898.13 | 0.00 | 0.00 |
Minimum of Months | 1.03 | 812.59 | 249.50 | 0.00 | 249.50 | 0.00 | 0.00 |
Maximum of Months | 1394.10 | 2330.50 | 1676.76 | 105.14 | 1571.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 266.67 | 1377.84 | 469.88 | 188.75 | 281.13 | 0.00 | 0.00 |
February | 443.15 | 1303.31 | 700.67 | 258.83 | 441.84 | 0.00 | 0.00 |
March | 429.43 | 1084.86 | 732.22 | 144.29 | 587.93 | 0.00 | 0.00 |
April | 2017.72 | 902.83 | 1966.07 | 923.87 | 1042.20 | 0.00 | 0.00 |
May | 2067.04 | 768.74 | 2067.26 | 901.50 | 1165.77 | 0.00 | 0.00 |
June | 2187.54 | 606.02 | 2046.21 | 817.24 | 1228.98 | 0.00 | 0.00 |
July | 2334.62 | 561.63 | 2088.78 | 887.73 | 1201.05 | 0.00 | 0.00 |
August | 2280.13 | 611.83 | 1978.66 | 945.39 | 1033.28 | 0.00 | 0.00 |
September | 1981.03 | 780.25 | 1781.85 | 947.51 | 834.34 | 0.00 | 0.00 |
October | 745.11 | 1030.65 | 860.12 | 356.46 | 503.67 | 0.00 | 0.00 |
November | 251.94 | 1231.28 | 448.41 | 152.82 | 295.58 | 0.00 | 0.00 |
December | 165.09 | 1478.87 | 332.32 | 123.55 | 208.77 | 0.00 | 0.00 |
Annual Sum or Average | 1267.08 | 976.58 | 1291.24 | 554.71 | 736.53 | 0.00 | 0.00 |
Minimum of Months | 165.09 | 561.63 | 332.32 | 123.55 | 208.77 | 0.00 | 0.00 |
Maximum of Months | 2334.62 | 1478.87 | 2088.78 | 947.51 | 1228.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1902.38 | 2031.57 | 1957.73 | 1267.32 | 690.41 | 0.00 | 0.00 |
February | 2386.12 | 2001.16 | 2391.01 | 1459.02 | 931.98 | 0.00 | 0.00 |
March | 1157.85 | 1681.76 | 1478.28 | 430.41 | 1047.87 | 0.00 | 0.00 |
April | 3442.86 | 1492.67 | 3069.76 | 1387.50 | 1682.27 | 0.00 | 0.00 |
May | 2628.71 | 1274.11 | 2538.98 | 826.61 | 1712.37 | 0.00 | 0.00 |
June | 2526.44 | 986.19 | 2338.94 | 566.16 | 1772.78 | 0.00 | 0.00 |
July | 2957.70 | 919.18 | 2534.20 | 793.61 | 1740.59 | 0.00 | 0.00 |
August | 3675.14 | 1009.23 | 2969.53 | 1335.80 | 1633.72 | 0.00 | 0.00 |
September | 4297.84 | 1283.42 | 3509.20 | 2055.75 | 1453.45 | 0.00 | 0.00 |
October | 2623.08 | 1621.38 | 2410.97 | 1409.10 | 1001.87 | 0.00 | 0.00 |
November | 1672.89 | 1888.25 | 1709.38 | 1039.86 | 669.52 | 0.00 | 0.00 |
December | 1285.45 | 2232.33 | 1354.84 | 868.05 | 486.79 | 0.00 | 0.00 |
Annual Sum or Average | 2542.88 | 1532.61 | 2351.63 | 1115.59 | 1236.05 | 0.00 | 0.00 |
Minimum of Months | 1157.85 | 919.18 | 1354.84 | 430.41 | 486.79 | 0.00 | 0.00 |
Maximum of Months | 4297.84 | 2232.33 | 3509.20 | 2055.75 | 1772.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 263.51 | 1435.11 | 456.94 | 150.97 | 305.96 | 0.00 | 0.00 |
February | 621.97 | 1378.83 | 809.03 | 341.60 | 467.43 | 0.00 | 0.00 |
March | 419.93 | 1133.63 | 731.54 | 139.94 | 591.59 | 0.00 | 0.00 |
April | 1733.13 | 984.26 | 1726.08 | 685.62 | 1040.47 | 0.00 | 0.00 |
May | 2028.33 | 836.87 | 2025.10 | 823.47 | 1201.62 | 0.00 | 0.00 |
June | 2371.75 | 667.75 | 2186.89 | 900.26 | 1286.63 | 0.00 | 0.00 |
July | 2528.49 | 625.02 | 2227.25 | 982.00 | 1245.25 | 0.00 | 0.00 |
August | 2144.26 | 682.39 | 1870.74 | 809.98 | 1060.76 | 0.00 | 0.00 |
September | 1652.88 | 850.82 | 1500.83 | 673.01 | 827.82 | 0.00 | 0.00 |
October | 684.78 | 1090.87 | 800.63 | 287.90 | 512.73 | 0.00 | 0.00 |
November | 253.88 | 1305.46 | 433.28 | 126.48 | 306.80 | 0.00 | 0.00 |
December | 85.08 | 1577.14 | 245.25 | 51.75 | 193.49 | 0.00 | 0.00 |
Annual Sum or Average | 1234.38 | 1045.67 | 1252.45 | 497.95 | 754.50 | 0.00 | 0.00 |
Minimum of Months | 85.08 | 625.02 | 245.25 | 51.75 | 193.49 | 0.00 | 0.00 |
Maximum of Months | 2528.49 | 1577.14 | 2227.25 | 982.00 | 1286.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 33.89 | 1986.50 | 344.83 | 0.00 | 344.83 | 0.00 | 0.00 |
February | 101.33 | 1852.39 | 538.47 | 0.00 | 538.47 | 0.00 | 0.00 |
March | 271.87 | 1554.40 | 745.15 | 0.00 | 745.15 | 0.00 | 0.00 |
April | 788.58 | 1297.07 | 1213.22 | 5.43 | 1207.79 | 0.00 | 0.00 |
May | 1003.00 | 1035.80 | 1516.83 | 73.18 | 1443.65 | 0.00 | 0.00 |
June | 1389.00 | 844.20 | 1676.76 | 105.14 | 1571.62 | 0.00 | 0.00 |
July | 1411.23 | 780.95 | 1590.50 | 90.68 | 1499.82 | 0.00 | 0.00 |
August | 1085.77 | 872.94 | 1250.21 | 19.59 | 1230.63 | 0.00 | 0.00 |
September | 732.28 | 1129.56 | 951.58 | 0.21 | 951.37 | 0.00 | 0.00 |
October | 286.46 | 1420.35 | 609.77 | 0.00 | 609.77 | 0.00 | 0.00 |
November | 52.70 | 1728.98 | 366.38 | 0.00 | 366.38 | 0.00 | 0.00 |
December | 6.67 | 2125.06 | 249.50 | 0.00 | 249.50 | 0.00 | 0.00 |
Annual Sum or Average | 599.40 | 1383.34 | 922.81 | 24.69 | 898.13 | 0.00 | 0.00 |
Minimum of Months | 6.67 | 780.95 | 249.50 | 0.00 | 249.50 | 0.00 | 0.00 |
Maximum of Months | 1411.23 | 2125.06 | 1676.76 | 105.14 | 1571.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 286.56 | 1250.70 | 469.88 | 188.75 | 281.13 | 0.00 | 0.00 |
February | 475.07 | 1182.27 | 700.67 | 258.83 | 441.84 | 0.00 | 0.00 |
March | 463.43 | 990.15 | 732.22 | 144.29 | 587.93 | 0.00 | 0.00 |
April | 2039.80 | 850.83 | 1966.07 | 923.87 | 1042.20 | 0.00 | 0.00 |
May | 2089.64 | 726.97 | 2067.26 | 901.50 | 1165.77 | 0.00 | 0.00 |
June | 2194.32 | 585.22 | 2046.21 | 817.24 | 1228.98 | 0.00 | 0.00 |
July | 2338.06 | 545.59 | 2088.78 | 887.73 | 1201.05 | 0.00 | 0.00 |
August | 2281.90 | 595.31 | 1978.66 | 945.39 | 1033.28 | 0.00 | 0.00 |
September | 1996.13 | 741.96 | 1781.85 | 947.51 | 834.34 | 0.00 | 0.00 |
October | 776.54 | 928.45 | 860.12 | 356.46 | 503.67 | 0.00 | 0.00 |
November | 272.66 | 1105.56 | 448.41 | 152.82 | 295.58 | 0.00 | 0.00 |
December | 178.48 | 1353.59 | 332.32 | 123.55 | 208.77 | 0.00 | 0.00 |
Annual Sum or Average | 1285.59 | 903.36 | 1291.24 | 554.71 | 736.53 | 0.00 | 0.00 |
Minimum of Months | 178.48 | 545.59 | 332.32 | 123.55 | 208.77 | 0.00 | 0.00 |
Maximum of Months | 2338.06 | 1353.59 | 2088.78 | 947.51 | 1228.98 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1953.74 | 1838.92 | 1957.73 | 1267.32 | 690.41 | 0.00 | 0.00 |
February | 2443.24 | 1816.82 | 2391.01 | 1459.02 | 931.98 | 0.00 | 0.00 |
March | 1213.25 | 1527.95 | 1478.28 | 430.41 | 1047.87 | 0.00 | 0.00 |
April | 3472.27 | 1403.64 | 3069.76 | 1387.50 | 1682.27 | 0.00 | 0.00 |
May | 2660.75 | 1196.53 | 2538.98 | 826.61 | 1712.37 | 0.00 | 0.00 |
June | 2540.12 | 945.86 | 2338.94 | 566.16 | 1772.78 | 0.00 | 0.00 |
July | 2966.21 | 886.21 | 2534.20 | 793.61 | 1740.59 | 0.00 | 0.00 |
August | 3678.35 | 976.64 | 2969.53 | 1335.80 | 1633.72 | 0.00 | 0.00 |
September | 4315.48 | 1218.99 | 3509.20 | 2055.75 | 1453.45 | 0.00 | 0.00 |
October | 2666.44 | 1463.18 | 2410.97 | 1409.10 | 1001.87 | 0.00 | 0.00 |
November | 1715.84 | 1691.62 | 1709.38 | 1039.86 | 669.52 | 0.00 | 0.00 |
December | 1319.10 | 2036.83 | 1354.84 | 868.05 | 486.79 | 0.00 | 0.00 |
Annual Sum or Average | 2575.11 | 1414.76 | 2351.63 | 1115.59 | 1236.05 | 0.00 | 0.00 |
Minimum of Months | 1213.25 | 886.21 | 1354.84 | 430.41 | 486.79 | 0.00 | 0.00 |
Maximum of Months | 4315.48 | 2036.83 | 3509.20 | 2055.75 | 1772.78 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 279.37 | 1316.40 | 456.94 | 150.97 | 305.96 | 0.00 | 0.00 |
February | 644.42 | 1270.21 | 809.03 | 341.60 | 467.43 | 0.00 | 0.00 |
March | 446.95 | 1045.23 | 731.54 | 139.94 | 591.59 | 0.00 | 0.00 |
April | 1754.89 | 928.22 | 1726.08 | 685.62 | 1040.47 | 0.00 | 0.00 |
May | 2048.10 | 791.87 | 2025.10 | 823.47 | 1201.62 | 0.00 | 0.00 |
June | 2377.15 | 643.43 | 2186.89 | 900.26 | 1286.63 | 0.00 | 0.00 |
July | 2531.21 | 604.66 | 2227.25 | 982.00 | 1245.25 | 0.00 | 0.00 |
August | 2146.44 | 660.67 | 1870.74 | 809.98 | 1060.76 | 0.00 | 0.00 |
September | 1668.10 | 806.60 | 1500.83 | 673.01 | 827.82 | 0.00 | 0.00 |
October | 709.70 | 995.59 | 800.63 | 287.90 | 512.73 | 0.00 | 0.00 |
November | 268.09 | 1190.31 | 433.28 | 126.48 | 306.80 | 0.00 | 0.00 |
December | 91.97 | 1460.15 | 245.25 | 51.75 | 193.49 | 0.00 | 0.00 |
Annual Sum or Average | 1249.20 | 974.61 | 1252.45 | 497.95 | 754.50 | 0.00 | 0.00 |
Minimum of Months | 91.97 | 604.66 | 245.25 | 51.75 | 193.49 | 0.00 | 0.00 |
Maximum of Months | 2531.21 | 1460.15 | 2227.25 | 982.00 | 1286.63 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 24433905.22 | 0.664446E+10 | 0.923582E+09 | 0.00 | 0.923582E+09 | 0.00 | 0.00 |
February | 86795854.97 | 0.562641E+10 | 0.130264E+10 | 0.00 | 0.130264E+10 | 0.00 | 0.00 |
March | 0.460221E+09 | 0.522990E+10 | 0.199576E+10 | 0.00 | 0.199576E+10 | 0.00 | 0.00 |
April | 0.180224E+10 | 0.397398E+10 | 0.314460E+10 | 14073759.71 | 0.313053E+10 | 0.00 | 0.00 |
May | 0.242735E+10 | 0.318508E+10 | 0.406260E+10 | 0.195999E+09 | 0.386661E+10 | 0.00 | 0.00 |
June | 0.348415E+10 | 0.241546E+10 | 0.434608E+10 | 0.272525E+09 | 0.407356E+10 | 0.00 | 0.00 |
July | 0.364124E+10 | 0.231156E+10 | 0.425991E+10 | 0.242878E+09 | 0.401704E+10 | 0.00 | 0.00 |
August | 0.278483E+10 | 0.260497E+10 | 0.334852E+10 | 52462277.64 | 0.329605E+10 | 0.00 | 0.00 |
September | 0.172881E+10 | 0.335732E+10 | 0.246647E+10 | 545772.20 | 0.246592E+10 | 0.00 | 0.00 |
October | 0.523776E+09 | 0.483143E+10 | 0.163317E+10 | 0.00 | 0.163317E+10 | 0.00 | 0.00 |
November | 38654117.89 | 0.588330E+10 | 0.949638E+09 | 0.00 | 0.949638E+09 | 0.00 | 0.00 |
December | 0.00 | 0.733665E+10 | 0.668258E+09 | 0.00 | 0.668258E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170025E+11 | 0.534005E+11 | 0.291012E+11 | 0.778483E+09 | 0.283228E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.231156E+10 | 0.668258E+09 | 0.00 | 0.668258E+09 | 0.00 | 0.00 |
Maximum of Months | 0.364124E+10 | 0.733665E+10 | 0.434608E+10 | 0.272525E+09 | 0.407356E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.661399E+09 | 0.407896E+10 | 0.125854E+10 | 0.505556E+09 | 0.752980E+09 | 0.00 | 0.00 |
February | 0.100954E+10 | 0.345771E+10 | 0.169508E+10 | 0.626175E+09 | 0.106890E+10 | 0.00 | 0.00 |
March | 0.105521E+10 | 0.318970E+10 | 0.196119E+10 | 0.386478E+09 | 0.157471E+10 | 0.00 | 0.00 |
April | 0.522303E+10 | 0.243939E+10 | 0.509608E+10 | 0.239468E+10 | 0.270140E+10 | 0.00 | 0.00 |
May | 0.553383E+10 | 0.215392E+10 | 0.553698E+10 | 0.241458E+10 | 0.312240E+10 | 0.00 | 0.00 |
June | 0.568611E+10 | 0.161971E+10 | 0.530381E+10 | 0.211829E+10 | 0.318552E+10 | 0.00 | 0.00 |
July | 0.627536E+10 | 0.154113E+10 | 0.559461E+10 | 0.237771E+10 | 0.321690E+10 | 0.00 | 0.00 |
August | 0.612776E+10 | 0.166525E+10 | 0.529967E+10 | 0.253213E+10 | 0.276754E+10 | 0.00 | 0.00 |
September | 0.513850E+10 | 0.209985E+10 | 0.461858E+10 | 0.245595E+10 | 0.216263E+10 | 0.00 | 0.00 |
October | 0.194107E+10 | 0.301605E+10 | 0.230376E+10 | 0.954739E+09 | 0.134902E+10 | 0.00 | 0.00 |
November | 0.602354E+09 | 0.359087E+10 | 0.116228E+10 | 0.396121E+09 | 0.766157E+09 | 0.00 | 0.00 |
December | 0.397255E+09 | 0.445267E+10 | 0.890103E+09 | 0.330928E+09 | 0.559175E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.396514E+11 | 0.333052E+11 | 0.407207E+11 | 0.174933E+11 | 0.232273E+11 | 0.00 | 0.00 |
Minimum of Months | 0.397255E+09 | 0.154113E+10 | 0.890103E+09 | 0.330928E+09 | 0.559175E+09 | 0.00 | 0.00 |
Maximum of Months | 0.627536E+10 | 0.445267E+10 | 0.559461E+10 | 0.253213E+10 | 0.321690E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.506162E+10 | 0.566578E+10 | 0.524342E+10 | 0.339427E+10 | 0.184914E+10 | 0.00 | 0.00 |
February | 0.575024E+10 | 0.502737E+10 | 0.578414E+10 | 0.352956E+10 | 0.225459E+10 | 0.00 | 0.00 |
March | 0.303376E+10 | 0.477522E+10 | 0.395930E+10 | 0.115277E+10 | 0.280654E+10 | 0.00 | 0.00 |
April | 0.892858E+10 | 0.399895E+10 | 0.795661E+10 | 0.359627E+10 | 0.436033E+10 | 0.00 | 0.00 |
May | 0.704832E+10 | 0.351026E+10 | 0.680023E+10 | 0.221392E+10 | 0.458631E+10 | 0.00 | 0.00 |
June | 0.654814E+10 | 0.263757E+10 | 0.606239E+10 | 0.146744E+10 | 0.459495E+10 | 0.00 | 0.00 |
July | 0.791745E+10 | 0.254218E+10 | 0.678743E+10 | 0.212554E+10 | 0.466189E+10 | 0.00 | 0.00 |
August | 0.985621E+10 | 0.277284E+10 | 0.795336E+10 | 0.357770E+10 | 0.437567E+10 | 0.00 | 0.00 |
September | 0.111872E+11 | 0.337622E+10 | 0.909559E+10 | 0.532833E+10 | 0.376726E+10 | 0.00 | 0.00 |
October | 0.701873E+10 | 0.452486E+10 | 0.645734E+10 | 0.377402E+10 | 0.268333E+10 | 0.00 | 0.00 |
November | 0.429806E+10 | 0.522137E+10 | 0.443057E+10 | 0.269522E+10 | 0.173535E+10 | 0.00 | 0.00 |
December | 0.337709E+10 | 0.644770E+10 | 0.362868E+10 | 0.232491E+10 | 0.130377E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.800254E+11 | 0.505003E+11 | 0.741591E+11 | 0.351799E+11 | 0.389791E+11 | 0.00 | 0.00 |
Minimum of Months | 0.303376E+10 | 0.254218E+10 | 0.362868E+10 | 0.115277E+10 | 0.130377E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111872E+11 | 0.644770E+10 | 0.909559E+10 | 0.532833E+10 | 0.466189E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.640595E+09 | 0.438955E+10 | 0.122386E+10 | 0.404370E+09 | 0.819495E+09 | 0.00 | 0.00 |
February | 0.140573E+10 | 0.389504E+10 | 0.195721E+10 | 0.826397E+09 | 0.113081E+10 | 0.00 | 0.00 |
March | 0.963694E+09 | 0.368387E+10 | 0.195935E+10 | 0.374824E+09 | 0.158453E+10 | 0.00 | 0.00 |
April | 0.433951E+10 | 0.293851E+10 | 0.447403E+10 | 0.177712E+10 | 0.269691E+10 | 0.00 | 0.00 |
May | 0.535680E+10 | 0.242260E+10 | 0.542404E+10 | 0.220560E+10 | 0.321844E+10 | 0.00 | 0.00 |
June | 0.608561E+10 | 0.189883E+10 | 0.566843E+10 | 0.233348E+10 | 0.333495E+10 | 0.00 | 0.00 |
July | 0.667186E+10 | 0.187162E+10 | 0.596548E+10 | 0.263020E+10 | 0.333528E+10 | 0.00 | 0.00 |
August | 0.563718E+10 | 0.207033E+10 | 0.501061E+10 | 0.216945E+10 | 0.284116E+10 | 0.00 | 0.00 |
September | 0.421979E+10 | 0.239499E+10 | 0.389017E+10 | 0.174444E+10 | 0.214573E+10 | 0.00 | 0.00 |
October | 0.171757E+10 | 0.343615E+10 | 0.214443E+10 | 0.771127E+09 | 0.137330E+10 | 0.00 | 0.00 |
November | 0.575546E+09 | 0.419673E+10 | 0.112306E+10 | 0.327834E+09 | 0.795222E+09 | 0.00 | 0.00 |
December | 0.178867E+09 | 0.533422E+10 | 0.656872E+09 | 0.138614E+09 | 0.518258E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.377928E+11 | 0.385324E+11 | 0.394975E+11 | 0.157035E+11 | 0.237941E+11 | 0.00 | 0.00 |
Minimum of Months | 0.178867E+09 | 0.187162E+10 | 0.656872E+09 | 0.138614E+09 | 0.518258E+09 | 0.00 | 0.00 |
Maximum of Months | 0.667186E+10 | 0.533422E+10 | 0.596548E+10 | 0.263020E+10 | 0.333528E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 52959337.74 | 0.588478E+10 | 0.923601E+09 | 0.00 | 0.923601E+09 | 0.00 | 0.00 |
February | 0.165310E+09 | 0.496829E+10 | 0.130267E+10 | 0.00 | 0.130267E+10 | 0.00 | 0.00 |
March | 0.605817E+09 | 0.460158E+10 | 0.199581E+10 | 0.00 | 0.199581E+10 | 0.00 | 0.00 |
April | 0.192825E+10 | 0.363128E+10 | 0.314466E+10 | 14074179.42 | 0.313058E+10 | 0.00 | 0.00 |
May | 0.254464E+10 | 0.297893E+10 | 0.406268E+10 | 0.196005E+09 | 0.386668E+10 | 0.00 | 0.00 |
June | 0.354316E+10 | 0.228935E+10 | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.00 | 0.00 |
July | 0.373395E+10 | 0.217643E+10 | 0.425999E+10 | 0.242885E+09 | 0.401711E+10 | 0.00 | 0.00 |
August | 0.287013E+10 | 0.243737E+10 | 0.334857E+10 | 52463842.21 | 0.329611E+10 | 0.00 | 0.00 |
September | 0.180946E+10 | 0.313932E+10 | 0.246651E+10 | 545788.48 | 0.246596E+10 | 0.00 | 0.00 |
October | 0.642247E+09 | 0.428398E+10 | 0.163320E+10 | 0.00 | 0.163320E+10 | 0.00 | 0.00 |
November | 85743155.02 | 0.503439E+10 | 0.949658E+09 | 0.00 | 0.949658E+09 | 0.00 | 0.00 |
December | 2755805.72 | 0.624201E+10 | 0.668272E+09 | 0.00 | 0.668272E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.179844E+11 | 0.476677E+11 | 0.291018E+11 | 0.778506E+09 | 0.283233E+11 | 0.00 | 0.00 |
Minimum of Months | 2755805.72 | 0.217643E+10 | 0.668272E+09 | 0.00 | 0.668272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.373395E+10 | 0.624201E+10 | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.714260E+09 | 0.369041E+10 | 0.125853E+10 | 0.505554E+09 | 0.752977E+09 | 0.00 | 0.00 |
February | 0.107208E+10 | 0.315298E+10 | 0.169507E+10 | 0.626173E+09 | 0.106890E+10 | 0.00 | 0.00 |
March | 0.115017E+10 | 0.290568E+10 | 0.196118E+10 | 0.386477E+09 | 0.157470E+10 | 0.00 | 0.00 |
April | 0.522994E+10 | 0.234014E+10 | 0.509606E+10 | 0.239467E+10 | 0.270139E+10 | 0.00 | 0.00 |
May | 0.553635E+10 | 0.205898E+10 | 0.553696E+10 | 0.241457E+10 | 0.312239E+10 | 0.00 | 0.00 |
June | 0.567010E+10 | 0.157081E+10 | 0.530378E+10 | 0.211828E+10 | 0.318550E+10 | 0.00 | 0.00 |
July | 0.625305E+10 | 0.150428E+10 | 0.559458E+10 | 0.237770E+10 | 0.321689E+10 | 0.00 | 0.00 |
August | 0.610709E+10 | 0.163871E+10 | 0.529965E+10 | 0.253212E+10 | 0.276753E+10 | 0.00 | 0.00 |
September | 0.513483E+10 | 0.202240E+10 | 0.461856E+10 | 0.245594E+10 | 0.216262E+10 | 0.00 | 0.00 |
October | 0.199571E+10 | 0.276050E+10 | 0.230375E+10 | 0.954735E+09 | 0.134902E+10 | 0.00 | 0.00 |
November | 0.653016E+09 | 0.319149E+10 | 0.116227E+10 | 0.396120E+09 | 0.766154E+09 | 0.00 | 0.00 |
December | 0.442165E+09 | 0.396100E+10 | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.399588E+11 | 0.307974E+11 | 0.407205E+11 | 0.174933E+11 | 0.232272E+11 | 0.00 | 0.00 |
Minimum of Months | 0.442165E+09 | 0.150428E+10 | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.00 | 0.00 |
Maximum of Months | 0.625305E+10 | 0.396100E+10 | 0.559458E+10 | 0.253212E+10 | 0.321689E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.509534E+10 | 0.544136E+10 | 0.524358E+10 | 0.339438E+10 | 0.184920E+10 | 0.00 | 0.00 |
February | 0.577249E+10 | 0.484121E+10 | 0.578432E+10 | 0.352967E+10 | 0.225465E+10 | 0.00 | 0.00 |
March | 0.310119E+10 | 0.450441E+10 | 0.395942E+10 | 0.115280E+10 | 0.280661E+10 | 0.00 | 0.00 |
April | 0.892390E+10 | 0.386900E+10 | 0.795683E+10 | 0.359639E+10 | 0.436043E+10 | 0.00 | 0.00 |
May | 0.704074E+10 | 0.341258E+10 | 0.680040E+10 | 0.221399E+10 | 0.458641E+10 | 0.00 | 0.00 |
June | 0.654852E+10 | 0.255621E+10 | 0.606254E+10 | 0.146749E+10 | 0.459505E+10 | 0.00 | 0.00 |
July | 0.792189E+10 | 0.246193E+10 | 0.678760E+10 | 0.212561E+10 | 0.466199E+10 | 0.00 | 0.00 |
August | 0.984350E+10 | 0.270311E+10 | 0.795358E+10 | 0.357781E+10 | 0.437576E+10 | 0.00 | 0.00 |
September | 0.111400E+11 | 0.332662E+10 | 0.909586E+10 | 0.532851E+10 | 0.376735E+10 | 0.00 | 0.00 |
October | 0.702566E+10 | 0.434270E+10 | 0.645754E+10 | 0.377414E+10 | 0.268340E+10 | 0.00 | 0.00 |
November | 0.433612E+10 | 0.489434E+10 | 0.443070E+10 | 0.269531E+10 | 0.173539E+10 | 0.00 | 0.00 |
December | 0.344294E+10 | 0.597907E+10 | 0.362880E+10 | 0.232499E+10 | 0.130381E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.801923E+11 | 0.483325E+11 | 0.741611E+11 | 0.351811E+11 | 0.389801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.310119E+10 | 0.246193E+10 | 0.362880E+10 | 0.115280E+10 | 0.130381E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111400E+11 | 0.597907E+10 | 0.909586E+10 | 0.532851E+10 | 0.466199E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.705772E+09 | 0.384381E+10 | 0.122386E+10 | 0.404368E+09 | 0.819492E+09 | 0.00 | 0.00 |
February | 0.150466E+10 | 0.333567E+10 | 0.195720E+10 | 0.826394E+09 | 0.113081E+10 | 0.00 | 0.00 |
March | 0.112475E+10 | 0.303633E+10 | 0.195935E+10 | 0.374823E+09 | 0.158452E+10 | 0.00 | 0.00 |
April | 0.449228E+10 | 0.255121E+10 | 0.447401E+10 | 0.177712E+10 | 0.269689E+10 | 0.00 | 0.00 |
May | 0.543269E+10 | 0.224148E+10 | 0.542402E+10 | 0.220559E+10 | 0.321842E+10 | 0.00 | 0.00 |
June | 0.614758E+10 | 0.173082E+10 | 0.566841E+10 | 0.233347E+10 | 0.333494E+10 | 0.00 | 0.00 |
July | 0.677230E+10 | 0.167405E+10 | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.00 | 0.00 |
August | 0.574319E+10 | 0.182772E+10 | 0.501059E+10 | 0.216944E+10 | 0.284114E+10 | 0.00 | 0.00 |
September | 0.428427E+10 | 0.220532E+10 | 0.389015E+10 | 0.174443E+10 | 0.214572E+10 | 0.00 | 0.00 |
October | 0.183411E+10 | 0.292178E+10 | 0.214442E+10 | 0.771124E+09 | 0.137330E+10 | 0.00 | 0.00 |
November | 0.658065E+09 | 0.338376E+10 | 0.112305E+10 | 0.327833E+09 | 0.795218E+09 | 0.00 | 0.00 |
December | 0.227876E+09 | 0.422420E+10 | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.389275E+11 | 0.329761E+11 | 0.394974E+11 | 0.157034E+11 | 0.237940E+11 | 0.00 | 0.00 |
Minimum of Months | 0.227876E+09 | 0.167405E+10 | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.00 | 0.00 |
Maximum of Months | 0.677230E+10 | 0.422420E+10 | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 90758862.44 | 0.532064E+10 | 0.923601E+09 | 0.00 | 0.923601E+09 | 0.00 | 0.00 |
February | 0.245126E+09 | 0.448131E+10 | 0.130267E+10 | 0.00 | 0.130267E+10 | 0.00 | 0.00 |
March | 0.728165E+09 | 0.416331E+10 | 0.199581E+10 | 0.00 | 0.199581E+10 | 0.00 | 0.00 |
April | 0.204399E+10 | 0.336201E+10 | 0.314466E+10 | 14074179.42 | 0.313058E+10 | 0.00 | 0.00 |
May | 0.268644E+10 | 0.277428E+10 | 0.406268E+10 | 0.196005E+09 | 0.386668E+10 | 0.00 | 0.00 |
June | 0.360030E+10 | 0.218817E+10 | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.00 | 0.00 |
July | 0.377984E+10 | 0.209169E+10 | 0.425999E+10 | 0.242885E+09 | 0.401711E+10 | 0.00 | 0.00 |
August | 0.290812E+10 | 0.233809E+10 | 0.334857E+10 | 52463842.21 | 0.329611E+10 | 0.00 | 0.00 |
September | 0.189806E+10 | 0.292783E+10 | 0.246651E+10 | 545788.48 | 0.246596E+10 | 0.00 | 0.00 |
October | 0.767256E+09 | 0.380428E+10 | 0.163320E+10 | 0.00 | 0.163320E+10 | 0.00 | 0.00 |
November | 0.136598E+09 | 0.448153E+10 | 0.949658E+09 | 0.00 | 0.949658E+09 | 0.00 | 0.00 |
December | 17873440.33 | 0.569177E+10 | 0.668272E+09 | 0.00 | 0.668272E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.189025E+11 | 0.436249E+11 | 0.291018E+11 | 0.778506E+09 | 0.283233E+11 | 0.00 | 0.00 |
Minimum of Months | 17873440.33 | 0.209169E+10 | 0.668272E+09 | 0.00 | 0.668272E+09 | 0.00 | 0.00 |
Maximum of Months | 0.377984E+10 | 0.569177E+10 | 0.434617E+10 | 0.272533E+09 | 0.407363E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.767512E+09 | 0.334988E+10 | 0.125853E+10 | 0.505554E+09 | 0.752977E+09 | 0.00 | 0.00 |
February | 0.114928E+10 | 0.286015E+10 | 0.169507E+10 | 0.626173E+09 | 0.106890E+10 | 0.00 | 0.00 |
March | 0.124124E+10 | 0.265202E+10 | 0.196118E+10 | 0.386477E+09 | 0.157470E+10 | 0.00 | 0.00 |
April | 0.528715E+10 | 0.220536E+10 | 0.509606E+10 | 0.239467E+10 | 0.270139E+10 | 0.00 | 0.00 |
May | 0.559690E+10 | 0.194712E+10 | 0.553696E+10 | 0.241457E+10 | 0.312239E+10 | 0.00 | 0.00 |
June | 0.568769E+10 | 0.151689E+10 | 0.530378E+10 | 0.211828E+10 | 0.318550E+10 | 0.00 | 0.00 |
July | 0.626226E+10 | 0.146132E+10 | 0.559458E+10 | 0.237770E+10 | 0.321689E+10 | 0.00 | 0.00 |
August | 0.611183E+10 | 0.159448E+10 | 0.529965E+10 | 0.253212E+10 | 0.276753E+10 | 0.00 | 0.00 |
September | 0.517397E+10 | 0.192316E+10 | 0.461856E+10 | 0.245594E+10 | 0.216262E+10 | 0.00 | 0.00 |
October | 0.207989E+10 | 0.248676E+10 | 0.230375E+10 | 0.954735E+09 | 0.134902E+10 | 0.00 | 0.00 |
November | 0.706739E+09 | 0.286562E+10 | 0.116227E+10 | 0.396120E+09 | 0.766154E+09 | 0.00 | 0.00 |
December | 0.478037E+09 | 0.362544E+10 | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.405425E+11 | 0.284882E+11 | 0.407205E+11 | 0.174933E+11 | 0.232272E+11 | 0.00 | 0.00 |
Minimum of Months | 0.478037E+09 | 0.146132E+10 | 0.890099E+09 | 0.330926E+09 | 0.559173E+09 | 0.00 | 0.00 |
Maximum of Months | 0.626226E+10 | 0.362544E+10 | 0.559458E+10 | 0.253212E+10 | 0.321689E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.523289E+10 | 0.492535E+10 | 0.524358E+10 | 0.339438E+10 | 0.184920E+10 | 0.00 | 0.00 |
February | 0.591068E+10 | 0.439525E+10 | 0.578432E+10 | 0.352967E+10 | 0.225465E+10 | 0.00 | 0.00 |
March | 0.324956E+10 | 0.409245E+10 | 0.395942E+10 | 0.115280E+10 | 0.280661E+10 | 0.00 | 0.00 |
April | 0.900013E+10 | 0.363824E+10 | 0.795683E+10 | 0.359639E+10 | 0.436043E+10 | 0.00 | 0.00 |
May | 0.712655E+10 | 0.320479E+10 | 0.680040E+10 | 0.221399E+10 | 0.458641E+10 | 0.00 | 0.00 |
June | 0.658400E+10 | 0.245166E+10 | 0.606254E+10 | 0.146749E+10 | 0.459505E+10 | 0.00 | 0.00 |
July | 0.794468E+10 | 0.237361E+10 | 0.678760E+10 | 0.212561E+10 | 0.466199E+10 | 0.00 | 0.00 |
August | 0.985210E+10 | 0.261584E+10 | 0.795358E+10 | 0.357781E+10 | 0.437576E+10 | 0.00 | 0.00 |
September | 0.111857E+11 | 0.315961E+10 | 0.909586E+10 | 0.532851E+10 | 0.376735E+10 | 0.00 | 0.00 |
October | 0.714180E+10 | 0.391899E+10 | 0.645754E+10 | 0.377414E+10 | 0.268340E+10 | 0.00 | 0.00 |
November | 0.444745E+10 | 0.438467E+10 | 0.443070E+10 | 0.269531E+10 | 0.173539E+10 | 0.00 | 0.00 |
December | 0.353309E+10 | 0.545545E+10 | 0.362880E+10 | 0.232499E+10 | 0.130381E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.812086E+11 | 0.446159E+11 | 0.741611E+11 | 0.351811E+11 | 0.389801E+11 | 0.00 | 0.00 |
Minimum of Months | 0.324956E+10 | 0.237361E+10 | 0.362880E+10 | 0.115280E+10 | 0.130381E+10 | 0.00 | 0.00 |
Maximum of Months | 0.111857E+11 | 0.545545E+10 | 0.909586E+10 | 0.532851E+10 | 0.466199E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.748257E+09 | 0.352584E+10 | 0.122386E+10 | 0.404368E+09 | 0.819492E+09 | 0.00 | 0.00 |
February | 0.155898E+10 | 0.307288E+10 | 0.195720E+10 | 0.826394E+09 | 0.113081E+10 | 0.00 | 0.00 |
March | 0.119711E+10 | 0.279956E+10 | 0.195935E+10 | 0.374823E+09 | 0.158452E+10 | 0.00 | 0.00 |
April | 0.454869E+10 | 0.240595E+10 | 0.447401E+10 | 0.177712E+10 | 0.269689E+10 | 0.00 | 0.00 |
May | 0.548563E+10 | 0.212093E+10 | 0.542402E+10 | 0.220559E+10 | 0.321842E+10 | 0.00 | 0.00 |
June | 0.616156E+10 | 0.166776E+10 | 0.566841E+10 | 0.233347E+10 | 0.333494E+10 | 0.00 | 0.00 |
July | 0.677959E+10 | 0.161951E+10 | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.00 | 0.00 |
August | 0.574902E+10 | 0.176953E+10 | 0.501059E+10 | 0.216944E+10 | 0.284114E+10 | 0.00 | 0.00 |
September | 0.432373E+10 | 0.209070E+10 | 0.389015E+10 | 0.174443E+10 | 0.214572E+10 | 0.00 | 0.00 |
October | 0.190086E+10 | 0.266659E+10 | 0.214442E+10 | 0.771124E+09 | 0.137330E+10 | 0.00 | 0.00 |
November | 0.694895E+09 | 0.308528E+10 | 0.112305E+10 | 0.327833E+09 | 0.795218E+09 | 0.00 | 0.00 |
December | 0.246322E+09 | 0.391087E+10 | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.393946E+11 | 0.307354E+11 | 0.394974E+11 | 0.157034E+11 | 0.237940E+11 | 0.00 | 0.00 |
Minimum of Months | 0.246322E+09 | 0.161951E+10 | 0.656869E+09 | 0.138614E+09 | 0.518256E+09 | 0.00 | 0.00 |
Maximum of Months | 0.677959E+10 | 0.391087E+10 | 0.596546E+10 | 0.263019E+10 | 0.333527E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.397719E+11 | -0.387437E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102813E+10 | 58.98 | 0.00 | 0.00 |
February | 0.363693E+11 | -0.354409E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -928420532.8 | 58.98 | 0.00 | 0.00 |
March | 0.424412E+11 | -0.414118E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102941E+10 | 58.98 | 0.00 | 0.00 |
April | 0.378283E+11 | -0.368378E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990541218.1 | 58.97 | 0.00 | 0.00 |
May | 0.393128E+11 | -0.382868E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102608E+10 | 58.98 | 0.00 | 0.00 |
June | 0.379192E+11 | -0.369261E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -993194248.5 | 58.98 | 0.00 | 0.00 |
July | 0.353935E+11 | -0.343728E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102073E+10 | 58.98 | 0.00 | 0.00 |
August | 0.383634E+11 | -0.373385E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102490E+10 | 58.98 | 0.00 | 0.00 |
September | 0.351161E+11 | -0.341257E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990384862.7 | 58.98 | 0.00 | 0.00 |
October | 0.369795E+11 | -0.359566E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102296E+10 | 58.98 | 0.00 | 0.00 |
November | 0.372675E+11 | -0.362771E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -990444104.5 | 58.98 | 0.00 | 0.00 |
December | 0.381159E+11 | -0.370907E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102527E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.454879E+12 | -0.442808E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120705E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.351161E+11 | -0.414118E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.102941E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.424412E+11 | -0.341257E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -928420532.8 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.65 | 0.61 | 01-JAN-08:50 | 3198.74 | 31.40 | 158.33 | 209.67 | 2839.22 | 37.25 | 190.17 | 176.33 |
February | 217.00 | 0.63 | 0.61 | 01-FEB-11:39 | 4794.36 | 33.06 | 193.50 | 235.33 | 2197.64 | 29.53 | 175.50 | 202.83 |
March | 215.50 | 0.63 | 0.61 | 01-MAR-11:39 | 3577.08 | 30.10 | 180.33 | 299.50 | 937.96 | 20.87 | 136.83 | 246.33 |
April | 359.67 | 0.64 | 0.61 | 01-APR-06:40 | 2083.69 | 18.16 | 0.00 | 347.17 | 1149.72 | 21.13 | 217.67 | 312.17 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1662.98 | 17.70 | 0.00 | 398.67 | 914.21 | 20.67 | 204.50 | 346.17 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:40 | 1621.87 | 18.01 | 0.00 | 399.50 | 883.28 | 20.97 | 200.50 | 351.67 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:30 | 1609.20 | 17.74 | 0.00 | 409.00 | 898.81 | 20.73 | 200.50 | 361.33 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-05:00 | 1855.85 | 17.79 | 0.00 | 370.50 | 1047.13 | 20.77 | 213.17 | 329.00 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2816.87 | 19.91 | 29.50 | 320.00 | 1261.67 | 21.36 | 203.83 | 287.67 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:00 | 6166.96 | 33.83 | 211.67 | 270.83 | 1697.57 | 24.04 | 170.50 | 225.00 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 3773.53 | 32.67 | 148.33 | 201.83 | 3270.59 | 37.16 | 167.33 | 159.17 |
December | 131.67 | 0.63 | 0.61 | 02-DEC-08:39 | 3011.69 | 31.74 | 101.33 | 163.83 | 2743.83 | 38.21 | 128.67 | 117.83 |
Annual Sum or Average | 3515.67 | 0.63 | 2676.46 | 22.81 | 1023.00 | 3625.83 | 1404.48 | 24.00 | 2209.17 | 3115.50 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 1609.20 | 17.70 | 0.00 | 163.83 | 883.28 | 20.67 | 128.67 | 117.83 | |
Maximum of Months | 429.00 | 0.65 | 0.61 | 6166.96 | 33.83 | 211.67 | 409.00 | 3270.59 | 38.21 | 217.67 | 361.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-08:50 | 1118.47 | 18.78 | 63.33 | 191.67 | 706.39 | 20.47 | 59.33 | 110.17 |
February | 217.00 | 0.64 | 0.61 | 01-FEB-11:39 | 1390.37 | 18.88 | 60.83 | 222.67 | 747.20 | 18.33 | 39.50 | 158.83 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1566.81 | 17.46 | 52.33 | 289.50 | 847.32 | 18.56 | 51.83 | 216.83 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:10 | 2819.49 | 16.40 | 51.33 | 354.67 | 1724.01 | 15.39 | 0.00 | 310.00 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 3090.95 | 15.89 | 53.17 | 410.17 | 1374.43 | 15.11 | 0.00 | 353.50 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:49 | 3099.67 | 14.20 | 0.00 | 408.00 | 1398.15 | 15.48 | 0.00 | 365.67 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-04:49 | 3040.11 | 14.02 | 3.67 | 419.83 | 1350.55 | 15.25 | 0.00 | 376.17 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:30 | 2950.78 | 16.08 | 53.00 | 378.33 | 1222.70 | 15.11 | 0.00 | 334.83 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2653.59 | 16.92 | 55.00 | 324.17 | 1526.81 | 15.81 | 5.50 | 286.17 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-06:49 | 2037.75 | 19.14 | 66.00 | 259.00 | 938.28 | 18.51 | 36.83 | 184.67 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 1161.63 | 19.13 | 53.00 | 182.83 | 655.94 | 18.78 | 37.67 | 100.17 |
December | 131.67 | 0.64 | 0.61 | 02-DEC-08:39 | 922.47 | 19.11 | 39.00 | 138.50 | 714.12 | 23.04 | 52.50 | 81.17 |
Annual Sum or Average | 3515.67 | 0.63 | 2446.68 | 16.57 | 550.67 | 3579.33 | 1210.60 | 16.68 | 283.17 | 2878.17 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 922.47 | 14.02 | 0.00 | 138.50 | 655.94 | 15.11 | 0.00 | 81.17 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3099.67 | 19.14 | 66.00 | 419.83 | 1724.01 | 23.04 | 59.33 | 376.17 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.68 | 0.61 | 01-JAN-09:39 | 413.20 | 0.00 | 0.00 | 154.83 | 241.01 | 0.00 | 0.00 | 15.33 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 548.74 | 0.00 | 0.00 | 205.17 | 321.83 | 0.00 | 0.00 | 81.17 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 690.05 | 0.00 | 0.00 | 281.50 | 370.92 | 0.00 | 0.00 | 150.17 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:40 | 898.01 | 0.00 | 0.00 | 353.00 | 535.98 | 0.00 | 0.00 | 302.67 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1073.30 | 0.00 | 0.00 | 418.00 | 614.08 | 0.00 | 0.00 | 377.67 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:00 | 1217.73 | 0.00 | 0.00 | 419.50 | 673.56 | 0.00 | 0.00 | 387.33 |
July | 429.00 | 0.62 | 0.61 | 01-JUL-04:00 | 1125.94 | 0.00 | 0.00 | 430.17 | 659.50 | 0.00 | 0.00 | 397.67 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:49 | 893.13 | 0.00 | 0.00 | 379.33 | 552.36 | 0.00 | 0.00 | 338.67 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 726.81 | 0.00 | 0.00 | 312.00 | 459.66 | 0.00 | 0.00 | 248.67 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:19 | 619.72 | 0.00 | 0.00 | 240.17 | 372.85 | 0.00 | 0.00 | 126.83 |
November | 171.33 | 0.66 | 0.61 | 01-NOV-11:39 | 458.02 | 0.00 | 0.00 | 148.67 | 268.90 | 0.00 | 0.00 | 38.67 |
December | 131.67 | 0.67 | 0.61 | 02-DEC-09:20 | 386.02 | 0.00 | 0.00 | 90.17 | 228.89 | 0.00 | 0.00 | 3.83 |
Annual Sum or Average | 3515.67 | 0.64 | 846.55 | 0.00 | 0.00 | 3432.50 | 495.78 | 0.00 | 0.00 | 2468.67 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 386.02 | 0.00 | 0.00 | 90.17 | 228.89 | 0.00 | 0.00 | 3.83 | |
Maximum of Months | 429.00 | 0.68 | 0.61 | 1217.73 | 0.00 | 0.00 | 430.17 | 673.56 | 0.00 | 0.00 | 397.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-09:39 | 1021.29 | 18.57 | 64.50 | 182.83 | 568.90 | 17.78 | 41.33 | 108.17 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 1431.28 | 16.78 | 39.67 | 218.50 | 848.22 | 17.79 | 35.00 | 151.17 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1477.46 | 17.43 | 53.67 | 288.00 | 822.03 | 17.00 | 34.50 | 216.50 |
April | 359.67 | 0.64 | 0.61 | 01-APR-07:10 | 2887.77 | 17.32 | 73.17 | 340.83 | 1287.12 | 15.28 | 0.00 | 305.33 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2502.74 | 13.71 | 0.00 | 398.33 | 1424.70 | 15.11 | 1.33 | 360.00 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:49 | 3047.04 | 14.10 | 0.00 | 402.33 | 1322.16 | 16.77 | 32.83 | 359.17 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:40 | 3005.81 | 13.75 | 0.00 | 411.83 | 1343.84 | 16.54 | 34.33 | 371.17 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-06:10 | 2580.18 | 14.02 | 8.50 | 367.50 | 1477.63 | 15.30 | 5.50 | 328.67 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 2473.75 | 17.82 | 75.17 | 310.33 | 1408.85 | 17.73 | 49.00 | 269.67 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:30 | 1936.42 | 18.79 | 65.17 | 251.50 | 880.88 | 18.08 | 36.50 | 181.00 |
November | 171.33 | 0.65 | 0.61 | 01-NOV-11:39 | 1135.35 | 18.51 | 50.50 | 173.67 | 597.82 | 17.90 | 32.83 | 102.67 |
December | 131.67 | 0.66 | 0.61 | 02-DEC-09:09 | 772.11 | 16.75 | 30.17 | 125.50 | 426.65 | 17.19 | 20.50 | 59.67 |
Annual Sum or Average | 3515.67 | 0.64 | 2292.46 | 15.93 | 460.50 | 3471.17 | 1159.20 | 16.61 | 323.67 | 2813.17 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 772.11 | 13.71 | 0.00 | 125.50 | 426.65 | 15.11 | 0.00 | 59.67 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3047.04 | 18.79 | 75.17 | 411.83 | 1477.63 | 18.08 | 49.00 | 371.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.65 | 0.61 | 01-JAN-08:50 | 2757.71 | 23.80 | 113.00 | 208.50 | 2830.90 | 34.97 | 176.00 | 175.67 |
February | 217.00 | 0.63 | 0.61 | 01-FEB-11:39 | 4743.61 | 32.20 | 193.17 | 234.00 | 2284.76 | 29.39 | 141.83 | 206.67 |
March | 215.50 | 0.63 | 0.61 | 01-MAR-11:39 | 3522.65 | 28.99 | 179.67 | 298.33 | 961.70 | 16.16 | 3.33 | 248.83 |
April | 359.67 | 0.64 | 0.61 | 01-APR-06:49 | 2045.15 | 12.33 | 0.00 | 345.17 | 1188.37 | 17.12 | 0.00 | 314.33 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1631.63 | 11.98 | 0.00 | 396.50 | 943.82 | 16.72 | 0.00 | 349.50 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:40 | 1589.22 | 12.31 | 0.00 | 397.17 | 910.56 | 17.04 | 0.00 | 353.50 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:30 | 1580.32 | 12.09 | 0.00 | 407.67 | 928.08 | 16.85 | 0.00 | 363.83 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-05:00 | 1949.15 | 12.36 | 5.50 | 368.17 | 1083.17 | 16.78 | 0.00 | 331.33 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 3708.20 | 17.67 | 75.67 | 318.67 | 1306.77 | 17.16 | 0.00 | 288.50 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:00 | 6075.79 | 32.88 | 209.00 | 268.33 | 1738.08 | 19.83 | 32.83 | 226.50 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 3473.86 | 28.16 | 125.17 | 198.67 | 3300.65 | 36.83 | 167.17 | 160.00 |
December | 131.67 | 0.63 | 0.61 | 02-DEC-08:39 | 2066.34 | 18.04 | 46.50 | 160.50 | 2761.30 | 37.35 | 126.17 | 118.83 |
Annual Sum or Average | 3515.67 | 0.63 | 2670.49 | 18.01 | 947.67 | 3601.67 | 1438.28 | 20.59 | 647.33 | 3137.50 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 1580.32 | 11.98 | 0.00 | 160.50 | 910.56 | 16.16 | 0.00 | 118.83 | |
Maximum of Months | 429.00 | 0.65 | 0.61 | 6075.79 | 32.88 | 209.00 | 407.67 | 3300.65 | 37.35 | 176.00 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-08:50 | 1112.14 | 16.83 | 63.00 | 190.17 | 719.41 | 18.74 | 59.33 | 114.00 |
February | 217.00 | 0.64 | 0.61 | 01-FEB-11:39 | 1225.19 | 14.17 | 39.83 | 221.17 | 764.67 | 16.17 | 39.50 | 162.50 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1557.03 | 15.02 | 52.33 | 288.50 | 865.48 | 16.69 | 52.17 | 221.17 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:10 | 2818.30 | 13.58 | 51.33 | 353.17 | 1759.44 | 12.72 | 0.00 | 313.67 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 3083.65 | 13.03 | 53.17 | 409.17 | 1407.89 | 12.65 | 0.00 | 355.83 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:49 | 3084.20 | 10.79 | 0.00 | 406.67 | 1433.23 | 13.05 | 0.00 | 368.33 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-04:49 | 3001.59 | 10.65 | 3.67 | 419.33 | 1386.01 | 12.80 | 0.00 | 379.17 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:30 | 2768.40 | 13.29 | 53.00 | 378.17 | 1257.20 | 12.55 | 0.00 | 337.50 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2656.19 | 14.20 | 55.00 | 322.33 | 1559.51 | 13.14 | 5.50 | 288.67 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-06:49 | 2030.36 | 16.96 | 66.00 | 257.50 | 962.49 | 16.27 | 36.83 | 187.67 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 1154.01 | 17.13 | 53.33 | 181.50 | 670.02 | 16.70 | 37.50 | 103.17 |
December | 131.67 | 0.64 | 0.61 | 02-DEC-08:39 | 914.99 | 16.87 | 39.00 | 137.50 | 719.23 | 20.95 | 50.17 | 82.67 |
Annual Sum or Average | 3515.67 | 0.63 | 2406.58 | 13.68 | 529.67 | 3565.17 | 1239.05 | 14.31 | 281.00 | 2914.33 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 914.99 | 10.65 | 0.00 | 137.50 | 670.02 | 12.55 | 0.00 | 82.67 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3084.20 | 17.13 | 66.00 | 419.33 | 1759.44 | 20.95 | 59.33 | 379.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.68 | 0.61 | 01-JAN-09:50 | 402.25 | 0.00 | 0.00 | 149.67 | 246.45 | 0.00 | 0.00 | 18.00 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 535.57 | 0.00 | 0.00 | 203.00 | 329.76 | 0.00 | 0.00 | 90.67 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 675.04 | 0.00 | 0.00 | 280.17 | 381.02 | 0.00 | 0.00 | 156.67 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:40 | 881.77 | 0.00 | 0.00 | 351.83 | 551.29 | 0.00 | 0.00 | 305.83 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1041.93 | 0.00 | 0.00 | 415.67 | 632.33 | 0.00 | 0.00 | 381.00 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:00 | 1197.03 | 0.00 | 0.00 | 418.67 | 720.68 | 0.00 | 0.00 | 392.17 |
July | 429.00 | 0.62 | 0.61 | 01-JUL-04:00 | 1109.75 | 0.00 | 0.00 | 429.67 | 678.25 | 0.00 | 0.00 | 399.67 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:40 | 891.35 | 0.00 | 0.00 | 381.50 | 568.10 | 0.00 | 0.00 | 341.67 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 712.71 | 0.00 | 0.00 | 309.83 | 472.21 | 0.00 | 0.00 | 253.17 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:19 | 605.66 | 0.00 | 0.00 | 236.33 | 382.30 | 0.00 | 0.00 | 132.67 |
November | 171.33 | 0.66 | 0.61 | 01-NOV-11:39 | 446.20 | 0.00 | 0.00 | 143.17 | 275.11 | 0.00 | 0.00 | 42.00 |
December | 131.67 | 0.68 | 0.61 | 02-DEC-09:20 | 375.43 | 0.00 | 0.00 | 85.67 | 233.80 | 0.00 | 0.00 | 5.50 |
Annual Sum or Average | 3515.67 | 0.64 | 830.97 | 0.00 | 0.00 | 3405.17 | 512.81 | 0.00 | 0.00 | 2519.00 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 375.43 | 0.00 | 0.00 | 85.67 | 233.80 | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 429.00 | 0.68 | 0.61 | 1197.03 | 0.00 | 0.00 | 429.67 | 720.68 | 0.00 | 0.00 | 399.67 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-09:39 | 1013.10 | 16.74 | 64.50 | 181.83 | 581.04 | 15.77 | 41.33 | 111.00 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 1424.19 | 14.25 | 39.67 | 217.67 | 867.99 | 15.60 | 35.00 | 155.50 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1465.73 | 15.04 | 53.67 | 287.83 | 839.71 | 14.86 | 34.50 | 220.33 |
April | 359.67 | 0.64 | 0.61 | 01-APR-07:10 | 2884.46 | 14.87 | 73.17 | 340.50 | 1319.27 | 12.72 | 0.00 | 308.33 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2490.42 | 10.33 | 0.00 | 397.50 | 1457.61 | 12.66 | 1.33 | 362.83 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:49 | 3029.14 | 10.69 | 0.00 | 401.33 | 1357.81 | 14.61 | 32.83 | 362.17 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:40 | 2990.37 | 10.34 | 0.00 | 411.50 | 1379.85 | 14.38 | 34.50 | 374.67 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-06:10 | 2574.87 | 10.78 | 8.50 | 365.83 | 1511.26 | 12.86 | 5.50 | 331.00 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 2474.45 | 15.48 | 75.33 | 309.83 | 1438.95 | 15.61 | 49.00 | 272.00 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:30 | 1926.73 | 16.66 | 65.17 | 251.00 | 903.36 | 15.86 | 36.50 | 184.50 |
November | 171.33 | 0.65 | 0.61 | 01-NOV-11:39 | 1126.86 | 16.44 | 50.50 | 172.67 | 611.43 | 15.73 | 32.83 | 106.17 |
December | 131.67 | 0.66 | 0.61 | 02-DEC-09:09 | 764.71 | 14.46 | 30.17 | 124.17 | 436.88 | 14.87 | 20.50 | 62.00 |
Annual Sum or Average | 3515.67 | 0.64 | 2283.21 | 13.14 | 460.67 | 3461.67 | 1187.16 | 14.35 | 323.83 | 2850.50 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 764.71 | 10.33 | 0.00 | 124.17 | 436.88 | 12.66 | 0.00 | 62.00 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3029.14 | 16.74 | 75.33 | 411.50 | 1511.26 | 15.86 | 49.00 | 374.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.65 | 0.61 | 01-JAN-08:50 | 2756.12 | 23.78 | 113.00 | 208.67 | 2831.69 | 34.96 | 176.00 | 175.83 |
February | 217.00 | 0.63 | 0.61 | 01-FEB-11:39 | 4742.41 | 32.18 | 193.17 | 233.83 | 2286.14 | 29.38 | 141.83 | 206.83 |
March | 215.50 | 0.63 | 0.61 | 01-MAR-11:39 | 3523.09 | 28.97 | 179.67 | 298.33 | 963.24 | 16.14 | 3.33 | 249.00 |
April | 359.67 | 0.64 | 0.61 | 01-APR-06:49 | 2046.10 | 12.29 | 0.00 | 345.17 | 1189.82 | 17.10 | 0.00 | 314.50 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1632.47 | 11.94 | 0.00 | 396.50 | 944.95 | 16.70 | 0.00 | 349.83 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:40 | 1590.09 | 12.27 | 0.00 | 397.17 | 911.66 | 17.02 | 0.00 | 353.50 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:30 | 1581.07 | 12.05 | 0.00 | 407.67 | 929.13 | 16.84 | 0.00 | 363.83 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-05:00 | 1949.94 | 12.32 | 5.50 | 368.33 | 1084.38 | 16.76 | 0.00 | 331.67 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 3708.53 | 17.63 | 75.67 | 318.67 | 1308.18 | 17.14 | 0.00 | 288.67 |
October | 234.00 | 0.63 | 0.61 | 01-OCT-06:00 | 6074.78 | 32.86 | 209.00 | 268.33 | 1739.69 | 19.81 | 32.83 | 226.50 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 3472.02 | 28.14 | 125.17 | 198.67 | 3301.80 | 36.82 | 167.17 | 160.00 |
December | 131.67 | 0.63 | 0.61 | 02-DEC-08:39 | 2064.54 | 18.01 | 46.50 | 160.67 | 2761.98 | 37.34 | 126.17 | 119.00 |
Annual Sum or Average | 3515.67 | 0.63 | 2670.64 | 17.98 | 947.67 | 3602.00 | 1439.51 | 20.57 | 647.33 | 3139.17 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 1581.07 | 11.94 | 0.00 | 160.67 | 911.66 | 16.14 | 0.00 | 119.00 | |
Maximum of Months | 429.00 | 0.65 | 0.61 | 6074.78 | 32.86 | 209.00 | 407.67 | 3301.80 | 37.34 | 176.00 | 363.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-08:50 | 1111.88 | 16.83 | 63.00 | 190.17 | 719.84 | 18.74 | 59.33 | 114.00 |
February | 217.00 | 0.64 | 0.61 | 01-FEB-11:39 | 1224.85 | 14.16 | 39.83 | 221.17 | 765.27 | 16.17 | 39.50 | 162.50 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1557.12 | 15.01 | 52.33 | 288.50 | 866.39 | 16.69 | 52.17 | 221.33 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:10 | 2817.91 | 13.57 | 51.33 | 353.17 | 1760.44 | 12.72 | 0.00 | 313.83 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 3083.66 | 13.01 | 53.17 | 409.00 | 1408.93 | 12.64 | 0.00 | 356.00 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:49 | 3084.25 | 10.77 | 0.00 | 406.67 | 1434.35 | 13.04 | 0.00 | 368.33 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-04:49 | 3001.48 | 10.64 | 3.67 | 419.33 | 1387.04 | 12.79 | 0.00 | 379.67 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:30 | 2768.04 | 13.27 | 53.00 | 378.17 | 1258.11 | 12.54 | 0.00 | 337.67 |
September | 337.67 | 0.63 | 0.61 | 01-SEP-07:40 | 2655.35 | 14.19 | 55.00 | 322.33 | 1560.28 | 13.13 | 5.50 | 288.83 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-06:49 | 2029.86 | 16.95 | 66.00 | 257.83 | 963.19 | 16.27 | 36.83 | 187.83 |
November | 171.33 | 0.64 | 0.61 | 01-NOV-11:39 | 1153.68 | 17.12 | 53.33 | 181.67 | 670.52 | 16.69 | 37.50 | 103.17 |
December | 131.67 | 0.64 | 0.61 | 02-DEC-08:39 | 914.63 | 16.86 | 39.00 | 137.50 | 719.65 | 20.94 | 50.17 | 82.83 |
Annual Sum or Average | 3515.67 | 0.63 | 2406.32 | 13.67 | 529.67 | 3565.50 | 1239.92 | 14.31 | 281.00 | 2916.00 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 914.63 | 10.64 | 0.00 | 137.50 | 670.52 | 12.54 | 0.00 | 82.83 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3084.25 | 17.12 | 66.00 | 419.33 | 1760.44 | 20.94 | 59.33 | 379.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.68 | 0.61 | 01-JAN-09:50 | 402.21 | 0.00 | 0.00 | 149.67 | 246.70 | 0.00 | 0.00 | 18.17 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 535.53 | 0.00 | 0.00 | 203.00 | 330.09 | 0.00 | 0.00 | 90.83 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 675.27 | 0.00 | 0.00 | 280.17 | 381.54 | 0.00 | 0.00 | 156.67 |
April | 359.67 | 0.63 | 0.61 | 01-APR-06:40 | 881.68 | 0.00 | 0.00 | 351.83 | 551.79 | 0.00 | 0.00 | 305.83 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 1041.96 | 0.00 | 0.00 | 415.67 | 632.95 | 0.00 | 0.00 | 381.33 |
June | 410.67 | 0.62 | 0.61 | 01-JUN-04:00 | 1197.13 | 0.00 | 0.00 | 418.67 | 721.39 | 0.00 | 0.00 | 392.17 |
July | 429.00 | 0.62 | 0.61 | 01-JUL-04:00 | 1109.71 | 0.00 | 0.00 | 429.67 | 678.86 | 0.00 | 0.00 | 399.83 |
August | 396.33 | 0.63 | 0.61 | 01-AUG-05:40 | 891.20 | 0.00 | 0.00 | 381.50 | 568.57 | 0.00 | 0.00 | 341.67 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 712.48 | 0.00 | 0.00 | 309.83 | 472.56 | 0.00 | 0.00 | 253.33 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:19 | 605.57 | 0.00 | 0.00 | 236.17 | 382.64 | 0.00 | 0.00 | 133.00 |
November | 171.33 | 0.66 | 0.61 | 01-NOV-11:39 | 446.15 | 0.00 | 0.00 | 143.50 | 275.38 | 0.00 | 0.00 | 42.17 |
December | 131.67 | 0.68 | 0.61 | 02-DEC-09:20 | 375.34 | 0.00 | 0.00 | 85.83 | 234.02 | 0.00 | 0.00 | 5.50 |
Annual Sum or Average | 3515.67 | 0.64 | 830.92 | 0.00 | 0.00 | 3405.50 | 513.29 | 0.00 | 0.00 | 2520.50 | ||
Minimum of Months | 131.67 | 0.62 | 0.61 | 375.34 | 0.00 | 0.00 | 85.83 | 234.02 | 0.00 | 0.00 | 5.50 | |
Maximum of Months | 429.00 | 0.68 | 0.61 | 1197.13 | 0.00 | 0.00 | 429.67 | 721.39 | 0.00 | 0.00 | 399.83 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 195.67 | 0.66 | 0.61 | 01-JAN-09:39 | 1012.79 | 16.73 | 64.50 | 181.83 | 581.50 | 15.76 | 41.33 | 111.33 |
February | 217.00 | 0.65 | 0.61 | 01-FEB-11:39 | 1423.76 | 14.24 | 39.67 | 217.67 | 868.62 | 15.60 | 35.00 | 155.83 |
March | 215.50 | 0.64 | 0.61 | 01-MAR-11:39 | 1465.82 | 15.03 | 53.67 | 287.83 | 840.63 | 14.85 | 34.50 | 220.83 |
April | 359.67 | 0.64 | 0.61 | 01-APR-07:10 | 2884.11 | 14.86 | 73.17 | 340.17 | 1320.27 | 12.71 | 0.00 | 308.33 |
May | 417.17 | 0.63 | 0.61 | 01-MAY-06:40 | 2490.35 | 10.31 | 0.00 | 397.50 | 1458.67 | 12.66 | 1.33 | 363.00 |
June | 410.67 | 0.63 | 0.61 | 01-JUN-05:49 | 3029.12 | 10.68 | 0.00 | 401.33 | 1358.97 | 14.61 | 32.83 | 362.33 |
July | 429.00 | 0.63 | 0.61 | 01-JUL-05:40 | 2990.15 | 10.32 | 0.00 | 411.50 | 1380.90 | 14.38 | 34.50 | 374.83 |
August | 396.33 | 0.64 | 0.61 | 01-AUG-06:10 | 2574.55 | 10.77 | 8.50 | 365.83 | 1512.26 | 12.85 | 5.50 | 331.00 |
September | 337.67 | 0.64 | 0.61 | 01-SEP-07:40 | 2473.87 | 15.47 | 75.33 | 309.83 | 1439.79 | 15.61 | 49.00 | 272.17 |
October | 234.00 | 0.64 | 0.61 | 01-OCT-07:30 | 1926.27 | 16.65 | 65.17 | 251.00 | 904.11 | 15.85 | 36.50 | 184.67 |
November | 171.33 | 0.65 | 0.61 | 01-NOV-11:39 | 1126.56 | 16.43 | 50.50 | 172.67 | 611.95 | 15.72 | 32.83 | 106.50 |
December | 131.67 | 0.66 | 0.61 | 02-DEC-09:09 | 764.47 | 14.45 | 30.17 | 124.17 | 437.28 | 14.87 | 20.50 | 62.00 |
Annual Sum or Average | 3515.67 | 0.64 | 2282.95 | 13.13 | 460.67 | 3461.33 | 1188.05 | 14.34 | 323.83 | 2852.83 | ||
Minimum of Months | 131.67 | 0.63 | 0.61 | 764.47 | 10.31 | 0.00 | 124.17 | 437.28 | 12.66 | 0.00 | 62.00 | |
Maximum of Months | 429.00 | 0.66 | 0.61 | 3029.12 | 16.73 | 75.33 | 411.50 | 1512.26 | 15.85 | 49.00 | 374.83 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.746226E+10 | 28393.65 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.438975E+10 | 23951.42 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.233248E+10 | 16419.50 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.197535E+09 | 13123.87 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.100690E+09 | 8862.36 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 230085.01 | 383.48 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 10092358.08 | 3644.37 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.334349E+09 | 8930.20 | 07-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.193054E+10 | 18424.73 | 29-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.491498E+10 | 21928.07 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.746226E+10 | 28393.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 61060367.60 | 6766.78 | 11-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 61060367.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 61060367.60 | 6766.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113534E+09 | 8531.65 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17946097.65 | 2528.10 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 623738.79 | 377.55 | 04-MAR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9898081.42 | 1064.73 | 29-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 83893947.47 | 4993.46 | 30-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.225896E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.113534E+09 | 8531.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.205074E+09 | 14631.23 | 10-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 52187535.73 | 3199.11 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 9158570.72 | 1258.16 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 109168.13 | 136.26 | 28-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 34191475.94 | 6645.23 | 27-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.151419E+09 | 14416.41 | 26-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.452140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.205074E+09 | 14631.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 2720780.78 | 303.79 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2720780.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2720780.78 | 303.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.120930E+12 | 312463.13 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.812713E+11 | 264335.58 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.601121E+11 | 194334.60 | 08-MAR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.913200E+10 | 162173.95 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.323323E+10 | 106954.58 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 67555301.43 | 27642.02 | 07-JUN-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.446347E+09 | 62889.10 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.103323E+11 | 110495.83 | 06-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.511746E+11 | 215816.06 | 29-NOV-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.117543E+12 | 249650.35 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.454242E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.120930E+12 | 312463.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.211286E+09 | 104163.67 | 02-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.211286E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.211286E+09 | 104163.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.180846E+11 | 100705.04 | 23-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112622E+11 | 104123.58 | 24-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.484077E+10 | 100491.24 | 06-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189217E+09 | 19036.21 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33120513.96 | 81089.36 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.166817E+10 | 100108.09 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.952654E+10 | 105409.23 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.245789E+11 | 100906.60 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701834E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.245789E+11 | 105409.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.146400E+11 | 135535.49 | 11-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.943148E+10 | 134665.87 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.527546E+10 | 132047.50 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 96623825.85 | 19172.91 | 11-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 22423332.71 | 65852.10 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.212585E+10 | 90325.31 | 21-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.893369E+10 | 133949.49 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.212359E+11 | 134575.55 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.617615E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.212359E+11 | 135535.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.113200E+11 | 197362.66 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.642512E+10 | 196574.21 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.444461E+10 | 192763.33 | 06-MAR-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128995E+09 | 15726.39 | 01-APR-05:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181268E+09 | 108194.94 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149802E+10 | 95419.35 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.650296E+10 | 195472.58 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.209954E+11 | 196066.06 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.514963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.209954E+11 | 197362.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112741E+11 | 131019.57 | 11-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.593968E+10 | 130475.91 | 17-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.304405E+10 | 108182.55 | 04-MAR-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 53778180.38 | 12679.67 | 01-APR-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 95847878.40 | 55125.19 | 05-MAY-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.134664E+10 | 45847.86 | 28-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.627835E+10 | 129741.18 | 29-NOV-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166304E+11 | 130136.80 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.446629E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.166304E+11 | 131019.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151371E+11 | 35480.99 | 10-JAN-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.112093E+11 | 31312.72 | 17-FEB-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.895047E+10 | 23773.93 | 08-MAR-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187569E+10 | 20488.34 | 08-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.783180E+09 | 14646.14 | 06-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 22323279.94 | 5286.81 | 08-JUN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 111448.93 | 185.75 | 05-JUL-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 839693.91 | 1404.84 | 24-AUG-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138544E+09 | 9677.03 | 21-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.221394E+10 | 15242.40 | 23-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.779459E+10 | 25746.71 | 29-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147872E+11 | 28390.99 | 29-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.629133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 111448.93 | 185.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.151371E+11 | 35480.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.456311E+10 | 73160.42 | 02-JAN-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.270482E+10 | 73351.11 | 13-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.127094E+10 | 73035.46 | 13-MAR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12727566.73 | 3627.68 | 03-APR-05:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.485976E+09 | 72039.27 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229297E+10 | 73279.53 | 20-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.567620E+10 | 73174.81 | 18-DEC-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.567620E+10 | 73351.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.564343E+10 | 11285.82 | 23-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.423801E+10 | 11305.83 | 07-FEB-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.293428E+10 | 11276.13 | 07-MAR-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.563622E+09 | 11184.42 | 11-APR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.331965E+09 | 11216.69 | 05-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7632812.67 | 9580.63 | 08-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 1811614.65 | 2340.31 | 31-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141120E+09 | 11197.82 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175020E+10 | 11271.79 | 30-OCT-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.392242E+10 | 11289.03 | 24-NOV-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.662439E+10 | 11288.43 | 05-DEC-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.261589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.662439E+10 | 11305.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376827E+10 | 15753.52 | 10-JAN-06:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.276932E+10 | 15698.12 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.210042E+10 | 15480.16 | 15-MAR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.241539E+09 | 13613.30 | 08-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150309E+09 | 15254.86 | 02-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 3189597.23 | 3039.37 | 07-JUN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 71072.65 | 473.82 | 31-JUL-05:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 48047793.50 | 5062.83 | 18-SEP-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120044E+10 | 15327.90 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.277972E+10 | 15551.47 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.462926E+10 | 15636.39 | 27-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.462926E+10 | 15753.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.397773E+10 | 23779.38 | 11-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.290420E+10 | 23734.20 | 17-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.264118E+10 | 23387.76 | 15-MAR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.448560E+09 | 19963.51 | 24-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.424016E+09 | 23048.71 | 05-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 34455697.46 | 18033.15 | 08-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 8559259.63 | 1818.58 | 01-JUL-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59851413.74 | 4823.35 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.137227E+10 | 23174.72 | 10-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304482E+10 | 23512.55 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.562776E+10 | 23638.00 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.562776E+10 | 23779.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.319978E+10 | 16318.07 | 11-JAN-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.214243E+10 | 16220.13 | 17-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161098E+10 | 16009.49 | 16-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.245235E+09 | 11292.31 | 01-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.213083E+09 | 15805.99 | 05-MAY-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 6307352.75 | 1582.38 | 08-JUN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 3593861.38 | 865.57 | 01-JUL-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 59824297.74 | 6583.27 | 07-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.100380E+10 | 15740.12 | 23-OCT-04:11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.223789E+10 | 16127.08 | 20-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.383410E+10 | 16215.54 | 30-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.145570E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.383410E+10 | 16318.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 897.69 | 897.69 | 0.78 | 30-JAN-06:13 | 0.78 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 2861.97 | 2861.97 | 1.05 | 20-MAR-04:50 | 1.05 | 0.00 |
April | 0.00 | 0.00 | 0.415575E+10 | 0.415001E+10 | 74165.38 | 30-APR-15:02 | 74165.38 | 0.00 |
May | 0.00 | 0.00 | 0.513317E+10 | 0.513317E+10 | 90113.46 | 22-MAY-15:00 | 90113.46 | 0.06 |
June | 0.00 | 0.00 | 0.170406E+11 | 0.166153E+11 | 116127.94 | 13-JUN-16:00 | 104958.34 | 0.21 |
July | 0.00 | 0.00 | 0.288682E+11 | 0.287131E+11 | 109903.95 | 21-JUL-15:20 | 109903.95 | 0.37 |
August | 0.00 | 0.00 | 0.383842E+11 | 0.379862E+11 | 114802.59 | 14-AUG-15:00 | 114802.59 | 0.45 |
September | 0.00 | 0.00 | 0.176532E+11 | 0.175849E+11 | 81151.75 | 13-SEP-14:20 | 81151.75 | 0.21 |
October | 0.00 | 0.00 | 0.929994E+09 | 0.929994E+09 | 22732.22 | 11-OCT-15:00 | 22732.22 | 0.00 |
November | 0.00 | 0.00 | 13330363.93 | 13330363.93 | 7941.22 | 24-NOV-12:00 | 7941.22 | 0.00 |
December | 0.00 | 0.00 | 1589.79 | 1589.79 | 0.94 | 26-DEC-06:13 | 0.94 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.112178E+12 | 0.111126E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.383842E+11 | 0.379862E+11 | 116127.94 | 114802.59 | 0.45 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 57669.71 | 57669.71 | 3.35 | 02-JAN-05:27 | 3.35 | 0.01 |
February | 0.00 | 0.00 | 84401.45 | 84401.45 | 1.41 | 13-FEB-06:01 | 1.41 | 0.02 |
March | 0.00 | 0.00 | 104418.45 | 104418.45 | 4.24 | 27-MAR-05:02 | 4.24 | 0.01 |
April | 0.00 | 0.00 | 0.331621E+11 | 0.331410E+11 | 715598.85 | 30-APR-14:51 | 715598.85 | 0.00 |
May | 0.00 | 0.00 | 0.422362E+11 | 0.422362E+11 | 755056.80 | 22-MAY-15:00 | 755056.80 | 0.06 |
June | 0.00 | 0.00 | 0.137546E+12 | 0.134450E+12 | 1043876.95 | 13-JUN-16:00 | 926282.52 | 0.20 |
July | 0.00 | 0.00 | 0.223227E+12 | 0.222704E+12 | 967036.22 | 21-JUL-15:40 | 967036.22 | 0.35 |
August | 0.00 | 0.00 | 0.282184E+12 | 0.280695E+12 | 907428.57 | 14-AUG-15:50 | 907428.57 | 0.44 |
September | 0.00 | 0.00 | 0.150846E+12 | 0.149723E+12 | 754057.27 | 13-SEP-14:40 | 754057.27 | 0.22 |
October | 0.00 | 0.00 | 0.714757E+10 | 0.714757E+10 | 191453.87 | 07-OCT-15:00 | 191453.87 | 0.01 |
November | 0.00 | 0.00 | 47130665.60 | 47130665.60 | 34976.39 | 24-NOV-12:00 | 34976.39 | 0.02 |
December | 0.00 | 0.00 | 47554.73 | 47554.73 | 2.35 | 26-DEC-06:02 | 2.35 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.876395E+12 | 0.870145E+12 | 0.11 | |||
Minimum of Months | 0.00 | 0.00 | 47554.73 | 47554.73 | 1.41 | 1.41 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.282184E+12 | 0.280695E+12 | 1043876.95 | 967036.22 | 0.44 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 27.89 | 27.89 | 0.33 | 11-JAN-04:09 | 0.33 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 182.78 | 182.78 | 0.30 | 18-MAR-12:40 | 0.30 | 0.00 |
April | 0.00 | 0.00 | 0.326169E+10 | 0.326169E+10 | 71618.80 | 30-APR-15:12 | 71618.80 | 0.00 |
May | 0.00 | 0.00 | 0.441918E+10 | 0.441918E+10 | 85737.35 | 22-MAY-15:00 | 85737.35 | 0.06 |
June | 0.00 | 0.00 | 0.146872E+11 | 0.143366E+11 | 126614.41 | 13-JUN-16:00 | 113096.29 | 0.19 |
July | 0.00 | 0.00 | 0.232846E+11 | 0.232266E+11 | 115771.07 | 21-JUL-15:40 | 115771.07 | 0.34 |
August | 0.00 | 0.00 | 0.275827E+11 | 0.274739E+11 | 106144.72 | 14-AUG-16:00 | 106144.72 | 0.43 |
September | 0.00 | 0.00 | 0.137438E+11 | 0.136853E+11 | 78646.76 | 13-SEP-15:20 | 78646.76 | 0.20 |
October | 0.00 | 0.00 | 0.531325E+09 | 0.531325E+09 | 18047.51 | 07-OCT-15:00 | 18047.51 | 0.00 |
November | 0.00 | 0.00 | 4474093.86 | 4474093.86 | 3328.76 | 24-NOV-12:00 | 3328.76 | 0.00 |
December | 0.00 | 0.00 | 21497.12 | 21497.12 | 241.36 | 26-DEC-04:09 | 241.36 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.875150E+11 | 0.869391E+11 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.275827E+11 | 0.274739E+11 | 126614.41 | 115771.07 | 0.43 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 18311.87 | 18311.87 | 27.00 | 20-JAN-21:20 | 27.00 | 0.00 |
February | 0.00 | 0.00 | 4482.34 | 4482.34 | 7.47 | 15-FEB-21:20 | 7.47 | 0.00 |
March | 0.00 | 0.00 | 843054.49 | 383024.99 | 5620.36 | 18-MAR-05:03 | 2553.50 | 0.00 |
April | 0.00 | 0.00 | 0.654900E+09 | 0.654900E+09 | 25723.73 | 28-APR-15:00 | 25723.73 | 0.00 |
May | 0.00 | 0.00 | 0.207754E+10 | 0.207754E+10 | 53700.89 | 22-MAY-15:00 | 53700.89 | 0.04 |
June | 0.00 | 0.00 | 0.752776E+10 | 0.749062E+10 | 56417.37 | 12-JUN-15:00 | 56417.37 | 0.11 |
July | 0.00 | 0.00 | 0.123686E+11 | 0.122859E+11 | 62464.96 | 10-JUL-11:00 | 62464.96 | 0.19 |
August | 0.00 | 0.00 | 0.161247E+11 | 0.160920E+11 | 61583.57 | 14-AUG-16:00 | 61583.57 | 0.30 |
September | 0.00 | 0.00 | 0.783205E+10 | 0.780943E+10 | 46424.50 | 25-SEP-13:00 | 46424.50 | 0.12 |
October | 0.00 | 0.00 | 0.128931E+09 | 0.115451E+09 | 20411.63 | 20-OCT-05:03 | 8763.46 | 0.00 |
November | 0.00 | 0.00 | 14806520.58 | 13679810.48 | 11822.17 | 15-NOV-05:02 | 11822.17 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.467301E+11 | 0.465400E+11 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.161247E+11 | 0.160920E+11 | 62464.96 | 62464.96 | 0.30 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.320555E+12 | 0.320536E+12 | 124195.99 | 19-JAN-22:05 | 124195.99 | 0.00 |
February | 0.00 | 0.00 | 0.510557E+12 | 0.510545E+12 | 215702.20 | 23-FEB-22:03 | 215702.20 | 0.00 |
March | 0.00 | 0.00 | 0.812015E+12 | 0.812013E+12 | 394133.95 | 31-MAR-24:00 | 394133.95 | 0.00 |
April | 0.00 | 0.00 | 0.102694E+13 | 0.102694E+13 | 408594.93 | 30-APR-19:43 | 408594.93 | 0.00 |
May | 0.00 | 0.00 | 0.327495E+12 | 0.326988E+12 | 211350.74 | 31-MAY-24:00 | 211350.74 | 0.00 |
June | 0.00 | 0.00 | 0.557432E+12 | 0.555129E+12 | 302736.20 | 30-JUN-24:00 | 302736.20 | 0.00 |
July | 0.00 | 0.00 | 0.824304E+12 | 0.821452E+12 | 395434.33 | 31-JUL-24:00 | 395434.33 | 0.00 |
August | 0.00 | 0.00 | 0.106938E+13 | 0.106667E+13 | 405437.90 | 17-AUG-15:30 | 400982.04 | 0.00 |
September | 0.00 | 0.00 | 0.322016E+12 | 0.320101E+12 | 211045.17 | 30-SEP-24:00 | 211045.17 | 0.00 |
October | 0.00 | 0.00 | 0.572047E+12 | 0.571483E+12 | 302901.56 | 31-OCT-24:00 | 302901.56 | 0.00 |
November | 0.00 | 0.00 | 0.788612E+12 | 0.788295E+12 | 307962.20 | 03-NOV-21:03 | 307962.20 | 0.00 |
December | 0.00 | 0.00 | 0.105783E+13 | 0.105783E+13 | 399659.45 | 26-DEC-22:03 | 399659.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.818918E+13 | 0.817798E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.320555E+12 | 0.320101E+12 | 124195.99 | 124195.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.106938E+13 | 0.106667E+13 | 408594.93 | 408594.93 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.414230E+10 | 0.414077E+10 | 2236.33 | 01-JAN-16:10 | 2230.62 | 0.00 |
February | 0.00 | 0.00 | 0.867132E+10 | 0.867004E+10 | 4353.84 | 19-FEB-17:00 | 4353.84 | 0.00 |
March | 0.00 | 0.00 | 0.150169E+11 | 0.150166E+11 | 7585.15 | 31-MAR-24:00 | 7585.15 | 0.00 |
April | 0.00 | 0.00 | 0.199500E+11 | 0.199497E+11 | 8693.44 | 30-APR-19:03 | 8693.44 | 0.00 |
May | 0.00 | 0.00 | 0.534160E+10 | 0.532084E+10 | 3925.58 | 31-MAY-24:00 | 3925.58 | 0.00 |
June | 0.00 | 0.00 | 0.104661E+11 | 0.103763E+11 | 5761.52 | 30-JUN-24:00 | 5761.52 | 0.00 |
July | 0.00 | 0.00 | 0.160433E+11 | 0.159326E+11 | 7820.85 | 31-JUL-24:00 | 7820.85 | 0.00 |
August | 0.00 | 0.00 | 0.210372E+11 | 0.209211E+11 | 8667.03 | 13-AUG-18:05 | 8655.14 | 0.00 |
September | 0.00 | 0.00 | 0.537767E+10 | 0.530876E+10 | 3811.18 | 30-SEP-24:00 | 3811.18 | 0.00 |
October | 0.00 | 0.00 | 0.101987E+11 | 0.101719E+11 | 5645.54 | 31-OCT-24:00 | 5645.54 | 0.00 |
November | 0.00 | 0.00 | 0.145499E+11 | 0.145339E+11 | 6095.85 | 19-NOV-16:00 | 6095.85 | 0.00 |
December | 0.00 | 0.00 | 0.198217E+11 | 0.198216E+11 | 7948.76 | 25-DEC-15:15 | 7948.76 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.150617E+12 | 0.150164E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.414230E+10 | 0.414077E+10 | 2236.33 | 2230.62 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.210372E+11 | 0.209211E+11 | 8693.44 | 8693.44 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.208188E+11 | 0.208040E+11 | 18461.08 | 19-JAN-16:20 | 18461.08 | 0.00 |
February | 0.00 | 0.00 | 0.667636E+11 | 0.667503E+11 | 38143.00 | 27-FEB-17:00 | 38143.00 | 0.00 |
March | 0.00 | 0.00 | 0.127179E+12 | 0.127175E+12 | 67889.95 | 31-MAR-23:50 | 67889.95 | 0.00 |
April | 0.00 | 0.00 | 0.183160E+12 | 0.183156E+12 | 82549.11 | 30-APR-18:00 | 82549.11 | 0.00 |
May | 0.00 | 0.00 | 0.436084E+11 | 0.434045E+11 | 35930.93 | 31-MAY-24:00 | 35930.93 | 0.00 |
June | 0.00 | 0.00 | 0.953459E+11 | 0.944592E+11 | 52388.58 | 30-JUN-24:00 | 52388.58 | 0.00 |
July | 0.00 | 0.00 | 0.149186E+12 | 0.148089E+12 | 73454.41 | 31-JUL-24:00 | 73454.41 | 0.00 |
August | 0.00 | 0.00 | 0.197602E+12 | 0.196445E+12 | 80547.58 | 13-AUG-18:05 | 80427.48 | 0.00 |
September | 0.00 | 0.00 | 0.450086E+11 | 0.443428E+11 | 33841.29 | 30-SEP-23:40 | 33841.29 | 0.00 |
October | 0.00 | 0.00 | 0.841563E+11 | 0.838912E+11 | 48626.34 | 31-OCT-24:00 | 48626.34 | 0.00 |
November | 0.00 | 0.00 | 0.120480E+12 | 0.120320E+12 | 55278.90 | 10-NOV-16:00 | 55089.55 | 0.00 |
December | 0.00 | 0.00 | 0.164223E+12 | 0.164222E+12 | 69394.81 | 21-DEC-15:20 | 69394.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129753E+13 | 0.129306E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.208188E+11 | 0.208040E+11 | 18461.08 | 18461.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.197602E+12 | 0.196445E+12 | 82549.11 | 82549.11 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.551204E+09 | 0.550314E+09 | 1666.78 | 19-JAN-16:30 | 1666.78 | 0.00 |
February | 0.00 | 0.00 | 0.481915E+10 | 0.481791E+10 | 3581.77 | 09-FEB-16:50 | 3581.77 | 0.00 |
March | 0.00 | 0.00 | 0.110243E+11 | 0.110240E+11 | 6252.96 | 31-MAR-23:20 | 6252.96 | 0.00 |
April | 0.00 | 0.00 | 0.174259E+11 | 0.174255E+11 | 8374.73 | 30-APR-18:10 | 8374.73 | 0.00 |
May | 0.00 | 0.00 | 0.356971E+10 | 0.354952E+10 | 3429.53 | 31-MAY-23:20 | 3429.53 | 0.00 |
June | 0.00 | 0.00 | 0.915979E+10 | 0.907140E+10 | 4980.33 | 30-JUN-23:20 | 4980.33 | 0.00 |
July | 0.00 | 0.00 | 0.146040E+11 | 0.144945E+11 | 7198.88 | 31-JUL-23:30 | 7198.88 | 0.00 |
August | 0.00 | 0.00 | 0.194572E+11 | 0.193418E+11 | 8100.41 | 13-AUG-18:05 | 8088.49 | 0.00 |
September | 0.00 | 0.00 | 0.381872E+10 | 0.375352E+10 | 2821.90 | 30-SEP-23:20 | 2821.90 | 0.00 |
October | 0.00 | 0.00 | 0.682216E+10 | 0.679645E+10 | 4262.70 | 31-OCT-23:20 | 4262.70 | 0.00 |
November | 0.00 | 0.00 | 0.101676E+11 | 0.101520E+11 | 5415.11 | 10-NOV-16:10 | 5393.21 | 0.00 |
December | 0.00 | 0.00 | 0.143606E+11 | 0.143605E+11 | 6648.41 | 21-DEC-15:20 | 6648.41 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115780E+12 | 0.115337E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.551204E+09 | 0.550314E+09 | 1666.78 | 1666.78 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.194572E+11 | 0.193418E+11 | 8374.73 | 8374.73 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 81934.32 | 963684.60 | 04-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 59546.47 | 971409.87 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 36986.52 | 950624.00 | 07-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5058.84 | 227819.94 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 2066.25 | 557222.80 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 54.73 | 58067.88 | 08-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 4.85 | 2379.94 | 31-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.30 | 1354.75 | 24-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 347.44 | 85336.11 | 21-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 9413.42 | 593202.32 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 40878.95 | 1023927.91 | 20-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 91887.96 | 1004155.81 | 18-DEC-05:01 |
Annual Sum or Average | 0.00 | 27256.45 | ||||
Minimum of Months | 0.00 | 0.00 | 0.30 | 1354.75 | ||
Maximum of Months | 0.00 | 0.00 | 91887.96 | 1023927.91 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 626.61 | 19702.05 | 10-JAN-06:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1121.34 | 19702.05 | 28-FEB-07:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1176.74 | 19702.06 | 29-MAR-05:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 31778.60 | 1056398.22 | 28-APR-15:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 37041.87 | 1080154.56 | 22-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 108126.05 | 1355945.39 | 13-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 182366.68 | 1256354.78 | 21-JUL-15:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 240966.67 | 1197829.62 | 14-AUG-15:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 126020.47 | 1077531.93 | 12-SEP-13:50 | 0.76 | 9878.61 | 05-SEP-04:10 |
October | 7630.86 | 472452.34 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 927.77 | 91875.43 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 538.70 | 19758.55 | 26-DEC-04:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 61966.51 | 0.06 | ||||
Minimum of Months | 538.70 | 19702.05 | 0.00 | 0.00 | ||
Maximum of Months | 240966.67 | 1355945.39 | 0.76 | 9878.61 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 85.78 | 18-MAR-05:03 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19955.48 | 1337736.41 | 30-APR-16:11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28204.70 | 1186325.93 | 22-MAY-15:50 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 88994.19 | 1353311.58 | 13-JUN-16:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 141256.00 | 1248330.08 | 21-JUL-15:40 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 185460.46 | 1259326.47 | 21-AUG-12:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 98835.34 | 1216458.78 | 10-SEP-15:02 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4206.56 | 281651.78 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 62.24 | 78324.37 | 09-NOV-05:03 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.02 | 169.52 | 26-DEC-04:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 47584.60 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 185460.46 | 1353311.58 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 165294.10 | 179522.00 | 19-JAN-16:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 307389.37 | 325084.79 | 19-FEB-17:07 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 449783.20 | 590949.06 | 31-MAR-24:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 620517.52 | 1212767.53 | 30-APR-18:11 | 0.00 | 0.00 | 01-APR-00:10 |
May | 186999.87 | 568677.68 | 22-MAY-15:00 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 361735.59 | 946751.97 | 13-JUN-17:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 561941.73 | 1327823.54 | 22-JUL-18:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 759096.18 | 1366260.11 | 14-AUG-17:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 208581.96 | 525987.58 | 13-SEP-16:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 316773.24 | 491635.95 | 07-OCT-15:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 449137.46 | 535170.02 | 24-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 582478.85 | 593094.22 | 22-DEC-22:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 415067.01 | 0.00 | ||||
Minimum of Months | 165294.10 | 179522.00 | 0.00 | 0.00 | ||
Maximum of Months | 759096.18 | 1366260.11 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 15877.36 | 53230.73 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16061.21 | 53332.60 | 23-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 16868.46 | 53225.84 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15619.38 | 52454.45 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 15704.10 | 51316.79 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15653.39 | 49881.74 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 14246.11 | 48626.18 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 15346.83 | 47974.83 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 14579.90 | 48622.30 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14840.43 | 49895.75 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15411.30 | 51274.55 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15262.49 | 52483.21 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 15452.47 | ||||
Minimum of Months | 0.00 | 0.00 | 14246.11 | 47974.83 | ||
Maximum of Months | 0.00 | 0.00 | 16868.46 | 53332.60 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15.35 | 17889.79 | 26-JAN-06:50 | 780.35 | 82428.11 | 07-JAN-06:30 |
February | 33.99 | 13905.56 | 02-FEB-06:02 | 1444.30 | 87929.01 | 06-FEB-06:50 |
March | 30.30 | 10455.00 | 24-MAR-16:15 | 1709.18 | 96701.18 | 14-MAR-05:02 |
April | 19272.57 | 1781260.18 | 28-APR-15:00 | 933.76 | 88847.28 | 03-APR-06:00 |
May | 26169.01 | 1712992.73 | 22-MAY-15:00 | 528.25 | 72639.50 | 05-MAY-05:40 |
June | 91996.36 | 2063221.35 | 13-JUN-16:00 | 435.48 | 71770.02 | 08-JUN-06:00 |
July | 137862.41 | 1881186.21 | 21-JUL-13:30 | 667.23 | 66739.09 | 31-JUL-05:30 |
August | 171520.60 | 1827192.31 | 28-AUG-15:30 | 483.42 | 59332.75 | 28-AUG-05:40 |
September | 94068.25 | 1720693.47 | 13-SEP-13:00 | 775.30 | 72788.16 | 20-SEP-06:00 |
October | 4105.41 | 282079.79 | 07-OCT-15:00 | 648.83 | 81565.79 | 19-OCT-05:50 |
November | 28.60 | 16540.62 | 03-NOV-11:00 | 1039.73 | 109276.32 | 17-NOV-06:50 |
December | 10.03 | 13408.43 | 08-DEC-05:53 | 664.86 | 104828.44 | 04-DEC-07:00 |
Annual Sum or Average | 45734.33 | 838.12 | ||||
Minimum of Months | 10.03 | 10455.00 | 435.48 | 59332.75 | ||
Maximum of Months | 171520.60 | 2063221.35 | 1709.18 | 109276.32 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.136582E+11 | 0.80 | 8957.95 | 01-JAN-00:20 | 1.41 |
February | 0.120368E+11 | 0.78 | 8957.95 | 01-FEB-05:02 | 1.40 |
March | 0.142364E+11 | 0.83 | 8957.95 | 01-MAR-05:02 | 1.40 |
April | 0.134159E+11 | 0.81 | 8957.95 | 01-APR-04:03 | 1.41 |
May | 0.140246E+11 | 0.82 | 8957.95 | 01-MAY-01:55 | 1.40 |
June | 0.140550E+11 | 0.85 | 8957.95 | 01-JUN-03:03 | 1.40 |
July | 0.135691E+11 | 0.79 | 8957.95 | 01-JUL-03:50 | 1.39 |
August | 0.149858E+11 | 0.87 | 8957.95 | 01-AUG-03:02 | 1.40 |
September | 0.137424E+11 | 0.83 | 8957.95 | 01-SEP-03:02 | 1.39 |
October | 0.138633E+11 | 0.81 | 8957.95 | 02-OCT-03:03 | 1.40 |
November | 0.132981E+11 | 0.80 | 8957.95 | 01-NOV-03:10 | 1.40 |
December | 0.131736E+11 | 0.77 | 8957.95 | 01-DEC-05:01 | 1.40 |
Annual Sum or Average | 0.164059E+12 | 0.81 | |||
Minimum of Months | 0.120368E+11 | 0.77 | 8957.95 | 1.39 | |
Maximum of Months | 0.149858E+11 | 0.87 | 8957.95 | 1.41 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.397298E+10 | 0.33 | 12364.66 | 10-JAN-06:01 | 1.40 |
February | 0.414292E+10 | 0.35 | 9263.91 | 13-FEB-05:01 | 1.17 |
March | 0.549942E+10 | 0.40 | 10460.06 | 18-MAR-05:03 | 1.25 |
April | 0.933033E+10 | 0.54 | 17098.62 | 28-APR-14:40 | 1.70 |
May | 0.723099E+10 | 0.46 | 13172.53 | 22-MAY-15:20 | 1.44 |
June | 0.937415E+10 | 0.55 | 16168.79 | 26-JUN-05:03 | 1.64 |
July | 0.109956E+11 | 0.60 | 19923.88 | 24-JUL-05:02 | 1.87 |
August | 0.129432E+11 | 0.68 | 19107.53 | 14-AUG-14:50 | 1.82 |
September | 0.806860E+10 | 0.49 | 14807.35 | 11-SEP-14:40 | 1.54 |
October | 0.602572E+10 | 0.40 | 11769.70 | 10-OCT-13:50 | 1.34 |
November | 0.504718E+10 | 0.37 | 12464.53 | 09-NOV-06:02 | 1.39 |
December | 0.471302E+10 | 0.35 | 11596.79 | 05-DEC-06:02 | 1.33 |
Annual Sum or Average | 0.873441E+11 | 0.46 | |||
Minimum of Months | 0.397298E+10 | 0.33 | 9263.91 | 1.17 | |
Maximum of Months | 0.129432E+11 | 0.68 | 19923.88 | 1.87 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.288539E+11 | 0.30 | 90569.91 | 20-JAN-06:03 | 1.21 |
February | 0.273422E+11 | 0.31 | 131804.04 | 24-FEB-06:02 | 1.53 |
March | 0.324692E+11 | 0.32 | 102553.64 | 27-MAR-05:02 | 1.31 |
April | 0.507943E+11 | 0.39 | 127641.62 | 28-APR-15:20 | 1.49 |
May | 0.526062E+11 | 0.40 | 106308.35 | 23-MAY-15:20 | 1.33 |
June | 0.647583E+11 | 0.46 | 133299.42 | 13-JUN-15:30 | 1.52 |
July | 0.698061E+11 | 0.46 | 131091.12 | 21-JUL-15:30 | 1.51 |
August | 0.776805E+11 | 0.50 | 125655.96 | 14-AUG-15:30 | 1.47 |
September | 0.615745E+11 | 0.44 | 132657.36 | 12-SEP-15:20 | 1.52 |
October | 0.388324E+11 | 0.33 | 90569.91 | 02-OCT-05:03 | 1.21 |
November | 0.290724E+11 | 0.30 | 140839.71 | 03-NOV-05:02 | 1.59 |
December | 0.277110E+11 | 0.30 | 34599.08 | 01-DEC-06:02 | 0.70 |
Annual Sum or Average | 0.561501E+12 | 0.38 | |||
Minimum of Months | 0.273422E+11 | 0.30 | 34599.08 | 0.70 | |
Maximum of Months | 0.776805E+11 | 0.50 | 140839.71 | 1.59 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.309459E+10 | 0.33 | 4479.53 | 02-JAN-04:11 | 0.77 |
February | 0.272360E+10 | 0.32 | 4479.53 | 06-FEB-05:01 | 0.77 |
March | 0.305631E+10 | 0.32 | 4479.53 | 06-MAR-05:22 | 0.77 |
April | 0.397576E+10 | 0.34 | 13414.07 | 28-APR-15:20 | 1.46 |
May | 0.440000E+10 | 0.35 | 12703.43 | 23-MAY-15:20 | 1.41 |
June | 0.580078E+10 | 0.41 | 16575.47 | 13-JUN-15:20 | 1.66 |
July | 0.642160E+10 | 0.42 | 15380.75 | 21-JUL-15:40 | 1.59 |
August | 0.677173E+10 | 0.44 | 13961.49 | 14-AUG-15:40 | 1.50 |
September | 0.484981E+10 | 0.37 | 13435.14 | 12-SEP-15:10 | 1.46 |
October | 0.306397E+10 | 0.30 | 5599.31 | 03-OCT-15:20 | 0.87 |
November | 0.282230E+10 | 0.31 | 4479.53 | 20-NOV-05:01 | 0.77 |
December | 0.322095E+10 | 0.34 | 4479.53 | 01-DEC-06:02 | 0.77 |
Annual Sum or Average | 0.502014E+11 | 0.35 | |||
Minimum of Months | 0.272360E+10 | 0.30 | 4479.53 | 0.77 | |
Maximum of Months | 0.677173E+10 | 0.44 | 16575.47 | 1.66 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.955115E+11 | 1.37 | 35659.90 | 01-JAN-00:05 | 1.36 |
February | 0.862684E+11 | 1.37 | 35659.90 | 01-FEB-00:10 | 1.37 |
March | 0.955115E+11 | 1.37 | 35659.90 | 01-MAR-00:10 | 1.37 |
April | 0.924305E+11 | 1.37 | 35659.90 | 01-APR-00:10 | 1.37 |
May | 0.955115E+11 | 1.37 | 35659.90 | 01-MAY-00:05 | 1.37 |
June | 0.924305E+11 | 1.36 | 35659.90 | 01-JUN-00:10 | 1.36 |
July | 0.955115E+11 | 1.36 | 35659.90 | 01-JUL-00:10 | 1.37 |
August | 0.955115E+11 | 1.36 | 35659.90 | 01-AUG-00:10 | 1.37 |
September | 0.924305E+11 | 1.36 | 35659.90 | 01-SEP-00:10 | 1.37 |
October | 0.955115E+11 | 1.37 | 35659.90 | 01-OCT-00:10 | 1.37 |
November | 0.924305E+11 | 1.37 | 35659.90 | 01-NOV-00:10 | 1.37 |
December | 0.955115E+11 | 1.37 | 35659.90 | 01-DEC-00:10 | 1.37 |
Annual Sum or Average | 0.112457E+13 | 1.37 | |||
Minimum of Months | 0.862684E+11 | 1.36 | 35659.90 | 1.36 | |
Maximum of Months | 0.955115E+11 | 1.37 | 35659.90 | 1.37 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149119E+10 | 0.93 | 556.75 | 01-JAN-00:05 | 0.92 |
February | 0.134688E+10 | 0.93 | 556.75 | 01-FEB-00:10 | 0.93 |
March | 0.149119E+10 | 0.93 | 556.75 | 01-MAR-00:10 | 0.92 |
April | 0.144308E+10 | 0.93 | 556.75 | 01-APR-00:10 | 0.93 |
May | 0.149119E+10 | 0.92 | 556.75 | 01-MAY-00:05 | 0.92 |
June | 0.144308E+10 | 0.92 | 556.75 | 01-JUN-00:10 | 0.92 |
July | 0.149119E+10 | 0.92 | 556.75 | 01-JUL-00:10 | 0.92 |
August | 0.149119E+10 | 0.92 | 556.75 | 01-AUG-00:10 | 0.92 |
September | 0.144308E+10 | 0.92 | 556.75 | 01-SEP-00:10 | 0.92 |
October | 0.149119E+10 | 0.92 | 556.75 | 01-OCT-00:10 | 0.93 |
November | 0.144308E+10 | 0.92 | 556.75 | 01-NOV-00:10 | 0.93 |
December | 0.149119E+10 | 0.93 | 556.75 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.175575E+11 | 0.92 | |||
Minimum of Months | 0.134688E+10 | 0.92 | 556.75 | 0.92 | |
Maximum of Months | 0.149119E+10 | 0.93 | 556.75 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142547E+11 | 0.93 | 5322.10 | 01-JAN-00:10 | 0.92 |
February | 0.128752E+11 | 0.93 | 5322.10 | 01-FEB-00:10 | 0.93 |
March | 0.142547E+11 | 0.93 | 5322.10 | 01-MAR-00:10 | 0.92 |
April | 0.137949E+11 | 0.93 | 5322.10 | 01-APR-00:10 | 0.93 |
May | 0.142547E+11 | 0.92 | 5322.10 | 01-MAY-00:05 | 0.92 |
June | 0.137949E+11 | 0.92 | 5322.10 | 01-JUN-00:10 | 0.92 |
July | 0.142547E+11 | 0.92 | 5322.10 | 01-JUL-00:10 | 0.92 |
August | 0.142547E+11 | 0.92 | 5322.10 | 01-AUG-00:10 | 0.92 |
September | 0.137949E+11 | 0.92 | 5322.10 | 01-SEP-00:10 | 0.92 |
October | 0.142547E+11 | 0.92 | 5322.10 | 01-OCT-00:10 | 0.93 |
November | 0.137949E+11 | 0.92 | 5322.10 | 01-NOV-00:10 | 0.93 |
December | 0.142547E+11 | 0.93 | 5322.10 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.167838E+12 | 0.92 | |||
Minimum of Months | 0.128752E+11 | 0.92 | 5322.10 | 0.92 | |
Maximum of Months | 0.142547E+11 | 0.93 | 5322.10 | 0.93 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144603E+10 | 0.93 | 539.88 | 01-JAN-00:05 | 0.92 |
February | 0.130609E+10 | 0.93 | 539.88 | 01-FEB-00:10 | 0.93 |
March | 0.144603E+10 | 0.93 | 539.88 | 01-MAR-00:10 | 0.92 |
April | 0.139938E+10 | 0.93 | 539.88 | 01-APR-00:10 | 0.93 |
May | 0.144603E+10 | 0.92 | 539.88 | 01-MAY-00:05 | 0.92 |
June | 0.139938E+10 | 0.92 | 539.88 | 01-JUN-00:10 | 0.92 |
July | 0.144603E+10 | 0.92 | 539.88 | 01-JUL-00:10 | 0.92 |
August | 0.144603E+10 | 0.92 | 539.88 | 01-AUG-00:10 | 0.92 |
September | 0.139938E+10 | 0.92 | 539.88 | 01-SEP-00:10 | 0.92 |
October | 0.144603E+10 | 0.92 | 539.88 | 01-OCT-00:10 | 0.93 |
November | 0.139938E+10 | 0.92 | 539.88 | 01-NOV-00:10 | 0.93 |
December | 0.144603E+10 | 0.93 | 539.88 | 01-DEC-00:10 | 0.93 |
Annual Sum or Average | 0.170258E+11 | 0.92 | |||
Minimum of Months | 0.130609E+10 | 0.92 | 539.88 | 0.92 | |
Maximum of Months | 0.144603E+10 | 0.93 | 539.88 | 0.93 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 18661126.93 | 16795014.23 | 382.01 | 02-JAN-06:03 | 343.81 | 343.81 | 43.55 | 5.69 |
February | 9191384.26 | 8272245.83 | 319.48 | 27-FEB-06:01 | 287.53 | 287.53 | 41.11 | 5.25 |
March | 5106708.47 | 4596037.62 | 316.76 | 06-MAR-06:01 | 285.08 | 285.08 | 39.25 | 5.23 |
April | 513447.67 | 462102.90 | 14.72 | 08-APR-06:05 | 13.25 | 13.25 | 28.17 | 1.03 |
May | 194014.39 | 174612.95 | 86.07 | 05-MAY-05:03 | 77.46 | 77.46 | 32.16 | 2.78 |
June | 3953.82 | 3558.44 | 1.91 | 08-JUN-05:02 | 1.72 | 1.72 | 22.25 | 0.24 |
July | 337.69 | 303.92 | 0.06 | 31-JUL-05:03 | 0.06 | 0.06 | 22.12 | 0.01 |
August | 20.98 | 18.88 | 0.04 | 24-AUG-06:10 | 0.03 | 0.03 | 22.09 | 0.01 |
September | 27229.19 | 24506.27 | 3.14 | 21-SEP-06:10 | 2.83 | 2.83 | 22.81 | 0.36 |
October | 1027431.29 | 924688.16 | 88.95 | 28-OCT-05:03 | 80.06 | 80.06 | 29.79 | 2.83 |
November | 6730649.16 | 6057584.24 | 320.85 | 27-NOV-06:01 | 288.76 | 288.76 | 37.90 | 5.26 |
December | 19272941.89 | 17345647.70 | 326.12 | 04-DEC-06:01 | 293.50 | 293.50 | 42.01 | 5.29 |
Annual Sum or Average | 60729245.73 | 54656321.16 | ||||||
Minimum of Months | 20.98 | 18.88 | 0.04 | 0.03 | 0.03 | 22.09 | 0.01 | |
Maximum of Months | 19272941.89 | 17345647.70 | 382.01 | 343.81 | 343.81 | 43.55 | 5.69 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 10.10 | 9.09 | 0.00 | 20-JAN-21:20 | 0.00 | 0.00 | 6.70 | 0.00 |
February | 13.26 | 11.93 | 0.00 | 15-FEB-21:20 | 0.00 | 0.00 | 6.70 | 0.00 |
March | 491.30 | 442.17 | 3.17 | 18-MAR-05:03 | 2.86 | 2.86 | 6.72 | 0.64 |
April | 28647514.07 | 25782762.67 | 6069.55 | 28-APR-15:00 | 5462.59 | 5462.59 | 8.01 | 52.33 |
May | 98452260.96 | 88607034.86 | 3921.51 | 22-MAY-15:50 | 3529.36 | 3529.36 | 7.24 | 43.64 |
June | 0.298072E+09 | 0.268265E+09 | 5815.33 | 20-JUN-15:00 | 5233.79 | 5233.79 | 7.61 | 51.42 |
July | 0.434914E+09 | 0.391423E+09 | 5116.12 | 06-JUL-14:10 | 4604.51 | 4604.51 | 7.86 | 48.77 |
August | 0.562256E+09 | 0.506030E+09 | 6059.05 | 21-AUG-12:10 | 5453.14 | 5453.14 | 7.49 | 52.30 |
September | 0.270719E+09 | 0.243648E+09 | 3236.63 | 12-SEP-14:50 | 2912.96 | 2912.96 | 7.69 | 40.23 |
October | 2871129.30 | 2584016.37 | 96.88 | 06-OCT-15:30 | 87.19 | 87.19 | 8.85 | 7.30 |
November | 70767.13 | 63690.41 | 32.60 | 09-NOV-05:03 | 29.34 | 29.34 | 8.48 | 3.77 |
December | 11.20 | 10.08 | 0.04 | 26-DEC-04:09 | 0.03 | 0.03 | 8.46 | 0.01 |
Annual Sum or Average | 0.169600E+10 | 0.152640E+10 | ||||||
Minimum of Months | 10.10 | 9.09 | 0.00 | 0.00 | 0.00 | 6.70 | 0.00 | |
Maximum of Months | 0.562256E+09 | 0.506030E+09 | 6069.55 | 5462.59 | 5462.59 | 8.85 | 52.33 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.940660E+09 | 0.846594E+09 | 11018.44 | 02-JAN-05:07 | 9916.60 | 9916.60 | 8.39 | 77.23 |
February | 0.151724E+10 | 0.136552E+10 | 11018.44 | 01-FEB-13:10 | 9916.60 | 9916.60 | 8.43 | 77.23 |
March | 0.176361E+10 | 0.158725E+10 | 11018.44 | 01-MAR-06:03 | 9916.60 | 9916.60 | 8.43 | 77.23 |
April | 0.330840E+10 | 0.297756E+10 | 11018.44 | 01-APR-16:20 | 9916.60 | 9916.60 | 8.43 | 77.23 |
May | 0.325507E+10 | 0.292956E+10 | 11018.44 | 01-MAY-04:10 | 9916.60 | 9916.60 | 8.46 | 77.23 |
June | 0.747161E+10 | 0.672445E+10 | 11018.44 | 01-JUN-04:03 | 9916.60 | 9916.60 | 8.44 | 77.23 |
July | 0.131045E+11 | 0.117941E+11 | 11018.44 | 01-JUL-05:03 | 9916.60 | 9916.60 | 8.60 | 77.23 |
August | 0.158377E+11 | 0.142539E+11 | 11018.44 | 01-AUG-03:02 | 9916.60 | 9916.60 | 8.72 | 77.23 |
September | 0.959255E+10 | 0.863329E+10 | 11018.44 | 01-SEP-03:02 | 9916.60 | 9916.60 | 8.46 | 77.23 |
October | 0.164038E+10 | 0.147634E+10 | 11018.44 | 01-OCT-13:13 | 9916.60 | 9916.60 | 8.46 | 77.23 |
November | 0.124013E+10 | 0.111611E+10 | 11018.44 | 01-NOV-13:50 | 9916.60 | 9916.60 | 8.43 | 77.23 |
December | 0.806928E+09 | 0.726235E+09 | 11018.44 | 04-DEC-05:07 | 9916.60 | 9916.60 | 8.43 | 77.23 |
Annual Sum or Average | 0.604788E+11 | 0.544309E+11 | ||||||
Minimum of Months | 0.806928E+09 | 0.726235E+09 | 11018.44 | 9916.60 | 9916.60 | 8.39 | 77.23 | |
Maximum of Months | 0.158377E+11 | 0.142539E+11 | 11018.44 | 9916.60 | 9916.60 | 8.72 | 77.23 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.896006E+10 | 0.806405E+10 | 3345.30 | 01-JAN-00:05 | 3010.77 | 3010.77 | 21.66 | 13.97 |
February | 0.809296E+10 | 0.728366E+10 | 3345.30 | 01-FEB-00:10 | 3010.77 | 3010.77 | 24.32 | 13.97 |
March | 0.896006E+10 | 0.806405E+10 | 3345.30 | 01-MAR-00:10 | 3010.77 | 3010.77 | 27.22 | 13.97 |
April | 0.867102E+10 | 0.780392E+10 | 3345.30 | 01-APR-00:10 | 3010.77 | 3010.77 | 30.40 | 13.97 |
May | 0.896006E+10 | 0.806405E+10 | 3345.30 | 01-MAY-00:05 | 3010.77 | 3010.77 | 22.63 | 13.97 |
June | 0.867102E+10 | 0.780392E+10 | 3345.30 | 01-JUN-00:10 | 3010.77 | 3010.77 | 24.88 | 13.97 |
July | 0.896006E+10 | 0.806405E+10 | 3345.30 | 01-JUL-00:10 | 3010.77 | 3010.77 | 27.64 | 13.97 |
August | 0.896006E+10 | 0.806405E+10 | 3345.30 | 01-AUG-00:10 | 3010.77 | 3010.77 | 30.55 | 13.97 |
September | 0.867102E+10 | 0.780392E+10 | 3345.30 | 01-SEP-00:10 | 3010.77 | 3010.77 | 22.53 | 13.97 |
October | 0.896006E+10 | 0.806405E+10 | 3345.30 | 01-OCT-00:10 | 3010.77 | 3010.77 | 24.83 | 13.97 |
November | 0.867102E+10 | 0.780392E+10 | 3345.30 | 01-NOV-00:10 | 3010.77 | 3010.77 | 27.57 | 13.97 |
December | 0.896006E+10 | 0.806405E+10 | 3345.30 | 01-DEC-00:10 | 3010.77 | 3010.77 | 29.97 | 13.97 |
Annual Sum or Average | 0.105497E+12 | 0.949477E+11 | ||||||
Minimum of Months | 0.809296E+10 | 0.728366E+10 | 3345.30 | 3010.77 | 3010.77 | 21.66 | 13.97 | |
Maximum of Months | 0.896006E+10 | 0.806405E+10 | 3345.30 | 3010.77 | 3010.77 | 30.55 | 13.97 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:05 | 1.79 | 1.79 | 55.20 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:03 | 1.79 | 1.79 | 55.44 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:03 | 1.79 | 1.79 | 56.34 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 55.28 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:03 | 1.79 | 1.79 | 55.90 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.68 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:03 | 1.79 | 1.79 | 56.66 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:03 | 1.79 | 1.79 | 56.18 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:03 | 1.79 | 1.79 | 56.23 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 55.45 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:03 | 1.79 | 1.79 | 56.56 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:02 | 1.79 | 1.79 | 55.57 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.20 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.68 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.119076E+10 | 0.107169E+10 | 13950.18 | 26-JAN-06:50 | 12555.16 | 12555.16 | 21.19 | 46.47 |
February | 0.192064E+10 | 0.172857E+10 | 13949.97 | 02-FEB-06:02 | 12554.98 | 12554.98 | 21.17 | 46.47 |
March | 0.223249E+10 | 0.200924E+10 | 13949.79 | 24-MAR-16:15 | 12554.82 | 12554.82 | 21.15 | 46.47 |
April | 0.420760E+10 | 0.378684E+10 | 27993.06 | 28-APR-15:00 | 25193.75 | 25193.75 | 25.69 | 92.94 |
May | 0.432532E+10 | 0.389279E+10 | 27988.94 | 22-MAY-15:00 | 25190.04 | 25190.04 | 25.51 | 92.94 |
June | 0.104520E+11 | 0.940678E+10 | 28010.10 | 13-JUN-16:00 | 25209.09 | 25209.09 | 26.41 | 92.94 |
July | 0.178567E+11 | 0.160711E+11 | 27999.10 | 21-JUL-13:30 | 25199.19 | 25199.19 | 25.94 | 92.94 |
August | 0.211454E+11 | 0.190309E+11 | 27995.83 | 28-AUG-15:30 | 25196.25 | 25196.25 | 25.80 | 92.94 |
September | 0.128569E+11 | 0.115712E+11 | 27989.40 | 13-SEP-13:00 | 25190.46 | 25190.46 | 25.53 | 92.94 |
October | 0.207718E+10 | 0.186947E+10 | 13963.83 | 07-OCT-15:00 | 12567.44 | 12567.44 | 22.55 | 46.47 |
November | 0.156985E+10 | 0.141287E+10 | 13950.11 | 03-NOV-11:00 | 12555.10 | 12555.10 | 21.19 | 46.47 |
December | 0.102147E+10 | 0.919326E+09 | 13949.95 | 08-DEC-05:53 | 12554.95 | 12554.95 | 21.17 | 46.47 |
Annual Sum or Average | 0.808563E+11 | 0.727707E+11 | ||||||
Minimum of Months | 0.102147E+10 | 0.919326E+09 | 13949.79 | 12554.82 | 12554.82 | 21.15 | 46.47 | |
Maximum of Months | 0.211454E+11 | 0.190309E+11 | 28010.10 | 25209.09 | 25209.09 | 26.41 | 92.94 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 32.16 | 32.16 | 81934.32 | 963684.60 | 04-JAN-06:02 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 23.68 | 23.68 | 59546.47 | 971409.87 | 13-FEB-06:01 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 27.09 | 27.09 | 36986.52 | 950624.00 | 07-MAR-06:02 |
April | 0.00 | 0.00 | 01-APR-00:10 | 25.27 | 25.27 | 5058.84 | 227819.94 | 08-APR-06:05 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 23.65 | 23.65 | 2066.25 | 557222.80 | 05-MAY-05:03 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.17 | 22.17 | 54.73 | 58067.88 | 08-JUN-05:02 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 22.34 | 22.34 | 4.85 | 2379.94 | 31-JUL-05:03 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 22.10 | 22.10 | 0.30 | 1354.75 | 24-AUG-06:10 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 22.09 | 22.09 | 347.44 | 85336.11 | 21-SEP-06:10 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 22.24 | 22.24 | 9413.42 | 593202.32 | 28-OCT-05:03 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 23.19 | 23.19 | 40878.95 | 1023927.91 | 20-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 27.30 | 27.30 | 91887.96 | 1004155.81 | 18-DEC-05:01 |
Annual Sum or Average | 0.00 | 27256.45 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.09 | 22.09 | 0.30 | 1354.75 | ||
Maximum of Months | 0.00 | 0.00 | 32.16 | 32.16 | 91887.96 | 1023927.91 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 626.61 | 19702.05 | 10-JAN-06:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 1121.34 | 19702.05 | 28-FEB-07:00 | 8.43 | 8.40 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 1176.74 | 19702.06 | 29-MAR-05:50 | 8.43 | 8.40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 31778.60 | 1056398.22 | 28-APR-15:00 | 10.96 | 7.69 | 0.00 | 0.00 | 01-APR-00:10 |
May | 37041.87 | 1080154.56 | 22-MAY-15:50 | 10.57 | 7.23 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 108126.05 | 1355945.39 | 13-JUN-16:00 | 10.92 | 6.73 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 182366.68 | 1256354.78 | 21-JUL-15:40 | 10.58 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 240966.67 | 1197829.62 | 14-AUG-15:50 | 10.53 | 6.83 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 126020.47 | 1077531.93 | 12-SEP-13:50 | 10.91 | 7.58 | 0.76 | 9878.61 | 05-SEP-04:10 |
October | 7630.86 | 472452.34 | 07-OCT-15:00 | 9.32 | 8.58 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 927.77 | 91875.43 | 24-NOV-12:00 | 8.59 | 8.45 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 538.70 | 19758.55 | 26-DEC-04:10 | 8.43 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 61966.51 | 0.06 | ||||||
Minimum of Months | 538.70 | 19702.05 | 8.43 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 240966.67 | 1355945.39 | 10.96 | 8.58 | 0.76 | 9878.61 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 6.70 | 6.70 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 6.70 | 6.70 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 85.78 | 18-MAR-05:03 | 6.73 | 8.40 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 19955.48 | 1337736.41 | 30-APR-16:11 | 17.28 | 7.73 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28204.70 | 1186325.93 | 22-MAY-15:50 | 13.19 | 8.49 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 88994.19 | 1353311.58 | 13-JUN-16:00 | 14.71 | 6.73 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 141256.00 | 1248330.08 | 21-JUL-15:40 | 14.19 | 6.70 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 185460.46 | 1259326.47 | 21-AUG-12:10 | 12.45 | 8.56 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 98835.34 | 1216458.78 | 10-SEP-15:02 | 14.59 | 8.12 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 4206.56 | 281651.78 | 07-OCT-15:00 | 16.91 | 8.59 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 62.24 | 78324.37 | 09-NOV-05:03 | 11.65 | 8.44 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.02 | 169.52 | 26-DEC-04:09 | 11.37 | 8.40 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 47584.60 | 0.00 | ||||||
Minimum of Months | 0.00 | 0.00 | 6.70 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 185460.46 | 1353311.58 | 17.28 | 8.59 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 165294.10 | 179522.00 | 19-JAN-16:10 | 22.03 | 18.33 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 307389.37 | 325084.79 | 19-FEB-17:07 | 25.01 | 18.33 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 449783.20 | 590949.06 | 31-MAR-24:00 | 30.40 | 18.33 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 620517.52 | 1212767.53 | 30-APR-18:11 | 42.82 | 29.60 | 0.00 | 0.00 | 01-APR-00:10 |
May | 186999.87 | 568677.68 | 22-MAY-15:00 | 29.95 | 25.75 | 0.00 | 0.00 | 01-MAY-00:05 |
June | 361735.59 | 946751.97 | 13-JUN-17:00 | 37.54 | 30.12 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 561941.73 | 1327823.54 | 22-JUL-18:00 | 45.08 | 34.50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 759096.18 | 1366260.11 | 14-AUG-17:40 | 45.84 | 32.63 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 208581.96 | 525987.58 | 13-SEP-16:00 | 29.09 | 24.78 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 316773.24 | 491635.95 | 07-OCT-15:00 | 28.39 | 21.75 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 449137.46 | 535170.02 | 24-NOV-12:00 | 29.28 | 19.89 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 582478.85 | 593094.22 | 22-DEC-22:10 | 30.45 | 18.33 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 415067.01 | 0.00 | ||||||
Minimum of Months | 165294.10 | 179522.00 | 22.03 | 18.33 | 0.00 | 0.00 | ||
Maximum of Months | 759096.18 | 1366260.11 | 45.84 | 34.50 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 56.44 | 56.44 | 15877.36 | 53230.73 | 31-JAN-12:20 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.13 | 56.13 | 16061.21 | 53332.60 | 23-FEB-12:20 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.78 | 56.78 | 16868.46 | 53225.84 | 01-MAR-12:20 |
April | 0.00 | 0.00 | 01-APR-00:10 | 55.94 | 55.94 | 15619.38 | 52454.45 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:05 | 56.76 | 56.76 | 15704.10 | 51316.79 | 01-MAY-11:50 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.21 | 57.21 | 15653.39 | 49881.74 | 01-JUN-11:40 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 57.21 | 57.21 | 14246.11 | 48626.18 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 56.79 | 56.79 | 15346.83 | 47974.83 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 56.85 | 56.85 | 14579.90 | 48622.30 | 29-SEP-11:20 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 56.56 | 56.56 | 14840.43 | 49895.75 | 31-OCT-12:00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 57.13 | 57.13 | 15411.30 | 51274.55 | 30-NOV-12:40 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.25 | 56.25 | 15262.49 | 52483.21 | 29-DEC-12:30 |
Annual Sum or Average | 0.00 | 15452.47 | ||||||
Minimum of Months | 0.00 | 0.00 | 55.94 | 55.94 | 14246.11 | 47974.83 | ||
Maximum of Months | 0.00 | 0.00 | 57.21 | 57.21 | 16868.46 | 53332.60 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15.35 | 17889.79 | 26-JAN-06:50 | 21.19 | 20.44 | 780.35 | 82428.11 | 07-JAN-06:30 |
February | 33.99 | 13905.56 | 02-FEB-06:02 | 21.17 | 20.38 | 1444.30 | 87929.01 | 06-FEB-06:50 |
March | 30.30 | 10455.00 | 24-MAR-16:15 | 21.15 | 20.48 | 1709.18 | 96701.18 | 14-MAR-05:02 |
April | 19272.57 | 1781260.18 | 28-APR-15:00 | 25.69 | 21.10 | 933.76 | 88847.28 | 03-APR-06:00 |
May | 26169.01 | 1712992.73 | 22-MAY-15:00 | 25.51 | 21.30 | 528.25 | 72639.50 | 05-MAY-05:40 |
June | 91996.36 | 2063221.35 | 13-JUN-16:00 | 26.41 | 22.37 | 435.48 | 71770.02 | 08-JUN-06:00 |
July | 137862.41 | 1881186.21 | 21-JUL-13:30 | 25.94 | 21.62 | 667.23 | 66739.09 | 31-JUL-05:30 |
August | 171520.60 | 1827192.31 | 28-AUG-15:30 | 25.80 | 21.28 | 483.42 | 59332.75 | 28-AUG-05:40 |
September | 94068.25 | 1720693.47 | 13-SEP-13:00 | 25.53 | 21.23 | 775.30 | 72788.16 | 20-SEP-06:00 |
October | 4105.41 | 282079.79 | 07-OCT-15:00 | 22.55 | 21.10 | 648.83 | 81565.79 | 19-OCT-05:50 |
November | 28.60 | 16540.62 | 03-NOV-11:00 | 21.19 | 20.47 | 1039.73 | 109276.32 | 17-NOV-06:50 |
December | 10.03 | 13408.43 | 08-DEC-05:53 | 21.17 | 20.32 | 664.86 | 104828.44 | 04-DEC-07:00 |
Annual Sum or Average | 45734.33 | 838.12 | ||||||
Minimum of Months | 10.03 | 10455.00 | 21.15 | 20.32 | 435.48 | 59332.75 | ||
Maximum of Months | 171520.60 | 2063221.35 | 26.41 | 22.37 | 1709.18 | 109276.32 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.784465E+10 | 0.00 | 897.69 | 0.397298E+10 | 0.00 | 0.00 |
February | 0.445988E+10 | 0.00 | 0.00 | 0.414292E+10 | 0.00 | 0.00 |
March | 0.234226E+10 | 0.00 | 2861.97 | 0.549942E+10 | 0.00 | 0.00 |
April | 0.197535E+09 | 0.00 | 0.415575E+10 | 0.933033E+10 | 0.00 | 0.00 |
May | 0.100690E+09 | 0.00 | 0.513317E+10 | 0.723099E+10 | 0.00 | 0.00 |
June | 230085.01 | 0.00 | 0.170406E+11 | 0.937415E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.288682E+11 | 0.109956E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.383842E+11 | 0.129432E+11 | 0.00 | 0.00 |
September | 10092358.08 | 0.00 | 0.176532E+11 | 0.806860E+10 | 0.00 | 0.00 |
October | 0.334458E+09 | 0.00 | 0.929994E+09 | 0.602572E+10 | 0.00 | 0.00 |
November | 0.197463E+10 | 0.00 | 13330363.93 | 0.504718E+10 | 0.00 | 0.00 |
December | 0.515029E+10 | 0.00 | 1589.79 | 0.471302E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.224147E+11 | 0.00 | 0.112178E+12 | 0.873441E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.397298E+10 | 0.00 | 0.00 |
Maximum of Months | 0.784465E+10 | 0.00 | 0.383842E+11 | 0.129432E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.176460E+12 | 0.00 | 57669.71 | 0.288539E+11 | 0.00 | 0.00 |
February | 0.114330E+12 | 0.00 | 84401.45 | 0.273422E+11 | 0.00 | 0.00 |
March | 0.777169E+11 | 0.00 | 104418.45 | 0.324692E+11 | 0.00 | 0.00 |
April | 0.960062E+10 | 0.00 | 0.331621E+11 | 0.507943E+11 | 0.00 | 0.00 |
May | 0.356589E+10 | 0.00 | 0.422362E+11 | 0.526062E+11 | 0.00 | 0.00 |
June | 67555301.43 | 0.00 | 0.137546E+12 | 0.647583E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.223227E+12 | 0.698061E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.282184E+12 | 0.776805E+11 | 0.00 | 0.00 |
September | 0.446347E+09 | 0.00 | 0.150846E+12 | 0.615745E+11 | 0.00 | 0.00 |
October | 0.169710E+11 | 0.00 | 0.714757E+10 | 0.388324E+11 | 0.00 | 0.00 |
November | 0.824162E+11 | 0.00 | 47130665.60 | 0.290724E+11 | 0.00 | 0.00 |
December | 0.200984E+12 | 0.00 | 47554.73 | 0.277110E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.682558E+12 | 0.00 | 0.876395E+12 | 0.561501E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 47554.73 | 0.273422E+11 | 0.00 | 0.00 |
Maximum of Months | 0.200984E+12 | 0.00 | 0.282184E+12 | 0.776805E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.362894E+11 | 0.00 | 27.89 | 0.309459E+10 | 0.00 | 0.00 |
February | 0.259680E+11 | 0.00 | 0.00 | 0.272360E+10 | 0.00 | 0.00 |
March | 0.195083E+11 | 0.00 | 182.78 | 0.305631E+10 | 0.00 | 0.00 |
April | 0.338737E+10 | 0.00 | 0.326169E+10 | 0.397576E+10 | 0.00 | 0.00 |
May | 0.190255E+10 | 0.00 | 0.441918E+10 | 0.440000E+10 | 0.00 | 0.00 |
June | 73908740.05 | 0.00 | 0.146872E+11 | 0.580078E+10 | 0.00 | 0.00 |
July | 14147257.24 | 0.00 | 0.232846E+11 | 0.642160E+10 | 0.00 | 0.00 |
August | 839693.91 | 0.00 | 0.275827E+11 | 0.677173E+10 | 0.00 | 0.00 |
September | 0.447388E+09 | 0.00 | 0.137438E+11 | 0.484981E+10 | 0.00 | 0.00 |
October | 0.802662E+10 | 0.00 | 0.531325E+09 | 0.306397E+10 | 0.00 | 0.00 |
November | 0.220724E+11 | 0.00 | 4474093.86 | 0.282230E+10 | 0.00 | 0.00 |
December | 0.411789E+11 | 0.00 | 21497.12 | 0.322095E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.158870E+12 | 0.00 | 0.875150E+11 | 0.502014E+11 | 0.00 | 0.00 |
Minimum of Months | 839693.91 | 0.00 | 0.00 | 0.272360E+10 | 0.00 | 0.00 |
Maximum of Months | 0.411789E+11 | 0.00 | 0.275827E+11 | 0.677173E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 18311.87 | 0.136582E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 4482.34 | 0.120368E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 843054.49 | 0.142364E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.654900E+09 | 0.134159E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.207754E+10 | 0.140246E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.752776E+10 | 0.140550E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.123686E+11 | 0.135691E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.161247E+11 | 0.149858E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.783205E+10 | 0.137424E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.128931E+09 | 0.138633E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 14806520.58 | 0.132981E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.131736E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.467301E+11 | 0.164059E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.120368E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.161247E+11 | 0.149858E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.400803E+12 | 0.176864E+12 | 0.00 | 0.41 |
February | 0.00 | 0.00 | 0.631916E+12 | 0.208344E+12 | 0.00 | 0.27 |
March | 0.00 | 0.00 | 0.997152E+12 | 0.281575E+12 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.125601E+13 | 0.322117E+12 | 0.00 | 0.23 |
May | 0.00 | 0.00 | 0.409052E+12 | 0.177163E+12 | 0.00 | 0.04 |
June | 0.00 | 0.00 | 0.690494E+12 | 0.225493E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.102006E+13 | 0.291271E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.132286E+13 | 0.349001E+12 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.402271E+12 | 0.172714E+12 | 0.00 | 0.01 |
October | 0.00 | 0.00 | 0.706721E+12 | 0.230295E+12 | 0.00 | 0.04 |
November | 0.00 | 0.00 | 0.967264E+12 | 0.271504E+12 | 0.00 | 0.16 |
December | 0.00 | 0.00 | 0.129082E+13 | 0.329580E+12 | 0.00 | 0.40 |
Annual Sum or Average | 0.00 | 0.00 | 0.100954E+14 | 0.303592E+13 | 0.00 | 1.90 |
Minimum of Months | 0.00 | 0.00 | 0.400803E+12 | 0.172714E+12 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.132286E+13 | 0.349001E+12 | 0.00 | 0.41 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.520852E+10 | 0.255741E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.107553E+11 | 0.343090E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.184540E+11 | 0.492830E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.243952E+11 | 0.588831E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.666723E+10 | 0.281682E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.129257E+11 | 0.390272E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.197913E+11 | 0.523919E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.259495E+11 | 0.640348E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.670547E+10 | 0.277088E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.125857E+11 | 0.387825E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.178429E+11 | 0.473605E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.242292E+11 | 0.589868E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185510E+12 | 0.524510E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.520852E+10 | 0.255741E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.259495E+11 | 0.640348E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.264846E+11 | 0.199205E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.831199E+11 | 0.292315E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.156689E+12 | 0.437649E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.224209E+12 | 0.548439E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.545691E+11 | 0.252154E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.117870E+12 | 0.363188E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.184176E+12 | 0.492453E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.243875E+12 | 0.605283E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.562494E+11 | 0.250357E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.104123E+12 | 0.342212E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.148182E+12 | 0.414974E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.201427E+12 | 0.514590E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160097E+13 | 0.471282E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.264846E+11 | 0.199205E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.243875E+12 | 0.605283E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.712901E+09 | 0.160772E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.602913E+10 | 0.251607E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.136227E+11 | 0.404442E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.213649E+11 | 0.533838E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.448144E+10 | 0.235776E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.113364E+11 | 0.357600E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.180473E+11 | 0.488937E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.240356E+11 | 0.602435E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.478716E+10 | 0.236782E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.847020E+10 | 0.309407E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.125469E+11 | 0.377867E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.176693E+11 | 0.475475E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.143104E+12 | 0.443494E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.712901E+09 | 0.160772E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.240356E+11 | 0.602435E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.397298E+10 | 897.69 | 0.784465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414292E+10 | 0.00 | 0.445988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549942E+10 | 2861.97 | 0.234226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.933033E+10 | 0.415575E+10 | 0.197535E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723099E+10 | 0.513317E+10 | 0.100690E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.937415E+10 | 0.170406E+11 | 230085.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109956E+11 | 0.288682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129432E+11 | 0.383842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.806860E+10 | 0.176532E+11 | 10092358.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.602572E+10 | 0.929994E+09 | 0.334458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504718E+10 | 13330363.93 | 0.197463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471302E+10 | 1589.79 | 0.515029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873441E+11 | 0.112178E+12 | 0.224147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129432E+11 | 0.383842E+11 | 0.784465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.288539E+11 | 57669.71 | 0.176460E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273422E+11 | 84401.45 | 0.114330E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324692E+11 | 104418.45 | 0.777169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.507943E+11 | 0.331621E+11 | 0.960062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.526062E+11 | 0.422362E+11 | 0.356589E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.647583E+11 | 0.137546E+12 | 67555301.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.698061E+11 | 0.223227E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.776805E+11 | 0.282184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.615745E+11 | 0.150846E+12 | 0.446347E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.388324E+11 | 0.714757E+10 | 0.169710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290724E+11 | 47130665.60 | 0.824162E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277110E+11 | 47554.73 | 0.200984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561501E+12 | 0.876395E+12 | 0.682558E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.273422E+11 | 47554.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.776805E+11 | 0.282184E+12 | 0.200984E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.309459E+10 | 27.89 | 0.362894E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272360E+10 | 0.00 | 0.259680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305631E+10 | 182.78 | 0.195083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397576E+10 | 0.326169E+10 | 0.338737E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.440000E+10 | 0.441918E+10 | 0.190255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580078E+10 | 0.146872E+11 | 73908740.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.642160E+10 | 0.232846E+11 | 14147257.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.677173E+10 | 0.275827E+11 | 839693.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.484981E+10 | 0.137438E+11 | 0.447388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306397E+10 | 0.531325E+09 | 0.802662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282230E+10 | 4474093.86 | 0.220724E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322095E+10 | 21497.12 | 0.411789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502014E+11 | 0.875150E+11 | 0.158870E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272360E+10 | 0.00 | 839693.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.677173E+10 | 0.275827E+11 | 0.411789E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.136582E+11 | 18311.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120368E+11 | 4482.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142364E+11 | 843054.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134159E+11 | 0.654900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140246E+11 | 0.207754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140550E+11 | 0.752776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135691E+11 | 0.123686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149858E+11 | 0.161247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137424E+11 | 0.783205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138633E+11 | 0.128938E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132981E+11 | 14806520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164059E+12 | 0.467301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149858E+11 | 0.161247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.955115E+11 | 0.320555E+12 | 0.00 | 0.00 | 0.00 | 0.109943E+10 | 0.00 | 0.00 |
February | 0.862684E+11 | 0.510557E+12 | 0.00 | 0.00 | 0.00 | 0.712838E+09 | 0.00 | 0.00 |
March | 0.955115E+11 | 0.812015E+12 | 0.00 | 0.00 | 0.00 | 0.922479E+09 | 0.00 | 0.00 |
April | 0.924305E+11 | 0.102694E+13 | 0.00 | 0.00 | 0.00 | 0.612962E+09 | 0.00 | 0.00 |
May | 0.955115E+11 | 0.327495E+12 | 0.00 | 0.00 | 0.00 | 93897737.69 | 0.00 | 0.00 |
June | 0.924305E+11 | 0.557432E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.955115E+11 | 0.824304E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.955115E+11 | 0.106938E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.924305E+11 | 0.322016E+12 | 0.00 | 0.00 | 0.00 | 27194283.55 | 0.00 | 0.00 |
October | 0.955115E+11 | 0.572047E+12 | 0.00 | 0.00 | 0.00 | 0.109703E+09 | 0.00 | 0.00 |
November | 0.924305E+11 | 0.788612E+12 | 0.00 | 0.00 | 0.00 | 0.420669E+09 | 0.00 | 0.00 |
December | 0.955115E+11 | 0.105783E+13 | 0.00 | 0.00 | 0.00 | 0.107956E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.112457E+13 | 0.818918E+13 | 0.00 | 0.00 | 0.00 | 0.507873E+10 | 0.00 | 0.00 |
Minimum of Months | 0.862684E+11 | 0.320555E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.955115E+11 | 0.106938E+13 | 0.00 | 0.00 | 0.00 | 0.109943E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149119E+10 | 0.414230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134688E+10 | 0.867132E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149119E+10 | 0.150169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144308E+10 | 0.199500E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149119E+10 | 0.534160E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144308E+10 | 0.104661E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149119E+10 | 0.160433E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149119E+10 | 0.210372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144308E+10 | 0.537767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149119E+10 | 0.101987E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144308E+10 | 0.145499E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149119E+10 | 0.198217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175575E+11 | 0.150617E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134688E+10 | 0.414230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149119E+10 | 0.210372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142547E+11 | 0.208188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128752E+11 | 0.667636E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142547E+11 | 0.127179E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137949E+11 | 0.183160E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142547E+11 | 0.436084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137949E+11 | 0.953459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142547E+11 | 0.149186E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142547E+11 | 0.197602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137949E+11 | 0.450086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142547E+11 | 0.841563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137949E+11 | 0.120480E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142547E+11 | 0.164223E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167838E+12 | 0.129753E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128752E+11 | 0.208188E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142547E+11 | 0.197602E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144603E+10 | 0.551204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130609E+10 | 0.481915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144603E+10 | 0.110243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139938E+10 | 0.174259E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144603E+10 | 0.356971E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139938E+10 | 0.915979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144603E+10 | 0.146040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144603E+10 | 0.194572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139938E+10 | 0.381872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144603E+10 | 0.682216E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139938E+10 | 0.101676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144603E+10 | 0.143606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170258E+11 | 0.115780E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130609E+10 | 0.551204E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144603E+10 | 0.194572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.397298E+10 | 0.784465E+10 | 897.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414292E+10 | 0.445988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.549942E+10 | 0.234226E+10 | 2861.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.933033E+10 | 0.197535E+09 | 0.415575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.723099E+10 | 0.100690E+09 | 0.513317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.937415E+10 | 230085.01 | 0.170406E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.109956E+11 | 0.00 | 0.288682E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.129432E+11 | 0.00 | 0.383842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.806860E+10 | 10092358.08 | 0.176532E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.602572E+10 | 0.334458E+09 | 0.929994E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.504718E+10 | 0.197463E+10 | 13330363.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.471302E+10 | 0.515029E+10 | 1589.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.873441E+11 | 0.224147E+11 | 0.112178E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.397298E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129432E+11 | 0.784465E+10 | 0.383842E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.288539E+11 | 0.176460E+12 | 57669.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.273422E+11 | 0.114330E+12 | 84401.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.324692E+11 | 0.777169E+11 | 104418.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.507943E+11 | 0.960062E+10 | 0.331621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.526062E+11 | 0.356589E+10 | 0.422362E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.647583E+11 | 67555301.43 | 0.137546E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.698061E+11 | 0.00 | 0.223227E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.776805E+11 | 0.00 | 0.282184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.615745E+11 | 0.446347E+09 | 0.150846E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.388324E+11 | 0.169710E+11 | 0.714757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.290724E+11 | 0.824162E+11 | 47130665.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.277110E+11 | 0.200984E+12 | 47554.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.561501E+12 | 0.682558E+12 | 0.876395E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.273422E+11 | 0.00 | 47554.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.776805E+11 | 0.200984E+12 | 0.282184E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.309459E+10 | 0.362894E+11 | 27.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.272360E+10 | 0.259680E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.305631E+10 | 0.195083E+11 | 182.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.397576E+10 | 0.338737E+10 | 0.326169E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.440000E+10 | 0.190255E+10 | 0.441918E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.580078E+10 | 73908740.05 | 0.146872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.642160E+10 | 14147257.24 | 0.232846E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.677173E+10 | 839693.91 | 0.275827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.484981E+10 | 0.447388E+09 | 0.137438E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.306397E+10 | 0.802662E+10 | 0.531325E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.282230E+10 | 0.220724E+11 | 4474093.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.322095E+10 | 0.411789E+11 | 21497.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.502014E+11 | 0.158870E+12 | 0.875150E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.272360E+10 | 839693.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.677173E+10 | 0.411789E+11 | 0.275827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.136582E+11 | 0.00 | 18311.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.120368E+11 | 0.00 | 4482.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142364E+11 | 0.00 | 843054.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.134159E+11 | 0.00 | 0.654900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.140246E+11 | 0.00 | 0.207754E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140550E+11 | 0.00 | 0.752776E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.135691E+11 | 0.00 | 0.123686E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149858E+11 | 0.00 | 0.161247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137424E+11 | 0.00 | 0.783205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.138633E+11 | 0.00 | 0.128931E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132981E+11 | 0.00 | 14806520.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164059E+12 | 0.00 | 0.467301E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.120368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149858E+11 | 0.00 | 0.161247E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.955115E+11 | 0.00 | 0.400803E+12 | 0.00 | 0.802483E+11 | 0.00 | 0.00 | 0.00 | 0.110438E+10 | 0.00 | 0.00 | 0.00 |
February | 0.862684E+11 | 0.00 | 0.631916E+12 | 0.00 | 0.121359E+12 | 0.00 | 0.00 | 0.00 | 0.716047E+09 | 0.00 | 0.00 | 0.00 |
March | 0.955115E+11 | 0.00 | 0.997152E+12 | 0.00 | 0.185137E+12 | 0.00 | 0.00 | 0.00 | 0.926632E+09 | 0.00 | 0.00 | 0.00 |
April | 0.924305E+11 | 0.00 | 0.125601E+13 | 0.00 | 0.229071E+12 | 0.00 | 0.00 | 0.00 | 0.615721E+09 | 0.00 | 0.00 | 0.00 |
May | 0.955115E+11 | 0.00 | 0.409052E+12 | 0.00 | 0.815575E+11 | 0.00 | 0.00 | 0.00 | 94320409.47 | 0.00 | 0.00 | 0.00 |
June | 0.924305E+11 | 0.00 | 0.690494E+12 | 0.00 | 0.133062E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.955115E+11 | 0.00 | 0.102006E+13 | 0.00 | 0.195760E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.955115E+11 | 0.00 | 0.132286E+13 | 0.00 | 0.253489E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.924305E+11 | 0.00 | 0.402271E+12 | 0.00 | 0.802558E+11 | 0.00 | 0.00 | 0.00 | 27316696.05 | 0.00 | 0.00 | 0.00 |
October | 0.955115E+11 | 0.00 | 0.706721E+12 | 0.00 | 0.134673E+12 | 0.00 | 0.00 | 0.00 | 0.110197E+09 | 0.00 | 0.00 | 0.00 |
November | 0.924305E+11 | 0.00 | 0.967264E+12 | 0.00 | 0.178651E+12 | 0.00 | 0.00 | 0.00 | 0.422562E+09 | 0.00 | 0.00 | 0.00 |
December | 0.955115E+11 | 0.00 | 0.129082E+13 | 0.00 | 0.232984E+12 | 0.00 | 0.00 | 0.00 | 0.108442E+10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112457E+13 | 0.00 | 0.100954E+14 | 0.00 | 0.190625E+13 | 0.00 | 0.00 | 0.00 | 0.510159E+10 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.862684E+11 | 0.00 | 0.400803E+12 | 0.00 | 0.802483E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.955115E+11 | 0.00 | 0.132286E+13 | 0.00 | 0.253489E+12 | 0.00 | 0.00 | 0.00 | 0.110438E+10 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149119E+10 | 0.00 | 0.520852E+10 | 0.00 | 0.106622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134688E+10 | 0.00 | 0.107553E+11 | 0.00 | 0.208402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149119E+10 | 0.00 | 0.184540E+11 | 0.00 | 0.343711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144308E+10 | 0.00 | 0.243952E+11 | 0.00 | 0.444522E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149119E+10 | 0.00 | 0.666723E+10 | 0.00 | 0.132563E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144308E+10 | 0.00 | 0.129257E+11 | 0.00 | 0.245963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149119E+10 | 0.00 | 0.197913E+11 | 0.00 | 0.374800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149119E+10 | 0.00 | 0.259495E+11 | 0.00 | 0.491229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144308E+10 | 0.00 | 0.670547E+10 | 0.00 | 0.132780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149119E+10 | 0.00 | 0.125857E+11 | 0.00 | 0.238706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144308E+10 | 0.00 | 0.178429E+11 | 0.00 | 0.329296E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149119E+10 | 0.00 | 0.242292E+11 | 0.00 | 0.440749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175575E+11 | 0.00 | 0.185510E+12 | 0.00 | 0.348934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134688E+10 | 0.00 | 0.520852E+10 | 0.00 | 0.106622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149119E+10 | 0.00 | 0.259495E+11 | 0.00 | 0.491229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142547E+11 | 0.00 | 0.264846E+11 | 0.00 | 0.566584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128752E+11 | 0.00 | 0.831199E+11 | 0.00 | 0.163563E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.142547E+11 | 0.00 | 0.156689E+12 | 0.00 | 0.295102E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137949E+11 | 0.00 | 0.224209E+12 | 0.00 | 0.410491E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.142547E+11 | 0.00 | 0.545691E+11 | 0.00 | 0.109607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.137949E+11 | 0.00 | 0.117870E+12 | 0.00 | 0.225239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142547E+11 | 0.00 | 0.184176E+12 | 0.00 | 0.349906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.142547E+11 | 0.00 | 0.243875E+12 | 0.00 | 0.462736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137949E+11 | 0.00 | 0.562494E+11 | 0.00 | 0.112408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142547E+11 | 0.00 | 0.104123E+12 | 0.00 | 0.199665E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137949E+11 | 0.00 | 0.148182E+12 | 0.00 | 0.277026E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142547E+11 | 0.00 | 0.201427E+12 | 0.00 | 0.372043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.167838E+12 | 0.00 | 0.160097E+13 | 0.00 | 0.303444E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128752E+11 | 0.00 | 0.264846E+11 | 0.00 | 0.566584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.142547E+11 | 0.00 | 0.243875E+12 | 0.00 | 0.462736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144603E+10 | 0.00 | 0.712901E+09 | 0.00 | 0.161697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130609E+10 | 0.00 | 0.602913E+10 | 0.00 | 0.120998E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144603E+10 | 0.00 | 0.136227E+11 | 0.00 | 0.259840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139938E+10 | 0.00 | 0.213649E+11 | 0.00 | 0.393900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144603E+10 | 0.00 | 0.448144E+10 | 0.00 | 0.911732E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139938E+10 | 0.00 | 0.113364E+11 | 0.00 | 0.217662E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.144603E+10 | 0.00 | 0.180473E+11 | 0.00 | 0.344334E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144603E+10 | 0.00 | 0.240356E+11 | 0.00 | 0.457833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139938E+10 | 0.00 | 0.478716E+10 | 0.00 | 0.968435E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144603E+10 | 0.00 | 0.847020E+10 | 0.00 | 0.164804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139938E+10 | 0.00 | 0.125469E+11 | 0.00 | 0.237929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.144603E+10 | 0.00 | 0.176693E+11 | 0.00 | 0.330872E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170258E+11 | 0.00 | 0.143104E+12 | 0.00 | 0.273236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130609E+10 | 0.00 | 0.712901E+09 | 0.00 | 0.161697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144603E+10 | 0.00 | 0.240356E+11 | 0.00 | 0.457833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.575346E+09 | 0.00 | 0.00 | 95779807.95 | 0.00 | 0.00 | 0.645478E+11 | 0.00 | 0.53 |
February | 0.425795E+09 | 0.00 | 0.00 | 91839934.98 | 0.00 | 0.00 | 0.591756E+11 | 0.00 | 0.55 |
March | 0.375731E+09 | 0.00 | 0.00 | 0.104360E+09 | 0.00 | 0.00 | 0.720737E+11 | 0.00 | 0.65 |
April | 0.333100E+09 | 0.00 | 0.00 | 0.108218E+09 | 0.00 | 0.00 | 0.704985E+11 | 0.00 | 0.87 |
May | 0.296803E+09 | 0.00 | 0.00 | 0.104836E+09 | 0.00 | 0.00 | 0.702182E+11 | 0.00 | 0.89 |
June | 0.249133E+09 | 1715151.83 | 0.00 | 0.108034E+09 | 0.00 | 0.00 | 0.671244E+11 | 0.00 | 1.16 |
July | 0.243267E+09 | 54927197.62 | 0.00 | 0.111656E+09 | 7155770.27 | 0.00 | 0.624305E+11 | 0.00 | 1.24 |
August | 0.240038E+09 | 0.00 | 0.00 | 0.123446E+09 | 0.00 | 0.00 | 0.662763E+11 | 0.00 | 1.47 |
September | 0.340428E+09 | 0.00 | 0.00 | 0.109057E+09 | 0.00 | 0.00 | 0.642968E+11 | 0.00 | 1.20 |
October | 0.369739E+09 | 0.00 | 0.00 | 0.108866E+09 | 0.00 | 0.00 | 0.722382E+11 | 0.00 | 0.85 |
November | 0.386857E+09 | 0.00 | 0.00 | 0.108310E+09 | 0.00 | 0.00 | 0.694273E+11 | 0.00 | 0.68 |
December | 0.558502E+09 | 0.00 | 0.00 | 0.107295E+09 | 0.00 | 0.00 | 0.669662E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.439474E+10 | 56642349.45 | 0.00 | 0.128170E+10 | 7155770.27 | 0.00 | 0.805273E+12 | 0.00 | 0.89 |
Minimum of Months | 0.240038E+09 | 0.00 | 0.00 | 91839934.98 | 0.00 | 0.00 | 0.591756E+11 | 0.00 | 0.53 |
Maximum of Months | 0.575346E+09 | 54927197.62 | 0.00 | 0.123446E+09 | 7155770.27 | 0.00 | 0.722382E+11 | 0.00 | 1.47 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.402258E+10 | 0.00 | 0.00 | 57949673.98 | 0.00 | 0.00 | 0.455507E+11 | 0.00 | 0.39 |
February | 0.178153E+10 | 0.00 | 0.00 | 66401537.69 | 0.00 | 0.00 | 0.446854E+11 | 0.00 | 0.41 |
March | 0.144602E+10 | 0.00 | 0.00 | 86199512.14 | 0.00 | 0.00 | 0.580590E+11 | 0.00 | 0.51 |
April | 0.555891E+10 | 0.00 | 0.00 | 93909624.60 | 0.00 | 0.00 | 0.602118E+11 | 0.00 | 0.77 |
May | 0.433237E+10 | 0.00 | 0.00 | 82425380.39 | 0.00 | 0.00 | 0.537540E+11 | 0.00 | 0.69 |
June | 0.532803E+10 | 5121123.90 | 0.00 | 90926612.61 | 68611524.75 | 0.00 | 0.541120E+11 | 0.00 | 0.95 |
July | 0.898655E+10 | 24669353.24 | 0.00 | 90082274.12 | 9239236.62 | 0.00 | 0.488986E+11 | 0.00 | 1.04 |
August | 0.105947E+11 | 0.00 | 0.00 | 0.102053E+09 | 0.00 | 0.00 | 0.508302E+11 | 0.00 | 1.21 |
September | 0.479714E+10 | 0.00 | 0.00 | 83784090.53 | 0.00 | 0.00 | 0.463129E+11 | 0.00 | 0.88 |
October | 0.233656E+10 | 0.00 | 0.00 | 81680159.76 | 0.00 | 0.00 | 0.536263E+11 | 0.00 | 0.63 |
November | 0.174309E+10 | 0.00 | 0.00 | 81818370.46 | 0.00 | 0.00 | 0.523815E+11 | 0.00 | 0.51 |
December | 0.142302E+10 | 0.00 | 0.00 | 80305772.33 | 0.00 | 0.00 | 0.517105E+11 | 0.00 | 0.42 |
Annual Sum or Average | 0.523505E+11 | 29790477.15 | 0.00 | 0.997536E+09 | 77850761.36 | 0.00 | 0.620133E+12 | 0.00 | 0.70 |
Minimum of Months | 0.142302E+10 | 0.00 | 0.00 | 57949673.98 | 0.00 | 0.00 | 0.446854E+11 | 0.00 | 0.39 |
Maximum of Months | 0.105947E+11 | 24669353.24 | 0.00 | 0.102053E+09 | 68611524.75 | 0.00 | 0.602118E+11 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219551E+12 | 0.00 | 0.00 | 0.165678E+09 | 0.00 | 0.00 | 0.157175E+12 | 0.00 | 0.30 |
February | 0.165162E+12 | 0.00 | 0.00 | 0.203319E+09 | 0.00 | 0.00 | 0.170528E+12 | 0.00 | 0.30 |
March | 0.154091E+12 | 0.00 | 0.00 | 0.308894E+09 | 0.00 | 0.00 | 0.247485E+12 | 0.00 | 0.35 |
April | 0.512086E+11 | 0.00 | 0.00 | 0.503754E+09 | 0.00 | 0.00 | 0.376355E+12 | 0.00 | 0.51 |
May | 0.623382E+11 | 0.00 | 0.00 | 0.531954E+09 | 0.00 | 0.00 | 0.388551E+12 | 0.00 | 0.55 |
June | 0.356432E+11 | 41005839.67 | 0.00 | 0.649163E+09 | 0.704710E+09 | 0.00 | 0.415229E+12 | 0.00 | 0.73 |
July | 0.438055E+11 | 0.267317E+09 | 0.00 | 0.637442E+09 | 0.135403E+09 | 0.00 | 0.358163E+12 | 0.00 | 0.75 |
August | 0.385141E+11 | 0.00 | 0.00 | 0.720408E+09 | 0.00 | 0.00 | 0.373858E+12 | 0.00 | 0.85 |
September | 0.445278E+11 | 0.00 | 0.00 | 0.584867E+09 | 0.00 | 0.00 | 0.357093E+12 | 0.00 | 0.71 |
October | 0.932716E+11 | 0.00 | 0.00 | 0.395344E+09 | 0.00 | 0.00 | 0.293404E+12 | 0.00 | 0.44 |
November | 0.150097E+12 | 0.00 | 0.00 | 0.241657E+09 | 0.00 | 0.00 | 0.195262E+12 | 0.00 | 0.33 |
December | 0.231633E+12 | 0.00 | 0.00 | 97621257.06 | 0.00 | 0.00 | 0.120016E+12 | 0.00 | 0.29 |
Annual Sum or Average | 0.128984E+13 | 0.308323E+09 | 0.00 | 0.504010E+10 | 0.840113E+09 | 0.00 | 0.345312E+13 | 0.00 | 0.51 |
Minimum of Months | 0.356432E+11 | 0.00 | 0.00 | 97621257.06 | 0.00 | 0.00 | 0.120016E+12 | 0.00 | 0.29 |
Maximum of Months | 0.231633E+12 | 0.267317E+09 | 0.00 | 0.720408E+09 | 0.704710E+09 | 0.00 | 0.415229E+12 | 0.00 | 0.85 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.299579E+11 | 0.00 | 0.00 | 365580.65 | 0.00 | 0.152883E+10 | 0.705897E+09 | 0.00 | 0.28 |
February | 0.270863E+11 | 0.00 | 0.00 | 389907.05 | 0.00 | 0.555940E+09 | 0.121353E+10 | 0.00 | 0.29 |
March | 0.291922E+11 | 0.00 | 0.00 | 2115350.90 | 0.00 | 0.410066E+09 | 0.370359E+10 | 0.00 | 0.31 |
April | 0.133323E+11 | 3726876.21 | 0.00 | 25368918.79 | 0.00 | 0.00 | 0.227332E+11 | 0.00 | 0.44 |
May | 0.119144E+11 | 0.00 | 0.00 | 32605021.47 | 0.00 | 0.00 | 0.271112E+11 | 0.00 | 0.49 |
June | 0.764970E+10 | 847031.97 | 0.00 | 50939305.43 | 57240695.56 | 0.00 | 0.346561E+11 | 0.00 | 0.70 |
July | 0.694796E+10 | 16079219.94 | 0.00 | 53991798.41 | 5778172.00 | 0.00 | 0.321031E+11 | 0.00 | 0.73 |
August | 0.684818E+10 | 0.00 | 0.00 | 57178988.47 | 0.00 | 0.00 | 0.321513E+11 | 0.00 | 0.81 |
September | 0.996514E+10 | 0.00 | 0.00 | 35956182.93 | 0.00 | 0.00 | 0.239721E+11 | 0.00 | 0.62 |
October | 0.202422E+11 | 0.00 | 0.00 | 7595091.03 | 0.00 | 0.204672E+09 | 0.873802E+10 | 0.00 | 0.36 |
November | 0.257105E+11 | 0.00 | 0.00 | 1056878.46 | 0.00 | 0.653947E+09 | 0.176780E+10 | 0.00 | 0.30 |
December | 0.293501E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140036E+10 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.218197E+12 | 20653128.13 | 0.00 | 0.267563E+09 | 63018867.56 | 0.475382E+10 | 0.188856E+12 | 0.00 | 0.47 |
Minimum of Months | 0.684818E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.299579E+11 | 16079219.94 | 0.00 | 57178988.47 | 57240695.56 | 0.152883E+10 | 0.346561E+11 | 0.00 | 0.81 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.425472E+10 | 0.00 | 0.00 | 168860.10 | 0.00 | 3606906.56 | 0.357268E+09 | 0.00 | 0.28 |
February | 0.352826E+10 | 0.00 | 0.00 | 414481.16 | 0.00 | 0.00 | 0.613932E+09 | 0.00 | 0.29 |
March | 0.292495E+10 | 0.00 | 0.00 | 2355990.37 | 0.00 | 0.00 | 0.215873E+10 | 0.00 | 0.35 |
April | 0.193759E+10 | 0.00 | 0.00 | 5908330.28 | 0.00 | 0.00 | 0.466428E+10 | 0.00 | 0.64 |
May | 0.173477E+10 | 0.00 | 0.00 | 5848540.42 | 0.00 | 0.00 | 0.446526E+10 | 0.00 | 0.61 |
June | 0.100572E+10 | 1008563.91 | 0.00 | 9609047.15 | 8620046.11 | 0.00 | 0.625238E+10 | 0.00 | 0.96 |
July | 0.133055E+10 | 4978951.65 | 0.00 | 10441377.40 | 1160776.50 | 0.00 | 0.595641E+10 | 0.00 | 1.08 |
August | 0.160340E+10 | 0.00 | 0.00 | 10886220.58 | 0.00 | 0.00 | 0.570788E+10 | 0.00 | 1.18 |
September | 0.184486E+10 | 0.00 | 0.00 | 5465381.38 | 0.00 | 0.00 | 0.350185E+10 | 0.00 | 0.75 |
October | 0.240766E+10 | 0.00 | 0.00 | 2799241.36 | 0.00 | 0.00 | 0.250475E+10 | 0.00 | 0.44 |
November | 0.304797E+10 | 0.00 | 0.00 | 1251128.48 | 0.00 | 0.00 | 0.134849E+10 | 0.00 | 0.32 |
December | 0.420312E+10 | 0.00 | 0.00 | 79021.42 | 0.00 | 0.00 | 0.235877E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.298236E+11 | 5987515.56 | 0.00 | 55227620.09 | 9780822.61 | 3606906.56 | 0.377671E+11 | 0.00 | 0.60 |
Minimum of Months | 0.100572E+10 | 0.00 | 0.00 | 79021.42 | 0.00 | 0.00 | 0.235877E+09 | 0.00 | 0.28 |
Maximum of Months | 0.425472E+10 | 4978951.65 | 0.00 | 10886220.58 | 8620046.11 | 3606906.56 | 0.625238E+10 | 0.00 | 1.18 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.383588E+10 | 0.00 | 0.00 | 171838.93 | 0.00 | 60884575.93 | 0.270260E+09 | 0.00 | 0.39 |
February | 0.331124E+10 | 0.00 | 0.00 | 544017.58 | 0.00 | 294090.31 | 0.477723E+09 | 0.00 | 0.41 |
March | 0.323375E+10 | 0.00 | 0.00 | 903836.22 | 0.00 | 0.00 | 0.114224E+10 | 0.00 | 0.46 |
April | 0.172873E+10 | 0.00 | 0.00 | 7381438.72 | 0.00 | 0.00 | 0.510930E+10 | 0.00 | 1.02 |
May | 0.139087E+10 | 0.00 | 0.00 | 7509614.26 | 0.00 | 0.00 | 0.518589E+10 | 0.00 | 1.01 |
June | 0.113782E+10 | 699374.87 | 0.00 | 9117241.31 | 7728531.73 | 0.00 | 0.559401E+10 | 0.00 | 1.40 |
July | 0.135673E+10 | 6166925.25 | 0.00 | 9603864.40 | 1045978.94 | 0.00 | 0.527626E+10 | 0.00 | 1.52 |
August | 0.167598E+10 | 0.00 | 0.00 | 10207660.12 | 0.00 | 0.00 | 0.524921E+10 | 0.00 | 1.71 |
September | 0.144404E+10 | 0.00 | 0.00 | 7447321.48 | 0.00 | 0.00 | 0.439996E+10 | 0.00 | 1.27 |
October | 0.250158E+10 | 0.00 | 0.00 | 2454759.74 | 0.00 | 0.00 | 0.209278E+10 | 0.00 | 0.64 |
November | 0.347294E+10 | 0.00 | 0.00 | 303408.77 | 0.00 | 0.00 | 0.444964E+09 | 0.00 | 0.45 |
December | 0.389367E+10 | 0.00 | 0.00 | 80581.83 | 0.00 | 1454126.65 | 0.104864E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.289832E+11 | 6866300.12 | 0.00 | 55725583.35 | 8774510.66 | 62632792.90 | 0.353475E+11 | 0.00 | 0.89 |
Minimum of Months | 0.113782E+10 | 0.00 | 0.00 | 80581.83 | 0.00 | 0.00 | 0.104864E+09 | 0.00 | 0.38 |
Maximum of Months | 0.389367E+10 | 6166925.25 | 0.00 | 10207660.12 | 7728531.73 | 60884575.93 | 0.559401E+10 | 0.00 | 1.71 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.453777E+10 | 0.00 | 0.00 | 2843379.34 | 0.00 | 0.118621E+09 | 0.225358E+10 | 0.00 | 0.43 |
February | 0.381380E+10 | 0.00 | 0.00 | 4157790.77 | 0.00 | 864181.59 | 0.297981E+10 | 0.00 | 0.48 |
March | 0.423236E+10 | 0.00 | 0.00 | 2893693.68 | 0.00 | 0.00 | 0.259028E+10 | 0.00 | 0.47 |
April | 0.231879E+10 | 0.00 | 0.00 | 13246895.36 | 0.00 | 0.00 | 0.900573E+10 | 0.00 | 1.15 |
May | 0.235913E+10 | 0.00 | 0.00 | 8985877.43 | 0.00 | 0.00 | 0.679099E+10 | 0.00 | 0.93 |
June | 0.184748E+10 | 1209344.82 | 0.00 | 11412792.25 | 11035937.31 | 0.00 | 0.731101E+10 | 0.00 | 1.25 |
July | 0.204292E+10 | 7165169.52 | 0.00 | 13776100.77 | 1493602.98 | 0.00 | 0.752394E+10 | 0.00 | 1.46 |
August | 0.217277E+10 | 0.00 | 0.00 | 18526692.32 | 0.00 | 0.00 | 0.879280E+10 | 0.00 | 1.85 |
September | 0.178608E+10 | 0.00 | 0.00 | 15616978.82 | 0.00 | 0.00 | 0.853790E+10 | 0.00 | 1.56 |
October | 0.308901E+10 | 0.00 | 0.00 | 7670150.53 | 0.00 | 0.00 | 0.588670E+10 | 0.00 | 0.85 |
November | 0.410501E+10 | 0.00 | 0.00 | 3088865.51 | 0.00 | 1048696.44 | 0.248070E+10 | 0.00 | 0.49 |
December | 0.480903E+10 | 0.00 | 0.00 | 1770936.29 | 0.00 | 20840987.59 | 0.146903E+10 | 0.00 | 0.39 |
Annual Sum or Average | 0.371141E+11 | 8374514.34 | 0.00 | 0.103990E+09 | 12529540.28 | 0.141375E+09 | 0.656225E+11 | 0.00 | 0.95 |
Minimum of Months | 0.178608E+10 | 0.00 | 0.00 | 1770936.29 | 0.00 | 0.00 | 0.146903E+10 | 0.00 | 0.39 |
Maximum of Months | 0.480903E+10 | 7165169.52 | 0.00 | 18526692.32 | 11035937.31 | 0.118621E+09 | 0.900573E+10 | 0.00 | 1.85 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.416417E+10 | 0.00 | 0.00 | 967287.04 | 0.00 | 0.00 | 0.112259E+10 | 0.00 | 0.50 |
February | 0.242770E+10 | 0.00 | 0.00 | 3355526.60 | 0.00 | 0.00 | 0.291505E+10 | 0.00 | 0.58 |
March | 0.951559E+09 | 0.00 | 0.00 | 7124812.77 | 0.00 | 0.00 | 0.594918E+10 | 0.00 | 0.74 |
April | 0.579624E+09 | 0.00 | 0.00 | 17259422.99 | 0.00 | 0.00 | 0.103068E+11 | 0.00 | 1.68 |
May | 0.997110E+09 | 0.00 | 0.00 | 10751870.83 | 0.00 | 0.00 | 0.724733E+10 | 0.00 | 1.30 |
June | 0.630159E+09 | 19807757.78 | 0.00 | 16361979.81 | 1739185.02 | 0.00 | 0.908952E+10 | 0.00 | 2.05 |
July | 0.823051E+09 | 10126698.38 | 0.00 | 20564809.12 | 280563.16 | 0.00 | 0.951796E+10 | 0.00 | 2.43 |
August | 0.932504E+09 | 0.00 | 0.00 | 23266444.33 | 0.00 | 0.00 | 0.100716E+11 | 0.00 | 2.79 |
September | 0.997795E+09 | 0.00 | 0.00 | 9629586.36 | 0.00 | 0.00 | 0.572499E+10 | 0.00 | 1.52 |
October | 0.133332E+10 | 0.00 | 0.00 | 6222363.26 | 0.00 | 0.00 | 0.508975E+10 | 0.00 | 0.92 |
November | 0.122147E+10 | 0.00 | 0.00 | 5145268.41 | 0.00 | 0.00 | 0.446580E+10 | 0.00 | 0.66 |
December | 0.162643E+10 | 0.00 | 0.00 | 4303836.98 | 0.00 | 0.00 | 0.390826E+10 | 0.00 | 0.54 |
Annual Sum or Average | 0.166849E+11 | 29934456.16 | 0.00 | 0.124953E+09 | 2019748.18 | 0.00 | 0.754088E+11 | 0.00 | 1.31 |
Minimum of Months | 0.579624E+09 | 0.00 | 0.00 | 967287.04 | 0.00 | 0.00 | 0.112259E+10 | 0.00 | 0.50 |
Maximum of Months | 0.416417E+10 | 19807757.78 | 0.00 | 23266444.33 | 1739185.02 | 0.00 | 0.103068E+11 | 0.00 | 2.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.292678E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160422E+11 | 0.00 | 0.00 | 0.28 |
February | 0.296328E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100733E+11 | 0.00 | 0.00 | 0.28 |
March | 0.412264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.360105E+10 | 0.00 | 0.00 | 0.31 |
April | 0.272195E+11 | 0.00 | 0.00 | 15725216.70 | 0.00 | 4080566.12 | 0.146763E+11 | 0.00 | 0.41 |
May | 0.265961E+11 | 0.00 | 0.00 | 23748027.81 | 0.00 | 11295513.48 | 0.192027E+11 | 0.00 | 0.46 |
June | 0.140022E+11 | 9086543.26 | 0.00 | 56597575.28 | 88349062.30 | 0.00 | 0.371335E+11 | 0.00 | 0.70 |
July | 0.133295E+11 | 55513408.39 | 0.00 | 60936278.46 | 16975346.17 | 0.00 | 0.351753E+11 | 0.00 | 0.75 |
August | 0.150807E+11 | 0.00 | 0.00 | 58655303.82 | 0.00 | 0.00 | 0.316873E+11 | 0.00 | 0.79 |
September | 0.235509E+11 | 0.00 | 0.00 | 27358526.96 | 0.00 | 0.00 | 0.170859E+11 | 0.00 | 0.58 |
October | 0.357366E+11 | 0.00 | 0.00 | 2059644.15 | 0.00 | 0.811192E+09 | 0.260847E+10 | 0.00 | 0.35 |
November | 0.321361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.749572E+10 | 0.00 | 0.00 | 0.30 |
December | 0.220743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216272E+11 | 0.00 | 0.00 | 0.28 |
Annual Sum or Average | 0.309853E+12 | 64599951.65 | 0.00 | 0.245081E+09 | 0.105324E+09 | 0.596660E+11 | 0.157569E+12 | 0.00 | 0.46 |
Minimum of Months | 0.133295E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.28 |
Maximum of Months | 0.412264E+11 | 55513408.39 | 0.00 | 60936278.46 | 88349062.30 | 0.216272E+11 | 0.371335E+11 | 0.00 | 0.79 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.298195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134270E+11 | 0.00 | 0.00 | 0.42 |
February | 0.302271E+11 | 0.00 | 0.00 | 212396.20 | 0.00 | 0.732242E+10 | 0.360968E+09 | 0.00 | 0.42 |
March | 0.391064E+11 | 0.00 | 0.00 | 103988.03 | 0.00 | 0.345366E+10 | 0.225334E+09 | 0.00 | 0.46 |
April | 0.150905E+11 | 0.00 | 0.00 | 58659251.68 | 0.00 | 8074531.06 | 0.399501E+11 | 0.00 | 0.85 |
May | 0.179209E+11 | 0.00 | 0.00 | 55492354.89 | 0.00 | 5275206.12 | 0.386259E+11 | 0.00 | 0.89 |
June | 0.114036E+11 | 6808906.34 | 0.00 | 76639418.80 | 84319090.76 | 0.00 | 0.469506E+11 | 0.00 | 1.25 |
July | 0.102520E+11 | 81350872.61 | 0.00 | 84506004.76 | 16201029.39 | 0.00 | 0.445154E+11 | 0.00 | 1.32 |
August | 0.110318E+11 | 0.00 | 0.00 | 89393437.00 | 0.00 | 0.00 | 0.461785E+11 | 0.00 | 1.49 |
September | 0.164965E+11 | 0.00 | 0.00 | 59995727.50 | 0.00 | 0.00 | 0.344787E+11 | 0.00 | 1.14 |
October | 0.293580E+11 | 0.00 | 0.00 | 11713125.16 | 0.00 | 0.871483E+09 | 0.941011E+10 | 0.00 | 0.56 |
November | 0.313684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.646594E+10 | 0.00 | 0.00 | 0.44 |
December | 0.217394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.199880E+11 | 0.00 | 0.00 | 0.42 |
Annual Sum or Average | 0.263814E+12 | 88159778.95 | 0.00 | 0.436716E+09 | 0.100520E+09 | 0.515418E+11 | 0.260696E+12 | 0.00 | 0.81 |
Minimum of Months | 0.102520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 0.391064E+11 | 81350872.61 | 0.00 | 89393437.00 | 84319090.76 | 0.199880E+11 | 0.469506E+11 | 0.00 | 1.49 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.432003E+11 | 0.00 | 0.00 | 20293989.23 | 0.00 | 0.856731E+10 | 0.165672E+11 | 0.00 | 0.43 |
February | 0.371472E+11 | 0.00 | 0.00 | 31463432.31 | 0.00 | 0.501973E+10 | 0.223951E+11 | 0.00 | 0.47 |
March | 0.487456E+11 | 0.00 | 0.00 | 12202513.39 | 0.00 | 0.231493E+10 | 0.115558E+11 | 0.00 | 0.43 |
April | 0.218251E+11 | 0.00 | 0.00 | 0.112796E+09 | 0.00 | 0.00 | 0.715743E+11 | 0.00 | 0.97 |
May | 0.277273E+11 | 0.00 | 0.00 | 70635001.47 | 0.00 | 47832542.59 | 0.532058E+11 | 0.00 | 0.84 |
June | 0.203537E+11 | 11445508.21 | 0.00 | 88264035.89 | 0.118535E+09 | 0.00 | 0.560487E+11 | 0.00 | 1.07 |
July | 0.167031E+11 | 0.102997E+09 | 0.00 | 0.109003E+09 | 22775272.37 | 0.00 | 0.589882E+11 | 0.00 | 1.21 |
August | 0.148944E+11 | 0.00 | 0.00 | 0.156590E+09 | 0.00 | 0.00 | 0.728676E+11 | 0.00 | 1.56 |
September | 0.181743E+11 | 0.00 | 0.00 | 0.154868E+09 | 0.00 | 0.00 | 0.785069E+11 | 0.00 | 1.52 |
October | 0.324461E+11 | 0.00 | 0.00 | 66714751.93 | 0.00 | 0.372257E+09 | 0.490021E+11 | 0.00 | 0.80 |
November | 0.401963E+11 | 0.00 | 0.00 | 17764289.77 | 0.00 | 0.470670E+10 | 0.139546E+11 | 0.00 | 0.44 |
December | 0.362108E+11 | 0.00 | 0.00 | 7702528.81 | 0.00 | 0.185637E+11 | 0.619084E+10 | 0.00 | 0.40 |
Annual Sum or Average | 0.357624E+12 | 0.114442E+09 | 0.00 | 0.848296E+09 | 0.141310E+09 | 0.395925E+11 | 0.510857E+12 | 0.00 | 0.85 |
Minimum of Months | 0.148944E+11 | 0.00 | 0.00 | 7702528.81 | 0.00 | 0.00 | 0.619084E+10 | 0.00 | 0.40 |
Maximum of Months | 0.487456E+11 | 0.102997E+09 | 0.00 | 0.156590E+09 | 0.118535E+09 | 0.185637E+11 | 0.785069E+11 | 0.00 | 1.56 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.352295E+11 | 0.00 | 0.00 | 559150.74 | 0.00 | 0.100489E+11 | 0.641273E+09 | 0.00 | 0.45 |
February | 0.330514E+11 | 0.00 | 0.00 | 4117969.89 | 0.00 | 0.427325E+10 | 0.366750E+10 | 0.00 | 0.45 |
March | 0.418326E+11 | 0.00 | 0.00 | 3122091.34 | 0.00 | 0.132331E+10 | 0.288376E+10 | 0.00 | 0.49 |
April | 0.207404E+11 | 0.00 | 0.00 | 52919221.25 | 0.00 | 0.00 | 0.341546E+11 | 0.00 | 0.87 |
May | 0.221959E+11 | 0.00 | 0.00 | 55955445.79 | 0.00 | 18512740.34 | 0.370721E+11 | 0.00 | 0.96 |
June | 0.118142E+11 | 0.194764E+09 | 0.00 | 88065574.45 | 10562202.54 | 0.00 | 0.502839E+11 | 0.00 | 1.37 |
July | 0.108449E+11 | 0.101316E+09 | 0.00 | 0.105253E+09 | 6821684.13 | 0.00 | 0.489805E+11 | 0.00 | 1.49 |
August | 0.105381E+11 | 0.00 | 0.00 | 97948770.85 | 0.00 | 0.00 | 0.455414E+11 | 0.00 | 1.50 |
September | 0.195813E+11 | 0.00 | 0.00 | 49441304.67 | 0.00 | 0.00 | 0.283939E+11 | 0.00 | 1.12 |
October | 0.338126E+11 | 0.00 | 0.00 | 10738177.04 | 0.00 | 0.122591E+09 | 0.921225E+10 | 0.00 | 0.62 |
November | 0.348176E+11 | 0.00 | 0.00 | 1076400.93 | 0.00 | 0.432744E+10 | 0.109594E+10 | 0.00 | 0.47 |
December | 0.289780E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152859E+11 | 0.00 | 0.00 | 0.45 |
Annual Sum or Average | 0.303436E+12 | 0.296079E+09 | 0.00 | 0.469197E+09 | 17383886.67 | 0.353999E+11 | 0.261927E+12 | 0.00 | 0.86 |
Minimum of Months | 0.105381E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.45 |
Maximum of Months | 0.418326E+11 | 0.194764E+09 | 0.00 | 0.105253E+09 | 10562202.54 | 0.152859E+11 | 0.502839E+11 | 0.00 | 1.50 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.949291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319521E+10 | 0.00 | 0.00 | 0.29 |
February | 0.129016E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239383E+10 | 0.00 | 0.00 | 0.29 |
March | 0.248106E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172641E+10 | 0.00 | 0.00 | 0.31 |
April | 0.285883E+10 | 0.00 | 0.00 | 719813.47 | 419985.91 | 0.368102E+09 | 0.754152E+09 | 0.00 | 0.39 |
May | 0.290652E+10 | 0.00 | 0.00 | 1552630.95 | 0.00 | 0.191047E+09 | 0.124199E+10 | 0.00 | 0.44 |
June | 0.177262E+10 | 177643.03 | 0.00 | 4535275.35 | 7187763.66 | 2763303.20 | 0.305092E+10 | 0.00 | 0.66 |
July | 0.141829E+10 | 2599525.16 | 0.00 | 5513019.70 | 725570.06 | 351348.35 | 0.327572E+10 | 0.00 | 0.72 |
August | 0.169436E+10 | 0.00 | 0.00 | 4785916.88 | 0.00 | 0.00 | 0.275904E+10 | 0.00 | 0.74 |
September | 0.240222E+10 | 0.00 | 0.00 | 1671546.51 | 0.00 | 88308333.37 | 0.115137E+10 | 0.00 | 0.53 |
October | 0.263262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.935385E+09 | 0.00 | 0.00 | 0.35 |
November | 0.144428E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214075E+10 | 0.00 | 0.00 | 0.30 |
December | 0.641564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333436E+10 | 0.00 | 0.00 | 0.29 |
Annual Sum or Average | 0.224918E+11 | 2777168.19 | 0.00 | 18778202.87 | 8333319.63 | 0.143765E+11 | 0.122332E+11 | 0.00 | 0.44 |
Minimum of Months | 0.641564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.29 |
Maximum of Months | 0.290652E+10 | 2599525.16 | 0.00 | 5513019.70 | 7187763.66 | 0.333436E+10 | 0.327572E+10 | 0.00 | 0.74 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.255085E+10 | 0.00 | 0.00 | 0.41 |
February | 0.149684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183173E+10 | 0.00 | 0.00 | 0.41 |
March | 0.252635E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130443E+10 | 0.00 | 0.00 | 0.44 |
April | 0.139187E+10 | 1237923.02 | 0.00 | 4428490.12 | 0.00 | 0.126875E+09 | 0.327611E+10 | 0.00 | 0.75 |
May | 0.182845E+10 | 0.00 | 0.00 | 4397860.43 | 0.00 | 82439581.80 | 0.320253E+10 | 0.00 | 0.82 |
June | 0.128991E+10 | 505210.69 | 0.00 | 7035144.51 | 6237971.68 | 462428.22 | 0.433196E+10 | 0.00 | 1.21 |
July | 0.934441E+09 | 5779620.43 | 0.00 | 8175172.05 | 662926.40 | 0.00 | 0.440645E+10 | 0.00 | 1.28 |
August | 0.101975E+10 | 0.00 | 0.00 | 8273735.32 | 0.00 | 0.00 | 0.451078E+10 | 0.00 | 1.43 |
September | 0.143646E+10 | 0.00 | 0.00 | 4937202.75 | 0.00 | 10482507.23 | 0.299946E+10 | 0.00 | 1.03 |
October | 0.205921E+10 | 0.00 | 0.00 | 628326.62 | 0.00 | 0.707056E+09 | 0.542801E+09 | 0.00 | 0.50 |
November | 0.152769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171893E+10 | 0.00 | 0.00 | 0.42 |
December | 0.775968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279039E+10 | 0.00 | 0.00 | 0.40 |
Annual Sum or Average | 0.174618E+11 | 7522754.14 | 0.00 | 37875931.80 | 6900898.09 | 0.111236E+11 | 0.232701E+11 | 0.00 | 0.76 |
Minimum of Months | 0.775968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.40 |
Maximum of Months | 0.252635E+10 | 5779620.43 | 0.00 | 8273735.32 | 6237971.68 | 0.279039E+10 | 0.451078E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259210E+10 | 0.00 | 0.00 | 891779.67 | 0.00 | 0.246058E+10 | 0.787735E+09 | 0.00 | 0.41 |
February | 0.259329E+10 | 0.00 | 0.00 | 1672592.22 | 0.00 | 0.169820E+10 | 0.125678E+10 | 0.00 | 0.44 |
March | 0.388994E+10 | 0.00 | 0.00 | 387551.68 | 0.00 | 0.158865E+10 | 0.349359E+09 | 0.00 | 0.44 |
April | 0.213903E+10 | 0.00 | 0.00 | 9350709.36 | 578746.66 | 0.281045E+09 | 0.633772E+10 | 0.00 | 0.90 |
May | 0.300584E+10 | 0.00 | 0.00 | 5884657.99 | 0.00 | 0.243805E+09 | 0.457691E+10 | 0.00 | 0.80 |
June | 0.236721E+10 | 710723.03 | 0.00 | 7922983.27 | 9408301.13 | 11477190.40 | 0.518956E+10 | 0.00 | 1.05 |
July | 0.170315E+10 | 2558907.88 | 0.00 | 10438069.06 | 2575093.64 | 0.00 | 0.596797E+10 | 0.00 | 1.20 |
August | 0.158933E+10 | 0.00 | 0.00 | 14222108.84 | 0.00 | 0.00 | 0.730862E+10 | 0.00 | 1.53 |
September | 0.184340E+10 | 0.00 | 0.00 | 13154504.48 | 0.00 | 676768.86 | 0.727236E+10 | 0.00 | 1.41 |
October | 0.273556E+10 | 0.00 | 0.00 | 4568340.16 | 0.00 | 0.712182E+09 | 0.352521E+10 | 0.00 | 0.70 |
November | 0.276000E+10 | 0.00 | 0.00 | 756382.13 | 0.00 | 0.173515E+10 | 0.615707E+09 | 0.00 | 0.43 |
December | 0.190158E+10 | 0.00 | 0.00 | 307806.61 | 0.00 | 0.326828E+10 | 0.238074E+09 | 0.00 | 0.40 |
Annual Sum or Average | 0.291204E+11 | 3269630.91 | 0.00 | 69557485.48 | 12562141.43 | 0.120000E+11 | 0.434260E+11 | 0.00 | 0.81 |
Minimum of Months | 0.158933E+10 | 0.00 | 0.00 | 307806.61 | 0.00 | 0.00 | 0.238074E+09 | 0.00 | 0.40 |
Maximum of Months | 0.388994E+10 | 2558907.88 | 0.00 | 14222108.84 | 9408301.13 | 0.326828E+10 | 0.730862E+10 | 0.00 | 1.53 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.191159E+10 | 0.00 | 0.00 | 8963.07 | 0.00 | 0.228168E+10 | 16480579.93 | 0.00 | 0.46 |
February | 0.220426E+10 | 0.00 | 0.00 | 160679.26 | 0.00 | 0.140653E+10 | 0.172924E+09 | 0.00 | 0.46 |
March | 0.328114E+10 | 0.00 | 0.00 | 137507.50 | 0.00 | 0.947993E+09 | 0.136389E+09 | 0.00 | 0.51 |
April | 0.241925E+10 | 0.00 | 0.00 | 4436208.12 | 436228.30 | 0.125024E+09 | 0.281390E+10 | 0.00 | 0.85 |
May | 0.244414E+10 | 0.00 | 0.00 | 4769041.26 | 0.00 | 97852027.32 | 0.326599E+10 | 0.00 | 0.93 |
June | 0.155663E+10 | 16126731.77 | 0.00 | 8059892.53 | 589562.66 | 224323.78 | 0.464102E+10 | 0.00 | 1.35 |
July | 0.112440E+10 | 4239193.30 | 0.00 | 10070191.37 | 177313.05 | 0.00 | 0.495066E+10 | 0.00 | 1.48 |
August | 0.125222E+10 | 0.00 | 0.00 | 8630660.85 | 0.00 | 0.00 | 0.435100E+10 | 0.00 | 1.47 |
September | 0.210223E+10 | 0.00 | 0.00 | 3954004.14 | 0.00 | 7323916.83 | 0.244190E+10 | 0.00 | 1.07 |
October | 0.273705E+10 | 0.00 | 0.00 | 730372.06 | 0.00 | 0.568635E+09 | 0.621531E+09 | 0.00 | 0.60 |
November | 0.225393E+10 | 0.00 | 0.00 | 17399.63 | 0.00 | 0.137411E+10 | 47435030.15 | 0.00 | 0.48 |
December | 0.131723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.270717E+10 | 0.00 | 0.00 | 0.46 |
Annual Sum or Average | 0.246041E+11 | 20365925.07 | 0.00 | 40974919.78 | 1203104.01 | 0.951655E+10 | 0.234592E+11 | 0.00 | 0.84 |
Minimum of Months | 0.112440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 0.328114E+10 | 16126731.77 | 0.00 | 10070191.37 | 589562.66 | 0.270717E+10 | 0.495066E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 2973733.42 | 0.00 | 0.00 | 0.637756E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 7332856.63 | 0.00 | 0.00 | 0.562101E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 12989157.99 | 0.00 | 0.00 | 0.623922E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 16938794.49 | 0.00 | 0.00 | 0.466955E+09 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 3860434.91 | 0.00 | 0.00 | 0.473145E+09 | 0.00 | 0.29 |
June | 0.00 | 105807.04 | 0.00 | 8305410.99 | 0.00 | 0.00 | 0.324835E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 12180832.18 | 0.00 | 0.00 | 0.231323E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 18054944.27 | 0.00 | 0.00 | 0.226661E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 3746041.82 | 0.00 | 0.00 | 0.313564E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 7880822.92 | 0.00 | 0.00 | 0.462543E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 11700228.44 | 0.00 | 0.00 | 0.530510E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 16144182.48 | 0.00 | 0.00 | 0.612628E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 105807.04 | 0.00 | 0.122107E+09 | 0.00 | 0.00 | 0.546594E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 2973733.42 | 0.00 | 0.00 | 0.226661E+09 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 105807.04 | 0.00 | 18054944.27 | 0.00 | 0.00 | 0.637756E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.103995E+09 | 0.00 | 0.00 | 15895949.88 | 0.00 | 0.00 | 0.628855E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 58748145.22 | 0.00 | 0.00 | 0.563506E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.112472E+09 | 0.00 | 0.00 | 0.625626E+10 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 0.157155E+09 | 0.00 | 0.00 | 0.468196E+10 | 0.00 | 0.29 |
May | 0.00 | 0.00 | 0.00 | 31838060.19 | 0.00 | 0.00 | 0.474079E+10 | 0.00 | 0.29 |
June | 0.00 | 971287.87 | 0.00 | 76547871.24 | 0.00 | 0.00 | 0.325857E+10 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 0.114341E+09 | 0.00 | 0.00 | 0.232213E+10 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 0.170677E+09 | 0.00 | 0.00 | 0.227653E+10 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 31547412.27 | 0.00 | 0.00 | 0.315517E+10 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 66351198.78 | 0.00 | 0.00 | 0.464044E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 99319653.13 | 0.00 | 0.00 | 0.532226E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.137660E+09 | 0.00 | 0.00 | 0.614872E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.103995E+09 | 971287.87 | 0.00 | 0.107255E+10 | 0.00 | 0.00 | 0.547264E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 15895949.88 | 0.00 | 0.00 | 0.227653E+10 | 0.00 | 0.28 |
Maximum of Months | 0.103995E+09 | 971287.87 | 0.00 | 0.170677E+09 | 0.00 | 0.00 | 0.628855E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.264579E+09 | 0.00 | 0.00 | 537194.08 | 0.00 | 0.00 | 0.369508E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 4709894.85 | 0.00 | 0.00 | 0.564755E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 10061636.01 | 0.00 | 0.00 | 0.626837E+09 | 0.00 | 0.30 |
April | 0.00 | 0.00 | 0.00 | 15139534.74 | 0.00 | 0.00 | 0.468767E+09 | 0.00 | 0.29 |
May | 3528139.06 | 0.00 | 0.00 | 2700658.73 | 0.00 | 0.00 | 0.471276E+09 | 0.00 | 0.29 |
June | 0.00 | 100866.72 | 0.00 | 7437406.01 | 0.00 | 0.00 | 0.326349E+09 | 0.00 | 0.30 |
July | 0.00 | 0.00 | 0.00 | 11296537.56 | 0.00 | 0.00 | 0.232532E+09 | 0.00 | 0.28 |
August | 0.00 | 0.00 | 0.00 | 16893331.62 | 0.00 | 0.00 | 0.228014E+09 | 0.00 | 0.31 |
September | 0.00 | 0.00 | 0.00 | 2726251.88 | 0.00 | 0.00 | 0.317023E+09 | 0.00 | 0.29 |
October | 0.00 | 0.00 | 0.00 | 5609646.33 | 0.00 | 0.00 | 0.465841E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 8755470.16 | 0.00 | 0.00 | 0.533709E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 12614876.79 | 0.00 | 0.00 | 0.616069E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.268107E+09 | 100866.72 | 0.00 | 98482438.76 | 0.00 | 0.00 | 0.522068E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 537194.08 | 0.00 | 0.00 | 0.228014E+09 | 0.00 | 0.28 |
Maximum of Months | 0.264579E+09 | 100866.72 | 0.00 | 16893331.62 | 0.00 | 0.00 | 0.626837E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.206978E+09 | 0.00 | 0.00 | 0.147251E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.398499E+09 | 0.00 | 0.00 | 0.126161E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.667989E+09 | 0.00 | 0.00 | 0.139634E+11 | 0.00 | 0.34 |
April | 0.00 | 0.00 | 0.00 | 0.844512E+09 | 0.00 | 0.00 | 0.102486E+11 | 0.00 | 0.32 |
May | 0.00 | 0.00 | 0.00 | 0.213494E+09 | 0.00 | 0.00 | 0.102034E+11 | 0.00 | 0.33 |
June | 0.00 | 5418795.08 | 0.00 | 0.416146E+09 | 0.00 | 0.00 | 0.672701E+10 | 0.00 | 0.34 |
July | 0.00 | 29607.45 | 0.00 | 0.601721E+09 | 0.00 | 0.00 | 0.461536E+10 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.00 | 0.892721E+09 | 0.00 | 0.00 | 0.439902E+10 | 0.00 | 0.34 |
September | 0.00 | 0.00 | 0.00 | 0.207459E+09 | 0.00 | 0.00 | 0.654550E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.416953E+09 | 0.00 | 0.00 | 0.989895E+10 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.605965E+09 | 0.00 | 0.00 | 0.115649E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.829642E+09 | 0.00 | 0.00 | 0.137287E+11 | 0.00 | 0.31 |
Annual Sum or Average | 0.00 | 5448402.53 | 0.00 | 0.630208E+10 | 0.00 | 0.00 | 0.119236E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.206978E+09 | 0.00 | 0.00 | 0.439902E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 5418795.08 | 0.00 | 0.892721E+09 | 0.00 | 0.00 | 0.147251E+11 | 0.00 | 0.34 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:36
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.159619E+12 | 0.658698E+10 | 0.00 | 0.179343E+13 | 0.528169E+12 |
February | 0.253147E+12 | 0.938674E+10 | 0.00 | 0.163069E+13 | 0.820980E+12 |
March | 0.298584E+12 | 0.586348E+10 | 0.00 | 0.189682E+13 | 0.129753E+13 |
April | 0.757965E+12 | 0.729872E+10 | 0.00 | 0.210092E+13 | 0.169816E+13 |
May | 0.934979E+12 | 0.173986E+11 | 0.00 | 0.208434E+13 | 0.587815E+12 |
June | 0.935968E+12 | 0.137008E+11 | 0.00 | 0.207011E+13 | 0.115459E+13 |
July | 0.943790E+12 | 0.130558E+11 | 0.00 | 0.207193E+13 | 0.173494E+13 |
August | 0.774457E+12 | 0.969966E+10 | 0.00 | 0.201100E+13 | 0.221996E+13 |
September | 0.578318E+12 | 0.103577E+11 | 0.00 | 0.212343E+13 | 0.771640E+12 |
October | 0.272783E+12 | 0.101215E+11 | 0.00 | 0.195363E+13 | 0.918371E+12 |
November | 0.127867E+12 | 0.122675E+11 | 0.00 | 0.177598E+13 | 0.125840E+13 |
December | 0.681897E+11 | 0.165760E+11 | 0.00 | 0.166119E+13 | 0.170001E+13 |
Annual Sum or Average | 0.610567E+13 | 0.132313E+12 | 0.00 | 0.231735E+14 | 0.146906E+14 |
Minimum of Months | 0.681897E+11 | 0.586348E+10 | 0.00 | 0.163069E+13 | 0.528169E+12 |
Maximum of Months | 0.943790E+12 | 0.173986E+11 | 0.00 | 0.212343E+13 | 0.221996E+13 |