Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04
Tabular Output Report in Format: HTML
Building: OfficeLarge
Environment: RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2023-10-16 09:04:14
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 32152.78 | 694.14 | 694.14 |
Net Site Energy | 32152.78 | 694.14 | 694.14 |
Total Source Energy | 96364.85 | 2080.40 | 2080.40 |
Net Source Energy | 96364.85 | 2080.40 | 2080.40 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 46320.38 |
Net Conditioned Building Area | 46320.38 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1885.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 3675.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 2743.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 448.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 2810.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 497.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 941.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4904.64 |
Humidification | 1283.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.46 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 736.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 29530.12 | 2622.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7662.26 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1885.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 3675.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 2743.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 448.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 5871.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 9341.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 59.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 1848.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 5.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 2810.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 497.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 941.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4904.64 |
Humidification | General | 1283.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.46 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 | |
Water Heater | 0.00 | 736.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1885.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 3675.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 2743.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 448.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 15213.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 1914.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 2810.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 497.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 941.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4904.64 |
Humidification | Unassigned | 1283.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 477.46 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 0.00 | 736.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2280.17 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 198.83 | 56.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 637.52 | 56.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 68.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 198.83 | 56.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Other | 369.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 637.52 | 56.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 29530.122 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 29530.122 | 100.00 |
Total On-Site and Utility Electric Sources | 29530.122 | 100.00 |
Total Electricity End Uses | 29530.122 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 7662.26 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 7662.26 | 100.00 |
Total Water End Uses | 7662.26 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 84.50 |
Time Setpoint Not Met During Occupied Cooling | 1575.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 5943.00 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
| Environment |ZoneCoolingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneHeatingSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ZoneElectricSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |SpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |PeakSpaceGainsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM |SpaceGainComponentsAtCoolingPeakMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |ComfortReportSimple55Monthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |OccupantComfortDataSummaryMonthly
| DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 | BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 |ChillerReportMonthly
| COOLSYS1 CHILLER1 | COOLSYS1 CHILLER2 |TowerReportMonthly
| CENTRAL TOWER | TOWERWATERSYS COOLTOWER 1 | TOWERWATERSYS COOLTOWER 2 |BoilerReportMonthly
| HEATSYS1 BOILER | CENTRAL BOILER |DXReportMonthly
| VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |WindowReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowEnergyReportMonthly
| PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW |WindowZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |WindowEnergyZoneSummaryMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| SWHSYS1 WATER HEATER |DaylightingReportMonthly
| PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_4_DAYLCTRL |CoilReportMonthly
| VAV_BOT WITH REHEAT HEATING COIL | CORE_BOTTOM VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | VAV_MID WITH REHEAT HEATING COIL | CORE_MID VAV BOX REHEAT COIL | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | VAV_TOP WITH REHEAT HEATING COIL | CORE_TOP VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | CAV_BAS HEATING COIL | AIRLOOP DATACENTER BASEMENT HEATING COIL | AIRLOOP DATACENTER BOT HEATING COIL | AIRLOOP DATACENTER MID HEATING COIL | AIRLOOP DATACENTER TOP HEATING COIL | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | AIRLOOP DATACENTER MID_SUPPHEATCOIL | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | VAV_BOT WITH REHEAT COOLING COIL | VAV_MID WITH REHEAT COOLING COIL | VAV_TOP WITH REHEAT COOLING COIL | CAV_BAS COOLING COIL | AIRLOOP DATACENTER BASEMENT COOLING COIL | AIRLOOP DATACENTER BOT COOLING COIL | AIRLOOP DATACENTER MID COOLING COIL | AIRLOOP DATACENTER TOP COOLING COIL |PlantLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |FanReportMonthly
| CAV_BAS FAN | VAV_BOT WITH REHEAT FAN | VAV_MID WITH REHEAT FAN | VAV_TOP WITH REHEAT FAN | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | AIRLOOP DATACENTER BOT SUPPLY FAN | AIRLOOP DATACENTER MID SUPPLY FAN | AIRLOOP DATACENTER TOP SUPPLY FAN |PumpReportMonthly
| HEATSYS1 PUMP | COOLSYS1 PUMP SECONDARY | COOLSYS1 PUMP | PLANT CIRC PUMP | SWHSYS1 PUMP | TOWERWATERSYS PUMP |CondLoopDemandReportMonthly
| HEATSYS1 | COOLSYS1_SUPPLY | COOLSYS1_DEMAND | SINGLE WATER PLANT LOOP | SWHSYS1 | TOWERWATERSYS |ZoneTemperatureOscillationReportMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | GROUNDFLOOR_PLENUM | MIDFLOOR_PLENUM | TOPFLOOR_PLENUM | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |AirLoopSystemEnergyAndWaterUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentLoadsMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |AirLoopSystemComponentEnergyUseMonthly
| VAV_BOT WITH REHEAT | VAV_MID WITH REHEAT | VAV_TOP WITH REHEAT | CAV_BAS | AIRLOOP DATACENTER BASEMENT | AIRLOOP DATACENTER BOT | AIRLOOP DATACENTER MID | AIRLOOP DATACENTER TOP |MechanicalVentilationLoadsMonthly
| BASEMENT | CORE_BOTTOM | CORE_MID | CORE_TOP | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_4 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_4 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_4 | DATACENTER_BOT_ZN_6 | DATACENTER_MID_ZN_6 | DATACENTER_TOP_ZN_6 | DATACENTER_BASEMENT_ZN_6 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 09:04 |
RunPeriod | RUNPERIOD 1 |
Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Latitude [deg] | 39.72 |
Longitude [deg] | -104.8 |
Elevation [m] | 1726.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 12183.89 | 3655.17 | 2436.78 | 3655.17 | 2436.78 |
Above Ground Wall Area [m2] | 11589.54 | 3476.86 | 2317.91 | 3476.86 | 2317.91 |
Window Opening Area [m2] | 3476.85 | 1043.06 | 695.37 | 1043.06 | 695.37 |
Gross Window-Wall Ratio [%] | 28.54 | 28.54 | 28.54 | 28.54 | 28.54 |
Above Ground Window-Wall Ratio [%] | 30.00 | 30.00 | 30.00 | 30.00 | 30.00 |
Total | |
Gross Roof Area [m2] | 3563.11 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
BASEMENT | 2779.43 | Yes | Yes | 6779.02 | 1.00 | 0.00 | 397.05 | 0.00 | 0.00 | 7.6202 | 18.58 | 4.8418 |
CORE_BOTTOM | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0697 |
CORE_MID | 2496.12 | Yes | Yes | 6849.35 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
CORE_TOP | 2496.12 | Yes | Yes | 6849.35 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.6202 | 18.58 | 8.0696 |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 860.00 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 860.02 | 10.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 554.22 | 10.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 860.00 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0700 |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 860.02 | 1.00 | 200.61 | 0.00 | 86.92 | 86.92 | 7.6202 | 18.58 | 8.0699 |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 554.22 | 1.00 | 133.74 | 0.00 | 57.95 | 57.95 | 7.6202 | 18.58 | 8.0699 |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 10.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 4344.14 | 1.00 | 297.11 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 99.34 | 10.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 99.34 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.5114 | 18.58 | 215.2992 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1911.37 | 1.00 | 0.00 | 197.31 | 0.00 | 0.00 | 7.6202 | 18.58 | 484.4232 |
Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Conditioned Total | 46320.38 | 126016.35 | 8024.24 | 594.36 | 3476.85 | 3476.85 | 7.6661 | 18.58 | 17.8789 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 42757.27 | 52129.67 | 3565.29 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
BASEMENT | 2779.43 | Yes | Yes | 1.00 | BASEMENT | GENERAL | BASEMENT | 7.6202 | 18.58 | 4.8418 | |
CORE_BOTTOM | 2496.12 | Yes | Yes | 1.00 | CORE_BOTTOM | GENERAL | CORE_BOTTOM | 7.6202 | 18.58 | 8.0697 | |
CORE_MID | 2496.12 | Yes | Yes | 10.00 | CORE_MID | GENERAL | CORE_MID | 7.6202 | 18.58 | 8.0696 | |
CORE_TOP | 2496.12 | Yes | Yes | 1.00 | CORE_TOP | GENERAL | CORE_TOP | 7.6202 | 18.58 | 8.0696 | |
PERIMETER_BOT_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_3 | GENERAL | PERIMETER_BOT_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_2 | GENERAL | PERIMETER_BOT_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_BOT_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_1 | GENERAL | PERIMETER_BOT_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_BOT_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_BOT_ZN_4 | GENERAL | PERIMETER_BOT_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_3 | 313.41 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_3 | GENERAL | PERIMETER_MID_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_2 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_2 | GENERAL | PERIMETER_MID_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_MID_ZN_1 | 313.42 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_1 | GENERAL | PERIMETER_MID_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_MID_ZN_4 | 201.98 | Yes | Yes | 10.00 | PERIMETER_MID_ZN_4 | GENERAL | PERIMETER_MID_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_3 | 313.41 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_3 | GENERAL | PERIMETER_TOP_ZN_3 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_2 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_2 | GENERAL | PERIMETER_TOP_ZN_2 | 7.6202 | 18.58 | 8.0700 | |
PERIMETER_TOP_ZN_1 | 313.42 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_1 | GENERAL | PERIMETER_TOP_ZN_1 | 7.6202 | 18.58 | 8.0699 | |
PERIMETER_TOP_ZN_4 | 201.98 | Yes | Yes | 1.00 | PERIMETER_TOP_ZN_4 | GENERAL | PERIMETER_TOP_ZN_4 | 7.6202 | 18.58 | 8.0699 | |
GROUNDFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | GROUNDFLOOR_PLENUM | GENERAL | GROUNDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
MIDFLOOR_PLENUM | 3563.11 | Yes | No | 10.00 | MIDFLOOR_PLENUM | GENERAL | MIDFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
TOPFLOOR_PLENUM | 3563.11 | Yes | No | 1.00 | TOPFLOOR_PLENUM | GENERAL | TOPFLOOR_PLENUM | 0.0000 | 0.00 | 0.0000 | |
DATACENTER_BOT_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_BOT_ZN_6 | GENERAL | DATACENTER_BOT_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_MID_ZN_6 | 36.20 | Yes | Yes | 10.00 | DATACENTER_MID_ZN_6 | GENERAL | DATACENTER_MID_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_TOP_ZN_6 | 36.20 | Yes | Yes | 1.00 | DATACENTER_TOP_ZN_6 | GENERAL | DATACENTER_TOP_ZN_6 | 12.5114 | 18.58 | 215.2992 | |
DATACENTER_BASEMENT_ZN_6 | 783.68 | Yes | Yes | 1.00 | DATACENTER_BASEMENT_ZN_6 | GENERAL | DATACENTER_BASEMENT_ZN_6 | 7.6202 | 18.58 | 484.4232 | |
Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Conditioned Total | 46320.38 | 7.6661 | 9.29 | 17.8789 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 42757.27 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 46320.38 | 46320.38 | 0.00 | 42757.27 | 2.3561 | 60.38 | 10.8345 |
Total | 46320.38 | 46320.38 | 0.00 | 42757.27 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-AUG-15:09 | 23-DEC-07:19 | - | - | - | - | - | - | - | - | - | - | 26-JUN-15:09 |
Heating | 0.00 | 1461485.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 432978.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 794004.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 83146.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 274880.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 50964.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 80361.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 38556.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 27833.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1989326.38 | 1489319.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Boiler | 0.00 | 1461485.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Cooling | General | 432978.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 234435.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DataCenterPlugLoads | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Exterior Equipment | Transformer | 3711.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
ElevatorLift | 79171.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
ElevatorLightsFan | 263.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Fans | General | 274880.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 50964.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 80361.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 38556.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Water Heater | 0.00 | 27833.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2044.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 11641.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 8689.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 1421.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 48180.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 6062.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 8902.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 1576.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 2982.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 4064.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 798.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 93521.90 | 2842.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 44.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 251.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2019.02 | 61.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 44.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 251.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 187.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 30.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 1040.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 130.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 192.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 34.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 64.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 87.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 0.00 | 17.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2019.02 | 61.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
BASEMENT DIRECT AIR | 6.43 |
DATACENTER_BOT_ZN_6 DIRECT AIR | 0.595637 |
DATACENTER_MID_ZN_6 DIRECT AIR | 5.70 |
DATACENTER_TOP_ZN_6 DIRECT AIR | 0.581486 |
DATACENTER_BASEMENT_ZN_6 DIRECT AIR | 26.28 |
Design Size Maximum Air Flow Rate [m3/s] | Design Size Constant Minimum Air Flow Fraction | User-Specified Constant Minimum Air Flow Fraction | Design Size Minimum Air Flow Rate [m3/s] | Design Size Maximum Flow Fraction during Reheat [] | User-Specified Maximum Flow Fraction during Reheat [] | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | Design Size Maximum Reheat Water Flow Rate [m3/s] | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | |
CORE_BOTTOM VAV BOX COMPONENT | 6.87 | 0.276874 | 0.293000 | 2.01 | 0.738330 | 0.500000 | 0.001376 | 0.000144 | 2.01 | 12.80 | 0.008000 |
CORE_MID VAV BOX COMPONENT | 64.55 | 0.294671 | 0.305000 | 19.69 | 0.785789 | 0.500000 | 0.001293 | 0.004017 | 19.69 | 12.80 | 0.008000 |
CORE_TOP VAV BOX COMPONENT | 6.40 | 0.297093 | 0.316000 | 2.02 | 0.792247 | 0.500000 | 0.001282 | 0.000868 | 3.64 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | 1.12 | 0.213477 | 0.226000 | 0.252831 | 0.569271 | 0.500000 | 0.001785 | 0.000134 | 0.560882 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | 1.34 | 0.114994 | 0.200000 | 0.267676 | 0.306650 | 0.500000 | 0.003313 | 0.000095 | 0.396865 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | 1.53 | 0.156039 | 0.200000 | 0.306111 | 0.416103 | 0.500000 | 0.002442 | 0.000154 | 0.644769 | 12.80 | 0.008000 |
PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | 1.72 | 0.089394 | 0.200000 | 0.344331 | 0.300000 | 0.500000 | 0.004262 | 0.000076 | 0.344331 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_3 VAV BOX COMPONENT | 10.47 | 0.228099 | 0.236000 | 2.47 | 0.608263 | 0.500000 | 0.001670 | 0.002114 | 8.88 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_2 VAV BOX COMPONENT | 14.05 | 0.109571 | 0.200000 | 2.81 | 0.300000 | 0.500000 | 0.003477 | 0.001418 | 5.96 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_1 VAV BOX COMPONENT | 14.91 | 0.160157 | 0.200000 | 2.98 | 0.427085 | 0.500000 | 0.002379 | 0.002137 | 8.98 | 12.80 | 0.008000 |
PERIMETER_MID_ZN_4 VAV BOX COMPONENT | 15.45 | 0.099647 | 0.200000 | 3.09 | 0.300000 | 0.500000 | 0.003824 | 0.001359 | 5.71 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | 1.21 | 0.197716 | 0.210000 | 0.253658 | 0.527243 | 0.500000 | 0.001927 | 0.000279 | 1.17 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | 1.41 | 0.109103 | 0.200000 | 0.282127 | 0.300000 | 0.500000 | 0.003492 | 0.000186 | 0.780594 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | 1.64 | 0.145479 | 0.200000 | 0.328331 | 0.387943 | 0.500000 | 0.002619 | 0.000281 | 1.18 | 12.80 | 0.008000 |
PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | 1.66 | 0.092806 | 0.200000 | 0.331670 | 0.300000 | 0.500000 | 0.004105 | 0.000182 | 0.763889 | 12.80 | 0.008000 |
Design Size Rated Capacity [W] | Design Size Maximum Water Flow Rate [m3/s] | Design Size U-Factor Times Area Value [W/K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | 16450.84 | 0.000144 | 331.64 |
CORE_MID VAV BOX REHEAT COIL | 459186.98 | 0.004017 | 11373.71 |
CORE_TOP VAV BOX REHEAT COIL | 99203.21 | 0.000868 | 2617.72 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 15270.18 | 0.000134 | 402.79 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10802.51 | 0.000095 | 284.92 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 17549.29 | 0.000154 | 462.86 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8644.12 | 0.000076 | 220.22 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 241639.41 | 0.002114 | 6371.22 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 162099.28 | 0.001418 | 4273.90 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 244293.37 | 0.002137 | 6441.15 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 155353.91 | 0.001359 | 4096.15 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 31845.99 | 0.000279 | 839.54 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 21223.89 | 0.000186 | 559.50 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 32171.88 | 0.000281 | 848.12 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 20770.02 | 0.000182 | 547.54 |
VAV_BOT WITH REHEAT HEATING COIL | 69971.82 | 0.000612 | 1120.01 |
VAV_MID WITH REHEAT HEATING COIL | 730417.81 | 0.006390 | 11536.81 |
VAV_TOP WITH REHEAT HEATING COIL | 72225.49 | 0.000632 | 1154.88 |
CAV_BAS HEATING COIL | 273563.32 | 0.002393 | 5951.55 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT | 6.29 | 3.18 | 12.58 | 3.18 | 11.18 | 11.18 | 0.300000 | 0.284889 | 11.18 |
VAV_MID WITH REHEAT | 59.71 | 31.04 | 119.42 | 45.09 | 103.85 | 103.85 | 0.300000 | 0.434137 | 103.85 |
VAV_TOP WITH REHEAT | 6.16 | 3.22 | 12.32 | 7.54 | 11.46 | 11.46 | 0.300000 | 0.657920 | 11.46 |
CAV_BAS | 6.43 | 6.43 | 6.43 | 6.43 | 6.43 | 6.43 | 1.00 | 1.00 | 6.43 |
AIRLOOP DATACENTER BASEMENT | 26.28 | 26.28 | 26.28 | 26.28 | 26.28 | 26.28 | 1.00 | 0.999986 | 26.28 |
AIRLOOP DATACENTER BOT | 0.595637 | 0.595637 | 0.595637 | 0.595637 | 0.595637 | 0.595637 | 1.00 | 1.00 | 0.595637 |
AIRLOOP DATACENTER MID | 5.70 | 5.70 | 5.70 | 5.70 | 5.70 | 5.70 | 1.00 | 1.00 | 5.70 |
AIRLOOP DATACENTER TOP | 0.581486 | 0.581486 | 0.581486 | 0.581486 | 0.581486 | 0.581486 | 1.00 | 1.00 | 0.581486 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | 11.18 | |
VAV_MID WITH REHEAT_OA_CONTROLLER | 103.85 | |
VAV_TOP WITH REHEAT_OA_CONTROLLER | 11.46 | |
CAV_BAS_OA_CONTROLLER | 6.43 | 1.20 |
AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | 26.28 | 0.338393 |
AIRLOOP DATACENTER BOT_OA_CONTROLLER | 0.595637 | 0.015632 |
AIRLOOP DATACENTER MID_OA_CONTROLLER | 5.70 | 0.156323 |
AIRLOOP DATACENTER TOP_OA_CONTROLLER | 0.581486 | 0.015632 |
Design Size Design Inlet Air Temperature [C] | Design Size Design Inlet Water Temperature [C] | Design Size Design Outlet Air Temperature [C] | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | Design Size Design Coil Load [W] | Design Size Design Water Flow Rate [m3/s] | Design Size Design Air Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT COOLING COIL | 26.33 | 6.67 | 10.52 | 0.006905 | 0.006905 | 175795.72 | 0.007479 | 11.18 |
VAV_MID WITH REHEAT COOLING COIL | 26.58 | 6.67 | 10.52 | 0.006874 | 0.006874 | 1659236.15 | 0.070588 | 103.85 |
VAV_TOP WITH REHEAT COOLING COIL | 26.20 | 6.67 | 10.52 | 0.006901 | 0.006901 | 178731.63 | 0.007604 | 11.46 |
CAV_BAS COOLING COIL | 25.93 | 6.67 | 11.10 | 0.007098 | 0.007098 | 94867.03 | 0.004036 | 6.43 |
Design Size Maximum Flow Rate [m3/s] | |
VAV_BOT WITH REHEAT FAN | 11.18 |
VAV_MID WITH REHEAT FAN | 103.85 |
VAV_TOP WITH REHEAT FAN | 11.46 |
Maximum Actuated Flow [m3/s] | Controller Convergence Tolerance | |
VAV_BOT WITH REHEAT_COOLC_CONTROLLER | 0.007479 | 0.000064 |
VAV_BOT WITH REHEAT_HEATC_CONTROLLER | 0.000612 | |
VAV_MID WITH REHEAT_COOLC_CONTROLLER | 0.070588 | 0.000007 |
VAV_MID WITH REHEAT_HEATC_CONTROLLER | 0.006390 | |
VAV_TOP WITH REHEAT_COOLC_CONTROLLER | 0.007604 | 0.000063 |
VAV_TOP WITH REHEAT_HEATC_CONTROLLER | 0.000632 | |
CAV_BAS_COOLC_CONTROLLER | 0.004036 | 0.000118 |
CAV_BAS_HEATC_CONTROLLER | 0.002393 |
Design Size Maximum Flow Rate [m3/s] | |
CAV_BAS FAN | 6.43 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Total Cooling Capacity [W] | Design Size Rated Sensible Cooling Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | 26.28 | 476647.15 | 249789.49 | 0.011673 |
AIRLOOP DATACENTER BOT COOLING COIL | 0.595637 | 10504.22 | 5559.89 | 0.000257 |
AIRLOOP DATACENTER MID COOLING COIL | 5.70 | 100513.41 | 53190.89 | 0.002462 |
AIRLOOP DATACENTER TOP COOLING COIL | 0.581486 | 10256.74 | 5428.27 | 0.000251 |
Supply Air Flow Rate [m3/s] | Supply Air Flow Rate During Heating Operation [m3/s] | Supply Air Flow Rate During Cooling Operation [m3/s] | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | Nominal Heating Capacity [W] | Nominal Cooling Capacity [W] | Supplemental Heating Coil Nominal Capacity [W] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | 26.28 | 26.28 | 26.28 | 26.28 | 476647.15 | 476647.15 | 19243.92 | 1.00 |
AIRLOOP DATACENTER BOT DXAC HEAT PUMP | 0.595637 | 0.595637 | 0.595637 | 0.595637 | 10504.22 | 10504.22 | 888.99 | 1.00 |
AIRLOOP DATACENTER MID DXAC HEAT PUMP | 5.70 | 5.70 | 5.70 | 5.70 | 100513.41 | 100513.41 | 8889.90 | 1.00 |
AIRLOOP DATACENTER TOP DXAC HEAT PUMP | 0.581486 | 0.581486 | 0.581486 | 0.581486 | 10256.74 | 10256.74 | 888.99 | 1.00 |
Design Size Maximum Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | 26.28 |
AIRLOOP DATACENTER BOT SUPPLY FAN | 0.595637 |
AIRLOOP DATACENTER MID SUPPLY FAN | 5.70 |
AIRLOOP DATACENTER TOP SUPPLY FAN | 0.581486 |
Design Size Rated Air Flow Rate [m3/s] | Design Size Rated Heating Capacity [W] | Design Size Rated Water Flow Rate [m3/s] | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | 26.28 | 476647.15 | 0.011673 |
AIRLOOP DATACENTER BOT HEATING COIL | 0.595637 | 10504.22 | 0.000257 |
AIRLOOP DATACENTER MID HEATING COIL | 5.70 | 100513.41 | 0.002462 |
AIRLOOP DATACENTER TOP HEATING COIL | 0.581486 | 10256.74 | 0.000251 |
Design Size Nominal Capacity [W] | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | 19243.92 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | 888.99 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | 8889.90 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | 888.99 |
Design Size Nominal Capacity Volume [m3/s] | User-Specified Nominal Capacity Volume [m3/s] | Design Size Rated Power [W] | User-Specified Rated Power [W] | |
DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | 0.000175 | 0.000037 | 96450.70 | 100000.00 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | Design Minimum Flow Rate [m3/s] | |
COOLSYS1 PUMP SECONDARY | 0.089706 | 18485.09 | |
HEATSYS1 PUMP | 0.023469 | 7067.92 | 0.000000 |
Maximum Loop Flow Rate [m3/s] | Plant Loop Volume [m3] | |
COOLSYS1_DEMAND | 0.089706 | 10.76 |
HEATSYS1 | 0.023469 | 2.82 |
COOLSYS1_SUPPLY | 0.089706 | 10.76 |
SINGLE WATER PLANT LOOP | 0.014643 | 1.76 |
SWHSYS1 | 0.000440 | 0.052800 |
Loop Supply Side Design Fluid Flow Rate [m3/s] | Loop Demand Side Design Fluid Flow Rate [m3/s] | Heat Exchanger U-Factor Times Area Value [W/C] | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | |
BYPASS HEAT EXCHANGER | 0.089706 | 0.089706 | 376541.16 | 5.60 |
Design Size Nominal Capacity [W] | User-Specified Nominal Capacity [W] | Design Size Design Water Flow Rate [m3/s] | |
HEATSYS1 BOILER | 2682683.32 | 2682683.32 | 0.023469 |
CENTRAL BOILER | 603168.53 | 589384.81 | 0.014643 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
COOLSYS1 PUMP | 0.089706 | 12797.85 |
PLANT CIRC PUMP | 0.014643 | 3734.71 |
SWHSYS1 PUMP | 0.000440 | 5.96 |
Design Size Reference Chilled Water Flow Rate [m3/s] | User-Specified Reference Chilled Water Flow Rate [m3/s] | Design Size Reference Capacity [W] | User-Specified Reference Capacity [W] | Design Size Reference Condenser Water Flow Rate [m3/s] | |
COOLSYS1 CHILLER1 | 0.089706 | 0.045211 | 1065337.24 | 1070390.00 | 0.052970 |
COOLSYS1 CHILLER2 | 0.089706 | 0.045211 | 1065337.24 | 1070390.00 | 0.052970 |
Design Water Flow Rate [m3/s] | Air Flow Rate at High Fan Speed [m3/s] | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | Air Flow Rate at Low Fan Speed [m3/s] | Fan Power at Low Fan Speed [W] | U-factor Times Area Value at Low Fan Speed [W/C] | |
CENTRAL TOWER | 0.014643 | 139666.47 | 54893.54 | 69833.23 | 7879.72 | 20946.66 |
Use Side Design Flow Rate [m3/s] | |
SWHSYS1 WATER HEATER | 0.000440 |
Maximum Loop Flow Rate [m3/s] | Condenser Loop Volume [m3] | |
TOWERWATERSYS | 0.105939 | 12.71 |
Design Flow Rate [m3/s] | Design Power Consumption [W] | |
TOWERWATERSYS PUMP | 0.105939 | 31906.60 |
Design Air Flow Rate [m3/s] | Nominal Capacity [W] | Air Flow Rate in free convection regime [m3/s] | Tower capacity in free convection regime at design conditions [W] | |
TOWERWATERSYS COOLTOWER 1 | 50.44 | 1271610.56 | 10.09 | 158951.32 |
TOWERWATERSYS COOLTOWER 2 | 50.44 | 1271610.56 | 10.09 | 158951.32 |
Design Water Flow Rate [m3/s] Equipment # 47 | |
WSHPPLANT OPERATION SCHEME | 0.055020 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
PERIMETER_BOT_ZN_3_WALL_NORTH | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | |
PERIMETER_BOT_ZN_2_WALL_EAST | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | |
PERIMETER_BOT_ZN_1_WALL_SOUTH | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | |
PERIMETER_BOT_ZN_4_WALL_WEST | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | |
PERIMETER_MID_ZN_3_WALL_NORTH | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_MID_ZN_2_WALL_EAST | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_MID_ZN_1_WALL_SOUTH | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_MID_ZN_4_WALL_WEST | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | |
PERIMETER_TOP_ZN_3_WALL_NORTH | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | |
PERIMETER_TOP_ZN_2_WALL_EAST | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | |
PERIMETER_TOP_ZN_1_WALL_SOUTH | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | |
PERIMETER_TOP_ZN_4_WALL_WEST | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
VersionVersion ID | |
1 | 22.1.0 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 7.10 | 3.00 | -1.00 | 0.80 | -0.20 | 4.80 | 6.10 | 13.70 | 22.20 | 22.70 | 21.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 1726.00 | 82237 | 0.9774 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.95 | 23.70 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | OfficeLarge | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 23 | 221 | 36 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | BASEMENT | 0.0 | 0.00 | 0.00 | 0.00 | 44.59 | 24.37 | -1.22 | 1 | 1 | 1 | 16.08 | 73.11 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 6779.02 | TARP | TARP | 2779.43 | 0.00 | 0.00 | 0.00 | 9 | 0 | 0 | Yes |
2 | CORE_BOTTOM | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 1.37 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 7 | 0 | 0 | Yes |
3 | CORE_MID | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 18.14 | 1 | 10 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
4 | CORE_TOP | 0.0 | 0.00 | 0.00 | 0.00 | 37.01 | 24.37 | 34.91 | 1 | 1 | 1 | 5.49 | 68.53 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 6849.35 | TARP | TARP | 2496.12 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
5 | PERIMETER_BOT_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 0.00 | 2.74 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
6 | PERIMETER_BOT_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 1.37 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
7 | PERIMETER_BOT_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 1.37 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 0.00 | 2.74 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 105.88 | 86.92 | 8 | 9 | 0 | Yes |
8 | PERIMETER_BOT_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 1.37 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 0.00 | 2.74 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 71.89 | 57.95 | 6 | 5 | 0 | Yes |
9 | PERIMETER_MID_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 16.77 | 19.51 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
10 | PERIMETER_MID_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 18.14 | 1 | 10 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
11 | PERIMETER_MID_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 18.14 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 16.77 | 19.51 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
12 | PERIMETER_MID_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 18.14 | 1 | 10 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 16.77 | 19.51 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
13 | PERIMETER_TOP_ZN_3 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 46.54 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 44.17 | 48.74 | 33.54 | 36.28 | 2.74 | 860.00 | TARP | TARP | 313.41 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
14 | PERIMETER_TOP_ZN_2 | 0.0 | 0.00 | 0.00 | 0.00 | 70.95 | 24.37 | 34.91 | 1 | 1 | 1 | 68.53 | 73.11 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
15 | PERIMETER_TOP_ZN_1 | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 2.20 | 34.91 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 4.57 | 33.54 | 36.28 | 2.74 | 860.02 | TARP | TARP | 313.42 | 200.61 | 113.68 | 86.92 | 7 | 1 | 0 | Yes |
16 | PERIMETER_TOP_ZN_4 | 0.0 | 0.00 | 0.00 | 0.00 | 2.16 | 24.37 | 34.91 | 1 | 1 | 1 | 0.00 | 4.57 | 0.00 | 48.74 | 33.54 | 36.28 | 2.74 | 554.22 | TARP | TARP | 201.98 | 133.74 | 75.79 | 57.95 | 6 | 1 | 0 | Yes |
17 | GROUNDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 3.35 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 2.74 | 3.96 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
18 | MIDFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 20.12 | 1 | 10 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 19.51 | 20.73 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
19 | TOPFLOOR_PLENUM | 0.0 | 0.00 | 0.00 | 0.00 | 36.55 | 24.37 | 36.89 | 1 | 1 | 1 | 0.00 | 73.11 | 0.00 | 48.74 | 36.28 | 37.50 | 1.22 | 4344.14 | TARP | TARP | 3563.11 | 297.11 | 297.11 | 0.00 | 11 | 0 | 0 | No |
20 | DATACENTER_BOT_ZN_6 | 0.0 | 5.49 | 44.17 | 0.00 | 5.03 | 24.37 | 1.37 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 0.00 | 2.74 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
21 | DATACENTER_MID_ZN_6 | 0.0 | 4.57 | 4.57 | 16.77 | 5.03 | 24.37 | 18.14 | 1 | 10 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 16.77 | 19.51 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
22 | DATACENTER_TOP_ZN_6 | 0.0 | 4.57 | 4.57 | 33.54 | 5.03 | 24.37 | 34.91 | 1 | 1 | 1 | 4.57 | 5.49 | 4.57 | 44.17 | 33.54 | 36.28 | 2.74 | 99.34 | TARP | TARP | 36.20 | 0.00 | 0.00 | 0.00 | 6 | 0 | 0 | Yes |
23 | DATACENTER_BASEMENT_ZN_6 | 0.0 | 16.08 | 0.00 | -2.44 | 8.04 | 24.37 | -1.22 | 1 | 1 | 1 | 0.00 | 16.08 | 0.00 | 48.74 | -2.44 | 0.00 | 2.44 | 1911.37 | TARP | TARP | 783.68 | 0.00 | 0.00 | 0.00 | 10 | 0 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | BASEMENT | 2779.43 | 149.6 | 18.579 | 5.382E-002 | 7.620 | 4.842 | 0.000 | 0.000 | 0.000 | 0.000 | 12.462 | No |
2 | CORE_BOTTOM | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
3 | CORE_MID | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
4 | CORE_TOP | 2496.12 | 134.4 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
5 | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
6 | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
7 | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
8 | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
9 | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
10 | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
11 | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
12 | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
13 | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
14 | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
15 | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
16 | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 18.579 | 5.382E-002 | 7.620 | 8.070 | 0.000 | 0.000 | 0.000 | 0.000 | 15.690 | No |
17 | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
18 | MIDFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
19 | TOPFLOOR_PLENUM | 3563.11 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
20 | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
21 | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
22 | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 18.579 | 5.382E-002 | 12.511 | 215.299 | 0.000 | 0.000 | 0.000 | 0.000 | 227.811 | No |
23 | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 18.579 | 5.382E-002 | 7.620 | 484.423 | 0.000 | 0.000 | 0.000 | 0.000 | 492.043 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | DATACENTER_BOT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | DATACENTER_MID_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | DATACENTER_TOP_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 1.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | DATACENTER_BASEMENT_ZN_6 | BLDG_OCC_SCH_WO_SB | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 42.2 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 42 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | BASEMENT | BLDG_OCC_SCH_WO_SB | BASEMENT | 2779.43 | 149.6 | 149.6 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 150 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | CORE_BOTTOM | BLDG_OCC_SCH_WO_SB | CORE_BOTTOM | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | CORE_MID | BLDG_OCC_SCH_WO_SB | CORE_MID | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | CORE_TOP | BLDG_OCC_SCH_WO_SB | CORE_TOP | 2496.12 | 134.4 | 134.4 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 134 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | PERIMETER_BOT_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | PERIMETER_BOT_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
11 | PERIMETER_BOT_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
12 | PERIMETER_BOT_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
13 | PERIMETER_MID_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
14 | PERIMETER_MID_ZN_2 | BLDG_OCC_SCH_W_SB | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
15 | PERIMETER_MID_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
16 | PERIMETER_MID_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
17 | PERIMETER_TOP_ZN_3 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
18 | PERIMETER_TOP_ZN_2 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
19 | PERIMETER_TOP_ZN_1 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 16.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 17 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
20 | PERIMETER_TOP_ZN_4 | BLDG_OCC_SCH_WO_SB | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 10.9 | 5.382E-002 | 18.579 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 11 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | BASEMENT_LIGHTS | LTG_SCH_OFFICE | BASEMENT | 2779.43 | 149.6 | 21179.739 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 21179.739 |
2 | CORE_BOTTOM_LIGHTS | LTG_SCH_OFFICE | CORE_BOTTOM | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
3 | CORE_MID_LIGHTS | LTG_SCH_OFFICE | CORE_MID | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
4 | CORE_TOP_LIGHTS | LTG_SCH_OFFICE | CORE_TOP | 2496.12 | 134.4 | 19020.895 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 19020.895 |
5 | PERIMETER_BOT_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
6 | PERIMETER_BOT_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
7 | PERIMETER_BOT_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
8 | PERIMETER_BOT_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
9 | PERIMETER_MID_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
10 | PERIMETER_MID_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
11 | PERIMETER_MID_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
12 | PERIMETER_MID_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
13 | PERIMETER_TOP_ZN_3_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2388.263 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.263 |
14 | PERIMETER_TOP_ZN_2_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
15 | PERIMETER_TOP_ZN_1_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2388.315 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2388.315 |
16 | PERIMETER_TOP_ZN_4_LIGHTS | LTG_SCH_OFFICE | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1539.088 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1539.088 |
17 | DATACENTER_BASEMENT_LIGHTS | LTG_SCH_OFFICE | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 5971.780 | 7.620 | 141.574 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 5971.780 |
18 | DATACENTER_BOT_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
19 | DATACENTER_MID_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
20 | DATACENTER_TOP_LIGHTS | LTG_SCH_DATACENTER | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 452.948 | 12.511 | 232.447 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 452.948 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | BASEMENT_MISCPLUG_EQUIP | ALWAYS_ON | BASEMENT | 2779.43 | 149.6 | 13457.544 | 4.842 | 89.956 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 13457.544 | 13457.544 |
2 | CORE_BOTTOM_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_BOTTOM | 2496.12 | 134.4 | 20142.877 | 8.070 | 149.925 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.877 |
3 | CORE_MID_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_MID | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
4 | CORE_TOP_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | CORE_TOP | 2496.12 | 134.4 | 20142.800 | 8.070 | 149.924 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 20142.800 |
5 | PERIMETER_BOT_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
6 | PERIMETER_BOT_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
7 | PERIMETER_BOT_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
8 | PERIMETER_BOT_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
9 | PERIMETER_MID_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
10 | PERIMETER_MID_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
11 | PERIMETER_MID_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
12 | PERIMETER_MID_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
13 | PERIMETER_TOP_ZN_3_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 2529.242 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.242 |
14 | PERIMETER_TOP_ZN_2_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 1629.940 | 8.070 | 149.931 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.940 |
15 | PERIMETER_TOP_ZN_1_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 2529.281 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 2529.281 |
16 | PERIMETER_TOP_ZN_4_MISCPLUG_EQUIP | BLDG_EQUIP_SCH | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 1629.929 | 8.070 | 149.930 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1629.929 |
17 | DATACENTER_BASEMENT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BASEMENT_ZN_6 | 783.68 | 42.2 | 379632.522 | 484.423 | 9000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 94908.130 | 379632.522 |
18 | DATACENTER_BOT_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_BOT_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
19 | DATACENTER_MID_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_MID_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
20 | DATACENTER_TOP_MISCPLUG_EQUIP | DATACENTER_EQUIP_SCH | DATACENTER_TOP_ZN_6 | 36.20 | 1.9 | 7794.422 | 215.299 | 4000.000 | 0.000 | 0.100 | 0.000 | 0.900 | DataCenterPlugLoads | 1948.606 | 7794.422 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | DROPCEILING | 4 | 1 | 3 | 0.167 | 4.488 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
4 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
5 | EXT_SLAB_8IN_WITH_CARPET | 8 | 2 | 7 | 0.167 | 3.285 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
6 | INT_SLAB_FLOOR | 12 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
7 | INT_SLAB_CEILING | 13 | 2 | 7 | 0.167 | 3.839 | 0.900 | 0.900 | 0.700 | 0.700 | VeryRough |
8 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1864 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
9 | NONRES_EXT_WALL_GRD | 20 | 3 | 9 | 0.167 | 1.226 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
10 | NONRES_EXT_WALL_MID | 21 | 3 | 9 | 0.167 | 1.149 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
11 | NONRES_EXT_WALL_TOP | 22 | 3 | 9 | 0.167 | 1.571 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
12 | BASEMENT_WALL_EAST_CFACTOR | 39 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | BASEMENT_WALL_SOUTH_CFACTOR | 40 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | BASEMENT_WALL_NORTH_CFACTOR | 41 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 42 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
16 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 43 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
17 | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 44 | 2 | 7 | 0.167 | 0.4185 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | AC02 ACOUSTIC CEILING | 0.0127 | 0.057 | 288.000 | 1339.000 | 0.2228 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
6 | 200MM NORMALWEIGHT CONCRETE FLOOR | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
7 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
8 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
9 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
10 | CP02 CARPET PAD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2165 |
11 | 100MM NORMALWEIGHT CONCRETE FLOOR | 0.1016 | 2.310 | 2322.000 | 832.000 | 0.4398E-01 |
12 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
13 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 5.307 |
14 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
15 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
16 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 0.6483 |
17 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
18 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
19 | NONRES_EXTERIOR_WALL_INSULATION_MID | 0.0000 | 0.000 | 0.000 | 0.000 | 0.7026 |
20 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
21 | 200MM NORMALWEIGHT CONCRETE WALL | 0.2032 | 2.310 | 2322.000 | 832.000 | 0.8797E-01 |
22 | NONRES_EXTERIOR_WALL_INSULATION_TOP | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4692 |
23 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
24 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
32 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
33 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
34 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 2.312 |
35 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 3 | -0.21589802E-09 | 0.15643069E-09 | -0.21589802E-09 | 0.12999471E-21 |
14 | 2 | 0.50772448E-02 | 0.30006816E-02 | 0.50772448E-02 | -0.13693132E-08 |
15 | 1 | -2.5944910 | 1.4597758 | -2.5944910 | 0.76344767E-02 |
16 | 0 | 7.0433378 | 2.9911476 | 7.0433378 | |
17 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
18 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
19 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
20 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
21 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
22 | 7 | -0.18651654E-16 | -0.16428647E-15 | -0.26578847E-08 | -0.25364002E-17 |
23 | 6 | 0.67402962E-01 | 0.99142722E-07 | 0.38101547E-02 | -0.76639482E-03 |
24 | 5 | -1.8580732 | 0.49502125E-04 | -0.10651409 | 0.21891119E-01 |
25 | 4 | 18.220105 | 0.12801333E-02 | 1.0775450 | -0.22586539 |
26 | 3 | -79.928293 | 0.66708484E-02 | -4.9803755 | 1.0625663 |
27 | 2 | 166.43177 | 0.75131194E-02 | 11.128837 | -2.4125483 |
28 | 1 | -159.97298 | 0.18548900E-02 | -11.587784 | 2.5494418 |
29 | 0 | 57.057412 | 0.52755123E-04 | 4.4818272 | |
30 | 7 | 0.43260499E-16 | 0.34524919E-16 | 0.52793240E-17 | 0.0000000 |
31 | 6 | 0.69434179E-09 | 0.98085174E-11 | 0.18162501E-10 | -0.40870994E-12 |
32 | 5 | -0.12888762E-04 | 0.28373718E-06 | -0.16918523E-06 | 0.92361873E-08 |
33 | 4 | 0.25174112E-01 | 0.33697681E-03 | 0.22646198E-03 | -0.31467795E-04 |
34 | 3 | -3.7600775 | 0.27170599E-01 | -0.48495626E-01 | 0.94171705E-02 |
35 | 2 | 51.553741 | 0.22121684 | 1.2284947 | -0.25833933 |
36 | 1 | -128.86110 | 0.21944682 | -5.1479470 | 1.1228340 |
37 | 0 | 81.526494 | 0.16043334E-01 | 4.4519351 | |
38 | 7 | 0.52793240E-17 | 0.34524919E-16 | 0.43260499E-16 | 0.0000000 |
39 | 6 | 0.18162501E-10 | 0.98085174E-11 | 0.69434179E-09 | -0.40870994E-12 |
40 | 5 | -0.16918523E-06 | 0.28373718E-06 | -0.12888762E-04 | 0.92361873E-08 |
41 | 4 | 0.22646198E-03 | 0.33697681E-03 | 0.25174112E-01 | -0.31467795E-04 |
42 | 3 | -0.48495626E-01 | 0.27170599E-01 | -3.7600775 | 0.94171705E-02 |
43 | 2 | 1.2284947 | 0.22121684 | 51.553741 | -0.25833933 |
44 | 1 | -5.1479470 | 0.21944682 | -128.86110 | 1.1228340 |
45 | 0 | 4.4519351 | 0.16043334E-01 | 81.526494 | |
46 | 3 | -0.62854340E-06 | 0.84784826E-09 | -0.38512804E-05 | 0.91756347E-17 |
47 | 2 | 0.78257096 | 0.11428808E-02 | 1.0614277 | -0.73836085E-06 |
48 | 1 | -21.991499 | 0.76199851E-01 | -6.3161914 | 0.20349372 |
49 | 0 | 21.357363 | 0.71091016E-01 | 5.4032014 | |
50 | 9 | 0.15847945E-14 | 0.40415870E-16 | -0.13570955E-09 | -0.55776231E-17 |
51 | 8 | 0.19900788E-07 | 0.16227319E-12 | 0.35673126E-03 | -0.22627880E-09 |
52 | 7 | -0.11611995E-01 | 0.86155623E-08 | -0.22179000E-01 | 0.13203260E-03 |
53 | 6 | 0.38824249 | 0.30290701E-05 | 0.45749374 | -0.45461023E-02 |
54 | 5 | -5.0235921 | 0.11413317E-03 | -4.3290265 | 0.61113495E-01 |
55 | 4 | 32.264180 | 0.94131685E-03 | 21.001374 | -0.41231550 |
56 | 3 | -109.65428 | 0.20665218E-02 | -54.756066 | 1.4924847 |
57 | 2 | 195.57288 | 0.11699747E-02 | 77.079281 | -2.8759721 |
58 | 1 | -170.58880 | 0.12564906E-03 | -55.024271 | 2.7354972 |
59 | 0 | 57.057407 | 0.71994484E-06 | 15.597457 | |
60 | 9 | 0.92194319E-15 | 0.45185080E-16 | -0.13934922E-09 | -0.37336789E-17 |
61 | 8 | 0.20414049E-07 | 0.15291409E-12 | 0.36227410E-03 | -0.23211478E-09 |
62 | 7 | -0.11777906E-01 | 0.80689916E-08 | -0.22418053E-01 | 0.13391908E-03 |
63 | 6 | 0.39275134 | 0.28300412E-05 | 0.46134659 | -0.45992504E-02 |
64 | 5 | -5.0676021 | 0.10641223E-03 | -4.3586752 | 0.61659190E-01 |
65 | 4 | 32.458904 | 0.87600040E-03 | 21.117392 | -0.41490080 |
66 | 3 | -110.06874 | 0.19199492E-02 | -54.985491 | 1.4984722 |
67 | 2 | 195.98384 | 0.10853975E-02 | 77.289466 | -2.8824978 |
68 | 1 | -170.74067 | 0.11640795E-03 | -55.084954 | 2.7381589 |
69 | 0 | 57.057407 | 0.66605595E-06 | 15.587079 | |
70 | 9 | 0.99499981E-15 | 0.49201796E-16 | -0.11918706E-09 | -0.33210447E-17 |
71 | 8 | 0.17565796E-07 | 0.20231051E-12 | 0.33086922E-03 | -0.19972915E-09 |
72 | 7 | -0.10835659E-01 | 0.11065463E-07 | -0.21059630E-01 | 0.12320537E-03 |
73 | 6 | 0.36714142 | 0.39371282E-05 | 0.43940598 | -0.42973741E-02 |
74 | 5 | -4.8175888 | 0.14987275E-03 | -4.1895891 | 0.58559222E-01 |
75 | 4 | 31.352470 | 0.12474171E-02 | 20.455190 | -0.40021127 |
76 | 3 | -107.71307 | 0.27606440E-02 | -53.675749 | 1.4644420 |
77 | 2 | 193.64724 | 0.15741070E-02 | 76.090603 | -2.8453956 |
78 | 1 | -169.87685 | 0.17016149E-03 | -54.740743 | 2.7230195 |
79 | 0 | 57.057407 | 0.98204117E-06 | 15.647518 | |
80 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
81 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
82 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
83 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
84 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
85 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
86 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
87 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
88 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
89 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
90 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
91 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
92 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
93 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
94 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
95 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
96 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
97 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
98 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
99 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
100 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
101 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
102 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
103 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
104 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
105 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
106 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
107 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
108 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
109 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
110 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
111 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
112 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
113 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
114 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
115 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
116 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
117 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
118 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
119 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 | |
120 | 7 | -0.98583555E-09 | -0.79843648E-16 | 0.12056005E-14 | 0.46388562E-17 |
121 | 6 | 0.11736010E-04 | 0.80964505E-08 | 0.31724491E-02 | -0.26613162E-04 |
122 | 5 | -0.85155955E-03 | 0.48044989E-05 | -0.22273424 | 0.19474091E-02 |
123 | 4 | 0.19629464E-01 | 0.21887653E-03 | 4.8130477 | -0.45106395E-01 |
124 | 3 | -0.17247723 | 0.17421542E-02 | -37.928201 | 0.39762344 |
125 | 2 | 0.61254091 | 0.29000861E-02 | 116.30250 | -1.4155123 |
126 | 1 | -0.88416489 | 0.88473762E-03 | -143.80049 | 2.0472841 |
127 | 0 | 0.43108349 | 0.21254961E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 35 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 36 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 37 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 | ||
4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 38 | 1 | VerySmooth | 2.171 | 2.171 | 1.000 | 0.381 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | GLAZING LAYER EAST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
2 | GLAZING LAYER SOUTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
3 | GLAZING LAYER WEST | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No | |
4 | GLAZING LAYER NORTH | SpectralAverage | 3.43662E-002 | 0.29373 | 0.49831 | 0.49831 | 0.38000 | 0.13982 | 0.18519 | 0.00000 | 0.84000 | 0.84000 | 0.11924 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Enclosure Name | Number of Exterior Windows | Number of Exterior Windows in Adjacent Enclosures | |
1 | PERIMETER_BOT_ZN_3 | 5 | 0 |
2 | PERIMETER_BOT_ZN_2 | 3 | 0 |
3 | PERIMETER_BOT_ZN_1 | 5 | 0 |
4 | PERIMETER_BOT_ZN_4 | 3 | 0 |
5 | PERIMETER_MID_ZN_3 | 1 | 0 |
6 | PERIMETER_MID_ZN_2 | 1 | 0 |
7 | PERIMETER_MID_ZN_1 | 1 | 0 |
8 | PERIMETER_MID_ZN_4 | 1 | 0 |
9 | PERIMETER_TOP_ZN_3 | 1 | 0 |
10 | PERIMETER_TOP_ZN_2 | 1 | 0 |
11 | PERIMETER_TOP_ZN_1 | 1 | 0 |
12 | PERIMETER_TOP_ZN_4 | 1 | 0 |
Enclosure Name | Number of Adjacent Enclosures with Windows | Adjacent Enclosure Names - 1st 100 (max) | |
1 | PERIMETER_BOT_ZN_3 | 0 | |
2 | PERIMETER_BOT_ZN_2 | 0 | |
3 | PERIMETER_BOT_ZN_1 | 0 | |
4 | PERIMETER_BOT_ZN_4 | 0 | |
5 | PERIMETER_MID_ZN_3 | 0 | |
6 | PERIMETER_MID_ZN_2 | 0 | |
7 | PERIMETER_MID_ZN_1 | 0 | |
8 | PERIMETER_MID_ZN_4 | 0 | |
9 | PERIMETER_TOP_ZN_3 | 0 | |
10 | PERIMETER_TOP_ZN_2 | 0 | |
11 | PERIMETER_TOP_ZN_1 | 0 | |
12 | PERIMETER_TOP_ZN_4 | 0 |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | 1.1356 | 87921.3 | 0.496 | 7.5104E-002 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | BASEMENT_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
2 | BASEMENT_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
3 | BASEMENT_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
4 | BASEMENT_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
5 | BASEMENT_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
10 | BASEMENT_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 52.56 | -999.00 | 0 | No | No |
11 | CORE_BOT_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
12 | CORE_BOT_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
13 | CORE_BOT_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
14 | CORE_BOT_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
16 | CORE_BOT_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
17 | CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
18 | CORE_BOTTOM_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
19 | CORE_MID_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
20 | CORE_MID_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
21 | CORE_MID_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
22 | CORE_MID_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
23 | CORE_MID_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
24 | CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
25 | CORE_MID_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
26 | CORE_TOP_ZN_5_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
27 | CORE_TOP_ZN_5_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
28 | CORE_TOP_ZN_5_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
29 | CORE_TOP_ZN_5_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
30 | CORE_TOP_ZN_5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
31 | CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
32 | CORE_TOP_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 48.64 | -999.00 | 0 | No | No |
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
47 | PERIMETER_BOT_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
49 | PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
51 | PERIMETER_BOT_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
60 | PERIMETER_BOT_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
61 | PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
78 | PERIMETER_BOT_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
79 | PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
81 | PERIMETER_BOT_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
90 | PERIMETER_BOT_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
91 | PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
93 | PERIMETER_MID_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
95 | PERIMETER_MID_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
99 | PERIMETER_MID_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
100 | PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
102 | PERIMETER_MID_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
107 | PERIMETER_MID_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
108 | PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
110 | PERIMETER_MID_ZN_1_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
116 | PERIMETER_MID_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
117 | PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
119 | PERIMETER_MID_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
124 | PERIMETER_MID_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
125 | PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0 | 869.22 | 250.73 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
133 | PERIMETER_TOP_ZN_3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
134 | PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
136 | PERIMETER_TOP_ZN_2_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 0 | 579.48 | 250.73 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
141 | PERIMETER_TOP_ZN_2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
142 | PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 3 | No | No |
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 0 | 869.22 | 221.21 | 37.50 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 2 | No | No |
146 | INT-PER3S-NE | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
150 | PERIMETER_TOP_ZN_1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
151 | PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 73.11 | 8.07 | 0.43 | 0 | No | No |
153 | PERIMETER_TOP_ZN_4_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 3 | No | No |
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0 | 579.48 | 172.48 | 37.50 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 2 | No | No |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
158 | PERIMETER_TOP_ZN_4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
159 | PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 48.74 | 7.58 | 0.43 | 0 | No | No |
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
162 | GROUNDFLOOR_PLENUM_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
164 | GROUNDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
165 | iz-CORE_BOT_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
166 | iz-PERIMETER_BOT_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
167 | iz-PERIMETER_BOT_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
168 | iz-PERIMETER_BOT_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
169 | iz-PERIMETER_BOT_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
170 | iz-DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
171 | GROUNDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
172 | MIDFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
173 | MIDFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
174 | MIDFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
175 | MIDFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
176 | iz-CORE_MID_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
177 | iz-PERIMETER_MID_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
178 | iz-PERIMETER_MID_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
179 | iz-PERIMETER_MID_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
180 | iz-PERIMETER_MID_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
181 | iz-DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
182 | MIDFLOOR_PLENUM_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
183 | TOPFLOOR_PLENUM_WALL_NORTH | 0 | 869.22 | 221.21 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
184 | TOPFLOOR_PLENUM_WALL_EAST | 0 | 579.48 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
185 | TOPFLOOR_PLENUM_WALL_WEST | 0 | 579.48 | 172.48 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
186 | TOPFLOOR_PLENUM_WALL_SOUTH | 0 | 869.22 | 250.73 | 37.50 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
187 | iz-CORE_TOP_ZN_5_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
188 | iz-PERIMETER_TOP_ZN_3_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
189 | iz-PERIMETER_TOP_ZN_2_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
190 | iz-PERIMETER_TOP_ZN_1_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
191 | iz-PERIMETER_TOP_ZN_4_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
192 | iz-DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
193 | BUILDING_ROOF | 0 | 3563.11 | 268.06 | 0.00 | 0 | 1.22 | 243.69 | 58.49 | 0.00 | 0 | No | No |
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
197 | DATACENTER_BOT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
198 | DATACENTER_BOT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
199 | DATACENTER_BOT_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
200 | DATACENTER_MID_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
202 | DATACENTER_MID_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
203 | DATACENTER_MID_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
204 | DATACENTER_MID_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
205 | DATACENTER_MID_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
206 | DATACENTER_TOP_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
207 | DATACENTER_TOP_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
210 | DATACENTER_TOP_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
211 | DATACENTER_TOP_ZN_6_CEILING | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.74 | 0.00 | 1.79 | -999.00 | 0 | No | No |
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | 0 | 0.00 | 0.00 | 0.00 | 0 | 2.44 | 0.00 | 24.18 | -999.00 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | PERIMETER_BOT_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | PERIMETER_BOT_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
3 | PERIMETER_BOT_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.482E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | PERIMETER_BOT_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_BOT_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.534E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
5 | PERIMETER_MID_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | PERIMETER_MID_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
7 | PERIMETER_MID_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | PERIMETER_MID_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_MID_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
9 | PERIMETER_TOP_ZN_3_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_3 | 313.41 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | PERIMETER_TOP_ZN_2_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_2 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
11 | PERIMETER_TOP_ZN_1_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_1 | 313.42 | 16.9 | 0.114 | 3.646E-004 | 5.696E-004 | 0.478 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | PERIMETER_TOP_ZN_4_INFILTRATION | INFIL_SCH_PNNL | PERIMETER_TOP_ZN_4 | 201.98 | 10.9 | 7.617E-002 | 3.771E-004 | 5.696E-004 | 0.495 | 0.000 | 0.000 | 0.224 | 0.000 |
13 | GROUNDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | GROUNDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | MIDFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | MIDFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 5.696E-004 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
15 | TOPFLOOR_PLENUM_INFILTRATION | INFIL_SCH_PNNL | TOPFLOOR_PLENUM | 3563.11 | 0.0 | 0.169 | 4.749E-005 | 4.384E-005 | 0.140 | 0.000 | 0.000 | 0.224 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | BASEMENT | Mixing/Well-Stirred |
2 | CORE_BOTTOM | Mixing/Well-Stirred |
3 | CORE_MID | Mixing/Well-Stirred |
4 | CORE_TOP | Mixing/Well-Stirred |
5 | PERIMETER_BOT_ZN_3 | Mixing/Well-Stirred |
6 | PERIMETER_BOT_ZN_2 | Mixing/Well-Stirred |
7 | PERIMETER_BOT_ZN_1 | Mixing/Well-Stirred |
8 | PERIMETER_BOT_ZN_4 | Mixing/Well-Stirred |
9 | PERIMETER_MID_ZN_3 | Mixing/Well-Stirred |
10 | PERIMETER_MID_ZN_2 | Mixing/Well-Stirred |
11 | PERIMETER_MID_ZN_1 | Mixing/Well-Stirred |
12 | PERIMETER_MID_ZN_4 | Mixing/Well-Stirred |
13 | PERIMETER_TOP_ZN_3 | Mixing/Well-Stirred |
14 | PERIMETER_TOP_ZN_2 | Mixing/Well-Stirred |
15 | PERIMETER_TOP_ZN_1 | Mixing/Well-Stirred |
16 | PERIMETER_TOP_ZN_4 | Mixing/Well-Stirred |
17 | GROUNDFLOOR_PLENUM | Mixing/Well-Stirred |
18 | MIDFLOOR_PLENUM | Mixing/Well-Stirred |
19 | TOPFLOOR_PLENUM | Mixing/Well-Stirred |
20 | DATACENTER_BOT_ZN_6 | Mixing/Well-Stirred |
21 | DATACENTER_MID_ZN_6 | Mixing/Well-Stirred |
22 | DATACENTER_TOP_ZN_6 | Mixing/Well-Stirred |
23 | DATACENTER_BASEMENT_ZN_6 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sizing Factor ID | Value | |
1 | Global | 1.0000 |
Sky Type | MonthAndDay | Daylighting Control Name | Enclosure Name | Window Name | Reference Point | Daylight Factor | |
1 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9395E-003 |
2 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9414E-003 |
3 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4423E-003 |
4 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4440E-003 |
5 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4020E-003 |
6 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4033E-003 |
7 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8674E-003 |
8 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8681E-003 |
9 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9840E-003 |
10 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1190E-003 |
11 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4804E-003 |
12 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.6002E-003 |
13 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4350E-003 |
14 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5326E-003 |
15 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8859E-003 |
16 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9330E-003 |
17 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1283 |
18 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 7.0708E-002 |
19 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 0.1463 |
20 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 8.0686E-002 |
21 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 9.4173E-002 |
22 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.9477E-002 |
23 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.9234E-002 |
24 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.3771E-002 |
25 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9842E-003 |
26 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.1185E-003 |
27 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4804E-003 |
28 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.5988E-003 |
29 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4350E-003 |
30 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.5326E-003 |
31 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8864E-003 |
32 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.9344E-003 |
33 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 4.9393E-003 |
34 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 4.9412E-003 |
35 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 5.4421E-003 |
36 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 5.4437E-003 |
37 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 3.4019E-003 |
38 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 3.4032E-003 |
39 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT1 | 1.8673E-003 |
40 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_1_DAYLCTRL | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | PERIMETER_BOT_ZN_1_DAYLREFPT2 | 1.8680E-003 |
41 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0715E-003 |
42 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.3331E-003 |
43 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.8397E-003 |
44 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.1270E-003 |
45 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6867E-003 |
46 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7997E-003 |
47 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1954E-003 |
48 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2279E-003 |
49 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.5753E-002 |
50 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.3719E-002 |
51 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.2307E-002 |
52 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.1247E-002 |
53 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.8412E-002 |
54 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 2.0528E-002 |
55 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 4.0350E-002 |
56 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 1.5085E-002 |
57 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.9862E-003 |
58 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 4.0778E-003 |
59 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.7285E-003 |
60 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.7948E-003 |
61 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.6502E-003 |
62 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.6754E-003 |
63 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT1 | 3.1955E-003 |
64 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_2_DAYLCTRL | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | PERIMETER_BOT_ZN_2_DAYLREFPT2 | 3.2284E-003 |
65 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9706E-003 |
66 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9724E-003 |
67 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6692E-003 |
68 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6706E-003 |
69 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4746E-003 |
70 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4757E-003 |
71 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
72 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8681E-003 |
73 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0110E-003 |
74 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1177E-003 |
75 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7019E-003 |
76 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7858E-003 |
77 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5009E-003 |
78 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5595E-003 |
79 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8864E-003 |
80 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9344E-003 |
81 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.1932E-002 |
82 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8577E-002 |
83 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4629E-002 |
84 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4053E-002 |
85 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.4897E-002 |
86 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 9.8789E-003 |
87 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 3.9234E-002 |
88 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.3767E-002 |
89 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 2.0103E-003 |
90 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 2.1146E-003 |
91 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.7015E-003 |
92 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.7838E-003 |
93 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.5009E-003 |
94 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.5595E-003 |
95 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8860E-003 |
96 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9331E-003 |
97 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.9705E-003 |
98 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.9723E-003 |
99 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.6691E-003 |
100 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.6706E-003 |
101 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.4746E-003 |
102 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.4757E-003 |
103 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT1 | 1.8674E-003 |
104 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_3_DAYLCTRL | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | PERIMETER_BOT_ZN_3_DAYLREFPT2 | 1.8680E-003 |
105 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0479E-003 |
106 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.1391E-003 |
107 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.8062E-003 |
108 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8722E-003 |
109 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.6981E-003 |
110 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.7236E-003 |
111 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1956E-003 |
112 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2284E-003 |
113 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.6934E-002 |
114 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.4205E-002 |
115 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.3781E-002 |
116 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.1855E-002 |
117 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.9398E-002 |
118 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 2.0934E-002 |
119 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.0350E-002 |
120 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 1.5085E-002 |
121 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 4.1361E-003 |
122 | Clear Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.4088E-003 |
123 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.9210E-003 |
124 | Clear Turbid Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 4.2226E-003 |
125 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.7347E-003 |
126 | Intermediate Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.8495E-003 |
127 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT1 | 3.1954E-003 |
128 | Overcast Sky | 12/21 | PERIMETER_BOT_ZN_4_DAYLCTRL | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | PERIMETER_BOT_ZN_4_DAYLREFPT2 | 3.2278E-003 |
129 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1171 |
130 | Clear Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 8.7384E-002 |
131 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 0.1288 |
132 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 9.8223E-002 |
133 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 9.8058E-002 |
134 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 5.3551E-002 |
135 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT1 | 4.5331E-002 |
136 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_1_DAYLCTRL | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_MID_ZN_1_DAYLREFPT2 | 2.1963E-002 |
137 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.2763E-002 |
138 | Clear Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 3.2750E-002 |
139 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.9016E-002 |
140 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.9821E-002 |
141 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 5.4983E-002 |
142 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.8673E-002 |
143 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT1 | 4.6386E-002 |
144 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_2_DAYLCTRL | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | PERIMETER_MID_ZN_2_DAYLREFPT2 | 2.2195E-002 |
145 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.7991E-002 |
146 | Clear Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.6893E-002 |
147 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0053E-002 |
148 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1164E-002 |
149 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 3.0294E-002 |
150 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 1.6418E-002 |
151 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT1 | 4.5332E-002 |
152 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_3_DAYLCTRL | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | PERIMETER_MID_ZN_3_DAYLREFPT2 | 2.1959E-002 |
153 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.4045E-002 |
154 | Clear Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.3389E-002 |
155 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.0617E-002 |
156 | Clear Turbid Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 3.0621E-002 |
157 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 5.6041E-002 |
158 | Intermediate Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.9184E-002 |
159 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT1 | 4.6386E-002 |
160 | Overcast Sky | 12/21 | PERIMETER_MID_ZN_4_DAYLCTRL | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | PERIMETER_MID_ZN_4_DAYLREFPT2 | 2.2195E-002 |
161 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1169 |
162 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 8.7489E-002 |
163 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 0.1286 |
164 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 9.8351E-002 |
165 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 9.8065E-002 |
166 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 5.3656E-002 |
167 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT1 | 4.5383E-002 |
168 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_1_DAYLCTRL | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | PERIMETER_TOP_ZN_1_DAYLREFPT2 | 2.2005E-002 |
169 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.2727E-002 |
170 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 3.2777E-002 |
171 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.8992E-002 |
172 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.9848E-002 |
173 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 5.4998E-002 |
174 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.8721E-002 |
175 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT1 | 4.6435E-002 |
176 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_2_DAYLCTRL | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | PERIMETER_TOP_ZN_2_DAYLREFPT2 | 2.2237E-002 |
177 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.7940E-002 |
178 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.6903E-002 |
179 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0018E-002 |
180 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.1173E-002 |
181 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 3.0309E-002 |
182 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 1.6442E-002 |
183 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT1 | 4.5383E-002 |
184 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_3_DAYLCTRL | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | PERIMETER_TOP_ZN_3_DAYLREFPT2 | 2.2001E-002 |
185 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.4009E-002 |
186 | Clear Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.3417E-002 |
187 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.0593E-002 |
188 | Clear Turbid Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 3.0650E-002 |
189 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 5.6056E-002 |
190 | Intermediate Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.9233E-002 |
191 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT1 | 4.6435E-002 |
192 | Overcast Sky | 12/21 | PERIMETER_TOP_ZN_4_DAYLCTRL | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | PERIMETER_TOP_ZN_4_DAYLREFPT2 | 2.2237E-002 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | BASEMENT | Cooling | 72212.34449 | 72212.34449 | 6.42605 | 6.42605 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
2 | BASEMENT | Heating | 0.00000 | 0.00000 | 0.00000 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | -17.90000 | 9.55238E-004 | 2779.42662 | 149.60210 | 1.20016 | 0.00000 |
3 | CORE_BOTTOM | Cooling | 77202.51077 | 77202.51077 | 6.86972 | 6.86972 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
4 | CORE_BOTTOM | Heating | 190.34407 | 190.34407 | 1.00288E-002 | 1.07782 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
5 | CORE_MID | Cooling | 725561.77930 | 725561.77930 | 64.54810 | 64.54810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 22.94800 | 5.45871E-003 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
6 | CORE_MID | Heating | 298284.18731 | 298284.18731 | 15.54900 | 15.54900 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 10.77825 | 0.00000 |
7 | CORE_TOP | Cooling | 71328.84975 | 71328.84975 | 6.40219 | 6.40219 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
8 | CORE_TOP | Heating | 69446.23327 | 69446.23327 | 3.64090 | 3.64090 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 2496.12046 | 134.35320 | 1.07782 | 0.00000 |
9 | PERIMETER_BOT_ZN_3 | Cooling | 12464.37141 | 12464.37141 | 1.11872 | 1.11872 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
10 | PERIMETER_BOT_ZN_3 | Heating | 10688.83390 | 10688.83390 | 0.56088 | 0.56088 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
11 | PERIMETER_BOT_ZN_2 | Cooling | 14912.06596 | 14912.06596 | 1.33838 | 1.33838 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 23.88533 | 5.46009E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
12 | PERIMETER_BOT_ZN_2 | Heating | 7560.64007 | 7560.64007 | 0.39686 | 0.39686 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
13 | PERIMETER_BOT_ZN_1 | Cooling | 17052.96075 | 17052.96075 | 1.53056 | 1.53056 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 33.28333 | 5.47432E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
14 | PERIMETER_BOT_ZN_1 | Heating | 12282.05594 | 12282.05594 | 0.64477 | 0.64477 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
15 | PERIMETER_BOT_ZN_4 | Cooling | 19182.27946 | 19182.27946 | 1.72166 | 1.72166 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 32.02533 | 5.47238E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
16 | PERIMETER_BOT_ZN_4 | Heating | 5832.33093 | 5832.33093 | 0.30582 | 0.30582 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
17 | PERIMETER_MID_ZN_3 | Cooling | 116655.20077 | 116655.20077 | 10.47005 | 10.47005 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 33.90000 | 5.47527E-003 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
18 | PERIMETER_MID_ZN_3 | Heating | 169086.69281 | 169086.69281 | 8.88380 | 8.88380 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 1.35332 | 0.00000 |
19 | PERIMETER_MID_ZN_2 | Cooling | 156500.25879 | 156500.25879 | 14.04610 | 14.04610 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25.76000 | 5.46288E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
20 | PERIMETER_MID_ZN_2 | Heating | 113425.68843 | 113425.68843 | 5.95989 | 5.95989 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
21 | PERIMETER_MID_ZN_1 | Cooling | 166146.88616 | 166146.88616 | 14.91199 | 14.91199 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 33.40667 | 5.47451E-003 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
22 | PERIMETER_MID_ZN_1 | Heating | 170942.19082 | 170942.19082 | 8.98151 | 8.98151 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 1.35335 | 0.00000 |
23 | PERIMETER_MID_ZN_4 | Cooling | 172087.18294 | 172087.18294 | 15.44505 | 15.44505 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
24 | PERIMETER_MID_ZN_4 | Heating | 108709.44718 | 108709.44718 | 5.71159 | 5.71159 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 0.87213 | 0.00000 |
25 | PERIMETER_TOP_ZN_3 | Cooling | 13458.22698 | 13458.22698 | 1.20790 | 1.20790 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 33.75200 | 5.47504E-003 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
26 | PERIMETER_TOP_ZN_3 | Heating | 22280.80506 | 22280.80506 | 1.17122 | 1.17122 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41284 | 16.86939 | 0.13533 | 0.00000 |
27 | PERIMETER_TOP_ZN_2 | Cooling | 15717.24449 | 15717.24449 | 1.41063 | 1.41063 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 26.59867 | 5.46414E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
28 | PERIMETER_TOP_ZN_2 | Heating | 14848.92042 | 14848.92042 | 0.78059 | 0.78059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
29 | PERIMETER_TOP_ZN_1 | Cooling | 18291.16780 | 18291.16780 | 1.64165 | 1.64165 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 33.65333 | 5.47489E-003 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
30 | PERIMETER_TOP_ZN_1 | Heating | 22508.65959 | 22508.65959 | 1.18322 | 1.18322 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 313.41969 | 16.86975 | 0.13533 | 0.00000 |
31 | PERIMETER_TOP_ZN_4 | Cooling | 18477.27388 | 18477.27388 | 1.65835 | 1.65835 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 31.82800 | 5.47208E-003 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
32 | PERIMETER_TOP_ZN_4 | Heating | 14531.55497 | 14531.55497 | 0.76389 | 0.76389 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | -17.90000 | 9.55238E-004 | 201.97515 | 10.87127 | 8.72129E-002 | 0.00000 |
33 | DATACENTER_BOT_ZN_6 | Cooling | 8413.80651 | 8413.80651 | 0.59564 | 0.59564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
34 | DATACENTER_BOT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
35 | DATACENTER_MID_ZN_6 | Cooling | 80480.98158 | 80480.98158 | 5.69752 | 5.69752 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 28.49800 | 5.46700E-003 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
36 | DATACENTER_MID_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 0.15632 | 0.00000 |
37 | DATACENTER_TOP_ZN_6 | Cooling | 8213.88456 | 8213.88456 | 0.58149 | 0.58149 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 28.86800 | 5.46756E-003 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
38 | DATACENTER_TOP_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | -17.90000 | 9.55238E-004 | 36.20274 | 1.94861 | 1.56323E-002 | 0.00000 |
39 | DATACENTER_BASEMENT_ZN_6 | Cooling | 371175.74206 | 371175.74206 | 26.27619 | 26.27619 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 20.43200 | 5.45503E-003 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
40 | DATACENTER_BASEMENT_ZN_6 | Heating | 0.00000 | 0.00000 | 0.00000 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | -17.90000 | 9.55238E-004 | 783.67941 | 42.18139 | 0.33839 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | VAV_BOT WITH REHEAT | Cooling | Sensible | 143237.43 | 11.17549 | 11.17549 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
2 | VAV_BOT WITH REHEAT | Heating | Sensible | 76531.67 | 2.98616 | 2.98616 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 |
3 | VAV_MID WITH REHEAT | Cooling | Sensible | 1318152.85 | 103.85145 | 103.85145 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
4 | VAV_MID WITH REHEAT | Heating | Sensible | 757574.02 | 45.08580 | 45.08580 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 |
5 | VAV_TOP WITH REHEAT | Cooling | Sensible | 150532.34 | 11.46009 | 11.46009 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 00:00:00 |
6 | VAV_TOP WITH REHEAT | Heating | Sensible | 76256.56 | 7.53982 | 7.53982 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 |
7 | CAV_BAS | Cooling | Sensible | 73347.41 | 6.42605 | 6.42605 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | CAV_BAS | Heating | Sensible | 68251.22 | 1.20016 | 1.20016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | AIRLOOP DATACENTER BASEMENT | Cooling | Sensible | 368296.77 | 26.27655 | 26.27655 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | AIRLOOP DATACENTER BASEMENT | Heating | Sensible | 19243.92 | 0.33839 | 0.33839 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | AIRLOOP DATACENTER BOT | Cooling | Sensible | 8332.54 | 0.59564 | 0.59564 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | AIRLOOP DATACENTER BOT | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | AIRLOOP DATACENTER MID | Cooling | Sensible | 79707.99 | 5.69752 | 5.69752 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | AIRLOOP DATACENTER MID | Heating | Sensible | 8889.90 | 0.15632 | 0.15632 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | AIRLOOP DATACENTER TOP | Cooling | Sensible | 8137.73 | 0.58149 | 0.58149 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | AIRLOOP DATACENTER TOP | Heating | Sensible | 888.99 | 1.56323E-002 | 1.56323E-002 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | BASEMENT DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 6.42605 |
2 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.86972 |
3 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.27687 |
4 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.29300 |
5 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.01283 |
6 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.73833 |
7 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
8 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.37608E-003 |
9 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.43919E-004 |
10 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 2.01283 |
11 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
12 | AirTerminal:SingleDuct:VAV:Reheat | CORE_BOTTOM VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
13 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 16450.84414 |
14 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.43919E-004 |
15 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 331.63621 |
16 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 64.54810 |
17 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29467 |
18 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.30500 |
19 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 19.68717 |
20 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.78579 |
21 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
22 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.29297E-003 |
23 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 4.01717E-003 |
24 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 19.68717 |
25 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
26 | AirTerminal:SingleDuct:VAV:Reheat | CORE_MID VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
27 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 459186.97533 |
28 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 4.01717E-003 |
29 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 11373.70822 |
30 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 6.40219 |
31 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.29709 |
32 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.31600 |
33 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.02309 |
34 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.79225 |
35 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
36 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.28243E-003 |
37 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 8.67873E-004 |
38 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 3.64090 |
39 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
40 | AirTerminal:SingleDuct:VAV:Reheat | CORE_TOP VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
41 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 99203.20504 |
42 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 8.67873E-004 |
43 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 2617.71842 |
44 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.11872 |
45 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.21348 |
46 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.22600 |
47 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25283 |
48 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.56927 |
49 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
50 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.78474E-003 |
51 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.33590E-004 |
52 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.56088 |
53 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
54 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
55 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 15270.18077 |
56 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.33590E-004 |
57 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 402.79458 |
58 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.33838 |
59 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.11499 |
60 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
61 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.26768 |
62 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30665 |
63 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
64 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.31322E-003 |
65 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 9.45050E-005 |
66 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.39686 |
67 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
68 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
69 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 10802.50657 |
70 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 9.45050E-005 |
71 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 284.91967 |
72 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.53056 |
73 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.15604 |
74 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
75 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.30611 |
76 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.41610 |
77 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
78 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.44170E-003 |
79 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.53529E-004 |
80 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.64477 |
81 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
82 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
83 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 17549.29481 |
84 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.53529E-004 |
85 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 462.85547 |
86 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.72166 |
87 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 8.93936E-002 |
88 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
89 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.34433 |
90 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
91 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
92 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.26205E-003 |
93 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 7.56225E-005 |
94 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.34433 |
95 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
96 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_BOT_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
97 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 8644.11992 |
98 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 7.56225E-005 |
99 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 220.21681 |
100 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 10.47005 |
101 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.22810 |
102 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.23600 |
103 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.47093 |
104 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.60826 |
105 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
106 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.67033E-003 |
107 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.11397E-003 |
108 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.88380 |
109 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
110 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
111 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 241639.40648 |
112 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.11397E-003 |
113 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6371.21977 |
114 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.04610 |
115 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10957 |
116 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
117 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.80922 |
118 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
119 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
120 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.47718E-003 |
121 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.41812E-003 |
122 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.95989 |
123 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
124 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
125 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 162099.27911 |
126 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.41812E-003 |
127 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4273.89603 |
128 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 14.91199 |
129 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.16016 |
130 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
131 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 2.98240 |
132 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.42709 |
133 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
134 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.37892E-003 |
135 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.13718E-003 |
136 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 8.98151 |
137 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
138 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
139 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 244293.37064 |
140 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.13718E-003 |
141 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 6441.15029 |
142 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 15.44505 |
143 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.96468E-002 |
144 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
145 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 3.08901 |
146 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
147 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
148 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.82350E-003 |
149 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.35910E-003 |
150 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 5.71159 |
151 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
152 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_MID_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
153 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 155353.90821 |
154 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.35910E-003 |
155 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 4096.14620 |
156 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.20790 |
157 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.19772 |
158 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.21000 |
159 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.25366 |
160 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.52724 |
161 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
162 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 1.92700E-003 |
163 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.78603E-004 |
164 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.17122 |
165 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
166 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_3 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
167 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 31845.98703 |
168 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.78603E-004 |
169 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 839.53743 |
170 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.41063 |
171 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.10910 |
172 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
173 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.28213 |
174 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
175 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
176 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 3.49210E-003 |
177 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.85676E-004 |
178 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.78059 |
179 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
180 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_2 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
181 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 21223.88752 |
182 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.85676E-004 |
183 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 559.50318 |
184 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.64165 |
185 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 0.14548 |
186 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
187 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.32833 |
188 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.38794 |
189 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
190 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 2.61894E-003 |
191 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 2.81454E-004 |
192 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 1.18322 |
193 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
194 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_1 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
195 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 32171.87966 |
196 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.81454E-004 |
197 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 848.12463 |
198 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Air Flow Rate [m3/s] | 1.65835 |
199 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Constant Minimum Air Flow Fraction | 9.28062E-002 |
200 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Constant Minimum Air Flow Fraction | 0.20000 |
201 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Minimum Air Flow Rate [m3/s] | 0.33167 |
202 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow Fraction during Reheat [] | 0.30000 |
203 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | User-Specified Maximum Flow Fraction during Reheat [] | 0.50000 |
204 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Flow per Zone Floor Area during Reheat [m3/s-m2] | 4.10533E-003 |
205 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Maximum Reheat Water Flow Rate [m3/s] | 1.81705E-004 |
206 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Air Volume Flow Rate [m3/s] | 0.76389 |
207 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Temperature [C] | 12.80000 |
208 | AirTerminal:SingleDuct:VAV:Reheat | PERIMETER_TOP_ZN_4 VAV BOX COMPONENT | Design Size Reheat Coil Sizing Inlet Air Humidity Ratio [kgWater/kgDryAir] | 8.00000E-003 |
209 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Rated Capacity [W] | 20770.02426 |
210 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size Maximum Water Flow Rate [m3/s] | 1.81705E-004 |
211 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Design Size U-Factor Times Area Value [W/K] | 547.54233 |
212 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BOT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.59564 |
213 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_MID_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 5.69752 |
214 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_TOP_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.58149 |
215 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | DATACENTER_BASEMENT_ZN_6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 26.27619 |
216 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.28951 |
217 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.18378 |
218 | AirLoopHVAC | VAV_BOT WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.57903 |
219 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 3.18378 |
220 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.17549 |
221 | AirLoopHVAC | VAV_BOT WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.17549 |
222 | AirLoopHVAC | VAV_BOT WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
223 | AirLoopHVAC | VAV_BOT WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.28489 |
224 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 59.71065 |
225 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 31.03873 |
226 | AirLoopHVAC | VAV_MID WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 119.42129 |
227 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 45.08580 |
228 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 103.85145 |
229 | AirLoopHVAC | VAV_MID WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 103.85145 |
230 | AirLoopHVAC | VAV_MID WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
231 | AirLoopHVAC | VAV_MID WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.43414 |
232 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.16036 |
233 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.21888 |
234 | AirLoopHVAC | VAV_TOP WITH REHEAT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 12.32073 |
235 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Heating Design Air Flow Rate [m3/s] | 7.53982 |
236 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Cooling Design Air Flow Rate [m3/s] | 11.46009 |
237 | AirLoopHVAC | VAV_TOP WITH REHEAT | Adjusted Main Design Air Flow Rate [m3/s] | 11.46009 |
238 | AirLoopHVAC | VAV_TOP WITH REHEAT | User Heating Air Flow Ratio [] | 0.30000 |
239 | AirLoopHVAC | VAV_TOP WITH REHEAT | Calculated Heating Air Flow Ratio [] | 0.65792 |
240 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 6.42605 |
241 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 6.42605 |
242 | AirLoopHVAC | CAV_BAS | Sum of Air Terminal Maximum Flow Rates [m3/s] | 6.42605 |
243 | AirLoopHVAC | CAV_BAS | Adjusted Heating Design Air Flow Rate [m3/s] | 6.42605 |
244 | AirLoopHVAC | CAV_BAS | Adjusted Cooling Design Air Flow Rate [m3/s] | 6.42605 |
245 | AirLoopHVAC | CAV_BAS | Adjusted Main Design Air Flow Rate [m3/s] | 6.42605 |
246 | AirLoopHVAC | CAV_BAS | User Heating Air Flow Ratio [] | 1.00000 |
247 | AirLoopHVAC | CAV_BAS | Calculated Heating Air Flow Ratio [] | 1.00000 |
248 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 26.27619 |
249 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 26.27619 |
250 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 26.27619 |
251 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Heating Design Air Flow Rate [m3/s] | 26.27619 |
252 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Cooling Design Air Flow Rate [m3/s] | 26.27655 |
253 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Adjusted Main Design Air Flow Rate [m3/s] | 26.27655 |
254 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | User Heating Air Flow Ratio [] | 1.00000 |
255 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Calculated Heating Air Flow Ratio [] | 0.99999 |
256 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.59564 |
257 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.59564 |
258 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.59564 |
259 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Heating Design Air Flow Rate [m3/s] | 0.59564 |
260 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.59564 |
261 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Adjusted Main Design Air Flow Rate [m3/s] | 0.59564 |
262 | AirLoopHVAC | AIRLOOP DATACENTER BOT | User Heating Air Flow Ratio [] | 1.00000 |
263 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Calculated Heating Air Flow Ratio [] | 1.00000 |
264 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 5.69752 |
265 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 5.69752 |
266 | AirLoopHVAC | AIRLOOP DATACENTER MID | Sum of Air Terminal Maximum Flow Rates [m3/s] | 5.69752 |
267 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Heating Design Air Flow Rate [m3/s] | 5.69752 |
268 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Cooling Design Air Flow Rate [m3/s] | 5.69752 |
269 | AirLoopHVAC | AIRLOOP DATACENTER MID | Adjusted Main Design Air Flow Rate [m3/s] | 5.69752 |
270 | AirLoopHVAC | AIRLOOP DATACENTER MID | User Heating Air Flow Ratio [] | 1.00000 |
271 | AirLoopHVAC | AIRLOOP DATACENTER MID | Calculated Heating Air Flow Ratio [] | 1.00000 |
272 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.58149 |
273 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.58149 |
274 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.58149 |
275 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Heating Design Air Flow Rate [m3/s] | 0.58149 |
276 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.58149 |
277 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Adjusted Main Design Air Flow Rate [m3/s] | 0.58149 |
278 | AirLoopHVAC | AIRLOOP DATACENTER TOP | User Heating Air Flow Ratio [] | 1.00000 |
279 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Calculated Heating Air Flow Ratio [] | 1.00000 |
280 | AirLoopHVAC | VAV_BOT WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.17549 |
281 | AirLoopHVAC | VAV_MID WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 103.85145 |
282 | AirLoopHVAC | VAV_TOP WITH REHEAT | Design Supply Air Flow Rate [m3/s] | 11.46009 |
283 | AirLoopHVAC | CAV_BAS | Design Supply Air Flow Rate [m3/s] | 6.42605 |
284 | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | Design Supply Air Flow Rate [m3/s] | 26.27655 |
285 | AirLoopHVAC | AIRLOOP DATACENTER BOT | Design Supply Air Flow Rate [m3/s] | 0.59564 |
286 | AirLoopHVAC | AIRLOOP DATACENTER MID | Design Supply Air Flow Rate [m3/s] | 5.69752 |
287 | AirLoopHVAC | AIRLOOP DATACENTER TOP | Design Supply Air Flow Rate [m3/s] | 0.58149 |
288 | Controller:OutdoorAir | VAV_BOT WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.17549 |
289 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.33037 |
290 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
291 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.51634 |
292 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.90538E-003 |
293 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.90538E-003 |
294 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 175795.71620 |
295 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.47876E-003 |
296 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.17549 |
297 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 69971.82426 |
298 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.12144E-004 |
299 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1120.01440 |
300 | Fan:VariableVolume | VAV_BOT WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.17549 |
301 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.47876E-003 |
302 | Controller:WaterCoil | VAV_BOT WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.36724E-005 |
303 | Controller:WaterCoil | VAV_BOT WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.12144E-004 |
304 | Controller:OutdoorAir | VAV_MID WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 103.85145 |
305 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.57903 |
306 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
307 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.51621 |
308 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87377E-003 |
309 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.87377E-003 |
310 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 1659236.14999 |
311 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.05877E-002 |
312 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 103.85145 |
313 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 730417.80809 |
314 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.39001E-003 |
315 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 11536.81124 |
316 | Fan:VariableVolume | VAV_MID WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 103.85145 |
317 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.05877E-002 |
318 | Controller:WaterCoil | VAV_MID WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.74608E-006 |
319 | Controller:WaterCoil | VAV_MID WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.39001E-003 |
320 | Controller:OutdoorAir | VAV_TOP WITH REHEAT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 11.46009 |
321 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Temperature [C] | 26.19531 |
322 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
323 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Temperature [C] | 10.51632 |
324 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 6.90081E-003 |
325 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 6.90081E-003 |
326 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Coil Load [W] | 178731.62861 |
327 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 7.60366E-003 |
328 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 11.46009 |
329 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Rated Capacity [W] | 72225.49204 |
330 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 6.31860E-004 |
331 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 1154.88439 |
332 | Fan:VariableVolume | VAV_TOP WITH REHEAT FAN | Design Size Maximum Flow Rate [m3/s] | 11.46009 |
333 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 7.60366E-003 |
334 | Controller:WaterCoil | VAV_TOP WITH REHEAT_COOLC_CONTROLLER | Controller Convergence Tolerance | 6.26265E-005 |
335 | Controller:WaterCoil | VAV_TOP WITH REHEAT_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 6.31860E-004 |
336 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 6.42605 |
337 | Controller:OutdoorAir | CAV_BAS_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.20016 |
338 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Temperature [C] | 25.93202 |
339 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Water Temperature [C] | 6.67000 |
340 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Temperature [C] | 11.09594 |
341 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Inlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09832E-003 |
342 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Outlet Air Humidity Ratio [kgWater/kgDryAir] | 7.09832E-003 |
343 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Coil Load [W] | 94867.02880 |
344 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Water Flow Rate [m3/s] | 4.03586E-003 |
345 | Coil:Cooling:Water | CAV_BAS COOLING COIL | Design Size Design Air Flow Rate [m3/s] | 6.42605 |
346 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Rated Capacity [W] | 273563.32163 |
347 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size Maximum Water Flow Rate [m3/s] | 2.39325E-003 |
348 | Coil:Heating:Water | CAV_BAS HEATING COIL | Design Size U-Factor Times Area Value [W/K] | 5951.54713 |
349 | Fan:ConstantVolume | CAV_BAS FAN | Design Size Maximum Flow Rate [m3/s] | 6.42605 |
350 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Maximum Actuated Flow [m3/s] | 4.03586E-003 |
351 | Controller:WaterCoil | CAV_BAS_COOLC_CONTROLLER | Controller Convergence Tolerance | 1.17990E-004 |
352 | Controller:WaterCoil | CAV_BAS_HEATC_CONTROLLER | Maximum Actuated Flow [m3/s] | 2.39325E-003 |
353 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 26.27655 |
354 | Controller:OutdoorAir | AIRLOOP DATACENTER BASEMENT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.33839 |
355 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.27655 |
356 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 476647.15072 |
357 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 249789.48542 |
358 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16731E-002 |
359 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 26.27655 |
360 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 26.27655 |
361 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 26.27655 |
362 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 26.27655 |
363 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 476647.15072 |
364 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 476647.15072 |
365 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 19243.92393 |
366 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BASEMENT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
367 | Fan:OnOff | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 26.27655 |
368 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 26.27655 |
369 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Heating Capacity [W] | 476647.15072 |
370 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BASEMENT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 1.16731E-002 |
371 | Coil:Heating:Electric | AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 19243.92393 |
372 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Nominal Capacity Volume [m3/s] | 1.74695E-004 |
373 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Nominal Capacity Volume [m3/s] | 3.72000E-005 |
374 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | Design Size Rated Power [W] | 96450.69782 |
375 | Humidifier:Steam:Electric | DATACENTER_BASEMENT_ZN_6 HUMIDIFIER | User-Specified Rated Power [W] | 100000.00000 |
376 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.59564 |
377 | Controller:OutdoorAir | AIRLOOP DATACENTER BOT_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
378 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59564 |
379 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10504.22342 |
380 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5559.88594 |
381 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.57248E-004 |
382 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.59564 |
383 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.59564 |
384 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.59564 |
385 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.59564 |
386 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10504.22342 |
387 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10504.22342 |
388 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
389 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER BOT DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
390 | Fan:OnOff | AIRLOOP DATACENTER BOT SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.59564 |
391 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.59564 |
392 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Heating Capacity [W] | 10504.22342 |
393 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER BOT HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.57248E-004 |
394 | Coil:Heating:Electric | AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
395 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 5.69752 |
396 | Controller:OutdoorAir | AIRLOOP DATACENTER MID_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.15632 |
397 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.69752 |
398 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 100513.41429 |
399 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 53190.89482 |
400 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.46157E-003 |
401 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 5.69752 |
402 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 5.69752 |
403 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 5.69752 |
404 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 5.69752 |
405 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Heating Capacity [W] | 100513.41429 |
406 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 100513.41429 |
407 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 8889.89563 |
408 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER MID DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
409 | Fan:OnOff | AIRLOOP DATACENTER MID SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 5.69752 |
410 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 5.69752 |
411 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Heating Capacity [W] | 100513.41429 |
412 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER MID HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.46157E-003 |
413 | Coil:Heating:Electric | AIRLOOP DATACENTER MID_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 8889.89563 |
414 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.58149 |
415 | Controller:OutdoorAir | AIRLOOP DATACENTER TOP_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 1.56323E-002 |
416 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58149 |
417 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Total Cooling Capacity [W] | 10256.74428 |
418 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Sensible Cooling Capacity [W] | 5428.26811 |
419 | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP COOLING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51187E-004 |
420 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate [m3/s] | 0.58149 |
421 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Heating Operation [m3/s] | 0.58149 |
422 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate During Cooling Operation [m3/s] | 0.58149 |
423 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supply Air Flow Rate When No Cooling or Heating is Needed [m3/s] | 0.58149 |
424 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Heating Capacity [W] | 10256.74428 |
425 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Nominal Cooling Capacity [W] | 10256.74428 |
426 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Supplemental Heating Coil Nominal Capacity [W] | 888.98956 |
427 | AirLoopHVAC:UnitaryHeatPump:WaterToAir | AIRLOOP DATACENTER TOP DXAC HEAT PUMP | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
428 | Fan:OnOff | AIRLOOP DATACENTER TOP SUPPLY FAN | Design Size Maximum Flow Rate [m3/s] | 0.58149 |
429 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Air Flow Rate [m3/s] | 0.58149 |
430 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Heating Capacity [W] | 10256.74428 |
431 | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AIRLOOP DATACENTER TOP HEATING COIL | Design Size Rated Water Flow Rate [m3/s] | 2.51187E-004 |
432 | Coil:Heating:Electric | AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Design Size Nominal Capacity [W] | 888.98956 |
433 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Flow Rate [m3/s] | 8.97060E-002 |
434 | Pump:VariableSpeed | COOLSYS1 PUMP SECONDARY | Design Power Consumption [W] | 18485.08528 |
435 | PlantLoop | COOLSYS1_DEMAND | Maximum Loop Flow Rate [m3/s] | 8.97060E-002 |
436 | PlantLoop | COOLSYS1_DEMAND | Plant Loop Volume [m3] | 10.76472 |
437 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Supply Side Design Fluid Flow Rate [m3/s] | 8.97060E-002 |
438 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop Demand Side Design Fluid Flow Rate [m3/s] | 8.97060E-002 |
439 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Heat Exchanger U-Factor Times Area Value [W/C] | 376541.16493 |
440 | HeatExchanger:FluidToFluid | BYPASS HEAT EXCHANGER | Loop-to-loop Temperature Difference Used to Size Heat Exchanger U-Factor Times Area Value [C] | 5.60000 |
441 | PlantLoop | HEATSYS1 | Maximum Loop Flow Rate [m3/s] | 2.34693E-002 |
442 | PlantLoop | HEATSYS1 | Plant Loop Volume [m3] | 2.81631 |
443 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Flow Rate [m3/s] | 2.34693E-002 |
444 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Power Consumption [W] | 7067.91767 |
445 | Pump:VariableSpeed | HEATSYS1 PUMP | Design Minimum Flow Rate [m3/s] | 0.00000 |
446 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Nominal Capacity [W] | 2682683.31551 |
447 | Boiler:HotWater | HEATSYS1 BOILER | User-Specified Nominal Capacity [W] | 2682683.32000 |
448 | Boiler:HotWater | HEATSYS1 BOILER | Design Size Design Water Flow Rate [m3/s] | 2.34693E-002 |
449 | PlantLoop | COOLSYS1_SUPPLY | Maximum Loop Flow Rate [m3/s] | 8.97060E-002 |
450 | PlantLoop | COOLSYS1_SUPPLY | Plant Loop Volume [m3] | 10.76472 |
451 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Flow Rate [m3/s] | 8.97060E-002 |
452 | Pump:ConstantSpeed | COOLSYS1 PUMP | Design Power Consumption [W] | 12797.84809 |
453 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.97060E-002 |
454 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.52109E-002 |
455 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Capacity [W] | 1065337.24264 |
456 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | User-Specified Reference Capacity [W] | 1070389.99500 |
457 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.29696E-002 |
458 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Chilled Water Flow Rate [m3/s] | 8.97060E-002 |
459 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Chilled Water Flow Rate [m3/s] | 4.52109E-002 |
460 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Capacity [W] | 1065337.24264 |
461 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | User-Specified Reference Capacity [W] | 1070389.99500 |
462 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | Design Size Reference Condenser Water Flow Rate [m3/s] | 5.29696E-002 |
463 | PlantLoop | SINGLE WATER PLANT LOOP | Maximum Loop Flow Rate [m3/s] | 1.46431E-002 |
464 | PlantLoop | SINGLE WATER PLANT LOOP | Plant Loop Volume [m3] | 1.75717 |
465 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Flow Rate [m3/s] | 1.46431E-002 |
466 | Pump:ConstantSpeed | PLANT CIRC PUMP | Design Power Consumption [W] | 3734.71253 |
467 | FluidCooler:TwoSpeed | CENTRAL TOWER | Design Water Flow Rate [m3/s] | 1.46431E-002 |
468 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at High Fan Speed [m3/s] | 139666.46671 |
469 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fluid cooler UA value at high fan speed based on nominal capacity input [W/K] | 54893.54367 |
470 | FluidCooler:TwoSpeed | CENTRAL TOWER | Air Flow Rate at Low Fan Speed [m3/s] | 69833.23335 |
471 | FluidCooler:TwoSpeed | CENTRAL TOWER | Fan Power at Low Fan Speed [W] | 7879.72339 |
472 | FluidCooler:TwoSpeed | CENTRAL TOWER | U-factor Times Area Value at Low Fan Speed [W/C] | 20946.66205 |
473 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [W] | 603168.53028 |
474 | Boiler:HotWater | CENTRAL BOILER | User-Specified Nominal Capacity [W] | 589384.81000 |
475 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [m3/s] | 1.46431E-002 |
476 | PlantLoop | SWHSYS1 | Maximum Loop Flow Rate [m3/s] | 4.40000E-004 |
477 | PlantLoop | SWHSYS1 | Plant Loop Volume [m3] | 5.28000E-002 |
478 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Flow Rate [m3/s] | 4.40000E-004 |
479 | Pump:ConstantSpeed | SWHSYS1 PUMP | Design Power Consumption [W] | 5.95776 |
480 | WaterHeater:Mixed | SWHSYS1 WATER HEATER | Use Side Design Flow Rate [m3/s] | 4.40000E-004 |
481 | CondenserLoop | TOWERWATERSYS | Maximum Loop Flow Rate [m3/s] | 0.10594 |
482 | CondenserLoop | TOWERWATERSYS | Condenser Loop Volume [m3] | 12.71271 |
483 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Flow Rate [m3/s] | 0.10594 |
484 | HeaderedPumps:VariableSpeed | TOWERWATERSYS PUMP | Design Power Consumption [W] | 31906.60171 |
485 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Design Air Flow Rate [m3/s] | 50.43994 |
486 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Nominal Capacity [W] | 1271610.55674 |
487 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Air Flow Rate in free convection regime [m3/s] | 10.08799 |
488 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 1 | Tower capacity in free convection regime at design conditions [W] | 158951.31959 |
489 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Design Air Flow Rate [m3/s] | 50.43994 |
490 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Nominal Capacity [W] | 1271610.55674 |
491 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Air Flow Rate in free convection regime [m3/s] | 10.08799 |
492 | CoolingTower:VariableSpeed | TOWERWATERSYS COOLTOWER 2 | Tower capacity in free convection regime at design conditions [W] | 158951.31959 |
493 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.50200E-002 |
494 | PlantEquipmentOperation:ComponentSetPoint | WSHPPLANT OPERATION SCHEME | Design Water Flow Rate [m3/s] Equipment # 47 | 5.50200E-002 |
Component Type | Name | Nominal Total Capacity {W} | |
1 | Coil:Heating:Water | CORE_BOTTOM VAV BOX REHEAT COIL | 15601.36 |
2 | Coil:Heating:Water | CORE_MID VAV BOX REHEAT COIL | 435144.87 |
3 | Coil:Heating:Water | CORE_TOP VAV BOX REHEAT COIL | 94038.80 |
4 | Coil:Heating:Water | PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | 14474.24 |
5 | Coil:Heating:Water | PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | 10239.26 |
6 | Coil:Heating:Water | PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | 16634.17 |
7 | Coil:Heating:Water | PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | 8190.93 |
8 | Coil:Heating:Water | PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | 229025.91 |
9 | Coil:Heating:Water | PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | 153636.95 |
10 | Coil:Heating:Water | PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | 231541.03 |
11 | Coil:Heating:Water | PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | 147244.39 |
12 | Coil:Heating:Water | PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | 30182.73 |
13 | Coil:Heating:Water | PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | 20115.33 |
14 | Coil:Heating:Water | PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | 30491.57 |
15 | Coil:Heating:Water | PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | 19685.20 |
16 | Coil:Heating:Water | VAV_BOT WITH REHEAT HEATING COIL | 50820.11 |
17 | Coil:Heating:Water | VAV_MID WITH REHEAT HEATING COIL | 515561.43 |
18 | Coil:Heating:Water | VAV_TOP WITH REHEAT HEATING COIL | 52364.37 |
19 | Coil:Heating:Water | CAV_BAS HEATING COIL | 211069.63 |
Component Type | Name | Nominal Total Capacity {W} | Nominal Sensible Capacity {W} | Nominal Latent Capacity {W} | Nominal Sensible Heat Ratio | Nominal Coil UA Value {W/C} | Nominal Coil Surface Area {m2} | |
1 | Coil:Cooling:Water | VAV_BOT WITH REHEAT COOLING COIL | 240126.94 | 151191.37 | 88935.57 | 0.63 | 24872.01 | 252.27 |
2 | Coil:Cooling:Water | VAV_MID WITH REHEAT COOLING COIL | 2246814.76 | 1410889.76 | 835925.00 | 0.63 | 232092.91 | 2354.02 |
3 | Coil:Cooling:Water | VAV_TOP WITH REHEAT COOLING COIL | 245302.57 | 154681.16 | 90621.41 | 0.63 | 25446.79 | 258.10 |
4 | Coil:Cooling:Water | CAV_BAS COOLING COIL | 129999.18 | 83284.13 | 46715.05 | 0.64 | 12806.36 | 129.89 |
Component Type | Component Name | IPLV in SI Units {W/W} | IPLV in IP Units {Btu/W-h} | |
1 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER1 | 6.84 | 23.33 |
2 | Chiller:Electric:ReformulatedEIR | COOLSYS1 CHILLER2 | 6.84 | 23.33 |
Zone Name | # Surfaces | |
1 | BASEMENT | 10 |
2 | CORE_BOTTOM | 8 |
3 | CORE_MID | 7 |
4 | CORE_TOP | 7 |
5 | PERIMETER_BOT_ZN_3 | 18 |
6 | PERIMETER_BOT_ZN_2 | 12 |
7 | PERIMETER_BOT_ZN_1 | 18 |
8 | PERIMETER_BOT_ZN_4 | 12 |
9 | PERIMETER_MID_ZN_3 | 9 |
10 | PERIMETER_MID_ZN_2 | 8 |
11 | PERIMETER_MID_ZN_1 | 9 |
12 | PERIMETER_MID_ZN_4 | 8 |
13 | PERIMETER_TOP_ZN_3 | 9 |
14 | PERIMETER_TOP_ZN_2 | 8 |
15 | PERIMETER_TOP_ZN_1 | 9 |
16 | PERIMETER_TOP_ZN_4 | 8 |
17 | GROUNDFLOOR_PLENUM | 11 |
18 | MIDFLOOR_PLENUM | 11 |
19 | TOPFLOOR_PLENUM | 11 |
20 | DATACENTER_BOT_ZN_6 | 6 |
21 | DATACENTER_MID_ZN_6 | 6 |
22 | DATACENTER_TOP_ZN_6 | 6 |
23 | DATACENTER_BASEMENT_ZN_6 | 10 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | BASEMENT_WALL_EAST | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_EAST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | BASEMENT_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 180.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | BASEMENT_WALL_NORTH | Wall | CTF - ConductionTransferFunction | BASEMENT_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 139.09 | 139.09 | 139.09 | 0.00 | 90.00 | 57.03 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
4 | BASEMENT_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
5 | BASEMENT_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 2779.43 | 2779.43 | 2779.43 | 0.00 | 180.00 | 57.03 | 48.74 | 0.00 | BASEMENT_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
6 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
7 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 57.03 | 4.57 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
8 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 2076.77 | 2076.77 | 2076.77 | 180.00 | 0.00 | 52.45 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
9 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 250.34 | 250.34 | 250.34 | 180.00 | 0.00 | 52.45 | 4.57 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
10 | BASEMENT_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 7126.21 | 7126.21 | 7126.21 | 0.00 | 90.00 | 7126.21 | 1.00 | 0.00 | BASEMENT_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
11 | CORE_BOT_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
12 | CORE_BOT_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
13 | CORE_BOT_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
14 | CORE_BOT_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
15 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 419.30 | 419.30 | 419.30 | 0.00 | 180.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
16 | CORE_BOT_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2076.82 | 2076.82 | 2076.82 | 0.00 | 180.00 | 52.46 | 39.59 | 0.00 | CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
17 | CORE_BOT_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
18 | CORE_BOTTOM_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_BOTTOM_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
19 | CORE_MID_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
20 | CORE_MID_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | CORE_MID_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | CORE_MID_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
23 | CORE_MID_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
24 | CORE_MID_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
25 | CORE_MID_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_MID_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
26 | CORE_TOP_ZN_5_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
27 | CORE_TOP_ZN_5_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | CORE_TOP_ZN_5_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
29 | CORE_TOP_ZN_5_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
30 | CORE_TOP_ZN_5_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
31 | CORE_TOP_ZN_5_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 2496.12 | 2496.12 | 2496.12 | 180.00 | 0.00 | 63.05 | 39.59 | 0.00 | iz-CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
32 | CORE_TOP_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 5064.65 | 5064.65 | 5064.65 | 0.00 | 90.00 | 5064.65 | 1.00 | 0.00 | CORE_TOP_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
33 | PERIMETER_BOT_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
34 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
35 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
36 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
37 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
38 | PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | Window | PERIMETER_BOT_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 0.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
39 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
40 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
41 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
42 | PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | Door | PERIMETER_BOT_ZN_3_WALL_NORTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 0.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
43 | PERIMETER_BOT_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
45 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
47 | PERIMETER_BOT_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.34 | 250.34 | 250.34 | 0.00 | 180.00 | 52.46 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
48 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 11.51 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
49 | PERIMETER_BOT_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
50 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_BOT_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
51 | PERIMETER_BOT_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
52 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
54 | PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | Window | PERIMETER_BOT_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 90.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
55 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | Door | PERIMETER_BOT_ZN_2_WALL_EAST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 90.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
57 | PERIMETER_BOT_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
58 | CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
59 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
60 | PERIMETER_BOT_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
61 | PERIMETER_BOT_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
62 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
63 | PERIMETER_BOT_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 105.88 | 200.61 | 105.88 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
64 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
65 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
66 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | Window | PERIMETER_BOT_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 17.38 | 17.38 | 17.38 | 180.00 | 90.00 | 13.65 | 1.27 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
70 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
71 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
72 | PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | Door | PERIMETER_BOT_ZN_1_WALL_SOUTH | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 180.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
73 | PERIMETER_BOT_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
74 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
75 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
77 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 63.07 | 63.07 | 63.07 | 0.00 | 180.00 | 16.08 | 4.57 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
78 | PERIMETER_BOT_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 250.35 | 250.35 | 250.35 | 0.00 | 180.00 | 57.03 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
79 | PERIMETER_BOT_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
80 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_BOT_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
81 | PERIMETER_BOT_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 71.89 | 133.74 | 71.89 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
82 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
83 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
84 | PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | Window | PERIMETER_BOT_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 19.32 | 19.32 | 19.32 | 270.00 | 90.00 | 15.43 | 1.25 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
85 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
86 | PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | Door | PERIMETER_BOT_ZN_4_WALL_WEST | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 1.95 | 1.95 | 1.95 | 270.00 | 90.00 | 0.91 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
87 | PERIMETER_BOT_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
88 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
89 | PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_BOT_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
90 | PERIMETER_BOT_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
91 | PERIMETER_BOT_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
92 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_BOT_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
93 | PERIMETER_MID_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_MID_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
95 | PERIMETER_MID_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
96 | CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
97 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
99 | PERIMETER_MID_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
100 | PERIMETER_MID_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
101 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_MID_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
102 | PERIMETER_MID_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_MID_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
104 | PERIMETER_MID_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
106 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
107 | PERIMETER_MID_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
108 | PERIMETER_MID_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
109 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
110 | PERIMETER_MID_ZN_1_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
111 | PERIMETER_MID_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
112 | PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_MID_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
113 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
115 | CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | PERIMETER_MID_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | PERIMETER_MID_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_MID_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
119 | PERIMETER_MID_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
120 | PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_MID_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
121 | PERIMETER_MID_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
122 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
123 | PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_MID_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
124 | PERIMETER_MID_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
125 | PERIMETER_MID_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
126 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_MID_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
127 | PERIMETER_TOP_ZN_3_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 0.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
128 | PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | Window | PERIMETER_TOP_ZN_3_WALL_NORTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_NORTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 0.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
129 | PERIMETER_TOP_ZN_3_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
130 | CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 180.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
131 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
132 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
133 | PERIMETER_TOP_ZN_3_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
134 | PERIMETER_TOP_ZN_3_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.41 | 313.41 | 313.41 | 180.00 | 0.00 | 63.96 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
135 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.83 | 626.83 | 626.83 | 0.00 | 90.00 | 626.83 | 1.00 | 0.00 | PERIMETER_TOP_ZN_3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
136 | PERIMETER_TOP_ZN_2_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 90.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
137 | PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | Window | PERIMETER_TOP_ZN_2_WALL_EAST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_EAST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 90.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
138 | PERIMETER_TOP_ZN_2_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
139 | CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_EAST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
140 | INT-PER3S-NE-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 225.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
141 | PERIMETER_TOP_ZN_2_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
142 | PERIMETER_TOP_ZN_2_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 225.00 | 0.00 | 6.47 | 39.59 | 0.00 | iz-PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
143 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
144 | PERIMETER_TOP_ZN_1_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 113.68 | 200.61 | 113.68 | 180.00 | 90.00 | 73.11 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
145 | PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | Window | PERIMETER_TOP_ZN_1_WALL_SOUTH | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | N/A | 2.171 | No | 86.92 | 86.92 | 86.92 | 180.00 | 90.00 | 73.11 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
146 | INT-PER3S-NE | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | INT-PER3S-NE-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
147 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
148 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 315.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
149 | CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 173.00 | 173.00 | 173.00 | 0.00 | 90.00 | 63.05 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_SOUTH | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
150 | PERIMETER_TOP_ZN_1_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
151 | PERIMETER_TOP_ZN_1_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 313.42 | 313.42 | 313.42 | 180.00 | 0.00 | 73.11 | 6.47 | 0.00 | iz-PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
152 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 626.84 | 626.84 | 626.84 | 0.00 | 90.00 | 626.84 | 1.00 | 0.00 | PERIMETER_TOP_ZN_1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
153 | PERIMETER_TOP_ZN_4_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 75.79 | 133.74 | 75.79 | 270.00 | 90.00 | 48.74 | 2.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
154 | PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | Window | PERIMETER_TOP_ZN_4_WALL_WEST | Window5 Detailed Fenestration | WINDOW_U_0.3822_SHGC_WEST_0.38 | N/A | 2.171 | No | 57.95 | 57.95 | 57.95 | 270.00 | 90.00 | 48.74 | 1.19 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
155 | PERIMETER_TOP_ZN_4_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 135.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
156 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
157 | PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 17.75 | 17.75 | 17.75 | 45.00 | 90.00 | 6.47 | 2.74 | 0.00 | PERIMETER_TOP_ZN_3_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
158 | PERIMETER_TOP_ZN_4_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
159 | PERIMETER_TOP_ZN_4_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | iz-PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
160 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 403.95 | 403.95 | 403.95 | 0.00 | 90.00 | 403.95 | 1.00 | 0.00 | PERIMETER_TOP_ZN_4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
161 | GROUNDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
162 | GROUNDFLOOR_PLENUM_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
163 | GROUNDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
164 | GROUNDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 1.226 | 1.036 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
165 | iz-CORE_BOT_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_BOT_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
166 | iz-PERIMETER_BOT_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_BOT_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
167 | iz-PERIMETER_BOT_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
168 | iz-PERIMETER_BOT_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_BOT_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
169 | iz-PERIMETER_BOT_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_BOT_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
170 | iz-DATACENTER_BOT_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
171 | GROUNDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | GROUNDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
172 | MIDFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
173 | MIDFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
174 | MIDFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
175 | MIDFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_MID | 1.149 | 0.981 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
176 | iz-CORE_MID_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_MID_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
177 | iz-PERIMETER_MID_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_MID_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
178 | iz-PERIMETER_MID_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_MID_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
179 | iz-PERIMETER_MID_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_MID_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
180 | iz-PERIMETER_MID_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_MID_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
181 | iz-DATACENTER_MID_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
182 | MIDFLOOR_PLENUM_CEILING | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | MIDFLOOR_PLENUM_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
183 | TOPFLOOR_PLENUM_WALL_NORTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 180.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
184 | TOPFLOOR_PLENUM_WALL_EAST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 90.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
185 | TOPFLOOR_PLENUM_WALL_WEST | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 59.42 | 59.42 | 59.42 | 270.00 | 90.00 | 48.74 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
186 | TOPFLOOR_PLENUM_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_TOP | 1.571 | 1.272 | 89.13 | 89.13 | 89.13 | 0.00 | 90.00 | 73.11 | 1.22 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
187 | iz-CORE_TOP_ZN_5_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 2496.12 | 2496.12 | 2496.12 | 0.00 | 180.00 | 63.05 | 39.59 | 0.00 | CORE_TOP_ZN_5_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
188 | iz-PERIMETER_TOP_ZN_3_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.41 | 313.41 | 313.41 | 0.00 | 180.00 | 63.96 | 6.47 | 0.00 | PERIMETER_TOP_ZN_3_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
189 | iz-PERIMETER_TOP_ZN_2_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 45.00 | 180.00 | 6.47 | 48.74 | 0.00 | PERIMETER_TOP_ZN_2_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
190 | iz-PERIMETER_TOP_ZN_1_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 313.42 | 313.42 | 313.42 | 0.00 | 180.00 | 73.11 | 6.47 | 0.00 | PERIMETER_TOP_ZN_1_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
191 | iz-PERIMETER_TOP_ZN_4_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 201.98 | 201.98 | 201.98 | 315.00 | 180.00 | 6.47 | 39.59 | 0.00 | PERIMETER_TOP_ZN_4_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
192 | iz-DATACENTER_TOP_ZN_6_CEILING | Floor | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.147 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
193 | BUILDING_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.186 | 0.180 | 3563.11 | 3563.11 | 3563.11 | 180.00 | 0.00 | 73.11 | 48.74 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
194 | DATACENTER_BOT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
195 | DATACENTER_BOT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
196 | DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_BOT_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
197 | DATACENTER_BOT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
198 | DATACENTER_BOT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
199 | DATACENTER_BOT_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_BOT_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
200 | DATACENTER_MID_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
201 | DATACENTER_MID_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
202 | DATACENTER_MID_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_MID_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
203 | DATACENTER_MID_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
204 | DATACENTER_MID_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_MID_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
205 | DATACENTER_MID_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_MID_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
206 | DATACENTER_TOP_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 90.00 | 90.00 | 39.59 | 2.74 | 0.00 | CORE_TOP_ZN_5_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
207 | DATACENTER_TOP_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 108.64 | 108.64 | 108.64 | 270.00 | 90.00 | 39.59 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
208 | DATACENTER_TOP_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 180.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
209 | DATACENTER_TOP_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 2.51 | 2.51 | 2.51 | 0.00 | 90.00 | 0.91 | 2.74 | 0.00 | DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
210 | DATACENTER_TOP_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | INT_SLAB_FLOOR | 3.839 | 1.986 | 36.20 | 36.20 | 36.20 | 0.00 | 180.00 | 0.91 | 39.59 | 0.00 | DATACENTER_TOP_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
211 | DATACENTER_TOP_ZN_6_CEILING | Roof | CTF - ConductionTransferFunction | DROPCEILING | 4.488 | 2.432 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | iz-DATACENTER_TOP_ZN_6_CEILING | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
212 | DATACENTER_BASEMENT_ZN_6_WALL_NORTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 0.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
213 | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 0.419 | 0.394 | 39.22 | 39.22 | 39.22 | 180.00 | 90.00 | 16.08 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
214 | DATACENTER_BASEMENT_ZN_6_WALL_WEST | Wall | CTF - ConductionTransferFunction | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 0.419 | 0.394 | 118.87 | 118.87 | 118.87 | 270.00 | 90.00 | 48.74 | 2.44 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
215 | DATACENTER_BASEMENT_ZN_6_WALL_EAST | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.87 | 118.87 | 118.87 | 90.00 | 90.00 | 48.74 | 2.44 | 0.00 | BASEMENT_WALL_WEST | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 0.50 | 0.50 | 4 | ||
216 | DATACENTER_BASEMENT_ZN_6_FLOOR | Floor | CTF - ConductionTransferFunction | EXT_SLAB_8IN_WITH_CARPET | 3.285 | 1.827 | 783.68 | 783.68 | 783.68 | 0.00 | 180.00 | 16.08 | 48.74 | 0.00 | DATACENTER_BASEMENT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.00 | 1.00 | 0.00 | 4 | ||
217 | DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 36.20 | 36.20 | 36.20 | 180.00 | 0.00 | 0.91 | 39.59 | 0.00 | DATACENTER_BOT_ZN_6_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
218 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 419.35 | 419.35 | 419.35 | 180.00 | 0.00 | 10.59 | 39.59 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
219 | PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 201.98 | 201.98 | 201.98 | 135.00 | 0.00 | 6.47 | 48.74 | 0.00 | PERIMETER_BOT_ZN_4_FLOOR | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
220 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.08 | 63.08 | 63.08 | 180.00 | 0.00 | 16.08 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
221 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | Roof | CTF - ConductionTransferFunction | INT_SLAB_CEILING | 3.839 | 2.228 | 63.07 | 63.07 | 63.07 | 180.00 | 0.00 | 11.51 | 6.47 | 0.00 | DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 1.00 | 0.00 | 1.00 | 4 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | BASEMENT | RunPeriod: RUNPERIOD 1 | 0.2498530238 | 0.1983502422 | Pass | Pass | 84.5364112736 | 391.1634191797 | Pass | Pass |
2 | CORE_BOTTOM | RunPeriod: RUNPERIOD 1 | 8.2204936791E-002 | 0.1603396410 | Pass | Pass | 0.1188657371 | 0.3230823634 | Pass | Pass |
3 | CORE_MID | RunPeriod: RUNPERIOD 1 | 4.1392129648E-002 | 8.8076377821E-002 | Pass | Pass | 9.0802026946E-002 | 0.2857235538 | Pass | Pass |
4 | CORE_TOP | RunPeriod: RUNPERIOD 1 | 5.5035667711E-002 | 4.0168056980E-002 | Pass | Pass | 0.5018822923 | 0.4909954641 | Pass | Pass |
5 | PERIMETER_BOT_ZN_3 | RunPeriod: RUNPERIOD 1 | 6.3981849557E-002 | 9.6656014925E-002 | Pass | Pass | 0.1185212224 | 0.3228288668 | Pass | Pass |
6 | PERIMETER_BOT_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1471472102 | 0.2216376636 | Pass | Pass | 0.1208084633 | 0.3269674230 | Pass | Pass |
7 | PERIMETER_BOT_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2123447352 | 0.3290499183 | Pass | Pass | 0.1288235206 | 0.3391622737 | Pass | Pass |
8 | PERIMETER_BOT_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1397099360 | 0.2426662319 | Pass | Pass | 0.1177939270 | 0.3166987083 | Pass | Pass |
9 | PERIMETER_MID_ZN_3 | RunPeriod: RUNPERIOD 1 | 3.2712343633E-002 | 3.2680911326E-002 | Pass | Pass | 9.0391759901E-002 | 0.2797400556 | Pass | Pass |
10 | PERIMETER_MID_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.1070920041 | 0.1466025295 | Pass | Pass | 9.2355856055E-002 | 0.2912292582 | Pass | Pass |
11 | PERIMETER_MID_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2182849670 | 0.3083728770 | Pass | Pass | 0.1139477791 | 0.3395681757 | Pass | Pass |
12 | PERIMETER_MID_ZN_4 | RunPeriod: RUNPERIOD 1 | 9.4666304583E-002 | 0.1365418491 | Pass | Pass | 8.8112371713E-002 | 0.2713954830 | Pass | Pass |
13 | PERIMETER_TOP_ZN_3 | RunPeriod: RUNPERIOD 1 | 0.3349854589 | 0.3425487270 | Pass | Pass | 17.7852507470 | 81.1698668048 | Pass | Pass |
14 | PERIMETER_TOP_ZN_2 | RunPeriod: RUNPERIOD 1 | 0.2181295692 | 0.2671458623 | Pass | Pass | 7.5447487648 | 35.4852794646 | Pass | Pass |
15 | PERIMETER_TOP_ZN_1 | RunPeriod: RUNPERIOD 1 | 0.2078523158 | 0.1931452525 | Pass | Pass | 0.6477277524 | 1.3612607464 | Pass | Pass |
16 | PERIMETER_TOP_ZN_4 | RunPeriod: RUNPERIOD 1 | 0.1583266261 | 0.1797101088 | Pass | Pass | 3.5540283136 | 27.7592678690 | Pass | Pass |
17 | GROUNDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.0061371713E-002 | 3.0417382456E-002 | Pass | Pass | 0.8735783266 | 4.0231675498 | Pass | Pass |
18 | MIDFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 2.5073482136E-002 | 3.8429461878E-002 | Pass | Pass | 0.1559074069 | 0.5147414636 | Pass | Pass |
19 | TOPFLOOR_PLENUM | RunPeriod: RUNPERIOD 1 | 0.1045783937 | 8.6968439604E-002 | Pass | Pass | 0.5385644587 | 0.5155442901 | Pass | Pass |
20 | DATACENTER_BOT_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.6348298608E-006 | 6.5731081382E-006 | Pass | Pass | 7.5576729188E-003 | 8.8032588289E-003 | Pass | Pass |
21 | DATACENTER_MID_ZN_6 | RunPeriod: RUNPERIOD 1 | 4.7842858808E-006 | 9.0650283052E-006 | Pass | Pass | 0.2844935988 | 1.5825025680 | Pass | Pass |
22 | DATACENTER_TOP_ZN_6 | RunPeriod: RUNPERIOD 1 | 5.2272551863E-002 | 4.9380486891E-002 | Pass | Pass | 7.7334497297E-003 | 1.1548210946E-002 | Pass | Pass |
23 | DATACENTER_BASEMENT_ZN_6 | RunPeriod: RUNPERIOD 1 | 2.1302542438E-006 | 3.4512338337E-006 | Pass | Pass | 6.0154826983E-005 | 1.0531551564E-004 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 8213.93 | 196.56 | 0.00 | 18564.74 | 22516.99 | 49492.21 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -17.90 | 0.00 | -17.90 | Wetbulb [C] | 2.50 | 180.00 |
DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 33.90 | 14.80 | 15.00 | Wetbulb [C] | 3.60 | 30.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 11.00 | 10 | |||
Feb | 15.00 | 16 | |||
Mar | 88.00 | 32 | |||
Apr | 159.00 | 54 | |||
May | 30.00 | 24 | |||
Jun | 11.00 | 4 | |||
Jul | 167.00 | 26 | |||
Aug | 33.00 | 24 | |||
Sep | 8.00 | 8 | |||
Oct | 13.00 | 10 | |||
Nov | 12.00 | 22 | |||
Dec | 11.00 | 18 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_EAST | BASEMENT_WALL_EAST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 90.00 | 90.00 | E |
BASEMENT_WALL_SOUTH | BASEMENT_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 180.00 | 90.00 | S |
BASEMENT_WALL_NORTH | BASEMENT_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 139.09 | 139.09 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_3_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_2_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 200.61 | 105.88 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_4_WALL_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 133.74 | 71.89 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_3_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_2_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 2006.06 | 1136.85 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_4_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 1337.37 | 757.90 | 270.00 | 90.00 | W |
PERIMETER_TOP_ZN_3_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_2_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_1_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 200.61 | 113.68 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_4_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 133.74 | 75.79 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 0.00 | 90.00 | N |
GROUNDFLOOR_PLENUM_WEST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 270.00 | 90.00 | W |
GROUNDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 89.13 | 89.13 | 180.00 | 90.00 | S |
GROUNDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_GRD | 0.30 | 1.036 | 1.226 | 59.42 | 59.42 | 90.00 | 90.00 | E |
MIDFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 0.00 | 90.00 | N |
MIDFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 270.00 | 90.00 | W |
MIDFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 891.32 | 891.32 | 180.00 | 90.00 | S |
MIDFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_MID | 0.30 | 0.981 | 1.149 | 594.21 | 594.21 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_NORTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 180.00 | 90.00 | S |
TOPFLOOR_PLENUM_WALL_EAST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 90.00 | 90.00 | E |
TOPFLOOR_PLENUM_WALL_WEST | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 59.42 | 59.42 | 270.00 | 90.00 | W |
TOPFLOOR_PLENUM_WALL_SOUTH | NONRES_EXT_WALL_TOP | 0.30 | 1.272 | 1.571 | 89.13 | 89.13 | 0.00 | 90.00 | N |
BUILDING_ROOF | NONRES_ROOF | 0.30 | 0.182 | 0.186 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_NORTH | DATACENTER_BASEMENT_ZN_6_WALL_NORTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6_WALL_SOUTH | DATACENTER_BASEMENT_ZN_6_WALL_SOUTH_CFACTOR | 1.00 | 0.399 | 0.419 | 39.22 | 39.22 | 180.00 | 90.00 | S |
DATACENTER_BASEMENT_ZN_6_WALL_WEST | DATACENTER_BASEMENT_ZN_6_WALL_WEST_CFACTOR | 1.00 | 0.399 | 0.419 | 118.87 | 118.87 | 270.00 | 90.00 | W |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
BASEMENT_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 270.00 | 90.00 | W |
BASEMENT_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 2779.43 | 2779.43 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_2_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 2076.77 | 2076.77 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 180.00 | 0.00 | |
CORE_BOT_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_BOT_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 419.30 | 419.30 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 2076.82 | 2076.82 | 0.00 | 180.00 | |
CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
CORE_MID_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
CORE_MID_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
CORE_MID_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 180.00 | 0.00 | |
CORE_TOP_ZN_5_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
CORE_TOP_ZN_5_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
CORE_TOP_ZN_5_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_BOT_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_BOT_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.34 | 250.34 | 0.00 | 180.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
PERIMETER_BOT_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_BOT_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
PERIMETER_BOT_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_BOT_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_BOT_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
DATACENTER_BASEMENT_ZN_6-PERIMETER_BOT_ZN_1-PPAUTOCREATEOTHER | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 250.35 | 250.35 | 0.00 | 180.00 | |
PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_BOT_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_BOT_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
PERIMETER_MID_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
CORE_MID_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
PERIMETER_MID_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
PERIMETER_MID_ZN_1_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 225.00 | 90.00 | W |
PERIMETER_MID_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 225.00 | 0.00 | |
PERIMETER_MID_ZN_1_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 315.00 | 90.00 | N |
CORE_MID_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1729.99 | 1729.99 | 0.00 | 90.00 | N |
PERIMETER_MID_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 180.00 | 0.00 | |
PERIMETER_MID_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 135.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
PERIMETER_MID_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 177.47 | 177.47 | 45.00 | 90.00 | E |
PERIMETER_MID_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 135.00 | 0.00 | |
PERIMETER_TOP_ZN_3_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
CORE_TOP_ZN_5_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_2_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
PERIMETER_TOP_ZN_3_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.41 | 313.41 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_2_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
INT-PER3S-NE-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 225.00 | 90.00 | W |
PERIMETER_TOP_ZN_2_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 45.00 | 180.00 | |
PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 225.00 | 0.00 | |
INT-PER3S-NE | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_4_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 315.00 | 90.00 | N |
CORE_TOP_ZN_5_WALL_SOUTH-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 173.00 | 173.00 | 0.00 | 90.00 | N |
PERIMETER_TOP_ZN_1_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 313.42 | 313.42 | 0.00 | 180.00 | |
PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 180.00 | 0.00 | |
PERIMETER_TOP_ZN_4_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 135.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
PERIMETER_TOP_ZN_3_WALL_WEST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 17.75 | 17.75 | 45.00 | 90.00 | E |
PERIMETER_TOP_ZN_4_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 201.98 | 201.98 | 315.00 | 180.00 | |
PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 135.00 | 0.00 | |
iz-CORE_BOT_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_BOT_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
GROUNDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 3563.11 | 3563.11 | 180.00 | 0.00 | |
iz-CORE_MID_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 24961.20 | 24961.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.13 | 3134.13 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 45.00 | 180.00 | |
iz-PERIMETER_MID_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 3134.20 | 3134.20 | 0.00 | 180.00 | |
iz-PERIMETER_MID_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2019.75 | 2019.75 | 315.00 | 180.00 | |
iz-DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 0.00 | 180.00 | |
MIDFLOOR_PLENUM_CEILING | INT_SLAB_CEILING | 0.30 | 2.104 | 3.839 | 35631.06 | 35631.06 | 180.00 | 0.00 | |
iz-CORE_TOP_ZN_5_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 2496.12 | 2496.12 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_3_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.41 | 313.41 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_2_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 45.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_1_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 313.42 | 313.42 | 0.00 | 180.00 | |
iz-PERIMETER_TOP_ZN_4_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 201.98 | 201.98 | 315.00 | 180.00 | |
iz-DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_BOT_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_BOT_ZN_6_WALL_EAST-PPAUTOCREATEOTHER | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_BOT_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_BOT_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_MID_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 270.00 | 90.00 | W |
DATACENTER_MID_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 180.00 | 90.00 | S |
DATACENTER_MID_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 1086.40 | 1086.40 | 90.00 | 90.00 | E |
DATACENTER_MID_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 25.09 | 25.09 | 0.00 | 90.00 | N |
DATACENTER_MID_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 362.03 | 362.03 | 0.00 | 180.00 | |
DATACENTER_MID_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 362.03 | 362.03 | 180.00 | 0.00 | |
DATACENTER_TOP_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 90.00 | 90.00 | E |
DATACENTER_TOP_ZN_6_WALL_WEST | INT_WALL | 0.30 | 2.511 | 6.299 | 108.64 | 108.64 | 270.00 | 90.00 | W |
DATACENTER_TOP_ZN_6_WALL_SOUTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 180.00 | 90.00 | S |
DATACENTER_TOP_ZN_6_WALL_NORTH | INT_WALL | 0.30 | 2.511 | 6.299 | 2.51 | 2.51 | 0.00 | 90.00 | N |
DATACENTER_TOP_ZN_6_FLOOR | INT_SLAB_FLOOR | 0.30 | 1.711 | 3.839 | 36.20 | 36.20 | 0.00 | 180.00 | |
DATACENTER_TOP_ZN_6_CEILING | DROPCEILING | 0.30 | 2.031 | 4.488 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_WALL_EAST | INT_WALL | 0.30 | 2.511 | 6.299 | 118.87 | 118.87 | 90.00 | 90.00 | E |
DATACENTER_BASEMENT_ZN_6_FLOOR | EXT_SLAB_8IN_WITH_CARPET | 0.30 | 1.591 | 3.285 | 783.68 | 783.68 | 0.00 | 180.00 | |
DATACENTER_BOT_ZN_6_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 36.20 | 36.20 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-CORE_BOT_ZN_5 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 419.35 | 419.35 | 180.00 | 0.00 | |
PERIMETER_BOT_ZN_4_FLOOR-PPAUTOCREATEOTHER | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 201.98 | 201.98 | 135.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_1 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.08 | 63.08 | 180.00 | 0.00 | |
DATACENTER_BASEMENT_ZN_6_CEILING-PERIMETER_BOT_ZN_3 | INT_SLAB_CEILING | 0.30 | 1.887 | 3.839 | 63.07 | 63.07 | 180.00 | 0.00 | |
BASEMENT_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 7126.21 | 0.00 | 90.00 | N | ||
CORE_BOTTOM_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
CORE_MID_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 50646.53 | 0.00 | 90.00 | N | ||
CORE_TOP_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 5064.65 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_BOT_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.26 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.50 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 6268.35 | 0.00 | 90.00 | N | ||
PERIMETER_MID_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 4039.48 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.83 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 626.84 | 0.00 | 90.00 | N | ||
PERIMETER_TOP_ZN_4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 403.95 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | WINDOW_U_0.3822_SHGC_EAST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 17.38 | 0.00 | 0.00 | 17.38 | 17.38 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | WINDOW_U_0.3822_SHGC_WEST_0.38 | 19.32 | 0.00 | 0.00 | 19.32 | 19.32 | 2.171 | 0.381 | 0.381 | No | PERIMETER_BOT_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 869.21 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 579.48 | 2.171 | 0.381 | 0.381 | No | PERIMETER_MID_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | WINDOW_U_0.3822_SHGC_NORTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_3_WALL_NORTH | 0.00 | 90.00 | N | |||||||
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | WINDOW_U_0.3822_SHGC_EAST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_2_WALL_EAST | 90.00 | 90.00 | E | |||||||
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | WINDOW_U_0.3822_SHGC_SOUTH_0.38 | 86.92 | 0.00 | 0.00 | 86.92 | 86.92 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_1_WALL_SOUTH | 180.00 | 90.00 | S | |||||||
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | WINDOW_U_0.3822_SHGC_WEST_0.38 | 57.95 | 0.00 | 0.00 | 57.95 | 57.95 | 2.171 | 0.381 | 0.381 | No | PERIMETER_TOP_ZN_4_WALL_WEST | 270.00 | 90.00 | W | |||||||
Total or Average | 3476.85 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
North Total or Average | 1043.06 | 2.171 | 0.381 | 0.381 | |||||||||||||||||
Non-North Total or Average | 2433.80 | 2.171 | 0.381 | 0.381 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_3_WALL_NORTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_3_WALL_NORTH |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_2_WALL_EAST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_2_WALL_EAST |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR3 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_1_WALL_SOUTH_DOOR4 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_1_WALL_SOUTH |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR1 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
PERIMETER_BOT_ZN_4_WALL_WEST_DOOR2 | SWINGING DOOR_CON | 1.598 | 2.101 | 1.95 | PERIMETER_BOT_ZN_4_WALL_WEST |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_MID_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 0.00 |
PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 | 0.00 | 0.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
BASEMENT_LIGHTS | BASEMENT | BASEMENT | GENERAL | 7.6202 | 2779.43 | 21179.74 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 177.74 |
CORE_BOTTOM_LIGHTS | CORE_BOTTOM | CORE_BOTTOM | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
CORE_MID_LIGHTS | CORE_MID | CORE_MID | GENERAL | 7.6202 | 24961.20 | 190208.95 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 1596.24 |
CORE_TOP_LIGHTS | CORE_TOP | CORE_TOP | GENERAL | 7.6202 | 2496.12 | 19020.89 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 159.62 |
PERIMETER_BOT_ZN_3_LIGHTS | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.90 | 0.0000 | Y | 13.85 |
PERIMETER_BOT_ZN_2_LIGHTS | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.89 | 0.0000 | Y | 8.93 |
PERIMETER_BOT_ZN_1_LIGHTS | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.67 | 0.0000 | Y | 13.75 |
PERIMETER_BOT_ZN_4_LIGHTS | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.67 | 0.0000 | Y | 8.86 |
PERIMETER_MID_ZN_3_LIGHTS | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3 | GENERAL | 7.6202 | 3134.13 | 23882.63 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.92 | 0.0000 | Y | 138.62 |
PERIMETER_MID_ZN_2_LIGHTS | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.90 | 0.0000 | Y | 89.28 |
PERIMETER_MID_ZN_1_LIGHTS | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1 | GENERAL | 7.6202 | 3134.20 | 23883.15 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.68 | 0.0000 | Y | 137.53 |
PERIMETER_MID_ZN_4_LIGHTS | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4 | GENERAL | 7.6202 | 2019.75 | 15390.88 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.67 | 0.0000 | Y | 88.62 |
PERIMETER_TOP_ZN_3_LIGHTS | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3 | GENERAL | 7.6202 | 313.41 | 2388.26 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.92 | 0.0000 | Y | 13.86 |
PERIMETER_TOP_ZN_2_LIGHTS | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.90 | 0.0000 | Y | 8.93 |
PERIMETER_TOP_ZN_1_LIGHTS | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1 | GENERAL | 7.6202 | 313.42 | 2388.32 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.68 | 0.0000 | Y | 13.75 |
PERIMETER_TOP_ZN_4_LIGHTS | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4 | GENERAL | 7.6202 | 201.98 | 1539.09 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 30.68 | 0.0000 | Y | 8.86 |
DATACENTER_BASEMENT_LIGHTS | DATACENTER_BASEMENT_ZN_6 | DATACENTER_BASEMENT_ZN_6 | GENERAL | 7.6202 | 783.68 | 5971.78 | LightsWired | LTG_SCH_OFFICE | 45.89 | 168.00 | 44.71 | 0.0000 | Y | 50.12 |
DATACENTER_BOT_LIGHTS | DATACENTER_BOT_ZN_6 | DATACENTER_BOT_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
DATACENTER_MID_LIGHTS | DATACENTER_MID_ZN_6 | DATACENTER_MID_ZN_6 | GENERAL | 12.5114 | 362.03 | 4529.48 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 46.40 |
DATACENTER_TOP_LIGHTS | DATACENTER_TOP_ZN_6 | DATACENTER_TOP_ZN_6 | GENERAL | 12.5114 | 36.20 | 452.95 | LightsWired | LTG_SCH_DATACENTER | 56.02 | 168.00 | 54.57 | 0.0000 | Y | 4.64 |
Interior Lighting Total | 7.6661 | 46320.38 | 355094.67 | 856.84 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
PERIMETER_BOT_ZN_1_DAYLREFPT1 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_BOT_ZN_1_DAYLREFPT2 | PERIMETER_BOT_ZN_1 | PERIMETER_BOT_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_BOT_ZN_2_DAYLREFPT1 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_2_DAYLREFPT2 | PERIMETER_BOT_ZN_2 | PERIMETER_BOT_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_BOT_ZN_3_DAYLREFPT1 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_BOT_ZN_3_DAYLREFPT2 | PERIMETER_BOT_ZN_3 | PERIMETER_BOT_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_BOT_ZN_4_DAYLREFPT1 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_BOT_ZN_4_DAYLREFPT2 | PERIMETER_BOT_ZN_4 | PERIMETER_BOT_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_1_DAYLREFPT1 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_MID_ZN_1_DAYLREFPT2 | PERIMETER_MID_ZN_1 | PERIMETER_MID_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_MID_ZN_2_DAYLREFPT1 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_2_DAYLREFPT2 | PERIMETER_MID_ZN_2 | PERIMETER_MID_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_MID_ZN_3_DAYLREFPT1 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_MID_ZN_3_DAYLREFPT2 | PERIMETER_MID_ZN_3 | PERIMETER_MID_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_MID_ZN_4_DAYLREFPT1 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_MID_ZN_4_DAYLREFPT2 | PERIMETER_MID_ZN_4 | PERIMETER_MID_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_1_DAYLREFPT1 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.32 | 921.17 |
PERIMETER_TOP_ZN_1_DAYLREFPT2 | PERIMETER_TOP_ZN_1 | PERIMETER_TOP_ZN_1_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.32 | 0.00 |
PERIMETER_TOP_ZN_2_DAYLREFPT1 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_2_DAYLREFPT2 | PERIMETER_TOP_ZN_2 | PERIMETER_TOP_ZN_2_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
PERIMETER_TOP_ZN_3_DAYLREFPT1 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 2388.26 | 921.15 |
PERIMETER_TOP_ZN_3_DAYLREFPT2 | PERIMETER_TOP_ZN_3 | PERIMETER_TOP_ZN_3_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 2388.26 | 0.00 |
PERIMETER_TOP_ZN_4_DAYLREFPT1 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.39 | 1539.09 | 593.63 |
PERIMETER_TOP_ZN_4_DAYLREFPT2 | PERIMETER_TOP_ZN_4 | PERIMETER_TOP_ZN_4_DAYLCTRL | SplitFlux | Continuous/Off | 0.00 | 1539.09 | 0.00 |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS_A | 9973.05 | AstronomicalClock | - | 42.26 | 42.26 | 79.12 | |
EXTERIOR_LIGHTS_B | 27638.03 | AstronomicalClock | - | 83.67 | 71.25 | 369.64 | |
Exterior Lighting Total | 37611.08 | 448.76 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
BYPASS HEAT EXCHANGER | HeatExchanger:FluidToFluid | 2103781.30 | |||||
HEATSYS1 BOILER | Boiler:HotWater | 2682683.32 | 0.81 | ||||
COOLSYS1 CHILLER1 | Chiller:Electric:ReformulatedEIR | 1070390.00 | 6.28 | 1024503.53 | 5.98 | 6.84 | 23.33 |
COOLSYS1 CHILLER2 | Chiller:Electric:ReformulatedEIR | 1070390.00 | 6.28 | 1024503.53 | 5.98 | 6.84 | 23.33 |
CENTRAL TOWER | FluidCooler:TwoSpeed | 582060.00 | |||||
CENTRAL BOILER | Boiler:HotWater | 589384.81 | 0.80 | ||||
TOWERWATERSYS COOLTOWER 1 | CoolingTower:VariableSpeed | 1271610.56 | |||||
TOWERWATERSYS COOLTOWER 2 | CoolingTower:VariableSpeed | 1271610.56 |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | 175795.72 | 240126.94 | 151191.37 | 88935.57 | 0.63 | - | 24872.01 | 252.27 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | 1659236.15 | 2246814.76 | 1410889.76 | 835925.00 | 0.63 | - | 232092.91 | 2354.02 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | 178731.63 | 245302.57 | 154681.16 | 90621.41 | 0.63 | - | 25446.79 | 258.10 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | 94867.03 | 129999.18 | 83284.13 | 46715.05 | 0.64 | - | 12806.36 | 129.89 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 476647.15 | 249789.49 | 226857.67 | 0.52 | 0.00 | |||
AIRLOOP DATACENTER BOT COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10504.22 | 5559.89 | 4944.34 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER MID COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 100513.41 | 53190.89 | 47322.52 | 0.53 | 0.00 | |||
AIRLOOP DATACENTER TOP COOLING COIL | Coil:Cooling:WaterToAirHeatPump:EquationFit | 10256.74 | 5428.27 | 4828.48 | 0.53 | 0.00 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
None |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
None |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | Coil:Heating:Water | 16450.84 | 15601.36 | - |
CORE_MID VAV BOX REHEAT COIL | Coil:Heating:Water | 459186.98 | 435144.87 | - |
CORE_TOP VAV BOX REHEAT COIL | Coil:Heating:Water | 99203.21 | 94038.80 | - |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 15270.18 | 14474.24 | - |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 10802.51 | 10239.26 | - |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 17549.29 | 16634.17 | - |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 8644.12 | 8190.93 | - |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 241639.41 | 229025.91 | - |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 162099.28 | 153636.95 | - |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 244293.37 | 231541.03 | - |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 155353.91 | 147244.39 | - |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | Coil:Heating:Water | 31845.99 | 30182.73 | - |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | Coil:Heating:Water | 21223.89 | 20115.33 | - |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | Coil:Heating:Water | 32171.88 | 30491.57 | - |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | Coil:Heating:Water | 20770.02 | 19685.20 | - |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | 69971.82 | 50820.11 | - |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | 730417.81 | 515561.43 | - |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | 72225.49 | 52364.37 | - |
CAV_BAS HEATING COIL | Coil:Heating:Water | 273563.32 | 211069.63 | - |
AIRLOOP DATACENTER BASEMENT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 476647.15 | 0.00 | |
AIRLOOP DATACENTER BOT HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10504.22 | 0.00 | |
AIRLOOP DATACENTER MID HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 100513.41 | 0.00 | |
AIRLOOP DATACENTER TOP HEATING COIL | Coil:Heating:WaterToAirHeatPump:EquationFit | 10256.74 | 0.00 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | 19243.92 | 1.00 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | 8889.90 | 1.00 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | 888.99 | 1.00 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.18 | 25386.18 | 2271.59 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 103.85 | 235908.26 | 2271.59 | 1.00 | 1.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 |
VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 0.61 | 1389.42 | 11.46 | 26032.66 | 2271.59 | 1.00 | 1.11 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 |
CAV_BAS FAN | Fan:ConstantVolume | 0.60 | 1018.41 | 6.43 | 10896.36 | 1695.65 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 0.62 | 1018.41 | 26.28 | 43154.82 | 1642.33 | 1.00 | 1.14 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 |
AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.60 | 667.18 | 1120.11 | 1.00 | 1.53 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 5.70 | 6381.83 | 1120.11 | 1.00 | 1.15 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.56 | 622.50 | 0.58 | 651.33 | 1120.11 | 1.00 | 1.54 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
COOLSYS1 PUMP SECONDARY | Pump:VariableSpeed | Intermittent | 133527.72 | 0.089706 | 18485.09 | 206062.94 | 0.90 | General |
HEATSYS1 PUMP | Pump:VariableSpeed | Intermittent | 180705.70 | 0.023469 | 7067.92 | 301156.09 | 0.90 | General |
COOLSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 92445.74 | 0.089706 | 12797.85 | 142664.32 | 0.90 | General |
PLANT CIRC PUMP | Pump:ConstantSpeed | Intermittent | 179045.11 | 0.014643 | 3734.71 | 255050.01 | 0.90 | General |
SWHSYS1 PUMP | Pump:ConstantSpeed | Intermittent | 3168.45 | 0.000440 | 5.96 | 13540.37 | 0.30 | General |
TOWERWATERSYS PUMP | HeaderedPumps:VariableSpeed | Intermittent | 180718.98 | 0.105939 | 31906.60 | 301178.23 | 0.90 | General |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
SWHSYS1 WATER HEATER | WaterHeater:Mixed | 1.14 | 87921.32 | 0.80 | 0.50 | 0.08 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 72212.34 | 72212.34 | 25.98 | 6.426 | 6.426 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00748 | 22.95 | 0.00546 | 1.200 | 0.00 |
CORE_BOTTOM | 77202.51 | 77202.51 | 30.93 | 6.870 | 6.870 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00740 | 22.95 | 0.00546 | 1.078 | 0.00 |
CORE_MID | 725561.78 | 725561.78 | 290.68 | 64.548 | 64.548 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 24.00 | 24.00 | 0.00743 | 22.95 | 0.00546 | 10.778 | 0.00 |
CORE_TOP | 71328.85 | 71328.85 | 28.58 | 6.402 | 6.402 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00743 | 33.90 | 0.00548 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 12464.37 | 12464.37 | 39.77 | 1.119 | 1.119 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 24.00 | 24.00 | 0.00727 | 33.90 | 0.00548 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 14912.07 | 14912.07 | 73.83 | 1.338 | 1.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:20:00 | 24.00 | 24.00 | 0.00715 | 23.89 | 0.00546 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 17052.96 | 17052.96 | 54.41 | 1.531 | 1.531 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | 24.00 | 24.00 | 0.00720 | 33.28 | 0.00547 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 19182.28 | 19182.28 | 94.97 | 1.722 | 1.722 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 16:50:00 | 24.00 | 24.00 | 0.00711 | 32.03 | 0.00547 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 116655.20 | 116655.20 | 372.21 | 10.470 | 10.470 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 24.00 | 24.00 | 0.00725 | 33.90 | 0.00548 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 156500.26 | 156500.26 | 774.85 | 14.046 | 14.046 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 24.00 | 24.00 | 0.00712 | 25.76 | 0.00546 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 166146.89 | 166146.89 | 530.11 | 14.912 | 14.912 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | 24.00 | 24.00 | 0.00717 | 33.41 | 0.00547 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 172087.18 | 172087.18 | 852.02 | 15.445 | 15.445 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00711 | 31.83 | 0.00547 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 13458.23 | 13458.23 | 42.94 | 1.208 | 1.208 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:10:00 | 24.00 | 24.00 | 0.00720 | 33.75 | 0.00548 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 15717.24 | 15717.24 | 77.82 | 1.411 | 1.411 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 09:20:00 | 24.00 | 24.00 | 0.00711 | 26.60 | 0.00546 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 18291.17 | 18291.17 | 58.36 | 1.642 | 1.642 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 24.00 | 24.00 | 0.00715 | 33.65 | 0.00547 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 18477.27 | 18477.27 | 91.48 | 1.658 | 1.658 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:00:00 | 24.00 | 24.00 | 0.00709 | 31.83 | 0.00547 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 8413.81 | 8413.81 | 232.41 | 0.596 | 0.596 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 80480.98 | 80480.98 | 2223.06 | 5.698 | 5.698 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 27.00 | 27.00 | 0.00709 | 28.50 | 0.00547 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 8213.88 | 8213.88 | 226.89 | 0.581 | 0.581 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 27.00 | 27.00 | 0.00709 | 28.87 | 0.00547 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 371175.74 | 371175.74 | 473.63 | 26.276 | 26.276 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:00:00 | 27.00 | 27.00 | 0.00704 | 20.43 | 0.00546 | 0.338 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.000 | 1.200 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:30:00 | 21.00 | 23.63 | 0.00096 | -17.90 | 0.00096 | 1.200 | 0.00 |
CORE_BOTTOM | 190.34 | 190.34 | 0.08 | 0.010 | 1.078 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | 21.00 | 21.01 | 0.00101 | -17.90 | 0.00096 | 1.078 | 0.00 |
CORE_MID | 298284.19 | 298284.19 | 119.50 | 15.549 | 15.549 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 10.778 | 0.00 |
CORE_TOP | 69446.23 | 69446.23 | 27.82 | 3.641 | 3.641 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00800 | -17.90 | 0.00096 | 1.078 | 0.00 |
PERIMETER_BOT_ZN_3 | 10688.83 | 10688.83 | 34.10 | 0.561 | 0.561 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00774 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_2 | 7560.64 | 7560.64 | 37.43 | 0.397 | 0.397 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00777 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_BOT_ZN_1 | 12282.06 | 12282.06 | 39.19 | 0.645 | 0.645 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00780 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_BOT_ZN_4 | 5832.33 | 5832.33 | 28.88 | 0.306 | 0.306 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00762 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_MID_ZN_3 | 169086.69 | 169086.69 | 539.50 | 8.884 | 8.884 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_2 | 113425.69 | 113425.69 | 561.58 | 5.960 | 5.960 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_MID_ZN_1 | 170942.19 | 170942.19 | 545.41 | 8.982 | 8.982 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00769 | -17.90 | 0.00096 | 1.353 | 0.00 |
PERIMETER_MID_ZN_4 | 108709.45 | 108709.45 | 538.23 | 5.712 | 5.712 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00768 | -17.90 | 0.00096 | 0.872 | 0.00 |
PERIMETER_TOP_ZN_3 | 22280.81 | 22280.81 | 71.09 | 1.171 | 1.171 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_2 | 14848.92 | 14848.92 | 73.52 | 0.781 | 0.781 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.087 | 0.00 |
PERIMETER_TOP_ZN_1 | 22508.66 | 22508.66 | 71.82 | 1.183 | 1.183 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00771 | -17.90 | 0.00096 | 0.135 | 0.00 |
PERIMETER_TOP_ZN_4 | 14531.55 | 14531.55 | 71.95 | 0.764 | 0.764 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21.00 | 21.00 | 0.00770 | -17.90 | 0.00096 | 0.087 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 25.14 | 0.00374 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.156 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 22.65 | 0.00170 | -17.90 | 0.00096 | 0.156 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:40:00 | 18.00 | 20.38 | 0.00162 | -17.90 | 0.00096 | 0.016 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.000 | 0.338 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:20:00 | 18.00 | 27.00 | 0.00700 | -17.90 | 0.00096 | 0.338 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
VAV_BOT WITH REHEAT | 11.18 | 11.18 | 2.99 | 2.99 | 11.1755 | 3.1838 | 11.1755 | 0.2849 | 0.3000 |
VAV_MID WITH REHEAT | 103.85 | 103.85 | 45.09 | 45.09 | 103.8515 | 45.0858 | 103.8515 | 0.4341 | 0.3000 |
VAV_TOP WITH REHEAT | 11.46 | 11.46 | 7.54 | 7.54 | 11.4601 | 7.5398 | 11.4601 | 0.6579 | 0.3000 |
CAV_BAS | 6.43 | 6.43 | 1.20 | 1.20 | 6.4261 | 6.4261 | 6.4261 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.28 | 26.28 | 0.34 | 0.34 | 26.2766 | 26.2762 | 26.2766 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.60 | 0.60 | 0.02 | 0.02 | 0.5956 | 0.5956 | 0.5956 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER MID | 5.70 | 5.70 | 0.16 | 0.16 | 5.6975 | 5.6975 | 5.6975 | 1.0000 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.58 | 0.58 | 0.02 | 0.02 | 0.5815 | 0.5815 | 0.5815 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | 16450.844 | 16450.844 | 2.012827 | 0.00014392 | 331.636 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | 16450.84 | 16450.84 | 2.012827 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.01 | 0.00101228 | 5.3682 | 190.34 | 0.00 | 16511.50 | 16511.50 |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | 459186.975 | 459186.975 | 19.687171 | 0.00401717 | 11373.708 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 459186.98 | 459186.98 | 19.687171 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 298284.19 | 0.00 | 460625.98 | 460625.98 |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | 99203.205 | 99203.205 | 3.640898 | 0.00086787 | 2617.718 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 99203.21 | 99203.21 | 3.640898 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00800000 | 41.9796 | 69446.23 | 0.00 | 99539.25 | 99539.25 |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | 15270.181 | 15270.181 | 0.560882 | 0.00013359 | 402.795 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 15270.18 | 15270.18 | 0.560882 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00773987 | 40.6339 | 10688.83 | 0.00 | 15320.85 | 15320.85 |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | 10802.507 | 10802.507 | 0.396865 | 0.00009451 | 284.920 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 10802.51 | 10802.51 | 0.396865 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00777284 | 40.8046 | 7560.64 | 0.00 | 10838.16 | 10838.16 |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | 17549.295 | 17549.295 | 0.644769 | 0.00015353 | 462.855 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 17549.29 | 17549.29 | 0.644769 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00779931 | 40.9416 | 12282.06 | 0.00 | 17607.12 | 17607.12 |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | 8644.120 | 8644.120 | 0.344331 | 0.00007562 | 220.217 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 8644.12 | 8644.12 | 0.344331 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00761610 | 39.9928 | 5832.33 | 0.00 | 8670.81 | 8670.81 |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | 241639.406 | 241639.406 | 8.883803 | 0.00211397 | 6371.220 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 241639.41 | 241639.41 | 8.883803 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769129 | 40.3833 | 169086.69 | 0.00 | 242421.75 | 242421.75 |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | 162099.279 | 162099.279 | 5.959892 | 0.00141812 | 4273.896 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 162099.28 | 162099.28 | 5.959892 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769359 | 40.3953 | 113425.69 | 0.00 | 162623.25 | 162623.25 |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | 244293.371 | 244293.371 | 8.981515 | 0.00213718 | 6441.150 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 244293.37 | 244293.37 | 8.981515 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00769464 | 40.4007 | 170942.19 | 0.00 | 245083.98 | 245083.98 |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | 155353.908 | 155353.908 | 5.711587 | 0.00135910 | 4096.146 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 155353.91 | 155353.91 | 5.711587 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00768035 | 40.3267 | 108709.45 | 0.00 | 155856.78 | 155856.78 |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | 31845.987 | 31845.987 | 1.171219 | 0.00027860 | 839.537 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 31845.99 | 31845.99 | 1.171219 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770916 | 40.4766 | 22280.81 | 0.00 | 31948.12 | 31948.12 |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | 21223.888 | 21223.888 | 0.780594 | 0.00018568 | 559.503 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 21223.89 | 21223.89 | 0.780594 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770897 | 40.4758 | 14848.92 | 0.00 | 21291.88 | 21291.88 |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | 32171.880 | 32171.880 | 1.183217 | 0.00028145 | 848.125 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 32171.88 | 32171.88 | 1.183217 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00771197 | 40.4912 | 22508.66 | 0.00 | 32275.03 | 32275.03 |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | 20770.024 | 20770.024 | 0.763889 | 0.00018171 | 547.542 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 20770.02 | 20770.02 | 0.763889 | 12.80 | 9.74 | 0.00800000 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 0.0000 | 21.00 | 0.00770311 | 40.4453 | 14531.55 | 0.00 | 20836.60 | 20836.60 |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 175795.716 | -999.000 | 11.175495 | 0.00747876 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 175795.72 | 175795.72 | 11.175495 | 26.33 | 13.72 | 0.00690538 | 10.52 | 7.71 | 0.00690538 | 33.90 | 0.00547527 | 15.07 | 22.7121 | 24.00 | 0.00734589 | 32.1593 | 120086.84 | 0.00 | 157365.83 | 157365.83 |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_BOT WITH REHEAT | 69971.824 | 69971.824 | 3.352648 | 0.00061214 | 1120.014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 69971.82 | 69971.82 | 3.352648 | -8.45 | -9.09 | 0.00190927 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 75.7070 | 21.03 | 0.00569577 | 29.9380 | 27662.95 | 0.00 | 61432.24 | 61432.24 |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 1659236.150 | -999.000 | 103.851453 | 0.07058774 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 1659236.15 | 1659236.14 | 103.851453 | 26.58 | 13.78 | 0.00687377 | 10.52 | 7.68 | 0.00687377 | 33.90 | 0.00547527 | 15.07 | 24.4406 | 24.00 | 0.00736666 | 32.2491 | 1085170.94 | 0.00 | 1482736.37 | 1482736.37 |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_MID WITH REHEAT | 730417.808 | 730417.808 | 31.155436 | 0.00639001 | 11536.811 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 730417.81 | 730417.81 | 31.155436 | -11.07 | -11.07 | 0.00219421 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 81.4688 | 19.35 | 0.00746758 | 43.4419 | 393418.20 | 0.00 | 623172.03 | 623172.03 |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 178731.629 | -999.000 | 11.460088 | 0.00760366 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | 178731.63 | 178731.63 | 11.460088 | 26.20 | 13.67 | 0.00690081 | 10.52 | 7.70 | 0.00690081 | 33.90 | 0.00547527 | 15.07 | 22.1481 | 24.00 | 0.00730721 | 31.9918 | 127476.35 | 0.00 | 159795.31 | 159795.31 |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoopHVAC | VAV_TOP WITH REHEAT | 72225.492 | 72225.492 | 3.438027 | 0.00063186 | 1154.884 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | 72225.49 | 72225.49 | 3.438027 | -8.59 | -8.59 | 0.00268982 | 12.80 | 9.74 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 73.8269 | 17.36 | 0.00742759 | 48.9611 | 45286.31 | 0.00 | 63312.84 | 63312.84 |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoopHVAC | CAV_BAS | 94867.029 | -999.000 | 6.426050 | 0.00403586 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | 94867.03 | 94867.03 | 6.426050 | 25.93 | 13.75 | 0.00709832 | 11.10 | 8.15 | 0.00709832 | 33.16 | 0.00547412 | 14.83 | 18.6764 | 24.00 | 0.00753279 | 32.9682 | 63356.89 | 0.00 | 85477.39 | 85477.39 |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoopHVAC | CAV_BAS | 273563.322 | 273563.322 | 6.426050 | 0.00239325 | 5951.547 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 273563.32 | 273563.32 | 6.426050 | -3.34 | -7.54 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 18.6764 | 23.73 | 0.00095524 | 4.2925 | 0.00 | 0.00 | 222667.53 | 222667.53 |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 476647.151 | 249789.485 | 26.276554 | 0.01167306 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | 405137.11 | 404170.79 | -999.0 | 28.80 | 14.64 | 0.00702201 | 12.80 | 8.76 | 0.00700000 | 33.90 | 0.00547527 | 15.07 | -999.0000 | 27.00 | 0.00704222 | 25.8134 | 370735.34 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10504.223 | 5559.886 | 0.595637 | 0.00025725 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8881.61 | 8839.10 | -999.0 | 28.21 | 14.47 | 0.00704319 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708567 | 25.9689 | 8411.21 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100513.414 | 53190.895 | 5.697516 | 0.00246157 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 84992.52 | 84568.46 | -999.0 | 28.22 | 14.47 | 0.00704503 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708955 | 25.9831 | 80447.91 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10256.744 | 5428.268 | 0.581486 | 0.00025119 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 8672.69 | 8630.16 | -999.0 | 28.21 | 14.47 | 0.00704425 | 12.80 | 8.76 | 0.00700000 | 28.87 | 0.00546756 | 13.38 | -999.0000 | 27.00 | 0.00708780 | 25.9767 | 8213.88 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 476647.151 | 476647.151 | 26.276554 | 0.01167306 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 476647.15 | 476647.15 | 26.276554 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2878 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER BOT | 10504.223 | 10504.223 | 0.595637 | 0.00025725 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10504.22 | 10504.22 | 0.595637 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6245 | 25.75 | 0.00374071 | 14.8328 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER MID | 100513.414 | 100513.414 | 5.697516 | 0.00246157 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 100513.41 | 100513.41 | 5.697516 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7437 | 23.83 | 0.00170052 | 7.5880 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoopHVAC | AIRLOOP DATACENTER TOP | 10256.744 | 10256.744 | 0.581486 | 0.00025119 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 10256.74 | 10256.74 | 0.581486 | -17.90 | -17.90 | 0.00095524 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6883 | 22.46 | 0.00162229 | 7.8636 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 19243.92 | 19243.92 | 26.276554 | -0.23 | -0.23 | 0.00692215 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 1.2878 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER BOT | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.595637 | -0.47 | -1.60 | 0.00366760 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6245 | 25.75 | 0.00374071 | 14.8328 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER MID | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 8889.90 | 8889.90 | 5.697516 | -0.49 | -4.62 | 0.00168007 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.7437 | 23.83 | 0.00170052 | 7.5880 | 0.00 | 0.00 | -999.00 | -999.00 |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoopHVAC | AIRLOOP DATACENTER TOP | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 888.99 | 888.99 | 0.581486 | -0.48 | -4.74 | 0.00160436 | 40.00 | 18.76 | 0.00800000 | -17.90 | 0.00095524 | -17.90 | 2.6883 | 22.46 | 0.00162229 | 7.8636 | 0.00 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
CORE_BOTTOM VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_BOTTOM VAV BOX | CORE_BOTTOM | N/A | N/A | N/A | Yes | Yes | Yes | No | 16450.844 | 16450.844 | 2.012827 | 0.00014392 | 331.636 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 0.6011 | 0.613223 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 07:40:00 | Sensible | 16450.84 | 16450.84 | 1.0000 | 1.96741329 | 2.012827 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.14390448 | 60.00 | 32.22 | 27.78 | 0.000 | 16450.84 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 13.98 | 0.00101228 | 21.01 | 0.00101228 | 5.3682 | 190.34 | 0.00 | 16511.50 | 16511.50 | 1.96741329 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 21.03 | 14.86 | 0.00800000 | 41452.3 | |
CORE_MID VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_MID VAV BOX | CORE_MID | N/A | N/A | N/A | Yes | Yes | Yes | No | 459186.975 | 459186.975 | 19.687171 | 0.00401717 | 11373.708 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 16.7790 | 17.116704 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 459186.98 | 459186.98 | 1.0000 | 19.24298127 | 19.687171 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 4.01675818 | 60.00 | 32.22 | 27.78 | 0.000 | 459186.98 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.87 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 298284.19 | 0.00 | 460625.98 | 460625.98 | 19.24298127 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 36.27 | 20.05 | 0.00800000 | 56997.2 | |
CORE_TOP VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | CORE_TOP VAV BOX | CORE_TOP | N/A | N/A | N/A | Yes | Yes | Yes | No | 99203.205 | 99203.205 | 3.640898 | 0.00086787 | 2617.718 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 3.6250 | 3.697910 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 99203.21 | 99203.21 | 1.0000 | 3.55875033 | 3.640898 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.86778438 | 60.00 | 32.22 | 27.78 | 0.000 | 99203.21 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00800000 | 21.00 | 0.00800000 | 41.9796 | 69446.23 | 0.00 | 99539.25 | 99539.25 | 3.55875033 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.23 | 21.25 | 0.00800000 | 61030.1 | |
PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_3 VAV BOX | PERIMETER_BOT_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 15270.181 | 15270.181 | 0.560882 | 0.00013359 | 402.795 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 0.5580 | 0.569213 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 15270.18 | 15270.18 | 1.0000 | 0.54822725 | 0.560882 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.13357658 | 60.00 | 32.22 | 27.78 | 0.000 | 15270.18 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00773987 | 21.00 | 0.00773987 | 40.6339 | 10688.83 | 0.00 | 15320.85 | 15320.85 | 0.54822725 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.21 | 21.24 | 0.00800000 | 61006.0 | |
PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_2 VAV BOX | PERIMETER_BOT_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 10802.507 | 10802.507 | 0.396865 | 0.00009451 | 284.920 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 0.3947 | 0.402675 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 10802.51 | 10802.51 | 1.0000 | 0.38791074 | 0.396865 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.09449540 | 60.00 | 32.22 | 27.78 | 0.000 | 10802.51 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00777284 | 21.00 | 0.00777284 | 40.8046 | 7560.64 | 0.00 | 10838.16 | 10838.16 | 0.38791074 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60999.7 | |
PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_1 VAV BOX | PERIMETER_BOT_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 17549.295 | 17549.295 | 0.644769 | 0.00015353 | 462.855 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 0.6413 | 0.654169 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 17549.29 | 17549.29 | 1.0000 | 0.63022195 | 0.644769 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.15351323 | 60.00 | 32.22 | 27.78 | 0.000 | 17549.29 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00779931 | 21.00 | 0.00779931 | 40.9416 | 12282.06 | 0.00 | 17607.12 | 17607.12 | 0.63022195 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.20 | 21.24 | 0.00800000 | 60997.8 | |
PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_BOT_ZN_4 VAV BOX | PERIMETER_BOT_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 8644.120 | 8644.120 | 0.344331 | 0.00007562 | 220.217 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 0.3159 | 0.322219 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 8644.12 | 8644.12 | 1.0000 | 0.33656216 | 0.344331 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.07561482 | 60.00 | 32.22 | 27.78 | 0.000 | 8644.12 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00761610 | 21.00 | 0.00761610 | 39.9928 | 5832.33 | 0.00 | 8670.81 | 8670.81 | 0.33656216 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 38.06 | 20.60 | 0.00800000 | 58822.7 | |
PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_3 VAV BOX | PERIMETER_MID_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 241639.406 | 241639.406 | 8.883803 | 0.00211397 | 6371.220 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 8.8297 | 9.007377 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 241639.41 | 241639.41 | 1.0000 | 8.68336337 | 8.883803 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.11375129 | 60.00 | 32.22 | 27.78 | 0.000 | 241639.41 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00769129 | 21.00 | 0.00769129 | 40.3833 | 169086.69 | 0.00 | 242421.75 | 242421.75 | 8.68336337 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.24 | 0.00800000 | 60977.8 | |
PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_2 VAV BOX | PERIMETER_MID_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 162099.279 | 162099.279 | 5.959892 | 0.00141812 | 4273.896 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 5.9232 | 6.042431 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 162099.28 | 162099.28 | 1.0000 | 5.82542304 | 5.959892 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.41797055 | 60.00 | 32.22 | 27.78 | 0.000 | 162099.28 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00769359 | 21.00 | 0.00769359 | 40.3953 | 113425.69 | 0.00 | 162623.25 | 162623.25 | 5.82542304 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60976.0 | |
PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_1 VAV BOX | PERIMETER_MID_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 244293.371 | 244293.371 | 8.981515 | 0.00213718 | 6441.150 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 8.9267 | 9.106307 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 244293.37 | 244293.37 | 1.0000 | 8.77887019 | 8.981515 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.13696696 | 60.00 | 32.22 | 27.78 | 0.000 | 244293.37 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00769464 | 21.00 | 0.00769464 | 40.4007 | 170942.19 | 0.00 | 245083.98 | 245083.98 | 8.77887019 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.3 | |
PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_MID_ZN_4 VAV BOX | PERIMETER_MID_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 155353.908 | 155353.908 | 5.711587 | 0.00135910 | 4096.146 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 5.6767 | 5.790989 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 155353.91 | 155353.91 | 1.0000 | 5.58271956 | 5.711587 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 1.35896512 | 60.00 | 32.22 | 27.78 | 0.000 | 155353.91 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00768035 | 21.00 | 0.00768035 | 40.3267 | 108709.45 | 0.00 | 155856.78 | 155856.78 | 5.58271956 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.18 | 21.23 | 0.00800000 | 60977.5 | |
PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_3 VAV BOX | PERIMETER_TOP_ZN_3 | N/A | N/A | N/A | Yes | Yes | Yes | No | 31845.987 | 31845.987 | 1.171219 | 0.00027860 | 839.537 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 1.1637 | 1.187095 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 31845.99 | 31845.99 | 1.0000 | 1.14479320 | 1.171219 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.27857417 | 60.00 | 32.22 | 27.78 | 0.000 | 31845.99 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770916 | 21.00 | 0.00770916 | 40.4766 | 22280.81 | 0.00 | 31948.12 | 31948.12 | 1.14479320 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60967.2 | |
PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_2 VAV BOX | PERIMETER_TOP_ZN_2 | N/A | N/A | N/A | Yes | Yes | Yes | No | 21223.888 | 21223.888 | 0.780594 | 0.00018568 | 559.503 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 0.7755 | 0.791144 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 21223.89 | 21223.89 | 1.0000 | 0.76298178 | 0.780594 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.18565689 | 60.00 | 32.22 | 27.78 | 0.000 | 21223.89 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770897 | 21.00 | 0.00770897 | 40.4758 | 14848.92 | 0.00 | 21291.88 | 21291.88 | 0.76298178 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.0 | |
PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_1 VAV BOX | PERIMETER_TOP_ZN_1 | N/A | N/A | N/A | Yes | Yes | Yes | No | 32171.880 | 32171.880 | 1.183217 | 0.00028145 | 848.125 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 1.1756 | 1.199243 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 32171.88 | 32171.88 | 1.0000 | 1.15652062 | 1.183217 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.28142493 | 60.00 | 32.22 | 27.78 | 0.000 | 32171.88 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00771197 | 21.00 | 0.00771197 | 40.4912 | 22508.66 | 0.00 | 32275.03 | 32275.03 | 1.15652062 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.8 | |
PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL | COIL:HEATING:WATER | Zone Equipment | ZONEHVAC:AIRDISTRIBUTIONUNIT | PERIMETER_TOP_ZN_4 VAV BOX | PERIMETER_TOP_ZN_4 | N/A | N/A | N/A | Yes | Yes | Yes | No | 20770.024 | 20770.024 | 0.763889 | 0.00018171 | 547.542 | 1.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 0.7590 | 0.774226 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 20770.02 | 20770.02 | 1.0000 | 0.74665420 | 0.763889 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 0.18168670 | 60.00 | 32.22 | 27.78 | 0.000 | 20770.02 | -17.90 | 0.00095524 | -17.90 | 0.00000000 | 0.0000 | 20.95 | 0.00770311 | 21.00 | 0.00770311 | 40.4453 | 14531.55 | 0.00 | 20836.60 | 20836.60 | 0.74665420 | 12.80 | 11.60 | 0.00800000 | 33059.8 | 40.17 | 21.23 | 0.00800000 | 60966.4 | |
VAV_BOT WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 175795.716 | -999.000 | 11.175495 | 0.00747876 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6767 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.175495 | 10.92334897 | 4197.9300 | 999.8980 | 89.69686606 | 12.27 | 6.67 | 5.60 | 2108630.52 | 8.3370 | 8.336962 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 175795.72 | 175795.72 | 1.0000 | 10.92334897 | 11.175495 | 26.33 | 13.72 | 0.00690538 | 44065.7 | 10.52 | 7.71 | 0.00690538 | 27972.2 | 7.47799324 | 6.67 | 12.27 | 5.60 | 25386.178 | 150409.54 | 33.90 | 0.00547527 | 15.07 | 2.53819000 | 22.7121 | 24.00 | 0.00734589 | 24.00 | 0.00734589 | 32.1593 | 120086.84 | 0.00 | 157365.83 | 157365.83 | 10.92334897 | 26.33 | 15.83 | 0.00690538 | 44065.7 | 12.17 | 10.18 | 0.00690538 | 29659.4 | |
VAV_BOT WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_BOT WITH REHEAT | CORE_BOTTOM; PERIMETER_BOT_ZN_3; PERIMETER_BOT_ZN_2; PERIMETER_BOT_ZN_1; PERIMETER_BOT_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 69971.824 | 69971.824 | 3.352648 | 0.00061214 | 1120.014 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_BOT WITH REHEAT FAN | Fan:VariableVolume | 11.175495 | 10.92334897 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 2.5568 | 2.608277 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 18:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 69971.82 | 69971.82 | 1.0000 | 3.27700469 | 3.352648 | -8.45 | -9.09 | 0.00190927 | -3745.1 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.61208160 | 60.00 | 32.22 | 27.78 | 0.000 | 69971.82 | -17.90 | 0.00095524 | -17.90 | 2.53819000 | 75.7070 | 21.00 | 0.00488241 | 21.03 | 0.00569577 | 29.9380 | 27662.95 | 0.00 | 61432.24 | 61432.24 | 3.27700469 | 2.80 | -1.32 | 0.00190927 | 7598.4 | 21.39 | 8.80 | 0.00190927 | 26344.9 | |
VAV_MID WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 1659236.150 | -999.000 | 103.851453 | 0.07058774 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6180 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 103.851453 | 101.50831631 | 4197.9300 | 999.8980 | 89.69686606 | 12.27 | 6.67 | 5.60 | 2108630.52 | 78.6879 | 78.687856 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 1659236.15 | 1659236.14 | 1.0000 | 101.50831631 | 103.851453 | 26.58 | 13.78 | 0.00687377 | 44238.2 | 10.52 | 7.68 | 0.00687377 | 27892.4 | 70.58054080 | 6.67 | 12.27 | 5.60 | 235908.258 | 1423327.89 | 33.90 | 0.00547527 | 15.07 | 25.38195000 | 24.4406 | 24.00 | 0.00736666 | 24.00 | 0.00736666 | 32.2491 | 1085170.94 | 0.00 | 1482736.37 | 1482736.37 | 101.50831631 | 26.58 | 15.90 | 0.00687377 | 44238.2 | 12.22 | 10.17 | 0.00687377 | 29631.1 | |
VAV_MID WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_MID WITH REHEAT | CORE_MID; PERIMETER_MID_ZN_3; PERIMETER_MID_ZN_2; PERIMETER_MID_ZN_1; PERIMETER_MID_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 730417.808 | 730417.808 | 31.155436 | 0.00639001 | 11536.811 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_MID WITH REHEAT FAN | Fan:VariableVolume | 103.851453 | 101.50831631 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 26.6900 | 27.227135 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 06:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 730417.81 | 730417.81 | 1.0000 | 30.45249489 | 31.155436 | -11.07 | -11.07 | 0.00219421 | -5680.6 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 6.38936177 | 60.00 | 32.22 | 27.78 | 0.000 | 730417.81 | -17.90 | 0.00095524 | -17.90 | 25.38195000 | 81.4688 | 18.96 | 0.00764111 | 19.35 | 0.00746758 | 43.4419 | 393418.20 | 0.00 | 623172.03 | 623172.03 | 30.45249489 | 2.80 | -0.88 | 0.00219421 | 8312.6 | 23.08 | 9.89 | 0.00219421 | 28776.3 | |
VAV_TOP WITH REHEAT COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 178731.629 | -999.000 | 11.460088 | 0.00760366 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1017.6683 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.460088 | 11.20152138 | 4197.9300 | 999.8980 | 89.69686606 | 12.27 | 6.67 | 5.60 | 2108630.52 | 8.4762 | 8.476195 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | Sensible | 178731.63 | 178731.63 | 1.0000 | 11.20152138 | 11.460088 | 26.20 | 13.67 | 0.00690081 | 43916.7 | 10.52 | 7.70 | 0.00690081 | 27960.6 | 7.60288100 | 6.67 | 12.27 | 5.60 | 26032.659 | 152698.97 | 33.90 | 0.00547527 | 15.07 | 2.53819000 | 22.1481 | 24.00 | 0.00730721 | 24.00 | 0.00730721 | 31.9918 | 127476.35 | 0.00 | 159795.31 | 159795.31 | 11.20152138 | 26.20 | 15.78 | 0.00690081 | 43916.7 | 12.18 | 10.18 | 0.00690081 | 29651.2 | |
VAV_TOP WITH REHEAT HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | VAV_TOP WITH REHEAT | CORE_TOP; PERIMETER_TOP_ZN_3; PERIMETER_TOP_ZN_2; PERIMETER_TOP_ZN_1; PERIMETER_TOP_ZN_4; | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 72225.492 | 72225.492 | 3.438027 | 0.00063186 | 1154.884 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | VAV_TOP WITH REHEAT FAN | Fan:VariableVolume | 11.460088 | 11.20152138 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 2.6392 | 2.692285 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 05:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 08:00:00 | Sensible | 72225.49 | 72225.49 | 1.0000 | 3.36045641 | 3.438027 | -8.59 | -8.59 | 0.00268982 | -1946.3 | 12.80 | 9.74 | 0.00800000 | 33059.8 | 0.63179566 | 60.00 | 32.22 | 27.78 | 0.000 | 72225.49 | -17.90 | 0.00095524 | -17.90 | 2.53819000 | 73.8269 | 17.68 | 0.00758261 | 17.36 | 0.00742759 | 48.9611 | 45286.31 | 0.00 | 63312.84 | 63312.84 | 3.36045641 | 2.80 | 0.07 | 0.00268982 | 9554.6 | 21.46 | 9.71 | 0.00268982 | 28395.2 | |
CAV_BAS COOLING COIL | Coil:Cooling:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | CoolingDesignCapacity | N/A | Yes | Yes | Yes | No | 94867.029 | -999.000 | 6.426050 | 0.00403586 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.0354 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 6.426050 | 6.28106299 | 4197.9300 | 999.8980 | 89.69686606 | 12.27 | 6.67 | 5.60 | 2108630.52 | 4.4990 | 4.498988 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 08:00:00 | Sensible | 94867.03 | 94867.03 | 1.0000 | 6.28106299 | 6.426050 | 25.93 | 13.75 | 0.00709832 | 44152.2 | 11.10 | 8.15 | 0.00709832 | 29048.5 | 4.03545101 | 6.67 | 12.27 | 5.60 | 10896.360 | 83970.67 | 33.16 | 0.00547412 | 14.83 | 1.20015641 | 18.6764 | 24.00 | 0.00753279 | 24.00 | 0.00753279 | 32.9682 | 63356.89 | 0.00 | 85477.39 | 85477.39 | 6.28106299 | 25.93 | 15.86 | 0.00709832 | 44152.2 | 12.56 | 10.56 | 0.00709832 | 30543.4 | |
CAV_BAS HEATING COIL | Coil:Heating:Water | AirLoop | AirLoopHVAC | CAV_BAS | BASEMENT | Coincident | HeatingDesignCapacity | N/A | Yes | Yes | Yes | No | 273563.322 | 273563.322 | 6.426050 | 0.00239325 | 5951.547 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | CAV_BAS FAN | Fan:ConstantVolume | 6.426050 | 6.28106299 | 4197.9300 | 999.8980 | 23.46688982 | 54.44 | 82.22 | 27.78 | 2736673.38 | 9.9962 | 10.197377 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 273563.32 | 273563.32 | 1.0000 | 6.28106299 | 6.426050 | -3.34 | -7.54 | 0.00095524 | -976.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | 2.39300714 | 60.00 | 32.22 | 27.78 | 0.000 | 273563.32 | -17.90 | 0.00095524 | -17.90 | 1.20015641 | 18.6764 | 0.00 | 0.00095524 | 23.73 | 0.00095524 | 4.2925 | 0.00 | 0.00 | 222667.53 | 222667.53 | 6.28106299 | 12.80 | 3.31 | 0.00095524 | 15273.7 | 48.02 | 18.26 | 0.00095524 | 50724.3 | |
AIRLOOP DATACENTER BASEMENT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 476647.151 | 249789.485 | 26.276554 | 0.01167306 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.8936 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 07:10:00 | Sensible | 405137.11 | 404170.79 | 0.8500 | -999.0 | -999.0 | 28.80 | 14.64 | 0.00702201 | 46872.6 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 405137.11 | 33.90 | 0.00547527 | 15.07 | 0.33839277 | -999.0000 | 27.00 | 0.00704222 | 27.00 | 0.00704222 | 25.8134 | 370735.34 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10504.223 | 5559.886 | 0.595637 | 0.00025725 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9329 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8881.61 | 8839.10 | 0.8455 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704319 | 46333.8 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8881.61 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | -999.0000 | 27.00 | 0.00708567 | 27.00 | 0.00708567 | 25.9689 | 8411.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 100513.414 | 53190.895 | 5.697516 | 0.00246157 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9364 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 84992.52 | 84568.46 | 0.8456 | -999.0 | -999.0 | 28.22 | 14.47 | 0.00704503 | 46340.7 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 84992.52 | 28.87 | 0.00546756 | 13.38 | 0.15632344 | -999.0000 | 27.00 | 0.00708955 | 27.00 | 0.00708955 | 25.9831 | 80447.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP COOLING COIL | COIL:COOLING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | CoolingDesignCapacity | N/A | Yes | No | unknown | No | 10256.744 | 5428.268 | 0.581486 | 0.00025119 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1017.9349 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 8672.69 | 8630.16 | 0.8456 | -999.0 | -999.0 | 28.21 | 14.47 | 0.00704425 | 46337.7 | 12.80 | 8.76 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8672.69 | 28.87 | 0.00546756 | 13.38 | 0.01563234 | -999.0000 | 27.00 | 0.00708780 | 27.00 | 0.00708780 | 25.9767 | 8213.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 476647.151 | 476647.151 | 26.276554 | 0.01167306 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 476647.15 | 476647.15 | 1.0000 | 25.68369219 | 26.276554 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 476647.15 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2878 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10504.223 | 10504.223 | 0.595637 | 0.00025725 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10504.22 | 10504.22 | 1.0000 | 0.58219822 | 0.595637 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10504.22 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6245 | 0.00 | 0.00374071 | 25.75 | 0.00374071 | 14.8328 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 100513.414 | 100513.414 | 5.697516 | 0.00246157 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 100513.41 | 100513.41 | 1.0000 | 5.56896614 | 5.697516 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 100513.41 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7437 | 0.00 | 0.00170052 | 23.83 | 0.00170052 | 7.5880 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP HEATING COIL | COIL:HEATING:WATERTOAIRHEATPUMP:EQUATIONFIT | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 10256.744 | 10256.744 | 0.581486 | 0.00025119 | -999.000 | -999.0000 | -999.00000 | -999.00000 | 1019.7116 | 1004.8586 | 0.9774 | unknown | unknown | -999.0 | -999.0 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 10256.74 | 10256.74 | 1.0000 | 0.56836654 | 0.581486 | -17.90 | -17.90 | 0.00095524 | -15629.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 10256.74 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6883 | 0.00 | 0.00162229 | 22.46 | 0.00162229 | 7.8636 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BASEMENT | DATACENTER_BASEMENT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 19243.924 | 19243.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BASEMENT SUPPLY FAN | Fan:OnOff | 26.276554 | 25.68369219 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 19243.92 | 19243.92 | 1.0000 | 25.68369219 | 26.276554 | -0.23 | -0.23 | 0.00692215 | 17077.3 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 19243.92 | -17.90 | 0.00095524 | -17.90 | 0.33839277 | 1.2878 | 0.00 | 0.00700000 | 27.00 | 0.00700000 | 25.6559 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER BOT_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER BOT | DATACENTER_BOT_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER BOT SUPPLY FAN | Fan:OnOff | 0.595637 | 0.58219822 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.58219822 | 0.595637 | -0.47 | -1.60 | 0.00366760 | 8697.2 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6245 | 0.00 | 0.00374071 | 25.75 | 0.00374071 | 14.8328 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER MID_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER MID | DATACENTER_MID_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 8889.896 | 8889.896 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER MID SUPPLY FAN | Fan:OnOff | 5.697516 | 5.56896614 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 8889.90 | 8889.90 | 1.0000 | 5.56896614 | 5.697516 | -0.49 | -4.62 | 0.00168007 | 3706.7 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 8889.90 | -17.90 | 0.00095524 | -17.90 | 0.15632344 | 2.7437 | 0.00 | 0.00170052 | 23.83 | 0.00170052 | 7.5880 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
AIRLOOP DATACENTER TOP_SUPPHEATCOIL | Coil:Heating:Electric | AirLoop | AirLoopHVAC | AIRLOOP DATACENTER TOP | DATACENTER_TOP_ZN_6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 888.990 | 888.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 0.9774 | AIRLOOP DATACENTER TOP SUPPLY FAN | Fan:OnOff | 0.581486 | 0.56836654 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 888.99 | 888.99 | 1.0000 | 0.56836654 | 0.581486 | -0.48 | -4.74 | 0.00160436 | 3527.4 | 40.00 | 18.76 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 888.99 | -17.90 | 0.00095524 | -17.90 | 0.01563234 | 2.6883 | 0.00 | 0.00162229 | 22.46 | 0.00162229 | 7.8636 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
VAV_BOT WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.18 | - | |||
VAV_MID WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 103.85 | - | |||
VAV_TOP WITH REHEAT_OA_CONTROLLER | DifferentialDryBulb | 0.00 | 11.46 | - | |||
CAV_BAS_OA_CONTROLLER | DifferentialDryBulb | 1.20 | 6.43 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
CORE_BOTTOM | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_MID | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
CORE_TOP | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 | ||
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT_DCV | 0.000000 | 0.000432 | 0.000000 | 0.000000 | Flow/Area | 1.00 | 1.00 |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
BASEMENT | 1821.33 | 1584.17 | 155.33 |
CORE_BOTTOM | 1699.00 | 1621.17 | 153.17 |
CORE_MID | 1106.83 | 3484.50 | 222.67 |
CORE_TOP | 1788.00 | 3920.33 | 907.17 |
PERIMETER_BOT_ZN_3 | 1697.83 | 3727.50 | 460.83 |
PERIMETER_BOT_ZN_2 | 2088.33 | 3292.83 | 533.00 |
PERIMETER_BOT_ZN_1 | 2492.33 | 2556.50 | 541.50 |
PERIMETER_BOT_ZN_4 | 2610.33 | 2196.50 | 367.00 |
PERIMETER_MID_ZN_3 | 2650.17 | 4156.67 | 1734.50 |
PERIMETER_MID_ZN_2 | 2370.00 | 3197.50 | 1239.00 |
PERIMETER_MID_ZN_1 | 2652.00 | 2935.50 | 922.00 |
PERIMETER_MID_ZN_4 | 2593.00 | 3727.00 | 1209.83 |
PERIMETER_TOP_ZN_3 | 3366.00 | 4287.00 | 2452.00 |
PERIMETER_TOP_ZN_2 | 3327.67 | 3865.17 | 1954.50 |
PERIMETER_TOP_ZN_1 | 2978.83 | 3296.33 | 1420.00 |
PERIMETER_TOP_ZN_4 | 3160.83 | 3944.50 | 1850.33 |
DATACENTER_BOT_ZN_6 | 5943.00 | 481.33 | 481.33 |
DATACENTER_MID_ZN_6 | 5671.00 | 76.33 | 61.50 |
DATACENTER_TOP_ZN_6 | 5015.83 | 300.00 | 94.83 |
DATACENTER_BASEMENT_ZN_6 | 5943.00 | 5894.00 | 5894.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 |
Facility | 5943.00 | 5943.00 | 5943.00 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
BASEMENT | 0.00 | 71.50 | 0.00 | 1.83 |
CORE_BOTTOM | 0.00 | 7.17 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.50 | 0.00 | 0.00 |
CORE_TOP | 8.17 | 0.33 | 0.67 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.67 | 4.00 | 0.00 | 2.50 |
PERIMETER_BOT_ZN_2 | 0.83 | 27.33 | 0.00 | 27.33 |
PERIMETER_BOT_ZN_1 | 1.67 | 65.67 | 0.00 | 63.50 |
PERIMETER_BOT_ZN_4 | 0.00 | 121.17 | 0.00 | 49.50 |
PERIMETER_MID_ZN_3 | 48.83 | 3.33 | 12.50 | 2.67 |
PERIMETER_MID_ZN_2 | 30.17 | 30.83 | 2.83 | 30.67 |
PERIMETER_MID_ZN_1 | 19.17 | 79.83 | 2.50 | 78.50 |
PERIMETER_MID_ZN_4 | 18.67 | 29.50 | 2.17 | 18.83 |
PERIMETER_TOP_ZN_3 | 225.33 | 7.17 | 81.00 | 5.33 |
PERIMETER_TOP_ZN_2 | 130.67 | 34.17 | 20.50 | 32.17 |
PERIMETER_TOP_ZN_1 | 112.17 | 49.67 | 21.33 | 46.50 |
PERIMETER_TOP_ZN_4 | 91.67 | 31.67 | 14.50 | 19.33 |
DATACENTER_BOT_ZN_6 | 0.00 | 71.67 | 0.00 | 65.83 |
DATACENTER_MID_ZN_6 | 0.00 | 44.50 | 0.00 | 43.17 |
DATACENTER_TOP_ZN_6 | 0.00 | 40.83 | 0.00 | 38.33 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 2102.83 | 0.00 | 1402.83 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 249.33 | 2368.33 | 84.50 | 1575.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 1.388 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 1.028 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.761 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.724 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.918 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 1.526 | 0.045 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 1.617 | 0.043 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 2.115 | 0.045 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.750 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 1.383 | 0.112 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 1.477 | 0.101 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 1.431 | 0.104 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.764 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 1.448 | 0.129 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 1.440 | 0.125 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 1.466 | 0.129 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.424 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.480 | 0.000 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
BASEMENT | 62.11 | 149.60 | 6779.02 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_BOTTOM | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_MID | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
CORE_TOP | 55.78 | 134.35 | 6849.35 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_BOT_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_2 | 3.94 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_MID_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_3 | 7.00 | 16.87 | 860.00 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_2 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_1 | 7.00 | 16.87 | 860.02 | 0.000 | 0.000 | 0.000 | 0.000 |
PERIMETER_TOP_ZN_4 | 4.51 | 10.87 | 554.22 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BOT_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_MID_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_TOP_ZN_6 | 0.81 | 1.95 | 99.34 | 0.000 | 0.000 | 0.000 | 0.000 |
DATACENTER_BASEMENT_ZN_6 | 17.51 | 42.18 | 1911.37 | 0.000 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
BASEMENT | CAV_BAS | 62.11 | 149.60 | 6779.02 | 2779.43 | 1.2002 | 1.200 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
CORE_MID | VAV_MID WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 10.778 |
CORE_TOP | VAV_TOP WITH REHEAT | 55.78 | 134.35 | 6849.35 | 2496.12 | 0.0000 | 1.078 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 3.94 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 1.353 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.872 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.00 | 313.41 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 7.00 | 16.87 | 860.02 | 313.42 | 0.0000 | 0.135 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 4.51 | 10.87 | 554.22 | 201.98 | 0.0000 | 0.087 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.81 | 1.95 | 99.34 | 36.20 | 0.1563 | 0.156 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.81 | 1.95 | 99.34 | 36.20 | 0.0156 | 0.016 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 17.51 | 42.18 | 1911.37 | 783.68 | 0.3384 | 0.338 |
Total Facility | 1029.47 | 2493.19 | 126016.35 | 46320.38 | 1.7261 | 158.471 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
BASEMENT | 58520265.41 | 0.00 | 58520265.41 | 0.00 | 58520265.41 | 37848132.68 | 3847.12 | 1049.19 | 3863.69 | 442.02 |
CORE_BOTTOM | 45071363.62 | 0.00 | 45071363.62 | 0.00 | 45071363.62 | 33990283.35 | 4531.58 | 39.11 | 4189.31 | 597.66 |
CORE_MID | 0.32E+09 | 0.00 | 0.32E+09 | 0.00 | 0.32E+09 | 0.34E+09 | 5987.58 | 36.52 | 2735.90 | 312.21 |
CORE_TOP | 30237585.42 | 0.00 | 30237585.42 | 0.00 | 30237585.42 | 33990283.35 | 6358.71 | 31.76 | 2369.54 | 398.89 |
PERIMETER_BOT_ZN_3 | 5088173.53 | 0.00 | 5088173.53 | 451114.65 | 5539288.18 | 4267819.30 | 4957.02 | 57.01 | 3745.97 | 597.66 |
PERIMETER_BOT_ZN_2 | 5448240.25 | 0.00 | 5448240.25 | 300742.89 | 5748983.14 | 2750345.05 | 3312.98 | 11.15 | 5435.87 | 597.66 |
PERIMETER_BOT_ZN_1 | 8713644.64 | 0.00 | 8713644.64 | 451114.65 | 9164759.28 | 4267912.63 | 3699.93 | 42.72 | 5017.35 | 597.66 |
PERIMETER_BOT_ZN_4 | 7550522.44 | 0.00 | 7550522.44 | 300742.89 | 7851265.33 | 2750345.05 | 3256.34 | 4.50 | 5499.16 | 597.66 |
PERIMETER_MID_ZN_3 | 39594150.69 | 0.00 | 39594150.69 | 1057988.21 | 40652138.90 | 42678193.03 | 5533.04 | 41.98 | 3184.97 | 312.21 |
PERIMETER_MID_ZN_2 | 49712974.66 | 0.00 | 49712974.66 | 705324.99 | 50418299.65 | 27503450.52 | 3830.01 | 9.44 | 4920.55 | 1221.21 |
PERIMETER_MID_ZN_1 | 76558505.11 | 0.00 | 76558505.11 | 1057988.21 | 77616493.32 | 42679126.28 | 3965.70 | 18.65 | 4775.66 | 312.21 |
PERIMETER_MID_ZN_4 | 48720932.68 | 0.00 | 48720932.68 | 705324.99 | 49426257.68 | 27503450.52 | 3809.97 | 12.58 | 4937.44 | 312.21 |
PERIMETER_TOP_ZN_3 | 4003201.46 | 0.00 | 4003201.46 | 1313602.61 | 5316804.07 | 4267819.30 | 5408.53 | 52.68 | 3298.78 | 398.89 |
PERIMETER_TOP_ZN_2 | 4867460.96 | 0.00 | 4867460.96 | 875734.47 | 5743195.43 | 2750345.05 | 3974.34 | 3.62 | 4782.04 | 398.89 |
PERIMETER_TOP_ZN_1 | 7451141.81 | 0.00 | 7451141.81 | 1313602.61 | 8764744.41 | 4267912.63 | 4027.08 | 3.28 | 4729.64 | 398.89 |
PERIMETER_TOP_ZN_4 | 4962601.77 | 0.00 | 4962601.77 | 875734.47 | 5838336.24 | 2750345.05 | 3964.57 | 5.38 | 4790.05 | 398.89 |
DATACENTER_BOT_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2442960.18 | 0.00 | 2442960.18 | 0.00 | 2442960.18 | 4929815.99 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 244296.02 | 0.00 | 244296.02 | 0.00 | 244296.02 | 492981.60 | 4419.00 | 4341.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 5288266.81 | 0.00 | 5288266.81 | 0.00 | 5288266.81 | 10671554.30 | 4419.00 | 4341.00 | 0.00 | 0.00 |
Total Facility | 0.56E+10 | 0.00 | 0.56E+10 | 41148653.23 | 0.56E+10 | 0.50E+10 | 6821.58 | 4413.70 | 5703.62 | 1957.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
BASEMENT | 2.5774 | 0.0000 | 2.5774 | 0.0000 | 2.5774 | 1.2002 | 1312.35 | 1045.93 | 3584.72 |
CORE_BOTTOM | 1.9285 | 0.0000 | 1.9285 | 0.0000 | 1.9285 | 1.0778 | 2210.37 | 35.53 | 3697.10 |
CORE_MID | 14.2912 | 0.0000 | 14.2912 | 0.0000 | 14.2912 | 10.7782 | 3321.81 | 35.24 | 2585.95 |
CORE_TOP | 1.3618 | 0.0000 | 1.3618 | 0.0000 | 1.3618 | 1.0778 | 3653.86 | 31.76 | 2257.38 |
PERIMETER_BOT_ZN_3 | 0.2166 | 0.0000 | 0.2166 | 0.0102 | 0.2267 | 0.1353 | 2628.06 | 52.89 | 3262.05 |
PERIMETER_BOT_ZN_2 | 0.2322 | 0.0000 | 0.2322 | 0.0068 | 0.2390 | 0.0872 | 1069.72 | 9.94 | 4863.34 |
PERIMETER_BOT_ZN_1 | 0.3815 | 0.0000 | 0.3815 | 0.0102 | 0.3917 | 0.1353 | 1410.06 | 39.91 | 4493.03 |
PERIMETER_BOT_ZN_4 | 0.3215 | 0.0000 | 0.3215 | 0.0068 | 0.3283 | 0.0872 | 1026.15 | 2.76 | 4914.08 |
PERIMETER_MID_ZN_3 | 1.7736 | 0.0000 | 1.7736 | 0.0239 | 1.7975 | 1.3533 | 2871.67 | 40.01 | 3031.32 |
PERIMETER_MID_ZN_2 | 2.1052 | 0.0000 | 2.1052 | 0.0171 | 2.1223 | 0.8721 | 1200.01 | 4.34 | 3829.64 |
PERIMETER_MID_ZN_1 | 3.4870 | 0.0000 | 3.4870 | 0.0239 | 3.5109 | 1.3533 | 1305.56 | 18.33 | 4619.10 |
PERIMETER_MID_ZN_4 | 2.1802 | 0.0000 | 2.1802 | 0.0159 | 2.1961 | 0.8721 | 1189.53 | 7.53 | 4745.93 |
PERIMETER_TOP_ZN_3 | 0.1806 | 0.0000 | 0.1806 | 0.0297 | 0.2103 | 0.1353 | 2706.55 | 52.47 | 3183.98 |
PERIMETER_TOP_ZN_2 | 0.2206 | 0.0000 | 0.2206 | 0.0198 | 0.2404 | 0.0872 | 1287.29 | 2.47 | 4653.24 |
PERIMETER_TOP_ZN_1 | 0.3402 | 0.0000 | 0.3402 | 0.0297 | 0.3698 | 0.1353 | 1325.83 | 2.95 | 4614.23 |
PERIMETER_TOP_ZN_4 | 0.2234 | 0.0000 | 0.2234 | 0.0198 | 0.2432 | 0.0872 | 1283.14 | 3.95 | 4655.91 |
DATACENTER_BOT_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.1142 | 0.0000 | 0.1142 | 0.0000 | 0.1142 | 0.1563 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.0114 | 0.0000 | 0.0114 | 0.0000 | 0.0114 | 0.0156 | 1602.00 | 4341.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.2472 | 0.0000 | 0.2472 | 0.0000 | 0.2472 | 0.3384 | 1602.00 | 4341.00 | 0.00 |
Total Facility | 247.7681 | 0.0000 | 247.7681 | 0.9407 | 248.7088 | 158.4706 | 4004.58 | 4385.89 | 4983.25 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
VAV_BOT WITH REHEAT | 68665418.81 | 0.00 | 68665418.81 | 48026705.38 | 3488.75 | 374.36 | 4896.89 | 597.66 |
VAV_MID WITH REHEAT | 0.51E+09 | 0.00 | 0.51E+09 | 0.48E+09 | 3988.17 | 208.27 | 4563.56 | 312.21 |
VAV_TOP WITH REHEAT | 49223293.95 | 0.00 | 49223293.95 | 48026705.38 | 4071.23 | 338.02 | 4350.76 | 398.72 |
CAV_BAS | 55909341.98 | 0.00 | 55909341.98 | 37848132.68 | 4915.74 | 18.89 | 3825.38 | 442.02 |
AIRLOOP DATACENTER BASEMENT | 5052327.01 | 0.00 | 5052327.01 | 10671554.30 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 2333965.77 | 0.00 | 2333965.77 | 4929815.99 | 8760.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 233396.58 | 0.00 | 233396.58 | 492981.60 | 8760.00 | 0.00 | 0.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
VAV_BOT WITH REHEAT | 2.9429 | 0.0000 | 2.9429 | 1.5229 | 1184.51 | 369.90 | 4388.60 |
VAV_MID WITH REHEAT | 22.9006 | 0.0000 | 22.9006 | 15.2292 | 1324.02 | 208.27 | 4410.71 |
VAV_TOP WITH REHEAT | 2.2228 | 0.0000 | 2.2228 | 1.5229 | 1366.46 | 338.02 | 4238.52 |
CAV_BAS | 2.4624 | 0.0000 | 2.4624 | 1.2002 | 2372.85 | 13.45 | 3556.70 |
AIRLOOP DATACENTER BASEMENT | 0.2361 | 0.0000 | 0.2361 | 0.3384 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.1091 | 0.0000 | 0.1091 | 0.1563 | 5943.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.0109 | 0.0000 | 0.0109 | 0.0156 | 5943.00 | 0.00 | 0.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
VAV_BOT WITH REHEAT | 0.00 | 0.08 | 4045.42 | 0.00 | 0.00 | 0.00 | 1485.56 | 0.00 | 0.00 | 0.00 |
VAV_MID WITH REHEAT | 0.00 | 0.03 | 3688.87 | 0.00 | 0.00 | 0.00 | 1459.25 | 0.00 | 0.00 | 0.00 |
VAV_TOP WITH REHEAT | 0.00 | 0.00 | 3058.95 | 0.00 | 0.00 | 0.00 | 2200.28 | 0.00 | 0.00 | 0.00 |
CAV_BAS | 0.00 | 1039.08 | 4071.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BASEMENT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER BOT | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER MID | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
AIRLOOP DATACENTER TOP | 0.00 | 4341.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
VAV_BOT WITH REHEAT | 0.0000 | 0.0000 | 4.3767 | 0.0000 | 0.0000 | 0.0000 | 1.6176 | 0.0000 | 0.0000 | 0.0000 |
VAV_MID WITH REHEAT | 0.0000 | 0.0000 | 33.4452 | 0.0000 | 0.0000 | 0.0000 | 15.8904 | 0.0000 | 0.0000 | 0.0000 |
VAV_TOP WITH REHEAT | 0.0000 | 0.0000 | 3.6629 | 0.0000 | 0.0000 | 0.0000 | 1.5760 | 0.0000 | 0.0000 | 0.0000 |
CAV_BAS | 0.0000 | 1.1467 | 3.7042 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BASEMENT | 0.0000 | 0.3234 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER BOT | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER MID | 0.0000 | 0.1494 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
AIRLOOP DATACENTER TOP | 0.0000 | 0.0149 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Surfaces by ClassTotal | Outdoors | |
Wall | 98 | 30 |
Floor | 41 | 0 |
Roof | 30 | 1 |
Internal Mass | 16 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 24 | 24 |
Door | 12 | 12 |
Glass Door | 0 | 0 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 8 |
Conditioned Zones | 23 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 3 |
Count | |
IDF Objects | 1380 |
Defaulted Fields | 1179 |
Fields with Defaults | 3862 |
Autosized Fields | 330 |
Autosizable Fields | 409 |
Autocalculated Fields | 226 |
Autocalculatable Fields | 473 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
Electricity:Building | 17957.28 | 247233.96 | 01-JAN-08:50 | 1055078.17 | 01-DEC-16:30 |
Electricity:Zone:BASEMENT | 602.14 | 14319.77 | 01-JAN-00:10 | 28977.00 | 02-JAN-08:10 |
Electricity:SpaceType:GENERAL | 17957.28 | 247233.96 | 01-JAN-08:50 | 1055078.17 | 01-DEC-16:30 |
InteriorLights:Electricity | 2743.87 | 13024.70 | 01-JAN-08:50 | 261074.09 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 2743.87 | 13024.70 | 01-JAN-08:50 | 261074.09 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity | 2743.87 | 13024.70 | 01-JAN-08:50 | 261074.09 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:BASEMENT | 177.74 | 862.23 | 01-JAN-00:10 | 15519.45 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 2743.87 | 13024.70 | 01-JAN-08:50 | 261074.09 | 02-JAN-16:50 |
Electricity:Zone:CORE_BOTTOM | 480.91 | 6817.20 | 01-JAN-00:10 | 32066.15 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_BOTTOM | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:CORE_MID | 4809.09 | 68171.81 | 01-JAN-00:10 | 320660.81 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_MID | 1596.25 | 7743.41 | 01-JAN-00:10 | 139375.61 | 02-JAN-08:10 |
Electricity:Zone:CORE_TOP | 480.91 | 6817.18 | 01-JAN-00:10 | 32066.08 | 02-JAN-08:10 |
InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:CORE_TOP | 159.62 | 774.34 | 01-JAN-00:10 | 13937.56 | 02-JAN-08:10 |
Electricity:Zone:PERIMETER_BOT_ZN_3 | 54.19 | 818.50 | 01-JAN-08:50 | 4026.32 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.85 | 59.73 | 01-JAN-08:50 | 1750.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_3 | 13.85 | 59.73 | 01-JAN-08:50 | 1750.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_2 | 34.92 | 527.47 | 01-JAN-07:50 | 2594.71 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.93 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_2 | 8.93 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_1 | 54.09 | 818.51 | 01-JAN-08:00 | 4026.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.75 | 59.73 | 01-JAN-08:00 | 1750.04 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_1 | 13.75 | 59.73 | 01-JAN-08:00 | 1750.04 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_BOT_ZN_4 | 34.86 | 527.47 | 01-JAN-08:50 | 2594.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_BOT_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_3 | 542.05 | 8184.99 | 01-JAN-08:50 | 40263.18 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 138.62 | 597.26 | 01-JAN-08:50 | 17500.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_3 | 138.62 | 597.26 | 01-JAN-08:50 | 17500.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_2 | 349.26 | 5274.72 | 01-JAN-07:50 | 25947.12 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.28 | 384.90 | 01-JAN-07:50 | 11277.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_2 | 89.28 | 384.90 | 01-JAN-07:50 | 11277.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_1 | 540.95 | 8185.12 | 01-JAN-08:00 | 40263.91 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.53 | 597.27 | 01-JAN-08:00 | 17500.38 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_1 | 137.53 | 597.27 | 01-JAN-08:00 | 17500.38 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_MID_ZN_4 | 348.60 | 5274.69 | 01-JAN-08:50 | 25947.03 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.62 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_MID_ZN_4 | 88.62 | 384.90 | 01-JAN-08:50 | 11277.66 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_3 | 54.20 | 818.50 | 01-JAN-08:50 | 4026.32 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.86 | 59.73 | 01-JAN-08:50 | 1750.00 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_3 | 13.86 | 59.73 | 01-JAN-08:50 | 1750.00 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_2 | 34.93 | 527.47 | 01-JAN-07:50 | 2594.71 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.93 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_2 | 8.93 | 38.49 | 01-JAN-07:50 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_1 | 54.10 | 818.51 | 01-JAN-08:00 | 4026.39 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.75 | 59.73 | 01-JAN-08:00 | 1750.04 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_1 | 13.75 | 59.73 | 01-JAN-08:00 | 1750.04 | 02-JAN-16:50 |
Electricity:Zone:PERIMETER_TOP_ZN_4 | 34.86 | 527.47 | 01-JAN-08:50 | 2594.70 | 02-JAN-16:50 |
InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
LightsWired:InteriorLights:Electricity:Zone:PERIMETER_TOP_ZN_4 | 8.86 | 38.49 | 01-JAN-08:50 | 1127.77 | 02-JAN-16:50 |
Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7544.97 | 95151.24 | 01-JAN-00:10 | 384008.34 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 50.12 | 243.11 | 01-JAN-00:10 | 4375.82 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_BOT_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_BOT_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_MID_ZN_6 | 1585.20 | 19711.13 | 01-JAN-00:10 | 81995.25 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_MID_ZN_6 | 46.40 | 225.07 | 01-JAN-00:10 | 4051.03 | 02-JAN-08:10 |
Electricity:Zone:DATACENTER_TOP_ZN_6 | 158.52 | 1971.11 | 01-JAN-00:10 | 8199.53 | 03-APR-07:10 |
InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
LightsWired:InteriorLights:Electricity:Zone:DATACENTER_TOP_ZN_6 | 4.64 | 22.51 | 01-JAN-00:10 | 405.10 | 02-JAN-08:10 |
InteriorEquipment:Electricity | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 15213.41 | 234209.26 | 01-JAN-00:10 | 794004.08 | 03-APR-07:10 |
MiscPlug:InteriorEquipment:Electricity | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:BASEMENT | 424.40 | 13457.54 | 01-JAN-00:10 | 13457.54 | 01-JAN-00:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 5871.99 | 115917.86 | 01-JAN-00:10 | 320838.49 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_BOTTOM | 321.29 | 6042.86 | 01-JAN-00:10 | 18128.59 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_MID | 3212.85 | 60428.40 | 01-JAN-00:10 | 181285.20 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:CORE_TOP | 321.28 | 6042.84 | 01-JAN-00:10 | 18128.52 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_BOT_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_3 | 403.42 | 7587.73 | 01-JAN-00:10 | 22763.18 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_2 | 259.98 | 4889.82 | 01-JAN-00:10 | 14669.46 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_1 | 403.43 | 7587.84 | 01-JAN-00:10 | 22763.53 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_MID_ZN_4 | 259.98 | 4889.79 | 01-JAN-00:10 | 14669.36 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_3 | 40.34 | 758.77 | 01-JAN-00:10 | 2276.32 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_2 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.95 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_1 | 40.34 | 758.78 | 01-JAN-00:10 | 2276.35 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:PERIMETER_TOP_ZN_4 | 26.00 | 488.98 | 01-JAN-00:10 | 1466.94 | 02-JAN-08:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BASEMENT_ZN_6 | 7494.86 | 94908.13 | 01-JAN-00:10 | 379632.52 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:SpaceType:GENERAL | 9341.42 | 118291.40 | 01-JAN-00:10 | 473165.59 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_BOT_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_MID_ZN_6 | 1538.81 | 19486.06 | 01-JAN-00:10 | 77944.22 | 31-MAR-23:10 |
InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
DataCenterPlugLoads:InteriorEquipment:Electricity:Zone:DATACENTER_TOP_ZN_6 | 153.88 | 1948.61 | 01-JAN-00:10 | 7794.42 | 31-MAR-23:10 |
Electricity:Plant | 2147.93 | 5903.68 | 05-JAN-19:00 | 346058.10 | 16-AUG-15:10 |
HeatRejection:Electricity | 941.82 | 1996.74 | 05-JAN-19:00 | 80361.09 | 15-JUN-13:20 |
General:HeatRejection:Electricity | 941.82 | 1996.74 | 05-JAN-19:00 | 80361.09 | 15-JUN-13:20 |
Electricity:HVAC | 7121.54 | 109912.65 | 08-JAN-03:30 | 543667.66 | 11-AUG-15:10 |
ExteriorEquipment:Electricity | 1914.38 | 28294.68 | 01-JAN-00:10 | 117200.65 | 21-DEC-08:20 |
Transformer:ExteriorEquipment:Electricity | 59.77 | 1112.61 | 01-JAN-00:10 | 3726.76 | 01-DEC-16:40 |
ElectricityPurchased:Facility | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
ElectricityPurchased:Plant | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
Cogeneration:ElectricityPurchased | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
General:Cogeneration:ElectricityPurchased | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
ElectricityNet:Plant | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
Cogeneration:ElectricityNet | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
General:Cogeneration:ElectricityNet | 29530.12 | 400045.56 | 16-JAN-10:10 | 1989326.38 | 16-AUG-15:10 |
Fans:Electricity | 2810.89 | 50855.16 | 05-JAN-22:20 | 293477.65 | 24-JUL-15:20 |
General:Fans:Electricity | 2810.89 | 50855.16 | 05-JAN-22:20 | 293477.65 | 24-JUL-15:20 |
ExteriorLights:Electricity | 448.76 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
General:ExteriorLights:Electricity | 448.76 | 0.00 | 01-JAN-07:30 | 37611.08 | 01-JAN-06:10 |
ElevatorLift:ExteriorEquipment:Electricity | 1848.78 | 27144.47 | 01-JAN-00:10 | 113101.96 | 01-JAN-07:10 |
ElevatorLightsFan:ExteriorEquipment:Electricity | 5.83 | 37.60 | 01-JAN-00:10 | 376.00 | 01-JAN-07:10 |
Cooling:Electricity | 3675.74 | 34786.80 | 05-JAN-07:10 | 432978.75 | 16-AUG-15:10 |
General:Cooling:Electricity | 3675.74 | 34786.80 | 05-JAN-07:10 | 432978.75 | 16-AUG-15:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Humidifier:Electricity | 1283.48 | 0.00 | 31-AUG-23:10 | 82269.92 | 17-AUG-06:10 |
General:Humidifier:Electricity | 1283.48 | 0.00 | 31-AUG-23:10 | 82269.92 | 17-AUG-06:10 |
Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Pumps:Electricity | 497.77 | 3734.71 | 01-JAN-00:10 | 64100.48 | 18-JUL-15:10 |
General:Pumps:Electricity | 497.77 | 3734.71 | 01-JAN-00:10 | 64100.48 | 18-JUL-15:10 |
WIRED_LTG_ELECTRICITY | 77.10 | 0.00 | 01-JAN-00:10 | 7336.18 | 02-JAN-17:00 |
WIRED_INT_EQUIP | 5871.99 | 115917.86 | 04-MAR-00:10 | 320838.49 | 03-APR-07:10 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2622.65 | 5695.87 | 08-APR-16:10 | 1489319.31 | 23-DEC-07:20 |
NaturalGas:Plant | 2622.65 | 5695.87 | 08-APR-16:10 | 1489319.31 | 23-DEC-07:20 |
Heating:NaturalGas | 1885.80 | 0.00 | 01-JAN-00:10 | 1461485.81 | 23-DEC-07:20 |
Boiler:Heating:NaturalGas | 1885.80 | 0.00 | 01-JAN-00:10 | 1461485.81 | 23-DEC-07:20 |
WaterSystems:NaturalGas | 736.85 | 5695.87 | 05-JAN-04:20 | 83550.15 | 10-FEB-12:30 |
Water Heater:WaterSystems:NaturalGas | 736.85 | 5695.87 | 05-JAN-04:20 | 83550.15 | 10-FEB-12:30 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
PlantLoopCoolingDemand:Facility | 19304.55 | 169866.92 | 05-JAN-08:00 | 2349938.71 | 16-AUG-15:10 |
PlantLoopCoolingDemand:HVAC | 19304.55 | 169866.92 | 05-JAN-08:00 | 2349938.71 | 16-AUG-15:10 |
CoolingCoils:PlantLoopCoolingDemand | 19304.55 | 169866.92 | 05-JAN-08:00 | 2349938.71 | 16-AUG-15:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 7662.26 | 0.00 | 31-AUG-23:10 | 0.00 | 26-JUN-15:10 |
Water:HVAC | 477.46 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
Humidifier:Water | 477.46 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
General:Humidifier:Water | 477.46 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
MainsWater:Facility | 7662.26 | 0.00 | 31-AUG-23:10 | 0.00 | 26-JUN-15:10 |
MainsWater:HVAC | 477.46 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
Humidifier:MainsWater | 477.46 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
General:Humidifier:MainsWater | 477.46 | 0.00 | 31-AUG-23:10 | 0.00 | 17-AUG-06:10 |
Water:Plant | 7184.80 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:Water | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
MainsWater:Plant | 7184.80 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-15:10 |
WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
WaterUse:WaterSystems:MainsWater | 2280.17 | 0.00 | 01-JAN-00:10 | 0.00 | 02-JAN-12:10 |
Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
HeatRejection:Water | 4904.64 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:50 |
General:HeatRejection:Water | 4904.64 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:50 |
HeatRejection:MainsWater | 4904.64 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:50 |
General:HeatRejection:MainsWater | 4904.64 | 0.00 | 01-JAN-00:10 | 0.00 | 26-JUN-16:50 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 53680.41 | 243792.19 | 08-JAN-02:50 | 8799004.70 | 16-AUG-15:10 |
EnergyTransfer:Building | 18500.41 | 88196.06 | 08-JAN-14:10 | 1583767.24 | 31-AUG-15:30 |
EnergyTransfer:Zone:BASEMENT | 645.76 | 0.00 | 01-JAN-00:40 | 68664.89 | 05-SEP-05:10 |
Heating:EnergyTransfer | 529.43 | 0.00 | 10-JAN-22:10 | 833535.72 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:BASEMENT | 3.17 | 0.00 | 01-JAN-00:20 | 19874.72 | 15-JUL-16:10 |
General:Heating:EnergyTransfer | 529.43 | 0.00 | 10-JAN-22:10 | 833535.72 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:BASEMENT | 3.17 | 0.00 | 01-JAN-00:20 | 19874.72 | 15-JUL-16:10 |
Cooling:EnergyTransfer | 17970.98 | 86802.33 | 08-JAN-05:30 | 1583767.24 | 31-AUG-15:30 |
Cooling:EnergyTransfer:Zone:BASEMENT | 642.59 | 0.00 | 01-JAN-00:40 | 68664.89 | 05-SEP-05:10 |
General:Cooling:EnergyTransfer | 17970.98 | 86802.33 | 08-JAN-05:30 | 1583767.24 | 31-AUG-15:30 |
General:Cooling:EnergyTransfer:Zone:BASEMENT | 642.59 | 0.00 | 01-JAN-00:40 | 68664.89 | 05-SEP-05:10 |
EnergyTransfer:Zone:CORE_BOTTOM | 605.52 | 0.00 | 01-JAN-00:10 | 55728.01 | 21-AUG-10:10 |
Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:CORE_BOTTOM | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 605.52 | 0.00 | 01-JAN-00:10 | 55728.01 | 21-AUG-10:10 |
General:Cooling:EnergyTransfer:Zone:CORE_BOTTOM | 605.52 | 0.00 | 01-JAN-00:10 | 55728.01 | 21-AUG-10:10 |
EnergyTransfer:Zone:CORE_MID | 4194.13 | 0.00 | 01-JAN-00:10 | 422287.88 | 24-JUL-13:10 |
Heating:EnergyTransfer:Zone:CORE_MID | 1.64 | 0.00 | 01-JAN-00:10 | 263407.90 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:CORE_MID | 1.64 | 0.00 | 01-JAN-00:10 | 263407.90 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:CORE_MID | 4192.49 | 0.00 | 01-JAN-00:10 | 422287.88 | 24-JUL-13:10 |
General:Cooling:EnergyTransfer:Zone:CORE_MID | 4192.49 | 0.00 | 01-JAN-00:10 | 422287.88 | 24-JUL-13:10 |
EnergyTransfer:Zone:CORE_TOP | 384.68 | 0.00 | 01-JAN-00:10 | 66579.80 | 06-FEB-05:10 |
Heating:EnergyTransfer:Zone:CORE_TOP | 12.30 | 0.00 | 01-JAN-00:10 | 66579.80 | 06-FEB-05:10 |
General:Heating:EnergyTransfer:Zone:CORE_TOP | 12.30 | 0.00 | 01-JAN-00:10 | 66579.80 | 06-FEB-05:10 |
Cooling:EnergyTransfer:Zone:CORE_TOP | 372.38 | 0.00 | 01-JAN-00:10 | 52123.44 | 26-JUN-14:40 |
General:Cooling:EnergyTransfer:Zone:CORE_TOP | 372.38 | 0.00 | 01-JAN-00:10 | 52123.44 | 26-JUN-14:40 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.97 | 0.00 | 01-JAN-00:10 | 11036.25 | 17-JUL-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.66 | 0.00 | 01-JAN-00:10 | 7125.44 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 0.66 | 0.00 | 01-JAN-00:10 | 7125.44 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.31 | 0.00 | 01-JAN-00:10 | 11036.25 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_3 | 66.31 | 0.00 | 01-JAN-00:10 | 11036.25 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.74 | 0.00 | 01-JAN-00:10 | 13153.46 | 17-JUL-08:20 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.64 | 0.00 | 01-JAN-00:10 | 6186.02 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 0.64 | 0.00 | 01-JAN-00:10 | 6186.02 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.10 | 0.00 | 01-JAN-00:10 | 13153.46 | 17-JUL-08:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_2 | 67.10 | 0.00 | 01-JAN-00:10 | 13153.46 | 17-JUL-08:20 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 115.66 | 0.00 | 01-JAN-00:10 | 18318.11 | 28-SEP-13:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.02 | 0.00 | 01-JAN-00:10 | 8975.40 | 21-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 1.02 | 0.00 | 01-JAN-00:10 | 8975.40 | 21-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.64 | 0.00 | 01-JAN-00:10 | 18318.11 | 28-SEP-13:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_1 | 114.64 | 0.00 | 01-JAN-00:10 | 18318.11 | 28-SEP-13:00 |
EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.43 | 0.00 | 01-JAN-00:10 | 19236.20 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1978.98 | 22-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 0.02 | 0.00 | 01-JAN-00:10 | 1978.98 | 22-DEC-06:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.41 | 0.00 | 01-JAN-00:10 | 19236.20 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_BOT_ZN_4 | 101.41 | 0.00 | 01-JAN-00:10 | 19236.20 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 551.01 | 0.00 | 01-JAN-00:10 | 115157.64 | 22-DEC-04:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 106.41 | 0.00 | 01-JAN-00:10 | 115157.64 | 22-DEC-04:20 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 106.41 | 0.00 | 01-JAN-00:10 | 115157.64 | 22-DEC-04:20 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 444.59 | 0.00 | 01-JAN-00:10 | 101734.43 | 17-JUL-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_3 | 444.59 | 0.00 | 01-JAN-00:10 | 101734.43 | 17-JUL-13:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 618.49 | 0.00 | 01-JAN-00:10 | 138829.69 | 17-JUL-08:30 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 58.01 | 0.00 | 01-JAN-00:10 | 106921.95 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 58.01 | 0.00 | 01-JAN-00:10 | 106921.95 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 560.48 | 0.00 | 01-JAN-00:10 | 138829.69 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_2 | 560.48 | 0.00 | 01-JAN-00:10 | 138829.69 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 1044.18 | 0.00 | 01-JAN-00:10 | 187836.54 | 28-SEP-13:20 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.62 | 0.00 | 01-JAN-00:10 | 140739.13 | 21-DEC-05:30 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 53.62 | 0.00 | 01-JAN-00:10 | 140739.13 | 21-DEC-05:30 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 990.56 | 0.00 | 01-JAN-00:10 | 187836.54 | 28-SEP-13:20 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_1 | 990.56 | 0.00 | 01-JAN-00:10 | 187836.54 | 28-SEP-13:20 |
EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 611.60 | 0.00 | 01-JAN-00:10 | 154980.79 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 40.45 | 0.00 | 01-JAN-00:10 | 98075.39 | 23-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 40.45 | 0.00 | 01-JAN-00:10 | 98075.39 | 23-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 571.15 | 0.00 | 01-JAN-00:10 | 154980.79 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_MID_ZN_4 | 571.15 | 0.00 | 01-JAN-00:10 | 154980.79 | 16-AUG-16:00 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 73.62 | 0.00 | 01-JAN-00:10 | 14989.37 | 19-MAR-07:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.66 | 0.00 | 01-JAN-00:10 | 14989.37 | 19-MAR-07:00 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 32.66 | 0.00 | 01-JAN-00:10 | 14989.37 | 19-MAR-07:00 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.96 | 0.00 | 01-JAN-00:10 | 11291.17 | 17-JUL-13:40 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_3 | 40.96 | 0.00 | 01-JAN-00:10 | 11291.17 | 17-JUL-13:40 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 69.86 | 0.00 | 01-JAN-00:10 | 14589.68 | 23-DEC-05:10 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.32 | 0.00 | 01-JAN-00:10 | 14589.68 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 17.32 | 0.00 | 01-JAN-00:10 | 14589.68 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.54 | 0.00 | 01-JAN-00:10 | 14108.99 | 17-JUL-08:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_2 | 52.54 | 0.00 | 01-JAN-00:10 | 14108.99 | 17-JUL-08:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 109.88 | 0.00 | 01-JAN-00:10 | 20079.52 | 28-SEP-13:30 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 19.09 | 0.00 | 01-JAN-00:10 | 17795.38 | 23-DEC-05:40 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 19.09 | 0.00 | 01-JAN-00:10 | 17795.38 | 23-DEC-05:40 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.79 | 0.00 | 01-JAN-00:10 | 20079.52 | 28-SEP-13:30 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_1 | 90.79 | 0.00 | 01-JAN-00:10 | 20079.52 | 28-SEP-13:30 |
EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 67.21 | 0.00 | 01-JAN-00:10 | 16406.14 | 16-AUG-16:00 |
Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.37 | 0.00 | 01-JAN-00:10 | 14679.35 | 23-DEC-05:10 |
General:Heating:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 13.37 | 0.00 | 01-JAN-00:10 | 14679.35 | 23-DEC-05:10 |
Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.84 | 0.00 | 01-JAN-00:10 | 16406.14 | 16-AUG-16:00 |
General:Cooling:EnergyTransfer:Zone:PERIMETER_TOP_ZN_4 | 53.84 | 0.00 | 01-JAN-00:10 | 16406.14 | 16-AUG-16:00 |
EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 56.44 | 0.00 | 01-JAN-00:10 | 9735.73 | 21-AUG-14:40 |
Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.60 | 0.00 | 01-JAN-00:10 | 4249.91 | 05-MAR-14:50 |
General:Heating:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 3.60 | 0.00 | 01-JAN-00:10 | 4249.91 | 05-MAR-14:50 |
Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.84 | 0.00 | 01-JAN-00:10 | 9735.73 | 21-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:GROUNDFLOOR_PLENUM | 52.84 | 0.00 | 01-JAN-00:10 | 9735.73 | 21-AUG-14:40 |
EnergyTransfer:Zone:MIDFLOOR_PLENUM | 444.74 | 0.00 | 01-JAN-00:10 | 80450.39 | 26-DEC-06:10 |
Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 117.01 | 0.00 | 01-JAN-00:10 | 80450.39 | 26-DEC-06:10 |
General:Heating:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 117.01 | 0.00 | 01-JAN-00:10 | 80450.39 | 26-DEC-06:10 |
Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 327.73 | 0.00 | 01-JAN-00:10 | 76686.68 | 17-JUL-16:00 |
General:Cooling:EnergyTransfer:Zone:MIDFLOOR_PLENUM | 327.73 | 0.00 | 01-JAN-00:10 | 76686.68 | 17-JUL-16:00 |
EnergyTransfer:Zone:TOPFLOOR_PLENUM | 105.09 | 0.00 | 01-JAN-00:10 | 26393.77 | 13-FEB-05:30 |
Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.47 | 0.00 | 01-JAN-00:10 | 26393.77 | 13-FEB-05:30 |
General:Heating:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 46.47 | 0.00 | 01-JAN-00:10 | 26393.77 | 13-FEB-05:30 |
Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.63 | 0.00 | 01-JAN-00:10 | 22207.99 | 26-JUN-13:30 |
General:Cooling:EnergyTransfer:Zone:TOPFLOOR_PLENUM | 58.63 | 0.00 | 01-JAN-00:10 | 22207.99 | 26-JUN-13:30 |
EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.48 | 475.33 | 06-JAN-06:20 | 8425.85 | 05-AUG-18:40 |
Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.48 | 475.33 | 06-JAN-06:20 | 8425.85 | 05-AUG-18:40 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BOT_ZN_6 | 138.48 | 475.33 | 06-JAN-06:20 | 8425.85 | 05-AUG-18:40 |
EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1187.99 | 13.17 | 08-JAN-19:40 | 78653.25 | 05-AUG-18:20 |
Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1.12 | 0.00 | 01-JAN-15:00 | 4837.41 | 01-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1.12 | 0.00 | 01-JAN-15:00 | 4837.41 | 01-JAN-08:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1186.87 | 0.00 | 01-JAN-00:10 | 78653.25 | 05-AUG-18:20 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_MID_ZN_6 | 1186.87 | 0.00 | 01-JAN-00:10 | 78653.25 | 05-AUG-18:20 |
EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 108.51 | 0.65 | 05-JAN-19:20 | 7974.89 | 13-AUG-18:50 |
Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.85 | 0.00 | 02-JAN-13:20 | 720.62 | 30-APR-23:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 0.85 | 0.00 | 02-JAN-13:20 | 720.62 | 30-APR-23:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.66 | 0.00 | 01-JAN-00:10 | 7974.89 | 13-AUG-18:50 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_TOP_ZN_6 | 107.66 | 0.00 | 01-JAN-00:10 | 7974.89 | 13-AUG-18:50 |
EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7131.42 | 86165.63 | 08-JAN-06:00 | 366701.78 | 18-DEC-17:00 |
Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7131.42 | 86165.63 | 08-JAN-06:00 | 366701.78 | 18-DEC-17:00 |
General:Cooling:EnergyTransfer:Zone:DATACENTER_BASEMENT_ZN_6 | 7131.42 | 86165.63 | 08-JAN-06:00 | 366701.78 | 18-DEC-17:00 |
PlantLoopHeatingDemand:Facility | 1858.18 | 0.00 | 01-JAN-00:10 | 1245456.46 | 23-DEC-07:10 |
PlantLoopHeatingDemand:Plant | 435.47 | 0.00 | 01-JAN-00:10 | 53786.72 | 13-FEB-12:40 |
WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53786.72 | 13-FEB-12:40 |
General:WaterSystems:PlantLoopHeatingDemand | 435.47 | 0.00 | 01-JAN-00:10 | 53786.72 | 13-FEB-12:40 |
EnergyTransfer:HVAC | 17759.86 | 152048.19 | 08-JAN-05:30 | 2131692.43 | 16-AUG-15:10 |
HeatingCoils:EnergyTransfer | 1422.72 | 0.00 | 01-JAN-00:10 | 1235470.06 | 23-DEC-07:10 |
PlantLoopHeatingDemand:HVAC | 1422.72 | 0.00 | 01-JAN-00:10 | 1235470.06 | 23-DEC-07:10 |
HeatingCoils:PlantLoopHeatingDemand | 1422.72 | 0.00 | 01-JAN-00:10 | 1235470.06 | 23-DEC-07:10 |
CoolingCoils:EnergyTransfer | 16337.15 | 135078.38 | 05-JAN-08:00 | 2131692.43 | 16-AUG-15:10 |
EnergyTransfer:Plant | 17420.14 | 0.00 | 01-JAN-00:10 | 5270772.41 | 26-JUN-15:10 |
LoopToLoop:EnergyTransfer | 5206.80 | -3046.28 | 09-JAN-13:20 | 1665983.21 | 26-JUN-15:10 |
WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53786.72 | 13-FEB-12:40 |
WaterUse:WaterSystems:EnergyTransfer | 435.47 | 0.00 | 01-JAN-00:10 | 53786.72 | 13-FEB-12:40 |
Boilers:EnergyTransfer | 1415.36 | 0.00 | 01-JAN-00:10 | 1220855.61 | 23-DEC-07:20 |
Chillers:EnergyTransfer | 4827.09 | 0.00 | 01-JAN-00:10 | 1674456.29 | 26-JUN-15:10 |
HeatRejection:EnergyTransfer | 5535.43 | 0.00 | 01-JAN-00:10 | 1896256.74 | 26-JUN-15:10 |
General:HeatRejection:EnergyTransfer | 5535.43 | 0.00 | 01-JAN-00:10 | 1896256.74 | 26-JUN-15:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
BASEMENT | 0.000 | 0.000 | 3.175 | -642.585 | 0.000 | 0.000 | 92.777 | 177.742 | 424.397 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -55.505 |
CORE_BOTTOM | 0.000 | 0.000 | 0.000 | -605.516 | 0.000 | 0.000 | 83.446 | 159.625 | 321.286 | 0.000 | 0.000 | 0.000 | 41.160 | 0.000 | 0.000 | 0.000 | 0.000 | -0.005 |
CORE_MID | 0.000 | 0.000 | 1.642 | -4192.470 | 0.000 | 0.000 | 845.711 | 1596.246 | 3212.845 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -1463.974 |
CORE_TOP | 0.000 | 0.000 | 12.303 | -372.374 | 0.000 | 0.000 | 87.720 | 159.625 | 321.285 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -208.558 |
PERIMETER_BOT_ZN_3 | 0.000 | 0.000 | 0.662 | -66.305 | 0.000 | 0.000 | 10.848 | 13.852 | 40.342 | 26.238 | 0.000 | 0.126 | 38.227 | 0.000 | -57.435 | 0.000 | -6.555 | 0.000 |
PERIMETER_BOT_ZN_2 | 0.000 | 0.000 | 0.640 | -67.096 | 0.000 | 0.000 | 6.990 | 8.925 | 25.998 | 61.341 | 0.000 | 0.085 | 3.259 | 0.000 | -35.821 | 0.000 | -4.321 | -0.000 |
PERIMETER_BOT_ZN_1 | 0.000 | 0.000 | 1.024 | -114.636 | 0.000 | 0.000 | 10.704 | 13.748 | 40.343 | 127.461 | 0.000 | 0.123 | 0.002 | 0.000 | -53.833 | 0.000 | -6.644 | -18.290 |
PERIMETER_BOT_ZN_4 | 0.000 | 0.000 | 0.019 | -101.407 | 0.000 | 0.000 | 6.873 | 8.860 | 25.998 | 55.222 | 0.000 | 0.079 | 49.709 | 0.000 | -40.581 | 0.000 | -4.773 | 0.000 |
PERIMETER_MID_ZN_3 | 0.000 | 0.000 | 106.413 | -444.591 | 0.000 | 0.000 | 113.723 | 138.625 | 403.423 | 273.060 | 0.000 | 2.968 | 66.993 | 0.000 | -522.589 | 0.000 | -138.025 | 0.000 |
PERIMETER_MID_ZN_2 | 0.000 | 0.000 | 58.007 | -560.481 | 0.000 | 0.000 | 52.911 | 89.276 | 259.981 | 614.817 | 0.000 | 1.911 | 0.044 | 0.000 | -337.717 | 0.000 | -94.665 | -84.040 |
PERIMETER_MID_ZN_1 | 0.000 | 0.000 | 53.621 | -990.546 | 0.000 | 0.000 | 108.332 | 137.526 | 403.429 | 1271.642 | 0.000 | 2.809 | 0.041 | 0.000 | -522.375 | 0.000 | -148.788 | -315.650 |
PERIMETER_MID_ZN_4 | 0.000 | 0.000 | 40.450 | -571.149 | 0.000 | 0.000 | 72.593 | 88.622 | 259.979 | 564.752 | 0.000 | 1.907 | 0.022 | 0.000 | -356.841 | 0.000 | -97.186 | -3.127 |
PERIMETER_TOP_ZN_3 | 0.000 | 0.000 | 32.655 | -40.959 | 0.000 | 0.000 | 11.538 | 13.863 | 40.342 | 27.739 | 0.000 | 0.349 | 0.001 | 0.000 | -49.226 | 0.000 | -16.213 | -20.087 |
PERIMETER_TOP_ZN_2 | 0.000 | 0.000 | 17.321 | -52.544 | 0.000 | 0.000 | 7.273 | 8.928 | 25.998 | 61.820 | 0.000 | 0.225 | 0.000 | 0.000 | -32.007 | 0.000 | -11.171 | -25.842 |
PERIMETER_TOP_ZN_1 | 0.000 | 0.000 | 19.087 | -90.792 | 0.000 | 0.000 | 11.012 | 13.753 | 40.343 | 127.745 | 0.000 | 0.336 | 0.003 | 0.000 | -49.390 | 0.000 | -17.479 | -54.614 |
PERIMETER_TOP_ZN_4 | 0.000 | 0.000 | 13.368 | -53.841 | 0.000 | 0.000 | 7.358 | 8.862 | 25.998 | 56.695 | 0.000 | 0.230 | 0.001 | 0.000 | -33.928 | 0.000 | -11.494 | -13.249 |
DATACENTER_BOT_ZN_6 | 0.000 | 0.000 | 0.000 | -138.484 | 0.000 | 0.000 | 0.948 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -20.984 |
DATACENTER_MID_ZN_6 | 0.000 | 0.000 | 1.122 | -1186.865 | 0.000 | 0.000 | 9.490 | 46.396 | 1538.806 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -408.949 |
DATACENTER_TOP_ZN_6 | 0.000 | 0.000 | 0.845 | -107.661 | 0.000 | 0.000 | 0.951 | 4.640 | 153.881 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -52.655 |
DATACENTER_BASEMENT_ZN_6 | 0.000 | 0.000 | 0.000 | -7131.432 | 0.000 | 0.000 | 19.094 | 50.116 | 7494.857 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | -432.635 |
GROUNDFLOOR_PLENUM | 3.602 | -52.841 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.232 | 62.994 | 0.000 | 0.000 | 0.000 | -13.986 | 0.000 |
MIDFLOOR_PLENUM | 117.011 | -327.729 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 4.278 | 444.641 | 0.000 | 0.000 | 0.000 | -238.201 | -0.003 |
TOPFLOOR_PLENUM | 46.466 | -58.627 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.362 | 36.885 | 0.000 | 0.000 | 0.000 | -25.087 | -0.007 |
Total Facility | 167.078 | -439.197 | 362.353 | -17531.733 | 0.000 | 0.000 | 1560.291 | 2743.867 | 15213.411 | 3268.532 | 0.000 | 16.021 | 743.980 | 0.000 | -2091.742 | 0.000 | -834.589 | -3178.175 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 23-OCT-03:01 | 0.00 | 0.00 | 0.00 | -105749.63 | 0.00 | 0.00 | 0.00 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 91429.86 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 13-NOV-04:01 | 0.00 | 0.00 | 0.00 | -86824.09 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.15 | 0.00 | 0.00 | 0.00 | 77992.60 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 28-AUG-03:02 | 0.00 | 0.00 | 0.00 | -793341.22 | 0.00 | 0.00 | 0.00 | 7743.41 | 80571.20 | 0.00 | 0.00 | 0.00 | 705026.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 24-JUL-03:02 | 0.00 | 0.00 | 0.00 | -80826.36 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 71994.90 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 16-JUL-14:12 | 0.00 | 0.00 | 0.00 | -15734.12 | 0.00 | 0.00 | 40.14 | 59.73 | 758.77 | 7875.51 | 0.00 | 291.73 | 6708.24 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 11-JUN-08:62 | 0.00 | 0.00 | 0.00 | -19753.25 | 0.00 | 0.00 | 22.87 | 38.49 | 488.98 | 14728.49 | 0.00 | 0.00 | 4597.82 | 0.00 | -0.00 | 0.00 | -123.41 | 0.00 |
PERIMETER_BOT_ZN_1 | 08-OCT-12:41 | 0.00 | 0.00 | 0.00 | -24515.11 | 0.00 | 0.00 | 31.94 | 59.73 | 758.78 | 23766.65 | 0.00 | 0.00 | 21.26 | 0.00 | -0.00 | 0.00 | -123.26 | 0.00 |
PERIMETER_BOT_ZN_4 | 11-JUN-17:21 | 0.00 | 0.00 | 0.00 | -27898.89 | 0.00 | 0.00 | 0.00 | 38.49 | 488.98 | 14754.23 | 0.00 | 0.00 | 12634.89 | 0.00 | -0.00 | 0.00 | -17.69 | 0.00 |
PERIMETER_MID_ZN_3 | 25-JUN-17:41 | 0.00 | 0.00 | 0.00 | -145795.38 | 0.00 | 0.00 | 0.00 | 597.26 | 7587.73 | 49308.76 | 0.00 | 4452.18 | 83849.46 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 20-AUG-08:51 | 0.00 | 0.00 | 0.00 | -222872.85 | 0.00 | 0.00 | 201.21 | 384.90 | 4889.82 | 150976.83 | 0.00 | 0.00 | 67351.28 | 0.00 | -0.00 | 0.00 | -931.19 | 0.00 |
PERIMETER_MID_ZN_1 | 05-NOV-12:41 | 0.00 | 0.00 | 0.00 | -246535.39 | 0.00 | 0.00 | 292.58 | 597.27 | 7587.84 | 280176.36 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -718.13 | -41400.53 |
PERIMETER_MID_ZN_4 | 25-JUN-16:21 | 0.00 | 0.00 | 0.00 | -252875.94 | 0.00 | 0.00 | 167.58 | 384.90 | 4889.79 | 164065.29 | 0.00 | 1112.24 | 82256.14 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 16-JUL-14:22 | 0.00 | 0.00 | 0.00 | -16611.81 | 0.00 | 0.00 | 37.65 | 59.73 | 758.77 | 7926.68 | 0.00 | 886.04 | 6942.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 02-JUL-09:52 | 0.00 | 0.00 | 0.00 | -20846.32 | 0.00 | 0.00 | 22.22 | 38.49 | 488.98 | 10472.00 | 0.00 | 0.00 | 10151.37 | 0.00 | -0.00 | 0.00 | -326.74 | 0.00 |
PERIMETER_TOP_ZN_1 | 09-OCT-13:41 | 0.00 | 0.00 | 0.00 | -26606.34 | 0.00 | 0.00 | 30.69 | 59.73 | 758.78 | 20923.48 | 0.00 | 0.00 | 5087.90 | 0.00 | -0.00 | 0.00 | -254.26 | 0.00 |
PERIMETER_TOP_ZN_4 | 11-JUN-16:31 | 0.00 | 0.00 | 0.00 | -27218.16 | 0.00 | 0.00 | 16.94 | 38.49 | 488.98 | 15971.64 | 0.00 | 0.00 | 10753.61 | 0.00 | -0.00 | 0.00 | -51.49 | 0.00 |
DATACENTER_BOT_ZN_6 | 05-AUG-18:40 | 0.00 | 0.00 | 0.00 | -8426.42 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 609.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 05-AUG-18:11 | 0.00 | 0.00 | 0.00 | -78653.02 | 0.00 | 0.00 | 0.00 | 225.07 | 77944.22 | 0.00 | 0.00 | 0.00 | 483.73 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 13-AUG-18:50 | 0.00 | 0.00 | 0.00 | -7981.74 | 0.00 | 0.00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 164.82 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 18-DEC-17:00 | 0.00 | 0.00 | 0.00 | -366698.97 | 0.00 | 0.00 | 1927.30 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -19236.67 |
GROUNDFLOOR_PLENUM | 21-AUG-05:15 | 0.00 | -12416.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12472.27 | 0.00 | -0.00 | 0.00 | -55.97 | 0.00 |
MIDFLOOR_PLENUM | 19-MAR-06:33 | 0.00 | -94722.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178560.20 | 0.00 | -0.00 | 0.00 | -83837.41 | 0.00 |
TOPFLOOR_PLENUM | 26-JUN-13:30 | 0.00 | -22206.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.38 | 22053.94 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 17-JUL-05:02 | 0.00 | -20873.43 | 0.00 | -1814440.74 | 0.00 | 0.00 | 15316.02 | 26826.04 | 504945.49 | 68535.07 | 0.00 | 0.00 | 1239662.27 | 0.00 | -16532.40 | 0.00 | -3438.33 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
BASEMENT | 15-JUL-16:01 | 0.00 | 0.00 | 21120.49 | 0.00 | 0.00 | 0.00 | 520.13 | 862.23 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -35960.39 |
CORE_BOTTOM | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 26-DEC-05:01 | 0.00 | 0.00 | 442418.80 | 0.00 | 0.00 | 0.00 | 0.00 | 15486.81 | 80571.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -538476.82 |
CORE_TOP | 06-FEB-04:11 | 0.00 | 0.00 | 75805.68 | 0.00 | 0.00 | 0.00 | 0.00 | 774.34 | 8057.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -84637.14 |
PERIMETER_BOT_ZN_3 | 23-DEC-05:01 | 0.00 | 0.00 | 11808.17 | 0.00 | 0.00 | 0.00 | 0.00 | 97.23 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6440.66 | 0.00 | -1273.32 | -4950.19 |
PERIMETER_BOT_ZN_2 | 23-DEC-05:01 | 0.00 | 0.00 | 11769.61 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4344.43 | 0.00 | -841.86 | -7134.96 |
PERIMETER_BOT_ZN_1 | 06-FEB-05:01 | 0.00 | 0.00 | 16447.03 | 0.00 | 0.00 | 0.00 | 0.00 | 194.46 | 1011.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4543.15 | 0.00 | -617.79 | -12492.26 |
PERIMETER_BOT_ZN_4 | 06-JAN-06:01 | 0.00 | 0.00 | 8298.28 | 0.00 | 0.00 | 0.00 | 94.15 | 125.31 | 651.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2997.38 | 0.00 | -107.57 | -6064.76 |
PERIMETER_MID_ZN_3 | 24-DEC-06:52 | 0.00 | 0.00 | 134252.48 | 0.00 | 0.00 | 0.00 | 907.15 | 972.26 | 7587.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -55995.28 | 0.00 | -33552.08 | -54172.27 |
PERIMETER_MID_ZN_2 | 24-DEC-06:52 | 0.00 | 0.00 | 174819.52 | 0.00 | 0.00 | 0.00 | 585.86 | 626.56 | 4889.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -38585.06 | 0.00 | -22866.79 | -119469.91 |
PERIMETER_MID_ZN_1 | 24-DEC-06:52 | 0.00 | 0.00 | 186725.22 | 0.00 | 0.00 | 0.00 | 902.90 | 972.28 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -58715.14 | 0.00 | -34139.61 | -103333.49 |
PERIMETER_MID_ZN_4 | 24-DEC-06:52 | 0.00 | 0.00 | 178534.28 | 0.00 | 0.00 | 0.00 | 579.99 | 626.56 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -37934.48 | 0.00 | -23223.52 | -123472.63 |
PERIMETER_TOP_ZN_3 | 19-MAR-06:11 | 0.00 | 0.00 | 16169.80 | 0.00 | 0.00 | 0.00 | 92.65 | 97.23 | 758.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4672.13 | 0.00 | -4891.80 | -7554.52 |
PERIMETER_TOP_ZN_2 | 19-MAR-06:11 | 0.00 | 0.00 | 18525.60 | 0.00 | 0.00 | 0.00 | 59.79 | 62.66 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2987.94 | 0.00 | -3324.09 | -12824.99 |
PERIMETER_TOP_ZN_1 | 19-MAR-06:11 | 0.00 | 0.00 | 21752.81 | 0.00 | 0.00 | 0.00 | 92.59 | 97.23 | 758.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4494.42 | 0.00 | -4946.85 | -13260.14 |
PERIMETER_TOP_ZN_4 | 19-MAR-06:11 | 0.00 | 0.00 | 21225.63 | 0.00 | 0.00 | 0.00 | 59.24 | 62.66 | 488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3173.46 | 0.00 | -3407.52 | -15255.53 |
DATACENTER_BOT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 01-JAN-08:05 | 0.00 | 0.00 | 4837.44 | 0.00 | 0.00 | 0.00 | 53.08 | 225.07 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -24601.64 |
DATACENTER_TOP_ZN_6 | 30-APR-23:05 | 0.00 | 0.00 | 725.43 | 0.00 | 0.00 | 0.00 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -2696.55 |
DATACENTER_BASEMENT_ZN_6 | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 26-DEC-06:02 | 15314.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -344.13 | -14970.54 |
MIDFLOOR_PLENUM | 01-JAN-13:53 | 96951.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -18899.92 | -78051.75 |
TOPFLOOR_PLENUM | 22-DEC-05:12 | 29608.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1800.50 | -27808.22 |
Total Facility | 06-FEB-06:01 | -272915.32 | 297045.09 | 1153044.38 | -297045.09 | 0.00 | 0.00 | 21298.33 | 29009.37 | 386654.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -181032.77 | 0.00 | -27794.39 | -1108263.69 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 12.5790 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.1755 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 119.4213 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 103.8515 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 12.3207 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 11.4601 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4261 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4261 | 0.1868 | 1.0000 | Not calculated | 1.2002 | 0.1868 | ||
AIRLOOP DATACENTER BASEMENT | 26.2762 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.2766 | 0.0129 | 1.0000 | Not calculated | 0.3384 | 0.0129 | ||
AIRLOOP DATACENTER BOT | 0.5956 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5956 | 0.0262 | 1.0000 | Not calculated | 0.0156 | 0.0262 | ||
AIRLOOP DATACENTER MID | 5.6975 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.6975 | 0.0274 | 1.0000 | Not calculated | 0.1563 | 0.0274 | ||
AIRLOOP DATACENTER TOP | 0.5815 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5815 | 0.0269 | 1.0000 | Not calculated | 0.0156 | 0.0269 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
VAV_BOT WITH REHEAT | 6.2895 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.1838 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_MID WITH REHEAT | 59.7106 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 31.0387 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
VAV_TOP WITH REHEAT | 6.1604 | 0.0000 | 0.0000 | 1.0000 | Calculated from schedules | 0.0000 | 3.2189 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
CAV_BAS | 6.4261 | 0.0000 | 149.6021 | 1.0000 | Calculated from schedules | 1.2002 | 6.4261 | 1.0000 | 1.0000 | Not calculated | 1.2002 | 0.1868 | ||
AIRLOOP DATACENTER BASEMENT | 26.2762 | 0.0000 | 42.1814 | 1.0000 | Calculated from schedules | 0.3384 | 26.2762 | 1.0000 | 1.0000 | Not calculated | 0.3384 | 0.0129 | ||
AIRLOOP DATACENTER BOT | 0.5956 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5956 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0262 | ||
AIRLOOP DATACENTER MID | 5.6975 | 0.0000 | 19.4861 | 1.0000 | Calculated from schedules | 0.1563 | 5.6975 | 1.0000 | 1.0000 | Not calculated | 0.1563 | 0.0274 | ||
AIRLOOP DATACENTER TOP | 0.5815 | 0.0000 | 1.9486 | 1.0000 | Calculated from schedules | 0.0156 | 0.5815 | 1.0000 | 1.0000 | Not calculated | 0.0156 | 0.0269 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
BASEMENT | CAV_BAS | 0.000000 | 149.6021 | 0.000432 | 2779.43 | 1.2002 | 1.0000 | 1.2002 | 1.000 | 1.2002 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_MID | VAV_MID WITH REHEAT | 0.000000 | 1343.5320 | 0.000432 | 24961.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | 0.000000 | 134.3532 | 0.000432 | 2496.12 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | 0.000000 | 168.6939 | 0.000432 | 3134.13 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | 0.000000 | 168.6975 | 0.000432 | 3134.20 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | 0.000000 | 108.7127 | 0.000432 | 2019.75 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | 0.000000 | 16.8694 | 0.000432 | 313.41 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | 0.000000 | 16.8698 | 0.000432 | 313.42 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | 0.000000 | 10.8713 | 0.000432 | 201.98 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | 0.000000 | 19.4861 | 0.000432 | 362.03 | 0.1563 | 1.0000 | 0.1563 | 1.000 | 0.1563 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | 0.000000 | 1.9486 | 0.000432 | 36.20 | 0.0156 | 1.0000 | 0.0156 | 1.000 | 0.0156 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.1814 | 0.000432 | 783.68 | 0.3384 | 1.0000 | 0.3384 | 1.000 | 0.3384 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
VAV_BOT WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
VAV_MID WITH REHEAT | 0.00 | 0.000432 | 35269.0328 | 0.0000 | 0.0000 | 0.0000 | |
VAV_TOP WITH REHEAT | 0.00 | 0.000432 | 3526.9033 | 0.0000 | 0.0000 | 0.0000 | |
CAV_BAS | 0.000000 | 149.60 | 0.000432 | 2779.4266 | 1.2002 | 1.2002 | 1.2002 |
AIRLOOP DATACENTER BASEMENT | 0.000000 | 42.18 | 0.000432 | 783.6794 | 0.3384 | 0.3384 | 0.3384 |
AIRLOOP DATACENTER BOT | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AIRLOOP DATACENTER MID | 0.000000 | 19.49 | 0.000432 | 362.0274 | 0.1563 | 0.1563 | 0.1563 |
AIRLOOP DATACENTER TOP | 0.000000 | 1.95 | 0.000432 | 36.2027 | 0.0156 | 0.0156 | 0.0156 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4261 | 6.4261 | 6.4261 | No | 1.2002 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.8697 | 6.8697 | 2.0128 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 64.5481 | 64.5481 | 19.6872 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 6.4022 | 6.4022 | 2.0231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.1187 | 1.1187 | 0.2528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.3384 | 1.3384 | 0.2677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.5306 | 1.5306 | 0.3061 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.7217 | 1.7217 | 0.3443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 10.4701 | 10.4701 | 2.4709 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.0461 | 14.0461 | 2.8092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 14.9120 | 14.9120 | 2.9824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 15.4451 | 15.4451 | 3.0890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.2079 | 1.2079 | 0.2537 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.4106 | 1.4106 | 0.2821 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6417 | 1.6417 | 0.3283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 1.6583 | 1.6583 | 0.3317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5956 | 0.5956 | 0.5956 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6975 | 5.6975 | 5.6975 | No | 0.1563 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5815 | 0.5815 | 0.5815 | No | 0.0156 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.2762 | 26.2762 | 26.2762 | No | 0.3384 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 12.5790 | 11.1755 | 12.5790 | 3.1838 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 119.4213 | 103.8515 | 119.4213 | 31.0387 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 12.3207 | 11.4601 | 12.3207 | 3.2189 | 0.0000 | 1.0000 |
CAV_BAS | 6.4261 | 6.4261 | 6.4261 | 6.4261 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.2762 | 26.2766 | 26.2762 | 26.2762 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5956 | 0.5956 | 0.5956 | 0.5956 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.6975 | 5.6975 | 5.6975 | 5.6975 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5815 | 0.5815 | 0.5815 | 0.5815 | 0.0156 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
BASEMENT | CAV_BAS | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 6.4261 | 6.4261 | 6.4261 | No | 1.2002 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_BOTTOM | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.4349 | 3.4349 | 2.0128 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_MID | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 32.2741 | 32.2741 | 19.6872 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
CORE_TOP | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 3.2011 | 3.2011 | 2.0231 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_3 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.5594 | 0.5594 | 0.2528 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_2 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6692 | 0.6692 | 0.2677 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_1 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7653 | 0.7653 | 0.3061 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_BOT_ZN_4 | VAV_BOT WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8608 | 0.8608 | 0.3443 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_3 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 5.2350 | 5.2350 | 2.4709 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_2 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.0230 | 7.0230 | 2.8092 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_1 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.4560 | 7.4560 | 2.9824 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_MID_ZN_4 | VAV_MID WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 7.7225 | 7.7225 | 3.0890 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_3 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.6039 | 0.6039 | 0.2537 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_2 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.7053 | 0.7053 | 0.2821 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_1 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8208 | 0.8208 | 0.3283 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
PERIMETER_TOP_ZN_4 | VAV_TOP WITH REHEAT | AIRTERMINAL:SINGLEDUCT:VAV:REHEAT | 0.8292 | 0.8292 | 0.3317 | No | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BOT_ZN_6 | AIRLOOP DATACENTER BOT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5956 | 0.5956 | 0.5956 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_MID_ZN_6 | AIRLOOP DATACENTER MID | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 5.6975 | 5.6975 | 5.6975 | No | 0.1563 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_TOP_ZN_6 | AIRLOOP DATACENTER TOP | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.5815 | 0.5815 | 0.5815 | No | 0.0156 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
DATACENTER_BASEMENT_ZN_6 | AIRLOOP DATACENTER BASEMENT | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 26.2762 | 26.2762 | 26.2762 | No | 0.3384 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
VAV_BOT WITH REHEAT | 6.2895 | 3.1838 | 3.1838 | 3.1838 | 0.0000 | 1.0000 |
VAV_MID WITH REHEAT | 59.7106 | 31.0387 | 31.0387 | 31.0387 | 0.0000 | 1.0000 |
VAV_TOP WITH REHEAT | 6.1604 | 3.2189 | 3.2189 | 3.2189 | 0.0000 | 1.0000 |
CAV_BAS | 6.4261 | 6.4261 | 6.4261 | 6.4261 | 1.2002 | 1.0000 |
AIRLOOP DATACENTER BASEMENT | 26.2762 | 26.2762 | 26.2762 | 26.2762 | 0.3384 | 1.0000 |
AIRLOOP DATACENTER BOT | 0.5956 | 0.5956 | 0.5956 | 0.5956 | 0.0156 | 1.0000 |
AIRLOOP DATACENTER MID | 5.6975 | 5.6975 | 5.6975 | 5.6975 | 0.1563 | 1.0000 |
AIRLOOP DATACENTER TOP | 0.5815 | 0.5815 | 0.5815 | 0.5815 | 0.0156 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
Total gross floor area [m2] | 46320.38 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
BASEMENT | 2779.43 | 2779.43 | 0.00 | 113.98 |
CORE_BOTTOM | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_MID | 2496.12 | 2496.12 | 0.00 | 113.98 |
CORE_TOP | 2496.12 | 2496.12 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_BOT_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_MID_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_MID_ZN_2 | 201.98 | 201.98 | 0.00 | 96.54 |
PERIMETER_MID_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_MID_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_3 | 313.41 | 313.41 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_2 | 201.98 | 201.98 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_1 | 313.42 | 313.42 | 0.00 | 113.98 |
PERIMETER_TOP_ZN_4 | 201.98 | 201.98 | 0.00 | 113.98 |
DATACENTER_BOT_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_MID_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_TOP_ZN_6 | 36.20 | 36.20 | 0.00 | 113.98 |
DATACENTER_BASEMENT_ZN_6 | 783.68 | 783.68 | 0.00 | 113.98 |
GROUNDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 3563.11 | 3563.11 | 0.00 | 0.00 |
Totals | 46320.38 | 46320.38 | 0.00 |
Data | |
Number of hours heating loads not met | 84.50 |
Number of hours cooling loads not met | 1575.17 |
Number of hours not met | 1628.83 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler | 0.00 | 0.00 | 1885.80 | 1461485.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 3675.74 | 432978.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 2743.87 | 261074.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 448.76 | 37611.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 5871.99 | 320838.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- DataCenterPlugLoads | 9341.42 | 473165.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Transformer | 59.77 | 3726.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLift | 1848.78 | 113101.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- ElevatorLightsFan | 5.83 | 376.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 2810.89 | 293477.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- General | 497.77 | 64100.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- General | 941.82 | 80361.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- General | 1283.48 | 82269.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- WaterUse | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 0.00 | 0.00 | 736.85 | 83550.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 15213.41 | 29530.12 |
Natural Gas | 0.00 | 2622.65 |
Additional | 0.00 | 0.00 |
Total | 15213.41 | 32152.78 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 59.24 |
Space Heating | 0.00 |
Space Cooling | 79.35 |
Fans (All) | 60.68 |
Service Water Heating | 0.00 |
Receptacle Equipment | 328.44 |
Miscellaneous (All) | 637.52 |
Subtotal | 637.52 |
Natural Gas [MJ/m2] | |
Space Heating | 40.71 |
Service Water Heating | 15.91 |
Miscellaneous (All) | 56.62 |
Subtotal | 56.62 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 8.53 |
Space Heating | 5.87 |
Space Cooling | 11.43 |
Fans (All) | 8.74 |
Service Water Heating | 2.29 |
Receptacle Equipment | 47.32 |
Miscellaneous | 15.82 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 4472. | 4472. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 6752. | 8760. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 6828. | 8760. |
ALWAYS_OFF | 0. | 0. |
LTG_SCH_OFFICE | 2393. | 8760. |
LTG_SCH_DATACENTER | 2921. | 8760. |
EXTERIOR_LIGHT_SCH | 4380. | 4380. |
BLDG_EQUIP_SCH | 4487. | 8760. |
DATACENTER_EQUIP_SCH | 5478. | 8760. |
BLDG_OCC_SCH | 2528. | 5992. |
BLDG_OCC_SCH_W_SB | 1878. | 5056. |
BLDG_OCC_SCH_WO_SB | 2557. | 5992. |
BLDG_ELEVATORS | 2270. | 8760. |
ELEV_LIGHT_FAN_SCH_24_7 | 8760. | 8760. |
ELEV_LIGHT_FAN_SCH_ADD_DF | 2154. | 8760. |
BLDG_SWH_SCH | 1474. | 6570. |
WORK_EFF_SCH | 0. | 0. |
INFIL_SCH | 3976. | 3976. |
INFIL_SCH_PNNL | 5172. | 8760. |
INFIL_HALF_ON_SCH | 6368. | 8760. |
FAN_SCH | 8760. | 8760. |
REHEATCOILAVAILSCHED | 8760. | 8760. |
COOLINGCOILAVAILSCHED | 8760. | 8760. |
MINOA_MOTORIZEDDAMPER_SCHED | 4472. | 4472. |
MINOA_SCHED | 8760. | 8760. |
CORE_BOTTOM SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_BOTTOM SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_MID SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_MID SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
CORE_TOP SUB CAT LATENT FRACT SCHED | 438. | 8760. |
CORE_TOP SUB CAT SENSIBLE FRACT SCHED | 1752. | 8760. |
SUPPLYFANSCH | 8760. | 8760. |
PERIMETER_MID_ZN_2_MDP_SCH | 1565. | 7824. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
HTGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | January | 18.00 | 365 | 18.00 | 365 |
CLGSETP_DC_SCH | DATACENTER COOLING SETPOINTS DUAL SP CONTROL | July | 27.00 | 365 | 27.00 | 365 |
HTGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | January | 21.00 | 365 | 15.60 | 365 |
CLGSETP_SCH_YES_OPTIMUM | CORE_BOTTOM DUAL SP CONTROL | July | 24.00 | 365 | 26.70 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 8678.67 | 81.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8755.83 | 4.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8737.83 | 22.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8735.67 | 24.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8604.00 | 156.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8727.00 | 33.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8732.50 | 27.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8726.83 | 33.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8726.33 | 33.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8734.67 | 25.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8726.33 | 33.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8703.17 | 56.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8724.17 | 35.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8729.67 | 30.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 6642.67 | 2032.00 | 85.33 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8714.67 | 45.33 | 0.00 | 0.00 | 0.00 |
Min | 6642.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 2032.00 | 85.33 | 0.00 | 0.00 |
Average | 8639.80 | 116.49 | 3.71 | 0.00 | 0.00 |
Sum | 198715.50 | 2679.17 | 85.33 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
BASEMENT | 368375.67 | 240.33 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330813.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2242.17 | 25.83 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2249.50 | 18.50 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2252.67 | 15.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 78999.50 | 22830.50 | 1565.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368375.67 | 22830.50 | 1565.00 | 0.00 | 0.00 |
Average | 79261.20 | 1005.67 | 68.04 | 0.00 | 0.00 |
Sum | 1823007.50 | 23130.50 | 1565.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 8560.00 | 200.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 8673.00 | 87.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 8675.00 | 85.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 8685.67 | 74.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 8705.33 | 54.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 8718.17 | 41.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 8704.00 | 56.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 8569.83 | 190.17 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 8733.00 | 27.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 8710.50 | 49.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 8719.17 | 40.83 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 8693.33 | 66.67 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 8729.00 | 31.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 8709.50 | 50.50 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 8721.67 | 38.33 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 8700.00 | 60.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 8757.67 | 2.33 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 7088.17 | 1671.83 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 8681.00 | 79.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 8710.83 | 49.17 | 0.00 | 0.00 | 0.00 |
Min | 7088.17 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1671.83 | 0.00 | 0.00 | 0.00 |
Average | 8630.21 | 129.79 | 0.00 | 0.00 | 0.00 |
Sum | 198494.83 | 2985.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
BASEMENT | 368072.50 | 543.50 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 330687.00 | 126.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 330720.00 | 93.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 330734.00 | 79.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_2 | 18354.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_MID_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 38925.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 24909.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 2267.33 | 0.67 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 2268.00 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 85260.67 | 18134.33 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 368072.50 | 18134.33 | 0.00 | 0.00 | 0.00 |
Average | 79509.85 | 825.07 | 0.00 | 0.00 | 0.00 |
Sum | 1828726.50 | 18976.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 09:04:14
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 8760.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 8760.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 8760.00 | 0.00 |
Average | 0.00 | 0.00 | 4570.43 | 0.00 |
Sum | 0.00 | 0.00 | 105120.00 | 0.00 |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
BASEMENT | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_BOTTOM | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_MID | 0.00 | 0.00 | 0.00 | 0.00 |
CORE_TOP | 0.00 | 0.00 | 0.00 | 0.00 |
PERIMETER_BOT_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_BOT_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_BOT_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_MID_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_2 | 0.00 | 0.00 | 18354.00 | 0.00 |
PERIMETER_MID_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_MID_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_3 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_2 | 0.00 | 0.00 | 24909.00 | 0.00 |
PERIMETER_TOP_ZN_1 | 0.00 | 0.00 | 38925.00 | 0.00 |
PERIMETER_TOP_ZN_4 | 0.00 | 0.00 | 24909.00 | 0.00 |
DATACENTER_BOT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_MID_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_TOP_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
DATACENTER_BASEMENT_ZN_6 | 0.00 | 0.00 | 0.00 | 0.00 |
GROUNDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
MIDFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
TOPFLOOR_PLENUM | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 0.00 | 0.00 | 38925.00 | 0.00 |
Average | 0.00 | 0.00 | 16367.35 | 0.00 |
Sum | 0.00 | 0.00 | 376449.00 | 0.00 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2018
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME OFFICELARGE
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5B
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CO_DENVER
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 0.846 |
February | -0.25 |
March | 4.824 |
April | 6.083 |
May | 13.735 |
June | 22.164 |
July | 22.707 |
August | 21.737 |
September | 18.538 |
October | 7.117 |
November | 3.031 |
December | -1.01 |
Annual Sum or Average | 10.017 |
Minimum of Months | -1.01 |
Maximum of Months | 22.707 |
Report: ZoneCoolingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.468372E+11 | 102044.53 | 02-JAN-04:01 | -2.8 | -3.4 | 0.564765E+10 | 7499.22 | 06-JAN-10:50 | 0.67 | -0.8 |
February | 0.410633E+11 | 100660.24 | 21-FEB-04:03 | -1.0 | -1.0 | 0.513213E+10 | 7499.14 | 08-FEB-14:20 | -1.0 | -1.0 |
March | 0.509682E+11 | 101159.93 | 13-MAR-03:02 | 7.83 | 1.71 | 0.612724E+10 | 7499.14 | 14-MAR-13:20 | 23.67 | 7.80 |
April | 0.496546E+11 | 101840.39 | 24-APR-03:01 | -2.0 | -2.5 | 0.544576E+10 | 7499.27 | 13-APR-13:00 | -2.0 | -2.5 |
May | 0.525379E+11 | 103800.28 | 01-MAY-03:01 | 5.92 | 2.18 | 0.589970E+10 | 7499.22 | 26-MAY-13:20 | 12.67 | 7.73 |
June | 0.567543E+11 | 96534.67 | 09-JUN-04:03 | 6.60 | 3.48 | 0.588205E+10 | 7499.15 | 22-JUN-13:20 | 19.60 | 16.32 |
July | 0.568116E+11 | 100435.07 | 03-JUL-03:02 | 11.00 | 7.63 | 0.547296E+10 | 7499.04 | 21-JUL-09:20 | 25.00 | 15.23 |
August | 0.666965E+11 | 95101.05 | 17-AUG-03:02 | 13.00 | 5.30 | 0.613940E+10 | 7551.95 | 21-AUG-09:09 | 25.33 | 14.07 |
September | 0.581655E+11 | 100359.85 | 25-SEP-03:02 | 7.70 | 3.87 | 0.545313E+10 | 7545.65 | 05-SEP-13:00 | 7.70 | 3.87 |
October | 0.568154E+11 | 105755.18 | 23-OCT-03:01 | -2.2 | -2.2 | 0.567003E+10 | 7499.36 | 03-OCT-13:20 | -2.2 | -2.2 |
November | 0.539494E+11 | 104613.50 | 27-NOV-04:01 | -7.0 | -7.0 | 0.561272E+10 | 7499.12 | 29-NOV-10:20 | -9.0 | -9.0 |
December | 0.523337E+11 | 103151.40 | 11-DEC-04:01 | -6.8 | -8.8 | 0.542786E+10 | 7499.03 | 12-DEC-14:09 | 8.00 | 2.07 |
Annual Sum or Average | 0.642588E+12 | 0.679106E+11 | ||||||||
Minimum of Months | 0.410633E+11 | 95101.05 | -7.0 | -8.8 | 0.513213E+10 | 7499.03 | -9.0 | -9.0 | ||
Maximum of Months | 0.666965E+11 | 105755.18 | 13.00 | 7.63 | 0.613940E+10 | 7551.95 | 25.33 | 16.32 |
Report: ZoneCoolingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.372211E+11 | 82428.66 | 02-JAN-05:01 | -2.2 | -3.4 | 0.506124E+10 | 6734.77 | 06-JAN-10:50 | 0.67 | -0.8 |
February | 0.345755E+11 | 82328.27 | 27-FEB-05:01 | 4.83 | 0.05 | 0.459178E+10 | 6734.71 | 14-FEB-14:00 | 4.83 | 0.05 |
March | 0.477705E+11 | 84098.77 | 13-MAR-03:02 | 7.83 | 1.71 | 0.549385E+10 | 6734.76 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.481288E+11 | 85384.04 | 10-APR-03:02 | 3.00 | -3.0 | 0.488584E+10 | 6735.07 | 13-APR-13:00 | 15.00 | 9.82 |
May | 0.491036E+11 | 86237.31 | 01-MAY-03:01 | 5.92 | 2.18 | 0.528867E+10 | 6734.87 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.602997E+11 | 84979.62 | 20-JUN-03:02 | 15.00 | 11.91 | 0.526989E+10 | 6734.94 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.636234E+11 | 86500.73 | 31-JUL-03:02 | 15.83 | 14.41 | 0.489687E+10 | 6734.77 | 26-JUL-09:09 | 15.83 | 14.41 |
August | 0.768395E+11 | 85243.40 | 11-AUG-05:03 | 16.17 | 11.25 | 0.549648E+10 | 6783.04 | 21-AUG-09:00 | 27.00 | 14.16 |
September | 0.522886E+11 | 85186.60 | 05-SEP-03:02 | 13.90 | 9.20 | 0.488290E+10 | 6735.41 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.472981E+11 | 85333.89 | 02-OCT-03:02 | 4.00 | 4.00 | 0.507753E+10 | 6735.00 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.450102E+11 | 86829.00 | 13-NOV-04:01 | 1.00 | 0.92 | 0.502589E+10 | 6734.76 | 29-NOV-10:20 | -9.0 | -9.0 |
December | 0.433580E+11 | 86738.71 | 04-DEC-04:02 | 1.83 | -0.9 | 0.489198E+10 | 6734.75 | 21-DEC-10:39 | -18.7 | -19.0 |
Annual Sum or Average | 0.605517E+12 | 0.608629E+11 | ||||||||
Minimum of Months | 0.345755E+11 | 82328.27 | -2.2 | -3.4 | 0.459178E+10 | 6734.71 | -18.7 | -19.0 | ||
Maximum of Months | 0.768395E+11 | 86829.00 | 16.17 | 14.41 | 0.549648E+10 | 6783.04 | 27.00 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259951E+11 | 69814.35 | 27-JAN-06:02 | -1.2 | -1.2 | 0.490516E+10 | 6734.69 | 31-JAN-10:20 | -0.3 | -0.6 |
February | 0.232677E+11 | 64037.97 | 28-FEB-06:03 | -3.0 | -3.4 | 0.436303E+10 | 6734.70 | 28-FEB-10:00 | 4.00 | 2.09 |
March | 0.314039E+11 | 72349.10 | 14-MAR-05:03 | 8.67 | 1.59 | 0.535065E+10 | 6734.70 | 02-MAR-10:20 | 8.67 | 1.59 |
April | 0.276792E+11 | 72945.96 | 14-APR-05:03 | 4.67 | 4.13 | 0.478409E+10 | 6734.99 | 13-APR-13:00 | 4.67 | 4.13 |
May | 0.385855E+11 | 75133.71 | 18-MAY-04:03 | 11.83 | 7.63 | 0.527511E+10 | 6734.83 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.481276E+11 | 76841.69 | 22-JUN-04:03 | 17.02 | 13.59 | 0.526541E+10 | 6734.93 | 20-JUN-13:00 | 17.02 | 13.59 |
July | 0.473553E+11 | 78988.73 | 10-JUL-03:02 | 17.83 | 9.72 | 0.489187E+10 | 6734.76 | 14-JUL-09:30 | 25.00 | 12.08 |
August | 0.495430E+11 | 79373.68 | 28-AUG-03:02 | 15.67 | 14.58 | 0.549598E+10 | 6734.75 | 10-AUG-09:39 | 15.67 | 14.58 |
September | 0.424601E+11 | 78697.99 | 05-SEP-03:02 | 13.90 | 9.20 | 0.487421E+10 | 6735.34 | 05-SEP-09:09 | 16.47 | 11.53 |
October | 0.329153E+11 | 74861.28 | 06-OCT-05:02 | 6.00 | 3.09 | 0.501391E+10 | 6734.91 | 03-OCT-13:09 | 6.00 | 3.09 |
November | 0.274873E+11 | 74205.54 | 09-NOV-06:02 | 9.17 | 4.69 | 0.492002E+10 | 6734.70 | 21-NOV-10:09 | 0.50 | -0.7 |
December | 0.244291E+11 | 28372.73 | 15-DEC-16:20 | 4.67 | 1.42 | 0.459792E+10 | 6734.69 | 08-DEC-10:09 | 4.67 | 1.42 |
Annual Sum or Average | 0.419249E+12 | 0.597374E+11 | ||||||||
Minimum of Months | 0.232677E+11 | 28372.73 | -3.0 | -3.4 | 0.436303E+10 | 6734.69 | -0.3 | -0.7 | ||
Maximum of Months | 0.495430E+11 | 79373.68 | 17.83 | 14.58 | 0.549598E+10 | 6735.34 | 25.00 | 14.58 |
Report: ZoneCoolingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.184108E+11 | 28584.63 | 20-JAN-16:30 | 15.00 | 6.47 | 0.433176E+10 | 6734.36 | 26-JAN-14:00 | 9.00 | 2.97 |
February | 0.164201E+11 | 23494.44 | 23-FEB-17:00 | 5.00 | 2.11 | 0.394843E+10 | 6734.56 | 24-FEB-14:50 | 8.17 | 2.53 |
March | 0.252533E+11 | 68153.35 | 15-MAR-05:03 | 10.83 | 3.07 | 0.500213E+10 | 6734.67 | 17-MAR-09:09 | 6.83 | 6.35 |
April | 0.241890E+11 | 69632.10 | 21-APR-05:02 | 5.83 | 3.87 | 0.448537E+10 | 6734.98 | 13-APR-13:00 | 5.83 | 3.87 |
May | 0.349502E+11 | 72713.38 | 18-MAY-05:03 | 11.67 | 7.89 | 0.517625E+10 | 6734.79 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.510884E+11 | 77981.46 | 26-JUN-03:02 | 16.05 | 10.54 | 0.526449E+10 | 6771.23 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.498763E+11 | 80838.13 | 24-JUL-03:02 | 18.83 | 14.98 | 0.489258E+10 | 6734.75 | 14-JUL-09:39 | 18.83 | 14.98 |
August | 0.512127E+11 | 79352.22 | 21-AUG-03:02 | 18.17 | 11.57 | 0.549350E+10 | 6734.77 | 10-AUG-09:50 | 18.17 | 11.57 |
September | 0.401387E+11 | 77954.98 | 11-SEP-03:02 | 17.10 | 8.74 | 0.484083E+10 | 6735.32 | 05-SEP-09:09 | 17.10 | 8.74 |
October | 0.250233E+11 | 57900.55 | 11-OCT-05:03 | 10.17 | 3.29 | 0.467145E+10 | 6734.70 | 03-OCT-13:30 | 10.17 | 3.29 |
November | 0.195461E+11 | 32315.07 | 08-NOV-16:20 | 16.33 | 7.18 | 0.440959E+10 | 6734.51 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.162677E+11 | 20074.69 | 15-DEC-16:20 | 4.67 | 1.42 | 0.407211E+10 | 6731.39 | 15-DEC-14:00 | 4.67 | 1.42 |
Annual Sum or Average | 0.372376E+12 | 0.565885E+11 | ||||||||
Minimum of Months | 0.162677E+11 | 20074.69 | 4.67 | 1.42 | 0.394843E+10 | 6731.39 | 4.67 | 1.42 | ||
Maximum of Months | 0.512127E+11 | 80838.13 | 18.83 | 14.98 | 0.549350E+10 | 6771.23 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.234942E+10 | 3214.06 | 20-JAN-15:00 | 20.00 | 6.78 | 0.559991E+09 | 845.59 | 23-JAN-14:00 | 19.00 | 5.82 |
February | 0.213732E+10 | 3847.37 | 27-FEB-15:30 | 13.50 | 4.54 | 0.502632E+09 | 845.61 | 28-FEB-14:39 | 4.33 | 2.90 |
March | 0.370358E+10 | 6158.97 | 14-MAR-14:30 | 23.00 | 7.59 | 0.651287E+09 | 845.62 | 17-MAR-09:09 | 6.83 | 6.35 |
April | 0.420896E+10 | 7056.76 | 20-APR-13:30 | 21.50 | 8.83 | 0.593915E+09 | 845.66 | 13-APR-13:50 | 21.50 | 8.83 |
May | 0.594281E+10 | 8185.75 | 17-MAY-13:30 | 29.00 | 11.78 | 0.659835E+09 | 845.64 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.102070E+11 | 14612.55 | 25-JUN-17:51 | 31.60 | 13.99 | 0.662274E+09 | 846.85 | 26-JUN-13:20 | 36.97 | 15.36 |
July | 0.105624E+11 | 15734.57 | 16-JUL-14:12 | 35.33 | 14.43 | 0.615807E+09 | 846.49 | 25-JUL-13:39 | 27.33 | 16.10 |
August | 0.113684E+11 | 12930.67 | 21-AUG-05:03 | 19.92 | 12.21 | 0.690354E+09 | 852.56 | 21-AUG-09:00 | 27.00 | 14.16 |
September | 0.669923E+10 | 12221.31 | 11-SEP-05:03 | 17.88 | 8.62 | 0.609939E+09 | 845.70 | 05-SEP-09:09 | 17.88 | 8.62 |
October | 0.374659E+10 | 6609.21 | 10-OCT-14:40 | 25.00 | 8.55 | 0.602988E+09 | 845.65 | 03-OCT-13:09 | 25.00 | 8.55 |
November | 0.300796E+10 | 5169.11 | 09-NOV-13:30 | 20.00 | 8.78 | 0.578286E+09 | 845.61 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.237159E+10 | 4621.72 | 04-DEC-14:10 | 19.83 | 6.62 | 0.543970E+09 | 845.61 | 04-DEC-10:00 | 19.83 | 6.62 |
Annual Sum or Average | 0.663053E+11 | 0.727128E+10 | ||||||||
Minimum of Months | 0.213732E+10 | 3214.06 | 13.50 | 4.54 | 0.502632E+09 | 845.59 | 4.33 | 2.90 | ||
Maximum of Months | 0.113684E+11 | 15734.57 | 35.33 | 14.43 | 0.690354E+09 | 852.56 | 36.97 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272121E+10 | 6564.37 | 20-JAN-09:30 | 12.00 | 3.86 | 0.368808E+09 | 544.96 | 10-JAN-10:09 | 12.00 | 3.86 |
February | 0.269306E+10 | 8689.32 | 27-FEB-09:10 | 9.17 | 2.67 | 0.335292E+09 | 544.95 | 23-FEB-10:09 | 9.17 | 2.67 |
March | 0.448443E+10 | 11484.95 | 12-MAR-08:43 | 13.50 | 4.88 | 0.418567E+09 | 544.97 | 27-MAR-09:20 | 1.33 | -0.7 |
April | 0.455852E+10 | 11088.98 | 21-APR-08:70 | 11.17 | 5.89 | 0.378112E+09 | 544.98 | 13-APR-13:50 | 11.17 | 5.89 |
May | 0.616967E+10 | 11234.22 | 16-MAY-08:70 | 20.50 | 11.07 | 0.425306E+09 | 545.00 | 31-MAY-09:00 | 25.00 | 13.24 |
June | 0.982651E+10 | 19749.63 | 11-JUN-08:62 | 17.67 | 10.77 | 0.426776E+09 | 546.17 | 26-JUN-09:39 | 29.40 | 15.89 |
July | 0.954533E+10 | 19249.68 | 16-JUL-08:51 | 33.00 | 14.82 | 0.396885E+09 | 546.62 | 18-JUL-09:50 | 30.50 | 14.42 |
August | 0.103220E+11 | 18929.52 | 20-AUG-09:02 | 26.33 | 13.95 | 0.444274E+09 | 551.88 | 21-AUG-09:00 | 27.00 | 14.16 |
September | 0.710271E+10 | 16511.82 | 04-SEP-09:02 | 24.68 | 13.41 | 0.393266E+09 | 546.22 | 18-SEP-09:20 | 23.47 | 10.85 |
October | 0.417499E+10 | 15185.35 | 01-OCT-09:13 | 13.33 | 7.78 | 0.383340E+09 | 544.98 | 03-OCT-13:09 | 12.17 | 8.60 |
November | 0.314968E+10 | 8463.98 | 06-NOV-08:50 | 12.50 | 3.54 | 0.370256E+09 | 544.95 | 27-NOV-10:39 | -0.3 | -1.4 |
December | 0.234815E+10 | 5451.20 | 18-DEC-09:15 | 1.00 | -1.7 | 0.345665E+09 | 544.95 | 27-DEC-10:20 | 3.00 | -2.0 |
Annual Sum or Average | 0.670963E+11 | 0.468655E+10 | ||||||||
Minimum of Months | 0.234815E+10 | 5451.20 | 1.00 | -1.7 | 0.335292E+09 | 544.95 | -0.3 | -2.0 | ||
Maximum of Months | 0.103220E+11 | 19749.63 | 33.00 | 14.82 | 0.444274E+09 | 551.88 | 30.50 | 15.89 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.805077E+10 | 21369.53 | 22-JAN-12:22 | 6.50 | 3.36 | 0.605902E+09 | 890.00 | 20-JAN-14:09 | 6.50 | 3.36 |
February | 0.735650E+10 | 21861.37 | 26-FEB-12:42 | 17.83 | 4.77 | 0.545014E+09 | 846.41 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.850131E+10 | 21704.05 | 12-MAR-12:02 | 18.17 | 6.11 | 0.655197E+09 | 875.34 | 13-MAR-13:30 | 22.50 | 6.94 |
April | 0.649952E+10 | 13832.65 | 19-APR-13:20 | 22.00 | 8.59 | 0.585460E+09 | 848.25 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.732726E+10 | 12326.97 | 07-MAY-13:32 | 21.00 | 9.43 | 0.655184E+09 | 845.68 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.113376E+11 | 15667.18 | 25-JUN-14:32 | 33.43 | 13.43 | 0.661974E+09 | 846.33 | 30-JUN-13:20 | 34.97 | 13.87 |
July | 0.120700E+11 | 21422.65 | 16-JUL-14:12 | 35.33 | 14.43 | 0.615812E+09 | 845.66 | 19-JUL-09:00 | 25.00 | 15.80 |
August | 0.154037E+11 | 21650.68 | 20-AUG-14:21 | 28.00 | 14.24 | 0.691124E+09 | 875.08 | 31-AUG-13:09 | 30.00 | 11.91 |
September | 0.120087E+11 | 22358.44 | 10-SEP-12:42 | 32.25 | 13.24 | 0.612227E+09 | 918.19 | 28-SEP-13:20 | 30.50 | 11.31 |
October | 0.971707E+10 | 24512.40 | 08-OCT-12:41 | 21.00 | 8.59 | 0.604133E+09 | 916.53 | 10-OCT-13:09 | 24.17 | 8.07 |
November | 0.899344E+10 | 22627.16 | 05-NOV-13:32 | 21.00 | 6.43 | 0.606783E+09 | 905.87 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.737068E+10 | 22039.42 | 03-DEC-13:22 | 17.60 | 6.45 | 0.577272E+09 | 865.15 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.114637E+12 | 0.741608E+10 | ||||||||
Minimum of Months | 0.649952E+10 | 12326.97 | 6.50 | 3.36 | 0.545014E+09 | 845.66 | 6.50 | 3.36 | ||
Maximum of Months | 0.154037E+11 | 24512.40 | 35.33 | 14.43 | 0.691124E+09 | 918.19 | 34.97 | 15.80 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415799E+10 | 9078.60 | 23-JAN-16:00 | 19.00 | 6.19 | 0.372263E+09 | 544.95 | 17-JAN-14:00 | 19.00 | 6.19 |
February | 0.442688E+10 | 14759.94 | 26-FEB-16:42 | 16.33 | 4.63 | 0.343893E+09 | 544.95 | 17-FEB-14:00 | 16.33 | 4.63 |
March | 0.722590E+10 | 24052.01 | 12-MAR-16:02 | 18.00 | 5.74 | 0.434617E+09 | 544.96 | 27-MAR-09:00 | 0.00 | -0.5 |
April | 0.820647E+10 | 22302.28 | 08-APR-17:42 | 14.33 | 4.60 | 0.392955E+09 | 545.00 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.754696E+10 | 15010.69 | 07-MAY-15:32 | 22.33 | 8.84 | 0.425773E+09 | 544.97 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.126340E+11 | 27899.12 | 11-JUN-17:21 | 27.50 | 12.48 | 0.427648E+09 | 544.99 | 20-JUN-13:00 | 23.30 | 16.53 |
July | 0.131029E+11 | 25881.19 | 02-JUL-16:41 | 28.00 | 12.40 | 0.397886E+09 | 544.98 | 26-JUL-09:09 | 25.17 | 15.80 |
August | 0.176974E+11 | 26278.52 | 20-AUG-15:41 | 28.00 | 14.08 | 0.446460E+09 | 551.71 | 21-AUG-09:00 | 27.00 | 14.16 |
September | 0.857956E+10 | 24908.59 | 10-SEP-16:41 | 30.78 | 12.29 | 0.393996E+09 | 545.01 | 05-SEP-09:09 | 30.78 | 12.29 |
October | 0.662248E+10 | 25524.86 | 08-OCT-14:41 | 20.00 | 8.96 | 0.395510E+09 | 544.98 | 03-OCT-13:09 | 20.00 | 8.96 |
November | 0.574038E+10 | 17153.59 | 05-NOV-15:32 | 19.67 | 6.02 | 0.392993E+09 | 544.95 | 16-NOV-14:09 | 16.00 | 6.65 |
December | 0.546593E+10 | 16535.83 | 03-DEC-15:22 | 17.00 | 6.47 | 0.380116E+09 | 544.96 | 15-DEC-14:39 | 10.00 | 3.25 |
Annual Sum or Average | 0.101407E+12 | 0.480411E+10 | ||||||||
Minimum of Months | 0.415799E+10 | 9078.60 | 14.33 | 4.60 | 0.343893E+09 | 544.95 | 0.00 | -0.5 | ||
Maximum of Months | 0.176974E+11 | 27899.12 | 30.78 | 14.08 | 0.446460E+09 | 551.71 | 30.78 | 16.53 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114664E+10 | 2508.45 | 20-JAN-15:50 | 18.33 | 7.40 | 0.489793E+09 | 769.18 | 20-JAN-14:00 | 18.33 | 7.40 |
February | 0.880424E+09 | 2436.11 | 27-FEB-14:50 | 14.00 | 4.75 | 0.437764E+09 | 752.01 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.190408E+10 | 4409.63 | 14-MAR-15:00 | 23.00 | 7.59 | 0.572720E+09 | 845.60 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.205152E+10 | 4691.14 | 20-APR-13:30 | 21.50 | 8.83 | 0.529277E+09 | 845.65 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.441150E+10 | 7621.00 | 17-MAY-13:30 | 29.00 | 11.78 | 0.642474E+09 | 845.63 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.852151E+10 | 14580.04 | 25-JUN-17:41 | 31.78 | 13.99 | 0.661453E+09 | 846.30 | 12-JUN-13:39 | 31.78 | 13.99 |
July | 0.832190E+10 | 14288.26 | 16-JUL-14:22 | 35.50 | 14.51 | 0.614883E+09 | 846.10 | 25-JUL-13:39 | 27.33 | 16.10 |
August | 0.750537E+10 | 10292.41 | 03-AUG-05:03 | 17.33 | 13.86 | 0.688842E+09 | 845.64 | 15-AUG-13:30 | 25.00 | 13.53 |
September | 0.529368E+10 | 8464.73 | 11-SEP-14:30 | 28.85 | 13.58 | 0.601850E+09 | 845.69 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.229640E+10 | 5008.50 | 11-OCT-14:00 | 27.00 | 9.73 | 0.548454E+09 | 845.61 | 10-OCT-13:50 | 27.00 | 9.73 |
November | 0.137540E+10 | 3007.04 | 09-NOV-13:50 | 20.00 | 8.66 | 0.500283E+09 | 845.60 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.750913E+09 | 2293.43 | 01-DEC-14:40 | 21.33 | 7.55 | 0.459234E+09 | 766.27 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.444593E+11 | 0.674703E+10 | ||||||||
Minimum of Months | 0.750913E+09 | 2293.43 | 14.00 | 4.75 | 0.437764E+09 | 752.01 | 12.83 | 4.75 | ||
Maximum of Months | 0.852151E+10 | 14580.04 | 35.50 | 14.51 | 0.688842E+09 | 846.30 | 31.78 | 16.10 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173485E+10 | 4714.43 | 20-JAN-09:40 | 12.67 | 4.18 | 0.244107E+09 | 521.20 | 20-JAN-11:20 | 18.67 | 6.97 |
February | 0.173297E+10 | 6261.67 | 27-FEB-09:20 | 9.33 | 2.70 | 0.226026E+09 | 521.20 | 17-FEB-11:09 | 9.33 | 2.70 |
March | 0.323868E+10 | 9985.53 | 15-MAR-09:00 | 14.00 | 4.18 | 0.290103E+09 | 521.22 | 27-MAR-10:09 | 0.33 | -0.4 |
April | 0.326330E+10 | 10771.89 | 21-APR-08:50 | 11.83 | 5.97 | 0.263350E+09 | 521.23 | 13-APR-14:09 | 11.83 | 5.97 |
May | 0.547841E+10 | 14207.12 | 28-MAY-09:23 | 13.00 | 8.85 | 0.307450E+09 | 521.24 | 31-MAY-10:09 | 25.17 | 13.22 |
June | 0.951837E+10 | 20289.18 | 25-JUN-10:22 | 30.50 | 12.35 | 0.313471E+09 | 527.58 | 29-JUN-07:19 | 24.03 | 12.62 |
July | 0.890930E+10 | 21582.66 | 09-JUL-09:21 | 26.00 | 13.06 | 0.292512E+09 | 531.07 | 17-JUL-07:19 | 26.00 | 12.45 |
August | 0.919081E+10 | 22289.43 | 20-AUG-08:51 | 26.00 | 13.90 | 0.326466E+09 | 522.04 | 07-AUG-07:30 | 26.00 | 13.90 |
September | 0.662743E+10 | 20779.21 | 04-SEP-09:22 | 25.25 | 13.40 | 0.286722E+09 | 521.26 | 05-SEP-08:00 | 16.10 | 11.43 |
October | 0.319217E+10 | 13314.56 | 01-OCT-09:02 | 13.17 | 7.72 | 0.267308E+09 | 521.21 | 03-OCT-12:50 | 12.83 | 8.70 |
November | 0.199064E+10 | 6098.58 | 07-NOV-09:10 | 14.00 | 4.09 | 0.248351E+09 | 521.21 | 07-NOV-11:20 | 17.33 | 6.25 |
December | 0.117150E+10 | 2678.05 | 14-DEC-11:50 | 15.50 | 4.37 | 0.224701E+09 | 513.68 | 15-DEC-09:00 | 5.00 | -0.3 |
Annual Sum or Average | 0.560484E+11 | 0.329057E+10 | ||||||||
Minimum of Months | 0.117150E+10 | 2678.05 | 9.33 | 2.70 | 0.224701E+09 | 513.68 | 0.33 | -0.4 | ||
Maximum of Months | 0.951837E+10 | 22289.43 | 30.50 | 13.90 | 0.326466E+09 | 531.07 | 26.00 | 13.90 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.780213E+10 | 21153.47 | 22-JAN-13:02 | 7.17 | 3.71 | 0.596095E+09 | 942.97 | 20-JAN-14:09 | 7.17 | 3.71 |
February | 0.681883E+10 | 21741.65 | 26-FEB-13:02 | 17.83 | 4.74 | 0.535584E+09 | 879.39 | 17-FEB-14:09 | 17.83 | 4.74 |
March | 0.724907E+10 | 21293.16 | 12-MAR-12:02 | 18.17 | 6.11 | 0.633671E+09 | 904.11 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.467033E+10 | 13184.30 | 21-APR-13:10 | 15.83 | 6.37 | 0.558994E+09 | 847.18 | 21-APR-13:50 | 15.17 | 5.71 |
May | 0.624212E+10 | 10965.97 | 16-MAY-13:20 | 27.33 | 12.20 | 0.644608E+09 | 845.67 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.983377E+10 | 20578.38 | 25-JUN-16:21 | 32.70 | 13.84 | 0.660819E+09 | 846.52 | 30-JUN-13:39 | 35.53 | 14.15 |
July | 0.996343E+10 | 18955.54 | 30-JUL-13:13 | 28.33 | 19.61 | 0.614901E+09 | 845.66 | 19-JUL-09:00 | 28.33 | 19.61 |
August | 0.119984E+11 | 21577.28 | 20-AUG-10:52 | 29.00 | 14.54 | 0.690413E+09 | 888.43 | 31-AUG-13:20 | 30.00 | 11.86 |
September | 0.114631E+11 | 23648.42 | 04-SEP-12:41 | 29.22 | 13.51 | 0.610682E+09 | 970.63 | 28-SEP-13:39 | 30.50 | 11.31 |
October | 0.910680E+10 | 24642.74 | 09-OCT-13:11 | 22.00 | 8.98 | 0.592284E+09 | 948.93 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.812175E+10 | 24655.00 | 05-NOV-12:41 | 20.83 | 6.41 | 0.593461E+09 | 949.39 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.578599E+10 | 21471.93 | 03-DEC-13:42 | 17.87 | 6.56 | 0.555055E+09 | 876.69 | 14-DEC-14:09 | 16.25 | 4.44 |
Annual Sum or Average | 0.990557E+11 | 0.728657E+10 | ||||||||
Minimum of Months | 0.467033E+10 | 10965.97 | 7.17 | 3.71 | 0.535584E+09 | 845.66 | 7.17 | 3.71 | ||
Maximum of Months | 0.119984E+11 | 24655.00 | 32.70 | 19.61 | 0.690413E+09 | 970.63 | 35.53 | 19.61 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.216455E+10 | 7062.35 | 20-JAN-16:00 | 18.00 | 7.49 | 0.333420E+09 | 544.93 | 24-JAN-14:00 | 17.00 | 6.48 |
February | 0.200949E+10 | 7626.60 | 17-FEB-16:30 | 13.50 | 6.66 | 0.301510E+09 | 544.94 | 17-FEB-14:00 | 13.50 | 6.66 |
March | 0.358521E+10 | 16145.12 | 12-MAR-16:42 | 18.00 | 5.62 | 0.376679E+09 | 544.94 | 16-MAR-13:50 | 16.00 | 5.38 |
April | 0.342234E+10 | 15991.87 | 08-APR-17:04 | 15.67 | 5.07 | 0.343472E+09 | 544.97 | 13-APR-13:39 | 16.00 | 9.74 |
May | 0.539123E+10 | 12712.11 | 31-MAY-16:00 | 28.00 | 14.86 | 0.408445E+09 | 544.96 | 10-MAY-13:39 | 28.00 | 14.86 |
June | 0.928571E+10 | 25288.30 | 25-JUN-16:21 | 32.70 | 13.84 | 0.425707E+09 | 544.99 | 20-JUN-13:00 | 32.70 | 13.84 |
July | 0.829667E+10 | 23026.57 | 02-JUL-16:41 | 28.00 | 12.40 | 0.395744E+09 | 544.96 | 14-JUL-09:30 | 25.00 | 12.08 |
August | 0.866475E+10 | 24418.80 | 13-AUG-17:11 | 22.33 | 10.08 | 0.443448E+09 | 544.98 | 15-AUG-13:30 | 25.00 | 13.53 |
September | 0.638157E+10 | 24857.47 | 10-SEP-15:51 | 32.20 | 12.77 | 0.385905E+09 | 545.00 | 05-SEP-09:09 | 32.20 | 12.77 |
October | 0.387023E+10 | 21577.61 | 09-OCT-16:31 | 21.33 | 8.70 | 0.354697E+09 | 544.97 | 10-OCT-13:50 | 24.83 | 8.58 |
November | 0.250302E+10 | 8676.14 | 07-NOV-15:40 | 21.33 | 7.24 | 0.336431E+09 | 544.94 | 09-NOV-14:00 | 18.00 | 8.10 |
December | 0.154055E+10 | 5515.44 | 01-DEC-15:30 | 19.50 | 7.14 | 0.312031E+09 | 544.92 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.571153E+11 | 0.441749E+10 | ||||||||
Minimum of Months | 0.154055E+10 | 5515.44 | 13.50 | 5.07 | 0.301510E+09 | 544.92 | 13.50 | 5.38 | ||
Maximum of Months | 0.928571E+10 | 25288.30 | 32.70 | 14.86 | 0.443448E+09 | 545.00 | 32.70 | 14.86 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.521637E+09 | 2491.65 | 20-JAN-15:20 | 19.33 | 7.07 | 0.472960E+09 | 744.80 | 20-JAN-14:00 | 19.33 | 7.07 |
February | 0.413214E+09 | 2055.18 | 17-FEB-14:00 | 15.00 | 6.22 | 0.426634E+09 | 714.81 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.136859E+10 | 4303.75 | 14-MAR-15:00 | 23.00 | 7.59 | 0.550825E+09 | 845.60 | 16-MAR-13:00 | 16.00 | 5.44 |
April | 0.162089E+10 | 5134.87 | 20-APR-13:30 | 21.50 | 8.83 | 0.506627E+09 | 845.64 | 13-APR-13:00 | 21.50 | 8.83 |
May | 0.396457E+10 | 8037.92 | 17-MAY-13:30 | 29.00 | 11.78 | 0.622341E+09 | 845.63 | 18-MAY-09:09 | 20.33 | 11.73 |
June | 0.891935E+10 | 16576.27 | 25-JUN-17:51 | 31.60 | 13.99 | 0.660823E+09 | 866.75 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.867829E+10 | 16611.40 | 16-JUL-14:22 | 35.50 | 14.51 | 0.614379E+09 | 846.87 | 17-JUL-13:20 | 35.67 | 14.82 |
August | 0.770591E+10 | 10381.57 | 20-AUG-15:41 | 28.00 | 14.08 | 0.686625E+09 | 845.64 | 09-AUG-13:09 | 28.00 | 14.08 |
September | 0.504994E+10 | 9009.59 | 11-SEP-14:30 | 28.85 | 13.58 | 0.592101E+09 | 845.69 | 05-SEP-09:09 | 28.85 | 13.58 |
October | 0.165452E+10 | 5150.34 | 11-OCT-14:50 | 26.17 | 9.50 | 0.517620E+09 | 845.61 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.748380E+09 | 2612.95 | 07-NOV-15:10 | 21.83 | 7.31 | 0.481412E+09 | 845.59 | 09-NOV-14:50 | 18.33 | 8.19 |
December | 0.314335E+09 | 1964.56 | 14-DEC-13:30 | 16.15 | 4.27 | 0.449261E+09 | 707.96 | 04-DEC-14:00 | 16.15 | 4.27 |
Annual Sum or Average | 0.409596E+11 | 0.658161E+10 | ||||||||
Minimum of Months | 0.314335E+09 | 1964.56 | 15.00 | 4.27 | 0.426634E+09 | 707.96 | 14.00 | 4.27 | ||
Maximum of Months | 0.891935E+10 | 16611.40 | 35.50 | 14.51 | 0.686625E+09 | 866.75 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.108518E+10 | 3148.61 | 20-JAN-10:10 | 14.67 | 5.12 | 0.318699E+09 | 544.93 | 20-JAN-10:00 | 18.00 | 6.66 |
February | 0.116553E+10 | 3687.83 | 27-FEB-09:30 | 9.50 | 2.73 | 0.298046E+09 | 544.95 | 23-FEB-10:09 | 9.50 | 2.73 |
March | 0.262029E+10 | 9092.30 | 15-MAR-09:10 | 14.17 | 4.19 | 0.388036E+09 | 544.96 | 27-MAR-09:30 | 1.00 | -0.6 |
April | 0.284500E+10 | 10268.63 | 21-APR-09:10 | 12.00 | 5.90 | 0.350304E+09 | 544.98 | 13-APR-13:50 | 12.00 | 5.90 |
May | 0.507562E+10 | 11065.74 | 16-MAY-08:50 | 22.50 | 11.55 | 0.413123E+09 | 544.99 | 17-MAY-09:09 | 25.33 | 11.72 |
June | 0.996749E+10 | 20762.16 | 11-JUN-09:12 | 20.73 | 10.95 | 0.426525E+09 | 547.67 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.932678E+10 | 20839.49 | 02-JUL-09:52 | 24.00 | 9.80 | 0.396465E+09 | 546.27 | 18-JUL-09:00 | 31.00 | 14.50 |
August | 0.949040E+10 | 20495.25 | 20-AUG-09:02 | 26.33 | 13.95 | 0.444074E+09 | 546.03 | 04-AUG-09:00 | 26.33 | 13.95 |
September | 0.646130E+10 | 20745.67 | 04-SEP-09:32 | 25.53 | 13.39 | 0.388007E+09 | 545.03 | 06-SEP-09:30 | 25.75 | 13.14 |
October | 0.249194E+10 | 7402.67 | 11-OCT-09:40 | 22.07 | 8.25 | 0.356831E+09 | 544.96 | 03-OCT-09:09 | 22.07 | 8.25 |
November | 0.129163E+10 | 4233.96 | 07-NOV-09:30 | 14.00 | 4.09 | 0.326843E+09 | 544.95 | 07-NOV-10:00 | 16.00 | 5.55 |
December | 0.722786E+09 | 2334.24 | 14-DEC-13:30 | 16.15 | 4.27 | 0.296684E+09 | 478.48 | 14-DEC-10:20 | 16.15 | 4.27 |
Annual Sum or Average | 0.525439E+11 | 0.440364E+10 | ||||||||
Minimum of Months | 0.722786E+09 | 2334.24 | 9.50 | 2.73 | 0.296684E+09 | 478.48 | 1.00 | -0.6 | ||
Maximum of Months | 0.996749E+10 | 20839.49 | 26.33 | 13.95 | 0.444074E+09 | 547.67 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.606447E+10 | 19099.49 | 20-JAN-13:40 | 21.00 | 6.96 | 0.572006E+09 | 892.37 | 20-JAN-14:09 | 20.83 | 6.93 |
February | 0.552171E+10 | 22806.60 | 26-FEB-13:22 | 17.50 | 4.55 | 0.518844E+09 | 845.88 | 23-FEB-14:00 | 17.50 | 4.55 |
March | 0.626329E+10 | 22780.70 | 12-MAR-12:42 | 18.83 | 6.01 | 0.614828E+09 | 874.29 | 15-MAR-13:39 | 20.67 | 6.10 |
April | 0.401665E+10 | 13628.65 | 21-APR-13:20 | 15.67 | 6.21 | 0.538622E+09 | 846.01 | 21-APR-13:39 | 15.33 | 5.87 |
May | 0.576757E+10 | 11454.99 | 16-MAY-13:30 | 27.50 | 12.26 | 0.625754E+09 | 845.67 | 26-MAY-13:09 | 12.83 | 7.87 |
June | 0.103635E+11 | 21545.55 | 25-JUN-15:51 | 32.70 | 13.68 | 0.658900E+09 | 862.82 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.104483E+11 | 22177.69 | 02-JUL-16:31 | 28.00 | 12.40 | 0.613459E+09 | 845.66 | 18-JUL-13:00 | 31.00 | 15.59 |
August | 0.123629E+11 | 23251.04 | 20-AUG-13:42 | 27.83 | 14.68 | 0.687627E+09 | 873.86 | 31-AUG-13:30 | 30.00 | 11.81 |
September | 0.112236E+11 | 26152.21 | 04-SEP-12:51 | 29.40 | 13.53 | 0.604026E+09 | 940.44 | 28-SEP-13:39 | 30.50 | 11.31 |
October | 0.789988E+10 | 26600.63 | 09-OCT-13:41 | 22.00 | 8.68 | 0.571050E+09 | 908.30 | 10-OCT-13:39 | 24.67 | 8.45 |
November | 0.639864E+10 | 25547.69 | 05-NOV-14:31 | 21.00 | 6.63 | 0.570547E+09 | 898.38 | 07-NOV-14:09 | 22.00 | 7.34 |
December | 0.446242E+10 | 22686.39 | 17-DEC-14:42 | 17.58 | 5.66 | 0.532561E+09 | 845.79 | 15-DEC-14:00 | 17.58 | 5.66 |
Annual Sum or Average | 0.907930E+11 | 0.710822E+10 | ||||||||
Minimum of Months | 0.401665E+10 | 11454.99 | 15.67 | 4.55 | 0.518844E+09 | 845.66 | 12.83 | 4.55 | ||
Maximum of Months | 0.123629E+11 | 26600.63 | 32.70 | 14.68 | 0.687627E+09 | 940.44 | 37.70 | 15.59 |
Report: ZoneCoolingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.150666E+10 | 6800.76 | 20-JAN-16:00 | 18.00 | 7.49 | 0.323250E+09 | 544.93 | 20-JAN-14:00 | 18.00 | 7.49 |
February | 0.149560E+10 | 7262.19 | 17-FEB-16:30 | 13.50 | 6.66 | 0.294663E+09 | 544.91 | 27-FEB-14:00 | 14.00 | 4.75 |
March | 0.307973E+10 | 14575.38 | 12-MAR-16:42 | 18.00 | 5.62 | 0.365017E+09 | 544.94 | 16-MAR-13:39 | 16.00 | 5.33 |
April | 0.300715E+10 | 16059.96 | 08-APR-17:04 | 15.67 | 5.07 | 0.331452E+09 | 544.95 | 19-APR-13:00 | 22.00 | 9.00 |
May | 0.511359E+10 | 13271.39 | 31-MAY-16:00 | 28.00 | 14.86 | 0.395561E+09 | 544.95 | 17-MAY-09:09 | 28.00 | 14.86 |
June | 0.968703E+10 | 27218.80 | 11-JUN-16:31 | 28.17 | 12.60 | 0.424236E+09 | 548.22 | 26-JUN-13:00 | 37.70 | 15.22 |
July | 0.864839E+10 | 26728.16 | 02-JUL-16:31 | 28.00 | 12.40 | 0.394292E+09 | 544.96 | 14-JUL-09:39 | 25.33 | 12.19 |
August | 0.889267E+10 | 24845.40 | 13-AUG-17:21 | 22.50 | 10.22 | 0.440594E+09 | 544.97 | 15-AUG-13:00 | 26.00 | 13.91 |
September | 0.627443E+10 | 25085.52 | 17-SEP-16:31 | 26.27 | 10.77 | 0.378396E+09 | 544.99 | 01-SEP-13:00 | 26.27 | 10.77 |
October | 0.326378E+10 | 23593.12 | 09-OCT-16:22 | 21.50 | 8.67 | 0.340379E+09 | 544.95 | 11-OCT-13:09 | 26.17 | 9.50 |
November | 0.181024E+10 | 8362.05 | 07-NOV-15:40 | 21.33 | 7.24 | 0.326163E+09 | 544.94 | 06-NOV-14:00 | 21.33 | 7.24 |
December | 0.106156E+10 | 5103.84 | 01-DEC-15:30 | 19.50 | 7.14 | 0.304814E+09 | 544.93 | 04-DEC-14:00 | 19.00 | 6.13 |
Annual Sum or Average | 0.538408E+11 | 0.431882E+10 | ||||||||
Minimum of Months | 0.106156E+10 | 5103.84 | 13.50 | 5.07 | 0.294663E+09 | 544.91 | 14.00 | 4.75 | ||
Maximum of Months | 0.968703E+10 | 27218.80 | 28.17 | 14.86 | 0.440594E+09 | 548.22 | 37.70 | 15.22 |
Report: ZoneCoolingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.119591E+10 | 5048.42 | 05-JAN-06:01 | -17.0 | -17.0 | 0.00 | 0.00 | 01-JAN-00:10 | -17.0 | -17.0 |
February | 0.990006E+09 | 3397.18 | 24-FEB-06:07 | 0.17 | -0.4 | 0.00 | 0.00 | 01-FEB-00:10 | 0.17 | -0.4 |
March | 0.248578E+10 | 5933.66 | 13-MAR-16:00 | 23.00 | 6.97 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 6.97 |
April | 0.279977E+10 | 5105.96 | 21-APR-13:40 | 15.33 | 5.87 | 0.00 | 0.00 | 01-APR-00:10 | 15.33 | 5.87 |
May | 0.452398E+10 | 6196.92 | 30-MAY-05:15 | 8.33 | 7.37 | 0.00 | 0.00 | 01-MAY-00:10 | 8.33 | 7.37 |
June | 0.863505E+10 | 9497.48 | 26-JUN-14:40 | 38.83 | 15.50 | 0.00 | 0.00 | 01-JUN-00:10 | 38.83 | 15.50 |
July | 0.890038E+10 | 11107.74 | 05-JUL-05:15 | 15.33 | 9.34 | 0.00 | 0.00 | 01-JUL-00:10 | 15.33 | 9.34 |
August | 0.101147E+11 | 12415.85 | 21-AUG-05:15 | 19.83 | 12.23 | 0.00 | 0.00 | 01-AUG-00:10 | 19.83 | 12.23 |
September | 0.654291E+10 | 11597.41 | 05-SEP-05:15 | 14.20 | 8.43 | 0.00 | 0.00 | 01-SEP-00:10 | 14.20 | 8.43 |
October | 0.330393E+10 | 8776.86 | 10-OCT-05:15 | 8.67 | 4.93 | 0.00 | 0.00 | 01-OCT-00:10 | 8.67 | 4.93 |
November | 0.215336E+10 | 4850.83 | 07-NOV-16:10 | 20.00 | 7.03 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 7.03 |
December | 0.119537E+10 | 4401.74 | 21-DEC-05:01 | -18.2 | -18.4 | 0.00 | 0.00 | 01-DEC-00:10 | -18.2 | -18.4 |
Annual Sum or Average | 0.528412E+11 | 0.00 | ||||||||
Minimum of Months | 0.990006E+09 | 3397.18 | -18.2 | -18.4 | 0.00 | 0.00 | -18.2 | -18.4 | ||
Maximum of Months | 0.101147E+11 | 12415.85 | 38.83 | 15.50 | 0.00 | 0.00 | 38.83 | 15.50 |
Report: ZoneCoolingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.402063E+09 | 7127.04 | 14-JAN-05:01 | -16.5 | -16.5 | 0.00 | 0.00 | 01-JAN-00:10 | -16.5 | -16.5 |
February | 0.364071E+09 | 7586.54 | 06-FEB-04:01 | -10.0 | -10.0 | 0.00 | 0.00 | 01-FEB-00:10 | -10.0 | -10.0 |
March | 0.106259E+10 | 9472.37 | 19-MAR-06:33 | -14.8 | -14.8 | 0.00 | 0.00 | 01-MAR-00:10 | -14.8 | -14.8 |
April | 0.794172E+09 | 7398.24 | 15-APR-04:01 | -4.2 | -4.2 | 0.00 | 0.00 | 01-APR-00:10 | -4.2 | -4.2 |
May | 0.277125E+10 | 4576.65 | 18-MAY-14:30 | 23.50 | 11.45 | 0.00 | 0.00 | 01-MAY-00:10 | 23.50 | 11.45 |
June | 0.670665E+10 | 7174.55 | 26-JUN-15:10 | 39.30 | 15.66 | 0.00 | 0.00 | 01-JUN-00:10 | 39.30 | 15.66 |
July | 0.676626E+10 | 7668.67 | 17-JUL-16:00 | 32.00 | 14.52 | 0.00 | 0.00 | 01-JUL-00:10 | 32.00 | 14.52 |
August | 0.667100E+10 | 7189.66 | 21-AUG-14:30 | 27.50 | 14.51 | 0.00 | 0.00 | 01-AUG-00:10 | 27.50 | 14.51 |
September | 0.478627E+10 | 6914.55 | 11-SEP-14:40 | 29.03 | 13.57 | 0.00 | 0.00 | 01-SEP-00:10 | 29.03 | 13.57 |
October | 0.157555E+10 | 8498.96 | 30-OCT-03:02 | -9.2 | -9.2 | 0.00 | 0.00 | 01-OCT-00:10 | -9.2 | -9.2 |
November | 0.604439E+09 | 7256.96 | 30-NOV-04:01 | -13.8 | -14.3 | 0.00 | 0.00 | 01-NOV-00:10 | -13.8 | -14.3 |
December | 0.268687E+09 | 9213.30 | 20-DEC-04:01 | -19.0 | -19.2 | 0.00 | 0.00 | 01-DEC-00:10 | -19.0 | -19.2 |
Annual Sum or Average | 0.327730E+11 | 0.00 | ||||||||
Minimum of Months | 0.268687E+09 | 4576.65 | -19.0 | -19.2 | 0.00 | 0.00 | -19.0 | -19.2 | ||
Maximum of Months | 0.676626E+10 | 9472.37 | 39.30 | 15.66 | 0.00 | 0.00 | 39.30 | 15.66 |
Report: ZoneCoolingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.239301E+09 | 4200.79 | 20-JAN-15:30 | 19.00 | 7.19 | 0.00 | 0.00 | 01-JAN-00:10 | 19.00 | 7.19 |
February | 0.329424E+09 | 4659.63 | 18-FEB-13:40 | 20.00 | 7.73 | 0.00 | 0.00 | 01-FEB-00:10 | 20.00 | 7.73 |
March | 0.186529E+10 | 11200.45 | 14-MAR-14:20 | 23.00 | 7.59 | 0.00 | 0.00 | 01-MAR-00:10 | 23.00 | 7.59 |
April | 0.217776E+10 | 11640.01 | 21-APR-13:30 | 15.50 | 6.04 | 0.00 | 0.00 | 01-APR-00:10 | 15.50 | 6.04 |
May | 0.537005E+10 | 15738.17 | 31-MAY-14:30 | 28.00 | 14.75 | 0.00 | 0.00 | 01-MAY-00:10 | 28.00 | 14.75 |
June | 0.134492E+11 | 22207.99 | 26-JUN-13:30 | 37.15 | 15.33 | 0.00 | 0.00 | 01-JUN-00:10 | 37.15 | 15.33 |
July | 0.123223E+11 | 19200.75 | 18-JUL-14:40 | 31.00 | 15.05 | 0.00 | 0.00 | 01-JUL-00:10 | 31.00 | 15.05 |
August | 0.123447E+11 | 21054.30 | 16-AUG-15:10 | 36.17 | 16.19 | 0.00 | 0.00 | 01-AUG-00:10 | 36.17 | 16.19 |
September | 0.758687E+10 | 15167.40 | 12-SEP-14:30 | 29.40 | 13.78 | 0.00 | 0.00 | 01-SEP-00:10 | 29.40 | 13.78 |
October | 0.221332E+10 | 10839.30 | 11-OCT-14:30 | 26.50 | 9.60 | 0.00 | 0.00 | 01-OCT-00:10 | 26.50 | 9.60 |
November | 0.606366E+09 | 5955.94 | 09-NOV-13:10 | 20.00 | 8.90 | 0.00 | 0.00 | 01-NOV-00:10 | 20.00 | 8.90 |
December | 0.123317E+09 | 2500.91 | 03-DEC-14:06 | 18.00 | 6.62 | 0.00 | 0.00 | 01-DEC-00:10 | 18.00 | 6.62 |
Annual Sum or Average | 0.586279E+11 | 0.00 | ||||||||
Minimum of Months | 0.123317E+09 | 2500.91 | 15.50 | 6.04 | 0.00 | 0.00 | 15.50 | 6.04 | ||
Maximum of Months | 0.134492E+11 | 22207.99 | 37.15 | 16.19 | 0.00 | 0.00 | 37.15 | 16.19 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326406E+10 | 2321.34 | 23-JAN-16:40 | 15.67 | 5.76 | 95230898.04 | 126.83 | 10-JAN-14:00 | 15.67 | 5.76 |
February | 0.762950E+10 | 4308.44 | 21-FEB-17:00 | 8.00 | 2.80 | 86396812.98 | 126.83 | 23-FEB-10:00 | 6.00 | 3.52 |
March | 0.140265E+11 | 7146.46 | 31-MAR-24:00 | 6.10 | 2.00 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.10 | 2.00 |
April | 0.187732E+11 | 8156.24 | 07-APR-17:50 | 17.33 | 7.10 | 91605842.94 | 126.83 | 28-APR-09:09 | 10.17 | 7.81 |
May | 0.432329E+10 | 3483.70 | 31-MAY-24:00 | 16.00 | 10.67 | 99237756.82 | 126.85 | 22-MAY-13:50 | 16.00 | 10.67 |
June | 0.943907E+10 | 5355.91 | 30-JUN-24:00 | 22.50 | 11.08 | 98962834.40 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.147594E+11 | 7256.72 | 31-JUL-24:00 | 18.90 | 16.75 | 91884676.60 | 126.85 | 28-JUL-09:09 | 18.90 | 16.75 |
August | 0.201816E+11 | 8426.54 | 05-AUG-18:40 | 19.33 | 15.14 | 0.105239E+09 | 151.02 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.440927E+10 | 3343.14 | 30-SEP-24:00 | 10.40 | 8.79 | 91608347.33 | 126.85 | 01-SEP-13:00 | 10.40 | 8.79 |
October | 0.914653E+10 | 4633.79 | 09-OCT-16:43 | 21.17 | 8.73 | 95231517.11 | 126.84 | 03-OCT-09:00 | 21.17 | 8.73 |
November | 0.136039E+11 | 6236.23 | 07-NOV-16:10 | 20.00 | 7.03 | 94301062.65 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.189280E+11 | 8050.09 | 03-DEC-16:15 | 14.33 | 5.69 | 91881071.67 | 126.82 | 28-DEC-14:00 | 9.00 | 2.96 |
Annual Sum or Average | 0.138484E+12 | 0.114482E+10 | ||||||||
Minimum of Months | 0.326406E+10 | 2321.34 | 6.10 | 2.00 | 86396812.98 | 126.82 | 5.00 | 2.00 | ||
Maximum of Months | 0.201816E+11 | 8426.54 | 22.50 | 16.75 | 0.105239E+09 | 151.02 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154135E+10 | 2094.04 | 24-JAN-16:40 | 13.00 | 4.84 | 95222516.72 | 126.83 | 10-JAN-14:00 | 13.00 | 4.84 |
February | 0.557638E+10 | 3972.62 | 23-FEB-17:00 | 5.00 | 2.11 | 86396808.84 | 126.83 | 23-FEB-10:00 | 5.00 | 2.11 |
March | 0.118594E+11 | 6589.51 | 31-MAR-23:40 | 6.53 | 2.12 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.53 | 2.12 |
April | 0.163329E+11 | 7631.89 | 07-APR-17:50 | 17.33 | 7.10 | 91605695.16 | 126.83 | 28-APR-09:00 | 11.00 | 8.15 |
May | 0.355019E+10 | 3275.85 | 31-MAY-24:00 | 16.00 | 10.67 | 99237115.23 | 126.85 | 22-MAY-09:00 | 16.00 | 10.67 |
June | 0.885353E+10 | 5228.79 | 30-JUN-24:00 | 22.50 | 11.08 | 98962569.84 | 126.85 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.139800E+11 | 6838.99 | 31-JUL-24:00 | 18.90 | 16.75 | 91884884.52 | 126.84 | 28-JUL-09:20 | 18.90 | 16.75 |
August | 0.187567E+11 | 7865.34 | 05-AUG-18:11 | 19.67 | 15.26 | 0.104420E+09 | 145.65 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.379671E+10 | 3005.48 | 30-SEP-24:00 | 10.40 | 8.79 | 91608204.29 | 126.85 | 01-SEP-13:00 | 10.40 | 8.79 |
October | 0.757582E+10 | 4112.72 | 09-OCT-16:43 | 21.17 | 8.73 | 95231426.34 | 126.83 | 03-OCT-09:00 | 21.17 | 8.73 |
November | 0.113939E+11 | 5811.11 | 07-NOV-16:20 | 19.00 | 6.82 | 94301054.67 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.154697E+11 | 7314.91 | 15-DEC-16:00 | 6.00 | 2.22 | 91880799.96 | 126.82 | 28-DEC-14:50 | 9.00 | 2.91 |
Annual Sum or Average | 0.118687E+12 | 0.114399E+10 | ||||||||
Minimum of Months | 0.154135E+10 | 2094.04 | 5.00 | 2.11 | 86396808.84 | 126.82 | 5.00 | 2.11 | ||
Maximum of Months | 0.187567E+11 | 7865.34 | 22.50 | 16.75 | 0.104420E+09 | 145.65 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.655515E+09 | 2083.90 | 20-JAN-16:40 | 14.00 | 6.06 | 93593770.87 | 126.84 | 02-JAN-14:09 | 14.00 | 6.06 |
February | 0.406344E+10 | 3930.48 | 17-FEB-17:00 | 13.00 | 6.46 | 86396934.63 | 126.83 | 23-FEB-10:00 | 6.00 | 3.52 |
March | 0.104819E+11 | 6392.59 | 31-MAR-23:20 | 6.97 | 2.22 | 0.103237E+09 | 126.83 | 17-MAR-13:00 | 6.97 | 2.22 |
April | 0.149321E+11 | 7720.46 | 07-APR-17:40 | 17.67 | 7.11 | 91605769.42 | 126.83 | 28-APR-09:00 | 11.00 | 8.15 |
May | 0.303660E+10 | 3231.12 | 31-MAY-24:00 | 16.00 | 10.67 | 99204522.04 | 126.84 | 30-MAY-09:00 | 16.00 | 10.67 |
June | 0.884883E+10 | 5242.58 | 30-JUN-24:00 | 22.50 | 11.08 | 98962802.48 | 126.86 | 22-JUN-13:09 | 22.50 | 11.08 |
July | 0.139902E+11 | 6736.71 | 31-JUL-24:00 | 18.90 | 16.75 | 91884975.57 | 126.84 | 28-JUL-09:20 | 18.90 | 16.75 |
August | 0.187265E+11 | 7981.74 | 13-AUG-18:50 | 21.33 | 9.71 | 0.104263E+09 | 145.96 | 16-AUG-13:00 | 37.00 | 16.36 |
September | 0.350382E+10 | 2782.74 | 10-SEP-17:40 | 29.77 | 11.98 | 91608151.62 | 126.85 | 01-SEP-13:00 | 29.77 | 11.98 |
October | 0.621582E+10 | 4077.71 | 08-OCT-16:50 | 17.17 | 8.30 | 95231395.55 | 126.83 | 03-OCT-09:00 | 17.17 | 8.30 |
November | 0.965105E+10 | 5805.72 | 07-NOV-16:20 | 19.00 | 6.82 | 94301084.46 | 126.83 | 10-NOV-10:00 | 5.00 | 5.00 |
December | 0.135556E+11 | 7250.23 | 14-DEC-16:00 | 13.00 | 4.65 | 91880813.98 | 126.82 | 19-DEC-14:09 | -14.2 | -14.8 |
Annual Sum or Average | 0.107661E+12 | 0.114217E+10 | ||||||||
Minimum of Months | 0.655515E+09 | 2083.90 | 6.97 | 2.22 | 86396934.63 | 126.82 | -14.2 | -14.8 | ||
Maximum of Months | 0.187265E+11 | 7981.74 | 29.77 | 16.75 | 0.104263E+09 | 145.96 | 37.00 | 16.75 |
Report: ZoneCoolingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.236818E+12 | 91521.53 | 24-JAN-17:00 | 12.00 | 4.41 | 0.206148E+10 | 2745.81 | 23-JAN-14:09 | 12.00 | 4.41 |
February | 0.433839E+12 | 183001.05 | 27-FEB-17:00 | 13.00 | 4.60 | 0.187271E+10 | 2749.75 | 06-FEB-10:00 | 13.00 | 4.60 |
March | 0.727138E+12 | 357921.59 | 31-MAR-24:00 | 6.10 | 2.00 | 0.223670E+10 | 2748.36 | 30-MAR-13:30 | 6.10 | 2.00 |
April | 0.935466E+12 | 365444.44 | 21-APR-07:15 | 9.67 | 5.88 | 0.224467E+10 | 3603.55 | 19-APR-13:00 | 9.67 | 5.88 |
May | 0.239882E+12 | 175659.55 | 31-MAY-24:00 | 16.00 | 10.67 | 0.214840E+10 | 2747.94 | 16-MAY-13:50 | 16.00 | 10.67 |
June | 0.470029E+12 | 267770.50 | 30-JUN-24:00 | 22.50 | 11.08 | 0.214408E+10 | 2749.64 | 16-JUN-09:09 | 22.50 | 11.08 |
July | 0.731187E+12 | 355872.50 | 31-JUL-23:15 | 18.70 | 17.05 | 0.198983E+10 | 2750.75 | 17-JUL-13:20 | 18.70 | 17.05 |
August | 0.957620E+12 | 365833.16 | 17-AUG-07:10 | 14.33 | 5.88 | 0.324359E+10 | 4648.95 | 16-AUG-13:00 | 14.33 | 5.88 |
September | 0.236485E+12 | 176081.66 | 30-SEP-24:00 | 10.40 | 8.79 | 0.198365E+10 | 2748.07 | 27-SEP-13:00 | 10.40 | 8.79 |
October | 0.486325E+12 | 265953.28 | 31-OCT-24:00 | -5.8 | -5.8 | 0.206424E+10 | 2749.80 | 26-OCT-13:00 | -5.8 | -5.8 |
November | 0.707207E+12 | 276363.22 | 07-NOV-17:00 | 15.00 | 5.62 | 0.204304E+10 | 2748.26 | 17-NOV-14:50 | 12.33 | 5.08 |
December | 0.969430E+12 | 366701.78 | 18-DEC-17:00 | -6.0 | -6.8 | 0.218103E+10 | 3472.59 | 04-DEC-14:00 | -6.0 | -6.8 |
Annual Sum or Average | 0.713142E+13 | 0.262134E+11 | ||||||||
Minimum of Months | 0.236485E+12 | 91521.53 | -6.0 | -6.8 | 0.187271E+10 | 2745.81 | -6.0 | -6.8 | ||
Maximum of Months | 0.969430E+12 | 366701.78 | 22.50 | 17.05 | 0.324359E+10 | 4648.95 | 22.50 | 17.05 |
Report: ZoneHeatingSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218306E+09 | 14618.64 | 17-JAN-04:52 | -1.0 |
February | 0.147893E+09 | 12813.29 | 21-FEB-04:07 | -1.0 |
March | 0.119988E+09 | 14186.40 | 14-MAR-03:53 | 7.00 |
April | 0.121397E+09 | 12631.70 | 27-APR-04:05 | 6.00 |
May | 0.238721E+09 | 12847.20 | 08-MAY-03:05 | 7.00 |
June | 0.316739E+09 | 18381.86 | 24-JUN-16:01 | 31.60 |
July | 0.475953E+09 | 21120.54 | 15-JUL-16:01 | 34.00 |
August | 0.424189E+09 | 19638.81 | 26-AUG-16:01 | 32.67 |
September | 0.409217E+09 | 15871.44 | 02-SEP-16:01 | 29.62 |
October | 0.302236E+09 | 12605.97 | 03-OCT-03:15 | 4.00 |
November | 0.226614E+09 | 12983.50 | 13-NOV-04:45 | 1.00 |
December | 0.173488E+09 | 12453.24 | 23-DEC-06:05 | -22.1 |
Annual Sum or Average | 0.317474E+10 | |||
Minimum of Months | 0.119988E+09 | 12453.24 | -22.1 | |
Maximum of Months | 0.475953E+09 | 21120.54 | 34.00 |
Report: ZoneHeatingSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 20049843.69 | 41183.37 | 06-FEB-06:01 | -10.0 |
March | 160108.17 | 2134.78 | 20-MAR-05:01 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.143976E+09 | 44241.83 | 26-DEC-05:01 | 3.67 |
Annual Sum or Average | 0.164186E+09 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.143976E+09 | 44241.83 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.230229E+10 | 72857.88 | 17-JAN-04:11 | -1.7 |
February | 0.229062E+10 | 75805.88 | 06-FEB-04:11 | -10.0 |
March | 0.107411E+10 | 73516.25 | 20-MAR-03:01 | -1.5 |
April | 0.138130E+10 | 72318.12 | 17-APR-03:01 | -8.0 |
May | 0.101114E+09 | 65980.47 | 01-MAY-04:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.820154E+09 | 71200.55 | 30-OCT-03:11 | -9.3 |
November | 0.113431E+10 | 67609.39 | 27-NOV-05:01 | -7.0 |
December | 0.319874E+10 | 74960.21 | 26-DEC-04:01 | 0.50 |
Annual Sum or Average | 0.123026E+11 | |||
Minimum of Months | 0.00 | 0.00 | -10.0 | |
Maximum of Months | 0.319874E+10 | 75805.88 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.117429E+09 | 11231.19 | 06-JAN-05:01 | -7.8 |
February | 99525881.68 | 11243.88 | 13-FEB-05:01 | -11.0 |
March | 2361230.67 | 10671.61 | 20-MAR-05:01 | 0.00 |
April | 505717.47 | 6742.90 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 12947459.63 | 10719.03 | 31-OCT-05:01 | -8.2 |
November | 38722406.33 | 10829.19 | 01-NOV-05:01 | -3.0 |
December | 0.390331E+09 | 11808.48 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.661822E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.390331E+09 | 11808.48 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 89061235.89 | 10903.35 | 06-JAN-05:01 | -7.8 |
February | 0.112462E+09 | 10858.40 | 06-FEB-05:01 | -10.0 |
March | 6721104.76 | 9875.29 | 20-MAR-05:01 | 0.00 |
April | 7010171.39 | 9193.68 | 17-APR-05:01 | -8.0 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 30161388.09 | 10477.54 | 30-OCT-05:01 | -10.0 |
November | 59831742.09 | 10651.35 | 30-NOV-05:01 | -12.8 |
December | 0.334632E+09 | 11770.15 | 23-DEC-05:01 | -21.4 |
Annual Sum or Average | 0.639879E+09 | |||
Minimum of Months | 0.00 | 0.00 | -21.4 | |
Maximum of Months | 0.334632E+09 | 11770.15 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.134153E+09 | 15660.36 | 06-JAN-05:01 | -7.8 |
February | 0.240387E+09 | 16447.00 | 06-FEB-05:01 | -10.0 |
March | 35038300.22 | 15135.12 | 20-MAR-04:01 | 0.83 |
April | 51497050.41 | 14876.15 | 17-APR-04:46 | -8.0 |
May | 15779.04 | 210.39 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 96915814.87 | 15191.91 | 31-OCT-04:01 | -8.0 |
November | 93316144.20 | 15349.02 | 01-NOV-04:01 | -3.0 |
December | 0.372231E+09 | 16305.84 | 22-DEC-05:01 | -21.0 |
Annual Sum or Average | 0.102355E+10 | |||
Minimum of Months | 0.00 | 0.00 | -21.0 | |
Maximum of Months | 0.372231E+09 | 16447.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 9104915.83 | 8298.18 | 06-JAN-06:01 | -7.0 |
February | 4050750.64 | 8236.18 | 06-FEB-06:01 | -10.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 380981.16 | 3450.54 | 31-OCT-05:01 | -8.2 |
November | 909225.05 | 7869.41 | 01-NOV-05:01 | -3.0 |
December | 4671647.45 | 6731.09 | 21-DEC-06:01 | -19.0 |
Annual Sum or Average | 19117520.12 | |||
Minimum of Months | 0.00 | 0.00 | -19.0 | |
Maximum of Months | 9104915.83 | 8298.18 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152537E+10 | 11807.61 | 06-JAN-04:01 | -11.3 |
February | 0.218977E+10 | 12848.60 | 12-FEB-05:52 | -19.0 |
March | 0.102859E+10 | 12989.71 | 19-MAR-06:33 | -14.8 |
April | 0.506809E+09 | 12063.88 | 17-APR-03:01 | -8.0 |
May | 22490895.57 | 10492.00 | 01-MAY-04:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 4005727.64 | 8647.87 | 22-SEP-05:02 | -1.7 |
October | 0.603977E+09 | 12076.30 | 30-OCT-03:02 | -9.2 |
November | 0.109071E+10 | 12103.73 | 01-NOV-03:01 | -3.5 |
December | 0.366959E+10 | 13425.37 | 24-DEC-06:52 | -20.0 |
Annual Sum or Average | 0.106413E+11 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.366959E+10 | 13425.37 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.723581E+09 | 15646.79 | 06-JAN-04:01 | -11.3 |
February | 0.113406E+10 | 16677.40 | 06-FEB-04:01 | -10.0 |
March | 0.583128E+09 | 16080.00 | 20-MAR-03:01 | -1.5 |
April | 0.297773E+09 | 15671.90 | 17-APR-03:01 | -8.0 |
May | 11611209.90 | 12853.23 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 2142324.27 | 5970.81 | 22-SEP-05:02 | -1.7 |
October | 0.422667E+09 | 15726.95 | 30-OCT-03:02 | -9.2 |
November | 0.609927E+09 | 16008.65 | 01-NOV-03:01 | -3.5 |
December | 0.201584E+10 | 17481.98 | 24-DEC-06:52 | -20.0 |
Annual Sum or Average | 0.580073E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.201584E+10 | 17481.98 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.481048E+09 | 15815.88 | 06-JAN-05:01 | -7.8 |
February | 0.109173E+10 | 17875.07 | 06-FEB-04:01 | -10.0 |
March | 0.683472E+09 | 18164.96 | 19-MAR-06:33 | -14.8 |
April | 0.434997E+09 | 17008.53 | 17-APR-03:01 | -8.0 |
May | 24659537.92 | 14542.34 | 01-MAY-04:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 1886737.18 | 5713.74 | 22-SEP-05:02 | -1.7 |
October | 0.507388E+09 | 16690.87 | 30-OCT-03:02 | -9.2 |
November | 0.501191E+09 | 17049.98 | 01-NOV-03:01 | -3.5 |
December | 0.163577E+10 | 18672.59 | 24-DEC-06:52 | -20.0 |
Annual Sum or Average | 0.536214E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.163577E+10 | 18672.59 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.510489E+09 | 15082.04 | 06-JAN-05:01 | -7.8 |
February | 0.764149E+09 | 17092.70 | 06-FEB-04:01 | -10.0 |
March | 0.383675E+09 | 15808.53 | 20-MAR-03:01 | -1.5 |
April | 0.224273E+09 | 15868.94 | 17-APR-03:01 | -8.0 |
May | 7028199.61 | 12919.14 | 01-MAY-05:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 2993729.05 | 6319.71 | 22-SEP-05:02 | -1.7 |
October | 0.298812E+09 | 15532.29 | 30-OCT-03:02 | -9.2 |
November | 0.406199E+09 | 16209.41 | 01-NOV-03:01 | -3.5 |
December | 0.144741E+10 | 17853.41 | 24-DEC-06:52 | -20.0 |
Annual Sum or Average | 0.404503E+10 | |||
Minimum of Months | 0.00 | 0.00 | -20.0 | |
Maximum of Months | 0.144741E+10 | 17853.41 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.548115E+10 | 15068.88 | 16-JAN-08:13 | -8.7 |
February | 0.582447E+10 | 15816.01 | 12-FEB-05:52 | -19.0 |
March | 0.373299E+10 | 16170.46 | 19-MAR-06:11 | -14.0 |
April | 0.246504E+10 | 15109.96 | 16-APR-20:12 | -2.3 |
May | 0.217274E+09 | 14085.27 | 01-MAY-03:01 | 5.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 81125965.14 | 12576.82 | 22-SEP-04:02 | -0.3 |
October | 0.242327E+10 | 15124.47 | 29-OCT-20:33 | -7.0 |
November | 0.385765E+10 | 14981.20 | 30-NOV-03:13 | -14.0 |
December | 0.857257E+10 | 15837.15 | 23-DEC-23:52 | -22.0 |
Annual Sum or Average | 0.326555E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.0 | |
Maximum of Months | 0.857257E+10 | 16170.46 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.260235E+10 | 16928.68 | 17-JAN-04:11 | -1.7 |
February | 0.295723E+10 | 18071.88 | 12-FEB-05:52 | -19.0 |
March | 0.196721E+10 | 18526.62 | 19-MAR-06:11 | -14.0 |
April | 0.138990E+10 | 17282.59 | 03-APR-03:11 | -8.0 |
May | 0.105184E+09 | 16171.21 | 01-MAY-03:01 | 5.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 39516727.84 | 14288.67 | 22-SEP-04:02 | -0.3 |
October | 0.149139E+10 | 17297.34 | 30-OCT-03:11 | -9.3 |
November | 0.198519E+10 | 17134.94 | 01-NOV-03:01 | -3.5 |
December | 0.478305E+10 | 18031.95 | 23-DEC-23:52 | -22.0 |
Annual Sum or Average | 0.173210E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.0 | |
Maximum of Months | 0.478305E+10 | 18526.62 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.218997E+10 | 19761.02 | 05-JAN-04:11 | -16.3 |
February | 0.331197E+10 | 20828.26 | 12-FEB-05:52 | -19.0 |
March | 0.268475E+10 | 21754.15 | 19-MAR-06:11 | -14.0 |
April | 0.210624E+10 | 20263.11 | 03-APR-03:11 | -8.0 |
May | 0.216178E+09 | 18970.50 | 01-MAY-03:01 | 5.92 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 59015690.04 | 16659.72 | 22-SEP-04:02 | -0.3 |
October | 0.191799E+10 | 20173.93 | 30-OCT-03:11 | -9.3 |
November | 0.195745E+10 | 20017.13 | 01-NOV-03:01 | -3.5 |
December | 0.464340E+10 | 20950.24 | 22-DEC-03:02 | -22.8 |
Annual Sum or Average | 0.190870E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.464340E+10 | 21754.15 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.207099E+10 | 19548.03 | 17-JAN-04:11 | -1.7 |
February | 0.232565E+10 | 20343.28 | 12-FEB-05:52 | -19.0 |
March | 0.153239E+10 | 21226.21 | 19-MAR-06:11 | -14.0 |
April | 0.987719E+09 | 19824.22 | 03-APR-03:11 | -8.0 |
May | 94232078.84 | 17248.18 | 01-MAY-04:01 | 6.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 37277374.11 | 16499.30 | 22-SEP-04:02 | -0.3 |
October | 0.109063E+10 | 19840.79 | 30-OCT-03:11 | -9.3 |
November | 0.150675E+10 | 19696.55 | 01-NOV-03:01 | -3.5 |
December | 0.372207E+10 | 20480.50 | 22-DEC-03:02 | -22.8 |
Annual Sum or Average | 0.133677E+11 | |||
Minimum of Months | 0.00 | 0.00 | -22.8 | |
Maximum of Months | 0.372207E+10 | 21226.21 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.404588E+09 | 11371.92 | 17-JAN-06:02 | -0.2 |
February | 0.777235E+09 | 12045.68 | 14-FEB-06:01 | -5.2 |
March | 0.333103E+09 | 12816.23 | 21-MAR-05:01 | 0.00 |
April | 0.174534E+09 | 13867.98 | 18-APR-04:01 | 5.50 |
May | 86847336.16 | 12463.83 | 01-MAY-03:01 | 5.92 |
June | 87094703.79 | 7702.76 | 25-JUN-16:31 | 32.70 |
July | 0.120678E+09 | 9007.69 | 31-JUL-03:02 | 15.83 |
August | 0.123845E+09 | 9326.89 | 20-AUG-15:01 | 28.00 |
September | 91216408.50 | 8417.09 | 25-SEP-03:02 | 7.70 |
October | 0.193253E+09 | 10673.71 | 26-OCT-04:01 | 3.83 |
November | 0.420190E+09 | 12466.28 | 03-NOV-04:01 | -2.0 |
December | 0.788966E+09 | 15308.91 | 26-DEC-06:02 | 7.00 |
Annual Sum or Average | 0.360155E+10 | |||
Minimum of Months | 86847336.16 | 7702.76 | -5.2 | |
Maximum of Months | 0.788966E+09 | 15308.91 | 32.70 |
Report: ZoneHeatingSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.178587E+10 | 9695.15 | 01-JAN-13:53 | 6.00 |
February | 0.225059E+10 | 7186.42 | 26-FEB-13:02 | 17.83 |
March | 0.142282E+10 | 8224.99 | 12-MAR-16:02 | 18.00 |
April | 0.108482E+10 | 7993.67 | 20-APR-05:03 | 7.00 |
May | 0.219337E+09 | 7996.53 | 04-MAY-05:02 | 8.17 |
June | 63317894.09 | 9562.01 | 25-JUN-16:21 | 32.70 |
July | 74940619.02 | 6480.34 | 09-JUL-14:02 | 34.50 |
August | 58763105.67 | 7767.88 | 20-AUG-15:31 | 28.00 |
September | 72414053.20 | 7919.98 | 17-SEP-16:01 | 26.52 |
October | 0.522938E+09 | 9289.00 | 09-OCT-15:11 | 22.00 |
November | 0.135077E+10 | 8897.30 | 05-NOV-12:43 | 20.83 |
December | 0.279428E+10 | 8997.55 | 26-DEC-06:02 | 7.00 |
Annual Sum or Average | 0.117009E+11 | |||
Minimum of Months | 58763105.67 | 6480.34 | 6.00 | |
Maximum of Months | 0.279428E+10 | 9695.15 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.765995E+10 | 23180.89 | 05-JAN-06:01 | -17.0 |
February | 0.744040E+10 | 27786.74 | 13-FEB-05:17 | -11.0 |
March | 0.535226E+10 | 23682.46 | 20-MAR-04:22 | 0.50 |
April | 0.390892E+10 | 25414.36 | 17-APR-04:22 | -8.0 |
May | 0.801730E+09 | 16610.68 | 19-MAY-05:02 | 5.17 |
June | 0.134469E+09 | 15593.64 | 09-JUN-05:03 | 6.97 |
July | 0.111563E+09 | 13417.09 | 03-JUL-04:03 | 11.00 |
August | 0.131055E+09 | 13650.12 | 23-AUG-05:02 | 11.17 |
September | 0.499542E+09 | 15945.44 | 27-SEP-05:02 | 9.22 |
October | 0.413299E+10 | 23865.36 | 30-OCT-04:12 | -10.0 |
November | 0.552431E+10 | 24190.87 | 30-NOV-06:02 | -12.0 |
December | 0.107686E+11 | 29608.72 | 22-DEC-05:12 | -21.0 |
Annual Sum or Average | 0.464658E+11 | |||
Minimum of Months | 0.111563E+09 | 13417.09 | -21.0 | |
Maximum of Months | 0.107686E+11 | 29608.72 | 11.17 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112200E+09 | 483.74 | 01-JAN-08:05 | -3.0 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.112200E+09 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.112200E+09 | 483.74 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.714124E+09 | 709.06 | 01-JAN-17:15 | 1.67 |
February | 83140318.11 | 659.49 | 13-FEB-03:30 | -12.0 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 2509994.20 | 725.43 | 30-APR-23:05 | 5.32 |
May | 29347907.09 | 683.33 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 4966261.75 | 322.08 | 22-SEP-04:55 | -1.7 |
October | 11081470.27 | 470.57 | 30-OCT-03:23 | -9.5 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.845170E+09 | |||
Minimum of Months | 0.00 | 0.00 | -12.0 | |
Maximum of Months | 0.714124E+09 | 725.43 | 22.27 |
Report: ZoneHeatingSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.50 |
February | 0.00 | 0.00 | 01-FEB-00:10 | -5.3 |
March | 0.00 | 0.00 | 01-MAR-00:10 | -1.1 |
April | 0.00 | 0.00 | 01-APR-00:10 | 5.90 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 5.43 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 15.88 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.27 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 18.93 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 18.18 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 10.30 |
November | 0.00 | 0.00 | 01-NOV-00:10 | -5.7 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 2.77 |
Annual Sum or Average | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | -5.7 | |
Maximum of Months | 0.00 | 0.00 | 22.27 |
Report: ZoneElectricSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.148304E+11 | 15519.45 | 02-JAN-08:09 | 0.360447E+11 | 13457.54 | 01-JAN-00:10 |
February | 0.134523E+11 | 15519.45 | 01-FEB-08:09 | 0.325565E+11 | 13457.54 | 01-FEB-00:10 |
March | 0.159851E+11 | 15519.45 | 01-MAR-08:09 | 0.360447E+11 | 13457.54 | 01-MAR-00:10 |
April | 0.142779E+11 | 15519.45 | 03-APR-07:10 | 0.348820E+11 | 13457.54 | 01-APR-00:10 |
May | 0.154078E+11 | 15519.45 | 01-MAY-07:10 | 0.360447E+11 | 13457.54 | 01-MAY-00:10 |
June | 0.153333E+11 | 15519.45 | 01-JUN-07:10 | 0.348820E+11 | 13457.54 | 01-JUN-00:10 |
July | 0.143524E+11 | 15519.45 | 03-JUL-07:10 | 0.360447E+11 | 13457.54 | 01-JUL-00:10 |
August | 0.159851E+11 | 15519.45 | 01-AUG-07:10 | 0.360447E+11 | 13457.54 | 01-AUG-00:10 |
September | 0.142779E+11 | 15519.45 | 01-SEP-07:10 | 0.348820E+11 | 13457.54 | 01-SEP-00:10 |
October | 0.148304E+11 | 15519.45 | 02-OCT-07:10 | 0.360447E+11 | 13457.54 | 01-OCT-00:10 |
November | 0.146566E+11 | 15519.45 | 01-NOV-07:10 | 0.348820E+11 | 13457.54 | 01-NOV-00:10 |
December | 0.143524E+11 | 15519.45 | 01-DEC-08:09 | 0.360447E+11 | 13457.54 | 01-DEC-00:10 |
Annual Sum or Average | 0.177742E+12 | 0.424397E+12 | ||||
Minimum of Months | 0.134523E+11 | 15519.45 | 0.325565E+11 | 13457.54 | ||
Maximum of Months | 0.159851E+11 | 15519.45 | 0.360447E+11 | 13457.54 |
Report: ZoneElectricSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270551E+11 | 18128.59 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244881E+11 | 18128.59 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280558E+11 | 18128.59 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261305E+11 | 18128.59 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275555E+11 | 18128.59 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270261E+11 | 18128.59 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266527E+11 | 18128.59 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280558E+11 | 18128.59 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261160E+11 | 18128.59 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270624E+11 | 18128.59 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264424E+11 | 18128.59 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266454E+11 | 18128.59 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321286E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244881E+11 | 18128.59 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280558E+11 | 18128.59 |
Report: ZoneElectricSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.133188E+11 | 13937.56 | 02-JAN-08:09 | 0.270550E+11 | 18128.52 | 02-JAN-08:09 |
February | 0.120811E+11 | 13937.56 | 01-FEB-08:09 | 0.244880E+11 | 18128.52 | 01-FEB-08:09 |
March | 0.143557E+11 | 13937.56 | 01-MAR-08:09 | 0.280557E+11 | 18128.52 | 01-MAR-08:09 |
April | 0.128226E+11 | 13937.56 | 03-APR-07:10 | 0.261304E+11 | 18128.52 | 03-APR-07:10 |
May | 0.138373E+11 | 13937.56 | 01-MAY-07:10 | 0.275554E+11 | 18128.52 | 01-MAY-07:10 |
June | 0.137704E+11 | 13937.56 | 01-JUN-07:10 | 0.270260E+11 | 18128.52 | 01-JUN-07:10 |
July | 0.128895E+11 | 13937.56 | 03-JUL-07:10 | 0.266526E+11 | 18128.52 | 03-JUL-07:10 |
August | 0.143557E+11 | 13937.56 | 01-AUG-07:10 | 0.280557E+11 | 18128.52 | 01-AUG-07:10 |
September | 0.128226E+11 | 13937.56 | 01-SEP-07:10 | 0.261159E+11 | 18128.52 | 01-SEP-07:10 |
October | 0.133188E+11 | 13937.56 | 02-OCT-07:10 | 0.270623E+11 | 18128.52 | 02-OCT-07:10 |
November | 0.131627E+11 | 13937.56 | 01-NOV-07:10 | 0.264423E+11 | 18128.52 | 01-NOV-07:10 |
December | 0.128895E+11 | 13937.56 | 01-DEC-08:09 | 0.266453E+11 | 18128.52 | 01-DEC-08:09 |
Annual Sum or Average | 0.159625E+12 | 0.321285E+12 | ||||
Minimum of Months | 0.120811E+11 | 13937.56 | 0.244880E+11 | 18128.52 | ||
Maximum of Months | 0.143557E+11 | 13937.56 | 0.280557E+11 | 18128.52 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125095E+10 | 1750.00 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108255E+10 | 1668.32 | 06-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123036E+10 | 1427.43 | 21-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107635E+10 | 1306.44 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114012E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112489E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105945E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119309E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108541E+10 | 1075.02 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.116897E+10 | 1561.41 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.122216E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.121745E+10 | 1750.00 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.138518E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105945E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.125095E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.799567E+09 | 1127.77 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.696314E+09 | 1075.83 | 06-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.793443E+09 | 897.36 | 21-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.695297E+09 | 798.26 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.737667E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.728233E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.685725E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.771967E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.700314E+09 | 692.79 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.751835E+09 | 996.50 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.784731E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.780070E+09 | 1127.77 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.892516E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.685725E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.799567E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121270E+10 | 1750.04 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106707E+10 | 1666.56 | 06-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122568E+10 | 1417.12 | 21-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107830E+10 | 1299.67 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114402E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113077E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106418E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119668E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108424E+10 | 1075.05 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.115972E+10 | 1551.71 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.119667E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.118808E+10 | 1750.04 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137481E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106418E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122568E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.786528E+09 | 1127.77 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.688364E+09 | 1072.90 | 06-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.789271E+09 | 929.42 | 21-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.693016E+09 | 863.01 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.735239E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.726042E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.683593E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.768342E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.698810E+09 | 798.96 | 25-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.749124E+09 | 1008.53 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.772541E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.769301E+09 | 1127.77 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.886017E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.683593E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.789271E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125301E+10 | 1750.00 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108424E+10 | 1670.78 | 06-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123119E+10 | 1437.11 | 21-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107665E+10 | 1319.60 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114043E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112513E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105968E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119302E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108589E+10 | 1075.02 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117010E+10 | 1567.07 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.122390E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.121925E+10 | 1750.00 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.138625E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105968E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.125301E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.799697E+09 | 1127.77 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.696777E+09 | 1076.23 | 06-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.793698E+09 | 899.85 | 21-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.695464E+09 | 802.85 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.737755E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.728348E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.685833E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.772060E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.700456E+09 | 692.79 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.752115E+09 | 997.78 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.785008E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.780423E+09 | 1127.77 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.892763E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.685833E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.799697E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121315E+10 | 1750.04 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106766E+10 | 1669.11 | 06-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122489E+10 | 1427.23 | 21-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107867E+10 | 1313.06 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114442E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113119E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106459E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119706E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108468E+10 | 1075.05 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.116043E+10 | 1557.84 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.119729E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.118856E+10 | 1750.04 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137526E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106459E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122489E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.786728E+09 | 1127.77 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.688579E+09 | 1073.38 | 06-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.789482E+09 | 930.94 | 21-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.693152E+09 | 865.01 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.735367E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.726128E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.683688E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.768456E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.699006E+09 | 800.79 | 25-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.749317E+09 | 1009.46 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.772731E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.769529E+09 | 1127.77 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.886216E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.683688E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.789482E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.125311E+10 | 1750.00 | 02-JAN-16:49 | 0.339718E+10 | 2276.32 | 02-JAN-08:09 |
February | 0.108425E+10 | 1670.70 | 06-FEB-16:00 | 0.307485E+10 | 2276.32 | 01-FEB-08:09 |
March | 0.123120E+10 | 1436.79 | 21-MAR-07:10 | 0.352283E+10 | 2276.32 | 01-MAR-08:09 |
April | 0.107665E+10 | 1319.18 | 03-APR-07:10 | 0.328108E+10 | 2276.32 | 03-APR-07:10 |
May | 0.114043E+10 | 1075.02 | 01-MAY-07:10 | 0.346000E+10 | 2276.32 | 01-MAY-07:10 |
June | 0.112513E+10 | 1075.02 | 01-JUN-07:10 | 0.339353E+10 | 2276.32 | 01-JUN-07:10 |
July | 0.105968E+10 | 1075.02 | 03-JUL-07:10 | 0.334664E+10 | 2276.32 | 03-JUL-07:10 |
August | 0.119302E+10 | 1075.02 | 01-AUG-07:10 | 0.352283E+10 | 2276.32 | 01-AUG-07:10 |
September | 0.108591E+10 | 1075.02 | 01-SEP-07:10 | 0.327926E+10 | 2276.32 | 01-SEP-07:10 |
October | 0.117010E+10 | 1566.88 | 30-OCT-07:10 | 0.339809E+10 | 2276.32 | 02-OCT-07:10 |
November | 0.122391E+10 | 1750.00 | 06-NOV-16:49 | 0.332024E+10 | 2276.32 | 01-NOV-07:10 |
December | 0.121928E+10 | 1750.00 | 01-DEC-16:30 | 0.334573E+10 | 2276.32 | 01-DEC-08:09 |
Annual Sum or Average | 0.138627E+11 | 0.403423E+11 | ||||
Minimum of Months | 0.105968E+10 | 1075.02 | 0.307485E+10 | 2276.32 | ||
Maximum of Months | 0.125311E+10 | 1750.00 | 0.352283E+10 | 2276.32 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.799718E+09 | 1127.77 | 02-JAN-16:49 | 0.218927E+10 | 1466.95 | 02-JAN-08:09 |
February | 0.696788E+09 | 1076.17 | 06-FEB-16:00 | 0.198155E+10 | 1466.95 | 01-FEB-08:09 |
March | 0.793706E+09 | 899.68 | 21-MAR-07:10 | 0.227025E+10 | 1466.95 | 01-MAR-08:09 |
April | 0.695464E+09 | 802.63 | 03-APR-07:10 | 0.211446E+10 | 1466.95 | 03-APR-07:10 |
May | 0.737755E+09 | 692.79 | 01-MAY-07:10 | 0.222976E+10 | 1466.95 | 01-MAY-07:10 |
June | 0.728364E+09 | 692.79 | 01-JUN-07:10 | 0.218692E+10 | 1466.95 | 01-JUN-07:10 |
July | 0.685834E+09 | 692.79 | 03-JUL-07:10 | 0.215670E+10 | 1466.95 | 03-JUL-07:10 |
August | 0.772063E+09 | 692.79 | 01-AUG-07:10 | 0.227025E+10 | 1466.95 | 01-AUG-07:10 |
September | 0.700459E+09 | 692.79 | 01-SEP-07:10 | 0.211328E+10 | 1466.95 | 01-SEP-07:10 |
October | 0.752119E+09 | 997.67 | 30-OCT-07:10 | 0.218986E+10 | 1466.95 | 02-OCT-07:10 |
November | 0.785020E+09 | 1127.77 | 06-NOV-16:49 | 0.213969E+10 | 1466.95 | 01-NOV-07:10 |
December | 0.780439E+09 | 1127.77 | 01-DEC-16:30 | 0.215612E+10 | 1466.95 | 01-DEC-08:09 |
Annual Sum or Average | 0.892773E+10 | 0.259981E+11 | ||||
Minimum of Months | 0.685834E+09 | 692.79 | 0.198155E+10 | 1466.95 | ||
Maximum of Months | 0.799718E+09 | 1127.77 | 0.227025E+10 | 1466.95 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.121316E+10 | 1750.04 | 02-JAN-16:49 | 0.339723E+10 | 2276.35 | 02-JAN-08:09 |
February | 0.106766E+10 | 1669.02 | 06-FEB-16:00 | 0.307490E+10 | 2276.35 | 01-FEB-08:09 |
March | 0.122489E+10 | 1426.92 | 21-MAR-07:10 | 0.352288E+10 | 2276.35 | 01-MAR-08:09 |
April | 0.107866E+10 | 1312.64 | 03-APR-07:10 | 0.328113E+10 | 2276.35 | 03-APR-07:10 |
May | 0.114442E+10 | 1075.05 | 01-MAY-07:10 | 0.346006E+10 | 2276.35 | 01-MAY-07:10 |
June | 0.113119E+10 | 1075.05 | 01-JUN-07:10 | 0.339359E+10 | 2276.35 | 01-JUN-07:10 |
July | 0.106459E+10 | 1075.05 | 03-JUL-07:10 | 0.334669E+10 | 2276.35 | 03-JUL-07:10 |
August | 0.119706E+10 | 1075.05 | 01-AUG-07:10 | 0.352288E+10 | 2276.35 | 01-AUG-07:10 |
September | 0.108468E+10 | 1075.05 | 01-SEP-07:10 | 0.327931E+10 | 2276.35 | 01-SEP-07:10 |
October | 0.116036E+10 | 1557.65 | 30-OCT-07:10 | 0.339814E+10 | 2276.35 | 02-OCT-07:10 |
November | 0.119742E+10 | 1750.04 | 06-NOV-16:49 | 0.332029E+10 | 2276.35 | 01-NOV-07:10 |
December | 0.118857E+10 | 1750.04 | 01-DEC-16:30 | 0.334578E+10 | 2276.35 | 01-DEC-08:09 |
Annual Sum or Average | 0.137527E+11 | 0.403429E+11 | ||||
Minimum of Months | 0.106459E+10 | 1075.05 | 0.307490E+10 | 2276.35 | ||
Maximum of Months | 0.122489E+10 | 1750.04 | 0.352288E+10 | 2276.35 |
Report: ZoneElectricSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.786743E+09 | 1127.77 | 02-JAN-16:49 | 0.218926E+10 | 1466.94 | 02-JAN-08:09 |
February | 0.688581E+09 | 1073.33 | 06-FEB-16:00 | 0.198154E+10 | 1466.94 | 01-FEB-08:09 |
March | 0.789500E+09 | 930.74 | 21-MAR-07:10 | 0.227023E+10 | 1466.94 | 01-MAR-08:09 |
April | 0.693153E+09 | 864.75 | 03-APR-07:10 | 0.211444E+10 | 1466.94 | 03-APR-07:10 |
May | 0.735369E+09 | 692.79 | 01-MAY-07:10 | 0.222974E+10 | 1466.94 | 01-MAY-07:10 |
June | 0.726131E+09 | 692.79 | 01-JUN-07:10 | 0.218691E+10 | 1466.94 | 01-JUN-07:10 |
July | 0.683690E+09 | 692.79 | 03-JUL-07:10 | 0.215669E+10 | 1466.94 | 03-JUL-07:10 |
August | 0.768461E+09 | 692.79 | 01-AUG-07:10 | 0.227023E+10 | 1466.94 | 01-AUG-07:10 |
September | 0.699011E+09 | 801.16 | 25-SEP-07:10 | 0.211327E+10 | 1466.94 | 01-SEP-07:10 |
October | 0.749316E+09 | 1009.34 | 30-OCT-07:10 | 0.218984E+10 | 1466.94 | 02-OCT-07:10 |
November | 0.772754E+09 | 1127.77 | 06-NOV-16:49 | 0.213967E+10 | 1466.94 | 01-NOV-07:10 |
December | 0.769655E+09 | 1127.77 | 01-DEC-16:30 | 0.215610E+10 | 1466.94 | 01-DEC-08:09 |
Annual Sum or Average | 0.886236E+10 | 0.259979E+11 | ||||
Minimum of Months | 0.683690E+09 | 692.79 | 0.198154E+10 | 1466.94 | ||
Maximum of Months | 0.789500E+09 | 1127.77 | 0.227023E+10 | 1466.94 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.387117E+09 | 405.10 | 02-JAN-08:09 | 0.521915E+10 | 1948.61 | 01-JAN-00:10 |
February | 0.351144E+09 | 405.10 | 01-FEB-08:09 | 0.942813E+10 | 3897.21 | 01-FEB-00:10 |
March | 0.417256E+09 | 405.10 | 01-MAR-08:09 | 0.156645E+11 | 7794.42 | 31-MAR-23:10 |
April | 0.372695E+09 | 405.10 | 03-APR-07:10 | 0.201821E+11 | 7794.42 | 01-APR-00:10 |
May | 0.402187E+09 | 405.10 | 01-MAY-07:10 | 0.522616E+10 | 3897.21 | 31-MAY-23:10 |
June | 0.400242E+09 | 405.10 | 01-JUN-07:10 | 0.101086E+11 | 5845.82 | 30-JUN-23:10 |
July | 0.374640E+09 | 405.10 | 03-JUL-07:10 | 0.156645E+11 | 7794.42 | 31-JUL-23:10 |
August | 0.417256E+09 | 405.10 | 01-AUG-07:10 | 0.208555E+11 | 7794.42 | 01-AUG-00:10 |
September | 0.372695E+09 | 405.10 | 01-SEP-07:10 | 0.505780E+10 | 3897.21 | 30-SEP-23:10 |
October | 0.387117E+09 | 405.10 | 02-OCT-07:10 | 0.104453E+11 | 5845.82 | 31-OCT-23:10 |
November | 0.382580E+09 | 405.10 | 01-NOV-07:10 | 0.151524E+11 | 5845.82 | 01-NOV-00:10 |
December | 0.374640E+09 | 405.10 | 01-DEC-08:09 | 0.208766E+11 | 7794.42 | 01-DEC-00:10 |
Annual Sum or Average | 0.463957E+10 | 0.153881E+12 | ||||
Minimum of Months | 0.351144E+09 | 405.10 | 0.505780E+10 | 1948.61 | ||
Maximum of Months | 0.417256E+09 | 405.10 | 0.208766E+11 | 7794.42 |
Report: ZoneElectricSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.418155E+10 | 4375.82 | 02-JAN-08:09 | 0.254202E+12 | 94908.13 | 01-JAN-00:10 |
February | 0.379298E+10 | 4375.82 | 01-FEB-08:09 | 0.459203E+12 | 189816.26 | 01-FEB-00:10 |
March | 0.450711E+10 | 4375.82 | 01-MAR-08:09 | 0.762947E+12 | 379632.52 | 31-MAR-23:10 |
April | 0.402577E+10 | 4375.82 | 03-APR-07:10 | 0.982982E+12 | 379632.52 | 01-APR-00:10 |
May | 0.434433E+10 | 4375.82 | 01-MAY-07:10 | 0.254544E+12 | 189816.26 | 31-MAY-23:10 |
June | 0.432333E+10 | 4375.82 | 01-JUN-07:10 | 0.492345E+12 | 284724.39 | 30-JUN-23:10 |
July | 0.404678E+10 | 4375.82 | 03-JUL-07:10 | 0.762947E+12 | 379632.52 | 31-JUL-23:10 |
August | 0.450711E+10 | 4375.82 | 01-AUG-07:10 | 0.101578E+13 | 379632.52 | 01-AUG-00:10 |
September | 0.402577E+10 | 4375.82 | 01-SEP-07:10 | 0.246344E+12 | 189816.26 | 30-SEP-23:10 |
October | 0.418155E+10 | 4375.82 | 02-OCT-07:10 | 0.508746E+12 | 284724.39 | 31-OCT-23:10 |
November | 0.413254E+10 | 4375.82 | 01-NOV-07:10 | 0.738006E+12 | 284724.39 | 01-NOV-00:10 |
December | 0.404678E+10 | 4375.82 | 01-DEC-08:09 | 0.101681E+13 | 379632.52 | 01-DEC-00:10 |
Annual Sum or Average | 0.501156E+11 | 0.749486E+13 | ||||
Minimum of Months | 0.379298E+10 | 4375.82 | 0.246344E+12 | 94908.13 | ||
Maximum of Months | 0.450711E+10 | 4375.82 | 0.101681E+13 | 379632.52 |
Report: SpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.139531E+11 | 0.154078E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.139143E+11 | 0.153333E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.128805E+11 | 0.142779E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.133902E+11 | 0.148304E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.132595E+11 | 0.146566E+11 | 0.348820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.129193E+11 | 0.143524E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.160687E+12 | 0.177742E+12 | 0.424397E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.121482E+11 | 0.134523E+11 | 0.325565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145160E+11 | 0.159851E+11 | 0.360447E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270551E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270261E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266527E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261160E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270624E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266454E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321286E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244881E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.120254E+11 | 0.133188E+11 | 0.270550E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.115676E+11 | 0.128226E+11 | 0.261304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.125309E+11 | 0.138373E+11 | 0.275554E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.124961E+11 | 0.137704E+11 | 0.270260E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.116025E+11 | 0.128895E+11 | 0.266526E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.115676E+11 | 0.128226E+11 | 0.261159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.120254E+11 | 0.133188E+11 | 0.270623E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.119080E+11 | 0.131627E+11 | 0.264423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.116025E+11 | 0.128895E+11 | 0.266453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.144308E+12 | 0.159625E+12 | 0.321285E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.109099E+11 | 0.120811E+11 | 0.244880E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.130364E+11 | 0.143557E+11 | 0.280557E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.125095E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.490082E+09 |
February | 0.136985E+10 | 0.108255E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.762084E+09 |
March | 0.163685E+10 | 0.123036E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4.44 | 0.836988E+09 |
April | 0.145243E+10 | 0.107635E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.912466E+09 |
May | 0.157338E+10 | 0.114012E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1764487.16 | 0.457267E+09 |
June | 0.156900E+10 | 0.112489E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37156073.94 | 0.190163E+09 |
July | 0.145680E+10 | 0.105945E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47405908.16 | 0.184882E+09 |
August | 0.163685E+10 | 0.119309E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24901169.14 | 0.181699E+09 |
September | 0.145243E+10 | 0.108541E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 14064817.00 | 0.287915E+09 |
October | 0.150991E+10 | 0.116897E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250147.76 | 0.638780E+09 |
November | 0.149516E+10 | 0.122216E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557766E+09 |
December | 0.145680E+10 | 0.121745E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105465E+10 |
Annual Sum or Average | 0.181194E+11 | 0.138518E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125543E+09 | 0.655474E+10 |
Minimum of Months | 0.136985E+10 | 0.105945E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181699E+09 |
Maximum of Months | 0.163685E+10 | 0.125095E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47405908.16 | 0.105465E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.799567E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329918E+09 |
February | 0.882782E+09 | 0.696314E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510424E+09 |
March | 0.105485E+10 | 0.793443E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2.87 | 0.554481E+09 |
April | 0.936002E+09 | 0.695297E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.595961E+09 |
May | 0.101394E+10 | 0.737667E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1180405.69 | 0.303202E+09 |
June | 0.101113E+10 | 0.728233E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25068745.88 | 0.122342E+09 |
July | 0.938820E+09 | 0.685725E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32393249.09 | 0.116947E+09 |
August | 0.105485E+10 | 0.771967E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16886299.36 | 0.107851E+09 |
September | 0.936002E+09 | 0.700314E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9310033.15 | 0.193000E+09 |
October | 0.973041E+09 | 0.751835E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166758.97 | 0.426547E+09 |
November | 0.963541E+09 | 0.784731E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.368285E+09 |
December | 0.938820E+09 | 0.780070E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.692416E+09 |
Annual Sum or Average | 0.116768E+11 | 0.892516E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 85005495.01 | 0.432137E+10 |
Minimum of Months | 0.882782E+09 | 0.685725E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107851E+09 |
Maximum of Months | 0.105485E+10 | 0.799567E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32393249.09 | 0.692416E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.121270E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.511223E+09 |
February | 0.136988E+10 | 0.106707E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783257E+09 |
March | 0.163688E+10 | 0.122568E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842490E+09 |
April | 0.145246E+10 | 0.107830E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.892799E+09 |
May | 0.157341E+10 | 0.114402E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1763251.66 | 0.452601E+09 |
June | 0.156904E+10 | 0.113077E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37044829.45 | 0.187438E+09 |
July | 0.145684E+10 | 0.106418E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47080645.58 | 0.182793E+09 |
August | 0.163688E+10 | 0.119668E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24252464.05 | 0.184641E+09 |
September | 0.145246E+10 | 0.108424E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12198890.20 | 0.301676E+09 |
October | 0.150994E+10 | 0.115972E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 191461.59 | 0.654611E+09 |
November | 0.149520E+10 | 0.119667E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.573777E+09 |
December | 0.145684E+10 | 0.118808E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107655E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137481E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122532E+09 | 0.664386E+10 |
Minimum of Months | 0.136988E+10 | 0.106418E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182793E+09 |
Maximum of Months | 0.163688E+10 | 0.122568E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47080645.58 | 0.107655E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.786528E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344850E+09 |
February | 0.882782E+09 | 0.688364E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543639E+09 |
March | 0.105485E+10 | 0.789271E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3.02 | 0.607045E+09 |
April | 0.936002E+09 | 0.693016E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.673172E+09 |
May | 0.101394E+10 | 0.735239E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1171819.43 | 0.326338E+09 |
June | 0.101113E+10 | 0.726042E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23873766.39 | 0.143624E+09 |
July | 0.938820E+09 | 0.683593E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29590465.72 | 0.140847E+09 |
August | 0.105485E+10 | 0.768342E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 15986155.28 | 0.146713E+09 |
September | 0.936002E+09 | 0.698810E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 8497398.62 | 0.212308E+09 |
October | 0.973041E+09 | 0.749124E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 166764.46 | 0.457959E+09 |
November | 0.963541E+09 | 0.772541E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.402714E+09 |
December | 0.938820E+09 | 0.769301E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.773405E+09 |
Annual Sum or Average | 0.116768E+11 | 0.886017E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 79286372.91 | 0.477262E+10 |
Minimum of Months | 0.882782E+09 | 0.683593E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140847E+09 |
Maximum of Months | 0.105485E+10 | 0.789271E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29590465.72 | 0.773405E+09 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.125301E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102226E+10 |
February | 0.136985E+10 | 0.108424E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160142E+10 |
March | 0.163685E+10 | 0.123119E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173704E+10 |
April | 0.145243E+10 | 0.107665E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185903E+10 |
May | 0.157338E+10 | 0.114043E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3941663.43 | 0.999356E+09 |
June | 0.156900E+10 | 0.112513E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86845709.00 | 0.435375E+09 |
July | 0.145680E+10 | 0.105968E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112046E+09 | 0.433076E+09 |
August | 0.163685E+10 | 0.119302E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 59356589.77 | 0.425001E+09 |
September | 0.145243E+10 | 0.108589E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34008493.59 | 0.626747E+09 |
October | 0.150991E+10 | 0.117010E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 562493.40 | 0.133777E+10 |
November | 0.149516E+10 | 0.122390E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116508E+10 |
December | 0.145680E+10 | 0.121925E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 16231.70 | 0.216033E+10 |
Annual Sum or Average | 0.181194E+11 | 0.138625E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296778E+09 | 0.138025E+11 |
Minimum of Months | 0.136985E+10 | 0.105968E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.425001E+09 |
Maximum of Months | 0.163685E+10 | 0.125301E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112046E+09 | 0.216033E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.715730E+09 | 0.799697E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703345E+09 |
February | 0.649041E+09 | 0.696777E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109928E+10 |
March | 0.773965E+09 | 0.793698E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119678E+10 |
April | 0.688021E+09 | 0.695464E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127486E+10 |
May | 0.744847E+09 | 0.737755E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2634205.16 | 0.679771E+09 |
June | 0.742030E+09 | 0.728348E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56847750.49 | 0.296020E+09 |
July | 0.690839E+09 | 0.685833E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72645860.21 | 0.300120E+09 |
August | 0.773965E+09 | 0.772060E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 37621571.47 | 0.295129E+09 |
September | 0.688021E+09 | 0.700456E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20979827.62 | 0.437806E+09 |
October | 0.715730E+09 | 0.752115E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 360033.28 | 0.925956E+09 |
November | 0.708685E+09 | 0.785008E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.793887E+09 |
December | 0.690839E+09 | 0.780423E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1940.00 | 0.146359E+10 |
Annual Sum or Average | 0.858171E+10 | 0.892763E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.191091E+09 | 0.946654E+10 |
Minimum of Months | 0.649041E+09 | 0.685833E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295129E+09 |
Maximum of Months | 0.773965E+09 | 0.799697E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72645860.21 | 0.146359E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.121315E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.116316E+10 |
February | 0.136988E+10 | 0.106766E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175449E+10 |
March | 0.163688E+10 | 0.122489E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.186695E+10 |
April | 0.145246E+10 | 0.107867E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192817E+10 |
May | 0.157341E+10 | 0.114442E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3932671.80 | 0.102060E+10 |
June | 0.156904E+10 | 0.113119E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85362766.18 | 0.436101E+09 |
July | 0.145684E+10 | 0.106459E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108687E+09 | 0.438951E+09 |
August | 0.163688E+10 | 0.119706E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55469711.31 | 0.456026E+09 |
September | 0.145246E+10 | 0.108468E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 27191781.31 | 0.691441E+09 |
October | 0.150994E+10 | 0.116043E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 287272.94 | 0.147180E+10 |
November | 0.149520E+10 | 0.119729E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129161E+10 |
December | 0.145684E+10 | 0.118856E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235956E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137526E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280931E+09 | 0.148788E+11 |
Minimum of Months | 0.136988E+10 | 0.106459E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.436101E+09 |
Maximum of Months | 0.163688E+10 | 0.122489E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108687E+09 | 0.235956E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.786728E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.721148E+09 |
February | 0.882782E+09 | 0.688579E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112117E+10 |
March | 0.105485E+10 | 0.789482E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121947E+10 |
April | 0.936002E+09 | 0.693152E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129817E+10 |
May | 0.101394E+10 | 0.735367E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2666283.57 | 0.701979E+09 |
June | 0.101113E+10 | 0.726128E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 56511012.72 | 0.317450E+09 |
July | 0.938820E+09 | 0.683688E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72075195.00 | 0.311373E+09 |
August | 0.105485E+10 | 0.768456E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 38820908.65 | 0.318557E+09 |
September | 0.936002E+09 | 0.699006E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 20267879.37 | 0.455997E+09 |
October | 0.973041E+09 | 0.749317E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 392395.20 | 0.941246E+09 |
November | 0.963541E+09 | 0.772731E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.814494E+09 |
December | 0.938820E+09 | 0.769529E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149751E+10 |
Annual Sum or Average | 0.116768E+11 | 0.886216E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190734E+09 | 0.971857E+10 |
Minimum of Months | 0.882782E+09 | 0.683688E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.311373E+09 |
Maximum of Months | 0.105485E+10 | 0.789482E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 72075195.00 | 0.149751E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150991E+10 | 0.125311E+10 | 0.339718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117690E+10 |
February | 0.136985E+10 | 0.108425E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188945E+10 |
March | 0.163685E+10 | 0.123120E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204997E+10 |
April | 0.145243E+10 | 0.107665E+10 | 0.328108E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214034E+10 |
May | 0.157338E+10 | 0.114043E+10 | 0.346000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4661586.58 | 0.117558E+10 |
June | 0.156900E+10 | 0.112513E+10 | 0.339353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103363E+09 | 0.538900E+09 |
July | 0.145680E+10 | 0.105968E+10 | 0.334664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130484E+09 | 0.538381E+09 |
August | 0.163685E+10 | 0.119302E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70131704.14 | 0.522562E+09 |
September | 0.145243E+10 | 0.108591E+10 | 0.327926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39594876.86 | 0.744807E+09 |
October | 0.150991E+10 | 0.117010E+10 | 0.339809E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 687323.78 | 0.153243E+10 |
November | 0.149516E+10 | 0.122391E+10 | 0.332024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 152226.48 | 0.133889E+10 |
December | 0.145680E+10 | 0.121928E+10 | 0.334573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47427.26 | 0.256515E+10 |
Annual Sum or Average | 0.181194E+11 | 0.138627E+11 | 0.403423E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.349123E+09 | 0.162134E+11 |
Minimum of Months | 0.136985E+10 | 0.105968E+10 | 0.307485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522562E+09 |
Maximum of Months | 0.163685E+10 | 0.125311E+10 | 0.352283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130484E+09 | 0.256515E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.799718E+09 | 0.218927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.802966E+09 |
February | 0.882782E+09 | 0.696788E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129902E+10 |
March | 0.105485E+10 | 0.793706E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141741E+10 |
April | 0.936002E+09 | 0.695464E+09 | 0.211446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147495E+10 |
May | 0.101394E+10 | 0.737755E+09 | 0.222976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3096919.83 | 0.809738E+09 |
June | 0.101113E+10 | 0.728364E+09 | 0.218692E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 67533749.59 | 0.369029E+09 |
July | 0.938820E+09 | 0.685834E+09 | 0.215670E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85110583.05 | 0.375629E+09 |
August | 0.105485E+10 | 0.772063E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 44907174.61 | 0.366636E+09 |
September | 0.936002E+09 | 0.700459E+09 | 0.211328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24057695.28 | 0.529085E+09 |
October | 0.973041E+09 | 0.752119E+09 | 0.218986E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 409505.37 | 0.107369E+10 |
November | 0.963541E+09 | 0.785020E+09 | 0.213969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917795E+09 |
December | 0.938820E+09 | 0.780439E+09 | 0.215612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6099.95 | 0.173549E+10 |
Annual Sum or Average | 0.116768E+11 | 0.892773E+10 | 0.259981E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225122E+09 | 0.111714E+11 |
Minimum of Months | 0.882782E+09 | 0.685834E+09 | 0.198155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366636E+09 |
Maximum of Months | 0.105485E+10 | 0.799718E+09 | 0.227025E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 85110583.05 | 0.173549E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.150994E+10 | 0.121316E+10 | 0.339723E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131987E+10 |
February | 0.136988E+10 | 0.106766E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206708E+10 |
March | 0.163688E+10 | 0.122489E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.220529E+10 |
April | 0.145246E+10 | 0.107866E+10 | 0.328113E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222481E+10 |
May | 0.157341E+10 | 0.114442E+10 | 0.346006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4627795.74 | 0.120494E+10 |
June | 0.156904E+10 | 0.113119E+10 | 0.339359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102705E+09 | 0.537743E+09 |
July | 0.145684E+10 | 0.106459E+10 | 0.334669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129037E+09 | 0.543305E+09 |
August | 0.163688E+10 | 0.119706E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 66989618.22 | 0.561890E+09 |
September | 0.145246E+10 | 0.108468E+10 | 0.327931E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 32491036.56 | 0.833403E+09 |
October | 0.150994E+10 | 0.116036E+10 | 0.339814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 455980.20 | 0.171068E+10 |
November | 0.149520E+10 | 0.119742E+10 | 0.332029E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150129E+10 |
December | 0.145684E+10 | 0.118857E+10 | 0.334578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276837E+10 |
Annual Sum or Average | 0.181198E+11 | 0.137527E+11 | 0.403429E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336306E+09 | 0.174787E+11 |
Minimum of Months | 0.136988E+10 | 0.106459E+10 | 0.307490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537743E+09 |
Maximum of Months | 0.163688E+10 | 0.122489E+10 | 0.352288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129037E+09 | 0.276837E+10 |
Report: SpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.973041E+09 | 0.786743E+09 | 0.218926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.826933E+09 |
February | 0.882782E+09 | 0.688581E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133007E+10 |
March | 0.105485E+10 | 0.789500E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144750E+10 |
April | 0.936002E+09 | 0.693153E+09 | 0.211444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150626E+10 |
May | 0.101394E+10 | 0.735369E+09 | 0.222974E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3275950.10 | 0.836632E+09 |
June | 0.101113E+10 | 0.726131E+09 | 0.218691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68457845.13 | 0.392544E+09 |
July | 0.938820E+09 | 0.683690E+09 | 0.215669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86243414.86 | 0.385455E+09 |
August | 0.105485E+10 | 0.768461E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47073390.93 | 0.392612E+09 |
September | 0.936002E+09 | 0.699011E+09 | 0.211327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24556962.27 | 0.548909E+09 |
October | 0.973041E+09 | 0.749316E+09 | 0.218984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 484600.23 | 0.109625E+10 |
November | 0.963541E+09 | 0.772754E+09 | 0.213967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951628E+09 |
December | 0.938820E+09 | 0.769655E+09 | 0.215610E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.177968E+10 |
Annual Sum or Average | 0.116768E+11 | 0.886236E+10 | 0.259979E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230092E+09 | 0.114945E+11 |
Minimum of Months | 0.882782E+09 | 0.683690E+09 | 0.198154E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385455E+09 |
Maximum of Months | 0.105485E+10 | 0.789500E+09 | 0.227023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 86243414.86 | 0.177968E+10 |
Report: SpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.174411E+09 | 0.387117E+09 | 0.521915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158233E+09 | 0.351144E+09 | 0.942813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.189074E+09 | 0.417256E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.167772E+09 | 0.372695E+09 | 0.201821E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.181743E+09 | 0.402187E+09 | 0.522616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181238E+09 | 0.400242E+09 | 0.101086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168277E+09 | 0.374640E+09 | 0.156645E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.189074E+09 | 0.417256E+09 | 0.208555E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.167772E+09 | 0.372695E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174411E+09 | 0.387117E+09 | 0.104453E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172708E+09 | 0.382580E+09 | 0.151524E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168277E+09 | 0.374640E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209299E+10 | 0.463957E+10 | 0.153881E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158233E+09 | 0.351144E+09 | 0.505780E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.189074E+09 | 0.417256E+09 | 0.208766E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 0.377547E+10 | 0.418155E+10 | 0.254202E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.342526E+10 | 0.379298E+10 | 0.459203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.409289E+10 | 0.450711E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.363176E+10 | 0.402577E+10 | 0.982982E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.393418E+10 | 0.434433E+10 | 0.254544E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.392325E+10 | 0.432333E+10 | 0.492345E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364269E+10 | 0.404678E+10 | 0.762947E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.409289E+10 | 0.450711E+10 | 0.101578E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.363176E+10 | 0.402577E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.377547E+10 | 0.418155E+10 | 0.508746E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373861E+10 | 0.413254E+10 | 0.738006E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.364269E+10 | 0.404678E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.453069E+11 | 0.501156E+11 | 0.749486E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.342526E+10 | 0.379298E+10 | 0.246344E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.409289E+10 | 0.450711E+10 | 0.101681E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105821E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163981E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179515E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192892E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2603962.79 | 0.951253E+09 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68533964.49 | 0.396344E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92776258.49 | 0.390436E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43780290.96 | 0.396084E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24096476.06 | 0.611510E+09 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223679.08 | 0.136747E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119368E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225752E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232015E+09 | 0.139864E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390436E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92776258.49 | 0.225752E+10 |
Report: SpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179943E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278166E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304659E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.324979E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4790004.16 | 0.165828E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125548E+09 | 0.700739E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171184E+09 | 0.693470E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 80657686.60 | 0.702453E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45171748.06 | 0.107055E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464489.59 | 0.235684E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.203059E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.372974E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.427817E+09 | 0.238201E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.693470E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171184E+09 | 0.372974E+10 |
Report: SpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181363E+10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290362E+10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.318500E+10 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.336981E+10 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3120236.67 | 0.183499E+10 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111635E+09 | 0.805296E+09 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143997E+09 | 0.806312E+09 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69707485.24 | 0.811856E+09 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33845837.96 | 0.117324E+10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129085.93 | 0.243733E+10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208760E+10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.385803E+10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.362434E+09 | 0.250867E+11 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.805296E+09 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.143997E+09 | 0.385803E+10 |
Report: PeakSpaceGainsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 17832.21 | 02-JAN-10:09 | 15519.45 | 02-JAN-08:09 | 13457.54 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17832.21 | 01-FEB-10:09 | 15519.45 | 01-FEB-08:09 | 13457.54 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17832.21 | 01-MAR-10:09 | 15519.45 | 01-MAR-08:09 | 13457.54 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 17832.21 | 03-APR-09:09 | 15519.45 | 03-APR-07:10 | 13457.54 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 17832.21 | 01-MAY-09:09 | 15519.45 | 01-MAY-07:10 | 13457.54 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 17832.21 | 01-JUN-09:09 | 15519.45 | 01-JUN-07:10 | 13457.54 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 17832.21 | 03-JUL-09:09 | 15519.45 | 03-JUL-07:10 | 13457.54 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 17832.21 | 01-AUG-09:09 | 15519.45 | 01-AUG-07:10 | 13457.54 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 17832.21 | 01-SEP-09:09 | 15519.45 | 01-SEP-07:10 | 13457.54 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 17832.21 | 02-OCT-09:09 | 15519.45 | 02-OCT-07:10 | 13457.54 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 17832.21 | 01-NOV-09:09 | 15519.45 | 01-NOV-07:10 | 13457.54 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 17832.21 | 01-DEC-10:09 | 15519.45 | 01-DEC-08:09 | 13457.54 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 17832.21 | 15519.45 | 13457.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.59 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.59 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.59 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.59 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.59 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.59 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.59 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.59 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.59 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.59 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.59 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.59 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 16014.58 | 02-JAN-10:09 | 13937.56 | 02-JAN-08:09 | 18128.52 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 16014.58 | 01-FEB-10:09 | 13937.56 | 01-FEB-08:09 | 18128.52 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 16014.58 | 01-MAR-10:09 | 13937.56 | 01-MAR-08:09 | 18128.52 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 16014.58 | 03-APR-09:09 | 13937.56 | 03-APR-07:10 | 18128.52 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 16014.58 | 01-MAY-09:09 | 13937.56 | 01-MAY-07:10 | 18128.52 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 16014.58 | 01-JUN-09:09 | 13937.56 | 01-JUN-07:10 | 18128.52 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 16014.58 | 03-JUL-09:09 | 13937.56 | 03-JUL-07:10 | 18128.52 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 16014.58 | 01-AUG-09:09 | 13937.56 | 01-AUG-07:10 | 18128.52 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 16014.58 | 01-SEP-09:09 | 13937.56 | 01-SEP-07:10 | 18128.52 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16014.58 | 02-OCT-09:09 | 13937.56 | 02-OCT-07:10 | 18128.52 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 16014.58 | 01-NOV-09:09 | 13937.56 | 01-NOV-07:10 | 18128.52 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 16014.58 | 01-DEC-10:09 | 13937.56 | 01-DEC-08:09 | 18128.52 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 16014.58 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 951.97 | 13-JAN-05:00 |
February | 2010.79 | 01-FEB-10:09 | 1668.32 | 06-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1181.18 | 05-FEB-22:52 |
March | 2010.79 | 01-MAR-10:09 | 1427.43 | 21-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 2447.32 | 19-MAR-06:51 |
April | 2010.79 | 03-APR-09:09 | 1306.44 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1723.21 | 16-APR-14:53 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 980.19 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 249.63 | 25-JUN-17:54 | 566.87 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 16-JUL-11:55 | 542.81 | 03-JUL-03:00 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 | 02-AUG-16:00 | 627.25 | 27-AUG-17:40 |
September | 2010.79 | 01-SEP-09:09 | 1075.02 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 158.19 | 10-SEP-14:50 | 617.94 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 1561.41 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 19.87 | 11-OCT-14:00 | 1468.36 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1419.64 | 01-NOV-03:55 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2040.21 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.81 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 2447.32 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 630.92 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1075.83 | 06-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 773.41 | 05-FEB-22:52 |
March | 1295.83 | 01-MAR-10:09 | 897.36 | 21-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14-MAR-13:00 | 1602.81 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 798.26 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1139.67 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-MAY-14:50 | 646.01 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 186.11 | 25-JUN-18:00 | 375.37 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.33 | 16-JUL-11:55 | 352.19 | 03-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.69 | 02-AUG-16:00 | 366.21 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 692.79 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.66 | 10-SEP-14:50 | 408.42 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 996.50 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 972.05 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 926.50 | 01-NOV-03:55 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1338.67 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 352.19 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 253.33 | 1602.81 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 960.84 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 1666.56 | 06-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1200.44 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 1417.12 | 21-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2347.43 | 19-MAR-06:51 |
April | 2010.83 | 03-APR-09:09 | 1299.67 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1614.53 | 16-APR-14:53 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 42.97 | 17-MAY-14:50 | 959.08 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 259.49 | 25-JUN-18:00 | 565.25 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 16-JUL-11:55 | 540.60 | 03-JUL-03:00 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 134.54 | 02-AUG-16:00 | 678.69 | 27-AUG-17:40 |
September | 2010.83 | 01-SEP-09:09 | 1075.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 142.79 | 10-SEP-15:00 | 610.11 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 1551.71 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 11-OCT-14:00 | 1440.84 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1374.45 | 01-NOV-04:09 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 2046.74 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 540.60 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 379.92 | 2347.43 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 669.42 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1072.90 | 06-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 837.03 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 929.42 | 21-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.01 | 14-MAR-13:00 | 1711.12 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 863.01 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 1263.20 | 16-APR-14:53 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.65 | 17-MAY-14:50 | 697.09 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 162.15 | 25-JUN-17:54 | 446.44 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.29 | 16-JUL-11:55 | 406.11 | 03-JUL-03:00 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 89.65 | 02-AUG-15:10 | 573.07 | 27-AUG-17:40 |
September | 1295.83 | 01-SEP-09:09 | 798.96 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 100.70 | 10-SEP-14:43 | 425.55 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1008.53 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 13.25 | 11-OCT-14:00 | 1036.37 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 1002.15 | 01-NOV-03:55 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 1438.06 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 406.11 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 253.29 | 1711.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1979.39 | 13-JAN-05:09 |
February | 2010.79 | 01-FEB-10:09 | 1670.78 | 06-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2391.47 | 23-FEB-24:00 |
March | 2010.79 | 01-MAR-10:09 | 1437.11 | 21-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5275.47 | 19-MAR-06:53 |
April | 2010.79 | 03-APR-09:09 | 1319.60 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.27 | 15-APR-04:57 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.48 | 17-MAY-14:50 | 2022.25 | 03-MAY-03:00 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 552.47 | 25-JUN-17:44 | 1231.98 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 880.97 | 16-JUL-11:55 | 1200.33 | 03-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 312.92 | 06-AUG-12:00 | 1435.50 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 1075.02 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 372.29 | 10-SEP-15:00 | 1348.81 | 22-SEP-02:00 |
October | 2010.79 | 02-OCT-09:09 | 1567.07 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 11-OCT-14:00 | 2899.89 | 29-OCT-09:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3238.78 | 01-NOV-04:10 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8.81 | 02-DEC-15:00 | 4433.94 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1200.33 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 880.97 | 5275.47 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1239.33 | 02-JAN-08:09 | 1127.77 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1320.93 | 13-JAN-05:04 |
February | 1239.33 | 01-FEB-08:09 | 1076.23 | 06-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1633.86 | 23-FEB-24:00 |
March | 1239.33 | 01-MAR-08:09 | 899.85 | 21-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3516.98 | 19-MAR-06:59 |
April | 1239.33 | 03-APR-07:10 | 802.85 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.22 | 15-APR-04:56 |
May | 1239.33 | 01-MAY-07:10 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1352.29 | 03-MAY-03:00 |
June | 1239.33 | 01-JUN-07:10 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 434.40 | 25-JUN-17:50 | 833.40 | 08-JUN-23:00 |
July | 1239.33 | 03-JUL-07:10 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 588.10 | 16-JUL-11:55 | 846.62 | 02-JUL-08:40 |
August | 1239.33 | 01-AUG-07:10 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 207.07 | 02-AUG-16:00 | 997.38 | 27-AUG-17:55 |
September | 1239.33 | 01-SEP-07:10 | 692.79 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 264.11 | 10-SEP-14:40 | 898.40 | 22-SEP-02:00 |
October | 1239.33 | 02-OCT-07:10 | 997.78 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 11-OCT-14:00 | 1963.48 | 29-OCT-09:00 |
November | 1239.33 | 01-NOV-07:10 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2159.24 | 01-NOV-04:10 |
December | 1239.33 | 01-DEC-08:09 | 1127.77 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2.23 | 02-DEC-15:00 | 2941.05 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.40 | |||||
Maximum of Months | 1239.33 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 588.10 | 3516.98 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2099.43 | 13-JAN-05:00 |
February | 2010.83 | 01-FEB-10:09 | 1669.11 | 06-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2635.67 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 1427.23 | 21-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5275.45 | 19-MAR-06:57 |
April | 2010.83 | 03-APR-09:09 | 1313.06 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3729.28 | 15-APR-04:57 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 97.47 | 17-MAY-14:50 | 2069.29 | 03-MAY-03:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 565.30 | 25-JUN-17:44 | 1233.59 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 881.17 | 16-JUL-11:55 | 1210.22 | 03-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 310.60 | 02-AUG-16:00 | 1678.00 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 1075.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 327.47 | 10-SEP-14:34 | 1364.89 | 22-SEP-02:00 |
October | 2010.83 | 02-OCT-09:09 | 1557.84 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 11-OCT-14:00 | 3059.18 | 29-OCT-09:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3238.80 | 01-NOV-04:10 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4536.49 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1210.22 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 881.17 | 5275.45 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1352.99 | 13-JAN-05:00 |
February | 1295.83 | 01-FEB-10:09 | 1073.38 | 06-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1688.52 | 23-FEB-24:00 |
March | 1295.83 | 01-MAR-10:09 | 930.94 | 21-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3517.01 | 19-MAR-06:51 |
April | 1295.83 | 03-APR-09:09 | 865.01 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 2486.22 | 15-APR-05:00 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 64.98 | 17-MAY-14:50 | 1420.75 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 366.93 | 25-JUN-17:43 | 912.25 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 613.08 | 16-JUL-12:00 | 875.52 | 03-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 223.53 | 06-AUG-11:55 | 1128.62 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 800.79 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 222.32 | 10-SEP-12:55 | 896.21 | 22-SEP-02:00 |
October | 1295.83 | 02-OCT-09:09 | 1009.46 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 29.94 | 11-OCT-14:00 | 1979.69 | 29-OCT-09:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2159.22 | 01-NOV-04:06 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3002.11 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 875.52 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 613.08 | 3517.01 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.79 | 02-JAN-10:09 | 1750.00 | 02-JAN-16:49 | 2276.32 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2469.18 | 13-JAN-05:10 |
February | 2010.79 | 01-FEB-10:09 | 1670.70 | 06-FEB-16:00 | 2276.32 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2956.23 | 05-FEB-22:58 |
March | 2010.79 | 01-MAR-10:09 | 1436.79 | 21-MAR-07:10 | 2276.32 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6552.44 | 19-MAR-07:00 |
April | 2010.79 | 03-APR-09:09 | 1319.18 | 03-APR-07:10 | 2276.32 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4548.89 | 15-APR-04:51 |
May | 2010.79 | 01-MAY-09:09 | 1075.02 | 01-MAY-07:10 | 2276.32 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2367.95 | 02-MAY-04:57 |
June | 2010.79 | 01-JUN-09:09 | 1075.02 | 01-JUN-07:10 | 2276.32 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 667.91 | 25-JUN-17:54 | 1497.37 | 08-JUN-23:00 |
July | 2010.79 | 03-JUL-09:09 | 1075.02 | 03-JUL-07:10 | 2276.32 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 16-JUL-11:55 | 1476.32 | 03-JUL-02:53 |
August | 2010.79 | 01-AUG-09:09 | 1075.02 | 01-AUG-07:10 | 2276.32 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.53 | 02-AUG-16:00 | 1816.32 | 27-AUG-17:55 |
September | 2010.79 | 01-SEP-09:09 | 1075.02 | 01-SEP-07:10 | 2276.32 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 424.44 | 10-SEP-14:50 | 1551.05 | 21-SEP-23:00 |
October | 2010.79 | 02-OCT-09:09 | 1566.88 | 30-OCT-07:10 | 2276.32 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 53.67 | 11-OCT-14:00 | 3358.28 | 29-OCT-19:00 |
November | 2010.79 | 01-NOV-09:09 | 1750.00 | 06-NOV-16:49 | 2276.32 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 23.63 | 05-NOV-15:00 | 3852.24 | 01-NOV-04:10 |
December | 2010.79 | 01-DEC-10:09 | 1750.00 | 01-DEC-16:30 | 2276.32 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 19.81 | 17-DEC-12:52 | 5400.17 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1476.32 | |||||
Maximum of Months | 2010.79 | 1750.00 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.11 | 6552.44 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.95 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1646.31 | 13-JAN-05:10 |
February | 1295.83 | 01-FEB-10:09 | 1076.17 | 06-FEB-16:00 | 1466.95 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1970.85 | 05-FEB-23:00 |
March | 1295.83 | 01-MAR-10:09 | 899.68 | 21-MAR-07:10 | 1466.95 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4382.12 | 19-MAR-06:57 |
April | 1295.83 | 03-APR-09:09 | 802.63 | 03-APR-07:10 | 1466.95 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3034.57 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.95 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1578.83 | 02-MAY-04:53 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.95 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 524.18 | 25-JUN-18:00 | 1016.58 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.95 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 721.67 | 16-JUL-11:55 | 1014.10 | 02-JUL-08:30 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.95 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 253.02 | 02-AUG-16:00 | 1255.13 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 692.79 | 01-SEP-07:10 | 1466.95 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 316.67 | 10-SEP-14:50 | 1039.29 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 997.67 | 30-OCT-07:10 | 1466.95 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2239.22 | 29-OCT-19:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.95 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2693.59 | 01-NOV-04:10 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.95 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5.51 | 02-DEC-15:00 | 3597.75 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1014.10 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 721.67 | 4382.12 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2010.83 | 02-JAN-10:09 | 1750.04 | 02-JAN-16:49 | 2276.35 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2469.48 | 13-JAN-05:07 |
February | 2010.83 | 01-FEB-10:09 | 1669.02 | 06-FEB-16:00 | 2276.35 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3059.45 | 23-FEB-24:00 |
March | 2010.83 | 01-MAR-10:09 | 1426.92 | 21-MAR-07:10 | 2276.35 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6573.00 | 19-MAR-07:00 |
April | 2010.83 | 03-APR-09:09 | 1312.64 | 03-APR-07:10 | 2276.35 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 4557.09 | 15-APR-04:51 |
May | 2010.83 | 01-MAY-09:09 | 1075.05 | 01-MAY-07:10 | 2276.35 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 116.93 | 17-MAY-14:50 | 2368.13 | 02-MAY-05:00 |
June | 2010.83 | 01-JUN-09:09 | 1075.05 | 01-JUN-07:10 | 2276.35 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 731.57 | 25-JUN-17:54 | 1499.02 | 08-JUN-23:00 |
July | 2010.83 | 03-JUL-09:09 | 1075.05 | 03-JUL-07:10 | 2276.35 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.50 | 16-JUL-11:55 | 1483.53 | 03-JUL-02:53 |
August | 2010.83 | 01-AUG-09:09 | 1075.05 | 01-AUG-07:10 | 2276.35 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 379.53 | 02-AUG-16:00 | 2092.94 | 27-AUG-17:55 |
September | 2010.83 | 01-SEP-09:09 | 1075.05 | 01-SEP-07:10 | 2276.35 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 397.13 | 10-SEP-15:00 | 1579.84 | 21-SEP-23:00 |
October | 2010.83 | 02-OCT-09:09 | 1557.65 | 30-OCT-07:10 | 2276.35 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 40.87 | 11-OCT-14:00 | 3358.31 | 29-OCT-19:00 |
November | 2010.83 | 01-NOV-09:09 | 1750.04 | 06-NOV-16:49 | 2276.35 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 4040.14 | 01-NOV-04:10 |
December | 2010.83 | 01-DEC-10:09 | 1750.04 | 01-DEC-16:30 | 2276.35 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5421.96 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.53 | |||||
Maximum of Months | 2010.83 | 1750.04 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 1081.50 | 6573.00 |
Report: PeakSpaceGainsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 1295.83 | 02-JAN-10:09 | 1127.77 | 02-JAN-16:49 | 1466.94 | 02-JAN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 1646.34 | 13-JAN-05:06 |
February | 1295.83 | 01-FEB-10:09 | 1073.33 | 06-FEB-16:00 | 1466.94 | 01-FEB-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 1978.71 | 05-FEB-22:54 |
March | 1295.83 | 01-MAR-10:09 | 930.74 | 21-MAR-07:10 | 1466.94 | 01-MAR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 4382.03 | 19-MAR-06:56 |
April | 1295.83 | 03-APR-09:09 | 864.75 | 03-APR-07:10 | 1466.94 | 03-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3040.60 | 15-APR-04:51 |
May | 1295.83 | 01-MAY-09:09 | 692.79 | 01-MAY-07:10 | 1466.94 | 01-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 77.95 | 17-MAY-14:50 | 1612.65 | 03-MAY-03:00 |
June | 1295.83 | 01-JUN-09:09 | 692.79 | 01-JUN-07:10 | 1466.94 | 01-JUN-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 430.80 | 25-JUN-17:54 | 1118.41 | 08-JUN-23:00 |
July | 1295.83 | 03-JUL-09:09 | 692.79 | 03-JUL-07:10 | 1466.94 | 03-JUL-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 735.39 | 16-JUL-11:55 | 1072.79 | 03-JUL-02:53 |
August | 1295.83 | 01-AUG-09:09 | 692.79 | 01-AUG-07:10 | 1466.94 | 01-AUG-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 288.85 | 06-AUG-12:00 | 1400.04 | 27-AUG-17:55 |
September | 1295.83 | 01-SEP-09:09 | 801.16 | 25-SEP-07:10 | 1466.94 | 01-SEP-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 275.32 | 10-SEP-14:43 | 1038.50 | 21-SEP-23:00 |
October | 1295.83 | 02-OCT-09:09 | 1009.34 | 30-OCT-07:10 | 1466.94 | 02-OCT-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 35.78 | 11-OCT-14:00 | 2239.11 | 29-OCT-19:00 |
November | 1295.83 | 01-NOV-09:09 | 1127.77 | 06-NOV-16:49 | 1466.94 | 01-NOV-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 2693.58 | 01-NOV-04:07 |
December | 1295.83 | 01-DEC-10:09 | 1127.77 | 01-DEC-16:30 | 1466.94 | 01-DEC-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3615.54 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 1295.83 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1038.50 | |||||
Maximum of Months | 1295.83 | 1127.77 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 735.39 | 4382.03 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 232.27 | 02-JAN-10:09 | 405.10 | 02-JAN-08:09 | 1948.61 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 232.27 | 01-FEB-10:09 | 405.10 | 01-FEB-08:09 | 3897.21 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 232.27 | 01-MAR-10:09 | 405.10 | 01-MAR-08:09 | 7794.42 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 232.27 | 03-APR-09:09 | 405.10 | 03-APR-07:10 | 7794.42 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 232.27 | 01-MAY-09:09 | 405.10 | 01-MAY-07:10 | 3897.21 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 232.27 | 01-JUN-09:09 | 405.10 | 01-JUN-07:10 | 5845.82 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 232.27 | 03-JUL-09:09 | 405.10 | 03-JUL-07:10 | 7794.42 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 232.27 | 01-AUG-09:09 | 405.10 | 01-AUG-07:10 | 7794.42 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 232.27 | 01-SEP-09:09 | 405.10 | 01-SEP-07:10 | 3897.21 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 232.27 | 02-OCT-09:09 | 405.10 | 02-OCT-07:10 | 5845.82 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 232.27 | 01-NOV-09:09 | 405.10 | 01-NOV-07:10 | 5845.82 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 232.27 | 01-DEC-10:09 | 405.10 | 01-DEC-08:09 | 7794.42 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 232.27 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 232.27 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 5027.92 | 02-JAN-10:09 | 4375.82 | 02-JAN-08:09 | 94908.13 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 5027.92 | 01-FEB-10:09 | 4375.82 | 01-FEB-08:09 | 189816.26 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 5027.92 | 01-MAR-10:09 | 4375.82 | 01-MAR-08:09 | 379632.52 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5027.92 | 03-APR-09:09 | 4375.82 | 03-APR-07:10 | 379632.52 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 5027.92 | 01-MAY-09:09 | 4375.82 | 01-MAY-07:10 | 189816.26 | 31-MAY-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5027.92 | 01-JUN-09:09 | 4375.82 | 01-JUN-07:10 | 284724.39 | 30-JUN-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 5027.92 | 03-JUL-09:09 | 4375.82 | 03-JUL-07:10 | 379632.52 | 31-JUL-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 5027.92 | 01-AUG-09:09 | 4375.82 | 01-AUG-07:10 | 379632.52 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 5027.92 | 01-SEP-09:09 | 4375.82 | 01-SEP-07:10 | 189816.26 | 30-SEP-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 5027.92 | 02-OCT-09:09 | 4375.82 | 02-OCT-07:10 | 284724.39 | 31-OCT-23:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5027.92 | 01-NOV-09:09 | 4375.82 | 01-NOV-07:10 | 284724.39 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 5027.92 | 01-DEC-10:09 | 4375.82 | 01-DEC-08:09 | 379632.52 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 5027.92 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 5027.92 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakSpaceGainsMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 2110.34 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2578.01 | 05-FEB-22:52 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5397.69 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 3628.99 | 15-APR-04:53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.07 | 17-MAY-14:40 | 2110.31 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 518.21 | 25-JUN-18:00 | 1145.79 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.58 | 16-JUL-12:00 | 1113.92 | 03-JUL-03:04 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.13 | 06-AUG-12:00 | 1310.05 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 320.10 | 10-SEP-15:00 | 1330.97 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.30 | 11-OCT-14:00 | 3153.55 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3109.20 | 01-NOV-03:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 4393.36 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1113.92 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.58 | 5397.69 |
Report: PeakSpaceGainsMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3652.81 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4291.01 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9179.42 | 19-MAR-06:51 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6212.62 | 15-APR-04:59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.41 | 17-MAY-14:40 | 3601.36 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 952.38 | 25-JUN-18:00 | 2015.64 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.42 | 16-JUL-12:00 | 1944.71 | 03-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 481.57 | 06-AUG-12:00 | 2251.97 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 597.43 | 10-SEP-15:00 | 2367.41 | 22-SEP-02:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.57 | 11-OCT-14:00 | 5334.04 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5192.13 | 01-NOV-03:55 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 7589.13 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1944.71 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1483.42 | 9179.42 |
Report: PeakSpaceGainsMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3552.97 | 13-JAN-05:00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4446.11 | 23-FEB-24:00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 9250.26 | 19-MAR-07:00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 6371.98 | 15-APR-04:51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.16 | 17-MAY-13:00 | 3545.75 | 03-MAY-03:00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 757.74 | 25-JUN-18:00 | 2232.23 | 08-JUN-23:00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1455.68 | 16-JUL-12:00 | 2178.25 | 03-JUL-02:53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 444.36 | 02-AUG-16:00 | 2921.43 | 27-AUG-17:55 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 449.46 | 10-SEP-14:30 | 2390.53 | 21-SEP-23:00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.91 | 11-OCT-14:00 | 5240.82 | 29-OCT-09:00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5184.25 | 01-NOV-04:00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 8183.66 | 21-DEC-22:52 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2178.25 | ||
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1455.68 | 9250.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 102044.53 | 02-JAN-04:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 100660.24 | 21-FEB-04:03 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 101159.93 | 13-MAR-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 101840.39 | 24-APR-03:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 103800.28 | 01-MAY-03:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 96534.67 | 09-JUN-04:03 | 0.00 | 6897.82 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 100435.07 | 03-JUL-03:02 | 0.00 | 4311.14 | 67287.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 95101.05 | 17-AUG-03:02 | 0.00 | 5173.36 | 80745.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 100359.85 | 25-SEP-03:02 | 0.00 | 3448.91 | 53830.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 105755.18 | 23-OCT-03:01 | 0.00 | 6897.82 | 107660.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 104613.50 | 27-NOV-04:01 | 0.00 | 6035.59 | 94202.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 103151.40 | 11-DEC-04:01 | 0.00 | 8622.27 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 95101.05 | 0.00 | 2586.68 | 40372.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 105755.18 | 0.00 | 8622.27 | 134575.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 82428.66 | 02-JAN-05:01 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 82328.27 | 27-FEB-05:01 | 0.00 | 10840.77 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 84098.77 | 13-MAR-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 85384.04 | 10-APR-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86237.31 | 01-MAY-03:01 | 0.00 | 5420.38 | 56400.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 84979.62 | 20-JUN-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 86500.73 | 31-JUL-03:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 85243.40 | 11-AUG-05:03 | 9673.43 | 9292.09 | 48342.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 85186.60 | 05-SEP-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 85333.89 | 02-OCT-03:02 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 86829.00 | 13-NOV-04:01 | 0.00 | 6194.72 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 86738.71 | 04-DEC-04:02 | 0.00 | 3871.70 | 40285.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 82328.27 | 0.00 | 3097.36 | 32228.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 86829.00 | 9673.43 | 10840.77 | 64457.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 69814.35 | 27-JAN-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 64037.97 | 28-FEB-06:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 72349.10 | 14-MAR-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 72945.96 | 14-APR-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 75133.71 | 18-MAY-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 76841.69 | 22-JUN-04:03 | 0.00 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 78988.73 | 10-JUL-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79373.68 | 28-AUG-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 78697.99 | 05-SEP-03:02 | 0.00 | 3097.36 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 74861.28 | 06-OCT-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 74205.54 | 09-NOV-06:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 28372.73 | 15-DEC-16:20 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 28372.73 | 0.00 | 3097.36 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 79373.68 | 15316.26 | 13937.56 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 28584.63 | 20-JAN-16:30 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 23494.44 | 23-FEB-17:00 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 68153.35 | 15-MAR-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 69632.10 | 21-APR-05:02 | 8061.19 | 7743.41 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 72713.38 | 18-MAY-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 77981.46 | 26-JUN-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 80838.13 | 24-JUL-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 79352.22 | 21-AUG-03:02 | 0.00 | 4646.04 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 77954.98 | 11-SEP-03:02 | 0.00 | 3871.70 | 40285.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 57900.55 | 11-OCT-05:03 | 6448.95 | 6194.72 | 32228.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 32315.07 | 08-NOV-16:20 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 20074.69 | 15-DEC-16:20 | 15316.26 | 13937.56 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 20074.69 | 0.00 | 3871.70 | 18128.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80838.13 | 15316.26 | 13937.56 | 48342.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3214.06 | 20-JAN-15:00 | 2010.79 | 1181.59 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.36 |
February | 3847.37 | 27-FEB-15:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.36 |
March | 6158.97 | 14-MAR-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.23 |
April | 7056.76 | 20-APR-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 |
May | 8185.75 | 17-MAY-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 34.84 | 0.00 |
June | 14612.55 | 25-JUN-17:51 | 0.00 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 228.13 | 0.00 |
July | 15734.57 | 16-JUL-14:12 | 607.30 | 358.36 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 291.73 | 0.00 |
August | 12930.67 | 21-AUG-05:03 | 1214.60 | 1166.71 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.73 |
September | 12221.31 | 11-SEP-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.44 |
October | 6609.21 | 10-OCT-14:40 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 4.76 | 0.00 |
November | 5169.11 | 09-NOV-13:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4.38 |
December | 4621.72 | 04-DEC-14:10 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.88 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3214.06 | 0.00 | 358.36 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15734.57 | 2010.79 | 1181.59 | 6070.18 | 0.00 | 0.00 | 0.00 | 0.00 | 291.73 | 149.36 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6564.37 | 20-JAN-09:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 |
February | 8689.32 | 27-FEB-09:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.85 |
March | 11484.95 | 12-MAR-08:43 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 291.74 |
April | 11088.98 | 21-APR-08:70 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 63.34 |
May | 11234.22 | 16-MAY-08:70 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.89 |
June | 19749.63 | 11-JUN-08:62 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.41 |
July | 19249.68 | 16-JUL-08:51 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 88.50 | 0.00 |
August | 18929.52 | 20-AUG-09:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.07 |
September | 16511.82 | 04-SEP-09:02 | 326.14 | 192.45 | 2444.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.19 |
October | 15185.35 | 01-OCT-09:13 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 338.65 |
November | 8463.98 | 06-NOV-08:50 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.05 |
December | 5451.20 | 18-DEC-09:15 | 2478.65 | 1385.57 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5451.20 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19749.63 | 2478.65 | 1385.57 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 88.50 | 338.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21369.53 | 22-JAN-12:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 552.05 |
February | 21861.37 | 26-FEB-12:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.39 |
March | 21704.05 | 12-MAR-12:02 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.06 |
April | 13832.65 | 19-APR-13:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.75 |
May | 12326.97 | 07-MAY-13:32 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.38 |
June | 15667.18 | 25-JUN-14:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 63.32 | 0.00 |
July | 21422.65 | 16-JUL-14:12 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 294.29 | 0.00 |
August | 21650.68 | 20-AUG-14:21 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 24.45 | 0.00 |
September | 22358.44 | 10-SEP-12:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 87.84 | 0.00 |
October | 24512.40 | 08-OCT-12:41 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.26 |
November | 22627.16 | 05-NOV-13:32 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.60 |
December | 22039.42 | 03-DEC-13:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 310.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12326.97 | 506.09 | 298.64 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24512.40 | 2010.83 | 1075.05 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 294.29 | 552.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9078.60 | 23-JAN-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.85 |
February | 14759.94 | 26-FEB-16:42 | 260.91 | 153.96 | 1955.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 279.03 |
March | 24052.01 | 12-MAR-16:02 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.54 |
April | 22302.28 | 08-APR-17:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.53 |
May | 15010.69 | 07-MAY-15:32 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 119.93 |
June | 27899.12 | 11-JUN-17:21 | 0.00 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 |
July | 25881.19 | 02-JUL-16:41 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.07 |
August | 26278.52 | 20-AUG-15:41 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.51 |
September | 24908.59 | 10-SEP-16:41 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 | 0.00 |
October | 25524.86 | 08-OCT-14:41 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.17 |
November | 17153.59 | 05-NOV-15:32 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 89.19 |
December | 16535.83 | 03-DEC-15:22 | 326.14 | 192.45 | 2444.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 9078.60 | 0.00 | 153.96 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27899.12 | 1239.33 | 692.79 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 | 279.03 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2508.45 | 20-JAN-15:50 | 1923.11 | 1375.45 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.42 |
February | 2436.11 | 27-FEB-14:50 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.41 |
March | 4409.63 | 14-MAR-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 |
April | 4691.14 | 20-APR-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.25 |
May | 7621.00 | 17-MAY-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 79.94 | 0.00 |
June | 14580.04 | 25-JUN-17:41 | 0.00 | 537.53 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 445.22 | 0.00 |
July | 14288.26 | 16-JUL-14:22 | 506.08 | 298.63 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 735.25 | 0.00 |
August | 10292.41 | 03-AUG-05:03 | 809.73 | 777.81 | 4046.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 |
September | 8464.73 | 11-SEP-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 123.65 | 0.00 |
October | 5008.50 | 11-OCT-14:00 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 44.92 | 0.00 |
November | 3007.04 | 09-NOV-13:50 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.91 |
December | 2293.43 | 01-DEC-14:40 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 6.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2293.43 | 0.00 | 298.63 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 14580.04 | 2010.79 | 1375.45 | 6828.95 | 0.00 | 0.00 | 0.00 | 0.00 | 735.25 | 331.41 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4714.43 | 20-JAN-09:40 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 |
February | 6261.67 | 27-FEB-09:20 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.84 |
March | 9985.53 | 15-MAR-09:00 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.69 |
April | 10771.89 | 21-APR-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.69 |
May | 14207.12 | 28-MAY-09:23 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.99 |
June | 20289.18 | 25-JUN-10:22 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 130.98 | 0.00 |
July | 21582.66 | 09-JUL-09:21 | 456.59 | 269.43 | 3422.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44.94 |
August | 22289.43 | 20-AUG-08:51 | 521.82 | 307.92 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.12 |
September | 20779.21 | 04-SEP-09:22 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.51 |
October | 13314.56 | 01-OCT-09:02 | 260.91 | 153.96 | 1955.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 774.61 |
November | 6098.58 | 07-NOV-09:10 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.19 |
December | 2678.05 | 14-DEC-11:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2678.05 | 260.91 | 153.96 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22289.43 | 1239.33 | 692.79 | 3911.86 | 0.00 | 0.00 | 0.00 | 0.00 | 130.98 | 774.61 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21153.47 | 22-JAN-13:02 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1464.98 |
February | 21741.65 | 26-FEB-13:02 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 711.93 |
March | 21293.16 | 12-MAR-12:02 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.50 |
April | 13184.30 | 21-APR-13:10 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.83 |
May | 10965.97 | 16-MAY-13:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 52.38 | 0.00 |
June | 20578.38 | 25-JUN-16:21 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 326.25 | 0.00 |
July | 18955.54 | 30-JUL-13:13 | 404.87 | 238.91 | 3035.14 | 0.00 | 0.00 | 0.00 | 0.00 | 63.09 | 0.00 |
August | 21577.28 | 20-AUG-10:52 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 28.48 | 0.00 |
September | 23648.42 | 04-SEP-12:41 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.36 | 0.00 |
October | 24642.74 | 09-OCT-13:11 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.87 |
November | 24655.00 | 05-NOV-12:41 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 71.81 |
December | 21471.93 | 03-DEC-13:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 693.61 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 10965.97 | 404.87 | 238.91 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24655.00 | 2010.83 | 1075.05 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 326.25 | 1464.98 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7062.35 | 20-JAN-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.29 |
February | 7626.60 | 17-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.25 |
March | 16145.12 | 12-MAR-16:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.56 |
April | 15991.87 | 08-APR-17:04 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.90 |
May | 12712.11 | 31-MAY-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 40.60 | 0.00 |
June | 25288.30 | 25-JUN-16:21 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 111.22 | 0.00 |
July | 23026.57 | 02-JUL-16:41 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.03 |
August | 24418.80 | 13-AUG-17:11 | 0.00 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 136.31 |
September | 24857.47 | 10-SEP-15:51 | 587.05 | 346.41 | 4400.81 | 0.00 | 0.00 | 0.00 | 0.00 | 51.24 | 0.00 |
October | 21577.61 | 09-OCT-16:31 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.80 |
November | 8676.14 | 07-NOV-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.60 |
December | 5515.44 | 01-DEC-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5515.44 | 0.00 | 230.94 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 25288.30 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 111.22 | 500.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 2491.65 | 20-JAN-15:20 | 1923.11 | 1251.43 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.98 |
February | 2055.18 | 17-FEB-14:00 | 3846.22 | 2150.05 | 4552.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.87 |
March | 4303.75 | 14-MAR-15:00 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.40 |
April | 5134.87 | 20-APR-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.08 |
May | 8037.92 | 17-MAY-13:30 | 2010.79 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 97.03 | 0.00 |
June | 16576.27 | 25-JUN-17:51 | 0.00 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 596.75 | 0.00 |
July | 16611.40 | 16-JUL-14:22 | 506.08 | 298.63 | 3793.86 | 0.00 | 0.00 | 0.00 | 0.00 | 886.04 | 0.00 |
August | 10381.57 | 20-AUG-15:41 | 708.51 | 418.08 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 53.62 | 0.00 |
September | 9009.59 | 11-SEP-14:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 150.00 | 0.00 |
October | 5150.34 | 11-OCT-14:50 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 45.22 | 0.00 |
November | 2612.95 | 07-NOV-15:10 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.36 |
December | 1964.56 | 14-DEC-13:30 | 1923.11 | 1075.02 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.24 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 1964.56 | 0.00 | 298.63 | 2276.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16611.40 | 3846.22 | 2150.05 | 5311.41 | 0.00 | 0.00 | 0.00 | 0.00 | 886.04 | 49.24 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3148.61 | 20-JAN-10:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.16 |
February | 3687.83 | 27-FEB-09:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.63 |
March | 9092.30 | 15-MAR-09:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.96 |
April | 10268.63 | 21-APR-09:10 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.61 |
May | 11065.74 | 16-MAY-08:50 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 |
June | 20762.16 | 11-JUN-09:12 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 322.41 |
July | 20839.49 | 02-JUL-09:52 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.74 |
August | 20495.25 | 20-AUG-09:02 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 57.26 |
September | 20745.67 | 04-SEP-09:32 | 391.37 | 230.94 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 68.13 |
October | 7402.67 | 11-OCT-09:40 | 1295.83 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.37 |
November | 4233.96 | 07-NOV-09:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.11 |
December | 2334.24 | 14-DEC-13:30 | 1239.33 | 692.79 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 36.14 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2334.24 | 391.37 | 230.94 | 1466.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.61 | |
Maximum of Months | 20839.49 | 1295.83 | 692.79 | 2933.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19099.49 | 20-JAN-13:40 | 1923.15 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.12 |
February | 22806.60 | 26-FEB-13:22 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 897.65 |
March | 22780.70 | 12-MAR-12:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1260.34 |
April | 13628.65 | 21-APR-13:20 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.57 |
May | 11454.99 | 16-MAY-13:30 | 2010.83 | 1075.05 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 63.84 | 0.00 |
June | 21545.55 | 25-JUN-15:51 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 340.09 | 0.00 |
July | 22177.69 | 02-JUL-16:31 | 1012.19 | 597.27 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 182.15 | 0.00 |
August | 23251.04 | 20-AUG-13:42 | 607.31 | 358.36 | 4552.71 | 0.00 | 0.00 | 0.00 | 0.00 | 38.96 | 0.00 |
September | 26152.21 | 04-SEP-12:51 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 14.55 | 0.00 |
October | 26600.63 | 09-OCT-13:41 | 809.75 | 477.82 | 6070.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.26 |
November | 25547.69 | 05-NOV-14:31 | 708.53 | 418.09 | 5311.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.82 |
December | 22686.39 | 17-DEC-14:42 | 506.09 | 298.64 | 3793.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 523.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11454.99 | 506.09 | 298.64 | 2276.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26600.63 | 2010.83 | 1075.05 | 7587.84 | 0.00 | 0.00 | 0.00 | 0.00 | 340.09 | 1260.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6800.76 | 20-JAN-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.91 |
February | 7262.19 | 17-FEB-16:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.15 |
March | 14575.38 | 12-MAR-16:42 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.10 |
April | 16059.96 | 08-APR-17:04 | 521.82 | 307.92 | 3911.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.45 |
May | 13271.39 | 31-MAY-16:00 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 0.00 |
June | 27218.80 | 11-JUN-16:31 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 51.49 |
July | 26728.16 | 02-JUL-16:31 | 652.28 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.61 |
August | 24845.40 | 13-AUG-17:21 | 0.00 | 384.90 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 133.57 |
September | 25085.52 | 17-SEP-16:31 | 456.59 | 269.43 | 3422.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.12 |
October | 23593.12 | 09-OCT-16:22 | 391.37 | 230.94 | 2933.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 181.55 |
November | 8362.05 | 07-NOV-15:40 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.13 |
December | 5103.84 | 01-DEC-15:30 | 1239.33 | 692.79 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5103.84 | 0.00 | 230.94 | 1466.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27218.80 | 1239.33 | 692.79 | 4889.79 | 0.00 | 0.00 | 0.00 | 0.00 | 49.00 | 624.45 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5048.42 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.01 |
February | 3397.18 | 24-FEB-06:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 546.77 |
March | 5933.66 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 |
April | 5105.96 | 21-APR-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 129.25 |
May | 6196.92 | 30-MAY-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 182.43 |
June | 9497.48 | 26-JUN-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.28 | 0.00 |
July | 11107.74 | 05-JUL-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.56 |
August | 12415.85 | 21-AUG-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.97 |
September | 11597.41 | 05-SEP-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.14 |
October | 8776.86 | 10-OCT-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.05 |
November | 4850.83 | 07-NOV-16:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 30.43 |
December | 4401.74 | 21-DEC-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1929.81 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 3397.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 12415.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.28 | 1929.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7127.04 | 14-JAN-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1153.29 |
February | 7586.54 | 06-FEB-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2394.29 |
March | 9472.37 | 19-MAR-06:33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8383.74 |
April | 7398.24 | 15-APR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5486.28 |
May | 4576.65 | 18-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.76 |
June | 7174.55 | 26-JUN-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 288.75 | 0.00 |
July | 7668.67 | 17-JUL-16:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.99 | 0.00 |
August | 7189.66 | 21-AUG-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 76.39 | 0.00 |
September | 6914.55 | 11-SEP-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.27 | 0.00 |
October | 8498.96 | 30-OCT-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2133.25 |
November | 7256.96 | 30-NOV-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2895.62 |
December | 9213.30 | 20-DEC-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 4223.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 4576.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 9472.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.99 | 8383.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY [] | ZONE LIGHTS TOTAL HEATING ENERGY [] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4200.79 | 20-JAN-15:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 79.20 |
February | 4659.63 | 18-FEB-13:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.57 |
March | 11200.45 | 14-MAR-14:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.08 |
April | 11640.01 | 21-APR-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.98 |
May | 15738.17 | 31-MAY-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.35 | 0.00 |
June | 22207.99 | 26-JUN-13:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.38 | 0.00 |
July | 19200.75 | 18-JUL-14:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.30 | 0.00 |
August | 21054.30 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.65 | 0.00 |
September | 15167.40 | 12-SEP-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.70 | 0.00 |
October | 10839.30 | 11-OCT-14:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.78 | 0.00 |
November | 5955.94 | 09-NOV-13:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.35 |
December | 2500.91 | 03-DEC-14:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 653.74 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 2500.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22207.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.30 | 653.74 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2321.34 | 23-JAN-16:40 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 4308.44 | 21-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 7146.46 | 31-MAR-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 8156.24 | 07-APR-17:50 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3483.70 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5355.91 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 7256.72 | 31-JUL-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 8426.54 | 05-AUG-18:40 | 0.00 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3343.14 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4633.79 | 09-OCT-16:43 | 70.15 | 135.04 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 6236.23 | 07-NOV-16:10 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 8050.09 | 03-DEC-16:15 | 23.38 | 45.01 | 15588.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2321.34 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 8426.54 | 222.14 | 405.10 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2094.04 | 24-JAN-16:40 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3972.62 | 23-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6589.51 | 31-MAR-23:40 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7631.89 | 07-APR-17:50 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3275.85 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5228.79 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6838.99 | 31-JUL-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7865.34 | 05-AUG-18:11 | 0.00 | 202.56 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 3005.48 | 30-SEP-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4112.72 | 09-OCT-16:43 | 70.15 | 135.04 | 23383.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5811.11 | 07-NOV-16:20 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7314.91 | 15-DEC-16:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2094.04 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7865.34 | 222.14 | 405.10 | 70149.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 2083.90 | 20-JAN-16:40 | 222.14 | 405.10 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 3930.48 | 17-FEB-17:00 | 222.14 | 405.10 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 6392.59 | 31-MAR-23:20 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 7720.46 | 07-APR-17:40 | 23.38 | 135.03 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 3231.12 | 31-MAY-24:00 | 0.00 | 22.51 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 5242.58 | 30-JUN-24:00 | 0.00 | 45.01 | 11691.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 6736.71 | 31-JUL-24:00 | 0.00 | 22.51 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 7981.74 | 13-AUG-18:50 | 0.00 | 180.06 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 2782.74 | 10-SEP-17:40 | 0.00 | 45.01 | 3897.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 4077.71 | 08-OCT-16:50 | 58.46 | 112.53 | 19486.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 5805.72 | 07-NOV-16:20 | 222.14 | 405.10 | 5845.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 7250.23 | 14-DEC-16:00 | 222.14 | 405.10 | 7794.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 2083.90 | 0.00 | 22.51 | 1948.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 7981.74 | 222.14 | 405.10 | 62355.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [] | |
January | 91521.53 | 24-JAN-17:00 | 4808.68 | 4375.82 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 183001.05 | 27-FEB-17:00 | 4808.68 | 4375.82 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357921.59 | 31-MAR-24:00 | 0.00 | 243.11 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 365444.44 | 21-APR-07:15 | 9617.36 | 8751.64 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 175659.55 | 31-MAY-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 267770.50 | 30-JUN-24:00 | 0.00 | 486.22 | 569448.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 355872.50 | 31-JUL-23:15 | 0.00 | 486.22 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 365833.16 | 17-AUG-07:10 | 9617.36 | 8751.64 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 176081.66 | 30-SEP-24:00 | 0.00 | 243.11 | 189816.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 265953.28 | 31-OCT-24:00 | 0.00 | 243.11 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 276363.22 | 07-NOV-17:00 | 4808.68 | 4375.82 | 284724.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 366701.78 | 18-DEC-17:00 | 4808.68 | 4375.82 | 379632.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||
Minimum of Months | 91521.53 | 0.00 | 243.11 | 94908.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 366701.78 | 9617.36 | 8751.64 | 759265.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.166544E+13 | 1103950.85 | 23-JAN-16:10 | 0.371409E+12 | 1106535.67 | 05-JAN-07:19 |
February | 0.190117E+13 | 1176340.76 | 17-FEB-16:19 | 0.402140E+12 | 1246735.32 | 06-FEB-07:19 |
March | 0.262805E+13 | 1582111.63 | 13-MAR-15:50 | 0.286087E+12 | 828523.52 | 20-MAR-05:19 |
April | 0.294109E+13 | 1644056.14 | 07-APR-15:30 | 0.187552E+12 | 860713.63 | 17-APR-06:19 |
May | 0.182716E+13 | 1316737.84 | 31-MAY-15:00 | 0.719773E+11 | 374621.53 | 01-MAY-04:10 |
June | 0.250092E+13 | 1617499.28 | 26-JUN-15:09 | 0.596719E+11 | 78595.70 | 01-JUN-11:00 |
July | 0.297276E+13 | 1808119.75 | 24-JUL-15:20 | 0.561649E+11 | 76421.72 | 03-JUL-11:30 |
August | 0.350569E+13 | 1989326.38 | 16-AUG-15:09 | 0.592250E+11 | 75235.64 | 01-AUG-11:30 |
September | 0.190576E+13 | 1414245.60 | 12-SEP-15:00 | 0.612751E+11 | 365896.99 | 22-SEP-06:10 |
October | 0.218375E+13 | 1441684.81 | 11-OCT-15:00 | 0.203311E+12 | 948973.63 | 30-OCT-06:30 |
November | 0.250240E+13 | 1479620.51 | 06-NOV-16:49 | 0.298642E+12 | 933733.70 | 30-NOV-07:10 |
December | 0.299593E+13 | 1585822.88 | 04-DEC-16:30 | 0.565199E+12 | 1489319.31 | 23-DEC-07:19 |
Annual Sum or Average | 0.295301E+14 | 0.262265E+13 | ||||
Minimum of Months | 0.166544E+13 | 1103950.85 | 0.561649E+11 | 75235.64 | ||
Maximum of Months | 0.350569E+13 | 1989326.38 | 0.565199E+12 | 1489319.31 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [J] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [J] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [J] | HUMIDIFIER:ELECTRICITY [J] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 0.232111E+12 | 0.484518E+11 | 0.811612E+12 | 0.162550E+12 | 0.201297E+12 | 0.189233E+11 | 0.00 | 0.115257E+12 | 0.183061E+11 | 0.569313E+11 | 0.00 | 0.00 | 0.00 |
February | 0.208877E+12 | 0.400445E+11 | 0.102011E+13 | 0.146826E+12 | 0.183536E+12 | 0.186572E+11 | 0.00 | 0.171949E+12 | 0.241530E+11 | 0.870184E+11 | 0.00 | 0.00 | 0.00 |
March | 0.246239E+12 | 0.390867E+11 | 0.146267E+13 | 0.162740E+12 | 0.216043E+12 | 0.241726E+11 | 0.00 | 0.281009E+12 | 0.643328E+11 | 0.131759E+12 | 0.00 | 0.00 | 0.00 |
April | 0.219174E+12 | 0.325081E+11 | 0.170311E+13 | 0.157288E+12 | 0.204044E+12 | 0.243086E+11 | 0.00 | 0.339878E+12 | 0.835690E+11 | 0.177213E+12 | 0.00 | 0.00 | 0.00 |
May | 0.235720E+12 | 0.294809E+11 | 0.820521E+12 | 0.162644E+12 | 0.236758E+12 | 0.399133E+11 | 0.00 | 0.174584E+12 | 0.733393E+11 | 0.541970E+11 | 0.00 | 0.00 | 0.00 |
June | 0.234232E+12 | 0.265890E+11 | 0.110677E+13 | 0.157466E+12 | 0.298205E+12 | 0.768595E+11 | 0.00 | 0.406380E+12 | 0.129346E+12 | 0.650703E+11 | 0.00 | 0.00 | 0.00 |
July | 0.219494E+12 | 0.280921E+11 | 0.143888E+13 | 0.162465E+12 | 0.293960E+12 | 0.820491E+11 | 0.00 | 0.524748E+12 | 0.137982E+12 | 0.850899E+11 | 0.00 | 0.00 | 0.00 |
August | 0.244935E+12 | 0.315494E+11 | 0.177780E+13 | 0.162739E+12 | 0.303657E+12 | 0.864155E+11 | 0.00 | 0.598366E+12 | 0.136104E+12 | 0.164131E+12 | 0.00 | 0.00 | 0.00 |
September | 0.219486E+12 | 0.355095E+11 | 0.784732E+12 | 0.157286E+12 | 0.254747E+12 | 0.589089E+11 | 0.00 | 0.242147E+12 | 0.104164E+12 | 0.487827E+11 | 0.00 | 0.00 | 0.00 |
October | 0.229464E+12 | 0.421783E+11 | 0.112899E+13 | 0.162550E+12 | 0.216566E+12 | 0.279965E+11 | 0.00 | 0.221506E+12 | 0.591880E+11 | 0.953102E+11 | 0.00 | 0.00 | 0.00 |
November | 0.229077E+12 | 0.455065E+11 | 0.140306E+13 | 0.157362E+12 | 0.199725E+12 | 0.207543E+11 | 0.00 | 0.265661E+12 | 0.519672E+11 | 0.129286E+12 | 0.00 | 0.00 | 0.00 |
December | 0.225059E+12 | 0.497607E+11 | 0.175516E+13 | 0.162466E+12 | 0.202354E+12 | 0.188117E+11 | 0.00 | 0.334253E+12 | 0.593702E+11 | 0.188692E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.274387E+13 | 0.448758E+12 | 0.152134E+14 | 0.191438E+13 | 0.281089E+13 | 0.497771E+12 | 0.00 | 0.367574E+13 | 0.941821E+12 | 0.128348E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.208877E+12 | 0.265890E+11 | 0.784732E+12 | 0.146826E+12 | 0.183536E+12 | 0.186572E+11 | 0.00 | 0.115257E+12 | 0.183061E+11 | 0.487827E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.246239E+12 | 0.497607E+11 | 0.177780E+13 | 0.162740E+12 | 0.303657E+12 | 0.864155E+11 | 0.00 | 0.598366E+12 | 0.137982E+12 | 0.188692E+12 | 0.00 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [J] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.304894E+12 | 0.00 | 0.665148E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.341222E+12 | 0.00 | 0.609180E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.216264E+12 | 0.00 | 0.698227E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.125131E+12 | 0.00 | 0.624208E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.861271E+10 | 0.00 | 0.633646E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.596719E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.561649E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.592250E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.578512E+10 | 0.00 | 0.554900E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.144039E+12 | 0.00 | 0.592717E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.238099E+12 | 0.00 | 0.605434E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.501756E+12 | 0.00 | 0.634426E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188580E+13 | 0.00 | 0.736850E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.554900E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.501756E+12 | 0.00 | 0.698227E+11 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | EXTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY {Maximum} [W] | PUMPS:ELECTRICITY {TIMESTAMP} | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 261074.09 | 02-JAN-16:49 | 37611.08 | 01-JAN-06:10 | 439129.89 | 02-JAN-08:09 | 117198.54 | 31-JAN-08:20 | 146949.67 | 24-JAN-16:30 | 49088.64 | 20-JAN-14:09 | 0.00 | 01-JAN-00:10 |
February | 257875.09 | 06-FEB-16:00 | 37611.08 | 01-FEB-06:10 | 557421.28 | 01-FEB-08:09 | 117198.69 | 08-FEB-08:20 | 143477.90 | 23-FEB-16:10 | 32775.69 | 18-FEB-13:30 | 0.00 | 01-FEB-00:10 |
March | 248323.97 | 21-MAR-07:10 | 37611.08 | 01-MAR-06:10 | 675712.68 | 01-MAR-08:09 | 117197.46 | 21-MAR-07:19 | 192793.32 | 15-MAR-15:00 | 50534.84 | 13-MAR-14:50 | 0.00 | 01-MAR-00:10 |
April | 243579.11 | 03-APR-07:10 | 37611.08 | 01-APR-05:10 | 794004.08 | 03-APR-07:10 | 117194.76 | 03-APR-07:19 | 187751.04 | 21-APR-13:39 | 48766.43 | 20-APR-12:50 | 0.00 | 01-APR-00:10 |
May | 234435.00 | 01-MAY-07:10 | 37611.08 | 01-MAY-18:49 | 439129.89 | 01-MAY-07:10 | 117189.56 | 01-MAY-07:19 | 222663.79 | 18-MAY-14:30 | 52802.90 | 31-MAY-12:00 | 0.00 | 01-MAY-00:10 |
June | 234435.00 | 01-JUN-07:10 | 37611.08 | 01-JUN-19:19 | 557421.28 | 01-JUN-07:10 | 117189.56 | 01-JUN-07:19 | 289801.49 | 30-JUN-15:09 | 63438.00 | 26-JUN-13:39 | 0.00 | 01-JUN-00:10 |
July | 234435.00 | 03-JUL-07:10 | 37611.08 | 01-JUL-19:30 | 675712.68 | 03-JUL-07:10 | 117189.56 | 03-JUL-07:19 | 293477.65 | 24-JUL-15:20 | 64100.48 | 18-JUL-15:09 | 0.00 | 01-JUL-00:10 |
August | 234435.00 | 01-AUG-07:10 | 37611.08 | 01-AUG-19:10 | 794004.08 | 01-AUG-07:10 | 117189.56 | 01-AUG-07:19 | 286211.36 | 11-AUG-15:09 | 61134.63 | 02-AUG-15:39 | 0.00 | 01-AUG-00:10 |
September | 235729.55 | 25-SEP-07:10 | 37611.08 | 01-SEP-05:10 | 439129.89 | 01-SEP-07:10 | 117190.30 | 25-SEP-07:19 | 266430.00 | 12-SEP-15:00 | 61822.95 | 12-SEP-15:50 | 0.00 | 01-SEP-00:10 |
October | 253578.45 | 30-OCT-07:10 | 37611.08 | 01-OCT-05:10 | 557421.28 | 02-OCT-07:10 | 117200.46 | 30-OCT-07:19 | 189182.93 | 10-OCT-15:00 | 51076.37 | 10-OCT-13:30 | 0.00 | 01-OCT-00:10 |
November | 261074.09 | 06-NOV-16:49 | 37611.08 | 01-NOV-05:10 | 675712.68 | 01-NOV-07:10 | 117198.94 | 01-NOV-07:19 | 161487.82 | 08-NOV-15:39 | 49227.76 | 06-NOV-14:20 | 0.00 | 01-NOV-00:10 |
December | 261074.09 | 01-DEC-16:30 | 37611.08 | 01-DEC-06:10 | 794004.08 | 01-DEC-08:09 | 117200.65 | 21-DEC-08:20 | 133724.78 | 04-DEC-15:20 | 48907.20 | 01-DEC-13:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | ||||||||||||||
Minimum of Months | 234435.00 | 37611.08 | 439129.89 | 117189.56 | 133724.78 | 32775.69 | 0.00 | |||||||
Maximum of Months | 261074.09 | 37611.08 | 794004.08 | 117200.65 | 293477.65 | 64100.48 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY {Maximum} [W] | HEATREJECTION:ELECTRICITY {TIMESTAMP} | HUMIDIFIER:ELECTRICITY {Maximum} [W] | HUMIDIFIER:ELECTRICITY {TIMESTAMP} | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [] | COGENERATION:ELECTRICITY [] | |
January | 126029.38 | 20-JAN-13:00 | 49502.97 | 20-JAN-15:50 | 25503.98 | 14-JAN-12:09 | 0.00 | 0.00 | 0.00 |
February | 143547.05 | 18-FEB-13:30 | 49487.24 | 18-FEB-14:30 | 40384.97 | 09-FEB-18:00 | 0.00 | 0.00 | 0.00 |
March | 297425.16 | 14-MAR-12:00 | 50468.51 | 13-MAR-14:09 | 62286.49 | 31-MAR-23:10 | 0.00 | 0.00 | 0.00 |
April | 239023.47 | 20-APR-12:50 | 49837.66 | 12-APR-13:30 | 80671.19 | 18-APR-20:49 | 0.00 | 0.00 | 0.00 |
May | 236821.81 | 31-MAY-12:20 | 53507.66 | 31-MAY-12:00 | 32483.26 | 31-MAY-23:00 | 0.00 | 0.00 | 0.00 |
June | 366330.64 | 26-JUN-15:09 | 80361.09 | 15-JUN-13:20 | 39046.85 | 09-JUN-06:00 | 0.00 | 0.00 | 0.00 |
July | 392196.78 | 17-JUL-12:00 | 80361.09 | 19-JUL-10:09 | 52355.45 | 03-JUL-06:00 | 0.00 | 0.00 | 0.00 |
August | 432978.75 | 16-AUG-15:09 | 80361.09 | 03-AUG-10:30 | 82269.92 | 17-AUG-06:10 | 0.00 | 0.00 | 0.00 |
September | 280151.42 | 12-SEP-15:50 | 54078.47 | 12-SEP-16:19 | 34454.94 | 30-SEP-23:19 | 0.00 | 0.00 | 0.00 |
October | 273666.29 | 11-OCT-12:20 | 50114.66 | 11-OCT-12:00 | 49449.09 | 31-OCT-23:00 | 0.00 | 0.00 | 0.00 |
November | 205834.38 | 07-NOV-15:00 | 49908.52 | 09-NOV-12:50 | 55043.52 | 10-NOV-18:00 | 0.00 | 0.00 | 0.00 |
December | 237316.14 | 01-DEC-13:00 | 49621.96 | 02-DEC-14:00 | 80581.22 | 16-DEC-07:30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||
Minimum of Months | 126029.38 | 49487.24 | 25503.98 | 0.00 | 0.00 | 0.00 | |||
Maximum of Months | 432978.75 | 80361.09 | 82269.92 | 0.00 | 0.00 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY {AT MAX/MIN} [W] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY {AT MAX/MIN} [W] | |
January | 1103950.85 | 23-JAN-16:10 | 242746.30 | 439129.89 | 0.00 | 83149.86 | 134758.64 | 32548.67 | 0.00 | 101023.08 | 49370.83 |
February | 1176340.76 | 17-FEB-16:19 | 237662.32 | 557421.28 | 0.00 | 83147.69 | 138107.69 | 3740.67 | 0.00 | 74273.89 | 45199.45 |
March | 1582111.63 | 13-MAR-15:50 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 169605.51 | 49774.30 | 0.00 | 285984.77 | 49838.45 |
April | 1644056.14 | 07-APR-15:30 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 175113.62 | 32953.20 | 0.00 | 219940.61 | 49497.17 |
May | 1316737.84 | 31-MAY-15:00 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 215608.85 | 51828.34 | 0.00 | 230184.00 | 52203.52 |
June | 1617499.28 | 26-JUN-15:09 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 272488.10 | 51051.65 | 0.00 | 366330.64 | 51581.52 |
July | 1808119.75 | 24-JUL-15:20 | 234435.00 | 675712.68 | 0.00 | 83146.17 | 293477.65 | 52356.56 | 0.00 | 376865.57 | 80361.09 |
August | 1989326.38 | 16-AUG-15:09 | 234435.00 | 794004.08 | 0.00 | 83146.17 | 274880.68 | 50964.55 | 0.00 | 432978.75 | 80361.09 |
September | 1414245.60 | 12-SEP-15:00 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 266430.00 | 61457.33 | 0.00 | 269248.11 | 51434.57 |
October | 1441684.81 | 11-OCT-15:00 | 234435.00 | 557421.28 | 0.00 | 83146.17 | 181125.29 | 50074.69 | 0.00 | 261603.23 | 49519.15 |
November | 1479620.51 | 06-NOV-16:49 | 261074.09 | 675712.68 | 37611.08 | 83158.86 | 126541.99 | 32518.23 | 0.00 | 172131.34 | 49356.44 |
December | 1585822.88 | 04-DEC-16:30 | 261074.09 | 794004.08 | 37611.08 | 83159.47 | 112954.18 | 32371.85 | 0.00 | 145878.73 | 49248.27 |
Annual Sum or Average | |||||||||||
Minimum of Months | 1103950.85 | 234435.00 | 439129.89 | 0.00 | 83146.17 | 112954.18 | 3740.67 | 0.00 | 74273.89 | 45199.45 | |
Maximum of Months | 1989326.38 | 261074.09 | 794004.08 | 37611.08 | 83159.47 | 293477.65 | 61457.33 | 0.00 | 432978.75 | 80361.09 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS {Maximum} [W] | WATERSYSTEMS:NATURALGAS {TIMESTAMP} | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 1076527.75 | 05-JAN-07:19 | 0.00 | 83436.76 | 31-JAN-12:39 | 0.00 |
February | 0.00 | 0.00 | 1216556.07 | 06-FEB-07:19 | 0.00 | 83550.15 | 10-FEB-12:30 | 0.00 |
March | 0.00 | 0.00 | 822827.65 | 20-MAR-05:19 | 0.00 | 83391.99 | 01-MAR-12:39 | 0.00 |
April | 0.00 | 0.00 | 830903.59 | 17-APR-06:19 | 0.00 | 82378.39 | 03-APR-11:30 | 0.00 |
May | 0.00 | 0.00 | 368925.66 | 01-MAY-04:10 | 0.00 | 80776.87 | 01-MAY-11:00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 78595.70 | 01-JUN-11:00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 76421.72 | 03-JUL-11:30 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 75235.64 | 01-AUG-11:30 | 0.00 |
September | 0.00 | 0.00 | 337111.43 | 22-SEP-06:10 | 0.00 | 76553.46 | 29-SEP-11:00 | 0.00 |
October | 0.00 | 0.00 | 927794.47 | 30-OCT-06:19 | 0.00 | 78481.59 | 27-OCT-11:30 | 0.00 |
November | 0.00 | 0.00 | 904387.06 | 30-NOV-07:10 | 0.00 | 80913.19 | 30-NOV-12:00 | 0.00 |
December | 0.00 | 0.00 | 1461485.81 | 23-DEC-07:19 | 0.00 | 82511.75 | 29-DEC-12:39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 75235.64 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 1461485.81 | 0.00 | 83550.15 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 26.86 | 1.17 | 26.93 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 26.39 | 0.00 | 26.39 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.91 | 0.00 | 25.91 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 25.89 | 0.00 | 25.89 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 26.30 | 0.00 | 26.30 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.00 | 25.97 | 0.00 | 25.97 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 7.17 | 26.34 | 0.00 | 26.34 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.13 | 0.00 | 26.13 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 7.83 | 26.17 | 0.17 | 26.20 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 9.83 | 26.45 | 0.17 | 26.46 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 26.35 | 0.33 | 26.39 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 26.40 | 0.00 | 26.40 |
Annual Sum or Average | 0.00 | 0.00 | 71.50 | 26.30 | 1.83 | 26.32 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 25.89 | 0.00 | 25.89 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 26.86 | 1.17 | 26.93 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 25.60 | 0.00 | 25.60 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 26.22 | 0.00 | 26.22 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.59 | 0.00 | 25.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.58 | 0.00 | 25.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 25.61 | 0.00 | 25.61 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 25.68 | 0.00 | 25.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 25.65 | 0.00 | 25.65 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.67 | 0.00 | 25.67 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.93 | 0.00 | 25.93 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 25.59 | 0.00 | 25.59 |
Annual Sum or Average | 0.00 | 0.00 | 7.17 | 25.66 | 0.00 | 25.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 26.22 | 0.00 | 26.22 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.50 | 25.57 | 0.00 | 25.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.58 | 0.00 | 25.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
February | 1.67 | 18.27 | 0.33 | 18.61 | 0.00 | 18.61 | 0.00 | 18.61 |
March | 0.83 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 | 0.00 | 18.71 |
April | 1.33 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 | 0.00 | 18.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 25.56 | 0.00 | 25.56 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 | 0.00 | 18.08 |
November | 0.33 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 | 0.00 | 18.92 |
December | 2.33 | 18.92 | 0.33 | 19.08 | 0.00 | 19.08 | 0.00 | 19.08 |
Annual Sum or Average | 8.17 | 18.62 | 0.67 | 18.74 | 0.33 | 18.99 | 0.00 | 18.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.33 | 18.92 | 0.33 | 19.08 | 0.17 | 25.56 | 0.00 | 25.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 27.41 | 0.17 | 27.39 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.27 | 2.33 | 27.37 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 25.68 | 0.00 | 25.68 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 | 0.00 | 19.09 |
Annual Sum or Average | 0.67 | 19.09 | 0.00 | 19.09 | 4.00 | 26.01 | 2.50 | 26.52 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 19.09 | 0.00 | 19.09 | 3.00 | 27.41 | 2.33 | 27.39 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.76 | 1.33 | 27.76 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 27.59 | 0.83 | 27.59 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.59 | 1.00 | 27.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 27.88 | 4.17 | 27.88 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 10.33 | 27.95 | 10.33 | 27.95 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.06 | 3.83 | 28.06 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.92 | 3.50 | 27.92 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.73 | 2.33 | 27.73 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.83 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 | 0.00 | 18.84 |
Annual Sum or Average | 0.83 | 18.84 | 0.00 | 18.84 | 27.33 | 27.63 | 27.33 | 27.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 18.84 | 0.00 | 18.84 | 10.33 | 28.06 | 10.33 | 28.06 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 19.37 | 0.00 | 19.37 | 5.33 | 26.69 | 5.33 | 26.91 |
February | 0.50 | 19.21 | 0.00 | 19.21 | 2.67 | 26.53 | 2.67 | 27.16 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 27.97 | 2.50 | 27.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 27.49 | 2.67 | 27.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 27.51 | 8.00 | 27.55 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.83 | 27.70 | 6.17 | 27.76 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 10.83 | 27.19 | 10.33 | 27.18 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 11.50 | 26.93 | 11.33 | 26.93 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 10.67 | 26.53 | 10.67 | 26.53 |
December | 0.83 | 18.85 | 0.00 | 18.85 | 3.83 | 26.47 | 3.83 | 27.22 |
Annual Sum or Average | 1.67 | 19.06 | 0.00 | 19.06 | 65.67 | 27.05 | 63.50 | 27.16 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.83 | 19.37 | 0.00 | 19.37 | 11.50 | 27.97 | 11.33 | 27.97 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.70 | 1.00 | 27.70 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 28.35 | 1.83 | 28.36 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 27.27 | 1.17 | 27.53 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 27.65 | 3.00 | 27.66 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 17.67 | 27.56 | 6.50 | 27.79 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 28.67 | 27.35 | 10.67 | 27.58 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 27.60 | 13.83 | 27.72 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 27.90 | 5.33 | 28.04 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 28.33 | 3.33 | 28.34 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 27.89 | 1.50 | 27.89 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 28.26 | 1.33 | 28.26 |
Annual Sum or Average | 0.00 | 0.00 | 121.17 | 27.60 | 49.50 | 27.77 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 50.50 | 28.35 | 13.83 | 28.36 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.33 | 18.80 | 0.33 | 18.94 | 0.00 | 18.94 | 0.00 | 18.94 |
February | 12.33 | 17.76 | 3.00 | 17.98 | 0.00 | 17.98 | 0.00 | 17.98 |
March | 4.33 | 17.15 | 1.50 | 16.66 | 0.00 | 16.66 | 0.00 | 16.66 |
April | 2.00 | 18.54 | 0.17 | 18.64 | 0.00 | 18.64 | 0.00 | 18.64 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.39 | 0.50 | 27.37 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.47 | 2.17 | 27.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 1.67 | 18.83 | 0.17 | 18.97 | 0.00 | 18.97 | 0.00 | 18.97 |
November | 3.50 | 18.86 | 0.50 | 19.02 | 0.00 | 19.02 | 0.00 | 19.02 |
December | 21.67 | 17.41 | 6.83 | 17.72 | 0.00 | 17.72 | 0.00 | 17.72 |
Annual Sum or Average | 48.83 | 17.77 | 12.50 | 17.91 | 3.33 | 18.40 | 2.67 | 18.76 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 21.67 | 18.86 | 6.83 | 19.02 | 2.33 | 27.47 | 2.17 | 27.48 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.83 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 | 0.00 | 18.66 |
February | 6.00 | 17.08 | 0.33 | 16.96 | 0.00 | 16.96 | 0.00 | 16.96 |
March | 4.50 | 16.71 | 1.50 | 16.19 | 0.50 | 17.07 | 0.50 | 17.82 |
April | 1.67 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 | 0.00 | 18.31 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 27.54 | 1.00 | 27.54 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 6.33 | 27.82 | 6.33 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 13.33 | 28.02 | 13.17 | 28.02 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 28.19 | 5.17 | 28.19 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.50 | 27.84 | 3.50 | 27.84 |
October | 1.50 | 18.41 | 0.00 | 18.41 | 1.00 | 22.03 | 1.00 | 23.59 |
November | 2.67 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 | 0.00 | 18.41 |
December | 11.00 | 16.22 | 1.00 | 16.16 | 0.00 | 16.16 | 0.00 | 16.16 |
Annual Sum or Average | 30.17 | 17.11 | 2.83 | 16.92 | 30.83 | 22.25 | 30.67 | 24.10 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.16 | 0.00 | 16.16 |
Maximum of Months | 11.00 | 18.66 | 1.50 | 18.66 | 13.33 | 28.19 | 13.17 | 28.19 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.00 | 18.83 | 0.00 | 18.83 | 12.17 | 25.47 | 12.17 | 25.74 |
February | 3.83 | 18.19 | 0.17 | 18.27 | 2.50 | 22.03 | 2.50 | 23.70 |
March | 3.50 | 16.99 | 1.50 | 16.49 | 6.33 | 21.69 | 6.33 | 23.16 |
April | 1.83 | 18.55 | 0.17 | 18.70 | 0.00 | 18.70 | 0.00 | 18.70 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.33 | 27.54 | 2.00 | 27.55 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 6.67 | 27.59 | 6.67 | 27.59 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 27.78 | 5.00 | 27.79 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 12.67 | 27.01 | 12.00 | 27.00 |
October | 1.17 | 18.58 | 0.00 | 18.58 | 15.00 | 26.00 | 14.83 | 26.27 |
November | 1.67 | 18.50 | 0.00 | 18.50 | 14.00 | 25.41 | 14.00 | 25.80 |
December | 6.17 | 17.04 | 0.67 | 16.93 | 3.00 | 20.36 | 3.00 | 22.18 |
Annual Sum or Average | 19.17 | 17.72 | 2.50 | 17.54 | 79.83 | 24.77 | 78.50 | 25.62 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 6.17 | 18.83 | 1.50 | 18.83 | 15.00 | 27.78 | 14.83 | 27.79 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.17 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 | 0.00 | 19.05 |
February | 3.17 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 | 0.00 | 18.23 |
March | 2.50 | 17.09 | 1.17 | 16.35 | 1.00 | 18.81 | 0.67 | 19.95 |
April | 1.33 | 18.56 | 0.00 | 18.56 | 0.17 | 19.62 | 0.17 | 20.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 27.52 | 1.17 | 27.52 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 28.47 | 4.00 | 28.54 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.17 | 28.10 | 5.50 | 28.07 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 28.44 | 2.00 | 28.48 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.50 | 28.12 | 3.67 | 28.15 |
October | 1.00 | 18.46 | 0.00 | 18.46 | 1.83 | 24.64 | 1.67 | 25.89 |
November | 1.83 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 | 0.00 | 18.40 |
December | 6.67 | 16.67 | 1.00 | 16.53 | 0.00 | 16.53 | 0.00 | 16.53 |
Annual Sum or Average | 18.67 | 17.67 | 2.17 | 17.41 | 29.50 | 23.73 | 18.83 | 24.95 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.53 | 0.00 | 16.53 |
Maximum of Months | 6.67 | 19.05 | 1.17 | 19.05 | 8.17 | 28.47 | 5.50 | 28.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 38.00 | 16.91 | 12.00 | 17.16 | 0.00 | 17.16 | 0.00 | 17.16 |
February | 39.83 | 16.59 | 13.83 | 16.77 | 0.00 | 16.77 | 0.00 | 16.77 |
March | 25.33 | 16.24 | 7.83 | 16.24 | 0.00 | 16.24 | 0.00 | 16.24 |
April | 23.00 | 16.69 | 9.00 | 16.86 | 0.00 | 16.86 | 0.00 | 16.86 |
May | 0.83 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 | 0.00 | 18.20 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 27.63 | 1.33 | 27.60 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 27.60 | 3.83 | 27.63 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 27.26 | 0.17 | 27.26 |
September | 0.17 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 | 0.00 | 19.14 |
October | 13.50 | 17.36 | 4.67 | 17.64 | 0.00 | 17.64 | 0.00 | 17.64 |
November | 18.17 | 18.11 | 5.00 | 18.52 | 0.00 | 18.52 | 0.00 | 18.52 |
December | 66.50 | 16.60 | 28.67 | 16.93 | 0.00 | 16.93 | 0.00 | 16.93 |
Annual Sum or Average | 225.33 | 16.79 | 81.00 | 17.02 | 7.17 | 17.27 | 5.33 | 17.44 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.24 | 0.00 | 16.24 |
Maximum of Months | 66.50 | 19.14 | 28.67 | 19.14 | 5.00 | 27.63 | 3.83 | 27.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 19.67 | 16.02 | 1.83 | 15.95 | 0.00 | 15.95 | 0.00 | 15.95 |
February | 24.17 | 15.69 | 4.00 | 15.53 | 0.00 | 15.53 | 0.00 | 15.53 |
March | 17.83 | 15.69 | 3.50 | 15.42 | 0.00 | 15.42 | 0.00 | 15.42 |
April | 15.00 | 15.52 | 3.67 | 15.38 | 0.00 | 15.38 | 0.00 | 15.38 |
May | 0.83 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 | 0.00 | 18.19 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.33 | 27.82 | 7.67 | 27.82 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 14.83 | 28.10 | 13.67 | 28.12 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 6.17 | 28.13 | 6.00 | 28.14 |
September | 0.17 | 19.14 | 0.00 | 19.14 | 4.83 | 27.37 | 4.83 | 27.51 |
October | 7.33 | 15.99 | 0.83 | 15.86 | 0.00 | 15.86 | 0.00 | 15.86 |
November | 9.67 | 16.94 | 0.33 | 16.97 | 0.00 | 16.97 | 0.00 | 16.97 |
December | 36.00 | 15.53 | 6.33 | 15.45 | 0.00 | 15.45 | 0.00 | 15.45 |
Annual Sum or Average | 130.67 | 15.81 | 20.50 | 15.66 | 34.17 | 17.93 | 32.17 | 19.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.38 | 0.00 | 15.38 |
Maximum of Months | 36.00 | 19.14 | 6.33 | 19.14 | 14.83 | 28.13 | 13.67 | 28.14 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 8.33 | 17.47 | 0.67 | 17.38 | 1.83 | 18.82 | 1.83 | 19.85 |
February | 22.00 | 16.22 | 4.83 | 16.13 | 1.17 | 16.62 | 1.17 | 17.07 |
March | 17.17 | 15.86 | 3.83 | 15.59 | 1.50 | 16.42 | 1.50 | 17.15 |
April | 16.67 | 15.97 | 5.00 | 15.92 | 0.00 | 15.92 | 0.00 | 15.92 |
May | 0.83 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 | 0.00 | 18.25 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 27.65 | 3.17 | 27.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 8.83 | 27.73 | 7.83 | 27.75 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.83 | 27.85 | 5.50 | 27.86 |
September | 0.17 | 19.22 | 0.00 | 19.22 | 11.67 | 27.06 | 10.50 | 27.09 |
October | 6.33 | 16.22 | 0.50 | 16.25 | 9.50 | 22.47 | 9.50 | 24.12 |
November | 8.33 | 17.67 | 0.33 | 17.77 | 3.67 | 20.47 | 3.67 | 21.94 |
December | 32.33 | 16.47 | 6.17 | 16.67 | 1.83 | 17.17 | 1.83 | 17.63 |
Annual Sum or Average | 112.17 | 16.42 | 21.33 | 16.38 | 49.67 | 19.35 | 46.50 | 20.97 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.92 | 0.00 | 15.92 |
Maximum of Months | 32.33 | 19.22 | 6.17 | 19.22 | 11.67 | 27.85 | 10.50 | 27.86 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 10.33 | 16.82 | 2.00 | 16.50 | 0.00 | 16.50 | 0.00 | 16.50 |
February | 19.50 | 15.91 | 4.33 | 15.67 | 0.00 | 15.67 | 0.00 | 15.67 |
March | 14.50 | 15.94 | 3.67 | 15.63 | 0.67 | 16.06 | 0.33 | 16.27 |
April | 7.50 | 16.13 | 0.33 | 16.08 | 0.17 | 16.33 | 0.17 | 16.57 |
May | 0.83 | 18.57 | 0.00 | 18.57 | 1.00 | 23.45 | 0.83 | 24.73 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 8.50 | 28.55 | 4.00 | 28.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 9.50 | 28.23 | 6.17 | 28.22 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 28.37 | 2.50 | 28.42 |
September | 0.17 | 19.21 | 0.00 | 19.21 | 6.00 | 27.91 | 4.17 | 28.03 |
October | 5.00 | 15.95 | 0.17 | 15.92 | 1.17 | 18.17 | 1.17 | 19.72 |
November | 6.83 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 | 0.00 | 17.53 |
December | 27.00 | 15.65 | 4.00 | 15.56 | 0.00 | 15.56 | 0.00 | 15.56 |
Annual Sum or Average | 91.67 | 16.11 | 14.50 | 15.92 | 31.67 | 18.76 | 19.33 | 19.94 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.56 | 0.00 | 15.56 |
Maximum of Months | 27.00 | 19.21 | 4.33 | 19.21 | 9.50 | 28.55 | 6.17 | 28.61 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 28.34 | 65.83 | 28.35 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 71.67 | 28.34 | 65.83 | 28.35 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 71.67 | 28.34 | 65.83 | 28.35 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 28.27 | 43.17 | 28.27 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 44.50 | 28.27 | 43.17 | 28.27 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 44.50 | 28.27 | 43.17 | 28.27 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 28.23 | 38.33 | 28.24 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 40.83 | 28.23 | 38.33 | 28.24 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 40.83 | 28.23 | 38.33 | 28.24 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 682.33 | 28.49 | 455.17 | 28.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 28.19 | 0.00 | 28.19 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.75 | 514.00 | 31.85 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 676.50 | 28.35 | 433.67 | 28.35 |
Annual Sum or Average | 0.00 | 0.00 | 2102.83 | 29.60 | 1402.83 | 29.66 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 743.17 | 31.75 | 514.00 | 31.85 |
Report: ComfortReportSimple55Monthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 198.17 | 23.92 | 67.33 | 24.50 | 0.00 | 24.50 |
February | 240.67 | 23.97 | 47.33 | 24.36 | 0.00 | 24.36 |
March | 274.17 | 23.99 | 50.50 | 24.28 | 0.00 | 24.28 |
April | 117.33 | 24.00 | 93.83 | 24.88 | 0.00 | 24.88 |
May | 92.00 | 24.00 | 148.33 | 24.88 | 0.00 | 24.88 |
June | 42.67 | 24.36 | 284.17 | 24.72 | 35.17 | 24.69 |
July | 92.67 | 24.57 | 341.67 | 24.79 | 79.67 | 24.77 |
August | 42.83 | 25.10 | 335.33 | 24.77 | 40.50 | 24.81 |
September | 28.33 | 24.00 | 176.50 | 25.25 | 0.00 | 25.25 |
October | 104.50 | 24.00 | 112.17 | 25.19 | 0.00 | 25.19 |
November | 86.17 | 23.98 | 102.00 | 25.31 | 0.00 | 25.31 |
December | 264.67 | 23.87 | 62.17 | 24.36 | 0.00 | 24.36 |
Annual Sum or Average | 1584.17 | 24.03 | 1821.33 | 24.73 | 155.33 | 24.73 |
Minimum of Months | 28.33 | 23.87 | 47.33 | 24.28 | 0.00 | 24.28 |
Maximum of Months | 274.17 | 25.10 | 341.67 | 25.31 | 79.67 | 25.31 |
Report: ComfortReportSimple55Monthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 253.00 | 23.93 | 26.67 | 24.08 | 0.00 | 24.08 |
February | 270.33 | 23.96 | 29.83 | 24.14 | 0.00 | 24.14 |
March | 231.17 | 23.98 | 28.50 | 24.12 | 0.00 | 24.12 |
April | 79.00 | 24.00 | 89.33 | 24.86 | 0.00 | 24.86 |
May | 64.83 | 24.00 | 148.33 | 24.64 | 0.00 | 24.64 |
June | 41.00 | 24.34 | 302.17 | 24.38 | 41.00 | 24.38 |
July | 91.17 | 24.36 | 362.00 | 24.37 | 84.83 | 24.37 |
August | 27.33 | 24.19 | 368.67 | 24.28 | 27.33 | 24.27 |
September | 40.83 | 23.99 | 155.50 | 24.68 | 0.00 | 24.68 |
October | 134.17 | 23.98 | 84.33 | 24.61 | 0.00 | 24.61 |
November | 109.83 | 23.98 | 72.83 | 24.68 | 0.00 | 24.68 |
December | 278.50 | 24.00 | 30.83 | 24.20 | 0.00 | 24.20 |
Annual Sum or Average | 1621.17 | 24.01 | 1699.00 | 24.37 | 153.17 | 24.37 |
Minimum of Months | 27.33 | 23.93 | 26.67 | 24.08 | 0.00 | 24.08 |
Maximum of Months | 278.50 | 24.36 | 368.67 | 24.86 | 84.83 | 24.86 |
Report: ComfortReportSimple55Monthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 470.00 | 23.30 | 0.00 | 23.30 | 0.00 | 23.30 |
February | 429.83 | 23.12 | 10.00 | 23.08 | 10.00 | 23.03 |
March | 481.17 | 23.44 | 5.67 | 23.45 | 1.00 | 23.44 |
April | 366.67 | 23.55 | 9.00 | 23.58 | 0.00 | 23.58 |
May | 163.50 | 23.86 | 97.50 | 24.22 | 0.00 | 24.22 |
June | 58.33 | 24.12 | 248.83 | 24.28 | 41.50 | 24.27 |
July | 107.17 | 24.21 | 284.83 | 24.29 | 89.33 | 24.29 |
August | 45.83 | 24.05 | 289.67 | 24.32 | 34.33 | 24.29 |
September | 105.83 | 23.86 | 107.50 | 24.33 | 0.00 | 24.33 |
October | 340.83 | 23.70 | 6.00 | 23.73 | 0.00 | 23.73 |
November | 418.33 | 23.54 | 1.33 | 23.55 | 0.00 | 23.55 |
December | 497.00 | 22.89 | 46.50 | 22.67 | 46.50 | 22.48 |
Annual Sum or Average | 3484.50 | 23.43 | 1106.83 | 23.62 | 222.67 | 23.60 |
Minimum of Months | 45.83 | 22.89 | 0.00 | 22.67 | 0.00 | 22.48 |
Maximum of Months | 497.00 | 24.21 | 289.67 | 24.33 | 89.33 | 24.33 |
Report: ComfortReportSimple55Monthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 500.67 | 21.63 | 148.33 | 21.23 | 148.33 | 20.98 |
February | 453.83 | 21.82 | 131.67 | 21.47 | 131.67 | 21.25 |
March | 503.17 | 22.45 | 65.50 | 22.13 | 65.50 | 21.87 |
April | 416.83 | 22.35 | 79.17 | 21.99 | 74.67 | 21.71 |
May | 238.83 | 23.41 | 59.50 | 23.58 | 3.83 | 23.54 |
June | 62.83 | 24.08 | 271.33 | 24.28 | 38.67 | 24.27 |
July | 94.67 | 24.22 | 317.83 | 24.31 | 86.67 | 24.30 |
August | 54.67 | 24.03 | 293.17 | 24.28 | 36.17 | 24.27 |
September | 157.33 | 23.52 | 99.83 | 23.99 | 0.00 | 23.99 |
October | 463.17 | 22.78 | 48.50 | 22.57 | 48.50 | 22.40 |
November | 477.33 | 22.14 | 70.83 | 21.97 | 70.83 | 21.83 |
December | 497.00 | 21.37 | 202.33 | 20.99 | 202.33 | 20.79 |
Annual Sum or Average | 3920.33 | 22.32 | 1788.00 | 22.41 | 907.17 | 22.19 |
Minimum of Months | 54.67 | 21.37 | 48.50 | 20.99 | 0.00 | 20.79 |
Maximum of Months | 503.17 | 24.22 | 317.83 | 24.31 | 202.33 | 24.30 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 22.17 | 82.33 | 21.97 | 82.33 | 21.82 |
February | 454.00 | 22.11 | 79.83 | 21.88 | 79.83 | 21.70 |
March | 503.17 | 22.90 | 19.83 | 22.79 | 19.83 | 22.69 |
April | 388.50 | 23.21 | 6.33 | 23.22 | 0.50 | 23.22 |
May | 195.17 | 23.71 | 99.67 | 24.04 | 0.00 | 24.04 |
June | 35.67 | 24.44 | 363.83 | 24.42 | 35.67 | 24.43 |
July | 77.00 | 24.56 | 406.00 | 24.50 | 77.00 | 24.51 |
August | 29.50 | 24.44 | 373.33 | 24.33 | 26.50 | 24.34 |
September | 137.17 | 23.69 | 126.17 | 24.21 | 0.00 | 24.21 |
October | 426.17 | 23.08 | 16.00 | 23.01 | 14.67 | 22.94 |
November | 482.17 | 22.77 | 19.17 | 22.70 | 19.17 | 22.63 |
December | 497.00 | 22.24 | 105.33 | 21.95 | 105.33 | 21.74 |
Annual Sum or Average | 3727.50 | 22.79 | 1697.83 | 23.08 | 460.83 | 22.98 |
Minimum of Months | 29.50 | 22.11 | 6.33 | 21.88 | 0.00 | 21.70 |
Maximum of Months | 503.17 | 24.56 | 406.00 | 24.50 | 105.33 | 24.51 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 465.50 | 22.20 | 55.17 | 22.09 | 50.83 | 21.97 |
February | 396.17 | 22.07 | 93.00 | 21.90 | 80.83 | 21.71 |
March | 392.17 | 22.45 | 47.17 | 22.44 | 24.83 | 22.32 |
April | 322.83 | 22.59 | 51.83 | 22.73 | 10.50 | 22.69 |
May | 140.17 | 23.43 | 178.50 | 24.08 | 2.33 | 24.10 |
June | 47.50 | 25.14 | 405.17 | 24.47 | 46.17 | 24.54 |
July | 101.00 | 25.18 | 429.17 | 24.63 | 100.17 | 24.72 |
August | 58.67 | 24.60 | 384.67 | 24.30 | 38.33 | 24.37 |
September | 99.83 | 23.73 | 218.00 | 24.36 | 10.17 | 24.45 |
October | 364.83 | 22.72 | 69.83 | 22.93 | 26.33 | 22.88 |
November | 426.67 | 22.43 | 38.00 | 22.41 | 27.50 | 22.32 |
December | 477.50 | 21.94 | 117.83 | 21.70 | 115.00 | 21.52 |
Annual Sum or Average | 3292.83 | 22.58 | 2088.33 | 23.08 | 533.00 | 23.02 |
Minimum of Months | 47.50 | 21.94 | 38.00 | 21.70 | 2.33 | 21.52 |
Maximum of Months | 477.50 | 25.18 | 429.17 | 24.63 | 115.00 | 24.72 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 307.00 | 22.52 | 133.50 | 22.89 | 39.67 | 22.77 |
February | 277.00 | 22.19 | 148.67 | 22.37 | 71.67 | 22.12 |
March | 322.33 | 22.46 | 85.17 | 22.59 | 32.17 | 22.44 |
April | 300.83 | 22.53 | 73.67 | 22.52 | 35.67 | 22.36 |
May | 181.00 | 23.37 | 133.83 | 23.88 | 0.00 | 23.88 |
June | 50.67 | 24.56 | 363.67 | 24.43 | 40.33 | 24.46 |
July | 87.17 | 24.86 | 405.17 | 24.56 | 84.67 | 24.61 |
August | 48.50 | 25.36 | 425.33 | 24.46 | 44.00 | 24.55 |
September | 91.17 | 24.36 | 263.50 | 24.61 | 23.50 | 24.77 |
October | 273.67 | 22.95 | 164.67 | 23.36 | 54.33 | 23.35 |
November | 267.00 | 22.86 | 152.00 | 23.41 | 35.17 | 23.39 |
December | 350.17 | 22.47 | 143.17 | 22.54 | 80.33 | 22.36 |
Annual Sum or Average | 2556.50 | 22.85 | 2492.33 | 23.46 | 541.50 | 23.41 |
Minimum of Months | 48.50 | 22.19 | 73.67 | 22.37 | 0.00 | 22.12 |
Maximum of Months | 350.17 | 25.36 | 425.33 | 24.61 | 84.67 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 411.17 | 22.50 | 44.00 | 22.50 | 25.00 | 22.42 |
February | 329.83 | 22.60 | 53.67 | 22.79 | 13.83 | 22.73 |
March | 237.00 | 23.16 | 92.33 | 23.59 | 10.33 | 23.59 |
April | 97.00 | 23.68 | 196.33 | 24.37 | 3.33 | 24.40 |
May | 86.67 | 23.72 | 237.83 | 24.48 | 7.00 | 24.53 |
June | 59.33 | 25.67 | 454.50 | 24.66 | 59.33 | 24.77 |
July | 103.67 | 25.54 | 486.17 | 24.78 | 103.67 | 24.89 |
August | 79.83 | 26.30 | 506.17 | 24.77 | 79.83 | 24.96 |
September | 71.00 | 24.44 | 272.00 | 24.70 | 21.67 | 24.84 |
October | 213.83 | 23.12 | 106.67 | 23.75 | 9.67 | 23.86 |
November | 219.17 | 23.08 | 82.50 | 23.61 | 3.50 | 23.61 |
December | 288.00 | 23.06 | 78.17 | 23.23 | 29.83 | 23.11 |
Annual Sum or Average | 2196.50 | 23.31 | 2610.33 | 24.00 | 367.00 | 24.07 |
Minimum of Months | 59.33 | 22.50 | 44.00 | 22.50 | 3.33 | 22.42 |
Maximum of Months | 411.17 | 26.30 | 506.17 | 24.78 | 103.67 | 24.96 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.74 | 274.83 | 20.51 | 274.83 | 20.40 |
February | 454.00 | 20.66 | 294.17 | 20.50 | 294.17 | 20.42 |
March | 514.00 | 21.49 | 174.33 | 21.14 | 174.33 | 20.93 |
April | 471.33 | 21.70 | 119.67 | 21.34 | 118.50 | 21.09 |
May | 305.67 | 23.20 | 52.83 | 23.32 | 6.50 | 23.28 |
June | 51.17 | 24.18 | 317.67 | 24.33 | 36.33 | 24.32 |
July | 89.00 | 24.22 | 352.67 | 24.39 | 84.67 | 24.37 |
August | 69.00 | 23.81 | 266.67 | 24.20 | 28.17 | 24.19 |
September | 215.00 | 23.26 | 81.33 | 23.64 | 1.00 | 23.63 |
October | 499.50 | 22.00 | 93.33 | 21.73 | 93.33 | 21.54 |
November | 489.00 | 21.18 | 234.50 | 20.96 | 234.50 | 20.85 |
December | 497.00 | 20.38 | 388.17 | 20.25 | 388.17 | 20.20 |
Annual Sum or Average | 4156.67 | 21.57 | 2650.17 | 21.69 | 1734.50 | 21.45 |
Minimum of Months | 51.17 | 20.38 | 52.83 | 20.25 | 1.00 | 20.20 |
Maximum of Months | 514.00 | 24.22 | 388.17 | 24.39 | 388.17 | 24.37 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 421.33 | 21.09 | 178.83 | 20.85 | 178.83 | 20.72 |
February | 366.83 | 21.07 | 175.33 | 20.74 | 174.33 | 20.57 |
March | 377.50 | 21.62 | 124.50 | 21.33 | 114.50 | 21.08 |
April | 328.50 | 21.52 | 115.33 | 21.30 | 92.17 | 21.03 |
May | 181.00 | 22.95 | 126.33 | 23.63 | 5.67 | 23.62 |
June | 47.33 | 25.30 | 328.17 | 24.61 | 43.17 | 24.70 |
July | 108.33 | 25.18 | 353.17 | 24.78 | 102.00 | 24.88 |
August | 67.00 | 24.73 | 313.83 | 24.53 | 44.00 | 24.63 |
September | 133.67 | 23.35 | 153.67 | 24.11 | 9.50 | 24.19 |
October | 345.00 | 21.90 | 97.50 | 21.86 | 72.67 | 21.65 |
November | 399.00 | 21.44 | 131.83 | 21.23 | 130.67 | 21.10 |
December | 422.00 | 20.60 | 271.50 | 20.36 | 271.50 | 20.26 |
Annual Sum or Average | 3197.50 | 21.74 | 2370.00 | 22.13 | 1239.00 | 21.92 |
Minimum of Months | 47.33 | 20.60 | 97.50 | 20.36 | 5.67 | 20.26 |
Maximum of Months | 422.00 | 25.30 | 353.17 | 24.78 | 271.50 | 24.88 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 321.50 | 22.13 | 172.17 | 22.44 | 82.00 | 22.26 |
February | 296.17 | 21.67 | 189.83 | 21.80 | 114.50 | 21.50 |
March | 358.00 | 21.91 | 142.83 | 21.84 | 96.33 | 21.59 |
April | 366.00 | 21.70 | 115.33 | 21.45 | 93.00 | 21.18 |
May | 235.50 | 23.04 | 111.50 | 23.47 | 6.00 | 23.43 |
June | 64.83 | 24.11 | 325.17 | 24.34 | 37.17 | 24.36 |
July | 109.67 | 24.43 | 370.50 | 24.48 | 86.33 | 24.50 |
August | 67.50 | 24.65 | 376.33 | 24.46 | 41.83 | 24.54 |
September | 123.67 | 24.03 | 244.83 | 24.46 | 24.83 | 24.63 |
October | 308.00 | 22.54 | 192.83 | 22.87 | 85.83 | 22.76 |
November | 299.67 | 22.35 | 184.33 | 22.82 | 75.33 | 22.69 |
December | 385.00 | 21.67 | 226.33 | 21.58 | 178.83 | 21.35 |
Annual Sum or Average | 2935.50 | 22.35 | 2652.00 | 22.89 | 922.00 | 22.71 |
Minimum of Months | 64.83 | 21.67 | 111.50 | 21.45 | 6.00 | 21.18 |
Maximum of Months | 385.00 | 24.65 | 376.33 | 24.48 | 178.83 | 24.63 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 474.17 | 21.25 | 170.50 | 21.01 | 170.50 | 20.87 |
February | 418.00 | 21.14 | 185.83 | 20.88 | 182.67 | 20.73 |
March | 441.83 | 21.61 | 123.00 | 21.41 | 105.67 | 21.18 |
April | 395.00 | 21.66 | 109.17 | 21.51 | 82.00 | 21.27 |
May | 236.17 | 22.88 | 139.83 | 23.51 | 3.33 | 23.51 |
June | 76.00 | 24.61 | 378.33 | 24.47 | 53.67 | 24.54 |
July | 103.00 | 24.54 | 403.17 | 24.47 | 92.33 | 24.51 |
August | 63.00 | 24.15 | 387.00 | 24.38 | 34.83 | 24.42 |
September | 171.33 | 23.32 | 188.33 | 24.02 | 15.17 | 24.12 |
October | 414.50 | 22.01 | 104.33 | 22.01 | 69.00 | 21.86 |
November | 447.17 | 21.57 | 123.67 | 21.40 | 120.83 | 21.28 |
December | 486.83 | 20.87 | 279.83 | 20.61 | 279.83 | 20.49 |
Annual Sum or Average | 3727.00 | 21.80 | 2593.00 | 22.23 | 1209.83 | 22.04 |
Minimum of Months | 63.00 | 20.87 | 104.33 | 20.61 | 3.33 | 20.49 |
Maximum of Months | 486.83 | 24.61 | 403.17 | 24.47 | 279.83 | 24.54 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.14 | 395.17 | 19.99 | 395.17 | 19.93 |
February | 454.00 | 20.24 | 376.83 | 20.14 | 376.83 | 20.10 |
March | 514.00 | 21.05 | 281.17 | 20.71 | 281.17 | 20.55 |
April | 474.17 | 21.08 | 205.17 | 20.62 | 204.33 | 20.36 |
May | 351.67 | 22.73 | 60.83 | 22.76 | 23.83 | 22.65 |
June | 62.33 | 23.99 | 316.17 | 24.30 | 32.17 | 24.31 |
July | 108.33 | 24.24 | 360.33 | 24.39 | 85.83 | 24.39 |
August | 92.17 | 23.53 | 271.83 | 24.09 | 28.83 | 24.09 |
September | 242.33 | 22.88 | 93.00 | 23.16 | 18.33 | 23.03 |
October | 500.00 | 21.30 | 198.83 | 20.95 | 198.83 | 20.76 |
November | 489.00 | 20.50 | 342.00 | 20.29 | 342.00 | 20.20 |
December | 497.00 | 19.95 | 464.67 | 19.90 | 464.67 | 19.88 |
Annual Sum or Average | 4287.00 | 21.12 | 3366.00 | 21.21 | 2452.00 | 20.96 |
Minimum of Months | 62.33 | 19.95 | 60.83 | 19.90 | 18.33 | 19.88 |
Maximum of Months | 514.00 | 24.24 | 464.67 | 24.39 | 464.67 | 24.39 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 502.00 | 20.51 | 314.67 | 20.24 | 314.67 | 20.12 |
February | 451.17 | 20.83 | 259.67 | 20.50 | 259.67 | 20.34 |
March | 458.50 | 21.44 | 198.67 | 21.03 | 194.50 | 20.78 |
April | 391.67 | 21.08 | 178.67 | 20.68 | 159.33 | 20.37 |
May | 230.00 | 22.62 | 144.33 | 23.20 | 13.33 | 23.11 |
June | 60.83 | 25.14 | 406.00 | 24.51 | 49.67 | 24.61 |
July | 125.33 | 25.08 | 432.67 | 24.67 | 114.33 | 24.77 |
August | 78.83 | 24.48 | 398.83 | 24.40 | 45.50 | 24.49 |
September | 154.17 | 23.10 | 197.83 | 23.85 | 18.33 | 23.86 |
October | 429.67 | 21.63 | 148.67 | 21.34 | 137.50 | 21.10 |
November | 486.00 | 20.99 | 257.50 | 20.69 | 257.50 | 20.55 |
December | 497.00 | 20.22 | 390.17 | 20.06 | 390.17 | 20.00 |
Annual Sum or Average | 3865.17 | 21.39 | 3327.67 | 21.71 | 1954.50 | 21.46 |
Minimum of Months | 60.83 | 20.22 | 144.33 | 20.06 | 13.33 | 20.00 |
Maximum of Months | 502.00 | 25.14 | 432.67 | 24.67 | 390.17 | 24.77 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 369.00 | 21.35 | 229.00 | 21.27 | 173.67 | 21.00 |
February | 329.33 | 21.18 | 223.17 | 21.15 | 168.33 | 20.88 |
March | 381.67 | 21.46 | 209.33 | 21.29 | 171.00 | 21.04 |
April | 381.33 | 21.03 | 175.83 | 20.62 | 158.17 | 20.31 |
May | 287.83 | 22.57 | 111.50 | 22.91 | 21.17 | 22.81 |
June | 97.83 | 23.88 | 323.83 | 24.25 | 38.17 | 24.30 |
July | 123.83 | 24.27 | 371.83 | 24.42 | 88.00 | 24.46 |
August | 95.00 | 24.15 | 372.17 | 24.35 | 43.67 | 24.43 |
September | 151.33 | 23.55 | 240.67 | 24.13 | 32.50 | 24.22 |
October | 335.17 | 21.88 | 231.33 | 22.06 | 142.50 | 21.84 |
November | 336.67 | 21.65 | 219.83 | 21.78 | 142.67 | 21.52 |
December | 407.33 | 20.94 | 270.33 | 20.74 | 240.17 | 20.52 |
Annual Sum or Average | 3296.33 | 21.82 | 2978.83 | 22.22 | 1420.00 | 21.96 |
Minimum of Months | 95.00 | 20.94 | 111.50 | 20.62 | 21.17 | 20.31 |
Maximum of Months | 407.33 | 24.27 | 372.17 | 24.42 | 240.17 | 24.46 |
Report: ComfortReportSimple55Monthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 484.33 | 20.65 | 293.00 | 20.39 | 293.00 | 20.27 |
February | 428.00 | 20.77 | 263.50 | 20.53 | 261.50 | 20.41 |
March | 447.33 | 21.19 | 206.83 | 20.96 | 191.33 | 20.77 |
April | 403.83 | 21.04 | 172.50 | 20.74 | 148.17 | 20.46 |
May | 280.50 | 22.46 | 130.33 | 23.00 | 15.67 | 22.95 |
June | 91.33 | 24.21 | 369.67 | 24.37 | 49.50 | 24.46 |
July | 130.00 | 24.29 | 398.33 | 24.39 | 95.17 | 24.44 |
August | 93.33 | 23.72 | 376.83 | 24.25 | 34.83 | 24.30 |
September | 209.83 | 23.00 | 185.50 | 23.69 | 23.50 | 23.75 |
October | 425.50 | 21.44 | 173.83 | 21.30 | 147.50 | 21.10 |
November | 458.67 | 21.04 | 232.33 | 20.79 | 232.00 | 20.67 |
December | 491.83 | 20.46 | 358.17 | 20.24 | 358.17 | 20.15 |
Annual Sum or Average | 3944.50 | 21.40 | 3160.83 | 21.73 | 1850.33 | 21.49 |
Minimum of Months | 91.33 | 20.46 | 130.33 | 20.24 | 15.67 | 20.15 |
Maximum of Months | 491.83 | 24.29 | 398.33 | 24.39 | 358.17 | 24.46 |
Report: ComfortReportSimple55Monthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 502.00 | 27.00 | 0.00 | 27.00 |
February | 4.50 | 27.00 | 454.00 | 27.00 | 4.50 | 27.00 |
March | 9.67 | 27.00 | 514.00 | 27.00 | 9.67 | 27.00 |
April | 23.33 | 27.01 | 485.00 | 27.00 | 23.33 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 16.00 | 27.00 | 496.00 | 27.00 | 16.00 | 27.00 |
July | 59.00 | 27.00 | 497.00 | 27.00 | 59.00 | 27.00 |
August | 329.50 | 27.32 | 514.00 | 27.25 | 329.50 | 27.27 |
September | 3.50 | 27.00 | 485.00 | 27.00 | 3.50 | 27.00 |
October | 8.67 | 27.00 | 502.00 | 27.00 | 8.67 | 27.00 |
November | 14.50 | 27.00 | 489.00 | 27.00 | 14.50 | 27.00 |
December | 12.67 | 27.01 | 497.00 | 27.00 | 12.67 | 27.00 |
Annual Sum or Average | 481.33 | 27.22 | 5943.00 | 27.03 | 481.33 | 27.05 |
Minimum of Months | 0.00 | 0.00 | 454.00 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 329.50 | 27.32 | 514.00 | 27.25 | 329.50 | 27.27 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 437.17 | 27.00 | 0.00 | 27.00 |
February | 0.00 | 0.00 | 393.83 | 27.00 | 0.00 | 27.00 |
March | 0.00 | 0.00 | 489.33 | 27.00 | 0.00 | 27.00 |
April | 0.67 | 27.00 | 470.50 | 27.00 | 0.67 | 27.00 |
May | 0.00 | 0.00 | 508.00 | 27.00 | 0.00 | 27.00 |
June | 2.67 | 27.00 | 496.00 | 27.00 | 2.67 | 27.00 |
July | 0.67 | 27.00 | 497.00 | 27.00 | 0.67 | 27.00 |
August | 54.67 | 28.02 | 514.00 | 27.21 | 54.67 | 27.28 |
September | 2.33 | 27.00 | 485.00 | 27.00 | 2.33 | 27.00 |
October | 0.50 | 27.00 | 494.33 | 27.00 | 0.50 | 27.00 |
November | 0.00 | 0.00 | 482.67 | 27.00 | 0.00 | 27.00 |
December | 14.83 | 27.00 | 403.17 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 76.33 | 27.73 | 5671.00 | 27.02 | 61.50 | 27.03 |
Minimum of Months | 0.00 | 0.00 | 393.83 | 27.00 | 0.00 | 27.00 |
Maximum of Months | 54.67 | 28.02 | 514.00 | 27.21 | 54.67 | 27.28 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 102.00 | 24.99 | 308.67 | 26.45 | 4.83 | 26.41 |
February | 25.50 | 27.00 | 277.83 | 27.00 | 0.00 | 27.00 |
March | 22.00 | 27.00 | 436.50 | 27.00 | 1.00 | 27.00 |
April | 16.33 | 27.00 | 415.00 | 27.00 | 2.00 | 27.00 |
May | 2.00 | 25.90 | 500.33 | 27.00 | 0.00 | 27.00 |
June | 9.50 | 27.00 | 496.00 | 27.00 | 9.50 | 27.00 |
July | 8.83 | 27.00 | 497.00 | 27.00 | 8.83 | 27.00 |
August | 64.67 | 27.79 | 514.00 | 27.18 | 64.67 | 27.24 |
September | 3.33 | 27.00 | 485.00 | 27.00 | 3.33 | 27.00 |
October | 3.33 | 27.00 | 421.17 | 27.00 | 0.67 | 27.00 |
November | 0.50 | 27.00 | 397.67 | 27.00 | 0.00 | 27.00 |
December | 42.00 | 27.00 | 266.67 | 27.00 | 0.00 | 27.00 |
Annual Sum or Average | 300.00 | 26.48 | 5015.83 | 26.98 | 94.83 | 26.98 |
Minimum of Months | 0.50 | 24.99 | 266.67 | 26.45 | 0.00 | 26.41 |
Maximum of Months | 102.00 | 27.79 | 514.00 | 27.18 | 64.67 | 27.24 |
Report: ComfortReportSimple55Monthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 453.00 | 27.00 | 502.00 | 27.00 | 453.00 | 27.00 |
February | 454.00 | 27.02 | 454.00 | 27.02 | 454.00 | 27.02 |
March | 514.00 | 27.01 | 514.00 | 27.01 | 514.00 | 27.01 |
April | 485.00 | 28.47 | 485.00 | 28.47 | 485.00 | 28.47 |
May | 508.00 | 27.00 | 508.00 | 27.00 | 508.00 | 27.00 |
June | 496.00 | 27.01 | 496.00 | 27.01 | 496.00 | 27.01 |
July | 497.00 | 27.01 | 497.00 | 27.01 | 497.00 | 27.01 |
August | 514.00 | 32.01 | 514.00 | 32.01 | 514.00 | 32.01 |
September | 485.00 | 27.00 | 485.00 | 27.00 | 485.00 | 27.00 |
October | 502.00 | 27.02 | 502.00 | 27.02 | 502.00 | 27.02 |
November | 489.00 | 27.01 | 489.00 | 27.01 | 489.00 | 27.01 |
December | 497.00 | 28.18 | 497.00 | 28.18 | 497.00 | 28.18 |
Annual Sum or Average | 5894.00 | 27.66 | 5943.00 | 27.66 | 5894.00 | 27.66 |
Minimum of Months | 453.00 | 27.00 | 454.00 | 27.00 | 453.00 | 27.00 |
Maximum of Months | 514.00 | 32.01 | 514.00 | 32.01 | 514.00 | 32.01 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00006 | 18.41761 | 0.72733 | 16.26678 |
February | 454.00000 | 27.00002 | 17.22551 | 0.75342 | 17.10018 |
March | 514.00000 | 27.00005 | 17.51109 | 0.81491 | 19.08955 |
April | 485.00000 | 27.00037 | 19.56179 | 0.88511 | 21.61341 |
May | 508.00000 | 27.00040 | 22.01944 | 0.14837 | 5.54133 |
June | 496.00000 | 27.00056 | 24.13198 | 0.25593 | 6.43254 |
July | 497.00000 | 27.00039 | 24.74680 | 0.30240 | 6.96138 |
August | 514.00000 | 27.20803 | 24.49352 | 0.44011 | 9.51045 |
September | 485.00000 | 27.00030 | 21.98585 | 0.17279 | 5.74176 |
October | 502.00000 | 27.00010 | 19.04408 | 0.80942 | 18.91540 |
November | 489.00000 | 27.00005 | 19.78349 | 0.83286 | 19.72827 |
December | 497.00000 | 27.00033 | 14.63775 | 0.80609 | 18.85906 |
Annual Sum or Average | 5943.00000 | 27.01821 | 20.32151 | 0.57751 | 13.77722 |
Minimum of Months | 454.00000 | 27.00002 | 14.63775 | 0.14837 | 5.54133 |
Maximum of Months | 514.00000 | 27.20803 | 24.74680 | 0.88511 | 21.61341 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.99889 | 18.44243 | 0.62548 | 13.40906 |
February | 454.00000 | 27.00002 | 17.21052 | 0.62196 | 13.35857 |
March | 514.00000 | 27.00004 | 17.49890 | 0.67803 | 14.84914 |
April | 485.00000 | 27.00006 | 19.55019 | 0.71687 | 16.00813 |
May | 508.00000 | 27.00035 | 22.05517 | 0.06692 | 5.24888 |
June | 496.00000 | 27.00054 | 24.14702 | 0.17765 | 5.75614 |
July | 497.00000 | 27.00040 | 24.75580 | 0.19959 | 5.90912 |
August | 514.00000 | 27.12045 | 24.58055 | 0.25235 | 6.68085 |
September | 485.00000 | 27.00028 | 22.00936 | 0.09986 | 5.37903 |
October | 502.00000 | 27.00010 | 19.03081 | 0.70553 | 15.64523 |
November | 489.00000 | 27.00005 | 19.77165 | 0.68697 | 15.06845 |
December | 497.00000 | 26.99999 | 14.62414 | 0.59928 | 12.78650 |
Annual Sum or Average | 5943.00000 | 27.01048 | 20.33173 | 0.45094 | 10.81456 |
Minimum of Months | 454.00000 | 26.99889 | 14.62414 | 0.06692 | 5.24888 |
Maximum of Months | 514.00000 | 27.12045 | 24.75580 | 0.71687 | 16.00813 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 26.56046 | 18.97116 | 0.45792 | 11.04972 |
February | 454.00000 | 27.00014 | 17.22568 | 0.55174 | 11.75074 |
March | 514.00000 | 27.00004 | 17.51759 | 0.62216 | 13.48951 |
April | 485.00000 | 27.00006 | 19.56455 | 0.65952 | 14.59703 |
May | 508.00000 | 26.99505 | 22.09513 | 0.03112 | 5.39957 |
June | 496.00000 | 27.00056 | 24.15424 | 0.18945 | 5.93171 |
July | 497.00000 | 27.00041 | 24.76421 | 0.21067 | 6.07779 |
August | 514.00000 | 27.10514 | 24.60325 | 0.25443 | 6.79191 |
September | 485.00000 | 27.00026 | 22.02530 | 0.08295 | 5.47938 |
October | 502.00000 | 27.00010 | 19.06668 | 0.64301 | 14.02951 |
November | 489.00000 | 27.00005 | 19.79201 | 0.60811 | 13.02852 |
December | 497.00000 | 26.99999 | 14.63050 | 0.52075 | 11.05290 |
Annual Sum or Average | 5943.00000 | 26.97168 | 20.39356 | 0.40122 | 9.86982 |
Minimum of Months | 454.00000 | 26.56046 | 14.63050 | 0.03112 | 5.39957 |
Maximum of Months | 514.00000 | 27.10514 | 24.76421 | 0.65952 | 14.59703 |
Report: OccupantComfortDataSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 27.00011 | 29.99969 | 1.03263 | 27.52699 |
February | 454.00000 | 27.01541 | 29.99820 | 1.19148 | 34.84542 |
March | 514.00000 | 27.00998 | 29.99862 | 1.34598 | 42.66329 |
April | 485.00000 | 28.47080 | 29.98986 | 1.80193 | 66.79156 |
May | 508.00000 | 27.00134 | 30.00324 | 0.46935 | 9.64685 |
June | 496.00000 | 27.01093 | 30.00296 | 0.71516 | 15.77230 |
July | 497.00000 | 27.00531 | 30.00445 | 0.91576 | 22.72028 |
August | 514.00000 | 32.01009 | 29.86603 | 2.60378 | 93.38834 |
September | 485.00000 | 27.00318 | 30.00165 | 0.53918 | 11.17163 |
October | 502.00000 | 27.01564 | 30.00071 | 1.24320 | 37.39218 |
November | 489.00000 | 27.00973 | 29.99974 | 1.37604 | 44.24378 |
December | 497.00000 | 28.18434 | 30.02124 | 1.74934 | 64.21342 |
Annual Sum or Average | 5943.00000 | 27.65829 | 29.99015 | 1.25183 | 39.32641 |
Minimum of Months | 454.00000 | 27.00011 | 29.86603 | 0.46935 | 9.64685 |
Maximum of Months | 514.00000 | 32.01009 | 30.02124 | 2.60378 | 93.38834 |
Report: OccupantComfortDataSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.40544 | 17.50158 | 0.29129 | 7.22052 |
February | 454.00000 | 24.40555 | 16.31437 | 0.27954 | 7.06507 |
March | 514.00000 | 24.33570 | 16.10976 | 0.27262 | 6.81797 |
April | 485.00000 | 24.44451 | 19.99980 | 0.32879 | 7.67374 |
May | 508.00000 | 24.46507 | 24.45559 | -0.4936 | 11.04738 |
June | 496.00000 | 24.44711 | 33.90289 | -0.4142 | 9.53642 |
July | 497.00000 | 24.59058 | 36.46945 | -0.3530 | 8.73234 |
August | 514.00000 | 24.48285 | 34.53595 | -0.3782 | 9.09752 |
September | 485.00000 | 24.54643 | 24.40908 | -0.4430 | 10.32743 |
October | 502.00000 | 24.57177 | 18.37020 | 0.35719 | 8.37168 |
November | 489.00000 | 24.55372 | 19.02416 | 0.35488 | 8.28264 |
December | 497.00000 | 24.38189 | 12.78996 | 0.26532 | 7.06986 |
Annual Sum or Average | 5943.00000 | 24.46914 | 22.88551 | 0.00278 | 8.44556 |
Minimum of Months | 454.00000 | 24.33570 | 12.78996 | -0.4936 | 6.81797 |
Maximum of Months | 514.00000 | 24.59058 | 36.46945 | 0.35719 | 11.04738 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 24.15909 | 19.37933 | 0.24325 | 6.46007 |
February | 454.00000 | 24.17635 | 17.86796 | 0.23745 | 6.43785 |
March | 514.00000 | 24.20344 | 17.35405 | 0.26204 | 6.57337 |
April | 485.00000 | 24.36715 | 21.21842 | 0.33425 | 7.68124 |
May | 508.00000 | 24.31448 | 25.54884 | -0.5134 | 11.06719 |
June | 496.00000 | 24.24595 | 35.24401 | -0.4310 | 9.30464 |
July | 497.00000 | 24.28859 | 37.67047 | -0.3939 | 8.65781 |
August | 514.00000 | 24.21698 | 36.18486 | -0.4003 | 8.68196 |
September | 485.00000 | 24.31566 | 25.89958 | -0.4904 | 10.63801 |
October | 502.00000 | 24.34810 | 19.46139 | 0.31438 | 7.37967 |
November | 489.00000 | 24.32968 | 20.15215 | 0.31066 | 7.28937 |
December | 497.00000 | 24.26341 | 13.98176 | 0.24359 | 6.54104 |
Annual Sum or Average | 5943.00000 | 24.26909 | 24.22459 | -0.0263 | 8.06865 |
Minimum of Months | 454.00000 | 24.15909 | 13.98176 | -0.5134 | 6.43785 |
Maximum of Months | 514.00000 | 24.36715 | 37.67047 | 0.33425 | 11.06719 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.35537 | 21.21934 | 0.02613 | 5.78127 |
February | 454.00000 | 23.17781 | 19.59073 | -0.0310 | 6.09729 |
March | 514.00000 | 23.51802 | 19.00938 | 0.06291 | 5.76288 |
April | 485.00000 | 23.71348 | 23.39140 | 0.13682 | 5.87448 |
May | 508.00000 | 24.18054 | 26.21761 | -0.5923 | 12.83729 |
June | 496.00000 | 24.17784 | 35.45450 | -0.4868 | 10.28561 |
July | 497.00000 | 24.21364 | 37.86108 | -0.4585 | 9.75037 |
August | 514.00000 | 24.22181 | 36.02850 | -0.4688 | 9.94651 |
September | 485.00000 | 24.19708 | 26.23114 | -0.5610 | 12.10165 |
October | 502.00000 | 23.91646 | 20.73209 | 0.18264 | 6.09997 |
November | 489.00000 | 23.63028 | 22.28836 | 0.10672 | 5.67558 |
December | 497.00000 | 22.88736 | 16.34247 | -0.1255 | 6.94427 |
Annual Sum or Average | 5943.00000 | 23.77056 | 25.41685 | -0.1858 | 8.11395 |
Minimum of Months | 454.00000 | 22.88736 | 16.34247 | -0.5923 | 5.67558 |
Maximum of Months | 514.00000 | 24.22181 | 37.86108 | 0.18264 | 12.83729 |
Report: OccupantComfortDataSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.63796 | 23.12906 | -0.4076 | 11.78059 |
February | 454.00000 | 21.82494 | 21.14542 | -0.3763 | 10.74357 |
March | 514.00000 | 22.48500 | 20.32745 | -0.1998 | 8.84570 |
April | 485.00000 | 22.59724 | 24.53515 | -0.1396 | 8.71959 |
May | 508.00000 | 23.83530 | 26.83318 | -0.7180 | 17.16270 |
June | 496.00000 | 24.18549 | 35.36607 | -0.4687 | 9.93109 |
July | 497.00000 | 24.24184 | 37.75823 | -0.4360 | 9.34551 |
August | 514.00000 | 24.21056 | 36.06265 | -0.4612 | 9.80185 |
September | 485.00000 | 24.03485 | 26.40199 | -0.6203 | 14.25685 |
October | 502.00000 | 22.87801 | 22.35899 | -0.0853 | 7.07623 |
November | 489.00000 | 22.18056 | 24.67621 | -0.2606 | 8.10442 |
December | 497.00000 | 21.36666 | 17.54632 | -0.5142 | 13.64590 |
Annual Sum or Average | 5943.00000 | 22.96680 | 26.39238 | -0.3910 | 10.78687 |
Minimum of Months | 454.00000 | 21.36666 | 17.54632 | -0.7180 | 7.07623 |
Maximum of Months | 514.00000 | 24.24184 | 37.75823 | -0.0853 | 17.16270 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.17061 | 21.07816 | -0.2610 | 7.74380 |
February | 454.00000 | 22.11034 | 19.14031 | -0.2841 | 8.35151 |
March | 514.00000 | 22.92689 | 18.15371 | -0.0791 | 6.53475 |
April | 485.00000 | 23.37666 | 21.59358 | 0.06422 | 6.05285 |
May | 508.00000 | 24.06031 | 25.37129 | -0.6189 | 13.91354 |
June | 496.00000 | 24.31717 | 34.26462 | -0.3761 | 8.59356 |
July | 497.00000 | 24.41305 | 36.71266 | -0.3251 | 8.03027 |
August | 514.00000 | 24.25047 | 35.45429 | -0.3874 | 8.72697 |
September | 485.00000 | 24.14533 | 25.54448 | -0.5667 | 12.96533 |
October | 502.00000 | 23.24873 | 20.54296 | 0.01533 | 6.16064 |
November | 489.00000 | 22.78552 | 21.80673 | -0.0993 | 6.23696 |
December | 497.00000 | 22.24361 | 14.97629 | -0.2817 | 8.67384 |
Annual Sum or Average | 5943.00000 | 23.34686 | 24.60655 | -0.2670 | 8.50114 |
Minimum of Months | 454.00000 | 22.11034 | 14.97629 | -0.6189 | 6.05285 |
Maximum of Months | 514.00000 | 24.41305 | 36.71266 | 0.06422 | 13.91354 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.35450 | 20.02567 | -0.1911 | 7.52603 |
February | 454.00000 | 22.35971 | 18.02793 | -0.1939 | 8.57474 |
March | 514.00000 | 22.86070 | 17.46232 | -0.0449 | 7.59608 |
April | 485.00000 | 23.08628 | 21.42343 | 0.04502 | 7.05825 |
May | 508.00000 | 24.05285 | 24.94746 | -0.5435 | 12.81894 |
June | 496.00000 | 24.32884 | 33.98670 | -0.2786 | 7.83656 |
July | 497.00000 | 24.43298 | 36.57775 | -0.2408 | 7.91642 |
August | 514.00000 | 24.16154 | 35.40173 | -0.3335 | 8.70479 |
September | 485.00000 | 24.19260 | 25.10641 | -0.4594 | 11.51076 |
October | 502.00000 | 23.18320 | 19.89478 | 0.04221 | 7.49713 |
November | 489.00000 | 22.66900 | 21.13067 | -0.0971 | 7.01597 |
December | 497.00000 | 22.03490 | 14.38614 | -0.3105 | 9.26296 |
Annual Sum or Average | 5943.00000 | 23.31761 | 24.08826 | -0.2177 | 8.61300 |
Minimum of Months | 454.00000 | 22.03490 | 14.38614 | -0.5435 | 7.01597 |
Maximum of Months | 514.00000 | 24.43298 | 36.57775 | 0.04502 | 12.81894 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 23.23951 | 18.83137 | 0.06556 | 8.54314 |
February | 454.00000 | 23.03230 | 17.15242 | 0.00509 | 9.52521 |
March | 514.00000 | 23.13005 | 17.16382 | 0.03323 | 8.49421 |
April | 485.00000 | 23.12866 | 21.46041 | 0.04001 | 7.37822 |
May | 508.00000 | 23.95793 | 25.32629 | -0.6226 | 14.74687 |
June | 496.00000 | 24.30111 | 34.21553 | -0.3619 | 8.63710 |
July | 497.00000 | 24.41655 | 36.62604 | -0.2969 | 8.08030 |
August | 514.00000 | 24.30317 | 35.15346 | -0.2961 | 7.99536 |
September | 485.00000 | 24.33063 | 24.85147 | -0.3933 | 10.74195 |
October | 502.00000 | 23.56992 | 19.30603 | 0.17202 | 9.27861 |
November | 489.00000 | 23.56711 | 19.78194 | 0.16551 | 8.90087 |
December | 497.00000 | 23.02307 | 13.44467 | -0.0305 | 9.22007 |
Annual Sum or Average | 5943.00000 | 23.67142 | 23.67149 | -0.1283 | 9.29852 |
Minimum of Months | 454.00000 | 23.02307 | 13.44467 | -0.6226 | 7.37822 |
Maximum of Months | 514.00000 | 24.41655 | 36.62604 | 0.17202 | 14.74687 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.80904 | 19.11618 | -0.0546 | 6.76018 |
February | 454.00000 | 23.09044 | 16.97318 | 0.01469 | 7.24556 |
March | 514.00000 | 23.78189 | 16.16544 | 0.21583 | 7.42553 |
April | 485.00000 | 24.23335 | 19.70135 | 0.37625 | 8.76366 |
May | 508.00000 | 24.27215 | 24.59048 | -0.4349 | 10.64555 |
June | 496.00000 | 24.48471 | 33.64068 | -0.1602 | 7.25859 |
July | 497.00000 | 24.60058 | 36.08899 | -0.1020 | 6.94727 |
August | 514.00000 | 24.52394 | 34.48009 | -0.0513 | 6.88007 |
September | 485.00000 | 24.37060 | 24.78826 | -0.3622 | 10.03391 |
October | 502.00000 | 23.83349 | 18.85562 | 0.23915 | 8.01847 |
November | 489.00000 | 23.82107 | 19.35041 | 0.21981 | 7.41652 |
December | 497.00000 | 23.64297 | 12.69436 | 0.12545 | 7.43476 |
Annual Sum or Average | 5943.00000 | 23.96095 | 23.09648 | 0.00160 | 7.90190 |
Minimum of Months | 454.00000 | 22.80904 | 12.69436 | -0.4349 | 6.76018 |
Maximum of Months | 514.00000 | 24.60058 | 36.08899 | 0.37625 | 10.64555 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.73978 | 22.64301 | -0.6368 | 15.50843 |
February | 454.00000 | 20.66469 | 20.45831 | -0.6745 | 16.56775 |
March | 514.00000 | 21.48742 | 19.92930 | -0.4484 | 11.99019 |
April | 485.00000 | 21.76826 | 24.17558 | -0.3369 | 10.44260 |
May | 508.00000 | 23.58796 | 26.48625 | -0.7996 | 20.28274 |
June | 496.00000 | 24.23738 | 34.24834 | -0.4320 | 9.40160 |
July | 497.00000 | 24.32715 | 36.76494 | -0.3885 | 8.87352 |
August | 514.00000 | 24.16162 | 35.58660 | -0.4785 | 10.30853 |
September | 485.00000 | 23.81327 | 26.11245 | -0.7019 | 17.35161 |
October | 502.00000 | 22.01255 | 22.37599 | -0.2951 | 8.89266 |
November | 489.00000 | 21.17950 | 23.91571 | -0.5121 | 11.81906 |
December | 497.00000 | 20.38259 | 16.51606 | -0.7804 | 20.05782 |
Annual Sum or Average | 5943.00000 | 22.37860 | 25.81695 | -0.5395 | 13.43397 |
Minimum of Months | 454.00000 | 20.38259 | 16.51606 | -0.7996 | 8.87352 |
Maximum of Months | 514.00000 | 24.32715 | 36.76494 | -0.2951 | 20.28274 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 427.00000 | 21.13176 | 21.01694 | -0.5186 | 12.63093 |
February | 385.00000 | 21.21734 | 18.83155 | -0.5080 | 14.29053 |
March | 433.00000 | 21.97232 | 18.20023 | -0.2910 | 11.19891 |
April | 410.00000 | 22.05333 | 22.83795 | -0.2243 | 10.58643 |
May | 430.00000 | 23.75537 | 25.58799 | -0.6666 | 17.34300 |
June | 418.00000 | 24.39263 | 33.50919 | -0.2797 | 8.22877 |
July | 422.00000 | 24.54653 | 35.95342 | -0.2275 | 8.45303 |
August | 433.00000 | 24.32244 | 34.83963 | -0.3189 | 9.03961 |
September | 410.00000 | 24.03820 | 25.12258 | -0.5379 | 14.23849 |
October | 427.00000 | 22.40046 | 20.63293 | -0.1703 | 9.38182 |
November | 417.00000 | 21.56143 | 22.24234 | -0.3969 | 10.36370 |
December | 422.00000 | 20.60388 | 15.25791 | -0.7036 | 18.13116 |
Annual Sum or Average | 5034.00000 | 22.67692 | 24.54522 | -0.4029 | 11.97459 |
Minimum of Months | 385.00000 | 20.60388 | 15.25791 | -0.7036 | 8.22877 |
Maximum of Months | 433.00000 | 24.54653 | 35.95342 | -0.1703 | 18.13116 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.93707 | 19.17328 | -0.0114 | 9.84847 |
February | 454.00000 | 22.60036 | 17.57937 | -0.1112 | 11.89006 |
March | 514.00000 | 22.61687 | 17.91732 | -0.1046 | 10.55129 |
April | 485.00000 | 22.29421 | 22.83677 | -0.1708 | 9.99455 |
May | 508.00000 | 23.69127 | 25.94965 | -0.7244 | 18.47866 |
June | 496.00000 | 24.23057 | 34.16654 | -0.4088 | 9.44736 |
July | 497.00000 | 24.36097 | 36.58258 | -0.3439 | 8.78716 |
August | 514.00000 | 24.29771 | 34.97928 | -0.3447 | 8.82075 |
September | 485.00000 | 24.22752 | 24.92739 | -0.4335 | 12.08355 |
October | 502.00000 | 23.21831 | 19.79540 | 0.08302 | 10.41158 |
November | 489.00000 | 23.16751 | 20.36758 | 0.05995 | 9.93673 |
December | 497.00000 | 22.27508 | 14.25112 | -0.2338 | 12.41195 |
Annual Sum or Average | 5943.00000 | 23.33304 | 24.10414 | -0.2300 | 11.05533 |
Minimum of Months | 454.00000 | 22.27508 | 14.25112 | -0.7244 | 8.78716 |
Maximum of Months | 514.00000 | 24.36097 | 36.58258 | 0.08302 | 18.47866 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 21.40166 | 20.84252 | -0.4357 | 11.50134 |
February | 454.00000 | 21.37986 | 18.81195 | -0.4525 | 12.91109 |
March | 514.00000 | 21.97510 | 18.47635 | -0.2740 | 10.52330 |
April | 485.00000 | 22.11567 | 22.89878 | -0.2008 | 9.68149 |
May | 508.00000 | 23.65685 | 25.80515 | -0.6911 | 18.25770 |
June | 496.00000 | 24.28398 | 33.99788 | -0.3081 | 8.74617 |
July | 497.00000 | 24.34553 | 36.59902 | -0.2962 | 8.29438 |
August | 514.00000 | 24.26027 | 35.13481 | -0.3348 | 8.87210 |
September | 485.00000 | 23.94927 | 25.47721 | -0.5586 | 14.91024 |
October | 502.00000 | 22.40719 | 20.82840 | -0.1456 | 8.88016 |
November | 489.00000 | 21.78343 | 22.12431 | -0.3229 | 9.37636 |
December | 497.00000 | 20.94049 | 15.22374 | -0.6028 | 15.78246 |
Annual Sum or Average | 5943.00000 | 22.72030 | 24.73912 | -0.3848 | 11.46788 |
Minimum of Months | 454.00000 | 20.94049 | 15.22374 | -0.6911 | 8.29438 |
Maximum of Months | 514.00000 | 24.34553 | 36.59902 | -0.1456 | 18.25770 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.13621 | 23.48112 | -0.8416 | 22.82463 |
February | 454.00000 | 20.23652 | 21.09737 | -0.8330 | 21.97400 |
March | 514.00000 | 21.04669 | 20.31763 | -0.5949 | 15.89981 |
April | 485.00000 | 21.14523 | 25.11147 | -0.5143 | 15.65536 |
May | 508.00000 | 23.15874 | 27.20156 | -0.9517 | 26.95993 |
June | 496.00000 | 24.20891 | 34.28940 | -0.4293 | 9.66976 |
July | 497.00000 | 24.30403 | 36.86295 | -0.3847 | 9.20127 |
August | 514.00000 | 24.09255 | 35.85851 | -0.4922 | 10.98857 |
September | 485.00000 | 23.57112 | 26.38883 | -0.7874 | 21.32484 |
October | 502.00000 | 21.31437 | 23.22551 | -0.4957 | 13.23423 |
November | 489.00000 | 20.50193 | 24.82499 | -0.7239 | 18.61054 |
December | 497.00000 | 19.95120 | 16.80048 | -0.9475 | 26.58590 |
Annual Sum or Average | 5943.00000 | 21.98841 | 26.33572 | -0.6650 | 17.70358 |
Minimum of Months | 454.00000 | 19.95120 | 16.80048 | -0.9517 | 9.20127 |
Maximum of Months | 514.00000 | 24.30403 | 36.86295 | -0.3847 | 26.95993 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.50968 | 22.29462 | -0.7105 | 18.93834 |
February | 454.00000 | 20.84661 | 19.79341 | -0.6383 | 17.64024 |
March | 514.00000 | 21.73375 | 18.83152 | -0.3799 | 13.34759 |
April | 485.00000 | 21.65454 | 23.74294 | -0.3408 | 14.38146 |
May | 508.00000 | 23.51444 | 25.91969 | -0.7465 | 20.35858 |
June | 496.00000 | 24.32263 | 33.71102 | -0.2641 | 7.99275 |
July | 497.00000 | 24.45366 | 36.34454 | -0.2204 | 8.36088 |
August | 514.00000 | 24.23944 | 34.99350 | -0.3074 | 8.88263 |
September | 485.00000 | 23.89968 | 25.27725 | -0.5681 | 15.43481 |
October | 502.00000 | 22.02191 | 21.49862 | -0.2931 | 11.58557 |
November | 489.00000 | 21.00376 | 23.40106 | -0.5707 | 14.76924 |
December | 497.00000 | 20.22058 | 16.05955 | -0.8457 | 23.09128 |
Annual Sum or Average | 5943.00000 | 22.38306 | 25.20395 | -0.4891 | 14.53464 |
Minimum of Months | 454.00000 | 20.22058 | 16.05955 | -0.8457 | 7.99275 |
Maximum of Months | 514.00000 | 24.45366 | 36.34454 | -0.2204 | 23.09128 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 22.10669 | 20.25819 | -0.2570 | 12.87048 |
February | 454.00000 | 22.02314 | 18.42900 | -0.2934 | 14.37300 |
March | 514.00000 | 22.16565 | 18.40342 | -0.2491 | 12.88789 |
April | 485.00000 | 21.67335 | 23.85953 | -0.3447 | 14.61066 |
May | 508.00000 | 23.28959 | 26.58827 | -0.8671 | 24.54400 |
June | 496.00000 | 24.15816 | 34.30587 | -0.4172 | 10.08185 |
July | 497.00000 | 24.30065 | 36.76330 | -0.3496 | 9.37944 |
August | 514.00000 | 24.21450 | 35.28001 | -0.3597 | 9.51345 |
September | 485.00000 | 24.04156 | 25.12463 | -0.4992 | 14.68650 |
October | 502.00000 | 22.67565 | 20.55780 | -0.0817 | 12.44706 |
November | 489.00000 | 22.49351 | 21.29990 | -0.1465 | 11.56551 |
December | 497.00000 | 21.55564 | 14.88609 | -0.4510 | 16.87328 |
Annual Sum or Average | 5943.00000 | 22.89985 | 24.70384 | -0.3605 | 13.65139 |
Minimum of Months | 454.00000 | 21.55564 | 14.88609 | -0.8671 | 9.37944 |
Maximum of Months | 514.00000 | 24.30065 | 36.76330 | -0.0817 | 24.54400 |
Report: OccupantComfortDataSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 502.00000 | 20.76570 | 21.73569 | -0.6358 | 17.36696 |
February | 454.00000 | 20.95982 | 19.48526 | -0.5967 | 16.64395 |
March | 514.00000 | 21.58202 | 18.82697 | -0.4015 | 13.21234 |
April | 485.00000 | 21.55039 | 23.79216 | -0.3562 | 13.81547 |
May | 508.00000 | 23.28500 | 26.34057 | -0.8213 | 23.72511 |
June | 496.00000 | 24.21278 | 34.14214 | -0.3153 | 9.36781 |
July | 497.00000 | 24.27995 | 36.78642 | -0.3036 | 8.91588 |
August | 514.00000 | 24.15861 | 35.44504 | -0.3556 | 9.72471 |
September | 485.00000 | 23.71234 | 25.68989 | -0.6378 | 18.22978 |
October | 502.00000 | 21.86751 | 21.52606 | -0.3039 | 11.63958 |
November | 489.00000 | 21.23054 | 22.84944 | -0.4978 | 13.28952 |
December | 497.00000 | 20.49815 | 15.65684 | -0.7580 | 20.84071 |
Annual Sum or Average | 5943.00000 | 22.35495 | 25.24171 | -0.4978 | 14.71237 |
Minimum of Months | 454.00000 | 20.49815 | 15.65684 | -0.8213 | 8.91588 |
Maximum of Months | 514.00000 | 24.27995 | 36.78642 | -0.3036 | 23.72511 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.528204E+10 | 73712.96 | 20-JAN-14:00 | 85.63 | 0.319239E+11 | 0.00 | 0.372060E+11 | 0.57 | 7.33 | 20-JAN-14:30 | 0.00 | 0.00 |
February | 0.287980E+10 | 59422.69 | 18-FEB-13:30 | 92.95 | 0.144318E+11 | 0.00 | 0.173116E+11 | 0.64 | 6.84 | 18-FEB-13:30 | 0.00 | 0.00 |
March | 0.126020E+11 | 78933.35 | 14-MAR-13:00 | 134.24 | 0.759631E+11 | 0.00 | 0.885651E+11 | 0.93 | 7.40 | 15-MAR-16:00 | 0.00 | 0.00 |
April | 0.128978E+11 | 76334.77 | 20-APR-12:50 | 140.65 | 0.771142E+11 | 0.00 | 0.900120E+11 | 1.01 | 7.37 | 20-APR-12:50 | 0.00 | 0.00 |
May | 0.419354E+11 | 86861.53 | 31-MAY-12:20 | 270.75 | 0.267181E+12 | 0.00 | 0.309117E+12 | 2.09 | 7.40 | 09-MAY-15:30 | 0.00 | 0.00 |
June | 0.108739E+12 | 110900.22 | 26-JUN-15:10 | 532.87 | 0.741546E+12 | 0.00 | 0.850284E+12 | 4.63 | 7.57 | 14-JUN-05:02 | 0.00 | 0.00 |
July | 0.113207E+12 | 104529.87 | 18-JUL-15:10 | 587.20 | 0.764834E+12 | 0.00 | 0.878040E+12 | 4.84 | 7.56 | 17-JUL-05:02 | 0.00 | 0.00 |
August | 0.108696E+12 | 107366.23 | 16-AUG-15:10 | 627.45 | 0.736581E+12 | 0.00 | 0.845277E+12 | 5.03 | 7.77 | 04-AUG-05:04 | 0.00 | 0.00 |
September | 0.797997E+11 | 103971.22 | 12-SEP-15:50 | 412.15 | 0.531423E+12 | 0.00 | 0.611223E+12 | 3.53 | 7.52 | 12-SEP-15:50 | 0.00 | 0.00 |
October | 0.205127E+11 | 85937.91 | 10-OCT-13:30 | 166.28 | 0.130614E+12 | 0.00 | 0.151126E+12 | 1.23 | 7.37 | 17-OCT-14:10 | 0.00 | 0.00 |
November | 0.855281E+10 | 74128.06 | 06-NOV-14:20 | 106.28 | 0.526233E+11 | 0.00 | 0.611761E+11 | 0.76 | 7.34 | 09-NOV-12:00 | 0.00 | 0.00 |
December | 0.539584E+10 | 74043.93 | 01-DEC-14:00 | 84.44 | 0.314487E+11 | 0.00 | 0.368445E+11 | 0.56 | 7.29 | 01-DEC-14:00 | 0.00 | 0.00 |
Annual Sum or Average | 0.520500E+12 | 3240.89 | 0.345568E+13 | 0.00 | 0.397618E+13 | 2.16 | 0.00 | 0.00 | ||||
Minimum of Months | 0.287980E+10 | 59422.69 | 84.44 | 0.144318E+11 | 0.00 | 0.173116E+11 | 0.56 | 6.84 | 0.00 | 0.00 | ||
Maximum of Months | 0.113207E+12 | 110900.22 | 627.45 | 0.764834E+12 | 0.00 | 0.878040E+12 | 5.03 | 7.77 | 0.00 | 0.00 |
Report: ChillerReportMonthly
For: COOLSYS1 CHILLER2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCHILLER ELECTRICITY ENERGY [J] | CHILLER ELECTRICITY RATE {Maximum} [W] | CHILLER ELECTRICITY RATE {TIMESTAMP} | CHILLER ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | CHILLER EVAPORATOR COOLING ENERGY [J] | CHILLER EVAPORATOR COOLING RATE [] | CHILLER CONDENSER HEAT TRANSFER ENERGY [J] | CHILLER COP [W/W] | CHILLER COP {Maximum} [W/W] | CHILLER COP {TIMESTAMP} | CHILLER PART LOAD RATIO [] | CHILLER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.678468E+09 | 78933.35 | 14-MAR-13:00 | 2.50 | 0.492115E+10 | 0.00 | 0.559962E+10 | 0.02 | 7.31 | 14-MAR-13:00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 |
May | 0.704371E+10 | 86861.53 | 31-MAY-12:20 | 25.00 | 0.507184E+11 | 0.00 | 0.577621E+11 | 0.24 | 7.34 | 31-MAY-12:20 | 0.00 | 0.00 |
June | 0.524002E+11 | 110900.22 | 26-JUN-15:10 | 169.64 | 0.383683E+12 | 0.00 | 0.436083E+12 | 1.72 | 7.57 | 14-JUN-05:02 | 0.00 | 0.00 |
July | 0.487860E+11 | 104529.87 | 18-JUL-15:10 | 159.59 | 0.356064E+12 | 0.00 | 0.404850E+12 | 1.56 | 7.56 | 17-JUL-05:02 | 0.00 | 0.00 |
August | 0.490836E+11 | 107366.23 | 16-AUG-15:10 | 159.06 | 0.359181E+12 | 0.00 | 0.408265E+12 | 1.56 | 7.77 | 04-AUG-05:04 | 0.00 | 0.00 |
September | 0.271352E+11 | 103971.22 | 12-SEP-15:50 | 92.26 | 0.197219E+12 | 0.00 | 0.224354E+12 | 0.93 | 7.52 | 12-SEP-15:50 | 0.00 | 0.00 |
October | 0.271284E+10 | 85937.91 | 10-OCT-13:30 | 9.67 | 0.196193E+11 | 0.00 | 0.223322E+11 | 0.09 | 7.34 | 10-OCT-13:20 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 |
Annual Sum or Average | 0.187840E+12 | 617.71 | 0.137140E+13 | 0.00 | 0.155924E+13 | 0.51 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.524002E+11 | 110900.22 | 169.64 | 0.383683E+12 | 0.00 | 0.436083E+12 | 1.72 | 7.77 | 0.00 | 0.00 |
Report: TowerReportMonthly
For: CENTRAL TOWER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.182966E+11 | 744.00 | 49248.27 | 19-JAN-12:40 | 246670.29 | 20-JAN-16:20 | 22.17 | 18.39 | 15.60 |
February | 0.241501E+11 | 672.00 | 49248.27 | 17-FEB-13:30 | 404523.93 | 26-FEB-17:12 | 25.05 | 18.40 | 15.60 |
March | 0.642974E+11 | 744.00 | 49248.27 | 06-MAR-12:50 | 683259.97 | 31-MAR-24:00 | 28.62 | 18.97 | 15.60 |
April | 0.835311E+11 | 720.00 | 49248.27 | 05-APR-16:00 | 733223.74 | 08-APR-18:12 | 31.99 | 19.42 | 15.60 |
May | 0.730024E+11 | 744.00 | 49248.27 | 03-MAY-13:00 | 385365.38 | 31-MAY-23:50 | 24.09 | 19.94 | 15.60 |
June | 0.125785E+12 | 720.00 | 49248.27 | 01-JUN-00:10 | 561797.98 | 30-JUN-23:33 | 33.87 | 26.54 | 15.60 |
July | 0.131422E+12 | 744.00 | 49248.27 | 01-JUL-00:05 | 692950.68 | 31-JUL-24:00 | 39.00 | 28.75 | 15.60 |
August | 0.131907E+12 | 744.00 | 49248.27 | 01-AUG-00:10 | 774617.18 | 26-AUG-19:32 | 42.69 | 29.50 | 15.60 |
September | 0.103236E+12 | 720.00 | 49248.27 | 01-SEP-00:05 | 374846.02 | 30-SEP-24:00 | 26.90 | 22.60 | 15.60 |
October | 0.591121E+11 | 744.00 | 49248.27 | 01-OCT-10:22 | 510282.38 | 31-OCT-23:45 | 26.04 | 19.11 | 15.60 |
November | 0.519452E+11 | 720.00 | 49248.27 | 03-NOV-11:40 | 579845.27 | 07-NOV-16:10 | 28.40 | 18.73 | 15.60 |
December | 0.593593E+11 | 744.00 | 49248.27 | 01-DEC-09:40 | 734285.40 | 03-DEC-16:03 | 31.14 | 18.73 | 15.60 |
Annual Sum or Average | 0.926044E+12 | 8760.00 | 30.03 | 21.61 | 15.60 | ||||
Minimum of Months | 0.182966E+11 | 672.00 | 49248.27 | 246670.29 | 22.17 | 18.39 | 15.60 | ||
Maximum of Months | 0.131907E+12 | 744.00 | 49248.27 | 774617.18 | 42.69 | 29.50 | 15.60 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 9471113.90 | 20.33 | 254.70 | 20-JAN-15:50 | 628633.41 | 20-JAN-14:30 | 21.05 | 20.98 | 2.48 |
February | 2911161.94 | 7.75 | 238.96 | 18-FEB-14:30 | 480100.83 | 18-FEB-13:30 | 21.05 | 21.01 | 1.90 |
March | 32789822.95 | 57.23 | 610.12 | 13-MAR-14:10 | 985670.59 | 13-MAR-14:50 | 21.18 | 21.00 | 5.59 |
April | 37849121.10 | 59.83 | 589.39 | 12-APR-13:30 | 800283.44 | 19-APR-13:30 | 21.16 | 20.99 | 6.25 |
May | 0.282946E+09 | 190.22 | 2197.14 | 31-MAY-17:10 | 1048894.25 | 31-MAY-12:20 | 21.81 | 21.19 | 16.58 |
June | 0.238308E+10 | 440.07 | 15556.41 | 15-JUN-13:20 | 1100733.12 | 23-JUN-15:00 | 23.00 | 21.18 | 36.19 |
July | 0.433386E+10 | 470.87 | 15556.41 | 19-JUL-10:10 | 1099693.50 | 10-JUL-10:20 | 22.96 | 21.14 | 38.53 |
August | 0.273911E+10 | 440.75 | 15556.41 | 03-AUG-10:30 | 1100649.38 | 14-AUG-10:40 | 22.86 | 21.08 | 38.46 |
September | 0.684734E+09 | 344.13 | 2415.10 | 12-SEP-16:20 | 1099819.63 | 06-SEP-15:10 | 22.55 | 21.20 | 28.35 |
October | 67372758.58 | 88.65 | 670.55 | 07-OCT-16:01 | 989303.39 | 10-OCT-12:50 | 21.28 | 20.99 | 8.53 |
November | 22011659.27 | 36.30 | 660.25 | 09-NOV-12:50 | 856947.33 | 07-NOV-15:00 | 21.07 | 20.95 | 4.06 |
December | 10979612.13 | 21.29 | 373.69 | 02-DEC-15:00 | 627153.80 | 01-DEC-14:20 | 21.06 | 20.99 | 2.71 |
Annual Sum or Average | 0.106071E+11 | 2177.45 | 21.76 | 21.06 | 15.89 | ||||
Minimum of Months | 2911161.94 | 7.75 | 238.96 | 480100.83 | 21.05 | 20.95 | 1.90 | ||
Maximum of Months | 0.433386E+10 | 470.87 | 15556.41 | 1100733.12 | 23.00 | 21.20 | 38.53 |
Report: TowerReportMonthly
For: TOWERWATERSYS COOLTOWER 2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING TOWER FAN ELECTRICITY ENERGY [J] | COOLING TOWER FAN ELECTRICITY ENERGY {HOURS NON-ZERO} [HOURS] | COOLING TOWER FAN ELECTRICITY RATE {Maximum} [W] | COOLING TOWER FAN ELECTRICITY RATE {TIMESTAMP} | COOLING TOWER HEAT TRANSFER RATE {Maximum} [W] | COOLING TOWER HEAT TRANSFER RATE {TIMESTAMP} | COOLING TOWER INLET TEMPERATURE [C] | COOLING TOWER OUTLET TEMPERATURE [C] | COOLING TOWER MASS FLOW RATE [kg/s] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 21.05 | 21.05 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 21.05 | 21.05 | 0.00 |
March | 2598284.52 | 1.50 | 610.12 | 13-MAR-14:10 | 985670.59 | 13-MAR-14:50 | 21.18 | 21.17 | 0.11 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 01-APR-00:10 | 21.16 | 21.16 | 0.00 |
May | 53892931.16 | 13.67 | 2129.69 | 31-MAY-13:00 | 1048894.25 | 31-MAY-12:20 | 21.81 | 21.73 | 0.97 |
June | 0.117800E+10 | 141.37 | 15556.41 | 15-JUN-13:20 | 1100733.12 | 23-JUN-15:00 | 23.00 | 22.17 | 10.36 |
July | 0.222549E+10 | 128.83 | 15556.41 | 19-JUL-10:10 | 1099693.50 | 10-JUL-10:20 | 22.96 | 22.24 | 9.14 |
August | 0.145834E+10 | 138.37 | 15556.41 | 03-AUG-10:30 | 1100649.38 | 14-AUG-10:40 | 22.86 | 22.06 | 9.81 |
September | 0.243431E+09 | 74.17 | 2415.10 | 12-SEP-16:20 | 1099819.63 | 06-SEP-15:10 | 22.55 | 22.09 | 5.43 |
October | 8504414.30 | 7.17 | 433.20 | 11-OCT-13:00 | 989303.39 | 10-OCT-12:50 | 21.28 | 21.24 | 0.51 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 21.07 | 21.07 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 01-DEC-00:10 | 21.06 | 21.06 | 0.00 |
Annual Sum or Average | 0.517026E+10 | 505.07 | 21.76 | 21.51 | 3.04 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 21.05 | 21.05 | 0.00 | ||
Maximum of Months | 0.222549E+10 | 141.37 | 15556.41 | 1100733.12 | 23.00 | 22.24 | 10.36 |
Report: BoilerReportMonthly
For: HEATSYS1 BOILER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO {Maximum} [] | BOILER PART LOAD RATIO {TIMESTAMP} | |
January | 0.228628E+12 | 0.00 | 437.07 | 1223642.34 | 30-JAN-06:01 | 0.00 | 28.74 | 58.67 | 0.43 | 0.00 | 0.03 | 0.46 | 30-JAN-06:01 |
February | 0.256198E+12 | 0.00 | 406.26 | 1472100.42 | 13-FEB-06:02 | 0.00 | 28.68 | 59.56 | 0.53 | 0.00 | 0.04 | 0.55 | 13-FEB-06:02 |
March | 0.156171E+12 | 0.00 | 334.43 | 1275163.21 | 21-MAR-04:01 | 0.00 | 26.66 | 50.09 | 0.28 | 0.00 | 0.02 | 0.48 | 21-MAR-04:01 |
April | 0.890454E+11 | 0.00 | 254.12 | 1188559.86 | 04-APR-04:01 | 0.00 | 25.74 | 44.54 | 0.17 | 0.00 | 0.01 | 0.44 | 04-APR-04:01 |
May | 0.574299E+10 | 0.00 | 49.81 | 1227356.24 | 01-MAY-05:01 | 0.00 | 23.48 | 27.14 | 0.01 | 0.00 | 0.00 | 0.46 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 22.63 | 22.63 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 22.63 | 22.63 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 22.63 | 22.63 | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.382473E+10 | 0.00 | 23.17 | 665467.67 | 22-SEP-05:02 | 0.00 | 23.30 | 25.06 | 0.01 | 0.00 | 0.00 | 0.25 | 22-SEP-05:02 |
October | 0.109213E+12 | 0.00 | 224.32 | 1187798.02 | 24-OCT-05:01 | 0.00 | 25.03 | 41.11 | 0.20 | 0.00 | 0.02 | 0.44 | 24-OCT-05:01 |
November | 0.176594E+12 | 0.00 | 329.24 | 1389521.94 | 27-NOV-05:01 | 0.00 | 26.25 | 50.45 | 0.33 | 0.00 | 0.03 | 0.52 | 27-NOV-05:01 |
December | 0.389941E+12 | 0.00 | 494.60 | 1660739.20 | 27-DEC-06:01 | 0.00 | 30.60 | 63.15 | 0.80 | 0.00 | 0.05 | 0.62 | 27-DEC-06:01 |
Annual Sum or Average | 0.141536E+13 | 0.00 | 2553.03 | 0.00 | 25.52 | 40.54 | 0.23 | 0.00 | 0.02 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 22.63 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.389941E+12 | 0.00 | 494.60 | 1660739.20 | 0.00 | 30.60 | 63.15 | 0.80 | 0.00 | 0.05 | 0.62 |
Report: BoilerReportMonthly
For: CENTRAL BOILER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportBOILER HEATING ENERGY [J] | BOILER GAS CONSUMPTION [] | BOILER HEATING ENERGY {HOURS NON-ZERO} [HOURS] | BOILER HEATING RATE {Maximum} [W] | BOILER HEATING RATE {TIMESTAMP} | BOILER GAS CONSUMPTION RATE [] | BOILER INLET TEMPERATURE [C] | BOILER OUTLET TEMPERATURE [C] | BOILER MASS FLOW RATE [kg/s] | BOILER ANCILLARY ELECTRICITY RATE [W] | BOILER PART LOAD RATIO [] | BOILER PART LOAD RATIO [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 22.17 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 25.05 | 25.05 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 28.62 | 28.62 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 31.99 | 31.99 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 24.09 | 24.09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 33.87 | 33.87 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 39.00 | 39.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 42.69 | 42.69 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 26.90 | 26.90 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 26.04 | 26.04 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 28.40 | 28.40 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 31.14 | 31.14 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 30.03 | 30.03 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.17 | 22.17 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.69 | 42.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.283962E+10 | 0.00 | 32.83 | 0.283962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 54823.91 | 20-JAN-14:00 | 54823.91 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.944835E+09 | 0.00 | 20.50 | 0.944835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32907.08 | 18-FEB-13:30 | 32907.08 | 18-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.890292E+10 | 0.00 | 85.85 | 0.890292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 91526.55 | 13-MAR-16:00 | 91526.55 | 13-MAR-16:00 | 0.00 | 0.00 | 0.00 |
April | 0.978636E+10 | 0.00 | 96.90 | 0.978636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77662.88 | 19-APR-13:40 | 77662.88 | 19-APR-13:40 | 0.00 | 0.00 | 0.00 |
May | 0.313647E+11 | 0.00 | 247.72 | 0.313647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100467.44 | 31-MAY-15:20 | 100467.44 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.104988E+12 | 0.00 | 508.39 | 0.104775E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 143482.25 | 26-JUN-14:40 | 143482.25 | 26-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.112260E+12 | 0.00 | 561.67 | 0.109519E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 136432.40 | 17-JUL-10:20 | 136432.40 | 17-JUL-10:20 | 0.00 | 0.00 | 0.00 |
August | 0.120327E+12 | 0.00 | 606.42 | 0.119327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 143771.40 | 16-AUG-14:30 | 143771.40 | 16-AUG-14:30 | 0.00 | 0.00 | 0.00 |
September | 0.688340E+11 | 0.00 | 384.47 | 0.688340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 120773.38 | 12-SEP-15:50 | 120773.38 | 12-SEP-15:50 | 0.00 | 0.00 | 0.00 |
October | 0.143030E+11 | 0.00 | 123.21 | 0.143030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 109938.02 | 10-OCT-16:00 | 109938.02 | 10-OCT-16:00 | 0.00 | 0.00 | 0.00 |
November | 0.570420E+10 | 0.00 | 53.37 | 0.570420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76415.62 | 06-NOV-14:00 | 76415.62 | 06-NOV-14:00 | 0.00 | 0.00 | 0.00 |
December | 0.333768E+10 | 0.00 | 36.64 | 0.333768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 63734.96 | 01-DEC-14:00 | 63734.96 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.483592E+12 | 0.00 | 2757.97 | 0.479639E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.944835E+09 | 0.00 | 20.50 | 0.944835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 32907.08 | 32907.08 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.120327E+12 | 0.00 | 606.42 | 0.119327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 143771.40 | 143771.40 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.233997E+11 | 0.00 | 83.97 | 0.233997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 437975.19 | 20-JAN-14:10 | 437975.19 | 20-JAN-14:10 | 0.00 | 0.00 | 0.00 |
February | 0.897062E+10 | 0.00 | 91.12 | 0.897062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336576.99 | 18-FEB-14:00 | 336576.99 | 18-FEB-14:00 | 0.00 | 0.00 | 0.00 |
March | 0.674521E+11 | 0.00 | 130.50 | 0.674521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 706436.03 | 14-MAR-13:00 | 706436.03 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.571348E+11 | 0.00 | 132.89 | 0.571348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 521767.83 | 20-APR-13:00 | 521767.83 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.263572E+12 | 0.00 | 253.23 | 0.263572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 907494.53 | 31-MAY-16:00 | 907494.53 | 31-MAY-16:00 | 0.00 | 0.00 | 0.00 |
June | 0.898283E+12 | 0.00 | 459.31 | 0.896784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1288050.03 | 26-JUN-15:10 | 1288050.03 | 26-JUN-15:10 | 0.00 | 0.00 | 0.00 |
July | 0.905863E+12 | 0.00 | 468.46 | 0.887949E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1195684.52 | 17-JUL-10:30 | 1195684.52 | 17-JUL-10:30 | 0.00 | 0.00 | 0.00 |
August | 0.870009E+12 | 0.00 | 455.42 | 0.866203E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1273398.48 | 04-AUG-05:02 | 1245403.03 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.595871E+12 | 0.00 | 375.78 | 0.595871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1124472.73 | 12-SEP-16:00 | 1124472.73 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.117840E+12 | 0.00 | 156.63 | 0.117840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 894101.05 | 11-OCT-15:00 | 894101.05 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.409706E+11 | 0.00 | 101.54 | 0.409706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 571337.61 | 07-NOV-15:00 | 571337.61 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.218743E+11 | 0.00 | 79.54 | 0.218743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 421010.74 | 01-DEC-14:00 | 421010.74 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.387124E+13 | 0.00 | 2788.40 | 0.384802E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.897062E+10 | 0.00 | 79.54 | 0.897062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 336576.99 | 336576.99 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.905863E+12 | 0.00 | 468.46 | 0.896784E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 1288050.03 | 1288050.03 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.174577E+10 | 0.00 | 29.32 | 0.174577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40880.31 | 20-JAN-14:00 | 40880.31 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 0.630822E+09 | 0.00 | 17.72 | 0.630822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30806.55 | 18-FEB-13:30 | 30806.55 | 18-FEB-13:30 | 0.00 | 0.00 | 0.00 |
March | 0.620200E+10 | 0.00 | 79.89 | 0.620200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73083.34 | 14-MAR-13:10 | 73083.34 | 14-MAR-13:10 | 0.00 | 0.00 | 0.00 |
April | 0.588128E+10 | 0.00 | 87.84 | 0.588128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 58750.10 | 20-APR-13:00 | 58750.10 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.272054E+11 | 0.00 | 229.18 | 0.272054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 111611.51 | 31-MAY-15:20 | 111611.51 | 31-MAY-15:20 | 0.00 | 0.00 | 0.00 |
June | 0.101902E+12 | 0.00 | 451.96 | 0.101792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164541.01 | 26-JUN-14:40 | 164541.01 | 26-JUN-14:40 | 0.00 | 0.00 | 0.00 |
July | 0.100797E+12 | 0.00 | 464.73 | 0.990265E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 144328.34 | 17-JUL-14:00 | 144328.34 | 17-JUL-14:00 | 0.00 | 0.00 | 0.00 |
August | 0.967176E+11 | 0.00 | 448.76 | 0.963874E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 155132.51 | 16-AUG-15:10 | 155132.51 | 16-AUG-15:10 | 0.00 | 0.00 | 0.00 |
September | 0.623306E+11 | 0.00 | 362.47 | 0.623306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 130266.02 | 12-SEP-16:00 | 130266.02 | 12-SEP-16:00 | 0.00 | 0.00 | 0.00 |
October | 0.105823E+11 | 0.00 | 113.33 | 0.105823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 100824.49 | 11-OCT-15:00 | 100824.49 | 11-OCT-15:00 | 0.00 | 0.00 | 0.00 |
November | 0.331335E+10 | 0.00 | 43.46 | 0.331335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55281.35 | 07-NOV-15:00 | 55281.35 | 07-NOV-15:00 | 0.00 | 0.00 | 0.00 |
December | 0.168163E+10 | 0.00 | 32.03 | 0.168163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39112.20 | 01-DEC-14:00 | 39112.20 | 01-DEC-14:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.418990E+12 | 0.00 | 2360.69 | 0.416779E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.630822E+09 | 0.00 | 17.72 | 0.630822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 30806.55 | 30806.55 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.101902E+12 | 0.00 | 464.73 | 0.101792E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 164541.01 | 164541.01 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL RUNTIME FRACTION [] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE [] | COOLING COIL ELECTRICITY RATE [] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.101590E+10 | 0.00 | 18.00 | 0.101590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 29858.76 | 20-JAN-14:00 | 29858.76 | 20-JAN-14:00 | 0.00 | 0.00 | 0.00 |
February | 81446874.48 | 0.00 | 3.50 | 81446874.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10584.25 | 18-FEB-13:00 | 10584.25 | 18-FEB-13:00 | 0.00 | 0.00 | 0.00 |
March | 0.344417E+10 | 0.00 | 45.42 | 0.344417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 53474.31 | 14-MAR-13:00 | 53474.31 | 14-MAR-13:00 | 0.00 | 0.00 | 0.00 |
April | 0.397344E+10 | 0.00 | 60.67 | 0.397344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 39577.02 | 20-APR-13:00 | 39577.02 | 20-APR-13:00 | 0.00 | 0.00 | 0.00 |
May | 0.180353E+11 | 0.00 | 170.02 | 0.180317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 57399.28 | 31-MAY-14:00 | 57399.28 | 31-MAY-14:00 | 0.00 | 0.00 | 0.00 |
June | 0.577863E+11 | 0.00 | 357.41 | 0.577609E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78550.85 | 26-JUN-15:00 | 78550.85 | 26-JUN-15:00 | 0.00 | 0.00 | 0.00 |
July | 0.586508E+11 | 0.00 | 359.50 | 0.580517E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 78691.06 | 17-JUL-10:00 | 78691.06 | 17-JUL-10:00 | 0.00 | 0.00 | 0.00 |
August | 0.629855E+11 | 0.00 | 387.52 | 0.627297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 96858.01 | 20-AUG-13:31 | 96858.01 | 20-AUG-13:31 | 0.00 | 0.00 | 0.00 |
September | 0.423431E+11 | 0.00 | 302.91 | 0.423419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97303.42 | 10-SEP-15:54 | 97303.42 | 10-SEP-15:54 | 0.00 | 0.00 | 0.00 |
October | 0.721101E+10 | 0.00 | 75.68 | 0.721101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 68290.14 | 10-OCT-14:00 | 68290.14 | 10-OCT-14:00 | 0.00 | 0.00 | 0.00 |
November | 0.266115E+10 | 0.00 | 31.87 | 0.266115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 51440.94 | 06-NOV-13:10 | 51440.94 | 06-NOV-13:10 | 0.00 | 0.00 | 0.00 |
December | 0.143717E+10 | 0.00 | 20.38 | 0.143717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40095.56 | 04-DEC-12:00 | 40095.56 | 04-DEC-12:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259625E+12 | 0.00 | 1832.87 | 0.258740E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 81446874.48 | 0.00 | 3.50 | 81446874.48 | 0.00 | 0.00 | 0.00 | 0.00 | 10584.25 | 10584.25 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.629855E+11 | 0.00 | 387.52 | 0.627297E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 97303.42 | 97303.42 | 0.00 | 0.00 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.395501E+12 | 0.100694E+12 | 744.00 | 0.345171E+12 | 0.503298E+11 | 0.00 | 0.38 | 20-JAN-14:00 | 0.34 | 05-JAN-08:00 | 152603.64 | 19-JAN-22:10 | 133322.71 | 20-JAN-14:10 | 19913.52 | 19-JAN-12:00 | 44871.62 | 20-JAN-14:00 | 0.00 |
February | 0.611597E+12 | 0.147663E+12 | 672.00 | 0.533130E+12 | 0.784671E+11 | 0.00 | 0.61 | 18-FEB-13:00 | 0.57 | 01-FEB-07:10 | 259014.13 | 17-FEB-22:03 | 225319.74 | 27-FEB-22:03 | 34210.95 | 17-FEB-11:00 | 72095.81 | 18-FEB-13:20 | 0.00 |
March | 0.960785E+12 | 0.226807E+12 | 744.00 | 0.840716E+12 | 0.120069E+12 | 0.00 | 1.00 | 31-MAR-23:10 | 0.79 | 04-MAR-18:00 | 461509.32 | 31-MAR-24:00 | 404206.06 | 31-MAR-24:00 | 58449.35 | 31-MAR-23:10 | 114352.17 | 14-MAR-13:00 | 0.00 |
April | 0.121253E+13 | 0.274025E+12 | 720.00 | 0.104885E+13 | 0.163680E+12 | 0.00 | 1.00 | 01-APR-00:10 | 0.42 | 30-APR-24:00 | 479334.10 | 12-APR-21:03 | 410367.43 | 21-APR-00:07 | 74541.01 | 18-APR-20:50 | 134471.11 | 19-APR-14:00 | 0.00 |
May | 0.403487E+12 | 0.108133E+12 | 744.00 | 0.353735E+12 | 0.497520E+11 | 0.00 | 0.60 | 31-MAY-23:30 | 0.36 | 03-MAY-06:10 | 250948.78 | 31-MAY-24:00 | 220597.50 | 31-MAY-24:00 | 30351.27 | 31-MAY-24:00 | 64923.05 | 31-MAY-23:20 | 0.00 |
June | 0.646633E+12 | 0.203499E+12 | 720.00 | 0.584783E+12 | 0.618493E+11 | 0.00 | 0.84 | 30-JUN-23:13 | 0.59 | 01-JUN-06:10 | 342784.42 | 30-JUN-24:00 | 312693.97 | 30-JUN-24:00 | 34794.97 | 23-JUN-06:10 | 117099.77 | 26-JUN-15:00 | 0.00 |
July | 0.932490E+12 | 0.299525E+12 | 744.00 | 0.850859E+12 | 0.816318E+11 | 0.00 | 1.00 | 31-JUL-23:05 | 0.81 | 03-JUL-06:10 | 440614.02 | 31-JUL-24:00 | 398027.54 | 31-JUL-24:00 | 48826.02 | 03-JUL-07:40 | 152480.01 | 16-JUL-13:00 | 0.00 |
August | 0.123079E+13 | 0.359817E+12 | 744.00 | 0.107804E+13 | 0.152748E+12 | 0.00 | 1.00 | 01-AUG-00:10 | 0.45 | 31-AUG-24:00 | 486346.88 | 17-AUG-02:55 | 412669.88 | 17-AUG-03:03 | 79169.50 | 21-AUG-17:00 | 178028.91 | 16-AUG-16:00 | 0.00 |
September | 0.393007E+12 | 0.115016E+12 | 720.00 | 0.348541E+12 | 0.444654E+11 | 0.00 | 0.59 | 30-SEP-24:00 | 0.36 | 22-SEP-06:10 | 253329.76 | 30-SEP-24:00 | 221131.19 | 30-SEP-24:00 | 32310.18 | 30-SEP-23:10 | 60909.19 | 30-SEP-24:00 | 0.00 |
October | 0.686245E+12 | 0.169530E+12 | 744.00 | 0.599500E+12 | 0.867457E+11 | 0.00 | 0.81 | 31-OCT-23:45 | 0.58 | 31-OCT-06:10 | 358387.06 | 31-OCT-23:45 | 311907.49 | 31-OCT-23:45 | 46485.50 | 31-OCT-24:00 | 88758.31 | 11-OCT-14:00 | 0.00 |
November | 0.935721E+12 | 0.218827E+12 | 720.00 | 0.816929E+12 | 0.118792E+12 | 0.00 | 0.85 | 07-NOV-15:00 | 0.79 | 01-NOV-06:10 | 366660.44 | 07-NOV-22:03 | 319609.24 | 07-NOV-15:00 | 48834.72 | 10-NOV-11:00 | 109836.76 | 07-NOV-15:00 | 0.00 |
December | 0.125644E+13 | 0.278120E+12 | 744.00 | 0.108372E+13 | 0.172720E+12 | 0.00 | 1.00 | 01-DEC-00:10 | 1.00 | 23-DEC-18:00 | 480820.76 | 03-DEC-17:10 | 410505.92 | 03-DEC-16:57 | 73344.25 | 14-DEC-16:40 | 133754.27 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.966522E+13 | 0.250166E+13 | 8760.00 | 0.848397E+13 | 0.118125E+13 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.393007E+12 | 0.100694E+12 | 672.00 | 0.345171E+12 | 0.444654E+11 | 0.00 | 0.38 | 0.34 | 152603.64 | 133322.71 | 19913.52 | 44871.62 | 0.00 | ||||||
Maximum of Months | 0.125644E+13 | 0.359817E+12 | 744.00 | 0.108372E+13 | 0.172720E+12 | 0.00 | 1.00 | 1.00 | 486346.88 | 412669.88 | 79169.50 | 178028.91 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.457984E+10 | 0.126590E+10 | 744.00 | 0.457121E+10 | 8629595.39 | 0.00 | 0.35 | 23-JAN-16:20 | 0.09 | 05-JAN-07:05 | 2815.10 | 23-JAN-16:30 | 2815.10 | 23-JAN-16:30 | 105.87 | 10-JAN-16:20 | 812.14 | 23-JAN-16:00 | 0.00 |
February | 0.878910E+10 | 0.229413E+10 | 672.00 | 0.878499E+10 | 4111306.17 | 0.00 | 0.56 | 26-FEB-16:42 | 0.32 | 06-FEB-07:10 | 4761.58 | 17-FEB-17:00 | 4736.27 | 17-FEB-17:00 | 88.23 | 28-FEB-16:50 | 1301.92 | 26-FEB-16:23 | 0.00 |
March | 0.153951E+11 | 0.391304E+10 | 744.00 | 0.153836E+11 | 11537061.22 | 0.00 | 0.85 | 31-MAR-24:00 | 0.55 | 20-MAR-06:10 | 7813.64 | 31-MAR-24:00 | 7813.64 | 31-MAR-24:00 | 155.94 | 17-MAR-15:10 | 2275.60 | 13-MAR-17:00 | 0.00 |
April | 0.201796E+11 | 0.494838E+10 | 720.00 | 0.201527E+11 | 26897455.40 | 0.00 | 1.00 | 08-APR-17:20 | 0.31 | 30-APR-24:00 | 8831.25 | 08-APR-18:14 | 8831.25 | 08-APR-18:14 | 242.35 | 28-APR-16:10 | 2695.94 | 19-APR-14:00 | 0.00 |
May | 0.594423E+10 | 0.167079E+10 | 744.00 | 0.589132E+10 | 52906694.01 | 0.00 | 0.48 | 31-MAY-24:00 | 0.19 | 03-MAY-06:10 | 4171.26 | 31-MAY-24:00 | 4151.03 | 31-MAY-24:00 | 221.39 | 22-MAY-14:10 | 1106.24 | 31-MAY-23:30 | 0.00 |
June | 0.112425E+11 | 0.366450E+10 | 720.00 | 0.111364E+11 | 0.106059E+09 | 0.00 | 0.73 | 30-JUN-23:13 | 0.45 | 10-JUN-06:40 | 6023.09 | 30-JUN-24:00 | 6023.09 | 30-JUN-24:00 | 329.54 | 20-JUN-17:00 | 2386.89 | 26-JUN-15:10 | 0.00 |
July | 0.166513E+11 | 0.551964E+10 | 744.00 | 0.165185E+11 | 0.132728E+09 | 0.00 | 0.93 | 01-JUL-18:35 | 0.66 | 05-JUL-21:00 | 7923.90 | 31-JUL-24:00 | 7923.90 | 31-JUL-24:00 | 504.03 | 31-JUL-16:00 | 3166.04 | 16-JUL-13:00 | 0.00 |
August | 0.220239E+11 | 0.713896E+10 | 744.00 | 0.219139E+11 | 0.110007E+09 | 0.00 | 1.00 | 02-AUG-12:20 | 0.34 | 31-AUG-24:00 | 9126.39 | 05-AUG-18:53 | 9104.03 | 05-AUG-18:50 | 519.70 | 29-AUG-15:00 | 3740.27 | 16-AUG-16:00 | 0.00 |
September | 0.606291E+10 | 0.186675E+10 | 720.00 | 0.602322E+10 | 39686216.99 | 0.00 | 0.46 | 30-SEP-24:00 | 0.17 | 22-SEP-06:10 | 4010.31 | 30-SEP-24:00 | 4010.31 | 30-SEP-24:00 | 226.20 | 01-SEP-14:40 | 1350.31 | 10-SEP-17:11 | 0.00 |
October | 0.105966E+11 | 0.279203E+10 | 744.00 | 0.105782E+11 | 18470310.50 | 0.00 | 0.64 | 09-OCT-16:42 | 0.35 | 31-OCT-06:10 | 5300.97 | 09-OCT-16:43 | 5300.97 | 09-OCT-16:43 | 142.71 | 03-OCT-11:00 | 1703.89 | 11-OCT-14:00 | 0.00 |
November | 0.149170E+11 | 0.369966E+10 | 720.00 | 0.149030E+11 | 13992721.13 | 0.00 | 0.82 | 07-NOV-16:00 | 0.56 | 01-NOV-06:10 | 6862.25 | 05-NOV-16:14 | 6862.25 | 05-NOV-16:14 | 138.17 | 09-NOV-17:00 | 2181.00 | 07-NOV-16:00 | 0.00 |
December | 0.201918E+11 | 0.498881E+10 | 744.00 | 0.201918E+11 | 0.00 | 0.00 | 1.00 | 03-DEC-15:12 | 0.75 | 23-DEC-07:03 | 8758.62 | 03-DEC-16:15 | 8758.62 | 03-DEC-16:15 | 0.00 | 17-DEC-16:03 | 2734.95 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.156574E+12 | 0.437626E+11 | 8760.00 | 0.156049E+12 | 0.525026E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.457984E+10 | 0.126590E+10 | 672.00 | 0.457121E+10 | 0.00 | 0.00 | 0.35 | 0.09 | 2815.10 | 2815.10 | 0.00 | 812.14 | 0.00 | ||||||
Maximum of Months | 0.220239E+11 | 0.713896E+10 | 744.00 | 0.219139E+11 | 0.132728E+09 | 0.00 | 1.00 | 0.75 | 9126.39 | 9104.03 | 519.70 | 3740.27 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.266695E+11 | 0.765616E+10 | 739.78 | 0.265879E+11 | 81590107.78 | 0.00 | 0.33 | 23-JAN-16:30 | 0.00 | 02-JAN-07:10 | 25505.92 | 23-JAN-16:40 | 25505.92 | 23-JAN-16:40 | 1062.84 | 10-JAN-16:20 | 7310.54 | 23-JAN-16:00 | 0.00 |
February | 0.666591E+11 | 0.177310E+11 | 672.00 | 0.666178E+11 | 41293675.43 | 0.00 | 0.52 | 17-FEB-17:00 | 0.16 | 06-FEB-07:10 | 43991.95 | 17-FEB-17:00 | 43682.58 | 17-FEB-17:00 | 881.10 | 28-FEB-16:50 | 11186.44 | 26-FEB-16:33 | 0.00 |
March | 0.131503E+12 | 0.339197E+11 | 744.00 | 0.131388E+12 | 0.115038E+09 | 0.00 | 0.83 | 31-MAR-23:50 | 0.41 | 20-MAR-06:10 | 72276.93 | 31-MAR-23:40 | 72276.93 | 31-MAR-23:40 | 1554.20 | 17-MAR-15:10 | 21518.99 | 13-MAR-17:00 | 0.00 |
April | 0.176643E+12 | 0.439006E+11 | 720.00 | 0.176374E+12 | 0.269129E+09 | 0.00 | 0.99 | 08-APR-17:31 | 0.14 | 30-APR-24:00 | 82333.74 | 08-APR-18:00 | 82333.74 | 08-APR-18:00 | 2400.39 | 28-APR-16:10 | 25099.31 | 19-APR-14:00 | 0.00 |
May | 0.509274E+11 | 0.144795E+11 | 744.00 | 0.504058E+11 | 0.521607E+09 | 0.00 | 0.48 | 31-MAY-23:50 | 0.09 | 01-MAY-06:10 | 39361.15 | 31-MAY-24:00 | 39141.92 | 31-MAY-24:00 | 2197.19 | 22-MAY-14:10 | 10467.88 | 31-MAY-23:20 | 0.00 |
June | 0.105815E+12 | 0.345930E+11 | 720.00 | 0.104757E+12 | 0.105745E+10 | 0.00 | 0.74 | 30-JUN-23:13 | 0.42 | 10-JUN-06:40 | 58669.72 | 30-JUN-24:00 | 58669.72 | 30-JUN-24:00 | 3237.03 | 20-JUN-17:00 | 22846.47 | 26-JUN-18:00 | 0.00 |
July | 0.157940E+12 | 0.524333E+11 | 744.00 | 0.156615E+12 | 0.132537E+10 | 0.00 | 0.93 | 01-JUL-18:35 | 0.64 | 29-JUL-06:10 | 74771.73 | 31-JUL-24:00 | 74771.73 | 31-JUL-24:00 | 4981.06 | 31-JUL-16:00 | 29816.88 | 16-JUL-13:00 | 0.00 |
August | 0.205234E+12 | 0.669088E+11 | 744.00 | 0.204136E+12 | 0.109819E+10 | 0.00 | 1.00 | 02-AUG-12:50 | 0.29 | 31-AUG-24:00 | 85358.15 | 05-AUG-18:12 | 85035.30 | 05-AUG-18:11 | 5048.21 | 29-AUG-15:00 | 35778.47 | 16-AUG-16:00 | 0.00 |
September | 0.537465E+11 | 0.167189E+11 | 720.00 | 0.533551E+11 | 0.391417E+09 | 0.00 | 0.45 | 10-SEP-17:22 | 0.12 | 22-SEP-06:10 | 36436.67 | 30-SEP-24:00 | 36436.67 | 30-SEP-24:00 | 2211.67 | 01-SEP-14:40 | 12843.29 | 10-SEP-17:22 | 0.00 |
October | 0.894818E+11 | 0.238909E+11 | 744.00 | 0.892985E+11 | 0.183314E+09 | 0.00 | 0.60 | 09-OCT-16:42 | 0.22 | 30-OCT-06:10 | 47509.05 | 09-OCT-16:43 | 47509.05 | 09-OCT-16:43 | 1409.51 | 03-OCT-11:00 | 16054.93 | 11-OCT-14:00 | 0.00 |
November | 0.126320E+12 | 0.317849E+11 | 720.00 | 0.126180E+12 | 0.140014E+09 | 0.00 | 0.80 | 07-NOV-16:00 | 0.46 | 02-NOV-06:10 | 63327.51 | 07-NOV-16:10 | 63327.51 | 07-NOV-16:10 | 1348.67 | 09-NOV-17:00 | 20382.33 | 07-NOV-16:00 | 0.00 |
December | 0.166559E+12 | 0.419647E+11 | 744.00 | 0.166559E+12 | 0.00 | 0.00 | 0.94 | 01-DEC-15:50 | 0.60 | 26-DEC-04:01 | 77960.22 | 01-DEC-16:00 | 77960.22 | 01-DEC-16:00 | 0.00 | 29-DEC-05:27 | 24702.51 | 02-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.135750E+13 | 0.385981E+12 | 8755.78 | 0.135227E+13 | 0.522441E+10 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.266695E+11 | 0.765616E+10 | 672.00 | 0.265879E+11 | 0.00 | 0.00 | 0.33 | 0.00 | 25505.92 | 25505.92 | 0.00 | 7310.54 | 0.00 | ||||||
Maximum of Months | 0.205234E+12 | 0.669088E+11 | 744.00 | 0.204136E+12 | 0.132537E+10 | 0.00 | 1.00 | 0.64 | 85358.15 | 85035.30 | 5048.21 | 35778.47 | 0.00 |
Report: DXReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE [] | |
January | 0.121823E+10 | 0.358718E+09 | 442.39 | 0.121148E+10 | 6754175.83 | 0.00 | 0.32 | 20-JAN-16:20 | 0.00 | 01-JAN-00:05 | 2543.58 | 20-JAN-16:30 | 2543.58 | 20-JAN-16:30 | 105.37 | 10-JAN-16:20 | 709.62 | 20-JAN-16:00 | 0.00 |
February | 0.510167E+10 | 0.138073E+10 | 656.71 | 0.509766E+10 | 4012578.76 | 0.00 | 0.51 | 17-FEB-17:00 | 0.00 | 05-FEB-18:35 | 4392.75 | 17-FEB-17:00 | 4364.89 | 17-FEB-17:00 | 86.16 | 28-FEB-17:00 | 1085.50 | 17-FEB-17:00 | 0.00 |
March | 0.118079E+11 | 0.308885E+10 | 744.00 | 0.117966E+11 | 11290751.69 | 0.00 | 0.82 | 13-MAR-17:00 | 0.23 | 20-MAR-03:01 | 7043.92 | 31-MAR-23:20 | 7043.92 | 31-MAR-23:20 | 154.76 | 17-MAR-15:10 | 2174.98 | 13-MAR-17:00 | 0.00 |
April | 0.162951E+11 | 0.410621E+10 | 719.00 | 0.162683E+11 | 26760862.63 | 0.00 | 0.98 | 08-APR-17:31 | 0.00 | 30-APR-23:05 | 8261.85 | 08-APR-17:47 | 8261.85 | 08-APR-17:47 | 240.41 | 28-APR-16:10 | 2549.72 | 19-APR-14:00 | 0.00 |
May | 0.458453E+10 | 0.132131E+10 | 734.86 | 0.453286E+10 | 51676855.81 | 0.00 | 0.47 | 31-MAY-23:30 | 0.00 | 01-MAY-00:10 | 3904.90 | 31-MAY-23:50 | 3882.61 | 31-MAY-24:00 | 220.42 | 22-MAY-14:00 | 1043.74 | 31-MAY-23:20 | 0.00 |
June | 0.106108E+11 | 0.348436E+10 | 720.00 | 0.105051E+11 | 0.105683E+09 | 0.00 | 0.73 | 30-JUN-23:13 | 0.38 | 10-JUN-06:40 | 5893.91 | 30-JUN-24:00 | 5893.91 | 30-JUN-24:00 | 325.69 | 20-JUN-17:00 | 2347.60 | 26-JUN-18:00 | 0.00 |
July | 0.158393E+11 | 0.527784E+10 | 744.00 | 0.157069E+11 | 0.132396E+09 | 0.00 | 0.93 | 01-JUL-18:35 | 0.61 | 29-JUL-06:10 | 7388.04 | 31-JUL-24:00 | 7388.04 | 31-JUL-24:00 | 499.84 | 31-JUL-16:00 | 3072.85 | 16-JUL-13:00 | 0.00 |
August | 0.205286E+11 | 0.672126E+10 | 744.00 | 0.204190E+11 | 0.109609E+09 | 0.00 | 1.00 | 02-AUG-15:20 | 0.29 | 31-AUG-24:00 | 8653.51 | 13-AUG-18:52 | 8653.51 | 13-AUG-18:52 | 505.90 | 29-AUG-15:00 | 3650.93 | 16-AUG-16:00 | 0.00 |
September | 0.511072E+10 | 0.161061E+10 | 719.50 | 0.507173E+10 | 38986611.17 | 0.00 | 0.47 | 10-SEP-17:35 | 0.00 | 22-SEP-06:10 | 3434.07 | 10-SEP-17:35 | 3434.07 | 10-SEP-17:35 | 222.95 | 01-SEP-14:40 | 1382.25 | 10-SEP-17:11 | 0.00 |
October | 0.761194E+10 | 0.206748E+10 | 744.00 | 0.759402E+10 | 17913900.07 | 0.00 | 0.59 | 11-OCT-16:30 | 0.03 | 30-OCT-03:23 | 4729.04 | 08-OCT-16:50 | 4729.04 | 08-OCT-16:50 | 142.36 | 03-OCT-11:00 | 1627.66 | 11-OCT-14:00 | 0.00 |
November | 0.109230E+11 | 0.279675E+10 | 720.00 | 0.109093E+11 | 13773984.41 | 0.00 | 0.78 | 07-NOV-16:00 | 0.33 | 30-NOV-04:15 | 6340.45 | 07-NOV-16:10 | 6340.45 | 07-NOV-16:10 | 134.42 | 09-NOV-17:00 | 2045.58 | 07-NOV-16:00 | 0.00 |
December | 0.147771E+11 | 0.378360E+10 | 744.00 | 0.147771E+11 | -0.0 | 0.00 | 0.92 | 01-DEC-15:50 | 0.45 | 25-DEC-06:50 | 7744.34 | 01-DEC-16:00 | 7744.34 | 01-DEC-16:00 | 0.00 | 26-DEC-00:20 | 2441.99 | 01-DEC-15:00 | 0.00 |
Annual Sum or Average | 0.124409E+12 | 0.359977E+11 | 8432.46 | 0.123890E+12 | 0.518858E+09 | 0.00 | 0.00 | ||||||||||||
Minimum of Months | 0.121823E+10 | 0.358718E+09 | 442.39 | 0.121148E+10 | -0.0 | 0.00 | 0.32 | 0.00 | 2543.58 | 2543.58 | 0.00 | 709.62 | 0.00 | ||||||
Maximum of Months | 0.205286E+11 | 0.672126E+10 | 744.00 | 0.204190E+11 | 0.132396E+09 | 0.00 | 1.00 | 0.61 | 8653.51 | 8653.51 | 505.90 | 3650.93 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.13 | 0.00 | 103.13 | 13.49 | 575.49 | 0.00 | 0.00 | 0.00 |
February | 129.63 | 0.00 | 129.63 | 17.45 | 578.72 | 0.00 | 0.00 | 0.00 |
March | 176.38 | 0.00 | 176.38 | 67.98 | 445.45 | 0.00 | 0.00 | 0.00 |
April | 221.51 | 1.23 | 220.28 | 107.14 | 394.56 | 0.00 | 0.00 | 0.00 |
May | 302.59 | 10.00 | 292.59 | 263.32 | 218.38 | 0.00 | 0.00 | 0.00 |
June | 331.82 | 36.79 | 295.03 | 439.15 | 117.69 | 0.00 | 0.00 | 0.00 |
July | 313.81 | 20.31 | 293.49 | 420.22 | 110.92 | 0.00 | 0.00 | 0.00 |
August | 249.77 | 5.91 | 243.86 | 316.38 | 129.53 | 0.00 | 0.00 | 0.00 |
September | 209.80 | 0.05 | 209.75 | 233.54 | 201.26 | 0.00 | 0.00 | 0.00 |
October | 150.27 | 0.00 | 150.27 | 73.91 | 431.06 | 0.00 | 0.00 | 0.00 |
November | 114.07 | 0.00 | 114.07 | 23.88 | 527.00 | 0.00 | 0.00 | 0.00 |
December | 96.50 | 0.00 | 96.50 | 10.44 | 654.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.31 | 6.21 | 194.10 | 166.40 | 364.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.50 | 0.00 | 96.50 | 10.44 | 110.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.82 | 36.79 | 295.03 | 439.15 | 654.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.13 | 0.00 | 103.13 | 13.49 | 575.49 | 0.00 | 0.00 | 0.00 |
February | 129.63 | 0.00 | 129.63 | 17.45 | 578.72 | 0.00 | 0.00 | 0.00 |
March | 176.38 | 0.00 | 176.38 | 67.98 | 445.45 | 0.00 | 0.00 | 0.00 |
April | 221.51 | 1.23 | 220.28 | 107.13 | 394.56 | 0.00 | 0.00 | 0.00 |
May | 302.59 | 10.00 | 292.59 | 263.31 | 218.38 | 0.00 | 0.00 | 0.00 |
June | 331.81 | 36.79 | 295.02 | 439.14 | 117.69 | 0.00 | 0.00 | 0.00 |
July | 313.80 | 20.31 | 293.49 | 420.21 | 110.92 | 0.00 | 0.00 | 0.00 |
August | 249.76 | 5.91 | 243.86 | 316.37 | 129.53 | 0.00 | 0.00 | 0.00 |
September | 209.80 | 0.05 | 209.75 | 233.54 | 201.26 | 0.00 | 0.00 | 0.00 |
October | 150.27 | 0.00 | 150.27 | 73.91 | 431.06 | 0.00 | 0.00 | 0.00 |
November | 114.07 | 0.00 | 114.07 | 23.88 | 527.00 | 0.00 | 0.00 | 0.00 |
December | 96.49 | 0.00 | 96.49 | 10.44 | 654.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.30 | 6.21 | 194.10 | 166.40 | 364.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.49 | 0.00 | 96.49 | 10.44 | 110.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.81 | 36.79 | 295.02 | 439.14 | 654.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.13 | 0.00 | 103.13 | 13.49 | 575.49 | 0.00 | 0.00 | 0.00 |
February | 129.63 | 0.00 | 129.63 | 17.45 | 578.72 | 0.00 | 0.00 | 0.00 |
March | 176.38 | 0.00 | 176.38 | 67.98 | 445.45 | 0.00 | 0.00 | 0.00 |
April | 221.51 | 1.23 | 220.28 | 107.13 | 394.56 | 0.00 | 0.00 | 0.00 |
May | 302.59 | 10.00 | 292.59 | 263.32 | 218.38 | 0.00 | 0.00 | 0.00 |
June | 331.81 | 36.79 | 295.03 | 439.15 | 117.69 | 0.00 | 0.00 | 0.00 |
July | 313.80 | 20.31 | 293.49 | 420.21 | 110.92 | 0.00 | 0.00 | 0.00 |
August | 249.76 | 5.91 | 243.86 | 316.37 | 129.53 | 0.00 | 0.00 | 0.00 |
September | 209.80 | 0.05 | 209.75 | 233.54 | 201.26 | 0.00 | 0.00 | 0.00 |
October | 150.27 | 0.00 | 150.27 | 73.91 | 431.06 | 0.00 | 0.00 | 0.00 |
November | 114.07 | 0.00 | 114.07 | 23.88 | 527.00 | 0.00 | 0.00 | 0.00 |
December | 96.49 | 0.00 | 96.49 | 10.44 | 654.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.30 | 6.21 | 194.10 | 166.40 | 364.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.49 | 0.00 | 96.49 | 10.44 | 110.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.81 | 36.79 | 295.03 | 439.15 | 654.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.13 | 0.00 | 103.13 | 13.49 | 575.49 | 0.00 | 0.00 | 0.00 |
February | 129.63 | 0.00 | 129.63 | 17.45 | 578.72 | 0.00 | 0.00 | 0.00 |
March | 176.38 | 0.00 | 176.38 | 67.98 | 445.45 | 0.00 | 0.00 | 0.00 |
April | 221.51 | 1.23 | 220.28 | 107.13 | 394.56 | 0.00 | 0.00 | 0.00 |
May | 302.59 | 10.00 | 292.59 | 263.31 | 218.38 | 0.00 | 0.00 | 0.00 |
June | 331.81 | 36.79 | 295.02 | 439.14 | 117.69 | 0.00 | 0.00 | 0.00 |
July | 313.80 | 20.31 | 293.49 | 420.21 | 110.92 | 0.00 | 0.00 | 0.00 |
August | 249.76 | 5.91 | 243.86 | 316.37 | 129.53 | 0.00 | 0.00 | 0.00 |
September | 209.80 | 0.05 | 209.75 | 233.54 | 201.26 | 0.00 | 0.00 | 0.00 |
October | 150.27 | 0.00 | 150.27 | 73.91 | 431.06 | 0.00 | 0.00 | 0.00 |
November | 114.07 | 0.00 | 114.07 | 23.88 | 527.00 | 0.00 | 0.00 | 0.00 |
December | 96.49 | 0.00 | 96.49 | 10.44 | 654.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.30 | 6.21 | 194.10 | 166.40 | 364.25 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.49 | 0.00 | 96.49 | 10.44 | 110.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.81 | 36.79 | 295.02 | 439.14 | 654.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 103.13 | 0.00 | 103.13 | 13.48 | 575.47 | 0.00 | 0.00 | 0.00 |
February | 129.62 | 0.00 | 129.62 | 17.45 | 578.70 | 0.00 | 0.00 | 0.00 |
March | 176.37 | 0.00 | 176.37 | 67.97 | 445.43 | 0.00 | 0.00 | 0.00 |
April | 221.50 | 1.23 | 220.27 | 107.13 | 394.55 | 0.00 | 0.00 | 0.00 |
May | 302.58 | 10.00 | 292.58 | 263.31 | 218.37 | 0.00 | 0.00 | 0.00 |
June | 331.80 | 36.78 | 295.01 | 439.13 | 117.69 | 0.00 | 0.00 | 0.00 |
July | 313.79 | 20.31 | 293.48 | 420.19 | 110.92 | 0.00 | 0.00 | 0.00 |
August | 249.75 | 5.91 | 243.85 | 316.36 | 129.52 | 0.00 | 0.00 | 0.00 |
September | 209.79 | 0.05 | 209.74 | 233.53 | 201.25 | 0.00 | 0.00 | 0.00 |
October | 150.26 | 0.00 | 150.26 | 73.91 | 431.04 | 0.00 | 0.00 | 0.00 |
November | 114.07 | 0.00 | 114.07 | 23.88 | 526.98 | 0.00 | 0.00 | 0.00 |
December | 96.49 | 0.00 | 96.49 | 10.44 | 654.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 200.30 | 6.20 | 194.09 | 166.40 | 364.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.49 | 0.00 | 96.49 | 10.44 | 110.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 331.80 | 36.78 | 295.01 | 439.13 | 654.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 358.83 | 219.90 | 138.93 | 306.80 | 587.32 | 0.00 | 0.00 | 0.00 |
February | 476.67 | 300.92 | 175.75 | 438.62 | 601.61 | 0.00 | 0.00 | 0.00 |
March | 575.32 | 335.58 | 239.74 | 573.32 | 461.14 | 0.00 | 0.00 | 0.00 |
April | 590.02 | 287.41 | 302.61 | 574.65 | 408.70 | 0.00 | 0.00 | 0.00 |
May | 689.73 | 288.10 | 401.63 | 774.66 | 240.42 | 0.00 | 0.00 | 0.00 |
June | 841.54 | 441.79 | 399.75 | 1133.59 | 128.29 | 0.00 | 0.00 | 0.00 |
July | 765.03 | 364.29 | 400.74 | 1040.50 | 118.29 | 0.00 | 0.00 | 0.00 |
August | 771.63 | 424.99 | 346.65 | 1042.23 | 133.63 | 0.00 | 0.00 | 0.00 |
September | 642.04 | 348.77 | 293.27 | 818.44 | 211.22 | 0.00 | 0.00 | 0.00 |
October | 464.96 | 254.77 | 210.19 | 482.04 | 456.85 | 0.00 | 0.00 | 0.00 |
November | 361.92 | 204.34 | 157.57 | 328.99 | 544.87 | 0.00 | 0.00 | 0.00 |
December | 313.32 | 180.50 | 132.83 | 254.81 | 665.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.28 | 304.13 | 267.15 | 648.37 | 378.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 313.32 | 180.50 | 132.83 | 254.81 | 118.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 841.54 | 441.79 | 401.63 | 1133.59 | 665.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 358.83 | 219.90 | 138.93 | 306.80 | 587.32 | 0.00 | 0.00 | 0.00 |
February | 476.67 | 300.92 | 175.75 | 438.62 | 601.61 | 0.00 | 0.00 | 0.00 |
March | 575.32 | 335.58 | 239.74 | 573.32 | 461.14 | 0.00 | 0.00 | 0.00 |
April | 590.02 | 287.41 | 302.61 | 574.65 | 408.70 | 0.00 | 0.00 | 0.00 |
May | 689.73 | 288.10 | 401.63 | 774.66 | 240.42 | 0.00 | 0.00 | 0.00 |
June | 841.54 | 441.79 | 399.75 | 1133.59 | 128.29 | 0.00 | 0.00 | 0.00 |
July | 765.03 | 364.29 | 400.74 | 1040.50 | 118.29 | 0.00 | 0.00 | 0.00 |
August | 771.63 | 424.99 | 346.65 | 1042.23 | 133.63 | 0.00 | 0.00 | 0.00 |
September | 642.04 | 348.77 | 293.27 | 818.44 | 211.22 | 0.00 | 0.00 | 0.00 |
October | 464.96 | 254.77 | 210.19 | 482.04 | 456.85 | 0.00 | 0.00 | 0.00 |
November | 361.92 | 204.34 | 157.57 | 328.99 | 544.87 | 0.00 | 0.00 | 0.00 |
December | 313.32 | 180.50 | 132.83 | 254.81 | 665.59 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.28 | 304.13 | 267.15 | 648.37 | 378.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 313.32 | 180.50 | 132.83 | 254.81 | 118.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 841.54 | 441.79 | 401.63 | 1133.59 | 665.59 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 358.82 | 219.90 | 138.93 | 306.80 | 587.31 | 0.00 | 0.00 | 0.00 |
February | 476.66 | 300.91 | 175.75 | 438.62 | 601.60 | 0.00 | 0.00 | 0.00 |
March | 575.31 | 335.57 | 239.74 | 573.31 | 461.13 | 0.00 | 0.00 | 0.00 |
April | 590.01 | 287.41 | 302.61 | 574.64 | 408.69 | 0.00 | 0.00 | 0.00 |
May | 689.72 | 288.10 | 401.62 | 774.64 | 240.42 | 0.00 | 0.00 | 0.00 |
June | 841.52 | 441.78 | 399.75 | 1133.57 | 128.29 | 0.00 | 0.00 | 0.00 |
July | 765.01 | 364.28 | 400.73 | 1040.48 | 118.28 | 0.00 | 0.00 | 0.00 |
August | 771.62 | 424.98 | 346.64 | 1042.21 | 133.63 | 0.00 | 0.00 | 0.00 |
September | 642.03 | 348.77 | 293.26 | 818.43 | 211.22 | 0.00 | 0.00 | 0.00 |
October | 464.96 | 254.77 | 210.19 | 482.03 | 456.84 | 0.00 | 0.00 | 0.00 |
November | 361.91 | 204.34 | 157.57 | 328.98 | 544.86 | 0.00 | 0.00 | 0.00 |
December | 313.32 | 180.49 | 132.82 | 254.81 | 665.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 571.27 | 304.12 | 267.14 | 648.36 | 378.62 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 313.32 | 180.49 | 132.82 | 254.81 | 118.28 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 841.52 | 441.78 | 401.62 | 1133.57 | 665.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 988.41 | 813.07 | 175.34 | 1121.03 | 499.79 | 0.00 | 0.00 | 0.00 |
February | 948.07 | 755.86 | 192.21 | 1066.50 | 519.43 | 0.00 | 0.00 | 0.00 |
March | 698.99 | 459.89 | 239.10 | 795.53 | 419.65 | 0.00 | 0.00 | 0.00 |
April | 452.72 | 182.04 | 270.68 | 465.28 | 385.73 | 0.00 | 0.00 | 0.00 |
May | 414.87 | 76.04 | 338.83 | 468.78 | 235.09 | 0.00 | 0.00 | 0.00 |
June | 382.49 | 69.91 | 312.59 | 551.50 | 129.08 | 0.00 | 0.00 | 0.00 |
July | 398.17 | 71.30 | 326.87 | 575.36 | 118.83 | 0.00 | 0.00 | 0.00 |
August | 506.95 | 211.92 | 295.03 | 735.14 | 136.11 | 0.00 | 0.00 | 0.00 |
September | 652.23 | 363.94 | 288.29 | 888.06 | 205.48 | 0.00 | 0.00 | 0.00 |
October | 779.88 | 553.34 | 226.54 | 941.12 | 414.05 | 0.00 | 0.00 | 0.00 |
November | 950.18 | 757.43 | 192.75 | 1102.74 | 479.48 | 0.00 | 0.00 | 0.00 |
December | 908.61 | 735.42 | 173.20 | 1007.04 | 566.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.91 | 418.94 | 252.97 | 808.36 | 341.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.49 | 69.91 | 173.20 | 465.28 | 118.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.41 | 813.07 | 338.83 | 1121.03 | 566.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 988.40 | 813.06 | 175.34 | 1121.02 | 499.79 | 0.00 | 0.00 | 0.00 |
February | 948.06 | 755.85 | 192.21 | 1066.49 | 519.43 | 0.00 | 0.00 | 0.00 |
March | 698.98 | 459.89 | 239.09 | 795.52 | 419.65 | 0.00 | 0.00 | 0.00 |
April | 452.71 | 182.04 | 270.68 | 465.27 | 385.73 | 0.00 | 0.00 | 0.00 |
May | 414.86 | 76.04 | 338.82 | 468.77 | 235.09 | 0.00 | 0.00 | 0.00 |
June | 382.49 | 69.91 | 312.58 | 551.50 | 129.08 | 0.00 | 0.00 | 0.00 |
July | 398.16 | 71.30 | 326.87 | 575.35 | 118.83 | 0.00 | 0.00 | 0.00 |
August | 506.94 | 211.92 | 295.02 | 735.14 | 136.11 | 0.00 | 0.00 | 0.00 |
September | 652.23 | 363.94 | 288.29 | 888.05 | 205.48 | 0.00 | 0.00 | 0.00 |
October | 779.88 | 553.34 | 226.54 | 941.11 | 414.05 | 0.00 | 0.00 | 0.00 |
November | 950.17 | 757.42 | 192.75 | 1102.73 | 479.48 | 0.00 | 0.00 | 0.00 |
December | 908.61 | 735.41 | 173.19 | 1007.03 | 566.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.90 | 418.94 | 252.96 | 808.36 | 341.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.49 | 69.91 | 173.19 | 465.27 | 118.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.40 | 813.06 | 338.82 | 1121.02 | 566.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 988.41 | 813.07 | 175.34 | 1121.03 | 499.79 | 0.00 | 0.00 | 0.00 |
February | 948.07 | 755.86 | 192.21 | 1066.50 | 519.43 | 0.00 | 0.00 | 0.00 |
March | 698.99 | 459.89 | 239.10 | 795.53 | 419.65 | 0.00 | 0.00 | 0.00 |
April | 452.72 | 182.04 | 270.68 | 465.28 | 385.73 | 0.00 | 0.00 | 0.00 |
May | 414.87 | 76.04 | 338.83 | 468.78 | 235.09 | 0.00 | 0.00 | 0.00 |
June | 382.49 | 69.91 | 312.59 | 551.50 | 129.08 | 0.00 | 0.00 | 0.00 |
July | 398.17 | 71.30 | 326.87 | 575.36 | 118.83 | 0.00 | 0.00 | 0.00 |
August | 506.95 | 211.92 | 295.03 | 735.14 | 136.11 | 0.00 | 0.00 | 0.00 |
September | 652.23 | 363.94 | 288.29 | 888.06 | 205.48 | 0.00 | 0.00 | 0.00 |
October | 779.88 | 553.34 | 226.54 | 941.12 | 414.05 | 0.00 | 0.00 | 0.00 |
November | 950.18 | 757.43 | 192.75 | 1102.74 | 479.48 | 0.00 | 0.00 | 0.00 |
December | 908.61 | 735.42 | 173.20 | 1007.04 | 566.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.91 | 418.94 | 252.97 | 808.36 | 341.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.49 | 69.91 | 173.20 | 465.28 | 118.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.41 | 813.07 | 338.83 | 1121.03 | 566.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 988.40 | 813.06 | 175.34 | 1121.02 | 499.79 | 0.00 | 0.00 | 0.00 |
February | 948.06 | 755.85 | 192.21 | 1066.49 | 519.43 | 0.00 | 0.00 | 0.00 |
March | 698.98 | 459.89 | 239.09 | 795.52 | 419.65 | 0.00 | 0.00 | 0.00 |
April | 452.71 | 182.04 | 270.68 | 465.27 | 385.73 | 0.00 | 0.00 | 0.00 |
May | 414.86 | 76.04 | 338.82 | 468.77 | 235.09 | 0.00 | 0.00 | 0.00 |
June | 382.49 | 69.91 | 312.58 | 551.50 | 129.08 | 0.00 | 0.00 | 0.00 |
July | 398.16 | 71.30 | 326.87 | 575.35 | 118.83 | 0.00 | 0.00 | 0.00 |
August | 506.94 | 211.92 | 295.02 | 735.14 | 136.11 | 0.00 | 0.00 | 0.00 |
September | 652.23 | 363.94 | 288.29 | 888.05 | 205.48 | 0.00 | 0.00 | 0.00 |
October | 779.88 | 553.34 | 226.54 | 941.11 | 414.05 | 0.00 | 0.00 | 0.00 |
November | 950.17 | 757.42 | 192.75 | 1102.73 | 479.48 | 0.00 | 0.00 | 0.00 |
December | 908.61 | 735.41 | 173.19 | 1007.03 | 566.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.90 | 418.94 | 252.96 | 808.36 | 341.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.49 | 69.91 | 173.19 | 465.27 | 118.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.40 | 813.06 | 338.82 | 1121.02 | 566.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 988.36 | 813.03 | 175.33 | 1120.98 | 499.77 | 0.00 | 0.00 | 0.00 |
February | 948.02 | 755.82 | 192.20 | 1066.45 | 519.41 | 0.00 | 0.00 | 0.00 |
March | 698.96 | 459.87 | 239.08 | 795.49 | 419.63 | 0.00 | 0.00 | 0.00 |
April | 452.70 | 182.03 | 270.67 | 465.25 | 385.72 | 0.00 | 0.00 | 0.00 |
May | 414.85 | 76.04 | 338.81 | 468.76 | 235.08 | 0.00 | 0.00 | 0.00 |
June | 382.48 | 69.91 | 312.57 | 551.48 | 129.07 | 0.00 | 0.00 | 0.00 |
July | 398.15 | 71.30 | 326.85 | 575.33 | 118.83 | 0.00 | 0.00 | 0.00 |
August | 506.92 | 211.91 | 295.01 | 735.11 | 136.11 | 0.00 | 0.00 | 0.00 |
September | 652.21 | 363.93 | 288.28 | 888.02 | 205.47 | 0.00 | 0.00 | 0.00 |
October | 779.85 | 553.32 | 226.53 | 941.08 | 414.03 | 0.00 | 0.00 | 0.00 |
November | 950.13 | 757.39 | 192.74 | 1102.69 | 479.46 | 0.00 | 0.00 | 0.00 |
December | 908.58 | 735.39 | 173.19 | 1007.00 | 566.03 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 671.88 | 418.92 | 252.95 | 808.33 | 341.39 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 382.48 | 69.91 | 173.19 | 465.25 | 118.83 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 988.36 | 813.03 | 338.81 | 1120.98 | 566.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.71 | 241.88 | 139.84 | 349.99 | 629.48 | 0.00 | 0.00 | 0.00 |
February | 460.29 | 285.25 | 175.05 | 418.46 | 652.12 | 0.00 | 0.00 | 0.00 |
March | 538.97 | 297.36 | 241.61 | 519.59 | 521.76 | 0.00 | 0.00 | 0.00 |
April | 507.47 | 214.85 | 292.62 | 459.24 | 485.08 | 0.00 | 0.00 | 0.00 |
May | 620.26 | 218.66 | 401.59 | 688.58 | 274.04 | 0.00 | 0.00 | 0.00 |
June | 758.61 | 365.00 | 393.61 | 1023.02 | 162.75 | 0.00 | 0.00 | 0.00 |
July | 618.09 | 226.39 | 391.69 | 830.74 | 152.33 | 0.00 | 0.00 | 0.00 |
August | 645.11 | 318.69 | 326.42 | 847.29 | 181.29 | 0.00 | 0.00 | 0.00 |
September | 572.02 | 274.32 | 297.70 | 727.16 | 243.50 | 0.00 | 0.00 | 0.00 |
October | 481.22 | 275.05 | 206.17 | 507.27 | 502.96 | 0.00 | 0.00 | 0.00 |
November | 394.87 | 239.73 | 155.13 | 367.68 | 607.21 | 0.00 | 0.00 | 0.00 |
December | 318.94 | 188.41 | 130.54 | 257.22 | 749.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 524.96 | 261.82 | 263.14 | 583.70 | 428.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 318.94 | 188.41 | 130.54 | 257.22 | 152.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.61 | 365.00 | 401.59 | 1023.02 | 749.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.71 | 241.88 | 139.84 | 349.99 | 629.48 | 0.00 | 0.00 | 0.00 |
February | 460.29 | 285.25 | 175.05 | 418.46 | 652.12 | 0.00 | 0.00 | 0.00 |
March | 538.97 | 297.36 | 241.61 | 519.59 | 521.76 | 0.00 | 0.00 | 0.00 |
April | 507.47 | 214.85 | 292.62 | 459.24 | 485.08 | 0.00 | 0.00 | 0.00 |
May | 620.26 | 218.66 | 401.59 | 688.58 | 274.04 | 0.00 | 0.00 | 0.00 |
June | 758.61 | 365.00 | 393.61 | 1023.02 | 162.75 | 0.00 | 0.00 | 0.00 |
July | 618.09 | 226.39 | 391.69 | 830.74 | 152.33 | 0.00 | 0.00 | 0.00 |
August | 645.11 | 318.69 | 326.42 | 847.29 | 181.29 | 0.00 | 0.00 | 0.00 |
September | 572.02 | 274.32 | 297.70 | 727.16 | 243.50 | 0.00 | 0.00 | 0.00 |
October | 481.22 | 275.05 | 206.17 | 507.27 | 502.96 | 0.00 | 0.00 | 0.00 |
November | 394.87 | 239.73 | 155.13 | 367.68 | 607.21 | 0.00 | 0.00 | 0.00 |
December | 318.94 | 188.41 | 130.54 | 257.22 | 749.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 524.96 | 261.82 | 263.14 | 583.70 | 428.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 318.94 | 188.41 | 130.54 | 257.22 | 152.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.61 | 365.00 | 401.59 | 1023.02 | 749.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 381.71 | 241.87 | 139.84 | 349.98 | 629.46 | 0.00 | 0.00 | 0.00 |
February | 460.29 | 285.24 | 175.04 | 418.45 | 652.11 | 0.00 | 0.00 | 0.00 |
March | 538.96 | 297.36 | 241.61 | 519.58 | 521.75 | 0.00 | 0.00 | 0.00 |
April | 507.46 | 214.85 | 292.61 | 459.24 | 485.07 | 0.00 | 0.00 | 0.00 |
May | 620.25 | 218.66 | 401.59 | 688.56 | 274.04 | 0.00 | 0.00 | 0.00 |
June | 758.60 | 364.99 | 393.61 | 1023.00 | 162.74 | 0.00 | 0.00 | 0.00 |
July | 618.08 | 226.39 | 391.69 | 830.73 | 152.33 | 0.00 | 0.00 | 0.00 |
August | 645.10 | 318.69 | 326.41 | 847.27 | 181.29 | 0.00 | 0.00 | 0.00 |
September | 572.01 | 274.32 | 297.69 | 727.14 | 243.49 | 0.00 | 0.00 | 0.00 |
October | 481.21 | 275.05 | 206.16 | 507.26 | 502.95 | 0.00 | 0.00 | 0.00 |
November | 394.86 | 239.73 | 155.13 | 367.67 | 607.20 | 0.00 | 0.00 | 0.00 |
December | 318.94 | 188.41 | 130.53 | 257.22 | 749.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 524.95 | 261.81 | 263.14 | 583.69 | 428.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 318.94 | 188.41 | 130.53 | 257.22 | 152.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 758.60 | 364.99 | 401.59 | 1023.00 | 749.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.67 | 0.00 | 515.67 | 94.27 | 2615.80 | 0.00 | 0.00 | 0.00 |
February | 648.14 | 0.00 | 648.14 | 122.71 | 2627.86 | 0.00 | 0.00 | 0.00 |
March | 881.90 | 0.00 | 881.90 | 396.11 | 2001.19 | 0.00 | 0.00 | 0.00 |
April | 1107.54 | 6.14 | 1101.40 | 598.23 | 1726.29 | 0.00 | 0.00 | 0.00 |
May | 1512.97 | 50.01 | 1462.96 | 1345.90 | 1034.81 | 0.00 | 0.00 | 0.00 |
June | 1659.08 | 183.94 | 1475.14 | 2209.52 | 573.89 | 0.00 | 0.00 | 0.00 |
July | 1569.03 | 101.57 | 1467.47 | 2116.95 | 542.95 | 0.00 | 0.00 | 0.00 |
August | 1248.83 | 29.54 | 1219.29 | 1609.60 | 620.89 | 0.00 | 0.00 | 0.00 |
September | 1049.02 | 0.25 | 1048.77 | 1191.59 | 954.58 | 0.00 | 0.00 | 0.00 |
October | 751.35 | 0.00 | 751.35 | 412.06 | 1973.13 | 0.00 | 0.00 | 0.00 |
November | 570.37 | 0.00 | 570.37 | 158.62 | 2363.16 | 0.00 | 0.00 | 0.00 |
December | 482.48 | 0.00 | 482.48 | 85.34 | 2912.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1001.53 | 31.03 | 970.50 | 865.87 | 1657.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 482.48 | 0.00 | 482.48 | 85.34 | 542.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.08 | 183.94 | 1475.14 | 2209.52 | 2912.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1076.48 | 659.70 | 416.78 | 945.16 | 1641.07 | 0.00 | 0.00 | 0.00 |
February | 1429.98 | 902.74 | 527.24 | 1330.50 | 1684.45 | 0.00 | 0.00 | 0.00 |
March | 1725.95 | 1006.73 | 719.22 | 1729.57 | 1290.74 | 0.00 | 0.00 | 0.00 |
April | 1770.05 | 862.22 | 907.83 | 1734.98 | 1125.50 | 0.00 | 0.00 | 0.00 |
May | 2069.17 | 864.30 | 1204.87 | 2319.94 | 697.55 | 0.00 | 0.00 | 0.00 |
June | 2524.59 | 1325.35 | 1199.25 | 3384.41 | 387.61 | 0.00 | 0.00 | 0.00 |
July | 2295.06 | 1092.85 | 1202.21 | 3104.24 | 367.30 | 0.00 | 0.00 | 0.00 |
August | 2314.88 | 1274.95 | 1039.93 | 3109.80 | 420.48 | 0.00 | 0.00 | 0.00 |
September | 1926.10 | 1046.31 | 879.79 | 2448.82 | 616.67 | 0.00 | 0.00 | 0.00 |
October | 1394.88 | 764.31 | 630.57 | 1452.45 | 1293.89 | 0.00 | 0.00 | 0.00 |
November | 1085.73 | 613.02 | 472.72 | 1007.39 | 1522.50 | 0.00 | 0.00 | 0.00 |
December | 939.96 | 541.48 | 398.47 | 792.78 | 1841.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1713.81 | 912.38 | 801.43 | 1949.57 | 1070.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 939.96 | 541.48 | 398.47 | 792.78 | 367.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2524.59 | 1325.35 | 1204.87 | 3384.41 | 1841.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4942.13 | 4065.43 | 876.70 | 5580.85 | 2466.47 | 0.00 | 0.00 | 0.00 |
February | 4740.42 | 3779.36 | 961.06 | 5303.77 | 2528.67 | 0.00 | 0.00 | 0.00 |
March | 3495.00 | 2299.51 | 1195.49 | 3965.98 | 2013.86 | 0.00 | 0.00 | 0.00 |
April | 2263.62 | 910.21 | 1353.41 | 2337.06 | 1801.69 | 0.00 | 0.00 | 0.00 |
May | 2074.36 | 380.22 | 1694.14 | 2342.91 | 1146.14 | 0.00 | 0.00 | 0.00 |
June | 1912.49 | 349.55 | 1562.94 | 2760.32 | 633.91 | 0.00 | 0.00 | 0.00 |
July | 1990.86 | 356.51 | 1634.35 | 2880.01 | 589.31 | 0.00 | 0.00 | 0.00 |
August | 2534.77 | 1059.63 | 1475.14 | 3674.83 | 671.79 | 0.00 | 0.00 | 0.00 |
September | 3261.23 | 1819.75 | 1441.48 | 4420.01 | 1012.89 | 0.00 | 0.00 | 0.00 |
October | 3899.47 | 2766.77 | 1132.71 | 4684.31 | 2022.56 | 0.00 | 0.00 | 0.00 |
November | 4750.97 | 3787.21 | 963.76 | 5490.88 | 2339.62 | 0.00 | 0.00 | 0.00 |
December | 4543.16 | 3677.17 | 865.99 | 5034.13 | 2707.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3359.60 | 2094.76 | 1264.84 | 4032.35 | 1656.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1912.49 | 349.55 | 865.99 | 2337.06 | 589.31 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4942.13 | 4065.43 | 1694.14 | 5580.85 | 2707.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1145.13 | 725.62 | 419.51 | 1082.03 | 1722.58 | 0.00 | 0.00 | 0.00 |
February | 1380.87 | 855.73 | 525.14 | 1294.84 | 1747.79 | 0.00 | 0.00 | 0.00 |
March | 1616.91 | 892.08 | 724.82 | 1610.28 | 1353.82 | 0.00 | 0.00 | 0.00 |
April | 1522.39 | 644.55 | 877.84 | 1442.48 | 1190.28 | 0.00 | 0.00 | 0.00 |
May | 1860.75 | 655.98 | 1204.77 | 2091.00 | 762.29 | 0.00 | 0.00 | 0.00 |
June | 2275.81 | 1094.98 | 1180.83 | 3089.49 | 453.97 | 0.00 | 0.00 | 0.00 |
July | 1854.25 | 679.18 | 1175.07 | 2525.34 | 414.23 | 0.00 | 0.00 | 0.00 |
August | 1935.31 | 956.07 | 979.24 | 2595.00 | 465.11 | 0.00 | 0.00 | 0.00 |
September | 1716.04 | 822.96 | 893.08 | 2199.67 | 679.53 | 0.00 | 0.00 | 0.00 |
October | 1443.65 | 825.15 | 618.49 | 1557.01 | 1349.09 | 0.00 | 0.00 | 0.00 |
November | 1184.59 | 719.19 | 465.40 | 1151.37 | 1584.11 | 0.00 | 0.00 | 0.00 |
December | 956.82 | 565.22 | 391.60 | 826.51 | 1895.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1574.87 | 785.45 | 789.42 | 1790.82 | 1131.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 956.82 | 565.22 | 391.60 | 826.51 | 414.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2275.81 | 1094.98 | 1204.77 | 3089.49 | 1895.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 515.67 | 0.00 | 515.67 | 115.36 | 2429.66 | 0.00 | 0.00 | 0.00 |
February | 648.14 | 0.00 | 648.14 | 141.66 | 2482.11 | 0.00 | 0.00 | 0.00 |
March | 881.90 | 0.00 | 881.90 | 419.55 | 1882.58 | 0.00 | 0.00 | 0.00 |
April | 1107.54 | 6.14 | 1101.40 | 627.11 | 1586.15 | 0.00 | 0.00 | 0.00 |
May | 1512.97 | 50.01 | 1462.96 | 1375.88 | 985.19 | 0.00 | 0.00 | 0.00 |
June | 1659.08 | 183.94 | 1475.14 | 2195.95 | 571.65 | 0.00 | 0.00 | 0.00 |
July | 1569.03 | 101.57 | 1467.47 | 2102.31 | 543.30 | 0.00 | 0.00 | 0.00 |
August | 1248.83 | 29.54 | 1219.29 | 1601.27 | 614.26 | 0.00 | 0.00 | 0.00 |
September | 1049.02 | 0.25 | 1048.77 | 1198.46 | 919.54 | 0.00 | 0.00 | 0.00 |
October | 751.35 | 0.00 | 751.35 | 443.02 | 1830.56 | 0.00 | 0.00 | 0.00 |
November | 570.37 | 0.00 | 570.37 | 187.21 | 2185.29 | 0.00 | 0.00 | 0.00 |
December | 482.48 | 0.00 | 482.48 | 98.07 | 2758.63 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1001.53 | 31.03 | 970.50 | 879.58 | 1560.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 482.48 | 0.00 | 482.48 | 98.07 | 543.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1659.08 | 183.94 | 1475.14 | 2195.95 | 2758.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1076.48 | 659.70 | 416.78 | 976.04 | 1524.06 | 0.00 | 0.00 | 0.00 |
February | 1429.98 | 902.74 | 527.24 | 1353.08 | 1596.21 | 0.00 | 0.00 | 0.00 |
March | 1725.95 | 1006.73 | 719.22 | 1746.79 | 1222.10 | 0.00 | 0.00 | 0.00 |
April | 1770.05 | 862.22 | 907.83 | 1753.46 | 1041.47 | 0.00 | 0.00 | 0.00 |
May | 2069.17 | 864.30 | 1204.87 | 2331.44 | 671.41 | 0.00 | 0.00 | 0.00 |
June | 2524.59 | 1325.35 | 1199.25 | 3371.11 | 388.20 | 0.00 | 0.00 | 0.00 |
July | 2295.06 | 1092.85 | 1202.21 | 3091.20 | 369.17 | 0.00 | 0.00 | 0.00 |
August | 2314.88 | 1274.95 | 1039.93 | 3099.76 | 419.38 | 0.00 | 0.00 | 0.00 |
September | 1926.10 | 1046.31 | 879.79 | 2448.23 | 601.63 | 0.00 | 0.00 | 0.00 |
October | 1394.88 | 764.31 | 630.57 | 1468.72 | 1213.78 | 0.00 | 0.00 | 0.00 |
November | 1085.73 | 613.02 | 472.72 | 1035.59 | 1418.57 | 0.00 | 0.00 | 0.00 |
December | 939.96 | 541.48 | 398.47 | 814.07 | 1749.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1713.81 | 912.38 | 801.43 | 1960.29 | 1014.95 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 939.96 | 541.48 | 398.47 | 814.07 | 369.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2524.59 | 1325.35 | 1204.87 | 3371.11 | 1749.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 4942.13 | 4065.43 | 876.70 | 5640.41 | 2287.17 | 0.00 | 0.00 | 0.00 |
February | 4740.42 | 3779.36 | 961.06 | 5336.92 | 2390.16 | 0.00 | 0.00 | 0.00 |
March | 3495.00 | 2299.51 | 1195.49 | 3988.88 | 1900.92 | 0.00 | 0.00 | 0.00 |
April | 2263.62 | 910.21 | 1353.41 | 2361.80 | 1663.53 | 0.00 | 0.00 | 0.00 |
May | 2074.36 | 380.22 | 1694.14 | 2362.50 | 1092.26 | 0.00 | 0.00 | 0.00 |
June | 1912.49 | 349.55 | 1562.94 | 2747.04 | 629.47 | 0.00 | 0.00 | 0.00 |
July | 1990.86 | 356.51 | 1634.35 | 2865.72 | 587.94 | 0.00 | 0.00 | 0.00 |
August | 2534.77 | 1059.63 | 1475.14 | 3662.61 | 666.06 | 0.00 | 0.00 | 0.00 |
September | 3261.23 | 1819.75 | 1441.48 | 4417.76 | 984.88 | 0.00 | 0.00 | 0.00 |
October | 3899.47 | 2766.77 | 1132.71 | 4705.17 | 1899.59 | 0.00 | 0.00 | 0.00 |
November | 4750.97 | 3787.21 | 963.76 | 5531.86 | 2188.33 | 0.00 | 0.00 | 0.00 |
December | 4543.16 | 3677.17 | 865.99 | 5075.97 | 2557.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3359.60 | 2094.76 | 1264.84 | 4050.76 | 1566.14 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 1912.49 | 349.55 | 865.99 | 2361.80 | 587.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 4942.13 | 4065.43 | 1694.14 | 5640.41 | 2557.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 1145.13 | 725.62 | 419.51 | 1102.48 | 1607.94 | 0.00 | 0.00 | 0.00 |
February | 1380.87 | 855.73 | 525.14 | 1306.93 | 1663.12 | 0.00 | 0.00 | 0.00 |
March | 1616.91 | 892.08 | 724.82 | 1621.14 | 1283.97 | 0.00 | 0.00 | 0.00 |
April | 1522.39 | 644.55 | 877.84 | 1455.94 | 1107.81 | 0.00 | 0.00 | 0.00 |
May | 1860.75 | 655.98 | 1204.77 | 2101.40 | 731.47 | 0.00 | 0.00 | 0.00 |
June | 2275.81 | 1094.98 | 1180.83 | 3079.29 | 451.57 | 0.00 | 0.00 | 0.00 |
July | 1854.25 | 679.18 | 1175.07 | 2515.40 | 412.78 | 0.00 | 0.00 | 0.00 |
August | 1935.31 | 956.07 | 979.24 | 2588.02 | 461.05 | 0.00 | 0.00 | 0.00 |
September | 1716.04 | 822.96 | 893.08 | 2201.00 | 660.27 | 0.00 | 0.00 | 0.00 |
October | 1443.65 | 825.15 | 618.49 | 1570.68 | 1271.92 | 0.00 | 0.00 | 0.00 |
November | 1184.59 | 719.19 | 465.40 | 1168.63 | 1488.98 | 0.00 | 0.00 | 0.00 |
December | 956.82 | 565.22 | 391.60 | 838.19 | 1806.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 1574.87 | 785.45 | 789.42 | 1797.80 | 1075.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 956.82 | 565.22 | 391.60 | 838.19 | 412.78 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2275.81 | 1094.98 | 1204.77 | 3079.29 | 1806.81 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276236E+09 | 0.00 | 0.276236E+09 | 36119981.94 | 0.154139E+10 |
February | 0.313596E+09 | 0.00 | 0.313596E+09 | 42221208.05 | 0.140005E+10 |
March | 0.472418E+09 | 0.00 | 0.472418E+09 | 0.182074E+09 | 0.119308E+10 |
April | 0.574150E+09 | 3185116.15 | 0.570965E+09 | 0.277695E+09 | 0.102271E+10 |
May | 0.810468E+09 | 26790626.87 | 0.783677E+09 | 0.705277E+09 | 0.584914E+09 |
June | 0.860065E+09 | 95351519.88 | 0.764714E+09 | 0.113828E+10 | 0.305064E+09 |
July | 0.840500E+09 | 54406724.38 | 0.786094E+09 | 0.112551E+10 | 0.297098E+09 |
August | 0.668976E+09 | 15825583.50 | 0.653150E+09 | 0.847383E+09 | 0.346934E+09 |
September | 0.543812E+09 | 127730.90 | 0.543685E+09 | 0.605344E+09 | 0.521663E+09 |
October | 0.402484E+09 | 0.00 | 0.402484E+09 | 0.197972E+09 | 0.115454E+10 |
November | 0.295681E+09 | 0.00 | 0.295681E+09 | 61897440.18 | 0.136598E+10 |
December | 0.258453E+09 | 0.00 | 0.258453E+09 | 27958611.80 | 0.175359E+10 |
Annual Sum or Average | 0.631684E+10 | 0.195687E+09 | 0.612115E+10 | 0.524772E+10 | 0.114870E+11 |
Minimum of Months | 0.258453E+09 | 0.00 | 0.258453E+09 | 27958611.80 | 0.297098E+09 |
Maximum of Months | 0.860065E+09 | 95351519.88 | 0.786094E+09 | 0.113828E+10 | 0.175359E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276232E+09 | 0.00 | 0.276232E+09 | 36118634.21 | 0.154139E+10 |
February | 0.313592E+09 | 0.00 | 0.313592E+09 | 42219893.64 | 0.140005E+10 |
March | 0.472412E+09 | 0.00 | 0.472412E+09 | 0.182069E+09 | 0.119308E+10 |
April | 0.574142E+09 | 3185046.13 | 0.570957E+09 | 0.277689E+09 | 0.102271E+10 |
May | 0.810456E+09 | 26790037.91 | 0.783666E+09 | 0.705263E+09 | 0.584914E+09 |
June | 0.860054E+09 | 95349423.69 | 0.764704E+09 | 0.113826E+10 | 0.305062E+09 |
July | 0.840488E+09 | 54405528.32 | 0.786083E+09 | 0.112549E+10 | 0.297096E+09 |
August | 0.668967E+09 | 15825235.59 | 0.653142E+09 | 0.847373E+09 | 0.346933E+09 |
September | 0.543805E+09 | 127728.09 | 0.543678E+09 | 0.605337E+09 | 0.521661E+09 |
October | 0.402479E+09 | 0.00 | 0.402479E+09 | 0.197968E+09 | 0.115454E+10 |
November | 0.295677E+09 | 0.00 | 0.295677E+09 | 61895870.30 | 0.136598E+10 |
December | 0.258449E+09 | 0.00 | 0.258449E+09 | 27957841.52 | 0.175359E+10 |
Annual Sum or Average | 0.631675E+10 | 0.195683E+09 | 0.612107E+10 | 0.524764E+10 | 0.114870E+11 |
Minimum of Months | 0.258449E+09 | 0.00 | 0.258449E+09 | 27957841.52 | 0.297096E+09 |
Maximum of Months | 0.860054E+09 | 95349423.69 | 0.786083E+09 | 0.113826E+10 | 0.175359E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276233E+09 | 0.00 | 0.276233E+09 | 36119083.45 | 0.154139E+10 |
February | 0.313593E+09 | 0.00 | 0.313593E+09 | 42220331.78 | 0.140005E+10 |
March | 0.472414E+09 | 0.00 | 0.472414E+09 | 0.182071E+09 | 0.119308E+10 |
April | 0.574145E+09 | 3185069.47 | 0.570960E+09 | 0.277691E+09 | 0.102271E+10 |
May | 0.810460E+09 | 26790234.23 | 0.783670E+09 | 0.705267E+09 | 0.584914E+09 |
June | 0.860057E+09 | 95350122.42 | 0.764707E+09 | 0.113827E+10 | 0.305063E+09 |
July | 0.840492E+09 | 54405927.00 | 0.786086E+09 | 0.112550E+10 | 0.297097E+09 |
August | 0.668970E+09 | 15825351.56 | 0.653145E+09 | 0.847376E+09 | 0.346933E+09 |
September | 0.543808E+09 | 127729.02 | 0.543680E+09 | 0.605339E+09 | 0.521661E+09 |
October | 0.402481E+09 | 0.00 | 0.402481E+09 | 0.197970E+09 | 0.115454E+10 |
November | 0.295678E+09 | 0.00 | 0.295678E+09 | 61896393.59 | 0.136598E+10 |
December | 0.258450E+09 | 0.00 | 0.258450E+09 | 27958098.28 | 0.175359E+10 |
Annual Sum or Average | 0.631678E+10 | 0.195684E+09 | 0.612110E+10 | 0.524767E+10 | 0.114870E+11 |
Minimum of Months | 0.258450E+09 | 0.00 | 0.258450E+09 | 27958098.28 | 0.297097E+09 |
Maximum of Months | 0.860057E+09 | 95350122.42 | 0.786086E+09 | 0.113827E+10 | 0.175359E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276232E+09 | 0.00 | 0.276232E+09 | 36118634.21 | 0.154139E+10 |
February | 0.313592E+09 | 0.00 | 0.313592E+09 | 42219893.64 | 0.140005E+10 |
March | 0.472412E+09 | 0.00 | 0.472412E+09 | 0.182069E+09 | 0.119308E+10 |
April | 0.574142E+09 | 3185046.13 | 0.570957E+09 | 0.277689E+09 | 0.102271E+10 |
May | 0.810456E+09 | 26790037.91 | 0.783666E+09 | 0.705263E+09 | 0.584914E+09 |
June | 0.860054E+09 | 95349423.69 | 0.764704E+09 | 0.113826E+10 | 0.305062E+09 |
July | 0.840488E+09 | 54405528.32 | 0.786083E+09 | 0.112549E+10 | 0.297096E+09 |
August | 0.668967E+09 | 15825235.59 | 0.653142E+09 | 0.847373E+09 | 0.346933E+09 |
September | 0.543805E+09 | 127728.09 | 0.543678E+09 | 0.605337E+09 | 0.521661E+09 |
October | 0.402479E+09 | 0.00 | 0.402479E+09 | 0.197968E+09 | 0.115454E+10 |
November | 0.295677E+09 | 0.00 | 0.295677E+09 | 61895870.30 | 0.136598E+10 |
December | 0.258449E+09 | 0.00 | 0.258449E+09 | 27957841.52 | 0.175359E+10 |
Annual Sum or Average | 0.631675E+10 | 0.195683E+09 | 0.612107E+10 | 0.524764E+10 | 0.114870E+11 |
Minimum of Months | 0.258449E+09 | 0.00 | 0.258449E+09 | 27957841.52 | 0.297096E+09 |
Maximum of Months | 0.860054E+09 | 95349423.69 | 0.786083E+09 | 0.113826E+10 | 0.175359E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_3_WALL_NORTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.276222E+09 | 0.00 | 0.276222E+09 | 36117403.08 | 0.154133E+10 |
February | 0.313580E+09 | 0.00 | 0.313580E+09 | 42218411.05 | 0.139999E+10 |
March | 0.472394E+09 | 0.00 | 0.472394E+09 | 0.182063E+09 | 0.119303E+10 |
April | 0.574120E+09 | 3184929.43 | 0.570935E+09 | 0.277678E+09 | 0.102267E+10 |
May | 0.810425E+09 | 26789056.31 | 0.783636E+09 | 0.705237E+09 | 0.584890E+09 |
June | 0.860021E+09 | 95345930.04 | 0.764675E+09 | 0.113822E+10 | 0.305050E+09 |
July | 0.840456E+09 | 54403534.87 | 0.786053E+09 | 0.112545E+10 | 0.297084E+09 |
August | 0.668942E+09 | 15824655.74 | 0.653117E+09 | 0.847340E+09 | 0.346919E+09 |
September | 0.543785E+09 | 127723.41 | 0.543657E+09 | 0.605313E+09 | 0.521640E+09 |
October | 0.402464E+09 | 0.00 | 0.402464E+09 | 0.197961E+09 | 0.115450E+10 |
November | 0.295666E+09 | 0.00 | 0.295666E+09 | 61893637.26 | 0.136592E+10 |
December | 0.258440E+09 | 0.00 | 0.258440E+09 | 27956843.07 | 0.175352E+10 |
Annual Sum or Average | 0.631651E+10 | 0.195676E+09 | 0.612084E+10 | 0.524745E+10 | 0.114865E+11 |
Minimum of Months | 0.258440E+09 | 0.00 | 0.258440E+09 | 27956843.07 | 0.297084E+09 |
Maximum of Months | 0.860021E+09 | 95345930.04 | 0.786053E+09 | 0.113822E+10 | 0.175352E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.961090E+09 | 0.588985E+09 | 0.372105E+09 | 0.821737E+09 | 0.157308E+10 |
February | 0.115315E+10 | 0.727979E+09 | 0.425170E+09 | 0.106112E+10 | 0.145541E+10 |
March | 0.154094E+10 | 0.898818E+09 | 0.642124E+09 | 0.153559E+10 | 0.123512E+10 |
April | 0.152934E+10 | 0.744970E+09 | 0.784373E+09 | 0.148949E+10 | 0.105935E+10 |
May | 0.184737E+10 | 0.771653E+09 | 0.107572E+10 | 0.207484E+10 | 0.643945E+09 |
June | 0.218127E+10 | 0.114511E+10 | 0.103616E+10 | 0.293826E+10 | 0.332531E+09 |
July | 0.204905E+10 | 0.975706E+09 | 0.107334E+10 | 0.278687E+10 | 0.316816E+09 |
August | 0.206675E+10 | 0.113829E+10 | 0.928456E+09 | 0.279150E+10 | 0.357910E+09 |
September | 0.166417E+10 | 0.904022E+09 | 0.760144E+09 | 0.212141E+10 | 0.547485E+09 |
October | 0.124536E+10 | 0.682385E+09 | 0.562975E+09 | 0.129109E+10 | 0.122362E+10 |
November | 0.938084E+09 | 0.529652E+09 | 0.408432E+09 | 0.852743E+09 | 0.141231E+10 |
December | 0.839201E+09 | 0.483440E+09 | 0.355762E+09 | 0.682489E+09 | 0.178271E+10 |
Annual Sum or Average | 0.180158E+11 | 0.959101E+10 | 0.842476E+10 | 0.204471E+11 | 0.119403E+11 |
Minimum of Months | 0.839201E+09 | 0.483440E+09 | 0.355762E+09 | 0.682489E+09 | 0.316816E+09 |
Maximum of Months | 0.218127E+10 | 0.114511E+10 | 0.107572E+10 | 0.293826E+10 | 0.178271E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.961090E+09 | 0.588985E+09 | 0.372105E+09 | 0.821737E+09 | 0.157308E+10 |
February | 0.115315E+10 | 0.727979E+09 | 0.425170E+09 | 0.106112E+10 | 0.145541E+10 |
March | 0.154094E+10 | 0.898818E+09 | 0.642124E+09 | 0.153559E+10 | 0.123512E+10 |
April | 0.152934E+10 | 0.744970E+09 | 0.784373E+09 | 0.148949E+10 | 0.105935E+10 |
May | 0.184737E+10 | 0.771653E+09 | 0.107572E+10 | 0.207484E+10 | 0.643945E+09 |
June | 0.218127E+10 | 0.114511E+10 | 0.103616E+10 | 0.293826E+10 | 0.332531E+09 |
July | 0.204905E+10 | 0.975706E+09 | 0.107334E+10 | 0.278687E+10 | 0.316816E+09 |
August | 0.206675E+10 | 0.113829E+10 | 0.928456E+09 | 0.279150E+10 | 0.357910E+09 |
September | 0.166417E+10 | 0.904022E+09 | 0.760144E+09 | 0.212141E+10 | 0.547485E+09 |
October | 0.124536E+10 | 0.682385E+09 | 0.562975E+09 | 0.129109E+10 | 0.122362E+10 |
November | 0.938084E+09 | 0.529652E+09 | 0.408432E+09 | 0.852743E+09 | 0.141231E+10 |
December | 0.839201E+09 | 0.483440E+09 | 0.355762E+09 | 0.682489E+09 | 0.178271E+10 |
Annual Sum or Average | 0.180158E+11 | 0.959101E+10 | 0.842476E+10 | 0.204471E+11 | 0.119403E+11 |
Minimum of Months | 0.839201E+09 | 0.483440E+09 | 0.355762E+09 | 0.682489E+09 | 0.316816E+09 |
Maximum of Months | 0.218127E+10 | 0.114511E+10 | 0.107572E+10 | 0.293826E+10 | 0.178271E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_2_WALL_EAST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.961072E+09 | 0.588974E+09 | 0.372098E+09 | 0.821722E+09 | 0.157305E+10 |
February | 0.115313E+10 | 0.727965E+09 | 0.425163E+09 | 0.106110E+10 | 0.145538E+10 |
March | 0.154091E+10 | 0.898802E+09 | 0.642113E+09 | 0.153556E+10 | 0.123510E+10 |
April | 0.152931E+10 | 0.744956E+09 | 0.784359E+09 | 0.148946E+10 | 0.105933E+10 |
May | 0.184734E+10 | 0.771639E+09 | 0.107570E+10 | 0.207480E+10 | 0.643933E+09 |
June | 0.218123E+10 | 0.114509E+10 | 0.103614E+10 | 0.293821E+10 | 0.332525E+09 |
July | 0.204901E+10 | 0.975688E+09 | 0.107332E+10 | 0.278682E+10 | 0.316810E+09 |
August | 0.206671E+10 | 0.113827E+10 | 0.928439E+09 | 0.279145E+10 | 0.357904E+09 |
September | 0.166413E+10 | 0.904005E+09 | 0.760130E+09 | 0.212137E+10 | 0.547475E+09 |
October | 0.124534E+10 | 0.682373E+09 | 0.562965E+09 | 0.129107E+10 | 0.122360E+10 |
November | 0.938067E+09 | 0.529642E+09 | 0.408425E+09 | 0.852728E+09 | 0.141228E+10 |
December | 0.839186E+09 | 0.483431E+09 | 0.355755E+09 | 0.682476E+09 | 0.178267E+10 |
Annual Sum or Average | 0.180154E+11 | 0.959083E+10 | 0.842461E+10 | 0.204468E+11 | 0.119401E+11 |
Minimum of Months | 0.839186E+09 | 0.483431E+09 | 0.355755E+09 | 0.682476E+09 | 0.316810E+09 |
Maximum of Months | 0.218123E+10 | 0.114509E+10 | 0.107570E+10 | 0.293821E+10 | 0.178267E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264735E+10 | 0.217773E+10 | 0.469622E+09 | 0.300257E+10 | 0.133863E+10 |
February | 0.229356E+10 | 0.182857E+10 | 0.464993E+09 | 0.258008E+10 | 0.125661E+10 |
March | 0.187217E+10 | 0.123178E+10 | 0.640392E+09 | 0.213074E+10 | 0.112399E+10 |
April | 0.117344E+10 | 0.471844E+09 | 0.701600E+09 | 0.120599E+10 | 0.999824E+09 |
May | 0.111118E+10 | 0.203670E+09 | 0.907509E+09 | 0.125557E+10 | 0.629662E+09 |
June | 0.991425E+09 | 0.181203E+09 | 0.810222E+09 | 0.142949E+10 | 0.334572E+09 |
July | 0.106645E+10 | 0.190970E+09 | 0.875481E+09 | 0.154103E+10 | 0.318285E+09 |
August | 0.135781E+10 | 0.567610E+09 | 0.790196E+09 | 0.196900E+10 | 0.364567E+09 |
September | 0.169059E+10 | 0.943337E+09 | 0.747255E+09 | 0.230184E+10 | 0.532596E+09 |
October | 0.208883E+10 | 0.148207E+10 | 0.606762E+09 | 0.252069E+10 | 0.110898E+10 |
November | 0.246285E+10 | 0.196325E+10 | 0.499605E+09 | 0.285830E+10 | 0.124282E+10 |
December | 0.243363E+10 | 0.196975E+10 | 0.463887E+09 | 0.269726E+10 | 0.151613E+10 |
Annual Sum or Average | 0.211893E+11 | 0.132118E+11 | 0.797753E+10 | 0.254926E+11 | 0.107667E+11 |
Minimum of Months | 0.991425E+09 | 0.181203E+09 | 0.463887E+09 | 0.120599E+10 | 0.318285E+09 |
Maximum of Months | 0.264735E+10 | 0.217773E+10 | 0.907509E+09 | 0.300257E+10 | 0.151613E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264733E+10 | 0.217771E+10 | 0.469620E+09 | 0.300255E+10 | 0.133863E+10 |
February | 0.229354E+10 | 0.182855E+10 | 0.464991E+09 | 0.258005E+10 | 0.125661E+10 |
March | 0.187216E+10 | 0.123177E+10 | 0.640389E+09 | 0.213072E+10 | 0.112399E+10 |
April | 0.117344E+10 | 0.471840E+09 | 0.701597E+09 | 0.120598E+10 | 0.999825E+09 |
May | 0.111117E+10 | 0.203668E+09 | 0.907505E+09 | 0.125556E+10 | 0.629661E+09 |
June | 0.991420E+09 | 0.181201E+09 | 0.810219E+09 | 0.142948E+10 | 0.334571E+09 |
July | 0.106645E+10 | 0.190968E+09 | 0.875477E+09 | 0.154102E+10 | 0.318285E+09 |
August | 0.135780E+10 | 0.567606E+09 | 0.790192E+09 | 0.196899E+10 | 0.364566E+09 |
September | 0.169058E+10 | 0.943330E+09 | 0.747251E+09 | 0.230183E+10 | 0.532595E+09 |
October | 0.208882E+10 | 0.148206E+10 | 0.606759E+09 | 0.252067E+10 | 0.110898E+10 |
November | 0.246284E+10 | 0.196323E+10 | 0.499603E+09 | 0.285828E+10 | 0.124282E+10 |
December | 0.243362E+10 | 0.196973E+10 | 0.463884E+09 | 0.269724E+10 | 0.151613E+10 |
Annual Sum or Average | 0.211892E+11 | 0.132117E+11 | 0.797749E+10 | 0.254924E+11 | 0.107667E+11 |
Minimum of Months | 0.991420E+09 | 0.181201E+09 | 0.463884E+09 | 0.120598E+10 | 0.318285E+09 |
Maximum of Months | 0.264733E+10 | 0.217771E+10 | 0.907505E+09 | 0.300255E+10 | 0.151613E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264735E+10 | 0.217773E+10 | 0.469622E+09 | 0.300257E+10 | 0.133863E+10 |
February | 0.229356E+10 | 0.182857E+10 | 0.464993E+09 | 0.258008E+10 | 0.125661E+10 |
March | 0.187217E+10 | 0.123178E+10 | 0.640392E+09 | 0.213074E+10 | 0.112399E+10 |
April | 0.117344E+10 | 0.471844E+09 | 0.701600E+09 | 0.120599E+10 | 0.999824E+09 |
May | 0.111118E+10 | 0.203670E+09 | 0.907509E+09 | 0.125557E+10 | 0.629662E+09 |
June | 0.991425E+09 | 0.181203E+09 | 0.810222E+09 | 0.142949E+10 | 0.334572E+09 |
July | 0.106645E+10 | 0.190970E+09 | 0.875481E+09 | 0.154103E+10 | 0.318285E+09 |
August | 0.135781E+10 | 0.567610E+09 | 0.790196E+09 | 0.196900E+10 | 0.364567E+09 |
September | 0.169059E+10 | 0.943337E+09 | 0.747255E+09 | 0.230184E+10 | 0.532596E+09 |
October | 0.208883E+10 | 0.148207E+10 | 0.606762E+09 | 0.252069E+10 | 0.110898E+10 |
November | 0.246285E+10 | 0.196325E+10 | 0.499605E+09 | 0.285830E+10 | 0.124282E+10 |
December | 0.243363E+10 | 0.196975E+10 | 0.463887E+09 | 0.269726E+10 | 0.151613E+10 |
Annual Sum or Average | 0.211893E+11 | 0.132118E+11 | 0.797753E+10 | 0.254926E+11 | 0.107667E+11 |
Minimum of Months | 0.991425E+09 | 0.181203E+09 | 0.463887E+09 | 0.120599E+10 | 0.318285E+09 |
Maximum of Months | 0.264735E+10 | 0.217773E+10 | 0.907509E+09 | 0.300257E+10 | 0.151613E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264733E+10 | 0.217771E+10 | 0.469620E+09 | 0.300255E+10 | 0.133863E+10 |
February | 0.229354E+10 | 0.182855E+10 | 0.464991E+09 | 0.258005E+10 | 0.125661E+10 |
March | 0.187216E+10 | 0.123177E+10 | 0.640389E+09 | 0.213072E+10 | 0.112399E+10 |
April | 0.117344E+10 | 0.471840E+09 | 0.701597E+09 | 0.120598E+10 | 0.999825E+09 |
May | 0.111117E+10 | 0.203668E+09 | 0.907505E+09 | 0.125556E+10 | 0.629661E+09 |
June | 0.991420E+09 | 0.181201E+09 | 0.810219E+09 | 0.142948E+10 | 0.334571E+09 |
July | 0.106645E+10 | 0.190968E+09 | 0.875477E+09 | 0.154102E+10 | 0.318285E+09 |
August | 0.135780E+10 | 0.567606E+09 | 0.790192E+09 | 0.196899E+10 | 0.364566E+09 |
September | 0.169058E+10 | 0.943330E+09 | 0.747251E+09 | 0.230183E+10 | 0.532595E+09 |
October | 0.208882E+10 | 0.148206E+10 | 0.606759E+09 | 0.252067E+10 | 0.110898E+10 |
November | 0.246284E+10 | 0.196323E+10 | 0.499603E+09 | 0.285828E+10 | 0.124282E+10 |
December | 0.243362E+10 | 0.196973E+10 | 0.463884E+09 | 0.269724E+10 | 0.151613E+10 |
Annual Sum or Average | 0.211892E+11 | 0.132117E+11 | 0.797749E+10 | 0.254924E+11 | 0.107667E+11 |
Minimum of Months | 0.991420E+09 | 0.181201E+09 | 0.463884E+09 | 0.120598E+10 | 0.318285E+09 |
Maximum of Months | 0.264733E+10 | 0.217771E+10 | 0.907505E+09 | 0.300255E+10 | 0.151613E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_1_WALL_SOUTH_WINDOW5
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.264723E+10 | 0.217763E+10 | 0.469602E+09 | 0.300244E+10 | 0.133857E+10 |
February | 0.229346E+10 | 0.182849E+10 | 0.464973E+09 | 0.257996E+10 | 0.125656E+10 |
March | 0.187209E+10 | 0.123172E+10 | 0.640365E+09 | 0.213064E+10 | 0.112394E+10 |
April | 0.117339E+10 | 0.471823E+09 | 0.701570E+09 | 0.120594E+10 | 0.999784E+09 |
May | 0.111113E+10 | 0.203661E+09 | 0.907471E+09 | 0.125552E+10 | 0.629636E+09 |
June | 0.991383E+09 | 0.181195E+09 | 0.810188E+09 | 0.142943E+10 | 0.334558E+09 |
July | 0.106640E+10 | 0.190961E+09 | 0.875443E+09 | 0.154097E+10 | 0.318272E+09 |
August | 0.135775E+10 | 0.567585E+09 | 0.790162E+09 | 0.196892E+10 | 0.364552E+09 |
September | 0.169052E+10 | 0.943295E+09 | 0.747223E+09 | 0.230174E+10 | 0.532574E+09 |
October | 0.208874E+10 | 0.148200E+10 | 0.606736E+09 | 0.252058E+10 | 0.110894E+10 |
November | 0.246275E+10 | 0.196316E+10 | 0.499584E+09 | 0.285818E+10 | 0.124277E+10 |
December | 0.243353E+10 | 0.196966E+10 | 0.463867E+09 | 0.269714E+10 | 0.151607E+10 |
Annual Sum or Average | 0.211884E+11 | 0.132112E+11 | 0.797718E+10 | 0.254915E+11 | 0.107662E+11 |
Minimum of Months | 0.991383E+09 | 0.181195E+09 | 0.463867E+09 | 0.120594E+10 | 0.318272E+09 |
Maximum of Months | 0.264723E+10 | 0.217763E+10 | 0.907471E+09 | 0.300244E+10 | 0.151607E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102238E+10 | 0.647838E+09 | 0.374546E+09 | 0.937401E+09 | 0.168599E+10 |
February | 0.111354E+10 | 0.690067E+09 | 0.423476E+09 | 0.101234E+10 | 0.157762E+10 |
March | 0.144359E+10 | 0.796460E+09 | 0.647128E+09 | 0.139167E+10 | 0.139748E+10 |
April | 0.131536E+10 | 0.556901E+09 | 0.758459E+09 | 0.119036E+10 | 0.125732E+10 |
May | 0.166130E+10 | 0.585669E+09 | 0.107563E+10 | 0.184428E+10 | 0.733994E+09 |
June | 0.196632E+10 | 0.946074E+09 | 0.102025E+10 | 0.265166E+10 | 0.421837E+09 |
July | 0.165549E+10 | 0.606376E+09 | 0.104912E+10 | 0.222505E+10 | 0.408001E+09 |
August | 0.172786E+10 | 0.853589E+09 | 0.874274E+09 | 0.226937E+10 | 0.485578E+09 |
September | 0.148267E+10 | 0.711042E+09 | 0.771633E+09 | 0.188479E+10 | 0.631142E+09 |
October | 0.128890E+10 | 0.736703E+09 | 0.552198E+09 | 0.135868E+10 | 0.134714E+10 |
November | 0.102349E+10 | 0.621388E+09 | 0.402106E+09 | 0.953022E+09 | 0.157388E+10 |
December | 0.854260E+09 | 0.504634E+09 | 0.349626E+09 | 0.688944E+09 | 0.200718E+10 |
Annual Sum or Average | 0.165552E+11 | 0.825674E+10 | 0.829844E+10 | 0.184076E+11 | 0.135272E+11 |
Minimum of Months | 0.854260E+09 | 0.504634E+09 | 0.349626E+09 | 0.688944E+09 | 0.408001E+09 |
Maximum of Months | 0.196632E+10 | 0.946074E+09 | 0.107563E+10 | 0.265166E+10 | 0.200718E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102238E+10 | 0.647838E+09 | 0.374546E+09 | 0.937401E+09 | 0.168599E+10 |
February | 0.111354E+10 | 0.690067E+09 | 0.423476E+09 | 0.101234E+10 | 0.157762E+10 |
March | 0.144359E+10 | 0.796460E+09 | 0.647128E+09 | 0.139167E+10 | 0.139748E+10 |
April | 0.131536E+10 | 0.556901E+09 | 0.758459E+09 | 0.119036E+10 | 0.125732E+10 |
May | 0.166130E+10 | 0.585669E+09 | 0.107563E+10 | 0.184428E+10 | 0.733994E+09 |
June | 0.196632E+10 | 0.946074E+09 | 0.102025E+10 | 0.265166E+10 | 0.421837E+09 |
July | 0.165549E+10 | 0.606376E+09 | 0.104912E+10 | 0.222505E+10 | 0.408001E+09 |
August | 0.172786E+10 | 0.853589E+09 | 0.874274E+09 | 0.226937E+10 | 0.485578E+09 |
September | 0.148267E+10 | 0.711042E+09 | 0.771633E+09 | 0.188479E+10 | 0.631142E+09 |
October | 0.128890E+10 | 0.736703E+09 | 0.552198E+09 | 0.135868E+10 | 0.134714E+10 |
November | 0.102349E+10 | 0.621388E+09 | 0.402106E+09 | 0.953022E+09 | 0.157388E+10 |
December | 0.854260E+09 | 0.504634E+09 | 0.349626E+09 | 0.688944E+09 | 0.200718E+10 |
Annual Sum or Average | 0.165552E+11 | 0.825674E+10 | 0.829844E+10 | 0.184076E+11 | 0.135272E+11 |
Minimum of Months | 0.854260E+09 | 0.504634E+09 | 0.349626E+09 | 0.688944E+09 | 0.408001E+09 |
Maximum of Months | 0.196632E+10 | 0.946074E+09 | 0.107563E+10 | 0.265166E+10 | 0.200718E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_BOT_ZN_4_WALL_WEST_WINDOW3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.102237E+10 | 0.647827E+09 | 0.374539E+09 | 0.937384E+09 | 0.168596E+10 |
February | 0.111352E+10 | 0.690054E+09 | 0.423468E+09 | 0.101232E+10 | 0.157759E+10 |
March | 0.144356E+10 | 0.796445E+09 | 0.647117E+09 | 0.139164E+10 | 0.139745E+10 |
April | 0.131534E+10 | 0.556891E+09 | 0.758445E+09 | 0.119034E+10 | 0.125730E+10 |
May | 0.166127E+10 | 0.585658E+09 | 0.107561E+10 | 0.184425E+10 | 0.733981E+09 |
June | 0.196629E+10 | 0.946057E+09 | 0.102023E+10 | 0.265161E+10 | 0.421830E+09 |
July | 0.165546E+10 | 0.606365E+09 | 0.104910E+10 | 0.222501E+10 | 0.407993E+09 |
August | 0.172783E+10 | 0.853573E+09 | 0.874258E+09 | 0.226933E+10 | 0.485569E+09 |
September | 0.148265E+10 | 0.711029E+09 | 0.771619E+09 | 0.188476E+10 | 0.631130E+09 |
October | 0.128888E+10 | 0.736689E+09 | 0.552187E+09 | 0.135865E+10 | 0.134711E+10 |
November | 0.102348E+10 | 0.621376E+09 | 0.402099E+09 | 0.953005E+09 | 0.157386E+10 |
December | 0.854244E+09 | 0.504625E+09 | 0.349619E+09 | 0.688932E+09 | 0.200714E+10 |
Annual Sum or Average | 0.165549E+11 | 0.825659E+10 | 0.829829E+10 | 0.184072E+11 | 0.135269E+11 |
Minimum of Months | 0.854244E+09 | 0.504625E+09 | 0.349619E+09 | 0.688932E+09 | 0.407993E+09 |
Maximum of Months | 0.196629E+10 | 0.946057E+09 | 0.107561E+10 | 0.265161E+10 | 0.200714E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138118E+10 | 0.00 | 0.138118E+10 | 0.252500E+09 | 0.700615E+10 |
February | 0.156797E+10 | 0.00 | 0.156797E+10 | 0.296849E+09 | 0.635732E+10 |
March | 0.236209E+10 | 0.00 | 0.236209E+10 | 0.106094E+10 | 0.535999E+10 |
April | 0.287075E+10 | 15925682.24 | 0.285482E+10 | 0.155061E+10 | 0.447454E+10 |
May | 0.405234E+10 | 0.133954E+09 | 0.391839E+10 | 0.360485E+10 | 0.277165E+10 |
June | 0.430032E+10 | 0.476761E+09 | 0.382356E+10 | 0.572709E+10 | 0.148751E+10 |
July | 0.420250E+10 | 0.272035E+09 | 0.393047E+10 | 0.567004E+10 | 0.145423E+10 |
August | 0.334487E+10 | 79128421.74 | 0.326574E+10 | 0.431116E+10 | 0.166300E+10 |
September | 0.271906E+10 | 638658.55 | 0.271842E+10 | 0.308860E+10 | 0.247428E+10 |
October | 0.201242E+10 | 0.00 | 0.201242E+10 | 0.110367E+10 | 0.528484E+10 |
November | 0.147840E+10 | 0.00 | 0.147840E+10 | 0.411147E+09 | 0.612531E+10 |
December | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.228565E+09 | 0.780006E+10 |
Annual Sum or Average | 0.315842E+11 | 0.978443E+09 | 0.306057E+11 | 0.273060E+11 | 0.522589E+11 |
Minimum of Months | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.228565E+09 | 0.145423E+10 |
Maximum of Months | 0.430032E+10 | 0.476761E+09 | 0.393047E+10 | 0.572709E+10 | 0.780006E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.288324E+10 | 0.176694E+10 | 0.111630E+10 | 0.253151E+10 | 0.439545E+10 |
February | 0.345941E+10 | 0.218391E+10 | 0.127550E+10 | 0.321874E+10 | 0.407503E+10 |
March | 0.462278E+10 | 0.269643E+10 | 0.192635E+10 | 0.463248E+10 | 0.345711E+10 |
April | 0.458798E+10 | 0.223489E+10 | 0.235309E+10 | 0.449707E+10 | 0.291730E+10 |
May | 0.554205E+10 | 0.231494E+10 | 0.322712E+10 | 0.621371E+10 | 0.186832E+10 |
June | 0.654375E+10 | 0.343529E+10 | 0.310845E+10 | 0.877240E+10 | 0.100469E+10 |
July | 0.614708E+10 | 0.292709E+10 | 0.321999E+10 | 0.831440E+10 | 0.983780E+09 |
August | 0.620017E+10 | 0.341483E+10 | 0.278534E+10 | 0.832929E+10 | 0.112622E+10 |
September | 0.499244E+10 | 0.271204E+10 | 0.228041E+10 | 0.634734E+10 | 0.159840E+10 |
October | 0.373604E+10 | 0.204714E+10 | 0.168891E+10 | 0.389025E+10 | 0.346554E+10 |
November | 0.281422E+10 | 0.158894E+10 | 0.122528E+10 | 0.261115E+10 | 0.394632E+10 |
December | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.212339E+10 | 0.493358E+10 |
Annual Sum or Average | 0.540468E+11 | 0.287727E+11 | 0.252740E+11 | 0.614817E+11 | 0.337717E+11 |
Minimum of Months | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.212339E+10 | 0.983780E+09 |
Maximum of Months | 0.654375E+10 | 0.343529E+10 | 0.322712E+10 | 0.877240E+10 | 0.493358E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132370E+11 | 0.108889E+11 | 0.234814E+10 | 0.149478E+11 | 0.660620E+10 |
February | 0.114680E+11 | 0.914303E+10 | 0.232499E+10 | 0.128309E+11 | 0.611737E+10 |
March | 0.936101E+10 | 0.615902E+10 | 0.320200E+10 | 0.106225E+11 | 0.539393E+10 |
April | 0.586731E+10 | 0.235927E+10 | 0.350804E+10 | 0.605766E+10 | 0.466997E+10 |
May | 0.555597E+10 | 0.101837E+10 | 0.453760E+10 | 0.627526E+10 | 0.306982E+10 |
June | 0.495718E+10 | 0.906033E+09 | 0.405114E+10 | 0.715476E+10 | 0.164309E+10 |
July | 0.533232E+10 | 0.954869E+09 | 0.437745E+10 | 0.771382E+10 | 0.157841E+10 |
August | 0.678912E+10 | 0.283811E+10 | 0.395101E+10 | 0.984267E+10 | 0.179931E+10 |
September | 0.845310E+10 | 0.471678E+10 | 0.373632E+10 | 0.114567E+11 | 0.262540E+10 |
October | 0.104444E+11 | 0.741051E+10 | 0.303385E+10 | 0.125465E+11 | 0.541723E+10 |
November | 0.123145E+11 | 0.981645E+10 | 0.249806E+10 | 0.142324E+11 | 0.606428E+10 |
December | 0.121684E+11 | 0.984894E+10 | 0.231946E+10 | 0.134834E+11 | 0.725245E+10 |
Annual Sum or Average | 0.105948E+12 | 0.660602E+11 | 0.398881E+11 | 0.127164E+12 | 0.522375E+11 |
Minimum of Months | 0.495718E+10 | 0.906033E+09 | 0.231946E+10 | 0.605766E+10 | 0.157841E+10 |
Maximum of Months | 0.132370E+11 | 0.108889E+11 | 0.453760E+10 | 0.149478E+11 | 0.725245E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_MID_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306712E+10 | 0.194350E+10 | 0.112363E+10 | 0.289810E+10 | 0.461375E+10 |
February | 0.334059E+10 | 0.207018E+10 | 0.127041E+10 | 0.313247E+10 | 0.422825E+10 |
March | 0.433072E+10 | 0.238936E+10 | 0.194137E+10 | 0.431297E+10 | 0.362607E+10 |
April | 0.394604E+10 | 0.167069E+10 | 0.227535E+10 | 0.373891E+10 | 0.308519E+10 |
May | 0.498384E+10 | 0.175699E+10 | 0.322685E+10 | 0.560054E+10 | 0.204171E+10 |
June | 0.589891E+10 | 0.283819E+10 | 0.306072E+10 | 0.800797E+10 | 0.117668E+10 |
July | 0.496642E+10 | 0.181911E+10 | 0.314731E+10 | 0.676386E+10 | 0.110948E+10 |
August | 0.518354E+10 | 0.256074E+10 | 0.262280E+10 | 0.695045E+10 | 0.124576E+10 |
September | 0.444798E+10 | 0.213310E+10 | 0.231488E+10 | 0.570156E+10 | 0.176135E+10 |
October | 0.386666E+10 | 0.221008E+10 | 0.165658E+10 | 0.417029E+10 | 0.361340E+10 |
November | 0.307045E+10 | 0.186414E+10 | 0.120631E+10 | 0.298436E+10 | 0.410602E+10 |
December | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.221374E+10 | 0.507643E+10 |
Annual Sum or Average | 0.496650E+11 | 0.247700E+11 | 0.248951E+11 | 0.564752E+11 | 0.356841E+11 |
Minimum of Months | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.221374E+10 | 0.110948E+10 |
Maximum of Months | 0.589891E+10 | 0.283819E+10 | 0.322685E+10 | 0.800797E+10 | 0.507643E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_3_WALL_NORTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.138118E+10 | 0.00 | 0.138118E+10 | 0.308973E+09 | 0.650761E+10 |
February | 0.156797E+10 | 0.00 | 0.156797E+10 | 0.342704E+09 | 0.600472E+10 |
March | 0.236209E+10 | 0.00 | 0.236209E+10 | 0.112373E+10 | 0.504229E+10 |
April | 0.287075E+10 | 15925682.24 | 0.285482E+10 | 0.162547E+10 | 0.411129E+10 |
May | 0.405234E+10 | 0.133954E+09 | 0.391839E+10 | 0.368517E+10 | 0.263874E+10 |
June | 0.430032E+10 | 0.476761E+09 | 0.382356E+10 | 0.569191E+10 | 0.148171E+10 |
July | 0.420250E+10 | 0.272035E+09 | 0.393047E+10 | 0.563082E+10 | 0.145518E+10 |
August | 0.334487E+10 | 79128421.74 | 0.326574E+10 | 0.428884E+10 | 0.164524E+10 |
September | 0.271906E+10 | 638658.55 | 0.271842E+10 | 0.310642E+10 | 0.238346E+10 |
October | 0.201242E+10 | 0.00 | 0.201242E+10 | 0.118659E+10 | 0.490298E+10 |
November | 0.147840E+10 | 0.00 | 0.147840E+10 | 0.485250E+09 | 0.566426E+10 |
December | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.262676E+09 | 0.738872E+10 |
Annual Sum or Average | 0.315842E+11 | 0.978443E+09 | 0.306057E+11 | 0.277385E+11 | 0.492262E+11 |
Minimum of Months | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.262676E+09 | 0.145518E+10 |
Maximum of Months | 0.430032E+10 | 0.476761E+09 | 0.393047E+10 | 0.569191E+10 | 0.738872E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_2_WALL_EAST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.288324E+10 | 0.176694E+10 | 0.111630E+10 | 0.261422E+10 | 0.408206E+10 |
February | 0.345941E+10 | 0.218391E+10 | 0.127550E+10 | 0.327337E+10 | 0.386155E+10 |
March | 0.462278E+10 | 0.269643E+10 | 0.192635E+10 | 0.467859E+10 | 0.327327E+10 |
April | 0.458798E+10 | 0.223489E+10 | 0.235309E+10 | 0.454498E+10 | 0.269950E+10 |
May | 0.554205E+10 | 0.231494E+10 | 0.322712E+10 | 0.624452E+10 | 0.179831E+10 |
June | 0.654375E+10 | 0.343529E+10 | 0.310845E+10 | 0.873792E+10 | 0.100621E+10 |
July | 0.614708E+10 | 0.292709E+10 | 0.321999E+10 | 0.827946E+10 | 0.988776E+09 |
August | 0.620017E+10 | 0.341483E+10 | 0.278534E+10 | 0.830241E+10 | 0.112326E+10 |
September | 0.499244E+10 | 0.271204E+10 | 0.228041E+10 | 0.634581E+10 | 0.155942E+10 |
October | 0.373604E+10 | 0.204714E+10 | 0.168891E+10 | 0.393382E+10 | 0.325099E+10 |
November | 0.281422E+10 | 0.158894E+10 | 0.122528E+10 | 0.268426E+10 | 0.367694E+10 |
December | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.218040E+10 | 0.468716E+10 |
Annual Sum or Average | 0.540468E+11 | 0.287727E+11 | 0.252740E+11 | 0.618198E+11 | 0.320075E+11 |
Minimum of Months | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.218040E+10 | 0.988776E+09 |
Maximum of Months | 0.654375E+10 | 0.343529E+10 | 0.322712E+10 | 0.873792E+10 | 0.468716E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_1_WALL_SOUTH_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.132370E+11 | 0.108889E+11 | 0.234814E+10 | 0.151073E+11 | 0.612597E+10 |
February | 0.114680E+11 | 0.914303E+10 | 0.232499E+10 | 0.129111E+11 | 0.578227E+10 |
March | 0.936101E+10 | 0.615902E+10 | 0.320200E+10 | 0.106838E+11 | 0.509143E+10 |
April | 0.586731E+10 | 0.235927E+10 | 0.350804E+10 | 0.612179E+10 | 0.431187E+10 |
May | 0.555597E+10 | 0.101837E+10 | 0.453760E+10 | 0.632771E+10 | 0.292552E+10 |
June | 0.495718E+10 | 0.906033E+09 | 0.405114E+10 | 0.712032E+10 | 0.163160E+10 |
July | 0.533232E+10 | 0.954869E+09 | 0.437745E+10 | 0.767554E+10 | 0.157474E+10 |
August | 0.678912E+10 | 0.283811E+10 | 0.395101E+10 | 0.980992E+10 | 0.178398E+10 |
September | 0.845310E+10 | 0.471678E+10 | 0.373632E+10 | 0.114508E+11 | 0.255281E+10 |
October | 0.104444E+11 | 0.741051E+10 | 0.303385E+10 | 0.126023E+11 | 0.508786E+10 |
November | 0.123145E+11 | 0.981645E+10 | 0.249806E+10 | 0.143386E+11 | 0.567215E+10 |
December | 0.121684E+11 | 0.984894E+10 | 0.231946E+10 | 0.135955E+11 | 0.684975E+10 |
Annual Sum or Average | 0.105948E+12 | 0.660602E+11 | 0.398881E+11 | 0.127745E+12 | 0.493899E+11 |
Minimum of Months | 0.495718E+10 | 0.906033E+09 | 0.231946E+10 | 0.612179E+10 | 0.157474E+10 |
Maximum of Months | 0.132370E+11 | 0.108889E+11 | 0.453760E+10 | 0.151073E+11 | 0.684975E+10 |
Report: WindowEnergyReportMonthly
For: PERIMETER_TOP_ZN_4_WALL_WEST_WINDOW
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.306712E+10 | 0.194350E+10 | 0.112363E+10 | 0.295289E+10 | 0.430670E+10 |
February | 0.334059E+10 | 0.207018E+10 | 0.127041E+10 | 0.316172E+10 | 0.402343E+10 |
March | 0.433072E+10 | 0.238936E+10 | 0.194137E+10 | 0.434205E+10 | 0.343900E+10 |
April | 0.394604E+10 | 0.167069E+10 | 0.227535E+10 | 0.377379E+10 | 0.287144E+10 |
May | 0.498384E+10 | 0.175699E+10 | 0.322685E+10 | 0.562838E+10 | 0.195916E+10 |
June | 0.589891E+10 | 0.283819E+10 | 0.306072E+10 | 0.798151E+10 | 0.117046E+10 |
July | 0.496642E+10 | 0.181911E+10 | 0.314731E+10 | 0.673724E+10 | 0.110558E+10 |
August | 0.518354E+10 | 0.256074E+10 | 0.262280E+10 | 0.693176E+10 | 0.123487E+10 |
September | 0.444798E+10 | 0.213310E+10 | 0.231488E+10 | 0.570500E+10 | 0.171143E+10 |
October | 0.386666E+10 | 0.221008E+10 | 0.165658E+10 | 0.420691E+10 | 0.340670E+10 |
November | 0.307045E+10 | 0.186414E+10 | 0.120631E+10 | 0.302909E+10 | 0.385944E+10 |
December | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.224502E+10 | 0.483937E+10 |
Annual Sum or Average | 0.496650E+11 | 0.247700E+11 | 0.248951E+11 | 0.566954E+11 | 0.339276E+11 |
Minimum of Months | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.224502E+10 | 0.110558E+10 |
Maximum of Months | 0.589891E+10 | 0.283819E+10 | 0.322685E+10 | 0.798151E+10 | 0.483937E+10 |
Report: WindowZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 67.43 | 2877.43 | 515.66 | 0.00 | 515.66 | 0.00 | 0.00 |
February | 87.26 | 2893.59 | 648.13 | 0.00 | 648.13 | 0.00 | 0.00 |
March | 339.88 | 2227.21 | 881.89 | 0.00 | 881.89 | 0.00 | 0.00 |
April | 535.66 | 1972.80 | 1107.52 | 6.14 | 1101.38 | 0.00 | 0.00 |
May | 1316.57 | 1091.90 | 1512.94 | 50.01 | 1462.93 | 0.00 | 0.00 |
June | 2195.71 | 588.46 | 1659.05 | 183.93 | 1475.12 | 0.00 | 0.00 |
July | 2101.04 | 554.61 | 1569.01 | 101.56 | 1467.44 | 0.00 | 0.00 |
August | 1581.86 | 647.64 | 1248.81 | 29.54 | 1219.27 | 0.00 | 0.00 |
September | 1167.70 | 1006.28 | 1049.00 | 0.25 | 1048.76 | 0.00 | 0.00 |
October | 369.56 | 2155.27 | 751.34 | 0.00 | 751.34 | 0.00 | 0.00 |
November | 119.40 | 2634.96 | 570.36 | 0.00 | 570.36 | 0.00 | 0.00 |
December | 52.19 | 3273.56 | 482.47 | 0.00 | 482.47 | 0.00 | 0.00 |
Annual Sum or Average | 832.01 | 1821.24 | 1001.51 | 31.03 | 970.49 | 0.00 | 0.00 |
Minimum of Months | 52.19 | 554.61 | 482.47 | 0.00 | 482.47 | 0.00 | 0.00 |
Maximum of Months | 2195.71 | 3273.56 | 1659.05 | 183.93 | 1475.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 920.40 | 1761.95 | 1076.48 | 659.70 | 416.78 | 0.00 | 0.00 |
February | 1315.87 | 1804.81 | 1429.99 | 902.75 | 527.24 | 0.00 | 0.00 |
March | 1719.96 | 1383.41 | 1725.96 | 1006.73 | 719.22 | 0.00 | 0.00 |
April | 1723.93 | 1226.09 | 1770.06 | 862.23 | 907.83 | 0.00 | 0.00 |
May | 2323.95 | 721.26 | 2069.17 | 864.30 | 1204.87 | 0.00 | 0.00 |
June | 3400.74 | 384.87 | 2524.60 | 1325.35 | 1199.25 | 0.00 | 0.00 |
July | 3121.47 | 354.85 | 2295.07 | 1092.85 | 1202.21 | 0.00 | 0.00 |
August | 3126.67 | 400.88 | 2314.89 | 1274.96 | 1039.93 | 0.00 | 0.00 |
September | 2455.32 | 633.66 | 1926.11 | 1046.31 | 879.79 | 0.00 | 0.00 |
October | 1446.11 | 1370.53 | 1394.88 | 764.32 | 630.57 | 0.00 | 0.00 |
November | 986.97 | 1634.60 | 1085.74 | 613.02 | 472.72 | 0.00 | 0.00 |
December | 764.43 | 1996.75 | 939.96 | 541.48 | 398.48 | 0.00 | 0.00 |
Annual Sum or Average | 1945.11 | 1135.86 | 1713.82 | 912.38 | 801.44 | 0.00 | 0.00 |
Minimum of Months | 764.43 | 354.85 | 939.96 | 541.48 | 398.48 | 0.00 | 0.00 |
Maximum of Months | 3400.74 | 1996.75 | 2524.60 | 1325.35 | 1204.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5605.09 | 2498.91 | 4941.97 | 4065.30 | 876.67 | 0.00 | 0.00 |
February | 5332.43 | 2597.14 | 4740.27 | 3779.24 | 961.04 | 0.00 | 0.00 |
March | 3977.58 | 2098.23 | 3494.90 | 2299.44 | 1195.46 | 0.00 | 0.00 |
April | 2326.35 | 1928.66 | 2263.56 | 910.18 | 1353.38 | 0.00 | 0.00 |
May | 2343.86 | 1175.43 | 2074.31 | 380.20 | 1694.11 | 0.00 | 0.00 |
June | 2757.47 | 645.39 | 1912.45 | 349.54 | 1562.91 | 0.00 | 0.00 |
July | 2876.75 | 594.17 | 1990.81 | 356.50 | 1634.32 | 0.00 | 0.00 |
August | 3675.67 | 680.56 | 2534.71 | 1059.59 | 1475.11 | 0.00 | 0.00 |
September | 4440.23 | 1027.37 | 3261.14 | 1819.69 | 1441.45 | 0.00 | 0.00 |
October | 4705.53 | 2070.22 | 3899.36 | 2766.68 | 1132.68 | 0.00 | 0.00 |
November | 5513.64 | 2397.39 | 4750.82 | 3787.09 | 963.73 | 0.00 | 0.00 |
December | 5035.15 | 2830.26 | 4543.02 | 3677.05 | 865.97 | 0.00 | 0.00 |
Annual Sum or Average | 4041.77 | 1707.03 | 3359.50 | 2094.69 | 1264.82 | 0.00 | 0.00 |
Minimum of Months | 2326.35 | 594.17 | 1912.45 | 349.54 | 865.97 | 0.00 | 0.00 |
Maximum of Months | 5605.09 | 2830.26 | 4941.97 | 4065.30 | 1694.11 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1049.95 | 1888.42 | 1145.14 | 725.62 | 419.52 | 0.00 | 0.00 |
February | 1255.37 | 1956.36 | 1380.87 | 855.73 | 525.14 | 0.00 | 0.00 |
March | 1558.76 | 1565.27 | 1616.91 | 892.09 | 724.83 | 0.00 | 0.00 |
April | 1377.72 | 1455.23 | 1522.40 | 644.56 | 877.84 | 0.00 | 0.00 |
May | 2065.71 | 822.12 | 1860.76 | 655.99 | 1204.77 | 0.00 | 0.00 |
June | 3069.03 | 488.23 | 2275.82 | 1094.99 | 1180.84 | 0.00 | 0.00 |
July | 2492.21 | 456.99 | 1854.26 | 679.18 | 1175.08 | 0.00 | 0.00 |
August | 2541.84 | 543.88 | 1935.32 | 956.08 | 979.24 | 0.00 | 0.00 |
September | 2181.46 | 730.48 | 1716.05 | 822.96 | 893.09 | 0.00 | 0.00 |
October | 1521.81 | 1508.88 | 1443.65 | 825.15 | 618.50 | 0.00 | 0.00 |
November | 1103.03 | 1821.61 | 1184.59 | 719.19 | 465.40 | 0.00 | 0.00 |
December | 771.66 | 2248.17 | 956.83 | 565.22 | 391.60 | 0.00 | 0.00 |
Annual Sum or Average | 1751.09 | 1286.82 | 1574.87 | 785.45 | 789.42 | 0.00 | 0.00 |
Minimum of Months | 771.66 | 456.99 | 956.83 | 565.22 | 391.60 | 0.00 | 0.00 |
Maximum of Months | 3069.03 | 2248.17 | 2275.82 | 1094.99 | 1204.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 94.27 | 2615.80 | 515.67 | 0.00 | 515.67 | 0.00 | 0.00 |
February | 122.71 | 2627.86 | 648.14 | 0.00 | 648.14 | 0.00 | 0.00 |
March | 396.11 | 2001.19 | 881.90 | 0.00 | 881.90 | 0.00 | 0.00 |
April | 598.23 | 1726.29 | 1107.54 | 6.14 | 1101.40 | 0.00 | 0.00 |
May | 1345.90 | 1034.81 | 1512.97 | 50.01 | 1462.96 | 0.00 | 0.00 |
June | 2209.52 | 573.89 | 1659.08 | 183.94 | 1475.14 | 0.00 | 0.00 |
July | 2116.95 | 542.95 | 1569.03 | 101.57 | 1467.47 | 0.00 | 0.00 |
August | 1609.60 | 620.89 | 1248.83 | 29.54 | 1219.29 | 0.00 | 0.00 |
September | 1191.59 | 954.58 | 1049.02 | 0.25 | 1048.77 | 0.00 | 0.00 |
October | 412.06 | 1973.13 | 751.35 | 0.00 | 751.35 | 0.00 | 0.00 |
November | 158.62 | 2363.16 | 570.37 | 0.00 | 570.37 | 0.00 | 0.00 |
December | 85.34 | 2912.21 | 482.48 | 0.00 | 482.48 | 0.00 | 0.00 |
Annual Sum or Average | 865.87 | 1657.12 | 1001.53 | 31.03 | 970.50 | 0.00 | 0.00 |
Minimum of Months | 85.34 | 542.95 | 482.48 | 0.00 | 482.48 | 0.00 | 0.00 |
Maximum of Months | 2209.52 | 2912.21 | 1659.08 | 183.94 | 1475.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 945.16 | 1641.07 | 1076.48 | 659.70 | 416.78 | 0.00 | 0.00 |
February | 1330.50 | 1684.45 | 1429.98 | 902.74 | 527.24 | 0.00 | 0.00 |
March | 1729.57 | 1290.74 | 1725.95 | 1006.73 | 719.22 | 0.00 | 0.00 |
April | 1734.98 | 1125.50 | 1770.05 | 862.22 | 907.83 | 0.00 | 0.00 |
May | 2319.94 | 697.55 | 2069.17 | 864.30 | 1204.87 | 0.00 | 0.00 |
June | 3384.41 | 387.61 | 2524.59 | 1325.35 | 1199.25 | 0.00 | 0.00 |
July | 3104.24 | 367.30 | 2295.06 | 1092.85 | 1202.21 | 0.00 | 0.00 |
August | 3109.80 | 420.48 | 2314.88 | 1274.95 | 1039.93 | 0.00 | 0.00 |
September | 2448.82 | 616.67 | 1926.10 | 1046.31 | 879.79 | 0.00 | 0.00 |
October | 1452.45 | 1293.89 | 1394.88 | 764.31 | 630.57 | 0.00 | 0.00 |
November | 1007.39 | 1522.50 | 1085.73 | 613.02 | 472.72 | 0.00 | 0.00 |
December | 792.78 | 1841.99 | 939.96 | 541.48 | 398.47 | 0.00 | 0.00 |
Annual Sum or Average | 1949.57 | 1070.90 | 1713.81 | 912.38 | 801.43 | 0.00 | 0.00 |
Minimum of Months | 792.78 | 367.30 | 939.96 | 541.48 | 398.47 | 0.00 | 0.00 |
Maximum of Months | 3384.41 | 1841.99 | 2524.59 | 1325.35 | 1204.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5580.85 | 2466.47 | 4942.13 | 4065.43 | 876.70 | 0.00 | 0.00 |
February | 5303.77 | 2528.67 | 4740.42 | 3779.36 | 961.06 | 0.00 | 0.00 |
March | 3965.98 | 2013.86 | 3495.00 | 2299.51 | 1195.49 | 0.00 | 0.00 |
April | 2337.06 | 1801.69 | 2263.62 | 910.21 | 1353.41 | 0.00 | 0.00 |
May | 2342.91 | 1146.14 | 2074.36 | 380.22 | 1694.14 | 0.00 | 0.00 |
June | 2760.32 | 633.91 | 1912.49 | 349.55 | 1562.94 | 0.00 | 0.00 |
July | 2880.01 | 589.31 | 1990.86 | 356.51 | 1634.35 | 0.00 | 0.00 |
August | 3674.83 | 671.79 | 2534.77 | 1059.63 | 1475.14 | 0.00 | 0.00 |
September | 4420.01 | 1012.89 | 3261.23 | 1819.75 | 1441.48 | 0.00 | 0.00 |
October | 4684.31 | 2022.56 | 3899.47 | 2766.77 | 1132.71 | 0.00 | 0.00 |
November | 5490.88 | 2339.62 | 4750.97 | 3787.21 | 963.76 | 0.00 | 0.00 |
December | 5034.13 | 2707.76 | 4543.16 | 3677.17 | 865.99 | 0.00 | 0.00 |
Annual Sum or Average | 4032.35 | 1656.44 | 3359.60 | 2094.76 | 1264.84 | 0.00 | 0.00 |
Minimum of Months | 2337.06 | 589.31 | 1912.49 | 349.55 | 865.99 | 0.00 | 0.00 |
Maximum of Months | 5580.85 | 2707.76 | 4942.13 | 4065.43 | 1694.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1082.03 | 1722.58 | 1145.13 | 725.62 | 419.51 | 0.00 | 0.00 |
February | 1294.84 | 1747.79 | 1380.87 | 855.73 | 525.14 | 0.00 | 0.00 |
March | 1610.28 | 1353.82 | 1616.91 | 892.08 | 724.82 | 0.00 | 0.00 |
April | 1442.48 | 1190.28 | 1522.39 | 644.55 | 877.84 | 0.00 | 0.00 |
May | 2091.00 | 762.29 | 1860.75 | 655.98 | 1204.77 | 0.00 | 0.00 |
June | 3089.49 | 453.97 | 2275.81 | 1094.98 | 1180.83 | 0.00 | 0.00 |
July | 2525.34 | 414.23 | 1854.25 | 679.18 | 1175.07 | 0.00 | 0.00 |
August | 2595.00 | 465.11 | 1935.31 | 956.07 | 979.24 | 0.00 | 0.00 |
September | 2199.67 | 679.53 | 1716.04 | 822.96 | 893.08 | 0.00 | 0.00 |
October | 1557.01 | 1349.09 | 1443.65 | 825.15 | 618.49 | 0.00 | 0.00 |
November | 1151.37 | 1584.11 | 1184.59 | 719.19 | 465.40 | 0.00 | 0.00 |
December | 826.51 | 1895.32 | 956.82 | 565.22 | 391.60 | 0.00 | 0.00 |
Annual Sum or Average | 1790.82 | 1131.54 | 1574.87 | 785.45 | 789.42 | 0.00 | 0.00 |
Minimum of Months | 826.51 | 414.23 | 956.82 | 565.22 | 391.60 | 0.00 | 0.00 |
Maximum of Months | 3089.49 | 1895.32 | 2275.81 | 1094.98 | 1204.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 115.36 | 2429.66 | 515.67 | 0.00 | 515.67 | 0.00 | 0.00 |
February | 141.66 | 2482.11 | 648.14 | 0.00 | 648.14 | 0.00 | 0.00 |
March | 419.55 | 1882.58 | 881.90 | 0.00 | 881.90 | 0.00 | 0.00 |
April | 627.11 | 1586.15 | 1107.54 | 6.14 | 1101.40 | 0.00 | 0.00 |
May | 1375.88 | 985.19 | 1512.97 | 50.01 | 1462.96 | 0.00 | 0.00 |
June | 2195.95 | 571.65 | 1659.08 | 183.94 | 1475.14 | 0.00 | 0.00 |
July | 2102.31 | 543.30 | 1569.03 | 101.57 | 1467.47 | 0.00 | 0.00 |
August | 1601.27 | 614.26 | 1248.83 | 29.54 | 1219.29 | 0.00 | 0.00 |
September | 1198.46 | 919.54 | 1049.02 | 0.25 | 1048.77 | 0.00 | 0.00 |
October | 443.02 | 1830.56 | 751.35 | 0.00 | 751.35 | 0.00 | 0.00 |
November | 187.21 | 2185.29 | 570.37 | 0.00 | 570.37 | 0.00 | 0.00 |
December | 98.07 | 2758.63 | 482.48 | 0.00 | 482.48 | 0.00 | 0.00 |
Annual Sum or Average | 879.58 | 1560.95 | 1001.53 | 31.03 | 970.50 | 0.00 | 0.00 |
Minimum of Months | 98.07 | 543.30 | 482.48 | 0.00 | 482.48 | 0.00 | 0.00 |
Maximum of Months | 2195.95 | 2758.63 | 1659.08 | 183.94 | 1475.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 976.04 | 1524.06 | 1076.48 | 659.70 | 416.78 | 0.00 | 0.00 |
February | 1353.08 | 1596.21 | 1429.98 | 902.74 | 527.24 | 0.00 | 0.00 |
March | 1746.79 | 1222.10 | 1725.95 | 1006.73 | 719.22 | 0.00 | 0.00 |
April | 1753.46 | 1041.47 | 1770.05 | 862.22 | 907.83 | 0.00 | 0.00 |
May | 2331.44 | 671.41 | 2069.17 | 864.30 | 1204.87 | 0.00 | 0.00 |
June | 3371.11 | 388.20 | 2524.59 | 1325.35 | 1199.25 | 0.00 | 0.00 |
July | 3091.20 | 369.17 | 2295.06 | 1092.85 | 1202.21 | 0.00 | 0.00 |
August | 3099.76 | 419.38 | 2314.88 | 1274.95 | 1039.93 | 0.00 | 0.00 |
September | 2448.23 | 601.63 | 1926.10 | 1046.31 | 879.79 | 0.00 | 0.00 |
October | 1468.72 | 1213.78 | 1394.88 | 764.31 | 630.57 | 0.00 | 0.00 |
November | 1035.59 | 1418.57 | 1085.73 | 613.02 | 472.72 | 0.00 | 0.00 |
December | 814.07 | 1749.99 | 939.96 | 541.48 | 398.47 | 0.00 | 0.00 |
Annual Sum or Average | 1960.29 | 1014.95 | 1713.81 | 912.38 | 801.43 | 0.00 | 0.00 |
Minimum of Months | 814.07 | 369.17 | 939.96 | 541.48 | 398.47 | 0.00 | 0.00 |
Maximum of Months | 3371.11 | 1749.99 | 2524.59 | 1325.35 | 1204.87 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 5640.41 | 2287.17 | 4942.13 | 4065.43 | 876.70 | 0.00 | 0.00 |
February | 5336.92 | 2390.16 | 4740.42 | 3779.36 | 961.06 | 0.00 | 0.00 |
March | 3988.88 | 1900.92 | 3495.00 | 2299.51 | 1195.49 | 0.00 | 0.00 |
April | 2361.80 | 1663.53 | 2263.62 | 910.21 | 1353.41 | 0.00 | 0.00 |
May | 2362.50 | 1092.26 | 2074.36 | 380.22 | 1694.14 | 0.00 | 0.00 |
June | 2747.04 | 629.47 | 1912.49 | 349.55 | 1562.94 | 0.00 | 0.00 |
July | 2865.72 | 587.94 | 1990.86 | 356.51 | 1634.35 | 0.00 | 0.00 |
August | 3662.61 | 666.06 | 2534.77 | 1059.63 | 1475.14 | 0.00 | 0.00 |
September | 4417.76 | 984.88 | 3261.23 | 1819.75 | 1441.48 | 0.00 | 0.00 |
October | 4705.17 | 1899.59 | 3899.47 | 2766.77 | 1132.71 | 0.00 | 0.00 |
November | 5531.86 | 2188.33 | 4750.97 | 3787.21 | 963.76 | 0.00 | 0.00 |
December | 5075.97 | 2557.40 | 4543.16 | 3677.17 | 865.99 | 0.00 | 0.00 |
Annual Sum or Average | 4050.76 | 1566.14 | 3359.60 | 2094.76 | 1264.84 | 0.00 | 0.00 |
Minimum of Months | 2361.80 | 587.94 | 1912.49 | 349.55 | 865.99 | 0.00 | 0.00 |
Maximum of Months | 5640.41 | 2557.40 | 4942.13 | 4065.43 | 1694.14 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 1102.48 | 1607.94 | 1145.13 | 725.62 | 419.51 | 0.00 | 0.00 |
February | 1306.93 | 1663.12 | 1380.87 | 855.73 | 525.14 | 0.00 | 0.00 |
March | 1621.14 | 1283.97 | 1616.91 | 892.08 | 724.82 | 0.00 | 0.00 |
April | 1455.94 | 1107.81 | 1522.39 | 644.55 | 877.84 | 0.00 | 0.00 |
May | 2101.40 | 731.47 | 1860.75 | 655.98 | 1204.77 | 0.00 | 0.00 |
June | 3079.29 | 451.57 | 2275.81 | 1094.98 | 1180.83 | 0.00 | 0.00 |
July | 2515.40 | 412.78 | 1854.25 | 679.18 | 1175.07 | 0.00 | 0.00 |
August | 2588.02 | 461.05 | 1935.31 | 956.07 | 979.24 | 0.00 | 0.00 |
September | 2201.00 | 660.27 | 1716.04 | 822.96 | 893.08 | 0.00 | 0.00 |
October | 1570.68 | 1271.92 | 1443.65 | 825.15 | 618.49 | 0.00 | 0.00 |
November | 1168.63 | 1488.98 | 1184.59 | 719.19 | 465.40 | 0.00 | 0.00 |
December | 838.19 | 1806.81 | 956.82 | 565.22 | 391.60 | 0.00 | 0.00 |
Annual Sum or Average | 1797.80 | 1075.84 | 1574.87 | 785.45 | 789.42 | 0.00 | 0.00 |
Minimum of Months | 838.19 | 412.78 | 956.82 | 565.22 | 391.60 | 0.00 | 0.00 |
Maximum of Months | 3079.29 | 1806.81 | 2275.81 | 1094.98 | 1204.77 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.180594E+09 | 0.770690E+10 | 0.138115E+10 | 0.00 | 0.138115E+10 | 0.00 | 0.00 |
February | 0.211100E+09 | 0.700017E+10 | 0.156795E+10 | 0.00 | 0.156795E+10 | 0.00 | 0.00 |
March | 0.910346E+09 | 0.596535E+10 | 0.236205E+10 | 0.00 | 0.236205E+10 | 0.00 | 0.00 |
April | 0.138844E+10 | 0.511349E+10 | 0.287070E+10 | 15925207.31 | 0.285477E+10 | 0.00 | 0.00 |
May | 0.352631E+10 | 0.292455E+10 | 0.405226E+10 | 0.133950E+09 | 0.391831E+10 | 0.00 | 0.00 |
June | 0.569129E+10 | 0.152530E+10 | 0.430025E+10 | 0.476746E+09 | 0.382350E+10 | 0.00 | 0.00 |
July | 0.562743E+10 | 0.148547E+10 | 0.420243E+10 | 0.272027E+09 | 0.393040E+10 | 0.00 | 0.00 |
August | 0.423685E+10 | 0.173465E+10 | 0.334482E+10 | 79126061.97 | 0.326570E+10 | 0.00 | 0.00 |
September | 0.302667E+10 | 0.260829E+10 | 0.271901E+10 | 638639.51 | 0.271838E+10 | 0.00 | 0.00 |
October | 0.989839E+09 | 0.577267E+10 | 0.201239E+10 | 0.00 | 0.201239E+10 | 0.00 | 0.00 |
November | 0.309479E+09 | 0.682983E+10 | 0.147838E+10 | 0.00 | 0.147838E+10 | 0.00 | 0.00 |
December | 0.139789E+09 | 0.876790E+10 | 0.129224E+10 | 0.00 | 0.129224E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.262381E+11 | 0.574346E+11 | 0.315836E+11 | 0.978414E+09 | 0.306052E+11 | 0.00 | 0.00 |
Minimum of Months | 0.139789E+09 | 0.148547E+10 | 0.129224E+10 | 0.00 | 0.129224E+10 | 0.00 | 0.00 |
Maximum of Months | 0.569129E+10 | 0.876790E+10 | 0.430025E+10 | 0.476746E+09 | 0.393040E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246520E+10 | 0.471921E+10 | 0.288325E+10 | 0.176694E+10 | 0.111631E+10 | 0.00 | 0.00 |
February | 0.318334E+10 | 0.436620E+10 | 0.345943E+10 | 0.218392E+10 | 0.127550E+10 | 0.00 | 0.00 |
March | 0.460673E+10 | 0.370533E+10 | 0.462280E+10 | 0.269644E+10 | 0.192636E+10 | 0.00 | 0.00 |
April | 0.446844E+10 | 0.317802E+10 | 0.458800E+10 | 0.223490E+10 | 0.235310E+10 | 0.00 | 0.00 |
May | 0.622448E+10 | 0.193182E+10 | 0.554208E+10 | 0.231495E+10 | 0.322713E+10 | 0.00 | 0.00 |
June | 0.881473E+10 | 0.997588E+09 | 0.654377E+10 | 0.343531E+10 | 0.310847E+10 | 0.00 | 0.00 |
July | 0.836055E+10 | 0.950443E+09 | 0.614711E+10 | 0.292710E+10 | 0.322001E+10 | 0.00 | 0.00 |
August | 0.837446E+10 | 0.107372E+10 | 0.620020E+10 | 0.341485E+10 | 0.278535E+10 | 0.00 | 0.00 |
September | 0.636418E+10 | 0.164245E+10 | 0.499247E+10 | 0.271205E+10 | 0.228042E+10 | 0.00 | 0.00 |
October | 0.387325E+10 | 0.367083E+10 | 0.373606E+10 | 0.204714E+10 | 0.168891E+10 | 0.00 | 0.00 |
November | 0.255821E+10 | 0.423690E+10 | 0.281424E+10 | 0.158895E+10 | 0.122529E+10 | 0.00 | 0.00 |
December | 0.204745E+10 | 0.534809E+10 | 0.251759E+10 | 0.145031E+10 | 0.106728E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.613410E+11 | 0.358206E+11 | 0.540470E+11 | 0.287728E+11 | 0.252741E+11 | 0.00 | 0.00 |
Minimum of Months | 0.204745E+10 | 0.950443E+09 | 0.251759E+10 | 0.145031E+10 | 0.106728E+10 | 0.00 | 0.00 |
Maximum of Months | 0.881473E+10 | 0.534809E+10 | 0.654377E+10 | 0.343531E+10 | 0.322713E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.150127E+11 | 0.669309E+10 | 0.132366E+11 | 0.108885E+11 | 0.234809E+10 | 0.00 | 0.00 |
February | 0.129002E+11 | 0.628300E+10 | 0.114677E+11 | 0.914273E+10 | 0.232494E+10 | 0.00 | 0.00 |
March | 0.106536E+11 | 0.561991E+10 | 0.936074E+10 | 0.615881E+10 | 0.320193E+10 | 0.00 | 0.00 |
April | 0.602990E+10 | 0.499908E+10 | 0.586716E+10 | 0.235919E+10 | 0.350796E+10 | 0.00 | 0.00 |
May | 0.627779E+10 | 0.314828E+10 | 0.555583E+10 | 0.101834E+10 | 0.453750E+10 | 0.00 | 0.00 |
June | 0.714737E+10 | 0.167284E+10 | 0.495707E+10 | 0.906003E+09 | 0.405107E+10 | 0.00 | 0.00 |
July | 0.770508E+10 | 0.159141E+10 | 0.533220E+10 | 0.954838E+09 | 0.437736E+10 | 0.00 | 0.00 |
August | 0.984491E+10 | 0.182282E+10 | 0.678896E+10 | 0.283802E+10 | 0.395094E+10 | 0.00 | 0.00 |
September | 0.115091E+11 | 0.266296E+10 | 0.845287E+10 | 0.471663E+10 | 0.373624E+10 | 0.00 | 0.00 |
October | 0.126033E+11 | 0.554487E+10 | 0.104440E+11 | 0.741026E+10 | 0.303378E+10 | 0.00 | 0.00 |
November | 0.142913E+11 | 0.621404E+10 | 0.123141E+11 | 0.981613E+10 | 0.249800E+10 | 0.00 | 0.00 |
December | 0.134861E+11 | 0.758057E+10 | 0.121680E+11 | 0.984862E+10 | 0.231941E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127461E+12 | 0.538329E+11 | 0.105945E+12 | 0.660581E+11 | 0.398872E+11 | 0.00 | 0.00 |
Minimum of Months | 0.602990E+10 | 0.159141E+10 | 0.495707E+10 | 0.906003E+09 | 0.231941E+10 | 0.00 | 0.00 |
Maximum of Months | 0.150127E+11 | 0.758057E+10 | 0.132366E+11 | 0.108885E+11 | 0.453750E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.281219E+10 | 0.505793E+10 | 0.306713E+10 | 0.194350E+10 | 0.112363E+10 | 0.00 | 0.00 |
February | 0.303699E+10 | 0.473283E+10 | 0.334061E+10 | 0.207019E+10 | 0.127042E+10 | 0.00 | 0.00 |
March | 0.417498E+10 | 0.419241E+10 | 0.433074E+10 | 0.238937E+10 | 0.194137E+10 | 0.00 | 0.00 |
April | 0.357106E+10 | 0.377194E+10 | 0.394606E+10 | 0.167069E+10 | 0.227536E+10 | 0.00 | 0.00 |
May | 0.553281E+10 | 0.220197E+10 | 0.498386E+10 | 0.175700E+10 | 0.322686E+10 | 0.00 | 0.00 |
June | 0.795492E+10 | 0.126550E+10 | 0.589893E+10 | 0.283821E+10 | 0.306073E+10 | 0.00 | 0.00 |
July | 0.667512E+10 | 0.122400E+10 | 0.496644E+10 | 0.181912E+10 | 0.314733E+10 | 0.00 | 0.00 |
August | 0.680807E+10 | 0.145673E+10 | 0.518356E+10 | 0.256075E+10 | 0.262281E+10 | 0.00 | 0.00 |
September | 0.565433E+10 | 0.189341E+10 | 0.444800E+10 | 0.213311E+10 | 0.231489E+10 | 0.00 | 0.00 |
October | 0.407601E+10 | 0.404138E+10 | 0.386668E+10 | 0.221009E+10 | 0.165658E+10 | 0.00 | 0.00 |
November | 0.285905E+10 | 0.472162E+10 | 0.307046E+10 | 0.186415E+10 | 0.120631E+10 | 0.00 | 0.00 |
December | 0.206682E+10 | 0.602149E+10 | 0.256276E+10 | 0.151389E+10 | 0.104887E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.552224E+11 | 0.405812E+11 | 0.496652E+11 | 0.247701E+11 | 0.248952E+11 | 0.00 | 0.00 |
Minimum of Months | 0.206682E+10 | 0.122400E+10 | 0.256276E+10 | 0.151389E+10 | 0.104887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.795492E+10 | 0.602149E+10 | 0.589893E+10 | 0.283821E+10 | 0.322686E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.252500E+09 | 0.700615E+10 | 0.138118E+10 | 0.00 | 0.138118E+10 | 0.00 | 0.00 |
February | 0.296849E+09 | 0.635732E+10 | 0.156797E+10 | 0.00 | 0.156797E+10 | 0.00 | 0.00 |
March | 0.106094E+10 | 0.535999E+10 | 0.236209E+10 | 0.00 | 0.236209E+10 | 0.00 | 0.00 |
April | 0.155061E+10 | 0.447454E+10 | 0.287075E+10 | 15925682.24 | 0.285482E+10 | 0.00 | 0.00 |
May | 0.360485E+10 | 0.277165E+10 | 0.405234E+10 | 0.133954E+09 | 0.391839E+10 | 0.00 | 0.00 |
June | 0.572709E+10 | 0.148751E+10 | 0.430032E+10 | 0.476761E+09 | 0.382356E+10 | 0.00 | 0.00 |
July | 0.567004E+10 | 0.145423E+10 | 0.420250E+10 | 0.272035E+09 | 0.393047E+10 | 0.00 | 0.00 |
August | 0.431116E+10 | 0.166300E+10 | 0.334487E+10 | 79128421.74 | 0.326574E+10 | 0.00 | 0.00 |
September | 0.308860E+10 | 0.247428E+10 | 0.271906E+10 | 638658.55 | 0.271842E+10 | 0.00 | 0.00 |
October | 0.110367E+10 | 0.528484E+10 | 0.201242E+10 | 0.00 | 0.201242E+10 | 0.00 | 0.00 |
November | 0.411147E+09 | 0.612531E+10 | 0.147840E+10 | 0.00 | 0.147840E+10 | 0.00 | 0.00 |
December | 0.228565E+09 | 0.780006E+10 | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.273060E+11 | 0.522589E+11 | 0.315842E+11 | 0.978443E+09 | 0.306057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.228565E+09 | 0.145423E+10 | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.572709E+10 | 0.780006E+10 | 0.430032E+10 | 0.476761E+09 | 0.393047E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.253151E+10 | 0.439545E+10 | 0.288324E+10 | 0.176694E+10 | 0.111630E+10 | 0.00 | 0.00 |
February | 0.321874E+10 | 0.407503E+10 | 0.345941E+10 | 0.218391E+10 | 0.127550E+10 | 0.00 | 0.00 |
March | 0.463248E+10 | 0.345711E+10 | 0.462278E+10 | 0.269643E+10 | 0.192635E+10 | 0.00 | 0.00 |
April | 0.449707E+10 | 0.291730E+10 | 0.458798E+10 | 0.223489E+10 | 0.235309E+10 | 0.00 | 0.00 |
May | 0.621371E+10 | 0.186832E+10 | 0.554205E+10 | 0.231494E+10 | 0.322712E+10 | 0.00 | 0.00 |
June | 0.877240E+10 | 0.100469E+10 | 0.654375E+10 | 0.343529E+10 | 0.310845E+10 | 0.00 | 0.00 |
July | 0.831440E+10 | 0.983780E+09 | 0.614708E+10 | 0.292709E+10 | 0.321999E+10 | 0.00 | 0.00 |
August | 0.832929E+10 | 0.112622E+10 | 0.620017E+10 | 0.341483E+10 | 0.278534E+10 | 0.00 | 0.00 |
September | 0.634734E+10 | 0.159840E+10 | 0.499244E+10 | 0.271204E+10 | 0.228041E+10 | 0.00 | 0.00 |
October | 0.389025E+10 | 0.346554E+10 | 0.373604E+10 | 0.204714E+10 | 0.168891E+10 | 0.00 | 0.00 |
November | 0.261115E+10 | 0.394632E+10 | 0.281422E+10 | 0.158894E+10 | 0.122528E+10 | 0.00 | 0.00 |
December | 0.212339E+10 | 0.493358E+10 | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.614817E+11 | 0.337717E+11 | 0.540468E+11 | 0.287727E+11 | 0.252740E+11 | 0.00 | 0.00 |
Minimum of Months | 0.212339E+10 | 0.983780E+09 | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.00 | 0.00 |
Maximum of Months | 0.877240E+10 | 0.493358E+10 | 0.654375E+10 | 0.343529E+10 | 0.322712E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.149478E+11 | 0.660620E+10 | 0.132370E+11 | 0.108889E+11 | 0.234814E+10 | 0.00 | 0.00 |
February | 0.128309E+11 | 0.611737E+10 | 0.114680E+11 | 0.914303E+10 | 0.232499E+10 | 0.00 | 0.00 |
March | 0.106225E+11 | 0.539393E+10 | 0.936101E+10 | 0.615902E+10 | 0.320200E+10 | 0.00 | 0.00 |
April | 0.605766E+10 | 0.466997E+10 | 0.586731E+10 | 0.235927E+10 | 0.350804E+10 | 0.00 | 0.00 |
May | 0.627526E+10 | 0.306982E+10 | 0.555597E+10 | 0.101837E+10 | 0.453760E+10 | 0.00 | 0.00 |
June | 0.715476E+10 | 0.164309E+10 | 0.495718E+10 | 0.906033E+09 | 0.405114E+10 | 0.00 | 0.00 |
July | 0.771382E+10 | 0.157841E+10 | 0.533232E+10 | 0.954869E+09 | 0.437745E+10 | 0.00 | 0.00 |
August | 0.984267E+10 | 0.179931E+10 | 0.678912E+10 | 0.283811E+10 | 0.395101E+10 | 0.00 | 0.00 |
September | 0.114567E+11 | 0.262540E+10 | 0.845310E+10 | 0.471678E+10 | 0.373632E+10 | 0.00 | 0.00 |
October | 0.125465E+11 | 0.541723E+10 | 0.104444E+11 | 0.741051E+10 | 0.303385E+10 | 0.00 | 0.00 |
November | 0.142324E+11 | 0.606428E+10 | 0.123145E+11 | 0.981645E+10 | 0.249806E+10 | 0.00 | 0.00 |
December | 0.134834E+11 | 0.725245E+10 | 0.121684E+11 | 0.984894E+10 | 0.231946E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127164E+12 | 0.522375E+11 | 0.105948E+12 | 0.660602E+11 | 0.398881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.605766E+10 | 0.157841E+10 | 0.495718E+10 | 0.906033E+09 | 0.231946E+10 | 0.00 | 0.00 |
Maximum of Months | 0.149478E+11 | 0.725245E+10 | 0.132370E+11 | 0.108889E+11 | 0.453760E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.289810E+10 | 0.461375E+10 | 0.306712E+10 | 0.194350E+10 | 0.112363E+10 | 0.00 | 0.00 |
February | 0.313247E+10 | 0.422825E+10 | 0.334059E+10 | 0.207018E+10 | 0.127041E+10 | 0.00 | 0.00 |
March | 0.431297E+10 | 0.362607E+10 | 0.433072E+10 | 0.238936E+10 | 0.194137E+10 | 0.00 | 0.00 |
April | 0.373891E+10 | 0.308519E+10 | 0.394604E+10 | 0.167069E+10 | 0.227535E+10 | 0.00 | 0.00 |
May | 0.560054E+10 | 0.204171E+10 | 0.498384E+10 | 0.175699E+10 | 0.322685E+10 | 0.00 | 0.00 |
June | 0.800797E+10 | 0.117668E+10 | 0.589891E+10 | 0.283819E+10 | 0.306072E+10 | 0.00 | 0.00 |
July | 0.676386E+10 | 0.110948E+10 | 0.496642E+10 | 0.181911E+10 | 0.314731E+10 | 0.00 | 0.00 |
August | 0.695045E+10 | 0.124576E+10 | 0.518354E+10 | 0.256074E+10 | 0.262280E+10 | 0.00 | 0.00 |
September | 0.570156E+10 | 0.176135E+10 | 0.444798E+10 | 0.213310E+10 | 0.231488E+10 | 0.00 | 0.00 |
October | 0.417029E+10 | 0.361340E+10 | 0.386666E+10 | 0.221008E+10 | 0.165658E+10 | 0.00 | 0.00 |
November | 0.298436E+10 | 0.410602E+10 | 0.307045E+10 | 0.186414E+10 | 0.120631E+10 | 0.00 | 0.00 |
December | 0.221374E+10 | 0.507643E+10 | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.564752E+11 | 0.356841E+11 | 0.496650E+11 | 0.247700E+11 | 0.248951E+11 | 0.00 | 0.00 |
Minimum of Months | 0.221374E+10 | 0.110948E+10 | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.800797E+10 | 0.507643E+10 | 0.589891E+10 | 0.283819E+10 | 0.322685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.308973E+09 | 0.650761E+10 | 0.138118E+10 | 0.00 | 0.138118E+10 | 0.00 | 0.00 |
February | 0.342704E+09 | 0.600472E+10 | 0.156797E+10 | 0.00 | 0.156797E+10 | 0.00 | 0.00 |
March | 0.112373E+10 | 0.504229E+10 | 0.236209E+10 | 0.00 | 0.236209E+10 | 0.00 | 0.00 |
April | 0.162547E+10 | 0.411129E+10 | 0.287075E+10 | 15925682.24 | 0.285482E+10 | 0.00 | 0.00 |
May | 0.368517E+10 | 0.263874E+10 | 0.405234E+10 | 0.133954E+09 | 0.391839E+10 | 0.00 | 0.00 |
June | 0.569191E+10 | 0.148171E+10 | 0.430032E+10 | 0.476761E+09 | 0.382356E+10 | 0.00 | 0.00 |
July | 0.563082E+10 | 0.145518E+10 | 0.420250E+10 | 0.272035E+09 | 0.393047E+10 | 0.00 | 0.00 |
August | 0.428884E+10 | 0.164524E+10 | 0.334487E+10 | 79128421.74 | 0.326574E+10 | 0.00 | 0.00 |
September | 0.310642E+10 | 0.238346E+10 | 0.271906E+10 | 638658.55 | 0.271842E+10 | 0.00 | 0.00 |
October | 0.118659E+10 | 0.490298E+10 | 0.201242E+10 | 0.00 | 0.201242E+10 | 0.00 | 0.00 |
November | 0.485250E+09 | 0.566426E+10 | 0.147840E+10 | 0.00 | 0.147840E+10 | 0.00 | 0.00 |
December | 0.262676E+09 | 0.738872E+10 | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.277385E+11 | 0.492262E+11 | 0.315842E+11 | 0.978443E+09 | 0.306057E+11 | 0.00 | 0.00 |
Minimum of Months | 0.262676E+09 | 0.145518E+10 | 0.129226E+10 | 0.00 | 0.129226E+10 | 0.00 | 0.00 |
Maximum of Months | 0.569191E+10 | 0.738872E+10 | 0.430032E+10 | 0.476761E+09 | 0.393047E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.261422E+10 | 0.408206E+10 | 0.288324E+10 | 0.176694E+10 | 0.111630E+10 | 0.00 | 0.00 |
February | 0.327337E+10 | 0.386155E+10 | 0.345941E+10 | 0.218391E+10 | 0.127550E+10 | 0.00 | 0.00 |
March | 0.467859E+10 | 0.327327E+10 | 0.462278E+10 | 0.269643E+10 | 0.192635E+10 | 0.00 | 0.00 |
April | 0.454498E+10 | 0.269950E+10 | 0.458798E+10 | 0.223489E+10 | 0.235309E+10 | 0.00 | 0.00 |
May | 0.624452E+10 | 0.179831E+10 | 0.554205E+10 | 0.231494E+10 | 0.322712E+10 | 0.00 | 0.00 |
June | 0.873792E+10 | 0.100621E+10 | 0.654375E+10 | 0.343529E+10 | 0.310845E+10 | 0.00 | 0.00 |
July | 0.827946E+10 | 0.988776E+09 | 0.614708E+10 | 0.292709E+10 | 0.321999E+10 | 0.00 | 0.00 |
August | 0.830241E+10 | 0.112326E+10 | 0.620017E+10 | 0.341483E+10 | 0.278534E+10 | 0.00 | 0.00 |
September | 0.634581E+10 | 0.155942E+10 | 0.499244E+10 | 0.271204E+10 | 0.228041E+10 | 0.00 | 0.00 |
October | 0.393382E+10 | 0.325099E+10 | 0.373604E+10 | 0.204714E+10 | 0.168891E+10 | 0.00 | 0.00 |
November | 0.268426E+10 | 0.367694E+10 | 0.281422E+10 | 0.158894E+10 | 0.122528E+10 | 0.00 | 0.00 |
December | 0.218040E+10 | 0.468716E+10 | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.618198E+11 | 0.320075E+11 | 0.540468E+11 | 0.287727E+11 | 0.252740E+11 | 0.00 | 0.00 |
Minimum of Months | 0.218040E+10 | 0.988776E+09 | 0.251758E+10 | 0.145030E+10 | 0.106727E+10 | 0.00 | 0.00 |
Maximum of Months | 0.873792E+10 | 0.468716E+10 | 0.654375E+10 | 0.343529E+10 | 0.322712E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.151073E+11 | 0.612597E+10 | 0.132370E+11 | 0.108889E+11 | 0.234814E+10 | 0.00 | 0.00 |
February | 0.129111E+11 | 0.578227E+10 | 0.114680E+11 | 0.914303E+10 | 0.232499E+10 | 0.00 | 0.00 |
March | 0.106838E+11 | 0.509143E+10 | 0.936101E+10 | 0.615902E+10 | 0.320200E+10 | 0.00 | 0.00 |
April | 0.612179E+10 | 0.431187E+10 | 0.586731E+10 | 0.235927E+10 | 0.350804E+10 | 0.00 | 0.00 |
May | 0.632771E+10 | 0.292552E+10 | 0.555597E+10 | 0.101837E+10 | 0.453760E+10 | 0.00 | 0.00 |
June | 0.712032E+10 | 0.163160E+10 | 0.495718E+10 | 0.906033E+09 | 0.405114E+10 | 0.00 | 0.00 |
July | 0.767554E+10 | 0.157474E+10 | 0.533232E+10 | 0.954869E+09 | 0.437745E+10 | 0.00 | 0.00 |
August | 0.980992E+10 | 0.178398E+10 | 0.678912E+10 | 0.283811E+10 | 0.395101E+10 | 0.00 | 0.00 |
September | 0.114508E+11 | 0.255281E+10 | 0.845310E+10 | 0.471678E+10 | 0.373632E+10 | 0.00 | 0.00 |
October | 0.126023E+11 | 0.508786E+10 | 0.104444E+11 | 0.741051E+10 | 0.303385E+10 | 0.00 | 0.00 |
November | 0.143386E+11 | 0.567215E+10 | 0.123145E+11 | 0.981645E+10 | 0.249806E+10 | 0.00 | 0.00 |
December | 0.135955E+11 | 0.684975E+10 | 0.121684E+11 | 0.984894E+10 | 0.231946E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.127745E+12 | 0.493899E+11 | 0.105948E+12 | 0.660602E+11 | 0.398881E+11 | 0.00 | 0.00 |
Minimum of Months | 0.612179E+10 | 0.157474E+10 | 0.495718E+10 | 0.906033E+09 | 0.231946E+10 | 0.00 | 0.00 |
Maximum of Months | 0.151073E+11 | 0.684975E+10 | 0.132370E+11 | 0.108889E+11 | 0.453760E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.295289E+10 | 0.430670E+10 | 0.306712E+10 | 0.194350E+10 | 0.112363E+10 | 0.00 | 0.00 |
February | 0.316172E+10 | 0.402343E+10 | 0.334059E+10 | 0.207018E+10 | 0.127041E+10 | 0.00 | 0.00 |
March | 0.434205E+10 | 0.343900E+10 | 0.433072E+10 | 0.238936E+10 | 0.194137E+10 | 0.00 | 0.00 |
April | 0.377379E+10 | 0.287144E+10 | 0.394604E+10 | 0.167069E+10 | 0.227535E+10 | 0.00 | 0.00 |
May | 0.562838E+10 | 0.195916E+10 | 0.498384E+10 | 0.175699E+10 | 0.322685E+10 | 0.00 | 0.00 |
June | 0.798151E+10 | 0.117046E+10 | 0.589891E+10 | 0.283819E+10 | 0.306072E+10 | 0.00 | 0.00 |
July | 0.673724E+10 | 0.110558E+10 | 0.496642E+10 | 0.181911E+10 | 0.314731E+10 | 0.00 | 0.00 |
August | 0.693176E+10 | 0.123487E+10 | 0.518354E+10 | 0.256074E+10 | 0.262280E+10 | 0.00 | 0.00 |
September | 0.570500E+10 | 0.171143E+10 | 0.444798E+10 | 0.213310E+10 | 0.231488E+10 | 0.00 | 0.00 |
October | 0.420691E+10 | 0.340670E+10 | 0.386666E+10 | 0.221008E+10 | 0.165658E+10 | 0.00 | 0.00 |
November | 0.302909E+10 | 0.385944E+10 | 0.307045E+10 | 0.186414E+10 | 0.120631E+10 | 0.00 | 0.00 |
December | 0.224502E+10 | 0.483937E+10 | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.566954E+11 | 0.339276E+11 | 0.496650E+11 | 0.247700E+11 | 0.248951E+11 | 0.00 | 0.00 |
Minimum of Months | 0.224502E+10 | 0.110558E+10 | 0.256275E+10 | 0.151389E+10 | 0.104887E+10 | 0.00 | 0.00 |
Maximum of Months | 0.798151E+10 | 0.483937E+10 | 0.589891E+10 | 0.283819E+10 | 0.322685E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 0.85 | -1.5 | -4.5 | 2.30 | -12.1 | 27.63 | 226.20 | 0.01 |
February | -0.2 | -2.7 | -6.1 | 3.74 | -13.6 | 32.55 | 253.27 | 0.01 |
March | 4.82 | 0.36 | -5.5 | 4.48 | -7.8 | 54.65 | 233.06 | 0.03 |
April | 6.08 | 2.29 | -2.0 | 5.23 | -4.9 | 81.86 | 179.11 | 0.05 |
May | 13.74 | 7.52 | 1.82 | 4.10 | 2.75 | 117.64 | 180.87 | 0.01 |
June | 22.16 | 12.46 | 5.10 | 4.19 | 9.76 | 95.26 | 290.95 | 0.00 |
July | 22.71 | 13.25 | 6.43 | 4.25 | 12.01 | 110.54 | 215.12 | 0.03 |
August | 21.74 | 12.79 | 6.20 | 3.81 | 10.76 | 77.72 | 272.61 | 0.02 |
September | 18.54 | 9.35 | 1.35 | 4.13 | 5.52 | 70.51 | 233.03 | 0.01 |
October | 7.12 | 2.51 | -2.7 | 3.54 | -5.8 | 44.60 | 216.74 | 0.01 |
November | 3.03 | 0.31 | -2.9 | 2.79 | -8.8 | 30.71 | 220.86 | 0.01 |
December | -1.0 | -4.5 | -9.5 | 4.43 | -15.4 | 27.45 | 194.75 | 0.01 |
Annual Sum or Average | 10.02 | 4.37 | -1.0 | 3.91 | -2.2 | 64.46 | 226.11 | 0.02 |
Minimum of Months | -1.0 | -4.5 | -9.5 | 2.30 | -15.4 | 27.45 | 179.11 | 0.00 |
Maximum of Months | 22.71 | 13.25 | 6.43 | 5.23 | 12.01 | 117.64 | 290.95 | 0.05 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 21.00 | 20-JAN-12:00 | 6.97 | -11.0 | 0.50 | 6.55 | 41.00 | 961.00 |
February | 20.00 | 18-FEB-12:00 | 7.74 | -5.0 | 3.60 | 6.35 | 56.00 | 998.00 |
March | 24.00 | 14-MAR-12:00 | 7.90 | -12.0 | 3.10 | 11.65 | 160.00 | 837.50 |
April | 22.00 | 19-APR-13:09 | 8.49 | -5.7 | 5.52 | 11.55 | 235.67 | 789.67 |
May | 29.00 | 17-MAY-12:00 | 11.92 | -3.0 | 5.10 | 18.99 | 432.50 | 162.00 |
June | 39.40 | 26-JUN-14:00 | 15.63 | -2.8 | 4.60 | 21.96 | 136.50 | 752.00 |
July | 37.00 | 16-JUL-12:00 | 14.90 | -3.0 | 3.10 | 26.65 | 319.50 | 109.50 |
August | 37.00 | 16-AUG-13:00 | 16.36 | 3.00 | 3.60 | 28.27 | 90.00 | 895.00 |
September | 32.70 | 09-SEP-12:00 | 13.05 | -3.9 | 3.00 | 16.30 | 270.50 | 562.00 |
October | 27.00 | 11-OCT-13:00 | 9.73 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 22.00 | 06-NOV-13:09 | 7.10 | -13.0 | 2.60 | 4.92 | 88.67 | 883.33 |
December | 22.00 | 01-DEC-13:00 | 7.94 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 6.97 | -13.0 | 0.50 | 4.92 | 41.00 | 109.50 | |
Maximum of Months | 39.40 | 16.36 | 3.00 | 5.52 | 28.27 | 432.50 | 998.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -19.0 | 05-JAN-18:00 | -19.0 | -19.0 | 1.50 | -37.1 | 0.00 | 0.00 |
February | -20.0 | 12-FEB-04:00 | -20.0 | -20.0 | 3.60 | -39.1 | 0.00 | 0.00 |
March | -15.6 | 19-MAR-06:00 | -15.6 | -15.6 | 10.80 | -25.3 | 24.00 | 0.00 |
April | -8.0 | 03-APR-02:00 | -8.0 | -8.0 | 3.10 | -22.2 | 0.00 | 0.00 |
May | -1.0 | 03-MAY-01:00 | -2.4 | -4.0 | 4.10 | -15.7 | 0.00 | 0.00 |
June | 6.60 | 09-JUN-03:00 | 3.45 | 0.00 | 3.60 | -6.9 | 0.00 | 0.00 |
July | 9.00 | 02-JUL-04:00 | 3.30 | -3.0 | 3.60 | -5.3 | 20.00 | 184.50 |
August | 11.00 | 12-AUG-22:00 | 7.22 | 4.00 | 4.10 | 5.13 | 0.00 | 0.00 |
September | -1.7 | 22-SEP-05:10 | -2.9 | -4.3 | 3.60 | -15.8 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.0 | -10.0 | 2.60 | -18.6 | 0.00 | 0.00 |
November | -15.0 | 29-NOV-20:00 | -15.0 | -15.0 | 3.10 | -33.5 | 0.00 | 0.00 |
December | -23.0 | 22-DEC-02:00 | -23.0 | -23.0 | 3.60 | -42.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -23.0 | -23.0 | -23.0 | 1.50 | -42.7 | 0.00 | 0.00 | |
Maximum of Months | 11.00 | 7.22 | 4.00 | 10.80 | 5.13 | 24.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 7.55 | 20-JAN-11:00 | 20.00 | -6.0 | 2.60 | 7.95 | 43.00 | 971.50 |
February | 7.98 | 18-FEB-14:00 | 19.00 | -3.0 | 3.60 | 5.94 | 151.00 | 410.00 |
March | 8.00 | 31-MAR-17:00 | 15.00 | 2.00 | 2.60 | 1.58 | 19.50 | 261.00 |
April | 12.50 | 28-APR-13:00 | 18.00 | 9.00 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 14.87 | 31-MAY-13:00 | 28.00 | 7.00 | 4.60 | 14.47 | 157.50 | 830.50 |
June | 19.65 | 18-JUN-11:00 | 29.40 | 15.50 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 19.75 | 30-JUL-13:00 | 29.00 | 16.00 | 3.60 | 18.99 | 217.50 | 412.00 |
August | 18.80 | 05-AUG-14:09 | 25.83 | 15.33 | 6.62 | 20.54 | 196.33 | 4.00 |
September | 14.95 | 01-SEP-11:00 | 24.40 | 9.40 | 3.00 | 10.69 | 193.50 | 684.00 |
October | 9.73 | 11-OCT-13:00 | 27.00 | -9.0 | 4.60 | 12.03 | 89.50 | 844.00 |
November | 9.33 | 09-NOV-10:00 | 20.00 | 0.00 | 1.50 | 11.07 | 112.00 | 860.50 |
December | 7.94 | 01-DEC-13:00 | 22.00 | -8.0 | 2.60 | 5.13 | 49.00 | 862.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.55 | 15.00 | -9.0 | 1.50 | 1.58 | 19.50 | 4.00 | |
Maximum of Months | 19.75 | 29.40 | 16.00 | 9.80 | 20.54 | 335.00 | 971.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 5.00 | 28-JAN-10:00 | 5.00 | 5.00 | 1.00 | -6.2 | 207.00 | 309.00 |
February | 5.00 | 19-FEB-14:30 | 5.00 | 5.00 | 1.80 | -0.4 | 188.00 | 467.00 |
March | 7.00 | 17-MAR-14:00 | 8.00 | 7.39 | 8.20 | 1.16 | 121.50 | 3.00 |
April | 9.00 | 28-APR-13:00 | 18.00 | 12.50 | 9.80 | 9.72 | 335.00 | 196.50 |
May | 11.00 | 21-MAY-21:10 | 12.83 | 11.73 | 2.68 | 6.78 | 0.00 | 0.00 |
June | 15.50 | 18-JUN-11:00 | 29.40 | 19.65 | 6.10 | 16.85 | 272.50 | 596.00 |
July | 17.00 | 28-JUL-16:00 | 20.00 | 17.92 | 5.70 | 15.02 | 155.00 | 32.00 |
August | 18.00 | 04-AUG-01:00 | 18.00 | 18.00 | 2.60 | 8.74 | 0.00 | 0.00 |
September | 12.20 | 30-SEP-14:00 | 17.20 | 13.90 | 5.10 | 9.72 | 209.00 | 82.50 |
October | 6.00 | 01-OCT-19:00 | 9.00 | 7.28 | 3.10 | 3.69 | 0.00 | 0.00 |
November | 7.00 | 09-NOV-23:00 | 8.00 | 7.40 | 4.10 | 3.06 | 0.00 | 0.00 |
December | 1.00 | 30-DEC-14:00 | 7.00 | 4.06 | 9.80 | -1.2 | 101.00 | 91.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | 5.00 | 4.06 | 1.00 | -6.2 | 0.00 | 0.00 | |
Maximum of Months | 18.00 | 29.40 | 19.65 | 9.80 | 16.85 | 335.00 | 596.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 8.52 | 21.53 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 7.90 | 29.36 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 8.65 | 35.75 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 10.64 | 38.62 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 13.34 | 48.35 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.03 | 59.81 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.97 | 52.29 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 18.66 | 51.98 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.88 | 41.73 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 15.85 | 30.82 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 13.14 | 23.90 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 10.46 | 18.59 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 13.28 | 37.76 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 7.90 | 18.59 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 18.66 | 59.81 | 0.00 |
Report: WaterHeaterReportMonthly
For: SWHSYS1 WATER HEATER
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.412110E+11 | -0.401830E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102808E+10 | 58.97 | 0.00 | 0.00 |
February | 0.378955E+11 | -0.369667E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -928839445.2 | 58.97 | 0.00 | 0.00 |
March | 0.438723E+11 | -0.428415E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.103084E+10 | 58.98 | 0.00 | 0.00 |
April | 0.383118E+11 | -0.373189E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992893242.7 | 58.98 | 0.00 | 0.00 |
May | 0.386762E+11 | -0.376510E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102520E+10 | 58.97 | 0.00 | 0.00 |
June | 0.361028E+11 | -0.351108E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -992014828.5 | 58.98 | 0.00 | 0.00 |
July | 0.328873E+11 | -0.318673E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.101995E+10 | 58.98 | 0.00 | 0.00 |
August | 0.353527E+11 | -0.343296E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102313E+10 | 58.97 | 0.00 | 0.00 |
September | 0.327363E+11 | -0.317479E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988377250.4 | 58.98 | 0.00 | 0.00 |
October | 0.353828E+11 | -0.343620E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102081E+10 | 58.97 | 0.00 | 0.00 |
November | 0.368060E+11 | -0.358172E+11 | 0.00 | 0.00 | 720.00 | 0.00 | -988752083.1 | 58.98 | 0.00 | 0.00 |
December | 0.387338E+11 | -0.377066E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -0.102718E+10 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.447969E+12 | -0.435903E+12 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.120661E+11 | 58.98 | 0.00 | 0.00 |
Minimum of Months | 0.327363E+11 | -0.428415E+11 | 0.00 | 0.00 | 672.00 | 0.00 | -0.103084E+10 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.438723E+11 | -0.317479E+11 | 0.00 | 0.00 | 744.00 | 0.00 | -928839445.2 | 58.98 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.64 | 0.61 | 01-JAN-07:00 | 8892.93 | 34.81 | 231.83 | 255.00 | 4844.23 | 34.93 | 236.83 | 256.17 |
February | 245.50 | 0.63 | 0.61 | 01-FEB-10:39 | 12399.16 | 37.44 | 228.50 | 255.33 | 1798.22 | 24.66 | 114.00 | 231.67 |
March | 296.17 | 0.63 | 0.61 | 01-MAR-06:00 | 2200.25 | 17.86 | 9.83 | 316.67 | 1210.67 | 20.51 | 94.50 | 271.67 |
April | 296.67 | 0.64 | 0.61 | 03-APR-09:39 | 1679.81 | 17.50 | 0.00 | 330.67 | 956.56 | 20.46 | 115.17 | 278.17 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:49 | 1518.16 | 17.55 | 0.00 | 381.50 | 823.60 | 20.52 | 200.33 | 336.33 |
June | 421.50 | 0.64 | 0.61 | 01-JUN-05:40 | 1220.09 | 16.88 | 0.00 | 376.50 | 724.79 | 19.95 | 103.00 | 329.50 |
July | 430.33 | 0.64 | 0.61 | 01-JUL-05:00 | 1379.44 | 17.12 | 0.00 | 381.83 | 770.07 | 20.12 | 167.33 | 337.33 |
August | 394.50 | 0.64 | 0.61 | 01-AUG-05:00 | 1460.27 | 16.92 | 0.00 | 360.83 | 876.40 | 19.90 | 115.83 | 317.17 |
September | 354.00 | 0.63 | 0.61 | 01-SEP-06:10 | 2453.42 | 18.91 | 29.50 | 321.67 | 1078.16 | 20.44 | 132.00 | 290.67 |
October | 262.67 | 0.63 | 0.61 | 01-OCT-06:30 | 12128.72 | 35.86 | 238.67 | 293.17 | 1483.73 | 21.14 | 105.00 | 255.33 |
November | 257.67 | 0.63 | 0.61 | 01-NOV-08:39 | 10400.54 | 36.27 | 228.67 | 253.17 | 2944.41 | 29.38 | 175.17 | 235.17 |
December | 251.17 | 0.63 | 0.61 | 01-DEC-07:49 | 8332.40 | 35.90 | 220.00 | 247.67 | 6951.42 | 40.45 | 248.33 | 239.50 |
Annual Sum or Average | 3902.00 | 0.63 | 4560.33 | 23.63 | 1187.00 | 3774.00 | 1800.09 | 23.53 | 1807.50 | 3378.67 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1220.09 | 16.88 | 0.00 | 247.67 | 724.79 | 19.90 | 94.50 | 231.67 | |
Maximum of Months | 430.33 | 0.64 | 0.61 | 12399.16 | 37.44 | 238.67 | 381.83 | 6951.42 | 40.45 | 248.33 | 337.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.61 | 01-JAN-07:49 | 2069.95 | 18.75 | 82.50 | 216.67 | 1099.09 | 17.72 | 52.67 | 173.00 |
February | 245.50 | 0.64 | 0.61 | 01-FEB-10:39 | 3019.07 | 18.75 | 66.17 | 233.00 | 1965.78 | 19.62 | 61.00 | 183.33 |
March | 296.17 | 0.64 | 0.61 | 01-MAR-06:49 | 2985.85 | 17.84 | 67.83 | 302.50 | 1722.95 | 17.38 | 45.83 | 251.17 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 3439.29 | 15.54 | 39.33 | 329.50 | 1389.05 | 14.56 | 0.00 | 275.33 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:40 | 2609.64 | 13.53 | 0.00 | 388.17 | 1448.93 | 14.79 | 0.00 | 349.83 |
June | 421.50 | 0.63 | 0.61 | 01-JUN-04:00 | 3052.77 | 12.83 | 0.00 | 389.67 | 1817.52 | 14.39 | 0.00 | 357.33 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-05:10 | 2793.08 | 13.30 | 3.67 | 392.67 | 1540.58 | 14.45 | 0.00 | 353.83 |
August | 394.50 | 0.64 | 0.61 | 01-AUG-05:49 | 3992.29 | 15.49 | 56.50 | 358.33 | 1542.12 | 14.10 | 0.00 | 321.17 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-05:49 | 3094.59 | 16.06 | 56.00 | 319.50 | 1222.53 | 14.66 | 5.50 | 290.33 |
October | 262.67 | 0.64 | 0.61 | 01-OCT-06:30 | 2870.66 | 18.57 | 66.33 | 272.83 | 1675.42 | 18.10 | 43.00 | 218.33 |
November | 257.67 | 0.65 | 0.61 | 01-NOV-08:39 | 1785.55 | 16.92 | 51.00 | 225.17 | 1031.61 | 17.83 | 42.83 | 178.00 |
December | 251.17 | 0.65 | 0.61 | 01-DEC-07:49 | 2066.20 | 19.71 | 78.00 | 214.50 | 1267.24 | 20.30 | 63.50 | 166.00 |
Annual Sum or Average | 3902.00 | 0.64 | 2868.85 | 16.00 | 567.33 | 3642.50 | 1487.70 | 16.10 | 314.33 | 3117.67 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1785.55 | 12.83 | 0.00 | 214.50 | 1031.61 | 14.10 | 0.00 | 166.00 | |
Maximum of Months | 430.33 | 0.66 | 0.61 | 3992.29 | 19.71 | 82.50 | 392.67 | 1965.78 | 20.30 | 63.50 | 357.33 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.67 | 0.61 | 01-JAN-08:50 | 437.43 | 0.00 | 0.00 | 183.17 | 296.39 | 0.00 | 0.00 | 73.33 |
February | 245.50 | 0.64 | 0.61 | 01-FEB-10:39 | 520.76 | 0.00 | 0.00 | 218.67 | 365.81 | 0.00 | 0.00 | 132.00 |
March | 296.17 | 0.64 | 0.61 | 01-MAR-07:19 | 682.87 | 0.00 | 0.00 | 299.50 | 446.99 | 0.00 | 0.00 | 213.33 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 922.46 | 0.00 | 0.00 | 337.33 | 546.15 | 0.00 | 0.00 | 264.00 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:40 | 1089.63 | 0.00 | 0.00 | 399.33 | 620.79 | 0.00 | 0.00 | 363.83 |
June | 421.50 | 0.62 | 0.61 | 01-JUN-05:10 | 1209.24 | 0.00 | 0.00 | 409.33 | 680.89 | 0.00 | 0.00 | 395.67 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-05:10 | 1155.64 | 0.00 | 0.00 | 409.67 | 628.41 | 0.00 | 0.00 | 372.83 |
August | 394.50 | 0.63 | 0.61 | 01-AUG-05:00 | 893.09 | 0.00 | 0.00 | 373.33 | 553.94 | 0.00 | 0.00 | 326.67 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-06:10 | 749.80 | 0.00 | 0.00 | 313.67 | 476.95 | 0.00 | 0.00 | 260.67 |
October | 262.67 | 0.64 | 0.61 | 01-OCT-06:49 | 631.17 | 0.00 | 0.00 | 264.67 | 432.58 | 0.00 | 0.00 | 187.00 |
November | 257.67 | 0.66 | 0.61 | 01-NOV-08:39 | 488.48 | 0.00 | 0.00 | 205.50 | 339.03 | 0.00 | 0.00 | 119.33 |
December | 251.17 | 0.66 | 0.61 | 01-DEC-08:30 | 449.77 | 0.00 | 0.00 | 193.33 | 303.76 | 0.00 | 0.00 | 74.83 |
Annual Sum or Average | 3902.00 | 0.64 | 821.79 | 0.00 | 0.00 | 3607.50 | 498.74 | 0.00 | 0.00 | 2783.50 | ||
Minimum of Months | 245.50 | 0.62 | 0.61 | 437.43 | 0.00 | 0.00 | 183.17 | 296.39 | 0.00 | 0.00 | 73.33 | |
Maximum of Months | 430.33 | 0.67 | 0.61 | 1209.24 | 0.00 | 0.00 | 409.67 | 680.89 | 0.00 | 0.00 | 395.67 |
Report: DaylightingReportMonthly
For: PERIMETER_BOT_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.65 | 0.61 | 01-JAN-08:50 | 2286.56 | 19.23 | 83.33 | 229.00 | 1476.64 | 20.76 | 78.83 | 172.33 |
February | 245.50 | 0.63 | 0.61 | 01-FEB-10:39 | 2517.34 | 19.04 | 68.50 | 240.50 | 1292.98 | 18.14 | 44.17 | 188.67 |
March | 296.17 | 0.63 | 0.61 | 01-MAR-07:19 | 2771.56 | 17.91 | 73.00 | 315.67 | 1662.76 | 17.44 | 45.83 | 260.00 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 2774.34 | 15.51 | 41.33 | 334.17 | 1157.71 | 14.69 | 0.00 | 283.67 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:00 | 2311.66 | 13.58 | 0.00 | 383.50 | 1209.35 | 14.81 | 0.00 | 345.67 |
June | 421.50 | 0.63 | 0.61 | 01-JUN-05:49 | 2687.95 | 12.85 | 0.00 | 387.50 | 1545.77 | 14.39 | 0.00 | 358.17 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-06:10 | 2323.34 | 13.37 | 3.67 | 391.67 | 1267.83 | 14.55 | 0.00 | 355.17 |
August | 394.50 | 0.63 | 0.61 | 01-AUG-06:10 | 3109.71 | 14.97 | 48.17 | 370.00 | 1371.42 | 14.24 | 0.00 | 334.83 |
September | 354.00 | 0.63 | 0.61 | 01-SEP-06:30 | 2640.34 | 16.16 | 59.17 | 319.17 | 1470.67 | 14.86 | 5.50 | 288.83 |
October | 262.67 | 0.63 | 0.61 | 01-OCT-06:00 | 3640.09 | 21.14 | 91.83 | 284.00 | 1290.36 | 18.40 | 43.83 | 230.67 |
November | 257.67 | 0.64 | 0.61 | 01-NOV-08:39 | 2368.17 | 19.71 | 77.17 | 236.83 | 1401.33 | 20.92 | 69.33 | 191.83 |
December | 251.17 | 0.64 | 0.61 | 01-DEC-08:30 | 1959.87 | 20.28 | 80.67 | 231.33 | 1054.74 | 19.25 | 52.17 | 174.67 |
Annual Sum or Average | 3902.00 | 0.63 | 2615.86 | 16.42 | 626.83 | 3723.33 | 1355.10 | 16.43 | 339.67 | 3184.50 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1959.87 | 12.85 | 0.00 | 229.00 | 1054.74 | 14.24 | 0.00 | 172.33 | |
Maximum of Months | 430.33 | 0.65 | 0.61 | 3640.09 | 21.14 | 91.83 | 391.67 | 1662.76 | 20.92 | 78.83 | 358.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.64 | 0.61 | 01-JAN-07:00 | 8890.84 | 33.64 | 231.83 | 255.00 | 4917.57 | 32.96 | 205.33 | 256.67 |
February | 245.50 | 0.63 | 0.61 | 01-FEB-10:39 | 12420.93 | 36.81 | 228.50 | 254.50 | 1878.27 | 20.29 | 69.33 | 232.17 |
March | 296.17 | 0.63 | 0.61 | 01-MAR-06:00 | 2260.80 | 11.72 | 9.83 | 321.17 | 1265.94 | 16.21 | 3.50 | 275.00 |
April | 296.67 | 0.64 | 0.61 | 03-APR-09:39 | 1654.48 | 11.72 | 0.00 | 328.33 | 991.20 | 16.53 | 0.00 | 281.67 |
May | 415.33 | 0.64 | 0.61 | 01-MAY-05:49 | 1487.09 | 11.81 | 0.00 | 380.17 | 848.29 | 16.57 | 0.00 | 339.50 |
June | 421.50 | 0.64 | 0.61 | 01-JUN-05:40 | 1202.36 | 11.52 | 0.00 | 374.67 | 748.78 | 16.41 | 0.00 | 331.83 |
July | 430.33 | 0.64 | 0.61 | 01-JUL-05:00 | 1353.76 | 11.51 | 0.00 | 380.67 | 793.95 | 16.29 | 0.00 | 340.17 |
August | 394.50 | 0.64 | 0.61 | 01-AUG-05:00 | 1444.85 | 11.31 | 0.00 | 359.17 | 909.90 | 16.15 | 0.00 | 318.83 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-06:19 | 2435.97 | 13.36 | 29.50 | 321.00 | 1121.45 | 16.27 | 0.00 | 292.50 |
October | 262.67 | 0.63 | 0.61 | 01-OCT-06:30 | 12127.60 | 35.19 | 238.00 | 292.33 | 1551.40 | 16.39 | 3.33 | 258.50 |
November | 257.67 | 0.63 | 0.61 | 01-NOV-08:39 | 10399.70 | 35.37 | 228.67 | 252.33 | 3010.95 | 25.64 | 124.33 | 234.67 |
December | 251.17 | 0.63 | 0.61 | 01-DEC-07:49 | 8328.48 | 34.90 | 220.00 | 247.67 | 6944.41 | 38.48 | 234.00 | 236.17 |
Annual Sum or Average | 3902.00 | 0.63 | 4552.64 | 19.56 | 1186.33 | 3767.00 | 1840.82 | 19.81 | 639.83 | 3397.67 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1202.36 | 11.31 | 0.00 | 247.67 | 748.78 | 16.15 | 0.00 | 232.17 | |
Maximum of Months | 430.33 | 0.64 | 0.61 | 12420.93 | 36.81 | 238.00 | 380.67 | 6944.41 | 38.48 | 234.00 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.61 | 01-JAN-07:49 | 2077.50 | 16.90 | 82.50 | 217.67 | 1125.96 | 15.78 | 52.67 | 178.67 |
February | 245.50 | 0.64 | 0.61 | 01-FEB-10:39 | 3030.66 | 16.60 | 66.17 | 232.33 | 2001.48 | 17.91 | 61.00 | 186.83 |
March | 296.17 | 0.64 | 0.61 | 01-MAR-06:49 | 3003.84 | 15.43 | 67.83 | 302.17 | 1607.46 | 15.32 | 45.83 | 255.33 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 3080.60 | 12.64 | 39.33 | 328.67 | 1427.39 | 12.00 | 0.00 | 278.67 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:40 | 2592.04 | 10.04 | 0.00 | 387.50 | 1483.17 | 12.34 | 0.00 | 351.83 |
June | 421.50 | 0.63 | 0.61 | 01-JUN-04:00 | 3043.46 | 9.29 | 0.00 | 388.83 | 1861.04 | 11.94 | 0.00 | 359.50 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-05:10 | 2778.06 | 9.82 | 3.67 | 391.83 | 1573.50 | 12.02 | 0.00 | 356.50 |
August | 394.50 | 0.64 | 0.61 | 01-AUG-05:49 | 3993.99 | 12.65 | 56.50 | 358.00 | 1509.38 | 11.60 | 0.00 | 320.83 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-05:49 | 3107.51 | 13.26 | 56.00 | 318.50 | 1261.34 | 12.07 | 5.50 | 292.83 |
October | 262.67 | 0.64 | 0.61 | 01-OCT-06:30 | 2876.30 | 16.37 | 66.33 | 272.17 | 1713.49 | 16.07 | 43.00 | 220.33 |
November | 257.67 | 0.65 | 0.61 | 01-NOV-08:39 | 1793.07 | 14.58 | 51.00 | 225.00 | 1042.37 | 15.63 | 41.83 | 183.33 |
December | 251.17 | 0.65 | 0.61 | 01-DEC-07:49 | 2071.25 | 17.84 | 78.00 | 214.00 | 1153.53 | 16.73 | 50.00 | 169.33 |
Annual Sum or Average | 3902.00 | 0.64 | 2842.21 | 13.22 | 567.33 | 3636.67 | 1494.14 | 13.71 | 299.83 | 3154.00 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1793.07 | 9.29 | 0.00 | 214.00 | 1042.37 | 11.60 | 0.00 | 169.33 | |
Maximum of Months | 430.33 | 0.66 | 0.61 | 3993.99 | 17.84 | 82.50 | 391.83 | 2001.48 | 17.91 | 61.00 | 359.50 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.68 | 0.61 | 01-JAN-08:50 | 429.75 | 0.00 | 0.00 | 180.17 | 304.85 | 0.00 | 0.00 | 83.17 |
February | 245.50 | 0.64 | 0.61 | 01-FEB-10:39 | 514.22 | 0.00 | 0.00 | 215.17 | 377.36 | 0.00 | 0.00 | 139.67 |
March | 296.17 | 0.64 | 0.61 | 01-MAR-07:19 | 673.44 | 0.00 | 0.00 | 297.00 | 461.13 | 0.00 | 0.00 | 219.17 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 907.63 | 0.00 | 0.00 | 336.00 | 562.84 | 0.00 | 0.00 | 269.00 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:40 | 1108.65 | 0.00 | 0.00 | 400.00 | 638.08 | 0.00 | 0.00 | 365.83 |
June | 421.50 | 0.62 | 0.61 | 01-JUN-05:10 | 1196.03 | 0.00 | 0.00 | 408.67 | 674.02 | 0.00 | 0.00 | 386.00 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-05:10 | 1140.14 | 0.00 | 0.00 | 408.83 | 647.49 | 0.00 | 0.00 | 375.00 |
August | 394.50 | 0.63 | 0.61 | 01-AUG-05:49 | 904.48 | 0.00 | 0.00 | 374.67 | 571.65 | 0.00 | 0.00 | 331.50 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-06:10 | 738.74 | 0.00 | 0.00 | 311.50 | 491.63 | 0.00 | 0.00 | 264.00 |
October | 262.67 | 0.64 | 0.61 | 01-OCT-06:49 | 621.55 | 0.00 | 0.00 | 261.83 | 445.44 | 0.00 | 0.00 | 191.17 |
November | 257.67 | 0.66 | 0.61 | 01-NOV-08:39 | 479.96 | 0.00 | 0.00 | 202.33 | 348.56 | 0.00 | 0.00 | 130.00 |
December | 251.17 | 0.66 | 0.61 | 01-DEC-08:30 | 440.23 | 0.00 | 0.00 | 189.67 | 311.58 | 0.00 | 0.00 | 91.00 |
Annual Sum or Average | 3902.00 | 0.64 | 816.21 | 0.00 | 0.00 | 3585.83 | 510.73 | 0.00 | 0.00 | 2845.50 | ||
Minimum of Months | 245.50 | 0.62 | 0.61 | 429.75 | 0.00 | 0.00 | 180.17 | 304.85 | 0.00 | 0.00 | 83.17 | |
Maximum of Months | 430.33 | 0.68 | 0.61 | 1196.03 | 0.00 | 0.00 | 408.83 | 674.02 | 0.00 | 0.00 | 386.00 |
Report: DaylightingReportMonthly
For: PERIMETER_MID_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.65 | 0.61 | 01-JAN-08:50 | 2279.57 | 17.19 | 82.33 | 228.67 | 1503.86 | 19.10 | 79.00 | 180.17 |
February | 245.50 | 0.63 | 0.61 | 01-FEB-10:39 | 2029.17 | 13.81 | 44.67 | 240.00 | 1330.38 | 16.13 | 44.17 | 192.50 |
March | 296.17 | 0.63 | 0.61 | 01-MAR-07:19 | 2778.09 | 15.49 | 72.00 | 315.33 | 1698.50 | 15.41 | 46.00 | 265.83 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 2543.26 | 12.72 | 41.33 | 333.50 | 1191.33 | 12.16 | 0.00 | 286.17 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:00 | 2907.59 | 10.14 | 0.00 | 383.17 | 1241.90 | 12.40 | 0.00 | 349.00 |
June | 421.50 | 0.63 | 0.61 | 01-JUN-05:49 | 2679.00 | 9.39 | 0.00 | 386.50 | 1585.72 | 11.99 | 0.00 | 361.50 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-06:10 | 2308.80 | 10.01 | 3.67 | 391.00 | 1300.46 | 12.18 | 0.00 | 357.83 |
August | 394.50 | 0.63 | 0.61 | 01-AUG-06:10 | 3110.34 | 12.15 | 48.33 | 369.33 | 1407.03 | 11.77 | 0.00 | 337.83 |
September | 354.00 | 0.63 | 0.61 | 01-SEP-06:40 | 2621.56 | 13.23 | 56.17 | 318.00 | 1503.55 | 12.32 | 5.50 | 292.17 |
October | 262.67 | 0.63 | 0.61 | 01-OCT-06:00 | 3264.54 | 16.72 | 69.67 | 283.00 | 1328.70 | 16.23 | 43.00 | 233.17 |
November | 257.67 | 0.64 | 0.61 | 01-NOV-08:39 | 2375.32 | 17.74 | 77.17 | 236.17 | 1283.00 | 16.79 | 50.50 | 192.67 |
December | 251.17 | 0.64 | 0.61 | 01-DEC-08:30 | 1965.69 | 18.44 | 80.67 | 230.50 | 1080.73 | 17.22 | 52.17 | 179.33 |
Annual Sum or Average | 3902.00 | 0.63 | 2602.36 | 13.34 | 576.00 | 3715.17 | 1379.06 | 14.04 | 320.33 | 3228.17 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1965.69 | 9.39 | 0.00 | 228.67 | 1080.73 | 11.77 | 0.00 | 179.33 | |
Maximum of Months | 430.33 | 0.65 | 0.61 | 3264.54 | 18.44 | 82.33 | 391.00 | 1698.50 | 19.10 | 79.00 | 361.50 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_1_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.64 | 0.61 | 01-JAN-07:00 | 8889.61 | 33.62 | 231.83 | 255.00 | 4918.54 | 32.95 | 205.33 | 256.67 |
February | 245.50 | 0.63 | 0.61 | 01-FEB-10:39 | 12420.19 | 36.79 | 228.50 | 254.50 | 1879.27 | 20.27 | 69.33 | 232.17 |
March | 296.17 | 0.63 | 0.61 | 01-MAR-06:00 | 2261.14 | 11.68 | 9.83 | 321.00 | 1267.01 | 16.19 | 3.50 | 275.00 |
April | 296.67 | 0.64 | 0.61 | 03-APR-09:39 | 1655.26 | 11.68 | 0.00 | 328.50 | 992.29 | 16.51 | 0.00 | 281.83 |
May | 415.33 | 0.64 | 0.61 | 01-MAY-05:49 | 1487.91 | 11.77 | 0.00 | 380.17 | 849.33 | 16.55 | 0.00 | 339.67 |
June | 421.50 | 0.64 | 0.61 | 01-JUN-05:40 | 1202.69 | 11.48 | 0.00 | 374.50 | 749.47 | 16.39 | 0.00 | 331.83 |
July | 430.33 | 0.64 | 0.61 | 01-JUL-05:00 | 1354.40 | 11.46 | 0.00 | 380.67 | 794.84 | 16.27 | 0.00 | 340.17 |
August | 394.50 | 0.64 | 0.61 | 01-AUG-05:00 | 1445.33 | 11.27 | 0.00 | 359.17 | 910.74 | 16.13 | 0.00 | 318.83 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-06:19 | 2436.57 | 13.32 | 29.50 | 321.00 | 1122.57 | 16.25 | 0.00 | 292.50 |
October | 262.67 | 0.63 | 0.61 | 01-OCT-06:30 | 12127.36 | 35.17 | 238.00 | 292.33 | 1552.60 | 16.37 | 3.33 | 258.50 |
November | 257.67 | 0.63 | 0.61 | 01-NOV-08:39 | 10398.20 | 35.36 | 228.67 | 252.33 | 3012.10 | 25.62 | 124.33 | 234.67 |
December | 251.17 | 0.63 | 0.61 | 01-DEC-07:49 | 8326.73 | 34.89 | 220.00 | 247.33 | 6934.09 | 38.30 | 232.67 | 236.00 |
Annual Sum or Average | 3902.00 | 0.63 | 4552.66 | 19.52 | 1186.33 | 3766.50 | 1841.08 | 19.79 | 638.50 | 3397.83 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1202.69 | 11.27 | 0.00 | 247.33 | 749.47 | 16.13 | 0.00 | 232.17 | |
Maximum of Months | 430.33 | 0.64 | 0.61 | 12420.19 | 36.79 | 238.00 | 380.67 | 6934.09 | 38.30 | 232.67 | 340.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_2_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.66 | 0.61 | 01-JAN-07:49 | 2077.05 | 16.89 | 82.50 | 217.67 | 1126.32 | 15.77 | 52.67 | 178.67 |
February | 245.50 | 0.64 | 0.61 | 01-FEB-10:39 | 3029.97 | 16.59 | 66.17 | 232.33 | 2001.86 | 17.90 | 61.00 | 186.83 |
March | 296.17 | 0.64 | 0.61 | 01-MAR-06:49 | 3003.08 | 15.42 | 67.83 | 302.17 | 1608.05 | 15.31 | 45.83 | 255.50 |
April | 296.67 | 0.64 | 0.61 | 03-APR-09:39 | 3080.34 | 12.63 | 39.33 | 328.67 | 1428.29 | 11.99 | 0.00 | 278.83 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:40 | 2592.12 | 10.03 | 0.00 | 387.50 | 1484.22 | 12.33 | 0.00 | 351.83 |
June | 421.50 | 0.63 | 0.61 | 01-JUN-04:00 | 3043.05 | 9.27 | 0.00 | 388.83 | 1861.92 | 11.93 | 0.00 | 359.67 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-05:10 | 2777.99 | 9.81 | 3.67 | 392.00 | 1574.49 | 12.01 | 0.00 | 356.50 |
August | 394.50 | 0.64 | 0.61 | 01-AUG-05:49 | 3993.69 | 12.63 | 56.50 | 358.00 | 1600.83 | 11.59 | 0.00 | 321.00 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-05:49 | 3107.15 | 13.25 | 56.00 | 318.50 | 1857.93 | 12.06 | 5.50 | 293.00 |
October | 262.67 | 0.64 | 0.61 | 01-OCT-06:30 | 2875.45 | 16.36 | 66.33 | 272.17 | 1714.04 | 16.06 | 43.00 | 220.50 |
November | 257.67 | 0.65 | 0.61 | 01-NOV-08:39 | 1792.49 | 14.56 | 51.00 | 224.83 | 1042.79 | 15.62 | 41.83 | 183.33 |
December | 251.17 | 0.65 | 0.61 | 01-DEC-07:49 | 2070.69 | 17.83 | 78.00 | 213.83 | 1153.91 | 16.72 | 50.00 | 169.50 |
Annual Sum or Average | 3902.00 | 0.64 | 2841.82 | 13.21 | 567.33 | 3636.50 | 1558.08 | 13.70 | 299.83 | 3155.17 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1792.49 | 9.27 | 0.00 | 213.83 | 1042.79 | 11.59 | 0.00 | 169.50 | |
Maximum of Months | 430.33 | 0.66 | 0.61 | 3993.69 | 17.83 | 82.50 | 392.00 | 2001.86 | 17.90 | 61.00 | 359.67 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_3_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.68 | 0.61 | 01-JAN-08:50 | 429.53 | 0.00 | 0.00 | 179.83 | 305.01 | 0.00 | 0.00 | 83.33 |
February | 245.50 | 0.64 | 0.61 | 01-FEB-10:39 | 513.92 | 0.00 | 0.00 | 214.83 | 377.54 | 0.00 | 0.00 | 139.83 |
March | 296.17 | 0.64 | 0.61 | 01-MAR-07:19 | 673.25 | 0.00 | 0.00 | 296.83 | 461.44 | 0.00 | 0.00 | 219.17 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 907.62 | 0.00 | 0.00 | 336.33 | 563.34 | 0.00 | 0.00 | 269.17 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:40 | 1108.76 | 0.00 | 0.00 | 399.83 | 638.73 | 0.00 | 0.00 | 366.00 |
June | 421.50 | 0.62 | 0.61 | 01-JUN-05:10 | 1195.89 | 0.00 | 0.00 | 408.67 | 674.55 | 0.00 | 0.00 | 386.17 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-05:10 | 1140.19 | 0.00 | 0.00 | 408.67 | 648.11 | 0.00 | 0.00 | 375.00 |
August | 394.50 | 0.63 | 0.61 | 01-AUG-05:49 | 904.32 | 0.00 | 0.00 | 374.67 | 572.07 | 0.00 | 0.00 | 331.67 |
September | 354.00 | 0.64 | 0.61 | 01-SEP-06:10 | 738.58 | 0.00 | 0.00 | 311.50 | 491.99 | 0.00 | 0.00 | 264.17 |
October | 262.67 | 0.64 | 0.61 | 01-OCT-06:49 | 621.21 | 0.00 | 0.00 | 261.83 | 445.66 | 0.00 | 0.00 | 191.17 |
November | 257.67 | 0.66 | 0.61 | 01-NOV-08:39 | 479.64 | 0.00 | 0.00 | 202.17 | 348.72 | 0.00 | 0.00 | 130.00 |
December | 251.17 | 0.66 | 0.61 | 01-DEC-08:30 | 439.96 | 0.00 | 0.00 | 189.67 | 311.75 | 0.00 | 0.00 | 91.00 |
Annual Sum or Average | 3902.00 | 0.64 | 816.07 | 0.00 | 0.00 | 3584.83 | 511.12 | 0.00 | 0.00 | 2846.67 | ||
Minimum of Months | 245.50 | 0.62 | 0.61 | 429.53 | 0.00 | 0.00 | 179.83 | 305.01 | 0.00 | 0.00 | 83.33 | |
Maximum of Months | 430.33 | 0.68 | 0.61 | 1195.89 | 0.00 | 0.00 | 408.67 | 674.55 | 0.00 | 0.00 | 386.17 |
Report: DaylightingReportMonthly
For: PERIMETER_TOP_ZN_4_DAYLCTRL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER {FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {MIN FOR HOURS SHOWN} [] | DAYLIGHTING LIGHTING POWER MULTIPLIER {TIMESTAMP} | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE {FOR HOURS SHOWN} [lux] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX {FOR HOURS SHOWN} [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [hr] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [hr] | |
January | 276.50 | 0.65 | 0.61 | 01-JAN-08:50 | 2279.18 | 17.18 | 82.33 | 228.67 | 1504.23 | 19.10 | 79.00 | 180.17 |
February | 245.50 | 0.63 | 0.61 | 01-FEB-10:39 | 2028.57 | 13.80 | 44.67 | 240.17 | 1330.80 | 16.12 | 44.17 | 192.50 |
March | 296.17 | 0.63 | 0.61 | 01-MAR-07:19 | 2777.56 | 15.48 | 72.00 | 315.33 | 1699.13 | 15.40 | 46.00 | 266.33 |
April | 296.67 | 0.63 | 0.61 | 03-APR-09:39 | 2543.20 | 12.71 | 41.33 | 333.50 | 1192.22 | 12.15 | 0.00 | 286.33 |
May | 415.33 | 0.63 | 0.61 | 01-MAY-05:00 | 2907.85 | 10.13 | 0.00 | 383.17 | 1243.01 | 12.39 | 0.00 | 349.00 |
June | 421.50 | 0.63 | 0.61 | 01-JUN-05:49 | 2678.73 | 9.37 | 0.00 | 386.50 | 1586.58 | 11.98 | 0.00 | 361.67 |
July | 430.33 | 0.63 | 0.61 | 01-JUL-06:10 | 2308.94 | 10.00 | 3.67 | 391.00 | 1301.47 | 12.17 | 0.00 | 357.83 |
August | 394.50 | 0.63 | 0.61 | 01-AUG-06:10 | 3110.09 | 12.14 | 48.33 | 369.33 | 1407.74 | 11.76 | 0.00 | 337.83 |
September | 354.00 | 0.63 | 0.61 | 01-SEP-06:40 | 2621.22 | 13.21 | 56.17 | 317.50 | 1504.35 | 12.31 | 5.50 | 292.17 |
October | 262.67 | 0.63 | 0.61 | 01-OCT-06:00 | 3263.84 | 16.71 | 69.67 | 283.00 | 1329.25 | 16.22 | 43.00 | 233.33 |
November | 257.67 | 0.64 | 0.61 | 01-NOV-08:39 | 2374.74 | 17.73 | 77.17 | 235.83 | 1283.39 | 16.78 | 50.50 | 192.83 |
December | 251.17 | 0.64 | 0.61 | 01-DEC-08:30 | 1965.17 | 18.43 | 80.67 | 230.50 | 1081.10 | 17.21 | 52.17 | 179.50 |
Annual Sum or Average | 3902.00 | 0.63 | 2602.09 | 13.33 | 576.00 | 3714.50 | 1379.78 | 14.03 | 320.33 | 3229.50 | ||
Minimum of Months | 245.50 | 0.63 | 0.61 | 1965.17 | 9.37 | 0.00 | 228.67 | 1081.10 | 11.76 | 0.00 | 179.50 | |
Maximum of Months | 430.33 | 0.65 | 0.61 | 3263.84 | 18.43 | 82.33 | 391.00 | 1699.13 | 19.10 | 79.00 | 361.67 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.830430E+10 | 41928.21 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.806569E+10 | 30832.07 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.377355E+10 | 26922.19 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.154502E+10 | 23239.42 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 56719010.74 | 8462.89 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.148061E+09 | 11624.63 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.325648E+10 | 26910.29 | 30-OCT-07:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.494618E+10 | 35348.08 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131489E+11 | 48644.72 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.432449E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131489E+11 | 48644.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_BOTTOM VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.318201E+09 | 14529.31 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.313001E+09 | 14535.59 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 17678409.67 | 13486.64 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 5330696.85 | 9347.16 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 69033025.86 | 13446.12 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.114582E+09 | 13443.79 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.704078E+09 | 14468.59 | 19-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.154190E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.704078E+09 | 14535.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.307301E+09 | 13835.59 | 14-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.424260E+09 | 13841.30 | 10-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.121125E+09 | 13228.74 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 44742248.34 | 13837.61 | 17-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.155715E+09 | 13476.65 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227983E+09 | 13474.39 | 29-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.765370E+09 | 13877.94 | 08-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.204650E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.765370E+09 | 13877.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.315309E+09 | 19010.31 | 07-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.523842E+09 | 19031.23 | 09-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166164E+09 | 18236.60 | 20-MAR-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.122327E+09 | 19133.22 | 03-APR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 194438.48 | 2592.51 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.270267E+09 | 19062.51 | 30-OCT-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.227929E+09 | 19003.06 | 21-NOV-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.672597E+09 | 19059.96 | 11-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.672597E+09 | 19133.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_BOT_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.112127E+09 | 12384.73 | 05-JAN-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 59465914.09 | 12388.35 | 06-FEB-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 16521538.82 | 5267.14 | 31-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 9356355.12 | 12259.69 | 01-NOV-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67983882.72 | 12683.31 | 21-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265455E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.112127E+09 | 12683.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.118574E+12 | 439654.85 | 05-JAN-19:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.121104E+12 | 335984.75 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.736646E+11 | 293128.85 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.400586E+11 | 281711.51 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199101E+10 | 125062.67 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.228569E+10 | 139136.80 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.519650E+11 | 314403.93 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.904042E+11 | 376925.82 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.180432E+12 | 552876.56 | 23-DEC-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.680479E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.180432E+12 | 552876.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_MID VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 9362154.31 | 8534.71 | 02-JAN-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164656E+10 | 560876.63 | 06-FEB-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.373814E+09 | 125126.09 | 20-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.368592E+10 | 547857.29 | 27-DEC-06:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.571566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.368592E+10 | 560876.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.254402E+11 | 137461.79 | 26-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.330249E+11 | 134353.81 | 28-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174125E+11 | 127365.86 | 18-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.910606E+10 | 127049.45 | 15-APR-04:45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.529709E+09 | 126462.67 | 01-MAY-04:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138683E+09 | 121538.08 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.991768E+10 | 137286.51 | 17-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194305E+11 | 131688.95 | 16-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.509603E+11 | 127641.09 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.165960E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.509603E+11 | 137461.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.159171E+11 | 169642.21 | 07-JAN-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.198272E+11 | 170888.81 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123059E+11 | 168524.45 | 29-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.711388E+10 | 169356.22 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.355478E+09 | 164852.24 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136975E+09 | 83893.58 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.877576E+10 | 169445.38 | 30-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.135876E+11 | 169341.76 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.327920E+11 | 169115.70 | 11-DEC-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.110812E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.327920E+11 | 170888.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.866812E+10 | 180142.63 | 06-JAN-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.164537E+11 | 181477.10 | 06-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.123139E+11 | 180501.10 | 20-MAR-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.754584E+10 | 180415.84 | 24-APR-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.618409E+09 | 179589.22 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.126913E+09 | 80338.87 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.857398E+10 | 180229.72 | 31-OCT-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.866994E+10 | 180545.17 | 01-NOV-03:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.239554E+11 | 181658.82 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.869262E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.239554E+11 | 181658.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_MID_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.138998E+11 | 175401.72 | 06-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166868E+11 | 175460.36 | 06-FEB-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.105076E+11 | 175140.82 | 29-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.578133E+10 | 175461.14 | 17-APR-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.439786E+09 | 169199.97 | 01-MAY-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.166318E+09 | 88729.16 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.721978E+10 | 175331.67 | 30-OCT-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.111882E+11 | 175447.44 | 29-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.270263E+11 | 175388.28 | 19-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.929159E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.270263E+11 | 175461.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151541E+11 | 50932.84 | 05-JAN-07:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148615E+11 | 36937.02 | 11-FEB-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.951318E+10 | 34515.56 | 04-MAR-18:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.554163E+10 | 33496.22 | 17-APR-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.401853E+09 | 16887.85 | 02-MAY-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.391013E+09 | 19509.54 | 22-SEP-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.733920E+10 | 37757.87 | 30-OCT-06:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.118122E+11 | 43228.88 | 29-NOV-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.221971E+11 | 63501.78 | 23-DEC-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.872118E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.221971E+11 | 63501.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CORE_TOP VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.486247E+10 | 77988.58 | 30-JAN-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.490296E+10 | 77420.97 | 08-FEB-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.258397E+10 | 77505.25 | 20-MAR-05:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.247482E+10 | 77639.57 | 24-APR-05:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.229668E+09 | 77907.58 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.188913E+10 | 77390.77 | 24-OCT-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273287E+10 | 77842.22 | 13-NOV-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.688174E+10 | 77421.86 | 27-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.265576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.688174E+10 | 77988.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_3 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.727579E+10 | 14746.90 | 30-JAN-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.754456E+10 | 14733.59 | 21-FEB-06:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.498859E+10 | 14747.82 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332788E+10 | 14730.70 | 24-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.345511E+09 | 14735.91 | 01-MAY-05:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143382E+09 | 14636.87 | 22-SEP-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.334346E+10 | 14724.31 | 23-OCT-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.538228E+10 | 14742.02 | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.107279E+11 | 14703.53 | 04-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.430793E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.107279E+11 | 14747.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_2 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.398427E+10 | 17131.34 | 30-JAN-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.414151E+10 | 17160.98 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.290304E+10 | 17142.16 | 02-MAR-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.206441E+10 | 17160.43 | 04-APR-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.188848E+09 | 17104.99 | 01-MAY-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 84676152.37 | 16971.84 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.225606E+10 | 17193.73 | 23-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.319571E+10 | 17169.04 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.648313E+10 | 17137.43 | 06-DEC-06:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.253016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.648313E+10 | 17193.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_1 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.312677E+10 | 20080.68 | 30-JAN-05:23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.425882E+10 | 19972.79 | 21-FEB-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.366152E+10 | 20025.51 | 21-MAR-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.297782E+10 | 20004.56 | 24-APR-04:53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.380385E+09 | 20031.80 | 01-MAY-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.105439E+09 | 19758.16 | 22-SEP-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.269416E+10 | 19993.46 | 23-OCT-04:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280056E+10 | 20034.90 | 13-NOV-05:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595169E+10 | 19917.99 | 28-DEC-06:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.259572E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.595169E+10 | 20080.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PERIMETER_TOP_ZN_4 VAV BOX REHEAT COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.357776E+10 | 20041.72 | 06-JAN-05:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.371427E+10 | 20116.36 | 02-FEB-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.266961E+10 | 20045.03 | 18-MAR-05:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.180094E+10 | 20066.63 | 24-APR-04:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.233131E+09 | 20010.05 | 01-MAY-04:22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.104429E+09 | 19927.31 | 22-SEP-04:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.195966E+10 | 20094.33 | 30-OCT-03:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.280704E+10 | 20202.36 | 24-NOV-05:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.553688E+10 | 20042.52 | 19-DEC-05:12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.224037E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.553688E+10 | 20202.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: CAV_BAS HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP HEATING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP_SUPPHEATCOIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: VAV_BOT WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.283962E+10 | 0.283962E+10 | 54823.91 | 20-JAN-14:00 | 54823.91 | 0.00 |
February | 0.00 | 0.00 | 0.944835E+09 | 0.944835E+09 | 32907.08 | 18-FEB-13:30 | 32907.08 | 0.00 |
March | 0.00 | 0.00 | 0.890292E+10 | 0.890292E+10 | 91526.55 | 13-MAR-16:00 | 91526.55 | 0.00 |
April | 0.00 | 0.00 | 0.978636E+10 | 0.978636E+10 | 77662.88 | 19-APR-13:40 | 77662.88 | 0.00 |
May | 0.00 | 0.00 | 0.313647E+11 | 0.313647E+11 | 100467.44 | 31-MAY-15:20 | 100467.44 | 0.02 |
June | 0.00 | 0.00 | 0.104988E+12 | 0.104775E+12 | 143482.25 | 26-JUN-14:40 | 143482.25 | 0.28 |
July | 0.00 | 0.00 | 0.112260E+12 | 0.109519E+12 | 136432.40 | 17-JUL-10:20 | 136432.40 | 0.36 |
August | 0.00 | 0.00 | 0.120327E+12 | 0.119327E+12 | 143771.40 | 16-AUG-14:30 | 143771.40 | 0.42 |
September | 0.00 | 0.00 | 0.688340E+11 | 0.688340E+11 | 120773.38 | 12-SEP-15:50 | 120773.38 | 0.05 |
October | 0.00 | 0.00 | 0.143030E+11 | 0.143030E+11 | 109938.02 | 10-OCT-16:00 | 109938.02 | 0.00 |
November | 0.00 | 0.00 | 0.570420E+10 | 0.570420E+10 | 76415.62 | 06-NOV-14:00 | 76415.62 | 0.00 |
December | 0.00 | 0.00 | 0.333768E+10 | 0.333768E+10 | 63734.96 | 01-DEC-14:00 | 63734.96 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.483592E+12 | 0.479639E+12 | 0.10 | |||
Minimum of Months | 0.00 | 0.00 | 0.944835E+09 | 0.944835E+09 | 32907.08 | 32907.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120327E+12 | 0.119327E+12 | 143771.40 | 143771.40 | 0.42 |
Report: CoilReportMonthly
For: VAV_MID WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.233997E+11 | 0.233997E+11 | 437975.19 | 20-JAN-14:10 | 437975.19 | 0.00 |
February | 0.00 | 0.00 | 0.897062E+10 | 0.897062E+10 | 336576.99 | 18-FEB-14:00 | 336576.99 | 0.00 |
March | 0.00 | 0.00 | 0.674521E+11 | 0.674521E+11 | 706436.03 | 14-MAR-13:00 | 706436.03 | 0.00 |
April | 0.00 | 0.00 | 0.571348E+11 | 0.571348E+11 | 521767.83 | 20-APR-13:00 | 521767.83 | 0.00 |
May | 0.00 | 0.00 | 0.263572E+12 | 0.263572E+12 | 907494.53 | 31-MAY-16:00 | 907494.53 | 0.02 |
June | 0.00 | 0.00 | 0.898283E+12 | 0.896784E+12 | 1288050.03 | 26-JUN-15:10 | 1288050.03 | 0.26 |
July | 0.00 | 0.00 | 0.905863E+12 | 0.887949E+12 | 1195684.52 | 17-JUL-10:30 | 1195684.52 | 0.29 |
August | 0.00 | 0.00 | 0.870009E+12 | 0.866203E+12 | 1273398.48 | 04-AUG-05:02 | 454470.25 | 0.29 |
September | 0.00 | 0.00 | 0.595871E+12 | 0.595871E+12 | 1124472.73 | 12-SEP-16:00 | 1124472.73 | 0.05 |
October | 0.00 | 0.00 | 0.117840E+12 | 0.117840E+12 | 894101.05 | 11-OCT-15:00 | 894101.05 | 0.00 |
November | 0.00 | 0.00 | 0.409706E+11 | 0.409706E+11 | 571337.61 | 07-NOV-15:00 | 571337.61 | 0.00 |
December | 0.00 | 0.00 | 0.218743E+11 | 0.218743E+11 | 421010.74 | 01-DEC-14:00 | 421010.74 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.387124E+13 | 0.384802E+13 | 0.08 | |||
Minimum of Months | 0.00 | 0.00 | 0.897062E+10 | 0.897062E+10 | 336576.99 | 336576.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.905863E+12 | 0.896784E+12 | 1288050.03 | 1288050.03 | 0.29 |
Report: CoilReportMonthly
For: VAV_TOP WITH REHEAT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.174577E+10 | 0.174577E+10 | 40880.31 | 20-JAN-14:00 | 40880.31 | 0.00 |
February | 0.00 | 0.00 | 0.630822E+09 | 0.630822E+09 | 30806.55 | 18-FEB-13:30 | 30806.55 | 0.00 |
March | 0.00 | 0.00 | 0.620200E+10 | 0.620200E+10 | 73083.34 | 14-MAR-13:10 | 73083.34 | 0.00 |
April | 0.00 | 0.00 | 0.588128E+10 | 0.588128E+10 | 58750.10 | 20-APR-13:00 | 58750.10 | 0.00 |
May | 0.00 | 0.00 | 0.272054E+11 | 0.272054E+11 | 111611.51 | 31-MAY-15:20 | 111611.51 | 0.02 |
June | 0.00 | 0.00 | 0.101902E+12 | 0.101792E+12 | 164541.01 | 26-JUN-14:40 | 164541.01 | 0.25 |
July | 0.00 | 0.00 | 0.100797E+12 | 0.990265E+11 | 144328.34 | 17-JUL-14:00 | 144328.34 | 0.29 |
August | 0.00 | 0.00 | 0.967176E+11 | 0.963874E+11 | 155132.51 | 16-AUG-15:10 | 155132.51 | 0.27 |
September | 0.00 | 0.00 | 0.623306E+11 | 0.623306E+11 | 130266.02 | 12-SEP-16:00 | 130266.02 | 0.04 |
October | 0.00 | 0.00 | 0.105823E+11 | 0.105823E+11 | 100824.49 | 11-OCT-15:00 | 100824.49 | 0.00 |
November | 0.00 | 0.00 | 0.331335E+10 | 0.331335E+10 | 55281.35 | 07-NOV-15:00 | 55281.35 | 0.00 |
December | 0.00 | 0.00 | 0.168163E+10 | 0.168163E+10 | 39112.20 | 01-DEC-14:00 | 39112.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.418990E+12 | 0.416779E+12 | 0.07 | |||
Minimum of Months | 0.00 | 0.00 | 0.630822E+09 | 0.630822E+09 | 30806.55 | 30806.55 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.101902E+12 | 0.101792E+12 | 164541.01 | 164541.01 | 0.29 |
Report: CoilReportMonthly
For: CAV_BAS COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.101590E+10 | 0.101590E+10 | 29858.76 | 20-JAN-14:00 | 29858.76 | 0.00 |
February | 0.00 | 0.00 | 81446874.48 | 81446874.48 | 10584.25 | 18-FEB-13:00 | 10584.25 | 0.00 |
March | 0.00 | 0.00 | 0.344417E+10 | 0.344417E+10 | 53474.31 | 14-MAR-13:00 | 53474.31 | 0.00 |
April | 0.00 | 0.00 | 0.397344E+10 | 0.397344E+10 | 39577.02 | 20-APR-13:00 | 39577.02 | 0.00 |
May | 0.00 | 0.00 | 0.180353E+11 | 0.180317E+11 | 57399.28 | 31-MAY-14:00 | 57399.28 | 0.02 |
June | 0.00 | 0.00 | 0.577863E+11 | 0.577609E+11 | 78550.85 | 26-JUN-15:00 | 78550.85 | 0.20 |
July | 0.00 | 0.00 | 0.586508E+11 | 0.580517E+11 | 78691.06 | 17-JUL-10:00 | 78691.06 | 0.25 |
August | 0.00 | 0.00 | 0.629855E+11 | 0.627297E+11 | 96858.01 | 20-AUG-13:31 | 96858.01 | 0.23 |
September | 0.00 | 0.00 | 0.423431E+11 | 0.423419E+11 | 97303.42 | 10-SEP-15:54 | 97303.42 | 0.04 |
October | 0.00 | 0.00 | 0.721101E+10 | 0.721101E+10 | 68290.14 | 10-OCT-14:00 | 68290.14 | 0.00 |
November | 0.00 | 0.00 | 0.266115E+10 | 0.266115E+10 | 51440.94 | 06-NOV-13:10 | 51440.94 | 0.00 |
December | 0.00 | 0.00 | 0.143717E+10 | 0.143717E+10 | 40095.56 | 04-DEC-12:00 | 40095.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.259625E+12 | 0.258740E+12 | 0.06 | |||
Minimum of Months | 0.00 | 0.00 | 81446874.48 | 81446874.48 | 10584.25 | 10584.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.629855E+11 | 0.627297E+11 | 97303.42 | 97303.42 | 0.25 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BASEMENT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.395501E+12 | 0.345171E+12 | 152603.64 | 19-JAN-22:10 | 132871.28 | 0.00 |
February | 0.00 | 0.00 | 0.611597E+12 | 0.533130E+12 | 259014.13 | 17-FEB-22:03 | 225197.82 | 0.00 |
March | 0.00 | 0.00 | 0.960785E+12 | 0.840716E+12 | 461509.32 | 31-MAR-24:00 | 404206.06 | 0.00 |
April | 0.00 | 0.00 | 0.121253E+13 | 0.104885E+13 | 479334.10 | 12-APR-21:03 | 406352.72 | 0.00 |
May | 0.00 | 0.00 | 0.403487E+12 | 0.353735E+12 | 250948.78 | 31-MAY-24:00 | 220597.50 | 0.00 |
June | 0.00 | 0.00 | 0.646633E+12 | 0.584783E+12 | 342784.42 | 30-JUN-24:00 | 312693.97 | 0.00 |
July | 0.00 | 0.00 | 0.932490E+12 | 0.850859E+12 | 440614.02 | 31-JUL-24:00 | 398027.54 | 0.00 |
August | 0.00 | 0.00 | 0.123079E+13 | 0.107804E+13 | 486346.88 | 17-AUG-02:55 | 412409.06 | 0.00 |
September | 0.00 | 0.00 | 0.393007E+12 | 0.348541E+12 | 253329.76 | 30-SEP-24:00 | 221131.19 | 0.00 |
October | 0.00 | 0.00 | 0.686245E+12 | 0.599500E+12 | 358387.06 | 31-OCT-23:45 | 311907.49 | 0.00 |
November | 0.00 | 0.00 | 0.935721E+12 | 0.816929E+12 | 366660.44 | 07-NOV-22:03 | 319279.49 | 0.00 |
December | 0.00 | 0.00 | 0.125644E+13 | 0.108372E+13 | 480820.76 | 03-DEC-17:10 | 409793.52 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.966522E+13 | 0.848397E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.393007E+12 | 0.345171E+12 | 152603.64 | 132871.28 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.125644E+13 | 0.108372E+13 | 486346.88 | 412409.06 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER BOT COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.457984E+10 | 0.457121E+10 | 2815.10 | 23-JAN-16:30 | 2815.10 | 0.00 |
February | 0.00 | 0.00 | 0.878910E+10 | 0.878499E+10 | 4761.58 | 17-FEB-17:00 | 4736.27 | 0.00 |
March | 0.00 | 0.00 | 0.153951E+11 | 0.153836E+11 | 7813.64 | 31-MAR-24:00 | 7813.64 | 0.00 |
April | 0.00 | 0.00 | 0.201796E+11 | 0.201527E+11 | 8831.25 | 08-APR-18:14 | 8831.25 | 0.00 |
May | 0.00 | 0.00 | 0.594423E+10 | 0.589132E+10 | 4171.26 | 31-MAY-24:00 | 4151.03 | 0.00 |
June | 0.00 | 0.00 | 0.112425E+11 | 0.111364E+11 | 6023.09 | 30-JUN-24:00 | 6023.09 | 0.00 |
July | 0.00 | 0.00 | 0.166513E+11 | 0.165185E+11 | 7923.90 | 31-JUL-24:00 | 7923.90 | 0.00 |
August | 0.00 | 0.00 | 0.220239E+11 | 0.219139E+11 | 9126.39 | 05-AUG-18:53 | 9092.99 | 0.00 |
September | 0.00 | 0.00 | 0.606291E+10 | 0.602322E+10 | 4010.31 | 30-SEP-24:00 | 4010.31 | 0.00 |
October | 0.00 | 0.00 | 0.105966E+11 | 0.105782E+11 | 5300.97 | 09-OCT-16:43 | 5300.97 | 0.00 |
November | 0.00 | 0.00 | 0.149170E+11 | 0.149030E+11 | 6862.25 | 05-NOV-16:14 | 6862.25 | 0.00 |
December | 0.00 | 0.00 | 0.201918E+11 | 0.201918E+11 | 8758.62 | 03-DEC-16:15 | 8758.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.156574E+12 | 0.156049E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.457984E+10 | 0.457121E+10 | 2815.10 | 2815.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.220239E+11 | 0.219139E+11 | 9126.39 | 9092.99 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER MID COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.266695E+11 | 0.265879E+11 | 25505.92 | 23-JAN-16:40 | 25505.92 | 0.00 |
February | 0.00 | 0.00 | 0.666591E+11 | 0.666178E+11 | 43991.95 | 17-FEB-17:00 | 43682.58 | 0.00 |
March | 0.00 | 0.00 | 0.131503E+12 | 0.131388E+12 | 72276.93 | 31-MAR-23:40 | 72276.93 | 0.00 |
April | 0.00 | 0.00 | 0.176643E+12 | 0.176374E+12 | 82333.74 | 08-APR-18:00 | 82333.74 | 0.00 |
May | 0.00 | 0.00 | 0.509274E+11 | 0.504058E+11 | 39361.15 | 31-MAY-24:00 | 39141.92 | 0.00 |
June | 0.00 | 0.00 | 0.105815E+12 | 0.104757E+12 | 58669.72 | 30-JUN-24:00 | 58669.72 | 0.00 |
July | 0.00 | 0.00 | 0.157940E+12 | 0.156615E+12 | 74771.73 | 31-JUL-24:00 | 74771.73 | 0.00 |
August | 0.00 | 0.00 | 0.205234E+12 | 0.204136E+12 | 85358.15 | 05-AUG-18:12 | 85035.05 | 0.00 |
September | 0.00 | 0.00 | 0.537465E+11 | 0.533551E+11 | 36436.67 | 30-SEP-24:00 | 36436.67 | 0.00 |
October | 0.00 | 0.00 | 0.894818E+11 | 0.892985E+11 | 47509.05 | 09-OCT-16:43 | 47509.05 | 0.00 |
November | 0.00 | 0.00 | 0.126320E+12 | 0.126180E+12 | 63327.51 | 07-NOV-16:10 | 63327.51 | 0.00 |
December | 0.00 | 0.00 | 0.166559E+12 | 0.166559E+12 | 77960.22 | 01-DEC-16:00 | 77960.22 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135750E+13 | 0.135227E+13 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.266695E+11 | 0.265879E+11 | 25505.92 | 25505.92 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205234E+12 | 0.204136E+12 | 85358.15 | 85035.05 | 0.00 |
Report: CoilReportMonthly
For: AIRLOOP DATACENTER TOP COOLING COIL
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.121823E+10 | 0.121148E+10 | 2543.58 | 20-JAN-16:30 | 2543.58 | 0.00 |
February | 0.00 | 0.00 | 0.510167E+10 | 0.509766E+10 | 4392.75 | 17-FEB-17:00 | 4364.89 | 0.00 |
March | 0.00 | 0.00 | 0.118079E+11 | 0.117966E+11 | 7043.92 | 31-MAR-23:20 | 7043.92 | 0.00 |
April | 0.00 | 0.00 | 0.162951E+11 | 0.162683E+11 | 8261.85 | 08-APR-17:47 | 8261.85 | 0.00 |
May | 0.00 | 0.00 | 0.458453E+10 | 0.453286E+10 | 3904.90 | 31-MAY-23:50 | 3880.86 | 0.00 |
June | 0.00 | 0.00 | 0.106108E+11 | 0.105051E+11 | 5893.91 | 30-JUN-24:00 | 5893.91 | 0.00 |
July | 0.00 | 0.00 | 0.158393E+11 | 0.157069E+11 | 7388.04 | 31-JUL-24:00 | 7388.04 | 0.00 |
August | 0.00 | 0.00 | 0.205286E+11 | 0.204190E+11 | 8653.51 | 13-AUG-18:52 | 8653.51 | 0.00 |
September | 0.00 | 0.00 | 0.511072E+10 | 0.507173E+10 | 3434.07 | 10-SEP-17:35 | 3434.07 | 0.00 |
October | 0.00 | 0.00 | 0.761194E+10 | 0.759402E+10 | 4729.04 | 08-OCT-16:50 | 4729.04 | 0.00 |
November | 0.00 | 0.00 | 0.109230E+11 | 0.109093E+11 | 6340.45 | 07-NOV-16:10 | 6340.45 | 0.00 |
December | 0.00 | 0.00 | 0.147771E+11 | 0.147771E+11 | 7744.34 | 01-DEC-16:00 | 7744.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.124409E+12 | 0.123890E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.121823E+10 | 0.121148E+10 | 2543.58 | 2543.58 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.205286E+11 | 0.204190E+11 | 8653.51 | 8653.51 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 85359.89 | 1223642.34 | 30-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 105902.10 | 1472100.42 | 13-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 58307.61 | 1275163.21 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 34353.95 | 1188559.86 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 2144.19 | 1227356.24 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 1475.59 | 665467.67 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 40775.48 | 1187798.02 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 68130.56 | 1389521.94 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 145587.41 | 1660739.20 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 44880.75 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 145587.41 | 1660739.20 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 23655.12 | 1078505.91 | 20-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 11836.59 | 806810.17 | 18-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 56314.57 | 1154405.48 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 59044.71 | 1124452.25 | 20-APR-12:50 | 0.63 | 10863.93 | 09-APR-15:23 |
May | 198278.57 | 1275271.82 | 31-MAY-12:20 | 42.60 | 198737.37 | 21-MAY-13:53 |
June | 570104.78 | 1674456.29 | 26-JUN-15:10 | 40.49 | 105157.52 | 18-JUN-05:42 |
July | 568809.93 | 1572141.99 | 18-JUL-15:10 | 27.81 | 83815.03 | 09-JUL-05:23 |
August | 547887.40 | 1614763.88 | 16-AUG-15:10 | 1.38 | 14735.16 | 12-AUG-19:03 |
September | 408089.75 | 1563049.23 | 12-SEP-15:50 | 22.12 | 71236.22 | 05-SEP-00:12 |
October | 96894.36 | 1246628.10 | 10-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 40289.92 | 1086059.66 | 06-NOV-14:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23299.24 | 1079518.47 | 01-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218155.11 | 11.29 | ||||
Minimum of Months | 11836.59 | 806810.17 | 0.00 | 0.00 | ||
Maximum of Months | 570104.78 | 1674456.29 | 42.60 | 198737.37 |
Report: PlantLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15051.83 | 770042.58 | 20-JAN-14:10 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5815.10 | 538793.57 | 18-FEB-13:30 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 42207.72 | 1181459.50 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 37014.68 | 848576.03 | 20-APR-13:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 148678.89 | 1282545.46 | 31-MAY-12:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 491409.09 | 2193842.11 | 14-JUN-05:02 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 482214.64 | 2249501.97 | 17-JUL-05:02 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 471969.04 | 2784227.94 | 04-AUG-05:02 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 333753.06 | 1581505.42 | 30-SEP-05:02 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 71034.49 | 1295331.57 | 10-OCT-13:30 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27398.36 | 983950.92 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13645.10 | 729037.97 | 01-DEC-14:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 179284.75 | 0.00 | ||||
Minimum of Months | 5815.10 | 538793.57 | 0.00 | 0.00 | ||
Maximum of Months | 491409.09 | 2784227.94 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 208421.52 | 509292.67 | 20-JAN-14:00 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 365493.99 | 689546.90 | 18-FEB-14:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 561378.32 | 1200754.67 | 14-MAR-13:00 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 747765.93 | 1340781.37 | 19-APR-14:00 | 0.00 | 0.00 | 01-APR-00:10 |
May | 313314.02 | 980754.41 | 17-MAY-14:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 853788.61 | 1871838.21 | 26-JUN-15:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1140395.80 | 1984870.54 | 16-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1348334.53 | 2249949.28 | 16-AUG-16:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 468117.70 | 1185291.90 | 10-SEP-13:40 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 419529.57 | 1129354.83 | 11-OCT-14:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 549166.55 | 1097624.03 | 07-NOV-15:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 700405.72 | 1314546.68 | 02-DEC-15:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 641764.82 | 0.00 | ||||
Minimum of Months | 208421.52 | 509292.67 | 0.00 | 0.00 | ||
Maximum of Months | 1348334.53 | 2249949.28 | 0.00 | 0.00 |
Report: PlantLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 16408.62 | 55406.87 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 16683.68 | 55579.41 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 17397.18 | 55340.28 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 15808.28 | 53647.26 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 15467.35 | 51247.38 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 14952.58 | 48242.39 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 13310.01 | 45617.74 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 14225.67 | 44370.04 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 13661.76 | 45799.07 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 14243.72 | 48489.60 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 15229.44 | 51404.46 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 15485.94 | 53828.33 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 15231.23 | ||||
Minimum of Months | 0.00 | 0.00 | 13310.01 | 44370.04 | ||
Maximum of Months | 0.00 | 0.00 | 17397.18 | 55579.41 |
Report: PlantLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12682.06 | 692285.05 | 20-JAN-14:10 | 1886.58 | 132660.19 | 13-JAN-06:50 |
February | 4362.12 | 480100.83 | 18-FEB-13:30 | 2806.71 | 132626.84 | 10-FEB-14:10 |
March | 39420.84 | 1971341.17 | 13-MAR-14:50 | 2068.22 | 132040.38 | 29-MAR-12:40 |
April | 35208.95 | 800283.44 | 19-APR-13:30 | 2525.65 | 132399.87 | 10-APR-05:50 |
May | 161520.65 | 2097788.50 | 31-MAY-12:20 | 1496.27 | 113199.09 | 02-MAY-13:10 |
June | 613500.20 | 2201466.24 | 23-JUN-15:00 | 901.98 | 85208.60 | 09-JUN-06:20 |
July | 593126.94 | 2199387.00 | 10-JUL-10:20 | 839.17 | 77462.87 | 01-JUL-22:10 |
August | 586249.47 | 2201298.76 | 14-AUG-10:40 | 1788.24 | 80691.57 | 18-AUG-01:40 |
September | 413681.27 | 2199639.27 | 06-SEP-15:10 | 866.15 | 110298.30 | 22-SEP-11:20 |
October | 72425.49 | 1978606.79 | 10-OCT-12:50 | 1855.33 | 115952.23 | 23-OCT-05:50 |
November | 23603.92 | 856947.33 | 07-NOV-15:00 | 2146.70 | 126670.88 | 02-NOV-12:30 |
December | 12177.35 | 689873.50 | 01-DEC-14:00 | 2001.78 | 132608.53 | 08-DEC-12:30 |
Annual Sum or Average | 215089.47 | 1758.37 | ||||
Minimum of Months | 4362.12 | 480100.83 | 839.17 | 77462.87 | ||
Maximum of Months | 613500.20 | 2201466.24 | 2806.71 | 132660.19 |
Report: FanReportMonthly
For: CAV_BAS FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165652E+11 | 0.97 | 10896.36 | 01-JAN-00:05 | 1.72 |
February | 0.146440E+11 | 0.95 | 10896.36 | 01-FEB-05:01 | 1.72 |
March | 0.173041E+11 | 1.02 | 10896.36 | 01-MAR-05:01 | 1.71 |
April | 0.160860E+11 | 0.98 | 10896.36 | 01-APR-04:03 | 1.71 |
May | 0.169972E+11 | 1.00 | 10896.36 | 01-MAY-03:01 | 1.71 |
June | 0.171977E+11 | 1.04 | 10896.36 | 01-JUN-03:02 | 1.70 |
July | 0.169264E+11 | 0.99 | 10896.36 | 01-JUL-03:02 | 1.72 |
August | 0.190488E+11 | 1.11 | 10896.36 | 01-AUG-03:02 | 1.71 |
September | 0.177138E+11 | 1.07 | 10896.36 | 01-SEP-03:02 | 1.69 |
October | 0.176085E+11 | 1.03 | 10896.36 | 01-OCT-19:50 | 1.69 |
November | 0.163756E+11 | 0.99 | 10896.36 | 01-NOV-04:01 | 1.72 |
December | 0.162014E+11 | 0.95 | 10896.36 | 01-DEC-05:01 | 1.72 |
Annual Sum or Average | 0.202669E+12 | 1.01 | |||
Minimum of Months | 0.146440E+11 | 0.95 | 10896.36 | 1.69 | |
Maximum of Months | 0.190488E+11 | 1.11 | 10896.36 | 1.72 |
Report: FanReportMonthly
For: VAV_BOT WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.542246E+10 | 0.43 | 15020.21 | 07-JAN-06:01 | 1.65 |
February | 0.526724E+10 | 0.44 | 15020.21 | 09-FEB-06:01 | 1.65 |
March | 0.811060E+10 | 0.54 | 17010.79 | 13-MAR-16:00 | 1.79 |
April | 0.904790E+10 | 0.56 | 17017.03 | 07-APR-14:50 | 1.79 |
May | 0.920849E+10 | 0.57 | 14175.11 | 31-MAY-15:20 | 1.58 |
June | 0.152946E+11 | 0.81 | 25376.02 | 06-JUN-05:03 | 2.28 |
July | 0.156829E+11 | 0.83 | 25376.02 | 05-JUL-05:02 | 2.29 |
August | 0.196653E+11 | 0.99 | 25376.02 | 07-AUG-09:50 | 2.27 |
September | 0.111300E+11 | 0.65 | 24321.92 | 05-SEP-05:02 | 2.22 |
October | 0.778178E+10 | 0.52 | 19308.18 | 10-OCT-16:00 | 1.93 |
November | 0.707163E+10 | 0.50 | 15292.68 | 06-NOV-15:30 | 1.67 |
December | 0.658624E+10 | 0.47 | 17362.37 | 21-DEC-06:01 | 1.81 |
Annual Sum or Average | 0.120269E+12 | 0.61 | |||
Minimum of Months | 0.526724E+10 | 0.43 | 14175.11 | 1.58 | |
Maximum of Months | 0.196653E+11 | 0.99 | 25376.02 | 2.29 |
Report: FanReportMonthly
For: VAV_MID WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.388986E+11 | 0.39 | 113244.97 | 26-JAN-06:02 | 1.45 |
February | 0.367751E+11 | 0.42 | 125151.84 | 23-FEB-06:02 | 1.54 |
March | 0.496074E+11 | 0.45 | 111271.33 | 31-MAR-05:03 | 1.43 |
April | 0.426741E+11 | 0.40 | 121624.92 | 10-APR-05:02 | 1.52 |
May | 0.683396E+11 | 0.49 | 132492.98 | 18-MAY-14:30 | 1.59 |
June | 0.120986E+12 | 0.71 | 235813.89 | 14-JUN-05:02 | 2.30 |
July | 0.113388E+12 | 0.66 | 235813.89 | 17-JUL-05:02 | 2.29 |
August | 0.116761E+12 | 0.68 | 219657.14 | 03-AUG-05:03 | 2.17 |
September | 0.860551E+11 | 0.58 | 166894.98 | 13-SEP-15:20 | 1.83 |
October | 0.505251E+11 | 0.43 | 112235.50 | 17-OCT-05:02 | 1.44 |
November | 0.407137E+11 | 0.40 | 112578.29 | 16-NOV-06:03 | 1.44 |
December | 0.390285E+11 | 0.42 | 58191.02 | 26-DEC-05:01 | 0.99 |
Annual Sum or Average | 0.803753E+12 | 0.50 | |||
Minimum of Months | 0.367751E+11 | 0.39 | 58191.02 | 0.99 | |
Maximum of Months | 0.120986E+12 | 0.71 | 235813.89 | 2.30 |
Report: FanReportMonthly
For: VAV_TOP WITH REHEAT FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.419994E+10 | 0.45 | 5980.61 | 20-JAN-16:20 | 0.95 |
February | 0.382108E+10 | 0.44 | 5561.20 | 01-FEB-06:01 | 0.91 |
March | 0.481006E+10 | 0.47 | 12381.66 | 15-MAR-16:00 | 1.45 |
April | 0.441905E+10 | 0.44 | 11401.45 | 21-APR-13:30 | 1.37 |
May | 0.600202E+10 | 0.44 | 14799.78 | 31-MAY-16:00 | 1.59 |
June | 0.129095E+11 | 0.69 | 26022.25 | 26-JUN-13:30 | 2.28 |
July | 0.117518E+11 | 0.64 | 26022.25 | 18-JUL-14:40 | 2.28 |
August | 0.119716E+11 | 0.65 | 23030.61 | 11-AUG-15:10 | 2.12 |
September | 0.803162E+10 | 0.53 | 19631.03 | 12-SEP-16:00 | 1.91 |
October | 0.443986E+10 | 0.42 | 11403.41 | 10-OCT-16:00 | 1.38 |
November | 0.374788E+10 | 0.40 | 6827.41 | 07-NOV-16:10 | 1.02 |
December | 0.432688E+10 | 0.46 | 5561.20 | 04-DEC-06:01 | 0.91 |
Annual Sum or Average | 0.804312E+11 | 0.50 | |||
Minimum of Months | 0.374788E+10 | 0.40 | 5561.20 | 0.91 | |
Maximum of Months | 0.129095E+11 | 0.69 | 26022.25 | 2.28 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BASEMENT SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.115586E+12 | 1.65 | 43154.82 | 01-JAN-00:05 | 1.65 |
February | 0.104400E+12 | 1.65 | 43154.82 | 01-FEB-00:10 | 1.65 |
March | 0.115586E+12 | 1.65 | 43154.82 | 01-MAR-00:10 | 1.65 |
April | 0.111857E+12 | 1.65 | 43154.82 | 01-APR-00:10 | 1.65 |
May | 0.115586E+12 | 1.65 | 43154.82 | 01-MAY-00:10 | 1.65 |
June | 0.111857E+12 | 1.65 | 43154.82 | 01-JUN-00:10 | 1.65 |
July | 0.115586E+12 | 1.65 | 43154.82 | 01-JUL-00:05 | 1.65 |
August | 0.115586E+12 | 1.64 | 43154.82 | 01-AUG-00:10 | 1.65 |
September | 0.111857E+12 | 1.65 | 43154.82 | 01-SEP-00:05 | 1.65 |
October | 0.115586E+12 | 1.65 | 43154.82 | 01-OCT-00:10 | 1.65 |
November | 0.111857E+12 | 1.65 | 43154.82 | 01-NOV-00:10 | 1.65 |
December | 0.115586E+12 | 1.65 | 43154.82 | 01-DEC-00:10 | 1.65 |
Annual Sum or Average | 0.136093E+13 | 1.65 | |||
Minimum of Months | 0.104400E+12 | 1.64 | 43154.82 | 1.65 | |
Maximum of Months | 0.115586E+12 | 1.65 | 43154.82 | 1.65 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER BOT SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.178697E+10 | 1.13 | 667.18 | 01-JAN-00:05 | 1.13 |
February | 0.161404E+10 | 1.13 | 667.18 | 01-FEB-00:10 | 1.13 |
March | 0.178697E+10 | 1.13 | 667.18 | 01-MAR-00:10 | 1.13 |
April | 0.172933E+10 | 1.13 | 667.18 | 01-APR-00:10 | 1.13 |
May | 0.178697E+10 | 1.13 | 667.18 | 01-MAY-00:10 | 1.13 |
June | 0.172933E+10 | 1.13 | 667.18 | 01-JUN-00:10 | 1.13 |
July | 0.178697E+10 | 1.13 | 667.18 | 01-JUL-00:05 | 1.13 |
August | 0.178697E+10 | 1.13 | 667.18 | 01-AUG-00:10 | 1.13 |
September | 0.172933E+10 | 1.13 | 667.18 | 01-SEP-00:05 | 1.13 |
October | 0.178697E+10 | 1.13 | 667.18 | 01-OCT-00:10 | 1.13 |
November | 0.172933E+10 | 1.13 | 667.18 | 01-NOV-00:10 | 1.13 |
December | 0.178697E+10 | 1.13 | 667.18 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.210401E+11 | 1.13 | |||
Minimum of Months | 0.161404E+10 | 1.13 | 667.18 | 1.13 | |
Maximum of Months | 0.178697E+10 | 1.13 | 667.18 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER MID SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170931E+11 | 1.13 | 6381.83 | 01-JAN-00:05 | 1.13 |
February | 0.154389E+11 | 1.13 | 6381.83 | 01-FEB-00:10 | 1.13 |
March | 0.170931E+11 | 1.13 | 6381.83 | 01-MAR-00:10 | 1.13 |
April | 0.165417E+11 | 1.13 | 6381.83 | 01-APR-00:10 | 1.13 |
May | 0.170931E+11 | 1.13 | 6381.83 | 01-MAY-00:10 | 1.13 |
June | 0.165417E+11 | 1.13 | 6381.83 | 01-JUN-00:10 | 1.13 |
July | 0.170931E+11 | 1.13 | 6381.83 | 01-JUL-00:05 | 1.13 |
August | 0.170931E+11 | 1.13 | 6381.83 | 01-AUG-00:20 | 1.13 |
September | 0.165417E+11 | 1.13 | 6381.83 | 01-SEP-00:05 | 1.13 |
October | 0.170931E+11 | 1.13 | 6381.83 | 01-OCT-00:10 | 1.13 |
November | 0.165417E+11 | 1.13 | 6381.83 | 01-NOV-00:10 | 1.13 |
December | 0.170931E+11 | 1.13 | 6381.83 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.201257E+12 | 1.13 | |||
Minimum of Months | 0.154389E+11 | 1.13 | 6381.83 | 1.13 | |
Maximum of Months | 0.170931E+11 | 1.13 | 6381.83 | 1.13 |
Report: FanReportMonthly
For: AIRLOOP DATACENTER TOP SUPPLY FAN
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.174452E+10 | 1.13 | 651.33 | 01-JAN-00:05 | 1.13 |
February | 0.157569E+10 | 1.13 | 651.33 | 01-FEB-00:10 | 1.13 |
March | 0.174452E+10 | 1.13 | 651.33 | 01-MAR-00:10 | 1.13 |
April | 0.168824E+10 | 1.13 | 651.33 | 01-APR-00:10 | 1.13 |
May | 0.174452E+10 | 1.13 | 651.33 | 01-MAY-00:10 | 1.13 |
June | 0.168824E+10 | 1.13 | 651.33 | 01-JUN-00:10 | 1.13 |
July | 0.174452E+10 | 1.13 | 651.33 | 01-JUL-00:05 | 1.13 |
August | 0.174452E+10 | 1.13 | 651.33 | 01-AUG-00:10 | 1.13 |
September | 0.168824E+10 | 1.13 | 651.33 | 01-SEP-00:05 | 1.13 |
October | 0.174452E+10 | 1.13 | 651.33 | 01-OCT-00:10 | 1.13 |
November | 0.168824E+10 | 1.13 | 651.33 | 01-NOV-00:10 | 1.13 |
December | 0.174452E+10 | 1.13 | 651.33 | 01-DEC-00:10 | 1.13 |
Annual Sum or Average | 0.205403E+11 | 1.13 | |||
Minimum of Months | 0.157569E+10 | 1.13 | 651.33 | 1.13 | |
Maximum of Months | 0.174452E+10 | 1.13 | 651.33 | 1.13 |
Report: PumpReportMonthly
For: HEATSYS1 PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 21536486.07 | 19382837.46 | 351.77 | 06-JAN-06:01 | 316.59 | 316.59 | 44.51 | 6.46 |
February | 24015484.06 | 21613935.65 | 1023.86 | 06-FEB-06:01 | 921.48 | 921.48 | 48.75 | 10.45 |
March | 11044336.80 | 9939903.12 | 440.97 | 20-MAR-05:01 | 396.87 | 396.87 | 46.33 | 7.17 |
April | 6635748.54 | 5972173.68 | 348.11 | 04-APR-05:01 | 313.30 | 313.30 | 43.55 | 6.43 |
May | 296464.34 | 266817.91 | 343.85 | 01-MAY-05:01 | 309.47 | 309.47 | 34.33 | 6.42 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 22.63 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 22.63 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 22.63 | 0.00 |
September | 165021.42 | 148519.27 | 85.52 | 22-SEP-05:02 | 76.96 | 76.96 | 31.85 | 3.22 |
October | 10164272.98 | 9147845.68 | 346.36 | 31-OCT-05:01 | 311.72 | 311.72 | 43.68 | 6.42 |
November | 14477871.91 | 13030084.72 | 369.88 | 01-NOV-05:01 | 332.89 | 332.89 | 45.89 | 6.61 |
December | 62924161.45 | 56631745.30 | 1047.30 | 26-DEC-06:02 | 942.57 | 942.57 | 45.74 | 10.56 |
Annual Sum or Average | 0.151260E+09 | 0.136134E+09 | ||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.63 | 0.00 | |
Maximum of Months | 62924161.45 | 56631745.30 | 1047.30 | 942.57 | 942.57 | 48.75 | 10.56 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP SECONDARY
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 29595836.21 | 26636252.59 | 861.33 | 20-JAN-14:50 | 775.19 | 775.19 | 8.98 | 24.18 |
February | 5962881.97 | 5366593.77 | 376.74 | 18-FEB-13:30 | 339.06 | 339.06 | 8.73 | 16.16 |
March | 0.104051E+09 | 93645836.49 | 2220.81 | 13-MAR-14:50 | 1998.73 | 1998.73 | 7.64 | 37.20 |
April | 39021118.47 | 35119006.62 | 559.79 | 20-APR-13:00 | 503.81 | 503.81 | 7.95 | 19.67 |
May | 0.291330E+09 | 0.262197E+09 | 4483.33 | 31-MAY-13:00 | 4034.99 | 4034.99 | 7.14 | 50.35 |
June | 0.194378E+10 | 0.174940E+10 | 15131.79 | 26-JUN-13:40 | 13618.61 | 13618.61 | 6.74 | 82.70 |
July | 0.174484E+10 | 0.157036E+10 | 15797.03 | 18-JUL-15:10 | 14217.32 | 14217.32 | 6.74 | 84.12 |
August | 0.207897E+10 | 0.187107E+10 | 18594.15 | 04-AUG-05:02 | 16734.73 | 16734.73 | 8.48 | 89.70 |
September | 0.100126E+10 | 0.901135E+09 | 13520.36 | 12-SEP-15:50 | 12168.32 | 12168.32 | 6.73 | 79.09 |
October | 0.174968E+09 | 0.157471E+09 | 2788.20 | 10-OCT-13:30 | 2509.38 | 2509.38 | 7.32 | 41.10 |
November | 56750999.32 | 51075899.39 | 1495.88 | 07-NOV-15:00 | 1346.29 | 1346.29 | 7.82 | 31.19 |
December | 18241058.82 | 16416952.94 | 661.55 | 01-DEC-14:00 | 595.40 | 595.40 | 8.76 | 21.32 |
Annual Sum or Average | 0.748877E+10 | 0.673990E+10 | ||||||
Minimum of Months | 5962881.97 | 5366593.77 | 376.74 | 339.06 | 339.06 | 6.73 | 16.16 | |
Maximum of Months | 0.207897E+10 | 0.187107E+10 | 18594.15 | 16734.73 | 16734.73 | 8.98 | 89.70 |
Report: PumpReportMonthly
For: COOLSYS1 PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.394532E+10 | 0.355079E+10 | 12797.85 | 01-JAN-14:53 | 11518.06 | 11518.06 | 8.43 | 89.70 |
February | 0.428236E+10 | 0.385412E+10 | 12797.85 | 01-FEB-05:01 | 11518.06 | 11518.06 | 8.43 | 89.70 |
March | 0.618483E+10 | 0.556635E+10 | 12797.85 | 01-MAR-05:01 | 11518.06 | 11518.06 | 8.43 | 89.70 |
April | 0.648195E+10 | 0.583375E+10 | 12797.85 | 03-APR-03:05 | 11518.06 | 11518.06 | 8.48 | 89.70 |
May | 0.124868E+11 | 0.112381E+11 | 12797.85 | 01-MAY-03:06 | 11518.06 | 11518.06 | 8.43 | 89.70 |
June | 0.245935E+11 | 0.221341E+11 | 12797.85 | 01-JUN-03:02 | 11518.06 | 11518.06 | 8.59 | 89.70 |
July | 0.270914E+11 | 0.243822E+11 | 12797.85 | 01-JUL-00:10 | 11518.06 | 11518.06 | 7.48 | 89.70 |
August | 0.289130E+11 | 0.260217E+11 | 12797.85 | 01-AUG-00:23 | 11518.06 | 11518.06 | 8.77 | 89.70 |
September | 0.190218E+11 | 0.171196E+11 | 12797.85 | 01-SEP-00:05 | 11518.06 | 11518.06 | 8.08 | 89.70 |
October | 0.766099E+10 | 0.689489E+10 | 12797.85 | 01-OCT-07:50 | 11518.06 | 11518.06 | 8.47 | 89.70 |
November | 0.489638E+10 | 0.440675E+10 | 12797.85 | 02-NOV-03:07 | 11518.06 | 11518.06 | 8.43 | 89.70 |
December | 0.389055E+10 | 0.350150E+10 | 12797.85 | 01-DEC-05:01 | 11518.06 | 11518.06 | 8.57 | 89.70 |
Annual Sum or Average | 0.149449E+12 | 0.134504E+12 | ||||||
Minimum of Months | 0.389055E+10 | 0.350150E+10 | 12797.85 | 11518.06 | 11518.06 | 7.48 | 89.70 | |
Maximum of Months | 0.289130E+11 | 0.260217E+11 | 12797.85 | 11518.06 | 11518.06 | 8.77 | 89.70 |
Report: PumpReportMonthly
For: PLANT CIRC PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.100031E+11 | 0.900275E+10 | 3734.71 | 01-JAN-00:05 | 3361.24 | 3361.24 | 22.04 | 15.60 |
February | 0.903502E+10 | 0.813151E+10 | 3734.71 | 01-FEB-00:10 | 3361.24 | 3361.24 | 24.66 | 15.60 |
March | 0.100031E+11 | 0.900275E+10 | 3734.71 | 01-MAR-00:10 | 3361.24 | 3361.24 | 27.57 | 15.60 |
April | 0.968037E+10 | 0.871234E+10 | 3734.71 | 01-APR-00:10 | 3361.24 | 3361.24 | 30.83 | 15.60 |
May | 0.100031E+11 | 0.900275E+10 | 3734.71 | 01-MAY-00:10 | 3361.24 | 3361.24 | 22.71 | 15.60 |
June | 0.968037E+10 | 0.871234E+10 | 3734.71 | 01-JUN-00:10 | 3361.24 | 3361.24 | 27.03 | 15.60 |
July | 0.100031E+11 | 0.900275E+10 | 3734.71 | 01-JUL-00:05 | 3361.24 | 3361.24 | 38.36 | 15.60 |
August | 0.100031E+11 | 0.900275E+10 | 3734.71 | 01-AUG-00:10 | 3361.24 | 3361.24 | 38.90 | 15.60 |
September | 0.968037E+10 | 0.871234E+10 | 3734.71 | 01-SEP-00:05 | 3361.24 | 3361.24 | 26.28 | 15.60 |
October | 0.100031E+11 | 0.900275E+10 | 3734.71 | 01-OCT-00:10 | 3361.24 | 3361.24 | 25.22 | 15.60 |
November | 0.968037E+10 | 0.871234E+10 | 3734.71 | 01-NOV-00:10 | 3361.24 | 3361.24 | 27.67 | 15.60 |
December | 0.100031E+11 | 0.900275E+10 | 3734.71 | 01-DEC-00:10 | 3361.24 | 3361.24 | 30.30 | 15.60 |
Annual Sum or Average | 0.117778E+12 | 0.106000E+12 | ||||||
Minimum of Months | 0.903502E+10 | 0.813151E+10 | 3734.71 | 3361.24 | 3361.24 | 22.04 | 15.60 | |
Maximum of Months | 0.100031E+11 | 0.900275E+10 | 3734.71 | 3361.24 | 3361.24 | 38.90 | 15.60 |
Report: PumpReportMonthly
For: SWHSYS1 PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 11967951.72 | 3590385.52 | 5.96 | 01-JAN-06:03 | 1.79 | 1.79 | 55.76 | 0.44 |
February | 10809762.85 | 3242928.85 | 5.96 | 01-FEB-06:01 | 1.79 | 1.79 | 56.38 | 0.44 |
March | 11967951.72 | 3590385.52 | 5.96 | 01-MAR-06:01 | 1.79 | 1.79 | 56.26 | 0.44 |
April | 11581888.76 | 3474566.63 | 5.96 | 01-APR-05:03 | 1.79 | 1.79 | 55.92 | 0.44 |
May | 11967951.72 | 3590385.52 | 5.96 | 01-MAY-05:01 | 1.79 | 1.79 | 56.83 | 0.44 |
June | 11581888.76 | 3474566.63 | 5.96 | 01-JUN-05:03 | 1.79 | 1.79 | 56.53 | 0.44 |
July | 11967951.72 | 3590385.52 | 5.96 | 01-JUL-05:02 | 1.79 | 1.79 | 56.71 | 0.44 |
August | 11967951.72 | 3590385.52 | 5.96 | 01-AUG-05:02 | 1.79 | 1.79 | 56.98 | 0.44 |
September | 11581888.76 | 3474566.63 | 5.96 | 01-SEP-05:02 | 1.79 | 1.79 | 56.09 | 0.44 |
October | 11967951.72 | 3590385.52 | 5.96 | 01-OCT-05:10 | 1.79 | 1.79 | 56.41 | 0.44 |
November | 11581888.76 | 3474566.63 | 5.96 | 01-NOV-05:01 | 1.79 | 1.79 | 56.02 | 0.44 |
December | 11967951.72 | 3590385.52 | 5.96 | 01-DEC-06:01 | 1.79 | 1.79 | 56.42 | 0.44 |
Annual Sum or Average | 0.140913E+09 | 42273893.99 | ||||||
Minimum of Months | 10809762.85 | 3242928.85 | 5.96 | 1.79 | 1.79 | 55.76 | 0.44 | |
Maximum of Months | 11967951.72 | 3590385.52 | 5.96 | 1.79 | 1.79 | 56.98 | 0.44 |
Report: PumpReportMonthly
For: TOWERWATERSYS PUMP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPUMP ELECTRICITY ENERGY [J] | PUMP FLUID HEAT GAIN ENERGY [J] | PUMP ELECTRICITY RATE {Maximum} [W] | PUMP ELECTRICITY RATE {TIMESTAMP} | PUMP SHAFT POWER {AT MAX/MIN} [W] | PUMP FLUID HEAT GAIN RATE {AT MAX/MIN} [W] | PUMP OUTLET TEMPERATURE {AT MAX/MIN} [C] | PUMP MASS FLOW RATE {AT MAX/MIN} [kg/s] | |
January | 0.491180E+10 | 0.442062E+10 | 31707.26 | 20-JAN-14:10 | 28536.53 | 28536.53 | 22.67 | 105.51 |
February | 0.529904E+10 | 0.476914E+10 | 15860.43 | 18-FEB-13:30 | 14274.39 | 14274.39 | 23.28 | 52.75 |
March | 0.785762E+10 | 0.707186E+10 | 31775.50 | 13-MAR-14:50 | 28597.95 | 28597.95 | 25.57 | 105.51 |
April | 0.808905E+10 | 0.728015E+10 | 31710.50 | 20-APR-12:50 | 28539.45 | 28539.45 | 22.81 | 105.51 |
May | 0.171199E+11 | 0.154079E+11 | 31783.14 | 31-MAY-12:20 | 28604.83 | 28604.83 | 25.86 | 105.51 |
June | 0.406303E+11 | 0.365672E+11 | 31789.40 | 23-JUN-15:00 | 28610.46 | 28610.46 | 26.09 | 105.51 |
July | 0.431979E+11 | 0.388781E+11 | 31789.28 | 10-JUL-10:20 | 28610.35 | 28610.35 | 26.09 | 105.51 |
August | 0.454085E+11 | 0.408677E+11 | 31789.39 | 14-AUG-10:40 | 28610.45 | 28610.45 | 26.09 | 105.51 |
September | 0.291938E+11 | 0.262744E+11 | 31789.29 | 06-SEP-15:10 | 28610.36 | 28610.36 | 26.09 | 105.51 |
October | 0.101354E+11 | 0.912183E+10 | 31775.94 | 10-OCT-12:50 | 28598.35 | 28598.35 | 25.59 | 105.51 |
November | 0.609475E+10 | 0.548527E+10 | 31713.03 | 06-NOV-13:20 | 28541.72 | 28541.72 | 22.92 | 105.51 |
December | 0.482495E+10 | 0.434245E+10 | 31707.13 | 01-DEC-14:00 | 28536.42 | 28536.42 | 22.66 | 105.51 |
Annual Sum or Average | 0.222763E+12 | 0.200487E+12 | ||||||
Minimum of Months | 0.482495E+10 | 0.434245E+10 | 15860.43 | 14274.39 | 14274.39 | 22.66 | 52.75 | |
Maximum of Months | 0.454085E+11 | 0.408677E+11 | 31789.40 | 28610.46 | 28610.46 | 26.09 | 105.51 |
Report: CondLoopDemandReportMonthly
For: HEATSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 38.55 | 38.55 | 85359.89 | 1223642.34 | 30-JAN-06:01 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 30.35 | 30.35 | 105902.10 | 1472100.42 | 13-FEB-06:02 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 25.09 | 25.09 | 58307.61 | 1275163.21 | 21-MAR-04:01 |
April | 0.00 | 0.00 | 01-APR-00:10 | 23.96 | 23.96 | 34353.95 | 1188559.86 | 04-APR-04:01 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 22.67 | 22.67 | 2144.19 | 1227356.24 | 01-MAY-05:01 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 22.63 | 22.63 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 22.63 | 22.63 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 22.63 | 22.63 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 22.63 | 22.63 | 1475.59 | 665467.67 | 22-SEP-05:02 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 24.58 | 24.58 | 40775.48 | 1187798.02 | 24-OCT-05:01 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 35.24 | 82.03 | 68130.56 | 1389521.94 | 27-NOV-05:01 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 29.98 | 29.98 | 145587.41 | 1660739.20 | 27-DEC-06:01 |
Annual Sum or Average | 0.00 | 44880.75 | ||||||
Minimum of Months | 0.00 | 0.00 | 22.63 | 22.63 | 0.00 | 0.00 | ||
Maximum of Months | 0.00 | 0.00 | 38.55 | 82.03 | 145587.41 | 1660739.20 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_SUPPLY
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 23655.12 | 1078505.91 | 20-JAN-14:00 | 10.43 | 8.97 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 11836.59 | 806810.17 | 18-FEB-13:30 | 9.85 | 8.77 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 56314.57 | 1154405.48 | 14-MAR-13:00 | 10.18 | 7.11 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 59044.71 | 1124452.25 | 20-APR-12:50 | 10.45 | 8.83 | 0.63 | 10863.93 | 09-APR-15:23 |
May | 198278.57 | 1275271.82 | 31-MAY-12:20 | 10.10 | 6.71 | 42.60 | 198737.37 | 21-MAY-13:53 |
June | 570104.78 | 1674456.29 | 26-JUN-15:10 | 11.16 | 6.70 | 40.49 | 105157.52 | 18-JUN-05:42 |
July | 568809.93 | 1572141.99 | 18-JUL-15:10 | 10.88 | 6.70 | 27.81 | 83815.03 | 09-JUL-05:23 |
August | 547887.40 | 1614763.88 | 16-AUG-15:10 | 11.00 | 6.70 | 1.38 | 14735.16 | 12-AUG-19:03 |
September | 408089.75 | 1563049.23 | 12-SEP-15:50 | 10.86 | 6.70 | 22.12 | 71236.22 | 05-SEP-00:12 |
October | 96894.36 | 1246628.10 | 10-OCT-13:30 | 10.35 | 7.03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 40289.92 | 1086059.66 | 06-NOV-14:20 | 10.40 | 8.93 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 23299.24 | 1079518.47 | 01-DEC-14:00 | 10.28 | 8.82 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 218155.11 | 11.29 | ||||||
Minimum of Months | 11836.59 | 806810.17 | 9.85 | 6.70 | 0.00 | 0.00 | ||
Maximum of Months | 570104.78 | 1674456.29 | 11.16 | 8.97 | 42.60 | 198737.37 |
Report: CondLoopDemandReportMonthly
For: COOLSYS1_DEMAND
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 15051.83 | 770042.58 | 20-JAN-14:10 | 14.39 | 8.92 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 5815.10 | 538793.57 | 18-FEB-13:30 | 14.66 | 8.73 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 42207.72 | 1181459.50 | 14-MAR-13:00 | 14.40 | 8.46 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 37014.68 | 848576.03 | 20-APR-13:00 | 17.01 | 8.53 | 0.00 | 0.00 | 01-APR-00:10 |
May | 148678.89 | 1282545.46 | 31-MAY-12:20 | 12.88 | 6.83 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 491409.09 | 2193842.11 | 14-JUN-05:02 | 15.90 | 7.86 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 482214.64 | 2249501.97 | 17-JUL-05:02 | 14.94 | 8.01 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 471969.04 | 2784227.94 | 04-AUG-05:02 | 14.12 | 8.33 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 333753.06 | 1581505.42 | 30-SEP-05:02 | 16.53 | 8.68 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 71034.49 | 1295331.57 | 10-OCT-13:30 | 14.23 | 7.03 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 27398.36 | 983950.92 | 07-NOV-15:00 | 14.24 | 8.53 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 13645.10 | 729037.97 | 01-DEC-14:00 | 14.87 | 8.76 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 179284.75 | 0.00 | ||||||
Minimum of Months | 5815.10 | 538793.57 | 12.88 | 6.83 | 0.00 | 0.00 | ||
Maximum of Months | 491409.09 | 2784227.94 | 17.01 | 8.92 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SINGLE WATER PLANT LOOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 208421.52 | 509292.67 | 20-JAN-14:00 | 27.67 | 23.44 | 0.00 | 0.00 | 01-JAN-00:05 |
February | 365493.99 | 689546.90 | 18-FEB-14:00 | 30.94 | 24.01 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 561378.32 | 1200754.67 | 14-MAR-13:00 | 40.11 | 29.95 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 747765.93 | 1340781.37 | 19-APR-14:00 | 42.59 | 29.63 | 0.00 | 0.00 | 01-APR-00:10 |
May | 313314.02 | 980754.41 | 17-MAY-14:00 | 36.18 | 31.64 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 853788.61 | 1871838.21 | 26-JUN-15:10 | 51.90 | 44.01 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 1140395.80 | 1984870.54 | 16-JUL-13:00 | 53.86 | 43.31 | 0.00 | 0.00 | 01-JUL-00:05 |
August | 1348334.53 | 2249949.28 | 16-AUG-16:00 | 58.44 | 45.06 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 468117.70 | 1185291.90 | 10-SEP-13:40 | 39.83 | 35.33 | 0.00 | 0.00 | 01-SEP-00:05 |
October | 419529.57 | 1129354.83 | 11-OCT-14:00 | 38.84 | 31.37 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 549166.55 | 1097624.03 | 07-NOV-15:00 | 38.27 | 28.00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 700405.72 | 1314546.68 | 02-DEC-15:00 | 42.12 | 29.45 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 641764.82 | 0.00 | ||||||
Minimum of Months | 208421.52 | 509292.67 | 27.67 | 23.44 | 0.00 | 0.00 | ||
Maximum of Months | 1348334.53 | 2249949.28 | 58.44 | 45.06 | 0.00 | 0.00 |
Report: CondLoopDemandReportMonthly
For: SWHSYS1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 57.39 | 57.39 | 16408.62 | 55406.87 | 31-JAN-12:30 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 56.73 | 56.73 | 16683.68 | 55579.41 | 09-FEB-12:10 |
March | 0.00 | 0.00 | 01-MAR-00:10 | 56.60 | 56.60 | 17397.18 | 55340.28 | 01-MAR-13:00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 56.71 | 56.71 | 15808.28 | 53647.26 | 03-APR-11:50 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 57.43 | 57.43 | 15467.35 | 51247.38 | 01-MAY-11:30 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 57.10 | 57.10 | 14952.58 | 48242.39 | 01-JUN-11:30 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 57.17 | 57.17 | 13310.01 | 45617.74 | 03-JUL-11:50 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 57.41 | 57.41 | 14225.67 | 44370.04 | 31-AUG-11:30 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 56.57 | 56.57 | 13661.76 | 45799.07 | 29-SEP-11:30 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 57.35 | 57.35 | 14243.72 | 48489.60 | 31-OCT-11:20 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 56.42 | 56.42 | 15229.44 | 51404.46 | 30-NOV-12:30 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 56.88 | 56.88 | 15485.94 | 53828.33 | 29-DEC-13:00 |
Annual Sum or Average | 0.00 | 15231.23 | ||||||
Minimum of Months | 0.00 | 0.00 | 56.42 | 56.42 | 13310.01 | 44370.04 | ||
Maximum of Months | 0.00 | 0.00 | 57.43 | 57.43 | 17397.18 | 55579.41 |
Report: CondLoopDemandReportMonthly
For: TOWERWATERSYS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportPLANT SUPPLY SIDE COOLING DEMAND RATE [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE COOLING DEMAND RATE {TIMESTAMP} | PLANT SUPPLY SIDE INLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE OUTLET TEMPERATURE {AT MAX/MIN} [C] | PLANT SUPPLY SIDE HEATING DEMAND RATE [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {Maximum} [W] | PLANT SUPPLY SIDE HEATING DEMAND RATE {TIMESTAMP} | |
January | 12682.06 | 692285.05 | 20-JAN-14:10 | 22.67 | 21.85 | 1886.58 | 132660.19 | 13-JAN-06:50 |
February | 4362.12 | 480100.83 | 18-FEB-13:30 | 23.28 | 21.10 | 2806.71 | 132626.84 | 10-FEB-14:10 |
March | 39420.84 | 1971341.17 | 13-MAR-14:50 | 25.57 | 21.10 | 2068.22 | 132040.38 | 29-MAR-12:40 |
April | 35208.95 | 800283.44 | 19-APR-13:30 | 24.73 | 21.10 | 2525.65 | 132399.87 | 10-APR-05:50 |
May | 161520.65 | 2097788.50 | 31-MAY-12:20 | 25.86 | 21.10 | 1496.27 | 113199.09 | 02-MAY-13:10 |
June | 613500.20 | 2201466.24 | 23-JUN-15:00 | 26.09 | 21.10 | 901.98 | 85208.60 | 09-JUN-06:20 |
July | 593126.94 | 2199387.00 | 10-JUL-10:20 | 26.09 | 21.10 | 839.17 | 77462.87 | 01-JUL-22:10 |
August | 586249.47 | 2201298.76 | 14-AUG-10:40 | 26.09 | 21.10 | 1788.24 | 80691.57 | 18-AUG-01:40 |
September | 413681.27 | 2199639.27 | 06-SEP-15:10 | 26.09 | 21.10 | 866.15 | 110298.30 | 22-SEP-11:20 |
October | 72425.49 | 1978606.79 | 10-OCT-12:50 | 25.59 | 21.10 | 1855.33 | 115952.23 | 23-OCT-05:50 |
November | 23603.92 | 856947.33 | 07-NOV-15:00 | 24.99 | 21.10 | 2146.70 | 126670.88 | 02-NOV-12:30 |
December | 12177.35 | 689873.50 | 01-DEC-14:00 | 22.66 | 21.85 | 2001.78 | 132608.53 | 08-DEC-12:30 |
Annual Sum or Average | 215089.47 | 1758.37 | ||||||
Minimum of Months | 4362.12 | 480100.83 | 22.66 | 21.10 | 839.17 | 77462.87 | ||
Maximum of Months | 613500.20 | 2201466.24 | 26.09 | 21.85 | 2806.71 | 132660.19 |
Report: ZoneTemperatureOscillationReportMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: GROUNDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: MIDFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: TOPFLOOR_PLENUM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.935724E+10 | 0.00 | 0.283962E+10 | 0.542246E+10 | 0.00 | 0.00 |
February | 0.938625E+10 | 0.00 | 0.944835E+09 | 0.526724E+10 | 0.00 | 0.00 |
March | 0.407851E+10 | 0.00 | 0.890292E+10 | 0.811060E+10 | 0.00 | 0.00 |
April | 0.171742E+10 | 0.00 | 0.978636E+10 | 0.904790E+10 | 0.00 | 0.00 |
May | 56913449.22 | 0.00 | 0.313647E+11 | 0.920849E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.104988E+12 | 0.152946E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.112260E+12 | 0.156829E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.120327E+12 | 0.196653E+11 | 0.00 | 0.00 |
September | 0.148061E+09 | 0.00 | 0.688340E+11 | 0.111300E+11 | 0.00 | 0.00 |
October | 0.376802E+10 | 0.00 | 0.143030E+11 | 0.778178E+10 | 0.00 | 0.00 |
November | 0.552603E+10 | 0.00 | 0.570420E+10 | 0.707163E+10 | 0.00 | 0.00 |
December | 0.153589E+11 | 0.00 | 0.333768E+10 | 0.658624E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.493974E+11 | 0.00 | 0.483592E+12 | 0.120269E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.944835E+09 | 0.526724E+10 | 0.00 | 0.00 |
Maximum of Months | 0.153589E+11 | 0.00 | 0.120327E+12 | 0.196653E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.182509E+12 | 0.00 | 0.233997E+11 | 0.388986E+11 | 0.00 | 0.00 |
February | 0.208743E+12 | 0.00 | 0.897062E+10 | 0.367751E+11 | 0.00 | 0.00 |
March | 0.126578E+12 | 0.00 | 0.674521E+11 | 0.496074E+11 | 0.00 | 0.00 |
April | 0.696057E+11 | 0.00 | 0.571348E+11 | 0.426741E+11 | 0.00 | 0.00 |
May | 0.393440E+10 | 0.00 | 0.263572E+12 | 0.683396E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.898283E+12 | 0.120986E+12 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.905863E+12 | 0.113388E+12 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.870009E+12 | 0.116761E+12 | 0.00 | 0.00 |
September | 0.285458E+10 | 0.00 | 0.595871E+12 | 0.860551E+11 | 0.00 | 0.00 |
October | 0.864522E+11 | 0.00 | 0.117840E+12 | 0.505251E+11 | 0.00 | 0.00 |
November | 0.143280E+12 | 0.00 | 0.409706E+11 | 0.407137E+11 | 0.00 | 0.00 |
December | 0.318852E+12 | 0.00 | 0.218743E+11 | 0.390285E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.114281E+13 | 0.00 | 0.387124E+13 | 0.803753E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.897062E+10 | 0.367751E+11 | 0.00 | 0.00 |
Maximum of Months | 0.318852E+12 | 0.00 | 0.905863E+12 | 0.120986E+12 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.379812E+11 | 0.00 | 0.174577E+10 | 0.419994E+10 | 0.00 | 0.00 |
February | 0.394236E+11 | 0.00 | 0.630822E+09 | 0.382108E+10 | 0.00 | 0.00 |
March | 0.263199E+11 | 0.00 | 0.620200E+10 | 0.481006E+10 | 0.00 | 0.00 |
April | 0.181875E+11 | 0.00 | 0.588128E+10 | 0.441905E+10 | 0.00 | 0.00 |
May | 0.177940E+10 | 0.00 | 0.272054E+11 | 0.600202E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.101902E+12 | 0.129095E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.100797E+12 | 0.117518E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.967176E+11 | 0.119716E+11 | 0.00 | 0.00 |
September | 0.828940E+09 | 0.00 | 0.623306E+11 | 0.803162E+10 | 0.00 | 0.00 |
October | 0.194817E+11 | 0.00 | 0.105823E+11 | 0.443986E+10 | 0.00 | 0.00 |
November | 0.287306E+11 | 0.00 | 0.331335E+10 | 0.374788E+10 | 0.00 | 0.00 |
December | 0.577784E+11 | 0.00 | 0.168163E+10 | 0.432688E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.230511E+12 | 0.00 | 0.418990E+12 | 0.804312E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.630822E+09 | 0.374788E+10 | 0.00 | 0.00 |
Maximum of Months | 0.577784E+11 | 0.00 | 0.101902E+12 | 0.129095E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.101590E+10 | 0.165652E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 81446874.48 | 0.146440E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.344417E+10 | 0.173041E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.397344E+10 | 0.160860E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.180353E+11 | 0.169972E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.577863E+11 | 0.171977E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.586508E+11 | 0.169264E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.629855E+11 | 0.190488E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.423431E+11 | 0.177138E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.721101E+10 | 0.176085E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.266115E+10 | 0.163756E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.143717E+10 | 0.162014E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.259625E+12 | 0.202669E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 81446874.48 | 0.146440E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.629855E+11 | 0.190488E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.496195E+12 | 0.273211E+12 | 0.00 | 21.18 |
February | 0.00 | 0.00 | 0.759260E+12 | 0.339082E+12 | 0.00 | 32.37 |
March | 0.00 | 0.00 | 0.118759E+13 | 0.474152E+12 | 0.00 | 49.01 |
April | 0.00 | 0.00 | 0.148655E+13 | 0.563096E+12 | 0.00 | 65.92 |
May | 0.00 | 0.00 | 0.511620E+12 | 0.277916E+12 | 0.00 | 20.16 |
June | 0.00 | 0.00 | 0.850132E+12 | 0.380427E+12 | 0.00 | 24.21 |
July | 0.00 | 0.00 | 0.123201E+13 | 0.500200E+12 | 0.00 | 31.65 |
August | 0.00 | 0.00 | 0.159060E+13 | 0.639535E+12 | 0.00 | 61.06 |
September | 0.00 | 0.00 | 0.508023E+12 | 0.275656E+12 | 0.00 | 18.15 |
October | 0.00 | 0.00 | 0.855775E+12 | 0.380426E+12 | 0.00 | 35.46 |
November | 0.00 | 0.00 | 0.115455E+13 | 0.459970E+12 | 0.00 | 48.09 |
December | 0.00 | 0.00 | 0.153456E+13 | 0.582398E+12 | 0.00 | 70.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.121669E+14 | 0.514607E+13 | 0.00 | 477.46 |
Minimum of Months | 0.00 | 0.00 | 0.496195E+12 | 0.273211E+12 | 0.00 | 18.15 |
Maximum of Months | 0.00 | 0.00 | 0.159060E+13 | 0.639535E+12 | 0.00 | 70.19 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.584574E+10 | 0.305287E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.110832E+11 | 0.390817E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.193081E+11 | 0.570001E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.251280E+11 | 0.667771E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.761501E+10 | 0.345776E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.149070E+11 | 0.539383E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.221709E+11 | 0.730661E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.291629E+11 | 0.892593E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.792966E+10 | 0.359608E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.133887E+11 | 0.457900E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.186167E+11 | 0.542899E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.251806E+11 | 0.677578E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.200336E+12 | 0.648027E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.584574E+10 | 0.305287E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.291629E+11 | 0.892593E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.343257E+11 | 0.247493E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.843901E+11 | 0.331699E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.165423E+12 | 0.510128E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.220543E+12 | 0.604423E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.654069E+11 | 0.315726E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140408E+12 | 0.511347E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.210373E+12 | 0.695264E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272143E+12 | 0.840019E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.704654E+11 | 0.332606E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.113373E+12 | 0.409840E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.158105E+12 | 0.483266E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.208524E+12 | 0.590578E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.174348E+13 | 0.587239E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.343257E+11 | 0.247493E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272143E+12 | 0.840019E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.157695E+10 | 0.210323E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.648240E+10 | 0.295642E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.148967E+11 | 0.483337E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.204013E+11 | 0.579445E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.590585E+10 | 0.306583E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.140951E+11 | 0.517260E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.211171E+11 | 0.702236E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.272499E+11 | 0.846577E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.672132E+10 | 0.329885E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.967942E+10 | 0.381200E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.137198E+11 | 0.448499E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.185607E+11 | 0.552812E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.160407E+12 | 0.565380E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.157695E+10 | 0.210323E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.272499E+11 | 0.846577E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.542246E+10 | 0.283962E+10 | 0.935724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526724E+10 | 0.944835E+09 | 0.938625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.811060E+10 | 0.890292E+10 | 0.407851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.904790E+10 | 0.978636E+10 | 0.171742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.920849E+10 | 0.313647E+11 | 56913449.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152946E+11 | 0.104988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156829E+11 | 0.112260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196653E+11 | 0.120327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111300E+11 | 0.688340E+11 | 0.148061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.778178E+10 | 0.143030E+11 | 0.376802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.707163E+10 | 0.570420E+10 | 0.552603E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658624E+10 | 0.333768E+10 | 0.153589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120269E+12 | 0.483592E+12 | 0.493974E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.526724E+10 | 0.944835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196653E+11 | 0.120327E+12 | 0.153589E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.388986E+11 | 0.233997E+11 | 0.182509E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367751E+11 | 0.897062E+10 | 0.208743E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496074E+11 | 0.674521E+11 | 0.126578E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426741E+11 | 0.571348E+11 | 0.696057E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.683396E+11 | 0.263572E+12 | 0.393440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120986E+12 | 0.898283E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113388E+12 | 0.905863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116761E+12 | 0.870009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.860551E+11 | 0.595871E+12 | 0.285458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.505251E+11 | 0.117840E+12 | 0.864522E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407137E+11 | 0.409706E+11 | 0.143280E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390285E+11 | 0.218743E+11 | 0.318852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.803753E+12 | 0.387124E+13 | 0.114281E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367751E+11 | 0.897062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120986E+12 | 0.905863E+12 | 0.318852E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.419994E+10 | 0.174577E+10 | 0.379812E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382108E+10 | 0.630822E+09 | 0.394236E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481006E+10 | 0.620200E+10 | 0.263199E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441905E+10 | 0.588128E+10 | 0.181875E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.600202E+10 | 0.272054E+11 | 0.177940E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129095E+11 | 0.101902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117518E+11 | 0.100797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119716E+11 | 0.967176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.803162E+10 | 0.623306E+11 | 0.828940E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.443986E+10 | 0.105823E+11 | 0.194817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.374788E+10 | 0.331335E+10 | 0.287306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432688E+10 | 0.168163E+10 | 0.577784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.804312E+11 | 0.418990E+12 | 0.230511E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374788E+10 | 0.630822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129095E+11 | 0.101902E+12 | 0.577784E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165652E+11 | 0.101590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146440E+11 | 81446874.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173041E+11 | 0.344417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160860E+11 | 0.397344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169972E+11 | 0.180353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171977E+11 | 0.577863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169264E+11 | 0.586508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190488E+11 | 0.629855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177138E+11 | 0.423431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176085E+11 | 0.721101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163756E+11 | 0.266115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162014E+11 | 0.143717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202669E+12 | 0.259625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146440E+11 | 81446874.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190488E+11 | 0.629855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.115586E+12 | 0.395501E+12 | 0.00 | 0.00 | 0.00 | 0.566762E+11 | 0.00 | 0.00 |
February | 0.104400E+12 | 0.611597E+12 | 0.00 | 0.00 | 0.00 | 0.866284E+11 | 0.00 | 0.00 |
March | 0.115586E+12 | 0.960785E+12 | 0.00 | 0.00 | 0.00 | 0.131168E+12 | 0.00 | 0.00 |
April | 0.111857E+12 | 0.121253E+13 | 0.00 | 0.00 | 0.00 | 0.176419E+12 | 0.00 | 0.00 |
May | 0.115586E+12 | 0.403487E+12 | 0.00 | 0.00 | 0.00 | 0.539541E+11 | 0.00 | 0.00 |
June | 0.111857E+12 | 0.646633E+12 | 0.00 | 0.00 | 0.00 | 0.647787E+11 | 0.00 | 0.00 |
July | 0.115586E+12 | 0.932490E+12 | 0.00 | 0.00 | 0.00 | 0.847086E+11 | 0.00 | 0.00 |
August | 0.115586E+12 | 0.123079E+13 | 0.00 | 0.00 | 0.00 | 0.163396E+12 | 0.00 | 0.00 |
September | 0.111857E+12 | 0.393007E+12 | 0.00 | 0.00 | 0.00 | 0.485641E+11 | 0.00 | 0.00 |
October | 0.115586E+12 | 0.686245E+12 | 0.00 | 0.00 | 0.00 | 0.948831E+11 | 0.00 | 0.00 |
November | 0.111857E+12 | 0.935721E+12 | 0.00 | 0.00 | 0.00 | 0.128706E+12 | 0.00 | 0.00 |
December | 0.115586E+12 | 0.125644E+13 | 0.00 | 0.00 | 0.00 | 0.187847E+12 | 0.00 | 0.00 |
Annual Sum or Average | 0.136093E+13 | 0.966522E+13 | 0.00 | 0.00 | 0.00 | 0.127773E+13 | 0.00 | 0.00 |
Minimum of Months | 0.104400E+12 | 0.393007E+12 | 0.00 | 0.00 | 0.00 | 0.485641E+11 | 0.00 | 0.00 |
Maximum of Months | 0.115586E+12 | 0.125644E+13 | 0.00 | 0.00 | 0.00 | 0.187847E+12 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.178697E+10 | 0.457984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161404E+10 | 0.878910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178697E+10 | 0.153951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172933E+10 | 0.201796E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178697E+10 | 0.594423E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172933E+10 | 0.112425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178697E+10 | 0.166513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178697E+10 | 0.220239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172933E+10 | 0.606291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178697E+10 | 0.105966E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172933E+10 | 0.149170E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178697E+10 | 0.201918E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210401E+11 | 0.156574E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161404E+10 | 0.457984E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178697E+10 | 0.220239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170931E+11 | 0.266695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154389E+11 | 0.666591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170931E+11 | 0.131503E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165417E+11 | 0.176643E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170931E+11 | 0.509274E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165417E+11 | 0.105815E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170931E+11 | 0.157940E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170931E+11 | 0.205234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165417E+11 | 0.537465E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170931E+11 | 0.894818E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165417E+11 | 0.126320E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170931E+11 | 0.166559E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201257E+12 | 0.135750E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154389E+11 | 0.266695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170931E+11 | 0.205234E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.174452E+10 | 0.121823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157569E+10 | 0.510167E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174452E+10 | 0.118079E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168824E+10 | 0.162951E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174452E+10 | 0.458453E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168824E+10 | 0.106108E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174452E+10 | 0.158393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174452E+10 | 0.205286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168824E+10 | 0.511072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174452E+10 | 0.761194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168824E+10 | 0.109230E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174452E+10 | 0.147771E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205403E+11 | 0.124409E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157569E+10 | 0.121823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174452E+10 | 0.205286E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_BOT WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.542246E+10 | 0.935724E+10 | 0.283962E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.526724E+10 | 0.938625E+10 | 0.944835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.811060E+10 | 0.407851E+10 | 0.890292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.904790E+10 | 0.171742E+10 | 0.978636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.920849E+10 | 56913449.22 | 0.313647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.152946E+11 | 0.00 | 0.104988E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156829E+11 | 0.00 | 0.112260E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.196653E+11 | 0.00 | 0.120327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.111300E+11 | 0.148061E+09 | 0.688340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.778178E+10 | 0.376802E+10 | 0.143030E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.707163E+10 | 0.552603E+10 | 0.570420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.658624E+10 | 0.153589E+11 | 0.333768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.120269E+12 | 0.493974E+11 | 0.483592E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.526724E+10 | 0.00 | 0.944835E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.196653E+11 | 0.153589E+11 | 0.120327E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_MID WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.388986E+11 | 0.182509E+12 | 0.233997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.367751E+11 | 0.208743E+12 | 0.897062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.496074E+11 | 0.126578E+12 | 0.674521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.426741E+11 | 0.696057E+11 | 0.571348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.683396E+11 | 0.393440E+10 | 0.263572E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.120986E+12 | 0.00 | 0.898283E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.113388E+12 | 0.00 | 0.905863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.116761E+12 | 0.00 | 0.870009E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.860551E+11 | 0.285458E+10 | 0.595871E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.505251E+11 | 0.864522E+11 | 0.117840E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.407137E+11 | 0.143280E+12 | 0.409706E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.390285E+11 | 0.318852E+12 | 0.218743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.803753E+12 | 0.114281E+13 | 0.387124E+13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.367751E+11 | 0.00 | 0.897062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.120986E+12 | 0.318852E+12 | 0.905863E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: VAV_TOP WITH REHEAT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.419994E+10 | 0.379812E+11 | 0.174577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.382108E+10 | 0.394236E+11 | 0.630822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.481006E+10 | 0.263199E+11 | 0.620200E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.441905E+10 | 0.181875E+11 | 0.588128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.600202E+10 | 0.177940E+10 | 0.272054E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.129095E+11 | 0.00 | 0.101902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.117518E+11 | 0.00 | 0.100797E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.119716E+11 | 0.00 | 0.967176E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.803162E+10 | 0.828940E+09 | 0.623306E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.443986E+10 | 0.194817E+11 | 0.105823E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.374788E+10 | 0.287306E+11 | 0.331335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.432688E+10 | 0.577784E+11 | 0.168163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.804312E+11 | 0.230511E+12 | 0.418990E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.374788E+10 | 0.00 | 0.630822E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.129095E+11 | 0.577784E+11 | 0.101902E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: CAV_BAS
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165652E+11 | 0.00 | 0.101590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.146440E+11 | 0.00 | 81446874.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173041E+11 | 0.00 | 0.344417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.160860E+11 | 0.00 | 0.397344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.169972E+11 | 0.00 | 0.180353E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.171977E+11 | 0.00 | 0.577863E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169264E+11 | 0.00 | 0.586508E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.190488E+11 | 0.00 | 0.629855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177138E+11 | 0.00 | 0.423431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176085E+11 | 0.00 | 0.721101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163756E+11 | 0.00 | 0.266115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162014E+11 | 0.00 | 0.143717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.202669E+12 | 0.00 | 0.259625E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.146440E+11 | 0.00 | 81446874.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.190488E+11 | 0.00 | 0.629855E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.115586E+12 | 0.00 | 0.496195E+12 | 0.00 | 0.100694E+12 | 0.00 | 0.00 | 0.00 | 0.569313E+11 | 0.00 | 0.00 | 0.00 |
February | 0.104400E+12 | 0.00 | 0.759260E+12 | 0.00 | 0.147663E+12 | 0.00 | 0.00 | 0.00 | 0.870184E+11 | 0.00 | 0.00 | 0.00 |
March | 0.115586E+12 | 0.00 | 0.118759E+13 | 0.00 | 0.226807E+12 | 0.00 | 0.00 | 0.00 | 0.131759E+12 | 0.00 | 0.00 | 0.00 |
April | 0.111857E+12 | 0.00 | 0.148655E+13 | 0.00 | 0.274025E+12 | 0.00 | 0.00 | 0.00 | 0.177213E+12 | 0.00 | 0.00 | 0.00 |
May | 0.115586E+12 | 0.00 | 0.511620E+12 | 0.00 | 0.108133E+12 | 0.00 | 0.00 | 0.00 | 0.541970E+11 | 0.00 | 0.00 | 0.00 |
June | 0.111857E+12 | 0.00 | 0.850132E+12 | 0.00 | 0.203499E+12 | 0.00 | 0.00 | 0.00 | 0.650703E+11 | 0.00 | 0.00 | 0.00 |
July | 0.115586E+12 | 0.00 | 0.123201E+13 | 0.00 | 0.299525E+12 | 0.00 | 0.00 | 0.00 | 0.850899E+11 | 0.00 | 0.00 | 0.00 |
August | 0.115586E+12 | 0.00 | 0.159060E+13 | 0.00 | 0.359817E+12 | 0.00 | 0.00 | 0.00 | 0.164131E+12 | 0.00 | 0.00 | 0.00 |
September | 0.111857E+12 | 0.00 | 0.508023E+12 | 0.00 | 0.115016E+12 | 0.00 | 0.00 | 0.00 | 0.487827E+11 | 0.00 | 0.00 | 0.00 |
October | 0.115586E+12 | 0.00 | 0.855775E+12 | 0.00 | 0.169530E+12 | 0.00 | 0.00 | 0.00 | 0.953102E+11 | 0.00 | 0.00 | 0.00 |
November | 0.111857E+12 | 0.00 | 0.115455E+13 | 0.00 | 0.218827E+12 | 0.00 | 0.00 | 0.00 | 0.129286E+12 | 0.00 | 0.00 | 0.00 |
December | 0.115586E+12 | 0.00 | 0.153456E+13 | 0.00 | 0.278120E+12 | 0.00 | 0.00 | 0.00 | 0.188692E+12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.136093E+13 | 0.00 | 0.121669E+14 | 0.00 | 0.250166E+13 | 0.00 | 0.00 | 0.00 | 0.128348E+13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.104400E+12 | 0.00 | 0.496195E+12 | 0.00 | 0.100694E+12 | 0.00 | 0.00 | 0.00 | 0.487827E+11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.115586E+12 | 0.00 | 0.159060E+13 | 0.00 | 0.359817E+12 | 0.00 | 0.00 | 0.00 | 0.188692E+12 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER BOT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.178697E+10 | 0.00 | 0.584574E+10 | 0.00 | 0.126590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161404E+10 | 0.00 | 0.110832E+11 | 0.00 | 0.229413E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.178697E+10 | 0.00 | 0.193081E+11 | 0.00 | 0.391304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172933E+10 | 0.00 | 0.251280E+11 | 0.00 | 0.494838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178697E+10 | 0.00 | 0.761501E+10 | 0.00 | 0.167079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172933E+10 | 0.00 | 0.149070E+11 | 0.00 | 0.366450E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.178697E+10 | 0.00 | 0.221709E+11 | 0.00 | 0.551964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.178697E+10 | 0.00 | 0.291629E+11 | 0.00 | 0.713896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172933E+10 | 0.00 | 0.792966E+10 | 0.00 | 0.186675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.178697E+10 | 0.00 | 0.133887E+11 | 0.00 | 0.279203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172933E+10 | 0.00 | 0.186167E+11 | 0.00 | 0.369966E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.178697E+10 | 0.00 | 0.251806E+11 | 0.00 | 0.498881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210401E+11 | 0.00 | 0.200336E+12 | 0.00 | 0.437626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.161404E+10 | 0.00 | 0.584574E+10 | 0.00 | 0.126590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.178697E+10 | 0.00 | 0.291629E+11 | 0.00 | 0.713896E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170931E+11 | 0.00 | 0.343257E+11 | 0.00 | 0.765616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154389E+11 | 0.00 | 0.843901E+11 | 0.00 | 0.177310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.170931E+11 | 0.00 | 0.165423E+12 | 0.00 | 0.339197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165417E+11 | 0.00 | 0.220543E+12 | 0.00 | 0.439006E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170931E+11 | 0.00 | 0.654069E+11 | 0.00 | 0.144795E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.165417E+11 | 0.00 | 0.140408E+12 | 0.00 | 0.345930E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.170931E+11 | 0.00 | 0.210373E+12 | 0.00 | 0.524333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.170931E+11 | 0.00 | 0.272143E+12 | 0.00 | 0.669088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165417E+11 | 0.00 | 0.704654E+11 | 0.00 | 0.167189E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170931E+11 | 0.00 | 0.113373E+12 | 0.00 | 0.238909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165417E+11 | 0.00 | 0.158105E+12 | 0.00 | 0.317849E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.170931E+11 | 0.00 | 0.208524E+12 | 0.00 | 0.419647E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201257E+12 | 0.00 | 0.174348E+13 | 0.00 | 0.385981E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154389E+11 | 0.00 | 0.343257E+11 | 0.00 | 0.765616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.170931E+11 | 0.00 | 0.272143E+12 | 0.00 | 0.669088E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: AIRLOOP DATACENTER TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.174452E+10 | 0.00 | 0.157695E+10 | 0.00 | 0.358718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157569E+10 | 0.00 | 0.648240E+10 | 0.00 | 0.138073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174452E+10 | 0.00 | 0.148967E+11 | 0.00 | 0.308885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.168824E+10 | 0.00 | 0.204013E+11 | 0.00 | 0.410621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.174452E+10 | 0.00 | 0.590585E+10 | 0.00 | 0.132131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168824E+10 | 0.00 | 0.140951E+11 | 0.00 | 0.348436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174452E+10 | 0.00 | 0.211171E+11 | 0.00 | 0.527784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174452E+10 | 0.00 | 0.272499E+11 | 0.00 | 0.672126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.168824E+10 | 0.00 | 0.672132E+10 | 0.00 | 0.161061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.174452E+10 | 0.00 | 0.967942E+10 | 0.00 | 0.206748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.168824E+10 | 0.00 | 0.137198E+11 | 0.00 | 0.279675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174452E+10 | 0.00 | 0.185607E+11 | 0.00 | 0.378360E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.205403E+11 | 0.00 | 0.160407E+12 | 0.00 | 0.359977E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.157569E+10 | 0.00 | 0.157695E+10 | 0.00 | 0.358718E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174452E+10 | 0.00 | 0.272499E+11 | 0.00 | 0.672126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: BASEMENT
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.128111E+10 | 0.00 | 0.00 | 0.104614E+09 | 0.00 | 0.00 | 0.665880E+11 | 0.00 | 0.71 |
February | 0.473036E+09 | 0.00 | 0.00 | 97121481.16 | 0.00 | 0.00 | 0.601160E+11 | 0.00 | 0.63 |
March | 0.393252E+09 | 0.00 | 0.00 | 0.112829E+09 | 0.00 | 0.00 | 0.704635E+11 | 0.00 | 0.96 |
April | 0.428028E+09 | 0.00 | 0.00 | 0.107235E+09 | 0.00 | 0.00 | 0.666152E+11 | 0.00 | 1.04 |
May | 0.127111E+09 | 13621221.16 | 0.00 | 0.103835E+09 | 273229.39 | 0.00 | 0.570951E+11 | 0.00 | 1.32 |
June | 65538343.28 | 0.166594E+10 | 0.00 | 79255807.42 | 21775724.06 | 0.00 | 0.235134E+11 | 0.00 | 1.09 |
July | 84011046.80 | 0.160868E+10 | 0.00 | 85696969.49 | 61993160.32 | 0.00 | 0.213803E+11 | 0.00 | 1.03 |
August | 0.125404E+09 | 0.164427E+10 | 0.00 | 0.115241E+09 | 23416850.10 | 0.00 | 0.301572E+11 | 0.00 | 1.22 |
September | 0.182837E+09 | 0.323812E+09 | 0.00 | 0.112318E+09 | 20650352.91 | 0.00 | 0.387172E+11 | 0.00 | 1.33 |
October | 0.333765E+09 | 0.00 | 0.00 | 0.127782E+09 | 0.00 | 0.00 | 0.724486E+11 | 0.00 | 1.08 |
November | 0.358892E+09 | 0.00 | 0.00 | 0.128400E+09 | 0.00 | 0.00 | 0.727362E+11 | 0.00 | 0.86 |
December | 0.469650E+10 | 0.00 | 0.00 | 0.114000E+09 | 0.00 | 0.00 | 0.675829E+11 | 0.00 | 0.71 |
Annual Sum or Average | 0.854949E+10 | 0.525632E+10 | 0.00 | 0.128833E+10 | 0.128109E+09 | 0.00 | 0.647414E+12 | 0.00 | 1.00 |
Minimum of Months | 65538343.28 | 0.00 | 0.00 | 79255807.42 | 0.00 | 0.00 | 0.213803E+11 | 0.00 | 0.63 |
Maximum of Months | 0.469650E+10 | 0.166594E+10 | 0.00 | 0.128400E+09 | 61993160.32 | 0.00 | 0.727362E+11 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_BOTTOM
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.403015E+10 | 0.00 | 0.00 | 70721836.57 | 0.00 | 0.00 | 0.453192E+11 | 0.00 | 0.49 |
February | 0.396944E+10 | 0.00 | 0.00 | 67988862.66 | 0.00 | 0.00 | 0.424781E+11 | 0.00 | 0.47 |
March | 0.296848E+10 | 0.00 | 0.00 | 93511131.96 | 0.00 | 0.00 | 0.540436E+11 | 0.00 | 0.73 |
April | 0.286743E+10 | 0.00 | 0.00 | 91232376.57 | 0.00 | 0.00 | 0.529101E+11 | 0.00 | 0.82 |
May | 0.263822E+10 | 7897553.79 | 0.00 | 86147818.72 | 812878.45 | 0.00 | 0.424494E+11 | 0.00 | 0.94 |
June | 0.518951E+10 | 0.741289E+09 | 0.00 | 70272670.58 | 63777569.78 | 0.00 | 0.161778E+11 | 0.00 | 0.86 |
July | 0.609338E+10 | 0.762663E+09 | 0.00 | 69913847.00 | 0.187100E+09 | 0.00 | 0.135752E+11 | 0.00 | 0.88 |
August | 0.978747E+10 | 0.762369E+09 | 0.00 | 97135446.42 | 0.261271E+09 | 0.00 | 0.232997E+11 | 0.00 | 1.13 |
September | 0.295018E+10 | 0.148161E+09 | 0.00 | 84204764.40 | 63035141.91 | 0.00 | 0.259544E+11 | 0.00 | 0.88 |
October | 0.360231E+10 | 0.00 | 0.00 | 88881250.70 | 0.00 | 0.00 | 0.500582E+11 | 0.00 | 0.74 |
November | 0.342440E+10 | 0.00 | 0.00 | 90832645.40 | 0.00 | 0.00 | 0.521542E+11 | 0.00 | 0.63 |
December | 0.394817E+10 | 0.00 | 0.00 | 88356290.35 | 0.00 | 0.00 | 0.554391E+11 | 0.00 | 0.55 |
Annual Sum or Average | 0.514691E+11 | 0.242238E+10 | 0.00 | 0.999199E+09 | 0.575996E+09 | 0.00 | 0.473859E+12 | 0.00 | 0.76 |
Minimum of Months | 0.263822E+10 | 0.00 | 0.00 | 67988862.66 | 0.00 | 0.00 | 0.135752E+11 | 0.00 | 0.47 |
Maximum of Months | 0.978747E+10 | 0.762663E+09 | 0.00 | 97135446.42 | 0.261271E+09 | 0.00 | 0.554391E+11 | 0.00 | 1.13 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_MID
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.178822E+12 | 0.00 | 0.00 | 0.246362E+09 | 0.00 | 0.00 | 0.192304E+12 | 0.00 | 0.36 |
February | 0.200513E+12 | 0.00 | 0.00 | 0.183294E+09 | 0.00 | 0.414238E+09 | 0.141623E+12 | 0.00 | 0.35 |
March | 0.147084E+12 | 0.00 | 0.00 | 0.374422E+09 | 0.00 | 6558299.67 | 0.243277E+12 | 0.00 | 0.51 |
April | 0.958855E+11 | 0.00 | 0.00 | 0.327623E+09 | 0.00 | 0.00 | 0.234281E+12 | 0.00 | 0.50 |
May | 0.244192E+11 | 97329334.01 | 0.00 | 0.636114E+09 | 28722199.99 | 0.00 | 0.319469E+12 | 0.00 | 0.75 |
June | 0.230565E+11 | 0.800043E+10 | 0.00 | 0.578179E+09 | 0.800213E+09 | 0.00 | 0.132308E+12 | 0.00 | 0.67 |
July | 0.198104E+11 | 0.777467E+10 | 0.00 | 0.571810E+09 | 0.150361E+10 | 0.00 | 0.107436E+12 | 0.00 | 0.63 |
August | 0.216109E+11 | 0.779375E+10 | 0.00 | 0.704302E+09 | 0.863809E+09 | 0.00 | 0.166383E+12 | 0.00 | 0.70 |
September | 0.198644E+11 | 0.157941E+10 | 0.00 | 0.666953E+09 | 0.446256E+09 | 0.00 | 0.202581E+12 | 0.00 | 0.71 |
October | 0.867490E+11 | 0.00 | 0.00 | 0.481760E+09 | 0.00 | 0.00 | 0.291314E+12 | 0.00 | 0.54 |
November | 0.138363E+12 | 0.00 | 0.00 | 0.314031E+09 | 0.00 | 0.00 | 0.226003E+12 | 0.00 | 0.42 |
December | 0.244063E+12 | 0.00 | 0.00 | 0.153474E+09 | 0.00 | 0.953345E+09 | 0.136749E+12 | 0.00 | 0.35 |
Annual Sum or Average | 0.120024E+13 | 0.252456E+11 | 0.00 | 0.523832E+10 | 0.364260E+10 | 0.137414E+10 | 0.239373E+13 | 0.00 | 0.54 |
Minimum of Months | 0.198104E+11 | 0.00 | 0.00 | 0.153474E+09 | 0.00 | 0.00 | 0.107436E+12 | 0.00 | 0.35 |
Maximum of Months | 0.244063E+12 | 0.800043E+10 | 0.00 | 0.704302E+09 | 0.150361E+10 | 0.953345E+09 | 0.319469E+12 | 0.00 | 0.75 |
Report: MechanicalVentilationLoadsMonthly
For: CORE_TOP
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.247241E+11 | 0.00 | 0.00 | 4380316.94 | 0.00 | 0.194483E+10 | 0.419728E+10 | 0.00 | 0.32 |
February | 0.224243E+11 | 0.00 | 0.00 | 3542384.34 | 0.00 | 0.225890E+10 | 0.394224E+10 | 0.00 | 0.30 |
March | 0.200157E+11 | 0.00 | 0.00 | 18297678.29 | 0.00 | 0.563635E+09 | 0.130922E+11 | 0.00 | 0.46 |
April | 0.145056E+11 | 0.00 | 0.00 | 19850820.67 | 0.00 | 0.711298E+09 | 0.148914E+11 | 0.00 | 0.47 |
May | 0.609703E+10 | 468115.39 | 0.00 | 46513663.02 | 3361945.23 | 0.114078E+09 | 0.245757E+11 | 0.00 | 0.70 |
June | 0.219466E+10 | 0.561573E+09 | 0.00 | 62632666.10 | 53122902.92 | 0.00 | 0.127444E+11 | 0.00 | 0.70 |
July | 0.166799E+10 | 0.498642E+09 | 0.00 | 62438514.01 | 0.106637E+09 | 0.00 | 0.103427E+11 | 0.00 | 0.65 |
August | 0.206234E+10 | 0.580252E+09 | 0.00 | 71856429.21 | 62895690.14 | 0.00 | 0.153273E+11 | 0.00 | 0.69 |
September | 0.315532E+10 | 0.110777E+09 | 0.00 | 57654395.03 | 38525535.26 | 0.00 | 0.158510E+11 | 0.00 | 0.67 |
October | 0.160601E+11 | 0.00 | 0.00 | 19839902.66 | 0.00 | 0.102909E+10 | 0.131919E+11 | 0.00 | 0.47 |
November | 0.218221E+11 | 0.00 | 0.00 | 8145632.14 | 0.00 | 0.119032E+10 | 0.654501E+10 | 0.00 | 0.36 |
December | 0.251040E+11 | 0.00 | 0.00 | 1877269.01 | 0.00 | 0.440937E+10 | 0.185255E+10 | 0.00 | 0.31 |
Annual Sum or Average | 0.159833E+12 | 0.175171E+10 | 0.00 | 0.377030E+09 | 0.264543E+09 | 0.122215E+11 | 0.136554E+12 | 0.00 | 0.51 |
Minimum of Months | 0.166799E+10 | 0.00 | 0.00 | 1877269.01 | 0.00 | 0.00 | 0.185255E+10 | 0.00 | 0.30 |
Maximum of Months | 0.251040E+11 | 0.580252E+09 | 0.00 | 71856429.21 | 0.106637E+09 | 0.440937E+10 | 0.245757E+11 | 0.00 | 0.70 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.347589E+10 | 0.00 | 0.00 | 494569.07 | 0.00 | 0.357546E+09 | 0.457748E+09 | 0.00 | 0.32 |
February | 0.327412E+10 | 0.00 | 0.00 | 464695.31 | 0.00 | 0.278339E+09 | 0.484967E+09 | 0.00 | 0.32 |
March | 0.279289E+10 | 0.00 | 0.00 | 2986904.34 | 0.00 | 5505921.76 | 0.203408E+10 | 0.00 | 0.52 |
April | 0.185517E+10 | 0.00 | 0.00 | 4719120.55 | 0.00 | 326300.45 | 0.315892E+10 | 0.00 | 0.64 |
May | 0.909922E+09 | 1798421.05 | 0.00 | 8331042.38 | 102105.48 | 0.00 | 0.408427E+10 | 0.00 | 0.92 |
June | 0.754335E+09 | 0.158966E+09 | 0.00 | 10806042.84 | 7977262.13 | 0.00 | 0.224163E+10 | 0.00 | 1.07 |
July | 0.852437E+09 | 0.168399E+09 | 0.00 | 10544068.94 | 22491972.70 | 0.00 | 0.183424E+10 | 0.00 | 1.06 |
August | 0.138662E+10 | 0.145296E+09 | 0.00 | 12995432.56 | 32818132.31 | 0.00 | 0.279821E+10 | 0.00 | 1.22 |
September | 0.787114E+09 | 30959930.50 | 0.00 | 8747160.24 | 7917830.36 | 0.00 | 0.230917E+10 | 0.00 | 0.84 |
October | 0.241472E+10 | 0.00 | 0.00 | 3317619.81 | 0.00 | 0.108170E+09 | 0.198385E+10 | 0.00 | 0.53 |
November | 0.308205E+10 | 0.00 | 0.00 | 1631560.38 | 0.00 | 0.151110E+09 | 0.113768E+10 | 0.00 | 0.41 |
December | 0.305812E+10 | 0.00 | 0.00 | 728178.52 | 0.00 | 0.849003E+09 | 0.692454E+09 | 0.00 | 0.33 |
Annual Sum or Average | 0.246434E+11 | 0.505419E+09 | 0.00 | 65766394.93 | 71307302.97 | 0.175000E+10 | 0.232172E+11 | 0.00 | 0.68 |
Minimum of Months | 0.754335E+09 | 0.00 | 0.00 | 464695.31 | 0.00 | 0.00 | 0.457748E+09 | 0.00 | 0.32 |
Maximum of Months | 0.347589E+10 | 0.168399E+09 | 0.00 | 12995432.56 | 32818132.31 | 0.849003E+09 | 0.408427E+10 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.329874E+10 | 0.00 | 0.00 | 1813460.84 | 0.00 | 0.322642E+09 | 0.119527E+10 | 0.00 | 0.57 |
February | 0.256899E+10 | 0.00 | 0.00 | 2938677.32 | 0.00 | 0.443522E+09 | 0.182000E+10 | 0.00 | 0.60 |
March | 0.257958E+10 | 0.00 | 0.00 | 5960548.76 | 0.00 | 33652705.55 | 0.348285E+10 | 0.00 | 0.98 |
April | 0.205340E+10 | 0.00 | 0.00 | 5821981.05 | 0.00 | 38100958.27 | 0.369265E+10 | 0.00 | 1.08 |
May | 0.966805E+09 | 1361150.83 | 0.00 | 9102516.88 | 108100.50 | 0.00 | 0.454161E+10 | 0.00 | 1.50 |
June | 0.800816E+09 | 0.114711E+09 | 0.00 | 11511859.96 | 8293469.65 | 0.00 | 0.263132E+10 | 0.00 | 1.75 |
July | 0.900171E+09 | 0.126475E+09 | 0.00 | 10434173.40 | 22200336.57 | 0.00 | 0.171868E+10 | 0.00 | 1.55 |
August | 0.155361E+10 | 0.102315E+09 | 0.00 | 12270862.93 | 34745014.17 | 0.00 | 0.298039E+10 | 0.00 | 1.91 |
September | 0.794370E+09 | 26207867.93 | 0.00 | 10180766.22 | 8382717.37 | 0.00 | 0.293062E+10 | 0.00 | 1.49 |
October | 0.231335E+10 | 0.00 | 0.00 | 5168464.45 | 0.00 | 0.198172E+09 | 0.280027E+10 | 0.00 | 0.94 |
November | 0.298990E+10 | 0.00 | 0.00 | 2695909.89 | 0.00 | 0.240796E+09 | 0.162923E+10 | 0.00 | 0.68 |
December | 0.308514E+10 | 0.00 | 0.00 | 1184568.32 | 0.00 | 0.991528E+09 | 0.876564E+09 | 0.00 | 0.55 |
Annual Sum or Average | 0.239049E+11 | 0.371071E+09 | 0.00 | 79083790.01 | 73729638.27 | 0.226841E+10 | 0.302995E+11 | 0.00 | 1.14 |
Minimum of Months | 0.794370E+09 | 0.00 | 0.00 | 1184568.32 | 0.00 | 0.00 | 0.876564E+09 | 0.00 | 0.55 |
Maximum of Months | 0.329874E+10 | 0.126475E+09 | 0.00 | 12270862.93 | 34745014.17 | 0.991528E+09 | 0.454161E+10 | 0.00 | 1.91 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.220111E+10 | 0.00 | 0.00 | 13391376.33 | 0.00 | 0.391937E+09 | 0.798108E+10 | 0.00 | 0.95 |
February | 0.194281E+10 | 0.00 | 0.00 | 13261477.07 | 0.00 | 0.499989E+09 | 0.793125E+10 | 0.00 | 0.92 |
March | 0.256241E+10 | 0.00 | 0.00 | 13182254.45 | 0.00 | 64809571.04 | 0.751497E+10 | 0.00 | 1.21 |
April | 0.222974E+10 | 0.00 | 0.00 | 8449250.15 | 0.00 | 99265229.63 | 0.537818E+10 | 0.00 | 1.05 |
May | 0.137142E+10 | 2519041.49 | 0.00 | 9885692.59 | 123622.75 | 407539.56 | 0.472086E+10 | 0.00 | 1.15 |
June | 0.977698E+09 | 0.173730E+09 | 0.00 | 11309766.45 | 9658355.81 | 0.00 | 0.211289E+10 | 0.00 | 1.14 |
July | 0.104686E+10 | 0.211186E+09 | 0.00 | 11334284.38 | 20082778.86 | 0.00 | 0.180800E+10 | 0.00 | 1.16 |
August | 0.165846E+10 | 0.205357E+09 | 0.00 | 18146756.18 | 39734083.42 | 0.00 | 0.340992E+10 | 0.00 | 1.54 |
September | 0.850445E+09 | 59303363.70 | 0.00 | 17320036.65 | 9586399.64 | 0.00 | 0.404821E+10 | 0.00 | 1.44 |
October | 0.178983E+10 | 0.00 | 0.00 | 19700898.47 | 0.00 | 0.319107E+09 | 0.826094E+10 | 0.00 | 1.41 |
November | 0.209972E+10 | 0.00 | 0.00 | 17896001.76 | 0.00 | 0.208076E+09 | 0.869712E+10 | 0.00 | 1.16 |
December | 0.233863E+10 | 0.00 | 0.00 | 13375955.39 | 0.00 | 0.776177E+09 | 0.712147E+10 | 0.00 | 0.91 |
Annual Sum or Average | 0.210691E+11 | 0.652095E+09 | 0.00 | 0.167254E+09 | 79185240.49 | 0.235977E+10 | 0.689849E+11 | 0.00 | 1.17 |
Minimum of Months | 0.850445E+09 | 0.00 | 0.00 | 8449250.15 | 0.00 | 0.00 | 0.180800E+10 | 0.00 | 0.91 |
Maximum of Months | 0.256241E+10 | 0.211186E+09 | 0.00 | 19700898.47 | 39734083.42 | 0.776177E+09 | 0.869712E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_BOT_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.405698E+10 | 0.00 | 0.00 | 2903450.10 | 0.00 | 62585081.39 | 0.236419E+10 | 0.00 | 0.81 |
February | 0.321316E+10 | 0.00 | 0.00 | 4633302.99 | 0.00 | 13994165.55 | 0.342833E+10 | 0.00 | 0.85 |
March | 0.185860E+10 | 0.00 | 0.00 | 10994059.40 | 0.00 | 0.00 | 0.663620E+10 | 0.00 | 1.51 |
April | 0.765208E+09 | 0.00 | 0.00 | 13946295.48 | 0.00 | 0.00 | 0.844555E+10 | 0.00 | 1.87 |
May | 0.832368E+09 | 2893080.74 | 0.00 | 11114213.13 | 139057.78 | 0.00 | 0.543669E+10 | 0.00 | 1.81 |
June | 0.707693E+09 | 0.229652E+09 | 0.00 | 14348482.31 | 2616659.61 | 0.00 | 0.279047E+10 | 0.00 | 1.95 |
July | 0.784965E+09 | 0.240239E+09 | 0.00 | 14074419.21 | 15336942.79 | 0.00 | 0.256744E+10 | 0.00 | 2.02 |
August | 0.569460E+09 | 0.288525E+09 | 0.00 | 28484776.36 | 5619182.63 | 0.00 | 0.576888E+10 | 0.00 | 2.87 |
September | 0.773047E+09 | 46138325.64 | 0.00 | 12098715.54 | 6747844.48 | 0.00 | 0.319744E+10 | 0.00 | 1.68 |
October | 0.214309E+10 | 0.00 | 0.00 | 10059316.48 | 0.00 | 513837.04 | 0.515795E+10 | 0.00 | 1.42 |
November | 0.233530E+10 | 0.00 | 0.00 | 7689217.32 | 0.00 | 703705.14 | 0.491762E+10 | 0.00 | 1.11 |
December | 0.262556E+10 | 0.00 | 0.00 | 7873733.91 | 0.00 | 22325425.41 | 0.512870E+10 | 0.00 | 0.96 |
Annual Sum or Average | 0.206654E+11 | 0.807447E+09 | 0.00 | 0.138220E+09 | 30459687.30 | 0.100122E+09 | 0.558395E+11 | 0.00 | 1.58 |
Minimum of Months | 0.569460E+09 | 0.00 | 0.00 | 2903450.10 | 0.00 | 0.00 | 0.236419E+10 | 0.00 | 0.81 |
Maximum of Months | 0.405698E+10 | 0.288525E+09 | 0.00 | 28484776.36 | 15336942.79 | 62585081.39 | 0.844555E+10 | 0.00 | 2.87 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.219639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214060E+11 | 0.00 | 0.00 | 0.33 |
February | 0.185382E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227546E+11 | 0.00 | 0.00 | 0.32 |
March | 0.250289E+11 | 0.00 | 0.00 | 6619685.06 | 0.00 | 0.131203E+11 | 0.394886E+10 | 0.00 | 0.42 |
April | 0.230627E+11 | 0.00 | 0.00 | 9822308.24 | 0.00 | 0.604758E+10 | 0.635815E+10 | 0.00 | 0.42 |
May | 0.134971E+11 | 18417665.45 | 0.00 | 52347943.50 | 3604917.19 | 0.460263E+09 | 0.231533E+11 | 0.00 | 0.70 |
June | 0.354514E+10 | 0.190045E+10 | 0.00 | 85949999.39 | 0.100435E+09 | 0.00 | 0.176056E+11 | 0.00 | 0.86 |
July | 0.305120E+10 | 0.198922E+10 | 0.00 | 83070886.22 | 0.188717E+09 | 0.00 | 0.140047E+11 | 0.00 | 0.79 |
August | 0.455784E+10 | 0.165881E+10 | 0.00 | 85558718.52 | 0.109644E+09 | 0.00 | 0.176818E+11 | 0.00 | 0.75 |
September | 0.902595E+10 | 0.345771E+09 | 0.00 | 61300569.21 | 56009444.01 | 0.201444E+09 | 0.141369E+11 | 0.00 | 0.66 |
October | 0.252721E+11 | 0.00 | 0.00 | 7530238.41 | 0.00 | 0.838961E+10 | 0.415806E+10 | 0.00 | 0.42 |
November | 0.233546E+11 | 0.00 | 0.00 | 1602405.23 | 0.00 | 0.161391E+11 | 0.114103E+10 | 0.00 | 0.35 |
December | 0.147229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355320E+11 | 0.00 | 0.00 | 0.34 |
Annual Sum or Average | 0.185621E+12 | 0.591266E+10 | 0.00 | 0.393803E+09 | 0.458410E+09 | 0.124051E+12 | 0.102188E+12 | 0.00 | 0.53 |
Minimum of Months | 0.305120E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.32 |
Maximum of Months | 0.252721E+11 | 0.198922E+10 | 0.00 | 85949999.39 | 0.188717E+09 | 0.355320E+11 | 0.231533E+11 | 0.00 | 0.86 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.281408E+11 | 0.00 | 0.00 | 3844635.76 | 0.00 | 0.175206E+11 | 0.335632E+10 | 0.00 | 0.58 |
February | 0.240012E+11 | 0.00 | 0.00 | 10223942.54 | 0.00 | 0.170995E+11 | 0.633971E+10 | 0.00 | 0.59 |
March | 0.230885E+11 | 0.00 | 0.00 | 37207262.12 | 0.00 | 0.104926E+11 | 0.222664E+11 | 0.00 | 0.89 |
April | 0.199852E+11 | 0.00 | 0.00 | 37207536.15 | 0.00 | 0.508022E+10 | 0.237256E+11 | 0.00 | 0.92 |
May | 0.115950E+11 | 17048237.39 | 0.00 | 75773213.58 | 4098453.47 | 0.264083E+09 | 0.363396E+11 | 0.00 | 1.35 |
June | 0.384692E+10 | 0.150291E+10 | 0.00 | 0.112049E+09 | 0.110097E+09 | 0.00 | 0.259726E+11 | 0.00 | 1.65 |
July | 0.339754E+10 | 0.178034E+10 | 0.00 | 0.103864E+09 | 0.159280E+09 | 0.00 | 0.167764E+11 | 0.00 | 1.37 |
August | 0.455173E+10 | 0.154038E+10 | 0.00 | 0.122359E+09 | 0.123537E+09 | 0.00 | 0.301428E+11 | 0.00 | 1.60 |
September | 0.852781E+10 | 0.350633E+09 | 0.00 | 90413458.70 | 63658889.74 | 84868596.25 | 0.244464E+11 | 0.00 | 1.38 |
October | 0.209312E+11 | 0.00 | 0.00 | 31856807.96 | 0.00 | 0.920143E+10 | 0.180060E+11 | 0.00 | 0.85 |
November | 0.268575E+11 | 0.00 | 0.00 | 10129022.27 | 0.00 | 0.135041E+11 | 0.644164E+10 | 0.00 | 0.64 |
December | 0.219592E+11 | 0.00 | 0.00 | 391013.22 | 0.00 | 0.298538E+11 | 0.606533E+09 | 0.00 | 0.58 |
Annual Sum or Average | 0.196883E+12 | 0.519130E+10 | 0.00 | 0.635319E+09 | 0.460671E+09 | 0.103101E+12 | 0.214420E+12 | 0.00 | 1.03 |
Minimum of Months | 0.339754E+10 | 0.00 | 0.00 | 391013.22 | 0.00 | 0.00 | 0.606533E+09 | 0.00 | 0.58 |
Maximum of Months | 0.281408E+11 | 0.178034E+10 | 0.00 | 0.122359E+09 | 0.159280E+09 | 0.298538E+11 | 0.363396E+11 | 0.00 | 1.65 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.214453E+11 | 0.00 | 0.00 | 0.134011E+09 | 0.00 | 0.734512E+10 | 0.743420E+11 | 0.00 | 0.94 |
February | 0.167701E+11 | 0.00 | 0.00 | 0.123999E+09 | 0.00 | 0.110920E+11 | 0.714915E+11 | 0.00 | 0.90 |
March | 0.189570E+11 | 0.00 | 0.00 | 0.115838E+09 | 0.00 | 0.981710E+10 | 0.634688E+11 | 0.00 | 1.11 |
April | 0.207981E+11 | 0.00 | 0.00 | 56660474.54 | 0.00 | 0.516595E+10 | 0.348872E+11 | 0.00 | 0.83 |
May | 0.140707E+11 | 30612672.95 | 0.00 | 80801843.84 | 4351109.35 | 0.549347E+09 | 0.366312E+11 | 0.00 | 0.99 |
June | 0.543197E+10 | 0.212599E+10 | 0.00 | 92627809.26 | 0.120856E+09 | 0.00 | 0.173173E+11 | 0.00 | 0.95 |
July | 0.433459E+10 | 0.256421E+10 | 0.00 | 93724090.97 | 0.176335E+09 | 0.00 | 0.145689E+11 | 0.00 | 0.91 |
August | 0.499139E+10 | 0.277241E+10 | 0.00 | 0.144160E+09 | 0.119671E+09 | 0.00 | 0.263731E+11 | 0.00 | 1.11 |
September | 0.722482E+10 | 0.802517E+09 | 0.00 | 0.163138E+09 | 67583246.24 | 0.111888E+09 | 0.353585E+11 | 0.00 | 1.34 |
October | 0.140207E+11 | 0.00 | 0.00 | 0.195930E+09 | 0.00 | 0.858919E+10 | 0.738807E+11 | 0.00 | 1.34 |
November | 0.187599E+11 | 0.00 | 0.00 | 0.172953E+09 | 0.00 | 0.655940E+10 | 0.763468E+11 | 0.00 | 1.09 |
December | 0.217675E+11 | 0.00 | 0.00 | 0.104110E+09 | 0.00 | 0.172524E+11 | 0.507178E+11 | 0.00 | 0.81 |
Annual Sum or Average | 0.168572E+12 | 0.829574E+10 | 0.00 | 0.147795E+10 | 0.488796E+09 | 0.664824E+11 | 0.575384E+12 | 0.00 | 1.03 |
Minimum of Months | 0.433459E+10 | 0.00 | 0.00 | 56660474.54 | 0.00 | 0.00 | 0.145689E+11 | 0.00 | 0.81 |
Maximum of Months | 0.217675E+11 | 0.277241E+10 | 0.00 | 0.195930E+09 | 0.176335E+09 | 0.172524E+11 | 0.763468E+11 | 0.00 | 1.34 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_MID_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.334334E+11 | 0.00 | 0.00 | 9897199.27 | 0.00 | 0.142340E+11 | 0.733185E+10 | 0.00 | 0.67 |
February | 0.289646E+11 | 0.00 | 0.00 | 12016951.69 | 0.00 | 0.154084E+11 | 0.890075E+10 | 0.00 | 0.67 |
March | 0.304917E+11 | 0.00 | 0.00 | 33094881.40 | 0.00 | 0.104132E+11 | 0.190927E+11 | 0.00 | 1.02 |
April | 0.264630E+11 | 0.00 | 0.00 | 31269906.72 | 0.00 | 0.430605E+10 | 0.192167E+11 | 0.00 | 0.97 |
May | 0.154119E+11 | 29307083.67 | 0.00 | 65031747.40 | 4476622.12 | 0.386282E+09 | 0.294314E+11 | 0.00 | 1.34 |
June | 0.514666E+10 | 0.258452E+10 | 0.00 | 85224846.75 | 38424391.96 | 0.00 | 0.154144E+11 | 0.00 | 1.35 |
July | 0.448120E+10 | 0.237601E+10 | 0.00 | 71467881.13 | 0.145795E+09 | 0.00 | 0.123092E+11 | 0.00 | 1.21 |
August | 0.545298E+10 | 0.236657E+10 | 0.00 | 0.104290E+09 | 0.108960E+09 | 0.00 | 0.178006E+11 | 0.00 | 1.29 |
September | 0.105628E+11 | 0.463822E+09 | 0.00 | 75268364.57 | 49771937.28 | 0.248022E+09 | 0.173781E+11 | 0.00 | 1.24 |
October | 0.274633E+11 | 0.00 | 0.00 | 38876221.05 | 0.00 | 0.855668E+10 | 0.178721E+11 | 0.00 | 1.01 |
November | 0.327534E+11 | 0.00 | 0.00 | 14082691.03 | 0.00 | 0.109240E+11 | 0.902566E+10 | 0.00 | 0.75 |
December | 0.274043E+11 | 0.00 | 0.00 | 4927793.64 | 0.00 | 0.267890E+11 | 0.360978E+10 | 0.00 | 0.65 |
Annual Sum or Average | 0.248029E+12 | 0.782023E+10 | 0.00 | 0.545449E+09 | 0.347428E+09 | 0.912655E+11 | 0.177383E+12 | 0.00 | 1.01 |
Minimum of Months | 0.448120E+10 | 0.00 | 0.00 | 4927793.64 | 0.00 | 0.00 | 0.360978E+10 | 0.00 | 0.65 |
Maximum of Months | 0.334334E+11 | 0.258452E+10 | 0.00 | 0.104290E+09 | 0.145795E+09 | 0.267890E+11 | 0.294314E+11 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_3
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.110346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.319814E+10 | 0.00 | 0.00 | 0.34 |
February | 0.954856E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304838E+10 | 0.00 | 0.00 | 0.33 |
March | 0.181184E+10 | 0.00 | 0.00 | 457927.85 | 0.00 | 0.195882E+10 | 0.307542E+09 | 0.00 | 0.42 |
April | 0.173524E+10 | 0.00 | 0.00 | 833485.16 | 0.00 | 0.126945E+10 | 0.560189E+09 | 0.00 | 0.43 |
May | 0.141696E+10 | 136462.86 | 0.00 | 4413558.86 | 387924.38 | 0.115011E+09 | 0.193638E+10 | 0.00 | 0.67 |
June | 0.367404E+09 | 0.126268E+09 | 0.00 | 9650518.05 | 6544172.63 | 0.00 | 0.172813E+10 | 0.00 | 0.89 |
July | 0.318950E+09 | 0.120384E+09 | 0.00 | 9338292.80 | 11782867.45 | 0.00 | 0.134041E+10 | 0.00 | 0.81 |
August | 0.560122E+09 | 0.113955E+09 | 0.00 | 9032158.20 | 7934817.65 | 0.00 | 0.159177E+10 | 0.00 | 0.75 |
September | 0.899333E+09 | 22692300.13 | 0.00 | 6006913.36 | 4830381.11 | 61556296.00 | 0.119991E+10 | 0.00 | 0.65 |
October | 0.203005E+10 | 0.00 | 0.00 | 439730.78 | 0.00 | 0.148599E+10 | 0.197473E+09 | 0.00 | 0.43 |
November | 0.123747E+10 | 0.00 | 0.00 | 57238.32 | 0.00 | 0.260552E+10 | 60807378.81 | 0.00 | 0.36 |
December | 0.732714E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.454415E+10 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.131684E+11 | 0.383435E+09 | 0.00 | 40229823.38 | 31480163.21 | 0.182870E+11 | 0.892262E+10 | 0.00 | 0.54 |
Minimum of Months | 0.318950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 |
Maximum of Months | 0.203005E+10 | 0.126268E+09 | 0.00 | 9650518.05 | 11782867.45 | 0.454415E+10 | 0.193638E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_2
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.199255E+10 | 0.00 | 0.00 | 87018.97 | 0.00 | 0.220288E+10 | 0.127322E+09 | 0.00 | 0.55 |
February | 0.189873E+10 | 0.00 | 0.00 | 311046.64 | 0.00 | 0.187939E+10 | 0.253197E+09 | 0.00 | 0.53 |
March | 0.182997E+10 | 0.00 | 0.00 | 2741700.81 | 0.00 | 0.132985E+10 | 0.174604E+10 | 0.00 | 0.82 |
April | 0.151852E+10 | 0.00 | 0.00 | 3053674.79 | 0.00 | 0.974548E+09 | 0.208361E+10 | 0.00 | 0.89 |
May | 0.112817E+10 | 270691.72 | 0.00 | 6782883.53 | 296214.75 | 62488082.25 | 0.326072E+10 | 0.00 | 1.31 |
June | 0.330939E+09 | 0.100081E+09 | 0.00 | 12700952.67 | 6998989.42 | 0.00 | 0.264613E+10 | 0.00 | 1.73 |
July | 0.300624E+09 | 0.107538E+09 | 0.00 | 11780813.22 | 9877129.75 | 0.00 | 0.167096E+10 | 0.00 | 1.40 |
August | 0.437057E+09 | 0.105785E+09 | 0.00 | 13322364.17 | 8825366.98 | 0.00 | 0.296807E+10 | 0.00 | 1.61 |
September | 0.749981E+09 | 22935969.37 | 0.00 | 9056192.06 | 5372509.85 | 38785873.99 | 0.222595E+10 | 0.00 | 1.36 |
October | 0.166427E+10 | 0.00 | 0.00 | 2095956.28 | 0.00 | 0.123799E+10 | 0.125740E+10 | 0.00 | 0.79 |
November | 0.182500E+10 | 0.00 | 0.00 | 459964.96 | 0.00 | 0.186130E+10 | 0.372051E+09 | 0.00 | 0.59 |
December | 0.150889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308815E+10 | 0.00 | 0.00 | 0.54 |
Annual Sum or Average | 0.151847E+11 | 0.336610E+09 | 0.00 | 62392568.11 | 31370210.75 | 0.126754E+11 | 0.186115E+11 | 0.00 | 1.01 |
Minimum of Months | 0.300624E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.199255E+10 | 0.107538E+09 | 0.00 | 13322364.17 | 9877129.75 | 0.308815E+10 | 0.326072E+10 | 0.00 | 1.73 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_1
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.168257E+10 | 0.00 | 0.00 | 8534411.24 | 0.00 | 0.152575E+10 | 0.550788E+10 | 0.00 | 0.84 |
February | 0.151577E+10 | 0.00 | 0.00 | 9018382.99 | 0.00 | 0.140687E+10 | 0.571344E+10 | 0.00 | 0.81 |
March | 0.164296E+10 | 0.00 | 0.00 | 9383056.59 | 0.00 | 0.139229E+10 | 0.577414E+10 | 0.00 | 1.08 |
April | 0.166582E+10 | 0.00 | 0.00 | 4908898.21 | 0.00 | 0.118883E+10 | 0.331425E+10 | 0.00 | 0.82 |
May | 0.157458E+10 | 388298.73 | 0.00 | 7130345.90 | 344725.97 | 0.133641E+09 | 0.329948E+10 | 0.00 | 0.98 |
June | 0.665147E+09 | 0.136736E+09 | 0.00 | 10664171.25 | 8470672.43 | 0.00 | 0.176380E+10 | 0.00 | 1.02 |
July | 0.497728E+09 | 0.148069E+09 | 0.00 | 10827369.83 | 11633441.61 | 0.00 | 0.146084E+10 | 0.00 | 0.95 |
August | 0.648559E+09 | 0.178486E+09 | 0.00 | 16324343.39 | 10270701.12 | 0.00 | 0.258292E+10 | 0.00 | 1.14 |
September | 0.727104E+09 | 49294029.11 | 0.00 | 17642046.24 | 6204213.93 | 55422023.30 | 0.343017E+10 | 0.00 | 1.35 |
October | 0.120195E+10 | 0.00 | 0.00 | 16539124.35 | 0.00 | 0.129315E+10 | 0.664960E+10 | 0.00 | 1.31 |
November | 0.146312E+10 | 0.00 | 0.00 | 11731405.56 | 0.00 | 0.139463E+10 | 0.582031E+10 | 0.00 | 0.98 |
December | 0.186209E+10 | 0.00 | 0.00 | 6637594.83 | 0.00 | 0.240354E+10 | 0.350417E+10 | 0.00 | 0.72 |
Annual Sum or Average | 0.151474E+11 | 0.512973E+09 | 0.00 | 0.129341E+09 | 36923755.06 | 0.107941E+11 | 0.488210E+11 | 0.00 | 1.00 |
Minimum of Months | 0.497728E+09 | 0.00 | 0.00 | 4908898.21 | 0.00 | 0.00 | 0.146084E+10 | 0.00 | 0.72 |
Maximum of Months | 0.186209E+10 | 0.178486E+09 | 0.00 | 17642046.24 | 11633441.61 | 0.240354E+10 | 0.664960E+10 | 0.00 | 1.35 |
Report: MechanicalVentilationLoadsMonthly
For: PERIMETER_TOP_ZN_4
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.225260E+10 | 0.00 | 0.00 | 646030.55 | 0.00 | 0.233580E+10 | 0.522651E+09 | 0.00 | 0.66 |
February | 0.209755E+10 | 0.00 | 0.00 | 929771.20 | 0.00 | 0.208144E+10 | 0.718678E+09 | 0.00 | 0.65 |
March | 0.255104E+10 | 0.00 | 0.00 | 2870031.60 | 0.00 | 0.151249E+10 | 0.180866E+10 | 0.00 | 1.02 |
April | 0.224775E+10 | 0.00 | 0.00 | 2847731.46 | 0.00 | 0.933809E+09 | 0.190635E+10 | 0.00 | 1.00 |
May | 0.170265E+10 | 341872.30 | 0.00 | 5895006.14 | 348231.61 | 82980819.35 | 0.272999E+10 | 0.00 | 1.36 |
June | 0.556047E+09 | 0.162834E+09 | 0.00 | 10246764.31 | 2532919.12 | 0.00 | 0.159285E+10 | 0.00 | 1.43 |
July | 0.458408E+09 | 0.137037E+09 | 0.00 | 8555556.17 | 10575229.34 | 0.00 | 0.124745E+10 | 0.00 | 1.26 |
August | 0.677437E+09 | 0.156124E+09 | 0.00 | 11657951.14 | 4383299.55 | 0.00 | 0.167205E+10 | 0.00 | 1.31 |
September | 0.105814E+10 | 30702043.08 | 0.00 | 8056034.93 | 4114164.35 | 51581496.20 | 0.166196E+10 | 0.00 | 1.28 |
October | 0.232447E+10 | 0.00 | 0.00 | 3282076.21 | 0.00 | 0.127338E+10 | 0.160249E+10 | 0.00 | 1.03 |
November | 0.218375E+10 | 0.00 | 0.00 | 1035318.52 | 0.00 | 0.197770E+10 | 0.719196E+09 | 0.00 | 0.73 |
December | 0.182027E+10 | 0.00 | 0.00 | 311342.87 | 0.00 | 0.317386E+10 | 0.237550E+09 | 0.00 | 0.63 |
Annual Sum or Average | 0.199301E+11 | 0.487038E+09 | 0.00 | 56333615.08 | 21953843.97 | 0.134230E+11 | 0.164199E+11 | 0.00 | 1.03 |
Minimum of Months | 0.458408E+09 | 0.00 | 0.00 | 311342.87 | 0.00 | 0.00 | 0.237550E+09 | 0.00 | 0.63 |
Maximum of Months | 0.255104E+10 | 0.162834E+09 | 0.00 | 11657951.14 | 10575229.34 | 0.317386E+10 | 0.272999E+10 | 0.00 | 1.43 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BOT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 3475987.85 | 0.00 | 0.00 | 0.566230E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 8069903.01 | 0.00 | 0.00 | 0.533008E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 14511736.95 | 0.00 | 0.00 | 0.509050E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 17368841.63 | 0.00 | 0.00 | 0.396311E+09 | 0.00 | 0.29 |
May | 0.00 | 158742.58 | 0.00 | 3870771.06 | 0.00 | 0.00 | 0.262723E+09 | 0.00 | 0.29 |
June | 0.00 | 27383020.09 | 0.00 | 5010339.64 | 0.00 | 0.00 | 47055086.37 | 0.00 | 0.30 |
July | 0.00 | 51875404.44 | 0.00 | 5380602.18 | 0.00 | 0.00 | 30702071.77 | 0.00 | 0.28 |
August | 0.00 | 26196675.39 | 0.00 | 12464210.87 | 0.00 | 0.00 | 61770133.85 | 0.00 | 0.30 |
September | 0.00 | 683000.08 | 0.00 | 3767309.72 | 0.00 | 0.00 | 0.165338E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 8439315.32 | 0.00 | 0.00 | 0.427957E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 13215322.32 | 0.00 | 0.00 | 0.499302E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 18303446.59 | 0.00 | 0.00 | 0.597213E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.00 | 0.106297E+09 | 0.00 | 0.113878E+09 | 0.00 | 0.00 | 0.409666E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 3475987.85 | 0.00 | 0.00 | 30702071.77 | 0.00 | 0.28 |
Maximum of Months | 0.00 | 51875404.44 | 0.00 | 18303446.59 | 0.00 | 0.00 | 0.597213E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_MID_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.167506E+09 | 0.00 | 0.00 | 21316998.55 | 0.00 | 0.00 | 0.551243E+10 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 63913943.44 | 0.00 | 0.00 | 0.534650E+10 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 0.126763E+09 | 0.00 | 0.00 | 0.510857E+10 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 0.155521E+09 | 0.00 | 0.00 | 0.398117E+10 | 0.00 | 0.29 |
May | 0.00 | 1427041.01 | 0.00 | 32906502.91 | 0.00 | 0.00 | 0.264036E+10 | 0.00 | 0.29 |
June | 0.00 | 0.270398E+09 | 0.00 | 47454874.32 | 0.00 | 0.00 | 0.473753E+09 | 0.00 | 0.30 |
July | 0.00 | 0.515691E+09 | 0.00 | 51342725.01 | 0.00 | 0.00 | 0.309583E+09 | 0.00 | 0.28 |
August | 0.00 | 0.265539E+09 | 0.00 | 0.114045E+09 | 0.00 | 0.00 | 0.606161E+09 | 0.00 | 0.30 |
September | 0.00 | 6691356.92 | 0.00 | 33132038.88 | 0.00 | 0.00 | 0.166287E+10 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 72212346.77 | 0.00 | 0.00 | 0.429224E+10 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 0.114367E+09 | 0.00 | 0.00 | 0.501009E+10 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 0.156815E+09 | 0.00 | 0.00 | 0.599796E+10 | 0.00 | 0.28 |
Annual Sum or Average | 0.167506E+09 | 0.105975E+10 | 0.00 | 0.989790E+09 | 0.00 | 0.00 | 0.409417E+11 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 21316998.55 | 0.00 | 0.00 | 0.309583E+09 | 0.00 | 0.28 |
Maximum of Months | 0.167506E+09 | 0.515691E+09 | 0.00 | 0.156815E+09 | 0.00 | 0.00 | 0.599796E+10 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_TOP_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.209160E+09 | 0.00 | 0.00 | 1133010.04 | 0.00 | 0.00 | 0.356505E+09 | 0.00 | 0.28 |
February | 0.00 | 0.00 | 0.00 | 5359818.50 | 0.00 | 0.00 | 0.535832E+09 | 0.00 | 0.29 |
March | 0.00 | 0.00 | 0.00 | 11762964.30 | 0.00 | 0.00 | 0.512017E+09 | 0.00 | 0.31 |
April | 0.00 | 0.00 | 0.00 | 14874283.33 | 0.00 | 0.00 | 0.398950E+09 | 0.00 | 0.29 |
May | 7535940.24 | 152166.17 | 0.00 | 2975729.52 | 0.00 | 0.00 | 0.257230E+09 | 0.00 | 0.29 |
June | 0.00 | 27052765.83 | 0.00 | 4767686.64 | 0.00 | 0.00 | 47400420.15 | 0.00 | 0.30 |
July | 0.00 | 51523782.03 | 0.00 | 5147662.18 | 0.00 | 0.00 | 30962324.10 | 0.00 | 0.28 |
August | 0.00 | 26591470.72 | 0.00 | 11356585.36 | 0.00 | 0.00 | 60230493.96 | 0.00 | 0.30 |
September | 3558689.08 | 659774.62 | 0.00 | 3123857.72 | 0.00 | 0.00 | 0.163094E+09 | 0.00 | 0.28 |
October | 0.00 | 0.00 | 0.00 | 6293881.24 | 0.00 | 0.00 | 0.430646E+09 | 0.00 | 0.28 |
November | 0.00 | 0.00 | 0.00 | 10284074.98 | 0.00 | 0.00 | 0.502431E+09 | 0.00 | 0.28 |
December | 0.00 | 0.00 | 0.00 | 14497690.78 | 0.00 | 0.00 | 0.600998E+09 | 0.00 | 0.28 |
Annual Sum or Average | 0.220254E+09 | 0.105980E+09 | 0.00 | 91577244.56 | 0.00 | 0.00 | 0.389629E+10 | 0.00 | 0.29 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 1133010.04 | 0.00 | 0.00 | 30962324.10 | 0.00 | 0.28 |
Maximum of Months | 0.209160E+09 | 51523782.03 | 0.00 | 14874283.33 | 0.00 | 0.00 | 0.600998E+09 | 0.00 | 0.31 |
Report: MechanicalVentilationLoadsMonthly
For: DATACENTER_BASEMENT_ZN_6
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.00 | 0.00 | 0.00 | 0.229748E+09 | 0.00 | 0.00 | 0.153924E+11 | 0.00 | 0.32 |
February | 0.00 | 0.00 | 0.00 | 0.444212E+09 | 0.00 | 0.00 | 0.146548E+11 | 0.00 | 0.32 |
March | 0.00 | 0.00 | 0.00 | 0.742073E+09 | 0.00 | 0.00 | 0.145398E+11 | 0.00 | 0.35 |
April | 0.00 | 0.00 | 0.00 | 0.895710E+09 | 0.00 | 0.00 | 0.124844E+11 | 0.00 | 0.33 |
May | 0.00 | 0.00 | 0.00 | 0.213663E+09 | 0.00 | 0.00 | 0.786969E+10 | 0.00 | 0.33 |
June | 0.00 | 0.285331E+09 | 0.00 | 0.321706E+09 | 0.00 | 0.00 | 0.212583E+10 | 0.00 | 0.34 |
July | 0.00 | 0.665984E+09 | 0.00 | 0.353637E+09 | 0.00 | 0.00 | 0.125643E+10 | 0.00 | 0.31 |
August | 0.00 | 0.00 | 0.00 | 0.981410E+09 | 0.00 | 0.00 | 0.715495E+10 | 0.00 | 0.35 |
September | 0.00 | 0.00 | 0.00 | 0.209961E+09 | 0.00 | 0.00 | 0.566009E+10 | 0.00 | 0.32 |
October | 0.00 | 0.00 | 0.00 | 0.445538E+09 | 0.00 | 0.00 | 0.121316E+11 | 0.00 | 0.32 |
November | 0.00 | 0.00 | 0.00 | 0.681663E+09 | 0.00 | 0.00 | 0.133504E+11 | 0.00 | 0.32 |
December | 0.00 | 0.00 | 0.00 | 0.960823E+09 | 0.00 | 0.00 | 0.177780E+11 | 0.00 | 0.32 |
Annual Sum or Average | 0.00 | 0.951315E+09 | 0.00 | 0.648015E+10 | 0.00 | 0.00 | 0.124398E+12 | 0.00 | 0.33 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.209961E+09 | 0.00 | 0.00 | 0.125643E+10 | 0.00 | 0.31 |
Maximum of Months | 0.00 | 0.665984E+09 | 0.00 | 0.981410E+09 | 0.00 | 0.00 | 0.177780E+11 | 0.00 | 0.35 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 09:04:14
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.464121E+12 | 0.148992E+11 | 0.00 | 0.180010E+13 | 0.683688E+12 |
February | 0.584963E+12 | 0.234154E+11 | 0.00 | 0.157194E+13 | 0.100340E+13 |
March | 0.720243E+12 | 0.253818E+11 | 0.00 | 0.176619E+13 | 0.164649E+13 |
April | 0.774252E+12 | 0.266896E+11 | 0.00 | 0.178879E+13 | 0.200283E+13 |
May | 0.885841E+12 | 0.137322E+11 | 0.00 | 0.181854E+13 | 0.109420E+13 |
June | 0.930841E+12 | 0.620326E+10 | 0.00 | 0.110905E+13 | 0.268968E+13 |
July | 0.881323E+12 | 0.497445E+10 | 0.00 | 0.929193E+12 | 0.315118E+13 |
August | 0.863415E+12 | 0.516872E+10 | 0.00 | 0.986215E+12 | 0.361654E+13 |
September | 0.653832E+12 | 0.889051E+10 | 0.00 | 0.136042E+13 | 0.174756E+13 |
October | 0.575160E+12 | 0.189889E+11 | 0.00 | 0.194186E+13 | 0.130174E+13 |
November | 0.490588E+12 | 0.169906E+11 | 0.00 | 0.184761E+13 | 0.155045E+13 |
December | 0.389357E+12 | 0.312204E+11 | 0.00 | 0.164460E+13 | 0.202917E+13 |
Annual Sum or Average | 0.821393E+13 | 0.196555E+12 | 0.00 | 0.185645E+14 | 0.225169E+14 |
Minimum of Months | 0.389357E+12 | 0.497445E+10 | 0.00 | 0.929193E+12 | 0.683688E+12 |
Maximum of Months | 0.930841E+12 | 0.312204E+11 | 0.00 | 0.194186E+13 | 0.361654E+13 |