Table of Contents

Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04

Tabular Output Report in Format: HTML

Building: OfficeLarge

Environment: RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880

Simulation Timestamp: 2023-10-16 09:04:59


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [GJ] Energy Per Total Building Area [MJ/m2] Energy Per Conditioned Building Area [MJ/m2]
Total Site Energy 31644.45 683.16 683.16
Net Site Energy 31644.45 683.16 683.16
Total Source Energy 98876.74 2134.63 2134.63
Net Source Energy 98876.74 2134.63 2134.63


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [m2]
Total Building Area 46320.38
Net Conditioned Building Area 46320.38
Unconditioned Building Area 0.00


End Uses

Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating 0.00 48.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 5101.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2740.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 447.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2510.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 1113.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 1896.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11132.31
Humidification 1.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
Heat Recovery 60.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 595.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 31000.55 643.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 13413.05
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 48.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 5101.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 2740.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 447.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 5871.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 9341.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 59.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 1848.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 5.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 2510.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 1113.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 1896.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11132.31
Humidification General 1.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
Heat Recovery General 60.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
  Water Heater 0.00 595.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [GJ] Natural Gas [GJ] Gasoline [GJ] Diesel [GJ] Coal [GJ] Fuel Oil No 1 [GJ] Fuel Oil No 2 [GJ] Propane [GJ] Other Fuel 1 [GJ] Other Fuel 2 [GJ] District Cooling [GJ] District Heating [GJ] Water [m3]
Heating Unassigned 0.00 48.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 5101.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 2740.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 447.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 15213.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 1914.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 2510.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 1113.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 1896.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11132.31
Humidification Unassigned 1.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.57
Heat Recovery Unassigned 60.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 595.33 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2280.17
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 229.37 13.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Other 371.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 669.26 13.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29


Utility Use Per Total Floor Area

Electricity Intensity [MJ/m2] Natural Gas Intensity [MJ/m2] Gasoline Intensity [MJ/m2] Diesel Intensity [MJ/m2] Coal Intensity [MJ/m2] Fuel Oil No 1 Intensity [MJ/m2] Fuel Oil No 2 Intensity [MJ/m2] Propane Intensity [MJ/m2] Other Fuel 1 Intensity [MJ/m2] Other Fuel 2 Intensity [MJ/m2] District Cooling Intensity [MJ/m2] District Heating Intensity [MJ/m2] Water Intensity [m3/m2]
Lighting 68.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 229.37 13.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29
Other 371.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 669.26 13.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.29


Electric Loads Satisfied

Electricity [GJ] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 31000.553 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 31000.553 100.00
     
Total On-Site and Utility Electric Sources 31000.553 100.00
Total Electricity End Uses 31000.553 100.00


On-Site Thermal Sources

Heat [GJ] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 2232.72 98.55
Air to Air Heat Recovery for Heating 32.93 1.45
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 2265.64 100.00


Water Source Summary

Water [m3] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 13413.05 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 13413.05 100.00
Total Water End Uses 13413.05 100.00


Setpoint Not Met Criteria

Degrees [deltaC]
Tolerance for Zone Heating Setpoint Not Met Time 0.56
Tolerance for Zone Cooling Setpoint Not Met Time 0.56


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 1.50
Time Setpoint Not Met During Occupied Cooling 754.67
Time Not Comfortable Based on Simple ASHRAE 55-2004 5943.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual Thermal Resilience Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

| Environment |

NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

| Environment |

NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

| Environment |

NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

| Environment |

NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

| Environment |

NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

| Environment |

ZoneCoolingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneHeatingSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ZoneElectricSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

SpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

PeakSpaceGainsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |

SpaceGainComponentsAtCoolingPeakMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

EnergyConsumptionElectricityNaturalGasMonthly

| Meter |

EndUseEnergyConsumptionElectricityMonthly

| Meter |

EndUseEnergyConsumptionNaturalGasMonthly

| Meter |

PeakEnergyEndUseElectricityPart1Monthly

| Meter |

PeakEnergyEndUseElectricityPart2Monthly

| Meter |

ElectricComponentsOfPeakDemandMonthly

| Meter |

PeakEnergyEndUseNaturalGasMonthly

| Meter |

SetpointsNotMetWithTemperaturesMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

ComfortReportSimple55Monthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

OccupantComfortDataSummaryMonthly

| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |

ChillerReportMonthly

| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |

TowerReportMonthly

| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |

BoilerReportMonthly

| HEATSYS1 BOILER | CENTRAL BOILER |

DXReportMonthly

| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

WindowReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowEnergyReportMonthly

| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |

WindowZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

WindowEnergyZoneSummaryMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AverageOutdoorConditionsMonthly

| Environment |

OutdoorConditionsMaximumDryBulbMonthly

| Environment |

OutdoorConditionsMinimumDryBulbMonthly

| Environment |

OutdoorConditionsMaximumWetBulbMonthly

| Environment |

OutdoorConditionsMaximumDewPointMonthly

| Environment |

OutdoorGroundConditionsMonthly

| Environment |

WaterHeaterReportMonthly

| SWHSYS1 WATER HEATER |

DaylightingReportMonthly

| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |

CoilReportMonthly

| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |

PlantLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

FanReportMonthly

| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |

PumpReportMonthly

| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |

CondLoopDemandReportMonthly

| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |

ZoneTemperatureOscillationReportMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

AirLoopSystemEnergyAndWaterUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentLoadsMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

AirLoopSystemComponentEnergyUseMonthly

| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |

MechanicalVentilationLoadsMonthly

| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |

HeatEmissionsReportMonthly

| Environment |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

General

Value
Program Version and Build EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
RunPeriod RUNPERIOD 1
Weather File Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Latitude [deg] 27.85
Longitude [deg] -82.5
Elevation [m] 8.00
Time Zone -5.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [m2] 12183.89 3655.17 2436.78 3655.17 2436.78
Above Ground Wall Area [m2] 11589.54 3476.86 2317.91 3476.86 2317.91
Window Opening Area [m2] 3476.85 1043.06 695.37 1043.06 695.37
Gross Window-Wall Ratio [%] 28.54 28.54 28.54 28.54 28.54
Above Ground Window-Wall Ratio [%] 30.00 30.00 30.00 30.00 30.00


Skylight-Roof Ratio

Total
Gross Roof Area [m2] 3563.11
Skylight Area [m2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [m3] Multipliers Above Ground Gross Wall Area [m2] Underground Gross Wall Area [m2] Window Glass Area [m2] Opening Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
BASEMENT 2779.43 Yes Yes 6779.02 1.00 0.00 397.05 0.00 0.00 7.6202 18.58 4.8418
CORE_BOTTOM 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0697
CORE_MID 2496.12 Yes Yes 6849.35 10.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
CORE_TOP 2496.12 Yes Yes 6849.35 1.00 0.00 0.00 0.00 0.00 7.6202 18.58 8.0696
PERIMETER_BOT_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_BOT_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_BOT_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_MID_ZN_3 313.41 Yes Yes 860.00 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_MID_ZN_2 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_MID_ZN_1 313.42 Yes Yes 860.02 10.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_MID_ZN_4 201.98 Yes Yes 554.22 10.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_3 313.41 Yes Yes 860.00 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_2 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0700
PERIMETER_TOP_ZN_1 313.42 Yes Yes 860.02 1.00 200.61 0.00 86.92 86.92 7.6202 18.58 8.0699
PERIMETER_TOP_ZN_4 201.98 Yes Yes 554.22 1.00 133.74 0.00 57.95 57.95 7.6202 18.58 8.0699
GROUNDFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
MIDFLOOR_PLENUM 3563.11 Yes No 4344.14 10.00 297.11 0.00 0.00 0.00 0.0000   0.0000
TOPFLOOR_PLENUM 3563.11 Yes No 4344.14 1.00 297.11 0.00 0.00 0.00 0.0000   0.0000
DATACENTER_BOT_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_MID_ZN_6 36.20 Yes Yes 99.34 10.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_TOP_ZN_6 36.20 Yes Yes 99.34 1.00 0.00 0.00 0.00 0.00 12.5114 18.58 215.2992
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1911.37 1.00 0.00 197.31 0.00 0.00 7.6202 18.58 484.4232
Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Conditioned Total 46320.38     126016.35   8024.24 594.36 3476.85 3476.85 7.6661 18.58 17.8789
Unconditioned Total 0.00     0.00   0.00 0.00 0.00 0.00      
Not Part of Total 42757.27     52129.67   3565.29 0.00 0.00 0.00 0.0000   0.0000


Space Summary

Area [m2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [W/m2] People [m2 per person] Plug and Process [W/m2] Tags
BASEMENT 2779.43 Yes Yes 1.00 BASEMENT GENERAL BASEMENT 7.6202 18.58 4.8418  
CORE_BOTTOM 2496.12 Yes Yes 1.00 CORE_BOTTOM GENERAL CORE_BOTTOM 7.6202 18.58 8.0697  
CORE_MID 2496.12 Yes Yes 10.00 CORE_MID GENERAL CORE_MID 7.6202 18.58 8.0696  
CORE_TOP 2496.12 Yes Yes 1.00 CORE_TOP GENERAL CORE_TOP 7.6202 18.58 8.0696  
PERIMETER_BOT_ZN_3 313.41 Yes Yes 1.00 PERIMETER_BOT_ZN_3 GENERAL PERIMETER_BOT_ZN_3 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_2 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_2 GENERAL PERIMETER_BOT_ZN_2 7.6202 18.58 8.0700  
PERIMETER_BOT_ZN_1 313.42 Yes Yes 1.00 PERIMETER_BOT_ZN_1 GENERAL PERIMETER_BOT_ZN_1 7.6202 18.58 8.0699  
PERIMETER_BOT_ZN_4 201.98 Yes Yes 1.00 PERIMETER_BOT_ZN_4 GENERAL PERIMETER_BOT_ZN_4 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_3 313.41 Yes Yes 10.00 PERIMETER_MID_ZN_3 GENERAL PERIMETER_MID_ZN_3 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_2 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_2 GENERAL PERIMETER_MID_ZN_2 7.6202 18.58 8.0700  
PERIMETER_MID_ZN_1 313.42 Yes Yes 10.00 PERIMETER_MID_ZN_1 GENERAL PERIMETER_MID_ZN_1 7.6202 18.58 8.0699  
PERIMETER_MID_ZN_4 201.98 Yes Yes 10.00 PERIMETER_MID_ZN_4 GENERAL PERIMETER_MID_ZN_4 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_3 313.41 Yes Yes 1.00 PERIMETER_TOP_ZN_3 GENERAL PERIMETER_TOP_ZN_3 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_2 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_2 GENERAL PERIMETER_TOP_ZN_2 7.6202 18.58 8.0700  
PERIMETER_TOP_ZN_1 313.42 Yes Yes 1.00 PERIMETER_TOP_ZN_1 GENERAL PERIMETER_TOP_ZN_1 7.6202 18.58 8.0699  
PERIMETER_TOP_ZN_4 201.98 Yes Yes 1.00 PERIMETER_TOP_ZN_4 GENERAL PERIMETER_TOP_ZN_4 7.6202 18.58 8.0699  
GROUNDFLOOR_PLENUM 3563.11 Yes No 1.00 GROUNDFLOOR_PLENUM GENERAL GROUNDFLOOR_PLENUM 0.0000 0.00 0.0000  
MIDFLOOR_PLENUM 3563.11 Yes No 10.00 MIDFLOOR_PLENUM GENERAL MIDFLOOR_PLENUM 0.0000 0.00 0.0000  
TOPFLOOR_PLENUM 3563.11 Yes No 1.00 TOPFLOOR_PLENUM GENERAL TOPFLOOR_PLENUM 0.0000 0.00 0.0000  
DATACENTER_BOT_ZN_6 36.20 Yes Yes 1.00 DATACENTER_BOT_ZN_6 GENERAL DATACENTER_BOT_ZN_6 12.5114 18.58 215.2992  
DATACENTER_MID_ZN_6 36.20 Yes Yes 10.00 DATACENTER_MID_ZN_6 GENERAL DATACENTER_MID_ZN_6 12.5114 18.58 215.2992  
DATACENTER_TOP_ZN_6 36.20 Yes Yes 1.00 DATACENTER_TOP_ZN_6 GENERAL DATACENTER_TOP_ZN_6 12.5114 18.58 215.2992  
DATACENTER_BASEMENT_ZN_6 783.68 Yes Yes 1.00 DATACENTER_BASEMENT_ZN_6 GENERAL DATACENTER_BASEMENT_ZN_6 7.6202 18.58 484.4232  
Total 46320.38             7.6661 9.29 17.8789  
Conditioned Total 46320.38             7.6661 9.29 17.8789  
Unconditioned Total 0.00             0.0000 0.00 0.0000  
Not Part of Total 42757.27             0.0000 0.00 0.0000  


Space Type Summary

Total Area [m2] Conditioned Area [m2] Unconditioned Area [m2] Not Part of Total Area [m2] Lighting [W/m2] People [m2 per person] Plug and Process [W/m2]
GENERAL 46320.38 46320.38 0.00 42757.27 2.3561 60.38 10.8345
Total 46320.38 46320.38 0.00 42757.27      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

End Uses

Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Time of Peak 03-AUG-15:20 21-DEC-07:10 - - - - - - - - - - 13-JUN-15:09
Heating 0.00 467400.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 443007.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 794004.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 83146.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 200875.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 70372.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 93886.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 28401.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1925340.49 495802.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Subcategory

Subcategory Electricity [W] Natural Gas [W] Gasoline [W] Diesel [W] Coal [W] Fuel Oil No 1 [W] Fuel Oil No 2 [W] Propane [W] Other Fuel 1 [W] Other Fuel 2 [W] District Cooling [W] Steam [W] Water [m3/s]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 467400.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 443007.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting LightsWired 234435.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment MiscPlug 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  DataCenterPlugLoads 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Transformer 3711.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLift 79171.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  ElevatorLightsFan 263.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 200875.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 70372.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 93886.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater 0.00 28401.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [GJ] Source Natural Gas [GJ] Source Gasoline [GJ] Source Diesel [GJ] Source Coal [GJ] Source Fuel Oil No 1 [GJ] Source Fuel Oil No 2 [GJ] Source Propane [GJ] Source Other Fuel 1 [GJ] Source Other Fuel 2 [GJ] Source District Cooling [GJ] Source District Heating [GJ]
Heating 0.00 52.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 16157.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8680.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1416.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 48180.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 6062.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 7951.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 3527.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 6006.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 4.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 190.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 645.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 98178.75 697.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 348.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 171.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 76.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 129.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2119.56 15.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [MJ/m2] Source Natural Gas [MJ/m2] Source Gasoline [MJ/m2] Source Diesel [MJ/m2] Source Coal [MJ/m2] Source Fuel Oil No 1 [MJ/m2] Source Fuel Oil No 2 [MJ/m2] Source Propane [MJ/m2] Source Other Fuel 1 [MJ/m2] Source Other Fuel 2 [MJ/m2] Source District Cooling [MJ/m2] Source District Heating [MJ/m2]
Heating 0.00 1.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 348.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 187.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 30.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1040.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 130.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 171.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 76.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 129.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 4.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 13.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2119.56 15.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [m3/s]
BASEMENT DIRECT AIR 5.48
DATACENTER_BOT_ZN_6 DIRECT AIR 0.465681
DATACENTER_MID_ZN_6 DIRECT AIR 4.43
DATACENTER_TOP_ZN_6 DIRECT AIR 0.451387
DATACENTER_BASEMENT_ZN_6 DIRECT AIR 21.33
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:VAV:Reheat

Design Size Maximum Air Flow Rate [m3/s] Design Size Constant Minimum Air Flow Fraction User-Specified Constant Minimum Air Flow Fraction Design Size Minimum Air Flow Rate [m3/s] Design Size Maximum Flow Fraction during Reheat [] User-Specified Maximum Flow Fraction during Reheat [] Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] Design Size Maximum Reheat Water Flow Rate [m3/s] Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] Design Size Reheat Coil Sizing Inlet Air Temperature [C] Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir]
CORE_BOTTOM VAV BOX COMPONENT 5.64 0.337300 0.335000 1.89 0.899466 0.500000 0.001130 0.000166 1.89 12.80 0.008000
CORE_MID VAV BOX COMPONENT 52.80 0.360250 0.349000 18.43 0.960666 0.500000 0.001058 0.003224 18.43 12.80 0.008000
CORE_TOP VAV BOX COMPONENT 5.23 0.363666 0.361000 1.89 0.969775 0.500000 0.001048 0.000540 1.89 12.80 0.008000
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT 0.908251 0.262946 0.261000 0.237053 0.701188 0.500000 0.001449 0.000049 0.237053 12.80 0.008000
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT 0.929224 0.165628 0.200000 0.185845 0.441673 0.500000 0.002300 0.000038 0.185845 12.80 0.008000
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT 1.10 0.217235 0.216000 0.237468 0.579293 0.500000 0.001754 0.000064 0.237468 12.80 0.008000
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT 1.20 0.128667 0.200000 0.239230 0.343112 0.500000 0.002961 0.000030 0.239230 12.80 0.008000
PERIMETER_MID_ZN_3 VAV BOX COMPONENT 8.42 0.283510 0.275000 2.32 0.756026 0.500000 0.001344 0.001293 4.41 12.80 0.008000
PERIMETER_MID_ZN_2 VAV BOX COMPONENT 9.49 0.162210 0.200000 1.90 0.432560 0.500000 0.002349 0.000863 2.94 12.80 0.008000
PERIMETER_MID_ZN_1 VAV BOX COMPONENT 10.35 0.230798 0.224000 2.32 0.615461 0.500000 0.001651 0.001285 4.38 12.80 0.008000
PERIMETER_MID_ZN_4 VAV BOX COMPONENT 10.05 0.153077 0.200000 2.01 0.408207 0.500000 0.002489 0.000766 2.61 12.80 0.008000
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT 0.967470 0.246851 0.245000 0.237030 0.658268 0.500000 0.001543 0.000173 0.589819 12.80 0.008000
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT 0.969264 0.158786 0.200000 0.193853 0.423428 0.500000 0.002399 0.000114 0.389472 12.80 0.008000
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT 1.16 0.206721 0.205000 0.236838 0.551255 0.500000 0.001843 0.000172 0.586603 12.80 0.008000
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT 1.09 0.141130 0.200000 0.218104 0.376347 0.500000 0.002700 0.000107 0.364566 12.80 0.008000
User-Specified values were used. Design Size values were used if no User-Specified values were provided. Design Size values may be derived from alternate User-Specified values.

Coil:Heating:Water

Design Size Rated Capacity [W] Design Size Maximum Water Flow Rate [m3/s] Design Size U-Factor Times Area Value [W/K]
CORE_BOTTOM VAV BOX REHEAT COIL 19004.94 0.000166 383.12
CORE_MID VAV BOX REHEAT COIL 368521.24 0.003224 8236.55
CORE_TOP VAV BOX REHEAT COIL 61690.93 0.000540 1609.03
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 5654.10 0.000049 132.03
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4326.48 0.000038 100.36
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 7343.12 0.000064 187.12
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3453.00 0.000030 72.73
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 147829.41 0.001293 3900.55
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 98605.52 0.000863 2601.67
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 146866.25 0.001285 3875.16
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 87523.00 0.000766 2309.53
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 19765.21 0.000173 521.35
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 13050.70 0.000114 344.23
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 19657.69 0.000172 518.52
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 12217.78 0.000107 322.28
VAV_BOT WITH REHEAT HEATING COIL 26182.45 0.000229 452.91
VAV_MID WITH REHEAT HEATING COIL 246020.64 0.002152 4252.08
VAV_TOP WITH REHEAT HEATING COIL 23750.39 0.000208 412.95
CAV_BAS HEATING COIL 258285.90 0.002260 5860.88
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [m3/s] Sum of Air Terminal Minimum Heating Flow Rates [m3/s] Sum of Air Terminal Maximum Flow Rates [m3/s] Adjusted Heating Design Air Flow Rate [m3/s] Adjusted Cooling Design Air Flow Rate [m3/s] Adjusted Main Design Air Flow Rate [m3/s] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT 4.89 2.79 9.77 2.79 8.94 8.94 0.300000 0.311872 8.94
VAV_MID WITH REHEAT 45.56 26.97 91.11 26.97 82.72 82.72 0.300000 0.326035 82.72
VAV_TOP WITH REHEAT 4.71 2.77 9.41 3.74 8.94 8.94 0.300000 0.418601 8.94
CAV_BAS 5.48 5.48 5.48 5.48 5.48 5.48 1.00 1.00 5.48
AIRLOOP DATACENTER BASEMENT 21.33 21.33 21.33 21.33 21.33 21.33 1.00 0.999990 21.33
AIRLOOP DATACENTER BOT 0.465681 0.465681 0.465681 0.465681 0.465681 0.465681 1.00 1.00 0.465681
AIRLOOP DATACENTER MID 4.43 4.43 4.43 4.43 4.43 4.43 1.00 1.00 4.43
AIRLOOP DATACENTER TOP 0.451387 0.451387 0.451387 0.451387 0.451387 0.451387 1.00 1.00 0.451387
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:OutdoorAir

Maximum Outdoor Air Flow Rate [m3/s] Minimum Outdoor Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT_OA_CONTROLLER 8.94  
VAV_MID WITH REHEAT_OA_CONTROLLER 82.72  
VAV_TOP WITH REHEAT_OA_CONTROLLER 8.94  
CAV_BAS_OA_CONTROLLER 5.48 1.20
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER 21.33 0.338393
AIRLOOP DATACENTER BOT_OA_CONTROLLER 0.465681 0.015632
AIRLOOP DATACENTER MID_OA_CONTROLLER 4.43 0.156323
AIRLOOP DATACENTER TOP_OA_CONTROLLER 0.451387 0.015632
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

Design Size Nominal Supply Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT OA HEAT RECOVERY 2.54
VAV_MID WITH REHEAT OA HEAT RECOVERY 25.38
VAV_TOP WITH REHEAT OA HEAT RECOVERY 2.54
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:Water

Design Size Design Inlet Air Temperature [C] Design Size Design Inlet Water Temperature [C] Design Size Design Outlet Air Temperature [C] Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] Design Size Design Coil Load [W] Design Size Design Water Flow Rate [m3/s] Design Size Design Air Flow Rate [m3/s]
VAV_BOT WITH REHEAT COOLING COIL 26.93 6.67 11.05 0.011175 0.008500 247829.88 0.010543 8.94
VAV_MID WITH REHEAT COOLING COIL 27.29 6.67 11.05 0.011535 0.008500 2420734.69 0.102984 82.72
VAV_TOP WITH REHEAT COOLING COIL 26.82 6.67 11.05 0.011143 0.008500 245566.35 0.010447 8.94
CAV_BAS COOLING COIL 25.00 6.67 11.42 0.010624 0.008500 127008.98 0.005403 5.48
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:VariableVolume

Design Size Maximum Flow Rate [m3/s]
VAV_BOT WITH REHEAT FAN 8.94
VAV_MID WITH REHEAT FAN 82.72
VAV_TOP WITH REHEAT FAN 8.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Controller:WaterCoil

Maximum Actuated Flow [m3/s] Controller Convergence Tolerance
VAV_BOT WITH REHEAT_COOLC_CONTROLLER 0.010543 0.000045
VAV_BOT WITH REHEAT_HEATC_CONTROLLER 0.000229  
VAV_MID WITH REHEAT_COOLC_CONTROLLER 0.102984 0.000005
VAV_MID WITH REHEAT_HEATC_CONTROLLER 0.002152  
VAV_TOP WITH REHEAT_COOLC_CONTROLLER 0.010447 0.000046
VAV_TOP WITH REHEAT_HEATC_CONTROLLER 0.000208  
CAV_BAS_COOLC_CONTROLLER 0.005403 0.000088
CAV_BAS_HEATC_CONTROLLER 0.002260  
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:ConstantVolume

Design Size Maximum Flow Rate [m3/s]
CAV_BAS FAN 5.48
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Total Cooling Capacity [W] Design Size Rated Sensible Cooling Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT COOLING COIL 21.33 434337.82 312325.51 0.010637
AIRLOOP DATACENTER BOT COOLING COIL 0.465681 9501.30 6820.69 0.000233
AIRLOOP DATACENTER MID COOLING COIL 4.43 90544.49 64905.21 0.002217
AIRLOOP DATACENTER TOP COOLING COIL 0.451387 9227.99 6617.53 0.000226
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:WaterToAir

Supply Air Flow Rate [m3/s] Supply Air Flow Rate During Heating Operation [m3/s] Supply Air Flow Rate During Cooling Operation [m3/s] Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] Nominal Heating Capacity [W] Nominal Cooling Capacity [W] Supplemental Heating Coil Nominal Capacity [W] Fraction of Supply Air Flow That Goes Through the Controlling Zone
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP 21.33 21.33 21.33 21.33 434337.82 434337.82 14482.89 1.00
AIRLOOP DATACENTER BOT DXAC HEAT PUMP 0.465681 0.465681 0.465681 0.465681 9501.30 9501.30 669.05 1.00
AIRLOOP DATACENTER MID DXAC HEAT PUMP 4.43 4.43 4.43 4.43 90544.49 90544.49 6690.49 1.00
AIRLOOP DATACENTER TOP DXAC HEAT PUMP 0.451387 0.451387 0.451387 0.451387 9227.99 9227.99 669.05 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT SUPPLY FAN 21.33
AIRLOOP DATACENTER BOT SUPPLY FAN 0.465681
AIRLOOP DATACENTER MID SUPPLY FAN 4.43
AIRLOOP DATACENTER TOP SUPPLY FAN 0.451387
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT

Design Size Rated Air Flow Rate [m3/s] Design Size Rated Heating Capacity [W] Design Size Rated Water Flow Rate [m3/s]
AIRLOOP DATACENTER BASEMENT HEATING COIL 21.33 434337.82 0.010637
AIRLOOP DATACENTER BOT HEATING COIL 0.465681 9501.30 0.000233
AIRLOOP DATACENTER MID HEATING COIL 4.43 90544.49 0.002217
AIRLOOP DATACENTER TOP HEATING COIL 0.451387 9227.99 0.000226
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [W]
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL 14482.89
AIRLOOP DATACENTER BOT_SUPPHEATCOIL 669.05
AIRLOOP DATACENTER MID_SUPPHEATCOIL 6690.49
AIRLOOP DATACENTER TOP_SUPPHEATCOIL 669.05
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Humidifier:Steam:Electric

Design Size Nominal Capacity Volume [m3/s] User-Specified Nominal Capacity Volume [m3/s] Design Size Rated Power [W] User-Specified Rated Power [W]
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER 0.000080 0.000037 96450.70 100000.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W] Design Minimum Flow Rate [m3/s]
COOLSYS1 PUMP SECONDARY 0.129377 26659.83  
HEATSYS1 PUMP 0.013733 4135.73 0.000000
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [m3/s] Plant Loop Volume [m3]
COOLSYS1_DEMAND 0.129377 15.53
HEATSYS1 0.013733 1.65
COOLSYS1_SUPPLY 0.129377 15.53
SINGLE WATER PLANT LOOP 0.013313 1.60
SWHSYS1 0.000440 0.052800
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:FluidToFluid

Loop Supply Side Design Fluid Flow Rate [m3/s] Loop Demand Side Design Fluid Flow Rate [m3/s] Heat Exchanger U-Factor Times Area Value [W/C] Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C]
BYPASS HEAT EXCHANGER 0.129377 0.129377 543060.70 5.60
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [W] User-Specified Nominal Capacity [W] Design Size Design Water Flow Rate [m3/s]
HEATSYS1 BOILER 1569748.75 1569748.75 0.013733
CENTRAL BOILER 548382.01 537788.84 0.013313
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:ConstantSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
COOLSYS1 PUMP 0.129377 18457.50
PLANT CIRC PUMP 0.013313 3395.48
SWHSYS1 PUMP 0.000440 5.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Chiller:Electric:ReformulatedEIR

Design Size Reference Chilled Water Flow Rate [m3/s] User-Specified Reference Chilled Water Flow Rate [m3/s] Design Size Reference Capacity [W] User-Specified Reference Capacity [W] Design Size Reference Condenser Water Flow Rate [m3/s]
COOLSYS1 CHILLER1 0.129377 0.065210 1536592.25 1543939.29 0.076404
COOLSYS1 CHILLER2 0.129377 0.065210 1536592.25 1543939.29 0.076404
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

FluidCooler:TwoSpeed

Design Water Flow Rate [m3/s] Air Flow Rate at High Fan Speed [m3/s] Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] Air Flow Rate at Low Fan Speed [m3/s] Fan Power at Low Fan Speed [W] U-factor Times Area Value at Low Fan Speed [W/C]
CENTRAL TOWER 0.013313 139666.47 59194.70 69833.23 7879.72 21407.40
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Use Side Design Flow Rate [m3/s]
SWHSYS1 WATER HEATER 0.000440
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CondenserLoop

Maximum Loop Flow Rate [m3/s] Condenser Loop Volume [m3]
TOWERWATERSYS 0.152808 18.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeaderedPumps:VariableSpeed

Design Flow Rate [m3/s] Design Power Consumption [W]
TOWERWATERSYS PUMP 0.152808 46022.34
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

CoolingTower:VariableSpeed

Design Air Flow Rate [m3/s] Nominal Capacity [W] Air Flow Rate in free convection regime [m3/s] Tower capacity in free convection regime at design conditions [W]
TOWERWATERSYS COOLTOWER 1 58.79 1831858.06 11.76 228982.26
TOWERWATERSYS COOLTOWER 2 58.79 1831858.06 11.76 228982.26
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantEquipmentOperation:ComponentSetPoint

Design Water Flow Rate [m3/s] Equipment # 47
WSHPPLANT OPERATION SCHEME 0.079360
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

None


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
PERIMETER_BOT_ZN_3_WALL_NORTH PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 |
PERIMETER_BOT_ZN_2_WALL_EAST PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 |
PERIMETER_BOT_ZN_1_WALL_SOUTH PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 |
PERIMETER_BOT_ZN_4_WALL_WEST PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 |
PERIMETER_MID_ZN_3_WALL_NORTH PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_MID_ZN_2_WALL_EAST PERIMETER_MID_ZN_2_WALL_EAST_WINDOW |
PERIMETER_MID_ZN_1_WALL_SOUTH PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_MID_ZN_4_WALL_WEST PERIMETER_MID_ZN_4_WALL_WEST_WINDOW |
PERIMETER_TOP_ZN_3_WALL_NORTH PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW |
PERIMETER_TOP_ZN_2_WALL_EAST PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW |
PERIMETER_TOP_ZN_1_WALL_SOUTH PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW |
PERIMETER_TOP_ZN_4_WALL_WEST PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Version

Version ID
1 22.1.0


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes Yes No Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.556 0.556


Site:GroundTemperature:BuildingSurface

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00 18.00


Site:GroundTemperature:FCfactorMethod

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 24.20 18.90 15.70 13.60 15.50 17.10 21.20 26.90 27.60 27.90 27.40 26.20


Site:GroundTemperature:Shallow

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00 13.00


Site:GroundTemperature:Deep

Jan{C} Feb{C} Mar{C} Apr{C} May{C} Jun{C} Jul{C} Aug{C} Sep{C} Oct{C} Nov{C} Dec{C}
1 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00 16.00


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {m} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Sensor Height Above Ground {m} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 10.000 0.140 270.000 1.500 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {m} Standard Pressure at Elevation {Pa} Standard RhoAir at Elevation
1 Tampa-MacDill AFB FL USA TMY3 WMO#=747880 27.85 -82.52 -5.00 8.00 101229 1.2032


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{C} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} Fixed Default Water Mains Temperature{C}
1 Correlation NA 21.85 14.30 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 OfficeLarge 0.000 City 4.00000E-002 0.20000 FullInteriorAndExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 TARP


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Value {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
1 ThirdOrderBackwardDifference


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {m} Air Temperature Gradient Coefficient {K/m}
1 0.330 460.000 6.500000E-003


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 UpperLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{C}


Surface Convection Coefficient Lower Limit {W/m2-K}


Surface Convection Coefficient Upper Limit {W/m2-K}


1 CTF - ConductionTransferFunction 200 0.10 1000.0


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 0


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 23 221 36


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {m} Origin Y-Coordinate {m} Origin Z-Coordinate {m} Centroid X-Coordinate {m} Centroid Y-Coordinate {m} Centroid Z-Coordinate {m} Type Zone Multiplier Zone List Multiplier Minimum X {m} Maximum X {m} Minimum Y {m} Maximum Y {m} Minimum Z {m} Maximum Z {m} Ceiling Height {m} Volume {m3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {m2} Exterior Gross Wall Area {m2} Exterior Net Wall Area {m2} Exterior Window Area {m2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BASEMENT 0.0 0.00 0.00 0.00 44.59 24.37 -1.22 1 1 1 16.08 73.11 0.00 48.74 -2.44 0.00 2.44 6779.02 TARP TARP 2779.43 0.00 0.00 0.00 9 0 0 Yes
2 CORE_BOTTOM 0.0 0.00 0.00 0.00 37.01 24.37 1.37 1 1 1 5.49 68.53 4.57 44.17 0.00 2.74 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 7 0 0 Yes
3 CORE_MID 0.0 0.00 0.00 0.00 37.01 24.37 18.14 1 10 1 5.49 68.53 4.57 44.17 16.77 19.51 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
4 CORE_TOP 0.0 0.00 0.00 0.00 37.01 24.37 34.91 1 1 1 5.49 68.53 4.57 44.17 33.54 36.28 2.74 6849.35 TARP TARP 2496.12 0.00 0.00 0.00 6 0 0 Yes
5 PERIMETER_BOT_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 1.37 1 1 1 0.00 73.11 44.17 48.74 0.00 2.74 2.74 860.00 TARP TARP 313.41 200.61 105.88 86.92 8 9 0 Yes
6 PERIMETER_BOT_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 1.37 1 1 1 68.53 73.11 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
7 PERIMETER_BOT_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 1.37 1 1 1 0.00 73.11 0.00 4.57 0.00 2.74 2.74 860.02 TARP TARP 313.42 200.61 105.88 86.92 8 9 0 Yes
8 PERIMETER_BOT_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 1.37 1 1 1 0.00 4.57 0.00 48.74 0.00 2.74 2.74 554.22 TARP TARP 201.98 133.74 71.89 57.95 6 5 0 Yes
9 PERIMETER_MID_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 18.14 1 10 1 0.00 73.11 44.17 48.74 16.77 19.51 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
10 PERIMETER_MID_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 18.14 1 10 1 68.53 73.11 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
11 PERIMETER_MID_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 18.14 1 10 1 0.00 73.11 0.00 4.57 16.77 19.51 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
12 PERIMETER_MID_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 18.14 1 10 1 0.00 4.57 0.00 48.74 16.77 19.51 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
13 PERIMETER_TOP_ZN_3 0.0 0.00 0.00 0.00 36.55 46.54 34.91 1 1 1 0.00 73.11 44.17 48.74 33.54 36.28 2.74 860.00 TARP TARP 313.41 200.61 113.68 86.92 7 1 0 Yes
14 PERIMETER_TOP_ZN_2 0.0 0.00 0.00 0.00 70.95 24.37 34.91 1 1 1 68.53 73.11 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
15 PERIMETER_TOP_ZN_1 0.0 0.00 0.00 0.00 36.55 2.20 34.91 1 1 1 0.00 73.11 0.00 4.57 33.54 36.28 2.74 860.02 TARP TARP 313.42 200.61 113.68 86.92 7 1 0 Yes
16 PERIMETER_TOP_ZN_4 0.0 0.00 0.00 0.00 2.16 24.37 34.91 1 1 1 0.00 4.57 0.00 48.74 33.54 36.28 2.74 554.22 TARP TARP 201.98 133.74 75.79 57.95 6 1 0 Yes
17 GROUNDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 3.35 1 1 1 0.00 73.11 0.00 48.74 2.74 3.96 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
18 MIDFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 20.12 1 10 1 0.00 73.11 0.00 48.74 19.51 20.73 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
19 TOPFLOOR_PLENUM 0.0 0.00 0.00 0.00 36.55 24.37 36.89 1 1 1 0.00 73.11 0.00 48.74 36.28 37.50 1.22 4344.14 TARP TARP 3563.11 297.11 297.11 0.00 11 0 0 No
20 DATACENTER_BOT_ZN_6 0.0 5.49 44.17 0.00 5.03 24.37 1.37 1 1 1 4.57 5.49 4.57 44.17 0.00 2.74 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
21 DATACENTER_MID_ZN_6 0.0 4.57 4.57 16.77 5.03 24.37 18.14 1 10 1 4.57 5.49 4.57 44.17 16.77 19.51 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
22 DATACENTER_TOP_ZN_6 0.0 4.57 4.57 33.54 5.03 24.37 34.91 1 1 1 4.57 5.49 4.57 44.17 33.54 36.28 2.74 99.34 TARP TARP 36.20 0.00 0.00 0.00 6 0 0 Yes
23 DATACENTER_BASEMENT_ZN_6 0.0 16.08 0.00 -2.44 8.04 24.37 -1.22 1 1 1 0.00 16.08 0.00 48.74 -2.44 0.00 2.44 1911.37 TARP TARP 783.68 0.00 0.00 0.00 10 0 0 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {m2} # Occupants Area per Occupant {m2/person} Occupant per Area {person/m2} Interior Lighting {W/m2} Electric Load {W/m2} Gas Load {W/m2} Other Load {W/m2} Hot Water Eq {W/m2} Steam Equipment {W/m2} Sum Loads per Area {W/m2} Outdoor Controlled Baseboard Heat
1 BASEMENT 2779.43 149.6 18.579 5.382E-002 7.620 4.842 0.000 0.000 0.000 0.000 12.462 No
2 CORE_BOTTOM 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
3 CORE_MID 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
4 CORE_TOP 2496.12 134.4 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
5 PERIMETER_BOT_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
6 PERIMETER_BOT_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
7 PERIMETER_BOT_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
8 PERIMETER_BOT_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
9 PERIMETER_MID_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
10 PERIMETER_MID_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
11 PERIMETER_MID_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
12 PERIMETER_MID_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
13 PERIMETER_TOP_ZN_3 313.41 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
14 PERIMETER_TOP_ZN_2 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
15 PERIMETER_TOP_ZN_1 313.42 16.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
16 PERIMETER_TOP_ZN_4 201.98 10.9 18.579 5.382E-002 7.620 8.070 0.000 0.000 0.000 0.000 15.690 No
17 GROUNDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
18 MIDFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
19 TOPFLOOR_PLENUM 3563.11 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
20 DATACENTER_BOT_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
21 DATACENTER_MID_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
22 DATACENTER_TOP_ZN_6 36.20 1.9 18.579 5.382E-002 12.511 215.299 0.000 0.000 0.000 0.000 227.811 No
23 DATACENTER_BASEMENT_ZN_6 783.68 42.2 18.579 5.382E-002 7.620 484.423 0.000 0.000 0.000 0.000 492.043 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Number of People {} People/Floor Area {person/m2} Floor Area per person {m2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People MRT Calculation Type Work Efficiency Clothing Insulation Calculation Method Clothing Insulation Calculation Method Schedule Clothing Air Velocity Fanger Calculation Pierce Calculation KSU Calculation Cooling Effect Calculation Ankle Draft Calculation
1 DATACENTER_BOT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BOT_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
2 DATACENTER_MID_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_MID_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
3 DATACENTER_TOP_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_TOP_ZN_6 36.20 1.9 1.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
4 DATACENTER_BASEMENT_ZN_6 BLDG_OCC_SCH_WO_SB DATACENTER_BASEMENT_ZN_6 783.68 42.2 42.2 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 42 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
5 BASEMENT BLDG_OCC_SCH_WO_SB BASEMENT 2779.43 149.6 149.6 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 150 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
6 CORE_BOTTOM BLDG_OCC_SCH_WO_SB CORE_BOTTOM 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
7 CORE_MID BLDG_OCC_SCH_WO_SB CORE_MID 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
8 CORE_TOP BLDG_OCC_SCH_WO_SB CORE_TOP 2496.12 134.4 134.4 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 134 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
9 PERIMETER_BOT_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
10 PERIMETER_BOT_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
11 PERIMETER_BOT_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
12 PERIMETER_BOT_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_BOT_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
13 PERIMETER_MID_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
14 PERIMETER_MID_ZN_2 BLDG_OCC_SCH_W_SB PERIMETER_MID_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
15 PERIMETER_MID_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
16 PERIMETER_MID_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_MID_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
17 PERIMETER_TOP_ZN_3 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_3 313.41 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
18 PERIMETER_TOP_ZN_2 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_2 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
19 PERIMETER_TOP_ZN_1 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_1 313.42 16.9 16.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 17 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No
20 PERIMETER_TOP_ZN_4 BLDG_OCC_SCH_WO_SB PERIMETER_TOP_ZN_4 201.98 10.9 10.9 5.382E-002 18.579 0.300 0.700 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 11 Zone Averaged WORK_EFF_SCH Clothing Insulation Schedule N/A CLOTHING_SCH AIR_VELO_SCH Yes No No No No


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Lighting Level {W} Lights/Floor Area {W/m2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {W} Nominal Maximum Lighting Level {W}
1 BASEMENT_LIGHTS LTG_SCH_OFFICE BASEMENT 2779.43 149.6 21179.739 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 21179.739
2 CORE_BOTTOM_LIGHTS LTG_SCH_OFFICE CORE_BOTTOM 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
3 CORE_MID_LIGHTS LTG_SCH_OFFICE CORE_MID 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
4 CORE_TOP_LIGHTS LTG_SCH_OFFICE CORE_TOP 2496.12 134.4 19020.895 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 19020.895
5 PERIMETER_BOT_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
6 PERIMETER_BOT_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
7 PERIMETER_BOT_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
8 PERIMETER_BOT_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_BOT_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
9 PERIMETER_MID_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
10 PERIMETER_MID_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
11 PERIMETER_MID_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
12 PERIMETER_MID_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_MID_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
13 PERIMETER_TOP_ZN_3_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_3 313.41 16.9 2388.263 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.263
14 PERIMETER_TOP_ZN_2_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_2 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
15 PERIMETER_TOP_ZN_1_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_1 313.42 16.9 2388.315 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 2388.315
16 PERIMETER_TOP_ZN_4_LIGHTS LTG_SCH_OFFICE PERIMETER_TOP_ZN_4 201.98 10.9 1539.088 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 1539.088
17 DATACENTER_BASEMENT_LIGHTS LTG_SCH_OFFICE DATACENTER_BASEMENT_ZN_6 783.68 42.2 5971.780 7.620 141.574 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 5971.780
18 DATACENTER_BOT_LIGHTS LTG_SCH_DATACENTER DATACENTER_BOT_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
19 DATACENTER_MID_LIGHTS LTG_SCH_DATACENTER DATACENTER_MID_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948
20 DATACENTER_TOP_LIGHTS LTG_SCH_DATACENTER DATACENTER_TOP_ZN_6 36.20 1.9 452.948 12.511 232.447 0.000 0.700 0.200 0.100 1.000 LightsWired 0.000 452.948


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Equipment Level {W} Equipment/Floor Area {W/m2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {W} Nominal Maximum Equipment Level {W}
1 BASEMENT_MISCPLUG_EQUIP ALWAYS_ON BASEMENT 2779.43 149.6 13457.544 4.842 89.956 0.000 0.500 0.000 0.500 MiscPlug 13457.544 13457.544
2 CORE_BOTTOM_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_BOTTOM 2496.12 134.4 20142.877 8.070 149.925 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.877
3 CORE_MID_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_MID 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
4 CORE_TOP_MISCPLUG_EQUIP BLDG_EQUIP_SCH CORE_TOP 2496.12 134.4 20142.800 8.070 149.924 0.000 0.500 0.000 0.500 MiscPlug 0.000 20142.800
5 PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
6 PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
7 PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
8 PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_BOT_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
9 PERIMETER_MID_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
10 PERIMETER_MID_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
11 PERIMETER_MID_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
12 PERIMETER_MID_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_MID_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
13 PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_3 313.41 16.9 2529.242 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.242
14 PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_2 201.98 10.9 1629.940 8.070 149.931 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.940
15 PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_1 313.42 16.9 2529.281 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 2529.281
16 PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP BLDG_EQUIP_SCH PERIMETER_TOP_ZN_4 201.98 10.9 1629.929 8.070 149.930 0.000 0.500 0.000 0.500 MiscPlug 0.000 1629.929
17 DATACENTER_BASEMENT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BASEMENT_ZN_6 783.68 42.2 379632.522 484.423 9000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 94908.130 379632.522
18 DATACENTER_BOT_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_BOT_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
19 DATACENTER_MID_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_MID_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422
20 DATACENTER_TOP_MISCPLUG_EQUIP DATACENTER_EQUIP_SCH DATACENTER_TOP_ZN_6 36.20 1.9 7794.422 215.299 4000.000 0.000 0.100 0.000 0.900 DataCenterPlugLoads 1948.606 7794.422


Construction CTF

Construction Name Index #Layers #CTFs Time Step {hours} ThermalConductance {w/m2-K} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 SWINGING DOOR_CON 1 1 1 0.167 3.464 0.900 0.900 0.700 0.700 MediumRough
2 INTERIORFURNISHINGS 2 1 9 0.167 0.8000 0.900 0.900 0.700 0.700 MediumSmooth
3 DROPCEILING 4 1 3 0.167 4.488 0.900 0.900 0.700 0.700 MediumSmooth
4 INT_WALL 7 2 4 0.167 6.299 0.900 0.900 0.700 0.700 Smooth
5 EXT_SLAB_8IN_WITH_CARPET 8 2 7 0.167 3.285 0.900 0.900 0.700 0.700 MediumRough
6 INT_SLAB_FLOOR 12 2 7 0.167 3.839 0.900 0.900 0.700 0.700 MediumRough
7 INT_SLAB_CEILING 13 2 7 0.167 3.839 0.900 0.900 0.700 0.700 VeryRough
8 NONRES_ROOF 17 3 3 0.167 0.2284 0.750 0.900 0.450 0.700 Rough
9 NONRES_EXT_WALL_GRD 20 3 9 0.167 1.743 0.900 0.900 0.700 0.700 MediumRough
10 NONRES_EXT_WALL_MID 21 3 9 0.167 1.656 0.900 0.900 0.700 0.700 MediumRough
11 NONRES_EXT_WALL_TOP 22 3 9 0.167 2.135 0.900 0.900 0.700 0.700 MediumRough
12 BASEMENT_WALL_EAST_CFACTOR 39 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
13 BASEMENT_WALL_SOUTH_CFACTOR 40 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
14 BASEMENT_WALL_NORTH_CFACTOR 41 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
15 DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 42 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
16 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 43 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough
17 DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 44 2 7 0.167 0.9401 0.000 0.900 0.000 0.700 MediumRough


Material CTF Summary

Material Name Thickness {m} Conductivity {w/m-K} Density {kg/m3} Specific Heat {J/kg-K} ThermalResistance {m2-K/w}
1 OPAQUE DOOR PANEL_CON 0.0000 0.000 0.000 0.000 0.2887
2 STD WOOD 6INCH 0.1500 0.120 540.000 1210.000 1.250
3 AC02 ACOUSTIC CEILING 0.0127 0.057 288.000 1339.000 0.2228
4 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
5 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
6 200MM NORMALWEIGHT CONCRETE FLOOR 0.2032 2.310 2322.000 832.000 0.8797E-01
7 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
8 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
9 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
10 CP02 CARPET PAD 0.0000 0.000 0.000 0.000 0.2165
11 100MM NORMALWEIGHT CONCRETE FLOOR 0.1016 2.310 2322.000 832.000 0.4398E-01
12 F13 BUILT-UP ROOFING 0.0095 0.160 1120.000 1460.000 0.5938E-01
13 NONRES_ROOF_INSULATION 0.0000 0.000 0.000 0.000 4.319
14 F08 METAL SURFACE 0.0008 45.280 7824.000 500.000 0.1767E-04
15 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
16 NONRES_EXTERIOR_WALL_INSULATION_GRD 0.0000 0.000 0.000 0.000 0.4064
17 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
18 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
19 NONRES_EXTERIOR_WALL_INSULATION_MID 0.0000 0.000 0.000 0.000 0.4365
20 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
21 200MM NORMALWEIGHT CONCRETE WALL 0.2032 2.310 2322.000 832.000 0.8797E-01
22 NONRES_EXTERIOR_WALL_INSULATION_TOP 0.0000 0.000 0.000 0.000 0.3009
23 G01 13MM GYPSUM BOARD 0.0127 0.160 800.000 1090.000 0.7937E-01
24 ~FC_Insulation_1 0.0000 0.000 0.000 0.000 0.9868
25 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
26 ~FC_Insulation_2 0.0000 0.000 0.000 0.000 0.9868
27 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
28 ~FC_Insulation_3 0.0000 0.000 0.000 0.000 0.9868
29 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
30 ~FC_Insulation_4 0.0000 0.000 0.000 0.000 0.9868
31 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
32 ~FC_Insulation_5 0.0000 0.000 0.000 0.000 0.9868
33 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01
34 ~FC_Insulation_6 0.0000 0.000 0.000 0.000 0.9868
35 ~FC_Concrete 0.1500 1.950 2240.000 900.000 0.7692E-01


CTF

Time Outside Cross Inside Flux (except final one)
1 1 0.0000000 0.0000000 -0.0000000 -0.0000000
2 0 3.4637404 3.4637404 3.4637404  
3 9 -0.27580628E-02 0.97439125E-12 -0.27580628E-02 0.28516790E-03
4 8 0.73590997E-01 0.21837543E-08 0.73590997E-01 -0.77836043E-02
5 7 -0.82599318 0.23162835E-06 -0.82599318 0.89703933E-01
6 6 5.1113916 0.48671053E-05 5.1113916 -0.57224845
7 5 -19.214933 0.30163627E-04 -19.214933 2.2266322
8 4 45.557404 0.63181060E-04 45.557404 -5.4853312
9 3 -68.275533 0.44785456E-04 -68.275533 8.5710568
10 2 62.555368 0.93952058E-05 62.555368 -8.2111738
11 1 -31.904423 0.39200004E-06 -31.904423 4.3886678
12 0 6.9260389 0.77047546E-09 6.9260389  
13 3 -0.21589802E-09 0.15643069E-09 -0.21589802E-09 0.12999471E-21
14 2 0.50772448E-02 0.30006816E-02 0.50772448E-02 -0.13693132E-08
15 1 -2.5944910 1.4597758 -2.5944910 0.76344767E-02
16 0 7.0433378 2.9911476 7.0433378  
17 4 0.68458728E-09 0.26079551E-09 0.68458728E-09 -0.34507121E-18
18 3 -0.72180374E-03 0.24295686E-03 -0.72180374E-03 0.69691454E-09
19 2 0.83054762 0.27682775 0.83054762 -0.35168967E-03
20 1 -12.650482 3.3590720 -12.650482 0.19281313
21 0 16.907513 1.4507143 16.907513  
22 7 -0.18651654E-16 -0.16428647E-15 -0.26578847E-08 -0.25364002E-17
23 6 0.67402962E-01 0.99142722E-07 0.38101547E-02 -0.76639482E-03
24 5 -1.8580732 0.49502125E-04 -0.10651409 0.21891119E-01
25 4 18.220105 0.12801333E-02 1.0775450 -0.22586539
26 3 -79.928293 0.66708484E-02 -4.9803755 1.0625663
27 2 166.43177 0.75131194E-02 11.128837 -2.4125483
28 1 -159.97298 0.18548900E-02 -11.587784 2.5494418
29 0 57.057412 0.52755123E-04 4.4818272  
30 7 0.43260499E-16 0.34524919E-16 0.52793240E-17 0.0000000
31 6 0.69434179E-09 0.98085174E-11 0.18162501E-10 -0.40870994E-12
32 5 -0.12888762E-04 0.28373718E-06 -0.16918523E-06 0.92361873E-08
33 4 0.25174112E-01 0.33697681E-03 0.22646198E-03 -0.31467795E-04
34 3 -3.7600775 0.27170599E-01 -0.48495626E-01 0.94171705E-02
35 2 51.553741 0.22121684 1.2284947 -0.25833933
36 1 -128.86110 0.21944682 -5.1479470 1.1228340
37 0 81.526494 0.16043334E-01 4.4519351  
38 7 0.52793240E-17 0.34524919E-16 0.43260499E-16 0.0000000
39 6 0.18162501E-10 0.98085174E-11 0.69434179E-09 -0.40870994E-12
40 5 -0.16918523E-06 0.28373718E-06 -0.12888762E-04 0.92361873E-08
41 4 0.22646198E-03 0.33697681E-03 0.25174112E-01 -0.31467795E-04
42 3 -0.48495626E-01 0.27170599E-01 -3.7600775 0.94171705E-02
43 2 1.2284947 0.22121684 51.553741 -0.25833933
44 1 -5.1479470 0.21944682 -128.86110 1.1228340
45 0 4.4519351 0.16043334E-01 81.526494  
46 3 -0.62451068E-06 0.10350887E-08 -0.38276125E-05 0.11995084E-16
47 2 0.77976586 0.13989883E-02 1.0579789 -0.73382352E-06
48 1 -21.958702 0.93426804E-01 -6.3215779 0.20283230
49 0 21.361010 0.87247630E-01 5.4456762  
50 9 0.76055735E-15 0.55973061E-16 -0.11090261E-09 -0.43371185E-17
51 8 0.16390423E-07 0.22068143E-12 0.31740643E-03 -0.18636477E-09
52 7 -0.10429999E-01 0.12271718E-07 -0.20474149E-01 0.11859286E-03
53 6 0.35611320 0.43955117E-05 0.42991281 -0.41673803E-02
54 5 -4.7098961 0.16827687E-03 -4.1162358 0.57223947E-01
55 4 30.875684 0.14076848E-02 20.167480 -0.39388153
56 3 -106.69740 0.31291265E-02 -53.106522 1.4497707
57 2 192.63914 0.17911574E-02 75.570394 -2.8293896
58 1 -169.50392 0.19431750E-03 -54.592911 2.7164834
59 0 57.057407 0.11257899E-05 15.674734  
60 9 0.11474244E-14 0.54197419E-16 -0.11508650E-09 -0.49945851E-17
61 8 0.16984416E-07 0.21156325E-12 0.32425024E-03 -0.19311866E-09
62 7 -0.10636353E-01 0.11664670E-07 -0.20772028E-01 0.12093918E-03
63 6 0.36172330 0.41637772E-05 0.43474562 -0.42335086E-02
64 5 -4.7646824 0.15893927E-03 -4.1535939 0.57903236E-01
65 4 31.118254 0.13261305E-02 20.314042 -0.39710182
66 3 -107.21418 0.29411649E-02 -53.396504 1.4572354
67 2 193.15212 0.16802168E-02 75.835339 -2.8375342
68 1 -169.69371 0.18194848E-03 -54.668081 2.7198097
69 0 57.057407 0.10520719E-05 15.660794  
70 9 0.66246833E-15 0.57738042E-16 -0.92036509E-10 -0.27018983E-17
71 8 0.13701644E-07 0.25726543E-12 0.28527343E-03 -0.15579243E-09
72 7 -0.94571194E-02 0.14940887E-07 -0.19068097E-01 0.10753086E-03
73 6 0.32965778 0.54453531E-05 0.40701455 -0.38555430E-02
74 5 -4.4514676 0.21157254E-03 -3.9387765 0.54019785E-01
75 4 29.731016 0.17930056E-02 19.470280 -0.37868589
76 3 -104.25747 0.40308508E-02 -51.726693 1.4145289
77 2 190.21562 0.23301583E-02 74.311741 -2.7909129
78 1 -168.60668 0.25508611E-03 -54.239505 2.7007581
79 0 57.057407 0.14924561E-05 15.743350  
80 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
81 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
82 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
83 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
84 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
85 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
86 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
87 0 1.0055995 0.48413807E-04 60.838472  
88 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
89 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
90 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
91 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
92 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
93 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
94 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
95 0 1.0055995 0.48413807E-04 60.838472  
96 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
97 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
98 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
99 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
100 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
101 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
102 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
103 0 1.0055995 0.48413807E-04 60.838472  
104 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
105 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
106 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
107 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
108 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
109 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
110 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
111 0 1.0055995 0.48413807E-04 60.838472  
112 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
113 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
114 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
115 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
116 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
117 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
118 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
119 0 1.0055995 0.48413807E-04 60.838472  
120 7 -0.41493644E-09 0.26375357E-16 0.26213203E-14 -0.63268016E-17
121 6 0.27465604E-04 0.18700671E-07 0.31288692E-02 -0.26247577E-04
122 5 -0.19935291E-02 0.11146933E-04 -0.22025565 0.19255324E-02
123 4 0.45890804E-01 0.50864553E-03 4.7717348 -0.44709298E-01
124 3 -0.40280019 0.40571884E-02 -37.694667 0.39504237
125 2 1.4296488 0.67623010E-02 115.84777 -1.4094303
126 1 -2.0629154 0.20697549E-02 -143.53273 2.0428830
127 0 1.0055995 0.48413807E-04 60.838472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {W/m2-K} Conductance (Before Adjusted) {W/m2-K} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 WINDOW_U_0.5047_SHGC_EAST_0.25 35 1 VerySmooth 2.869 2.869 1.000 0.251    
2 WINDOW_U_0.5047_SHGC_SOUTH_0.25 36 1 VerySmooth 2.869 2.869 1.000 0.251    
3 WINDOW_U_0.5047_SHGC_WEST_0.25 37 1 VerySmooth 2.869 2.869 1.000 0.251    
4 WINDOW_U_0.5047_SHGC_NORTH_0.25 38 1 VerySmooth 2.869 2.869 1.000 0.251    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {m} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLAZING LAYER EAST SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
2 GLAZING LAYER SOUTH SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
3 GLAZING LAYER WEST SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No
4 GLAZING LAYER NORTH SpectralAverage   1.90891E-002 0.16139 0.61055 0.61055 0.25000 0.16143 0.23877 0.00000 0.84000 0.84000 0.10708 1.00000 No


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 30 15000 SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Enclosure/Window Adjacency Daylighting Counts

Enclosure Name Number of Exterior Windows Number of Exterior Windows in Adjacent Enclosures
1 PERIMETER_BOT_ZN_3 5 0
2 PERIMETER_BOT_ZN_2 3 0
3 PERIMETER_BOT_ZN_1 5 0
4 PERIMETER_BOT_ZN_4 3 0
5 PERIMETER_MID_ZN_3 1 0
6 PERIMETER_MID_ZN_2 1 0
7 PERIMETER_MID_ZN_1 1 0
8 PERIMETER_MID_ZN_4 1 0
9 PERIMETER_TOP_ZN_3 1 0
10 PERIMETER_TOP_ZN_2 1 0
11 PERIMETER_TOP_ZN_1 1 0
12 PERIMETER_TOP_ZN_4 1 0


Enclosure/Window Adjacency Daylighting Matrix

Enclosure Name Number of Adjacent Enclosures with Windows Adjacent Enclosure Names - 1st 100 (max)
1 PERIMETER_BOT_ZN_3 0  
2 PERIMETER_BOT_ZN_2 0  
3 PERIMETER_BOT_ZN_1 0  
4 PERIMETER_BOT_ZN_4 0  
5 PERIMETER_MID_ZN_3 0  
6 PERIMETER_MID_ZN_2 0  
7 PERIMETER_MID_ZN_1 0  
8 PERIMETER_MID_ZN_4 0  
9 PERIMETER_TOP_ZN_3 0  
10 PERIMETER_TOP_ZN_2 0  
11 PERIMETER_TOP_ZN_1 0  
12 PERIMETER_TOP_ZN_4 0  


Water Heater Information

Type Name Volume {m3} Maximum Capacity {W} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed SWHSYS1 WATER HEATER 1.1356 87921.3 0.496 7.5104E-002


Surface Convection Parameters

Surface Name Outside Model Assignment Outside Area [m2] Outside Perimeter [m] Outside Height [m] Inside Model Assignment Inside Height [m] Inside Perimeter Envelope [m] Inside Hydraulic Diameter [m] Window Wall Ratio Window Location Near Radiant {Yes/No} Has Active HVAC {Yes/No}
1 BASEMENT_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
2 BASEMENT_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
3 BASEMENT_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
4 BASEMENT_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
5 BASEMENT_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
10 BASEMENT_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.44 0.00 52.56 -999.00 0 No No
11 CORE_BOT_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
12 CORE_BOT_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
13 CORE_BOT_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
14 CORE_BOT_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
16 CORE_BOT_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
17 CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
18 CORE_BOTTOM_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
19 CORE_MID_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
20 CORE_MID_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
21 CORE_MID_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
22 CORE_MID_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
23 CORE_MID_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
24 CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
25 CORE_MID_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
26 CORE_TOP_ZN_5_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
27 CORE_TOP_ZN_5_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
28 CORE_TOP_ZN_5_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
29 CORE_TOP_ZN_5_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
30 CORE_TOP_ZN_5_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
31 CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
32 CORE_TOP_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 0.00 48.64 -999.00 0 No No
33 PERIMETER_BOT_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 0 No No
43 PERIMETER_BOT_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
47 PERIMETER_BOT_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
49 PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
51 PERIMETER_BOT_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 0 No No
57 PERIMETER_BOT_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
60 PERIMETER_BOT_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
61 PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
63 PERIMETER_BOT_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 0 No No
73 PERIMETER_BOT_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
78 PERIMETER_BOT_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
79 PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
81 PERIMETER_BOT_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 0 No No
87 PERIMETER_BOT_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
90 PERIMETER_BOT_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
91 PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
93 PERIMETER_MID_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
95 PERIMETER_MID_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
99 PERIMETER_MID_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
100 PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
102 PERIMETER_MID_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
104 PERIMETER_MID_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
107 PERIMETER_MID_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
108 PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
110 PERIMETER_MID_ZN_1_WALL_EAST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
111 PERIMETER_MID_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
116 PERIMETER_MID_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
117 PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
119 PERIMETER_MID_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
121 PERIMETER_MID_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
124 PERIMETER_MID_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
125 PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
127 PERIMETER_TOP_ZN_3_WALL_NORTH 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 3 No No
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0 869.22 250.73 37.50 0 2.74 73.11 8.07 0.43 2 No No
129 PERIMETER_TOP_ZN_3_WALL_WEST 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
133 PERIMETER_TOP_ZN_3_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
134 PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
136 PERIMETER_TOP_ZN_2_WALL_EAST 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 3 No No
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 0 579.48 250.73 37.50 0 2.74 48.74 7.58 0.43 2 No No
138 PERIMETER_TOP_ZN_2_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
140 INT-PER3S-NE-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
141 PERIMETER_TOP_ZN_2_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
142 PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
144 PERIMETER_TOP_ZN_1_WALL_SOUTH 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 3 No No
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 0 869.22 221.21 37.50 0 2.74 73.11 8.07 0.43 2 No No
146 INT-PER3S-NE 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
150 PERIMETER_TOP_ZN_1_FLOOR 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
151 PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 73.11 8.07 0.43 0 No No
153 PERIMETER_TOP_ZN_4_WALL_WEST 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 3 No No
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0 579.48 172.48 37.50 0 2.74 48.74 7.58 0.43 2 No No
155 PERIMETER_TOP_ZN_4_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
158 PERIMETER_TOP_ZN_4_FLOOR 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
159 PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 0 0.00 0.00 0.00 0 2.74 48.74 7.58 0.43 0 No No
161 GROUNDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
162 GROUNDFLOOR_PLENUM_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
163 GROUNDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
164 GROUNDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
165 iz-CORE_BOT_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
166 iz-PERIMETER_BOT_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
167 iz-PERIMETER_BOT_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
168 iz-PERIMETER_BOT_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
169 iz-PERIMETER_BOT_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
170 iz-DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
171 GROUNDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
172 MIDFLOOR_PLENUM_WALL_NORTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
173 MIDFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
174 MIDFLOOR_PLENUM_WALL_SOUTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
175 MIDFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
176 iz-CORE_MID_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
177 iz-PERIMETER_MID_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
178 iz-PERIMETER_MID_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
179 iz-PERIMETER_MID_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
180 iz-PERIMETER_MID_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
181 iz-DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
182 MIDFLOOR_PLENUM_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
183 TOPFLOOR_PLENUM_WALL_NORTH 0 869.22 221.21 37.50 0 1.22 243.69 58.49 0.00 0 No No
184 TOPFLOOR_PLENUM_WALL_EAST 0 579.48 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
185 TOPFLOOR_PLENUM_WALL_WEST 0 579.48 172.48 37.50 0 1.22 243.69 58.49 0.00 0 No No
186 TOPFLOOR_PLENUM_WALL_SOUTH 0 869.22 250.73 37.50 0 1.22 243.69 58.49 0.00 0 No No
187 iz-CORE_TOP_ZN_5_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
188 iz-PERIMETER_TOP_ZN_3_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
189 iz-PERIMETER_TOP_ZN_2_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
190 iz-PERIMETER_TOP_ZN_1_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
191 iz-PERIMETER_TOP_ZN_4_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
192 iz-DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 1.22 243.69 58.49 0.00 0 No No
193 BUILDING_ROOF 0 3563.11 268.06 0.00 0 1.22 243.69 58.49 0.00 0 No No
194 DATACENTER_BOT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
195 DATACENTER_BOT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
197 DATACENTER_BOT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
198 DATACENTER_BOT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
199 DATACENTER_BOT_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
200 DATACENTER_MID_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
201 DATACENTER_MID_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
202 DATACENTER_MID_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
203 DATACENTER_MID_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
204 DATACENTER_MID_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
205 DATACENTER_MID_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
206 DATACENTER_TOP_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
207 DATACENTER_TOP_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
208 DATACENTER_TOP_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
209 DATACENTER_TOP_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
210 DATACENTER_TOP_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
211 DATACENTER_TOP_ZN_6_CEILING 0 0.00 0.00 0.00 0 2.74 0.00 1.79 -999.00 0 No No
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
216 DATACENTER_BASEMENT_ZN_6_FLOOR 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 0 0.00 0.00 0.00 0 2.44 0.00 24.18 -999.00 0 No No


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {m2} # Zone Occupants Design Volume Flow Rate {m3/s} Volume Flow Rate/Floor Area {m3/s-m2} Volume Flow Rate/Exterior Surface Area {m3/s-m2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 PERIMETER_BOT_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_3 313.41 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
2 PERIMETER_BOT_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
3 PERIMETER_BOT_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_1 313.42 16.9 0.114 3.646E-004 5.482E-004 0.478 0.000 0.000 0.224 0.000
4 PERIMETER_BOT_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_BOT_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.534E-004 0.495 0.000 0.000 0.224 0.000
5 PERIMETER_MID_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
6 PERIMETER_MID_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
7 PERIMETER_MID_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
8 PERIMETER_MID_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_MID_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
9 PERIMETER_TOP_ZN_3_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_3 313.41 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
10 PERIMETER_TOP_ZN_2_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_2 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
11 PERIMETER_TOP_ZN_1_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_1 313.42 16.9 0.114 3.646E-004 5.696E-004 0.478 0.000 0.000 0.224 0.000
12 PERIMETER_TOP_ZN_4_INFILTRATION INFIL_SCH_PNNL PERIMETER_TOP_ZN_4 201.98 10.9 7.617E-002 3.771E-004 5.696E-004 0.495 0.000 0.000 0.224 0.000
13 GROUNDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL GROUNDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
14 MIDFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL MIDFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 5.696E-004 0.140 0.000 0.000 0.224 0.000
15 TOPFLOOR_PLENUM_INFILTRATION INFIL_SCH_PNNL TOPFLOOR_PLENUM 3563.11 0.0 0.169 4.749E-005 4.384E-005 0.140 0.000 0.000 0.224 0.000


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BASEMENT Mixing/Well-Stirred
2 CORE_BOTTOM Mixing/Well-Stirred
3 CORE_MID Mixing/Well-Stirred
4 CORE_TOP Mixing/Well-Stirred
5 PERIMETER_BOT_ZN_3 Mixing/Well-Stirred
6 PERIMETER_BOT_ZN_2 Mixing/Well-Stirred
7 PERIMETER_BOT_ZN_1 Mixing/Well-Stirred
8 PERIMETER_BOT_ZN_4 Mixing/Well-Stirred
9 PERIMETER_MID_ZN_3 Mixing/Well-Stirred
10 PERIMETER_MID_ZN_2 Mixing/Well-Stirred
11 PERIMETER_MID_ZN_1 Mixing/Well-Stirred
12 PERIMETER_MID_ZN_4 Mixing/Well-Stirred
13 PERIMETER_TOP_ZN_3 Mixing/Well-Stirred
14 PERIMETER_TOP_ZN_2 Mixing/Well-Stirred
15 PERIMETER_TOP_ZN_1 Mixing/Well-Stirred
16 PERIMETER_TOP_ZN_4 Mixing/Well-Stirred
17 GROUNDFLOOR_PLENUM Mixing/Well-Stirred
18 MIDFLOOR_PLENUM Mixing/Well-Stirred
19 TOPFLOOR_PLENUM Mixing/Well-Stirred
20 DATACENTER_BOT_ZN_6 Mixing/Well-Stirred
21 DATACENTER_MID_ZN_6 Mixing/Well-Stirred
22 DATACENTER_TOP_ZN_6 Mixing/Well-Stirred
23 DATACENTER_BASEMENT_ZN_6 Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Sky Daylight Factors

Sky Type MonthAndDay Daylighting Control Name Enclosure Name Window Name Reference Point Daylight Factor
1 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6254E-003
2 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6265E-003
3 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7661E-003
4 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7670E-003
5 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1309E-003
6 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1315E-003
7 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
8 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2452E-003
9 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6512E-003
10 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7229E-003
11 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7871E-003
12 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8468E-003
13 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1472E-003
14 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1952E-003
15 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2574E-003
16 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2891E-003
17 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 7.2727E-002
18 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.0291E-002
19 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 8.0494E-002
20 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 3.2035E-002
21 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 5.9708E-002
22 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2098E-002
23 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6042E-002
24 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 PERIMETER_BOT_ZN_1_DAYLREFPT2 9.1095E-003
25 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6579E-003
26 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7555E-003
27 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7943E-003
28 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.8820E-003
29 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1538E-003
30 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.2204E-003
31 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2577E-003
32 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2900E-003
33 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.6253E-003
34 Clear Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.6267E-003
35 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.7661E-003
36 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.7672E-003
37 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 2.1309E-003
38 Intermediate Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 2.1317E-003
39 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT1 1.2447E-003
40 Overcast Sky 01/21 PERIMETER_BOT_ZN_1_DAYLCTRL PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 PERIMETER_BOT_ZN_1_DAYLREFPT2 1.2451E-003
41 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.8368E-003
42 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.9662E-003
43 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.7256E-003
44 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8595E-003
45 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.5577E-003
46 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.6254E-003
47 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1302E-003
48 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1521E-003
49 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4075E-002
50 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.6441E-002
51 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.2729E-002
52 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.5117E-002
53 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 3.4408E-002
54 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 1.3988E-002
55 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6787E-002
56 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 PERIMETER_BOT_ZN_2_DAYLREFPT2 9.9865E-003
57 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.8074E-003
58 Clear Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.8584E-003
59 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.6892E-003
60 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.7267E-003
61 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.5378E-003
62 Intermediate Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.5542E-003
63 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT1 2.1303E-003
64 Overcast Sky 01/21 PERIMETER_BOT_ZN_2_DAYLCTRL PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 PERIMETER_BOT_ZN_2_DAYLREFPT2 2.1525E-003
65 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2173E-003
66 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2185E-003
67 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0474E-003
68 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0484E-003
69 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.3115E-004
70 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.3188E-004
71 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
72 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2452E-003
73 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2446E-003
74 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3113E-003
75 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0699E-003
76 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1233E-003
77 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4925E-004
78 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.8862E-004
79 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2577E-003
80 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2900E-003
81 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.8942E-002
82 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0694E-002
83 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4825E-002
84 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 8.1954E-003
85 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.4675E-002
86 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 5.8147E-003
87 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT1 2.6042E-002
88 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.1067E-003
89 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2422E-003
90 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.3084E-003
91 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0669E-003
92 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.1173E-003
93 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.4412E-004
94 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.7295E-004
95 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2574E-003
96 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2891E-003
97 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2172E-003
98 Clear Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2184E-003
99 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.0473E-003
100 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.0482E-003
101 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 9.3105E-004
102 Intermediate Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 9.3158E-004
103 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT1 1.2447E-003
104 Overcast Sky 01/21 PERIMETER_BOT_ZN_3_DAYLCTRL PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 PERIMETER_BOT_ZN_3_DAYLREFPT2 1.2451E-003
105 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3332E-003
106 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.3869E-003
107 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1155E-003
108 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1543E-003
109 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.0937E-003
110 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1081E-003
111 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1303E-003
112 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1525E-003
113 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.4812E-002
114 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.2955E-002
115 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1647E-002
116 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.0967E-002
117 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.5251E-002
118 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 1.0492E-002
119 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.6787E-002
120 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 PERIMETER_BOT_ZN_4_DAYLREFPT2 9.9865E-003
121 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.3553E-003
122 Clear Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.4510E-003
123 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1434E-003
124 Clear Turbid Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.2365E-003
125 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1120E-003
126 Intermediate Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1695E-003
127 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT1 2.1302E-003
128 Overcast Sky 01/21 PERIMETER_BOT_ZN_4_DAYLCTRL PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 PERIMETER_BOT_ZN_4_DAYLREFPT2 2.1521E-003
129 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.3410E-002
130 Clear Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.1344E-002
131 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 7.9692E-002
132 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 4.3683E-002
133 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 6.3222E-002
134 Intermediate Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 3.1272E-002
135 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT1 3.0133E-002
136 Overcast Sky 01/21 PERIMETER_MID_ZN_1_DAYLCTRL PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW PERIMETER_MID_ZN_1_DAYLREFPT2 1.4574E-002
137 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9035E-002
138 Clear Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.2699E-002
139 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.7576E-002
140 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 2.1160E-002
141 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.9026E-002
142 Intermediate Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.9643E-002
143 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT1 3.0820E-002
144 Overcast Sky 01/21 PERIMETER_MID_ZN_2_DAYLCTRL PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW PERIMETER_MID_ZN_2_DAYLREFPT2 1.4729E-002
145 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 2.2861E-002
146 Clear Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.5883E-002
147 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8361E-002
148 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.2694E-002
149 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 1.8134E-002
150 Intermediate Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 9.9391E-003
151 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT1 3.0133E-002
152 Overcast Sky 01/21 PERIMETER_MID_ZN_3_DAYLCTRL PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW PERIMETER_MID_ZN_3_DAYLREFPT2 1.4571E-002
153 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.8977E-002
154 Clear Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.8133E-002
155 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.5522E-002
156 Clear Turbid Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5701E-002
157 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 2.9157E-002
158 Intermediate Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.5175E-002
159 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT1 3.0820E-002
160 Overcast Sky 01/21 PERIMETER_MID_ZN_4_DAYLCTRL PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW PERIMETER_MID_ZN_4_DAYLREFPT2 1.4729E-002
161 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.3413E-002
162 Clear Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.1409E-002
163 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 7.9711E-002
164 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 4.3759E-002
165 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 6.3264E-002
166 Intermediate Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 3.1337E-002
167 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT1 3.0168E-002
168 Overcast Sky 01/21 PERIMETER_TOP_ZN_1_DAYLCTRL PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW PERIMETER_TOP_ZN_1_DAYLREFPT2 1.4602E-002
169 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9027E-002
170 Clear Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.2722E-002
171 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.7578E-002
172 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 2.1183E-002
173 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.9047E-002
174 Intermediate Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.9678E-002
175 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT1 3.0854E-002
176 Overcast Sky 01/21 PERIMETER_TOP_ZN_2_DAYLCTRL PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW PERIMETER_TOP_ZN_2_DAYLREFPT2 1.4757E-002
177 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 2.2836E-002
178 Clear Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.5890E-002
179 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8344E-002
180 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.2700E-002
181 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 1.8144E-002
182 Intermediate Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 9.9535E-003
183 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT1 3.0168E-002
184 Overcast Sky 01/21 PERIMETER_TOP_ZN_3_DAYLCTRL PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW PERIMETER_TOP_ZN_3_DAYLREFPT2 1.4599E-002
185 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.8960E-002
186 Clear Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.8147E-002
187 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.5513E-002
188 Clear Turbid Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5714E-002
189 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 2.9171E-002
190 Intermediate Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.5200E-002
191 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT1 3.0854E-002
192 Overcast Sky 01/21 PERIMETER_TOP_ZN_4_DAYLCTRL PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW PERIMETER_TOP_ZN_4_DAYLREFPT2 1.4757E-002


Zone Sizing Information

Zone Name Load Type Calc Des Load {W} User Des Load {W} Calc Des Air Flow Rate {m3/s} User Des Air Flow Rate {m3/s} Design Day Name Date/Time of Peak Temperature at Peak {C} Humidity Ratio at Peak {kgWater/kgDryAir} Floor Area {m2} # Occupants Calc Outdoor Air Flow Rate {m3/s} Calc DOAS Heat Addition Rate {W}
1 BASEMENT Cooling 76041.58315 76041.58315 5.47886 5.47886 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2779.42662 149.60210 1.20016 0.00000
2 BASEMENT Heating 0.00000 0.00000 0.00000 1.20016   00:10:00 4.60000 5.25715E-003 2779.42662 149.60210 1.20016 0.00000
3 CORE_BOTTOM Cooling 78274.25347 78274.25347 5.63903 5.63903 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
4 CORE_BOTTOM Heating 0.00000 0.00000 0.00000 1.07782   00:10:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
5 CORE_MID Cooling 733090.74824 733090.74824 52.79794 52.79794 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 10.77825 0.00000
6 CORE_MID Heating 183142.69633 183142.69633 7.67434 10.77825 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 10.77825 0.00000
7 CORE_TOP Cooling 72622.80178 72622.80178 5.23020 5.23020 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 28.05400 1.65254E-002 2496.12046 134.35320 1.07782 0.00000
8 CORE_TOP Heating 42695.79090 42695.79090 1.81005 1.81005 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 2496.12046 134.35320 1.07782 0.00000
9 PERIMETER_BOT_ZN_3 Cooling 12489.88707 12489.88707 0.90825 0.90825 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 33.90000 1.65364E-002 313.41284 16.86939 0.13533 0.00000
10 PERIMETER_BOT_ZN_3 Heating 3273.41376 3273.41376 0.13793 0.13793 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
11 PERIMETER_BOT_ZN_2 Cooling 12778.37453 12778.37453 0.92922 0.92922 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:40:00 30.45033 1.65299E-002 201.97515 10.87127 8.72129E-002 0.00000
12 PERIMETER_BOT_ZN_2 Heating 2459.77317 2459.77317 0.10391 0.10391 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
13 PERIMETER_BOT_ZN_1 Cooling 15118.40346 15118.40346 1.09939 1.09939 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 33.76833 1.65361E-002 313.41969 16.86975 0.13533 0.00000
14 PERIMETER_BOT_ZN_1 Heating 4957.07671 4957.07671 0.21006 0.21006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
15 PERIMETER_BOT_ZN_4 Cooling 16449.13132 16449.13132 1.19615 1.19615 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
16 PERIMETER_BOT_ZN_4 Heating 1052.25000 1052.25000 4.46141E-002 8.72129E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
17 PERIMETER_MID_ZN_3 Cooling 115832.27826 115832.27826 8.42372 8.42372 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 33.90000 1.65364E-002 313.41284 16.86939 1.35332 0.00000
18 PERIMETER_MID_ZN_3 Heating 103514.34719 103514.34719 4.40836 4.40836 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 1.35332 0.00000
19 PERIMETER_MID_ZN_2 Cooling 130468.12308 130468.12308 9.48802 9.48802 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 30.67417 1.65303E-002 201.97515 10.87127 0.87213 0.00000
20 PERIMETER_MID_ZN_2 Heating 69043.46998 69043.46998 2.94069 2.94069 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
21 PERIMETER_MID_ZN_1 Cooling 142290.72837 142290.72837 10.34783 10.34783 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 33.83417 1.65363E-002 313.41969 16.86975 1.35335 0.00000
22 PERIMETER_MID_ZN_1 Heating 102840.94518 102840.94518 4.37957 4.37957 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 1.35335 0.00000
23 PERIMETER_MID_ZN_4 Cooling 138251.92159 138251.92159 10.05406 10.05406 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 32.66233 1.65340E-002 201.97515 10.87127 0.87213 0.00000
24 PERIMETER_MID_ZN_4 Heating 61294.69647 61294.69647 2.60952 2.60952 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 0.87213 0.00000
25 PERIMETER_TOP_ZN_3 Cooling 13303.12849 13303.12849 0.96747 0.96747 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 33.82100 1.65362E-002 313.41284 16.86939 0.13533 0.00000
26 PERIMETER_TOP_ZN_3 Heating 13834.64805 13834.64805 0.58982 0.58982 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41284 16.86939 0.13533 0.00000
27 PERIMETER_TOP_ZN_2 Cooling 13327.86167 13327.86167 0.96926 0.96926 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:10:00 31.09550 1.65311E-002 201.97515 10.87127 8.72129E-002 0.00000
28 PERIMETER_TOP_ZN_2 Heating 9134.59591 9134.59591 0.38947 0.38947 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
29 PERIMETER_TOP_ZN_1 Cooling 15886.01902 15886.01902 1.15531 1.15531 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 33.90000 1.65364E-002 313.41969 16.86975 0.13533 0.00000
30 PERIMETER_TOP_ZN_1 Heating 13759.49424 13759.49424 0.58660 0.58660 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 313.41969 16.86975 0.13533 0.00000
31 PERIMETER_TOP_ZN_4 Cooling 14995.22512 14995.22512 1.09052 1.09052 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 32.79400 1.65343E-002 201.97515 10.87127 8.72129E-002 0.00000
32 PERIMETER_TOP_ZN_4 Heating 8552.35816 8552.35816 0.36457 0.36457 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4.60000 5.25715E-003 201.97515 10.87127 8.72129E-002 0.00000
33 DATACENTER_BOT_ZN_6 Cooling 8120.36112 8120.36112 0.46568 0.46568 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:20:00 26.05267 1.65216E-002 36.20274 1.94861 1.56323E-002 0.00000
34 DATACENTER_BOT_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56323E-002 0.00000
35 DATACENTER_MID_ZN_6 Cooling 77163.21473 77163.21473 4.42564 4.42564 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 0.15632 0.00000
36 DATACENTER_MID_ZN_6 Heating 0.00000 0.00000 0.00000 0.15632   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 0.15632 0.00000
37 DATACENTER_TOP_ZN_6 Cooling 7870.19515 7870.19515 0.45139 0.45139 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 31.21400 1.65313E-002 36.20274 1.94861 1.56323E-002 0.00000
38 DATACENTER_TOP_ZN_6 Heating 0.00000 0.00000 0.00000 1.56323E-002   00:10:00 4.60000 5.25715E-003 36.20274 1.94861 1.56323E-002 0.00000
39 DATACENTER_BASEMENT_ZN_6 Cooling 371959.72717 371959.72717 21.33288 21.33288 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 26.71100 1.65229E-002 783.67941 42.18139 0.33839 0.00000
40 DATACENTER_BASEMENT_ZN_6 Heating 0.00000 0.00000 0.00000 0.33839   00:10:00 4.60000 5.25715E-003 783.67941 42.18139 0.33839 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [m3/s] User Des Air Flow Rate [m3/s] Design Day Name Date/Time of Peak
1 VAV_BOT WITH REHEAT Cooling Sensible 146314.48 8.94172 8.94172 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
2 VAV_BOT WITH REHEAT Heating Sensible 16030.11 1.61693 1.61693 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
3 VAV_MID WITH REHEAT Cooling Sensible 1336440.30 82.71906 82.71906 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
4 VAV_MID WITH REHEAT Heating Sensible 249001.53 25.11640 25.11640 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00
5 VAV_TOP WITH REHEAT Cooling Sensible 150861.96 8.93574 8.93574 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 00:00:00
6 VAV_TOP WITH REHEAT Heating Sensible 25149.12 3.74052 3.74052 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 13:00:00
7 CAV_BAS Cooling Sensible 80481.36 5.47886 5.47886 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CAV_BAS Heating Sensible 51365.55 1.20016 1.20016 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
9 AIRLOOP DATACENTER BASEMENT Cooling Sensible 368539.76 21.33310 21.33310 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 AIRLOOP DATACENTER BASEMENT Heating Sensible 14482.89 0.33839 0.33839 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
11 AIRLOOP DATACENTER BOT Cooling Sensible 8069.30 0.46568 0.46568 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 AIRLOOP DATACENTER BOT Heating Sensible 669.05 1.56323E-002 1.56323E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
13 AIRLOOP DATACENTER MID Cooling Sensible 76766.78 4.42564 4.42564 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 AIRLOOP DATACENTER MID Heating Sensible 6690.49 0.15632 0.15632 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
15 AIRLOOP DATACENTER TOP Cooling Sensible 7831.26 0.45139 0.45139 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 AIRLOOP DATACENTER TOP Heating Sensible 669.05 1.56323E-002 1.56323E-002 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat BASEMENT DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 5.47886
2 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.63903
3 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.33730
4 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.33500
5 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.88908
6 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.89947
7 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
8 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.12956E-003
9 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.66263E-004
10 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.88908
11 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
12 AirTerminal:SingleDuct:VAV:Reheat CORE_BOTTOM VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
13 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19004.93673
14 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.66263E-004
15 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 383.12461
16 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 52.79794
17 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36025
18 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.34900
19 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 18.42648
20 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.96067
21 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
22 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.05760E-003
23 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.22398E-003
24 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 18.42648
25 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
26 AirTerminal:SingleDuct:VAV:Reheat CORE_MID VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
27 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Rated Capacity [W] 368521.24448
28 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.22398E-003
29 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 8236.54941
30 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 5.23020
31 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.36367
32 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.36100
33 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.88810
34 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.96978
35 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
36 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.04767E-003
37 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 5.39699E-004
38 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 1.88810
39 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
40 AirTerminal:SingleDuct:VAV:Reheat CORE_TOP VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
41 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Rated Capacity [W] 61690.92905
42 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 5.39699E-004
43 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 1609.03079
44 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.90825
45 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.26295
46 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.26100
47 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23705
48 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.70119
49 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
50 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.44897E-003
51 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 4.94645E-005
52 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23705
53 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
54 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
55 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 5654.09781
56 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 4.94645E-005
57 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 132.02861
58 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.92922
59 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16563
60 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
61 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.18584
62 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.44167
63 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
64 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.30034E-003
65 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.78499E-005
66 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.18584
67 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
68 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
69 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 4326.47754
70 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.78499E-005
71 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 100.35627
72 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.09939
73 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.21723
74 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.21600
75 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23747
76 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.57929
77 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
78 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.75386E-003
79 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 6.42408E-005
80 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23747
81 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
82 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
83 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 7343.11521
84 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 6.42408E-005
85 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 187.12359
86 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.19615
87 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.12867
88 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
89 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23923
90 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.34311
91 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
92 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.96113E-003
93 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 3.02084E-005
94 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.23923
95 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
96 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_BOT_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
97 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 3453.00346
98 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 3.02084E-005
99 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 72.72870
100 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 8.42372
101 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.28351
102 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.27500
103 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.31652
104 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.75603
105 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
106 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.34387E-003
107 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.29328E-003
108 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.40836
109 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
110 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
111 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 147829.41000
112 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.29328E-003
113 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3900.55004
114 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 9.48802
115 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.16221
116 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
117 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 1.89760
118 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.43256
119 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
120 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.34881E-003
121 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 8.62644E-004
122 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.94069
123 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
124 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
125 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 98605.52248
126 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 8.62644E-004
127 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2601.66588
128 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.34783
129 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.23080
130 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.22400
131 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.31791
132 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.61546
133 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
134 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.65080E-003
135 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.28485E-003
136 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 4.37957
137 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
138 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
139 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 146866.25488
140 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.28485E-003
141 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 3875.16332
142 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 10.05406
143 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15308
144 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
145 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 2.01081
146 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.40821
147 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
148 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.48894E-003
149 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 7.65689E-004
150 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 2.60952
151 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
152 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_MID_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
153 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 87523.00276
154 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 7.65689E-004
155 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 2309.52518
156 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.96747
157 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.24685
158 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.24500
159 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23703
160 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.65827
161 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
162 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.54344E-003
163 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.72915E-004
164 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.58982
165 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
166 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_3 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
167 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19765.20623
168 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.72915E-004
169 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 521.34882
170 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 0.96926
171 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.15879
172 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
173 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.19385
174 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.42343
175 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
176 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.39946E-003
177 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.14173E-004
178 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.38947
179 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
180 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_2 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
181 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 13050.69875
182 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.14173E-004
183 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 344.23061
184 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.15531
185 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.20672
186 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20500
187 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.23684
188 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.55126
189 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
190 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 1.84307E-003
191 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.71974E-004
192 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.58660
193 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
194 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_1 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
195 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 19657.69134
196 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.71974E-004
197 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 518.51591
198 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Air Flow Rate [m3/s] 1.09052
199 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Constant Minimum Air Flow Fraction 0.14113
200 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Constant Minimum Air Flow Fraction 0.20000
201 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Minimum Air Flow Rate [m3/s] 0.21810
202 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow Fraction during Reheat [] 0.37635
203 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT User-Specified Maximum Flow Fraction during Reheat [] 0.50000
204 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] 2.69964E-003
205 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Maximum Reheat Water Flow Rate [m3/s] 1.06886E-004
206 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] 0.36457
207 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Temperature [C] 12.80000
208 AirTerminal:SingleDuct:VAV:Reheat PERIMETER_TOP_ZN_4 VAV BOX COMPONENT Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] 8.00000E-003
209 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Rated Capacity [W] 12217.77503
210 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size Maximum Water Flow Rate [m3/s] 1.06886E-004
211 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Design Size U-Factor Times Area Value [W/K] 322.28105
212 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BOT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.46568
213 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_MID_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 4.42564
214 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_TOP_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 0.45139
215 AirTerminal:SingleDuct:ConstantVolume:NoReheat DATACENTER_BASEMENT_ZN_6 DIRECT AIR Design Size Maximum Air Flow Rate [m3/s] 21.33288
216 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.88602
217 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.78867
218 AirLoopHVAC VAV_BOT WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.77205
219 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 2.78867
220 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.94172
221 AirLoopHVAC VAV_BOT WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.94172
222 AirLoopHVAC VAV_BOT WITH REHEAT User Heating Air Flow Ratio [] 0.30000
223 AirLoopHVAC VAV_BOT WITH REHEAT Calculated Heating Air Flow Ratio [] 0.31187
224 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 45.55579
225 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 26.96933
226 AirLoopHVAC VAV_MID WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 91.11158
227 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 26.96933
228 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 82.71906
229 AirLoopHVAC VAV_MID WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 82.71906
230 AirLoopHVAC VAV_MID WITH REHEAT User Heating Air Flow Ratio [] 0.30000
231 AirLoopHVAC VAV_MID WITH REHEAT Calculated Heating Air Flow Ratio [] 0.32604
232 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.70638
233 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 2.77393
234 AirLoopHVAC VAV_TOP WITH REHEAT Sum of Air Terminal Maximum Flow Rates [m3/s] 9.41276
235 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Heating Design Air Flow Rate [m3/s] 3.74052
236 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Cooling Design Air Flow Rate [m3/s] 8.93574
237 AirLoopHVAC VAV_TOP WITH REHEAT Adjusted Main Design Air Flow Rate [m3/s] 8.93574
238 AirLoopHVAC VAV_TOP WITH REHEAT User Heating Air Flow Ratio [] 0.30000
239 AirLoopHVAC VAV_TOP WITH REHEAT Calculated Heating Air Flow Ratio [] 0.41860
240 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 5.47886
241 AirLoopHVAC CAV_BAS Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 5.47886
242 AirLoopHVAC CAV_BAS Sum of Air Terminal Maximum Flow Rates [m3/s] 5.47886
243 AirLoopHVAC CAV_BAS Adjusted Heating Design Air Flow Rate [m3/s] 5.47886
244 AirLoopHVAC CAV_BAS Adjusted Cooling Design Air Flow Rate [m3/s] 5.47886
245 AirLoopHVAC CAV_BAS Adjusted Main Design Air Flow Rate [m3/s] 5.47886
246 AirLoopHVAC CAV_BAS User Heating Air Flow Ratio [] 1.00000
247 AirLoopHVAC CAV_BAS Calculated Heating Air Flow Ratio [] 1.00000
248 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 21.33288
249 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 21.33288
250 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Sum of Air Terminal Maximum Flow Rates [m3/s] 21.33288
251 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Heating Design Air Flow Rate [m3/s] 21.33288
252 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Cooling Design Air Flow Rate [m3/s] 21.33310
253 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Adjusted Main Design Air Flow Rate [m3/s] 21.33310
254 AirLoopHVAC AIRLOOP DATACENTER BASEMENT User Heating Air Flow Ratio [] 1.00000
255 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Calculated Heating Air Flow Ratio [] 0.99999
256 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.46568
257 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.46568
258 AirLoopHVAC AIRLOOP DATACENTER BOT Sum of Air Terminal Maximum Flow Rates [m3/s] 0.46568
259 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Heating Design Air Flow Rate [m3/s] 0.46568
260 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Cooling Design Air Flow Rate [m3/s] 0.46568
261 AirLoopHVAC AIRLOOP DATACENTER BOT Adjusted Main Design Air Flow Rate [m3/s] 0.46568
262 AirLoopHVAC AIRLOOP DATACENTER BOT User Heating Air Flow Ratio [] 1.00000
263 AirLoopHVAC AIRLOOP DATACENTER BOT Calculated Heating Air Flow Ratio [] 1.00000
264 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 4.42564
265 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 4.42564
266 AirLoopHVAC AIRLOOP DATACENTER MID Sum of Air Terminal Maximum Flow Rates [m3/s] 4.42564
267 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Heating Design Air Flow Rate [m3/s] 4.42564
268 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Cooling Design Air Flow Rate [m3/s] 4.42564
269 AirLoopHVAC AIRLOOP DATACENTER MID Adjusted Main Design Air Flow Rate [m3/s] 4.42564
270 AirLoopHVAC AIRLOOP DATACENTER MID User Heating Air Flow Ratio [] 1.00000
271 AirLoopHVAC AIRLOOP DATACENTER MID Calculated Heating Air Flow Ratio [] 1.00000
272 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Heating Flow Rates [m3/s] 0.45139
273 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Minimum Heating Flow Rates [m3/s] 0.45139
274 AirLoopHVAC AIRLOOP DATACENTER TOP Sum of Air Terminal Maximum Flow Rates [m3/s] 0.45139
275 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Heating Design Air Flow Rate [m3/s] 0.45139
276 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Cooling Design Air Flow Rate [m3/s] 0.45139
277 AirLoopHVAC AIRLOOP DATACENTER TOP Adjusted Main Design Air Flow Rate [m3/s] 0.45139
278 AirLoopHVAC AIRLOOP DATACENTER TOP User Heating Air Flow Ratio [] 1.00000
279 AirLoopHVAC AIRLOOP DATACENTER TOP Calculated Heating Air Flow Ratio [] 1.00000
280 AirLoopHVAC VAV_BOT WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.94172
281 AirLoopHVAC VAV_MID WITH REHEAT Design Supply Air Flow Rate [m3/s] 82.71906
282 AirLoopHVAC VAV_TOP WITH REHEAT Design Supply Air Flow Rate [m3/s] 8.93574
283 AirLoopHVAC CAV_BAS Design Supply Air Flow Rate [m3/s] 5.47886
284 AirLoopHVAC AIRLOOP DATACENTER BASEMENT Design Supply Air Flow Rate [m3/s] 21.33310
285 AirLoopHVAC AIRLOOP DATACENTER BOT Design Supply Air Flow Rate [m3/s] 0.46568
286 AirLoopHVAC AIRLOOP DATACENTER MID Design Supply Air Flow Rate [m3/s] 4.42564
287 AirLoopHVAC AIRLOOP DATACENTER TOP Design Supply Air Flow Rate [m3/s] 0.45139
288 Controller:OutdoorAir VAV_BOT WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.94172
289 HeatExchanger:AirToAir:SensibleAndLatent VAV_BOT WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
290 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.93365
291 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
292 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04880
293 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.11747E-002
294 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
295 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 247829.88187
296 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.05433E-002
297 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.94172
298 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 26182.45066
299 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.29055E-004
300 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 452.91327
301 Fan:VariableVolume VAV_BOT WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.94172
302 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.05433E-002
303 Controller:WaterCoil VAV_BOT WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.51654E-005
304 Controller:WaterCoil VAV_BOT WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.29055E-004
305 Controller:OutdoorAir VAV_MID WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 82.71906
306 HeatExchanger:AirToAir:SensibleAndLatent VAV_MID WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 25.38195
307 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 27.29353
308 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
309 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04995
310 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.15349E-002
311 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
312 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 2420734.69453
313 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 0.10298
314 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 82.71906
315 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 246020.64182
316 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.15230E-003
317 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 4252.08254
318 Fan:VariableVolume VAV_MID WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 82.71906
319 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 0.10298
320 Controller:WaterCoil VAV_MID WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.62394E-006
321 Controller:WaterCoil VAV_MID WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.15230E-003
322 Controller:OutdoorAir VAV_TOP WITH REHEAT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 8.93574
323 HeatExchanger:AirToAir:SensibleAndLatent VAV_TOP WITH REHEAT OA HEAT RECOVERY Design Size Nominal Supply Air Flow Rate [m3/s] 2.53819
324 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Temperature [C] 26.82250
325 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
326 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Temperature [C] 11.04870
327 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.11429E-002
328 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
329 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Coil Load [W] 245566.35331
330 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Water Flow Rate [m3/s] 1.04470E-002
331 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL Design Size Design Air Flow Rate [m3/s] 8.93574
332 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Rated Capacity [W] 23750.38579
333 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.07779E-004
334 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL Design Size U-Factor Times Area Value [W/K] 412.95426
335 Fan:VariableVolume VAV_TOP WITH REHEAT FAN Design Size Maximum Flow Rate [m3/s] 8.93574
336 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 1.04470E-002
337 Controller:WaterCoil VAV_TOP WITH REHEAT_COOLC_CONTROLLER Controller Convergence Tolerance 4.55817E-005
338 Controller:WaterCoil VAV_TOP WITH REHEAT_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.07779E-004
339 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 5.47886
340 Controller:OutdoorAir CAV_BAS_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.20016
341 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Temperature [C] 25.00074
342 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Water Temperature [C] 6.67000
343 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Temperature [C] 11.42450
344 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] 1.06240E-002
345 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] 8.50000E-003
346 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Coil Load [W] 127008.98187
347 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Water Flow Rate [m3/s] 5.40326E-003
348 Coil:Cooling:Water CAV_BAS COOLING COIL Design Size Design Air Flow Rate [m3/s] 5.47886
349 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Rated Capacity [W] 258285.90198
350 Coil:Heating:Water CAV_BAS HEATING COIL Design Size Maximum Water Flow Rate [m3/s] 2.25960E-003
351 Coil:Heating:Water CAV_BAS HEATING COIL Design Size U-Factor Times Area Value [W/K] 5860.87899
352 Fan:ConstantVolume CAV_BAS FAN Design Size Maximum Flow Rate [m3/s] 5.47886
353 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Maximum Actuated Flow [m3/s] 5.40326E-003
354 Controller:WaterCoil CAV_BAS_COOLC_CONTROLLER Controller Convergence Tolerance 8.81303E-005
355 Controller:WaterCoil CAV_BAS_HEATC_CONTROLLER Maximum Actuated Flow [m3/s] 2.25960E-003
356 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 21.33310
357 Controller:OutdoorAir AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.33839
358 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 21.33310
359 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Total Cooling Capacity [W] 434337.81672
360 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 312325.50573
361 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 1.06369E-002
362 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 21.33310
363 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 21.33310
364 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 21.33310
365 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 21.33310
366 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Heating Capacity [W] 434337.81672
367 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Nominal Cooling Capacity [W] 434337.81672
368 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 14482.88751
369 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
370 Fan:OnOff AIRLOOP DATACENTER BASEMENT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 21.33310
371 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 21.33310
372 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Heating Capacity [W] 434337.81672
373 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BASEMENT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 1.06369E-002
374 Coil:Heating:Electric AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Design Size Nominal Capacity [W] 14482.88751
375 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Nominal Capacity Volume [m3/s] 8.01492E-005
376 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Nominal Capacity Volume [m3/s] 3.72000E-005
377 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER Design Size Rated Power [W] 96450.69782
378 Humidifier:Steam:Electric DATACENTER_BASEMENT_ZN_6 HUMIDIFIER User-Specified Rated Power [W] 100000.00000
379 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.46568
380 Controller:OutdoorAir AIRLOOP DATACENTER BOT_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
381 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.46568
382 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Total Cooling Capacity [W] 9501.30473
383 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6820.68720
384 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.32686E-004
385 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.46568
386 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.46568
387 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.46568
388 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.46568
389 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Heating Capacity [W] 9501.30473
390 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Nominal Cooling Capacity [W] 9501.30473
391 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.04940
392 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER BOT DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
393 Fan:OnOff AIRLOOP DATACENTER BOT SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.46568
394 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.46568
395 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Heating Capacity [W] 9501.30473
396 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER BOT HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.32686E-004
397 Coil:Heating:Electric AIRLOOP DATACENTER BOT_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.04940
398 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 4.42564
399 Controller:OutdoorAir AIRLOOP DATACENTER MID_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 0.15632
400 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Air Flow Rate [m3/s] 4.42564
401 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Total Cooling Capacity [W] 90544.48627
402 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 64905.21163
403 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.21743E-003
404 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 4.42564
405 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 4.42564
406 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 4.42564
407 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 4.42564
408 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Heating Capacity [W] 90544.48627
409 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Nominal Cooling Capacity [W] 90544.48627
410 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 6690.49404
411 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER MID DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
412 Fan:OnOff AIRLOOP DATACENTER MID SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 4.42564
413 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Air Flow Rate [m3/s] 4.42564
414 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Heating Capacity [W] 90544.48627
415 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER MID HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.21743E-003
416 Coil:Heating:Electric AIRLOOP DATACENTER MID_SUPPHEATCOIL Design Size Nominal Capacity [W] 6690.49404
417 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Maximum Outdoor Air Flow Rate [m3/s] 0.45139
418 Controller:OutdoorAir AIRLOOP DATACENTER TOP_OA_CONTROLLER Minimum Outdoor Air Flow Rate [m3/s] 1.56323E-002
419 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Air Flow Rate [m3/s] 0.45139
420 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Total Cooling Capacity [W] 9227.99310
421 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Sensible Cooling Capacity [W] 6617.52579
422 COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP COOLING COIL Design Size Rated Water Flow Rate [m3/s] 2.25993E-004
423 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate [m3/s] 0.45139
424 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Heating Operation [m3/s] 0.45139
425 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate During Cooling Operation [m3/s] 0.45139
426 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] 0.45139
427 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Heating Capacity [W] 9227.99310
428 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Nominal Cooling Capacity [W] 9227.99310
429 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Supplemental Heating Coil Nominal Capacity [W] 669.04940
430 AirLoopHVAC:UnitaryHeatPump:WaterToAir AIRLOOP DATACENTER TOP DXAC HEAT PUMP Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
431 Fan:OnOff AIRLOOP DATACENTER TOP SUPPLY FAN Design Size Maximum Flow Rate [m3/s] 0.45139
432 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Air Flow Rate [m3/s] 0.45139
433 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Heating Capacity [W] 9227.99310
434 COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AIRLOOP DATACENTER TOP HEATING COIL Design Size Rated Water Flow Rate [m3/s] 2.25993E-004
435 Coil:Heating:Electric AIRLOOP DATACENTER TOP_SUPPHEATCOIL Design Size Nominal Capacity [W] 669.04940
436 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Flow Rate [m3/s] 0.12938
437 Pump:VariableSpeed COOLSYS1 PUMP SECONDARY Design Power Consumption [W] 26659.82968
438 PlantLoop COOLSYS1_DEMAND Maximum Loop Flow Rate [m3/s] 0.12938
439 PlantLoop COOLSYS1_DEMAND Plant Loop Volume [m3] 15.52525
440 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Supply Side Design Fluid Flow Rate [m3/s] 0.12938
441 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop Demand Side Design Fluid Flow Rate [m3/s] 0.12938
442 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Heat Exchanger U-Factor Times Area Value [W/C] 543060.69850
443 HeatExchanger:FluidToFluid BYPASS HEAT EXCHANGER Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] 5.60000
444 PlantLoop HEATSYS1 Maximum Loop Flow Rate [m3/s] 1.37328E-002
445 PlantLoop HEATSYS1 Plant Loop Volume [m3] 1.64794
446 Pump:VariableSpeed HEATSYS1 PUMP Design Flow Rate [m3/s] 1.37328E-002
447 Pump:VariableSpeed HEATSYS1 PUMP Design Power Consumption [W] 4135.73038
448 Pump:VariableSpeed HEATSYS1 PUMP Design Minimum Flow Rate [m3/s] 0.00000
449 Boiler:HotWater HEATSYS1 BOILER Design Size Nominal Capacity [W] 1569748.74601
450 Boiler:HotWater HEATSYS1 BOILER User-Specified Nominal Capacity [W] 1569748.75000
451 Boiler:HotWater HEATSYS1 BOILER Design Size Design Water Flow Rate [m3/s] 1.37328E-002
452 PlantLoop COOLSYS1_SUPPLY Maximum Loop Flow Rate [m3/s] 0.12938
453 PlantLoop COOLSYS1_SUPPLY Plant Loop Volume [m3] 15.52525
454 Pump:ConstantSpeed COOLSYS1 PUMP Design Flow Rate [m3/s] 0.12938
455 Pump:ConstantSpeed COOLSYS1 PUMP Design Power Consumption [W] 18457.49939
456 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12938
457 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.52100E-002
458 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Capacity [W] 1536592.24705
459 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 User-Specified Reference Capacity [W] 1543939.29500
460 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 Design Size Reference Condenser Water Flow Rate [m3/s] 7.64038E-002
461 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Chilled Water Flow Rate [m3/s] 0.12938
462 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Chilled Water Flow Rate [m3/s] 6.52100E-002
463 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Capacity [W] 1536592.24705
464 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 User-Specified Reference Capacity [W] 1543939.29500
465 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 Design Size Reference Condenser Water Flow Rate [m3/s] 7.64038E-002
466 PlantLoop SINGLE WATER PLANT LOOP Maximum Loop Flow Rate [m3/s] 1.33130E-002
467 PlantLoop SINGLE WATER PLANT LOOP Plant Loop Volume [m3] 1.59756
468 Pump:ConstantSpeed PLANT CIRC PUMP Design Flow Rate [m3/s] 1.33130E-002
469 Pump:ConstantSpeed PLANT CIRC PUMP Design Power Consumption [W] 3395.48410
470 FluidCooler:TwoSpeed CENTRAL TOWER Design Water Flow Rate [m3/s] 1.33130E-002
471 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at High Fan Speed [m3/s] 139666.46671
472 FluidCooler:TwoSpeed CENTRAL TOWER Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] 59194.70296
473 FluidCooler:TwoSpeed CENTRAL TOWER Air Flow Rate at Low Fan Speed [m3/s] 69833.23335
474 FluidCooler:TwoSpeed CENTRAL TOWER Fan Power at Low Fan Speed [W] 7879.72339
475 FluidCooler:TwoSpeed CENTRAL TOWER U-factor Times Area Value at Low Fan Speed [W/C] 21407.39688
476 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [W] 548382.00728
477 Boiler:HotWater CENTRAL BOILER User-Specified Nominal Capacity [W] 537788.84000
478 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [m3/s] 1.33130E-002
479 PlantLoop SWHSYS1 Maximum Loop Flow Rate [m3/s] 4.40000E-004
480 PlantLoop SWHSYS1 Plant Loop Volume [m3] 5.28000E-002
481 Pump:ConstantSpeed SWHSYS1 PUMP Design Flow Rate [m3/s] 4.40000E-004
482 Pump:ConstantSpeed SWHSYS1 PUMP Design Power Consumption [W] 5.95776
483 WaterHeater:Mixed SWHSYS1 WATER HEATER Use Side Design Flow Rate [m3/s] 4.40000E-004
484 CondenserLoop TOWERWATERSYS Maximum Loop Flow Rate [m3/s] 0.15281
485 CondenserLoop TOWERWATERSYS Condenser Loop Volume [m3] 18.33692
486 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Flow Rate [m3/s] 0.15281
487 HeaderedPumps:VariableSpeed TOWERWATERSYS PUMP Design Power Consumption [W] 46022.34362
488 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Design Air Flow Rate [m3/s] 58.79022
489 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Nominal Capacity [W] 1831858.06222
490 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Air Flow Rate in free convection regime [m3/s] 11.75804
491 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 1 Tower capacity in free convection regime at design conditions [W] 228982.25778
492 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Design Air Flow Rate [m3/s] 58.79022
493 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Nominal Capacity [W] 1831858.06222
494 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Air Flow Rate in free convection regime [m3/s] 11.75804
495 CoolingTower:VariableSpeed TOWERWATERSYS COOLTOWER 2 Tower capacity in free convection regime at design conditions [W] 228982.25778
496 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.93600E-002
497 PlantEquipmentOperation:ComponentSetPoint WSHPPLANT OPERATION SCHEME Design Water Flow Rate [m3/s] Equipment # 47 7.93600E-002


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {W}
1 Coil:Heating:Water CORE_BOTTOM VAV BOX REHEAT COIL 18020.38
2 Coil:Heating:Water CORE_MID VAV BOX REHEAT COIL 349236.22
3 Coil:Heating:Water CORE_TOP VAV BOX REHEAT COIL 58416.50
4 Coil:Heating:Water PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL 5356.82
5 Coil:Heating:Water PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL 4099.13
6 Coil:Heating:Water PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL 6953.99
7 Coil:Heating:Water PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL 3273.46
8 Coil:Heating:Water PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL 140070.62
9 Coil:Heating:Water PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL 93429.65
10 Coil:Heating:Water PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL 139158.19
11 Coil:Heating:Water PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL 82930.64
12 Coil:Heating:Water PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL 18726.72
13 Coil:Heating:Water PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL 12364.94
14 Coil:Heating:Water PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL 18624.88
15 Coil:Heating:Water PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL 11575.92
16 Coil:Heating:Water VAV_BOT WITH REHEAT HEATING COIL 22237.61
17 Coil:Heating:Water VAV_MID WITH REHEAT HEATING COIL 208610.62
18 Coil:Heating:Water VAV_TOP WITH REHEAT HEATING COIL 20368.63
19 Coil:Heating:Water CAV_BAS HEATING COIL 209415.47


Water Cooling Coil Capacity Information

Component Type Name Nominal Total Capacity {W} Nominal Sensible Capacity {W} Nominal Latent Capacity {W} Nominal Sensible Heat Ratio Nominal Coil UA Value {W/C} Nominal Coil Surface Area {m2}
1 Coil:Cooling:Water VAV_BOT WITH REHEAT COOLING COIL 246350.29 166037.70 80312.59 0.67 25674.37 260.40
2 Coil:Cooling:Water VAV_MID WITH REHEAT COOLING COIL 2324475.12 1557559.90 766915.21 0.67 243261.58 2467.29
3 Coil:Cooling:Water VAV_TOP WITH REHEAT COOLING COIL 245446.72 165579.17 79867.55 0.67 25572.17 259.37
4 Coil:Cooling:Water CAV_BAS COOLING COIL 139490.03 96230.52 43259.51 0.69 14218.79 144.21


Chiller Standard Rating Information

Component Type Component Name IPLV in SI Units {W/W} IPLV in IP Units {Btu/W-h}
1 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER1 6.84 23.33
2 Chiller:Electric:ReformulatedEIR COOLSYS1 CHILLER2 6.84 23.33


Zone Surfaces

Zone Name # Surfaces
1 BASEMENT 10
2 CORE_BOTTOM 8
3 CORE_MID 7
4 CORE_TOP 7
5 PERIMETER_BOT_ZN_3 18
6 PERIMETER_BOT_ZN_2 12
7 PERIMETER_BOT_ZN_1 18
8 PERIMETER_BOT_ZN_4 12
9 PERIMETER_MID_ZN_3 9
10 PERIMETER_MID_ZN_2 8
11 PERIMETER_MID_ZN_1 9
12 PERIMETER_MID_ZN_4 8
13 PERIMETER_TOP_ZN_3 9
14 PERIMETER_TOP_ZN_2 8
15 PERIMETER_TOP_ZN_1 9
16 PERIMETER_TOP_ZN_4 8
17 GROUNDFLOOR_PLENUM 11
18 MIDFLOOR_PLENUM 11
19 TOPFLOOR_PLENUM 11
20 DATACENTER_BOT_ZN_6 6
21 DATACENTER_MID_ZN_6 6
22 DATACENTER_TOP_ZN_6 6
23 DATACENTER_BASEMENT_ZN_6 10


HeatTransfer Surface

Surface Name Surface Class Base Surface Heat Transfer Algorithm Construction Nominal U (w/o film coefs) {W/m2-K} Nominal U (with film coefs) {W/m2-K} Solar Diffusing Area (Net) {m2} Area (Gross) {m2} Area (Sunlit Calc) {m2} Azimuth {deg} Tilt {deg} ~Width {m} ~Height {m} Reveal {m} ExtBoundCondition ExtConvCoeffCalc IntConvCoeffCalc SunExposure WindExposure ViewFactorToGround ViewFactorToSky ViewFactorToGround-IR ViewFactorToSky-IR #Sides
1 BASEMENT_WALL_EAST Wall   CTF - ConductionTransferFunction BASEMENT_WALL_EAST_CFACTOR 0.940 0.824   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
2 BASEMENT_WALL_SOUTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_SOUTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 180.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
3 BASEMENT_WALL_NORTH Wall   CTF - ConductionTransferFunction BASEMENT_WALL_NORTH_CFACTOR 0.940 0.824   139.09 139.09 139.09 0.00 90.00 57.03 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
4 BASEMENT_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 DATACENTER_BASEMENT_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
5 BASEMENT_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   2779.43 2779.43 2779.43 0.00 180.00 57.03 48.74 0.00 BASEMENT_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
6 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
7 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 57.03 4.57 0.00 PERIMETER_BOT_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
8 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   2076.77 2076.77 2076.77 180.00 0.00 52.45 39.59 0.00 CORE_BOT_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
9 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   250.34 250.34 250.34 180.00 0.00 52.45 4.57 0.00 PERIMETER_BOT_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
10 BASEMENT_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   7126.21 7126.21 7126.21 0.00 90.00 7126.21 1.00 0.00 BASEMENT_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
11 CORE_BOT_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
12 CORE_BOT_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
13 CORE_BOT_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
14 CORE_BOT_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
15 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   419.30 419.30 419.30 0.00 180.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
16 CORE_BOT_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2076.82 2076.82 2076.82 0.00 180.00 52.46 39.59 0.00 CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
17 CORE_BOT_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
18 CORE_BOTTOM_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_BOTTOM_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
19 CORE_MID_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
20 CORE_MID_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
21 CORE_MID_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
22 CORE_MID_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
23 CORE_MID_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
24 CORE_MID_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
25 CORE_MID_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_MID_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
26 CORE_TOP_ZN_5_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
27 CORE_TOP_ZN_5_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
28 CORE_TOP_ZN_5_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
29 CORE_TOP_ZN_5_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
30 CORE_TOP_ZN_5_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
31 CORE_TOP_ZN_5_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   2496.12 2496.12 2496.12 180.00 0.00 63.05 39.59 0.00 iz-CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
32 CORE_TOP_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   5064.65 5064.65 5064.65 0.00 90.00 5064.65 1.00 0.00 CORE_TOP_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
33 PERIMETER_BOT_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
34 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
35 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
36 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
37 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
38 PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 Window PERIMETER_BOT_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 17.38 17.38 17.38 0.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
39 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
40 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
41 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
42 PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 Door PERIMETER_BOT_ZN_3_WALL_NORTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 0.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
43 PERIMETER_BOT_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
44 CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
45 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
46 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
47 PERIMETER_BOT_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.34 250.34 250.34 0.00 180.00 52.46 6.47 0.00 PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
48 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 11.51 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
49 PERIMETER_BOT_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
50 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_BOT_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
51 PERIMETER_BOT_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
52 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
53 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
54 PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 Window PERIMETER_BOT_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 19.32 19.32 19.32 90.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
55 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
56 PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 Door PERIMETER_BOT_ZN_2_WALL_EAST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 90.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
57 PERIMETER_BOT_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
58 CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
59 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
60 PERIMETER_BOT_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
61 PERIMETER_BOT_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
62 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
63 PERIMETER_BOT_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   105.88 200.61 105.88 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
64 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
65 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
66 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
67 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
68 PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 Window PERIMETER_BOT_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 17.38 17.38 17.38 180.00 90.00 13.65 1.27 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
69 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
70 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
71 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
72 PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 Door PERIMETER_BOT_ZN_1_WALL_SOUTH CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 180.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
73 PERIMETER_BOT_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
74 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
75 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
76 CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_BOT_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
77 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   63.07 63.07 63.07 0.00 180.00 16.08 4.57 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
78 PERIMETER_BOT_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   250.35 250.35 250.35 0.00 180.00 57.03 6.47 0.00 PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
79 PERIMETER_BOT_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
80 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_BOT_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
81 PERIMETER_BOT_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   71.89 133.74 71.89 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
82 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
83 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
84 PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 Window PERIMETER_BOT_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 19.32 19.32 19.32 270.00 90.00 15.43 1.25 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
85 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
86 PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 Door PERIMETER_BOT_ZN_4_WALL_WEST CTF - ConductionTransferFunction SWINGING DOOR_CON 3.464 3.464   1.95 1.95 1.95 270.00 90.00 0.91 2.13 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
87 PERIMETER_BOT_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
88 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
89 PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_BOT_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
90 PERIMETER_BOT_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
91 PERIMETER_BOT_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
92 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_BOT_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
93 PERIMETER_MID_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
94 PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_MID_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
95 PERIMETER_MID_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
96 CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
97 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
98 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
99 PERIMETER_MID_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
100 PERIMETER_MID_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
101 PERIMETER_MID_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_MID_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
102 PERIMETER_MID_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
103 PERIMETER_MID_ZN_2_WALL_EAST_WINDOW Window PERIMETER_MID_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
104 PERIMETER_MID_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
105 CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
106 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
107 PERIMETER_MID_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
108 PERIMETER_MID_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
109 PERIMETER_MID_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
110 PERIMETER_MID_ZN_1_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
111 PERIMETER_MID_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
112 PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_MID_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
113 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
114 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
115 CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_MID_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
116 PERIMETER_MID_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
117 PERIMETER_MID_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
118 PERIMETER_MID_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_MID_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
119 PERIMETER_MID_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
120 PERIMETER_MID_ZN_4_WALL_WEST_WINDOW Window PERIMETER_MID_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
121 PERIMETER_MID_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
122 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
123 PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_MID_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
124 PERIMETER_MID_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
125 PERIMETER_MID_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
126 PERIMETER_MID_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_MID_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
127 PERIMETER_TOP_ZN_3_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 0.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
128 PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW Window PERIMETER_TOP_ZN_3_WALL_NORTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_NORTH_0.25 N/A 2.869 No 86.92 86.92 86.92 0.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
129 PERIMETER_TOP_ZN_3_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
130 CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 180.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
131 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
132 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
133 PERIMETER_TOP_ZN_3_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
134 PERIMETER_TOP_ZN_3_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.41 313.41 313.41 180.00 0.00 63.96 6.47 0.00 iz-PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
135 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.83 626.83 626.83 0.00 90.00 626.83 1.00 0.00 PERIMETER_TOP_ZN_3_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
136 PERIMETER_TOP_ZN_2_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 90.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
137 PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW Window PERIMETER_TOP_ZN_2_WALL_EAST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_EAST_0.25 N/A 2.869 No 57.95 57.95 57.95 90.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
138 PERIMETER_TOP_ZN_2_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
139 CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_EAST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
140 INT-PER3S-NE-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 225.00 90.00 6.47 2.74 0.00 INT-PER3S-NE Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
141 PERIMETER_TOP_ZN_2_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
142 PERIMETER_TOP_ZN_2_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 225.00 0.00 6.47 39.59 0.00 iz-PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
143 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_2_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
144 PERIMETER_TOP_ZN_1_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   113.68 200.61 113.68 180.00 90.00 73.11 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
145 PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW Window PERIMETER_TOP_ZN_1_WALL_SOUTH Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_SOUTH_0.25 N/A 2.869 No 86.92 86.92 86.92 180.00 90.00 73.11 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
146 INT-PER3S-NE Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 INT-PER3S-NE-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
147 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
148 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 315.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
149 CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   173.00 173.00 173.00 0.00 90.00 63.05 2.74 0.00 CORE_TOP_ZN_5_WALL_SOUTH Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
150 PERIMETER_TOP_ZN_1_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
151 PERIMETER_TOP_ZN_1_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   313.42 313.42 313.42 180.00 0.00 73.11 6.47 0.00 iz-PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
152 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   626.84 626.84 626.84 0.00 90.00 626.84 1.00 0.00 PERIMETER_TOP_ZN_1_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
153 PERIMETER_TOP_ZN_4_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   75.79 133.74 75.79 270.00 90.00 48.74 2.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
154 PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW Window PERIMETER_TOP_ZN_4_WALL_WEST Window5 Detailed Fenestration WINDOW_U_0.5047_SHGC_WEST_0.25 N/A 2.869 No 57.95 57.95 57.95 270.00 90.00 48.74 1.19 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
155 PERIMETER_TOP_ZN_4_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 135.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
156 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
157 PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   17.75 17.75 17.75 45.00 90.00 6.47 2.74 0.00 PERIMETER_TOP_ZN_3_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.50 0.50 0.50 0.50 4
158 PERIMETER_TOP_ZN_4_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
159 PERIMETER_TOP_ZN_4_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 iz-PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
160 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Internal Mass   CTF - ConductionTransferFunction INTERIORFURNISHINGS 0.800 0.800   403.95 403.95 403.95 0.00 90.00 403.95 1.00 0.00 PERIMETER_TOP_ZN_4_INTERNALMASS_1 Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 1.00 0.00 0
161 GROUNDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
162 GROUNDFLOOR_PLENUM_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
163 GROUNDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
164 GROUNDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_GRD 1.743 1.382   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
165 iz-CORE_BOT_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_BOT_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
166 iz-PERIMETER_BOT_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_BOT_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
167 iz-PERIMETER_BOT_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
168 iz-PERIMETER_BOT_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_BOT_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
169 iz-PERIMETER_BOT_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_BOT_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
170 iz-DATACENTER_BOT_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
171 GROUNDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 GROUNDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
172 MIDFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
173 MIDFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
174 MIDFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
175 MIDFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_MID 1.656 1.327   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
176 iz-CORE_MID_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_MID_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
177 iz-PERIMETER_MID_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_MID_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
178 iz-PERIMETER_MID_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_MID_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
179 iz-PERIMETER_MID_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_MID_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
180 iz-PERIMETER_MID_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_MID_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
181 iz-DATACENTER_MID_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
182 MIDFLOOR_PLENUM_CEILING Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 MIDFLOOR_PLENUM_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
183 TOPFLOOR_PLENUM_WALL_NORTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 180.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
184 TOPFLOOR_PLENUM_WALL_EAST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 90.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
185 TOPFLOOR_PLENUM_WALL_WEST Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   59.42 59.42 59.42 270.00 90.00 48.74 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
186 TOPFLOOR_PLENUM_WALL_SOUTH Wall   CTF - ConductionTransferFunction NONRES_EXT_WALL_TOP 2.135 1.618   89.13 89.13 89.13 0.00 90.00 73.11 1.22 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.50 0.50 0.50 0.50 4
187 iz-CORE_TOP_ZN_5_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   2496.12 2496.12 2496.12 0.00 180.00 63.05 39.59 0.00 CORE_TOP_ZN_5_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
188 iz-PERIMETER_TOP_ZN_3_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.41 313.41 313.41 0.00 180.00 63.96 6.47 0.00 PERIMETER_TOP_ZN_3_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
189 iz-PERIMETER_TOP_ZN_2_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 45.00 180.00 6.47 48.74 0.00 PERIMETER_TOP_ZN_2_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
190 iz-PERIMETER_TOP_ZN_1_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   313.42 313.42 313.42 0.00 180.00 73.11 6.47 0.00 PERIMETER_TOP_ZN_1_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
191 iz-PERIMETER_TOP_ZN_4_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   201.98 201.98 201.98 315.00 180.00 6.47 39.59 0.00 PERIMETER_TOP_ZN_4_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
192 iz-DATACENTER_TOP_ZN_6_CEILING Floor   CTF - ConductionTransferFunction DROPCEILING 4.488 2.147   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 1.00 0.00 1.00 0.00 4
193 BUILDING_ROOF Roof   CTF - ConductionTransferFunction NONRES_ROOF 0.228 0.219   3563.11 3563.11 3563.11 180.00 0.00 73.11 48.74 0.00 ExternalEnvironment ASHRAETARP ASHRAETARP SunExposed WindExposed 0.00 1.00 0.00 1.00 4
194 DATACENTER_BOT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
195 DATACENTER_BOT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
196 DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_BOT_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
197 DATACENTER_BOT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
198 DATACENTER_BOT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
199 DATACENTER_BOT_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_BOT_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
200 DATACENTER_MID_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
201 DATACENTER_MID_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
202 DATACENTER_MID_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_MID_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
203 DATACENTER_MID_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
204 DATACENTER_MID_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_MID_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
205 DATACENTER_MID_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_MID_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
206 DATACENTER_TOP_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 90.00 90.00 39.59 2.74 0.00 CORE_TOP_ZN_5_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
207 DATACENTER_TOP_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   108.64 108.64 108.64 270.00 90.00 39.59 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
208 DATACENTER_TOP_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 180.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
209 DATACENTER_TOP_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   2.51 2.51 2.51 0.00 90.00 0.91 2.74 0.00 DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
210 DATACENTER_TOP_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction INT_SLAB_FLOOR 3.839 1.986   36.20 36.20 36.20 0.00 180.00 0.91 39.59 0.00 DATACENTER_TOP_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
211 DATACENTER_TOP_ZN_6_CEILING Roof   CTF - ConductionTransferFunction DROPCEILING 4.488 2.432   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 iz-DATACENTER_TOP_ZN_6_CEILING Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
212 DATACENTER_BASEMENT_ZN_6_WALL_NORTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 0.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
213 DATACENTER_BASEMENT_ZN_6_WALL_SOUTH Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 0.940 0.824   39.22 39.22 39.22 180.00 90.00 16.08 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
214 DATACENTER_BASEMENT_ZN_6_WALL_WEST Wall   CTF - ConductionTransferFunction DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 0.940 0.824   118.87 118.87 118.87 270.00 90.00 48.74 2.44 0.00 FCGround N/A-FCGround ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
215 DATACENTER_BASEMENT_ZN_6_WALL_EAST Wall   CTF - ConductionTransferFunction INT_WALL 6.299 3.242   118.87 118.87 118.87 90.00 90.00 48.74 2.44 0.00 BASEMENT_WALL_WEST Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.50 0.50 0.50 4
216 DATACENTER_BASEMENT_ZN_6_FLOOR Floor   CTF - ConductionTransferFunction EXT_SLAB_8IN_WITH_CARPET 3.285 1.827   783.68 783.68 783.68 0.00 180.00 16.08 48.74 0.00 DATACENTER_BASEMENT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 0.00 1.00 0.00 4
217 DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   36.20 36.20 36.20 180.00 0.00 0.91 39.59 0.00 DATACENTER_BOT_ZN_6_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
218 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   419.35 419.35 419.35 180.00 0.00 10.59 39.59 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
219 PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   201.98 201.98 201.98 135.00 0.00 6.47 48.74 0.00 PERIMETER_BOT_ZN_4_FLOOR Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
220 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.08 63.08 63.08 180.00 0.00 16.08 6.47 0.00 DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4
221 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 Roof   CTF - ConductionTransferFunction INT_SLAB_CEILING 3.839 2.228   63.07 63.07 63.07 180.00 0.00 11.51 6.47 0.00 DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER Other/Same Surface Int Conv ASHRAETARP NoSun NoWind 0.00 1.00 0.00 1.00 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 RUNPERIOD 1 WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day No No No Yes Yes Clark and Allen


Environment:Special Days

Special Day Name Special Day Type Source Start Date Duration {#days}
1 NEW YEARS DAY Holiday InputFile 01/01 1Environment:Special Days


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 Yes InputFile 03/12 11/05


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaC} Std Dev Warmup Temperature Difference {deltaC} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {W} Std Dev Warmup Load Difference {W} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BASEMENT RunPeriod: RUNPERIOD 1 0.2137772604 0.2138114317 Pass Pass 0.6983254466 0.6635844730 Pass Pass
2 CORE_BOTTOM RunPeriod: RUNPERIOD 1 0.2779531181 0.2448828691 Pass Pass 0.2948710649 0.4528436479 Pass Pass
3 CORE_MID RunPeriod: RUNPERIOD 1 0.1607523704 0.2008086195 Pass Pass 0.2332335304 0.4215222089 Pass Pass
4 CORE_TOP RunPeriod: RUNPERIOD 1 0.1453835253 0.1967262428 Pass Pass 0.2245773836 0.4149793043 Pass Pass
5 PERIMETER_BOT_ZN_3 RunPeriod: RUNPERIOD 1 0.2232170369 0.2075386451 Pass Pass 0.2940590136 0.4524296115 Pass Pass
6 PERIMETER_BOT_ZN_2 RunPeriod: RUNPERIOD 1 0.2943537134 0.2786977093 Pass Pass 0.2957214022 0.4527831682 Pass Pass
7 PERIMETER_BOT_ZN_1 RunPeriod: RUNPERIOD 1 0.4108400743 0.5199614057 Pass Pass 0.3347059714 0.4999660248 Pass Pass
8 PERIMETER_BOT_ZN_4 RunPeriod: RUNPERIOD 1 0.3847274494 0.3836479870 Pass Pass 0.3012588087 0.4518471448 Pass Pass
9 PERIMETER_MID_ZN_3 RunPeriod: RUNPERIOD 1 0.1363666115 0.1691947869 Pass Pass 0.2318251869 0.4203152299 Pass Pass
10 PERIMETER_MID_ZN_2 RunPeriod: RUNPERIOD 1 0.2094990881 0.2363970741 Pass Pass 0.2335652425 0.4224965040 Pass Pass
11 PERIMETER_MID_ZN_1 RunPeriod: RUNPERIOD 1 0.3448620155 0.5076044814 Pass Pass 0.2814064208 0.4925364547 Pass Pass
12 PERIMETER_MID_ZN_4 RunPeriod: RUNPERIOD 1 0.2115586731 0.2891746034 Pass Pass 0.2335338066 0.4195373098 Pass Pass
13 PERIMETER_TOP_ZN_3 RunPeriod: RUNPERIOD 1 0.1290791877 0.1688626524 Pass Pass 0.2239731635 0.4137517113 Pass Pass
14 PERIMETER_TOP_ZN_2 RunPeriod: RUNPERIOD 1 0.1994223504 0.2263827315 Pass Pass 0.2257532957 0.4159830524 Pass Pass
15 PERIMETER_TOP_ZN_1 RunPeriod: RUNPERIOD 1 0.3451102564 0.5262533203 Pass Pass 0.2714273401 0.4917846578 Pass Pass
16 PERIMETER_TOP_ZN_4 RunPeriod: RUNPERIOD 1 0.2090554843 0.2878429613 Pass Pass 0.2253725342 0.4130166603 Pass Pass
17 GROUNDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 5.3516382014E-002 4.5836656463E-002 Pass Pass 0.5233926237 2.3266375629 Pass Pass
18 MIDFLOOR_PLENUM RunPeriod: RUNPERIOD 1 4.2245890431E-002 4.6117621775E-002 Pass Pass 0.7844715080 6.0825273154 Pass Pass
19 TOPFLOOR_PLENUM RunPeriod: RUNPERIOD 1 6.2256133760E-002 6.5623035030E-002 Pass Pass 0.2473076538 0.4570897443 Pass Pass
20 DATACENTER_BOT_ZN_6 RunPeriod: RUNPERIOD 1 7.4109437117E-006 8.4931035236E-006 Pass Pass 3.1287125972E-003 3.6623397606E-003 Pass Pass
21 DATACENTER_MID_ZN_6 RunPeriod: RUNPERIOD 1 6.9957677153E-006 8.2933606108E-006 Pass Pass 4.0133893296E-003 4.3557143232E-003 Pass Pass
22 DATACENTER_TOP_ZN_6 RunPeriod: RUNPERIOD 1 6.7761443669E-006 8.1529628763E-006 Pass Pass 6.3040276873E-003 4.7267348112E-003 Pass Pass
23 DATACENTER_BASEMENT_ZN_6 RunPeriod: RUNPERIOD 1 1.0303987002E-005 1.4372986124E-005 Pass Pass 4.6808360229E-005 1.0617894138E-004 Pass Pass



Table of Contents

Report: Annual Heat Emissions Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Heat Emission by Components

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [GJ] 5988.10 -31.9 0.00 3638.66 32326.33 41921.20



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

SizingPeriod:DesignDay

Maximum Dry Bulb [C] Daily Temperature Range [deltaC] Humidity Value Humidity Type Wind Speed [m/s] Wind Direction
TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 4.60 0.00 4.60 Wetbulb [C] 2.50 10.00
TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 33.90 7.90 25.10 Wetbulb [C] 3.10 270.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [mm] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [mm] Monthly Total Roof Irrigation Depth [mm] Monthly Total Rain Collection Volume [m3]
Jan 66.00 12      
Feb 66.00 22      
Mar 126.00 32      
Apr 206.00 19      
May 144.00 46      
Jun 99.00 30      
Jul 192.00 52      
Aug 240.00 34      
Sep 310.00 44      
Oct 34.00 10      
Nov 63.00 12      
Dec 35.00 24      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Opaque Exterior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_EAST BASEMENT_WALL_EAST_CFACTOR 1.00 0.845 0.940 118.87 118.87 90.00 90.00 E
BASEMENT_WALL_SOUTH BASEMENT_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 180.00 90.00 S
BASEMENT_WALL_NORTH BASEMENT_WALL_NORTH_CFACTOR 1.00 0.845 0.940 139.09 139.09 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 200.61 105.88 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 133.74 71.89 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 2006.06 1136.85 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 1337.37 757.90 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 200.61 113.68 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 133.74 75.79 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 0.00 90.00 N
GROUNDFLOOR_PLENUM_WEST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 270.00 90.00 W
GROUNDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_GRD 0.30 1.382 1.743 89.13 89.13 180.00 90.00 S
GROUNDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_GRD 0.30 1.382 1.743 59.42 59.42 90.00 90.00 E
MIDFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 0.00 90.00 N
MIDFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 270.00 90.00 W
MIDFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_MID 0.30 1.327 1.656 891.32 891.32 180.00 90.00 S
MIDFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_MID 0.30 1.327 1.656 594.21 594.21 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_NORTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 180.00 90.00 S
TOPFLOOR_PLENUM_WALL_EAST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 90.00 90.00 E
TOPFLOOR_PLENUM_WALL_WEST NONRES_EXT_WALL_TOP 0.30 1.618 2.135 59.42 59.42 270.00 90.00 W
TOPFLOOR_PLENUM_WALL_SOUTH NONRES_EXT_WALL_TOP 0.30 1.618 2.135 89.13 89.13 0.00 90.00 N
BUILDING_ROOF NONRES_ROOF 0.55 0.221 0.228 3563.11 3563.11 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_NORTH DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR 1.00 0.845 0.940 39.22 39.22 180.00 90.00 S
DATACENTER_BASEMENT_ZN_6_WALL_WEST DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR 1.00 0.845 0.940 118.87 118.87 270.00 90.00 W


Opaque Interior

Construction Reflectance U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Net Area [m2] Azimuth [deg] Tilt [deg] Cardinal Direction
BASEMENT_WALL_WEST INT_WALL 0.30 2.511 6.299 118.87 118.87 270.00 90.00 W
BASEMENT_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 2779.43 2779.43 0.00 180.00  
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 2076.77 2076.77 180.00 0.00  
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 250.34 250.34 180.00 0.00  
CORE_BOT_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_BOT_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 419.30 419.30 0.00 180.00  
CORE_BOT_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 2076.82 2076.82 0.00 180.00  
CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
CORE_MID_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
CORE_MID_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
CORE_MID_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
CORE_MID_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 24961.20 24961.20 0.00 180.00  
CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 180.00 0.00  
CORE_TOP_ZN_5_WALL_SOUTH INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
CORE_TOP_ZN_5_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
CORE_TOP_ZN_5_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2496.12 2496.12 0.00 180.00  
CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 180.00 0.00  
PERIMETER_BOT_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_BOT_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.34 250.34 0.00 180.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_BOT_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_BOT_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 45.00 180.00  
PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
PERIMETER_BOT_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER INT_SLAB_FLOOR 0.30 1.887 3.839 63.07 63.07 0.00 180.00  
PERIMETER_BOT_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 250.35 250.35 0.00 180.00  
PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_BOT_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_BOT_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 201.98 201.98 315.00 180.00  
PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
PERIMETER_MID_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 180.00 90.00 S
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
PERIMETER_MID_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.13 3134.13 0.00 180.00  
PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 180.00 0.00  
PERIMETER_MID_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 225.00 90.00 W
PERIMETER_MID_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 45.00 180.00  
PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 225.00 0.00  
PERIMETER_MID_ZN_1_WALL_EAST INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 315.00 90.00 N
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1729.99 1729.99 0.00 90.00 N
PERIMETER_MID_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 3134.20 3134.20 0.00 180.00  
PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 180.00 0.00  
PERIMETER_MID_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 177.47 177.47 135.00 90.00 S
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 177.47 177.47 45.00 90.00 E
PERIMETER_MID_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 2019.75 2019.75 315.00 180.00  
PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 135.00 0.00  
PERIMETER_TOP_ZN_3_WALL_WEST INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 180.00 90.00 S
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
PERIMETER_TOP_ZN_3_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.41 313.41 0.00 180.00  
PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 180.00 0.00  
PERIMETER_TOP_ZN_2_WALL_NORTH INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
INT-PER3S-NE-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 225.00 90.00 W
PERIMETER_TOP_ZN_2_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 45.00 180.00  
PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 225.00 0.00  
INT-PER3S-NE INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 315.00 90.00 N
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 173.00 173.00 0.00 90.00 N
PERIMETER_TOP_ZN_1_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 313.42 313.42 0.00 180.00  
PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 180.00 0.00  
PERIMETER_TOP_ZN_4_WALL_SOUTH INT_WALL 0.30 2.511 6.299 17.75 17.75 135.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 17.75 17.75 45.00 90.00 E
PERIMETER_TOP_ZN_4_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 201.98 201.98 315.00 180.00  
PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 135.00 0.00  
iz-CORE_BOT_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_BOT_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_BOT_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_BOT_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_BOT_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
GROUNDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 3563.11 3563.11 180.00 0.00  
iz-CORE_MID_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 24961.20 24961.20 0.00 180.00  
iz-PERIMETER_MID_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 3134.13 3134.13 0.00 180.00  
iz-PERIMETER_MID_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 45.00 180.00  
iz-PERIMETER_MID_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 3134.20 3134.20 0.00 180.00  
iz-PERIMETER_MID_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 2019.75 2019.75 315.00 180.00  
iz-DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 0.00 180.00  
MIDFLOOR_PLENUM_CEILING INT_SLAB_CEILING 0.30 2.104 3.839 35631.06 35631.06 180.00 0.00  
iz-CORE_TOP_ZN_5_CEILING DROPCEILING 0.30 2.031 4.488 2496.12 2496.12 0.00 180.00  
iz-PERIMETER_TOP_ZN_3_CEILING DROPCEILING 0.30 2.031 4.488 313.41 313.41 0.00 180.00  
iz-PERIMETER_TOP_ZN_2_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 45.00 180.00  
iz-PERIMETER_TOP_ZN_1_CEILING DROPCEILING 0.30 2.031 4.488 313.42 313.42 0.00 180.00  
iz-PERIMETER_TOP_ZN_4_CEILING DROPCEILING 0.30 2.031 4.488 201.98 201.98 315.00 180.00  
iz-DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_BOT_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_BOT_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_BOT_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.887 3.839 36.20 36.20 0.00 180.00  
DATACENTER_BOT_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_MID_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 270.00 90.00 W
DATACENTER_MID_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 25.09 25.09 180.00 90.00 S
DATACENTER_MID_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 1086.40 1086.40 90.00 90.00 E
DATACENTER_MID_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 25.09 25.09 0.00 90.00 N
DATACENTER_MID_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 362.03 362.03 0.00 180.00  
DATACENTER_MID_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 362.03 362.03 180.00 0.00  
DATACENTER_TOP_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 108.64 108.64 90.00 90.00 E
DATACENTER_TOP_ZN_6_WALL_WEST INT_WALL 0.30 2.511 6.299 108.64 108.64 270.00 90.00 W
DATACENTER_TOP_ZN_6_WALL_SOUTH INT_WALL 0.30 2.511 6.299 2.51 2.51 180.00 90.00 S
DATACENTER_TOP_ZN_6_WALL_NORTH INT_WALL 0.30 2.511 6.299 2.51 2.51 0.00 90.00 N
DATACENTER_TOP_ZN_6_FLOOR INT_SLAB_FLOOR 0.30 1.711 3.839 36.20 36.20 0.00 180.00  
DATACENTER_TOP_ZN_6_CEILING DROPCEILING 0.30 2.031 4.488 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_WALL_EAST INT_WALL 0.30 2.511 6.299 118.87 118.87 90.00 90.00 E
DATACENTER_BASEMENT_ZN_6_FLOOR EXT_SLAB_8IN_WITH_CARPET 0.30 1.591 3.285 783.68 783.68 0.00 180.00  
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 36.20 36.20 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 INT_SLAB_CEILING 0.30 1.887 3.839 419.35 419.35 180.00 0.00  
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER INT_SLAB_CEILING 0.30 1.887 3.839 201.98 201.98 135.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 INT_SLAB_CEILING 0.30 1.887 3.839 63.08 63.08 180.00 0.00  
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 INT_SLAB_CEILING 0.30 1.887 3.839 63.07 63.07 180.00 0.00  
BASEMENT_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 7126.21   0.00 90.00 N
CORE_BOTTOM_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
CORE_MID_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 50646.53   0.00 90.00 N
CORE_TOP_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 5064.65   0.00 90.00 N
PERIMETER_BOT_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_BOT_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_BOT_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_BOT_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_MID_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.26   0.00 90.00 N
PERIMETER_MID_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.50   0.00 90.00 N
PERIMETER_MID_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 6268.35   0.00 90.00 N
PERIMETER_MID_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 4039.48   0.00 90.00 N
PERIMETER_TOP_ZN_3_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.83   0.00 90.00 N
PERIMETER_TOP_ZN_2_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N
PERIMETER_TOP_ZN_1_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 626.84   0.00 90.00 N
PERIMETER_TOP_ZN_4_INTERNALMASS_1 INTERIORFURNISHINGS 0.30   0.800 403.95   0.00 90.00 N


Exterior Fenestration

Construction Frame and Divider Glass Area [m2] Frame Area [m2] Divider Area [m2] Area of One Opening [m2] Area of Multiplied Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance Frame Conductance [W/m2-K] Divider Conductance [W/m2-K] NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 WINDOW_U_0.5047_SHGC_NORTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 WINDOW_U_0.5047_SHGC_EAST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 WINDOW_U_0.5047_SHGC_SOUTH_0.25   17.38 0.00 0.00 17.38 17.38 2.869 0.251 0.251             No PERIMETER_BOT_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 WINDOW_U_0.5047_SHGC_WEST_0.25   19.32 0.00 0.00 19.32 19.32 2.869 0.251 0.251             No PERIMETER_BOT_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.5047_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 869.21 2.869 0.251 0.251             No PERIMETER_MID_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.5047_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 579.48 2.869 0.251 0.251             No PERIMETER_MID_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.5047_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 869.21 2.869 0.251 0.251             No PERIMETER_MID_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.5047_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 579.48 2.869 0.251 0.251             No PERIMETER_MID_ZN_4_WALL_WEST 270.00 90.00 W
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW WINDOW_U_0.5047_SHGC_NORTH_0.25   86.92 0.00 0.00 86.92 86.92 2.869 0.251 0.251             No PERIMETER_TOP_ZN_3_WALL_NORTH 0.00 90.00 N
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW WINDOW_U_0.5047_SHGC_EAST_0.25   57.95 0.00 0.00 57.95 57.95 2.869 0.251 0.251             No PERIMETER_TOP_ZN_2_WALL_EAST 90.00 90.00 E
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW WINDOW_U_0.5047_SHGC_SOUTH_0.25   86.92 0.00 0.00 86.92 86.92 2.869 0.251 0.251             No PERIMETER_TOP_ZN_1_WALL_SOUTH 180.00 90.00 S
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW WINDOW_U_0.5047_SHGC_WEST_0.25   57.95 0.00 0.00 57.95 57.95 2.869 0.251 0.251             No PERIMETER_TOP_ZN_4_WALL_WEST 270.00 90.00 W
Total or Average             3476.85 2.869 0.251 0.251                      
North Total or Average             1043.06 2.869 0.251 0.251                      
Non-North Total or Average             2433.80 2.869 0.251 0.251                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [W/m2-K] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [m2] Area of Openings [m2] Glass U-Factor [W/m2-K] Glass SHGC Glass Visible Transmittance
Total or Average     0.00 - - -


Exterior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_3_WALL_NORTH
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_2_WALL_EAST
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_1_WALL_SOUTH
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 SWINGING DOOR_CON 2.281 3.464 1.95 PERIMETER_BOT_ZN_4_WALL_WEST


Interior Door

Construction U-Factor with Film [W/m2-K] U-Factor no Film [W/m2-K] Gross Area [m2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW 0.00 0.00 0.00 1.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW 1.00 1.00 0.00 1.00 1.00 0.00 1.00 1.00 0.00
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW 1.00 1.00 1.00 0.00 1.00 1.00 1.00 1.00 1.00
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW 0.00 0.00 1.00 0.00 0.00 1.00 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
None          



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [W/m2] Space Area [m2] Total Power [W] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [GJ]
BASEMENT_LIGHTS BASEMENT BASEMENT GENERAL 7.6202 2779.43 21179.74 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 177.74
CORE_BOTTOM_LIGHTS CORE_BOTTOM CORE_BOTTOM GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
CORE_MID_LIGHTS CORE_MID CORE_MID GENERAL 7.6202 24961.20 190208.95 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 1596.24
CORE_TOP_LIGHTS CORE_TOP CORE_TOP GENERAL 7.6202 2496.12 19020.89 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 159.62
PERIMETER_BOT_ZN_3_LIGHTS PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.71 0.0000 Y 13.77
PERIMETER_BOT_ZN_2_LIGHTS PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.65 0.0000 Y 8.86
PERIMETER_BOT_ZN_1_LIGHTS PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.46 0.0000 Y 13.66
PERIMETER_BOT_ZN_4_LIGHTS PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.64 0.0000 Y 8.85
PERIMETER_MID_ZN_3_LIGHTS PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3 GENERAL 7.6202 3134.13 23882.63 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.75 0.0000 Y 137.84
PERIMETER_MID_ZN_2_LIGHTS PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.66 0.0000 Y 88.58
PERIMETER_MID_ZN_1_LIGHTS PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1 GENERAL 7.6202 3134.20 23883.15 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.48 0.0000 Y 136.65
PERIMETER_MID_ZN_4_LIGHTS PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4 GENERAL 7.6202 2019.75 15390.88 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.66 0.0000 Y 88.58
PERIMETER_TOP_ZN_3_LIGHTS PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3 GENERAL 7.6202 313.41 2388.26 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.75 0.0000 Y 13.78
PERIMETER_TOP_ZN_2_LIGHTS PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.66 0.0000 Y 8.86
PERIMETER_TOP_ZN_1_LIGHTS PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1 GENERAL 7.6202 313.42 2388.32 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.48 0.0000 Y 13.67
PERIMETER_TOP_ZN_4_LIGHTS PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4 GENERAL 7.6202 201.98 1539.09 LightsWired LTG_SCH_OFFICE 45.89 168.00 30.66 0.0000 Y 8.86
DATACENTER_BASEMENT_LIGHTS DATACENTER_BASEMENT_ZN_6 DATACENTER_BASEMENT_ZN_6 GENERAL 7.6202 783.68 5971.78 LightsWired LTG_SCH_OFFICE 45.89 168.00 44.71 0.0000 Y 50.12
DATACENTER_BOT_LIGHTS DATACENTER_BOT_ZN_6 DATACENTER_BOT_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
DATACENTER_MID_LIGHTS DATACENTER_MID_ZN_6 DATACENTER_MID_ZN_6 GENERAL 12.5114 362.03 4529.48 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 46.40
DATACENTER_TOP_LIGHTS DATACENTER_TOP_ZN_6 DATACENTER_TOP_ZN_6 GENERAL 12.5114 36.20 452.95 LightsWired LTG_SCH_DATACENTER 56.02 168.00 54.57 0.0000 Y 4.64
Interior Lighting Total       7.6661 46320.38 355094.67               856.11


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [W] Lighting Controlled [W]
PERIMETER_BOT_ZN_1_DAYLREFPT1 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_BOT_ZN_1_DAYLREFPT2 PERIMETER_BOT_ZN_1 PERIMETER_BOT_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_BOT_ZN_2_DAYLREFPT1 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_2_DAYLREFPT2 PERIMETER_BOT_ZN_2 PERIMETER_BOT_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_BOT_ZN_3_DAYLREFPT1 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_BOT_ZN_3_DAYLREFPT2 PERIMETER_BOT_ZN_3 PERIMETER_BOT_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_BOT_ZN_4_DAYLREFPT1 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_BOT_ZN_4_DAYLREFPT2 PERIMETER_BOT_ZN_4 PERIMETER_BOT_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_1_DAYLREFPT1 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_MID_ZN_1_DAYLREFPT2 PERIMETER_MID_ZN_1 PERIMETER_MID_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_MID_ZN_2_DAYLREFPT1 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_2_DAYLREFPT2 PERIMETER_MID_ZN_2 PERIMETER_MID_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_MID_ZN_3_DAYLREFPT1 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_MID_ZN_3_DAYLREFPT2 PERIMETER_MID_ZN_3 PERIMETER_MID_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_MID_ZN_4_DAYLREFPT1 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_MID_ZN_4_DAYLREFPT2 PERIMETER_MID_ZN_4 PERIMETER_MID_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_1_DAYLREFPT1 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.32 921.17
PERIMETER_TOP_ZN_1_DAYLREFPT2 PERIMETER_TOP_ZN_1 PERIMETER_TOP_ZN_1_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.32 0.00
PERIMETER_TOP_ZN_2_DAYLREFPT1 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_2_DAYLREFPT2 PERIMETER_TOP_ZN_2 PERIMETER_TOP_ZN_2_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00
PERIMETER_TOP_ZN_3_DAYLREFPT1 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.39 2388.26 921.15
PERIMETER_TOP_ZN_3_DAYLREFPT2 PERIMETER_TOP_ZN_3 PERIMETER_TOP_ZN_3_DAYLCTRL SplitFlux Continuous/Off 0.00 2388.26 0.00
PERIMETER_TOP_ZN_4_DAYLREFPT1 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.39 1539.09 593.63
PERIMETER_TOP_ZN_4_DAYLREFPT2 PERIMETER_TOP_ZN_4 PERIMETER_TOP_ZN_4_DAYLCTRL SplitFlux Continuous/Off 0.00 1539.09 0.00


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [GJ]
EXTERIOR_LIGHTS_A 9973.05 AstronomicalClock -   41.73 41.73 78.11
EXTERIOR_LIGHTS_B 27638.03 AstronomicalClock -   83.73 71.13 369.00
Exterior Lighting Total 37611.08           447.11



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Central Plant

Type Reference Capacity [W] Reference Efficiency [W/W] Rated Capacity [W] Rated Efficiency [W/W] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
BYPASS HEAT EXCHANGER HeatExchanger:FluidToFluid 3034146.19          
HEATSYS1 BOILER Boiler:HotWater 1569748.75 0.81        
COOLSYS1 CHILLER1 Chiller:Electric:ReformulatedEIR 1543939.29 6.28 1477742.28 5.98 6.84 23.33
COOLSYS1 CHILLER2 Chiller:Electric:ReformulatedEIR 1543939.29 6.28 1477742.28 5.98 6.84 23.33
CENTRAL TOWER FluidCooler:TwoSpeed 582060.00          
CENTRAL BOILER Boiler:HotWater 537788.84 0.80        
TOWERWATERSYS COOLTOWER 1 CoolingTower:VariableSpeed 1831858.06          
TOWERWATERSYS COOLTOWER 2 CoolingTower:VariableSpeed 1831858.06          


Cooling Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Sensible Capacity [W] Nominal Latent Capacity [W] Nominal Sensible Heat Ratio Nominal Efficiency [W/W] Nominal Coil UA Value [W/C] Nominal Coil Surface Area [m2]
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water 247829.88 246350.29 166037.70 80312.59 0.67 - 25674.37 260.40
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water 2420734.69 2324475.12 1557559.90 766915.21 0.67 - 243261.58 2467.29
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water 245566.35 245446.72 165579.17 79867.55 0.67 - 25572.17 259.37
CAV_BAS COOLING COIL Coil:Cooling:Water 127008.98 139490.03 96230.52 43259.51 0.69 - 14218.79 144.21
AIRLOOP DATACENTER BASEMENT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   434337.82 312325.51 122012.31 0.72 0.00    
AIRLOOP DATACENTER BOT COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9501.30 6820.69 2680.62 0.72 0.00    
AIRLOOP DATACENTER MID COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   90544.49 64905.21 25639.27 0.72 0.00    
AIRLOOP DATACENTER TOP COOLING COIL Coil:Cooling:WaterToAirHeatPump:EquationFit   9227.99 6617.53 2610.47 0.72 0.00    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [W] Standard Rated Net COP [W/W] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
None              


DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [W] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [W] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [W] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [W] Rated Electric Power Test D [W]
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [W] Low Temperature Heating (net) Rating Capacity [W] HSPF [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [W] Nominal Total Capacity [W] Nominal Efficiency [W/W]
CORE_BOTTOM VAV BOX REHEAT COIL Coil:Heating:Water 19004.94 18020.38 -
CORE_MID VAV BOX REHEAT COIL Coil:Heating:Water 368521.24 349236.22 -
CORE_TOP VAV BOX REHEAT COIL Coil:Heating:Water 61690.93 58416.50 -
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 5654.10 5356.82 -
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 4326.48 4099.13 -
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 7343.12 6953.99 -
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 3453.00 3273.46 -
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 147829.41 140070.62 -
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 98605.52 93429.65 -
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 146866.25 139158.19 -
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 87523.00 82930.64 -
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL Coil:Heating:Water 19765.21 18726.72 -
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL Coil:Heating:Water 13050.70 12364.94 -
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL Coil:Heating:Water 19657.69 18624.88 -
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL Coil:Heating:Water 12217.78 11575.92 -
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water 26182.45 22237.61 -
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water 246020.64 208610.62 -
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water 23750.39 20368.63 -
CAV_BAS HEATING COIL Coil:Heating:Water 258285.90 209415.47 -
AIRLOOP DATACENTER BASEMENT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   434337.82 0.00
AIRLOOP DATACENTER BOT HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9501.30 0.00
AIRLOOP DATACENTER MID HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   90544.49 0.00
AIRLOOP DATACENTER TOP HEATING COIL Coil:Heating:WaterToAirHeatPump:EquationFit   9227.99 0.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric   14482.89 1.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric   669.05 1.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric   6690.49 1.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric   669.05 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [W/W] Delta Pressure [pa] Max Air Flow Rate [m3/s] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-s/m3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
VAV_BOT WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.94 19322.59 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_MID WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 82.72 178751.49 2160.95 1.00 1.08 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00
VAV_TOP WITH REHEAT FAN Fan:VariableVolume 0.61 1314.72 8.94 19309.67 2160.95 1.00 1.12 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00
CAV_BAS FAN Fan:ConstantVolume 0.60 1018.41 5.48 9290.26 1695.65 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 0.61 1018.41 21.33 35369.70 1657.97 1.00 1.13 General TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00
AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.56 622.50 0.47 521.61 1120.11 1.00 1.64 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 0.56 622.50 4.43 4957.19 1120.11 1.00 1.16 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00
AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.56 622.50 0.45 505.60 1120.11 1.00 1.65 General TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00


Pumps

Type Control Head [pa] Water Flow [m3/s] Electricity Rate [W] Power Per Water Flow Rate [W-s/m3] Motor Efficiency [W/W] End Use Subcategory
COOLSYS1 PUMP SECONDARY Pump:VariableSpeed Intermittent 133527.72 0.129377 26659.83 206062.94 0.90 General
HEATSYS1 PUMP Pump:VariableSpeed Intermittent 180705.70 0.013733 4135.73 301156.09 0.90 General
COOLSYS1 PUMP Pump:ConstantSpeed Intermittent 92445.74 0.129377 18457.50 142664.32 0.90 General
PLANT CIRC PUMP Pump:ConstantSpeed Intermittent 179045.11 0.013313 3395.48 255050.01 0.90 General
SWHSYS1 PUMP Pump:ConstantSpeed Intermittent 3168.45 0.000440 5.96 13540.37 0.30 General
TOWERWATERSYS PUMP HeaderedPumps:VariableSpeed Intermittent 180718.98 0.152808 46022.34 301178.23 0.90 General


Service Water Heating

Type Storage Volume [m3] Input [W] Thermal Efficiency [W/W] Recovery Efficiency [W/W] Energy Factor
SWHSYS1 WATER HEATER WaterHeater:Mixed 1.14 87921.32 0.80 0.50 0.08



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Zone Sensible Cooling

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 76041.58 76041.58 27.36 5.479 5.479 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00896 28.05 0.01653 1.200 0.00
CORE_BOTTOM 78274.25 78274.25 31.36 5.639 5.639 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00890 28.05 0.01653 1.078 0.00
CORE_MID 733090.75 733090.75 293.69 52.798 52.798 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00893 28.05 0.01653 10.778 0.00
CORE_TOP 72622.80 72622.80 29.09 5.230 5.230 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 24.00 24.00 0.00893 28.05 0.01653 1.078 0.00
PERIMETER_BOT_ZN_3 12489.89 12489.89 39.85 0.908 0.908 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:50:00 24.00 24.00 0.00895 33.90 0.01654 0.135 0.00
PERIMETER_BOT_ZN_2 12778.37 12778.37 63.27 0.929 0.929 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:40:00 24.00 24.00 0.00879 30.45 0.01653 0.087 0.00
PERIMETER_BOT_ZN_1 15118.40 15118.40 48.24 1.099 1.099 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:40:00 24.00 24.00 0.00887 33.77 0.01654 0.135 0.00
PERIMETER_BOT_ZN_4 16449.13 16449.13 81.44 1.196 1.196 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00872 32.79 0.01653 0.087 0.00
PERIMETER_MID_ZN_3 115832.28 115832.28 369.58 8.424 8.424 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 24.00 24.00 0.00918 33.90 0.01654 1.353 0.00
PERIMETER_MID_ZN_2 130468.12 130468.12 645.96 9.488 9.488 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 24.00 24.00 0.00891 30.67 0.01653 0.872 0.00
PERIMETER_MID_ZN_1 142290.73 142290.73 453.99 10.348 10.348 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 24.00 24.00 0.00906 33.83 0.01654 1.353 0.00
PERIMETER_MID_ZN_4 138251.92 138251.92 684.50 10.054 10.054 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 24.00 24.00 0.00888 32.66 0.01653 0.872 0.00
PERIMETER_TOP_ZN_3 13303.13 13303.13 42.45 0.967 0.967 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:10:00 24.00 24.00 0.00917 33.82 0.01654 0.135 0.00
PERIMETER_TOP_ZN_2 13327.86 13327.86 65.99 0.969 0.969 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:10:00 24.00 24.00 0.00895 31.10 0.01653 0.087 0.00
PERIMETER_TOP_ZN_1 15886.02 15886.02 50.69 1.155 1.155 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:20:00 24.00 24.00 0.00906 33.90 0.01654 0.135 0.00
PERIMETER_TOP_ZN_4 14995.23 14995.23 74.24 1.091 1.091 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 24.00 24.00 0.00890 32.79 0.01653 0.087 0.00
DATACENTER_BOT_ZN_6 8120.36 8120.36 224.30 0.466 0.466 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:20:00 27.00 27.00 0.00850 26.05 0.01652 0.016 0.00
DATACENTER_MID_ZN_6 77163.21 77163.21 2131.42 4.426 4.426 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.156 0.00
DATACENTER_TOP_ZN_6 7870.20 7870.20 217.39 0.451 0.451 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 27.00 27.00 0.00859 31.21 0.01653 0.016 0.00
DATACENTER_BASEMENT_ZN_6 371959.73 371959.73 474.63 21.333 21.333 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:00:00 27.00 27.00 0.00854 26.71 0.01652 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [W] User Design Load [W] User Design Load per Area [W/m2] Calculated Design Air Flow [m3/s] User Design Air Flow [m3/s] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [C] Indoor Temperature at Peak Load [C] Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Outdoor Temperature at Peak Load [C] Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] Minimum Outdoor Air Flow Rate [m3/s] Heat Gain Rate from DOAS [W]
BASEMENT 0.00 0.00 0.00 0.000 1.200   00:10:00 15.60 25.28 0.00526 4.60 0.00526 1.200 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.000 1.078   00:10:00 15.60 22.87 0.00526 4.60 0.00526 1.078 0.00
CORE_MID 183142.70 183142.70 73.37 7.674 10.778 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 10.778 0.00
CORE_TOP 42695.79 42695.79 17.10 1.810 1.810 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00800 4.60 0.00526 1.078 0.00
PERIMETER_BOT_ZN_3 3273.41 3273.41 10.44 0.138 0.138 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00711 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_2 2459.77 2459.77 12.18 0.104 0.104 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00720 4.60 0.00526 0.087 0.00
PERIMETER_BOT_ZN_1 4957.08 4957.08 15.82 0.210 0.210 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00738 4.60 0.00526 0.135 0.00
PERIMETER_BOT_ZN_4 1052.25 1052.25 5.21 0.045 0.087 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00668 4.60 0.00526 0.087 0.00
PERIMETER_MID_ZN_3 103514.35 103514.35 330.28 4.408 4.408 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00764 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_2 69043.47 69043.47 341.84 2.941 2.941 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00766 4.60 0.00526 0.872 0.00
PERIMETER_MID_ZN_1 102840.95 102840.95 328.13 4.380 4.380 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00764 4.60 0.00526 1.353 0.00
PERIMETER_MID_ZN_4 61294.70 61294.70 303.48 2.610 2.610 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00757 4.60 0.00526 0.872 0.00
PERIMETER_TOP_ZN_3 13834.65 13834.65 44.14 0.590 0.590 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_2 9134.60 9134.60 45.23 0.389 0.389 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 4.60 0.00526 0.087 0.00
PERIMETER_TOP_ZN_1 13759.49 13759.49 43.90 0.587 0.587 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00776 4.60 0.00526 0.135 0.00
PERIMETER_TOP_ZN_4 8552.36 8552.36 42.34 0.365 0.365 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 21.00 21.00 0.00773 4.60 0.00526 0.087 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.016 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.000 0.156   00:10:00 18.00 24.95 0.00797 4.60 0.00526 0.156 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.000 0.016   00:10:00 18.00 24.02 0.00549 4.60 0.00526 0.016 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.000 0.338   00:10:00 18.00 27.00 0.00850 4.60 0.00526 0.338 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [m3/s] User cooling [m3/s] Calculated heating [m3/s] User heating [m3/s] Adjusted cooling [m3/s] Adjusted heating [m3/s] Adjusted main [m3/s] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
VAV_BOT WITH REHEAT 8.94 8.94 1.62 1.62 8.9417 2.7887 8.9417 0.3119 0.3000
VAV_MID WITH REHEAT 82.72 82.72 25.12 25.12 82.7191 26.9693 82.7191 0.3260 0.3000
VAV_TOP WITH REHEAT 8.94 8.94 3.74 3.74 8.9357 3.7405 8.9357 0.4186 0.3000
CAV_BAS 5.48 5.48 1.20 1.20 5.4789 5.4789 5.4789 1.0000 1.0000
AIRLOOP DATACENTER BASEMENT 21.33 21.33 0.34 0.34 21.3331 21.3329 21.3331 1.0000 1.0000
AIRLOOP DATACENTER BOT 0.47 0.47 0.02 0.02 0.4657 0.4657 0.4657 1.0000 1.0000
AIRLOOP DATACENTER MID 4.43 4.43 0.16 0.16 4.4256 4.4256 4.4256 1.0000 1.0000
AIRLOOP DATACENTER TOP 0.45 0.45 0.02 0.02 0.4514 0.4514 0.4514 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [m3/s] Algorithm Volume Flow Rate [m3/s] Coincident Design Volume Flow Rate [m3/s] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX 19004.937 19004.937 1.889076 0.00016626 383.125   1/21 00:10:00   1/21 00:10:00 19004.94 19004.94 1.889076 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 0.00 0.00 19075.01 19075.01
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX 368521.244 368521.244 18.426480 0.00322398 8236.549 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 368521.24 368521.24 18.426480 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 183142.70 0.00 369784.63 369784.63
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX 61690.929 61690.929 1.888102 0.00053970 1609.031 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 61690.93 61690.93 1.888102 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00800000 51.6744 42695.79 0.00 61879.53 61879.53
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX 5654.098 5654.098 0.237053 0.00004946 132.029 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 5654.10 5654.10 0.237053 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00710692 45.9738 3273.41 0.00 5672.69 5672.69
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX 4326.478 4326.478 0.185845 0.00003785 100.356 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 4326.48 4326.48 0.185845 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00719888 46.5621 2459.77 0.00 4340.76 4340.76
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX 7343.115 7343.115 0.237468 0.00006424 187.124 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 7343.12 7343.12 0.237468 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00738152 47.7294 4957.08 0.00 7365.78 7365.78
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX 3453.003 3453.003 0.239230 0.00003021 72.729 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 3453.00 3453.00 0.239230 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00667577 43.2134 1052.25 0.00 3465.48 3465.48
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX 147829.410 147829.410 4.408361 0.00129328 3900.550 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 147829.41 147829.41 4.408361 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00764445 49.4092 103514.35 0.00 148328.09 148328.09
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX 98605.522 98605.522 2.940693 0.00086264 2601.666 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 98605.52 98605.52 2.940693 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00765689 49.4886 69043.47 0.00 98937.52 98937.52
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX 146866.255 146866.255 4.379573 0.00128485 3875.163 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 146866.25 146866.25 4.379573 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00764032 49.3828 102840.95 0.00 147361.87 147361.87
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX 87523.003 87523.003 2.609522 0.00076569 2309.525 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 87523.00 87523.00 2.609522 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00757209 48.9476 61294.70 0.00 87819.60 87819.60
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX 19765.206 19765.206 0.589819 0.00017291 521.349 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19765.21 19765.21 0.589819 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00775967 50.1441 13834.65 0.00 19830.69 19830.69
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX 13050.699 13050.699 0.389472 0.00011417 344.231 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 13050.70 13050.70 0.389472 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00776160 50.1565 9134.60 0.00 13093.87 13093.87
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX 19657.691 19657.691 0.586603 0.00017197 518.516 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 19657.69 19657.69 0.586603 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00775753 50.1305 13759.49 0.00 19722.84 19722.84
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX 12217.775 12217.775 0.364566 0.00010689 322.281 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 12217.78 12217.78 0.364566 12.80 11.59 0.00800000 40.00 21.17 0.00800000 4.60 0.00525715 4.60 0.0000 21.00 0.00772955 49.9521 8552.36 0.00 12258.34 12258.34
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_BOT WITH REHEAT 247829.882 -999.000 8.941724 0.01054326 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 247829.88 172633.37 8.941724 26.93 19.52 0.01117472 11.05 11.05 0.00850000 33.90 0.01653638 25.13 28.3859 24.00 0.00891574 47.9268 117750.75 0.00 248209.30 168596.78
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_BOT WITH REHEAT 26182.451 26182.451 2.682517 0.00022906 452.913 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 26182.45 26182.45 2.682517 4.73 4.71 0.00529132 12.80 11.59 0.00800000 4.60 0.00525715 4.60 94.6197 21.96 0.00617385 37.7135 11742.51 0.00 26920.67 26920.67
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_MID WITH REHEAT 2420734.695 -999.000 82.719065 0.10298365 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 2420734.69 1632276.66 82.719065 27.29 19.91 0.01153489 11.05 11.05 0.00850000 33.90 0.01653638 25.13 30.6845 24.00 0.00904016 48.5870 1048802.15 0.00 2423637.37 1599968.41
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_MID WITH REHEAT 246020.642 246020.642 24.815719 0.00215230 4252.083 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 246020.64 246020.64 24.815719 4.60 4.60 0.00525715 12.80 11.59 0.00800000 4.60 0.00525715 4.60 102.2817 21.00 0.00776067 50.1499 519836.16 0.00 252541.00 252541.00
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoopHVAC VAV_TOP WITH REHEAT 245566.353 -999.000 8.935743 0.01044696 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 245566.35 171304.97 8.935743 26.82 19.47 0.01114288 11.05 11.05 0.00850000 33.90 0.01653638 25.13 28.4049 24.00 0.00899056 48.3245 122368.39 0.00 245939.19 167231.14
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoopHVAC VAV_TOP WITH REHEAT 23750.386 23750.386 2.680723 0.00020778 412.954 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 13:00:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 23750.39 23750.39 2.680723 5.47 5.23 0.00539518 12.80 11.59 0.00800000 4.60 0.00525715 4.60 94.6830 21.00 0.00785329 50.7399 59135.00 0.00 24658.51 24658.51
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoopHVAC CAV_BAS 127008.982 -999.000 5.478862 0.00540326 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 127008.98 91034.07 5.478862 25.00 18.47 0.01062400 11.42 11.42 0.00850000 28.55 0.01652632 23.72 21.9052 24.00 0.00895956 48.1587 75031.25 0.00 127162.48 88610.75
CAV_BAS HEATING COIL Coil:Heating:Water AirLoopHVAC CAV_BAS 258285.902 258285.902 5.478862 0.00225960 5860.879 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 258285.90 258285.90 5.478862 1.01 1.01 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 21.9052 25.28 0.00525715 26.3315 0.00 0.00 221550.43 221550.43
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 434337.817 312325.506 21.333099 0.01063691 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 406947.05 397013.16 -999.0 28.51 18.07 0.00866922 12.80 12.09 0.00850000 33.90 0.01653638 25.13 -999.0000 27.00 0.00854225 38.4505 371459.76 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9501.305 6820.687 0.465681 0.00023269 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:20:00 8904.61 8448.66 -999.0 28.09 18.08 0.00885599 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00858924 38.6568 8115.11 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90544.486 64905.212 4.425639 0.00221743 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 84897.54 80341.80 -999.0 28.09 18.10 0.00887421 12.80 12.09 0.00850000 31.21 0.01653132 24.43 -999.0000 27.00 0.00859384 38.6775 77163.21 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9227.993 6617.526 0.451387 0.00022599 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 8651.41 8195.83 -999.0 28.10 18.09 0.00886692 12.80 12.09 0.00850000 31.41 0.01653169 24.48 -999.0000 27.00 0.00859193 38.6689 7869.54 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BASEMENT 434337.817 434337.817 21.333099 0.01063691 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 434337.82 434337.82 21.333099 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 1.5862 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER BOT 9501.305 9501.305 0.465681 0.00023269 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9501.30 9501.30 0.465681 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.3569 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER MID 90544.486 90544.486 4.425639 0.00221743 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 90544.49 90544.49 4.425639 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5322 24.95 0.00796561 40.5098 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoopHVAC AIRLOOP DATACENTER TOP 9227.993 9227.993 0.451387 0.00022599 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 9227.99 9227.99 0.451387 4.60 4.60 0.00525715 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4632 24.02 0.00548951 29.6249 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BASEMENT 14482.888 14482.888 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 14482.89 14482.89 21.333099 0.07 0.07 0.00844856 40.00 21.17 0.00800000 4.60 0.00525715 4.60 1.5862 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER BOT 669.049 669.049 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.05 669.05 0.465681 0.15 0.15 0.00839114 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.3569 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER MID 6690.494 6690.494 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 6690.49 6690.49 4.425639 0.16 0.16 0.00786994 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.5322 24.95 0.00796561 40.5098 0.00 0.00 -999.00 -999.00
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoopHVAC AIRLOOP DATACENTER TOP 669.049 669.049 -999.0 -999.0 -999.000 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 669.05 669.05 0.451387 0.16 0.16 0.00548147 40.00 21.17 0.00800000 4.60 0.00525715 4.60 3.4632 24.02 0.00548951 29.6249 0.00 0.00 -999.00 -999.00



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [W] Coil Final Gross Sensible Capacity [W] Coil Final Reference Air Volume Flow Rate [m3/s] Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] Coil U-value Times Area Value [W/K] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [J/kg-K] Dry Air Heat Capacity [J/kg-K] Standard Air Density Adjusted for Elevation [kg/m3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [m3/s] Supply Fan Maximum Air Mass Flow Rate [kg/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [J/kg-K] Plant Fluid Density [kg/m3] Plant Maximum Fluid Mass Flow Rate [kg/s] Plant Design Fluid Return Temperature [C] Plant Design Fluid Supply Temperature [C] Plant Design Fluid Temperature Difference [deltaC] Plant Design Capacity [W] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [W] Coil Sensible Capacity at Ideal Loads Peak [W] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] Coil Entering Air Drybulb at Ideal Loads Peak [C] Coil Entering Air Wetbulb at Ideal Loads Peak [C] Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Leaving Air Drybulb at Ideal Loads Peak [C] Coil Leaving Air Wetbulb at Ideal Loads Peak [C] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] Supply Fan Air Heat Gain at Ideal Loads Peak [W] Coil and Fan Net Total Capacity at Ideal Loads Peak [W] Outdoor Air Drybulb at Ideal Loads Peak [C] Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [C] Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [C] System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Drybulb at Ideal Loads Peak [C] Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [W] Zone Latent Heat Gain at Ideal Loads Peak [W] Coil Total Capacity at Rating Conditions [W] Coil Sensible Capacity at Rating Conditions [W] Coil Air Mass Flow Rate at Rating Conditions [kg/s] Coil Entering Air Drybulb at Rating Conditions [C] Coil Entering Air Wetbulb at Rating Conditions [C] Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] Coil Leaving Air Drybulb at Rating Conditions [C] Coil Leaving Air Wetbulb at Rating Conditions [C] Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K]
CORE_BOTTOM VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_BOTTOM VAV BOX CORE_BOTTOM N/A N/A N/A Yes Yes Yes No 19004.937 19004.937 1.889076 0.00016626 383.125 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 1.1868 1.210699   1/21 00:10:00 unknown unknown   1/21 00:10:00 Sensible 19004.94 19004.94 1.0000 2.27287324 1.889076 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.16624652 60.00 32.22 27.78 0.000 19004.94 4.60 0.00525715 4.60 0.00000000 0.0000 21.00 0.00800000 21.00 0.00800000 51.6744 0.00 0.00 19075.01 19075.01 2.27287324 12.80 11.60 0.00800000 33059.8 21.03 14.86 0.00800000 41452.3
CORE_MID VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_MID VAV BOX CORE_MID N/A N/A N/A Yes Yes Yes No 368521.244 368521.244 18.426480 0.00322398 8236.549 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 23.0133 23.476448 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 368521.24 368521.24 1.0000 22.17013120 18.426480 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 3.22365573 60.00 32.22 27.78 0.000 368521.24 4.60 0.00525715 4.60 0.00000000 0.0000 20.57 0.00800000 21.00 0.00800000 51.6744 183142.70 0.00 369784.63 369784.63 22.17013120 12.80 11.60 0.00800000 33059.8 29.16 17.75 0.00800000 49739.2
CORE_TOP VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT CORE_TOP VAV BOX CORE_TOP N/A N/A N/A Yes Yes Yes No 61690.929 61690.929 1.888102 0.00053970 1609.031 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 3.8525 3.929987 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 61690.93 61690.93 1.0000 2.27170139 1.888102 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.53964410 60.00 32.22 27.78 0.000 61690.93 4.60 0.00525715 4.60 0.00000000 0.0000 20.86 0.00800000 21.00 0.00800000 51.6744 42695.79 0.00 61879.53 61879.53 2.27170139 12.80 11.60 0.00800000 33059.8 39.51 21.04 0.00800000 60299.1
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_3 VAV BOX PERIMETER_BOT_ZN_3 N/A N/A N/A Yes Yes Yes No 5654.098 5654.098 0.237053 0.00004946 132.029 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 0.3531 0.360191 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 5654.10 5654.10 1.0000 0.28521482 0.237053 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.04945947 60.00 32.22 27.78 0.000 5654.10 4.60 0.00525715 4.60 0.00000000 0.0000 20.87 0.00710692 21.00 0.00710692 45.9738 3273.41 0.00 5672.69 5672.69 0.28521482 12.80 11.60 0.00800000 33059.8 32.30 18.80 0.00800000 52949.0
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_2 VAV BOX PERIMETER_BOT_ZN_2 N/A N/A N/A Yes Yes Yes No 4326.478 4326.478 0.185845 0.00003785 100.356 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 0.2702 0.275616 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 4326.48 4326.48 1.0000 0.22360230 0.185845 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.03784605 60.00 32.22 27.78 0.000 4326.48 4.60 0.00525715 4.60 0.00000000 0.0000 20.87 0.00719888 21.00 0.00719888 46.5621 2459.77 0.00 4340.76 4340.76 0.22360230 12.80 11.60 0.00800000 33059.8 31.84 18.64 0.00800000 52472.7
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_1 VAV BOX PERIMETER_BOT_ZN_1 N/A N/A N/A Yes Yes Yes No 7343.115 7343.115 0.237468 0.00006424 187.124 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 0.4586 0.467789 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 7343.12 7343.12 1.0000 0.28571408 0.237468 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.06423422 60.00 32.22 27.78 0.000 7343.12 4.60 0.00525715 4.60 0.00000000 0.0000 20.86 0.00738152 21.00 0.00738152 47.7294 4957.08 0.00 7365.78 7365.78 0.28571408 12.80 11.60 0.00800000 33059.8 38.08 20.61 0.00800000 58840.1
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_BOT_ZN_4 VAV BOX PERIMETER_BOT_ZN_4 N/A N/A N/A Yes Yes Yes No 3453.003 3453.003 0.239230 0.00003021 72.729 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 0.2156 0.219972 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 3453.00 3453.00 1.0000 0.28783346 0.239230 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.03020530 60.00 32.22 27.78 0.000 3453.00 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00667577 21.00 0.00667577 43.2134 1052.25 0.00 3465.48 3465.48 0.28783346 12.80 11.60 0.00800000 33059.8 24.61 16.17 0.00800000 45099.7
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_3 VAV BOX PERIMETER_MID_ZN_3 N/A N/A N/A Yes Yes Yes No 147829.410 147829.410 4.408361 0.00129328 3900.550 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 9.2316 9.417393 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 147829.41 147829.41 1.0000 5.30399358 4.408361 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.29314424 60.00 32.22 27.78 0.000 147829.41 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00764445 21.00 0.00764445 49.4092 103514.35 0.00 148328.09 148328.09 5.30399358 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61025.2
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_2 VAV BOX PERIMETER_MID_ZN_2 N/A N/A N/A Yes Yes Yes No 98605.522 98605.522 2.940693 0.00086264 2601.666 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 6.1577 6.281612 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 98605.52 98605.52 1.0000 3.53814431 2.940693 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.86255613 60.00 32.22 27.78 0.000 98605.52 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00765689 21.00 0.00765689 49.4886 69043.47 0.00 98937.52 98937.52 3.53814431 12.80 11.60 0.00800000 33059.8 40.22 21.25 0.00800000 61022.9
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_1 VAV BOX PERIMETER_MID_ZN_1 N/A N/A N/A Yes Yes Yes No 146866.255 146866.255 4.379573 0.00128485 3875.163 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 9.1715 9.356036 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 146866.25 146866.25 1.0000 5.26935745 4.379573 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 1.28471900 60.00 32.22 27.78 0.000 146866.25 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00764032 21.00 0.00764032 49.3828 102840.95 0.00 147361.87 147361.87 5.26935745 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61025.6
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_MID_ZN_4 VAV BOX PERIMETER_MID_ZN_4 N/A N/A N/A Yes Yes Yes No 87523.003 87523.003 2.609522 0.00076569 2309.525 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 5.4656 5.575606 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 87523.00 87523.00 1.0000 3.13969091 2.609522 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.76561130 60.00 32.22 27.78 0.000 87523.00 4.60 0.00525715 4.60 0.00000000 0.0000 20.91 0.00757209 21.00 0.00757209 48.9476 61294.70 0.00 87819.60 87819.60 3.13969091 12.80 11.60 0.00800000 33059.8 40.23 21.25 0.00800000 61030.6
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_3 VAV BOX PERIMETER_TOP_ZN_3 N/A N/A N/A Yes Yes Yes No 19765.206 19765.206 0.589819 0.00017291 521.349 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 1.2343 1.259132 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19765.21 19765.21 1.0000 0.70965110 0.589819 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.17289701 60.00 32.22 27.78 0.000 19765.21 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00775967 21.00 0.00775967 50.1441 13834.65 0.00 19830.69 19830.69 0.70965110 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61004.1
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_2 VAV BOX PERIMETER_TOP_ZN_2 N/A N/A N/A Yes Yes Yes No 13050.699 13050.699 0.389472 0.00011417 344.231 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 0.8150 0.831388 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 13050.70 13050.70 1.0000 0.46859974 0.389472 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.11416156 60.00 32.22 27.78 0.000 13050.70 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00776160 21.00 0.00776160 50.1565 9134.60 0.00 13093.87 13093.87 0.46859974 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61002.4
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_1 VAV BOX PERIMETER_TOP_ZN_1 N/A N/A N/A Yes Yes Yes No 19657.691 19657.691 0.586603 0.00017197 518.516 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 1.2276 1.252283 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 19657.69 19657.69 1.0000 0.70578189 0.586603 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.17195652 60.00 32.22 27.78 0.000 19657.69 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00775753 21.00 0.00775753 50.1305 13759.49 0.00 19722.84 19722.84 0.70578189 12.80 11.60 0.00800000 33059.8 40.20 21.24 0.00800000 61004.5
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL COIL:HEATING:WATER Zone Equipment ZONEHVAC:AIRDISTRIBUTIONUNIT PERIMETER_TOP_ZN_4 VAV BOX PERIMETER_TOP_ZN_4 N/A N/A N/A Yes Yes Yes No 12217.775 12217.775 0.364566 0.00010689 322.281 1.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 0.7630 0.778327 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 12217.78 12217.78 1.0000 0.43863325 0.364566 12.80 11.59 0.00800000 33059.8 40.00 21.17 0.00800000 60796.0 0.10687552 60.00 32.22 27.78 0.000 12217.78 4.60 0.00525715 4.60 0.00000000 0.0000 20.95 0.00772955 21.00 0.00772955 49.9521 8552.36 0.00 12258.34 12258.34 0.43863325 12.80 11.60 0.00800000 33059.8 40.21 21.24 0.00800000 61006.5
VAV_BOT WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 247829.882 -999.000 8.941724 0.01054326 -999.000 -999.0000 1.00000 1.00000 1025.6133 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.941724 10.75838654   4197.9300 999.8980 129.36392424 12.27 6.67 5.60 3041139.91 8.1492 8.149243 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 247829.88 172633.37 1.0000 10.75838654 8.941724 26.93 19.52 0.01117472 55570.8 11.05 11.05 0.00850000 32534.9 10.54218056 6.67 12.27 5.60 19322.590 228507.29 33.90 0.01653638 25.13 2.53819000 28.3859 24.00 0.00891574 24.00 0.00891574 47.9268 117750.75 0.00 248209.30 168596.78 10.75838654 26.93 19.54 0.01117472 55570.8 11.65 11.36 0.00824123 32499.6
VAV_BOT WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_BOT WITH REHEAT CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 26182.451 26182.451 2.682517 0.00022906 452.913 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_BOT WITH REHEAT FAN Fan:VariableVolume 8.941724 10.75838654   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 1.6350 1.667939 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 26182.45 26182.45 1.0000 3.22751596 2.682517 4.73 4.71 0.00529132 18029.6 12.80 11.59 0.00800000 33059.8 0.22903213 60.00 32.22 27.78 0.000 26182.45 4.60 0.00525715 4.60 2.53819000 94.6197 6.96 0.00589222 21.96 0.00617385 37.7135 11742.51 0.00 26920.67 26920.67 3.22751596 2.80 2.80 0.00529132 16074.4 11.02 7.85 0.00529132 24415.3
VAV_MID WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 2420734.695 -999.000 82.719065 0.10298365 -999.000 -999.0000 1.00000 1.00000 1026.2828 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 82.719065 99.52484064   4197.9300 999.8980 129.36392424 12.27 6.67 5.60 3041139.91 79.5996 79.599583 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 2420734.69 1632276.66 1.0000 99.52484064 82.719065 27.29 19.91 0.01153489 56858.9 11.05 11.05 0.00850000 32536.0 102.97314452 6.67 12.27 5.60 178751.494 2241983.20 33.90 0.01653638 25.13 25.38195000 30.6845 24.00 0.00904016 24.00 0.00904016 48.5870 1048802.15 0.00 2423637.37 1599968.41 99.52484064 27.29 19.92 0.01153489 56858.9 11.63 11.36 0.00825409 32506.9
VAV_MID WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_MID WITH REHEAT CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 246020.642 246020.642 24.815719 0.00215230 4252.083 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_MID WITH REHEAT FAN Fan:VariableVolume 82.719065 99.52484064   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 15.3634 15.672613 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 246020.64 246020.64 1.0000 29.85745219 24.815719 4.60 4.60 0.00525715 17815.0 12.80 11.59 0.00800000 33059.8 2.15207634 60.00 32.22 27.78 0.000 246020.64 4.60 0.00525715 4.60 25.38195000 102.2817 20.76 0.00779025 21.00 0.00776067 50.1499 519836.16 0.00 252541.00 252541.00 29.85745219 2.80 2.80 0.00525715 15988.7 11.14 7.87 0.00525715 24447.0
VAV_TOP WITH REHEAT COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident CoolingDesignCapacity N/A Yes Yes Yes No 245566.353 -999.000 8.935743 0.01044696 -999.000 -999.0000 1.00000 1.00000 1025.5541 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.935743 10.75119035   4197.9300 999.8980 129.36392424 12.27 6.67 5.60 3041139.91 8.0748 8.074813 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:40:00 Sensible 245566.35 171304.97 1.0000 10.75119035 8.935743 26.82 19.47 0.01114288 55375.6 11.05 11.05 0.00850000 32534.8 10.44589465 6.67 12.27 5.60 19309.665 226256.69 33.90 0.01653638 25.13 2.53819000 28.4049 24.00 0.00899056 24.00 0.00899056 48.3245 122368.39 0.00 245939.19 167231.14 10.75119035 26.82 19.48 0.01114288 55375.6 11.66 11.36 0.00824078 32500.1
VAV_TOP WITH REHEAT HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC VAV_TOP WITH REHEAT CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; Coincident HeatingDesignCapacity N/A Yes Yes Yes No 23750.386 23750.386 2.680723 0.00020778 412.954 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 VAV_TOP WITH REHEAT FAN Fan:VariableVolume 8.935743 10.75119035   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 1.4832 1.513006 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 13:00:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 08:00:00 Sensible 23750.39 23750.39 1.0000 3.22535710 2.680723 5.47 5.23 0.00539518 19046.4 12.80 11.59 0.00800000 33059.8 0.20775754 60.00 32.22 27.78 0.000 23750.39 4.60 0.00525715 4.60 2.53819000 94.6830 21.00 0.00785329 21.00 0.00785329 50.7399 59135.00 0.00 24658.51 24658.51 3.22535710 2.80 2.80 0.00539518 16334.7 10.33 7.64 0.00539518 23979.9
CAV_BAS COOLING COIL Coil:Cooling:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident CoolingDesignCapacity N/A Yes Yes Yes No 127008.982 -999.000 5.478862 0.00540326 -999.000 -999.0000 1.00000 1.00000 1024.5895 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.478862 6.59198528   4197.9300 999.8980 129.36392424 12.27 6.67 5.60 3041139.91 4.1764 4.176361 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:20:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 08:00:00 Sensible 127008.98 91034.07 1.0000 6.59198528 5.478862 25.00 18.47 0.01062400 52185.5 11.42 11.42 0.00850000 32918.3 5.40270451 6.67 12.27 5.60 9290.256 117718.73 28.55 0.01652632 23.72 1.20015641 21.9052 24.00 0.00895956 24.00 0.00895956 48.1587 75031.25 0.00 127162.48 88610.75 6.59198528 25.00 18.48 0.01062400 52185.5 11.88 11.52 0.00830604 32895.0
CAV_BAS HEATING COIL Coil:Heating:Water AirLoop AirLoopHVAC CAV_BAS BASEMENT Coincident HeatingDesignCapacity N/A Yes Yes Yes No 258285.902 258285.902 5.478862 0.00225960 5860.879 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 CAV_BAS FAN Fan:ConstantVolume 5.478862 6.59198528   4197.9300 999.8980 13.73144592 54.44 82.22 27.78 1601340.56 16.1294 16.453965 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 258285.90 258285.90 1.0000 6.59198528 5.478862 1.01 1.01 0.00525715 14170.2 40.00 21.17 0.00800000 60796.0 2.25936724 60.00 32.22 27.78 0.000 258285.90 4.60 0.00525715 4.60 1.20015641 21.9052 0.00 0.00525715 25.28 0.00525715 26.3315 0.00 0.00 221550.43 221550.43 6.59198528 12.80 8.65 0.00525715 26134.9 45.93 20.95 0.00525715 59743.9
AIRLOOP DATACENTER BASEMENT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 434337.817 312325.506 21.333099 0.01063691 -999.000 -999.0000 -999.00000 -999.00000 1020.9556 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 07:10:00 Sensible 406947.05 397013.16 0.9369 -999.0 -999.0 28.51 18.07 0.00866922 50787.4 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 406947.05 33.90 0.01653638 25.13 0.33839277 -999.0000 27.00 0.00854225 27.00 0.00854225 38.4505 371459.76 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9501.305 6820.687 0.465681 0.00023269 -999.000 -999.0000 -999.00000 -999.00000 1021.3028 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:20:00 Sensible 8904.61 8448.66 0.9372 -999.0 -999.0 28.09 18.08 0.00885599 50833.6 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8904.61 31.21 0.01653132 24.43 0.01563234 -999.0000 27.00 0.00858924 27.00 0.00858924 38.6568 8115.11 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 90544.486 64905.212 4.425639 0.00221743 -999.000 -999.0000 -999.00000 -999.00000 1021.3367 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 84897.54 80341.80 0.9376 -999.0 -999.0 28.09 18.10 0.00887421 50887.5 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 84897.54 31.21 0.01653132 24.43 0.15632344 -999.0000 27.00 0.00859384 27.00 0.00859384 38.6775 77163.21 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP COOLING COIL COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident CoolingDesignCapacity N/A Yes No unknown No 9227.993 6617.526 0.451387 0.00022599 -999.000 -999.0000 -999.00000 -999.00000 1021.3232 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:30:00 TAMPA-MACDILL.AFB_FL_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 Sensible 8651.41 8195.83 0.9375 -999.0 -999.0 28.10 18.09 0.00886692 50873.0 12.80 12.09 0.00850000 34322.2 -999.0 -999.00 -999.00 -999.00 0.000 8651.41 31.41 0.01653169 24.48 0.01563234 -999.0000 27.00 0.00859193 27.00 0.00859193 38.6689 7869.54 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 434337.817 434337.817 21.333099 0.01063691 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 434337.82 434337.82 1.0000 25.66727840 21.333099 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 434337.82 4.60 0.00525715 4.60 0.33839277 1.5862 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9501.305 9501.305 0.465681 0.00023269 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9501.30 9501.30 1.0000 0.56029140 0.465681 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9501.30 4.60 0.00525715 4.60 0.01563234 3.3569 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 90544.486 90544.486 4.425639 0.00221743 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 90544.49 90544.49 1.0000 5.32478286 4.425639 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 90544.49 4.60 0.00525715 4.60 0.15632344 3.5322 0.00 0.00796561 24.95 0.00796561 40.5098 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP HEATING COIL COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 9227.993 9227.993 0.451387 0.00022599 -999.000 -999.0000 -999.00000 -999.00000 1019.7116 1004.8586 1.2032 unknown unknown -999.0 -999.0   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 9227.99 9227.99 1.0000 0.54309410 0.451387 4.60 4.60 0.00525715 17815.0 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 9227.99 4.60 0.00525715 4.60 0.01563234 3.4632 0.00 0.00548951 24.02 0.00548951 29.6249 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BASEMENT DATACENTER_BASEMENT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 14482.888 14482.888 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER BASEMENT SUPPLY FAN Fan:OnOff 21.333099 25.66727840   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 14482.89 14482.89 1.0000 25.66727840 21.333099 0.07 0.07 0.00844856 21203.8 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 14482.89 4.60 0.00525715 4.60 0.33839277 1.5862 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER BOT_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER BOT DATACENTER_BOT_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.049 669.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER BOT SUPPLY FAN Fan:OnOff 0.465681 0.56029140   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.05 669.05 1.0000 0.56029140 0.465681 0.15 0.15 0.00839114 21143.3 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.05 4.60 0.00525715 4.60 0.01563234 3.3569 0.00 0.00850000 27.00 0.00850000 38.2570 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER MID_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER MID DATACENTER_MID_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 6690.494 6690.494 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER MID SUPPLY FAN Fan:OnOff 4.425639 5.32478286   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 6690.49 6690.49 1.0000 5.32478286 4.425639 0.16 0.16 0.00786994 19847.9 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 6690.49 4.60 0.00525715 4.60 0.15632344 3.5322 0.00 0.00796561 24.95 0.00796561 40.5098 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0
AIRLOOP DATACENTER TOP_SUPPHEATCOIL Coil:Heating:Electric AirLoop AirLoopHVAC AIRLOOP DATACENTER TOP DATACENTER_TOP_ZN_6 Coincident HeatingDesignCapacity N/A Yes No unknown No 669.049 669.049 -999.0 -999.0 -999.000 -999.0000 1.00000 1.00000 1019.7116 1004.8586 1.2032 AIRLOOP DATACENTER TOP SUPPLY FAN Fan:OnOff 0.451387 0.54309410   -999.0000 -999.0000 -999.0 -999.00 -999.00 -999.00 -999.00 -999.0000 -999.0 TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 unknown unknown TAMPA-MACDILL.AFB_FL_USA ANN HTG 99.6% CONDNS DB 1/21 00:10:00 Sensible 669.05 669.05 1.0000 0.54309410 0.451387 0.16 0.16 0.00548147 13870.5 40.00 21.17 0.00800000 60796.0 -999.0 -999.00 -999.00 -999.00 0.000 669.05 4.60 0.00525715 4.60 0.01563234 3.4632 0.00 0.00548951 24.02 0.00548951 29.6249 0.00 0.00 -999.00 -999.00 -999.0 -999.00 -999.00 -999.0 -999.0 -999.00 -999.00 -999.0 -999.0



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Economizer

High Limit Shutoff Control Minimum Outdoor Air [m3/s] Maximum Outdoor Air [m3/s] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [C] Outdoor Air Enthalpy Limit [C]
VAV_BOT WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.94 -      
VAV_MID WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 82.72 -      
VAV_TOP WITH REHEAT_OA_CONTROLLER DifferentialEnthalpy 0.00 8.94 -      
CAV_BAS_OA_CONTROLLER DifferentialEnthalpy 1.20 5.48 -      


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [m3/s-person] Outdoor Air Per Area [m3/s-m2] Outdoor Air Per Zone [m3/s] Outdoor Air ACH [ach] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
CORE_BOTTOM VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_MID VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
CORE_TOP VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT_DCV 0.000000 0.000432 0.000000 0.000000 Flow/Area   1.00 1.00  


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
BASEMENT 4934.67 1918.83 1852.83
CORE_BOTTOM 4916.50 93.67 0.33
CORE_MID 4470.83 664.33 0.00
CORE_TOP 4275.83 1228.00 36.17
PERIMETER_BOT_ZN_3 4402.17 1159.00 107.50
PERIMETER_BOT_ZN_2 4440.50 1160.50 245.83
PERIMETER_BOT_ZN_1 4867.67 812.50 297.67
PERIMETER_BOT_ZN_4 5097.17 862.17 528.00
PERIMETER_MID_ZN_3 3968.00 2047.83 439.50
PERIMETER_MID_ZN_2 3497.00 1648.17 472.17
PERIMETER_MID_ZN_1 4674.83 1229.00 487.33
PERIMETER_MID_ZN_4 4352.83 1623.67 440.83
PERIMETER_TOP_ZN_3 4103.00 2327.17 776.67
PERIMETER_TOP_ZN_2 4195.83 2035.33 647.33
PERIMETER_TOP_ZN_1 4580.50 1519.33 612.67
PERIMETER_TOP_ZN_4 4304.67 1925.17 621.00
DATACENTER_BOT_ZN_6 5943.00 1603.17 1603.17
DATACENTER_MID_ZN_6 5940.67 138.33 138.33
DATACENTER_TOP_ZN_6 5890.83 394.67 383.17
DATACENTER_BASEMENT_ZN_6 5943.00 5943.00 5943.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00
Facility 5943.00 5943.00 5943.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
BASEMENT 0.00 77.00 0.00 3.17
CORE_BOTTOM 0.00 4.17 0.00 0.00
CORE_MID 0.00 0.17 0.00 0.00
CORE_TOP 0.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 8.17 0.00 1.33
PERIMETER_BOT_ZN_2 0.00 34.67 0.00 31.83
PERIMETER_BOT_ZN_1 0.00 66.33 0.00 54.33
PERIMETER_BOT_ZN_4 0.00 235.67 0.00 75.67
PERIMETER_MID_ZN_3 0.00 1.67 0.00 0.50
PERIMETER_MID_ZN_2 0.00 47.83 0.00 44.83
PERIMETER_MID_ZN_1 0.00 52.33 0.00 46.83
PERIMETER_MID_ZN_4 0.00 59.33 0.00 27.83
PERIMETER_TOP_ZN_3 6.00 26.17 1.50 17.33
PERIMETER_TOP_ZN_2 3.33 70.50 0.17 57.67
PERIMETER_TOP_ZN_1 1.83 72.83 0.00 55.67
PERIMETER_TOP_ZN_4 1.83 71.67 0.00 34.50
DATACENTER_BOT_ZN_6 0.00 48.67 0.00 48.67
DATACENTER_MID_ZN_6 0.00 53.33 0.00 53.33
DATACENTER_TOP_ZN_6 0.00 27.17 0.00 27.17
DATACENTER_BASEMENT_ZN_6 0.00 640.50 0.00 560.33
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Facility 6.00 1067.00 1.50 754.67
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.43 149.60 6779.02 0.986 0.000 0.000 0.000
CORE_BOTTOM 56.07 134.35 6849.35 0.685 0.000 0.000 0.000
CORE_MID 56.07 134.35 6849.35 0.582 0.000 0.000 0.000
CORE_TOP 56.07 134.35 6849.35 0.544 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.04 16.87 860.00 0.672 0.034 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 0.838 0.035 0.000 0.000
PERIMETER_BOT_ZN_1 7.04 16.87 860.02 0.991 0.034 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 1.338 0.035 0.000 0.000
PERIMETER_MID_ZN_3 7.04 16.87 860.00 0.618 0.079 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 0.784 0.087 0.000 0.000
PERIMETER_MID_ZN_1 7.04 16.87 860.02 0.948 0.079 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 0.918 0.082 0.000 0.000
PERIMETER_TOP_ZN_3 7.04 16.87 860.00 0.607 0.098 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 0.835 0.102 0.000 0.000
PERIMETER_TOP_ZN_1 7.04 16.87 860.02 0.898 0.098 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 0.903 0.102 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.427 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.60 42.18 1911.37 0.481 0.000 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Mechanical Ventilation [ach] Infiltration [ach] AFN Infiltration [ach] Simple Ventilation [ach]
BASEMENT 62.43 149.60 6779.02 0.000 0.000 0.000 0.000
CORE_BOTTOM 56.07 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_MID 56.07 134.35 6849.35 0.000 0.000 0.000 0.000
CORE_TOP 56.07 134.35 6849.35 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_3 7.04 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_1 7.04 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_BOT_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_3 7.04 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_2 3.97 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_1 7.04 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_MID_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_3 7.04 16.87 860.00 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_2 4.54 10.87 554.22 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_1 7.04 16.87 860.02 0.000 0.000 0.000 0.000
PERIMETER_TOP_ZN_4 4.54 10.87 554.22 0.000 0.000 0.000 0.000
DATACENTER_BOT_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_MID_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_TOP_ZN_6 0.81 1.95 99.34 0.000 0.000 0.000 0.000
DATACENTER_BASEMENT_ZN_6 17.60 42.18 1911.37 0.000 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [m3] Zone Area [m2] Design Zone Outdoor Airflow - Voz [m3/s] Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s]
BASEMENT CAV_BAS 62.43 149.60 6779.02 2779.43 1.2002 1.200
CORE_BOTTOM VAV_BOT WITH REHEAT 56.07 134.35 6849.35 2496.12 0.0000 1.078
CORE_MID VAV_MID WITH REHEAT 56.07 134.35 6849.35 2496.12 0.0000 10.778
CORE_TOP VAV_TOP WITH REHEAT 56.07 134.35 6849.35 2496.12 0.0000 1.078
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 7.04 16.87 860.00 313.41 0.0000 0.135
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 7.04 16.87 860.02 313.42 0.0000 0.135
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 7.04 16.87 860.00 313.41 0.0000 1.353
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 3.97 10.87 554.22 201.98 0.0000 0.872
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 7.04 16.87 860.02 313.42 0.0000 1.353
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.872
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 7.04 16.87 860.00 313.41 0.0000 0.135
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 7.04 16.87 860.02 313.42 0.0000 0.135
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 4.54 10.87 554.22 201.98 0.0000 0.087
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.81 1.95 99.34 36.20 0.1563 0.156
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.81 1.95 99.34 36.20 0.0156 0.016
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 17.60 42.18 1911.37 783.68 0.3384 0.338
Total Facility   1034.72 2493.19 126016.35 46320.38 1.7261 158.471


Total Outdoor Air by Zone

Mechanical Ventilation [m3] Natural Ventilation [m3] Total Ventilation [m3] Infiltration [m3] Total Ventilation and Infiltration [m3] Dynamic Target Ventilation - Voz-dyn [m3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
BASEMENT 41242949.08 0.00 41242949.08 0.00 41242949.08 37848132.68 4061.63 2807.70 1890.66 279.57
CORE_BOTTOM 29007425.90 0.00 29007425.90 0.00 29007425.90 33990283.35 6650.01 66.62 2043.37 260.44
CORE_MID 0.24E+09 0.00 0.24E+09 0.00 0.24E+09 0.34E+09 6884.13 157.07 1718.80 57.31
CORE_TOP 21909880.07 0.00 21909880.07 0.00 21909880.07 33990283.35 6997.90 220.17 1541.93 53.44
PERIMETER_BOT_ZN_3 3562426.67 0.00 3562426.67 328931.10 3891357.77 4267819.30 4504.54 103.84 4151.61 260.44
PERIMETER_BOT_ZN_2 2857984.58 0.00 2857984.58 219287.25 3077271.83 2750345.05 4207.53 54.47 4498.00 260.44
PERIMETER_BOT_ZN_1 5161264.68 0.00 5161264.68 328931.10 5490195.77 4267912.63 4114.47 52.34 4593.19 260.44
PERIMETER_BOT_ZN_4 4533338.36 0.00 4533338.36 219287.25 4752625.61 2750345.05 3905.14 0.17 4854.69 260.44
PERIMETER_MID_ZN_3 31343744.06 0.00 31343744.06 771421.61 32115165.67 42678193.03 4815.45 168.19 3776.36 57.31
PERIMETER_MID_ZN_2 27674715.71 0.00 27674715.71 514280.72 28188996.44 27503450.52 4235.93 17.25 4506.82 966.31
PERIMETER_MID_ZN_1 47911853.13 0.00 47911853.13 771421.61 48683274.74 42679126.28 4318.35 137.60 4304.05 57.31
PERIMETER_MID_ZN_4 29998114.40 0.00 29998114.40 514280.72 30512395.13 27503450.52 4187.78 3.53 4568.68 57.31
PERIMETER_TOP_ZN_3 3063840.16 0.00 3063840.16 957784.80 4021624.96 4267819.30 4909.01 221.47 3629.52 53.44
PERIMETER_TOP_ZN_2 2713892.85 0.00 2713892.85 638522.76 3352415.62 2750345.05 4275.69 12.33 4471.99 53.44
PERIMETER_TOP_ZN_1 4519844.20 0.00 4519844.20 957784.80 5477629.00 4267912.63 4435.09 184.92 4139.99 53.44
PERIMETER_TOP_ZN_4 2938320.15 0.00 2938320.15 638522.76 3576842.91 2750345.05 4248.09 2.50 4509.41 53.44
DATACENTER_BOT_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_MID_ZN_6 2442960.18 0.00 2442960.18 0.00 2442960.18 4929815.99 4419.00 4341.00 0.00 0.00
DATACENTER_TOP_ZN_6 244296.02 0.00 244296.02 0.00 244296.02 492981.60 4419.00 4341.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5288266.81 0.00 5288266.81 0.00 5288266.81 10671554.30 4419.00 4341.00 0.00 0.00
Total Facility 0.39E+10 0.00 0.39E+10 30003098.57 0.39E+10 0.50E+10 7433.97 4358.71 5001.69 1336.25


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Infiltration [m3/s] Total Ventilation and Infiltration [m3/s] Dynamic Target Ventilation - Voz-dyn [m3/s] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
BASEMENT 1.8166 0.0000 1.8166 0.0000 1.8166 1.2002 1441.32 2805.78 1695.89
CORE_BOTTOM 1.2761 0.0000 1.2761 0.0000 1.2761 1.0778 4074.68 65.27 1803.05
CORE_MID 10.8425 0.0000 10.8425 0.0000 10.8425 10.7782 4118.96 157.07 1666.97
CORE_TOP 1.0141 0.0000 1.0141 0.0000 1.0141 1.0778 4201.74 220.12 1521.15
PERIMETER_BOT_ZN_3 0.1572 0.0000 0.1572 0.0079 0.1651 0.1353 1926.96 102.38 3913.67
PERIMETER_BOT_ZN_2 0.1263 0.0000 0.1263 0.0053 0.1315 0.0872 1645.17 54.07 4243.77
PERIMETER_BOT_ZN_1 0.2318 0.0000 0.2318 0.0079 0.2397 0.1353 1537.13 50.73 4355.14
PERIMETER_BOT_ZN_4 0.2016 0.0000 0.2016 0.0053 0.2069 0.0872 1348.58 0.17 4594.26
PERIMETER_MID_ZN_3 1.4449 0.0000 1.4449 0.0185 1.4633 1.3533 2050.11 168.19 3724.70
PERIMETER_MID_ZN_2 1.1817 0.0000 1.1817 0.0131 1.1948 0.8721 1443.78 12.27 3577.95
PERIMETER_MID_ZN_1 2.2185 0.0000 2.2185 0.0185 2.2370 1.3533 1552.89 137.60 4252.51
PERIMETER_MID_ZN_4 1.3840 0.0000 1.3840 0.0123 1.3963 0.8721 1425.21 3.53 4514.25
PERIMETER_TOP_ZN_3 0.1420 0.0000 0.1420 0.0229 0.1649 0.1353 2114.36 221.39 3607.24
PERIMETER_TOP_ZN_2 0.1259 0.0000 0.1259 0.0153 0.1412 0.0872 1482.69 11.45 4448.86
PERIMETER_TOP_ZN_1 0.2100 0.0000 0.2100 0.0229 0.2329 0.1353 1639.26 184.87 4118.87
PERIMETER_TOP_ZN_4 0.1362 0.0000 0.1362 0.0153 0.1515 0.0872 1457.16 2.29 4483.54
DATACENTER_BOT_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_MID_ZN_6 0.1142 0.0000 0.1142 0.0000 0.1142 0.1563 1602.00 4341.00 0.00
DATACENTER_TOP_ZN_6 0.0114 0.0000 0.0114 0.0000 0.0114 0.0156 1602.00 4341.00 0.00
DATACENTER_BASEMENT_ZN_6 0.2472 0.0000 0.2472 0.0000 0.2472 0.3384 1602.00 4341.00 0.00
Total Facility 177.5652 0.0000 177.5652 0.7263 178.2916 158.4706 4616.97 4353.20 4635.13


Total Outdoor Air by AirLoop

Mechanical Ventilation [m3] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
VAV_BOT WITH REHEAT 65320344.90 0.00 65320344.90 48026705.38 3905.14 0.94 4853.92 260.44
VAV_MID WITH REHEAT 0.54E+09 0.00 0.54E+09 0.48E+09 4174.66 2.36 4582.98 57.31
VAV_TOP WITH REHEAT 50876716.33 0.00 50876716.33 48026705.38 4236.54 1.92 4521.55 53.44
CAV_BAS 59703729.48 0.00 59703729.48 37848132.68 4021.96 2.04 4736.00 279.57
AIRLOOP DATACENTER BASEMENT 7655350.99 0.00 7655350.99 10671554.30 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER BOT 353645.50 0.00 353645.50 492981.60 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER MID 3536455.01 0.00 3536455.01 4929815.99 4419.00 0.00 4341.00 0.00
AIRLOOP DATACENTER TOP 353645.50 0.00 353645.50 492981.60 4419.00 0.00 4341.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [m3/s] Natural Ventilation [m3/s] Total Ventilation [m3/s] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
VAV_BOT WITH REHEAT 2.8852 0.0000 2.8852 1.5229 1348.58 0.67 4593.76
VAV_MID WITH REHEAT 24.8511 0.0000 24.8511 15.2292 1412.40 2.15 4528.45
VAV_TOP WITH REHEAT 2.3567 0.0000 2.3567 1.5229 1447.63 0.82 4494.55
CAV_BAS 2.6298 0.0000 2.6298 1.2002 1436.27 0.42 4506.31
AIRLOOP DATACENTER BASEMENT 0.3578 0.0000 0.3578 0.3384 1602.00 0.00 4341.00
AIRLOOP DATACENTER BOT 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00
AIRLOOP DATACENTER MID 0.1653 0.0000 0.1653 0.1563 1602.00 0.00 4341.00
AIRLOOP DATACENTER TOP 0.0165 0.0000 0.0165 0.0156 1602.00 0.00 4341.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
VAV_BOT WITH REHEAT 0.00 0.00 1938.50 0.00 0.00 0.00 2916.36 0.00 0.00 0.00
VAV_MID WITH REHEAT 0.00 0.03 1651.09 0.00 0.00 0.00 2942.11 0.00 0.00 0.00
VAV_TOP WITH REHEAT 0.00 0.03 1529.29 0.00 0.00 0.00 3048.17 0.00 0.00 0.00
CAV_BAS 0.00 2805.42 1985.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BASEMENT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER BOT 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER MID 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
AIRLOOP DATACENTER TOP 0.00 4341.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [m3/s] Limits and Scheduled Limits [m3/s] Economizer [m3/s] Exhaust Flow [m3/s] Mixed Air Flow [m3/s] High Humidity [m3/s] Demand Controlled Ventilation [m3/s] Night Ventilation [m3/s] Demand Limiting [m3/s] Energy Management System [m3/s]
VAV_BOT WITH REHEAT 0.0000 0.0000 6.1214 0.0000 0.0000 0.0000 2.3577 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT 0.0000 0.0000 48.4655 0.0000 0.0000 0.0000 23.9567 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT 0.0000 0.0000 4.6000 0.0000 0.0000 0.0000 2.3690 0.0000 0.0000 0.0000
CAV_BAS 0.0000 1.7376 6.3041 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BASEMENT 0.0000 0.4900 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER BOT 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER MID 0.0000 0.2263 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
AIRLOOP DATACENTER TOP 0.0000 0.0226 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Surfaces by Class

Total Outdoors
Wall 98 30
Floor 41 0
Roof 30 1
Internal Mass 16 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 24 24
Door 12 12
Glass Door 0 0
Shading 0 0
Overhang 0 0
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 8
Conditioned Zones 23
Unconditioned Zones 0
Supply Plenums 0
Return Plenums 3


Input Fields

Count
IDF Objects 1386
Defaulted Fields 1179
Fields with Defaults 3922
Autosized Fields 333
Autosizable Fields 412
Autocalculated Fields 226
Autocalculatable Fields 473



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Annual and Peak Values - Electricity

Electricity Annual Value [GJ] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
Electricity:Building 17954.39 247233.96 01-JAN-08:50 1049209.74 12-DEC-08:10
Electricity:Zone:BASEMENT 602.14 14319.77 01-JAN-00:10 28977.00 02-JAN-08:10
Electricity:SpaceType:GENERAL 17954.39 247233.96 01-JAN-08:50 1049209.74 12-DEC-08:10
InteriorLights:Electricity 2740.98 13024.70 01-JAN-08:50 255624.72 25-OCT-07:10
InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
InteriorLights:Electricity:SpaceType:GENERAL 2740.98 13024.70 01-JAN-08:50 255624.72 25-OCT-07:10
LightsWired:InteriorLights:Electricity 2740.98 13024.70 01-JAN-08:50 255624.72 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:BASEMENT 177.74 862.23 01-JAN-00:10 15519.45 02-JAN-08:10
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL 2740.98 13024.70 01-JAN-08:50 255624.72 25-OCT-07:10
Electricity:Zone:CORE_BOTTOM 480.91 6817.20 01-JAN-00:10 32066.15 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:CORE_MID 4809.09 68171.81 01-JAN-00:10 320660.81 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_MID 1596.25 7743.41 01-JAN-00:10 139375.61 02-JAN-08:10
Electricity:Zone:CORE_TOP 480.91 6817.18 01-JAN-00:10 32066.08 02-JAN-08:10
InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP 159.62 774.34 01-JAN-00:10 13937.56 02-JAN-08:10
Electricity:Zone:PERIMETER_BOT_ZN_3 54.11 818.50 01-JAN-08:50 3890.83 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.77 59.73 01-JAN-08:50 1614.51 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 13.77 59.73 01-JAN-08:50 1614.51 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_2 34.85 527.47 01-JAN-07:50 2491.03 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.86 38.49 01-JAN-07:50 1024.08 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 8.86 38.49 01-JAN-07:50 1024.08 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_1 54.00 818.51 01-JAN-08:00 3882.56 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.66 59.73 01-JAN-08:00 1606.21 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 13.66 59.73 01-JAN-08:00 1606.21 25-OCT-07:10
Electricity:Zone:PERIMETER_BOT_ZN_4 34.85 527.47 01-JAN-08:50 2514.29 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.85 38.49 01-JAN-08:50 1047.35 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 8.85 38.49 01-JAN-08:50 1047.35 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_3 541.26 8184.99 01-JAN-08:50 38947.98 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 137.84 597.26 01-JAN-08:50 16184.80 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 137.84 597.26 01-JAN-08:50 16184.80 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_2 348.57 5274.72 01-JAN-07:50 24923.19 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 88.59 384.90 01-JAN-07:50 10253.73 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 88.59 384.90 01-JAN-07:50 10253.73 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_1 540.08 8185.12 01-JAN-08:00 38868.83 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 136.65 597.27 01-JAN-08:00 16105.31 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 136.65 597.27 01-JAN-08:00 16105.31 25-OCT-07:10
Electricity:Zone:PERIMETER_MID_ZN_4 348.56 5274.69 01-JAN-08:50 25148.89 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 88.58 384.90 01-JAN-08:50 10479.53 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 88.58 384.90 01-JAN-08:50 10479.53 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_3 54.13 818.50 01-JAN-08:50 3894.67 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.78 59.73 01-JAN-08:50 1618.36 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 13.78 59.73 01-JAN-08:50 1618.36 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_2 34.86 527.47 01-JAN-07:50 2492.26 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.86 38.49 01-JAN-07:50 1025.32 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 8.86 38.49 01-JAN-07:50 1025.32 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_1 54.01 818.51 01-JAN-08:00 3886.76 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.67 59.73 01-JAN-08:00 1610.41 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 13.67 59.73 01-JAN-08:00 1610.41 25-OCT-07:10
Electricity:Zone:PERIMETER_TOP_ZN_4 34.86 527.47 01-JAN-08:50 2514.81 25-OCT-07:10
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.86 38.49 01-JAN-08:50 1047.88 25-OCT-07:10
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 8.86 38.49 01-JAN-08:50 1047.88 25-OCT-07:10
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7544.97 95151.24 01-JAN-00:10 384008.34 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 50.12 243.11 01-JAN-00:10 4375.82 02-JAN-08:10
Electricity:Zone:DATACENTER_BOT_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
Electricity:Zone:DATACENTER_MID_ZN_6 1585.20 19711.13 01-JAN-00:10 81995.25 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 46.40 225.07 01-JAN-00:10 4051.03 02-JAN-08:10
Electricity:Zone:DATACENTER_TOP_ZN_6 158.52 1971.11 01-JAN-00:10 8199.53 03-APR-07:10
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 4.64 22.51 01-JAN-00:10 405.10 02-JAN-08:10
InteriorEquipment:Electricity 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
InteriorEquipment:Electricity:SpaceType:GENERAL 15213.41 234209.26 01-JAN-00:10 794004.08 03-APR-07:10
MiscPlug:InteriorEquipment:Electricity 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT 424.40 13457.54 01-JAN-00:10 13457.54 01-JAN-00:10
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL 5871.99 115917.86 01-JAN-00:10 320838.49 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM 321.29 6042.86 01-JAN-00:10 18128.59 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID 3212.85 60428.40 01-JAN-00:10 181285.20 02-JAN-08:10
InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP 321.28 6042.84 01-JAN-00:10 18128.52 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 403.42 7587.73 01-JAN-00:10 22763.18 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 259.98 4889.82 01-JAN-00:10 14669.46 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 403.43 7587.84 01-JAN-00:10 22763.53 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 259.98 4889.79 01-JAN-00:10 14669.36 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 40.34 758.77 01-JAN-00:10 2276.32 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 26.00 488.98 01-JAN-00:10 1466.95 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 40.34 758.78 01-JAN-00:10 2276.35 02-JAN-08:10
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 26.00 488.98 01-JAN-00:10 1466.94 02-JAN-08:10
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 7494.86 94908.13 01-JAN-00:10 379632.52 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL 9341.42 118291.40 01-JAN-00:10 473165.59 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 1538.81 19486.06 01-JAN-00:10 77944.22 31-MAR-23:10
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 153.88 1948.61 01-JAN-00:10 7794.42 31-MAR-23:10
Electricity:Plant 5139.72 6988.29 05-JAN-08:00 448410.02 24-OCT-13:30
HeatRejection:Electricity 1896.49 3256.62 05-JAN-08:00 93886.47 18-JAN-15:00
General:HeatRejection:Electricity 1896.49 3256.62 05-JAN-08:00 93886.47 18-JAN-15:00
Electricity:HVAC 5604.72 76371.97 22-JAN-08:30 431440.41 18-APR-14:30
ExteriorEquipment:Electricity 1914.38 28294.68 01-JAN-00:10 117201.62 25-OCT-07:20
Transformer:ExteriorEquipment:Electricity 59.77 1112.61 01-JAN-00:10 3723.66 25-OCT-07:20
ElectricityPurchased:Facility 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
ElectricityPurchased:Plant 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
Cogeneration:ElectricityPurchased 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
General:Cogeneration:ElectricityPurchased 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
ElectricityNet:Plant 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
Cogeneration:ElectricityNet 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
General:Cogeneration:ElectricityNet 31000.55 370259.68 22-JAN-10:10 1925340.49 03-AUG-15:20
Fans:Electricity 2510.59 41354.11 03-JAN-01:40 261005.24 18-APR-14:40
General:Fans:Electricity 2510.59 41354.11 03-JAN-01:40 261005.24 18-APR-14:40
ExteriorLights:Electricity 447.11 0.00 01-JAN-07:30 37611.08 01-JAN-06:10
General:ExteriorLights:Electricity 447.11 0.00 01-JAN-07:30 37611.08 01-JAN-06:10
ElevatorLift:ExteriorEquipment:Electricity 1848.78 27144.47 01-JAN-00:10 113101.96 01-JAN-07:10
ElevatorLightsFan:ExteriorEquipment:Electricity 5.83 37.60 01-JAN-00:10 376.00 01-JAN-07:10
HeatRecovery:Electricity 60.30 0.00 01-JAN-00:10 5613.48 02-JAN-10:50
General:HeatRecovery:Electricity 60.30 0.00 01-JAN-00:10 5613.48 02-JAN-10:50
Cooling:Electricity 5101.82 30632.58 05-JAN-08:00 443337.10 03-AUG-15:30
General:Cooling:Electricity 5101.82 30632.58 05-JAN-08:00 443337.10 03-AUG-15:30
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Humidifier:Electricity 1.54 0.00 01-JAN-00:10 4283.79 08-MAR-22:00
General:Humidifier:Electricity 1.54 0.00 01-JAN-00:10 4283.79 08-MAR-22:00
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 1113.93 3395.48 01-JAN-01:00 73611.76 11-OCT-14:30
General:Pumps:Electricity 1113.93 3395.48 01-JAN-01:00 73611.76 11-OCT-14:30
WIRED_LTG_ELECTRICITY 77.02 0.00 01-JAN-00:10 7183.05 25-OCT-07:20
WIRED_INT_EQUIP 5871.99 115917.86 04-MAR-00:10 320838.49 03-APR-07:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [GJ] Natural Gas Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 643.90 5695.87 01-JAN-00:10 495802.30 21-DEC-07:10
NaturalGas:Plant 643.90 5695.87 01-JAN-00:10 495802.30 21-DEC-07:10
Heating:NaturalGas 48.57 0.00 01-JAN-00:10 467400.92 21-DEC-07:10
Boiler:Heating:NaturalGas 48.57 0.00 01-JAN-00:10 467400.92 21-DEC-07:10
WaterSystems:NaturalGas 595.33 5695.87 01-JAN-00:10 73397.75 25-JAN-12:20
Water Heater:WaterSystems:NaturalGas 595.33 5695.87 01-JAN-00:10 73397.75 25-JAN-12:20


Annual and Peak Values - Cooling

Cooling Annual Value [GJ] Cooling Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
PlantLoopCoolingDemand:Facility 27682.44 150405.05 05-JAN-08:00 2391599.86 14-AUG-13:30
PlantLoopCoolingDemand:HVAC 27682.44 150405.05 05-JAN-08:00 2391599.86 14-AUG-13:30
CoolingCoils:PlantLoopCoolingDemand 27682.44 150405.05 05-JAN-08:00 2391599.86 14-AUG-13:30


Annual and Peak Values - Water

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
Water:Facility 13413.05 0.00 01-JAN-00:10 0.00 13-JUN-15:10
Water:HVAC 0.57 0.00 01-JAN-00:10 0.00 08-MAR-22:00
Humidifier:Water 0.57 0.00 01-JAN-00:10 0.00 08-MAR-22:00
General:Humidifier:Water 0.57 0.00 01-JAN-00:10 0.00 08-MAR-22:00
MainsWater:Facility 13413.05 0.00 01-JAN-00:10 0.00 13-JUN-15:10
MainsWater:HVAC 0.57 0.00 01-JAN-00:10 0.00 08-MAR-22:00
Humidifier:MainsWater 0.57 0.00 01-JAN-00:10 0.00 08-MAR-22:00
General:Humidifier:MainsWater 0.57 0.00 01-JAN-00:10 0.00 08-MAR-22:00
Water:Plant 13412.48 0.00 01-JAN-00:10 0.00 13-JUN-15:10
WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:Water 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
MainsWater:Plant 13412.48 0.00 01-JAN-00:10 0.00 13-JUN-15:10
WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
WaterUse:WaterSystems:MainsWater 2280.17 0.00 01-JAN-00:10 0.00 02-JAN-12:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
HeatRejection:Water 11132.31 0.00 01-JAN-00:10 0.00 13-JUN-15:00
General:HeatRejection:Water 11132.31 0.00 01-JAN-00:10 0.00 13-JUN-15:00
HeatRejection:MainsWater 11132.31 0.00 01-JAN-00:10 0.00 13-JUN-15:00
General:HeatRejection:MainsWater 11132.31 0.00 01-JAN-00:10 0.00 13-JUN-15:00


Annual and Peak Values - Other by Weight/Mass

Annual Value [kg] Minimum Value [kg/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [kg/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [m3] Minimum Value [m3/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [m3/s] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [L] Minimum Value [L] Timestamp of Minimum {TIMESTAMP} Maximum Value [L] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [GJ] Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 93542.36 228686.34 22-JAN-06:00 9643553.02 24-OCT-13:30
EnergyTransfer:Building 21096.02 93871.03 22-JAN-08:20 1561106.62 30-AUG-16:00
EnergyTransfer:Zone:BASEMENT 711.74 0.00 01-JAN-00:10 75518.68 13-NOV-06:10
Heating:EnergyTransfer 31.34 0.00 01-JAN-00:10 220247.47 06-FEB-06:10
Heating:EnergyTransfer:Zone:BASEMENT 4.94 0.00 01-JAN-00:10 23436.72 22-JUL-16:10
General:Heating:EnergyTransfer 31.34 0.00 01-JAN-00:10 220247.47 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:BASEMENT 4.94 0.00 01-JAN-00:10 23436.72 22-JUL-16:10
Cooling:EnergyTransfer 21064.68 93358.64 22-JAN-08:20 1561106.62 30-AUG-16:00
Cooling:EnergyTransfer:Zone:BASEMENT 706.80 0.00 01-JAN-00:10 75518.68 13-NOV-06:10
General:Cooling:EnergyTransfer 21064.68 93358.64 22-JAN-08:20 1561106.62 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:BASEMENT 706.80 0.00 01-JAN-00:10 75518.68 13-NOV-06:10
EnergyTransfer:Zone:CORE_BOTTOM 724.45 0.00 01-JAN-00:10 52916.76 21-AUG-09:20
Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_BOTTOM 724.45 0.00 01-JAN-00:10 52916.76 21-AUG-09:20
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM 724.45 0.00 01-JAN-00:10 52916.76 21-AUG-09:20
EnergyTransfer:Zone:CORE_MID 5377.21 0.00 01-JAN-00:10 474978.64 18-APR-13:50
Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:CORE_MID 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:CORE_MID 5377.21 0.00 01-JAN-00:10 474978.64 18-APR-13:50
General:Cooling:EnergyTransfer:Zone:CORE_MID 5377.21 0.00 01-JAN-00:10 474978.64 18-APR-13:50
EnergyTransfer:Zone:CORE_TOP 540.84 0.00 01-JAN-00:10 50160.73 18-APR-14:40
Heating:EnergyTransfer:Zone:CORE_TOP 0.22 0.00 01-JAN-00:10 34926.64 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:CORE_TOP 0.22 0.00 01-JAN-00:10 34926.64 06-FEB-06:10
Cooling:EnergyTransfer:Zone:CORE_TOP 540.62 0.00 01-JAN-00:10 50160.73 18-APR-14:40
General:Cooling:EnergyTransfer:Zone:CORE_TOP 540.62 0.00 01-JAN-00:10 50160.73 18-APR-14:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 101.84 0.00 01-JAN-00:10 11201.63 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 101.84 0.00 01-JAN-00:10 11201.63 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 101.84 0.00 01-JAN-00:10 11201.63 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 79.20 0.00 01-JAN-00:10 10281.61 11-SEP-09:20
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 79.20 0.00 01-JAN-00:10 10281.61 11-SEP-09:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 79.20 0.00 01-JAN-00:10 10281.61 11-SEP-09:20
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 131.65 0.00 01-JAN-00:10 15887.02 06-NOV-13:40
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 131.65 0.00 01-JAN-00:10 15887.02 06-NOV-13:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 131.65 0.00 01-JAN-00:10 15887.02 06-NOV-13:40
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 122.40 0.00 01-JAN-00:10 15177.23 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 122.40 0.00 01-JAN-00:10 15177.23 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 122.40 0.00 01-JAN-00:10 15177.23 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 784.04 0.00 01-JAN-00:10 98148.33 21-AUG-14:30
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.63 0.00 01-JAN-00:10 54126.40 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 2.63 0.00 01-JAN-00:10 54126.40 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 781.40 0.00 01-JAN-00:10 98148.33 21-AUG-14:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 781.40 0.00 01-JAN-00:10 98148.33 21-AUG-14:30
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 689.28 0.00 01-JAN-00:10 103775.36 03-MAY-09:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.07 0.00 01-JAN-00:10 30977.83 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 1.07 0.00 01-JAN-00:10 30977.83 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 688.21 0.00 01-JAN-00:10 103775.36 03-MAY-09:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 688.21 0.00 01-JAN-00:10 103775.36 03-MAY-09:00
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1102.65 0.00 01-JAN-00:10 152819.53 06-NOV-13:50
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.34 0.00 01-JAN-00:10 30241.18 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 0.34 0.00 01-JAN-00:10 30241.18 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1102.31 0.00 01-JAN-00:10 152819.53 06-NOV-13:50
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 1102.31 0.00 01-JAN-00:10 152819.53 06-NOV-13:50
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 738.44 0.00 01-JAN-00:10 119556.50 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.41 0.00 01-JAN-00:10 23735.83 06-FEB-06:10
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 0.41 0.00 01-JAN-00:10 23735.83 06-FEB-06:10
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 738.03 0.00 01-JAN-00:10 119556.50 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 738.03 0.00 01-JAN-00:10 119556.50 30-AUG-16:00
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 82.72 0.00 01-JAN-00:10 12331.18 06-FEB-05:10
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.42 0.00 01-JAN-00:10 12331.18 06-FEB-05:10
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 2.42 0.00 01-JAN-00:10 12331.18 06-FEB-05:10
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 80.31 0.00 01-JAN-00:10 10769.58 21-AUG-14:40
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 80.31 0.00 01-JAN-00:10 10769.58 21-AUG-14:40
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 72.86 0.00 01-JAN-00:10 10632.88 03-MAY-09:30
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.02 0.00 01-JAN-00:10 8759.23 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 1.02 0.00 01-JAN-00:10 8759.23 06-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 71.85 0.00 01-JAN-00:10 10632.88 03-MAY-09:30
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 71.85 0.00 01-JAN-00:10 10632.88 03-MAY-09:30
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 112.12 0.00 01-JAN-00:10 16629.89 06-NOV-14:20
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.83 0.00 01-JAN-00:10 9884.04 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 0.83 0.00 01-JAN-00:10 9884.04 06-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 111.29 0.00 01-JAN-00:10 16629.89 06-NOV-14:20
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 111.29 0.00 01-JAN-00:10 16629.89 06-NOV-14:20
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 76.80 0.00 01-JAN-00:10 12720.95 30-AUG-16:00
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.68 0.00 01-JAN-00:10 6342.86 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 0.68 0.00 01-JAN-00:10 6342.86 06-FEB-06:20
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 76.12 0.00 01-JAN-00:10 12720.95 30-AUG-16:00
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 76.12 0.00 01-JAN-00:10 12720.95 30-AUG-16:00
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 93.54 0.00 01-JAN-00:10 10272.89 10-OCT-05:20
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.00 0.00 01-JAN-00:10 4150.48 31-DEC-11:10
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 1.00 0.00 01-JAN-00:10 4150.48 31-DEC-11:10
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 92.54 0.00 01-JAN-00:10 10272.89 10-OCT-05:20
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM 92.54 0.00 01-JAN-00:10 10272.89 10-OCT-05:20
EnergyTransfer:Zone:MIDFLOOR_PLENUM 681.61 0.00 01-JAN-00:10 81198.10 22-MAY-05:20
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 8.90 0.00 01-JAN-00:10 28591.24 20-FEB-13:30
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM 8.90 0.00 01-JAN-00:10 28591.24 20-FEB-13:30
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 672.71 0.00 01-JAN-00:10 81198.10 22-MAY-05:20
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM 672.71 0.00 01-JAN-00:10 81198.10 22-MAY-05:20
EnergyTransfer:Zone:TOPFLOOR_PLENUM 112.66 0.00 01-JAN-00:10 20443.99 07-JUL-14:30
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 6.80 0.00 01-JAN-00:10 13965.29 06-FEB-06:20
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM 6.80 0.00 01-JAN-00:10 13965.29 06-FEB-06:20
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 105.86 0.00 01-JAN-00:10 20443.99 07-JUL-14:30
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM 105.86 0.00 01-JAN-00:10 20443.99 07-JUL-14:30
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.25 1046.44 05-JAN-08:00 7906.36 16-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.25 1046.44 05-JAN-08:00 7906.36 16-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 142.25 1046.44 05-JAN-08:00 7906.36 16-APR-18:10
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1314.92 3801.76 10-JAN-06:30 74571.13 16-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1314.92 3801.76 10-JAN-06:30 74571.13 16-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 1314.92 3801.76 10-JAN-06:30 74571.13 16-APR-18:10
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 128.44 2.61 10-JAN-09:30 7640.94 23-APR-18:10
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.09 0.00 01-JAN-00:10 520.41 22-JAN-06:30
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 0.09 0.00 01-JAN-00:10 520.41 22-JAN-06:30
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 128.35 0.00 04-JAN-04:40 7640.94 23-APR-18:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 128.35 0.00 04-JAN-04:40 7640.94 23-APR-18:10
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7174.36 88095.99 22-JAN-06:00 369889.36 09-AUG-21:10
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7174.36 88095.99 22-JAN-06:00 369889.36 09-AUG-21:10
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 7174.36 88095.99 22-JAN-06:00 369889.36 09-AUG-21:10
PlantLoopHeatingDemand:Facility 355.29 0.00 01-JAN-00:10 372655.06 21-DEC-07:10
PlantLoopHeatingDemand:Plant 321.87 0.00 01-JAN-00:10 40639.77 23-JAN-12:20
WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40639.77 23-JAN-12:20
General:WaterSystems:PlantLoopHeatingDemand 321.87 0.00 01-JAN-00:10 40639.77 23-JAN-12:20
EnergyTransfer:HVAC 27008.98 131497.36 27-JAN-22:00 2665135.32 07-AUG-13:00
HeatingCoils:EnergyTransfer 33.42 0.00 01-JAN-00:10 359420.23 21-DEC-07:10
PlantLoopHeatingDemand:HVAC 33.42 0.00 01-JAN-00:10 359420.23 21-DEC-07:10
HeatingCoils:PlantLoopHeatingDemand 33.42 0.00 01-JAN-00:10 359420.23 21-DEC-07:10
CoolingCoils:EnergyTransfer 24709.92 119772.48 05-JAN-08:00 2229849.36 07-AUG-14:40
HeatRecoveryForHeating:EnergyTransfer 32.93 0.00 01-JAN-00:10 240675.94 20-DEC-08:00
HeatRecoveryForCooling:EnergyTransfer 2232.72 0.00 01-JAN-00:10 599444.45 22-JUL-16:00
EnergyTransfer:Plant 45437.36 0.00 01-JAN-00:10 5791331.88 11-OCT-14:30
LoopToLoop:EnergyTransfer 15476.02 0.00 01-JAN-00:10 1896461.94 22-MAY-05:10
WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40639.77 23-JAN-12:20
WaterUse:WaterSystems:EnergyTransfer 321.87 0.00 01-JAN-00:10 40639.77 23-JAN-12:20
Boilers:EnergyTransfer 32.93 0.00 01-JAN-00:10 387855.82 21-DEC-07:10
Chillers:EnergyTransfer 13738.62 0.00 01-JAN-00:10 1838412.30 11-OCT-14:30
HeatRejection:EnergyTransfer 15867.92 0.00 01-JAN-00:10 2108853.97 24-OCT-13:30
General:HeatRejection:EnergyTransfer 15867.92 0.00 01-JAN-00:10 2108853.97 24-OCT-13:30
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [GJ] HVAC Zone Eq & Other Sensible Air Cooling [GJ] HVAC Terminal Unit Sensible Air Heating [GJ] HVAC Terminal Unit Sensible Air Cooling [GJ] HVAC Input Heated Surface Heating [GJ] HVAC Input Cooled Surface Cooling [GJ] People Sensible Heat Addition [GJ] Lights Sensible Heat Addition [GJ] Equipment Sensible Heat Addition [GJ] Window Heat Addition [GJ] Interzone Air Transfer Heat Addition [GJ] Infiltration Heat Addition [GJ] Opaque Surface Conduction and Other Heat Addition [GJ] Equipment Sensible Heat Removal [GJ] Window Heat Removal [GJ] Interzone Air Transfer Heat Removal [GJ] Infiltration Heat Removal [GJ] Opaque Surface Conduction and Other Heat Removal [GJ]
BASEMENT 0.000 0.000 4.940 -706.802 0.000 0.000 92.680 177.742 424.397 0.000 0.000 0.000 7.043 0.000 0.000 0.000 0.000 -0.001
CORE_BOTTOM 0.000 0.000 0.000 -724.446 0.000 0.000 83.427 159.625 321.286 0.000 0.000 0.000 160.108 0.000 0.000 0.000 0.000 -0.003
CORE_MID 0.000 0.000 0.000 -5377.198 0.000 0.000 835.911 1596.246 3212.845 0.000 0.000 0.000 0.031 0.000 0.000 0.000 0.000 -267.804
CORE_TOP 0.000 0.000 0.221 -540.619 0.000 0.000 84.325 159.625 321.285 0.000 0.000 0.000 0.013 0.000 0.000 0.000 0.000 -24.837
PERIMETER_BOT_ZN_3 0.000 0.000 0.000 -101.837 0.000 0.000 10.542 13.768 40.342 31.360 0.000 0.383 32.655 0.000 -25.390 0.000 -1.824 0.000
PERIMETER_BOT_ZN_2 0.000 0.000 0.000 -79.199 0.000 0.000 6.782 8.855 25.998 45.647 0.000 0.259 8.234 0.000 -15.368 0.000 -1.207 -0.000
PERIMETER_BOT_ZN_1 0.000 0.000 0.000 -131.646 0.000 0.000 10.491 13.656 40.343 78.636 0.000 0.364 14.232 0.000 -24.122 0.000 -1.953 -0.001
PERIMETER_BOT_ZN_4 0.000 0.000 0.000 -122.405 0.000 0.000 6.749 8.854 25.998 43.553 0.000 0.225 57.874 0.000 -19.399 0.000 -1.448 0.000
PERIMETER_MID_ZN_3 0.000 0.000 2.634 -781.391 0.000 0.000 107.319 137.840 403.423 320.990 0.000 8.624 70.130 0.000 -231.084 0.000 -38.484 0.000
PERIMETER_MID_ZN_2 0.000 0.000 1.068 -688.198 0.000 0.000 50.318 88.585 259.981 454.433 0.000 5.372 4.761 0.000 -148.938 0.000 -27.382 -0.000
PERIMETER_MID_ZN_1 0.000 0.000 0.336 -1102.292 0.000 0.000 105.267 136.651 403.429 784.014 0.000 8.023 0.031 0.000 -235.956 0.000 -45.104 -54.368
PERIMETER_MID_ZN_4 0.000 0.000 0.414 -738.021 0.000 0.000 68.627 88.577 259.979 445.742 0.000 5.285 63.651 0.000 -165.233 0.000 -29.021 -0.000
PERIMETER_TOP_ZN_3 0.000 0.000 2.416 -80.305 0.000 0.000 10.849 13.784 40.342 31.962 0.000 1.001 6.261 0.000 -21.869 0.000 -4.442 -0.000
PERIMETER_TOP_ZN_2 0.000 0.000 1.016 -71.844 0.000 0.000 6.902 8.859 25.998 45.364 0.000 0.630 0.525 0.000 -14.259 0.000 -3.190 -0.001
PERIMETER_TOP_ZN_1 0.000 0.000 0.829 -111.288 0.000 0.000 10.598 13.665 40.343 78.172 0.000 0.937 0.002 0.000 -22.732 0.000 -5.313 -5.212
PERIMETER_TOP_ZN_4 0.000 0.000 0.680 -76.118 0.000 0.000 6.934 8.858 25.998 44.416 0.000 0.632 7.838 0.000 -15.831 0.000 -3.406 -0.001
DATACENTER_BOT_ZN_6 0.000 0.000 0.000 -142.250 0.000 0.000 0.948 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -17.218
DATACENTER_MID_ZN_6 0.000 0.000 0.000 -1314.926 0.000 0.000 9.482 46.396 1538.806 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -279.757
DATACENTER_TOP_ZN_6 0.000 0.000 0.087 -128.349 0.000 0.000 0.949 4.640 153.881 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -31.207
DATACENTER_BASEMENT_ZN_6 0.000 0.000 0.000 -7174.374 0.000 0.000 20.106 50.116 7494.857 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -390.704
GROUNDFLOOR_PLENUM 1.004 -92.536 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.675 94.896 0.000 0.000 0.000 -4.038 0.000
MIDFLOOR_PLENUM 8.899 -672.704 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 12.200 720.684 0.000 0.000 0.000 -69.079 0.000
TOPFLOOR_PLENUM 6.799 -105.859 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 1.066 105.261 0.000 0.000 0.000 -7.266 -0.001
Total Facility 16.702 -871.100 14.642 -20193.508 0.000 0.000 1529.205 2740.978 15213.411 2404.288 0.000 45.676 1354.229 0.000 -940.182 0.000 -243.159 -1071.116


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 20-MAR-03:02 0.00 0.00 0.00 -110471.10 0.00 0.00 0.00 862.23 13457.54 0.00 0.00 0.00 96151.33 0.00 -0.00 0.00 0.00 0.00
CORE_BOTTOM 18-DEC-04:02 0.00 0.00 0.00 -92273.06 0.00 0.00 0.00 774.34 8057.15 0.00 0.00 0.00 83441.57 0.00 -0.00 0.00 0.00 0.00
CORE_MID 01-MAY-03:02 0.00 0.00 0.00 -805825.92 0.00 0.00 0.00 7743.41 80571.20 0.00 0.00 0.00 717511.31 0.00 -0.00 0.00 0.00 0.00
CORE_TOP 01-MAY-03:02 0.00 0.00 0.00 -80133.20 0.00 0.00 0.00 774.34 8057.12 0.00 0.00 0.00 71301.74 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 21-AUG-03:02 0.00 0.00 0.00 -14199.66 0.00 0.00 0.00 97.23 1011.70 0.00 0.00 10.13 13552.06 0.00 -471.45 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 07-MAY-09:22 0.00 0.00 0.00 -16840.93 0.00 0.00 24.23 38.49 488.98 9992.70 0.00 31.43 6265.10 0.00 -0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 11-NOV-13:22 0.00 0.00 0.00 -20999.58 0.00 0.00 35.60 59.73 758.78 15348.75 0.00 0.00 4859.77 0.00 -0.00 0.00 -63.05 0.00
PERIMETER_BOT_ZN_4 03-SEP-15:51 0.00 0.00 0.00 -22562.17 0.00 0.00 21.44 38.49 488.98 10689.44 0.00 80.93 11242.89 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 25-JUN-16:31 0.00 0.00 0.00 -144609.24 0.00 0.00 429.99 597.26 7587.73 42183.33 0.00 1128.34 92682.60 0.00 -0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 29-MAY-08:42 0.00 0.00 0.00 -180212.66 0.00 0.00 224.81 384.90 4889.82 109977.31 0.00 0.00 64836.59 0.00 -0.00 0.00 -100.77 0.00
PERIMETER_MID_ZN_1 01-JAN-14:11 0.00 0.00 0.00 -206661.78 0.00 0.00 331.83 597.27 7587.84 154558.06 0.00 0.00 44575.45 0.00 -0.00 0.00 -988.69 0.00
PERIMETER_MID_ZN_4 11-JUN-17:11 0.00 0.00 0.00 -191349.64 0.00 0.00 0.00 384.90 4889.79 89581.99 0.00 1127.91 95365.06 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 25-JUN-16:31 0.00 0.00 0.00 -17180.45 0.00 0.00 40.43 59.73 758.77 4069.28 0.00 125.07 12127.17 0.00 -0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 29-MAY-08:42 0.00 0.00 0.00 -18540.35 0.00 0.00 22.05 38.49 488.98 10935.72 0.00 0.00 7071.33 0.00 -0.00 0.00 -16.23 0.00
PERIMETER_TOP_ZN_1 01-JAN-15:02 0.00 0.00 0.00 -22569.38 0.00 0.00 33.85 59.73 758.78 12285.57 0.00 0.00 9594.41 0.00 -0.00 0.00 -162.96 0.00
PERIMETER_TOP_ZN_4 29-MAY-16:01 0.00 0.00 0.00 -21246.60 0.00 0.00 20.06 38.49 488.98 11035.28 0.00 103.63 9560.16 0.00 -0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 16-APR-18:02 0.00 0.00 0.00 -7906.33 0.00 0.00 0.00 22.51 7794.42 0.00 0.00 0.00 89.40 0.00 -0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 16-APR-18:02 0.00 0.00 0.00 -74570.87 0.00 0.00 0.00 225.07 77944.22 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -3598.42
DATACENTER_TOP_ZN_6 23-APR-18:03 0.00 0.00 0.00 -7640.92 0.00 0.00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -176.01
DATACENTER_BASEMENT_ZN_6 09-AUG-21:13 0.00 0.00 0.00 -371121.41 0.00 0.00 114.68 486.22 379632.52 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -9112.02
GROUNDFLOOR_PLENUM 10-OCT-05:15 0.00 -14016.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14077.56 0.00 -0.00 0.00 -61.37 0.00
MIDFLOOR_PLENUM 22-MAY-05:13 0.00 -127032.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 309.53 126723.14 0.00 -0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 07-JUL-14:30 0.00 -20443.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.49 20330.55 0.00 -0.00 0.00 0.00 0.00
Total Facility 21-AUG-05:02 0.00 -49783.94 0.00 -1909826.22 0.00 0.00 15652.28 29009.37 623236.89 0.00 0.00 330.32 1303994.63 0.00 -12613.33 0.00 0.00 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [W] HVAC Zone Eq & Other Sensible Air Cooling [W] HVAC Terminal Unit Sensible Air Heating [W] HVAC Terminal Unit Sensible Air Cooling [W] HVAC Input Heated Surface Heating [W] HVAC Input Cooled Surface Cooling [W] People Sensible Heat Addition [W] Lights Sensible Heat Addition [W] Equipment Sensible Heat Addition [W] Window Heat Addition [W] Interzone Air Transfer Heat Addition [W] Infiltration Heat Addition [W] Opaque Surface Conduction and Other Heat Addition [W] Equipment Sensible Heat Removal [W] Window Heat Removal [W] Interzone Air Transfer Heat Removal [W] Infiltration Heat Removal [W] Opaque Surface Conduction and Other Heat Removal [W]
BASEMENT 22-JUL-16:02 0.00 0.00 25013.68 0.00 0.00 0.00 520.12 862.23 13457.54 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -39853.57
CORE_BOTTOM - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_MID - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CORE_TOP 06-FEB-05:01 0.00 0.00 58718.54 0.00 0.00 0.00 0.00 1548.68 8057.12 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -68324.34
PERIMETER_BOT_ZN_3 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 06-FEB-05:01 0.00 0.00 108109.81 0.00 0.00 0.00 0.00 1944.52 10116.97 0.00 0.00 0.00 0.00 0.00 -33808.85 0.00 -4628.60 -81733.86
PERIMETER_MID_ZN_2 06-FEB-05:01 0.00 0.00 94711.65 0.00 0.00 0.00 0.00 1253.13 6519.76 0.00 0.00 0.00 0.00 0.00 -23321.03 0.00 -3219.58 -75943.93
PERIMETER_MID_ZN_1 21-DEC-06:01 0.00 0.00 120985.99 0.00 0.00 0.00 1461.00 1944.57 10117.12 0.00 0.00 0.00 0.00 0.00 -42986.85 0.00 -2358.10 -89163.73
PERIMETER_MID_ZN_4 21-DEC-06:01 0.00 0.00 83051.21 0.00 0.00 0.00 941.49 1253.13 6519.72 0.00 0.00 0.00 0.00 0.00 -28369.19 0.00 -1571.37 -61824.98
PERIMETER_TOP_ZN_3 05-FEB-07:43 0.00 0.00 14470.80 0.00 0.00 0.00 88.34 86.93 758.77 0.00 0.00 0.00 0.00 0.00 -3782.50 0.00 -2221.26 -9401.08
PERIMETER_TOP_ZN_2 06-FEB-04:01 0.00 0.00 13460.87 0.00 0.00 0.00 0.00 62.66 651.98 0.00 0.00 0.00 0.00 0.00 -1827.58 0.00 -349.47 -11998.46
PERIMETER_TOP_ZN_1 06-FEB-04:01 0.00 0.00 15923.27 0.00 0.00 0.00 0.00 97.23 1011.71 0.00 0.00 0.00 0.00 0.00 -2961.61 0.00 -570.76 -13499.85
PERIMETER_TOP_ZN_4 06-FEB-04:01 0.00 0.00 12850.81 0.00 0.00 0.00 0.00 62.66 651.97 0.00 0.00 0.00 0.00 0.00 -2029.68 0.00 -384.93 -11150.84
DATACENTER_BOT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 10-JAN-04:45 0.00 0.00 523.18 0.00 0.00 0.00 0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 0.00 -2494.30
DATACENTER_BASEMENT_ZN_6 - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 21-DEC-05:01 10890.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -816.72 -10073.94
MIDFLOOR_PLENUM 22-MAY-03:02 76717.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -220.14 -76497.70
TOPFLOOR_PLENUM 09-NOV-06:02 17407.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -0.00 0.00 -483.32 -16924.09
Total Facility 06-FEB-06:01 -571785.36 553093.32 499569.19 -553093.32 0.00 0.00 19239.26 29009.37 386654.09 0.00 0.00 0.00 0.00 0.00 -144741.17 0.00 -7038.43 -210906.96



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 9.7720 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.9417 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 91.1116 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 82.7191 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 9.4128 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 8.9357 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.4789 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.4789 0.2191 1.0000 Not calculated 1.2002 0.2191    
AIRLOOP DATACENTER BASEMENT 21.3329 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.3331 0.0159 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4657 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4657 0.0336 1.0000 Not calculated 0.0156 0.0336    
AIRLOOP DATACENTER MID 4.4256 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.4256 0.0353 1.0000 Not calculated 0.1563 0.0353    
AIRLOOP DATACENTER TOP 0.4514 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4514 0.0346 1.0000 Not calculated 0.0156 0.0346    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [m3/s] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] System Primary Airflow - Vps [m3/s] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [m3/s] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
VAV_BOT WITH REHEAT 4.8860 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.7887 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_MID WITH REHEAT 45.5558 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 26.9693 0.0000 1.0000 Not calculated 0.0000 0.0000    
VAV_TOP WITH REHEAT 4.7064 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 2.7739 0.0000 1.0000 Not calculated 0.0000 0.0000    
CAV_BAS 5.4789 0.0000 149.6021 1.0000 Calculated from schedules 1.2002 5.4789 1.0000 1.0000 Not calculated 1.2002 0.2191    
AIRLOOP DATACENTER BASEMENT 21.3329 0.0000 42.1814 1.0000 Calculated from schedules 0.3384 21.3329 1.0000 1.0000 Not calculated 0.3384 0.0159    
AIRLOOP DATACENTER BOT 0.4657 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4657 1.0000 1.0000 Not calculated 0.0156 0.0336    
AIRLOOP DATACENTER MID 4.4256 0.0000 19.4861 1.0000 Calculated from schedules 0.1563 4.4256 1.0000 1.0000 Not calculated 0.1563 0.0353    
AIRLOOP DATACENTER TOP 0.4514 0.0000 1.9486 1.0000 Calculated from schedules 0.0156 0.4514 1.0000 1.0000 Not calculated 0.0156 0.0346    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [m3/s-person] Zone Population - Pz Area Outdoor Air Rate - Ra [m3/s-m2] Zone Floor Area - Az [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [m3/s]
BASEMENT CAV_BAS 0.000000 149.6021 0.000432 2779.43 1.2002 1.0000 1.2002 1.000 1.2002
CORE_BOTTOM VAV_BOT WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
CORE_MID VAV_MID WITH REHEAT 0.000000 1343.5320 0.000432 24961.20 0.0000 1.0000 0.0000 1.000 0.0000
CORE_TOP VAV_TOP WITH REHEAT 0.000000 134.3532 0.000432 2496.12 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT 0.000000 168.6939 0.000432 3134.13 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT 0.000000 168.6975 0.000432 3134.20 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT 0.000000 108.7127 0.000432 2019.75 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT 0.000000 16.8694 0.000432 313.41 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT 0.000000 16.8698 0.000432 313.42 0.0000 1.0000 0.0000 1.000 0.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT 0.000000 10.8713 0.000432 201.98 0.0000 1.0000 0.0000 1.000 0.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID 0.000000 19.4861 0.000432 362.03 0.1563 1.0000 0.1563 1.000 0.1563
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP 0.000000 1.9486 0.000432 36.20 0.0156 1.0000 0.0156 1.000 0.0156
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT 0.000000 42.1814 0.000432 783.68 0.3384 1.0000 0.3384 1.000 0.3384


System Ventilation Parameters

People Outdoor Air Rate - Rp [m3/s-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [m3/s-m2] Sum of Zone Floor Area - Az-sum [m2] Breathing Zone Outdoor Airflow - Vbz [m3/s] Cooling Zone Outdoor Airflow - Voz-clg [m3/s] Heating Zone Outdoor Airflow - Voz-htg [m3/s]
VAV_BOT WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
VAV_MID WITH REHEAT   0.00 0.000432 35269.0328 0.0000 0.0000 0.0000
VAV_TOP WITH REHEAT   0.00 0.000432 3526.9033 0.0000 0.0000 0.0000
CAV_BAS 0.000000 149.60 0.000432 2779.4266 1.2002 1.2002 1.2002
AIRLOOP DATACENTER BASEMENT 0.000000 42.18 0.000432 783.6794 0.3384 0.3384 0.3384
AIRLOOP DATACENTER BOT 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156
AIRLOOP DATACENTER MID 0.000000 19.49 0.000432 362.0274 0.1563 0.1563 0.1563
AIRLOOP DATACENTER TOP 0.000000 1.95 0.000432 36.2027 0.0156 0.0156 0.0156


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4789 5.4789 5.4789 No 1.2002 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.6390 5.6390 1.8891 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 52.7979 52.7979 18.4265 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.2302 5.2302 1.8881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9083 0.9083 0.2371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9292 0.9292 0.1858 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0994 1.0994 0.2375 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1961 1.1961 0.2392 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 8.4237 8.4237 2.3165 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 9.4880 9.4880 1.8976 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.3478 10.3478 2.3179 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 10.0541 10.0541 2.0108 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9675 0.9675 0.2370 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.9693 0.9693 0.1939 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.1553 1.1553 0.2368 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 1.0905 1.0905 0.2181 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4657 0.4657 0.4657 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.4256 4.4256 4.4256 No 0.1563 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4514 0.4514 0.4514 No 0.0156 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.3329 21.3329 21.3329 No 0.3384 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Cooling - Voz-clg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 9.7720 8.9417 9.7720 2.7887 0.0000 1.0000
VAV_MID WITH REHEAT 91.1116 82.7191 91.1116 26.9693 0.0000 1.0000
VAV_TOP WITH REHEAT 9.4128 8.9357 9.4128 2.7739 0.0000 1.0000
CAV_BAS 5.4789 5.4789 5.4789 5.4789 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.3329 21.3331 21.3329 21.3329 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4657 0.4657 0.4657 0.4657 0.0156 1.0000
AIRLOOP DATACENTER MID 4.4256 4.4256 4.4256 4.4256 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4514 0.4514 0.4514 0.4514 0.0156 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [m3/s] Zone Discharge Airflow - Vdz [m3/s] Minimum Zone Primary Airflow - Vpz-min [m3/s] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [m3/s] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
BASEMENT CAV_BAS AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 5.4789 5.4789 5.4789 No 1.2002 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_BOTTOM VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.8195 2.8195 1.8891 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_MID VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 26.3990 26.3990 18.4265 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
CORE_TOP VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 2.6151 2.6151 1.8881 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_3 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4541 0.4541 0.2371 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_2 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4646 0.4646 0.1858 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_1 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5497 0.5497 0.2375 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_BOT_ZN_4 VAV_BOT WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5981 0.5981 0.2392 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_3 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.2119 4.2119 2.3165 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_2 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 4.7440 4.7440 1.8976 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_1 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.1739 5.1739 2.3179 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_MID_ZN_4 VAV_MID WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 5.0270 5.0270 2.0108 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_3 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4837 0.4837 0.2370 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_2 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.4846 0.4846 0.1939 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_1 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5777 0.5777 0.2368 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
PERIMETER_TOP_ZN_4 VAV_TOP WITH REHEAT AIRTERMINAL:SINGLEDUCT:VAV:REHEAT 0.5453 0.5453 0.2181 No 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BOT_ZN_6 AIRLOOP DATACENTER BOT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4657 0.4657 0.4657 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_MID_ZN_6 AIRLOOP DATACENTER MID AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 4.4256 4.4256 4.4256 No 0.1563 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_TOP_ZN_6 AIRLOOP DATACENTER TOP AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 0.4514 0.4514 0.4514 No 0.0156 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
DATACENTER_BASEMENT_ZN_6 AIRLOOP DATACENTER BASEMENT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 21.3329 21.3329 21.3329 No 0.3384 1.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [m3/s] System Primary Airflow - Vps [m3/s] Sum of Zone Discharge Airflow - Vdz-sum [m3/s] Sum of Min Zone Primary Airflow - Vpz-min [m3/s] Zone Outdoor Airflow Heating - Voz-htg [m3/s] Zone Ventilation Efficiency - Evz-min
VAV_BOT WITH REHEAT 4.8860 2.7887 2.7887 2.7887 0.0000 1.0000
VAV_MID WITH REHEAT 45.5558 26.9693 26.9693 26.9693 0.0000 1.0000
VAV_TOP WITH REHEAT 4.7064 2.7739 2.7739 2.7739 0.0000 1.0000
CAV_BAS 5.4789 5.4789 5.4789 5.4789 1.2002 1.0000
AIRLOOP DATACENTER BASEMENT 21.3329 21.3329 21.3329 21.3329 0.3384 1.0000
AIRLOOP DATACENTER BOT 0.4657 0.4657 0.4657 0.4657 0.0156 1.0000
AIRLOOP DATACENTER MID 4.4256 4.4256 4.4256 4.4256 0.1563 1.0000
AIRLOOP DATACENTER TOP 0.4514 0.4514 0.4514 0.4514 0.0156 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Sec1.1A-General Information

Data
Weather File RUNPERIOD 1 ** Tampa-MacDill AFB FL USA TMY3 WMO#=747880
Total gross floor area [m2] 46320.38
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [m2] Regularly Occupied Area [m2] Unconditioned Area [m2] Typical Hours/Week in Operation [hr/wk]
BASEMENT 2779.43 2779.43 0.00 113.98
CORE_BOTTOM 2496.12 2496.12 0.00 113.98
CORE_MID 2496.12 2496.12 0.00 113.98
CORE_TOP 2496.12 2496.12 0.00 113.98
PERIMETER_BOT_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_BOT_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_BOT_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_BOT_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_MID_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_MID_ZN_2 201.98 201.98 0.00 96.54
PERIMETER_MID_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_MID_ZN_4 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_3 313.41 313.41 0.00 113.98
PERIMETER_TOP_ZN_2 201.98 201.98 0.00 113.98
PERIMETER_TOP_ZN_1 313.42 313.42 0.00 113.98
PERIMETER_TOP_ZN_4 201.98 201.98 0.00 113.98
DATACENTER_BOT_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_MID_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_TOP_ZN_6 36.20 36.20 0.00 113.98
DATACENTER_BASEMENT_ZN_6 783.68 783.68 0.00 113.98
GROUNDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
MIDFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
TOPFLOOR_PLENUM 3563.11 3563.11 0.00 0.00
Totals 46320.38 46320.38 0.00  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 1.50
Number of hours cooling loads not met 754.67
Number of hours not met 756.17


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [GJ] Electricity Demand [W] Natural Gas Energy Use [GJ] Natural Gas Demand [W] Gasoline Use [GJ] Gasoline Demand [W] Diesel Use [GJ] Diesel Demand [W] Coal Use [GJ] Coal Demand [W] Fuel Oil No 1 Use [GJ] Fuel Oil No 1 Demand [W] Fuel Oil No 2 Use [GJ] Fuel Oil No 2 Demand [W] Propane Use [GJ] Propane Demand [W] Other Fuel 1 Use [GJ] Other Fuel 1 Demand [W] Other Fuel 2 Use [GJ] Other Fuel 2 Demand [W] District Cooling Use [GJ] District Cooling Demand [W] District Heating Use [GJ] District Heating Demand [W]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 48.57 467400.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 5101.82 443337.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- LightsWired 2740.98 255624.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- General 447.11 37611.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- MiscPlug 5871.99 320838.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- DataCenterPlugLoads 9341.42 473165.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Transformer 59.77 3723.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLift 1848.78 113101.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- ElevatorLightsFan 5.83 376.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2510.59 261005.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 1113.93 73611.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- General 1896.49 93886.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- General 1.54 4283.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 60.30 5613.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- WaterUse 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 595.33 73397.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [GJ] Total Energy Use [GJ]
Electricity 15213.41 31000.55
Natural Gas 0.00 643.90
Additional 0.00 0.00
Total 15213.41 31644.45


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [GJ]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [MJ/m2]
Interior Lighting (All) 59.17
Space Heating 0.00
Space Cooling 110.14
Fans (All) 54.20
Service Water Heating 0.00
Receptacle Equipment 328.44
Miscellaneous (All) 669.26
Subtotal 669.26


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [MJ/m2]
Space Heating 1.05
Service Water Heating 12.85
Miscellaneous (All) 13.90
Subtotal 13.90


EAp2-17c. Energy Use Intensity - Additional

Additional [MJ/m2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 8.66
Space Heating 0.15
Space Cooling 16.12
Fans (All) 7.93
Service Water Heating 1.88
Receptacle Equipment 48.08
Miscellaneous 17.17


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
EXTERIOR_LIGHTING_SCHEDULE_A 6570. 6570.
EXTERIOR_LIGHTING_SCHEDULE_B 8103. 8760.
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 4472. 4472.
EXTERIOR_LIGHTING_SCHEDULE_B_2016 7665. 8760.
EXTERIOR_LIGHTING_SCHEDULE_C_2016 6752. 8760.
ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_ALWAYS_ON 8760. 8760.
EXTERIOR_LGT_189_1 6828. 8760.
ALWAYS_OFF 0. 0.
LTG_SCH_OFFICE 2393. 8760.
LTG_SCH_DATACENTER 2921. 8760.
EXTERIOR_LIGHT_SCH 4380. 4380.
BLDG_EQUIP_SCH 4487. 8760.
DATACENTER_EQUIP_SCH 5478. 8760.
BLDG_OCC_SCH 2528. 5992.
BLDG_OCC_SCH_W_SB 1878. 5056.
BLDG_OCC_SCH_WO_SB 2557. 5992.
BLDG_ELEVATORS 2270. 8760.
ELEV_LIGHT_FAN_SCH_24_7 8760. 8760.
ELEV_LIGHT_FAN_SCH_ADD_DF 2154. 8760.
BLDG_SWH_SCH 1474. 6570.
WORK_EFF_SCH 0. 0.
INFIL_SCH 3976. 3976.
INFIL_SCH_PNNL 5172. 8760.
INFIL_HALF_ON_SCH 6368. 8760.
FAN_SCH 8760. 8760.
REHEATCOILAVAILSCHED 8760. 8760.
COOLINGCOILAVAILSCHED 8760. 8760.
MINOA_MOTORIZEDDAMPER_SCHED 4472. 4472.
MINOA_SCHED 8760. 8760.
CORE_BOTTOM SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_MID SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_MID SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
CORE_TOP SUB CAT LATENT FRACT SCHED 438. 8760.
CORE_TOP SUB CAT SENSIBLE FRACT SCHED 1752. 8760.
SUPPLYFANSCH 8760. 8760.
PERIMETER_MID_ZN_2_MDP_SCH 1565. 7824.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [C] Days with Same 11am Value 11pm First Wednesday [C] Days with Same 11pm Value
HTGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL January 18.00 365 18.00 365
CLGSETP_DC_SCH DATACENTER COOLING SETPOINTS DUAL SP CONTROL July 27.00 365 27.00 365
HTGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL January 21.00 365 15.60 365
CLGSETP_SCH_YES_OPTIMUM CORE_BOTTOM DUAL SP CONTROL July 24.00 365 26.70 365



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Heat Index Hours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 7478.83 1281.17 0.00 0.00 0.00
CORE_BOTTOM 8695.83 64.17 0.00 0.00 0.00
CORE_MID 8759.50 0.50 0.00 0.00 0.00
CORE_TOP 8754.17 5.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 8707.50 52.50 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 8621.67 138.33 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 8537.00 223.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 7562.00 1198.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 8564.00 196.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 8266.00 494.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 8238.33 521.67 0.00 0.00 0.00
PERIMETER_MID_ZN_4 7811.50 948.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 8427.83 332.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 8139.50 620.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 8109.17 650.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 7817.83 942.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 3499.33 5260.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 3607.83 5152.17 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 3559.67 5200.33 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 2825.83 5934.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 8760.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 8444.00 316.00 0.00 0.00 0.00
Min 2825.83 0.00 0.00 0.00 0.00
Max 8760.00 5934.17 0.00 0.00 0.00
Average 7475.97 1284.03 0.00 0.00 0.00
Sum 171947.33 29532.67 0.00 0.00 0.00


Heat Index OccupantHours

Safe (≤ 26.7°C) [hr] Caution (> 26.7, ≤ 32.2°C) [hr] Extreme Caution (> 32.2, ≤ 39.4°C) [hr] Danger (> 39.4, ≤ 51.7°C) [hr] Extreme Danger (> 51.7°C) [hr]
BASEMENT 364798.67 3817.33 0.00 0.00 0.00
CORE_BOTTOM 330727.00 86.00 0.00 0.00 0.00
CORE_MID 330813.00 0.00 0.00 0.00 0.00
CORE_TOP 330809.00 4.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18354.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24909.00 0.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 525.00 1743.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 523.50 1744.50 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 516.00 1752.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 24521.33 78873.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 364798.67 78873.67 0.00 0.00 0.00
Average 76507.93 3826.98 0.00 0.00 0.00
Sum 1759682.50 88020.50 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 4144.67 4615.33 0.00 0.00 0.00
CORE_BOTTOM 7146.83 1613.17 0.00 0.00 0.00
CORE_MID 6812.83 1947.17 0.00 0.00 0.00
CORE_TOP 6686.33 2073.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 6520.17 2239.83 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 6874.33 1885.67 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 6235.83 2524.17 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 5875.67 2884.33 0.00 0.00 0.00
PERIMETER_MID_ZN_3 6385.33 2374.67 0.00 0.00 0.00
PERIMETER_MID_ZN_2 6279.33 2480.67 0.00 0.00 0.00
PERIMETER_MID_ZN_1 6035.00 2725.00 0.00 0.00 0.00
PERIMETER_MID_ZN_4 6111.50 2648.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 6395.00 2365.00 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 6300.50 2459.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 6057.17 2702.83 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 6155.83 2604.17 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 5749.33 3010.67 0.00 0.00 0.00
DATACENTER_MID_ZN_6 5757.17 3002.83 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 5732.00 3028.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 5241.33 3518.67 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 5936.67 2823.33 0.00 0.00 0.00
MIDFLOOR_PLENUM 5647.50 3112.50 0.00 0.00 0.00
TOPFLOOR_PLENUM 4450.83 4309.17 0.00 0.00 0.00
Min 4144.67 1613.17 0.00 0.00 0.00
Max 7146.83 4615.33 0.00 0.00 0.00
Average 6023.09 2736.91 0.00 0.00 0.00
Sum 138531.17 62948.83 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BASEMENT 287829.83 80786.17 0.00 0.00 0.00
CORE_BOTTOM 327853.00 2960.00 0.00 0.00 0.00
CORE_MID 327707.00 3106.00 0.00 0.00 0.00
CORE_TOP 325783.00 5030.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_2 24909.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_1 38925.00 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_4 24909.00 0.00 0.00 0.00 0.00
PERIMETER_MID_ZN_3 38894.83 30.17 0.00 0.00 0.00
PERIMETER_MID_ZN_2 18340.50 13.50 0.00 0.00 0.00
PERIMETER_MID_ZN_1 38902.50 22.50 0.00 0.00 0.00
PERIMETER_MID_ZN_4 24900.67 8.33 0.00 0.00 0.00
PERIMETER_TOP_ZN_3 38851.50 73.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_2 24889.83 19.17 0.00 0.00 0.00
PERIMETER_TOP_ZN_1 38867.50 57.50 0.00 0.00 0.00
PERIMETER_TOP_ZN_4 24897.00 12.00 0.00 0.00 0.00
DATACENTER_BOT_ZN_6 726.67 1541.33 0.00 0.00 0.00
DATACENTER_MID_ZN_6 722.67 1545.33 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 712.83 1555.17 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 37014.83 66380.17 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 327853.00 80786.17 0.00 0.00 0.00
Average 73241.83 7093.08 0.00 0.00 0.00
Sum 1684562.17 163140.83 0.00 0.00 0.00


Heating SET Hours

SET ≤ 12.2°C Hours (°C) SET ≤ 12.2°C OccupantHours (°C) Longest SET ≤ 12.2°C Duration [hr] Start Time of the Longest SET ≤ 12.2°C Duration
None        


Cooling SET Hours

SET > 30°C Hours (°C) SET > 30°C OccupantHours (°C) Longest SET > 30°C Duration [hr] Start Time of the Longest SET > 30°C Duration
None        



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2023-10-16 09:04:59

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 8760.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 8760.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 8760.00 0.00
Average 0.00 0.00 4570.43 0.00
Sum 0.00 0.00 105120.00 0.00


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
BASEMENT 0.00 0.00 0.00 0.00
CORE_BOTTOM 0.00 0.00 0.00 0.00
CORE_MID 0.00 0.00 0.00 0.00
CORE_TOP 0.00 0.00 0.00 0.00
PERIMETER_BOT_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_BOT_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_BOT_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_MID_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_2 0.00 0.00 18354.00 0.00
PERIMETER_MID_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_MID_ZN_4 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_3 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_2 0.00 0.00 24909.00 0.00
PERIMETER_TOP_ZN_1 0.00 0.00 38925.00 0.00
PERIMETER_TOP_ZN_4 0.00 0.00 24909.00 0.00
DATACENTER_BOT_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_MID_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_TOP_ZN_6 0.00 0.00 0.00 0.00
DATACENTER_BASEMENT_ZN_6 0.00 0.00 0.00 0.00
GROUNDFLOOR_PLENUM 0.00 0.00 0.00 0.00
MIDFLOOR_PLENUM 0.00 0.00 0.00 0.00
TOPFLOOR_PLENUM 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 38925.00 0.00
Average 0.00 0.00 16367.35 0.00
Sum 0.00 0.00 376449.00 0.00



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 2A

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_FL_TAMPA

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C]
January 13.572
February 15.490
March 17.074
April 21.231
May 26.899
June 27.606
July 27.937
August 27.434
September 26.232
October 24.234
November 18.911
December 15.677
   
Annual Sum or Average 21.892
Minimum of Months 13.572
Maximum of Months 27.937



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.569420E+11 106684.89 23-JAN-04:03 8.00 6.50 0.566824E+10 7499.42 12-JAN-10:09 8.00 6.50
February 0.497781E+11 109574.77 13-FEB-04:03 6.38 2.53 0.514041E+10 7499.11 09-FEB-10:00 6.38 2.53
March 0.571125E+11 110548.58 20-MAR-03:02 12.55 8.37 0.613292E+10 7499.70 23-MAR-09:20 16.97 14.65
April 0.526144E+11 106601.17 10-APR-03:02 13.30 9.00 0.544938E+10 7499.32 12-APR-09:20 21.23 16.81
May 0.566859E+11 78461.54 30-MAY-03:02 25.60 23.91 0.590206E+10 7498.83 26-MAY-09:20 25.60 23.91
June 0.568225E+11 79393.90 07-JUN-03:02 21.10 18.25 0.588158E+10 7498.83 29-JUN-09:20 29.63 25.44
July 0.591844E+11 77787.42 18-JUL-03:02 24.40 22.88 0.547440E+10 7498.82 14-JUL-09:20 24.40 22.88
August 0.688889E+11 80747.66 28-AUG-03:02 26.27 23.76 0.613929E+10 7498.78 25-AUG-13:20 26.27 23.76
September 0.611075E+11 81548.92 05-SEP-03:02 22.62 22.62 0.545382E+10 7498.81 14-SEP-13:20 28.13 24.89
October 0.644411E+11 97505.74 28-OCT-05:02 10.00 5.56 0.567324E+10 7499.09 17-OCT-13:20 10.00 5.56
November 0.625421E+11 109129.27 24-NOV-04:02 10.03 8.79 0.561732E+10 7504.26 10-NOV-10:09 10.03 8.79
December 0.606785E+11 109257.88 18-DEC-04:02 3.17 -0.2 0.547420E+10 7499.56 08-DEC-10:00 3.17 -0.2
                     
Annual Sum or Average 0.706798E+12         0.680069E+11        
Minimum of Months 0.497781E+11 77787.42   3.17 -0.2 0.514041E+10 7498.78   3.17 -0.2
Maximum of Months 0.688889E+11 110548.58   26.27 23.91 0.613929E+10 7504.26   29.63 25.44



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.470816E+11 88919.37 17-JAN-04:03 16.83 16.83 0.507408E+10 6734.83 05-JAN-14:09 16.83 16.83
February 0.456065E+11 90725.95 21-FEB-04:02 17.30 17.30 0.460572E+10 6734.91 28-FEB-14:30 25.00 20.38
March 0.579824E+11 91701.52 20-MAR-03:02 12.55 8.37 0.549901E+10 6735.29 23-MAR-09:09 16.78 14.63
April 0.633986E+11 87699.10 10-APR-03:02 13.30 9.00 0.488009E+10 6907.87 18-APR-13:00 27.70 15.13
May 0.601381E+11 84254.60 23-MAY-03:02 24.90 23.43 0.528552E+10 6734.57 03-MAY-09:00 24.90 23.43
June 0.648408E+11 85752.99 07-JUN-03:02 21.10 18.25 0.526557E+10 6734.56 01-JUN-13:09 21.10 18.25
July 0.695588E+11 80350.40 10-JUL-05:04 24.60 23.27 0.489204E+10 6734.62 24-JUL-13:00 27.20 23.27
August 0.770628E+11 78632.04 14-AUG-05:03 26.10 23.77 0.549321E+10 6734.57 07-AUG-13:00 26.10 23.77
September 0.586029E+11 85164.06 08-SEP-03:02 22.85 22.73 0.488019E+10 6734.54 07-SEP-13:00 22.85 22.73
October 0.632841E+11 90148.84 30-OCT-03:02 17.00 14.54 0.507613E+10 6734.80 18-OCT-09:30 17.00 14.54
November 0.586188E+11 91445.26 27-NOV-04:02 14.30 13.51 0.502954E+10 6734.81 21-NOV-14:00 14.30 13.51
December 0.582709E+11 92293.82 18-DEC-04:02 3.17 -0.2 0.490020E+10 6735.00 08-DEC-10:30 3.17 -0.2
                     
Annual Sum or Average 0.724446E+12         0.608813E+11        
Minimum of Months 0.456065E+11 78632.04   3.17 -0.2 0.460572E+10 6734.54   3.17 -0.2
Maximum of Months 0.770628E+11 92293.82   26.10 23.77 0.549901E+10 6907.87   27.70 23.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.356287E+11 78052.20 20-JAN-05:03 17.00 17.00 0.503255E+10 6734.80 05-JAN-14:09 17.00 17.00
February 0.336796E+11 77514.36 11-FEB-06:02 13.30 12.93 0.457323E+10 6734.93 28-FEB-14:50 25.00 20.38
March 0.414467E+11 80458.51 20-MAR-03:02 12.55 8.37 0.547351E+10 6735.25 23-MAR-09:09 16.78 14.63
April 0.427854E+11 78916.00 19-APR-04:03 17.45 15.97 0.487837E+10 6783.36 18-APR-13:50 17.45 15.97
May 0.515058E+11 80602.55 01-MAY-03:02 25.27 22.91 0.528290E+10 6734.60 03-MAY-09:20 27.93 21.46
June 0.518089E+11 78502.25 01-JUN-03:02 21.95 21.06 0.526606E+10 6734.61 01-JUN-13:09 23.90 20.94
July 0.513479E+11 74015.48 12-JUL-05:04 23.90 23.16 0.489060E+10 6734.58 20-JUL-13:00 28.90 23.37
August 0.535479E+11 77602.18 01-AUG-05:04 23.90 22.91 0.549510E+10 6734.60 25-AUG-13:09 27.80 24.45
September 0.484379E+11 78237.43 20-SEP-03:02 22.38 21.02 0.487454E+10 6734.57 15-SEP-13:09 22.38 21.02
October 0.486279E+11 80219.90 17-OCT-03:02 18.08 14.23 0.507084E+10 6734.82 17-OCT-13:09 22.17 15.50
November 0.414274E+11 77840.09 25-NOV-06:02 15.00 14.01 0.501336E+10 6734.84 13-NOV-14:09 15.00 14.01
December 0.374773E+11 78680.80 14-DEC-05:03 20.00 20.00 0.486631E+10 6735.02 08-DEC-10:39 20.00 20.00
                     
Annual Sum or Average 0.537721E+12         0.607174E+11        
Minimum of Months 0.336796E+11 74015.48   12.55 8.37 0.457323E+10 6734.57   15.00 14.01
Maximum of Months 0.535479E+11 80602.55   25.27 23.16 0.549510E+10 6783.36   28.90 24.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.294304E+11 74775.42 19-JAN-06:03 18.83 18.83 0.477951E+10 6734.55 27-JAN-14:00 18.00 12.42
February 0.298614E+11 76885.92 01-FEB-06:02 16.10 16.10 0.442479E+10 6734.79 28-FEB-14:39 25.00 20.38
March 0.375237E+11 77094.14 01-MAR-06:02 15.52 13.84 0.536269E+10 6734.69 24-MAR-09:09 19.03 14.07
April 0.426611E+11 78292.76 24-APR-03:02 20.18 20.07 0.486449E+10 6734.90 10-APR-13:00 20.18 20.07
May 0.563427E+11 80152.36 01-MAY-03:02 25.27 22.91 0.528633E+10 6734.55 26-MAY-13:09 26.97 24.64
June 0.578197E+11 79249.67 06-JUN-03:02 23.22 21.76 0.526952E+10 6734.58 01-JUN-13:09 23.22 21.76
July 0.575473E+11 76312.70 01-JUL-03:02 24.57 23.11 0.489597E+10 6734.56 03-JUL-13:09 31.70 25.89
August 0.591441E+11 77973.53 29-AUG-03:02 23.43 23.01 0.549830E+10 6734.55 22-AUG-13:09 23.43 23.01
September 0.514912E+11 77884.07 06-SEP-03:02 24.70 23.43 0.487860E+10 6734.56 07-SEP-13:00 24.40 22.88
October 0.501442E+11 79028.84 10-OCT-03:02 22.00 19.94 0.506319E+10 6734.80 17-OCT-13:09 22.17 15.50
November 0.371959E+11 77976.40 08-NOV-05:03 19.90 19.21 0.495855E+10 6734.76 13-NOV-14:09 23.30 17.20
December 0.314597E+11 72963.56 14-DEC-06:03 20.00 20.00 0.470123E+10 6734.94 08-DEC-10:39 20.00 20.00
                     
Annual Sum or Average 0.540621E+12         0.599832E+11        
Minimum of Months 0.294304E+11 72963.56   15.52 13.84 0.442479E+10 6734.55   18.00 12.42
Maximum of Months 0.591441E+11 80152.36   25.27 23.43 0.549830E+10 6734.94   31.70 25.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.421638E+10 11905.46 02-JAN-06:02 16.00 15.39 0.607240E+09 845.61 27-JAN-14:00 18.00 12.42
February 0.453334E+10 9750.23 28-FEB-06:02 18.38 17.90 0.564171E+09 845.65 28-FEB-14:30 25.00 20.38
March 0.616173E+10 11152.39 27-MAR-05:02 19.82 18.59 0.680469E+09 845.66 23-MAR-09:20 19.82 18.59
April 0.844622E+10 11604.08 07-APR-05:02 19.90 18.48 0.611715E+09 867.02 18-APR-13:00 27.70 15.13
May 0.104987E+11 12459.10 30-MAY-03:02 25.60 23.91 0.664749E+09 845.85 16-MAY-13:50 25.60 23.91
June 0.118384E+11 12109.64 26-JUN-04:03 25.00 23.68 0.662453E+09 845.88 05-JUN-13:50 25.00 23.68
July 0.123646E+11 14172.33 23-JUL-13:02 33.80 26.10 0.616098E+09 846.04 20-JUL-13:39 33.80 26.10
August 0.131176E+11 14203.20 21-AUG-03:02 26.27 23.88 0.690890E+09 847.19 22-AUG-13:00 32.20 25.17
September 0.937261E+10 12573.31 06-SEP-03:02 24.70 23.43 0.613737E+09 845.60 07-SEP-13:50 25.23 23.17
October 0.927859E+10 12129.56 23-OCT-04:53 25.00 24.24 0.637003E+09 845.64 17-OCT-13:09 25.00 24.24
November 0.643720E+10 11503.38 02-NOV-05:02 23.38 22.55 0.627318E+09 845.64 21-NOV-14:00 22.20 15.14
December 0.557238E+10 11324.74 12-DEC-06:02 20.17 20.17 0.601406E+09 845.65 08-DEC-10:30 20.17 20.17
                     
Annual Sum or Average 0.101838E+12         0.757725E+10        
Minimum of Months 0.421638E+10 9750.23   16.00 15.39 0.564171E+09 845.60   18.00 12.42
Maximum of Months 0.131176E+11 14203.20   33.80 26.10 0.690890E+09 867.02   33.80 26.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.356431E+10 8255.62 01-JAN-09:53 20.00 16.19 0.400961E+09 544.96 11-JAN-10:09 14.67 12.06
February 0.380890E+10 7986.17 26-FEB-10:43 24.25 19.98 0.367356E+09 544.97 28-FEB-14:30 25.00 20.38
March 0.525892E+10 12168.71 26-MAR-09:02 23.67 19.70 0.438459E+09 545.01 23-MAR-09:09 23.67 19.70
April 0.678647E+10 16376.50 23-APR-09:13 24.97 20.75 0.393717E+09 553.78 18-APR-13:00 24.97 20.75
May 0.851861E+10 16847.88 07-MAY-09:22 29.15 23.43 0.428685E+09 545.31 03-MAY-09:50 29.15 23.43
June 0.908089E+10 11043.27 29-JUN-05:02 25.18 24.55 0.426924E+09 545.27 12-JUN-09:00 25.18 24.55
July 0.925006E+10 16752.61 23-JUL-09:02 29.68 25.89 0.397007E+09 545.11 20-JUL-09:00 29.68 25.89
August 0.932142E+10 15075.14 27-AUG-10:23 30.00 24.51 0.445024E+09 544.94 25-AUG-13:09 30.00 24.51
September 0.721812E+10 16821.18 24-SEP-09:32 29.03 25.00 0.395802E+09 545.42 11-SEP-09:00 29.03 25.00
October 0.724939E+10 16327.62 09-OCT-08:53 27.10 22.26 0.410607E+09 544.96 18-OCT-09:30 21.50 17.07
November 0.504968E+10 10432.73 11-NOV-09:23 24.40 21.68 0.404641E+09 544.96 27-NOV-14:09 25.82 17.52
December 0.409322E+10 5661.18 10-DEC-09:43 23.33 19.53 0.385475E+09 544.98 08-DEC-10:30 23.33 19.53
                     
Annual Sum or Average 0.792000E+11         0.489466E+10        
Minimum of Months 0.356431E+10 5661.18   20.00 16.19 0.367356E+09 544.94   14.67 12.06
Maximum of Months 0.932142E+10 16847.88   30.00 25.89 0.445024E+09 553.78   30.00 25.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.854832E+10 19949.38 01-JAN-13:52 26.00 17.88 0.629397E+09 858.25 19-JAN-14:20 25.00 21.54
February 0.836133E+10 19818.23 26-FEB-14:43 26.18 20.05 0.573604E+09 859.02 27-FEB-14:20 25.70 20.08
March 0.873218E+10 19176.97 26-MAR-13:43 29.90 19.94 0.682435E+09 846.00 29-MAR-13:00 25.00 21.11
April 0.990174E+10 13692.53 29-APR-05:02 23.20 21.68 0.612383E+09 890.74 18-APR-13:00 23.20 21.68
May 0.107338E+11 14347.00 01-MAY-05:02 25.92 23.71 0.664813E+09 845.63 31-MAY-13:09 23.27 21.49
June 0.114975E+11 14419.25 26-JUN-04:03 25.00 23.68 0.662385E+09 845.63 01-JUN-13:09 25.00 23.68
July 0.122664E+11 15979.21 23-JUL-13:02 33.80 26.10 0.616063E+09 845.63 24-JUL-13:00 27.20 23.27
August 0.141650E+11 18809.56 27-AUG-13:02 33.17 23.64 0.691143E+09 845.92 31-AUG-13:00 31.60 25.03
September 0.113831E+11 19654.20 03-SEP-15:12 32.53 24.63 0.614518E+09 845.97 12-SEP-13:20 31.60 24.10
October 0.137808E+11 19856.92 08-OCT-11:43 30.83 25.74 0.639079E+09 858.57 10-OCT-13:09 31.00 22.17
November 0.116855E+11 21006.21 11-NOV-13:22 26.35 22.79 0.632516E+09 890.01 06-NOV-14:09 26.35 22.79
December 0.105907E+11 19838.54 10-DEC-13:42 27.00 20.22 0.610516E+09 867.09 15-DEC-14:30 29.00 21.83
                     
Annual Sum or Average 0.131646E+12         0.762885E+10        
Minimum of Months 0.836133E+10 13692.53   23.20 17.88 0.573604E+09 845.63   23.20 20.08
Maximum of Months 0.141650E+11 21006.21   33.80 26.10 0.691143E+09 890.74   31.60 25.03



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.524480E+10 16714.11 16-JAN-15:53 25.00 17.90 0.400997E+09 544.96 05-JAN-14:20 25.00 17.90
February 0.621088E+10 19228.16 26-FEB-15:23 25.80 20.01 0.370703E+09 544.99 28-FEB-14:30 25.00 20.38
March 0.876754E+10 19527.38 26-MAR-14:23 26.90 20.14 0.445002E+09 545.00 23-MAR-09:09 26.90 20.14
April 0.121067E+11 21178.71 23-APR-16:32 27.37 21.80 0.396549E+09 561.01 18-APR-14:00 27.37 21.80
May 0.103241E+11 21240.88 28-MAY-16:21 32.50 24.77 0.429025E+09 544.94 03-MAY-09:00 32.50 24.77
June 0.123043E+11 20992.23 11-JUN-16:42 33.12 21.82 0.427701E+09 544.94 01-JUN-13:09 33.12 21.82
July 0.135345E+11 20719.03 16-JUL-15:52 31.70 25.48 0.397981E+09 544.95 24-JUL-13:00 27.20 23.27
August 0.160425E+11 20763.98 06-AUG-16:22 25.00 22.52 0.446385E+09 544.95 07-AUG-13:00 24.00 22.63
September 0.960117E+10 22571.25 03-SEP-15:51 32.20 24.61 0.396266E+09 544.94 07-SEP-13:50 25.23 23.17
October 0.107658E+11 21487.10 22-OCT-15:52 28.90 23.86 0.412118E+09 544.96 17-OCT-13:09 28.90 23.86
November 0.882539E+10 21584.90 11-NOV-15:22 26.35 22.93 0.407812E+09 544.98 27-NOV-14:09 25.82 17.52
December 0.867725E+10 19820.40 10-DEC-15:42 27.17 20.20 0.397140E+09 544.98 08-DEC-10:30 27.17 20.20
                     
Annual Sum or Average 0.122405E+12         0.492768E+10        
Minimum of Months 0.524480E+10 16714.11   25.00 17.90 0.370703E+09 544.94   24.00 17.52
Maximum of Months 0.160425E+11 22571.25   33.12 25.48 0.446385E+09 561.01   33.12 24.77



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.287946E+10 5208.97 31-JAN-14:40 25.00 21.54 0.558308E+09 845.60 02-JAN-14:50 25.00 21.54
February 0.313250E+10 5437.44 28-FEB-15:00 25.00 20.38 0.532062E+09 845.64 28-FEB-14:50 25.00 20.38
March 0.409000E+10 9249.26 27-MAR-05:02 19.82 18.59 0.648010E+09 845.62 15-MAR-13:09 19.82 18.59
April 0.557779E+10 10168.52 29-APR-05:02 23.20 21.68 0.606309E+09 851.80 18-APR-13:50 23.20 21.68
May 0.938808E+10 14098.03 29-MAY-16:01 32.43 23.42 0.664703E+09 845.79 16-MAY-13:50 32.43 23.42
June 0.101685E+11 14463.46 25-JUN-16:31 32.40 24.97 0.662719E+09 845.76 05-JUN-13:39 32.40 24.97
July 0.100117E+11 13185.16 03-JUL-03:02 28.03 25.04 0.616356E+09 845.86 20-JUL-13:00 28.90 23.37
August 0.994140E+10 13192.26 21-AUG-03:02 26.27 23.88 0.691288E+09 845.83 14-AUG-13:50 26.27 23.88
September 0.799543E+10 11478.23 11-SEP-05:03 25.42 23.91 0.613411E+09 845.60 07-SEP-13:39 25.42 23.91
October 0.727557E+10 14273.06 08-OCT-14:52 31.00 25.74 0.634183E+09 845.64 17-OCT-13:09 22.17 15.50
November 0.434089E+10 10587.25 01-NOV-05:03 22.62 22.36 0.607593E+09 845.62 21-NOV-14:00 22.20 15.14
December 0.333913E+10 10121.05 15-DEC-06:02 21.00 21.00 0.552526E+09 845.61 14-DEC-14:39 21.00 21.00
                     
Annual Sum or Average 0.781404E+11         0.738747E+10        
Minimum of Months 0.287946E+10 5208.97   19.82 18.59 0.532062E+09 845.60   19.82 15.14
Maximum of Months 0.101685E+11 14463.46   32.43 25.74 0.691288E+09 851.80   32.43 24.97



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.266650E+10 6396.73 19-JAN-10:00 23.00 20.89 0.279069E+09 521.20 19-JAN-16:00 24.00 20.62
February 0.300592E+10 6835.02 27-FEB-10:00 21.10 19.21 0.261109E+09 521.22 09-FEB-11:09 21.10 19.21
March 0.419942E+10 10696.95 26-MAR-09:43 25.13 20.13 0.313302E+09 521.24 23-MAR-08:00 25.13 20.13
April 0.559309E+10 17342.48 23-APR-09:32 25.53 20.92 0.289116E+09 523.19 18-APR-14:00 25.53 20.92
May 0.822051E+10 18026.50 29-MAY-08:42 27.62 23.19 0.315710E+09 521.21 03-MAY-08:00 27.62 23.19
June 0.857205E+10 16781.62 11-JUN-08:32 26.87 20.94 0.314190E+09 521.32 28-JUN-10:30 31.40 24.40
July 0.842053E+10 16754.31 30-JUL-09:02 29.50 25.11 0.293319E+09 521.63 20-JUL-10:30 29.50 25.11
August 0.824259E+10 16631.63 27-AUG-10:23 30.00 24.51 0.327648E+09 521.20 29-AUG-14:20 30.87 23.97
September 0.666116E+10 16594.00 10-SEP-09:42 33.73 27.29 0.291439E+09 521.20 07-SEP-14:20 33.73 27.29
October 0.638727E+10 16009.14 08-OCT-14:52 31.00 25.74 0.301586E+09 521.22 17-OCT-12:20 21.33 14.79
November 0.397458E+10 9791.74 02-NOV-05:02 23.38 22.55 0.294188E+09 521.21 21-NOV-15:20 21.83 15.14
December 0.287740E+10 5974.59 15-DEC-06:02 21.00 21.00 0.269262E+09 521.21 01-DEC-11:09 21.00 21.00
                     
Annual Sum or Average 0.688210E+11         0.354994E+10        
Minimum of Months 0.266650E+10 5974.59   21.00 19.21 0.261109E+09 521.20   21.00 14.79
Maximum of Months 0.857205E+10 18026.50   33.73 27.29 0.327648E+09 523.19   33.73 27.29



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.759863E+10 20670.25 01-JAN-14:11 25.67 18.12 0.622666E+09 884.91 19-JAN-14:39 25.00 21.54
February 0.726445E+10 19317.52 26-FEB-13:42 26.52 19.51 0.567975E+09 876.94 27-FEB-14:39 25.90 20.26
March 0.685394E+10 18022.03 26-MAR-13:43 29.90 19.94 0.670800E+09 845.84 06-MAR-14:50 29.90 19.94
April 0.722567E+10 13865.96 23-APR-15:32 28.07 21.86 0.609787E+09 865.35 18-APR-13:50 28.07 21.86
May 0.963564E+10 17008.33 29-MAY-16:01 32.43 23.42 0.664772E+09 845.62 03-MAY-09:20 32.43 23.42
June 0.979700E+10 17435.51 25-JUN-15:51 32.80 24.12 0.662572E+09 845.62 12-JUN-13:09 32.80 24.12
July 0.992573E+10 15255.13 20-JUL-03:02 26.70 24.39 0.616277E+09 845.62 20-JUL-13:00 28.90 23.37
August 0.110951E+11 17675.59 27-AUG-13:02 33.17 23.64 0.691606E+09 845.80 31-AUG-13:00 31.60 25.03
September 0.101942E+11 18443.03 17-SEP-14:22 31.60 26.01 0.614389E+09 845.81 12-SEP-13:39 31.60 26.01
October 0.122323E+11 19513.53 08-OCT-14:52 31.00 25.74 0.639199E+09 876.25 13-OCT-13:50 32.87 23.24
November 0.994987E+10 19448.05 05-NOV-13:32 27.20 20.74 0.631181E+09 911.73 06-NOV-14:09 28.30 21.03
December 0.845852E+10 20198.37 10-DEC-12:42 27.00 20.34 0.601869E+09 879.99 15-DEC-14:39 29.00 21.74
                     
Annual Sum or Average 0.110231E+12         0.759309E+10        
Minimum of Months 0.685394E+10 13865.96   25.67 18.12 0.567975E+09 845.62   25.00 19.94
Maximum of Months 0.122323E+11 20670.25   33.17 26.01 0.691606E+09 911.73   32.87 26.01



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.316809E+10 13871.29 01-JAN-15:32 25.00 18.55 0.373965E+09 544.94 02-JAN-14:50 26.83 18.62
February 0.353744E+10 17306.88 26-FEB-17:03 24.22 19.76 0.351774E+09 544.97 28-FEB-14:50 25.00 20.38
March 0.443169E+10 12330.72 27-MAR-05:02 19.82 18.59 0.424135E+09 544.95 24-MAR-09:50 19.82 18.59
April 0.610923E+10 18710.30 23-APR-16:52 27.20 21.71 0.393509E+09 548.69 18-APR-13:30 27.20 21.71
May 0.808852E+10 19114.55 29-MAY-16:01 32.43 23.42 0.428743E+09 544.94 03-MAY-09:20 32.43 23.42
June 0.870965E+10 19141.24 11-JUN-17:11 32.93 21.75 0.427481E+09 544.94 12-JUN-09:20 29.07 22.55
July 0.844149E+10 16408.38 16-JUL-15:52 31.70 25.48 0.397636E+09 544.94 20-JUL-13:00 28.90 23.37
August 0.890172E+10 15568.64 21-AUG-03:02 26.27 23.88 0.446001E+09 544.94 25-AUG-13:09 27.80 24.45
September 0.715455E+10 18481.81 17-SEP-15:42 32.10 25.59 0.395769E+09 544.94 07-SEP-13:39 32.10 25.59
October 0.704165E+10 18334.73 08-OCT-16:12 30.33 25.03 0.410119E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.452532E+10 12341.82 05-NOV-15:32 27.20 19.72 0.396804E+09 544.96 21-NOV-14:00 22.20 15.14
December 0.369359E+10 17173.28 10-DEC-15:22 27.50 20.13 0.368216E+09 544.95 14-DEC-14:39 27.67 22.98
                     
Annual Sum or Average 0.738029E+11         0.481415E+10        
Minimum of Months 0.316809E+10 12330.72   19.82 18.55 0.351774E+09 544.94   19.82 15.14
Maximum of Months 0.890172E+10 19141.24   32.93 25.59 0.446001E+09 548.69   32.43 25.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.221614E+10 5478.47 31-JAN-15:00 25.00 21.54 0.533050E+09 845.60 02-JAN-14:00 25.00 21.54
February 0.272501E+10 5753.84 22-FEB-14:30 25.55 20.41 0.514102E+09 845.63 28-FEB-14:39 25.00 20.38
March 0.379669E+10 8266.40 27-MAR-05:02 19.82 18.59 0.625155E+09 845.61 15-MAR-13:50 19.82 18.59
April 0.562746E+10 11860.74 29-APR-05:02 23.20 21.68 0.599637E+09 845.64 12-APR-13:30 23.20 21.68
May 0.101436E+11 16997.61 29-MAY-16:01 32.43 23.42 0.664919E+09 845.73 16-MAY-13:50 32.43 23.42
June 0.111431E+11 17184.13 25-JUN-16:31 32.40 24.97 0.662904E+09 845.60 12-JUN-13:09 32.40 24.97
July 0.110335E+11 16506.11 02-JUL-17:03 29.90 25.00 0.616713E+09 846.17 20-JUL-13:39 30.57 24.32
August 0.108293E+11 16294.45 27-AUG-16:12 33.33 24.08 0.691464E+09 845.97 21-AUG-13:20 33.33 24.08
September 0.847257E+10 16408.81 17-SEP-15:42 32.10 25.59 0.613465E+09 845.61 07-SEP-13:00 32.10 25.59
October 0.754256E+10 16909.88 08-OCT-14:52 31.00 25.74 0.630941E+09 845.64 17-OCT-13:09 22.17 15.50
November 0.400143E+10 12237.82 02-NOV-05:02 23.38 22.55 0.589903E+09 845.63 21-NOV-14:00 22.20 15.14
December 0.277534E+10 6360.99 15-DEC-15:00 29.00 21.56 0.528145E+09 845.61 14-DEC-14:39 29.00 21.56
                     
Annual Sum or Average 0.803066E+11         0.727040E+10        
Minimum of Months 0.221614E+10 5478.47   19.82 18.59 0.514102E+09 845.60   19.82 15.14
Maximum of Months 0.111431E+11 17184.13   33.33 25.74 0.691464E+09 846.17   33.33 25.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.230210E+10 6126.19 19-JAN-10:20 23.57 21.08 0.363271E+09 544.94 02-JAN-10:09 23.57 21.08
February 0.275892E+10 6651.82 27-FEB-10:30 21.90 19.28 0.346756E+09 544.96 28-FEB-14:39 25.00 20.38
March 0.399937E+10 9620.83 27-MAR-05:02 19.82 18.59 0.420055E+09 545.00 23-MAR-09:09 19.82 18.59
April 0.575005E+10 17028.12 23-APR-11:02 26.70 20.26 0.391681E+09 544.98 12-APR-13:30 26.70 20.26
May 0.894686E+10 18545.74 29-MAY-08:42 27.62 23.19 0.428911E+09 545.31 03-MAY-09:00 27.62 23.19
June 0.945390E+10 17141.03 11-JUN-08:32 26.87 20.94 0.427430E+09 545.23 13-JUN-09:20 29.60 24.10
July 0.936872E+10 17923.63 23-JUL-09:02 29.68 25.89 0.397722E+09 545.23 07-JUL-09:00 29.68 25.89
August 0.907681E+10 17072.57 27-AUG-10:13 30.00 24.62 0.445808E+09 545.08 10-AUG-09:00 30.00 24.62
September 0.718654E+10 17116.62 10-SEP-09:42 33.73 27.29 0.395664E+09 545.33 11-SEP-09:00 28.80 24.74
October 0.674101E+10 16827.65 08-OCT-14:52 31.00 25.74 0.408299E+09 544.96 18-OCT-09:50 22.50 17.62
November 0.375316E+10 9879.80 02-NOV-05:02 23.38 22.55 0.395459E+09 544.96 21-NOV-14:00 22.20 15.14
December 0.250856E+10 4897.81 16-DEC-10:10 24.33 21.30 0.354106E+09 544.98 08-DEC-10:39 24.33 21.30
                     
Annual Sum or Average 0.718460E+11         0.477516E+10        
Minimum of Months 0.230210E+10 4897.81   19.82 18.59 0.346756E+09 544.94   19.82 15.14
Maximum of Months 0.945390E+10 18545.74   33.73 27.29 0.445808E+09 545.33   30.00 25.89



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.635802E+10 22582.53 01-JAN-15:02 25.00 18.55 0.607190E+09 860.99 19-JAN-14:50 25.00 21.54
February 0.658472E+10 21361.69 26-FEB-13:52 26.60 19.72 0.556547E+09 855.51 27-FEB-14:39 25.90 20.26
March 0.643290E+10 17332.89 05-MAR-13:33 27.70 18.32 0.654003E+09 845.89 06-MAR-14:50 26.18 21.15
April 0.730673E+10 18208.64 23-APR-15:01 28.62 21.65 0.604942E+09 845.68 12-APR-13:30 28.62 21.65
May 0.104099E+11 20140.95 29-MAY-16:01 32.43 23.42 0.664958E+09 845.62 31-MAY-13:09 23.27 21.49
June 0.107478E+11 20181.35 25-JUN-15:51 32.80 24.12 0.662760E+09 845.62 12-JUN-13:09 32.80 24.12
July 0.109323E+11 18875.07 23-JUL-13:02 33.80 26.10 0.616605E+09 845.62 14-JUL-13:20 33.80 26.10
August 0.120695E+11 19872.62 27-AUG-12:53 33.00 23.68 0.691741E+09 845.88 31-AUG-13:00 31.60 25.03
September 0.108395E+11 20821.25 17-SEP-14:22 31.60 26.01 0.614405E+09 845.98 19-SEP-13:20 28.87 24.26
October 0.126754E+11 22252.80 08-OCT-14:52 31.00 25.74 0.637126E+09 861.96 13-OCT-13:00 33.00 23.24
November 0.939724E+10 22413.15 11-NOV-14:02 26.18 22.88 0.624962E+09 887.57 06-NOV-14:20 26.18 22.88
December 0.753593E+10 22516.71 10-DEC-12:52 27.00 20.22 0.586121E+09 856.85 15-DEC-14:39 29.00 21.74
                     
Annual Sum or Average 0.111290E+12         0.752136E+10        
Minimum of Months 0.635802E+10 17332.89   25.00 18.32 0.556547E+09 845.62   23.27 20.26
Maximum of Months 0.126754E+11 22582.53   33.80 26.10 0.691741E+09 887.57   33.80 26.10



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.275138E+10 9251.06 01-JAN-17:03 23.33 19.19 0.358704E+09 544.94 02-JAN-14:50 26.83 18.62
February 0.328908E+10 15223.43 26-FEB-17:12 24.03 19.67 0.341052E+09 544.96 28-FEB-14:39 25.00 20.38
March 0.426678E+10 13101.05 27-MAR-05:02 19.82 18.59 0.409763E+09 544.94 15-MAR-13:39 19.82 18.59
April 0.620931E+10 19355.22 23-APR-17:01 26.92 21.65 0.389769E+09 544.98 12-APR-13:30 26.92 21.65
May 0.869581E+10 21253.96 29-MAY-16:01 32.43 23.42 0.428744E+09 544.94 31-MAY-13:09 23.27 21.49
June 0.947028E+10 21132.71 11-JUN-17:11 32.93 21.75 0.427485E+09 544.94 12-JUN-13:09 31.78 20.56
July 0.924908E+10 19132.36 30-JUL-16:52 27.20 24.74 0.397677E+09 544.94 14-JUL-13:09 27.20 24.74
August 0.961146E+10 17648.68 27-AUG-16:12 33.33 24.08 0.446020E+09 544.94 25-AUG-13:09 33.33 24.08
September 0.759574E+10 20236.31 17-SEP-15:42 32.10 25.59 0.395569E+09 544.94 07-SEP-13:00 32.10 25.59
October 0.732783E+10 20213.05 08-OCT-16:12 30.33 25.03 0.408183E+09 544.96 17-OCT-13:09 22.17 15.50
November 0.433667E+10 17809.92 11-NOV-15:22 26.35 22.93 0.386901E+09 544.96 21-NOV-14:00 22.20 15.14
December 0.331590E+10 18918.04 10-DEC-16:12 26.33 20.05 0.353111E+09 544.95 14-DEC-14:39 27.67 22.98
                     
Annual Sum or Average 0.761193E+11         0.474298E+10        
Minimum of Months 0.275138E+10 9251.06   19.82 18.59 0.341052E+09 544.94   19.82 15.14
Maximum of Months 0.961146E+10 21253.96   33.33 25.59 0.446020E+09 544.98   33.33 25.59



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.387755E+10 11952.62 02-JAN-06:15 16.00 15.39 0.00 0.00 01-JAN-00:10 16.00 15.39
February 0.430433E+10 8690.61 27-FEB-06:15 17.70 17.70 0.00 0.00 01-FEB-00:10 17.70 17.70
March 0.567338E+10 9503.76 27-MAR-05:15 19.73 18.53 0.00 0.00 01-MAR-00:10 19.73 18.53
April 0.735718E+10 8564.63 24-APR-05:15 20.17 20.05 0.00 0.00 01-APR-00:10 20.17 20.05
May 0.924257E+10 13943.61 22-MAY-05:13 26.10 22.55 0.00 0.00 01-MAY-00:10 26.10 22.55
June 0.997463E+10 9890.61 12-JUN-05:15 23.70 21.42 0.00 0.00 01-JUN-00:10 23.70 21.42
July 0.105501E+11 13585.21 24-JUL-05:15 26.83 24.96 0.00 0.00 01-JUL-00:10 26.83 24.96
August 0.116539E+11 13830.48 28-AUG-05:15 25.33 23.69 0.00 0.00 01-AUG-00:10 25.33 23.69
September 0.875982E+10 13759.94 05-SEP-05:15 22.80 22.80 0.00 0.00 01-SEP-00:10 22.80 22.80
October 0.906198E+10 14017.82 10-OCT-05:15 21.97 20.04 0.00 0.00 01-OCT-00:10 21.97 20.04
November 0.668095E+10 9779.61 06-NOV-06:15 18.80 17.70 0.00 0.00 01-NOV-00:10 18.80 17.70
December 0.540021E+10 9113.80 11-DEC-06:15 20.67 20.21 0.00 0.00 01-DEC-00:10 20.67 20.21
                     
Annual Sum or Average 0.925366E+11         0.00        
Minimum of Months 0.387755E+10 8564.63   16.00 15.39 0.00 0.00   16.00 15.39
Maximum of Months 0.116539E+11 14017.82   26.83 24.96 0.00 0.00   26.83 24.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.205626E+10 6891.05 02-JAN-06:15 16.00 15.39 0.00 0.00 01-JAN-00:10 16.00 15.39
February 0.242079E+10 5175.24 24-FEB-06:13 14.60 14.60 0.00 0.00 01-FEB-00:10 14.60 14.60
March 0.332932E+10 5778.22 01-MAR-06:13 15.53 13.91 0.00 0.00 01-MAR-00:10 15.53 13.91
April 0.496999E+10 6430.65 28-APR-15:20 32.93 23.96 0.00 0.00 01-APR-00:10 32.93 23.96
May 0.804588E+10 12706.03 22-MAY-05:13 26.10 22.55 0.00 0.00 01-MAY-00:10 26.10 22.55
June 0.834218E+10 8560.51 23-JUN-05:02 25.60 23.86 0.00 0.00 01-JUN-00:10 25.60 23.86
July 0.832922E+10 8011.97 31-JUL-05:13 24.40 23.27 0.00 0.00 01-JUL-00:10 24.40 23.27
August 0.866537E+10 8964.87 28-AUG-05:02 25.67 23.79 0.00 0.00 01-AUG-00:10 25.67 23.79
September 0.721044E+10 8556.71 05-SEP-05:15 22.80 22.80 0.00 0.00 01-SEP-00:10 22.80 22.80
October 0.700211E+10 9605.40 10-OCT-05:15 21.97 20.04 0.00 0.00 01-OCT-00:10 21.97 20.04
November 0.405458E+10 6676.58 04-NOV-05:15 20.57 20.00 0.00 0.00 01-NOV-00:10 20.57 20.00
December 0.284487E+10 5782.50 15-DEC-06:15 21.00 21.00 0.00 0.00 01-DEC-00:10 21.00 21.00
                     
Annual Sum or Average 0.672710E+11         0.00        
Minimum of Months 0.205626E+10 5175.24   14.60 13.91 0.00 0.00   14.60 13.91
Maximum of Months 0.866537E+10 12706.03   32.93 23.96 0.00 0.00   32.93 23.96



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.209665E+10 9748.93 19-JAN-15:00 25.00 21.54 0.00 0.00 01-JAN-00:10 25.00 21.54
February 0.327521E+10 11609.51 24-FEB-15:00 25.50 20.83 0.00 0.00 01-FEB-00:10 25.50 20.83
March 0.471593E+10 12987.63 06-MAR-15:00 26.10 21.05 0.00 0.00 01-MAR-00:10 26.10 21.05
April 0.825277E+10 18175.10 28-APR-15:00 33.30 23.06 0.00 0.00 01-APR-00:10 33.30 23.06
May 0.137456E+11 19299.57 10-MAY-14:40 32.80 23.17 0.00 0.00 01-MAY-00:10 32.80 23.17
June 0.152682E+11 20243.21 28-JUN-14:00 33.90 26.45 0.00 0.00 01-JUN-00:10 33.90 26.45
July 0.146116E+11 20443.99 07-JUL-14:30 34.45 24.41 0.00 0.00 01-JUL-00:10 34.45 24.41
August 0.147212E+11 19533.00 10-AUG-14:00 32.70 25.03 0.00 0.00 01-AUG-00:10 32.70 25.03
September 0.111470E+11 17594.43 01-SEP-15:10 31.38 24.60 0.00 0.00 01-SEP-00:10 31.38 24.60
October 0.103807E+11 16472.91 05-OCT-15:40 32.67 23.68 0.00 0.00 01-OCT-00:10 32.67 23.68
November 0.477868E+10 13018.03 02-NOV-14:00 29.40 24.47 0.00 0.00 01-NOV-00:10 29.40 24.47
December 0.286747E+10 11020.87 15-DEC-15:00 29.00 21.56 0.00 0.00 01-DEC-00:10 29.00 21.56
                     
Annual Sum or Average 0.105861E+12         0.00        
Minimum of Months 0.209665E+10 9748.93   25.00 20.83 0.00 0.00   25.00 20.83
Maximum of Months 0.152682E+11 20443.99   34.45 26.45 0.00 0.00   34.45 26.45



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.402286E+10 2052.06 01-JAN-17:27 22.00 18.79 95232581.71 126.85 12-JAN-14:00 19.00 15.91
February 0.839474E+10 4115.35 26-FEB-17:42 23.48 19.39 86406041.54 126.85 28-FEB-10:00 22.20 19.62
March 0.144437E+11 7197.45 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 07-MAR-10:09 20.70 19.78
April 0.189954E+11 7906.36 16-APR-18:10 18.43 13.27 91654201.66 129.29 28-APR-13:00 32.70 23.02
May 0.462645E+10 3491.61 31-MAY-24:00 23.00 21.40 99236232.38 126.85 08-MAY-13:00 23.00 21.40
June 0.935289E+10 5345.11 30-JUN-23:57 25.10 23.16 98982601.12 126.87 19-JUN-09:09 25.10 23.16
July 0.147288E+11 7222.33 31-JUL-23:57 25.20 23.65 91894438.39 126.85 14-JUL-09:20 25.20 23.65
August 0.198424E+11 7789.06 06-AUG-18:00 25.00 23.59 0.105052E+09 136.33 28-AUG-13:00 33.00 25.67
September 0.450423E+10 3520.03 30-SEP-24:00 22.30 21.22 91606025.36 126.82 22-SEP-09:09 22.30 21.22
October 0.968260E+10 5366.73 31-OCT-24:00 21.60 20.90 95249542.69 126.88 24-OCT-09:30 21.60 20.90
November 0.141309E+11 5953.60 06-NOV-17:00 26.60 19.72 94307121.14 126.85 01-NOV-09:20 26.60 19.72
December 0.195249E+11 7830.98 10-DEC-16:54 25.00 19.63 91882435.98 126.83 28-DEC-10:09 18.33 18.33
                     
Annual Sum or Average 0.142250E+12         0.114475E+10        
Minimum of Months 0.402286E+10 2052.06   18.43 13.27 86406041.54 126.82   18.33 15.91
Maximum of Months 0.198424E+11 7906.36   26.60 23.65 0.105052E+09 136.33   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.288993E+10 1855.74 18-JAN-17:00 22.00 19.94 95231305.39 126.84 02-JAN-10:50 22.00 19.94
February 0.727985E+10 3774.27 26-FEB-17:54 23.30 19.29 86405408.59 126.85 24-FEB-14:00 23.30 19.29
March 0.132181E+11 6775.73 31-MAR-24:00 20.70 19.78 0.103242E+09 126.84 07-MAR-14:00 20.70 19.78
April 0.180191E+11 7457.11 16-APR-18:10 18.43 13.27 91666820.86 130.27 28-APR-13:00 32.70 23.02
May 0.430312E+10 3304.87 31-MAY-24:00 23.00 21.40 99234505.64 126.85 03-MAY-13:00 23.00 21.40
June 0.889764E+10 5202.21 30-JUN-23:57 25.10 23.16 98981196.38 126.86 19-JUN-09:09 25.10 23.16
July 0.140306E+11 6956.68 31-JUL-23:57 25.20 23.65 91894988.33 126.85 31-JUL-13:00 25.20 23.65
August 0.188162E+11 7262.04 06-AUG-18:10 25.00 23.59 0.105139E+09 135.91 28-AUG-13:00 33.00 25.67
September 0.410087E+10 3312.39 30-SEP-24:00 22.30 21.22 91605454.09 126.82 05-SEP-13:39 22.30 21.22
October 0.904887E+10 5025.17 31-OCT-24:00 21.60 20.90 95248447.57 126.87 24-OCT-09:20 21.60 20.90
November 0.130149E+11 5638.16 06-NOV-17:00 26.60 19.72 94306956.43 126.84 01-NOV-09:00 26.60 19.72
December 0.178731E+11 7368.55 15-DEC-17:00 28.00 21.24 91882307.51 126.83 28-DEC-10:09 18.33 18.33
                     
Annual Sum or Average 0.131492E+12         0.114484E+10        
Minimum of Months 0.288993E+10 1855.74   18.43 13.27 86405408.59 126.82   18.33 18.33
Maximum of Months 0.188162E+11 7457.11   28.00 23.65 0.105139E+09 135.91   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.191250E+10 1905.45 19-JAN-17:00 24.00 20.62 95152088.18 126.84 02-JAN-14:09 24.00 20.62
February 0.651988E+10 3796.23 26-FEB-17:42 23.48 19.39 86405574.66 126.85 24-FEB-14:00 23.48 19.39
March 0.126758E+11 6671.83 31-MAR-24:00 20.70 19.78 0.103242E+09 126.85 07-MAR-14:00 20.70 19.78
April 0.178941E+11 7640.94 23-APR-18:08 25.13 21.19 91645258.59 128.54 28-APR-13:00 32.70 23.02
May 0.440921E+10 3268.37 31-MAY-24:00 23.00 21.40 99235595.90 126.85 08-MAY-13:00 23.00 21.40
June 0.901576E+10 5231.75 30-JUN-23:57 25.10 23.16 98982517.33 126.87 01-JUN-13:09 25.10 23.16
July 0.141630E+11 6940.03 31-JUL-23:57 25.20 23.65 91895686.84 126.85 31-JUL-13:00 25.20 23.65
August 0.189362E+11 7506.99 06-AUG-17:40 25.33 23.69 0.104404E+09 134.41 28-AUG-13:00 33.00 25.67
September 0.418582E+10 3354.81 30-SEP-24:00 22.30 21.22 91605555.65 126.82 05-SEP-13:39 22.30 21.22
October 0.899440E+10 4967.20 31-OCT-24:00 21.60 20.90 95249176.71 126.87 24-OCT-13:00 21.60 20.90
November 0.125636E+11 5697.61 06-NOV-17:00 26.60 19.72 94307275.39 126.85 01-NOV-09:00 26.60 19.72
December 0.170788E+11 7431.07 15-DEC-17:00 28.00 21.24 91882643.81 126.83 28-DEC-14:20 19.33 19.33
                     
Annual Sum or Average 0.128349E+12         0.114401E+10        
Minimum of Months 0.191250E+10 1905.45   20.70 19.39 86405574.66 126.82   19.33 19.33
Maximum of Months 0.189362E+11 7640.94   28.00 23.69 0.104404E+09 134.41   33.00 25.67



Table of Contents

Report: ZoneCoolingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.240798E+12 92998.12 02-JAN-17:00 26.00 18.38 0.206180E+10 2746.99 10-JAN-10:09 7.33 2.79
February 0.436995E+12 183714.69 27-FEB-17:00 24.40 20.28 0.187059E+10 2747.74 13-FEB-14:09 24.40 20.28
March 0.728776E+12 358582.23 31-MAR-24:00 20.70 19.78 0.223496E+10 2747.57 09-MAR-10:09 20.70 19.78
April 0.940594E+12 367523.33 28-APR-21:02 23.82 23.08 0.204340E+10 3335.60 28-APR-13:00 23.82 23.08
May 0.240801E+12 175679.32 31-MAY-24:00 23.00 21.40 0.214903E+10 2747.22 22-MAY-13:00 23.00 21.40
June 0.469290E+12 267329.23 30-JUN-23:57 25.10 23.16 0.214280E+10 2746.58 01-JUN-13:09 25.10 23.16
July 0.731501E+12 359638.50 31-JUL-23:53 25.20 23.65 0.198925E+10 2745.93 12-JUL-13:30 25.20 23.65
August 0.972797E+12 371126.47 09-AUG-21:13 23.27 22.90 0.260630E+10 3584.01 28-AUG-13:00 33.00 25.67
September 0.236881E+12 176634.57 30-SEP-24:00 22.30 21.22 0.198397E+10 2747.19 18-SEP-13:00 22.30 21.22
October 0.488655E+12 268703.72 31-OCT-24:00 21.60 20.90 0.206196E+10 2746.76 24-OCT-09:30 21.60 20.90
November 0.709669E+12 276635.21 06-NOV-17:00 26.60 19.72 0.204148E+10 2746.47 22-NOV-14:50 19.32 9.14
December 0.977605E+12 368064.53 26-DEC-17:00 12.70 5.60 0.201565E+10 3142.64 13-DEC-14:00 12.70 5.60
                     
Annual Sum or Average 0.717436E+13         0.252012E+11        
Minimum of Months 0.236881E+12 92998.12   12.70 5.60 0.187059E+10 2745.93   7.33 2.79
Maximum of Months 0.977605E+12 371126.47   26.60 23.65 0.260630E+10 3584.01   33.00 25.67



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.389851E+09 11609.52 09-JAN-04:07 8.83
February 0.282664E+09 12651.45 20-FEB-18:13 19.93
March 0.226493E+09 12330.33 22-MAR-03:13 9.43
April 0.248526E+09 16624.09 22-APR-16:02 30.08
May 0.383351E+09 18580.83 27-MAY-16:02 31.60
June 0.361605E+09 21787.33 10-JUN-16:02 33.72
July 0.530143E+09 25011.20 22-JUL-16:02 35.92
August 0.456420E+09 19357.65 26-AUG-16:02 32.10
September 0.591552E+09 24685.01 09-SEP-16:02 35.73
October 0.514719E+09 18693.11 07-OCT-16:02 31.58
November 0.464543E+09 13228.58 02-NOV-03:53 23.60
December 0.489818E+09 12975.48 10-DEC-15:22 27.50
         
Annual Sum or Average 0.493969E+10      
Minimum of Months 0.226493E+09 11609.52   8.83
Maximum of Months 0.591552E+09 25011.20   35.92



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 21849803.10 52384.39 23-JAN-06:02 6.83
February 0.186428E+09 58718.53 06-FEB-05:01 3.03
March 11027137.54 51132.42 13-MAR-05:03 6.68
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 2085987.25 21990.12 21-DEC-06:01 0.83
         
Annual Sum or Average 0.221391E+09      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 0.186428E+09 58718.53   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.107683E+09 10436.38 10-JAN-05:01 1.33
February 65417805.82 10811.09 06-FEB-05:01 3.03
March 27542948.81 9817.05 09-MAR-06:02 1.10
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 62759350.60 10493.39 21-DEC-05:01 0.17
         
Annual Sum or Average 0.263403E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.107683E+09 10811.09   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 38985844.95 8888.37 10-JAN-06:02 3.00
February 22879517.62 9471.34 06-FEB-05:01 3.03
March 11525654.74 6652.82 11-MAR-06:03 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 33392040.76 9306.93 21-DEC-05:01 0.17
         
Annual Sum or Average 0.106783E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 38985844.95 9471.34   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 8318441.49 11917.56 10-JAN-06:02 3.00
February 6025746.43 12066.74 06-FEB-06:01 2.88
March 2041047.71 4715.90 11-MAR-06:03 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 17237014.54 12098.54 21-DEC-06:01 0.83
         
Annual Sum or Average 33622250.17      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 17237014.54 12098.54   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 16909615.47 8199.59 10-JAN-06:02 3.00
February 10029344.91 8292.87 06-FEB-06:01 2.88
March 419126.84 2464.63 11-MAR-06:03 6.60
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 14074296.98 8305.06 21-DEC-06:01 0.83
         
Annual Sum or Average 41432384.19      
Minimum of Months 0.00 0.00   0.83
Maximum of Months 16909615.47 8305.06   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.926120E+09 13200.75 23-JAN-04:03 8.00
February 0.566121E+09 14470.85 05-FEB-07:43 -3.4
March 0.326631E+09 12737.03 13-MAR-04:01 7.05
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 39581504.96 11659.82 16-NOV-06:02 9.40
December 0.557823E+09 12911.10 20-DEC-05:01 4.67
         
Annual Sum or Average 0.241628E+10      
Minimum of Months 0.00 0.00   -3.4
Maximum of Months 0.926120E+09 14470.85   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.364885E+09 12048.77 05-JAN-05:01 0.83
February 0.206928E+09 13460.88 06-FEB-04:01 3.35
March 0.167155E+09 11626.80 10-MAR-05:02 5.83
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 8134511.06 10442.54 16-NOV-06:02 9.40
December 0.269070E+09 12070.29 21-DEC-05:01 0.17
         
Annual Sum or Average 0.101617E+10      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.364885E+09 13460.88   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.272133E+09 14887.21 10-JAN-05:01 1.33
February 0.181105E+09 15923.28 06-FEB-04:01 3.35
March 0.191874E+09 14342.89 11-MAR-05:02 7.27
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 7835.57 65.30 16-NOV-06:04 9.40
December 0.184191E+09 15116.44 21-DEC-05:01 0.17
         
Annual Sum or Average 0.829312E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.272133E+09 15923.28   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.279142E+09 12065.80 10-JAN-05:01 1.33
February 0.159980E+09 12850.81 06-FEB-04:01 3.35
March 95548271.55 10993.00 10-MAR-05:02 5.83
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 1528477.85 3916.14 16-NOV-06:02 9.40
December 0.143403E+09 12123.78 21-DEC-05:01 0.17
         
Annual Sum or Average 0.679602E+09      
Minimum of Months 0.00 0.00   0.17
Maximum of Months 0.279142E+09 12850.81   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 89445357.58 10306.08 23-JAN-05:01 7.83
February 77436961.55 10861.04 06-FEB-05:01 3.03
March 0.104277E+09 10037.05 20-MAR-03:02 12.55
April 0.111668E+09 9737.59 10-APR-03:02 13.30
May 55285840.82 7917.31 24-MAY-03:02 25.00
June 48222977.10 6880.22 07-JUN-03:02 21.10
July 53549778.41 4529.07 23-JUL-13:02 33.80
August 43739654.01 5152.79 06-AUG-11:43 31.00
September 57354031.08 7480.34 21-SEP-03:02 22.70
October 84147969.14 9944.23 30-OCT-03:02 17.00
November 0.119486E+09 10143.13 27-NOV-04:02 14.30
December 0.158977E+09 10890.41 21-DEC-05:01 0.17
         
Annual Sum or Average 0.100359E+10      
Minimum of Months 43739654.01 4529.07   0.17
Maximum of Months 0.158977E+09 10890.41   33.80



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.180705E+09 7497.43 13-JAN-06:02 7.17
February 0.150863E+09 7496.93 08-FEB-06:02 12.10
March 0.113174E+09 7399.92 20-MAR-03:02 12.55
April 39986892.57 6611.21 10-APR-03:02 13.30
May 45947907.20 7673.22 22-MAY-03:02 26.10
June 36771598.36 6819.18 28-JUN-03:02 27.20
July 34262649.31 6819.34 27-JUL-03:02 25.50
August 34539193.02 7009.73 10-AUG-03:02 26.45
September 43326147.10 6542.75 07-SEP-03:02 25.60
October 50494804.84 6594.46 25-OCT-03:02 26.17
November 56063098.23 6050.12 14-NOV-05:03 15.50
December 0.103755E+09 7406.21 22-DEC-06:03 10.00
         
Annual Sum or Average 0.889890E+09      
Minimum of Months 34262649.31 6050.12   7.17
Maximum of Months 0.180705E+09 7673.22   27.20



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.193236E+10 17053.78 03-JAN-06:02 2.83
February 0.121520E+10 17365.35 06-FEB-06:13 3.07
March 0.110324E+10 16504.86 20-MAR-05:03 12.10
April 0.238997E+09 16222.49 11-APR-05:03 10.63
May 48414437.68 9513.99 15-MAY-03:02 24.22
June 38421408.56 8691.48 07-JUN-04:03 21.10
July 34245329.08 7680.51 21-JUL-03:02 25.60
August 33892079.89 7389.26 30-AUG-03:02 25.32
September 43186885.11 8359.77 18-SEP-03:02 25.00
October 0.141477E+09 13632.79 18-OCT-05:03 15.17
November 0.478803E+09 17405.42 09-NOV-06:02 10.42
December 0.149097E+10 15832.96 01-DEC-06:02 11.00
         
Annual Sum or Average 0.679921E+10      
Minimum of Months 33892079.89 7389.26   2.83
Maximum of Months 0.193236E+10 17405.42   25.60



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 87168840.80 523.18 10-JAN-04:45 1.17
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 87168840.80      
Minimum of Months 0.00 0.00   1.17
Maximum of Months 87168840.80 523.18   25.13



Table of Contents

Report: ZoneHeatingSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C]
January 0.00 0.00 01-JAN-00:05 17.00
February 0.00 0.00 01-FEB-00:10 18.20
March 0.00 0.00 01-MAR-00:10 17.62
April 0.00 0.00 01-APR-00:10 20.72
May 0.00 0.00 01-MAY-00:05 22.45
June 0.00 0.00 01-JUN-00:10 22.93
July 0.00 0.00 01-JUL-00:03 25.07
August 0.00 0.00 01-AUG-00:03 25.13
September 0.00 0.00 01-SEP-00:05 24.85
October 0.00 0.00 01-OCT-00:10 22.17
November 0.00 0.00 01-NOV-00:10 21.63
December 0.00 0.00 01-DEC-00:10 14.12
         
Annual Sum or Average 0.00      
Minimum of Months 0.00 0.00   14.12
Maximum of Months 0.00 0.00   25.13



Table of Contents

Report: ZoneElectricSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.148304E+11 15519.45 02-JAN-08:09 0.360447E+11 13457.54 01-JAN-00:10
February 0.134523E+11 15519.45 01-FEB-08:09 0.325565E+11 13457.54 01-FEB-00:10
March 0.159851E+11 15519.45 01-MAR-08:09 0.360447E+11 13457.54 01-MAR-00:10
April 0.142779E+11 15519.45 03-APR-07:10 0.348820E+11 13457.54 01-APR-00:10
May 0.154078E+11 15519.45 01-MAY-07:10 0.360447E+11 13457.54 01-MAY-00:10
June 0.153333E+11 15519.45 01-JUN-07:10 0.348820E+11 13457.54 01-JUN-00:10
July 0.143524E+11 15519.45 03-JUL-07:10 0.360447E+11 13457.54 01-JUL-00:10
August 0.159851E+11 15519.45 01-AUG-07:10 0.360447E+11 13457.54 01-AUG-00:10
September 0.142779E+11 15519.45 01-SEP-07:10 0.348820E+11 13457.54 01-SEP-00:10
October 0.148304E+11 15519.45 02-OCT-07:10 0.360447E+11 13457.54 01-OCT-00:10
November 0.146566E+11 15519.45 01-NOV-07:10 0.348820E+11 13457.54 01-NOV-00:10
December 0.143524E+11 15519.45 01-DEC-08:09 0.360447E+11 13457.54 01-DEC-00:10
             
Annual Sum or Average 0.177742E+12     0.424397E+12    
Minimum of Months 0.134523E+11 15519.45   0.325565E+11 13457.54  
Maximum of Months 0.159851E+11 15519.45   0.360447E+11 13457.54  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270551E+11 18128.59 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244881E+11 18128.59 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280558E+11 18128.59 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261305E+11 18128.59 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275555E+11 18128.59 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270261E+11 18128.59 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266527E+11 18128.59 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280558E+11 18128.59 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261160E+11 18128.59 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270624E+11 18128.59 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264424E+11 18128.59 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266454E+11 18128.59 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321286E+12    
Minimum of Months 0.120811E+11 13937.56   0.244881E+11 18128.59  
Maximum of Months 0.143557E+11 13937.56   0.280558E+11 18128.59  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.133188E+11 13937.56 02-JAN-08:09 0.270550E+11 18128.52 02-JAN-08:09
February 0.120811E+11 13937.56 01-FEB-08:09 0.244880E+11 18128.52 01-FEB-08:09
March 0.143557E+11 13937.56 01-MAR-08:09 0.280557E+11 18128.52 01-MAR-08:09
April 0.128226E+11 13937.56 03-APR-07:10 0.261304E+11 18128.52 03-APR-07:10
May 0.138373E+11 13937.56 01-MAY-07:10 0.275554E+11 18128.52 01-MAY-07:10
June 0.137704E+11 13937.56 01-JUN-07:10 0.270260E+11 18128.52 01-JUN-07:10
July 0.128895E+11 13937.56 03-JUL-07:10 0.266526E+11 18128.52 03-JUL-07:10
August 0.143557E+11 13937.56 01-AUG-07:10 0.280557E+11 18128.52 01-AUG-07:10
September 0.128226E+11 13937.56 01-SEP-07:10 0.261159E+11 18128.52 01-SEP-07:10
October 0.133188E+11 13937.56 02-OCT-07:10 0.270623E+11 18128.52 02-OCT-07:10
November 0.131627E+11 13937.56 01-NOV-07:10 0.264423E+11 18128.52 01-NOV-07:10
December 0.128895E+11 13937.56 01-DEC-08:09 0.266453E+11 18128.52 01-DEC-08:09
             
Annual Sum or Average 0.159625E+12     0.321285E+12    
Minimum of Months 0.120811E+11 13937.56   0.244880E+11 18128.52  
Maximum of Months 0.143557E+11 13937.56   0.280557E+11 18128.52  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120204E+10 1525.96 31-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.106348E+10 1561.87 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.123594E+10 1477.64 27-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108831E+10 1504.27 14-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.115157E+10 1243.87 23-MAY-07:30 0.346000E+10 2276.32 01-MAY-07:10
June 0.113758E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.107202E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.120389E+10 1276.27 21-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.109492E+10 1474.55 26-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.115663E+10 1614.51 25-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.118464E+10 1570.75 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.117701E+10 1604.50 12-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.137680E+11     0.403423E+11    
Minimum of Months 0.106348E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.123594E+10 1614.51   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.766708E+09 964.48 04-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.681522E+09 981.55 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.792549E+09 906.86 27-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.701629E+09 944.30 14-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.744864E+09 802.12 30-MAY-15:30 0.222976E+10 1466.95 01-MAY-07:10
June 0.737295E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.693308E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.777390E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.705544E+09 902.72 26-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.743134E+09 1024.08 25-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.758148E+09 1020.12 21-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.753024E+09 1024.01 12-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.885511E+10     0.259981E+11    
Minimum of Months 0.681522E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.792549E+09 1024.08   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.116670E+10 1493.99 31-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.104529E+10 1541.87 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.122724E+10 1466.75 27-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.109022E+10 1508.53 14-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.115830E+10 1279.30 23-MAY-07:19 0.346006E+10 2276.35 01-MAY-07:10
June 0.114551E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.107745E+10 1216.90 14-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.120708E+10 1315.84 21-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.109361E+10 1471.26 26-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.114754E+10 1606.21 25-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.115278E+10 1537.51 21-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.114392E+10 1592.83 12-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.136556E+11     0.403429E+11    
Minimum of Months 0.104529E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.122724E+10 1606.21   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.763255E+09 994.16 31-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.680797E+09 1013.27 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.798371E+09 979.22 13-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.705034E+09 987.18 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.746777E+09 880.96 24-MAY-07:19 0.222974E+10 1466.94 01-MAY-07:10
June 0.736966E+09 806.15 08-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.693853E+09 840.50 14-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.779455E+09 932.17 23-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.709726E+09 978.74 26-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.745265E+09 1047.35 25-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.750901E+09 1028.27 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.743145E+09 1035.42 12-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.885355E+10     0.259979E+11    
Minimum of Months 0.680797E+09 806.15   0.198154E+10 1466.94  
Maximum of Months 0.798371E+09 1047.35   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120479E+10 1532.38 31-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.106505E+10 1567.29 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.123742E+10 1485.74 27-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108886E+10 1511.49 14-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.115212E+10 1258.37 23-MAY-07:30 0.346000E+10 2276.32 01-MAY-07:10
June 0.113803E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.107254E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.120457E+10 1290.21 21-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.109571E+10 1482.63 26-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.115779E+10 1618.48 25-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.118683E+10 1575.96 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.118026E+10 1608.72 12-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.137840E+11     0.403423E+11    
Minimum of Months 0.106505E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.123742E+10 1618.48   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.767014E+09 967.16 04-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.681866E+09 983.28 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.792801E+09 910.38 27-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.701849E+09 946.98 14-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.745063E+09 802.93 30-MAY-15:30 0.222976E+10 1466.95 01-MAY-07:10
June 0.737501E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.693493E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.777547E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.705781E+09 906.63 26-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.743436E+09 1025.37 25-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.758636E+09 1020.96 21-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.753544E+09 1025.04 12-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.885853E+10     0.259981E+11    
Minimum of Months 0.681866E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.792801E+09 1025.37   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.116698E+10 1501.73 31-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.104565E+10 1548.12 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.122793E+10 1475.31 27-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.109097E+10 1515.58 14-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.115908E+10 1292.50 23-MAY-07:19 0.346006E+10 2276.35 01-MAY-07:10
June 0.114622E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.107810E+10 1231.65 14-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.120792E+10 1328.20 21-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.109413E+10 1479.46 26-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.114833E+10 1610.53 25-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.115465E+10 1544.28 21-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.114514E+10 1597.59 12-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.136651E+11     0.403429E+11    
Minimum of Months 0.104565E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.122793E+10 1610.53   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.763666E+09 995.18 31-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.681145E+09 1014.13 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.798827E+09 982.49 13-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.705414E+09 988.22 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.747044E+09 882.49 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.737198E+09 809.54 08-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.694042E+09 842.63 14-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.779708E+09 933.98 23-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.709997E+09 979.85 26-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.745661E+09 1047.95 25-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.751503E+09 1029.08 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.743465E+09 1036.12 12-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.885767E+10     0.259979E+11    
Minimum of Months 0.681145E+09 809.54   0.198154E+10 1466.94  
Maximum of Months 0.798827E+09 1047.95   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.120489E+10 1532.18 31-JAN-08:09 0.339718E+10 2276.32 02-JAN-08:09
February 0.106506E+10 1567.12 01-FEB-08:09 0.307485E+10 2276.32 01-FEB-08:09
March 0.123743E+10 1485.53 27-MAR-07:10 0.352283E+10 2276.32 01-MAR-08:09
April 0.108886E+10 1511.27 14-APR-07:10 0.328108E+10 2276.32 03-APR-07:10
May 0.115214E+10 1257.95 23-MAY-07:30 0.346000E+10 2276.32 01-MAY-07:10
June 0.113803E+10 1075.02 01-JUN-07:10 0.339353E+10 2276.32 01-JUN-07:10
July 0.107254E+10 1075.02 03-JUL-07:10 0.334664E+10 2276.32 03-JUL-07:10
August 0.120457E+10 1289.92 21-AUG-07:10 0.352283E+10 2276.32 01-AUG-07:10
September 0.109571E+10 1482.42 26-SEP-07:10 0.327926E+10 2276.32 01-SEP-07:10
October 0.115779E+10 1618.36 25-OCT-07:10 0.339809E+10 2276.32 02-OCT-07:10
November 0.118686E+10 1575.84 01-NOV-07:10 0.332024E+10 2276.32 01-NOV-07:10
December 0.118021E+10 1608.57 12-DEC-08:09 0.334573E+10 2276.32 01-DEC-08:09
             
Annual Sum or Average 0.137841E+11     0.403423E+11    
Minimum of Months 0.106506E+10 1075.02   0.307485E+10 2276.32  
Maximum of Months 0.123743E+10 1618.36   0.352283E+10 2276.32  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.767035E+09 967.35 04-JAN-16:00 0.218927E+10 1466.95 02-JAN-08:09
February 0.681879E+09 983.20 01-FEB-08:09 0.198155E+10 1466.95 01-FEB-08:09
March 0.792807E+09 910.31 27-MAR-07:10 0.227025E+10 1466.95 01-MAR-08:09
April 0.701864E+09 946.87 14-APR-07:10 0.211446E+10 1466.95 03-APR-07:10
May 0.745062E+09 802.83 30-MAY-15:30 0.222976E+10 1466.95 01-MAY-07:10
June 0.737499E+09 692.79 01-JUN-07:10 0.218692E+10 1466.95 01-JUN-07:10
July 0.693476E+09 692.79 03-JUL-07:10 0.215670E+10 1466.95 03-JUL-07:10
August 0.777547E+09 692.79 01-AUG-07:10 0.227025E+10 1466.95 01-AUG-07:10
September 0.705780E+09 906.55 26-SEP-07:10 0.211328E+10 1466.95 01-SEP-07:10
October 0.743439E+09 1025.32 25-OCT-07:10 0.218986E+10 1466.95 02-OCT-07:10
November 0.758653E+09 1020.87 21-NOV-16:00 0.213969E+10 1466.95 01-NOV-07:10
December 0.753522E+09 1024.95 12-DEC-08:09 0.215612E+10 1466.95 01-DEC-08:09
             
Annual Sum or Average 0.885856E+10     0.259981E+11    
Minimum of Months 0.681879E+09 692.79   0.198155E+10 1466.95  
Maximum of Months 0.792807E+09 1025.32   0.227025E+10 1466.95  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.116698E+10 1501.54 31-JAN-08:09 0.339723E+10 2276.35 02-JAN-08:09
February 0.104565E+10 1547.95 01-FEB-08:09 0.307490E+10 2276.35 01-FEB-08:09
March 0.122794E+10 1475.11 27-MAR-07:10 0.352288E+10 2276.35 01-MAR-08:09
April 0.109096E+10 1515.36 14-APR-07:10 0.328113E+10 2276.35 03-APR-07:10
May 0.115908E+10 1292.11 23-MAY-07:19 0.346006E+10 2276.35 01-MAY-07:10
June 0.114624E+10 1075.05 01-JUN-07:10 0.339359E+10 2276.35 01-JUN-07:10
July 0.107809E+10 1231.28 14-JUL-07:10 0.334669E+10 2276.35 03-JUL-07:10
August 0.120791E+10 1327.90 21-AUG-07:10 0.352288E+10 2276.35 01-AUG-07:10
September 0.109412E+10 1479.25 26-SEP-07:10 0.327931E+10 2276.35 01-SEP-07:10
October 0.114833E+10 1610.41 25-OCT-07:10 0.339814E+10 2276.35 02-OCT-07:10
November 0.115466E+10 1544.14 21-NOV-16:00 0.332029E+10 2276.35 01-NOV-07:10
December 0.114514E+10 1597.44 12-DEC-08:09 0.334578E+10 2276.35 01-DEC-08:09
             
Annual Sum or Average 0.136651E+11     0.403429E+11    
Minimum of Months 0.104565E+10 1075.05   0.307490E+10 2276.35  
Maximum of Months 0.122794E+10 1610.41   0.352288E+10 2276.35  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.763685E+09 995.06 31-JAN-08:09 0.218926E+10 1466.94 02-JAN-08:09
February 0.681196E+09 1014.02 01-FEB-08:09 0.198154E+10 1466.94 01-FEB-08:09
March 0.798839E+09 982.68 13-MAR-07:10 0.227023E+10 1466.94 01-MAR-08:09
April 0.705422E+09 988.08 14-APR-07:10 0.211444E+10 1466.94 03-APR-07:10
May 0.747045E+09 882.37 24-MAY-07:10 0.222974E+10 1466.94 01-MAY-07:10
June 0.737200E+09 809.89 08-JUN-07:10 0.218691E+10 1466.94 01-JUN-07:10
July 0.694040E+09 842.40 14-JUL-07:10 0.215669E+10 1466.94 03-JUL-07:10
August 0.779707E+09 933.96 23-AUG-07:10 0.227023E+10 1466.94 01-AUG-07:10
September 0.709994E+09 979.71 26-SEP-07:10 0.211327E+10 1466.94 01-SEP-07:10
October 0.745663E+09 1047.88 25-OCT-07:10 0.218984E+10 1466.94 02-OCT-07:10
November 0.751516E+09 1029.01 01-NOV-07:10 0.213967E+10 1466.94 01-NOV-07:10
December 0.743472E+09 1036.02 12-DEC-08:09 0.215610E+10 1466.94 01-DEC-08:09
             
Annual Sum or Average 0.885778E+10     0.259979E+11    
Minimum of Months 0.681196E+09 809.89   0.198154E+10 1466.94  
Maximum of Months 0.798839E+09 1047.88   0.227023E+10 1466.94  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.387117E+09 405.10 02-JAN-08:09 0.521915E+10 1948.61 01-JAN-00:10
February 0.351144E+09 405.10 01-FEB-08:09 0.942813E+10 3897.21 01-FEB-00:10
March 0.417256E+09 405.10 01-MAR-08:09 0.156645E+11 7794.42 31-MAR-23:10
April 0.372695E+09 405.10 03-APR-07:10 0.201821E+11 7794.42 01-APR-00:10
May 0.402187E+09 405.10 01-MAY-07:10 0.522616E+10 3897.21 31-MAY-23:10
June 0.400242E+09 405.10 01-JUN-07:10 0.101086E+11 5845.82 30-JUN-23:10
July 0.374640E+09 405.10 03-JUL-07:10 0.156645E+11 7794.42 31-JUL-23:10
August 0.417256E+09 405.10 01-AUG-07:10 0.208555E+11 7794.42 01-AUG-00:10
September 0.372695E+09 405.10 01-SEP-07:10 0.505780E+10 3897.21 30-SEP-23:10
October 0.387117E+09 405.10 02-OCT-07:10 0.104453E+11 5845.82 31-OCT-23:10
November 0.382580E+09 405.10 01-NOV-07:10 0.151524E+11 5845.82 01-NOV-00:10
December 0.374640E+09 405.10 01-DEC-08:09 0.208766E+11 7794.42 01-DEC-00:10
             
Annual Sum or Average 0.463957E+10     0.153881E+12    
Minimum of Months 0.351144E+09 405.10   0.505780E+10 1948.61  
Maximum of Months 0.417256E+09 405.10   0.208766E+11 7794.42  



Table of Contents

Report: ZoneElectricSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE LIGHTS ELECTRICITY ENERGY [J] ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP}
January 0.418155E+10 4375.82 02-JAN-08:09 0.254202E+12 94908.13 01-JAN-00:10
February 0.379298E+10 4375.82 01-FEB-08:09 0.459203E+12 189816.26 01-FEB-00:10
March 0.450711E+10 4375.82 01-MAR-08:09 0.762947E+12 379632.52 31-MAR-23:10
April 0.402577E+10 4375.82 03-APR-07:10 0.982982E+12 379632.52 01-APR-00:10
May 0.434433E+10 4375.82 01-MAY-07:10 0.254544E+12 189816.26 31-MAY-23:10
June 0.432333E+10 4375.82 01-JUN-07:10 0.492345E+12 284724.39 30-JUN-23:10
July 0.404678E+10 4375.82 03-JUL-07:10 0.762947E+12 379632.52 31-JUL-23:10
August 0.450711E+10 4375.82 01-AUG-07:10 0.101578E+13 379632.52 01-AUG-00:10
September 0.402577E+10 4375.82 01-SEP-07:10 0.246344E+12 189816.26 30-SEP-23:10
October 0.418155E+10 4375.82 02-OCT-07:10 0.508746E+12 284724.39 31-OCT-23:10
November 0.413254E+10 4375.82 01-NOV-07:10 0.738006E+12 284724.39 01-NOV-00:10
December 0.404678E+10 4375.82 01-DEC-08:09 0.101681E+13 379632.52 01-DEC-00:10
             
Annual Sum or Average 0.501156E+11     0.749486E+13    
Minimum of Months 0.379298E+10 4375.82   0.246344E+12 94908.13  
Maximum of Months 0.450711E+10 4375.82   0.101681E+13 379632.52  



Table of Contents

Report: SpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139531E+11 0.154078E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.139143E+11 0.153333E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128805E+11 0.142779E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.133902E+11 0.148304E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.132595E+11 0.146566E+11 0.348820E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.129193E+11 0.143524E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.160687E+12 0.177742E+12 0.424397E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.121482E+11 0.134523E+11 0.325565E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.145160E+11 0.159851E+11 0.360447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270551E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261305E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275555E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270261E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266527E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261160E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270624E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264424E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266454E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321286E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244881E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280558E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.120254E+11 0.133188E+11 0.270550E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.115676E+11 0.128226E+11 0.261304E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.125309E+11 0.138373E+11 0.275554E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.124961E+11 0.137704E+11 0.270260E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.116025E+11 0.128895E+11 0.266526E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.115676E+11 0.128226E+11 0.261159E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.120254E+11 0.133188E+11 0.270623E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.119080E+11 0.131627E+11 0.264423E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.116025E+11 0.128895E+11 0.266453E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.144308E+12 0.159625E+12 0.321285E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.109099E+11 0.120811E+11 0.244880E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.130364E+11 0.143557E+11 0.280557E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.120204E+10 0.339718E+10 0.00 0.00 0.00 0.00 974161.34 0.375169E+09
February 0.136985E+10 0.106348E+10 0.307485E+10 0.00 0.00 0.00 0.00 1921699.49 0.291296E+09
March 0.163685E+10 0.123594E+10 0.352283E+10 0.00 0.00 0.00 0.00 5951757.09 0.305302E+09
April 0.145243E+10 0.108831E+10 0.328108E+10 0.00 0.00 0.00 0.00 12543804.67 0.128619E+09
May 0.157338E+10 0.115157E+10 0.346000E+10 0.00 0.00 0.00 0.00 53549439.09 19246284.17
June 0.156900E+10 0.113758E+10 0.339353E+10 0.00 0.00 0.00 0.00 49977927.57 11948972.17
July 0.145680E+10 0.107202E+10 0.334664E+10 0.00 0.00 0.00 0.00 71341319.32 2894365.39
August 0.163685E+10 0.120389E+10 0.352283E+10 0.00 0.00 0.00 0.00 69467745.92 12923222.95
September 0.145243E+10 0.109492E+10 0.327926E+10 0.00 0.00 0.00 0.00 60316856.77 32441257.98
October 0.150991E+10 0.115663E+10 0.339809E+10 0.00 0.00 0.00 0.00 48859971.58 0.109399E+09
November 0.149516E+10 0.118464E+10 0.332024E+10 0.00 0.00 0.00 0.00 5177065.44 0.193813E+09
December 0.145680E+10 0.117701E+10 0.334573E+10 0.00 0.00 0.00 0.00 3359680.51 0.341095E+09
                   
Annual Sum or Average 0.181194E+11 0.137680E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.383441E+09 0.182415E+10
Minimum of Months 0.136985E+10 0.106348E+10 0.307485E+10 0.00 0.00 0.00 0.00 974161.34 2894365.39
Maximum of Months 0.163685E+10 0.123594E+10 0.352283E+10 0.00 0.00 0.00 0.00 71341319.32 0.375169E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.766708E+09 0.218927E+10 0.00 0.00 0.00 0.00 549070.00 0.255973E+09
February 0.882782E+09 0.681522E+09 0.198155E+10 0.00 0.00 0.00 0.00 1171627.62 0.196977E+09
March 0.105485E+10 0.792549E+09 0.227025E+10 0.00 0.00 0.00 0.00 3547424.65 0.202162E+09
April 0.936002E+09 0.701629E+09 0.211446E+10 0.00 0.00 0.00 0.00 8375031.05 83373641.87
May 0.101394E+10 0.744864E+09 0.222976E+10 0.00 0.00 0.00 0.00 35120518.58 12534009.69
June 0.101113E+10 0.737295E+09 0.218692E+10 0.00 0.00 0.00 0.00 34088494.32 6796704.99
July 0.938820E+09 0.693308E+09 0.215670E+10 0.00 0.00 0.00 0.00 50171084.46 1286581.58
August 0.105485E+10 0.777390E+09 0.227025E+10 0.00 0.00 0.00 0.00 49809547.81 5779293.91
September 0.936002E+09 0.705544E+09 0.211328E+10 0.00 0.00 0.00 0.00 38812840.27 20977691.77
October 0.973041E+09 0.743134E+09 0.218986E+10 0.00 0.00 0.00 0.00 31662502.53 71285483.66
November 0.963541E+09 0.758148E+09 0.213969E+10 0.00 0.00 0.00 0.00 3220874.71 0.128968E+09
December 0.938820E+09 0.753024E+09 0.215612E+10 0.00 0.00 0.00 0.00 2125436.72 0.221250E+09
                   
Annual Sum or Average 0.116768E+11 0.885511E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.258654E+09 0.120736E+10
Minimum of Months 0.882782E+09 0.681522E+09 0.198155E+10 0.00 0.00 0.00 0.00 549070.00 1286581.58
Maximum of Months 0.105485E+10 0.792549E+09 0.227025E+10 0.00 0.00 0.00 0.00 50171084.46 0.255973E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.116670E+10 0.339723E+10 0.00 0.00 0.00 0.00 646326.54 0.406076E+09
February 0.136988E+10 0.104529E+10 0.307490E+10 0.00 0.00 0.00 0.00 1505366.13 0.310251E+09
March 0.163688E+10 0.122724E+10 0.352288E+10 0.00 0.00 0.00 0.00 4619351.13 0.312857E+09
April 0.145246E+10 0.109022E+10 0.328113E+10 0.00 0.00 0.00 0.00 11346228.08 0.133595E+09
May 0.157341E+10 0.115830E+10 0.346006E+10 0.00 0.00 0.00 0.00 53153281.28 19501705.95
June 0.156904E+10 0.114551E+10 0.339359E+10 0.00 0.00 0.00 0.00 50484432.79 11684805.54
July 0.145684E+10 0.107745E+10 0.334669E+10 0.00 0.00 0.00 0.00 71345453.03 2945049.45
August 0.163688E+10 0.120708E+10 0.352288E+10 0.00 0.00 0.00 0.00 67694736.07 13842605.76
September 0.145246E+10 0.109361E+10 0.327931E+10 0.00 0.00 0.00 0.00 55283859.02 36551894.76
October 0.150994E+10 0.114754E+10 0.339814E+10 0.00 0.00 0.00 0.00 41535091.46 0.127190E+09
November 0.149520E+10 0.115278E+10 0.332029E+10 0.00 0.00 0.00 0.00 4062273.64 0.213157E+09
December 0.145684E+10 0.114392E+10 0.334578E+10 0.00 0.00 0.00 0.00 2627015.42 0.365604E+09
                   
Annual Sum or Average 0.181198E+11 0.136556E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.364303E+09 0.195326E+10
Minimum of Months 0.136988E+10 0.104529E+10 0.307490E+10 0.00 0.00 0.00 0.00 646326.54 2945049.45
Maximum of Months 0.163688E+10 0.122724E+10 0.352288E+10 0.00 0.00 0.00 0.00 71345453.03 0.406076E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.763255E+09 0.218926E+10 0.00 0.00 0.00 0.00 488738.48 0.275048E+09
February 0.882782E+09 0.680797E+09 0.198154E+10 0.00 0.00 0.00 0.00 1051079.53 0.219534E+09
March 0.105485E+10 0.798371E+09 0.227023E+10 0.00 0.00 0.00 0.00 3192466.83 0.236287E+09
April 0.936002E+09 0.705034E+09 0.211444E+10 0.00 0.00 0.00 0.00 6841098.56 0.110037E+09
May 0.101394E+10 0.746777E+09 0.222974E+10 0.00 0.00 0.00 0.00 33671834.80 20140208.85
June 0.101113E+10 0.736966E+09 0.218691E+10 0.00 0.00 0.00 0.00 30019315.94 13709422.98
July 0.938820E+09 0.693853E+09 0.215669E+10 0.00 0.00 0.00 0.00 40246142.41 6145390.78
August 0.105485E+10 0.779455E+09 0.227023E+10 0.00 0.00 0.00 0.00 39580037.62 20221112.52
September 0.936002E+09 0.709726E+09 0.211327E+10 0.00 0.00 0.00 0.00 36714561.84 30521968.28
October 0.973041E+09 0.745265E+09 0.218984E+10 0.00 0.00 0.00 0.00 28293582.44 94100481.20
November 0.963541E+09 0.750901E+09 0.213967E+10 0.00 0.00 0.00 0.00 2807817.76 0.152905E+09
December 0.938820E+09 0.743145E+09 0.215610E+10 0.00 0.00 0.00 0.00 1799612.96 0.269114E+09
                   
Annual Sum or Average 0.116768E+11 0.885355E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.224706E+09 0.144776E+10
Minimum of Months 0.882782E+09 0.680797E+09 0.198154E+10 0.00 0.00 0.00 0.00 488738.48 6145390.78
Maximum of Months 0.105485E+10 0.798371E+09 0.227023E+10 0.00 0.00 0.00 0.00 40246142.41 0.275048E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.120479E+10 0.339718E+10 0.00 0.00 0.00 0.00 4448082.49 0.761386E+09
February 0.136985E+10 0.106505E+10 0.307485E+10 0.00 0.00 0.00 0.00 5804147.70 0.585739E+09
March 0.163685E+10 0.123742E+10 0.352283E+10 0.00 0.00 0.00 0.00 16455130.57 0.635373E+09
April 0.145243E+10 0.108886E+10 0.328108E+10 0.00 0.00 0.00 0.00 29045569.87 0.291214E+09
May 0.157338E+10 0.115212E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.119009E+09 52609521.04
June 0.156900E+10 0.113803E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.109291E+09 39609051.98
July 0.145680E+10 0.107254E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.153591E+09 17101076.31
August 0.163685E+10 0.120457E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.149488E+09 51788699.24
September 0.145243E+10 0.109571E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.138119E+09 78781674.45
October 0.150991E+10 0.115779E+10 0.339809E+10 0.00 0.00 0.00 0.00 0.112585E+09 0.246803E+09
November 0.149516E+10 0.118683E+10 0.332024E+10 0.00 0.00 0.00 0.00 14656280.32 0.401139E+09
December 0.145680E+10 0.118026E+10 0.334573E+10 0.00 0.00 0.00 0.00 9893478.65 0.686839E+09
                   
Annual Sum or Average 0.181194E+11 0.137840E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.862384E+09 0.384838E+10
Minimum of Months 0.136985E+10 0.106505E+10 0.307485E+10 0.00 0.00 0.00 0.00 4448082.49 17101076.31
Maximum of Months 0.163685E+10 0.123742E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.153591E+09 0.761386E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.715730E+09 0.767014E+09 0.218927E+10 0.00 0.00 0.00 0.00 1575387.72 0.541079E+09
February 0.649041E+09 0.681866E+09 0.198155E+10 0.00 0.00 0.00 0.00 2877929.32 0.417141E+09
March 0.773965E+09 0.792801E+09 0.227025E+10 0.00 0.00 0.00 0.00 7894946.02 0.448751E+09
April 0.688021E+09 0.701849E+09 0.211446E+10 0.00 0.00 0.00 0.00 17682546.12 0.210961E+09
May 0.744847E+09 0.745063E+09 0.222976E+10 0.00 0.00 0.00 0.00 75095513.63 39204555.10
June 0.742030E+09 0.737501E+09 0.218692E+10 0.00 0.00 0.00 0.00 71409726.09 28303762.68
July 0.690839E+09 0.693493E+09 0.215670E+10 0.00 0.00 0.00 0.00 98217113.83 13665038.41
August 0.773965E+09 0.777547E+09 0.227025E+10 0.00 0.00 0.00 0.00 96829241.67 37592015.30
September 0.688021E+09 0.705781E+09 0.211328E+10 0.00 0.00 0.00 0.00 85731844.59 57149953.01
October 0.715730E+09 0.743436E+09 0.218986E+10 0.00 0.00 0.00 0.00 67559050.99 0.177395E+09
November 0.708685E+09 0.758636E+09 0.213969E+10 0.00 0.00 0.00 0.00 7397771.34 0.288394E+09
December 0.690839E+09 0.753544E+09 0.215612E+10 0.00 0.00 0.00 0.00 4908674.25 0.478611E+09
                   
Annual Sum or Average 0.858171E+10 0.885853E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.537180E+09 0.273825E+10
Minimum of Months 0.649041E+09 0.681866E+09 0.198155E+10 0.00 0.00 0.00 0.00 1575387.72 13665038.41
Maximum of Months 0.773965E+09 0.792801E+09 0.227025E+10 0.00 0.00 0.00 0.00 98217113.83 0.541079E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.116698E+10 0.339723E+10 0.00 0.00 0.00 0.00 1227508.23 0.921348E+09
February 0.136988E+10 0.104565E+10 0.307490E+10 0.00 0.00 0.00 0.00 3246596.79 0.693118E+09
March 0.163688E+10 0.122793E+10 0.352288E+10 0.00 0.00 0.00 0.00 10182470.50 0.694737E+09
April 0.145246E+10 0.109097E+10 0.328113E+10 0.00 0.00 0.00 0.00 25909459.06 0.316644E+09
May 0.157341E+10 0.115908E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.118622E+09 53532424.13
June 0.156904E+10 0.114622E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.111450E+09 38132014.39
July 0.145684E+10 0.107810E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.154879E+09 16756390.42
August 0.163688E+10 0.120792E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.145446E+09 55658366.87
September 0.145246E+10 0.109413E+10 0.327931E+10 0.00 0.00 0.00 0.00 0.124368E+09 92808362.69
October 0.150994E+10 0.114833E+10 0.339814E+10 0.00 0.00 0.00 0.00 92249178.65 0.313285E+09
November 0.149520E+10 0.115465E+10 0.332029E+10 0.00 0.00 0.00 0.00 8955093.77 0.488879E+09
December 0.145684E+10 0.114514E+10 0.334578E+10 0.00 0.00 0.00 0.00 5812238.77 0.825546E+09
                   
Annual Sum or Average 0.181198E+11 0.136651E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.802348E+09 0.451044E+10
Minimum of Months 0.136988E+10 0.104565E+10 0.307490E+10 0.00 0.00 0.00 0.00 1227508.23 16756390.42
Maximum of Months 0.163688E+10 0.122793E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.154879E+09 0.921348E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.763666E+09 0.218926E+10 0.00 0.00 0.00 0.00 1582889.58 0.559223E+09
February 0.882782E+09 0.681145E+09 0.198154E+10 0.00 0.00 0.00 0.00 2766428.34 0.429307E+09
March 0.105485E+10 0.798827E+09 0.227023E+10 0.00 0.00 0.00 0.00 8773075.64 0.462709E+09
April 0.936002E+09 0.705414E+09 0.211444E+10 0.00 0.00 0.00 0.00 16002039.32 0.228453E+09
May 0.101394E+10 0.747044E+09 0.222974E+10 0.00 0.00 0.00 0.00 76347307.22 45522098.53
June 0.101113E+10 0.737198E+09 0.218691E+10 0.00 0.00 0.00 0.00 68984337.45 35391388.40
July 0.938820E+09 0.694042E+09 0.215669E+10 0.00 0.00 0.00 0.00 95109090.46 18778687.34
August 0.105485E+10 0.779708E+09 0.227023E+10 0.00 0.00 0.00 0.00 94580140.01 48552032.83
September 0.936002E+09 0.709997E+09 0.211327E+10 0.00 0.00 0.00 0.00 84146588.75 67037038.56
October 0.973041E+09 0.745661E+09 0.218984E+10 0.00 0.00 0.00 0.00 67466756.98 0.199664E+09
November 0.963541E+09 0.751503E+09 0.213967E+10 0.00 0.00 0.00 0.00 7699429.82 0.298351E+09
December 0.938820E+09 0.743465E+09 0.215610E+10 0.00 0.00 0.00 0.00 5030779.47 0.509061E+09
                   
Annual Sum or Average 0.116768E+11 0.885767E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.528489E+09 0.290205E+10
Minimum of Months 0.882782E+09 0.681145E+09 0.198154E+10 0.00 0.00 0.00 0.00 1582889.58 18778687.34
Maximum of Months 0.105485E+10 0.798827E+09 0.227023E+10 0.00 0.00 0.00 0.00 95109090.46 0.559223E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150991E+10 0.120489E+10 0.339718E+10 0.00 0.00 0.00 0.00 7124180.21 0.849127E+09
February 0.136985E+10 0.106506E+10 0.307485E+10 0.00 0.00 0.00 0.00 7720923.37 0.652873E+09
March 0.163685E+10 0.123743E+10 0.352283E+10 0.00 0.00 0.00 0.00 19439840.86 0.732220E+09
April 0.145243E+10 0.108886E+10 0.328108E+10 0.00 0.00 0.00 0.00 33049585.49 0.349322E+09
May 0.157338E+10 0.115214E+10 0.346000E+10 0.00 0.00 0.00 0.00 0.138917E+09 71274894.11
June 0.156900E+10 0.113803E+10 0.339353E+10 0.00 0.00 0.00 0.00 0.127935E+09 54275388.23
July 0.145680E+10 0.107254E+10 0.334664E+10 0.00 0.00 0.00 0.00 0.174672E+09 25687395.55
August 0.163685E+10 0.120457E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.174986E+09 69910712.59
September 0.145243E+10 0.109571E+10 0.327926E+10 0.00 0.00 0.00 0.00 0.157492E+09 0.104441E+09
October 0.150991E+10 0.115779E+10 0.339809E+10 0.00 0.00 0.00 0.00 0.128565E+09 0.296083E+09
November 0.149516E+10 0.118686E+10 0.332024E+10 0.00 0.00 0.00 0.00 17719653.91 0.459338E+09
December 0.145680E+10 0.118021E+10 0.334573E+10 0.00 0.00 0.00 0.00 13414787.99 0.777718E+09
                   
Annual Sum or Average 0.181194E+11 0.137841E+11 0.403423E+11 0.00 0.00 0.00 0.00 0.100104E+10 0.444227E+10
Minimum of Months 0.136985E+10 0.106506E+10 0.307485E+10 0.00 0.00 0.00 0.00 7124180.21 25687395.55
Maximum of Months 0.163685E+10 0.123743E+10 0.352283E+10 0.00 0.00 0.00 0.00 0.174986E+09 0.849127E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.767035E+09 0.218927E+10 0.00 0.00 0.00 0.00 2413020.69 0.606798E+09
February 0.882782E+09 0.681879E+09 0.198155E+10 0.00 0.00 0.00 0.00 3434814.44 0.467456E+09
March 0.105485E+10 0.792807E+09 0.227025E+10 0.00 0.00 0.00 0.00 8917658.49 0.524865E+09
April 0.936002E+09 0.701864E+09 0.211446E+10 0.00 0.00 0.00 0.00 20190029.00 0.256364E+09
May 0.101394E+10 0.745062E+09 0.222976E+10 0.00 0.00 0.00 0.00 89264052.01 52410847.19
June 0.101113E+10 0.737499E+09 0.218692E+10 0.00 0.00 0.00 0.00 84239476.96 38535369.62
July 0.938820E+09 0.693476E+09 0.215670E+10 0.00 0.00 0.00 0.00 0.113623E+09 19724702.02
August 0.105485E+10 0.777547E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.114485E+09 50340854.41
September 0.936002E+09 0.705780E+09 0.211328E+10 0.00 0.00 0.00 0.00 0.100070E+09 75436027.77
October 0.973041E+09 0.743439E+09 0.218986E+10 0.00 0.00 0.00 0.00 78793789.22 0.214519E+09
November 0.963541E+09 0.758653E+09 0.213969E+10 0.00 0.00 0.00 0.00 8483792.10 0.336962E+09
December 0.938820E+09 0.753522E+09 0.215612E+10 0.00 0.00 0.00 0.00 5974341.10 0.546402E+09
                   
Annual Sum or Average 0.116768E+11 0.885856E+10 0.259981E+11 0.00 0.00 0.00 0.00 0.629890E+09 0.318981E+10
Minimum of Months 0.882782E+09 0.681879E+09 0.198155E+10 0.00 0.00 0.00 0.00 2413020.69 19724702.02
Maximum of Months 0.105485E+10 0.792807E+09 0.227025E+10 0.00 0.00 0.00 0.00 0.114485E+09 0.606798E+09



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.150994E+10 0.116698E+10 0.339723E+10 0.00 0.00 0.00 0.00 1453228.26 0.105780E+10
February 0.136988E+10 0.104565E+10 0.307490E+10 0.00 0.00 0.00 0.00 3767432.52 0.785850E+09
March 0.163688E+10 0.122794E+10 0.352288E+10 0.00 0.00 0.00 0.00 11881572.49 0.811434E+09
April 0.145246E+10 0.109096E+10 0.328113E+10 0.00 0.00 0.00 0.00 29678866.01 0.383323E+09
May 0.157341E+10 0.115908E+10 0.346006E+10 0.00 0.00 0.00 0.00 0.138744E+09 72530632.77
June 0.156904E+10 0.114624E+10 0.339359E+10 0.00 0.00 0.00 0.00 0.129941E+09 52491431.21
July 0.145684E+10 0.107809E+10 0.334669E+10 0.00 0.00 0.00 0.00 0.176414E+09 25144358.98
August 0.163688E+10 0.120791E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.171510E+09 75107001.06
September 0.145246E+10 0.109412E+10 0.327931E+10 0.00 0.00 0.00 0.00 0.146266E+09 0.122645E+09
October 0.150994E+10 0.114833E+10 0.339814E+10 0.00 0.00 0.00 0.00 0.109530E+09 0.385110E+09
November 0.149520E+10 0.115466E+10 0.332029E+10 0.00 0.00 0.00 0.00 10767721.50 0.582516E+09
December 0.145684E+10 0.114514E+10 0.334578E+10 0.00 0.00 0.00 0.00 6896469.22 0.958832E+09
                   
Annual Sum or Average 0.181198E+11 0.136651E+11 0.403429E+11 0.00 0.00 0.00 0.00 0.936850E+09 0.531278E+10
Minimum of Months 0.136988E+10 0.104565E+10 0.307490E+10 0.00 0.00 0.00 0.00 1453228.26 25144358.98
Maximum of Months 0.163688E+10 0.122794E+10 0.352288E+10 0.00 0.00 0.00 0.00 0.176414E+09 0.105780E+10



Table of Contents

Report: SpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.973041E+09 0.763685E+09 0.218926E+10 0.00 0.00 0.00 0.00 2268054.90 0.639381E+09
February 0.882782E+09 0.681196E+09 0.198154E+10 0.00 0.00 0.00 0.00 3366380.00 0.489028E+09
March 0.105485E+10 0.798839E+09 0.227023E+10 0.00 0.00 0.00 0.00 10499933.05 0.541874E+09
April 0.936002E+09 0.705422E+09 0.211444E+10 0.00 0.00 0.00 0.00 18970839.01 0.276669E+09
May 0.101394E+10 0.747045E+09 0.222974E+10 0.00 0.00 0.00 0.00 91678204.14 58977943.17
June 0.101113E+10 0.737200E+09 0.218691E+10 0.00 0.00 0.00 0.00 82919143.89 46350694.09
July 0.938820E+09 0.694040E+09 0.215669E+10 0.00 0.00 0.00 0.00 0.112768E+09 24916743.96
August 0.105485E+10 0.779707E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.113350E+09 63058548.28
September 0.936002E+09 0.709994E+09 0.211327E+10 0.00 0.00 0.00 0.00 0.100468E+09 86265376.53
October 0.973041E+09 0.745663E+09 0.218984E+10 0.00 0.00 0.00 0.00 80051193.22 0.241770E+09
November 0.963541E+09 0.751516E+09 0.213967E+10 0.00 0.00 0.00 0.00 9424909.19 0.349874E+09
December 0.938820E+09 0.743472E+09 0.215610E+10 0.00 0.00 0.00 0.00 6353001.42 0.587914E+09
                   
Annual Sum or Average 0.116768E+11 0.885778E+10 0.259979E+11 0.00 0.00 0.00 0.00 0.632118E+09 0.340608E+10
Minimum of Months 0.882782E+09 0.681196E+09 0.198154E+10 0.00 0.00 0.00 0.00 2268054.90 24916743.96
Maximum of Months 0.105485E+10 0.798839E+09 0.227023E+10 0.00 0.00 0.00 0.00 0.113350E+09 0.639381E+09



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.174411E+09 0.387117E+09 0.521915E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.158233E+09 0.351144E+09 0.942813E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.189074E+09 0.417256E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.167772E+09 0.372695E+09 0.201821E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.181743E+09 0.402187E+09 0.522616E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.181238E+09 0.400242E+09 0.101086E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.168277E+09 0.374640E+09 0.156645E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.189074E+09 0.417256E+09 0.208555E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.167772E+09 0.372695E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.174411E+09 0.387117E+09 0.104453E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.172708E+09 0.382580E+09 0.151524E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.168277E+09 0.374640E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.209299E+10 0.463957E+10 0.153881E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.158233E+09 0.351144E+09 0.505780E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.189074E+09 0.417256E+09 0.208766E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [J] ZONE LIGHTS TOTAL HEATING ENERGY [J] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 0.377547E+10 0.418155E+10 0.254202E+12 0.00 0.00 0.00 0.00 0.00 0.00
February 0.342526E+10 0.379298E+10 0.459203E+12 0.00 0.00 0.00 0.00 0.00 0.00
March 0.409289E+10 0.450711E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.363176E+10 0.402577E+10 0.982982E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.393418E+10 0.434433E+10 0.254544E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.392325E+10 0.432333E+10 0.492345E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.364269E+10 0.404678E+10 0.762947E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.409289E+10 0.450711E+10 0.101578E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.363176E+10 0.402577E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.377547E+10 0.418155E+10 0.508746E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.373861E+10 0.413254E+10 0.738006E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.364269E+10 0.404678E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00
                   
Annual Sum or Average 0.453069E+11 0.501156E+11 0.749486E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.342526E+10 0.379298E+10 0.246344E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.409289E+10 0.450711E+10 0.101681E+13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 756616.99 0.831277E+09
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2105378.49 0.642694E+09
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8465324.97 0.663163E+09
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19872015.22 0.287452E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 96284671.94 36334020.21
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 89668350.85 27884009.65
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133522E+09 8964353.71
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.121910E+09 37255899.35
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.107992E+09 69111371.37
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 82794927.72 0.250326E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 7146446.06 0.430944E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4675997.62 0.752936E+09
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.675194E+09 0.403834E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 756616.99 8964353.71
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.133522E+09 0.831277E+09



Table of Contents

Report: SpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2457497.91 0.141169E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4751408.35 0.108941E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 18121804.62 0.113401E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36170905.58 0.504331E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.171254E+09 66827058.93
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.157965E+09 53479403.91
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.239734E+09 17590643.05
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.216997E+09 72785163.98
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.198877E+09 0.120467E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.149844E+09 0.435246E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14385621.44 0.736413E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9451998.33 0.126568E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.122001E+10 0.690793E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2457497.91 17590643.05
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.239734E+09 0.141169E+10



Table of Contents

Report: SpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1339814.18 0.141611E+10
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1887338.76 0.109397E+10
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9655160.32 0.120211E+10
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 24535461.27 0.576125E+09
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.150044E+09 91778973.87
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.144173E+09 69147311.57
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.209851E+09 29863348.02
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.203402E+09 94892426.91
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.182470E+09 0.148711E+09
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.121525E+09 0.483314E+09
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10035417.17 0.767395E+09
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6972336.08 0.129296E+10
                   
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.106589E+10 0.726638E+10
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1339814.18 29863348.02
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.209851E+09 0.141611E+10



Table of Contents

Report: PeakSpaceGainsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 17832.21 02-JAN-10:09 15519.45 02-JAN-08:09 13457.54 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 17832.21 01-FEB-10:09 15519.45 01-FEB-08:09 13457.54 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 17832.21 01-MAR-10:09 15519.45 01-MAR-08:09 13457.54 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
April 17832.21 03-APR-09:09 15519.45 03-APR-07:10 13457.54 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 17832.21 01-MAY-09:09 15519.45 01-MAY-07:10 13457.54 01-MAY-00:10 0.00 0.00 0.00 0.00 0.00 0.00
June 17832.21 01-JUN-09:09 15519.45 01-JUN-07:10 13457.54 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
July 17832.21 03-JUL-09:09 15519.45 03-JUL-07:10 13457.54 01-JUL-00:10 0.00 0.00 0.00 0.00 0.00 0.00
August 17832.21 01-AUG-09:09 15519.45 01-AUG-07:10 13457.54 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 17832.21 01-SEP-09:09 15519.45 01-SEP-07:10 13457.54 01-SEP-00:10 0.00 0.00 0.00 0.00 0.00 0.00
October 17832.21 02-OCT-09:09 15519.45 02-OCT-07:10 13457.54 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00 0.00
November 17832.21 01-NOV-09:09 15519.45 01-NOV-07:10 13457.54 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 17832.21 01-DEC-10:09 15519.45 01-DEC-08:09 13457.54 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17832.21   15519.45   13457.54   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.59 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.59 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.59 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.59 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.59 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.59 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.59 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.59 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.59 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.59 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.59 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.59 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.59   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 16014.58 02-JAN-10:09 13937.56 02-JAN-08:09 18128.52 02-JAN-08:09 0.00 0.00 0.00 0.00 0.00 0.00
February 16014.58 01-FEB-10:09 13937.56 01-FEB-08:09 18128.52 01-FEB-08:09 0.00 0.00 0.00 0.00 0.00 0.00
March 16014.58 01-MAR-10:09 13937.56 01-MAR-08:09 18128.52 01-MAR-08:09 0.00 0.00 0.00 0.00 0.00 0.00
April 16014.58 03-APR-09:09 13937.56 03-APR-07:10 18128.52 03-APR-07:10 0.00 0.00 0.00 0.00 0.00 0.00
May 16014.58 01-MAY-09:09 13937.56 01-MAY-07:10 18128.52 01-MAY-07:10 0.00 0.00 0.00 0.00 0.00 0.00
June 16014.58 01-JUN-09:09 13937.56 01-JUN-07:10 18128.52 01-JUN-07:10 0.00 0.00 0.00 0.00 0.00 0.00
July 16014.58 03-JUL-09:09 13937.56 03-JUL-07:10 18128.52 03-JUL-07:10 0.00 0.00 0.00 0.00 0.00 0.00
August 16014.58 01-AUG-09:09 13937.56 01-AUG-07:10 18128.52 01-AUG-07:10 0.00 0.00 0.00 0.00 0.00 0.00
September 16014.58 01-SEP-09:09 13937.56 01-SEP-07:10 18128.52 01-SEP-07:10 0.00 0.00 0.00 0.00 0.00 0.00
October 16014.58 02-OCT-09:09 13937.56 02-OCT-07:10 18128.52 02-OCT-07:10 0.00 0.00 0.00 0.00 0.00 0.00
November 16014.58 01-NOV-09:09 13937.56 01-NOV-07:10 18128.52 01-NOV-07:10 0.00 0.00 0.00 0.00 0.00 0.00
December 16014.58 01-DEC-10:09 13937.56 01-DEC-08:09 18128.52 01-DEC-08:09 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16014.58   13937.56   18128.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1525.96 31-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 46.24 16-JAN-15:00 698.19 09-JAN-05:00
February 2010.79 01-FEB-10:09 1561.87 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 49.90 02-FEB-13:00 978.72 05-FEB-08:00
March 2010.79 01-MAR-10:09 1477.64 27-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 98.99 05-MAR-12:53 846.44 20-MAR-22:00
April 2010.79 03-APR-09:09 1504.27 14-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 151.52 29-APR-17:02 518.20 01-APR-21:00
May 2010.79 01-MAY-09:09 1243.87 23-MAY-07:30 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 231.51 21-MAY-13:53 109.60 09-MAY-02:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 267.85 10-JUN-17:02 157.66 06-JUN-22:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 233.11 22-JUL-18:50 92.62 30-JUL-11:00
August 2010.79 01-AUG-09:09 1276.27 21-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 329.70 20-AUG-14:00 191.82 25-AUG-24:00
September 2010.79 01-SEP-09:09 1474.55 26-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 320.63 09-SEP-17:02 198.99 05-SEP-03:00
October 2010.79 02-OCT-09:09 1614.51 25-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 368.55 09-OCT-14:00 420.55 29-OCT-02:00
November 2010.79 01-NOV-09:09 1570.75 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 62.66 05-NOV-13:10 602.79 12-NOV-08:00
December 2010.79 01-DEC-10:09 1604.50 12-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 58.01 10-DEC-15:10 911.51 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 46.24   92.62  
Maximum of Months 2010.79   1614.51   2276.32   0.00 0.00 0.00 0.00 368.55   978.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 964.48 04-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 24.82 16-JAN-15:00 463.20 22-JAN-08:00
February 1295.83 01-FEB-10:09 981.55 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 33.27 02-FEB-13:00 682.79 05-FEB-10:00
March 1295.83 01-MAR-10:09 906.86 27-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 57.14 05-MAR-13:00 557.34 20-MAR-22:00
April 1295.83 03-APR-09:09 944.30 14-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 105.57 29-APR-17:02 335.10 01-APR-21:00
May 1295.83 01-MAY-09:09 802.12 30-MAY-15:30 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 171.81 21-MAY-13:53 75.13 14-MAY-12:10
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 187.98 10-JUN-17:02 100.47 06-JUN-22:00
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 164.82 22-JUL-18:50 88.66 30-JUL-11:00
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 222.80 20-AUG-14:00 117.72 25-AUG-24:00
September 1295.83 01-SEP-09:09 902.72 26-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 216.84 09-SEP-22:53 130.97 05-SEP-03:00
October 1295.83 02-OCT-09:09 1024.08 25-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 237.46 09-OCT-13:40 277.39 29-OCT-02:00
November 1295.83 01-NOV-09:09 1020.12 21-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 40.49 05-NOV-13:10 451.88 12-NOV-08:30
December 1295.83 01-DEC-10:09 1024.01 12-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 38.68 10-DEC-15:10 587.06 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 24.82   75.13  
Maximum of Months 1295.83   1024.08   1466.95   0.00 0.00 0.00 0.00 237.46   682.79  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1493.99 31-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 18.32 19-JAN-12:10 721.06 26-JAN-03:00
February 2010.83 01-FEB-10:09 1541.87 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 49.90 02-FEB-13:00 974.68 05-FEB-08:00
March 2010.83 01-MAR-10:09 1466.75 27-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 70.79 26-MAR-13:48 857.71 20-MAR-22:00
April 2010.83 03-APR-09:09 1508.53 14-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 133.25 29-APR-17:02 526.89 01-APR-21:00
May 2010.83 01-MAY-09:09 1279.30 23-MAY-07:19 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 228.31 21-MAY-13:53 110.27 09-MAY-02:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 275.78 10-JUN-17:02 156.68 06-JUN-22:00
July 2010.83 03-JUL-09:09 1216.90 14-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 237.07 22-JUL-18:50 100.00 30-JUL-11:00
August 2010.83 01-AUG-09:09 1315.84 21-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 325.24 20-AUG-14:00 195.07 25-AUG-24:00
September 2010.83 01-SEP-09:09 1471.26 26-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 304.72 09-SEP-17:02 212.48 05-SEP-03:00
October 2010.83 02-OCT-09:09 1606.21 25-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 341.60 09-OCT-14:00 441.31 29-OCT-02:00
November 2010.83 01-NOV-09:09 1537.51 21-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 38.10 07-NOV-13:00 656.35 12-NOV-08:10
December 2010.83 01-DEC-10:09 1592.83 12-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 36.30 13-DEC-14:00 899.22 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 18.32   100.00  
Maximum of Months 2010.83   1606.21   2276.35   0.00 0.00 0.00 0.00 341.60   974.68  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 994.16 31-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 12.22 19-JAN-12:10 501.19 26-JAN-03:00
February 1295.83 01-FEB-10:09 1013.27 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 33.27 02-FEB-13:00 692.41 05-FEB-07:55
March 1295.83 01-MAR-10:09 979.22 13-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 53.97 26-MAR-13:48 628.99 20-MAR-22:00
April 1295.83 03-APR-09:09 987.18 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 57.24 29-APR-17:07 427.75 01-APR-21:00
May 1295.83 01-MAY-09:09 880.96 24-MAY-07:19 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 158.40 21-MAY-13:53 96.23 09-MAY-02:00
June 1295.83 01-JUN-09:09 806.15 08-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 162.78 10-JUN-17:08 147.06 06-JUN-22:00
July 1295.83 03-JUL-09:09 840.50 14-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 137.12 16-JUL-15:14 94.88 30-JUL-11:00
August 1295.83 01-AUG-09:09 932.17 23-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 210.19 20-AUG-14:00 177.29 25-AUG-24:00
September 1295.83 01-SEP-09:09 978.74 26-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 196.43 09-SEP-17:08 153.06 13-SEP-02:50
October 1295.83 02-OCT-09:09 1047.35 25-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 230.45 09-OCT-13:36 328.67 29-OCT-02:00
November 1295.83 01-NOV-09:09 1028.27 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 25.82 07-NOV-13:00 443.74 12-NOV-08:00
December 1295.83 01-DEC-10:09 1035.42 12-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 24.20 13-DEC-14:00 694.56 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   806.15   1466.94   0.00 0.00 0.00 0.00 12.22   94.88  
Maximum of Months 1295.83   1047.35   1466.94   0.00 0.00 0.00 0.00 230.45   694.56  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1532.38 31-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 173.59 16-JAN-15:00 1453.54 21-JAN-05:55
February 2010.79 01-FEB-10:09 1567.29 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 207.59 20-FEB-14:53 1978.03 05-FEB-07:55
March 2010.79 01-MAR-10:09 1485.74 27-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 306.42 05-MAR-12:43 1780.29 20-MAR-22:00
April 2010.79 03-APR-09:09 1511.49 14-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 382.90 29-APR-17:02 1051.03 01-APR-21:00
May 2010.79 01-MAY-09:09 1258.37 23-MAY-07:30 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 496.42 07-MAY-13:53 233.90 09-MAY-02:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 632.00 10-JUN-17:02 324.29 06-JUN-22:00
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 545.60 22-JUL-18:50 208.13 30-JUL-11:00
August 2010.79 01-AUG-09:09 1290.21 21-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 725.46 20-AUG-14:00 465.54 25-AUG-23:53
September 2010.79 01-SEP-09:09 1482.63 26-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 751.83 09-SEP-17:02 480.87 05-SEP-02:55
October 2010.79 02-OCT-09:09 1618.48 25-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 848.78 09-OCT-14:00 840.97 29-OCT-02:00
November 2010.79 01-NOV-09:09 1575.96 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 204.47 05-NOV-13:00 1259.20 12-NOV-06:55
December 2010.79 01-DEC-10:09 1608.72 12-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 181.85 10-DEC-14:50 1792.49 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 173.59   208.13  
Maximum of Months 2010.79   1618.48   2276.32   0.00 0.00 0.00 0.00 848.78   1978.03  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1239.33 02-JAN-08:09 967.16 04-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 87.34 16-JAN-15:00 966.54 21-JAN-05:55
February 1239.33 01-FEB-08:09 983.28 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 113.35 20-FEB-14:53 1403.18 05-FEB-08:00
March 1239.33 01-MAR-08:09 910.38 27-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 133.20 05-MAR-13:10 1209.40 20-MAR-22:00
April 1239.33 03-APR-07:10 946.98 14-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 240.07 29-APR-17:02 723.68 01-APR-21:00
May 1239.33 01-MAY-07:10 802.93 30-MAY-15:30 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 316.60 21-MAY-13:40 198.65 14-MAY-12:10
June 1239.33 01-JUN-07:10 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 431.09 10-JUN-17:02 222.58 06-JUN-22:00
July 1239.33 03-JUL-07:10 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 362.53 22-JUL-18:50 243.53 30-JUL-11:00
August 1239.33 01-AUG-07:10 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 483.53 20-AUG-14:00 319.81 25-AUG-23:53
September 1239.33 01-SEP-07:10 906.63 26-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 502.97 09-SEP-17:02 338.48 05-SEP-02:55
October 1239.33 02-OCT-07:10 1025.37 25-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 585.73 09-OCT-13:56 580.48 29-OCT-02:00
November 1239.33 01-NOV-07:10 1020.96 21-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 97.80 05-NOV-13:00 974.64 12-NOV-08:40
December 1239.33 01-DEC-08:09 1025.04 12-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 91.43 10-DEC-14:55 1201.14 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1239.33   692.79   1466.95   0.00 0.00 0.00 0.00 87.34   198.65  
Maximum of Months 1239.33   1025.37   1466.95   0.00 0.00 0.00 0.00 585.73   1403.18  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1501.73 31-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 38.49 19-JAN-12:10 1583.02 26-JAN-03:00
February 2010.83 01-FEB-10:09 1548.12 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 114.07 02-FEB-13:00 2105.80 05-FEB-08:00
March 2010.83 01-MAR-10:09 1475.31 27-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 161.33 26-MAR-13:48 1862.17 20-MAR-22:00
April 2010.83 03-APR-09:09 1515.58 14-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 330.72 29-APR-17:02 1113.00 01-APR-21:00
May 2010.83 01-MAY-09:09 1292.50 23-MAY-07:19 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 465.46 07-MAY-13:53 240.96 09-MAY-02:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 650.69 10-JUN-17:02 325.83 06-JUN-22:00
July 2010.83 03-JUL-09:09 1231.65 14-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 558.40 22-JUL-18:50 216.70 30-JUL-11:00
August 2010.83 01-AUG-09:09 1328.20 21-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 725.31 20-AUG-14:00 478.22 25-AUG-23:53
September 2010.83 01-SEP-09:09 1479.46 26-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 709.26 09-SEP-17:02 519.82 05-SEP-02:55
October 2010.83 02-OCT-09:09 1610.53 25-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 780.85 09-OCT-14:00 972.95 29-OCT-02:00
November 2010.83 01-NOV-09:09 1544.28 21-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 83.05 07-NOV-13:00 1431.70 12-NOV-08:00
December 2010.83 01-DEC-10:09 1597.59 12-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 83.27 13-DEC-14:00 1889.38 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 38.49   216.70  
Maximum of Months 2010.83   1610.53   2276.35   0.00 0.00 0.00 0.00 780.85   2105.80  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 995.18 31-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 60.11 16-JAN-13:00 998.79 26-JAN-03:00
February 1295.83 01-FEB-10:09 1014.13 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 76.05 02-FEB-13:00 1350.26 05-FEB-07:55
March 1295.83 01-MAR-10:09 982.49 13-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 178.65 05-MAR-12:43 1254.75 20-MAR-22:00
April 1295.83 03-APR-09:09 988.22 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 138.05 29-APR-17:07 791.53 01-APR-17:55
May 1295.83 01-MAY-09:09 882.49 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 321.36 21-MAY-14:00 202.27 06-MAY-20:00
June 1295.83 01-JUN-09:09 809.54 08-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 373.96 10-JUN-17:08 256.54 06-JUN-22:00
July 1295.83 03-JUL-09:09 842.63 14-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 328.29 16-JUL-13:00 176.83 31-JUL-02:70
August 1295.83 01-AUG-09:09 933.98 23-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 483.54 20-AUG-14:00 353.86 25-AUG-23:53
September 1295.83 01-SEP-09:09 979.85 26-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 455.01 09-SEP-17:08 354.48 05-SEP-02:55
October 1295.83 02-OCT-09:09 1047.95 25-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 568.91 09-OCT-13:56 628.33 29-OCT-02:00
November 1295.83 01-NOV-09:09 1029.08 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 116.60 05-NOV-13:00 885.36 12-NOV-06:55
December 1295.83 01-DEC-10:09 1036.12 12-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 87.44 10-DEC-11:30 1245.24 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   809.54   1466.94   0.00 0.00 0.00 0.00 60.11   176.83  
Maximum of Months 1295.83   1047.95   1466.94   0.00 0.00 0.00 0.00 568.91   1350.26  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.79 02-JAN-10:09 1532.18 31-JAN-08:09 2276.32 02-JAN-08:09 0.00 0.00 0.00 0.00 233.02 16-JAN-15:00 1790.90 21-JAN-06:00
February 2010.79 01-FEB-10:09 1567.12 01-FEB-08:09 2276.32 01-FEB-08:09 0.00 0.00 0.00 0.00 232.96 20-FEB-14:43 2289.82 05-FEB-08:00
March 2010.79 01-MAR-10:09 1485.53 27-MAR-07:10 2276.32 01-MAR-08:09 0.00 0.00 0.00 0.00 382.00 05-MAR-12:33 2078.79 20-MAR-22:00
April 2010.79 03-APR-09:09 1511.27 14-APR-07:10 2276.32 03-APR-07:10 0.00 0.00 0.00 0.00 413.14 29-APR-17:02 1264.86 01-APR-17:55
May 2010.79 01-MAY-09:09 1257.95 23-MAY-07:30 2276.32 01-MAY-07:10 0.00 0.00 0.00 0.00 599.35 07-MAY-13:53 297.91 09-MAY-02:00
June 2010.79 01-JUN-09:09 1075.02 01-JUN-07:10 2276.32 01-JUN-07:10 0.00 0.00 0.00 0.00 721.55 10-JUN-17:02 413.45 06-JUN-21:20
July 2010.79 03-JUL-09:09 1075.02 03-JUL-07:10 2276.32 03-JUL-07:10 0.00 0.00 0.00 0.00 580.46 16-JUL-15:16 317.09 30-JUL-10:53
August 2010.79 01-AUG-09:09 1289.92 21-AUG-07:10 2276.32 01-AUG-07:10 0.00 0.00 0.00 0.00 886.90 20-AUG-14:00 570.34 25-AUG-23:53
September 2010.79 01-SEP-09:09 1482.42 26-SEP-07:10 2276.32 01-SEP-07:10 0.00 0.00 0.00 0.00 886.78 09-SEP-17:02 635.48 05-SEP-02:55
October 2010.79 02-OCT-09:09 1618.36 25-OCT-07:10 2276.32 02-OCT-07:10 0.00 0.00 0.00 0.00 1030.75 09-OCT-13:56 908.66 29-OCT-02:00
November 2010.79 01-NOV-09:09 1575.84 01-NOV-07:10 2276.32 01-NOV-07:10 0.00 0.00 0.00 0.00 234.19 05-NOV-13:00 1485.87 12-NOV-06:55
December 2010.79 01-DEC-10:09 1608.57 12-DEC-08:09 2276.32 01-DEC-08:09 0.00 0.00 0.00 0.00 213.11 10-DEC-15:00 1945.37 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.79   1075.02   2276.32   0.00 0.00 0.00 0.00 213.11   297.91  
Maximum of Months 2010.79   1618.36   2276.32   0.00 0.00 0.00 0.00 1030.75   2289.82  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 967.35 04-JAN-16:00 1466.95 02-JAN-08:09 0.00 0.00 0.00 0.00 115.47 16-JAN-15:00 1193.97 21-JAN-05:55
February 1295.83 01-FEB-10:09 983.20 01-FEB-08:09 1466.95 01-FEB-08:09 0.00 0.00 0.00 0.00 111.31 20-FEB-15:10 1526.89 05-FEB-07:55
March 1295.83 01-MAR-10:09 910.31 27-MAR-07:10 1466.95 01-MAR-08:09 0.00 0.00 0.00 0.00 156.10 05-MAR-13:00 1426.17 20-MAR-22:00
April 1295.83 03-APR-09:09 946.87 14-APR-07:10 1466.95 03-APR-07:10 0.00 0.00 0.00 0.00 254.13 29-APR-17:02 880.53 01-APR-17:55
May 1295.83 01-MAY-09:09 802.83 30-MAY-15:30 1466.95 01-MAY-07:10 0.00 0.00 0.00 0.00 418.23 21-MAY-13:53 271.04 14-MAY-12:10
June 1295.83 01-JUN-09:09 692.79 01-JUN-07:10 1466.95 01-JUN-07:10 0.00 0.00 0.00 0.00 491.70 10-JUN-17:02 284.21 06-JUN-21:20
July 1295.83 03-JUL-09:09 692.79 03-JUL-07:10 1466.95 03-JUL-07:10 0.00 0.00 0.00 0.00 404.18 16-JUL-15:16 234.45 30-JUL-10:50
August 1295.83 01-AUG-09:09 692.79 01-AUG-07:10 1466.95 01-AUG-07:10 0.00 0.00 0.00 0.00 591.25 20-AUG-14:00 392.86 25-AUG-23:53
September 1295.83 01-SEP-09:09 906.55 26-SEP-07:10 1466.95 01-SEP-07:10 0.00 0.00 0.00 0.00 592.52 09-SEP-17:02 441.83 05-SEP-02:55
October 1295.83 02-OCT-09:09 1025.32 25-OCT-07:10 1466.95 02-OCT-07:10 0.00 0.00 0.00 0.00 718.74 09-OCT-13:56 632.88 29-OCT-02:00
November 1295.83 01-NOV-09:09 1020.87 21-NOV-16:00 1466.95 01-NOV-07:10 0.00 0.00 0.00 0.00 108.65 05-NOV-13:00 1142.20 12-NOV-08:40
December 1295.83 01-DEC-10:09 1024.95 12-DEC-08:09 1466.95 01-DEC-08:09 0.00 0.00 0.00 0.00 113.18 10-DEC-15:00 1309.12 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   692.79   1466.95   0.00 0.00 0.00 0.00 108.65   234.45  
Maximum of Months 1295.83   1025.32   1466.95   0.00 0.00 0.00 0.00 718.74   1526.89  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 2010.83 02-JAN-10:09 1501.54 31-JAN-08:09 2276.35 02-JAN-08:09 0.00 0.00 0.00 0.00 47.10 19-JAN-12:00 1790.93 21-JAN-05:55
February 2010.83 01-FEB-10:09 1547.95 01-FEB-08:09 2276.35 01-FEB-08:09 0.00 0.00 0.00 0.00 137.94 02-FEB-13:00 2290.08 05-FEB-07:55
March 2010.83 01-MAR-10:09 1475.11 27-MAR-07:10 2276.35 01-MAR-08:09 0.00 0.00 0.00 0.00 200.12 26-MAR-13:57 2198.28 20-MAR-22:00
April 2010.83 03-APR-09:09 1515.36 14-APR-07:10 2276.35 03-APR-07:10 0.00 0.00 0.00 0.00 344.76 29-APR-17:02 1360.44 01-APR-17:55
May 2010.83 01-MAY-09:09 1292.11 23-MAY-07:19 2276.35 01-MAY-07:10 0.00 0.00 0.00 0.00 588.76 07-MAY-13:53 306.99 09-MAY-02:00
June 2010.83 01-JUN-09:09 1075.05 01-JUN-07:10 2276.35 01-JUN-07:10 0.00 0.00 0.00 0.00 743.06 10-JUN-17:02 415.93 06-JUN-21:20
July 2010.83 03-JUL-09:09 1231.28 14-JUL-07:10 2276.35 03-JUL-07:10 0.00 0.00 0.00 0.00 579.96 22-JUL-18:50 324.57 30-JUL-10:53
August 2010.83 01-AUG-09:09 1327.90 21-AUG-07:10 2276.35 01-AUG-07:10 0.00 0.00 0.00 0.00 886.89 20-AUG-14:00 587.27 25-AUG-23:53
September 2010.83 01-SEP-09:09 1479.25 26-SEP-07:10 2276.35 01-SEP-07:10 0.00 0.00 0.00 0.00 833.45 09-SEP-17:10 679.30 05-SEP-02:55
October 2010.83 02-OCT-09:09 1610.41 25-OCT-07:10 2276.35 02-OCT-07:10 0.00 0.00 0.00 0.00 944.29 09-OCT-14:00 1093.62 29-OCT-02:00
November 2010.83 01-NOV-09:09 1544.14 21-NOV-16:00 2276.35 01-NOV-07:10 0.00 0.00 0.00 0.00 107.05 07-NOV-13:00 1776.03 12-NOV-11:00
December 2010.83 01-DEC-10:09 1597.44 12-DEC-08:09 2276.35 01-DEC-08:09 0.00 0.00 0.00 0.00 101.07 13-DEC-14:00 2044.23 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 2010.83   1075.05   2276.35   0.00 0.00 0.00 0.00 47.10   306.99  
Maximum of Months 2010.83   1610.41   2276.35   0.00 0.00 0.00 0.00 944.29   2290.08  



Table of Contents

Report: PeakSpaceGainsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 1295.83 02-JAN-10:09 995.06 31-JAN-08:09 1466.94 02-JAN-08:09 0.00 0.00 0.00 0.00 95.79 16-JAN-13:23 1194.02 21-JAN-05:55
February 1295.83 01-FEB-10:09 1014.02 01-FEB-08:09 1466.94 01-FEB-08:09 0.00 0.00 0.00 0.00 91.96 02-FEB-13:00 1526.72 05-FEB-07:55
March 1295.83 01-MAR-10:09 982.68 13-MAR-07:10 1466.94 01-MAR-08:09 0.00 0.00 0.00 0.00 220.83 05-MAR-12:33 1478.82 20-MAR-22:00
April 1295.83 03-APR-09:09 988.08 14-APR-07:10 1466.94 03-APR-07:10 0.00 0.00 0.00 0.00 162.87 29-APR-17:07 969.61 01-APR-17:55
May 1295.83 01-MAY-09:09 882.37 24-MAY-07:10 1466.94 01-MAY-07:10 0.00 0.00 0.00 0.00 435.83 21-MAY-13:53 241.56 06-MAY-19:50
June 1295.83 01-JUN-09:09 809.89 08-JUN-07:10 1466.94 01-JUN-07:10 0.00 0.00 0.00 0.00 456.51 10-JUN-17:08 326.80 06-JUN-21:20
July 1295.83 03-JUL-09:09 842.40 14-JUL-07:10 1466.94 03-JUL-07:10 0.00 0.00 0.00 0.00 400.17 02-JUL-11:50 235.62 31-JUL-02:00
August 1295.83 01-AUG-09:09 933.96 23-AUG-07:10 1466.94 01-AUG-07:10 0.00 0.00 0.00 0.00 591.27 20-AUG-14:00 436.26 25-AUG-23:53
September 1295.83 01-SEP-09:09 979.71 26-SEP-07:10 1466.94 01-SEP-07:10 0.00 0.00 0.00 0.00 558.90 09-SEP-17:08 456.11 05-SEP-02:55
October 1295.83 02-OCT-09:09 1047.88 25-OCT-07:10 1466.94 02-OCT-07:10 0.00 0.00 0.00 0.00 705.55 09-OCT-13:56 706.81 29-OCT-02:00
November 1295.83 01-NOV-09:09 1029.01 01-NOV-07:10 1466.94 01-NOV-07:10 0.00 0.00 0.00 0.00 129.73 05-NOV-13:00 1048.89 12-NOV-06:55
December 1295.83 01-DEC-10:09 1036.02 12-DEC-08:09 1466.94 01-DEC-08:09 0.00 0.00 0.00 0.00 122.02 10-DEC-11:00 1373.02 20-DEC-01:00
                             
Annual Sum or Average             0.00 0.00 0.00 0.00        
Minimum of Months 1295.83   809.89   1466.94   0.00 0.00 0.00 0.00 91.96   235.62  
Maximum of Months 1295.83   1047.88   1466.94   0.00 0.00 0.00 0.00 705.55   1526.72  



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 232.27 02-JAN-10:09 405.10 02-JAN-08:09 1948.61 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 232.27 01-FEB-10:09 405.10 01-FEB-08:09 3897.21 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 232.27 01-MAR-10:09 405.10 01-MAR-08:09 7794.42 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 232.27 03-APR-09:09 405.10 03-APR-07:10 7794.42 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 232.27 01-MAY-09:09 405.10 01-MAY-07:10 3897.21 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 232.27 01-JUN-09:09 405.10 01-JUN-07:10 5845.82 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 232.27 03-JUL-09:09 405.10 03-JUL-07:10 7794.42 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 232.27 01-AUG-09:09 405.10 01-AUG-07:10 7794.42 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 232.27 01-SEP-09:09 405.10 01-SEP-07:10 3897.21 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 232.27 02-OCT-09:09 405.10 02-OCT-07:10 5845.82 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 232.27 01-NOV-09:09 405.10 01-NOV-07:10 5845.82 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 232.27 01-DEC-10:09 405.10 01-DEC-08:09 7794.42 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 232.27   405.10   1948.61   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 232.27   405.10   7794.42   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 5027.92 02-JAN-10:09 4375.82 02-JAN-08:09 94908.13 01-JAN-00:10 0.00 0.00 0.00 0.00 0.00 0.00
February 5027.92 01-FEB-10:09 4375.82 01-FEB-08:09 189816.26 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00 0.00
March 5027.92 01-MAR-10:09 4375.82 01-MAR-08:09 379632.52 31-MAR-23:10 0.00 0.00 0.00 0.00 0.00 0.00
April 5027.92 03-APR-09:09 4375.82 03-APR-07:10 379632.52 01-APR-00:10 0.00 0.00 0.00 0.00 0.00 0.00
May 5027.92 01-MAY-09:09 4375.82 01-MAY-07:10 189816.26 31-MAY-23:10 0.00 0.00 0.00 0.00 0.00 0.00
June 5027.92 01-JUN-09:09 4375.82 01-JUN-07:10 284724.39 30-JUN-23:10 0.00 0.00 0.00 0.00 0.00 0.00
July 5027.92 03-JUL-09:09 4375.82 03-JUL-07:10 379632.52 31-JUL-23:10 0.00 0.00 0.00 0.00 0.00 0.00
August 5027.92 01-AUG-09:09 4375.82 01-AUG-07:10 379632.52 01-AUG-00:10 0.00 0.00 0.00 0.00 0.00 0.00
September 5027.92 01-SEP-09:09 4375.82 01-SEP-07:10 189816.26 30-SEP-23:10 0.00 0.00 0.00 0.00 0.00 0.00
October 5027.92 02-OCT-09:09 4375.82 02-OCT-07:10 284724.39 31-OCT-23:10 0.00 0.00 0.00 0.00 0.00 0.00
November 5027.92 01-NOV-09:09 4375.82 01-NOV-07:10 284724.39 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00 0.00
December 5027.92 01-DEC-10:09 4375.82 01-DEC-08:09 379632.52 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average             0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 5027.92   4375.82   94908.13   0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 5027.92   4375.82   379632.52   0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: PeakSpaceGainsMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.79 16-JAN-15:00 1530.68 26-JAN-03:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 84.58 02-FEB-13:00 2190.64 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 182.80 26-MAR-14:00 1851.27 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 291.21 29-APR-17:02 1080.59 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 484.22 21-MAY-14:00 175.27 09-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 575.57 10-JUN-17:02 286.87 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 491.24 22-JUL-18:53 131.57 31-JUL-02:30
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 680.34 20-AUG-14:00 404.58 25-AUG-24:00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 653.27 09-SEP-17:02 386.49 05-SEP-03:00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 734.97 09-OCT-14:00 913.07 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90.63 05-NOV-12:52 1288.85 12-NOV-08:00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 88.41 10-DEC-14:52 2025.10 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 62.79   131.57  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 734.97   2190.64  



Table of Contents

Report: PeakSpaceGainsMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 178.26 16-JAN-15:00 2639.72 21-JAN-05:55
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 153.74 20-FEB-15:00 3785.34 05-FEB-07:55
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 382.63 05-MAR-12:53 3217.16 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 554.58 29-APR-17:02 1845.54 01-APR-21:00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 826.94 07-MAY-13:53 301.05 09-MAY-02:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1046.93 10-JUN-17:02 514.83 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 911.56 22-JUL-18:53 237.27 31-JUL-03:00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1237.37 20-AUG-14:00 741.21 25-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1188.51 09-SEP-17:02 666.89 05-SEP-03:04
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1329.00 09-OCT-14:00 1562.18 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 191.13 05-NOV-13:00 2223.51 12-NOV-06:55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 197.79 10-DEC-15:00 3462.36 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 153.74   237.27  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1329.00   3785.34  



Table of Contents

Report: PeakSpaceGainsMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP}
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 167.25 16-JAN-15:00 2638.30 21-JAN-06:00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 138.17 02-FEB-13:00 3478.42 05-FEB-08:00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 284.73 26-MAR-14:00 3399.01 20-MAR-22:00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 389.87 29-APR-17:02 2071.37 01-APR-17:55
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 706.33 07-MAY-13:55 624.68 14-MAY-12:00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 979.95 10-JUN-17:02 542.39 06-JUN-21:20
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 721.64 02-JUL-10:53 601.52 30-JUL-10:53
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1142.09 20-AUG-14:00 828.27 25-AUG-23:53
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1268.77 09-SEP-22:53 897.32 05-SEP-03:04
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 976.64 08-OCT-14:00 1493.44 29-OCT-02:00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 122.47 05-NOV-13:00 2335.15 12-NOV-06:55
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 116.08 10-DEC-15:00 3308.44 20-DEC-01:00
                       
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00        
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 116.08   542.39  
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1268.77   3478.42  



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 106684.89 23-JAN-04:03 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
February 109574.77 13-FEB-04:03 0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
March 110548.58 20-MAR-03:02 0.00 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
April 106601.17 10-APR-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
May 78461.54 30-MAY-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
June 79393.90 07-JUN-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
July 77787.42 18-JUL-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
August 80747.66 28-AUG-03:02 0.00 5173.36 80745.26 0.00 0.00 0.00 0.00 0.00 0.00
September 81548.92 05-SEP-03:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
October 97505.74 28-OCT-05:02 8976.13 8622.27 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
November 109129.27 24-NOV-04:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
December 109257.88 18-DEC-04:02 0.00 4311.14 67287.72 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 77787.42   0.00 3448.91 53830.18 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 110548.58   8976.13 8622.27 80745.26 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 88919.37 17-JAN-04:03 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
February 90725.95 21-FEB-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
March 91701.52 20-MAR-03:02 0.00 4646.04 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
April 87699.10 10-APR-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
May 84254.60 23-MAY-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
June 85752.99 07-JUN-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
July 80350.40 10-JUL-05:04 8061.19 7743.41 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
August 78632.04 14-AUG-05:03 9673.43 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00
September 85164.06 08-SEP-03:02 0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
October 90148.84 30-OCT-03:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
November 91445.26 27-NOV-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
December 92293.82 18-DEC-04:02 0.00 3871.70 40285.75 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 78632.04   0.00 3097.36 32228.60 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 92293.82   9673.43 9292.09 48342.90 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 78052.20 20-JAN-05:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
February 77514.36 11-FEB-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 80458.51 20-MAR-03:02 0.00 4646.04 48342.72 0.00 0.00 0.00 0.00 0.00 0.00
April 78916.00 19-APR-04:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
May 80602.55 01-MAY-03:02 0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
June 78502.25 01-JUN-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
July 74015.48 12-JUL-05:04 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
August 77602.18 01-AUG-05:04 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
September 78237.43 20-SEP-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 80219.90 17-OCT-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 77840.09 25-NOV-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
December 78680.80 14-DEC-05:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 74015.48   0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 80602.55   8061.19 7743.41 48342.72 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 74775.42 19-JAN-06:03 6448.95 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
February 76885.92 01-FEB-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
March 77094.14 01-MAR-06:02 8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
April 78292.76 24-APR-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
May 80152.36 01-MAY-03:02 0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
June 79249.67 06-JUN-03:02 0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
July 76312.70 01-JUL-03:02 0.00 3871.70 30214.20 0.00 0.00 0.00 0.00 0.00 0.00
August 77973.53 29-AUG-03:02 0.00 3097.36 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
September 77884.07 06-SEP-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
October 79028.84 10-OCT-03:02 0.00 3871.70 40285.60 0.00 0.00 0.00 0.00 0.00 0.00
November 77976.40 08-NOV-05:03 0.00 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
December 72963.56 14-DEC-06:03 6448.95 6194.72 32228.48 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 72963.56   0.00 3097.36 30214.20 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 80152.36   8061.19 7743.41 40285.60 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11905.46 02-JAN-06:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 18.95
February 9750.23 28-FEB-06:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 10.28
March 11152.39 27-MAR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 24.02
April 11604.08 07-APR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 13.09
May 12459.10 30-MAY-03:02 0.00 486.13 5058.48 0.00 0.00 0.00 0.00 0.00 0.55
June 12109.64 26-JUN-04:03 0.00 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 0.00
July 14172.33 23-JUL-13:02 404.87 238.90 3035.09 0.00 0.00 0.00 0.00 86.38 0.00
August 14203.20 21-AUG-03:02 0.00 583.36 6070.18 0.00 0.00 0.00 0.00 10.13 0.00
September 12573.31 06-SEP-03:02 0.00 486.13 5058.48 0.00 0.00 0.00 0.00 0.00 26.59
October 12129.56 23-OCT-04:53 0.00 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 1.25
November 11503.38 02-NOV-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 2.45
December 11324.74 12-DEC-06:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 19.37
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9750.23   0.00 238.90 3035.09 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14203.20   1012.16 972.26 6070.18 0.00 0.00 0.00 0.00 86.38 26.59



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 8255.62 01-JAN-09:53 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 134.32
February 7986.17 26-FEB-10:43 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 9.93
March 12168.71 26-MAR-09:02 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 27.48
April 16376.50 23-APR-09:13 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 31.28
May 16847.88 07-MAY-09:22 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 31.43 0.00
June 11043.27 29-JUN-05:02 652.28 626.56 3259.88 0.00 0.00 0.00 0.00 0.20 0.00
July 16752.61 23-JUL-09:02 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 8.54 0.00
August 15075.14 27-AUG-10:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 46.24 0.00
September 16821.18 24-SEP-09:32 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 17.78 0.00
October 16327.62 09-OCT-08:53 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 2.23
November 10432.73 11-NOV-09:23 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 28.50
December 5661.18 10-DEC-09:43 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 58.28
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5661.18   195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 16847.88   652.28 626.56 3259.88 0.00 0.00 0.00 0.00 46.24 134.32



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 19949.38 01-JAN-13:52 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 16.42
February 19818.23 26-FEB-14:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 28.45
March 19176.97 26-MAR-13:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 56.76 0.00
April 13692.53 29-APR-05:02 1012.19 972.28 5058.56 0.00 0.00 0.00 0.00 0.00 4.97
May 14347.00 01-MAY-05:02 1012.19 972.28 5058.56 0.00 0.00 0.00 0.00 2.28 0.00
June 14419.25 26-JUN-04:03 0.00 777.83 4046.85 0.00 0.00 0.00 0.00 0.00 0.00
July 15979.21 23-JUL-13:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 86.55 0.00
August 18809.56 27-AUG-13:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 135.60 0.00
September 19654.20 03-SEP-15:12 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 135.87 0.00
October 19856.92 08-OCT-11:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 145.01 0.00
November 21006.21 11-NOV-13:22 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 63.05
December 19838.54 10-DEC-13:42 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 8.76
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13692.53   0.00 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21006.21   1012.19 972.28 5058.56 0.00 0.00 0.00 0.00 145.01 63.05



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 16714.11 16-JAN-15:53 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 18.17
February 19228.16 26-FEB-15:23 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 13.77
March 19527.38 26-MAR-14:23 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.67 0.00
April 21178.71 23-APR-16:32 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 3.66 0.00
May 21240.88 28-MAY-16:21 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 80.84 0.00
June 20992.23 11-JUN-16:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 55.85 0.00
July 20719.03 16-JUL-15:52 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 113.38 0.00
August 20763.98 06-AUG-16:22 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 31.08
September 22571.25 03-SEP-15:51 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 80.93 0.00
October 21487.10 22-OCT-15:52 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 15.80 0.00
November 21584.90 11-NOV-15:22 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 20.03
December 19820.40 10-DEC-15:42 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 3.68 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 16714.11   260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22571.25   456.59 269.43 3422.85 0.00 0.00 0.00 0.00 113.38 31.08



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5208.97 31-JAN-14:40 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 23.12 0.00
February 5437.44 28-FEB-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 24.57 0.00
March 9249.26 27-MAR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 54.09
April 10168.52 29-APR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 12.59
May 14098.03 29-MAY-16:01 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 213.63 0.00
June 14463.46 25-JUN-16:31 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 112.83 0.00
July 13185.16 03-JUL-03:02 0.00 486.13 5058.48 0.00 0.00 0.00 0.00 153.41 0.00
August 13192.26 21-AUG-03:02 0.00 583.36 6070.18 0.00 0.00 0.00 0.00 12.78 0.00
September 11478.23 11-SEP-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 9.99 0.00
October 14273.06 08-OCT-14:52 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 485.06 0.00
November 10587.25 01-NOV-05:03 809.73 777.81 4046.79 0.00 0.00 0.00 0.00 0.00 10.25
December 10121.05 15-DEC-06:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 50.60
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5208.97   0.00 358.36 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14463.46   2010.79 1075.02 6070.18 0.00 0.00 0.00 0.00 485.06 54.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6396.73 19-JAN-10:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 15.86
February 6835.02 27-FEB-10:00 1239.33 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 4.26
March 10696.95 26-MAR-09:43 195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 64.17
April 17342.48 23-APR-09:32 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 0.00 75.00
May 18026.50 29-MAY-08:42 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 0.00 10.08
June 16781.62 11-JUN-08:32 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 23.05
July 16754.31 30-JUL-09:02 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 108.61 0.00
August 16631.63 27-AUG-10:23 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 97.36 0.00
September 16594.00 10-SEP-09:42 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 274.19 0.00
October 16009.14 08-OCT-14:52 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 326.44 0.00
November 9791.74 02-NOV-05:02 652.28 626.56 3259.88 0.00 0.00 0.00 0.00 0.00 3.65
December 5974.59 15-DEC-06:02 652.28 626.56 3259.88 0.00 0.00 0.00 0.00 0.00 33.67
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5974.59   195.68 115.47 1466.95 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18026.50   1239.33 692.79 3259.88 0.00 0.00 0.00 0.00 326.44 75.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 20670.25 01-JAN-14:11 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 0.00 98.87
February 19317.52 26-FEB-13:42 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 75.62
March 18022.03 26-MAR-13:43 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 131.64 0.00
April 13865.96 23-APR-15:32 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 98.13 0.00
May 17008.33 29-MAY-16:01 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 215.00 0.00
June 17435.51 25-JUN-15:51 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 95.25 0.00
July 15255.13 20-JUL-03:02 0.00 486.14 5058.56 0.00 0.00 0.00 0.00 16.13 0.00
August 17675.59 27-AUG-13:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 317.92 0.00
September 18443.03 17-SEP-14:22 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 273.91 0.00
October 19513.53 08-OCT-14:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 296.58 0.00
November 19448.05 05-NOV-13:32 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 48.87
December 20198.37 10-DEC-12:42 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 75.55
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 13865.96   0.00 238.91 3035.14 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20670.25   708.53 486.14 5311.49 0.00 0.00 0.00 0.00 317.92 98.87



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 13871.29 01-JAN-15:32 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 34.90
February 17306.88 26-FEB-17:03 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 75.25
March 12330.72 27-MAR-05:02 652.28 626.56 3259.86 0.00 0.00 0.00 0.00 0.00 38.29
April 18710.30 23-APR-16:52 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 45.73
May 19114.55 29-MAY-16:01 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 95.05 0.00
June 19141.24 11-JUN-17:11 0.00 269.43 3422.85 0.00 0.00 0.00 0.00 112.79 0.00
July 16408.38 16-JUL-15:52 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 264.12 0.00
August 15568.64 21-AUG-03:02 0.00 375.94 3911.83 0.00 0.00 0.00 0.00 12.21 0.00
September 18481.81 17-SEP-15:42 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 243.53 0.00
October 18334.73 08-OCT-16:12 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 214.48 0.00
November 12341.82 05-NOV-15:32 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 7.48 0.00
December 17173.28 10-DEC-15:22 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 20.23 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 12330.72   0.00 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 19141.24   652.28 626.56 3911.83 0.00 0.00 0.00 0.00 264.12 75.25



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 5478.47 31-JAN-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 25.20 0.00
February 5753.84 22-FEB-14:30 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 13.81 0.00
March 8266.40 27-MAR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 68.37
April 11860.74 29-APR-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 21.23
May 16997.61 29-MAY-16:01 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 229.79 0.00
June 17184.13 25-JUN-16:31 708.51 418.08 5311.41 0.00 0.00 0.00 0.00 125.07 0.00
July 16506.11 02-JUL-17:03 0.00 238.90 3035.09 0.00 0.00 0.00 0.00 259.49 0.00
August 16294.45 27-AUG-16:12 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 625.09 0.00
September 16408.81 17-SEP-15:42 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 554.18 0.00
October 16909.88 08-OCT-14:52 607.30 358.36 4552.64 0.00 0.00 0.00 0.00 525.96 0.00
November 12237.82 02-NOV-05:02 1012.16 972.26 5058.48 0.00 0.00 0.00 0.00 0.00 9.07
December 6360.99 15-DEC-15:00 2010.79 1075.02 2276.32 0.00 0.00 0.00 0.00 64.02 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 5478.47   0.00 238.90 2276.32 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 17184.13   2010.79 1075.02 5311.41 0.00 0.00 0.00 0.00 625.09 68.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6126.19 19-JAN-10:20 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 11.53
February 6651.82 27-FEB-10:30 1295.83 692.79 1466.95 0.00 0.00 0.00 0.00 0.00 16.66
March 9620.83 27-MAR-05:02 652.28 626.56 3259.88 0.00 0.00 0.00 0.00 0.00 46.07
April 17028.12 23-APR-11:02 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 9.62
May 18545.74 29-MAY-08:42 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 0.00 16.23
June 17141.03 11-JUN-08:32 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 0.00 35.48
July 17923.63 23-JUL-09:02 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 18.79 0.00
August 17072.57 27-AUG-10:13 260.91 153.96 1955.93 0.00 0.00 0.00 0.00 118.50 0.00
September 17116.62 10-SEP-09:42 326.14 192.45 2444.91 0.00 0.00 0.00 0.00 326.42 0.00
October 16827.65 08-OCT-14:52 391.37 230.94 2933.89 0.00 0.00 0.00 0.00 358.47 0.00
November 9879.80 02-NOV-05:02 652.28 626.56 3259.88 0.00 0.00 0.00 0.00 0.00 4.86
December 4897.81 16-DEC-10:10 409.21 230.93 814.97 0.00 0.00 0.00 0.00 1.12 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 4897.81   260.91 153.96 814.97 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 18545.74   1295.83 692.79 3259.88 0.00 0.00 0.00 0.00 358.47 46.07



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 22582.53 01-JAN-15:02 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 162.96
February 21361.69 26-FEB-13:52 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 0.00 89.53
March 17332.89 05-MAR-13:33 303.66 179.18 2276.35 0.00 0.00 0.00 0.00 57.89 0.00
April 18208.64 23-APR-15:01 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 171.20 0.00
May 20140.95 29-MAY-16:01 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 234.97 0.00
June 20181.35 25-JUN-15:51 708.53 418.09 5311.49 0.00 0.00 0.00 0.00 106.56 0.00
July 18875.07 23-JUL-13:02 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 243.57 0.00
August 19872.62 27-AUG-12:53 404.87 238.91 3035.14 0.00 0.00 0.00 0.00 364.22 0.00
September 20821.25 17-SEP-14:22 506.09 298.64 3793.92 0.00 0.00 0.00 0.00 306.16 0.00
October 22252.80 08-OCT-14:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 308.25 0.00
November 22413.15 11-NOV-14:02 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 217.82
December 22516.71 10-DEC-12:52 607.31 358.36 4552.71 0.00 0.00 0.00 0.00 0.00 98.36
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 17332.89   303.66 179.18 2276.35 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 22582.53   708.53 418.09 5311.49 0.00 0.00 0.00 0.00 364.22 217.82



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9251.06 01-JAN-17:03 260.91 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 59.79
February 15223.43 26-FEB-17:12 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 96.61
March 13101.05 27-MAR-05:02 652.28 626.56 3259.86 0.00 0.00 0.00 0.00 0.00 46.65
April 19355.22 23-APR-17:01 0.00 269.43 3422.85 0.00 0.00 0.00 0.00 0.00 38.17
May 21253.96 29-MAY-16:01 456.59 269.43 3422.85 0.00 0.00 0.00 0.00 103.63 0.00
June 21132.71 11-JUN-17:11 0.00 269.43 3422.85 0.00 0.00 0.00 0.00 125.88 0.00
July 19132.36 30-JUL-16:52 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 14.17
August 17648.68 27-AUG-16:12 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 412.18 0.00
September 20236.31 17-SEP-15:42 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 272.37 0.00
October 20213.05 08-OCT-16:12 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 226.77 0.00
November 17809.92 11-NOV-15:22 326.14 192.45 2444.89 0.00 0.00 0.00 0.00 0.00 32.23
December 18918.04 10-DEC-16:12 391.37 230.94 2933.87 0.00 0.00 0.00 0.00 0.00 35.64
                       
Annual Sum or Average           0.00 0.00 0.00 0.00    
Minimum of Months 9251.06   0.00 153.96 1955.92 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 21253.96   652.28 626.56 3422.85 0.00 0.00 0.00 0.00 412.18 96.61



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 11952.62 02-JAN-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 53.75
February 8690.61 27-FEB-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 9503.76 27-MAR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 57.96
April 8564.63 24-APR-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 6.04
May 13943.61 22-MAY-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.36 0.00
June 9890.61 12-JUN-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.51
July 13585.21 24-JUL-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 2.95 0.00
August 13830.48 28-AUG-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.99
September 13759.94 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 54.91
October 14017.82 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 61.37
November 9779.61 06-NOV-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 11.68
December 9113.80 11-DEC-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 44.84
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 8564.63   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 14017.82   0.00 0.00 0.00 0.00 0.00 0.00 0.00 19.36 61.37



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 6891.05 02-JAN-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93.60
February 5175.24 24-FEB-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 5778.22 01-MAR-06:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 233.49
April 6430.65 28-APR-15:20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 198.65 0.00
May 12706.03 22-MAY-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 30.95 0.00
June 8560.51 23-JUN-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 4.35 0.00
July 8011.97 31-JUL-05:13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 25.47
August 8964.87 28-AUG-05:02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.85 0.00
September 8556.71 05-SEP-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 93.73
October 9605.40 10-OCT-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 111.55
November 6676.58 04-NOV-05:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 45.34
December 5782.50 15-DEC-06:15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 90.88
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 5175.24   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 12706.03   0.00 0.00 0.00 0.00 0.00 0.00 0.00 198.65 233.49



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY [] ZONE LIGHTS TOTAL HEATING ENERGY [] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W]
January 9748.93 19-JAN-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 36.09
February 11609.51 24-FEB-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.23
March 12987.63 06-MAR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.08 0.00
April 18175.10 28-APR-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 227.16 0.00
May 19299.57 10-MAY-14:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 33.90 0.00
June 20243.21 28-JUN-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 58.60 0.00
July 20443.99 07-JUL-14:30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 112.49 0.00
August 19533.00 10-AUG-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 124.91 0.00
September 17594.43 01-SEP-15:10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 133.14 0.00
October 16472.91 05-OCT-15:40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 92.92 0.00
November 13018.03 02-NOV-14:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 77.30 0.00
December 11020.87 15-DEC-15:00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 63.96 0.00
                       
Annual Sum or Average     0.00 0.00 0.00 0.00 0.00 0.00 0.00    
Minimum of Months 9748.93   0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 20443.99   0.00 0.00 0.00 0.00 0.00 0.00 0.00 227.16 36.09



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 2052.06 01-JAN-17:27 35.07 67.52 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
February 4115.35 26-FEB-17:42 46.77 90.03 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
March 7197.45 31-MAR-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7906.36 16-APR-18:10 0.00 112.53 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3491.61 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5345.11 30-JUN-23:57 0.00 67.52 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 7222.33 31-JUL-23:57 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7789.06 06-AUG-18:00 0.00 90.03 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
September 3520.03 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5366.73 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5953.60 06-NOV-17:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7830.98 10-DEC-16:54 58.46 112.53 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 2052.06   0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7906.36   222.14 405.10 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1855.74 18-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3774.27 26-FEB-17:54 58.46 112.53 19486.06 0.00 0.00 0.00 0.00 0.00 0.00
March 6775.73 31-MAR-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7457.11 16-APR-18:10 0.00 112.53 38972.11 0.00 0.00 0.00 0.00 0.00 0.00
May 3304.87 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5202.21 30-JUN-23:57 0.00 67.52 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 6956.68 31-JUL-23:57 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7262.04 06-AUG-18:10 0.00 45.01 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
September 3312.39 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 5025.17 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5638.16 06-NOV-17:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7368.55 15-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1855.74   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7457.11   222.14 405.10 38972.11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 1905.45 19-JAN-17:00 222.14 405.10 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
February 3796.23 26-FEB-17:42 46.77 90.03 15588.84 0.00 0.00 0.00 0.00 0.00 0.00
March 6671.83 31-MAR-24:00 0.00 22.51 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
April 7640.94 23-APR-18:08 0.00 90.03 31177.69 0.00 0.00 0.00 0.00 0.00 0.00
May 3268.37 31-MAY-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
June 5231.75 30-JUN-23:57 0.00 67.52 17537.45 0.00 0.00 0.00 0.00 0.00 0.00
July 6940.03 31-JUL-23:57 0.00 67.52 23383.27 0.00 0.00 0.00 0.00 0.00 0.00
August 7506.99 06-AUG-17:40 0.00 135.04 46766.53 0.00 0.00 0.00 0.00 0.00 0.00
September 3354.81 30-SEP-24:00 0.00 22.51 3897.21 0.00 0.00 0.00 0.00 0.00 0.00
October 4967.20 31-OCT-24:00 0.00 22.51 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
November 5697.61 06-NOV-17:00 222.14 405.10 5845.82 0.00 0.00 0.00 0.00 0.00 0.00
December 7431.07 15-DEC-17:00 222.14 405.10 7794.42 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 1905.45   0.00 22.51 1948.61 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 7640.94   222.14 405.10 46766.53 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SpaceGainComponentsAtCoolingPeakMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY []
January 92998.12 02-JAN-17:00 4808.68 4375.82 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
February 183714.69 27-FEB-17:00 4808.68 4375.82 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
March 358582.23 31-MAR-24:00 0.00 243.11 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
April 367523.33 28-APR-21:02 1518.53 2917.33 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00
May 175679.32 31-MAY-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
June 267329.23 30-JUN-23:57 0.00 729.33 854173.17 0.00 0.00 0.00 0.00 0.00 0.00
July 359638.50 31-JUL-23:53 0.00 729.33 1138897.57 0.00 0.00 0.00 0.00 0.00 0.00
August 371126.47 09-AUG-21:13 1518.53 2917.33 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00
September 176634.57 30-SEP-24:00 0.00 243.11 189816.26 0.00 0.00 0.00 0.00 0.00 0.00
October 268703.72 31-OCT-24:00 0.00 243.11 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
November 276635.21 06-NOV-17:00 4808.68 4375.82 284724.39 0.00 0.00 0.00 0.00 0.00 0.00
December 368064.53 26-DEC-17:00 4808.68 4375.82 379632.52 0.00 0.00 0.00 0.00 0.00 0.00
                       
Annual Sum or Average           0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 92998.12   0.00 243.11 94908.13 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 371126.47   4808.68 4375.82 2277795.13 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: EnergyConsumptionElectricityNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ELECTRICITY:FACILITY [J] ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} NATURALGAS:FACILITY [J] NATURALGAS:FACILITY {Maximum} [W] NATURALGAS:FACILITY {TIMESTAMP}
January 0.169750E+13 1345079.74 31-JAN-16:19 0.725824E+11 432689.59 05-JAN-07:10
February 0.196418E+13 1515298.59 28-FEB-16:10 0.587335E+11 426078.39 06-FEB-07:10
March 0.264295E+13 1678944.96 06-MAR-16:19 0.639663E+11 346886.28 09-MAR-07:10
April 0.306537E+13 1901572.29 28-APR-15:09 0.494398E+11 102122.93 18-APR-14:30
May 0.220616E+13 1438105.25 17-MAY-15:50 0.493999E+11 66573.75 02-MAY-11:50
June 0.259850E+13 1608137.44 28-JUN-15:20 0.465482E+11 62646.36 05-JUN-11:30
July 0.306872E+13 1772619.75 18-JUL-15:20 0.446472E+11 60186.17 06-JUL-11:50
August 0.355094E+13 1925340.49 03-AUG-15:20 0.476434E+11 61272.35 28-AUG-11:30
September 0.210608E+13 1440386.78 06-SEP-15:30 0.456884E+11 64604.33 29-SEP-11:30
October 0.251466E+13 1591812.26 06-OCT-15:00 0.494216E+11 67824.40 26-OCT-11:50
November 0.261891E+13 1690341.90 03-NOV-15:00 0.509044E+11 108639.75 27-NOV-14:20
December 0.296660E+13 1834878.73 12-DEC-16:30 0.649260E+11 495802.30 21-DEC-07:10
             
Annual Sum or Average 0.310006E+14     0.643901E+12    
Minimum of Months 0.169750E+13 1345079.74   0.446472E+11 60186.17  
Maximum of Months 0.355094E+13 1925340.49   0.725824E+11 495802.30  



Table of Contents

Report: EndUseEnergyConsumptionElectricityMonthly

For: Meter

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY [J] EXTERIORLIGHTS:ELECTRICITY [J] INTERIOREQUIPMENT:ELECTRICITY [J] EXTERIOREQUIPMENT:ELECTRICITY [J] FANS:ELECTRICITY [J] PUMPS:ELECTRICITY [J] HEATING:ELECTRICITY [J] COOLING:ELECTRICITY [J] HEATREJECTION:ELECTRICITY [J] HUMIDIFIER:ELECTRICITY [J] HEATRECOVERY:ELECTRICITY [J] WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 0.230309E+12 0.445478E+11 0.811612E+12 0.162550E+12 0.175919E+12 0.463976E+11 0.00 0.150440E+12 0.727784E+11 0.502569E+09 0.244205E+10 0.00 0.00
February 0.208114E+12 0.379910E+11 0.102011E+13 0.146826E+12 0.163671E+12 0.551294E+11 0.00 0.230157E+12 0.995200E+11 0.351114E+09 0.231275E+10 0.00 0.00
March 0.246449E+12 0.386805E+11 0.146267E+13 0.162740E+12 0.191131E+12 0.664477E+11 0.00 0.344906E+12 0.126810E+12 0.227752E+09 0.289038E+10 0.00 0.00
April 0.219690E+12 0.341555E+11 0.170311E+13 0.157288E+12 0.201569E+12 0.957589E+11 0.00 0.498945E+12 0.150544E+12 62952719.63 0.424323E+10 0.00 0.00
May 0.236263E+12 0.323392E+11 0.820521E+12 0.162644E+12 0.239326E+12 0.112129E+12 0.00 0.401429E+12 0.193955E+12 0.00 0.755798E+10 0.00 0.00
June 0.234810E+12 0.296873E+11 0.110677E+13 0.157466E+12 0.240092E+12 0.119605E+12 0.00 0.506234E+12 0.196270E+12 0.00 0.755798E+10 0.00 0.00
July 0.220025E+12 0.315268E+11 0.143888E+13 0.162465E+12 0.238938E+12 0.128437E+12 0.00 0.630543E+12 0.210730E+12 0.00 0.717402E+10 0.00 0.00
August 0.245403E+12 0.339189E+11 0.177780E+13 0.162740E+12 0.251643E+12 0.133354E+12 0.00 0.727707E+12 0.210514E+12 0.00 0.786111E+10 0.00 0.00
September 0.219913E+12 0.360511E+11 0.784732E+12 0.157287E+12 0.220528E+12 0.107567E+12 0.00 0.383003E+12 0.189823E+12 0.00 0.717402E+10 0.00 0.00
October 0.229023E+12 0.406889E+11 0.112899E+13 0.162550E+12 0.218979E+12 0.107033E+12 0.00 0.442420E+12 0.179253E+12 53688292.87 0.566287E+10 0.00 0.00
November 0.227547E+12 0.422343E+11 0.140306E+13 0.157361E+12 0.187993E+12 0.797311E+11 0.00 0.380846E+12 0.137432E+12 80917418.96 0.262430E+10 0.00 0.00
December 0.223432E+12 0.452925E+11 0.175516E+13 0.162466E+12 0.180798E+12 0.623430E+11 0.00 0.405186E+12 0.128862E+12 0.257510E+09 0.280281E+10 0.00 0.00
                           
Annual Sum or Average 0.274098E+13 0.447114E+12 0.152134E+14 0.191438E+13 0.251059E+13 0.111393E+13 0.00 0.510182E+13 0.189649E+13 0.153650E+10 0.603035E+11 0.00 0.00
Minimum of Months 0.208114E+12 0.296873E+11 0.784732E+12 0.146826E+12 0.163671E+12 0.463976E+11 0.00 0.150440E+12 0.727784E+11 0.00 0.231275E+10 0.00 0.00
Maximum of Months 0.246449E+12 0.452925E+11 0.177780E+13 0.162740E+12 0.251643E+12 0.133354E+12 0.00 0.727707E+12 0.210730E+12 0.502569E+09 0.786111E+10 0.00 0.00



Table of Contents

Report: EndUseEnergyConsumptionNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS [J] COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS [J] COGENERATION:NATURALGAS [] HUMIDIFIER:NATURALGAS []
January 0.00 0.00 0.179037E+11 0.00 0.546788E+11 0.00 0.00
February 0.00 0.00 0.942274E+10 0.00 0.493107E+11 0.00 0.00
March 0.00 0.00 0.852877E+10 0.00 0.554375E+11 0.00 0.00
April 0.00 0.00 0.342146E+09 0.00 0.490977E+11 0.00 0.00
May 0.00 0.00 0.00 0.00 0.493999E+11 0.00 0.00
June 0.00 0.00 0.00 0.00 0.465482E+11 0.00 0.00
July 0.00 0.00 0.00 0.00 0.446472E+11 0.00 0.00
August 0.00 0.00 0.00 0.00 0.476434E+11 0.00 0.00
September 0.00 0.00 0.00 0.00 0.456884E+11 0.00 0.00
October 0.00 0.00 11781611.69 0.00 0.494098E+11 0.00 0.00
November 0.00 0.00 0.294006E+09 0.00 0.506104E+11 0.00 0.00
December 0.00 0.00 0.120646E+11 0.00 0.528614E+11 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.485677E+11 0.00 0.595333E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.446472E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.179037E+11 0.00 0.554375E+11 0.00 0.00



Table of Contents

Report: PeakEnergyEndUseElectricityPart1Monthly

For: Meter

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

INTERIORLIGHTS:ELECTRICITY {Maximum} [W] INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} FANS:ELECTRICITY {Maximum} [W] FANS:ELECTRICITY {TIMESTAMP} PUMPS:ELECTRICITY {Maximum} [W] PUMPS:ELECTRICITY {TIMESTAMP} HEATING:ELECTRICITY {Maximum} [W] HEATING:ELECTRICITY {TIMESTAMP}
January 251691.20 31-JAN-08:09 37611.08 01-JAN-06:10 439129.89 02-JAN-08:09 117199.38 31-JAN-08:20 151013.44 02-JAN-13:39 72022.64 19-JAN-15:20 0.00 01-JAN-00:10
February 253346.39 01-FEB-08:09 37611.08 01-FEB-06:10 557421.28 01-FEB-08:09 117200.32 01-FEB-08:20 163054.74 28-FEB-16:40 72381.17 27-FEB-11:00 0.00 01-FEB-00:10
March 250193.82 27-MAR-07:10 37611.08 01-MAR-06:10 675712.68 01-MAR-08:09 117198.53 27-MAR-07:19 190186.15 24-MAR-14:50 70038.08 07-MAR-14:50 0.00 01-MAR-00:10
April 251535.70 14-APR-07:10 37611.08 01-APR-05:10 794004.08 03-APR-07:10 117199.29 14-APR-07:19 261005.24 18-APR-14:39 70385.95 19-APR-13:00 0.00 01-APR-00:10
May 241221.90 23-MAY-07:19 37611.08 01-MAY-05:10 439129.89 01-MAY-07:10 117193.42 23-MAY-07:30 202263.60 04-MAY-15:00 70211.44 16-MAY-13:39 0.00 01-MAY-00:10
June 235832.96 08-JUN-07:10 37611.08 01-JUN-05:10 557421.28 01-JUN-07:10 117190.36 08-JUN-07:19 202723.19 13-JUN-15:30 70354.74 13-JUN-15:00 0.00 01-JUN-00:10
July 238094.86 14-JUL-07:10 37611.08 01-JUL-05:10 675712.68 03-JUL-07:10 117191.64 14-JUL-07:19 202061.93 06-JUL-14:50 70380.47 12-JUL-15:30 0.00 01-JUL-00:10
August 242522.88 21-AUG-07:10 37611.08 01-AUG-05:10 794004.08 01-AUG-07:10 117194.16 21-AUG-07:19 207541.00 29-AUG-15:50 71132.90 30-AUG-13:00 0.00 01-AUG-00:10
September 250168.11 26-SEP-07:10 37611.08 01-SEP-05:10 439129.89 01-SEP-07:10 117198.51 26-SEP-07:19 203884.10 06-SEP-15:39 71016.10 01-SEP-14:20 0.00 01-SEP-00:10
October 255624.72 25-OCT-07:10 37611.08 01-OCT-05:10 557421.28 02-OCT-07:10 117201.62 25-OCT-07:19 189733.25 12-OCT-15:39 73611.76 11-OCT-14:30 0.00 01-OCT-00:10
November 253389.50 21-NOV-16:00 37611.08 01-NOV-05:10 675712.68 01-NOV-07:10 117200.24 01-NOV-07:19 168707.40 07-NOV-16:49 73100.78 02-NOV-13:09 0.00 01-NOV-00:10
December 255205.66 12-DEC-08:09 37611.08 01-DEC-06:10 794004.08 01-DEC-08:09 117201.38 12-DEC-08:20 164332.06 14-DEC-16:49 72643.67 14-DEC-13:30 0.00 01-DEC-00:10
                             
Annual Sum or Average                            
Minimum of Months 235832.96   37611.08   439129.89   117190.36   151013.44   70038.08   0.00  
Maximum of Months 255624.72   37611.08   794004.08   117201.62   261005.24   73611.76   0.00  



Table of Contents

Report: PeakEnergyEndUseElectricityPart2Monthly

For: Meter

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING:ELECTRICITY {Maximum} [W] COOLING:ELECTRICITY {TIMESTAMP} HEATREJECTION:ELECTRICITY {Maximum} [W] HEATREJECTION:ELECTRICITY {TIMESTAMP} HUMIDIFIER:ELECTRICITY {Maximum} [W] HUMIDIFIER:ELECTRICITY {TIMESTAMP} HEATRECOVERY:ELECTRICITY {Maximum} [W] HEATRECOVERY:ELECTRICITY {TIMESTAMP} WATERSYSTEMS:ELECTRICITY [] COGENERATION:ELECTRICITY []
January 292652.70 19-JAN-10:50 93886.47 18-JAN-14:00 4027.77 21-JAN-12:00 5613.48 02-JAN-10:50 0.00 0.00
February 335464.94 24-FEB-13:09 93886.47 02-FEB-13:20 4043.93 16-FEB-21:00 5613.48 01-FEB-13:09 0.00 0.00
March 363761.01 30-MAR-12:50 93886.47 06-MAR-09:50 4283.79 08-MAR-21:00 5613.48 04-MAR-16:10 0.00 0.00
April 429723.76 28-APR-13:00 93886.47 14-APR-10:20 3733.87 11-APR-16:10 5613.48 01-APR-06:10 0.00 0.00
May 323490.16 24-MAY-12:50 93886.47 01-MAY-06:40 0.00 01-MAY-00:10 5613.48 01-MAY-06:10 0.00 0.00
June 370001.79 28-JUN-14:30 93886.47 01-JUN-06:30 0.00 01-JUN-00:10 5613.48 01-JUN-06:10 0.00 0.00
July 418240.31 18-JUL-14:00 93886.47 01-JUL-07:10 0.00 01-JUL-00:10 5613.48 01-JUL-06:10 0.00 0.00
August 443337.10 03-AUG-15:30 93886.47 01-AUG-07:40 0.00 01-AUG-00:10 5613.48 01-AUG-06:10 0.00 0.00
September 328692.50 18-SEP-13:00 93886.47 01-SEP-06:10 0.00 01-SEP-00:10 5613.48 01-SEP-06:10 0.00 0.00
October 388160.81 24-OCT-13:30 93886.47 02-OCT-09:50 2510.90 27-OCT-16:10 5613.48 02-OCT-09:39 0.00 0.00
November 408552.39 02-NOV-13:09 93886.47 01-NOV-08:20 2664.89 22-NOV-18:10 5613.48 01-NOV-06:10 0.00 0.00
December 424241.47 14-DEC-13:30 93886.47 11-DEC-10:20 3466.80 20-DEC-20:00 5613.48 02-DEC-13:30 0.00 0.00
                     
Annual Sum or Average                 0.00 0.00
Minimum of Months 292652.70   93886.47   0.00   5613.48   0.00 0.00
Maximum of Months 443337.10   93886.47   4283.79   5613.48   0.00 0.00



Table of Contents

Report: ElectricComponentsOfPeakDemandMonthly

For: Meter

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ELECTRICITY:FACILITY {Maximum} [W] ELECTRICITY:FACILITY {TIMESTAMP} INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] FANS:ELECTRICITY {AT MAX/MIN} [W] PUMPS:ELECTRICITY {AT MAX/MIN} [W] HEATING:ELECTRICITY {AT MAX/MIN} [W] COOLING:ELECTRICITY {AT MAX/MIN} [W] HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W]
January 1345079.74 31-JAN-16:19 234435.00 439129.89 0.00 83146.17 141319.63 69642.79 0.00 277906.31 93886.47
February 1515298.59 28-FEB-16:10 234435.00 557421.28 0.00 83146.17 157497.68 69838.04 0.00 313460.46 93886.47
March 1678944.96 06-MAR-16:19 234435.00 675712.68 0.00 83146.17 168028.38 69528.22 0.00 348594.55 93886.47
April 1901572.29 28-APR-15:09 234435.00 794004.08 0.00 83146.17 199677.44 69841.90 0.00 420967.75 93886.47
May 1438105.25 17-MAY-15:50 234435.00 439129.89 0.00 83146.17 197371.06 70210.26 0.00 314312.92 93886.47
June 1608137.44 28-JUN-15:20 234435.00 557421.28 0.00 83146.17 198039.28 70104.54 0.00 365491.21 93886.47
July 1772619.75 18-JUL-15:20 234435.00 675712.68 0.00 83146.17 192274.85 70345.78 0.00 417205.31 93886.47
August 1925340.49 03-AUG-15:20 234435.00 794004.08 0.00 83146.17 200875.52 70372.68 0.00 443007.08 93886.47
September 1440386.78 06-SEP-15:30 234435.00 439129.89 0.00 83146.17 199517.21 70175.62 0.00 314482.93 93886.47
October 1591812.26 06-OCT-15:00 234435.00 557421.28 0.00 83146.17 181965.06 70479.63 0.00 364865.16 93886.47
November 1690341.90 03-NOV-15:00 234435.00 675712.68 0.00 83146.17 156403.94 70076.68 0.00 371067.47 93886.47
December 1834878.73 12-DEC-16:30 239586.09 794004.08 0.00 83148.47 156386.94 69959.91 0.00 392293.29 93886.47
                       
Annual Sum or Average                      
Minimum of Months 1345079.74   234435.00 439129.89 0.00 83146.17 141319.63 69528.22 0.00 277906.31 93886.47
Maximum of Months 1925340.49   239586.09 794004.08 0.00 83148.47 200875.52 70479.63 0.00 443007.08 93886.47



Table of Contents

Report: PeakEnergyEndUseNaturalGasMonthly

For: Meter

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

INTERIOREQUIPMENT:NATURALGAS [] EXTERIOREQUIPMENT:NATURALGAS [] HEATING:NATURALGAS {Maximum} [W] HEATING:NATURALGAS {TIMESTAMP} COOLING:NATURALGAS [] WATERSYSTEMS:NATURALGAS {Maximum} [W] WATERSYSTEMS:NATURALGAS {TIMESTAMP} COGENERATION:NATURALGAS []
January 0.00 0.00 404211.18 05-JAN-07:10 0.00 73397.75 25-JAN-12:20 0.00
February 0.00 0.00 397592.43 06-FEB-07:10 0.00 73298.50 02-FEB-12:50 0.00
March 0.00 0.00 341190.41 09-MAR-07:10 0.00 72048.76 06-MAR-12:00 0.00
April 0.00 0.00 70880.51 18-APR-14:30 0.00 69029.66 04-APR-11:20 0.00
May 0.00 0.00 0.00 01-MAY-00:10 0.00 66573.75 02-MAY-11:50 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 62646.36 05-JUN-11:30 0.00
July 0.00 0.00 0.00 01-JUL-00:10 0.00 60186.17 06-JUL-11:50 0.00
August 0.00 0.00 0.00 01-AUG-00:10 0.00 61272.35 28-AUG-11:30 0.00
September 0.00 0.00 0.00 01-SEP-00:10 0.00 64604.33 29-SEP-11:30 0.00
October 0.00 0.00 1704.83 28-OCT-06:40 0.00 67824.40 26-OCT-11:50 0.00
November 0.00 0.00 68819.76 27-NOV-14:20 0.00 71170.87 29-NOV-12:50 0.00
December 0.00 0.00 467400.92 21-DEC-07:10 0.00 72673.47 28-DEC-12:30 0.00
                 
Annual Sum or Average 0.00 0.00     0.00     0.00
Minimum of Months 0.00 0.00 0.00   0.00 60186.17   0.00
Maximum of Months 0.00 0.00 467400.92   0.00 73397.75   0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 8.33 26.42 0.50 26.47
February 0.00 0.00 0.00 0.00 5.50 26.43 0.67 26.53
March 0.00 0.00 0.00 0.00 2.67 26.13 0.00 26.13
April 0.00 0.00 0.00 0.00 2.33 25.95 0.00 25.95
May 0.00 0.00 0.00 0.00 4.33 26.26 0.17 26.20
June 0.00 0.00 0.00 0.00 3.33 26.11 0.00 26.11
July 0.00 0.00 0.00 0.00 6.83 26.43 0.17 26.39
August 0.00 0.00 0.00 0.00 6.83 26.05 0.17 26.08
September 0.00 0.00 0.00 0.00 7.83 26.61 0.00 26.61
October 0.00 0.00 0.00 0.00 9.50 26.61 0.17 26.62
November 0.00 0.00 0.00 0.00 8.83 26.75 0.67 26.80
December 0.00 0.00 0.00 0.00 10.67 26.72 0.67 26.77
                 
Annual Sum or Average 0.00   0.00   77.00 26.46 3.17 26.49
Minimum of Months 0.00 0.00 0.00 0.00 2.33 25.95 0.00 25.95
Maximum of Months 0.00 0.00 0.00 0.00 10.67 26.75 0.67 26.80



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
February 0.00 0.00 0.00 0.00 0.17 25.58 0.00 25.58
March 0.00 0.00 0.00 0.00 0.50 25.59 0.00 25.59
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 1.17 25.60 0.00 25.60
September 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
October 0.00 0.00 0.00 0.00 0.33 25.67 0.00 25.67
November 0.00 0.00 0.00 0.00 0.83 25.58 0.00 25.58
December 0.00 0.00 0.00 0.00 0.83 25.63 0.00 25.63
                 
Annual Sum or Average 0.00   0.00   4.17 25.60 0.00 25.60
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 1.17 25.67 0.00 25.67



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.17 25.56 0.00 25.56
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.17 25.56 0.00 25.56



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.17 19.34 0.00 19.34 0.00 19.34 0.00 19.34
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.17 19.34 0.00 19.34 0.00 19.34 0.00 19.34
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.17 19.34 0.00 19.34 0.00 19.34 0.00 19.34



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.67 25.67 0.00 25.67
June 0.00 0.00 0.00 0.00 0.50 25.61 0.00 25.61
July 0.00 0.00 0.00 0.00 3.50 26.37 1.00 26.60
August 0.00 0.00 0.00 0.00 2.67 25.98 0.33 26.13
September 0.00 0.00 0.00 0.00 0.50 25.62 0.00 25.62
October 0.00 0.00 0.00 0.00 0.33 25.63 0.00 25.63
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   8.17 26.07 1.33 26.25
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 3.50 26.37 1.00 26.60



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.50 27.27 0.50 27.27
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.83 27.39 0.83 27.39
April 0.00 0.00 0.00 0.00 1.17 27.68 1.17 27.68
May 0.00 0.00 0.00 0.00 7.67 27.57 7.17 27.63
June 0.00 0.00 0.00 0.00 2.67 27.62 2.67 27.62
July 0.00 0.00 0.00 0.00 6.67 27.40 5.67 27.52
August 0.00 0.00 0.00 0.00 3.67 26.99 2.67 27.21
September 0.00 0.00 0.00 0.00 7.17 27.56 6.83 27.61
October 0.00 0.00 0.00 0.00 3.67 27.58 3.67 27.58
November 0.00 0.00 0.00 0.00 0.67 27.37 0.67 27.37
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   34.67 27.47 31.83 27.54
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 7.67 27.68 7.17 27.68



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 6.17 27.76 6.17 27.76
February 0.00 0.00 0.00 0.00 2.83 27.65 2.83 27.65
March 0.00 0.00 0.00 0.00 2.33 27.50 2.33 27.50
April 0.00 0.00 0.00 0.00 1.00 26.88 1.00 26.88
May 0.00 0.00 0.00 0.00 0.83 26.01 0.17 26.22
June 0.00 0.00 0.00 0.00 0.33 25.62 0.00 25.62
July 0.00 0.00 0.00 0.00 3.50 26.38 1.33 26.65
August 0.00 0.00 0.00 0.00 8.00 26.81 4.67 27.04
September 0.00 0.00 0.00 0.00 10.00 27.39 7.83 27.51
October 0.00 0.00 0.00 0.00 13.67 27.48 10.50 27.62
November 0.00 0.00 0.00 0.00 10.33 27.50 10.33 27.50
December 0.00 0.00 0.00 0.00 7.33 27.82 7.17 27.84
                 
Annual Sum or Average 0.00   0.00   66.33 27.37 54.33 27.49
Minimum of Months 0.00 0.00 0.00 0.00 0.33 25.62 0.00 25.62
Maximum of Months 0.00 0.00 0.00 0.00 13.67 27.82 10.50 27.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 1.33 27.66 1.33 27.66
February 0.00 0.00 0.00 0.00 3.67 27.16 2.17 27.39
March 0.00 0.00 0.00 0.00 9.67 27.00 3.33 27.21
April 0.00 0.00 0.00 0.00 25.67 27.02 7.00 27.16
May 0.00 0.00 0.00 0.00 16.67 26.91 5.00 27.12
June 0.00 0.00 0.00 0.00 25.33 27.00 6.33 27.17
July 0.00 0.00 0.00 0.00 39.50 27.29 13.50 27.42
August 0.00 0.00 0.00 0.00 51.50 27.42 12.17 27.51
September 0.00 0.00 0.00 0.00 16.50 27.04 5.67 27.27
October 0.00 0.00 0.00 0.00 22.33 27.02 8.33 27.24
November 0.00 0.00 0.00 0.00 12.17 26.98 5.00 27.24
December 0.00 0.00 0.00 0.00 11.33 27.16 5.83 27.37
                 
Annual Sum or Average 0.00   0.00   235.67 27.15 75.67 27.32
Minimum of Months 0.00 0.00 0.00 0.00 1.33 26.91 1.33 27.12
Maximum of Months 0.00 0.00 0.00 0.00 51.50 27.66 13.50 27.66



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.17 25.69 0.00 25.69
June 0.00 0.00 0.00 0.00 0.33 26.42 0.17 26.70
July 0.00 0.00 0.00 0.00 0.50 25.61 0.00 25.61
August 0.00 0.00 0.00 0.00 0.67 26.45 0.33 26.73
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   1.67 26.11 0.50 26.38
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.67 26.45 0.33 26.73



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.50 27.47 0.50 27.47
April 0.00 0.00 0.00 0.00 1.17 27.88 1.17 27.88
May 0.00 0.00 0.00 0.00 9.50 27.65 8.33 27.71
June 0.00 0.00 0.00 0.00 7.17 27.50 6.83 27.53
July 0.00 0.00 0.00 0.00 9.83 27.55 9.00 27.60
August 0.00 0.00 0.00 0.00 6.67 27.42 6.00 27.49
September 0.00 0.00 0.00 0.00 7.67 27.73 7.67 27.73
October 0.00 0.00 0.00 0.00 5.17 27.60 5.17 27.60
November 0.00 0.00 0.00 0.00 0.17 27.31 0.17 27.31
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   47.83 27.58 44.83 27.62
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 9.83 27.88 9.00 27.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 5.67 27.80 5.67 27.80
February 0.00 0.00 0.00 0.00 2.00 27.77 2.00 27.77
March 0.00 0.00 0.00 0.00 1.83 27.45 1.83 27.45
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.33 26.50 0.17 26.76
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.50 25.59 0.00 25.59
August 0.00 0.00 0.00 0.00 3.33 26.94 2.50 27.13
September 0.00 0.00 0.00 0.00 9.00 27.50 7.50 27.58
October 0.00 0.00 0.00 0.00 12.00 27.60 9.67 27.72
November 0.00 0.00 0.00 0.00 11.67 27.01 11.50 27.01
December 0.00 0.00 0.00 0.00 6.00 27.86 6.00 27.86
                 
Annual Sum or Average 0.00   0.00   52.33 27.44 46.83 27.50
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 12.00 27.86 11.50 27.86



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.17 27.31 0.17 27.31
February 0.00 0.00 0.00 0.00 0.50 27.82 0.50 27.82
March 0.00 0.00 0.00 0.00 0.83 27.57 0.83 27.57
April 0.00 0.00 0.00 0.00 3.17 27.75 1.67 27.78
May 0.00 0.00 0.00 0.00 7.33 27.40 3.17 27.56
June 0.00 0.00 0.00 0.00 9.17 27.12 3.17 27.33
July 0.00 0.00 0.00 0.00 13.17 27.05 5.33 27.23
August 0.00 0.00 0.00 0.00 10.00 26.74 3.67 26.99
September 0.00 0.00 0.00 0.00 7.67 27.54 3.83 27.72
October 0.00 0.00 0.00 0.00 5.83 27.63 4.00 27.72
November 0.00 0.00 0.00 0.00 1.00 27.49 1.00 27.49
December 0.00 0.00 0.00 0.00 0.50 27.49 0.50 27.49
                 
Annual Sum or Average 0.00   0.00   59.33 27.24 27.83 27.42
Minimum of Months 0.00 0.00 0.00 0.00 0.17 26.74 0.17 26.99
Maximum of Months 0.00 0.00 0.00 0.00 13.17 27.82 5.33 27.82



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 2.00 18.99 0.00 18.99 0.00 18.99 0.00 18.99
February 2.83 17.33 1.50 17.10 0.00 17.10 0.00 17.10
March 0.67 19.33 0.00 19.33 0.00 19.33 0.00 19.33
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 4.00 27.22 2.50 27.31
June 0.00 0.00 0.00 0.00 4.17 27.32 2.33 27.38
July 0.00 0.00 0.00 0.00 9.00 27.22 5.67 27.31
August 0.00 0.00 0.00 0.00 4.67 27.18 3.17 27.29
September 0.00 0.00 0.00 0.00 2.83 27.38 2.17 27.43
October 0.00 0.00 0.00 0.00 1.50 27.42 1.50 27.42
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 18.72 0.00 18.72 0.00 18.72 0.00 18.72
                 
Annual Sum or Average 6.00 18.22 1.50 17.91 26.17 25.18 17.33 25.95
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 2.83 19.33 1.50 19.33 9.00 27.42 5.67 27.43



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.50 18.98 0.00 18.98 0.00 18.98 0.00 18.98
February 0.83 17.48 0.17 17.05 0.00 17.05 0.00 17.05
March 0.50 19.40 0.00 19.40 0.50 23.37 0.50 24.70
April 0.00 0.00 0.00 0.00 2.33 27.68 2.33 27.68
May 0.00 0.00 0.00 0.00 11.17 27.74 8.50 27.84
June 0.00 0.00 0.00 0.00 9.50 27.62 7.50 27.69
July 0.00 0.00 0.00 0.00 17.17 27.59 13.33 27.67
August 0.00 0.00 0.00 0.00 10.33 27.52 8.00 27.61
September 0.00 0.00 0.00 0.00 12.50 27.75 10.83 27.79
October 0.00 0.00 0.00 0.00 7.00 27.65 6.67 27.65
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.50 18.77 0.00 18.77 0.00 18.77 0.00 18.77
                 
Annual Sum or Average 3.33 18.64 0.17 18.46 70.50 27.21 57.67 27.46
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 1.50 19.40 0.17 19.40 17.17 27.75 13.33 27.84



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 19.32 0.00 19.32 3.67 26.07 3.67 26.88
February 0.33 18.65 0.00 18.65 1.67 26.30 1.67 27.00
March 0.00 0.00 0.00 0.00 2.00 27.50 2.00 27.50
April 0.00 0.00 0.00 0.00 1.00 27.42 1.00 27.42
May 0.00 0.00 0.00 0.00 5.33 27.29 3.67 27.37
June 0.00 0.00 0.00 0.00 4.00 27.26 2.50 27.33
July 0.00 0.00 0.00 0.00 9.17 27.21 6.33 27.31
August 0.00 0.00 0.00 0.00 8.00 27.30 5.50 27.41
September 0.00 0.00 0.00 0.00 12.83 27.57 8.67 27.69
October 0.00 0.00 0.00 0.00 13.33 27.67 9.17 27.83
November 0.00 0.00 0.00 0.00 7.33 27.72 7.17 27.73
December 0.50 19.11 0.00 19.11 4.50 27.06 4.33 27.48
                 
Annual Sum or Average 1.83 19.14 0.00 19.14 72.83 27.33 55.67 27.51
Minimum of Months 0.00 0.00 0.00 0.00 1.00 26.07 1.00 26.88
Maximum of Months 1.00 19.32 0.00 19.32 13.33 27.72 9.17 27.83



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 1.00 19.11 0.00 19.11 0.17 20.28 0.17 21.16
February 0.33 18.65 0.00 18.65 0.67 24.68 0.67 25.88
March 0.00 0.00 0.00 0.00 1.17 27.58 1.00 27.58
April 0.00 0.00 0.00 0.00 3.33 27.83 1.67 27.88
May 0.00 0.00 0.00 0.00 7.83 27.72 3.67 27.83
June 0.00 0.00 0.00 0.00 10.33 27.42 3.67 27.60
July 0.00 0.00 0.00 0.00 17.67 27.30 7.83 27.46
August 0.00 0.00 0.00 0.00 11.17 27.03 4.33 27.26
September 0.00 0.00 0.00 0.00 10.83 27.69 5.33 27.83
October 0.00 0.00 0.00 0.00 7.00 27.71 4.67 27.82
November 0.00 0.00 0.00 0.00 1.00 27.53 1.00 27.53
December 0.50 19.07 0.00 19.07 0.50 23.35 0.50 24.77
                 
Annual Sum or Average 1.83 19.02 0.00 19.02 71.67 27.25 34.50 27.47
Minimum of Months 0.00 0.00 0.00 0.00 0.17 20.28 0.17 21.16
Maximum of Months 1.00 19.11 0.00 19.11 17.67 27.83 7.83 27.88



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.00 27.62 1.00 27.62
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 47.67 27.74 47.67 27.74
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   48.67 27.73 48.67 27.73
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 47.67 27.74 47.67 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 1.67 27.66 1.67 27.66
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 51.67 27.74 51.67 27.74
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   53.33 27.74 53.33 27.74
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 51.67 27.74 51.67 27.74



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.67 27.61 0.67 27.61
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 26.50 27.72 26.50 27.72
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00   0.00   27.17 27.71 27.17 27.71
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 26.50 27.72 26.50 27.72



Table of Contents

Report: SetpointsNotMetWithTemperaturesMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 105.83 28.15 104.50 28.15
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 493.83 28.88 415.00 28.95
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 40.83 28.03 40.83 28.03
                 
Annual Sum or Average 0.00   0.00   640.50 28.70 560.33 28.75
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 493.83 28.88 415.00 28.95



Table of Contents

Report: ComfortReportSimple55Monthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 56.83 24.52 238.50 25.01 39.50 24.98
February 90.50 24.58 311.17 24.70 70.00 24.70
March 106.17 24.57 311.50 24.63 82.00 24.65
April 172.83 24.75 430.17 24.62 172.83 24.65
May 292.50 24.87 508.00 24.63 292.50 24.70
June 252.00 24.85 496.00 24.58 252.00 24.65
July 245.33 25.23 497.00 24.82 245.33 24.92
August 180.33 25.28 514.00 24.70 180.33 24.82
September 219.50 25.19 485.00 24.76 219.50 24.86
October 165.67 25.47 452.50 24.89 165.67 25.02
November 75.00 25.34 381.00 24.88 75.00 24.95
December 62.17 24.99 309.83 24.97 58.17 24.98
             
Annual Sum or Average 1918.83 25.01 4934.67 24.74 1852.83 24.81
Minimum of Months 56.83 24.52 238.50 24.58 39.50 24.65
Maximum of Months 292.50 25.47 514.00 25.01 292.50 25.02



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 45.67 23.90 215.33 24.52 0.33 24.53
February 24.50 23.91 306.67 24.40 0.00 24.40
March 15.50 23.88 317.67 24.41 0.00 24.41
April 0.00 0.00 433.17 24.28 0.00 24.28
May 0.00 0.00 508.00 24.26 0.00 24.26
June 0.00 0.00 496.00 24.17 0.00 24.17
July 0.00 0.00 497.00 24.21 0.00 24.21
August 0.00 0.00 514.00 24.17 0.00 24.17
September 0.00 0.00 485.00 24.27 0.00 24.27
October 0.00 0.00 451.83 24.35 0.00 24.35
November 0.00 0.00 380.33 24.46 0.00 24.46
December 8.00 23.98 311.50 24.53 0.00 24.53
             
Annual Sum or Average 93.67 23.91 4916.50 24.31 0.33 24.31
Minimum of Months 0.00 0.00 215.33 24.17 0.00 24.17
Maximum of Months 45.67 23.98 514.00 24.53 0.33 24.53



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 216.67 23.59 140.67 23.84 0.00 23.84
February 123.33 23.62 229.00 24.00 0.00 24.00
March 119.50 23.63 249.17 24.06 0.00 24.06
April 5.83 23.95 405.33 24.31 0.00 24.31
May 0.00 0.00 506.67 24.23 0.00 24.23
June 0.00 0.00 495.83 24.19 0.00 24.19
July 0.00 0.00 496.17 24.20 0.00 24.20
August 0.00 0.00 514.00 24.21 0.00 24.21
September 0.00 0.00 481.33 24.18 0.00 24.18
October 14.83 23.72 439.50 24.27 0.00 24.27
November 46.17 23.72 303.83 24.22 0.00 24.22
December 138.00 23.55 209.33 24.00 0.00 24.00
             
Annual Sum or Average 664.33 23.61 4470.83 24.16 0.00 24.16
Minimum of Months 0.00 0.00 140.67 23.84 0.00 23.84
Maximum of Months 216.67 23.95 514.00 24.31 0.00 24.31



Table of Contents

Report: ComfortReportSimple55Monthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 351.17 22.66 122.83 22.99 7.00 22.95
February 206.50 22.60 197.00 23.16 19.00 23.04
March 191.17 22.95 234.33 23.58 5.83 23.53
April 30.33 23.47 381.50 24.21 0.00 24.21
May 0.00 0.00 508.00 24.28 0.00 24.28
June 0.00 0.00 496.00 24.25 0.00 24.25
July 0.00 0.00 497.00 24.28 0.00 24.28
August 0.00 0.00 514.00 24.26 0.00 24.26
September 0.00 0.00 485.00 24.25 0.00 24.25
October 39.00 23.31 427.17 24.23 0.00 24.23
November 148.67 23.32 247.83 23.85 0.00 23.85
December 261.17 22.82 165.17 23.30 4.33 23.28
             
Annual Sum or Average 1228.00 22.85 4275.83 23.91 36.17 23.89
Minimum of Months 0.00 0.00 122.83 22.99 0.00 22.95
Maximum of Months 351.17 23.47 514.00 24.28 19.00 24.28



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 320.67 22.84 137.00 23.25 0.00 23.25
February 184.67 22.94 211.17 23.56 4.17 23.53
March 185.67 23.29 241.67 23.83 0.00 23.83
April 25.67 23.72 404.17 24.19 0.00 24.19
May 19.83 26.15 508.00 24.47 19.83 24.53
June 4.67 26.69 496.00 24.37 4.67 24.39
July 23.83 26.66 497.00 24.56 23.83 24.65
August 15.50 26.67 514.00 24.38 15.50 24.45
September 20.67 26.12 485.00 24.47 20.67 24.54
October 48.33 24.57 437.83 24.41 18.83 24.47
November 106.17 23.61 269.83 24.06 0.00 24.06
December 203.33 23.19 200.50 23.70 0.00 23.70
             
Annual Sum or Average 1159.00 23.41 4402.17 24.14 107.50 24.17
Minimum of Months 4.67 22.84 137.00 23.25 0.00 23.25
Maximum of Months 320.67 26.69 514.00 24.56 23.83 24.65



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 265.50 22.98 148.83 23.51 3.00 23.53
February 163.33 23.04 215.67 23.72 3.00 23.72
March 163.00 23.07 251.50 23.84 4.17 23.87
April 32.17 24.03 395.33 24.22 6.00 24.26
May 49.50 26.63 508.00 24.65 49.50 24.81
June 25.33 26.72 496.00 24.47 25.33 24.57
July 44.17 26.71 497.00 24.63 44.17 24.79
August 24.33 26.69 514.00 24.39 24.33 24.49
September 49.67 26.69 485.00 24.66 49.67 24.84
October 55.00 25.31 436.50 24.53 33.33 24.66
November 89.83 23.49 298.17 24.15 2.83 24.17
December 198.67 22.88 194.50 23.56 0.50 23.56
             
Annual Sum or Average 1160.50 23.78 4440.50 24.25 245.83 24.35
Minimum of Months 24.33 22.88 148.83 23.51 0.50 23.53
Maximum of Months 265.50 26.72 514.00 24.66 49.67 24.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 173.83 23.58 222.67 24.18 21.50 24.32
February 101.50 23.47 294.33 24.16 13.83 24.21
March 135.17 23.34 289.50 24.05 10.17 24.12
April 21.00 24.33 409.33 24.31 4.83 24.34
May 28.33 26.25 508.00 24.50 28.33 24.59
June 7.00 26.64 496.00 24.37 7.00 24.40
July 29.17 26.65 497.00 24.57 29.17 24.68
August 25.33 26.76 514.00 24.46 25.33 24.56
September 48.67 26.69 485.00 24.69 48.67 24.86
October 61.83 26.29 458.33 24.77 52.33 24.96
November 56.83 25.44 393.83 24.69 30.67 24.84
December 123.83 23.94 299.67 24.43 25.83 24.58
             
Annual Sum or Average 812.50 24.45 4867.67 24.45 297.67 24.56
Minimum of Months 7.00 23.34 222.67 24.05 4.83 24.12
Maximum of Months 173.83 26.76 514.00 24.77 52.33 24.96



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 199.67 23.29 212.67 23.93 6.00 23.97
February 83.00 23.75 311.33 24.36 9.33 24.42
March 57.00 24.69 364.17 24.58 19.67 24.68
April 49.67 26.85 467.33 24.81 49.67 24.99
May 46.83 26.82 508.00 24.71 46.83 24.88
June 54.33 26.82 496.00 24.72 54.33 24.91
July 88.67 26.79 497.00 24.96 88.67 25.20
August 88.50 26.77 514.00 24.86 88.50 25.10
September 50.67 26.78 485.00 24.76 50.67 24.93
October 58.50 26.67 470.83 24.85 54.83 25.04
November 31.67 26.55 423.17 24.76 27.33 24.88
December 53.67 25.61 347.67 24.89 32.17 25.04
             
Annual Sum or Average 862.17 25.46 5097.17 24.71 528.00 24.88
Minimum of Months 31.67 23.29 212.67 23.93 6.00 23.97
Maximum of Months 199.67 26.85 514.00 24.96 88.67 25.20



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 396.33 21.82 112.00 22.07 38.33 21.99
February 292.33 22.06 143.17 22.44 28.33 22.28
March 288.33 22.48 169.33 22.96 13.83 22.88
April 97.50 23.61 326.00 24.08 12.67 24.12
May 49.50 25.82 508.00 24.53 49.50 24.63
June 32.67 26.21 496.00 24.50 32.67 24.60
July 63.67 26.19 497.00 24.68 63.67 24.84
August 55.33 26.02 514.00 24.53 55.33 24.66
September 70.50 25.63 485.00 24.52 70.50 24.65
October 104.33 24.29 407.83 24.35 48.00 24.47
November 247.83 22.83 181.67 23.37 5.17 23.38
December 349.50 22.13 128.00 22.53 21.50 22.48
             
Annual Sum or Average 2047.83 22.88 3968.00 23.77 439.50 23.83
Minimum of Months 32.67 21.82 112.00 22.07 5.17 21.99
Maximum of Months 396.33 26.21 514.00 24.68 70.50 24.84



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 314.83 22.26 95.50 22.64 15.83 22.60
February 210.00 22.37 130.17 22.89 17.33 22.78
March 201.00 22.60 183.00 23.39 10.33 23.38
April 60.67 24.24 311.17 24.42 22.17 24.52
May 68.83 26.51 430.00 24.85 68.83 25.05
June 50.33 26.61 417.33 24.75 50.33 24.93
July 71.17 26.66 422.00 24.95 71.17 25.17
August 62.33 26.44 433.00 24.75 62.33 24.94
September 75.00 26.29 409.00 24.81 75.00 25.01
October 95.50 24.98 349.83 24.67 55.17 24.86
November 165.83 23.14 193.00 23.81 7.00 23.85
December 272.67 22.36 123.00 22.85 16.67 22.82
             
Annual Sum or Average 1648.17 23.49 3497.00 24.15 472.17 24.29
Minimum of Months 50.33 22.26 95.50 22.64 7.00 22.60
Maximum of Months 314.83 26.66 433.00 24.95 75.00 25.17



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 209.17 23.20 206.67 23.89 28.50 24.03
February 137.17 22.97 259.33 23.83 18.00 23.82
March 184.67 22.84 251.00 23.65 12.33 23.67
April 60.50 24.04 373.67 24.30 16.17 24.36
May 55.83 25.88 508.00 24.55 55.83 24.67
June 31.83 26.10 496.00 24.47 31.83 24.57
July 63.50 26.18 497.00 24.67 63.50 24.82
August 59.33 26.23 514.00 24.60 59.33 24.75
September 76.50 26.23 485.00 24.72 76.50 24.90
October 86.33 25.83 452.00 24.78 64.00 24.98
November 88.67 24.60 356.83 24.58 32.83 24.74
December 175.50 23.32 275.33 24.09 28.50 24.22
             
Annual Sum or Average 1229.00 24.15 4674.83 24.38 487.33 24.52
Minimum of Months 31.83 22.84 206.67 23.65 12.33 23.67
Maximum of Months 209.17 26.23 514.00 24.78 76.50 24.98



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 329.00 22.26 134.67 22.75 17.33 22.72
February 213.67 22.36 201.83 23.10 17.83 23.01
March 208.83 22.66 242.33 23.48 12.00 23.48
April 57.67 24.64 392.67 24.46 22.00 24.56
May 54.00 26.29 508.00 24.65 54.00 24.79
June 43.83 26.65 496.00 24.65 43.83 24.80
July 72.50 26.53 497.00 24.82 72.50 25.01
August 58.83 26.55 514.00 24.68 58.83 24.85
September 70.50 26.19 485.00 24.68 70.50 24.85
October 84.17 25.14 439.00 24.59 51.83 24.75
November 163.50 23.19 256.17 23.86 9.17 23.91
December 267.17 22.45 186.17 23.18 11.00 23.18
             
Annual Sum or Average 1623.67 23.45 4352.83 24.14 440.83 24.26
Minimum of Months 43.83 22.26 134.67 22.75 9.17 22.72
Maximum of Months 329.00 26.65 514.00 24.82 72.50 25.01



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 422.67 21.32 189.33 21.38 131.33 21.22
February 326.17 21.62 169.50 21.77 82.00 21.52
March 319.50 22.02 195.00 22.41 54.00 22.20
April 141.00 23.21 301.67 23.90 13.17 23.94
May 66.33 26.03 508.00 24.61 66.33 24.76
June 46.00 26.38 494.83 24.58 46.00 24.73
July 68.17 26.43 497.00 24.76 68.17 24.94
August 66.17 26.12 514.00 24.59 66.17 24.75
September 82.83 25.73 483.83 24.59 82.83 24.73
October 124.00 24.00 399.67 24.30 54.33 24.44
November 290.50 22.37 170.67 22.90 23.67 22.86
December 373.83 21.61 179.50 21.87 88.67 21.72
             
Annual Sum or Average 2327.17 22.57 4103.00 23.48 776.67 23.47
Minimum of Months 46.00 21.32 169.50 21.38 13.17 21.22
Maximum of Months 422.67 26.43 514.00 24.76 131.33 24.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 392.17 21.74 148.50 21.93 71.00 21.77
February 271.83 21.93 160.83 22.31 41.83 22.08
March 248.33 22.23 243.50 22.99 41.50 22.86
April 90.83 23.69 360.67 24.23 23.00 24.32
May 72.83 26.49 508.00 24.75 72.83 24.94
June 55.17 26.66 494.50 24.68 55.17 24.86
July 73.67 26.74 497.00 24.87 73.67 25.08
August 66.50 26.46 514.00 24.67 66.50 24.86
September 82.00 26.25 482.83 24.73 82.00 24.92
October 121.00 24.58 414.00 24.52 61.67 24.72
November 216.67 22.79 208.83 23.50 8.50 23.52
December 344.33 21.92 163.17 22.34 49.67 22.21
             
Annual Sum or Average 2035.33 23.04 4195.83 23.85 647.33 23.92
Minimum of Months 55.17 21.74 148.50 21.93 8.50 21.77
Maximum of Months 392.17 26.74 514.00 24.87 82.00 25.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 256.33 22.55 199.83 23.17 52.83 23.14
February 184.00 22.35 248.17 23.25 34.33 23.13
March 221.83 22.38 255.00 23.14 42.50 23.02
April 96.33 23.56 347.17 24.17 18.50 24.24
May 67.17 26.02 508.00 24.61 67.17 24.76
June 45.00 26.29 494.83 24.56 45.00 24.69
July 67.17 26.39 497.00 24.74 67.17 24.92
August 65.17 26.25 514.00 24.63 65.17 24.79
September 83.67 26.18 484.17 24.74 83.67 24.92
October 96.33 25.46 446.83 24.73 66.00 24.94
November 120.50 23.74 326.00 24.33 27.50 24.46
December 215.83 22.66 259.50 23.55 42.83 23.56
             
Annual Sum or Average 1519.33 23.65 4580.50 24.19 612.67 24.28
Minimum of Months 45.00 22.35 199.83 23.14 18.50 23.02
Maximum of Months 256.33 26.39 514.00 24.74 83.67 24.94



Table of Contents

Report: ComfortReportSimple55Monthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 366.00 21.75 164.17 22.09 67.17 21.96
February 258.50 21.92 197.33 22.51 45.50 22.31
March 249.83 22.20 238.67 22.97 35.83 22.85
April 89.67 23.88 364.83 24.31 23.17 24.42
May 62.50 26.27 508.00 24.67 62.50 24.83
June 52.50 26.66 495.00 24.69 52.50 24.86
July 80.17 26.60 497.00 24.87 80.17 25.08
August 66.83 26.60 514.00 24.72 66.83 24.91
September 77.33 26.16 482.83 24.70 77.33 24.87
October 100.83 24.76 428.50 24.54 57.17 24.71
November 215.67 22.70 223.17 23.49 11.67 23.54
December 305.33 21.95 191.17 22.59 41.17 22.50
             
Annual Sum or Average 1925.17 23.05 4304.67 23.90 621.00 23.98
Minimum of Months 52.50 21.75 164.17 22.09 11.67 21.96
Maximum of Months 366.00 26.66 514.00 24.87 80.17 25.08



Table of Contents

Report: ComfortReportSimple55Monthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00
             
Annual Sum or Average 0.00   0.00   0.00  
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 4.50 27.00 502.00 27.00 4.50 27.00
February 15.83 27.00 454.00 27.00 15.83 27.00
March 59.00 27.00 514.00 27.00 59.00 27.00
April 262.17 27.01 485.00 27.01 262.17 27.01
May 11.83 27.00 508.00 27.00 11.83 27.00
June 109.00 27.00 496.00 27.00 109.00 27.00
July 271.17 27.00 497.00 27.00 271.17 27.00
August 484.17 27.14 514.00 27.14 484.17 27.14
September 37.17 27.00 485.00 27.00 37.17 27.00
October 98.17 27.00 502.00 27.00 98.17 27.00
November 95.50 27.00 489.00 27.00 95.50 27.00
December 154.67 27.00 497.00 27.00 154.67 27.00
             
Annual Sum or Average 1603.17 27.04 5943.00 27.02 1603.17 27.02
Minimum of Months 4.50 27.00 454.00 27.00 4.50 27.00
Maximum of Months 484.17 27.14 514.00 27.14 484.17 27.14



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 0.00 0.00 502.00 27.00 0.00 27.00
February 0.00 0.00 451.67 27.00 0.00 27.00
March 0.00 0.00 514.00 27.00 0.00 27.00
April 6.83 27.31 485.00 27.01 6.83 27.01
May 0.00 0.00 508.00 27.00 0.00 27.00
June 0.00 0.00 496.00 27.00 0.00 27.00
July 1.17 27.00 497.00 27.00 1.17 27.00
August 123.67 27.52 514.00 27.21 123.67 27.26
September 0.00 0.00 485.00 27.00 0.00 27.00
October 0.50 27.00 502.00 27.00 0.50 27.00
November 1.50 27.00 489.00 27.00 1.50 27.00
December 4.67 27.00 497.00 27.00 4.67 27.00
             
Annual Sum or Average 138.33 27.48 5940.67 27.02 138.33 27.03
Minimum of Months 0.00 0.00 451.67 27.00 0.00 27.00
Maximum of Months 123.67 27.52 514.00 27.21 123.67 27.26



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 5.50 26.19 481.17 26.99 0.00 26.99
February 7.67 27.00 436.33 27.00 1.67 27.00
March 1.33 27.00 507.00 27.00 1.33 27.00
April 39.83 27.04 485.00 27.01 39.83 27.01
May 15.33 27.00 508.00 27.00 15.33 27.00
June 37.67 27.00 496.00 27.00 37.67 27.00
July 76.50 27.00 497.00 27.00 76.50 27.00
August 144.50 27.29 514.00 27.13 144.50 27.16
September 19.17 27.00 485.00 27.00 19.17 27.00
October 31.33 27.00 502.00 27.00 31.33 27.00
November 6.67 27.00 489.00 27.00 6.67 27.00
December 9.17 27.00 490.33 27.00 9.17 27.00
             
Annual Sum or Average 394.67 27.10 5890.83 27.01 383.17 27.02
Minimum of Months 1.33 26.19 436.33 26.99 0.00 26.99
Maximum of Months 144.50 27.29 514.00 27.13 144.50 27.16



Table of Contents

Report: ComfortReportSimple55Monthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C]
January 502.00 27.00 502.00 27.00 502.00 27.00
February 454.00 27.00 454.00 27.00 454.00 27.00
March 514.00 27.00 514.00 27.00 514.00 27.00
April 485.00 27.28 485.00 27.28 485.00 27.28
May 508.00 27.00 508.00 27.00 508.00 27.00
June 496.00 27.00 496.00 27.00 496.00 27.00
July 497.00 27.00 497.00 27.00 497.00 27.00
August 514.00 28.68 514.00 28.68 514.00 28.68
September 485.00 27.00 485.00 27.00 485.00 27.00
October 502.00 27.00 502.00 27.00 502.00 27.00
November 489.00 27.00 489.00 27.00 489.00 27.00
December 497.00 27.11 497.00 27.11 497.00 27.11
             
Annual Sum or Average 5943.00 27.18 5943.00 27.18 5943.00 27.18
Minimum of Months 454.00 27.00 454.00 27.00 454.00 27.00
Maximum of Months 514.00 28.68 514.00 28.68 514.00 28.68



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00021 32.41350 0.88576 21.69884
February 454.00000 27.00094 33.67847 0.94033 23.79517
March 514.00000 27.00055 33.95099 0.97846 25.29395
April 485.00000 27.00401 36.63871 1.04973 28.29059
May 508.00000 27.00035 42.22260 0.34470 7.51351
June 496.00000 27.00234 40.64782 0.38074 8.05580
July 497.00000 27.00136 39.91345 0.42335 8.77134
August 514.00000 27.13143 39.22418 0.50720 10.54353
September 485.00000 27.00020 42.61318 0.35024 7.59969
October 502.00000 27.00182 38.51082 1.01328 26.72956
November 489.00000 27.00064 35.55206 1.00702 26.46487
December 497.00000 27.00017 33.55634 1.00908 26.57764
           
Annual Sum or Average 5943.00000 27.01241 37.43111 0.73888 18.38526
Minimum of Months 454.00000 27.00017 32.41350 0.34470 7.51351
Maximum of Months 514.00000 27.13143 42.61318 1.04973 28.29059



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00013 32.49914 0.81196 19.09821
February 454.00000 27.00089 33.69464 0.85348 20.58534
March 514.00000 27.00052 33.92015 0.88319 21.60031
April 485.00000 27.00493 36.59214 0.96089 24.55059
May 508.00000 27.00020 42.42097 0.29973 6.91244
June 496.00000 27.00223 40.71039 0.31380 7.08656
July 497.00000 27.00137 39.92894 0.32967 7.29590
August 514.00000 27.13538 39.21660 0.38270 8.22749
September 485.00000 27.00012 42.90302 0.29615 6.87511
October 502.00000 27.00173 38.56250 0.95540 24.35020
November 489.00000 27.00062 35.52266 0.91219 22.65342
December 497.00000 27.00015 33.50296 0.88044 21.51456
           
Annual Sum or Average 5943.00000 27.01277 37.47707 0.65462 15.84260
Minimum of Months 454.00000 27.00012 32.49914 0.29615 6.87511
Maximum of Months 514.00000 27.13538 42.90302 0.96089 24.55059



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 26.98190 32.59388 0.75799 17.51511
February 454.00000 27.00091 33.74378 0.81610 19.46089
March 514.00000 27.00054 33.95035 0.85753 20.78953
April 485.00000 27.00337 36.62199 0.95777 24.46916
May 508.00000 27.00029 42.34730 0.31743 7.17538
June 496.00000 27.00235 40.69575 0.33611 7.42565
July 497.00000 27.00144 39.94094 0.35313 7.66684
August 514.00000 27.08406 39.27249 0.38980 8.34344
September 485.00000 27.00013 42.84248 0.30988 7.08539
October 502.00000 27.00180 38.57039 0.95755 24.49548
November 489.00000 27.00065 35.55727 0.88872 21.83742
December 497.00000 27.00018 33.53799 0.83869 20.13356
           
Annual Sum or Average 5943.00000 27.00670 37.49369 0.64656 15.48484
Minimum of Months 454.00000 26.98190 32.59388 0.30988 7.08539
Maximum of Months 514.00000 27.08406 42.84248 0.95777 24.49548



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 27.00147 33.86132 1.11351 31.16488
February 454.00000 27.00198 35.11065 1.26539 38.52176
March 514.00000 27.00110 34.92304 1.39888 45.46222
April 485.00000 27.28110 36.96329 1.60259 56.42752
May 508.00000 27.00415 40.24930 0.57261 11.91178
June 496.00000 27.00292 39.76167 0.78324 17.94614
July 497.00000 27.00140 39.51757 0.99621 25.97541
August 514.00000 28.67645 37.90373 1.67252 59.87193
September 485.00000 27.00466 40.29943 0.63296 13.46116
October 502.00000 27.00238 38.15307 1.33036 41.85149
November 489.00000 27.00083 36.20186 1.44770 48.07347
December 497.00000 27.10578 34.73743 1.57762 55.10554
           
Annual Sum or Average 5943.00000 27.17851 37.31663 1.19986 37.17626
Minimum of Months 454.00000 27.00083 33.86132 0.57261 11.91178
Maximum of Months 514.00000 28.67645 40.29943 1.67252 59.87193



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.54671 38.18362 0.49384 11.02254
February 454.00000 24.51620 46.34240 0.54038 11.91955
March 514.00000 24.41071 45.26981 0.51038 11.20576
April 485.00000 24.49827 56.87606 0.61121 13.56156
May 508.00000 24.49899 64.73033 -0.1810 6.93540
June 496.00000 24.44874 64.03564 -0.1981 6.83931
July 497.00000 24.61111 63.18433 -0.1452 7.05813
August 514.00000 24.49222 61.29135 -0.1765 6.95829
September 485.00000 24.56440 62.30023 -0.1572 7.04431
October 502.00000 24.61702 56.81991 0.65920 15.24040
November 489.00000 24.61877 47.67094 0.59119 13.22669
December 497.00000 24.60778 42.78921 0.54912 12.33580
           
Annual Sum or Average 5943.00000 24.53550 54.16941 0.25502 10.25539
Minimum of Months 454.00000 24.41071 38.18362 -0.1981 6.83931
Maximum of Months 514.00000 24.61877 64.73033 0.65920 15.24040



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.30075 38.97513 0.44179 9.58816
February 454.00000 24.33140 44.76451 0.49717 10.66179
March 514.00000 24.27491 43.43484 0.48479 10.32531
April 485.00000 24.24760 51.53518 0.54803 11.50887
May 508.00000 24.25985 56.47276 -0.2837 7.00206
June 496.00000 24.17402 56.36455 -0.3014 7.03896
July 497.00000 24.21364 55.96302 -0.2828 6.83435
August 514.00000 24.16945 55.63178 -0.2826 6.79611
September 485.00000 24.26775 56.35077 -0.2785 6.95308
October 502.00000 24.31499 51.78926 0.56618 12.02418
November 489.00000 24.37220 46.12676 0.53644 11.43997
December 497.00000 24.35232 42.00858 0.49827 10.66120
           
Annual Sum or Average 5943.00000 24.27251 49.97890 0.17537 9.21792
Minimum of Months 454.00000 24.16945 38.97513 -0.3014 6.79611
Maximum of Months 514.00000 24.37220 56.47276 0.56618 12.02418



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.92671 40.64003 0.33273 7.81563
February 454.00000 24.00102 46.40708 0.39572 8.86018
March 514.00000 24.04934 45.06183 0.40651 8.96703
April 485.00000 24.25622 52.88796 0.52201 11.02287
May 508.00000 24.22646 56.87572 -0.3154 7.38111
June 496.00000 24.19414 56.79335 -0.3248 7.44603
July 497.00000 24.19492 56.90178 -0.3262 7.48390
August 514.00000 24.21115 56.81749 -0.3180 7.39956
September 485.00000 24.17964 57.11658 -0.3315 7.55879
October 502.00000 24.24775 52.48829 0.52801 11.14361
November 489.00000 24.15968 47.51265 0.45820 9.72926
December 497.00000 24.00896 44.10363 0.38477 8.65959
           
Annual Sum or Average 5943.00000 24.13866 51.15819 0.11468 8.61322
Minimum of Months 454.00000 23.92671 40.64003 -0.3315 7.38111
Maximum of Months 514.00000 24.25622 57.11658 0.52801 11.14361



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.07753 43.20244 0.11965 7.19394
February 454.00000 23.35964 48.47232 0.23876 8.64696
March 514.00000 23.68420 46.37174 0.31398 8.66960
April 485.00000 24.17537 53.13120 0.50535 10.70555
May 508.00000 24.28138 56.46810 -0.2803 7.04573
June 496.00000 24.25005 56.25120 -0.2856 7.02468
July 497.00000 24.28449 56.31608 -0.2775 6.95394
August 514.00000 24.26390 56.41985 -0.2833 7.05485
September 485.00000 24.25172 56.83629 -0.2961 7.16199
October 502.00000 24.21486 52.77321 0.52672 11.36503
November 489.00000 23.87115 48.80230 0.38346 8.72564
December 497.00000 23.41670 46.31229 0.23359 7.85470
           
Annual Sum or Average 5943.00000 23.93101 51.79410 0.07265 8.19126
Minimum of Months 454.00000 23.07753 43.20244 -0.2961 6.95394
Maximum of Months 514.00000 24.28449 56.83629 0.52672 11.36503



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.31598 40.99646 0.17746 7.31759
February 454.00000 23.63181 45.24975 0.29649 8.42785
March 514.00000 23.85456 43.75975 0.35134 8.68380
April 485.00000 24.17095 51.09188 0.51573 10.86700
May 508.00000 24.40181 56.07869 -0.1974 6.62369
June 496.00000 24.34729 55.30359 -0.1947 6.42501
July 497.00000 24.45532 55.15037 -0.1561 6.50604
August 514.00000 24.31481 54.98476 -0.1972 6.46764
September 485.00000 24.40016 56.32911 -0.2124 6.83545
October 502.00000 24.32356 51.80951 0.57120 12.48167
November 489.00000 24.05014 46.38462 0.42619 9.35928
December 497.00000 23.75597 43.22927 0.31571 8.18978
           
Annual Sum or Average 5943.00000 24.08781 50.05572 0.13927 8.17283
Minimum of Months 454.00000 23.31598 40.99646 -0.2124 6.42501
Maximum of Months 514.00000 24.45532 56.32911 0.57120 12.48167



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.56860 40.00187 0.25553 8.11723
February 454.00000 23.75243 44.69326 0.34765 9.04020
March 514.00000 23.84211 43.41294 0.37806 9.54427
April 485.00000 24.14270 50.91785 0.53840 11.58571
May 508.00000 24.45561 55.56468 -0.1324 6.73283
June 496.00000 24.35400 55.07623 -0.1544 6.40282
July 497.00000 24.44885 54.94722 -0.1257 6.62379
August 514.00000 24.27838 54.99383 -0.1880 6.53060
September 485.00000 24.45741 55.78466 -0.1611 7.07509
October 502.00000 24.35091 51.38151 0.60189 13.50043
November 489.00000 24.09060 45.99861 0.45733 10.18780
December 497.00000 23.63548 43.24553 0.30149 8.36570
           
Annual Sum or Average 5943.00000 24.11668 49.69490 0.17433 8.63150
Minimum of Months 454.00000 23.56860 40.00187 -0.1880 6.40282
Maximum of Months 514.00000 24.45741 55.78466 0.60189 13.50043



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 24.01902 38.55234 0.40084 10.38912
February 454.00000 24.09881 43.52520 0.46340 11.24708
March 514.00000 23.99104 42.98641 0.41881 10.22793
April 485.00000 24.25174 50.70929 0.55536 11.90499
May 508.00000 24.40681 56.03572 -0.1916 6.64007
June 496.00000 24.33618 55.36845 -0.2055 6.52109
July 497.00000 24.45001 55.16753 -0.1601 6.56443
August 514.00000 24.34251 54.78656 -0.1691 6.41336
September 485.00000 24.49041 55.73352 -0.1423 6.92916
October 502.00000 24.51598 50.70851 0.67655 15.69262
November 489.00000 24.45813 44.71325 0.59623 13.54148
December 497.00000 24.21807 41.41676 0.49340 11.96372
           
Annual Sum or Average 5943.00000 24.29855 49.17475 0.22511 9.81412
Minimum of Months 454.00000 23.99104 38.55234 -0.2055 6.41336
Maximum of Months 514.00000 24.51598 56.03572 0.67655 15.69262



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.91264 38.78650 0.36886 9.42369
February 454.00000 24.26583 43.02766 0.51884 12.05090
March 514.00000 24.37589 41.74364 0.56633 12.84613
April 485.00000 24.56991 49.36623 0.73474 17.22217
May 508.00000 24.51687 55.18050 -0.0671 6.46412
June 496.00000 24.49413 54.41449 -0.0281 6.38716
July 497.00000 24.63463 53.98552 0.03592 6.83471
August 514.00000 24.52915 53.68246 0.05144 6.58094
September 485.00000 24.54423 55.18542 -0.0683 6.73052
October 502.00000 24.58179 50.32530 0.71896 16.87053
November 489.00000 24.54309 44.37242 0.63563 14.39234
December 497.00000 24.53564 40.41717 0.59564 13.71650
           
Annual Sum or Average 5943.00000 24.45925 48.40363 0.33638 10.76510
Minimum of Months 454.00000 23.91264 38.78650 -0.0683 6.38716
Maximum of Months 514.00000 24.63463 55.18542 0.73474 17.22217



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.26338 44.15995 -0.0800 7.76974
February 454.00000 22.72474 47.94750 0.07013 8.53143
March 514.00000 23.15562 46.17857 0.17080 8.00898
April 485.00000 23.99988 53.10251 0.45389 9.99933
May 508.00000 24.40066 57.48575 -0.2074 6.79071
June 496.00000 24.39007 56.49383 -0.1981 6.67194
July 497.00000 24.48754 57.35949 -0.1639 6.79679
August 514.00000 24.37284 57.55178 -0.2089 6.81239
September 485.00000 24.36246 58.47213 -0.2357 7.03598
October 502.00000 24.18607 54.04951 0.52987 11.95971
November 489.00000 23.41723 48.85046 0.26011 7.78337
December 497.00000 22.67013 47.01680 0.04705 7.65306
           
Annual Sum or Average 5943.00000 23.70880 52.41242 0.03524 7.97651
Minimum of Months 454.00000 22.26338 44.15995 -0.2357 6.67194
Maximum of Months 514.00000 24.48754 58.47213 0.52987 11.95971



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 427.00000 22.76311 42.45182 0.05459 7.63674
February 385.00000 23.13417 46.10579 0.18502 8.53813
March 433.00000 23.46599 44.41118 0.27018 9.23977
April 410.00000 24.23394 51.85764 0.54051 12.10244
May 430.00000 24.58285 56.60341 -0.1033 7.12647
June 418.00000 24.52578 55.81284 -0.1154 6.77393
July 422.00000 24.66248 56.50021 -0.0697 7.23043
August 433.00000 24.50687 56.90351 -0.1311 6.91489
September 410.00000 24.53829 57.45870 -0.1472 7.51762
October 427.00000 24.38127 53.22000 0.60074 14.16586
November 417.00000 23.78515 47.16576 0.36732 9.17930
December 422.00000 22.97037 45.68563 0.13112 8.11518
           
Annual Sum or Average 5034.00000 23.96664 51.20209 0.13090 8.70790
Minimum of Months 385.00000 22.76311 42.45182 -0.1472 6.77393
Maximum of Months 433.00000 24.66248 57.45870 0.60074 14.16586



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.79181 39.69618 0.34449 10.10038
February 454.00000 23.85395 44.40423 0.39758 10.81330
March 514.00000 23.69844 44.21151 0.33657 9.66585
April 485.00000 24.18943 52.20917 0.52212 11.43790
May 508.00000 24.40605 57.42988 -0.2011 6.78535
June 496.00000 24.37008 56.61313 -0.2125 6.73814
July 497.00000 24.47664 57.40690 -0.1695 6.81739
August 514.00000 24.40635 57.24085 -0.1759 6.72384
September 485.00000 24.47639 57.51309 -0.1537 7.10825
October 502.00000 24.50055 52.15490 0.66886 15.74279
November 489.00000 24.34243 45.43569 0.55561 12.85119
December 497.00000 23.95797 42.99025 0.41971 11.41044
           
Annual Sum or Average 5943.00000 24.20706 50.64791 0.19165 9.66418
Minimum of Months 454.00000 23.69844 39.69618 -0.2125 6.72384
Maximum of Months 514.00000 24.50055 57.51309 0.66886 15.74279



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.89419 41.96979 0.09834 7.98574
February 454.00000 23.28023 45.87295 0.23818 9.48735
March 514.00000 23.54646 44.54210 0.30189 9.35257
April 485.00000 24.28762 51.68888 0.57596 12.91090
May 508.00000 24.47166 56.78720 -0.1298 6.67249
June 496.00000 24.46806 55.84734 -0.1150 6.64914
July 497.00000 24.57102 56.50887 -0.0842 6.87621
August 514.00000 24.46554 56.61751 -0.1109 6.61120
September 485.00000 24.46182 57.37317 -0.1465 7.00754
October 502.00000 24.36982 52.76330 0.61921 14.27318
November 489.00000 23.82496 47.06934 0.39410 9.56275
December 497.00000 23.24860 44.84962 0.21703 8.67779
           
Annual Sum or Average 5943.00000 23.99494 51.02031 0.15321 8.82402
Minimum of Months 454.00000 22.89419 41.96979 -0.1465 6.61120
Maximum of Months 514.00000 24.57102 57.37317 0.61921 14.27318



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 21.72349 45.90755 -0.2322 9.96799
February 454.00000 22.26167 49.54705 -0.0523 10.11290
March 514.00000 22.77569 47.16787 0.07295 8.94561
April 485.00000 23.85007 53.49753 0.42159 9.87485
May 508.00000 24.42619 57.40154 -0.1813 6.81849
June 496.00000 24.41619 56.24551 -0.1685 6.68289
July 497.00000 24.53388 57.14610 -0.1281 6.96600
August 514.00000 24.39813 57.51547 -0.1820 6.84097
September 485.00000 24.38955 58.67727 -0.2124 7.19772
October 502.00000 24.11306 54.63940 0.52052 12.38664
November 489.00000 23.03227 50.04808 0.16481 7.95960
December 497.00000 22.18961 48.83554 -0.0828 8.96533
           
Annual Sum or Average 5943.00000 23.51735 53.06833 -0.0056 8.54727
Minimum of Months 454.00000 21.72349 45.90755 -0.2322 6.68289
Maximum of Months 514.00000 24.53388 58.67727 0.52052 12.38664



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.24239 44.19161 -0.0815 8.70090
February 454.00000 22.75181 47.77018 0.09369 9.58912
March 514.00000 23.23193 45.41108 0.21545 9.83652
April 485.00000 24.09389 52.10946 0.52533 11.94185
May 508.00000 24.50154 56.48833 -0.0907 6.97103
June 496.00000 24.45991 55.59954 -0.0925 6.62989
July 497.00000 24.58744 56.26228 -0.0511 7.17754
August 514.00000 24.44162 56.74092 -0.1128 6.78284
September 485.00000 24.46203 57.56032 -0.1387 7.48055
October 502.00000 24.25097 53.44791 0.58970 14.23291
November 489.00000 23.53391 48.16560 0.30984 8.90015
December 497.00000 22.58701 47.33867 0.03078 8.76822
           
Annual Sum or Average 5943.00000 23.76838 51.77768 0.09883 8.90718
Minimum of Months 454.00000 22.24239 44.19161 -0.1387 6.62989
Maximum of Months 514.00000 24.58744 57.56032 0.58970 14.23291



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 23.35785 41.26345 0.21958 9.99579
February 454.00000 23.45883 45.74942 0.29298 11.10319
March 514.00000 23.38413 45.13779 0.25454 10.10262
April 485.00000 24.06455 52.55133 0.49624 11.27923
May 508.00000 24.42808 57.35867 -0.1758 6.81271
June 496.00000 24.39730 56.36670 -0.1828 6.73191
July 497.00000 24.52054 57.20073 -0.1346 6.97653
August 514.00000 24.42575 57.21021 -0.1501 6.76707
September 485.00000 24.48538 57.74959 -0.1340 7.29147
October 502.00000 24.44400 52.66137 0.66511 16.00929
November 489.00000 24.14361 46.16584 0.50138 12.27730
December 497.00000 23.57774 44.55123 0.31577 11.23723
           
Annual Sum or Average 5943.00000 24.06014 51.19724 0.16183 9.69694
Minimum of Months 454.00000 23.35785 41.26345 -0.1828 6.73191
Maximum of Months 514.00000 24.52054 57.74959 0.66511 16.00929



Table of Contents

Report: OccupantComfortDataSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%]
January 502.00000 22.37851 43.56076 -0.0396 8.98026
February 454.00000 22.84774 47.32127 0.12892 10.26888
March 514.00000 23.18313 45.48319 0.21212 9.72875
April 485.00000 24.15028 52.01589 0.54799 12.65398
May 508.00000 24.47560 56.74992 -0.1101 6.73342
June 496.00000 24.47476 55.66406 -0.0913 6.71207
July 497.00000 24.58687 56.36454 -0.0585 7.05571
August 514.00000 24.47546 56.59178 -0.0891 6.70117
September 485.00000 24.45602 57.61561 -0.1325 7.19964
October 502.00000 24.29247 53.29945 0.61028 14.48982
November 489.00000 23.48697 48.06857 0.31239 9.24579
December 497.00000 22.78814 46.51001 0.09860 9.13957
           
Annual Sum or Average 5943.00000 23.80546 51.62679 0.11462 9.05907
Minimum of Months 454.00000 22.37851 43.56076 -0.1325 6.70117
Maximum of Months 514.00000 24.58687 57.61561 0.61028 14.48982



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.493740E+11 121397.73 19-JAN-10:50 241.27 0.299688E+12 0.00 0.349062E+12 1.78 7.54 19-JAN-06:03 0.00 0.00
February 0.659877E+11 121685.67 24-FEB-13:10 303.18 0.410166E+12 0.00 0.476154E+12 2.55 7.52 28-FEB-06:02 0.00 0.00
March 0.831328E+11 151976.61 07-MAR-06:04 373.95 0.527083E+12 0.00 0.610215E+12 2.88 7.72 27-MAR-05:04 0.00 0.00
April 0.130919E+12 172874.55 29-APR-05:02 552.73 0.844256E+12 0.00 0.975175E+12 4.47 7.79 14-APR-05:04 0.00 0.00
May 0.193945E+12 220288.16 24-MAY-05:03 575.33 0.126510E+13 0.00 0.145905E+13 4.83 7.64 17-MAY-05:03 0.00 0.00
June 0.198666E+12 194350.28 29-JUN-05:02 626.02 0.127202E+13 0.00 0.147069E+13 5.24 7.69 08-JUN-05:02 0.00 0.00
July 0.209246E+12 218476.13 31-JUL-05:04 678.07 0.130879E+13 0.00 0.151804E+13 5.32 7.39 17-JUL-05:02 0.00 0.00
August 0.210491E+12 201022.27 01-AUG-05:04 696.96 0.133789E+13 0.00 0.154838E+13 5.51 7.52 17-AUG-05:02 0.00 0.00
September 0.188506E+12 208490.59 12-SEP-05:02 558.20 0.122160E+13 0.00 0.141011E+13 4.83 7.72 22-SEP-05:02 0.00 0.00
October 0.167602E+12 210125.99 25-OCT-05:02 567.44 0.107501E+13 0.00 0.124261E+13 4.56 7.69 03-OCT-05:02 0.00 0.00
November 0.104293E+12 181705.25 02-NOV-05:02 444.21 0.659003E+12 0.00 0.763297E+12 3.54 7.75 08-NOV-06:04 0.00 0.00
December 0.720656E+11 183059.78 15-DEC-06:04 340.09 0.453448E+12 0.00 0.525514E+12 2.56 7.78 14-DEC-06:03 0.00 0.00
                         
Annual Sum or Average 0.167423E+13     5957.46 0.106741E+14 0.00 0.123483E+14 4.01     0.00 0.00
Minimum of Months 0.493740E+11 121397.73   241.27 0.299688E+12 0.00 0.349062E+12 1.78 7.39   0.00 0.00
Maximum of Months 0.210491E+12 220288.16   696.96 0.133789E+13 0.00 0.154838E+13 5.51 7.79   0.00 0.00



Table of Contents

Report: ChillerReportMonthly

For: COOLSYS1 CHILLER2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

CHILLER ELECTRICITY ENERGY [J] CHILLER ELECTRICITY RATE {Maximum} [W] CHILLER ELECTRICITY RATE {TIMESTAMP} CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] CHILLER EVAPORATOR COOLING ENERGY [J] CHILLER EVAPORATOR COOLING RATE [] CHILLER CONDENSER HEAT TRANSFER ENERGY [J] CHILLER COP [W/W] CHILLER COP {Maximum} [W/W] CHILLER COP {TIMESTAMP} CHILLER PART LOAD RATIO [] CHILLER PART LOAD RATIO []
January 0.247809E+10 121397.73 19-JAN-10:50 6.04 0.174406E+11 0.00 0.199187E+11 0.06 7.54 19-JAN-06:03 0.00 0.00
February 0.535638E+10 121685.67 24-FEB-13:10 13.18 0.380766E+11 0.00 0.434330E+11 0.14 7.52 28-FEB-06:02 0.00 0.00
March 0.394873E+10 151976.61 07-MAR-06:04 9.57 0.275343E+11 0.00 0.314830E+11 0.09 7.72 27-MAR-05:04 0.00 0.00
April 0.123459E+11 172874.55 29-APR-05:02 29.39 0.855380E+11 0.00 0.978839E+11 0.28 7.79 14-APR-05:04 0.00 0.00
May 0.666471E+11 220288.16 24-MAY-05:03 154.28 0.452499E+12 0.00 0.519146E+12 1.41 7.64 17-MAY-05:03 0.00 0.00
June 0.711357E+11 194350.28 29-JUN-05:02 162.78 0.476925E+12 0.00 0.548061E+12 1.52 7.69 08-JUN-05:02 0.00 0.00
July 0.734434E+11 218476.13 31-JUL-05:04 166.19 0.486224E+12 0.00 0.559667E+12 1.48 7.39 17-JUL-05:02 0.00 0.00
August 0.828367E+11 201022.27 01-AUG-05:04 188.64 0.551777E+12 0.00 0.634614E+12 1.69 7.52 17-AUG-05:02 0.00 0.00
September 0.597492E+11 208490.59 12-SEP-05:02 138.10 0.403211E+12 0.00 0.462960E+12 1.29 7.72 22-SEP-05:02 0.00 0.00
October 0.523297E+11 210125.99 25-OCT-05:02 119.89 0.354909E+12 0.00 0.407238E+12 1.09 7.69 03-OCT-05:02 0.00 0.00
November 0.162195E+11 181705.25 02-NOV-05:02 37.41 0.111134E+12 0.00 0.127354E+12 0.36 7.75 08-NOV-06:04 0.00 0.00
December 0.857686E+10 183059.78 15-DEC-06:04 20.23 0.592970E+11 0.00 0.678738E+11 0.19 7.78 14-DEC-06:03 0.00 0.00
                         
Annual Sum or Average 0.455067E+12     1045.70 0.306457E+13 0.00 0.351963E+13 0.80     0.00 0.00
Minimum of Months 0.247809E+10 121397.73   6.04 0.174406E+11 0.00 0.199187E+11 0.06 7.39   0.00 0.00
Maximum of Months 0.828367E+11 220288.16   188.64 0.551777E+12 0.00 0.634614E+12 1.69 7.79   0.00 0.00



Table of Contents

Report: TowerReportMonthly

For: CENTRAL TOWER

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.672863E+11 744.00 49248.27 01-JAN-00:05 227032.29 31-JAN-16:20 23.28 19.57 14.18
February 0.920280E+11 672.00 49248.27 01-FEB-00:10 380509.02 24-FEB-14:20 27.42 20.76 14.18
March 0.116885E+12 744.00 49248.27 01-MAR-00:10 624442.19 31-MAR-24:00 32.12 22.53 14.18
April 0.127346E+12 720.00 49248.27 01-APR-00:10 706303.92 28-APR-17:20 39.64 26.90 14.18
May 0.131907E+12 744.00 49248.27 01-MAY-00:05 343014.06 31-MAY-23:40 33.12 28.80 14.18
June 0.127652E+12 720.00 49248.27 01-JUN-00:10 495852.93 30-JUN-23:43 38.28 30.88 14.18
July 0.131907E+12 744.00 49248.27 01-JUL-00:03 648110.58 31-JUL-23:53 43.05 32.59 14.18
August 0.131907E+12 744.00 49248.27 01-AUG-00:03 712405.50 06-AUG-15:31 46.69 33.39 14.18
September 0.127652E+12 720.00 49248.27 01-SEP-00:05 342735.80 30-SEP-23:50 32.49 28.14 14.18
October 0.129909E+12 744.00 49248.27 01-OCT-00:10 483716.75 31-OCT-24:00 34.73 27.51 14.18
November 0.120732E+12 720.00 49248.27 01-NOV-00:10 552738.27 01-NOV-14:20 33.51 23.75 14.18
December 0.117204E+12 744.00 49248.27 01-DEC-00:10 687667.28 13-DEC-17:10 34.99 22.62 14.18
                   
Annual Sum or Average 0.142241E+13 8760.00         34.99 26.49 14.18
Minimum of Months 0.672863E+11 672.00 49248.27   227032.29   23.28 19.57 14.18
Maximum of Months 0.131907E+12 744.00 49248.27   712405.50   46.69 33.39 14.18



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.499659E+10 176.28 22319.10 02-JAN-10:40 1202221.34 02-JAN-13:30 21.61 21.16 21.49
February 0.647430E+10 242.24 22319.10 01-FEB-13:00 1164302.07 27-FEB-09:50 22.00 21.33 31.36
March 0.915374E+10 293.26 22319.10 06-MAR-06:04 1329907.79 24-MAR-16:00 22.08 21.30 34.52
April 0.203082E+11 472.38 22319.10 01-APR-04:03 1421570.61 18-APR-14:15 22.94 21.66 55.14
May 0.455160E+11 575.33 22319.10 01-MAY-01:07 1361955.28 22-MAY-05:05 26.01 24.24 57.75
June 0.488779E+11 625.91 22319.10 01-JUN-03:02 1289408.92 08-JUN-05:04 26.35 24.49 63.05
July 0.544825E+11 678.07 22319.10 01-JUL-00:03 1428077.42 31-JUL-05:04 27.32 25.48 63.97
August 0.549568E+11 695.12 22319.10 01-AUG-00:10 1167900.29 29-AUG-05:03 26.71 24.83 67.51
September 0.444077E+11 558.20 22319.10 01-SEP-00:05 1324031.10 05-SEP-05:04 26.57 24.80 56.06
October 0.343425E+11 539.79 22319.10 02-OCT-09:20 1353980.04 11-OCT-05:04 24.92 23.38 54.51
November 0.131339E+11 360.72 22319.10 01-NOV-00:53 1220823.05 08-NOV-06:04 22.68 21.69 43.09
December 0.995309E+10 261.54 22319.10 08-DEC-11:10 1183432.82 08-DEC-12:00 22.01 21.35 31.24
                   
Annual Sum or Average 0.346603E+12 5478.85         24.28 22.99 48.38
Minimum of Months 0.499659E+10 176.28 22319.10   1164302.07   21.61 21.16 21.49
Maximum of Months 0.549568E+11 695.12 22319.10   1428077.42   27.32 25.48 67.51



Table of Contents

Report: TowerReportMonthly

For: TOWERWATERSYS COOLTOWER 2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING TOWER FAN ELECTRICITY ENERGY [J] COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} COOLING TOWER INLET TEMPERATURE [C] COOLING TOWER OUTLET TEMPERATURE [C] COOLING TOWER MASS FLOW RATE [kg/s]
January 0.495484E+09 6.17 22319.10 18-JAN-15:00 1033424.11 19-JAN-10:50 21.61 21.58 0.63
February 0.101775E+10 12.67 22319.10 02-FEB-13:20 1020541.85 28-FEB-13:20 22.00 21.94 1.43
March 0.771348E+09 9.60 22319.10 06-MAR-06:04 1229808.57 27-MAR-05:04 22.08 22.04 0.98
April 0.288918E+10 36.04 22319.10 07-APR-05:04 1421570.61 18-APR-14:15 22.94 22.80 3.76
May 0.165328E+11 205.76 22319.10 01-MAY-03:02 1361955.28 22-MAY-05:05 26.01 25.21 19.94
June 0.197411E+11 245.69 22319.10 01-JUN-03:02 1289408.92 08-JUN-05:04 26.35 25.37 22.84
July 0.243405E+11 302.94 22319.10 01-JUL-03:02 1428077.42 31-JUL-05:04 27.32 26.20 25.61
August 0.236502E+11 294.34 22319.10 01-AUG-05:02 1167900.29 29-AUG-05:03 26.71 25.60 26.34
September 0.177636E+11 221.08 22319.10 01-SEP-03:02 1324031.10 05-SEP-05:04 26.57 25.73 20.42
October 0.150020E+11 186.71 22319.10 02-OCT-09:50 1353980.04 11-OCT-05:04 24.92 24.21 16.40
November 0.356592E+10 44.38 22319.10 01-NOV-04:03 1220823.05 08-NOV-06:04 22.68 22.49 4.50
December 0.170473E+10 21.22 22319.10 11-DEC-10:20 1156703.20 15-DEC-06:04 22.01 21.92 2.17
                   
Annual Sum or Average 0.127475E+12 1586.59         24.28 23.77 12.16
Minimum of Months 0.495484E+09 6.17 22319.10   1020541.85   21.61 21.58 0.63
Maximum of Months 0.243405E+11 302.94 22319.10   1428077.42   27.32 26.20 26.34



Table of Contents

Report: BoilerReportMonthly

For: HEATSYS1 BOILER

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO {Maximum} [] BOILER PART LOAD RATIO {TIMESTAMP}
January 0.121505E+11 0.00 173.51 835681.10 10-JAN-06:02 0.00 32.58 44.23 0.02 0.00 0.00 0.53 10-JAN-06:02
February 0.649651E+10 0.00 90.70 846264.83 06-FEB-06:01 0.00 26.00 32.77 0.01 0.00 0.00 0.54 06-FEB-06:01
March 0.562852E+10 0.00 65.11 580033.84 11-MAR-06:03 0.00 29.81 34.41 0.01 0.00 0.00 0.37 11-MAR-06:03
April 0.223118E+09 0.00 9.42 45413.30 18-APR-14:30 0.00 49.38 49.80 0.00 0.00 0.00 0.03 18-APR-14:30
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 58.89 58.89 0.00 0.00 0.00 0.00 01-MAY-00:05
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 58.89 58.89 0.00 0.00 0.00 0.00 01-JUN-00:10
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 58.89 58.89 0.00 0.00 0.00 0.00 01-JUL-00:03
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 58.89 58.89 0.00 0.00 0.00 0.00 01-AUG-00:03
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 58.89 58.89 0.00 0.00 0.00 0.00 01-SEP-00:05
October 7548505.89 0.00 4.33 1092.29 28-OCT-06:40 0.00 58.44 58.57 0.00 0.00 0.00 0.00 28-OCT-06:40
November 0.189057E+09 0.00 21.94 44092.98 27-NOV-14:20 0.00 45.66 46.78 0.00 0.00 0.00 0.03 27-NOV-14:20
December 0.823094E+10 0.00 123.16 852257.95 21-DEC-06:01 0.00 27.01 35.71 0.01 0.00 0.00 0.54 21-DEC-06:01
                           
Annual Sum or Average 0.329262E+11 0.00 488.17     0.00 47.05 49.82 0.01 0.00 0.00    
Minimum of Months 0.00 0.00 0.00 0.00   0.00 26.00 32.77 0.00 0.00 0.00 0.00  
Maximum of Months 0.121505E+11 0.00 173.51 852257.95   0.00 58.89 58.89 0.02 0.00 0.00 0.54  



Table of Contents

Report: BoilerReportMonthly

For: CENTRAL BOILER

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

BOILER HEATING ENERGY [J] BOILER GAS CONSUMPTION [] BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] BOILER HEATING RATE {Maximum} [W] BOILER HEATING RATE {TIMESTAMP} BOILER GAS CONSUMPTION RATE [] BOILER INLET TEMPERATURE [C] BOILER OUTLET TEMPERATURE [C] BOILER MASS FLOW RATE [kg/s] BOILER ANCILLARY ELECTRICITY RATE [W] BOILER PART LOAD RATIO [] BOILER PART LOAD RATIO []
January 0.00 0.00 0.00 0.00 01-JAN-00:05 0.00 23.28 23.28 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 01-FEB-00:10 0.00 27.42 27.42 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 01-MAR-00:10 0.00 32.12 32.12 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 01-APR-00:10 0.00 39.64 39.64 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 01-MAY-00:05 0.00 33.12 33.12 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 01-JUN-00:10 0.00 38.28 38.28 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 01-JUL-00:03 0.00 43.05 43.05 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 01-AUG-00:03 0.00 46.69 46.69 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 01-SEP-00:05 0.00 32.49 32.49 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 01-OCT-00:10 0.00 34.73 34.73 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 01-NOV-00:10 0.00 33.51 33.51 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 01-DEC-00:10 0.00 34.99 34.99 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.00 0.00 0.00     0.00 34.99 34.99 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00   0.00 23.28 23.28 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00   0.00 46.69 46.69 0.00 0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.342391E+11 0.00 218.17 0.265937E+11 0.00 0.00 0.00 0.00 168799.79 19-JAN-06:03 116493.73 19-JAN-06:03 0.00 0.00 0.00
February 0.488738E+11 0.00 283.99 0.366752E+11 0.00 0.00 0.00 0.00 180386.99 28-FEB-06:02 98737.65 27-FEB-16:20 0.00 0.00 0.00
March 0.651581E+11 0.00 359.62 0.542407E+11 0.00 0.00 0.00 0.00 208959.66 07-MAR-06:02 150596.70 06-MAR-06:02 0.00 0.00 0.00
April 0.109851E+12 0.00 537.65 0.928891E+11 0.00 0.00 0.00 0.00 206446.93 29-APR-05:02 147285.91 18-APR-13:55 0.00 0.00 0.00
May 0.150401E+12 0.00 540.49 0.122674E+12 0.00 0.00 0.00 0.00 232449.88 24-MAY-03:02 154576.84 30-MAY-05:02 0.00 0.00 0.00
June 0.162738E+12 0.00 588.26 0.134790E+12 0.00 0.00 0.00 0.00 220574.81 28-JUN-05:02 153773.02 28-JUN-05:02 0.00 0.00 0.00
July 0.176160E+12 0.00 632.74 0.143564E+12 0.00 0.00 0.00 0.00 223397.89 03-JUL-05:02 159961.74 24-JUL-05:04 0.00 0.00 0.00
August 0.193773E+12 0.00 657.63 0.159654E+12 0.00 0.00 0.00 0.00 224764.42 21-AUG-05:03 158800.86 21-AUG-05:03 0.00 0.00 0.00
September 0.149166E+12 0.00 524.48 0.115876E+12 0.00 0.00 0.00 0.00 229700.99 05-SEP-03:02 153305.26 11-SEP-05:03 0.00 0.00 0.00
October 0.137372E+12 0.00 535.84 0.113254E+12 0.00 0.00 0.00 0.00 221490.55 06-OCT-05:02 154122.79 10-OCT-05:03 0.00 0.00 0.00
November 0.805258E+11 0.00 423.09 0.678669E+11 0.00 0.00 0.00 0.00 208890.27 02-NOV-05:02 146522.41 02-NOV-05:02 0.00 0.00 0.00
December 0.590780E+11 0.00 317.73 0.483666E+11 0.00 0.00 0.00 0.00 208236.56 16-DEC-06:02 144691.07 12-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.136734E+13 0.00 5619.68 0.111644E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.342391E+11 0.00 218.17 0.265937E+11 0.00 0.00 0.00 0.00 168799.79   98737.65   0.00 0.00 0.00
Maximum of Months 0.193773E+12 0.00 657.63 0.159654E+12 0.00 0.00 0.00 0.00 232449.88   159961.74   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.267454E+12 0.00 207.32 0.202814E+12 0.00 0.00 0.00 0.00 1454570.34 19-JAN-06:03 902346.59 02-JAN-15:10 0.00 0.00 0.00
February 0.378432E+12 0.00 265.66 0.278911E+12 0.00 0.00 0.00 0.00 1515309.23 28-FEB-06:02 826335.64 27-FEB-16:20 0.00 0.00 0.00
March 0.479486E+12 0.00 315.29 0.384419E+12 0.00 0.00 0.00 0.00 2053829.77 07-MAR-06:02 1309335.07 07-MAR-06:02 0.00 0.00 0.00
April 0.794848E+12 0.00 409.30 0.645535E+12 0.00 0.00 0.00 0.00 2047377.13 26-APR-05:03 1353741.78 24-APR-05:03 0.00 0.00 0.00
May 0.135751E+13 0.00 494.89 0.106824E+13 0.00 0.00 0.00 0.00 2591312.84 22-MAY-03:02 1410317.62 01-MAY-05:02 0.00 0.00 0.00
June 0.139215E+13 0.00 504.49 0.110351E+13 0.00 0.00 0.00 0.00 2177070.60 19-JUN-03:02 1431312.10 28-JUN-05:02 0.00 0.00 0.00
July 0.143176E+13 0.00 520.44 0.108864E+13 0.00 0.00 0.00 0.00 2254851.86 26-JUL-05:03 1434920.18 05-JUL-05:02 0.00 0.00 0.00
August 0.148707E+13 0.00 515.82 0.113376E+13 0.00 0.00 0.00 0.00 2404068.81 15-AUG-03:02 1416564.29 21-AUG-05:02 0.00 0.00 0.00
September 0.131486E+13 0.00 481.53 0.967551E+12 0.00 0.00 0.00 0.00 2751506.84 05-SEP-03:02 1423298.66 01-SEP-05:03 0.00 0.00 0.00
October 0.113814E+13 0.00 458.70 0.887973E+12 0.00 0.00 0.00 0.00 2282805.22 07-OCT-03:02 1419532.00 10-OCT-03:02 0.00 0.00 0.00
November 0.606307E+12 0.00 373.33 0.491463E+12 0.00 0.00 0.00 0.00 2124444.42 01-NOV-05:03 1357596.17 04-NOV-05:03 0.00 0.00 0.00
December 0.412523E+12 0.00 258.12 0.317558E+12 0.00 0.00 0.00 0.00 2076060.99 15-DEC-06:02 1325051.51 15-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.110606E+14 0.00 4804.89 0.857037E+13 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.267454E+12 0.00 207.32 0.202814E+12 0.00 0.00 0.00 0.00 1454570.34   826335.64   0.00 0.00 0.00
Maximum of Months 0.148707E+13 0.00 520.44 0.113376E+13 0.00 0.00 0.00 0.00 2751506.84   1434920.18   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.257704E+11 0.00 202.19 0.192649E+11 0.00 0.00 0.00 0.00 143803.00 19-JAN-06:03 89372.11 19-JAN-15:50 0.00 0.00 0.00
February 0.378887E+11 0.00 260.53 0.281386E+11 0.00 0.00 0.00 0.00 139287.12 28-FEB-06:02 96002.11 27-FEB-15:50 0.00 0.00 0.00
March 0.493188E+11 0.00 307.61 0.395297E+11 0.00 0.00 0.00 0.00 195943.60 27-MAR-05:02 125380.04 30-MAR-05:03 0.00 0.00 0.00
April 0.847841E+11 0.00 404.28 0.696855E+11 0.00 0.00 0.00 0.00 220697.29 29-APR-05:02 140539.13 29-APR-05:02 0.00 0.00 0.00
May 0.150982E+12 0.00 504.10 0.120857E+12 0.00 0.00 0.00 0.00 265803.82 22-MAY-03:02 153948.02 22-MAY-03:02 0.00 0.00 0.00
June 0.157677E+12 0.00 514.80 0.127809E+12 0.00 0.00 0.00 0.00 243274.61 30-JUN-03:02 155107.09 21-JUN-03:02 0.00 0.00 0.00
July 0.162030E+12 0.00 534.63 0.126017E+12 0.00 0.00 0.00 0.00 251496.59 26-JUL-03:02 153917.38 26-JUL-03:02 0.00 0.00 0.00
August 0.165969E+12 0.00 529.55 0.129198E+12 0.00 0.00 0.00 0.00 259936.57 11-AUG-03:02 153441.95 23-AUG-03:02 0.00 0.00 0.00
September 0.142064E+12 0.00 485.39 0.106046E+12 0.00 0.00 0.00 0.00 296074.12 05-SEP-03:02 152072.83 07-SEP-03:02 0.00 0.00 0.00
October 0.122309E+12 0.00 459.64 0.966161E+11 0.00 0.00 0.00 0.00 256083.09 25-OCT-03:02 153030.58 25-OCT-03:02 0.00 0.00 0.00
November 0.594080E+11 0.00 364.91 0.482725E+11 0.00 0.00 0.00 0.00 218228.23 02-NOV-05:02 140363.44 02-NOV-05:02 0.00 0.00 0.00
December 0.397464E+11 0.00 251.64 0.302889E+11 0.00 0.00 0.00 0.00 183256.79 15-DEC-06:02 113090.48 15-DEC-06:02 0.00 0.00 0.00
                               
Annual Sum or Average 0.119795E+13 0.00 4819.27 0.941723E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.257704E+11 0.00 202.19 0.192649E+11 0.00 0.00 0.00 0.00 139287.12   89372.11   0.00 0.00 0.00
Maximum of Months 0.165969E+12 0.00 534.63 0.129198E+12 0.00 0.00 0.00 0.00 296074.12   155107.09   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION [] COOLING COIL RUNTIME FRACTION [] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE [] COOLING COIL ELECTRICITY RATE [] COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.218968E+11 0.00 150.82 0.169084E+11 0.00 0.00 0.00 0.00 119639.89 01-JAN-16:12 98091.48 01-JAN-16:12 0.00 0.00 0.00
February 0.263542E+11 0.00 199.37 0.215636E+11 0.00 0.00 0.00 0.00 109905.30 03-FEB-06:03 97462.06 21-FEB-04:02 0.00 0.00 0.00
March 0.354979E+11 0.00 239.76 0.300986E+11 0.00 0.00 0.00 0.00 139139.19 07-MAR-04:03 93382.55 06-MAR-05:23 0.00 0.00 0.00
April 0.562278E+11 0.00 350.29 0.488070E+11 0.00 0.00 0.00 0.00 141680.75 29-APR-04:03 87614.99 24-APR-03:04 0.00 0.00 0.00
May 0.103677E+12 0.00 438.17 0.800205E+11 0.00 0.00 0.00 0.00 173131.55 22-MAY-03:02 91011.86 30-MAY-03:02 0.00 0.00 0.00
June 0.108815E+12 0.00 429.98 0.815867E+11 0.00 0.00 0.00 0.00 172825.55 19-JUN-03:02 91753.22 12-JUN-03:02 0.00 0.00 0.00
July 0.117942E+12 0.00 429.38 0.834478E+11 0.00 0.00 0.00 0.00 160889.34 17-JUL-03:02 90979.62 18-JUL-03:02 0.00 0.00 0.00
August 0.130714E+12 0.00 476.88 0.949890E+11 0.00 0.00 0.00 0.00 169304.83 06-AUG-14:12 93931.14 21-AUG-00:53 0.00 0.00 0.00
September 0.110906E+12 0.00 445.55 0.810925E+11 0.00 0.00 0.00 0.00 169974.94 17-SEP-14:20 94109.91 05-SEP-03:02 0.00 0.00 0.00
October 0.953928E+11 0.00 419.04 0.734004E+11 0.00 0.00 0.00 0.00 168365.14 08-OCT-14:58 95306.42 01-OCT-15:22 0.00 0.00 0.00
November 0.523303E+11 0.00 308.20 0.433700E+11 0.00 0.00 0.00 0.00 143605.32 03-NOV-03:02 94017.72 05-NOV-15:30 0.00 0.00 0.00
December 0.342941E+11 0.00 208.44 0.277316E+11 0.00 0.00 0.00 0.00 137277.76 10-DEC-15:20 95889.66 10-DEC-15:20 0.00 0.00 0.00
                               
Annual Sum or Average 0.894049E+12 0.00 4095.88 0.683016E+12 0.00 0.00 0.00 0.00         0.00 0.00 0.00
Minimum of Months 0.218968E+11 0.00 150.82 0.169084E+11 0.00 0.00 0.00 0.00 109905.30   87614.99   0.00 0.00 0.00
Maximum of Months 0.130714E+12 0.00 476.88 0.949890E+11 0.00 0.00 0.00 0.00 173131.55   98091.48   0.00 0.00 0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.331718E+12 0.857884E+11 744.00 0.329000E+12 0.271843E+10 0.00 0.37 19-JAN-12:00 0.31 21-JAN-07:10 136409.24 31-JAN-16:40 128368.54 02-JAN-15:00 9993.42 31-JAN-17:00 44156.01 02-JAN-15:00 0.00
February 0.522753E+12 0.132873E+12 672.00 0.517891E+12 0.486193E+10 0.00 0.60 24-FEB-13:50 0.52 13-FEB-07:20 227508.79 24-FEB-16:50 218743.41 24-FEB-13:10 9718.32 24-FEB-17:10 76378.79 02-FEB-13:10 0.00
March 0.823430E+12 0.212843E+12 744.00 0.818567E+12 0.486294E+10 0.00 0.95 31-MAR-24:00 0.72 15-MAR-07:00 393952.00 31-MAR-24:00 393952.00 31-MAR-24:00 11308.23 07-MAR-15:00 111275.29 30-MAR-13:00 0.00
April 0.103628E+13 0.290624E+12 720.00 0.103012E+13 0.616229E+10 0.00 1.00 03-APR-13:30 0.37 30-APR-23:55 422269.30 28-APR-18:00 404198.58 18-APR-16:50 18479.12 28-APR-18:00 147537.14 28-APR-15:00 0.00
May 0.349000E+12 0.116550E+12 744.00 0.336384E+12 0.126161E+11 0.00 0.56 31-MAY-23:20 0.34 07-MAY-01:00 212762.30 31-MAY-23:10 211053.36 31-MAY-24:00 14568.64 23-MAY-16:00 63138.09 31-MAY-23:20 0.00
June 0.576229E+12 0.193659E+12 720.00 0.562358E+12 0.138713E+11 0.00 0.78 30-JUN-23:35 0.55 01-JUN-05:00 302726.56 30-JUN-23:03 302698.94 30-JUN-23:57 17736.67 29-JUN-15:00 94851.73 30-JUN-23:20 0.00
July 0.842408E+12 0.284092E+12 744.00 0.827501E+12 0.149065E+11 0.00 0.99 31-JUL-23:23 0.78 01-JUL-01:30 395008.21 31-JUL-23:53 395008.21 31-JUL-23:53 16618.81 12-JUL-12:50 134005.95 21-JUL-16:00 0.00
August 0.108075E+13 0.352864E+12 744.00 0.106732E+13 0.134305E+11 0.00 1.00 01-AUG-06:40 0.39 31-AUG-24:00 424437.60 07-AUG-14:00 410412.81 06-AUG-15:55 20710.88 07-AUG-14:00 155030.22 30-AUG-16:00 0.00
September 0.342098E+12 0.111896E+12 720.00 0.328554E+12 0.135440E+11 0.00 0.55 30-SEP-23:20 0.34 22-SEP-06:10 213274.21 30-SEP-24:00 212005.73 30-SEP-24:00 14066.39 18-SEP-10:40 62453.15 30-SEP-23:20 0.00
October 0.593623E+12 0.183038E+12 744.00 0.582774E+12 0.108490E+11 0.00 0.76 31-OCT-24:00 0.53 17-OCT-07:00 304073.58 31-OCT-24:00 304073.58 31-OCT-24:00 15961.13 24-OCT-09:00 91339.71 05-OCT-15:00 0.00
November 0.804250E+12 0.214475E+12 720.00 0.798245E+12 0.600517E+10 0.00 0.84 02-NOV-13:10 0.72 15-NOV-07:10 324540.11 03-NOV-16:00 312644.47 03-NOV-14:00 12829.72 03-NOV-16:10 114382.62 02-NOV-13:00 0.00
December 0.107079E+13 0.267171E+12 744.00 0.106704E+13 0.374641E+10 0.00 1.00 07-DEC-13:20 0.91 18-DEC-07:20 416142.25 13-DEC-18:00 403726.83 13-DEC-18:00 13034.76 11-DEC-15:10 138753.65 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.837333E+13 0.244587E+13 8760.00 0.826575E+13 0.107575E+12 0.00                         0.00
Minimum of Months 0.331718E+12 0.857884E+11 672.00 0.328554E+12 0.271843E+10 0.00 0.37   0.31   136409.24   128368.54   9718.32   44156.01   0.00
Maximum of Months 0.108075E+13 0.352864E+12 744.00 0.106732E+13 0.149065E+11 0.00 1.00   0.91   424437.60   410412.81   20710.88   155030.22   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.522595E+10 0.135569E+10 744.00 0.511722E+10 0.108729E+09 0.00 0.34 19-JAN-17:00 0.15 05-JAN-08:00 2815.04 19-JAN-17:00 2573.79 01-JAN-17:30 400.79 31-JAN-17:00 829.76 02-JAN-15:00 0.00
February 0.963334E+10 0.242875E+10 672.00 0.944020E+10 0.193142E+09 0.00 0.57 27-FEB-17:00 0.39 17-FEB-07:10 4743.07 27-FEB-17:00 4636.94 26-FEB-17:47 398.40 24-FEB-17:00 1475.09 02-FEB-13:10 0.00
March 0.158168E+11 0.403685E+10 744.00 0.156121E+11 0.204692E+09 0.00 0.87 31-MAR-24:00 0.60 11-MAR-18:00 7719.06 31-MAR-24:00 7719.06 31-MAR-24:00 481.49 07-MAR-15:00 2204.21 30-MAR-13:00 0.00
April 0.205463E+11 0.567964E+10 720.00 0.202581E+11 0.288232E+09 0.00 1.00 21-APR-16:00 0.31 30-APR-23:55 8661.28 28-APR-17:20 8427.98 16-APR-18:06 556.82 28-APR-17:30 3096.05 28-APR-15:00 0.00
May 0.656738E+10 0.213719E+10 744.00 0.606268E+10 0.504705E+09 0.00 0.50 31-MAY-23:20 0.26 13-MAY-06:10 4098.04 31-MAY-23:10 4013.58 31-MAY-24:00 555.62 23-MAY-16:00 1187.25 31-MAY-23:20 0.00
June 0.113496E+11 0.371859E+10 720.00 0.107689E+11 0.580682E+09 0.00 0.70 30-JUN-23:43 0.48 01-JUN-06:00 5880.12 30-JUN-23:43 5866.74 30-JUN-23:57 686.13 29-JUN-15:00 1869.01 29-JUN-14:00 0.00
July 0.168360E+11 0.554200E+10 744.00 0.161843E+11 0.651725E+09 0.00 0.90 31-JUL-23:45 0.70 11-JUL-21:20 7743.94 31-JUL-23:57 7743.94 31-JUL-23:57 666.48 12-JUL-10:00 2734.19 21-JUL-16:00 0.00
August 0.219447E+11 0.711090E+10 744.00 0.212887E+11 0.655960E+09 0.00 1.00 01-AUG-09:40 0.33 31-AUG-24:00 8920.93 07-AUG-13:50 8310.67 06-AUG-17:55 741.27 07-AUG-13:40 3253.07 30-AUG-16:00 0.00
September 0.639852E+10 0.203724E+10 720.00 0.585585E+10 0.542676E+09 0.00 0.49 30-SEP-24:00 0.26 28-SEP-06:10 4072.46 30-SEP-24:00 4041.72 30-SEP-24:00 585.39 18-SEP-14:30 1169.12 30-SEP-23:20 0.00
October 0.115026E+11 0.347400E+10 744.00 0.110511E+11 0.451561E+09 0.00 0.69 31-OCT-24:00 0.43 28-OCT-07:00 5896.72 31-OCT-24:00 5888.35 31-OCT-24:00 685.51 24-OCT-14:10 1840.31 05-OCT-15:00 0.00
November 0.155902E+11 0.409321E+10 720.00 0.153395E+11 0.250694E+09 0.00 0.80 02-NOV-16:00 0.62 15-NOV-07:10 6812.59 07-NOV-16:40 6469.19 06-NOV-17:00 560.94 01-NOV-11:00 2285.07 01-NOV-14:00 0.00
December 0.208571E+11 0.514964E+10 744.00 0.206805E+11 0.176594E+09 0.00 1.00 15-DEC-16:40 0.78 20-DEC-07:20 8752.63 14-DEC-17:00 8352.59 10-DEC-16:54 565.24 12-DEC-15:00 2895.89 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.162269E+12 0.467637E+11 8760.00 0.157659E+12 0.460939E+10 0.00                         0.00
Minimum of Months 0.522595E+10 0.135569E+10 672.00 0.511722E+10 0.108729E+09 0.00 0.34   0.15   2815.04   2573.79   398.40   829.76   0.00
Maximum of Months 0.219447E+11 0.711090E+10 744.00 0.212887E+11 0.655960E+09 0.00 1.00   0.78   8920.93   8427.98   741.27   3253.07   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.402077E+11 0.106336E+11 744.00 0.391491E+11 0.105860E+10 0.00 0.34 19-JAN-17:00 0.07 10-JAN-07:10 26479.92 19-JAN-17:00 22891.68 19-JAN-17:00 3954.27 31-JAN-17:00 7741.99 19-JAN-16:50 0.00
February 0.845363E+11 0.215230E+11 672.00 0.826269E+11 0.190945E+10 0.00 0.56 27-FEB-17:00 0.30 06-FEB-07:10 45068.26 27-FEB-17:00 42699.93 26-FEB-17:54 3960.27 24-FEB-17:00 13904.43 02-FEB-13:10 0.00
March 0.145211E+12 0.373124E+11 744.00 0.143172E+12 0.203927E+10 0.00 0.87 31-MAR-24:00 0.52 13-MAR-06:55 72714.50 31-MAR-24:00 72714.50 31-MAR-24:00 4800.87 07-MAR-15:00 21090.65 30-MAR-13:00 0.00
April 0.195032E+12 0.539815E+11 720.00 0.192146E+12 0.288524E+10 0.00 1.00 21-APR-16:00 0.29 30-APR-23:55 82671.37 28-APR-17:20 79528.48 16-APR-18:06 5549.13 28-APR-17:30 29508.13 28-APR-15:00 0.00
May 0.616944E+11 0.200938E+11 744.00 0.566988E+11 0.499564E+10 0.00 0.49 31-MAY-23:20 0.25 13-MAY-06:10 38933.34 31-MAY-23:10 38009.77 31-MAY-24:00 5486.69 23-MAY-16:00 11274.55 31-MAY-23:20 0.00
June 0.108247E+12 0.354574E+11 720.00 0.102466E+12 0.578103E+10 0.00 0.72 30-JUN-23:53 0.47 07-JUN-06:10 57115.28 30-JUN-23:53 56979.50 30-JUN-23:57 6809.05 29-JUN-15:00 17923.87 29-JUN-14:00 0.00
July 0.160671E+12 0.528726E+11 744.00 0.154167E+12 0.650356E+10 0.00 0.91 31-JUL-23:53 0.69 11-JUL-21:20 74523.99 31-JUL-23:57 74523.99 31-JUL-23:57 6657.80 12-JUL-10:00 26150.61 21-JUL-16:00 0.00
August 0.208488E+12 0.675803E+11 744.00 0.201930E+12 0.655838E+10 0.00 1.00 01-AUG-09:10 0.30 31-AUG-24:00 84741.14 07-AUG-13:50 77816.05 03-AUG-18:00 7368.24 07-AUG-13:40 31001.50 30-AUG-16:00 0.00
September 0.592091E+11 0.188865E+11 720.00 0.538525E+11 0.535660E+10 0.00 0.49 30-SEP-24:00 0.24 28-SEP-06:10 38398.57 30-SEP-24:00 38082.00 30-SEP-24:00 5824.50 18-SEP-14:30 11026.43 30-SEP-23:20 0.00
October 0.107970E+12 0.327005E+11 744.00 0.103480E+12 0.448989E+10 0.00 0.68 31-OCT-24:00 0.39 28-OCT-07:00 55315.74 31-OCT-24:00 55208.91 31-OCT-24:00 6830.37 24-OCT-14:10 17577.05 05-OCT-15:00 0.00
November 0.144059E+12 0.380433E+11 720.00 0.141564E+12 0.249463E+10 0.00 0.80 02-NOV-15:00 0.57 15-NOV-07:10 64978.12 07-NOV-16:40 61278.67 06-NOV-17:00 5606.36 01-NOV-11:00 21887.17 01-NOV-14:00 0.00
December 0.191363E+12 0.476051E+11 744.00 0.189594E+12 0.176981E+10 0.00 1.00 15-DEC-17:00 0.72 20-DEC-07:10 83141.25 14-DEC-17:00 78843.23 15-DEC-17:00 5640.65 12-DEC-15:00 27575.24 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.150669E+13 0.436690E+12 8760.00 0.146085E+13 0.458421E+11 0.00                         0.00
Minimum of Months 0.402077E+11 0.106336E+11 672.00 0.391491E+11 0.105860E+10 0.00 0.34   0.07   26479.92   22891.68   3954.27   7741.99   0.00
Maximum of Months 0.208488E+12 0.675803E+11 744.00 0.201930E+12 0.655838E+10 0.00 1.00   0.72   84741.14   79528.48   7368.24   31001.50   0.00



Table of Contents

Report: DXReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL ELECTRICITY ENERGY [J] COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL LATENT COOLING ENERGY [J] COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] COOLING COIL RUNTIME FRACTION {Maximum} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL RUNTIME FRACTION {MINIMUM} [] COOLING COIL RUNTIME FRACTION {TIMESTAMP} COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} COOLING COIL LATENT COOLING RATE {Maximum} [W] COOLING COIL LATENT COOLING RATE {TIMESTAMP} COOLING COIL ELECTRICITY RATE {Maximum} [W] COOLING COIL ELECTRICITY RATE {TIMESTAMP} COOLING COIL CRANKCASE HEATER ELECTRICITY RATE []
January 0.298188E+10 0.809863E+09 706.41 0.287757E+10 0.104307E+09 0.00 0.34 19-JAN-17:00 0.00 04-JAN-07:10 2716.01 19-JAN-17:00 2356.05 19-JAN-17:00 398.52 31-JAN-17:00 796.31 19-JAN-16:00 0.00
February 0.771631E+10 0.198835E+10 672.00 0.752664E+10 0.189672E+09 0.00 0.56 27-FEB-17:00 0.10 05-FEB-08:50 4565.92 27-FEB-17:00 4301.81 26-FEB-17:47 396.52 24-FEB-17:00 1408.86 02-FEB-13:40 0.00
March 0.140046E+11 0.363163E+10 744.00 0.138013E+11 0.203249E+09 0.00 0.84 31-MAR-24:00 0.39 12-MAR-08:00 7177.44 31-MAR-24:00 7177.44 31-MAR-24:00 480.12 07-MAR-15:00 2129.33 30-MAR-13:00 0.00
April 0.194033E+11 0.539456E+10 720.00 0.191153E+11 0.288026E+09 0.00 1.00 28-APR-12:40 0.29 30-APR-23:55 8367.72 28-APR-17:20 8146.55 23-APR-18:08 548.50 28-APR-17:30 3006.78 28-APR-15:00 0.00
May 0.630387E+10 0.205537E+10 744.00 0.580248E+10 0.501390E+09 0.00 0.48 31-MAY-23:20 0.25 13-MAY-06:10 3872.97 31-MAY-23:10 3774.38 31-MAY-24:00 553.98 23-MAY-16:00 1123.87 31-MAY-23:20 0.00
June 0.109690E+11 0.359719E+10 720.00 0.103903E+11 0.578689E+09 0.00 0.71 30-JUN-23:53 0.45 07-JUN-06:10 5751.01 30-JUN-23:53 5737.37 30-JUN-23:57 684.14 29-JUN-15:00 1829.65 29-JUN-14:00 0.00
July 0.162259E+11 0.534739E+10 744.00 0.155756E+11 0.650263E+09 0.00 0.90 31-JUL-23:53 0.68 15-JUL-06:00 7445.64 31-JUL-23:57 7445.64 31-JUL-23:57 666.59 12-JUL-10:00 2663.54 21-JUL-16:00 0.00
August 0.209977E+11 0.682412E+10 744.00 0.203413E+11 0.656396E+09 0.00 1.00 01-AUG-10:30 0.29 31-AUG-24:00 8559.26 14-AUG-16:00 8019.34 27-AUG-17:23 736.46 07-AUG-13:40 3159.05 30-AUG-16:00 0.00
September 0.603300E+10 0.192771E+10 720.00 0.549586E+10 0.537146E+09 0.00 0.49 30-SEP-23:30 0.23 28-SEP-06:10 3891.55 30-SEP-24:00 3860.50 30-SEP-24:00 582.78 18-SEP-14:40 1138.71 09-SEP-17:00 0.00
October 0.107689E+11 0.327579E+10 744.00 0.103200E+11 0.448904E+09 0.00 0.66 31-OCT-24:00 0.32 28-OCT-07:00 5484.20 31-OCT-24:00 5472.80 31-OCT-24:00 684.19 24-OCT-14:10 1793.19 05-OCT-15:00 0.00
November 0.139793E+11 0.372249E+10 720.00 0.137308E+11 0.248512E+09 0.00 0.80 02-NOV-15:10 0.50 16-NOV-07:10 6558.31 07-NOV-16:40 6197.21 06-NOV-17:00 560.83 01-NOV-11:00 2209.82 01-NOV-14:00 0.00
December 0.183680E+11 0.461828E+10 744.00 0.181916E+11 0.176411E+09 0.00 0.99 15-DEC-17:00 0.62 20-DEC-07:10 8371.61 14-DEC-17:00 7958.07 15-DEC-17:00 563.85 12-DEC-15:00 2775.87 13-DEC-15:00 0.00
                                       
Annual Sum or Average 0.147752E+12 0.431927E+11 8722.41 0.143169E+12 0.458296E+10 0.00                         0.00
Minimum of Months 0.298188E+10 0.809863E+09 672.00 0.287757E+10 0.104307E+09 0.00 0.34   0.00   2716.01   2356.05   396.52   796.31   0.00
Maximum of Months 0.209977E+11 0.682412E+10 744.00 0.203413E+11 0.656396E+09 0.00 1.00   0.68   8559.26   8146.55   736.46   3159.05   0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 50.27 365.65 0.00 0.00 0.00
February 98.34 0.00 98.34 71.65 310.43 0.00 0.00 0.00
March 114.09 0.00 114.09 108.45 263.45 0.00 0.00 0.00
April 134.65 0.55 134.10 180.28 157.19 0.00 0.00 0.00
May 152.52 5.58 146.94 314.74 42.85 0.00 0.00 0.00
June 173.44 12.01 161.43 372.91 35.47 0.00 0.00 0.00
July 168.32 6.41 161.90 357.36 23.90 0.00 0.00 0.00
August 150.73 1.19 149.54 321.78 34.44 0.00 0.00 0.00
September 130.20 0.01 130.19 256.09 51.57 0.00 0.00 0.00
October 113.14 0.00 113.14 203.94 98.91 0.00 0.00 0.00
November 85.89 0.00 85.89 85.00 235.88 0.00 0.00 0.00
December 77.49 0.00 77.49 55.07 321.73 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.49 198.89 161.02 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 50.27 23.90 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 372.91 365.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 50.27 365.65 0.00 0.00 0.00
February 98.34 0.00 98.34 71.65 310.43 0.00 0.00 0.00
March 114.09 0.00 114.09 108.45 263.45 0.00 0.00 0.00
April 134.65 0.55 134.09 180.28 157.19 0.00 0.00 0.00
May 152.51 5.58 146.94 314.73 42.85 0.00 0.00 0.00
June 173.44 12.01 161.43 372.91 35.47 0.00 0.00 0.00
July 168.31 6.41 161.90 357.36 23.89 0.00 0.00 0.00
August 150.73 1.19 149.54 321.77 34.44 0.00 0.00 0.00
September 130.19 0.01 130.18 256.09 51.57 0.00 0.00 0.00
October 113.14 0.00 113.14 203.94 98.91 0.00 0.00 0.00
November 85.89 0.00 85.89 84.99 235.88 0.00 0.00 0.00
December 77.49 0.00 77.49 55.07 321.73 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.48 198.89 161.02 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 50.27 23.89 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 372.91 365.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 50.27 365.65 0.00 0.00 0.00
February 98.34 0.00 98.34 71.65 310.43 0.00 0.00 0.00
March 114.09 0.00 114.09 108.45 263.45 0.00 0.00 0.00
April 134.65 0.55 134.10 180.28 157.19 0.00 0.00 0.00
May 152.51 5.58 146.94 314.74 42.85 0.00 0.00 0.00
June 173.44 12.01 161.43 372.91 35.47 0.00 0.00 0.00
July 168.31 6.41 161.90 357.36 23.90 0.00 0.00 0.00
August 150.73 1.19 149.54 321.77 34.44 0.00 0.00 0.00
September 130.20 0.01 130.19 256.09 51.57 0.00 0.00 0.00
October 113.14 0.00 113.14 203.94 98.91 0.00 0.00 0.00
November 85.89 0.00 85.89 84.99 235.88 0.00 0.00 0.00
December 77.49 0.00 77.49 55.07 321.73 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.48 198.89 161.02 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 50.27 23.90 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 372.91 365.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 50.27 365.65 0.00 0.00 0.00
February 98.34 0.00 98.34 71.65 310.43 0.00 0.00 0.00
March 114.09 0.00 114.09 108.45 263.45 0.00 0.00 0.00
April 134.65 0.55 134.09 180.28 157.19 0.00 0.00 0.00
May 152.51 5.58 146.94 314.73 42.85 0.00 0.00 0.00
June 173.44 12.01 161.43 372.91 35.47 0.00 0.00 0.00
July 168.31 6.41 161.90 357.36 23.89 0.00 0.00 0.00
August 150.73 1.19 149.54 321.77 34.44 0.00 0.00 0.00
September 130.19 0.01 130.18 256.09 51.57 0.00 0.00 0.00
October 113.14 0.00 113.14 203.94 98.91 0.00 0.00 0.00
November 85.89 0.00 85.89 84.99 235.88 0.00 0.00 0.00
December 77.49 0.00 77.49 55.07 321.73 0.00 0.00 0.00
                 
Annual Sum or Average 123.64 2.15 121.48 198.89 161.02 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 50.27 23.89 0.00 0.00 0.00
Maximum of Months 173.44 12.01 161.90 372.91 365.65 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 83.36 0.00 83.36 50.26 365.64 0.00 0.00 0.00
February 98.34 0.00 98.34 71.64 310.42 0.00 0.00 0.00
March 114.08 0.00 114.08 108.44 263.44 0.00 0.00 0.00
April 134.64 0.55 134.09 180.28 157.18 0.00 0.00 0.00
May 152.51 5.58 146.93 314.72 42.85 0.00 0.00 0.00
June 173.43 12.01 161.43 372.89 35.47 0.00 0.00 0.00
July 168.31 6.41 161.89 357.34 23.89 0.00 0.00 0.00
August 150.72 1.19 149.54 321.76 34.44 0.00 0.00 0.00
September 130.19 0.01 130.18 256.08 51.56 0.00 0.00 0.00
October 113.13 0.00 113.13 203.93 98.90 0.00 0.00 0.00
November 85.89 0.00 85.89 84.99 235.87 0.00 0.00 0.00
December 77.49 0.00 77.49 55.07 321.72 0.00 0.00 0.00
                 
Annual Sum or Average 123.63 2.15 121.48 198.88 161.02 0.00 0.00 0.00
Minimum of Months 77.49 0.00 77.49 50.26 23.89 0.00 0.00 0.00
Maximum of Months 173.43 12.01 161.89 372.89 365.64 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 238.37 121.38 116.99 269.33 369.40 0.00 0.00 0.00
February 265.44 128.15 137.29 320.89 311.32 0.00 0.00 0.00
March 312.24 150.59 161.66 417.02 264.59 0.00 0.00 0.00
April 342.65 154.97 187.68 529.80 161.38 0.00 0.00 0.00
May 353.18 153.15 200.03 664.16 46.78 0.00 0.00 0.00
June 358.18 142.05 216.14 699.31 36.50 0.00 0.00 0.00
July 345.34 126.38 218.96 675.29 22.35 0.00 0.00 0.00
August 318.22 109.41 208.81 623.25 32.03 0.00 0.00 0.00
September 281.88 96.91 184.97 523.19 55.44 0.00 0.00 0.00
October 278.56 117.55 161.01 489.41 102.27 0.00 0.00 0.00
November 246.62 125.81 120.81 337.01 235.12 0.00 0.00 0.00
December 194.18 87.96 106.22 230.69 321.32 0.00 0.00 0.00
                 
Annual Sum or Average 294.67 126.13 168.54 482.49 162.44 0.00 0.00 0.00
Minimum of Months 194.18 87.96 106.22 230.69 22.35 0.00 0.00 0.00
Maximum of Months 358.18 154.97 218.96 699.31 369.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 238.37 121.38 116.99 269.33 369.40 0.00 0.00 0.00
February 265.44 128.15 137.29 320.89 311.32 0.00 0.00 0.00
March 312.24 150.59 161.66 417.02 264.59 0.00 0.00 0.00
April 342.65 154.97 187.68 529.80 161.38 0.00 0.00 0.00
May 353.18 153.15 200.03 664.16 46.78 0.00 0.00 0.00
June 358.18 142.05 216.14 699.31 36.50 0.00 0.00 0.00
July 345.34 126.38 218.96 675.29 22.35 0.00 0.00 0.00
August 318.22 109.41 208.81 623.25 32.03 0.00 0.00 0.00
September 281.88 96.91 184.97 523.19 55.44 0.00 0.00 0.00
October 278.56 117.55 161.01 489.41 102.27 0.00 0.00 0.00
November 246.62 125.81 120.81 337.01 235.12 0.00 0.00 0.00
December 194.18 87.96 106.22 230.69 321.32 0.00 0.00 0.00
                 
Annual Sum or Average 294.67 126.13 168.54 482.49 162.44 0.00 0.00 0.00
Minimum of Months 194.18 87.96 106.22 230.69 22.35 0.00 0.00 0.00
Maximum of Months 358.18 154.97 218.96 699.31 369.40 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 238.37 121.38 116.99 269.32 369.39 0.00 0.00 0.00
February 265.43 128.14 137.29 320.88 311.31 0.00 0.00 0.00
March 312.24 150.58 161.65 417.02 264.58 0.00 0.00 0.00
April 342.64 154.97 187.67 529.79 161.37 0.00 0.00 0.00
May 353.17 153.14 200.03 664.15 46.78 0.00 0.00 0.00
June 358.18 142.04 216.13 699.30 36.50 0.00 0.00 0.00
July 345.33 126.37 218.96 675.28 22.35 0.00 0.00 0.00
August 318.21 109.40 208.81 623.24 32.03 0.00 0.00 0.00
September 281.88 96.91 184.97 523.18 55.44 0.00 0.00 0.00
October 278.55 117.55 161.01 489.40 102.27 0.00 0.00 0.00
November 246.62 125.81 120.81 337.01 235.12 0.00 0.00 0.00
December 194.17 87.96 106.22 230.69 321.31 0.00 0.00 0.00
                 
Annual Sum or Average 294.67 126.13 168.54 482.48 162.44 0.00 0.00 0.00
Minimum of Months 194.17 87.96 106.22 230.69 22.35 0.00 0.00 0.00
Maximum of Months 358.18 154.97 218.96 699.30 369.39 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.83 343.63 138.20 681.14 327.79 0.00 0.00 0.00
February 436.99 282.86 154.13 630.55 283.45 0.00 0.00 0.00
March 278.98 125.91 153.08 413.19 252.18 0.00 0.00 0.00
April 206.78 48.45 158.33 340.45 161.55 0.00 0.00 0.00
May 158.00 6.71 151.28 329.81 44.66 0.00 0.00 0.00
June 156.07 1.45 154.62 336.89 36.88 0.00 0.00 0.00
July 163.38 3.00 160.38 348.65 23.75 0.00 0.00 0.00
August 192.21 23.07 169.14 411.45 36.88 0.00 0.00 0.00
September 230.62 60.78 169.84 455.73 55.69 0.00 0.00 0.00
October 357.81 186.38 171.43 648.01 103.70 0.00 0.00 0.00
November 455.33 313.50 141.83 703.02 222.00 0.00 0.00 0.00
December 470.80 338.11 132.70 693.26 295.52 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 498.71 152.98 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 329.81 23.75 0.00 0.00 0.00
Maximum of Months 481.83 343.63 171.43 703.02 327.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.82 343.62 138.20 681.13 327.79 0.00 0.00 0.00
February 436.99 282.85 154.13 630.55 283.45 0.00 0.00 0.00
March 278.98 125.90 153.08 413.18 252.18 0.00 0.00 0.00
April 206.78 48.45 158.33 340.45 161.55 0.00 0.00 0.00
May 158.00 6.71 151.28 329.81 44.66 0.00 0.00 0.00
June 156.07 1.45 154.62 336.89 36.88 0.00 0.00 0.00
July 163.38 3.00 160.38 348.65 23.75 0.00 0.00 0.00
August 192.21 23.07 169.14 411.45 36.88 0.00 0.00 0.00
September 230.62 60.78 169.84 455.73 55.69 0.00 0.00 0.00
October 357.81 186.38 171.42 648.01 103.70 0.00 0.00 0.00
November 455.33 313.50 141.83 703.02 222.00 0.00 0.00 0.00
December 470.80 338.10 132.70 693.25 295.51 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 498.71 152.98 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 329.81 23.75 0.00 0.00 0.00
Maximum of Months 481.82 343.62 171.42 703.02 327.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.83 343.63 138.20 681.14 327.79 0.00 0.00 0.00
February 436.99 282.86 154.13 630.55 283.45 0.00 0.00 0.00
March 278.98 125.91 153.08 413.19 252.18 0.00 0.00 0.00
April 206.78 48.45 158.33 340.45 161.55 0.00 0.00 0.00
May 158.00 6.71 151.28 329.81 44.66 0.00 0.00 0.00
June 156.07 1.45 154.62 336.89 36.88 0.00 0.00 0.00
July 163.38 3.00 160.38 348.65 23.75 0.00 0.00 0.00
August 192.21 23.07 169.14 411.45 36.88 0.00 0.00 0.00
September 230.62 60.78 169.84 455.73 55.69 0.00 0.00 0.00
October 357.81 186.38 171.43 648.01 103.70 0.00 0.00 0.00
November 455.33 313.50 141.83 703.02 222.00 0.00 0.00 0.00
December 470.80 338.11 132.70 693.26 295.52 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 498.71 152.98 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 329.81 23.75 0.00 0.00 0.00
Maximum of Months 481.83 343.63 171.43 703.02 327.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.82 343.62 138.20 681.13 327.79 0.00 0.00 0.00
February 436.99 282.85 154.13 630.55 283.45 0.00 0.00 0.00
March 278.98 125.90 153.08 413.18 252.18 0.00 0.00 0.00
April 206.78 48.45 158.33 340.45 161.55 0.00 0.00 0.00
May 158.00 6.71 151.28 329.81 44.66 0.00 0.00 0.00
June 156.07 1.45 154.62 336.89 36.88 0.00 0.00 0.00
July 163.38 3.00 160.38 348.65 23.75 0.00 0.00 0.00
August 192.21 23.07 169.14 411.45 36.88 0.00 0.00 0.00
September 230.62 60.78 169.84 455.73 55.69 0.00 0.00 0.00
October 357.81 186.38 171.42 648.01 103.70 0.00 0.00 0.00
November 455.33 313.50 141.83 703.02 222.00 0.00 0.00 0.00
December 470.80 338.10 132.70 693.25 295.51 0.00 0.00 0.00
                 
Annual Sum or Average 298.34 143.77 154.57 498.71 152.98 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.70 329.81 23.75 0.00 0.00 0.00
Maximum of Months 481.82 343.62 171.42 703.02 327.79 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 481.81 343.61 138.20 681.11 327.78 0.00 0.00 0.00
February 436.97 282.84 154.13 630.53 283.44 0.00 0.00 0.00
March 278.97 125.90 153.07 413.17 252.17 0.00 0.00 0.00
April 206.77 48.45 158.32 340.44 161.55 0.00 0.00 0.00
May 157.99 6.71 151.27 329.80 44.65 0.00 0.00 0.00
June 156.07 1.45 154.61 336.88 36.88 0.00 0.00 0.00
July 163.38 3.00 160.37 348.64 23.75 0.00 0.00 0.00
August 192.20 23.07 169.13 411.43 36.88 0.00 0.00 0.00
September 230.61 60.78 169.84 455.71 55.68 0.00 0.00 0.00
October 357.79 186.38 171.42 647.98 103.70 0.00 0.00 0.00
November 455.31 313.49 141.83 702.99 221.99 0.00 0.00 0.00
December 470.78 338.09 132.69 693.23 295.50 0.00 0.00 0.00
                 
Annual Sum or Average 298.33 143.77 154.56 498.69 152.98 0.00 0.00 0.00
Minimum of Months 156.07 1.45 132.69 329.80 23.75 0.00 0.00 0.00
Maximum of Months 481.81 343.61 171.42 702.99 327.78 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 253.55 137.10 116.44 307.07 416.30 0.00 0.00 0.00
February 287.07 145.30 141.77 360.22 368.95 0.00 0.00 0.00
March 282.94 125.25 157.69 369.63 326.85 0.00 0.00 0.00
April 351.42 161.66 189.76 530.96 214.39 0.00 0.00 0.00
May 292.25 95.20 197.05 556.30 64.91 0.00 0.00 0.00
June 324.65 113.84 210.81 627.94 59.78 0.00 0.00 0.00
July 296.35 82.20 214.14 568.00 47.14 0.00 0.00 0.00
August 299.64 91.73 207.92 570.96 68.94 0.00 0.00 0.00
September 275.92 94.65 181.27 508.02 75.10 0.00 0.00 0.00
October 282.49 122.06 160.43 493.18 135.33 0.00 0.00 0.00
November 242.12 121.68 120.44 336.14 296.15 0.00 0.00 0.00
December 232.90 123.85 109.05 291.31 396.99 0.00 0.00 0.00
                 
Annual Sum or Average 284.95 117.60 167.35 460.35 205.05 0.00 0.00 0.00
Minimum of Months 232.90 82.20 109.05 291.31 47.14 0.00 0.00 0.00
Maximum of Months 351.42 161.66 214.14 627.94 416.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 253.55 137.10 116.44 307.07 416.30 0.00 0.00 0.00
February 287.07 145.30 141.77 360.22 368.95 0.00 0.00 0.00
March 282.94 125.25 157.69 369.63 326.85 0.00 0.00 0.00
April 351.42 161.66 189.76 530.96 214.39 0.00 0.00 0.00
May 292.25 95.20 197.05 556.30 64.91 0.00 0.00 0.00
June 324.65 113.84 210.81 627.94 59.78 0.00 0.00 0.00
July 296.35 82.20 214.14 568.00 47.14 0.00 0.00 0.00
August 299.64 91.73 207.92 570.96 68.94 0.00 0.00 0.00
September 275.92 94.65 181.27 508.02 75.10 0.00 0.00 0.00
October 282.49 122.06 160.43 493.18 135.33 0.00 0.00 0.00
November 242.12 121.68 120.44 336.14 296.15 0.00 0.00 0.00
December 232.90 123.85 109.05 291.31 396.99 0.00 0.00 0.00
                 
Annual Sum or Average 284.95 117.60 167.35 460.35 205.05 0.00 0.00 0.00
Minimum of Months 232.90 82.20 109.05 291.31 47.14 0.00 0.00 0.00
Maximum of Months 351.42 161.66 214.14 627.94 416.30 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 253.54 137.10 116.44 307.06 416.29 0.00 0.00 0.00
February 287.07 145.30 141.77 360.22 368.94 0.00 0.00 0.00
March 282.93 125.25 157.69 369.62 326.84 0.00 0.00 0.00
April 351.41 161.66 189.76 530.95 214.39 0.00 0.00 0.00
May 292.24 95.20 197.04 556.29 64.91 0.00 0.00 0.00
June 324.65 113.84 210.81 627.92 59.77 0.00 0.00 0.00
July 296.34 82.20 214.14 567.99 47.14 0.00 0.00 0.00
August 299.64 91.72 207.92 570.95 68.93 0.00 0.00 0.00
September 275.92 94.65 181.26 508.01 75.10 0.00 0.00 0.00
October 282.48 122.06 160.42 493.17 135.33 0.00 0.00 0.00
November 242.12 121.68 120.44 336.14 296.15 0.00 0.00 0.00
December 232.90 123.85 109.05 291.31 396.98 0.00 0.00 0.00
                 
Annual Sum or Average 284.94 117.59 167.35 460.34 205.05 0.00 0.00 0.00
Minimum of Months 232.90 82.20 109.05 291.31 47.14 0.00 0.00 0.00
Maximum of Months 351.41 161.66 214.14 627.92 416.29 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.80 0.00 416.80 293.93 1642.49 0.00 0.00 0.00
February 491.72 0.00 491.72 398.73 1383.59 0.00 0.00 0.00
March 570.44 0.00 570.44 578.48 1193.27 0.00 0.00 0.00
April 673.25 2.76 670.48 921.19 747.13 0.00 0.00 0.00
May 762.58 27.89 734.69 1576.91 214.44 0.00 0.00 0.00
June 867.22 60.05 807.17 1868.73 184.97 0.00 0.00 0.00
July 841.58 32.06 809.51 1797.92 122.32 0.00 0.00 0.00
August 753.65 5.93 747.72 1627.92 171.62 0.00 0.00 0.00
September 650.98 0.05 650.93 1289.25 245.14 0.00 0.00 0.00
October 565.69 0.00 565.69 1036.84 464.67 0.00 0.00 0.00
November 429.45 0.00 429.45 460.39 1055.88 0.00 0.00 0.00
December 387.46 0.00 387.46 319.11 1408.12 0.00 0.00 0.00
                 
Annual Sum or Average 618.19 10.76 607.43 1017.85 732.76 0.00 0.00 0.00
Minimum of Months 387.46 0.00 387.46 293.93 122.32 0.00 0.00 0.00
Maximum of Months 867.22 60.05 809.51 1868.73 1642.49 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 715.11 364.14 350.98 824.03 1028.59 0.00 0.00 0.00
February 796.30 384.43 411.87 975.73 871.99 0.00 0.00 0.00
March 936.72 451.75 484.96 1249.90 759.35 0.00 0.00 0.00
April 1027.94 464.91 563.03 1572.02 497.68 0.00 0.00 0.00
May 1059.53 459.43 600.10 1972.62 150.63 0.00 0.00 0.00
June 1074.54 426.13 648.41 2078.93 128.63 0.00 0.00 0.00
July 1036.01 379.12 656.88 2005.72 85.50 0.00 0.00 0.00
August 954.65 328.22 626.43 1851.46 119.85 0.00 0.00 0.00
September 845.64 290.73 554.91 1557.52 169.60 0.00 0.00 0.00
October 835.67 352.65 483.02 1455.45 308.97 0.00 0.00 0.00
November 739.86 377.43 362.43 1012.80 673.47 0.00 0.00 0.00
December 582.53 263.87 318.66 705.54 898.23 0.00 0.00 0.00
                 
Annual Sum or Average 884.01 378.40 505.61 1441.00 472.28 0.00 0.00 0.00
Minimum of Months 582.53 263.87 318.66 705.54 85.50 0.00 0.00 0.00
Maximum of Months 1074.54 464.91 656.88 2078.93 1028.59 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2409.18 1718.17 691.02 3376.14 1609.27 0.00 0.00 0.00
February 2184.99 1414.31 770.68 3132.70 1379.42 0.00 0.00 0.00
March 1394.95 629.54 765.41 2058.88 1211.05 0.00 0.00 0.00
April 1033.92 242.27 791.64 1700.91 792.14 0.00 0.00 0.00
May 789.99 33.57 756.41 1650.91 223.53 0.00 0.00 0.00
June 780.37 7.27 773.10 1691.93 189.67 0.00 0.00 0.00
July 816.92 15.01 801.91 1756.49 119.71 0.00 0.00 0.00
August 961.07 115.36 845.71 2066.89 186.22 0.00 0.00 0.00
September 1153.12 303.90 849.22 2270.37 274.06 0.00 0.00 0.00
October 1789.07 931.94 857.14 3219.47 517.98 0.00 0.00 0.00
November 2276.71 1567.54 709.17 3495.49 1086.56 0.00 0.00 0.00
December 2354.07 1690.56 663.50 3450.17 1429.01 0.00 0.00 0.00
                 
Annual Sum or Average 1491.72 718.87 772.84 2486.09 748.21 0.00 0.00 0.00
Minimum of Months 780.37 7.27 663.50 1650.91 119.71 0.00 0.00 0.00
Maximum of Months 2409.18 1718.17 857.14 3495.49 1609.27 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 760.64 411.31 349.33 949.75 1112.97 0.00 0.00 0.00
February 861.21 435.89 425.32 1117.34 956.24 0.00 0.00 0.00
March 848.81 375.75 473.06 1145.82 832.33 0.00 0.00 0.00
April 1054.25 484.97 569.27 1629.46 555.77 0.00 0.00 0.00
May 876.73 285.60 591.13 1681.08 176.31 0.00 0.00 0.00
June 973.95 341.51 632.43 1905.65 156.39 0.00 0.00 0.00
July 889.03 246.60 642.43 1742.77 107.42 0.00 0.00 0.00
August 898.92 275.17 623.75 1763.70 149.01 0.00 0.00 0.00
September 827.76 283.96 543.80 1536.82 196.09 0.00 0.00 0.00
October 847.45 366.17 481.28 1503.40 353.22 0.00 0.00 0.00
November 726.37 365.04 361.32 1048.26 748.47 0.00 0.00 0.00
December 698.70 371.56 327.14 923.61 970.86 0.00 0.00 0.00
                 
Annual Sum or Average 854.83 352.79 502.04 1413.44 523.95 0.00 0.00 0.00
Minimum of Months 698.70 246.60 327.14 923.61 107.42 0.00 0.00 0.00
Maximum of Months 1054.25 484.97 642.43 1905.65 1112.97 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 416.80 0.00 416.80 323.53 1504.56 0.00 0.00 0.00
February 491.72 0.00 491.72 421.39 1273.08 0.00 0.00 0.00
March 570.44 0.00 570.44 593.90 1118.65 0.00 0.00 0.00
April 673.25 2.76 670.48 917.83 726.90 0.00 0.00 0.00
May 762.58 27.89 734.69 1550.94 226.68 0.00 0.00 0.00
June 867.22 60.05 807.17 1839.20 198.34 0.00 0.00 0.00
July 841.58 32.06 809.51 1764.14 136.10 0.00 0.00 0.00
August 753.65 5.93 747.72 1600.98 182.50 0.00 0.00 0.00
September 650.98 0.05 650.93 1264.00 256.05 0.00 0.00 0.00
October 565.69 0.00 565.69 1025.22 457.06 0.00 0.00 0.00
November 429.45 0.00 429.45 477.05 983.10 0.00 0.00 0.00
December 387.46 0.00 387.46 340.97 1294.77 0.00 0.00 0.00
                 
Annual Sum or Average 618.19 10.76 607.43 1013.51 693.45 0.00 0.00 0.00
Minimum of Months 387.46 0.00 387.46 323.53 136.10 0.00 0.00 0.00
Maximum of Months 867.22 60.05 809.51 1839.20 1504.56 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 715.11 364.14 350.98 855.19 949.08 0.00 0.00 0.00
February 796.30 384.43 411.87 997.57 810.34 0.00 0.00 0.00
March 936.72 451.75 484.96 1257.62 722.07 0.00 0.00 0.00
April 1027.94 464.91 563.03 1565.93 490.29 0.00 0.00 0.00
May 1059.53 459.43 600.10 1952.59 158.78 0.00 0.00 0.00
June 1074.54 426.13 648.41 2057.54 138.13 0.00 0.00 0.00
July 1036.01 379.12 656.88 1982.24 94.77 0.00 0.00 0.00
August 954.65 328.22 626.43 1831.47 127.20 0.00 0.00 0.00
September 845.64 290.73 554.91 1539.62 177.08 0.00 0.00 0.00
October 835.67 352.65 483.02 1445.22 306.13 0.00 0.00 0.00
November 739.86 377.43 362.43 1023.60 639.16 0.00 0.00 0.00
December 582.53 263.87 318.66 724.50 835.87 0.00 0.00 0.00
                 
Annual Sum or Average 884.01 378.40 505.61 1438.48 452.17 0.00 0.00 0.00
Minimum of Months 582.53 263.87 318.66 724.50 94.77 0.00 0.00 0.00
Maximum of Months 1074.54 464.91 656.88 2057.54 949.08 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 2409.18 1718.17 691.02 3405.84 1505.21 0.00 0.00 0.00
February 2184.99 1414.31 770.68 3156.76 1294.27 0.00 0.00 0.00
March 1394.95 629.54 765.41 2067.38 1149.08 0.00 0.00 0.00
April 1033.92 242.27 791.64 1691.90 775.82 0.00 0.00 0.00
May 789.99 33.57 756.41 1624.75 236.10 0.00 0.00 0.00
June 780.37 7.27 773.10 1663.62 204.08 0.00 0.00 0.00
July 816.92 15.01 801.91 1721.83 133.27 0.00 0.00 0.00
August 961.07 115.36 845.71 2038.77 198.10 0.00 0.00 0.00
September 1153.12 303.90 849.22 2244.48 285.72 0.00 0.00 0.00
October 1789.07 931.94 857.14 3200.89 516.39 0.00 0.00 0.00
November 2276.71 1567.54 709.17 3500.59 1044.47 0.00 0.00 0.00
December 2354.07 1690.56 663.50 3468.17 1344.38 0.00 0.00 0.00
                 
Annual Sum or Average 1491.72 718.87 772.84 2478.80 720.82 0.00 0.00 0.00
Minimum of Months 780.37 7.27 663.50 1624.75 133.27 0.00 0.00 0.00
Maximum of Months 2409.18 1718.17 857.14 3500.59 1505.21 0.00 0.00 0.00



Table of Contents

Report: WindowReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] SURFACE WINDOW HEAT GAIN RATE [W] SURFACE WINDOW HEAT LOSS RATE [W] SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS]
January 760.64 411.31 349.33 965.67 1037.21 0.00 0.00 0.00
February 861.21 435.89 425.32 1127.83 895.50 0.00 0.00 0.00
March 848.81 375.75 473.06 1150.53 789.69 0.00 0.00 0.00
April 1054.25 484.97 569.27 1621.68 544.55 0.00 0.00 0.00
May 876.73 285.60 591.13 1664.45 182.76 0.00 0.00 0.00
June 973.95 341.51 632.43 1886.73 163.47 0.00 0.00 0.00
July 889.03 246.60 642.43 1722.04 113.73 0.00 0.00 0.00
August 898.92 275.17 623.75 1745.94 154.97 0.00 0.00 0.00
September 827.76 283.96 543.80 1521.59 201.68 0.00 0.00 0.00
October 847.45 366.17 481.28 1493.94 349.39 0.00 0.00 0.00
November 726.37 365.04 361.32 1054.17 709.56 0.00 0.00 0.00
December 698.70 371.56 327.14 934.01 907.02 0.00 0.00 0.00
                 
Annual Sum or Average 854.83 352.79 502.04 1408.43 502.00 0.00 0.00 0.00
Minimum of Months 698.70 246.60 327.14 934.01 113.73 0.00 0.00 0.00
Maximum of Months 1054.25 484.97 642.43 1886.73 1037.21 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223271E+09 0.00 0.223271E+09 0.134637E+09 0.979361E+09
February 0.237915E+09 0.00 0.237915E+09 0.173332E+09 0.750993E+09
March 0.305574E+09 0.00 0.305574E+09 0.290464E+09 0.705629E+09
April 0.349011E+09 1432452.17 0.347579E+09 0.467297E+09 0.407428E+09
May 0.408498E+09 14941839.27 0.393557E+09 0.842992E+09 0.114763E+09
June 0.449564E+09 31128636.17 0.418436E+09 0.966582E+09 91947773.30
July 0.450816E+09 17175142.31 0.433641E+09 0.957158E+09 64001331.13
August 0.403714E+09 3175239.04 0.400538E+09 0.861844E+09 92244014.98
September 0.337469E+09 25991.58 0.337443E+09 0.663790E+09 0.133660E+09
October 0.303029E+09 0.00 0.303029E+09 0.546233E+09 0.264912E+09
November 0.222627E+09 0.00 0.222627E+09 0.220309E+09 0.611392E+09
December 0.207556E+09 0.00 0.207556E+09 0.147495E+09 0.861724E+09
           
Annual Sum or Average 0.389904E+10 67879300.53 0.383116E+10 0.627213E+10 0.507806E+10
Minimum of Months 0.207556E+09 0.00 0.207556E+09 0.134637E+09 64001331.13
Maximum of Months 0.450816E+09 31128636.17 0.433641E+09 0.966582E+09 0.979361E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223268E+09 0.00 0.223268E+09 0.134635E+09 0.979360E+09
February 0.237912E+09 0.00 0.237912E+09 0.173330E+09 0.750991E+09
March 0.305570E+09 0.00 0.305570E+09 0.290460E+09 0.705628E+09
April 0.349007E+09 1432420.68 0.347574E+09 0.467292E+09 0.407426E+09
May 0.408493E+09 14941510.79 0.393551E+09 0.842984E+09 0.114762E+09
June 0.449558E+09 31127951.84 0.418430E+09 0.966572E+09 91946389.67
July 0.450809E+09 17174764.73 0.433634E+09 0.957147E+09 64000018.18
August 0.403708E+09 3175169.23 0.400533E+09 0.861836E+09 92242641.50
September 0.337464E+09 25991.01 0.337438E+09 0.663783E+09 0.133659E+09
October 0.303025E+09 0.00 0.303025E+09 0.546228E+09 0.264911E+09
November 0.222624E+09 0.00 0.222624E+09 0.220306E+09 0.611390E+09
December 0.207553E+09 0.00 0.207553E+09 0.147493E+09 0.861723E+09
           
Annual Sum or Average 0.389899E+10 67877808.28 0.383111E+10 0.627206E+10 0.507804E+10
Minimum of Months 0.207553E+09 0.00 0.207553E+09 0.134635E+09 64000018.18
Maximum of Months 0.450809E+09 31127951.84 0.433634E+09 0.966572E+09 0.979360E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223269E+09 0.00 0.223269E+09 0.134635E+09 0.979360E+09
February 0.237913E+09 0.00 0.237913E+09 0.173331E+09 0.750992E+09
March 0.305571E+09 0.00 0.305571E+09 0.290461E+09 0.705628E+09
April 0.349008E+09 1432431.18 0.347576E+09 0.467294E+09 0.407427E+09
May 0.408494E+09 14941620.28 0.393553E+09 0.842987E+09 0.114762E+09
June 0.449560E+09 31128179.95 0.418432E+09 0.966575E+09 91946850.88
July 0.450811E+09 17174890.59 0.433636E+09 0.957151E+09 64000455.84
August 0.403710E+09 3175192.50 0.400535E+09 0.861839E+09 92243099.32
September 0.337466E+09 25991.20 0.337440E+09 0.663785E+09 0.133659E+09
October 0.303026E+09 0.00 0.303026E+09 0.546230E+09 0.264911E+09
November 0.222625E+09 0.00 0.222625E+09 0.220307E+09 0.611391E+09
December 0.207554E+09 0.00 0.207554E+09 0.147494E+09 0.861723E+09
           
Annual Sum or Average 0.389901E+10 67878305.70 0.383113E+10 0.627209E+10 0.507804E+10
Minimum of Months 0.207554E+09 0.00 0.207554E+09 0.134635E+09 64000455.84
Maximum of Months 0.450811E+09 31128179.95 0.433636E+09 0.966575E+09 0.979360E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223268E+09 0.00 0.223268E+09 0.134635E+09 0.979360E+09
February 0.237912E+09 0.00 0.237912E+09 0.173330E+09 0.750991E+09
March 0.305570E+09 0.00 0.305570E+09 0.290460E+09 0.705628E+09
April 0.349007E+09 1432420.68 0.347574E+09 0.467292E+09 0.407426E+09
May 0.408493E+09 14941510.79 0.393551E+09 0.842984E+09 0.114762E+09
June 0.449558E+09 31127951.84 0.418430E+09 0.966572E+09 91946389.67
July 0.450809E+09 17174764.73 0.433634E+09 0.957147E+09 64000018.18
August 0.403708E+09 3175169.23 0.400533E+09 0.861836E+09 92242641.50
September 0.337464E+09 25991.01 0.337438E+09 0.663783E+09 0.133659E+09
October 0.303025E+09 0.00 0.303025E+09 0.546228E+09 0.264911E+09
November 0.222624E+09 0.00 0.222624E+09 0.220306E+09 0.611390E+09
December 0.207553E+09 0.00 0.207553E+09 0.147493E+09 0.861723E+09
           
Annual Sum or Average 0.389899E+10 67877808.28 0.383111E+10 0.627206E+10 0.507804E+10
Minimum of Months 0.207553E+09 0.00 0.207553E+09 0.134635E+09 64000018.18
Maximum of Months 0.450809E+09 31127951.84 0.433634E+09 0.966572E+09 0.979360E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.223260E+09 0.00 0.223260E+09 0.134630E+09 0.979320E+09
February 0.237903E+09 0.00 0.237903E+09 0.173323E+09 0.750961E+09
March 0.305558E+09 0.00 0.305558E+09 0.290449E+09 0.705600E+09
April 0.348993E+09 1432368.20 0.347561E+09 0.467274E+09 0.407410E+09
May 0.408477E+09 14940963.33 0.393536E+09 0.842951E+09 0.114757E+09
June 0.449541E+09 31126811.29 0.418414E+09 0.966535E+09 91942914.42
July 0.450792E+09 17174135.44 0.433618E+09 0.957111E+09 63997657.52
August 0.403693E+09 3175052.89 0.400517E+09 0.861802E+09 92239152.62
September 0.337451E+09 25990.05 0.337425E+09 0.663757E+09 0.133654E+09
October 0.303013E+09 0.00 0.303013E+09 0.546207E+09 0.264900E+09
November 0.222615E+09 0.00 0.222615E+09 0.220298E+09 0.611366E+09
December 0.207545E+09 0.00 0.207545E+09 0.147488E+09 0.861688E+09
           
Annual Sum or Average 0.389884E+10 67875321.21 0.383097E+10 0.627182E+10 0.507784E+10
Minimum of Months 0.207545E+09 0.00 0.207545E+09 0.134630E+09 63997657.52
Maximum of Months 0.450792E+09 31126811.29 0.433618E+09 0.966535E+09 0.979320E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.638461E+09 0.325107E+09 0.313354E+09 0.721368E+09 0.989398E+09
February 0.642146E+09 0.310011E+09 0.332135E+09 0.776294E+09 0.753137E+09
March 0.836308E+09 0.403329E+09 0.432980E+09 0.111695E+10 0.708667E+09
April 0.888146E+09 0.401684E+09 0.486462E+09 0.137324E+10 0.418287E+09
May 0.945954E+09 0.410184E+09 0.535770E+09 0.177889E+10 0.125299E+09
June 0.928410E+09 0.368182E+09 0.560228E+09 0.181262E+10 94609742.59
July 0.924957E+09 0.338484E+09 0.586473E+09 0.180870E+10 59856402.48
August 0.852319E+09 0.293034E+09 0.559285E+09 0.166932E+10 85779608.05
September 0.730643E+09 0.251193E+09 0.479451E+09 0.135611E+10 0.143707E+09
October 0.746094E+09 0.314849E+09 0.431244E+09 0.131083E+10 0.273928E+09
November 0.639250E+09 0.326106E+09 0.313143E+09 0.873540E+09 0.609434E+09
December 0.520086E+09 0.235587E+09 0.284498E+09 0.617887E+09 0.860616E+09
           
Annual Sum or Average 0.929277E+10 0.397775E+10 0.531502E+10 0.152157E+11 0.512272E+10
Minimum of Months 0.520086E+09 0.235587E+09 0.284498E+09 0.617887E+09 59856402.48
Maximum of Months 0.945954E+09 0.410184E+09 0.586473E+09 0.181262E+10 0.989398E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.638461E+09 0.325107E+09 0.313354E+09 0.721368E+09 0.989398E+09
February 0.642146E+09 0.310011E+09 0.332135E+09 0.776294E+09 0.753137E+09
March 0.836308E+09 0.403329E+09 0.432980E+09 0.111695E+10 0.708667E+09
April 0.888146E+09 0.401684E+09 0.486462E+09 0.137324E+10 0.418287E+09
May 0.945954E+09 0.410184E+09 0.535770E+09 0.177889E+10 0.125299E+09
June 0.928410E+09 0.368182E+09 0.560228E+09 0.181262E+10 94609742.59
July 0.924957E+09 0.338484E+09 0.586473E+09 0.180870E+10 59856402.48
August 0.852319E+09 0.293034E+09 0.559285E+09 0.166932E+10 85779608.05
September 0.730643E+09 0.251193E+09 0.479451E+09 0.135611E+10 0.143707E+09
October 0.746094E+09 0.314849E+09 0.431244E+09 0.131083E+10 0.273928E+09
November 0.639250E+09 0.326106E+09 0.313143E+09 0.873540E+09 0.609434E+09
December 0.520086E+09 0.235587E+09 0.284498E+09 0.617887E+09 0.860616E+09
           
Annual Sum or Average 0.929277E+10 0.397775E+10 0.531502E+10 0.152157E+11 0.512272E+10
Minimum of Months 0.520086E+09 0.235587E+09 0.284498E+09 0.617887E+09 59856402.48
Maximum of Months 0.945954E+09 0.410184E+09 0.586473E+09 0.181262E+10 0.989398E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.638450E+09 0.325101E+09 0.313349E+09 0.721355E+09 0.989380E+09
February 0.642135E+09 0.310006E+09 0.332129E+09 0.776280E+09 0.753124E+09
March 0.836293E+09 0.403321E+09 0.432972E+09 0.111693E+10 0.708654E+09
April 0.888130E+09 0.401677E+09 0.486453E+09 0.137321E+10 0.418280E+09
May 0.945937E+09 0.410176E+09 0.535761E+09 0.177886E+10 0.125296E+09
June 0.928393E+09 0.368175E+09 0.560218E+09 0.181259E+10 94608013.86
July 0.924940E+09 0.338478E+09 0.586462E+09 0.180867E+10 59855308.77
August 0.852304E+09 0.293029E+09 0.559275E+09 0.166929E+10 85778040.67
September 0.730630E+09 0.251188E+09 0.479442E+09 0.135609E+10 0.143704E+09
October 0.746080E+09 0.314843E+09 0.431237E+09 0.131080E+10 0.273923E+09
November 0.639238E+09 0.326100E+09 0.313138E+09 0.873524E+09 0.609422E+09
December 0.520076E+09 0.235583E+09 0.284493E+09 0.617876E+09 0.860600E+09
           
Annual Sum or Average 0.929260E+10 0.397768E+10 0.531493E+10 0.152155E+11 0.512262E+10
Minimum of Months 0.520076E+09 0.235583E+09 0.284493E+09 0.617876E+09 59855308.77
Maximum of Months 0.945937E+09 0.410176E+09 0.586462E+09 0.181259E+10 0.989380E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129053E+10 0.920368E+09 0.370159E+09 0.182435E+10 0.877959E+09
February 0.105717E+10 0.684285E+09 0.372883E+09 0.152543E+10 0.685728E+09
March 0.747233E+09 0.337225E+09 0.410008E+09 0.110668E+10 0.675433E+09
April 0.535976E+09 0.125591E+09 0.410385E+09 0.882456E+09 0.418749E+09
May 0.423176E+09 17984196.22 0.405192E+09 0.883365E+09 0.119606E+09
June 0.404542E+09 3770670.32 0.400771E+09 0.873226E+09 95591703.47
July 0.437605E+09 8043046.48 0.429562E+09 0.933824E+09 63617911.30
August 0.514818E+09 61793137.02 0.453025E+09 0.110202E+10 98780825.48
September 0.597768E+09 0.157536E+09 0.440232E+09 0.118125E+10 0.144340E+09
October 0.958355E+09 0.499210E+09 0.459145E+09 0.173564E+10 0.277758E+09
November 0.118023E+10 0.812596E+09 0.367630E+09 0.182223E+10 0.575413E+09
December 0.126100E+10 0.905582E+09 0.355420E+09 0.185682E+10 0.791508E+09
           
Annual Sum or Average 0.940840E+10 0.453399E+10 0.487441E+10 0.157273E+11 0.482449E+10
Minimum of Months 0.404542E+09 3770670.32 0.355420E+09 0.873226E+09 63617911.30
Maximum of Months 0.129053E+10 0.920368E+09 0.459145E+09 0.185682E+10 0.877959E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129052E+10 0.920361E+09 0.370157E+09 0.182434E+10 0.877958E+09
February 0.105716E+10 0.684280E+09 0.372881E+09 0.152542E+10 0.685728E+09
March 0.747229E+09 0.337223E+09 0.410006E+09 0.110667E+10 0.675433E+09
April 0.535973E+09 0.125590E+09 0.410383E+09 0.882451E+09 0.418749E+09
May 0.423174E+09 17984064.43 0.405190E+09 0.883362E+09 0.119606E+09
June 0.404540E+09 3770642.69 0.400769E+09 0.873223E+09 95591215.25
July 0.437603E+09 8042987.54 0.429560E+09 0.933820E+09 63617485.32
August 0.514816E+09 61792684.20 0.453023E+09 0.110202E+10 98780350.78
September 0.597765E+09 0.157535E+09 0.440230E+09 0.118124E+10 0.144339E+09
October 0.958349E+09 0.499207E+09 0.459142E+09 0.173563E+10 0.277758E+09
November 0.118022E+10 0.812590E+09 0.367628E+09 0.182222E+10 0.575413E+09
December 0.126099E+10 0.905576E+09 0.355418E+09 0.185680E+10 0.791507E+09
           
Annual Sum or Average 0.940834E+10 0.453395E+10 0.487439E+10 0.157272E+11 0.482448E+10
Minimum of Months 0.404540E+09 3770642.69 0.355418E+09 0.873223E+09 63617485.32
Maximum of Months 0.129052E+10 0.920361E+09 0.459142E+09 0.185680E+10 0.877958E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129053E+10 0.920368E+09 0.370159E+09 0.182435E+10 0.877959E+09
February 0.105717E+10 0.684285E+09 0.372883E+09 0.152543E+10 0.685728E+09
March 0.747233E+09 0.337225E+09 0.410008E+09 0.110668E+10 0.675433E+09
April 0.535976E+09 0.125591E+09 0.410385E+09 0.882456E+09 0.418749E+09
May 0.423176E+09 17984196.22 0.405192E+09 0.883365E+09 0.119606E+09
June 0.404542E+09 3770670.32 0.400771E+09 0.873226E+09 95591703.47
July 0.437605E+09 8043046.48 0.429562E+09 0.933824E+09 63617911.30
August 0.514818E+09 61793137.02 0.453025E+09 0.110202E+10 98780825.48
September 0.597768E+09 0.157536E+09 0.440232E+09 0.118125E+10 0.144340E+09
October 0.958355E+09 0.499210E+09 0.459145E+09 0.173564E+10 0.277758E+09
November 0.118023E+10 0.812596E+09 0.367630E+09 0.182223E+10 0.575413E+09
December 0.126100E+10 0.905582E+09 0.355420E+09 0.185682E+10 0.791508E+09
           
Annual Sum or Average 0.940840E+10 0.453399E+10 0.487441E+10 0.157273E+11 0.482449E+10
Minimum of Months 0.404542E+09 3770670.32 0.355420E+09 0.873226E+09 63617911.30
Maximum of Months 0.129053E+10 0.920368E+09 0.459145E+09 0.185682E+10 0.877959E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129052E+10 0.920361E+09 0.370157E+09 0.182434E+10 0.877958E+09
February 0.105716E+10 0.684280E+09 0.372881E+09 0.152542E+10 0.685728E+09
March 0.747229E+09 0.337223E+09 0.410006E+09 0.110667E+10 0.675433E+09
April 0.535973E+09 0.125590E+09 0.410383E+09 0.882451E+09 0.418749E+09
May 0.423174E+09 17984064.43 0.405190E+09 0.883362E+09 0.119606E+09
June 0.404540E+09 3770642.69 0.400769E+09 0.873223E+09 95591215.25
July 0.437603E+09 8042987.54 0.429560E+09 0.933820E+09 63617485.32
August 0.514816E+09 61792684.20 0.453023E+09 0.110202E+10 98780350.78
September 0.597765E+09 0.157535E+09 0.440230E+09 0.118124E+10 0.144339E+09
October 0.958349E+09 0.499207E+09 0.459142E+09 0.173563E+10 0.277758E+09
November 0.118022E+10 0.812590E+09 0.367628E+09 0.182222E+10 0.575413E+09
December 0.126099E+10 0.905576E+09 0.355418E+09 0.185680E+10 0.791507E+09
           
Annual Sum or Average 0.940834E+10 0.453395E+10 0.487439E+10 0.157272E+11 0.482448E+10
Minimum of Months 0.404540E+09 3770642.69 0.355418E+09 0.873223E+09 63617485.32
Maximum of Months 0.129052E+10 0.920361E+09 0.459142E+09 0.185680E+10 0.877958E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.129047E+10 0.920327E+09 0.370144E+09 0.182427E+10 0.877923E+09
February 0.105712E+10 0.684255E+09 0.372867E+09 0.152537E+10 0.685700E+09
March 0.747201E+09 0.337211E+09 0.409990E+09 0.110663E+10 0.675406E+09
April 0.535953E+09 0.125586E+09 0.410367E+09 0.882418E+09 0.418732E+09
May 0.423158E+09 17983405.49 0.405175E+09 0.883327E+09 0.119601E+09
June 0.404524E+09 3770504.53 0.400754E+09 0.873189E+09 95587606.60
July 0.437587E+09 8042692.84 0.429544E+09 0.933784E+09 63615134.24
August 0.514796E+09 61790420.09 0.453006E+09 0.110198E+10 98776606.82
September 0.597743E+09 0.157529E+09 0.440213E+09 0.118120E+10 0.144334E+09
October 0.958314E+09 0.499188E+09 0.459125E+09 0.173556E+10 0.277747E+09
November 0.118017E+10 0.812560E+09 0.367614E+09 0.182215E+10 0.575390E+09
December 0.126095E+10 0.905542E+09 0.355404E+09 0.185673E+10 0.791476E+09
           
Annual Sum or Average 0.940799E+10 0.453379E+10 0.487420E+10 0.157266E+11 0.482429E+10
Minimum of Months 0.404524E+09 3770504.53 0.355404E+09 0.873189E+09 63615134.24
Maximum of Months 0.129047E+10 0.920327E+09 0.459125E+09 0.185673E+10 0.877923E+09



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.679104E+09 0.367222E+09 0.311882E+09 0.822446E+09 0.111501E+10
February 0.694487E+09 0.351506E+09 0.342981E+09 0.871455E+09 0.892566E+09
March 0.757826E+09 0.335471E+09 0.422355E+09 0.990017E+09 0.875424E+09
April 0.910877E+09 0.419021E+09 0.491856E+09 0.137625E+10 0.555699E+09
May 0.782752E+09 0.254983E+09 0.527769E+09 0.148999E+10 0.173855E+09
June 0.841498E+09 0.295069E+09 0.546429E+09 0.162761E+10 0.154939E+09
July 0.793735E+09 0.220170E+09 0.573565E+09 0.152132E+10 0.126253E+09
August 0.802566E+09 0.245676E+09 0.556890E+09 0.152926E+10 0.184637E+09
September 0.715188E+09 0.245344E+09 0.469844E+09 0.131679E+10 0.194659E+09
October 0.756612E+09 0.326924E+09 0.429688E+09 0.132094E+10 0.362469E+09
November 0.627587E+09 0.315400E+09 0.312187E+09 0.871284E+09 0.767622E+09
December 0.623808E+09 0.331732E+09 0.292075E+09 0.780256E+09 0.106329E+10
           
Annual Sum or Average 0.898604E+10 0.370852E+10 0.527752E+10 0.145176E+11 0.646642E+10
Minimum of Months 0.623808E+09 0.220170E+09 0.292075E+09 0.780256E+09 0.126253E+09
Maximum of Months 0.910877E+09 0.419021E+09 0.573565E+09 0.162761E+10 0.111501E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.679104E+09 0.367222E+09 0.311882E+09 0.822446E+09 0.111501E+10
February 0.694487E+09 0.351506E+09 0.342981E+09 0.871455E+09 0.892566E+09
March 0.757826E+09 0.335471E+09 0.422355E+09 0.990017E+09 0.875424E+09
April 0.910877E+09 0.419021E+09 0.491856E+09 0.137625E+10 0.555699E+09
May 0.782752E+09 0.254983E+09 0.527769E+09 0.148999E+10 0.173855E+09
June 0.841498E+09 0.295069E+09 0.546429E+09 0.162761E+10 0.154939E+09
July 0.793735E+09 0.220170E+09 0.573565E+09 0.152132E+10 0.126253E+09
August 0.802566E+09 0.245676E+09 0.556890E+09 0.152926E+10 0.184637E+09
September 0.715188E+09 0.245344E+09 0.469844E+09 0.131679E+10 0.194659E+09
October 0.756612E+09 0.326924E+09 0.429688E+09 0.132094E+10 0.362469E+09
November 0.627587E+09 0.315400E+09 0.312187E+09 0.871284E+09 0.767622E+09
December 0.623808E+09 0.331732E+09 0.292075E+09 0.780256E+09 0.106329E+10
           
Annual Sum or Average 0.898604E+10 0.370852E+10 0.527752E+10 0.145176E+11 0.646642E+10
Minimum of Months 0.623808E+09 0.220170E+09 0.292075E+09 0.780256E+09 0.126253E+09
Maximum of Months 0.910877E+09 0.419021E+09 0.573565E+09 0.162761E+10 0.111501E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.679091E+09 0.367215E+09 0.311876E+09 0.822431E+09 0.111499E+10
February 0.694475E+09 0.351500E+09 0.342975E+09 0.871439E+09 0.892549E+09
March 0.757812E+09 0.335464E+09 0.422348E+09 0.989999E+09 0.875408E+09
April 0.910860E+09 0.419013E+09 0.491847E+09 0.137622E+10 0.555688E+09
May 0.782738E+09 0.254978E+09 0.527759E+09 0.148997E+10 0.173852E+09
June 0.841483E+09 0.295063E+09 0.546419E+09 0.162758E+10 0.154936E+09
July 0.793720E+09 0.220166E+09 0.573554E+09 0.152130E+10 0.126250E+09
August 0.802552E+09 0.245672E+09 0.556880E+09 0.152923E+10 0.184634E+09
September 0.715175E+09 0.245339E+09 0.469836E+09 0.131677E+10 0.194656E+09
October 0.756598E+09 0.326918E+09 0.429680E+09 0.132091E+10 0.362463E+09
November 0.627576E+09 0.315394E+09 0.312181E+09 0.871268E+09 0.767608E+09
December 0.623796E+09 0.331726E+09 0.292070E+09 0.780242E+09 0.106327E+10
           
Annual Sum or Average 0.898588E+10 0.370845E+10 0.527743E+10 0.145174E+11 0.646630E+10
Minimum of Months 0.623796E+09 0.220166E+09 0.292070E+09 0.780242E+09 0.126250E+09
Maximum of Months 0.910860E+09 0.419013E+09 0.573554E+09 0.162758E+10 0.111499E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111635E+10 0.00 0.111635E+10 0.787268E+09 0.439925E+10
February 0.118957E+10 0.00 0.118957E+10 0.964611E+09 0.334717E+10
March 0.152787E+10 0.00 0.152787E+10 0.154939E+10 0.319606E+10
April 0.174505E+10 7162306.50 0.173789E+10 0.238773E+10 0.193656E+10
May 0.204249E+10 74709672.45 0.196778E+10 0.422360E+10 0.574348E+09
June 0.224782E+10 0.155644E+09 0.209218E+10 0.484376E+10 0.479434E+09
July 0.225408E+10 85876258.80 0.216820E+10 0.481554E+10 0.327610E+09
August 0.201857E+10 15876296.36 0.200269E+10 0.436022E+10 0.459679E+09
September 0.168734E+10 129958.71 0.168721E+10 0.334174E+10 0.635404E+09
October 0.151514E+10 0.00 0.151514E+10 0.277708E+10 0.124458E+10
November 0.111313E+10 0.00 0.111313E+10 0.119332E+10 0.273684E+10
December 0.103778E+10 0.00 0.103778E+10 0.854705E+09 0.377150E+10
           
Annual Sum or Average 0.194952E+11 0.339399E+09 0.191558E+11 0.320990E+11 0.231084E+11
Minimum of Months 0.103778E+10 0.00 0.103778E+10 0.787268E+09 0.327610E+09
Maximum of Months 0.225408E+10 0.155644E+09 0.216820E+10 0.484376E+10 0.439925E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.191536E+10 0.975310E+09 0.940054E+09 0.220709E+10 0.275498E+10
February 0.192642E+10 0.930024E+09 0.996395E+09 0.236048E+10 0.210951E+10
March 0.250890E+10 0.120997E+10 0.129893E+10 0.334774E+10 0.203383E+10
April 0.266441E+10 0.120504E+10 0.145937E+10 0.407467E+10 0.128999E+10
May 0.283783E+10 0.123054E+10 0.160729E+10 0.528348E+10 0.403450E+09
June 0.278520E+10 0.110453E+10 0.168067E+10 0.538859E+10 0.333404E+09
July 0.277484E+10 0.101544E+10 0.175940E+10 0.537211E+10 0.229001E+09
August 0.255693E+10 0.879093E+09 0.167784E+10 0.495894E+10 0.321015E+09
September 0.219191E+10 0.753571E+09 0.143834E+10 0.403709E+10 0.439605E+09
October 0.223826E+10 0.944538E+09 0.129372E+10 0.389826E+10 0.827550E+09
November 0.191773E+10 0.978309E+09 0.939421E+09 0.262518E+10 0.174564E+10
December 0.156024E+10 0.706755E+09 0.853486E+09 0.188971E+10 0.240581E+10
           
Annual Sum or Average 0.278780E+11 0.119331E+11 0.159449E+11 0.454433E+11 0.148938E+11
Minimum of Months 0.156024E+10 0.706755E+09 0.853486E+09 0.188971E+10 0.229001E+09
Maximum of Months 0.283783E+10 0.123054E+10 0.175940E+10 0.538859E+10 0.275498E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.645276E+10 0.460194E+10 0.185082E+10 0.904264E+10 0.431028E+10
February 0.528594E+10 0.342150E+10 0.186444E+10 0.757862E+10 0.333709E+10
March 0.373623E+10 0.168616E+10 0.205006E+10 0.551450E+10 0.324369E+10
April 0.267991E+10 0.627970E+09 0.205194E+10 0.440876E+10 0.205322E+10
May 0.211590E+10 89922872.05 0.202598E+10 0.442181E+10 0.598691E+09
June 0.202273E+10 18853748.06 0.200387E+10 0.438548E+10 0.491633E+09
July 0.218805E+10 40216078.06 0.214783E+10 0.470457E+10 0.320626E+09
August 0.257412E+10 0.308972E+09 0.226515E+10 0.553595E+10 0.498782E+09
September 0.298889E+10 0.787698E+09 0.220119E+10 0.588479E+10 0.710375E+09
October 0.479186E+10 0.249610E+10 0.229575E+10 0.862303E+10 0.138736E+10
November 0.590124E+10 0.406306E+10 0.183817E+10 0.906031E+10 0.281637E+10
December 0.630513E+10 0.452801E+10 0.177712E+10 0.924092E+10 0.382745E+10
           
Annual Sum or Average 0.470427E+11 0.226704E+11 0.243723E+11 0.784014E+11 0.235956E+11
Minimum of Months 0.202273E+10 18853748.06 0.177712E+10 0.438548E+10 0.320626E+09
Maximum of Months 0.645276E+10 0.460194E+10 0.229575E+10 0.924092E+10 0.431028E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.203729E+10 0.110165E+10 0.935636E+09 0.254380E+10 0.298098E+10
February 0.208344E+10 0.105451E+10 0.102893E+10 0.270308E+10 0.231334E+10
March 0.227345E+10 0.100640E+10 0.126705E+10 0.306895E+10 0.222931E+10
April 0.273260E+10 0.125705E+10 0.147555E+10 0.422356E+10 0.144055E+10
May 0.234823E+10 0.764941E+09 0.158329E+10 0.450260E+10 0.472226E+09
June 0.252447E+10 0.885198E+09 0.163927E+10 0.493945E+10 0.405355E+09
July 0.238118E+10 0.660502E+09 0.172068E+10 0.466783E+10 0.287709E+09
August 0.240767E+10 0.737022E+09 0.167065E+10 0.472389E+10 0.399109E+09
September 0.214554E+10 0.736024E+09 0.140952E+10 0.398343E+10 0.508277E+09
October 0.226981E+10 0.980761E+09 0.128905E+10 0.402671E+10 0.946052E+09
November 0.188274E+10 0.946191E+09 0.936552E+09 0.271709E+10 0.194004E+10
December 0.187140E+10 0.995187E+09 0.876217E+09 0.247380E+10 0.260036E+10
           
Annual Sum or Average 0.269578E+11 0.111254E+11 0.158324E+11 0.445742E+11 0.165233E+11
Minimum of Months 0.187140E+10 0.660502E+09 0.876217E+09 0.247380E+10 0.287709E+09
Maximum of Months 0.273260E+10 0.125705E+10 0.172068E+10 0.493945E+10 0.298098E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.111635E+10 0.00 0.111635E+10 0.866551E+09 0.402982E+10
February 0.118957E+10 0.00 0.118957E+10 0.101943E+10 0.307984E+10
March 0.152787E+10 0.00 0.152787E+10 0.159070E+10 0.299619E+10
April 0.174505E+10 7162306.50 0.173789E+10 0.237902E+10 0.188412E+10
May 0.204249E+10 74709672.45 0.196778E+10 0.415405E+10 0.607128E+09
June 0.224782E+10 0.155644E+09 0.209218E+10 0.476720E+10 0.514104E+09
July 0.225408E+10 85876258.80 0.216820E+10 0.472508E+10 0.364535E+09
August 0.201857E+10 15876296.36 0.200269E+10 0.428808E+10 0.488797E+09
September 0.168734E+10 129958.71 0.168721E+10 0.327629E+10 0.663694E+09
October 0.151514E+10 0.00 0.151514E+10 0.274595E+10 0.122420E+10
November 0.111313E+10 0.00 0.111313E+10 0.123652E+10 0.254819E+10
December 0.103778E+10 0.00 0.103778E+10 0.913261E+09 0.346790E+10
           
Annual Sum or Average 0.194952E+11 0.339399E+09 0.191558E+11 0.319621E+11 0.218685E+11
Minimum of Months 0.103778E+10 0.00 0.103778E+10 0.866551E+09 0.364535E+09
Maximum of Months 0.225408E+10 0.155644E+09 0.216820E+10 0.476720E+10 0.402982E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.191536E+10 0.975310E+09 0.940054E+09 0.229053E+10 0.254201E+10
February 0.192642E+10 0.930024E+09 0.996395E+09 0.241332E+10 0.196037E+10
March 0.250890E+10 0.120997E+10 0.129893E+10 0.336841E+10 0.193399E+10
April 0.266441E+10 0.120504E+10 0.145937E+10 0.405888E+10 0.127084E+10
May 0.283783E+10 0.123054E+10 0.160729E+10 0.522983E+10 0.425281E+09
June 0.278520E+10 0.110453E+10 0.168067E+10 0.533314E+10 0.358044E+09
July 0.277484E+10 0.101544E+10 0.175940E+10 0.530922E+10 0.253832E+09
August 0.255693E+10 0.879093E+09 0.167784E+10 0.490541E+10 0.340691E+09
September 0.219191E+10 0.753571E+09 0.143834E+10 0.399069E+10 0.458994E+09
October 0.223826E+10 0.944538E+09 0.129372E+10 0.387088E+10 0.819931E+09
November 0.191773E+10 0.978309E+09 0.939421E+09 0.265317E+10 0.165671E+10
December 0.156024E+10 0.706755E+09 0.853486E+09 0.194049E+10 0.223879E+10
           
Annual Sum or Average 0.278780E+11 0.119331E+11 0.159449E+11 0.453640E+11 0.142595E+11
Minimum of Months 0.156024E+10 0.706755E+09 0.853486E+09 0.194049E+10 0.253832E+09
Maximum of Months 0.283783E+10 0.123054E+10 0.175940E+10 0.533314E+10 0.254201E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.645276E+10 0.460194E+10 0.185082E+10 0.912220E+10 0.403156E+10
February 0.528594E+10 0.342150E+10 0.186444E+10 0.763683E+10 0.313111E+10
March 0.373623E+10 0.168616E+10 0.205006E+10 0.553727E+10 0.307770E+10
April 0.267991E+10 0.627970E+09 0.205194E+10 0.438539E+10 0.201093E+10
May 0.211590E+10 89922872.05 0.202598E+10 0.435173E+10 0.632373E+09
June 0.202273E+10 18853748.06 0.200387E+10 0.431211E+10 0.528963E+09
July 0.218805E+10 40216078.06 0.214783E+10 0.461174E+10 0.356953E+09
August 0.257412E+10 0.308972E+09 0.226515E+10 0.546063E+10 0.530579E+09
September 0.298889E+10 0.787698E+09 0.220119E+10 0.581768E+10 0.740574E+09
October 0.479186E+10 0.249610E+10 0.229575E+10 0.857325E+10 0.138310E+10
November 0.590124E+10 0.406306E+10 0.183817E+10 0.907352E+10 0.270728E+10
December 0.630513E+10 0.452801E+10 0.177712E+10 0.928915E+10 0.360078E+10
           
Annual Sum or Average 0.470427E+11 0.226704E+11 0.243723E+11 0.781715E+11 0.227319E+11
Minimum of Months 0.202273E+10 18853748.06 0.177712E+10 0.431211E+10 0.356953E+09
Maximum of Months 0.645276E+10 0.460194E+10 0.229575E+10 0.928915E+10 0.403156E+10



Table of Contents

Report: WindowEnergyReportMonthly

For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] SURFACE WINDOW HEAT GAIN ENERGY [J] SURFACE WINDOW HEAT LOSS ENERGY [J]
January 0.203729E+10 0.110165E+10 0.935636E+09 0.258644E+10 0.277807E+10
February 0.208344E+10 0.105451E+10 0.102893E+10 0.272846E+10 0.216638E+10
March 0.227345E+10 0.100640E+10 0.126705E+10 0.308158E+10 0.211511E+10
April 0.273260E+10 0.125705E+10 0.147555E+10 0.420340E+10 0.141148E+10
May 0.234823E+10 0.764941E+09 0.158329E+10 0.445807E+10 0.489515E+09
June 0.252447E+10 0.885198E+09 0.163927E+10 0.489041E+10 0.423720E+09
July 0.238118E+10 0.660502E+09 0.172068E+10 0.461230E+10 0.304613E+09
August 0.240767E+10 0.737022E+09 0.167065E+10 0.467633E+10 0.415078E+09
September 0.214554E+10 0.736024E+09 0.140952E+10 0.394396E+10 0.522755E+09
October 0.226981E+10 0.980761E+09 0.128905E+10 0.400137E+10 0.935806E+09
November 0.188274E+10 0.946191E+09 0.936552E+09 0.273241E+10 0.183919E+10
December 0.187140E+10 0.995187E+09 0.876217E+09 0.250166E+10 0.242937E+10
           
Annual Sum or Average 0.269578E+11 0.111254E+11 0.158324E+11 0.444164E+11 0.158311E+11
Minimum of Months 0.187140E+10 0.660502E+09 0.876217E+09 0.250166E+10 0.304613E+09
Maximum of Months 0.273260E+10 0.125705E+10 0.172068E+10 0.489041E+10 0.277807E+10



Table of Contents

Report: WindowZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 251.33 1828.24 416.79 0.00 416.79 0.00 0.00
February 358.24 1552.14 491.71 0.00 491.71 0.00 0.00
March 542.22 1317.25 570.43 0.00 570.43 0.00 0.00
April 901.41 785.92 673.24 2.76 670.47 0.00 0.00
May 1573.66 214.23 762.57 27.89 734.67 0.00 0.00
June 1864.52 177.37 867.20 60.05 807.15 0.00 0.00
July 1786.78 119.47 841.56 32.06 809.50 0.00 0.00
August 1608.85 172.20 753.63 5.93 747.71 0.00 0.00
September 1280.44 257.83 650.97 0.05 650.92 0.00 0.00
October 1019.69 494.53 565.68 0.00 565.68 0.00 0.00
November 424.97 1179.37 429.44 0.00 429.44 0.00 0.00
December 275.34 1608.64 387.46 0.00 387.46 0.00 0.00
               
Annual Sum or Average 994.42 805.11 618.18 10.76 607.42 0.00 0.00
Minimum of Months 251.33 119.47 387.46 0.00 387.46 0.00 0.00
Maximum of Months 1864.52 1828.24 867.20 60.05 809.50 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 807.98 1108.19 715.12 364.14 350.98 0.00 0.00
February 962.66 933.94 796.31 384.44 411.87 0.00 0.00
March 1251.06 793.75 936.72 451.75 484.97 0.00 0.00
April 1589.39 484.13 1027.94 464.91 563.03 0.00 0.00
May 1992.47 140.34 1059.53 459.43 600.10 0.00 0.00
June 2097.93 109.50 1074.54 426.13 648.41 0.00 0.00
July 2025.86 67.04 1036.01 379.12 656.89 0.00 0.00
August 1869.75 96.08 954.65 328.22 626.44 0.00 0.00
September 1569.57 166.33 845.65 290.73 554.92 0.00 0.00
October 1468.21 306.82 835.67 352.65 483.02 0.00 0.00
November 1011.04 705.36 739.87 377.44 362.43 0.00 0.00
December 692.07 963.95 582.53 263.87 318.66 0.00 0.00
               
Annual Sum or Average 1447.46 487.32 884.01 378.40 505.61 0.00 0.00
Minimum of Months 692.07 67.04 582.53 263.87 318.66 0.00 0.00
Maximum of Months 2097.93 1108.19 1074.54 464.91 656.89 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3405.64 1638.95 2409.11 1718.11 691.00 0.00 0.00
February 3152.73 1417.25 2184.93 1414.26 770.67 0.00 0.00
March 2065.91 1260.88 1394.91 629.52 765.39 0.00 0.00
April 1702.25 807.77 1033.89 242.26 791.63 0.00 0.00
May 1649.04 223.28 789.97 33.57 756.40 0.00 0.00
June 1684.45 184.40 780.36 7.27 773.08 0.00 0.00
July 1743.23 118.76 816.91 15.01 801.89 0.00 0.00
August 2057.22 184.40 961.05 115.35 845.69 0.00 0.00
September 2278.61 278.43 1153.09 303.89 849.20 0.00 0.00
October 3240.03 518.51 1789.02 931.91 857.12 0.00 0.00
November 3515.07 1109.97 2276.64 1567.49 709.16 0.00 0.00
December 3466.24 1477.56 2353.99 1690.51 663.49 0.00 0.00
               
Annual Sum or Average 2493.52 764.91 1491.68 718.85 772.82 0.00 0.00
Minimum of Months 1649.04 118.76 780.36 7.27 663.49 0.00 0.00
Maximum of Months 3515.07 1638.95 2409.11 1718.11 857.12 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 921.19 1248.88 760.64 411.31 349.33 0.00 0.00
February 1080.67 1106.85 861.21 435.89 425.32 0.00 0.00
March 1108.88 980.53 848.81 375.75 473.07 0.00 0.00
April 1592.87 643.17 1054.25 484.97 569.27 0.00 0.00
May 1668.89 194.73 876.73 285.60 591.14 0.00 0.00
June 1883.79 179.33 973.95 341.51 632.44 0.00 0.00
July 1703.98 141.41 889.03 246.60 642.43 0.00 0.00
August 1712.87 206.81 898.93 275.17 623.75 0.00 0.00
September 1524.05 225.30 827.76 283.96 543.80 0.00 0.00
October 1479.54 405.99 847.45 366.18 481.28 0.00 0.00
November 1008.42 888.45 726.37 365.04 361.33 0.00 0.00
December 873.94 1190.95 698.71 371.56 327.14 0.00 0.00
               
Annual Sum or Average 1381.04 615.14 854.83 352.79 502.04 0.00 0.00
Minimum of Months 873.94 141.41 698.71 246.60 327.14 0.00 0.00
Maximum of Months 1883.79 1248.88 1054.25 484.97 642.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 293.93 1642.49 416.80 0.00 416.80 0.00 0.00
February 398.73 1383.59 491.72 0.00 491.72 0.00 0.00
March 578.48 1193.27 570.44 0.00 570.44 0.00 0.00
April 921.19 747.13 673.25 2.76 670.48 0.00 0.00
May 1576.91 214.44 762.58 27.89 734.69 0.00 0.00
June 1868.73 184.97 867.22 60.05 807.17 0.00 0.00
July 1797.92 122.32 841.58 32.06 809.51 0.00 0.00
August 1627.92 171.62 753.65 5.93 747.72 0.00 0.00
September 1289.25 245.14 650.98 0.05 650.93 0.00 0.00
October 1036.84 464.67 565.69 0.00 565.69 0.00 0.00
November 460.39 1055.88 429.45 0.00 429.45 0.00 0.00
December 319.11 1408.12 387.46 0.00 387.46 0.00 0.00
               
Annual Sum or Average 1017.85 732.76 618.19 10.76 607.43 0.00 0.00
Minimum of Months 293.93 122.32 387.46 0.00 387.46 0.00 0.00
Maximum of Months 1868.73 1642.49 867.22 60.05 809.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 824.03 1028.59 715.11 364.14 350.98 0.00 0.00
February 975.73 871.99 796.30 384.43 411.87 0.00 0.00
March 1249.90 759.35 936.72 451.75 484.96 0.00 0.00
April 1572.02 497.68 1027.94 464.91 563.03 0.00 0.00
May 1972.62 150.63 1059.53 459.43 600.10 0.00 0.00
June 2078.93 128.63 1074.54 426.13 648.41 0.00 0.00
July 2005.72 85.50 1036.01 379.12 656.88 0.00 0.00
August 1851.46 119.85 954.65 328.22 626.43 0.00 0.00
September 1557.52 169.60 845.64 290.73 554.91 0.00 0.00
October 1455.45 308.97 835.67 352.65 483.02 0.00 0.00
November 1012.80 673.47 739.86 377.43 362.43 0.00 0.00
December 705.54 898.23 582.53 263.87 318.66 0.00 0.00
               
Annual Sum or Average 1441.00 472.28 884.01 378.40 505.61 0.00 0.00
Minimum of Months 705.54 85.50 582.53 263.87 318.66 0.00 0.00
Maximum of Months 2078.93 1028.59 1074.54 464.91 656.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3376.14 1609.27 2409.18 1718.17 691.02 0.00 0.00
February 3132.70 1379.42 2184.99 1414.31 770.68 0.00 0.00
March 2058.88 1211.05 1394.95 629.54 765.41 0.00 0.00
April 1700.91 792.14 1033.92 242.27 791.64 0.00 0.00
May 1650.91 223.53 789.99 33.57 756.41 0.00 0.00
June 1691.93 189.67 780.37 7.27 773.10 0.00 0.00
July 1756.49 119.71 816.92 15.01 801.91 0.00 0.00
August 2066.89 186.22 961.07 115.36 845.71 0.00 0.00
September 2270.37 274.06 1153.12 303.90 849.22 0.00 0.00
October 3219.47 517.98 1789.07 931.94 857.14 0.00 0.00
November 3495.49 1086.56 2276.71 1567.54 709.17 0.00 0.00
December 3450.17 1429.01 2354.07 1690.56 663.50 0.00 0.00
               
Annual Sum or Average 2486.09 748.21 1491.72 718.87 772.84 0.00 0.00
Minimum of Months 1650.91 119.71 780.37 7.27 663.50 0.00 0.00
Maximum of Months 3495.49 1609.27 2409.18 1718.17 857.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 949.75 1112.97 760.64 411.31 349.33 0.00 0.00
February 1117.34 956.24 861.21 435.89 425.32 0.00 0.00
March 1145.82 832.33 848.81 375.75 473.06 0.00 0.00
April 1629.46 555.77 1054.25 484.97 569.27 0.00 0.00
May 1681.08 176.31 876.73 285.60 591.13 0.00 0.00
June 1905.65 156.39 973.95 341.51 632.43 0.00 0.00
July 1742.77 107.42 889.03 246.60 642.43 0.00 0.00
August 1763.70 149.01 898.92 275.17 623.75 0.00 0.00
September 1536.82 196.09 827.76 283.96 543.80 0.00 0.00
October 1503.40 353.22 847.45 366.17 481.28 0.00 0.00
November 1048.26 748.47 726.37 365.04 361.32 0.00 0.00
December 923.61 970.86 698.70 371.56 327.14 0.00 0.00
               
Annual Sum or Average 1413.44 523.95 854.83 352.79 502.04 0.00 0.00
Minimum of Months 923.61 107.42 698.70 246.60 327.14 0.00 0.00
Maximum of Months 1905.65 1112.97 1054.25 484.97 642.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 323.53 1504.56 416.80 0.00 416.80 0.00 0.00
February 421.39 1273.08 491.72 0.00 491.72 0.00 0.00
March 593.90 1118.65 570.44 0.00 570.44 0.00 0.00
April 917.83 726.90 673.25 2.76 670.48 0.00 0.00
May 1550.94 226.68 762.58 27.89 734.69 0.00 0.00
June 1839.20 198.34 867.22 60.05 807.17 0.00 0.00
July 1764.14 136.10 841.58 32.06 809.51 0.00 0.00
August 1600.98 182.50 753.65 5.93 747.72 0.00 0.00
September 1264.00 256.05 650.98 0.05 650.93 0.00 0.00
October 1025.22 457.06 565.69 0.00 565.69 0.00 0.00
November 477.05 983.10 429.45 0.00 429.45 0.00 0.00
December 340.97 1294.77 387.46 0.00 387.46 0.00 0.00
               
Annual Sum or Average 1013.51 693.45 618.19 10.76 607.43 0.00 0.00
Minimum of Months 323.53 136.10 387.46 0.00 387.46 0.00 0.00
Maximum of Months 1839.20 1504.56 867.22 60.05 809.51 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 855.19 949.08 715.11 364.14 350.98 0.00 0.00
February 997.57 810.34 796.30 384.43 411.87 0.00 0.00
March 1257.62 722.07 936.72 451.75 484.96 0.00 0.00
April 1565.93 490.29 1027.94 464.91 563.03 0.00 0.00
May 1952.59 158.78 1059.53 459.43 600.10 0.00 0.00
June 2057.54 138.13 1074.54 426.13 648.41 0.00 0.00
July 1982.24 94.77 1036.01 379.12 656.88 0.00 0.00
August 1831.47 127.20 954.65 328.22 626.43 0.00 0.00
September 1539.62 177.08 845.64 290.73 554.91 0.00 0.00
October 1445.22 306.13 835.67 352.65 483.02 0.00 0.00
November 1023.60 639.16 739.86 377.43 362.43 0.00 0.00
December 724.50 835.87 582.53 263.87 318.66 0.00 0.00
               
Annual Sum or Average 1438.48 452.17 884.01 378.40 505.61 0.00 0.00
Minimum of Months 724.50 94.77 582.53 263.87 318.66 0.00 0.00
Maximum of Months 2057.54 949.08 1074.54 464.91 656.88 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 3405.84 1505.21 2409.18 1718.17 691.02 0.00 0.00
February 3156.76 1294.27 2184.99 1414.31 770.68 0.00 0.00
March 2067.38 1149.08 1394.95 629.54 765.41 0.00 0.00
April 1691.90 775.82 1033.92 242.27 791.64 0.00 0.00
May 1624.75 236.10 789.99 33.57 756.41 0.00 0.00
June 1663.62 204.08 780.37 7.27 773.10 0.00 0.00
July 1721.83 133.27 816.92 15.01 801.91 0.00 0.00
August 2038.77 198.10 961.07 115.36 845.71 0.00 0.00
September 2244.48 285.72 1153.12 303.90 849.22 0.00 0.00
October 3200.89 516.39 1789.07 931.94 857.14 0.00 0.00
November 3500.59 1044.47 2276.71 1567.54 709.17 0.00 0.00
December 3468.17 1344.38 2354.07 1690.56 663.50 0.00 0.00
               
Annual Sum or Average 2478.80 720.82 1491.72 718.87 772.84 0.00 0.00
Minimum of Months 1624.75 133.27 780.37 7.27 663.50 0.00 0.00
Maximum of Months 3500.59 1505.21 2409.18 1718.17 857.14 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 965.67 1037.21 760.64 411.31 349.33 0.00 0.00
February 1127.83 895.50 861.21 435.89 425.32 0.00 0.00
March 1150.53 789.69 848.81 375.75 473.06 0.00 0.00
April 1621.68 544.55 1054.25 484.97 569.27 0.00 0.00
May 1664.45 182.76 876.73 285.60 591.13 0.00 0.00
June 1886.73 163.47 973.95 341.51 632.43 0.00 0.00
July 1722.04 113.73 889.03 246.60 642.43 0.00 0.00
August 1745.94 154.97 898.92 275.17 623.75 0.00 0.00
September 1521.59 201.68 827.76 283.96 543.80 0.00 0.00
October 1493.94 349.39 847.45 366.17 481.28 0.00 0.00
November 1054.17 709.56 726.37 365.04 361.32 0.00 0.00
December 934.01 907.02 698.70 371.56 327.14 0.00 0.00
               
Annual Sum or Average 1408.43 502.00 854.83 352.79 502.04 0.00 0.00
Minimum of Months 934.01 113.73 698.70 246.60 327.14 0.00 0.00
Maximum of Months 1886.73 1037.21 1054.25 484.97 642.43 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN RATE [W] ZONE WINDOWS TOTAL HEAT LOSS RATE [W] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.673171E+09 0.489676E+10 0.111634E+10 0.00 0.111634E+10 0.00 0.00
February 0.866645E+09 0.375493E+10 0.118956E+10 0.00 0.118956E+10 0.00 0.00
March 0.145229E+10 0.352811E+10 0.152784E+10 0.00 0.152784E+10 0.00 0.00
April 0.233645E+10 0.203712E+10 0.174503E+10 7162092.90 0.173786E+10 0.00 0.00
May 0.421490E+10 0.573806E+09 0.204246E+10 74707444.46 0.196775E+10 0.00 0.00
June 0.483284E+10 0.459730E+09 0.224778E+10 0.155640E+09 0.209214E+10 0.00 0.00
July 0.478571E+10 0.319999E+09 0.225404E+10 85873697.81 0.216816E+10 0.00 0.00
August 0.430916E+10 0.461212E+09 0.201853E+10 15875822.90 0.200266E+10 0.00 0.00
September 0.331890E+10 0.668291E+09 0.168731E+10 129954.84 0.168718E+10 0.00 0.00
October 0.273112E+10 0.132455E+10 0.151512E+10 0.00 0.151512E+10 0.00 0.00
November 0.110153E+10 0.305693E+10 0.111311E+10 0.00 0.111311E+10 0.00 0.00
December 0.737464E+09 0.430858E+10 0.103776E+10 0.00 0.103776E+10 0.00 0.00
               
Annual Sum or Average 0.313602E+11 0.253900E+11 0.194949E+11 0.339389E+09 0.191555E+11 0.00 0.00
Minimum of Months 0.673171E+09 0.319999E+09 0.103776E+10 0.00 0.103776E+10 0.00 0.00
Maximum of Months 0.483284E+10 0.489676E+10 0.225404E+10 0.155640E+09 0.216816E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.216409E+10 0.296818E+10 0.191537E+10 0.975314E+09 0.940057E+09 0.00 0.00
February 0.232887E+10 0.225940E+10 0.192643E+10 0.930028E+09 0.996399E+09 0.00 0.00
March 0.335084E+10 0.212599E+10 0.250891E+10 0.120998E+10 0.129893E+10 0.00 0.00
April 0.411969E+10 0.125485E+10 0.266442E+10 0.120504E+10 0.145938E+10 0.00 0.00
May 0.533663E+10 0.375893E+09 0.283785E+10 0.123054E+10 0.160730E+10 0.00 0.00
June 0.543784E+10 0.283827E+09 0.278521E+10 0.110454E+10 0.168067E+10 0.00 0.00
July 0.542606E+10 0.179568E+09 0.277485E+10 0.101545E+10 0.175941E+10 0.00 0.00
August 0.500793E+10 0.257337E+09 0.255694E+10 0.879096E+09 0.167785E+10 0.00 0.00
September 0.406831E+10 0.431117E+09 0.219192E+10 0.753574E+09 0.143834E+10 0.00 0.00
October 0.393246E+10 0.821779E+09 0.223827E+10 0.944542E+09 0.129373E+10 0.00 0.00
November 0.262060E+10 0.182829E+10 0.191774E+10 0.978313E+09 0.939424E+09 0.00 0.00
December 0.185365E+10 0.258183E+10 0.156025E+10 0.706758E+09 0.853490E+09 0.00 0.00
               
Annual Sum or Average 0.456470E+11 0.153681E+11 0.278782E+11 0.119332E+11 0.159450E+11 0.00 0.00
Minimum of Months 0.185365E+10 0.179568E+09 0.156025E+10 0.706758E+09 0.853490E+09 0.00 0.00
Maximum of Months 0.543784E+10 0.296818E+10 0.283785E+10 0.123054E+10 0.175941E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.912166E+10 0.438976E+10 0.645256E+10 0.460178E+10 0.185078E+10 0.00 0.00
February 0.762708E+10 0.342861E+10 0.528578E+10 0.342138E+10 0.186440E+10 0.00 0.00
March 0.553334E+10 0.337714E+10 0.373613E+10 0.168611E+10 0.205002E+10 0.00 0.00
April 0.441223E+10 0.209373E+10 0.267985E+10 0.627949E+09 0.205190E+10 0.00 0.00
May 0.441678E+10 0.598026E+09 0.211586E+10 89919926.79 0.202594E+10 0.00 0.00
June 0.436609E+10 0.477953E+09 0.202269E+10 18853130.54 0.200383E+10 0.00 0.00
July 0.466907E+10 0.318086E+09 0.218800E+10 40214760.86 0.214779E+10 0.00 0.00
August 0.551007E+10 0.493899E+09 0.257406E+10 0.308962E+09 0.226510E+10 0.00 0.00
September 0.590617E+10 0.721691E+09 0.298881E+10 0.787672E+09 0.220114E+10 0.00 0.00
October 0.867809E+10 0.138878E+10 0.479172E+10 0.249602E+10 0.229570E+10 0.00 0.00
November 0.911106E+10 0.287704E+10 0.590106E+10 0.406293E+10 0.183813E+10 0.00 0.00
December 0.928397E+10 0.395751E+10 0.630494E+10 0.452786E+10 0.177708E+10 0.00 0.00
               
Annual Sum or Average 0.786356E+11 0.241222E+11 0.470415E+11 0.226697E+11 0.243718E+11 0.00 0.00
Minimum of Months 0.436609E+10 0.318086E+09 0.202269E+10 18853130.54 0.177708E+10 0.00 0.00
Maximum of Months 0.928397E+10 0.438976E+10 0.645256E+10 0.460178E+10 0.229570E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.246732E+10 0.334501E+10 0.203730E+10 0.110166E+10 0.935640E+09 0.00 0.00
February 0.261435E+10 0.267768E+10 0.208345E+10 0.105451E+10 0.102894E+10 0.00 0.00
March 0.297003E+10 0.262626E+10 0.227346E+10 0.100641E+10 0.126706E+10 0.00 0.00
April 0.412871E+10 0.166709E+10 0.273261E+10 0.125705E+10 0.147556E+10 0.00 0.00
May 0.446995E+10 0.521562E+09 0.234824E+10 0.764944E+09 0.158330E+10 0.00 0.00
June 0.488280E+10 0.464814E+09 0.252448E+10 0.885201E+09 0.163928E+10 0.00 0.00
July 0.456394E+10 0.378755E+09 0.238119E+10 0.660505E+09 0.172068E+10 0.00 0.00
August 0.458774E+10 0.553909E+09 0.240768E+10 0.737025E+09 0.167066E+10 0.00 0.00
September 0.395035E+10 0.583974E+09 0.214555E+10 0.736027E+09 0.140952E+10 0.00 0.00
October 0.396279E+10 0.108740E+10 0.226982E+10 0.980765E+09 0.128906E+10 0.00 0.00
November 0.261384E+10 0.230285E+10 0.188275E+10 0.946195E+09 0.936555E+09 0.00 0.00
December 0.234075E+10 0.318985E+10 0.187141E+10 0.995191E+09 0.876220E+09 0.00 0.00
               
Annual Sum or Average 0.435526E+11 0.193992E+11 0.269580E+11 0.111255E+11 0.158325E+11 0.00 0.00
Minimum of Months 0.234075E+10 0.378755E+09 0.187141E+10 0.660505E+09 0.876220E+09 0.00 0.00
Maximum of Months 0.488280E+10 0.334501E+10 0.273261E+10 0.125705E+10 0.172068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.787268E+09 0.439925E+10 0.111635E+10 0.00 0.111635E+10 0.00 0.00
February 0.964611E+09 0.334717E+10 0.118957E+10 0.00 0.118957E+10 0.00 0.00
March 0.154939E+10 0.319606E+10 0.152787E+10 0.00 0.152787E+10 0.00 0.00
April 0.238773E+10 0.193656E+10 0.174505E+10 7162306.50 0.173789E+10 0.00 0.00
May 0.422360E+10 0.574348E+09 0.204249E+10 74709672.45 0.196778E+10 0.00 0.00
June 0.484376E+10 0.479434E+09 0.224782E+10 0.155644E+09 0.209218E+10 0.00 0.00
July 0.481554E+10 0.327610E+09 0.225408E+10 85876258.80 0.216820E+10 0.00 0.00
August 0.436022E+10 0.459679E+09 0.201857E+10 15876296.36 0.200269E+10 0.00 0.00
September 0.334174E+10 0.635404E+09 0.168734E+10 129958.71 0.168721E+10 0.00 0.00
October 0.277708E+10 0.124458E+10 0.151514E+10 0.00 0.151514E+10 0.00 0.00
November 0.119332E+10 0.273684E+10 0.111313E+10 0.00 0.111313E+10 0.00 0.00
December 0.854705E+09 0.377150E+10 0.103778E+10 0.00 0.103778E+10 0.00 0.00
               
Annual Sum or Average 0.320990E+11 0.231084E+11 0.194952E+11 0.339399E+09 0.191558E+11 0.00 0.00
Minimum of Months 0.787268E+09 0.327610E+09 0.103778E+10 0.00 0.103778E+10 0.00 0.00
Maximum of Months 0.484376E+10 0.439925E+10 0.225408E+10 0.155644E+09 0.216820E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.220709E+10 0.275498E+10 0.191536E+10 0.975310E+09 0.940054E+09 0.00 0.00
February 0.236048E+10 0.210951E+10 0.192642E+10 0.930024E+09 0.996395E+09 0.00 0.00
March 0.334774E+10 0.203383E+10 0.250890E+10 0.120997E+10 0.129893E+10 0.00 0.00
April 0.407467E+10 0.128999E+10 0.266441E+10 0.120504E+10 0.145937E+10 0.00 0.00
May 0.528348E+10 0.403450E+09 0.283783E+10 0.123054E+10 0.160729E+10 0.00 0.00
June 0.538859E+10 0.333404E+09 0.278520E+10 0.110453E+10 0.168067E+10 0.00 0.00
July 0.537211E+10 0.229001E+09 0.277484E+10 0.101544E+10 0.175940E+10 0.00 0.00
August 0.495894E+10 0.321015E+09 0.255693E+10 0.879093E+09 0.167784E+10 0.00 0.00
September 0.403709E+10 0.439605E+09 0.219191E+10 0.753571E+09 0.143834E+10 0.00 0.00
October 0.389826E+10 0.827550E+09 0.223826E+10 0.944538E+09 0.129372E+10 0.00 0.00
November 0.262518E+10 0.174564E+10 0.191773E+10 0.978309E+09 0.939421E+09 0.00 0.00
December 0.188971E+10 0.240581E+10 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
               
Annual Sum or Average 0.454433E+11 0.148938E+11 0.278780E+11 0.119331E+11 0.159449E+11 0.00 0.00
Minimum of Months 0.188971E+10 0.229001E+09 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
Maximum of Months 0.538859E+10 0.275498E+10 0.283783E+10 0.123054E+10 0.175940E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.904264E+10 0.431028E+10 0.645276E+10 0.460194E+10 0.185082E+10 0.00 0.00
February 0.757862E+10 0.333709E+10 0.528594E+10 0.342150E+10 0.186444E+10 0.00 0.00
March 0.551450E+10 0.324369E+10 0.373623E+10 0.168616E+10 0.205006E+10 0.00 0.00
April 0.440876E+10 0.205322E+10 0.267991E+10 0.627970E+09 0.205194E+10 0.00 0.00
May 0.442181E+10 0.598691E+09 0.211590E+10 89922872.05 0.202598E+10 0.00 0.00
June 0.438548E+10 0.491633E+09 0.202273E+10 18853748.06 0.200387E+10 0.00 0.00
July 0.470457E+10 0.320626E+09 0.218805E+10 40216078.06 0.214783E+10 0.00 0.00
August 0.553595E+10 0.498782E+09 0.257412E+10 0.308972E+09 0.226515E+10 0.00 0.00
September 0.588479E+10 0.710375E+09 0.298889E+10 0.787698E+09 0.220119E+10 0.00 0.00
October 0.862303E+10 0.138736E+10 0.479186E+10 0.249610E+10 0.229575E+10 0.00 0.00
November 0.906031E+10 0.281637E+10 0.590124E+10 0.406306E+10 0.183817E+10 0.00 0.00
December 0.924092E+10 0.382745E+10 0.630513E+10 0.452801E+10 0.177712E+10 0.00 0.00
               
Annual Sum or Average 0.784014E+11 0.235956E+11 0.470427E+11 0.226704E+11 0.243723E+11 0.00 0.00
Minimum of Months 0.438548E+10 0.320626E+09 0.202273E+10 18853748.06 0.177712E+10 0.00 0.00
Maximum of Months 0.924092E+10 0.431028E+10 0.645276E+10 0.460194E+10 0.229575E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.254380E+10 0.298098E+10 0.203729E+10 0.110165E+10 0.935636E+09 0.00 0.00
February 0.270308E+10 0.231334E+10 0.208344E+10 0.105451E+10 0.102893E+10 0.00 0.00
March 0.306895E+10 0.222931E+10 0.227345E+10 0.100640E+10 0.126705E+10 0.00 0.00
April 0.422356E+10 0.144055E+10 0.273260E+10 0.125705E+10 0.147555E+10 0.00 0.00
May 0.450260E+10 0.472226E+09 0.234823E+10 0.764941E+09 0.158329E+10 0.00 0.00
June 0.493945E+10 0.405355E+09 0.252447E+10 0.885198E+09 0.163927E+10 0.00 0.00
July 0.466783E+10 0.287709E+09 0.238118E+10 0.660502E+09 0.172068E+10 0.00 0.00
August 0.472389E+10 0.399109E+09 0.240767E+10 0.737022E+09 0.167065E+10 0.00 0.00
September 0.398343E+10 0.508277E+09 0.214554E+10 0.736024E+09 0.140952E+10 0.00 0.00
October 0.402671E+10 0.946052E+09 0.226981E+10 0.980761E+09 0.128905E+10 0.00 0.00
November 0.271709E+10 0.194004E+10 0.188274E+10 0.946191E+09 0.936552E+09 0.00 0.00
December 0.247380E+10 0.260036E+10 0.187140E+10 0.995187E+09 0.876217E+09 0.00 0.00
               
Annual Sum or Average 0.445742E+11 0.165233E+11 0.269578E+11 0.111254E+11 0.158324E+11 0.00 0.00
Minimum of Months 0.247380E+10 0.287709E+09 0.187140E+10 0.660502E+09 0.876217E+09 0.00 0.00
Maximum of Months 0.493945E+10 0.298098E+10 0.273260E+10 0.125705E+10 0.172068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.866551E+09 0.402982E+10 0.111635E+10 0.00 0.111635E+10 0.00 0.00
February 0.101943E+10 0.307984E+10 0.118957E+10 0.00 0.118957E+10 0.00 0.00
March 0.159070E+10 0.299619E+10 0.152787E+10 0.00 0.152787E+10 0.00 0.00
April 0.237902E+10 0.188412E+10 0.174505E+10 7162306.50 0.173789E+10 0.00 0.00
May 0.415405E+10 0.607128E+09 0.204249E+10 74709672.45 0.196778E+10 0.00 0.00
June 0.476720E+10 0.514104E+09 0.224782E+10 0.155644E+09 0.209218E+10 0.00 0.00
July 0.472508E+10 0.364535E+09 0.225408E+10 85876258.80 0.216820E+10 0.00 0.00
August 0.428808E+10 0.488797E+09 0.201857E+10 15876296.36 0.200269E+10 0.00 0.00
September 0.327629E+10 0.663694E+09 0.168734E+10 129958.71 0.168721E+10 0.00 0.00
October 0.274595E+10 0.122420E+10 0.151514E+10 0.00 0.151514E+10 0.00 0.00
November 0.123652E+10 0.254819E+10 0.111313E+10 0.00 0.111313E+10 0.00 0.00
December 0.913261E+09 0.346790E+10 0.103778E+10 0.00 0.103778E+10 0.00 0.00
               
Annual Sum or Average 0.319621E+11 0.218685E+11 0.194952E+11 0.339399E+09 0.191558E+11 0.00 0.00
Minimum of Months 0.866551E+09 0.364535E+09 0.103778E+10 0.00 0.103778E+10 0.00 0.00
Maximum of Months 0.476720E+10 0.402982E+10 0.225408E+10 0.155644E+09 0.216820E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.229053E+10 0.254201E+10 0.191536E+10 0.975310E+09 0.940054E+09 0.00 0.00
February 0.241332E+10 0.196037E+10 0.192642E+10 0.930024E+09 0.996395E+09 0.00 0.00
March 0.336841E+10 0.193399E+10 0.250890E+10 0.120997E+10 0.129893E+10 0.00 0.00
April 0.405888E+10 0.127084E+10 0.266441E+10 0.120504E+10 0.145937E+10 0.00 0.00
May 0.522983E+10 0.425281E+09 0.283783E+10 0.123054E+10 0.160729E+10 0.00 0.00
June 0.533314E+10 0.358044E+09 0.278520E+10 0.110453E+10 0.168067E+10 0.00 0.00
July 0.530922E+10 0.253832E+09 0.277484E+10 0.101544E+10 0.175940E+10 0.00 0.00
August 0.490541E+10 0.340691E+09 0.255693E+10 0.879093E+09 0.167784E+10 0.00 0.00
September 0.399069E+10 0.458994E+09 0.219191E+10 0.753571E+09 0.143834E+10 0.00 0.00
October 0.387088E+10 0.819931E+09 0.223826E+10 0.944538E+09 0.129372E+10 0.00 0.00
November 0.265317E+10 0.165671E+10 0.191773E+10 0.978309E+09 0.939421E+09 0.00 0.00
December 0.194049E+10 0.223879E+10 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
               
Annual Sum or Average 0.453640E+11 0.142595E+11 0.278780E+11 0.119331E+11 0.159449E+11 0.00 0.00
Minimum of Months 0.194049E+10 0.253832E+09 0.156024E+10 0.706755E+09 0.853486E+09 0.00 0.00
Maximum of Months 0.533314E+10 0.254201E+10 0.283783E+10 0.123054E+10 0.175940E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.912220E+10 0.403156E+10 0.645276E+10 0.460194E+10 0.185082E+10 0.00 0.00
February 0.763683E+10 0.313111E+10 0.528594E+10 0.342150E+10 0.186444E+10 0.00 0.00
March 0.553727E+10 0.307770E+10 0.373623E+10 0.168616E+10 0.205006E+10 0.00 0.00
April 0.438539E+10 0.201093E+10 0.267991E+10 0.627970E+09 0.205194E+10 0.00 0.00
May 0.435173E+10 0.632373E+09 0.211590E+10 89922872.05 0.202598E+10 0.00 0.00
June 0.431211E+10 0.528963E+09 0.202273E+10 18853748.06 0.200387E+10 0.00 0.00
July 0.461174E+10 0.356953E+09 0.218805E+10 40216078.06 0.214783E+10 0.00 0.00
August 0.546063E+10 0.530579E+09 0.257412E+10 0.308972E+09 0.226515E+10 0.00 0.00
September 0.581768E+10 0.740574E+09 0.298889E+10 0.787698E+09 0.220119E+10 0.00 0.00
October 0.857325E+10 0.138310E+10 0.479186E+10 0.249610E+10 0.229575E+10 0.00 0.00
November 0.907352E+10 0.270728E+10 0.590124E+10 0.406306E+10 0.183817E+10 0.00 0.00
December 0.928915E+10 0.360078E+10 0.630513E+10 0.452801E+10 0.177712E+10 0.00 0.00
               
Annual Sum or Average 0.781715E+11 0.227319E+11 0.470427E+11 0.226704E+11 0.243723E+11 0.00 0.00
Minimum of Months 0.431211E+10 0.356953E+09 0.202273E+10 18853748.06 0.177712E+10 0.00 0.00
Maximum of Months 0.928915E+10 0.403156E+10 0.645276E+10 0.460194E+10 0.229575E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.258644E+10 0.277807E+10 0.203729E+10 0.110165E+10 0.935636E+09 0.00 0.00
February 0.272846E+10 0.216638E+10 0.208344E+10 0.105451E+10 0.102893E+10 0.00 0.00
March 0.308158E+10 0.211511E+10 0.227345E+10 0.100640E+10 0.126705E+10 0.00 0.00
April 0.420340E+10 0.141148E+10 0.273260E+10 0.125705E+10 0.147555E+10 0.00 0.00
May 0.445807E+10 0.489515E+09 0.234823E+10 0.764941E+09 0.158329E+10 0.00 0.00
June 0.489041E+10 0.423720E+09 0.252447E+10 0.885198E+09 0.163927E+10 0.00 0.00
July 0.461230E+10 0.304613E+09 0.238118E+10 0.660502E+09 0.172068E+10 0.00 0.00
August 0.467633E+10 0.415078E+09 0.240767E+10 0.737022E+09 0.167065E+10 0.00 0.00
September 0.394396E+10 0.522755E+09 0.214554E+10 0.736024E+09 0.140952E+10 0.00 0.00
October 0.400137E+10 0.935806E+09 0.226981E+10 0.980761E+09 0.128905E+10 0.00 0.00
November 0.273241E+10 0.183919E+10 0.188274E+10 0.946191E+09 0.936552E+09 0.00 0.00
December 0.250166E+10 0.242937E+10 0.187140E+10 0.995187E+09 0.876217E+09 0.00 0.00
               
Annual Sum or Average 0.444164E+11 0.158311E+11 0.269578E+11 0.111254E+11 0.158324E+11 0.00 0.00
Minimum of Months 0.250166E+10 0.304613E+09 0.187140E+10 0.660502E+09 0.876217E+09 0.00 0.00
Maximum of Months 0.489041E+10 0.277807E+10 0.273260E+10 0.125705E+10 0.172068E+10 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: WindowEnergyZoneSummaryMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J]
January 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 0.00 0.00 0.00 0.00 0.00
               
Annual Sum or Average 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AverageOutdoorConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE [C] SITE OUTDOOR AIR WETBULB TEMPERATURE [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] SITE WIND SPEED [m/s] SITE SKY TEMPERATURE [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] SITE RAIN STATUS []
January 13.57 11.02 8.64 3.24 3.13 48.31 209.17 0.01
February 15.49 12.82 10.40 2.82 4.36 58.07 218.23 0.02
March 17.07 13.58 10.72 3.68 7.24 76.61 186.08 0.03
April 21.23 17.54 15.23 2.65 11.47 90.28 216.86 0.02
May 26.90 22.82 21.10 3.11 19.64 106.10 173.47 0.04
June 27.61 23.37 21.62 2.44 19.77 115.40 187.69 0.03
July 27.94 24.58 23.34 2.53 20.70 123.49 154.05 0.05
August 27.43 23.90 22.52 3.20 20.40 118.51 145.78 0.03
September 26.23 23.37 22.24 3.39 19.02 101.73 135.58 0.05
October 24.23 20.47 18.40 4.11 16.60 78.24 178.15 0.01
November 18.91 15.31 12.62 2.63 7.99 49.56 205.43 0.01
December 15.68 12.88 10.53 3.17 6.01 45.08 191.18 0.02
                 
Annual Sum or Average 21.89 18.50 16.48 3.09 13.08 84.44 183.16 0.03
Minimum of Months 13.57 11.02 8.64 2.44 3.13 45.08 135.58 0.01
Maximum of Months 27.94 24.58 23.34 4.11 20.70 123.49 218.23 0.05



Table of Contents

Report: OutdoorConditionsMaximumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 27.00 02-JAN-14:00 18.67 14.00 1.50 17.75 146.50 0.00
February 28.30 02-FEB-12:00 20.78 17.20 6.60 17.93 127.50 748.50
March 30.00 26-MAR-13:00 19.88 14.40 3.00 19.52 288.50 548.00
April 33.30 28-APR-14:00 23.06 18.80 4.10 23.15 150.50 762.50
May 33.90 07-MAY-13:00 23.76 19.40 4.10 23.15 287.50 507.50
June 35.00 14-JUN-13:00 23.95 19.40 2.10 24.16 194.50 712.50
July 36.10 21-JUL-15:00 25.96 22.20 1.50 26.65 216.00 245.00
August 36.30 30-AUG-15:00 23.74 18.50 2.40 25.33 116.00 698.50
September 36.40 09-SEP-16:00 26.65 23.40 4.40 26.48 114.00 401.50
October 34.00 05-OCT-14:00 24.05 20.00 2.60 29.55 169.50 606.00
November 30.00 01-NOV-13:00 25.01 23.30 2.00 26.48 216.50 118.00
December 30.00 13-DEC-14:00 21.84 18.00 3.10 20.92 101.50 682.50
                 
Annual Sum or Average                
Minimum of Months 27.00   18.67 14.00 1.50 17.75 101.50 0.00
Maximum of Months 36.40   26.65 23.40 6.60 29.55 288.50 762.50



Table of Contents

Report: OutdoorConditionsMinimumDryBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 0.00 05-JAN-05:00 -0.0 -0.0 2.10 -16.0 0.00 0.00
February -3.4 05-FEB-07:10 -5.4 -9.4 4.68 -21.3 0.00 0.00
March 1.10 09-MAR-05:00 -2.1 -7.3 3.60 -14.4 0.00 0.00
April 8.30 11-APR-05:00 6.95 5.50 0.00 -6.9 0.00 0.00
May 21.10 07-MAY-00:00 19.58 18.90 0.00 11.46 0.00 0.00
June 20.60 07-JUN-01:00 18.00 16.70 3.60 10.50 0.00 0.00
July 22.20 11-JUL-19:00 21.37 21.10 2.10 20.22 0.00 0.00
August 20.20 25-AUG-23:00 20.20 20.20 5.30 11.84 0.00 0.00
September 19.20 07-SEP-17:00 19.20 19.20 2.50 16.85 35.00 7.00
October 10.00 28-OCT-04:00 5.56 0.00 3.60 -0.1 0.00 0.00
November 7.20 12-NOV-07:49 4.12 0.18 4.60 -9.0 36.00 517.00
December 0.00 21-DEC-04:00 -0.9 -2.0 2.10 -16.2 0.00 0.00
                 
Annual Sum or Average                
Minimum of Months -3.4   -5.4 -9.4 0.00 -21.3 0.00 0.00
Maximum of Months 22.20   21.37 21.10 5.30 20.22 36.00 517.00



Table of Contents

Report: OutdoorConditionsMaximumWetBulbMonthly

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 22.11 31-JAN-12:00 25.00 21.00 5.70 20.92 336.50 96.00
February 21.49 24-FEB-12:00 27.70 18.80 4.10 17.75 165.00 746.50
March 22.77 30-MAR-12:00 29.40 20.00 2.50 27.14 340.00 0.00
April 25.55 28-APR-15:00 32.20 23.30 3.60 22.47 156.00 575.50
May 25.84 27-MAY-13:00 31.70 23.90 3.10 22.13 168.50 735.50
June 26.52 29-JUN-16:00 29.40 25.60 1.50 26.32 164.00 36.00
July 27.17 22-JUL-10:00 32.20 25.60 2.10 21.96 191.00 719.50
August 27.24 07-AUG-12:00 31.00 26.00 3.10 27.95 473.00 200.00
September 27.79 10-SEP-12:00 35.00 25.50 2.90 24.66 239.50 662.00
October 28.18 07-OCT-07:00 29.00 28.00 2.60 21.09 95.00 500.50
November 25.01 01-NOV-13:00 30.00 23.30 2.00 26.48 216.50 118.00
December 24.12 12-DEC-13:00 27.00 23.00 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 21.49   25.00 18.80 1.50 17.75 95.00 0.00
Maximum of Months 28.18   35.00 28.00 5.70 27.95 473.00 746.50



Table of Contents

Report: OutdoorConditionsMaximumDewPointMonthly

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] SITE WIND SPEED {AT MAX/MIN} [m/s] SITE SKY TEMPERATURE {AT MAX/MIN} [C] SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2]
January 21.00 31-JAN-12:00 25.00 22.11 5.70 20.92 336.50 96.00
February 20.20 02-FEB-22:00 21.50 20.56 4.80 14.65 0.00 0.00
March 21.10 07-MAR-08:00 23.30 21.69 2.00 13.91 126.00 566.50
April 23.30 28-APR-15:00 32.20 25.55 3.60 22.47 156.00 575.50
May 24.40 26-MAY-08:20 27.07 25.09 3.10 23.71 252.67 47.33
June 25.60 29-JUN-14:00 27.20 26.00 5.10 24.16 335.00 238.00
July 25.60 02-JUL-05:00 26.10 25.71 2.60 19.52 30.50 8.50
August 26.60 09-AUG-18:00 26.60 26.60 1.90 19.52 26.00 23.00
September 25.50 10-SEP-12:00 35.00 27.79 2.90 24.66 239.50 662.00
October 28.00 07-OCT-07:00 29.00 28.18 2.60 21.09 95.00 500.50
November 23.80 01-NOV-10:00 26.10 24.39 2.00 22.64 228.50 113.00
December 23.00 12-DEC-13:00 27.00 24.12 2.10 19.17 160.50 599.50
                 
Annual Sum or Average                
Minimum of Months 20.20   21.50 20.56 1.90 13.91 0.00 0.00
Maximum of Months 28.00   35.00 28.18 5.70 24.66 336.50 662.00



Table of Contents

Report: OutdoorGroundConditionsMonthly

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE GROUND TEMPERATURE [C] SITE SURFACE GROUND TEMPERATURE [C] SITE DEEP GROUND TEMPERATURE [C] SITE MAINS WATER TEMPERATURE [C] SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] SITE SNOW ON GROUND STATUS []
January 18.00 13.00 16.00 20.46 29.60 0.00
February 18.00 13.00 16.00 20.78 36.65 0.00
March 18.00 13.00 16.00 22.23 38.94 0.00
April 18.00 13.00 16.00 24.49 49.11 0.00
May 18.00 13.00 16.00 26.95 46.95 0.00
June 18.00 13.00 16.00 28.93 51.71 0.00
July 18.00 13.00 16.00 29.89 48.43 0.00
August 18.00 13.00 16.00 29.58 45.50 0.00
September 18.00 13.00 16.00 28.08 39.22 0.00
October 18.00 13.00 16.00 25.80 37.51 0.00
November 18.00 13.00 16.00 23.35 31.26 0.00
December 18.00 13.00 16.00 21.40 27.18 0.00
             
Annual Sum or Average 18.00 13.00 16.00 25.18 40.17 0.00
Minimum of Months 18.00 13.00 16.00 20.46 27.18 0.00
Maximum of Months 18.00 13.00 16.00 29.89 51.71 0.00



Table of Contents

Report: WaterHeaterReportMonthly

For: SWHSYS1 WATER HEATER

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] WATER HEATER BURNER HEATING ENERGY [] WATER HEATER GAS CONSUMPTION [] WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] WATER HEATER LOSS DEMAND ENERGY [] WATER HEATER HEAT LOSS ENERGY [J] WATER HEATER TANK TEMPERATURE [C] WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] WATER HEATER SOURCE ENERGY []
January 0.316941E+11 -0.306723E+11 0.00 0.00 744.00 0.00 -0.102181E+10 58.98 0.00 0.00
February 0.285705E+11 -0.276466E+11 0.00 0.00 672.00 0.00 -923821343.2 58.97 0.00 0.00
March 0.322990E+11 -0.312722E+11 0.00 0.00 744.00 0.00 -0.102675E+10 58.98 0.00 0.00
April 0.276058E+11 -0.266158E+11 0.00 0.00 720.00 0.00 -989956834.6 58.96 0.00 0.00
May 0.274494E+11 -0.264264E+11 0.00 0.00 744.00 0.00 -0.102308E+10 58.97 0.00 0.00
June 0.255533E+11 -0.245617E+11 0.00 0.00 720.00 0.00 -991542835.9 58.97 0.00 0.00
July 0.236217E+11 -0.226027E+11 0.00 0.00 744.00 0.00 -0.101895E+10 58.97 0.00 0.00
August 0.260438E+11 -0.250211E+11 0.00 0.00 744.00 0.00 -0.102267E+10 58.97 0.00 0.00
September 0.248604E+11 -0.238729E+11 0.00 0.00 720.00 0.00 -987477863.9 58.97 0.00 0.00
October 0.274556E+11 -0.264370E+11 0.00 0.00 744.00 0.00 -0.101858E+10 58.97 0.00 0.00
November 0.288190E+11 -0.278328E+11 0.00 0.00 720.00 0.00 -986211668.9 58.98 0.00 0.00
December 0.302298E+11 -0.292107E+11 0.00 0.00 744.00 0.00 -0.101904E+10 58.97 0.00 0.00
                     
Annual Sum or Average 0.334202E+12 -0.322172E+12 0.00 0.00 8760.00 0.00 -0.120299E+11 58.97 0.00 0.00
Minimum of Months 0.236217E+11 -0.312722E+11 0.00 0.00 672.00 0.00 -0.102675E+10 58.96 0.00 0.00
Maximum of Months 0.322990E+11 -0.226027E+11 0.00 0.00 744.00 0.00 -923821343.2 58.98 0.00 0.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.64 0.61 01-JAN-07:00 6725.53 34.61 279.17 288.50 1112.85 25.01 167.17 270.67
February 295.50 0.63 0.61 01-FEB-11:39 2777.54 26.53 165.17 272.50 953.61 21.96 106.50 257.17
March 296.00 0.64 0.61 02-MAR-12:39 1216.55 16.86 0.00 306.50 703.80 19.77 50.00 258.17
April 347.33 0.65 0.61 01-APR-07:30 965.20 16.00 0.00 309.50 553.46 18.85 19.83 258.83
May 353.67 0.64 0.61 01-MAY-06:00 864.11 16.13 0.00 332.17 484.50 19.05 5.50 266.67
June 394.00 0.64 0.61 01-JUN-06:40 819.52 15.75 0.00 332.50 462.56 18.67 1.67 266.83
July 390.00 0.64 0.61 01-JUL-06:40 910.33 16.19 0.00 345.00 496.97 19.09 10.17 279.50
August 380.83 0.64 0.61 01-AUG-06:00 1062.71 16.59 0.00 335.00 567.17 19.44 36.50 281.67
September 342.17 0.64 0.61 01-SEP-06:00 1257.42 16.96 3.67 305.83 658.05 19.70 93.33 261.17
October 330.00 0.63 0.61 01-OCT-06:00 2251.76 21.48 80.50 307.17 887.59 20.92 144.50 271.17
November 308.00 0.63 0.61 01-NOV-07:49 6845.52 35.40 293.83 282.17 1061.02 22.98 131.33 262.00
December 282.83 0.64 0.61 01-DEC-07:49 6828.55 35.14 260.50 275.83 1454.25 26.98 168.17 258.83
                         
Annual Sum or Average 4027.67 0.64     2528.61 21.68 1082.83 3692.67 755.76 20.82 934.67 3192.67
Minimum of Months 282.83 0.63 0.61   819.52 15.75 0.00 272.50 462.56 18.67 1.67 257.17
Maximum of Months 394.00 0.65 0.61   6845.52 35.40 293.83 345.00 1454.25 26.98 168.17 281.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.66 0.61 01-JAN-07:49 1570.43 17.11 81.17 238.00 804.55 16.51 53.33 174.67
February 295.50 0.65 0.61 01-FEB-11:39 1735.06 16.85 71.67 237.17 943.11 17.88 62.00 191.67
March 296.00 0.64 0.61 02-MAR-12:39 1821.33 15.09 48.50 294.50 927.00 13.45 0.00 230.50
April 347.33 0.65 0.61 01-APR-07:10 1850.45 11.54 0.00 305.67 993.99 12.90 0.00 259.17
May 353.67 0.64 0.61 01-MAY-06:40 2070.86 12.21 0.00 339.67 817.13 13.38 0.00 278.17
June 394.00 0.64 0.61 01-JUN-06:10 1935.40 12.24 0.00 340.33 772.01 13.31 0.00 282.50
July 390.00 0.64 0.61 01-JUL-06:10 1808.71 12.61 0.00 347.50 765.15 13.57 0.00 285.00
August 380.83 0.64 0.61 01-AUG-06:49 1669.00 12.58 0.00 331.17 873.34 13.63 0.00 280.33
September 342.17 0.65 0.61 01-SEP-06:49 1599.61 12.78 5.67 296.00 815.11 13.84 3.67 246.33
October 330.00 0.64 0.61 01-OCT-06:49 1662.53 17.16 75.33 283.50 828.56 16.73 46.50 238.17
November 308.00 0.65 0.61 01-NOV-07:49 1267.09 15.62 56.83 236.67 703.99 17.00 53.33 189.67
December 282.83 0.66 0.61 01-DEC-07:49 1486.68 17.38 75.50 225.83 804.50 17.87 59.67 166.67
                         
Annual Sum or Average 4027.67 0.64     1718.08 14.23 414.67 3476.00 835.83 14.85 278.50 2822.83
Minimum of Months 282.83 0.64 0.61   1267.09 11.54 0.00 225.83 703.99 12.90 0.00 166.67
Maximum of Months 394.00 0.66 0.61   2070.86 17.38 81.17 347.50 993.99 17.88 62.00 285.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.67 0.61 01-JAN-08:50 401.73 0.00 0.00 194.67 265.47 0.00 0.00 54.00
February 295.50 0.66 0.61 01-FEB-11:39 463.81 0.00 0.00 215.83 307.40 0.00 0.00 112.33
March 296.00 0.65 0.61 02-MAR-12:39 548.39 0.00 0.00 282.00 348.93 0.00 0.00 156.67
April 347.33 0.64 0.61 01-APR-07:30 658.81 0.00 0.00 313.83 404.02 0.00 0.00 241.00
May 353.67 0.63 0.61 01-MAY-06:49 816.33 0.00 0.00 353.83 473.31 0.00 0.00 294.50
June 394.00 0.63 0.61 01-JUN-06:19 955.82 0.00 0.00 362.67 501.73 0.00 0.00 314.50
July 390.00 0.63 0.61 01-JUL-06:19 937.83 0.00 0.00 364.00 507.07 0.00 0.00 313.67
August 380.83 0.64 0.61 01-AUG-06:49 818.64 0.00 0.00 342.50 459.36 0.00 0.00 286.83
September 342.17 0.64 0.61 01-SEP-06:00 682.19 0.00 0.00 301.17 392.86 0.00 0.00 215.33
October 330.00 0.64 0.61 01-OCT-07:19 578.23 0.00 0.00 278.83 357.92 0.00 0.00 188.83
November 308.00 0.67 0.61 01-NOV-08:30 412.00 0.00 0.00 199.17 274.04 0.00 0.00 60.83
December 282.83 0.67 0.61 01-DEC-08:30 400.84 0.00 0.00 190.83 266.93 0.00 0.00 41.33
                         
Annual Sum or Average 4027.67 0.65     660.18 0.00 0.00 3399.33 388.87 0.00 0.00 2279.83
Minimum of Months 282.83 0.63 0.61   400.84 0.00 0.00 190.83 265.47 0.00 0.00 41.33
Maximum of Months 394.00 0.67 0.61   955.82 0.00 0.00 364.00 507.07 0.00 0.00 314.50



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_BOT_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.66 0.61 01-JAN-08:50 1770.46 17.54 83.67 245.33 1037.37 19.07 80.17 183.33
February 295.50 0.65 0.61 01-FEB-11:39 1614.34 17.58 77.83 245.33 819.79 16.87 50.00 200.00
March 296.00 0.64 0.61 02-MAR-12:39 1730.22 14.65 45.33 289.33 868.44 13.30 0.00 222.67
April 347.33 0.65 0.61 01-APR-07:49 1946.70 11.63 0.00 305.83 1034.14 13.01 0.00 263.83
May 353.67 0.64 0.61 01-MAY-07:30 1596.40 12.25 0.00 334.50 694.13 13.43 0.00 276.17
June 394.00 0.64 0.61 01-JUN-06:00 1749.52 12.18 0.00 340.00 705.11 13.25 0.00 283.33
July 390.00 0.64 0.61 01-JUL-06:49 1604.45 12.57 0.00 347.83 681.70 13.54 0.00 286.17
August 380.83 0.64 0.61 01-AUG-07:10 1623.29 12.66 0.00 332.00 727.02 13.72 0.00 279.67
September 342.17 0.64 0.61 01-SEP-07:30 1512.31 12.71 5.50 296.83 752.68 13.65 0.00 246.17
October 330.00 0.63 0.61 01-OCT-07:40 1919.38 17.75 83.17 287.50 788.94 15.12 9.67 241.17
November 308.00 0.65 0.61 01-NOV-08:00 1563.10 17.26 79.50 241.33 849.15 17.83 63.17 186.50
December 282.83 0.65 0.61 01-DEC-08:39 1678.16 18.69 84.83 243.33 870.32 18.13 58.83 173.33
                         
Annual Sum or Average 4027.67 0.64     1691.86 14.56 459.83 3509.17 811.62 14.91 261.83 2842.33
Minimum of Months 282.83 0.63 0.61   1512.31 11.63 0.00 241.33 681.70 13.01 0.00 173.33
Maximum of Months 394.00 0.66 0.61   1946.70 18.69 84.83 347.83 1037.37 19.07 80.17 286.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.64 0.61 01-JAN-07:00 6715.41 33.93 278.83 287.50 1153.68 20.87 92.17 271.67
February 295.50 0.63 0.61 01-FEB-11:39 2765.80 23.22 165.17 272.17 991.05 17.78 36.33 259.17
March 296.00 0.64 0.61 02-MAR-12:39 1203.26 11.02 0.00 305.33 730.22 15.94 0.00 260.33
April 347.33 0.65 0.61 01-APR-07:30 950.87 10.58 0.00 308.00 571.62 15.28 0.00 262.67
May 353.67 0.64 0.61 01-MAY-06:00 847.82 10.58 0.00 330.33 498.52 15.36 0.00 270.50
June 394.00 0.64 0.61 01-JUN-06:40 804.00 10.25 0.00 331.17 475.89 14.98 0.00 272.17
July 390.00 0.64 0.61 01-JUL-06:40 891.79 10.51 0.00 343.17 510.94 15.22 0.00 283.83
August 380.83 0.64 0.61 01-AUG-06:00 1040.46 10.90 0.00 332.83 583.31 15.56 0.00 285.67
September 342.17 0.64 0.61 01-SEP-06:00 1229.60 11.18 3.67 304.67 677.24 15.65 0.00 263.00
October 330.00 0.63 0.61 01-OCT-06:00 2220.90 16.37 77.17 306.00 922.87 16.97 10.33 273.50
November 308.00 0.64 0.61 01-NOV-07:49 6795.94 33.52 279.00 278.00 1130.95 20.67 90.83 269.33
December 282.83 0.64 0.61 01-DEC-07:00 6770.31 33.17 248.83 272.33 1496.40 23.18 110.83 259.50
                         
Annual Sum or Average 4027.67 0.64     2505.15 17.18 1052.67 3671.50 783.37 17.07 340.50 3231.33
Minimum of Months 282.83 0.63 0.61   804.00 10.25 0.00 272.17 475.89 14.98 0.00 259.17
Maximum of Months 394.00 0.65 0.61   6795.94 33.93 279.00 343.17 1496.40 23.18 110.83 285.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.66 0.61 01-JAN-07:49 1569.52 15.14 81.33 237.67 823.65 14.63 53.33 180.33
February 295.50 0.65 0.61 01-FEB-11:39 1735.37 14.66 71.67 236.67 964.76 16.13 62.17 197.17
March 296.00 0.64 0.61 02-MAR-12:39 1610.91 12.38 48.50 294.17 954.27 10.91 0.00 237.00
April 347.33 0.65 0.61 01-APR-07:10 1841.50 8.21 0.00 304.17 1017.92 10.57 0.00 263.33
May 353.67 0.64 0.61 01-MAY-06:40 2053.78 8.71 0.00 339.50 842.86 11.07 0.00 284.33
June 394.00 0.64 0.61 01-JUN-06:10 1845.87 8.87 0.00 338.83 795.42 11.13 0.00 287.83
July 390.00 0.64 0.61 01-JUL-06:19 1793.54 9.21 0.00 346.17 788.13 11.36 0.00 288.83
August 380.83 0.64 0.61 01-AUG-06:49 1650.87 9.24 0.00 330.33 895.03 11.35 0.00 284.83
September 342.17 0.65 0.61 01-SEP-06:49 1594.91 9.53 5.67 295.33 836.03 11.47 3.67 251.83
October 330.00 0.64 0.61 01-OCT-06:49 1663.17 14.85 75.33 282.50 850.23 14.68 47.17 242.83
November 308.00 0.65 0.61 01-NOV-07:49 1265.60 13.15 56.83 236.17 723.64 15.06 53.67 195.83
December 282.83 0.66 0.61 01-DEC-07:49 1484.76 15.39 75.50 224.83 822.29 16.08 59.67 172.33
                         
Annual Sum or Average 4027.67 0.65     1687.76 11.36 414.83 3466.33 858.08 12.70 279.67 2886.50
Minimum of Months 282.83 0.64 0.61   1265.60 8.21 0.00 224.83 723.64 10.57 0.00 172.33
Maximum of Months 394.00 0.66 0.61   2053.78 15.39 81.33 346.17 1017.92 16.13 62.17 288.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.68 0.61 01-JAN-08:50 394.77 0.00 0.00 188.67 273.00 0.00 0.00 66.67
February 295.50 0.66 0.61 01-FEB-11:39 456.51 0.00 0.00 212.50 316.41 0.00 0.00 123.50
March 296.00 0.65 0.61 02-MAR-12:39 540.47 0.00 0.00 279.00 359.63 0.00 0.00 171.67
April 347.33 0.65 0.61 01-APR-07:30 649.19 0.00 0.00 312.33 416.45 0.00 0.00 248.83
May 353.67 0.63 0.61 01-MAY-06:49 802.24 0.00 0.00 353.00 482.99 0.00 0.00 294.17
June 394.00 0.63 0.61 01-JUN-06:19 940.17 0.00 0.00 361.83 524.98 0.00 0.00 324.83
July 390.00 0.63 0.61 01-JUL-06:19 920.50 0.00 0.00 363.50 521.26 0.00 0.00 318.83
August 380.83 0.64 0.61 01-AUG-06:00 803.20 0.00 0.00 340.67 472.29 0.00 0.00 290.33
September 342.17 0.64 0.61 01-SEP-06:00 669.84 0.00 0.00 299.50 404.10 0.00 0.00 222.00
October 330.00 0.64 0.61 01-OCT-07:19 568.07 0.00 0.00 277.00 368.10 0.00 0.00 196.17
November 308.00 0.67 0.61 01-NOV-08:39 405.04 0.00 0.00 196.00 281.85 0.00 0.00 76.67
December 282.83 0.67 0.61 01-DEC-08:30 393.46 0.00 0.00 185.00 274.26 0.00 0.00 52.83
                         
Annual Sum or Average 4027.67 0.65     648.87 0.00 0.00 3369.00 400.59 0.00 0.00 2386.50
Minimum of Months 282.83 0.63 0.61   393.46 0.00 0.00 185.00 273.00 0.00 0.00 52.83
Maximum of Months 394.00 0.68 0.61   940.17 0.00 0.00 363.50 524.98 0.00 0.00 324.83



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_MID_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.66 0.61 01-JAN-08:50 1762.94 15.44 82.67 244.67 1057.80 17.45 80.50 189.83
February 295.50 0.65 0.61 01-FEB-11:39 1419.40 12.88 51.33 244.83 842.88 14.93 50.00 206.00
March 296.00 0.64 0.61 02-MAR-12:39 1739.41 11.96 45.33 288.50 892.13 10.82 0.00 230.50
April 347.33 0.65 0.61 01-APR-07:49 1935.96 8.28 0.00 305.50 1058.38 10.66 0.00 267.33
May 353.67 0.64 0.61 01-MAY-07:30 1580.02 8.87 0.00 333.33 715.56 11.18 0.00 281.33
June 394.00 0.64 0.61 01-JUN-06:00 1680.71 8.88 0.00 338.67 726.96 11.09 0.00 289.17
July 390.00 0.64 0.61 01-JUL-06:49 1553.76 9.25 0.00 345.83 702.30 11.37 0.00 290.67
August 380.83 0.64 0.61 01-AUG-07:10 1606.16 9.34 0.00 330.83 748.15 11.45 0.00 283.17
September 342.17 0.64 0.61 01-SEP-07:30 1507.40 9.46 5.50 295.83 773.12 11.24 0.00 249.33
October 330.00 0.63 0.61 01-OCT-07:40 1919.71 15.47 83.17 286.83 803.01 12.37 7.00 244.00
November 308.00 0.65 0.61 01-NOV-08:00 1562.19 15.14 79.50 240.83 820.92 14.67 50.67 189.17
December 282.83 0.65 0.61 01-DEC-08:39 1678.88 16.75 84.83 242.17 880.38 15.90 55.83 178.67
                         
Annual Sum or Average 4027.67 0.64     1661.62 11.55 432.33 3497.83 828.16 12.60 244.00 2899.17
Minimum of Months 282.83 0.63 0.61   1419.40 8.28 0.00 240.83 702.30 10.66 0.00 178.67
Maximum of Months 394.00 0.66 0.61   1935.96 16.75 84.83 345.83 1058.38 17.45 80.50 290.67



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_1_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.64 0.61 01-JAN-07:00 6715.08 33.91 278.83 287.50 1154.60 20.86 92.17 271.67
February 295.50 0.63 0.61 01-FEB-11:39 2766.12 23.19 165.17 272.17 991.94 17.76 36.33 259.17
March 296.00 0.64 0.61 02-MAR-12:39 1203.75 10.98 0.00 305.33 730.97 15.92 0.00 260.33
April 347.33 0.65 0.61 01-APR-07:30 951.24 10.54 0.00 308.00 572.21 15.26 0.00 262.67
May 353.67 0.64 0.61 01-MAY-06:00 848.16 10.54 0.00 330.33 499.06 15.34 0.00 270.67
June 394.00 0.64 0.61 01-JUN-06:40 804.31 10.21 0.00 331.17 476.40 14.97 0.00 272.50
July 390.00 0.64 0.61 01-JUL-06:40 892.24 10.47 0.00 343.17 511.53 15.20 0.00 284.17
August 380.83 0.64 0.61 01-AUG-06:00 1041.08 10.86 0.00 332.83 584.04 15.54 0.00 286.00
September 342.17 0.64 0.61 01-SEP-06:00 1230.38 11.14 3.67 304.67 678.14 15.63 0.00 263.00
October 330.00 0.63 0.61 01-OCT-06:00 2221.55 16.34 77.17 305.83 923.94 16.95 10.33 273.50
November 308.00 0.64 0.61 01-NOV-07:49 6795.90 33.51 279.00 278.00 1131.88 20.66 90.83 269.33
December 282.83 0.64 0.61 01-DEC-07:00 6769.81 33.16 248.83 272.33 1497.38 23.17 110.83 259.50
                         
Annual Sum or Average 4027.67 0.64     2505.46 17.15 1052.67 3671.33 784.14 17.06 340.50 3232.50
Minimum of Months 282.83 0.63 0.61   804.31 10.21 0.00 272.17 476.40 14.97 0.00 259.17
Maximum of Months 394.00 0.65 0.61   6795.90 33.91 279.00 343.17 1497.38 23.17 110.83 286.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_2_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.66 0.61 01-JAN-07:49 1569.18 15.13 81.33 237.67 824.05 14.62 53.33 180.33
February 295.50 0.65 0.61 01-FEB-11:39 1735.03 14.65 71.67 236.67 965.24 16.12 62.17 197.17
March 296.00 0.64 0.61 02-MAR-12:39 1610.54 12.37 48.50 294.00 954.87 10.90 0.00 237.00
April 347.33 0.65 0.61 01-APR-07:10 1841.47 8.20 0.00 304.17 1018.53 10.56 0.00 263.67
May 353.67 0.64 0.61 01-MAY-06:40 2053.78 8.70 0.00 339.50 843.58 11.06 0.00 284.83
June 394.00 0.64 0.61 01-JUN-06:10 1845.97 8.86 0.00 338.83 796.17 11.12 0.00 287.83
July 390.00 0.64 0.61 01-JUL-06:19 1793.78 9.20 0.00 346.17 788.96 11.35 0.00 289.00
August 380.83 0.64 0.61 01-AUG-06:49 1651.16 9.23 0.00 330.33 889.70 11.34 0.00 284.50
September 342.17 0.65 0.61 01-SEP-06:49 1595.14 9.52 5.67 295.33 811.72 11.46 3.67 249.33
October 330.00 0.64 0.61 01-OCT-06:49 1662.88 14.84 75.33 282.67 850.90 14.68 47.17 242.83
November 308.00 0.65 0.61 01-NOV-07:49 1265.25 13.13 56.83 236.17 724.07 15.06 53.67 196.00
December 282.83 0.66 0.61 01-DEC-07:49 1484.44 15.38 75.50 224.50 822.68 16.07 59.67 172.50
                         
Annual Sum or Average 4027.67 0.65     1687.69 11.35 414.83 3466.00 856.00 12.70 279.67 2885.00
Minimum of Months 282.83 0.64 0.61   1265.25 8.20 0.00 224.50 724.07 10.56 0.00 172.50
Maximum of Months 394.00 0.66 0.61   2053.78 15.38 81.33 346.17 1018.53 16.12 62.17 289.00



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_3_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.68 0.61 01-JAN-08:50 394.60 0.00 0.00 188.83 273.17 0.00 0.00 66.83
February 295.50 0.66 0.61 01-FEB-11:39 456.32 0.00 0.00 212.50 316.60 0.00 0.00 123.67
March 296.00 0.65 0.61 02-MAR-12:39 540.36 0.00 0.00 279.00 359.89 0.00 0.00 172.00
April 347.33 0.65 0.61 01-APR-07:30 649.16 0.00 0.00 312.33 416.80 0.00 0.00 249.33
May 353.67 0.63 0.61 01-MAY-06:49 802.39 0.00 0.00 353.00 483.49 0.00 0.00 294.33
June 394.00 0.63 0.61 01-JUN-06:19 940.41 0.00 0.00 361.83 525.54 0.00 0.00 325.17
July 390.00 0.63 0.61 01-JUL-06:19 920.81 0.00 0.00 363.33 521.86 0.00 0.00 319.17
August 380.83 0.64 0.61 01-AUG-06:00 803.43 0.00 0.00 340.67 472.82 0.00 0.00 290.83
September 342.17 0.64 0.61 01-SEP-06:00 669.95 0.00 0.00 299.50 404.52 0.00 0.00 222.67
October 330.00 0.64 0.61 01-OCT-07:19 567.98 0.00 0.00 277.00 368.40 0.00 0.00 196.50
November 308.00 0.67 0.61 01-NOV-08:39 404.85 0.00 0.00 196.00 282.02 0.00 0.00 76.67
December 282.83 0.67 0.61 01-DEC-08:30 393.27 0.00 0.00 184.83 274.42 0.00 0.00 53.00
                         
Annual Sum or Average 4027.67 0.65     648.89 0.00 0.00 3368.83 400.95 0.00 0.00 2390.17
Minimum of Months 282.83 0.63 0.61   393.27 0.00 0.00 184.83 273.17 0.00 0.00 53.00
Maximum of Months 394.00 0.68 0.61   940.41 0.00 0.00 363.33 525.54 0.00 0.00 325.17



Table of Contents

Report: DaylightingReportMonthly

For: PERIMETER_TOP_ZN_4_DAYLCTRL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr]
January 307.33 0.66 0.61 01-JAN-08:50 1762.61 15.43 82.67 244.67 1058.19 17.44 80.50 189.83
February 295.50 0.65 0.61 01-FEB-11:39 1418.97 12.87 51.33 244.67 843.36 14.92 50.00 206.17
March 296.00 0.64 0.61 02-MAR-12:39 1739.17 11.94 45.33 288.00 892.68 10.81 0.00 230.50
April 347.33 0.65 0.61 01-APR-07:49 1935.91 8.27 0.00 305.50 1059.02 10.65 0.00 267.50
May 353.67 0.64 0.61 01-MAY-07:30 1580.16 8.85 0.00 333.33 881.93 11.18 0.00 281.50
June 394.00 0.64 0.61 01-JUN-06:00 1680.88 8.86 0.00 338.50 727.67 11.09 0.00 289.33
July 390.00 0.64 0.61 01-JUL-06:49 1554.11 9.24 0.00 345.83 710.05 11.36 0.00 290.67
August 380.83 0.64 0.61 01-AUG-07:10 1606.49 9.32 0.00 330.83 864.27 11.44 0.00 283.50
September 342.17 0.64 0.61 01-SEP-07:30 1507.59 9.45 5.50 295.50 773.87 11.23 0.00 249.67
October 330.00 0.63 0.61 01-OCT-07:40 1919.49 15.46 83.17 286.83 803.67 12.36 7.00 244.17
November 308.00 0.65 0.61 01-NOV-08:00 1561.84 15.13 79.50 240.83 821.33 14.67 50.67 189.33
December 282.83 0.65 0.61 01-DEC-08:39 1678.52 16.74 84.83 242.17 880.77 15.89 55.83 178.83
                         
Annual Sum or Average 4027.67 0.64     1661.58 11.54 432.33 3496.67 854.90 12.59 244.00 2901.00
Minimum of Months 282.83 0.63 0.61   1418.97 8.27 0.00 240.83 710.05 10.65 0.00 178.83
Maximum of Months 394.00 0.66 0.61   1935.91 16.74 84.83 345.83 1059.02 17.44 80.50 290.67



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 73616678.49 14292.01 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 34311161.85 13105.10 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 26985485.57 12386.10 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 45546390.94 15646.13 18-APR-15:20 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 240.64 0.25 27-OCT-18:00 0.00 0.00 0.00 0.00 0.00
November 3342.80 14.57 05-NOV-16:27 0.00 0.00 0.00 0.00 0.00
December 31006491.88 14684.33 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.211470E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 73616678.49 15646.13   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_BOTTOM VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 1247208.14 314.94 05-JAN-06:40 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 1247208.14     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1247208.14 314.94   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 2893907.14 810.79 05-JAN-06:07 0.00 0.00 0.00 0.00 0.00
February 58743.04 97.91 06-FEB-07:00 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 6906973.45 1828.68 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 9859623.62     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 6906973.45 1828.68   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 376650.20 484.24 21-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 424832.96 346.69 06-FEB-06:40 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 1229523.18 538.83 20-DEC-07:30 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 2031006.34     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 1229523.18 538.83   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.160286E+10 165263.11 04-JAN-08:10 0.00 0.00 0.00 0.00 0.00
February 0.781001E+09 150964.81 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 0.631684E+09 150058.89 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 0.118713E+09 52316.77 18-APR-14:55 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 1960.52 3.27 17-OCT-07:00 0.00 0.00 0.00 0.00 0.00
November 26889846.40 18590.95 27-NOV-14:20 0.00 0.00 0.00 0.00 0.00
December 0.108309E+10 174130.95 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.424424E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.160286E+10 174130.95   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_MID VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.365185E+10 138362.26 04-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.183058E+10 136868.50 17-FEB-06:03 0.00 0.00 0.00 0.00 0.00
March 0.124294E+10 138329.67 09-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 18542076.21 9071.59 16-NOV-06:08 0.00 0.00 0.00 0.00 0.00
December 0.221914E+10 136043.31 23-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.896305E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.365185E+10 138362.26   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.153425E+10 121392.01 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.689780E+09 117558.40 06-FEB-05:01 0.00 0.00 0.00 0.00 0.00
March 0.846056E+09 88687.96 11-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 2060122.62 2704.56 16-NOV-06:50 0.00 0.00 0.00 0.00 0.00
December 0.129239E+10 120131.52 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.436455E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.153425E+10 121392.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.435735E+09 150830.02 10-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.241320E+09 150855.54 06-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.592079E+09 65145.39 11-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.526566E+09 154237.29 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.179570E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.592079E+09 154237.29   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.120659E+10 115954.71 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.556624E+09 112183.05 06-FEB-06:01 0.00 0.00 0.00 0.00 0.00
March 0.524121E+09 40252.86 11-MAR-06:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.629063E+09 114739.15 20-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.291640E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.120659E+10 115954.71   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.128761E+09 21393.84 05-JAN-07:10 0.00 0.00 0.00 0.00 0.00
February 50788732.52 19804.16 17-FEB-07:10 0.00 0.00 0.00 0.00 0.00
March 43773498.48 19868.95 09-MAR-07:10 0.00 0.00 0.00 0.00 0.00
April 10379427.72 3416.92 18-APR-14:50 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 247329.35 148.48 28-OCT-06:10 0.00 0.00 0.00 0.00 0.00
November 5787500.76 5152.16 15-NOV-07:10 0.00 0.00 0.00 0.00 0.00
December 69263721.09 22713.15 21-DEC-07:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.309001E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.128761E+09 22713.15   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CORE_TOP VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.200109E+09 67620.34 23-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.351065E+09 68600.34 06-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.136800E+09 67370.36 13-MAR-05:03 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 53527624.84 34286.47 21-DEC-06:01 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.741502E+09     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.351065E+09 68600.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.171152E+10 14512.01 23-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.955808E+09 14439.26 06-FEB-06:17 0.00 0.00 0.00 0.00 0.00
March 0.594658E+09 14448.74 13-MAR-04:03 0.00 0.00 0.00 0.00 0.00
April 2600002.75 485.88 03-APR-06:00 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 12526897.90 1290.10 28-OCT-06:40 0.00 0.00 0.00 0.00 0.00
November 0.116399E+09 14406.84 24-NOV-06:03 0.00 0.00 0.00 0.00 0.00
December 0.108454E+10 14453.25 05-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.447805E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.171152E+10 14512.01   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.698628E+09 13854.68 05-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.384120E+09 13800.49 06-FEB-05:23 0.00 0.00 0.00 0.00 0.00
March 0.337092E+09 13722.30 10-MAR-05:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 5513041.28 989.64 28-OCT-06:40 0.00 0.00 0.00 0.00 0.00
November 39120330.47 13528.79 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.578284E+09 13854.72 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.204276E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.698628E+09 13854.72   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.505116E+09 17223.05 09-JAN-06:03 0.00 0.00 0.00 0.00 0.00
February 0.314837E+09 17190.14 06-FEB-06:04 0.00 0.00 0.00 0.00 0.00
March 0.369572E+09 17201.29 13-MAR-04:01 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 264006.07 211.27 28-OCT-06:40 0.00 0.00 0.00 0.00 0.00
November 6205328.53 1631.59 16-NOV-06:04 0.00 0.00 0.00 0.00 0.00
December 0.364691E+09 17193.78 30-DEC-06:02 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.156069E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.505116E+09 17223.05   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.697370E+09 14134.12 05-JAN-06:02 0.00 0.00 0.00 0.00 0.00
February 0.363108E+09 14088.37 06-FEB-06:02 0.00 0.00 0.00 0.00 0.00
March 0.262433E+09 13950.99 09-MAR-06:02 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 2015415.22 394.37 28-OCT-06:50 0.00 0.00 0.00 0.00 0.00
November 30235777.77 5346.06 16-NOV-06:02 0.00 0.00 0.00 0.00 0.00
December 0.426811E+09 14165.34 21-DEC-06:03 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.178197E+10     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.697370E+09 14165.34   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP HEATING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [J] HEATING COIL HEATING RATE {Maximum} [W] HEATING COIL HEATING RATE {TIMESTAMP} COOLING COIL TOTAL COOLING ENERGY [] COOLING COIL SENSIBLE COOLING ENERGY [] COOLING COIL TOTAL COOLING RATE [] COOLING COIL SENSIBLE COOLING RATE [] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 01-JAN-00:05 0.00 0.00 0.00 0.00 0.00
February 0.00 0.00 01-FEB-00:10 0.00 0.00 0.00 0.00 0.00
March 0.00 0.00 01-MAR-00:10 0.00 0.00 0.00 0.00 0.00
April 0.00 0.00 01-APR-00:10 0.00 0.00 0.00 0.00 0.00
May 0.00 0.00 01-MAY-00:05 0.00 0.00 0.00 0.00 0.00
June 0.00 0.00 01-JUN-00:10 0.00 0.00 0.00 0.00 0.00
July 0.00 0.00 01-JUL-00:03 0.00 0.00 0.00 0.00 0.00
August 0.00 0.00 01-AUG-00:03 0.00 0.00 0.00 0.00 0.00
September 0.00 0.00 01-SEP-00:05 0.00 0.00 0.00 0.00 0.00
October 0.00 0.00 01-OCT-00:10 0.00 0.00 0.00 0.00 0.00
November 0.00 0.00 01-NOV-00:10 0.00 0.00 0.00 0.00 0.00
December 0.00 0.00 01-DEC-00:10 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.00     0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.00 0.00   0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: CoilReportMonthly

For: VAV_BOT WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.342391E+11 0.265937E+11 168799.79 19-JAN-06:03 116493.73 0.23
February 0.00 0.00 0.488738E+11 0.366752E+11 180386.99 28-FEB-06:02 72370.12 0.38
March 0.00 0.00 0.651581E+11 0.542407E+11 208959.66 07-MAR-06:02 145354.89 0.38
April 0.00 0.00 0.109851E+12 0.928891E+11 206446.93 29-APR-05:02 144850.01 0.69
May 0.00 0.00 0.150401E+12 0.122674E+12 232449.88 24-MAY-03:02 142643.92 0.73
June 0.00 0.00 0.162738E+12 0.134790E+12 220574.81 28-JUN-05:02 153773.02 0.82
July 0.00 0.00 0.176160E+12 0.143564E+12 223397.89 03-JUL-05:02 153972.99 0.85
August 0.00 0.00 0.193773E+12 0.159654E+12 224764.42 21-AUG-05:03 158800.86 0.88
September 0.00 0.00 0.149166E+12 0.115876E+12 229700.99 05-SEP-03:02 150011.52 0.73
October 0.00 0.00 0.137372E+12 0.113254E+12 221490.55 06-OCT-05:02 150186.54 0.67
November 0.00 0.00 0.805258E+11 0.678669E+11 208890.27 02-NOV-05:02 146522.41 0.50
December 0.00 0.00 0.590780E+11 0.483666E+11 208236.56 16-DEC-06:02 144651.25 0.36
                 
Annual Sum or Average 0.00 0.00 0.136734E+13 0.111644E+13       0.60
Minimum of Months 0.00 0.00 0.342391E+11 0.265937E+11 168799.79   72370.12 0.23
Maximum of Months 0.00 0.00 0.193773E+12 0.159654E+12 232449.88   158800.86 0.88



Table of Contents

Report: CoilReportMonthly

For: VAV_MID WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.267454E+12 0.202814E+12 1454570.34 19-JAN-06:03 529668.76 0.21
February 0.00 0.00 0.378432E+12 0.278911E+12 1515309.23 28-FEB-06:02 607455.15 0.35
March 0.00 0.00 0.479486E+12 0.384419E+12 2053829.77 07-MAR-06:02 1309335.07 0.33
April 0.00 0.00 0.794848E+12 0.645535E+12 2047377.13 26-APR-05:03 1346779.57 0.51
May 0.00 0.00 0.135751E+13 0.106824E+13 2591312.84 22-MAY-03:02 1384820.44 0.67
June 0.00 0.00 0.139215E+13 0.110351E+13 2177070.60 19-JUN-03:02 1391219.91 0.70
July 0.00 0.00 0.143176E+13 0.108864E+13 2254851.86 26-JUL-05:03 1398748.05 0.70
August 0.00 0.00 0.148707E+13 0.113376E+13 2404068.81 15-AUG-03:02 1387955.00 0.69
September 0.00 0.00 0.131486E+13 0.967551E+12 2751506.84 05-SEP-03:02 1318266.43 0.67
October 0.00 0.00 0.113814E+13 0.887973E+12 2282805.22 07-OCT-03:02 1383667.02 0.57
November 0.00 0.00 0.606307E+12 0.491463E+12 2124444.42 01-NOV-05:03 1341207.78 0.43
December 0.00 0.00 0.412523E+12 0.317558E+12 2076060.99 15-DEC-06:02 1325051.51 0.28
                 
Annual Sum or Average 0.00 0.00 0.110606E+14 0.857037E+13       0.51
Minimum of Months 0.00 0.00 0.267454E+12 0.202814E+12 1454570.34   529668.76 0.21
Maximum of Months 0.00 0.00 0.148707E+13 0.113376E+13 2751506.84   1398748.05 0.70



Table of Contents

Report: CoilReportMonthly

For: VAV_TOP WITH REHEAT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.257704E+11 0.192649E+11 143803.00 19-JAN-06:03 87545.09 0.20
February 0.00 0.00 0.378887E+11 0.281386E+11 139287.12 28-FEB-06:02 55756.47 0.34
March 0.00 0.00 0.493188E+11 0.395297E+11 195943.60 27-MAR-05:02 85343.94 0.32
April 0.00 0.00 0.847841E+11 0.696855E+11 220697.29 29-APR-05:02 140539.13 0.50
May 0.00 0.00 0.150982E+12 0.120857E+12 265803.82 22-MAY-03:02 153948.02 0.68
June 0.00 0.00 0.157677E+12 0.127809E+12 243274.61 30-JUN-03:02 152399.39 0.71
July 0.00 0.00 0.162030E+12 0.126017E+12 251496.59 26-JUL-03:02 153917.38 0.72
August 0.00 0.00 0.165969E+12 0.129198E+12 259936.57 11-AUG-03:02 147958.41 0.71
September 0.00 0.00 0.142064E+12 0.106046E+12 296074.12 05-SEP-03:02 140557.56 0.67
October 0.00 0.00 0.122309E+12 0.966161E+11 256083.09 25-OCT-03:02 153030.58 0.57
November 0.00 0.00 0.594080E+11 0.482725E+11 218228.23 02-NOV-05:02 140363.44 0.42
December 0.00 0.00 0.397464E+11 0.302889E+11 183256.79 15-DEC-06:02 113090.48 0.27
                 
Annual Sum or Average 0.00 0.00 0.119795E+13 0.941723E+12       0.51
Minimum of Months 0.00 0.00 0.257704E+11 0.192649E+11 139287.12   55756.47 0.20
Maximum of Months 0.00 0.00 0.165969E+12 0.129198E+12 296074.12   153948.02 0.72



Table of Contents

Report: CoilReportMonthly

For: CAV_BAS COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.218968E+11 0.169084E+11 119639.89 01-JAN-16:12 98091.48 0.16
February 0.00 0.00 0.263542E+11 0.215636E+11 109905.30 03-FEB-06:03 42174.88 0.27
March 0.00 0.00 0.354979E+11 0.300986E+11 139139.19 07-MAR-04:03 86073.13 0.25
April 0.00 0.00 0.562278E+11 0.488070E+11 141680.75 29-APR-04:03 83502.45 0.44
May 0.00 0.00 0.103677E+12 0.800205E+11 173131.55 22-MAY-03:02 79669.10 0.59
June 0.00 0.00 0.108815E+12 0.815867E+11 172825.55 19-JUN-03:02 87580.28 0.60
July 0.00 0.00 0.117942E+12 0.834478E+11 160889.34 17-JUL-03:02 87119.64 0.58
August 0.00 0.00 0.130714E+12 0.949890E+11 169304.83 06-AUG-14:12 87136.56 0.64
September 0.00 0.00 0.110906E+12 0.810925E+11 169974.94 17-SEP-14:20 85360.28 0.62
October 0.00 0.00 0.953928E+11 0.734004E+11 168365.14 08-OCT-14:58 86783.60 0.52
November 0.00 0.00 0.523303E+11 0.433700E+11 143605.32 03-NOV-03:02 87453.91 0.37
December 0.00 0.00 0.342941E+11 0.277316E+11 137277.76 10-DEC-15:20 95889.66 0.24
                 
Annual Sum or Average 0.00 0.00 0.894049E+12 0.683016E+12       0.44
Minimum of Months 0.00 0.00 0.218968E+11 0.169084E+11 109905.30   42174.88 0.16
Maximum of Months 0.00 0.00 0.130714E+12 0.949890E+11 173131.55   98091.48 0.64



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BASEMENT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.331718E+12 0.329000E+12 136409.24 31-JAN-16:40 126594.14 0.00
February 0.00 0.00 0.522753E+12 0.517891E+12 227508.79 24-FEB-16:50 217934.04 0.00
March 0.00 0.00 0.823430E+12 0.818567E+12 393952.00 31-MAR-24:00 393952.00 0.00
April 0.00 0.00 0.103628E+13 0.103012E+13 422269.30 28-APR-18:00 403790.18 0.00
May 0.00 0.00 0.349000E+12 0.336384E+12 212762.30 31-MAY-23:10 210450.49 0.00
June 0.00 0.00 0.576229E+12 0.562358E+12 302726.56 30-JUN-23:03 302021.96 0.00
July 0.00 0.00 0.842408E+12 0.827501E+12 395008.21 31-JUL-23:53 395008.21 0.00
August 0.00 0.00 0.108075E+13 0.106732E+13 424437.60 07-AUG-14:00 403726.71 0.00
September 0.00 0.00 0.342098E+12 0.328554E+12 213274.21 30-SEP-24:00 212005.73 0.00
October 0.00 0.00 0.593623E+12 0.582774E+12 304073.58 31-OCT-24:00 304073.58 0.00
November 0.00 0.00 0.804250E+12 0.798245E+12 324540.11 03-NOV-16:00 311897.23 0.00
December 0.00 0.00 0.107079E+13 0.106704E+13 416142.25 13-DEC-18:00 403726.83 0.00
                 
Annual Sum or Average 0.00 0.00 0.837333E+13 0.826575E+13       0.00
Minimum of Months 0.00 0.00 0.331718E+12 0.328554E+12 136409.24   126594.14 0.00
Maximum of Months 0.00 0.00 0.108075E+13 0.106732E+13 424437.60   403790.18 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER BOT COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.522595E+10 0.511722E+10 2815.04 19-JAN-17:00 2453.19 0.00
February 0.00 0.00 0.963334E+10 0.944020E+10 4743.07 27-FEB-17:00 4382.47 0.00
March 0.00 0.00 0.158168E+11 0.156121E+11 7719.06 31-MAR-24:00 7719.06 0.00
April 0.00 0.00 0.205463E+11 0.202581E+11 8661.28 28-APR-17:20 8122.95 0.00
May 0.00 0.00 0.656738E+10 0.606268E+10 4098.04 31-MAY-23:10 3955.32 0.00
June 0.00 0.00 0.113496E+11 0.107689E+11 5880.12 30-JUN-23:43 5866.48 0.00
July 0.00 0.00 0.168360E+11 0.161843E+11 7743.94 31-JUL-23:57 7743.94 0.00
August 0.00 0.00 0.219447E+11 0.212887E+11 8920.93 07-AUG-13:50 8181.00 0.00
September 0.00 0.00 0.639852E+10 0.585585E+10 4072.46 30-SEP-24:00 4041.72 0.00
October 0.00 0.00 0.115026E+11 0.110511E+11 5896.72 31-OCT-24:00 5888.35 0.00
November 0.00 0.00 0.155902E+11 0.153395E+11 6812.59 07-NOV-16:40 6277.34 0.00
December 0.00 0.00 0.208571E+11 0.206805E+11 8752.63 14-DEC-17:00 8285.41 0.00
                 
Annual Sum or Average 0.00 0.00 0.162269E+12 0.157659E+12       0.00
Minimum of Months 0.00 0.00 0.522595E+10 0.511722E+10 2815.04   2453.19 0.00
Maximum of Months 0.00 0.00 0.219447E+11 0.212887E+11 8920.93   8285.41 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER MID COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.402077E+11 0.391491E+11 26479.92 19-JAN-17:00 22891.68 0.00
February 0.00 0.00 0.845363E+11 0.826269E+11 45068.26 27-FEB-17:00 41487.15 0.00
March 0.00 0.00 0.145211E+12 0.143172E+12 72714.50 31-MAR-24:00 72714.50 0.00
April 0.00 0.00 0.195032E+12 0.192146E+12 82671.37 28-APR-17:20 77324.51 0.00
May 0.00 0.00 0.616944E+11 0.566988E+11 38933.34 31-MAY-23:10 37406.82 0.00
June 0.00 0.00 0.108247E+12 0.102466E+12 57115.28 30-JUN-23:53 56979.32 0.00
July 0.00 0.00 0.160671E+12 0.154167E+12 74523.99 31-JUL-23:57 74523.99 0.00
August 0.00 0.00 0.208488E+12 0.201930E+12 84741.14 07-AUG-13:50 77382.41 0.00
September 0.00 0.00 0.592091E+11 0.538525E+11 38398.57 30-SEP-24:00 38082.00 0.00
October 0.00 0.00 0.107970E+12 0.103480E+12 55315.74 31-OCT-24:00 55208.91 0.00
November 0.00 0.00 0.144059E+12 0.141564E+12 64978.12 07-NOV-16:40 59646.44 0.00
December 0.00 0.00 0.191363E+12 0.189594E+12 83141.25 14-DEC-17:00 78477.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.150669E+13 0.146085E+13       0.00
Minimum of Months 0.00 0.00 0.402077E+11 0.391491E+11 26479.92   22891.68 0.00
Maximum of Months 0.00 0.00 0.208488E+12 0.201930E+12 84741.14   78477.30 0.00



Table of Contents

Report: CoilReportMonthly

For: AIRLOOP DATACENTER TOP COOLING COIL

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

HEATING COIL HEATING ENERGY [] HEATING COIL HEATING RATE [] COOLING COIL TOTAL COOLING ENERGY [J] COOLING COIL SENSIBLE COOLING ENERGY [J] COOLING COIL TOTAL COOLING RATE {Maximum} [W] COOLING COIL TOTAL COOLING RATE {TIMESTAMP} COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] COOLING COIL WETTED AREA FRACTION []
January 0.00 0.00 0.298188E+10 0.287757E+10 2716.01 19-JAN-17:00 2356.05 0.00
February 0.00 0.00 0.771631E+10 0.752664E+10 4565.92 27-FEB-17:00 4207.69 0.00
March 0.00 0.00 0.140046E+11 0.138013E+11 7177.44 31-MAR-24:00 7177.44 0.00
April 0.00 0.00 0.194033E+11 0.191153E+11 8367.72 28-APR-17:20 7829.91 0.00
May 0.00 0.00 0.630387E+10 0.580248E+10 3872.97 31-MAY-23:10 3719.37 0.00
June 0.00 0.00 0.109690E+11 0.103903E+11 5751.01 30-JUN-23:53 5737.35 0.00
July 0.00 0.00 0.162259E+11 0.155756E+11 7445.64 31-JUL-23:57 7445.64 0.00
August 0.00 0.00 0.209977E+11 0.203413E+11 8559.26 14-AUG-16:00 7894.47 0.00
September 0.00 0.00 0.603300E+10 0.549586E+10 3891.55 30-SEP-24:00 3860.50 0.00
October 0.00 0.00 0.107689E+11 0.103200E+11 5484.20 31-OCT-24:00 5472.80 0.00
November 0.00 0.00 0.139793E+11 0.137308E+11 6558.31 07-NOV-16:40 6024.84 0.00
December 0.00 0.00 0.183680E+11 0.181916E+11 8371.61 14-DEC-17:00 7905.30 0.00
                 
Annual Sum or Average 0.00 0.00 0.147752E+12 0.143169E+12       0.00
Minimum of Months 0.00 0.00 0.298188E+10 0.287757E+10 2716.01   2356.05 0.00
Maximum of Months 0.00 0.00 0.209977E+11 0.203413E+11 8559.26   7905.30 0.00



Table of Contents

Report: PlantLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 4536.50 835681.10 10-JAN-06:02
February 0.00 0.00 01-FEB-00:10 2685.40 846264.83 06-FEB-06:01
March 0.00 0.00 01-MAR-00:10 2101.45 580033.84 11-MAR-06:03
April 0.00 0.00 01-APR-00:10 86.08 45413.30 18-APR-14:30
May 0.00 0.00 01-MAY-00:05 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:03 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:03 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 2.82 1092.29 28-OCT-06:40
November 0.00 0.00 01-NOV-00:10 72.94 44092.98 27-NOV-14:20
December 0.00 0.00 01-DEC-00:10 3073.08 852257.95 21-DEC-06:01
             
Annual Sum or Average 0.00     1044.08    
Minimum of Months 0.00 0.00   0.00 0.00  
Maximum of Months 0.00 0.00   4536.50 852257.95  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 222199.35 1776720.36 19-JAN-06:03 0.97 17378.04 01-JAN-05:23
February 336658.15 1712163.92 24-FEB-13:10 1.00 12086.88 26-FEB-09:23
March 390658.08 2302650.67 07-MAR-06:04 34.33 183171.99 19-MAR-08:13
April 647032.32 2593334.71 29-APR-05:02 0.05 781.84 09-APR-23:33
May 940377.28 3141983.77 24-MAY-05:03 0.00 0.00 01-MAY-00:05
June 977051.04 2843070.04 08-JUN-05:04 0.00 0.00 01-JUN-00:10
July 972937.46 3289953.98 31-JUL-05:04 0.00 0.00 01-JUL-00:03
August 994884.68 2901200.29 01-AUG-05:04 0.00 0.00 01-AUG-00:03
September 938046.35 2963436.30 13-SEP-05:03 0.00 0.00 01-SEP-00:05
October 798755.53 3032100.65 20-OCT-05:04 2.46 28471.76 29-OCT-19:33
November 505261.07 2678073.48 02-NOV-05:02 15.81 84048.06 19-NOV-18:53
December 336297.72 2756609.21 15-DEC-06:04 4.69 44427.22 31-DEC-21:13
             
Annual Sum or Average 673390.59     4.98    
Minimum of Months 222199.35 1712163.92   0.00 0.00  
Maximum of Months 994884.68 3289953.98   34.33 183171.99  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 159967.97 3193301.15 19-JAN-06:03 0.00 0.00 01-JAN-00:05
February 251897.80 3482738.19 28-FEB-06:02 0.00 0.00 01-FEB-00:10
March 283276.52 4125445.37 07-MAR-06:02 0.00 0.00 01-MAR-00:10
April 476826.81 4130577.91 29-APR-05:02 0.00 0.00 01-APR-00:10
May 748842.17 4362661.83 10-MAY-05:02 0.00 0.00 01-MAY-00:05
June 785753.50 4230109.91 08-JUN-05:02 0.00 0.00 01-JUN-00:10
July 774027.55 4281972.98 31-JUL-05:02 0.00 0.00 01-JUL-00:03
August 813379.75 4341884.70 07-AUG-05:02 0.00 0.00 01-AUG-00:03
September 750530.31 4710341.63 05-SEP-03:02 0.00 0.00 01-SEP-00:05
October 633304.96 4343121.36 11-OCT-05:02 0.00 0.00 01-OCT-00:10
November 372531.03 4193746.16 02-NOV-05:02 0.00 0.00 01-NOV-00:10
December 248841.98 4262561.13 15-DEC-06:02 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 526392.48     0.00    
Minimum of Months 159967.97 3193301.15   0.00 0.00  
Maximum of Months 813379.75 4710341.63   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 244437.57 744419.59 02-JAN-15:00 0.00 0.00 01-JAN-00:05
February 450640.28 1035948.96 02-FEB-13:10 0.00 0.00 01-FEB-00:10
March 687278.79 1336119.03 30-MAR-13:00 0.00 0.00 01-MAR-00:10
April 1069279.24 1758685.33 28-APR-15:00 0.00 0.00 01-APR-00:10
May 737325.01 1101891.63 18-MAY-16:00 0.00 0.00 01-MAY-00:05
June 999142.31 1425474.56 14-JUN-14:00 0.00 0.00 01-JUN-00:10
July 1243310.74 1739962.02 21-JUL-16:00 0.00 0.00 01-JUL-00:03
August 1431570.18 1911302.02 30-AUG-16:10 0.00 0.00 01-AUG-00:03
September 705062.85 1264988.73 09-SEP-17:00 0.00 0.00 01-SEP-00:05
October 819014.29 1376855.99 05-OCT-15:00 0.00 0.00 01-OCT-00:10
November 757228.59 1382792.26 02-NOV-13:00 0.00 0.00 01-NOV-00:10
December 832637.59 1575232.05 13-DEC-15:00 0.00 0.00 01-DEC-00:10
             
Annual Sum or Average 833978.40     0.00    
Minimum of Months 244437.57 744419.59   0.00 0.00  
Maximum of Months 1431570.18 1911302.02   0.00 0.00  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 12872.40 42424.01 25-JAN-12:40
February 0.00 0.00 01-FEB-00:10 12848.26 42362.61 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 13094.26 41421.46 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 11687.11 39162.13 03-APR-12:00
May 0.00 0.00 01-MAY-00:05 11287.80 36776.47 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 10898.83 34320.97 01-JUN-11:40
July 0.00 0.00 01-JUL-00:03 9869.12 32682.26 03-JUL-11:40
August 0.00 0.00 01-AUG-00:03 10767.89 33345.93 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 10638.63 35304.02 29-SEP-11:50
October 0.00 0.00 01-OCT-00:10 11291.04 38011.11 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 12157.86 40419.46 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 12325.05 41967.03 29-DEC-12:50
             
Annual Sum or Average 0.00     11638.24    
Minimum of Months 0.00 0.00   9869.12 32682.26  
Maximum of Months 0.00 0.00   13094.26 42424.01  



Table of Contents

Report: PlantLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 180137.24 3674544.78 19-JAN-12:00 1943.88 190590.83 21-JAN-11:30
February 272230.40 3580410.81 24-FEB-13:20 1130.59 181561.35 17-FEB-07:50
March 334616.96 4098203.56 07-MAR-11:30 1586.49 188773.57 09-MAR-11:00
April 664928.68 5615019.25 28-APR-16:00 793.97 132029.93 10-APR-08:20
May 1864149.01 6067390.26 24-MAY-05:05 0.00 0.00 01-MAY-00:05
June 2175860.82 6239731.25 28-JUN-14:00 0.00 0.00 01-JUN-00:10
July 2554553.19 6519640.34 12-JUL-10:10 0.00 0.00 01-JUL-00:03
August 2467901.48 6453960.77 14-AUG-11:00 0.44 3948.61 20-AUG-04:40
September 1987138.32 6451798.07 18-SEP-14:00 0.00 0.00 01-SEP-00:05
October 1497200.70 6692347.80 24-OCT-13:30 334.79 119709.13 27-OCT-17:50
November 590867.10 5428491.22 01-NOV-14:00 1535.17 154065.82 22-NOV-09:50
December 350792.14 5083777.27 12-DEC-14:20 1759.05 182682.84 20-DEC-15:30
             
Annual Sum or Average 1251825.12     755.88    
Minimum of Months 180137.24 3580410.81   0.00 0.00  
Maximum of Months 2554553.19 6692347.80   1943.88 190590.83  



Table of Contents

Report: FanReportMonthly

For: CAV_BAS FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.151143E+11 0.84 9290.26 01-JAN-00:20 1.37
February 0.132172E+11 0.81 9290.26 01-FEB-04:03 1.38
March 0.151784E+11 0.84 9290.26 01-MAR-04:03 1.38
April 0.138852E+11 0.79 9290.26 01-APR-03:02 1.38
May 0.149819E+11 0.83 9290.26 01-MAY-03:02 1.38
June 0.146433E+11 0.83 9290.26 01-JUN-03:02 1.38
July 0.147184E+11 0.81 9290.26 01-JUL-03:02 1.38
August 0.162706E+11 0.90 9290.26 01-AUG-03:03 1.38
September 0.153983E+11 0.88 9290.26 01-SEP-03:02 1.38
October 0.158403E+11 0.88 9290.26 01-OCT-13:16 1.37
November 0.153407E+11 0.88 9290.26 01-NOV-03:05 1.37
December 0.153907E+11 0.86 9290.26 01-DEC-04:03 1.39
           
Annual Sum or Average 0.179979E+12 0.85      
Minimum of Months 0.132172E+11 0.79 9290.26   1.37
Maximum of Months 0.162706E+11 0.90 9290.26   1.39



Table of Contents

Report: FanReportMonthly

For: VAV_BOT WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.592536E+10 0.39 19314.86 02-JAN-06:02 1.76
February 0.620593E+10 0.43 19254.93 27-FEB-06:02 1.76
March 0.839646E+10 0.50 19314.86 27-MAR-05:02 1.76
April 0.102676E+11 0.60 19314.86 18-APR-12:05 1.76
May 0.105108E+11 0.58 19314.86 01-MAY-05:02 1.76
June 0.117660E+11 0.66 19314.86 08-JUN-05:02 1.76
July 0.125788E+11 0.68 19314.86 06-JUL-05:03 1.76
August 0.150613E+11 0.76 19314.86 02-AUG-05:02 1.76
September 0.980537E+10 0.57 19314.86 05-SEP-03:02 1.76
October 0.101668E+11 0.57 19314.86 03-OCT-05:02 1.76
November 0.857445E+10 0.51 19314.86 02-NOV-05:02 1.76
December 0.781333E+10 0.48 19314.86 12-DEC-06:02 1.76
           
Annual Sum or Average 0.117072E+12 0.56      
Minimum of Months 0.592536E+10 0.39 19254.93   1.76
Maximum of Months 0.150613E+11 0.76 19314.86   1.76



Table of Contents

Report: FanReportMonthly

For: VAV_MID WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.406986E+11 0.33 128434.74 02-JAN-06:02 1.43
February 0.404960E+11 0.35 140524.93 28-FEB-06:02 1.51
March 0.521199E+11 0.39 178679.99 27-MAR-05:02 1.76
April 0.639477E+11 0.43 178679.99 18-APR-14:40 1.77
May 0.928688E+11 0.54 178679.99 01-MAY-05:02 1.76
June 0.956132E+11 0.57 178679.99 01-JUN-05:03 1.76
July 0.905658E+11 0.54 178679.99 03-JUL-05:02 1.76
August 0.985827E+11 0.57 178679.99 01-AUG-05:02 1.76
September 0.797594E+11 0.51 178679.99 01-SEP-05:03 1.76
October 0.744310E+11 0.47 178679.99 05-OCT-03:02 1.76
November 0.522700E+11 0.39 178679.99 01-NOV-05:03 1.76
December 0.431209E+11 0.34 178679.99 15-DEC-06:02 1.76
           
Annual Sum or Average 0.824474E+12 0.45      
Minimum of Months 0.404960E+11 0.33 128434.74   1.43
Maximum of Months 0.985827E+11 0.57 178679.99   1.77



Table of Contents

Report: FanReportMonthly

For: VAV_TOP WITH REHEAT FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.341808E+10 0.31 10153.34 02-JAN-06:02 1.17
February 0.370760E+10 0.33 12319.46 27-FEB-06:02 1.32
March 0.467302E+10 0.36 18520.59 27-MAR-05:02 1.71
April 0.627882E+10 0.41 19301.94 18-APR-14:20 1.77
May 0.102022E+11 0.55 19301.94 04-MAY-05:02 1.76
June 0.108801E+11 0.59 19301.94 12-JUN-05:02 1.76
July 0.103120E+11 0.57 19301.94 01-JUL-05:03 1.76
August 0.109654E+11 0.58 19301.94 01-AUG-05:02 1.76
September 0.837518E+10 0.50 19301.94 01-SEP-05:03 1.76
October 0.777843E+10 0.46 19301.94 06-OCT-05:02 1.76
November 0.461798E+10 0.35 19301.94 02-NOV-05:02 1.76
December 0.371020E+10 0.31 11396.30 15-DEC-06:02 1.26
           
Annual Sum or Average 0.849189E+11 0.44      
Minimum of Months 0.341808E+10 0.31 10153.34   1.17
Maximum of Months 0.109654E+11 0.59 19301.94   1.77



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.947342E+11 1.35 35369.70 01-JAN-00:10 1.35
February 0.855664E+11 1.35 35369.70 01-FEB-00:10 1.35
March 0.947342E+11 1.35 35369.70 01-MAR-00:10 1.35
April 0.916783E+11 1.35 35369.70 01-APR-00:10 1.35
May 0.947342E+11 1.35 35369.70 01-MAY-00:05 1.35
June 0.916783E+11 1.35 35369.70 01-JUN-00:10 1.35
July 0.947342E+11 1.35 35369.70 01-JUL-00:03 1.35
August 0.947342E+11 1.35 35369.70 01-AUG-00:03 1.35
September 0.916783E+11 1.35 35369.70 01-SEP-00:10 1.35
October 0.947342E+11 1.35 35369.70 01-OCT-00:10 1.35
November 0.916783E+11 1.35 35369.70 01-NOV-00:10 1.35
December 0.947342E+11 1.35 35369.70 01-DEC-00:10 1.35
           
Annual Sum or Average 0.111542E+13 1.35      
Minimum of Months 0.855664E+11 1.35 35369.70   1.35
Maximum of Months 0.947342E+11 1.35 35369.70   1.35



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER BOT SUPPLY FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.139709E+10 0.91 521.61 01-JAN-00:05 0.91
February 0.126188E+10 0.91 521.61 01-FEB-00:10 0.91
March 0.139709E+10 0.91 521.61 01-MAR-00:10 0.91
April 0.135202E+10 0.91 521.61 01-APR-00:10 0.91
May 0.139709E+10 0.91 521.61 01-MAY-00:10 0.91
June 0.135202E+10 0.91 521.61 01-JUN-00:10 0.91
July 0.139709E+10 0.91 521.61 01-JUL-00:03 0.91
August 0.139709E+10 0.91 521.61 01-AUG-00:03 0.91
September 0.135202E+10 0.91 521.61 01-SEP-00:05 0.91
October 0.139709E+10 0.91 521.61 01-OCT-00:20 0.91
November 0.135202E+10 0.91 521.61 01-NOV-00:10 0.91
December 0.139709E+10 0.91 521.61 01-DEC-00:10 0.91
           
Annual Sum or Average 0.164496E+11 0.91      
Minimum of Months 0.126188E+10 0.91 521.61   0.91
Maximum of Months 0.139709E+10 0.91 521.61   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER MID SUPPLY FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.132773E+11 0.91 4957.19 01-JAN-00:05 0.91
February 0.119924E+11 0.91 4957.19 01-FEB-00:10 0.91
March 0.132773E+11 0.91 4957.19 01-MAR-00:10 0.91
April 0.128490E+11 0.91 4957.19 01-APR-00:10 0.91
May 0.132773E+11 0.91 4957.19 01-MAY-00:05 0.91
June 0.128490E+11 0.91 4957.19 01-JUN-00:10 0.91
July 0.132773E+11 0.91 4957.19 01-JUL-00:03 0.91
August 0.132773E+11 0.91 4957.19 01-AUG-00:03 0.91
September 0.128490E+11 0.91 4957.19 01-SEP-00:05 0.91
October 0.132773E+11 0.91 4957.19 01-OCT-00:10 0.91
November 0.128490E+11 0.91 4957.19 01-NOV-00:10 0.91
December 0.132773E+11 0.91 4957.19 01-DEC-00:10 0.91
           
Annual Sum or Average 0.156330E+12 0.91      
Minimum of Months 0.119924E+11 0.91 4957.19   0.91
Maximum of Months 0.132773E+11 0.91 4957.19   0.91



Table of Contents

Report: FanReportMonthly

For: AIRLOOP DATACENTER TOP SUPPLY FAN

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

FAN ELECTRICITY ENERGY [J] FAN RISE IN AIR TEMPERATURE [deltaC] FAN ELECTRICITY RATE {Maximum} [W] FAN ELECTRICITY RATE {TIMESTAMP} FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC]
January 0.135421E+10 0.91 505.60 01-JAN-00:05 0.91
February 0.122315E+10 0.91 505.60 01-FEB-00:10 0.91
March 0.135421E+10 0.91 505.60 01-MAR-00:10 0.91
April 0.131052E+10 0.91 505.60 01-APR-00:10 0.91
May 0.135421E+10 0.91 505.60 01-MAY-00:05 0.91
June 0.131052E+10 0.91 505.60 01-JUN-00:10 0.91
July 0.135421E+10 0.91 505.60 01-JUL-00:03 0.91
August 0.135421E+10 0.91 505.60 01-AUG-00:03 0.91
September 0.131052E+10 0.91 505.60 01-SEP-00:10 0.91
October 0.135421E+10 0.91 505.60 01-OCT-00:10 0.91
November 0.131052E+10 0.91 505.60 01-NOV-00:10 0.91
December 0.135421E+10 0.91 505.60 01-DEC-00:10 0.91
           
Annual Sum or Average 0.159447E+11 0.91      
Minimum of Months 0.122315E+10 0.91 505.60   0.91
Maximum of Months 0.135421E+10 0.91 505.60   0.91



Table of Contents

Report: PumpReportMonthly

For: HEATSYS1 PUMP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 55649384.98 50084446.48 2669.34 10-JAN-06:02 2402.41 2402.41 36.06 4.49
February 30888926.61 27800033.95 2793.81 06-FEB-06:01 2514.43 2514.43 39.74 4.95
March 24487271.51 22038544.36 2117.72 11-MAR-06:03 1905.94 1905.94 33.79 3.00
April 1735457.38 1561911.65 331.83 18-APR-15:00 298.64 298.64 55.69 0.35
May 0.00 0.00 0.00 01-MAY-00:05 0.00 0.00 58.89 0.00
June 0.00 0.00 0.00 01-JUN-00:10 0.00 0.00 58.89 0.00
July 0.00 0.00 0.00 01-JUL-00:03 0.00 0.00 58.89 0.00
August 0.00 0.00 0.00 01-AUG-00:03 0.00 0.00 58.89 0.00
September 0.00 0.00 0.00 01-SEP-00:05 0.00 0.00 58.89 0.00
October 79966.15 71969.54 11.46 28-OCT-06:40 10.32 10.32 56.80 0.01
November 1187226.51 1068503.86 259.01 16-NOV-06:02 233.11 233.11 43.33 0.27
December 36508158.26 32857342.44 2705.52 20-DEC-06:02 2434.97 2434.97 37.45 4.62
                 
Annual Sum or Average 0.150536E+09 0.135483E+09            
Minimum of Months 0.00 0.00 0.00   0.00 0.00 33.79 0.00
Maximum of Months 55649384.98 50084446.48 2793.81   2514.43 2514.43 58.89 4.95



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP SECONDARY

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.332519E+09 0.299267E+09 13035.71 19-JAN-06:03 11732.14 11732.14 8.26 97.03
February 0.556023E+09 0.500421E+09 17249.40 28-FEB-06:02 15524.46 15524.46 8.25 108.61
March 0.571491E+09 0.514342E+09 26817.12 27-MAR-05:02 24135.41 24135.41 8.08 129.36
April 0.955206E+09 0.859686E+09 26817.12 24-APR-05:03 24135.41 24135.41 8.07 129.36
May 0.187000E+10 0.168300E+10 26817.12 04-MAY-05:02 24135.41 24135.41 7.71 129.36
June 0.189859E+10 0.170873E+10 26817.12 01-JUN-05:03 24135.41 24135.41 7.80 129.36
July 0.189812E+10 0.170831E+10 26817.12 03-JUL-05:02 24135.41 24135.41 7.29 129.36
August 0.211437E+10 0.190293E+10 26817.12 01-AUG-05:02 24135.41 24135.41 7.52 129.36
September 0.180486E+10 0.162437E+10 26817.12 05-SEP-05:02 24135.41 24135.41 8.07 129.36
October 0.190060E+10 0.171054E+10 26817.12 10-OCT-05:03 24135.41 24135.41 7.81 129.36
November 0.996723E+09 0.897050E+09 26817.12 02-NOV-05:02 24135.41 24135.41 7.80 129.36
December 0.621114E+09 0.559002E+09 25814.34 15-DEC-06:02 23232.91 23232.91 7.90 127.43
                 
Annual Sum or Average 0.155196E+11 0.139677E+11            
Minimum of Months 0.332519E+09 0.299267E+09 13035.71   11732.14 11732.14 7.29 97.03
Maximum of Months 0.211437E+10 0.190293E+10 26817.12   24135.41 24135.41 8.26 129.36



Table of Contents

Report: PumpReportMonthly

For: COOLSYS1 PUMP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.160346E+11 0.144311E+11 18457.50 01-JAN-00:23 16611.75 16611.75 8.22 129.36
February 0.201493E+11 0.181344E+11 18457.50 01-FEB-04:03 16611.75 16611.75 9.21 129.36
March 0.248665E+11 0.223798E+11 18457.50 01-MAR-04:03 16611.75 16611.75 9.19 129.36
April 0.367297E+11 0.330567E+11 18457.50 01-APR-03:02 16611.75 16611.75 9.35 129.36
May 0.382292E+11 0.344063E+11 18457.50 01-MAY-00:05 16611.75 16611.75 7.54 129.36
June 0.415971E+11 0.374374E+11 18457.50 01-JUN-03:02 16611.75 16611.75 11.26 129.36
July 0.450560E+11 0.405504E+11 18457.50 01-JUL-00:03 16611.75 16611.75 7.15 129.36
August 0.463108E+11 0.416797E+11 18457.50 01-AUG-00:10 16611.75 16611.75 7.13 129.36
September 0.370909E+11 0.333818E+11 18457.50 01-SEP-00:05 16611.75 16611.75 7.17 129.36
October 0.377111E+11 0.339400E+11 18457.50 01-OCT-07:33 16611.75 16611.75 8.50 129.36
November 0.295383E+11 0.265844E+11 18457.50 01-NOV-00:53 16611.75 16611.75 8.73 129.36
December 0.226055E+11 0.203449E+11 18457.50 01-DEC-04:03 16611.75 16611.75 8.46 129.36
                 
Annual Sum or Average 0.395919E+12 0.356327E+12            
Minimum of Months 0.160346E+11 0.144311E+11 18457.50   16611.75 16611.75 7.13 129.36
Maximum of Months 0.463108E+11 0.416797E+11 18457.50   16611.75 16611.75 11.26 129.36



Table of Contents

Report: PumpReportMonthly

For: PLANT CIRC PUMP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.909446E+10 0.818502E+10 3395.48 01-JAN-00:05 3055.94 3055.94 22.61 14.18
February 0.821436E+10 0.739292E+10 3395.48 01-FEB-00:10 3055.94 3055.94 27.13 14.18
March 0.909446E+10 0.818502E+10 3395.48 01-MAR-00:10 3055.94 3055.94 30.56 14.18
April 0.880109E+10 0.792099E+10 3395.48 01-APR-00:10 3055.94 3055.94 38.71 14.18
May 0.909446E+10 0.818502E+10 3395.48 01-MAY-00:05 3055.94 3055.94 28.63 14.18
June 0.880109E+10 0.792099E+10 3395.48 01-JUN-00:10 3055.94 3055.94 32.83 14.18
July 0.909446E+10 0.818502E+10 3395.48 01-JUL-00:03 3055.94 3055.94 39.34 14.18
August 0.909446E+10 0.818502E+10 3395.48 01-AUG-00:03 3055.94 3055.94 43.77 14.18
September 0.880109E+10 0.792099E+10 3395.48 01-SEP-00:05 3055.94 3055.94 31.49 14.18
October 0.909446E+10 0.818502E+10 3395.48 01-OCT-00:10 3055.94 3055.94 32.07 14.18
November 0.880109E+10 0.792099E+10 3395.48 01-NOV-00:10 3055.94 3055.94 35.60 14.18
December 0.909446E+10 0.818502E+10 3395.48 01-DEC-00:10 3055.94 3055.94 30.82 14.18
                 
Annual Sum or Average 0.107080E+12 0.963720E+11            
Minimum of Months 0.821436E+10 0.739292E+10 3395.48   3055.94 3055.94 22.61 14.18
Maximum of Months 0.909446E+10 0.818502E+10 3395.48   3055.94 3055.94 43.77 14.18



Table of Contents

Report: PumpReportMonthly

For: SWHSYS1 PUMP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 11967951.72 3590385.52 5.96 01-JAN-06:05 1.79 1.79 56.23 0.44
February 10809762.85 3242928.85 5.96 01-FEB-06:02 1.79 1.79 56.30 0.44
March 11967951.72 3590385.52 5.96 01-MAR-06:02 1.79 1.79 56.42 0.44
April 11581888.76 3474566.63 5.96 01-APR-05:03 1.79 1.79 57.16 0.44
May 11967951.72 3590385.52 5.96 01-MAY-05:02 1.79 1.79 57.03 0.44
June 11581888.76 3474566.63 5.96 01-JUN-05:03 1.79 1.79 57.04 0.44
July 11967951.72 3590385.52 5.96 01-JUL-05:03 1.79 1.79 56.90 0.44
August 11967951.72 3590385.52 5.96 01-AUG-05:02 1.79 1.79 56.57 0.44
September 11581888.76 3474566.63 5.96 01-SEP-05:03 1.79 1.79 56.93 0.44
October 11967951.72 3590385.52 5.96 01-OCT-05:10 1.79 1.79 56.63 0.44
November 11581888.76 3474566.63 5.96 01-NOV-05:03 1.79 1.79 57.12 0.44
December 11967951.72 3590385.52 5.96 01-DEC-06:02 1.79 1.79 56.58 0.44
                 
Annual Sum or Average 0.140913E+09 42273893.99            
Minimum of Months 10809762.85 3242928.85 5.96   1.79 1.79 56.23 0.44
Maximum of Months 11967951.72 3590385.52 5.96   1.79 1.79 57.16 0.44



Table of Contents

Report: PumpReportMonthly

For: TOWERWATERSYS PUMP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PUMP ELECTRICITY ENERGY [J] PUMP FLUID HEAT GAIN ENERGY [J] PUMP ELECTRICITY RATE {Maximum} [W] PUMP ELECTRICITY RATE {TIMESTAMP} PUMP SHAFT POWER {AT MAX/MIN} [W] PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s]
January 0.208684E+11 0.187816E+11 45883.48 19-JAN-12:00 41295.13 41295.13 26.88 152.19
February 0.261680E+11 0.235512E+11 45877.79 24-FEB-13:20 41290.01 41290.01 26.73 152.19
March 0.318788E+11 0.286909E+11 45909.13 07-MAR-11:30 41318.22 41318.22 27.54 152.19
April 0.492596E+11 0.443336E+11 45957.91 28-APR-15:40 41362.12 41362.12 29.16 152.19
May 0.629230E+11 0.566307E+11 45957.91 01-MAY-05:04 41362.12 41362.12 28.94 152.19
June 0.672962E+11 0.605666E+11 45957.91 01-JUN-11:30 41362.12 41362.12 28.94 152.19
July 0.723766E+11 0.651390E+11 45957.91 03-JUL-05:04 41362.12 41362.12 28.94 152.19
August 0.758219E+11 0.682397E+11 45957.91 01-AUG-08:70 41362.12 41362.12 28.94 152.19
September 0.598585E+11 0.538727E+11 45957.91 01-SEP-07:40 41362.12 41362.12 29.14 152.19
October 0.583151E+11 0.524836E+11 45957.91 05-OCT-08:50 41362.12 41362.12 28.87 152.19
November 0.403822E+11 0.363440E+11 45957.91 01-NOV-12:10 41362.12 41362.12 29.07 152.19
December 0.299735E+11 0.269762E+11 45957.91 12-DEC-14:10 41362.12 41362.12 28.93 152.19
                 
Annual Sum or Average 0.595122E+12 0.535610E+12            
Minimum of Months 0.208684E+11 0.187816E+11 45877.79   41290.01 41290.01 26.73 152.19
Maximum of Months 0.758219E+11 0.682397E+11 45957.91   41362.12 41362.12 29.16 152.19



Table of Contents

Report: CondLoopDemandReportMonthly

For: HEATSYS1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 79.40 79.40 4536.50 835681.10 10-JAN-06:02
February 0.00 0.00 01-FEB-00:10 23.87 23.87 2685.40 846264.83 06-FEB-06:01
March 0.00 0.00 01-MAR-00:10 24.51 24.51 2101.45 580033.84 11-MAR-06:03
April 0.00 0.00 01-APR-00:10 44.84 44.84 86.08 45413.30 18-APR-14:30
May 0.00 0.00 01-MAY-00:05 58.89 58.89 0.00 0.00 01-MAY-00:05
June 0.00 0.00 01-JUN-00:10 58.89 58.89 0.00 0.00 01-JUN-00:10
July 0.00 0.00 01-JUL-00:03 58.89 58.89 0.00 0.00 01-JUL-00:03
August 0.00 0.00 01-AUG-00:03 58.89 58.89 0.00 0.00 01-AUG-00:03
September 0.00 0.00 01-SEP-00:05 58.89 58.89 0.00 0.00 01-SEP-00:05
October 0.00 0.00 01-OCT-00:10 58.89 58.89 2.82 1092.29 28-OCT-06:40
November 0.00 0.00 01-NOV-00:10 55.16 55.16 72.94 44092.98 27-NOV-14:20
December 0.00 0.00 01-DEC-00:10 39.44 39.44 3073.08 852257.95 21-DEC-06:01
                 
Annual Sum or Average 0.00         1044.08    
Minimum of Months 0.00 0.00   23.87 23.87 0.00 0.00  
Maximum of Months 0.00 0.00   79.40 79.40 4536.50 852257.95  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_SUPPLY

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 222199.35 1776720.36 19-JAN-06:03 11.16 7.88 0.97 17378.04 01-JAN-05:23
February 336658.15 1712163.92 24-FEB-13:10 9.86 6.70 1.00 12086.88 26-FEB-09:23
March 390658.08 2302650.67 07-MAR-06:04 11.79 7.54 34.33 183171.99 19-MAR-08:13
April 647032.32 2593334.71 29-APR-05:02 12.01 7.23 0.05 781.84 09-APR-23:33
May 940377.28 3141983.77 24-MAY-05:03 12.76 7.06 0.00 0.00 01-MAY-00:05
June 977051.04 2843070.04 08-JUN-05:04 12.62 7.38 0.00 0.00 01-JUN-00:10
July 972937.46 3289953.98 31-JUL-05:04 13.12 7.42 0.00 0.00 01-JUL-00:03
August 994884.68 2901200.29 01-AUG-05:04 12.48 7.12 0.00 0.00 01-AUG-00:03
September 938046.35 2963436.30 13-SEP-05:03 12.69 7.22 0.00 0.00 01-SEP-00:05
October 798755.53 3032100.65 20-OCT-05:04 13.01 7.41 2.46 28471.76 29-OCT-19:33
November 505261.07 2678073.48 02-NOV-05:02 12.14 7.20 15.81 84048.06 19-NOV-18:53
December 336297.72 2756609.21 15-DEC-06:04 12.65 7.56 4.69 44427.22 31-DEC-21:13
                 
Annual Sum or Average 673390.59         4.98    
Minimum of Months 222199.35 1712163.92   9.86 6.70 0.00 0.00  
Maximum of Months 994884.68 3289953.98   13.12 7.88 34.33 183171.99  



Table of Contents

Report: CondLoopDemandReportMonthly

For: COOLSYS1_DEMAND

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 159967.97 3193301.15 19-JAN-06:03 14.56 7.93 0.00 0.00 01-JAN-00:05
February 251897.80 3482738.19 28-FEB-06:02 14.36 7.99 0.00 0.00 01-FEB-00:10
March 283276.52 4125445.37 07-MAR-06:02 14.44 7.58 0.00 0.00 01-MAR-00:10
April 476826.81 4130577.91 29-APR-05:02 14.77 7.57 0.00 0.00 01-APR-00:10
May 748842.17 4362661.83 10-MAY-05:02 14.76 7.54 0.00 0.00 01-MAY-00:05
June 785753.50 4230109.91 08-JUN-05:02 14.51 7.62 0.00 0.00 01-JUN-00:10
July 774027.55 4281972.98 31-JUL-05:02 14.61 7.49 0.00 0.00 01-JUL-00:03
August 813379.75 4341884.70 07-AUG-05:02 14.72 7.22 0.00 0.00 01-AUG-00:03
September 750530.31 4710341.63 05-SEP-03:02 15.50 7.34 0.00 0.00 01-SEP-00:05
October 633304.96 4343121.36 11-OCT-05:02 14.72 7.67 0.00 0.00 01-OCT-00:10
November 372531.03 4193746.16 02-NOV-05:02 14.45 7.62 0.00 0.00 01-NOV-00:10
December 248841.98 4262561.13 15-DEC-06:02 14.69 7.62 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 526392.48         0.00    
Minimum of Months 159967.97 3193301.15   14.36 7.22 0.00 0.00  
Maximum of Months 813379.75 4710341.63   15.50 7.99 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SINGLE WATER PLANT LOOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 244437.57 744419.59 02-JAN-15:00 33.28 28.91 0.00 0.00 01-JAN-00:05
February 450640.28 1035948.96 02-FEB-13:10 39.02 31.52 0.00 0.00 01-FEB-00:10
March 687278.79 1336119.03 30-MAR-13:00 44.86 34.17 0.00 0.00 01-MAR-00:10
April 1069279.24 1758685.33 28-APR-15:00 52.99 39.43 0.00 0.00 01-APR-00:10
May 737325.01 1101891.63 18-MAY-16:00 40.30 35.45 0.00 0.00 01-MAY-00:05
June 999142.31 1425474.56 14-JUN-14:00 46.59 38.58 0.00 0.00 01-JUN-00:10
July 1243310.74 1739962.02 21-JUL-16:00 52.63 41.25 0.00 0.00 01-JUL-00:03
August 1431570.18 1911302.02 30-AUG-16:10 55.89 42.26 0.00 0.00 01-AUG-00:03
September 705062.85 1264988.73 09-SEP-17:00 43.48 38.58 0.00 0.00 01-SEP-00:05
October 819014.29 1376855.99 05-OCT-15:00 45.65 37.60 0.00 0.00 01-OCT-00:10
November 757228.59 1382792.26 02-NOV-13:00 45.76 34.87 0.00 0.00 01-NOV-00:10
December 832637.59 1575232.05 13-DEC-15:00 49.47 36.04 0.00 0.00 01-DEC-00:10
                 
Annual Sum or Average 833978.40         0.00    
Minimum of Months 244437.57 744419.59   33.28 28.91 0.00 0.00  
Maximum of Months 1431570.18 1911302.02   55.89 42.26 0.00 0.00  



Table of Contents

Report: CondLoopDemandReportMonthly

For: SWHSYS1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 0.00 0.00 01-JAN-00:05 57.91 57.91 12872.40 42424.01 25-JAN-12:40
February 0.00 0.00 01-FEB-00:10 56.87 56.87 12848.26 42362.61 01-FEB-12:30
March 0.00 0.00 01-MAR-00:10 56.87 56.87 13094.26 41421.46 01-MAR-12:50
April 0.00 0.00 01-APR-00:10 57.31 57.31 11687.11 39162.13 03-APR-12:00
May 0.00 0.00 01-MAY-00:05 57.55 57.55 11287.80 36776.47 01-MAY-11:20
June 0.00 0.00 01-JUN-00:10 57.44 57.44 10898.83 34320.97 01-JUN-11:40
July 0.00 0.00 01-JUL-00:03 57.23 57.23 9869.12 32682.26 03-JUL-11:40
August 0.00 0.00 01-AUG-00:03 56.89 56.89 10767.89 33345.93 31-AUG-11:40
September 0.00 0.00 01-SEP-00:05 57.31 57.31 10638.63 35304.02 29-SEP-11:50
October 0.00 0.00 01-OCT-00:10 57.36 57.36 11291.04 38011.11 31-OCT-11:40
November 0.00 0.00 01-NOV-00:10 57.58 57.58 12157.86 40419.46 30-NOV-12:30
December 0.00 0.00 01-DEC-00:10 57.01 57.01 12325.05 41967.03 29-DEC-12:50
                 
Annual Sum or Average 0.00         11638.24    
Minimum of Months 0.00 0.00   56.87 56.87 9869.12 32682.26  
Maximum of Months 0.00 0.00   57.91 57.91 13094.26 42424.01  



Table of Contents

Report: CondLoopDemandReportMonthly

For: TOWERWATERSYS

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

PLANT SUPPLY SIDE COOLING DEMAND RATE [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] PLANT SUPPLY SIDE HEATING DEMAND RATE [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP}
January 180137.24 3674544.78 19-JAN-12:00 26.88 23.82 1943.88 190590.83 21-JAN-11:30
February 272230.40 3580410.81 24-FEB-13:20 26.73 23.55 1130.59 181561.35 17-FEB-07:50
March 334616.96 4098203.56 07-MAR-11:30 27.54 24.41 1586.49 188773.57 09-MAR-11:00
April 664928.68 5615019.25 28-APR-16:00 29.93 26.99 793.97 132029.93 10-APR-08:20
May 1864149.01 6067390.26 24-MAY-05:05 30.64 26.49 0.00 0.00 01-MAY-00:05
June 2175860.82 6239731.25 28-JUN-14:00 30.91 27.87 0.00 0.00 01-JUN-00:10
July 2554553.19 6519640.34 12-JUL-10:10 31.35 28.15 0.00 0.00 01-JUL-00:03
August 2467901.48 6453960.77 14-AUG-11:00 31.25 28.09 0.44 3948.61 20-AUG-04:40
September 1987138.32 6451798.07 18-SEP-14:00 31.24 28.09 0.00 0.00 01-SEP-00:05
October 1497200.70 6692347.80 24-OCT-13:30 31.62 28.24 334.79 119709.13 27-OCT-17:50
November 590867.10 5428491.22 01-NOV-14:00 29.63 26.58 1535.17 154065.82 22-NOV-09:50
December 350792.14 5083777.27 12-DEC-14:20 29.09 25.85 1759.05 182682.84 20-DEC-15:30
                 
Annual Sum or Average 1251825.12         755.88    
Minimum of Months 180137.24 3580410.81   26.73 23.55 0.00 0.00  
Maximum of Months 2554553.19 6692347.80   31.62 28.24 1943.88 190590.83  



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: GROUNDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: MIDFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: TOPFLOOR_PLENUM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: ZoneTemperatureOscillationReportMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} []
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00  
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 78134443.96 0.00 0.342391E+11 0.592536E+10 0.00 0.00
February 34794737.85 0.00 0.488738E+11 0.620593E+10 0.00 0.00
March 26985485.57 0.00 0.651581E+11 0.839646E+10 0.00 0.00
April 45546390.94 0.00 0.109851E+12 0.102676E+11 0.00 0.00
May 0.00 0.00 0.150401E+12 0.105108E+11 0.00 0.00
June 0.00 0.00 0.162738E+12 0.117660E+11 0.00 0.00
July 0.00 0.00 0.176160E+12 0.125788E+11 0.00 0.00
August 0.00 0.00 0.193773E+12 0.150613E+11 0.00 0.00
September 0.00 0.00 0.149166E+12 0.980537E+10 0.00 0.00
October 240.64 0.00 0.137372E+12 0.101668E+11 0.00 0.00
November 3342.80 0.00 0.805258E+11 0.857445E+10 0.00 0.00
December 39142988.51 0.00 0.590780E+11 0.781333E+10 0.00 0.00
             
Annual Sum or Average 0.224608E+09 0.00 0.136734E+13 0.117072E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.342391E+11 0.592536E+10 0.00 0.00
Maximum of Months 78134443.96 0.00 0.193773E+12 0.150613E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.843129E+10 0.00 0.267454E+12 0.406986E+11 0.00 0.00
February 0.409931E+10 0.00 0.378432E+12 0.404960E+11 0.00 0.00
March 0.383688E+10 0.00 0.479486E+12 0.521199E+11 0.00 0.00
April 0.118713E+09 0.00 0.794848E+12 0.639477E+11 0.00 0.00
May 0.00 0.00 0.135751E+13 0.928688E+11 0.00 0.00
June 0.00 0.00 0.139215E+13 0.956132E+11 0.00 0.00
July 0.00 0.00 0.143176E+13 0.905658E+11 0.00 0.00
August 0.00 0.00 0.148707E+13 0.985827E+11 0.00 0.00
September 0.00 0.00 0.131486E+13 0.797594E+11 0.00 0.00
October 1960.52 0.00 0.113814E+13 0.744310E+11 0.00 0.00
November 47492045.22 0.00 0.606307E+12 0.522700E+11 0.00 0.00
December 0.575025E+10 0.00 0.412523E+12 0.431209E+11 0.00 0.00
             
Annual Sum or Average 0.222839E+11 0.00 0.110606E+14 0.824474E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.267454E+12 0.404960E+11 0.00 0.00
Maximum of Months 0.843129E+10 0.00 0.148707E+13 0.985827E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.394150E+10 0.00 0.257704E+11 0.341808E+10 0.00 0.00
February 0.241973E+10 0.00 0.378887E+11 0.370760E+10 0.00 0.00
March 0.174433E+10 0.00 0.493188E+11 0.467302E+10 0.00 0.00
April 12979430.47 0.00 0.847841E+11 0.627882E+10 0.00 0.00
May 0.00 0.00 0.150982E+12 0.102022E+11 0.00 0.00
June 0.00 0.00 0.157677E+12 0.108801E+11 0.00 0.00
July 0.00 0.00 0.162030E+12 0.103120E+11 0.00 0.00
August 0.00 0.00 0.165969E+12 0.109654E+11 0.00 0.00
September 0.00 0.00 0.142064E+12 0.837518E+10 0.00 0.00
October 20566689.82 0.00 0.122309E+12 0.777843E+10 0.00 0.00
November 0.197748E+09 0.00 0.594080E+11 0.461798E+10 0.00 0.00
December 0.257711E+10 0.00 0.397464E+11 0.371020E+10 0.00 0.00
             
Annual Sum or Average 0.109140E+11 0.00 0.119795E+13 0.849189E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.257704E+11 0.341808E+10 0.00 0.00
Maximum of Months 0.394150E+10 0.00 0.165969E+12 0.109654E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.218968E+11 0.151143E+11 0.00 0.00
February 0.00 0.00 0.263542E+11 0.132172E+11 0.00 0.00
March 0.00 0.00 0.354979E+11 0.151784E+11 0.00 0.00
April 0.00 0.00 0.562278E+11 0.138852E+11 0.00 0.00
May 0.00 0.00 0.103677E+12 0.149819E+11 0.00 0.00
June 0.00 0.00 0.108815E+12 0.146433E+11 0.00 0.00
July 0.00 0.00 0.117942E+12 0.147184E+11 0.00 0.00
August 0.00 0.00 0.130714E+12 0.162706E+11 0.00 0.00
September 0.00 0.00 0.110906E+12 0.153983E+11 0.00 0.00
October 0.00 0.00 0.953928E+11 0.158403E+11 0.00 0.00
November 0.00 0.00 0.523303E+11 0.153407E+11 0.00 0.00
December 0.00 0.00 0.342941E+11 0.153907E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.894049E+12 0.179979E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.218968E+11 0.132172E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.130714E+12 0.162706E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.417507E+12 0.181025E+12 0.00 0.19
February 0.00 0.00 0.655626E+12 0.218791E+12 0.00 0.13
March 0.00 0.00 0.103627E+13 0.307805E+12 0.00 0.08
April 0.00 0.00 0.132691E+13 0.382366E+12 0.00 0.02
May 0.00 0.00 0.465550E+12 0.211284E+12 0.00 0.00
June 0.00 0.00 0.769888E+12 0.285338E+12 0.00 0.00
July 0.00 0.00 0.112650E+13 0.378826E+12 0.00 0.00
August 0.00 0.00 0.143361E+13 0.447598E+12 0.00 0.00
September 0.00 0.00 0.453994E+12 0.203575E+12 0.00 0.00
October 0.00 0.00 0.776661E+12 0.277826E+12 0.00 0.02
November 0.00 0.00 0.101872E+13 0.306234E+12 0.00 0.03
December 0.00 0.00 0.133796E+13 0.362163E+12 0.00 0.10
             
Annual Sum or Average 0.00 0.00 0.108192E+14 0.356283E+13 0.00 0.57
Minimum of Months 0.00 0.00 0.417507E+12 0.181025E+12 0.00 0.00
Maximum of Months 0.00 0.00 0.143361E+13 0.447598E+12 0.00 0.19



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.658165E+10 0.275278E+10 0.00 0.00
February 0.00 0.00 0.120621E+11 0.369063E+10 0.00 0.00
March 0.00 0.00 0.198537E+11 0.543394E+10 0.00 0.00
April 0.00 0.00 0.262259E+11 0.703166E+10 0.00 0.00
May 0.00 0.00 0.870458E+10 0.353428E+10 0.00 0.00
June 0.00 0.00 0.150682E+11 0.507061E+10 0.00 0.00
July 0.00 0.00 0.223780E+11 0.693909E+10 0.00 0.00
August 0.00 0.00 0.290556E+11 0.850799E+10 0.00 0.00
September 0.00 0.00 0.843577E+10 0.338926E+10 0.00 0.00
October 0.00 0.00 0.149766E+11 0.487109E+10 0.00 0.00
November 0.00 0.00 0.196834E+11 0.544522E+10 0.00 0.00
December 0.00 0.00 0.260067E+11 0.654672E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.209032E+12 0.632133E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.658165E+10 0.275278E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.290556E+11 0.850799E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.508414E+11 0.239110E+11 0.00 0.00
February 0.00 0.00 0.106059E+12 0.335154E+11 0.00 0.00
March 0.00 0.00 0.182524E+12 0.505897E+11 0.00 0.00
April 0.00 0.00 0.249013E+12 0.668306E+11 0.00 0.00
May 0.00 0.00 0.817882E+11 0.333711E+11 0.00 0.00
June 0.00 0.00 0.143704E+12 0.483064E+11 0.00 0.00
July 0.00 0.00 0.213543E+12 0.661499E+11 0.00 0.00
August 0.00 0.00 0.276068E+12 0.808577E+11 0.00 0.00
September 0.00 0.00 0.780957E+11 0.317356E+11 0.00 0.00
October 0.00 0.00 0.140670E+12 0.459778E+11 0.00 0.00
November 0.00 0.00 0.182102E+12 0.508923E+11 0.00 0.00
December 0.00 0.00 0.238969E+12 0.608825E+11 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.194338E+13 0.593020E+12 0.00 0.00
Minimum of Months 0.00 0.00 0.508414E+11 0.239110E+11 0.00 0.00
Maximum of Months 0.00 0.00 0.276068E+12 0.808577E+11 0.00 0.00



Table of Contents

Report: AirLoopSystemEnergyAndWaterUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM HOT WATER ENERGY [J] AIR SYSTEM STEAM ENERGY [J] AIR SYSTEM CHILLED WATER ENERGY [J] AIR SYSTEM ELECTRICITY ENERGY [J] AIR SYSTEM NATURAL GAS ENERGY [] AIR SYSTEM WATER VOLUME [m3]
January 0.00 0.00 0.379174E+10 0.216407E+10 0.00 0.00
February 0.00 0.00 0.970467E+10 0.321151E+10 0.00 0.00
March 0.00 0.00 0.176362E+11 0.498583E+10 0.00 0.00
April 0.00 0.00 0.247979E+11 0.670508E+10 0.00 0.00
May 0.00 0.00 0.835925E+10 0.340958E+10 0.00 0.00
June 0.00 0.00 0.145662E+11 0.490771E+10 0.00 0.00
July 0.00 0.00 0.215733E+11 0.670160E+10 0.00 0.00
August 0.00 0.00 0.278218E+11 0.817832E+10 0.00 0.00
September 0.00 0.00 0.796071E+10 0.323823E+10 0.00 0.00
October 0.00 0.00 0.140447E+11 0.462999E+10 0.00 0.00
November 0.00 0.00 0.177018E+11 0.503301E+10 0.00 0.00
December 0.00 0.00 0.229863E+11 0.597249E+10 0.00 0.00
             
Annual Sum or Average 0.00 0.00 0.190944E+12 0.591374E+11 0.00 0.00
Minimum of Months 0.00 0.00 0.379174E+10 0.216407E+10 0.00 0.00
Maximum of Months 0.00 0.00 0.278218E+11 0.817832E+10 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.592536E+10 0.342391E+11 78134443.96 0.579760E+09 0.622798E+09 0.00 0.00 0.00
February 0.620593E+10 0.488738E+11 34794737.85 0.227691E+09 0.108677E+10 0.00 0.00 0.00
March 0.839646E+10 0.651581E+11 26985485.57 0.135627E+09 0.200521E+10 0.00 0.00 0.00
April 0.102676E+11 0.109851E+12 45546390.94 0.00 0.550623E+10 0.00 0.00 0.00
May 0.105108E+11 0.150401E+12 0.00 0.00 0.255005E+11 0.00 0.00 0.00
June 0.117660E+11 0.162738E+12 0.00 0.00 0.315630E+11 0.00 0.00 0.00
July 0.125788E+11 0.176160E+12 0.00 0.00 0.353239E+11 0.00 0.00 0.00
August 0.150613E+11 0.193773E+12 0.00 0.00 0.346446E+11 0.00 0.00 0.00
September 0.980537E+10 0.149166E+12 0.00 0.00 0.227554E+11 0.00 0.00 0.00
October 0.101668E+11 0.137372E+12 240.64 0.00 0.198112E+11 0.00 0.00 0.00
November 0.857445E+10 0.805258E+11 3342.80 0.00 0.496281E+10 0.00 0.00 0.00
December 0.781333E+10 0.590780E+11 39142988.51 0.229344E+09 0.259094E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.117072E+12 0.136734E+13 0.224608E+09 0.117242E+10 0.186373E+12 0.00 0.00 0.00
Minimum of Months 0.592536E+10 0.342391E+11 0.00 0.00 0.622798E+09 0.00 0.00 0.00
Maximum of Months 0.150613E+11 0.193773E+12 78134443.96 0.579760E+09 0.353239E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.406986E+11 0.267454E+12 0.843129E+10 0.105883E+11 0.642394E+10 0.00 0.00 0.00
February 0.404960E+11 0.378432E+12 0.409931E+10 0.557734E+10 0.116439E+11 0.00 0.00 0.00
March 0.521199E+11 0.479486E+12 0.383688E+10 0.333129E+10 0.201811E+11 0.00 0.00 0.00
April 0.639477E+11 0.794848E+12 0.118713E+09 0.00 0.535308E+11 0.00 0.00 0.00
May 0.928688E+11 0.135751E+13 0.00 0.00 0.255419E+12 0.00 0.00 0.00
June 0.956132E+11 0.139215E+13 0.00 0.00 0.316946E+12 0.00 0.00 0.00
July 0.905658E+11 0.143176E+13 0.00 0.00 0.354932E+12 0.00 0.00 0.00
August 0.985827E+11 0.148707E+13 0.00 0.00 0.344565E+12 0.00 0.00 0.00
September 0.797594E+11 0.131486E+13 0.00 0.00 0.229375E+12 0.00 0.00 0.00
October 0.744310E+11 0.113814E+13 1960.52 0.00 0.199853E+12 0.00 0.00 0.00
November 0.522700E+11 0.606307E+12 47492045.22 47338405.56 0.500533E+11 0.00 0.00 0.00
December 0.431209E+11 0.412523E+12 0.575025E+10 0.683158E+10 0.261556E+11 0.00 0.00 0.00
                 
Annual Sum or Average 0.824474E+12 0.110606E+14 0.222839E+11 0.263759E+11 0.186908E+13 0.00 0.00 0.00
Minimum of Months 0.404960E+11 0.267454E+12 0.00 0.00 0.642394E+10 0.00 0.00 0.00
Maximum of Months 0.985827E+11 0.148707E+13 0.843129E+10 0.105883E+11 0.354932E+12 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.341808E+10 0.257704E+11 0.394150E+10 0.212490E+10 0.154330E+09 0.00 0.00 0.00
February 0.370760E+10 0.378887E+11 0.241973E+10 0.108240E+10 0.516296E+09 0.00 0.00 0.00
March 0.467302E+10 0.493188E+11 0.174433E+10 0.720139E+09 0.151549E+10 0.00 0.00 0.00
April 0.627882E+10 0.847841E+11 12979430.47 517937.45 0.466142E+10 0.00 0.00 0.00
May 0.102022E+11 0.150982E+12 0.00 0.00 0.245808E+11 0.00 0.00 0.00
June 0.108801E+11 0.157677E+12 0.00 0.00 0.304655E+11 0.00 0.00 0.00
July 0.103120E+11 0.162030E+12 0.00 0.00 0.340201E+11 0.00 0.00 0.00
August 0.109654E+11 0.165969E+12 0.00 0.00 0.332634E+11 0.00 0.00 0.00
September 0.837518E+10 0.142064E+12 0.00 0.00 0.220680E+11 0.00 0.00 0.00
October 0.777843E+10 0.122309E+12 20566689.82 2977314.11 0.190876E+11 0.00 0.00 0.00
November 0.461798E+10 0.594080E+11 0.197748E+09 45416986.13 0.473784E+10 0.00 0.00 0.00
December 0.371020E+10 0.397464E+11 0.257711E+10 0.140474E+10 0.219213E+10 0.00 0.00 0.00
                 
Annual Sum or Average 0.849189E+11 0.119795E+13 0.109140E+11 0.538108E+10 0.177263E+12 0.00 0.00 0.00
Minimum of Months 0.341808E+10 0.257704E+11 0.00 0.00 0.154330E+09 0.00 0.00 0.00
Maximum of Months 0.109654E+11 0.165969E+12 0.394150E+10 0.212490E+10 0.340201E+11 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.151143E+11 0.218968E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132172E+11 0.263542E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.151784E+11 0.354979E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138852E+11 0.562278E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149819E+11 0.103677E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.146433E+11 0.108815E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147184E+11 0.117942E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.162706E+11 0.130714E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.153983E+11 0.110906E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.158403E+11 0.953928E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.153407E+11 0.523303E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153907E+11 0.342941E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.179979E+12 0.894049E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132172E+11 0.218968E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162706E+11 0.130714E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.947342E+11 0.331718E+12 0.00 0.00 0.00 0.500317E+09 0.00 0.00
February 0.855664E+11 0.522753E+12 0.00 0.00 0.00 0.349540E+09 0.00 0.00
March 0.947342E+11 0.823430E+12 0.00 0.00 0.00 0.226732E+09 0.00 0.00
April 0.916783E+11 0.103628E+13 0.00 0.00 0.00 62670613.80 0.00 0.00
May 0.947342E+11 0.349000E+12 0.00 0.00 0.00 0.00 0.00 0.00
June 0.916783E+11 0.576229E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.947342E+11 0.842408E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.947342E+11 0.108075E+13 0.00 0.00 0.00 0.00 0.00 0.00
September 0.916783E+11 0.342098E+12 0.00 0.00 0.00 0.00 0.00 0.00
October 0.947342E+11 0.593623E+12 0.00 0.00 0.00 53447703.09 0.00 0.00
November 0.916783E+11 0.804250E+12 0.00 0.00 0.00 80554809.11 0.00 0.00
December 0.947342E+11 0.107079E+13 0.00 0.00 0.00 0.256356E+09 0.00 0.00
                 
Annual Sum or Average 0.111542E+13 0.837333E+13 0.00 0.00 0.00 0.152962E+10 0.00 0.00
Minimum of Months 0.855664E+11 0.331718E+12 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.947342E+11 0.108075E+13 0.00 0.00 0.00 0.500317E+09 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.139709E+10 0.522595E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.126188E+10 0.963334E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139709E+10 0.158168E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135202E+10 0.205463E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139709E+10 0.656738E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.135202E+10 0.113496E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139709E+10 0.168360E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139709E+10 0.219447E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135202E+10 0.639852E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139709E+10 0.115026E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.135202E+10 0.155902E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139709E+10 0.208571E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.164496E+11 0.162269E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126188E+10 0.522595E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139709E+10 0.219447E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.132773E+11 0.402077E+11 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119924E+11 0.845363E+11 0.00 0.00 0.00 0.00 0.00 0.00
March 0.132773E+11 0.145211E+12 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128490E+11 0.195032E+12 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132773E+11 0.616944E+11 0.00 0.00 0.00 0.00 0.00 0.00
June 0.128490E+11 0.108247E+12 0.00 0.00 0.00 0.00 0.00 0.00
July 0.132773E+11 0.160671E+12 0.00 0.00 0.00 0.00 0.00 0.00
August 0.132773E+11 0.208488E+12 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128490E+11 0.592091E+11 0.00 0.00 0.00 0.00 0.00 0.00
October 0.132773E+11 0.107970E+12 0.00 0.00 0.00 0.00 0.00 0.00
November 0.128490E+11 0.144059E+12 0.00 0.00 0.00 0.00 0.00 0.00
December 0.132773E+11 0.191363E+12 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.156330E+12 0.150669E+13 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119924E+11 0.402077E+11 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132773E+11 0.208488E+12 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentLoadsMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN AIR HEATING ENERGY [J] AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J]
January 0.135421E+10 0.298188E+10 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122315E+10 0.771631E+10 0.00 0.00 0.00 0.00 0.00 0.00
March 0.135421E+10 0.140046E+11 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131052E+10 0.194033E+11 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135421E+10 0.630387E+10 0.00 0.00 0.00 0.00 0.00 0.00
June 0.131052E+10 0.109690E+11 0.00 0.00 0.00 0.00 0.00 0.00
July 0.135421E+10 0.162259E+11 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135421E+10 0.209977E+11 0.00 0.00 0.00 0.00 0.00 0.00
September 0.131052E+10 0.603300E+10 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135421E+10 0.107689E+11 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131052E+10 0.139793E+11 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135421E+10 0.183680E+11 0.00 0.00 0.00 0.00 0.00 0.00
                 
Annual Sum or Average 0.159447E+11 0.147752E+12 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122315E+10 0.298188E+10 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135421E+10 0.209977E+11 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_BOT WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.592536E+10 78134443.96 0.342391E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.620593E+10 34794737.85 0.488738E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.839646E+10 26985485.57 0.651581E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.102676E+11 45546390.94 0.109851E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.105108E+11 0.00 0.150401E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.117660E+11 0.00 0.162738E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.125788E+11 0.00 0.176160E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.150613E+11 0.00 0.193773E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.980537E+10 0.00 0.149166E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.101668E+11 240.64 0.137372E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.857445E+10 3342.80 0.805258E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.781333E+10 39142988.51 0.590780E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.117072E+12 0.224608E+09 0.136734E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.592536E+10 0.00 0.342391E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.150613E+11 78134443.96 0.193773E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_MID WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.406986E+11 0.843129E+10 0.267454E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.404960E+11 0.409931E+10 0.378432E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.521199E+11 0.383688E+10 0.479486E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.639477E+11 0.118713E+09 0.794848E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.928688E+11 0.00 0.135751E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.956132E+11 0.00 0.139215E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.905658E+11 0.00 0.143176E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.985827E+11 0.00 0.148707E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.797594E+11 0.00 0.131486E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.744310E+11 1960.52 0.113814E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.522700E+11 47492045.22 0.606307E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.431209E+11 0.575025E+10 0.412523E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.824474E+12 0.222839E+11 0.110606E+14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.404960E+11 0.00 0.267454E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.985827E+11 0.843129E+10 0.148707E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: VAV_TOP WITH REHEAT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.341808E+10 0.394150E+10 0.257704E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.370760E+10 0.241973E+10 0.378887E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.467302E+10 0.174433E+10 0.493188E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.627882E+10 12979430.47 0.847841E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.102022E+11 0.00 0.150982E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.108801E+11 0.00 0.157677E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.103120E+11 0.00 0.162030E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.109654E+11 0.00 0.165969E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.837518E+10 0.00 0.142064E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.777843E+10 20566689.82 0.122309E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.461798E+10 0.197748E+09 0.594080E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.371020E+10 0.257711E+10 0.397464E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.849189E+11 0.109140E+11 0.119795E+13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.341808E+10 0.00 0.257704E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.109654E+11 0.394150E+10 0.165969E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: CAV_BAS

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.151143E+11 0.00 0.218968E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.132172E+11 0.00 0.263542E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.151784E+11 0.00 0.354979E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.138852E+11 0.00 0.562278E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.149819E+11 0.00 0.103677E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.146433E+11 0.00 0.108815E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.147184E+11 0.00 0.117942E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.162706E+11 0.00 0.130714E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.153983E+11 0.00 0.110906E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.158403E+11 0.00 0.953928E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.153407E+11 0.00 0.523303E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.153907E+11 0.00 0.342941E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.179979E+12 0.00 0.894049E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.132172E+11 0.00 0.218968E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.162706E+11 0.00 0.130714E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.947342E+11 0.00 0.417507E+12 0.00 0.857884E+11 0.00 0.00 0.00 0.502569E+09 0.00 0.00 0.00
February 0.855664E+11 0.00 0.655626E+12 0.00 0.132873E+12 0.00 0.00 0.00 0.351114E+09 0.00 0.00 0.00
March 0.947342E+11 0.00 0.103627E+13 0.00 0.212843E+12 0.00 0.00 0.00 0.227752E+09 0.00 0.00 0.00
April 0.916783E+11 0.00 0.132691E+13 0.00 0.290624E+12 0.00 0.00 0.00 62952719.63 0.00 0.00 0.00
May 0.947342E+11 0.00 0.465550E+12 0.00 0.116550E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.916783E+11 0.00 0.769888E+12 0.00 0.193659E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.947342E+11 0.00 0.112650E+13 0.00 0.284092E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.947342E+11 0.00 0.143361E+13 0.00 0.352864E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.916783E+11 0.00 0.453994E+12 0.00 0.111896E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.947342E+11 0.00 0.776661E+12 0.00 0.183038E+12 0.00 0.00 0.00 53688292.87 0.00 0.00 0.00
November 0.916783E+11 0.00 0.101872E+13 0.00 0.214475E+12 0.00 0.00 0.00 80917418.96 0.00 0.00 0.00
December 0.947342E+11 0.00 0.133796E+13 0.00 0.267171E+12 0.00 0.00 0.00 0.257510E+09 0.00 0.00 0.00
                         
Annual Sum or Average 0.111542E+13 0.00 0.108192E+14 0.00 0.244587E+13 0.00 0.00 0.00 0.153650E+10 0.00 0.00 0.00
Minimum of Months 0.855664E+11 0.00 0.417507E+12 0.00 0.857884E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.947342E+11 0.00 0.143361E+13 0.00 0.352864E+12 0.00 0.00 0.00 0.502569E+09 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER BOT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.139709E+10 0.00 0.658165E+10 0.00 0.135569E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.126188E+10 0.00 0.120621E+11 0.00 0.242875E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.139709E+10 0.00 0.198537E+11 0.00 0.403685E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.135202E+10 0.00 0.262259E+11 0.00 0.567964E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.139709E+10 0.00 0.870458E+10 0.00 0.213719E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.135202E+10 0.00 0.150682E+11 0.00 0.371859E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.139709E+10 0.00 0.223780E+11 0.00 0.554200E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.139709E+10 0.00 0.290556E+11 0.00 0.711090E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.135202E+10 0.00 0.843577E+10 0.00 0.203724E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.139709E+10 0.00 0.149766E+11 0.00 0.347400E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.135202E+10 0.00 0.196834E+11 0.00 0.409321E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.139709E+10 0.00 0.260067E+11 0.00 0.514964E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.164496E+11 0.00 0.209032E+12 0.00 0.467637E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.126188E+10 0.00 0.658165E+10 0.00 0.135569E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.139709E+10 0.00 0.290556E+11 0.00 0.711090E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.132773E+11 0.00 0.508414E+11 0.00 0.106336E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.119924E+11 0.00 0.106059E+12 0.00 0.215230E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.132773E+11 0.00 0.182524E+12 0.00 0.373124E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.128490E+11 0.00 0.249013E+12 0.00 0.539815E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.132773E+11 0.00 0.817882E+11 0.00 0.200938E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.128490E+11 0.00 0.143704E+12 0.00 0.354574E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.132773E+11 0.00 0.213543E+12 0.00 0.528726E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.132773E+11 0.00 0.276068E+12 0.00 0.675803E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.128490E+11 0.00 0.780957E+11 0.00 0.188865E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.132773E+11 0.00 0.140670E+12 0.00 0.327005E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.128490E+11 0.00 0.182102E+12 0.00 0.380433E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.132773E+11 0.00 0.238969E+12 0.00 0.476051E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.156330E+12 0.00 0.194338E+13 0.00 0.436690E+12 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.119924E+11 0.00 0.508414E+11 0.00 0.106336E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.132773E+11 0.00 0.276068E+12 0.00 0.675803E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: AirLoopSystemComponentEnergyUseMonthly

For: AIRLOOP DATACENTER TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

AIR SYSTEM FAN ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] AIR SYSTEM HEATING COIL STEAM ENERGY [J] AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J]
January 0.135421E+10 0.00 0.379174E+10 0.00 0.809863E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
February 0.122315E+10 0.00 0.970467E+10 0.00 0.198835E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
March 0.135421E+10 0.00 0.176362E+11 0.00 0.363163E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
April 0.131052E+10 0.00 0.247979E+11 0.00 0.539456E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
May 0.135421E+10 0.00 0.835925E+10 0.00 0.205537E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
June 0.131052E+10 0.00 0.145662E+11 0.00 0.359719E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
July 0.135421E+10 0.00 0.215733E+11 0.00 0.534739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
August 0.135421E+10 0.00 0.278218E+11 0.00 0.682412E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
September 0.131052E+10 0.00 0.796071E+10 0.00 0.192771E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
October 0.135421E+10 0.00 0.140447E+11 0.00 0.327579E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
November 0.131052E+10 0.00 0.177018E+11 0.00 0.372249E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
December 0.135421E+10 0.00 0.229863E+11 0.00 0.461828E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Annual Sum or Average 0.159447E+11 0.00 0.190944E+12 0.00 0.431927E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Minimum of Months 0.122315E+10 0.00 0.379174E+10 0.00 0.809863E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Maximum of Months 0.135421E+10 0.00 0.278218E+11 0.00 0.682412E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: BASEMENT

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.294843E+09 0.156221E+10 0.00 0.102668E+09 0.00 0.00 0.566564E+11 0.00 0.98
February 0.225278E+09 0.158565E+10 0.00 80431359.77 3899243.67 0.00 0.429519E+11 0.00 1.07
March 0.140611E+09 0.323684E+10 0.00 85931506.76 7394895.87 0.00 0.458338E+11 0.00 1.08
April 0.139339E+09 0.568647E+10 0.00 57897958.13 73823185.45 0.00 0.209665E+11 0.00 0.94
May 2177251.66 0.263903E+11 0.00 1477259.60 0.151749E+09 0.00 50393268.98 0.00 0.34
June 3262071.92 0.319195E+11 0.00 2272378.28 0.210620E+09 0.00 0.151259E+09 0.00 0.36
July 0.00 0.387442E+11 0.00 0.00 0.409581E+09 0.00 0.00 0.00 0.31
August 0.00 0.396452E+11 0.00 155258.92 0.234963E+09 0.00 11290501.41 0.00 0.34
September 1371945.20 0.294477E+11 0.00 1564247.73 0.294490E+09 0.00 0.136254E+09 0.00 0.34
October 0.130875E+09 0.222595E+11 0.00 39048133.73 0.231871E+09 0.00 0.125914E+11 0.00 0.68
November 0.241434E+09 0.663252E+10 0.00 93823836.95 8365468.69 0.00 0.373023E+11 0.00 1.14
December 0.326302E+09 0.422008E+10 0.00 97015428.70 11211159.27 0.00 0.507271E+11 0.00 0.96
                   
Annual Sum or Average 0.150549E+10 0.211330E+12 0.00 0.562285E+09 0.163797E+10 0.00 0.267379E+12 0.00 0.71
Minimum of Months 0.00 0.156221E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.326302E+09 0.396452E+11 0.00 0.102668E+09 0.409581E+09 0.00 0.566564E+11 0.00 1.14



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_BOTTOM

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.216531E+10 0.129778E+10 0.00 65802497.98 0.00 0.00 0.365343E+11 0.00 0.63
February 0.223284E+10 0.139639E+10 0.00 59722707.64 10060613.65 0.00 0.262459E+11 0.00 0.69
March 0.259117E+10 0.247915E+10 0.00 68360700.38 46531758.95 0.00 0.328359E+11 0.00 0.76
April 0.521991E+10 0.404203E+10 0.00 38832363.57 41815637.12 0.00 0.117190E+11 0.00 0.69
May 0.00 0.106809E+11 0.00 0.00 0.109595E+09 0.00 0.00 0.00 0.26
June 25371720.04 0.113848E+11 0.00 129713.15 0.115919E+09 0.00 2255272.27 0.00 0.26
July 0.00 0.135739E+11 0.00 0.00 0.212657E+09 0.00 0.00 0.00 0.24
August 58250652.66 0.140694E+11 0.00 0.00 0.139004E+09 0.00 0.00 0.00 0.27
September 0.00 0.131766E+11 0.00 0.00 0.230498E+09 0.00 0.00 0.00 0.26
October 0.110263E+10 0.860759E+10 0.00 22515527.59 0.145309E+09 0.00 0.790051E+10 0.00 0.43
November 0.366004E+10 0.368868E+10 0.00 62902178.60 32021022.64 0.00 0.242554E+11 0.00 0.78
December 0.417318E+10 0.312440E+10 0.00 66988301.28 45722884.09 0.00 0.350252E+11 0.00 0.68
                   
Annual Sum or Average 0.212287E+11 0.875218E+11 0.00 0.385254E+09 0.112914E+10 0.00 0.174519E+12 0.00 0.49
Minimum of Months 0.00 0.129778E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Maximum of Months 0.521991E+10 0.140694E+11 0.00 68360700.38 0.230498E+09 0.00 0.365343E+11 0.00 0.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_MID

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.643631E+11 0.120606E+11 0.00 0.359167E+09 0.00 0.00 0.224751E+12 0.00 0.50
February 0.350357E+11 0.128570E+11 0.00 0.341813E+09 96467075.04 0.00 0.168170E+12 0.00 0.53
March 0.265324E+11 0.226701E+11 0.00 0.430078E+09 0.748571E+09 0.00 0.223812E+12 0.00 0.57
April 0.137313E+11 0.381975E+11 0.00 0.313727E+09 0.415253E+09 0.00 0.907754E+11 0.00 0.51
May 0.00 0.105561E+12 0.00 0.00 0.109275E+10 0.00 0.00 0.00 0.26
June 0.163701E+09 0.112591E+12 0.00 4348758.31 0.115859E+10 0.00 46491242.35 0.00 0.27
July 0.00 0.133000E+12 0.00 0.00 0.213051E+10 0.00 0.00 0.00 0.24
August 0.00 0.136241E+12 0.00 0.00 0.128488E+10 0.00 0.00 0.00 0.27
September 0.00 0.129016E+12 0.00 0.00 0.223000E+10 0.00 0.00 0.00 0.26
October 0.786834E+10 0.846052E+11 0.00 0.167964E+09 0.145199E+10 0.00 0.615518E+11 0.00 0.38
November 0.212389E+11 0.356595E+11 0.00 0.401447E+09 0.326357E+09 0.00 0.167630E+12 0.00 0.58
December 0.452938E+11 0.290139E+11 0.00 0.342754E+09 0.979951E+09 0.00 0.199784E+12 0.00 0.47
                   
Annual Sum or Average 0.214227E+12 0.851473E+12 0.00 0.236130E+10 0.119153E+11 0.00 0.113652E+13 0.00 0.40
Minimum of Months 0.00 0.120606E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.24
Maximum of Months 0.643631E+11 0.136241E+12 0.00 0.430078E+09 0.223000E+10 0.00 0.224751E+12 0.00 0.58



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: CORE_TOP

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.125170E+11 0.125632E+10 0.00 13057530.60 52426210.54 31285411.96 0.951765E+10 0.00 0.43
February 0.721584E+10 0.131532E+10 0.00 17297986.31 33920142.90 72838448.51 0.901699E+10 0.00 0.47
March 0.637784E+10 0.236849E+10 0.00 25172792.99 46944772.37 9565311.94 0.137725E+11 0.00 0.51
April 0.172190E+10 0.378956E+10 0.00 24650542.65 45079647.12 0.00 0.726650E+10 0.00 0.48
May 0.00 0.103987E+11 0.00 0.00 0.110753E+09 0.00 0.00 0.00 0.26
June 4874384.35 0.110911E+11 0.00 333223.49 0.111340E+09 0.00 2531420.13 0.00 0.26
July 0.00 0.131946E+11 0.00 0.00 0.264556E+09 0.00 0.00 0.00 0.24
August 0.00 0.133644E+11 0.00 0.00 0.171705E+09 0.00 0.00 0.00 0.27
September 0.00 0.127175E+11 0.00 0.00 0.226776E+09 0.00 0.00 0.00 0.26
October 0.114616E+10 0.815973E+10 0.00 13491908.54 0.142337E+09 0.00 0.465009E+10 0.00 0.37
November 0.509633E+10 0.339497E+10 0.00 24174547.54 71533771.49 0.00 0.103237E+11 0.00 0.52
December 0.100787E+11 0.287028E+10 0.00 12397629.62 66852893.03 1314971.86 0.800285E+10 0.00 0.41
                   
Annual Sum or Average 0.441586E+11 0.839209E+11 0.00 0.130576E+09 0.134422E+10 0.115004E+09 0.625528E+11 0.00 0.37
Minimum of Months 0.00 0.125632E+10 0.00 0.00 33920142.90 0.00 0.00 0.00 0.24
Maximum of Months 0.125170E+11 0.133644E+11 0.00 25172792.99 0.264556E+09 72838448.51 0.137725E+11 0.00 0.52



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.231288E+10 0.159733E+09 0.00 1500153.10 0.00 0.00 0.105398E+10 0.00 0.46
February 0.142479E+10 0.182227E+09 0.00 2538188.81 1262470.80 0.00 0.116795E+10 0.00 0.54
March 0.136886E+10 0.352986E+09 0.00 3588273.40 5839105.74 0.00 0.181768E+10 0.00 0.61
April 0.808924E+09 0.623594E+09 0.00 3602656.09 5247296.30 0.00 0.103732E+10 0.00 0.68
May 0.00 0.196842E+10 0.00 0.00 13752734.94 0.00 0.00 0.00 0.38
June 3237466.89 0.227811E+10 0.00 3117.28 14546208.71 0.00 79166.71 0.00 0.42
July 0.00 0.265511E+10 0.00 0.00 26685600.88 0.00 0.00 0.00 0.37
August 7309668.24 0.256170E+10 0.00 0.00 17443166.60 0.00 0.00 0.00 0.39
September 0.00 0.218726E+10 0.00 0.00 28924440.03 0.00 0.00 0.00 0.34
October 0.279130E+09 0.144981E+10 0.00 1885933.16 18234339.70 0.00 0.669477E+09 0.00 0.47
November 0.984686E+09 0.509907E+09 0.00 4081382.28 4018204.80 0.00 0.163106E+10 0.00 0.64
December 0.187843E+10 0.403760E+09 0.00 2298667.85 5737602.90 0.00 0.135277E+10 0.00 0.50
                   
Annual Sum or Average 0.906823E+10 0.153326E+11 0.00 19498371.99 0.141691E+09 0.00 0.873032E+10 0.00 0.48
Minimum of Months 0.00 0.159733E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.34
Maximum of Months 0.231288E+10 0.265511E+10 0.00 4081382.28 28924440.03 0.00 0.181768E+10 0.00 0.68



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.130643E+10 0.120080E+09 0.00 2294894.24 790885.51 0.00 0.161425E+10 0.00 0.60
February 0.986404E+09 0.140503E+09 0.00 2601165.82 989750.02 0.00 0.126597E+10 0.00 0.71
March 0.107627E+10 0.269656E+09 0.00 3550459.95 6957834.22 0.00 0.176028E+10 0.00 0.84
April 0.679854E+09 0.478346E+09 0.00 2973903.54 5004246.48 0.00 0.981182E+09 0.00 0.88
May 0.00 0.156300E+10 0.00 0.00 10781849.14 0.00 0.00 0.00 0.48
June 2602613.47 0.172568E+10 0.00 0.00 11403915.56 0.00 0.00 0.00 0.49
July 0.00 0.197123E+10 0.00 0.00 20920938.58 0.00 0.00 0.00 0.43
August 5730623.08 0.178475E+10 0.00 0.00 13675068.39 0.00 0.00 0.00 0.42
September 0.00 0.163506E+10 0.00 0.00 22676140.44 0.00 0.00 0.00 0.40
October 0.219604E+09 0.110663E+10 0.00 1541298.30 14295331.13 0.00 0.543583E+09 0.00 0.57
November 0.839862E+09 0.362736E+09 0.00 3341739.08 3150186.36 0.00 0.141157E+10 0.00 0.80
December 0.157405E+10 0.246938E+09 0.00 1930139.32 7464066.22 0.00 0.110562E+10 0.00 0.61
                   
Annual Sum or Average 0.669080E+10 0.114046E+11 0.00 18233600.24 0.118110E+09 0.00 0.868247E+10 0.00 0.60
Minimum of Months 0.00 0.120080E+09 0.00 0.00 790885.51 0.00 0.00 0.00 0.40
Maximum of Months 0.157405E+10 0.197123E+10 0.00 3550459.95 22676140.44 0.00 0.176028E+10 0.00 0.88



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.110108E+10 0.271342E+09 0.00 10579293.86 0.00 0.00 0.553334E+10 0.00 0.94
February 0.816444E+09 0.358026E+09 0.00 7528306.78 1264680.74 0.00 0.348807E+10 0.00 0.94
March 0.113674E+10 0.484761E+09 0.00 6574725.11 5849327.02 0.00 0.310946E+10 0.00 0.88
April 0.793591E+09 0.735354E+09 0.00 4380486.13 5256481.63 0.00 0.123164E+10 0.00 0.79
May 0.00 0.199545E+10 0.00 0.00 13776808.93 0.00 0.00 0.00 0.39
June 3243134.04 0.219353E+10 0.00 2535.00 14571671.66 0.00 79893.02 0.00 0.40
July 0.00 0.262142E+10 0.00 0.00 26732313.69 0.00 0.00 0.00 0.37
August 7322463.72 0.277065E+10 0.00 0.00 17473700.65 0.00 0.00 0.00 0.42
September 0.00 0.265075E+10 0.00 0.00 28975071.90 0.00 0.00 0.00 0.42
October 0.194038E+09 0.210207E+10 0.00 3541094.53 15394254.57 0.00 0.110209E+10 0.00 0.70
November 0.540748E+09 0.827477E+09 0.00 11785343.76 4025238.62 0.00 0.410811E+10 0.00 1.17
December 0.110637E+10 0.655597E+09 0.00 10255178.25 5747646.50 0.00 0.477396E+10 0.00 0.98
                   
Annual Sum or Average 0.569958E+10 0.176664E+11 0.00 54646963.42 0.139067E+09 0.00 0.233468E+11 0.00 0.70
Minimum of Months 0.00 0.271342E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.37
Maximum of Months 0.113674E+10 0.277065E+10 0.00 11785343.76 28975071.90 0.00 0.553334E+10 0.00 1.17



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_BOT_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.143801E+10 0.190439E+09 0.00 4124543.78 0.00 0.00 0.261917E+10 0.00 0.88
February 0.595650E+09 0.242414E+09 0.00 6142063.15 194898.94 0.00 0.274294E+10 0.00 1.12
March 0.461888E+09 0.448384E+09 0.00 8861673.49 2962655.49 0.00 0.409334E+10 0.00 1.39
April 0.393986E+09 0.897782E+09 0.00 8886650.00 885290.06 0.00 0.221549E+10 0.00 1.51
May 0.00 0.190415E+10 0.00 0.00 10527361.98 0.00 0.00 0.00 0.58
June 2364817.68 0.230667E+10 0.00 43921.67 4362501.01 0.00 1231916.50 0.00 0.67
July 0.00 0.284310E+10 0.00 0.00 7078995.34 0.00 0.00 0.00 0.62
August 0.00 0.311060E+10 0.00 33128.52 4288592.34 0.00 7482000.07 0.00 0.73
September 0.00 0.221345E+10 0.00 0.00 18432236.30 0.00 0.00 0.00 0.54
October 0.123596E+09 0.161654E+10 0.00 3136373.24 13491183.58 0.00 0.103278E+10 0.00 0.86
November 0.418723E+09 0.648276E+09 0.00 8795392.76 1077982.32 0.00 0.320383E+10 0.00 1.37
December 0.499331E+09 0.567455E+09 0.00 8747097.77 5790281.45 0.00 0.434632E+10 0.00 1.20
                   
Annual Sum or Average 0.393355E+10 0.169893E+11 0.00 48770844.38 69091978.81 0.00 0.202626E+11 0.00 0.95
Minimum of Months 0.00 0.190439E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.54
Maximum of Months 0.143801E+10 0.311060E+10 0.00 8886650.00 18432236.30 0.00 0.434632E+10 0.00 1.51



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.244271E+11 0.121826E+10 0.00 2634565.42 0.190172E+09 0.261359E+10 0.182704E+10 0.00 0.41
February 0.164610E+11 0.151918E+10 0.00 5674478.41 57409523.56 0.107739E+10 0.289950E+10 0.00 0.44
March 0.179516E+11 0.294616E+10 0.00 10193427.74 0.201571E+09 0.894865E+09 0.485219E+10 0.00 0.46
April 0.567048E+10 0.578415E+10 0.00 18969701.91 0.107209E+09 0.00 0.500772E+10 0.00 0.49
May 0.00 0.200696E+11 0.00 0.00 0.137377E+09 0.00 0.00 0.00 0.40
June 22681844.76 0.238103E+11 0.00 131398.87 0.145654E+09 0.00 336693.09 0.00 0.45
July 0.00 0.280017E+11 0.00 0.00 0.267841E+09 0.00 0.00 0.00 0.41
August 0.00 0.265448E+11 0.00 0.00 0.161532E+09 0.00 0.00 0.00 0.42
September 0.00 0.218217E+11 0.00 0.00 0.280348E+09 0.00 0.00 0.00 0.35
October 0.340507E+10 0.145128E+11 0.00 11562497.04 0.202252E+09 0.00 0.382261E+10 0.00 0.42
November 0.138693E+11 0.473630E+10 0.00 13141709.16 87979136.82 0.00 0.485616E+10 0.00 0.48
December 0.220678E+11 0.333689E+10 0.00 1555776.44 0.269435E+09 0.147261E+10 0.837301E+09 0.00 0.39
                   
Annual Sum or Average 0.103875E+12 0.154302E+12 0.00 63863554.99 0.210878E+10 0.605846E+10 0.241029E+11 0.00 0.42
Minimum of Months 0.00 0.121826E+10 0.00 0.00 57409523.56 0.00 0.00 0.00 0.35
Maximum of Months 0.244271E+11 0.280017E+11 0.00 18969701.91 0.280348E+09 0.261359E+10 0.500772E+10 0.00 0.49



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.164809E+11 0.106202E+10 0.00 6468156.74 0.127077E+09 0.123173E+10 0.627036E+10 0.00 0.52
February 0.106112E+11 0.138591E+10 0.00 13002362.46 37731022.94 0.426570E+09 0.669131E+10 0.00 0.61
March 0.116823E+11 0.282017E+10 0.00 24438372.61 0.122450E+09 0.664513E+09 0.103818E+11 0.00 0.73
April 0.370321E+10 0.554139E+10 0.00 26417039.67 78835623.35 0.00 0.825614E+10 0.00 0.78
May 0.00 0.171011E+11 0.00 0.00 0.112534E+09 0.00 0.00 0.00 0.53
June 18580079.77 0.197075E+11 0.00 78552.12 0.119314E+09 0.00 256531.72 0.00 0.57
July 0.00 0.234504E+11 0.00 0.00 0.219405E+09 0.00 0.00 0.00 0.52
August 0.00 0.217413E+11 0.00 0.00 0.132321E+09 0.00 0.00 0.00 0.53
September 0.00 0.177701E+11 0.00 0.00 0.229650E+09 0.00 0.00 0.00 0.45
October 0.238684E+10 0.124266E+11 0.00 12400655.44 0.159549E+09 0.00 0.400712E+10 0.00 0.57
November 0.826977E+10 0.395016E+10 0.00 21421922.74 0.125171E+09 0.00 0.882946E+10 0.00 0.67
December 0.154029E+11 0.248430E+10 0.00 6829877.04 0.297461E+09 0.866863E+09 0.422584E+10 0.00 0.50
                   
Annual Sum or Average 0.685557E+11 0.129441E+12 0.00 0.111057E+09 0.176150E+10 0.318968E+10 0.486623E+11 0.00 0.58
Minimum of Months 0.00 0.106202E+10 0.00 0.00 37731022.94 0.00 0.00 0.00 0.45
Maximum of Months 0.164809E+11 0.234504E+11 0.00 26417039.67 0.297461E+09 0.123173E+10 0.103818E+11 0.00 0.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.104733E+11 0.279461E+10 0.00 92869806.47 11766040.89 0.420832E+09 0.467883E+11 0.00 0.86
February 0.779081E+10 0.381752E+10 0.00 59999146.70 11428227.43 0.148281E+09 0.273381E+11 0.00 0.84
March 0.120168E+11 0.477682E+10 0.00 47985002.35 60605653.49 0.196228E+09 0.208426E+11 0.00 0.74
April 0.415881E+10 0.730639E+10 0.00 31639252.03 94444573.03 0.00 0.866901E+10 0.00 0.63
May 0.00 0.204221E+11 0.00 0.00 0.137460E+09 0.00 0.00 0.00 0.41
June 22695479.32 0.227668E+11 0.00 134634.02 0.145742E+09 0.00 435324.14 0.00 0.43
July 0.00 0.276543E+11 0.00 0.00 0.268002E+09 0.00 0.00 0.00 0.40
August 0.00 0.295268E+11 0.00 0.00 0.161629E+09 0.00 0.00 0.00 0.47
September 0.00 0.277230E+11 0.00 0.00 0.280517E+09 0.00 0.00 0.00 0.45
October 0.197865E+10 0.228185E+11 0.00 29687653.66 0.153116E+09 0.00 0.876520E+10 0.00 0.70
November 0.448823E+10 0.899409E+10 0.00 99412343.07 40564482.03 0.00 0.330591E+11 0.00 1.05
December 0.100799E+11 0.696628E+10 0.00 80513050.23 52393708.17 0.378088E+09 0.347283E+11 0.00 0.84
                   
Annual Sum or Average 0.510092E+11 0.185567E+12 0.00 0.442241E+09 0.141767E+10 0.114343E+10 0.180191E+12 0.00 0.65
Minimum of Months 0.00 0.279461E+10 0.00 0.00 11428227.43 0.00 0.00 0.00 0.40
Maximum of Months 0.120168E+11 0.295268E+11 0.00 99412343.07 0.280517E+09 0.420832E+09 0.467883E+11 0.00 1.05



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_MID_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.178373E+11 0.149405E+10 0.00 12863843.35 33551757.54 0.857749E+09 0.833026E+10 0.00 0.60
February 0.114681E+11 0.189248E+10 0.00 16927847.28 11845718.09 0.334277E+09 0.758687E+10 0.00 0.69
March 0.127285E+11 0.298838E+10 0.00 24603014.10 57016330.04 28674461.69 0.112177E+11 0.00 0.77
April 0.272420E+10 0.643834E+10 0.00 30994991.41 58292097.71 0.00 0.810487E+10 0.00 0.82
May 0.00 0.169574E+11 0.00 0.00 0.105137E+09 0.00 0.00 0.00 0.53
June 17961882.62 0.199024E+11 0.00 162659.71 66593242.83 0.00 2143485.59 0.00 0.59
July 0.00 0.234452E+11 0.00 0.00 0.115717E+09 0.00 0.00 0.00 0.53
August 0.00 0.238818E+11 0.00 0.00 0.103316E+09 0.00 0.00 0.00 0.59
September 0.00 0.192745E+11 0.00 0.00 0.181303E+09 0.00 0.00 0.00 0.49
October 0.232445E+10 0.134803E+11 0.00 14603043.40 0.119882E+09 0.00 0.443897E+10 0.00 0.63
November 0.930447E+10 0.472977E+10 0.00 23341693.03 27778783.60 0.00 0.893131E+10 0.00 0.76
December 0.168796E+11 0.364643E+10 0.00 11257742.70 45764374.36 0.393018E+09 0.539117E+10 0.00 0.60
                   
Annual Sum or Average 0.732844E+11 0.138131E+12 0.00 0.134755E+09 0.926198E+09 0.161372E+10 0.540033E+11 0.00 0.63
Minimum of Months 0.00 0.149405E+10 0.00 0.00 11845718.09 0.00 0.00 0.00 0.49
Maximum of Months 0.178373E+11 0.238818E+11 0.00 30994991.41 0.181303E+09 0.857749E+09 0.112177E+11 0.00 0.82



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_3

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.181438E+10 0.127072E+09 0.00 144631.31 26526125.75 0.711863E+09 74951204.38 0.00 0.40
February 0.128356E+10 0.148065E+09 0.00 321536.23 14238526.74 0.377445E+09 0.177067E+09 0.00 0.42
March 0.165532E+10 0.284195E+09 0.00 661331.58 34445733.16 0.249419E+09 0.277203E+09 0.00 0.45
April 0.538771E+09 0.555928E+09 0.00 1690521.38 19065865.21 0.00 0.442122E+09 0.00 0.48
May 0.00 0.194580E+10 0.00 0.00 13903747.28 0.00 0.00 0.00 0.39
June 795245.20 0.227648E+10 0.00 10156.54 15463323.14 0.00 9473.89 0.00 0.43
July 0.00 0.269503E+10 0.00 0.00 33212112.56 0.00 0.00 0.00 0.39
August 0.00 0.255652E+10 0.00 0.00 21555709.82 0.00 0.00 0.00 0.41
September 0.00 0.213079E+10 0.00 0.00 30527715.48 0.00 0.00 0.00 0.35
October 0.321630E+09 0.138847E+10 0.00 1002537.19 21599212.30 0.00 0.314022E+09 0.00 0.41
November 0.127377E+10 0.417113E+09 1356474.06 913075.98 41489630.51 40517188.25 0.361402E+09 3920.38 0.46
December 0.160482E+10 0.297382E+09 243593.85 70935.59 55467870.07 0.520276E+09 37146241.80 2998.65 0.38
                   
Annual Sum or Average 0.849305E+10 0.148228E+11 1600067.91 4814725.79 0.327496E+09 0.189952E+10 0.168392E+10 6919.03 0.42
Minimum of Months 0.00 0.127072E+09 0.00 0.00 13903747.28 0.00 0.00 0.00 0.35
Maximum of Months 0.181438E+10 0.269503E+10 1356474.06 1690521.38 55467870.07 0.711863E+09 0.442122E+09 3920.38 0.48



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_2

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.165722E+10 0.119597E+09 0.00 219619.20 15517990.67 0.269478E+09 0.194196E+09 0.00 0.52
February 0.101915E+10 0.144142E+09 0.00 874650.92 7403987.45 0.122479E+09 0.419812E+09 0.00 0.59
March 0.996096E+09 0.289362E+09 0.00 2105140.05 18101682.61 0.144527E+09 0.875952E+09 0.00 0.70
April 0.299272E+09 0.545053E+09 0.00 2606021.54 11571305.13 0.00 0.808864E+09 0.00 0.78
May 0.00 0.167669E+10 0.00 0.00 11371044.83 0.00 0.00 0.00 0.52
June 580948.58 0.190585E+10 0.00 6334.10 12878975.03 0.00 75098.70 0.00 0.56
July 0.00 0.228154E+10 0.00 0.00 24277801.69 0.00 0.00 0.00 0.51
August 0.00 0.212401E+10 0.00 0.00 17629128.15 0.00 0.00 0.00 0.53
September 0.00 0.175872E+10 0.00 0.00 30868391.54 0.00 0.00 0.00 0.45
October 0.223878E+09 0.120976E+10 0.00 1185224.22 17036076.09 0.00 0.342906E+09 0.00 0.57
November 0.761467E+09 0.372744E+09 0.00 1658562.05 28774039.54 13045512.51 0.703362E+09 0.00 0.64
December 0.133978E+10 0.236941E+09 0.00 361851.15 45530756.24 0.272763E+09 0.164803E+09 0.00 0.49
                   
Annual Sum or Average 0.629744E+10 0.126644E+11 0.00 9017403.22 0.240961E+09 0.822293E+09 0.350997E+10 0.00 0.57
Minimum of Months 0.00 0.119597E+09 0.00 0.00 7403987.45 0.00 0.00 0.00 0.45
Maximum of Months 0.165722E+10 0.228154E+10 0.00 2606021.54 45530756.24 0.272763E+09 0.875952E+09 0.00 0.78



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_1

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.882401E+09 0.317877E+09 0.00 7558440.09 4500544.85 0.206552E+09 0.350554E+10 0.00 0.75
February 0.723924E+09 0.391791E+09 0.00 4699842.41 1425432.40 0.110905E+09 0.216795E+10 0.00 0.76
March 0.107844E+10 0.472536E+09 0.00 4080860.31 13648290.41 0.143708E+09 0.179425E+10 0.00 0.70
April 0.417017E+09 0.698123E+09 0.00 2990483.47 14890473.91 0.00 0.799304E+09 0.00 0.62
May 0.00 0.197699E+10 0.00 0.00 13892465.47 0.00 0.00 0.00 0.40
June 709768.39 0.217859E+10 0.00 10843.18 15894574.91 0.00 94524.29 0.00 0.41
July 0.00 0.265822E+10 0.00 0.00 33185163.49 0.00 0.00 0.00 0.39
August 0.00 0.283149E+10 0.00 0.00 21538219.03 0.00 0.00 0.00 0.45
September 0.00 0.269012E+10 0.00 0.00 26503740.12 0.00 0.00 0.00 0.44
October 0.198963E+09 0.216302E+10 0.00 2968782.45 14544047.79 0.00 0.750720E+09 0.00 0.68
November 0.454467E+09 0.847354E+09 0.00 8421404.60 8114729.06 149694.76 0.295575E+10 0.00 0.99
December 0.947909E+09 0.659562E+09 0.00 6236878.57 17359928.32 0.131350E+09 0.268231E+10 0.00 0.78
                   
Annual Sum or Average 0.470383E+10 0.178857E+11 0.00 36967535.08 0.185498E+09 0.592664E+09 0.146559E+11 0.00 0.61
Minimum of Months 0.00 0.317877E+09 0.00 0.00 1425432.40 0.00 0.00 0.00 0.39
Maximum of Months 0.107844E+10 0.283149E+10 0.00 8421404.60 33185163.49 0.206552E+09 0.350554E+10 0.00 0.99



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: PERIMETER_TOP_ZN_4

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.159503E+10 0.159715E+09 0.00 810080.97 9410611.45 0.310597E+09 0.576542E+09 0.00 0.61
February 0.104065E+10 0.193410E+09 0.00 1192129.07 3442341.55 0.150890E+09 0.608632E+09 0.00 0.68
March 0.125836E+10 0.291992E+09 0.00 2056970.25 13707123.34 0.119423E+09 0.940374E+09 0.00 0.77
April 0.325693E+09 0.615493E+09 0.00 2762305.63 8718335.93 0.00 0.722337E+09 0.00 0.81
May 0.00 0.162269E+10 0.00 0.00 9276654.48 0.00 0.00 0.00 0.51
June 653625.76 0.186665E+10 0.00 14199.36 5518383.19 0.00 98341.21 0.00 0.56
July 0.00 0.221937E+10 0.00 0.00 12266853.32 0.00 0.00 0.00 0.50
August 0.00 0.226070E+10 0.00 0.00 12908024.60 0.00 0.00 0.00 0.56
September 0.00 0.186421E+10 0.00 0.00 23839593.06 0.00 0.00 0.00 0.47
October 0.237326E+09 0.127365E+10 0.00 1439498.47 13302449.74 0.00 0.384740E+09 0.00 0.62
November 0.979667E+09 0.437517E+09 0.00 1826425.59 15553036.70 7044191.72 0.727576E+09 0.00 0.74
December 0.148456E+10 0.340356E+09 0.00 795931.30 23754407.76 0.201694E+09 0.397005E+09 0.00 0.60
                   
Annual Sum or Average 0.692193E+10 0.131457E+11 0.00 10897540.64 0.151698E+09 0.789648E+09 0.435731E+10 0.00 0.62
Minimum of Months 0.00 0.159715E+09 0.00 0.00 3442341.55 0.00 0.00 0.00 0.47
Maximum of Months 0.159503E+10 0.226070E+10 0.00 2762305.63 23839593.06 0.310597E+09 0.940374E+09 0.00 0.81



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BOT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 31171110.80 0.00 2676190.27 0.00 0.00 0.326026E+09 0.00 0.28
February 0.00 48201917.42 0.00 4432491.84 0.00 0.00 0.176014E+09 0.00 0.29
March 0.00 83138210.77 0.00 8577087.26 0.00 0.00 0.220159E+09 0.00 0.31
April 0.00 0.159000E+09 0.00 4903372.94 0.00 0.00 50695113.11 0.00 0.29
May 0.00 0.422331E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.519274E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.601281E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.604596E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.427770E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.348255E+09 0.00 1535060.49 0.00 0.00 45155846.69 0.00 0.28
November 0.00 0.123660E+09 0.00 6759912.08 0.00 0.00 0.125931E+09 0.00 0.28
December 0.00 90330746.47 0.00 10864818.43 0.00 0.00 0.241486E+09 0.00 0.28
                   
Annual Sum or Average 0.00 0.345901E+10 0.00 39748933.31 0.00 0.00 0.118547E+10 0.00 0.29
Minimum of Months 0.00 31171110.80 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.604596E+09 0.00 10864818.43 0.00 0.00 0.326026E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_MID_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.298280E+09 0.00 20055692.85 0.00 0.00 0.327033E+10 0.00 0.28
February 0.00 0.476950E+09 0.00 38924448.20 0.00 0.00 0.176508E+10 0.00 0.29
March 0.00 0.830311E+09 0.00 78470903.54 0.00 0.00 0.220448E+10 0.00 0.31
April 0.00 0.159201E+10 0.00 46416107.14 0.00 0.00 0.507103E+09 0.00 0.29
May 0.00 0.418739E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.517955E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.600688E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.604095E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.422804E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.347029E+10 0.00 14130169.21 0.00 0.00 0.451595E+09 0.00 0.28
November 0.00 0.123506E+10 0.00 62451922.37 0.00 0.00 0.126096E+10 0.00 0.28
December 0.00 0.903810E+09 0.00 99561346.15 0.00 0.00 0.241800E+10 0.00 0.28
                   
Annual Sum or Average 0.00 0.344495E+11 0.00 0.360011E+09 0.00 0.00 0.118775E+11 0.00 0.29
Minimum of Months 0.00 0.298280E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 0.00 0.604095E+10 0.00 99561346.15 0.00 0.00 0.327033E+10 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_TOP_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 36794530.98 29611974.49 0.00 1369048.12 0.00 0.00 0.291432E+09 0.00 0.28
February 0.00 47466476.53 0.00 3532054.14 0.00 0.00 0.177339E+09 0.00 0.29
March 0.00 82849716.23 0.00 7487902.22 0.00 0.00 0.221113E+09 0.00 0.31
April 0.00 0.159005E+09 0.00 4594099.33 0.00 0.00 50883005.36 0.00 0.29
May 0.00 0.420131E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
June 0.00 0.518287E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.30
July 0.00 0.600553E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.28
August 0.00 0.607391E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
September 0.00 0.423949E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.29
October 0.00 0.347038E+09 0.00 1358214.89 0.00 0.00 45296830.17 0.00 0.28
November 0.00 0.123285E+09 0.00 6023839.28 0.00 0.00 0.126597E+09 0.00 0.28
December 0.00 90167365.16 0.00 9468698.47 0.00 0.00 0.242604E+09 0.00 0.28
                   
Annual Sum or Average 36794530.98 0.344973E+10 0.00 33833856.45 0.00 0.00 0.115527E+10 0.00 0.29
Minimum of Months 0.00 29611974.49 0.00 0.00 0.00 0.00 0.00 0.00 0.28
Maximum of Months 36794530.98 0.607391E+09 0.00 9468698.47 0.00 0.00 0.291432E+09 0.00 0.31



Table of Contents

Report: MechanicalVentilationLoadsMonthly

For: DATACENTER_BASEMENT_ZN_6

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

ZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach]
January 0.00 0.823293E+09 0.00 0.159213E+09 0.00 0.00 0.745830E+10 0.00 0.32
February 0.00 0.111714E+10 0.00 0.223179E+09 0.00 0.00 0.404521E+10 0.00 0.32
March 0.00 0.182904E+10 0.00 0.431959E+09 0.00 0.00 0.482783E+10 0.00 0.34
April 0.00 0.308023E+10 0.00 0.239291E+09 0.00 0.00 0.108909E+10 0.00 0.32
May 0.00 0.994081E+10 0.00 0.00 0.00 0.00 0.00 0.00 0.33
June 0.00 0.116372E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.34
July 0.00 0.132427E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.31
August 0.00 0.112334E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.35
September 0.00 0.101546E+11 0.00 0.00 0.00 0.00 0.00 0.00 0.33
October 0.00 0.783394E+10 0.00 78074821.39 0.00 0.00 0.101473E+10 0.00 0.32
November 0.00 0.272192E+10 0.00 0.337924E+09 0.00 0.00 0.269382E+10 0.00 0.32
December 0.00 0.182197E+10 0.00 0.544572E+09 0.00 0.00 0.526009E+10 0.00 0.31
                   
Annual Sum or Average 0.00 0.754363E+11 0.00 0.201421E+10 0.00 0.00 0.263891E+11 0.00 0.33
Minimum of Months 0.00 0.823293E+09 0.00 0.00 0.00 0.00 0.00 0.00 0.31
Maximum of Months 0.00 0.132427E+11 0.00 0.544572E+09 0.00 0.00 0.745830E+10 0.00 0.35



Table of Contents

Report: HeatEmissionsReportMonthly

For: Environment

Timestamp: 2023-10-16 09:04:59

Custom Monthly Report

SITE TOTAL SURFACE HEAT EMISSION TO AIR [J] SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J]
January 0.431339E+12 0.103534E+11 0.00 0.147288E+13 0.967846E+12
February 0.459024E+12 0.816866E+10 0.00 0.123101E+13 0.146220E+13
March 0.524105E+12 0.789550E+10 0.00 0.123364E+13 0.210218E+13
April 0.578944E+12 0.144821E+10 0.00 0.669908E+12 0.298023E+13
May 0.574997E+12 -0.110683E+11 0.00 -0.564678E+12 0.289061E+13
June 0.571216E+12 -0.880602E+10 0.00 -0.661765E+12 0.331308E+13
July 0.590954E+12 -0.158830E+11 0.00 -0.769809E+12 0.383340E+13
August 0.545171E+12 -0.148966E+11 0.00 -0.750264E+12 0.433691E+13
September 0.473773E+12 -0.142917E+11 0.00 -0.581536E+12 0.275191E+13
October 0.477881E+12 -0.809111E+10 0.00 -0.210959E+11 0.290752E+13
November 0.373525E+12 0.439422E+10 0.00 0.105978E+13 0.235378E+13
December 0.387172E+12 0.888376E+10 0.00 0.132037E+13 0.242660E+13
           
Annual Sum or Average 0.598810E+13 -0.318930E+11 0.00 0.363843E+13 0.323263E+14
Minimum of Months 0.373525E+12 -0.158830E+11 0.00 -0.769809E+12 0.967846E+12
Maximum of Months 0.590954E+12 0.103534E+11 0.00 0.147288E+13 0.433691E+13