Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2023-10-16 09:04:27


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 32341.82 698.22 698.22
Net Site Energy 32341.82 698.22 698.22
Total Source Energy 90002.44 1943.04 1943.04
Net Source Energy 90002.44 1943.04 1943.04


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 5099.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2538.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2786.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 455.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1914.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2303.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 337.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 542.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1141.13
Humidification 228.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.13
Heat Recovery 57.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 865.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 26377.30 5964.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3506.43
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 5099.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 2538.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2786.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 455.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 59.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2303.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 337.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 542.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1141.13
Humidification General 228.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.13
Heat Recovery General 57.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 865.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 5099.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 2538.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2786.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 455.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1914.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2303.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 337.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 542.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1141.13
Humidification Unassigned 228.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 85.13
Heat Recovery Unassigned 57.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 865.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 69.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 128.46 128.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08
Other 371.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 569.45 128.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 69.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 128.46 128.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08
Other 371.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 569.45 128.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.08


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 26377.296 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 26377.296 100.00
     
Total On-Site and Utility Electric Sources 26377.296 100.00
Total Electricity End Uses 26377.296 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1.77 0.05
Air to Air Heat Recovery for Heating 3881.85 99.95
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 3883.62 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 3506.43 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 3506.43 100.00
Total Water End Uses 3506.43 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 273.83
Time Setpoint Not Met During Occupied Cooling 83.83
Time Not Comfortable Based on Simple ASHRAE 55-2004 5910.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
RunPeriod RUNPERIOD 1
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [m] 133.00
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 7.6202 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 7.6202 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 7.6202 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 7.6202 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 7.6202 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 7.6202 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 7.6202 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 7.6202 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 12.5114 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 12.5114 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 12.5114 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 7.6202 18.58 484.4232  
Total 46320.38             7.6661 9.29 17.8789  
Conditioned Total 46320.38             7.6661 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.3561 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 11-AUG-15:39 27-FEB-07:19 - - - - - - - - - - 20-JUL-15:09
Heating 0.00 2627511.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 335376.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 83146.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 249103.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 51515.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 51417.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 6524.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 31331.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1805522.45 2658842.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 2627511.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 335376.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3711.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 249103.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 51515.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 51417.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 6524.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 31331.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 5527.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8040.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8824.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1442.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6062.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7293.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1068.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1717.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 724.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 181.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 938.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 83536.90 6465.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 119.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 173.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 190.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 157.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 23.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 37.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 15.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 20.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1803.46 139.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 119.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 173.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 190.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 31.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 157.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 23.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 37.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 15.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 3.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 20.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1803.46 139.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.34
DATACENTER_BOT_ZN_6 DIRECT AIR 0.511014
DATACENTER_MID_ZN_6 DIRECT AIR 4.91
DATACENTER_TOP_ZN_6 DIRECT AIR 0.495707
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.68
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.74 0.331418 0.334000 1.92 0.883781 0.500000 0.001150 0.000273 1.92 12.80 0.008000
CORE_MID VAV BOX COMPONENT 53.98 0.352361 0.348000 18.79 0.939629 0.500000 0.001081 0.004557 18.79 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.29 0.359289 0.362000 1.92 0.958104 0.500000 0.001060 0.001055 3.65 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.932869 0.256006 0.258000 0.240680 0.682684 0.500000 0.001488 0.000182 0.631041 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 1.23 0.125116 0.200000 0.246019 0.333644 0.500000 0.003045 0.000125 0.433051 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.88 0.126721 0.200000 0.376933 0.337922 0.500000 0.003007 0.000196 0.680086 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.46 0.105423 0.200000 0.291977 0.300000 0.500000 0.003614 0.000101 0.350669 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.57 0.278772 0.276000 2.36 0.743392 0.500000 0.001367 0.002386 8.27 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 12.98 0.118530 0.200000 2.60 0.316081 0.500000 0.003214 0.001583 5.48 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 19.78 0.120744 0.200000 3.96 0.321984 0.500000 0.003155 0.002371 8.21 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 13.27 0.116013 0.200000 2.65 0.309369 0.500000 0.003284 0.001520 5.26 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 1.12 0.212617 0.272000 0.305522 0.566979 0.500000 0.001792 0.000324 1.12 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 1.29 0.119043 0.200000 0.258570 0.317449 0.500000 0.003201 0.000214 0.740531 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 2.05 0.116400 0.200000 0.410352 0.310401 0.500000 0.003273 0.000322 1.12 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.38 0.111905 0.200000 0.275063 0.300000 0.500000 0.003405 0.000210 0.726739 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 31172.07 0.000273 670.83
CORE_MID VAV BOX REHEAT COIL 520844.41 0.004557 12809.01
CORE_TOP VAV BOX REHEAT COIL 120587.92 0.001055 3182.02
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 20833.58 0.000182 549.51
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 14295.06 0.000125 377.03
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 22449.41 0.000196 592.09
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 11581.48 0.000101 305.53
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 272765.95 0.002386 7192.83
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 180956.04 0.001583 4771.70
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 271050.32 0.002371 7147.62
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 173723.64 0.001520 4581.12
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 37048.14 0.000324 976.77
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 24424.45 0.000214 643.94
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 36819.49 0.000322 970.74
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 23969.97 0.000210 631.96
VAV_BOT WITH REHEAT HEATING COIL 162916.74 0.001425 2165.47
VAV_MID WITH REHEAT HEATING COIL 1646683.49 0.014406 21341.14
VAV_TOP WITH REHEAT HEATING COIL 164484.67 0.001439 2174.89
CAV_BAS HEATING COIL 314275.84 0.002749 6455.75
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 5.62 3.07 11.25 3.17 9.43 9.43 0.300000 0.336482 9.43
VAV_MID WITH REHEAT 54.29 30.36 108.58 41.60 87.88 87.88 0.300000 0.473329 87.88
VAV_TOP WITH REHEAT 5.57 3.17 11.14 7.36 9.36 9.36 0.300000 0.785864 9.36
CAV_BAS 5.34 5.34 5.34 5.34 5.34 5.34 1.00 1.00 5.34
AIRLOOP DATACENTER BASEMENT 21.68 21.68 21.68 21.68 21.68 21.68 1.00 0.999995 21.68
AIRLOOP DATACENTER BOT 0.511014 0.511014 0.511014 0.511014 0.511014 0.511014 1.00 1.00 0.511014
AIRLOOP DATACENTER MID 4.91 4.91 4.91 4.91 4.91 4.91 1.00 1.00 4.91
AIRLOOP DATACENTER TOP 0.495707 0.495707 0.495707 0.495707 0.495707 0.495707 1.00 1.00 0.495707
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 9.43  
VAV_MID WITH REHEAT_OA_CONTROLLER 87.88  
VAV_TOP WITH REHEAT_OA_CONTROLLER 9.36  
CAV_BAS_OA_CONTROLLER 5.34 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.68 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.511014 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.91 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.495707 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
CAV_BAS OA HEAT RECOVERY 1.20
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 24.93 6.67 10.91 0.007248 0.007000 166551.84 0.007086 9.43
VAV_MID WITH REHEAT COOLING COIL 25.01 6.67 10.91 0.007260 0.007000 1564103.86 0.066541 87.88
VAV_TOP WITH REHEAT COOLING COIL 24.92 6.67 10.91 0.007247 0.007000 165272.27 0.007031 9.36
CAV_BAS COOLING COIL 24.73 6.67 11.40 0.007395 0.007000 92269.25 0.003925 5.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 9.43
VAV_MID WITH REHEAT FAN 87.88
VAV_TOP WITH REHEAT FAN 9.36
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.007086 0.000067
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.001425  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.066541 0.000007
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.014406  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.007031 0.000068
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.001439  
CAV_BAS_COOLC_CONTROLLER 0.003925 0.000121
CAV_BAS_HEATC_CONTROLLER 0.002749  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.68 442331.78 280364.99 0.010833
AIRLOOP DATACENTER BOT COOLING COIL 0.511014 10140.98 6499.66 0.000248
AIRLOOP DATACENTER MID COOLING COIL 4.91 97427.63 62437.55 0.002386
AIRLOOP DATACENTER TOP COOLING COIL 0.495707 9838.12 6305.00 0.000241
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.68 21.68 21.68 21.68 442331.78 442331.78 33013.32 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.511014 0.511014 0.511014 0.511014 10140.98 10140.98 1525.08 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.91 4.91 4.91 4.91 97427.63 97427.63 15250.79 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.495707 0.495707 0.495707 0.495707 9838.12 9838.12 1525.08 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.68
AIRLOOP DATACENTER BOT SUPPLY FAN 0.511014
AIRLOOP DATACENTER MID SUPPLY FAN 4.91
AIRLOOP DATACENTER TOP SUPPLY FAN 0.495707
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.68 442331.78 0.010833
AIRLOOP DATACENTER BOT HEATING COIL 0.511014 10140.98 0.000248
AIRLOOP DATACENTER MID HEATING COIL 4.91 97427.63 0.002386
AIRLOOP DATACENTER TOP HEATING COIL 0.495707 9838.12 0.000241
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 33013.32
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 1525.08
AIRLOOP DATACENTER MID_SUPPHEATCOIL 15250.79
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 1525.08
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000197 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.084583 17429.32  
HEATSYS1 PUMP 0.035439 10672.64 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.084583 10.15
HEATSYS1 0.035439 4.25
COOLSYS1_SUPPLY 0.084583 10.15
SINGLE WATER PLANT LOOP 0.013708 1.64
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.084583 0.084583 355035.22 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 4050882.66 4050882.66 0.035439
CENTRAL BOILER 564650.44 553720.47 0.013708
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.084583 12066.91
PLANT CIRC PUMP 0.013708 3496.22
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.084583 0.042564 1001633.26 1007729.23 0.051090
COOLSYS1 CHILLER2 0.084583 0.042564 1001633.26 1007729.23 0.051090
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013708 139666.47 57722.85 69833.23 7879.72 21257.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.102179 12.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.102179 30774.23
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 39.15 1197132.82 7.83 149641.60
TOWERWATERSYS COOLTOWER 2 39.15 1197132.82 7.83 149641.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.051798
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 -3.10 -17.70 -19.30 -17.60 -15.40 -10.30 0.70 10.60 16.00 16.90 14.20 6.70


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 64.82 -147.85 -9.00 133.00 99737 1.1854


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA -1.53 36.20 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 7.620 4.842 0.000 0.000 0.000 0.000 12.462 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 7.620 484.423 0.000 0.000 0.000 0.000 492.043 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 21179.739 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 21179.739
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5971.780 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5971.780
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 2.101 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.1625 0.900 0.900 0.700 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.002 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 0.9296 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 1.327 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.3542 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.4760
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 6.093
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.8307
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.9084
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.5862
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 2.747
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 2.747
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 2.747
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 2.747
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 2.747
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 2.747
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 2.1009573 2.1009573 2.1009573  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.63083111E-06 0.74112372E-09 -0.38647046E-05 0.15329585E-16
47 2 0.78415922 0.99752939E-03 1.0633801 -0.74093433E-06
48 1 -22.010056 0.66447931E-01 -6.3131541 0.20386814
49 0 21.355302 0.61958938E-01 5.3791822  
50 9 -0.33543647E-15 0.37175517E-16 -0.14631797E-09 0.12118624E-17
51 8 0.21396566E-07 0.13443687E-12 0.37275451E-03 -0.24328632E-09
52 7 -0.12091173E-01 0.70158236E-08 -0.22869277E-01 0.13748104E-03
53 6 0.40126415 0.24497036E-05 0.46860994 -0.46995957E-02
54 5 -5.1506864 0.91758480E-04 -4.4145205 0.62689390E-01
55 4 32.826465 0.75276522E-03 21.335811 -0.41978091
56 3 -110.85094 0.16448005E-02 -55.417368 1.5097726
57 2 196.75927 0.92731797E-03 77.685319 -2.8948114
58 1 -171.02718 0.99203986E-04 -55.199609 2.7431803
59 0 57.057407 0.56605462E-06 15.567773  
60 9 -0.28960779E-14 0.35098193E-16 -0.14971922E-09 0.47215659E-16
61 8 0.21874741E-07 0.12520865E-12 0.37779602E-03 -0.24872334E-09
62 7 -0.12241669E-01 0.65002252E-08 -0.23085984E-01 0.13919224E-03
63 6 0.40535349 0.22649272E-05 0.47209413 -0.47477991E-02
64 5 -5.1905946 0.84684606E-04 -4.4412874 0.63184232E-01
65 4 33.002996 0.69360465E-03 21.440451 -0.42212474
66 3 -111.22654 0.15133424E-02 -55.624249 1.5151992
67 2 197.13156 0.85210513E-03 77.875032 -2.9007233
68 1 -171.16470 0.91049108E-04 -55.254723 2.7455905
69 0 57.057407 0.51888301E-06 15.558627  
70 9 0.91129428E-15 0.43215878E-16 -0.13089627E-09 -0.20490080E-17
71 8 0.19220221E-07 0.17438783E-12 0.34930596E-03 -0.21854054E-09
72 7 -0.11389480E-01 0.93361245E-08 -0.21858301E-01 0.12950253E-03
73 6 0.38219501 0.32933165E-05 0.45231959 -0.44748175E-02
74 5 -4.9645592 0.12444350E-03 -4.2891815 0.60381528E-01
75 4 32.002960 0.10289719E-02 20.845393 -0.40884736
76 3 -109.09821 0.22640533E-02 -54.447585 1.4844515
77 2 195.02141 0.12843697E-02 76.796791 -2.8672153
78 1 -170.38497 0.13818870E-03 -54.942931 2.7319248
79 0 57.057407 0.79338380E-06 15.611548  
80 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
81 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
82 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
83 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
84 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
85 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
86 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
87 0 0.36311555 0.17917760E-04 60.838472  
88 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
89 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
90 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
91 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
92 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
93 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
94 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
95 0 0.36311555 0.17917760E-04 60.838472  
96 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
97 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
98 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
99 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
100 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
101 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
102 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
103 0 0.36311555 0.17917760E-04 60.838472  
104 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
105 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
106 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
107 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
108 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
109 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
110 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
111 0 0.36311555 0.17917760E-04 60.838472  
112 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
113 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
114 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
115 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
116 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
117 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
118 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
119 0 0.36311555 0.17917760E-04 60.838472  
120 7 -0.11729247E-08 -0.12287178E-15 0.68000855E-14 -0.85819789E-16
121 6 0.99010087E-05 0.68275672E-08 0.31776201E-02 -0.26656541E-04
122 5 -0.71743827E-03 0.40498262E-05 -0.22302824 0.19500041E-02
123 4 0.16534150E-01 0.18445051E-03 4.8179460 -0.45153479E-01
124 3 -0.14527752 0.14677644E-02 -37.955880 0.39792938
125 2 0.51595076 0.24428280E-02 116.35639 -1.4162330
126 1 -0.74475336 0.74501918E-03 -143.83221 2.0478056
127 0 0.36311555 0.17917760E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.2925_SHGC_EAST_0.45 35 1 VerySmooth 1.661 1.661 1.000 0.451    
2 WINDOW_U_0.2925_SHGC_SOUTH_0.45 36 1 VerySmooth 1.661 1.661 1.000 0.451    
3 WINDOW_U_0.2925_SHGC_WEST_0.45 37 1 VerySmooth 1.661 1.661 1.000 0.451    
4 WINDOW_U_0.2925_SHGC_NORTH_0.45 38 1 VerySmooth 1.661 1.661 1.000 0.451    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   4.24435E-002 0.36619 0.44086 0.44086 0.45000 0.13324 0.16828 0.00000 0.84000 0.84000 9.92517E-002 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   4.24435E-002 0.36619 0.44086 0.44086 0.45000 0.13324 0.16828 0.00000 0.84000 0.84000 9.92517E-002 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   4.24435E-002 0.36619 0.44086 0.44086 0.45000 0.13324 0.16828 0.00000 0.84000 0.84000 9.92517E-002 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   4.24435E-002 0.36619 0.44086 0.44086 0.45000 0.13324 0.16828 0.00000 0.84000 0.84000 9.92517E-002 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.7271E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.7298E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.9152E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9176E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.4650E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.4664E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2272E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2280E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.7878E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.9550E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.9685E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.1202E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5019E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6058E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2498E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3065E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1235
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.0288E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 0.1420
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 0.1090
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.4936E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.7218E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 4.6760E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.6376E-002
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.8102E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.0812E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.9956E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 8.2728E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.5138E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.6506E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2504E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.3082E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 6.7270E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 6.7306E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.9151E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 7.9186E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 3.4649E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.4669E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.2271E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2279E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.6591E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 7.7929E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.9735E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 8.4843E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8269E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.9723E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8114E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8505E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 7.7924E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.3035E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 8.1275E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.4555E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.5458E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8313E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.8092E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.7944E-002
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.3608E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.5001E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 6.5513E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 6.6598E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 4.7886E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 4.8314E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.8116E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 3.8512E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8543E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8573E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4433E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4460E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9944E-003
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9960E-003
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2272E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2280E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9196E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0787E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.5023E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6412E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0356E-003
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.1293E-003
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2504E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3083E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 5.1950E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.9822E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.1602E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3568E-002
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 3.7460E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.4513E-002
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 4.6760E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.6371E-002
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.9164E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 3.0885E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4950E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.6345E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.0255E-003
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.0970E-003
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2499E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.3066E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.8541E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.8569E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.4431E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.4454E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.9942E-003
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.9954E-003
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.2271E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 2.2279E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.9787E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.1332E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.5999E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.7171E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.1495E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.1837E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8116E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8512E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.5891E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.0994E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.0322E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.7579E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.2903E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2567E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.8092E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.7944E-002
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 5.0999E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.4215E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.7747E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 5.1426E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 4.1820E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 4.2924E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 3.8114E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 3.8505E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1377
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1172
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 0.1577
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 0.1405
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 9.4080E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 5.2040E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 5.4054E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 2.6152E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 8.8632E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 5.8461E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 9.2396E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 6.1047E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 7.3885E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 3.8945E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 5.5299E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.6428E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 6.0185E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 4.1822E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.9030E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 3.3934E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 4.4540E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.3347E-002
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 5.4054E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 2.6147E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.4470E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 4.2225E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.8438E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.8140E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 6.0419E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 3.1794E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 5.5299E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 2.6428E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1373
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1172
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 0.1573
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 0.1404
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 9.4074E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 5.2122E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 5.4117E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 2.6202E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 8.8511E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 5.8500E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 9.2265E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 6.1089E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 7.3896E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 3.9008E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 5.5358E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.6479E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 6.0103E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 4.1841E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.8968E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 3.3950E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 4.4567E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.3384E-002
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 5.4117E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 2.6197E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.4398E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 4.2252E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.8376E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.8165E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 6.0437E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 3.1845E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 5.5358E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 2.6479E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 72811.09182 72811.09182 5.33862 5.33862 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:10:00 -41.90000 6.45023E-005 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 78271.65433 78271.65433 5.73911 5.73911 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 12171.71979 12171.71979 0.52031 1.07782 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 736392.25862 736392.25862 53.98002 53.98002 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 334643.07043 334643.07043 14.36900 14.36900 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 72223.01078 72223.01078 5.29391 5.29391 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 19.85200 6.99585E-003 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 84416.72780 84416.72780 3.64915 3.64915 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12605.47805 12605.47805 0.93287 0.93287 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38200 6.99811E-003 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 14579.08646 14579.08646 0.63104 0.63104 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 16621.93760 16621.93760 1.23009 1.23009 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 21.79000 6.99871E-003 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 10002.89642 10002.89642 0.43305 0.43305 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 25466.92448 25466.92448 1.88466 1.88466 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 27.40000 7.00714E-003 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 15708.74082 15708.74082 0.68009 0.68009 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 19727.05460 19727.05460 1.45988 1.45988 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.69700 7.00305E-003 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 8106.01622 8106.01622 0.35067 0.35067 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 115760.91520 115760.91520 8.56687 8.56687 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:10:00 21.22900 6.99788E-003 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 190839.55490 190839.55490 8.26630 8.26630 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 175455.58996 175455.58996 12.98444 12.98444 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 22.36800 6.99957E-003 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 126602.55877 126602.55877 5.48422 5.48422 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 267275.96169 267275.96169 19.77955 19.77955 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 27.40000 7.00714E-003 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 189640.17244 189640.17244 8.21422 8.21422 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 179262.40319 179262.40319 13.26616 13.26616 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.44200 7.00266E-003 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 121546.11285 121546.11285 5.26470 5.26470 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 11955.84832 11955.84832 0.88479 0.88479 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 21.38200 6.99811E-003 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 25915.73297 25915.73297 1.12324 1.12324 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 17469.97014 17469.97014 1.29285 1.29285 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 22.65700 7.00000E-003 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 17085.08181 17085.08181 0.74053 0.74053 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 27724.96382 27724.96382 2.05176 2.05176 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 27.40000 7.00714E-003 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 25755.88013 25755.88013 1.11630 1.11630 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 18584.31881 18584.31881 1.37531 1.37531 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.44200 7.00266E-003 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 16767.30697 16767.30697 0.72674 0.72674 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 -41.90000 6.45023E-005 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8754.65897 8754.65897 0.51101 0.51101 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 21.84100 6.99878E-003 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -41.90000 6.45023E-005 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 84099.16479 84099.16479 4.90893 4.90893 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 21.99400 6.99901E-003 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 -41.90000 6.45023E-005 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 8492.39249 8492.39249 0.49571 0.49571 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 21.99400 6.99901E-003 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 -41.90000 6.45023E-005 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 371391.66349 371391.66349 21.67808 21.67808 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 18.11800 6.99333E-003 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:00:00 -41.90000 6.45023E-005 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 134534.19 9.42896 9.42896 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 165086.38 3.17267 3.17267 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:50:00
3 VAV_MID WITH REHEAT Cooling Sensible 1244465.14 87.88480 87.88480 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 1644657.81 41.59845 41.59845 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:10:00
5 VAV_TOP WITH REHEAT Cooling Sensible 134720.74 9.36036 9.36036 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 164818.52 7.35597 7.35597 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:00:00
7 CAV_BAS Cooling Sensible 67318.37 5.33862 5.33862 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CAV_BAS Heating Sensible 117086.28 1.20016 1.20016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 366333.60 21.67820 21.67820 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 33013.32 0.33839 0.33839 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8549.49 0.51101 0.51101 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 1525.08 1.56323E-002 1.56323E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 82093.66 4.90893 4.90893 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 15250.79 0.15632 0.15632 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 8290.79 0.49571 0.49571 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 1525.08 1.56323E-002 1.56323E-002 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.33862
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.73911
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33142
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33400
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.91686
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.88378
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.14961E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.72707E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.91686
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 31172.06647
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.72707E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 670.83491
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 53.98002
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35236
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34800
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 18.78505
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.93963
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.08128E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.55657E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 18.78505
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 520844.41034
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.55657E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 12809.01208
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.29391
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.35929
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.36200
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.91639
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.95810
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.06043E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.05496E-003
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 3.64915
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 120587.91882
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.05496E-003
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3182.01973
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.93287
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.25601
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.25800
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24068
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.68268
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.48824E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.82261E-004
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.63104
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 20833.58449
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.82261E-004
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 549.51247
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.23009
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12512
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.24602
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33364
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.04516E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.25059E-004
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.43305
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 14295.05707
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.25059E-004
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 377.02694
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.88466
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12672
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.37693
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.33792
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.00661E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.96397E-004
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.68009
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 22449.41369
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.96397E-004
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 592.09134
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.45988
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.10542
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.29198
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.61402E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.01320E-004
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.35067
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 11581.47547
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.01320E-004
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 305.52793
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.56687
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.27877
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27600
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.36446
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.74339
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.36671E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.38628E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.26630
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 272765.94526
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.38628E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7192.82817
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 12.98444
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11853
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.59689
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31608
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.21437E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.58308E-003
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.48422
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 180956.04420
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.58308E-003
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4771.69958
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 19.77955
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12074
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 3.95591
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.32198
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.15544E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.37127E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 8.21422
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 271050.32103
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.37127E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 7147.62243
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 13.26616
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11601
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.65323
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30937
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.28411E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.51981E-003
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 5.26470
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 173723.64455
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.51981E-003
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 4581.11645
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.12324
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21262
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27200
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.30552
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.56698
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.79195E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.24113E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.12324
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 37048.13843
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.24113E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 976.76736
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.29285
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11904
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.25857
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31745
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.20052E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.13676E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.74053
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 24424.44777
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.13676E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 643.93797
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 2.05176
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11640
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.41035
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.31040
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.27319E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.22113E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.11630
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 36819.48809
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.22113E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 970.74243
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.37531
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.11191
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.27506
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.30000
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 3.40466E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 2.09700E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.72674
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 23969.96536
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 2.09700E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 631.96074
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.51101
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.90893
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.49571
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.67808
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.62331
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.07247
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.24662
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.17267
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.42896
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.42896
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.33648
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 54.28852
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 30.35553
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 108.57704
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 41.59845
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 87.88480
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 87.88480
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.47333
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.56854
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 3.16590
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 11.13707
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 7.35597
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 9.36036
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 9.36036
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.78586
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.33862
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.33862
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.33862
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.33862
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.33862
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.33862
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.67808
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.67808
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.67808
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.67808
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.67820
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.67820
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.51101
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.51101
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.51101
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.51101
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.51101
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.51101
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.90893
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.90893
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.90893
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.90893
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.90893
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.90893
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.49571
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.49571
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.49571
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.49571
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.49571
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.49571
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.42896
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 87.88480
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 9.36036
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.33862
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.67820
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.51101
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.90893
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.49571
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.42896
289 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 24.92567
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90817
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.24848E-003
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 166551.83534
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.08550E-003
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.42896
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 162916.73589
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.42527E-003
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2165.46590
301 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.42896
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.08550E-003
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.72063E-005
304 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.42527E-003
305 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 87.88480
306 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 25.00757
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90821
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.25991E-003
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 1564103.86354
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 6.65406E-002
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 87.88480
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 1646683.49092
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.44059E-002
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 21341.13708
318 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 87.88480
319 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 6.65406E-002
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 7.15639E-006
321 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.44059E-002
322 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 9.36036
323 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 24.92429
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 10.90816
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.24663E-003
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 165272.27139
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 7.03106E-003
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 9.36036
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 164484.66732
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 1.43898E-003
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 2174.89380
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 9.36036
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 7.03106E-003
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 6.77267E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 1.43898E-003
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.33862
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 HeatExchanger:AirToAir:SensibleAndLatent CAV_BAS OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 1.20016
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 24.73127
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.39570
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 7.39500E-003
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 7.00000E-003
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 92269.24554
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 3.92535E-003
349 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.33862
350 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 314275.84490
351 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.74942E-003
352 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 6455.75072
353 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.33862
354 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 3.92535E-003
355 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 1.21312E-004
356 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.74942E-003
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.67820
358 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.67820
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 442331.78379
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 280364.99371
362 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.08327E-002
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.67820
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.67820
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.67820
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.67820
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 442331.78379
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 442331.78379
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 33013.32304
370 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
371 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.67820
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.67820
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 442331.78379
374 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.08327E-002
375 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 33013.32304
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 1.96942E-004
377 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
379 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
380 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.51101
381 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.51101
383 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 10140.98397
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6499.65805
385 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.48352E-004
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.51101
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.51101
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.51101
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.51101
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 10140.98397
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 10140.98397
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1525.07876
393 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
394 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.51101
395 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.51101
396 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 10140.98397
397 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.48352E-004
398 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 1525.07876
399 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.90893
400 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.90893
402 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 97427.62688
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 62437.55017
404 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.38600E-003
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.90893
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.90893
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.90893
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.90893
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 97427.62688
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 97427.62688
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 15250.78758
412 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
413 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.90893
414 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.90893
415 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 97427.62688
416 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.38600E-003
417 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 15250.78758
418 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.49571
419 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.49571
421 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9838.11902
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6304.99995
423 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.40935E-004
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.49571
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.49571
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.49571
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.49571
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9838.11902
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9838.11902
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 1525.07876
431 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
432 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.49571
433 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.49571
434 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9838.11902
435 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.40935E-004
436 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 1525.07876
437 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 8.45825E-002
438 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 17429.31950
439 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 8.45825E-002
440 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 10.14990
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 8.45825E-002
442 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 8.45825E-002
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 355035.21711
444 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
445 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 3.54389E-002
446 PlantLoop HEATSYS1 Plant Loop Volume [m3] 4.25267
447 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 3.54389E-002
448 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 10672.63697
449 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
450 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 4050882.66005
451 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 4050882.66000
452 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 3.54389E-002
453 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 8.45825E-002
454 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 10.14990
455 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 8.45825E-002
456 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 12066.90582
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 8.45825E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.25642E-002
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1001633.25897
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1007729.23500
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 5.10897E-002
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 8.45825E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 4.25642E-002
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1001633.25897
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1007729.23500
466 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 5.10897E-002
467 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.37080E-002
468 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.64496
469 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.37080E-002
470 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3496.21535
471 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.37080E-002
472 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
473 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 57722.85269
474 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
475 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
476 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21257.97286
477 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 564650.44015
478 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 553720.47000
479 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.37080E-002
480 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
481 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
482 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
483 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
484 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
485 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.10218
486 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 12.26153
487 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.10218
488 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 30774.22562
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 39.15368
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1197132.82102
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 7.83074
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 149641.60263
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 39.15368
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1197132.82102
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 7.83074
496 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 149641.60263
497 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.17975E-002
498 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 5.17975E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 29546.59
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 493337.11
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 114263.79
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 19739.41
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 13544.13
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 21270.10
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 10973.57
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 258428.79
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 171443.91
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 256803.58
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 164592.57
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 35099.53
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 23139.75
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 34882.93
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 22709.20
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 91146.40
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 890632.47
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 91387.50
19 Coil:Heating:Water CAV_BAS HEATING COIL 226361.61


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 249262.16 170867.34 78394.82 0.69 35154.52 356.56
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2329671.78 1595263.27 734408.50 0.68 327745.12 3324.17
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 247407.10 169606.56 77800.54 0.69 34896.00 353.93
4 Coil:Cooling:Water CAV_BAS COOLING COIL 137089.93 94832.62 42257.30 0.69 18467.50 187.31


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 7.08 24.14
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 7.08 24.14


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.354 0.336   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.354 0.336   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.354 0.336   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_NORTH_0.45 N/A 1.661 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_NORTH_0.45 N/A 1.661 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_NORTH_0.45 N/A 1.661 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_NORTH_0.45 N/A 1.661 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_NORTH_0.45 N/A 1.661 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_EAST_0.45 N/A 1.661 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_EAST_0.45 N/A 1.661 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_EAST_0.45 N/A 1.661 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_SOUTH_0.45 N/A 1.661 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_SOUTH_0.45 N/A 1.661 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_SOUTH_0.45 N/A 1.661 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_SOUTH_0.45 N/A 1.661 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_SOUTH_0.45 N/A 1.661 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_WEST_0.45 N/A 1.661 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_WEST_0.45 N/A 1.661 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_WEST_0.45 N/A 1.661 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 2.101 2.101   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_NORTH_0.45 N/A 1.661 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_EAST_0.45 N/A 1.661 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_SOUTH_0.45 N/A 1.661 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_WEST_0.45 N/A 1.661 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_NORTH_0.45 N/A 1.661 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_EAST_0.45 N/A 1.661 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_SOUTH_0.45 N/A 1.661 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.2925_SHGC_WEST_0.45 N/A 1.661 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.002 0.871   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 0.930 0.816   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 1.327 1.107   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.163 0.158   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.354 0.336   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.354 0.336   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.354 0.336   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 7.2599775955E-004 1.7611190931E-003 Pass Pass 0.0000000000 0.0000000000 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.1319397194 7.2521861119E-002 Pass Pass 0.4155465919 0.4888304275 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 8.6081274719E-003 5.0123513336E-003 Pass Pass 0.4848116436 0.4902222321 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.1609747609 0.1475475883 Pass Pass 0.7732650462 0.9765602043 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 5.3800862514E-002 6.2931781717E-002 Pass Pass 2.8809081421 18.9171538680 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.1411382763 0.1380548019 Pass Pass 22.3302458495 209.9983711972 Fail Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.1923054128 0.1797538675 Pass Pass 25.4138223050 286.6673367426 Fail Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 7.7673057703E-002 5.0206891111E-002 Pass Pass 0.4234860369 0.4918032697 Pass Fail
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.6379065030 0.5436095378 Pass Pass 0.6271410031 0.5620288600 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.6708118910 0.6460259544 Pass Pass 0.6759252258 0.6507296082 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.6335435372 0.6106528240 Pass Pass 0.6778299202 0.6587602027 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.5787432453 0.5638511461 Pass Pass 0.6890873501 0.6542310211 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.8746000485 0.7393042187 Pass Pass 0.5966673228 0.5554432963 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.8953200206 0.8502898342 Pass Pass 0.6193397547 0.6026432612 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.8529316537 0.8150192344 Pass Pass 0.6237877140 0.6086275305 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.8121813736 0.7813929761 Pass Pass 0.6367530994 0.5976641252 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.4343759779E-002 3.4173373856E-002 Pass Pass 0.4594109332 0.5036495567 Fail Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.1003219510 6.0481032972E-002 Pass Pass 0.4860477864 0.4844662887 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 0.2330404000 0.1522525608 Pass Pass 0.4891624461 0.4946523076 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 3.6496240828E-003 3.0777940664E-003 Pass Pass 1.3181544560E-003 1.3334063964E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 3.3689229748E-003 2.0260066834E-003 Pass Pass 1.8543577232E-003 1.4160916324E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 5.5227577116E-003 3.4236192133E-003 Pass Pass 3.2285701994E-003 2.1257933214E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.1537212325E-003 1.0168148518E-003 Pass Pass 8.9323863554E-005 1.4751634501E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 4552.15 226.56 0.00 24021.23 15808.92 44608.86



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -41.90 0.00 -41.90 Wetbulb [C] 0.30 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 27.40 10.20 16.10 Wetbulb [C] 3.10 180.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.340 0.354 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.340 0.354 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.340 0.354 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.871 1.002 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.871 1.002 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.871 1.002 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 0.871 1.002 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.816 0.930 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.816 0.930 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.816 0.930 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.816 0.930 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.107 1.327 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.107 1.327 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.107 1.327 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.107 1.327 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 0.871 1.002 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 0.871 1.002 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 0.871 1.002 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 0.871 1.002 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 0.816 0.930 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 0.816 0.930 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 0.816 0.930 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 0.816 0.930 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.107 1.327 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.107 1.327 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.107 1.327 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.107 1.327 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.30 0.159 0.163 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.340 0.354 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.340 0.354 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.340 0.354 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.2925_SHGC_NORTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.2925_SHGC_NORTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.2925_SHGC_NORTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.2925_SHGC_NORTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.2925_SHGC_NORTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.2925_SHGC_EAST_0.45   19.32 0.00 0.00 19.32 19.32 1.661 0.451 0.452             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.2925_SHGC_EAST_0.45   19.32 0.00 0.00 19.32 19.32 1.661 0.451 0.452             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.2925_SHGC_EAST_0.45   19.32 0.00 0.00 19.32 19.32 1.661 0.451 0.452             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.2925_SHGC_SOUTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.2925_SHGC_SOUTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.2925_SHGC_SOUTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.2925_SHGC_SOUTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.2925_SHGC_SOUTH_0.45   17.38 0.00 0.00 17.38 17.38 1.661 0.451 0.452             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.2925_SHGC_WEST_0.45   19.32 0.00 0.00 19.32 19.32 1.661 0.451 0.452             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.2925_SHGC_WEST_0.45   19.32 0.00 0.00 19.32 19.32 1.661 0.451 0.452             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.2925_SHGC_WEST_0.45   19.32 0.00 0.00 19.32 19.32 1.661 0.451 0.452             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.2925_SHGC_NORTH_0.45   86.92 0.00 0.00 86.92 869.21 1.661 0.451 0.452             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.2925_SHGC_EAST_0.45   57.95 0.00 0.00 57.95 579.48 1.661 0.451 0.452             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.2925_SHGC_SOUTH_0.45   86.92 0.00 0.00 86.92 869.21 1.661 0.451 0.452             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.2925_SHGC_WEST_0.45   57.95 0.00 0.00 57.95 579.48 1.661 0.451 0.452             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.2925_SHGC_NORTH_0.45   86.92 0.00 0.00 86.92 86.92 1.661 0.451 0.452             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.2925_SHGC_EAST_0.45   57.95 0.00 0.00 57.95 57.95 1.661 0.451 0.452             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.2925_SHGC_SOUTH_0.45   86.92 0.00 0.00 86.92 86.92 1.661 0.451 0.452             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.2925_SHGC_WEST_0.45   57.95 0.00 0.00 57.95 57.95 1.661 0.451 0.452             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 1.661 0.451 0.452                      
North Total or Average             1043.06 1.661 0.451 0.452                      
Non-North Total or Average             2433.80 1.661 0.451 0.452                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 1.598 2.101 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 0.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 1.00 1.00 1.00 0.00 1.00 0.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 7.6202 2779.43 21179.74 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 177.74
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 7.6202 24961.20 190208.95 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 1596.24
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.47 0.0000 Y 15.00
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.24 0.0000 Y 9.60
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 32.83 0.0000 Y 14.72
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.16 0.0000 Y 9.58
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 7.6202 3134.13 23882.63 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.52 0.0000 Y 150.26
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.26 0.0000 Y 96.08
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 7.6202 3134.20 23883.15 LightsWired LTG_SCH_OFFICE 45.89 168.00 32.88 0.0000 Y 147.40
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.18 0.0000 Y 95.87
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.52 0.0000 Y 15.03
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.26 0.0000 Y 9.61
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 32.88 0.0000 Y 14.74
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 33.18 0.0000 Y 9.59
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 7.6202 783.68 5971.78 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 50.12
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 12.5114 362.03 4529.48 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 46.40
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
Interior Lighting Total       7.6661 46320.38 355094.67               867.48


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   44.84 44.84 83.95
EXTERIOR_LIGHTS_B 27638.03 AstronomicalClock -   83.06 71.59 371.43
Exterior Lighting Total 37611.08           455.38



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 1983624.95          
HEATSYS1 BOILER Boiler:HotWater 4050882.66 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1007729.23 5.33 996381.71 4.98 7.08 24.14
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1007729.23 5.33 996381.71 4.98 7.08 24.14
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 553720.47 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1197132.82          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1197132.82          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 166551.84 249262.16 170867.34 78394.82 0.69 - 35154.52 356.56
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 1564103.86 2329671.78 1595263.27 734408.50 0.68 - 327745.12 3324.17
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 165272.27 247407.10 169606.56 77800.54 0.69 - 34896.00 353.93
CAV_BAS COOLING COIL Coil:Cooling:Water 92269.25 137089.93 94832.62 42257.30 0.69 - 18467.50 187.31
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   442331.78 280364.99 161966.79 0.63 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   10140.98 6499.66 3641.33 0.64 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   97427.63 62437.55 34990.08 0.64 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9838.12 6305.00 3533.12 0.64 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 31172.07 29546.59 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 520844.41 493337.11 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 120587.92 114263.79 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 20833.58 19739.41 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 14295.06 13544.13 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 22449.41 21270.10 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 11581.48 10973.57 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 272765.95 258428.79 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 180956.04 171443.91 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 271050.32 256803.58 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 173723.64 164592.57 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 37048.14 35099.53 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 24424.45 23139.75 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 36819.49 34882.93 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 23969.97 22709.20 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 162916.74 91146.40 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 1646683.49 890632.47 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 164484.67 91387.50 -
CAV_BAS HEATING COIL Coil:Heating:Water 314275.84 226361.61 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   442331.78 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   10140.98 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   97427.63 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9838.12 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   33013.32 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   1525.08 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   15250.79 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   1525.08 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.43 21533.17 2283.73 1.00 1.11 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 87.88 200704.96 2283.73 1.00 1.07 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1389.42 9.36 21376.51 2283.73 1.00 1.11 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.34 9052.46 1695.65 1.00 1.16 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.62 1018.41 21.68 35752.70 1649.25 1.00 1.14 General FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.51 572.39 1120.11 1.00 1.60 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.91 5498.54 1120.11 1.00 1.16 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.50 555.25 1120.11 1.00 1.61 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.084583 17429.32 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.035439 10672.64 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.084583 12066.91 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013708 3496.22 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.102179 30774.23 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 72811.09 72811.09 26.20 5.339 5.339 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00748 19.85 0.00700 1.200 0.00
CORE_BOTTOM 78271.65 78271.65 31.36 5.739 5.739 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00740 19.85 0.00700 1.078 0.00
CORE_MID 736392.26 736392.26 295.01 53.980 53.980 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00742 19.85 0.00700 10.778 0.00
CORE_TOP 72223.01 72223.01 28.93 5.294 5.294 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 24.00 24.00 0.00743 19.85 0.00700 1.078 0.00
PERIMETER_BOT_ZN_3 12605.48 12605.48 40.22 0.933 0.933 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 24.00 24.00 0.00730 21.38 0.00700 0.135 0.00
PERIMETER_BOT_ZN_2 16621.94 16621.94 82.30 1.230 1.230 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:00:00 24.00 24.00 0.00715 21.79 0.00700 0.087 0.00
PERIMETER_BOT_ZN_1 25466.92 25466.92 81.26 1.885 1.885 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 24.00 24.00 0.00715 27.40 0.00701 0.135 0.00
PERIMETER_BOT_ZN_4 19727.05 19727.05 97.67 1.460 1.460 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 24.00 24.00 0.00712 24.70 0.00700 0.087 0.00
PERIMETER_MID_ZN_3 115760.92 115760.92 369.36 8.567 8.567 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:10:00 24.00 24.00 0.00731 21.23 0.00700 1.353 0.00
PERIMETER_MID_ZN_2 175455.59 175455.59 868.70 12.984 12.984 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:20:00 24.00 24.00 0.00714 22.37 0.00700 0.872 0.00
PERIMETER_MID_ZN_1 267275.96 267275.96 852.77 19.780 19.780 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 24.00 24.00 0.00714 27.40 0.00701 1.353 0.00
PERIMETER_MID_ZN_4 179262.40 179262.40 887.55 13.266 13.266 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.00 24.00 0.00713 24.44 0.00700 0.872 0.00
PERIMETER_TOP_ZN_3 11955.85 11955.85 38.15 0.885 0.885 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 21:00:00 24.00 24.00 0.00730 21.38 0.00700 0.135 0.00
PERIMETER_TOP_ZN_2 17469.97 17469.97 86.50 1.293 1.293 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 09:30:00 24.00 24.00 0.00714 22.66 0.00700 0.087 0.00
PERIMETER_TOP_ZN_1 27724.96 27724.96 88.46 2.052 2.052 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 24.00 24.00 0.00713 27.40 0.00701 0.135 0.00
PERIMETER_TOP_ZN_4 18584.32 18584.32 92.01 1.375 1.375 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 24.00 24.00 0.00713 24.44 0.00700 0.087 0.00
DATACENTER_BOT_ZN_6 8754.66 8754.66 241.82 0.511 0.511 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 27.00 27.00 0.00708 21.84 0.00700 0.016 0.00
DATACENTER_MID_ZN_6 84099.16 84099.16 2323.01 4.909 4.909 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 27.00 27.00 0.00709 21.99 0.00700 0.156 0.00
DATACENTER_TOP_ZN_6 8492.39 8492.39 234.58 0.496 0.496 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 27.00 27.00 0.00709 21.99 0.00700 0.016 0.00
DATACENTER_BASEMENT_ZN_6 371391.66 371391.66 473.91 21.678 21.678 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:00:00 27.00 27.00 0.00704 18.12 0.00699 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:10:00 21.00 22.38 0.00006 -41.90 0.00006 1.200 0.00
CORE_BOTTOM 12171.72 12171.72 4.88 0.520 1.078 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -41.90 0.00006 1.078 0.00
CORE_MID 334643.07 334643.07 134.07 14.369 14.369 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -41.90 0.00006 10.778 0.00
CORE_TOP 84416.73 84416.73 33.82 3.649 3.649 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 -41.90 0.00006 1.078 0.00
PERIMETER_BOT_ZN_3 14579.09 14579.09 46.52 0.631 0.631 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00796 -41.90 0.00006 0.135 0.00
PERIMETER_BOT_ZN_2 10002.90 10002.90 49.53 0.433 0.433 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00797 -41.90 0.00006 0.087 0.00
PERIMETER_BOT_ZN_1 15708.74 15708.74 50.12 0.680 0.680 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00797 -41.90 0.00006 0.135 0.00
PERIMETER_BOT_ZN_4 8106.02 8106.02 40.13 0.351 0.351 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 0.087 0.00
PERIMETER_MID_ZN_3 190839.55 190839.55 608.91 8.266 8.266 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 1.353 0.00
PERIMETER_MID_ZN_2 126602.56 126602.56 626.82 5.484 5.484 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 0.872 0.00
PERIMETER_MID_ZN_1 189640.17 189640.17 605.07 8.214 8.214 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 1.353 0.00
PERIMETER_MID_ZN_4 121546.11 121546.11 601.79 5.265 5.265 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00794 -41.90 0.00006 0.872 0.00
PERIMETER_TOP_ZN_3 25915.73 25915.73 82.69 1.123 1.123 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 0.135 0.00
PERIMETER_TOP_ZN_2 17085.08 17085.08 84.59 0.741 0.741 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 0.087 0.00
PERIMETER_TOP_ZN_1 25755.88 25755.88 82.18 1.116 1.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 0.135 0.00
PERIMETER_TOP_ZN_4 16767.31 16767.31 83.02 0.727 0.727 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00795 -41.90 0.00006 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 24.05 0.00056 -41.90 0.00006 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:40:00 18.00 22.24 0.00056 -41.90 0.00006 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:30:00 18.00 19.41 0.00056 -41.90 0.00006 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 14:00:00 18.00 27.00 0.00700 -41.90 0.00006 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 9.43 9.43 3.17 3.17 9.4290 3.1727 9.4290 0.3365 0.3000
VAV_MID WITH REHEAT 87.88 87.88 41.60 41.60 87.8848 41.5984 87.8848 0.4733 0.3000
VAV_TOP WITH REHEAT 9.36 9.36 7.36 7.36 9.3604 7.3560 9.3604 0.7859 0.3000
CAV_BAS 5.34 5.34 1.20 1.20 5.3386 5.3386 5.3386 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.68 21.68 0.34 0.34 21.6782 21.6781 21.6782 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.51 0.51 0.02 0.02 0.5110 0.5110 0.5110 1.0000 1.0000
AIRLOOP DATACENTER MID 4.91 4.91 0.16 0.16 4.9089 4.9089 4.9089 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.50 0.50 0.02 0.02 0.4957 0.4957 0.4957 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 31172.066 31172.066 1.916863 0.00027271 670.835 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 31172.07 31172.07 1.916863 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00799999 50.9130 12171.72 0.00 31281.10 31281.10
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 520844.410 520844.410 18.785046 0.00455657 12809.012 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 520844.41 520844.41 18.785046 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00800000 50.9130 334643.07 0.00 522483.60 522483.60
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 120587.919 120587.919 3.649155 0.00105496 3182.020 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 120587.92 120587.92 3.649155 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00800000 50.9130 84416.73 0.00 120996.49 120996.49
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 20833.584 20833.584 0.631041 0.00018226 549.512 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 20833.58 20833.58 0.631041 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00796496 50.6934 14579.09 0.00 20902.48 20902.48
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 14295.057 14295.057 0.433051 0.00012506 377.027 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 14295.06 14295.06 0.433051 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00796759 50.7099 10002.90 0.00 14342.16 14342.16
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 22449.414 22449.414 0.680086 0.00019640 592.091 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 22449.41 22449.41 0.680086 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00796964 50.7227 15708.74 0.00 22523.36 22523.36
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 11581.475 11581.475 0.350669 0.00010132 305.528 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 11581.48 11581.48 0.350669 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00794504 50.5684 8106.02 0.00 11620.15 11620.15
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 272765.945 272765.945 8.266303 0.00238628 7192.828 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 272765.95 272765.95 8.266303 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00794542 50.5710 190839.55 0.00 273655.60 273655.60
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 180956.044 180956.044 5.484223 0.00158308 4771.700 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 180956.04 180956.04 5.484223 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00794545 50.5711 126602.56 0.00 181545.49 181545.49
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 271050.321 271050.321 8.214222 0.00237127 7147.622 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 271050.32 271050.32 8.214222 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00794500 50.5683 189640.17 0.00 271934.63 271934.63
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 173723.645 173723.645 5.264703 0.00151981 4581.116 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 173723.64 173723.64 5.264703 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00794264 50.5535 121546.11 0.00 174290.48 174290.48
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 37048.138 37048.138 1.123241 0.00032411 976.767 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 37048.14 36931.65 1.123241 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00795188 50.6116 25915.73 0.00 37167.60 37167.60
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 24424.448 24424.448 0.740531 0.00021368 643.938 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 24424.45 24424.45 0.740531 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00795138 50.6085 17085.08 0.00 24503.15 24503.15
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 36819.488 36819.488 1.116301 0.00032211 970.742 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 36819.49 36819.49 1.116301 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00795156 50.6097 25755.88 0.00 36938.24 36938.24
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 23969.965 23969.965 0.726739 0.00020970 631.961 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23969.97 23969.97 0.726739 12.80 11.46 0.00800000 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 0.0000 21.00 0.00795040 50.6024 16767.31 0.00 24047.23 24047.23
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 166551.835 -999.000 9.428956 0.00708550 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 166551.84 160476.20 9.428956 24.93 15.47 0.00724848 10.91 9.59 0.00700000 27.40 0.00700714 16.15 26.9191 24.00 0.00733888 38.9659 125857.47 0.00 168932.83 168932.83
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 162916.736 162916.736 2.828687 0.00142527 2165.466 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:50:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 162916.74 162916.74 2.828687 -35.55 -35.55 0.00087534 12.80 11.46 0.00800000 -41.90 0.00006450 -41.90 89.7303 19.72 0.00795166 54.7874 37634.11 0.00 110133.34 110133.34
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 1564103.864 -999.000 87.884799 0.06654059 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 1564103.86 1504803.33 87.884799 25.01 15.51 0.00725991 10.91 9.59 0.00700000 27.40 0.00700714 16.15 28.8809 24.00 0.00736648 39.1108 1156393.31 0.00 1586350.66 1586350.66
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 1646683.491 1646683.491 26.365440 0.01440591 21341.137 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 1646683.49 1646683.49 26.365440 -39.63 -39.63 0.00035833 12.80 11.46 0.00800000 -41.90 0.00006450 -41.90 96.2698 19.30 0.00791459 55.9738 485963.93 0.00 1075773.56 1075773.56
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 165272.271 -999.000 9.360357 0.00703106 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 165272.27 159286.10 9.360357 24.92 15.47 0.00724663 10.91 9.59 0.00700000 27.40 0.00700714 16.15 27.1164 24.00 0.00733615 38.9516 126046.46 0.00 167635.57 167635.57
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 164484.667 164484.667 2.808107 0.00143898 2174.894 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 164484.67 164484.67 2.808107 -36.37 -36.37 0.00082063 12.80 11.46 0.00800000 -41.90 0.00006450 -41.90 90.3879 15.60 0.00790388 70.6102 53567.08 0.00 110418.98 110418.98
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 92269.246 -999.000 5.338625 0.00392535 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 92269.25 86972.75 5.338625 24.73 15.53 0.00739500 11.40 9.81 0.00700000 26.89 0.00700637 15.97 22.4806 24.00 0.00752689 39.9526 65157.93 0.00 93583.55 93583.55
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 314275.845 314275.845 5.338625 0.00274942 6455.751 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 314275.84 314275.84 5.338625 -9.42 -12.80 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 22.4806 22.50 0.00006450 0.3794 0.00 0.00 238765.03 238765.03
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 442331.784 280364.994 21.678197 0.01083268 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 397189.65 395116.57 -999.0 28.42 16.54 0.00704165 12.80 10.42 0.00700000 27.40 0.00700714 16.15 -999.0000 27.00 0.00704220 31.3059 370906.36 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10140.984 6499.658 0.511014 0.00024835 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 9059.18 8966.14 -999.0 27.81 16.35 0.00707987 12.80 10.42 0.00700000 21.99 0.00699901 14.15 -999.0000 27.00 0.00708243 31.4806 8754.44 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 97427.627 62437.550 4.908934 0.00238600 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 87035.62 86106.23 -999.0 27.80 16.35 0.00708306 12.80 10.42 0.00700000 21.99 0.00699901 14.15 -999.0000 27.00 0.00708582 31.4957 84099.16 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9838.119 6305.000 0.495707 0.00024093 -999.000 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 8788.73 8695.70 -999.0 27.80 16.35 0.00708234 12.80 10.42 0.00700000 21.99 0.00699901 14.15 -999.0000 27.00 0.00708505 31.4922 8492.39 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 442331.784 442331.784 21.678197 0.01083268 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 442331.78 442331.78 21.678197 -41.90 -41.90 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 1.5610 27.00 0.00700000 31.1156 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 10140.984 10140.984 0.511014 0.00024835 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 10140.98 10140.98 0.511014 -41.90 -41.90 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.0591 24.93 0.00056008 2.8425 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 97427.627 97427.627 4.908934 0.00238600 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 97427.63 97427.63 4.908934 -41.90 -41.90 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.1845 23.52 0.00056011 3.0943 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9838.119 9838.119 0.495707 0.00024093 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9838.12 9838.12 0.495707 -41.90 -41.90 0.00006450 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.1535 21.72 0.00055956 3.4473 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 33013.323 33013.323 -999.0 -999.0 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 33013.32 33013.32 21.678197 -0.65 -0.65 0.00689174 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 1.5610 27.00 0.00700000 31.1156 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 1525.079 1525.079 -999.0 -999.0 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1525.08 1525.08 0.511014 -1.28 -6.15 0.00054492 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.0591 24.93 0.00056008 2.8425 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 15250.788 15250.788 -999.0 -999.0 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 15250.79 15250.79 4.908934 -1.33 -6.19 0.00054433 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.1845 23.52 0.00056011 3.0943 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 1525.079 1525.079 -999.0 -999.0 -999.000 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 1525.08 1525.08 0.495707 -1.32 -6.18 0.00054395 40.00 21.00 0.00800000 -41.90 0.00006450 -41.90 3.1535 21.72 0.00055956 3.4473 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 31172.066 31172.066 1.916863 0.00027271 670.835 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.7543 0.769513 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 31172.07 31172.07 1.0000 2.27232434 1.916863 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.27267902 60.00 32.22 27.78 0.000 31172.07 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.69 0.00799999 21.00 0.00799999 50.9130 12171.72 0.00 31281.10 31281.10 2.27232434 12.80 11.60 0.00800000 33059.8 26.30 16.77 0.00800000 46826.0
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 520844.410 520844.410 18.785046 0.00455657 12809.012 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 12.6039 12.857554 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 520844.41 520844.41 1.0000 22.26853208 18.785046 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 4.55610930 60.00 32.22 27.78 0.000 520844.41 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.87 0.00800000 21.00 0.00800000 50.9130 334643.07 0.00 522483.60 522483.60 22.26853208 12.80 11.60 0.00800000 33059.8 35.81 19.91 0.00800000 56522.7
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 120587.919 120587.919 3.649155 0.00105496 3182.020 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 2.9181 2.976831 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 120587.92 120587.92 1.0000 4.32585140 3.649155 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 1.05484810 60.00 32.22 27.78 0.000 120587.92 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00800000 21.00 0.00800000 50.9130 84416.73 0.00 120996.49 120996.49 4.32585140 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61030.4
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 20833.584 20833.584 0.631041 0.00018226 549.512 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.5042 0.514297 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 20833.58 20833.58 1.0000 0.74806100 0.631041 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.18224269 60.00 32.22 27.78 0.000 20833.58 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00796496 21.00 0.00796496 50.6934 14579.09 0.00 20902.48 20902.48 0.74806100 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61002.0
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 14295.057 14295.057 0.433051 0.00012506 377.027 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.3459 0.352887 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 14295.06 14295.06 1.0000 0.51335534 0.433051 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.12504664 60.00 32.22 27.78 0.000 14295.06 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00796759 21.00 0.00796759 50.7099 10002.90 0.00 14342.16 14342.16 0.51335534 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60997.9
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 22449.414 22449.414 0.680086 0.00019640 592.091 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.5433 0.554186 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 22449.41 22449.41 1.0000 0.80620091 0.680086 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.19637723 60.00 32.22 27.78 0.000 22449.41 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00796964 21.00 0.00796964 50.7227 15708.74 0.00 22523.36 22523.36 0.80620091 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 60997.5
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 11581.475 11581.475 0.350669 0.00010132 305.528 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.2803 0.285900 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 11581.48 11581.48 1.0000 0.41569648 0.350669 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.10130946 60.00 32.22 27.78 0.000 11581.48 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00794504 21.00 0.00794504 50.5684 8106.02 0.00 11620.15 11620.15 0.41569648 12.80 11.60 0.00800000 33059.8 40.21 21.25 0.00800000 61013.3
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 272765.945 272765.945 8.266303 0.00238628 7192.828 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 6.6007 6.733494 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 272765.95 272765.95 1.0000 9.79920041 8.266303 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 2.38603206 60.00 32.22 27.78 0.000 272765.95 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00794542 21.00 0.00794542 50.5710 190839.55 0.00 273655.60 273655.60 9.79920041 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.1
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 180956.044 180956.044 5.484223 0.00158308 4771.700 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 4.3789 4.467077 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 180956.04 180956.04 1.0000 6.50121387 5.484223 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 1.58292092 60.00 32.22 27.78 0.000 180956.04 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00794545 21.00 0.00794545 50.5711 126602.56 0.00 181545.49 181545.49 6.50121387 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60984.7
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 271050.321 271050.321 8.214222 0.00237127 7147.622 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 6.5591 6.691142 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 271050.32 271050.32 1.0000 9.73746113 8.214222 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 2.37102456 60.00 32.22 27.78 0.000 271050.32 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00794500 21.00 0.00794500 50.5683 189640.17 0.00 271934.63 271934.63 9.73746113 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.5
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 173723.645 173723.645 5.264703 0.00151981 4581.116 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 4.2039 4.288538 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 173723.64 173723.64 1.0000 6.24098535 5.264703 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 1.51965519 60.00 32.22 27.78 0.000 173723.64 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00794264 21.00 0.00794264 50.5535 121546.11 0.00 174290.48 174290.48 6.24098535 12.80 11.60 0.00800000 33059.8 40.19 21.24 0.00800000 60986.6
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 37048.138 37048.138 1.123241 0.00032411 976.767 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.8965 0.914570 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 37048.14 36931.65 1.0000 1.33153458 1.123241 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.32408021 60.00 32.22 27.78 0.000 37048.14 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00795188 21.00 0.00795188 50.6116 25915.73 0.00 37167.60 37167.60 1.33153458 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60973.2
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 24424.448 24424.448 0.740531 0.00021368 643.938 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.5910 0.602941 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 24424.45 24424.45 1.0000 0.87785498 0.740531 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.21365393 60.00 32.22 27.78 0.000 24424.45 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00795138 21.00 0.00795138 50.6085 17085.08 0.00 24503.15 24503.15 0.87785498 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.3
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 36819.488 36819.488 1.116301 0.00032211 970.742 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.8910 0.908925 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 36819.49 36819.49 1.0000 1.32330659 1.116301 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.32208008 60.00 32.22 27.78 0.000 36819.49 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00795156 21.00 0.00795156 50.6097 25755.88 0.00 36938.24 36938.24 1.32330659 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60973.4
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 23969.965 23969.965 0.726739 0.00020970 631.961 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 0.5800 0.591722 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23969.97 23969.97 1.0000 0.86150531 0.726739 12.80 11.46 0.00800000 33059.8 40.00 21.00 0.00800000 60796.0 0.20967832 60.00 32.22 27.78 0.000 23969.97 -41.90 0.00006450 -41.90 0.00000000 0.0000 20.95 0.00795040 21.00 0.00795040 50.6024 16767.31 0.00 24047.23 24047.23 0.86150531 12.80 11.60 0.00800000 33059.8 40.17 21.23 0.00800000 60972.9
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 166551.835 -999.000 9.428956 0.00708550 -999.000 -999.0000 1.00000 1.00000 1018.3146 1004.8586 1.1854 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.428956 11.17745491   4197.9300 999.8980 84.57387739 12.27 6.67 5.60 1988197.22 8.3770 8.377028 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 166551.84 160476.20 1.0000 11.17745491 9.428956 24.93 15.47 0.00724848 43510.2 10.91 9.59 0.00700000 28609.5 7.08477730 6.67 12.27 5.60 21533.169 145018.67 27.40 0.00700714 16.15 2.53819000 26.9191 24.00 0.00733888 24.00 0.00733888 38.9659 125857.47 0.00 168932.83 168932.83 11.17745491 24.93 15.63 0.00724848 43510.2 10.08 9.62 0.00724848 28396.5
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 162916.736 162916.736 2.828687 0.00142527 2165.466 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 9.428956 11.17745491   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 3.9424 4.021759 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:50:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 162916.74 162916.74 1.0000 3.35323647 2.828687 -35.55 -35.55 0.00087534 -33590.7 12.80 11.46 0.00800000 33059.8 1.42512128 60.00 32.22 27.78 0.000 162916.74 -41.90 0.00006450 -41.90 2.53819000 89.7303 19.93 0.00795999 19.72 0.00795166 54.7874 37634.11 0.00 110133.34 110133.34 3.35323647 2.80 -2.99 0.00087534 5007.3 35.43 13.67 0.00087534 37851.2
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 1564103.864 -999.000 87.884799 0.06654059 -999.000 -999.0000 1.00000 1.00000 1018.3358 1004.8586 1.1854 VAV_MID WITH REHEAT FAN Fan:VariableVolume 87.884799 104.18209403   4197.9300 999.8980 84.57387739 12.27 6.67 5.60 1988197.22 78.6695 78.669452 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 1564103.86 1504803.33 1.0000 104.18209403 87.884799 25.01 15.51 0.00725991 43622.7 10.91 9.59 0.00700000 28609.5 66.53380627 6.67 12.27 5.60 200704.960 1363398.90 27.40 0.00700714 16.15 25.38195000 28.8809 24.00 0.00736648 24.00 0.00736648 39.1108 1156393.31 0.00 1586350.66 1586350.66 104.18209403 25.01 15.67 0.00725991 43622.7 10.06 9.62 0.00725991 28396.0
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 1646683.491 1646683.491 26.365440 0.01440591 21341.137 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV_MID WITH REHEAT FAN Fan:VariableVolume 87.884799 104.18209403   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 39.8480 40.649992 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 06:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 1646683.49 1646683.49 1.0000 31.25462821 26.365440 -39.63 -39.63 0.00035833 -38953.4 12.80 11.46 0.00800000 33059.8 14.40443597 60.00 32.22 27.78 0.000 1646683.49 -41.90 0.00006450 -41.90 25.38195000 96.2698 18.92 0.00794150 19.30 0.00791459 55.9738 485963.93 0.00 1075773.56 1075773.56 31.25462821 2.80 -3.86 0.00035833 3711.6 37.03 13.79 0.00035833 38131.2
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 165272.271 -999.000 9.360357 0.00703106 -999.000 -999.0000 1.00000 1.00000 1018.3111 1004.8586 1.1854 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.360357 11.09613441   4197.9300 999.8980 84.57387739 12.27 6.67 5.60 1988197.22 8.3127 8.312670 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:40:00 Sensible 165272.27 159286.10 1.0000 11.09613441 9.360357 24.92 15.47 0.00724663 43504.1 10.91 9.59 0.00700000 28609.5 7.03034724 6.67 12.27 5.60 21376.506 143895.76 27.40 0.00700714 16.15 2.53819000 27.1164 24.00 0.00733615 24.00 0.00733615 38.9516 126046.46 0.00 167635.57 167635.57 11.09613441 24.92 15.63 0.00724663 43504.1 10.09 9.62 0.00724663 28396.5
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 164484.667 164484.667 2.808107 0.00143898 2174.894 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 9.360357 11.09613441   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 3.9804 4.060465 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 05:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 164484.67 164484.67 1.0000 3.32884032 2.808107 -36.37 -36.37 0.00082063 -34552.3 12.80 11.46 0.00800000 33059.8 1.43883683 60.00 32.22 27.78 0.000 164484.67 -41.90 0.00006450 -41.90 2.53819000 90.3879 15.60 0.00793099 15.60 0.00790388 70.6102 53567.08 0.00 110418.98 110418.98 3.32884032 2.80 -3.08 0.00082063 4870.2 35.76 13.75 0.00082063 38040.6
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 92269.246 -999.000 5.338625 0.00392535 -999.000 -999.0000 1.00000 1.00000 1018.5869 1004.8586 1.1854 CAV_BAS FAN Fan:ConstantVolume 5.338625 6.32861584   4197.9300 999.8980 84.57387739 12.27 6.67 5.60 1988197.22 4.6408 4.640850 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 13:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 08:00:00 Sensible 92269.25 86972.75 1.0000 6.32861584 5.338625 24.73 15.53 0.00739500 43685.4 11.40 9.81 0.00700000 29105.7 3.92494658 6.67 12.27 5.60 9052.463 83216.78 26.89 0.00700637 15.97 1.20015641 22.4806 24.00 0.00752689 24.00 0.00752689 39.9526 65157.93 0.00 93583.55 93583.55 6.32861584 24.73 15.69 0.00739500 43685.4 10.21 9.84 0.00739500 28898.0
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 314275.845 314275.845 5.338625 0.00274942 6455.751 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 CAV_BAS FAN Fan:ConstantVolume 5.338625 6.32861584   4197.9300 999.8980 35.43527353 54.44 82.22 27.78 4132408.28 7.6051 7.758207 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 314275.84 314275.84 1.0000 6.32861584 5.338625 -9.42 -12.80 0.00006450 -9304.8 40.00 21.00 0.00800000 60796.0 2.74914172 60.00 32.22 27.78 0.000 314275.84 -41.90 0.00006450 -41.90 1.20015641 22.4806 0.00 0.00006450 22.50 0.00006450 0.3794 0.00 0.00 238765.03 238765.03 6.32861584 12.80 2.07 0.00006450 13024.8 50.34 18.29 0.00006450 50752.6
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 442331.784 280364.994 21.678197 0.01083268 -999.000 -999.0000 -999.00000 -999.00000 1017.9301 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 07:10:00 Sensible 397189.65 395116.57 0.8979 -999.0 -999.0 28.42 16.54 0.00704165 46539.2 12.80 10.42 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 397189.65 27.40 0.00700714 16.15 0.33839277 -999.0000 27.00 0.00704220 27.00 0.00704220 31.3059 370906.36 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 10140.984 6499.658 0.511014 0.00024835 -999.000 -999.0000 -999.00000 -999.00000 1018.0011 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:30:00 Sensible 9059.18 8966.14 0.8933 -999.0 -999.0 27.81 16.35 0.00707987 46012.9 12.80 10.42 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 9059.18 21.99 0.00699901 14.15 0.01563234 -999.0000 27.00 0.00708243 27.00 0.00708243 31.4806 8754.44 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 97427.627 62437.550 4.908934 0.00238600 -999.000 -999.0000 -999.00000 -999.00000 1018.0071 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 Sensible 87035.62 86106.23 0.8933 -999.0 -999.0 27.80 16.35 0.00708306 46014.6 12.80 10.42 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 87035.62 21.99 0.00699901 14.15 0.15632344 -999.0000 27.00 0.00708582 27.00 0.00708582 31.4957 84099.16 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9838.119 6305.000 0.495707 0.00024093 -999.000 -999.0000 -999.00000 -999.00000 1018.0057 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 Sensible 8788.73 8695.70 0.8933 -999.0 -999.0 27.80 16.35 0.00708234 46014.3 12.80 10.42 0.00700000 30535.1 -999.0 -999.00 -999.00 -999.00 0.000 8788.73 21.99 0.00699901 14.15 0.01563234 -999.0000 27.00 0.00708505 27.00 0.00708505 31.4922 8492.39 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 442331.784 442331.784 21.678197 0.01083268 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 442331.78 442331.78 1.0000 25.69818668 21.678197 -41.90 -41.90 0.00006450 -41946.5 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 442331.78 -41.90 0.00006450 -41.90 0.33839277 1.5610 0.00 0.00700000 27.00 0.00700000 31.1156 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 10140.984 10140.984 0.511014 0.00024835 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 10140.98 10140.98 1.0000 0.60577591 0.511014 -41.90 -41.90 0.00006450 -41946.5 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 10140.98 -41.90 0.00006450 -41.90 0.01563234 3.0591 0.00 0.00056008 24.93 0.00056008 2.8425 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 97427.627 97427.627 4.908934 0.00238600 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 97427.63 97427.63 1.0000 5.81924362 4.908934 -41.90 -41.90 0.00006450 -41946.5 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 97427.63 -41.90 0.00006450 -41.90 0.15632344 3.1845 0.00 0.00056011 23.52 0.00056011 3.0943 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9838.119 9838.119 0.495707 0.00024093 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.1854 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9838.12 9838.12 1.0000 0.58763043 0.495707 -41.90 -41.90 0.00006450 -41946.5 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9838.12 -41.90 0.00006450 -41.90 0.01563234 3.1535 0.00 0.00055956 21.72 0.00055956 3.4473 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 33013.323 33013.323 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.678197 25.69818668   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 33013.32 33013.32 1.0000 25.69818668 21.678197 -0.65 -0.65 0.00689174 16570.2 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 33013.32 -41.90 0.00006450 -41.90 0.33839277 1.5610 0.00 0.00700000 27.00 0.00700000 31.1156 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1525.079 1525.079 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.511014 0.60577591   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1525.08 1525.08 1.0000 0.60577591 0.511014 -1.28 -6.15 0.00054492 73.6 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1525.08 -41.90 0.00006450 -41.90 0.01563234 3.0591 0.00 0.00056008 24.93 0.00056008 2.8425 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 15250.788 15250.788 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.908934 5.81924362   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 15250.79 15250.79 1.0000 5.81924362 4.908934 -1.33 -6.19 0.00054433 19.2 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 15250.79 -41.90 0.00006450 -41.90 0.15632344 3.1845 0.00 0.00056011 23.52 0.00056011 3.0943 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 1525.079 1525.079 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.1854 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.495707 0.58763043   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 1525.08 1525.08 1.0000 0.58763043 0.495707 -1.32 -6.18 0.00054395 31.3 40.00 21.00 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 1525.08 -41.90 0.00006450 -41.90 0.01563234 3.1535 0.00 0.00055956 21.72 0.00055956 3.4473 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.43 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 87.88 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialDryBulb 0.00 9.36 -      
CAV_BAS_OA_CONTROLLER DifferentialDryBulb 1.20 5.34 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 1050.17 3020.83 16.83
CORE_BOTTOM 1016.50 3132.33 22.00
CORE_MID 1515.17 4042.17 921.33
CORE_TOP 2867.17 4511.33 2387.50
PERIMETER_BOT_ZN_3 2922.67 4127.33 2059.17
PERIMETER_BOT_ZN_2 3286.17 3840.67 2106.83
PERIMETER_BOT_ZN_1 3306.50 3707.83 1986.33
PERIMETER_BOT_ZN_4 2723.83 3404.00 1097.00
PERIMETER_MID_ZN_3 3569.00 4520.67 2990.83
PERIMETER_MID_ZN_2 3246.33 3590.67 2391.33
PERIMETER_MID_ZN_1 3628.50 4001.17 2450.50
PERIMETER_MID_ZN_4 3694.00 4282.33 2780.33
PERIMETER_TOP_ZN_3 3908.50 4805.83 3444.17
PERIMETER_TOP_ZN_2 4103.67 4347.00 3135.83
PERIMETER_TOP_ZN_1 3931.83 4306.50 2903.83
PERIMETER_TOP_ZN_4 3956.67 4563.67 3149.67
DATACENTER_BOT_ZN_6 5452.67 155.17 135.83
DATACENTER_MID_ZN_6 3645.00 553.83 30.83
DATACENTER_TOP_ZN_6 3160.83 1074.33 100.17
DATACENTER_BASEMENT_ZN_6 5943.00 5365.17 5365.17
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5910.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 28.00 0.00 1.50
CORE_BOTTOM 0.00 0.50 0.00 0.00
CORE_MID 4.00 0.00 1.33 0.00
CORE_TOP 48.83 0.00 11.00 0.00
PERIMETER_BOT_ZN_3 12.50 10.00 1.00 0.00
PERIMETER_BOT_ZN_2 13.33 15.00 0.00 9.83
PERIMETER_BOT_ZN_1 15.83 17.83 0.17 17.33
PERIMETER_BOT_ZN_4 3.17 64.17 0.00 16.83
PERIMETER_MID_ZN_3 283.83 5.00 119.83 0.00
PERIMETER_MID_ZN_2 134.33 13.33 28.00 10.50
PERIMETER_MID_ZN_1 105.50 17.50 19.67 17.00
PERIMETER_MID_ZN_4 91.17 16.67 15.83 5.00
PERIMETER_TOP_ZN_3 615.67 1.67 257.50 0.00
PERIMETER_TOP_ZN_2 349.50 9.17 83.67 8.00
PERIMETER_TOP_ZN_1 291.17 12.67 67.00 12.00
PERIMETER_TOP_ZN_4 275.50 14.00 70.50 3.83
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 12.17 0.00 12.17
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 684.50 172.17 273.83 83.83
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 1.004 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.818 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.674 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.630 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.838 0.028 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 1.352 0.029 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 1.444 0.028 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 1.658 0.029 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.744 0.065 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 1.242 0.072 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 1.445 0.065 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 1.221 0.067 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.826 0.080 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 1.324 0.083 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 1.392 0.080 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 1.198 0.083 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.429 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.428 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.428 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.484 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 60.99 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 54.77 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.86 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 6.88 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.43 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 6.88 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.43 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.79 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.20 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 60.99 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 54.77 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.86 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 6.88 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 6.88 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.43 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.79 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.79 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.20 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1010.73 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 40546067.87 0.00 40546067.87 0.00 40546067.87 37848132.68 4164.78 2046.84 2548.38 226.65
CORE_BOTTOM 34721969.91 0.00 34721969.91 0.00 34721969.91 33990283.35 5338.62 41.65 3379.73 506.69
CORE_MID 0.28E+09 0.00 0.28E+09 0.00 0.28E+09 0.34E+09 6606.90 22.32 2130.79 607.55
CORE_TOP 25748793.26 0.00 25748793.26 0.00 25748793.26 33990283.35 6895.72 19.28 1845.01 415.65
PERIMETER_BOT_ZN_3 4470680.99 0.00 4470680.99 288582.77 4759263.76 4267819.30 6324.64 25.53 2409.83 506.69
PERIMETER_BOT_ZN_2 4636585.63 0.00 4636585.63 192388.38 4828974.01 2750345.05 3702.78 7.96 5049.26 506.69
PERIMETER_BOT_ZN_1 7642999.10 0.00 7642999.10 288582.77 7931581.87 4267912.63 3705.15 7.20 5047.65 506.69
PERIMETER_BOT_ZN_4 5704160.52 0.00 5704160.52 192388.38 5896548.90 2750345.05 3662.86 3.84 5093.29 506.69
PERIMETER_MID_ZN_3 38717503.79 0.00 38717503.79 676813.33 39394317.12 42678193.03 6137.93 48.93 2573.14 607.55
PERIMETER_MID_ZN_2 45619322.14 0.00 45619322.14 451208.58 46070530.73 27503450.52 4025.78 3.28 4730.95 1516.55
PERIMETER_MID_ZN_1 74569844.50 0.00 74569844.50 676813.33 75246657.83 42679126.28 4029.77 2.75 4727.48 607.55
PERIMETER_MID_ZN_4 41052290.81 0.00 41052290.81 451208.58 41503499.39 27503450.52 4026.99 0.73 4732.28 607.55
PERIMETER_TOP_ZN_3 4244571.96 0.00 4244571.96 840343.21 5084915.18 4267819.30 4153.17 5.62 4601.21 415.65
PERIMETER_TOP_ZN_2 4355340.15 0.00 4355340.15 560228.43 4915568.58 2750345.05 4125.04 1.43 4633.53 415.65
PERIMETER_TOP_ZN_1 7101361.52 0.00 7101361.52 840343.21 7941704.73 4267912.63 4125.04 0.75 4634.21 415.65
PERIMETER_TOP_ZN_4 3968592.71 0.00 3968592.71 560228.43 4528821.13 2750345.05 4124.39 0.45 4635.16 415.62
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.50E+10 0.00 0.50E+10 26323523.88 0.50E+10 0.50E+10 7164.25 4386.05 5197.46 2105.31


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.8438 0.0000 1.8438 0.0000 1.8438 1.2002 1448.87 2044.03 2450.11
CORE_BOTTOM 1.5181 0.0000 1.5181 0.0000 1.5181 1.0778 2836.12 37.17 3069.72
CORE_MID 12.5228 0.0000 12.5228 0.0000 12.5228 10.7782 3905.81 20.64 2016.55
CORE_TOP 1.1734 0.0000 1.1734 0.0000 1.1734 1.0778 4157.29 18.51 1767.21
PERIMETER_BOT_ZN_3 0.1956 0.0000 0.1956 0.0065 0.2020 0.1353 3817.69 20.88 2104.43
PERIMETER_BOT_ZN_2 0.2036 0.0000 0.2036 0.0043 0.2079 0.0872 1258.55 4.89 4679.57
PERIMETER_BOT_ZN_1 0.3373 0.0000 0.3373 0.0065 0.3438 0.1353 1259.99 3.83 4679.17
PERIMETER_BOT_ZN_4 0.2494 0.0000 0.2494 0.0043 0.2537 0.0872 1230.99 2.94 4709.07
PERIMETER_MID_ZN_3 1.7392 0.0000 1.7392 0.0152 1.7544 1.3533 3437.12 47.67 2458.21
PERIMETER_MID_ZN_2 1.8717 0.0000 1.8717 0.0109 1.8825 0.8721 1342.66 2.97 3688.37
PERIMETER_MID_ZN_1 3.3778 0.0000 3.3778 0.0152 3.3930 1.3533 1345.32 2.53 4595.15
PERIMETER_MID_ZN_4 1.8397 0.0000 1.8397 0.0101 1.8499 0.8721 1342.77 0.51 4599.72
PERIMETER_TOP_ZN_3 0.1934 0.0000 0.1934 0.0189 0.2123 0.1353 1417.79 5.62 4519.58
PERIMETER_TOP_ZN_2 0.1995 0.0000 0.1995 0.0126 0.2121 0.0872 1393.05 1.14 4548.81
PERIMETER_TOP_ZN_1 0.3255 0.0000 0.3255 0.0189 0.3444 0.1353 1392.71 0.64 4549.65
PERIMETER_TOP_ZN_4 0.1807 0.0000 0.1807 0.0126 0.1933 0.0872 1392.18 0.34 4550.48
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 221.3432 0.0000 221.3432 0.5991 221.9424 158.4706 4347.25 4368.84 4754.69


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 80350273.86 0.00 80350273.86 48026705.38 3694.17 3.53 5062.30 506.69
VAV_MID WITH REHEAT 0.67E+09 0.00 0.67E+09 0.48E+09 4037.63 1.86 4720.51 607.55
VAV_TOP WITH REHEAT 63825324.41 0.00 63825324.41 48026705.38 4128.08 0.88 4631.04 415.30
CAV_BAS 56978023.57 0.00 56978023.57 37848132.68 4092.55 3.72 4663.73 226.65
AIRLOOP DATACENTER BASEMENT 7431423.23 0.00 7431423.23 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 343300.97 0.00 343300.97 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3433009.67 0.00 3433009.67 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 343300.97 0.00 343300.97 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 3.5188 0.0000 3.5188 1.5229 1250.22 1.29 4691.49
VAV_MID WITH REHEAT 30.2700 0.0000 30.2700 15.2292 1350.77 1.83 4590.40
VAV_TOP WITH REHEAT 2.9125 0.0000 2.9125 1.5229 1394.84 0.59 4547.58
CAV_BAS 2.5911 0.0000 2.5911 1.2002 1415.55 1.69 4525.76
AIRLOOP DATACENTER BASEMENT 0.3473 0.0000 0.3473 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0160 0.0000 0.0160 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1605 0.0000 0.1605 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0160 0.0000 0.0160 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.00 3038.38 0.00 0.00 0.00 2329.92 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.00 3108.89 0.00 0.00 0.00 2415.68 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.00 2574.76 0.00 0.00 0.00 2635.58 0.00 0.00 0.00
CAV_BAS 0.00 2035.17 2828.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 6.0349 0.0000 0.0000 0.0000 2.4208 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 49.2886 0.0000 0.0000 0.0000 23.4467 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 5.1415 0.0000 0.0000 0.0000 2.3562 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.6867 4.6007 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4756 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0220 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2197 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0220 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1388
Defaulted Fields 1179
Fields with Defaults 3942
Autosized Fields 334
Autosizable Fields 413
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
Electricity:Building 17999.92 247233.96 29-JAN-11:10 1055078.17 01-DEC-08:10
Electricity:Zone:BASEMENT 602.14 14319.77 01-JAN-00:10 28977.00 02-JAN-08:10
Electricity:SpaceType:GENERAL 17999.92 247233.96 29-JAN-11:10 1055078.17 01-DEC-08:10
InteriorLights:Electricity 2786.51 13024.70 29-JAN-11:10 261074.09 02-JAN-08:10
InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2786.51 13024.70 29-JAN-11:10 261074.09 02-JAN-08:10
LightsWired:InteriorLights:Electricity 2786.51 13024.70 29-JAN-11:10 261074.09 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2786.51 13024.70 29-JAN-11:10 261074.09 02-JAN-08:10
Electricity:Zone:CORE_BOTTOM 480.91 6817.20 01-JAN-00:10 32066.15 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:CORE_MID 4809.09 68171.81 01-JAN-00:10 320660.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
Electricity:Zone:CORE_TOP 480.91 6817.18 01-JAN-00:10 32066.08 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 55.35 818.50 29-JAN-11:10 4026.32 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 15.00 59.73 29-JAN-11:10 1750.00 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 15.00 59.73 29-JAN-11:10 1750.00 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_2 35.60 527.47 15-JAN-11:30 2594.71 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 9.60 38.49 15-JAN-11:30 1127.77 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 9.60 38.49 15-JAN-11:30 1127.77 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_1 55.06 818.51 08-JAN-11:20 4026.39 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 14.72 59.73 08-JAN-11:20 1750.04 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 14.72 59.73 08-JAN-11:20 1750.04 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_4 35.58 527.47 22-JAN-11:50 2594.70 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 9.58 38.49 22-JAN-11:50 1127.77 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 9.58 38.49 22-JAN-11:50 1127.77 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_3 553.68 8184.99 29-JAN-11:10 40263.18 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 150.26 597.26 29-JAN-11:10 17500.00 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 150.26 597.26 29-JAN-11:10 17500.00 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_2 356.06 5274.72 16-JAN-11:30 25947.12 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 96.08 384.90 16-JAN-11:30 11277.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 96.08 384.90 16-JAN-11:30 11277.66 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_1 550.83 8185.12 08-JAN-11:30 40263.91 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 147.40 597.27 08-JAN-11:30 17500.38 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 147.40 597.27 08-JAN-11:30 17500.38 02-JAN-08:10
Electricity:Zone:PERIMETER_MID_ZN_4 355.85 5274.69 22-JAN-12:00 25947.03 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 95.87 384.90 22-JAN-12:00 11277.66 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 95.87 384.90 22-JAN-12:00 11277.66 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_3 55.37 818.50 29-JAN-11:10 4026.32 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 15.03 59.73 29-JAN-11:10 1750.00 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 15.03 59.73 29-JAN-11:10 1750.00 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_2 35.61 527.47 16-JAN-11:30 2594.71 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 9.61 38.49 16-JAN-11:30 1127.77 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 9.61 38.49 16-JAN-11:30 1127.77 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_1 55.08 818.51 08-JAN-11:30 4026.39 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 14.74 59.73 08-JAN-11:30 1750.04 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 14.74 59.73 08-JAN-11:30 1750.04 02-JAN-08:10
Electricity:Zone:PERIMETER_TOP_ZN_4 35.59 527.47 22-JAN-12:00 2594.70 02-JAN-08:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 9.59 38.49 22-JAN-12:00 1127.77 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 9.59 38.49 22-JAN-12:00 1127.77 02-JAN-08:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7544.97 95151.24 01-JAN-00:10 384008.34 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1585.20 19711.13 01-JAN-00:10 81995.25 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 1092.79 4713.38 12-JAN-05:50 323087.16 30-JUN-12:20
HeatRejection:Electricity 542.16 980.41 12-JAN-08:00 78538.83 29-JUN-10:20
General:HeatRejection:Electricity 542.16 980.41 12-JAN-08:00 78538.83 29-JUN-10:20
Electricity:HVAC 4974.59 74631.03 01-JAN-12:40 418392.84 11-AUG-15:40
ExteriorEquipment:Electricity 1914.41 28294.68 01-JAN-00:10 117204.73 02-JAN-08:20
Transformer:ExteriorEquipment:Electricity 59.79 1112.61 01-JAN-00:10 3726.76 01-DEC-08:20
ElectricityPurchased:Facility 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
ElectricityPurchased:Plant 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
Cogeneration:ElectricityPurchased 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
General:Cogeneration:ElectricityPurchased 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
ElectricityNet:Plant 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
Cogeneration:ElectricityNet 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
General:Cogeneration:ElectricityNet 26377.30 362095.09 01-JAN-11:20 1805522.45 11-AUG-15:40
Fans:Electricity 2303.01 42378.87 02-JAN-06:00 257925.20 12-JUL-12:10
General:Fans:Electricity 2303.01 42378.87 02-JAN-06:00 257925.20 12-JUL-12:10
ExteriorLights:Electricity 455.38 0.00 01-JAN-11:20 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 455.38 0.00 01-JAN-11:20 37611.08 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 57.42 0.00 01-JAN-00:10 6524.59 02-JAN-07:10
General:HeatRecovery:Electricity 57.42 0.00 01-JAN-00:10 6524.59 02-JAN-07:10
Cooling:Electricity 2538.70 25561.58 12-JAN-08:00 352160.95 11-AUG-15:20
General:Cooling:Electricity 2538.70 25561.58 12-JAN-08:00 352160.95 11-AUG-15:20
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 228.85 0.00 03-JUN-17:10 23732.62 28-DEC-07:10
General:Humidifier:Electricity 228.85 0.00 03-JUN-17:10 23732.62 28-DEC-07:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 337.45 3496.22 02-JAN-04:40 51515.43 11-AUG-15:40
General:Pumps:Electricity 337.45 3496.22 02-JAN-04:40 51515.43 11-AUG-15:40
WIRED_LTG_ELECTRICITY 78.30 0.00 01-JAN-00:10 7336.18 02-JAN-08:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 5964.52 5695.87 02-JAN-06:00 2658842.51 27-FEB-07:20
NaturalGas:Plant 5964.52 5695.87 02-JAN-06:00 2658842.51 27-FEB-07:20
Heating:NaturalGas 5099.07 0.00 01-JAN-00:40 2627511.03 27-FEB-07:20
Boiler:Heating:NaturalGas 5099.07 0.00 01-JAN-00:40 2627511.03 27-FEB-07:20
WaterSystems:NaturalGas 865.45 5695.87 02-JAN-05:30 87759.79 03-JAN-13:00
Water Heater:WaterSystems:NaturalGas 865.45 5695.87 02-JAN-05:30 87759.79 03-JAN-13:00


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 13500.08 124316.04 12-JAN-08:00 1979497.53 11-AUG-15:40
PlantLoopCoolingDemand:HVAC 13500.08 124316.04 12-JAN-08:00 1979497.53 11-AUG-15:40
CoolingCoils:PlantLoopCoolingDemand 13500.08 124316.04 12-JAN-08:00 1979497.53 11-AUG-15:40


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 3506.43 0.00 21-JUL-23:10 0.00 20-JUL-15:10
Water:HVAC 85.13 0.00 03-JUN-17:10 0.00 28-DEC-07:10
Humidifier:Water 85.13 0.00 03-JUN-17:10 0.00 28-DEC-07:10
General:Humidifier:Water 85.13 0.00 03-JUN-17:10 0.00 28-DEC-07:10
MainsWater:Facility 3506.43 0.00 21-JUL-23:10 0.00 20-JUL-15:10
MainsWater:HVAC 85.13 0.00 03-JUN-17:10 0.00 28-DEC-07:10
Humidifier:MainsWater 85.13 0.00 03-JUN-17:10 0.00 28-DEC-07:10
General:Humidifier:MainsWater 85.13 0.00 03-JUN-17:10 0.00 28-DEC-07:10
Water:Plant 3421.30 0.00 01-JAN-00:10 0.00 20-JUL-15:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 3421.30 0.00 01-JAN-00:10 0.00 20-JUL-15:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 1141.13 0.00 01-JAN-00:10 0.00 20-JUL-15:10
General:HeatRejection:Water 1141.13 0.00 01-JAN-00:10 0.00 20-JUL-15:10
HeatRejection:MainsWater 1141.13 0.00 01-JAN-00:10 0.00 20-JUL-15:10
General:HeatRejection:MainsWater 1141.13 0.00 01-JAN-00:10 0.00 20-JUL-15:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 46533.06 203775.84 01-JAN-03:20 8086865.14 11-AUG-15:20
EnergyTransfer:Building 18317.94 86440.70 02-JAN-04:40 1600317.61 04-DEC-06:20
EnergyTransfer:Zone:BASEMENT 552.40 0.00 01-JAN-00:10 69575.03 05-SEP-05:10
Heating:EnergyTransfer 2278.60 0.00 01-FEB-01:00 1487493.71 02-JAN-06:20
Heating:EnergyTransfer:Zone:BASEMENT 2.38 0.00 01-JAN-00:10 14829.06 29-JUL-16:10
General:Heating:EnergyTransfer 2278.60 0.00 01-FEB-01:00 1487493.71 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:BASEMENT 2.38 0.00 01-JAN-00:10 14829.06 29-JUL-16:10
Cooling:EnergyTransfer 16039.34 79894.80 02-JAN-02:00 1575683.12 10-AUG-15:30
Cooling:EnergyTransfer:Zone:BASEMENT 550.01 0.00 01-JAN-00:10 69575.03 05-SEP-05:10
General:Cooling:EnergyTransfer 16039.34 79894.80 02-JAN-02:00 1575683.12 10-AUG-15:30
General:Cooling:EnergyTransfer:Zone:BASEMENT 550.01 0.00 01-JAN-00:10 69575.03 05-SEP-05:10
EnergyTransfer:Zone:CORE_BOTTOM 515.10 0.00 01-JAN-00:40 50486.23 05-SEP-05:10
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.06 0.00 01-JAN-00:10 17367.69 02-JAN-06:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.06 0.00 01-JAN-00:10 17367.69 02-JAN-06:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 515.03 0.00 01-JAN-00:40 50486.23 05-SEP-05:10
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 515.03 0.00 01-JAN-00:40 50486.23 05-SEP-05:10
EnergyTransfer:Zone:CORE_MID 3766.58 0.00 01-JAN-00:40 502890.65 02-JAN-05:10
Heating:EnergyTransfer:Zone:CORE_MID 43.80 0.00 01-JAN-00:20 502890.65 02-JAN-05:10
General:Heating:EnergyTransfer:Zone:CORE_MID 43.80 0.00 01-JAN-00:20 502890.65 02-JAN-05:10
Cooling:EnergyTransfer:Zone:CORE_MID 3722.78 0.00 01-JAN-00:40 419506.38 31-JUL-05:10
General:Cooling:EnergyTransfer:Zone:CORE_MID 3722.78 0.00 01-JAN-00:40 419506.38 31-JUL-05:10
EnergyTransfer:Zone:CORE_TOP 338.84 0.00 01-JAN-00:40 69060.32 30-JAN-05:30
Heating:EnergyTransfer:Zone:CORE_TOP 59.74 0.00 01-JAN-00:40 69060.32 30-JAN-05:30
General:Heating:EnergyTransfer:Zone:CORE_TOP 59.74 0.00 01-JAN-00:40 69060.32 30-JAN-05:30
Cooling:EnergyTransfer:Zone:CORE_TOP 279.10 0.00 01-JAN-00:20 45024.59 21-JUL-15:20
General:Cooling:EnergyTransfer:Zone:CORE_TOP 279.10 0.00 01-JAN-00:20 45024.59 21-JUL-15:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 58.34 0.00 01-JAN-00:40 12749.50 11-JUL-05:10
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 9.67 0.00 01-JAN-00:40 11087.22 30-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 9.67 0.00 01-JAN-00:40 11087.22 30-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 48.67 0.00 01-JAN-00:20 12749.50 11-JUL-05:10
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 48.67 0.00 01-JAN-00:20 12749.50 11-JUL-05:10
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 58.83 0.00 01-JAN-00:40 15006.03 07-JUL-08:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 8.44 0.00 01-JAN-00:40 8797.70 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 8.44 0.00 01-JAN-00:40 8797.70 02-JAN-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 50.39 0.00 01-JAN-00:20 15006.03 07-JUL-08:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 50.39 0.00 01-JAN-00:20 15006.03 07-JUL-08:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 98.74 0.00 01-JAN-00:40 22462.40 10-AUG-13:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 12.67 0.00 01-JAN-00:40 14620.36 30-JAN-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 12.67 0.00 01-JAN-00:40 14620.36 30-JAN-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 86.08 0.00 01-JAN-00:20 22462.40 10-AUG-13:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 86.08 0.00 01-JAN-00:20 22462.40 10-AUG-13:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 72.42 0.00 01-JAN-00:40 14818.89 10-AUG-16:50
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.32 0.00 01-JAN-00:10 6578.45 30-JAN-05:20
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 1.32 0.00 01-JAN-00:10 6578.45 30-JAN-05:20
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 71.10 0.00 01-JAN-00:40 14818.89 10-AUG-16:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 71.10 0.00 01-JAN-00:40 14818.89 10-AUG-16:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 783.24 0.00 01-JAN-00:40 127651.91 29-JAN-00:20
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 464.90 0.00 01-JAN-00:40 127651.91 29-JAN-00:20
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 464.90 0.00 01-JAN-00:40 127651.91 29-JAN-00:20
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 318.34 0.00 01-JAN-00:10 105716.77 11-JUL-05:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 318.34 0.00 01-JAN-00:10 105716.77 11-JUL-05:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 720.79 0.00 01-JAN-00:40 160913.83 07-JUL-08:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 296.03 0.00 01-JAN-00:40 151581.40 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 296.03 0.00 01-JAN-00:40 151581.40 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 424.76 0.00 01-JAN-00:20 160913.83 07-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 424.76 0.00 01-JAN-00:20 160913.83 07-JUL-08:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1106.48 0.00 01-JAN-00:40 242108.91 10-AUG-13:40
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 350.92 0.00 01-JAN-00:40 225742.85 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 350.92 0.00 01-JAN-00:40 225742.85 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 755.56 0.00 01-JAN-00:20 242108.91 10-AUG-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 755.56 0.00 01-JAN-00:20 242108.91 10-AUG-13:40
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 599.58 0.00 01-JAN-00:40 144261.35 30-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 238.12 0.00 01-JAN-00:40 144261.35 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 238.12 0.00 01-JAN-00:40 144261.35 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 361.46 0.00 01-JAN-00:20 131253.46 06-JUL-17:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 361.46 0.00 01-JAN-00:20 131253.46 06-JUL-17:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 121.17 0.00 01-JAN-00:40 17496.87 29-JAN-00:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 92.63 0.00 01-JAN-00:40 17496.87 29-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 92.63 0.00 01-JAN-00:40 17496.87 29-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 28.54 0.00 01-JAN-00:10 9601.25 11-JUL-05:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 28.54 0.00 01-JAN-00:10 9601.25 11-JUL-05:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 94.39 0.00 01-JAN-00:40 17209.42 30-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 56.67 0.00 01-JAN-00:40 17209.42 30-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 56.67 0.00 01-JAN-00:40 17209.42 30-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 37.71 0.00 01-JAN-00:10 16051.01 07-JUL-08:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 37.71 0.00 01-JAN-00:10 16051.01 07-JUL-08:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 138.84 0.00 01-JAN-00:40 26083.25 30-JAN-05:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 73.07 0.00 01-JAN-00:40 26083.25 30-JAN-05:30
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 73.07 0.00 01-JAN-00:40 26083.25 30-JAN-05:30
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 65.76 0.00 01-JAN-00:10 24490.61 10-AUG-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 65.76 0.00 01-JAN-00:10 24490.61 10-AUG-13:50
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 80.38 0.00 01-JAN-00:40 17153.19 30-JAN-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 48.48 0.00 01-JAN-00:40 17153.19 30-JAN-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 48.48 0.00 01-JAN-00:40 17153.19 30-JAN-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 31.90 0.00 01-JAN-00:10 13507.12 11-JUL-17:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 31.90 0.00 01-JAN-00:10 13507.12 11-JUL-17:40
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 52.49 0.00 01-JAN-00:40 11601.19 02-JAN-06:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 16.50 0.00 01-JAN-00:40 11601.19 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 16.50 0.00 01-JAN-00:40 11601.19 02-JAN-06:20
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 35.99 0.00 01-JAN-00:10 8432.56 24-JUL-05:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 35.99 0.00 01-JAN-00:10 8432.56 24-JUL-05:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 602.43 0.00 01-JAN-00:40 209057.82 02-JAN-06:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 354.56 0.00 01-JAN-00:40 209057.82 02-JAN-06:20
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 354.56 0.00 01-JAN-00:40 209057.82 02-JAN-06:20
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 247.87 0.00 01-JAN-00:10 66483.96 24-JUL-15:30
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 247.87 0.00 01-JAN-00:10 66483.96 24-JUL-15:30
EnergyTransfer:Zone:TOPFLOOR_PLENUM 165.98 0.00 01-JAN-00:40 34260.26 27-FEB-05:10
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 139.62 0.00 01-JAN-00:40 34260.26 27-FEB-05:10
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 139.62 0.00 01-JAN-00:40 34260.26 27-FEB-05:10
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 26.36 0.00 01-JAN-00:10 14558.24 21-JUL-14:40
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 26.36 0.00 01-JAN-00:10 14558.24 21-JUL-14:40
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 128.23 5.31 14-JAN-01:00 8506.34 20-APR-18:50
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.20 0.00 02-JAN-07:20 575.30 01-JAN-19:50
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.20 0.00 02-JAN-07:20 575.30 01-JAN-19:50
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 128.04 0.00 01-JAN-00:10 8506.34 20-APR-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 128.04 0.00 01-JAN-00:10 8506.34 20-APR-18:50
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1055.50 5.09 26-FEB-23:30 80923.23 20-APR-18:50
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 7.49 0.00 02-JAN-07:20 5749.59 10-JAN-00:20
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 7.49 0.00 02-JAN-07:20 5749.59 10-JAN-00:20
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1048.01 0.00 01-JAN-00:10 80923.23 20-APR-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1048.01 0.00 01-JAN-00:10 80923.23 20-APR-18:50
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 92.30 1.21 28-SEP-08:50 8069.81 20-APR-18:50
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.34 0.00 02-JAN-07:20 605.71 10-JAN-00:20
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 1.34 0.00 02-JAN-07:20 605.71 10-JAN-00:20
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 90.96 0.00 01-JAN-00:10 8069.81 20-APR-18:50
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 90.96 0.00 01-JAN-00:10 8069.81 20-APR-18:50
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7114.92 79890.64 02-JAN-01:50 368008.18 28-AUG-16:00
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7114.92 79890.64 02-JAN-01:50 368008.18 28-AUG-16:00
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7114.92 79890.64 02-JAN-01:50 368008.18 28-AUG-16:00
PlantLoopHeatingDemand:Facility 4472.58 0.00 01-JAN-00:40 2248250.90 27-FEB-07:10
PlantLoopHeatingDemand:Plant 538.62 0.00 01-JAN-00:10 61984.71 17-MAR-12:00
WaterSystems:PlantLoopHeatingDemand 538.62 0.00 01-JAN-00:10 61984.71 17-MAR-12:00
General:WaterSystems:PlantLoopHeatingDemand 538.62 0.00 01-JAN-00:10 61984.71 17-MAR-12:00
EnergyTransfer:HVAC 18992.14 117237.14 01-JAN-03:20 2420955.07 27-FEB-07:10
HeatingCoils:EnergyTransfer 3933.96 0.00 01-JAN-00:40 2227661.53 27-FEB-07:10
PlantLoopHeatingDemand:HVAC 3933.96 0.00 01-JAN-00:40 2227661.53 27-FEB-07:10
HeatingCoils:PlantLoopHeatingDemand 3933.96 0.00 01-JAN-00:40 2227661.53 27-FEB-07:10
CoolingCoils:EnergyTransfer 11174.56 98754.46 12-JAN-08:00 1820444.75 11-AUG-15:40
HeatRecoveryForHeating:EnergyTransfer 3881.85 0.00 01-JAN-00:10 877920.79 26-JAN-18:00
HeatRecoveryForCooling:EnergyTransfer 1.77 0.00 01-JAN-00:10 136095.75 29-JUL-16:00
EnergyTransfer:Plant 9222.97 0.00 01-JAN-00:40 4708696.17 11-AUG-15:20
LoopToLoop:EnergyTransfer 1598.06 -136.17 07-JAN-12:10 1497446.01 11-AUG-15:20
WaterSystems:EnergyTransfer 538.62 0.00 01-JAN-00:10 61984.71 17-MAR-12:00
WaterUse:WaterSystems:EnergyTransfer 538.62 0.00 01-JAN-00:10 61984.71 17-MAR-12:00
Boilers:EnergyTransfer 3913.40 0.00 01-JAN-00:40 2188694.13 27-FEB-07:20
Chillers:EnergyTransfer 1479.85 0.00 01-JAN-00:10 1486815.83 11-AUG-15:20
HeatRejection:EnergyTransfer 1693.04 0.00 01-JAN-00:10 1681435.79 11-AUG-15:20
General:HeatRejection:EnergyTransfer 1693.04 0.00 01-JAN-00:10 1681435.79 11-AUG-15:20
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 2.385 -550.011 0.000 0.000 94.145 177.742 424.397 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -148.657
CORE_BOTTOM 0.000 0.000 0.061 -515.035 0.000 0.000 84.221 159.625 321.286 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -50.158
CORE_MID 0.000 0.000 43.799 -3722.784 0.000 0.000 882.617 1596.246 3212.845 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -2012.723
CORE_TOP 0.000 0.000 59.739 -279.098 0.000 0.000 91.937 159.625 321.285 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -353.488
PERIMETER_BOT_ZN_3 0.000 0.000 9.669 -48.667 0.000 0.000 11.400 15.005 40.342 21.947 0.000 0.004 35.351 0.000 -77.810 0.000 -7.242 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 8.438 -50.392 0.000 0.000 7.330 9.603 25.998 50.642 0.000 0.003 2.041 0.000 -48.867 0.000 -4.796 -0.001
PERIMETER_BOT_ZN_1 0.000 0.000 12.666 -86.077 0.000 0.000 11.338 14.720 40.343 99.635 0.000 0.004 0.000 0.000 -69.488 0.000 -7.243 -15.897
PERIMETER_BOT_ZN_4 0.000 0.000 1.320 -71.096 0.000 0.000 7.228 9.580 25.998 34.543 0.000 0.002 50.804 0.000 -53.244 0.000 -5.136 0.000
PERIMETER_MID_ZN_3 0.000 0.000 464.905 -318.337 0.000 0.000 116.962 150.256 403.423 224.565 0.000 0.086 0.001 0.000 -732.736 0.000 -157.804 -151.319
PERIMETER_MID_ZN_2 0.000 0.000 296.024 -424.763 0.000 0.000 54.968 96.080 259.981 507.135 0.000 0.058 0.006 0.000 -467.414 0.000 -106.871 -215.198
PERIMETER_MID_ZN_1 0.000 0.000 350.916 -755.555 0.000 0.000 114.928 147.399 403.429 996.372 0.000 0.078 0.009 0.000 -675.666 0.000 -164.332 -417.568
PERIMETER_MID_ZN_4 0.000 0.000 238.122 -361.455 0.000 0.000 75.367 95.872 259.979 352.768 0.000 0.048 0.001 0.000 -486.931 0.000 -108.995 -64.778
PERIMETER_TOP_ZN_3 0.000 0.000 92.627 -28.540 0.000 0.000 11.891 15.026 40.342 23.076 0.000 0.010 0.001 0.000 -70.630 0.000 -18.792 -65.011
PERIMETER_TOP_ZN_2 0.000 0.000 56.674 -37.713 0.000 0.000 7.538 9.608 25.998 51.081 0.000 0.006 0.001 0.000 -45.206 0.000 -12.801 -55.186
PERIMETER_TOP_ZN_1 0.000 0.000 73.074 -65.762 0.000 0.000 11.652 14.740 40.343 100.290 0.000 0.009 0.001 0.000 -65.113 0.000 -19.601 -89.633
PERIMETER_TOP_ZN_4 0.000 0.000 48.480 -31.899 0.000 0.000 7.629 9.587 25.998 35.558 0.000 0.006 0.001 0.000 -47.119 0.000 -13.054 -35.185
DATACENTER_BOT_ZN_6 0.000 0.000 0.199 -128.036 0.000 0.000 0.951 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -31.634
DATACENTER_MID_ZN_6 0.000 0.000 7.486 -1048.011 0.000 0.000 9.587 46.396 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -554.263
DATACENTER_TOP_ZN_6 0.000 0.000 1.336 -90.961 0.000 0.000 0.967 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -69.863
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7114.923 0.000 0.000 20.557 50.116 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -450.606
GROUNDFLOOR_PLENUM 16.496 -35.991 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.005 34.670 0.000 0.000 0.000 -15.179 -0.001
MIDFLOOR_PLENUM 354.568 -247.870 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.091 153.700 0.000 0.000 0.000 -260.490 -0.007
TOPFLOOR_PLENUM 139.622 -26.358 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.006 0.001 0.000 0.000 0.000 -28.261 -85.009
Total Facility 510.686 -310.220 1767.921 -15729.114 0.000 0.000 1623.211 2786.505 15213.411 2497.612 0.000 0.416 276.587 0.000 -2840.223 0.000 -930.595 -4866.185


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 10-JUL-03:02 0.00 0.00 0.00 -105834.05 0.00 0.00 0.00 862.23 13457.54 0.00 0.00 0.00 91514.28 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 05-SEP-03:02 0.00 0.00 0.00 -90771.26 0.00 0.00 0.00 774.34 8057.15 0.00 0.00 0.00 81939.77 0.00 -0.00 0.00 0.00 0.00
CORE_MID 14-AUG-03:02 0.00 0.00 0.00 -818280.09 0.00 0.00 0.00 7743.41 80571.20 0.00 0.00 0.00 729965.49 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 24-JUL-03:02 0.00 0.00 0.00 -79155.32 0.00 0.00 0.00 774.34 8057.12 0.00 0.00 0.00 70323.86 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 11-JUL-04:54 0.00 0.00 0.00 -15688.85 0.00 0.00 0.00 119.45 1011.70 13186.62 0.00 0.00 1566.87 0.00 -0.00 0.00 -195.79 0.00
PERIMETER_BOT_ZN_2 14-MAY-09:31 0.00 0.00 0.00 -23170.27 0.00 0.00 20.76 38.49 488.98 16793.08 0.00 0.00 6038.75 0.00 -0.00 0.00 -209.79 0.00
PERIMETER_BOT_ZN_1 23-JUL-12:41 0.00 0.00 0.00 -36149.34 0.00 0.00 30.79 59.73 758.78 26869.54 0.00 0.00 8481.78 0.00 -0.00 0.00 -51.29 0.00
PERIMETER_BOT_ZN_4 27-AUG-17:12 0.00 0.00 0.00 -25482.23 0.00 0.00 0.00 38.49 488.98 15511.23 0.00 0.00 9683.32 0.00 -0.00 0.00 -239.79 0.00
PERIMETER_MID_ZN_3 11-JUL-05:03 0.00 0.00 0.00 -133262.04 0.00 0.00 933.79 1194.52 10116.97 126272.89 0.00 0.00 0.00 0.00 -0.00 0.00 -1073.07 -4183.06
PERIMETER_MID_ZN_2 21-MAY-09:01 0.00 0.00 0.00 -243674.77 0.00 0.00 207.34 384.90 4889.82 185891.00 0.00 0.00 63158.91 0.00 -0.00 0.00 -10857.19 0.00
PERIMETER_MID_ZN_1 21-MAY-13:02 0.00 0.00 0.00 -358824.28 0.00 0.00 337.68 597.27 7587.84 272547.70 0.00 0.00 91341.02 0.00 -0.00 0.00 -13587.23 0.00
PERIMETER_MID_ZN_4 21-MAY-18:22 0.00 0.00 0.00 -233435.88 0.00 0.00 0.00 384.90 4889.79 126128.38 0.00 0.00 106088.47 0.00 -0.00 0.00 -4055.66 0.00
PERIMETER_TOP_ZN_3 11-JUL-05:03 0.00 0.00 0.00 -16742.80 0.00 0.00 95.34 119.45 1011.70 12626.44 0.00 0.00 3016.53 0.00 -0.00 0.00 -126.66 0.00
PERIMETER_TOP_ZN_2 23-JUL-11:51 0.00 0.00 0.00 -23557.81 0.00 0.00 21.95 38.49 488.98 5199.33 0.00 0.00 17809.06 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 23-JUL-12:31 0.00 0.00 0.00 -40428.76 0.00 0.00 28.65 59.73 758.78 26734.28 0.00 0.00 12986.76 0.00 -0.00 0.00 -139.43 0.00
PERIMETER_TOP_ZN_4 21-MAY-17:42 0.00 0.00 0.00 -23686.47 0.00 0.00 0.00 38.49 488.98 14596.18 0.00 0.00 9084.02 0.00 -0.00 0.00 -521.19 0.00
DATACENTER_BOT_ZN_6 20-APR-18:50 0.00 0.00 0.00 -8505.80 0.00 0.00 10.62 135.03 7794.42 0.00 0.00 0.00 565.73 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 20-APR-18:50 0.00 0.00 0.00 -80917.95 0.00 0.00 106.16 1350.33 77944.22 0.00 0.00 0.00 1517.25 0.00 -0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 20-APR-18:50 0.00 0.00 0.00 -8069.28 0.00 0.00 10.62 135.03 7794.42 0.00 0.00 0.00 129.21 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 28-AUG-16:00 0.00 0.00 0.00 -368013.30 0.00 0.00 2183.09 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -18178.13
GROUNDFLOOR_PLENUM 24-JUL-05:15 0.00 -12319.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12401.59 0.00 -0.00 0.00 -81.63 0.00
MIDFLOOR_PLENUM 23-OCT-03:11 0.00 -83505.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 106045.65 0.00 -0.00 0.00 -22539.97 0.00
TOPFLOOR_PLENUM 21-JUL-14:40 0.00 -14560.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.80 14534.20 0.00 -0.00 0.00 0.00 0.00
Total Facility 10-AUG-05:02 0.00 27286.89 0.00 -1854749.32 0.00 0.00 15920.51 26543.75 623236.89 217838.53 0.00 0.00 979974.04 0.00 -26289.80 0.00 -9761.48 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 29-JUL-16:02 0.00 0.00 16098.00 0.00 0.00 0.00 520.12 862.23 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -30937.89
CORE_BOTTOM 02-JAN-05:01 0.00 0.00 23301.67 0.00 0.00 0.00 0.00 1548.68 8057.15 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -32907.51
CORE_MID 02-JAN-04:01 0.00 0.00 585136.42 0.00 0.00 0.00 0.00 7743.41 80571.20 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -673451.02
CORE_TOP 01-JAN-23:22 0.00 0.00 77295.64 0.00 0.00 0.00 0.00 774.34 6042.84 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -84112.82
PERIMETER_BOT_ZN_3 02-JAN-04:01 0.00 0.00 13405.02 0.00 0.00 0.00 0.00 97.23 1011.70 0.00 0.00 0.00 0.00 0.00 -3932.66 0.00 -489.22 -10092.07
PERIMETER_BOT_ZN_2 02-JAN-04:01 0.00 0.00 16187.31 0.00 0.00 0.00 0.00 62.66 651.98 0.00 0.00 0.00 0.00 0.00 -2599.51 0.00 -328.07 -13974.36
PERIMETER_BOT_ZN_1 30-JAN-04:01 0.00 0.00 25311.35 0.00 0.00 0.00 0.00 97.23 1011.71 0.00 0.00 0.00 0.00 0.00 -5207.64 0.00 -1052.23 -20160.42
PERIMETER_BOT_ZN_4 02-JAN-04:01 0.00 0.00 13952.75 0.00 0.00 0.00 0.00 62.66 651.97 0.00 0.00 0.00 0.00 0.00 -2719.23 0.00 -344.66 -11603.49
PERIMETER_MID_ZN_3 30-JAN-04:11 0.00 0.00 135155.89 0.00 0.00 0.00 0.00 972.26 10116.97 0.00 0.00 0.00 0.00 0.00 -51367.89 0.00 -23352.40 -71524.83
PERIMETER_MID_ZN_2 30-JAN-04:11 0.00 0.00 201321.62 0.00 0.00 0.00 0.00 626.56 6519.76 0.00 0.00 0.00 0.00 0.00 -33439.26 0.00 -15757.54 -159271.15
PERIMETER_MID_ZN_1 30-JAN-04:11 0.00 0.00 304631.75 0.00 0.00 0.00 0.00 972.28 10117.12 0.00 0.00 0.00 0.00 0.00 -50328.32 0.00 -23711.35 -241681.48
PERIMETER_MID_ZN_4 30-JAN-04:11 0.00 0.00 200155.94 0.00 0.00 0.00 0.00 626.56 6519.72 0.00 0.00 0.00 0.00 0.00 -34482.26 0.00 -15861.32 -156958.65
PERIMETER_TOP_ZN_3 30-JAN-05:21 0.00 0.00 18341.34 0.00 0.00 0.00 0.00 194.45 1011.70 0.00 0.00 0.00 0.00 0.00 -5076.20 0.00 -3101.66 -11369.64
PERIMETER_TOP_ZN_2 29-JAN-00:01 0.00 0.00 20434.07 0.00 0.00 0.00 0.00 62.66 488.98 0.00 0.00 0.00 0.00 0.00 -3423.31 0.00 -6019.30 -11543.10
PERIMETER_TOP_ZN_1 29-JAN-00:01 0.00 0.00 32117.21 0.00 0.00 0.00 0.00 97.23 758.78 0.00 0.00 0.00 0.00 0.00 -5021.88 0.00 -9086.58 -18864.76
PERIMETER_TOP_ZN_4 29-JAN-00:01 0.00 0.00 21554.07 0.00 0.00 0.00 0.00 62.66 488.98 0.00 0.00 0.00 0.00 0.00 -3349.36 0.00 -6055.55 -12700.79
DATACENTER_BOT_ZN_6 01-JAN-18:02 0.00 0.00 575.31 0.00 0.00 0.00 0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2546.42
DATACENTER_MID_ZN_6 12-JAN-22:13 0.00 0.00 5799.96 0.00 0.00 0.00 56.71 450.09 19486.06 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -25792.82
DATACENTER_TOP_ZN_6 30-JAN-23:45 0.00 0.00 606.91 0.00 0.00 0.00 6.40 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2584.42
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 02-JAN-06:13 13711.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -114.18 -13597.58
MIDFLOOR_PLENUM 02-JAN-06:13 230356.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -1932.85 -228423.33
TOPFLOOR_PLENUM 12-JAN-05:33 36282.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -36282.08
Total Facility 02-JAN-04:01 -28630.78 88335.23 1631543.18 -88335.23 0.00 0.00 0.00 14504.71 268362.69 0.00 0.00 0.00 0.00 0.00 -148090.07 0.00 -63302.11 -1674387.63



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 11.2466 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.4290 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 108.5770 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 87.8848 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 11.1371 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 9.3604 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.3386 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.3386 0.2248 1.0000 Not calculated 1.2002 0.2248    
AIRLOOP DATACENTER BASEMENT 21.6781 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.6782 0.0156 1.0000 Not calculated 0.3384 0.0156    
AIRLOOP DATACENTER BOT 0.5110 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5110 0.0306 1.0000 Not calculated 0.0156 0.0306    
AIRLOOP DATACENTER MID 4.9089 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.9089 0.0318 1.0000 Not calculated 0.1563 0.0318    
AIRLOOP DATACENTER TOP 0.4957 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4957 0.0315 1.0000 Not calculated 0.0156 0.0315    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 5.6233 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.0725 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 54.2885 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 30.3555 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 5.5685 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 3.1659 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.3386 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.3386 1.0000 1.0000 Not calculated 1.2002 0.2248    
AIRLOOP DATACENTER BASEMENT 21.6781 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.6781 1.0000 1.0000 Not calculated 0.3384 0.0156    
AIRLOOP DATACENTER BOT 0.5110 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.5110 1.0000 1.0000 Not calculated 0.0156 0.0306    
AIRLOOP DATACENTER MID 4.9089 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.9089 1.0000 1.0000 Not calculated 0.1563 0.0318    
AIRLOOP DATACENTER TOP 0.4957 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4957 1.0000 1.0000 Not calculated 0.0156 0.0315    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.3386 5.3386 5.3386 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.7391 5.7391 1.9169 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 53.9800 53.9800 18.7850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2939 5.2939 1.9164 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9329 0.9329 0.2407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2301 1.2301 0.2460 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.8847 1.8847 0.3769 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.4599 1.4599 0.2920 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.5669 8.5669 2.3645 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 12.9844 12.9844 2.5969 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 19.7795 19.7795 3.9559 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 13.2662 13.2662 2.6532 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1232 1.1232 0.3055 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.2928 1.2928 0.2586 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.0518 2.0518 0.4104 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.3753 1.3753 0.2751 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5110 0.5110 0.5110 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.9089 4.9089 4.9089 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4957 0.4957 0.4957 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.6781 21.6781 21.6781 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 11.2466 9.4290 11.2466 3.0725 0.0000 1.0000
VAV_MID WITH REHEAT 108.5770 87.8848 108.5770 30.3555 0.0000 1.0000
VAV_TOP WITH REHEAT 11.1371 9.3604 11.1371 3.1659 0.0000 1.0000
CAV_BAS 5.3386 5.3386 5.3386 5.3386 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.6781 21.6782 21.6781 21.6781 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5110 0.5110 0.5110 0.5110 0.0156 1.0000
AIRLOOP DATACENTER MID 4.9089 4.9089 4.9089 4.9089 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4957 0.4957 0.4957 0.4957 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.3386 5.3386 5.3386 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8696 2.8696 1.9169 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 26.9900 26.9900 18.7850 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6470 2.6470 1.9164 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4664 0.4664 0.2407 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6150 0.6150 0.2460 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9423 0.9423 0.3769 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.7299 0.7299 0.2920 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.2834 4.2834 2.3645 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.4922 6.4922 2.5969 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.8898 9.8898 3.9559 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 6.6331 6.6331 2.6532 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5616 0.5616 0.3055 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6464 0.6464 0.2586 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0259 1.0259 0.4104 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.6877 0.6877 0.2751 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.5110 0.5110 0.5110 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.9089 4.9089 4.9089 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4957 0.4957 0.4957 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.6781 21.6781 21.6781 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 5.6233 3.0725 3.0725 3.0725 0.0000 1.0000
VAV_MID WITH REHEAT 54.2885 30.3555 30.3555 30.3555 0.0000 1.0000
VAV_TOP WITH REHEAT 5.5685 3.1659 3.1659 3.1659 0.0000 1.0000
CAV_BAS 5.3386 5.3386 5.3386 5.3386 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.6781 21.6781 21.6781 21.6781 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.5110 0.5110 0.5110 0.5110 0.0156 1.0000
AIRLOOP DATACENTER MID 4.9089 4.9089 4.9089 4.9089 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4957 0.4957 0.4957 0.4957 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 273.83
Number of hours cooling loads not met 83.83
Number of hours not met 357.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 5099.07 2627511.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 2538.70 352160.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2786.51 261074.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 455.38 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 59.79 3726.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2303.01 257925.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 337.45 51515.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 542.16 78538.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 228.85 23732.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 57.42 6524.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 865.45 87759.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 26377.30
Natural Gas 0.00 5964.52
Additional 0.00 0.00
Total 15213.41 32341.82


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 60.16
Space Heating 0.00
Space Cooling 54.81
Fans (All) 49.72
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 569.45
Subtotal 569.45


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 110.08
Service Water Heating 18.68
Miscellaneous (All) 128.77
Subtotal 128.77


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.62
Space Heating 15.77
Space Cooling 7.85
Fans (All) 7.12
Service Water Heating 2.68
Receptacle Equipment 47.04
Miscellaneous 10.93


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2393. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 8650.17 109.83 0.00 0.00 0.00
CORE_BOTTOM 8756.00 4.00 0.00 0.00 0.00
CORE_MID 8760.00 0.00 0.00 0.00 0.00
CORE_TOP 8760.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8759.00 1.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8750.67 9.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8749.17 10.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8614.33 145.67 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8759.17 0.83 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8745.83 14.17 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8738.17 21.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8734.83 25.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8749.33 10.67 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8743.50 16.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8740.33 19.67 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8742.33 17.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8758.00 2.00 0.00 0.00 0.00
Min 8614.33 0.00 0.00 0.00 0.00
Max 8760.00 145.67 0.00 0.00 0.00
Average 8742.21 17.79 0.00 0.00 0.00
Sum 201070.83 409.17 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 368358.17 257.83 0.00 0.00 0.00
CORE_BOTTOM 330813.00 0.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330813.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 103035.17 359.83 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368358.17 359.83 0.00 0.00 0.00
Average 80308.06 26.86 0.00 0.00 0.00
Sum 1847085.33 617.67 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 8577.33 182.67 0.00 0.00 0.00
CORE_BOTTOM 8696.50 63.50 0.00 0.00 0.00
CORE_MID 8697.50 62.50 0.00 0.00 0.00
CORE_TOP 8734.33 25.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8751.83 8.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8749.33 10.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8750.00 10.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 8635.83 124.17 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8758.83 1.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8744.00 16.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8743.17 16.83 0.00 0.00 0.00
PERIMETER_MID_ZN_4 8739.00 21.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8760.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8745.67 14.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8746.00 14.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 8746.00 14.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 8760.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 8760.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8753.17 6.83 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8758.50 1.50 0.00 0.00 0.00
Min 8577.33 0.00 0.00 0.00 0.00
Max 8760.00 182.67 0.00 0.00 0.00
Average 8734.22 25.78 0.00 0.00 0.00
Sum 200887.00 593.00 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 368133.00 483.00 0.00 0.00 0.00
CORE_BOTTOM 330708.00 105.00 0.00 0.00 0.00
CORE_MID 330721.00 92.00 0.00 0.00 0.00
CORE_TOP 330791.00 22.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 2268.00 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 103395.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 368133.00 483.00 0.00 0.00 0.00
Average 80304.39 30.52 0.00 0.00 0.00
Sum 1847001.00 702.00 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:27

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 8

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_AK_FAIRBANKS

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January -17.62
February -15.41
March -10.29
April 0.726
May 10.596
June 15.955
July 16.857
August 14.239
September 6.723
October -3.07
November -17.64
December -19.26
   
Annual Sum or Average -1.44
Minimum of Months -19.26
Maximum of Months 16.857



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.289409E+11 94124.52 26-JAN-06:01 -24.0 -24.3 0.524634E+10 7662.52 10-JAN-14:09 -24.0 -24.3
February 0.303642E+11 95882.19 13-FEB-06:01 -16.3 -16.6 0.495077E+10 7501.10 07-FEB-14:09 -16.3 -16.6
March 0.389857E+11 98860.45 20-MAR-04:01 -4.5 -5.7 0.607289E+10 7504.18 02-MAR-10:00 -4.5 -5.7
April 0.455077E+11 102007.48 24-APR-03:02 -2.8 -5.4 0.544353E+10 7500.67 03-APR-09:30 -2.8 -5.4
May 0.509238E+11 102299.99 30-MAY-03:02 3.90 2.96 0.589697E+10 7499.04 19-MAY-09:20 3.90 2.96
June 0.541613E+11 104265.99 19-JUN-03:02 7.62 7.07 0.587947E+10 7499.07 29-JUN-13:09 24.60 15.77
July 0.562016E+11 105869.98 10-JUL-03:02 9.90 8.75 0.547192E+10 7500.44 19-JUL-09:20 17.57 14.42
August 0.628856E+11 104268.17 28-AUG-03:02 8.72 7.37 0.613644E+10 7499.02 18-AUG-13:20 8.72 7.37
September 0.517343E+11 103592.66 18-SEP-03:02 3.03 1.93 0.544911E+10 7499.18 08-SEP-13:20 3.03 1.93
October 0.467475E+11 104609.14 10-OCT-03:01 -0.6 -0.9 0.566234E+10 7500.79 26-OCT-13:50 -10.6 -11.7
November 0.434363E+11 98961.78 13-NOV-05:01 -20.2 -20.4 0.532890E+10 7740.90 07-NOV-10:09 -20.2 -20.4
December 0.401231E+11 99307.58 26-DEC-05:01 -12.2 -12.5 0.500371E+10 7629.98 22-DEC-10:30 -12.2 -12.5
                     
Annual Sum or Average 0.550012E+12         0.665424E+11        
Minimum of Months 0.289409E+11 94124.52   -24.0 -24.3 0.495077E+10 7499.02   -24.0 -24.3
Maximum of Months 0.628856E+11 105869.98   9.90 8.75 0.613644E+10 7740.90   24.60 15.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.253035E+11 24643.00 25-JAN-14:10 -18.9 -19.2 0.468749E+10 6734.62 26-JAN-10:50 -22.8 -23.0
February 0.264210E+11 78760.90 10-FEB-06:02 -9.5 -10.1 0.447437E+10 6734.72 15-FEB-10:09 -17.4 -17.7
March 0.381217E+11 82317.44 23-MAR-04:01 -2.3 -3.8 0.544692E+10 6746.87 20-MAR-09:30 -2.3 -3.8
April 0.477136E+11 86320.96 24-APR-03:02 -2.8 -5.4 0.487822E+10 6743.74 07-APR-13:39 -2.8 -5.4
May 0.515777E+11 85949.52 01-MAY-03:02 6.70 2.21 0.528321E+10 6734.74 19-MAY-13:00 13.30 8.13
June 0.584617E+11 88762.41 26-JUN-03:02 12.70 11.22 0.527070E+10 6734.79 29-JUN-13:30 25.00 15.96
July 0.627233E+11 87536.49 03-JUL-03:02 10.50 10.21 0.489581E+10 6735.86 19-JUL-09:09 17.38 14.45
August 0.668087E+11 87278.43 07-AUG-03:02 11.10 10.49 0.549773E+10 6734.73 25-AUG-09:00 15.60 11.89
September 0.428238E+11 90792.72 05-SEP-03:02 5.50 5.03 0.487847E+10 6747.02 29-SEP-13:20 0.97 -0.9
October 0.369760E+11 85621.28 10-OCT-04:01 -0.6 -1.1 0.505395E+10 6739.45 12-OCT-13:50 -1.1 -3.6
November 0.301291E+11 75746.72 02-NOV-05:01 -11.0 -11.4 0.495097E+10 6734.75 07-NOV-10:09 -22.9 -23.1
December 0.279741E+11 31179.24 26-DEC-17:00 -15.6 -15.9 0.476919E+10 6734.75 22-DEC-14:50 -15.6 -15.9
                     
Annual Sum or Average 0.515034E+12         0.600870E+11        
Minimum of Months 0.253035E+11 24643.00   -18.9 -19.2 0.447437E+10 6734.62   -22.9 -23.1
Maximum of Months 0.668087E+11 90792.72   12.70 11.22 0.549773E+10 6747.02   25.00 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.185318E+11 20871.33 19-JAN-14:50 -6.2 -6.8 0.405605E+10 6111.73 26-JAN-14:00 -18.3 -18.7
February 0.200951E+11 21997.11 03-FEB-16:20 -8.3 -8.6 0.386063E+10 6543.16 17-FEB-14:00 -11.1 -12.7
March 0.254319E+11 46076.08 31-MAR-15:07 -9.9 -12.2 0.495350E+10 6758.67 22-MAR-13:20 -9.9 -12.2
April 0.297338E+11 76599.44 21-APR-05:02 -2.0 -3.0 0.469861E+10 6786.45 13-APR-09:00 -2.0 -3.0
May 0.424349E+11 76877.62 02-MAY-05:02 4.08 1.38 0.526652E+10 6734.73 19-MAY-13:00 13.30 8.13
June 0.469646E+11 78451.56 26-JUN-05:02 12.38 11.28 0.526551E+10 6734.78 29-JUN-13:20 24.80 15.87
July 0.460357E+11 80023.84 24-JUL-03:02 13.72 12.61 0.489281E+10 6735.70 19-JUL-09:09 13.72 12.61
August 0.458430E+11 81847.12 14-AUG-03:02 12.12 10.59 0.549049E+10 6734.72 18-AUG-13:09 13.62 12.18
September 0.325289E+11 77007.96 13-SEP-05:02 6.10 5.77 0.482932E+10 6742.04 29-SEP-09:20 -3.9 -4.4
October 0.248015E+11 69659.00 05-OCT-05:02 -0.6 -1.4 0.467770E+10 6734.73 05-OCT-09:50 4.17 1.61
November 0.205148E+11 17379.53 03-NOV-16:00 -11.1 -11.5 0.414068E+10 6218.64 03-NOV-13:00 -11.1 -11.5
December 0.193622E+11 16417.23 22-DEC-17:00 -21.7 -22.0 0.391499E+10 5978.98 22-DEC-14:00 -21.7 -22.0
                     
Annual Sum or Average 0.372278E+12         0.560468E+11        
Minimum of Months 0.185318E+11 16417.23   -21.7 -22.0 0.386063E+10 5978.98   -21.7 -22.0
Maximum of Months 0.469646E+11 81847.12   13.72 12.61 0.549049E+10 6786.45   24.80 15.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.756752E+10 14227.56 20-JAN-17:00 -11.1 -11.2 0.372686E+10 5328.46 20-JAN-14:00 -11.1 -11.2
February 0.984515E+10 16460.27 09-FEB-17:00 -2.2 -2.6 0.346526E+10 5904.86 09-FEB-14:00 -2.2 -2.6
March 0.168041E+11 18459.64 22-MAR-16:00 5.60 2.61 0.432398E+10 6282.82 22-MAR-13:00 5.60 2.61
April 0.227388E+11 34218.95 21-APR-16:00 14.40 5.45 0.429542E+10 6734.44 27-APR-13:00 11.10 4.54
May 0.361400E+11 69601.81 11-MAY-05:03 4.68 1.21 0.518537E+10 6734.73 19-MAY-13:00 13.30 8.13
June 0.456958E+11 76136.69 15-JUN-05:02 10.00 8.53 0.525098E+10 6734.75 29-JUN-13:00 25.60 16.24
July 0.443484E+11 79156.88 24-JUL-03:02 13.72 12.61 0.488341E+10 6735.56 19-JUL-09:09 13.72 12.61
August 0.407808E+11 76626.94 14-AUG-04:03 11.60 10.40 0.544482E+10 6734.67 18-AUG-13:09 13.62 12.18
September 0.232856E+11 31795.82 01-SEP-16:00 15.60 10.82 0.446531E+10 6734.66 08-SEP-13:09 11.28 7.64
October 0.158607E+11 18923.55 04-OCT-16:00 10.00 4.57 0.403676E+10 6490.17 04-OCT-13:00 10.00 4.57
November 0.863431E+10 14529.20 02-NOV-16:00 -8.9 -9.4 0.371144E+10 5371.88 02-NOV-13:00 -8.9 -9.4
December 0.739690E+10 13356.20 21-DEC-17:00 -16.7 -17.3 0.358155E+10 5126.38 21-DEC-14:00 -16.7 -17.3
                     
Annual Sum or Average 0.279098E+12         0.523712E+11        
Minimum of Months 0.739690E+10 13356.20   -16.7 -17.3 0.346526E+10 5126.38   -16.7 -17.3
Maximum of Months 0.456958E+11 79156.88   15.60 12.61 0.544482E+10 6735.56   25.60 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.204348E+09 1609.20 20-JAN-14:20 -9.6 -9.9 0.466216E+09 636.96 20-JAN-14:30 -10.0 -10.3
February 0.802635E+09 2442.57 10-FEB-06:02 -9.5 -10.1 0.434479E+09 726.21 09-FEB-14:00 -9.5 -10.1
March 0.203104E+10 2827.52 22-MAR-14:00 5.60 1.90 0.562365E+09 845.60 22-MAR-13:30 5.60 1.90
April 0.393328E+10 5445.95 28-APR-14:00 11.70 4.88 0.579862E+09 845.62 24-APR-09:20 11.70 4.88
May 0.646332E+10 13617.36 31-MAY-04:33 11.87 7.50 0.660810E+09 845.63 19-MAY-13:39 11.87 7.50
June 0.984724E+10 14449.63 12-JUN-03:53 7.20 5.88 0.661805E+09 845.66 29-JUN-13:30 25.00 15.96
July 0.994398E+10 15689.66 11-JUL-04:54 15.00 11.90 0.615234E+09 845.76 19-JUL-09:09 17.38 14.45
August 0.840325E+10 12640.01 02-AUG-05:02 11.10 10.22 0.688798E+09 845.63 18-AUG-13:09 13.62 12.18
September 0.373527E+10 5279.53 01-SEP-13:40 14.63 10.60 0.588239E+09 845.63 08-SEP-13:09 11.28 7.64
October 0.231942E+10 3058.16 04-OCT-14:40 11.10 4.80 0.542580E+09 845.60 02-OCT-13:09 11.10 4.80
November 0.741767E+09 2100.50 02-NOV-05:02 -11.0 -11.4 0.466972E+09 684.21 02-NOV-13:00 -8.9 -9.5
December 0.241137E+09 1673.33 26-DEC-12:00 -10.6 -11.5 0.451722E+09 652.55 26-DEC-10:00 -10.6 -11.5
                     
Annual Sum or Average 0.486667E+11         0.671908E+10        
Minimum of Months 0.204348E+09 1609.20   -11.0 -11.5 0.434479E+09 636.96   -10.6 -11.5
Maximum of Months 0.994398E+10 15689.66   15.00 11.90 0.688798E+09 845.76   25.00 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.114617E+09 1669.27 23-JAN-06:03 -11.2 -11.4 0.300102E+09 403.40 03-JAN-10:20 -11.2 -11.4
February 0.733327E+09 2529.17 10-FEB-06:02 -9.5 -10.1 0.280314E+09 506.27 15-FEB-10:00 -15.6 -15.8
March 0.256099E+10 6815.39 27-MAR-09:35 -10.2 -12.2 0.385408E+09 546.37 20-MAR-09:30 -10.2 -12.2
April 0.471171E+10 10252.17 22-APR-09:20 8.87 3.75 0.377385E+09 544.95 13-APR-09:39 8.87 3.75
May 0.851614E+10 23171.19 14-MAY-09:31 15.73 8.25 0.426365E+09 545.85 09-MAY-09:00 15.73 8.25
June 0.935028E+10 21191.53 04-JUN-09:12 16.33 10.97 0.426110E+09 546.19 07-JUN-09:39 15.53 8.90
July 0.962622E+10 21840.99 23-JUL-10:01 21.38 14.90 0.396046E+09 546.62 07-JUL-09:30 21.38 14.90
August 0.819079E+10 14206.50 10-AUG-08:50 14.22 9.95 0.442936E+09 545.98 11-AUG-09:20 17.23 10.78
September 0.400699E+10 17147.79 10-SEP-10:13 13.33 7.36 0.378313E+09 544.97 08-SEP-13:09 13.33 7.36
October 0.220772E+10 6425.62 03-OCT-09:45 3.43 2.35 0.345322E+09 544.95 13-OCT-09:50 -7.1 -8.0
November 0.315707E+09 2175.86 02-NOV-05:02 -11.0 -11.4 0.298397E+09 423.63 08-NOV-10:00 -17.8 -18.2
December 57481339.56 1641.37 18-DEC-06:04 -16.7 -17.1 0.290117E+09 403.38 12-DEC-14:30 -16.7 -17.1
                     
Annual Sum or Average 0.503920E+11         0.434682E+10        
Minimum of Months 57481339.56 1641.37   -16.7 -17.1 0.280314E+09 403.38   -17.8 -18.2
Maximum of Months 0.962622E+10 23171.19   21.38 14.90 0.442936E+09 546.62   21.38 14.90



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.381146E+09 3372.29 25-JAN-13:20 -20.0 -20.3 0.469142E+09 758.94 25-JAN-14:09 -18.9 -19.2
February 0.192318E+10 10170.93 15-FEB-13:30 -8.9 -9.7 0.459710E+09 845.63 14-FEB-14:00 -8.9 -9.7
March 0.579356E+10 16117.30 31-MAR-13:30 -11.4 -13.3 0.608443E+09 845.64 29-MAR-13:20 -11.4 -13.3
April 0.104351E+11 27994.73 23-APR-11:23 10.00 3.80 0.581927E+09 847.56 07-APR-13:39 10.00 3.80
May 0.118410E+11 34056.04 14-MAY-12:12 18.17 9.44 0.655164E+09 847.23 12-MAY-13:50 18.17 9.44
June 0.136761E+11 33385.58 04-JUN-14:32 19.23 11.76 0.660496E+09 845.73 29-JUN-13:30 25.00 15.96
July 0.145066E+11 36137.48 23-JUL-12:41 24.82 15.36 0.614184E+09 846.52 12-JUL-13:00 24.82 15.36
August 0.146059E+11 33084.31 27-AUG-13:12 18.33 13.81 0.686684E+09 847.00 31-AUG-13:00 13.30 4.88
September 0.766312E+10 20856.95 10-SEP-11:32 15.20 8.17 0.578858E+09 847.18 29-SEP-13:20 0.97 -0.9
October 0.412117E+10 16918.03 03-OCT-13:30 10.85 6.24 0.542978E+09 846.62 12-OCT-13:50 -1.1 -3.6
November 0.101431E+10 7089.53 08-NOV-13:30 -13.6 -14.4 0.474938E+09 845.63 08-NOV-14:00 -13.9 -14.6
December 0.116371E+09 2550.82 27-DEC-12:40 -22.6 -22.8 0.449647E+09 625.93 12-DEC-14:00 -22.6 -22.8
                     
Annual Sum or Average 0.860776E+11         0.678217E+10        
Minimum of Months 0.116371E+09 2550.82   -22.6 -22.8 0.449647E+09 625.93   -22.6 -22.8
Maximum of Months 0.146059E+11 36137.48   24.82 15.36 0.686684E+09 847.56   25.00 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.613777E+09 2031.01 23-JAN-14:20 -9.5 -10.0 0.301554E+09 420.76 23-JAN-14:39 -10.0 -10.5
February 0.185387E+10 3323.40 09-FEB-06:01 0.00 -0.5 0.291794E+09 523.93 09-FEB-14:00 0.00 -1.0
March 0.398987E+10 7658.61 27-MAR-16:00 -4.4 -7.8 0.398258E+09 544.95 22-MAR-09:00 -4.4 -7.8
April 0.845592E+10 23643.04 22-APR-17:04 14.13 6.18 0.391757E+09 545.85 07-APR-13:39 14.13 6.18
May 0.790559E+10 24872.04 29-MAY-16:02 13.30 8.10 0.426185E+09 544.96 19-MAY-13:39 13.30 8.10
June 0.112265E+11 25128.98 11-JUN-16:42 18.90 11.02 0.427474E+09 544.99 29-JUN-13:30 25.00 15.96
July 0.120108E+11 24505.82 23-JUL-15:21 25.60 15.14 0.397610E+09 545.07 19-JUL-09:09 25.60 15.14
August 0.122177E+11 25483.43 27-AUG-17:12 20.93 12.63 0.445997E+09 544.96 28-AUG-09:00 12.20 8.79
September 0.486474E+10 12996.98 02-SEP-17:08 16.70 10.21 0.380758E+09 544.96 08-SEP-13:09 11.28 7.64
October 0.342729E+10 6319.05 03-OCT-14:50 12.62 6.87 0.364445E+09 544.94 04-OCT-13:39 11.30 4.92
November 0.237101E+10 3120.16 02-NOV-05:01 -11.0 -11.4 0.319617E+09 507.11 08-NOV-14:00 -13.9 -14.6
December 0.215852E+10 2493.23 26-DEC-05:01 -12.2 -12.5 0.303374E+09 470.28 26-DEC-10:00 -10.0 -10.8
                     
Annual Sum or Average 0.710956E+11         0.444882E+10        
Minimum of Months 0.613777E+09 2031.01   -12.2 -12.5 0.291794E+09 420.76   -13.9 -14.6
Maximum of Months 0.122177E+11 25483.43   25.60 15.14 0.445997E+09 545.85   25.60 15.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 12069770.29 1440.56 07-JAN-17:02 -9.0 -9.0 0.461485E+09 626.01 03-JAN-10:30 -9.0 -9.0
February 39177079.24 1462.23 11-FEB-17:02 -1.2 -2.7 0.420081E+09 625.95 28-FEB-10:30 -25.3 -25.6
March 0.367001E+09 2059.14 21-MAR-14:30 1.40 0.52 0.509262E+09 725.25 22-MAR-13:00 5.60 1.90
April 0.194510E+10 3485.61 28-APR-14:00 11.70 4.88 0.506075E+09 845.59 27-APR-13:00 11.70 4.88
May 0.491035E+10 11666.01 31-MAY-05:03 12.07 7.63 0.652188E+09 845.63 19-MAY-13:39 12.07 7.63
June 0.819842E+10 13272.27 19-JUN-05:03 8.27 7.22 0.660694E+09 845.65 29-JUN-13:20 24.80 15.87
July 0.758766E+10 13326.37 11-JUL-05:03 15.18 11.97 0.614340E+09 845.74 19-JUL-09:09 17.38 14.45
August 0.547816E+10 9001.86 10-AUG-05:02 10.10 7.54 0.678918E+09 845.62 18-AUG-13:09 13.62 12.18
September 0.251908E+10 3524.14 01-SEP-14:00 15.00 10.77 0.537625E+09 845.60 01-SEP-13:09 15.00 10.77
October 0.750471E+09 2069.54 04-OCT-16:00 10.00 4.57 0.477943E+09 749.00 06-OCT-13:00 10.60 4.48
November 11604580.19 1439.48 18-NOV-17:02 -13.0 -13.3 0.458635E+09 625.97 28-NOV-14:00 -25.6 -25.8
December 14659406.78 1446.21 23-DEC-17:02 -2.6 -3.4 0.445965E+09 626.00 07-DEC-10:50 -2.6 -3.4
                     
Annual Sum or Average 0.318337E+11         0.642321E+10        
Minimum of Months 11604580.19 1439.48   -13.0 -13.3 0.420081E+09 625.95   -25.6 -25.8
Maximum of Months 0.819842E+10 13326.37   15.18 11.97 0.678918E+09 845.74   24.80 15.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 19825611.86 1793.90 20-JAN-06:04 -7.6 -7.8 0.218748E+09 385.83 11-JAN-09:20 -7.6 -7.8
February 0.128977E+09 1825.85 15-FEB-11:30 -13.6 -14.0 0.199039E+09 406.53 15-FEB-11:39 -13.0 -13.4
March 0.129137E+10 5050.79 22-MAR-09:50 1.13 -0.3 0.253453E+09 521.20 31-MAR-10:09 -15.9 -17.2
April 0.338912E+10 9837.28 22-APR-09:30 9.15 3.96 0.259511E+09 538.76 13-APR-10:20 9.15 3.96
May 0.816287E+10 24366.37 21-MAY-09:01 12.30 5.76 0.311278E+09 522.39 12-MAY-10:30 12.30 5.76
June 0.909558E+10 22589.95 04-JUN-09:22 16.70 11.16 0.312349E+09 524.98 13-JUN-07:19 16.13 10.80
July 0.902226E+10 23087.55 23-JUL-10:12 21.67 15.01 0.291533E+09 525.48 07-JUL-07:19 21.67 15.01
August 0.708838E+10 14955.48 10-AUG-09:00 14.40 10.07 0.323359E+09 526.37 30-AUG-07:10 0.78 -1.1
September 0.324849E+10 16344.79 10-SEP-10:02 13.07 7.24 0.258899E+09 522.97 15-SEP-08:50 3.12 2.28
October 0.990311E+09 4667.05 03-OCT-10:25 5.00 3.43 0.229161E+09 524.04 03-OCT-10:30 5.00 3.43
November 19083081.38 1807.42 14-NOV-06:04 -15.6 -15.9 0.216717E+09 385.85 27-NOV-08:09 -26.7 -26.9
December 19933339.01 1766.67 20-DEC-06:04 -15.8 -16.1 0.210911E+09 385.81 27-DEC-08:00 -21.1 -21.5
                     
Annual Sum or Average 0.424762E+11         0.308496E+10        
Minimum of Months 19083081.38 1766.67   -15.8 -16.1 0.199039E+09 385.81   -26.7 -26.9
Maximum of Months 0.909558E+10 24366.37   21.67 15.01 0.323359E+09 538.76   21.67 15.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.187269E+09 3147.86 25-JAN-13:40 -19.5 -19.7 0.464848E+09 705.09 25-JAN-14:09 -18.9 -19.2
February 0.122232E+10 14195.55 15-FEB-13:40 -8.7 -9.6 0.444918E+09 847.75 13-FEB-14:09 -8.7 -9.6
March 0.449352E+10 28402.29 31-MAR-15:07 -9.9 -12.2 0.579202E+09 897.18 27-MAR-13:39 -9.9 -12.2
April 0.910794E+10 26699.36 09-APR-14:02 2.48 -2.4 0.560881E+09 873.39 03-APR-13:30 2.48 -2.4
May 0.116765E+11 35881.63 21-MAY-13:02 14.60 6.77 0.646479E+09 847.49 12-MAY-13:00 14.60 6.77
June 0.128393E+11 35382.46 04-JUN-14:42 19.32 11.73 0.656905E+09 845.96 16-JUN-13:00 19.40 10.50
July 0.128785E+11 35654.21 23-JUL-13:32 25.00 15.26 0.611002E+09 846.99 20-JUL-13:50 25.00 15.26
August 0.126515E+11 35089.74 27-AUG-13:12 18.33 13.81 0.678963E+09 846.13 09-AUG-13:39 18.33 13.81
September 0.723003E+10 33866.59 10-SEP-11:22 15.00 8.08 0.559826E+09 845.69 08-SEP-13:09 15.00 8.08
October 0.285557E+10 16357.60 03-OCT-13:30 10.85 6.24 0.512055E+09 845.63 04-OCT-13:39 11.30 4.92
November 0.382514E+09 4755.66 08-NOV-13:50 -13.4 -14.2 0.464737E+09 845.63 08-NOV-14:50 -13.8 -14.5
December 31097863.26 2702.74 20-DEC-06:04 -15.8 -16.1 0.447181E+09 626.03 05-DEC-10:30 -15.8 -16.1
                     
Annual Sum or Average 0.755560E+11         0.662700E+10        
Minimum of Months 31097863.26 2702.74   -19.5 -19.7 0.444918E+09 626.03   -18.9 -19.2
Maximum of Months 0.128785E+11 35881.63   25.00 15.26 0.678963E+09 897.18   25.00 15.26



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 21422958.03 1833.09 23-JAN-06:04 -11.2 -11.4 0.299024E+09 403.43 12-JAN-10:39 -11.2 -11.4
February 0.142099E+09 1831.52 09-FEB-06:03 0.00 -0.5 0.271961E+09 413.65 09-FEB-14:00 0.00 -1.0
March 0.904823E+09 3399.01 31-MAR-15:07 -9.9 -12.2 0.333093E+09 509.78 31-MAR-15:00 -9.4 -11.8
April 0.381579E+10 14442.93 22-APR-17:04 14.13 6.18 0.337689E+09 544.93 27-APR-13:00 11.10 4.54
May 0.579372E+10 23343.45 21-MAY-18:22 16.10 7.39 0.411989E+09 544.95 19-MAY-13:39 16.10 7.39
June 0.795141E+10 22589.29 04-JUN-19:22 18.60 11.50 0.424429E+09 544.97 29-JUN-13:20 24.80 15.87
July 0.725970E+10 17728.66 09-JUL-19:33 19.60 13.08 0.394398E+09 545.03 19-JUL-09:09 17.38 14.45
August 0.619010E+10 22394.23 27-AUG-17:52 20.60 12.18 0.434720E+09 544.95 18-AUG-13:09 20.60 12.18
September 0.306536E+10 8709.23 02-SEP-17:10 16.70 10.21 0.339589E+09 544.93 01-SEP-13:00 16.70 10.21
October 0.934061E+09 2608.81 03-OCT-15:20 12.43 6.74 0.308406E+09 509.92 03-OCT-15:30 12.25 6.65
November 40055430.15 1855.69 14-NOV-06:04 -15.6 -15.9 0.296399E+09 403.40 28-NOV-10:50 -28.9 -29.1
December 27109961.01 1811.61 20-DEC-06:04 -15.8 -16.1 0.288381E+09 403.41 15-DEC-10:39 -15.8 -16.1
                     
Annual Sum or Average 0.361457E+11         0.414008E+10        
Minimum of Months 21422958.03 1811.61   -15.8 -16.1 0.271961E+09 403.40   -28.9 -29.1
Maximum of Months 0.795141E+10 23343.45   20.60 13.08 0.434720E+09 545.03   24.80 15.87



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 10656757.64 1816.25 07-JAN-17:02 -9.0 -9.0 0.459311E+09 626.07 12-JAN-14:39 -36.1 -36.2
February 12499423.97 1999.27 09-FEB-06:06 0.00 -0.5 0.417969E+09 626.05 24-FEB-10:30 -25.0 -25.5
March 92362893.76 2164.85 22-MAR-16:00 5.60 2.61 0.503462E+09 647.90 22-MAR-13:00 5.60 2.61
April 0.146129E+10 2939.05 20-APR-14:10 14.32 6.25 0.467917E+09 793.61 28-APR-13:00 11.70 4.88
May 0.446592E+10 9798.32 31-MAY-05:03 12.07 7.63 0.615378E+09 845.63 19-MAY-13:39 12.07 7.63
June 0.790817E+10 15724.23 29-JUN-05:02 12.38 11.04 0.657439E+09 845.64 29-JUN-13:00 25.60 16.24
July 0.738508E+10 16743.21 11-JUL-05:03 15.18 11.97 0.610141E+09 845.71 19-JUL-09:09 17.38 14.45
August 0.514459E+10 6835.93 02-AUG-14:00 22.80 15.29 0.654082E+09 845.61 25-AUG-13:00 22.80 15.44
September 0.180886E+10 2941.90 01-SEP-16:00 15.60 10.82 0.477172E+09 796.04 01-SEP-13:00 15.60 10.82
October 0.226464E+09 2210.11 04-OCT-16:00 10.00 4.57 0.464708E+09 653.73 04-OCT-13:00 10.00 4.57
November 9826533.96 1809.89 18-NOV-17:02 -13.0 -13.3 0.456872E+09 626.03 30-NOV-14:39 -25.7 -26.0
December 14047432.59 1824.33 23-DEC-17:02 -2.6 -3.4 0.443711E+09 626.10 27-DEC-14:30 -23.9 -24.1
                     
Annual Sum or Average 0.285398E+11         0.622816E+10        
Minimum of Months 9826533.96 1809.89   -13.0 -13.3 0.417969E+09 626.03   -36.1 -36.2
Maximum of Months 0.790817E+10 16743.21   22.80 15.29 0.657439E+09 845.71   25.60 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 12596879.12 1525.41 07-JAN-17:02 -9.0 -9.0 0.298377E+09 403.46 12-JAN-14:00 -36.1 -36.2
February 26425569.36 1754.47 09-FEB-06:04 0.00 -0.5 0.271057E+09 403.40 24-FEB-10:30 -25.0 -25.5
March 0.654610E+09 2712.38 22-MAR-10:40 2.43 0.50 0.334060E+09 533.55 22-MAR-09:00 2.43 0.50
April 0.252612E+10 8130.48 22-APR-09:30 9.15 3.96 0.341367E+09 544.95 13-APR-09:00 9.15 3.96
May 0.728589E+10 23251.73 21-MAY-09:01 12.30 5.76 0.420384E+09 545.55 31-MAY-09:00 17.20 9.87
June 0.898341E+10 17685.84 09-JUN-05:02 10.28 7.07 0.424417E+09 545.87 08-JUN-09:39 10.28 7.07
July 0.892743E+10 23557.55 23-JUL-11:51 23.90 15.81 0.394200E+09 546.14 07-JUL-09:50 23.90 15.81
August 0.659525E+10 14570.33 10-AUG-09:10 14.97 10.30 0.437849E+09 545.52 10-AUG-09:00 17.80 11.30
September 0.223780E+10 6389.96 10-SEP-09:28 11.95 6.71 0.329942E+09 544.96 08-SEP-13:09 11.95 6.71
October 0.431793E+09 2502.01 03-OCT-10:25 5.00 3.43 0.303762E+09 522.48 03-OCT-09:00 5.00 3.43
November 14619849.15 1523.08 18-NOV-17:02 -13.0 -13.3 0.295646E+09 403.46 27-NOV-10:30 -27.2 -27.4
December 17256436.39 1533.11 23-DEC-17:02 -2.6 -3.4 0.287706E+09 403.47 05-DEC-10:09 -2.6 -3.4
                     
Annual Sum or Average 0.377132E+11         0.413877E+10        
Minimum of Months 12596879.12 1523.08   -13.0 -13.3 0.271057E+09 403.40   -36.1 -36.2
Maximum of Months 0.898341E+10 23557.55   23.90 15.81 0.437849E+09 546.14   23.90 15.81



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 51972437.08 2763.53 18-JAN-06:04 -20.0 -20.2 0.463142E+09 626.07 03-JAN-10:09 -20.0 -20.2
February 0.626698E+09 5664.53 15-FEB-14:00 -8.3 -9.2 0.431856E+09 845.63 15-FEB-14:00 -7.2 -8.6
March 0.298166E+10 13209.28 31-MAR-14:20 -10.7 -12.8 0.559390E+09 845.64 27-MAR-13:39 -10.7 -12.8
April 0.734621E+10 22394.84 20-APR-14:00 14.40 6.23 0.541765E+09 845.98 21-APR-13:20 13.17 5.35
May 0.104440E+11 36053.65 14-MAY-13:42 19.32 9.65 0.629329E+09 846.92 12-MAY-13:50 19.32 9.65
June 0.125736E+11 34912.07 18-JUN-12:42 16.60 11.66 0.651141E+09 845.70 29-JUN-13:00 25.60 16.24
July 0.126695E+11 40417.04 23-JUL-12:31 24.63 15.46 0.605076E+09 847.16 20-JUL-13:50 24.63 15.46
August 0.118653E+11 36045.24 27-AUG-13:52 19.40 14.21 0.665613E+09 846.13 25-AUG-13:00 19.40 14.21
September 0.538205E+10 17264.34 08-SEP-14:30 13.05 8.68 0.523929E+09 845.68 08-SEP-13:09 13.05 8.68
October 0.163484E+10 13622.25 03-OCT-13:40 11.13 6.36 0.489954E+09 845.63 13-OCT-13:30 0.55 -2.7
November 0.156756E+09 3572.22 08-NOV-13:50 -13.4 -14.2 0.460407E+09 758.02 08-NOV-14:09 -13.4 -14.2
December 30163301.61 2438.00 23-DEC-17:02 -2.6 -3.4 0.446522E+09 626.10 12-DEC-14:00 -2.6 -3.4
                     
Annual Sum or Average 0.657628E+11         0.646813E+10        
Minimum of Months 30163301.61 2438.00   -20.0 -20.2 0.431856E+09 626.07   -20.0 -20.2
Maximum of Months 0.126695E+11 40417.04   24.63 15.46 0.665613E+09 847.16   25.60 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 16219896.78 1631.60 07-JAN-17:02 -9.0 -9.0 0.298482E+09 403.45 12-JAN-10:09 -38.1 -38.2
February 43293556.66 1911.38 08-FEB-06:04 -10.5 -10.7 0.271202E+09 403.43 24-FEB-10:39 -24.8 -25.3
March 0.460104E+09 2495.24 22-MAR-16:00 5.60 2.61 0.328149E+09 479.94 22-MAR-15:00 5.60 2.61
April 0.305665E+10 12546.70 22-APR-17:06 14.13 6.18 0.320187E+09 544.09 28-APR-13:00 11.70 4.88
May 0.516294E+10 23685.57 21-MAY-17:42 16.10 7.34 0.394824E+09 544.95 19-MAY-13:39 16.10 7.34
June 0.775553E+10 22138.75 10-JUN-17:04 21.20 10.81 0.420942E+09 544.97 29-JUN-13:00 25.60 16.24
July 0.707243E+10 18397.07 23-JUL-16:32 25.93 15.00 0.390666E+09 544.97 07-JUL-13:09 25.93 15.00
August 0.573419E+10 21924.42 27-AUG-17:52 20.60 12.18 0.422656E+09 544.95 25-AUG-13:00 20.60 12.18
September 0.216369E+10 6669.08 08-SEP-16:00 14.40 9.03 0.315429E+09 528.23 01-SEP-13:00 14.40 9.03
October 0.390083E+09 2441.60 03-OCT-15:20 12.43 6.74 0.301566E+09 472.78 03-OCT-15:30 12.25 6.65
November 21334792.06 1887.85 02-NOV-05:04 -11.0 -11.4 0.295858E+09 403.44 27-NOV-10:50 -27.2 -27.4
December 23236171.64 1851.53 07-DEC-06:04 -22.8 -23.1 0.287889E+09 403.45 07-DEC-10:00 -23.9 -24.3
                     
Annual Sum or Average 0.318997E+11         0.404785E+10        
Minimum of Months 16219896.78 1631.60   -22.8 -23.1 0.271202E+09 403.43   -38.1 -38.2
Maximum of Months 0.775553E+10 23685.57   25.93 15.00 0.422656E+09 544.97   25.93 16.24



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 17087257.76 5236.55 12-JAN-04:01 -37.3 -37.4 0.00 0.00 01-JAN-00:10 -37.3 -37.4
February 0.109674E+09 5552.44 25-FEB-05:01 -24.4 -24.9 0.00 0.00 01-FEB-00:10 -24.4 -24.9
March 0.421705E+09 4247.93 01-MAR-05:01 -28.3 -28.7 0.00 0.00 01-MAR-00:10 -28.3 -28.7
April 0.267046E+10 4770.04 21-APR-16:00 14.40 5.45 0.00 0.00 01-APR-00:10 14.40 5.45
May 0.525917E+10 5981.29 31-MAY-15:20 21.47 10.76 0.00 0.00 01-MAY-00:10 21.47 10.76
June 0.781230E+10 9374.29 05-JUN-05:15 10.77 8.82 0.00 0.00 01-JUN-00:10 10.77 8.82
July 0.816491E+10 12320.47 24-JUL-05:15 13.17 12.61 0.00 0.00 01-JUL-00:10 13.17 12.61
August 0.749723E+10 8552.30 07-AUG-05:15 10.60 10.26 0.00 0.00 01-AUG-00:10 10.60 10.26
September 0.305199E+10 7141.07 05-SEP-05:15 5.00 4.17 0.00 0.00 01-SEP-00:10 5.00 4.17
October 0.958245E+09 4180.73 05-OCT-05:10 -0.6 -1.4 0.00 0.00 01-OCT-00:10 -0.6 -1.4
November 18710136.01 4417.05 27-NOV-05:01 -25.8 -26.0 0.00 0.00 01-NOV-00:10 -25.8 -26.0
December 10043477.26 4566.18 15-DEC-05:01 -33.2 -33.3 0.00 0.00 01-DEC-00:10 -33.2 -33.3
                     
Annual Sum or Average 0.359915E+11         0.00        
Minimum of Months 10043477.26 4180.73   -37.3 -37.4 0.00 0.00   -37.3 -37.4
Maximum of Months 0.816491E+10 12320.47   21.47 12.61 0.00 0.00   21.47 12.61



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.197220E+09 8174.01 28-JAN-04:01 -18.5 -19.2 0.00 0.00 01-JAN-00:10 -18.5 -19.2
February 0.304534E+09 7540.05 26-FEB-03:51 -25.6 -26.0 0.00 0.00 01-FEB-00:10 -25.6 -26.0
March 0.168369E+09 7653.76 25-MAR-04:01 -12.2 -12.9 0.00 0.00 01-MAR-00:10 -12.2 -12.9
April 0.844230E+09 8223.11 03-APR-03:01 -21.1 -21.6 0.00 0.00 01-APR-00:10 -21.1 -21.6
May 0.345732E+10 4419.28 12-MAY-05:15 5.73 1.89 0.00 0.00 01-MAY-00:10 5.73 1.89
June 0.589394E+10 6292.36 30-JUN-14:30 27.75 17.00 0.00 0.00 01-JUN-00:10 27.75 17.00
July 0.604417E+10 6648.40 24-JUL-15:30 21.40 15.90 0.00 0.00 01-JUL-00:10 21.40 15.90
August 0.493869E+10 5853.50 14-AUG-05:15 11.10 10.22 0.00 0.00 01-AUG-00:10 11.10 10.22
September 0.176306E+10 5748.03 30-SEP-05:01 -4.5 -5.0 0.00 0.00 01-SEP-00:10 -4.5 -5.0
October 0.403387E+09 8350.53 23-OCT-03:11 -11.5 -12.4 0.00 0.00 01-OCT-00:10 -11.5 -12.4
November 0.420571E+09 7893.25 10-NOV-04:01 -18.9 -19.3 0.00 0.00 01-NOV-00:10 -18.9 -19.3
December 0.351534E+09 8339.58 09-DEC-04:11 -24.4 -24.7 0.00 0.00 01-DEC-00:10 -24.4 -24.7
                     
Annual Sum or Average 0.247870E+11         0.00        
Minimum of Months 0.168369E+09 4419.28   -25.6 -26.0 0.00 0.00   -25.6 -26.0
Maximum of Months 0.604417E+10 8350.53   27.75 17.00 0.00 0.00   27.75 17.00



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -14.9 -15.4 0.00 0.00 01-JAN-00:10 -14.9 -15.4
February 0.00 0.00 01-FEB-00:03 -20.2 -20.7 0.00 0.00 01-FEB-00:10 -20.2 -20.7
March 1516613.11 563.57 22-MAR-16:30 5.60 2.18 0.00 0.00 01-MAR-00:10 5.60 2.18
April 0.831881E+09 6163.08 20-APR-15:20 13.70 6.18 0.00 0.00 01-APR-00:10 13.70 6.18
May 0.404612E+10 12398.42 31-MAY-14:40 20.73 10.55 0.00 0.00 01-MAY-00:10 20.73 10.55
June 0.805047E+10 14052.04 29-JUN-14:50 26.02 16.10 0.00 0.00 01-JUN-00:10 26.02 16.10
July 0.795660E+10 14558.24 21-JUL-14:40 27.23 14.65 0.00 0.00 01-JUL-00:10 27.23 14.65
August 0.497478E+10 11806.64 11-AUG-15:30 25.00 14.43 0.00 0.00 01-AUG-00:10 25.00 14.43
September 0.495702E+09 3703.53 07-SEP-15:40 16.83 8.91 0.00 0.00 01-SEP-00:10 16.83 8.91
October 1914384.77 560.82 04-OCT-16:30 9.70 4.43 0.00 0.00 01-OCT-00:10 9.70 4.43
November 0.00 0.00 01-NOV-00:10 -10.0 -10.9 0.00 0.00 01-NOV-00:10 -10.0 -10.9
December 0.00 0.00 01-DEC-00:10 -25.8 -26.0 0.00 0.00 01-DEC-00:10 -25.8 -26.0
                     
Annual Sum or Average 0.263590E+11         0.00        
Minimum of Months 0.00 0.00   -25.8 -26.0 0.00 0.00   -25.8 -26.0
Maximum of Months 0.805047E+10 14558.24   27.23 16.10 0.00 0.00   27.23 16.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.961767E+09 1056.71 23-JAN-15:20 -10.4 -10.8 94558327.13 126.82 20-JAN-14:50 -10.4 -10.8
February 0.618688E+10 3517.32 15-FEB-16:20 -7.4 -8.8 86396479.95 126.82 02-FEB-14:00 -7.4 -8.8
March 0.131075E+11 6703.89 31-MAR-23:55 -11.8 -13.4 0.103236E+09 126.82 10-MAR-14:09 -11.8 -13.4
April 0.187365E+11 8506.34 20-APR-18:50 11.28 4.73 91605002.66 126.82 18-APR-13:09 11.28 4.73
May 0.437802E+10 3452.93 31-MAY-24:00 12.40 8.53 99233127.75 126.82 17-MAY-09:00 12.40 8.53
June 0.939021E+10 5345.54 30-JUN-23:15 15.97 11.62 98962234.35 126.85 27-JUN-09:00 15.97 11.62
July 0.147333E+11 7258.76 31-JUL-23:40 17.10 11.88 91886070.26 126.84 25-JUL-09:09 17.10 11.88
August 0.196696E+11 8357.92 27-AUG-18:45 19.60 11.80 0.103239E+09 126.83 04-AUG-09:09 19.60 11.80
September 0.381834E+10 2893.27 30-SEP-24:00 1.30 -0.1 91606655.09 126.83 05-SEP-13:00 1.30 -0.1
October 0.816305E+10 4423.98 31-OCT-24:00 -10.1 -11.0 95230022.52 126.82 04-OCT-13:09 -10.1 -11.0
November 0.118699E+11 5465.05 08-NOV-15:55 -16.1 -16.4 94300268.10 126.82 01-NOV-13:20 -16.1 -16.4
December 0.170206E+11 6950.32 26-DEC-17:00 -15.6 -15.9 91880854.33 126.82 04-DEC-14:09 -15.6 -15.9
                     
Annual Sum or Average 0.128036E+12         0.114213E+10        
Minimum of Months 0.961767E+09 1056.71   -16.1 -16.4 86396479.95 126.82   -16.1 -16.4
Maximum of Months 0.196696E+11 8506.34   19.60 11.88 0.103239E+09 126.85   19.60 11.88



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.363680E+09 644.35 12-JAN-08:65 -38.2 -38.3 86757318.03 126.82 20-JAN-14:00 -11.1 -11.3
February 0.348737E+10 2883.86 16-FEB-16:10 -4.6 -6.9 86396483.41 126.82 07-FEB-14:00 -4.6 -6.9
March 0.101199E+11 5720.19 31-MAR-23:20 -12.1 -13.7 0.103236E+09 126.82 07-MAR-14:30 -12.1 -13.7
April 0.164898E+11 8092.32 20-APR-18:50 11.28 4.73 91605035.95 126.82 18-APR-13:09 11.28 4.73
May 0.366862E+10 3222.95 31-MAY-24:00 12.40 8.53 99233130.47 126.82 17-MAY-09:00 12.40 8.53
June 0.875517E+10 5133.57 30-JUN-24:00 15.10 14.10 98961931.15 126.84 27-JUN-13:00 15.10 14.10
July 0.139117E+11 7024.50 31-JUL-24:00 16.60 11.46 91886181.83 126.84 25-JUL-13:30 16.60 11.46
August 0.185182E+11 7824.57 27-AUG-18:45 19.60 11.80 0.103239E+09 126.83 18-AUG-13:00 19.60 11.80
September 0.260188E+10 2116.25 30-SEP-23:50 1.17 -0.3 91606490.21 126.83 05-SEP-13:00 1.17 -0.3
October 0.547322E+10 3399.89 03-OCT-16:00 11.70 6.37 95230029.91 126.82 04-OCT-13:09 11.60 5.09
November 0.832380E+10 4648.97 08-NOV-15:50 -15.7 -16.1 94300273.47 126.82 14-NOV-14:09 -13.9 -14.5
December 0.130877E+11 5858.41 21-DEC-17:00 -16.7 -17.3 91880860.68 126.82 04-DEC-14:09 -16.7 -17.3
                     
Annual Sum or Average 0.104801E+12         0.113433E+10        
Minimum of Months 0.363680E+09 644.35   -38.2 -38.3 86396483.41 126.82   -16.7 -17.3
Maximum of Months 0.185182E+11 8092.32   19.60 14.10 0.103239E+09 126.84   19.60 14.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.323735E+09 628.10 12-JAN-08:15 -38.1 -38.2 78703535.46 121.53 19-JAN-14:00 -6.1 -6.7
February 0.208860E+10 2463.04 09-FEB-16:00 0.60 -0.5 86295071.08 126.82 07-FEB-14:09 0.60 -0.5
March 0.808596E+10 4985.25 31-MAR-17:30 -9.4 -11.7 0.103236E+09 126.82 02-MAR-14:00 -9.4 -11.7
April 0.149424E+11 8069.81 20-APR-18:50 11.28 4.73 91605047.19 126.82 18-APR-13:09 11.28 4.73
May 0.296624E+10 3177.53 31-MAY-24:00 12.40 8.53 99232861.20 126.82 17-MAY-09:00 12.40 8.53
June 0.855978E+10 5094.26 30-JUN-24:00 15.10 14.10 98961964.61 126.85 27-JUN-13:00 15.10 14.10
July 0.137453E+11 6986.60 31-JUL-23:40 17.10 11.88 91886256.66 126.84 25-JUL-13:30 17.10 11.88
August 0.181130E+11 7822.50 27-AUG-18:45 19.60 11.80 0.103239E+09 126.83 04-AUG-09:09 19.60 11.80
September 0.133062E+10 1825.84 08-SEP-17:30 13.85 8.80 91319425.66 126.83 13-SEP-13:00 12.20 9.08
October 0.333638E+10 3131.57 03-OCT-16:00 11.70 6.37 95229833.99 126.82 04-OCT-13:09 11.60 5.09
November 0.631807E+10 4190.92 08-NOV-15:50 -15.7 -16.1 94300275.49 126.82 01-NOV-13:09 -15.7 -16.1
December 0.111511E+11 5375.43 21-DEC-17:00 -16.7 -17.3 91880862.99 126.82 19-DEC-14:00 -16.7 -17.3
                     
Annual Sum or Average 0.909612E+11         0.112589E+10        
Minimum of Months 0.323735E+09 628.10   -38.1 -38.2 78703535.46 121.53   -16.7 -17.3
Maximum of Months 0.181130E+11 8069.81   19.60 14.10 0.103239E+09 126.85   19.60 14.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.228347E+12 88891.74 25-JAN-17:00 -20.6 -20.9 0.206189E+10 2746.12 26-JAN-14:09 -18.3 -18.6
February 0.427313E+12 180431.96 09-FEB-17:00 -2.2 -2.6 0.187077E+10 2746.34 14-FEB-10:50 -13.5 -13.8
March 0.721902E+12 356675.03 31-MAR-24:00 -11.8 -13.4 0.223522E+10 2746.08 01-MAR-14:09 -11.8 -13.4
April 0.939696E+12 366334.23 21-APR-16:00 14.40 5.45 0.198315E+10 2750.68 17-APR-13:00 14.40 5.45
May 0.238758E+12 175284.87 31-MAY-24:00 12.40 8.53 0.214860E+10 2747.46 31-MAY-09:30 12.40 8.53
June 0.468588E+12 267091.02 30-JUN-24:00 15.10 14.10 0.214323E+10 2749.67 15-JUN-09:00 15.10 14.10
July 0.731001E+12 359781.43 31-JUL-23:57 16.60 11.46 0.198969E+10 2751.03 25-JUL-09:09 16.60 11.46
August 0.977193E+12 368008.18 28-AUG-16:00 20.00 12.62 0.224138E+10 2833.62 23-AUG-13:00 20.00 12.62
September 0.233410E+12 174493.31 30-SEP-24:00 1.30 -0.1 0.198359E+10 2747.96 21-SEP-09:00 1.30 -0.1
October 0.482170E+12 265431.36 31-OCT-24:00 -10.1 -11.0 0.206198E+10 2746.84 12-OCT-13:20 -10.1 -11.0
November 0.700116E+12 273399.54 08-NOV-17:00 -18.3 -18.6 0.204179E+10 2746.20 27-NOV-10:00 -27.2 -27.4
December 0.966428E+12 364639.71 26-DEC-17:00 -15.6 -15.9 0.198915E+10 2745.63 15-DEC-10:30 -15.6 -15.9
                     
Annual Sum or Average 0.711492E+13         0.247504E+11        
Minimum of Months 0.228347E+12 88891.74   -20.6 -20.9 0.187077E+10 2745.63   -27.2 -27.4
Maximum of Months 0.977193E+12 368008.18   20.00 14.10 0.224138E+10 2833.62   20.00 14.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.249484E+09 10352.81 24-JAN-06:04 -19.9
February 69667817.61 10755.31 21-FEB-06:05 -23.3
March 79985563.09 10710.79 06-MAR-06:05 -21.1
April 0.105121E+09 10909.07 29-APR-04:05 -1.7
May 0.174709E+09 13093.82 19-MAY-04:53 4.40
June 0.209910E+09 12016.09 28-JUN-03:53 11.10
July 0.371038E+09 16097.95 29-JUL-16:02 30.00
August 0.343613E+09 12018.33 06-AUG-22:23 11.95
September 0.429417E+09 10986.44 11-SEP-03:05 3.30
October 0.145363E+09 11084.92 16-OCT-04:25 -1.4
November 85396619.39 10463.35 20-NOV-05:03 -19.2
December 0.121123E+09 10688.25 05-DEC-06:05 -27.9
         
Annual Sum or Average 0.238483E+10      
Minimum of Months 69667817.61 10352.81   -27.9
Maximum of Months 0.429417E+09 16097.95   30.00



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 60775544.12 23301.70 02-JAN-05:01 -15.6
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 60775544.12      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 60775544.12 23301.70   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.199537E+10 58513.69 02-JAN-04:01 -15.1
February 0.619340E+09 51047.42 27-FEB-05:11 -36.1
March 61721002.47 44995.61 06-MAR-06:03 -21.1
April 6095327.33 44224.26 03-APR-05:01 -21.2
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 74314506.54 47585.00 30-OCT-04:01 -14.4
November 0.663678E+09 50672.02 27-NOV-05:01 -25.8
December 0.959367E+09 50689.22 04-DEC-05:01 -19.9
         
Annual Sum or Average 0.437989E+10      
Minimum of Months 0.00 0.00   -36.1
Maximum of Months 0.199537E+10 58513.69   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.149033E+11 77295.30 01-JAN-23:22 -15.0
February 0.933510E+10 77243.29 27-FEB-04:01 -34.7
March 0.535145E+10 75344.97 06-MAR-04:01 -20.0
April 0.142765E+10 73577.24 03-APR-03:11 -21.1
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.157469E+09 66017.15 25-SEP-04:01 -1.1
October 0.376266E+10 76030.39 30-OCT-03:11 -13.7
November 0.110894E+11 77167.31 27-NOV-04:11 -25.9
December 0.137125E+11 76988.50 04-DEC-04:11 -20.0
         
Annual Sum or Average 0.597395E+11      
Minimum of Months 0.00 0.00   -34.7
Maximum of Months 0.149033E+11 77295.30   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.359840E+10 13405.02 02-JAN-04:01 -15.1
February 0.155692E+10 12872.76 27-FEB-04:01 -34.7
March 0.594413E+09 12376.38 01-MAR-04:01 -27.9
April 20520760.88 10974.64 03-APR-05:01 -21.2
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.142518E+09 11285.75 31-OCT-04:01 -17.9
November 0.126777E+10 12105.16 30-NOV-05:01 -27.8
December 0.248905E+10 12117.54 06-DEC-05:01 -28.0
         
Annual Sum or Average 0.966960E+10      
Minimum of Months 0.00 0.00   -34.7
Maximum of Months 0.359840E+10 13405.02   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.280294E+10 16187.31 02-JAN-04:01 -15.1
February 0.112326E+10 15701.51 27-FEB-04:01 -34.7
March 0.392437E+09 15031.44 01-MAR-04:01 -27.9
April 20102249.45 12017.39 03-APR-05:01 -21.2
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.141784E+09 13484.21 31-OCT-04:01 -17.9
November 0.131993E+10 14736.52 30-NOV-05:01 -27.8
December 0.263806E+10 14631.62 01-DEC-05:01 -21.8
         
Annual Sum or Average 0.843850E+10      
Minimum of Months 0.00 0.00   -34.7
Maximum of Months 0.280294E+10 16187.31   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.444001E+10 25310.74 30-JAN-04:01 -25.1
February 0.155632E+10 24629.60 27-FEB-04:01 -34.7
March 0.514691E+09 22539.45 02-MAR-05:01 -26.7
April 28865537.93 18828.00 03-APR-05:01 -21.2
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 193915.62 894.63 28-SEP-05:04 -2.3
October 0.246563E+09 22229.64 30-OCT-04:01 -14.4
November 0.189544E+10 22916.45 30-NOV-05:01 -27.8
December 0.398385E+10 24186.18 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.126659E+11      
Minimum of Months 0.00 0.00   -34.7
Maximum of Months 0.444001E+10 25310.74   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.101396E+10 13952.75 02-JAN-04:01 -15.1
February 0.206217E+09 12896.77 27-FEB-05:01 -36.1
March 26555176.52 12200.56 01-MAR-05:01 -28.3
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 4899167.24 11405.84 31-OCT-05:01 -18.2
November 37669844.60 11386.65 29-NOV-06:01 -28.9
December 31072918.04 11431.80 02-DEC-06:01 -21.1
         
Annual Sum or Average 0.132038E+10      
Minimum of Months 0.00 0.00   -36.1
Maximum of Months 0.101396E+10 13952.75   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.111639E+11 13515.67 30-JAN-04:11 -25.2
February 0.748400E+10 13071.61 26-FEB-09:51 -27.2
March 0.466361E+10 12610.97 13-MAR-01:22 -20.9
April 0.106934E+10 12649.73 03-APR-03:01 -21.1
May 282016.33 1880.11 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 84264763.76 10375.27 30-SEP-04:01 -4.0
October 0.280812E+10 12717.23 30-OCT-01:52 -12.8
November 0.827440E+10 12743.98 26-NOV-16:12 -22.6
December 0.109425E+11 12807.67 04-DEC-00:01 -22.1
         
Annual Sum or Average 0.464904E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.111639E+11 13515.67   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.771784E+10 20132.38 30-JAN-04:11 -25.2
February 0.444147E+10 19253.99 26-FEB-05:11 -25.6
March 0.196060E+10 18615.61 01-MAR-04:01 -27.9
April 0.446646E+09 18609.90 03-APR-03:01 -21.1
May 25255.67 168.37 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 45086295.67 14852.41 28-SEP-05:02 -2.3
October 0.158292E+10 18880.62 30-OCT-03:11 -13.7
November 0.568116E+10 18922.87 27-NOV-04:11 -25.9
December 0.772679E+10 18950.93 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.296025E+11      
Minimum of Months 0.00 0.00   -27.9
Maximum of Months 0.772679E+10 20132.38   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.984421E+10 30463.49 30-JAN-04:11 -25.2
February 0.450951E+10 29209.02 26-FEB-05:11 -25.6
March 0.199411E+10 28104.03 01-MAR-04:01 -27.9
April 0.379529E+09 27054.18 03-APR-03:01 -21.1
May 243923.58 1626.16 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 36449330.66 22397.54 30-SEP-05:01 -4.5
October 0.158792E+10 28600.54 30-OCT-03:11 -13.7
November 0.620276E+10 28700.83 27-NOV-04:11 -25.9
December 0.105369E+11 28826.94 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.350917E+11      
Minimum of Months 0.00 0.00   -27.9
Maximum of Months 0.105369E+11 30463.49   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.658960E+10 20015.80 30-JAN-04:11 -25.2
February 0.368214E+10 19302.53 26-FEB-09:51 -27.2
March 0.189114E+10 18488.41 01-MAR-04:01 -27.9
April 0.265453E+09 17781.19 03-APR-03:01 -21.1
May 288434.23 1922.89 27-MAY-05:03 0.10
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 30386391.66 14599.59 30-SEP-05:01 -4.5
October 0.128541E+10 18718.60 30-OCT-03:11 -13.7
November 0.413979E+10 18788.03 27-NOV-04:11 -25.9
December 0.592804E+10 18800.72 04-DEC-04:01 -20.0
         
Annual Sum or Average 0.238123E+11      
Minimum of Months 0.00 0.00   -27.9
Maximum of Months 0.658960E+10 20015.80   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.190595E+11 18341.44 30-JAN-05:21 -25.6
February 0.144675E+11 17890.49 26-FEB-18:42 -26.8
March 0.111548E+11 17484.08 27-MAR-01:22 -17.5
April 0.371727E+10 17515.49 02-APR-21:52 -14.4
May 68510416.42 14169.65 27-MAY-04:02 0.00
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 51438501.04 13631.53 31-AUG-04:03 -0.7
September 0.103767E+10 15368.47 25-SEP-03:02 -0.7
October 0.786075E+10 17489.58 22-OCT-20:12 -14.6
November 0.160126E+11 17491.59 13-NOV-03:12 -19.6
December 0.191965E+11 17857.20 03-DEC-10:12 -22.8
         
Annual Sum or Average 0.926265E+11      
Minimum of Months 0.00 0.00   -26.8
Maximum of Months 0.191965E+11 18341.44   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.128134E+11 20433.87 29-JAN-00:01 -25.0
February 0.870809E+10 20105.87 26-FEB-00:42 -27.1
March 0.499340E+10 19478.71 27-MAR-01:22 -17.5
April 0.162220E+10 19469.30 02-APR-21:52 -14.4
May 16014768.53 15809.63 27-MAY-04:02 0.00
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 20307831.59 10902.00 31-AUG-05:02 -1.2
September 0.428742E+09 16760.03 28-SEP-04:01 -1.8
October 0.438698E+10 19597.92 30-OCT-01:52 -12.8
November 0.106202E+11 19607.64 26-NOV-05:32 -24.6
December 0.130649E+11 20142.53 03-DEC-10:12 -22.8
         
Annual Sum or Average 0.566742E+11      
Minimum of Months 0.00 0.00   -27.1
Maximum of Months 0.130649E+11 20433.87   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.175301E+11 32116.88 29-JAN-00:01 -25.0
February 0.100045E+11 31560.01 26-FEB-00:42 -27.1
March 0.578469E+10 30243.01 03-MAR-04:01 -25.6
April 0.178160E+10 30478.62 02-APR-07:12 -15.2
May 45521455.66 24869.90 27-MAY-04:02 0.00
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 20409786.96 15594.81 31-AUG-05:02 -1.2
September 0.534217E+09 26448.42 28-SEP-04:01 -1.8
October 0.524000E+10 30876.91 30-OCT-01:52 -12.8
November 0.133102E+11 30882.77 27-NOV-04:11 -25.9
December 0.188234E+11 31842.63 03-DEC-10:12 -22.8
         
Annual Sum or Average 0.730746E+11      
Minimum of Months 0.00 0.00   -27.1
Maximum of Months 0.188234E+11 32116.88   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.117222E+11 21553.84 29-JAN-00:01 -25.0
February 0.756269E+10 20947.39 26-FEB-10:01 -27.2
March 0.486055E+10 20329.84 03-MAR-04:01 -25.6
April 0.114565E+10 20166.51 03-APR-03:11 -21.1
May 30727864.98 16633.82 27-MAY-04:02 0.00
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 10890130.60 10179.03 31-AUG-05:02 -1.2
September 0.357656E+09 17525.03 28-SEP-04:01 -1.8
October 0.368551E+10 20439.39 30-OCT-03:11 -13.7
November 0.844790E+10 20460.25 27-NOV-04:11 -25.9
December 0.106563E+11 20914.45 03-DEC-10:12 -22.8
         
Annual Sum or Average 0.484801E+11      
Minimum of Months 0.00 0.00   -27.2
Maximum of Months 0.117222E+11 21553.84   14.88



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.470221E+10 13711.78 02-JAN-06:13 -15.2
February 0.242700E+10 12599.10 09-FEB-06:01 0.00
March 0.168004E+10 13213.36 07-MAR-06:01 -8.0
April 0.346432E+09 12847.74 10-APR-04:01 -5.3
May 0.124627E+09 10116.18 01-MAY-03:02 6.70
June 97716243.56 9490.12 26-JUN-03:02 12.70
July 0.135079E+09 9710.62 03-JUL-03:02 10.50
August 0.149171E+09 10886.72 16-AUG-03:02 11.60
September 70820076.45 10025.10 25-SEP-04:01 -1.1
October 0.603703E+09 12199.84 16-OCT-04:01 -1.2
November 0.241324E+10 11008.05 02-NOV-05:01 -11.0
December 0.374517E+10 4951.78 04-DEC-14:10 -21.2
         
Annual Sum or Average 0.164952E+11      
Minimum of Months 70820076.45 4951.78   -21.2
Maximum of Months 0.470221E+10 13711.78   12.70



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.843451E+10 23035.62 02-JAN-06:13 -15.2
February 0.528413E+10 14198.59 27-FEB-06:12 -35.7
March 0.412894E+10 9549.99 31-MAR-15:05 -9.9
April 0.134968E+10 13102.36 09-APR-14:02 2.48
May 0.111039E+09 12000.01 21-MAY-11:42 14.22
June 68638590.58 7515.53 04-JUN-15:22 19.70
July 71026307.88 8874.27 23-JUL-11:32 23.53
August 59281701.46 10129.91 27-AUG-16:32 20.93
September 0.200661E+09 10124.97 10-SEP-11:22 15.00
October 0.235137E+10 8199.86 04-OCT-05:03 7.70
November 0.596233E+10 12775.43 27-NOV-06:06 -26.7
December 0.743451E+10 15148.99 04-DEC-06:12 -19.4
         
Annual Sum or Average 0.354561E+11      
Minimum of Months 59281701.46 7515.53   -35.7
Maximum of Months 0.843451E+10 23035.62   23.53



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275589E+11 36282.07 12-JAN-05:33 -38.1
February 0.207364E+11 35283.02 27-FEB-05:41 -36.1
March 0.161566E+11 31676.37 06-MAR-05:12 -20.4
April 0.589145E+10 30635.16 03-APR-04:12 -21.1
May 0.703881E+09 18392.45 12-MAY-05:03 5.37
June 0.143628E+09 19142.94 02-JUN-05:03 5.78
July 0.129251E+09 18404.36 06-JUL-05:02 8.77
August 0.468323E+09 14804.00 10-AUG-05:02 10.10
September 0.286910E+10 13684.61 25-SEP-05:03 -1.2
October 0.120327E+11 29848.70 30-OCT-04:13 -14.4
November 0.243072E+11 33702.17 27-NOV-05:13 -26.0
December 0.286240E+11 33246.17 28-DEC-06:13 -28.0
         
Annual Sum or Average 0.139622E+12      
Minimum of Months 0.129251E+09 13684.61   -38.1
Maximum of Months 0.286240E+11 36282.07   10.10



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.198805E+09 575.31 01-JAN-18:02 -14.4
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.198805E+09      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.198805E+09 575.31   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.747728E+09 579.99 12-JAN-22:13 -36.3
February 829028.77 82.59 27-FEB-04:01 -34.7
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.748557E+09      
Minimum of Months 0.00 0.00   -36.3
Maximum of Months 0.747728E+09 579.99   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.776737E+09 606.91 30-JAN-23:45 -24.4
February 0.280052E+09 586.41 26-FEB-17:40 -24.8
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 17910861.61 559.49 28-MAY-04:25 1.95
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.158090E+09 577.17 30-SEP-03:00 -3.3
October 0.103690E+09 566.70 22-OCT-21:13 -15.4
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.133648E+10      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.776737E+09 606.91   16.35



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:02 -14.9
February 0.00 0.00 01-FEB-00:03 -20.2
March 0.00 0.00 01-MAR-00:05 -28.9
April 0.00 0.00 01-APR-00:10 -11.7
May 0.00 0.00 01-MAY-00:10 6.70
June 0.00 0.00 01-JUN-00:10 12.17
July 0.00 0.00 01-JUL-00:10 14.88
August 0.00 0.00 01-AUG-00:05 16.35
September 0.00 0.00 01-SEP-00:10 8.08
October 0.00 0.00 01-OCT-00:10 1.42
November 0.00 0.00 01-NOV-00:10 -10.0
December 0.00 0.00 01-DEC-00:10 -25.8
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   -28.9
Maximum of Months 0.00 0.00   16.35



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.148304E+11 15519.45 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.134523E+11 15519.45 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.159851E+11 15519.45 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.142779E+11 15519.45 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.154078E+11 15519.45 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.153333E+11 15519.45 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.143524E+11 15519.45 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.159851E+11 15519.45 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.142779E+11 15519.45 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.148304E+11 15519.45 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.146566E+11 15519.45 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.143524E+11 15519.45 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.177742E+12     0.424397E+12    
Minimum of Months 0.134523E+11 15519.45   0.325565E+11 13457.54  
Maximum of Months 0.159851E+11 15519.45   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321286E+12    
Minimum of Months 0.120811E+11 13937.56   0.244881E+11 18128.59  
Maximum of Months 0.143557E+11 13937.56   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158655E+10 1750.00 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.124994E+10 1750.00 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.127271E+10 1750.00 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.104944E+10 1179.00 04-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.110649E+10 1075.02 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.108633E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.102643E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.116766E+10 1075.02 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110022E+10 1683.33 28-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.127541E+10 1750.00 03-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.149303E+10 1750.00 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.159064E+10 1750.00 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.150049E+11     0.403423E+11    
Minimum of Months 0.102643E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.159064E+10 1750.00   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.999786E+09 1127.77 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.789954E+09 1127.77 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.815073E+09 1127.77 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.677728E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.719182E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.704768E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.665956E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.756561E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.708571E+09 1013.59 28-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.813510E+09 1127.77 03-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.934347E+09 1127.77 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.101733E+10 1127.77 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.960277E+10     0.259981E+11    
Minimum of Months 0.665956E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.101733E+10 1127.77   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.151091E+10 1750.04 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.119721E+10 1750.04 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.125296E+10 1750.04 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.105259E+10 1176.88 04-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.111491E+10 1075.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.109426E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.103321E+10 1075.05 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.117176E+10 1075.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.109230E+10 1632.01 28-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.124482E+10 1750.04 03-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.140288E+10 1750.04 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.155215E+10 1750.04 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.147199E+11     0.403429E+11    
Minimum of Months 0.103321E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.155215E+10 1750.04   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.100592E+10 1127.77 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.782054E+09 1127.77 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.813737E+09 1127.77 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.678427E+09 859.76 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.713861E+09 692.79 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.701271E+09 692.79 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.662181E+09 692.79 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.751992E+09 692.79 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.705886E+09 1088.11 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.809869E+09 1127.77 03-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.934699E+09 1127.77 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.102054E+10 1127.77 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.958044E+10     0.259979E+11    
Minimum of Months 0.662181E+09 692.79   0.198154E+10 1466.94  
Maximum of Months 0.102054E+10 1127.77   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158952E+10 1750.00 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.125387E+10 1750.00 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.127413E+10 1750.00 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.104981E+10 1195.98 04-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.110673E+10 1075.02 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.108654E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.102679E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.116895E+10 1075.02 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110171E+10 1685.76 28-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.127852E+10 1750.00 03-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.149733E+10 1750.00 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.159170E+10 1750.00 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.150256E+11     0.403423E+11    
Minimum of Months 0.102679E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.159170E+10 1750.00   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.100081E+10 1127.77 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.790619E+09 1127.77 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.815355E+09 1127.77 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.677871E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.719311E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.704932E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.666064E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.756714E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.708871E+09 1017.84 28-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.814024E+09 1127.77 03-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.935614E+09 1127.77 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.101785E+10 1127.77 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.960803E+10     0.259981E+11    
Minimum of Months 0.666064E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.101785E+10 1127.77   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.151454E+10 1750.04 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.119830E+10 1750.04 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.125546E+10 1750.04 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.105304E+10 1193.89 04-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.111544E+10 1075.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.109478E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.103367E+10 1075.05 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.117227E+10 1075.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.109270E+10 1636.84 28-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.124598E+10 1750.04 03-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.140612E+10 1750.04 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.155760E+10 1750.04 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.147399E+11     0.403429E+11    
Minimum of Months 0.103367E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.155760E+10 1750.04   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.100690E+10 1127.77 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.782606E+09 1127.77 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.814059E+09 1127.77 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.678598E+09 863.36 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.713965E+09 692.79 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.701381E+09 692.79 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.662309E+09 692.79 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.752148E+09 692.79 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.706336E+09 1089.09 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.810458E+09 1127.77 03-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.937548E+09 1127.77 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.102094E+10 1127.77 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.958725E+10     0.259979E+11    
Minimum of Months 0.662309E+09 692.79   0.198154E+10 1466.94  
Maximum of Months 0.102094E+10 1127.77   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.158955E+10 1750.00 02-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.125395E+10 1750.00 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.127414E+10 1750.00 01-MAR-08:09 0.352283E+10 2276.32 01-MAR-08:09
April 0.104982E+10 1195.68 04-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.110674E+10 1075.02 01-MAY-07:10 0.346000E+10 2276.32 01-MAY-07:10
June 0.108655E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.102680E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.116895E+10 1075.02 01-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.110171E+10 1685.83 28-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.127853E+10 1750.00 03-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.149734E+10 1750.00 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.159171E+10 1750.00 01-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.150258E+11     0.403423E+11    
Minimum of Months 0.102680E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.159171E+10 1750.00   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.100083E+10 1127.77 02-JAN-08:09 0.218927E+10 1466.95 02-JAN-08:09
February 0.790638E+09 1127.77 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.815364E+09 1127.77 01-MAR-08:09 0.227025E+10 1466.95 01-MAR-08:09
April 0.677876E+09 692.79 03-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.719315E+09 692.79 01-MAY-07:10 0.222976E+10 1466.95 01-MAY-07:10
June 0.704933E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.666064E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.756715E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.708887E+09 1018.19 28-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.814027E+09 1127.77 03-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.935636E+09 1127.77 01-NOV-07:10 0.213969E+10 1466.95 01-NOV-07:10
December 0.101786E+10 1127.77 01-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.960814E+10     0.259981E+11    
Minimum of Months 0.666064E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.101786E+10 1127.77   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.151458E+10 1750.04 02-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.119832E+10 1750.04 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.125546E+10 1750.04 01-MAR-08:09 0.352288E+10 2276.35 01-MAR-08:09
April 0.105305E+10 1193.59 04-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.111544E+10 1075.05 01-MAY-07:10 0.346006E+10 2276.35 01-MAY-07:10
June 0.109478E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.103367E+10 1075.05 03-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.117227E+10 1075.05 01-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.109270E+10 1637.04 28-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.124598E+10 1750.04 03-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.140623E+10 1750.04 01-NOV-07:10 0.332029E+10 2276.35 01-NOV-07:10
December 0.155768E+10 1750.04 01-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.147402E+11     0.403429E+11    
Minimum of Months 0.103367E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.155768E+10 1750.04   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.100692E+10 1127.77 02-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.782619E+09 1127.77 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.814069E+09 1127.77 01-MAR-08:09 0.227023E+10 1466.94 01-MAR-08:09
April 0.678601E+09 863.42 03-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.713968E+09 692.79 01-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.701382E+09 692.79 01-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.662310E+09 692.79 03-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.752150E+09 692.79 01-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.706336E+09 1089.14 29-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.810462E+09 1127.77 03-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.937570E+09 1127.77 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.102095E+10 1127.77 01-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.958734E+10     0.259979E+11    
Minimum of Months 0.662310E+09 692.79   0.198154E+10 1466.94  
Maximum of Months 0.102095E+10 1127.77   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.418155E+10 4375.82 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.379298E+10 4375.82 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.450711E+10 4375.82 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.402577E+10 4375.82 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.434433E+10 4375.82 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.432333E+10 4375.82 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.404678E+10 4375.82 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.450711E+10 4375.82 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.402577E+10 4375.82 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.418155E+10 4375.82 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.413254E+10 4375.82 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.404678E+10 4375.82 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.501156E+11     0.749486E+13    
Minimum of Months 0.379298E+10 4375.82   0.246344E+12 94908.13  
Maximum of Months 0.450711E+10 4375.82   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.154078E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.153333E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.146566E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.177742E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.158655E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.772322E+09
February 0.136985E+10 0.124994E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.631051E+09
March 0.163685E+10 0.127271E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.963390E+09
April 0.145243E+10 0.104944E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.110281E+10
May 0.157338E+10 0.110649E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.00 0.644581E+09
June 0.156900E+10 0.108633E+10 0.339353E+10 0.00 0.00 0.00 0.00 813642.07 0.377482E+09
July 0.145680E+10 0.102643E+10 0.334664E+10 0.00 0.00 0.00 0.00 2578037.36 0.274005E+09
August 0.163685E+10 0.116766E+10 0.352283E+10 0.00 0.00 0.00 0.00 380749.99 0.331164E+09
September 0.145243E+10 0.110022E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.00 0.405539E+09
October 0.150991E+10 0.127541E+10 0.339809E+10 0.00 0.00 0.00 0.00 0.00 0.864381E+09
November 0.149516E+10 0.149303E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.296175E+09
December 0.145680E+10 0.159064E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.579553E+09
                   
Annual Sum or Average 0.181194E+11 0.150049E+11 0.403423E+11 0.00 0.00 0.00 0.00 3772429.42 0.724246E+10
Minimum of Months 0.136985E+10 0.102643E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.274005E+09
Maximum of Months 0.163685E+10 0.159064E+10 0.352283E+10 0.00 0.00 0.00 0.00 2578037.36 0.110281E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.999786E+09 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.511834E+09
February 0.882782E+09 0.789954E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.418741E+09
March 0.105485E+10 0.815073E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.643888E+09
April 0.936002E+09 0.677728E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.734342E+09
May 0.101394E+10 0.719182E+09 0.222976E+10 0.00 0.00 0.00 0.00 0.00 0.433079E+09
June 0.101113E+10 0.704768E+09 0.218692E+10 0.00 0.00 0.00 0.00 542421.89 0.245805E+09
July 0.938820E+09 0.665956E+09 0.215670E+10 0.00 0.00 0.00 0.00 1846599.08 0.175604E+09
August 0.105485E+10 0.756561E+09 0.227025E+10 0.00 0.00 0.00 0.00 253875.63 0.211916E+09
September 0.936002E+09 0.708571E+09 0.211328E+10 0.00 0.00 0.00 0.00 0.00 0.272139E+09
October 0.973041E+09 0.813510E+09 0.218986E+10 0.00 0.00 0.00 0.00 0.00 0.572548E+09
November 0.963541E+09 0.934347E+09 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.195097E+09
December 0.938820E+09 0.101733E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.380671E+09
                   
Annual Sum or Average 0.116768E+11 0.960277E+10 0.259981E+11 0.00 0.00 0.00 0.00 2642896.59 0.479567E+10
Minimum of Months 0.882782E+09 0.665956E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.175604E+09
Maximum of Months 0.105485E+10 0.101733E+10 0.227025E+10 0.00 0.00 0.00 0.00 1846599.08 0.734342E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.151091E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.762322E+09
February 0.136988E+10 0.119721E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.630197E+09
March 0.163688E+10 0.125296E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.974788E+09
April 0.145246E+10 0.105259E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.112811E+10
May 0.157341E+10 0.111491E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.00 0.651024E+09
June 0.156904E+10 0.109426E+10 0.339359E+10 0.00 0.00 0.00 0.00 813622.77 0.373757E+09
July 0.145684E+10 0.103321E+10 0.334669E+10 0.00 0.00 0.00 0.00 2412167.83 0.271961E+09
August 0.163688E+10 0.117176E+10 0.352288E+10 0.00 0.00 0.00 0.00 379835.55 0.331888E+09
September 0.145246E+10 0.109230E+10 0.327931E+10 0.00 0.00 0.00 0.00 0.00 0.409035E+09
October 0.150994E+10 0.124482E+10 0.339814E+10 0.00 0.00 0.00 0.00 0.00 0.853739E+09
November 0.149520E+10 0.140288E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.290915E+09
December 0.145684E+10 0.155215E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.565306E+09
                   
Annual Sum or Average 0.181198E+11 0.147199E+11 0.403429E+11 0.00 0.00 0.00 0.00 3605626.15 0.724304E+10
Minimum of Months 0.136988E+10 0.103321E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.271961E+09
Maximum of Months 0.163688E+10 0.155215E+10 0.352288E+10 0.00 0.00 0.00 0.00 2412167.83 0.112811E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.100592E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.526145E+09
February 0.882782E+09 0.782054E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.434354E+09
March 0.105485E+10 0.813737E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.680674E+09
April 0.936002E+09 0.678427E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.814155E+09
May 0.101394E+10 0.713861E+09 0.222974E+10 0.00 0.00 0.00 0.00 0.00 0.458228E+09
June 0.101113E+10 0.701271E+09 0.218691E+10 0.00 0.00 0.00 0.00 542424.20 0.273191E+09
July 0.938820E+09 0.662181E+09 0.215669E+10 0.00 0.00 0.00 0.00 1383718.24 0.202146E+09
August 0.105485E+10 0.751992E+09 0.227023E+10 0.00 0.00 0.00 0.00 253821.39 0.245364E+09
September 0.936002E+09 0.705886E+09 0.211327E+10 0.00 0.00 0.00 0.00 0.00 0.285170E+09
October 0.973041E+09 0.809869E+09 0.218984E+10 0.00 0.00 0.00 0.00 0.00 0.604540E+09
November 0.963541E+09 0.934699E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.206116E+09
December 0.938820E+09 0.102054E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.405650E+09
                   
Annual Sum or Average 0.116768E+11 0.958044E+10 0.259979E+11 0.00 0.00 0.00 0.00 2179963.82 0.513573E+10
Minimum of Months 0.882782E+09 0.662181E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.202146E+09
Maximum of Months 0.105485E+10 0.102054E+10 0.227023E+10 0.00 0.00 0.00 0.00 1383718.24 0.814155E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.158952E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.174225E+10
February 0.136985E+10 0.125387E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.140518E+10
March 0.163685E+10 0.127413E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.208329E+10
April 0.145243E+10 0.104981E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.230875E+10
May 0.157338E+10 0.110673E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.00 0.141959E+10
June 0.156900E+10 0.108654E+10 0.339353E+10 0.00 0.00 0.00 0.00 1768841.09 0.847094E+09
July 0.145680E+10 0.102679E+10 0.334664E+10 0.00 0.00 0.00 0.00 6048985.66 0.633799E+09
August 0.163685E+10 0.116895E+10 0.352283E+10 0.00 0.00 0.00 0.00 780297.67 0.742929E+09
September 0.145243E+10 0.110171E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.00 0.868135E+09
October 0.150991E+10 0.127852E+10 0.339809E+10 0.00 0.00 0.00 0.00 0.00 0.181869E+10
November 0.149516E+10 0.149733E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.644337E+09
December 0.145680E+10 0.159170E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.126634E+10
                   
Annual Sum or Average 0.181194E+11 0.150256E+11 0.403423E+11 0.00 0.00 0.00 0.00 8598124.42 0.157804E+11
Minimum of Months 0.136985E+10 0.102679E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.633799E+09
Maximum of Months 0.163685E+10 0.159170E+10 0.352283E+10 0.00 0.00 0.00 0.00 6048985.66 0.230875E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.100081E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.116398E+10
February 0.649041E+09 0.790619E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.939395E+09
March 0.773965E+09 0.815355E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.141373E+10
April 0.688021E+09 0.677871E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.159745E+10
May 0.744847E+09 0.719311E+09 0.222976E+10 0.00 0.00 0.00 0.00 0.00 0.975760E+09
June 0.742030E+09 0.704932E+09 0.218692E+10 0.00 0.00 0.00 0.00 1179591.02 0.567323E+09
July 0.690839E+09 0.666064E+09 0.215670E+10 0.00 0.00 0.00 0.00 4116383.10 0.429108E+09
August 0.773965E+09 0.756714E+09 0.227025E+10 0.00 0.00 0.00 0.00 524826.80 0.503101E+09
September 0.688021E+09 0.708871E+09 0.211328E+10 0.00 0.00 0.00 0.00 0.00 0.598665E+09
October 0.715730E+09 0.814024E+09 0.218986E+10 0.00 0.00 0.00 0.00 0.00 0.122516E+10
November 0.708685E+09 0.935614E+09 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.429420E+09
December 0.690839E+09 0.101785E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.843994E+09
                   
Annual Sum or Average 0.858171E+10 0.960803E+10 0.259981E+11 0.00 0.00 0.00 0.00 5820800.92 0.106871E+11
Minimum of Months 0.649041E+09 0.666064E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.429108E+09
Maximum of Months 0.773965E+09 0.101785E+10 0.227025E+10 0.00 0.00 0.00 0.00 4116383.10 0.159745E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.151454E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.175047E+10
February 0.136988E+10 0.119830E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.142752E+10
March 0.163688E+10 0.125546E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.219164E+10
April 0.145246E+10 0.105304E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.253303E+10
May 0.157341E+10 0.111544E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.00 0.148973E+10
June 0.156904E+10 0.109478E+10 0.339359E+10 0.00 0.00 0.00 0.00 1768757.99 0.860350E+09
July 0.145684E+10 0.103367E+10 0.334669E+10 0.00 0.00 0.00 0.00 5291927.84 0.653378E+09
August 0.163688E+10 0.117227E+10 0.352288E+10 0.00 0.00 0.00 0.00 778020.23 0.782216E+09
September 0.145246E+10 0.109270E+10 0.327931E+10 0.00 0.00 0.00 0.00 0.00 0.933389E+09
October 0.150994E+10 0.124598E+10 0.339814E+10 0.00 0.00 0.00 0.00 0.00 0.189320E+10
November 0.149520E+10 0.140612E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.648909E+09
December 0.145684E+10 0.155760E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.126935E+10
                   
Annual Sum or Average 0.181198E+11 0.147399E+11 0.403429E+11 0.00 0.00 0.00 0.00 7838706.06 0.164332E+11
Minimum of Months 0.136988E+10 0.103367E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.648909E+09
Maximum of Months 0.163688E+10 0.155760E+10 0.352288E+10 0.00 0.00 0.00 0.00 5291927.84 0.253303E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.100690E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.116919E+10
February 0.882782E+09 0.782606E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.945085E+09
March 0.105485E+10 0.814059E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.142318E+10
April 0.936002E+09 0.678598E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.167230E+10
May 0.101394E+10 0.713965E+09 0.222974E+10 0.00 0.00 0.00 0.00 0.00 0.100475E+10
June 0.101113E+10 0.701381E+09 0.218691E+10 0.00 0.00 0.00 0.00 1179227.15 0.590409E+09
July 0.938820E+09 0.662309E+09 0.215669E+10 0.00 0.00 0.00 0.00 3130381.49 0.447495E+09
August 0.105485E+10 0.752148E+09 0.227023E+10 0.00 0.00 0.00 0.00 520182.36 0.523688E+09
September 0.936002E+09 0.706336E+09 0.211327E+10 0.00 0.00 0.00 0.00 0.00 0.601770E+09
October 0.973041E+09 0.810458E+09 0.218984E+10 0.00 0.00 0.00 0.00 0.00 0.123573E+10
November 0.963541E+09 0.937548E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.433525E+09
December 0.938820E+09 0.102094E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.852349E+09
                   
Annual Sum or Average 0.116768E+11 0.958725E+10 0.259979E+11 0.00 0.00 0.00 0.00 4829791.00 0.108995E+11
Minimum of Months 0.882782E+09 0.662309E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.433525E+09
Maximum of Months 0.105485E+10 0.102094E+10 0.227023E+10 0.00 0.00 0.00 0.00 3130381.49 0.167230E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.158955E+10 0.339718E+10 0.00 0.00 0.00 0.00 0.00 0.214120E+10
February 0.136985E+10 0.125395E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.171896E+10
March 0.163685E+10 0.127414E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.00 0.251549E+10
April 0.145243E+10 0.104982E+10 0.328108E+10 0.00 0.00 0.00 0.00 0.00 0.269907E+10
May 0.157338E+10 0.110674E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.00 0.163200E+10
June 0.156900E+10 0.108655E+10 0.339353E+10 0.00 0.00 0.00 0.00 2031040.54 0.100954E+10
July 0.145680E+10 0.102680E+10 0.334664E+10 0.00 0.00 0.00 0.00 7102365.46 0.764966E+09
August 0.163685E+10 0.116895E+10 0.352283E+10 0.00 0.00 0.00 0.00 851754.99 0.870377E+09
September 0.145243E+10 0.110171E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.00 0.969550E+09
October 0.150991E+10 0.127853E+10 0.339809E+10 0.00 0.00 0.00 0.00 0.00 0.212360E+10
November 0.149516E+10 0.149734E+10 0.332024E+10 0.00 0.00 0.00 0.00 0.00 0.789207E+09
December 0.145680E+10 0.159171E+10 0.334573E+10 0.00 0.00 0.00 0.00 0.00 0.155761E+10
                   
Annual Sum or Average 0.181194E+11 0.150258E+11 0.403423E+11 0.00 0.00 0.00 0.00 9985160.99 0.187916E+11
Minimum of Months 0.136985E+10 0.102680E+10 0.307485E+10 0.00 0.00 0.00 0.00 0.00 0.764966E+09
Maximum of Months 0.163685E+10 0.159171E+10 0.352283E+10 0.00 0.00 0.00 0.00 7102365.46 0.269907E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.100083E+10 0.218927E+10 0.00 0.00 0.00 0.00 0.00 0.143457E+10
February 0.882782E+09 0.790638E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.115092E+10
March 0.105485E+10 0.815364E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.00 0.169307E+10
April 0.936002E+09 0.677876E+09 0.211446E+10 0.00 0.00 0.00 0.00 0.00 0.186830E+10
May 0.101394E+10 0.719315E+09 0.222976E+10 0.00 0.00 0.00 0.00 0.00 0.115461E+10
June 0.101113E+10 0.704933E+09 0.218692E+10 0.00 0.00 0.00 0.00 1354010.63 0.686831E+09
July 0.938820E+09 0.666064E+09 0.215670E+10 0.00 0.00 0.00 0.00 4497790.55 0.527220E+09
August 0.105485E+10 0.756715E+09 0.227025E+10 0.00 0.00 0.00 0.00 558825.75 0.603691E+09
September 0.936002E+09 0.708887E+09 0.211328E+10 0.00 0.00 0.00 0.00 0.00 0.683482E+09
October 0.973041E+09 0.814027E+09 0.218986E+10 0.00 0.00 0.00 0.00 0.00 0.142923E+10
November 0.963541E+09 0.935636E+09 0.213969E+10 0.00 0.00 0.00 0.00 0.00 0.527409E+09
December 0.938820E+09 0.101786E+10 0.215612E+10 0.00 0.00 0.00 0.00 0.00 0.104137E+10
                   
Annual Sum or Average 0.116768E+11 0.960814E+10 0.259981E+11 0.00 0.00 0.00 0.00 6410626.92 0.128007E+11
Minimum of Months 0.882782E+09 0.666064E+09 0.198155E+10 0.00 0.00 0.00 0.00 0.00 0.527220E+09
Maximum of Months 0.105485E+10 0.101786E+10 0.227025E+10 0.00 0.00 0.00 0.00 4497790.55 0.186830E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.151458E+10 0.339723E+10 0.00 0.00 0.00 0.00 0.00 0.215522E+10
February 0.136988E+10 0.119832E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.173642E+10
March 0.163688E+10 0.125546E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.00 0.259848E+10
April 0.145246E+10 0.105305E+10 0.328113E+10 0.00 0.00 0.00 0.00 0.00 0.295405E+10
May 0.157341E+10 0.111544E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.00 0.176137E+10
June 0.156904E+10 0.109478E+10 0.339359E+10 0.00 0.00 0.00 0.00 2030994.89 0.103659E+10
July 0.145684E+10 0.103367E+10 0.334669E+10 0.00 0.00 0.00 0.00 5900884.07 0.799274E+09
August 0.163688E+10 0.117227E+10 0.352288E+10 0.00 0.00 0.00 0.00 835367.83 0.938211E+09
September 0.145246E+10 0.109270E+10 0.327931E+10 0.00 0.00 0.00 0.00 0.00 0.107318E+10
October 0.150994E+10 0.124598E+10 0.339814E+10 0.00 0.00 0.00 0.00 0.00 0.219132E+10
November 0.149520E+10 0.140623E+10 0.332029E+10 0.00 0.00 0.00 0.00 0.00 0.793142E+09
December 0.145684E+10 0.155768E+10 0.334578E+10 0.00 0.00 0.00 0.00 0.00 0.156340E+10
                   
Annual Sum or Average 0.181198E+11 0.147402E+11 0.403429E+11 0.00 0.00 0.00 0.00 8767246.79 0.196007E+11
Minimum of Months 0.136988E+10 0.103367E+10 0.307490E+10 0.00 0.00 0.00 0.00 0.00 0.793142E+09
Maximum of Months 0.163688E+10 0.155768E+10 0.352288E+10 0.00 0.00 0.00 0.00 5900884.07 0.295405E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.100692E+10 0.218926E+10 0.00 0.00 0.00 0.00 0.00 0.143797E+10
February 0.882782E+09 0.782619E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.115700E+10
March 0.105485E+10 0.814069E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.00 0.170567E+10
April 0.936002E+09 0.678601E+09 0.211444E+10 0.00 0.00 0.00 0.00 0.00 0.195806E+10
May 0.101394E+10 0.713968E+09 0.222974E+10 0.00 0.00 0.00 0.00 0.00 0.119003E+10
June 0.101113E+10 0.701382E+09 0.218691E+10 0.00 0.00 0.00 0.00 1354018.37 0.713197E+09
July 0.938820E+09 0.662310E+09 0.215669E+10 0.00 0.00 0.00 0.00 3594086.11 0.547436E+09
August 0.105485E+10 0.752150E+09 0.227023E+10 0.00 0.00 0.00 0.00 558464.07 0.626640E+09
September 0.936002E+09 0.706336E+09 0.211327E+10 0.00 0.00 0.00 0.00 0.00 0.693763E+09
October 0.973041E+09 0.810462E+09 0.218984E+10 0.00 0.00 0.00 0.00 0.00 0.144923E+10
November 0.963541E+09 0.937570E+09 0.213967E+10 0.00 0.00 0.00 0.00 0.00 0.529911E+09
December 0.938820E+09 0.102095E+10 0.215610E+10 0.00 0.00 0.00 0.00 0.00 0.104512E+10
                   
Annual Sum or Average 0.116768E+11 0.958734E+10 0.259979E+11 0.00 0.00 0.00 0.00 5506568.54 0.130540E+11
Minimum of Months 0.882782E+09 0.662310E+09 0.198154E+10 0.00 0.00 0.00 0.00 0.00 0.529911E+09
Maximum of Months 0.105485E+10 0.102095E+10 0.227023E+10 0.00 0.00 0.00 0.00 3594086.11 0.195806E+10



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.418155E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.379298E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.450711E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.402577E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.434433E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.432333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.404678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.450711E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.402577E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.418155E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.413254E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.404678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.501156E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.379298E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.450711E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.161803E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.132812E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.203650E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.232640E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133561E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 946136.20 0.768956E+09
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3743189.42 0.564003E+09
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 261882.84 0.694706E+09
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.850140E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.182350E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.624565E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.120876E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4951208.46 0.151793E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.564003E+09
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3743189.42 0.232640E+10



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.277114E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.227230E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.347402E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.395129E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.234486E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1630689.15 0.135610E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7007043.35 0.100212E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 448865.05 0.122747E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.147622E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.307768E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.105522E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.204056E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9086597.55 0.260490E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.100212E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7007043.35 0.395129E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.304692E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.248591E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.374602E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.421445E+10
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.258137E+10
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 991005.49 0.156090E+10
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4921762.41 0.118150E+10
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 86326.53 0.137624E+10
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.153128E+10
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.317039E+10
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.113643E+10
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.222918E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5999094.44 0.282606E+11
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.113643E+10
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4921762.41 0.421445E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 15519.45 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 15519.45 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 15519.45 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 15519.45 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 15519.45 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 15519.45 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 15519.45 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 15519.45 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 15519.45 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 15519.45 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 15519.45 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 15519.45 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1750.00 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 3370.92 28-JAN-23:51
February 2010.79 01-FEB-10:09 1750.00 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2057.74 25-FEB-01:00
March 2010.79 01-MAR-10:09 1750.00 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 1485.72 25-MAR-03:55
April 2010.79 03-APR-09:09 1179.00 04-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2273.27 01-APR-19:00
May 2010.79 01-MAY-09:09 1075.02 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1084.23 26-MAY-02:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 45.86 30-JUN-15:00 1097.15 25-JUN-06:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 113.63 21-JUL-16:00 703.30 04-JUL-16:53
August 2010.79 01-AUG-09:09 1075.02 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 17.23 11-AUG-16:00 859.61 30-AUG-01:00
September 2010.79 01-SEP-09:09 1683.33 28-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 718.25 04-SEP-14:00
October 2010.79 02-OCT-09:09 1750.00 03-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1377.20 21-OCT-04:01
November 2010.79 01-NOV-09:09 1750.00 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1141.19 10-NOV-01:53
December 2010.79 01-DEC-10:09 1750.00 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1212.54 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   703.30  
Maximum of Months 2010.79   1750.00   2276.32   0.00 0.00 0.00 0.00 113.63   3370.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 2228.38 28-JAN-23:51
February 1295.83 01-FEB-10:09 1127.77 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1363.33 25-FEB-01:00
March 1295.83 01-MAR-10:09 1127.77 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 988.43 14-MAR-21:01
April 1295.83 03-APR-09:09 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1491.92 01-APR-19:00
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 723.31 26-MAY-02:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 30.57 30-JUN-15:00 714.27 25-JUN-06:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 80.32 29-JUL-20:00 438.81 04-JUL-17:20
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 11.49 11-AUG-16:00 559.23 30-AUG-01:00
September 1295.83 01-SEP-09:09 1013.59 28-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 479.91 04-SEP-14:00
October 1295.83 02-OCT-09:09 1127.77 03-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 904.50 21-OCT-04:01
November 1295.83 01-NOV-09:09 1127.77 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 750.92 10-NOV-01:53
December 1295.83 01-DEC-10:09 1127.77 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 796.12 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   438.81  
Maximum of Months 1295.83   1127.77   1466.95   0.00 0.00 0.00 0.00 80.32   2228.38  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1750.04 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 3324.32 28-JAN-23:51
February 2010.83 01-FEB-10:09 1750.04 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 2043.86 25-FEB-01:00
March 2010.83 01-MAR-10:09 1750.04 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 1688.41 12-MAR-14:57
April 2010.83 03-APR-09:09 1176.88 04-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 2388.56 01-APR-19:00
May 2010.83 01-MAY-09:09 1075.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1086.00 26-MAY-02:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 45.86 30-JUN-15:00 1043.48 25-JUN-06:00
July 2010.83 03-JUL-09:09 1075.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 113.63 21-JUL-16:00 678.72 04-JUL-16:43
August 2010.83 01-AUG-09:09 1075.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 17.23 11-AUG-16:00 849.15 30-AUG-01:00
September 2010.83 01-SEP-09:09 1632.01 28-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 689.09 04-SEP-14:00
October 2010.83 02-OCT-09:09 1750.04 03-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 1348.00 22-OCT-17:55
November 2010.83 01-NOV-09:09 1750.04 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1130.93 10-NOV-01:53
December 2010.83 01-DEC-10:09 1750.04 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1187.81 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   678.72  
Maximum of Months 2010.83   1750.04   2276.35   0.00 0.00 0.00 0.00 113.63   3324.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 2300.01 28-JAN-23:51
February 1295.83 01-FEB-10:09 1127.77 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 1416.28 25-FEB-01:00
March 1295.83 01-MAR-10:09 1127.77 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 1045.42 12-MAR-14:57
April 1295.83 03-APR-09:09 859.76 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 1870.87 01-APR-19:00
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 762.41 26-MAY-02:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 30.57 30-JUN-15:00 793.55 25-JUN-06:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 75.75 21-JUL-16:00 505.57 04-JUL-17:20
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 11.49 11-AUG-16:00 628.49 30-AUG-01:00
September 1295.83 01-SEP-09:09 1088.11 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 499.84 04-SEP-14:00
October 1295.83 02-OCT-09:09 1127.77 03-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 967.71 21-OCT-04:01
November 1295.83 01-NOV-09:09 1127.77 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 798.17 10-NOV-01:53
December 1295.83 01-DEC-10:09 1127.77 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 847.72 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.94   0.00 0.00 0.00 0.00 0.00   499.84  
Maximum of Months 1295.83   1127.77   1466.94   0.00 0.00 0.00 0.00 75.75   2300.01  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1750.00 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 7780.20 28-JAN-23:58
February 2010.79 01-FEB-10:09 1750.00 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 4611.47 25-FEB-01:00
March 2010.79 01-MAR-10:09 1750.00 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 3464.69 14-MAR-21:01
April 2010.79 03-APR-09:09 1195.98 04-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 4727.61 01-APR-18:53
May 2010.79 01-MAY-09:09 1075.02 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2332.83 26-MAY-02:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 104.82 30-JUN-15:00 2210.21 25-JUN-06:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 261.11 21-JUL-16:00 1693.65 04-JUL-16:53
August 2010.79 01-AUG-09:09 1075.02 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 37.66 11-AUG-16:00 1842.81 30-AUG-01:00
September 2010.79 01-SEP-09:09 1685.76 28-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1443.36 04-SEP-14:00
October 2010.79 02-OCT-09:09 1750.00 03-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3126.12 21-OCT-05:00
November 2010.79 01-NOV-09:09 1750.00 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2514.75 10-NOV-05:00
December 2010.79 01-DEC-10:09 1750.00 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2652.08 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   1443.36  
Maximum of Months 2010.79   1750.00   2276.32   0.00 0.00 0.00 0.00 261.11   7780.20  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 1127.77 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 5186.80 28-JAN-23:54
February 1239.33 01-FEB-08:09 1127.77 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3074.46 25-FEB-01:00
March 1239.33 01-MAR-08:09 1127.77 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 2311.98 14-MAR-21:01
April 1239.33 03-APR-07:10 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3183.77 01-APR-18:53
May 1239.33 01-MAY-07:10 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1572.24 26-MAY-02:00
June 1239.33 01-JUN-07:10 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 69.88 30-JUN-15:00 1463.90 25-JUN-06:00
July 1239.33 03-JUL-07:10 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 185.85 29-JUL-20:00 1149.88 04-JUL-16:53
August 1239.33 01-AUG-07:10 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 25.11 11-AUG-16:00 1224.36 30-AUG-01:00
September 1239.33 01-SEP-07:10 1017.84 28-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 992.25 04-SEP-14:00
October 1239.33 02-OCT-07:10 1127.77 03-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2084.08 21-OCT-04:53
November 1239.33 01-NOV-07:10 1127.77 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1689.16 10-NOV-05:07
December 1239.33 01-DEC-08:09 1127.77 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1768.07 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   992.25  
Maximum of Months 1239.33   1127.77   1466.95   0.00 0.00 0.00 0.00 185.85   5186.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1750.04 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 7780.18 28-JAN-23:58
February 2010.83 01-FEB-10:09 1750.04 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 4611.35 25-FEB-01:00
March 2010.83 01-MAR-10:09 1750.04 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 3926.66 12-MAR-14:53
April 2010.83 03-APR-09:09 1193.89 04-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5417.30 01-APR-18:53
May 2010.83 01-MAY-09:09 1075.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2387.80 26-MAY-02:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 104.82 30-JUN-15:00 2196.56 18-JUN-14:20
July 2010.83 03-JUL-09:09 1075.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 261.11 21-JUL-16:00 1758.33 04-JUL-16:53
August 2010.83 01-AUG-09:09 1075.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 37.65 11-AUG-16:10 1857.18 30-AUG-01:00
September 2010.83 01-SEP-09:09 1636.84 28-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1514.62 30-SEP-21:00
October 2010.83 02-OCT-09:09 1750.04 03-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3146.43 21-OCT-04:04
November 2010.83 01-NOV-09:09 1750.04 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2537.32 10-NOV-05:04
December 2010.83 01-DEC-10:09 1750.04 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2652.10 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   1514.62  
Maximum of Months 2010.83   1750.04   2276.35   0.00 0.00 0.00 0.00 261.11   7780.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 5186.79 28-JAN-23:57
February 1295.83 01-FEB-10:09 1127.77 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3074.39 25-FEB-01:00
March 1295.83 01-MAR-10:09 1127.77 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 2313.95 14-MAR-21:01
April 1295.83 03-APR-09:09 863.36 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 4016.98 01-APR-18:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1584.61 26-MAY-02:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 69.88 30-JUN-15:00 1483.99 24-JUN-21:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 174.07 21-JUL-16:00 1188.80 04-JUL-16:53
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 25.11 11-AUG-16:00 1245.85 30-AUG-01:00
September 1295.83 01-SEP-09:09 1089.09 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 984.73 04-SEP-14:00
October 1295.83 02-OCT-09:09 1127.77 03-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2100.18 21-OCT-04:04
November 1295.83 01-NOV-09:09 1127.77 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 1691.36 10-NOV-05:04
December 1295.83 01-DEC-10:09 1127.77 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 1768.04 28-DEC-02:55
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.94   0.00 0.00 0.00 0.00 0.00   984.73  
Maximum of Months 1295.83   1127.77   1466.94   0.00 0.00 0.00 0.00 174.07   5186.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1750.00 02-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 9455.41 28-JAN-23:51
February 2010.79 01-FEB-10:09 1750.00 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 5740.82 25-FEB-01:00
March 2010.79 01-MAR-10:09 1750.00 01-MAR-08:09 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 4297.38 14-MAR-21:01
April 2010.79 03-APR-09:09 1195.68 04-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 5469.22 01-APR-18:53
May 2010.79 01-MAY-09:09 1075.02 01-MAY-07:10 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2686.67 27-MAY-04:05
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 126.76 30-JUN-15:00 2495.44 24-JUN-21:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 317.51 21-JUL-16:00 1979.95 04-JUL-16:53
August 2010.79 01-AUG-09:09 1075.02 01-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 43.35 11-AUG-16:00 2104.58 30-AUG-01:00
September 2010.79 01-SEP-09:09 1685.83 28-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1700.68 30-SEP-04:52
October 2010.79 02-OCT-09:09 1750.00 03-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3897.29 21-OCT-04:50
November 2010.79 01-NOV-09:09 1750.00 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3131.84 10-NOV-05:00
December 2010.79 01-DEC-10:09 1750.00 01-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3301.32 28-DEC-03:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 0.00   1700.68  
Maximum of Months 2010.79   1750.00   2276.32   0.00 0.00 0.00 0.00 317.51   9455.41  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-08:09 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 6378.44 28-JAN-23:51
February 1295.83 01-FEB-10:09 1127.77 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3827.27 25-FEB-01:00
March 1295.83 01-MAR-10:09 1127.77 01-MAR-08:09 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 2867.64 14-MAR-21:01
April 1295.83 03-APR-09:09 692.79 03-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 3681.37 01-APR-18:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1811.88 26-MAY-02:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 84.51 30-JUN-15:00 1656.69 24-JUN-21:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 211.67 21-JUL-16:00 1348.75 04-JUL-16:53
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 28.90 11-AUG-16:00 1410.03 30-AUG-01:00
September 1295.83 01-SEP-09:09 1018.19 28-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1133.88 30-SEP-04:52
October 1295.83 02-OCT-09:09 1127.77 03-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2598.25 21-OCT-04:45
November 1295.83 01-NOV-09:09 1127.77 01-NOV-07:10 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2087.80 10-NOV-05:00
December 1295.83 01-DEC-10:09 1127.77 01-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2200.88 28-DEC-03:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 0.00   1133.88  
Maximum of Months 1295.83   1127.77   1466.95   0.00 0.00 0.00 0.00 211.67   6378.44  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1750.04 02-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 9578.23 28-JAN-23:51
February 2010.83 01-FEB-10:09 1750.04 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 5740.96 25-FEB-01:00
March 2010.83 01-MAR-10:09 1750.04 01-MAR-08:09 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 4316.72 14-MAR-21:01
April 2010.83 03-APR-09:09 1193.59 04-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 6307.07 01-APR-18:53
May 2010.83 01-MAY-09:09 1075.05 01-MAY-07:10 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2753.49 26-MAY-02:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 126.76 30-JUN-15:00 2826.37 18-JUN-14:00
July 2010.83 03-JUL-09:09 1075.05 03-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 317.51 21-JUL-16:00 2062.13 04-JUL-16:53
August 2010.83 01-AUG-09:09 1075.05 01-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 43.33 11-AUG-16:10 2142.18 30-AUG-01:00
September 2010.83 01-SEP-09:09 1637.04 28-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1729.66 30-SEP-21:00
October 2010.83 02-OCT-09:09 1750.04 03-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 3897.31 21-OCT-04:45
November 2010.83 01-NOV-09:09 1750.04 01-NOV-07:10 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 3131.62 10-NOV-05:00
December 2010.83 01-DEC-10:09 1750.04 01-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 3301.44 28-DEC-03:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 0.00   1729.66  
Maximum of Months 2010.83   1750.04   2276.35   0.00 0.00 0.00 0.00 317.51   9578.23  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 1127.77 02-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 6383.32 28-JAN-23:51
February 1295.83 01-FEB-10:09 1127.77 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 3827.16 25-FEB-01:00
March 1295.83 01-MAR-10:09 1127.77 01-MAR-08:09 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 2870.94 14-MAR-21:01
April 1295.83 03-APR-09:09 863.42 03-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 4708.03 01-APR-18:53
May 1295.83 01-MAY-09:09 692.79 01-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 1825.01 26-MAY-02:00
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 84.51 30-JUN-15:00 1703.18 24-JUN-21:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 211.67 21-JUL-16:00 1397.92 04-JUL-16:53
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 28.90 11-AUG-16:00 1438.77 30-AUG-01:00
September 1295.83 01-SEP-09:09 1089.14 29-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1136.39 30-SEP-04:52
October 1295.83 02-OCT-09:09 1127.77 03-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2598.23 21-OCT-04:47
November 1295.83 01-NOV-09:09 1127.77 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2087.62 10-NOV-05:00
December 1295.83 01-DEC-10:09 1127.77 01-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2200.96 28-DEC-03:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.94   0.00 0.00 0.00 0.00 0.00   1136.39  
Maximum of Months 1295.83   1127.77   1466.94   0.00 0.00 0.00 0.00 211.67   6383.32  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4375.82 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4375.82 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4375.82 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4375.82 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4375.82 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4375.82 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4375.82 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4375.82 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4375.82 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4375.82 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4375.82 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4375.82 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4375.82   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4375.82   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 7321.92 28-JAN-23:51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 4402.13 25-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 3176.79 25-MAR-04:04
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 4918.49 01-APR-18:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 2273.00 26-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 76.29 30-JUN-15:00 2241.61 25-JUN-06:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 198.86 29-JUL-17:02 1465.28 04-JUL-16:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 20.25 11-AUG-16:00 1791.05 30-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 1419.17 04-SEP-14:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 2942.71 21-OCT-04:01
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 2440.77 10-NOV-01:53
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 2574.25 28-DEC-02:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   1419.17  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 198.86   7321.92  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 12544.94 28-JAN-23:51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 7591.93 25-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 5439.69 25-MAR-04:50
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 8318.18 01-APR-18:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 4000.17 26-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 134.67 30-JUN-15:00 3859.60 25-JUN-06:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 374.53 29-JUL-17:02 2595.71 04-JUL-16:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 34.40 11-AUG-16:00 3145.96 30-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2375.18 04-SEP-14:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 5017.88 21-OCT-04:20
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4198.68 10-NOV-01:53
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4355.48 28-DEC-02:55
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2375.18  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 374.53   12544.94  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 13451.86 28-JAN-23:51
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 8391.31 25-FEB-01:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 6097.24 14-MAR-21:01
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 9088.06 01-APR-18:53
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-MAY-00:10 4192.15 26-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 130.14 30-JUN-15:00 3919.51 24-JUN-21:00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 361.06 21-JUL-16:00 3100.99 04-JUL-16:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.52 11-AUG-18:00 3252.71 30-AUG-01:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 2430.13 04-SEP-14:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 5268.38 21-OCT-04:50
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 4479.97 10-NOV-02:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 4774.84 28-DEC-03:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00   2430.13  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 361.06   13451.86  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 94124.52 26-JAN-06:01 14361.80 13795.64 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
February 95882.19 13-FEB-06:01 14361.80 13795.64 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
March 98860.45 20-MAR-04:01 0.00 12071.18 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
April 102007.48 24-APR-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
May 102299.99 30-MAY-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
June 104265.99 19-JUN-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 105869.98 10-JUL-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 104268.17 28-AUG-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
September 103592.66 18-SEP-03:02 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
October 104609.14 10-OCT-03:01 0.00 6897.82 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
November 98961.78 13-NOV-05:01 0.00 13795.64 107660.35 0.00 0.00 0.00 0.00 0.00 0.00
December 99307.58 26-DEC-05:01 0.00 12071.18 94202.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 94124.52   0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 105869.98   14361.80 13795.64 107660.35 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 24643.00 25-JAN-14:10 16014.58 13937.56 18128.59 0.00 0.00 0.00 0.00 0.00 0.00
February 78760.90 10-FEB-06:02 12897.91 12389.45 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
March 82317.44 23-MAR-04:01 0.00 10840.77 56400.06 0.00 0.00 0.00 0.00 0.00 0.00
April 86320.96 24-APR-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
May 85949.52 01-MAY-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
June 88762.41 26-JUN-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
July 87536.49 03-JUL-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
August 87278.43 07-AUG-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
September 90792.72 05-SEP-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
October 85621.28 10-OCT-04:01 0.00 10840.77 56400.06 0.00 0.00 0.00 0.00 0.00 0.00
November 75746.72 02-NOV-05:01 12897.91 12389.45 64457.21 0.00 0.00 0.00 0.00 0.00 0.00
December 31179.24 26-DEC-17:00 15316.26 13937.56 18128.59 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 24643.00   0.00 3097.36 18128.59 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 90792.72   16014.58 13937.56 64457.21 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 20871.33 19-JAN-14:50 16014.58 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 21997.11 03-FEB-16:20 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 46076.08 31-MAR-15:07 91897.59 83625.36 108771.12 0.00 0.00 0.00 0.00 0.00 0.00
April 76599.44 21-APR-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 76877.62 02-MAY-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
June 78451.56 26-JUN-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 80023.84 24-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 81847.12 14-AUG-03:02 0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
September 77007.96 13-SEP-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 69659.00 05-OCT-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 17379.53 03-NOV-16:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
December 16417.23 22-DEC-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16417.23   0.00 3097.36 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 81847.12   91897.59 83625.36 108771.12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 14227.56 20-JAN-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
February 16460.27 09-FEB-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
March 18459.64 22-MAR-16:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
April 34218.95 21-APR-16:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
May 69601.81 11-MAY-05:03 6448.95 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
June 76136.69 15-JUN-05:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 79156.88 24-JUL-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 76626.94 14-AUG-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
September 31795.82 01-SEP-16:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
October 18923.55 04-OCT-16:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
November 14529.20 02-NOV-16:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
December 13356.20 21-DEC-17:00 15316.26 13937.56 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 13356.20   0.00 3871.70 18128.52 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 79156.88   15316.26 13937.56 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1609.20 20-JAN-14:20 2010.79 1692.98 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
February 2442.57 10-FEB-06:02 1619.46 1555.62 8093.57 0.00 0.00 0.00 0.00 0.00 158.08
March 2827.52 22-MAR-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
April 5445.95 28-APR-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
May 13617.36 31-MAY-04:33 0.00 477.81 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
June 14449.63 12-JUN-03:53 0.00 179.18 3035.09 0.00 0.00 0.00 0.00 0.00 288.16
July 15689.66 11-JUL-04:54 0.00 597.26 5058.48 0.00 0.00 0.00 0.00 0.00 195.79
August 12640.01 02-AUG-05:02 1012.16 597.26 5058.48 0.00 0.00 0.00 0.00 0.00 30.51
September 5279.53 01-SEP-13:40 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 38.03
October 3058.16 04-OCT-14:40 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 127.01
November 2100.50 02-NOV-05:02 1619.46 1555.62 8093.57 0.00 0.00 0.00 0.00 0.00 77.61
December 1673.33 26-DEC-12:00 1923.11 1655.42 2276.32 0.00 0.00 0.00 0.00 0.00 259.87
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1609.20   0.00 179.18 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 15689.66   2010.79 1692.98 8093.57 0.00 0.00 0.00 0.00 0.00 288.16



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1669.27 23-JAN-06:03 913.19 877.19 4563.83 0.00 0.00 0.00 0.00 0.00 0.00
February 2529.17 10-FEB-06:02 1043.64 1002.50 5215.81 0.00 0.00 0.00 0.00 0.00 105.77
March 6815.39 27-MAR-09:35 2591.66 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 146.70
April 10252.17 22-APR-09:20 409.21 230.93 814.97 0.00 0.00 0.00 0.00 0.00 35.05
May 23171.19 14-MAY-09:31 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 0.00 209.79
June 21191.53 04-JUN-09:12 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 150.32
July 21840.99 23-JUL-10:01 521.82 307.92 3911.86 0.00 0.00 0.00 0.00 0.00 50.93
August 14206.50 10-AUG-08:50 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 14.93
September 17147.79 10-SEP-10:13 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 211.73
October 6425.62 03-OCT-09:45 2591.66 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 79.75
November 2175.86 02-NOV-05:02 1043.64 1002.50 5215.81 0.00 0.00 0.00 0.00 0.00 51.90
December 1641.37 18-DEC-06:04 913.19 877.19 4563.83 0.00 0.00 0.00 0.00 0.00 63.01
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1641.37   260.91 153.96 814.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23171.19   2591.66 1385.57 5215.81 0.00 0.00 0.00 0.00 0.00 211.73



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3372.29 25-JAN-13:20 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 123.05
February 10170.93 15-FEB-13:30 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
March 16117.30 31-MAR-13:30 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 183.23
April 27994.73 23-APR-11:23 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 474.90
May 34056.04 14-MAY-12:12 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 251.54
June 33385.58 04-JUN-14:32 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 259.47
July 36137.48 23-JUL-12:41 809.75 477.82 6070.27 0.00 0.00 0.00 0.00 0.00 51.29
August 33084.31 27-AUG-13:12 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 121.63
September 20856.95 10-SEP-11:32 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 243.74
October 16918.03 03-OCT-13:30 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 130.74
November 7089.53 08-NOV-13:30 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 134.39
December 2550.82 27-DEC-12:40 1058.33 1431.32 2023.42 0.00 0.00 0.00 0.00 0.00 138.45
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2550.82   404.87 238.91 2023.42 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 36137.48   2010.83 1431.32 6070.27 0.00 0.00 0.00 0.00 0.00 474.90



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2031.01 23-JAN-14:20 1295.83 862.46 1466.94 0.00 0.00 0.00 0.00 0.00 73.94
February 3323.40 09-FEB-06:01 913.19 877.19 4563.80 0.00 0.00 0.00 0.00 0.00 58.18
March 7658.61 27-MAR-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 167.52
April 23643.04 22-APR-17:04 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 449.74
May 24872.04 29-MAY-16:02 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 246.64
June 25128.98 11-JUN-16:42 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 297.87
July 24505.82 23-JUL-15:21 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 12.96
August 25483.43 27-AUG-17:12 0.00 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 239.79
September 12996.98 02-SEP-17:08 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 118.20
October 6319.05 03-OCT-14:50 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 64.58
November 3120.16 02-NOV-05:01 1043.64 1002.50 5215.77 0.00 0.00 0.00 0.00 0.00 54.04
December 2493.23 26-DEC-05:01 0.00 877.19 4563.80 0.00 0.00 0.00 0.00 0.00 369.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2031.01   0.00 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 12.96
Maximum of Months 25483.43   1295.83 1002.50 5215.77 0.00 0.00 0.00 0.00 0.00 449.74



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1440.56 07-JAN-17:02 607.30 583.36 4552.64 0.00 0.00 0.00 0.00 0.00 433.56
February 1462.23 11-FEB-17:02 506.08 486.13 3793.86 0.00 0.00 0.00 0.00 0.00 160.54
March 2059.14 21-MAR-14:30 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 295.94
April 3485.61 28-APR-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
May 11666.01 31-MAY-05:03 607.30 358.36 3035.09 0.00 0.00 0.00 0.00 0.00 18.31
June 13272.27 19-JUN-05:03 1214.60 716.71 6070.18 0.00 0.00 0.00 0.00 0.00 106.34
July 13326.37 11-JUL-05:03 1214.60 716.71 6070.18 0.00 0.00 0.00 0.00 0.00 107.31
August 9001.86 10-AUG-05:02 1012.16 597.26 5058.48 0.00 0.00 0.00 0.00 0.00 168.82
September 3524.14 01-SEP-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 80.26
October 2069.54 04-OCT-16:00 1923.11 1201.17 2276.32 0.00 0.00 0.00 0.00 0.00 143.49
November 1439.48 18-NOV-17:02 607.30 583.36 4552.64 0.00 0.00 0.00 0.00 0.00 0.00
December 1446.21 23-DEC-17:02 607.30 583.36 4552.64 0.00 0.00 0.00 0.00 0.00 304.06
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1439.48   506.08 358.36 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 13326.37   2010.79 1201.17 6070.18 0.00 0.00 0.00 0.00 0.00 433.56



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1793.90 20-JAN-06:04 1043.64 1002.50 5215.81 0.00 0.00 0.00 0.00 0.00 229.74
February 1825.85 15-FEB-11:30 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 83.52
March 5050.79 22-MAR-09:50 0.00 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 0.00
April 9837.28 22-APR-09:30 0.00 230.93 814.97 0.00 0.00 0.00 0.00 0.00 76.90
May 24366.37 21-MAY-09:01 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 0.00 1085.72
June 22589.95 04-JUN-09:22 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 433.18
July 23087.55 23-JUL-10:12 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 0.00 92.63
August 14955.48 10-AUG-09:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 41.65
September 16344.79 10-SEP-10:02 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 496.49
October 4667.05 03-OCT-10:25 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 172.82
November 1807.42 14-NOV-06:04 913.19 877.19 4563.83 0.00 0.00 0.00 0.00 0.00 171.06
December 1766.67 20-DEC-06:04 1043.64 1002.50 5215.81 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1766.67   0.00 153.96 814.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 24366.37   2478.65 1385.57 5215.81 0.00 0.00 0.00 0.00 0.00 1085.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 3147.86 25-JAN-13:40 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 139.74
February 14195.55 15-FEB-13:40 5769.46 3225.15 6829.06 0.00 0.00 0.00 0.00 0.00 0.00
March 28402.29 31-MAR-15:07 11538.91 6450.29 13658.12 0.00 0.00 0.00 0.00 0.00 385.93
April 26699.36 09-APR-14:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 1312.67
May 35881.63 21-MAY-13:02 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 1358.72
June 35382.46 04-JUN-14:42 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 638.43
July 35654.21 23-JUL-13:32 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 101.80
August 35089.74 27-AUG-13:12 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 293.81
September 33866.59 10-SEP-11:22 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 641.07
October 16357.60 03-OCT-13:30 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 309.17
November 4755.66 08-NOV-13:50 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 349.10
December 2702.74 20-DEC-06:04 1619.50 1555.65 8093.70 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2702.74   404.87 238.91 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 35881.63   11538.91 6450.29 13658.12 0.00 0.00 0.00 0.00 0.00 1358.72



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1833.09 23-JAN-06:04 913.19 877.19 4563.80 0.00 0.00 0.00 0.00 0.00 0.00
February 1831.52 09-FEB-06:03 913.19 877.19 4563.80 0.00 0.00 0.00 0.00 0.00 127.41
March 3399.01 31-MAR-15:07 7435.95 4156.72 8801.62 0.00 0.00 0.00 0.00 0.00 247.50
April 14442.93 22-APR-17:04 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 1046.06
May 23343.45 21-MAY-18:22 0.00 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 405.57
June 22589.29 04-JUN-19:22 0.00 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 494.91
July 17728.66 09-JUL-19:33 0.00 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 309.42
August 22394.23 27-AUG-17:52 0.00 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 410.99
September 8709.23 02-SEP-17:10 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 278.62
October 2608.81 03-OCT-15:20 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 138.22
November 1855.69 14-NOV-06:04 913.19 877.19 4563.80 0.00 0.00 0.00 0.00 0.00 171.20
December 1811.61 20-DEC-06:04 1043.64 1002.50 5215.77 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1811.61   0.00 153.96 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23343.45   7435.95 4156.72 8801.62 0.00 0.00 0.00 0.00 0.00 1046.06



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1816.25 07-JAN-17:02 607.30 583.36 4552.64 0.00 0.00 0.00 0.00 0.00 538.02
February 1999.27 09-FEB-06:06 1417.03 1361.17 7081.88 0.00 0.00 0.00 0.00 0.00 236.89
March 2164.85 22-MAR-16:00 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
April 2939.05 20-APR-14:10 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 77.91
May 9798.32 31-MAY-05:03 607.30 358.36 3035.09 0.00 0.00 0.00 0.00 0.00 22.75
June 15724.23 29-JUN-05:02 1214.60 716.71 6070.18 0.00 0.00 0.00 0.00 0.00 136.96
July 16743.21 11-JUL-05:03 1214.60 716.71 6070.18 0.00 0.00 0.00 0.00 0.00 126.66
August 6835.93 02-AUG-14:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 15.37
September 2941.90 01-SEP-16:00 1923.11 1075.02 2276.32 0.00 0.00 0.00 0.00 0.00 110.71
October 2210.11 04-OCT-16:00 1923.11 1200.96 2276.32 0.00 0.00 0.00 0.00 0.00 162.32
November 1809.89 18-NOV-17:02 607.30 583.36 4552.64 0.00 0.00 0.00 0.00 0.00 0.00
December 1824.33 23-DEC-17:02 607.30 583.36 4552.64 0.00 0.00 0.00 0.00 0.00 377.32
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1809.89   607.30 358.36 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16743.21   2010.79 1361.17 7081.88 0.00 0.00 0.00 0.00 0.00 538.02



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1525.41 07-JAN-17:02 391.37 375.94 2933.89 0.00 0.00 0.00 0.00 0.00 358.22
February 1754.47 09-FEB-06:04 913.19 877.19 4563.83 0.00 0.00 0.00 0.00 0.00 158.97
March 2712.38 22-MAR-10:40 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 111.79
April 8130.48 22-APR-09:30 409.21 230.93 814.97 0.00 0.00 0.00 0.00 0.00 96.17
May 23251.73 21-MAY-09:01 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 0.00 1303.42
June 17685.84 09-JUN-05:02 782.73 461.88 3911.86 0.00 0.00 0.00 0.00 0.00 169.41
July 23557.55 23-JUL-11:51 456.59 269.43 3422.87 0.00 0.00 0.00 0.00 0.00 0.00
August 14570.33 10-AUG-09:10 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 57.94
September 6389.96 10-SEP-09:28 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 650.71
October 2502.01 03-OCT-10:25 2478.65 1385.57 2933.89 0.00 0.00 0.00 0.00 0.00 211.72
November 1523.08 18-NOV-17:02 391.37 375.94 2933.89 0.00 0.00 0.00 0.00 0.00 0.00
December 1533.11 23-DEC-17:02 391.37 375.94 2933.89 0.00 0.00 0.00 0.00 0.00 251.17
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1523.08   326.14 192.45 814.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23557.55   2478.65 1385.57 4563.83 0.00 0.00 0.00 0.00 0.00 1303.42



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 2763.53 18-JAN-06:04 1821.93 1750.11 9105.41 0.00 0.00 0.00 0.00 0.00 107.28
February 5664.53 15-FEB-14:00 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
March 13209.28 31-MAR-14:20 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 491.79
April 22394.84 20-APR-14:00 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 77.36
May 36053.65 14-MAY-13:42 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 1184.43
June 34912.07 18-JUN-12:42 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 1002.18
July 40417.04 23-JUL-12:31 809.75 477.82 6070.27 0.00 0.00 0.00 0.00 0.00 139.43
August 36045.24 27-AUG-13:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 446.73
September 17264.34 08-SEP-14:30 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 184.02
October 13622.25 03-OCT-13:40 2010.83 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 372.59
November 3572.22 08-NOV-13:50 1923.15 1075.05 2276.35 0.00 0.00 0.00 0.00 0.00 421.59
December 2438.00 23-DEC-17:02 607.31 583.37 4552.71 0.00 0.00 0.00 0.00 0.00 376.92
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 2438.00   506.09 298.64 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 40417.04   2010.83 1750.11 9105.41 0.00 0.00 0.00 0.00 0.00 1184.43



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 1631.60 07-JAN-17:02 391.37 375.94 2933.87 0.00 0.00 0.00 0.00 0.00 358.55
February 1911.38 08-FEB-06:04 1043.64 1002.50 5215.77 0.00 0.00 0.00 0.00 0.00 255.96
March 2495.24 22-MAR-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
April 12546.70 22-APR-17:06 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 1309.30
May 23685.57 21-MAY-17:42 0.00 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 521.19
June 22138.75 10-JUN-17:04 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 193.34
July 18397.07 23-JUL-16:32 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 53.24
August 21924.42 27-AUG-17:52 0.00 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 515.32
September 6669.08 08-SEP-16:00 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 124.58
October 2441.60 03-OCT-15:20 1239.33 692.79 1466.94 0.00 0.00 0.00 0.00 0.00 161.42
November 1887.85 02-NOV-05:04 1043.64 1002.50 5215.77 0.00 0.00 0.00 0.00 0.00 151.70
December 1851.53 07-DEC-06:04 1174.10 1127.81 5867.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 1631.60   0.00 192.45 1466.94 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 23685.57   1239.33 1127.81 5867.75 0.00 0.00 0.00 0.00 0.00 1309.30



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5236.55 12-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1784.00
February 5552.44 25-FEB-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3149.81
March 4247.93 01-MAR-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 4770.04 21-APR-16:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.97
May 5981.29 31-MAY-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 49.78
June 9374.29 05-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 215.36
July 12320.47 24-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 81.63
August 8552.30 07-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 155.16
September 7141.07 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124.90
October 4180.73 05-OCT-05:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 139.83
November 4417.05 27-NOV-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 4566.18 15-DEC-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4180.73   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12320.47   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 3149.81



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8174.01 28-JAN-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5127.47
February 7540.05 26-FEB-03:51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5916.28
March 7653.76 25-MAR-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 5419.72
April 8223.11 03-APR-03:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4112.62
May 4419.28 12-MAY-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 280.72
June 6292.36 30-JUN-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 109.68 0.00
July 6648.40 24-JUL-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 83.87
August 5853.50 14-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 386.35
September 5748.03 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 532.14
October 8350.53 23-OCT-03:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2254.00
November 7893.25 10-NOV-04:01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2086.40
December 8339.58 09-DEC-04:11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 4419.28   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8350.53   0.00 0.00 0.00 0.00 0.00 0.00 0.00 109.68 5916.28



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2678.76
February 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2267.80
March 563.57 22-MAR-16:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 6163.08 20-APR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 339.97
May 12398.42 31-MAY-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 159.56
June 14052.04 29-JUN-14:50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.73 0.00
July 14558.24 21-JUL-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.80 0.00
August 11806.64 11-AUG-15:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18.13
September 3703.53 07-SEP-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 105.71
October 560.82 04-OCT-16:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 215.25
November 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2492.46
December 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 0.00   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14558.24   0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.80 2678.76



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1056.71 23-JAN-15:20 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3517.32 15-FEB-16:20 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 6703.89 31-MAR-23:55 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
April 8506.34 20-APR-18:50 23.38 135.03 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3452.93 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5345.54 30-JUN-23:15 0.00 45.01 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
July 7258.76 31-JUL-23:40 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 8357.92 27-AUG-18:45 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 2893.27 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4423.98 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5465.05 08-NOV-15:55 444.28 810.21 11691.63 0.00 0.00 0.00 0.00 0.00 0.00
December 6950.32 26-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1056.71   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8506.34   444.28 810.21 15588.84 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 644.35 12-JAN-08:65 444.28 810.21 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
February 2883.86 16-FEB-16:10 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 5720.19 31-MAR-23:20 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 8092.32 20-APR-18:50 23.38 135.03 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3222.95 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5133.57 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 7024.50 31-JUL-24:00 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7824.57 27-AUG-18:45 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 2116.25 30-SEP-23:50 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 3399.89 03-OCT-16:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 4648.97 08-NOV-15:50 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 5858.41 21-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 644.35   0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8092.32   444.28 810.21 23383.27 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 628.10 12-JAN-08:15 444.28 810.21 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
February 2463.04 09-FEB-16:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
March 4985.25 31-MAR-17:30 23.38 135.03 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
April 8069.81 20-APR-18:50 23.38 135.03 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
May 3177.53 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5094.26 30-JUN-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
July 6986.60 31-JUL-23:40 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
August 7822.50 27-AUG-18:45 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 1825.84 08-SEP-17:30 23.38 135.03 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
October 3131.57 03-OCT-16:00 222.14 405.10 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
November 4190.92 08-NOV-15:50 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 5375.43 21-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 628.10   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 8069.81   444.28 810.21 15588.84 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 88891.74 25-JAN-17:00 4808.68 4375.82 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 180431.96 09-FEB-17:00 4808.68 4375.82 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 356675.03 31-MAR-24:00 0.00 486.22 759265.04 0.00 0.00 0.00 0.00 0.00 0.00
April 366334.23 21-APR-16:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
May 175284.87 31-MAY-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267091.02 30-JUN-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
July 359781.43 31-JUL-23:57 0.00 729.33 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 368008.18 28-AUG-16:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
September 174493.31 30-SEP-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 265431.36 31-OCT-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 273399.54 08-NOV-17:00 4808.68 4375.82 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 364639.71 26-DEC-17:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 88891.74   0.00 243.11 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 368008.18   4808.68 4375.82 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.159010E+13 1008152.81 27-JAN-08:20 0.130709E+13 2411667.25 30-JAN-07:19
February 0.178293E+13 1158500.45 14-FEB-08:20 0.830045E+12 2658842.51 27-FEB-07:19
March 0.239015E+13 1309761.77 30-MAR-13:50 0.487433E+12 1980861.11 01-MAR-07:19
April 0.266770E+13 1512319.20 21-APR-15:39 0.171015E+12 987208.65 03-APR-05:10
May 0.164781E+13 1247197.64 31-MAY-15:39 0.787284E+11 346595.39 27-MAY-06:10
June 0.215152E+13 1503171.30 29-JUN-15:39 0.733213E+11 87001.21 01-JUN-11:50
July 0.260573E+13 1651622.03 11-JUL-15:50 0.689825E+11 85761.52 03-JUL-11:20
August 0.298747E+13 1805522.45 11-AUG-15:39 0.741747E+11 397914.80 31-AUG-06:10
September 0.151269E+13 1064142.40 07-SEP-15:30 0.966118E+11 549948.98 25-SEP-06:10
October 0.196498E+13 1161533.05 13-OCT-07:19 0.347491E+12 1278268.39 23-OCT-06:10
November 0.231448E+13 1307427.99 24-NOV-08:00 0.102410E+13 2286383.62 27-NOV-07:19
December 0.276173E+13 1454288.96 29-DEC-08:20 0.140552E+13 2126830.65 15-DEC-07:40
             
Annual Sum or Average 0.263773E+14     0.596452E+13    
Minimum of Months 0.151269E+13 1008152.81   0.689825E+11 85761.52  
Maximum of Months 0.298747E+13 1805522.45   0.140552E+13 2658842.51  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.244816E+12 0.686941E+11 0.811612E+12 0.162557E+12 0.175831E+12 0.199840E+11 0.00 0.797074E+11 0.484481E+10 0.136289E+11 0.842901E+10 0.00 0.00
February 0.214731E+12 0.495000E+11 0.102011E+13 0.146829E+12 0.156923E+12 0.222584E+11 0.00 0.136736E+12 0.858457E+10 0.196255E+11 0.763867E+10 0.00 0.00
March 0.247672E+12 0.405986E+11 0.146267E+13 0.162740E+12 0.173182E+12 0.269745E+11 0.00 0.223339E+12 0.156022E+11 0.286055E+11 0.876858E+10 0.00 0.00
April 0.218158E+12 0.255188E+11 0.170311E+13 0.157288E+12 0.180454E+12 0.177737E+11 0.00 0.282650E+12 0.495579E+11 0.291282E+11 0.405756E+10 0.00 0.00
May 0.234490E+12 0.148908E+11 0.820521E+12 0.162644E+12 0.216658E+12 0.258253E+11 0.00 0.116223E+12 0.458190E+11 0.101517E+11 0.582051E+09 0.00 0.00
June 0.232754E+12 0.705245E+10 0.110677E+13 0.157465E+12 0.243366E+12 0.473898E+11 0.00 0.239935E+12 0.106891E+12 0.937559E+10 0.517907E+09 0.00 0.00
July 0.218234E+12 0.104920E+11 0.143888E+13 0.162465E+12 0.241998E+12 0.541059E+11 0.00 0.344630E+12 0.124534E+12 0.959993E+10 0.796654E+09 0.00 0.00
August 0.243967E+12 0.209997E+11 0.177780E+13 0.162739E+12 0.229973E+12 0.413822E+11 0.00 0.370557E+12 0.120783E+12 0.188907E+11 0.377398E+09 0.00 0.00
September 0.219960E+12 0.333205E+11 0.784732E+12 0.157287E+12 0.174428E+12 0.139916E+11 0.00 0.945087E+11 0.220667E+11 0.941292E+10 0.298511E+10 0.00 0.00
October 0.233265E+12 0.486775E+11 0.112899E+13 0.162552E+12 0.167960E+12 0.222198E+11 0.00 0.159057E+12 0.169278E+11 0.185607E+11 0.676410E+10 0.00 0.00
November 0.238640E+12 0.612129E+11 0.140306E+13 0.157367E+12 0.167391E+12 0.277863E+11 0.00 0.211928E+12 0.116791E+11 0.272439E+11 0.817401E+10 0.00 0.00
December 0.239819E+12 0.744260E+11 0.175516E+13 0.162474E+12 0.174841E+12 0.177546E+11 0.00 0.279427E+12 0.148699E+11 0.346292E+11 0.833296E+10 0.00 0.00
                           
Annual Sum or Average 0.278651E+13 0.455383E+12 0.152134E+14 0.191441E+13 0.230301E+13 0.337446E+12 0.00 0.253870E+13 0.542160E+12 0.228853E+12 0.574240E+11 0.00 0.00
Minimum of Months 0.214731E+12 0.705245E+10 0.784732E+12 0.146829E+12 0.156923E+12 0.139916E+11 0.00 0.797074E+11 0.484481E+10 0.937559E+10 0.377398E+09 0.00 0.00
Maximum of Months 0.247672E+12 0.744260E+11 0.177780E+13 0.162740E+12 0.243366E+12 0.541059E+11 0.00 0.370557E+12 0.124534E+12 0.346292E+11 0.876858E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.123209E+13 0.00 0.750066E+11 0.00 0.00
February 0.00 0.00 0.761994E+12 0.00 0.680516E+11 0.00 0.00
March 0.00 0.00 0.408418E+12 0.00 0.790144E+11 0.00 0.00
April 0.00 0.00 0.983827E+11 0.00 0.726327E+11 0.00 0.00
May 0.00 0.00 0.216357E+10 0.00 0.765648E+11 0.00 0.00
June 0.00 0.00 2292051.12 0.00 0.733190E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.689825E+11 0.00 0.00
August 0.00 0.00 0.161305E+10 0.00 0.725617E+11 0.00 0.00
September 0.00 0.00 0.299748E+11 0.00 0.666370E+11 0.00 0.00
October 0.00 0.00 0.277683E+12 0.00 0.698079E+11 0.00 0.00
November 0.00 0.00 0.953931E+12 0.00 0.701721E+11 0.00 0.00
December 0.00 0.00 0.133282E+13 0.00 0.726998E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.509907E+13 0.00 0.865450E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.666370E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.133282E+13 0.00 0.790144E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 261074.09 02-JAN-08:09 37611.08 01-JAN-06:10 439129.89 02-JAN-08:09 117204.73 02-JAN-08:20 111431.74 02-JAN-06:19 31172.41 09-JAN-05:10 0.00 01-JAN-00:10
February 261074.09 01-FEB-08:09 37611.08 01-FEB-06:10 557421.28 01-FEB-08:09 117204.73 01-FEB-08:20 103785.56 27-FEB-06:10 31055.92 21-FEB-07:19 0.00 01-FEB-00:10
March 261074.09 01-MAR-08:09 37611.08 01-MAR-06:10 675712.68 01-MAR-08:09 117204.73 01-MAR-08:20 221567.80 30-MAR-13:50 30949.14 06-MAR-07:30 0.00 01-MAR-00:10
April 239237.72 04-APR-07:10 37611.08 01-APR-05:10 794004.08 03-APR-07:10 117192.29 04-APR-07:19 193522.68 21-APR-15:39 30939.44 01-APR-05:10 0.00 01-APR-00:10
May 234435.00 01-MAY-07:10 37611.08 01-MAY-21:10 439129.89 01-MAY-07:10 117189.56 01-MAY-07:19 216245.86 31-MAY-14:50 46958.12 31-MAY-15:39 0.00 01-MAY-00:10
June 234435.00 01-JUN-07:10 37611.08 01-JUN-22:49 557421.28 01-JUN-07:10 117189.56 01-JUN-07:19 246110.38 30-JUN-12:09 50287.26 21-JUN-14:00 0.00 01-JUN-00:10
July 234435.00 03-JUL-07:10 37611.08 11-JUL-22:00 675712.68 03-JUL-07:10 117189.56 03-JUL-07:19 257925.20 12-JUL-12:09 51051.51 06-JUL-14:50 0.00 01-JUL-00:10
August 234435.00 01-AUG-07:10 37611.08 01-AUG-21:00 794004.08 01-AUG-07:10 117189.56 01-AUG-07:19 250890.29 10-AUG-15:00 51515.43 11-AUG-15:39 0.00 01-AUG-00:10
September 257148.71 28-SEP-07:10 37611.08 01-SEP-05:10 439129.89 01-SEP-07:10 117202.49 28-SEP-07:19 153711.81 08-SEP-15:30 30951.41 07-SEP-15:00 0.00 01-SEP-00:10
October 261074.09 03-OCT-07:10 37611.08 01-OCT-05:10 557421.28 02-OCT-07:10 117204.73 03-OCT-07:19 113923.14 03-OCT-13:39 31183.29 30-OCT-05:10 0.00 01-OCT-00:10
November 261074.09 01-NOV-07:10 37611.08 01-NOV-05:10 675712.68 01-NOV-07:10 117204.73 01-NOV-07:19 99867.82 27-NOV-05:10 31385.75 27-NOV-06:10 0.00 01-NOV-00:10
December 261074.09 01-DEC-08:09 37611.08 01-DEC-06:10 794004.08 01-DEC-08:09 117204.73 01-DEC-08:20 98653.54 18-DEC-06:10 31067.84 04-DEC-07:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 234435.00   37611.08   439129.89   117189.56   98653.54   30939.44   0.00  
Maximum of Months 261074.09   37611.08   794004.08   117204.73   257925.20   51515.43   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 33546.82 11-JAN-06:10 3201.90 21-JAN-20:00 11049.26 11-JAN-20:00 6524.59 02-JAN-07:10 0.00 0.00
February 61081.22 16-FEB-15:20 6485.59 09-FEB-01:00 14543.31 18-FEB-07:19 6524.59 01-FEB-07:10 0.00 0.00
March 107812.85 31-MAR-23:19 20908.93 20-MAR-14:09 18642.85 04-MAR-07:00 6524.59 01-MAR-07:10 0.00 0.00
April 132922.89 20-APR-14:09 49248.27 17-APR-11:00 19765.86 03-APR-06:10 6524.59 01-APR-06:10 0.00 0.00
May 181767.73 31-MAY-15:00 50315.68 31-MAY-14:00 7584.95 05-MAY-06:00 6524.59 27-MAY-06:30 0.00 0.00
June 287149.03 30-JUN-12:20 78538.83 29-JUN-10:20 9313.16 02-JUN-06:10 6524.59 20-JUN-15:39 0.00 0.00
July 319829.97 21-JUL-15:50 78538.83 03-JUL-14:50 11154.15 31-JUL-06:10 6524.59 11-JUL-12:50 0.00 0.00
August 352160.95 11-AUG-15:20 78538.83 23-AUG-14:30 18253.72 30-AUG-06:10 6524.59 11-AUG-15:39 0.00 0.00
September 77239.28 07-SEP-15:00 49372.03 07-SEP-15:00 8506.58 30-SEP-16:10 6524.59 23-SEP-16:10 0.00 0.00
October 82542.99 31-OCT-23:30 38004.44 01-OCT-14:00 14335.60 30-OCT-19:00 6524.59 07-OCT-16:10 0.00 0.00
November 85446.93 18-NOV-06:40 6519.77 18-NOV-03:00 18942.70 27-NOV-07:00 6524.59 01-NOV-06:10 0.00 0.00
December 108200.85 13-DEC-01:10 15868.49 24-DEC-11:00 23732.62 28-DEC-07:10 6524.59 01-DEC-07:10 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 33546.82   3201.90   7584.95   6524.59   0.00 0.00
Maximum of Months 352160.95   78538.83   23732.62   6524.59   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1008152.81 27-JAN-08:20 261074.09 439129.89 37611.08 117204.73 75994.26 30856.47 0.00 30741.64 1936.28
February 1158500.45 14-FEB-08:20 261074.09 557421.28 37611.08 117204.73 76146.35 30852.80 0.00 56892.74 3209.54
March 1309761.77 30-MAR-13:50 234435.00 675712.68 0.00 37754.99 221567.80 30891.25 0.00 85802.46 5445.72
April 1512319.20 21-APR-15:39 234435.00 794004.08 0.00 83146.17 193522.68 30841.86 0.00 118880.40 49248.27
May 1247197.64 31-MAY-15:39 234435.00 439129.89 0.00 83146.17 211770.42 46958.12 0.00 180911.10 50263.29
June 1503171.30 29-JUN-15:39 234435.00 557421.28 0.00 83146.17 225685.78 47853.89 0.00 269565.75 78538.83
July 1651622.03 11-JUL-15:50 234435.00 675712.68 0.00 83146.17 245611.68 48023.80 0.00 305039.02 53129.07
August 1805522.45 11-AUG-15:39 234435.00 794004.08 0.00 83146.17 249103.87 51515.43 0.00 335376.28 51417.03
September 1064142.40 07-SEP-15:30 234435.00 439129.89 0.00 83146.17 151268.02 30925.38 0.00 72659.52 49338.28
October 1161533.05 13-OCT-07:19 261074.09 557421.28 37611.08 117204.73 76954.76 30846.42 0.00 59792.96 4011.39
November 1307427.99 24-NOV-08:00 261074.09 675712.68 37611.08 117204.73 76894.37 30874.11 0.00 81818.90 4442.94
December 1454288.96 29-DEC-08:20 261074.09 794004.08 37611.08 117204.73 76015.67 30860.00 0.00 106440.71 6111.65
                       
Annual Sum or Average                      
Minimum of Months 1008152.81   234435.00 439129.89 0.00 37754.99 75994.26 30841.86 0.00 30741.64 1936.28
Maximum of Months 1805522.45   261074.09 794004.08 37611.08 117204.73 249103.87 51515.43 0.00 335376.28 78538.83



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 2378981.53 30-JAN-07:19 0.00 87759.79 03-JAN-12:00 0.00
February 0.00 0.00 2627511.03 27-FEB-07:19 0.00 87718.97 28-FEB-12:20 0.00
March 0.00 0.00 1947287.05 01-MAR-07:19 0.00 87738.78 21-MAR-11:20 0.00
April 0.00 0.00 981512.78 03-APR-05:10 0.00 87712.61 24-APR-11:20 0.00
May 0.00 0.00 326346.22 27-MAY-06:10 0.00 87712.59 02-MAY-11:20 0.00
June 0.00 0.00 2366.37 02-JUN-06:10 0.00 87001.21 01-JUN-11:50 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 85761.52 03-JUL-11:20 0.00
August 0.00 0.00 367924.24 31-AUG-06:10 0.00 84868.55 01-AUG-11:00 0.00
September 0.00 0.00 526873.42 25-SEP-06:10 0.00 84662.56 29-SEP-11:30 0.00
October 0.00 0.00 1248109.21 23-OCT-06:10 0.00 85539.03 31-OCT-11:20 0.00
November 0.00 0.00 2255411.17 27-NOV-07:19 0.00 86680.28 30-NOV-12:30 0.00
December 0.00 0.00 2093780.12 15-DEC-07:40 0.00 87711.33 28-DEC-12:30 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 84662.56   0.00
Maximum of Months 0.00 0.00 2627511.03   0.00 87759.79   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 25.64 0.00 25.64
April 0.00 0.00 0.00 0.00 0.67 25.78 0.00 25.78
May 0.00 0.00 0.00 0.00 1.67 25.66 0.00 25.66
June 0.00 0.00 0.00 0.00 2.00 25.85 0.00 25.85
July 0.00 0.00 0.00 0.00 5.00 26.37 0.00 26.37
August 0.00 0.00 0.00 0.00 5.33 26.36 0.00 26.36
September 0.00 0.00 0.00 0.00 9.00 26.52 1.50 26.65
October 0.00 0.00 0.00 0.00 3.67 26.24 0.00 26.24
November 0.00 0.00 0.00 0.00 0.17 25.59 0.00 25.59
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   28.00 26.29 1.50 26.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.00 26.52 1.50 26.65



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.33 25.60 0.00 25.60
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.50 25.59 0.00 25.59
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.33 25.60 0.00 25.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 3.00 19.28 1.33 19.49 0.00 19.49 0.00 19.49
February 0.33 18.76 0.00 18.76 0.00 18.76 0.00 18.76
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.17 18.57 0.00 18.57 0.00 18.57 0.00 18.57
December 0.50 18.84 0.00 18.84 0.00 18.84 0.00 18.84
                 
Annual Sum or Average 4.00 19.15 1.33 19.35 0.00 19.35 0.00 19.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 3.00 19.28 1.33 19.49 0.00 19.49 0.00 19.49



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 12.00 18.73 2.83 18.95 0.00 18.95 0.00 18.95
February 8.67 18.85 2.50 19.10 0.00 19.10 0.00 19.10
March 3.67 18.67 0.17 18.74 0.00 18.74 0.00 18.74
April 0.50 18.07 0.00 18.07 0.00 18.07 0.00 18.07
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 3.00 18.70 0.50 18.93 0.00 18.93 0.00 18.93
November 9.67 18.88 2.83 19.13 0.00 19.13 0.00 19.13
December 11.33 18.80 2.17 18.98 0.00 18.98 0.00 18.98
                 
Annual Sum or Average 48.83 18.78 11.00 19.00 0.00 19.00 0.00 19.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12.00 18.88 2.83 19.13 0.00 19.13 0.00 19.13



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.67 18.88 0.83 19.06 0.00 19.06 0.00 19.06
February 2.33 18.99 0.17 19.05 0.00 19.05 0.00 19.05
March 0.67 19.02 0.00 19.02 0.00 19.02 0.00 19.02
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 25.73 0.00 25.73
June 0.00 0.00 0.00 0.00 7.00 25.98 0.00 25.98
July 0.00 0.00 0.00 0.00 2.83 25.94 0.00 25.94
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.83 19.20 0.00 19.20 0.00 19.20 0.00 19.20
December 3.00 19.23 0.00 19.23 0.00 19.23 0.00 19.23
                 
Annual Sum or Average 12.50 19.01 1.00 19.10 10.00 22.02 0.00 22.02
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.67 19.23 0.83 19.23 7.00 25.98 0.00 25.98



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.50 18.45 0.00 18.45 0.00 18.45 0.00 18.45
February 2.33 18.71 0.00 18.71 0.00 18.71 0.00 18.71
March 0.83 18.98 0.00 18.98 0.00 18.98 0.00 18.98
April 0.00 0.00 0.00 0.00 0.67 27.55 0.67 27.55
May 0.00 0.00 0.00 0.00 3.33 28.08 3.17 28.14
June 0.00 0.00 0.00 0.00 4.50 26.45 1.00 26.72
July 0.00 0.00 0.00 0.00 5.00 27.37 3.50 27.61
August 0.00 0.00 0.00 0.00 0.33 27.74 0.33 27.74
September 0.00 0.00 0.00 0.00 1.17 27.67 1.17 27.67
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 1.00 19.02 0.00 19.02 0.00 19.02 0.00 19.02
December 3.67 18.99 0.00 18.99 0.00 18.99 0.00 18.99
                 
Annual Sum or Average 13.33 18.72 0.00 18.72 15.00 23.26 9.83 24.47
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5.50 19.02 0.00 19.02 5.00 28.08 3.50 28.14



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.83 18.36 0.00 18.36 0.00 18.36 0.00 18.36
February 2.67 18.80 0.17 18.89 0.00 18.89 0.00 18.89
March 0.83 19.04 0.00 19.04 0.00 19.04 0.00 19.04
April 0.00 0.00 0.00 0.00 2.50 27.83 2.50 27.83
May 0.00 0.00 0.00 0.00 4.67 27.89 4.67 27.89
June 0.00 0.00 0.00 0.00 2.83 27.88 2.83 27.88
July 0.00 0.00 0.00 0.00 4.33 28.02 4.17 28.04
August 0.00 0.00 0.00 0.00 3.00 28.02 2.67 28.05
September 0.00 0.00 0.00 0.00 0.50 27.80 0.50 27.80
October 0.17 19.17 0.00 19.17 0.00 19.17 0.00 19.17
November 1.83 19.09 0.00 19.09 0.00 19.09 0.00 19.09
December 4.50 18.88 0.00 18.88 0.00 18.88 0.00 18.88
                 
Annual Sum or Average 15.83 18.71 0.17 18.73 17.83 23.58 17.33 25.06
Minimum of Months 0.00 0.00 0.00 0.00 0.00 18.36 0.00 18.36
Maximum of Months 5.83 19.17 0.17 19.17 4.67 28.02 4.67 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.33 18.97 0.00 18.97 0.00 18.97 0.00 18.97
February 0.83 19.32 0.00 19.32 0.00 19.32 0.00 19.32
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 6.33 27.82 2.83 27.84
May 0.00 0.00 0.00 0.00 5.83 28.14 2.17 28.11
June 0.00 0.00 0.00 0.00 11.67 27.27 2.33 27.41
July 0.00 0.00 0.00 0.00 21.17 27.11 5.67 27.24
August 0.00 0.00 0.00 0.00 18.83 26.95 3.67 27.09
September 0.00 0.00 0.00 0.00 0.33 27.73 0.17 27.78
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 3.17 19.06 0.00 19.06 64.17 26.88 16.83 27.07
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.33 19.32 0.00 19.32 21.17 28.14 5.67 28.11



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 80.50 17.14 38.17 17.40 0.00 17.40 0.00 17.40
February 52.50 17.33 22.17 17.64 0.00 17.64 0.00 17.64
March 26.50 18.83 8.83 19.15 0.00 19.15 0.00 19.15
April 6.50 18.25 1.50 18.58 0.00 18.58 0.00 18.58
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 3.50 25.85 0.00 25.85
July 0.00 0.00 0.00 0.00 1.50 25.80 0.00 25.80
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 12.17 18.16 2.83 18.52 0.00 18.52 0.00 18.52
November 41.50 18.11 17.67 18.38 0.00 18.38 0.00 18.38
December 64.17 17.92 28.67 18.20 0.00 18.20 0.00 18.20
                 
Annual Sum or Average 283.83 17.72 119.83 17.99 5.00 18.09 0.00 18.09
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 80.50 18.83 38.17 19.15 3.50 25.85 0.00 25.85



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 44.67 15.37 13.17 15.19 0.00 15.19 0.00 15.19
February 24.67 15.88 4.17 15.73 0.00 15.73 0.00 15.73
March 8.50 17.81 0.00 17.81 0.00 17.81 0.00 17.81
April 2.17 18.42 0.00 18.42 0.00 18.42 0.00 18.42
May 0.00 0.00 0.00 0.00 3.17 28.35 3.17 28.35
June 0.00 0.00 0.00 0.00 3.67 26.67 1.50 26.99
July 0.00 0.00 0.00 0.00 5.33 27.79 4.67 27.90
August 0.00 0.00 0.00 0.00 0.67 27.65 0.67 27.65
September 0.00 0.00 0.00 0.00 0.50 27.74 0.50 27.74
October 4.50 17.23 0.17 17.15 0.00 17.15 0.00 17.15
November 19.83 16.58 3.50 16.45 0.00 16.45 0.00 16.45
December 30.00 15.89 7.00 15.71 0.00 15.71 0.00 15.71
                 
Annual Sum or Average 134.33 16.02 28.00 15.82 13.33 16.71 10.50 17.35
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.19 0.00 15.19
Maximum of Months 44.67 18.42 13.17 18.42 5.33 28.35 4.67 28.35



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 37.83 15.51 10.67 15.31 0.00 15.31 0.00 15.31
February 14.33 16.60 2.00 16.35 0.00 16.35 0.00 16.35
March 7.00 18.31 0.00 18.31 0.17 18.45 0.17 18.59
April 1.33 18.63 0.00 18.63 2.33 24.50 2.33 25.81
May 0.00 0.00 0.00 0.00 5.00 28.07 5.00 28.07
June 0.00 0.00 0.00 0.00 2.67 27.94 2.67 27.94
July 0.00 0.00 0.00 0.00 4.17 28.14 4.00 28.16
August 0.00 0.00 0.00 0.00 2.83 28.16 2.50 28.19
September 0.00 0.00 0.00 0.00 0.33 28.05 0.33 28.05
October 3.33 17.73 0.00 17.73 0.00 17.73 0.00 17.73
November 14.17 17.10 0.67 17.06 0.00 17.06 0.00 17.06
December 27.50 16.05 6.33 15.85 0.00 15.85 0.00 15.85
                 
Annual Sum or Average 105.50 16.31 19.67 16.07 17.50 17.53 17.00 18.65
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.31 0.00 15.31
Maximum of Months 37.83 18.63 10.67 18.63 5.00 28.16 5.00 28.19



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 36.00 15.57 10.67 15.36 0.00 15.36 0.00 15.36
February 15.00 16.48 2.50 16.21 0.00 16.21 0.00 16.21
March 7.67 18.15 0.00 18.15 0.00 18.15 0.00 18.15
April 1.50 18.68 0.00 18.68 0.67 21.47 0.17 21.94
May 0.00 0.00 0.00 0.00 4.83 27.97 1.33 27.95
June 0.00 0.00 0.00 0.00 4.67 28.01 1.17 28.03
July 0.00 0.00 0.00 0.00 4.17 27.76 1.50 27.73
August 0.00 0.00 0.00 0.00 2.17 27.85 0.67 27.85
September 0.00 0.00 0.00 0.00 0.17 27.27 0.17 27.27
October 3.50 17.84 0.00 17.84 0.00 17.84 0.00 17.84
November 10.17 17.96 0.33 17.96 0.00 17.96 0.00 17.96
December 17.33 16.73 2.33 16.51 0.00 16.51 0.00 16.51
                 
Annual Sum or Average 91.17 16.56 15.83 16.29 16.67 17.86 5.00 18.24
Minimum of Months 0.00 0.00 0.00 0.00 0.00 15.36 0.00 15.36
Maximum of Months 36.00 18.68 10.67 18.68 4.83 28.01 1.50 28.03



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 127.17 16.44 57.00 16.77 0.00 16.77 0.00 16.77
February 100.50 16.54 43.67 16.86 0.00 16.86 0.00 16.86
March 79.50 17.10 29.67 17.49 0.00 17.49 0.00 17.49
April 25.83 16.57 7.33 16.64 0.00 16.64 0.00 16.64
May 0.17 19.29 0.00 19.29 0.00 19.29 0.00 19.29
June 0.00 0.00 0.00 0.00 1.00 25.65 0.00 25.65
July 0.00 0.00 0.00 0.00 0.67 25.87 0.00 25.87
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 1.50 18.58 0.00 18.58 0.00 18.58 0.00 18.58
October 41.83 16.67 14.83 16.85 0.00 16.85 0.00 16.85
November 102.83 16.64 45.50 16.91 0.00 16.91 0.00 16.91
December 136.33 16.78 59.50 17.16 0.00 17.16 0.00 17.16
                 
Annual Sum or Average 615.67 16.68 257.50 16.99 1.67 17.01 0.00 17.01
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 136.33 19.29 59.50 19.29 1.00 25.87 0.00 25.87



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 71.17 14.83 19.67 14.75 0.00 14.75 0.00 14.75
February 56.67 15.10 14.17 15.02 0.00 15.02 0.00 15.02
March 34.17 15.71 1.83 15.68 0.00 15.68 0.00 15.68
April 13.00 16.26 1.00 16.15 0.00 16.15 0.00 16.15
May 0.17 19.33 0.00 19.33 2.50 27.67 2.50 27.94
June 0.00 0.00 0.00 0.00 1.50 27.14 1.00 27.38
July 0.00 0.00 0.00 0.00 4.83 27.80 4.17 27.94
August 0.00 0.00 0.00 0.00 0.33 27.71 0.33 27.71
September 1.33 18.82 0.00 18.82 0.00 18.82 0.00 18.82
October 26.17 15.79 5.33 15.65 0.00 15.65 0.00 15.65
November 66.17 15.04 20.00 14.95 0.00 14.95 0.00 14.95
December 80.67 14.98 21.67 14.92 0.00 14.92 0.00 14.92
                 
Annual Sum or Average 349.50 15.18 83.67 15.08 9.17 15.34 8.00 15.57
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.75 0.00 14.75
Maximum of Months 80.67 19.33 21.67 19.33 4.83 27.80 4.17 27.94



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 64.83 14.86 17.50 14.78 0.00 14.78 0.00 14.78
February 44.33 15.32 8.50 15.27 0.00 15.27 0.00 15.27
March 23.50 16.23 2.17 16.15 0.00 16.15 0.00 16.15
April 8.00 16.85 1.00 16.60 0.83 17.52 0.83 18.29
May 0.17 19.36 0.00 19.36 3.50 27.54 3.50 27.73
June 0.00 0.00 0.00 0.00 2.50 27.88 2.50 27.88
July 0.00 0.00 0.00 0.00 3.83 28.27 3.50 28.30
August 0.00 0.00 0.00 0.00 1.83 28.39 1.50 28.46
September 1.00 18.82 0.00 18.82 0.17 20.07 0.17 21.01
October 20.83 16.06 3.50 15.93 0.00 15.93 0.00 15.93
November 54.50 15.17 16.00 15.07 0.00 15.07 0.00 15.07
December 74.00 15.01 18.33 14.92 0.00 14.92 0.00 14.92
                 
Annual Sum or Average 291.17 15.29 67.00 15.18 12.67 15.62 12.00 16.01
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.78 0.00 14.78
Maximum of Months 74.00 19.36 18.33 19.36 3.83 28.39 3.50 28.46



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 62.83 14.85 17.17 14.74 0.00 14.74 0.00 14.74
February 48.50 15.25 13.17 15.14 0.00 15.14 0.00 15.14
March 24.83 16.17 2.67 16.08 0.00 16.08 0.00 16.08
April 7.67 16.83 2.00 16.43 0.50 16.97 0.17 17.14
May 0.17 19.36 0.00 19.36 3.67 27.44 0.67 27.46
June 0.00 0.00 0.00 0.00 4.33 28.03 1.17 28.05
July 0.00 0.00 0.00 0.00 4.17 27.74 1.33 27.73
August 0.00 0.00 0.00 0.00 1.33 27.99 0.50 27.93
September 1.17 18.97 0.00 18.97 0.00 18.97 0.00 18.97
October 20.83 16.14 4.00 15.99 0.00 15.99 0.00 15.99
November 51.33 15.33 16.33 15.23 0.00 15.23 0.00 15.23
December 58.17 15.13 15.17 15.02 0.00 15.02 0.00 15.02
                 
Annual Sum or Average 275.50 15.36 70.50 15.23 14.00 15.72 3.83 15.84
Minimum of Months 0.00 0.00 0.00 0.00 0.00 14.74 0.00 14.74
Maximum of Months 62.83 19.36 17.17 19.36 4.33 28.03 1.33 28.05



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 12.17 27.79 12.17 27.79
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   12.17 27.79 12.17 27.79
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.17 27.79 12.17 27.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 486.33 23.37 16.83 23.31 16.83 23.25
February 424.33 23.75 0.00 23.75 0.00 23.75
March 433.83 23.95 0.50 23.96 0.00 23.96
April 334.17 24.01 33.50 24.22 0.00 24.22
May 171.83 24.00 70.17 24.64 0.00 24.64
June 12.67 24.00 176.50 25.06 0.00 25.06
July 0.00 0.00 337.33 24.85 0.00 24.85
August 17.17 24.00 248.00 24.87 0.00 24.87
September 66.17 24.00 99.50 25.32 0.00 25.32
October 239.67 24.01 54.67 24.44 0.00 24.44
November 385.00 23.51 2.00 23.52 0.00 23.52
December 449.67 23.31 11.17 23.37 0.00 23.37
             
Annual Sum or Average 3020.83 23.69 1050.17 24.09 16.83 24.08
Minimum of Months 0.00 0.00 0.00 23.31 0.00 23.25
Maximum of Months 486.33 24.01 337.33 25.32 16.83 25.32



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 22.79 22.00 22.68 22.00 22.58
February 448.00 23.52 0.00 23.52 0.00 23.52
March 437.67 23.82 0.00 23.82 0.00 23.82
April 247.50 23.99 26.83 24.19 0.00 24.19
May 128.33 23.97 39.67 24.42 0.00 24.42
June 1.50 23.99 178.17 24.67 0.00 24.67
July 0.00 0.00 369.83 24.37 0.00 24.37
August 10.67 24.00 286.17 24.41 0.00 24.41
September 94.67 23.85 64.50 24.65 0.00 24.65
October 288.67 23.85 29.33 24.03 0.00 24.03
November 487.67 23.79 0.00 23.79 0.00 23.79
December 485.67 23.51 0.00 23.51 0.00 23.51
             
Annual Sum or Average 3132.33 23.58 1016.50 23.83 22.00 23.81
Minimum of Months 0.00 0.00 0.00 22.68 0.00 22.58
Maximum of Months 502.00 24.00 369.83 24.67 22.00 24.67



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 21.12 260.33 20.87 260.33 20.74
February 454.00 21.66 137.50 21.39 137.50 21.23
March 514.00 22.52 40.17 22.41 40.17 22.33
April 457.00 23.35 4.83 23.32 4.83 23.30
May 261.83 23.85 3.83 23.88 0.00 23.88
June 31.00 23.81 129.33 24.51 0.00 24.51
July 0.50 23.70 270.67 24.47 0.00 24.47
August 58.17 23.80 172.67 24.37 0.00 24.37
September 280.33 23.59 17.33 23.69 0.00 23.69
October 497.33 22.82 27.17 22.72 27.17 22.64
November 489.00 21.54 179.83 21.32 179.83 21.19
December 497.00 21.21 271.50 21.00 271.50 20.90
             
Annual Sum or Average 4042.17 22.29 1515.17 22.25 921.33 22.01
Minimum of Months 0.50 21.12 3.83 20.87 0.00 20.74
Maximum of Months 514.00 23.85 271.50 24.51 271.50 24.51



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.21 462.83 20.16 462.83 20.15
February 454.00 20.43 339.83 20.28 339.83 20.22
March 514.00 21.05 286.17 20.83 286.17 20.73
April 485.00 22.20 118.17 21.82 118.17 21.56
May 371.17 23.42 4.33 23.40 3.33 23.38
June 94.33 23.70 94.17 24.11 0.00 24.11
July 18.33 23.49 252.33 24.35 0.00 24.35
August 132.83 23.34 132.17 23.90 0.00 23.90
September 451.67 22.64 27.00 22.54 27.00 22.45
October 502.00 21.06 229.50 20.78 229.50 20.64
November 489.00 20.30 434.50 20.24 434.50 20.21
December 497.00 20.20 486.17 20.19 486.17 20.19
             
Annual Sum or Average 4511.33 21.33 2867.17 21.17 2387.50 20.93
Minimum of Months 18.33 20.20 4.33 20.16 0.00 20.15
Maximum of Months 514.00 23.70 486.17 24.35 486.17 24.35



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.32 481.33 20.31 481.33 20.30
February 454.00 20.71 329.00 20.59 329.00 20.55
March 514.00 21.55 216.67 21.33 216.67 21.22
April 472.67 23.10 32.83 22.95 32.83 22.82
May 264.67 23.86 4.50 23.89 0.00 23.89
June 2.17 24.00 228.83 24.48 0.00 24.48
July 0.17 27.17 411.33 24.41 0.17 24.41
August 46.83 23.72 208.17 24.24 0.00 24.24
September 384.33 23.16 10.83 23.22 0.00 23.22
October 500.50 22.01 106.00 21.78 106.00 21.62
November 489.00 20.73 415.00 20.69 415.00 20.68
December 497.00 20.63 478.17 20.62 478.17 20.61
             
Annual Sum or Average 4127.33 21.66 2922.67 21.67 2059.17 21.42
Minimum of Months 0.17 20.32 4.50 20.31 0.00 20.30
Maximum of Months 514.00 27.17 481.33 24.48 481.33 24.48



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.26 488.33 20.25 488.33 20.24
February 454.00 20.74 324.50 20.62 324.50 20.58
March 490.67 21.81 160.33 21.57 159.67 21.42
April 345.00 22.75 51.17 22.81 24.17 22.71
May 139.50 23.78 143.67 24.25 9.33 24.35
June 20.50 24.26 301.33 24.33 4.17 24.36
July 20.50 26.00 407.33 24.45 15.17 24.53
August 73.00 23.41 276.33 24.03 1.83 24.05
September 318.00 22.88 55.50 23.24 2.00 23.26
October 491.50 21.85 109.83 21.64 109.83 21.49
November 489.00 20.59 470.83 20.58 470.83 20.57
December 497.00 20.45 497.00 20.45 497.00 20.45
             
Annual Sum or Average 3840.67 21.46 3286.17 21.68 2106.83 21.43
Minimum of Months 20.50 20.26 51.17 20.25 1.83 20.24
Maximum of Months 502.00 26.00 497.00 24.45 497.00 24.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.22 473.83 20.18 473.83 20.17
February 441.00 21.03 274.00 20.81 274.00 20.71
March 421.33 21.74 156.33 21.64 134.50 21.48
April 266.17 22.72 122.50 23.06 32.67 22.94
May 193.00 23.48 130.00 23.99 9.17 24.08
June 43.33 24.33 295.17 24.40 10.33 24.47
July 26.17 25.76 405.00 24.49 17.33 24.59
August 81.67 23.81 323.00 24.24 10.33 24.31
September 292.33 22.76 92.67 23.20 1.00 23.21
October 457.00 21.76 122.50 21.59 111.67 21.43
November 486.83 20.67 416.17 20.58 416.17 20.54
December 497.00 20.34 495.33 20.34 495.33 20.34
             
Annual Sum or Average 3707.83 21.47 3306.50 21.76 1986.33 21.49
Minimum of Months 26.17 20.22 92.67 20.18 1.00 20.17
Maximum of Months 502.00 25.76 495.33 24.49 495.33 24.59



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 20.59 420.00 20.55 420.00 20.53
February 454.00 21.27 192.50 21.10 192.50 21.01
March 464.17 22.54 40.67 22.47 35.67 22.37
April 146.33 23.69 123.33 24.38 5.50 24.44
May 103.83 23.76 118.17 24.49 6.50 24.57
June 10.33 27.01 409.17 24.62 10.33 24.67
July 24.83 26.94 495.50 24.68 24.83 24.79
August 19.50 26.35 467.33 24.59 15.50 24.66
September 247.33 23.09 68.83 23.50 0.83 23.51
October 445.67 22.47 28.33 22.42 25.33 22.34
November 489.00 21.46 122.67 21.36 122.67 21.30
December 497.00 21.34 237.33 21.23 237.33 21.17
             
Annual Sum or Average 3404.00 21.94 2723.83 22.49 1097.00 22.28
Minimum of Months 10.33 20.59 28.33 20.55 0.83 20.53
Maximum of Months 502.00 27.01 495.50 24.68 420.00 24.79



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.81 502.00 19.81 502.00 19.81
February 454.00 19.95 451.33 19.95 451.33 19.95
March 514.00 20.38 464.83 20.34 464.83 20.32
April 485.00 21.50 190.33 21.14 190.33 20.93
May 406.33 23.50 0.00 23.50 0.00 23.50
June 29.33 23.57 156.50 24.26 0.00 24.26
July 4.50 23.55 321.83 24.39 0.00 24.39
August 159.50 23.20 100.67 23.64 0.83 23.63
September 478.00 22.25 44.00 22.13 44.00 22.02
October 502.00 20.55 351.50 20.40 351.50 20.33
November 489.00 19.86 489.00 19.86 489.00 19.86
December 497.00 19.79 497.00 19.79 497.00 19.79
             
Annual Sum or Average 4520.67 20.89 3569.00 20.81 2990.83 20.59
Minimum of Months 4.50 19.79 0.00 19.79 0.00 19.79
Maximum of Months 514.00 23.57 502.00 24.39 502.00 24.39



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 427.00 19.68 427.00 19.68 427.00 19.68
February 385.00 19.89 379.17 19.88 379.17 19.88
March 431.33 20.74 307.17 20.56 307.17 20.49
April 351.67 21.85 114.50 21.60 102.17 21.37
May 181.17 23.41 99.00 23.91 10.17 24.03
June 51.67 23.77 224.17 24.29 5.83 24.35
July 37.50 25.18 329.00 24.63 19.83 24.75
August 117.67 23.18 200.17 23.95 2.50 23.98
September 342.83 22.16 51.83 22.34 23.17 22.26
October 425.83 20.63 275.33 20.45 275.33 20.38
November 417.00 19.71 417.00 19.71 417.00 19.71
December 422.00 19.63 422.00 19.63 422.00 19.63
             
Annual Sum or Average 3590.67 20.81 3246.33 20.98 2391.33 20.73
Minimum of Months 37.50 19.63 51.83 19.63 2.50 19.63
Maximum of Months 431.33 25.18 427.00 24.63 427.00 24.75



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.93 493.17 19.92 493.17 19.91
February 448.17 20.52 366.50 20.35 366.50 20.29
March 437.00 21.13 266.50 20.98 247.83 20.83
April 301.67 22.08 164.83 22.28 80.67 22.06
May 232.17 23.19 132.67 23.71 14.50 23.81
June 94.00 23.66 266.33 24.21 11.17 24.30
July 68.67 24.12 363.50 24.42 16.67 24.52
August 138.50 23.30 270.00 24.06 10.50 24.14
September 321.67 22.34 102.33 22.78 13.83 22.74
October 471.33 21.09 239.00 20.86 232.00 20.73
November 489.00 20.08 466.67 20.04 466.67 20.02
December 497.00 19.86 497.00 19.86 497.00 19.86
             
Annual Sum or Average 4001.17 21.09 3628.50 21.32 2450.50 21.06
Minimum of Months 68.67 19.86 102.33 19.86 10.50 19.86
Maximum of Months 502.00 24.12 497.00 24.42 497.00 24.52



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.93 502.00 19.93 502.00 19.93
February 454.00 20.10 439.67 20.08 439.67 20.07
March 514.00 20.71 393.83 20.59 393.83 20.54
April 392.50 21.88 133.83 21.70 107.17 21.47
May 277.00 23.13 57.00 23.41 3.33 23.44
June 59.83 23.54 243.17 24.32 4.83 24.36
July 29.17 24.00 369.00 24.42 6.83 24.46
August 136.17 23.07 222.67 23.91 3.17 23.93
September 429.67 22.17 39.00 22.17 25.67 22.11
October 502.00 20.70 308.83 20.54 308.83 20.47
November 489.00 20.01 488.00 20.01 488.00 20.01
December 497.00 19.92 497.00 19.92 497.00 19.92
             
Annual Sum or Average 4282.33 20.93 3694.00 21.06 2780.33 20.82
Minimum of Months 29.17 19.92 39.00 19.92 3.17 19.92
Maximum of Months 514.00 24.00 502.00 24.42 502.00 24.46



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.61 502.00 19.61 502.00 19.61
February 454.00 19.73 454.00 19.73 454.00 19.73
March 514.00 20.06 506.17 20.05 506.17 20.05
April 485.00 20.67 310.50 20.43 310.50 20.33
May 464.17 22.70 33.17 22.55 33.17 22.41
June 78.00 23.09 117.83 23.82 0.00 23.82
July 57.33 23.28 278.83 24.11 0.00 24.11
August 278.33 22.67 79.83 22.91 12.17 22.85
September 485.00 21.14 177.17 20.96 177.17 20.86
October 502.00 19.97 463.00 19.92 463.00 19.91
November 489.00 19.68 489.00 19.68 489.00 19.68
December 497.00 19.59 497.00 19.59 497.00 19.59
             
Annual Sum or Average 4805.83 20.55 3908.50 20.46 3444.17 20.28
Minimum of Months 57.33 19.59 33.17 19.59 0.00 19.59
Maximum of Months 514.00 23.28 506.17 24.11 506.17 24.11



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.72 502.00 19.72 502.00 19.72
February 454.00 19.85 453.00 19.84 453.00 19.84
March 514.00 20.34 435.83 20.22 435.83 20.18
April 440.00 21.42 197.67 21.02 194.33 20.79
May 223.50 22.91 114.67 23.35 17.83 23.35
June 68.83 23.18 287.00 24.09 4.33 24.12
July 68.33 24.21 380.33 24.39 19.83 24.50
August 158.50 22.79 224.17 23.65 4.33 23.65
September 429.83 21.54 104.83 21.37 100.17 21.22
October 502.00 20.13 418.17 20.02 418.17 19.97
November 489.00 19.76 489.00 19.76 489.00 19.76
December 497.00 19.70 497.00 19.70 497.00 19.70
             
Annual Sum or Average 4347.00 20.61 4103.67 20.78 3135.83 20.55
Minimum of Months 68.33 19.70 104.83 19.70 4.33 19.70
Maximum of Months 514.00 24.21 502.00 24.39 502.00 24.50



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.75 502.00 19.75 502.00 19.75
February 454.00 20.08 414.83 19.99 414.83 19.96
March 470.50 20.71 342.33 20.46 342.33 20.36
April 341.67 21.48 215.83 21.49 150.67 21.22
May 269.17 22.56 127.33 23.06 22.67 23.04
June 124.83 23.13 248.67 23.96 10.33 24.04
July 110.50 23.52 336.50 24.21 15.17 24.30
August 190.50 22.81 248.67 23.67 13.67 23.69
September 372.00 21.62 140.17 21.79 80.00 21.62
October 485.33 20.38 374.67 20.22 371.33 20.14
November 489.00 19.83 483.83 19.81 483.83 19.81
December 497.00 19.71 497.00 19.71 497.00 19.71
             
Annual Sum or Average 4306.50 20.77 3931.83 20.94 2903.83 20.70
Minimum of Months 110.50 19.71 127.33 19.71 10.33 19.71
Maximum of Months 502.00 23.52 502.00 24.21 502.00 24.30



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 19.76 502.00 19.76 502.00 19.76
February 454.00 19.90 450.83 19.89 450.83 19.89
March 514.00 20.32 455.50 20.25 455.50 20.22
April 416.83 21.24 207.67 20.98 189.83 20.77
May 333.67 22.55 64.67 22.72 16.50 22.64
June 106.00 23.10 226.33 24.05 5.00 24.09
July 80.67 23.42 336.17 24.21 7.67 24.26
August 212.50 22.71 191.67 23.45 8.17 23.44
September 456.00 21.49 110.50 21.36 102.83 21.24
October 502.00 20.18 425.33 20.09 425.33 20.06
November 489.00 19.83 489.00 19.83 489.00 19.83
December 497.00 19.76 497.00 19.76 497.00 19.76
             
Annual Sum or Average 4563.67 20.68 3956.67 20.77 3149.67 20.55
Minimum of Months 80.67 19.76 64.67 19.76 5.00 19.76
Maximum of Months 514.00 23.42 502.00 24.21 502.00 24.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 19.33 25.87 177.67 26.89 0.00 26.89
February 0.00 0.00 337.33 27.00 0.00 27.00
March 0.00 0.00 508.83 27.00 0.00 27.00
April 18.17 27.00 485.00 27.00 18.17 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 6.83 27.00 496.00 27.00 6.83 27.00
July 35.67 27.00 497.00 27.00 35.67 27.00
August 75.17 27.00 514.00 27.00 75.17 27.00
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.00 0.00 502.00 27.00 0.00 27.00
November 0.00 0.00 466.83 27.00 0.00 27.00
December 0.00 0.00 475.00 27.00 0.00 27.00
             
Annual Sum or Average 155.17 26.86 5452.67 27.00 135.83 27.00
Minimum of Months 0.00 0.00 177.67 26.89 0.00 26.89
Maximum of Months 75.17 27.00 514.00 27.00 75.17 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 361.83 25.27 16.33 25.19 12.00 25.09
February 58.33 27.00 86.50 27.00 0.00 27.00
March 4.00 27.00 243.33 27.00 0.00 27.00
April 4.83 27.00 421.00 27.00 4.83 27.00
May 0.00 0.00 508.00 27.00 0.00 27.00
June 1.33 27.00 496.00 27.00 1.33 27.00
July 7.17 27.00 497.00 27.00 7.17 27.00
August 5.50 27.00 514.00 27.00 5.50 27.00
September 0.00 0.00 485.00 27.00 0.00 27.00
October 3.67 27.00 333.33 27.00 0.00 27.00
November 43.17 27.00 36.50 27.00 0.00 27.00
December 64.00 27.00 8.00 27.00 0.00 27.00
             
Annual Sum or Average 553.83 25.87 3645.00 26.84 30.83 26.82
Minimum of Months 0.00 0.00 8.00 25.19 0.00 25.09
Maximum of Months 361.83 27.00 514.00 27.00 12.00 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 491.67 24.32 79.83 23.95 79.83 23.68
February 118.50 26.71 25.67 26.77 0.00 26.77
March 71.33 27.00 115.00 27.00 0.00 27.00
April 33.50 27.00 334.33 27.00 4.00 27.00
May 0.00 0.00 500.17 27.00 0.00 27.00
June 1.83 27.00 496.00 27.00 1.83 27.00
July 8.33 27.00 497.00 27.00 8.33 27.00
August 6.17 27.00 514.00 27.00 6.17 27.00
September 14.00 26.05 421.00 26.97 0.00 26.97
October 61.17 27.00 176.83 27.00 0.00 27.00
November 126.83 27.00 1.00 27.00 0.00 27.00
December 141.00 27.00 0.00 27.00 0.00 27.00
             
Annual Sum or Average 1074.33 25.73 3160.83 26.58 100.17 26.49
Minimum of Months 0.00 0.00 0.00 23.95 0.00 23.68
Maximum of Months 491.67 27.00 514.00 27.00 79.83 27.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 449.17 27.00 454.00 27.00 449.17 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.00 485.00 27.00 485.00 27.00
May 437.00 27.00 508.00 27.00 437.00 27.00
June 496.00 27.01 496.00 27.01 496.00 27.01
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 27.04 514.00 27.04 514.00 27.04
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.00 497.00 27.00 497.00 27.00
             
Annual Sum or Average 5365.17 27.01 5943.00 27.01 5365.17 27.01
Minimum of Months 0.00 0.00 454.00 27.00 0.00 27.00
Maximum of Months 514.00 27.04 514.00 27.04 514.00 27.04



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.89220 11.39954 0.50359 10.43757
February 454.00000 27.00000 11.34807 0.60531 12.81776
March 514.00000 27.00000 12.18121 0.70633 15.63070
April 485.00000 26.99999 15.40702 0.84659 20.26547
May 508.00000 27.00000 22.38903 0.15325 5.56760
June 496.00000 27.00038 28.62555 0.28613 6.75972
July 497.00000 27.00046 30.33239 0.34378 7.50792
August 514.00000 27.00018 28.88277 0.36136 7.77998
September 485.00000 27.00012 25.27830 0.13199 5.50492
October 502.00000 27.00000 17.59356 0.72945 16.34675
November 489.00000 27.00000 9.97633 0.63267 13.45072
December 497.00000 27.00000 9.03367 0.62875 13.35494
           
Annual Sum or Average 5943.00000 26.99099 18.60358 0.49297 11.26100
Minimum of Months 454.00000 26.89220 9.03367 0.13199 5.50492
Maximum of Months 514.00000 27.00046 30.33239 0.84659 20.26547



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 25.68770 11.25580 0.16827 6.93503
February 454.00000 27.00000 11.32421 0.45947 9.60407
March 514.00000 27.00000 12.16937 0.53923 11.26427
April 485.00000 26.99999 15.39682 0.68805 15.28924
May 508.00000 27.00000 22.37563 0.07633 5.26794
June 496.00000 27.00036 28.63081 0.20384 5.95732
July 497.00000 27.00047 30.35136 0.23747 6.24610
August 514.00000 27.00020 28.88195 0.22107 6.13751
September 485.00000 27.00011 25.31241 0.01360 5.21758
October 502.00000 27.00000 17.57720 0.57982 12.25406
November 489.00000 27.00000 9.96228 0.44859 9.30630
December 497.00000 27.00000 9.02750 0.43275 9.00731
           
Annual Sum or Average 5943.00000 26.88925 18.58830 0.33780 8.52199
Minimum of Months 454.00000 25.68770 9.02750 0.01360 5.21758
Maximum of Months 514.00000 27.00047 30.35136 0.68805 15.28924



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.36243 11.32711 -0.1406 7.85749
February 454.00000 26.92545 11.33280 0.37371 8.38876
March 514.00000 27.00000 12.17221 0.46016 9.67520
April 485.00000 26.99999 15.39931 0.61465 13.46182
May 508.00000 26.99977 22.37979 0.02522 5.34401
June 496.00000 27.00036 28.64058 0.19308 5.95371
July 497.00000 27.00047 30.35915 0.22697 6.21018
August 514.00000 27.00021 28.89303 0.18649 5.98180
September 485.00000 26.95295 25.43695 -0.1052 5.77843
October 502.00000 26.99991 17.58013 0.48945 10.27694
November 489.00000 27.00000 9.96570 0.37376 8.09641
December 497.00000 27.00000 9.02901 0.36361 7.91899
           
Annual Sum or Average 5943.00000 26.76773 18.60903 0.25393 7.89843
Minimum of Months 454.00000 24.36243 9.02901 -0.1406 5.34401
Maximum of Months 514.00000 27.00047 30.35915 0.61465 13.46182



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00247 30.00088 0.91886 22.87277
February 454.00000 27.00323 30.00014 1.11240 31.10432
March 514.00000 27.00239 29.99923 1.29672 40.11064
April 485.00000 27.00129 29.99884 1.47401 49.49303
May 508.00000 27.00254 29.99894 0.44898 9.25281
June 496.00000 27.00526 30.18593 0.69633 15.21038
July 497.00000 27.00408 30.49277 0.91763 22.79718
August 514.00000 27.03560 30.16756 1.12577 31.73280
September 485.00000 27.00308 30.00067 0.48975 10.06031
October 502.00000 27.00307 29.99966 1.20069 35.29165
November 489.00000 27.00257 30.00020 1.30826 40.69876
December 497.00000 27.00197 30.00032 1.42349 46.77060
           
Annual Sum or Average 5943.00000 27.00573 30.07112 1.03371 29.58985
Minimum of Months 454.00000 27.00129 29.99884 0.44898 9.25281
Maximum of Months 514.00000 27.03560 30.49277 1.47401 49.49303



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.42209 16.13987 -0.0013 6.15495
February 454.00000 23.84858 13.72769 0.10037 6.09744
March 514.00000 24.17006 13.60217 0.18704 6.03620
April 485.00000 24.41236 14.33819 0.27137 6.84626
May 508.00000 24.42738 20.82946 -0.5363 11.69750
June 496.00000 24.41575 33.50109 -0.4350 9.71263
July 497.00000 24.57664 42.55722 -0.3127 8.27921
August 514.00000 24.45688 36.62278 -0.3813 9.02319
September 485.00000 24.49513 26.09420 -0.4664 10.61868
October 502.00000 24.46264 17.95733 0.30711 7.43641
November 489.00000 23.94559 11.28517 0.13308 6.55508
December 497.00000 23.51860 11.31007 0.02056 6.38527
           
Annual Sum or Average 5943.00000 24.18170 21.58218 -0.0948 7.91782
Minimum of Months 454.00000 23.42209 11.28517 -0.5363 6.03620
Maximum of Months 514.00000 24.57664 42.55722 0.30711 11.69750



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.78988 17.52360 -0.1414 6.62768
February 454.00000 23.53149 17.29747 0.04849 5.62709
March 514.00000 23.94714 15.92777 0.16270 5.85539
April 485.00000 24.26407 15.32048 0.26654 6.71422
May 508.00000 24.23211 21.66823 -0.5616 11.92659
June 496.00000 24.26088 34.56140 -0.4373 9.46773
July 497.00000 24.27863 42.96526 -0.3626 8.10016
August 514.00000 24.24728 37.79739 -0.4064 8.83014
September 485.00000 24.28190 27.86424 -0.5233 11.40280
October 502.00000 24.14928 21.35277 0.25029 6.69392
November 489.00000 23.79503 15.92259 0.10434 5.52891
December 497.00000 23.53233 14.53220 0.02266 5.49209
           
Annual Sum or Average 5943.00000 23.94491 23.63126 -0.1335 7.70502
Minimum of Months 454.00000 22.78988 14.53220 -0.5616 5.49209
Maximum of Months 514.00000 24.28190 42.96526 0.26654 11.92659



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.11844 17.55278 -0.5675 13.78046
February 454.00000 21.66358 18.45791 -0.4170 10.35735
March 514.00000 22.51700 18.93339 -0.2006 6.82744
April 485.00000 23.43371 17.73243 0.03815 5.98776
May 508.00000 24.05318 22.39484 -0.6465 14.06623
June 496.00000 24.19131 34.89544 -0.4933 10.42844
July 497.00000 24.24272 43.71543 -0.4155 9.03173
August 514.00000 24.17600 38.46875 -0.4806 10.26688
September 485.00000 23.88773 29.40579 -0.6846 15.56134
October 502.00000 22.82782 24.43053 -0.0864 6.40519
November 489.00000 21.54494 17.87627 -0.4553 10.40617
December 497.00000 21.20564 14.86148 -0.5590 12.56027
           
Annual Sum or Average 5943.00000 22.91580 24.96402 -0.4141 10.46798
Minimum of Months 454.00000 21.11844 14.86148 -0.6846 5.98776
Maximum of Months 514.00000 24.24272 43.71543 0.03815 15.56134



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.20631 18.55529 -0.8398 22.41007
February 454.00000 20.43453 20.28164 -0.7544 19.81271
March 514.00000 21.04759 20.20518 -0.5862 14.13764
April 485.00000 22.20049 19.04149 -0.2755 9.56613
May 508.00000 23.61753 23.45941 -0.8082 20.06183
June 496.00000 24.09072 35.01721 -0.5282 11.17879
July 497.00000 24.16919 43.88400 -0.4423 9.41640
August 514.00000 23.95031 39.27980 -0.5700 12.78135
September 485.00000 22.73490 32.57392 -1.1035 32.40739
October 502.00000 21.06490 26.86618 -0.5368 13.40532
November 489.00000 20.29960 19.63231 -0.8019 20.85126
December 497.00000 20.20234 15.84291 -0.8570 22.60206
           
Annual Sum or Average 5943.00000 22.01647 26.28110 -0.6743 17.33356
Minimum of Months 454.00000 20.20234 15.84291 -1.1035 9.41640
Maximum of Months 514.00000 24.16919 43.88400 -0.2755 32.40739



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.32443 17.32851 -0.8077 20.39177
February 454.00000 20.70566 17.69487 -0.6715 15.84385
March 514.00000 21.54743 16.61160 -0.4433 10.35298
April 485.00000 23.13702 15.48880 -0.0357 6.47252
May 508.00000 24.02714 21.04926 -0.6481 14.20907
June 496.00000 24.24928 33.55277 -0.4116 8.87564
July 497.00000 24.34021 41.97522 -0.3250 7.71404
August 514.00000 24.13983 37.38470 -0.4691 10.10213
September 485.00000 23.38429 28.72107 -0.8722 22.53140
October 502.00000 22.02061 22.05952 -0.2872 8.33839
November 489.00000 20.73277 16.68567 -0.6719 15.00102
December 497.00000 20.62789 14.52689 -0.7363 17.05081
           
Annual Sum or Average 5943.00000 22.45071 23.65441 -0.5306 13.03393
Minimum of Months 454.00000 20.32443 14.52689 -0.8722 6.47252
Maximum of Months 514.00000 24.34021 41.97522 -0.0357 22.53140



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.25776 16.55228 -0.8381 21.55446
February 454.00000 20.73620 16.85498 -0.6651 15.66175
March 514.00000 21.91435 15.53550 -0.3308 9.36739
April 485.00000 23.20201 14.71416 0.03229 7.19342
May 508.00000 24.12198 20.37402 -0.4821 11.77206
June 496.00000 24.20226 33.40142 -0.3394 8.28280
July 497.00000 24.28023 41.79593 -0.2534 7.58921
August 514.00000 24.00319 37.32721 -0.4308 9.92105
September 485.00000 23.40787 28.01396 -0.8060 21.66459
October 502.00000 21.89809 21.46302 -0.3010 8.66129
November 489.00000 20.58567 15.85666 -0.7270 16.77681
December 497.00000 20.44966 13.81591 -0.8076 19.64289
           
Annual Sum or Average 5943.00000 22.43636 23.04232 -0.4941 13.12735
Minimum of Months 454.00000 20.25776 13.81591 -0.8381 7.19342
Maximum of Months 514.00000 24.28023 41.79593 0.03229 21.66459



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.22108 16.60492 -0.8463 22.26929
February 454.00000 21.11170 16.54786 -0.5648 14.37841
March 514.00000 22.20356 15.11965 -0.2413 9.57261
April 485.00000 23.44169 14.25557 0.12603 8.31616
May 508.00000 23.98516 20.56533 -0.5540 14.02453
June 496.00000 24.21815 33.38164 -0.3497 8.69621
July 497.00000 24.29972 41.78589 -0.2565 7.71141
August 514.00000 24.12676 36.96909 -0.3612 9.46713
September 485.00000 23.37598 27.89782 -0.7896 21.68351
October 502.00000 21.98014 21.35188 -0.2763 9.11648
November 489.00000 20.68030 15.80698 -0.6984 16.68569
December 497.00000 20.33840 13.93742 -0.8368 20.96968
           
Annual Sum or Average 5943.00000 22.51128 22.92001 -0.4697 13.54052
Minimum of Months 454.00000 20.22108 13.93742 -0.8463 7.71141
Maximum of Months 514.00000 24.29972 41.78589 0.12603 22.26929



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 20.58909 16.09611 -0.7075 16.61182
February 454.00000 21.27251 16.16729 -0.4901 11.10633
March 514.00000 22.71701 14.57898 -0.1146 6.80630
April 485.00000 24.23725 13.59234 0.33991 8.60208
May 508.00000 24.22673 20.32095 -0.4739 11.02527
June 496.00000 24.45758 32.88262 -0.2104 7.17636
July 497.00000 24.56867 41.02715 -0.1050 6.62072
August 514.00000 24.46459 36.10972 -0.1855 7.07245
September 485.00000 23.71669 27.27002 -0.6840 16.91555
October 502.00000 22.68396 20.30044 -0.0948 6.80581
November 489.00000 21.46499 14.92508 -0.4462 9.61003
December 497.00000 21.34158 12.97497 -0.4923 10.56922
           
Annual Sum or Average 5943.00000 22.99204 22.25366 -0.3040 9.87896
Minimum of Months 454.00000 20.58909 12.97497 -0.7075 6.62072
Maximum of Months 514.00000 24.56867 41.02715 0.33991 16.91555



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.81106 16.60998 -1.0358 29.73293
February 454.00000 19.94965 17.88170 -0.9578 26.69726
March 514.00000 20.38445 18.02793 -0.7978 20.21659
April 485.00000 21.50298 17.52850 -0.4449 12.21702
May 508.00000 23.60951 21.84100 -0.8054 19.72783
June 496.00000 24.12572 33.91912 -0.4747 10.06139
July 497.00000 24.25607 42.39184 -0.3865 8.52921
August 514.00000 23.82795 38.36333 -0.6131 14.16255
September 485.00000 22.27326 30.98371 -1.2557 39.40786
October 502.00000 20.54683 24.37338 -0.6910 17.09682
November 489.00000 19.86289 17.44849 -0.9981 28.17778
December 497.00000 19.79199 13.96527 -1.0594 30.54020
           
Annual Sum or Average 5943.00000 21.67900 24.51058 -0.7914 21.29339
Minimum of Months 454.00000 19.79199 13.96527 -1.2557 8.52921
Maximum of Months 514.00000 24.25607 42.39184 -0.3865 39.40786



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 19.67851 15.65406 -1.0698 31.27751
February 385.00000 19.88893 16.71622 -0.9577 26.73264
March 433.00000 20.75047 16.51865 -0.6659 16.52808
April 410.00000 22.20591 15.54738 -0.2329 10.01709
May 430.00000 23.89199 20.43693 -0.5777 15.12590
June 418.00000 24.17002 33.36648 -0.3679 9.19339
July 422.00000 24.37956 41.63077 -0.2458 8.18584
August 433.00000 23.92994 37.26401 -0.4865 11.94366
September 410.00000 22.57384 29.18408 -1.1058 34.32145
October 427.00000 20.63762 23.02316 -0.6550 16.19412
November 417.00000 19.70671 16.41925 -1.0366 29.90088
December 422.00000 19.62525 13.13391 -1.1019 32.51951
           
Annual Sum or Average 5034.00000 21.80034 23.29585 -0.7064 20.07605
Minimum of Months 385.00000 19.62525 13.13391 -1.1058 8.18584
Maximum of Months 433.00000 24.37956 41.63077 -0.2329 34.32145



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.93211 15.95258 -0.9868 27.79534
February 454.00000 20.56028 16.69880 -0.7483 20.05394
March 514.00000 21.60772 16.22111 -0.4093 13.14200
April 485.00000 22.91423 15.19588 -0.0033 9.86590
May 508.00000 23.75218 20.85659 -0.6215 16.92613
June 496.00000 24.09327 33.66338 -0.3954 9.95668
July 497.00000 24.23646 42.10048 -0.2910 8.69192
August 514.00000 23.97706 37.36724 -0.4245 11.63418
September 485.00000 23.00924 28.73495 -0.9078 27.02654
October 502.00000 21.26730 22.82979 -0.4719 12.97553
November 489.00000 20.07997 16.48503 -0.9137 25.02446
December 497.00000 19.85822 13.36947 -1.0403 29.73160
           
Annual Sum or Average 5943.00000 22.12190 23.35904 -0.5995 17.67957
Minimum of Months 454.00000 19.85822 13.36947 -1.0403 8.69192
Maximum of Months 514.00000 24.23646 42.10048 -0.0033 29.73160



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.93390 15.89290 -0.9942 27.93354
February 454.00000 20.09542 17.04733 -0.8937 24.09663
March 514.00000 20.71058 17.00549 -0.6795 16.59258
April 485.00000 22.31878 15.93950 -0.1857 9.74617
May 508.00000 23.62698 21.31411 -0.7180 18.28872
June 496.00000 24.16175 33.72048 -0.3856 9.52981
July 497.00000 24.25925 42.19740 -0.3161 8.24241
August 514.00000 23.89776 37.78571 -0.5074 12.31833
September 485.00000 22.39871 29.85374 -1.1605 35.70817
October 502.00000 20.70134 23.46501 -0.6322 15.18198
November 489.00000 20.01390 16.48322 -0.9388 25.63505
December 497.00000 19.92201 13.25399 -1.0058 28.19152
           
Annual Sum or Average 5943.00000 21.85269 23.73248 -0.6995 19.20749
Minimum of Months 454.00000 19.92201 13.25399 -1.1605 8.24241
Maximum of Months 514.00000 24.25925 42.19740 -0.1857 35.70817



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.61047 16.75138 -1.1554 34.78550
February 454.00000 19.73153 18.68112 -1.0858 31.99291
March 514.00000 20.05653 18.68544 -0.9496 26.22959
April 485.00000 20.66535 18.34126 -0.6806 17.76187
May 508.00000 22.81204 22.90471 -1.0735 31.18136
June 496.00000 23.96034 34.23148 -0.5316 11.80211
July 497.00000 24.07039 42.73324 -0.4494 9.81617
August 514.00000 23.31005 39.51834 -0.7882 20.71921
September 485.00000 21.13813 33.11510 -1.6751 59.56117
October 502.00000 19.96819 25.75474 -0.8996 24.70958
November 489.00000 19.68067 18.05228 -1.1239 33.46174
December 497.00000 19.58766 13.94735 -1.1873 36.09616
           
Annual Sum or Average 5943.00000 21.23278 25.29103 -0.9646 28.08344
Minimum of Months 454.00000 19.58766 13.94735 -1.6751 9.81617
Maximum of Months 514.00000 24.07039 42.73324 -0.4494 59.56117



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.72440 16.53512 -1.1325 33.70778
February 454.00000 19.84519 18.39260 -1.0388 30.04733
March 514.00000 20.33963 18.15152 -0.8111 21.67501
April 485.00000 21.66762 16.95378 -0.3857 13.14974
May 508.00000 23.59918 21.12990 -0.6756 18.51499
June 496.00000 24.04887 33.61341 -0.3862 9.92472
July 497.00000 24.22624 41.87797 -0.2731 8.58553
August 514.00000 23.73388 38.05526 -0.5448 13.99472
September 485.00000 21.86255 31.47461 -1.3841 46.50894
October 502.00000 20.12885 25.23575 -0.8340 22.51869
November 489.00000 19.75847 17.77745 -1.1078 32.72347
December 497.00000 19.69785 13.80364 -1.1690 35.21181
           
Annual Sum or Average 5943.00000 21.57004 24.47761 -0.8089 23.76463
Minimum of Months 454.00000 19.69785 13.80364 -1.3841 8.58553
Maximum of Months 514.00000 24.22624 41.87797 -0.2731 46.50894



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.75194 16.52050 -1.1010 32.50669
February 454.00000 20.08347 18.12068 -0.9249 26.27256
March 514.00000 20.98408 17.48837 -0.6147 18.03852
April 485.00000 22.29266 16.12696 -0.1906 12.29392
May 508.00000 23.33708 21.48888 -0.7795 23.09135
June 496.00000 23.92614 33.94675 -0.4512 11.91095
July 497.00000 24.07621 42.37011 -0.3441 10.07929
August 514.00000 23.70471 38.07501 -0.5270 15.07320
September 485.00000 22.25365 30.63434 -1.2133 40.37290
October 502.00000 20.50160 24.72743 -0.7134 19.61199
November 489.00000 19.82698 17.70267 -1.0512 30.59347
December 497.00000 19.71281 13.81578 -1.1533 34.57147
           
Annual Sum or Average 5943.00000 21.71989 24.31550 -0.7532 22.79051
Minimum of Months 454.00000 19.71281 13.81578 -1.2133 10.07929
Maximum of Months 514.00000 24.07621 42.37011 -0.1906 40.37290



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 19.75995 16.45717 -1.1076 32.67934
February 454.00000 19.89513 18.28369 -1.0076 28.77049
March 514.00000 20.32205 18.09895 -0.8292 21.90154
April 485.00000 21.64354 16.92740 -0.3777 13.41094
May 508.00000 23.12498 22.02858 -0.8986 25.64001
June 496.00000 24.00008 33.98818 -0.4403 11.29232
July 497.00000 24.10103 42.46829 -0.3700 9.46992
August 514.00000 23.56905 38.59388 -0.6268 16.38027
September 485.00000 21.65163 31.72430 -1.4553 49.63745
October 502.00000 20.17788 25.08745 -0.8140 21.43378
November 489.00000 19.82779 17.65753 -1.0533 30.47315
December 497.00000 19.75747 13.75025 -1.1161 32.97691
           
Annual Sum or Average 5943.00000 21.50166 24.65358 -0.8393 24.41620
Minimum of Months 454.00000 19.75747 13.75025 -1.4553 9.46992
Maximum of Months 514.00000 24.10103 42.46829 -0.3700 49.63745



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.800638E+09 2130.09 23-JAN-07:10 105.99 0.413756E+10 0.00 0.493819E+10 0.74 5.27 27-JAN-08:00 0.00 0.00
February 0.105535E+10 2199.08 16-FEB-13:10 139.19 0.545367E+10 0.00 0.650902E+10 1.07 5.27 09-FEB-18:00 0.00 0.00
March 0.138149E+10 16815.09 31-MAR-15:25 178.47 0.713660E+10 0.00 0.851809E+10 1.24 5.27 15-MAR-19:10 0.00 0.00
April 0.810445E+09 16729.48 20-APR-14:10 88.35 0.418319E+10 0.00 0.499364E+10 0.63 5.27 24-APR-05:50 0.00 0.00
May 0.158820E+11 71951.68 31-MAY-16:10 165.28 0.100787E+12 0.00 0.116669E+12 1.28 7.80 12-MAY-12:40 0.00 0.00
June 0.537315E+11 98270.75 30-JUN-12:20 361.42 0.372921E+12 0.00 0.426653E+12 3.22 7.81 08-JUN-12:20 0.00 0.00
July 0.627465E+11 95817.75 21-JUL-13:10 407.13 0.441715E+12 0.00 0.504461E+12 3.53 7.81 31-JUL-11:00 0.00 0.00
August 0.390987E+11 97309.98 11-AUG-15:20 301.86 0.270456E+12 0.00 0.309555E+12 2.54 7.80 10-AUG-11:00 0.00 0.00
September 0.148729E+10 37996.53 07-SEP-16:00 49.94 0.765319E+10 0.00 0.914048E+10 0.36 6.55 07-SEP-16:00 0.00 0.00
October 0.100353E+10 3024.49 13-OCT-07:10 130.36 0.518403E+10 0.00 0.618756E+10 0.91 5.27 21-OCT-14:00 0.00 0.00
November 0.144579E+10 2625.02 07-NOV-08:00 188.97 0.747262E+10 0.00 0.891840E+10 1.36 5.27 06-NOV-20:40 0.00 0.00
December 0.635973E+09 3192.72 27-DEC-13:00 83.30 0.328563E+10 0.00 0.392160E+10 0.58 5.27 09-DEC-08:40 0.00 0.00
                         
Annual Sum or Average 0.180079E+12     2200.27 0.123039E+13 0.00 0.141046E+13 1.46     0.00 0.00
Minimum of Months 0.635973E+09 2130.09   49.94 0.328563E+10 0.00 0.392160E+10 0.36 5.27   0.00 0.00
Maximum of Months 0.627465E+11 98270.75   407.13 0.441715E+12 0.00 0.504461E+12 3.53 7.81   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 0.00
May 0.160569E+09 67655.01 31-MAY-16:00 0.67 0.122846E+10 0.00 0.138903E+10 0.01 7.69 31-MAY-15:40 0.00 0.00
June 0.887241E+10 98270.75 30-JUN-12:20 32.00 0.667593E+11 0.00 0.756317E+11 0.33 7.73 21-JUN-13:30 0.00 0.00
July 0.166288E+11 95817.75 21-JUL-13:10 61.83 0.125238E+12 0.00 0.141867E+12 0.63 7.72 11-JUL-09:50 0.00 0.00
August 0.744225E+10 97309.98 11-AUG-15:20 28.17 0.562403E+11 0.00 0.636826E+11 0.29 7.74 25-AUG-13:40 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 0.00
                         
Annual Sum or Average 0.331040E+11     122.67 0.249466E+12 0.00 0.282570E+12 0.11     0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.166288E+11 98270.75   61.83 0.125238E+12 0.00 0.141867E+12 0.63 7.74   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.484481E+10 744.00 3201.90 21-JAN-21:00 166456.17 27-JAN-22:10 21.26 18.33 14.60
February 0.858457E+10 672.00 6485.59 09-FEB-02:00 315866.41 09-FEB-22:10 24.06 18.33 14.60
March 0.156022E+11 744.00 20908.93 20-MAR-14:10 596311.84 31-MAR-23:30 27.05 18.33 14.59
April 0.495579E+11 720.00 49248.27 17-APR-12:00 636299.63 22-APR-18:11 30.17 18.38 14.59
May 0.457695E+11 744.00 49248.27 06-MAY-14:00 329375.52 31-MAY-24:00 22.26 18.55 14.59
June 0.105551E+12 720.00 49248.27 01-JUN-10:50 480476.88 30-JUN-23:23 27.24 20.57 14.60
July 0.122396E+12 744.00 49248.27 01-JUL-00:10 632771.82 31-JUL-23:42 31.70 22.16 14.60
August 0.119988E+12 744.00 49248.27 01-AUG-00:05 668280.46 11-AUG-21:02 33.58 21.37 14.60
September 0.220660E+11 720.00 49248.27 02-SEP-15:00 313097.78 30-SEP-24:00 21.94 18.33 14.55
October 0.169278E+11 744.00 38004.44 01-OCT-15:00 443136.80 31-OCT-23:30 24.41 18.33 14.57
November 0.116791E+11 720.00 6519.77 18-NOV-04:00 455055.39 03-NOV-21:10 26.85 18.33 14.60
December 0.148699E+11 744.00 15869.97 24-DEC-12:00 597904.32 27-DEC-22:10 29.53 18.33 14.60
                   
Annual Sum or Average 0.537837E+12 8760.00         26.69 19.12 14.59
Minimum of Months 0.484481E+10 672.00 3201.90   166456.17   21.26 18.33 14.55
Maximum of Months 0.122396E+12 744.00 49248.27   668280.46   33.58 22.16 14.60



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:02 199138.22 28-JAN-09:30 21.03 21.02 0.79
February 0.00 0.00 0.00 01-FEB-00:03 199160.01 17-FEB-22:00 20.98 20.96 1.50
March 0.00 0.00 0.00 01-MAR-00:05 199175.29 18-MAR-10:20 20.97 20.94 1.58
April 0.00 0.00 0.00 01-APR-00:10 199156.85 08-APR-10:00 20.97 20.95 0.90
May 49165367.13 67.98 1067.41 31-MAY-15:00 897756.60 31-MAY-15:40 21.18 20.95 9.29
June 0.945561E+09 293.32 14645.28 29-JUN-10:20 1040138.40 21-JUN-15:10 22.12 21.23 24.08
July 0.182691E+10 335.53 14645.28 03-JUL-14:50 1040216.03 21-JUL-12:50 22.21 21.14 26.08
August 0.643853E+09 213.73 14645.28 23-AUG-14:30 1039192.58 11-AUG-14:40 21.75 21.13 18.21
September 735029.75 4.17 123.76 07-SEP-16:00 297210.29 07-SEP-16:00 21.01 20.99 1.65
October 0.00 0.00 0.00 01-OCT-00:10 199180.66 28-OCT-07:40 20.93 20.91 1.10
November 0.00 0.00 0.00 01-NOV-00:10 199186.81 22-NOV-19:30 21.00 20.96 1.68
December 0.00 0.00 0.00 01-DEC-00:10 199172.79 23-DEC-14:00 20.95 20.93 0.84
                   
Annual Sum or Average 0.346622E+10 914.72         21.26 21.01 7.36
Minimum of Months 0.00 0.00 0.00   199138.22   20.93 20.91 0.79
Maximum of Months 0.182691E+10 335.53 14645.28   1040216.03   22.21 21.23 26.08



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 21.03 21.03 0.00
February 0.00 0.00 0.00 01-FEB-00:03 0.00 01-FEB-00:03 20.98 20.98 0.00
March 0.00 0.00 0.00 01-MAR-00:05 0.00 01-MAR-00:05 20.97 20.97 0.00
April 0.00 0.00 0.00 01-APR-00:10 0.00 01-APR-00:10 20.97 20.97 0.00
May 304506.93 0.17 507.51 31-MAY-15:40 897756.60 31-MAY-15:40 21.18 21.18 0.01
June 0.393773E+09 19.00 14645.28 29-JUN-10:20 1040138.40 21-JUN-15:10 22.12 22.01 1.34
July 0.311589E+09 33.83 14645.28 03-JUL-14:50 1040216.03 21-JUL-12:50 22.21 22.02 2.31
August 0.151208E+09 13.67 14645.28 23-AUG-14:30 1039192.58 11-AUG-14:40 21.75 21.67 0.93
September 0.00 0.00 0.00 01-SEP-00:10 0.00 01-SEP-00:10 21.01 21.01 0.00
October 0.00 0.00 0.00 01-OCT-00:10 0.00 01-OCT-00:10 20.93 20.93 0.00
November 0.00 0.00 0.00 01-NOV-00:10 0.00 01-NOV-00:10 21.00 21.00 0.00
December 0.00 0.00 0.00 01-DEC-00:10 0.00 01-DEC-00:10 20.95 20.95 0.00
                   
Annual Sum or Average 0.856875E+09 66.67         21.26 21.23 0.39
Minimum of Months 0.00 0.00 0.00   0.00   20.93 20.93 0.00
Maximum of Months 0.393773E+09 33.83 14645.28   1040216.03   22.21 22.02 2.31



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.961452E+12 0.00 637.47 2326765.49 17-JAN-04:01 0.00 36.43 75.37 2.06 0.00 0.09 0.57 17-JAN-04:01
February 0.579344E+12 0.00 556.89 2226751.33 27-FEB-07:10 0.00 35.24 74.19 1.33 0.00 0.06 0.55 27-FEB-07:10
March 0.295569E+12 0.00 571.47 1866112.97 03-MAR-06:01 0.00 33.45 70.52 0.61 0.00 0.03 0.46 03-MAR-06:01
April 0.675141E+11 0.00 334.83 1830111.06 03-APR-05:01 0.00 28.97 52.59 0.13 0.00 0.01 0.45 03-APR-05:01
May 0.140945E+10 0.00 46.05 253346.90 27-MAY-05:03 0.00 25.55 28.95 0.00 0.00 0.00 0.06 27-MAY-05:03
June 1487975.19 0.00 1.67 1536.22 02-JUN-06:10 0.00 23.01 23.14 0.00 0.00 0.00 0.00 02-JUN-06:10
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 23.00 23.00 0.00 0.00 0.00 0.00 01-JUL-00:10
August 0.105999E+10 0.00 22.63 253375.85 31-AUG-06:10 0.00 23.22 24.88 0.00 0.00 0.00 0.06 31-AUG-06:10
September 0.197939E+11 0.00 228.14 1596247.77 30-SEP-05:01 0.00 27.07 43.88 0.04 0.00 0.00 0.39 30-SEP-05:01
October 0.192345E+12 0.00 493.15 1954057.91 30-OCT-04:01 0.00 30.70 63.55 0.37 0.00 0.02 0.48 30-OCT-04:01
November 0.735908E+12 0.00 591.25 2094081.98 06-NOV-05:01 0.00 35.41 73.66 1.57 0.00 0.07 0.52 06-NOV-05:01
December 0.105900E+13 0.00 649.48 2047130.68 20-DEC-06:01 0.00 36.89 76.20 2.24 0.00 0.10 0.51 20-DEC-06:01
                           
Annual Sum or Average 0.391340E+13 0.00 4133.04     0.00 29.88 52.36 0.69 0.00 0.03    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 23.00 23.00 0.00 0.00 0.00 0.00  
Maximum of Months 0.105900E+13 0.00 649.48 2326765.49   0.00 36.89 76.20 2.24 0.00 0.10 0.57  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 21.26 21.26 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:03 0.00 24.06 24.06 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:05 0.00 27.05 27.05 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 30.17 30.17 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:10 0.00 22.26 22.26 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 27.24 27.24 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:10 0.00 31.70 31.70 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:05 0.00 33.58 33.58 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:10 0.00 21.94 21.94 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 24.41 24.41 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 26.85 26.85 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 29.53 29.53 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 26.69 26.69 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 21.26 21.26 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 33.58 33.58 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 4159758.06 0.00 55.25 4159758.06 0.00 0.00 0.00 0.00 192.90 25-JAN-11:20 192.90 25-JAN-11:20 0.00 0.00 0.00
February 15111421.04 0.00 86.86 15111421.04 0.00 0.00 0.00 0.00 3489.01 09-FEB-08:20 3489.01 09-FEB-08:20 0.00 0.00 0.00
March 30970039.96 0.00 90.85 30970039.96 0.00 0.00 0.00 0.00 6033.83 24-MAR-07:10 6033.83 24-MAR-07:10 0.00 0.00 0.00
April 84166107.27 0.00 36.19 84166107.27 0.00 0.00 0.00 0.00 9746.96 20-APR-14:00 9746.96 20-APR-14:00 0.00 0.00 0.00
May 0.915031E+10 0.00 155.21 0.915031E+10 0.00 0.00 0.00 0.00 76209.13 31-MAY-16:00 76209.13 31-MAY-16:00 0.00 0.00 0.00
June 0.428501E+11 0.00 352.87 0.427169E+11 0.00 0.00 0.00 0.00 117467.01 30-JUN-12:20 110341.72 20-JUN-15:30 0.00 0.00 0.00
July 0.576274E+11 0.00 388.95 0.574392E+11 0.00 0.00 0.00 0.00 124106.52 03-JUL-15:00 117232.56 11-JUL-15:30 0.00 0.00 0.00
August 0.329116E+11 0.00 292.11 0.329116E+11 0.00 0.00 0.00 0.00 117653.67 11-AUG-15:20 117653.67 11-AUG-15:20 0.00 0.00 0.00
September 0.561326E+09 0.00 41.89 0.561326E+09 0.00 0.00 0.00 0.00 22968.65 07-SEP-16:00 22968.65 07-SEP-16:00 0.00 0.00 0.00
October 17713995.31 0.00 81.61 17713995.31 0.00 0.00 0.00 0.00 8787.15 13-OCT-07:10 8787.15 13-OCT-07:10 0.00 0.00 0.00
November 20285948.10 0.00 117.72 20285948.10 0.00 0.00 0.00 0.00 2803.79 16-NOV-08:20 2803.79 16-NOV-08:20 0.00 0.00 0.00
December 5297400.63 0.00 45.78 5297400.63 0.00 0.00 0.00 0.00 1588.60 26-DEC-08:30 1588.60 26-DEC-08:30 0.00 0.00 0.00
                               
Annual Sum or Average 0.143278E+12 0.00 1745.29 0.142957E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 4159758.06 0.00 36.19 4159758.06 0.00 0.00 0.00 0.00 192.90   192.90   0.00 0.00 0.00
Maximum of Months 0.576274E+11 0.00 388.95 0.574392E+11 0.00 0.00 0.00 0.00 124106.52   117653.67   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 16680259.29 0.00 41.04 16680259.29 0.00 0.00 0.00 0.00 754.28 07-JAN-12:10 754.28 07-JAN-12:10 0.00 0.00 0.00
February 36563613.89 0.00 64.08 36563613.89 0.00 0.00 0.00 0.00 2605.87 15-FEB-12:20 2605.87 15-FEB-12:20 0.00 0.00 0.00
March 0.171794E+09 0.00 78.90 0.171794E+09 0.00 0.00 0.00 0.00 148418.29 31-MAR-15:25 148418.29 31-MAR-15:25 0.00 0.00 0.00
April 0.598701E+09 0.00 46.24 0.598701E+09 0.00 0.00 0.00 0.00 73577.05 20-APR-14:00 73577.05 20-APR-14:00 0.00 0.00 0.00
May 0.829991E+11 0.00 152.64 0.829991E+11 0.00 0.00 0.00 0.00 715353.03 31-MAY-16:00 715353.03 31-MAY-16:00 0.00 0.00 0.00
June 0.373115E+12 0.00 328.72 0.372000E+12 0.00 0.00 0.00 0.00 1115119.69 30-JUN-12:20 1037190.27 30-JUN-14:30 0.00 0.00 0.00
July 0.481717E+12 0.00 348.41 0.480453E+12 0.00 0.00 0.00 0.00 1064825.92 21-JUL-14:40 1064825.92 21-JUL-14:40 0.00 0.00 0.00
August 0.258144E+12 0.00 256.47 0.258144E+12 0.00 0.00 0.00 0.00 1044142.88 11-AUG-15:40 1044142.88 11-AUG-15:40 0.00 0.00 0.00
September 0.476980E+10 0.00 36.86 0.476980E+10 0.00 0.00 0.00 0.00 199182.86 07-SEP-16:00 199182.86 07-SEP-16:00 0.00 0.00 0.00
October 31782058.86 0.00 77.19 31782058.86 0.00 0.00 0.00 0.00 3423.87 03-OCT-10:10 3423.87 03-OCT-10:10 0.00 0.00 0.00
November 25233660.08 0.00 64.39 25233660.08 0.00 0.00 0.00 0.00 1533.43 03-NOV-20:50 1533.43 03-NOV-20:50 0.00 0.00 0.00
December 6679649.85 0.00 27.58 6679649.85 0.00 0.00 0.00 0.00 691.37 23-DEC-12:10 691.37 23-DEC-12:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.120163E+13 0.00 1522.53 0.119925E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 6679649.85 0.00 27.58 6679649.85 0.00 0.00 0.00 0.00 691.37   691.37   0.00 0.00 0.00
Maximum of Months 0.481717E+12 0.00 348.41 0.480453E+12 0.00 0.00 0.00 0.00 1115119.69   1064825.92   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 686372.80 0.00 5.84 686372.80 0.00 0.00 0.00 0.00 884.01 09-JAN-06:04 884.01 09-JAN-06:04 0.00 0.00 0.00
February 4108599.94 0.00 21.03 4108599.94 0.00 0.00 0.00 0.00 151.84 06-FEB-17:10 151.84 06-FEB-17:10 0.00 0.00 0.00
March 14499805.83 0.00 41.82 14499805.83 0.00 0.00 0.00 0.00 436.47 11-MAR-12:50 436.47 11-MAR-12:50 0.00 0.00 0.00
April 48164889.81 0.00 47.83 48164889.81 0.00 0.00 0.00 0.00 3688.47 22-APR-14:00 3688.47 22-APR-14:00 0.00 0.00 0.00
May 0.797518E+10 0.00 146.00 0.797518E+10 0.00 0.00 0.00 0.00 78760.34 31-MAY-16:00 78760.34 31-MAY-16:00 0.00 0.00 0.00
June 0.386869E+11 0.00 323.69 0.385602E+11 0.00 0.00 0.00 0.00 126537.62 30-JUN-12:30 119318.70 29-JUN-14:40 0.00 0.00 0.00
July 0.499574E+11 0.00 342.54 0.498395E+11 0.00 0.00 0.00 0.00 123062.32 21-JUL-14:40 123062.32 21-JUL-14:40 0.00 0.00 0.00
August 0.258079E+11 0.00 247.31 0.258079E+11 0.00 0.00 0.00 0.00 114221.20 11-AUG-15:40 114221.20 11-AUG-15:40 0.00 0.00 0.00
September 0.360093E+09 0.00 38.13 0.360093E+09 0.00 0.00 0.00 0.00 15976.34 07-SEP-16:00 15976.34 07-SEP-16:00 0.00 0.00 0.00
October 9732057.36 0.00 29.24 9732057.36 0.00 0.00 0.00 0.00 565.00 03-OCT-11:00 565.00 03-OCT-11:00 0.00 0.00 0.00
November 661238.14 0.00 1.48 661238.14 0.00 0.00 0.00 0.00 2118.32 06-NOV-06:01 2118.32 06-NOV-06:01 0.00 0.00 0.00
December 589027.74 0.00 9.00 589027.74 0.00 0.00 0.00 0.00 105.88 23-DEC-12:10 105.88 23-DEC-12:10 0.00 0.00 0.00
                               
Annual Sum or Average 0.122866E+12 0.00 1253.90 0.122621E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 589027.74 0.00 1.48 589027.74 0.00 0.00 0.00 0.00 105.88   105.88   0.00 0.00 0.00
Maximum of Months 0.499574E+11 0.00 342.54 0.498395E+11 0.00 0.00 0.00 0.00 126537.62   123062.32   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 11866734.55 0.00 96.69 11866734.55 0.00 0.00 0.00 0.00 435.45 18-JAN-08:20 435.45 18-JAN-08:20 0.00 0.00 0.00
February 23795020.82 0.00 129.53 23795020.82 0.00 0.00 0.00 0.00 3404.76 10-FEB-17:10 3404.76 10-FEB-17:10 0.00 0.00 0.00
March 30465001.10 0.00 166.68 30465001.10 0.00 0.00 0.00 0.00 2296.38 27-MAR-16:10 2296.38 27-MAR-16:10 0.00 0.00 0.00
April 8754644.20 0.00 50.92 8754644.20 0.00 0.00 0.00 0.00 3121.74 03-APR-16:10 3121.74 03-APR-16:10 0.00 0.00 0.00
May 0.245919E+10 0.00 61.56 0.245919E+10 0.00 0.00 0.00 0.00 37984.93 31-MAY-16:00 37984.93 31-MAY-16:00 0.00 0.00 0.00
June 0.179986E+11 0.00 230.39 0.179838E+11 0.00 0.00 0.00 0.00 52173.09 13-JUN-13:20 52173.09 13-JUN-13:20 0.00 0.00 0.00
July 0.276962E+11 0.00 254.71 0.275970E+11 0.00 0.00 0.00 0.00 63402.65 03-JUL-15:00 58602.25 31-JUL-15:00 0.00 0.00 0.00
August 0.149942E+11 0.00 187.92 0.149707E+11 0.00 0.00 0.00 0.00 58381.21 27-AUG-19:02 58381.21 27-AUG-19:02 0.00 0.00 0.00
September 23690172.40 0.00 9.62 23690172.40 0.00 0.00 0.00 0.00 6993.92 07-SEP-16:00 6993.92 07-SEP-16:00 0.00 0.00 0.00
October 25591816.49 0.00 100.97 25591816.49 0.00 0.00 0.00 0.00 5568.38 24-OCT-16:10 5568.38 24-OCT-16:10 0.00 0.00 0.00
November 40371042.59 0.00 163.17 40371042.59 0.00 0.00 0.00 0.00 5520.10 07-NOV-08:00 5520.10 07-NOV-08:00 0.00 0.00 0.00
December 19180840.16 0.00 70.47 19180840.16 0.00 0.00 0.00 0.00 10740.30 27-DEC-13:00 10740.30 27-DEC-13:00 0.00 0.00 0.00
                               
Annual Sum or Average 0.633319E+11 0.00 1522.64 0.631944E+11 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 8754644.20 0.00 9.62 8754644.20 0.00 0.00 0.00 0.00 435.45   435.45   0.00 0.00 0.00
Maximum of Months 0.276962E+11 0.00 254.71 0.275970E+11 0.00 0.00 0.00 0.00 63402.65   58602.25   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.308256E+12 0.784025E+11 744.00 0.301249E+12 0.700751E+10 0.00 0.33 26-JAN-22:02 0.27 12-JAN-08:00 125673.17 26-JAN-22:02 122404.19 25-JAN-22:02 4063.49 12-JAN-08:20 31574.40 26-JAN-22:02 0.00
February 0.509104E+12 0.122315E+12 672.00 0.495535E+12 0.135690E+11 0.00 0.55 09-FEB-22:03 0.49 27-FEB-07:03 219926.86 09-FEB-22:03 213861.82 09-FEB-22:03 7632.92 18-FEB-11:00 52389.74 09-FEB-22:03 0.00
March 0.820245E+12 0.188807E+12 744.00 0.798976E+12 0.212687E+11 0.00 0.94 31-MAR-23:55 0.71 01-MAR-07:03 403729.19 31-MAR-23:55 393068.19 31-MAR-23:55 11245.65 04-MAR-08:70 89198.80 31-MAR-23:55 0.00
April 0.104501E+13 0.231992E+12 720.00 0.102176E+13 0.232499E+11 0.00 0.95 21-APR-16:00 0.37 30-APR-24:00 410632.67 30-APR-23:00 399828.35 20-APR-21:02 12940.35 08-APR-09:00 97096.95 22-APR-14:00 0.00
May 0.334672E+12 0.850059E+11 744.00 0.327272E+12 0.739926E+10 0.00 0.54 31-MAY-24:00 0.31 27-MAY-07:00 216071.74 31-MAY-24:00 211325.31 31-MAY-24:00 4746.43 31-MAY-24:00 51639.52 31-MAY-24:00 0.00
June 0.567000E+12 0.146203E+12 720.00 0.556845E+12 0.101557E+11 0.00 0.75 30-JUN-23:33 0.53 01-JUN-06:10 308610.59 30-JUN-24:00 303247.18 30-JUN-23:33 7127.41 27-JUN-12:10 79034.78 30-JUN-15:00 0.00
July 0.835821E+12 0.217535E+12 744.00 0.823309E+12 0.125121E+11 0.00 0.96 31-JUL-23:13 0.74 01-JUL-06:10 399351.33 31-JUL-24:00 395739.59 31-JUL-24:00 10663.16 31-JUL-06:10 115263.52 29-JUL-17:00 0.00
August 0.108747E+13 0.265688E+12 744.00 0.106764E+13 0.198302E+11 0.00 1.00 02-AUG-13:00 0.37 31-AUG-24:00 413495.10 30-AUG-22:00 403423.39 11-AUG-21:23 14957.31 08-AUG-06:05 130103.91 11-AUG-18:00 0.00
September 0.324343E+12 0.817888E+11 720.00 0.316483E+12 0.785976E+10 0.00 0.54 30-SEP-24:00 0.31 29-SEP-07:00 216497.79 30-SEP-24:00 210601.19 30-SEP-24:00 5896.61 30-SEP-24:00 51663.46 30-SEP-24:00 0.00
October 0.577297E+12 0.138382E+12 744.00 0.563444E+12 0.138531E+11 0.00 0.74 31-OCT-24:00 0.52 31-OCT-07:00 308470.48 31-OCT-24:00 301600.96 31-OCT-24:00 7866.20 30-OCT-09:00 70753.29 31-OCT-24:00 0.00
November 0.791578E+12 0.182390E+12 720.00 0.771693E+12 0.198846E+11 0.00 0.76 24-NOV-22:02 0.72 30-NOV-07:03 315513.02 24-NOV-22:02 306687.77 07-NOV-22:02 11874.53 27-NOV-08:10 72053.02 24-NOV-22:02 0.00
December 0.106596E+13 0.237059E+12 744.00 0.103953E+13 0.264335E+11 0.00 0.95 27-DEC-22:02 0.91 01-DEC-07:04 410622.08 27-DEC-22:02 398123.62 26-DEC-22:02 16478.19 12-DEC-17:00 90404.20 27-DEC-22:02 0.00
                                       
Annual Sum or Average 0.826676E+13 0.197557E+13 8760.00 0.808374E+13 0.183023E+12 0.00                         0.00
Minimum of Months 0.308256E+12 0.784025E+11 672.00 0.301249E+12 0.700751E+10 0.00 0.33   0.27   125673.17   122404.19   4063.49   31574.40   0.00
Maximum of Months 0.108747E+13 0.265688E+12 744.00 0.106764E+13 0.264335E+11 0.00 1.00   0.91   413495.10   403423.39   16478.19   130103.91   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.121010E+10 0.379589E+09 623.60 0.121010E+10 -0.0 0.00 0.18 28-JAN-21:19 0.00 01-JAN-00:02 1242.08 28-JAN-21:19 1242.08 28-JAN-21:19 0.00 17-JAN-17:30 368.25 28-JAN-21:19 0.00
February 0.667895E+10 0.179374E+10 672.00 0.667895E+10 -0.0 0.00 0.44 16-FEB-16:10 0.18 27-FEB-07:02 3548.53 09-FEB-16:00 3548.53 09-FEB-16:00 0.00 09-FEB-01:10 905.41 16-FEB-16:10 0.00
March 0.137054E+11 0.345034E+10 744.00 0.137054E+11 0.00 0.00 0.86 31-MAR-23:55 0.45 01-MAR-07:02 7276.28 31-MAR-23:55 7276.28 31-MAR-23:55 0.00 09-MAR-22:07 1778.74 31-MAR-23:55 0.00
April 0.196558E+11 0.463982E+10 720.00 0.196558E+11 0.00 0.00 0.99 08-APR-18:37 0.31 30-APR-24:00 8957.06 22-APR-18:40 8957.06 22-APR-18:40 0.00 01-APR-19:50 2077.10 21-APR-18:10 0.00
May 0.555123E+10 0.145338E+10 744.00 0.555107E+10 158549.04 0.00 0.46 31-MAY-24:00 0.16 27-MAY-07:00 4025.32 31-MAY-24:00 4025.32 31-MAY-24:00 17.16 16-MAY-16:10 969.46 31-MAY-24:00 0.00
June 0.107182E+11 0.275171E+10 720.00 0.106459E+11 72247797.04 0.00 0.65 30-JUN-23:15 0.42 01-JUN-06:10 5956.95 30-JUN-23:03 5918.00 30-JUN-23:15 250.21 27-JUN-16:00 1564.46 30-JUN-15:00 0.00
July 0.162310E+11 0.417846E+10 744.00 0.160822E+11 0.148853E+09 0.00 0.85 31-JUL-23:23 0.62 01-JUL-06:40 7845.22 31-JUL-23:40 7831.17 31-JUL-23:40 323.23 26-JUL-15:00 2269.08 21-JUL-16:00 0.00
August 0.210293E+11 0.512262E+10 744.00 0.209098E+11 0.119495E+09 0.00 0.97 27-AUG-18:45 0.31 31-AUG-24:00 8930.31 27-AUG-18:45 8930.31 27-AUG-18:45 249.58 03-AUG-14:00 2681.85 11-AUG-18:10 0.00
September 0.485127E+10 0.125028E+10 720.00 0.483482E+10 16444539.89 0.00 0.43 30-SEP-24:00 0.12 30-SEP-07:00 3465.66 30-SEP-24:00 3465.66 30-SEP-24:00 98.64 05-SEP-15:40 890.47 30-SEP-24:00 0.00
October 0.898064E+10 0.229059E+10 744.00 0.898038E+10 256198.39 0.00 0.61 31-OCT-24:00 0.29 30-OCT-06:05 4996.37 31-OCT-24:00 4996.37 31-OCT-24:00 41.30 02-OCT-16:10 1267.83 31-OCT-24:00 0.00
November 0.123109E+11 0.316542E+10 720.00 0.123109E+11 -0.0 0.00 0.66 19-NOV-15:23 0.47 30-NOV-07:02 5396.41 19-NOV-15:28 5396.41 19-NOV-15:28 0.00 05-NOV-07:17 1368.72 19-NOV-15:23 0.00
December 0.174195E+11 0.434024E+10 744.00 0.174195E+11 0.00 0.00 0.83 24-DEC-13:00 0.68 15-DEC-07:02 7214.04 24-DEC-17:57 7214.04 24-DEC-17:57 0.00 22-DEC-01:00 1727.22 24-DEC-13:10 0.00
                                       
Annual Sum or Average 0.138342E+12 0.348162E+11 8639.60 0.137985E+12 0.357455E+09 0.00                         0.00
Minimum of Months 0.121010E+10 0.379589E+09 623.60 0.121010E+10 -0.0 0.00 0.18   0.00   1242.08   1242.08   0.00   368.25   0.00
Maximum of Months 0.210293E+11 0.512262E+10 744.00 0.209098E+11 0.148853E+09 0.00 0.99   0.68   8957.06   8957.06   323.23   2681.85   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.280579E+09 0.124684E+09 65.71 0.280579E+09 0.00 0.00 0.07 20-JAN-22:08 0.00 01-JAN-00:02 4109.29 20-JAN-22:08 4109.29 20-JAN-22:08 0.00 19-JAN-15:10 1322.94 20-JAN-22:08 0.00
February 0.392410E+11 0.109265E+11 672.00 0.392410E+11 -0.0 0.00 0.38 16-FEB-16:10 0.01 27-FEB-07:02 28435.77 16-FEB-16:10 28435.77 16-FEB-16:10 0.00 08-FEB-17:20 7504.82 16-FEB-16:10 0.00
March 0.106575E+12 0.274346E+11 744.00 0.106575E+12 0.00 0.00 0.78 31-MAR-23:10 0.34 01-MAR-07:02 62700.42 31-MAR-23:20 62700.42 31-MAR-23:20 0.00 23-MAR-13:50 15560.03 31-MAR-23:10 0.00
April 0.173508E+12 0.413917E+11 720.00 0.173508E+12 0.00 0.00 0.96 22-APR-18:50 0.24 30-APR-24:00 83838.45 22-APR-18:50 83838.45 22-APR-18:50 0.00 08-APR-07:40 19811.94 21-APR-18:10 0.00
May 0.478149E+11 0.126315E+11 744.00 0.478131E+11 1802314.15 0.00 0.45 31-MAY-24:00 0.10 27-MAY-07:00 37728.08 31-MAY-24:00 37728.08 31-MAY-24:00 197.88 16-MAY-16:10 9109.73 31-MAY-24:00 0.00
June 0.100243E+12 0.258295E+11 720.00 0.995245E+11 0.718283E+09 0.00 0.65 30-JUN-23:23 0.39 24-JUN-17:00 57014.85 30-JUN-24:00 56834.96 30-JUN-24:00 2489.26 27-JUN-16:00 14974.46 30-JUN-15:00 0.00
July 0.153484E+12 0.396055E+11 744.00 0.152003E+12 0.148168E+10 0.00 0.85 31-JUL-23:13 0.59 06-JUL-06:10 75944.17 31-JUL-23:57 75743.90 31-JUL-24:00 3208.26 26-JUL-15:00 21683.00 21-JUL-16:00 0.00
August 0.198174E+12 0.484333E+11 744.00 0.196981E+12 0.119369E+10 0.00 0.95 10-AUG-19:00 0.24 31-AUG-24:00 83744.25 27-AUG-18:50 83744.25 27-AUG-18:50 2488.82 03-AUG-14:00 25622.01 11-AUG-18:10 0.00
September 0.357572E+11 0.939717E+10 720.00 0.355998E+11 0.157408E+09 0.00 0.35 30-SEP-23:50 0.04 30-SEP-07:00 26661.02 30-SEP-23:50 26661.02 30-SEP-23:50 971.58 05-SEP-15:50 6991.99 30-SEP-23:50 0.00
October 0.623056E+11 0.163021E+11 744.00 0.623027E+11 2918864.81 0.00 0.49 31-OCT-23:20 0.12 30-OCT-06:05 37503.27 31-OCT-23:20 37503.27 31-OCT-23:20 410.80 02-OCT-16:00 9770.89 31-OCT-23:20 0.00
November 0.870645E+11 0.231047E+11 720.00 0.870645E+11 0.00 0.00 0.57 08-NOV-15:50 0.30 27-NOV-07:03 44013.77 08-NOV-15:50 44013.77 08-NOV-15:50 0.00 07-NOV-04:04 11310.47 08-NOV-15:50 0.00
December 0.134264E+12 0.343931E+11 744.00 0.134264E+12 -0.0 0.00 0.74 22-DEC-22:01 0.55 26-DEC-04:01 58842.95 21-DEC-22:05 58842.95 21-DEC-22:10 0.00 12-DEC-01:50 14745.90 22-DEC-22:01 0.00
                                       
Annual Sum or Average 0.113871E+13 0.289574E+12 8081.71 0.113516E+13 0.355578E+10 0.00                         0.00
Minimum of Months 0.280579E+09 0.124684E+09 65.71 0.280579E+09 -0.0 0.00 0.07   0.00   4109.29   4109.29   0.00   1322.94   0.00
Maximum of Months 0.198174E+12 0.484333E+11 744.00 0.196981E+12 0.148168E+10 0.00 0.96   0.59   83838.45   83838.45   3208.26   25622.01   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00 01-JAN-00:02 0.00
February 0.225922E+10 0.645121E+09 554.85 0.225922E+10 0.00 0.00 0.32 09-FEB-16:00 0.00 01-FEB-00:03 2523.50 09-FEB-16:00 2523.50 09-FEB-16:00 0.00 12-FEB-10:30 644.46 09-FEB-16:00 0.00
March 0.863812E+10 0.226614E+10 744.00 0.863812E+10 -0.0 0.00 0.67 31-MAR-23:10 0.22 06-MAR-04:03 5311.20 31-MAR-23:10 5311.20 31-MAR-23:10 0.00 22-MAR-04:01 1347.04 31-MAR-23:10 0.00
April 0.158174E+11 0.381618E+10 720.00 0.158174E+11 0.00 0.00 0.94 22-APR-18:35 0.15 30-APR-24:00 8330.09 20-APR-18:50 8330.09 20-APR-18:50 0.00 15-APR-12:10 1981.30 21-APR-18:10 0.00
May 0.407568E+10 0.108998E+10 739.67 0.407552E+10 162917.44 0.00 0.44 31-MAY-24:00 0.00 27-MAY-02:25 3732.78 31-MAY-24:00 3732.78 31-MAY-24:00 18.75 16-MAY-16:10 903.04 31-MAY-24:00 0.00
June 0.984277E+10 0.254679E+10 720.00 0.977105E+10 71720901.87 0.00 0.64 30-JUN-23:15 0.33 26-JUN-06:10 5674.39 30-JUN-23:03 5649.57 30-JUN-24:00 249.12 27-JUN-16:00 1517.73 30-JUN-15:00 0.00
July 0.151963E+11 0.393569E+10 744.00 0.150483E+11 0.148027E+09 0.00 0.84 31-JUL-23:13 0.55 06-JUL-06:10 7560.65 31-JUL-23:57 7541.86 31-JUL-23:40 320.58 26-JUL-15:00 2189.99 21-JUL-16:00 0.00
August 0.194265E+11 0.477237E+10 744.00 0.193073E+11 0.119171E+09 0.00 0.95 10-AUG-18:50 0.18 31-AUG-24:00 8377.74 27-AUG-18:45 8377.74 27-AUG-18:45 248.84 03-AUG-14:00 2578.82 11-AUG-18:10 0.00
September 0.216028E+10 0.585139E+09 645.54 0.214587E+10 14414658.52 0.00 0.29 02-SEP-18:03 0.00 05-SEP-01:05 2357.28 02-SEP-18:07 2357.28 02-SEP-18:07 95.30 05-SEP-16:00 591.20 02-SEP-18:00 0.00
October 0.400478E+10 0.107875E+10 718.04 0.400453E+10 251329.53 0.00 0.41 31-OCT-23:10 0.00 09-OCT-04:25 3399.41 03-OCT-16:00 3399.41 03-OCT-16:00 36.60 02-OCT-16:00 822.57 03-OCT-16:00 0.00
November 0.671475E+10 0.182245E+10 720.00 0.671475E+10 -0.0 0.00 0.51 08-NOV-15:50 0.17 27-NOV-03:50 3948.77 08-NOV-15:50 3948.77 08-NOV-15:50 0.00 14-NOV-13:00 1027.32 08-NOV-15:50 0.00
December 0.115042E+11 0.299910E+10 744.00 0.115042E+11 -0.0 0.00 0.68 20-DEC-22:02 0.41 04-DEC-00:25 5546.56 19-DEC-22:10 5546.56 19-DEC-22:10 0.00 26-DEC-13:40 1377.92 20-DEC-22:02 0.00
                                       
Annual Sum or Average 0.996400E+11 0.255577E+11 7794.10 0.992863E+11 0.353748E+09 0.00                         0.00
Minimum of Months 0.00 0.00 0.00 0.00 -0.0 0.00 0.00   0.00   0.00   0.00   0.00   0.00   0.00
Maximum of Months 0.194265E+11 0.477237E+10 744.00 0.193073E+11 0.148027E+09 0.00 0.95   0.55   8377.74   8377.74   320.58   2578.82   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.61 0.00 12.61 0.00 921.73 0.00 0.00 0.00
February 55.75 0.00 55.75 0.00 838.48 0.00 0.00 0.00
March 149.11 0.00 149.11 9.18 634.09 0.00 0.00 0.00
April 269.78 5.94 263.84 96.59 348.16 0.00 0.00 0.00
May 413.47 65.74 347.74 308.98 147.46 0.00 0.00 0.00
June 539.47 119.97 419.50 518.37 67.75 0.00 0.00 0.00
July 452.77 73.59 379.18 443.19 82.57 0.00 0.00 0.00
August 289.11 16.16 272.95 227.05 140.77 0.00 0.00 0.00
September 161.29 0.16 161.13 53.83 297.34 0.00 0.00 0.00
October 78.48 0.00 78.48 3.25 556.50 0.00 0.00 0.00
November 24.36 0.00 24.36 0.00 923.84 0.00 0.00 0.00
December 3.83 0.00 3.83 0.00 985.48 0.00 0.00 0.00
                 
Annual Sum or Average 204.90 23.57 181.33 139.19 493.47 0.00 0.00 0.00
Minimum of Months 3.83 0.00 3.83 0.00 67.75 0.00 0.00 0.00
Maximum of Months 539.47 119.97 419.50 518.37 985.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.61 0.00 12.61 0.00 921.73 0.00 0.00 0.00
February 55.75 0.00 55.75 0.00 838.48 0.00 0.00 0.00
March 149.10 0.00 149.10 9.17 634.09 0.00 0.00 0.00
April 269.77 5.94 263.83 96.59 348.17 0.00 0.00 0.00
May 413.47 65.74 347.73 308.97 147.46 0.00 0.00 0.00
June 539.46 119.97 419.49 518.36 67.75 0.00 0.00 0.00
July 452.76 73.59 379.17 443.18 82.57 0.00 0.00 0.00
August 289.11 16.16 272.95 227.04 140.77 0.00 0.00 0.00
September 161.29 0.16 161.13 53.83 297.34 0.00 0.00 0.00
October 78.48 0.00 78.48 3.25 556.51 0.00 0.00 0.00
November 24.36 0.00 24.36 0.00 923.84 0.00 0.00 0.00
December 3.83 0.00 3.83 0.00 985.48 0.00 0.00 0.00
                 
Annual Sum or Average 204.90 23.57 181.33 139.19 493.47 0.00 0.00 0.00
Minimum of Months 3.83 0.00 3.83 0.00 67.75 0.00 0.00 0.00
Maximum of Months 539.46 119.97 419.49 518.36 985.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.61 0.00 12.61 0.00 921.73 0.00 0.00 0.00
February 55.75 0.00 55.75 0.00 838.48 0.00 0.00 0.00
March 149.11 0.00 149.11 9.18 634.09 0.00 0.00 0.00
April 269.77 5.94 263.83 96.59 348.17 0.00 0.00 0.00
May 413.47 65.74 347.73 308.97 147.46 0.00 0.00 0.00
June 539.46 119.97 419.49 518.36 67.75 0.00 0.00 0.00
July 452.76 73.59 379.17 443.19 82.57 0.00 0.00 0.00
August 289.11 16.16 272.95 227.04 140.77 0.00 0.00 0.00
September 161.29 0.16 161.13 53.83 297.34 0.00 0.00 0.00
October 78.48 0.00 78.48 3.25 556.51 0.00 0.00 0.00
November 24.36 0.00 24.36 0.00 923.84 0.00 0.00 0.00
December 3.83 0.00 3.83 0.00 985.48 0.00 0.00 0.00
                 
Annual Sum or Average 204.90 23.57 181.33 139.19 493.47 0.00 0.00 0.00
Minimum of Months 3.83 0.00 3.83 0.00 67.75 0.00 0.00 0.00
Maximum of Months 539.46 119.97 419.49 518.36 985.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.61 0.00 12.61 0.00 921.73 0.00 0.00 0.00
February 55.75 0.00 55.75 0.00 838.48 0.00 0.00 0.00
March 149.10 0.00 149.10 9.17 634.09 0.00 0.00 0.00
April 269.77 5.94 263.83 96.59 348.17 0.00 0.00 0.00
May 413.47 65.74 347.73 308.97 147.46 0.00 0.00 0.00
June 539.46 119.97 419.49 518.36 67.75 0.00 0.00 0.00
July 452.76 73.59 379.17 443.18 82.57 0.00 0.00 0.00
August 289.11 16.16 272.95 227.04 140.77 0.00 0.00 0.00
September 161.29 0.16 161.13 53.83 297.34 0.00 0.00 0.00
October 78.48 0.00 78.48 3.25 556.51 0.00 0.00 0.00
November 24.36 0.00 24.36 0.00 923.84 0.00 0.00 0.00
December 3.83 0.00 3.83 0.00 985.48 0.00 0.00 0.00
                 
Annual Sum or Average 204.90 23.57 181.33 139.19 493.47 0.00 0.00 0.00
Minimum of Months 3.83 0.00 3.83 0.00 67.75 0.00 0.00 0.00
Maximum of Months 539.46 119.97 419.49 518.36 985.48 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 12.61 0.00 12.61 0.00 921.69 0.00 0.00 0.00
February 55.75 0.00 55.75 0.00 838.45 0.00 0.00 0.00
March 149.10 0.00 149.10 9.17 634.07 0.00 0.00 0.00
April 269.76 5.94 263.82 96.59 348.15 0.00 0.00 0.00
May 413.45 65.73 347.72 308.96 147.45 0.00 0.00 0.00
June 539.44 119.96 419.48 518.34 67.75 0.00 0.00 0.00
July 452.74 73.59 379.15 443.17 82.57 0.00 0.00 0.00
August 289.10 16.16 272.94 227.03 140.77 0.00 0.00 0.00
September 161.28 0.16 161.12 53.83 297.32 0.00 0.00 0.00
October 78.48 0.00 78.48 3.25 556.48 0.00 0.00 0.00
November 24.35 0.00 24.35 0.00 923.80 0.00 0.00 0.00
December 3.83 0.00 3.83 0.00 985.44 0.00 0.00 0.00
                 
Annual Sum or Average 204.89 23.57 181.32 139.18 493.45 0.00 0.00 0.00
Minimum of Months 3.83 0.00 3.83 0.00 67.75 0.00 0.00 0.00
Maximum of Months 539.44 119.96 419.48 518.34 985.44 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 36.91 11.62 25.30 3.23 988.28 0.00 0.00 0.00
February 203.96 97.32 106.63 103.21 837.76 0.00 0.00 0.00
March 581.76 294.61 287.15 473.75 625.83 0.00 0.00 0.00
April 799.65 404.54 395.11 716.16 346.57 0.00 0.00 0.00
May 1161.67 653.96 507.71 1244.84 176.10 0.00 0.00 0.00
June 1068.76 497.91 570.85 1187.62 84.43 0.00 0.00 0.00
July 1015.18 491.61 523.57 1156.28 95.51 0.00 0.00 0.00
August 804.09 391.05 413.04 874.67 151.55 0.00 0.00 0.00
September 497.43 217.75 279.68 446.58 303.60 0.00 0.00 0.00
October 262.75 105.43 157.32 177.89 553.59 0.00 0.00 0.00
November 55.89 19.53 36.36 4.25 979.21 0.00 0.00 0.00
December 7.98 1.91 6.07 0.00 1075.58 0.00 0.00 0.00
                 
Annual Sum or Average 543.41 266.77 276.63 535.28 516.52 0.00 0.00 0.00
Minimum of Months 7.98 1.91 6.07 0.00 84.43 0.00 0.00 0.00
Maximum of Months 1161.67 653.96 570.85 1244.84 1075.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 36.91 11.62 25.30 3.23 988.28 0.00 0.00 0.00
February 203.96 97.32 106.63 103.21 837.76 0.00 0.00 0.00
March 581.76 294.61 287.15 473.75 625.83 0.00 0.00 0.00
April 799.65 404.54 395.11 716.16 346.57 0.00 0.00 0.00
May 1161.67 653.96 507.71 1244.84 176.10 0.00 0.00 0.00
June 1068.76 497.91 570.85 1187.62 84.43 0.00 0.00 0.00
July 1015.18 491.61 523.57 1156.28 95.51 0.00 0.00 0.00
August 804.09 391.05 413.04 874.67 151.55 0.00 0.00 0.00
September 497.43 217.75 279.68 446.58 303.60 0.00 0.00 0.00
October 262.75 105.43 157.32 177.89 553.59 0.00 0.00 0.00
November 55.89 19.53 36.36 4.25 979.21 0.00 0.00 0.00
December 7.98 1.91 6.07 0.00 1075.58 0.00 0.00 0.00
                 
Annual Sum or Average 543.41 266.77 276.63 535.28 516.52 0.00 0.00 0.00
Minimum of Months 7.98 1.91 6.07 0.00 84.43 0.00 0.00 0.00
Maximum of Months 1161.67 653.96 570.85 1244.84 1075.58 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 36.91 11.62 25.30 3.23 988.26 0.00 0.00 0.00
February 203.95 97.32 106.63 103.20 837.74 0.00 0.00 0.00
March 581.75 294.60 287.14 473.74 625.82 0.00 0.00 0.00
April 799.64 404.53 395.11 716.15 346.56 0.00 0.00 0.00
May 1161.65 653.95 507.70 1244.82 176.09 0.00 0.00 0.00
June 1068.74 497.90 570.84 1187.60 84.43 0.00 0.00 0.00
July 1015.16 491.60 523.56 1156.26 95.51 0.00 0.00 0.00
August 804.08 391.04 413.04 874.65 151.55 0.00 0.00 0.00
September 497.42 217.74 279.68 446.58 303.60 0.00 0.00 0.00
October 262.74 105.43 157.31 177.88 553.58 0.00 0.00 0.00
November 55.89 19.53 36.36 4.25 979.19 0.00 0.00 0.00
December 7.98 1.91 6.07 0.00 1075.56 0.00 0.00 0.00
                 
Annual Sum or Average 543.40 266.77 276.63 535.27 516.51 0.00 0.00 0.00
Minimum of Months 7.98 1.91 6.07 0.00 84.43 0.00 0.00 0.00
Maximum of Months 1161.65 653.95 570.84 1244.82 1075.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 151.30 99.68 51.62 86.46 815.67 0.00 0.00 0.00
February 520.62 362.15 158.48 429.91 667.13 0.00 0.00 0.00
March 894.02 605.97 288.04 853.13 518.81 0.00 0.00 0.00
April 1090.68 678.51 412.17 1162.56 343.59 0.00 0.00 0.00
May 899.36 466.01 433.35 989.74 183.27 0.00 0.00 0.00
June 821.15 336.57 484.58 929.36 97.13 0.00 0.00 0.00
July 791.15 344.55 446.61 916.41 102.90 0.00 0.00 0.00
August 819.32 451.54 367.78 933.93 153.99 0.00 0.00 0.00
September 662.16 398.78 263.37 682.88 273.77 0.00 0.00 0.00
October 476.75 302.49 174.27 420.38 450.66 0.00 0.00 0.00
November 255.62 178.49 77.13 163.83 776.18 0.00 0.00 0.00
December 45.37 31.98 13.39 7.81 918.37 0.00 0.00 0.00
                 
Annual Sum or Average 618.80 354.19 264.61 631.89 440.69 0.00 0.00 0.00
Minimum of Months 45.37 31.98 13.39 7.81 97.13 0.00 0.00 0.00
Maximum of Months 1090.68 678.51 484.58 1162.56 918.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 151.30 99.68 51.62 86.46 815.67 0.00 0.00 0.00
February 520.62 362.14 158.48 429.90 667.13 0.00 0.00 0.00
March 894.01 605.97 288.04 853.12 518.81 0.00 0.00 0.00
April 1090.67 678.50 412.17 1162.55 343.59 0.00 0.00 0.00
May 899.35 466.00 433.35 989.73 183.27 0.00 0.00 0.00
June 821.14 336.56 484.58 929.35 97.13 0.00 0.00 0.00
July 791.15 344.54 446.60 916.40 102.90 0.00 0.00 0.00
August 819.31 451.53 367.78 933.92 153.99 0.00 0.00 0.00
September 662.15 398.78 263.37 682.87 273.77 0.00 0.00 0.00
October 476.75 302.48 174.27 420.38 450.66 0.00 0.00 0.00
November 255.62 178.49 77.13 163.83 776.18 0.00 0.00 0.00
December 45.37 31.98 13.39 7.81 918.37 0.00 0.00 0.00
                 
Annual Sum or Average 618.79 354.19 264.61 631.88 440.69 0.00 0.00 0.00
Minimum of Months 45.37 31.98 13.39 7.81 97.13 0.00 0.00 0.00
Maximum of Months 1090.67 678.50 484.58 1162.55 918.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 151.30 99.68 51.62 86.46 815.67 0.00 0.00 0.00
February 520.62 362.15 158.48 429.91 667.13 0.00 0.00 0.00
March 894.02 605.97 288.04 853.13 518.81 0.00 0.00 0.00
April 1090.68 678.51 412.17 1162.56 343.59 0.00 0.00 0.00
May 899.36 466.01 433.35 989.74 183.27 0.00 0.00 0.00
June 821.15 336.57 484.58 929.36 97.13 0.00 0.00 0.00
July 791.15 344.55 446.61 916.41 102.90 0.00 0.00 0.00
August 819.32 451.54 367.78 933.93 153.99 0.00 0.00 0.00
September 662.16 398.78 263.37 682.88 273.77 0.00 0.00 0.00
October 476.75 302.49 174.27 420.38 450.66 0.00 0.00 0.00
November 255.62 178.49 77.13 163.83 776.18 0.00 0.00 0.00
December 45.37 31.98 13.39 7.81 918.37 0.00 0.00 0.00
                 
Annual Sum or Average 618.80 354.19 264.61 631.89 440.69 0.00 0.00 0.00
Minimum of Months 45.37 31.98 13.39 7.81 97.13 0.00 0.00 0.00
Maximum of Months 1090.68 678.51 484.58 1162.56 918.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 151.30 99.68 51.62 86.46 815.67 0.00 0.00 0.00
February 520.62 362.14 158.48 429.90 667.13 0.00 0.00 0.00
March 894.01 605.97 288.04 853.12 518.81 0.00 0.00 0.00
April 1090.67 678.50 412.17 1162.55 343.59 0.00 0.00 0.00
May 899.35 466.00 433.35 989.73 183.27 0.00 0.00 0.00
June 821.14 336.56 484.58 929.35 97.13 0.00 0.00 0.00
July 791.15 344.54 446.60 916.40 102.90 0.00 0.00 0.00
August 819.31 451.53 367.78 933.92 153.99 0.00 0.00 0.00
September 662.15 398.78 263.37 682.87 273.77 0.00 0.00 0.00
October 476.75 302.48 174.27 420.38 450.66 0.00 0.00 0.00
November 255.62 178.49 77.13 163.83 776.18 0.00 0.00 0.00
December 45.37 31.98 13.39 7.81 918.37 0.00 0.00 0.00
                 
Annual Sum or Average 618.79 354.19 264.61 631.88 440.69 0.00 0.00 0.00
Minimum of Months 45.37 31.98 13.39 7.81 97.13 0.00 0.00 0.00
Maximum of Months 1090.67 678.50 484.58 1162.55 918.37 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 151.29 99.68 51.62 86.45 815.64 0.00 0.00 0.00
February 520.60 362.13 158.47 429.89 667.10 0.00 0.00 0.00
March 893.98 605.95 288.03 853.09 518.79 0.00 0.00 0.00
April 1090.63 678.48 412.15 1162.51 343.58 0.00 0.00 0.00
May 899.32 465.99 433.33 989.70 183.26 0.00 0.00 0.00
June 821.11 336.55 484.56 929.32 97.12 0.00 0.00 0.00
July 791.12 344.53 446.59 916.37 102.89 0.00 0.00 0.00
August 819.28 451.52 367.77 933.88 153.99 0.00 0.00 0.00
September 662.13 398.77 263.36 682.85 273.76 0.00 0.00 0.00
October 476.73 302.47 174.26 420.36 450.64 0.00 0.00 0.00
November 255.61 178.48 77.13 163.83 776.15 0.00 0.00 0.00
December 45.37 31.98 13.39 7.81 918.33 0.00 0.00 0.00
                 
Annual Sum or Average 618.77 354.17 264.60 631.86 440.68 0.00 0.00 0.00
Minimum of Months 45.37 31.98 13.39 7.81 97.12 0.00 0.00 0.00
Maximum of Months 1090.63 678.48 484.56 1162.51 918.33 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.42 3.47 15.95 0.00 1034.75 0.00 0.00 0.00
February 114.63 39.86 74.77 20.75 906.72 0.00 0.00 0.00
March 344.06 147.91 196.15 181.12 685.81 0.00 0.00 0.00
April 816.43 423.08 393.35 742.05 413.51 0.00 0.00 0.00
May 793.84 361.52 432.33 780.12 200.17 0.00 0.00 0.00
June 870.01 370.95 499.06 929.44 111.31 0.00 0.00 0.00
July 727.95 275.37 452.58 779.28 122.64 0.00 0.00 0.00
August 598.30 253.35 344.95 602.04 187.03 0.00 0.00 0.00
September 362.09 151.63 210.46 279.28 331.54 0.00 0.00 0.00
October 141.80 42.63 99.17 45.01 615.10 0.00 0.00 0.00
November 56.74 20.61 36.12 4.93 1026.01 0.00 0.00 0.00
December 5.09 0.54 4.56 0.00 1140.28 0.00 0.00 0.00
                 
Annual Sum or Average 405.24 174.61 230.63 365.11 562.79 0.00 0.00 0.00
Minimum of Months 5.09 0.54 4.56 0.00 111.31 0.00 0.00 0.00
Maximum of Months 870.01 423.08 499.06 929.44 1140.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.42 3.47 15.95 0.00 1034.75 0.00 0.00 0.00
February 114.63 39.86 74.77 20.75 906.72 0.00 0.00 0.00
March 344.06 147.91 196.15 181.12 685.81 0.00 0.00 0.00
April 816.43 423.08 393.35 742.05 413.51 0.00 0.00 0.00
May 793.84 361.52 432.33 780.12 200.17 0.00 0.00 0.00
June 870.01 370.95 499.06 929.44 111.31 0.00 0.00 0.00
July 727.95 275.37 452.58 779.28 122.64 0.00 0.00 0.00
August 598.30 253.35 344.95 602.04 187.03 0.00 0.00 0.00
September 362.09 151.63 210.46 279.28 331.54 0.00 0.00 0.00
October 141.80 42.63 99.17 45.01 615.10 0.00 0.00 0.00
November 56.74 20.61 36.12 4.93 1026.01 0.00 0.00 0.00
December 5.09 0.54 4.56 0.00 1140.28 0.00 0.00 0.00
                 
Annual Sum or Average 405.24 174.61 230.63 365.11 562.79 0.00 0.00 0.00
Minimum of Months 5.09 0.54 4.56 0.00 111.31 0.00 0.00 0.00
Maximum of Months 870.01 423.08 499.06 929.44 1140.28 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 19.42 3.47 15.95 0.00 1034.73 0.00 0.00 0.00
February 114.63 39.86 74.77 20.75 906.70 0.00 0.00 0.00
March 344.06 147.91 196.15 181.11 685.79 0.00 0.00 0.00
April 816.41 423.07 393.34 742.03 413.50 0.00 0.00 0.00
May 793.83 361.51 432.32 780.11 200.16 0.00 0.00 0.00
June 870.00 370.95 499.05 929.43 111.31 0.00 0.00 0.00
July 727.94 275.36 452.58 779.27 122.63 0.00 0.00 0.00
August 598.28 253.35 344.94 602.03 187.03 0.00 0.00 0.00
September 362.08 151.62 210.46 279.27 331.53 0.00 0.00 0.00
October 141.80 42.63 99.17 45.01 615.09 0.00 0.00 0.00
November 56.74 20.61 36.12 4.93 1025.99 0.00 0.00 0.00
December 5.09 0.54 4.56 0.00 1140.26 0.00 0.00 0.00
                 
Annual Sum or Average 405.23 174.61 230.63 365.11 562.78 0.00 0.00 0.00
Minimum of Months 5.09 0.54 4.56 0.00 111.31 0.00 0.00 0.00
Maximum of Months 870.00 423.07 499.05 929.43 1140.26 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.06 0.00 63.06 0.00 4446.52 0.00 0.00 0.00
February 278.75 0.00 278.75 0.00 3985.09 0.00 0.00 0.00
March 745.53 0.00 745.53 64.12 2949.28 0.00 0.00 0.00
April 1348.88 29.70 1319.18 549.79 1562.84 0.00 0.00 0.00
May 2067.38 328.69 1738.69 1573.37 704.17 0.00 0.00 0.00
June 2697.35 599.86 2097.49 2598.51 327.85 0.00 0.00 0.00
July 2263.85 367.97 1895.88 2224.89 402.31 0.00 0.00 0.00
August 1445.56 80.79 1364.77 1158.26 669.52 0.00 0.00 0.00
September 806.46 0.81 805.65 299.39 1365.91 0.00 0.00 0.00
October 392.42 0.00 392.42 27.18 2534.01 0.00 0.00 0.00
November 121.78 0.00 121.78 0.00 4355.06 0.00 0.00 0.00
December 19.13 0.00 19.13 0.00 4685.90 0.00 0.00 0.00
                 
Annual Sum or Average 1024.50 117.84 906.66 712.09 2323.49 0.00 0.00 0.00
Minimum of Months 19.13 0.00 19.13 0.00 327.85 0.00 0.00 0.00
Maximum of Months 2697.35 599.86 2097.49 2598.51 4685.90 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.74 34.85 75.89 9.89 2874.72 0.00 0.00 0.00
February 611.86 291.96 319.90 319.99 2405.91 0.00 0.00 0.00
March 1745.26 883.82 861.44 1443.60 1780.34 0.00 0.00 0.00
April 2398.94 1213.61 1185.33 2167.66 974.58 0.00 0.00 0.00
May 3484.97 1961.86 1523.11 3723.55 512.43 0.00 0.00 0.00
June 3206.25 1493.70 1712.55 3547.92 251.26 0.00 0.00 0.00
July 3045.52 1474.81 1570.70 3449.89 290.86 0.00 0.00 0.00
August 2412.25 1173.13 1239.12 2613.34 454.42 0.00 0.00 0.00
September 1492.27 653.23 839.04 1352.49 860.83 0.00 0.00 0.00
October 788.23 316.28 471.95 551.26 1541.42 0.00 0.00 0.00
November 167.67 58.59 109.08 14.07 2792.14 0.00 0.00 0.00
December 23.95 5.73 18.22 0.00 3102.53 0.00 0.00 0.00
                 
Annual Sum or Average 1630.20 800.31 829.89 1608.11 1482.16 0.00 0.00 0.00
Minimum of Months 23.95 5.73 18.22 0.00 251.26 0.00 0.00 0.00
Maximum of Months 3484.97 1961.86 1712.55 3723.55 3102.53 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 756.51 498.41 258.09 437.52 3997.54 0.00 0.00 0.00
February 2603.17 1810.77 792.40 2168.56 3241.16 0.00 0.00 0.00
March 4470.18 3029.94 1440.24 4276.14 2517.07 0.00 0.00 0.00
April 5453.49 3392.62 2060.87 5805.68 1660.66 0.00 0.00 0.00
May 4496.87 2330.08 2166.79 4928.77 901.38 0.00 0.00 0.00
June 4105.81 1682.87 2422.94 4631.65 480.15 0.00 0.00 0.00
July 3955.83 1722.77 2233.06 4568.16 515.19 0.00 0.00 0.00
August 4096.66 2257.73 1838.93 4658.08 764.17 0.00 0.00 0.00
September 3310.84 1993.96 1316.88 3410.82 1342.71 0.00 0.00 0.00
October 2383.82 1512.47 871.35 2120.62 2163.72 0.00 0.00 0.00
November 1278.12 892.46 385.66 837.64 3736.68 0.00 0.00 0.00
December 226.88 159.92 66.96 40.21 4452.63 0.00 0.00 0.00
                 
Annual Sum or Average 3094.04 1770.98 1323.06 3159.47 2142.52 0.00 0.00 0.00
Minimum of Months 226.88 159.92 66.96 40.21 480.15 0.00 0.00 0.00
Maximum of Months 5453.49 3392.62 2422.94 5805.68 4452.63 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 58.25 10.40 47.86 0.00 2953.48 0.00 0.00 0.00
February 343.89 119.58 224.31 70.41 2523.94 0.00 0.00 0.00
March 1032.18 443.72 588.46 579.92 1840.65 0.00 0.00 0.00
April 2449.26 1269.22 1180.03 2289.94 1082.05 0.00 0.00 0.00
May 2381.51 1084.55 1296.96 2361.83 562.30 0.00 0.00 0.00
June 2610.02 1112.85 1497.17 2809.91 306.72 0.00 0.00 0.00
July 2183.83 826.09 1357.74 2369.30 333.50 0.00 0.00 0.00
August 1794.87 760.04 1034.83 1845.63 496.39 0.00 0.00 0.00
September 1086.25 454.88 631.37 870.17 897.44 0.00 0.00 0.00
October 425.41 127.89 297.52 155.19 1628.85 0.00 0.00 0.00
November 170.21 61.84 108.37 18.56 2816.45 0.00 0.00 0.00
December 15.28 1.61 13.67 0.00 3147.01 0.00 0.00 0.00
                 
Annual Sum or Average 1215.70 523.82 691.88 1118.62 1544.05 0.00 0.00 0.00
Minimum of Months 15.28 1.61 13.67 0.00 306.72 0.00 0.00 0.00
Maximum of Months 2610.02 1269.22 1497.17 2809.91 3147.01 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 63.06 0.00 63.06 0.00 4357.85 0.00 0.00 0.00
February 278.75 0.00 278.75 0.00 3880.84 0.00 0.00 0.00
March 745.53 0.00 745.53 73.54 2836.11 0.00 0.00 0.00
April 1348.88 29.70 1319.18 602.53 1455.99 0.00 0.00 0.00
May 2067.38 328.69 1738.69 1636.97 658.65 0.00 0.00 0.00
June 2697.35 599.86 2097.49 2607.21 316.50 0.00 0.00 0.00
July 2263.85 367.97 1895.88 2232.98 390.22 0.00 0.00 0.00
August 1445.56 80.79 1364.77 1187.31 633.29 0.00 0.00 0.00
September 806.46 0.81 805.65 348.86 1228.54 0.00 0.00 0.00
October 392.42 0.00 392.42 40.99 2379.74 0.00 0.00 0.00
November 121.78 0.00 121.78 0.00 4248.51 0.00 0.00 0.00
December 19.13 0.00 19.13 0.00 4593.23 0.00 0.00 0.00
                 
Annual Sum or Average 1024.50 117.84 906.66 731.74 2239.65 0.00 0.00 0.00
Minimum of Months 19.13 0.00 19.13 0.00 316.50 0.00 0.00 0.00
Maximum of Months 2697.35 599.86 2097.49 2607.21 4593.23 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 110.74 34.85 75.89 10.20 2820.09 0.00 0.00 0.00
February 611.86 291.96 319.90 326.57 2342.73 0.00 0.00 0.00
March 1745.26 883.82 861.44 1466.04 1706.67 0.00 0.00 0.00
April 2398.94 1213.61 1185.33 2203.05 915.00 0.00 0.00 0.00
May 3484.97 1961.86 1523.11 3740.65 490.05 0.00 0.00 0.00
June 3206.25 1493.70 1712.55 3547.14 245.87 0.00 0.00 0.00
July 3045.52 1474.81 1570.70 3448.10 285.71 0.00 0.00 0.00
August 2412.25 1173.13 1239.12 2620.30 438.81 0.00 0.00 0.00
September 1492.27 653.23 839.04 1385.44 791.14 0.00 0.00 0.00
October 788.23 316.28 471.95 571.50 1447.53 0.00 0.00 0.00
November 167.67 58.59 109.08 14.83 2725.38 0.00 0.00 0.00
December 23.95 5.73 18.22 0.00 3046.61 0.00 0.00 0.00
                 
Annual Sum or Average 1630.20 800.31 829.89 1619.78 1433.47 0.00 0.00 0.00
Minimum of Months 23.95 5.73 18.22 0.00 245.87 0.00 0.00 0.00
Maximum of Months 3484.97 1961.86 1712.55 3740.65 3046.61 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 756.51 498.41 258.09 444.19 3914.73 0.00 0.00 0.00
February 2603.17 1810.77 792.40 2197.71 3137.46 0.00 0.00 0.00
March 4470.18 3029.94 1440.24 4318.15 2399.61 0.00 0.00 0.00
April 5453.49 3392.62 2060.87 5844.79 1561.02 0.00 0.00 0.00
May 4496.87 2330.08 2166.79 4949.13 854.10 0.00 0.00 0.00
June 4105.81 1682.87 2422.94 4631.97 467.56 0.00 0.00 0.00
July 3955.83 1722.77 2233.06 4567.33 504.15 0.00 0.00 0.00
August 4096.66 2257.73 1838.93 4666.41 735.83 0.00 0.00 0.00
September 3310.84 1993.96 1316.88 3453.91 1239.10 0.00 0.00 0.00
October 2383.82 1512.47 871.35 2166.74 2024.49 0.00 0.00 0.00
November 1278.12 892.46 385.66 852.18 3633.60 0.00 0.00 0.00
December 226.88 159.92 66.96 41.05 4364.81 0.00 0.00 0.00
                 
Annual Sum or Average 3094.04 1770.98 1323.06 3180.18 2064.70 0.00 0.00 0.00
Minimum of Months 226.88 159.92 66.96 41.05 467.56 0.00 0.00 0.00
Maximum of Months 5453.49 3392.62 2422.94 5844.79 4364.81 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 58.25 10.40 47.86 0.00 2893.23 0.00 0.00 0.00
February 343.89 119.58 224.31 72.55 2460.78 0.00 0.00 0.00
March 1032.18 443.72 588.46 591.51 1770.29 0.00 0.00 0.00
April 2449.26 1269.22 1180.03 2316.91 1018.60 0.00 0.00 0.00
May 2381.51 1084.55 1296.96 2380.46 533.17 0.00 0.00 0.00
June 2610.02 1112.85 1497.17 2810.75 299.09 0.00 0.00 0.00
July 2183.83 826.09 1357.74 2369.66 326.01 0.00 0.00 0.00
August 1794.87 760.04 1034.83 1854.64 477.11 0.00 0.00 0.00
September 1086.25 454.88 631.37 895.32 830.47 0.00 0.00 0.00
October 425.41 127.89 297.52 166.44 1541.24 0.00 0.00 0.00
November 170.21 61.84 108.37 19.60 2749.44 0.00 0.00 0.00
December 15.28 1.61 13.67 0.00 3088.93 0.00 0.00 0.00
                 
Annual Sum or Average 1215.70 523.82 691.88 1127.54 1494.13 0.00 0.00 0.00
Minimum of Months 15.28 1.61 13.67 0.00 299.09 0.00 0.00 0.00
Maximum of Months 2610.02 1269.22 1497.17 2810.75 3088.93 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33779162.98 0.00 33779162.98 0.00 0.246875E+10
February 0.134870E+09 0.00 0.134870E+09 0.00 0.202845E+10
March 0.399368E+09 0.00 0.399368E+09 24575764.90 0.169835E+10
April 0.699261E+09 15396779.91 0.683865E+09 0.250372E+09 0.902442E+09
May 0.110745E+10 0.176070E+09 0.931381E+09 0.827570E+09 0.394946E+09
June 0.139831E+10 0.310967E+09 0.108734E+10 0.134362E+10 0.175604E+09
July 0.121269E+10 0.197112E+09 0.101558E+10 0.118705E+10 0.221159E+09
August 0.774357E+09 43276541.74 0.731081E+09 0.608120E+09 0.377043E+09
September 0.418069E+09 420964.79 0.417648E+09 0.139532E+09 0.770693E+09
October 0.210209E+09 0.00 0.210209E+09 8693370.37 0.149054E+10
November 63130848.20 0.00 63130848.20 0.00 0.239459E+10
December 10246828.08 0.00 10246828.08 0.00 0.263951E+10
           
Annual Sum or Average 0.646174E+10 0.743244E+09 0.571850E+10 0.438953E+10 0.155621E+11
Minimum of Months 10246828.08 0.00 10246828.08 0.00 0.175604E+09
Maximum of Months 0.139831E+10 0.310967E+09 0.108734E+10 0.134362E+10 0.263951E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33778590.32 0.00 33778590.32 0.00 0.246875E+10
February 0.134868E+09 0.00 0.134868E+09 0.00 0.202845E+10
March 0.399362E+09 0.00 0.399362E+09 24573716.27 0.169835E+10
April 0.699251E+09 15396441.43 0.683855E+09 0.250363E+09 0.902445E+09
May 0.110743E+10 0.176066E+09 0.931367E+09 0.827549E+09 0.394946E+09
June 0.139828E+10 0.310961E+09 0.108732E+10 0.134359E+10 0.175604E+09
July 0.121267E+10 0.197108E+09 0.101557E+10 0.118702E+10 0.221159E+09
August 0.774345E+09 43275590.36 0.731070E+09 0.608106E+09 0.377043E+09
September 0.418063E+09 420955.54 0.417642E+09 0.139527E+09 0.770694E+09
October 0.210205E+09 0.00 0.210205E+09 8692651.08 0.149054E+10
November 63129777.96 0.00 63129777.96 0.00 0.239459E+10
December 10246646.75 0.00 10246646.75 0.00 0.263950E+10
           
Annual Sum or Average 0.646164E+10 0.743228E+09 0.571841E+10 0.438942E+10 0.155621E+11
Minimum of Months 10246646.75 0.00 10246646.75 0.00 0.175604E+09
Maximum of Months 0.139828E+10 0.310961E+09 0.108732E+10 0.134359E+10 0.263950E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33778781.21 0.00 33778781.21 0.00 0.246875E+10
February 0.134868E+09 0.00 0.134868E+09 0.00 0.202845E+10
March 0.399364E+09 0.00 0.399364E+09 24574399.15 0.169835E+10
April 0.699255E+09 15396554.26 0.683858E+09 0.250366E+09 0.902444E+09
May 0.110744E+10 0.176067E+09 0.931372E+09 0.827556E+09 0.394946E+09
June 0.139829E+10 0.310963E+09 0.108733E+10 0.134360E+10 0.175604E+09
July 0.121268E+10 0.197109E+09 0.101557E+10 0.118703E+10 0.221159E+09
August 0.774349E+09 43275907.49 0.731073E+09 0.608111E+09 0.377043E+09
September 0.418065E+09 420958.62 0.417644E+09 0.139529E+09 0.770693E+09
October 0.210206E+09 0.00 0.210206E+09 8692890.84 0.149054E+10
November 63130134.71 0.00 63130134.71 0.00 0.239459E+10
December 10246707.19 0.00 10246707.19 0.00 0.263951E+10
           
Annual Sum or Average 0.646167E+10 0.743233E+09 0.571844E+10 0.438946E+10 0.155621E+11
Minimum of Months 10246707.19 0.00 10246707.19 0.00 0.175604E+09
Maximum of Months 0.139829E+10 0.310963E+09 0.108733E+10 0.134360E+10 0.263951E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33778590.32 0.00 33778590.32 0.00 0.246875E+10
February 0.134868E+09 0.00 0.134868E+09 0.00 0.202845E+10
March 0.399362E+09 0.00 0.399362E+09 24573716.27 0.169835E+10
April 0.699251E+09 15396441.43 0.683855E+09 0.250363E+09 0.902445E+09
May 0.110743E+10 0.176066E+09 0.931367E+09 0.827549E+09 0.394946E+09
June 0.139828E+10 0.310961E+09 0.108732E+10 0.134359E+10 0.175604E+09
July 0.121267E+10 0.197108E+09 0.101557E+10 0.118702E+10 0.221159E+09
August 0.774345E+09 43275590.36 0.731070E+09 0.608106E+09 0.377043E+09
September 0.418063E+09 420955.54 0.417642E+09 0.139527E+09 0.770694E+09
October 0.210205E+09 0.00 0.210205E+09 8692651.08 0.149054E+10
November 63129777.96 0.00 63129777.96 0.00 0.239459E+10
December 10246646.75 0.00 10246646.75 0.00 0.263950E+10
           
Annual Sum or Average 0.646164E+10 0.743228E+09 0.571841E+10 0.438942E+10 0.155621E+11
Minimum of Months 10246646.75 0.00 10246646.75 0.00 0.175604E+09
Maximum of Months 0.139828E+10 0.310961E+09 0.108732E+10 0.134359E+10 0.263950E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 33777324.33 0.00 33777324.33 0.00 0.246865E+10
February 0.134863E+09 0.00 0.134863E+09 0.00 0.202837E+10
March 0.399346E+09 0.00 0.399346E+09 24573067.27 0.169828E+10
April 0.699225E+09 15395877.30 0.683829E+09 0.250355E+09 0.902408E+09
May 0.110739E+10 0.176060E+09 0.931332E+09 0.827519E+09 0.394930E+09
June 0.139823E+10 0.310949E+09 0.108728E+10 0.134354E+10 0.175597E+09
July 0.121263E+10 0.197101E+09 0.101553E+10 0.118698E+10 0.221150E+09
August 0.774316E+09 43274004.72 0.731042E+09 0.608084E+09 0.377028E+09
September 0.418047E+09 420940.11 0.417626E+09 0.139523E+09 0.770663E+09
October 0.210197E+09 0.00 0.210197E+09 8692420.60 0.149048E+10
November 63127411.92 0.00 63127411.92 0.00 0.239450E+10
December 10246263.99 0.00 10246263.99 0.00 0.263940E+10
           
Annual Sum or Average 0.646140E+10 0.743200E+09 0.571819E+10 0.438926E+10 0.155615E+11
Minimum of Months 10246263.99 0.00 10246263.99 0.00 0.175597E+09
Maximum of Months 0.139823E+10 0.310949E+09 0.108728E+10 0.134354E+10 0.263940E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 98871890.73 31116260.30 67755630.43 8656274.81 0.264700E+10
February 0.493409E+09 0.235440E+09 0.257969E+09 0.249676E+09 0.202670E+10
March 0.155818E+10 0.789081E+09 0.769099E+09 0.126889E+10 0.167623E+10
April 0.207270E+10 0.104857E+10 0.102414E+10 0.185629E+10 0.898309E+09
May 0.311141E+10 0.175156E+10 0.135985E+10 0.333418E+10 0.471655E+09
June 0.277022E+10 0.129057E+10 0.147965E+10 0.307831E+10 0.218845E+09
July 0.271907E+10 0.131673E+10 0.140234E+10 0.309698E+10 0.255811E+09
August 0.215368E+10 0.104738E+10 0.110630E+10 0.234272E+10 0.405909E+09
September 0.128934E+10 0.564396E+09 0.724939E+09 0.115755E+10 0.786937E+09
October 0.703740E+09 0.282382E+09 0.421358E+09 0.476456E+09 0.148273E+10
November 0.144866E+09 50620862.64 94244678.23 11007767.01 0.253811E+10
December 21386826.70 5119625.73 16267200.97 0.00 0.288085E+10
           
Annual Sum or Average 0.171369E+11 0.841297E+10 0.872391E+10 0.168807E+11 0.162891E+11
Minimum of Months 21386826.70 5119625.73 16267200.97 0.00 0.218845E+09
Maximum of Months 0.311141E+10 0.175156E+10 0.147965E+10 0.333418E+10 0.288085E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 98871890.73 31116260.30 67755630.43 8656274.81 0.264700E+10
February 0.493409E+09 0.235440E+09 0.257969E+09 0.249676E+09 0.202670E+10
March 0.155818E+10 0.789081E+09 0.769099E+09 0.126889E+10 0.167623E+10
April 0.207270E+10 0.104857E+10 0.102414E+10 0.185629E+10 0.898309E+09
May 0.311141E+10 0.175156E+10 0.135985E+10 0.333418E+10 0.471655E+09
June 0.277022E+10 0.129057E+10 0.147965E+10 0.307831E+10 0.218845E+09
July 0.271907E+10 0.131673E+10 0.140234E+10 0.309698E+10 0.255811E+09
August 0.215368E+10 0.104738E+10 0.110630E+10 0.234272E+10 0.405909E+09
September 0.128934E+10 0.564396E+09 0.724939E+09 0.115755E+10 0.786937E+09
October 0.703740E+09 0.282382E+09 0.421358E+09 0.476456E+09 0.148273E+10
November 0.144866E+09 50620862.64 94244678.23 11007767.01 0.253811E+10
December 21386826.70 5119625.73 16267200.97 0.00 0.288085E+10
           
Annual Sum or Average 0.171369E+11 0.841297E+10 0.872391E+10 0.168807E+11 0.162891E+11
Minimum of Months 21386826.70 5119625.73 16267200.97 0.00 0.218845E+09
Maximum of Months 0.311141E+10 0.175156E+10 0.147965E+10 0.333418E+10 0.288085E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 98870084.13 31115691.74 67754392.39 8656116.64 0.264696E+10
February 0.493400E+09 0.235436E+09 0.257965E+09 0.249671E+09 0.202666E+10
March 0.155815E+10 0.789067E+09 0.769085E+09 0.126887E+10 0.167620E+10
April 0.207267E+10 0.104855E+10 0.102412E+10 0.185626E+10 0.898292E+09
May 0.311135E+10 0.175153E+10 0.135982E+10 0.333412E+10 0.471647E+09
June 0.277017E+10 0.129055E+10 0.147963E+10 0.307825E+10 0.218841E+09
July 0.271902E+10 0.131670E+10 0.140231E+10 0.309692E+10 0.255807E+09
August 0.215364E+10 0.104736E+10 0.110628E+10 0.234268E+10 0.405902E+09
September 0.128931E+10 0.564386E+09 0.724926E+09 0.115752E+10 0.786922E+09
October 0.703727E+09 0.282377E+09 0.421350E+09 0.476447E+09 0.148270E+10
November 0.144863E+09 50619937.68 94242956.18 11007565.87 0.253806E+10
December 21386435.91 5119532.19 16266903.73 0.00 0.288079E+10
           
Annual Sum or Average 0.171366E+11 0.841281E+10 0.872375E+10 0.168804E+11 0.162888E+11
Minimum of Months 21386435.91 5119532.19 16266903.73 0.00 0.218841E+09
Maximum of Months 0.311135E+10 0.175153E+10 0.147963E+10 0.333412E+10 0.288079E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.405237E+09 0.266985E+09 0.138252E+09 0.231572E+09 0.218470E+10
February 0.125949E+10 0.876107E+09 0.383387E+09 0.104003E+10 0.161392E+10
March 0.239454E+10 0.162304E+10 0.771498E+09 0.228503E+10 0.138958E+10
April 0.282704E+10 0.175870E+10 0.106834E+10 0.301336E+10 0.890585E+09
May 0.240884E+10 0.124815E+10 0.116069E+10 0.265092E+10 0.490863E+09
June 0.212842E+10 0.872381E+09 0.125604E+10 0.240890E+10 0.251750E+09
July 0.211902E+10 0.922832E+09 0.119619E+10 0.245450E+10 0.275601E+09
August 0.219446E+10 0.120940E+10 0.985065E+09 0.250143E+10 0.412453E+09
September 0.171631E+10 0.103365E+10 0.682663E+09 0.177002E+10 0.709623E+09
October 0.127694E+10 0.810181E+09 0.466757E+09 0.112595E+10 0.120706E+10
November 0.662564E+09 0.462641E+09 0.199924E+09 0.424654E+09 0.201186E+10
December 0.121531E+09 85662558.95 35868430.68 20911273.23 0.245975E+10
           
Annual Sum or Average 0.195144E+11 0.111697E+11 0.834468E+10 0.199273E+11 0.138977E+11
Minimum of Months 0.121531E+09 85662558.95 35868430.68 20911273.23 0.251750E+09
Maximum of Months 0.282704E+10 0.175870E+10 0.125604E+10 0.301336E+10 0.245975E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.405234E+09 0.266983E+09 0.138251E+09 0.231569E+09 0.218470E+10
February 0.125949E+10 0.876101E+09 0.383385E+09 0.104002E+10 0.161392E+10
March 0.239452E+10 0.162303E+10 0.771494E+09 0.228501E+10 0.138958E+10
April 0.282702E+10 0.175868E+10 0.106833E+10 0.301333E+10 0.890585E+09
May 0.240883E+10 0.124814E+10 0.116069E+10 0.265090E+10 0.490863E+09
June 0.212841E+10 0.872374E+09 0.125603E+10 0.240888E+10 0.251750E+09
July 0.211901E+10 0.922825E+09 0.119618E+10 0.245449E+10 0.275601E+09
August 0.219445E+10 0.120939E+10 0.985060E+09 0.250141E+10 0.412453E+09
September 0.171630E+10 0.103364E+10 0.682659E+09 0.177001E+10 0.709623E+09
October 0.127693E+10 0.810175E+09 0.466754E+09 0.112594E+10 0.120706E+10
November 0.662560E+09 0.462638E+09 0.199922E+09 0.424649E+09 0.201185E+10
December 0.121530E+09 85661931.21 35868182.48 20910837.26 0.245975E+10
           
Annual Sum or Average 0.195143E+11 0.111696E+11 0.834463E+10 0.199271E+11 0.138977E+11
Minimum of Months 0.121530E+09 85661931.21 35868182.48 20910837.26 0.251750E+09
Maximum of Months 0.282702E+10 0.175868E+10 0.125603E+10 0.301333E+10 0.245975E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.405237E+09 0.266985E+09 0.138252E+09 0.231572E+09 0.218470E+10
February 0.125949E+10 0.876107E+09 0.383387E+09 0.104003E+10 0.161392E+10
March 0.239454E+10 0.162304E+10 0.771498E+09 0.228503E+10 0.138958E+10
April 0.282704E+10 0.175870E+10 0.106834E+10 0.301336E+10 0.890585E+09
May 0.240884E+10 0.124815E+10 0.116069E+10 0.265092E+10 0.490863E+09
June 0.212842E+10 0.872381E+09 0.125604E+10 0.240890E+10 0.251750E+09
July 0.211902E+10 0.922832E+09 0.119619E+10 0.245450E+10 0.275601E+09
August 0.219446E+10 0.120940E+10 0.985065E+09 0.250143E+10 0.412453E+09
September 0.171631E+10 0.103365E+10 0.682663E+09 0.177002E+10 0.709623E+09
October 0.127694E+10 0.810181E+09 0.466757E+09 0.112595E+10 0.120706E+10
November 0.662564E+09 0.462641E+09 0.199924E+09 0.424654E+09 0.201186E+10
December 0.121531E+09 85662558.95 35868430.68 20911273.23 0.245975E+10
           
Annual Sum or Average 0.195144E+11 0.111697E+11 0.834468E+10 0.199273E+11 0.138977E+11
Minimum of Months 0.121531E+09 85662558.95 35868430.68 20911273.23 0.251750E+09
Maximum of Months 0.282704E+10 0.175870E+10 0.125604E+10 0.301336E+10 0.245975E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.405234E+09 0.266983E+09 0.138251E+09 0.231569E+09 0.218470E+10
February 0.125949E+10 0.876101E+09 0.383385E+09 0.104002E+10 0.161392E+10
March 0.239452E+10 0.162303E+10 0.771494E+09 0.228501E+10 0.138958E+10
April 0.282702E+10 0.175868E+10 0.106833E+10 0.301333E+10 0.890585E+09
May 0.240883E+10 0.124814E+10 0.116069E+10 0.265090E+10 0.490863E+09
June 0.212841E+10 0.872374E+09 0.125603E+10 0.240888E+10 0.251750E+09
July 0.211901E+10 0.922825E+09 0.119618E+10 0.245449E+10 0.275601E+09
August 0.219445E+10 0.120939E+10 0.985060E+09 0.250141E+10 0.412453E+09
September 0.171630E+10 0.103364E+10 0.682659E+09 0.177001E+10 0.709623E+09
October 0.127693E+10 0.810175E+09 0.466754E+09 0.112594E+10 0.120706E+10
November 0.662560E+09 0.462638E+09 0.199922E+09 0.424649E+09 0.201185E+10
December 0.121530E+09 85661931.21 35868182.48 20910837.26 0.245975E+10
           
Annual Sum or Average 0.195143E+11 0.111696E+11 0.834463E+10 0.199271E+11 0.138977E+11
Minimum of Months 0.121530E+09 85661931.21 35868182.48 20910837.26 0.251750E+09
Maximum of Months 0.282702E+10 0.175868E+10 0.125603E+10 0.301333E+10 0.245975E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.405219E+09 0.266973E+09 0.138246E+09 0.231561E+09 0.218461E+10
February 0.125944E+10 0.876068E+09 0.383371E+09 0.103998E+10 0.161386E+10
March 0.239444E+10 0.162297E+10 0.771465E+09 0.228493E+10 0.138952E+10
April 0.282691E+10 0.175862E+10 0.106829E+10 0.301322E+10 0.890549E+09
May 0.240874E+10 0.124810E+10 0.116064E+10 0.265080E+10 0.490844E+09
June 0.212833E+10 0.872342E+09 0.125598E+10 0.240879E+10 0.251740E+09
July 0.211893E+10 0.922791E+09 0.119614E+10 0.245440E+10 0.275590E+09
August 0.219437E+10 0.120934E+10 0.985023E+09 0.250132E+10 0.412436E+09
September 0.171623E+10 0.103360E+10 0.682633E+09 0.176995E+10 0.709594E+09
October 0.127688E+10 0.810146E+09 0.466737E+09 0.112590E+10 0.120701E+10
November 0.662535E+09 0.462621E+09 0.199915E+09 0.424634E+09 0.201177E+10
December 0.121526E+09 85658792.52 35866860.93 20910212.44 0.245965E+10
           
Annual Sum or Average 0.195135E+11 0.111692E+11 0.834432E+10 0.199264E+11 0.138972E+11
Minimum of Months 0.121526E+09 85658792.52 35866860.93 20910212.44 0.251740E+09
Maximum of Months 0.282691E+10 0.175862E+10 0.125598E+10 0.301322E+10 0.245965E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52009464.82 9281157.37 42728307.45 0.00 0.277147E+10
February 0.277312E+09 96429882.74 0.180882E+09 50208231.51 0.219353E+10
March 0.921537E+09 0.396158E+09 0.525379E+09 0.485104E+09 0.183686E+10
April 0.211618E+10 0.109662E+10 0.101956E+10 0.192339E+10 0.107182E+10
May 0.212623E+10 0.968294E+09 0.115794E+10 0.208947E+10 0.536124E+09
June 0.225508E+10 0.961508E+09 0.129357E+10 0.240912E+10 0.288522E+09
July 0.194974E+10 0.737539E+09 0.121220E+10 0.208723E+10 0.328471E+09
August 0.160247E+10 0.678572E+09 0.923902E+09 0.161252E+10 0.500951E+09
September 0.938528E+09 0.393019E+09 0.545509E+09 0.723885E+09 0.859350E+09
October 0.379810E+09 0.114185E+09 0.265625E+09 0.120564E+09 0.164748E+10
November 0.147061E+09 53432196.16 93628368.67 12769388.02 0.265941E+10
December 13642686.64 1434095.19 12208591.45 0.00 0.305411E+10
           
Annual Sum or Average 0.127796E+11 0.550647E+10 0.727313E+10 0.115143E+11 0.177481E+11
Minimum of Months 13642686.64 1434095.19 12208591.45 0.00 0.288522E+09
Maximum of Months 0.225508E+10 0.109662E+10 0.129357E+10 0.240912E+10 0.305411E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52009464.82 9281157.37 42728307.45 0.00 0.277147E+10
February 0.277312E+09 96429882.74 0.180882E+09 50208231.51 0.219353E+10
March 0.921537E+09 0.396158E+09 0.525379E+09 0.485104E+09 0.183686E+10
April 0.211618E+10 0.109662E+10 0.101956E+10 0.192339E+10 0.107182E+10
May 0.212623E+10 0.968294E+09 0.115794E+10 0.208947E+10 0.536124E+09
June 0.225508E+10 0.961508E+09 0.129357E+10 0.240912E+10 0.288522E+09
July 0.194974E+10 0.737539E+09 0.121220E+10 0.208723E+10 0.328471E+09
August 0.160247E+10 0.678572E+09 0.923902E+09 0.161252E+10 0.500951E+09
September 0.938528E+09 0.393019E+09 0.545509E+09 0.723885E+09 0.859350E+09
October 0.379810E+09 0.114185E+09 0.265625E+09 0.120564E+09 0.164748E+10
November 0.147061E+09 53432196.16 93628368.67 12769388.02 0.265941E+10
December 13642686.64 1434095.19 12208591.45 0.00 0.305411E+10
           
Annual Sum or Average 0.127796E+11 0.550647E+10 0.727313E+10 0.115143E+11 0.177481E+11
Minimum of Months 13642686.64 1434095.19 12208591.45 0.00 0.288522E+09
Maximum of Months 0.225508E+10 0.109662E+10 0.129357E+10 0.240912E+10 0.305411E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 52008514.49 9280987.78 42727526.71 0.00 0.277142E+10
February 0.277307E+09 96428120.75 0.180879E+09 50207314.09 0.219349E+10
March 0.921520E+09 0.396151E+09 0.525369E+09 0.485095E+09 0.183683E+10
April 0.211614E+10 0.109660E+10 0.101954E+10 0.192335E+10 0.107180E+10
May 0.212620E+10 0.968276E+09 0.115792E+10 0.208944E+10 0.536114E+09
June 0.225504E+10 0.961491E+09 0.129355E+10 0.240907E+10 0.288517E+09
July 0.194971E+10 0.737525E+09 0.121218E+10 0.208719E+10 0.328465E+09
August 0.160244E+10 0.678560E+09 0.923885E+09 0.161249E+10 0.500942E+09
September 0.938511E+09 0.393012E+09 0.545499E+09 0.723872E+09 0.859334E+09
October 0.379803E+09 0.114183E+09 0.265620E+09 0.120562E+09 0.164745E+10
November 0.147058E+09 53431219.84 93626657.88 12769154.70 0.265936E+10
December 13642437.36 1434068.99 12208368.37 0.00 0.305406E+10
           
Annual Sum or Average 0.127794E+11 0.550637E+10 0.727300E+10 0.115140E+11 0.177478E+11
Minimum of Months 13642437.36 1434068.99 12208368.37 0.00 0.288517E+09
Maximum of Months 0.225504E+10 0.109660E+10 0.129355E+10 0.240907E+10 0.305406E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168896E+09 0.00 0.168896E+09 0.00 0.119096E+11
February 0.674350E+09 0.00 0.674350E+09 0.00 0.964072E+10
March 0.199684E+10 0.00 0.199684E+10 0.171731E+09 0.789935E+10
April 0.349631E+10 76984390.17 0.341932E+10 0.142506E+10 0.405087E+10
May 0.553726E+10 0.880355E+09 0.465691E+10 0.421412E+10 0.188605E+10
June 0.699154E+10 0.155485E+10 0.543669E+10 0.673535E+10 0.849783E+09
July 0.606349E+10 0.985567E+09 0.507792E+10 0.595915E+10 0.107754E+10
August 0.387179E+10 0.216384E+09 0.365541E+10 0.310229E+10 0.179324E+10
September 0.209035E+10 2104837.37 0.208824E+10 0.776025E+09 0.354043E+10
October 0.105104E+10 0.00 0.105104E+10 72811921.39 0.678708E+10
November 0.315655E+09 0.00 0.315655E+09 0.00 0.112883E+11
December 51234282.39 0.00 51234282.39 0.00 0.125507E+11
           
Annual Sum or Average 0.323088E+11 0.371624E+10 0.285925E+11 0.224565E+11 0.732736E+11
Minimum of Months 51234282.39 0.00 51234282.39 0.00 0.849783E+09
Maximum of Months 0.699154E+10 0.155485E+10 0.543669E+10 0.673535E+10 0.125507E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.296613E+09 93347829.41 0.203265E+09 26480022.19 0.769964E+10
February 0.148021E+10 0.706313E+09 0.773900E+09 0.774111E+09 0.582039E+10
March 0.467449E+10 0.236722E+10 0.230727E+10 0.386652E+10 0.476847E+10
April 0.621805E+10 0.314568E+10 0.307237E+10 0.561857E+10 0.252610E+10
May 0.933414E+10 0.525464E+10 0.407950E+10 0.997317E+10 0.137250E+10
June 0.831059E+10 0.387167E+10 0.443892E+10 0.919620E+10 0.651277E+09
July 0.815712E+10 0.395014E+10 0.420697E+10 0.924019E+10 0.779040E+09
August 0.646096E+10 0.314210E+10 0.331886E+10 0.699958E+10 0.121712E+10
September 0.386797E+10 0.169317E+10 0.217480E+10 0.350566E+10 0.223126E+10
October 0.211120E+10 0.847137E+09 0.126406E+10 0.147651E+10 0.412855E+10
November 0.434592E+09 0.151861E+09 0.282731E+09 36459925.16 0.723722E+10
December 64159826.11 15358720.65 48801105.47 0.00 0.830983E+10
           
Annual Sum or Average 0.514101E+11 0.252386E+11 0.261715E+11 0.507135E+11 0.467414E+11
Minimum of Months 64159826.11 15358720.65 48801105.47 0.00 0.651277E+09
Maximum of Months 0.933414E+10 0.525464E+10 0.443892E+10 0.997317E+10 0.830983E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.202622E+10 0.133495E+10 0.691274E+09 0.117186E+10 0.107070E+11
February 0.629760E+10 0.438063E+10 0.191697E+10 0.524619E+10 0.784102E+10
March 0.119729E+11 0.811538E+10 0.385755E+10 0.114532E+11 0.674173E+10
April 0.141354E+11 0.879367E+10 0.534177E+10 0.150483E+11 0.430442E+10
May 0.120444E+11 0.624088E+10 0.580353E+10 0.132012E+11 0.241425E+10
June 0.106423E+11 0.436199E+10 0.628027E+10 0.120052E+11 0.124455E+10
July 0.105953E+11 0.461426E+10 0.598103E+10 0.122354E+11 0.137988E+10
August 0.109725E+11 0.604711E+10 0.492539E+10 0.124762E+11 0.204675E+10
September 0.858170E+10 0.516834E+10 0.341336E+10 0.884085E+10 0.348030E+10
October 0.638482E+10 0.405099E+10 0.233383E+10 0.567986E+10 0.579530E+10
November 0.331289E+10 0.231325E+10 0.999636E+09 0.217117E+10 0.968548E+10
December 0.607667E+09 0.428322E+09 0.179346E+09 0.107700E+09 0.119259E+11
           
Annual Sum or Average 0.975737E+11 0.558498E+11 0.417240E+11 0.996372E+11 0.675666E+11
Minimum of Months 0.607667E+09 0.428322E+09 0.179346E+09 0.107700E+09 0.124455E+10
Maximum of Months 0.141354E+11 0.879367E+10 0.628027E+10 0.150483E+11 0.119259E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.156027E+09 27843188.30 0.128184E+09 0.00 0.791060E+10
February 0.831928E+09 0.289287E+09 0.542642E+09 0.170324E+09 0.610591E+10
March 0.276458E+10 0.118846E+10 0.157612E+10 0.155326E+10 0.493000E+10
April 0.634847E+10 0.328983E+10 0.305865E+10 0.593552E+10 0.280467E+10
May 0.637864E+10 0.290485E+10 0.347378E+10 0.632592E+10 0.150606E+10
June 0.676516E+10 0.288450E+10 0.388067E+10 0.728328E+10 0.795007E+09
July 0.584917E+10 0.221259E+10 0.363657E+10 0.634593E+10 0.893241E+09
August 0.480737E+10 0.203570E+10 0.277168E+10 0.494334E+10 0.132952E+10
September 0.281556E+10 0.117904E+10 0.163651E+10 0.225549E+10 0.232617E+10
October 0.113942E+10 0.342551E+09 0.796868E+09 0.415660E+09 0.436271E+10
November 0.441177E+09 0.160295E+09 0.280882E+09 48119594.12 0.730023E+10
December 40927642.74 4302241.72 36625401.02 0.00 0.842895E+10
           
Annual Sum or Average 0.383384E+11 0.165193E+11 0.218192E+11 0.352768E+11 0.486931E+11
Minimum of Months 40927642.74 4302241.72 36625401.02 0.00 0.795007E+09
Maximum of Months 0.676516E+10 0.328983E+10 0.388067E+10 0.728328E+10 0.842895E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.168896E+09 0.00 0.168896E+09 0.00 0.116721E+11
February 0.674350E+09 0.00 0.674350E+09 0.00 0.938853E+10
March 0.199684E+10 0.00 0.199684E+10 0.196958E+09 0.759624E+10
April 0.349631E+10 76984390.17 0.341932E+10 0.156176E+10 0.377393E+10
May 0.553726E+10 0.880355E+09 0.465691E+10 0.438447E+10 0.176412E+10
June 0.699154E+10 0.155485E+10 0.543669E+10 0.675788E+10 0.820379E+09
July 0.606349E+10 0.985567E+09 0.507792E+10 0.598081E+10 0.104515E+10
August 0.387179E+10 0.216384E+09 0.365541E+10 0.318009E+10 0.169620E+10
September 0.209035E+10 2104837.37 0.208824E+10 0.904254E+09 0.318436E+10
October 0.105104E+10 0.00 0.105104E+10 0.109794E+09 0.637389E+10
November 0.315655E+09 0.00 0.315655E+09 0.00 0.110121E+11
December 51234282.39 0.00 51234282.39 0.00 0.123025E+11
           
Annual Sum or Average 0.323088E+11 0.371624E+10 0.285925E+11 0.230760E+11 0.706295E+11
Minimum of Months 51234282.39 0.00 51234282.39 0.00 0.820379E+09
Maximum of Months 0.699154E+10 0.155485E+10 0.543669E+10 0.675788E+10 0.123025E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.296613E+09 93347829.41 0.203265E+09 27315399.81 0.755332E+10
February 0.148021E+10 0.706313E+09 0.773900E+09 0.790046E+09 0.566753E+10
March 0.467449E+10 0.236722E+10 0.230727E+10 0.392663E+10 0.457115E+10
April 0.621805E+10 0.314568E+10 0.307237E+10 0.571030E+10 0.237168E+10
May 0.933414E+10 0.525464E+10 0.407950E+10 0.100190E+11 0.131256E+10
June 0.831059E+10 0.387167E+10 0.443892E+10 0.919420E+10 0.637306E+09
July 0.815712E+10 0.395014E+10 0.420697E+10 0.923540E+10 0.765252E+09
August 0.646096E+10 0.314210E+10 0.331886E+10 0.701821E+10 0.117530E+10
September 0.386797E+10 0.169317E+10 0.217480E+10 0.359107E+10 0.205064E+10
October 0.211120E+10 0.847137E+09 0.126406E+10 0.153070E+10 0.387705E+10
November 0.434592E+09 0.151861E+09 0.282731E+09 38433135.49 0.706420E+10
December 64159826.11 15358720.65 48801105.47 0.00 0.816003E+10
           
Annual Sum or Average 0.514101E+11 0.252386E+11 0.261715E+11 0.510813E+11 0.452060E+11
Minimum of Months 64159826.11 15358720.65 48801105.47 0.00 0.637306E+09
Maximum of Months 0.933414E+10 0.525464E+10 0.443892E+10 0.100190E+11 0.816003E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.202622E+10 0.133495E+10 0.691274E+09 0.118972E+10 0.104852E+11
February 0.629760E+10 0.438063E+10 0.191697E+10 0.531671E+10 0.759015E+10
March 0.119729E+11 0.811538E+10 0.385755E+10 0.115657E+11 0.642711E+10
April 0.141354E+11 0.879367E+10 0.534177E+10 0.151497E+11 0.404617E+10
May 0.120444E+11 0.624088E+10 0.580353E+10 0.132557E+11 0.228762E+10
June 0.106423E+11 0.436199E+10 0.628027E+10 0.120061E+11 0.121192E+10
July 0.105953E+11 0.461426E+10 0.598103E+10 0.122331E+11 0.135033E+10
August 0.109725E+11 0.604711E+10 0.492539E+10 0.124985E+11 0.197083E+10
September 0.858170E+10 0.516834E+10 0.341336E+10 0.895253E+10 0.321174E+10
October 0.638482E+10 0.405099E+10 0.233383E+10 0.580341E+10 0.542240E+10
November 0.331289E+10 0.231325E+10 0.999636E+09 0.220886E+10 0.941830E+10
December 0.607667E+09 0.428322E+09 0.179346E+09 0.109941E+09 0.116907E+11
           
Annual Sum or Average 0.975737E+11 0.558498E+11 0.417240E+11 0.100290E+12 0.651125E+11
Minimum of Months 0.607667E+09 0.428322E+09 0.179346E+09 0.109941E+09 0.121192E+10
Maximum of Months 0.141354E+11 0.879367E+10 0.628027E+10 0.151497E+11 0.116907E+11



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.156027E+09 27843188.30 0.128184E+09 0.00 0.774922E+10
February 0.831928E+09 0.289287E+09 0.542642E+09 0.175511E+09 0.595313E+10
March 0.276458E+10 0.118846E+10 0.157612E+10 0.158430E+10 0.474154E+10
April 0.634847E+10 0.328983E+10 0.305865E+10 0.600542E+10 0.264022E+10
May 0.637864E+10 0.290485E+10 0.347378E+10 0.637583E+10 0.142804E+10
June 0.676516E+10 0.288450E+10 0.388067E+10 0.728546E+10 0.775239E+09
July 0.584917E+10 0.221259E+10 0.363657E+10 0.634690E+10 0.873177E+09
August 0.480737E+10 0.203570E+10 0.277168E+10 0.496746E+10 0.127788E+10
September 0.281556E+10 0.117904E+10 0.163651E+10 0.232067E+10 0.215257E+10
October 0.113942E+10 0.342551E+09 0.796868E+09 0.445806E+09 0.412806E+10
November 0.441177E+09 0.160295E+09 0.280882E+09 50807488.65 0.712655E+10
December 40927642.74 4302241.72 36625401.02 0.00 0.827339E+10
           
Annual Sum or Average 0.383384E+11 0.165193E+11 0.218192E+11 0.355582E+11 0.471190E+11
Minimum of Months 40927642.74 4302241.72 36625401.02 0.00 0.775239E+09
Maximum of Months 0.676516E+10 0.328983E+10 0.388067E+10 0.728546E+10 0.827339E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 4608.59 63.06 0.00 63.06 0.00 0.00
February 0.00 4192.36 278.74 0.00 278.74 0.00 0.00
March 45.87 3170.43 745.52 0.00 745.52 0.00 0.00
April 482.96 1740.81 1348.86 29.70 1319.16 0.00 0.00
May 1544.86 737.27 2067.33 328.68 1738.66 0.00 0.00
June 2591.79 338.74 2697.29 599.85 2097.45 0.00 0.00
July 2215.91 412.85 2263.80 367.96 1895.84 0.00 0.00
August 1135.20 703.85 1445.53 80.79 1364.75 0.00 0.00
September 269.15 1486.67 806.45 0.81 805.63 0.00 0.00
October 16.23 2782.50 392.41 0.00 392.41 0.00 0.00
November 0.00 4619.16 121.78 0.00 121.78 0.00 0.00
December 0.00 4927.35 19.13 0.00 19.13 0.00 0.00
               
Annual Sum or Average 695.94 2467.33 1024.48 117.84 906.64 0.00 0.00
Minimum of Months 0.00 338.74 19.13 0.00 19.13 0.00 0.00
Maximum of Months 2591.79 4927.35 2697.29 599.85 2097.45 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.70 2964.82 110.74 34.85 75.89 0.00 0.00
February 309.62 2513.25 611.86 291.96 319.90 0.00 0.00
March 1421.24 1877.48 1745.26 883.82 861.44 0.00 0.00
April 2148.47 1039.70 2398.95 1213.61 1185.33 0.00 0.00
May 3734.49 528.28 3484.98 1961.86 1523.12 0.00 0.00
June 3562.83 253.29 3206.26 1493.71 1712.55 0.00 0.00
July 3468.81 286.53 3045.53 1474.82 1570.71 0.00 0.00
August 2624.00 454.64 2412.26 1173.13 1239.13 0.00 0.00
September 1339.74 910.80 1492.28 653.23 839.04 0.00 0.00
October 533.66 1660.75 788.23 316.29 471.95 0.00 0.00
November 12.74 2937.61 167.67 58.59 109.08 0.00 0.00
December 0.00 3226.73 23.95 5.73 18.22 0.00 0.00
               
Annual Sum or Average 1605.84 1549.56 1630.21 800.32 829.89 0.00 0.00
Minimum of Months 0.00 253.29 23.95 5.73 18.22 0.00 0.00
Maximum of Months 3734.49 3226.73 3484.98 1961.86 1712.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 432.29 4078.33 756.48 498.40 258.08 0.00 0.00
February 2149.50 3335.63 2603.09 1810.72 792.38 0.00 0.00
March 4265.61 2594.02 4470.04 3029.84 1440.21 0.00 0.00
April 5812.73 1717.94 5453.32 3392.51 2060.82 0.00 0.00
May 4948.64 916.33 4496.74 2330.00 2166.74 0.00 0.00
June 4646.74 485.63 4105.70 1682.81 2422.89 0.00 0.00
July 4581.98 514.48 3955.72 1722.71 2233.01 0.00 0.00
August 4669.58 769.95 4096.54 2257.66 1838.89 0.00 0.00
September 3414.36 1368.86 3310.74 1993.89 1316.85 0.00 0.00
October 2101.88 2253.30 2383.74 1512.42 871.33 0.00 0.00
November 819.15 3880.86 1278.08 892.43 385.65 0.00 0.00
December 39.04 4591.79 226.87 159.91 66.96 0.00 0.00
               
Annual Sum or Average 3159.41 2203.45 3093.95 1770.93 1323.03 0.00 0.00
Minimum of Months 39.04 485.63 226.87 159.91 66.96 0.00 0.00
Maximum of Months 5812.73 4591.79 5453.32 3392.51 2422.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 3104.22 58.25 10.40 47.86 0.00 0.00
February 62.26 2720.13 343.89 119.58 224.31 0.00 0.00
March 543.35 2057.40 1032.18 443.72 588.46 0.00 0.00
April 2226.13 1240.52 2449.27 1269.23 1180.04 0.00 0.00
May 2340.35 600.49 2381.52 1084.55 1296.97 0.00 0.00
June 2788.32 333.94 2610.03 1112.85 1497.18 0.00 0.00
July 2337.83 367.91 2183.84 826.09 1357.75 0.00 0.00
August 1806.12 561.10 1794.87 760.04 1034.83 0.00 0.00
September 837.82 994.61 1086.25 454.88 631.37 0.00 0.00
October 135.04 1845.28 425.41 127.89 297.52 0.00 0.00
November 14.78 3078.00 170.21 61.84 108.37 0.00 0.00
December 0.00 3420.81 15.28 1.61 13.67 0.00 0.00
               
Annual Sum or Average 1095.34 1688.35 1215.71 523.82 691.88 0.00 0.00
Minimum of Months 0.00 333.94 15.28 1.61 13.67 0.00 0.00
Maximum of Months 2788.32 3420.81 2610.03 1269.23 1497.18 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 4446.52 63.06 0.00 63.06 0.00 0.00
February 0.00 3985.09 278.75 0.00 278.75 0.00 0.00
March 64.12 2949.28 745.53 0.00 745.53 0.00 0.00
April 549.79 1562.84 1348.88 29.70 1319.18 0.00 0.00
May 1573.37 704.17 2067.38 328.69 1738.69 0.00 0.00
June 2598.51 327.85 2697.35 599.86 2097.49 0.00 0.00
July 2224.89 402.31 2263.85 367.97 1895.88 0.00 0.00
August 1158.26 669.52 1445.56 80.79 1364.77 0.00 0.00
September 299.39 1365.91 806.46 0.81 805.65 0.00 0.00
October 27.18 2534.01 392.42 0.00 392.42 0.00 0.00
November 0.00 4355.06 121.78 0.00 121.78 0.00 0.00
December 0.00 4685.90 19.13 0.00 19.13 0.00 0.00
               
Annual Sum or Average 712.09 2323.49 1024.50 117.84 906.66 0.00 0.00
Minimum of Months 0.00 327.85 19.13 0.00 19.13 0.00 0.00
Maximum of Months 2598.51 4685.90 2697.35 599.86 2097.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 9.89 2874.72 110.74 34.85 75.89 0.00 0.00
February 319.99 2405.91 611.86 291.96 319.90 0.00 0.00
March 1443.60 1780.34 1745.26 883.82 861.44 0.00 0.00
April 2167.66 974.58 2398.94 1213.61 1185.33 0.00 0.00
May 3723.55 512.43 3484.97 1961.86 1523.11 0.00 0.00
June 3547.92 251.26 3206.25 1493.70 1712.55 0.00 0.00
July 3449.89 290.86 3045.52 1474.81 1570.70 0.00 0.00
August 2613.34 454.42 2412.25 1173.13 1239.12 0.00 0.00
September 1352.49 860.83 1492.27 653.23 839.04 0.00 0.00
October 551.26 1541.42 788.23 316.28 471.95 0.00 0.00
November 14.07 2792.14 167.67 58.59 109.08 0.00 0.00
December 0.00 3102.53 23.95 5.73 18.22 0.00 0.00
               
Annual Sum or Average 1608.11 1482.16 1630.20 800.31 829.89 0.00 0.00
Minimum of Months 0.00 251.26 23.95 5.73 18.22 0.00 0.00
Maximum of Months 3723.55 3102.53 3484.97 1961.86 1712.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 437.52 3997.54 756.51 498.41 258.09 0.00 0.00
February 2168.56 3241.16 2603.17 1810.77 792.40 0.00 0.00
March 4276.14 2517.07 4470.18 3029.94 1440.24 0.00 0.00
April 5805.68 1660.66 5453.49 3392.62 2060.87 0.00 0.00
May 4928.77 901.38 4496.87 2330.08 2166.79 0.00 0.00
June 4631.65 480.15 4105.81 1682.87 2422.94 0.00 0.00
July 4568.16 515.19 3955.83 1722.77 2233.06 0.00 0.00
August 4658.08 764.17 4096.66 2257.73 1838.93 0.00 0.00
September 3410.82 1342.71 3310.84 1993.96 1316.88 0.00 0.00
October 2120.62 2163.72 2383.82 1512.47 871.35 0.00 0.00
November 837.64 3736.68 1278.12 892.46 385.66 0.00 0.00
December 40.21 4452.63 226.88 159.92 66.96 0.00 0.00
               
Annual Sum or Average 3159.47 2142.52 3094.04 1770.98 1323.06 0.00 0.00
Minimum of Months 40.21 480.15 226.88 159.92 66.96 0.00 0.00
Maximum of Months 5805.68 4452.63 5453.49 3392.62 2422.94 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 2953.48 58.25 10.40 47.86 0.00 0.00
February 70.41 2523.94 343.89 119.58 224.31 0.00 0.00
March 579.92 1840.65 1032.18 443.72 588.46 0.00 0.00
April 2289.94 1082.05 2449.26 1269.22 1180.03 0.00 0.00
May 2361.83 562.30 2381.51 1084.55 1296.96 0.00 0.00
June 2809.91 306.72 2610.02 1112.85 1497.17 0.00 0.00
July 2369.30 333.50 2183.83 826.09 1357.74 0.00 0.00
August 1845.63 496.39 1794.87 760.04 1034.83 0.00 0.00
September 870.17 897.44 1086.25 454.88 631.37 0.00 0.00
October 155.19 1628.85 425.41 127.89 297.52 0.00 0.00
November 18.56 2816.45 170.21 61.84 108.37 0.00 0.00
December 0.00 3147.01 15.28 1.61 13.67 0.00 0.00
               
Annual Sum or Average 1118.62 1544.05 1215.70 523.82 691.88 0.00 0.00
Minimum of Months 0.00 306.72 15.28 1.61 13.67 0.00 0.00
Maximum of Months 2809.91 3147.01 2610.02 1269.22 1497.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 4357.85 63.06 0.00 63.06 0.00 0.00
February 0.00 3880.84 278.75 0.00 278.75 0.00 0.00
March 73.54 2836.11 745.53 0.00 745.53 0.00 0.00
April 602.53 1455.99 1348.88 29.70 1319.18 0.00 0.00
May 1636.97 658.65 2067.38 328.69 1738.69 0.00 0.00
June 2607.21 316.50 2697.35 599.86 2097.49 0.00 0.00
July 2232.98 390.22 2263.85 367.97 1895.88 0.00 0.00
August 1187.31 633.29 1445.56 80.79 1364.77 0.00 0.00
September 348.86 1228.54 806.46 0.81 805.65 0.00 0.00
October 40.99 2379.74 392.42 0.00 392.42 0.00 0.00
November 0.00 4248.51 121.78 0.00 121.78 0.00 0.00
December 0.00 4593.23 19.13 0.00 19.13 0.00 0.00
               
Annual Sum or Average 731.74 2239.65 1024.50 117.84 906.66 0.00 0.00
Minimum of Months 0.00 316.50 19.13 0.00 19.13 0.00 0.00
Maximum of Months 2607.21 4593.23 2697.35 599.86 2097.49 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 10.20 2820.09 110.74 34.85 75.89 0.00 0.00
February 326.57 2342.73 611.86 291.96 319.90 0.00 0.00
March 1466.04 1706.67 1745.26 883.82 861.44 0.00 0.00
April 2203.05 915.00 2398.94 1213.61 1185.33 0.00 0.00
May 3740.65 490.05 3484.97 1961.86 1523.11 0.00 0.00
June 3547.14 245.87 3206.25 1493.70 1712.55 0.00 0.00
July 3448.10 285.71 3045.52 1474.81 1570.70 0.00 0.00
August 2620.30 438.81 2412.25 1173.13 1239.12 0.00 0.00
September 1385.44 791.14 1492.27 653.23 839.04 0.00 0.00
October 571.50 1447.53 788.23 316.28 471.95 0.00 0.00
November 14.83 2725.38 167.67 58.59 109.08 0.00 0.00
December 0.00 3046.61 23.95 5.73 18.22 0.00 0.00
               
Annual Sum or Average 1619.78 1433.47 1630.20 800.31 829.89 0.00 0.00
Minimum of Months 0.00 245.87 23.95 5.73 18.22 0.00 0.00
Maximum of Months 3740.65 3046.61 3484.97 1961.86 1712.55 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 444.19 3914.73 756.51 498.41 258.09 0.00 0.00
February 2197.71 3137.46 2603.17 1810.77 792.40 0.00 0.00
March 4318.15 2399.61 4470.18 3029.94 1440.24 0.00 0.00
April 5844.79 1561.02 5453.49 3392.62 2060.87 0.00 0.00
May 4949.13 854.10 4496.87 2330.08 2166.79 0.00 0.00
June 4631.97 467.56 4105.81 1682.87 2422.94 0.00 0.00
July 4567.33 504.15 3955.83 1722.77 2233.06 0.00 0.00
August 4666.41 735.83 4096.66 2257.73 1838.93 0.00 0.00
September 3453.91 1239.10 3310.84 1993.96 1316.88 0.00 0.00
October 2166.74 2024.49 2383.82 1512.47 871.35 0.00 0.00
November 852.18 3633.60 1278.12 892.46 385.66 0.00 0.00
December 41.05 4364.81 226.88 159.92 66.96 0.00 0.00
               
Annual Sum or Average 3180.18 2064.70 3094.04 1770.98 1323.06 0.00 0.00
Minimum of Months 41.05 467.56 226.88 159.92 66.96 0.00 0.00
Maximum of Months 5844.79 4364.81 5453.49 3392.62 2422.94 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 2893.23 58.25 10.40 47.86 0.00 0.00
February 72.55 2460.78 343.89 119.58 224.31 0.00 0.00
March 591.51 1770.29 1032.18 443.72 588.46 0.00 0.00
April 2316.91 1018.60 2449.26 1269.22 1180.03 0.00 0.00
May 2380.46 533.17 2381.51 1084.55 1296.96 0.00 0.00
June 2810.75 299.09 2610.02 1112.85 1497.17 0.00 0.00
July 2369.66 326.01 2183.83 826.09 1357.74 0.00 0.00
August 1854.64 477.11 1794.87 760.04 1034.83 0.00 0.00
September 895.32 830.47 1086.25 454.88 631.37 0.00 0.00
October 166.44 1541.24 425.41 127.89 297.52 0.00 0.00
November 19.60 2749.44 170.21 61.84 108.37 0.00 0.00
December 0.00 3088.93 15.28 1.61 13.67 0.00 0.00
               
Annual Sum or Average 1127.54 1494.13 1215.70 523.82 691.88 0.00 0.00
Minimum of Months 0.00 299.09 15.28 1.61 13.67 0.00 0.00
Maximum of Months 2810.75 3088.93 2610.02 1269.22 1497.17 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.123436E+11 0.168892E+09 0.00 0.168892E+09 0.00 0.00
February 0.00 0.101422E+11 0.674336E+09 0.00 0.674336E+09 0.00 0.00
March 0.122871E+09 0.849168E+10 0.199680E+10 0.00 0.199680E+10 0.00 0.00
April 0.125182E+10 0.451218E+10 0.349624E+10 76982094.35 0.341926E+10 0.00 0.00
May 0.413774E+10 0.197471E+10 0.553715E+10 0.880329E+09 0.465682E+10 0.00 0.00
June 0.671793E+10 0.878013E+09 0.699139E+10 0.155480E+10 0.543659E+10 0.00 0.00
July 0.593509E+10 0.110579E+10 0.606335E+10 0.985538E+09 0.507782E+10 0.00 0.00
August 0.304053E+10 0.188520E+10 0.387171E+10 0.216378E+09 0.365534E+10 0.00 0.00
September 0.697639E+09 0.385344E+10 0.209031E+10 2104774.60 0.208820E+10 0.00 0.00
October 43463983.97 0.745266E+10 0.105102E+10 0.00 0.105102E+10 0.00 0.00
November 0.00 0.119729E+11 0.315648E+09 0.00 0.315648E+09 0.00 0.00
December 0.00 0.131974E+11 51233092.76 0.00 51233092.76 0.00 0.00
               
Annual Sum or Average 0.219471E+11 0.778098E+11 0.323081E+11 0.371613E+10 0.285920E+11 0.00 0.00
Minimum of Months 0.00 0.878013E+09 51233092.76 0.00 51233092.76 0.00 0.00
Maximum of Months 0.671793E+10 0.131974E+11 0.699139E+10 0.155480E+10 0.543659E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 25968666.26 0.794097E+10 0.296614E+09 93348212.34 0.203266E+09 0.00 0.00
February 0.749023E+09 0.608006E+10 0.148022E+10 0.706315E+09 0.773903E+09 0.00 0.00
March 0.380666E+10 0.502865E+10 0.467451E+10 0.236723E+10 0.230728E+10 0.00 0.00
April 0.556884E+10 0.269491E+10 0.621808E+10 0.314569E+10 0.307239E+10 0.00 0.00
May 0.100025E+11 0.141496E+10 0.933418E+10 0.525466E+10 0.407952E+10 0.00 0.00
June 0.923486E+10 0.656530E+09 0.831062E+10 0.387169E+10 0.443894E+10 0.00 0.00
July 0.929087E+10 0.767429E+09 0.815715E+10 0.395016E+10 0.420699E+10 0.00 0.00
August 0.702811E+10 0.121772E+10 0.646099E+10 0.314212E+10 0.331887E+10 0.00 0.00
September 0.347261E+10 0.236080E+10 0.386798E+10 0.169318E+10 0.217480E+10 0.00 0.00
October 0.142936E+10 0.444816E+10 0.211121E+10 0.847140E+09 0.126407E+10 0.00 0.00
November 33023099.89 0.761429E+10 0.434594E+09 0.151862E+09 0.282732E+09 0.00 0.00
December 0.00 0.864248E+10 64160089.31 15358783.65 48801305.66 0.00 0.00
               
Annual Sum or Average 0.506418E+11 0.488669E+11 0.514103E+11 0.252387E+11 0.261716E+11 0.00 0.00
Minimum of Months 0.00 0.656530E+09 64160089.31 15358783.65 48801305.66 0.00 0.00
Maximum of Months 0.100025E+11 0.864248E+10 0.933418E+10 0.525466E+10 0.443894E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.115784E+10 0.109234E+11 0.202616E+10 0.133491E+10 0.691253E+09 0.00 0.00
February 0.520008E+10 0.806955E+10 0.629740E+10 0.438048E+10 0.191692E+10 0.00 0.00
March 0.114250E+11 0.694784E+10 0.119726E+11 0.811511E+10 0.385745E+10 0.00 0.00
April 0.150666E+11 0.445289E+10 0.141350E+11 0.879338E+10 0.534164E+10 0.00 0.00
May 0.132544E+11 0.245430E+10 0.120441E+11 0.624068E+10 0.580339E+10 0.00 0.00
June 0.120443E+11 0.125874E+10 0.106420E+11 0.436185E+10 0.628013E+10 0.00 0.00
July 0.122724E+11 0.137799E+10 0.105950E+11 0.461411E+10 0.598089E+10 0.00 0.00
August 0.125070E+11 0.206225E+10 0.109722E+11 0.604691E+10 0.492527E+10 0.00 0.00
September 0.885002E+10 0.354808E+10 0.858144E+10 0.516817E+10 0.341328E+10 0.00 0.00
October 0.562968E+10 0.603523E+10 0.638462E+10 0.405086E+10 0.233376E+10 0.00 0.00
November 0.212324E+10 0.100592E+11 0.331278E+10 0.231318E+10 0.999606E+09 0.00 0.00
December 0.104554E+09 0.122987E+11 0.607648E+09 0.428308E+09 0.179340E+09 0.00 0.00
               
Annual Sum or Average 0.996352E+11 0.694881E+11 0.975709E+11 0.558479E+11 0.417229E+11 0.00 0.00
Minimum of Months 0.104554E+09 0.125874E+10 0.607648E+09 0.428308E+09 0.179340E+09 0.00 0.00
Maximum of Months 0.150666E+11 0.122987E+11 0.141350E+11 0.879338E+10 0.628013E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.831435E+10 0.156027E+09 27843302.52 0.128184E+09 0.00 0.00
February 0.150624E+09 0.658054E+10 0.831932E+09 0.289288E+09 0.542644E+09 0.00 0.00
March 0.145530E+10 0.551055E+10 0.276459E+10 0.118847E+10 0.157613E+10 0.00 0.00
April 0.577012E+10 0.321543E+10 0.634850E+10 0.328984E+10 0.305866E+10 0.00 0.00
May 0.626838E+10 0.160836E+10 0.637866E+10 0.290486E+10 0.347380E+10 0.00 0.00
June 0.722731E+10 0.865562E+09 0.676519E+10 0.288451E+10 0.388068E+10 0.00 0.00
July 0.626165E+10 0.985407E+09 0.584919E+10 0.221260E+10 0.363659E+10 0.00 0.00
August 0.483752E+10 0.150285E+10 0.480739E+10 0.203570E+10 0.277169E+10 0.00 0.00
September 0.217164E+10 0.257803E+10 0.281557E+10 0.117905E+10 0.163652E+10 0.00 0.00
October 0.361690E+09 0.494241E+10 0.113942E+10 0.342552E+09 0.796871E+09 0.00 0.00
November 38307930.75 0.797819E+10 0.441179E+09 0.160296E+09 0.280883E+09 0.00 0.00
December 0.00 0.916229E+10 40927810.63 4302259.37 36625551.27 0.00 0.00
               
Annual Sum or Average 0.345426E+11 0.532440E+11 0.383386E+11 0.165193E+11 0.218193E+11 0.00 0.00
Minimum of Months 0.00 0.865562E+09 40927810.63 4302259.37 36625551.27 0.00 0.00
Maximum of Months 0.722731E+10 0.916229E+10 0.676519E+10 0.328984E+10 0.388068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.119096E+11 0.168896E+09 0.00 0.168896E+09 0.00 0.00
February 0.00 0.964072E+10 0.674350E+09 0.00 0.674350E+09 0.00 0.00
March 0.171731E+09 0.789935E+10 0.199684E+10 0.00 0.199684E+10 0.00 0.00
April 0.142506E+10 0.405087E+10 0.349631E+10 76984390.17 0.341932E+10 0.00 0.00
May 0.421412E+10 0.188605E+10 0.553726E+10 0.880355E+09 0.465691E+10 0.00 0.00
June 0.673535E+10 0.849783E+09 0.699154E+10 0.155485E+10 0.543669E+10 0.00 0.00
July 0.595915E+10 0.107754E+10 0.606349E+10 0.985567E+09 0.507792E+10 0.00 0.00
August 0.310229E+10 0.179324E+10 0.387179E+10 0.216384E+09 0.365541E+10 0.00 0.00
September 0.776025E+09 0.354043E+10 0.209035E+10 2104837.37 0.208824E+10 0.00 0.00
October 72811921.39 0.678708E+10 0.105104E+10 0.00 0.105104E+10 0.00 0.00
November 0.00 0.112883E+11 0.315655E+09 0.00 0.315655E+09 0.00 0.00
December 0.00 0.125507E+11 51234282.39 0.00 51234282.39 0.00 0.00
               
Annual Sum or Average 0.224565E+11 0.732736E+11 0.323088E+11 0.371624E+10 0.285925E+11 0.00 0.00
Minimum of Months 0.00 0.849783E+09 51234282.39 0.00 51234282.39 0.00 0.00
Maximum of Months 0.673535E+10 0.125507E+11 0.699154E+10 0.155485E+10 0.543669E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 26480022.19 0.769964E+10 0.296613E+09 93347829.41 0.203265E+09 0.00 0.00
February 0.774111E+09 0.582039E+10 0.148021E+10 0.706313E+09 0.773900E+09 0.00 0.00
March 0.386652E+10 0.476847E+10 0.467449E+10 0.236722E+10 0.230727E+10 0.00 0.00
April 0.561857E+10 0.252610E+10 0.621805E+10 0.314568E+10 0.307237E+10 0.00 0.00
May 0.997317E+10 0.137250E+10 0.933414E+10 0.525464E+10 0.407950E+10 0.00 0.00
June 0.919620E+10 0.651277E+09 0.831059E+10 0.387167E+10 0.443892E+10 0.00 0.00
July 0.924019E+10 0.779040E+09 0.815712E+10 0.395014E+10 0.420697E+10 0.00 0.00
August 0.699958E+10 0.121712E+10 0.646096E+10 0.314210E+10 0.331886E+10 0.00 0.00
September 0.350566E+10 0.223126E+10 0.386797E+10 0.169317E+10 0.217480E+10 0.00 0.00
October 0.147651E+10 0.412855E+10 0.211120E+10 0.847137E+09 0.126406E+10 0.00 0.00
November 36459925.16 0.723722E+10 0.434592E+09 0.151861E+09 0.282731E+09 0.00 0.00
December 0.00 0.830983E+10 64159826.11 15358720.65 48801105.47 0.00 0.00
               
Annual Sum or Average 0.507135E+11 0.467414E+11 0.514101E+11 0.252386E+11 0.261715E+11 0.00 0.00
Minimum of Months 0.00 0.651277E+09 64159826.11 15358720.65 48801105.47 0.00 0.00
Maximum of Months 0.997317E+10 0.830983E+10 0.933414E+10 0.525464E+10 0.443892E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.117186E+10 0.107070E+11 0.202622E+10 0.133495E+10 0.691274E+09 0.00 0.00
February 0.524619E+10 0.784102E+10 0.629760E+10 0.438063E+10 0.191697E+10 0.00 0.00
March 0.114532E+11 0.674173E+10 0.119729E+11 0.811538E+10 0.385755E+10 0.00 0.00
April 0.150483E+11 0.430442E+10 0.141354E+11 0.879367E+10 0.534177E+10 0.00 0.00
May 0.132012E+11 0.241425E+10 0.120444E+11 0.624088E+10 0.580353E+10 0.00 0.00
June 0.120052E+11 0.124455E+10 0.106423E+11 0.436199E+10 0.628027E+10 0.00 0.00
July 0.122354E+11 0.137988E+10 0.105953E+11 0.461426E+10 0.598103E+10 0.00 0.00
August 0.124762E+11 0.204675E+10 0.109725E+11 0.604711E+10 0.492539E+10 0.00 0.00
September 0.884085E+10 0.348030E+10 0.858170E+10 0.516834E+10 0.341336E+10 0.00 0.00
October 0.567986E+10 0.579530E+10 0.638482E+10 0.405099E+10 0.233383E+10 0.00 0.00
November 0.217117E+10 0.968548E+10 0.331289E+10 0.231325E+10 0.999636E+09 0.00 0.00
December 0.107700E+09 0.119259E+11 0.607667E+09 0.428322E+09 0.179346E+09 0.00 0.00
               
Annual Sum or Average 0.996372E+11 0.675666E+11 0.975737E+11 0.558498E+11 0.417240E+11 0.00 0.00
Minimum of Months 0.107700E+09 0.124455E+10 0.607667E+09 0.428322E+09 0.179346E+09 0.00 0.00
Maximum of Months 0.150483E+11 0.119259E+11 0.141354E+11 0.879367E+10 0.628027E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.791060E+10 0.156027E+09 27843188.30 0.128184E+09 0.00 0.00
February 0.170324E+09 0.610591E+10 0.831928E+09 0.289287E+09 0.542642E+09 0.00 0.00
March 0.155326E+10 0.493000E+10 0.276458E+10 0.118846E+10 0.157612E+10 0.00 0.00
April 0.593552E+10 0.280467E+10 0.634847E+10 0.328983E+10 0.305865E+10 0.00 0.00
May 0.632592E+10 0.150606E+10 0.637864E+10 0.290485E+10 0.347378E+10 0.00 0.00
June 0.728328E+10 0.795007E+09 0.676516E+10 0.288450E+10 0.388067E+10 0.00 0.00
July 0.634593E+10 0.893241E+09 0.584917E+10 0.221259E+10 0.363657E+10 0.00 0.00
August 0.494334E+10 0.132952E+10 0.480737E+10 0.203570E+10 0.277168E+10 0.00 0.00
September 0.225549E+10 0.232617E+10 0.281556E+10 0.117904E+10 0.163651E+10 0.00 0.00
October 0.415660E+09 0.436271E+10 0.113942E+10 0.342551E+09 0.796868E+09 0.00 0.00
November 48119594.12 0.730023E+10 0.441177E+09 0.160295E+09 0.280882E+09 0.00 0.00
December 0.00 0.842895E+10 40927642.74 4302241.72 36625401.02 0.00 0.00
               
Annual Sum or Average 0.352768E+11 0.486931E+11 0.383384E+11 0.165193E+11 0.218192E+11 0.00 0.00
Minimum of Months 0.00 0.795007E+09 40927642.74 4302241.72 36625401.02 0.00 0.00
Maximum of Months 0.728328E+10 0.842895E+10 0.676516E+10 0.328983E+10 0.388067E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.116721E+11 0.168896E+09 0.00 0.168896E+09 0.00 0.00
February 0.00 0.938853E+10 0.674350E+09 0.00 0.674350E+09 0.00 0.00
March 0.196958E+09 0.759624E+10 0.199684E+10 0.00 0.199684E+10 0.00 0.00
April 0.156176E+10 0.377393E+10 0.349631E+10 76984390.17 0.341932E+10 0.00 0.00
May 0.438447E+10 0.176412E+10 0.553726E+10 0.880355E+09 0.465691E+10 0.00 0.00
June 0.675788E+10 0.820379E+09 0.699154E+10 0.155485E+10 0.543669E+10 0.00 0.00
July 0.598081E+10 0.104515E+10 0.606349E+10 0.985567E+09 0.507792E+10 0.00 0.00
August 0.318009E+10 0.169620E+10 0.387179E+10 0.216384E+09 0.365541E+10 0.00 0.00
September 0.904254E+09 0.318436E+10 0.209035E+10 2104837.37 0.208824E+10 0.00 0.00
October 0.109794E+09 0.637389E+10 0.105104E+10 0.00 0.105104E+10 0.00 0.00
November 0.00 0.110121E+11 0.315655E+09 0.00 0.315655E+09 0.00 0.00
December 0.00 0.123025E+11 51234282.39 0.00 51234282.39 0.00 0.00
               
Annual Sum or Average 0.230760E+11 0.706295E+11 0.323088E+11 0.371624E+10 0.285925E+11 0.00 0.00
Minimum of Months 0.00 0.820379E+09 51234282.39 0.00 51234282.39 0.00 0.00
Maximum of Months 0.675788E+10 0.123025E+11 0.699154E+10 0.155485E+10 0.543669E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 27315399.81 0.755332E+10 0.296613E+09 93347829.41 0.203265E+09 0.00 0.00
February 0.790046E+09 0.566753E+10 0.148021E+10 0.706313E+09 0.773900E+09 0.00 0.00
March 0.392663E+10 0.457115E+10 0.467449E+10 0.236722E+10 0.230727E+10 0.00 0.00
April 0.571030E+10 0.237168E+10 0.621805E+10 0.314568E+10 0.307237E+10 0.00 0.00
May 0.100190E+11 0.131256E+10 0.933414E+10 0.525464E+10 0.407950E+10 0.00 0.00
June 0.919420E+10 0.637306E+09 0.831059E+10 0.387167E+10 0.443892E+10 0.00 0.00
July 0.923540E+10 0.765252E+09 0.815712E+10 0.395014E+10 0.420697E+10 0.00 0.00
August 0.701821E+10 0.117530E+10 0.646096E+10 0.314210E+10 0.331886E+10 0.00 0.00
September 0.359107E+10 0.205064E+10 0.386797E+10 0.169317E+10 0.217480E+10 0.00 0.00
October 0.153070E+10 0.387705E+10 0.211120E+10 0.847137E+09 0.126406E+10 0.00 0.00
November 38433135.49 0.706420E+10 0.434592E+09 0.151861E+09 0.282731E+09 0.00 0.00
December 0.00 0.816003E+10 64159826.11 15358720.65 48801105.47 0.00 0.00
               
Annual Sum or Average 0.510813E+11 0.452060E+11 0.514101E+11 0.252386E+11 0.261715E+11 0.00 0.00
Minimum of Months 0.00 0.637306E+09 64159826.11 15358720.65 48801105.47 0.00 0.00
Maximum of Months 0.100190E+11 0.816003E+10 0.933414E+10 0.525464E+10 0.443892E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.118972E+10 0.104852E+11 0.202622E+10 0.133495E+10 0.691274E+09 0.00 0.00
February 0.531671E+10 0.759015E+10 0.629760E+10 0.438063E+10 0.191697E+10 0.00 0.00
March 0.115657E+11 0.642711E+10 0.119729E+11 0.811538E+10 0.385755E+10 0.00 0.00
April 0.151497E+11 0.404617E+10 0.141354E+11 0.879367E+10 0.534177E+10 0.00 0.00
May 0.132557E+11 0.228762E+10 0.120444E+11 0.624088E+10 0.580353E+10 0.00 0.00
June 0.120061E+11 0.121192E+10 0.106423E+11 0.436199E+10 0.628027E+10 0.00 0.00
July 0.122331E+11 0.135033E+10 0.105953E+11 0.461426E+10 0.598103E+10 0.00 0.00
August 0.124985E+11 0.197083E+10 0.109725E+11 0.604711E+10 0.492539E+10 0.00 0.00
September 0.895253E+10 0.321174E+10 0.858170E+10 0.516834E+10 0.341336E+10 0.00 0.00
October 0.580341E+10 0.542240E+10 0.638482E+10 0.405099E+10 0.233383E+10 0.00 0.00
November 0.220886E+10 0.941830E+10 0.331289E+10 0.231325E+10 0.999636E+09 0.00 0.00
December 0.109941E+09 0.116907E+11 0.607667E+09 0.428322E+09 0.179346E+09 0.00 0.00
               
Annual Sum or Average 0.100290E+12 0.651125E+11 0.975737E+11 0.558498E+11 0.417240E+11 0.00 0.00
Minimum of Months 0.109941E+09 0.121192E+10 0.607667E+09 0.428322E+09 0.179346E+09 0.00 0.00
Maximum of Months 0.151497E+11 0.116907E+11 0.141354E+11 0.879367E+10 0.628027E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.774922E+10 0.156027E+09 27843188.30 0.128184E+09 0.00 0.00
February 0.175511E+09 0.595313E+10 0.831928E+09 0.289287E+09 0.542642E+09 0.00 0.00
March 0.158430E+10 0.474154E+10 0.276458E+10 0.118846E+10 0.157612E+10 0.00 0.00
April 0.600542E+10 0.264022E+10 0.634847E+10 0.328983E+10 0.305865E+10 0.00 0.00
May 0.637583E+10 0.142804E+10 0.637864E+10 0.290485E+10 0.347378E+10 0.00 0.00
June 0.728546E+10 0.775239E+09 0.676516E+10 0.288450E+10 0.388067E+10 0.00 0.00
July 0.634690E+10 0.873177E+09 0.584917E+10 0.221259E+10 0.363657E+10 0.00 0.00
August 0.496746E+10 0.127788E+10 0.480737E+10 0.203570E+10 0.277168E+10 0.00 0.00
September 0.232067E+10 0.215257E+10 0.281556E+10 0.117904E+10 0.163651E+10 0.00 0.00
October 0.445806E+09 0.412806E+10 0.113942E+10 0.342551E+09 0.796868E+09 0.00 0.00
November 50807488.65 0.712655E+10 0.441177E+09 0.160295E+09 0.280882E+09 0.00 0.00
December 0.00 0.827339E+10 40927642.74 4302241.72 36625401.02 0.00 0.00
               
Annual Sum or Average 0.355582E+11 0.471190E+11 0.383384E+11 0.165193E+11 0.218192E+11 0.00 0.00
Minimum of Months 0.00 0.775239E+09 40927642.74 4302241.72 36625401.02 0.00 0.00
Maximum of Months 0.728546E+10 0.827339E+10 0.676516E+10 0.328983E+10 0.388067E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January -17.6 -17.9 -19.9 1.62 -32.2 4.20 17.57 0.00
February -15.4 -16.0 -18.9 1.58 -31.2 17.68 68.90 0.00
March -10.3 -11.6 -17.1 2.46 -25.4 47.11 147.56 0.00
April 0.73 -2.7 -8.8 3.74 -14.2 75.81 230.75 0.00
May 10.60 5.25 -1.5 3.99 -2.1 92.54 252.99 0.00
June 15.96 10.88 6.41 3.45 5.66 116.77 222.76 0.00
July 16.86 12.85 9.90 2.85 7.58 107.92 197.90 0.00
August 14.24 10.70 7.59 2.94 4.33 81.01 176.65 0.00
September 6.72 4.45 1.76 2.11 -4.1 51.38 110.92 0.00
October -3.1 -4.4 -7.1 2.79 -14.3 26.50 62.95 0.00
November -17.6 -18.1 -20.3 0.70 -32.8 8.03 31.72 0.00
December -19.3 -19.6 -21.9 1.25 -33.6 1.27 5.23 0.00
                 
Annual Sum or Average -1.4 -3.8 -7.4 2.46 -14.3 52.69 127.40 0.00
Minimum of Months -19.3 -19.6 -21.9 0.70 -33.6 1.27 5.23 0.00
Maximum of Months 16.86 12.85 9.90 3.99 7.58 116.77 252.99 0.00



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -1.1 21-JAN-20:00 -2.7 -5.6 0.00 -9.0 0.00 0.00
February 2.80 08-FEB-15:09 -0.7 -6.5 2.68 -7.9 21.67 32.33
March 6.70 20-MAR-14:09 2.60 -3.5 1.37 -7.5 138.33 487.67
April 15.60 22-APR-13:00 7.03 -3.3 4.10 -0.8 117.50 760.50
May 22.20 31-MAY-15:00 10.79 -1.1 3.10 7.75 143.50 516.50
June 28.30 30-JUN-14:00 17.30 10.60 6.20 17.57 223.50 277.50
July 30.00 29-JUL-16:19 18.34 11.70 4.67 18.88 163.67 322.83
August 25.60 11-AUG-15:00 14.77 6.70 6.20 12.22 99.50 604.00
September 17.20 07-SEP-15:00 8.91 0.00 1.50 2.64 77.00 480.50
October 13.90 01-OCT-14:00 8.01 1.70 2.60 1.58 78.50 227.50
November -3.9 18-NOV-03:00 -5.6 -8.9 1.50 -12.4 0.00 0.00
December 1.70 24-DEC-11:00 -0.1 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -3.9   -5.6 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 30.00   18.34 11.70 6.20 18.88 223.50 760.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -38.3 12-JAN-05:00 -38.4 -40.4 0.00 -60.9 0.00 0.00
February -36.1 27-FEB-04:00 -36.2 -39.4 0.00 -58.7 0.00 0.00
March -28.9 01-MAR-00:10 -29.2 -34.0 0.65 -51.0 0.00 0.00
April -21.7 03-APR-05:00 -22.3 -27.2 2.60 -42.7 0.00 0.00
May 0.00 27-MAY-03:00 -1.1 -2.8 6.20 -7.1 29.00 14.00
June 3.30 02-JUN-03:00 2.38 1.10 1.50 -11.2 45.50 266.00
July 7.20 31-JUL-03:49 6.67 6.10 2.18 -7.6 0.00 0.00
August -1.7 31-AUG-05:00 -2.9 -5.0 2.60 -18.6 25.00 538.50
September -5.6 29-SEP-06:00 -6.1 -7.2 2.60 -21.6 0.00 0.00
October -20.6 22-OCT-05:00 -20.8 -22.2 2.60 -40.2 0.00 0.00
November -30.0 29-NOV-09:00 -30.2 -33.3 0.00 -51.8 0.00 0.00
December -33.9 15-DEC-07:00 -34.0 -37.8 0.00 -56.5 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -38.3   -38.4 -40.4 0.00 -60.9 0.00 0.00
Maximum of Months 7.20   6.67 6.10 6.20 -7.1 45.50 538.50



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -2.7 21-JAN-20:00 -1.1 -5.6 0.00 -9.0 0.00 0.00
February 1.24 09-FEB-01:00 2.80 -1.1 8.80 -4.1 0.00 0.00
March 2.65 20-MAR-13:00 6.70 -3.3 0.00 -7.6 139.00 515.00
April 7.03 22-APR-13:00 15.60 -3.3 4.10 -0.8 117.50 760.50
May 10.97 31-MAY-17:00 21.70 0.00 2.60 11.07 73.50 187.00
June 18.33 30-JUN-11:00 25.60 14.40 1.50 15.21 221.00 616.00
July 18.36 29-JUL-17:19 29.07 12.23 3.10 19.29 141.00 225.33
August 16.14 04-AUG-19:00 21.70 12.80 3.10 14.28 25.50 28.50
September 10.82 01-SEP-15:00 15.60 6.70 2.60 4.31 145.50 176.00
October 8.01 01-OCT-14:00 13.90 1.70 2.60 1.58 78.50 227.50
November -5.6 18-NOV-03:00 -3.9 -8.9 1.50 -12.4 0.00 0.00
December -0.1 24-DEC-11:00 1.70 -2.8 2.60 -8.8 13.50 31.50
                 
Annual Sum or Average                
Minimum of Months -5.6   -3.9 -8.9 0.00 -12.4 0.00 0.00
Maximum of Months 18.36   29.07 14.40 8.80 19.29 221.00 760.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January -4.4 06-JAN-19:00 -1.7 -2.7 2.60 -12.4 0.00 0.00
February -0.6 09-FEB-00:00 1.70 0.78 3.60 -5.0 0.00 0.00
March 0.00 21-MAR-15:00 1.10 0.62 2.10 -5.5 70.50 4.00
April 0.00 30-APR-07:00 3.30 1.91 2.60 -8.3 198.00 170.00
May 6.10 16-MAY-19:00 8.90 7.49 5.20 3.69 16.00 15.00
June 15.60 30-JUN-17:00 18.90 16.75 3.60 12.22 99.50 223.00
July 17.80 03-JUL-14:00 19.40 18.27 1.50 10.11 223.00 401.50
August 15.00 12-AUG-22:00 16.10 15.38 0.00 12.79 0.00 0.00
September 8.90 04-SEP-11:00 10.00 9.41 2.60 5.33 238.50 0.50
October 5.60 02-OCT-11:09 7.30 6.41 4.95 0.30 123.67 16.00
November -8.3 18-NOV-04:00 -5.0 -6.1 1.50 -13.4 0.00 0.00
December -2.8 24-DEC-09:00 1.10 -0.5 3.10 -6.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -8.3   -5.0 -6.1 0.00 -13.4 0.00 0.00
Maximum of Months 17.80   19.40 18.27 5.20 12.79 238.50 401.50



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 0.00 1.10 0.00
February 18.00 13.00 16.00 0.00 5.89 0.00
March 18.00 13.00 16.00 0.00 18.25 0.00
April 18.00 13.00 16.00 0.00 35.02 0.00
May 18.00 13.00 16.00 0.44 43.39 0.00
June 18.00 13.00 16.00 2.62 46.67 0.00
July 18.00 13.00 16.00 4.74 42.09 0.00
August 18.00 13.00 16.00 6.08 32.30 0.00
September 18.00 13.00 16.00 6.25 18.21 0.00
October 18.00 13.00 16.00 5.21 8.04 0.00
November 18.00 13.00 16.00 3.27 2.12 0.00
December 18.00 13.00 16.00 0.94 0.28 0.00
             
Annual Sum or Average 18.00 13.00 16.00 2.48 21.19 0.00
Minimum of Months 18.00 13.00 16.00 0.00 0.28 0.00
Maximum of Months 18.00 13.00 16.00 6.25 46.67 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.480387E+11 -0.469738E+11 0.00 0.00 744.00 0.00 -0.106488E+10 58.97 0.00 0.00
February 0.436322E+11 -0.426845E+11 0.00 0.00 672.00 0.00 -947671336.3 58.97 0.00 0.00
March 0.512581E+11 -0.502196E+11 0.00 0.00 744.00 0.00 -0.103853E+10 58.97 0.00 0.00
April 0.465253E+11 -0.455310E+11 0.00 0.00 720.00 0.00 -994307727.7 58.96 0.00 0.00
May 0.492860E+11 -0.482590E+11 0.00 0.00 744.00 0.00 -0.102695E+10 58.97 0.00 0.00
June 0.470801E+11 -0.460863E+11 0.00 0.00 720.00 0.00 -993873373.4 58.99 0.00 0.00
July 0.431860E+11 -0.421656E+11 0.00 0.00 744.00 0.00 -0.102034E+10 58.98 0.00 0.00
August 0.460699E+11 -0.450450E+11 0.00 0.00 744.00 0.00 -0.102487E+10 58.99 0.00 0.00
September 0.417040E+11 -0.407130E+11 0.00 0.00 720.00 0.00 -990948041.2 58.99 0.00 0.00
October 0.438591E+11 -0.428326E+11 0.00 0.00 744.00 0.00 -0.102647E+10 58.98 0.00 0.00
November 0.445470E+11 -0.435385E+11 0.00 0.00 720.00 0.00 -0.100850E+10 58.98 0.00 0.00
December 0.461808E+11 -0.451245E+11 0.00 0.00 744.00 0.00 -0.105635E+10 58.98 0.00 0.00
                     
Annual Sum or Average 0.551367E+12 -0.539173E+12 0.00 0.00 8760.00 0.00 -0.121937E+11 58.98 0.00 0.00
Minimum of Months 0.417040E+11 -0.502196E+11 0.00 0.00 672.00 0.00 -0.106488E+10 58.96 0.00 0.00
Maximum of Months 0.512581E+11 -0.407130E+11 0.00 0.00 744.00 0.00 -947671336.3 58.99 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.72 0.61 03-JAN-11:30 490.36 9.67 0.00 55.67 394.78 15.50 5.50 34.00
February 205.83 0.66 0.61 01-FEB-10:50 1199.18 13.70 0.00 164.50 2047.98 32.33 158.33 146.33
March 329.50 0.64 0.61 01-MAR-09:20 5612.75 31.55 269.17 295.00 5052.63 33.81 283.50 277.67
April 421.83 0.64 0.61 01-APR-07:10 8240.58 30.36 283.67 374.33 1437.11 20.99 247.33 326.67
May 545.00 0.65 0.61 01-MAY-04:00 4614.58 21.43 144.67 440.83 1050.27 19.65 252.17 379.33
June 583.50 0.66 0.61 01-JUN-04:10 1782.38 16.44 0.00 462.50 966.16 19.40 269.67 391.67
July 562.83 0.65 0.61 01-JUL-03:00 2167.69 17.11 15.67 459.67 986.79 19.48 259.00 384.50
August 467.17 0.65 0.61 01-AUG-04:49 5868.55 25.81 241.33 397.17 1111.72 20.12 226.33 341.33
September 356.33 0.65 0.61 01-SEP-06:40 4644.04 29.55 264.33 312.50 1523.49 21.56 188.67 270.00
October 265.50 0.65 0.61 01-OCT-07:40 2380.97 26.65 171.33 226.83 2083.14 31.72 218.83 204.00
November 135.83 0.68 0.61 01-NOV-09:50 619.04 11.66 0.00 105.33 541.43 21.43 36.17 70.83
December 71.17 0.85 0.61 04-DEC-11:09 146.01 5.03 0.00 1.17 105.51 9.76 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     3830.02 22.10 1390.17 3295.50 1510.77 22.31 2145.50 2826.33
Minimum of Months 71.17 0.64 0.61   146.01 5.03 0.00 1.17 105.51 9.76 0.00 0.00
Maximum of Months 583.50 0.85 0.61   8240.58 31.55 283.67 462.50 5052.63 33.81 283.50 391.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.79 0.61 14-JAN-12:20 234.26 8.84 2.83 21.67 157.78 19.04 43.17 9.00
February 205.83 0.69 0.61 01-FEB-10:50 862.92 18.29 72.00 132.00 519.11 17.12 48.67 82.67
March 329.50 0.66 0.61 01-MAR-09:20 2021.51 17.91 83.17 270.00 1357.92 19.13 88.00 223.83
April 421.83 0.64 0.61 01-APR-06:49 2555.62 17.55 80.83 375.33 1753.45 17.64 51.50 333.50
May 545.00 0.65 0.61 01-MAY-04:40 3722.16 16.09 86.67 450.33 1938.20 14.41 0.00 401.17
June 583.50 0.65 0.61 01-JUN-03:20 3250.75 15.58 76.33 482.33 1403.62 14.44 0.00 418.50
July 562.83 0.65 0.61 01-JUL-03:39 3154.96 15.68 79.33 467.67 1672.61 14.32 0.00 408.00
August 467.17 0.65 0.61 01-AUG-04:40 2549.83 16.51 85.00 399.33 1294.66 14.87 5.33 344.00
September 356.33 0.66 0.61 01-SEP-06:19 1979.50 17.87 99.83 288.50 1045.93 16.61 50.83 236.50
October 265.50 0.67 0.61 01-OCT-07:30 1017.55 17.19 74.83 199.67 620.82 17.33 63.83 137.67
November 135.83 0.74 0.61 01-NOV-09:50 318.23 16.17 36.50 54.00 172.64 11.57 0.00 7.83
December 71.17 0.91 0.71 04-DEC-11:30 85.18 4.55 0.00 0.00 49.80 5.98 0.00 0.00
                         
Annual Sum or Average 4053.17 0.67     2433.73 16.25 777.33 3140.83 1306.92 15.58 351.33 2602.67
Minimum of Months 71.17 0.64 0.61   85.18 4.55 0.00 0.00 49.80 5.98 0.00 0.00
Maximum of Months 583.50 0.91 0.71   3722.16 18.29 99.83 482.33 1938.20 19.13 88.00 418.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.85 0.61 28-JAN-11:30 148.08 0.00 0.00 1.50 86.37 0.00 0.00 0.00
February 205.83 0.72 0.61 01-FEB-12:09 327.19 0.00 0.00 83.50 193.16 0.00 0.00 10.83
March 329.50 0.66 0.61 01-MAR-09:50 605.37 0.00 0.00 258.17 359.13 0.00 0.00 163.67
April 421.83 0.63 0.61 01-APR-07:10 786.92 0.00 0.00 385.50 495.40 0.00 0.00 318.17
May 545.00 0.64 0.61 01-MAY-04:40 970.84 0.00 0.00 493.17 568.67 0.00 0.00 439.17
June 583.50 0.64 0.61 01-JUN-03:09 1178.65 0.00 0.00 524.50 667.89 0.00 0.00 487.17
July 562.83 0.64 0.61 01-JUL-03:39 1041.87 0.00 0.00 507.33 605.75 0.00 0.00 449.17
August 467.17 0.64 0.61 01-AUG-04:40 829.95 0.00 0.00 415.83 493.26 0.00 0.00 345.67
September 356.33 0.66 0.61 01-SEP-06:40 594.96 0.00 0.00 284.17 342.50 0.00 0.00 162.17
October 265.50 0.68 0.61 01-OCT-07:49 417.12 0.00 0.00 164.33 229.84 0.00 0.00 16.00
November 135.83 0.80 0.61 01-NOV-09:00 198.94 0.00 0.00 12.00 114.10 0.00 0.00 0.00
December 71.17 0.94 0.83 04-DEC-11:30 58.08 0.00 0.00 0.00 34.32 0.00 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     779.57 0.00 0.00 3130.00 456.06 0.00 0.00 2392.00
Minimum of Months 71.17 0.63 0.61   58.08 0.00 0.00 0.00 34.32 0.00 0.00 0.00
Maximum of Months 583.50 0.94 0.83   1178.65 0.00 0.00 524.50 667.89 0.00 0.00 487.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.80 0.61 21-JAN-11:50 201.07 8.47 2.33 11.00 130.53 18.23 35.50 3.33
February 205.83 0.68 0.61 01-FEB-11:30 702.86 18.59 71.33 136.50 415.01 17.45 47.17 66.50
March 329.50 0.65 0.61 01-MAR-09:50 1568.12 17.77 76.17 280.50 973.98 18.97 69.00 236.50
April 421.83 0.64 0.61 01-APR-07:40 3100.46 19.12 110.83 375.67 1563.69 17.72 53.00 328.33
May 545.00 0.64 0.61 01-MAY-05:10 2454.27 14.88 55.67 465.33 1253.54 16.51 48.67 414.17
June 583.50 0.65 0.61 01-JUN-04:10 2686.83 14.82 51.00 492.17 1359.80 17.15 73.83 431.67
July 562.83 0.64 0.61 01-JUL-03:00 2312.69 14.89 55.50 482.83 1196.47 17.06 66.00 419.83
August 467.17 0.64 0.61 01-AUG-04:00 2082.51 16.60 82.17 409.00 1277.38 16.70 52.17 353.67
September 356.33 0.65 0.61 01-SEP-06:49 1665.43 18.47 97.83 305.00 1033.74 18.31 72.83 241.83
October 265.50 0.66 0.61 01-OCT-07:49 822.62 16.94 69.00 202.33 487.04 17.97 61.00 112.33
November 135.83 0.74 0.61 01-NOV-09:00 335.40 14.69 34.50 54.83 210.81 17.60 35.33 17.33
December 71.17 0.92 0.78 04-DEC-11:30 74.47 4.04 0.00 0.00 43.04 5.34 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     1982.08 16.02 706.33 3215.17 1074.79 17.21 614.50 2625.50
Minimum of Months 71.17 0.64 0.61   74.47 4.04 0.00 0.00 43.04 5.34 0.00 0.00
Maximum of Months 583.50 0.92 0.78   3100.46 19.12 110.83 492.17 1563.69 18.97 73.83 431.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.72 0.61 08-JAN-11:30 471.91 3.10 0.00 53.00 402.90 9.63 5.50 34.00
February 205.83 0.66 0.61 01-FEB-10:50 1166.25 6.59 0.00 162.50 2073.93 30.98 154.67 147.00
March 329.50 0.65 0.61 01-MAR-09:20 5532.67 30.60 265.67 291.83 5101.45 33.20 276.83 278.33
April 421.83 0.64 0.61 01-APR-07:10 8189.10 28.75 283.67 372.17 1488.16 16.77 0.00 329.00
May 545.00 0.65 0.61 01-MAY-04:00 4579.73 17.71 144.33 438.50 1086.87 15.73 0.00 383.00
June 583.50 0.66 0.61 01-JUN-04:19 1741.13 10.81 0.00 459.67 996.42 15.38 0.00 394.67
July 562.83 0.66 0.61 01-JUL-04:10 2125.94 11.59 15.67 456.33 1018.01 15.39 0.00 387.67
August 467.17 0.65 0.61 01-AUG-04:49 5823.32 23.33 237.50 395.50 1149.14 15.82 0.00 344.17
September 356.33 0.65 0.61 01-SEP-06:40 4211.26 26.43 240.00 311.83 1558.40 17.38 26.50 271.17
October 265.50 0.65 0.61 01-OCT-07:40 1172.23 8.11 0.00 224.67 2084.73 30.05 207.17 205.17
November 135.83 0.68 0.61 01-NOV-09:50 594.24 4.62 0.00 102.00 461.94 10.56 0.00 68.33
December 71.17 0.86 0.61 04-DEC-11:20 133.24 0.53 0.00 0.00 104.02 4.08 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     3676.07 17.15 1186.83 3268.00 1540.00 18.49 670.67 2842.50
Minimum of Months 71.17 0.64 0.61   133.24 0.53 0.00 0.00 104.02 4.08 0.00 0.00
Maximum of Months 583.50 0.86 0.61   8189.10 30.60 283.67 459.67 5101.45 33.20 276.83 394.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.79 0.61 14-JAN-12:30 229.28 6.13 1.83 20.67 160.90 15.58 41.50 9.33
February 205.83 0.69 0.61 01-FEB-11:20 713.83 13.54 46.83 131.00 530.83 15.25 46.17 84.33
March 329.50 0.66 0.61 01-MAR-09:20 2002.03 15.65 82.17 269.67 1385.71 17.29 81.17 227.50
April 421.83 0.64 0.61 01-APR-06:49 2550.83 15.03 80.83 374.17 1787.58 15.36 51.50 335.67
May 545.00 0.65 0.61 01-MAY-04:40 3438.58 13.50 86.67 449.67 1976.97 11.97 0.00 404.50
June 583.50 0.65 0.61 01-JUN-03:20 3114.41 12.98 75.83 480.83 1436.49 12.17 0.00 422.33
July 562.83 0.65 0.61 01-JUL-03:39 3149.37 13.07 78.83 466.67 1706.10 11.95 0.00 412.67
August 467.17 0.65 0.61 01-AUG-04:40 2542.69 14.02 84.83 398.17 1325.17 12.39 5.33 346.33
September 356.33 0.66 0.61 01-SEP-06:19 1970.45 15.87 100.00 287.33 1040.08 14.30 47.00 240.67
October 265.50 0.67 0.61 01-OCT-07:30 1010.75 14.98 75.00 198.67 583.33 14.53 50.50 141.33
November 135.83 0.74 0.61 01-NOV-09:50 313.60 12.24 35.00 52.83 211.39 14.45 35.17 14.00
December 71.17 0.91 0.72 04-DEC-11:30 83.40 2.95 0.00 0.00 50.82 4.22 0.00 0.00
                         
Annual Sum or Average 4053.17 0.67     2363.16 13.64 747.83 3129.67 1329.87 13.41 358.33 2638.67
Minimum of Months 71.17 0.64 0.61   83.40 2.95 0.00 0.00 50.82 4.22 0.00 0.00
Maximum of Months 583.50 0.91 0.72   3438.58 15.87 100.00 480.83 1976.97 17.29 81.17 422.33



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.85 0.61 28-JAN-11:50 142.92 0.00 0.00 1.00 87.70 0.00 0.00 0.00
February 205.83 0.72 0.61 01-FEB-12:20 317.51 0.00 0.00 77.17 196.97 0.00 0.00 12.33
March 329.50 0.66 0.61 01-MAR-09:50 590.81 0.00 0.00 255.17 367.83 0.00 0.00 172.00
April 421.83 0.64 0.61 01-APR-07:10 770.61 0.00 0.00 384.00 508.36 0.00 0.00 323.00
May 545.00 0.64 0.61 01-MAY-04:40 952.57 0.00 0.00 491.83 604.85 0.00 0.00 457.33
June 583.50 0.64 0.61 01-JUN-03:09 1107.02 0.00 0.00 522.33 684.72 0.00 0.00 488.83
July 562.83 0.64 0.61 01-JUL-03:39 1020.68 0.00 0.00 505.33 621.68 0.00 0.00 452.17
August 467.17 0.64 0.61 01-AUG-04:40 808.31 0.00 0.00 411.50 506.06 0.00 0.00 350.17
September 356.33 0.66 0.61 01-SEP-06:40 581.19 0.00 0.00 280.50 351.16 0.00 0.00 170.00
October 265.50 0.68 0.61 01-OCT-07:49 406.52 0.00 0.00 158.00 235.36 0.00 0.00 18.50
November 135.83 0.81 0.61 01-NOV-09:00 192.50 0.00 0.00 10.17 116.10 0.00 0.00 0.00
December 71.17 0.94 0.83 04-DEC-11:30 55.81 0.00 0.00 0.00 34.73 0.00 0.00 0.00
                         
Annual Sum or Average 4053.17 0.67     755.70 0.00 0.00 3097.00 470.51 0.00 0.00 2444.33
Minimum of Months 71.17 0.64 0.61   55.81 0.00 0.00 0.00 34.73 0.00 0.00 0.00
Maximum of Months 583.50 0.94 0.83   1107.02 0.00 0.00 522.33 684.72 0.00 0.00 488.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.80 0.61 21-JAN-11:50 197.88 5.90 2.33 10.50 133.28 14.75 32.50 3.67
February 205.83 0.68 0.61 01-FEB-11:30 698.04 16.95 71.33 134.83 424.27 15.51 45.67 68.33
March 329.50 0.65 0.61 01-MAR-09:50 1564.30 15.66 76.50 279.50 995.47 17.01 64.83 239.33
April 421.83 0.64 0.61 01-APR-07:40 3098.73 16.89 110.83 374.67 1597.46 15.46 53.00 330.67
May 545.00 0.64 0.61 01-MAY-05:10 2449.02 12.07 55.67 464.33 1282.55 14.35 48.83 419.00
June 583.50 0.65 0.61 01-JUN-04:19 2678.41 11.97 51.00 490.33 1388.28 15.19 73.83 436.50
July 562.83 0.64 0.61 01-JUL-03:00 2304.87 12.11 55.50 481.67 1212.57 14.02 48.50 420.00
August 467.17 0.64 0.61 01-AUG-04:00 2054.33 13.94 79.00 408.17 1291.67 14.54 52.17 356.00
September 356.33 0.65 0.61 01-SEP-06:49 1542.12 14.70 77.00 303.17 1019.08 16.40 73.17 243.17
October 265.50 0.66 0.61 01-OCT-07:49 810.94 14.29 62.50 201.00 497.33 16.02 61.50 119.00
November 135.83 0.75 0.61 01-NOV-09:00 297.57 6.87 0.00 48.83 215.54 14.24 34.67 17.83
December 71.17 0.93 0.79 04-DEC-11:30 73.06 2.39 0.00 0.00 43.94 3.56 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     1962.11 13.19 641.67 3197.00 1092.04 14.95 588.67 2653.50
Minimum of Months 71.17 0.64 0.61   73.06 2.39 0.00 0.00 43.94 3.56 0.00 0.00
Maximum of Months 583.50 0.93 0.79   3098.73 16.95 110.83 490.33 1597.46 17.01 73.83 436.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.72 0.61 08-JAN-11:30 471.34 3.06 0.00 53.00 402.94 9.61 5.50 34.00
February 205.83 0.66 0.61 01-FEB-10:50 1164.89 6.54 0.00 162.50 2074.16 30.97 154.67 147.00
March 329.50 0.65 0.61 01-MAR-09:20 5530.98 30.58 265.67 291.83 5102.64 33.19 276.83 278.33
April 421.83 0.64 0.61 01-APR-07:10 8188.50 28.73 283.67 372.17 1489.80 16.75 0.00 329.00
May 545.00 0.66 0.61 01-MAY-04:00 4580.24 17.68 144.33 438.33 1088.13 15.71 0.00 383.17
June 583.50 0.66 0.61 01-JUN-04:19 1741.93 10.78 0.00 459.33 997.70 15.36 0.00 394.67
July 562.83 0.66 0.61 01-JUL-04:10 2126.71 11.55 15.67 456.33 1019.34 15.37 0.00 387.83
August 467.17 0.65 0.61 01-AUG-04:49 5823.56 23.30 237.50 395.50 1150.57 15.81 0.00 344.17
September 356.33 0.65 0.61 01-SEP-06:40 4210.52 26.41 239.83 311.83 1559.69 17.36 26.50 271.17
October 265.50 0.65 0.61 01-OCT-07:40 1171.46 8.07 0.00 224.67 2085.41 30.04 207.17 205.17
November 135.83 0.68 0.61 01-NOV-09:50 593.55 4.58 0.00 102.00 462.06 10.53 0.00 68.33
December 71.17 0.86 0.61 04-DEC-11:20 133.00 0.51 0.00 0.00 104.01 4.06 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     3675.96 17.12 1186.67 3267.50 1541.14 18.47 670.67 2842.83
Minimum of Months 71.17 0.64 0.61   133.00 0.51 0.00 0.00 104.01 4.06 0.00 0.00
Maximum of Months 583.50 0.86 0.61   8188.50 30.58 283.67 459.33 5102.64 33.19 276.83 394.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.79 0.61 14-JAN-12:30 229.14 6.12 1.83 20.67 161.04 15.58 41.50 9.33
February 205.83 0.69 0.61 01-FEB-11:20 713.49 13.53 46.83 130.83 531.16 15.24 46.17 84.83
March 329.50 0.66 0.61 01-MAR-09:20 2001.31 15.63 82.17 269.67 1386.36 17.28 81.17 227.67
April 421.83 0.64 0.61 01-APR-06:49 2549.89 15.02 80.83 374.00 1788.44 15.36 51.50 335.83
May 545.00 0.65 0.61 01-MAY-04:40 3437.80 13.49 86.67 449.50 1977.92 11.96 0.00 404.50
June 583.50 0.65 0.61 01-JUN-03:20 3114.08 12.97 75.83 480.67 1437.58 12.17 0.00 422.67
July 562.83 0.65 0.61 01-JUL-03:39 3148.96 13.06 78.83 466.67 1707.17 11.94 0.00 412.67
August 467.17 0.65 0.61 01-AUG-04:40 2542.26 14.01 84.83 398.17 1326.13 12.38 5.33 346.33
September 356.33 0.66 0.61 01-SEP-06:19 1969.95 15.86 100.00 287.33 1040.81 14.29 47.00 240.67
October 265.50 0.67 0.61 01-OCT-07:30 1010.55 14.97 75.00 198.67 583.82 14.53 50.50 141.50
November 135.83 0.74 0.61 01-NOV-09:50 313.47 12.23 35.00 52.83 211.57 14.44 35.17 14.00
December 71.17 0.91 0.72 04-DEC-11:30 83.34 2.94 0.00 0.00 50.87 4.21 0.00 0.00
                         
Annual Sum or Average 4053.17 0.67     2362.66 13.63 747.83 3129.00 1330.68 13.41 358.33 2640.00
Minimum of Months 71.17 0.64 0.61   83.34 2.94 0.00 0.00 50.87 4.21 0.00 0.00
Maximum of Months 583.50 0.91 0.72   3437.80 15.86 100.00 480.67 1977.92 17.28 81.17 422.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.85 0.61 28-JAN-11:50 142.87 0.00 0.00 1.00 87.79 0.00 0.00 0.00
February 205.83 0.72 0.61 01-FEB-12:20 317.43 0.00 0.00 77.17 197.16 0.00 0.00 12.50
March 329.50 0.66 0.61 01-MAR-09:50 590.71 0.00 0.00 254.83 368.18 0.00 0.00 172.50
April 421.83 0.64 0.61 01-APR-07:10 770.36 0.00 0.00 383.83 508.77 0.00 0.00 323.17
May 545.00 0.64 0.61 01-MAY-04:40 952.34 0.00 0.00 491.67 605.33 0.00 0.00 457.33
June 583.50 0.64 0.61 01-JUN-03:09 1106.85 0.00 0.00 522.33 685.31 0.00 0.00 489.00
July 562.83 0.64 0.61 01-JUL-03:39 1020.62 0.00 0.00 505.33 622.27 0.00 0.00 452.17
August 467.17 0.64 0.61 01-AUG-04:40 808.27 0.00 0.00 411.50 506.56 0.00 0.00 350.17
September 356.33 0.66 0.61 01-SEP-06:40 581.18 0.00 0.00 280.50 351.54 0.00 0.00 170.00
October 265.50 0.68 0.61 01-OCT-07:49 406.58 0.00 0.00 158.00 235.64 0.00 0.00 18.50
November 135.83 0.81 0.61 01-NOV-09:00 192.46 0.00 0.00 10.33 116.22 0.00 0.00 0.00
December 71.17 0.94 0.83 04-DEC-11:30 55.78 0.00 0.00 0.00 34.76 0.00 0.00 0.00
                         
Annual Sum or Average 4053.17 0.67     755.59 0.00 0.00 3096.50 470.94 0.00 0.00 2445.33
Minimum of Months 71.17 0.64 0.61   55.78 0.00 0.00 0.00 34.76 0.00 0.00 0.00
Maximum of Months 583.50 0.94 0.83   1106.85 0.00 0.00 522.33 685.31 0.00 0.00 489.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 108.67 0.80 0.61 21-JAN-11:50 197.79 5.89 2.33 10.50 133.40 14.75 32.50 3.67
February 205.83 0.68 0.61 01-FEB-11:30 697.81 16.94 71.33 134.50 424.56 15.50 45.67 68.50
March 329.50 0.65 0.61 01-MAR-09:50 1563.94 15.65 76.50 279.50 996.02 17.00 64.83 239.67
April 421.83 0.64 0.61 01-APR-07:40 3097.78 16.88 110.83 374.50 1598.27 15.45 53.00 330.83
May 545.00 0.64 0.61 01-MAY-05:10 2448.59 12.06 55.67 464.33 1283.39 14.35 48.83 419.00
June 583.50 0.65 0.61 01-JUN-04:19 2678.17 11.96 51.00 490.33 1389.22 15.18 73.83 436.50
July 562.83 0.64 0.61 01-JUL-03:00 2304.72 12.10 55.50 481.67 1213.51 14.02 48.50 420.33
August 467.17 0.64 0.61 01-AUG-04:00 2054.12 13.93 79.00 408.00 1292.47 14.53 52.17 356.33
September 356.33 0.65 0.61 01-SEP-06:49 1541.84 14.69 77.00 303.00 1019.67 16.40 73.17 243.17
October 265.50 0.66 0.61 01-OCT-07:49 810.87 14.28 62.50 201.00 497.74 16.02 61.50 119.17
November 135.83 0.75 0.61 01-NOV-09:00 297.44 6.86 0.00 48.67 215.72 14.24 34.67 17.83
December 71.17 0.93 0.79 04-DEC-11:30 73.02 2.38 0.00 0.00 43.98 3.55 0.00 0.00
                         
Annual Sum or Average 4053.17 0.66     1961.79 13.17 641.67 3196.00 1092.74 14.94 588.67 2655.00
Minimum of Months 71.17 0.64 0.61   73.02 2.38 0.00 0.00 43.98 3.55 0.00 0.00
Maximum of Months 583.50 0.93 0.79   3097.78 16.94 110.83 490.33 1598.27 17.00 73.83 436.50



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.214342E+11 96835.78 12-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.123020E+11 90321.40 27-FEB-07:07 0.00 0.00 0.00 0.00 0.00
March 0.369021E+10 77099.46 01-MAR-07:08 0.00 0.00 0.00 0.00 0.00
April 0.349386E+09 29260.07 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 24090422.14 12907.07 27-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 96.27 0.15 09-JUN-20:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 17869578.71 14918.93 31-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.204421E+09 17940.91 25-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.391535E+09 37210.11 23-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.185206E+11 76920.08 29-NOV-10:00 0.00 0.00 0.00 0.00 0.00
December 0.302151E+11 85908.59 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.871494E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.302151E+11 96835.78   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.242794E+09 36003.10 02-JAN-06:17 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.242794E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.242794E+09 36003.10   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.569383E+10 13735.07 02-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.284921E+10 14712.66 14-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.127408E+10 14848.21 29-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 66194943.16 14738.23 01-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.483304E+09 14372.97 26-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.270975E+10 14708.80 03-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.448437E+10 13667.85 02-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175607E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.569383E+10 14848.21   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.500182E+10 16563.97 02-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.251898E+10 16953.44 14-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.101139E+10 17006.31 30-MAR-05:01 0.00 0.00 0.00 0.00 0.00
April 81153183.36 16984.24 01-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 10313791.55 1139.55 30-SEP-05:04 0.00 0.00 0.00 0.00 0.00
October 0.624792E+09 16818.44 26-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.321721E+10 16980.76 02-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.485772E+10 16532.84 04-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173234E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.500182E+10 17006.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.764239E+10 25710.19 02-JAN-05:22 0.00 0.00 0.00 0.00 0.00
February 0.328278E+10 26314.25 14-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.130178E+10 26423.90 10-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.128585E+09 26361.77 01-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 43838263.38 4284.74 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.101250E+10 26382.97 25-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.439787E+10 26356.61 02-NOV-05:01 0.00 0.00 0.00 0.00 0.00
December 0.736083E+10 25665.45 22-DEC-05:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.251706E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.764239E+10 26423.90   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.317856E+10 15717.59 14-JAN-05:02 0.00 0.00 0.00 0.00 0.00
February 0.996852E+09 15714.55 27-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.163162E+09 15689.36 01-MAR-06:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 95478888.11 15687.33 31-OCT-05:01 0.00 0.00 0.00 0.00 0.00
November 0.498908E+09 15692.32 27-NOV-06:01 0.00 0.00 0.00 0.00 0.00
December 0.705626E+09 15693.49 04-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.563859E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.317856E+10 15717.59   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.253853E+12 1037439.41 12-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.148215E+12 976492.64 27-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.478880E+11 823772.04 01-MAR-07:03 0.00 0.00 0.00 0.00 0.00
April 0.637270E+10 324711.81 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 0.436720E+09 145096.12 27-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 8696.91 5.64 21-JUN-08:00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.535849E+09 189031.38 31-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.304051E+10 324511.15 29-SEP-09:07 0.00 0.00 0.00 0.00 0.00
October 0.638169E+10 421072.62 23-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.217496E+12 817561.94 29-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 0.355733E+12 921572.86 15-DEC-08:00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.103995E+13     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.355733E+12 1037439.41   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.595203E+11 602478.94 18-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.244126E+11 602037.13 06-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.423851E+10 600210.08 01-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.646021E+09 598117.18 03-APR-05:01 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.348317E+10 601640.15 31-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.271939E+11 601812.47 27-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.443313E+11 602290.52 26-DEC-05:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.163826E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.595203E+11 602478.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.137937E+12 126625.03 09-JAN-05:04 0.00 0.00 0.00 0.00 0.00
February 0.972993E+11 126302.30 01-FEB-06:05 0.00 0.00 0.00 0.00 0.00
March 0.685457E+11 126291.57 06-MAR-06:05 0.00 0.00 0.00 0.00 0.00
April 0.175070E+11 136619.31 26-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 11196467.85 40756.44 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 29659029.41 16264.13 31-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.294112E+10 125803.91 25-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.436254E+11 126393.69 10-OCT-05:02 0.00 0.00 0.00 0.00 0.00
November 0.106831E+12 126642.34 14-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.136099E+12 126642.98 26-DEC-05:23 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.610826E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.137937E+12 136619.31   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.102468E+12 191048.04 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.662806E+11 190385.74 10-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.355664E+11 190281.25 27-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 0.941727E+10 190313.73 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 7578388.13 25785.63 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 50461941.10 17853.68 30-AUG-05:03 0.00 0.00 0.00 0.00 0.00
September 0.223355E+10 188175.61 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.312972E+11 190468.43 24-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.809315E+11 191133.42 15-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.102203E+12 191127.24 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.430455E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.102468E+12 191133.42   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.135277E+12 289537.73 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.713421E+11 289373.74 24-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.378639E+11 288914.35 08-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.924304E+10 289300.70 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.124139E+09 52976.46 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 31381025.12 17498.55 30-AUG-05:05 0.00 0.00 0.00 0.00 0.00
September 0.228949E+10 285339.64 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.339555E+11 289411.12 30-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.955867E+11 289667.06 15-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.143140E+12 289657.69 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.528853E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.143140E+12 289667.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.913647E+11 189898.98 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.587445E+11 189795.06 24-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.380219E+11 189489.78 08-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.729047E+10 189748.78 03-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.137710E+09 43846.59 27-MAY-05:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 11030624.19 6668.11 30-AUG-05:08 0.00 0.00 0.00 0.00 0.00
September 0.234207E+10 187138.20 30-SEP-05:01 0.00 0.00 0.00 0.00 0.00
October 0.288958E+11 189818.75 30-OCT-04:03 0.00 0.00 0.00 0.00 0.00
November 0.655659E+11 189878.62 25-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.842095E+11 189836.23 02-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.376584E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.913647E+11 189898.98   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.361145E+11 115370.88 12-JAN-07:01 0.00 0.00 0.00 0.00 0.00
February 0.218551E+11 101808.10 27-FEB-08:10 0.00 0.00 0.00 0.00 0.00
March 0.763221E+10 90898.82 01-MAR-07:02 0.00 0.00 0.00 0.00 0.00
April 0.775660E+09 37572.98 08-APR-06:10 0.00 0.00 0.00 0.00 0.00
May 73533515.55 19175.51 27-MAY-06:10 0.00 0.00 0.00 0.00 0.00
June 974037.21 1623.38 02-JUN-06:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 37398059.45 24053.39 31-AUG-06:10 0.00 0.00 0.00 0.00 0.00
September 0.197976E+09 26091.11 25-SEP-06:10 0.00 0.00 0.00 0.00 0.00
October 0.250905E+10 44682.87 23-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 0.315244E+11 90461.80 29-NOV-07:02 0.00 0.00 0.00 0.00 0.00
December 0.464863E+11 101862.24 15-DEC-07:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.147207E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.464863E+11 115370.88   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.277105E+11 78055.58 21-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.184707E+11 78130.67 07-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.121139E+11 78105.92 20-MAR-04:04 0.00 0.00 0.00 0.00 0.00
April 0.335357E+10 77877.13 10-APR-05:03 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.747553E+09 78017.91 25-SEP-04:03 0.00 0.00 0.00 0.00 0.00
October 0.925630E+10 78229.29 10-OCT-04:04 0.00 0.00 0.00 0.00 0.00
November 0.224155E+11 78049.77 21-NOV-05:04 0.00 0.00 0.00 0.00 0.00
December 0.270450E+11 78047.93 20-DEC-06:04 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.121113E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.277105E+11 78229.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.226507E+11 16629.17 20-JAN-06:04 0.00 0.00 0.00 0.00 0.00
February 0.175478E+11 16628.67 04-FEB-05:04 0.00 0.00 0.00 0.00 0.00
March 0.144854E+11 16627.57 10-MAR-06:04 0.00 0.00 0.00 0.00 0.00
April 0.533810E+10 16598.61 05-APR-05:04 0.00 0.00 0.00 0.00 0.00
May 0.195696E+09 16514.81 27-MAY-04:03 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.118666E+09 16394.12 31-AUG-04:03 0.00 0.00 0.00 0.00 0.00
September 0.221092E+10 16584.50 30-SEP-05:03 0.00 0.00 0.00 0.00 0.00
October 0.106761E+11 16626.86 19-OCT-05:03 0.00 0.00 0.00 0.00 0.00
November 0.193834E+11 16628.15 02-NOV-05:04 0.00 0.00 0.00 0.00 0.00
December 0.229788E+11 16578.63 26-DEC-04:43 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.115586E+12     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.229788E+11 16629.17   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.156096E+11 18994.00 06-JAN-05:53 0.00 0.00 0.00 0.00 0.00
February 0.111543E+11 19043.22 04-FEB-05:23 0.00 0.00 0.00 0.00 0.00
March 0.723610E+10 19050.10 03-MAR-06:06 0.00 0.00 0.00 0.00 0.00
April 0.246904E+10 19000.83 03-APR-03:14 0.00 0.00 0.00 0.00 0.00
May 78454465.03 18780.96 27-MAY-04:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 42707856.33 13930.91 31-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.108704E+10 19021.44 29-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.650724E+10 19054.68 31-OCT-05:06 0.00 0.00 0.00 0.00 0.00
November 0.132515E+11 19048.30 17-NOV-05:43 0.00 0.00 0.00 0.00 0.00
December 0.159102E+11 18993.74 23-DEC-05:53 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.733463E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.159102E+11 19054.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.217668E+11 30107.56 05-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.133217E+11 30180.34 08-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.856729E+10 30106.25 11-MAR-05:13 0.00 0.00 0.00 0.00 0.00
April 0.289968E+10 30064.45 08-APR-05:02 0.00 0.00 0.00 0.00 0.00
May 0.228513E+09 29800.95 27-MAY-04:02 0.00 0.00 0.00 0.00 0.00
June 639980.75 404.09 26-JUN-05:40 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 88902124.28 19925.80 31-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.142704E+10 30025.79 28-SEP-04:02 0.00 0.00 0.00 0.00 0.00
October 0.808860E+10 30137.24 21-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.172401E+11 30112.92 03-NOV-04:13 0.00 0.00 0.00 0.00 0.00
December 0.231362E+11 30110.29 30-DEC-05:53 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.967655E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.231362E+11 30180.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.145531E+11 20189.77 05-JAN-05:23 0.00 0.00 0.00 0.00 0.00
February 0.100393E+11 20192.85 10-FEB-05:02 0.00 0.00 0.00 0.00 0.00
March 0.737681E+10 20210.25 09-MAR-05:12 0.00 0.00 0.00 0.00 0.00
April 0.203019E+10 20125.04 01-APR-04:23 0.00 0.00 0.00 0.00 0.00
May 0.135603E+09 19966.36 27-MAY-04:02 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 55165066.80 13001.98 31-AUG-05:02 0.00 0.00 0.00 0.00 0.00
September 0.115241E+10 20024.64 28-SEP-04:01 0.00 0.00 0.00 0.00 0.00
October 0.595336E+10 20202.10 21-OCT-04:02 0.00 0.00 0.00 0.00 0.00
November 0.110790E+11 20236.06 03-NOV-04:13 0.00 0.00 0.00 0.00 0.00
December 0.133973E+11 20114.75 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.657722E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145531E+11 20236.06   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.453296E+10 49693.19 13-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 0.169746E+10 30558.23 28-FEB-22:00 0.00 0.00 0.00 0.00 0.00
March 0.156272E+09 31181.60 01-MAR-07:20 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 116.08 0.77 28-AUG-03:02 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.185259E+10 28280.05 30-NOV-21:00 0.00 0.00 0.00 0.00 0.00
December 0.235020E+10 32603.78 15-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.105895E+11     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.453296E+10 49693.19   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:02 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:03 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:05 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:05 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 4159758.06 4159758.06 192.90 25-JAN-11:20 192.90 0.00
February 0.00 0.00 15111421.04 15111421.04 3489.01 09-FEB-08:20 3489.01 0.00
March 0.00 0.00 30970039.96 30970039.96 6033.83 24-MAR-07:10 6033.83 0.00
April 0.00 0.00 84166107.27 84166107.27 9746.96 20-APR-14:00 9746.96 0.00
May 0.00 0.00 0.915031E+10 0.915031E+10 76209.13 31-MAY-16:00 76209.13 0.00
June 0.00 0.00 0.428501E+11 0.427169E+11 117467.01 30-JUN-12:20 106846.81 0.12
July 0.00 0.00 0.576274E+11 0.574392E+11 124106.52 03-JUL-15:00 54401.53 0.38
August 0.00 0.00 0.329116E+11 0.329116E+11 117653.67 11-AUG-15:20 117653.67 0.23
September 0.00 0.00 0.561326E+09 0.561326E+09 22968.65 07-SEP-16:00 22968.65 0.00
October 0.00 0.00 17713995.31 17713995.31 8787.15 13-OCT-07:10 8787.15 0.00
November 0.00 0.00 20285948.10 20285948.10 2803.79 16-NOV-08:20 2803.79 0.00
December 0.00 0.00 5297400.63 5297400.63 1588.60 26-DEC-08:30 1588.60 0.00
                 
Annual Sum or Average 0.00 0.00 0.143278E+12 0.142957E+12       0.06
Minimum of Months 0.00 0.00 4159758.06 4159758.06 192.90   192.90 0.00
Maximum of Months 0.00 0.00 0.576274E+11 0.574392E+11 124106.52   117653.67 0.38



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 16680259.29 16680259.29 754.28 07-JAN-12:10 754.28 0.00
February 0.00 0.00 36563613.89 36563613.89 2605.87 15-FEB-12:20 2605.87 0.00
March 0.00 0.00 0.171794E+09 0.171794E+09 148418.29 31-MAR-15:25 148418.29 0.00
April 0.00 0.00 0.598701E+09 0.598701E+09 73577.05 20-APR-14:00 73577.05 0.00
May 0.00 0.00 0.829991E+11 0.829991E+11 715353.03 31-MAY-16:00 715353.03 0.00
June 0.00 0.00 0.373115E+12 0.372000E+12 1115119.69 30-JUN-12:20 1014785.48 0.11
July 0.00 0.00 0.481717E+12 0.480453E+12 1064825.92 21-JUL-14:40 1064825.92 0.33
August 0.00 0.00 0.258144E+12 0.258144E+12 1044142.88 11-AUG-15:40 1044142.88 0.20
September 0.00 0.00 0.476980E+10 0.476980E+10 199182.86 07-SEP-16:00 199182.86 0.00
October 0.00 0.00 31782058.86 31782058.86 3423.87 03-OCT-10:10 3423.87 0.00
November 0.00 0.00 25233660.08 25233660.08 1533.43 03-NOV-20:50 1533.43 0.00
December 0.00 0.00 6679649.85 6679649.85 691.37 23-DEC-12:10 691.37 0.00
                 
Annual Sum or Average 0.00 0.00 0.120163E+13 0.119925E+13       0.05
Minimum of Months 0.00 0.00 6679649.85 6679649.85 691.37   691.37 0.00
Maximum of Months 0.00 0.00 0.481717E+12 0.480453E+12 1115119.69   1064825.92 0.33



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 686372.80 686372.80 884.01 09-JAN-06:04 884.01 0.00
February 0.00 0.00 4108599.94 4108599.94 151.84 06-FEB-17:10 151.84 0.00
March 0.00 0.00 14499805.83 14499805.83 436.47 11-MAR-12:50 436.47 0.00
April 0.00 0.00 48164889.81 48164889.81 3688.47 22-APR-14:00 3688.47 0.00
May 0.00 0.00 0.797518E+10 0.797518E+10 78760.34 31-MAY-16:00 78760.34 0.00
June 0.00 0.00 0.386869E+11 0.385602E+11 126537.62 30-JUN-12:30 116448.58 0.10
July 0.00 0.00 0.499574E+11 0.498395E+11 123062.32 21-JUL-14:40 123062.32 0.32
August 0.00 0.00 0.258079E+11 0.258079E+11 114221.20 11-AUG-15:40 114221.20 0.19
September 0.00 0.00 0.360093E+09 0.360093E+09 15976.34 07-SEP-16:00 15976.34 0.00
October 0.00 0.00 9732057.36 9732057.36 565.00 03-OCT-11:00 565.00 0.00
November 0.00 0.00 661238.14 661238.14 2118.32 06-NOV-06:01 2118.32 0.00
December 0.00 0.00 589027.74 589027.74 105.88 23-DEC-12:10 105.88 0.00
                 
Annual Sum or Average 0.00 0.00 0.122866E+12 0.122621E+12       0.05
Minimum of Months 0.00 0.00 589027.74 589027.74 105.88   105.88 0.00
Maximum of Months 0.00 0.00 0.499574E+11 0.498395E+11 126537.62   123062.32 0.32



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 11866734.55 11866734.55 435.45 18-JAN-08:20 435.45 0.00
February 0.00 0.00 23795020.82 23795020.82 3404.76 10-FEB-17:10 3404.76 0.00
March 0.00 0.00 30465001.10 30465001.10 2296.38 27-MAR-16:10 2296.38 0.00
April 0.00 0.00 8754644.20 8754644.20 3121.74 03-APR-16:10 3121.74 0.00
May 0.00 0.00 0.245919E+10 0.245919E+10 37984.93 31-MAY-16:00 37984.93 0.00
June 0.00 0.00 0.179986E+11 0.179838E+11 52173.09 13-JUN-13:20 52173.09 0.09
July 0.00 0.00 0.276962E+11 0.275970E+11 63402.65 03-JUL-15:00 28815.59 0.24
August 0.00 0.00 0.149942E+11 0.149707E+11 58381.21 27-AUG-19:02 58381.21 0.15
September 0.00 0.00 23690172.40 23690172.40 6993.92 07-SEP-16:00 6993.92 0.00
October 0.00 0.00 25591816.49 25591816.49 5568.38 24-OCT-16:10 5568.38 0.00
November 0.00 0.00 40371042.59 40371042.59 5520.10 07-NOV-08:00 5520.10 0.00
December 0.00 0.00 19180840.16 19180840.16 10740.30 27-DEC-13:00 10740.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.633319E+11 0.631944E+11       0.04
Minimum of Months 0.00 0.00 8754644.20 8754644.20 435.45   435.45 0.00
Maximum of Months 0.00 0.00 0.276962E+11 0.275970E+11 63402.65   58381.21 0.24



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.308256E+12 0.301249E+12 125673.17 26-JAN-22:02 122361.54 0.00
February 0.00 0.00 0.509104E+12 0.495535E+12 219926.86 09-FEB-22:03 213861.82 0.00
March 0.00 0.00 0.820245E+12 0.798976E+12 403729.19 31-MAR-23:55 393068.19 0.00
April 0.00 0.00 0.104501E+13 0.102176E+13 410632.67 30-APR-23:00 399200.96 0.00
May 0.00 0.00 0.334672E+12 0.327272E+12 216071.74 31-MAY-24:00 211325.31 0.00
June 0.00 0.00 0.567000E+12 0.556845E+12 308610.59 30-JUN-24:00 303167.04 0.00
July 0.00 0.00 0.835821E+12 0.823309E+12 399351.33 31-JUL-24:00 395739.59 0.00
August 0.00 0.00 0.108747E+13 0.106764E+13 413495.10 30-AUG-22:00 401102.02 0.00
September 0.00 0.00 0.324343E+12 0.316483E+12 216497.79 30-SEP-24:00 210601.19 0.00
October 0.00 0.00 0.577297E+12 0.563444E+12 308470.48 31-OCT-24:00 301600.96 0.00
November 0.00 0.00 0.791578E+12 0.771693E+12 315513.02 24-NOV-22:02 306521.17 0.00
December 0.00 0.00 0.106596E+13 0.103953E+13 410622.08 27-DEC-22:02 397976.25 0.00
                 
Annual Sum or Average 0.00 0.00 0.826676E+13 0.808374E+13       0.00
Minimum of Months 0.00 0.00 0.308256E+12 0.301249E+12 125673.17   122361.54 0.00
Maximum of Months 0.00 0.00 0.108747E+13 0.106764E+13 413495.10   401102.02 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.121010E+10 0.121010E+10 1242.08 28-JAN-21:19 1242.08 0.00
February 0.00 0.00 0.667895E+10 0.667895E+10 3548.53 09-FEB-16:00 3548.53 0.00
March 0.00 0.00 0.137054E+11 0.137054E+11 7276.28 31-MAR-23:55 7276.28 0.00
April 0.00 0.00 0.196558E+11 0.196558E+11 8957.06 22-APR-18:40 8957.06 0.00
May 0.00 0.00 0.555123E+10 0.555107E+10 4025.32 31-MAY-24:00 4025.32 0.00
June 0.00 0.00 0.107182E+11 0.106459E+11 5956.95 30-JUN-23:03 5914.42 0.00
July 0.00 0.00 0.162310E+11 0.160822E+11 7845.22 31-JUL-23:40 7831.17 0.00
August 0.00 0.00 0.210293E+11 0.209098E+11 8930.31 27-AUG-18:45 8930.31 0.00
September 0.00 0.00 0.485127E+10 0.483482E+10 3465.66 30-SEP-24:00 3465.66 0.00
October 0.00 0.00 0.898064E+10 0.898038E+10 4996.37 31-OCT-24:00 4996.37 0.00
November 0.00 0.00 0.123109E+11 0.123109E+11 5396.41 19-NOV-15:28 5396.41 0.00
December 0.00 0.00 0.174195E+11 0.174195E+11 7214.04 24-DEC-17:57 7214.04 0.00
                 
Annual Sum or Average 0.00 0.00 0.138342E+12 0.137985E+12       0.00
Minimum of Months 0.00 0.00 0.121010E+10 0.121010E+10 1242.08   1242.08 0.00
Maximum of Months 0.00 0.00 0.210293E+11 0.209098E+11 8957.06   8957.06 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.280579E+09 0.280579E+09 4109.29 20-JAN-22:08 4109.29 0.00
February 0.00 0.00 0.392410E+11 0.392410E+11 28435.77 16-FEB-16:10 28435.77 0.00
March 0.00 0.00 0.106575E+12 0.106575E+12 62700.42 31-MAR-23:20 62700.42 0.00
April 0.00 0.00 0.173508E+12 0.173508E+12 83838.45 22-APR-18:50 83838.45 0.00
May 0.00 0.00 0.478149E+11 0.478131E+11 37728.08 31-MAY-24:00 37728.08 0.00
June 0.00 0.00 0.100243E+12 0.995245E+11 57014.85 30-JUN-24:00 56834.96 0.00
July 0.00 0.00 0.153484E+12 0.152003E+12 75944.17 31-JUL-23:57 75743.89 0.00
August 0.00 0.00 0.198174E+12 0.196981E+12 83744.25 27-AUG-18:50 83744.25 0.00
September 0.00 0.00 0.357572E+11 0.355998E+11 26661.02 30-SEP-23:50 26661.02 0.00
October 0.00 0.00 0.623056E+11 0.623027E+11 37503.27 31-OCT-23:20 37503.27 0.00
November 0.00 0.00 0.870645E+11 0.870645E+11 44013.77 08-NOV-15:50 44013.77 0.00
December 0.00 0.00 0.134264E+12 0.134264E+12 58842.95 21-DEC-22:05 58842.95 0.00
                 
Annual Sum or Average 0.00 0.00 0.113871E+13 0.113516E+13       0.00
Minimum of Months 0.00 0.00 0.280579E+09 0.280579E+09 4109.29   4109.29 0.00
Maximum of Months 0.00 0.00 0.198174E+12 0.196981E+12 83838.45   83838.45 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.00 0.00 0.00 01-JAN-00:02 0.00 0.00
February 0.00 0.00 0.225922E+10 0.225922E+10 2523.50 09-FEB-16:00 2523.50 0.00
March 0.00 0.00 0.863812E+10 0.863812E+10 5311.20 31-MAR-23:10 5311.20 0.00
April 0.00 0.00 0.158174E+11 0.158174E+11 8330.09 20-APR-18:50 8330.09 0.00
May 0.00 0.00 0.407568E+10 0.407552E+10 3732.78 31-MAY-24:00 3732.78 0.00
June 0.00 0.00 0.984277E+10 0.977105E+10 5674.39 30-JUN-23:03 5629.98 0.00
July 0.00 0.00 0.151963E+11 0.150483E+11 7560.65 31-JUL-23:57 7540.59 0.00
August 0.00 0.00 0.194265E+11 0.193073E+11 8377.74 27-AUG-18:45 8377.74 0.00
September 0.00 0.00 0.216028E+10 0.214587E+10 2357.28 02-SEP-18:07 2357.28 0.00
October 0.00 0.00 0.400478E+10 0.400453E+10 3399.41 03-OCT-16:00 3399.41 0.00
November 0.00 0.00 0.671475E+10 0.671475E+10 3948.77 08-NOV-15:50 3948.77 0.00
December 0.00 0.00 0.115042E+11 0.115042E+11 5546.56 19-DEC-22:10 5546.56 0.00
                 
Annual Sum or Average 0.00 0.00 0.996400E+11 0.992863E+11       0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00   0.00 0.00
Maximum of Months 0.00 0.00 0.194265E+11 0.193073E+11 8377.74   8377.74 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 358965.15 2326765.49 17-JAN-04:01
February 0.00 0.00 01-FEB-00:03 239477.49 2226751.33 27-FEB-07:10
March 0.00 0.00 01-MAR-00:05 110352.68 1866112.97 03-MAR-06:01
April 0.00 0.00 01-APR-00:10 26047.11 1830111.06 03-APR-05:01
May 0.00 0.00 01-MAY-00:10 526.23 253346.90 27-MAY-05:03
June 0.00 0.00 01-JUN-00:10 0.57 1536.22 02-JUN-06:10
July 0.00 0.00 01-JUL-00:10 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:05 395.76 253375.85 31-AUG-06:10
September 0.00 0.00 01-SEP-00:10 7636.53 1596247.77 30-SEP-05:01
October 0.00 0.00 01-OCT-00:10 71813.39 1954057.91 30-OCT-04:01
November 0.00 0.00 01-NOV-00:10 283915.31 2094081.98 06-NOV-05:01
December 0.00 0.00 01-DEC-00:10 395386.56 2047130.68 20-DEC-06:01
             
Annual Sum or Average 0.00     124093.12    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   395386.56 2326765.49  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 3069.76 21612.15 23-JAN-07:05 0.00 0.00 01-JAN-00:02
February 4479.74 22884.35 15-FEB-12:20 0.00 0.00 01-FEB-00:03
March 5289.55 168373.36 31-MAR-15:25 0.00 0.00 01-MAR-00:05
April 3183.79 170168.11 20-APR-14:10 0.00 0.00 01-APR-00:10
May 74797.34 1097886.41 31-MAY-16:10 5.82 87983.07 14-MAY-08:12
June 286320.45 1439636.73 20-JUN-14:40 29.16 134710.38 04-JUN-08:43
July 328386.19 1456546.23 21-JUL-13:10 12.91 41783.08 22-JUL-23:53
August 200968.19 1486815.83 11-AUG-15:20 1.10 6142.45 05-AUG-21:53
September 5863.17 494292.64 07-SEP-16:00 0.00 0.00 01-SEP-00:10
October 3843.53 30895.38 13-OCT-07:10 0.00 0.00 01-OCT-00:10
November 5728.94 26978.50 07-NOV-08:00 0.00 0.00 01-NOV-00:10
December 2437.69 32772.75 27-DEC-13:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 77646.25     4.08    
Minimum of Months 2437.69 21612.15   0.00 0.00  
Maximum of Months 328386.19 1486815.83   29.16 134710.38  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.98 101.15 27-JAN-15:10 0.00 0.00 01-JAN-00:02
February 10.96 1521.31 16-FEB-08:20 0.00 0.00 01-FEB-00:03
March 79.66 163227.26 31-MAR-15:25 0.00 0.00 01-MAR-00:05
April 366.89 107236.78 20-APR-14:00 0.00 0.00 01-APR-00:10
May 47521.15 1075767.51 31-MAY-16:00 0.00 0.00 01-MAY-00:10
June 218145.34 1505749.06 20-JUN-14:40 0.00 0.00 01-JUN-00:10
July 277729.71 1532286.91 21-JUL-13:10 0.00 0.00 01-JUL-00:10
August 156172.65 1556712.40 11-AUG-15:20 0.00 0.00 01-AUG-00:05
September 2741.75 305997.57 07-SEP-16:00 0.00 0.00 01-SEP-00:10
October 37.75 9720.34 13-OCT-07:10 0.00 0.00 01-OCT-00:10
November 38.08 4425.38 07-NOV-08:00 0.00 0.00 01-NOV-00:10
December 12.83 9053.23 27-DEC-13:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 59088.40     0.00    
Minimum of Months 0.98 101.15   0.00 0.00  
Maximum of Months 277729.71 1556712.40   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 148672.85 166456.17 27-JAN-22:10 0.00 0.00 01-JAN-00:02
February 291200.47 315866.41 09-FEB-22:10 0.00 0.00 01-FEB-00:03
March 444128.93 596311.84 31-MAR-23:30 0.00 0.00 01-MAR-00:05
April 604993.14 759403.59 22-APR-14:00 0.00 0.00 01-APR-00:10
May 199155.48 496791.05 31-MAY-16:00 0.00 0.00 01-MAY-00:10
June 454844.58 1073606.85 30-JUN-15:00 0.00 0.00 01-JUN-00:10
July 685733.91 1397762.54 29-JUL-17:00 0.00 0.00 01-JUL-00:10
August 783119.50 1365238.22 11-AUG-18:00 0.00 0.00 01-AUG-00:05
September 181337.08 313097.78 30-SEP-24:00 0.00 0.00 01-SEP-00:10
October 307588.51 443136.80 31-OCT-23:30 0.00 0.00 01-OCT-00:10
November 434252.04 455055.39 03-NOV-21:10 0.00 0.00 01-NOV-00:10
December 572337.73 597904.32 27-DEC-22:10 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 426792.50     0.00    
Minimum of Months 148672.85 166456.17   0.00 0.00  
Maximum of Months 783119.50 1397762.54   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 18930.55 63781.79 30-JAN-12:55
February 0.00 0.00 01-FEB-00:03 19036.51 63850.53 28-FEB-12:55
March 0.00 0.00 01-MAR-00:05 20139.73 63883.03 29-MAR-11:13
April 0.00 0.00 01-APR-00:10 18958.53 63746.83 04-APR-11:55
May 0.00 0.00 01-MAY-00:10 19409.78 63741.63 09-MAY-11:20
June 0.00 0.00 01-JUN-00:10 19173.91 62189.72 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 17141.20 59648.77 03-JUL-11:50
August 0.00 0.00 01-AUG-00:05 18215.25 57882.63 01-AUG-12:00
September 0.00 0.00 01-SEP-00:10 17113.70 57533.15 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 17395.63 59181.09 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 18195.23 61484.10 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 18243.15 63741.63 29-DEC-12:20
             
Annual Sum or Average 0.00     18493.14    
Minimum of Months 0.00 0.00   17113.70 57533.15  
Maximum of Months 0.00 0.00   20139.73 63883.03  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 126.29 22908.85 28-JAN-09:30 4227.06 126125.66 07-JAN-12:50
February 273.43 23333.46 17-FEB-22:00 5991.87 126038.25 09-FEB-21:20
March 255.15 23631.29 18-MAR-10:20 7227.72 126173.76 14-MAR-20:30
April 183.26 86951.73 20-APR-14:20 3404.06 125927.52 03-APR-20:10
May 43012.79 1795513.21 31-MAY-15:40 850.66 75755.73 17-MAY-17:10
June 225470.35 2183254.24 30-JUN-12:20 414.94 61941.08 12-JUN-08:40
July 295029.96 2080432.06 21-JUL-12:50 444.74 49585.96 18-JUL-08:30
August 160447.51 2078385.15 11-AUG-14:40 893.78 105136.78 30-AUG-08:20
September 1772.45 297210.29 07-SEP-16:00 1001.17 123221.79 29-SEP-06:20
October 201.29 23735.99 28-OCT-07:40 5111.18 126021.26 18-OCT-20:40
November 281.75 23855.82 22-NOV-19:30 7598.31 126169.17 08-NOV-20:00
December 144.56 23582.59 23-DEC-14:00 3404.75 126727.43 10-DEC-05:12
             
Annual Sum or Average 61135.98     3362.42    
Minimum of Months 126.29 22908.85   414.94 49585.96  
Maximum of Months 295029.96 2183254.24   7598.31 126727.43  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.125141E+11 0.73 9052.46 02-JAN-06:01 1.39
February 0.114713E+11 0.74 9052.46 01-FEB-06:03 1.42
March 0.138154E+11 0.81 9052.46 01-MAR-06:01 1.42
April 0.131030E+11 0.79 9052.46 01-APR-04:01 1.42
May 0.139091E+11 0.81 9052.46 01-MAY-03:02 1.42
June 0.140489E+11 0.84 9052.46 01-JUN-04:03 1.41
July 0.137810E+11 0.80 9052.46 01-JUL-03:20 1.40
August 0.152086E+11 0.88 9052.46 01-AUG-03:02 1.40
September 0.139254E+11 0.84 9052.46 01-SEP-03:02 1.41
October 0.133606E+11 0.78 9052.46 02-OCT-03:02 1.41
November 0.124818E+11 0.75 9052.46 01-NOV-04:01 1.42
December 0.124327E+11 0.73 9052.46 01-DEC-06:01 1.42
           
Annual Sum or Average 0.160052E+12 0.79      
Minimum of Months 0.114713E+11 0.73 9052.46   1.39
Maximum of Months 0.152086E+11 0.88 9052.46   1.42



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.321954E+10 0.32 5760.82 02-JAN-05:01 0.86
February 0.300011E+10 0.31 14020.43 14-FEB-06:02 1.46
March 0.460730E+10 0.36 14020.43 08-MAR-06:01 1.46
April 0.779580E+10 0.48 17411.91 07-APR-12:30 1.67
May 0.910141E+10 0.52 17480.30 11-MAY-05:03 1.67
June 0.121604E+11 0.64 21524.56 09-JUN-05:02 1.90
July 0.128032E+11 0.65 21524.56 07-JUL-05:02 1.89
August 0.127796E+11 0.66 21524.56 10-AUG-05:02 1.90
September 0.561495E+10 0.39 10515.27 01-SEP-03:02 1.21
October 0.423696E+10 0.33 15700.92 12-OCT-12:10 1.56
November 0.328925E+10 0.31 14020.43 03-NOV-05:01 1.45
December 0.316368E+10 0.31 3901.89 01-DEC-06:01 0.70
           
Annual Sum or Average 0.817721E+11 0.44      
Minimum of Months 0.300011E+10 0.31 3901.89   0.70
Maximum of Months 0.128032E+11 0.66 21524.56   1.90



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.414088E+11 0.41 58161.13 02-JAN-04:01 0.90
February 0.355236E+11 0.40 58161.13 06-FEB-05:11 0.90
March 0.366570E+11 0.36 162350.79 31-MAR-15:05 1.67
April 0.455063E+11 0.37 200624.68 13-APR-10:10 1.91
May 0.742580E+11 0.47 142041.78 13-MAY-05:03 1.53
June 0.981857E+11 0.56 200624.68 22-JUN-05:02 1.89
July 0.932644E+11 0.53 197863.69 31-JUL-05:03 1.88
August 0.816334E+11 0.49 174543.49 12-AUG-05:02 1.73
September 0.417466E+11 0.35 100533.04 29-SEP-05:03 1.24
October 0.328909E+11 0.32 91814.68 04-OCT-05:03 1.17
November 0.369998E+11 0.39 58161.13 06-NOV-05:01 0.90
December 0.404652E+11 0.40 58161.13 02-DEC-06:01 0.90
           
Annual Sum or Average 0.658540E+12 0.42      
Minimum of Months 0.328909E+11 0.32 58161.13   0.90
Maximum of Months 0.981857E+11 0.56 200624.68   1.91



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.518097E+10 0.47 5687.08 04-JAN-06:12 0.86
February 0.440507E+10 0.45 5687.08 01-FEB-05:01 0.85
March 0.459510E+10 0.43 5687.08 15-MAR-05:01 0.85
April 0.420322E+10 0.38 9442.93 21-APR-16:00 1.15
May 0.588224E+10 0.40 15314.33 31-MAY-15:20 1.54
June 0.912487E+10 0.52 17189.36 29-JUN-14:30 1.64
July 0.864189E+10 0.48 18391.64 12-JUL-15:20 1.72
August 0.684405E+10 0.43 17096.39 10-AUG-15:50 1.65
September 0.329536E+10 0.31 6212.79 08-SEP-15:30 0.89
October 0.396371E+10 0.38 5687.08 02-OCT-05:02 0.85
November 0.477416E+10 0.46 5687.08 08-NOV-06:01 0.85
December 0.527169E+10 0.48 5687.08 01-DEC-05:01 0.86
           
Annual Sum or Average 0.661823E+11 0.43      
Minimum of Months 0.329536E+10 0.31 5687.08   0.85
Maximum of Months 0.912487E+10 0.52 18391.64   1.72



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.957600E+11 1.37 35752.70 01-JAN-00:02 1.37
February 0.864929E+11 1.37 35752.70 01-FEB-00:03 1.37
March 0.957600E+11 1.37 35752.70 01-MAR-00:05 1.37
April 0.926710E+11 1.37 35752.70 01-APR-00:10 1.37
May 0.957600E+11 1.37 35752.70 01-MAY-00:10 1.37
June 0.926710E+11 1.37 35752.70 01-JUN-00:10 1.37
July 0.957600E+11 1.37 35752.70 01-JUL-00:10 1.37
August 0.957600E+11 1.37 35752.70 01-AUG-00:05 1.37
September 0.926710E+11 1.37 35752.70 01-SEP-00:10 1.37
October 0.957600E+11 1.37 35752.70 01-OCT-00:10 1.37
November 0.926710E+11 1.37 35752.70 01-NOV-00:10 1.37
December 0.957600E+11 1.37 35752.70 01-DEC-00:10 1.37
           
Annual Sum or Average 0.112750E+13 1.37      
Minimum of Months 0.864929E+11 1.37 35752.70   1.37
Maximum of Months 0.957600E+11 1.37 35752.70   1.37



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.153309E+10 0.94 572.39 01-JAN-00:02 0.93
February 0.138473E+10 0.94 572.39 01-FEB-00:03 0.94
March 0.153309E+10 0.94 572.39 01-MAR-00:05 0.94
April 0.148364E+10 0.93 572.39 01-APR-00:10 0.94
May 0.153309E+10 0.93 572.39 01-MAY-00:10 0.93
June 0.148364E+10 0.93 572.39 01-JUN-00:10 0.93
July 0.153309E+10 0.93 572.39 01-JUL-00:10 0.93
August 0.153309E+10 0.93 572.39 01-AUG-00:05 0.93
September 0.148364E+10 0.93 572.39 01-SEP-00:10 0.93
October 0.153309E+10 0.93 572.39 01-OCT-00:10 0.93
November 0.148364E+10 0.94 572.39 01-NOV-00:10 0.94
December 0.153309E+10 0.94 572.39 01-DEC-00:10 0.94
           
Annual Sum or Average 0.180509E+11 0.93      
Minimum of Months 0.138473E+10 0.93 572.39   0.93
Maximum of Months 0.153309E+10 0.94 572.39   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.147273E+11 0.94 5498.54 01-JAN-00:02 0.93
February 0.133021E+11 0.94 5498.54 01-FEB-00:03 0.94
March 0.147273E+11 0.94 5498.54 01-MAR-00:05 0.94
April 0.142522E+11 0.93 5498.54 01-APR-00:10 0.94
May 0.147273E+11 0.93 5498.54 01-MAY-00:10 0.93
June 0.142522E+11 0.93 5498.54 01-JUN-00:10 0.93
July 0.147273E+11 0.93 5498.54 01-JUL-00:10 0.93
August 0.147273E+11 0.93 5498.54 01-AUG-00:05 0.93
September 0.142522E+11 0.93 5498.54 01-SEP-00:10 0.93
October 0.147273E+11 0.93 5498.54 01-OCT-00:10 0.93
November 0.142522E+11 0.94 5498.54 01-NOV-00:10 0.94
December 0.147273E+11 0.94 5498.54 01-DEC-00:10 0.94
           
Annual Sum or Average 0.173402E+12 0.93      
Minimum of Months 0.133021E+11 0.93 5498.54   0.93
Maximum of Months 0.147273E+11 0.94 5498.54   0.94



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.148717E+10 0.94 555.25 01-JAN-00:02 0.93
February 0.134325E+10 0.94 555.25 01-FEB-00:03 0.94
March 0.148717E+10 0.94 555.25 01-MAR-00:05 0.94
April 0.143920E+10 0.93 555.25 01-APR-00:10 0.94
May 0.148717E+10 0.93 555.25 01-MAY-00:10 0.93
June 0.143920E+10 0.93 555.25 01-JUN-00:10 0.93
July 0.148717E+10 0.93 555.25 01-JUL-00:10 0.93
August 0.148717E+10 0.93 555.25 01-AUG-00:05 0.93
September 0.143920E+10 0.93 555.25 01-SEP-00:10 0.93
October 0.148717E+10 0.93 555.25 01-OCT-00:10 0.93
November 0.143920E+10 0.94 555.25 01-NOV-00:10 0.94
December 0.148717E+10 0.94 555.25 01-DEC-00:10 0.94
           
Annual Sum or Average 0.175102E+11 0.93      
Minimum of Months 0.134325E+10 0.93 555.25   0.93
Maximum of Months 0.148717E+10 0.94 555.25   0.94



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.176505E+09 0.158855E+09 1026.35 12-JAN-07:10 923.72 923.72 45.91 13.18
February 90238980.36 81215082.32 1265.33 27-FEB-07:10 1138.80 1138.80 45.38 14.47
March 32681557.42 29413401.68 904.58 01-MAR-06:02 814.12 814.12 48.22 12.44
April 4234971.23 3811474.11 887.51 03-APR-05:01 798.76 798.76 46.74 12.35
May 43649.85 39284.86 11.60 27-MAY-05:03 10.44 10.44 27.16 1.12
June 38.97 35.07 0.04 02-JUN-06:10 0.04 0.04 23.01 0.01
July 0.00 0.00 0.00 01-JUL-00:10 0.00 0.00 23.00 0.00
August 36202.65 32582.39 11.78 31-AUG-06:10 10.60 10.60 27.98 1.14
September 820707.03 738636.33 306.45 30-SEP-05:01 275.80 275.80 31.16 7.54
October 13597056.35 12237350.72 904.29 31-OCT-05:01 813.86 813.86 47.48 12.45
November 0.113722E+09 0.102349E+09 912.66 27-NOV-06:01 821.40 821.40 46.81 12.50
December 0.179674E+09 0.161706E+09 915.44 04-DEC-06:01 823.90 823.90 47.84 12.51
                 
Annual Sum or Average 0.611554E+09 0.550398E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 23.00 0.00
Maximum of Months 0.179674E+09 0.161706E+09 1265.33   1138.80 1138.80 48.22 14.47



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 3563.52 3207.17 0.11 09-JAN-06:04 0.10 0.10 6.76 0.03
February 9204.51 8284.06 0.52 09-FEB-08:20 0.47 0.47 7.15 0.12
March 42919.54 38627.59 50.66 31-MAR-15:25 45.59 45.59 8.19 5.16
April 175110.20 157599.18 27.73 20-APR-14:00 24.96 24.96 8.45 3.50
May 44715791.50 40244212.35 748.53 31-MAY-15:50 673.67 673.67 7.91 21.93
June 0.407962E+09 0.367166E+09 4093.40 21-JUN-15:00 3684.06 3684.06 6.98 46.83
July 0.785037E+09 0.706533E+09 4860.24 06-JUL-14:50 4374.21 4374.21 7.63 50.34
August 0.457220E+09 0.411498E+09 5318.67 11-AUG-15:40 4786.80 4786.80 6.96 52.27
September 1318853.87 1186968.48 93.37 07-SEP-16:00 84.03 84.03 8.81 7.43
October 11736.29 10562.66 1.20 13-OCT-07:10 1.08 1.08 8.48 0.27
November 11137.81 10024.03 0.52 07-NOV-08:00 0.46 0.46 8.44 0.12
December 3787.01 3408.31 1.04 27-DEC-13:00 0.93 0.93 8.43 0.23
                 
Annual Sum or Average 0.169651E+10 0.152686E+10            
Minimum of Months 3563.52 3207.17 0.11   0.10 0.10 6.76 0.03
Maximum of Months 0.785037E+09 0.706533E+09 5318.67   4786.80 4786.80 8.81 52.27



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.460417E+10 0.414375E+10 12066.91 05-JAN-07:03 10860.22 10860.22 8.39 84.57
February 0.604661E+10 0.544195E+10 12066.91 01-FEB-08:40 10860.22 10860.22 8.43 84.57
March 0.775307E+10 0.697777E+10 12066.91 02-MAR-12:10 10860.22 10860.22 8.43 84.57
April 0.383800E+10 0.345420E+10 12066.91 01-APR-03:01 10860.22 10860.22 8.43 84.57
May 0.718229E+10 0.646406E+10 12066.91 01-MAY-14:50 10860.22 10860.22 8.43 84.57
June 0.157325E+11 0.141592E+11 12066.91 01-JUN-10:10 10860.22 10860.22 8.51 84.57
July 0.177128E+11 0.159415E+11 12066.91 01-JUL-04:03 10860.22 10860.22 8.65 84.57
August 0.131234E+11 0.118110E+11 12066.91 01-AUG-00:20 10860.22 10860.22 8.29 84.57
September 0.216951E+10 0.195256E+10 12066.91 01-SEP-13:40 10860.22 10860.22 8.44 84.57
October 0.566290E+10 0.509661E+10 12066.91 02-OCT-12:50 10860.22 10860.22 8.43 84.57
November 0.820914E+10 0.738822E+10 12066.91 01-NOV-06:05 10860.22 10860.22 8.43 84.57
December 0.361874E+10 0.325687E+10 12066.91 01-DEC-15:10 10860.22 10860.22 8.43 84.57
                 
Annual Sum or Average 0.956530E+11 0.860877E+11            
Minimum of Months 0.216951E+10 0.195256E+10 12066.91   10860.22 10860.22 8.29 84.57
Maximum of Months 0.177128E+11 0.159415E+11 12066.91   10860.22 10860.22 8.65 84.57



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.936426E+10 0.842784E+10 3496.22 01-JAN-00:02 3146.59 3146.59 21.31 14.60
February 0.845804E+10 0.761224E+10 3496.22 01-FEB-00:03 3146.59 3146.59 22.93 14.60
March 0.936426E+10 0.842784E+10 3496.22 01-MAR-00:05 3146.59 3146.59 26.35 14.60
April 0.906219E+10 0.815597E+10 3496.22 01-APR-00:10 3146.59 3146.59 29.99 14.60
May 0.936426E+10 0.842784E+10 3496.22 01-MAY-00:10 3146.59 3146.59 22.40 14.60
June 0.906219E+10 0.815597E+10 3496.22 01-JUN-00:10 3146.59 3146.59 24.81 14.60
July 0.936426E+10 0.842784E+10 3496.22 01-JUL-00:10 3146.59 3146.59 28.71 14.60
August 0.936426E+10 0.842784E+10 3496.22 01-AUG-00:05 3146.59 3146.59 34.50 14.60
September 0.906219E+10 0.815597E+10 3496.22 01-SEP-00:10 3146.59 3146.59 22.42 14.60
October 0.936426E+10 0.842784E+10 3496.22 01-OCT-00:10 3146.59 3146.59 24.47 14.60
November 0.906219E+10 0.815597E+10 3496.22 01-NOV-00:10 3146.59 3146.59 27.00 14.60
December 0.936426E+10 0.842784E+10 3496.22 01-DEC-00:10 3146.59 3146.59 29.38 14.60
                 
Annual Sum or Average 0.110257E+12 0.992310E+11            
Minimum of Months 0.845804E+10 0.761224E+10 3496.22   3146.59 3146.59 21.31 14.60
Maximum of Months 0.936426E+10 0.842784E+10 3496.22   3146.59 3146.59 34.50 14.60



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:02 1.79 1.79 55.23 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:03 1.79 1.79 55.81 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:01 1.79 1.79 55.94 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:01 1.79 1.79 55.68 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:02 1.79 1.79 55.99 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:02 1.79 1.79 55.09 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:03 1.79 1.79 55.40 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:03 1.79 1.79 55.03 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 55.17 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 55.27 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:01 1.79 1.79 56.14 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:01 1.79 1.79 55.67 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 55.03 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 56.14 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.582713E+10 0.524442E+10 15274.79 28-JAN-09:30 13747.31 13747.31 21.21 50.88
February 0.765274E+10 0.688746E+10 15274.81 17-FEB-22:00 13747.33 13747.33 21.21 50.88
March 0.981244E+10 0.883119E+10 15274.83 18-MAR-10:20 13747.34 13747.34 21.21 50.88
April 0.485749E+10 0.437174E+10 15278.10 20-APR-14:20 13750.29 13750.29 21.51 50.88
May 0.922202E+10 0.829982E+10 30641.39 31-MAY-15:40 27577.25 27577.25 25.32 101.76
June 0.221756E+11 0.199581E+11 30664.81 30-JUN-12:20 27598.33 27598.33 26.23 101.76
July 0.262319E+11 0.236087E+11 30658.59 21-JUL-12:50 27592.74 27592.74 25.99 101.76
August 0.184254E+11 0.165828E+11 30658.47 11-AUG-14:40 27592.62 27592.62 25.99 101.76
September 0.274615E+10 0.247153E+10 15288.96 07-SEP-16:00 13760.06 13760.06 22.50 50.88
October 0.716709E+10 0.645038E+10 15274.83 28-OCT-07:40 13747.35 13747.35 21.21 50.88
November 0.103897E+11 0.935071E+10 15274.84 22-NOV-19:30 13747.35 13747.35 21.21 50.88
December 0.457995E+10 0.412196E+10 15274.82 23-DEC-14:00 13747.34 13747.34 21.21 50.88
                 
Annual Sum or Average 0.129088E+12 0.116179E+12            
Minimum of Months 0.274615E+10 0.247153E+10 15274.79   13747.31 13747.31 21.21 50.88
Maximum of Months 0.262319E+11 0.236087E+11 30664.81   27598.33 27598.33 26.23 101.76



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 41.17 82.20 358965.15 2326765.49 17-JAN-04:01
February 0.00 0.00 01-FEB-00:03 36.00 82.20 239477.49 2226751.33 27-FEB-07:10
March 0.00 0.00 01-MAR-00:05 41.05 41.05 110352.68 1866112.97 03-MAR-06:01
April 0.00 0.00 01-APR-00:10 37.59 82.20 26047.11 1830111.06 03-APR-05:01
May 0.00 0.00 01-MAY-00:10 26.74 26.74 526.23 253346.90 27-MAY-05:03
June 0.00 0.00 01-JUN-00:10 23.01 23.01 0.57 1536.22 02-JUN-06:10
July 0.00 0.00 01-JUL-00:10 23.00 23.00 0.00 0.00 01-JUL-00:10
August 0.00 0.00 01-AUG-00:05 23.00 23.00 395.76 253375.85 31-AUG-06:10
September 0.00 0.00 01-SEP-00:10 27.88 27.88 7636.53 1596247.77 30-SEP-05:01
October 0.00 0.00 01-OCT-00:10 24.01 24.01 71813.39 1954057.91 30-OCT-04:01
November 0.00 0.00 01-NOV-00:10 33.58 33.58 283915.31 2094081.98 06-NOV-05:01
December 0.00 0.00 01-DEC-00:10 41.13 82.20 395386.56 2047130.68 20-DEC-06:01
                 
Annual Sum or Average 0.00         124093.12    
Minimum of Months 0.00 0.00   23.00 23.00 0.00 0.00  
Maximum of Months 0.00 0.00   41.17 82.20 395386.56 2326765.49  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 3069.76 21612.15 23-JAN-07:05 8.43 8.40 0.00 0.00 01-JAN-00:02
February 4479.74 22884.35 15-FEB-12:20 8.43 8.40 0.00 0.00 01-FEB-00:03
March 5289.55 168373.36 31-MAR-15:25 8.84 8.61 0.00 0.00 01-MAR-00:05
April 3183.79 170168.11 20-APR-14:10 8.85 8.61 0.00 0.00 01-APR-00:10
May 74797.34 1097886.41 31-MAY-16:10 10.49 8.81 5.82 87983.07 14-MAY-08:12
June 286320.45 1439636.73 20-JUN-14:40 11.07 7.01 29.16 134710.38 04-JUN-08:43
July 328386.19 1456546.23 21-JUL-13:10 11.11 7.00 12.91 41783.08 22-JUL-23:53
August 200968.19 1486815.83 11-AUG-15:20 11.18 6.99 1.10 6142.45 05-AUG-21:53
September 5863.17 494292.64 07-SEP-16:00 9.52 8.82 0.00 0.00 01-SEP-00:10
October 3843.53 30895.38 13-OCT-07:10 8.46 8.41 0.00 0.00 01-OCT-00:10
November 5728.94 26978.50 07-NOV-08:00 8.45 8.41 0.00 0.00 01-NOV-00:10
December 2437.69 32772.75 27-DEC-13:00 8.46 8.42 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 77646.25         4.08    
Minimum of Months 2437.69 21612.15   8.43 6.99 0.00 0.00  
Maximum of Months 328386.19 1486815.83   11.18 8.82 29.16 134710.38  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.98 101.15 27-JAN-15:10 8.06 8.40 0.00 0.00 01-JAN-00:02
February 10.96 1521.31 16-FEB-08:20 10.49 8.40 0.00 0.00 01-FEB-00:03
March 79.66 163227.26 31-MAR-15:25 14.26 8.57 0.00 0.00 01-MAR-00:05
April 366.89 107236.78 20-APR-14:00 14.02 8.60 0.00 0.00 01-APR-00:10
May 47521.15 1075767.51 31-MAY-16:00 18.49 8.58 0.00 0.00 01-MAY-00:10
June 218145.34 1505749.06 20-JUN-14:40 15.06 7.01 0.00 0.00 01-JUN-00:10
July 277729.71 1532286.91 21-JUL-13:10 14.06 7.01 0.00 0.00 01-JUL-00:10
August 156172.65 1556712.40 11-AUG-15:20 14.29 6.99 0.00 0.00 01-AUG-00:05
September 2741.75 305997.57 07-SEP-16:00 16.54 8.82 0.00 0.00 01-SEP-00:10
October 37.75 9720.34 13-OCT-07:10 15.39 8.41 0.00 0.00 01-OCT-00:10
November 38.08 4425.38 07-NOV-08:00 15.62 8.41 0.00 0.00 01-NOV-00:10
December 12.83 9053.23 27-DEC-13:00 15.99 8.41 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 59088.40         0.00    
Minimum of Months 0.98 101.15   8.06 6.99 0.00 0.00  
Maximum of Months 277729.71 1556712.40   18.49 8.82 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 148672.85 166456.17 27-JAN-22:10 21.61 18.33 0.00 0.00 01-JAN-00:02
February 291200.47 315866.41 09-FEB-22:10 24.54 18.33 0.00 0.00 01-FEB-00:03
March 444128.93 596311.84 31-MAR-23:30 29.99 18.33 0.00 0.00 01-MAR-00:05
April 604993.14 759403.59 22-APR-14:00 33.14 21.29 0.00 0.00 01-APR-00:10
May 199155.48 496791.05 31-MAY-16:00 28.06 24.09 0.00 0.00 01-MAY-00:10
June 454844.58 1073606.85 30-JUN-15:00 39.15 31.84 0.00 0.00 01-JUN-00:10
July 685733.91 1397762.54 29-JUL-17:00 45.27 35.02 0.00 0.00 01-JUL-00:10
August 783119.50 1365238.22 11-AUG-18:00 44.66 31.86 0.00 0.00 01-AUG-00:05
September 181337.08 313097.78 30-SEP-24:00 24.49 18.33 0.00 0.00 01-SEP-00:10
October 307588.51 443136.80 31-OCT-23:30 27.02 18.33 0.00 0.00 01-OCT-00:10
November 434252.04 455055.39 03-NOV-21:10 27.25 18.33 0.00 0.00 01-NOV-00:10
December 572337.73 597904.32 27-DEC-22:10 30.02 18.33 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 426792.50         0.00    
Minimum of Months 148672.85 166456.17   21.61 18.33 0.00 0.00  
Maximum of Months 783119.50 1397762.54   45.27 35.02 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:02 56.31 56.31 18930.55 63781.79 30-JAN-12:55
February 0.00 0.00 01-FEB-00:03 56.53 56.53 19036.51 63850.53 28-FEB-12:55
March 0.00 0.00 01-MAR-00:05 56.42 56.42 20139.73 63883.03 29-MAR-11:13
April 0.00 0.00 01-APR-00:10 56.01 56.01 18958.53 63746.83 04-APR-11:55
May 0.00 0.00 01-MAY-00:10 56.99 56.99 19409.78 63741.63 09-MAY-11:20
June 0.00 0.00 01-JUN-00:10 55.84 55.84 19173.91 62189.72 01-JUN-11:40
July 0.00 0.00 01-JUL-00:10 56.11 56.11 17141.20 59648.77 03-JUL-11:50
August 0.00 0.00 01-AUG-00:05 55.70 55.70 18215.25 57882.63 01-AUG-12:00
September 0.00 0.00 01-SEP-00:10 56.03 56.03 17113.70 57533.15 29-SEP-11:30
October 0.00 0.00 01-OCT-00:10 55.74 55.74 17395.63 59181.09 31-OCT-11:50
November 0.00 0.00 01-NOV-00:10 56.57 56.57 18195.23 61484.10 30-NOV-12:20
December 0.00 0.00 01-DEC-00:10 56.22 56.22 18243.15 63741.63 29-DEC-12:20
                 
Annual Sum or Average 0.00         18493.14    
Minimum of Months 0.00 0.00   55.70 55.70 17113.70 57533.15  
Maximum of Months 0.00 0.00   56.99 56.99 20139.73 63883.03  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 126.29 22908.85 28-JAN-09:30 21.21 20.27 4227.06 126125.66 07-JAN-12:50
February 273.43 23333.46 17-FEB-22:00 21.21 20.27 5991.87 126038.25 09-FEB-21:20
March 255.15 23631.29 18-MAR-10:20 21.21 20.27 7227.72 126173.76 14-MAR-20:30
April 183.26 86951.73 20-APR-14:20 21.51 20.81 3404.06 125927.52 03-APR-20:10
May 43012.79 1795513.21 31-MAY-15:40 25.32 21.10 850.66 75755.73 17-MAY-17:10
June 225470.35 2183254.24 30-JUN-12:20 26.23 22.38 414.94 61941.08 12-JUN-08:40
July 295029.96 2080432.06 21-JUL-12:50 25.99 21.10 444.74 49585.96 18-JUL-08:30
August 160447.51 2078385.15 11-AUG-14:40 25.99 21.10 893.78 105136.78 30-AUG-08:20
September 1772.45 297210.29 07-SEP-16:00 22.50 21.10 1001.17 123221.79 29-SEP-06:20
October 201.29 23735.99 28-OCT-07:40 21.21 20.28 5111.18 126021.26 18-OCT-20:40
November 281.75 23855.82 22-NOV-19:30 21.21 20.28 7598.31 126169.17 08-NOV-20:00
December 144.56 23582.59 23-DEC-14:00 21.21 20.27 3404.75 126727.43 10-DEC-05:12
                 
Annual Sum or Average 61135.98         3362.42    
Minimum of Months 126.29 22908.85   21.21 20.27 414.94 49585.96  
Maximum of Months 295029.96 2183254.24   26.23 22.38 7598.31 126727.43  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.431936E+11 0.00 4159758.06 0.321954E+10 0.00 0.00
February 0.219498E+11 0.00 15111421.04 0.300011E+10 0.00 0.00
March 0.744062E+10 0.00 30970039.96 0.460730E+10 0.00 0.00
April 0.625319E+09 0.00 84166107.27 0.779580E+10 0.00 0.00
May 24090422.14 0.00 0.915031E+10 0.910141E+10 0.00 0.00
June 96.27 0.00 0.428501E+11 0.121604E+11 0.00 0.00
July 0.00 0.00 0.576274E+11 0.128032E+11 0.00 0.00
August 17869578.71 0.00 0.329116E+11 0.127796E+11 0.00 0.00
September 0.258573E+09 0.00 0.561326E+09 0.561495E+10 0.00 0.00
October 0.260761E+10 0.00 17713995.31 0.423696E+10 0.00 0.00
November 0.293443E+11 0.00 20285948.10 0.328925E+10 0.00 0.00
December 0.476236E+11 0.00 5297400.63 0.316368E+10 0.00 0.00
             
Annual Sum or Average 0.153085E+12 0.00 0.143278E+12 0.817721E+11 0.00 0.00
Minimum of Months 0.00 0.00 4159758.06 0.300011E+10 0.00 0.00
Maximum of Months 0.476236E+11 0.00 0.576274E+11 0.128032E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.780420E+12 0.00 16680259.29 0.414088E+11 0.00 0.00
February 0.466294E+12 0.00 36563613.89 0.355236E+11 0.00 0.00
March 0.232124E+12 0.00 0.171794E+09 0.366570E+11 0.00 0.00
April 0.504765E+11 0.00 0.598701E+09 0.455063E+11 0.00 0.00
May 0.717344E+09 0.00 0.829991E+11 0.742580E+11 0.00 0.00
June 8696.91 0.00 0.373115E+12 0.981857E+11 0.00 0.00
July 0.00 0.00 0.481717E+12 0.932644E+11 0.00 0.00
August 0.658381E+09 0.00 0.258144E+12 0.816334E+11 0.00 0.00
September 0.128467E+11 0.00 0.476980E+10 0.417466E+11 0.00 0.00
October 0.147639E+12 0.00 31782058.86 0.328909E+11 0.00 0.00
November 0.593605E+12 0.00 25233660.08 0.369998E+11 0.00 0.00
December 0.865716E+12 0.00 6679649.85 0.404652E+11 0.00 0.00
             
Annual Sum or Average 0.315050E+13 0.00 0.120163E+13 0.658540E+12 0.00 0.00
Minimum of Months 0.00 0.00 6679649.85 0.328909E+11 0.00 0.00
Maximum of Months 0.865716E+12 0.00 0.481717E+12 0.981857E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.138405E+12 0.00 686372.80 0.518097E+10 0.00 0.00
February 0.923889E+11 0.00 4108599.94 0.440507E+10 0.00 0.00
March 0.574117E+11 0.00 14499805.83 0.459510E+10 0.00 0.00
April 0.168662E+11 0.00 48164889.81 0.420322E+10 0.00 0.00
May 0.711799E+09 0.00 0.797518E+10 0.588224E+10 0.00 0.00
June 1614017.95 0.00 0.386869E+11 0.912487E+10 0.00 0.00
July 0.00 0.00 0.499574E+11 0.864189E+10 0.00 0.00
August 0.342840E+09 0.00 0.258079E+11 0.684405E+10 0.00 0.00
September 0.682294E+10 0.00 0.360093E+09 0.329536E+10 0.00 0.00
October 0.429907E+11 0.00 9732057.36 0.396371E+10 0.00 0.00
November 0.114894E+12 0.00 661238.14 0.477416E+10 0.00 0.00
December 0.148954E+12 0.00 589027.74 0.527169E+10 0.00 0.00
             
Annual Sum or Average 0.619790E+12 0.00 0.122866E+12 0.661823E+11 0.00 0.00
Minimum of Months 0.00 0.00 589027.74 0.329536E+10 0.00 0.00
Maximum of Months 0.148954E+12 0.00 0.499574E+11 0.912487E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.453296E+10 0.00 11866734.55 0.125141E+11 0.00 0.00
February 0.169746E+10 0.00 23795020.82 0.114713E+11 0.00 0.00
March 0.156272E+09 0.00 30465001.10 0.138154E+11 0.00 0.00
April 0.00 0.00 8754644.20 0.131030E+11 0.00 0.00
May 0.00 0.00 0.245919E+10 0.139091E+11 0.00 0.00
June 0.00 0.00 0.179986E+11 0.140489E+11 0.00 0.00
July 0.00 0.00 0.276962E+11 0.137810E+11 0.00 0.00
August 116.08 0.00 0.149942E+11 0.152086E+11 0.00 0.00
September 0.00 0.00 23690172.40 0.139254E+11 0.00 0.00
October 0.00 0.00 25591816.49 0.133606E+11 0.00 0.00
November 0.185259E+10 0.00 40371042.59 0.124818E+11 0.00 0.00
December 0.235020E+10 0.00 19180840.16 0.124327E+11 0.00 0.00
             
Annual Sum or Average 0.105895E+11 0.00 0.633319E+11 0.160052E+12 0.00 0.00
Minimum of Months 0.00 0.00 8754644.20 0.114713E+11 0.00 0.00
Maximum of Months 0.453296E+10 0.00 0.276962E+11 0.152086E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.386659E+12 0.187791E+12 0.00 5.07
February 0.00 0.00 0.631419E+12 0.228433E+12 0.00 7.30
March 0.00 0.00 0.100905E+13 0.313172E+12 0.00 10.64
April 0.00 0.00 0.127700E+13 0.353791E+12 0.00 10.84
May 0.00 0.00 0.419678E+12 0.190918E+12 0.00 3.78
June 0.00 0.00 0.713204E+12 0.248250E+12 0.00 3.49
July 0.00 0.00 0.105336E+13 0.322895E+12 0.00 3.57
August 0.00 0.00 0.135316E+13 0.380339E+12 0.00 7.03
September 0.00 0.00 0.406132E+12 0.183873E+12 0.00 3.50
October 0.00 0.00 0.715680E+12 0.252703E+12 0.00 6.90
November 0.00 0.00 0.973968E+12 0.302305E+12 0.00 10.13
December 0.00 0.00 0.130302E+13 0.367448E+12 0.00 12.88
             
Annual Sum or Average 0.00 0.00 0.102423E+14 0.333192E+13 0.00 85.13
Minimum of Months 0.00 0.00 0.386659E+12 0.183873E+12 0.00 3.49
Maximum of Months 0.00 0.00 0.135316E+13 0.380339E+12 0.00 12.88



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.158969E+10 0.191268E+10 0.00 0.00
February 0.00 0.00 0.847269E+10 0.317847E+10 0.00 0.00
March 0.00 0.00 0.171557E+11 0.498343E+10 0.00 0.00
April 0.00 0.00 0.242956E+11 0.612346E+10 0.00 0.00
May 0.00 0.00 0.700461E+10 0.298647E+10 0.00 0.00
June 0.00 0.00 0.134699E+11 0.423534E+10 0.00 0.00
July 0.00 0.00 0.204095E+11 0.571155E+10 0.00 0.00
August 0.00 0.00 0.261519E+11 0.665571E+10 0.00 0.00
September 0.00 0.00 0.610155E+10 0.273391E+10 0.00 0.00
October 0.00 0.00 0.112712E+11 0.382368E+10 0.00 0.00
November 0.00 0.00 0.154763E+11 0.464906E+10 0.00 0.00
December 0.00 0.00 0.217598E+11 0.587334E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.173158E+12 0.528671E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.158969E+10 0.191268E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.261519E+11 0.665571E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.405263E+09 0.148520E+11 0.00 0.00
February 0.00 0.00 0.501675E+11 0.242286E+11 0.00 0.00
March 0.00 0.00 0.134010E+12 0.421619E+11 0.00 0.00
April 0.00 0.00 0.214900E+12 0.556439E+11 0.00 0.00
May 0.00 0.00 0.604464E+11 0.273587E+11 0.00 0.00
June 0.00 0.00 0.126072E+12 0.400817E+11 0.00 0.00
July 0.00 0.00 0.193090E+12 0.543328E+11 0.00 0.00
August 0.00 0.00 0.246608E+12 0.631606E+11 0.00 0.00
September 0.00 0.00 0.451544E+11 0.236494E+11 0.00 0.00
October 0.00 0.00 0.786077E+11 0.310294E+11 0.00 0.00
November 0.00 0.00 0.110169E+12 0.373569E+11 0.00 0.00
December 0.00 0.00 0.168657E+12 0.491204E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.142829E+13 0.462976E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.405263E+09 0.148520E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.246608E+12 0.631606E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.00 0.148717E+10 0.00 0.00
February 0.00 0.00 0.290434E+10 0.198837E+10 0.00 0.00
March 0.00 0.00 0.109043E+11 0.375331E+10 0.00 0.00
April 0.00 0.00 0.196336E+11 0.525537E+10 0.00 0.00
May 0.00 0.00 0.516566E+10 0.257715E+10 0.00 0.00
June 0.00 0.00 0.123896E+11 0.398599E+10 0.00 0.00
July 0.00 0.00 0.191320E+11 0.542286E+10 0.00 0.00
August 0.00 0.00 0.241989E+11 0.625954E+10 0.00 0.00
September 0.00 0.00 0.274542E+10 0.202434E+10 0.00 0.00
October 0.00 0.00 0.508353E+10 0.256592E+10 0.00 0.00
November 0.00 0.00 0.853720E+10 0.326165E+10 0.00 0.00
December 0.00 0.00 0.145033E+11 0.448627E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.125198E+12 0.430679E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.148717E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.241989E+11 0.625954E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.321954E+10 4159758.06 0.431936E+11 0.551963E+11 0.00 0.00 0.00 0.00
February 0.300011E+10 15111421.04 0.219498E+11 0.439970E+11 0.00 0.00 0.00 0.00
March 0.460730E+10 30970039.96 0.744062E+10 0.446649E+11 0.00 0.00 0.00 0.00
April 0.779580E+10 84166107.27 0.625319E+09 0.898859E+10 0.00 0.00 0.00 0.00
May 0.910141E+10 0.915031E+10 24090422.14 0.450370E+09 0.00 0.00 0.00 0.00
June 0.121604E+11 0.428501E+11 96.27 0.195541E+09 1203056.35 0.00 0.00 0.00
July 0.128032E+11 0.576274E+11 0.00 0.387806E+09 0.129762E+09 0.00 0.00 0.00
August 0.127796E+11 0.329116E+11 17869578.71 0.116525E+09 350124.24 0.00 0.00 0.00
September 0.561495E+10 0.561326E+09 0.258573E+09 0.339801E+10 0.00 0.00 0.00 0.00
October 0.423696E+10 17713995.31 0.260761E+10 0.274421E+11 0.00 0.00 0.00 0.00
November 0.328925E+10 20285948.10 0.293443E+11 0.524915E+11 0.00 0.00 0.00 0.00
December 0.316368E+10 5297400.63 0.476236E+11 0.491165E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.817721E+11 0.143278E+12 0.153085E+12 0.286445E+12 0.131316E+09 0.00 0.00 0.00
Minimum of Months 0.300011E+10 4159758.06 0.00 0.116525E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.128032E+11 0.576274E+11 0.476236E+11 0.551963E+11 0.129762E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.414088E+11 16680259.29 0.780420E+12 0.553996E+12 0.00 0.00 0.00 0.00
February 0.355236E+11 36563613.89 0.466294E+12 0.464832E+12 0.00 0.00 0.00 0.00
March 0.366570E+11 0.171802E+09 0.232124E+12 0.522888E+12 0.00 0.00 0.00 0.00
April 0.455063E+11 0.598701E+09 0.504765E+11 0.142139E+12 0.00 0.00 0.00 0.00
May 0.742580E+11 0.829991E+11 0.717344E+09 0.633030E+10 0.00 0.00 0.00 0.00
June 0.981857E+11 0.373115E+12 8696.91 0.224702E+10 14553389.58 0.00 0.00 0.00
July 0.932644E+11 0.481717E+12 0.00 0.390910E+10 0.141720E+10 0.00 0.00 0.00
August 0.816334E+11 0.258144E+12 0.658381E+09 0.242008E+10 2207627.24 0.00 0.00 0.00
September 0.417466E+11 0.476980E+10 0.128467E+11 0.567504E+11 0.00 0.00 0.00 0.00
October 0.328909E+11 31782058.86 0.147639E+12 0.342630E+12 0.00 0.00 0.00 0.00
November 0.369998E+11 25233660.08 0.593605E+12 0.547224E+12 0.00 0.00 0.00 0.00
December 0.404652E+11 6679649.85 0.865716E+12 0.486128E+12 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.658540E+12 0.120163E+13 0.315050E+13 0.313149E+13 0.143396E+10 0.00 0.00 0.00
Minimum of Months 0.328909E+11 6679649.85 0.00 0.224702E+10 0.00 0.00 0.00 0.00
Maximum of Months 0.981857E+11 0.481717E+12 0.865716E+12 0.553996E+12 0.141720E+10 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.518097E+10 686372.80 0.138405E+12 0.542951E+11 0.00 0.00 0.00 0.00
February 0.440507E+10 4108599.94 0.923889E+11 0.472720E+11 0.00 0.00 0.00 0.00
March 0.459510E+10 14499805.83 0.574117E+11 0.548847E+11 0.00 0.00 0.00 0.00
April 0.420322E+10 48164889.81 0.168662E+11 0.172988E+11 0.00 0.00 0.00 0.00
May 0.588224E+10 0.797518E+10 0.711799E+09 0.107437E+10 0.00 0.00 0.00 0.00
June 0.912487E+10 0.386869E+11 1614017.95 0.127378E+09 6672001.42 0.00 0.00 0.00
July 0.864189E+10 0.499574E+11 0.00 0.251741E+09 0.109461E+09 0.00 0.00 0.00
August 0.684405E+10 0.258079E+11 0.342840E+09 0.569399E+09 0.00 0.00 0.00 0.00
September 0.329536E+10 0.360093E+09 0.682294E+10 0.918315E+10 0.00 0.00 0.00 0.00
October 0.396371E+10 9732057.36 0.429907E+11 0.377999E+11 0.00 0.00 0.00 0.00
November 0.477416E+10 661238.14 0.114894E+12 0.533412E+11 0.00 0.00 0.00 0.00
December 0.527169E+10 589027.74 0.148954E+12 0.470847E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.661823E+11 0.122866E+12 0.619790E+12 0.323182E+12 0.116133E+09 0.00 0.00 0.00
Minimum of Months 0.329536E+10 589027.74 0.00 0.127378E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.912487E+10 0.499574E+11 0.148954E+12 0.548847E+11 0.109461E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.125141E+11 11866734.55 0.453296E+10 0.363881E+11 0.00 0.00 0.00 0.00
February 0.114713E+11 23795020.82 0.169746E+10 0.236025E+11 0.00 0.00 0.00 0.00
March 0.138154E+11 30465001.10 0.156272E+09 0.197520E+11 0.00 0.00 0.00 0.00
April 0.131030E+11 8754644.20 0.00 0.232631E+10 0.00 0.00 0.00 0.00
May 0.139091E+11 0.245919E+10 0.00 0.163473E+09 0.00 0.00 0.00 0.00
June 0.140489E+11 0.179986E+11 0.00 0.375869E+09 2007448.41 0.00 0.00 0.00
July 0.137810E+11 0.276962E+11 0.00 0.453481E+09 86160037.36 0.00 0.00 0.00
August 0.152086E+11 0.149942E+11 116.08 0.197439E+09 0.00 0.00 0.00 0.00
September 0.139254E+11 23690172.40 0.00 0.373284E+09 0.00 0.00 0.00 0.00
October 0.133606E+11 25591816.49 0.00 0.631981E+10 0.00 0.00 0.00 0.00
November 0.124818E+11 40371042.59 0.185259E+10 0.213180E+11 0.00 0.00 0.00 0.00
December 0.124327E+11 19180840.16 0.235020E+10 0.294552E+11 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.160052E+12 0.633319E+11 0.105895E+11 0.140726E+12 88167485.77 0.00 0.00 0.00
Minimum of Months 0.114713E+11 8754644.20 0.00 0.163473E+09 0.00 0.00 0.00 0.00
Maximum of Months 0.152086E+11 0.276962E+11 0.453296E+10 0.363881E+11 86160037.36 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.957600E+11 0.308256E+12 0.00 0.00 0.00 0.135679E+11 0.00 0.00
February 0.864929E+11 0.509104E+12 0.00 0.00 0.00 0.195376E+11 0.00 0.00
March 0.957600E+11 0.820245E+12 0.00 0.00 0.00 0.284773E+11 0.00 0.00
April 0.926710E+11 0.104501E+13 0.00 0.00 0.00 0.289977E+11 0.00 0.00
May 0.957600E+11 0.334672E+12 0.00 0.00 0.00 0.101062E+11 0.00 0.00
June 0.926710E+11 0.567000E+12 0.00 0.00 0.00 0.933358E+10 0.00 0.00
July 0.957600E+11 0.835821E+12 0.00 0.00 0.00 0.955691E+10 0.00 0.00
August 0.957600E+11 0.108747E+13 0.00 0.00 0.00 0.188061E+11 0.00 0.00
September 0.926710E+11 0.324343E+12 0.00 0.00 0.00 0.937074E+10 0.00 0.00
October 0.957600E+11 0.577297E+12 0.00 0.00 0.00 0.184776E+11 0.00 0.00
November 0.926710E+11 0.791578E+12 0.00 0.00 0.00 0.271218E+11 0.00 0.00
December 0.957600E+11 0.106596E+13 0.00 0.00 0.00 0.344740E+11 0.00 0.00
                 
Annual Sum or Average 0.112750E+13 0.826676E+13 0.00 0.00 0.00 0.227827E+12 0.00 0.00
Minimum of Months 0.864929E+11 0.308256E+12 0.00 0.00 0.00 0.933358E+10 0.00 0.00
Maximum of Months 0.957600E+11 0.108747E+13 0.00 0.00 0.00 0.344740E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.153309E+10 0.121010E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138473E+10 0.667895E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153309E+10 0.137054E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148364E+10 0.196558E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153309E+10 0.555123E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148364E+10 0.107182E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153309E+10 0.162310E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153309E+10 0.210293E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148364E+10 0.485127E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153309E+10 0.898064E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148364E+10 0.123109E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153309E+10 0.174195E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.180509E+11 0.138342E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138473E+10 0.121010E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153309E+10 0.210293E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.147273E+11 0.280579E+09 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133021E+11 0.392410E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147273E+11 0.106575E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142522E+11 0.173508E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147273E+11 0.478149E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142522E+11 0.100243E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147273E+11 0.153484E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147273E+11 0.198174E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142522E+11 0.357572E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147273E+11 0.623056E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142522E+11 0.870645E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147273E+11 0.134264E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.173402E+12 0.113871E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133021E+11 0.280579E+09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147273E+11 0.198174E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.148717E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134325E+10 0.225922E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148717E+10 0.863812E+10 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143920E+10 0.158174E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148717E+10 0.407568E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143920E+10 0.984277E+10 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148717E+10 0.151963E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148717E+10 0.194265E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143920E+10 0.216028E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148717E+10 0.400478E+10 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143920E+10 0.671475E+10 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148717E+10 0.115042E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.175102E+11 0.996400E+11 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.134325E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148717E+10 0.194265E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.321954E+10 0.431936E+11 4159758.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.300011E+10 0.219498E+11 15111421.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.460730E+10 0.744062E+10 30970039.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.779580E+10 0.625319E+09 84166107.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.910141E+10 24090422.14 0.915031E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.121604E+11 96.27 0.428501E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.128032E+11 0.00 0.576274E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.127796E+11 17869578.71 0.329116E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.561495E+10 0.258573E+09 0.561326E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.423696E+10 0.260761E+10 17713995.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.328925E+10 0.293443E+11 20285948.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.316368E+10 0.476236E+11 5297400.63 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.817721E+11 0.153085E+12 0.143278E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.300011E+10 0.00 4159758.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128032E+11 0.476236E+11 0.576274E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.414088E+11 0.780420E+12 16680259.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.355236E+11 0.466294E+12 36563613.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.366570E+11 0.232124E+12 0.171794E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.455063E+11 0.504765E+11 0.598701E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.742580E+11 0.717344E+09 0.829991E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.981857E+11 8696.91 0.373115E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.932644E+11 0.00 0.481717E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.816334E+11 0.658381E+09 0.258144E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.417466E+11 0.128467E+11 0.476980E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.328909E+11 0.147639E+12 31782058.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.369998E+11 0.593605E+12 25233660.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.404652E+11 0.865716E+12 6679649.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.658540E+12 0.315050E+13 0.120163E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.328909E+11 0.00 6679649.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.981857E+11 0.865716E+12 0.481717E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.518097E+10 0.138405E+12 686372.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.440507E+10 0.923889E+11 4108599.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.459510E+10 0.574117E+11 14499805.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.420322E+10 0.168662E+11 48164889.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.588224E+10 0.711799E+09 0.797518E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.912487E+10 1614017.95 0.386869E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.864189E+10 0.00 0.499574E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.684405E+10 0.342840E+09 0.258079E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.329536E+10 0.682294E+10 0.360093E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.396371E+10 0.429907E+11 9732057.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.477416E+10 0.114894E+12 661238.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.527169E+10 0.148954E+12 589027.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.661823E+11 0.619790E+12 0.122866E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.329536E+10 0.00 589027.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.912487E+10 0.148954E+12 0.499574E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.125141E+11 0.453296E+10 11866734.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.114713E+11 0.169746E+10 23795020.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.138154E+11 0.156272E+09 30465001.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131030E+11 0.00 8754644.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139091E+11 0.00 0.245919E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.140489E+11 0.00 0.179986E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.137810E+11 0.00 0.276962E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.152086E+11 116.08 0.149942E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.139254E+11 0.00 23690172.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133606E+11 0.00 25591816.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.124818E+11 0.185259E+10 40371042.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.124327E+11 0.235020E+10 19180840.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.160052E+12 0.105895E+11 0.633319E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.114713E+11 0.00 8754644.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.152086E+11 0.453296E+10 0.276962E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.957600E+11 0.00 0.386659E+12 0.00 0.784025E+11 0.00 0.00 0.00 0.136289E+11 0.00 0.00 0.00
February 0.864929E+11 0.00 0.631419E+12 0.00 0.122315E+12 0.00 0.00 0.00 0.196255E+11 0.00 0.00 0.00
March 0.957600E+11 0.00 0.100905E+13 0.00 0.188807E+12 0.00 0.00 0.00 0.286055E+11 0.00 0.00 0.00
April 0.926710E+11 0.00 0.127700E+13 0.00 0.231992E+12 0.00 0.00 0.00 0.291282E+11 0.00 0.00 0.00
May 0.957600E+11 0.00 0.419678E+12 0.00 0.850059E+11 0.00 0.00 0.00 0.101517E+11 0.00 0.00 0.00
June 0.926710E+11 0.00 0.713204E+12 0.00 0.146203E+12 0.00 0.00 0.00 0.937559E+10 0.00 0.00 0.00
July 0.957600E+11 0.00 0.105336E+13 0.00 0.217535E+12 0.00 0.00 0.00 0.959993E+10 0.00 0.00 0.00
August 0.957600E+11 0.00 0.135316E+13 0.00 0.265688E+12 0.00 0.00 0.00 0.188907E+11 0.00 0.00 0.00
September 0.926710E+11 0.00 0.406132E+12 0.00 0.817888E+11 0.00 0.00 0.00 0.941292E+10 0.00 0.00 0.00
October 0.957600E+11 0.00 0.715680E+12 0.00 0.138382E+12 0.00 0.00 0.00 0.185607E+11 0.00 0.00 0.00
November 0.926710E+11 0.00 0.973968E+12 0.00 0.182390E+12 0.00 0.00 0.00 0.272439E+11 0.00 0.00 0.00
December 0.957600E+11 0.00 0.130302E+13 0.00 0.237059E+12 0.00 0.00 0.00 0.346292E+11 0.00 0.00 0.00
                         
Annual Sum or Average 0.112750E+13 0.00 0.102423E+14 0.00 0.197557E+13 0.00 0.00 0.00 0.228853E+12 0.00 0.00 0.00
Minimum of Months 0.864929E+11 0.00 0.386659E+12 0.00 0.784025E+11 0.00 0.00 0.00 0.937559E+10 0.00 0.00 0.00
Maximum of Months 0.957600E+11 0.00 0.135316E+13 0.00 0.265688E+12 0.00 0.00 0.00 0.346292E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.153309E+10 0.00 0.158969E+10 0.00 0.379589E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.138473E+10 0.00 0.847269E+10 0.00 0.179374E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.153309E+10 0.00 0.171557E+11 0.00 0.345034E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.148364E+10 0.00 0.242956E+11 0.00 0.463982E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.153309E+10 0.00 0.700461E+10 0.00 0.145338E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.148364E+10 0.00 0.134699E+11 0.00 0.275171E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.153309E+10 0.00 0.204095E+11 0.00 0.417846E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.153309E+10 0.00 0.261519E+11 0.00 0.512262E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.148364E+10 0.00 0.610155E+10 0.00 0.125028E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.153309E+10 0.00 0.112712E+11 0.00 0.229059E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.148364E+10 0.00 0.154763E+11 0.00 0.316542E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153309E+10 0.00 0.217598E+11 0.00 0.434024E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.180509E+11 0.00 0.173158E+12 0.00 0.348162E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.138473E+10 0.00 0.158969E+10 0.00 0.379589E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153309E+10 0.00 0.261519E+11 0.00 0.512262E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.147273E+11 0.00 0.405263E+09 0.00 0.124684E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.133021E+11 0.00 0.501675E+11 0.00 0.109265E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.147273E+11 0.00 0.134010E+12 0.00 0.274346E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.142522E+11 0.00 0.214900E+12 0.00 0.413917E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.147273E+11 0.00 0.604464E+11 0.00 0.126315E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.142522E+11 0.00 0.126072E+12 0.00 0.258295E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147273E+11 0.00 0.193090E+12 0.00 0.396055E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.147273E+11 0.00 0.246608E+12 0.00 0.484333E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.142522E+11 0.00 0.451544E+11 0.00 0.939717E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.147273E+11 0.00 0.786077E+11 0.00 0.163021E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.142522E+11 0.00 0.110169E+12 0.00 0.231047E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.147273E+11 0.00 0.168657E+12 0.00 0.343931E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.173402E+12 0.00 0.142829E+13 0.00 0.289574E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.133021E+11 0.00 0.405263E+09 0.00 0.124684E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.147273E+11 0.00 0.246608E+12 0.00 0.484333E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.148717E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.134325E+10 0.00 0.290434E+10 0.00 0.645121E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.148717E+10 0.00 0.109043E+11 0.00 0.226614E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.143920E+10 0.00 0.196336E+11 0.00 0.381618E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.148717E+10 0.00 0.516566E+10 0.00 0.108998E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.143920E+10 0.00 0.123896E+11 0.00 0.254679E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.148717E+10 0.00 0.191320E+11 0.00 0.393569E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.148717E+10 0.00 0.241989E+11 0.00 0.477237E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.143920E+10 0.00 0.274542E+10 0.00 0.585139E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.148717E+10 0.00 0.508353E+10 0.00 0.107875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.143920E+10 0.00 0.853720E+10 0.00 0.182245E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.148717E+10 0.00 0.145033E+11 0.00 0.299910E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.175102E+11 0.00 0.125198E+12 0.00 0.255577E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.134325E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.148717E+10 0.00 0.241989E+11 0.00 0.477237E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.253210E+11 0.00 0.00 29690295.49 0.00 0.00 0.260194E+11 0.00 0.32
February 0.135295E+11 0.00 0.00 44896631.69 0.00 0.00 0.349437E+11 0.00 0.33
March 0.440937E+10 0.00 0.00 83980122.87 0.00 0.00 0.545057E+11 0.00 0.37
April 0.186200E+09 0.00 0.00 0.101403E+09 0.00 0.00 0.636748E+11 0.00 0.56
May 93167001.07 0.00 0.00 98963743.97 0.00 0.00 0.680117E+11 0.00 1.01
June 88226548.95 317625.56 0.00 0.106792E+09 0.00 0.00 0.555756E+11 0.00 1.34
July 91360275.34 0.132470E+09 0.00 0.109882E+09 24333530.33 0.00 0.475931E+11 0.00 1.26
August 0.128087E+09 0.00 0.00 0.128371E+09 0.00 0.00 0.689504E+11 0.00 1.33
September 0.208231E+09 0.00 0.00 0.110633E+09 0.00 0.00 0.704903E+11 0.00 0.75
October 0.228894E+09 0.00 0.00 0.106661E+09 0.00 0.00 0.654229E+11 0.00 0.45
November 0.188747E+11 0.00 0.00 69428820.06 0.00 0.00 0.441926E+11 0.00 0.33
December 0.327363E+11 0.00 0.00 35431414.59 0.00 0.00 0.270951E+11 0.00 0.32
                   
Annual Sum or Average 0.958951E+11 0.132787E+09 0.00 0.102613E+10 24333530.33 0.00 0.626475E+12 0.00 0.70
Minimum of Months 88226548.95 0.00 0.00 29690295.49 0.00 0.00 0.260194E+11 0.00 0.32
Maximum of Months 0.327363E+11 0.132470E+09 0.00 0.128371E+09 24333530.33 0.00 0.704903E+11 0.00 1.34



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.309506E+11 0.00 0.00 8445744.55 0.00 83872115.75 0.913333E+10 0.00 0.28
February 0.195167E+11 0.00 0.00 23401540.44 0.00 0.00 0.172946E+11 0.00 0.30
March 0.847700E+10 0.00 0.00 60480541.77 0.00 0.00 0.377131E+11 0.00 0.35
April 0.526077E+10 0.00 0.00 89433782.86 0.00 0.00 0.531129E+11 0.00 0.53
May 0.595794E+10 0.00 0.00 84477536.63 0.00 0.00 0.544178E+11 0.00 0.83
June 0.738508E+10 109962.04 0.00 92440187.53 0.00 0.00 0.443966E+11 0.00 1.08
July 0.122282E+11 0.117934E+09 0.00 88138120.00 20594493.53 0.00 0.368160E+11 0.00 1.09
August 0.112396E+11 0.00 0.00 0.104148E+09 0.00 0.00 0.554178E+11 0.00 1.12
September 0.292080E+10 0.00 0.00 77588459.30 0.00 0.00 0.502183E+11 0.00 0.55
October 0.438940E+10 0.00 0.00 61947340.69 0.00 0.00 0.394147E+11 0.00 0.37
November 0.164237E+11 0.00 0.00 30719813.66 0.00 0.00 0.283044E+11 0.00 0.31
December 0.214285E+11 0.00 0.00 22147897.34 0.00 0.00 0.273291E+11 0.00 0.29
                   
Annual Sum or Average 0.146178E+12 0.118044E+09 0.00 0.743369E+09 20594493.53 83872115.75 0.453569E+12 0.00 0.59
Minimum of Months 0.292080E+10 0.00 0.00 8445744.55 0.00 0.00 0.913333E+10 0.00 0.28
Maximum of Months 0.309506E+11 0.117934E+09 0.00 0.104148E+09 20594493.53 83872115.75 0.554178E+11 0.00 1.12



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.355103E+12 0.00 0.00 0.00 0.00 0.197698E+11 0.00 0.00 0.28
February 0.297703E+12 0.00 0.00 5189693.76 0.00 0.914783E+10 0.114518E+11 0.00 0.29
March 0.256522E+12 0.00 0.00 52061968.99 0.00 0.892361E+09 0.553383E+11 0.00 0.30
April 0.140281E+12 0.00 0.00 0.285708E+09 0.00 59767265.77 0.215456E+12 0.00 0.37
May 0.542494E+11 0.00 0.00 0.640330E+09 0.00 0.00 0.437782E+12 0.00 0.70
June 0.420687E+11 1454988.06 0.00 0.753897E+09 0.00 0.00 0.368988E+12 0.00 0.87
July 0.505827E+11 0.103897E+10 0.00 0.704494E+09 0.186546E+09 0.00 0.296143E+12 0.00 0.81
August 0.351167E+11 0.00 0.00 0.767508E+09 0.00 0.00 0.416883E+12 0.00 0.79
September 0.819133E+11 0.00 0.00 0.420691E+09 0.00 0.00 0.316417E+12 0.00 0.44
October 0.190779E+12 0.00 0.00 0.113683E+09 0.00 0.111401E+10 0.952295E+11 0.00 0.30
November 0.361758E+12 0.00 0.00 0.00 0.00 0.898795E+10 0.00 0.00 0.28
December 0.437190E+12 0.00 0.00 0.00 0.00 0.907013E+10 0.00 0.00 0.28
                   
Annual Sum or Average 0.230327E+13 0.104042E+10 0.00 0.374356E+10 0.186546E+09 0.490419E+11 0.221369E+13 0.00 0.48
Minimum of Months 0.351167E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.437190E+12 0.103897E+10 0.00 0.767508E+09 0.186546E+09 0.197698E+11 0.437782E+12 0.00 0.87



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.145794E+11 0.00 0.00 0.00 0.00 0.157859E+11 0.00 0.00 0.25
February 0.134172E+11 0.00 0.00 0.00 0.00 0.109350E+11 0.00 0.00 0.26
March 0.194902E+11 0.00 0.00 29908.59 0.00 0.435763E+10 0.114872E+09 0.00 0.28
April 0.181942E+11 0.00 0.00 7921619.56 0.00 0.649124E+09 0.838638E+10 0.00 0.32
May 0.100654E+11 0.00 0.00 41135654.52 0.00 0.00 0.315631E+11 0.00 0.61
June 0.422328E+10 9711398.85 0.00 67613390.69 0.00 0.00 0.354000E+11 0.00 0.86
July 0.476371E+10 93754194.97 0.00 63697069.05 13664275.80 0.00 0.274494E+11 0.00 0.80
August 0.559165E+10 0.00 0.00 57484352.75 0.00 0.00 0.329076E+11 0.00 0.72
September 0.173096E+11 0.00 0.00 9903182.59 0.00 0.133363E+09 0.102268E+11 0.00 0.35
October 0.173280E+11 0.00 0.00 297181.42 0.00 0.257819E+10 0.815436E+09 0.00 0.27
November 0.161615E+11 0.00 0.00 0.00 0.00 0.134545E+11 0.00 0.00 0.26
December 0.184031E+11 0.00 0.00 0.00 0.00 0.177897E+11 0.00 0.00 0.25
                   
Annual Sum or Average 0.159527E+12 0.103466E+09 0.00 0.248082E+09 13664275.80 0.656834E+11 0.146864E+12 0.00 0.44
Minimum of Months 0.422328E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.25
Maximum of Months 0.194902E+11 93754194.97 0.00 67613390.69 13664275.80 0.177897E+11 0.354000E+11 0.00 0.86



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.631766E+09 0.00 0.00 0.00 0.00 0.446489E+10 0.00 0.00 0.28
February 0.171306E+10 0.00 0.00 0.00 0.00 0.255667E+10 0.00 0.00 0.27
March 0.331396E+10 0.00 0.00 115990.99 0.00 0.986821E+09 0.169827E+09 0.00 0.27
April 0.256602E+10 0.00 0.00 3284736.10 0.00 40590272.51 0.274925E+10 0.00 0.40
May 0.109039E+10 0.00 0.00 9513961.28 0.00 0.00 0.646873E+10 0.00 0.85
June 0.769144E+09 21489.81 0.00 17624295.03 0.00 0.00 0.773434E+10 0.00 1.43
July 0.150492E+10 20791666.06 0.00 15186232.95 2585833.84 0.00 0.586826E+10 0.00 1.37
August 0.164755E+10 0.00 0.00 11925826.06 0.00 0.00 0.651101E+10 0.00 1.16
September 0.253018E+10 0.00 0.00 2845644.91 0.00 0.00 0.246458E+10 0.00 0.43
October 0.320781E+10 0.00 0.00 411827.20 0.00 0.341590E+09 0.438065E+09 0.00 0.27
November 0.189626E+10 0.00 0.00 0.00 0.00 0.308313E+10 0.00 0.00 0.26
December 0.672288E+09 0.00 0.00 0.00 0.00 0.508982E+10 0.00 0.00 0.26
                   
Annual Sum or Average 0.215434E+11 20813155.87 0.00 60908514.51 2585833.84 0.165635E+11 0.324041E+11 0.00 0.61
Minimum of Months 0.631766E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.26
Maximum of Months 0.331396E+10 20791666.06 0.00 17624295.03 2585833.84 0.508982E+10 0.773434E+10 0.00 1.43



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.511129E+09 0.00 0.00 0.00 0.00 0.461690E+10 0.00 0.00 0.44
February 0.194995E+10 0.00 0.00 0.00 0.00 0.238915E+10 0.00 0.00 0.43
March 0.304451E+10 0.00 0.00 1650455.21 0.00 0.795174E+09 0.103024E+10 0.00 0.46
April 0.238605E+10 0.00 0.00 5674856.11 0.00 59909320.92 0.394839E+10 0.00 0.71
May 0.109762E+10 0.00 0.00 14436118.36 0.00 0.00 0.899618E+10 0.00 1.69
June 0.903241E+09 20647.09 0.00 15228422.81 0.00 0.00 0.772454E+10 0.00 2.14
July 0.159814E+10 14640333.94 0.00 14893437.22 2643191.72 0.00 0.583290E+10 0.00 2.10
August 0.191215E+10 0.00 0.00 11138642.17 0.00 0.00 0.659043E+10 0.00 1.74
September 0.238301E+10 0.00 0.00 4008425.24 0.00 0.00 0.298345E+10 0.00 0.69
October 0.311118E+10 0.00 0.00 680856.57 0.00 0.463500E+09 0.567403E+09 0.00 0.43
November 0.136501E+10 0.00 0.00 0.00 0.00 0.372446E+10 0.00 0.00 0.42
December 0.320518E+09 0.00 0.00 0.00 0.00 0.556727E+10 0.00 0.00 0.42
                   
Annual Sum or Average 0.205825E+11 14660981.03 0.00 67711213.68 2643191.72 0.176164E+11 0.376735E+11 0.00 0.98
Minimum of Months 0.320518E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.42
Maximum of Months 0.311118E+10 14640333.94 0.00 15228422.81 2643191.72 0.556727E+10 0.899618E+10 0.00 2.14



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.106292E+10 0.00 0.00 0.00 0.00 0.681225E+10 0.00 0.00 0.43
February 0.304263E+10 0.00 0.00 956697.72 0.00 0.312539E+10 0.712758E+09 0.00 0.44
March 0.391001E+10 0.00 0.00 6644300.46 0.00 0.113146E+10 0.425250E+10 0.00 0.55
April 0.302296E+10 0.00 0.00 14992485.20 0.00 90193532.91 0.106523E+11 0.00 1.07
May 0.238407E+10 0.00 0.00 17849678.85 0.00 0.00 0.113362E+11 0.00 1.63
June 0.159370E+10 47810.25 0.00 20794738.07 0.00 0.00 0.953427E+10 0.00 2.03
July 0.254372E+10 37451062.35 0.00 21991062.60 3284987.80 0.00 0.706295E+10 0.00 1.99
August 0.287853E+10 0.00 0.00 20646787.32 0.00 0.00 0.105757E+11 0.00 2.04
September 0.351589E+10 0.00 0.00 8727890.19 0.00 1570294.00 0.667173E+10 0.00 0.91
October 0.444893E+10 0.00 0.00 2812811.93 0.00 0.597624E+09 0.216623E+10 0.00 0.48
November 0.283876E+10 0.00 0.00 147134.33 0.00 0.488043E+10 0.118262E+09 0.00 0.41
December 0.827001E+09 0.00 0.00 0.00 0.00 0.820089E+10 0.00 0.00 0.41
                   
Annual Sum or Average 0.320691E+11 37498872.60 0.00 0.115564E+09 3284987.80 0.248398E+11 0.630829E+11 0.00 1.04
Minimum of Months 0.827001E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.41
Maximum of Months 0.444893E+10 37451062.35 0.00 21991062.60 3284987.80 0.820089E+10 0.113362E+11 0.00 2.04



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.208440E+10 0.00 0.00 0.00 0.00 0.398451E+10 0.00 0.00 0.52
February 0.389478E+10 0.00 0.00 18904.94 0.00 0.118660E+10 53738135.65 0.00 0.50
March 0.381641E+10 0.00 0.00 2272798.05 0.00 0.116713E+09 0.188399E+10 0.00 0.55
April 0.892995E+09 0.00 0.00 14568134.39 0.00 0.00 0.944255E+10 0.00 1.24
May 0.100535E+10 0.00 0.00 12965833.59 0.00 0.00 0.791264E+10 0.00 1.63
June 0.806661E+09 19467.99 0.00 20093254.55 0.00 0.00 0.804384E+10 0.00 2.51
July 0.128666E+10 34649356.72 0.00 20273991.15 838008.94 0.00 0.686101E+10 0.00 2.50
August 0.114814E+10 0.00 0.00 21430548.92 0.00 0.00 0.994213E+10 0.00 2.55
September 0.207698E+10 0.00 0.00 4927528.41 0.00 0.00 0.425920E+10 0.00 0.86
October 0.362334E+10 0.00 0.00 1285096.74 0.00 8391326.68 0.131325E+10 0.00 0.52
November 0.552087E+10 0.00 0.00 6442.47 0.00 0.491426E+09 14442385.84 0.00 0.49
December 0.681938E+10 0.00 0.00 0.00 0.00 0.145750E+09 0.00 0.00 0.50
                   
Annual Sum or Average 0.329760E+11 34668824.72 0.00 97842533.21 838008.94 0.593339E+10 0.497268E+11 0.00 1.20
Minimum of Months 0.806661E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
Maximum of Months 0.681938E+10 34649356.72 0.00 21430548.92 838008.94 0.398451E+10 0.994213E+10 0.00 2.55



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.463849E+09 0.00 0.00 0.00 0.00 0.590356E+11 0.00 0.00 0.33
February 0.152729E+10 0.00 0.00 0.00 0.00 0.466665E+11 0.00 0.00 0.32
March 0.962373E+10 0.00 0.00 0.00 0.00 0.329734E+11 0.00 0.00 0.31
April 0.273144E+11 0.00 0.00 2877130.65 0.00 0.852121E+10 0.344389E+10 0.00 0.32
May 0.152758E+11 0.00 0.00 58823581.58 0.00 5059153.78 0.422732E+11 0.00 0.67
June 0.434615E+10 296006.06 0.00 0.147189E+09 0.00 0.00 0.649488E+11 0.00 1.20
July 0.627651E+10 0.190194E+09 0.00 0.120540E+09 23480322.63 0.00 0.467983E+11 0.00 1.06
August 0.129300E+11 0.00 0.00 71105556.22 0.00 0.00 0.394099E+11 0.00 0.78
September 0.316032E+11 0.00 0.00 5425379.40 0.00 0.198742E+10 0.641604E+10 0.00 0.35
October 0.154075E+11 0.00 0.00 0.00 0.00 0.201684E+11 0.00 0.00 0.29
November 0.617537E+09 0.00 0.00 0.00 0.00 0.535170E+11 0.00 0.00 0.31
December 0.697592E+09 0.00 0.00 0.00 0.00 0.680782E+11 0.00 0.00 0.34
                   
Annual Sum or Average 0.126084E+12 0.190490E+09 0.00 0.405961E+09 23480322.63 0.290953E+12 0.203290E+12 0.00 0.52
Minimum of Months 0.463849E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Maximum of Months 0.316032E+11 0.190194E+09 0.00 0.147189E+09 23480322.63 0.680782E+11 0.649488E+11 0.00 1.20



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.694964E+09 0.00 0.00 0.00 0.00 0.526969E+11 0.00 0.00 0.48
February 0.500297E+10 0.00 0.00 0.00 0.00 0.401686E+11 0.00 0.00 0.49
March 0.204031E+11 0.00 0.00 4319822.00 0.00 0.205423E+11 0.290132E+10 0.00 0.51
April 0.203831E+11 0.00 0.00 35157707.93 0.00 0.536814E+10 0.259715E+11 0.00 0.65
May 0.116970E+11 0.00 0.00 0.136449E+09 0.00 5556478.53 0.837964E+11 0.00 1.64
June 0.631007E+10 325023.41 0.00 0.150725E+09 0.00 0.00 0.761514E+11 0.00 2.08
July 0.756165E+10 0.164506E+09 0.00 0.154446E+09 25092662.09 0.00 0.580897E+11 0.00 1.98
August 0.107764E+11 0.00 0.00 0.102554E+09 0.00 0.00 0.604626E+11 0.00 1.52
September 0.293505E+11 0.00 0.00 21388432.46 0.00 0.135518E+10 0.172362E+11 0.00 0.65
October 0.197654E+11 0.00 0.00 1149946.21 0.00 0.178835E+11 0.813593E+09 0.00 0.49
November 0.804602E+09 0.00 0.00 0.00 0.00 0.514481E+11 0.00 0.00 0.49
December 0.900362E+09 0.00 0.00 0.00 0.00 0.621368E+11 0.00 0.00 0.48
                   
Annual Sum or Average 0.133650E+12 0.164831E+09 0.00 0.606190E+09 25092662.09 0.251605E+12 0.325423E+12 0.00 0.96
Minimum of Months 0.694964E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.48
Maximum of Months 0.293505E+11 0.164506E+09 0.00 0.154446E+09 25092662.09 0.621368E+11 0.837964E+11 0.00 2.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.488414E+10 0.00 0.00 0.00 0.00 0.759771E+11 0.00 0.00 0.47
February 0.182680E+11 0.00 0.00 5790025.19 0.00 0.468935E+11 0.394855E+10 0.00 0.49
March 0.281281E+11 0.00 0.00 54434879.40 0.00 0.237121E+11 0.303564E+11 0.00 0.62
April 0.240517E+11 0.00 0.00 0.132984E+09 0.00 0.534691E+10 0.916318E+11 0.00 1.02
May 0.246238E+11 0.00 0.00 0.178965E+09 0.00 8464333.48 0.108403E+12 0.00 1.64
June 0.157319E+11 715031.54 0.00 0.194946E+09 0.00 0.00 0.857697E+11 0.00 1.91
July 0.163679E+11 0.423180E+09 0.00 0.203740E+09 30723567.22 0.00 0.618498E+11 0.00 1.77
August 0.194218E+11 0.00 0.00 0.188616E+09 0.00 0.00 0.923280E+11 0.00 1.79
September 0.357026E+11 0.00 0.00 80853360.81 0.00 0.137407E+10 0.598479E+11 0.00 0.91
October 0.310105E+11 0.00 0.00 20294333.38 0.00 0.196960E+11 0.140097E+11 0.00 0.52
November 0.927791E+10 0.00 0.00 696808.84 0.00 0.694166E+11 0.507223E+09 0.00 0.48
December 0.139819E+10 0.00 0.00 0.00 0.00 0.942934E+11 0.00 0.00 0.47
                   
Annual Sum or Average 0.228867E+12 0.423895E+09 0.00 0.106132E+10 30723567.22 0.336718E+12 0.548652E+12 0.00 1.01
Minimum of Months 0.139819E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.47
Maximum of Months 0.357026E+11 0.423180E+09 0.00 0.203740E+09 30723567.22 0.942934E+11 0.108403E+12 0.00 1.91



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.758524E+09 0.00 0.00 0.00 0.00 0.531409E+11 0.00 0.00 0.49
February 0.523690E+10 0.00 0.00 0.00 0.00 0.403357E+11 0.00 0.00 0.50
March 0.193420E+11 0.00 0.00 1039327.68 0.00 0.236252E+11 0.117121E+10 0.00 0.51
April 0.242543E+11 0.00 0.00 36277434.72 0.00 0.424119E+10 0.278339E+11 0.00 0.74
May 0.179968E+11 0.00 0.00 79913709.17 0.00 5677035.92 0.479632E+11 0.00 1.25
June 0.773446E+10 214540.50 0.00 0.129767E+09 0.00 0.00 0.519172E+11 0.00 1.80
July 0.865402E+10 0.271289E+09 0.00 0.103679E+09 21147580.83 0.00 0.360751E+11 0.00 1.54
August 0.137526E+11 0.00 0.00 83273677.78 0.00 0.00 0.405557E+11 0.00 1.35
September 0.338422E+11 0.00 0.00 12999807.20 0.00 0.130124E+10 0.122728E+11 0.00 0.67
October 0.217564E+11 0.00 0.00 141768.29 0.00 0.171244E+11 0.208493E+09 0.00 0.49
November 0.263127E+10 0.00 0.00 0.00 0.00 0.501699E+11 0.00 0.00 0.49
December 0.171551E+10 0.00 0.00 0.00 0.00 0.618661E+11 0.00 0.00 0.49
                   
Annual Sum or Average 0.157675E+12 0.271503E+09 0.00 0.447091E+09 21147580.83 0.251810E+12 0.217998E+12 0.00 0.86
Minimum of Months 0.758524E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.49
Maximum of Months 0.338422E+11 0.271289E+09 0.00 0.129767E+09 21147580.83 0.618661E+11 0.519172E+11 0.00 1.80



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 27880027.55 0.00 0.00 0.00 0.00 0.673662E+10 0.00 0.00 0.41
February 31390612.06 0.00 0.00 0.00 0.00 0.502853E+10 0.00 0.00 0.39
March 0.286764E+09 0.00 0.00 0.00 0.00 0.407348E+10 0.00 0.00 0.39
April 0.276677E+10 0.00 0.00 3841.07 0.00 0.145249E+10 29038262.27 0.00 0.40
May 0.311248E+10 0.00 0.00 2851974.08 0.00 99081635.14 0.242162E+10 0.00 0.66
June 0.750325E+09 2509851.53 0.00 12677696.13 0.00 0.00 0.589066E+10 0.00 1.18
July 0.105199E+10 16945544.67 0.00 10374717.46 2178430.46 0.00 0.404647E+10 0.00 1.06
August 0.227768E+10 0.00 0.00 4820251.82 0.00 49255885.30 0.275802E+10 0.00 0.78
September 0.321854E+10 0.00 0.00 3756.23 0.00 0.101219E+10 19901508.37 0.00 0.43
October 0.563681E+09 0.00 0.00 0.00 0.00 0.289479E+10 0.00 0.00 0.36
November 24166929.67 0.00 0.00 0.00 0.00 0.611443E+10 0.00 0.00 0.39
December 36549533.06 0.00 0.00 0.00 0.00 0.807595E+10 0.00 0.00 0.43
                   
Annual Sum or Average 0.141482E+11 19455396.20 0.00 30732236.79 2178430.46 0.355368E+11 0.151657E+11 0.00 0.57
Minimum of Months 24166929.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.36
Maximum of Months 0.321854E+10 16945544.67 0.00 12677696.13 2178430.46 0.807595E+10 0.589066E+10 0.00 1.18



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 24015882.08 0.00 0.00 0.00 0.00 0.468081E+10 0.00 0.00 0.46
February 94629473.58 0.00 0.00 0.00 0.00 0.349339E+10 0.00 0.00 0.46
March 0.104814E+10 0.00 0.00 31115.08 0.00 0.231910E+10 27580829.63 0.00 0.48
April 0.181760E+10 0.00 0.00 2058808.39 0.00 0.687044E+09 0.150127E+10 0.00 0.58
May 0.108696E+10 0.00 0.00 11658896.51 0.00 39091844.74 0.725087E+10 0.00 1.50
June 0.602341E+09 1520706.75 0.00 14696555.27 0.00 0.00 0.748831E+10 0.00 2.08
July 0.765934E+09 14760269.45 0.00 15428457.36 1790956.74 0.00 0.562494E+10 0.00 1.99
August 0.105267E+10 0.00 0.00 9262930.24 0.00 27224869.46 0.531931E+10 0.00 1.45
September 0.253663E+10 0.00 0.00 1045571.15 0.00 0.466274E+09 0.745272E+09 0.00 0.58
October 0.832013E+09 0.00 0.00 8099.31 0.00 0.199559E+10 12638436.03 0.00 0.46
November 20945438.47 0.00 0.00 0.00 0.00 0.435326E+10 0.00 0.00 0.45
December 30984887.23 0.00 0.00 0.00 0.00 0.550957E+10 0.00 0.00 0.46
                   
Annual Sum or Average 0.991287E+10 16280976.20 0.00 54190433.32 1790956.74 0.235714E+11 0.279702E+11 0.00 0.92
Minimum of Months 20945438.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.253663E+10 14760269.45 0.00 15428457.36 1790956.74 0.550957E+10 0.748831E+10 0.00 2.08



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.148049E+09 0.00 0.00 0.00 0.00 0.690850E+10 0.00 0.00 0.46
February 0.761653E+09 0.00 0.00 150131.20 0.00 0.463862E+10 90518592.26 0.00 0.46
March 0.158822E+10 0.00 0.00 3177818.86 0.00 0.273656E+10 0.166439E+10 0.00 0.55
April 0.188299E+10 0.00 0.00 9653429.16 0.00 0.787531E+09 0.727094E+10 0.00 0.91
May 0.248500E+10 0.00 0.00 15185816.29 0.00 98448071.12 0.968420E+10 0.00 1.51
June 0.172970E+10 2674668.90 0.00 18653256.12 0.00 0.00 0.845714E+10 0.00 1.90
July 0.197909E+10 36667271.54 0.00 20095456.42 1583996.78 0.00 0.586822E+10 0.00 1.80
August 0.217958E+10 0.00 0.00 16836614.43 0.00 52911542.64 0.830675E+10 0.00 1.73
September 0.304913E+10 0.00 0.00 5245753.28 0.00 0.617525E+09 0.401896E+10 0.00 0.80
October 0.173176E+10 0.00 0.00 1006283.42 0.00 0.237512E+10 0.655379E+09 0.00 0.49
November 0.270376E+09 0.00 0.00 0.00 0.00 0.637897E+10 0.00 0.00 0.45
December 49288504.36 0.00 0.00 0.00 0.00 0.830426E+10 0.00 0.00 0.45
                   
Annual Sum or Average 0.178548E+11 39341940.44 0.00 90004559.19 1583996.78 0.328984E+11 0.460165E+11 0.00 0.96
Minimum of Months 49288504.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.304913E+10 36667271.54 0.00 20095456.42 1583996.78 0.830426E+10 0.968420E+10 0.00 1.90



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 27234205.39 0.00 0.00 0.00 0.00 0.469938E+10 0.00 0.00 0.47
February 0.106696E+09 0.00 0.00 0.00 0.00 0.353114E+10 0.00 0.00 0.47
March 0.921885E+09 0.00 0.00 0.00 0.00 0.259914E+10 0.00 0.00 0.51
April 0.202067E+10 0.00 0.00 2692326.03 0.00 0.639224E+09 0.211102E+10 0.00 0.70
May 0.219885E+10 0.00 0.00 6048585.83 0.00 77692785.54 0.379667E+10 0.00 1.16
June 0.954159E+09 3753272.27 0.00 12098901.56 0.00 0.00 0.494250E+10 0.00 1.79
July 0.110712E+10 24319504.41 0.00 9637221.06 1447291.35 0.00 0.323381E+10 0.00 1.55
August 0.164965E+10 0.00 0.00 6888364.05 0.00 36039813.16 0.335606E+10 0.00 1.31
September 0.285139E+10 0.00 0.00 670505.28 0.00 0.488531E+09 0.630018E+09 0.00 0.63
October 0.998832E+09 0.00 0.00 0.00 0.00 0.199406E+10 0.00 0.00 0.49
November 32544471.53 0.00 0.00 0.00 0.00 0.431674E+10 0.00 0.00 0.46
December 34777475.45 0.00 0.00 0.00 0.00 0.531988E+10 0.00 0.00 0.45
                   
Annual Sum or Average 0.129038E+11 28072776.69 0.00 38035903.81 1447291.35 0.237018E+11 0.180701E+11 0.00 0.83
Minimum of Months 27234205.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.45
Maximum of Months 0.285139E+10 24319504.41 0.00 12098901.56 1447291.35 0.531988E+10 0.494250E+10 0.00 1.79



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.158796E+09 0.00 0.00 1151921.19 0.00 0.00 0.102967E+10 0.00 0.28
February 0.00 0.00 0.00 6049147.12 0.00 0.00 0.973490E+09 0.00 0.29
March 0.00 0.00 0.00 14146953.79 0.00 0.00 0.102502E+10 0.00 0.31
April 0.00 0.00 0.00 17596362.74 0.00 0.00 0.636723E+09 0.00 0.29
May 0.00 0.00 0.00 3899541.43 0.00 0.00 0.454633E+09 0.00 0.30
June 0.00 1503445.45 0.00 8112578.06 0.00 0.00 0.251663E+09 0.00 0.30
July 0.00 2255028.17 0.00 11140434.99 0.00 0.00 0.126387E+09 0.00 0.28
August 0.00 6787.73 0.00 17970455.83 0.00 0.00 0.262795E+09 0.00 0.30
September 0.00 0.00 0.00 3573042.56 0.00 0.00 0.539916E+09 0.00 0.29
October 0.00 0.00 0.00 7447953.96 0.00 0.00 0.805125E+09 0.00 0.28
November 0.00 0.00 0.00 10713412.26 0.00 0.00 0.112763E+10 0.00 0.28
December 0.00 0.00 0.00 15823801.48 0.00 0.00 0.120988E+10 0.00 0.28
                   
Annual Sum or Average 0.158796E+09 3765261.35 0.00 0.117626E+09 0.00 0.00 0.844294E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 1151921.19 0.00 0.00 0.126387E+09 0.00 0.28
Maximum of Months 0.158796E+09 2255028.17 0.00 17970455.83 0.00 0.00 0.120988E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.994565E+10 0.00 0.00 721991.41 0.00 0.00 0.158970E+10 0.00 0.28
February 0.00 0.00 0.00 41614824.62 0.00 0.00 0.975226E+10 0.00 0.29
March 0.00 0.00 0.00 0.115502E+09 0.00 0.00 0.102761E+11 0.00 0.31
April 0.00 0.00 0.00 0.158065E+09 0.00 0.00 0.638542E+10 0.00 0.29
May 0.00 0.00 0.00 33913789.48 0.00 0.00 0.455153E+10 0.00 0.30
June 0.00 14763890.10 0.00 76419552.42 0.00 0.00 0.252347E+10 0.00 0.30
July 0.00 22328795.62 0.00 0.105811E+09 0.00 0.00 0.127273E+10 0.00 0.28
August 0.00 66696.48 0.00 0.169849E+09 0.00 0.00 0.263815E+10 0.00 0.30
September 0.00 0.00 0.00 26086075.68 0.00 0.00 0.541570E+10 0.00 0.29
October 0.00 0.00 0.00 55244042.15 0.00 0.00 0.806954E+10 0.00 0.28
November 0.00 0.00 0.00 83113881.74 0.00 0.00 0.113000E+11 0.00 0.28
December 0.00 0.00 0.00 0.130736E+09 0.00 0.00 0.121264E+11 0.00 0.28
                   
Annual Sum or Average 0.994565E+10 37159382.20 0.00 0.997077E+09 0.00 0.00 0.759011E+11 0.00 0.29
Minimum of Months 0.00 0.00 0.00 721991.41 0.00 0.00 0.127273E+10 0.00 0.28
Maximum of Months 0.994565E+10 22328795.62 0.00 0.169849E+09 0.00 0.00 0.121264E+11 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.111847E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
February 8004145.15 0.00 0.00 3121076.00 0.00 0.00 0.967887E+09 0.00 0.29
March 0.00 0.00 0.00 10113855.38 0.00 0.00 0.102905E+10 0.00 0.31
April 0.00 0.00 0.00 14860753.17 0.00 0.00 0.639481E+09 0.00 0.29
May 2390789.42 0.00 0.00 2992527.59 0.00 0.00 0.453169E+09 0.00 0.30
June 0.00 1481786.86 0.00 7581964.00 0.00 0.00 0.252543E+09 0.00 0.30
July 0.00 2233195.20 0.00 10517719.65 0.00 0.00 0.127469E+09 0.00 0.28
August 0.00 6592.47 0.00 16707659.41 0.00 0.00 0.264284E+09 0.00 0.30
September 74306217.09 0.00 0.00 1574234.97 0.00 0.00 0.468293E+09 0.00 0.29
October 0.00 0.00 0.00 4226631.72 0.00 0.00 0.808287E+09 0.00 0.28
November 0.00 0.00 0.00 7201031.80 0.00 0.00 0.113112E+10 0.00 0.28
December 0.00 0.00 0.00 11935422.77 0.00 0.00 0.121378E+10 0.00 0.28
                   
Annual Sum or Average 0.120317E+10 3721574.53 0.00 90832876.46 0.00 0.00 0.735536E+10 0.00 0.29
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.111847E+10 2233195.20 0.00 16707659.41 0.00 0.00 0.121378E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.00 0.00 0.208519E+09 0.00 0.00 0.312636E+11 0.00 0.32
February 0.00 0.00 0.00 0.394693E+09 0.00 0.00 0.257091E+11 0.00 0.32
March 0.00 0.00 0.00 0.764587E+09 0.00 0.00 0.273422E+11 0.00 0.35
April 0.00 0.00 0.00 0.878403E+09 0.00 0.00 0.174393E+11 0.00 0.33
May 0.00 0.00 0.00 0.208791E+09 0.00 0.00 0.118786E+11 0.00 0.33
June 0.00 41929660.85 0.00 0.398796E+09 0.00 0.00 0.558979E+10 0.00 0.34
July 0.00 56957385.18 0.00 0.529233E+09 0.00 0.00 0.244406E+10 0.00 0.32
August 0.00 249774.08 0.00 0.885738E+09 0.00 0.00 0.563094E+10 0.00 0.34
September 0.00 0.00 0.00 0.215126E+09 0.00 0.00 0.128713E+11 0.00 0.33
October 0.00 0.00 0.00 0.429555E+09 0.00 0.00 0.207254E+11 0.00 0.32
November 0.00 0.00 0.00 0.618472E+09 0.00 0.00 0.297319E+11 0.00 0.32
December 0.00 0.00 0.00 0.888186E+09 0.00 0.00 0.317770E+11 0.00 0.32
                   
Annual Sum or Average 0.00 99136820.10 0.00 0.642010E+10 0.00 0.00 0.222403E+12 0.00 0.33
Minimum of Months 0.00 0.00 0.00 0.208519E+09 0.00 0.00 0.244406E+10 0.00 0.32
Maximum of Months 0.00 56957385.18 0.00 0.888186E+09 0.00 0.00 0.317770E+11 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:04:27

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January -0.128617E+11 0.247189E+11 0.00 0.189493E+13 0.681908E+12
February 0.833942E+11 0.202886E+11 0.00 0.173608E+13 0.909830E+12
March 0.384092E+12 0.307252E+11 0.00 0.207097E+13 0.133449E+13
April 0.671442E+12 0.334195E+11 0.00 0.200754E+13 0.165084E+13
May 0.826085E+12 0.199458E+11 0.00 0.227174E+13 0.679717E+12
June 0.851279E+12 0.111951E+11 0.00 0.188940E+13 0.153902E+13
July 0.772828E+12 0.902412E+10 0.00 0.197806E+13 0.215612E+13
August 0.583292E+12 0.106014E+11 0.00 0.211377E+13 0.220294E+13
September 0.279553E+12 0.124056E+11 0.00 0.212509E+13 0.513770E+12
October 0.129866E+12 0.265360E+11 0.00 0.196946E+13 0.937525E+12
November 0.142517E+11 0.956115E+10 0.00 0.198786E+13 0.137228E+13
December -0.310668E+11 0.181381E+11 0.00 0.197632E+13 0.183046E+13
           
Annual Sum or Average 0.455215E+13 0.226560E+12 0.00 0.240212E+14 0.158089E+14
Minimum of Months -0.310668E+11 0.902412E+10 0.00 0.173608E+13 0.513770E+12
Maximum of Months 0.851279E+12 0.334195E+11 0.00 0.227174E+13 0.220294E+13